FMC Location #8442-1 411 Lone Pine Blvd. The Dalles, OR 97058

Transcription

FMC Location #8442-1 411 Lone Pine Blvd. The Dalles, OR 97058
CLR. - Clear Dimension is to face of finished material
D.
Where existing construction and/or finish is modified, repair to match existing
unless noted otherwise.
G.
Contractor shall coordinate with Owner for removal of all Owner items in existing
spaces of new construction.
Protect all existing finishes from damage, repair all damaged areas at no cost to
Owner.
See Mechanical & Electrical Drawings. Work shall comply with other General
Notes provided
H.
Fill all holes, cracks and recesses in concrete slab with non-shrink grout for a
smooth finish prepare to receive floor finishes.
I.
Verify and coordinate walls and framing thicknesses for recessed items. If there
are any discrepancies contact Architect prior to any work. Coordinate with
Mechanical and Electrical.
J.
Coordinate with Owner for salvaged items. Deliver those items to the Owner as
directed by Owner.
DeNovo
Other
This is a B occupancy building and tenant based on OAR 333-700, alternative method 05-02.
Greenfield
CONTRACTOR
MFIA
TBD
One area, storage/mech/water treatment, is treated as a special hazard and protected by both
sprinklers and separation from adjacent spaces with a 1 hour fire barrier.
Expansion
Nocturnal
AT
ACOUSTICAL
ADJUSTABLE
ALUMINUM
ABOVE FINISHED FLOOR
ANODIZED
HDCP.
HDR.
HM
HR.
HGT.
HVAC
HANDICAPPED
HEADER
HOLLOW METAL
HOUR
HEIGHT
HEATING VENTILATING & AIR CON.
B.L.
BITUM.
BLDG.
BD.
BRG.
BUS/RCPT
BRICK LEDGE
BITUMINOUS
BUILDING
BOARD
BEARING
BUSINESS/RECEPTION
ID
IE
INSUL.
INSIDE DIAMETER
INVERT ELEVATION
INSULATION
JB
JST.
JUNCTION BOX
JOIST
C
CAB.
CI
CER. T.
CH
CJ
CKT.
CL
CLG.
CLO.
CMU
CNTR.
COL.
CONC.
CONN.
CONS.
CONT.
CONTR.
CORR.
CP
CR
CRS
CSBA
CT
CTR.
CU
CONDUIT
CABINET
CAST IRON
CERAMIC TILE
COAT HOOK
CONTROL JOINT
CIRCUIT
CARPET LINE
CEILING
CLOSET
CONCRETE MASONRY UNITS
COUNTER
COLUMN
CONCRETE
CONNECTION
CONSULATION/OFFICE
CONTINUOUS
CONTRACTOR
CORRIDOR
CHROME PLATED
CRASH RAIL
COURSE
COLOR SELECTED BY ARCHITECT
CURTAIN TRACK
COUNTER
COPPER
KS
KW
KNEE SPACE
KILOWATT
LAB
LGW
LL
LLH
LLV
LP
LABORATORY
LEAD GLASS WINDOW
LEAD LINED
LONG LEG HORIZONTAL
LONG LEG VERTICAL
LIGHTPROOF
MAX.
M
MFR.
MIN.
M.0.
M/S
MTP
M/SURG.
MTG.
MAXIMUM
MIRROR
MANUFACTURER
MINIMUM
MASONRY OPENING
MIRROR & SHELF
METAL TOILET PARTITION
MINOR SURGERY
MOUNTING
NEC
NIC
N/S
NATIONAL ELECTRICAL CODE
NOT IN CONTRACT
NURSE STATION
DAPW
DN.
DWG.
DENS ARMOR PLUS WALLBOARD
DOWN
DRAWING
O.C.
O.D.
O.F.
O.F.I.C.
OFC.
OPP.
ON CENTER
OUTSIDE DIAMETER
OVERFLOW
OWNER FURNISHED, INSTALLED BY CONTRACTOR
OFFICE
OPPOSITE HAND
EDF
EUH
EWH
ELECT.
EJ
EA.
EL.
ELEV.
EMERG.
EP
ES
EQUIP.
EXIST.
EXT.
EXAM
EXP.
ELECTRIC DRINKING FOUNTAIN
ELECTRIC UNIT HEATER
ELECTRIC WALL HEATER
ELECTRIC
EXPANSION JOINT
EACH
ELEVATION
ELEVATOR
EMERGENCY
END PANEL
END SUPPORT
EQUIPMENT
EXISTING
EXTERIOR
EXAMINATION
EXPANSION
PA
P.H.
PB
PC
PD
PL
PLS
PTD.
PLWD.
PT
PARTITION ANCHOR
PANIC HARDWARE
PASS BOX
PIPE COLUMN
PENCIL DRAWER
PLATE
PLASTIC LAMINATE SHELF
PAINTED
PLYWOOD
PASS-THRU
QT.
QUARRY TILE
FACP
FD
FE
FEC
FG
FHC
FIN.
FLR.
FUT.
FTG.
FURR.
FIRE ALARM CONTROL PANEL
FLOOR DRAIN
FIRE EXTINGUISHER
FIRE EXTINGUISHER CABINET
FIXED GLASS
FIRE HOSE CABINET
FINISHED
FLOOR
FUTURE
FOOTING
FURRING
RD
REF.
REFR.
REF. SP.
REINF.
RM.
R.O.
R&S
RSA
RX
ROOF DRAIN
REFRACTORY
REFRIGERATOR
REFRIGERATOR SPACE
REINFORCING
ROOM
ROUGH OPENING
ROD & SHELF
RENTAL SUITE AREA
PRESCRIPTION DESK
GALV.
GA.
GALVANIZED
GAUGE
SIM*
SHT.
SFT.
SGW
SH.
SP
SIMILAR- SEE *NOTE FOR INFO
SHEET
SOFFIT
SLIDING GLASS WINDOW
SHELF
SUPPORT BRACKET
GB
GWB
GYP
GRAB BAR
GYPSUM WALLBOARD
GYPSUM
S/P
STL.
SPECIAL PROCEDURE
STEEL
STRUCT.
SS
SSP
SURG.
STRUCTURAL
STAINLESS STEEL
SCALE SPACE
SURGICAL
TC
TOC
TEL.
T&P
TEMJ
TOS
TLT.
TW
TYP.
TUBE COLUMN
TOP OF COLUMN
TELEPHONE
TEMPERATURE & PRESSURE
TOP ELEVATION MATCHES JOIST
TOP OF STEEL
TOILET
TYPEWRITER SPACE
TYPICAL
UL
URS
UNO
UNDERWRITERS LABORATORIES
UNDERCOUNTER REFRIGERATOR SPACE
UNLESS NOTED OTHERWISE
VWC
VB
VERT.
V.I.F.
VINYL WALL COVERING
VIEW BOX
VERTICAL
VERIFY IN FIELD
W/
WDW.
WG
WL
WP
WWM
W.D.
WITH
WINDOW
WIRE GLASS
WARNING LIGHT
WEATHERPROOF
WELDED WIRE MESH
WRITING DESK
ZFMR.
TRANSFORMER
PERSPECTIVE
REVISION DATE
Facility Room Space Standards
Jan. 2012
Standard Specifications
Jan. 2012
Standard Details
Jan. 2012
Color Materials Selection Form
Contract Document Checklist
Jan. 2012
I _______________________________________, architect of
record certify that to the best of my knowledge and belief, I
have incorporated to the fullest extent practical the latest
revision of RECS Documents, as noted above, into the
Contract Documents; and that I have reviewed the
Contract Documents to ensure that they meet the
requirements of RECS Contract Document Checklist, which is
available upon request.
Alex Hill, Principal
______________________________________
Name
APPLICABLE CODES
APPLICABLE CODE
DATE
SPECIAL PASSAGES
OREGON STRUCTURAL SPECIALTY CODE:
2010
903.1.1.1
907.2.6
NFPA 101:
NFPA 13 - FIRE SPRINKLERS:
NFPA 72 - FIRE ALARM:
2000
2009
2009
OREGON MECHANICAL SPECIALTY CODE:
2010
OREGON ELECTRICAL SPECIALTY CODE:
2007
OREGON PLUMBING SPECIALTY CODE:
2008
OREGON ADMINISTRATIVE RULES:
2010
OREGON ENERGY EFFICIENCY
SPECIALTY CODE:
2010
06/09/12
____________
Date
NFPA CERTIFICATION
NFPA 101, LIFE SAFETY CODE , 2000 CERTIFICATION
SPRINKLERS
FIRE ALARM
I______________________________, Architect of
record certify that the contract documents
comply with NFPA 101, Life Safety Code,
Chapter
20 or 21 and all referenced sections and other
NFPA codes.
Alex Hill, Principal
333-700-0130
Name
06/09/12
Date
CONSTRUCTION SET
Date: June 9th, 2012
DRAWING INDEX
ARCHITECTURAL
-GENERALT1.0
LS1.0
TITLE SHEET
FIRE AND LIFE SAFETY PLAN
-ARCHITECTURALA2.0
A2.3
A2.4
A2.5
A2.7
A2.8
A6.0
A6.1
A6.5
A6.6
A6.7
A6.8
A6.9
BLOCK CAN BE RESIZED AS NEEDED
@
ACOUS.
ADJ.
AL. OR ALUM.
A.F.F.
ANOD.
Portland, OR 97209
Fax: 503/224-7116
Above Habitable Space
See Detail AG-19 on Sheet A6.9 for the FMC Clinic Responsibility Schedule
ABBREVIATIONS
333 NW 5th Ave.
Phone: 503/224-4848
Renovation
FMC Family of Exterior Signage
PIC: John VanBladeren
MECH PM: Mark Denyer
ELECT PM: Ron Mart
TECH PM: Gary Adovnik
2007 SE Ash
Portland, OR 97214
(phone: contact Architect)
VICINITY MAP
Relocation
RECS DOCUMENT
There is a a smoke barrier subdividing the tenancy into two discreet compartments.
The building is fully sprinklered and includes smoke detection and fire alarm.
ENGINEER
BLOCK CAN BE RESIZED AS NEEDED
K.
.
FLOOR PLAN
FINISH FLOOR PLAN
EQUIPMENT / FURNISHINGS PLAN
CEILING PLAN
PARTITION TYPES, DOOR, & WINDOW
SCHEDULE
ROOM FINISH SCHEDULE
INTERIOR ELEVATIONS
INTERIOR ELEVATIONS
INTERIOR DETAILS
INTERIOR DETAILS
INTERIOR DETAILS
INTERIOR DETAILS
INTERIOR DETAILS
ENGINEERING
OTHERS
MECHANICAL
M1.0
MECH. SCHEDULES
M2.0
HVAC PLAN
M2.1
MECHANICAL ROOF PLAN
M3.0
MECH. DETAILS
P1.0
P2.0
P2.2
P2.4
P3.0
ME-1
PLUMBING SCHEDULES & DETAILS
PLUMBING FLOOR PLAN
PLUMBNG UNDERSLAB PLAN
PROCESS WATER PLAN
PLUMBING DETAILS
ELECTRICAL
E0.0
LIGHT FIXTURE SCHEDULE
E2.0
LIGHTING PLAN
E2.1
POWER PLAN
E2.2
TELCO FLOOR PLAN
E3.0
PANEL SCHEDULE / ONE LINE DIAGRAMS
E4.0
TELCO DETAILS / DIAGRAMS
E4.1
DIAGRAMS
E4.2
ELECTRICAL DETAILS
REVERSE OSMOSIS PROCESS
WATER DISTRIBUTION SCHEMATIC
DEFERRED
SPRINKLER SHOP DRAWINGS AND
HYDRAULIC CALCULATIONS BY:
DESIGN/BUILD CONTRACTOR - TBD
Drafted By: AH
Checked By: AK
Date Drawn:
6/9/12
Project #:
FIRE ALARM / DETECTION DRAWINGS AND
ELECTRICAL DESIGN BY:
DESIGN/BUILD CONTRACTOR - TBD
11054
DATE
F.
Portland OR,
97209
503-224-4848
2121 SW Broadway, Suite 111
Portland, OR 97201
* R.O. process water system designer / vendor
*FF&E - see Equipment / Furnishings Plan
Type of Project:
REV #
E.
PIC / PM - Alex Hill
Designer/ Tech - Ryan Dyson
333 NW 5th Ave.
PM: Gary Pete
Tenant build out for new dialysis clinic in a new building. Shell architect is Stack Architecture, see shell
plans for site work and related design. This projects consists of the build out of this single tenant building
to be an outpatient renal dialysis clinic. It includes 8 dialysis stations and 4 future stations. Space
includes home hemo dialysis traning and and exam room.
REVISION DESCRIPTION
C.
Clark//Kjos Architects
Fresenius Medical Services
CERTIFICATION THAT THE CONTRACT DOCUMENTS
CONFORM TO FRESENIUS MEDICAL CARE'S
DIALYSIS CLINIC STANDARDS
FMC LOCATION #8442-1
(address pending)
The Dalles, OR 97058
Dimensions are to face or center line of framing or structure as indicated by the
dimension leader line type;
PROJECT CLIENT*
FMC CERTIFICATION
FMC The Dalles
B.
ARCHITECT
Contractor to verify all conditions and dimensions, and notify Architect of any
discrepancies prior to any work.
PROJECT INFORMATION
BLOCK CAN BE RESIZED AS NEEDED
A.
PROJECT TEAM
Tenant Improvements
GENERAL NOTES
DO NOT CHANGE BLOCK LOCATION AND SIZE
FMC Location #8442-1
411 Lone Pine Blvd.
The Dalles, OR 97058
TITLE SHEET
SCALE: AS NOTED
T1.0
TITLE SHEET
GENERAL NOTES
1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR
VERIFYING THAT ALL TRADES ARE THOROUGHLY
FAMILIAR AND COMPLY WITH THE REQUIREMENTS
SHOWN HERE
39 SF
ROOM SCHEDULE
C
Room
EMERGENCY
GENERATOR
1
218
SF
A
EVACUATION
ROUTE
547
SF
FE
23
FE
R.O. & S.D.S.
SYSTEM
MONITORS
FIRE ALARM
ANNUNCIATOR
WAITNG
2
321 SF
15 SF
MED WASTE
SOILED HOLDING
JANITOR
CLINIC MANAGER
RECEPTION
VESTIBULE
MULTI PURPOSE
STAFF TOILET
STAFF TOILET
VISITOR TOILET
HOME HEMO
DR. / EXAM
CONFERENCE
HEMO NURSE
STAFF LOUNGE
STAFF LOCKERS
PATIENT TOILET
TREATMENT
SEPARATION
CLEAN UTILITY
CORRIDOR
CORRIDOR
HALLWAY
17
16
18
8
4
1
28
20
22
3
29
31
32
27
23
26
5
7
9
10
30
24
15
66 SF
39 SF
36 SF
122 SF
105 SF
85 SF
133 SF
62 SF
62 SF
53 SF
152 SF
141 SF
178 SF
84 SF
184 SF
30 SF
74 SF
2212 SF
127 SF
35 SF
163 SF
221 SF
57 SF
100 SF
100 SF
100 SF
100 SF
100 SF
100 SF
100 SF
100 SF
100 SF
100 SF
100 SF
100 SF
100 SF
100 SF
100 SF
100 SF
100 SF
100 SF
100 SF
100 SF
100 SF
100 SF
100 SF
WATER
TREATMENT
STORAGE
ELECTRICAL
WIRING CLOSET
MED RECORDS
RISER ROOM
WATER HEATER
TECH REPAIR
139
SF
2
11
405 SF
300 SF
14
19
21
6
25
12
13
396 SF
60 SF
73 SF
69 SF
35 SF
17 SF
216 SF
300 SF
300 SF
300 SF
300 SF
300 SF
300 SF
300 SF
2. ALL RATED ASSEMBLIES SHALL BE CONSTRUCTED
TO PREVENT THE MOVEMENT OF FLAME OR GASSES
PER CODE.
21.415782
21.415782
0.656181
0.39423
0.361128
1.220488
1.047676
0.853448
1.325015
0.617969
0.61689
0.52533
1.518253
1.414176
1.775827
0.842946
1.835493
0.29855
0.738147
22.123438
1.273765
0.347528
1.627083
2.20868
0.572908
44.195147
1.349814
3. INSTALL RATED ENCLOSURES FOR ALL RECESSED
ITEMS IN RATED WALLS PER CODE. SEE
ARCHITECTURAL DETAILS.
4. ALL PENETRATIONS THROUGH RATED ASSEMBLIES
IN AREA OF WORK SHALL BE FIRESTOPPED OR
SEALED PER CODE.
5. SEE FLOOR PLAN FOR WALL CONSTRUCTION
6. LABEL ALL FIRE WALLS PER DETAIL AG-22/A6.9
LEGEND
ROOM NAME
Occupancy Type
SQ.FT.
Occupancy Calc.
Occ / Sf
ROOM OCCUPANCY TAG
1 HOUR WALL (SPECIAL
HAZARD) ROOMS*
SMOKE BARRIER*
* RATED WALLS MUST EXTEND
TO UNDERSIDE OF ROOF DECK.
SEE WALL TYPES FOR TOP OF
WALL CONDITIONS
1.319931
0.201391
0.244321
0.230017
0.117061
0.057416
0.719459
4.23941
69.850339
FE
VAN
23
999
OCCUPANT EXIT LOAD
DOOR ASSEMBLIES:
20 MIN.
AT SMOKE BARRIER - HG DOORS
EXEMPT FROM HOSE STREAM
TEST
45 MIN.
AT SPECIAL HAZARD ROOMS
CODE REVIEW
FE
PROJECT NAME:
FMC The Dalles
ADDRESS:
411 Lone Pine Blvd.
The Dalles, OR 97058
OWNER:
Fresenius Medical Care
CODES:
OREGON STRUCTURAL SPECIALTY CODE 2010
NFPA 101- CHAPTER 38
OCCUPANCY:
GROUP B
FE
137
SF
FIRE EXTINGUISHER
EXIT SIGN, ARROW(S) INDICATES
DIRECTION (IF SHOWN)
FE
ELECTRICAL
ROOM
527
SF
Portland, OR 97209
Fax: 503/224-7116
C
Factor
333 NW 5th Ave.
Phone: 503/224-4848
C
Area
NUMBER OF STORIES: One
CONSTRUCTION TYPE:
V-B
FIRE PROTECTION:
FULLY SPRINKLED
FIRE ALARM SYSTEM:
YES
FMC LOCATION #8442-1
(address pending)
The Dalles, OR 97058
Circulation
Number
FMC The Dalles
Name
Tenant Improvements
Divisions
Occupant
Load
ALLOWABLE SQUARE FOOTAGE: (TABLE 503)
(see original shell documents - no change)
23
ACTUAL SQUARE FOOTAGE: Tenant Space = 6,684 gsf
SPRINKLER
RISER ROOM
FIRE SEPARATION DISTANCE: >10'
MAXIMUM AREA OF EXTERIOR WALL OPENINGS:
UNPROTECTED, SPRINKLERED
30' OR GREATER- NOT REQUIRED
TOTAL OCCUPANT LOAD = 70 (SEE TABLE FOR CALCULATION BASIS)
RATED GYPSUM WALL BOARD
ASSEMBLY
MAX. COMMON PATH OF TRAVEL (1014.3):
75 FT (100' W/ SPRINKLER)
METAL STUD / BLOCKING AS
REQUIRED
MAX. TRAVEL DISTANCE(1016.1):
200 FT (300' W/ SPRINKLER)
FIRE RESISTIVE RATINGS: (TABLE NO. 60I, 602 OF THE I.B.C.)
METALLIC PIPE w/ UP TO 1"
FIBERGLASS INSULATION
1/8" = 1'-0"
REPRESENTATIVE SAMPLES OF ACCEPTABLE RATED WALL PENETRATION DETAILS. ALL PENETRATIONS
TO BE SEALED WITH APPROVED RATED ASSEMBLIES
STEEL, IRON OR COPPER PIPE
OR CONDUIT
RATED GYPSUM WALL BOARD
ASSEMBLY
0 HOUR
0 HOUR
0 HOUR
0 HOUR
Drafted By: AH
Checked By: AK
0 HOUR
Date Drawn:
0 HOUR
0 HOUR
Project #:
6/9/12
11054
RATED GYPSUM WALL BOARD
ASSEMBLY
PVCC 2" CLOSED PIPE OR
CONDUIT
FIRE SEALANT TO FULL DEPTH
OF WALL BOARD. ADD A
GENEROUS CROWN.
