standard construction details
Transcription
standard construction details
VILLAGE OF SHOREWOOD STANDARD CONSTRUCTION DETAILS UPDATED SEPTEMBER 2014 Village of Shorewood Construction Standards Christopher B. Burke Engineering, Ltd. Last Updated: September 2014 Detail Name Standard Description of Revisions Revision Date Pavement, Curb and Gutter, Sidewalks PVT-1 Roadway Cross Section (Major Arterial) PVT-2 Roadway Cross Section (Major Collector) PVT-3 Roadway Cross Section (Minor Collector) PVT-4 PVT-5 PVT-6 PVT-7 PVT-8 PVT-9 PVT-10 PVT-11 Roadway Cross Section (Local) Roadway Cross Section (Industrial) Parking Lot Pavement Right-In/Right-Out Driveway Entrance Barrier Combination Concrete Curb & Gutter, Type B-6.12 Mountable Combination Concrete Curb & Gutter, Type M-3.12 Residential Driveway Commercial Entrance PVT-12 PVT-13 PVT-14 PVT-15 PVT-16 PVT-17 PVT-18 PVT-19 PVT-20 PVT-21 Sidewalk Handicap Sidewalk Ramp Bituminous Bicycle Path Pavement Concentric Cul-De-Sac Eccentric Cul-De-Sac Butt Joint Bituminous Pavement Patching Open-Cutting Pavement Within the Public Right-of-Way Crack Sealing Typical Driveway Pinning STM-1 Storm Sewer System Storm Sewer Installation STM-2 STM-3 STM-4 STM-5 STM-6 STM-7 STM-8 STM-9 STM-10 Storm Manhole Type A Catch Basin Type A Catch Basin Type C Inlet Casting Installation and Adjusting Subsurface Drain Tile & Sump Pump Connection Sump Discharge Service Line Detention Pond Restrictor Pipe Restrictor Revised to allow for alternative pavement section using geogrid Revised to allow for alternative pavement section using geogrid Revised to allow for alternative pavement section using geogrid Revised to allow for alternative pavement section using geogrid Revised to allow for alternative pavement section using Revised to allow for alternative pavement section using New detail No revisions made No revisions made New detail New detail Added note indicating that at driveways, sidewalk PCC and base thickness shall match that of the driveway New detail Revised to require use of geogrid New detail New detail New detail New detail New detail New detail New detail No revisions made New detail; created separate details for storm and sanitary manholes Added note identifying structure wall thickness Added note identifying structure wall thickness Deleted Plan View Detail No revisions made New detail New detail New detail No revisions made September 2014 September 2014 September 2014 September 2014 September 2014 September 2014 June 2007 June 2007 June 2007 June 2007 June 2007 June 2007 July 2008 September 2014 June 2007 June 2007 June 2007 June 2007 October 2009 September 2011 September 2011 June 2007 June 2007 June 2007 June 2007 June 2007 June 2007 June 2007 June 2007 June 2007 June 2007 Sanitary Sewer System SAN-1 Sanitary Sewer Installation SAN-2 SAN-3 SAN-4 SAN-5 SAN-6 SAN-7 Sanitary Sewer Manhole Sanitary Manhole Frame & Cover Sanitary Manhole Pipe Connection Drop Connection Non-Residential Sewer Service Residential Sewer Service WTR-1 WTR-2 WTR-3 WTR-4 WTR-5 Water Distribution System Water Main Installation Thrust Block Installations Valve Vault Pressure Connection Valve Vault Valve Vault Frame and Cover WTR-6 Fire Hydrant WTR-7 Water Service WTR-8 Water Sampling Station Added table for required pipe materials; added note for joint requirements for gravity sanitary sewer New detail; created separate details for storm and sanitary manholes New detail No revisions made No revisions made New detail No revisions made June 2007 June 2007 June 2007 June 2007 June 2007 June 2007 June 2007 Revised testing requirements per Public Works direction June 2007 No revisions made June 2007 New detail June 2007 Added reference to detail WTR-5 June 2007 New detail June 2007 Revision to allowed manufacturers and new requirement for mechanical joint September 2014 Revised catalog numbers for corp and curb stops; added Notes #4-7 June 2007 New detail June 2007 Electrical System ELE-1 Ornamental Type Light Pole ELE-1A Pedestrian Scale (10') Ornamental Type Light Pole ELE-2 Pedestrian Scale Symmetrical Ornamental Type Light Pole N:\Shorewood\CONSTRUCTION STANDARDS\STANDARD DETAILS\Index of Revisions - September 2014.xls Revised catalog numbers to reflect new manufacturer codes and updated specifications New Standard New Standard April 2009 April 2009 April 2009 Detail Name Standard Description of Revisions ELE-3B ELE-4 ELE-5 ELE-6 ELE-7 ELE-8 ELE-9 ELE-10 Roadway Type Light Pole with Pedestrian Fixture Concrete Light Pole Foundation Light Pole Handhole Wiring Diagram Splicing Electrical Cables Conduit Installation Direct Connected Street Light Service Disconnect Com-Ed Overhead Connection for Lighting Controller Lighting Controller Revised catalog numbers to reflect new manufacturer codes and updated specifications New Standard; Revised catalog numbers to reflect new manufacturer codes and updated specifications Consoldated two old details into one New detail No revisions made Consolidated old conduit and trench details Miscellaneous minor revisions Miscellaneous minor revisions Revised for consistency with other detail revisions SGN-1 SGN-2 SGN-3 SGN-4 SGN-5 SGN-6 SGN-7 Street Signs Sign Standards No Parking Sign Residential Speed Limit Sign Sprinkling Sign 5 Ton Weight Limit Sign Sign Spacing for Typical Residential Subdivision Entrance Signage for Future Street Connection Revised Note #3A and 3E No revisions made No revisions made No revisions made No revisions made New detail New detail MSC-1 MSC-2 MSC-3 MSC-4 MSC-5 Miscellaneous Standards Permanent Monuments Casing Pipe Typical Service Laterals Handicap Stall Park Stall Striping New detail No revisions made No revisions made New detail New detail ELE-3A Roadway Type Light Pole N:\Shorewood\CONSTRUCTION STANDARDS\STANDARD DETAILS\Index of Revisions - September 2014.xls Revision Date April 2009 April 2009 July 2007 July 2007 July 2007 July 2007 July 2007 July 2007 July 2007 June 2007 June 2007 June 2007 June 2007 June 2007 July 2007 July 2007 June 2007 June 2007 June 2007 June 2007 January 2008 PVT-1 C/L R.O.W. LINE R.O.W. LINE 120' RIGHT OF WAY 33 12' 5' 27 33 12' 53' BACK TO BACK 30" 48' 1 2' 1' 1 4" PE R 2' 21 1 2' 10' F OOT ( T Y P. ) 2' 1 1/2" HOT-MIX. 12" ASPHALT SURFACE COURSE, MIX "D", (TYP.) N70 BIKEPATH (SEE PVT-14) PARKWAY SLOPE AT 1 2" PER 12" HOT-MIX ASPHALT BINDER FOOT (TYP.) COURSE, IL-19, N70 COMBINATION CONCRETE CURB & SIDEWALK (SEE PVT-12) GUTTER, TYPE B-6.24 12" AGGREGATE SUBBASE GRANULAR MATERIALS, TYPE B * ALTERNATE PAVEMENT SECTION THE FOLLOWING ALTERNATE PAVEMENT SECTION MAY BE USED, WITH THE USE OF TENSAR TRIAX TX5 GEOGRID (OR APPROVED EQUAL), AS ALLOWED BY THE VILLAGE ENGINEER: - 1 1/2" HOT-MIX. ASPHALT NOTES: 1. ALL CURBS AND SIDEWALKS SHALL BE CONSTRUCTED WITH IDOT CLASS "SI" CONCRETE WITH A MINIMUM COMPRESSIVE STRENGTH OF 3,500 PSI AT 14 DAYS. SURFACE COURSE, MIX "D", N70 - 10" HOT-MIX ASPHALT BINDER COURSE, IL-19, N70 - 12" AGGREGATE SUBBASE GRANULAR MATERIALS, TYPE B 2. PARKWAYS SHALL BE FINISHED WITH A MINIMUM OF SIX INCHES OF TOPSOIL. 3. TESTING OF SUBGRADE AND ALL ROADWAY MATERIALS SHALL BE DONE IN ACCORDANCE WITH THE VILLAGE'S SUBDIVISION ORDINANCE. 4. LIME MODIFICATION (OR EQUIVALENT) MAY BE USED TO REDUCE AGGREGATE SUBBASE THICKNESS AS APPROVED BY THE VILLAGE ENGINEER. 5. STANDARD ROADWAY TYPE LIGHT POLES SHALL BE INSTALLED WITH AN OPPOSITE CONFIGURATION & AT 190 FOOT SPACING, UNLESS OTHERWISE DIRECTED BY THE VILLAGE ENGINEER. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR ROADWAY CROSS-SECTION MAJOR ARTERIAL DATE: SEPTEMBER 2014 pvt-1 (arterial).dgn PVT-2 C/L R.O.W. LINE R.O.W. LINE ' 100' RIGHT OF WAY 48' BACK TO BACK 26' 26' 18" 5' 45' 20' 1' 1 4" PE R 14' 10' 2' F OOT ( T Y P. ) 1' 4" (TYP.) 1 1/2" HOT-MIX. PARKWAY ASPHALT SURFACE SLOPE AT COURSE, MIX "D", BIKEPATH 1 2" PER N70 (SEE PVT-14) 2 1/2" HOT-MIX ASPHALT FOOT (TYP.) BINDER COURSE, IL-19, N70 COMBINATION CONCRETE 1 8 2" HOT-MIX ASPHALT BASE COURSE CURB & GUTTER, TYPE B-6.12 (SEE DETAIL) SIDEWALK (SEE PVT-12) 4" AGGREGATE SUBBASE GRANULAR MATERIALS, TYPE B * ALTERNATE PAVEMENT SECTION THE FOLLOWING ALTERNATE PAVEMENT SECTION MAY BE USED, WITH THE USE OF TENSAR TRIAX TX5 GEOGRID (OR APPROVED EQUAL), AS ALLOWED BY THE VILLAGE ENGINEER: - 1 1/2" HOT-MIX. ASPHALT SURFACE COURSE, MIX "D", N70 NOTES: 1. ALL CURBS AND SIDEWALKS SHALL BE CONSTRUCTED WITH IDOT CLASS "SI" CONCRETE WITH A MINIMUM COMPRESSIVE STRENGTH OF 3,500 PSI AT 14 DAYS. 2. PARKWAYS SHALL BE FINISHED WITH A MINIMUM OF SIX INCHES OF TOPSOIL. - 2 1/2" HOT-MIX ASPHALT BINDER COURSE, IL-19, N70 - 6" HOT-MIX ASPHALT BASE COURSE - 8" AGGREGATE SUBBASE GRANULAR MATERIALS, TYPE B 3. TESTING OF SUBGRADE AND ALL ROADWAY MATERIALS SHALL BE DONE IN ACCORDANCE WITH THE VILLAGE'S SUBDIVISION ORDINANCE. 4. LIME MODIFICATION (OR EQUIVALENT) MAY BE USED TO REDUCE AGGREGATE SUBBASE THICKNESS AS APPROVED BY THE VILLAGE ENGINEER. 5. STANDARD ROADWAY TYPE LIGHT POLES SHALL BE INSTALLED WITH A SINGLE SIDED CONFIGURATION & AT 125 FOOT SPACING, UNLESS OTHERWISE DIRECTED BY THE VILLAGE ENGINEER. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR ROADWAY CROSS-SECTION MAJOR COLLECTOR DATE: SEPTEMBER 2014 pvt-2 (major collector).dgn PVT-3 C/L R.O.W. LINE R.O.W. LINE ' 80' RIGHT OF WAY 19 1 2' 41' BACK TO BACK 19 1 2' 18" 5' 13 1 2' 38' 1' 1 4" PE R 7 1 2' 10' 2' F OOT ( T Y P. ) 1' 4" (TYP.) 1 1/2" HOT-MIX. PARKWAY ASPHALT SURFACE SLOPE AT COURSE, MIX "D", BIKEPATH 1 2" PER N70 (SEE PVT-14) 2 1/2" HOT-MIX ASPHALT FOOT (TYP.) BINDER COURSE, IL-19, N70 COMBINATION CONCRETE CURB & GUTTER, TYPE 1 7 2" HOT-MIX ASPHALT B-6.12 (SEE DETAIL) BASE COURSE SIDEWALK (SEE PVT-12) 4" AGGREGATE SUBBASE GRANULAR MATERIALS, TYPE B * ALTERNATE PAVEMENT SECTION THE FOLLOWING ALTERNATE PAVEMENT SECTION MAY BE USED, WITH THE USE OF TENSAR TRIAX TX5 GEOGRID (OR APPROVED EQUAL), AS ALLOWED BY THE VILLAGE ENGINEER: NOTES: 1. ALL CURBS AND SIDEWALKS SHALL BE CONSTRUCTED WITH IDOT CLASS "SI" CONCRETE WITH A MINIMUM COMPRESSIVE STRENGTH OF 3,500 PSI AT 14 DAYS. 2. PARKWAYS SHALL BE FINISHED WITH A MINIMUM OF SIX INCHES OF TOPSOIL. 3. TESTING OF SUBGRADE AND ALL ROADWAY MATERIALS SHALL BE DONE IN ACCORDANCE WITH THE VILLAGE'S - 1 1/2" HOT-MIX. ASPHALT SURFACE COURSE, MIX "D", N70 - 2 1/2" HOT-MIX ASPHALT BINDER COURSE, IL-19, N70 - 5" HOT-MIX ASPHALT BASE COURSE - 8" AGGREGATE SUBBASE GRANULAR MATERIALS, TYPE B SUBDIVISION ORDINANCE. 4. LIME MODIFICATION (OR EQUIVALENT) MAY BE USED TO REDUCE AGGREGATE SUBBASE THICKNESS AS APPROVED BY THE VILLAGE ENGINEER. 5. STANDARD ROADWAY TYPE LIGHT POLES SHALL BE INSTALLED WITH A SINGLE SIDED CONFIGURATION & AT 175 FOOT SPACING, UNLESS OTHERWISE DIRECTED BY THE VILLAGE ENGINEER. