www.RenewAire.com • (800) 627-4499 • Fax: (608) 221

Transcription

www.RenewAire.com • (800) 627-4499 • Fax: (608) 221
www.RenewAire.com • (800) 627-4499 • Fax: (608) 221-2824
4510 Helgesen Drive • Madison, Wisconsin 53718 USA
In CANADA
www.MitsubishiElectric.ca • (905) 475-8989 • Fax: (905) 475-5231
In MEXICO, CENTRAL and SOUTH AMERICA and the CARIBBEAN
www.Soler-Palau.com.mx • 52 (222) 2 233 911 • Fax: 52 (222) 2 233 914
Energy Recovery Ventilation: the proven
advantages of heat and humidity transfer
Improves Indoor Air Quality
By providing simultaneous exhaust and fresh air
supply, RenewAire reduces the concentration of
harmful pollutants in indoor air - an absolute must
in schools, offices and smoking environments.
Meets Ventilation Codes for Air Exchange
Indoor Air Quality Problems Solved!
Provides ample ventilation to meet ASHRAE 62 and
the International Mechanical Code that now requires
two to three more air exchanges than in the past.
Controls Excess Moisture
Unlike conventional ventilation or basic heat
exchangers, RenewAire moderates not only the
temperature but the humidity content of incoming
air, limiting humidity swings and associated
biologic growths.
Optimum Cold Weather Performance
Recaptures heat otherwise lost to exhaust air while
controlling humidity extremes. This greatly reduces
the demand on heating equipment - lowering both
initial costs and energy bills. Also protects heating
coils from freeze damage.
Optimum Warm Weather Performance
Pre-cools and dehumidifies the fresh airstream
by transfer of heat and humidity to the exhaust
airstream. This greatly reduces air conditioning
demand - lowering both initial costs and energy
bills. On retrofits, the ventilation rate of exisitng
A/C equipment can be as much as doubled.
Energy Saved = Dollars Saved
RenewAire’s all-weather performance can cut annual
energy bills for heating, cooling and dehumidification
of ventilation air by 50% or more.
Ideal for Hot or Cold Environments
Catalog Page Reference
2
4
5
6
7
8
9
10
12
14
16
18
20
22
24
26
28
30
32
34
Residential
Products
BR70
BR130
EV70
EV130
EV200
EV300
Commercial
Indoor Products
EV450IN
HE1XINH
HE1XINV
HE2XINH
HE2XINV
HE3XINH
HE3XINV
HE4XINH
HE4XINV
HE6XIN
HE8XIN
Commercial
Outdoor Products
36
38
40
42
44
46
48
50
52
54
56
58
60
62
64
66
67
67
EV450RT
HE1XRT
HE1XRTC
HE2XRT
HE2XRTC
HE3XRT
HE3XRTC
HE4XRT
HE4XRTC
HE6XRT
HE8XRT
Applied Products
CA-Series
PA-Series
Commercial Controls
HVI Certified
AHRI Certified
CA/PA Model
Number Guide
68 EV/HE Model
Number Guide
69 Company History
For Technical Support E-mail: [email protected]
To Place an Order E-mail: [email protected]
Why RenewAirE?
INSIDE
OUTSIDE
Fresh Air to Room
Stale Room Air
(exhausted to outside)
Fixed Partition
and Spacer Plates
The Static-Plate Core is the Key!
Since the early 1980’s, RenewAire has pioneered the use of the
patented Lossnay (Registered trademark of Mitsubishi Electric
Corporation) exchange core throughout the Americas. Listed
below are some of the many reasons why this technology has
become the ERV system preferred by leading HVAC professionals
around the world.
(proprietary resin
composite media)
Positive Airstream Separation
Stale Room Air
G5
Outside Air
Enhanced Humidity
Transfer
RenewAire is proud to introduce
the fifth generation energy
recovery ventilation (ERV) core.
• Over 22% more humidity transfer
at AHRI summer conditions
• reduced pressure drop - among
the lowest for static-plate ERV
HE1X = 0.65” @ 750 SCFM
EV450 = 0.6” @ 450 SCFM
In the RenewAire core, fresh air never comes in contact with
exhaust air passages. Hydroscopic resin plates separate the two
airstreams so effectively that AHRI certifies zero exhaust air transfer
at normal, balanced operating conditions. As a result, RenewAire is
perfect for controlled exhaust applications such as toilet areas, as
well as for food service and health care occupancies.
No Condensate or Active Defrost
Direct water vapor transfer, driven by vapor pressure, eliminates
condensation - and frosting - in virtually all applications and climate
zones. No condensation allows for closer plate spacing, resulting
in higher efficiencies and easier installations. It also means no
need for the dampers or electrical defrost elements that reduce
ventilation and rob energy efficiency in competing technologies.
Maintenance - Nothing Could Be Easier
The scheduled maintenance for RenewAire is so simple, it can be
performed by any janitorial staff. No expensive service contracts
are necessary because there is no wheel disassembly and washing,
no seal or belt adjustments and no complex controls to calibrate.
The result is the lowest maintenance cost of any ERV.
The Unbeatable RenewAire Warranty
Try RenewAire’s
ERV Calculation Software
at www.ervcalc.renewaire.com
RenewAire’s remarkable performance
is independently certified by:
An investment in RenewAire is protected by a 10-year core
warranty (2 years on balance of the unit). This commitment twice as long as coverage on the best wheel products - speaks
volumes about RenewAire’s reliability, durability and consistently
high performance.
Award-Winning Service and Support
RenewAire’s team of professionals knows ERV. And our nationwide
network of Sales Reps and quality Distributors are ready to serve
you locally. When you call our support number, you’ll talk to a
knowledgeable factory expert - someone who knows not only our
product line, but the best ways to integrate RenewAire with your
preferred lines of heating and air conditioning equipment.
Residential/Small
Commercial Products
• Commercial quality, ducted equipment
sized to meet required ventilation rates for
homes and small commercial buildings.
• Positive airstream separation that is
critical for smoking environments and
bathroom exhaust.
• Static-plate technology makes total energy
savings practical for small-capacity systems.
• No condensate pan or drain required.
• May be mounted in any orientation.
• Quiet, powerful blowers eliminate the need
for air balancing in most applications.
• Easiest maintenance of any ERV.
• Performance certified by HVI.
• Ten year core warranty.
Central Exhaust - Use EV Series
EA: Exhaust Air to outdoors
OA: Outdoor Air intake
RA: Room Air to be exhausted
FA: Fresh Air to inside
NOTE: ERV Blower may be operated separately from Furnace Blower
General Exhaust - EV Series (or BR Series
mounted to furnace return air which requires
furnace blower interconnect)
(See manual for additional
installation methods.)
NOTE: ERV Blower may be operated separately from Furnace Blower
PTL Control
PBL Control
• primary control for EV70,
EV130, EV200 & EV300
• runs unit an adjustable
amount of time each hour
• two wire, low voltage
connection to ERV
• push button control turns on
unit from bathrooms or other
intermittent exhaust locations
• 20 minute run-time
with one touch
• push 2x for 40 or
3x for 60 minutes
• two wire, low voltage
connection to PTL Control
2
(800) 627-4499
•
Fax: (608) 221-2824
FM Control
• alternate primary control for
EV70, EV130, EV200 & EV300
• wires to EV unit and either
thermostat or furnace control
to turn on furnace blower
• six wire, low voltage
connection
Residential Energy Recovery Ventilators:
BR70, BR130, EV70, EV130, EV200 and EV300
Part I - General
A. Product Specification
1. Energy Recovery Ventilator (ERV) shall be a packaged unit as manufactured
by RenewAire and shall transfer both heat and humidity using static plate
core technology.
B. Quality Assurance
1. The energy recovery ventilator shall be Certified by the Home Ventilating
Institute (HVI) under CSA 439. Both a heating and a cooling test must be run
to demonstrate year round energy recovery.
2. Manufacturer shall be able to provide evidence of independent testing
of the core by Underwriters Laboratory (UL), verifying a maximum flame
spread index (FSI) of 25 and a maximum smoke developed index (SDI) of 50
thereby meeting NFPA 90A and NFPA 90B requirements for materials in a
compartment handling air intended for circulation through a duct system.
The method of test shall be UL Standard 723.
3. Unit shall be Listed under UL 1812 Standard for Ducted Air to Air Heat
Exchangers. The unit must pass commercial flammability requirements and
shall not be labeled “For Residential Use Only”.
4. The ERV core shall be warranted to be free of manufacturing defects and
to retain its functional characteristics, under circumstances of normal use,
for a period of ten years from the date of purchase. The balance-of-unit
shall be warranted to be free of manufacturing defects and to retain its
functional characteristics, under circumstances of normal use, for a period
of two years from the date of purchase.
Part II – Performance
A. Energy Transfer
The ERV shall be capable of transferring both sensible and latent energy
between airstreams. Latent energy transfer shall be accomplished by direct
water vapor transfer from one airstream to the other, without exposing
transfer media in succeeding cycles directly to the exhaust air and then to
the fresh air.
B. Passive Frost Control
The ERV core shall perform without condensing or frosting under normal
operating conditions (defined as outside temperatures above -10°F and
inside relative humidity below 40%). Occasional more extreme conditions
shall not affect the usual function, performance or durability of the core.
No condensate drains will be allowed.
C. Continuous Ventilation
Unit shall have the capacity to operate continuously without the need for bypass,
recirculation, pre-heaters or defrost cycles under normal operating conditions.
D. Positive Airstream Separation
Water vapor transfer shall be through molecular transport by hydroscopic
resin and shall not be accomplished by “porous plate” mechanisms. Exhaust
and fresh airstreams shall travel at all times in separate passages and
airstreams shall not mix.
E. Laminar Flow
Airflow through the ERV core shall be laminar over the products entire
operating airflow range, avoiding deposition of particulates on the interior
of the energy exchange plate material.
Part III – Product
A. Construction
1. The energy recovery component shall be of fixed-plate cross-flow
construction, with no moving parts.
2. No condensate drain pans or drains shall be allowed and unit shall
be capable of operating in both winter and summer conditions without
generating condensate.
3. The unit case shall be constructed of 24-gauge steel, with lapped corners
and zinc plated screw fasteners. The case shall be finished with textured,
powder coat paint.
4. Access doors shall provide easy access to blowers, ERV cores and filters.
Doors shall have an airtight compression seal using closed cell foam gaskets.
5. Case walls and doors shall be fully insulated with 1 inch, expanded polystyrene
foam insulation faced with a cleanable foil face on all exposed surfaces.
6. The ERV cores shall be protected by a MERV-8 rated, spun polyester,
disposable filter in both airstreams.
7. The unit shall have a line cord power connection and be supplied with an
internal 24 VAC transformer and relay.
8. Standby power draw shall not exceed 1 Watt for the unit along with an
optional automatic control.
B. Options (Select options based on application requirements)
1. For BR-Series: Through the wall kit and duct collar kit (automatic control
is built into the unit standard).
2. For EV-Series: Controls including proportional run time, push button and
furnace interlock and a variety of weather hoods.
Part IV – Installation
A. Unit Location
1. Locate and orient unit to provide the shortest and most straight duct
connections. Provide service clearances as indicated on the plans. Locate
units distant from sound critical occupancies.
2. Use integral mounting flange and hanging bar system to mount the unit to a
structurally suitable surface. The units may be mounted in any orientation.
B. Vibration Isolation
1. Utilize factory supplied vibration isolation kit following instructions.
2. Provide flexible duct connections at unit duct flanges.
C. Duct Design
1. All ductwork shall be designed, constructed, supported and sealed in
accordance with SMACNA HVAC Duct Construction Standards and pressure
classifications.
2. At a minimum all duct runs to the outdoors shall be thermally insulated
at levels appropriate to the local climate. A continuous vapor barrier shall
also be provided on warm surface of the insulation.
D. Sound Control
1. To control sound radiated from the unit:
a. Provide acoustic treatment in mechanical room walls and ceilings.
2. To control sound associated with the two blower outlets:
a. Utilize insulated, flexible duct.
b. In sound critical applications provide increased duct sizing and
consider the use of sound attenuators.
E. Test and Balancing
1. Test and Balancing may not begin until 100% of the installation is
complete and fully functional.
2. Follow National Comfort Institute (NCI) air test and balance procedures
specific to Heat Recovery Ventilator Balancing Procedure including standard
reports to the owner’s representative.
3
www.RenewAire.com
BR70
Specifications
Indoor Unit
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 40-70 CFM
Number Motors: One, 0.08 hp
V
HZ
Phase
Input
Watts
FLA
120
60
Single
94 @ 69 CFM
0.9
Control Voltage: 24 VAC
Filters: MERV 8, spun polyester media. 7 1/2” x 10 1/2” x 1”
Weight: 39 lbs (unit), 50 lbs (in carton)
Shipping Dimensions: 21 1/2”W x 29”L x 14 1/2”H
Options: Thru-the-Wall Kit
Duct Collar Kit
G4 Performance
Airflow CFM
ESP in H20
Temp EFF%
Total EFF% Winter/Summer*
35
0.50
84
75/60
51
0.40
80
71/56
63
0.30
77
68/53
79
0.20
73
64/48
90
0.10
70
61/45
* (See HVI certification report on page 66 for complete certified rating).
Dimensions
EA:
OA:
RA:
FA:
OA (TW)
RA (DH)
EA (TW)
FA (DH)
Exhaust Air to outdoors
Outdoor Air intake
Room Air to be exhausted
Fresh Air to inside
6
2
17 5/8
1 1/8
TW: Thru Wall
DH: Duct Hung
CUT HOLE IN DUCT
(MINIMUM SIZE)
TOP VIEW
OA (TW)
RA (DH)
36" LINE CORD
EA (TW)
FA (DH)
RA (TW)
OA (DH)
FA (TW)
EA (DH)
6 DIA
10 5/8
SIDE VIEW
24 VAC
CONTROL
TERMINAL
27 1/8
18 1/2
SERVICE
AREA
PROPORTIONAL
RUNTIME
CONTROL
18 1/4
RIGHT
VIEW
5
4 1/2
BOTTOM VIEW
(DOOR REMOVED)
4
(800) 627-4499
•
Fax: (608) 221-2824
8 DIA
BR130
Specifications
Indoor Unit
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 50-140 CFM
Unit may be mounted in any orientation
Number Motors: One, 0.1 hp
V
HZ
Phase
Input
Watts
FLA
120
60
Single
121 @ 124 CFM
1.3
Control Voltage: Built in proportional runtime control and
switched terminals for furnace / AC interconnect
Filters: MERV 8, spun polyester media. 10 1/2” x 10 1/2” x 1”
Weight: 49 lbs (unit), 60 lbs (in carton)
G4 Performance
Shipping Dimensions: 21”W x 32”L x 17 1/2”H
Airflow CFM
ESP in H20
Temp EFF%
Total EFF% Winter/Summer*
52
0.70
83
75/60
69
0.60
80
72/57
94
0.50
76
67/52
113
0.40
73
64/48
132
0.30
70
60/44
141
0.20
68
59/43
148
0.10
67
57/41
Options: Thru-the-Wall Kit
Duct Collar Kit
* (See HVI certification report on page 66 for complete certified rating).
Dimensions
OA (TW)
RA (DH)
EA:
OA:
RA:
FA:
EA (TW)
FA (DH)
6
2
1 1/8
OA (TW)
RA (DH)
TW: Thru Wall
DH: Duct Hung
CUT HOLE IN DUCT
(MINIMUM SIZE)
20 1/2
TOP VIEW
Exhaust Air to outdoors
Outdoor Air intake
Room Air to be exhausted
Fresh Air to inside
36" LINE CORD
EA (TW)
FA (DH)
4 3/4
6 1/8
RA (TW)
OA (DH)
SIDE VIEW
FA (TW)
EA (DH)
6 DIA
24 VAC
CONTROL
TERMINAL
30 7/8
8 DIA
13 3/8
18 1/2
SERVICE
AREA
PROPORTIONAL
RUNTIME
CONTROL
18 1/4
RIGHT
VIEW
5
4 1/2
BOTTOM VIEW
(DOOR REMOVED)
5
www.RenewAire.com
EV70
Specifications
Indoor Unit
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 40-70 CFM
Unit may be mounted in any orientation
Number Motors: One, 0.08 hp
V
HZ
Phase
Input
Watts
FLA
120
60
Single
94 @ 69 CFM
0.9
Control Voltage: 24 VAC
Filters: MERV 8, spun polyester media. 7 1/2” x 10 1/2” x 1”
Weight: 39 lbs (unit), 48 lbs (in carton)
Shipping Dimensions: 21 1/2”W x 29”L x 14 1/2”H
G4 Performance
Airflow CFM
ESP in H20
Temp EFF%
Total EFF% Winter/Summer*
46
0.40
81
74/60
59
0.30
78
71/57
73
0.20
74
68/53
86
0.10
71
64/49
Options: PTL - Percentage Timer Control
PBL - Push Button Point-of-Use Controls
FM - Percentage Timer Control with Furnace Interlock
DH24 - Dehumidistat Control
Wall Caps
* (See HVI certification report on page 66 for complete certified rating).
Dimensions
34" Line Cord
Exhaust Air to outdoors
Outdoor Air intake
Room Air to be exhausted
Fresh Air to inside
4 1/2"
4 1/8"
EA:
OA:
RA:
FA:
10 1/8"
Blowers
Interlock Switch
25 1/8"
8"
Line Cord
5 1/2"
6"
RA
Filters
EA
FA
Energy Transfer Core
FRONT VIEW
27 7/8" Service Access
RIGHT VIEW
6
(800) 627-4499
20 1/8"
8 1/8"
9 1/8"
OA
6"
24 Volt AC
Control Terminal
6"
5 1/2"
TOP VIEW
•
Fax: (608) 221-2824
EV130
Specifications
Indoor Unit
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 50-140 CFM
Unit may be mounted in any orientation
Number Motors: One, 0.1 hp
V
HZ
Phase
Input
Watts
FLA
120
60
Single
121 @ 124 CFM
1.2
Control Voltage: 24 VAC
Filters: MERV 8, spun polyester media. 10 1/2” x 10 1/2” x 1”
Weight: 49 lbs (unit), 58 lbs (in carton)
Shipping Dimensions: 21”W x 32”L x 17 1/2”H
G4 Performance
Airflow CFM
ESP in H20
Temp EFF%
Total EFF% Winter/Summer*
52
0.70
83
75/60
69
0.60
80
72/57
94
0.50
76
67/52
113
0.40
73
64/48
132
0.30
70
60/44
141
0.20
68
59/43
148
0.10
67
57/41
Options: PTL - Percentage Timer Control
PBL - Push Button Point-of-Use Controls
FM - Percentage Timer Control with Furnace Interlock
DH24 - Dehumidistat Control
Wall Caps
* (See HVI certification report on page 66 for complete certified rating).