TYPE V-B
0 HOUR
FIRE SEALANT FULL WIDTH OF
WALL BOARD.
DATE
ELECTRICAL, TELEPHONE, DATA
CABLES.
ROUND STEEL HVAC DUCT
ELECTRICAL, TELEPHONE OR
DATA CABLE
RECTANGULAR STEEL HVAC DUCT
FIRE SEALANT OR PUTTY 5/8"
DEPTH w/ 3/8" CROWN FOR
1 HOUR RATING.
STEEL FLANGE - FASTEN TO DUCT,
& SECURE TO DRYWALL w/ 3/16"
EXPANDING ANCHORS & 1-1/4"
FENDER WASHERS. DRILL 3/4"
HOLES IN FLANGE FOR ANCHORS
TO ALLOW FOR MOVEMENT.
1-1/4" MIN. FIRE SEALANT
WITH 1/4" CROWN
RATED GYP. BRD. ASSEMBLY
6pcf MINERAL WOOL TO FULL
DEPTH OF CAVITY
ANNULAR SPACE - 1/2" MAX.
ANNULAR SPACE 1/4" MAX.
ANNULAR SPACE - 3/4" MAX.
NOTE: NOT SUITABLE FOR USE WITH
FIRE OR FIRE/SMOKE DAMPERS
NOTE: NOT SUITABLE FOR USE WITH
FIRE OR FIRE/SMOKE DAMPERS
HVAC/DUCTWORK - GYP. BRD. WALL
WGDM1HRB.dwg / (NOT TO SCALE)
date: 9/23/96
UL #1479 SYSTEM # W-L-1049R.
ELECTRICAL CABLE - GYP. BRD. WALL
STI DRAWING #EJ2010
WGEN1HRA.dwg / (NOT TO SCALE)
date: 9/23/96
REV #
1
FIRE AND LIFE SAFETY PLAN
BUILDING ELEMENT (>10' SEPARATION)
STRUCTURAL FRAME
BEARING WALLS
EXTERIOR
INTERIOR
NON BEARING WALLS AND PARTITIONS
EXTERIOR
INTERIOR
FLOOR CONSTRUCTION
INCLUDING SUPPORTING BEAMS AND JOISTS
ROOF CONSTRUCTION
INCLUDING SUPPORTING BEAMS AND JOISTS
EXTERIOR DOORS AND WINDOWS
REVISION DESCRIPTION
STEEL OR IRON PIPE CONDUIT
OR EMT.
UL #1479. SYS. # W-L-3024
MULTIPLE PENETRANTS - GYP. BOARD. WALL
STI DRAWING #DS1018
WGMM1HRA.dwg / (NOT TO SCALE)
date: 9/23/96
UL #1479 SYSTEM W-L-8003
HVAC/DUCTWORK - GYP. BRD. WALL
STI DRAWING #DS1053
WGDM1HRA.dwg / (NOT TO SCALE)
UL #1479 SYSTEM W-L-1049
date: 9/23/96
STI DRAWING #EJ2011
LS1.0
FIRE AND LIFE
SAFETY PLAN
1
1.
SEE PARTITION TYPES SHEET FOR LEGEND
AND CONSTRUCTION ASSEMBLIES.
2.
ALL DIMENSIONS TO FACE OF STUD
UNLESS OTHERWISE NOTED.
3.
SEE MECHANICAL AND ELECTRICAL FOR
ADDITIONAL INFORMATION.
4.
SEE PLUMBING FOR ACTUAL ROUTING. FMC
STANDARD DETAILS PROVIDED FOR
REFERENCE AND INTENT.
5.
SEE SHEET A6.9 FOR INSTALLATION
RESPONSIBILITY SCHEDULE
A
WINDOW TYPES - SEE SHEET A2.7
A
8
A8
5
6' - 9 3/8"
A6
P74
P FRP-8'
P89
AT-CU A6.7
F71
P FRP-8'
P-3
9
4
WATER HEATER
12
R14
A
A6.5
P74
P FRP-8'
18 SF
6' - 2 1/2"
AS-6
12
17 SF
11
DOMESTIC
WATER
HEATER
12
A3
10' - 6"
7
15' - 7"
7
2212 SF
8
14' - 4"
A5
A12
A5
3
3
MED PREP
P-4
A6.1
2
P-3
4
F71
5
9
A8
A10
A11
13' - 4"
9
11
A6.0
A5
A6
4
A6.1
6
Eq.
A10
P74
VALVE BOX
OFOI EMPLOYEE TIME CLOCK. PROVIDE
POWER/DATA
PROVIDE 5" THICK FLOOR SLAB AND VAPOR
BARRIER THROUGHOUT
42" HIGH WALL WITH WOOD VENEER FINISH
CHASE FOR R.O. WATER LOOP. SEE AS-37 ON
SHEET A6.9
SLEEVE THROUGH WALL FOR R.O. LOOP
FIRE EXTINGUISHER CABINET
NO VERTICAL CHASE BEHIND THIS SINK.
PROVIDE WIDE SPLASH GUARD ACROSS WIDTH
OF COUNTER. SEE PLUMBING DRAWINGS FOR
PLUMBING ROUTING
FIXED ACCESS LADDER TO ROOF HATCH.
COORDINATE PRECISE LOCATION WITH SHELL
DOCUMENTS
SYMBOL LEGEND
TYP. ALL
EXTERIOR
WALLS
10
15
A6.0
1/4:12
SLOPE
2
16
MODIFIER
C
10' - 4 1/2"
A3
EM-SHOWER
12
A
A11
WALL TAG
STUD SIZE
ASSEMBLY
GROUP
A3
STORAGE
SURFACE SLOPE
A11
14
?
396 SF
KEYNOTE
1
P-3
A6
5' - 2"
A5
CLR
5' - 2"
17
66 SF
57 SF
7' - 6 1/8"
11' - 0"
R14
16
24B
6' - 1"
19
6' - 5"
P74
A
R14
39 SF
A6.1
14
R14
A
15
5' - 6 1/2"
P MR
SIM*
R14
A6.8
F71
6' - 6 3/4"
18' - 6 5/8"
A10
18
A
S04
P MR
JANITOR
18
AA-4
36 SF
P-8
A
S04
AS-3
E
STAFF LOCKERS
26
A2
30 SF
(E)25
AP-10
CLR
7' - 1"
AA-11
G
VISITOR TOILET
3
AP-9
A6.0
P74
A
A
P74
A
P06
AA-11
STAFF TOILET
A6.6 AA-10
22
4
WAITNG
7' - 5"
4
FLOOR PLAN
2
3
P74
A
DRAWING NUMBER
4
A3.00
2
P74
P-5
19
29
P74 HEMO NURSE
1 1/4"
1 1/4"
A6.1
31
27
84 SF
18
P74
A
HOME HEMO
152 SF
P-11
A6.6
P74
A
AA-5a
A
P74
A6.1
31
141 SF
A
P74
5' - 0"
P-10
CLR.
8' - 1 7/8"
14' - 4 3/4"
Date Drawn:
6/9/12
Project #:
11054
DIMENSION TO FACE OF
FRAMING, FACE OF
CONCRETE, GRID
LINE, OR AS NOTED.
PROJECT NORTH
(SEE CIVIL FOR TRUE
NORTH)
2
(E) 98.75'
A6.5
AA-5
Checked By: AK
NORTH ARROW
P-6
29
Drafted By: AH
CLEAR DIMENSION TO
FINISH FACE OR AS NOTED
178 SF
DR. / EXAM
INTERIOR ELEVATION
SHEET NUMBER
3
32
CORRIDOR
DRAWING NUMBER
EXTERIOR ELEVATION
SHEET NUMBER
1
30
P74
A3.00
3' - 4 1/8"
CLR
30
WALL SECTION
1
10' - 11 3/4"
P74
SIM
2
62 SF
24A
BUILDING SECTION
A101
A
P74
321 SF
P74
22
1
3
3
A
P74
SIM
A101
P74
A6.6
MULTI PURPOSE
28
A3
2
53 SF
A10
1
EXISTING SPOT ELEV
TYP.
F71
98.75'
TYP. ALL
EXTERIOR
WALLS
(E)24
5' - 0 5/8"
CALLOUT
32
+/- 10' - 11 3/4"
20
DRAWING NUMBER
SIM
CONFERENCE
7' - 0"
A6.1
(E)1
163 SF
21
35 SF
1/4" = 1'-0"
2
P74
A
RISER ROOM
1
H
NC
62 SF
A6.6 AA-10
27
R14
5' - 1 3/4"
A
S04
85 SF
ROOM TAG
150 SF
ROOM NUMBER
(Area-Program SF)
DRAWING REVISION
1
1
A101
20
20
CLR.
184 SF
25
A6.8
A
P76
10' - 5 1/2"
5' - 0"
CTR. OPENING
ON OPP.
CORRIDOR
23
101
A6.0
1
A
P74
ELEVATION TAG
Room name
A
R14
1
6
28
STAFF LOUNGE
A
R14
A6.0
5
CEILING MATERIAL
CEILING TAG
CEILING HEIGHT ABOVE
FINISHED FLOOR- ALL
CEILINGS 9'-0" UNLESS
OTHERWISE NOTED.
F74
VESTIBULE
69 SF
P74
A3
NC
6
STAFF TOILET
221 SF
16
AP-9
A
R14
122 SF
24
A6.1
A6.6 AP-10
105 SF
MED RECORDS
133 SF
23
F71
Name
Elevation
4
6
S04
A
CORRIDOR
17
9'-0"
74 SF
7
RECEPTION
P74
P-5
5
WINDOW TYPE REF WINDOW SCH
WINDOW TAG
SHEET NUMBER
6' - 4 1/2"
F71
P
P06
A
7' - 10 3/4"
21
1t
S04
8
73 SF
G
4
CLINIC MANAGER
21
PATIENT TOILET
CLR
8
P-3
WIRING CLOSET
5
P74
A
5' - 6"
9' - 6"
A10
16
FINISH TAG
REVISION DESCRIPTION
19
6' - 4 3/4"
8
A-1
P89
A6
SOILED HOLDING
P-14
60 SF
P-3H
A6.0
E
ELECTRICAL
P74
A
DATE
R14
R14
LAB PREP
15
17
MED WASTE
7' - 7 5/8"
P-3
101
DOOR NUMBER REF DOOR SCH
DOOR TAG
6' - 9"
7
P-15
HALLWAY
P74
3' - 7 1/2"
A5
14
R14
A
3' - 6"
11' - 3 1/2"
R14
A
(E)17
A6.1
8' - 10 3/4"
10' - 6"
P-3
1
3' - 1"
A12
(E)14
13' - 4 3/4"
10' - 11 3/8"
REV #
TECH REPAIR
A1
A2
(E)7
A6.0
7' - 6"
A6.8
AS-13
4' - 3 1/2"
KEYNOTES
A10
14
10' - 6"
A
A62
216 SF
A
C
P04
6' - 8 3/4"
A11
10
13
A6.0
Eq.
A6.6
TECH REPAIR
P-15A
TREATMENT
SLIDING GATE
AS-11
P74
P FRP-8'
9
13
P-3
7' - 6"
TRENCH DRAIN
12
13
12
5' - 2 7/16"
35 SF
A6.1
10
J
A6.0
10
127 SF
11
P74
10
CLEAN UTILITY
11
9
C
A6.0
R14
A
SEPARATION
333 NW 5th Ave.
Phone: 503/224-4848
P74
WALL SCONCES
TYP. SEE
ELECTRICAL
FMC LOCATION #8442-1
(address pending)
The Dalles, OR 97058
R14
A
6
FMC The Dalles
11
405 SF
TYP. ALL
EXTERIOR
WALLS
P-3
Tenant Improvements
1
WATER TREATMENT
7
8' - 11 3/8"
8
A
P04
4' - 3 1/2"
FRP-8'
A62
P
14' - 10 1/2"
F71
P FRP-8'
F71
10' - 7"
F71
P FRP-8'
A1
A8
4' - 9"
O
Portland, OR 97209
Fax: 503/224-7116
GENERAL NOTES / LEGEND
NEW SPOT ELEV
A2.0
FLOOR PLAN
1
A
GENERAL NOTES
F1
WATER TREATMENT
SEPARATION
11
9
VERTICAL FACE
OF SOFFIT - PA-2
2. FILL ALL HOLES CRACKS AND RECESSES IN
CONCRETE FLOOR WITH NON-SHRINK
GROUT FOR A SMOOTH FINISH PREPARED
TO RECEIVE FLOOR FINISH.
CG
CG
CG
3. HEAT WELD ALL SHEET VINYL SEAMS.
CG
4. TOP-SET RUBBER OR VINYL WALL BASE,
WHERE USED, SHALL BE SEALED TIGHTLY TO
THE FLOOR AS WELL AS TO THE WALL.
F1
CLEAN UTILITY
CG
10
TYP. ALL
WALLS THIS
ROOM
5. PROVIDE TRANSITION STRIP WHERE
FLOORING CHANGES
F6
CG
F6
6. SEE FINISH SCHEDULE SHEET A2.8 FOR
PAINT LOCATIONS
333 NW 5th Ave.
Phone: 503/224-4848
CG
Portland, OR 97209
Fax: 503/224-7116
1. REFER TO INTERIOR FINISH
SPECIFICATIONS FOR CODE DESCRIPTIONS
AND ADDITIONAL INFORMATION.
TYP. ALL
WALLS THIS
ROOM
WATER HEATER
12
VERTICAL
FACE OF
SOFFIT - PA-2
VERTICAL FACE
OF SOFFIT - PA-2
TREATMENT
7
CG
CG
LEGEND
P-n
CG
CHR CHAIR RAIL
TECH REPAIR
F1
FINISH ABOVE CHAIR RAIL
P-n
13
TYP. ALL
WALLS THIS
ROOM
FINISH BELOW CHAIR RAIL
WALL PROTECTION
CG
CG
CORNER GUARD - SEE DETAIL AG-4/A6.5
CG
FLOOR FINISH MATERIALS
F6
CG
SV-1 (FIELD)
CG
F1
TYP. ALL
WALLS THIS
ROOM
F6
SV-2 (ACCENT)
CG
AS-5
CG
A6.8
TYP.
.
.
CG
CG
CG
CG
EPOXY FLOOR W/ 6" COVE
CG
CG
F1
HALLWAY
17
TYP. ALL
WALLS THIS
ROOM
SEALED CONCRETE
CG CG
MED WASTE
PATIENT TOILET
VERTICAL FACE
OF SOFFIT - PA-2
15
5
SOILED HOLDING
16
F5
TYP. ALL WALLS
THIS ROOM
ELECTRICAL
FMC LOCATION #8442-1
(address pending)
The Dalles, OR 97058
CPT-2 (walk off carpet)
Tenant Improvements
EPOXY
FMC The Dalles
CPT-1
RECEPTION
19
4
VESTIBULE
CHR
1
JANITOR
18
CLINIC MANAGER
MED RECORDS
8
6
F5
F5
- FINISH KEYNOTES-
WIRING CLOSET
21
CG
CG
F1
F5
CHR
P1
CHR
PA-1
STAFF TOILET
VISITOR TOILET
20
3
F6
MULTI PURPOSE
WAITNG
28
2
CHR
CORRIDOR
CHR
CHR
TYP. THIS
ROOM
24
CG
WC-1
CHR
WC-2
CLASS A FRP TO 8-0" A.F.F.
CLASS A FRP TO 4' A.F.F. J CHANNEL ON EXPOSED EDGES SILICONE SEALANT
HEAVY DOTTED LINE INDICATES EXTENT OF COVED BASE AT
NURSE STATION. USE RB-1 AROUND INTERIOR OF NURSE
STATION AND AROUND SINK SUPPORTS.
CHR
CHR
STAFF TOILET
CHR
Drafted By: AH
CHR
22
Checked By: AK
P1
CHR
PA-1
Date Drawn:
CG
STAFF LOUNGE
CORRIDOR
23
30
6/9/12
Project #:
CHR
11054
REVISION DESCRIPTION
P1
CHR
PA-1
CG
P1
CHR
PA-1
CONFERENCE
CG CG
25
29
31
2
A6.5
HEMO NURSE
27
STAFF LOCKERS
REV #
RISER ROOM
DR. / EXAM
DATE
CHR
HOME HEMO
CHR
32
26
CG CG
CHR
A2.3
1
FINISH PLAN
1/4" = 1'-0"
FINISH FLOOR
PLAN
1
EQUIPMENT SCHEDULE
8
O
RO
RO
RO
RCL
RCL
RO
RCL
RCL
RCL
EQUIPMENT BY WATER
TREATMENT VENDOR. SEE
OTHER SHEETS AND
SPECIFICATION FOR WORK
REQUIRED
1
TV
TV
TV
TV
TV
TV
RCL
CHR-T
12
4
18 SF
DOMESTIC
WATER
HEATER
RO
TV
RO
RCL
CC
RO
TV
RCL
RO
TV
RCL
UC-REF
TV
RCL
RO
TV
RCL
HD-STOR
RO
CHR-T
RCL
CHR-T
Bookcase
Crash Cart
Chair - Lounge
Chair - Side
Chair - Task
Chair - Waiting Room
Portland, OR 97209
Fax: 503/224-7116
BOOK
1
CC
1
CHR-LNG
16
CHR-S
2
CHR-T
10
CHR-W
12
COF
1
COP
1
CPU
7
DESK-2x5
6
FILE-L
4
HD-STOR
1
HOYER
1
MIC
1
RCL
14
REF-F
1
RO
13
SCA
1
SCA-READ
1
SHRED
1
STL
1
TBL-42x96
1
TBL-END
3
TBL-EXAM
1
TBL-RND
2
TIME CLOCK
1
TV
17
UC-REF
4
WCHR
5
Coffee Maker
Copier
Computer
Desk - 2'x5'
Lateral File
High Density Storage System
Hoyer Lift
Microwave
Recliner
Refrigerator - Full Height
333 NW 5th Ave.
Phone: 503/224-4848
A
Reverse Osmosis Machine
Patient Scale
Scale Read Out
Shredder
Physician Stool
Table - 42" x 96"
Table - End
Table - Exam
Table - Rount
Employee Time Clock
Television
Refrigerator - Under Counter
Wheel Chair
RO
TV
WCHR
TV
RCL
Tenant Improvements
HOYER
SCA
UC-REF
SCA-READ
COP
DESK-2x5
FMC LOCATION #8442-1
(address pending)
The Dalles, OR 97058
WCHR
FMC The Dalles
RO
CPU
SHRED
BOOK
CHR-T
CHR-T
CPU
FILE-L
FILE-L
DESK-2x5
CHR-W CHR-W TBL-END
CPU
CHR-W
CHR-T
FILE-L
REF-F
COF
MIC
DESK-2x5
CHR-T
WCHR
CPU
TBL-RND
CHR-W
CHR-W
CHR-W
CHR-W
CHR-W
WCHR
CHR-LNG
CHR-LNG
CHR-W
TV
TBL-END CHR-W CHR-W CHR-W TBL-END
WCHR
CHR-LNG
Drafted By: AH
Checked By: AK
Date Drawn:
CHR-LNG
CHR-LNG
6/9/12
11054
REVISION DESCRIPTION
Project #:
UC-REF
CHR-LNG TBL-RND CHR-LNG
DESK-2x5
CHR-LNG
TV
CHR-LNG
CHR-LNG
CHR-LNG
CHR-LNG
TV
FILE-L
CHR-T
UC-REF
CPU
TBL-42x96
STL
CHR-LNG
CHR-LNG
CHR-LNG
CHR-LNG
TBL-EXAM
RCL
DATE
DESK-2x5
CHR-T
CPU
RO
CHR-T
TV
REV #
CPU
TIME
CLOCK
DESK-2x5
A2.4
1
EQUIPMENT / FURNISHINGS PLAN
1/4" = 1'-0"
EQUIPMENT /
FURNISHINGS
PLAN
GENERAL NOTES
1
A
1. ALL CEILING HEIGHTS ARE RELATIVE TO TOP OF SLAB OR SUBFLOOR, U.N.O.
3. FIELD VERIFY EXISTING CEILING LAYOUTS PRIOR TO ANY WORK.
6
SCONCE
7
SCONCE
8
SCONCE
11
C6
C6
C6
4. SUSPENSION SYSTEMS FOR NEW AND EXISTING SUSPENDED GYPSUM BOARD
CEILINGS SHALL BE MODIFIED TO FRAME AROUND CEILING INSTALLED ITEMS. SEE
MECHANICAL AND ELECTRICAL DRAWINGS.
