Series C Roof Upblast and Sidewall Centrifugal Exhaust Fans
Transcription
Series C Roof Upblast and Sidewall Centrifugal Exhaust Fans
Centrifugal Upblast & Sidewall Exhaust Models CUBE, CUE, CWB, CW and USGF • General Clean Air • Restaurant Grease • High Wind • Seismic • Smoke Control • Contaminants ® Performance data now included. August 2013 Models CUE, CUBE, CW, CWB, USGF Centrifugal Exhaust Fans Roof Upblast and Sidewall Table of Contents Standard Construction Features . . . . . . . . . .4-5 Vari-Green Options: Vari-Green® Motor . . . . . . . . . . . . . . . . . 10 Vari-Green® Controls . . . . . . . . . . . . . . . 11 Applications: Options and Accessories . . . . . . . . . . . . .12-13 Model Comparison . . . . . . . . . . . . . . . . . . . . . 3 General Clean Air . . . . . . . . . . . . . . . . . . . 6 Typical Installations . . . . . . . . . . . . . . . . . .14-15 Restaurant Grease . . . . . . . . . . . . . . . . . . 6 Performance and Dimensions: Heavy Grease . . . . . . . . . . . . . . . . . . . . . . 6 Model Number Code . . . . . . . . . . . . . . . 16 Emergency Smoke Control . . . . . . . . . . . . 7 Performance Pages. . . . . . . . . . . . . . .17-48 Seismic . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Typical Specifications . . . . . . . . . . . . . . . .49-55 High Wind & Hurricane . . . . . . . . . . . . . . . 8 Quick Build Program . . . . . . . . . . . . . . . . . . . 56 Severe Duty Roof Curbs . . . . . . . . . . . . . . 9 Our Commitment. . . . . . . . . . . . . . . . . . . . . . 56 Modes CUE, CUBE, CW, CWB, and USGF meet CE (Conformité Européenne). • CUBE, CUE, CWB, and CW models are Listed for Electrical (UL/cUL 705) File no. E40001 • CUBE, CWB, USGF and models CUE and CW sizes 099 and larger are Listed for Grease Removal (UL/cUL 762) File no. MH11745 • CUBE and USGF models are Listed for Emergency Smoke Control Systems (UL/cUL Listed for 500˚F (260˚C) for 4 hours and 1,000˚F (538˚C) for 15 minutes) File no. MH17511 Note: UL/cUL is optional and must be specified Model sizes CUBE-099, 161XP, 240XP, 300HP & 300XP are excluded for Emergency Smoke Control. 2 Greenheck Fan Corporation certifies that the Model CUBE, CUE, CWB, CW and USGF shown herein are licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and Publication 311 and comply with the requirements of the AMCA Certified Ratings Program. The certified ratings for Model CUBE, CUE, CWB, CW and USGF, are shown on pages 17-48. Models CUE, CUBE, CW, CWB, USGF Centrifugal Exhaust Fans Roof Upblast and Sidewall Model Comparison Maximum Static Pressure (in. wg) Relative Cost Mixed Flow 9 9 9 9 9 Belt 9 9 9 9 9 9 9 9 9 9 Propeller/Axial High Temp (above 200°F ) High Wind (150 mph) Smoke Control (UL) Grease (UL 762) Recirculate Reversible 9 9 9 9 9 9 9 9 9 99 9 9 9 Maximum Volume (cfm) 9 Supply Wall Hanging Base/Floor Roof Curb 9 9 9 9 9 9 Centrifugal USGF 9 9 9 9 9 9 Impeller Type Performance Direct CWB 9 9 9 9 9 9 Spark Resistant CUBE 9 Contaminated Air CW 9 9 9 9 9 Drive Type Application General/Clean Air CUE Indoor Outdoor Model Airflow Exhaust Mounting Ceiling Mounted Location 6,400 3 $$ 6,400 3 $$ 30,000 5 $$ 12,500 2.75 $$ 6,800 2 $$$$ When you buy a Greenheck roof upblast or sidewall exhaust fan, you’ll receive a fan with the industry’s best performance and durability for general clean air, restaurant grease, smoke control, light contaminants, seismic, high wind, and hurricane applications. Both roof upblast and sidewall configurations are specifically designed to discharge air directly away from the mounting surface. • Performance as cataloged is assured. All fan sizes are tested in our AMCA Accredited Laboratory and all models are licensed to bear the AMCA Sound and Air Performance seal. • UL/cUL Listed for Electrical, Grease and Smoke Control. • Greenheck subjects these products to extensive life testing, assuring you the fans will provide many years of reliable performance. 3 Standard Construction Features Standard Construction Features 1 2 3 CUE CW USGF CUBE CWB 9 Wheel An aluminum, backward-inclined, non-overloading centrifugal wheel is utilized to generate high-efficiency and minimal sound. Wheel cones are carefully matched to the venturi for maximum efficiency. Each wheel is statically and dynamically balanced for long life and quiet operation. 9 9 *NonStick, Steel Vibration Isolation True vibration isolators consist of two independent studs separated by a neoprene (rubber) center. Reduces vibration and noise transfer between drive system and fan housing. (No metal to metal contact. Factory-mounted ground wire used to ground system). 9 9 9 NEMA-1 switch is factory-mounted and wiring is provided from the motor as standard (other switches are available). All wiring and electrical components comply with the National Electric Code (NEC) and are either UL/cUL Listed or Recognized. 9 9 Disconnect Switch NEMA-3R switch is factory-mounted and wired as standard. All wiring and electrical components comply with the National Electric Code (NEC) and are either UL/cUL Listed or Recognized. 9 4 Bearings 100% factory tested and designed specifically for air handling applications with a minimum L10 life in excess of 100,000 hours (L 50 life of 500,000 hours). 9 9 9 5 Fan Shaft Precisely sized, ground and polished so the first critical speed is at least 25% over the maximum operating speed. Where the shaft makes contact with bearings, close tolerances result in longer bearing life. 9 9 9 6 Drive Assembly Belts, pulleys and keys are oversized 150% of driven horsepower. Machined cast pulleys are adjustable for final system balancing. Belts are static-free and oil-resistant. 9 9 9 7 Motor Cover Constructed of aluminum. Attached with stainless steel fasteners for easy removal and access to the motor compartment and drive assembly. 9 9 *Steel 8 Stainless Steel Fasteners Allow easy removal and access to the motor compartment and drive assembly. 9 9 9 9 Windband One-piece, heavy-gauge aluminum with a rolled bead for extra strength directs exhaust air away from the mounting surface. 9 9 *Steel 10 Motor Carefully matched to the fan load and is mounted out of the airstream. 9 9 9 11 Motor Cooling Tube Cooling fins located on top of fan wheel draw outside air through a large breather tube directly into the motor compartment. Positive motor cooling with fresh air results in maximum motor life. 9 9 9 12 Internal Supports Heavy-gauge supports provide additional strength to withstand winds of 150 mph and supports motor and drives. 9 9 9 13 Leakproof Construction One-piece windband is continuously welded to the curb cap and drain trough for leakproof protection on models CUE, USGF and CUBE sizes 99 through 300 and all sizes with UL/cUL 762. 9 9 9 14 Curb Cap with Mounting Holes One-piece for a weather-tight fit. Constructed of aluminum with an integral deep spun venturi. Aluminum curb cap has pre-punched mounting holes to ensure correct attachment to the roof. 9 9 *Steel 15 Drain Trough Allows for one-point drainage of water, grease and other residues. 9 16 Galvanized Mounting Plate Allows mounting and sealing to the wall prior to mounting the entire unit. The remainder of the unit is attached to the mounting plate without locating and fastening problems associated with mounting a heavy sidewall unit to a wall. 9 17 Galvanized Birdscreen Rigid wire protects the fan discharge from birds and small objects. Standard on all sidewall fan models. 9 18 Nameplate Permanent stamped aluminum nameplate for exact model and serial number identification. 9 9 For easy internal electrical wiring in applications. (Not available on UL 762 rated fans per NFPA 96). 9 9 Not Internal Conduit Shown Chase *Differences from the standard construction feature. 4 9 9 9 9 9 Standard Construction Features 5 6 7 4 8 3 9 10 2 11 1 12 16 13 15 17 14 Models CW & CWB Models CUBE and CUE Standard Construction Features - Continued 19 Dual Drives CUE CW USGF CUBE CWB 9 Oversized 150%, adjustable, static-free and oil-resistant. Not Hinged Curb Allows maintenance personnel to gain access to wheel and ductwork for regular Shown Base with Cables inspection and cleaning by utilizing the hinged curb base with cables. 9 20 Clean-Out Port Allows the entire centrifugal wheel to be easily cleaned through a 4-inch diameter hole on outside of the fan windband. Meets NFPA 96 standard. 9 21 PermatectorTM Coating Typically used for applications that require corrosion resistance in indoor and outdoor environments. 9 22 Lifting Points Various lifting points located on the drive frame and bearing plate. 9 9 9 19 3 22 20 18 21 Model USGF 5 Applications Restaurant and High Grease Clean Air Applications Models CUBE, CUE, CWB and CW These spun aluminum fans are specifically designed for roof mounted or wall mounted applications. General clean or lightly contaminated exhaust air can be discharged directly upward, away from the roof surface or discharged out and away from building walls. • Most advanced motor cooling of any fan in its class. • One-piece windband, continuously welded to the curb cap, ensures leak-proof construction for the life of the fan. • Performance as cataloged is assured. All fan sizes are tested in our AMCA Accredited Laboratory and all models are licensed to bear the AMCA Sound and Air Performance seal. • Greenheck subjects these products to extensive life testing, assuring you the fans will provide many years of reliable performance. Restaurant and Grease Applications Models CUBE, CUE, CWB and CW When you choose a Greenheck fan, you have selected a fan with the industry’s best performance and durability for restaurant and grease applications. Spun aluminum exhaust fans, models CUBE, CWB and models CUE and CW sizes 099 and larger, are specifically designed for use in restaurant applications to discharge air directly away from the mounting surface. • Most advanced motor cooling of any fan in its class. • One-piece windband, continuously welded to the curb cap, ensures leak-proof construction for the life of the fan. • UL/cUL 762 Listed for exhausting restaurant grease exhaust. Ultimate Steel Grease Fan for Heavy Grease Applications Model USGF Fan model USGF is the industry’s best for performance and durability for heavy grease applications. This spun steel exhaust fan is specifically designed to remove large amounts of grease and/or solid fuels and discharge the air directly away from the mounting surface. • Only spun steel fan in the industry. • Withstands the most severe cleaning conditions. • Most advanced motor cooling of any grease fan. Capable of continuously handling 400°F (204°C) airstream temperatures. • UL/cUL 762 Listed for restaurant grease exhaust. • Only kitchen-specific exhaust fan to meet Miami-Dade County Test protocols for Large Missile Impact Test. Refer to page 16 for size chart. 