Dimensions
6 3/8"
4 1/8"
EA:
OA:
RA:
FA:
Exhaust Air to outdoors
Outdoor Air intake
Room Air to be exhausted
Fresh Air to inside
34" Line Cord
13"
5 1/2"
TOP VIEW
8"
Blowers
Interlock Switch
Line Cord
6"
28 3/4"
5 1/2"
6"
RA
Filters
Energy Transfer Core
EA
20 1/8"
8 1/8"
OA
9 1/8"
6"
24 Volt AC
Control Terminal
FA
30 5/8" Service Access
RIGHT VIEW
FRONT VIEW
7
www.RenewAire.com
EV200
Specifications
Indoor Unit
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 100-200 CFM
Number Motors: One, 0.1 hp
V
HZ
Phase
Input
Watts
FLA
120
60
Single
157 @ 181 CFM
1.5
Control Voltage: 24 VAC
Filters: MERV 8, spun polyester media. 10 1/2” x 21 3/4” x 1”
Weight: 70 lbs (unit), 82 lbs (in carton)
Shipping Dimensions: 21 1/2”W x 32”L x 29”H
G4 Performance
Airflow CFM
ESP in H20
Temp EFF%
Total EFF% Winter/Summer*
122
0.70
82
74/59
149
0.65
80
72/56
168
0.50
79
70/55
176
0.40
78
69/54
186
0.30
77
68/53
192
0.20
77
68/52
200
0.10
76
67/52
Options: PTL - Percentage Timer Control
PBL - Push Button Point-of-Use Controls
FM - Percentage Timer Control with Furnace Interlock
DH24 - Dehumidistat Control
Wall Caps
* (See HVI certification report on page 66 for complete certified rating).
EA:
OA:
RA:
FA:
11 7/8"
11 7/8"
Dimensions
Exhaust Air to outdoors
Outdoor Air intake
Room Air to be exhausted
Fresh Air to inside
34" Line Cord
TOP VIEW
23 7/8"
Interlock Switch
Blowers
Line Cord
6"
6"
6"
EA
20 1/8"
8 1/8"
9 1/8"
5 1/2"
RA
5 1/2"
28 3/4"
OA
8"
24 Volt AC
Control Terminal
FA
41 1/2" Service Access
Filters
Energy Transfer Core
FRONT VIEW
RIGHT VIEW
8
(800) 627-4499
•
Fax: (608) 221-2824
EV300
Indoor Unit
Specifications
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 150-300 CFM
Number Motors: One, 0.2 hp
V
HZ
Phase
Input
Watts
FLA
120
60
Single
310 @ 293 CFM
3.3
Control Voltage: 24 VAC
Filters: MERV 8, spun polyester media. 10 1/2” x 21 3/4” x 1”
Weight: 72 lbs (unit), 85 lbs (in carton)
Shipping Dimensions: 21 1/2”W x 32”L x 29”H
G4 Performance
Airflow CFM
ESP in H20
Temp EFF%
Total EFF% Winter/Summer*
155
1.0
80
70/51
199
0.9
76
67/48
249
0.8
72
62/44
268
0.7
71
61/42
289
0.6
69
58/39
300
0.5
68
57/38
310
0.4
67
56/37
Options: PTL - Percentage Timer Control
PBL - Push Button Point-of-Use Controls
FM - Percentage Timer Control with Furnace Interlock
DH24 - Dehumidistat Control
8” Wall Caps
* (See HVI certification report on page 66 for complete certified rating).
Dimensions
10"
EA:
OA:
RA:
FA:
9 3/4"
Exhaust Air to outdoors
Outdoor Air intake
Room Air to be exhausted
Fresh Air to inside
34" Line Cord
To Fit 8" Duct
TOP VIEW
23 7/8"
Interlock Switch
Blowers
28 3/4"
5 1/2"
5 1/2"
OA
7 3/8"
EA
9 1/8"
9 1/8"
RA
8 3/4"
24 Volt AC
Control
Terminal
5 1/2"
5 1/2"
FA
20 1/8"
41 1/2" Service Access
Filters
Line Cord
Energy Transfer Core
FRONT VIEW
RIGHT VIEW
9
www.RenewAire.com
Commercial
INDOOR Products
• Horizontal and vertical configuration.
• Wide range of airflow and static capacities.
• AHRI certified performance data for
efficiency and cross leakage.
• UL tested flammability and smoke
generation that meets NFPA 90A and
90B test standards for commercial
applications.
• Easy installation and service.
• Ten year core warranty.
RenewAire means Trouble-Free ERV.
EA:
OA:
RA:
FA:
10
(800) 627-4499
•
Fax: (608) 221-2824
Exhaust Air to outdoors
Outdoor Air intake
Room Air to be exhausted
Fresh Air to inside
Packaged Indoor Energy Recovery Ventilators:
EV450IN, HE1XIN, HE2XIN, HE3XIN, HE4XIN, HE6XIN, HE8XIN
Part I - General
Part III – Product
A. Product Specification
A. Construction
1. Energy Recovery Ventilator (ERV) shall be a packaged unit as
manufactured by RenewAire and shall transfer both heat and humidity
using static plate core technology.
1. The energy recovery component shall be of fixed-plate cross-flow
construction, with no moving parts.
B. Quality Assurance
1. The energy recovery cores used in these products shall be third
party Certified by AHRI under its Standard 1060 for Energy Recovery
Ventilators. AHRI published certifications shall confirm manufacture’s
published performance for airflow, static pressure, temperature and
total effectiveness, purge air (OACF) and exhaust air leakage (EATR).
Products that are not currently AHRI Certified will not be accepted.
2. Manufacturer shall be able to provide evidence of independent testing
of the core by Underwriters Laboratory (UL), verifying a maximum flame
spread index (FSI) of 25 and a maximum smoke developed index (SDI) of
50 thereby meeting NFPA 90A and NFPA 90B requirements for materials
in a compartment handling air intended for circulation through a duct
system. The method of test shall be UL Standard 723.
3. Unit shall be Listed under UL 1812 Standard for Ducted Air to Air
Heat Exchangers. (Note that a few low volume product or product
configurations are not UL Listed.)
4. The ERV core shall be warranted to be free of manufacturing defects
and to retain its functional characteristics, under circumstances of
normal use, for a period of ten years from the date of purchase. The
balance-of-unit shall be warranted to be free of manufacturing defects
and to retain its functional characteristics, under circumstances of
normal use, for a period of two years from the date of purchase.
Part II – Performance
2. No condensate drain pans or drains shall be allowed and unit shall
be capable of operating in both winter and summer conditions without
generating condensate.
3. The unit case shall be constructed of G90 galvanized, 20-gauge
steel, with lapped corners and zinc plated screw fasteners.
4. Access doors shall provide easy access to blowers, ERV cores and
filters. Doors shall have an airtight compression seal using closed cell
foam gaskets.
5. Case walls and doors shall be insulated with 1 inch, 4 pound density,
foil/scrim faced, high-density fiberglass board insulation, providing a
cleanable surface and eliminating the possibility of exposing the fresh
air to glass fibers.
6. The ERV cores shall be protected by a MERV-8 rated, 2” nominal,
pleated, disposable filter in both airstreams.
7. Unit shall have single-point power connection and a single-point 24
VAC contactor control connection (except Inverter Ready units that have
terminal connections for an independent inverter for each airstream).
8. Blower motors shall be EPACT compliant for energy efficiency and
be thermally protected or supplied with external starters.
9. Blowers shall be quiet running, forward curve type and be either direct
drive or belt drive. HE6X and HE8X units use backward incline, belt drive
blower packages. Belt drive motors shall be provided with adjustable
pulleys and motor mounts allowing for proper belt tensioning.
A. Energy Transfer
The ERV shall be capable of transferring both sensible and latent energy
between airstreams. Latent energy transfer shall be accomplished by
direct water vapor transfer from one airstream to the other, without
exposing transfer media in succeeding cycles directly to the exhaust
air and then to the fresh air.
B. Passive Frost Control
The ERV core shall perform without condensing or frosting under
normal operating conditions (defined as outside temperatures above
-10°F and inside relative humidity below 40%). Occasional more
extreme conditions shall not affect the usual function, performance or
durability of the core. No condensate drains will be allowed.
C. Continuous Ventilation
Unit shall have the capacity to operate continuously without the need
for bypass, recirculation, pre-heaters or defrost cycles under normal
operating conditions.
B. Options (Select options based on application requirements.)
1. Provide unit and duct connection orientation per project schedule.
2. Provide double wall construction with 24-gauge galvanized steel liner.
3. Units are available single or three phase at a full range of operating
voltages. See project schedule.
4. Provide motor horsepower as specified in project schedule.
5. Provide “inverter-ready” units which include shielded power
wiring and terminal connections for inverters (inverters provided and
installed by others).
6. Provide factory installed fused disconnects.
7. Provide factory installed non-fused disconnects.
D. Positive Airstream Separation
Water vapor transfer shall be through molecular transport by
hydroscopic resin and shall not be accomplished by “porous plate”
mechanisms. Exhaust and fresh airstreams shall travel at all times in
separate passages and airstreams shall not mix.
8. Provide factory installed transformer/relay package to supply a 24
VAC power source.
9. Provide factory installed filter monitors for each airstream.
E. Laminar Flow
Airflow through the ERV core shall be laminar over the products entire
operating airflow range, avoiding deposition of particulates on the
interior of the energy exchange plate material.
11
www.RenewAire.com
EV450IN
Indoor Unit
Specifications
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 200-500 CFM
AHRI 1060 Certified Core: One L85
Airflow Rating Points (for AHRI): 450 CFM and 338 CFM
Motors: One, 0.6 hp (Single Phase) One, 0.5hp (Three Phase)
V
HZ
Phase
FLA
115
60
Single
7.0
208-230
60
Single
3.5
277
60
Single
2.4
208-230
60
Three
1.7-1.5
460
60
Three
0.8
G5 Performance
Airflow
CFM
ESP in
H 20
Watts
1P
3P
Temp
EFF%
Total EFF%
Winter/Summer*
225
1.25
335
181
81
76/66
338
1.00
420
278
77
71/61
380
0.90
470
340
75
69/59
450
0.65
550
430
73
66/56
540
0.25
640
540
70
62/52
575
0.00
690
610
69
61/51
600
-0.25
735
664
68
60/50
Control Voltage: 24 VAC
Filters: Two total, MERV 8, 2” pleated, 14” x 20” nominal size
Weight: 141 lbs (unit), 160 lbs (in carton), up to 3 units on 50 lb pallet
Shipping Dimensions: 37 1/2” W x 48” L x 17” H
Options: 45EVHB - Hanging Bracket, Foot Kit
45EVDF - Rectangular 12” x 8” Flange Kit (2 in kit)
45EVT10 - 10” Round Transition Kit (2 in kit)
*At AHRI 1060 standard conditions
(See certified data on page 67 for core components.)
12
(800) 627-4499
•
Fax: (608) 221-2824
www.RenewAire.com
13
2 1/8"
4 1/4"
36 3/8"
32"
20 1/4"
16 1/8"
36 3/8"
32"
20 1/4"
16 1/8"
10"
2 1/8"
10"
4 1/4"
1 1/4"
FRONT VIEW
44 1/8"
8"
8"
8"
Optional Transitions (45EVT10) shown
FA
RA
Control Wire Entry
7/8" Dia.
Power Supply Entry
7/8" Dia.
EA
FRONT VIEW (Doors removed)
18"
8"
8"
TOP VIEW
13 1/4"
16"
33 7/8"
OA
Optional 45EVT10-10" Round
Transition Kit Shown
LEFT VIEWS
RA
OA
O
"R
0
O1
6 3/8"
D
UN
All other Access:
Screw-attached
panel
Filter Access:
Hinged and
Latched Door
2 1/8"
34 1/8"
Service
Area
36 3/8"
35 1/4"
RIGHT VIEWS
FA
EA
Optional 45EVDF Rectangular
12" X 8" Flange Kit Shown
5 1/4"
8 3/4"
1"
6 1/2"
Exhaust Air to outdoors
Outdoor Air intake
Room Air to be exhausted
Fresh Air to inside
13 1/4"
1"
1 1/2" Clearance required
to remove doors
from hinges.
11 1/8"
Unit Dimensions
25 1/8"
EA:
OA:
RA:
FA:
3 1/4"
5 3/8"
4 3/4"
2 1/8"
11 5/8"
Alternate
Power Supply Entry
7/8" Dia.
4 1/4"
EV450IN
26 1/4"
10 1/8"
16 1/8"
20 3/8"
24 7/8"
16 1/8"
20 1/4"
32"
HE1XINH
Indoor Unit
Specifications
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 250-925 CFM
AHRI 1060 Certified Core: One L125-00
Airflow Rating Points (for AHRI): 750 CFM and 560 CFM
Number Motors: Two
V
HZ
Phase
FLA
Min. Cir.
Amps
Max.
Fuse Size
115
60
Single
8.6
19.4
25
208-230
60
Single
4.3
9.7
15
277
60
Single
2.4
5.4
15
208-230
60
Three
2.1
5.2
15
460
60
Three
1.1
2.6
15
G5 Performance
CFM
Effectiveness (%)
250
500
Control Voltage: 24 VAC
750
1,000
Filters: Two total, MERV 8, 2” pleated, 20” x 20” nominal size
Weight: 211 lbs (unit), 250 lbs (shipping weight)
80
Sensible
Winter
60
Summ
Shipping Dimensions: 44” W x 56” L x 27” H
Total
er To
tal
40
*At AHRI 1060 standard conditions
(See certified data on page 67 for core components.)
Airflow Performance
Motor HP
Phase
External Static Pressure (Inches Water Column)
0.0
0.25
0.5
0.75
1.0
1.25
1.5
0.75 (Two DD)
Single Phase
970 CFM
1,490 Watts
925 CFM
1,375 Watts
860 CFM
1,270 Watts
795 CFM
1,160 Watts
720 CFM
1,030 Watts
635 CFM
950 Watts
350 CFM
750 Watts
0.75 (Two DD)
Three Phase
1,030 CFM
1,220 Watts
1,010 CFM
1,210 Watts
975 CFM
1,160 Watts
880 CFM
1,050 Watts
800 CFM
990 Watts
700 CFM
850 Watts
530 CFM
720 Watts
14
(800) 627-4499
•
Fax: (608) 221-2824
www.RenewAire.com
15
FA
EA
LEFT VIEW
9 1/2"
28 3/8"
12 7/8"
8 5/8"
Ø12" TYP
20 5/8"
FA
34 7/8" Case
EA
Power Wiring Inlet 7/ 8" Dia.
Control Wiring Inlet 7/8" Dia.
50 1/8"
Maximum Door Extension
Alternate Control Wiring Inlet
7/8" Dia.
Alternate Power Wiring Inlet
7/8" Dia.
Unit Dimensions
HE1XINH
FRONT VIEW
49 1/8" Case
RA
OA
36 3/8"
Overall
28 1/4"
9 5/8"
RIGHT VIEW
RA
OA
10 3/8"
21 3/4" Overall
Exhaust Air to outdoors
Outdoor Air intake
Room Air to be exhausted
Fresh Air to inside
40 5/8"
Minimum Service Area
(Doors can be taken off hinges.)
TOP VIEW
54 3/4" Overall
EA:
OA:
RA:
FA:
HE1XINV
Indoor Unit
Specifications
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 250-925 CFM
AHRI 1060 Certified Core: One L125-00
Airflow Rating Points (for AHRI): 750 CFM and 560 CFM
Number Motors: Two
V
HZ
Phase
FLA
Min. Cir.
Amps
Max.
Fuse Size
115
60
Single
8.6
19.4
25
208-230
60
Single
4.3
9.7
15
277
60
Single
2.4
5.4
15
208-230
60
Three
2.1
5.2
15
460
60
Three
1.1
2.6
15
G5 Performance
CFM
Effectiveness (%)
250
500
Control Voltage: 24 VAC
750
1,000
Filters: Two total, MERV 8, 2” pleated, 20” x 20” nominal size
Weight: 211 lbs (unit), 250 lbs (shipping weight)
80
Sensible
Winter
60
Summ
Shipping Dimensions: 44” W x 56” L x 27” H
Total
er To
tal
40
*At AHRI 1060 standard conditions
(See certified data on page 67 for core components.)
Airflow Performance
Motor HP
Phase
External Static Pressure (Inches Water Column)
0.0
0.25
0.5
0.75
1.0
1.25
1.5
0.75 (Two DD)
Single Phase
970 CFM
1,490 Watts
925 CFM
1,375 Watts
860 CFM
1,270 Watts
795 CFM
1,160 Watts
720
1,030
CFM
Watts
635
950
CFM
Watts
350
750
CFM
Watts
0.75 (Two DD)
Three Phase
1,030 CFM
1,220 Watts
1,010
1,210
975 CFM
1,160 Watts
880 CFM
1,050 Watts
800
990
CFM
Watts
700
850
CFM
Watts
530
720
CFM
Watts
CFM
Watts
16
(800) 627-4499
•
Fax: (608) 221-2824
www.RenewAire.com
17
41 5/8"
Control Wiring Inlet
7/8" Dia.
Power Wiring Inlet
7/8" Dia.
17"
10 3/8"
12 7/8"
FA
RA
Unit Dimensions
P
LEFT
VIEW
Ø
FA
RA
FRONT VIEW
34 7/8" Case
TOP VIEW
40 3/8" Overall
EA
OA
EA
OA
21 3/4" Overall
10 3/8"
RIGHT VIEW
50 1/8"
Maximum Door
Extension
40 5/8"
Minimum Service Area
(Doors can be taken off hinges.)
41 1/2"
TY
12
"
Exhaust Air to outdoors
Outdoor Air intake
Room Air to be exhausted
Fresh Air to inside
17"
EA:
OA:
RA:
FA:
50 5/8"
HE1XINV
51 3/8" Overall
20 5/8"
49 1/8" Case
HE2XINH
Indoor Unit
Specifications
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 500-2,000 CFM
AHRI 1060 Certified Core: Two L125-00
Airflow Rating Points (for AHRI): 1,500 CFM and 1,120 CFM
Number Motors: Direct Drive (DD) Four, Belt Drive (BD) Two
Drive
HP
Volts
HZ
Phase
FLA
Min.
Cir.
Amps
Max.