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR ROADWAY CROSS-SECTION MINOR COLLECTOR DATE: SEPTEMBER 2014 pvt-3 (minor collector).dgn PVT-4 C/L R.O.W. LINE R.O.W. LINE 66' RIGHT OF WAY 1712' 5' 31' BACK TO BACK 11 12' 18" 28' 1' 1 4" PE R F OOT ( T Y P. ) 1' 4.5" SIDEWALK 1 1 2" HOT-MIX ASPHALT SURFACE COURSE, (SEE PVT-12) MIX "D", N50 (TYP.) PARKWAY SLOPE AT 1 2" PER FOOT (TYP.) 3 1/2" HOT-MIX ASPHALT BINDER COURSE, IL-19, N50 COMBINATION CONCRETE CURB & PRIME COAT, MC-30, AT 0.30 GUTTER, TYPE M-3.12, GAL./S.Y. (SEE DETAIL) IN RESIDENTIAL 10" AGGREGATE BASE COURSE, TYPE B AREAS, AND COMB. CONC. CURB & GUTTER, TYPE B-6.12, (SEE DETAIL) IN ALL OTHER AREAS * ALTERNATE PAVEMENT SECTION THE FOLLOWING ALTERNATE PAVEMENT SECTION MAY BE USED, WITH THE USE OF TENSAR TRIAX TX5 GEOGRID (OR APPROVED EQUAL), AS ALLOWED BY THE VILLAGE ENGINEER: - 1 1/2" HOT-MIX. ASPHALT SURFACE COURSE, MIX "D", N50 - 3" HOT-MIX ASPHALT NOTES: 1. ALL CURBS AND SIDEWALKS SHALL BE CONSTRUCTED WITH IDOT CLASS "SI" CONCRETE BINDER COURSE, IL-19, N50 - 8" AGGREGATE SUBBASE GRANULAR MATERIALS, TYPE B WITH A MINIMUM COMPRESSIVE STRENGTH OF 3,500 PSI AT 14 DAYS. 2. PARKWAYS SHALL BE FINISHED WITH A MINIMUM OF FOUR INCHES OF TOPSOIL. 3. TESTING OF SUBGRADE AND ALL ROADWAY MATERIALS SHALL BE DONE IN ACCORDANCE WITH THE VILLAGE'S SUBDIVISION ORDINANCE. 4. LIME MODIFICATION (OR EQUIVALENT) MAY BE USED VILLAGE OF SHOREWOOD STANDARD DETAIL TO REDUCE AGGREGATE SUBBASE THICKNESS AS APPROVED BY THE VILLAGE ENGINEER. 5. STANDARD SINGLE HEAD ORNAMENTAL TYPE LIGHT POLES SHALL BE INSTALLED WITH A SINGLE SIDED CONFIGURATION & AT 110 FOOT SPACING, UNLESS FOR ROADWAY CROSS-SECTION LOCAL DATE: SEPTEMBER 2014 OTHERWISE DIRECTED BY THE VILLAGE ENGINEER. PVT-4 (Local).dgn PVT-5 C/L R.O.W. LINE R.O.W. LINE 100' RIGHT OF WAY 40' BACK TO BACK 30' 37' 24' 5' 1.5' 1' 4" CROWN 6" 2" HOT MIX ASPHALT SIDEWALK 4" SURFACE COURSE, (SEE PVT-12) MIX "D", N70 PARKWAY SLOPE AT 2 1/2" HOT MIX ASPHALT 1/4" PER BINDER COURSE, IL-19, N70 FOOT 7" HOT MIX ASPHALT B 6.12 CURB & BASE COURSE GUTTER 6" CRUSHED AGGREGATE BASE COURSE, TYPE B * ALTERNATE PAVEMENT SECTION THE FOLLOWING ALTERNATE PAVEMENT SECTION MAY BE USED, WITH THE USE OF TENSAR TRIAX TX5 GEOGRID (OR APPROVED EQUAL), AS ALLOWED BY THE VILLAGE ENGINEER: - 2" HOT-MIX. ASPHALT SURFACE COURSE, MIX "D", N50 - 2 1/2" HOT-MIX ASPHALT BINDER COURSE, IL-19, N70 - 5" HOT-MIX ASPHALT BASE COURSE - 8" CRUSHED AGGREGATE BASE COURSE, TYPE B NOTES: 1. A CONCRETE PAVEMENT SECTION ALTERNATIVE MAY BE SUBMITTED FOR REVIEW AND APPROVAL 2. ALL CURBS AND SIDEWALKS SHALL BE CONSTRUCTED WITH A MINIMUM COMPRESSIVE STRENGTH OF 3500 PSI AT 14 DAYS. 3. PARKWAYS SHALL BE FINISHED WITH A MINIMUM OF SIX INCHES OF TOPSOIL. 4. TESTING OF SUBGRADE AND ALL ROADWAY MATERIALS SHALL BE DONE IN ACCORDANCE WITH THE VILLAGE'S SUBDIVISION ORDINANCE. 5. LIME MODIFICATION (OR EQUIVALENT) MAY BE USED VILLAGE OF SHOREWOOD STANDARD DETAIL FOR ROADWAY CROSS-SECTION TO REDUCE AGGREGATE SUBBASE THICKNESS AS APPROVED BY THE VILLAGE ENGINEER. INDUSTRIAL DATE: SEPTEMBER 2014 PVT-5 (Industrial).dgn PVT-6 1-1/2" HOT-MIX ASPHALT SURFACE COURSE, MIX "D", N50 2-1/4" HOT MIX ASPHALT BINDER COURSE, IL-19, N50 TACK COAT 10" COMPACTED AGGREGATE BASE, CA-6 (FOR AUTOMOBILE MOVEMENT) 14" COMPACTED AGGREGATE BASE, CA-6 (FOR TRUCK MOVEMENT) OOT R F N. 1/4" PE OPE MI SL PRIME COAT 12" MIN. B-6.12 COMBINATION CONCRETE CURB AND GUTTER PROPERLY PREPARED AND COMPACTED SUBGRADE APPROVED BY SOILS ENGINEER * ALTERNATE PAVEMENT SECTION THE FOLLOWING ALTERNATE PAVEMENT SECTION MAY BE USED FOR TRUCK MOVEMENT AREAS, WITH THE USE OF TENSAR TRIAX TX5 GEOGRID (OR APPROVED EQUAL), AS ALLOWED BY THE VILLAGE ENGINEER: - 1 1/2" HOT-MIX. ASPHALT SURFACE COURSE, MIX "D", N70 - 2-1/4" HOT-MIX ASPHALT BINDER COURSE, IL-19, N50 - 10" COMPACTED AGGREGATE BASE, CA-6 GENERAL NOTES: 1. DIMENSIONS SHOWN ARE MINIMUM VALUES. SOIL ANALYSIS AND TRAFFIC COUNTS SHALL BE USED FOR VERIFYING REQUIRED PAVEMENT SECTION. 2. INTEGRAL CURB AND GUTTER SHALL NOT BE PERMITTED WITH RIGID OR COMPOSITE PAVEMENTS. 3. THE FOLLOWING MATERIALS ARE ACCEPTABLE AS BASE COURSE ALTERNATIVES: BITUMINOUS BASE COURSE AND P.C. CONCRETE. 4. LIME MODIFICATION (OR EQUIVALENT) MAYBE USED TO REDUCE AGGREGATE BASE THICKNESS AS APPROVED BY THE VILLAGE ENGINEER. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR TYPICAL PARKING LOT PAVEMENT DATE: SEPTEMBER 2014 PVT-6 (Parking Lot).dgn PVT-7 PROPERTY LINE 24" 36" VARIES 30" OR 1’ MIN. RAD. ONLY 5 M 0’ R IN A D . . STANDARD 14 M ’ IN . R3-5 SIGN 36" 30" 24" STANDARD R3-2 SIGN ’ 14 IN. M 50’ MIN. RAD. 1’ MIN. 2’ RAD. 35’ MIN. 10’ MIN. ENTER STOP 30" DO NOT 30" 30" EXISTING EOP 30" STANDARD STANDARD R5-1 SIGN R1-1 SIGN 36" 36" STANDARD R3-2 SIGN VILLAGE OF SHOREWOOD STANDARD DETAIL FOR RIGHT-IN RIGHT-OUT DRIVEWAY ENTRANCE DATE: JUNE 2007 ...\PVT-7 (Right-in Right-out Driveway Entrance).dgn PVT-8 12" GUTTER FLAG 1" 6" 6" (CURB HEIGHT) BITUMINOUS SURFACE R 2" 1/4" R 3" PITCH IN SLOPE 3/ 4" PER FO OT AT EXPANSION JOINTS AND AT CONNECTIONS 6" 5" BETWEEN NEW AND EXISTING CURB AND GUTTER 4" (TYP.) THICKNESS OF PAVEMENT STRUCTURE 2- #5 DOWELS 2’ LONG 1’ 2- #4 BARS CONTINUOUS THROUGHOUT CURB AND GUTTER 4" CRUSHED AGGREGATE SUBBASE MATERIALS, TYPE B NOT TO SCALE NOTES: 1. ALL CURB AND GUTTER SHALL BE CONSTRUCTED WITH IDOT CLASS SI CONCRETE WITH A MINIMUM COMPRESSIVE STRENGTH OF 4000 PSI AT 14 DAYS. PROVIDE AND TEST 3 CYLINDERS FOR EACH DAY’S POUR, OR 50 CUBIC YARDS, WHICHEVER IS LESS. 2. CONTRACTION JOINTS SHALL BE SAW-CUT AT 20’ INTERVALS AND CAULKED. 3. PREFORMED EXPANSION JOINTS, 3/4" THICK, SHALL BE PLACED FIVE FEET EITHER SIDE OF STORM STRUCTURES IN CURB AND GUTTER, AT CURB RETURNS AND AT POINTS OF CURVATURE, AT ALL CONNECTIONS BETWEEN NEW AND EXISTING CURB AND GUTTER, AND AT 100’ INTERVALS ON TANGENTS. 4. CURB AND GUTTER AT STORM STRUCTURES SHALL BE BOXED-OUT AND HAND-FORMED BETWEEN EXPANSION JOINTS. FORMS SHALL BE PLACED AND INSPECTED BY VILLAGE PRIOR TO POURING CONCRETE. STRUCTURE FRAMES SHALL BE PLACED AND ADJUSTED PRIOR TO THIS INSPECTION. 5. THE FOLLOWING SHALL BE STAMPED IN THE CURB AT THE INDICATED LOCATIONS: "W" FOR WATER SERVICES "S" FOR SANITARY SEWER SERVICES "ST" FOR STORM SEWER SERVICES "CO" FOR STORM SEWER SERVICE LINE CLEAN-OUTS 6. DOWELS AT EXPANSION JOINTS SHALL BE CENTERED ON THE VILLAGE OF SHOREWOOD STANDARD DETAIL FOR CONCRETE CURB & GUTTER TYPE B-6.12 JOINT (DRILLED INTO EXISTING CURB AND GUTTER), AND SHALL BE INSTALLED WITH GREASE CAPS ON ONE SIDE. DATE: JUNE 2007 ...\PVT\pvt-8 (b-6.12 curb).dgn 9 1/2" 8 1/4" PVT-9 BITUMINOUS 2-3/4" SURFACE R 4" R 3" PITCH IN SLOPE 3/ 4" PER FO OT 2- #5 EXPANSION JOINTS AND AT CONNECTIONS BETWEEN NEW 6" AND EXISTING CURB AND 5" GUTTER 4" (TYP.) THICKNESS OF PAVEMENT STRUCTURE DOWELS 2’ LONG AT 1’ 2- #4 BARS CONTINUOUS THROUGHOUT CURB & GUTTER 4" CRUSHED AGGREGATE SUBBASE MATERIALS, TYPE B NOT TO SCALE NOTES: 1. ALL CURB AND GUTTER SHALL BE CONSTRUCTED WITH IDOT CLASS SI CONCRETE WITH A MINIMUM COMPRESSIVE STRENGTH OF 4000 PSI AT 14 DAYS. PROVIDE AND TEST 3 CYLINDERS FOR EACH DAY’S POUR, OR 50 CUBIC YARDS, WHICHEVER IS LESS. 2. CONTRACTION JOINTS SHALL BE SAW-CUT AT 20’ INTERVALS AND CAULKED. 3. PREFORMED EXPANSION JOINTS, 3/4" THICK, SHALL BE PLACED FIVE FEET EITHER SIDE OF STORM STRUCTURES IN CURB AND GUTTER, AT CURB RETURNS AND AT POINTS OF CURVATURE, AT ALL CONNECTIONS BETWEEN NEW AND EXISTING CURB AND GUTTER, AND AT 100’ INTERVALS ON TANGENTS. 4. CURB AND GUTTER AT STORM STRUCTURES SHALL BE BOXED-OUT AND HAND-FORMED BETWEEN EXPANSION JOINTS. FORMS SHALL BE IN PLACE AND INSPECTED BY VILLAGE PRIOR TO POURING CONCRETE. STRUCTURE FRAMES SHALL BE PLACED AND ADJUSTED PRIOR TO THIS INSPECTION. 5. THE FOLLOWING SHALL BE STAMPED IN THE CURB AT THE INDICATED LOCATIONS: "W" FOR WATER SERVICES "S" FOR SANITARY SEWER SERVICES "ST" FOR STORM SEWER SERVICES "CO" FOR STORM SEWER SERVICE LINE CLEAN-OUTS 6. DOWELS AT EXPANSION JOINTS SHALL BE CENTERED ON THE JOINT (DRILLED INTO EXISTING CURB AND GUTTER), AND SHALL BE INSTALLED VILLAGE OF SHOREWOOD STANDARD DETAIL FOR CONCRETE CURB & GUTTER TYPE M-3.12 WITH GREASE CAPS ON ONE SIDE. DATE: JUNE 2007 ...\PVT\pvt-9 (m-3.12 curb).dgn 12" PREFORMED EXPANSION JOINT (TYP) 1’ PVT-11 ONE WAY 16’ MIN - 20’ MAX TWO WAY 5’ 24’ MIN - 36’ MAX P L SIDEWALK B-6.12 CONTRACTION CURB AND JOINT (TYP.) GUTTER 20’ RAD. MINIMUM EXISTING CURB AND GUTTER 6 %17 45% 5’ 34" PREFORMED EXPANSION JOINT WITH (2) 1-1/4" EPOXY DEPRESSED CURB & GUTTER EXISTING, PROPOSED, OR SAWCUT COATED DOWEL BARS WITH GREASE CAPS (TYP) R.O.W. LINE 34" PREFORMED EXPANSION JOINT 2% MAX MAX 1% MIN - 8% 5’ 1’ 5" CA-6 STONE BASE EXISTING ROADWAY 8" P.C.C PAVEMENT (3500 P.S.I. MIN) DEPRESSED COMBINATION CONCRETE CURB & GUTTER NOTES: 1. ALL CONCRETE SHALL BE IDOT CLASS "SI" CONCRETE WITH A MINIMUM COMPRESSIVE STRENGTH OF 3,500 PSI AT 14 DAYS. 2. THE SUBGRADE SHALL BE STABLE AND MECHANICALLY COMPACTED. VILLAGE OF SHOREWOOD STANDARD DETAIL 3. ALL AGGREGATE SUBBASE SHALL BE MECHANICALLY COMPACTED. 4. CONCRETE AND BASE THICKNESS OF SIDEWALK THRU DRIVEWAY SHALL MATCH THAT OF DRIVEWAY. 5. WELDED WIRE FABRIC (6"X6") OR WIRE MESH SHALL BE INSTALLED IN FOR COMMERCIAL ENTRANCE DRIVEWAYS AND IN SIDEWALKS THROUGH DRIVEWAYS AT 2" ABOVE BOTTOM SLAB. DATE: JUNE 2007 ...\PVT-11 (Nonresidential Driveway).dgn PVT-12 INSTALL #4 REINFORCING BARS, 12" LONG, EMBEDDED 6", AT ALL CONNECTIONS BETWEEN NEW AND EXISTING SIDEWALKS. (TYP. FOR 3) BARS SHALL BE SPACED A MINIMUM OF 6 INCHES FROM EACH OTHER AND FROM EDGES OF WALK. 5’ 2 12" (3") 5" 4" 6" (TYP.) CA-6 STONE BASE NOTES: 1. ALL SIDEWALK SHALL BE CONSTRUCTED WITH IDOT CLASS "SI" CONCRETE WITH A MINIMUM COMPRESSIVE STRENGTH OF 3,500 PSI AT 14 DAYS 2. PREFORMED EXPANSION JOINTS (34" THICK) SHALL BE CONSTRUCTED IN SIDEWALK EVERY 100 FEET AND AT ALL ABUTTING DRIVEWAYS AND CURB AND GUTTER. 3. TOOLED CONTRACTION JOINTS SHALL BE CONSTRUCTED IN SIDEWALK EVERY FIVE FEET. 4. SIDEWALK SHALL HAVE 14" PER FOOT CROSSSLOPE. 5. WELDED WIRE FABRIC (6X6/6X6) OR FIBER MESH SHALL BE INSTALLED THROUGH DRIVEWAYS AT 2" ABOVE SLAB BOTTOM. VILLAGE OF SHOREWOOD 6. FORMBOARD REQUIREMENTS: MINIMUM 2" X 6". STANDARD DETAIL 7. USE 2#4 REINFORCING BARS, 10’ LONG OVER FOR ALL UTILITY TRENCHES FOR NEW SIDEWALK. SIDEWALK 8. AT DRIVEWAYS, SIDEWALK PCC AND BASE THICKNESS SHALL MATCH THAT OF THE DRIVEWAY. DATE: JUNE 2007 ...\PVT\pvt-12 (sidewalk).dgn PVT-13 TYPE A TYPE A NON-WALKING TYPE B AREA TYPE A TYPE B 48" MIN. 36" 48" MIN. MIN. TYPE B 48" MIN. 24" MIN. TYPE B STRAIGHT CURB (TYP.) TYPE B LESS THAN 48" TYPE A 48" OR MORE RECOMMENDED LOCATION OF RAMPS TYPE A RAMPS TYPE B RAMPS RAMP RAMP TYPE B WIDTH WIDTH 6" SIDE 6" TYPE A CURB A TEXTURED SURFACE A 24" 24" RAMPS AT ALLEY OR DRIVEWAY SIDE FLARE 60" MIN. VARIA BL E 2% MAX. SIDE FLARE TYPE B TYPE A VARIA BL 60" MIN. E DETAILS OF RAMPS SECTION A-A 2"R 6" SEE DETAILS A & B FLUSH WITH TOP OF ROADWAY CURB AND TOP OF SIDEWALK SLOPE 1:12 MAX. VARIABLE RAMP THICKNESS RAMP DETAIL OF SIDE CURB RISE OF RAMP=30" MAX. SIDE CURB MAY BE CONSTRUCTED MONOLITHICALLY WITH RAMP. RAMP PROFILE VILLAGE OF SHOREWOOD SPECIAL DEPRESSED CURB EXPANSION JOINT GUTTER SLOPE SIDE CURB (WHERE REQUIRED) STANDARD DETAIL RAMP 2"R 1:20 MAX. FOR HANDICAP SIDEWALK RAMP DATE: JULY 2008 CURB RISE 1/2" MAX. DETAIL A DETAIL B SPECIAL DEPRESSED CURB 1 OF 2 ...