6 Applications Emergency Smoke and Seismic Emergency Smoke Control - CUBE, USGF When you buy a Greenheck model CUBE or USGF with the smoke control option, you receive a fan with the industry’s best performance and durability for smoke control applications (as found in emergency smoke control systems). Note: Model sizes CUBE-099, 161XP, 240XP, 300HP & 300XP are excluded for Emergency Smoke Control. Refer to page 16 for size chart. Seismic - CUBE, CUE, CWB, CW and USGF • UL/cUL Listed for 500°F (260°C) for 4 hours and 1,000°F (538°C) for 15 minutes. • Half the weight of traditional smoke control fans, ideal choice for roof load concerns. • Low profile, height is less than half of traditional smoke control fans, maximum of 481⁄8 inches (1334 mm) from curb cap to top of fan. • Multiple applications, capable of exhausting general clean air and satisfying emergency smoke control regulations. With changes in building codes and standards more equipment is being required to be seismically certified in areas of the country not commonly thought of as being in seismically active zones. The International Building Code (IBC) is designed to provide model code regulations that safeguard public health and safety in all U.S. communities. IBC 2009 and 2012 are the latest versions adopted on state or local levels. With this code, the standards are intended to improve the performance and design of non-structural systems subject to seismic events. The State of California, one of the most active seismic areas in the United States, has the Office of Statewide Health Planning and Development (OSHPD). OSHPD Plan regulates the design and construction of healthcare re facilities to ensure they are safe and capable of f providing services to the public after a seismic p event. OSHPD developed their own unique e certification process to incorporate the IBC and c ASCE testing standards to ensure equipment A remains operable after a seismic event. Protocols designed for seismic standards: Seismic Testing Criteria All Greenheck seismically certified models have been tested using the most severe seismic event that is found on the Spectral Response Map per IBC Figures 1613.5 (1-2). Because our testing is performed under the worst case scenario, using the highest mapped seismic load, highest level occupancy category, worst case site class, and highest code mandated importance factor, it allows Greenheck seismically certified fans to be used anywhere in the United States under any conditions. California OSHPD Test Protocols The California Office of Statewide Health Planning and Development (OSHPD) requires all certified models be shake table tested in accordance with ICC ES AC-156, in which the fans are physically subjected to the same or greater forces than they will see during a seismic event. By subjecting Greenheck model CUBE, CUE, CWB, CW and USGF fans to this type of testing ensures the fans will operate without problems after a seismic event. OSHPD Certification No. 0148-10 The OSHPD certification numbers and supporting documents can be viewed on OSHPD’s website and ensures that the fan has been subjected to and passed rigorous testing standards. State Licensed P.E. Calculations When using the fans in applications which are not covered by California OSHPD standards Greenheck models CUBE, CUE, CWB, CW and USGF have been certified by a third-party engineering firm to IBC 2009, 2012 and ASCE 7-05 standards. These engineers hold professional engineers (PE) licenses in all 50 states so no matter where your job is located you are backed by a PE signature for your state. Certified Independent Third-Party Testing All Greenheck Seismically Certified Fan models have gone through extensive testing procedures. Greenheck models CUBE, CUE, CWB, CW and USGF have been certified to IBC 2009, 2012, ASCE 7-05 and California OSHPD standards through both engineering calculations and shake table testing of all models by independent third-party engineering firms. 7 Applications High Wind and Hurricane High Wind and Hurricane - CUE, CUBE, CW, CWB and USGF Greenheck is leading the High Wind Standard for roof top fans and ventilators. Forceful winds and wind-borne debris are the cause of most hurricane damage. Hurricane winds start at 75 mph and can exert a force of 75 pounds per square foot of pressure—or over 900 pounds on a fan and curb. Forceful winds are not the only problem, wind-borne debris can also cause detrimental effects to objects and structures. High winds and extreme forces are the cause of most storm damage. By analyzing calculations, computer simulations, actual testing, and other standards—Greenheck developed the High Wind Standard. Atlantic, Gulf and Pacific history of major hurricane tracks. Protocols designed to protect against wind-borne debris and severe wind loads: Structural Performance Load A static load that is 1.5 times the design load (195 pounds per square foot pressure) is applied both positive and negative to simulate wind force loads in each direction. Structural Performance per Dade County Protocol TAS-202 (ASTM E-330). Large Missile Impact Test Large Missile Impact Testing is required when objects are located 30 feet or less from the ground. The test is per Dade County Protocol TAS-201. The test unit is impacted three times with a piece of lumber (2 in. x 4 in. x 6 ft.) weighing approximately nine pounds and traveling at 34 mph. This simulates wind-borne debris striking the fan. Miami-Dade County Greenheck has gone the extra mile and worked with Miami-Dade County to design a High Velocity Hurricane Zone standard for rooftop fans. The USGF has become the first rooftop fan certified and approved by the Test Protocols Miami-Dade Building Code Compliance office and Texas Department of Insurance for use in hurricane zones. Miami-Dade NOA Numbers The certifications can be viewed on the Miami-Dade County website under the NOA numbers listed below. Models CUBE, CUE, CWB, CW and USGF are the first upblast aluminum/steel fans in the industry that have received a Miami-Dade NOA for high wind (150 mph) and hurricane zones. CUBE, CUE, CWB, CW: 12-0120.13 and USGF: 12-0501.04 Texas Department of Insurance The certifications can be viewed on the Texas Department of Insurance Windstorm website under TDI number RV-42. Structural calculations performed by a state licensed Professional Engineer (P.E.) on models CUBE, State Licensed P.E. CUE, CWB, CW and USGF include Finite Element Analysis (FEA) and a stamped P.E. report of the fans compliance to ASCE 7-05 Minimum Design Loads for Buildings and Other Structures Standard and the Calculations Florida Building Code. The ASCE 7-05 Standard meets the IBC, Florida and Miami-Dade County codes. Certified Independent Third-Party Testing Each of the Greenheck models have been subjected to extensive testing procedures. The CUBE, CUE, CWB, CW and USGF have been certified by an independent third-party to the ASTM E-330 Static Pressure Difference Standard, Florida Building Code Test Protocols TAS-202 Static Pressure Difference and TAS-201 Large Missile Impact. All tests are video taped for documentation of test method and results. Computational Fluid Dynamics (CFD) All Greenheck high wind models have been analyzed using Computational Fluid Dynamics (CFD). CFD is computer software designed to simulate the flow of high speed winds over the surface of objects. The software records the force profile exerted on the fan so it can be utilized in Finite Element Analysis (FEA). Finite Element Analysis (FEA) Utilizing the results from CFD analysis Greenheck can accurately predict the stress, strain, and deflection resulting from high wind loads. Greenheck high wind units have been proven to withstand high winds through Finite Element Analysis utilizing CFD results. 8 Applications Severe Duty Roof Curbs for High Wind and Hurricane High wind and severe duty roof curbs are available on CUBE, CUE and USGF models with high wind certification. The severe duty roof curb models can ship separately to allow for final finishing of the roof prior to the fan arrival and installation. Available Heights 1 inch (25 mm) Insulation Flashing Flange GPF for flat roofs Curbs are used for high wind/seismic applications. Fully formed on three sides with a single, fully welded seam when dimension (L+Wx2) <118 inches (2997 mm). Larger sizes are a fully welded assembly. 9 5 inches 8 to 42 (127 mm) (203 to 1067) GPFHL for heavy load applications Curb construction is intended to support compression loads exceeding 1,000 pounds (454 kg). GPFHL is mounted directly to the roof deck structure, and the roofing material is brought to the vertical surface and sealed to the flashing flange. Additional standard construction features include 14 gauge galvanized steel and internal vertical support members. 9 5 inches 12 to 24 (127 mm) (305 to 610) Description GPFHD for supporting heavy load equipment For severe duty, high wind and seismic applications. The double thick flashing flange provides an extremely durable surface to secure the curb to the building structure. The roofing material is brought to the vertical surface and sealed to the flashing flange. Additional standard construction features include 12 gauge galvanized steel and internal vertical support members. 9 Inches (mm) Double Thick 12 to 24 5 inches (305 to 610) (127 mm) Large missile impact test on a model USGF fan. 9 Vari-Green® Motor Options Models CUE/CW Features Greenheck’s electronically commutated (EC) Vari-Green (VG) motor combines motor technology, controllability and energyefficiency into one single low maintenance unit and is the industry’s first fully controllable motor. When combined with Greenheck’s CUE and CW fans, all the CFM and static pressure ranges of a belt drive can be attained with the benefits of a direct drive. 1. Dial on Motor Control - a potentiometer (dial on motor control) is mounted on the motor for easy speed adjustment for system balance. Simply turn the dial. There are no belts and pulleys to adjust. 2. Control Wire Inputs - the motor accepts a 0-10V DC signal from Building Automated Systems or other controls to adjust motor speed. 50/60 HZ Motor Information RPM 1725 1725 1725 2500 1725 2200 1725 1725 1725 Volts 115/230 115/230 115/230 115/230 115/230 115/230 115/230 115/208-230 208-230 Phase Single Single Single Single Single Single Single Single Single FLA 3.1 3.9 6.2 6.5 10.1 11.3 12.4 12.0 / 6.0 12.0 Enclosure TENV ODP ODP ODP ODP ODP ODP TEFC TEFC Benefits Operates on AC power that’s converted to DC— providing a more efficient motor operation as compared to an AC operation. • The motor can attain up to 85% efficiency and reduce energy consumption. • Watt savings of 30-70% depending on RPM. Note: As motor speed is turned down, efficiency stays high as compared to an AC motor that decreases dramatically. • Operates cooler than a standard AC motor at lower • • • • • RPMs. A cooler motor has longer motor life and reduces energy consumption. 80% usable RPM turndown versus 30%, see Motor Turndown Comparison chart at right. CUE and CW fans with Vari-Green motors can provide all the CFM and static pressure ranges of a comparable belt drive. Maintenance costs are reduced as there are no belts or bearings to replace and no pulleys to adjust. Direct drive fans are often preferred where maintenance access is difficult. Provides a solution for demand controlled ventilation applications. Vari-Green Advantages • Initial cost is similar to a belt drive • Lower operating cost • No maintenance, no belts, pulleys or bearings • Easy RPM adjustment 10 1 2 Comparisons: Belt, Direct Drive with PSC and Direct Drive with Vari-Green Motor Turndown Comparison 50% 75% 100% 600 500 INPUT POWER (WATTS) HP 1/6 1/4 1/2 1/2 3/4 3/4 1 1 2 CUE-121 with PSC 400 Not recommended 300 EEnergy S Savings CUBE-121 Single Phase* 200 CUE-121 with 100 0 0 350 FAN SPEED (RPM) 1750 * CUBE is a belt driven fan The length of each curve indicates the practical turndown range. Data is for 1/2 hp motors with load of 0.35 Bhp at full speed Constant Volume Life Cycle Analysis Three Year Cost Comparison $2,000 1,750 1,500 1,250 1,000 750 500 250 $0 CUBE121 CUE121-A5 CUE121-VG Initial Cost Maintenance cost over three years Operating cost over three years Analysis is based on operating costs for a period of three years where the fans operate continuously at 1725 rpm, 24/7, with an energy rate of $0.10/kWh. Maintenance on the CUBE-121 is estimated at $65/yr. Note: Example is based on a relative cost. Use and installation variables may produce different results. Vari-Green® Control Options Vari-Green® Controls Transformer - Provides 24V power from the existing line voltage at the fan to the VariGreen motor and controls. Dual voltage primary (120/240V) transformer provided with the fan. Remote Dial - Allows for remote, manual airflow adjustments. Wall plate with dial may be mounted in a standard 2x4 inch electrical junction box. Two Speed Control with Integral Transformer Control allows motor rpm to be set at two independent speeds (high or low). Meets minimum airflow requirements with the ability to bump up to high speed in an emergency or meet maximum airflow requirements, or reset down to low for energy conservation. Constant Pressure Control – Indoor - Control Vari-Green motor via static (variable volume) or velocity (constant CFM) pressure on the inlet or outlet side of the fan. Optional, one or two, duct or room probes for use in: • Multifamily structures - Apartments, condos, hotels; dryers, residential kitchens and bathrooms. • Institutional facilities - Schools, prisons, multistory office buildings; bathrooms. Contact [email protected] for more information. Daily Operating Comparison: Variable Volume and Constant Volume % of Operation Applications requiring constant pressure or variable volume can utilize CUE or CW fans with Vari-Green motors and Vari-Green Variable Volume controls. Demand Operating Cost Analysis Variable Volume vs. Constant Volume control ventilation $ 2,000 systems reduce the amount of energy used 1,750 by decreasing the 1,500 speed of the fan when 1,250 demand is