Fuse
Size
DD
0.75
115
208-230
277
208-230
460
60
60
60
60
60
Single
Single
Single
Three
Three
8.6
4.3
2.4
2.1
1.1
36.6
18.3
10.2
9.8
4.9
45
20
15
15
15
BD
1.5
208-230
208-230
460
575
60
60
60
60
Single
Three
Three
Three
9.3-9.0
4.8-4.8
2.4
1.8
20.9
10.8
5.4
4.1
30
15
15
15
BD
2
208-230
208-230
460
575
60
60
60
60
Single
Three
Three
Three
11.3-10.5
6.2-6.2
3.1
2.3
25.4
14.0
7.0
5.2
35
20
15
15
G5 Performance
CFM
Effectiveness (%)
500
1,000
1,500
2,000
80
Sensible
Winter
Total
60
Control Voltage: 24 VAC
Filters: Four total, MERV 8, 2” pleated, 20” x 20” nominal size
Summ
er To
tal
Weight: 414 lbs (unit), 420 lbs (shipping weight)
40
Shipping Dimensions: 50” W x 62” L x 41” H
*At AHRI 1060 standard conditions
(See certified data on page 67 for core components.)
Airflow Performance
External Static Pressure (Inches Water Column)
Motor HP
Blower RPM
Nominal
Turns
Open
0.0
0.25
0.5
0.75
1.0
1.25
0.75 (Four DD)
Single Phase
N/A
N/A
N/A
N/A
1,950 CFM
2,240 Watts
1,830 CFM
2,155 Watts
1,670 CFM
2,020 Watts
1,400 CFM
1,795 Watts
1,150 CFM
1,490 Watts
700 CFM
1,190 Watts
0.75 (Four DD)
Three Phase
N/A
N/A
N/A
N/A
1,960 CFM
2,500 Watts
1,840 CFM
2,300 Watts
1,700 CFM
2,125 Watts
1,600 CFM
1,900 Watts
1,380 CFM
1,700 Watts
1,190 CFM
1,500 Watts
1.5
-
-
800 CFM
1,260 Watts
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
1.5 (BD)
1,000
1,230
1,420
4.5
2
0
1,378
1,694
1,956
0.5
0.9
1.4
1,175
1,550
1,850
0.5
0.9
1.4
900
1,335
1,680
0.4
0.8
1.2
635
1,125
1,475
0.4
0.7
1.2
1,000
1,300
0.7
1.1
500
1,200
0.6
1.1
930
0.9
2 (BD)
1,220
1,470
1,660
4.5
2
0
1,681
2,025
-
0.9
1.6
-
1,530
1,925
-
0.9
1.5
-
1,315
1,750
2,000
0.7
1.4
2.0
1,100
1,575
1,900
0.7
1.3
1.9
975
1,375
1,750
0.6
1.2
1.8
1,275
1,570
1.2
1.7
1,125
1,475
1.1
1.7
Note: Brake Horse Power (BHP) is for one blower motor package only.
18
(800) 627-4499
•
Fax: (608) 221-2824
19 5/8"
20 5/8"
2 3/4"
3 1/2"
Wiring Entry
7/8" Dia.
LEFT VIEW
Direct Drive Version
EA
FA
LEFT VIEW
Belt Driven Version
EA
33"
FA
FRONT VIEW
49 1/4" case
TOP VIEW
59" Service Area
OA
RIGHT VIEW
OA
RA
24" TYP
8"
41 1/4"
Note: Door lifts away.
Filters
RA
60" Service Area
Note: All duct flanges are 14" x 24".
EA
E-Box
E-Box
35 1/4" Case
FA
54 7/8" overall
Exhaust Air to outdoors
Outdoor Air intake
Room Air to be exhausted
Fresh Air to inside
21 5/8"
14" typ
2 7/8"
Unit Dimensions
34 3/4"
EA:
OA:
RA:
FA:
36 5/8"
HE2XINH
15 3/8"
www.RenewAire.com
19
HE2XINV
Indoor Unit
Specifications
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 500-2,000 CFM
AHRI 1060 Certified Core: Two L125-00
Airflow Rating Points (for AHRI): 1,500 CFM and 1,120 CFM
Number Motors: Direct Drive (DD) Four, Belt Drive (BD) Two
Drive
HP
Volts
HZ
Phase
FLA
Min.
Cir.
Amps
Max.
Fuse
Size
DD
0.75
115
208-230
277
208-230
460
60
60
60
60
60
Single
Single
Single
Three
Three
8.6
4.3
2.4
2.1
1.1
36.6
18.3
10.2
9.8
4.9
45
20
15
15
15
BD
1.5
208-230
208-230
460
575
60
60
60
60
Single
Three
Three
Three
9.3-9.0
4.8-4.8
2.4
1.8
20.9
10.8
5.4
4.1
30
15
15
15
BD
2
208-230
208-230
460
575
60
60
60
60
Single
Three
Three
Three
11.3-10.5
6.2-6.2
3.1
2.3
25.4
14.0
7.0
5.2
35
20
15
15
G5 Performance
CFM
Effectiveness (%)
500
1,000
1,500
2,000
80
Sensible
Winter
Total
60
Control Voltage: 24 VAC
Filters: Four total, MERV 8, 2” pleated, 20” x 20” nominal size
Summ
er To
tal
Weight: 399 lbs (unit), 420 lbs (shipping weight)
40
Shipping Dimensions: 48” W x 62” L x 55” H
*At AHRI 1060 standard conditions
(See certified data on page 67 for core components.)
Airflow Performance
External Static Pressure (Inches Water Column)
Blower RPM
Nominal
Turns
Open
0.0
0.25
0.5
0.75
1.0
1.25
0.75 (Four DD)
Single Phase
N/A
N/A
N/A
N/A
1,870 CFM
2,160 Watts
1,720 CFM
2,070 Watts
1,520 CFM
1,900 Watts
1,290 CFM
1,715 Watts
1,080 CFM
1,505 Watts
700 CFM
1,210 Watts
0.75 (Four DD)
Three Phase
N/A
N/A
N/A
N/A
1,870 CFM
2,500 Watts
1,720 CFM
2,300 Watts
1,540 CFM
2,125 Watts
1,350 CFM
1,950 Watts
1,240 CFM
1,730 Watts
1,030 CFM
1,490 Watts
Motor HP
1.5
-
-
800 CFM
1,240 Watts
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
1.5 (BD)
1,000
1,230
1,420
4.5
2
0
1,378
1,694
1,956
0.5
0.9
1.4
1,175
1,550
1,850
0.5
0.9
1.4
900
1,335
1,680
0.4
0.8
1.2
635
1,125
1,475
0.4
0.7
1.2
1,000
1,300
0.7
1.1
500
1,200
0.6
1.1
930
0.9
2 (BD)
1,220
1,470
1,660
4.5
2
0
1,681
2,025
-
0.9
1.6
-
1,530
1,925
-
0.9
1.5
-
1,315
1,750
2,000
0.7
1.4
2.0
1,100
1,575
1,900
0.7
1.3
1.9
975
1,375
1,750
0.6
1.2
1.8
430
1,275
1,570
0.6
1.2
1.7
1,125
1,475
1.1
1.7
Note: Brake Horse Power (BHP) is for one blower motor package only.
20
(800) 627-4499
•
Fax: (608) 221-2824
www.RenewAire.com
21
19 3/8"
LEFT END VIEW
DIRECT DRIVE
E-box power wire
7/8" Dia.
FA
RA
LEFT END VIEW
6 3/8"
BELT DRIVE
FA
RA
Unit Dimensions
HE2XINV
5 7/8"
FA
FRONT VIEW
38 3/4"
35 1/4"
w/ screws
Note: All duct flanges are 14" x 24".
19 3/8"
43 3/4"
EA
OA
TOP VIEW and Service Area
RA
4 1/4"
74 7/8" Clear
34 1/8"
39 1/4"
49 1/8"
14"
8 1/8"
3 1/2"
RIGHT END VIEW
DIRECT DRIVE
EA
OA
24"
41 1/2"
RIGHT END VIEW
BELT DRIVE
EA
35 5/8"
50 5/8"
Exhaust Air to outdoors
Outdoor Air intake
Room Air to be exhausted
Fresh Air to inside
OA
EA:
OA:
RA:
FA:
HE3XINH
Indoor Unit
Specifications
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 750-3,300 CFM
AHRI 1060 Certified Core: Three L125-00
Airflow Rating Points (for AHRI): 2,250 CFM and 1,690 CFM
Number Motors: Two
G5 Performance
HP
Volts
HZ
Phase
FLA
Min.
Cir.
Amps
Max.
Fuse
Size
2
208-230
208-230
460
575
60
60
60
60
Single
Three
Three
Three
11.3-10.5
6.2-6.2
3.1
2.3
25.4
14.0
7.0
5.2
35
20
15
15
3
208-230
208-230
460
575
60
60
60
60
Single
Three
Three
Three
13.7
9.2-8.6
4.3
3.2
30.8
20.7
9.7
7.2
45
30
15
15
5
208-230
460
575
60
60
60
Three
Three
Three
14.0-13.0
6.5
5.0
31.5
14.6
11.3
45
20
15
CFM
Effectiveness (%)
1,500
2,000
2,500
3,000
80
Control Voltage: 24 VAC
Sensible
Winter
60
Filters: Six total, MERV 8, 2” pleated, 20” x 20” nominal size
Total
Summ
Weight: 675 lbs (unit), 700 lbs (shipping weight)
Shipping Dimensions: 72” W x 84” L x 46” H
er To
tal
40
*At AHRI 1060 standard conditions
(See certified data on page 67 for core components.)
Airflow Performance
External Static Pressure (Inches Water Column)
Motor HP
Blower RPM
Nominal
Turns Open
0.0
CFM
0.25
BHP
CFM
0.5
BHP
CFM
0.75
BHP
CFM
1.0
BHP
CFM
1.25
BHP
CFM
1.5
BHP
CFM
BHP
2
1,095
1,220
1,340
4
2
0
2,040
2,340
2,590
1.3
1.5
1.8
1,760
2,110
2,370
1.3
1.4
1.7
1,370
1,790
2,130
1.2
1.3
1.6
920
1,380
1,760
1.1
1.2
1.4
940
1,310
1.2
1.3
980
1.2
-
-
3
1,345
1,535
1,685
4.5
2
0
2,420
2,850
-
2.3
2.8
-
2,280
2,760
-
2.2
2.7
-
2,090
2,570
-
2.1
2.6
-
1,760
2,380
2,660
2.0
2.5
2.9
1,280
2,090
2,470
1.9
2.4
2.7
860
1,810
2,280
1.9
2.2
2.6
1,330
2,000
2.1
2.4
5
1,495
1,675
1,855
6.5
3.5
0
2,850
3,280
-
3.1
3.8
-
2,710
3,140
-
3.0
3.7
-
2.520
2,990
3,470
2.9
3.5
4.9
2,280
2,800
3,330
2.8
3.3
4.7
2,040
2,610
3,140
2.7
3.1
4.5
1,620
2,380
3,040
2.5
2.9
4.4
1,140
2,090
2,760
2.4
2.7
4.0
22
(800) 627-4499
•
Fax: (608) 221-2824
12"
Left View
FA
EA
62 1/4"
12"
39"
E-box
FA
EA
55 1/8" Control Wiring Inlet
58 1/8" Power Wiring Inlet
E-box
Note: There are two 12" x 12" discharges.
5 1/2"
Unit Dimensions
18 5/8"
Front View
57 1/4"
Top View
64 1/2"
Service Area
64 1/2" overall
62 1/4"
RA
OA
97" Service Area
Right View
RA
12" X 34"
62 1/4"
4 1/4"
OA
12" X 34"
Exhaust Air to outdoors
Outdoor Air intake
Room Air to be exhausted
Fresh Air to inside
5 1/8"
26 1/8"
EA:
OA:
RA:
FA:
40 3/8"
HE3XINh
40 3/8"
22 3/8"
www.RenewAire.com
23
HE3XINV
Indoor Unit
Specifications
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 750-3,300 CFM
AHRI 1060 Certified Core: Three L125-00
Airflow Rating Points (for AHRI): 2,250 CFM and 1,690 CFM
Number Motors: Two
G5 Performance
HP
Volts
HZ
Phase
FLA
Min.
Cir.
Amps
Max.
Fuse
Size
2
208-230
208-230
460
575
60
60
60
60
Single
Three
Three
Three
11.3-10.5
6.2-6.2
3.1
2.3
25.4
14.0
7.0
5.2
35
20
15
15
3
208-230
208-230
460
575
60
60
60
60
Single
Three
Three
Three
13.7
9.2-8.6
4.3
3.2
30.8
20.7
9.7
7.2
45
30
15
15
5
208-230
460
575
60
60
60
Three
Three
Three
14.0-13.0
6.5
5.0
31.5
14.6
11.3
45
20
15
CFM
Effectiveness (%)
1,500
2,000
2,500
3,000
80
Control Voltage: 24 VAC
Sensible
Winter
60
Filters: Six total, MERV 8, 2” pleated, 20” x 20” nominal size
Total
Summ
Weight: 640 lbs (unit), 675 lbs (shipping weight)
er To
Shipping Dimensions: 45” W x 70” L x 70” H
tal
40
*At AHRI 1060 standard conditions
(See certified data on page 67 for core components.)
Airflow Performance
External Static Pressure (Inches Water Column)
Motor HP
Blower RPM
Nominal
Turns Open
0.0
CFM
0.25
BHP
CFM
0.5
BHP
CFM
0.75
BHP
CFM
1.0
BHP
CFM
1.25
BHP
CFM
1.5
BHP
CFM
BHP
2
1,095
1,220
1,340
4
2
0
1,900
2,200
2,300
1.3
1.5
1.7
1,600
1,960
2,160
1.2
1.4
1.6
1,250
1,610
1,950
1.2
1.3
1.5
850
1,240
1,580
1.1
1.3
1.4
860
1,150
1.2
1.3
800
1.2
-
-
3
1,345
1,535
1,685
4.5
2
0
2,400
2,720
-
2.2
2.7
-
2,250
2,450
2,870
2.2
2.5
3.0
1,970
2,250
2,740
2.1
2.4
2.9
1,570
1,950
2,540
2.0
2.3
2.8
1,170
1,650
2,340
1.9
2.2
2.7
900
1,200
2,090
1.8
2.0
2.5
875
1,800
1.9
2.4
5
1,495
1,675
1,855
6.5
3.5
0
2,850
3,230
3.520
2.7
3.7
4.5
2,610
3,090
3,370
2.6
3.5
4.3
2.380
2,850
3,230
2.5
3.3
4.1
2,090
2,610
3,090
2.4
3.1
3.9
1,710
2,380
2,850
2.2
2.9
3.6
1,330
2,090
2,610
2.1
2.7
3.4
950
1,810
2,380
2.0
2.5
3.2
24
(800) 627-4499
•
Fax: (608) 221-2824
OA
14" X 28"
62"
47"
12"
RA
EA
Left View
38 7/8"
61 3/4"
Top View
61 3/4" Unit
OA
1"
FA
12"
FA
EA
Front View
RA
35 1/4"
OA
43 1/4"
Service Area
EA 12" x 12"
95 7/8" Service Area
E-box
7/8" Dia.
Wiring Entries
12"
1"
12"
Right View
38 7/8"
FA 12" x 12"
61 3/4"
58 1/8"
55 7/8"
RA
14" X 28"
Exhaust Air to outdoors
Outdoor Air intake
Room Air to be exhausted
Fresh Air to inside
8 3/4"
Unit Dimensions
39 3/8"
overall
8 3/4"
3 7/8"
EA:
OA:
RA:
FA:
47"
62"
HE3XINV
37 1/2"
www.RenewAire.com
25
HE4XINH
Indoor Unit
Specifications
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 1,000-4,400 CFM
AHRI 1060 Certified Core: Four L125-00
Airflow Rating Points (for AHRI): 3,000 CFM and 2,250 CFM
Number Motors: Two
G5 Performance
HP
Volts
HZ
Phase
FLA
Min.
Cir.
Amps
Max.
Fuse
Size
2
208-230
208-230
460
575
60
60
60
60
Single
Three
Three
Three
11.3-10.5
6.2-6.2
3.5
2.3
25.4
14.0
7.9
5.2
35
20
15
15
3
208-230
208-230
460
575
60
60
60
60
Sinlge
Three
Three
Three
13.7
9.2-8.6
4.3
3.2
30.8
20.7
9.7
7.2
45
30
15
15
5
208-230
460
575
60
60
60
Three
Three
Three
14.0-13.0
6.5
5.0
31.5
14.6
11.3
45
20
15
CFM
Effectiveness (%)
1,000
2,000
3,000
4,000
80
Control Voltage: 24 VAC
Sensible
Winte
Filters: Eight total, MERV 8, 2” pleated, 20” x 20” nominal size
r Tota
60
Sum
l
mer
40
Weight: 846 lbs (unit), 900 lbs (shipping weight)
Shipping Dimensions: 84” W x 92” L x 46” H
Tota
l
*At AHRI 1060 standard conditions
(See certified data on page 67 for core components.)
Airflow Performance
External Static Pressure (Inches Water Column)
Motor HP
Blower RPM
Nominal
Turns Open
0.0
CFM
0.25
BHP
CFM
0.5
BHP
CFM
0.75
BHP
CFM
1.0
BHP
CFM
1.25
BHP
CFM
1.5
BHP
CFM
BHP
2
1,010
1,210
1,370
4.5
2
0
2,489
2,995
-
0.9
1.6
-
2,200
2,290
-
0.9
1.5
-
1,715
2,430
-
0.8
1.4
-
1,100
2,005
2,600
0.7
1.3
2.0
1,540
2,215
1.2
1.9
1,800
1.7
1,100
1.5
3
1,345
1,535
1,685
4.5
2
0
3,295
3,832
-
2.1
2.9
-
3,145
3,682
-
2.1
2.9
-
2,840
3,480
-
2.0
2.8
-
2,509
3,170
-
1.9
2.6
-
2,116
2,839
3,409
1.8
2.4
3.0
1,747
2,449
3,003
1.6
2.3
2.8
1,135
1,878
2,465
1.5
2.0
2.4
5
1,495
1,675
1,855
6
3
0
3,718
4,223
-
2.7
3.8
-
3,568
4,083
-
2.6
3.7
-
3,345
3,943
-
2.6
3.6
-
3,030
3,659
4,287
2.4
3.4
4.9
2,686
3,364
4,011
2.2
3.2
4.6
2,301
2,994
3,760
2.1
2.9
4.3
1,722
2,490
3,434
1.9
2.7
4.0
26
(800) 627-4499
•
Fax: (608) 221-2824
5 1/2"
22 3/8"
40 3/8"
39"
FA
EA
Left View
82"
Unit Dimensions
E-box
12" x 32" typ
E-box
FA
EA
74 7/8" Control Wiring Inlet
77 7/8" Power Wiring Inlet
18 5/8"
Front View
57 1/4"
Top View
64 1/2"
Service Area
64 1/2" overall
82"
RA
OA
RA
OA
4 1/4"
OA
12" X 40"
Exhaust Air to outdoors
Outdoor Air intake
Room Air to be exhausted
Fresh Air to inside
Right View
RA
12" X 40"
82"
EA:
OA:
RA:
FA:
40 3/8"
HE4XINh
5 1/8"
25 1/2"
www.RenewAire.com
27
116 3/4" Service Area
HE4XINV
Indoor Unit
Specifications
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 1,000-4,400 CFM
AHRI 1060 Certified Core: Four L125-00
Airflow Rating Points (for AHRI): 3,000 CFM and 2,250 CFM
Number Motors: Two
G5 Performance
HP
Volts
HZ
Phase
FLA
Min.