\PVT-13 (Handicap Sidewalk Ramp).dgn PVT-13 (42 min. - 60 max.) 1.66 min. - 2.35 max. (5) 0.2 0.4 (10) 0.9 (23) DETECTABLE WARNINGS DETAIL TRUNCATED DOME DETAIL GENERAL NOTES: N:\Shorewood\CONSTRUCTION STANDARDS\STANDARD DETAILS\PVT\PVT-13a (Handicap Sidewalk Ramp).dgn 1. RAMPS SHALL BE LOCATED AS SHOWN ON THE PLANS IN ALIGNMENT WITH NORMAL SIDEWALK AND/OR CROSSWALK AND SHALL HAVE SUFFICIENT CURB LENGTH AT CORNER RADIUS TO PREVENT VEHICULAR ENCROACHMENT. 2. CURB RAMPS AT MARKED CROSSINGS SHALL BE WHOLLY CONTAINED WITHIN THE MARKINGS, EXCLUDING ANY FLARED SIDES. 3. THE MAXIMUM SLOPE OF THE SIDE FLARE FOR TYPE B RAMPS SHALL BE 1:10. 4. RAMPS SHALL BE CONSTRUCTED OF P.C. CONCRETE IN ACCORDANCE WITH THE AND AN OBSTRUCTION IS LESS THAN 48", THE MAXIMUM SLOPE SHALL BE 1:12. IDOT "STANDARD SPECIFICATIONS FOR ROAD AND BRIDGE CONSTRUCTION". TEXTURED FINISH SHALL BE EAST JORDAN PLATE. 5. THICKNESS OF RAMPS WILL BE THE SAME AS THE ADJACENT SIDEWALK WITH A MINIMUM OF 5". 6. DETECTABLE WARNINGS SHALL BE INSTALLED AT CURB RAMPS, MEDIANS AND PEDESTRIAN REFUGE ISLANDS, AT-GRADE RAILROAD CROSSINGS, TRANSIT PLATFORMS EDGES, AND OTHER LOCATIONS WHERE PEDESTRIANS ARE REQUIRED TO CROSS A HAZARDOUS VEHICULAR WAY. DETECTABLE WARNINGS SHALL ALSO BE INSTALLED AT ALLEYS AND COMMERCIAL ENTRANCES WHEN PERMANENT TRAFFIC CONTROL DEVICES ARE PRESENT. 7. DETECTABLE WARNING SURFACE SHALL BE EAST JORDAN PLATE OR APPROVED EQUAL. PLATES SHALL BE INSTALLED PARALLEL TO AND ABUT AGAINST THE DEPRESSED CURB. PLATES AT CURB RAMPS WITHIN CURB RETURNS SHALL BE MANUFACTURED TO MATCH THE CURB RADIUS. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR HANDICAP SIDEWALK RAMP DATE: JULY 2008 2 OF 2 ...\PVT-13a (Handicap Sidewalk Ramp).dgn R. O. W. PVT-14 WIDTH + 2' WIDTH 2' WIDTH/2 1' MATCH SLOPE (TYP.) DIRECTION OF EXIST. GRADING (2.0% MAX) BEVEL EDGES AT 45° ANGLE 2" HOT-MIX ASPHALT SURFACE COURSE, MIX "D", N50 8" AGGREGATE BASE COURSE, CA 6 TENSAR TRIAX TX5 GEOGRID (OR APPROVED EQUAL) INSTALLED PER MANUFACTURER RECOMMENDATIONS. COMPACTED SUBGRADE NOTE: ALL EXISTING SUBGRADE MATERIALS TO BE RE-USED MUST BE TESTED AND COMPACTED AS REQUIRED TO MEET MINIMUM STABILITY REQUIREMENTS. WIDTH = 8' FOR LOCAL STREETS 10' FOR COLLECTOR STREETS VILLAGE OF SHOREWOOD STANDARD DETAIL FOR BITUMINOUS BICYCLE PATH PAVEMENT DATE: SEPTEMBER 2014 pvt-14 (bituminous bikepath) PVT-15 BACK SET LI NE EXPANSION JOINT ’ 30 1’ 5’ R ’R 2 6 15’R 11’ .O . .W /C B ’ R .0 5 4 22%%d T= 98.47’ TO CENTER 63 .5 8’ 22%%d 60’R 66’ R.O.W. 11.5’ 5’ 1’ 11.5’ 31’ 5’ 1’ NOTES: 1. MINIMUM PARKWAY WIDTH SHALL BE 11.0’. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR CONCENTRIC CUL-DE-SAC DATE: JUNE 2007 ...\PVT-15 (Cul-De-Sac Concentric).dgn ______ PVT-16 BACK EXPANSION JOINT LINE T SE ’ 0 3 TR .O .W . /C . B ’R .0 45 .R .0’ 11 62 ’R C U R A B N SI TI O N ’ .0 11 50’ MIN. ARC C / . B 60%%d ’R .0 45 5’ 43’R. B/C 11.5’ 1’ 37%%d-30’ T = 6 3 .5 7 ’ 114.66’(34.95M) TO CENTER 15’R 60’R 15’R 66’ R.O.W. 11.5’ 31’ 11.5’ 5’ 5’ NOTES: 1’ 1’ 1. MINIMUM PARKWAY WIDTH SHALL BE 11.0’. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR ___________ ECCENTRIC CUL-DE-SAC _____________ DATE: APRIL 2007 DATE: JUNE 2007 ...\PVT-16 (Cul-De-Sac Eccentric).dgn EXISTING CURB A PVT-17 & GUTTER B B 6’ PROPOSED (TYP.) WIDENING EXISTING ROADWAY EDGE 3’ (TYP.) A EDGE OF BUTT JOINT C L FOR WIDENING LESS THAN 8’(2.44M) WHERE COMPACTION IS DIFFICULT, CONCRETE SHALL BE USED. PROPOSED SURFACE EXISTING SURFACE (TYP.) 3’ (TYP.) PROPOSED BINDER EXISTING BINDER (TYP.) PROPOSED CURB & EXISTING BASE (TYP.) 18" GUTTER EXISTING SUBBASE PROPOSED BASE C L PROPOSED SUBBASE SECTION A-A EXISTING SURFACE (TYP.) PROPOSED SURFACE 6’ (TYP.) EXISTING BINDER (TYP.) PROPOSED BINDER PROPOSED BASE EXISTING BASE (TYP.) EXISTING SUBBASE (TYP.) PROPOSED SUBBASE SECTION B-B VILLAGE OF SHOREWOOD STANDARD DETAIL FOR BUTT JOINT DATE: JUNE 2007 ...\PVT\PVT-17 (Butt Joint).dgn PVT-18 PAVEMENT 36"MIN. PATCHING LIMITS ANGLES NOT LESS THAN 60%%176 A EXISTING LONGITUDINAL JOINT VARIABLE 36" MIN. F C B STRIP REFLECTIVE CRACK CONTROL TREATMENT - SYSTEM B B B B C A B B F ANGLES NOT LESS THAN 60%%176 PER IDOT STANDARDS C L CONSTRUCTION JOINT EXIST. PAV’T VARIABLE SECTION A-A SECTION B-B C L CONSTRUCTION JOINT C L EXIST. PAVEMENT SECTION C-C (BUILT IN TWO OPERATIONS) (3’-0") TO (3’-0") TO (5’-0") (5’-0") SECTION F-F (BUILT IN TWO OPERATIONS) GENERAL NOTES: 1. EXISTING TIE BARS SHALL BE EITHER CUT OR REMOVED. MARGINAL BARS SHALL BE CUT. 2. IN LOCATIONS WHERE BITUMINOUS PATCHES WILL BE OVERLAYED WITH BITUMINOUS SURFACE COURSE, STRIP REFLECTIVE CRACK CONTROL TREATMENT SHALL BE APPLIED TO ALL PAVEMENT JOINTS AND CENTERED ALONG THE RESPECTIVE JOINTS. 3. IN LOCATIONS WHERE THE PAVEMENT PATCH WILL NOT BE OVERLAYED, TWO (2) INCHES OF BITUMINOUS SURFACE COURSE SHALL BE LAID IN THE FINAL LIFT OF THE PATCH. 4. THE DEPTH OF THE BITUMINOUS PAVEMENT PATCH SHALL MATCH THE FULL DEPTH OF THE EXISTING PAVEMENT, BUT SHALL NOT BE LESS THAN THE VILLAGE STANDARD FOR THE RESPECTIVE PAVEMENT SECTION. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR BITUMINOUS PAVEMENT PATCHING DATE: JUNE 2007 ...\PVT-18 (Bituminous Pavement Patching).dgn PVT-19 NEW PAVEMENT MATCH EXISTING PAVEMENT SECTION TOP OF PAVEMENT SUBGRADE ELEVATION 12" MIN. 12" MIN. CONTROLLED LOW-STRENGTH MATERIAL (CLSM) 6" UTILITY PIPE 4" IDOT CA-7 BEDDING AND HAUNCHING TO 6" ABOVE PIPE IF ENCOUNTERED, REMOVE VARIABLE UNSUITABLE MATERIAL AND REPLACE WITH AGGREGATE MATERIAL, AS APPROVED BY VILLAGE NOTES: 1. THIS DETAIL SHALL BE USED FOR TRENCHING OPERATIONS WITHIN THE PUBLIC RIGHT-OF-WAY THAT ARE WITHIN FIVE (5) FEET OF STREETS, DRIVEWAYS, CURB AND GUTTER, PARKING LOTS AND OTHER PAVED AREAS INTENDED FOR VEHICULAR TRAVEL AS REQUIRED BY THE VILLAGE. 2. CONTROLLED LOW-STRENGTH MATERIAL (CLSM) SHALL BE IN ACCORDANCE WITH SECTION 593 OF THE IDOT SPECIFICATIONS AND SECTION 20-3.03 OF THE STANDARD SPECIFICATIONS FOR WATER AND SEWER CONSTRUCTION IN ILLINOIS, LATEST VERSIONS. 3. THERMAL PROTECTION SHALL BE PROVIDED PER IDOT STANDARD SPECIFICATIONS AND AS DIRECTED BY THE VILLAGE. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR OPEN CUTTING PAVEMENT WITHIN THE PUBLIC RIGHT-OF-WAY DATE: OCTOBER 2009 ...\PVT-19 (open cutting pavement).dgn PVT-20 1/32" MAX 1" ROUTE & FILL CRACK PER SPECIFICATIONS 1" PAVEMENT CRACK CROSS SECTION NOTE: PRIOR TO FINAL ACCEPTANCE OF A SUBDIVISION BY THE VILLAGE, CRACK SEALING OF ALL PUBLIC ROADWAYS IN ACCORDANCE WITH THIS DETAIL SHALL BE COMPLETED TO THE SATISFACTION OF THE ENGINEER. SPECIFICATIONS: THIS WORK SHALL CONSIST OF CLEANING EXISTING ROADWAY CRACKS AND PLACING RUBBER SEALANT AT THE LOCATIONS DESIGNATED BY THE ENGINEER. THE SEALING COMPOUND SHALL BE THE RUBBER-ASPHALT HOT-POURED TYPE CONFORMING TO THE FOLLOWING SPECIFICATION IN EFFECT AT THE TIME OF THE CONTRACT. FEDERAL SPECIFICATIONS SS-S-1401 ASTM D-3405 POURING TEMPATURE - 370^F SAFE HEATING TEMPERATURE - 390^F EXCEEDS REQUIREMENTS OF: ASTM-D-1190, AASHTO-M-173, SS-S-164 THE CONTRACTOR SHALL SUBMIT THE MANUFACTURER’S SPECIFICATIONS FOR THE HOT-POURED RUBBER-ASPHALT MATERIAL AT LEAST SEVEN (7) DAYS PRIOR TO THE START OF ANY WORK. THE POURING TEMPERATURE OF THE CRACK SEALER SHALL BE 370^F. CRACK FILLING MATERIAL SHALL BE PLACED ONLY WHEN THE CRACKS ARE IN A DRY CONDITION AND WEATHER CONDITIONS ARE FAVORABLE. THE CRACK FILLER MAY BE PLACED WHEN AIR TEMPERATURES IN THE SHADES ARE 40^F AND THE FORECAST IS FOR RISING TEMPERATURE. ALL CRACKS AND JOINTS UP TO 1-‰ INCHES IN WIDTH SHALL BE SEALED. PRIOR TO APPLICATION OF THE HOT-POURED RUBBERASPHALT MATERIAL, ALL CRACKS AND JOINTS TO BE SEALED SHALL BE ROUTED. ALL CRACKS LESS THAN INCH WIDE SHALL BE ROUTED TO A MINIMUM DEPTH OF ONE INCH. CRACKS THAT ARE BORDERED BY EXCESSIVE "ALLIGATORED" AREAS SHALL NOT BE ROUTED AS THIS MAY POP LOOSE THE SURROUNDING ASPHALT. THESE AREAS SHALL BE BLOWN CLEAN AND SEALED WITHOUT ROUTING. STREETS HAVING A CONCRETE SURFACE SHALL NOT REQUIRE ROUTING OF THE CRACKS PRIOR TO CLEANING AND SEALING. ROUTING OF CRACKS SHALL BE FOLLOWED BY CLEANING OF THE CRACKS WITH FORCED AIR. THE SEALANT MATERIAL SHALL BE APPLIED IMMEDIATELY FOLLOWING THE CLEANING OF THE CRACKS. THE HOT-POURED RUBBER-ASPHALT MATERIAL SHALL BE MELTED AND MIX-AGITATED TO THE PROPER TEMPERATURE, RATE AND TIME AS RECOMMENDED BY THE APPLICABLE MANUFACTURER’S SPECIFICATIONS. THIS SEALANT MATERIAL SHALL BE FORCED INTO THE CRACK OR JOINT UNTIL FULL, LEAVING NO EXCESSIVE SAGS OR VOIDS IN APPLIED MATERIAL ALONG THE CRACK. TO ENSURE FULL DEPTH PENETRATION, THE SEALANT SHALL BE "SQUEEGEED" ALONG THE CRACK WITH A "V" SHAPED SQUEEGEE, TO PROVIDE A "BAND AID" TYPE EFFECT APPROXIMATELY 2 INCHES WIDE FLUSH WITH THE PAVEMENT SURFACE WITH THE EDGES FEATHERED OUT. IF NECESSARY, A RESIDUAL AMOUNT OF SEALANT MATERIAL SHALL BE APPLIED TO FILL ANY EXCESSIVE SAGS OR VOIDS AFTER THE INITIAL APPLICATION. A COVER CONSISTING OF DRY SAND APPROVED BY THE ENGINEER SHALL BE APPLIED IMMEDIATELY TO THE HOT-POURED RUBBER-ASPHALT SEALANT TO MINIMIZE TRACKING BY VEHICULAR TRAFFIC. CONTRACTOR SHALL SUBMIT A CONSTRUCTION SCHEDULE AND SEQUENCE OF STREETS TO BE CRACK SEALED AT LEAST SEVEN (7) DAYS PRIOR TO THE START OF ANY WORK. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR PAVEMENT CRACK SEALING DATE: MAY 2011 ...\PVT\PVT-20 (Crack Seal).dgn PVT-21 R.O.W. SIDEWALK EXISTING PCC DRIVEWAY 6" FROM EDGE (TYP.) PAVEMENT TO REMAIN DRIVEWAY APRON 3/4" PREFORMED (SAWCUT PAVEMENT PRIOR EXPANSION JOINT TO REMOVAL) PINNED JOINT SEE NOTE #1 CURB & GUTTER NEW PCC DRIVEWAY APRON PER STD. DETAIL PVT-10 NOTES: 1. AT LOCATIONS WHERE ONLY A PORTION OF DRIVEWAY APRON IS TO BE REMOVED, NEW DRIVEWAY PAVEMENT SHALL BE CONCRETE AND SHALL BE PINNED TO THE EXISTING DRIVEWAY APRON WITH #4 REBAR A MINIMUM OF 6" INTO THE EXISTING SLAB. AFTER INSTALLATION, REBAR SHALL PROTRUDE FROM EXISTING DRIVEWAY PAVEMENT A MINIMUM OF 6". SIX (6) REBAR SHALL BE EVENLY SPACED IN EACH DRIVEWAY, STARTING 6" FROM EITHER DRIVEWAY EDGE. 2. FORMBOARD REQUIREMENTS: MINIMUM 2" X 6". 3. WELDED WIRE FABRIC (6"X6") OR WIRE MESH SHALL BE INSTALLED IN NEW DRIVEWAY PAVEMENT AT 2" ABOVE BOTTOM SLAB PER STD. DETAIL PVT-10. 4. PREFORMED EXPANSION JOINTS (3/4" THICK) SHALL BE CONSTRUCTED AT LOCATIONS WHERE NEW DRIVEWAY PAVEMENT ABUTS CURB AND GUTTER. 5. ALL AGGREGATE SUBBASE SHALL BE MECHANICALLY COMPACTED. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR TYPICAL DRIVEWAY PINNING DATE: AUGUST 2011 ...\PVT-21 (Driveway Pinning).dgn STM-1 EXCAVATED MATERIALS, IDOT CA-7 COMPACTED TO 85% 5’-6" MIN. COVER UNDER OR WITHIN MODIFIED PROCTOR 5 FEET MAXIMUM DENSITY, HORIZONTALLY OF EXCEPT WHERE CA-7 PAVEMENT, IS REQUIRED SIDEWALK, CURB & GUTTER OR DRIVEWAYS, OR STORM SEWER SHALL BE WHERE INDICATED REINFORCED CONCRETE ON PLANS PIPE, COMPLYING WITH ASTM C76, CLASS IV, WITH RUBBER RING GASKET JOINTS MEETING ASTM C443. WHERE ELLIPTICAL PIPE IS USED, IT SHALL COMPLY WITH ASTM C507. 4" IDOT CA-7 BEDDING AND HAUNCHING NO SCALE NOTES: 1. STORM SEWER SHALL BE TELEVISED FOLLOWING COMED AND NICOR UNDERGROUND UTILITIES AND PRIOR TO THE ISSUANCE OF THE FIRST CERTIFICATE OF FINAL OCCUPANCY. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR STORM SEWER INSTALLATION DATE: JUNE 2007 ...\stm-1 (storm sewer installation).dgn STM-2 STEPS SHALL BE COPOLYMER DRAINAGE FABRIC 18" WIDE POLYPROPYLENE PLASTIC WITH A 2’-0" MIRAFI 140S OR 8" 1 CONTINUOUS 2-INCH STEEL REINFORCEMENT AS MANUFACTURED BY APPROVED EQUAL. * M.A. INDUSTRIES, INC., OR APPROVED EQUAL 6" TOPSOIL & SOD. (TYP.) 16" 5" (MIN.) WASHED STONE PAVEMENT OR 6" 2’-0" WEEP HOLES 12" 12" 14" MORTAR WEEP HOLES LOWER THAN 6" BELOW FRAME * CONCRETE SECTIONS AND SECTION BOTTOM PER ASTM C478 4’ FOR SEWER 24" & UNDER, 5’ FOR SEWER 27" 5" TO 36" OR AS INDICATED ON PLANS FABRIC 5" A A 60 + R-2"– BENCH FOR ALL CLASS SI MANHOLES FLOW CONCRETE 1 1 1" DIA. WEEP HOLES (6 EACH) AT 60 TYPICAL * PRECAST CONCRETE PLAN 4" CA-7 BEDDING *NOTE: FOR STORM SEWER ONLY 6" BASE (TYP.) NO SCALE NOTE: 1. MANHOLE BARREL JOINTS SHALL BE TONGUE AND GROOVE TYPE WITH TWO ROWS OF EXTRUDIBLE PREFORMED PLASTIC GASKET MATERIAL (BUTYL ROPE). 2. INTERIOR JOINTS SHALL BE "BUTTERED" WITH NON-SHRINK GROUT. 3. STORM MANHOLES SHALL HAVE A WALL THICKNESS OF 6" FOR 5’ DIAMETER STRUCTURES AND 7" FOR 6’ DIAMETER STRUCTURES 4. SEE CASTING INSTALLATION AND ADJUSTING DETAIL FOR CASTING REQUIREMENTS. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR STORM MANHOLE TYPE A DATE: JUNE 2007 ...\stm-2 (storm manhole type a).dgn STM-3 DRAINAGE FABRIC 18" WIDE MIRAFI 140S ROTATE CB TOP SECT. AS NECESSARY TO OR APPROVED EQUAL. ACHIEVE OPTIMAL CASTING ALIGNMENT POLYPROPYLENE PLASTIC WASHED STONE 6" WITH A CONTINUOUS 1/2 PAVEMENT OR TOPSOIL & SOD. 6" STEPS SHALL BE COPOLYMER WEEP -INCH STEEL REINFORCEMENT 2’-0" HOLES AS MANUFACTURED BY M.A. 12" 12" INDUSTRIES, INC., OR APPROVED EQUAL MORTAR WEEP HOLES LOWER THAN 6" BELOW FRAME FABRIC A A TWO ROWS EXTRUDIBLE PREFORMED PLASTIC + GASKET (TYPICAL ALL 60 16" (TYP) 8" 2’-6" TO 3’-0" SECTION JOINTS) 1" DIA. WEEP HOLES (6 EACH) R 2" AT 60 TYPICAL PLAN NOTES: 1. SEE CASTING INSTALLATION AND ADJUSTMENT DETAIL FOR CASTING REQUIREMENTS. 2. INTERIOR JOINTS SHALL BE "BUTTERED" WITH NON-SHRINK GROUT. 3. STRUCTURE SHALL COMPLY WITH ASTM C478. UNLESS OTHERWISE 6" SPECIFIED ON PLANS NO SCALE T 4. T = STRUCTURE INSIDE DIAMETER +1" (5" MINIMUM) 4" CA-7 BEDDING 4’-0" 2’-6" T VILLAGE OF SHOREWOOD STANDARD DETAIL FOR CATCH BASIN TYPE A DATE: JUNE 2007 ...\stm-3 (catch basin type a).dgn 2’-0" STM-4 DRAINAGE FABRIC 18" WIDE MIRAFI 140S OR APPROVED EQUAL. MAX. WASHED STONE 6" PAVEMENT OR TOPSOIL & SOD. 6" 8" 6" PRECAST ADJUSTING RINGS (2 MAX.) WEEP HOLES TOP OF MASONRY 12" 12" MORTAR WEEP HOLES LOWER SECTION THAN 6" BELOW FRAME VARIABLE (46" MINIMUM) FABRIC A A 60 + 1" DIA. WEEP HOLES (6 EACH) OUTLET AT 60 TYPICAL PLAN 2’-0" T 1. FRAMES AND LIDS TO BE AS SHOWN IN GENERAL NOTES. 2. CATCH BASINS TO BE OF PRECAST REINFORCED CONCRETE CONSTRUCTION ONLY. 3. FOR ADJUSTMENTS, USE ONLY PRECAST CONCRETE ADJUSTING RINGS, MAXIMUM OF 8" TOTAL HEIGHT. 4. ADJUSTING RINGS AND FRAMES TO BE JOINED WITH MORTAR. 5. FOR RIM AND PIPE INVERT ELEVATIONS, REFER TO PLANS. 6. T = STRUCTURE INSIDE DIAMETER +1" (MINIMUM 5"). 4" T 15" SUMP NOTES: VILLAGE OF SHOREWOOD 4" CA-7 BEDDING STANDARD DETAIL FOR CATCH BASIN TYPE C NO SCALE DATE: JUNE 2007 ...\stm-4 (catch basin type c).dgn STM-5 5" MIN. 5" MIN. 2’-0" DIA. R=2" CAST-IN-PLACE CONCRETE FILLET SLOPE TO DRAIN PRECAST CONCRETE BOTTOM 4" CA-7 BEDDING NO SCALE NOTES: 1. SEE CASTING INSTALLATION AND ADJUSTMENT DETAIL FOR CASTING REQUIREMENTS. 2. INTERIOR JOINTS SHALL BE "BUTTERED" WITH NON-SHRINK GROUT. 3. STRUCTURE SHALL COMPLY WITH ASTM C478. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR INLET DATE: JUNE 2007 ...\STM\stm-5 (inlet).dgn STM-6 FOR SMOOTH FACED ADJUSTING RING TWO ROWS OF EXTRUDIBLE PRECAST ADJUSTING PREFORMED PLASTIC RINGS (SEE NOTE 1) GASKET EACH JOINT-OVERLAY ENDS TO GRADE SHOWN ON OF GASKET. ONE ROW CASTING ONLY REQUIRED ON PLANS – ONE ROW 0.5 OF STORM STRUCTURES FOR GROOVED AND WATER VALVES ADJUSTING RINGS EXTRUDIBLE PREFORMED PLASTIC 2" MIN GASKET 12"MAX PER GROOVE FOR GROOVED ADJUSTING RINGS. TOP BUTT ENDS SECTION TYPE A MH CATCH BASIN INLET TOP SECTION VALVE VAULT NO SCALE NOTES: 1. THERE SHALL BE A MAXIMUM OF 2 ADJUSTING RINGS WITH A MAXIMUM TOTAL HEIGHT OF 12". 2. ALL STRUCTURES IN CURB AND GUTTER OR PAVED AREAS SHALL USE PREFORMED RUBBER ADJUSTING RINGS. 3. IF THE CASTING MUST BE INSTALLED ON A SLOPE, PREFORMED RUBBER TAPERED RINGS MAY BE USED. 4. ADJUSTING RINGS 2" OR LESS IN THICKNESS SHALL BE PREFORMED RUBBER. 5. THE FOLLOWING CASTING, OR APPROVED EQUAL, SHALL BE UTILIZED AS INDICATED: A. SANITARY MANHOLES: EAST JORDAN IRON WORKS #1050, EX HD WATERTIGHT LID WITH CONCEALED PICKHOLE, O-RING GASKETS, AND "SHOREWOOD" AND "SANITARY" CAST IN LID. B. WATER VALVE VAULTS: EAST JORDAN IRON WORKS #1050, EX HD WATERIGHT LID WITH CONCEALED PICKHOLE, O-RING GASKETS, AND "SHOREWOOD" AND "WATER" CAST IN LID. C. STORM MANHOLES: EAST JORDAN IRON WORKS #1050, EX HD LID WITH CONCEALED PICKHOLE, AND "SHOREWOOD" AND "STORM" CAST IN LID, FOR LIDS INDICATED AS "SOLID" ON PLANS. FOR LIDS INDICATED AS "OPEN" ON PLANS, USE THE SAME CASTING, BUT WITH A TYPE M1 RADIAL FLAT GRATE. D. DRAINAGE STRUCTURES IN AREAS WITH UNPAVED SURFACES: EAST JORDAN IRON WORKS 6527. E. DRAINAGE STRUCTURES IN MOUNTABLE CURB AND GUTTER: EAST JORDAN IRON WORKS #7171 WITH TYPE M1 GRATE. F. DRAINAGE STRUCTURES IN BARRIER CURB AND GUTTER: EAST JORDAN IRON WORKS #7210 WITH TYPE M2 GRATE. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR CASTING INSTALLATION AND ADJUSTING DATE: JUNE 2007 ...\stm-6 (casting install & adjust).dgn STM-7 FINISH GRADE EXISTING DRAINAGE STRUCTURE WITH CASTING 6" MIN. A NON-SHRINK MORTAR COLLAR PROPOSED PERFORATED DRAIN TILE A CONNECTION HOLE SHALL BE CORE DRILLED. DRAIN TILE PIPE SHALL BE 4" DIA. SCHEDULE 40 P.V.C. TOPSOIL 6" MIN. 6" MIN. 6"MIN. 3/4" WASHED AGG. MIN. 6" AROUND PIPE. PERFORATIONS (DRAIN TILE ONLY) NON-WOVEN GEOTEXTILE 4" DIAMETER DRAIN TILE FABRIC OR SUMP PUMP PIPE SECTION A-A VILLAGE OF SHOREWOOD NOTES: 1. SEE DETAIL STM-8 FOR RESIDENTIAL SUMP DISHARGE SERVICE LINE. STANDARD DETAIL FOR SUBSURFACE DRAIN TILE & SUMP PUMP CONNECTION DATE: JUNE 2007 ...\STM-7 (Drain Tile & Sump Pump Connection).dgn STM-8 4" SERVICE LINE (TYP.) TYPICAL TRUNK LINE (PLAN VIEW) NO SCALE W/CONNECTIONS ONLY (TYP.) CLEANOUT STORM STRUCTURE 6" SUMP PUMP TRUNK SEWER 4" SERVICE LINE (TYP.) REMOVABLE WATER TIGHT PLUG 45 BENDS ONLY, 90 BENDS 3’-6" TYPICAL TRUNK LINE (PROFILE VIEW) LINE PUBLIC WALK 30" NO SCALE MINIMUM PROPERTY ARE NOT PERMITTED GRANULAR FILL FINISH CA ED LO TO HOUSE TION SEE SAN-X FOR CONNECTION DETAIL ELEVATION NO SCALE NOTES: 1. SUMP PUMP CONNECTION LINES SHALL BE POLYVINYL CHLORIDE (PVC) SDR 35 CONFORMING TO ASTM D-3034, SIZE AS INDICATED ON THE PLANS. 2. TRUNK LINES SHALL BE INSTALLED A MINIMUM OF THIRTY (30) INCHES BELOW THE TOP OF CURB AND FOLLOW THE CURB LINE FOR GRADE, AND SHALL BE LOCATED 2 FEET BEHIND THE FRONT PROPERTY LINE. 3. 10 GAUGE UNDERGROUND FEEDER TRACER WIRE SHALL BE INSTALLED IMMEDIATELY ABOVE THE TRUNK LINES AND SHALL TERMINATE AT THE CLEANOUTS OR STUBS. TRACER WIRE SHALL BE STRAPPED TO ALL STUBS AND CLEANOUTS AND SHALL EXTEND CONTINUOUSLY ALONG ALL PIPES, STUBS, AND CLEANOUTS. ADEQUATE WIRE SHALL BE LEFT IN ALL STRUCTURES TO ALLOW IT TO BE RAISED ABOVE THE FRAME. TRACER WIRE SHALL BE LOOPED BACK TO THE SERVICE STUB AND SHALL BE EXTENDED UP THROUGH THE CLEANOUT TO SURFACE GRADE. SPLICES IN TRACER WIRE SHALL USE A NO. 8 SPLIT BOLT SEALED WITH SELF-VULCANIZING TAPE. 4. UNDERGROUND CONTRACTOR SHALL ROTATE ELBOWS TO INSTALL SERVICE STUBS AS SHOWN IN TEMPORARY LOCATION. 5. HOUSE CONTRACTOR SHALL ROTATE ELBOWS TO INSTALL SERVICES AS SHOWN IN FINISHED LOCATION. 6. ALL CONNECTIONS TO INLETS, CATCH BASINS, OR MANHOLES FOR SERVICE STUBS OF SUMP PUMP MAINLINES SHALL BE CORED AND NOT SAWCUT. VILLAGE OF SHOREWOOD 7. PRIOR TO FINAL ACCEPTANCE OF THE SUMP STANDARD DETAIL PUMP COLLECTION SYSTEM, THE ENTIRE SYSTEM SHALL BE TELEVISED. A COPY OF THE VIDEO TAPE SHALL BE DELIVERED TO THE PUBLIC WORKS DEPT. AND ANY FOR SUMP DISCHARGE SERVICE LINE OBSTRUCTIONS SHALL BE REPAIRED. DATE: JUNE 2007 ...\STM-8 (Sump Discharge Service Line).dgn 72 " D IA . STM-9 4" OR 6" THICK PRECAST REINFORCED PCC WEIR WALL. A WATERTIGHT SEAL SHALL BE PROVIDED PLAN VIEW AT CONNECTION BETWEEN WEIR WALL AND STRUCTURE WALLS AND PROPOSED RIM ELEVATION BASE. 16" O.C. PRECAST CONCRETE (5" MIN. THICKNESS) OVERFLOW WEIR 72" DIA. C.I. MANHOLE TOP OF STEPS WALL = 2 YR HWL (COATED) 2 YR. RESTRICTOR CAST IN WEIR WALL (SIZE & ELEVATION PER PLAN) INLET PIPE OUTLET PIPE SEE VILLAGE DETAIL 100 YR. RESTRICTOR 18" MIN RESTRICTOR VARIES PIPE INVERT AS SHOWN ON PLANS REINFORCED CONCRETE BASE (SIZE AND ELEV. PER PLAN) 6" 8" CA-7 VILLAGE OF SHOREWOOD NOT TO SCALE STANDARD DETAIL FOR DETENTION POND RESTRICTOR STRUCTURE DATE: JUNE 2007 ...\STM-9 (Pond Restrictor 1).dgn STM-10 DRAINAGE STRUCTURE WALL FILL VOID SPACE WITH NON-SHRINK GROUT SPIGOT END OF PVC-SDR 35, ASTM D3034 PUSH-ON JOINT PIPE (ASTM D3212) L* FLOW RESTRICTOR DIAMETER AS INDICATED ON PLANS RESTRICTOR INVERT AS INDICATED ON PLANS OUTLET PIPE NO SCALE * L = 2.5 X DIAMETER VILLAGE OF SHOREWOOD STANDARD DETAIL FOR PIPE RESTRICTOR DATE: JUNE 2007 ...\STM-10 (Pond Restrictor 2).dgn SAN-1 EXCAVATED MATERIALS, COMPACTED TO 85% 6’ MIN. COVER MODIFIED PROCTOR MAXIMUM DENSITY, EXCEPT WHERE CA-7 IS REQUIRED IDOT CA-7 DEPTH UNDER OR DIA. WITHIN 5 FEET 6’ UP TO 15’ HORIZONTALLY OF PAVEMENT, PVC, DR 18 ASTM 2241 AWWA C900 4" - 12" SIDEWALK, CURB & GUTTER OR PVC, SDR 26 PVC, DR 18 ASTM 2241 AWWA C905 PVC, DR 25 PVC, DR 25 AWWA C905 AWWA C905 14" - 24" DRIVEWAYS, OR WHERE INDICATED ON PLANS 12" 24" - 36" 15’ AND DEEPER PVC, SDR 26 PIPE MATERIAL SHALL BE IN ACCORDANCE WITH CHART PROVIDED BELOW. IDOT CA-7 4" BEDDING, HAUNCHING AND INITIAL BACKFILL NOTES: NO SCALE 1. JOINTS FOR GRAVITY SANITARY SEWER SHALL USE PUSH ON BELL AND SPIGOT TYPE WITH RUBBER RING GASKETS CONFORMING TO ASTM D3034 FOR SDR 26 APPLICATIONS AND ASTM D3034 FOR AWWA C900 AND C905 APPLICATIONS. 2. GRAVITY SANITARY SEWER FITTINGS SHALL COMPLY WITH ASTM D2241 SDR26, AWWA C900 DR 18, OR AWWA DR 25 DEPENDANT UPON DEPTH. THE FITTINGS SHALL BE MADE WITH MANUFACTURER’S STANDARD PIPE BELLS AND GASKETS. GRAVITY SEWER RISERS AND SERVICE PIPE AND FITTINGS SHALL COMPLY WITH ASTM D2241 SDR 26, AWWA C900, OR AWWA C905 DEPENDANT UPON DEPTH.. 3. WHERE INDICATED ON THE PLANS, SANITARY SEWER PRESSURE PIPE SHALL COMPLY WITH ASTM D2241 FOR 160 PSI PRESSURE RATED PIPE SDR 26, MADE OF TYPE 1, GRADE 1 POLYVINYL CHLORIDE CONFORMING TO ASTM D1784. JOINTS SHALL USE PUSH-ON BELL AND SPIGOT TYPE WITH RUBBER RING SEAL GASKETS CONFORMING TO ASTM D3139. 4. PRESSURE SANITARY SEWER FITTINGS SHALL BE FACTORY FABRICATED WITH ATTACHED MAIN LINE COUPLING, WITH SAME RATING AS PIPE. PRESSURE SEWER RISERS AND SERVICE PIPE AND FITTINGS SHALL COMPLY WITH ASTM D2241, 160 PSI PRESSURE RATED, SDR 26 PIPE. SEPARATE NOTIFICATION SHALL BE PROVIDED TO PUBLIC WORKS DEPARTMENT PRIOR TO INSTALLING PRESSURE SANITARY SEWERS. 