5
SEPARATION
10' - 0"
9
C6
5. INSTALL BLOCKING AND BACKING FOR WINDOW COVERING TRACKS.
6. FOR TOP OF WALL DETAILS AND HEIGHT OF GYP BOARD ON WALLS, SEE PLANS,
PARTITION TYPES, AND DETAILS.
10' - 0"
TV
TV
EQ
TV
3'
EQ
EQ
2' - 3"
TV
EQ
7. RECESSED FIXTURES ARE TO MAINTAIN RATINGS WHERE LOCATED IN RATED CEILING
ASSEMBLIES.
C4
8. PROVIDE ROLLER SHADES AT ALL EXTERIOR WINDOWS AND INTERIOR RELITES
EQ
C3
12' - 0"
0"
Portland, OR 97209
Fax: 503/224-7116
WATER
TREATMENT
2. SEE ELECTRICAL AND MECHANICAL PLANS FOR LOCATIONS OF FIXTURES AND
EQUIPMENT.
TV
333 NW 5th Ave.
Phone: 503/224-4848
EQ
9' - 0"
9
2' - 0"
ROOF
16' - 0"
4
EQ
TV
C6
GYPSUM BOARD CEILING
FIRE SEAL ALL
PENETRATIONS
C2
ACT-1: "2x2"
10' - 0"
3
PROVIDE SUSPENSION /
SEISMIC ANCHORAGE FOR
FIXTURES, CEILINGS ETC.
MED PREP
C6
8' - 6"
TREATMENT
11
STRIP FIXTURE
ACT-2: 2"X2" MOISTURE
RESISTANT CEILING TILE
CERTAINTEED AQUAROCK OR
APPROVED EQUAL
CEILING
7
3
TV
A2.5
WALL MOUNTED LINEAR
DIRECT/INDIRECT
WATER TREATMENT
ROOM BEYOND
SCONCE
TV
EQ
SCONCE
2
CEILING TAG
CEILING HEIGHT
C6
7
10' - 0"
9'-0"
FIRE SEAL
AROUND JOIST
PENETRATIONS
TREATMENT
10
CEILING MATERIAL
A2.5
10' - 0"
STORAGE
2 x 4 DROP-IN FIXTURE
SCONCE
SCONCE
2
TV
EQ
8' - 0"
OPEN TO ABOVE
2' - 0"
TV
C6
12
UNDERCABINET LIGHT
R.O. CONDUIT RISER
IN CORNER OF
CLEAN UTILITY
14
SUSPENDED LINEAR
LIGHTING
PENDANT LIGHT
ROLLER SHADE
RECESSED DOWNLIGHT
WALL SCONCE
SCONCE
5' - 3"
CEILING KEYNOTES
TV ON
SOFFIT
(TYP.)
EQ
C6
EQ
7' - 2"
1' - 6"
GATE
C7
2
PLAN - SITE
0' - 0"
Rated Wall @ Mech.
1/2" = 1'-0"
C2
C3
C4
C6
C7
C8
C9
Tenant Improvements
C8
PROVIDE POWER AND DATA CONNECTIONS FOR OFOI TV (SEE DETAIL AT-49)
PENDANT FIXTURE AT SINK (TYP @ 4) SEE ELECTRICAL
CENTER TV ON WALL ABOVE DOOR
ROLLER SHADES -ALL WINDOWS
GYP. SOFFIT ABOVE CASEWORK, COORDINATE WITH CASEWORK DETAILS
ROOF HATCH ABOVE. COORDINATE W/ SHELL DOCUMENTS
LOWER SECTION OF GYP. SOFFIT ABOVE CASEWORK
MED WASTE
1' - 6"
17
PATIENT TOILET
1' - 6"
5
1' - 6"
10' - 0"
8' - 0"
8' - 0"
EQ
FMC LOCATION #8442-1
(address pending)
The Dalles, OR 97058
2' - 01'1/4"
- 11 13/16"
TV
8' - 0"
RATED WALL TERMINATES TO
UNDERSIDE OF DECK W/
APPROVED RATED ASSEMBLY
FMC The Dalles
SCONCE
LEGEND
EQ
SOILED HOLDING
16
ELECTRICAL
C6
C6
19
8' - 0"
CLINIC MANAGER
RECEPTION
8
4
8' - 0"
JANITOR
9' - 0"
18
1
9' - 0"
7' - 2"
MED RECORDS
WIRING CLOSET
C6
6
21
9' - 0"
ROOF
16' - 0"
C7
9' - 0"
8' - 0"
STAFF TOILET
8' - 0"
VESTIBULE
8' - 0"
PROVIDE SEISMIC RESTRAINT
AS REQUIRED
20
VISITOR TOILET
3
8' - 0"
MULTI PURPOSE
28
STAFF TOILET
WAITNG
TV ON
SOFFIT
8' - 0"
CEILING / SOFFIT BRACING AS
REQUIRED BY CONTRACTOR
2
10' - 0"
Drafted By: AH
9' - 0"
22
9' - 0"
Checked By: AK
C6
STAFF LOUNGE
9' - 0"
Date Drawn:
8' - 0"
6/9/12
Project #:
11054
REVISION DESCRIPTION
23
C9
7' - 2"
C6
9' - 0"
C6
C6
10' - 0"
7' - 2"
C6
9' - 0"
C7
HEMO NURSE
RISER ROOM
HOME HEMO
DR. / EXAM
29
31
DATE
CONFERENCE
32
REV #
27
2
25
A6.5
9' - 0"
C6
STAFF LOCKERS
NO CEILING
26
C6
9' - 0"
C7
C6
9' - 0"
C6
C6
C6
7' - 2"
PLAN - SITE
0' - 0"
2
A6.5
1
RCP - LEVEL 1
1/4" = 1'-0"
Sim
TYP. AT ROOMS
23, 27, 29 & 31
3
SECTION THROUGH TREATMENT ROOM
1/2" = 1'-0"
A2.5
CEILING PLAN
DOOR SCHEDULE
DOOR
FRAME
STRUCTURE
2 1/2"
ROOM
MARK NUMBER
METAL DECK
BRACE STUDS TO STRUCTURE- @
4'-0" O.C. ALTERNATING EACH WAY.
USE SAME GAUGE AS STUDS, MAX.
LENGTH 6'-0"
FIRE SEALANT
6"
(2) 2 1/2" METAL STUDS
(E)1
(E)7
(E)14
(E)17
(E)24
(E)25
2
3
4
5
6
7
8
9
10
11
12
14
16
17
18
19
20
21
22
23
24A
24B
27
28
29
30
31
32
5/8" TYPE 'X' GWB @ RATED
CONDITION
CEILING - SEE ROOM FINISH
SCHEDULE AND RCP FOR HEIGHT
AND FINISH
CEILING - SEE ROOM FINISH
SCHEDULE AND RCP FOR HEIGHT
AND FINISH
1 LAYER 5/8" GWB
3 1/2" ACOUSTIC BATT INSULATION
BASE- SEE FINISH SCHEDULE
BASE- SEE FINISH SCHEDULE
SECTION
SECTION
FIRE SEALANT @
RATED CONDITION
METAL FRAMING
2 1/2"
5/8" GWB
5/8" TYPE 'X' GWB @ RATED CONDITION
X
1"
3 1/2" ACOUSTIC BATT INSULATION
2 1/2"
*NOTE: THIS IS ALSO A
RATED WALL WHERE
ADJACENT WATER
TREATMENT.
A62
A6
PLAN
(2) 2 1/2" METAL STUDS
PLAN
STC = 63-64
GA FILE NO. WP 5006
X = 7 1/4"
P72
ACOUSTIC WALL 63 STC RATING
X = 3 3/4"
P74
X = 4 7/8"
P76
X = 7 1/4"
1 1/2" = 1'-0"
6
A2.7
BAR JOISTS
PARALLEL
PERP.
DEFLECTION TRACK
AT DECK, DO NOT
ATTACH TO BOTTOM
OF BAR JOISTS
PARTITION WALL
P7
ROOF DECK
SIZE
FIRE
HD
WIDTH HEIGHT TYPE MATERIAL TYPE FINISH RATING WR
ROOM NAME
VESTIBULE
TREATMENT
STORAGE
MED WASTE
CORRIDOR
RISER ROOM
VESTIBULE
VISITOR TOILET
RECEPTION
PATIENT TOILET
MED RECORDS
TREATMENT
CLINIC MANAGER
SEPARATION
CLEAN UTILITY
WATER TREATMENT
WATER HEATER
STORAGE
SOILED HOLDING
MED WASTE
JANITOR
ELECTRICAL
STAFF TOILET
WIRING CLOSET
STAFF TOILET
STAFF LOUNGE
CORRIDOR
CORRIDOR
HEMO NURSE
MULTI PURPOSE
HOME HEMO
CORRIDOR
DR. / EXAM
CONFERENCE
8' - 6"
4' - 0"
6' - 0"
3' - 0"
3' - 0"
3' - 0"
8' - 6"
3' - 0"
3' - 0"
3' - 0"
3' - 0"
3' - 6"
3' - 0"
3' - 6"
3' - 0"
4' - 0"
5' - 0"
3' - 6"
3' - 0"
3' - 0"
3' - 0"
3' - 0"
3' - 0"
3' - 0"
3' - 0"
3' - 0"
3' - 0"
3' - 0"
3' - 0"
3' - 0"
3' - 0"
3' - 0"
3' - 0"
3' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
8' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
7' - 0"
ELEC
STOR
F
F
F
F
ELEC
F
N
F
F
N
F
FG
F
SLID
F
N
F
F
F
F
F
F
F
N
FG
N
F
F
F
F
F
N
AL
AL
HM
HM
HM
HM
AL
WD
WD
WD
WD
WD
WD
WD
WD
HM
WD
WD
WD
WD
WD
WD
WD
WD
WD
WD
WD
WD
WD
WD
WD
WD
WD
WD
AL
AL
HM
HM
HM
HM
AL
HM
HM
HM
HM
HM
HM
HM
HM
HM
HM
HM
HM
HM
HM
HM
HM
HM
HM
HM
HM
HM
HM
HM
HM
HM
HM
HM
CLR
CLR
PT
PT
PT
PT
CLR
PT
PT
PT
PT
PT
PT
PT
PT
PT
PT
PT
PT
PT
PT
PT
PT
PT
PT
PT
PT
PT
PT
PT
PT
PT
PT
PT
20MIN
20MIN
20MIN
1HR
1HR
20MIN
20MIN
-
02
19
20HD
18EX
18
18EX
01
30
24*
30
33
35
24*
41
24
1. COORDINATE FRAME SIZES WITH WALL
THICKNESS AT NEW AND EXISTING
CONDITIONS
COMMENTS
2. WINDOW SIZES SHOWN ARE GLASS
OPENING DIMENSIONS
AUTO SLIDING ALUM. STOREFRONT
NARROW STILE ALUM. STOREFRONT
ABBREVIATIONS
AUTO SLIDING ALUM. STOREFRONT
AL
ALUMINUM
Rated-incl. closer
(E)
EXISTING, BY OTHERS
FF
FACTORY FINISH
GL
GLASS
HM
HOLLOW METAL
MFR
MANUFACTURER
MTL
METAL
OVHD
OVERHEAD
PFM
PREFINISHED METAL FRAME
PT
PAINT
SC
SOLID CORE
SGF
SOLID GROUT FRAME
SMOKE
S LABEL (SMOKE LABEL)
WD
WOOD
20 MIN.
20 MIN. UL RATED DOOR ASSEMBLY
45 MIN.
45 MIN. UL RATED DOOR ASSEMBLY
60 MIN.
60 MIN. UL RATED DOOR ASSEMBLY
*
INDICATES POTENTIAL HARDWARE
REQUIREMENT DIFFERENCE FROM
SPEC
RATED-INCL. CLOSER
SLIDING GATE, SEE DETAIL
21
32
22*
37
33
37
29
24
29
22
22
36
24
24
25
22
24
25
RATED-INCL. CLOSER
1 1/2" = 1'-0"
FACE OF RATED
WALL - MUST
EXTEND TO METAL
DECK
FIRE SEALANT
1
7
14
17
24
25
1
3
4
5
6
7
8
9
10
11
12
14
16
17
18
19
20
21
22
23
24
24
27
28
29
30
31
32
GENERAL NOTES
Portland, OR 97209
Fax: 503/224-7116
2 1/2"
1"
SIM.
333 NW 5th Ave.
Phone: 503/224-4848
6
A2.7
5/8" TYPE X GWB
EXISTING METAL
DECK (ROOF
STRUCTURE)
METAL FRAMING
5/8" GWB
ACOUSTIC INSULATION. ALL
WALLS UNO
R14
X = 4 7/8"
R16
X = 7 1/4"
2
PARTITION CONSTRUCTION SEE PARTITION TYPE
GA FILE NO. WP 1072
STC = 45-49
(W/ INSULATION)
TYPE E
1/4" = 1'-0"
PLAN
BASE AS SCHEDULED
R1
1 HOUR RATED FIRE BARRIER / SMOKE BARRIER
1 1/2" = 1'-0"
S02
X = 3 3/4"
S04
X = 4 7/8"
S06
X = 7 1/4"
1/4" LOW-VELOCITY SHOT-IN
PINS @ 16"O.C.
ALTERNATING SIDES CONTRACTOR OPTION TO
PROVIDE 1/4" EXPANSION
BOLTS @ 16"O.C. (2" EMBED)
IN LIEU OF SHOT-IN PINS
NON-RATED SMOKE PARTITION
S0
WHERE PARTITIONS ARE U.L. LISTED
ASSEMBLIES FOR PROPRIETARY
MANUFACTURERS, PROVIDE U.L.
LISTED ASSEMBLIES FOR ANY
ALTERNATE PRODUCTS INSTALLED.
1=
2.
ACOUSTIC INSULATION IN ALL
PARTITION WALLS UNLESS NOTED
OTHERWISE
F7
FURRING WALL
1 1/2" = 1'-0"
1'-4"
3'-6"
4'-6"
1'-6"
A = ACOUSTIC WALL (STC RATING)
F = FURRING WALL
H = SHAFT WALL, RATED (I.B.C. NUMBER)
P = PARTITION, NON-RATED
R = RATED FIRE BARRIER (I.B.C. NUMBER)
S = SMOKE PARTITION (I.B.C. NUMBER)
ASSEMBLY
X = 4 1/4"
F76
X = 6 5/8"
5
6'-6"
AG-3 MOUNTING HEIGHTS ELEVATION
1/4" = 1'-0"
SCALE: 1/4" = 1'-0"
MOUNTING HEIGHTS ELEVATION
4
AG-2 MOUNTING HEIGHTS ELEVATION
1/4" = 1'-0"
6'-5"
4'-0"
3'-4"
TOILET
TISSUE
DISPENSER
3'-4" MAX.
2'-0"
2'-10"
4'-0"
6"
4'-6"
7'-0"
7'-4"
5'-8"
MOUNTING HEIGHTS ELEVATION
LIGHT
PAPER TOWEL DISP.
SWITCH
MIRROR
NURSE CALL
GRAB BARS
9"
F74
DUPLEX OUTLET
MOP RACK
OVER MOP SINK
HC
WATER
FOUNTAIN
3'-0" MAX
METAL FRAMING
0=
3'-6"
4'-0"
5/8" GWB
PLAN
FIRE
HORN
STUD SIZE
GROUP
WALL
SCONCE
COAT
HOOK
7'-7"
X
TIME
CLOCK
EMERGENCY
LI G HTI NG
BATTERY PACK
2'-3" MIN.
DOME
LI GHT
NURSE CALL
A
P11
P
T
MODIFIER(S)
DIRECT TOUCH EDUCATION NETWORK
JACK IN CONFERENCE ROOM IF NO
CONFERENCE ROOM, INSTALL IN
LOUNGE
SECTION
X = 3 1/8"
HEATING
PAD
DUPLEX
TELEPHONE JACK OUTLET
DUPLEX OUTLET
DUPLEX OUTLET
3'-8"
2'-5"
4'-4"
T H E R M O S T AT
PAPER
TOWEL
DISPENSER
4'-8"
RECEPTION/
DOOR &
INTERCOM
CONTROLS
PULL
WALL TAG
JACK FOR
WALL
MICROWAVE DUPLEX OUTLET
MOUNTED
TELEPHONE
4'-0"
FIRE ALARM
PULL
STATION
2'-10"
FI RE
E XTI N G U I S H E R
CAB I N E T
1'-3"
RAIL
CHAIR
3'-4"
4'-4"
BASE- SEE FINISH SCHEDULE
F72
WALL TYPE LEGEND
3" = 1'-0"
C
AUTOMATIC
DOOR
OPENER
(POWER
ASSIST)
3
1.
GROUP
ASSEMBLY
PATIENT/
SERVICE
ENTRANCE
INTERCOM
CEILING - SEE ROOM FINISH
SCHEDULE AND RCP FOR HEIGHT
AND FINISH
TYPICAL FULL HEIGH PARTITION HEAD / SILL DETAIL
SCALE: 1/4" = 1'-0"
1=
2=
3=
4=
5=
6=
7=
8=
NON-RATED, FRAMING FULL HEIGHT,
FINISH FULL ONE SIDE, SEALANT
1-HOUR RATED, FIRE TAPE AND CAULK
2-HOUR RATED, FIRE TAPE AND CAULK
3-HOUR RATED, FIRE TAPE AND CAULK
45 STC RATING, INSULATION AND SEALANT
56 STC RATING, RESILIENT CHANNELS,
INSULATION AND SEALANT
63 STC RATING, RESILIENT CHANNELS,
INSULATION AND SEALANT
FRAMING 6" ABOVE CEILING, FINISH 6"
ABOVE CEILING
FRAMING FULL HEIGHT, FINISH 6"
ABOVE CEILING
FINISH FLOOR
FINISH
FLOOR
STUD SIZE
1 1/2" = 1'-0"
5/8" GWB
2'-10"
6"
METAL FRAMING
TYPE J
GENERAL NOTE
STRUCTURE
6
TYPE H
PROVIDE SAFETY GLAZING AS REQD. - OSSC 2404.4
PROVIDE RATED WINDOW ASSEMBLY AT SMOKE
BARRIER (TYPE E AND G)
EXISTING CONCRETE
FLOOR SLAB
ACOUSTIC INSULATION
TYPE G
WINDOW TYPES
X
PLAN
TYPE C
(HM-1)
FRAME TYPES
1/4" = 1'-0"
5/8" METAL FURRING CHANNELS
OVER EXISTING SUBSTRATE
2=
2 1/2" METAL STUDS AT 16"O.C.
3=
3 1/2" WOOD STUDS AT 16"O.C.
4=
3 5/8" METAL STUDS AT 16"O.C.
5=
5 1/2" WOOD STUDS AT 16"O.C.
6=
6" METAL STUDS AT 16"O.C.
7=
7 1/4" WOOD STUDS AT 16"O.C.
8=
8" METAL STUDS AT 16"O.C.
9=
DOUBLE PLUMBING WALL, DIM.
OUT-OUT, 3 5/8" STUDS AT 16"O.C.