low. This in 1,000 turn lessens the amount 750 of conditioned air 500 exhausted and further 250 reduces total operating $0 costs associated with Constant Variable Volume air conditioning and Volume heating in multistoried Heating Cost Cooling Cost buildings such as Fan Operating Cost hotels, multifamily complexes, institutional Example of potential savings based on a northeast city in facilities, and high rise the USA using Vari-Green commercial buildings. components for Variable Volume. The Vari-Green constant pressure control is preprogramed and easy to install for applications that include venting dryers, bathrooms, residential type kitchen space or industrial process exhaust. Hypothetical (Hotel Bathroom) Variable Volume - Load Shape 100 80$$$$$$$$$$$$$$$$$$$$$$$$ 60$$$$$$$$$$$$$$$$$$$$$$$$ 40$$$$$$$$$$$$$$$$$$$$$$$$ 20$$$$$$$$$$$$$$$$$$$$$$$$ 0%$$$$$$$$$$$$$$$$$$$$$$$$ 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Time of Day Series 1 Demand-controlled ventilation offers significant energy savings by exhausting only the necessary amount of air throughout the day. % of Operation Demand Control Ventilation for Multistory Buildings Constant Volume - Load Shape 100 80 60 40 20 0% 1 2 3 4 Series 2 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Time of Day Note: A standard VFD compatible motor can also function within a Variable Volume system. Constant Pressure Control – Outdoor - Control a Vari-Green motor via static pressure on the inlet side of the fan. Includes one duct probe and transducer for use in: • Multifamily structures - Apartments, condos, hotels; residential kitchen, dryer facilities and bathrooms. • Institutional facilities - Schools, prisons, multistory. Air Quality – VOC - Control a Vari-Green motor via changes in volatile organic compounds (VOC’s). VOC’s are gasses that are emitted from humans, building materials, perfumes, foods, and furniture off-gassing. Range is 0-2000 CO2 PPM equivalent. • Institutional facilities – Schools, court house, hospitals; bathrooms, waiting rooms, cafeteria. • Commercial buildings – Office space, conference rooms, bathrooms, break room. Air Quality – Temperature and Humidity - Control Vari-Green motor via changes in temperature, humidity, or both. Range is 32 to 120°F and 0 to 100% relative humidity. • Multifamily structures - Apartments, condos, hotels; bathrooms, utility rooms. • Commercial buildings - Office buildings, office space, conference rooms, utility rooms, bathrooms. 11 Options and Accessories The following chart shows which options and accessories are available on Greenheck’s roof upblast and sidewall exhaust fans. Options and Accessories Roof Curbs Curb Extensions Curb Seal Windband Extension Hinged Curb Cap with Cables Hinged Base Tie-Down Points Drain Connection Grease Trap Grease Trap with Absorbent Material Clean-Out Port Birdscreen Non-Stick Wheel Disconnect Switches Dampers CUBE CUE 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 Speed Controllers Motor Starters UL 705 UL 762 UL Emergency Smoke Control Systems Coatings 9 9 9 CWB CW Windband Extension — Aluminum tube raising the fan discharge an additional 36-inches (914 mm). USGF 9 9 9 9 std. 9 9 9 9 std. 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 Curb Extensions — Mounts between roof curb and fan for additional height from roof top. Vented Curb Extensions — Mounts between roof curb and roof mounted fan to meet NFPA requirements of 40-inch (1016 mm) minimum discharge above the roof when mounted on a minimum 8-inch (203 mm) high roof curb. Curb Seal — Rubber seal between fan and curb to assure proper sealing when attached to a curb. cap allows the entire fan to swing open to allow maintenance personnel access to the wheel and ductwork for regular inspection and cleaning. Hinged curb cap kit with cables is an option on all upblast models. Hinged Base — Available on sizes up to 540, allows for easy maintenance. Hinge and restraining cables are factory-mounted to a sub-base attached directly to curb without additional height added. Mounted hinged base with cables standard on all USGF fans. 9 Tie-Down Points — Four std. brackets located on the windband for securing the fan in heavy wind applications. 9 Roof Curbs — Wide variety of roof curbs are available for mounting the fan to the roof, including: vented, flanged, pitched and soundabsorbing. For more information on severe duty curbs refer to the information on page 9. 12 std. Hinged Curb Cap Kit with Cables — The hinged curb 9 Drain Connection — Allows for single-point drainage of grease, water or other residues. Grease Trap — Polypropylene trap designed to collect grease residue to avoid drainage onto roof surface. Grease Trap with Absorbent Material — Same as above with an absorbent material to collect grease residue for easy disposal. Clean-Out Port — Patented removable plug allows for easy spray or steam cleaning of wheel through the windband. Available on select models. Options and Accessories Birdscreen — Galvanized or aluminum rigid wire to protect the fan discharge from birds or small objects. Galvanized is standard on CWB and CW models. Non-Stick Aluminum Wheel — Patented coating helps prevent wheel imbalance in heavy grease applications and allows buildup on wheel to be easily removed. Disconnect Switches — Assorted NEMA rated switches are available for positive electrical shutoff and safety, including: dust-tight, rainproof and corrosion-resistant. Dampers — Designed to prevent outside air from entering back into the building when fan is off. Includes backdraft and motorized dampers. (Not available with UL/cUL 762 or USGF fans). Speed Controllers — Available for use with shaded pole and permanent split capacitor open motors on direct drive fans. They provide an economical means of system balancing. Motor Starters — The fundamental function of a motor starter is to protect the motor from damage that can occur from overheating. With a Greenheck motor starter you will be provided with the best motor protection available. UL/cUL 705 — Models CUBE, CUE, CWB and CW, may be UL Listed for Electrical. CUBE for Smoke Control comes standard with UL 705. UL/cUL 762 — Models CUBE, CWB and CUE and CW sizes 099 and larger, may be Listed for Grease Removal. Model USGF comes standard with UL 762. UL/cUL Emergency Smoke Control — Models CUBE and USGF may be Listed for Emergency Smoke Control. Note: Model sizes CUBE-099, 161XP, 240XP, 300HP & 300XP are excluded for Emergency Smoke Control. Coatings – Wide variety of coatings and colors are available for decorative to protective applications. Primer is applied at the factory to allow PRIMER for final finish in the field. Not available on model USGF. Permatector™ is our standard coating PERMATECTORTM HI-PRO POLYESTER on steel fans and is typically used for applications that require corrosion resistance in indoor and outdoor environments. Hi-Pro Polyester is resistant to salt water, chemical fumes and moisture in more corrosive atmospheres. Typically used for applications that require superior chemical resistance, excellent abrasion and outdoor UV protection. This coating exceeds protective qualities of Air Dried Heresite and Air Dry Phenolic. Baked Enamel Decorative Coatings are heat cured enamels applied either as wet paints or electrostatic powders. Customers can choose from 16 standard decorative colors or color match any color. Note: Colors are subject to change. See Performance Coatings for Commercial & Industrial Fans catalog for more details. Specific model components may include; SmartStart™ technology, physical interface, overload protection, disconnect, magnetic contactor, NEMA-1 or NEMA-3R steel enclosures and pre-engineered easy system integration. For complete information on specific Greenheck Motor Starter models refer to greenheck.com, Motor Starter web page. 13 Typical Installations by Application General Clean Air/Fume Hood (Non Grease) All CUBE, CUE, CWB and CW exhaust fans are designed for applications ranging from clean air to contaminated air. A typical installation is shown. When roofing materials extend to the top of the curb, roof curbs should be 1½-inches (¾-inch on a side) less than the unit curb cap to allow for roofing and flashing. • For recommended duct size, damper size and roof opening dimensions, refer to the performance data pages. • Installation must include a means for inspecting, cleaning and servicing the exhaust fan. Factory Wired Motor to Disconnect Wall Damper 8 or 12 in. (203 to 305 mm) Wiring by Others Damper Mounting Bolt Hole Circle Recommended Duct and Damper Size Recommended Wall Opening Roof Deck Recommended Duct and Damper Size Wiring by others Factory Wired Motor to Disconnect Recommended Roof Opening Models CUBE and CUE Models CWB and CW Emergency Smoke Control • Installation must include a means for inspecting, The CUBE with smoke option and the USGF are specifically designed for Emergency Smoke Control applications. These fans are UL/cUL Listed for Electrical and Power Ventilators for Smoke Control Systems for 500°F (260°C) for 4 hours and 1,000°F (538°C) for 15 minutes. • Exhaust fans used in emergency smoke cleaning and servicing the exhaust fan. applications must have external wiring. (Wiring must not be installed in the airstream). Factory Installed Heat Baffle NEMA-3R Disconnect factory wired from motor to disconnect through the breather tube • Due to the varying airstreams encountered in commercial ventilation, system designers must be aware of national, state, and local codes and guidelines governing these installations. Local code authorities should be consulted before proceeding with any ventilation project. Liquid Tight Flexible Conduit by Others • When roofing materials extend to the top of the curb, roof curbs should be 1½-inches (¾-inch on a side) less than the unit curb cap to allow for roofing and flashing. • For recommended duct size, damper size and Minimum 8 in. (203 mm) Roof Deck roof opening dimensions, refer to the performance data pages. Recommended Roof Opening Models CUBE and USGF 14 Typical Installations by Application Commercial Kitchen (Grease) Models CUBE, CWB, USGF and models CUE and CW sizes 099 and larger, are designed to meet restaurant and food service applications. These fans are UL/cUL Listed for Grease Removal and have been tested under high temperature [400°F (204°C)] and abnormal flare-up [600°F (316°C)] conditions. Wall Mounting Bolt Hole Circle Recommended Roof Opening Welded Duct by Others • Due to high temperatures and grease-laden airstreams in commercial kitchen ventilation, system designers must be aware of governing codes and guidelines. The National Fire Protection Association (NFPA) is the primary source which governs many codes for commercial kitchen ventilation. Selected information from NFPA 96 is shown below. Local code authorities should be consulted before proceeding with any kitchen ventilation project. • Exhaust fans used in kitchen ventilation applications must have external wiring. (Wiring must not be installed in the airstream). • Installation must include a means for inspecting, cleaning and servicing the exhaust fan. Greenheck offers a Hinged Curb Cap option for upblast exhaust fans and the Hinged Base is standard on model USGF. • No dampers are to be installed in the system. Note: • The typical installations shown on these two pages are recommendations based on national codes. Local authority may supersede these recommendations. Models CWB & CW • Drawing shows NEMA 1 Standard, NEMA 3R is optional. External Wiring Liquid Tight Flexible Conduit by Others NEMA-3R Disconnect factory wired from motor to disconnect through the breather tube (Optional) Minimum 40 in. (1016 mm) Discharge Height Grease Trap Welded Duct by others. Minimum of 18 in. (457 mm) above roof deck per NFPA Roof Deck NEMA-3R Disconnect factory wired from motor to disconnect through the breather tube (Optional) Minimum 40 in. (1016 mm) Discharge Height Vented Curb Extension 18 in. (457 mm) Minimum Height External Wiring Liquid Tight Flexible Conduit By Others Grease Trap Welded Duct by others. Minimum of 18 in. ( 457 mm) above roof deck per NFPA 24 in. (610 mm) Minimum Curb Height External Wiring Liquid Tight Flexible Conduit by Others Roof Deck Recommended Roof Opening Models CUBE & CUE Vented Installation Recommended Roof Opening Models CUBE & CUE Non-Vented Installation 15 Model Number Code Performance & Dimensions Quick Reference 131 • • 