Cir.
Amps
Max.
Fuse
Size
2
208-230
208-230
460
575
60
60
60
60
Single
Three
Three
Three
11.3-10.5
6.2-6.2
3.5
2.3
25.4
14.0
7.9
5.2
35
20
15
15
3
208-230
208-230
460
575
60
60
60
60
Sinlge
Three
Three
Three
13.7
9.2-8.6
4.3
3.2
30.8
20.7
9.7
7.2
45
30
15
15
5
208-230
460
575
60
60
60
Three
Three
Three
14.0-13.0
6.5
5.0
31.5
14.6
11.3
45
20
15
CFM
Effectiveness (%)
1,000
2,000
3,000
4,000
80
Control Voltage: 24 VAC
Sensible
Winte
Filters: Eight total, MERV 8, 2” pleated, 20” x 20” nominal size
r Tota
60
Sum
l
mer
40
Weight: 815 lbs (unit), 875 lbs (shipping weight)
Shipping Dimensions: 45” W x 90” L x 70” H
Tota
l
*At AHRI 1060 standard conditions
(See certified data on page 67 for core components.)
Airflow Performance
External Static Pressure (Inches Water Column)
Motor HP
Blower RPM
Nominal
Turns Open
0.0
CFM
0.25
BHP
CFM
0.5
BHP
CFM
0.75
BHP
CFM
1.0
BHP
CFM
1.25
BHP
CFM
1.5
BHP
CFM
BHP
2
1,010
1,210
1,370
4.5
2
0
2,300
2,800
3,068
0.9
1.5
2.2
1,810
2,350
2,754
0.8
1.4
2.0
1,300
1,950
2,430
0.7
1.3
1.9
1,500
2,082
1.3
1.8
1,050
1,725
1.2
1.7
1,342
1.6
-
-
3
1,345
1,535
1,685
4.5
2
0
3,042
3,452
-
2.0
2.7
-
2,705
3,226
-
1.9
2.6
-
2,341
2,955
-
1.8
2.5
-
1,983
2,696
3,148
1.7
2.3
2.9
1,611
2,422
2,884
1.6
2.2
2.8
1,211
2,093
2,595
1.5
2.0
2.6
1,722
2,269
1.9
2.4
5
1,495
1,675
1,855
6
3
0
3,348
3,896
-
2.7
3.9
-
3,114
3,688
-
2.6
3.7
-
2,820
3,466
4,229
2.4
3.6
4.9
2,549
3,232
3,979
2.3
3.4
4.6
2,268
2,972
3,700
2.2
3.2
4.3
1,917
2,694
3,430
2.1
3.0
4.0
1,523
2,392
3,178
1.9
2.8
3.8
28
(800) 627-4499
•
Fax: (608) 221-2824
62"
14" X 34"
47"
8 1/2"
RA
FA
81 1/2" Unit
EA
12" X 32"
EA
Left View
OA
81 3/8"
38 7/8"
1"
Top View
OA
115 1/2" Service Area
Unit Dimensions
39 3/8"
with flanges
3 7/8"
EA
OA
Front View
35 1/4"
FA
RA
E-box
12" X 32"
Right View
FA
RA
81 3/8"
75 1/2"
38 3/4"
1"
14" X 34"
Exhaust Air to outdoors
Outdoor Air intake
Room Air to be exhausted
Fresh Air to inside
7/8" Dia.
Wiring Entries
EA:
OA:
RA:
FA:
8 1/2"
47"
62 1/4"
HE4XINV
37 1/2"
www.RenewAire.com
29
HE6XIN
Indoor Unit
Specifications
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 1,500-6,500 CFM
AHRI 1060 Certified Core: Six L125-00
Airflow Rating Points (for AHRI): 4,500 CFM and 3,375 CFM
Number Motors: Two
G5 Performance
Effectiveness (%)
Volts
HZ
Phase
FLA
Min.
Cir.
Amps
Max.
Fuse
Size
5
208-230
460
575
60
60
60
Three
Three
Three
14.2-13.0
6.5
5.0
32.6
14.9
11.3
45
20
15
7.5
208-230
460
575
60
60
60
Three
Three
Three
20.9-19.2
9.6
7.6
47.0
21.6
17.1
70
30
25
Control Voltage: 24 VAC
CFM
3,000
HP
4,000
5,000
Filters: Twelve total, MERV 8, 2” pleated, 20” x 20” nominal size
6,000
Weight: 2,340 lbs (unit), 2,640 lbs (shipping weight)
80
Shipping Dimensions: 85” W x 114” L x 85” H
Sensible
Winter
60
Total
Summ
er To
tal
40
*At AHRI 1060 standard conditions
(See certified data on page 67 for core components.)
Airflow Performance
External Static Pressure (Inches Water Column)
Motor HP
Blower RPM
Nominal
Turns Open
0.0
CFM
0.25
BHP
CFM
0.5
BHP
CFM
0.75
BHP
CFM
1.0
BHP
CFM
1.25
BHP
CFM
1.5
BHP
CFM
BHP
5
1,460
1,610
1,725
4.5
2
0
5,005
5,550
-
3.2
4.2
-
4,800
5,375
-
3.2
4.2
-
4,650
5,250
-
3.1
4.1
-
4,475
5,100
5,525
3.0
4.1
5.0
4,200
4,900
5,475
2.9
4.0
5.0
4,000
4,650
5,200
2.8
3.9
4.9
3,750
4,500
5,050
2.8
3.8
4.8
7.5
1,560
1,740
1,865
4.5
2
0
5,275
5,950
6,500
3.7
5.0
6.5
5,200
5,825
6,350
3.6
5.0
6.5
4,900
5,625
6,225
3.5
4.9
6.4
4,775
5,490
6,125
3.5
4.9
6.4
4,550
5,325
5,910
3.4
4.8
6.3
4,350
5,125
5,825
3.3
4.7
6.2
4,125
4,950
5,625
3.3
4.7
6.1
30
(800) 627-4499
•
Fax: (608) 221-2824
62"
RIGHT VIEW
108 1/2" Base
EA
RA
BACK VIEW
9 1/2"
49"
OA
24"
typ
78 1/4" Overall
Core
Access
INDOOR UNITS: EA BLOWER Outlet is 18" x 24".
24" x 36" Duct Flange is also supplied. Field install only in location shown.
Power and
Control
Wiring
Entries
7/8" Dia.
Unit Dimensions
55"
36"
151 1/2" Service Area
34"
Service Area
HE6XIN
36"
22"
www.RenewAire.com
31
LEFT VIEW
62"
18"
108 1/2" Base
FA
112 3/4" Unit Roof
TOP VIEW
EA
148 1/4" Service Area
24"
77"
4"
9"
Exhaust Air to outdoors
Outdoor Air intake
Room Air to be exhausted
Fresh Air to inside
39 1/2" Min.
Clearance
FRONT VIEW
85 1/2" Unit Roof
FA BLOWER Outlet is 18" x 24".
24" x 36" Duct Flange is also supplied.
Field install only in location shown.
Front Views at 0.5X:
BLOWER ROTATION
Power and Control Wiring
Entries
EA:
OA:
RA:
FA:
HE8XIN
Indoor Unit
Specifications
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 2,000-8,000 CFM
AHRI 1060 Certified Core: Eight L125-00
Airflow Rating Points (for AHRI): 6,000 CFM and 4,500 CFM
Number Motors: Two
Effectiveness (%)
2,000
4,000
6,000
Max.
Fuse
Size
Three 14.2-13.0
Three
6.5
5.0
Three
32.6
14.9
11.3
45
20
15
60
60
60
Three 20.9-19.2
Three
9.6
Three
7.6
47.0
21.6
17.1
70
30
25
60
60
60
Three 29.0-26.8
Three
13.4
Three
10.0
65.3
30.2
22.5
90
45
35
Volts
HZ
Phase
5
208-230
460
575
60
60
60
7.5
208-230
460
575
10
208-230
460
575
G5 Performance
CFM
Min.
Cir.
Amps
HP
8,000
FLA
Control Voltage: 24 VAC
80
Filters: Sixteen total, MERV 8, 2” pleated, 20” x 20” nominal size
Sensible
Winte
Weight: 2,525 lbs (unit), 2,825 lbs (shipping weight)
r Tota
60
l
Summ
Shipping Dimensions: 85” W x 114” L x 85” H
er To
tal
40
*At AHRI 1060 standard conditions
(See certified data on page 67 for core components.)
Airflow Performance
External Static Pressure (Inches Water Column)
Motor HP
Blower RPM
Nominal
Turns Open
0.0
CFM
0.25
BHP
CFM
0.5
BHP
CFM
0.75
BHP
CFM
1.0
BHP
CFM
1.25
BHP
CFM
1.5
BHP
CFM
BHP
5
1,460
1,610
1,725
4.5
2
0.5
5,575
6,200
6,550
3.2
4.3
5.0
5,425
6,010
6,380
3.2
4.3
5.0
5,200
5,875
6,210
3.2
4.2
5.0
5,000
5,700
6,100
3.2
4.2
5.0
4,775
5,500
5,880
3.1
4.2
4.9
4,550
5,325
5,730
3.0
4.1
4.8
4,270
5,125
5,510
2.9
4.1
4.8
7.5
1,560
1,740
1,865
4.5
2
0
6,000
6,700
-
3.9
5.3
-
5,850
6,575
-
3.9
5.3
-
5,650
6,400
-
3.8
5.3
-
5,475
6,300
6,800
3.8
5.3
7.5
5,275
6,125
6,675
3.8
5.3
7.5
5,100
5,950
6,500
3.7
5.2
7.5
4,875
5,750
6,375
3.7
5.2
7.4
10
1,810
2,020
2,105
4.5
2
1
7,000
7,850
-
6.1
8.5
-
6,875
7,745
-
6.1
8.5
-
6,750
7,625
7,950
6.1
8.5
9.6
6,600
7,450
7,800
6.0
8.4
9.6
6,425
7,350
7,725
6.0
8.4
9.6
6,275
7,200
7,600
6.0
8.3
9.5
6,100
7,050
7,450
5.9
8.3
9.5
32
(800) 627-4499
•
Fax: (608) 221-2824
62"
RIGHT VIEW
108 1/2" Base
EA
RA
BACK VIEW
9 1/2"
49"
OA
24"
typ
78 1/4" Overall
Core
Access
INDOOR UNITS: EA BLOWER Outlet is 18" x 24".
24" x 36" Duct Flange is also supplied. Field install only in location shown.
Power and
Control
Wiring
Entries
7/8" Dia.
Unit Dimensions
55"
36"
151 1/2" Service Area
34"
Service Area
HE8XIN
36"
22"
www.RenewAire.com
33
LEFT VIEW
62"
18"
108 1/2" Base
FA
112 3/4" Unit Roof
TOP VIEW
EA
148 1/4" Service Area
24"
77"
4"
9"
Exhaust Air to outdoors
Outdoor Air intake
Room Air to be exhausted
Fresh Air to inside
39 1/2" Min.
Clearance
FRONT VIEW
85 1/2" Unit Roof
FA BLOWER Outlet is 18" x 24".
24" x 36" Duct Flange is also supplied.
Field install only in location shown.
Front Views at 0.5X:
BLOWER ROTATION
Power and Control Wiring
Entries
EA:
OA:
RA:
FA:
Commercial
OutDOOR Products
• Many airflow orientation options.
• Weatherized cabinets with hoods for
outdoor applications.
• Wide range of airflow and static capacities.
• Easy installation and service.
• AHRI certified performance data for
efficiency and cross leakage.
• UL tested flammability and smoke
generation that meets NFPA 90A and
90B test standards for commercial
applications.
• Ten year core warranty.
RenewAire means Trouble-Free ERV.
EA:
OA:
RA:
FA:
Contact RenewAire for other application schematics.
34
(800) 627-4499
•
Fax: (608) 221-2824
Exhaust Air to outdoors
Outdoor Air intake
Room Air to be exhausted
Fresh Air to inside
Packaged Rooftop Energy Recovery Ventilators:
EV450RT, HE1XRT, HE2XRT, HE3XRT, HE4XRT, HE6XRT & HE8XRT
Part I - General
A. Product Specification
1.Energy Recovery Ventilator (ERV) shall be a packaged unit as manufactured
by RenewAire and shall transfer both heat and humidity using static plate
core technology.
B. Quality Assurance
1.The energy recovery cores used in these products shall be third
party Certified by AHRI under its Standard 1060 for Energy Recovery
Ventilators. AHRI published certifications shall confirm manufacture’s
published performance for airflow, static pressure, temperature and total
effectiveness, purge air (OACF) and exhaust air leakage (EATR). Products
that are not currently AHRI Certified will not be accepted.
2. No condensate drain pans or drains shall be allowed and unit shall
be capable of operating in both winter and summer conditions without
generating condensate.
3. The unit case shall be constructed of G90 galvanized, 20-gauge steel,
with lapped corners and zinc plated screw fasteners. The unit roof shall be
one piece or have watertight standing seam joints and shall overlap wall
panels and doors in order to positively shed water.
4. Access doors shall provide easy access to blowers, ERV cores and filters.
Doors shall have an airtight compression seal using closed cell foam gaskets
rated for outdoor exposure.
5. Weatherhoods shall be screened to exclude birds and animals. Inlet
weatherhoods shall be sized to maintain inlet velocities below 500 fpm,
and equipped with rain excluder baffles.
2. Manufacturer shall be able to provide evidence of independent testing
of the core by Underwriters Laboratory (UL), verifying a maximum flame
spread index (FSI) of 25 and a maximum smoke developed index (SDI) of 50
thereby meeting NFPA 90A and NFPA 90B requirements for materials in a
compartment handling air intended for circulation through a duct system.
The method of test shall be UL Standard 723.
6. Case walls and doors shall be insulated with 1 inch, 4 pound density, foil/
scrim faced, high-density fiberglass board insulation, providing a cleanable
surface and eliminating the possibility of exposing the fresh air to glass fibers.
3. Unit shall be Listed under UL 1812 Standard for Ducted Air to Air Heat
Exchangers (Note that a few low volume product or product configurations
are not UL Listed). Units intended for “Outdoor Use” shall be listed using
the specific UL requirements for rain penetration, corrosion protection and
seal durability and shall be so labeled.
8. Unit shall have single-point power connection and a single-point 24
VAC contactor control connection (Except Inverter Ready units that have
terminal connections for an independent inverter for each airstream).
4. The ERV core shall be warranted to be free of manufacturing defects and
to retain its functional characteristics, under circumstances of normal use,
for a period of ten years from the date of purchase. The balance-of-unit
shall be warranted to be free of manufacturing defects and to retain its
functional characteristics, under circumstances of normal use, for a period
of two years from the date of purchase.
Part II – Performance
A. Energy Transfer
The ERV shall be capable of transferring both sensible and latent energy
between airstreams. Latent energy transfer shall be accomplished by direct
water vapor transfer from one airstream to the other, without exposing
transfer media in succeeding cycles directly to the exhaust air and then to
the fresh air.
B. Passive Frost Control
7. The ERV cores shall be protected by a MERV-8 rated, 2” nominal, pleated,
disposable filter in both airstreams.
9. Blower motors shall be EPACT compliant for energy efficiency and be
thermally protected or supplied with external starters.
10. Blowers shall be quiet running, forward curve type and be either direct
drive or belt drive. HE6X and HE8X units use backward incline, belt drive
blower packages. Belt drive motors shall be provided with adjustable
pulleys and motor mounts allowing for proper belt tensioning.
B. Options (Select options based on application requirements)
1. Provide unit and duct connection orientation per project schedule.
2. Provide double wall construction with 24-gauge galvanized steel liner.
3. Units are available single or three phase at a full range of operating
voltages. See project schedule.
4. Provide motor horsepower as specified in project schedule.
The ERV core shall perform without condensing or frosting under normal
operating conditions (defined as outside temperatures above -10°F and
inside relative humidity below 40%). Occasional more extreme conditions
shall not affect the usual function, performance or durability of the core.
No condensate drains will be allowed.
5. Provide “inverter-ready” units which include shielded power wiring
and terminal connections for inverters (inverters provided and installed
by others).
C. Continuous Ventilation
7. Provide factory installed non-fused disconnects.
Unit shall have the capacity to operate continuously without the need for bypass,
recirculation, pre-heaters or defrost cycles under normal operating conditions.
D. Positive Airstream Separation
Water vapor transfer shall be through molecular transport by hydroscopic
resin and shall not be accomplished by “porous plate” mechanisms. Exhaust
and fresh airstreams shall travel at all times in separate passages, and
airstreams shall not mix.
E. Laminar Flow
Airflow through the ERV core shall be laminar over the products entire
operating airflow range, avoiding deposition of particulates on the interior
of the energy exchange plate material.
Part III – Product
6. Provide factory installed fused disconnects.
8. Provide factory installed transformer/relay package to supply a 24VAC
power source.
9. Provide factory installed filter monitors for each airstream.
10. Provide 14 inch high, non-pitched roof curbs as available from the
factory. Pitched curbs, vibration curbs, seismic curbs and other custom
curbs are available directly from curb manufacturer.
11. RTC (RoofTop Connect) units shall have return air and fresh air
ducts configured to permit direct tie-in to rooftop air handlers using
factory offered transition piece. (See separate specification for factory
transition availability.)
12. Provide high wind tie-down kit.
A. Construction
1. The energy recovery component shall be of fixed-plate cross-flow
construction, with no moving parts.
35
www.RenewAire.com
EV450RT
Outdoor Unit
Specifications
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 240-550 CFM
AHRI 1060 Certified Core: One L85
Airflow Rating Points (for AHRI): 450 CFM and 338 CFM
Motors: One, 0.6 hp (Single Phase) One, 0.5 hp (Three Phase)
G5 Performance
Airflow
CFM
ESP in
H 20
Watts
1P
3P
Temp
EFF%
Total EFF%
Winter/Summer*
240
1.00
425
243
80
75/66
338
0.85
474
313
77
71/61
380
0.75
496
345
75
69/59
450
0.50
534
412
73
66/56
500
0.25
563
461
71
64/54
550
0.00
593
516
70
62/52
600
-0.25
623
572
68
60/50
V
HZ
Phase
FLA
115
60
Single
7.0
208-230
60
Single
3.5
277
60
Single
2.4
208-230
60
Three
1.7-1.5
460
60
Three
0.8
Control Voltage: 24 VAC
Filters: Two total, MERV 8, 2” pleated, 14” x 20” nominal size
Weight: 185 lbs (unit), 235 lbs (shipping weight)
Shipping Dimensions: 48” W x 90” L x 25” H (on pallet)
*At AHRI 1060 standard conditions
(See certified data on page 67 for core components.)