MODIFIER
A=
C=
E=
L=
ACOUSTIC INSULATION & SEALANT
5/8" RESILIENT FURRING CHANNELS
EXISTING CONSTRUCTION
LEAD LINED GYPSUM BOARD PER
PHYSICIST REPORT
MR= MOISTURE RESISTANT GYPSUM BOARD
MP= MARINE GRADE PLYWOOD IN-PLACE OF
GYPSUM BOARD
NA= NO ACOUSTIC INSULATION
P = PLYWOOD UNDERLAYMENT, SHEAR
OR WALL REINFORCEMENT
T = TILE FINISH AREA: SUBSTITUTE
CEMENTITIOUS BACKER BOARD
SHEAR WALL
S=
Drafted By: AH
Checked By: AK
Date Drawn:
Project #:
6/9/12
11054
REVISION DESCRIPTION
X
ACOUSTICAL
INSULATION - ALL
FULL HEIGHT WALLS
4' - 4"
SEALANT
2' - 10"
SECTION
1' - 4"
4' - 0"
5/8" TYPE X GWB. SEE MODIFIERS
FOR MOISTURE RESISTANT GYP.
PARTITION
CONSTRUCTION, SEE
PARTITION TYPE
4' - 0"
3' - 2"
BASE- SEE FINISH SCHEDULE
METAL FRAMING
5' - 0"
4' - 0"
4' - 0"
ACOUSTIC BATT INSULATION
FIRE SEALANT
*PROVIDE SAFETY GLAZING AS REQD. - OSSC 2404.4
DATE
2" DEEP DEFLECTION
TRACK W/ VERTICAL
SLOTTED SCREW
HOLES ON FLANGES
REGULAR TOP TRACK
1/4" = 1'-0"
3' - 2"
SECTION
CEILING - SEE ROOM FINISH
SCHEDULE AND RCP FOR HEIGHT
AND FINISH
(STORE)
ALUMINUM
STOREFRONT
(ELEC) SLIDING
DOOR TYPES
4' - 0"
CEILING - SEE ROOM FINISH
SCHEDULE AND RCP FOR
HEIGHT AND FINISH
ACOUSTIC BATT INSULATION. ALL
WALLS UNO
BASE- SEE FINISH SCHEDULE
1
(SL) SLIDING
(FG) FULL
GLASS
3' - 2"
6"
5/8" TYPE GWB
(N) NARROW
VIEW
6' - 0"
SCRIM FULL HEIGHT
(F) FLUSH
1' - 2"
1/2"
ACOUSTICAL SEALANT
FINISH FLOOR
REV #
UL APPROVED FIRE
CAULKING (WHEN
INDICATED BY
PARTITION TYPE &
FIRE RESISTIVE
RATING)
#8 SCREWS @
16"O.C.
ALTERNATING SIDES
WHERE POSSIBLE
METAL DECK
FMC LOCATION #8442-1
(address pending)
The Dalles, OR 97058
FIRESTOP
AROUND JOISTS
FMC The Dalles
SIM
Tenant Improvements
6
A2.7
A2.7
PARTITION TYPES,
DOOR, &
WINDOW
SCHEDULE
PF-1
WC-1/WC-2
PF-1/CT-1
PF-1
PF-1/CT-1
PF-1
PF-1
PF-1
WC-1/WC-2
PF-1/CT-1
PA-1
PF-1/CT-1
PA-1
PA-1
PL-2
PL-1
PL-2
PL-1/SS-1
PL-1/SS
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
CLINIC MANAGER
SEPARATION
CLEAN UTILITY
WATER TREATMENT
WATER HEATER
TECH REPAIR
STORAGE
HALLWAY
SOILED HOLDING
MED WASTE
JANITOR
ELECTRICAL
STAFF TOILET
WIRING CLOSET
STAFF TOILET
STAFF LOUNGE
CORRIDOR
RISER ROOM
STAFF LOCKERS
HEMO NURSE
MULTI PURPOSE
HOME HEMO
CORRIDOR
DR. / EXAM
CONFERENCE
CPT-1
SV-1
SV-1
EPOXY
EPOXY
EPOXY
EPOXY
SV-1
SV-2
SV-2
SV-2
SV-1
SV-2
SV-1
SV-2
SV-1
CPT-1
EPOXY
SV-2
CPT-1
CPT-1
SV-1
SV-1
SV-1
CPT-1
RB-2
COVE
RB-2
COVE
COVE
COVE
COVE
COVE
COVE
COVE
COVE
RB-2
COVE
RB-2
COVE
RB-2
RB-2
RB-2
RB-2
RB-2
RB-2
RB-2
RB-2
RB-2
RB-1
PF-1
PF-1
PF-1
PF-1
PF-1
PF-1
PF-1
PF-1
PF-1
PF-1
PF-1
PF-1
PF-1/CT-1
PF-1
PF-1/CT-1
PF-1/CT-1
PF-1
PF-1
PF-1
PF-1
PA-2
PF-1
PF-1
PF-1
WC-1/WC-2
PF-1
PA-2
PF-1
PF-1
PF-1
PF-1
PF-1
PF-1
PF-1
PF-1
PF-1
PF-1
PF-1/CT-1
PF-1
PF-1/CT-1
PF-1/CT-1
PF-1
PF-1
PF-1
PF-1
PF-1
PF-1
PF-1
PF-1
WC-1/WC-2
PA-2
PF-1
PF-1
PF-1
PF-1
PF-1
PF-1
PF-1
PF-1
PF-1
PF-1
PF-1
PF-1/CT-1
PF-1
PF-1/CT-1
PF-1/CT-1
PF-1
PF-1
PF-1
PF-1
PF-1
PF-1
PF-1
PF-1
WC-1/WC-2
PF-1
PF-1
PA-1
PF-1
PF-1
PF-1
PF-1
PF-1
PF-1
PF-1
PF-1
PF-1
PF-1/CT-1
PF-1
PF-1/CT-1
PF-1/CT-1
PF-1
PF-1
PF-1
PA-2
PF-1
PA-1
PF-1
PA-1
WC-1/WC-2
PL-2
PL-2
PL-2
PL-2
PL-2
PL-2
PL-2
PL-2
PL-2
PL-2
PL-2
SS
SS
SS
SS
SS
SS
Sheet vinyl AND walk off mat throughout
CT under reception window. Chair rail. See elevations
Solid surface transaction top, see details
PL-3 for interior surfaces of nurse stations and chases. See details for SS
counter locations. See finish plan for border location.
PT-1 above FRP which runs to 8' aff.
See schedule for locker color
Chair rail on wall, see elevations.
Drafted By: AH
Checked By: AK
Date Drawn:
6/9/12
Project #:
11054
REVISION DESCRIPTION
PF-1
WC-1/WC-2
PF-1/CT-1
PF-1
PF-1/CT-1
PF-1
PF-1
DATE
PF-1
WC-1/WC-2
PF-1/CT-1
PF-1
PF-1/CT-1
PF-1
PF-1
REV #
RB-2
RB-1
COVE
RB-2
COVE
RB-2
COVE
Portland, OR 97209
Fax: 503/224-7116
CPT-2
SV-1
SV-2
SV-1
SV-2
SV-1
SV-1
333 NW 5th Ave.
Phone: 503/224-4848
VESTIBULE
WAITNG
VISITOR TOILET
RECEPTION
PATIENT TOILET
MED RECORDS
TREATMENT
FMC LOCATION #8442-1
(address pending)
The Dalles, OR 97058
1
2
3
4
5
6
7
COMMENTS
FMC The Dalles
FLOOR
FLOOR BASE NORTH
Tenant Improvements
ROOM
NO.
ROOM NAME
ROOM FINISH SCHEDULE
WALL
CABINETRY
EAST
SOUTH
WEST LOWER UPPER COUNTERS
A2.8
ROOM FINISH
SCHEDULE
AA-1
A6.7
H
G
7
.
Portland, OR 97209
Fax: 503/224-7116
.
MOSAIC TILE
2
3/8" = 1'-0"
Waiting-North
3
3/8" = 1'-0"
Waiting-East
4
3/8" = 1'-0"
Waiting-South
3/8" = 1'-0"
333 NW 5th Ave.
Phone: 503/224-4848
Waiting-West
1
GYP. SOFFIT
GYP. SOFFIT
E
G
H
FILE-L
4' - 4"
6
COP
COP
MOUNT SCALE READOUT ON WINDOW ROUTE CONDUIT THROUGH WALL
5
Reception-West
6
3/8" = 1'-0"
Reception-East
3/8" = 1'-0"
7
LabPrep
8
3/8" = 1'-0"
Treatment-South
3/8" = 1'-0"
AT-46
A6.7
3. SEE DETAIL SHEETS FOR TYPICAL
CABINETRY CONSTRUCTION DETAILS
4. COORDINATE MOUNTING HEIGHTS FOR ALL
SIGNAGE, EQUIPMENT AND FIXTURES WITH
STANDARD MOUNTING HEIGHT DRAWING.
Treatment-West
9
10
3/8" = 1'-0"
5. PRIOR TO COVERING WALL, BACKING SHALL
BE PROVIDED TO ACCOMODATE ALL HUNG
ITEMS AND ACCESSORIES CALLED FOR ON
THE CONSTRUCTION DOCUMENTS. SUCH
ITEMS CONSIST OF, BUT ARE NOT LIMITED TO:
UPPERCASE CABINETS,
STORAGE
SHELVING, TELEVISIONS, COMPUTER
MONITORS, LAVATORY ACCESSORIES, AND
FUTURE INSTALLATION OF GRAB BARS AT
THE SIDES OF WATER CLOSETS.
NurseStation-West
3/8" = 1'-0"
C
C
FMC LOCATION #8442-1
(address pending)
The Dalles, OR 97058
2. GROMMETS AND ELECTRICAL OUTLETS:
INSTALL GROMMETS IN COUNTERTOPS FOR
ALL UNDER-COUNTER OUTLETS AS
FOLLOWS:
1 1/2" DIA. GROMMET FOR UP TO 2
OUTLETS
2 1/2" DIA. GROMMET FOR UP TO 4
OUTLETS
Tenant Improvements
1. CABINETMAKER SHALL COORDINATE WITH
OTHER TRADES, VENDORS AND
OWNER FOR ITEMS INSTALLED IN AND
AROUND CABINETRY
FMC The Dalles
GENERAL NOTES
C
J
Drafted By: AH
Checked By: AK
NARROW STILE
ALUM. STOREFRONT
Date Drawn:
Treatment-North
12
3/8" = 1'-0"
NurseStation-North
3/8" = 1'-0"
13
Separation-OutAngle
3/8" = 1'-0"
14
Separation-OutNorth
3/8" = 1'-0"
Project #:
11054
REV #
DATE
REVISION DESCRIPTION
11
6/9/12
AT-46
A6.7
15
NurseStation-East
3/8" = 1'-0"
16
Treatment-East
3/8" = 1'-0"
2'-0" WIDE 'SHROUD PANELS' AS SHOWN IN DETAILS ONLY OCCUR AT INDIRECT DRAINS AND RO PIPING
RISERS. OTHERWISE, CABINETS HANG FROM WALLS
AND ARE OPEN BELOW
A6.0
INTERIOR
ELEVATIONS
KEYNOTES
A7
SHALLOW DRAWERS TO ALLOW FOR R.O. LOOP
AT-51
Portland, OR 97209
Fax: 503/224-7116
A6.6
NurseStation-South
NurseStation-InS_W
2
3/8" = 1'-0"
A6.6
A6.6
MedPrep-South
4
3/8" = 1'-0"
NurseStation-InS_E
3/8" = 1'-0"
333 NW 5th Ave.
Phone: 503/224-4848
3/8" = 1'-0"
3
AT-51
AT-51
A6.6
6
3/8" = 1'-0"
NurseStation-InN_W
7
3/8" = 1'-0"
NurseStation-InN_N
8
3/8" = 1'-0"
NurseStation-InN_E
9
3/8" = 1'-0"
MedPrep-North
3/8" = 1'-0"
GYP. SOFFIT
AT-14
A6.8
9
C
J
C
A7
10
Separation-West
11
3/8" = 1'-0"
9
J
AT-14B
A6.8
Separation-North
Separation-East
12
3/8" = 1'-0"
AT-6
AT-4
A6.5
A6.5
13
3/8" = 1'-0"
AT-6
AT-4
A6.5
A6.5
Separation-South
14
3/8" = 1'-0"
AT-6
AT-4
A6.5
A6.5
Solied-West
15
3/8" = 1'-0"
FMC LOCATION #8442-1
(address pending)
The Dalles, OR 97058
NurseStation-InS_S
FMC The Dalles
5
Tenant Improvements
Soiled-South
3/8" = 1'-0"
SIM.
GYP.
SOFFIT
GYP. SOFFIT
GYP. SOFFIT
I8
I8
AT-51
DENS
ARMOR TO
48" AFF
E
COF
A6.6
MIC
23
REF-F
P-5
Drafted By: AH
Checked By: AK
SIM-NO BASE
CABINET
17
StaffLounge-North
DrExam
3/8" = 1'-0"
19
Conference-North
3/8" = 1'-0"
20
Lockers-West
3/8" = 1'-0"
21
Lockers-North
Project #:
11054
3/8" = 1'-0"
3/8" = 1'-0"
REVISION DESCRIPTION
3/8" = 1'-0"
18
6/9/12
DATE
16
StaffLounge-East
Date Drawn:
REV #
1
AT-50
A6.1
INTERIOR
ELEVATIONS
PLAS. LAM. END PANEL TO
MATCH CABINETS
ROCKER SWITCH IS IN "SECURE" POSITION. ELECTRIC LOCKSET IS
SECURE. WAITING ROOM DOOR OPENER BUTTON IS DEAD.
TREATMENT ROOM DOOR OPENER BUTTON, DOOR RELEASE AT
NURSES STATION, AND DOOR RELEASE AT RECEPTION WILL
UNLOCK THE ELECTRIC STRIKE AND ACTIVATE THE DOOR
OPERATOR.
REMOVABLE ADA
COMPLIANT
PLAS.LAMINATE
PANEL TO MATCH
CABINET.
4" RUBBER BASE SET IN
SILICONE SEALANT (TYP)
8"
9"
A.D.A. CLEARANCES
1. POWER REMOVED FROM LOCKSET 2. DOOR MANUALLY
OPERABLE FROM BOTH SIDES 3. ELECTRIC STRIKE IN FAIL SECURE
POSITION.
FINISHED FLOOR
48"
Portland, OR 97209
Fax: 503/224-7116
12"
24"
2'-0"
1/2" TH I CK SOLI D SU RFACE
SI DE SPLASH PANE L BE TWE E N
U PP E R AND LO WE R C AB I N E T
STAINLESS STEEL
UNDER MOUNT SINK
1/2" SOLID SURFACE
COUNTERTOP W/ NO-DRIP
EDGE
MANEUVERING CLEARANCES AT SWINGING DOORS
SIDE SPLASH TO
EXTEND TO EDGE OF
'NO-DRIP' EDGE
D-1
'NO-DRIP' EDGE
REMOVABLE
PLAS.LAMINATE
PANEL TO MATCH
CABINET.
4"
RUBBER BASE SET IN
SI LICONE SEALANT (TYP)
LAV O.K.
FI NI SHED FLOOR
LAV O.K.
36"
36"
18" 18"
18" 18"
LAV O.K.
18"
42"
6"
TREATMENT DOOR SCHEMATIC
TYP. SINK BASE
TYPICAL ADA SINK SECTION
AP-3
AT-4
1/4" = 1'-0"
INSTALL SINK PER
MANUFACTURER'S
INSTRUCTIONS
AT-1
3/4" = 1'-0"
3/4" = 1'-0"
4' - 8"
FIRE CONDITION:
(OR POWER LOSS)
4'-0" A.F.F.
C. L. OF UNDER CAB.
LIGHT SWITCH COOR.
LOCATION OF
D-1
SWITCH/REC WITH
SIDESPLASH
1/2" THICK SOLID SURFACE
PANEL BE TWE E N U PPE R AND
LOWER CABINET
(U S E 1/4 " WHERE AVAI LABLE)
4' - 8"
SECURE
MODE:
PLAS. LAM. SKIRT BD. TO
MATCH CABINETS.
60"
333 NW 5th Ave.
Phone: 503/224-4848
ROCKER SWITCH IS IN "UNSECURE" POSITION. INTERIOR AND
EXTERIOR DOOR OPENER BUTTONS WILL ACTIVATE DOOR. AS WELL
AS DOOR RELEASE AT NURSES STATION AND DOOR RELEASE AT
RECEPTION. PUSH-N-GO WILL ACTIVATE DOOR FROM BOTH SIDES.
UNSECURE
MODE:
INSTALL SURFACE
MOUNTED
TRANSFORMER,
SENSOR CONTROLS
AND
MIXING VALVES AT 1'-6"
A.F.F. RECESSED
RECEP. 1'-6" A.F.F.
OFFSET PIPING AS
REQ'D. TO FIT
BEHIND
REMOVABLE PANEL.
SOLID SURFACE
COUNTERTOP W/ NO-DRIP
EDGE
5"
THEORY OF OPERATION:
SENSOR CONTROL
FAUCET
1/ "
2
NOTE: SEE ELECTRICAL DETAIL EP-3 FOR
TREATMENT ROOM DOOR WIRING DIAGRAM
56"
UNDER CABINET LIGHT
LI G H T B AFFLE
2'-4"
DOOR RELEASE (NURSE'S STATION)
FURNISHED BY ELECT. CONTRACTOR
SEE PM FOR EXACT LOCATION
PAPER TOWEL
DISPENSER AT
3'-8" A.F.F.
48"
BLOCKING AS REQ'D
FOR WALL CABINETS
48"
LIGHT BAFFLE
ROCKER SWITCH
LOCATED ON
AUTOMATIC
OPENER HOUSING
(UNLESS PM DESIGNATES
ALT. LOCATION)
DOOR RELEASE (RECEPTION AREA)
FURNISHED BY ELECT. CONTRACTOR
SEE PM FOR EXACT LOCATION
TREATMENT
ROOM
1/2" THICK SOLID
SURFACE PANEL
BETWEEN UPPER AND
LOWER CABINET
(USE 1/4 " WHERE
AVAILABLE)
PRE-FAB CABINET W/
WIRE PULLS
48"
UNSECURE
2'-0"
PRE-FAB CABINET W/
WIRE PULLS
24"
AD J U S T AB L E S H E L F
5' - 6"
ELECTRIC
LOCK SET
DOOR
OPENER
UNDER CABINET LIGHT
2'-2"
SECURE
2'-5"
J
36"
18"
BLOCKING AS REQ'D
2'-10"
TREATMENT
ROOM
DOOR
ADJUSTABLE SHELF
48"
24 V, A/C
"FAIL SECURE"
ELEC
STRIKE
DOOR
OPENER
60"
WAITING ROOM
THIS IS A GENERIC DETAIL.
ARCHI TECT SHALL SHOW
CONDI TI ONS BE YOND SUCH AS
BASE CABINETRY OR END WALLS
AS THEY APPLY TO EACH
INSTALLATION.
3'-0"
INTERCOM
GYP BOARD SOFFIT
ABOVE WALL
60"
THIS IS A GENERIC
DETAIL. ARCHITECT
SHALL SHOW
CONDITIONS BEYOND
SUCH AS BASE
CABINETRY OR END
WALLS AS THEY APPLY
TO EACH INSTALLATION.
GYP BOARD SOFFIT ABOVE
WALL CABINETS
1'-0"
WIDTH AS NOTED ON PLAN
EASE ALL E XPOSE D E DG E S
SIDE SPLASH
SHALL EXTEND TO
EDGE OF 'NO-DRIP'
EDGE
D-1
D-1
AP-6
NOTE: SOLID SURFACE DIVIDER
TO MATCH COUNTERTOP
DRAWER
1'
DRAWER
2'-10"
1-1/4" DIA. 14 GA.
CHROME DOWEL
30"
FORWARD APPROACH
IN ALCOVE
DRAWE R
PARALLEL APPROACH
IN ALCOVE
30" 6"
TYP. HANDICAP BASE CABINET
AT-6
AT-2
3/4" = 1'-0"
17" MIN.