18 • 18 • 19 • 19 • 20 • 21 • 22 • 23 • 24 • 25 • 26 • 140 27 141 27 140HP 28 141HP 28 160 29 161 29 160HP 30 161HP 30 160XP 31 161XP 31 180 32 180HP 33 060 CUBE Smoke USGF Option 17 070 075 080 085 090 095 099 101 101HP 121 200 0.051 0.051 (1.3) (1.3) (1.3) 0.051 0.051 0.064 (1.3) (1.3) (1.6) 34 Configuration CUBE - Belt Drive Roof Mounted x CUE - Direct Drive Roof Mounted x CWB - Belt Drive Wall Mounted x • • (Belt Drive Only) VG = Vari-Green® (Direct Drive Only) • x x x x x 37 x 38 x 240HP 39 x 240XP 40 300 41 300HP 42 x 0.064 Motor HP (1.6) 0.040 0.064 (1.0) (1.6) 0.064 0.051 0.064 (1.6) (1.3) (1.6) 0.080 0.051 0.064 (2.0) (1.3) (1.6) x USGF 0.051 4 3 5 7 = = = = 1/4 1/3 1/2 3/4 (Belt Drive Only) 10 = 1 15 = 1½ 20 = 2 30 = 3 50 = 5 75 = 7½ (1.3) 60 HZ Motor RPM x CUBE only 46 HP - High-Pressure XP - Extended High-Pressure x 240 45 Wheel Pressure Level x 220HP 360XP (1.6) x x 360HP 0.064 (1.0) x x 44 0.040 (1.3) x 35 43 0.051 x 36 360 USGF - Belt Drive Roof Mounted x 220 300XP CW - Direct Drive Wall Mounted x • 060 through 480 x x • CUBE - 240 HP - VG/5/A X Fan Size 200HP 16 0.051 17 065 • Curb Caps CUE CW Motor Cover Model CUBE Size CWB Material Thickness Windband Page Index The Model number system is designed to completely identify the fan. The correct code letters must be specified to designate belt or direct drive. The remainder of the model number is determined by the size and performance. A = 1725 B = 1140 C = 860 (Direct Drive Only) D = 1550 E = 1050 G = 1300 50 HZ Motor RPM (Direct Drive Only) International (See CAPS for performance) x 0.080 0.064 0.080 (2.0) (1.6) (2.0) 420 47 x 0.080 0.064 0.100 480 48 x (2.0) (1.6) (2.5) Vari-Green option available on direct drive models K = 950 RPM L = 1290 RPM J = 1425 RPM X = UL 705 F = UL Smoke Control Systems G = UL 762 Roof Upblast/Sidewall Exhaust Size-060 and 065: CUE • CW 0.6 183⁄8 Direct Drive RPM (467) RPM (Direct) RPM (Vari Green) Density 0.075 lb/ft Density 1.2 lb/ft 140 E-1050 RPM 120 (432) 40 0.3 0.2 CUE CW 0.1 20 0 065 -D 06 0- D THE LEFT OF 60 0.4 DO NO TS ELE CT TO 1¾ (44) 80 Static Pressure (in. wg) (289) 100 Static Pressure (Pa) VG-1725 RPM G VG (343) 113⁄8 5-V 0- *13 ⁄2 06 06 D-1550 RPM 1 17 THIS SYST EM C URVE 0.5 G-1300 RPM 06 5-G 06 0- G 065 06 -E 0- E 0.0 0 50 100 150 113⁄4 200 250 300 Volume (CFM) (298) 183⁄8 (467) 14 ⁄4 3 0 100 200 300 400 500 3 (375) Volume (m /hr) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *131⁄2 (343) Motor HP Direct Fan RPM CUE CW ^Approximate Weight 29 (13) Damper Size 8 x 8 (203 x 203) Roof/Wall Opening 10½ x 10½ (267 x 267) Static Pressure in Inches wg 0.125 0.15 0.2 0.25 0 0.05 0.1 133 0.01 1.7 165 0.01 2.9 197 0.02 4.3 219 0.028 5.4 113 0.01 1.7 148 0.01 2.6 183 0.02 3.9 207 0.028 5 94 0.01 1.7 134 0.01 2.5 169 0.02 3.9 194 0.028 5.1 81 0.01 1.7 126 0.01 2.5 164 0.02 3.9 188 0.028 5.2 65 0.01 1.7 117 0.01 2.5 158 0.02 3.9 183 0.028 5.2 96 0.01 2.5 143 0.02 4.0 172 0.028 5.2 180 0.01 2.2 223 0.02 3.2 266 0.03 4.9 296 0.036 6.4 154 0.01 2.1 202 0.02 3.2 249 0.03 4.2 280 0.037 5.1 126 0.01 1.9 181 0.02 3.1 231 0.03 4.2 265 0.037 5.1 109 0.01 2.0 170 0.02 3.1 222 0.03 4.2 257 0.038 5.1 89 0.01 2.1 158 0.02 3.1 214 0.03 4.2 249 0.038 5.1 129 0.02 3.0 194 0.03 4.1 233 0.039 5 26 (12) 8 x 8 (203 x 203) 8½ x 8½ (216 X 216) 0.3 0.35 0.375 70 0.01 2.5 128 0.02 4.0 159 0.028 5.3 107 0.02 4.0 146 0.029 5.3 85 0.02 4.0 137 0.029 5.4 118 0.029 5.5 97 0.02 2.9 172 0.03 4.1 215 0.039 5 145 0.03 4.0 196 0.039 5 119 0.03 4.0 184 0.038 5 95 0.03 3.9 160 0.037 4.9 060 CFM BHP Sones CFM G-1/100 1300 BHP Sones CFM D-1/60 1550 BHP Sones CFM 1725 BHP Sones 065 CFM VG- E-1/100 1050 BHP 1/6 Sones CFM G-1/60 1300 BHP Sones CFM D-1/30 1550 BHP Sones CFM 1725 BHP Sones VG1/6 E-1/200 1050 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 17 Roof Upblast/Sidewall Exhaust Size-070 and 075: CUE • CW 183⁄8 0.6 Direct Drive RPM (467) E-1050 RPM 07 120 (432) 60 40 0.3 0.2 CUE 0.1 CW 20 0 0.0 0 5-V G 07 0-V G 07 5-D 07 0-D THE LEFT OF 1¾ (44) 80 0.4 07 5 070 -G -G DO NO TS ELE CT T O 113⁄8 (289) 100 Static Pressure (Pa) VG-1725 RPM Static Pressure (in. wg) D-1550 RPM (343) 17 THIS S YSTEM CURVE 0.5 G-1300 RPM *131⁄2 RPM (Direct) RPM (Vari Green) Density 0.075 lb/ft Density 1.2 lb/ft 140 0 07075-E -E 100 200 300 400 500 Volume (CFM) 11 ⁄4 3 (298) 183⁄8 0 (467) 143⁄4 200 400 600 800 Volume (m 3/hr) (375) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *131⁄2 (343) Motor HP Direct Fan RPM CUE CW ^Approximate Weight 29 (13) Damper Size 8 x 8 (203 x 203) Roof/Wall Opening 10½ x 10½ (267 x 267) Static Pressure in Inches wg 0.125 0.15 0.2 0.25 0 0.05 0.1 CFM BHP Sones CFM 1300 BHP Sones CFM 1550 BHP Sones CFM 1725 BHP Sones 250 0.01 2.7 309 0.01 4.1 369 0.02 5.6 411 0.032 6.8 224 0.01 2.1 288 0.01 3.8 351 0.02 5.4 395 0.032 6.7 193 0.01 1.7 267 0.02 3.4 333 0.03 5.2 379 0.033 6.7 171 0.01 1.4 255 0.02 3.3 325 0.03 5.2 371 0.034 6.6 143 0.01 1.1 241 0.02 3.2 316 0.03 5.1 363 0.035 6.6 205 0.02 2.8 293 0.03 4.9 346 0.036 6.5 CFM BHP Sones CFM 1300 BHP Sones CFM 1550 BHP Sones CFM 1725 BHP Sones 287 0.01 3.6 356 0.02 4.1 424 0.04 6.1 472 0.054 8 249 0.01 3 324 0.02 3.9 398 0.04 5.8 448 0.054 7.5 210 0.01 2.8 294 0.02 3.7 372 0.04 5.5 424 0.054 7.1 188 0.01 2.7 279 0.02 3.7 359 0.04 5.4 413 0.054 7 165 0.01 2.6 262 0.02 3.7 347 0.04 5.3 402 0.054 6.8 227 0.02 3.6 320 0.04 5 380 0.055 6.4 26 (12) 8 x 8 (203 x 203) 8½ x 8½ (216 X 216) 0.3 0.35 0.375 152 0.01 2.5 269 0.03 4.7 326 0.036 6.4 234 0.03 4.5 305 0.036 6.2 187 0.02 4.1 289 0.035 6.1 160 0.02 3.9 258 0.035 5.9 185 0.02 3.4 291 0.04 4.9 355 0.055 6.1 261 0.04 4.9 329 0.054 6 225 0.04 4.8 308 0.053 6 204 0.04 4.8 289 0.052 6 070 VG1/6 E-1/100 1050 G-1/60 D-1/30 075 VG1/6 E-1/40 G-1/30 D-1/20 1050 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 18 Roof Upblast/Sidewall Exhaust Size-080 and 085: CUE • CW 21 Direct Drive RPM 220 E-1050 RPM 200 G-1300 RPM 180 0.9 (533) CUE CW 80 60 0.4 0.3 0.2 40 20 0 5-V G 08 0- 0.1 VG 5-D 08 08 0- D THE LEFT OF (483) 100 0.5 08 5-G 08 0- TO 1¾ (44) 19 120 0.6 G 085 08 -E 0E NO TS ELE CT (292) 140 08 DO VG-1725 RPM Static Pressure (in. wg) (340) 111⁄2 0.7 160 Static Pressure (Pa) *133⁄8 THIS SYST EM C URVE D-1550 RPM RPM (Direct) RPM (Vari Green) 3 Density 0.075 lb/ft 3 Density 1.2 lb/ft 0.8 0.0 0 100 200 300 15 400 500 600 Volume (cfm) (381) 21 (533) 177⁄8 0 100 200 300 400 500 600 3 700 800 900 1000 1100 Volume (m /hr) (454) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *133⁄8 (340) Motor HP Direct Fan RPM CUE CW ^Approximate Weight 40 (18) Damper Size 10 x 10 (254 x 254) Roof/Wall Opening 12½ x 12½ (318 x 318) 40 (18) 10 x 10 (254 x 254) 10½ x 10½ (267 X 267) 0 0.1 0.125 Static Pressure in Inches wg 0.15 0.2 0.25 0.3 0.375 0.5 0.625 325 0.01 3.8 403 0.02 5.4 480 0.04 7.3 534 0.05 8.4 265 0.01 3.7 356 0.03 5.4 441 0.04 7.3 500 0.06 8.5 247 0.02 3.6 343 0.03 5.4 431 0.04 7.3 491 0.06 8.5 230 0.02 3.7 330 0.03 5.4 421 0.04 7.3 481 0.06 8.5 189 0.02 3.9 302 0.03 5.4 400 0.05 7.3 463 0.06 8.6 133 0.02 4.2 272 0.03 5.5 376 0.05 7.2 444 0.06 8.6 239 0.03 5.6 352 0.05 7.2 423 0.07 8.6 173 0.03 5.9 314 0.05 7.3 390 0.07 8.5 235 0.05 7.5 333 0.07 8.7 257 0.07 8.7 389 0.01 4.0 481 0.02 5.5 574 0.04 7.6 639 0.06 8.7 323 0.02 3.9 430 0.03 5.3 532 0.04 7.4 601 0.06 8.7 305 0.02 3.9 416 0.03 5.3 520 0.05 7.4 591 0.06 8.6 286 0.02 3.9 402 0.03 5.3 509 0.05 7.4 581 0.06 8.6 242 0.02 4.0 373 0.03 5.3 486 0.05 7.4 560 0.07 8.6 182 0.02 4.3 340 0.03 5.3 461 0.05 7.4 540 0.07 8.6 305 0.04 5.4 437 0.06 7.4 518 0.07 8.6 235 0.04 5.5 395 0.06 7.4 484 0.08 8.7 312 0.06 7.5 421 0.08 8.8 161 0.05 8.1 344 0.08 8.9 080 CFM BHP Sones CFM G-1/30 1300 BHP Sones CFM D-1/20 1550 BHP Sones CFM 1725 BHP Sones 085 CFM VG- E-1/40 1050 BHP 1/6 Sones CFM G-1/30 1300 BHP Sones CFM D-1/20 1550 BHP Sones CFM 1725 BHP Sones VG1/6 E-1/40 1050 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 19 Roof Upblast/Sidewall Exhaust Size-090: CUE • CW 1.0 21 Direct Drive RPM RPM (Direct) RPM (Vari-Green) 3 Density 0.075 lb/ft 3 Density 1.2 lb/ft (533) G-1300 RPM 100 0.4 CUE 50 0.2 0 0.0 09 0- VG 09 0- D THE LEFT OF 1¾ (44) 19 (483) 0.6 NO TS ELE CT T O (292) 150 Static Pressure (in. wg) VG-1725 RPM Static Pressure (Pa) *13 ⁄8 111⁄2 0.8 D-1550 RPM 3 (340) 200 THIS S YSTEM CURVE E-1050 RPM 0-G 09 0-E DO CW 09 0 200 400 15 600 800 1000 1200 Volume (cfm) (381) 21 (533) 17 ⁄8 7 0 500 1000 1500 2000 3 Volume (m /hr) (454) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *133⁄8 (340) Motor HP Direct Fan RPM CUE CW ^Approximate Weight 40 (18) Damper Size 10 x 10 (254 x 254) Roof/Wall Opening 12½ x 12½ (318 x 318) 40 (18) 10 x 10 (254 x 254) 10½ x 10½ (267 X 267) 0 0.1 0.125 Static Pressure in Inches wg 0.15 0.2 0.25 0.3 0.375 0.5 0.625 549 0.02 4.0 680 0.04 5.4 811 0.06 7.6 903 0.08 8.8 470 0.02 3.9 616 0.04 5.4 757 0.07 7.5 854 0.09 8.8 451 0.02 3.9 600 0.04 5.4 744 0.07 7.5 842 0.09 8.8 429 0.03 4.0 584 0.04 5.4 731 0.07 7.5 830 0.09 8.8 204 0.03 4.5 479 0.05 5.5 651 0.08 7.4 758 0.1 8.7 391 0.05 5.6 604 0.08 7.4 722 0.11 8.7 501 0.09 7.4 652 0.12 8.8 347 0.08 7.9 553 0.12 8.9 090 VG1/6 CFM BHP Sones CFM G-1/30 1300 BHP Sones CFM D-1/20 1550 BHP Sones CFM 1725 BHP Sones E-1/40 1050 381 0.03 4.1 553 0.05 5.4 704 0.07 7.5 806 0.1 8.8 306 0.03 4.2 517 0.05 5.5 677 0.08 7.5 782 0.1 8.8 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 20 Roof Upblast/Sidewall Exhaust Size-095: CUE • CW 1.0 21 Direct Drive RPM RPM (Direct) RPM (Vari-Green) 3 Density 0.075 lb/ft 3 Density 1.2 lb/ft (533) 0.8 (292) 1¾ (44) (483) 150 100 5- 0.6 0.4 CUE 50 0.2 0 0.0 09 THIS S VG-1725 RPM 111⁄2 09 D 095 -G 095 -E DO CW VG 5- NO TS ELE CT T O TH E LEF T OF (340) Static Pressure (in. wg) *13 ⁄8 Static Pressure (Pa) D-1550 RPM 3 19 200 YSTEM G-1300 RPM CURVE E-1050 RPM 0 200 400 15 600 800 1000 1200 Volume (cfm) (381) 21 (533) 17 ⁄8 7 0 500 1000 1500 2000 3 Volume (m /hr) (454) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *133⁄8 (340) Motor HP Direct Fan RPM CUE CW ^Approximate Weight 40 (18) Damper Size 10 x 10 (254 x 254) Roof/Wall Opening 12½ x 12½ (318 x 318) 40 (18) 10 x 10 (254 x 254) 10½ x 10½ (267 X 267) 0 0.1 0.125 Static Pressure in Inches wg 0.15 0.2 0.25 0.3 0.375 0.5 0.625 711 0.03 5.4 880 0.06 7.6 1049 0.1 9.6 1167 0.14 11.3 603 0.04 4.5 797 0.07 6.9 983 0.11 9.4 1108 0.15 11.1 570 0.04 4.5 774 0.07 6.7 964 0.11 9.3 1093 0.15 11.0 536 0.04 4.5 750 0.07 6.6 944 0.11 9.2 1077 0.15 11.0 265 0.03 4.6 587 0.07 6.4 816 0.12 8.4 967 0.16 10.2 484 0.07 6.4 747 0.12 8.3 905 0.17 9.9 199 0.05 6.8 616 0.12 8.1 802 0.17 9.8 442 0.11 7.8 680 0.17 9.6 095 VG1/6 CFM BHP Sones CFM G-1/12 1300 BHP Sones CFM D-1/8 1550 BHP Sones CFM 1725 BHP Sones E-1/30 1050 468 0.04 4.4 696 0.07 6.5 905 0.11 8.9 1041 0.16 10.8 381 0.04 4.5 641 0.07 6.4 861 0.12 8.6 1005 0.16 10.5 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 21 Roof Upblast/Sidewall Exhaust Size-099: CUBE • CUE • CWB • CW 247⁄8 Direct Drive RPM (632) 250 1.0 099-A CUR VE B-1140 RPM 100 SYS TEM 0.6 099-B 0.4 099-C CUBE • CUE 50 86 0.2 0 0.0 0 11 56 8 0 74 4 200 400 167⁄8 600 800 1000 1200 1400 Volume (cfm) (429) 247⁄8 0 (632) 19 ⁄4 3 500 1000 1500 2000 3 Volume (m /hr) (502) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *281⁄4 (718) Belt 40 10 95 DO CWB • CW NO TS EL EC TT OT HE LEF TO FT HIS (483) Static Pressure (in. wg) 19 150 0.8 36 13 1¾ (44) 200 32 15 (441) 25 VG-1725 RPM 17 (718) 173⁄8 Static Pressure (Pa) A-1725 RPM *281⁄4 RPM (Belt) RPM (Direct) RPM (Vari-Green) HP Density 0.075 lb/ft 3 Density 1.2 kg/m 3 HP 1.2 4 1/ 300 C-860 RPM Motor HP Direct Fan RPM 0 0.125 543 0.02 4.5 628 0.03 5.3 700 0.04 6.1 771 0.05 7.1 833 0.06 7.8 904 0.08 8.8 976 0.10 9.9 1047 0.13 10.8 1119 0.15 11.9 1191 0.19 13.0 1260 0.22 14.2 414 0.02 4.0 518 0.03 4.7 603 0.04 5.4 685 0.06 6.2 754 0.07 7.0 832 0.09 8.1 909 0.11 9.4 986 0.13 10.4 1062 0.16 11.4 1137 0.19 12.6 1209 0.23 13.8 0.25 CUBE ^Approximate Weight Damper Size Roof/Wall Opening CUE CWB 58 (26) 53 (24) 12 x 12 (305 x 305) 14½ x 14½ (368 x 368) Static Pressure in Inches wg 0.375 0.5 0.625 0.75 CW 58 (26) 53 (24) 12 x 12 (305 x 305) 12½ x 12½ (318 X 318) 0.875 1 1.125 099 744 VG1/4 C-1/8 860 958 1056 B-1/6 1140 1238 1/4 1336 1434 1532 1630 A-1/4 1725 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 376 0.03 4.3 490 0.04 4.9 588 0.06 5.7 665 0.07 6.3 752 0.09 7.2 837 0.11 8.5 920 0.14 9.7 1001 0.17 10.9 1080 0.20 12.1 1156 0.23 13.4 MAXIMUM BHP AT A GIVEN RPM = (RPM/3099)3 MAXIMUM RPM = 1725 TIP SPEED (ft/min) = RPM x 2.846 MAXIMUM MOTOR FRAME