5. ALL SANITARY SEWERS SHALL BE PRESSURE TESTED IN ACCORDANCE WITH ARTICLE 31-1.11B(3) OF THE STANDARD SPECIFICATIONS FOR SEWER & WATER CONSTRUCTION IN ILLINOIS, FIFTH EDITION; AND DEFLECTION TESTED IN ACCORDANCE WITH ARTICLE 31-1.11B(4) OF THE STANDARD SPECIFICATIONS FOR SEWER & WATER CONSTRUCTION IN ILLINOIS, FIFTH EDITION. DEFLECTION TESTING SHALL BE DONE NO SOONER THAN 30 DAYS AFTER THE PIPE HAS BEEN BACKFILLED. NO SOONER THAN 30 DAYS AFTER SEWERS HAVE BEEN INSTALLED, THEY SHALL BE INSPECTED BY CLOSED CIRCUIT COLOR TELEVISION TO DETERMINE IF ANY PIPE INSTALLATION DEFECTS HAVE OCCURRED, AND TO DETERMINE THE LOCATION OF SERVICES. ONE COPY OF THE VIDEOTAPE AND WRITTEN INSPECTION REPORT SHALL BE FURNISHED TO THE VILLAGE. 6. SEWER PLUGS SHALL BE INSTALLED AT DOWNSTREAM ENDS OF ALL NEW SEWERS AND LEFT IN PLACE UNTIL VILLAGE ACCEPTS SEWERS. SEWER PLUGS SHALL BE INSTALLED AT UPSTREAM ENDS OF NEW SEWERS AT THE END OF EACH DAY’S WORK. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR SANITARY SEWER INSTALLATION DATE: JUNE 2007 ...\san-1 (sanitary sewer installation).dgn SAN-2 48" Inside M.H. Dia. A A 60" < _ 21" >21" 5" 6" Ecc. Cone Sec.(L) 2’-6" 3’-9" MANHOLE DEPTH <12’ _ >12’ Pipe Dia. Wall Thickness 8" t 10" TOP OF CASTING PLAN SEE SAN-3 12" MAX. PRECAST CONC. ADJUSTING RINGS (2 RINGS MAX. NO MORE THAN ONE 2" ADJUSTING RING SHALL BE USED) 8" L ECCENTRIC CONE SECTION 24" DIA. DEPTH IN PAVED AREAS, USE CA-6 GRANULAR TRENCH BACKFILL AROUND MANHOLE TO 16" O.C. MAX. STEPS CONC. SECTIONS VARIABLE PRECAST REINFORCED SUBGRADE ELEVATION RUBBER BOOT POURED CONCRETE FILLET 2% SLOPE (TYP.) PROVIDE CONCRETE FILLET FOR ALL SANITARY MANHOLE INVERTS 1/2 PIPE DIA. t 6" SECTION A-A PRECAST REINFORCED CONCRETE MANHOLE BOTTOM WITH INTEGRAL SIDEWALL CA-7 AGGREGATE NOTE: 1. SANITARY MANHOLES SHALL HAVE WATERSTOP GASKETS CAST TO STRUCTURES AT ALL PIPE PENETRATIONS. (SEE MANHOLE PIPE CONNECTION DETAIL) 2. SANITARY MANHOLES SHALL HAVE CRETEX INTERNAL CHIMNEY ALS AND PARSONS RAINSTOPPER INSERTS. 3. SANITARY MANHOLES SHALL HAVE INTEGRAL BASES. 4. MACWRAP EXTERNAL JOINT SEALING BANDS IN ACCORDANCE TH ASTM C-877, OR APPROVED EQUIVALENT, MUST BE PROVIDED AT NITARY MANHOLE JOINTS. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR 5. INTERIOR JOINTS SHALL BE "BUTTERED" WITH NON-SHRINK GROUT. 6. STORM MANHOLES SHALL HAVE A WALL THICKNESS OF 6" FOR 5’ SANITARY SEWER MANHOLE AMETER STRUCTURES AND 7" FOR 6’ DIAMETER STRUCTURES 7. SANITARY MANHOLES SHALL PASS VACUUM-TESTING PER ASTM C-1244. 8. SEE CASTING INSTALLATION AND ADJUSTING DETAIL FOR CASTING REQUIREMENTS. DATE: JUNE 2007 ...\SAN-2 (Sanitary Sewer Manhole).dgn SAN-3 5/8" MIN. FOR D.I. 3/4" MIN. FOR C.I. VILLAGE D OF D SHOREWOOD SANITARY 2" RAISED LETTERS "VILLAGE OF SHOREWOOD" SEAL TITE LID SANITARY STAMPED IN LID SEAL TITE CONCEALED PICK HOLE 2-1/4" 2-1/2" 1-3/8" 1-3/8" CAST CLOSED LID (SEAL TITE CONCEALED PICK HOLE) 1) DUCTILE IRON SHALL BE GRADE 60-40-18 AND SHALL BE TESTED IN ACCORDANCE WITH FEDERAL SPECIFICATIONS. 2) ALL FRAMES AND COVERS SHALL HAVE MACHINED HORIZONTAL AND VERTICAL BEARING SURFACES. PICK HOLES SHALL NOT CREATE OPENINGS IN THE COVER. 3) THE MANHOLE COVERS SHALL HAVE RAISED LETTERS AS SHOWN. 4) MINIMUM WEIGHTS FOR CASTINGS AS SHOWN. 5) DIMENSIONS FOR CASTINGS ARE COMPARABLE TO EAST JORDAN 1022-3 OR NEENAH R-1772-CVH. 6) WATERPROOF, BOLTDOWN FRAME AND COVER SHALL BE USED AS NOTED ON THE PLANS. NEENAH R-1916-F1 OR EAST JORDAN IRON WORKS 1040-ZPT (OR APPROVED EQUAL). VILLAGE OF SHOREWOOD STANDARD DETAIL FOR SANITARY MANHOLE FRAME & COVER DATE: JUNE 2007 ...\SAN-3 (Sanitary Sewer Manhole Frame & Cover).dgn SAN-4 FLEXIBLE BOOTS MEETING ASTM C923 CLAMP-ON TYPE (CAST-IN BOOT SHOWN; PRESSED-IN BOOT ALSO PERMITTED) FLEXIBLE BOOTS MEETING ASTM C923 "A-LOCK" TYPE CLAMP SECURELY IN ACCORDANCE WITH BOOT MFR’S INSTRUCTIONS. INVERT CHANNEL USE A MINIMUM OF 2 STAINLESS CONCRETE STEEL CLAMPS. INSTALL PIPE IN ACCORDANCE WITH BOOT MFR’S INST. OR WHEN PLACING FIELD-POURED INVERT CHANNELS, PACK ANNULAR SPACES WITH EXTRUDIBLE PREFORMED PLASTIC GASKET MATERIAL TO PREVENT INVERT CONCRETE FROM ENTERING SPACE BETWEEN PIPE AND FLEXIBLE BOOT VILLAGE OF SHOREWOOD STANDARD DETAIL FOR SANITARY MANHOLE PIPE CONNECTION DATE: JUNE 2007 ...\san-4 (sanitary pipe connection).dgn SAN-5 FLOW 8" MIN. CLASS SI CONC. ENCASEMENT TO TOP OF BEND FOR INCOMING PIPE SMALLER THAN 12", USE VERTICAL PIPE OF SAME DIAMETER. FOR INCOMING PIPE 12" TO 18" USE 12" VERTICAL PIPE. SEE PLANS FOR PIPES LARGER THAN 18". ALL PIPING SHOWN SHALL BE DUCTILE IRON CLASS 52 M.J. NO SCALE PIPE AND MEGALUG FITTINGS VILLAGE OF SHOREWOOD STANDARD DETAIL FOR DROP CONNECTION DATE: JUNE 2007 ...\san-5 (drop connection).dgn SAN-6 PRIVATE DEVELOPMENT (MULTI-TENANT) NEW SEWER MANHOLE CLEANOUT (TYP.) SEWER SERVICE ROW NEW SEWER MANHOLE EXISTING SEWER FOR SERVICE CONNECTOR EOP PUBLIC ROADWAY ~ PUBLIC ROADWAY VILLAGE OF SHOREWOOD STANDARD DETAIL FOR NON-RESIDENTIAL SEWER SERVICE DATE: JUNE 2007 ...\SAN-6 (Non-Residential Sewer Service).dgn SAN-7 2’-0" PROPERTY LINE 4"X4" WOOD MARKER POST, 6" PVC PAINTED GREEN, 3’-0" ABOVE FINISHED GRADE, WYE BRANCH TO 2’-0" BELOW FINISHED GRADE 1% MIN SLOPE 10% MAX SLOPE MANUFACTURER’S PLUG 30 OR 45 ELBOW 6" SERVICE RISER WYE BRANCH f VARIES NOTES: 1. IF f < 45 USE PVC PUSH-ON JOINT WYE, P.V.C. ELBOW, P.V.C. RISER PIPE & P.V.C. TOP ELBOW. 2. IF f > 45 USE DUCTILE IRON M.J. TEE WITH P.V.C./DUCTILE TRANSITION GASKET, DUCTILE IRON RISER PIPE AND DUCTILE IRON TOP ELBOW. 3. ALL PVC PIPE AND FITTINGS SHALL BE ASTM D3034, SDR 26, WITH ELASTOMERIC GASKET TYPE JOINTS COMPLYING WITH ASTM F477 AND ASTM D3212, OR PRESSURE-RATED PIPE AND FITTINGS PER ASTM D2241 AS NOTED ON THE PLANS. 4. A MINIMUM DISTANCE OF 3 FT IS REQUIRED BETWEEN 45 BENDS. 5. TRENCH BACKFILL SHALL BE INSTALLED PER SANITARY SEWER INSTALLATION DETAIL. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR RESIDENTIAL SEWER SERVICE DATE: JUNE 2007 ...\san-7 (residential sewer service).dgn 5’-6" MIN. COVER WTR-1 IDOT CA-7 UNDER EXCAVATED MATERIALS, OR WITHIN 5 FEET COMPACTED TO 85% MODIFIED PROCTOR HORIZONTALLY OF MAXIMUM DENSITY, PAVEMENT, EXCEPT WHERE CA-7 IS SIDEWALK, CURB REQUIRED & GUTTER OR DRIVEWAYS, OR WHERE INDICATED ON PLANS DUCTILE IRON WATER MAIN PER AWWA C151, THICKNESS CLASS 52 PER AWWA C150, WITH PUSH-ON JOINTS PER AWWA C111 WITH SYNTHETIC RUBBER GASKETS, CEMENT 6" LINING PER AWWA C104, AND FITTINGS PER AWWA C110 OR AWWA C153 4" IDOT CA-7 BEDDING, HAUNCHING AND INITIAL BACKFILL NO SCALE NOTES: 1. PRESSURE AND LEAKAGE TESTS AND CHLORINATION SHALL BE COORDINATED WITH VILLAGE UTILITY FOREMAN. 2. MAINS SHALL BE PRESSURE TESTED AT A MINIMUM PRESSURE OF 150 PSI FOR TWO HOUR WITHOUT PRESSURE LOSS OR FURTHER PRESSURE APPLICATION. TEST SHALL BE PERFORMED IN ACCORDANCE WITH AWWA C600 AND AWWA C603. IF MAINS TO BE TESTED INCLUDE CONCRETE THRUST BLOCKING, DO NOT BEGIN TEST UNTIL AT LEAST 5 VILLAGE OF SHOREWOOD DAYS AFTER THE INSTALLATION OF THE THRUST BLOCKING. STANDARD DETAIL FOR 3. AFTER COMPLETING A SATISFACTORY PRESSURE TEST, WATER MAIN INSTALLATION THE WATER MAIN SHALL BE LEAKAGE TESTED FOR 24 HOURS AT SYSTEM PRESSURE, IN ACCORDANCE WITH THE STANDARD SPECIFICATIONS FOR WATER & SEWER MAIN CONSTRUCTION IN ILLINOIS, LATEST EDITION. DATE: JUNE 2007 ...\wtr-1 (watermain installation).dgn WTR-2 UNDISTURBED EARTH TRENCH WALL (TYP.) UNDISTURBED EARTH TRENCH WALL (TYP.) UNDISTURBED EARTH TRENCH WALL (TYP.) NOTES 1. PROVIDE PRECAST OR CAST-IN-PLACE PLANS IDOT CLASS SI CONCRETE THRUST BLOCKS OF ADEQUATE SIZE AND THRUST BEARING SURFACE TO PREVENT MOVEMENT OF PIPELINE UNDER PRESSURE. 2. PLACE THE BASE AND THRUST BEARING SIDES OF THRUST BLOCK DIRECTLY AGAINST UNDISTURBED EARTH. 3. PLACE THRUST BLOCKING SO THE FITTING NO SCALE UNDISTURBED EARTH JOINTS WILL BE ACCESSIBLE FOR REPAIR. 4. ALL FITTINGS SHALL HAVE MECHANICAL JOINTS WITH MEGA-LUG RETAINER GLANDS BY EBAA IRON, AND DURATRON SAC-NUTS ON 50% OF ALL BOLTS. SECTION VILLAGE OF SHOREWOOD STANDARD DETAIL FOR THRUST BLOCK INSTALLATIONS DATE: JUNE 2007 ...\WTR\wtr-2 (thrust block).dgn WTR-3 TOP OF CASTING SEE WTR-5 FINISHED GRADE 2’ PREFORMED NON-HARDENING 2’-8" MASTIC (TYPICAL ALL SECTION JOINT) 4’ UP TO AND INCLUDING 12" 5’-6" MIN. EXTRUDIBLE PREFORMED PLASTIC GASKET WATEROUS C-515 AFC2500 DUCTILE IRON GATE VALVE WITH STAINLESS STEEL HARDWARE FOR VALVES AWWA *C504 (PRESSURE CLASS 150B) BUTTERFLY VALVE FOR 16" AND LARGER PRECAST CONCRETE MANHOLE SECTIONS - ASTM C478 8" RUBBER BOOT (TYP.) SOLID PRECAST INTEGRAL BOTTOM 6" CA-7 6" 6" PRECAST CONC. BLOCK SUPPORT 1) VALVE MUST ALIGN WITH THE CENTER OF VAULT OPENINGS. 2) CONES MUST BE CONCENTRIC WITH VALVES 12" AND SMALLER. 3) BUTTERFLY VALVES AND PRESSURE TAP VALVES REQUIRE ECCENTRIC CONES. 4) WHEN ADJUSTMENTS ARE NECESSARY, THEY SHALL BE PERFORMED WITH A MAXIMUM OF TWO (2) PRECAST CONCRETE RINGS SET IN A BED OF PREFORMED NON-HARDENING MASTIC MATERIAL( CONSEAL CS-102B, OR APPROVED EQUAL) TO A MAXIMUM HEIGHT OF 12". 5) MANHOLE STEPS SHALL BE AT 16" O.C. COPOLYMER POLYPROPYLENE PLASTIC WITH CONTINUOUS 12" STEEL REINFORCEMENT BY M.A. INDUSTRIES, INC. OR APPROVED EQUAL. 6) DURATION SAC-NUTS SHALL BE USED ON 50% OF ALL BOLTS. 7) ALL HARDWARE SHALL BE STAINLESS STEEL. 8) USE 4’-0" DIAMETER FOR WATER MAIN SIZES 8" OR LESS, USE 5’-0" DIAMETER FOR WATER MAIN SIZES 10" THRU 20", USE 6’-0" DIAMETER FOR WATER MAIN SIZES GREATER THAN 20". BUTTERFLY VALVES SHALL: 9) HAVE A CAST IRON BODY, AND BE RUBBER-SEATED, TIGHT-CLOSING TYPE SUITABLE FOR BURIED SERVICE. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR 10) HAVE ANSI CLASS 125 STANDARD FLANGE OR VICTAULIC COUPLING ENDS. 11) HAVE VALVE SHAFT OF EITHER 18-8 OR TYPE 304 STAINLESS STEEL, VALVE VAULT EXTENDED THROUGH VALVE DISC AND BODY INTO OPERATOR. 12) HAVE A FULLY ENCLOSED, SEALED, GREASE-PACKED INTEGRAL GEARED MANUAL OPERATOR WITH A 2-INCH SQUARE OPERATING NUT. DATE: JUNE 2007 ...\WTR\WTR-3 (Valve Vault).dgn WTR-4 NOTES: 1. ECCENTRIC CONE REQUIRED 2. USE 4’-0" DIAMETER FOR WATER MAIN SIZES 8" OR LESS, USE 5’-0" DIAMETER FOR WATER MAIN SIZES 10" THRU 20", USE 6’-0" DIAMETER FOR WATER MAIN SIZES GREATER THAN 20". 3. TAPPING OF WATER MAINS SHALL BE DONE ONLY IN THE PRESENCE OF AN AUTHORIZED VILLAGE REPRESENTATIVE, AND AFTER 48 HOURS PRIOR NOTICE TO THE VILLAGE. 4. DURATION SAC-NUTS SHALL BE USED ON 50% OF ALL BOLTS. TOP OF CASTING AND LID FINISHED GRADE SEE WTR-5 PRECAST CONC. ADJUSTING RINGS (NO MORE THAN 2 RINGS FRAME AND COVER: OR 12" OF ADJUSTMENT) EJIW 1050 EX HD , OR NEENAH R-1712 SEE CASTING ADJUSTMENT DETAIL MANHOLE STEPS @ 16" C. TO C. COPOLYMER 6" POLYPROPYLENE PLASTIC W/ CONTINUOUS 1/2" EXTRUDIBLE PREFORMED 5’-6" MIN. COVER STEEL REINFORCEMENT PLASTIC GASKET MIN. (TYPICAL ALL BY M.A. INDUSTRIES, INC., OR APPROVED SECTION JOINTS) EQUAL WATEROUS C-515 AFC 2500, DUCTILE IRON, WITH STAINLESS STEEL HARDWARE PRECAST CONCRETE MANHOLE SECTIONS: ASTM C478 STAINLESS STEEL TAPPING SLEEVE: SMITH-BLAIR STYLE RUBBER BOOT NO. 662 WATER MAIN EXIST. WATER MIN. CONCRETE THRUST BLOCK 4" 8" MAIN CONCRETE SUPPORT GRANULAR BEDDING MATERIAL: CA-7 PRECAST CONC. OR 6" MIN. CAST-IN-PLACE CONC. BOTTOM EXTRUDIBLE PREFORMED PLASTIC GASKET VILLAGE OF SHOREWOOD STANDARD DETAIL FOR NO SCALE PRESSURE CONNECTION VALVE VAULT DATE: JUNE 2007 ...