UN C AS E D OP E N I N G
B E Y ON D ,
RUN QUARRY TI LE BASE
TO OUTE R E D GE OF
OP E N I N G
RUBBER BASE SET IN
CONTINUOUS BEAD
OF SILICONE
SEALED CONCRETE
FLOOR OR EPOXY
SHOP FLOOR
SUSPENDED ACT
CEILING
QUARRY TI LE
F L OO R
Head-Transom
10' - 0"
GYP. SOFFIT
4"
HOLD GYP. BD. 1/4" ABOVE
SUB-FLOOR W/ CONT.
J-CHANNEL. PROVIDE
BACKER-ROD & SEALANT
1x 4 M AHOGANY
THRE SHOLD, CHAM FE R @
45 DEG., M E CHANI CALLY
FASTEN TO SLAB,
ALI GN W/ OUTER EDGE
OF OPE NI NG
MECH/STOR. ROOM
WATER TREATMENT
4" TRENCH DRAIN, SET
FLUSH WITH SLAB AND
EXTEND 15" BEYOND
EACH SI DE OF UNCASED
OPENI NG
FINISH WINDOW
POCKET - TYPICAL
AT ALL WINDOWS
WATER TREAT WALL BASE DETAIL
AS-4
PRE-FAB CABINET W/
WHITE VINYL COATED
WIRE PULLS
UNDER CABINET
TASK LIGHT
1/2" SOLID SURFACE
COUNTERTOP W/ NO-DRIP
EDGE
GYP. OR HIGH DENSITY
FIBERBOARD PAINTED TO
MATCH SOFFIT FOR FINISHED
APPEARANCE FROM INTERIOR
OR EXTERIOR
1/2" THICK SOLID SURFACE
PANEL BETWEEN UPPER AND
LOWER CABINET
(USE 1/4" WHERE AVAILABLE)
D-1
3/4" = 1'-0"
CONCEALED "KEKU"
CLIPS
CORNER
GUARDS
BLOCKING AS
REQ'D
19"
MAX.
48"
CONTROLS
3' - 0"
MIN.
ADJUSTABLE SHELF
LIGHT BAFFLE
Head-Vision
8' - 0"
2' - 6"
* SIM. REFERS TO ROOMS
WHERE ACT CEILING
INTERSECTS WINDOWS AT 9' USE HDF AS VERTICAL CLOSURE
30"
GYP BOARD SOFFIT ABOVE
WALL CABINETS
EQ EQ
3' - 0"
MIN.
CONTINUOUS ICE &
WATER SHIELD.
7"
1 1/2" = 1'-0"
6"
1/8" THICK RESINOUS FLOORING
OVER MOISTURE MITIGATION
SYSTEM OVER PREPARED
CONCRETE SLAB (APPLY W/
INTEGRAL COVE BASE AS
SHOWN)
(EPOXY PAINTED CONCRETE
MAY ALSO BE USED. WHEN
USED, BRING PLYWOOD AND FRP
DOWN TO FLOOR, SEAL ALL
EDGES, AND INSTALL RUBBER
BASE)
AP-6A
PARALLEL APPROACH
IN ALCOVE
3/4" = 1'-0"
5/8" GYP BD. O/
3-5/8" STUDS @ 16"
O.C.
COAT RACK AND SHELF - SECTION
FORWARD APPROACH
IN ALCOVE
TYP. DRAWER BASE CABINET
12"
> 15"
2'-1"
30"
2'-1"
3-1/2" SOUND
ATTENUATION BLANKETS
TO DECK.
DENS ARMOR
PLUS FIRE WLDB.
48"
FI NI SHED FLOOR
2'-0"
1" RADIUS ON BOTTOM
EDGE OF FACE
FIN. FL.
CLASS "A" RATED FRP O/
GYP. BD. BEHIND
SDS/GRANUFLO AREA AND
THE EMERGENCY SHOWER
CLASS "A" RATED FRP
(ALL WALLS) MAINTAIN 1/4" GAP
AT BOTTOM OF PANEL, SET IN
CONTINOUS BEAD OF
SILICONE SEALANT
48" AFF ('X' LENGTH)
6"
DRAWE R
> 24"
FINISHED FLOOR
3/4" = 1'-0"
FACE OF WALL. FINISH
AS SCHEDULED
4'-0" MIN.
DRAWE R
48"
AT-11
PAINTED 3/4" CLEATS @
ENDS AND BETWEEN
RACKS
BEVEL LAST 4"
ADJACE NT
TO TRENCH DRAI N TO
A DEPTH OF 3/8" TO
ALLOW FOR
CONTI NOUS SLOPE TO
DRAI N
1x 4 MAHOGANY
TRANSITION STRIP,
CHAMFER OUT SIDE
EDGE @
45 DEG., MECHANICALLY
FASTEN TO SLAB,
ALIGN W/ OUTER EDGE
OF OPENING
48"
SIDE SPLASH
SHALL EXTEND TO
EDGE OF 'NO-DRIP'
EDGE
'NO-DRIP' EDGE
D-1
PARALLEL APPROACH
30"
SOLID SURFACE SINK DIVIDER
PAINTED 3/4" CLEAT AT BACK.
SCREW CLEAT ENDS AND
BACK INTO SOLID BLOCKING
BEHIND WALL.
4"
DRAWE R
DRAWER
62" AFF ('4X' LENGTH)
QUARRY TI LE
BASE BE YOND
DRAWER
THIS IS A GENERIC DETAIL.
ARCHI TECT SHALL SHOW
CONDITI ONS BEYOND SUCH
AS BASE CABINETRY OR END
WALLS AS THEY APPLY TO
EACH INSTALLATION.
2'-2"
2 3/4 "
5 1/2"
PAINTED 3/4" SHELF
10"
'NO-DRIP' EDGE
D-1
FORWARD APPROACH
ALIGNED
EQ
EQ
4' - 0"
CLEAR FLOOR SPACE
AT LAVATORIES
CLEAR FLOOR SPACE
AT REFRIGERATOR
(SIDE APPROACH ONLY)
CLEAR FLOOR SPACE
AT SHOWER
CLEAR FLOOR SPACE
Drafted By: AH
'NO-DRIP' EDGE
BY MANUFACTURER
D-1
GYP. SILL AT ALL WINDOWS
UNLESS NOTED OTHERWISE
Checked By: AK
Date Drawn:
INSTALL (4) "KEKU"
CLIPS PER PANEL
FRONT FOR
CONCEALE D
ACCESS UNDER SI NK
(N.I.C.)
PTD
SD
PTD
2
BASE AS SCHEDULED
Window Pocket
1/2" = 1'-0"
11054
REVISION DESCRIPTION
1'-3"
CHAIR RAIL WHERE
SHOWN ON FINISH
PLAN
6/9/12
3'-0"
Project #:
BEVEL LAST 4" ADJACENT
TO TRENCH DRAI N TO A
DEPTH OF 3/8" TO ALLOW
QUARRY TILE TO SLOPE
TOWARD THE DRAI N
FMC LOCATION #8442-1
(address pending)
The Dalles, OR 97058
BASE
CABI NET
3'-0"
1/2" = 1'-0"
CLEAR FLOOR SPACE
1/2" THICK SOLID SURFACE
SI D E SP L AS H P AN E L B E TWE E N
UPPER AND LOWER CABI NET
(U S E 1/4" WHERE AVAI BLABLE)
FMC The Dalles
AP-6
1/2" THICK SOLID SURFACE
SIDESPLASH PANEL BETWEEN
UPPER AND LOWER CABINET
(USE 1/4" WHERE AVAILABLE)
Tenant Improvements
AP-6 COAT RACK AND SHELF
1/2" SOLID SURFACE
COUNTERTOP W/ NO-DRIP
EDGE
1/2" THICK SOLID SURFACE
PANEL BE TWE E N U PPE R AND
LOWER CABINET
(U S E 1/4" WHERE AVAI LABLE)
1/2" SOLID SURFACE
COUNTERTOP W/ NO-DRIP
EDGE
15"
MAX
1" SOLI D SURFACE COUNTERTOP,
RO U T 1" WIDE X 1/4" D E E P R AB B E T
TO RECEIVE DIVIDER, ADHERE W/
CONTINOUS BEAD OF SILICONE
2'-4"
6" MOLDED
VINYL BASE
48"
48"
30"
4"
1/2" THICK SOLID SURFACE
PANEL BETWEEN UPPER AND
LOWER CABINET
(USE 1/4 " WHERE AVAILABLE)
UNDER CABINET LIGHT
LI G H T B AFFLE
48"
UNDER CABINET LIGHT
5' - 0"
30"
24"
MAX
1"
LOCKABLE PRE-FAB
CABINET W/ WIRE
PULLS
BLOCKING AS
REQ'D
48"
1" THICK SOLID SURFACE
DIVIDER TO BE SCRIBED TO
BOTH THE COUNTER AND THE
WALL. SEAL WITH SILICONE ON
BOTH SIDES.
PRE-FAB CABINET W/
WIRE PULLS
4' - 0"
CLEAR FLOOR SPACE AT WATER CLOSETS
AD J U S T AB L E S H E L F
2'-0"
BLOCKING AS
REQ'D
4' - 0"
30"
2'-2"
4'-0"
2'-10"
SOLI D
SU RFACE
DI VI DER
WC-2
ADJUSTABLE SHELF
GYP BOARD SOFFIT ABOVE
WALL CABINETS
2'-2"
CREATE 1" WI DE CHANNEL
USI NG SOLI D SURFACE
CLEATS SET I N CONTINUOUS
BEAD OF SI LICONE AND
SCREWE D TO BOTTOM OF
WALL CABI NET
THIS IS A GENERIC
DETAIL. ARCHITECT
SHALL SHOW
CONDITIONS BEYOND
SUCH AS BASE
CABINETRY OR END
WALLS AS THEY APPLY
TO EACH INSTALLATION.
2'-0"
CL
X
COAT RACK,
SHELF, AND
CHROME ROD
5'-2"
4X
WALL
CABI NET
2'-0"
CL
GYP BOARD SOFFIT ABOVE
WALL CABINETS
3'-0"
WALL COVERING 2
ABOVE COAT RACK
FINISHED FLOOR
VALVE BOX DRAIN, AIR GAP
FITTING, AND P-TRAP
WATER TREATMENT DRAIN
GYPSUM BOARD
TEXTURED HIGH
IMPACT SNAP-ON
COVER
CONTINUOUS
SHOCK CUSHION
2" TYPICAL
RUN WALL
CARPET/COVERING
BEHIND CORNER
GUARD WHERE
OCCURS
CONTINUOUS
RETAINER
P-3
P-15
6" MIN. SPACER BETWEEN
ELBOWS, SEE DETAIL AT-35
AT-3
RO/SDS SUPPLY AND
RETURN SLEEVES (2), BASE OF
CABINETS AND BOTTOM
DRAWER WILL HAVE TO BE
MODIFIED ON SITE
DATE
NOTE:
THIS DETAIL SHALL BE
USED IN I NSTANCES
WHERE A SLOPED
UNDER SINK PANEL
WI LL NOT WORK DUE
NOTE: SET
TO UNDER SINK
BOTTOM OF
ACCESSORI ES OR
CORNER
EQUIPMENT, SUCH AS
GUARD
WALL STUDS
WHEN A VALVE PANEL
DIRECTLY AT
TOP OF RUBBER IS SIDE MOUNTED ON
BASE- TYPICAL, THE CABINET
ADJACENT TO THE SINK.
SCREWS @ 18" TOP OF
STAGGERED
CORNER
VERTICALLY
GUARD SHALL
TERMINATE @
40" A.F.F. OR @
BOTTOM EDGE
OF CHAIR RAIL
3/4" = 1'-0"
BASE CABINET W/ FIXED PANEL-- SECTION
REV #
AS-6
SCALE: 3/4" = 1'-0"
A6.5
2" TYPICAL
INTERIOR DETAILS
CORNER GUARD
AG-4
CONCEALED CLIPS
AG-7
6" = 1'-0"
3/4" = 1'-0"
TOILET PAPER
DISPENSER
VITREOUS
CHINA
KNEE SHROUD
1'-6"
1'-6"
CLEAR
CLEAR
PATIENT TOILET ELEVATION - DRY WALL
1
1_ "
8
3"
INDIRECT
WASTE
LINE W/
FUNNEL
DRAIN
DIALYSIS CHASE
CABINETS PROVIDED
BY MILLWORK VENDOR,
INSTALLED BY GC
1/16" JOINTS (TYP.)
FINISH FLOOR
2'-0"
2'-0"
CL
PATIENT TOILET ELEVATION - DRY WALL
RO/SDS SLEEVE
DIALYSIS - RECEPTACLE CUT OUTS
2'-0"
2'-0"
SHEET VINYL
FLOORS WITH
FLASH COVE
TYPICAL ELECTRICAL
RECEPTACLES
HINGED ACCESS PANELS
BY MILLWORK VENDOR
DIALYSIS COUNTER ELEVATION
AT-26
3/8" = 1'-0"
1'-0"
2'-0" WIDE SHROUD PANELS
TO
COVER FLOOR DRAIN &
TEFLON SLEEVE
1'-0"
AP-9
3/8" = 1'-0"
HINGED PANELS BY
MILLWORK VENDOR,
INSTALLED BY GC
CUT-OUT FOR
SINGLE-GANG
RECEPTACLE
BOX
-TYPICAL
TANK LEVER SHALL BE LOCATED ON
SIDE OPPOSITE WALL/GRAB RAIL.
PROVIDE APPROPRIATE TOILET TANK
TYP.
CONTINUOUS BEAD OF CLEAR
SILICONE
CAULK AROUND PERIMETER OF BOWL
AP-10
3"
CL
Portland, OR 97209
Fax: 503/224-7116
CUT-OUT FOR
SINGLE-GANG
DATA BOX -TYPICAL,
SEE DETAIL FOR
RECEPTACLE
SPECIFICATION
333 NW 5th Ave.
Phone: 503/224-4848
3'-0"
6"
AT-26
A6.6
2'-3 5/8 "
42" LONG, 1- 1/2"
DIA. GRAB BAR W/
SAFETY GRIP
(PROVIDE WOOD
BLOCKING)
2'-0"
2'-10"
4'-0"
CERAMIC OR
PORCELAIN TILE
4'-2"
5'-0"
6'-6"
8'-0"
LIGHT SWITCH
AT 4'-0" O.C.
1'-0"
24X36
MIRRORCENTER
OVER
SINK
7"
SCHLUTER
"JOLLY" TRIM CAP
NURSE CALL W/
CHAIN AT 4'-0"
A.F.F.
42" LONG, 1 1/2" DIA. GRAB
BAR W/ SAFETY GRIP
(PROVIDE WOOD
BLOCKING)
3
2'-11 _ "
4
3' - 3"
(TYPICAL PATIENT STATION)
2'-4"
6"
PAPER TOWEL
DISPENSER
SIDE
MOUNTED
8'-0"
1'-6"
3'-6"
POWER & DATA FOR
PATIENT STATION
NETWORK - SEE
COUNTER PANEL DETAIL
4'-0" HIGH, 5/8" DENS
ARMOR PLUS
FIREGUARD
WALLBOARD BEHIND
ALL DIALYSIS COUNTERS.
FASTEN (OWNER
FURN.) VALVE BOX TO
FRAMING W/ STAINLESS
STEEL SCREWS IN
PRE-DRILLED 3/16"∅
HOLES TOP AND
BOTTOM. (TYP. 4 PL).
1 x 2 LAMINATED
FINISH TRIM BY
MILLWORK VENDOR
A6.6
2'-10"
NOTE: DENS ARMOR
PLUS FIRE WLBD.
THROUGHOUT (TYP)
4'-6"
AT-25
WALL MTD LIGHT
TOILET TISSUE DISPEN.
NURSE CALL WITH
EMERG. PULL CORD
2'-0"
BEDPAN WASHER
WHEN APPLICABLE.
(IN LIEU OF SOILED
UTILITY ROOM.)
2'-10"
18" LONG VERT. GRAB BAR
- PROVIDE BLOCKING AS
REQD.
NOTE: DENS ARMOR
PLUS FIRE WLBD.
THROUGHOUT (TYPICAL
ALL WALLS)
36" LONG, 1 1/2" DIA. GRAB
BAR W/ SAFETY GRIP
(PROVIDE WOOD
BLOCKING)
WALL MTD. LIGHT,
SEE ELEC. FIXTURE
SCHEDULE
FULL HEIGHT CERAMIC TILE ON WET WALL
3'-8" MAX.
WALL MTD LIGHT,
SEE ELEC. FIXTURE
SCHEDULE
AT-21
3/4" = 1'-0"
1/2" = 1'-0"
PATIENT TOILET ELEVATION
6'-6"
2'-10 1/2"
PLATE - 12x5x3/8"
CONT. BEAD OF CLEAR SI LI CONE
SEALANT AROUND PERI METER OF
BOWL
FLOOR/WALL
MOUNTED
POST
GYP. BD. TO 8" ABOVE
CLG.
LINE OF
8'-0"
CEILING
U TI LI TY CH ASE
WAL L
GATE HOOK
HOOK
RECEIVER
WALL HUNG
DIALYSIS
COUNTER
1 1/2"
VALVE
PANEL
(TYP.)
AT-24
2 x 6 CONT. WOOD BLOCKING
FLOOR DRAIN
7"
GATE: ITEM # FRES S4
POSTS: ITEM # FRES P8
FLOOR
MOUNTING
ANGLE
2'-0"
2'-0" 1'-0" 2'-0"
2'-0"
2'-0"
1'-0" 2'-0"
2'-0"
2'-0"
2'-0" 1'-0" 2'-0"
2'-0"
2'-0" 1'-0" 2'-0"
2'-0"
AT-24
1" = 1'-0"
= 1'-0"
PROVIDE 1" WIDE
FILLER STRIP ON
TOP
AND FRONT, BOTH
LOCKERS
9"W x
SIDES
12"D
x 60"H
1'-4"
TYP.
5'-0"
5/8"x 10"
PLYWOOD
STRIPS, FASTENED
TO STUDS (2 PLC.)
5/8" DRYWALL
OVER 3-5/8"
METAL STUDS.
PTD
SINK
"P-11"
9" TO C.L. OF
PLY.
BLOCKING
A.F.F.
4" ZEE MOUNT
BY MANUF.
SINK
"P-10"
2 BULB EGRESS
LIGHT @ 7'-4" A.F.F.
LINE OF DENS
ARMOR PLUS
FIRE WLBD.
BEHIND
COUNTER TO
48" A.F.F.
GFCI RECPT.
48" A.F.F.
SD
VISUAL FIRE ALARM
STROBE @ 7'-0" A.F.F.
PREFAB
LAMINATE
CABINETS W/
(NON
PLASTIC)
WIRE PULLS
PREFAB
LAMINATE
CABINETS W/
(NON
PLASTIC)
WIRE PULLS
1" FILLER @ WALL
(WHERE OCCURS)
PLY. BLOCKING A.F.F.
12"
6"
DIALYSIS COUNTER AT WALL
WATER TREATMENT ROOM SLIDING GATE DETAILS
1/ "
2
LINE OF DENS
ARMOR PLUS
FIRE WLBD.
BEHIND
COUNTER TO
48" A.F.F.
DRAWER
DRAWER
DRAWER
1'-4"
1'-0"
PROVIDE "WATER
ONLY" RECESSED
VALVE BOX AND
DRAIN ASSEMBLY
(CONNECT TO
CITY WATER).
30" SINK BASE
CABINET
4" RUBBER BASE
INDIVIDUAL
PATIENT
MACHINE
(N.I.C.)
3/8" = 1'-0"
NOTE: ALL DIMENSIONS TAKEN FROM FACE OF
STUD
STAFF LOCKER
SCALE:
3/8" = 1'-0"
DETAILS
DIALYSIS COUNTER END WALL
STAFF LOCKER DETAILS
AA-8
3/8" = 1'-0"
V
NURSE CALL PULL
STRING @ 4'-0" A.F.F.
Project #:
6/9/12
11054
DEDICATED GFCI
RECEPT. FOR IPM
18" A.F.F.