SIZE = 56 AVERAGE DISCHARGE VELOCITY (FPM) = CFM/1.28 464 0.06 5.3 565 0.07 5.9 668 0.09 6.7 760 0.12 7.6 848 0.14 8.8 935 0.17 10.0 1020 0.21 11.4 1100 0.24 12.9 408 0.07 5.5 559 0.09 6.4 674 0.12 7.3 776 0.14 8.3 868 0.18 9.4 956 0.21 10.8 1041 0.25 12.3 564 0.11 6.9 687 0.14 8.0 794 0.18 9.1 893 0.21 10.4 981 0.25 11.7 567 0.14 7.6 705 0.17 8.8 818 0.21 10.1 918 0.25 11.5 583 0.16 8.4 730 0.21 9.8 846 0.25 11.2 609 0.20 9.4 759 0.24 10.8 639 0.23 10.6 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 22 Roof Upblast/Sidewall Exhaust Size-101: CUBE • CUE • CWB • CW 247⁄8 1.4 Direct Drive RPM 4 1.2 FT HIS SY STE MC 0.4 CUBE • CUE 50 0.2 0 0.0 NO T 101-C CWB • CW TH EL EF TO 101-B TO 100 0.6 SE LE CT Static Pressure (Pa) (483) 150 0.8 48 14 1¾ (44) 200 11 4 0 86 0 DO 0 200 400 600 167⁄8 800 1000 1200 1400 1600 Volume (cfm) (429) 247⁄8 0 (632) 19 ⁄4 3 500 1000 1500 2000 2500 3 Volume (m /hr) (502) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *281⁄4 (718) Belt 20 0 25 17 166 17 ⁄8 (441) 1.0 UR VE 250 VG-1725 RPM 18 (718) Static Pressure (in. wg) *28 ⁄4 19 101-A A-1725 RPM RPM (Belt) RPM (Direct) RPM (Vari-Green) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m HP 300 B-1140 RPM 3 H P C-860 RPM 1 3 1/ 1/ (632) Motor HP Direct Fan RPM 0 0.125 0.25 732 0.03 4.6 811 0.041 5.5 890 0.054 6.5 970 0.07 7.2 1066 0.092 8 1149 0.12 8.9 1233 0.14 10.3 1316 0.17 11.8 1413 0.22 12.7 1468 0.24 13.3 1549 0.28 14.3 625 0.035 2.1 717 0.047 4.2 807 0.061 6.2 897 0.078 7 1000 0.1 8 1089 0.13 8.9 1176 0.15 10.2 1264 0.19 11.5 1365 0.23 12.3 1422 0.26 12.9 1505 0.3 13.7 481 0.036 1.3 603 0.05 3.1 707 0.066 5.6 806 0.084 6.5 920 0.11 7.6 1016 0.13 8.6 1112 0.16 9.9 1206 0.2 11.3 1313 0.24 12 1373 0.27 12.5 1459 0.31 13.4 CUBE ^Approximate Weight Damper Size Roof/Wall Opening CUE CWB 58 (26) 53 (24) 12 x 12 (305 x 305) 14½ x 14½ (368 x 368) Static Pressure in Inches wg 0.375 0.5 0.625 0.75 CW 58 (26) 53 (24) 12 x 12 (305 x 305) 12½ x 12½ (318 X 318) 0.875 1 1.125 101 C-1/8 VG1/4 860 953 1046 B-1/6 1140 1252 1/4 1350 1448 1546 1660 A-1/4 1725 1/3 1820 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 577 0.065 5.4 707 0.085 6 834 0.11 6.9 940 0.14 8.1 1040 0.17 9.5 1139 0.2 10.9 1251 0.25 11.6 1315 0.28 12 1406 0.32 12.7 MAXIMUM BHP AT A GIVEN RPM = (RPM/3099)3 MAXIMUM RPM = 1820 TIP SPEED (ft/min) = RPM x 2.846 MAXIMUM MOTOR FRAME SIZE = 56 AVERAGE DISCHARGE VELOCITY (FPM) = CFM/1.28 411 0.067 5.5 732 0.11 6.5 856 0.14 7.5 966 0.17 9 1072 0.21 10.5 1189 0.26 11.3 1255 0.29 11.7 1350 0.33 12.4 745 0.14 7 886 0.17 8.3 999 0.21 9.8 1125 0.26 10.8 1195 0.29 11.3 1293 0.34 12 763 0.17 8 915 0.21 9.3 1056 0.26 10.2 1129 0.29 10.8 1234 0.35 11.6 793 0.23 8.9 974 0.26 9.6 1062 0.29 10.2 1171 0.35 11.2 861 0.25 9.4 970 0.29 9.7 1106 0.35 10.6 900 0.33 10.1 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 23 Roof Upblast/Sidewall Exhaust Size-101HP: CUBE • CUE • CWB • CW 247⁄8 1/2 Direct Drive RPM (632) 2.5 500 (483) 200 THIS 1.5 1.0 CUBE • CUE 50 20 45 17 80 15 0.5 100 40 13 00 DO CWB • CW 00 22 LEF T OF 300 RPM (Belt) RPM (Vari-Green) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m 25 T HE 1¾ (44) 400 HP TO (441) 1/4 NO TS ELE CT Static Pressure (Pa) 17 ⁄8 3 2.0 HP HP 80 25 (718) Static Pressure (in. wg) *281⁄4 19 1/3 CURV E 600 SYST EM VG-2500 RPM 0 0.0 0 200 400 16 ⁄8 7 600 800 1000 Volume (cfm) (429) 247⁄8 0 (632) 193⁄4 500 1000 1500 3 Volume (m /hr) (502) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *281⁄4 (718) Motor HP Belt Direct Fan RPM 0.5 0.625 335 0.067 6 419 0.088 6.8 491 0.11 7.8 560 0.14 8.9 627 0.17 10.3 688 0.2 12.1 761 0.24 13.9 812 0.28 14.1 860 0.32 14.4 977 0.44 15.9 1014 0.48 16.8 182 0.056 6.3 350 0.088 6.6 438 0.11 7.5 512 0.14 8.6 583 0.17 9.9 651 0.21 11.4 729 0.26 13.5 782 0.29 14.1 832 0.33 14.4 954 0.44 15.6 992 0.48 16.4 0.75 CUBE ^Approximate Weight Damper Size Roof/Wall Opening CUE 58 (26) 53 (24) 12 x 12 (305 x 305) 14½ x 14½ (368 x 368) Static Pressure in Inches wg 1 1.25 1.5 1.75 2 CWB CW 58 (26) 53 (24) 12 x 12 (305 x 305) 12½ x 12½ (318 X 318) 2.25 2.5 101HP 1300 VG1/2 1420 1540 1/4 1660 1780 1900 2045 2150 1/3 2250 2500 1/2 2580 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP 191 0.073 6.9 371 0.11 7.3 461 0.14 8.4 538 0.17 9.6 610 0.21 11 693 0.26 12.7 752 0.3 13.5 804 0.34 14.2 929 0.45 15.3 969 0.49 16 MAXIMUM BHP AT A GIVEN RPM = (RPM/3195)3 MAXIMUM RPM = 2580 TIP SPEED (ft/min) = RPM x 2.913 MAXIMUM MOTOR FRAME SIZE = 56 AVERAGE DISCHARGE VELOCITY (FPM) = CFM/1.28 262 0.12 8.3 430 0.17 9.1 520 0.21 10.5 615 0.26 12.1 678 0.3 12.5 737 0.35 13.2 878 0.48 15 919 0.52 15.7 382 0.19 10.2 522 0.26 11.5 600 0.3 12 665 0.35 12.5 815 0.48 14.4 861 0.53 15.1 346 0.23 11.4 500 0.3 11.5 579 0.35 11.9 750 0.48 13.6 799 0.53 14.4 456 0.32 11.6 677 0.48 12.9 735 0.53 13.7 595 0.48 12.5 655 0.53 13.2 414 0.42 12.2 550 0.49 12.9 323 0.43 12.5 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 24 Roof Upblast/Sidewall Exhaust Size-121: CUBE • CUE • CWB • CW 247⁄8 1.8 Direct Drive RPM (632) (441) 121-C T CWB • CW 0.4 50 0 0.2 0.0 0 NO 68 400 600 DO 200 10 0 4 800 1000 1200 1400 1600 1800 2000 Volume (cfm) 167⁄8 (429) 247⁄8 0 (632) 19 ⁄4 3 500 1000 1500 2000 2500 3000 3500 3 Volume (m /hr) (502) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *281⁄4 (718) Belt 00 86 25 17 100 121-B 0.6 45 150 0.8 P 15 CUBE • CUE 200 1.0 H 50 12 40 11 (483) 250 1.2 3 10 14 1¾ (44) 19 300 SE LE CT TO VG-1725 RPM Static Pressure (in. wg) (718) 173⁄8 Static Pressure (Pa) *28 ⁄4 P 1/6 H A-1725 RPM 1 1/ CU RVE 1.4 121-A TH EL EF TO FT HIS SY STE M 350 B-1140 RPM RPM (Belt) RPM (Direct) RPM (Vari-Green) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m HP 1.6 HP 1/4 400 2 1/ C-860 RPM Motor HP Direct Fan RPM 0 0.125 808 0.02 4.4 912 0.04 4.8 1015 0.05 5.3 1181 0.08 6.2 1346 0.11 7.4 1476 0.15 8.8 1665 0.21 11.1 1748 0.25 11.9 1824 0.28 12.8 1931 0.33 14.1 2037 0.39 15.6 669 0.03 4.4 789 0.04 5 905 0.05 5.7 1084 0.08 6.6 1261 0.12 7.9 1397 0.16 9.3 1595 0.22 11.6 1681 0.26 12.4 1760 0.29 13.4 1870 0.34 14.7 1979 0.40 16.1 0.25 CUBE ^Approximate Weight Damper Size Damper Frame Size Roof/Wall Opening CUE CWB 66 (30) 64 (29) 12 x 12 (305 x 305) N/A 14½ x 14½ (368 x 368) Static Pressure in Inches wg 0.375 0.5 0.625 0.75 CW 66 (30)) 53 (24) 12 x 12 (305 x 305) 14 x 14 (356 x 356) 12½ x 12½ (318 X 318) 1 1.25 1.5 121 684 VG1/2 772 C-1/8 860 1000 1/4 B-1/6 1140 1250 1410 1480 1/3 1545 1635 1/2 A-1/2 1725 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP 630 0.043 5.1 781 0.06 5.6 993 0.09 6.8 1180 0.13 8.2 1323 0.17 9.9 1528 0.23 12.2 1617 0.27 13.1 1699 0.30 14 1811 0.36 15.2 1923 0.41 16.7 581 0.06 5.7 870 0.09 6.7 1091 0.13 8.2 1250 0.17 9.9 1463 0.24 12.5 1555 0.28 13.5 1639 0.31 14.5 1755 0.37 15.9 1869 0.43 17.3 MAXIMUM BHP AT A GIVEN RPM = (RPM/2199)3 MAXIMUM RPM = 1725 TIP SPEED (ft/min) = RPM x 3.419 MAXIMUM MOTOR FRAME SIZE = 56 AVERAGE DISCHARGE VELOCITY (FPM) = CFM/1.28 691 0.09 6.7 981 0.14 8 1159 0.18 10 1398 0.25 12.6 1493 0.29 13.7 1580 0.32 14.7 1699 0.38 16.2 1816 0.44 17.9 833 0.14 8.1 1053 0.18 9.8 1315 0.26 12.7 1421 0.29 13.8 1518 0.33 14.8 1643 0.39 16.4 1763 0.45 18.2 916 0.18 9.8 1224 0.26 12.7 1338 0.30 13.8 1441 0.34 14.9 1577 0.40 16.6 1710 0.46 18.4 965 0.25 12.3 1132 0.30 13.6 1262 0.34 14.9 1424 0.41 16.7 1571 0.47 18.7 990 0.33 14.6 1226 0.40 16.5 1406 0.48 18.6 1176 0.46 18.4 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 25 Roof Upblast/Sidewall Exhaust Size-131: CUBE • CUE • CWB • CW 1.8 Direct Drive RPM P 2H 1/ 247⁄8 (632) 400 1.6 350 1.4 0.0 TH EL EF TO FT HIS SY STE M SE LE CT TO 0 DO T NO 0 0 0 86 0 65 0 500 1000 167⁄8 1500 2000 2500 Volume (cfm) (429) 247⁄8 0 (632) 193⁄4 500 1000 1500 2000 2500 3000 3500 4000 3 Volume (m /hr) (502) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *281⁄4 (718) Belt HP 0.2 3/4 50 CWB • CW 11 4 10 0 131-C 25 0.4 67 15 100 46 131-B 0.6 16 CUBE • CUE 150 0.8 05 13 (483) 200 1.0 35 14 1¾ (44) 19 250 1.2 17 (441) 300 Static Pressure (in. wg) VG-1725 RPM HP 1/4 (718) 173⁄8 Static Pressure (Pa) A-1725 RPM *28 ⁄4 HP 1/3 B-1140 RPM 1 RPM (Belt) RPM (Direct) RPM (Vari-Green) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m 131-A CU RVE C-860 RPM Motor HP Direct Fan RPM 0 0.125 892 0.03 6.2 1036 0.04 7.2 1180 0.06 8.5 1372 0.10 10.7 1564 0.14 12.5 1790 0.22 14.6 1968 0.29 15.7 2041 0.32 16.2 2149 0.37 17.0 2258 0.43 17.9 2366 0.50 18.8 724 0.03 6.0 895 0.05 7.0 1057 0.07 8.3 1267 0.11 10.5 1471 0.15 12.2 1709 0.23 14.3 1895 0.30 15.5 1970 0.33 15.9 2082 0.39 16.8 2194 0.45 17.6 2305 0.51 18.6 0.25 CUBE ^Approximate Weight Damper Size Roof/Wall Opening CUE CWB 66 (30) 64 (29) 12 x 12 (305 x 305) 14½ x 14½ (368 x 368) Static Pressure in Inches wg 0.375 0.5 0.625 0.75 CW 66 (30) 53 (24) 12 x 12 (305 x 305) 12½ x 12½ (318 X 318) 1 1.25 1.5 131 650 VG3/4 755 C-1/8 860 1/4 1000 B-1/6 1140 1305 1/3 1435 1488 1567 1/2 1646 A-1/2 1725 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 697 0.05 6.3 914 0.07 7.7 1158 0.11 10.0 1379 0.16 11.8 1629 0.24 13.9 1822 0.31 15.1 1900 0.35 15.7 2015 0.40 16.5 2130 0.46 17.4 2244 0.53 18.4 675 0.07 6.9 1016 0.12 9.2 1280 0.17 11.2 1547 0.25 13.5 1749 0.32 14.8 1829 0.36 15.4 1948 0.41 16.3 2066 0.47 17.2 2183 0.54 18.2 MAXIMUM BHP AT A GIVEN RPM = (RPM/2041)3 MAXIMUM RPM = 1725 TIP SPEED (ft/min) = RPM x 3.420 MAXIMUM MOTOR FRAME SIZE = 56 AVERAGE DISCHARGE VELOCITY (FPM) = CFM/1.28 801 0.11 8.3 1144 0.17 10.3 1458 0.26 13.0 1671 0.33 14.3 1756 0.37 15.0 1881 0.43 15.9 2002 0.49 16.9 2122 0.56 18.0 964 0.17 9.7 1340 0.26 12.0 1586 0.34 13.8 1679 0.38 14.5 1808 0.44 15.5 1935 0.50 16.5 2061 0.57 17.6 1201 0.26 11.5 1479 0.35 13.1 1580 0.39 13.9 1728 0.45 15.0 1865 0.51 16.1 1994 0.58 17.2 1198 0.33 11.9 1342 0.38 12.7 1527 0.45 13.8 1686 0.52 15.1 1838 0.60 16.4 1222 0.42 12.6 1458 0.51 14.0 1646 0.60 15.3 1365 0.57 14.1 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 26 Roof Upblast/Sidewall Exhaust Size-140: USGF Size-141: CUBE • CUE • CWB • CW 2.0 Direct Drive RPM 141 -A TH EL EF TO FT HIS SYS TEM CUR VE TO SE LE CT Static Pressure (in. wg) 12 11 40 10 86 0 NO T DO 25 17 100 CWB • CW 90 141-C 0.5 13 141-B 95 15 1.0 95 14 USGF-140 • CUBE • CUE (660) HP (559) 200 4 1/ 1¾ (44) 300 P 3H 1/ 193⁄8 (492) 1.5 Static Pressure (Pa) VG-1725 RPM P (756) 26 400 A-1725 RPM *29 ⁄4 22 2H 1/ B-1140 RPM RPM (Belt) RPM (Direct) RPM (Vari-Green) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m HP P 4H 3/ C-860 RPM 3 1 287⁄8 (733) 59 0 0 0.0 0 400 800 1200 1600 2000 2400 2800 3200 Volume (cfm) 193⁄8 (492) 293⁄4 0 (756) 22 ⁄8 1 1000 2000 3000 4000 5000 3 Volume (m /hr) (562) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *293⁄4 (756) Belt Motor HP Direct Fan RPM 0 0.125 1069 0.04 5.0 1313 0.06 5.1 1558 0.11 7.3 2001 0.23 10.9 2065 0.25 11.3 2192 0.30 12.2 2518 0.45 14.9 2708 0.56 17.2 2808 0.63 18.7 2889 0.69 20.0 3124 0.87 26.0 851 0.04 4.5 1151 0.07 5.0 1427 0.12 7.5 1906 0.24 10.8 1973 0.26 11.3 2106 0.31 12.2 2445 0.47 14.7 2640 0.58 16.5 2743 0.64 17.8 2826 0.70 19.0 3066 0.88 23.0 0.25 CUBE ^Approximate Weight Damper Size Roof/Wall Opening CUE USGF 84 (38) 90 (41) 125 (57) 16 x 16 (406 x 406) N/A 18½ x 18½ (470 x 470) Static Pressure in Inches wg 0.375 0.5 0.75 1 1.25 CWB CW 84 (38) 90 (41) 15 x 15 (381 x 381) 15½ x 15½ (394 X 394) 1.50 1.75 140 / 141 590 VG3/4 or 1 725 1/4 C-1/8 860 1105 B-1/4 1140 1/3 1210 1/2 1390 1495 1550 3/4 1595 VG-1 1 A-1 1725 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 917 0.07 4.4 1264 0.12 7.1 1793 0.25 10.6 1864 0.27 11.0 2006 0.32 11.7 2362 0.48 14.2 2565 0.60 16.3 2671 0.66 17.5 2757 0.72 18.5 3005 0.90 22.0 1034 0.12 6.5 1667 0.26 10.3 1745 0.28 10.7 1896 0.33 11.6 2271 0.50 13.2 2483 0.61 15.6 2594 0.68 17.7 2683 0.74 19.5 2936 0.92 24.0 MAXIMUM BHP AT A GIVEN RPM = (RPM/1726)3 MAXIMUM RPM = 1725 TIP SPEED (ft/min) = RPM x 3.829 MAXIMUM MOTOR FRAME SIZE = 145T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/1.72 1515 0.26 10.0 1605 0.29 10.3 1773 0.34 11.2 2174 0.51 12.9 2396 0.62 13.9 2509 0.69 14.9 2602 0.75 16.1 2865 0.94 24.0 998 0.23 9.6 1167 0.27 10.0 1443 0.34 10.9 1949 0.52 12.1 2202 0.64 12.5 2329 0.71 12.9 2430 0.77 13.3 2711 0.97 15.1 1643 0.51 11.0 1967 0.65 12.2 2110 0.72 12.5 2225 0.79 12.3 2539 0.99 13.4 1617 0.61 10.8 1823 0.70 11.6 1968 0.78 12.6 2339 1.00 14.3 1349 0.62 10.2 1568 0.71 11.6 2085 0.98 13.8 1704 0.91 13.8 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 27 Roof Upblast/Sidewall Exhaust Size-140HP: USGF Size-141HP: CUBE • CUE • CWB • CW 3.5 