Dimensions
8 3/4
5 1/2
13 1/8
RA
10 1/4
4 1/2
2 3/4
2 5/8
11 3/4
FA
EA
OA
TOP VIEW WITH
DOOR OFF
EBOX
PWR AND
CONTROL WIRING
DRILL HERE
OR THRU BOTTOM
FILTERS
37 1/2
2 7/8
3 1/8
4 3/4
19 1/4
OA
EA
LEFT VIEW
33 7/8
RIGHT VIEW
3 1/8
1
1
4 3/8
12 3/8
FA
FRONT
VIEW
47 7/8
74 7/8
36
(800) 627-4499
•
Fax: (608) 221-2824
RA
EV450RT
Application options
Standard Roof Curb Shown (available option). Curbs for sloped roofs or
metal roofing are available on a custom basis from RenewAire or from
local curb fabricators.
For horizontal connection of either the Fresh Air duct or the Return Air
duct, stack the optional RTF/RTR Adapter on the Standard Roof Curb.
Duct openings to be field cut into adapter. Opening location and size
is flexible.
The RTH/RTC Adapter allows horizontal connection of both the Fresh Air
and the Return Air ducts. It is also possible to connect the adapter
directly to the return plenum of most Rooftop Units (openings must be
cut into RTU). Duct openings to be field cut into adapter.
Opening location and size is flexible.
EA:
OA:
RA:
FA:
Exhaust Air to outdoors
Outdoor Air intake
Room Air to be exhausted
Fresh Air to inside
37
www.RenewAire.com
HE1XRT
Outdoor Unit
Specifications
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 250-870 CFM
AHRI 1060 Certified Core: One L125-00
Airflow Rating Points (for AHRI): 750 CFM and 560 CFM
Number Motors: Two
V
HZ
Phase
FLA
Min. Cir.
Amps
Max.
Fuse Size
115
60
Single
8.6
19.4
25
208-230
60
Single
4.3
9.7
15
277
60
Single
2.4
5.4
15
208-230
60
Three
2.1
5.2
15
460
60
Three
1.1
2.6
15
G5 Performance
CFM
Effectiveness (%)
250
500
Control Voltage: 24 VAC
750
1,000
Filters: Two total, MERV 8, 2” pleated, 20” x 20” nominal size
Weight: 250 lbs (unit), 330 lbs (shipping weight)
80
Sensible
Winter
60
Summ
Total
er To
Shipping Dimensions: 31” W x 76” L x 45” H
Options: Controls (see pages 64 & 65)
Roof curb
Alternate duct connections
tal
40
*At AHRI 1060 standard conditions
(See certified data on page 67 for core components.)
Base Type/Airflow Orientations
RTV
RTF
EA
OA
RTR
EA
OA
OA
EA
FA
FA
FA
OA
RA
RA
RA
FA
RA
RTH
EA
Airflow Performance
Motor HP
Phase
External Static Pressure (Inches Water Column)
0.0
0.25
0.5
0.75
1.0
1.25
1.5
0.75 (Two DD)
Single Phase
950 CFM
1,630 Watts
880 CFM
1,550 Watts
820 CFM
1,475 Watts
775 CFM
1,430 Watts
730 CFM
1,385 Watts
650 CFM
1,300 Watts
540 CFM
1,200 Watts
0.75 (Two DD)
Three Phase
950 CFM
1,200 Watts
880 CFM
1,100 Watts
820 CFM
1,020 Watts
760 CFM
980 Watts
660 CFM
890 Watts
560 CFM
800 Watts
450 CFM
700 Watts
38
(800) 627-4499
•
Fax: (608) 221-2824
www.RenewAire.com
39
4 7/8"
LEFT VIEW
EA
9"
3"
10 3/8"
17 3/8" Control
19 1/4" Power
RTH, RTR
ONLY
4"
Power Wiring Inlet
7/8" Dia.
Control Wiring Inlet
7/8" Dia.
FA
FA (RTH,RTR)
12" x 12"
22 1/2"
56 1/8"
40 1/4"
Unit Dimensions
HE1XRT
RTV, RTF
ONLY
FA
FRONT
VIEW
TOP VIEW
Service Area
RA
63 7/8"
55"
44 1/4"
29 1/2"
14 3/4"
RTV, RTR
ONLY
RA
OA
RA (RTH,RTF)
12" x 12"
RTH, RTF
ONLY
OA
RA (RTV,RTR)
12" x 12"
FA (RTV,RTF)
12" x 12"
RIGHT VIEW
4 3/8"
4 7/8"
EA:
OA:
RA:
FA:
CURB1X
Exhaust Air to outdoors
Outdoor Air intake
Room Air to be exhausted
Fresh Air to inside
HE1XRTC
Outdoor Unit
Specifications
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 500-1,000 CFM
AHRI 1060 Certified Core: One L125-00
Airflow Rating Points (for AHRI): 750 CFM and 560 CFM
Number Motors: Two
G5 Performance
CFM
Effectiveness (%)
300
500
V
HZ
Phase
FLA
Min. Cir.
Amps
Max.
Fuse Size
115
60
Single
8.6
19.4
25
208-230
60
Single
4.3
9.7
15
277
60
Single
2.4
5.4
15
208-230
60
Three
2.1
5.2
15
460
60
Three
1.1
2.6
15
Control Voltage: 24 VAC
700
900
Filters: Two total, MERV 8, 2” pleated, 20” x 20” nominal size
Weight: 300 lbs (unit), 375 lbs (shipping weight)
80
Shipping Dimensions: 40” W x 87” L x 45” H
Sensible
Winte
r Tota
60
Summ
l
er Tot
al
40
*At AHRI 1060 standard conditions
(See certified data on page 67 for core components).
Airflow Performance
Damper
Position
Static Pressure in Adjacent Air Handler (Inches Water Column)
Total Watts
-0.5
1 Phase
3 Phase
-0.25
0.0
FA
EA
+0.25
FA
EA
+0.5
EA
FA
EA
1,035
900
985
950
940
985
FA
885
1,045
EA
FA
835
100% Open
1,295
1,155
855
65% Open
1,285
1,140
785
980
820
945
855
900
890
855
935
810
55% Open
1,275
1,130
775
965
805
920
840
875
865
835
900
790
45% Open
1,265
1,120
750
920
775
875
805
935
830
790
860
750
35% Open
1,265
1,110
695
860
730
820
760
775
790
740
820
700
25% Open
1,265
1,100
625
780
660
750
685
715
715
680
750
650
15% Open
1,260
1,085
575
585
615
630
650
665
685
705
730
745
40
(800) 627-4499
•
Fax: (608) 221-2824
LEFT VIEW
EA
9"
OA
OA
21 1/8"
OA
Access to
Electrical
Components,
OA filter
Access to blowers
22 1/2"
56 1/8"
Control Wire In
7/8" Dia.
Power Wire In
7/8" Dia.
Unit Dimensions
40 1/4"
FRONT VIEW
Shown with Leveling Legs
(shipped loose)
51"
Service Area
EA
46 3/8"
Lifting Lugs
72"
9"
HE1XRTC
RIGHT VIEW
RA
FA
TOP VIEW
FA
RA
19 7/8"
Lifting Lugs
RA
FA
16"
14 1/2" to 17 1/2"
height adjustment
3 1/2"
Exhaust Air to outdoors
Outdoor Air intake
Room Air to be exhausted
Fresh Air to inside
6 5/8"
EA:
OA:
RA:
FA:
11"
11"
www.RenewAire.com
41
HE2XRT
Outdoor Unit
Specifications
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 500-2,000 CFM
AHRI 1060 Certified Core: Two L125-00
Airflow Rating Points (for AHRI): 1,500 CFM and 1,120 CFM
Number Motors: Direct Drive (DD) Four, Belt Drive (BD) Two
Drive
HP
Volts
HZ
Phase
FLA
Min.
Cir.
Amps
Max.
Fuse
Size
DD
0.75
115
208-230
277
208-230
460
60
60
60
60
60
Single
Single
Single
Three
Three
8.6
4.3
2.4
2.1
1.1
36.6
18.3
10.2
9.8
4.9
45
20
15
15
15
BD
1.5
208-230
208-230
460
575
60
60
60
60
Single
Three
Three
Three
9.3-9.0
4.8-4.8
2.4
1.8
20.9
10.8
5.4
4.1
30
15
15
15
BD
2
208-230
208-230
460
575
60
60
60
60
Single
Three
Three
Three
11.3-10.5
6.2-6.2
3.1
2.3
25.4
14.0
7.0
5.2
35
20
15
15
G5 Performance
CFM
Effectiveness (%)
500
1,000
1,500
2,000
80
Sensible
Winte
60
Control Voltage: 24 VAC
r Tota
Summ
l
Filters: Four total, MERV 8, 2” pleated, 20” x 20” nominal size
er To
tal
Weight: 488 lbs (unit), 525 lbs (shipping weight)
40
Shipping Dimensions: 51” W x 76” L x 45” H
*At AHRI 1060 standard conditions
(See certified data on page 67 for core components).
Base Type/Airflow Orientations
RTV
RTF
EA
OA
RTR
EA
RA
OA
EA
FA
OA
RA
FA
FA
RA
RA
FA
RTH
EA
OA
Airflow Performance
External Static Pressure (Inches Water Column)
Motor HP
Blower RPM
Nominal
Turns
Open
0.0
0.25
0.5
0.75
1.0
1.25
0.75 (Four DD)
Single Phase
N/A
N/A
N/A
N/A
1,770 CFM
2,220 Watts
1,680 CFM
2,145 Watts
1,555 CFM
2,015 Watts
1,375 CFM
1,825 Watts
1,110 CFM
1,560 Watts
760 CFM
1,195 Watts
0.75 (Four DD)
Three Phase
N/A
N/A
N/A
N/A
1,760 CFM
2,300 Watts
1,670 CFM
2,200 Watts
1,550 CFM
2,050 Watts
1,375 CFM
1,825 Watts
1,120 CFM
1,530 Watts
850 CFM
1,375 Watts
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
1.5 (BD)
1,000
1,230
1,420
4.5
2
0
1,378
1,694
1,956
0.5
0.9
1.4
1,175
1,550
1,850
0.5
0.9
1.4
900
1,335
1,680
0.4
0.8
1.2
635
1,125
1,475
0.4
0.7
1.2
1,000
1,300
0.7
1.1
500
1,200
0.6
1.1
930
0.9
2 (BD)
1,220
1,470
1,660
4.5
2
0
1,681
2,025
-
0.9
1.6
-
1,530
1,925
-
0.9
1.5
-
1,315
1,750
2,000
0.7
1.4
2.0
1,100
1,575
1,900
0.7
1.3
1.9
975
1,375
1,750
0.6
1.2
1.8
430
1,275
1,570
0.6
1.2
1.7
1,125
1,475
1.1
1.7
Note: Brake Horse Power (BHP) is for one blower motor package only.
42
(800) 627-4499
•
Fax: (608) 221-2824
1.5
-
-
500 CFM
950 Watts
www.RenewAire.com
43
7 1/4"
76 1/8"
LEFT VIEW
EA
4" Wiring Inlet
42 1/4"
RTH, RTR
ONLY
EA
25 1/2"
Curb
Center
RTV, RTF
ONLY
FA
Service Area
15 3/4"
Power Wiring Inlet
7/8" Dia.
Control Wiring Inlet
7/8" Dia.
FA
3 3/4"
37 3/8"
power
10 5/8"
34 7/8"
control
FA (RTV, RTF)
10" X 24"
FA (RTH, RTR)
14" X 24"
4 5/8"
51 1/8"
RTV, RTR
ONLY
RA
72 3/8"
RTH, RTF
ONLY
FRONT
VIEW
RA
OA
TOP VIEW
15 3/4"
OA
RA (RTV RTR)
10" X 24"
20 1/8"
Curb
Center
Unit Dimensions
3"
Top of
Curb
HE2XRT
40 1/4"
43 1/4"
RA (RTH, RTF)
14" X 24"
RIGHT
VIEW
39 3/8"
EA:
OA:
RA:
FA:
CURB2X
Exhaust Air to outdoors
Outdoor Air intake
Room Air to be exhausted
Fresh Air to inside
HE2XRTC
Outdoor Unit
Specifications
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 1,000-1,700 CFM
AHRI 1060 Certified Core: Two L125-00
Airflow Rating Points (for AHRI): 1,500 CFM and 1,120 CFM
Number Motors: Two, Belt Drive
G5 Performance
Max.
Fuse
Size
Single 11.3-10.5
25.4
35
Three
Three
Three
14.0
7.0
5.2
20
15
15
Volts
HZ
Phase
BD
2
208-230
60
BD
2
208-230
460
575
60
60
60
FLA
6.2-6.2
3.1
2.3
Control Voltage: 24 VAC
CFM
500
Min.
Cir.
Amps
HP
1,000
Filters: Four total, MERV 8, 2” pleated, two 20” x 20” nominal size,
1,500
and two 14” x 20” nominal size
2,000
Effectiveness (%)
Weight: 538 lbs (unit), 575 lbs (shipping weight)
80
Shipping Dimensions: 51” W x 76” L x 45” H
Sensible
Winte
60
r Tota
Summ
l
er To
tal
40
*At AHRI 1060 standard conditions
(See certified data on page 67 for core components).
Airflow Performance
Static Pressure in Adjacent Air Handler (Inches Water Column)
Blower RPM
Nominal
Turns Open
1,420
0
1,700
1.8
1,850
1.9
-
1,360
1
1,540
1.7
1,720
1.8
1,860
1.9
1,920
2.0
1,980
2.0
1,300
2
1,375
1.5
1,600
1.7
1,740
1.8
1,800
1.8
1,860
1.9
1,240
3
1,240
1.4
1,440
1.6
1,625
1.7
1,690
1.7
1,740
1.7
1,180
4
1,080
1.3
1,300
1.4
1,500
1.5
1,575
1.6
1,640
1.6
1,675
0
-
-
1,630
2.0
1,575
2.0
1,465
1.9
1,595
1
1,720
2.0
1,620
2.0
1,530
1.9
1,440
1.8
1,355
1.7
1,515
2
1,630
1.9
1,520
1.8
1,430
1.8
1,355
1.7
1,230
1.6
1,435
3
1,530
1.8
1,430
1.7
1,320
1.7
1,250
1.6
1,135
1.5
4
1,415
1.6
1,310
1.6
1,225
1.5
1,150
1.5
1,035
1.4
-0.5
CFM
Exhaust Air
Fresh Air
1,355
-0.25
BHP
CFM
-
-
0.0
BHP
CFM
44
(800) 627-4499
•
Fax: (608) 221-2824
+0.25
BHP
CFM
-
-
+0.5
BHP
CFM
-
-
BHP
-
www.RenewAire.com
45
39 1/4"
RA
FA
BACK VIEW
OA
75 1/8"
57 3/4"
OA
101" Service Area
EA
RA
FA
FRONT VIEW
59" C-C
75 1/8"
57 3/4"
shown with leveling legs
(shipped loose)
Control Wiring In
7/8" Dia.
EA
60 3/8"
42 3/8"
40 1/8"
52 3/4"
Lifting Lugs
each corner
76"
4 1/2"
TOP VIEW and
service area
RA
39 1/4"
37 1/4"
Lifting
Lugs
LEFT VIEW
Power Wiring In
7/8" Dia.
EA
Filter Access
EA
FA
39 1/4"
OA
21 3/4"
11 1/8" typ
Unit Dimensions
39 1/4"
37 1/4"
32"
EA:
OA:
RA:
FA:
7 1/8"
HE2XRTC
RIGHT VIEW
7 3/4" to 10 1/2"
height adjustment
RA
FA
42 1/4"
29"
Exhaust Air to outdoors
Outdoor Air intake
Room Air to be exhausted
Fresh Air to inside
1 7/8"
HE3XRT
Outdoor Unit
Specifications
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 750-3,000 CFM
AHRI 1060 Certified Core: Three L125-00
Airflow Rating Points (for AHRI): 2,250 CFM and 1,690 CFM
Number Motors: Two
HP
Volts
HZ
Phase
FLA
Min.
Cir.
Amps
Max.
Fuse
Size
2
208-230
208-230
460
575
60
60
60
60
Single
Three
Three
Three
11.3-10.5
6.2-6.2
3.1
2.3
25.4
14.0
7.0
5.2
35
20
15
15
3
208-230
208-230
460
575
60
60
60
60
Single
Three
Three
Three
13.7
9.2-8.6
4.3
3.2
30.8
20.7
9.7
7.2
45
30
15
15
5
208-230
460
575
60
60
60
Three
Three
Three
14.0-13.0
6.5
5.0
31.5
14.6
11.3
45
20
15
G5 Performance
CFM
Effectiveness (%)
1,500
2,000
2,500
3,000
80
Control Voltage: 24 VAC
Sensible
Winter
60
Filters: Six total, MERV 8, 2” pleated, 20” x 20” nominal size
Total
Summ
Weight: 726 lbs (unit), 755 lbs (shipping weight)
Shipping Dimensions: 72” W x 84” L x 49” H
er To
tal
40
*At AHRI 1060 standard conditions
(See certified data on page 67 for core components).
Base Type/Airflow Orientations
RTV
RTF
EA
OA
RTR
EA
RA
OA
EA
FA
OA
RA
FA
FA
RA
RA
FA
RTH
EA
OA
Airflow Performance
External Static Pressure (Inches Water Column)
Motor HP
Blower RPM
Nominal
Turns Open
0.0
CFM
0.25
BHP
CFM
0.5
BHP
CFM
0.75
BHP
CFM
1.0
BHP
CFM
1.25
BHP
CFM
1.5
BHP
CFM
BHP
2
1,095
1,220
1,340
4
2
0
2,040
2,340
2,590
1.3
1.5
1.8
1,760
2,110
2,370
1.3
1.4
1.7
1,370
1,790
2,130
1.2
1.3
1.6
920
1,380
1,760
1.1
1.2
1.4
940
1,310
1.2
1.3
980
1.2
-
-
3
1,345
1,535
1,685
4.5
2
0
2,420
2,850
-
2.3
2.8
-
2,280
2,760
-
2.2
2.7
-
2,090
2,570
-
2.1
2.6
-
1,760
2,380
2,660
2.0
2.5
2.9
1,280
2,090
2,470
1.9
2.4
2.7
860
1,810
2,280
1.9
2.2
2.6
1,330
2,000
2.1
2.4
5
1,495
1,675
1,855
6.5
3.5
0
2,850
3,280
-
3.1
3.8
-
2,710
3,140
-
3.0
3.7
-
2.520
2,990
3,470
2.9
3.5
4.9
2,280
2,800
3,330
2.8
3.3
4.7
2,040
2,610
3,140
2.7
3.1
4.5
1,620
2,380
3,040
2.5
2.9
4.4
1,140
2,090
2,760
2.4
2.7
4.0
46
(800) 627-4499
•
Fax: (608) 221-2824
40 3/8"
FA
Left View
38 3/4"
12"
12" X 12"
FA Outlet
(RTH, RTR)
5 1/2"
21 3/4"
EA
55 1/8" Control Wire Inlet
58 1/8" Power Wire Inlet
Wiring In
7/8" Dia.