INSTALL (4) "KEKU"
CLIPS PER PANEL
FRONT
DRAWER
W
B
4" RUBBER BASE
HOME TRAINING CABINET ELEVATION
AA-5a
TYP. PLAN
Date Drawn:
HOME TRAINING CABINET ELEVATION
AA-5A HOME TRAINING CABINET ELEVATION
ADJACENT COUNTER EXI STS
1" = 1'-0"
18" DRWR BASE
CABINET
SINK
"P-10"
R.O.
EQUIP.
(N.I.C.)
SCALE: 3/8" = 1'-0"
EXTEND TO 2'-5" WHERE
AT-27
ALSO REFER TO DETAIL AA-5
FOR THE REMAINDER OF THE HH
TRAINING ROOM ELEVATIONS
STAFF
LOCKERS
Checked By: AK
SD
PTD
INSTALL (4) "KEKU"
CLIPS PER PANEL
FRONT
TYP. SECTION
Drafted By: AH
RIGID VINYL PANEL
TO 52" A.F.F., 36" IN
EACH DIRECTION
MED WASTE
CORNER GUARDS (TYP.)
ADHERE 1/2" SOLID
SURFACE MATERI AL
DIRECTLY TO WALL
FULL LENGT H
BET WE EN WAL L
CABI NET S
AND COUNTER TOPS
1" FILLER @ WALL
(WHERE OCCURS)
GFCI RECPT.
48" A.F.F.
TYP. ELEVATION
5"
(TYP.)
11"
1/4" = 1'-0"
PLAN
4'-11" TO C.L. OF
5/8' DENS ARMOR PLUS
FIREGUARD GYP. BD. TO 48"
A.F.F. BEHIND DIALYSIS
CABINETS
CORNER GUARDS
PLACED @ BOTH ENDS
(TYP.)
DIALYSIS COUNTER ELEV AT WALL
AT-22
BOTTOM GUIDE
SCALE:
PLASTIC LAMINATE DIALYSIS
COUNTER WITH 3MM EDGE
BAND BY MILLWORK VENDOR
AND INSTALLED BY
CONTRACTOR
SHEET VINYL W/
INTEGRAL
COVE BASE
OVER
CONCRETE
SLAB ON
GRADE
REVISION DESCRIPTION
WALL
MOUNTING
ANGLE
(3 PER POST TO BE SUPPLIED BY CONTRACTOR)
AS-11
REDUCE PARTITION
HEIGHT TO 42" WHERE
NO PLUMBING OCCURS
RO/SDS SLE E VE
POWER FOR PATIENT EQUIPMENT
TYPICAL AT EACH PATIENT
STATION - SEE RECEPTACLE
CUT-OUT DETAI L FOR EXACT
LOCATI
ONS SLE E VE
RO/SDS
1
1_"
4
SLIDING DOOR
TRACK
FLOOR/WALL
MOUNTED
POST (3)
1'-0
POWER & DATA FOR TV SYSTEM
(TYPICAL) - SEE RECEPTACLE
CUT-OUT DETAIL FOR
EXACT LOCATI ONS
7"
ELEVATION
1"
TY
P
11"
32'-0"
BOTTOM GUIDE
LAMINATED 1 X 2 TRIM BOARD SET
IN CONTINUOUS BEAD OF
SEALANT
1'-0"
PLYWOOD PANEL (TYP.)
AT-25
5/8" DENS ARMOR PLUS
FIREGUARD GYP. BD. TO 48" A.F.F.
10"
SINGLE CYLINDER
LOCK WITH THUMB
LATCH ON OPPOSITE
SIDE
8'-0"
3-5/8" METAL STUD FRAMING
@ 16" O.C..
1
1_"
4
WALL
MOUNTING
ANGLE
(3 PER POST, TO BE
SUPPLIED BY
CONTRACTOR)
NOTE:
WHEN ORDERING THIS
GATE KIT, YOU MUST
ALSO ORDER THE
3 POSTS. THEY ARE
NOT INCLUDED WITH
THE GATE.
C
L
8'-0"
(TYP. PATIENT
STATI ON)
U TI LI TY CH ASE
WAL L 8'-0"
DATE
OPENING INTO
WATER TREATMENT
ROOM
SLIDING GATE
1" = 1'-0"
REV #
FLOOR/WALL
MOUNTED
POST
AT-25
FMC LOCATION #8442-1
(address pending)
The Dalles, OR 97058
DIALYSIS COUNTER SECTION
TRACK
MOUNTING
BRACKET (TYP)
3/8" = 1'-0"
FLOOR DRAIN. REFER TO
PLUMBI NG DETAI LS.
3/4" = 1'-0"
FMC The Dalles
3/8" = 1'-0"
WALL
7 1/2"
2'-5"
STAFF TOILET
AT-51
1 1/2" = 1'-0"
SLIDING DOOR TRACK
AA-10
2 x 6 CONT. WOOD BLOCKING
SHEET VINYL
W/ INTEGRAL
COVE BASE
OVER
CONCRETE
SLAB ON
GRADE
AT-51 Low Wall @ Med Prep
AT-50
STAFF TOILET ELEVATION - WET WALL
LAMINATED
PLYWOOD SHROUD
AT ALL FLOOR
DRAINS & PVC
SLEEVES AT FLOOR
Tenant Improvements
AT-29_Posts
AA-11
WATER VENDOR TO PULL
RO/SDS TUBING AND MAKE
ALL CONNECTIONS
3/8"x3" CONC. ANCHORS
TANK LEVER SHALL BE
LOCATED ON SIDE
OPPOSITE WALL/GRAB RAIL.
PROVIDE APPROPRIATE
TOILET TANK
TROLLEY
ELEVATION
- DRY
ASSEMBLY
2 x 6 CONT. WOOD BLOCKING
7"
2'-0"
3
_
3'-2 "
4
FLOOR DRAI N I F
RE QU I RE D BY STATE ,
or F OR 2 N D FL OO R
AP PL I CAT I O N S
LAMINATED 1 X 2 TRIM BOARD
SET IN CONTINUOUS BEAD OF
SEALANT
WATER VENDOR TO FASTEN
VALVE BOX (24"W X 27.5" H
PANEL) TO HORIZ. FRAMING
W/ STAINLESS STEEL
SCREWS IN PRE-DRILLED
3/16"∅ HOLES TOP AND
BOTTOM. (TYP. 4 PL).
3'-0"
TOI LE T PAPE R
DI S P E N S E R
FLOOR DRAIN IF
REQUIRED BY STATE
OR FOR 2ND FLOOR
APPLICATIONS
CLEAR
1'-0"
TOP OF TILE
6'-6"
3'-4"
2'-10"
1'-6"
CLEAR
P.LAM ON LOW WALLS
2"
CONTI NU OU S BE AD OF
CLE AR SI LI CONE
SEALANT AT PE RI ME TER
OF BO WL
VITREOUS CHINA
KNEE SHROUD
1'-6"
HSS 5x5x3/8"
CERAMI C TI LE-SEE
DETAI L AG-8 FOR
PATTE RN
5/8" DENS ARMOR PLUS FIRE
WLBD BEHIND DIALYSIS
4'-0"
CABINETS.
WALL HUNG DIALYSIS
COUNTER BY
MILLWORK VENDOR,
INSTALLED BY
CONTRACTOR
AT-50
A6.6
P.LAM TOP
42" LONG, 1-1/2"
DIA. GRAB BAR
W/ SAFETY GRIP
(PROVIDE WOOD
BLOCKING)
P AP E R T O WE L
DI S P E N SE R S I D E
MOUNTED
SI NK
"P-2"
TOILET TISSUE DISPEN.
2'-0"
2'-10"
CERAMIC TILE
ALL WALLS
SD
(N.I.C.)
24X36
MIRRORCENTER
OVER
SINK
REMOVABLE PANEL
ACCESS TO TOP OF VALVE PANEL
2"
WALL MTD LIGHT
36" LONG, 1-1/2" DIA.
GRAB BAR W/ SAFETY
GRIP (PROVIDE WOOD
BLOCKING)
3'-2 3/4"+/-
DENS ARMOR PLUS FI RE
WLBD. TH ROUG H OU T
(TYP.)
2'-3 1/2"
DENS ARMOR PLUS
FIRE WLBD.
THROUGHOUT (TYP.)
LOW WALL STIFFENER / SUPPORTS:
PROVIDE AT 8' O.C. AND AT ENDS OF
ISLAND OR AS REQUIRED.
WALL
MTD
LI GHT,
SEE
ELEC.
FI XTURE
SCH E DU LE
18" LONG VERT. GRAB BAR
3'-0"
WAL L M O U N T E D
LI GHT, SEE ELEC.
FI XTURE
SC H E D U L E
3' - 7 1/2"
SCALE: 3/8" = 1'-0"
GFCI RECEPTACLE
@ 48" A.F.F.
SCALE: 3/8" = 1'-0"
AA-5 HOME TRAINING CABINET ELEVATION
ALSO REFER TO DETAIL AA-5A
FOR THE REMAINDER OF THE HH
TRAINING ROOM ELEVATIONS
A6.6
AA-5
3/8" = 1'-0"
INTERIOR DETAILS
MATERIALS LEGEND
P-LAM 1 = WILSONART # 7054-60 WILD CHERRY
P-LAM 2 = WILSONART # 7925-38 MONTICELLO MAPLE
P-LAM 3 = WILSONART # 4669-60 NATURAL TIGRIS
S. S. 1= WILSONART # 9033ML CARAMEL MELANGE
SINK BASE & BOOK SHELF END
NURSE STATION STORAGE
AT-41
AT-46
1/2" = 1'-0"
FI RE AL ARM PUL L STATI ON
ELEVATION/SECTION
6"
SCALE: 1/2" = 1'-0"
RECEPTION DESK SECTION
ELECTRONIC SCALE PLAN/ ELEVATION
AA-1
AT-19
3/4" = 1'-0"
1/2" = 1'-0"
IN-SWINGING DOOR DESIGNS
32" X 50" SCALE (OFIC)
SCALE TOP PLATE (OFIC)
WALL COVERING # 1
FRAME ANCHOR BOLTS
(OFIC) SET FRAME LEVEL.
5/ "
8
GYP. BOARD
OVER STUDS @ 16" O.C.
HEADER
6'-0 1/2 "
CLEAR FLOOR SPACE RE QU I RE M E NTS:
2" REDUCER STRIP
7'-1"
LOCKABLE SLIDING
GLASS WINDOW
4'-4"
SOLID SURFACE
TRANSACTION TOP
3"
TOP OF TRACK FLUSH
WITH SILL
3"
WOOD BLOCKING
INSWING: 60" X 54"
OUTSWING: 48" X 48"
MOSAIC TILE
PLAS. LAMINATE O/ 40#
PARTICLE BOARD O/ 3/4"
EXT. GRADE PLYWOOD
1'-4"
6" MOLDED VINYL BASE
WAITING ROOM SIDE
RECEPTIO N SIDE
CONCRETE FILL
CHANNELS FOR
SCALE FRAME (OFIC)
PLAN VIEW @ TRANSACTION
WINDOW
OUT-SWINGING DOOR DESIGNS
3" 'Z' CHANNEL SCALE SUBFRAME (OFIC). SET
INTO CONC. PRIOR TO INSTALLATION OF
SCALE.
TOILET ROOM DESIGN CONSIDERATIONS:
ELECTRONIC SCALE - FLOOR SECTION
FOR CEILING HEIGHTS
GREATER THAN 9'-0", RECEPTACLE
FOR T.V. TO BE MOUNTED NO
HIGHER THAN 9'-0" A.F.F.
1. ADA REQUIRES THAT THE TOILET ROOM MEET
THE VARIOUS INDIVIDUAL MINIMUM CLEARANCE
REQUIREMENTS NOTED ABOVE. ROOM
CONFIGURATIONS MAY VARY BASED ON SITE
SPECIFIC CONDITIONS BUT MUST MAINTAIN
THESE CLEARANCES
AT-20
3" = 1'-0"
TV WALL MOUNT DETAIL
2. OUTSWINGING DOORS MUST NOT ENCROACH UPON
MORE THAN 50% OF THE CORRIDOR WIDTH
REQUIREMENTS FOR EGRESS PATHS
RECEPTION WINDOW SECTION
AP-8
AA-2
3/4" = 1'-0"
LAVATORY: 30" X 48"
TO I L E T :
FRONT APPROACH: 48" X
66"
SIDE APPROACH: 48" X
56"
TURNING RADIUS:
60" DIAMETER OR 60" "T"
TURN
DOOR CLEARANCE:
ROUND CORNERS OF
TRANSACTION TOP
PLAS. LAMINATE
TRIM SKIRT BO ARD
2 x WOOD STUDS EACH SIDE
OF (FULL DEPTH) WALL
FRAMING EXTEND TO
STRUCTURE ABOVE
EXISTING CONC. SLAB
WAITING
ROOM
SIDE
7'-1 1/2 "
RECEPTION
SIDE
DOOR SWINGS MAY NOT
ENCROACH UPON REQ.
F I X T U R E CLEARANCES
5'-1"
ALIGN TO DOOR HEAD
MIN.
ANGLE BY SIMPSON STRONG
TIE (TYPICAL AT EACH
CORNER)
NOTE:
6"
VCT FLOORING
3"
8'-6" OR 6" BELOW CLG*
2 x 12 WOOD BLOCKING
FMC LOCATION #8442-1
(address pending)
The Dalles, OR 97058
5'-2"
7'-8"
7'-4"
8'-1 1/2 "
SEE DETAIL OF SCALE
SECTION @ FLOOR
1
_
3 "
4
PEERLESS
SMARTMOUNT SA740P
ARTICULATING ARM
* NOTE:
6'
FMC The Dalles
6" MOLDED VINYL BASE
6"
C
L
1'-0"
C
L
32" X 50"
SCALE
6'-10"
Tenant Improvements
3'-6"
2'-10"
A6.7
MOSAIC TILE FROM BASE
CHAIR RAIL/TRANS. CNTR.
6'-0 1/2 "
OVERCUT CONC.
SLAB 42" X 62" X 6"
MIN. CENTER SCALE
IN PIT AND PARALLEL
TO WALL.
6"
AT-20
BLOCKING AS REQ'D
CLASS "A" RATED IMPACT
RESISTANT WALL PANEL
6"
1'-0"
1 1/2"
1
_
2'-3 "
2
2'-5"
METAL
ANGLES BOTH
SIDES @ TOP
AND BACK OF
BRACE
40# PARTICLE BOARD
SUPPORT BRACE
WITH PLAS. LAMINATE
FINISH ALL VISIBLE
SURFACES
FIN. CEILING(9'-0" MIN.)
SINGLE GANG
BOX(110V RECEPT.) BY
E.C.
MTL. STUD FRAMING EACH SIDE
OF WOOD STUDS
GYP. BD. PARTITION
PLAN
SINGLE GANG BOX BY E.C. (FOR
OWNER INSTALLED COAX CABLE)
1/2" = 1'-0"
1'-2"
8"
NURSE STATION WORK COUNTER
AT-47
SCALE: 1/2" = 1'-0"
SOLID SURFACE
TRANSACTION TOP
3/4" ELEC. CONDUIT TO 6"
ABOVE FIN. CLG BY E.C.
REMOVABLE ACCESS
PANEL, HANG ON
Z- CLIPS (TYPICAL)
PANEL LOCATIONS
SHALL CORRESPOND
WI TH
ELEC/DATA/PHONE
J-BOX LOCATIONS
MAINTAIN MIN 7' CLEAR
WAITING ROOM SIDE
PLAN VIEW @ TRANSACTION
WINDOW
RECEPTION SIDE
AP-8A
3/4" = 1'-0"
6"
SEE DETAI L AA-2
3 MM
EDGE BAND
TV SOFFIT MOUNTING DETAIL
ALL FRAMING
MEMBERS SHALL HAVE
HOLES FOR WI RE
MANAGEMENT
7'-10"
ROUND EXPOSED CORNERS OF
TRANSACTION COUNTER
PLAS. LAMINATE O/
40# PARTICLE BOARD
O/ 3/4" EXT. GRADE
PLYWOOD
20 GAUGE METAL STUD
SOFFIT FRAMING
12" X 15" REMOVABLE PANEL
1'-3"
"
2 x 12 WOOD BLOCKING
3'
4'-5 1/4 "
PLAS. LAMI NATE
TRI M SKI RT BOARD
32" X 50" ELECTRONIC
SCALE
WALL
BASE
EXIST. CONC
SLAB
R11'-6
PEERLESS
SMARTMOUNT SA740P
ARTICULATING ARM
4'-2"
8"
C
L
LOCKABLE SLIDING
GLASS WINDOW
2'-7 1/4"
1"∅ FLEXIBLE CONDUIT
1'-0"
PAINTED GYP BD
@ WINDOW JAMB
METAL CANTI LEVER
BRACKET, AS REQUI RED
FOR WORKSURFACE
SUPPORT
2" GROMMET
42" GRAB BAR, PROVIDE
BACKING PLATE
SINGLE GANG BOX FOR
COAX CABLE
8'-0"
BOTTOM
OF
SOFFIT
P-LAM 3,
(WORKSURFACE)
333 NW 5th Ave.
Phone: 503/224-4848
WALL COVERING # 1
3'-6"
C
L
1'-2"
6"
2 x WOOD STUDS EACH SIDE
OF SOFFIT FRAMING
FIRE ALARM ANNUNCIATOR PANEL
CLASS "A" RATED IMPACT
RESISTANT WALL PANEL
TOP OF PANEL TO 42" A.F.F.
6"
PAINTED GYP
BD S OFF I T
TREATMENT ROOM DOOR
REL EASE BUTTON AND ROCKER
SWI TCH
I NNER VESTI BUL E DOOR
R E L E AS E B U T T O N
SOLID SURFACE TOPCAP
MTL. STUD FRAMING EACH SIDE
OF WOOD STUDS
TE M P ER E D GL AS S
SPLASH GUARD,
SECURED IN CHANNEL
AT EDGE AND BOTTOM
MAIN INTERCOM PANEL
3'-0"
3/4" ELEC. CONDUIT
BY E.C.
1"X 4" CORK BOARD
3'-0"
RECESSED ELECTRONIC
READOUT BOX (OFIC) OFFSET
FROM SCALE AND FASTENED TO
2 X 4 WOOD STUDS EACH SIDE
OF BOX
3'-4"
1/2" = 1'-0"
1'-0"
1/2" = 1'-0"
SINGLE GANG BOX
@ 9'-6" A.F.F.(120V
RECEPT.)
METABOX FULL
EXTENION
DRAWER SLIDES
(TYPICAL)
5'-2"
5'-7"
NURSE STATION ELEVATION
CEILING GRID (10'-0" MIN.)
6"
PROVIDE LOCKS ON
ALL DRAWERS
3'-3"
AT-42
1/2" = 1'-0"
2'-7"
3'-0"
6"
NURSE STATION WORK COUNTER
2'-7"
5'-5' MIN.
THIS DIMENSION CAN BE
LARGER IF SPACE ALLOWS ON
THE FL OOR
2'-6"
P-LAM 2
REMOVABLE ACCESS
PANEL, HANG ON
Z- CLIPS (TYPICAL)
PANEL LOCATIONS
SHALL CORRESPOND
WI TH
ELEC/DATA/PHONE
J-BOX LOCATIONS
AT-45
1'-6"
P-LAM 1
P-LAM 1
Portland, OR 97209
Fax: 503/224-7116
P-LAM 1
SOLID
SURFACE SINK
COUNTERTOP
W/ INTEGRAL
DRIP EDGE
P-LAM 1
SOLID SURFACE
COUNTERTOP
3'-4"
P-LAM 1
P-LAM 1
3'-0"
P-LAM 1
INSTALL 4 "KEKU"
CLIPS FOR FRONT
ACCESS PANEL
P-LAM 1
11"
SOLID
SURFACE SINK
COUNTERTOP
SOLID SURFACE
TOPCAP
P-LAM 1
P-LAM 2
LOW
VOLTAGE
ALL FRAMING
MEMBERS SHALL HAVE
HOLES FOR WI RE
MANAGEMENT
SOLID SURFACE
SINK COUNTERTOP
W/ INTEGRAL DRIP
EDGE
4"
P
SOLID SURFACE
TOPCAP
1'-0"
3'-0" MAX.