4H 3/ Direct Drive RPM 800 3.0 USGF-140HP • CUBE • CUE 141HP-A 1.5 1.0 18 16 05 65 5 5 0.5 895 D 0 0.0 0 200 400 600 800 193⁄8 1000 1200 1400 1600 1800 Volume (cfm) 28 ⁄8 7 (733) 0 500 1000 1500 2000 2500 3000 3 Volume (m /hr) (562) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *293⁄4 (756) Belt 25 108 100 221⁄8 45 17 127 200 CWB • CW (492) 00 10 14 O 26 (660) 300 Static Pressure (in. wg) Static Pressure (Pa) (483) 400 2.0 HP 1¾ (44) 22 500 2 193⁄8 22 21 P 600 HP (756) 2.5 H 1/4 *293⁄4 1/3 700 1/ VG-2200 RPM (492) RPM (Belt) RPM (Direct) RPM (Vari-Green) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m P A-1725 RPM NO TS EL EC TT OT HE LEF TO F TH IS S YST EM CUR VE 287⁄8 (733) Motor HP Direct Fan RPM 0.5 0.75 1 CUBE ^Approximate Weight Damper Size Roof/Wall Opening CUE USGF 84 (38) 90 (41) 125 (57) 16 x 16 (406 x 406) N/A 18½ x 18½ (470 x 470) Static Pressure in Inches wg 1.25 1.5 1.75 2 2.25 CWB CW 84 (38) 90 (41) 15 x 15 (381 x 381) 15½ x 15½ (394 X 394) 2.50 2.75 140HP / 141HP 895 VG3/4 1085 1/4 1275 1465 1/3 1605 A-1/2 1725 1/2 1845 1960 3/4 2035 2110 2200 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 331 0.06 5.7 625 0.11 7.5 833 0.17 11.0 1016 0.24 14.2 1146 0.31 15.3 1256 0.38 16.2 1363 0.46 17.1 1463 0.54 18.1 1528 0.60 19.0 1592 0.67 19.9 1669 0.75 21.0 377 0.10 9.5 700 0.17 10.5 920 0.26 13.5 1063 0.33 14.4 1178 0.40 15.4 1292 0.48 16.6 1399 0.57 17.8 1468 0.63 18.6 1536 0.70 19.4 1617 0.78 21.0 492 0.16 13.9 798 0.26 13.3 965 0.34 14.2 1098 0.42 15.0 1219 0.50 16.1 1330 0.59 17.4 1402 0.66 18.3 1473 0.72 19.2 1557 0.81 20.0 MAXIMUM BHP AT A GIVEN RPM = (RPM/2285)3 MAXIMUM RPM = 2200 TIP SPEED (ft/min) = RPM x 3.829 MAXIMUM MOTOR FRAME SIZE = 145T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/1.72 642 0.26 15.5 846 0.34 14.0 999 0.43 14.9 1137 0.52 16.0 1260 0.61 17.2 1335 0.68 18.1 1409 0.75 19.1 1496 0.84 20.0 704 0.34 15.3 879 0.43 14.7 1042 0.52 15.9 1176 0.62 17.1 1261 0.69 18.0 1341 0.77 19.0 1434 0.86 20.0 747 0.42 15.7 924 0.52 15.7 1086 0.63 17.0 1175 0.70 17.9 1262 0.78 18.8 1364 0.87 20.0 800 0.51 16.2 970 0.62 16.8 1077 0.70 17.7 1178 0.78 18.7 1284 0.88 19.9 854 0.62 17.0 965 0.69 17.5 1073 0.78 18.5 1200 0.89 19.7 826 0.67 17.9 965 0.77 18.3 1097 0.88 19.5 804 0.73 20.0 993 0.87 19.3 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 28 Roof Upblast/Sidewall Exhaust Size-160: USGF Size-161: CUBE • CUE • CWB • CW 287⁄8 2 Direct Drive RPM (733) C-860 RPM 600 0 NO T RV E CU EM TO S 0 73 0 1000 2000 193⁄8 3000 4000 5000 Volume (cfm) (492) 287⁄8 (733) 22 ⁄8 1 0 2000 4000 6000 8000 3 Volume (m /hr) (562) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *293⁄4 (756) Belt ST SY HIS FT TO EF EL TH DO 0.0 5 86 EL 100 0 65 11 40 EC 161-C 0.5 CWB • CW 12 96 T Static Pressure (in. wg) Static Pressure (Pa) 161-B 1.0 90 13 USGF-160 • CUBE • CUE (660) HP 200 1 26 HP 1/2 (559) 300 1.5 HP 1/3 HP 1/4 1¾ (44) 400 HP 3/4 19 ⁄8 (492) 2.0 25 17 500 VG-1725 RPM 3 22 HP A-1725 RPM (756) RPM (Belt) RPM (Direct) RPM (Vari-Green) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m /2 11 2.5 B-1140 RPM *293⁄4 HP 161-A Motor HP Direct Fan RPM CUBE ^Approximate Weight Damper Size Roof/Wall Opening CUE USGF 87 (39) 90 (41) 131 (59) 16 x 16 (406 x 406) N/A 18½ x 18½ (470 x 470) 0 0.125 0.25 Static Pressure in Inches wg 0.375 0.5 0.625 0.75 0.875 2098 0.13 8.1 2314 0.18 9.5 2472 0.22 10.7 2515 0.23 11 2774 0.31 12.4 3191 0.47 15 3277 0.51 15.7 3636 0.70 18.5 3737 0.76 19.1 3996 0.93 21 4959 1.77 30 1905 0.15 8 2143 0.20 9.2 2315 0.24 10.2 2362 0.26 10.6 2637 0.34 12 3072 0.51 14.6 3161 0.55 15.2 3532 0.74 18.1 3636 0.80 18.7 3901 0.97 21 4882 1.83 29 1669 0.15 7.8 1937 0.20 8.9 2126 0.25 9.9 2177 0.26 10.1 2477 0.35 11.5 2941 0.53 14.2 3035 0.57 14.8 3426 0.77 17.6 3534 0.84 18.3 3806 1.01 20 4806 1.88 29 1389 0.15 7.8 1708 0.20 8.8 1918 0.25 9.7 1974 0.26 9.9 2300 0.35 11.2 2796 0.53 13.8 2896 0.57 14.4 3301 0.78 17.2 3413 0.85 17.9 3698 1.03 19.7 4729 1.94 29 1770 0.49 12.5 1983 0.55 13.2 2583 0.78 15.8 2729 0.84 16.5 3078 1.04 18.4 4269 2.00 27 CWB CW 87 (39) 90 (41) 15 x 15 (381 x 381) 15½ x 15½ (394 X 394) 1 1.5 160 / 161 730 VG3/4 or 1 805 1/4 C-1/4 860 875 1/3 965 1/2 1110 B-1/2 1140 3/4 1265 VG-1 1300 1 1390 VG-2 A-2 1725 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 1396 0.19 8.7 1680 0.24 9.5 1744 0.26 9.7 2109 0.35 10.8 2641 0.54 13.5 2745 0.58 14.1 3172 0.79 16.8 3290 0.85 17.5 3584 1.04 19.3 4646 1.97 28 MAXIMUM BHP AT A GIVEN RPM = (RPM/1365)3 MAXIMUM RPM = 1725 TIP SPEED (ft/min) = RPM x 4.352 MAXIMUM MOTOR FRAME SIZE = 145T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/1.72 1365 0.24 9.7 1893 0.34 10.6 2475 0.53 13.1 2587 0.58 13.8 3036 0.79 16.5 3157 0.86 17.2 3464 1.04 19 4554 1.97 28 1584 0.33 10.6 2297 0.52 12.9 2421 0.57 13.5 2894 0.79 16.3 3022 0.86 17 3340 1.05 18.8 4463 1.98 27 2163 0.75 15.6 2357 0.82 16.3 2785 1.03 18 4070 2.01 27 2394 1.00 17.9 3855 1.99 26 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 29 Roof Upblast/Sidewall Exhaust Size-160HP: USGF Size-161HP: CUBE • CUE • CWB • CW 287⁄8 161HP-A Direct Drive RPM (733) B-1140 RPM 600 3/ 4 RV E CU EM ST SY IS TH FT E 1 10 140 65 CT LE DO 0.0 0 55 LE 1.0 0.5 0 13 4 12 OF 161HP-B TO Static Pressure (in. wg) 1.5 100 CWB • CW RPM (Belt) RPM (Direct) RPM (Vari-Green) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m 35 15 Static Pressure (Pa) P USGF-160HP • CUBE • CUE (660) H 200 26 2 1/ (559) 300 HP 1/3 HP 1¾ (44) 400 2.0 1/4 193⁄8 (492) 22 500 HP TH VG-1725 RPM (756) HP 90 25 16 17 A-1725 RPM *293⁄4 1 2.5 0 NO T 82 SE 500 5 1000 1500 2000 2500 3000 Volume (cfm) 19 ⁄8 3 (492) 287⁄8 0 (733) 221⁄8 1000 2000 3000 4000 5000 3 Volume (m /hr) (562) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *293⁄4 (756) Belt Motor HP Direct Fan RPM 0.5 0.625 0.75 CUBE ^Approximate Weight Damper Size Roof/Wall Opening CUE USGF 87 (39) 90 (41) 131 (59) 16 x 16 (406 x 406) N/A 18½ x 18½ (470 x 470) Static Pressure in Inches wg 0.875 1 1.25 1.5 1.75 CWB CW 87 (39) 90 (41) 15 x 15 (381 x 381) 15½ x 15½ (394 X 394) 2 2.25 160HP / 161HP 1/4 825 VG3/4 or 1 945 1065 B-1/3 1140 1/3 1165 1255 1/2 1340 3/4 1535 1550 1 1690 VG-1 A1 1/2 1725 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 889 0.12 6.1 1213 0.18 8.9 1487 0.25 11.1 1645 0.31 12.7 1697 0.32 12.9 1882 0.40 13.1 2053 0.48 14.2 2433 0.70 18.1 2461 0.72 18.3 2722 0.92 21 2787 0.97 22 1062 0.18 8.4 1377 0.26 10.7 1552 0.32 12.5 1608 0.33 12.8 1799 0.41 12.8 1975 0.49 13.8 2368 0.72 17.7 2398 0.74 17.9 2671 0.94 21 2736 0.99 21 1252 0.26 10.3 1444 0.32 12 1504 0.34 12.3 1715 0.42 12.5 1897 0.50 13.3 2301 0.73 17.3 2331 0.75 17.5 2611 0.95 20 2680 1.01 21 1093 0.26 9.7 1322 0.32 11.6 1395 0.34 11.8 1617 0.43 12 1816 0.51 12.9 2233 0.74 16.9 2264 0.76 17.1 2550 0.97 19.8 2620 1.03 21 MAXIMUM BHP AT A GIVEN RPM = (RPM/1660)3 MAXIMUM RPM = 1725 TIP SPEED (ft/min) = RPM x 4.352 MAXIMUM MOTOR FRAME SIZE = 145T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/1.72 1175 0.32 11 1252 0.34 11.2 1519 0.43 11.5 1724 0.52 12.4 2165 0.76 16.5 2197 0.78 16.7 2488 0.98 19.4 2560 1.04 20 1218 0.42 10.6 1513 0.52 11.3 2015 0.78 15.6 2051 0.80 15.9 2365 1.01 18.7 2439 1.07 19.4 1855 0.79 14.7 1892 0.81 15 2228 1.03 18 2310 1.10 18.7 1638 0.78 13.5 1683 0.81 13.8 2082 1.05 17.3 2167 1.11 18 1352 0.77 14.5 1899 1.05 16.1 2003 1.12 17.1 1664 1.03 15.1 1810 1.11 16 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 30 Roof Upblast/Sidewall Exhaust Size-160XP: USGF Size-161XP: CUBE 3.5 287⁄8 HP *293⁄4 (559) 26 USGF-160XP • CUBE (660) 300 0 URVE 05 F THIS 1.5 1.0 200 100 22 200 THE LEFT O 400 2.0 0.5 25 HP 5 175 0 155 0 DO 1¾ (44) 22 500 NO TS ELE CT T O Static Pressure (Pa) 19 ⁄8 (492) 2.5 Static Pressure (in. wg) 600 (756) RPM (Belt) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m HP 25 1 SYSTE MC 1/2 3.0 700 1/ 2 HP 800 3 1 3/4 (733) 0.0 0 400 800 1200 1600 2000 2400 2800 Volume (cfm) 0 500 1000 1500 2000 2500 3000 3500 4000 4500 3 Volume (m /hr) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. Motor HP Fan RPM 160XP / 161XP CFM 1550 BHP Sones CFM 1648 BHP 1/2 Sones CFM 1750 BHP Sones CFM 1880 BHP Sones CFM 1942 BHP 3/4 Sones CFM 2005 BHP Sones CFM 2138 BHP Sones 1 CFM 2205 BHP Sones CFM 2310 BHP Sones CFM 2432 BHP 11⁄2 Sones CFM 2525 BHP Sones 1 968 0.34 10.0 1157 0.42 11.1 1322 0.52 12.1 1515 0.7 13.7 1599 0.71 14.4 1684 0.77 15.0 1861 0.9 16.6 1946 1.01 17.5 2065 1.17 18.8 2206 1.36 21 2313 1.52 22 1.25 854 0.39 10.1 1116 0.49 11.4 1359 0.6 13.1 1456 0.7 14 1552 0.78 14.8 1743 1.0 16.4 1834 1.03 17.3 1974 1.18 18.7 2132 1.36 20 2241 1.52 22 1.5 726 0.43 10.6 1139 0.6 12.2 1271 0.68 13.2 1392 0.76 14.1 1611 0.9 15.9 1713 1.04 17 1865 1.2 18.5 2031 1.38 20 2155 1.54 22 CUBE ^Approximate Weight Damper Size Roof/Wall Opening USGF 87 (39) 131 (59) 16 x 16 (406 x 406) N/A 18½ x 18½ (470 x 470) Static Pressure in Inches wg 1.75 2 2.25 2.5 2.75 3 3.25 MAXIMUM BHP AT A GIVEN RPM = (RPM/2170)3 MAXIMUM RPM = 2525 TIP SPEED (ft/min) = RPM x 3.534 MAXIMUM MOTOR FRAME SIZE = 145T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/1.72 744 0.5 11.8 984 0.63 12.4 1161 0.72 13.4 1451 0.9 15.4 1578 1.01 16.4 1741 1.18 18.1 1926 1.4 20 2056 1.56 22 777 0.63 13.2 1226 0.9 14.8 1395 0.99 15.8 1597 1.16 17.5 1804 1.38 19.6 1946 1.56 21 869 0.8 14.8 1127 0.92 15.5 1415 1.12 17 1660 1.35 19.1 1828 1.53 21 634 0.73 16.4 1134 1.04 16.9 1483 1.31 18.7 1676 1.5 20 644 0.83 18.2 1225 1.23 18.7 1487 1.45 20 826 1.07 19.8 1221 1.35 20 810 1.16 22 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 31 Roof Upblast/Sidewall Exhaust Size-180: CUBE • CUE • USGF CWB • CW 353⁄8 2.5 Direct Drive RPM 600 (899) HIS SY STE MC UR VE OF T 95 EF T TH EL TO SE LE CT Static Pressure (in. wg) 14 75 94 0 NO T 0 82 0 74 O 5 1 2 25 3 4 5 6 Volume (cfm x 1000) (635) 35 ⁄8 3 (899) 273⁄4 0 2 4 6 8 10 3 Volume (m /hr x 1000) (705) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *285⁄8 (727) Belt 60 10 0 13 85 0.0 40 86 D 0 11 11 Static Pressure (Pa) HP 180-C 0.5 CWB • CW P 1H USGF-180 • CUBE • CUE (762) HP 200 1.0 HP 30 180-B 1/4 (762) 1.5 3 1/ 1¾ (44) 400 3/4 (553) HP (727) 21 30 HP 2.0 1/2 *28 ⁄8 HP 2 1/ B-1140 RPM VG-1000 RPM 5 RPM (Belt) RPM (Direct) RPM (Vari-Green) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m 2 1 C-860 RPM Motor HP Direct Fan RPM 0 0.125 0.25 2815 0.22 9.2 3098 0.30 11.2 3249 0.34 12.3 3551 0.45 13.8 3778 0.54 15.1 4061 0.67 16.5 4307 0.80 17.6 4477 0.90 18.5 4817 1.12 21 5138 1.36 23 5648 1.80 28 2617 0.24 8.6 2916 0.32 10.4 3074 0.37 11.7 3389 0.47 13.5 3625 0.57 14.9 3919 0.70 16.2 4173 0.83 17.1 4348 0.93 17.9 4697 1.15 20 5026 1.39 23 5546 1.84 27 2448 0.26 8.1 2759 0.34 10 2922 0.39 11.1 3243 0.49 13.1 3486 0.59 14.7 3786 0.73 15.8 4045 0.86 16.5 4224 0.96 17.1 4578 1.19 19.5 4913 1.43 22 5443 1.89 27 CUBE ^Approximate Weight Damper Size Roof/Wall Opening CUE USGF 126 (57) 142 (64) 190 (86) 18 x 18 (457 x 457) N/A 20½ x 20½ (521 x 521) Static Pressure in Inches wg 0.5 0.75 1 1.25 1.5 CWB CW 126 (57) 142 (64) 17 x 17 (432 x 432) 17½ x 17½ (445 X 445) 1.75 2 180 1/4 VG3/4 or 1 745 820 1/3 C-1/2 860 1/2 940 1000 VG-1 3/4 1075 B-1 1140 1 VG-2 1185 1275 11⁄2 1360 2 1495 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 1763 0.25 7.1 2257 0.34 9 2474 0.40 10.2 2879 0.52 12.4 3190 0.63 14.3 3554 0.78 15.5 3822 0.91 16.1 4005 1.01 16.5 4369 1.24 18.7 4710 1.49 21 5254 1.96 26 MAXIMUM BHP AT A GIVEN RPM = (RPM/1167)3 MAXIMUM RPM = 1495 TIP SPEED (ft/min) = RPM x 4.843 MAXIMUM MOTOR FRAME SIZE = 184T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/2.92 2363 0.50 11.2 2738 0.62 13.3 3141 0.78 14.7 3470 0.93 15.4 3703 1.04 16 4163 1.30 18.2 4532 1.56 21 5082 2.02 25 2652 0.75 13.3 3072 0.92 14.6 3336 1.04 15.2 3799 1.30 17.5 4232 1.58 20 4921 2.10 25 2477 0.85 13.6 2841 0.99 14.4 3437 1.28 16.7 3912 1.58 19.2 4598 2.10 24 2930 1.22 15.9 3537 1.54 18.3 4313 2.10 23 3023 1.46 17.3 3983 2.06 22 3564 1.99 21 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 32 Roof Upblast/Sidewall Exhaust Size-180HP: CUBE • CUE • USGF CWB • CW 3.5 2 3.0 700 1.0 100 0 SE 0.0 65 O N 0.5 10 92 84 5 5 T CWB • CW SY FT TO EF EL TH HP 200 35 15 TO 4 13 12 CT Static Pressure (Pa) HP 1/ 30 3 15 1/ 1.5 25 17 5 8 16 USGF-180HP • CUBE • CUE HP 30 (762) 300 P 2 (762) 400 2.0 1/ 1¾ (44) 30 500 H HP (553) 1 4 3/ 21 2.5 LE 600 Static Pressure (in. wg) (727) HI S *285⁄8 RPM (Belt) RPM (Direct) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m CU A-1725 RPM RVE HP 180HP-A 1 1/ 2 HP 800 EM Direct Drive RPM ST 353⁄8 (899) DO 0 1000 