\wtr-4 (pressure connection valve vault).dgn WTR-5 5/8" MIN. FOR D.I. 3/4" MIN. FOR C.I. 2" RAISED LETTERS VILLAGE "VILLAGE OF SHOREWOOD" D OF D SHOREWOOD WATER SEAL TITE LID SEAL TITE CONCEALED PICK HOLE 2-1/4" 2-1/2" MIN. 2-1/2" 1-3/8" 1-3/8" 22-3/4" 1-3/4" 3/4" Min. 5/8" 5/8" 6" DIA. CAST CLOSED LID (SEAL TITE CONCEALED PICK HOLE) 1) DUCTILE IRON SHALL BE GRADE 60-40-18 AND SHALL BE TESTED IN ACCORDANCE WITH FEDERAL SPECIFICATIONS. 2) ALL FRAMES AND COVERS SHALL HAVE MACHINED HORIZONTAL AND VERTICAL BEARING SURFACES. PICK HOLES SHALL NOT CREATE OPENINGS IN THE COVER. 3) THE MANHOLE COVERS SHALL HAVE RAISED LETTERS AS SHOWN. 4) DIMENSIONS FOR CASTINGS ARE COMPARABLE TO EAST JORDAN 1022-3 OR NEENAH R-1772-C. 5) LIDS AND FRAMES TO MEET AASHTO H-20 LOADING SPECIFICATIONS. 6) ALL CASTINGS SHALL BE SHOP PAINTED WITH ASPHALTIC BASE PAINT. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR VALVE VAULT FRAME & COVER DATE: JUNE 2007 ...\WTR-5 (Valve Vault Frame & Cover).dgn WTR-6 EAST JORDAN 5CD250 OR CLOW MEDALLION CAST IRON COVER MARKED "WATER" 18" (MIN.) BREAK FLANGE 26" (MAX.) 5'-6" COVER MUELLER VALVE BOX 10360 STABILIZER COVER W/ PLASTIC 6" AUXILIARY GATE VALVE: AWWA C-509 1 C.Y. (MIN) CA-7 CONCRETE THRUST BLOCKING CONCRETE TYLER "SWIVEL-TEE" BLOCKS MECHANICAL JOINT WITH FIELD-LOK GASKET AND MEGA LUG RESTRAINT MECHANICAL JOINT (FLANGED JOINT NOT PERMITTED) NO SCALE NOTES: 1. ALL BOLTS & NUTS BELOW GRADE ON FIRE HYDRANT SHALL BE STAINLESS STEEL. 2. ALL BOLTS & NUTS ON AUXILIARY VALVE SEAL PLATE AND BONNET SHALL BE STAINLESS STEEL. 3. THRUST BLOCKING SHALL BE CONSTRUCTED SO HYDRANT DRAIN HOLE IS NOT OBSTRUCTED. 4. HYDRANT SHALL BE PAINTED ACE BRAND RUST STOP VILLAGE OF SHOREWOOD STANDARD DETAIL FOR FIRE HYDRANT SAFETY RED. DATE: SEPTEMBER 2014 $FILEABBREV$ WTR-7 HORIZONTAL OFFSET 6" MIN. " 22" 10 " 45 10 WATER MAIN 8’ LINE FIN. GRADE SERVICE BOX: MUELLER H-10300 WITH STATIONARY 5’-0" MIN. PROPERTY PLAN EXTENSION ROD VARIABLE (ONE PIECE OF PIPE - NO SPLICES) WATER MAIN SERVICE PIPE: ASTM B88, 45 PRECAST CONCRETE BLOCK TYPE K, COMPRESSION FITTINGS CORPORATION STOP: CURB STOP: MUELLER, P-25155 MUELLER, H-15013 SECTION NO SCALE NOTES: 1. TRENCH BACKFILL SHALL BE INSTALLED PER WATER MAIN INSTALLATION DETAIL. 2. PLACE AND HAND-TAMP AT LEAST 1/4 CUBIC YARDS OF SAND AROUND CORPORATION STOP. 3. MINIMUM DISTANCE BETWEEN SERVICE TAPS SHALL BE 18 INCHES. 4. MINIMUM RESIDENTIAL SERVICE DIAMETER SHALL BE 1 1/2". 5. SERVICES SHALL NOT BE LOCATED WITHIN DRIVEWAYS. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR WATER SERVICE 6. ALL SERVICES TO BE ABANDONED OR RELOCATED SHALL BE CLOSED AT THE CORP STOP AND RE-TAPPED. DATE: JUNE 2007 7. SEE DETAIL MSC-3 FOR SERVICE LATERAL LOCATIONS. ...\WTR\wtr-7 (water service).dgn WTR-8 OPERATING HANDLE (OFF-ON) BRASS WATER NOZZLE (NON-THREADED) PUMP CONNECTOR RETAINING WASHER (COPPER TUBING) 22" MAXIMUM 16" MINIMUM LOCK PIN REMOVABLE LOCKABLE UPPER BRASS PET COCK HOUSING (MOLDED) PVC NIPPLE STAINLESS STEEL ANCHOR BOLTS AND NUTS WELDED STOP LOCKS BOTTOM MOLDED HOUSING FINISHED GRADE STEEL ANCHOR POST SERVICE BOX: MUELLER H-10300, OR VALVE STEM McDONALD 5614 PVC NIPPLE VARIABLE COPPER TUBING (ONE PIECE OF PIPE) WATER MAIN BRASS ELBOW 3/4" SERVICE PIPE: 45 ASTM 88, TYPE K, BRONZE BALL VALVE FLARED FITTINGS W/ CHROME PLATED BALL FLARED CORPORATION STOP WITH PLUG FLARED CURB STOP WITH VALVE: MUELLER, BALL VALVE AND MINNEAPOLIS PATTERN: FORD OR McDONALD MUELLER OR McDONALD PRECAST CONCRETE BLOCK 1) SAMPLING STATION SHALL BE GIL INDUSTRIES MODEL EH101-50 OR APPROVED EQUAL. 2) LOCATION OF SAMPLING STATION SHALL BE DETERMINED DURING FINAL ENGINEERING OF THE PROPOSED DEVELOPMENT. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR 3) CONTRACTOR SHALL HAVE SAMPLING STATION WATER SAMPLING STATION STAKED FOR LOCATION AND ELEVATION AND APPROVED BY THE VILLAGE PRIOR TO INSTALLATION. DATE: JUNE 2007 ...\WTR-8 (Water Sampling Station).dgn ELE-1 TWIN ASSEMBLY SINGLE ASSEMBLY 30" 36" 48" 33" 18’-0" DECORATIVE ARM 18’-0" %% 90 TRAFFIC FLOW d 16’-0" HANDHOLE POSITION INTERNAL SLEEVE PROVIDED POLE SHAFT 32" NOM. 32" NOM. 20" NOM. 20" NOM. ANCHOR RING 1" ABOVE GRADE NOTE: 15" DIA. BOLT CIRCLE ANCHOR RING 1" ABOVE GRADE HAND HOLE 1. LIGHT POLE ASSEMBLY SHALL BE SUN VALLEY DETAIL NO. CS-4092 REV. 9, OR APPROVED EQUAL. 2. DIRECT CONNECTED LIGHT POLES SHALL BE PROVIDED WITH 120V BUTTON-TYPE PHOTOELECTRIC CELL. 3. UPON FINAL ACCEPTANCE OF PUBLIC LIGHTING IMPROVEMENTS BY THE VILLAGE, DEVELOPER/CONTRACTOR SHALL PROVIDE A NON-REFUNDABLE CASH DEPOSIT EQUIVALENT TO 10% OF THE TOTAL CONSTRUCTION COST OF THE LIGHT POLE STANDARDS AND FIXTURES FOR FUTURE VILLAGE LIGHTING MAINTENANCE PURPOSES. 4. SEE SHEET 2 OF 2 FOR SPECIFICATIONS. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR ORNAMENTAL TYPE LIGHT POLE SHEET 1 OF 2 DATE: MARCH 2009 N:\Shorewood\CONSTRUCTION STANDARDS\STANDARD DETAILS\ELE\ele-1 (Ornamental Light Pole).dgn ELE-1 SPECIFICATIONS: LUMINAIRE: HOUSING AND DOOR FRAME-HEAVY WALL CAST ALUMINUM CONSTRUCTION WITH REMOVABLE BALLAST TRAY FOR EASY BALLAST ACCESS. REFLECTOR-HEAVY WALL ALUMINUM CONSTRUCTION. OPTICS: SEGMENTED REFLECTOR AND CLEAR ACRYLIC DIFFUSER. TWIN ASSEMBLY-TYPE III (ASYMMETRIC) LIGHT DISTRIBUTION. SINGLE ASSEMBLY-TYPE III (ASYMMETRIC) LIGHT DISTRIBUTION. LAMP HOLDER: MOGUL BASE, PORCELAIN. LAMP: 150 W. H.P.S.- PUBLIC STREET 250 W. H.P.S. - COMMERCIAL APPLICATION BALLAST: H.P.F./C.W.A. AUTOTRANSFORMER,-20^ STARTING TEMPERATURE. (MULTI-TAP VOLTAGE, WIRED FOR 120V.) ARM: DURABLE CORROSION RESISTANT, CAST, AND EXTRUDED ALUMINUM CONSTRUCTION. SHAFT: 16 FLUTES TAPERED ALUMINUM SHAFT (.188 WALL THICK.) HAS 7" BUTT TAPERING TO 4.5" TOP. SHAFT PROVIDED WITH INTERNAL REINFORCING SLEEVE FOR GREATER STRUCTURAL SUPPORT. SLEEVE AND SHAFT WELDED TO BASE. BASE: ONE PIECE CORROSION RESISTANT, DURABLE CAST ALUMINUM CONSTRUCTION. MINIMUM .210 WALL THICKNESS, BASE CONSISTS OF A SMOOTH, TAPERED BOTTOM SECTION, AND A HIGHLY DETAILED, DECORATIVE FLUTED SECTION, A DECORATIVE CAST ALUMINUM COLLAR AND FLUTED HAND HOLE COVER CONTOURED TO BASE DESIGN. HAND HOLE COVER SUPPLIED WITH TAMPER RESISITANT HARDWARE. GROUNDING LUG PROVIDED INSIDE BASE OPPOSITE HAND HOLE. ANCHORAGE: (4) 1"X36" FULLY GALVANIZED ANCHOR BOLTS. EACH BOLT SUPPLIED WITH TWO NUTS AND TWO WASHERS. FINISH: ELECTROSTATICALLY APPLIED BAKED ON TEXTURED ACRYLIC ENAMEL-HIGH GLOSS (COLOR: BLACK). NOTE: 1. HAND HOLE COVER TO READ "VILLAGE OF SHOREWOOD". 2. POLE ASSEMBLY RATED FOR 90 M.P.H. SUSTAINED WIND LOADS PLUS 1.3 WIND GUST. 3. OPTIONS: - SPEAKER BRACKET - BANNER ARMS (ROTATABLE OR FIXED) SPECIFY. - FLAG HOLDER (ROTATABLE OR FIXED) SPECIFY. - GFI VILLAGE OF SHOREWOOD STANDARD DETAIL FOR ORNAMENTAL TYPE LIGHT POLE SHEET 2 OF 2 DATE: MARCH 2009 N:\Shorewood\CONSTRUCTION STANDARDS\STANDARD DETAILS\ELE\ele-1 (Ornamental Light Pole).dgn ELE-1A 26 1/2 " 22" 42" 31" 10’-11 1/2 " 10’-0" DECORATIVE ARM d %% 90 TRAFFIC FLOW HANDHOLE POSITION POLE SHAFT 25" NOM. 17" NOM. ANCHOR RING 1" ABOVE GRADE HAND HOLE 12" DIA. BOLT CIRCLE NOTE: 1. LIGHT POLE ASSEMBLY SHALL BE SUN VALLEY DETAIL NO. CS-5198 REV. 1, OR APPROVED EQUAL. 2. DIRECT CONNECTED LIGHT POLES SHALL BE PROVIDED WITH 120V BUTTON-TYPE PHOTOELECTRIC CELL. 3. UPON FINAL ACCEPTANCE OF PUBLIC LIGHTING IMPROVEMENTS BY THE VILLAGE, DEVELOPER/CONTRACTOR SHALL PROVIDE A NON-REFUNDABLE CASH DEPOSIT EQUIVALENT TO 10% OF THE TOTAL CONSTRUCTION COST OF THE LIGHT POLE STANDARDS AND FIXTURES FOR FUTURE VILLAGE LIGHTING MAINTENANCE PURPOSES. 4. SEE SHEET 2 OF 2 FOR SPECIFICATIONS. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR PEDESTRIAN SCALE (10’) ORNAMENTAL TYPE LIGHT POLE SHEET 1 OF 2 DATE: MARCH 2009 N:\Shorewood\CONSTRUCTION STANDARDS\STANDARD DETAILS\ELE\ele-1A (Ped Level Ornamental Light Pole).dgn ELE-1A SPECIFICATIONS: FIXTURE: HOUSING - HEAVY WALL CAST ALUMINUM CONSTRUCTION. LUMINAIRE SUPPLIED WITH AN ALUMINUM HOOD, A DECORATIVE GASKETED HINGED CAGE AND A CAST ALUMINUM FITTER. OPTICS: PRECISELY DESIGNED UPPER BOROSILICATE PRISMATIC GLASS REFLECTOR REDIRECTS UPWARD LIGHT DOWNWORD TOWARD THE PRECISELY DESIGNED PRISM STRUCTURE OF THE LOWER BOROSILICATE GLASS REFRACTOR TO PROVIDE A TYPE III (ASYMMETRIC) LIGHT DISTRIBUTION. LAMP HOLDER: MEDIUM BASE PORCELAIN. LAMP: 70 W. H.P.S. BALLAST: H.P.F./C.W.A. AUTOTRANSFORMER,-20^ STARTING TEMPERATURE. (MULTI-TAP VOLTAGE) SHAFT: 4" DIA. EXTRUDED FROM 6063 ALLOY ALUMINUM. HEAT TREATED TO PRODUCE A T6 TEMPER. WALL THICKNESS .188 MINIMUM. DECORATIVE SHAFT HAS EVENLY SPACED HIGHLY DETAILED RAISED VERTICAL FLUTES EXTENDING THE ENTIRE LENGTH OF THE SHAFT. SHAFT IS CIRCUMFERENTIALLY WELDED TO BASE. BASE: ONE PIECE CORROSION RESISTANT, DURABLE CAST ALUMINUM CONSTRUCTION. MINIMUM .210 WALL THICKNESS, BASE CONSISTS OF A SMOOTH, TAPERED BOTTOM SECTION, AND A HIGHLY DETAILED, DECORATIVE FLUTED SECTION, A DECORATIVE CAST ALUMINUM COLLAR AND A FLUTED HAND HOLE COVER CONTOURED TO BASE DESIGN. HAND HOLE COVER SUPPLIED WITH TAMPER RESISITANT HARDWARE. GROUNDING LUG PROVIDED INSIDE BASE OPPOSITE HAND HOLE. ANCHORAGE: (4) 3/4 "X18" FULLY GALVANIZED ANCHOR BOLTS. EACH BOLT SUPPLIED WITH TWO NUTS AND TWO WASHERS. FINISH: POLYESTER POWDER COAT - HIGH GLOSS (COLOR: BLACK) NOTE: 1. HAND HOLE COVER TO READ "VILLAGE OF SHOREWOOD". 2. POLE ASSEMBLY RATED FOR 90 M.P.H. SUSTAINED WIND LOADS PLUS 1.3 WIND GUST. 3. OPTIONS: - SPEAKER BRACKET - BANNER ARMS (ROTATABLE OR FIXED) SPECIFY. - FLAG HOLDER (ROTATABLE OR FIXED) SPECIFY. - GFI VILLAGE OF SHOREWOOD STANDARD DETAIL FOR PEDESTRIAN SCALE (10’) ORNAMENTAL TYPE LIGHT POLE SHEET 2 OF 2 DATE: MARCH 2009 N:\Shorewood\CONSTRUCTION STANDARDS\STANDARD DETAILS\ELE\ele-1A (Ped Level Ornamental Light Pole).dgn ELE-2 23" 33" 10’-0" 25" NOM. 17" NOM. 12" DIA. BOLT CIRCLE ANCHOR RING 1" ABOVE GRADE HAND HOLE NOTE: 1. LIGHT POLE ASSEMBLY SHALL BE SUN VALLEY DETAIL NO. CS-5201 REV. 1, OR APPROVED EQUAL. 2. DIRECT CONNECTED LIGHT POLES SHALL BE PROVIDED WITH 120V BUTTON-TYPE PHOTOELECTRIC CELL. 3. UPON FINAL ACCEPTANCE OF PUBLIC LIGHTING IMPROVEMENTS BY THE VILLAGE, DEVELOPER/CONTRACTOR SHALL PROVIDE A NON-REFUNDABLE CASH DEPOSIT EQUIVALENT TO 10% OF THE TOTAL CONSTRUCTION COST OF THE LIGHT POLE STANDARDS AND FIXTURES FOR FUTURE VILLAGE LIGHTING MAINTENANCE PURPOSES. 