E-box
EA Outlet
FA
(RTV, RTF Only)
12" x 12"
EA
30 1/8"
Curb Center
FA
17 1/2"
Front View
2"
57"
89 3/4" Overall
55 1/4" lift lugs
RA
9"
RA
OA
OA Inlet
Right View
4 1/8"
60 1/4"
60 1/4" lift lugs
62 1/4"
Overall
97"
Service
Area
RA
(RTV, RTR Only)
11" x 34"
Top View
18 3/8"
64 1/2" Service Area
FA
28 3/4"
Curb Center
RA
Unit Dimensions
18 5/8"
14 3/4"
8 1/8"
4"
Top of Curb
HE3XRT
40 3/8"
34" X 12"
RA Inlet
(RTH, RTF)
5 1/8"
www.RenewAire.com
47
EA:
OA:
RA:
FA:
CURB3X
Exhaust Air to outdoors
Outdoor Air intake
Room Air to be exhausted
Fresh Air to inside
HE3XRTC
Specifications
Outdoor Unit
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 1,700-2,500 CFM
AHRI 1060 Certified Core: Three L125-00
Airflow Rating Points (for AHRI): 2,250 CFM and 1,690 CFM
Number Motors: Two
Volts
HZ
Phase
FLA
Min.
Cir.
Amps
Max.
Fuse
Size
3
208-230
60
Single
13.7-13.7
30.8
45
3
208-230
460
575
60
60
60
Three
Three
Three
9.2-8.6
4.4
3.2
20.7
9.9
7.2
30
15
15
Control Voltage: 24 VAC
G5 Performance
Filters: Five total, MERV 8, 2” pleated, three 20” x 20”
and two 16” x 25” nominal size
CFM
1,500
Effectiveness (%)
HP
2,000
2,500
3,000
Weight: 775 lbs (unit), 830 lbs (shipping weight)
Shipping Dimensions: 72” W x 84” L x 50” H
80
Sensible
Winter
60
Total
Summ
er To
tal
40
*At AHRI 1060 standard conditions
(See certified data on page 67 for core components).
Airflow Performance
Static Pressure in Adjacent Air Handler (Inches Water Column)
Blower RPM
Nominal
Turns Open
-0.5
CFM
Exhaust Air
Fresh Air
-0.25
BHP
CFM
0.0
BHP
CFM
+0.25
BHP
CFM
+0.5
BHP
CFM
BHP
1,520
0
-
-
-
-
-
-
-
-
-
-
1,465
1
2,130
2.9
-
-
-
-
-
-
-
-
1,405
2
2,000
2.5
2,245
2.8
2,455
3.0
-
-
-
-
1,345
3
1,915
2.3
2,135
2.6
2,345
2.7
2,475
2.8
2,575
2.9
1,285
4
1,725
1.8
1,950
2.1
2,180
2.3
2,345
2.4
2,455
2.5
1,800
0
2,565
3.0
2,385
2.9
2,225
2.8
2,065
2.7
1,830
2.4
1,740
1
2,480
2.8
2,290
2.7
2,150
2.6
1,975
2.5
1,740
2.2
1,680
2
2,375
2.6
2,210
2.5
2,070
2.4
1,910
2.3
1,645
2.0
1,620
3
2,290
2.4
2,125
2.4
1,990
2.3
1,825
2.1
1,555
1.8
1,560
4
2,200
2.1
2,040
2.1
1,910
2.0
1,725
1.9
1,450
1.5
48
(800) 627-4499
•
Fax: (608) 221-2824
www.RenewAire.com
49
45"
42"40"
Back View
OA Blower and
Filter Access
RA
FA
Wiring In
7/8" Dia.
74 1/2"
57"
33 1/8"
OA
Unit Dimensions
HE3XRTC
EA
OA
E-box Access
Left View
EA
EA
EA
OA
81 1/4"
57 1/2"
Top View
83 7/8"
Service Area
Core and EA
Blower Access
Front View
EA Blower Access
120"
Service
Area
OA
OA Blower and
Filter Access
RA Filter Access
RA
FA
36 3/8"
Service
Area
RA
FA
6 1/2"
25 1/2"
Right View
RA
FA
45"
Exhaust Air to outdoors
Outdoor Air intake
Room Air to be exhausted
Fresh Air to inside
61 3/4"
29"
28 1/4"
EA:
OA:
RA:
FA:
HE4XRT
Specifications
Outdoor Unit
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 1,000-4,400 CFM
AHRI 1060 Certified Core: Four L125-00
Airflow Rating Points (for AHRI): 3,000 CFM and 2,250 CFM
Number Motors: Two
HP
Volts
HZ
Phase
FLA
Min.
Cir.
Amps
Max.
Fuse
Size
2
208-230
208-230
460
575
60
60
60
60
Single
Three
Three
Three
11.3-10.5
6.2-6.2
3.5
2.3
25.4
14.0
7.9
5.2
35
20
15
15
3
208-230
208-230
460
575
60
60
60
60
Sinlge
Three
Three
Three
13.7
9.2-8.6
4.3
3.2
30.8
20.7
9.7
7.2
45
30
15
15
5
208-230
460
575
60
60
60
Three
Three
Three
14.0-13.0
6.5
5.0
31.5
14.6
11.3
45
20
15
G5 Performance
CFM
Effectiveness (%)
1,000
2,000
3,000
4,000
80
Control Voltage: 24 VAC
Sensible
Winte
Filters: Eight total, MERV 8, 2” pleated, 20” x 20” nominal size
r Tota
60
Sum
mer
l
Weight: 915 lbs (unit), 1,000 lbs (shipping weight)
Shipping Dimensions: 84” W x 92” L x 49” H
Tota
l
40
*At AHRI 1060 standard conditions
(See certified data on page 67 for core components).
Base Type/Airflow Orientations
RTV
RTF
EA
OA
RTR
EA
RA
OA
EA
FA
OA
RA
FA
FA
RA
RA
FA
RTH
EA
OA
Airflow Performance
External Static Pressure (Inches Water Column)
Motor HP
Blower RPM
Nominal
Turns Open
0.0
CFM
0.25
BHP
CFM
0.5
BHP
CFM
0.75
BHP
CFM
1.0
BHP
CFM
1.25
BHP
CFM
1.5
BHP
CFM
BHP
2
1,010
1,210
1,370
4.5
2
0
2,489
2,995
-
0.9
1.6
-
2,200
2,290
-
0.9
1.5
-
1,715
2,430
-
0.8
1.4
-
1,100
2,005
2,600
0.7
1.3
2.0
1,540
2,215
1.2
1.9
1,800
1.7
1,100
1.5
3
1,345
1,535
1,685
4.5
2
0
3,295
3,832
-
2.1
2.9
-
3,145
3,682
-
2.1
2.9
-
2,840
3,480
-
2.0
2.8
-
2,509
3,170
-
1.9
2.6
-
2,116
2,839
3,409
1.8
2.4
3.0
1,747
2,449
3.003
1.6
2.3
2.8
1,135
1,878
2,465
1.5
2.0
2.4
5
1,495
1,675
1,855
6
3
0
3,718
4,223
-
2.7
3.8
-
3,568
4,083
-
2.6
3.7
-
3,345
3,943
-
2.6
3.6
-
3,030
3,659
4,287
2.4
3.4
4.9
2,686
3,364
4,011
2.2
3.2
4.6
2,301
2,994
3,760
2.1
2.9
4.3
1,722
2,490
3,434
1.9
2.7
4.0
50
(800) 627-4499
•
Fax: (608) 221-2824
5 1/2"
40 3/8"
Left View
38 3/4"
12" X 32"
FA Outlet
(RTH, RTR)
21 3/4"
EA
74 3/4" Control Wire Inlet
77 3/4" Power Wire Inlet
Wiring In
7/8" Dia.
E-box
FA
17 3/4"
40 1/8"
Curb Center
12" X 32"
FA (RTV, RTF)
EA Outlet
18 5/8"
28 3/4" Curb Center
Front View
2"
57"
89 3/4" Overall
55 1/4" lift lugs
9"
RA
OA
OA Inlet
Right View
80"
82" Overall
79 3/4" lifting lugs
82 1/4"
Unit
117 1/4"
Service
Area
RA
(RTV, RTR Only)
11" x 46"
Top View
18 5/8"
64 1/2" Service Area
FA
Unit Dimensions
RA
12 1/4"
14 3/4"
4"
Top of Curb
HE4XRT
4"
40 3/8"
12" X 40"
RA Inlet
(RTH, RTF)
5 1/8"
www.RenewAire.com
51
EA:
OA:
RA:
FA:
CURB4X
Exhaust Air to outdoors
Outdoor Air intake
Room Air to be exhausted
Fresh Air to inside
HE4XRTC
Specifications
Outdoor Unit
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 2,500-3,700 CFM
AHRI 1060 Certified Core: Four L125-00
Airflow Rating Points (for AHRI): 3,000 CFM and 2,250 CFM
Number Motors: Two
HP
Volts
HZ
Phase
FLA
5
208-230
460
575
60
60
60
Three 14.0-13.0
Three
6.5
5.0
Three
Min.
Cir.
Amps
Max.
Fuse
Size
31.5
14.6
11.3
45
20
15
Control Voltage: 24 VAC
Filters: Six total, MERV 8, 2” pleated, four 20” x 20”, and two
16” x 25” nominal size
G5 Performance
CFM
Effectiveness (%)
1,000
2,000
Weight: 965 lbs (unit), 1,050 lbs (shipping weight)
3,000
4,000
Shipping Dimensions: 84” W x 92” L x 50” H
80
Sensible
Winte
r Tota
l
Sum
mer
Tota
l
60
40
*At AHRI 1060 standard conditions
(See certified data on page 67 for core components).
Airflow Performance
Blower
RPM
Nominal
Exhaust
Air
Fresh
Air
Static Pressure in Adjacent Air Handler (Inches Water Column)
Turns
Open
-0.5
CFM
-0.25
BHP
CFM
0.0
BHP
CFM
+0.25
BHP
CFM
+0.5
BHP
CFM
BHP
1,600
0
3,700
3.6
4,000
3.8
4,250
4.3
-
-
-
-
1,555
1
3.575
3.5
3.900
3.6
4,220
3.9
4,325
4.3
4,380
4.6
1,515
2
3,415
3.2
3,740
3.5
4,135
3.8
4,275
4.2
4,340
4.5
1,470
3
3,235
2.9
3,600
3.2
4,000
3.6
4,215
4.0
4,300
4.3
1,430
4
3,085
2.7
3,455
3.0
3,820
3.2
4,140
3.6
4,260
3.8
1,385
5
2,980
2.5
3,280
2.7
3,640
2.9
3,985
3.2
4,170
3.4
1,340
6
2,880
2.3
3,135
2.5
3,475
2.7
3,840
2.9
4,080
3.0
1,805
1
-
-
-
-
-
-
3,210
4.9
-
-
1,755
2
-
-
-
-
3,410
4.9
3,190
4.6
3,110
4.3
1,705
3
3,710
5.0
3,585
4.9
3,310
4.5
3,130
4.2
3,010
3.9
1,655
4
3,600
4.8
3,470
4.6
3,210
4.2
3,030
3.8
2,910
3.6
1,605
5
3,510
4.3
3,335
4.1
3,110
3.7
2,920
3.4
2,800
3.2
1,555
6
3,400
3.9
3,220
3.8
3,010
3.4
2,810
3.2
2,710
3.0
52
(800) 627-4499
•
Fax: (608) 221-2824
www.RenewAire.com
53
42"
40"
74 1/2"
57"
Back View
OA Blower and
Filter Access
RA
FA
33 1/8"
Wiring In
7/8" Dia.
OA
EA
E-box Access
Unit Dimensions
HE4XRTC
OA
Left View
EA
OA
RA
FA
82 1/4"
5 1/2"
36 3/8"
Service
Area
RA
FA
RA Filter
Access
Front View
80 3/4"
57 1/2"
Top View
82 1/4" Service Area
Core and EA
Blower Access
EA Blower
Access
EA
EA
139 1/2"
Service Area
OA
46 1/2"
OA Blower and
Filter Access
81 3/4"
Right View
RA
FA
37"
EA:
OA:
RA:
FA:
6 1/2"
11 1/4" typ
25 1/2"
45"
Exhaust Air to outdoors
Outdoor Air intake
Room Air to be exhausted
Fresh Air to inside
HE6XRT
Specifications
Outdoor Unit
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 1,500-6,500 CFM
AHRI 1060 Certified Core: Six L125-00
Airflow Rating Points (for AHRI): 4,500 CFM and 3,375 CFM
Number Motors: Two
G5 Performance
Effectiveness (%)
4,000
Volts
HZ
Phase
FLA
Min.
Cir.
Amps
Max.
Fuse
Size
5
208-230
460
575
60
60
60
Three
Three
Three
14.2-13.0
6.5
5.0
32.6
14.9
11.3
45
20
15
7.5
208-230
460
575
60
60
60
Three
Three
Three
20.9-19.2
9.6
7.6
47.0
21.6
17.1
70
30
25
Control Voltage: 24 VAC
CFM
3,000
HP
5,000
Filters: Twelve total, MERV 8, 2” pleated, 20” x 20” nominal size
6,000
Weight: 2,340 lbs (unit), 2,640 lbs (shipping weight)
80
Shipping Dimensions: 85” W x 114” L x 85” H
Sensible
Winter
60
Total
Summ
er Tot
al
40
*At AHRI 1060 standard conditions
(See certified data on page 67 for core components).
Base Type/Airflow Orientations
RTV
RTF
EA
OA
RTR
EA
RA
OA
EA
FA
OA
RA
FA
FA
RA
RA
FA
RTH
EA
OA
Airflow Performance
External Static Pressure (Inches Water Column)
Motor HP
Blower RPM
Nominal
Turns Open
0.0
CFM
0.25
BHP
CFM
0.5
BHP
CFM
0.75
BHP
CFM
1.0
BHP
CFM
1.25
BHP
CFM
1.5
BHP
CFM
BHP
5
1,460
1,610
1,725
4.5
2
0
5,005
5,550
-
3.2
4.2
-
4,800
5,375
-
3.2
4.2
-
4,650
5,250
-
3.1
4.1
-
4,475
5,100
5,525
3.0
4.1
5.0
4,200
4,900
5,475
2.9
4.0
5.0
4,000
4,650
5,200
2.8
3.9
4.9
3,750
4,500
5,050
2.8
3.8
4.8
7.5
1,560
1,740
1,865
4.5
2
0
5,275
5,950
6,500
3.7
5.0
6.5
5,200
5,825
6,350
3.6
5.0
6.5
4,900
5,625
6,225
3.5
4.9
6.4
4,775
5,490
6,125
3.5
4.9
6.4
4,550
5,325
5,910
3.4
4.8
6.3
4,350
5,125
5,825
3.3
4.7
6.2
4,125
4,950
5,625
3.3
4.7
6.1
54
(800) 627-4499
•
Fax: (608) 221-2824
RIGHT VIEW
108 1/2" Base
EA
OA
78 1/4" Overall
EA
60 7/8"
RA
BACK VIEW
49"
24"
81 1/2" Base
21 7/8"
Note:
All units have an integral
exhaust air backdraft damper.
Power and
Control
Wiring
Entries
7/8" Dia.
Core
Access
(RTF,RTH Only)
RA
34" Min.
Clearance
LEFT VIEW
62"
18"
108 1/2" Base
FA
39 1/2" Min.
Clearance
TOP VIEW
FA
112 3/4" Unit Roof
63 1/2"
EA
39 3/4"
Power and Control Wiring Entries
41 3/4"
12"
(RTV,RTR)
22"
59 3/8"
4"
160 1/4" Service Area
4"
9"
Unit Dimensions
24"
77"
HE6XRT
36"
www.RenewAire.com
55
165" Service Area
FRONT VIEW
Blower Access
85 1/2" Unit Roof
EA
RTH, RTR UNITS ONLY:
FA BLOWER Outlet is 18" x 24".
24" x 36" Duct Flange is also supplied.
Field install only in location shown.
Front Views at 0.5X:
BLOWER ROTATION
RTV, RTF UNITS ONLY:
FA Blower Outlet is 16" x 22".
Curb accepts up to 24" x 36" duct;
see separate Curb drawing.
Exhaust Air to outdoors
Outdoor Air intake
Room Air to be exhausted
Fresh Air to inside
CURB6X
EA:
OA:
RA:
FA:
HE8XRT
Specifications
Outdoor Unit
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 2,000-8,000 CFM
AHRI 1060 Certified Core: Eight L125-00
Airflow Rating Points (for AHRI): 6,000 CFM and 4,500 CFM
Number Motors: Two
Effectiveness (%)
2,000
4,000
6,000
Max.
Fuse
Size
Three 14.2-13.0
Three
6.5
5.0
Three
32.6
14.9
11.3
45
20
15
60
60
60
Three 20.9-19.2
Three
9.6
Three
7.6
47.0
21.6
17.1
70
30
25
60
60
60
Three 29.0-26.8
Three
13.4
Three
10.0
65.3
30.2
22.5
90
45
35
Volts
HZ
Phase
5
208-230
460
575
60
60
60
7.5
208-230
460
575
10
208-230
460
575
G5 Performance
CFM
Min.
Cir.
Amps
HP
8,000
FLA
Control Voltage: 24 VAC
80
Filters: Sixteen total, MERV 8, 2” pleated, 20” x 20” nominal size
Sensible
Winte
Weight: 2,730 lbs (unit), 3,080 lbs (shipping weight)
r Tota
60
Summ
Shipping Dimensions: 85” W x 114” L x 85” H
l
er To
tal
40
*At AHRI 1060 standard conditions
(See certified data on page 67 for core components).