2000 25 3000 4000 5000 Volume (cfm) (635) 353⁄8 0 (899) 27 ⁄4 3 1000 2000 3000 4000 5000 6000 7000 8000 3 Volume (m /hr) (705) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *285⁄8 (727) Motor HP Belt Direct Fan RPM 0.5 0.75 1 CUBE ^Approximate Weight Damper Size Roof/Wall Opening CUE USGF 126 (57) 142 (64) 190 (86) 18 x 18 (457 x 457) N/A 20½ x 20½ (521 x 521) Static Pressure in Inches wg 1.25 1.5 1.75 2 2.25 CWB CW 126 (57) 142 (64) 17 x 17 (432 x 432) 17½ x 17½ (445 X 445) 2.5 2.75 180HP 1/4 845 1/3 925 1/2 1065 3/4 1215 1275 1 1335 1430 11⁄2 1530 1610 2 1685 A-2 1725 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 1799 0.26 9.6 2104 0.34 10.8 2581 0.50 14.1 3063 0.72 15.4 3253 0.82 17 3441 0.93 19 3735 1.13 22 4035 1.36 24 4273 1.58 26 4495 1.79 28 4613 1.92 29 1688 0.35 9.9 2323 0.52 12.6 2868 0.76 14.8 3066 0.87 16.2 3261 0.98 17.8 3566 1.19 21 3884 1.43 23 4136 1.64 24 4369 1.86 27 4493 1.99 28 1933 0.53 12.5 2626 0.78 14.2 2853 0.89 15.6 3075 1.02 17.3 3401 1.23 20 3728 1.48 22 3986 1.70 24 4226 1.93 26 4353 2.06 27 MAXIMUM BHP AT A GIVEN RPM = (RPM/1315)3 MAXIMUM RPM = 1725 TIP SPEED (ft/min) = RPM x 4.843 MAXIMUM MOTOR FRAME SIZE = 184T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/2.92 2286 0.79 13.5 2566 0.91 15.1 2839 1.04 16.8 3206 1.26 19.6 3574 1.53 21 3840 1.76 23 4085 1.99 26 4215 2.12 29 1854 0.75 12.7 2209 0.89 14.3 2523 1.04 16.3 2964 1.27 19.2 3376 1.55 21 3674 1.79 22 3945 2.04 25 4078 2.18 27 2156 1.01 15.7 2669 1.28 18.8 3135 1.56 20 3485 1.81 22 3768 2.07 23 3917 2.21 25 2320 1.24 18.2 2859 1.57 19.7 3233 1.82 21 3575 2.08 22 3740 2.23 24 2534 1.53 19.1 2965 1.82 20 3325 2.09 22 3509 2.24 23 2656 1.78 19.8 3061 2.08 21 3265 2.25 22 1557 1.38 18.3 2766 2.04 21 2984 2.21 21 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 33 Roof Upblast/Sidewall Exhaust Size-200: CUBE • CUE • USGF CWB • CW 353⁄8 2.0 Direct Drive RPM (899) 1.5 *28 ⁄8 TEM SYS HIS FT TO EF EL TH 86 TO 0 76 0 CT 0.5 66 LE 100 SE CWB • CW 10 12 40 11 00 11 0 96 HP Static Pressure (Pa) HP P 200-C 4 Static Pressure (in. wg) 1 4H 3/ 1.0 1/ USGF-200 • CUBE • CUE (762) HP 30 1/3 (762) 200 P 1¾ (44) 300 H 1/2 (553) 30 CUR VE 200-B 400 (727) HP HP /2 11 B-1140 RPM 5 21 RPM (Belt) RPM (Direct) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m 2 C-860 RPM 5 60 O T 5 DO 0 0.0 0 N 1 2 25 3 4 5 6 7 Volume (cfm x 1000) (635) 35 ⁄8 3 0 (899) 273⁄4 2 4 6 8 10 3 Volume (m /hr x 1000) (705) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *285⁄8 (727) Motor HP Belt Direct Fan RPM CUBE ^Approximate Weight Damper Size Roof/Wall Opening CUE USGF 142 (64) 142 (64) 213 (97) 18 x 18 (457 x 457) N/A 20½ x 20½ (521 x 521) 0 0.125 0.25 Static Pressure in Inches wg 0.375 0.5 0.75 3403 0.25 8.2 3740 0.33 9.6 4275 0.49 12.3 4612 0.61 14.2 4837 0.71 15.8 4922 0.75 16.4 5400 0.98 18.9 5793 1.22 21 6187 1.48 24 6412 1.65 25 6806 1.97 24 3054 0.26 7.6 3422 0.34 9 3994 0.51 11.8 4350 0.63 14.1 4587 0.73 15.7 4676 0.77 16.4 5176 1.01 18.6 5585 1.24 21 5992 1.51 23 6224 1.67 24 6628 2 24 2675 0.26 6.8 3096 0.35 8.3 3718 0.52 11.1 4098 0.65 13.3 4346 0.74 14.9 4439 0.78 15.6 4958 1.03 18 5380 1.26 20 5798 1.53 23 6036 1.7 24 6451 2.03 23 2144 0.25 6.2 2699 0.35 7.5 3413 0.52 10.2 3828 0.65 12.5 4093 0.75 14.4 4192 0.79 15.1 4742 1.04 17.4 5179 1.28 19.7 5610 1.55 22 5855 1.72 23 6279 2.05 23 1 1.25 CWB CW 142 (64) 142 (64) 17 x 17 (432 x 432) 17½ x 17½ (445 X 445) 1.5 1.75 200 1/4 605 1/3 665 1/2 760 820 3/4 C-3/4 860 875 1 960 1030 11⁄2 1100 B-2 1140 2 1210 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 2073 0.33 7.2 3048 0.51 9.5 3523 0.65 11.5 3815 0.75 13 3922 0.79 13.7 4508 1.04 16.7 4968 1.29 19.2 5421 1.57 22 5674 1.74 22 6108 2.07 23 MAXIMUM BHP AT A GIVEN RPM = (RPM/946)3 MAXIMUM RPM = 1210 TIP SPEED (ft/min) = RPM x 5.595 MAXIMUM MOTOR FRAME SIZE = 184T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/2.92 2606 0.61 10.9 3084 0.73 12 3240 0.78 12.6 3985 1.04 15.2 4503 1.29 17.8 5006 1.57 21 5283 1.74 22 5748 2.09 22 3169 1.00 14.7 3917 1.27 16.6 4529 1.57 19.7 4837 1.74 21 5350 2.09 21 2972 1.18 17.1 3861 1.53 18.9 4276 1.73 19.6 4892 2.08 20 3445 1.63 20 4289 2.04 20 3365 1.88 21 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 34 Roof Upblast/Sidewall Exhaust Size-200HP: CUBE • USGF CWB 353⁄8 3.5 3 (899) 800 HP RPM (Belt) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m 3.0 2 CU EM ST SY HIS FT TO EF EL TH TO SE T DO 0.0 0 0 NO 1 2 3 4 5 6 7 Volume (cfm x 1000) 35 ⁄8 3 (899) 273⁄4 88 LE 0 0.5 25 (635) 11 10 10 10 CT Static Pressure (Pa) 100 70 1.0 200 CWB 00 USGF-200HP • CUBE (762) 300 1.5 12 30 14 (762) 400 2.0 P H 1 HP 4 3/ P 2H 1/ 1¾ (44) 30 500 HP 11 /2 HP 00 21 (553) Static Pressure (in. wg) 600 2.5 16 (727) RVE 700 *285⁄8 0 2 4 6 8 10 3 Volume (m /hr x 1000) (705) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *285⁄8 (727) Motor HP Fan RPM 0.5 0.75 1 CUBE USGF ^Approximate Weight 142 (64) 213 (97) Damper Size 18 x 18 (457 x 457) N/A Roof/Wall Opening 20½ x 20½ (521 x 521) Static Pressure in Inches wg 1.25 1.5 1.75 2 2.25 CWB 142 (64) 17 x 17 (432 x 432) 17½ x 17½ (445 X 445) 2.5 2.75 200HP 740 1/2 880 945 CWB • CUBE • USGF 3/4 1010 1 1110 1190 11⁄2 1270 1335 2 CUBE • USGF 1400 1465 3 1600 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 2024 0.31 8.2 2779 0.51 10.7 3094 0.62 12.3 3397 0.75 14.7 3851 0.98 17.1 4207 1.2 19.4 4558 1.44 22 4837 1.67 23 5110 1.91 25 5382 2.18 26 5943 2.81 29 2317 0.52 9.6 2711 0.64 11.7 3067 0.78 14.1 3561 1.02 16.5 3944 1.24 18.5 4312 1.49 21 4606 1.71 23 4898 1.96 24 5186 2.23 25 5775 2.88 27 2092 0.62 10.8 2637 0.79 13.5 3242 1.04 16 3661 1.27 17.9 4055 1.53 21 4369 1.76 22 4674 2.01 24 4972 2.28 25 5581 2.93 28 MAXIMUM BHP AT A GIVEN RPM = (RPM/1093)3 MAXIMUM RPM = 1600 TIP SPEED (ft/min) = RPM x 5.595 MAXIMUM MOTOR FRAME SIZE = 184T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/2.92 2806 1.04 15.8 3321 1.29 17.5 3789 1.56 20 4116 1.79 21 4436 2.05 23 4752 2.33 25 5385 2.99 28 2850 1.26 17.9 3433 1.56 19.3 3826 1.82 21 4195 2.09 22 4521 2.37 24 5182 3.03 28 2944 1.53 20 3482 1.82 21 3880 2.09 23 4269 2.4 23 4971 3.08 26 2946 1.75 22 3515 2.08 23 3956 2.4 25 4760 3.13 26 2982 2.01 24 3556 2.37 25 4476 3.13 28 4189 3.13 30 3760 3.06 31 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 35 Roof Upblast/Sidewall Exhaust Size-220: CUBE CWB 2.0 423⁄4 RV E CU EM ST SY IS TH OF FT LE E TH TO 68 T 5 60 EC Static Pressure (in. wg) 5 EL 0.0 0 NO 1 T 47 S 2 0 52 5 0 3 283⁄8 4 5 6 7 8 Volume (cfm x 1000) 42 ⁄32 25 (1087) 0 311⁄4 2 4 6 8 10 12 3 Volume (m /hr x 1000) (794) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *337⁄8 (860) Motor HP 5 DO (721) 86 CWB 5 0.5 100 0 95 1.0 75 Static Pressure (Pa) P 4H 3/ CUBE P HP 3 H 1 /4 200 1/ 1¾ (44) (864) 300 HP 251⁄2 (648) 1/2 (860) P H 1.5 *337⁄8 34 P 1H 400 RPM (Belt) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m 2 HP /2 11 (1086) Fan RPM 0 0.125 0.25 3585 0.19 7.4 3784 0.23 8 4142 0.3 9.3 4779 0.46 12 5138 0.57 13.6 5457 0.68 15 6014 0.91 17.7 6452 1.13 19 6890 1.37 21 7249 1.6 23 7607 1.85 25 3155 0.21 6.8 3377 0.25 7.3 3771 0.32 8.5 4457 0.48 11.1 4838 0.6 12.7 5174 0.71 14.2 5758 0.94 17 6213 1.16 18.5 6667 1.41 20 7036 1.64 22 7405 1.89 25 2624 0.22 6.2 2896 0.26 6.7 3357 0.34 7.7 4124 0.51 10.2 4539 0.63 12 4893 0.74 13.7 5502 0.98 16.6 5975 1.2 17.9 6443 1.45 19.6 6823 1.68 22 7202 1.93 24 ^Approximate Weight Damper Size Roof/Wall Opening Static Pressure in Inches wg 0.375 0.5 0.625 CUBE CWB 174 (79) 24 x 24 (610 x 610) 26½ x 26½ (673 x 673) 174 (79) 20 x 20 (508 x 508) 20½ x 20½ (521 X 521) 0.75 1 1.25 1.5 220 450 1/4 475 1/3 520 1/2 600 645 3/4 685 1 755 810 11⁄2 865 910 2 955 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 2268 0.25 6.2 2845 0.34 7.2 3736 0.52 9.5 4194 0.64 11.3 4581 0.76 13.2 5239 1.01 16.3 5737 1.24 17.6 6220 1.49 19.2 6612 1.72 21 7000 1.97 24 MAXIMUM BHP AT A GIVEN RPM = (RPM/743)3 MAXIMUM RPM = 955 TIP SPEED (ft/min) = RPM x 6.413 MAXIMUM MOTOR FRAME SIZE = 184T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/3.76 3279 0.52 8.9 3811 0.65 10.6 4234 0.78 12.3 4944 1.03 15.8 5470 1.26 17.2 5987 1.52 18.7 6400 1.76 21 6799 2.02 23 3346 0.64 10 3836 0.78 11.7 4620 1.04 14.9 5185 1.28 16.5 5729 1.54 18.1 6158 1.78 20 6580 2.05 23 3383 0.77 11.2 4258 1.04 14.4 4883 1.29 15.7 5453 1.56 17.4 5909 1.81 19.3 6347 2.07 22 4156 1.27 14.8 4835 1.57 16.5 5365 1.83 18.3 5844 2.11 20 4111 1.53 16.1 4704 1.81 17.4 5261 2.11 19.4 4602 2.07 18.9 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 36 Roof Upblast/Sidewall Exhaust Size-220HP: CUBE CWB 423⁄4 3.0 (1086) 3 700 CUR VE TEM SYS HIS FT TO 98 EF 5 EL 86 0 TH 1.0 78 TO 0 68 CT Static Pressure (in. wg) 40 12 LE 0 SE CWB 85 10 Static Pressure (Pa) HP CUBE 200 1.5 HP (864) 300 HP 34 400 2.0 3/4 1¾ (44) 500 1/2 (648) P (860) 1H *337⁄8 251⁄2 2 HP /2 11 2.5 600 RPM (Belt) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m HP 0.5 N O T 100 DO 0 0.0 0 1 2 3 283⁄8 (721) 4 5 6 7 8 Volume (cfm x 1000) 4225⁄32 (1087) 0 31 ⁄4 1 2 4 6 8 10 12 3 Volume (m /hr x 1000) (794) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *337⁄8 (860) Motor HP Fan RPM 0.5 0.75 2909 0.45 8.7 3151 0.51 9.7 3582 0.63 11.9 3902 0.74 13.4 4459 0.96 15 5281 1.39 19.1 5602 1.6 21 5920 1.82 23 6236 2.06 24 6570 2.34 25 6895 2.64 27 1940 0.42 7.7 2405 0.51 8.7 3006 0.65 11 3427 0.78 12.5 4075 1.02 14.3 4988 1.48 17.9 5335 1.69 19.8 5678 1.92 22 6006 2.17 23 6350 2.46 25 6684 2.76 26 1 ^Approximate Weight Damper Size Roof/Wall Opening CUBE CWB 174 (79) 24 x 24 (610 x 610) 26½ x 26½ (673 x 673) 174 (79) 20 x 20 (508 x 508) 20½ x 20½ (521 X 521) Static Pressure in Inches wg 1.25 1.5 1.75 2 2.25 2.5 2.75 220HP 650 1/2 680 735 CWB • CUBE 3/4 780 1 860 11⁄2 985 1035 2 1085 CUBE 1135 3 1188 1240 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones MAXIMUM BHP AT A GIVEN RPM = (RPM/847)3 MAXIMUM RPM = 1240 TIP SPEED (ft/min) = RPM x 6.413 MAXIMUM MOTOR FRAME SIZE = 184T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/3.76 2716 0.77 12.1 3578 1.05 13.9 4642 1.54 17.4 5033 1.77 18.9 5390 2 20 5743 2.26 22 6111 2.56 24 6469 2.88 26 2863 1.01 13.2 4220 1.57 17.1 4659 1.81 18.7 5061 2.06 20 5456 2.34 22 5848 2.65 24 6217 2.97 25 3674 1.56 16.5 4209 1.82 18.3 4679 2.1 20 5114 2.39 21 5540 2.71 23 5950 3.05 25 2825 1.46 14.9 3630 1.79 17.3 4210 2.09 19.6 4708 2.4 21 5202 2.75 23 5637 3.1 24 3573 2.03 18.1 4215 2.38 21 4792 2.76 22 5283 3.13 24 3518 2.28 19.5 4286 2.72 22 4885 3.13 24 3563 2.59 22 4374 3.08 24 3633 2.92 26 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 37 Roof Upblast/Sidewall Exhaust Size-240: CUBE CWB 423⁄4 1.6 2 1.2 CUR VE TEM S YS H IS FT TO EF EL TH TO CT 51 46 0 5 SE LE Static Pressure (Pa) Static Pressure (in. wg) T 0 0.0 NO 0.2 0 93 5 84 5 5 50 DO 0 1 2 3 4 5 6 7 8 9 Volume (cfm x 1000) 4225⁄32 (1087) 0 31 ⁄4 1 2 4 6 8 10 12 14 3 Volume (m /hr x 1000) (794) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *337⁄8 (860) Motor HP 0 58 0.4 283⁄8 (721) 67 0.6 CWB RPM (Belt) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m 73 HP 100 0.8 1/4 CUBE 150 HP 34 (864) 200 1.0 1/3 1¾ (44) 250 P 251⁄2 (648) HP 3/4 (860) H 1/2 *337⁄8 HP 300 P 1.4 1H 350 HP /2 11 (1086) Fan RPM 0 0.125 0.25 3717 0.16 6.4 4216 0.23 7.6 4623 0.31 8.9 5303 0.46 11.5 5693 0.57 12.9 6074 0.69 14.3 6663 0.92 16.6 7162 1.14 18.2 7660 1.39 19.6 8050 1.62 21 8431 1.86 24 3170 0.18 5.8 3768 0.25 7.0 4243 0.33 8.1 4961 0.49 10.5 5368 0.61 11.9 5763 0.74 13.4 6370 0.97 15.9 6883 1.20 17.5 7400 1.46 19.0 7802 1.69 21 8194 1.93 23 2471 0.18 5.3 3188 0.26 6.3 3717 0.34 7.3 4540 0.51 9.5 5010 0.63 11.1 5461 0.76 12.8 6133 0.99 15.5 6661 1.22 17.2 7184 1.49 18.6 7590 1.72 21 7985 1.98 23 ^Approximate Weight Damper Size Roof/Wall Opening Static Pressure in Inches wg 0.375 0.5 0.625 CUBE CWB 142 (64) 24 x 24 (610 x 610) 26½ x 26½ (673 x 673) 175 (79) 20 x 20 (508 x 508) 26½ x 26½ (673 X 673) 0.75 1 1.25 1.5 240 410 1/4 465 1/3 510 1/2 585 628 3/4 670 1 735 790 11⁄2 845 888 2 930 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 2162 0.23 5.9 3134 0.34 6.9 4093 0.52 8.8 4590 0.64 10.4 5052 0.78 12.2 5764 1.01 15.1 6361 1.25 16.8 6947 1.51 18.2 7394 1.75 20 7798 2.00 22 MAXIMUM BHP AT A GIVEN RPM = (RPM/725)3 MAXIMUM RPM = 930 TIP SPEED (ft/min) = RPM x 6.413 MAXIMUM MOTOR FRAME SIZE = 184T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/3.76 3565 0.51 8.4 4141 0.65 9.8 4659 0.79 11.5 5409 1.03 14.6 6011 1.27 16.3 6615 1.54 17.6 7083 1.78 19.5 7536 2.03 22 3600 0.63 9.4 4202 0.78 11.0 5037 1.04 13.9 