3'-0"
T/D
3'-0" MIN.
P-3 HAND
WASH SINK
W/ ELECTRIC
EYE
2'-0"
SOLID
SURFACE
TOPCAP
P-LAM 1
SOLID
SURFACE SINK
COUNTERTOP
W/ INTEGRAL
DRIP EDGE
2'-6 1/4" MIN.
2'-0"
3'-0"
NURSE CAL L
ANNUNCIATOR
TEMPERED GLASS
SPLASH GUARD,
SECURED IN CHANNEL
AT EDGE AND BOTTOM
8"
SOLID
SURFACE
TOPCAP
P-LAM 2 OVER
VERTICAL CHASE
1
4"
"
R1
1'-2"
SOL I D SURFACE
COUNTER TOP
SOLID
S UR F AC E
TRANSACTI ON
COUNTER
TE M P ER E D GL AS S
SPLASH GUARD,
SECURED IN CHANNEL
AT EDGE AND BOTTOM
1'-0"
1'-2"
SDS STATUS MONI TOR
TREATMENT ROOM DOOR
REL EASE BUTTON AND ROCKER
SWI TCH
I NNER VESTI BUL E DOOR
R E L E AS E B U T T O N
SOL I D SURFACE
TOPCAP
1'-7"
P-LAM 2 OVER
VERTICAL CHASE
1'-0"
MAIN INTERCOM PANEL
1"X 4" CORK BOARD
1'-7"
TEMPERED GLASS
SPLASH GUARD,
SECURED IN STAINLESS
STEEL CHANNEL AT
EDGE AND BOTTOM
3'-4"
RO STATUS MONI TOR
1 "
4
3'-0"
GENERATOR ANNUNCIATOR
FI RE AL ARM PUL L STATI ON
BOBRICK 2621 PTD
NO CHASE AT NORTHEAST AND
SOUTHEAST CORNERS, SEE FLOOR
PLAN. PROVIDE FULL WIDTH
SPLASH GUARDS IN THESE TWO
LOCATIONS
3'-4"
FI RE ALARM
ANNUNCIATOR PANEL
SOLID
S UR F AC E
TOPCAP
2'-4"
1" = 1'-0"
3. DIMENSIONS SHOWN IN THESE DESIGNS
ARE TO THE I NSI DE FACE OF TH E STUD
WAL L S
4. 6" WALL I S REQUIRED BEHIND THE
FI XTU RE S I N ALL TOI LE T ROOM S
5. I N STATES THAT REQUIRE COMPLI ANCE
WITH ANSI 117.1, THE CLEAR FLOOR AREA
AROUND THE TOILET SHALL BE 60" X 54"
AND AN ADDITIONAL VERTICAL SIDE WALL
GRAB BAR I S NEEDED.
SWINGING DOOR DESIGNS
AG-1
1/4" = 1'-0"
Drafted By: AH
Checked By: AK
Date Drawn:
WALL CO VE RI N G
PE R FI NI SH SCH E DU LE
C
L
1'-4"
55" WALL MOUNTED
TELEVISION
CONTINUOUS 2x4 BLOCKING
BEHIND EACH SHELF
STANDARD (TYPICAL)
MOLDED VINYL CHAIR RAIL,
SET IN PLACE WITH
CONSTRUCTION ADHESIVE
16" DEEP, PLASTIC
LAMINATE ON 3/4" PLYWOOD
SHELVES
ANGLE BY SIMPSON STRONG
TIE (TYPICAL AT EACH
CORNER)
K-V #85 STANDARDS
( 2'-0" O.C. MAX ) AND
K-V #185 BRACKETS
4'-6"
2 x WOOD STUDS EACH SIDE
OF (FULL DEPTH) WALL
FRAMING EXTEND TO
STRUCTURE ABOVE
4" RUBBER BASE
WALL CO VE RI N G
PE R FI NI SH SCH E DU LE
2'-0"
1'-4"
6" FROM END MAX.
O.C. MAX.
TYPICAL ELEVATION
SCALE: 1/4" = 1'-0"
CONF ROOM TV WALL MOUNT
CHAIR RAIL
AP-7
3/4" = 1'-0"
REVISION DESCRIPTION
TOP OF RAIL@ 34" A.F.F.
SINGLE GANG
BOX(110V RECEPT.) BY
E.C.
2 x 12 WOOD BLOCKING
AA-14
11054
DATE
1'-0"
SINGLE GANG BOX BY E.C.
(FOR COAX CABLE)
Project #:
6/9/12
REV #
C
L
3/4" ELEC. CONDUIT TO 6"
ABOVE FIN. CLG BY E.C.
SHELVING IN CLEAN UTILITY
AT-CU
6" = 1'-0"
1/4" = 1'-0"
A6.7
INTERIOR DETAILS
2'-10"
2'-5" (TYP)
(N.I.C.)
SD
(N.I.C.)
SD
CENTRIFUGE (N.I.C.)
U.C.R.
(N.I.C.)
SURFACE MOUNTED GFCI
ELEC. RECEPTACLE
BEHIND REMOVABLE
PANEL FOR ELECTRIC
EYE FAUCET
FRONT ELEVATI ON
BD 18
2'-1" CLR.
5'-10"
ELEVATION
5'-2"
CLEAN SIDE
CORNER GUARD
(TOP @ 3'-4")
W2424
PRE-FAB CABI NET
W/ WI RE PULLS
PANEL WHERE AVAILABLE)
SD
PTD
ELEVATION "X"
2'-0"
2'-2"
DB12
SI NK
"P-3"
INSTALL (4) "KEKU"
CLI PS PER PANEL
FRONT
4'-0"
SL OP E D
PROTE C TI VE
PANE L
2'-4"
BASE M ATERI AL
PE R
FI NI SH SCHE DU LE
SECTION
1/2" SOLID SURFACE
COUNTERTOP W/ NO-DRIP
EDGE INSTALL LOOSE
SIDESPLASH @ WALL
3'-0"
BASE MATERI AL
PER FI NISH
SCH E DU LE
ELEVATI ON
RO /S DS RE TU R N SL E E VE
RO/ SD S SU PPL Y SL E E VE
DI RT Y SI DE
11'-6"
SINK
"P-15A"
1/2" SOLID SURFACE
COUNTERTOP W/ NO-DRIP
EDGE INSTALL LOOSE
SIDESPLASH @ WALL
SURFACE MOUNTED GFCI
ELEC. RECEPTACLE
INSIDE BASE CABINET
FOR ELECTRIC EYE
FAUCET
1" FILLER (WHERE
NEEDED) TO BE
BACKED UP WITH CLEAT
LINE OF DENS ARMOR
PLUS FIRE WLBD.
BEHIND COUNTER TO
48" A.F.F.
G.F.I. RECEPTACLE
CENTER AT 4'-0"
ABOVE FIN. FLOOR
1/2" THICK SOLID
SURFACE PANEL @
SI DE AND BACK
G.F.I. RECEPTACLE
CENTER AT 4'-0"
ABOVE FIN. FLOOR
(N.I.C)
ELE V "X"
SLOPED
REMOVABLE PANEL
4" R U B BE R B AS E S E T I N
S I L I C O N E S E AL AN T ,
T YP I C AL
BD 18
2'-9"
VALVE BOX &
DRAIN MTD
ON SIDE OF
CABINET
ASSEMBLY
WHITE ENAMEL CAST IRON
P-15 DROP-IN SINK
SINK
"P-15"
W2424
1/ "
4
1'-4"
LINE OF DENS ARMOR
PLUS FIRE WLBD.
BEHIND COUNTER TO
48" A.F.F.
(3) DUPLEX RECEPTACLES &
(1)DATA JACK FOR DIALYSIS
EQUI PMENT MOUNTED 18"
A.F.F. - SEE DETAIL ET-14 FOR
SPECS.
1'-11"
GFCI RECEPT. 48" A.F.F.,
(TYP. 3 PLACES)
SLOPED
REMOVABLE PANEL
CLEAR
4'-6" MIN.
1/2" THICK SOLID
SU RFACE PANE L
BE TWE E N U PPE R AND
LOWER CABI NET @
SIDE AND BACK, (USE
1/2" THICK SOLID
SURFACE SIDE AND BACK
SPLASH, EXTEND 24"
HIGH, COLOR TO MATCH
COUNTERTOP
W2424
W2024
SINK "P-3"
2'-1"
HANDWASH /LAB PREP CABINET ELEVATION
SCALE: 3/8" = 1'-0"
MEDICAL PREP CABINET ELEVATION
HANDWASH/LAB PREP CABINET ELEVATION
AT-7
SEPARATION ROOM CABINET ELEVATION
AT-10
3/8" = 1'-0"
3/8" = 1'-0"
EQ.
MAX. 5'
MAX. 5'
GROMMET2" DIA. 1 OF 3
QU ARRY TI LE FLOOR AND
QUARRY TI LE BASE WI TH E POXY
GROU T, OVE R PRE PARE D
CONCR E TE SLAB
MOP SINK
QUARRY TILE FLOOR AND
QUARRY TILE BASE WITH
EPOXY GROUT
RU BB E R B ASE SE T I N
C O N T I N U O U S B E AD
OF S I L I C O N E
EPOXY RESI N SHOP FLOOR
5/8" DENS ARMOR
PLUS FIREGUARD
MECH/STOR. ROOM
WAT E R T R E AT M E N T
CLASS "A" RATED FRP,
S E T P AN E L 1/4" ABOVE
BASE AND SE T I N
CONTINUOUS BEAD OF
SI LI CONE SEALANT
3/8" = 1'-0"
SECTION A-A
WATER TREATMENT DETAIL
AS-4
3/4" = 1'-0"
CLASS "A" RATE D FRP
SH AL L E X TE ND U P TH E
WALLS 4'-0"
BEDPAN WASH ER
PAPE R TOWEL
DI SPENSER
1"
2'-5"
AFF
TY
(N.I.C.)
P
LAVATORY
AA-3
1'-8"
1/2" = 1'-0"
2'-4"
2'-7"
SINK "P-14"
PLASTIC LAMINATE OVER
EXTERIOR GRADE PLYWOOD
OPEN ON SIDES FOR TECH
REPAIR
OPEN TO FINISHED FLOOR
11"
3'-8"
SINK "P-13"
4'-0" FRP.
SD
RECEPTION DESK DETAILS
7"
SI DE ELEVATI ON
1'-3"
Date Drawn:
Project #:
6/9/12
11054
NOTE:
FIBERGLASS REINFORCED PANELS SHALL BE INSTALLED IN
THE EMERGENCY SHOWER AREA, MEDICAL WASTE ROOM,
TECH REPAIR STATION, JANITOR CLOSET, AND
SDS/GRANUFLO AREAS
ALL PANELS USED MUST BE CLASS "A" FIRE RATED
2'-0"
FRONT ELEVATI ON
AS-5
1 1/2" = 1'-0"
AS-13
1'-6"
CL AS S " A"
R AT E D F R P
(H AL F S H E E T
AL L WAL L S . )
C
L
SEALED CONCRETE FLOOR
Checked By: AK
FRP BASE DETAILS
TECH REPAIR ELEVATION
4" RU BBE R BASE . SE T I N
B E AD O F S I L I C O N E .
1-1/8"
CLINICAL SINK W/
CONTINUOUS SILICONE
SEALANT
SOAP DI SAT
PEWALL
NSE R
3 M M E D G E ON ALL
E XPO SE D SU RFACE S
1'-0"
WALL HUNG CLINICAL
SERVICE SINK REQUIRES
12" MINIMUM CHASE WALL.
8"
P. LAMINATE
ANGLED BRACE
FASTEN (OWNER FURN.)
VALVE BOX TO FRAMED BOX
W/ STAINLESS STEEL
SCREWS IN PRE-DRILLED
3/16" O HOLES TOP AND
BOTTOM. (TYP. 4 PL).
3'-2 1/2"
NOTE: DENS ARMOR PLUS
FIRE WLBD. TO 96" A.F.F.
4" RUBBER BASE
THOROUGHLY GLUED TO
FRP
Drafted By: AH
2'-6 1/2"
3/4"x16"x30" PLASTIC
LAM. SHELF. ON
STANDARDS 2'-0" O.C.,
PROVIDE WOOD
BLOCKING
1'-6"
5'-0" MIN.
7" HIGH CONTINUOUS
WATER SHIELD FLASHING
BEHIND GYP. BD. AND FRP
2'-6 1/2"
3-1/2" x 1-1/2" CLEAT
ATTACHED TO BACK
AND SIDE WALLS
8"
N.
REVISION DESCRIPTION
AS-3
6"
MI
INTEGRAL SHOP FLOOR
BASE TO 4"
SEALED CONCRETE
FLOOR OR E POXY
SHOP FLOOR
HOLD GYP. BD. 1/4" ABOVE
SUB-FLOOR W/ CONT.
J-CHANNEL. PROVIDE
BACKER-ROD & SEALANT
JANITOR CLOSET ELEVATION
---
0"
7" HIGH CONTINUOUS
WATER SHIELD FLASHING
BEHIND GYP. BD. AND FRP
AS-5
A-A
6'-
CLASS "A" RATED FRP,
S E T P AN E L 1/4" ABOVE
BASE AND SE T I N
CONTINUOUS BEAD OF
SI LI CONE SEALANT
7" HIGH CONTINUOUS
WATER SHIELD FLASHING
BEHIND GYP. BD. AND FRP
CONTINUOUS ICE &
WATER SHIELD.
SI NK
"P-8"
PLAS. LAMINATE O/
3/4" 40# PARTICLE
BOARD, SCRIBE TO
WALL
3-1/2" x 1-1/2" CLEAT
ATTACHED TO BACK
AND SIDE WALLS
5/8" DENS ARMOR
PLUS FIREGUARD
CLASS "A" RATED FRP,
S E T P AN E L 1/4" ABOVE
BASE AND SE T I N
CONTINUOUS BEAD OF
SI LI CONE SEALANT
5/8" GYP BD. O/
3-5/8" STUDS @ 16"
O.C.
7"
2x BLOCKING
30" HOSE AND
BRACKET
MOUNT @ 3'-0" A.F.F.
4'-6"
4 ' R U B B E R B AS E S E T
B AS E I N B E AD O F
S I L I C O N E S E AL AN T
(T YP I C AL )
GYP. BD. WALL
1
3_ "
2
2 '-
3'-0"
*SHELVES ON WALL
OPPOSITE SINK
5/8" DENS ARMOR
PLUS FIREGUARD
3-1/2" SOUND
ATTENU ATI ON BLANKE TS
TO DE CK.
D E N S AR M O R
PLU S FI RE WLDB.
2'-2"
P. LAMINATE
ANGLED BRACE
DETAILS
MOP BRACKE T,
PROVIDE SOLID WOOD
BLOCKING
CLASS "A" RATED FRP
WAINSCOT 48" A.F.F. ON 2
WALLS ADJACENT TO MOP
SINK
3'-0"
1
_
3 "
2
PLAN VIEW
1'-5"
1
3_ "
2
1'-9"
SUPPORT BRACE PLAS.
LAMINATE O/ 3/4" PARTICLE
BOARD - PROVIDE WALL
BLOCKING AS REQ'D.
1
1_ "
2
DENS ARMOR PLUS
GYP. BD. TO 96" A.F.F.
(ALL WALLS AND CEILING)
SHELVES ON K-V # 85
STANDARDS W/ K-V #
185 BRACKETS
CLASS "A" RATED FRP O/
GYP. BD. BEHIND
SDS/GRANUFLO AREA AND
THE EMERGENCY SHOWER
CLASS "A" RATED FRP
(ALL WALLS) MAINTAIN 1/4" GAP
AT BOTTOM OF PANEL, SET I N
CONTINOUS BEAD OF
SI LI CONE SEALANT
S U R F AC E M O U N T E D L I G H T ,
SE E E L E C . FI XT U R E SC H E DU LE
* 1" X 12" WOOD
3/8" = 1'-0"
DATE
3"
TYPICAL
GROMMET
LOCATION
EQ.
AT-14B
3/8" = 1'-0"
FRP TRIM AS REQ'D ON
ALL EXPOSED EDGES
WITH CONTINOUS
SILICONE SEAL
3"
SEPARATION ROOM LAB SINK
AT-14
REV #
SI DE ELEVATI ON
AT-2
W2424
AT-3
GYP BOARD SOFFIT
ABOVE WALL CABINETS
FMC LOCATION #8442-1
(address pending)
The Dalles, OR 97058
2'-4"
CORNER GUARDS
(MOUNT UP TO 3'-4")
CONFERENCE ROOM CABINET ELEVATION
FMC The Dalles
BASE M ATERI AL
PE R
FI NI SH SCHE DU LE
REMOVABLE SLOPED
PROTECTIVE PANEL
3'-6"
3'-0"
U.C.R. (N.I.C.)
4'-0"
3/8" = 1'-0"
LI NE OF DE NS ARM OR
PLU S FI RE WLBD. BEHI ND
COUNTE R TO 48" A.F.F.
1/2" SOLID SURFACE
COUNTERTOP W/
NON-DRIP EDGE; 1/2" BACK
& SIDE SPLASH ON WALL,
EXTEND UP TO BOTTOM
OF WALL CABI NETS
SINK "P-4"
BD18
Tenant Improvements
2'-2"
SOLI D SURFACE
TOP CAP
AT-1
PAPER TOWEL
DISPENSER (SIDE
WALL MOUNTED)
1/2" SOLID SURFACE
COUNTERTOP W/ NON-DRIP
EDGE
6" MOLDED VINYL BASE
SET WITH
CONSTRUCTION
ADHESIVE
NOTE #1:
WI DTH NE EDE D FOR RE FRI GE RATOR
IS BASED UPON NUMBER OF PATI ENT
STATI ONS IN FACI LI TY. RATI O I S AS
FOLLOWS:
-00 TO 14 STATIONS : 32"
-15 TO 24 STATIONS : 34"
-25 TO 30 STATIONS : 35"
-30 + STATIONS : 38"
SINK
"P-15"
END/CHASE
WALL
1/2" THICK SOLID SURFACE
PANEL BETWEEN UPPER AND
LOWER CABINET @ REAR AND
SIDES
2'-0"
LINE OF DENS ARMOR
PLUS FIRE WLBD.
BEHIND COUNTER TO
48" A.F.F.
SOLI D S U RFACE
SI DE SPLASH PANE L
W2724
SINK "P-5"
2'-0"
W2724
1/ " SOLI D SURFACE
2
COUNTERTOP W/ NO-DRIP
EDGE , LOOSE
SI DE SPL ASH AT WALL
REMOVABLE SLOPED
PANEL TO MATCH
CABINETRY
AA-13
GYP. BOARD SOFFITABOVE WALL CABINETS
LOCKABLE WALL CABI NETS
W/ WIRE PULLS
END/CHASE WALL
G.F.I. RECEPTACLE
CENTER AT 4'-0"
ABOVE FIN. FLOOR
SENSOR CONTROLLED
FIXTURE
SD
U.C.R.
(N.I.C.)
PLAN VIEW
LOCKABLE PRE-FAB
CABI NETS W/ WI RE PULLS
PAPE R TOWE L DI SPE NSE R
(SI DE WALL M OU NTE D)
3'-0"
GYP. BOARD SOFFIT ABOVE
WALL CABINETS
1'-4"
SIM.
8'-0" TYP. (7'-0" MIN.)
3/8" = 1'-0"
SINK "P-3"
AT-1
W2424
(N.I.C.)
RUBBER BASE SET IN
SILICONE SEALANT AND
TRIMMED TO 2"
AA-9
3/8" = 1'-0"
W2424
B24
LOUNGE CABINETS ELEVATION
AA-7
3/8" = 1'-0"
B24
VARI E S
INSTALL REMOVABLE LAMINATED PANEL TO
MATCH CABINETS. SET PANEL TO MAI NTAI N
ADA REQUI REMENTS FOR CLEAR SPACE. SEE
AT-4
EXAM ROOM CABINET ELEVATION
CLEAR SILICONE
CAULK AT JOINT (TYP)
LINE OF DENS ARMOR
PLUS FIRE WLBD.