Base Type/Airflow Orientations
RTV
RTF
EA
OA
RTR
EA
RA
OA
EA
FA
OA
RA
FA
FA
RA
RA
FA
RTH
EA
OA
Airflow Performance
External Static Pressure (Inches Water Column)
Motor HP
Blower RPM
Nominal
Turns Open
0.0
CFM
0.25
BHP
CFM
0.5
BHP
CFM
0.75
BHP
CFM
1.0
BHP
CFM
1.25
BHP
CFM
1.5
BHP
CFM
BHP
5
1,460
1,610
1,725
4.5
2
0.5
5,575
6,200
6,550
3.2
4.3
5.0
5,425
6,010
6,380
3.2
4.3
5.0
5,200
5,875
6,210
3.2
4.2
5.0
5,000
5,700
6,100
3.2
4.2
5.0
4,775
5,500
5,880
3.1
4.2
4.9
4,550
5,325
5,730
3.0
4.1
4.8
4,270
5,125
5,510
2.9
4.1
4.8
7.5
1,560
1,740
1,865
4.5
2
0
6,000
6,700
-
3.9
5.3
-
5,850
6,575
-
3.9
5.3
-
5,650
6,400
-
3.8
5.3
-
5,475
6,300
6,800
3.8
5.3
7.5
5,275
6,125
6,675
3.8
5.3
7.5
5,100
5,950
6,500
3.7
5.2
7.5
4,875
5,750
6,375
3.7
5.2
7.4
10
1,810
2,020
2,105
4.5
2
1
7,000
7,850
-
6.1
8.5
-
6,875
7,745
-
6.1
8.5
-
6,750
7,625
7,950
6.1
8.5
9.6
6,600
7,450
7,800
6.0
8.4
9.6
6,425
7,350
7,725
6.0
8.4
9.6
6,275
7,200
7,600
6.0
8.3
9.5
6,100
7,050
7,450
5.9
8.3
9.5
56
(800) 627-4499
•
Fax: (608) 221-2824
RIGHT VIEW
108 1/2" Base
EA
OA
EA
RA
BACK VIEW
49"
24"
81 1/2" Base
21 7/8"
(RTV,RTR)
OA Hoods on
Rooftop Units
only.
(RTF,RTH Only)
OA
Core Access
27 1/4"
35"
OA
LEFT VIEW
62"
18"
108 1/2" Base
FA
39 1/2" Min.
Clearance
TOP VIEW
FA
112 3/4" Unit Roof
29"
RA
63 1/2"
EA
39 3/4"
Power and Control Wiring Entries
34" Min.
Clearance
59 3/8"
60 7/8"
Note:
All units have an integral
exhaust air backdraft damper.
Power and
Control
Wiring
Entries
7/8" Dia.
78 1/4" Overall
41 3/4"
183 1/4" Service Area
4"
9"
Unit Dimensions
24"
77"
HE8XRT
22"
36"
4"
www.RenewAire.com
57
165" Service Area
FRONT VIEW
Blower Access
85 1/2" Unit Roof
EA
RTH, RTR UNITS ONLY:
FA BLOWER Outlet is 18" x 24".
24" x 36" Duct Flange is also supplied.
Field install only in location shown.
Front Views @ 0.5X:
BLOWER ROTATION
RTV, RTF UNITS ONLY:
FA Blower Outlet is 16" x 22".
Curb accepts up to 24" x 36" duct;
see separate Curb drawing.
Exhaust Air to outdoors
Outdoor Air intake
Room Air to be exhausted
Fresh Air to inside
CURB8X
EA:
OA:
RA:
FA:
Applied Products
• Cost effective energy recovery for virtually
any air handling system.
• AHRI certified performance data for
efficiency and cross leakage.
• Field assembled into air handling systems or
integrated in custom packaged air handlers.
• Unlimited airflow capacity.
• UL tested flammability and smoke
generation that meets NFPA 90A and
90B test standards for commercial
applications.
• Flexible installation and easy servicing.
• Ten year core warranty.
RenewAire means Trouble-Free ERV.
Installation Example
Central Air Handler using CA4X and exhaust and make-up air blowers.
(CA-Series provide side service access and a “side-by-side” airflow arrangement.)
CA4X
Similar designs can use PA-Series arrays.
(PA-Series provide top service access and an “over-under” airflow arrangement.)
58
(800) 627-4499
•
Fax: (608) 221-2824
CA & PA Series Applied Energy Recovery Ventilators:
CA2X, CA3X, CA4X, PA6X, PA9X, PA8X & PA12X
Part I - General
A. Product Specification
1. Energy Recovery Ventilator (ERV) shall be a packaged unit as manufactured
by RenewAire and shall transfer both heat and humidity using static plate
core technology.
B. Quality Assurance
1. The energy recovery cores used in these products shall be third
party Certified by AHRI under its Standard 1060 for Energy Recovery
Ventilators. AHRI published certifications shall confirm manufacture’s
published performance for airflow, static pressure, temperature and total
effectiveness, purge air (OACF) and exhaust air leakage (EATR). Products
that are not currently AHRI Certified will not be accepted.
2. The energy recovery core shall be a UL Listed Component complying
to UL Standard 723. Manufacturer shall be able to provide evidence of
independent testing of the core by Underwriters Laboratory (UL), verifying
a maximum flame spread index (FSI) of 25 and a maximum smoke developed
index (SDI) of 50 thereby meeting NFPA 90A and NFPA 90B requirements for
materials in a compartment handling air intended for circulation through
a duct system.
3. The ERV core shall be warranted to be free of manufacturing defects and
to retain its functional characteristics, under circumstances of normal use,
for a period of ten years from the date of purchase. The balance-of-unit
shall be warranted to be free of manufacturing defects and to retain its
functional characteristics, under circumstances of normal use, for a period
of two years from the date of purchase.
Part II – Performance
A. Energy Transfer
The ERV shall be capable of transferring both sensible and latent energy
between airstreams. Latent energy transfer shall be accomplished by direct
water vapor transfer from one airstream to the other, without exposing
transfer media in succeeding cycles directly to the exhaust air and then to
the fresh air.
B. Passive Frost Control
The ERV core shall perform without condensing or frosting under normal
operating conditions (defined as outside temperatures above -10°F and
inside relative humidity below 40%). Occasional more extreme conditions
shall not affect the usual function, performance or durability of the core.
No condensate drains will be allowed.
3. The unit case shall be constructed of G90 galvanized, 20-gauge steel,
with lapped corners and zinc plated screw fasteners.
4. Access doors shall provide easy access to ERV cores and filters. Doors
shall have an airtight compression seal using closed cell foam gaskets.
5. Case walls and doors shall be insulated with 1 inch, 4 pound density, foil/scrim
faced, high-density fiberglass board insulation, providing a cleanable surface
and eliminating the possibility of exposing the fresh air to glass fibers. PA-Series
bottom panels shall be insulated with ¼ inch sheet rubber insulation.
6. The ERV cores shall be protected by a MERV-8 rated, 2” nominal, pleated,
disposable filter in both airstreams.
7. CA-Series cabinet construction shall allow stacking of units up to three
cabinets high for larger airflow applications. Hinged and latched access
doors will be provided on each end of the unit.
8. PA-Series shall use RenewAire patented modular vertical stack of cores
(US Patent 5,660,228) allowing assembly of unlimited sizes of ERV systems.
Latched access doors are provided on the top of each unit.
B. Options (Select options based on application requirements)
1. Provide unit and duct connection orientation per project schedule.
2. Provide double wall construction with 24-gauge galvanized steel liner
(CA-Series only).
3. CA and PA-Series units are available pre-assembled on a structural steel base.
Part IV – Installation
A. Unit Location
1. Locate and orient unit to provide the shortest and most straight duct
connections. Provide service clearances as indicated on the plans. Locate
system blowers (provided by others) distant from sound critical occupancies.
2. Provide a poured concrete equipment pad for all floor mounted units.
The pad thickness, and floor plan dimensions to be determined based on
the unit selected, and site structural considerations.
3. Provide a structurally suitable support for the base of any wall mounted
or hung units.
B. Vibration Isolation
C. Continuous Ventilation
1. No moving parts are allowed in the ERV modular assemblies.
Unit shall have the capacity to operate continuously without the need
for bypass, recirculation, pre-heaters or defrost cycles under normal
operating conditions.
C. Duct Design
D. Positive Airstream Separation
Water vapor transfer shall be through molecular transport by hydroscopic
resin and shall not be accomplished by “porous plate” mechanisms. Exhaust
and fresh airstreams shall travel at all times in separate passages, and
airstreams shall not mix.
E. Laminar Flow
Airflow through the ERV core shall be laminar over the products entire
operating airflow range, avoiding deposition of particulates on the interior
of the energy exchange plate material.
1. All ductwork shall be designed, constructed, supported and sealed in
accordance with SMACNA HVAC Duct Construction Standards and pressure
classifications.
2. At a minimum all duct runs to the outdoors shall be thermally insulated
at levels appropriate to the local climate. A continuous vapor barrier shall
also be provided on warm surface of the insulation.
D. Sound Control
Part III – Product
1. The ERV cores shall act as flow straighteners and sound attenuators. This
attribute can be used to isolate mechanical noise from blowers and other
mechanical equipment from sound critical occupancies.
A. Construction
E. Test and Balancing
1. The energy recovery component shall be of fixed-plate cross-flow
construction, with no moving parts.
1. Test and Balancing may not begin until 100% of the installation is
complete and fully functional.
2. No condensate drain pans or drains shall be allowed and unit shall
be capable of operating in both winter and summer conditions without
generating condensate.
2. Follow National Comfort Institute (NCI) air test and balance procedures
specific to Heat Recovery Ventilator Balancing Procedure including standard
reports to the owner’s representative.
59
www.RenewAire.com
CA-Series
Indoor Unit - Up to 20,000 CFM in Stacked Arrays
Specifications
Ventilation Type: Static Plate, Heat and Humidity Transfer
Insulated sheet metal cabinets with energy exchange cores and filters.
Individual CA-Series units or stacks of units can be built into larger air
handling systems.
Blower not included and must be specified to meet job requirements.
Description
Typical Airflow Range CFM
AHRI 1060 Certified Core
Airflow Rating Points
(for AHRI)
Effectiveness (%)
1,000
1,500
Two L125-00 Three L125-00 Four L125-00
2,250 and
1,690 CFM
3,000 and
2,250 CFM
Unit Weight
225 lbs
325 lbs
400 lbs
Shipping Weight
275 lbs
375 lbs
475 lbs
Four Total
Six Total
Eight Total
2,000
Insulation: One inch, high density, FSK faced, fiberglass
80
Sensible
Winter To
tal
Summe
r Total
60
40
CA2X
CFM
1,250
1,750
2,250
80
2.750
Sensible
Winter Tota
Summer To l
tal
60
40
CA3X
Effectiveness (%)
CFM
Effectiveness (%)
CA4X
1,000-4,400
Shipping Dimensions: CA2X - 40” W x 48” L x 41” H
CA3X - 40” W x 67” L x 41” H
CA4X - 40” W x 87” L x 41” H
CFM
500
CA3X
750-3,300
1,500 and
1,120 CFM
Filters: MERV 8, 2” pleated
20” x 20” nominal size
G5 Performance
CA2X
500-2,200
1,000
80
40
CA4X
4X
CA
CA
3X
2X
CA
Internal Static Pressure
(in. H2O)
CA3X
0.5
1,000
2,000
3,000
4,000
Airflow (CFM)
60
(800) 627-4499
•
4,000
*At AHRI 1060 standard conditions
(See certified data on page 66 for core components).
2.0
1.0
3,000
Sensible
Winter T
otal
Summe
r Total
60
Airflow Performance
1.5
2,000
Fax: (608) 221-2824
www.RenewAire.com
61
39 3/4"
Left View
Top View
D ( Minimum Service Area)
2.5000
End View
34 3/4"
CA4X
81-5/8”
32”
149”
116”
7-5/8”
39-3/4”
34 3/4"
EA:
OA:
RA:
FA:
Exhaust Air to outdoors
Outdoor Air intake
Room Air to be exhausted
Fresh Air to inside
E
B
F
B
F
E
Right View
A
Note: Filters are provided for installation in
any two of the locations shown, depending
on which duct connections are selected for
inlets.
Filters are 2" x 20" x 20" pleated
disposable.
Double Wall Construction
Available Options:
15"
2.5000
CA3X
62”
24”
130”
96”
5-5/8”
29-5/8”
1"
C (Maximum Service Area)
CA2X
42”
14”
111”
77”
5-5/8”
19-3/4”
1"
Unit Dimensions
A
B
C
D
E
F
15"
CA-SERIES
34 3/4"
PA-Series
Specifications
Indoor Unit - Unlimited Airflow in Multiple Arrays
Ventilation Type: Static Plate, Heat and Humidity Transfer
Insulated sheet metal panels easily slide into receivers to enclose stacks of
energy exchange cores using unique patented design, US Patent 5,660,228
Individual PA-Series units can be joined together to provide unlimited airflow
capacities for larger air handling systems.
Blower not included and must be specified to meet job requirements.
Description
G5 Performance
PA6X
PA8X
PA9X
PA12X
Typical Airflow
Range CFM
1,500-6,600
2,000-8,800
2,250-9,900
3,000-13,200
AHRI 1060
Certified Core
Six L125-00
Eight L125-00 Nine L125-00
Twelve L125-00
Airflow Rating
Points (for AHRI)
4,500 and
3,375 CFM
6,000 and
4,500 CFM
6,750 and
5,062 CFM
9,000 and
6,750 CFM
Unit Weight
565 lbs
695 lbs
800 lbs
980 lbs
Shipping Weight
650 lbs
900 lbs
990 lbs
1,180 lbs
Filters: MERV 8, 2” pleated, 20” x 20” nominal size
PA6X - 12 Total
PA9X - 18 Total
PA8X - 16 Total
PA12X - 24 Total
Insulation: One inch, high density, FSK faced, fiberglass
CFM
CFM
4,000
5,000
3,500
6,000
80
Sensible
60
Winter Tota
l
Summer To
tal
40
PA6X
Effectiveness (%)
Effectiveness (%)
3,000
5,000
80
Winter To
tal
Summer
Total
40
PA9X
CFM
6,500
5,000
8,000
80
Sensible
60
Winter T
otal
Summer
Total
40
PA8X
Effectiveness (%)
Effectiveness (%)
5,000
7,000
9,000
Sensible
Winter Tota
l
Summer To
tal
60
40
PA12X
X
PA
1
2X
PA
9
PA
8
X
X
2.0
PA
6
Internal Static Pressure
(in. H2O)
Airflow Performance
1.0
CA3X
0.5
3,000
6,000
9,000
12,000
Airflow (CFM)
62
(800) 627-4499
•
11,000
80
*At AHRI 1060 standard conditions
(See certified data on page 66 for core components).
1.5
8,000
Sensible
60
CFM
3,500
6,500
Fax: (608) 221-2824
www.RenewAire.com
63
Side View
35 1/2"
Service
Area
G
22 1/2”
35 1/2"
35 1/2"
Unit Dimensions
PA-SERIES
PA-9X/12X
565
APPROX.
WEIGHT
Front View
D (Duct Flange)
A (Overall)
Service Area
Top View
A = 109 1/2
A = 73 1/4
PA-6X/8X
PA6X
73-1/4”
72-3/4”
28”
1-1/2”
66-1/4”
A
D
E
F
G
E
E
810
5”
F
PA9X
109-1/2”
109”
28”
1-1/2”
66-1/4”
700
PA8X
73-1/4”
72-3/4”
37”
3-1/8”
86”
EA:
OA:
RA:
FA:
35 1/2"
Arrangement 4
Same-side Entries
Parallel-path Airflows
Performance Derating:
Airflow arrangements 3 & 4 result in lower energy transfer.
Reduce sensible effectiveness by 2 percentage points.
Reduce total effectiveness by 1 percentage point.
35 1/2"
2
35 1/2"
Arrangement 2
Same-side Entries
Cross-path Airflows
35 1/2"
2
2
1
2
1
Arrangement 3
Opposite-side Entries
Parallel-path Airflows
1
1
1
2
2
1
1
2
Exhaust Air to outdoors
Outdoor Air intake
Room Air to be exhausted
Fresh Air to inside
Available Airflow Arrangements
(Side Views)
Assembled on structural
forklift base
Knockdown
Available Options:
Arrangement 1
Opposite-side Entries
Cross-path Airflows
2
1
1000
PA12X
109-1/2”
109”
37”
3-1/8”
86”
Commercial Controls & Interconnection Options
These controls are intended to turn RenewAire commercial energy recovery ventilation systems on and off at
appropriate times. Specification, installation and set-up is an easy process. RenewAire units should be ordered
with the 24 volt contactor option for all controls.
It is not necessary that RenewAire controls be used to operate RenewAire units. A wide range of controls or
building automation systems may be used. Make sure units are ordered with compatible contactor control voltage.
RenewAire residential units have their own line of compatible controls that are not intended to operate
RenewAire commercial units.