4. SEE SHEET 2 OF 2 FOR SPECIFICATIONS. N:\Shorewood\CONSTRUCTION STANDARDS\STANDARD DETAILS\ELE\ele-2 (Ped Symmetrical Ornamental Light Pole).dgn VILLAGE OF SHOREWOOD STANDARD DETAIL FOR PEDESTRIAN SCALE SYMMETRICAL ORNAMENTAL TYPE LIGHT POLE SHEET 1 OF 2 DATE: MARCH 2009 ELE-2 SPECIFICATIONS: LUMINAIRE: DURABLE CORROSION RESISTANT CAST ALUMINUM. HOUSING TOP HINGES FOR EASY RE-LAMPING. LUMINAIRE SUPPLIED WITH CLEAR ACRYLIC DIFFUSER. OPTICS: SEGMENTED HORIZONTAL REFLECTOR COMBINES WITH CLEAR ACRYLIC DIFFUSER TO PRODUCE TYPE III (ASYMMETRIC) LIGHT DISTRIBUTION. LAMP HOLDER: MEDIUM BASE, PORCELAIN. LAMP: 70 W. H.P.S. BALLAST: H.P.F./C.W.A. AUTOTRANSFORMER,-20^ STARTING TEMPERATURE. (MULTI-TAP VOLTAGE, SPECIFY VOLTAGE) SHAFT: 16 FLUTES TAPERED ALUMINUM SHAFT (.188 WALL THICK.) HAS 6" BUTT TAPERING TO 4.6" TOP. SHAFT PROVIDED WITH INTERNAL REINFORCING SLEEVE FOR GREATER STRUCTURAL SUPPORT. SLEEVE AND SHAFT WELDED TO BASE. BASE: ONE PIECE CORROSION RESISTANT, DURABLE CAST ALUMINUM CONSTRUCTION. MINIMUM .210 WALL THICKNESS. BASE CONSISTS OF A SMOOTH, TAPERED BOTTOM SECTION, AND A HIGHLY DETAILED, DECORATIVE FLUTED SECTION, A DECORATIVE CAST ALUMINUM COLLAR AND FLUTED HAND HOLE COVER CONTOURED TO BASE DESIGN. HAND HOLE COVER SUPPLIED WITH TAMPER RESISITANT HARDWARE. GROUNDING LUG PROVIDED INSIDE BASE OPPOSITE HAND HOLE. ANCHORAGE: (4) 3/4 "X24" FULLY GALVANIZED ANCHOR BOLTS. EACH BOLT SUPPLIED WITH TWO NUTS AND TWO WASHERS. FINISH: POLYESTER POWDER COAT - HIGH GLOSS (COLOR: BLACK) NOTE: 1. HAND HOLE COVER TO READ "VILLAGE OF SHOREWOOD". 2. POLE ASSEMBLY RATED FOR 90 M.P.H. SUSTAINED WIND LOADS PLUS 1.3 WIND GUST. 3. OPTIONS: - SPEAKER BRACKET - BANNER ARMS (ROTATABLE OR FIXED) SPECIFY. - FLAG HOLDER (ROTATABLE OR FIXED) SPECIFY. - GFI VILLAGE OF SHOREWOOD STANDARD DETAIL FOR PEDESTRIAN SCALE SYMMETRICAL ORNAMENTAL TYPE LIGHT POLE SHEET 2 OF 2 DATE: MARCH 2009 N:\Shorewood\CONSTRUCTION STANDARDS\STANDARD DETAILS\ELE\ele-2 (Ped Symmetrical Ornamental Light Pole).dgn ELE-5 TO 240 VOLT ROADWAY LUMINAIRE (NOTE 2) PHASE CONDUCTOR GROUND CONDUCTOR NEUTRAL CONDUCTOR 1 CONNECTOR KIT METHOD WITH 6A FUSES INSIDE A TWO POLE FUSE HOLDER AND INSULATING BOOTS 2 2 NO. 10 A.W.G. THWN WIRE 3 MULTIPLE COMPRESSION FITTINGS (SPLICE) 1 4 CONCRETE FOUNDATION 5 WIRE AS SHOWN ON PLANS 6 UNIT DUCT IN PVC RACEWAY 3 7 POLE GROUND LUG 8 #6 GROUND WIRE MECHANICALLY CLAMPED TO GROUND ROD 7 9 5/8 " DIA.x10’ GROUND ROD 5 8 4 9 6 NOTES: 1. TWIN HEADED LIGHT POLES HAVE SEPARATE FUSING & CIRCUIT FOR SECOND FIXTURE. 2. DIRECT CONNECTED LIGHT POLES HAVE 120 VOLT LUMINAIRES. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR LIGHT POLE HANDHOLE WIRING DIAGRAM DATE: JULY 2007 ELE-6 HEAT-SHRINKABLE CAP WITH FACTORY APPLIED WATERPROOF SEALANT, (SIZED TO ACCOMMODATE NUMBER OF CABLES) TRIMMED CABLES COMMISSION TYPE COPPER SLEEVE (SIZED FOR ACTUAL NUMBER OF CABLES AND MFG. SUGGESTED CRIMP TOOL USED) SEALANT TAPE OR INSERT (AROUND AND THROUGH CROTCH SPACE) ELECTRIC CABLES IN CONDUIT (SIZE & NUMBER AS NOTED ON CONTRACT DRAWINGS) #10 AWG ELECTRIC CABLE TO LUMINAIRE EXPOSED SEALANT VILLAGE OF SHOREWOOD STANDARD DETAIL FOR SPLICING ELECTRIC CABLES DATE: JULY 2007 ELE-7 MIN. 2’ VARIABLE MIN. 2’ R.O.W. MIN 30" R.O.W. RGS CONDUIT STREET CROSSING 1 CONDUIT SHALL BE HEAVY WALL RGS CONDUIT. 2 CONDUIT SHALL EXTEND A MINIMUM OF 2 FT. BEYOND BACK OF CURB. 3 CONDUIT SHALL BE A MINIMUM OF 30" BELOW CURB BOTTOM. 30" MINIMUM ~ OF TRENCH TRENCH BACKFILL RED WARNING TAPE 6" WIDE CONDUIT/DUCT SIZES AS SHOWN ON PLANS 12" MAXIMUM WIDTH EXCEPT AS APPROVED BY THE VILLAGE TRENCH CROSS SECTION VILLAGE OF SHOREWOOD STANDARD DETAIL FOR CONDUIT INSTALLATION DATE: JULY 2007 ELE-8 GENERAL NOTES: 1. DISCONNECT ENCLOSURE SHALL BE LOCATED A MINIMUM OF 10’ FROM COM ED TRANSFORMER/PEDESTAL. 2. INSTALL CONDUIT TO WITHIN 3’ FROM COM ED TRANSFORMER/PEDESTAL WITH SUFFICIENT CABLE/DUCT COILED UP. CONNECTION BY COM ED. 3. UNDERGROUND CONDUIT SHALL BE INSTALLED IN EASEMENTS OR RIGHT-OF-WAY ONLY. CONTRACTOR SHALL SUBMIT A WIRING DIAGRAM TO THE VILLAGE FOR REVIEW AND APPROVAL PRIOR TO CONSTRUCTION, AND SHALL SUBMIT AN AS-BUILT CONDUIT PLAN AFTER CONSTRUCTION. 4. PROVIDE GROUND RODS AT SERVICE DISCONNECT AND AT EACH LUMINAIRE AS SHOWN. PROVIDE EQUIPMENT GROUNDING CONDUCTOR IN RUN(S) TO LUMINAIRE(S) PER NEC. 5. SPLICE CONDUCTORS IN POLE BASE(S) USING COMPRESSION SLEEVES PER VILLAGE OF SHOREWOOD STANDARD DETAIL. 6. PROVIDE DUAL IN-LINE FUSEHOLDERS WITH 6A TIME-LAG FUSES IN POLE BASE(S) FOR EACH LUMINAIRE. USE THWN-#10 STRANDED COPPER WIRE IN POLE(S) FROM HANDHOLE TO THE LUMINAIRE(S). 7. USE PVC SCH 80 CONDUIT FOR ALL INSTALLATION WITHIN RIGHT-OF-WAYS. NEMA 3R PEDESTAL ENCLOSURE, MILBANK MODEL #U4329-0 SEE NOTE 1 13" 60A-120V CIRCUIT BREAKER, 22K AIC NEUTRAL/GROUND BUS COM ED TRANSFORMER/ PEDESTAL 58" 1/C #6, 1/C #6 NEUTRAL & 1/C #6 GROUND 1/C #6 & 1/C #6 NEUTRAL #8 AWG GROUND WIRE NOTE 2 12" 3/4 "x10’ COPPER CLAD GROUND ROD W/ MECHANICAL CONNECTION TO STREET LIGHT PHASE CONDUCTOR GROUND CONDUCTOR NEUTRAL CONDUCTOR VILLAGE OF SHOREWOOD 1" SCH 40 HDPE CONDUIT (NOTE 7) STANDARD DETAIL FOR DIRECT CONNECTED STREET LIGHT SERVICE DISCONNECT DATE: JULY 2007 ELE-9 BY C.E. CO. CONTRACTOR TO INSTALL SUFFICIENT CABLE SLACK TO REACH COM ED SECONDARY/TRANSFORMER WITHOUT SPLICING HEIGHT AS REQ’D COM ED WOOD UTILITY POLE FURNISHED BY CONTRACTOR INSTALLED BY C.E. CO. 30" FURNISHED & INSTALLED CONTRACTOR GRADE LINE MIN. 10’-2" GALV. CONDUIT 2 HOLE STRAPS, AS REQUIRED 10’ (NOTE 3) COM ED TO INSTALL FROM 10 FT. ABOVE GRADE AND UP 2" RIGID GLAVANIZED STEEL (RGS) ELBOW 2" RGS CONDUIT TO LIGHTING CONTROLLER 5/8"x10’ COPPERWELD GROUND ROD W/ #4 AWG SOLID COPPER GROUND WIRE ATTACHED W/ CLAMPS, LISTED FOR DIRECT BURIAL SERVICE NOTES: 1. ALL WORK SHALL CONFORM TO COM ED’S BOOK OF "INFORMATION AND REQUIREMENTS FOR THE SUPPLY OF ELECTRIC SERVICE." 2. CONTRACTOR TO PROVIDE CONDUIT BUSHING AND SEALING COMPOUND. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR COM ED OVERHEAD CONNECTION FOR LIGHTING CONTROLLER DATE: JULY 2007 ELE-10A 100A-120/240V, 1}, 3 WIRE, 60 HZ SERVICE METER TO BE SUPPLIED BY LOCAL UTILITY COMPANY PHASE CONDUCTOR NEUTRAL CONDUCTOR GROUND CONDUCTOR PHOTOCELL MOUNTED IN CABINET OVERHANG CABINET OUTLINE 1/C NO. 2 NEUTRAL 13 10 17 14 1 OFF 3 9 12 HAND AUTO 9 16 11 NEUTRAL BUS N.O. N.C. NO. 6 BONDING JUMPER 4 7 LATCHING CONTACT 2 CLEARING CONTACT 5 GROUND BUS 9 15 6 A B C SPARE D 8 9 #6 TYP. NO. 6 COPPER WIRE TO GROUND FIELD BRANCH CIRCUIT WIRING, MINIMUM (4/C #6 & 1/C #6 GND IN 1 1/4 " UNIT DUCT), TYP. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR LIGHTING CONTROLLER SHEET 1 OF 4 DATE: JULY 2007 ELE-10B ITEM SPECIFICATION MFG/MODEL NO. OR EQUAL 1 MAIN CIRCUIT BREAKER 100 AMPERE, 2P, 240V RATING, 22K AIC SIEMENS NO. ED42B100 2 LAMPHOLDER CIRCUIT BREAKER 20 AMPERE, 1P, 120V RATING, 22K AIC SIEMENS NO. ED41B020 3 PHOTOELECTRIC CONTROL CIRCUIT BREAKER 15 AMPERE, 1P, 120V RATING, 22K AIC SIEMENS NO. ED41B015 4 AUXILIARY RELAY 120 V OPERATED DPDT 60 HZ COIL 600V 2 N.O. & 2 N.C. CONTACTS MAGNECRAFT NO. 389FXBXC1-120A 5 CABINET RECEPTACLE AND BOX COMMERCIAL GRADE GFCI 20A/120V, MOUNTED IN A WEATHERPROOF CAST ALUMINUM SINGLE GANG BOX WITH WEATHERPROOF COVER RECEPT: LEVITON NO. 8899, 120V WEATHERPROOF LAMPHOLDER MOUNTED IN A CAST ALUMINUM BOX & EXT. GRADE 100W LAMP RAB NO. VX100DG 7 CONTACTOR 100 AMPERE, 2P, 120V COIL, MECH HELD SQUARE D NO. 8903SQO10V02 8 BRANCH LINE CIRCUIT BREAKERS 5-30 AMPERE, 2P, 240V RATING, 22K AIC SIEMENS NO. ED42B030 9 POWER DISTRIBUTION BLOCK 600 VOLT, INSULATED, SIZE AS REQUIRED MARATHON 10 SERVICE CABLES 3-600V (XLP-TYPE USE) NO. 2 N/A 11 LAMPHOLDER WIRE 2-600V MTW NO. 12 N/A 12 CONTROL WIRE 2-600V MTW NO. 12 N/A 13 SURGE ARRESTOR 10 K AMPERE RATING SQUARE D NO. SDSA 1175 14 PHOTOELECTRIC CONTROL WIRE 3-600V MTW NO. 12 3-600V XLP NO. 12 15 DOOR SWITCH 20A/120V, DOOR MOUNTED SNAP ACTION TYPE PLUNGER SWITCH OMRON NO. A-20GQ-K 16 HAND-AUTO-OFF CONTROL SWITCH 20A, 3 POS. MTD IN CAST ALUM. ENCLOSURE SQUARE D NO. 9001 KYK 111 17 PHOTOCELL 120V, MTD. ON CABINET, DELAY TYPE, SPST-NC FISHER PIERCE NO. FPFA-105M-120V 6 CABINET LIGHT & BOX BOX: APPLETON NO. WSM150 COVER: APPLETON NO. WHG1 VILLAGE OF SHOREWOOD STANDARD DETAIL FOR LIGHTING CONTROLLER SHEET 2 OF 4 DATE: JULY 2007 ELE-10C NOTES 1. CABINETS SHALL BE FABRICATED FROM 0.125-INCH SHEET TYPE 5052-H32 ALUMINUM, FORMED AND ARC WELDED ASSEMBLY. 2. ALL SCREWS AND HARDWARE SHALL BE PLATED, GALVANIZED, OR MADE OF BRASS, ALUMINUM OR STAINLESS STEEL. 3. NAME PLATE SHALL HAVE ENGRAVED 0.75-INCH HIGH LETTERS FILLED IN BLACK: "STREET LIGHTING." 4. CABINET SHALL BE PRIMED AND PAINTED AS SPECIFIED. FINISH COAT SHALL BE RAL6005 GREEN POWDER PAINT. 5. ELECTRIC UTILITY METER BOX SHALL BE MOUNTED ON THE SIDE OF CONTROL CABINET AS SHOWN ON THE PANEL LAYOUT DIAGRAM. 6. THE COMPLETED CONTROLLER WITH ALL OF ITS COMPONENTS SHALL BE UL LISTED AS AN "ENCLOSED INDUSTRIAL CONTROL PANEL UNDER UL508A. 7. METAL MOUNTING PANEL SHALL BE #10 GAUGE GALVANIZED SHEET STEEL FLANGED BACK 0.75-INCHES ID ON 4 SIDES. 8. CIRCUIT BREAKERS, CONTACTORS AND OTHER COMPONENTS SHALL BE MOUNTED ON 0.125-INCH THICK GLASTIC INSULATION BACK PANEL. 9. ALL DEVICES SHALL BE FRONT REMOVABLE. 10. BUS BAR SHALL HAVE 22 LUG TERMINALS SIZED TO ACCOMMODATE REQUIRED WIRE SIZES. NEUTRAL BUS SHALL BE PAINTED WHITE. GROUND BUS SHALL BE PAINTED GREEN. 11. ALL LUGS SHALL BE COPPER SCREWS AND CONNECTORS, SPRING HELD. 12. ALL WIRING TERMINATIONS SHALL BE RATED NOT LESS THAN 75 DEGREE CENTIGRADE. 13. ALL CONTROL WIRING SHALL BE 600V MACHINE TOOL WIRE TYPE MTW. 14. ALL POWER WIRING SHALL BE 600V TYPE RHH/RHW. 15. A LAMINATED COPY OF THE CIRCUIT SCHEMATIC DIAGRAM SHALL BE ATTACHED TO THE INSIDE OF THE CONTROLLER. 16. ALL 120 VOLT SYSTEM AND ALL CONTROL WIRING SHALL BE #12 AWG STRANDED UNLESS OTHERWISE INDICATED. 17. ALL WIRING SHALL BE NEATLY DRESSED AND SUPPORTED. 18. CONNECTION OF SURGE ARRESTOR TO LINE SIDE OF MAIN CIRCUIT BREAKER SHALL NOT BE "DOUBLE LUGGED." VILLAGE OF SHOREWOOD STANDARD DETAIL FOR LIGHTING CONTROLLER SHEET 3 OF 4 DATE: JULY 2007 ELE-10D VENT IN OVERHANG WITH TRAFFIC BOX ENCLOSURE TYPE IV ALUMINUM FABRICATED, ARRANGED FOR MOUNTING NEMA 3R ENCLOSURE FACTORY ON CONCRETE FOUNDATION PAINTED GREEN WITH SLOPED TOP AND SHIELD. CABINET SHALL SCREEN BE MANUFACTURED BY SOUTHERN COM ED SERVICE METER STEEL PLATE LETTERING 3/4 " SIZE W/ "STREET MFG (DIV OF ACCORD INDUSTRIES) AND AS COMPACT AS POSSIBLE CABINET DOOR SHALL FACE AWAY FROM ROADWAY LIGHTING" ENGRAVED ON NAME CORROSIVE RESISTANT PLATE PLATE LOUVERED DOOR WITH FILTER AND SCREEN ENDS OF CONDUITS TO BE SEALED TO PREVENT ENTRANCE OF MOISTURE CABINET SHALL HAVE CORBIN LOCK AND ALSO BE PADLOCKABLE 1/2 " DIA. x 12" ANCHOR BOLTS SIZE OF CONCRETE PAD 4" 1" CHAMFER WHERE NO SIDEWALK BUSHING COMPACTED 2’-6" EXISTS-24"x30"x5" GROUND LINE 4’-6" SAND BASE 3" PVC RACEWAYS. CONTRACTOR TO COORDINATE, NUMBER AND ORIENTATION (PROVIDE 2 SPARES) CONCRETE FOUNDATION #4 @ 12" TIES 6 #4 VERTICAL PLACED 2" RGS SERVICE CONDUIT TO COM ED POLE OR TRANSFORMER UNDISTURBED GROUND 3/4 "x10’ COPPERWELD GROUND ROD, TYP. SEE GROUND FIELD DETAIL THIS SHEET LIGHTING CONTROLLER CABINET & FOUNDATION 12"x12" GREEN POLYMER CONCRETE ACCESS WELL WITH "GROUND" LOGO EMBOSSED IN COVER, TYP. OF 3 " G 0 E ’. L A . E 0 1 P Y T 3/4 " X 10’ COPPERCLAD GROUND ROD MIN. 1’-0" BELOW GRADE (TYP.) EXOTHERMIC WELD, TYP.) NO. 6 COPPER GROUND WIRE (TYP. EACH LEG) VILLAGE OF SHOREWOOD STANDARD DETAIL NO. 6 COPPER GROUND WIRE TO LIGHTING CONTROLLER GROUND BUS FOR LIGHTING CONTROLLER SHEET 4 OF 4 GROUND FIELD DETAIL (TYP.) DATE: JULY 2007 SGN-1 1. SIGN POSTS A. ALL SIGN POSTS SHALL BE MADE OF A SQUARE TWO PIECE UNISTRUT TELESPAR AND SHALL BE 12-GAUGE HOT DIPPED GALVANIZED STEEL. B. THE BASE POST SHALL BE A MINIMUM OF 36 INCHES IN LENGTH AND SHALL MEASURE A MINIMUM OF 2 INCHES O.D. SQUARE.THE SIGN POST LENGTH SHALL VARY DEPENDING ON THE SIGN IN ORDER TO MAINTAIN A DISTANCE OF A MINIMUM OF 7 FEET FROM GRADE TO THE BOTTOM OF THE SIGN AND SHALL MEASURE A MINIMUM OF 1 3/4 INCHES O.D. SQUARE. C. THE BASE POST SHALL BE DRIVEN PLUMB INTO UNDISTURBED SOIL WITH A MAXIMUM OF 3 INCHES ABOVE GRADE.THE TOP OF THE POST SHALL NOT BE DISTORTED OR DAMAGED FROM DRIVING IT INTO THE SOIL. D. THE ASSEMBLY SHALL BE SECURED WITH A GALVANIZED OR EQUAL BOLT, FLAT WASHER, AND LOCK NUT.THE END OF BOLT IS TO BE PEENED OVER SO THE LOCK NUT CANNOT BE REMOVED. 