BEHIND COUNTER TO
48" A.F.F.
2'-0"
MEDICAL RECORDS ELEVATION
2'-0"
VARIES
SEE NOTE #1
6" TYP.
AA-4
(HAND WASHING)
BD15
2' MAX.
TYPICAL WALL
C
L
REFRIGERATOR (N.I.C.)
4'-0"
4" R U B B E R B AS E
ELEC. RECEPT.
@ 42" A.F.F.
SINK "P-5"
4" R U B BE R B AS E S E T I N
S I L I C O N E S E AL AN T ,
TYP I C AL .
BD18 (HAND WASHING)
(N.I.C.)
SD
PTD
ELE C.
RE CE P T. @
56" A.F.F.
LOCKABLE PRE-FAB
LAMINATE CABINETS W/
WIRE PULLS
333 NW 5th Ave.
Phone: 503/224-4848
SOLI D SURFACE
COUNTERTOP W/ NO-DRIP
EDGE , LOOSE
SI DE SPL ASH AT WALL
REMOVABLE SLOPED
PANEL TO MATCH
CABINETRY
LINE OF DENS ARMOR
PLUS FIRE WLBD.
BEHIND COUNTER TO
48" A.F.F.
W2424
COFFEE MAKER
MICROWAVE
(N.I.C.)
I NSTALL I NLI NE
FI LTER I N BASE
CAB. FOR I CE
M AK E R
1/ "
2
W2424
AT-4
2'-10"
SD
W2424
2'-4"
2'-0"
SENSOR CONTROLLED
FIXTURE
SINK "P-6"
4'-0"
1'-2"
1'-2"
1'-2"
1'-2"
PAPE R TOWE L DI SPE NSE R
(SI DE WALL M OU NTE D)
(N.I.C.)
G.F.I. RECEPTACLE
CENTER AT 4'-0"
ABOVE FIN. FLOOR
K-V #85
STANDARDS (2'-0"
O.C. MAX., 5'-0"
LONG) AND K-V
#185 BRACKETS.
W2424
2'-2"
1'-2"
LINE OF DENS ARMOR
PLUS FIRE WLBD.
BEHIND COUNTER TO
48" A.F.F.
NURSE CALL WITH
EMERG. PULL CORD
(WHERE REQ'D.)
LOCKABLE PRE-FAB
LAMINATE CABINETS W/
WIRE PULLS
W2424
1/2" THICK SOLID SURFACE
PANEL BETWEEN UPPER
AND LOWER CABINET,
COLOR SHALL MATCH
COUNTER
2'-2"
16" DEEP, 3/4" PAINTGRADE PLYWOOD
SHELVES WITH
HARDWOOD EDGEBAND
W2424
AT-6
1/2" THICK SOLID
SU RFACE PANE L
BE TWE E N U PPE R AND
LOWER CABINET, COLOR
TO MATCH COUNTER
(U S E 1/4" WH E RE
AVAILABLE)
ELECTRI
CAL
RECEPT. @42"
A.F.F.
RE C E S SE D WATE R
BOX FOR RE F. I CE
M AKE R M TD 30"
A.F.F.
2'-10"
1/2" THICK SOLID SURFACE
PANEL BETWEEN UPPER
AND LOWER CABINET,
COLOR SHALL MATCH
COUNTER
AT-4
AT-4
3'-0"
CONTINUOUS LAYER OF 1/2 "
PLYWOOD UNDER GYP.
BOARD ON WALLS TO
RECEI VE SHELVING
(TYPICAL) FOR BLOCKING
AT-6
AT-6
2'-2"
NO TE:
THIS ROOM TYPICALLY
HAS A 1 HOUR FIRE
RESISTANCE RATING , THIS
SHA LL IN CLUDE A LL WA LL
AND THE CEILING
Portland, OR 97209
Fax: 503/224-7116
1/2" SOLI D SU RFACE
COU NTE RTOP W/ NON- DRI P
EDG E; LOOSE SI DESPLASH @
WALL
3/8" = 1'-0"
VCT. FLOORING
NOTE: USE CLI NI CAL SI NK ONLY I N THOSE STATES THAT
REQUI RE I T, OTH ERWI SE USE BEDPAN WASHER I N PATI ENT
TOILET.
A6.8
SOILED UTILITY ELEVATION
AS-7
3/8" = 1'-0"
INTERIOR DETAILS
TAP E O R S TR AP P I NG TO
S E C UR E R E B AR TO S L E E V E
6" SCHEDULE 40 PVC
45 DEGREE ELBOW
METAL STRAPPI NG @
24" O.C. VERTICALLY
6"
M
IN
SP
A
C
ER
METAL STRAPPI NG @
24" O.C. VERTICALLY
SHALL BE RESPONSIBLE FOR SLEEVE
SHALL PROVIDE HEAVY DUTY PULL STRINGS IN
SHALL PROVIDE FOAM IN TOP OF SLEEVE AFTER
INSTALLED
4) BURI AL DEPTH OF SLEEVE CAN VARY DUE TO SI TE
CONDI TI ONS AND OTHER UTI LI TY OR STRUCTURAL EL EMENTS
5) A 6" LENGTH MI N. SPACER SHALL BE I NSTALLED BETWEEN THE
45 DEGREE ELBOWS TO ENSURE ADEQUATE BENDI NG RADI US
FOR THE TEFLON TUBI NG
6) 8" SCHEDULE 40 PI PE SHALL BE USED FOR SLEEVE WHEN 3 OR
MORE TUBI NG RUNS ARE REQUI RED
UNDERGROUND SLEEVE DETAIL
AT-35
PLASTIC LAMI NATE
DI ALYSI S COUNTER
TOP OVER SINGLE
LAYER MDF BOARD
OVER 3/4" PLYWOOD
1 X 3 FRAMING AT
24" O.C. OVER 2 X 4
LEDGER STRIP TO
SUPPORT COUNTER
EXTEND TO 2'-4" WHERE
WOOD FRAMING W/
HORIZONTAL BRACING
@ 24" O.C. VERTICALLY,
FRAMI NG SHALL BE
SPACED TO ALLOW 6 5/8"
O.D. SLEEVE TO PASS
BETWEEN
1'-4"
EXTEND TO 2'-4" WHERE
ADJACENT COUNTER EXI STS
NOTE: ALL DIMENSIONS TAKEN FROM FACE OF
STUD
DIALYSIS COUNTER END WALL w/ SLEEVE DETAIL
WOOD FRAMING W/
HORIZONTAL BRACING
@ 24" O.C. VERTICALLY,
FRAMI NG SHALL BE
SPACED TO ALLOW 6 5/8"
O.D. SLEEVE TO PASS
BETWEEN
1" TEFLON TUBING
BUNDLED WITH 1/2" SDS
TUBING
(BY OTHERS)
ADH E RE 1/2" SOLID
SURFACE M ATERI AL
DI RECTLY TO WALL
FU LL LE NG TH
BE T WE E N WAL L
CABINETS AND
COUNTER TOPS (0NLY
WH E RE SI NK
COUNTER I S
ADJACENT TO CHASE)
NOTE: ALL DIMENSIONS TAKEN FROM FACE OF
STUD
SCALE: 3/4" = 1'-0"
NOTE:
1) THI S DETAI L I S ONLY USED I N OVERHEAD SLEEVE
I NSTALLATI ONS
2) WHEN THE SIZE OF THE END CHASE WALL IS A CONCERN, 1
OR 2
4" SLE EVE S M AY BE U SE D.
PVC SLEEVE SHALL
EXTEND 3" BELOW TOP OF
COUNTE R
2 X 4 CHASE
FRAMING
1" = 1'-0"
1" TEFLON TUBING
BUNDLED WITH 1/2" SDS
TUBING
(BY OTHERS)
6" SCHEDULE 40 BELLED
END PVC SLEEVE,
STRAPPE D TO FRAMI NG
@ 24" O.C. VERTI CALLY
PLASTIC LAMINATE
TRI M BOARD
WOOD FRAMING W/
HORIZONTAL BRACING
@ 24" O.C. VERTICALLY,
FRAMI NG SHALL BE
SPACED TO ALLOW 6 5/8"
O.D. SLEEVE TO PASS
BETWEEN
1'-4"
METAL STRAPPI NG @
24" O.C. VERTICALLY
3 MM EDGE BAND
ADJACENT COUNTER EXI STS
6" SCHEDULE 40 BELLED
END PVC SLEEVE,
STRAPPE D TO FRAMI NG
@ 24" O.C. VERTI CALLY
PLASTIC LAMINATE
TRI M BOARD
3"
NOTES:
1) CONTRACTOR
INSTALLATION
2) CONTRACTOR
SLEEVE
3) CONTRACTOR
TUBING HAS BEEN
1" TEFLON TUBING
BUNDLED WITH 1/2" SDS
TUBING
(BY OTHERS)
6" SCHEDULE 40 BELLED
END PVC SLEEVE,
STRAPPE D TO FRAMI NG
@ 24" O.C. VERTI CALLY
ADH E RE 1/2" SOLID
SURFACE M ATERI AL
DI RECTLY TO WALL
FU LL LE NG TH
BE T WE E N WAL L
CABINETS AND
COUNTER TOPS (0NLY
WH E RE SI NK
COUNTER I S
ADJACENT TO CHASE)
3
6_ "
4
6" SCHEDULE 40 PVC
45 DEGREE ELBOW
NOT TO SCALE
PLASTIC LAMINATE
COUNTER TOP
6" SCHEDULE 40 BELLED
END PVC SLEEVE,
STRAPPE DTO FRAM I NG
@ 24" O.C. VERTI CALLY
WOOD FRAMING W/
HORIZONTAL BRACING
@ 24" O.C. VERTICALLY,
FRAMI NG SHALL BE
SPACED TO ALLOW 6 5/8"
O.D. SLEEVE TO PASS
BETWEEN
6" SCHEDULE 40 PVC
SLEEVE, 6" LENGTH MI N.
UNDERGROUND SLEEVE DETA IL
METAL STRAPPI NG @
24" O.C. VERTICALLY
PLASTIC LAMINATE
COUNTER TOP
Portland, OR 97209
Fax: 503/224-7116
(2) 24" REBAR, SECURED TO
EACH SI DE OF SLEEVE
CONCRETE SLAB
CONCRETE SLAB
PLASTIC LAMINATE
TRI M BOARD
I NDI RE CT WASTE
VENT PI PE
333 NW 5th Ave.
Phone: 503/224-4848
6"
6"
CONCRETE PATCH
(AS REQ'D)
I NDI RE CT WASTE
VENT PI PE
1
10 _ "
4
NON HARDENI NG FOAM
WATERPROOFI NG, SEALED
TIGHT AT ALL OPENI NGS
3 MM EDGE BAND
6" SCHEDULE 40 BELLED
END PVC SLEEVE SHALL
REST ON EDGE OF
FRAMING, FRAMING SHALL
BE AT FINISHED A.C.T.
HEIGHT
6 3/4"
1" RO TEFLON
TUBING, 1/2" BI-CARB
AND
1/2" ACID TUBING
(BY OTHERS)
45 DEGREE ELBOW,
POSITION TO DIRECT
TUBING TO ADJACENT
HANGING SLEEVE
6"
TEFLON TUBING SHALL BE
INSULATED FOR THE ENTIRE
LOOP TO ELIMINATE
EXPOSURE TO LIGHT AND TO
ALLOW FOR HEAT
DISINFECTI ON
(BY OTHERS)
DIALYSIS COUNTER END WALL W/ SLEEVE
DIALYSIS COUNTER END WALL WITH SLEEVE
AS-37
AT-38
3/4" = 1'-0"
3/4" = 1'-0"
VERTICAL SLEEVE CHASE
AT-36
3/4" = 1'-0"
MOUNTING BLOCK FOR
DEDICATED
TELEPHONE GROUND
10'-0"
AS-9
3'-2" MIN.
4'-0"
TV
AMPLI FI ER
12" x 18" x
5",
INSTALL
@ 7'-4"
A.F.F.
6" S LE E VE
BUILDING
MAINTENANCE
MANUAL
AS BUILT
DRAWINGS
FASTEN
SLATWALL
PANEL TO
WALL @ 5'-0"
A.F.F. TO TOP
OF PANEL
24" x 96" x 3/4"
PLYWOOD
@ 7'-0" A.F.F.
(SEE AS-9)
OPERATION &
MAINTENANCE
MANUAL
1'-0"
LSC 2000
MANUAL
VOL. 1
H ANG E R
BRACKETS
SHALL BE
INSTALLED
EVERY 6'-0"
5'-0"
NOTES:
1) THIS DETAIL I S ONLY USED
I N OVERHE AD SLEEVE
INSTALLATI ONS
2) CONTRACTOR SH ALL
PROVI DE HEAVY DUTY PULL
STRI NGS IN SLEEVE
FASTEN 3/4"
PLYWOOD TO
WALL @ 6'-9"
A.F.F. TO
SUPPORT
STEEL ANGLE
6'-9"
SECTION
VOICE/DATA PATIENT
NETWORK RACK 24"W
X 30"D X 81"H (O.F.I.C.)
2'-4"
3/4"
P L YWO O D
FULL HT. OF
WALL
4" R U BB E R
B AS E
FMC/GC
E XISTING
FURNISHED &
SUPPLIED
INST ALL E D
FU R N IS H E D
LANDLORD
COMMENTS
COORDINATION
& SCHEDULING
1/2" = 1'-0"
FURNISHED &
SUPPLIED
AS-9
1/2" = 1'-0"
GC
INST ALL E D
WIRING CLOSET TV BOARD ELEVATION
WATER
VENDOR
FURNISHE D
& SUPPLIED
FU R N IS H E D
AS-8
1/2" = 1'-0"
FMC
INST ALL E D
AT-39
WIRING CLOSET TV BOARD FP
SI T E WO RK
SEE DRAWI NGS
DEMOLITION
SEE DRAWI NGS
EXIT LIGHTING & SIGNS
TENANT DEMISING WALL
LI MI TED, SEE DRAWI NGS
SPRI NKLER SYSTEM PI PI NG AND HEADS
HVAC UNITS
GAS/POWER SUPPLY TO HVAC UNITS
1 HOUR RATED WALL
PROTECT ALL OPENINGS AND PENETRATIONS
3" (TYPICAL)
SLEEVE SUPPORT
NOTE: THIS DETAIL IS
ONLY TO BE USED
WHEN CLINICS ARE
NOT BEING EQUIPPED
WITH A DIRECT TOUCH
SYSTEM.
FU R N IS H E D
ELEVATI ON
FMC - CLINIC RESPONSIBILITY SCHEDULE
SLAT WALL NOTE S:
1) SUNCAST 1' X 4' SLAT
WALL PANEL
2) SUNCAST 8" X 12' X 8 1/2"
S T O R AG E B AS K E T
3) (2) SUNCAST 2" X 7" J-HOOK
4) 6" PVC TUBE, 28" LONG
FURNISHED &
SUPPLIED
FI NI SH ED
CE I LI NG
SLAT WALL NOTE S:
1) SUNCAST 1' X 4' SLAT
WALL PANEL
2) SUNCAST 8" X 12' X 8 1/2"
S T O R AG E B AS K E T
3) (2) SUNCAST 2" X 7" J-HOOK
4) 6" PVC TUBE, 28" LONG
INST ALL E D
NOTE: THIS DETAIL IS
ONLY TO BE USED
WHEN CLINICS ARE
NOT BEING EQUIPPED
WITH A DIRECT TOUCH
SYSTEM.
FU R N IS H E D
6'-0"
HVAC DUCTWORK
HVAC FIRE DAMPERS
FI RE ALAR M SYSTE M
SANI TARY SEWER LI NE TO BUI LDI NG
PRIMARY POWER TO BUILDING
(TYPICALLY ON MED RECORDS, MED WASTE, JANITOR CLOSET,
AND SOME TENANT DEMISING WALLS)
CI TY WATER SUPPLY TO BUI LDI NG
BACK FLOW PRE VE NT E RS
EMERGENCY WATER CONNECTION
PR O C E S S WAT E R H E AT E R
2 HOUR RATED WALL
PROTECT ALL OPENINGS AND PENETRATIONS
DOM ESTI C WATE R H E ATE R
WATE R TR E AT M E NT E Q U I PM E NT
Drafted By: AH
SDS & GRANUFLO EQUIPMENT
RO & SDS MONITORS & CABLING
(TYPICALLY ON TENANT DEMISING WALLS)
Checked By: AK
VALVE PANELS
TECH REPAI R VALVE BOX ASSE MBLY
DOUBLE EXIT DOOR AT REAR
TE M PE RATU RE C ON TR OL S YS TE M
1 HOUR RATED SMOKE & FIRE WALL
PROTECT ALL OPENINGS AND PENETRATIONS
Date Drawn:
Project #:
6/9/12
11054
DATA CABLING
REVISION DESCRIPTION
FASTEN SLATWALL
PANEL TO WALL @
5'-0" A.F.F. TO TOP
OF PANEL
6" SCHEDULE 40
SLEEVE
PROVIDE 2" CONDUIT
SLEEVES FOR
COAXIAL CABLE,
TERMINATE 6" BELOW
FINISH CEILING
10
/20 TAP TV
POWE R SU PP LY
TELEPHONE CABLING
TE LE VI SI ON/E NTE R TAI NM E NT SYSTE M
LOUNGE APPLIANCES
FURNITURE
(TYPICALLY ON WALLS THAT SEPARATE THE CLINIC INTO TWO
OR MORE SMOKE COMPARTMENTS)
PH ONE S YSTE M
SATE LLI TE H OO KU P
NETWORK RACKS
RECESSED SCALE FRAME & EQUI PMENT
LI GHT FI XTURES
NOTES:
1) STENCILS SHALL BE APPLIED TO EACH AND EVERY RATED WALL IN THE FACILITY.
2) STENCILS SHALL BE APPLIED SO THAT THE BOTTOM OF THE LETTERS ARE 6" ABOVE
THE CEILING GRID AND @ EVERY 10'-0" ON CENTER ALONG THE LENGTH OF THE
WALL.
3) WHERE THERE IS NOT A CEILING GRID, STENCILS SHALL BE APPLIED 10'-0" A.F.F.,
AND @ EVERY 10'-0" ON CENTER ALONG THE LENGTH OF THE WALL.
DATE
TAP TV
POWER
SU PPLY 17 1/4" X 18" X 7"
DE E P,
I N S T AL L @
7'-4" A.F.F.
10
/20
9'-0"
TI E - WRAPS
SH ALL BE
U S E D E VE R Y
18"
110 PUNCH
DOWN BLOCK
PLU MBI NG FI XTURE S
TIME CLOCK
S T AF F L O C K E R S
REV #
INSULATED
1" TEFLON
R.O. TUBING
(BY
OTHERS)
24" X 96" X 3/4"
PLYWOOD
BACKER BOARD
TV AMPLI FI ER
6"
WALL
MOU NTE D
PARTNER ACS
DU PLE X RE CEPTACLE
@ 90"A.F.F. ON 20A
DE DI CATE D CI RCUI T
3/4" PLYWOOD
FULL HT. OF WALL
FMC LOCATION #8442-1
(address pending)
The Dalles, OR 97058
H ANG E R
BRACKETS
SHALL BE
INSTALLED
EVERY 6'-0"
1/2 "A" AND
"B'
CONCENTRATE
TUBING
(BY OTHERS)
7'-6"
2" CONDUIT W/ PULL
STRING FOR
INCOMING "D-MARK"
PHONE LOCATION
FMC The Dalles
ROD
CONNECTED
TO UNI STRUT
ABOVE
Tenant Improvements
3/ "
8
CRASH CART
DIALYSIS MACHINES
OXYGEN CONCENTRATORS
OXYGEN CYLINDER STORAGE CONTAINER
H OYE R LI FT
MULTI FUNCTI ON PRI NTER
RATED WALL STENCILS
AG-22
1/2" = 1'-0"
A6.9
RESPONSIBILITY SCHEDULE
AG-19
1/4" = 1'-0"
INTERIOR DETAILS