Digital Time Clock
TC7D
•
•
•
•
•
•
up to 8 on/off cycles per day or 56 per week
24 VAC power requirement
battery back-up
wall mount or outdoor enclosure options
wall mount fits any 4” x 4” electrical box
optional RenewAire transformer relay
package (TR40) may be used
Motion (occupancy) Control
MC
•
•
•
•
•
passive infared sensor
adjustable time-off delay to 30 minutes
24 VAC power requirement
ceiling mount or directable wall mount
covers up to 1500 sq. ft. floor space
TC7D-W
Wall Mount
TC7D-E Control
In NEMA 3R Enclosures
MC-C
Ceiling Mount
MC-W
Wall Mount
ceiling mount - walking motion coverage up to 22 foot radius
wall mount - various coverage patterns up to 90 linear feet of sensitivity
• requires the use of RenewAire transformer relay package
(TR40) (ordered separately)
Carbon Dioxide Control
CO2
CO2-W
Wall Mount
•
•
•
•
•
•
•
adjustable control from 600-2000 PPM
digital display
24 VAC power requirement
computer/BAS interface for information and control
self calibrates during periods of low occupancy
wall mount or add duct mount accessory
requires the use of RenewAire transformer relay package
(TR40) (ordered separately)
64
(800) 627-4499
•
Fax: (608) 221-2824
CO2-D
Duct Mount
DH24
Dehumidistat Control
•
•
•
•
•
DH24
Wall Mount
secondary control to time clock or other primary control
mechanical switching of 24 VAC (or 120 VAC)
adjustable from 0 - 100% relative humidity
wall mount to single gang box
Note: RenewAire ERVs are not to be used for applications
where indoor relative humidity exceeds 50% RH for extended
periods of time
Disconnect Switch
DS
•
•
•
•
•
fused or non-fused
indoor or NEMA 3R exterior enclosures - I or E
installation voltage must be specified 115, 208-230, 460
installed on unit and wired to unit contactor
disconnects are configured as part of the model numbering for a unit (see page 67)
Transformer Relay Package
TR40
•
•
•
•
•
•
IBC
provides a 24 VAC, 40 VA class II power supply for unit control
includes isolation relay with low voltage circuit breaker
handles any RenewAire unit with one contactor
installation voltage must be specified 115, 208-230, 460
installed in unit electric box
TR40 is configured as part of the model numbering for a unit (see page 67)
Independent Blower Control
• adds a second contactor to allow independent control of exhaust fan and
supply fan
• may be used to provide economizer (no heat recovery operation) function
• can provide relief fan or make-up air function to benefit building pressurization
• IBC is configured as part of the model numbering guide for a unit (see page 67)
65
www.RenewAire.com
HVI
Tested/Certified
Per CSA C439
BR70/EV70 - Ventilation Performance
Gross Airflow
Net Supply Airflow
Supply
Exhaust
in. wg
L/S
CFM
L/S
CFM
L/S
CFM
0.1
41
86
42
89
46
97
0.2
34
73
35
75
39
84
0.3
28
59
29
61
32
69
0.4
21
46
22
47
25
53
0.9
Pa
25
50
75
100
in. wg. (PA = n x 248.8)
Ext. Static Pressure
Electrical Requirements Volts 120 Amps 1.0
Exhaust Air Transfer Rao = 4% @ 0.2 in. wg (50 PA) and 4% @ 0.4 in. wg (100 PA)
Net Airflow
Average Power
Watts
L/S
CFM
32
69
94
30
64
94
Sensible Recovery Apparent Sensible
Efficiency %
Effectiveness %
66
0.6
0.5
0.4
0.3
0.2
0.1
0
77
Total Recovery Efficiency %
42
25
50
75
100
125
150
175
CFM (L/S = n x 0.4719)
Net Moisture
Transfer %
Gross Supply
Gross Exhaust
53
BR130/EV130 - Ventilation Performance
Gross Airflow
Net Supply Airflow
Supply
Exhaust
in. wg
L/S
CFM
L/S
CFM
L/S
CFM
0.1
70
148
71
151
75
159
0.2
66
141
67
143
69
147
0.3
62
132
63
134
64
135
0.4
53
113
54
115
56
119
0.5
44
94
45
96
47
99
0.6
32
69
33
70
29
62
0.7
24
52
25
53
21
45
0.9
in. wg. (PA = n x 248.8)
Ext. Static Pressure
Pa
25
50
75
100
125
150
175
0.7
0.0
BR70/EV70 - Energy Performance
Supply
Temperature
C°
F°
Heating
0°
32°
Cooling
35°
95°
0.8
Electrical Requirements Volts 120 Amps 1.3
Exhaust Air Transfer Rao = 2% @ 0.2 in. wg (50 PA) and 2% @ 0.4 in. wg (100 PA)
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.0
0
25
50
75
100
125
150
175
CFM (L/S = n x 0.4719)
BR130/EV130 - Energy Performance
Supply
Temperature
C°
F°
Heating
0°
32°
Cooling
35°
95°
Net Airflow
Average Power
Watts
L/S
CFM
58
124
121
59
126
121
Sensible Recovery Apparent Sensible
Efficiency %
Effectiveness %
72
Gross Supply
Net Moisture
Transfer %
80
Total Recovery Efficiency %
46
Gross Exhaust
55
EV200 - Ventilation Performance
Pa
25
50
75
100
125
150
175
in. wg
0.1
0.2
0.3
0.4
0.5
0.6
0.7
Net Supply Airflow
L/S
97
90
88
83
79
70
57
CFM
207
192
186
176
168
149
122
0.9
Gross Airflow
Supply
Exhaust
L/S
CFM
L/S
CFM
100
213
109
232
93
199
104
221
90
192
101
216
85
181
96
204
81
173
88
187
72
154
76
162
59
126
68
145
in. wg. (PA = n x 248.8)
Ext. Static Pressure
Electrical Requirements Volts 120 Amps 1.5
Exhaust Air Transfer Rao = 3% @ 0.2 in. wg (50 PA) and 3% @ 0.4 in. wg (100 PA)
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.0
0
25
50
75
100 125
150 175 200 225 250
CFM (L/S = n x 0.4719)
EV200 - Energy Performance
Supply
Temperature
C°
F°
Heating
0°
32°
Cooling
35°
95°
Net Airflow
Average Power
Watts
L/S
CFM
85
181
157
85
180
155
Sensible Recovery Apparent Sensible
Efficiency %
Effectiveness %
78
Gross Supply
Net Moisture
Transfer %
85
Total Recovery Efficiency %
52
Gross Exhaust
62
EV300 - Ventilation Performance
Pa
100
125
150
175
200
225
250
in. wg
0.4
0.5
0.6
0.7
0.8
0.9
1.0
Net Supply Airflow
L/S
145
141
136
126
117
94
73
CFM
310
300
289
268
249
199
155
Gross Airflow
Supply
Exhaust
L/S
CFM
L/S
CFM
150
320
143
305
145
310
138
295
140
299
127
270
130
276
114
242
121
251
92
195
97
206
79
169
75
160
65
138
in. wg. (PA = n x 248.8)
Ext. Static Pressure
Electrical Requirements Volts 120 Amps 3.3
Exhaust Air Transfer Rao = 4% @ 0.4 in. wg (100 PA)
1.1
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.0
0
50
100
150
200
250
300
350
CFM (L/S = n x 0.4719)
EV300 - Energy Performance
Supply
Temperature
C°
F°
Heating
0°
32°
Cooling
35°
95°
Net Airflow
Average Power
Watts
L/S
CFM
138
293
310
120
272
299
Sensible Recovery Apparent Sensible
Efficiency %
Effectiveness %
68
Net Moisture
Transfer %
76
Total Recovery Efficiency %
38
45
66
(800) 627-4499
•
Fax: (608) 221-2824
Gross Supply
Gross Exhaust
AHRI 1060-2005
Certified Performance
AHRI-1060 Certified Performance - Model Number L85-G5
Type
Tilt Angle
Nominal Airflow
Pressure Drop
Plate
N/A
100% - 450 SCFM
75% - 338 SCFM
0.6 in. H20
0.5 in. H20
Leakage Ratings
Thermal Effectiveness Ratings at 0” Pressure Differential
Pressure
Differential
EATR
Purge Angle
OACF
or Setting
Test 1
-1 in. H20
1.0%
1.00
N/A
Test 2
0 in. H20
0.0%
1.02
N/A
Test 3
1 in. H20
0.0%
1.05
N/A
Net
Net
Airflow Sensible
Nominal
Airflow
Sensible
Latent
Total
450 Heating
CFM Cooling
73%
73%
53%
46%
66%
56%
450
CFM
338 Heating
CFM Cooling
77%
77%
60%
52%
71%
61%
338
CFM
Net
Latent
Net
Total
73%
73%
53%
46%
66%
56%
77%
77%
60%
52%
71%
61%
AHRI-1060 Certified Performance - Model Number L125-G5
Type
Tilt Angle
Nominal Airflow
Pressure Drop
N/A
100% - 750 SCFM
75% - 563 SCFM
0.65 in. H20
0.45 in. H20
Plate
Leakage Ratings
Thermal Effectiveness Ratings at 0” Pressure Differential
Pressure
Differential
EATR
Purge Angle
OACF
or Setting
Test 1
-1 in. H20
1.0%
1.00
N/A
Test 2
0 in. H20
0.0%
1.02
N/A
Test 3
1 in. H20
0.0%
1.05
N/A
NOTE: SCFM = Standard Cubic Feet per Minute
Net
Net
Airflow Sensible
Nominal
Airflow
Sensible
Latent
Total
750 Heating
CFM Cooling
71%
71%
52%
43%
64%
53%
750
CFM
563 Heating
CFM Cooling
75%
75%
59%
50%
69%
59%
563
CFM
OACF = Outdoor Air Correction Factor
Net
Latent
Net
Total
71%
71%
52%
43%
64%
53%
75%
75%
59%
50%
69%
59%
EATR = Exhaust Air Transfer Ratio
N/A = Not Applicable
Energy recovery component certified in accordance with AHRI Standard 1060-2005.
Actual performance in packaged equipment may vary.
Model Numbering Guide
6
STANDARD
FEATURES
MODEL
NUMBER
CORE: "J" = G5
7-8 "IN" = INDOOR
J I N
1
2
3
4
5
6
Not all options are available on every model.
7
8
12-20
UNUSED IN PA, CA MODELS
- - - - - - - - - - - 9
10
11
12
13
14
15
16
17
18
19
20
21
22
N
23
24
25
25
UL: "N" = NON-LISTED
MULTIPLE-CHOICE OR
OPTIONAL FEATURES
1-2 MODEL:
"CA" = CABINET APPLIED
"PA" = PANELIZED APPLIED
QTY OF CORES:
24 OPTION 4: PRE-ASSEMBLY
"K" = KNOCKDOWN (PA MODELS)
"A" = ASSEMBLED (PA MODELS)
"-" = NOT APPLICABLE (CA MODELS)
3-5
"nX" = (n) CORES
n = 2, 3, 4 (CA MODELS)
n = 6, 8, 9, 12 (PA MODELS)
BASE TYPE (SEE DIAGRAM)
23 OPTION 3 (RESERVED): "-" = NONE
22 OPTION 2 (RESERVED): "-" = NONE
9
(CA) "-" (NONE)
(PA) "9" = FORKLIFT BASE
CA & PA MODELS
10
AIRFLOW ORIENTATION (UNUSED IN CA MODELS)
"1" = OPPOSITE-SIDE ENTRY, CROSS-FLOW
"2" = SAME-SIDE ENTRY, CROSS FLOW
"3" = OPPOSITE-SIDE ENTRY, PARALLEL-FLOW
"4" = SAME-SIDE ENTRY, PARALLEL-FLOW
"-" = DEFAULT IN CA MODELS AND IN PA MODELS WITH
PRE-ASSEMBLY OPTION "K" (KNOCK-DOWN).
21 OPTION 1 (RESERVED): "-" = NONE
11 WALL TYPE (UNUSED IN PA MODELS):
"S" = SINGLE (CA MODELS ONLY)
"D" = DOUBLE (CA MODELS ONLY)
67
www.RenewAire.com
1
2
3
4
5
6
J
6
7
7-8
-
9
VOLTAGE: (SEE RESTRICTIONS 2, 3, 4 & 5)
FA HORSEPOWER
RESTRICTION 6
EA HORSEPOWER
15
OPTION 4: OTHERS
OPTION 2: FILTER MONITOR (RESTRICTION 13)
22
OPTION 1: 24V TRANS. (RESTRICTIONS 11 & 12):
DISCONNECT (RESTRICTIONS 9 & 10):
UNIT CONTROL (RESTRICTIONS 7 & 8)
EV/HE MODELS
"A" = (1) 24V CONTACTOR
"D" = (2) 24V CONTACTORS
"R" = INVERTER READY (NO CONTACTOR)
19
"N" = NON-FUSED
"F" = FUSED
"-" = NONE
20
"-" = NONE
"T" = TR40 (TRANSFORMER WITH ISOLATION RELAY)
21
"-" = NONE,
"F" = FILTER MONITOR BOTH AIRSTREAMS
OTHER OPTIONS (RESERVED)
23
"-" = NONE,
"W" = WHITE PAINT, "C" = CUSTOM PAINT
"X" = CUSTOM UNIT
24
UL LISTING (SEE RESTRICTION 15):
UL: "L" = LISTED "N" = NON-LISTED
25
UNUSED IN THESE MODELS
14: SOME UNITS WITH CUSTOM "X" CODE NOT
UL-LISTED.
13: FILTER MONITORS NOT AVAILABLE IN EV450.
12: TRANSFORMER CODE "T" (TR40) NOT AVAILABLE
WITH UNIT CONTROL CODES "D" (2 CONTACTORS) OR
"R" (INVERTER READY), EXCEPT IN MODELS HE-6X &
HE-8X.
11: TRANSFORMER CODE "T" (TR40) AVAILABLE ONLY
WITH VOLTAGE CODES 1, 4, 5 & 9.
10: DISCONNECT CODES "N" & "F" NOT AVAILABLE
WITH UNIT CONTROL CODE "R" (INVERTER READY).
9: DISCONNECT CODES "N" & "F" AVAILABLE ONLY
WITH VOLTAGE CODES 1, 4, 5, 8 & 9.
8: UNIT CONTROL CODE "D" (2 CONTACTORS) NOT
AVAILABLE IN MODEL EV450.
7: UNIT CONTROL CODE "R" (INVERTER READY) NOT
AVAILABLE WITH PHASE CODE "1" (SINGLE PHASE),
OR IN MODEL EV450.
6: VOLTAGE CODES "1" & "6" AVAILABLE ONLY WITH
FA/EA HORSEPOWER CODES "H", 'Q" & "-".
5: VOLTAGE CODE "8" (575V) NOT AVAILABLE WITH
HORSEPOWER CODES "H", "Q" OR WITH MODEL
EV450.
VOLTAGE CODES "1" (115V), "6" (115/208-230V), "7"
(208-230/460V), "9" (277V) NOT AVAILABLE IN HE-6X,
HE-8X.
VOLTAGE CODE "5" (208-230V) NOT AVAILABLE WITH
PHASE CODE "1" (SINGLE-PHASE) IN MODELS HE-6X &
HE-8X.
4. VOLTAGE CODE "9" (277V) AVAILABLE ONLY WITH
HORSEPOWER CODES "H", "Q" OR EV450 MODEL.
3: VOLTAGE CODES "4", "7" & "8" AVAILABLE WITH
PHASE CODE "3" (THREE-PHASE) ONLY.
2: VOLTAGE CODES "1", "6" & "9" AVAILABLE WITH
PHASE CODE "1" (SINGLE-PHASE) ONLY.
1: BASE TYPE "C" NOT AVAILABLE WITH MODELS
EV450, HE-6X, HE-8X.
BASE TYPE "T" AVAILABLE ONLY IN HE-6X, HE-8X.
RESTRICTIONS:
Note: Not all options are available on every model.
Model Numbering Guide
For Technical Support E-mail: [email protected]
To Place an Order E-mail: [email protected]
"H" = 0.75 HP EPACT DIRECT-DRIVE (HE-1X ONLY)
"J" = 1.5HP EPACT (HE-2X ONLY)
"K" = 2HP EPACT (HE-2X, HE-3X, HE-4X ONLY)
"L" = 3HP EPACT (HE-3X, HE-4X ONLY)
"M" = 5HP EPACT (HE-3X, HE-4X, HE-6X, HE-8X ONLY)
"N" 7.5HP EPACT (HE-6X, HE-8X ONLY)
"P" 10HP EPACT (HE-8X ONLY)
"Q" = (2) 0.75HP EPACT DIRECT-DRIVE (HE-2X ONLY)
"-" = DEFAULT IN EV450
14
13
PHASE: "1" = SINGLE-PHASE, "3" = THREE-PHASE 12
"1" = 115V, "4" = 460V, "5" = 208-230V,
"6" = 115/208-230V, "7" = 208-230/460V,
"8" = 575V, "9" = 277V
- - -
16-18
UNUSED IN HE MODEL
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
WALL TYPE: "S" = SINGLE, "D" = DOUBLE 11
"V", "H", "T" (INDOOR UNITS)
"V", "H", "R", "F", "C" (ROOFTOP UNITS)
"-" - DEFAULT IN HE450
8
10
CORE: "J" = G5
1-5
BASE TYPE (SEE RESTRICTION 1)
"IN" = INDOOR, "RT" = ROOFTOP
INDOOR/OUTDOOR
"EV450", "HE-1X", "HE-2X"
"HE-3X", "HE-4X", "HE-6X, "HE-8X"
MODEL
MODEL
NUMBER
STANDARD
FEATURES
MULTIPLE-CHOICE OR
OPTIONAL FEATURES
RenewAire Product & Ventilation Commitment
RenewAire ventilation products will give you cleaner air to breathe - letting you and your family feel better
and healthier AND will do so in the most consistent, controlled, safe and energy-efficient manner possible.
Gree
n
Save Energy
Reduce Pollution
Ample Airflow
Material Efficient
Pressure Balanced
People Friendly
Ve n
Quiet Operation
Energy Efficient
Automatic Control
t
il a
tio n
For over 30 years, RenewAire has been a pioneer in the use of plate exchangers that simultaneously tranfer heat and
humidity between ventilation airstreams in extreme climates. From cool-dry (Point Barrow, Alaska) to hot-humid
(Puerto Rico) climates, RenewAire exceeds customer expectations for effective, reliable ventilation solutions.
1980
First HRV and ERV installations using a variety of plate and wheel technologies.
ERV manufacturing begins using Mitsubishi “Lossnay” core.
1987
RenewAire model is the first listed by UL-1812 standard for ERV safety.
HVI residential unit certification confirms superior heat and humidity transfer.
1998
2006
New factory achieves LEED-Silver rating. 120,000th North American unit sold.
2007 sales result in 30,000 tons of CO2 emission reductions!
Introduction of RD Series dedicated outdoor air system.
2009
2004
Introduction of BREEZE® easy to install residential unit.
Energy Star Qualified with energy use in the lowest 20% of comparable buildings.
2007
2001
Over 100 school projects shipped in one year.
G4 - 4th generation core introduced with enhanced humidity transfer.
2005
1996
Introduction of first roof-top connected unit (RTC).
ARI-1060 commercial product certification of only ERV with 0% cross contamination.
2003
1983
2008
Introduction of V-Series Ventilation Exhaust Fans.
G5 - 5th generation core introduced with enhanced humidity transfer.
2010
Full Line of Ventilation Products
Residential & Small Commercial
• 5 Models
• 50 - 300 CFM
• built-in 24 V transformer/relay package
Commercial Products
•
•
•
•
23 Models
250 - 7,950 CFM
1 or 3 phase multi-voltage
24 volt control
Applied Products
• CA-Series (cabinet) - 500 - 20,000 CFM
• PA-Series (panelized) - 1,500 - Unlimited CFM
• (requires blowers & manifolds by others)
Dedicated Outdoor Air Systems
•
•
•
•
4 Models
500 - 4400 CFM
integrated VFD for each airstream
coil options including DX, chilled
water, hot water and combinations
Ventilation Exhaust Fans
•
•
•
•
4 Models
50 - 150 CFM
robust steel housing and duct collar
the most efficient line of exhaust fans
available in North America
This piece was printed using earth-friendly soy ink on 100% post-consumer recycled paper.
RenewAire ERVs are proudly manufactured in our LEED-Silver Certified facility using 100% wind generated electricity.
© RenewAire LLC, 2010