2. SIGNS A. STREET NAME SIGN BLADES SHALL BE 9-INCH WIDE EXTRUDED ALUMINUM WITH WHITE DIAMOND GRADE SHEETING. STREET NAMES SHALL BE MADE OF 6 INCH SERIES "B" LETTERS.THE STREET DESIGNATION SUFFIX SHALL BE MADE OF 3 INCH SERIES "B" LETTERS.THE LETTERS SHALL BE PLACED STRAIGHT AND EVENLY SPACED. B. THE BASE COLOR SHALL BE DIAMOND GRADE WHITE WITH GREEN E.C. FILM LETTERING AND SHALL VARY IN LENGTH ACCORDING TO THE STREET NAME.THE VILLAGE OF SHOREWOOD LOGO SHALL BE ON THE LEFT SIDE OF THE SIGN AND SHALL BEGIN 3 INCHES FROM THE END OF THE BLADE.THE LETTERING SHALL BEGIN 2 INCHES FROM THE LOGO AND END 3 INCHES FROM THE END OF THE BLADE. C. STOP SIGNS (R1-1) SHALL BE 30-INCH WITH DIAMOND GRADE VIP SHEETING. THE"ALL WAY" PLACARD (R1-4) SHALL BE APPLIED TO ALL STOP SIGNS AT ALL WAY STOP INTERSECTIONS. D. STOP SIGNS (R1-1) SHALL BE 36-INCH WITH DIAMOND GRADE VIP SHEETING AT ALL INTERSECTIONS WITH U.S. ROUTE 52 AND ILLINOIS ROUTE 59. E. YIELD SIGNS (R1-2) SHALL BE 36-INCH WITH DIAMOND GRADE VIP SHEETING. F. SPEED LIMIT SIGNS FOR LOCAL ROADS SHALL HAVE BLACK LETTERING AND BORDERS ON A WHITE BACKGROUND WITH DIAMOND GRADE VIP SHEETING. 1. SPEED LIMIT SIGNS FOR LOCAL ROADS SHALL BE 24-INCH X 36-INCH WITH "RESIDENTIAL" "25 MPH" "UNLESS OTHERWISE POSTED" TEXT. 2. SPEED LIMIT SIGNS (R2-1) FOR COLLECTOR STREETS SHALL BE 24-INCH X 30-INCH. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR SIGN STANDARDS SHEET 1 OF 2 DATE: JUNE 2007 ...\SGN\sgn-1 (sign standards).dgn SGN-1 G. WEIGHT LIMIT - 5 TONS (R12-1) SIGNS SHALL HAVE BLACK LETTERING AND BORDERS ON A WHITE BACKGROUND AND SHALL BE 24-INCH X 30-INCH WITH DIAMOND GRADE VIP SHEETING. H. SPRINKLING RESTRICTION SIGNS SHALL HAVE BLACK LETTERING AND BORDERS ON A WHITE BACKGROUND AND SHALL BE 24-INCH X 30-INCH WITH DIAMOND GRADE VIP SHEETING WITH "SPRINKLING ALLOWED" "6AM TO 10AM" "6PM TO 10PM" "ODD/EVEN" TEXT. I. NO PARKING ON VILLAGE STREETS AFTER 2 INCH SNOWFALL SINGS SHALL HAVE RED LETTERING AND BORDERS ON A WHITE BACKGROUND AND SHALL BE 24-INCH X 30-INCH WITH DIAMOND GRADE VIP SHEETING. 3. HARDWARE AND INSTALLATION A. ALL BANDING, BUCKLES AND CLIPS SHALL BE STAINLESS STEEL AND POWDER - COATED BLACK. BANDING SHALL HAVE A MINIMUM OF * INCH WIDTH AND SHALL HAVE A MINIMUM OF 30 THOUSANDS INCH THICKNESS. B. ALL STREET NAME SIGNS SHALL BE MOUNTED ON A STREET LIGHT POLE USING A 14 INCH WING BRACKET FOR BLADES UNDER 36 INCHES AND A 24 INCH WING BRACKET FOR BLADES 36 INCHES OR OVER.ALL WING BRACKETS SHALL BE MADE FOR EXTRUDED BLADES; MOUNTED TO STREET LIGHT POLES WITH THREE BANDS; SECURED USING 5/16 INCH BY 1* INCH GALVANIZED BOLTS OR EQUAL, WITH A FLAT WASHER AND LOCK NUT; AND BE PLACED A MINIMUM OF 12 FEET ABOVE GRADE ON THE LIGHT POLE.REGULATORY SIGNS SHALL BE MOUNTED WITH VANDAL-PROOF HARDWARE. C. ALL STREETS NAME SIGNS SHALL BE PLACED A MINIMUM OF 12 FEET FROM GRADE AND PLACED PARALLEL TO THE STREET NAMED. D. ALL SIGN INSTALLATIONS SHALL CONFORM TO THE MANUAL ON UNIFORM TRAFFIC CONTROL DEVICES, 2003 EDITION AND SHALL BE CONSISTENT WITH THE APPROVED TRAFFIC CONTROL, STRIPING, AND SIGNAGE PLANS. IN THE CASE OF A CONFLICT, THE VILLAGE OF SHOREWOOD CODE SHALL TAKE PRECEDENCE. E. FOR NEW SUBDIVISION CONSTRUCTION, PERMANENT STREET SIGNS MAY BE MOUNTED ON A TEMPORARY POST WITH A MINIMUM OF 2-POUND GREEN OR GALVANIZED U POST AND WITH A MINIMUM LENGTH OF 12 FEET.STREET SIGNS AND REGULATORY SIGNS ARE TO BE ERECTED PRIOR TO THE ISSUANCE OF THE FIRST BUILDING PERMIT.THE SIGNS SHALL BE INSTALLED IN ACCORDANCE WITH THE APPROVED SIGNAGE PLAN.THE DEVELOPER IS SOLELY RESPONSIBLE FOR THE MAINTENANCE OF THE SIGN INSTALLATIONS UNTIL THE VILLAGE ACCEPTS THE SIGNS. ALL PERMAMENT SIGNS SHALL BE INSTALLED ON PERMAMENT MOUNTS AT THE TIME OF ROADWAY SURFACE PLACEMENT. F. ALL SIGNS ON TEMPORARY POSTS WILL BE TRANSFERRED TO A LIGHT POLE OR A SQUARE POST WHERE THERE IS NO LIGHT POLE. SIGNS MUST BE TRANSFERRED TO THE POLE/POST AT THE TIME STREET LIGHTING IS INSTALLED OR AT THE REQUEST OF THE VILLAGE. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR SIGN STANDARDS SHEET 2 OF 2 DATE: JUNE 2007 ...\sgn-1a (sign standards).dgn SGN-2 24" NO ON VILLAGE 30" PARKING STREETS AFTER 2-INCH SNOWFALL VILLAGE OF SHOREWOOD STANDARD DETAIL FOR NO PARKING SIGN DATE: JUNE 2007 ...\SGN\sgn-2 (no parking).dgn SGN-3 3" RESIDENTIAL 30" 3 12" 8" SPEED LIMIT 36" 6" 24" 25 UNLESS 2" OTHERWISE POSTED NOTES: 1. PREFERRED LETTER SIZES NOTED. 2. PLACE ABOVE WEIGHT LIMIT SIGN ON SAME POST. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR RESIDENTIAL SPEED LIMIT SIGN DATE: JUNE 2007 ...\sgn-3 (residential speed limit).dgn SGN-4 24" 6AM TO 10 AM 30" SPRINKLING ALLOWED 6PM TO 10 PM ODD / EVEN YEAR ROUND REGULATION NOTE: 1. THIS SIGN IS TO BE DELIVERED TO THE PUBLIC WORKS DEPARTMENT, NOT INSTALLED. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR SPRINKLING SIGN DATE: JUNE 2007 ...\SGN\sgn-4 (sprinkling).dgn SGN-5 24" LIMIT 30" WEIGHT 5 TONS NOTE: PLACE UNDERNEATH SPEED LIMIT SIGN ON SAME POST. VILLAGE OF SHOREWOOD STANDARD DETAIL 5 TON WEIGHT LIMIT SIGN DATE: JUNE 2007 ...\SGN\sgn-5 (weight limit).dgn SGN-6 VILLAGE STANDARD 75’ NO PARKING SIGN VILLAGE STANDARD WEIGHT LIMIT SIGN OVER 75’ VILLAGE STANDARD SPEED LIMIT SIGN 25’ SUBDIVISION TO RESIDENTIAL SPRINKLING SIGN END CURB RETURN VILLAGE OF SHOREWOOD SIGN SPACING FOR TYPICAL RESIDENTIAL SUBDIVISION ENTRANCE DATE: JULY 2007 ...\SGN\SGN-6 (Sign Spacing).dgn 1 .8 7 5 " 21.00" 21.00" 8" 4" FUT UREST REET ON CONNECT I 8" 27.75" 5" 30" 27.75" 5" R .75" .5" SGN-7 60" NOTE: TO BE MOUNTED ON TYPE III BARRICADES BELOW ROAD CLOSED SIGN. VILLAGE OF SHOREWOOD SIGNAGE FOR FUTURE STREET CONNECTION DATE: JULY 2007 ...\SGN-7 (Signage for future).dgn MSC-1 TOP OF CONCRETE 6" SCREW ON CAP MONUMENT TO BE TO BE SET FLUSH SET FLUSH WITH WITH FINISHED GRADE FINISHED GRADE FINISHED GRADE 6" STAMPED BRASS OF G E SH O R 72" MINIMUM DISK, 4" DIA. MIN. E O ELEVATION O D VI LL A IN CENTER W 36" MINIMUM (1) # 4 BAR B 2 701.25 E 1 N 1 CH . M AR K NO 6" P.V.C. PIPE 6" P.V.C. PIPE 6" PERMANENT CONCRETE MONUMENT 6" PERMANENT BENCHMARK NO SCALE NOTES: 1. PERMANENT CONCRETE MONUMENTS SHALL BE PLACED AT ALL CORNERS AND CHANGES IN BEARING OF THE EXTERIOR BOUNDARY. 2. A MINIMUM OF ONE PERMANENT BENCHMARK SHALL BE ESTABLISHED FOR EACH 50 ACRES, OR FRACTION THEREOF, SUBDIVIDED, AT A LOCATION DESIGNATED ON THE CONSTRUCTION PLANS AND APPROVED BY THE VILLAGE ENGINEER. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR PERMANENT MONUMENTS DATE: JUNE 2007 ...\MSC-1 (Permanent Monuments).dgn NOTES: MSC-2 1. CASING PIPE SHALL BE NEW PIPE CONFORMING TO ASTM C139 GRADE A WITH CONTINUOUS FIELD-WELDED BUTT JOINTS IN ACCORDANCE WITH AWWA C206, A MINIMUM YIELD STRENGTH OF 35,000 PSI, AND THE FOLLOWING MINIMUM WALL THICKNESS: NOMINAL PIPE SIZE - INCHES MINIMUM WALL THICKNESS - INCHES UNDER HIGHWAY UNDER 14 14 AND 16 0.188 0.250 UNDER RAILROAD 0.2500 0.3125 18 0.250 0.3125 20 0.250 0.3750 24 0.312 0.4375 30 0.312 0.5000 36 0.375 0.5625 42 0.375 48 0.375 0.625 54 0.500 0.719 60 0.575 0.781 66 0.650 0.875 72 0.650 0.938 0.563 2. COAT EXTERIOR SURFACES OF THE CASING PIPE WITH COAL-TAR EPOXY COMPLYING WITH AWWA C210. 3. PROVIDE CARRIER PIPE SUPPORT SYSTEM TO POSITION CARRIER PIPE AT THE INDICATED ELEVATION AND SLOPE WITHIN THE CASING, USING POWERSEAL CASING CHOCK MODEL 4810 STAINLESS STEEL SPACERS CONSISTING OF 4 GAUGE TYPE 304 STAINLESS STEEL SHELLS, PVC LINER, HIGH MOLECULAR WEIGHT POLYMER RUNNERS, AND STAINLESS STEEL BOLTS AND LOCK NUTS, OR APPROVED EQUAL. A MINIMUM OF THREE SPACERS SHALL BE PROVIDED PER CARRIER PIPE LENGTH, ON 6-FOOT CENTERS. 4. FILL ANNULAR SPACE BETWEEN CARRIER AND CASING PIPES FOR ALL PIPES EXCEPT WATER MAINS WITH PEA GRAVEL. 5. CONSTRUCT END SEALS WITH CONCRETE BRICK LAID LENGTHWISE WITH MORTAR OR PREMANUFACTURED RUBBER END SEALS MADE SPECIFICALLY FOR THIS PURPOSE. 6. FILL VOIDS AROUND EXTERIOR OF CASING PIPE WITH MEARL GEOFOAM LIQUID CONCENTRATE LOW DENSITY CELLULAR CONCRETE GROUT HAVING A MINIMUM NET DENSITY OF 45 PCF AND A MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS OF 160 PSI. CASING SPACERS (SEE NOTE 3) CASING PIPE (SEE PLANS FOR SIZE) CARRIER PIPE (SEE PLANS FOR SIZE AND MATERIAL) PEA GRAVEL (SEE NOTE 4) VILLAGE OF SHOREWOOD STANDARD DETAIL NO SCALE FOR CASING PIPE DATE: JUNE 2007 ...\MSC\msc-2 (casing pipe).dgn CENTER OF LOT PLUGGED END OF 5’ 5’ SERVICE LOCATED AT PROPERTY LINE 8’ W W W SANITARY SEWER W W W W CORPORATION STOP SA SERVICE WATER SERVICE SA SA SA SA SA SA SA SA 8’ 5’ 5’ CURB STOP W/ BOX RIGHT-OF-WAY CENTER OF LOT NOTES: 1. LOCATION OF SEWER AND WATER SERVICES SHALL BE AS SHOWN BELOW UNLESS INDICATED OTHERWISE ON PLANS. 2. THE END OF EACH WATER SERVICE SHALL BE MARKED WITH A BLUE 4"X4" POST, AND STAMPED "W" ON THE CURB. 3. THE END OF EACH SANITARY SEWER SERVICE SHALL BE MARKED WITH A GREEN 4"X4" POST, AND STAMPED "S" ON THE CURB. 4. WATER SERVICES SHALL END AT THE BUFFALO BOX UNLESS OTHERWISE INDICATED ON PLANS. MSC-3 VILLAGE OF SHOREWOOD FOR STANDARD DETAIL DATE: JUNE 2007 ...\msc-3 (typical service laterals).dgn TYPICAL SERVICE LATERALS NO SCALE CURB FACE MSC-4 ACCESSIBLE ROUTE RAMPS AS NECCESSARY ACCESS AISLE 18’ 8’-0" 8’-0" 8’-0" 16’-0" 8’-0" 16’-0" STANDARD IL DESIGN NOTE: 1. A HIGH QUALITY YELLOW PAINT RECOMMENDED BY THE PAINT MANUFACTURER FOR PAVEMENT STRIPING SHALL BE USED. THE ARROW SHOULD BE OMITTED WHERE THERE RESERVED PARKING IS ONLY ONE SPACE. 2. REFER TO THE VILLAGE ORDINANCE FOR MINIMUM THE ARROW MAY ALSO REQUIRED NUMBER OF BE MADE TO POINT IN HANDICAP STALLS. ONLY ONE DIRECTION. THE SIGN MUST BE 3. HANDICAP LOGO SHALL BE SUPPLEMENTED WITH INSTALLED USING YELLOW THE ILLINOIS STANDARD PAINT. R7-I101 PLATE GIVING THE AMOUNT OF THE FINE FOR ILLEGALLY PARKING IN THE RESERVED SPACE(S). R7-8 THIS PLATE MAY BE MOUNTED DIRECTLY $350 FINE BELOW THE R7-8 SIGN OR COMBINED WITH THAT SIGN ON A SINGLE 12" BY 24" PANEL. ILLINOIS STANDARD R7-I101 VILLAGE OF SHOREWOOD STANDARD DETAIL FOR HANDICAP STALL DATE: JUNE 2007 ...\MSC\MSC-4 (Handicap Stall).dgn MSC-5 CURB FACE 1’-0" (TYP.) 18’ 8’-0" (TYP.) 9’-0" (TYP.) SEE NOTE 1 NOTE: 1. A HIGH QUALITY YELLOW PAINT RECOMMENDED BY THE PAINT MANUFACTURER FOR PAVEMENT STRIPING SHALL BE USED. VILLAGE OF SHOREWOOD STANDARD DETAIL FOR PARKING STALL STRIPING DATE: JANUARY 2008 ...\MSC-5 (ParkingStripingl).dgn