5693 1.28 15.7 6304 1.56 17.0 6772 1.81 18.7 7233 2.06 21 3524 0.73 10.6 4618 1.03 13.4 5332 1.29 15.0 6002 1.57 16.4 6489 1.82 18.0 6953 2.08 19.9 4453 1.24 14.3 5282 1.56 15.4 5854 1.83 17.0 6375 2.10 18.7 5088 1.77 16.4 5706 2.07 17.8 4324 1.83 17.9 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 38 Roof Upblast/Sidewall Exhaust Size-240HP: CUBE CWB 423⁄4 3.0 (1086) 3H P 700 RVE CU EM ST SY H IS FT EF EL TH 0 77 CT 5 67 (721) SE T DO 0.0 5 O 100 0 5 85 TO 1.0 0.5 283⁄8 97 TO HP LE Static Pressure (in. wg) Static Pressure (Pa) CWB 30 4 70 200 3/ 10 CUBE HP (864) 300 1.5 HP 34 400 2.0 1/2 1¾ (44) 500 1 (648) 12 (860) 251⁄2 P H *337⁄8 2 HP /2 11 2.5 600 RPM (Belt) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m 0 N 1 2 3 4 5 6 7 8 Volume (cfm x 1000) 4225⁄32 (1087) 0 311⁄4 2 4 6 8 10 12 3 Volume (m /hr x 1000) (794) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *337⁄8 (860) Motor HP Fan RPM 0.5 0.625 3046 0.43 8.1 3405 0.51 9.4 3824 0.62 11.3 4233 0.75 13.1 4812 0.96 14.5 5286 1.16 16.4 5737 1.39 18.4 6075 1.59 20 6404 1.80 22 6960 2.21 24 7513 2.68 26 2673 0.43 7.4 3070 0.52 8.8 3547 0.64 10.7 3979 0.77 12.5 4599 0.99 14.0 5094 1.20 15.8 5567 1.43 17.9 5927 1.63 19.6 6272 1.84 22 6836 2.26 24 7395 2.73 25 0.75 1 ^Approximate Weight Damper Size Roof/Wall Opening CUBE CWB 175 (79) 24 x 24 (610 x 610) 26½ x 26½ (673 x 673) 175 (79) 20 x 20 (508 x 508) 20½ x 20½ (521 X 521) Static Pressure in Inches wg 1.25 1.5 1.75 2 2.25 2.5 240HP 635 1/2 675 725 3/4 CWB • CUBE 775 1 850 913 11⁄2 975 1023 2 1070 CUBE 1150 3 1230 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 2607 0.51 8.4 3222 0.65 10.3 3704 0.78 12.1 4367 1.01 13.8 4890 1.23 15.4 5387 1.48 17.3 5756 1.68 19.0 6112 1.89 21 6711 2.30 23 7280 2.77 25 MAXIMUM BHP AT A GIVEN RPM = (RPM/837)3 MAXIMUM RPM = 1230 TIP SPEED (ft/min) = RPM x 6.413 MAXIMUM MOTOR FRAME SIZE = 184T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/3.76 2940 0.77 11.8 3846 1.04 13.4 4448 1.28 15.2 4988 1.53 16.9 5389 1.75 18.3 5775 1.98 19.7 6406 2.40 22 7016 2.88 25 3025 1.00 12.6 3932 1.29 14.7 4539 1.56 16.6 4995 1.80 18.1 5407 2.04 19.7 6077 2.48 22 6730 2.98 25 4006 1.56 15.9 4533 1.81 17.7 4990 2.07 19.4 5735 2.55 22 6410 3.05 24 3854 1.77 16.4 4550 2.08 18.8 5335 2.57 21 6090 3.13 24 3625 1.95 16.6 4925 2.58 21 5709 3.14 23 4212 2.49 20 5326 3.16 23 4722 3.09 25 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 39 Roof Upblast/Sidewall Exhaust Size-240XP: CUBE 3 423⁄4 2 5 HP 1 1200 YSTE H IS S OF T 95 L EF T 17 20 THE 1/2 HP 15 TO 2 18 1 11 95 65 D O NO 200 00 13 CT CUBE 3/ 4H P 3 ELE 400 HP TS 1¾ (44) 34 (864) 600 Static Pressure (in. wg) Static Pressure (Pa) (648) 800 1 65 251⁄2 4 21 (860) M CU HP RVE 2 1/ 1000 *337⁄8 RPM (Belt) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m P H (1086) 0 0 0 500 1000 1500 2000 2500 3000 3500 4000 4500 Volume (cfm) 0 2000 4000 6000 3 Volume (m /hr) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. Motor HP Fan RPM 1 1.25 1292 0.40 10.9 1613 0.53 11.6 2079 0.77 13.6 2223 0.86 14.4 2424 1.00 15.9 2743 1.28 18.6 2939 1.48 21 3333 1.94 24 3469 2.13 25 3632 2.37 26 3927 2.85 29 789 0.34 11.9 1321 0.51 12.1 1886 0.78 13.4 2042 0.88 14.2 2256 1.03 15.3 2604 1.31 18.0 2815 1.51 19.8 3222 1.98 23 3361 2.16 24 3529 2.40 25 3830 2.89 28 1.5 2 CUBE ^Approximate Weight Damper Size Roof/Wall Opening Static Pressure in Inches wg 2.5 3 175 (79) 24 x 24 (610 x 610) 26½ x 26½ (673 x 673) 3.5 4 4.5 5 240XP 1100 1/2 1195 3/4 1365 1421 1 1500 1635 11⁄2 1720 2 1895 1956 3 2030 2165 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 792 0.43 13.4 1645 0.77 13.7 1837 0.88 14.2 2079 1.04 15.1 2450 1.33 17.5 2671 1.53 19.2 3109 2.01 22 3252 2.20 23 3423 2.44 25 3733 2.93 28 MAXIMUM BHP AT A GIVEN RPM = (RPM/1478)3 MAXIMUM RPM = 2165 TIP SPEED (ft/min) = RPM x 4.778 MAXIMUM MOTOR FRAME SIZE = 184T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/3.76 1209 0.79 15.3 1630 1.01 15.5 2101 1.34 17.0 2366 1.57 18.4 2847 2.07 21 3006 2.26 22 3197 2.51 24 3535 3.01 27 1631 1.28 17.7 1975 1.53 18.4 2566 2.10 21 2739 2.30 22 2945 2.56 23 3305 3.07 26 1336 1.35 20 2202 2.05 21 2414 2.28 21 2667 2.58 23 3063 3.12 25 1706 1.92 22 2032 2.21 22 2319 2.51 23 2787 3.11 25 1326 1.89 25 1852 2.38 25 2461 3.05 25 2048 2.93 27 1324 2.47 31 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 40 Roof Upblast/Sidewall Exhaust Size-300: CUBE CWB 50 2.5 (1270) 5 600 MC STE SY H IS FT TO EF EL TH TO CT Static Pressure (in. wg) Static Pressure (Pa) LE SE T NO 53 0 48 0 42 0 36 5 2 4 6 3527⁄32 (910) 5 90 0 5 0.0 76 5 0 60 DO 5 0.5 CWB 66 CUBE 1.0 HP /2 11 200 1.5 P HP P P 3/4 2 H /3 H 1/ 1 (1016) 400 1H 1¾ (44) 40 UR VE P P 2H 29 RPM (Belt) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m 3H 2.0 *36 (914) (737) HP 8 10 12 14 16 Volume (cfm x 1000) 50 (1270) 0 38 ⁄8 3 5 10 (975) 15 20 25 3 Volume (m /hr x 1000) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *36 (914) Motor HP Fan RPM 0 0.125 0.25 5777 0.27 6.9 5940 0.29 7.2 6835 0.45 9.0 7811 0.67 11.0 8625 0.90 13.3 9845 1.34 17.0 10822 1.77 20 12449 2.70 24 12937 3.03 26 13832 3.71 29 14727 4.47 32 5132 0.30 6.3 5316 0.33 6.5 6314 0.49 8.2 7377 0.72 10.5 8231 0.95 12.7 9501 1.40 16.4 10508 1.85 19.7 12176 2.78 24 12675 3.12 25 13587 3.80 28 14497 4.57 32 4227 0.31 5.3 4464 0.34 5.7 5660 0.52 7.5 6844 0.76 9.9 7772 1.00 12.2 9127 1.46 15.7 10193 1.92 18.6 11904 2.86 23 12413 3.20 24 13342 3.89 28 14266 4.67 32 ^Approximate Weight Damper Size Roof/Wall Opening CUBE CWB 313(142) 30 x 30 (762 x 762) 32½ x 32½ (826 x 826) 313(142) 25 x 25 (635 x 635) 25½ x 25½ (648 x 648) Static Pressure in Inches wg 0.5 0.75 1 1.25 1.5 1.75 2 300 355 1/3 CWB • CUBE 365 1/2 420 3/4 480 1 530 11⁄2 605 2 665 3 765 CUBE 795 5 850 905 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones MAXIMUM BHP AT A GIVEN RPM = (RPM/522)3 MAXIMUM RPM = 905 TIP SPEED (ft/min) = RPM x 7.983 MAXIMUM MOTOR FRAME SIZE = 213T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/5.50 5440 0.77 8.5 6636 1.05 11.2 8226 1.54 14.8 9411 2.02 17.5 11273 3.00 22 11818 3.35 23 12808 4.05 26 13788 4.85 29 7084 1.55 13.5 8495 2.07 16.7 10554 3.09 21 11145 3.46 22 12207 4.19 25 13223 5.00 28 7271 2.04 15.1 9743 3.15 20 10404 3.53 22 11521 4.27 25 12614 5.11 28 8756 3.14 18.7 9479 3.53 21 10771 4.32 24 11963 5.19 27 7352 2.98 17 8302 3.43 18.5 9883 4.31 22 11191 5.21 26 8694 4.16 20 10357 5.20 24 9178 5.01 22 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 41 Roof Upblast/Sidewall Exhaust Size-300HP: CUBE CWB 50 3.0 (1270) 5 700 3 *36 HP CU EM ST SY HIS FT TO EF EL 0 70 TO 0 CT 61 0 0.0 SE 4 5 T 0 5 2 DO 0 55 48 0.5 100 3527⁄32 77 TH 1.0 O CWB (910) HP LE Static Pressure (in. wg) 200 1.5 45 10 CUBE 300 2 5 88 40 (1016) 400 2.0 HP P 1 H 3/4 HP 1/2 1¾ (44) 500 HP /2 11 (737) Static Pressure (Pa) (914) 29 RPM (Belt) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m RVE 2.5 600 HP N 6 8 10 12 Volume (cfm x 1000) 50 (1270) 383⁄8 0 2 4 6 8 10 12 14 16 18 20 3 (975) Volume (m /hr x 1000) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *36 (914) Motor HP Fan RPM 0.5 0.75 1 ^Approximate Weight Damper Size Roof/Wall Opening CUBE CWB 313(142) 30 x 30 (762 x 762) 32½ x 32½ (826 x 826) 313(142) 25 x 25 (635 x 635) 25½ x 25½ (648 x 648) Static Pressure in Inches wg 1.25 1.5 1.75 2 2.25 2.5 2.75 300HP CFM BHP Sones CFM 485 BHP Sones CFM 555 BHP Sones CFM 610 BHP Sones CFM 700 BHP Sones CFM 770 BHP Sones CFM 828 BHP Sones CFM 885 BHP Sones CFM 938 BHP Sones CFM 991 BHP Sones CFM 1045 BHP Sones 460 1/2 CWB • CUBE 3/4 1 11⁄2 2 CUBE 3 5 3125 0.44 7.3 3639 0.52 7.9 4788 0.77 10.4 5549 1.00 12.4 6741 1.47 16.0 7613 1.91 18.6 8324 2.34 21 9014 2.83 23 9649 3.34 26 10275 3.90 30 10909 4.54 35 3651 0.76 9.9 4731 1.03 11.3 6149 1.53 15.2 7107 2.00 18.1 7879 2.45 21 8603 2.94 23 9262 3.46 26 9913 4.03 29 10570 4.68 34 MAXIMUM BHP AT A GIVEN RPM = (RPM/602)3 MAXIMUM RPM = 1045 TIP SPEED (ft/min) = RPM x 7.983 MAXIMUM MOTOR FRAME SIZE = 213T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/5.50 5390 1.57 14.0 6535 2.06 17.4 7373 2.52 20 8150 3.03 23 8859 3.57 26 9546 4.16 29 10222 4.82 34 5814 2.09 16.2 6776 2.57 19.1 7678 3.12 22 8413 3.66 25 9133 4.26 28 9855 4.94 33 4684 1.99 16.0 6059 2.58 18.3 7062 3.15 21 7923 3.73 24 8711 4.35 28 9455 5.04 32 6353 3.14 21 7331 3.76 23 8201 4.41 27 9054 5.13 31 6624 3.73 23 7641 4.44 26 8533 5.17 31 6946 4.39 25 8002 5.21 30 7330 5.15 28 6463 4.99 27 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 42 Roof Upblast/Sidewall Exhaust Size-300XP: CUBE 50 5 (1270) 5 1200 P H 3H SYST THIS T OF 14 LEF 25 THE 12 11 30 ELE CT TO 2 1 0 0 DO NO 200 45 99 90 TS Static Pressure (in. wg) Static Pressure (Pa) P H 400 4 3/ CUBE HP (1016) 600 3 1 1¾ (44) 800 HP /2 11 (737) 90 16 HP (914) 29 40 EM C 2 4 URVE P 1000 *36 RPM (Belt) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m 0 0 0 1 2 3 4 5 6 7 8 9 Volume (cfm x 1000) 0 2 4 6 8 10 12 14 3 Volume (m /hr x 1000) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. Motor HP Fan RPM 1 1.25 1.5 2 CUBE ^Approximate Weight Damper Size Roof/Wall Opening Static Pressure in Inches wg 2.5 3 313 (142) 30 x 30 (762 x 762) 32½ x 32½ (826 x 826) 3.5 4 4.5 4.75 300XP 790 3/4 900 1 990 1060 1 ⁄2 1 1130 2 1245 1335 3 1425 1493 5 1560 1690 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 1776 0.48 9.4 2958 0.79 12.2 3619 1.04 14.6 4073 1.25 16.5 4511 1.48 18.9 5182 1.92 22 5695 2.32 24 6199 2.78 27 6574 3.16 29 6941 3.57 31 7643 4.47 36 2273 0.75 11.3 3167 1.05 13.4 3708 1.28 15.3 4201 1.53 17.8 4930 1.99 21 5465 2.40 24 5983 2.86 26 6369 3.25 28 6746 3.67 30 7464 4.57 35 2538 1.00 12.8 3255 1.28 14.4 3833 1.56 16.8 4648 2.04 20 5220 2.47 23 5768 2.95 25 6164 3.34 28 6549 3.76 30 7284 4.68 34 MAXIMUM BHP AT A GIVEN RPM = (RPM/972)3 MAXIMUM RPM = 1690 TIP SPEED (ft/min) = RPM x 5.825 MAXIMUM MOTOR FRAME SIZE = 213T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/5.50 2773 1.46 15.6 3943 2.08 18.6 4648 2.56 21 5286 3.07 24 5722 3.49 26 6143 3.93 28 6920 4.87 33 2705 1.86 17.9 3905 2.53 19.4 4695 3.14 22 5200 3.58 24 5684 4.05 27 6528 5.04 31 3886 3.03 21 4550 3.57 23 5134 4.12 25 6091 5.16 30 3646 3.37 22 4441 4.02 24 5587 5.24 29 3049 3.50 24 4951 5.14 28 4100 4.88 28 3070 4.32 28 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 43 Roof Upblast/Sidewall Exhaust Size-360: CUBE 585⁄8 2.0 5 HP (1489) 3H RPM (Belt) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m P 400 RV E CU EM ST SY IS TH OF FT LE E T EC EL T NO 0 5 32 S 0 36 40 TO 0 TH 46 Static Pressure (Pa) 5 HP P DO 0.0 0 69 50 4 0.5 100 0 0 58 P 1H CUBE 2H 200 3/ (1168) 1.0 1/ 1¾ (44) 300 HP /2 11 293⁄8 (746) Static Pressure (in. wg) P (994) 46 2H 1.5 *391⁄8 0 5 10 15 20 Volume (cfm x 1000) 0 10 20 30 3 Volume (m /hr x 1000) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. Motor HP Fan RPM 0 0.125 0.25 8092 0.37 6.9 8631 0.44 7.7 9845 0.66 10.2 10789 0.87 12.7 12408 1.32 16.8 13621 1.74 20 14646 2.17 22 15644 2.64 23 16642 3.18 25 17640 3.78 27 18611 4.44 30 7206 0.42 5.9 7820 0.50 6.8 9142 0.72 9.4 10153 0.94 11.9 11862 1.40 16.5 13125 1.83 20 14184 2.26 22 15212 2.74 23 16236 3.29 25 17257 3.90 27 18248 4.57 29 6023 0.43 5.4 6755 0.52 6.0 8299 0.77 8.5 9426 0.99 11.1 11281 1.48 15.8 12602 1.92 19.8 13705 2.36 21 14769 2.84 23 15826 3.40 25 16873 4.02 27 17884 4.69 28 CUBE ^Approximate Weight Damper Size Roof/Wall Opening Static Pressure in Inches wg 0.375 0.5 0.75 440 (200) 36 x 36 (914 x 914) 38½ x 38½ (978 x 978) 1 1.25 1.5 1.75 360 300 1/2 320 3/4 365 1 400 11⁄2 460 2 505 543 3 580 617 5 654 690 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 5256 0.51 6.6 7286 0.78 8.0 8556 1.02 10.3 10587 1.53 15.1 12022 1.99 19.0 13209 2.45 21 14306 2.94 22 15391 3.50 24 16466 4.13 26 17504 4.81 28 5767 0.74 8.3 7575 1.02 9.9 9814 1.55 14.5 11359 2.04 18.6 12606 2.50 20 13783 3.02 22 14942 3.60 24 16056 4.24 26 17115 4.93 28 MAXIMUM BHP AT A GIVEN RPM = (RPM/396)3 MAXIMUM RPM = 690 TIP SPEED (ft/min) = RPM x 9.425 MAXIMUM MOTOR FRAME SIZE = 213T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/7.25 7809 1.52 13.5 9878 2.06 17.9 11302 2.56 19.3 12597 3.10 21 13862 3.71 23 15084 4.39 25 16236 5.11 27 9606 2.52 18.2 11287 3.13 20 12684 3.76 22 14000 4.46 23 15243 5.21 25 9381 3.02 18.4 11227 3.73 21 12831 4.48 22 14187 5.26 24 11217 4.38 21 12985 5.25 23 11290 5.09 22 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 44 Roof Upblast/Sidewall Exhaust Size-360HP: CUBE 585⁄8 3.0 (1489) 700 E MC STE SY HIS FT TO EF EL TH 55 TO 1.0 CT 5 44 SE 0 NO T 0.5 5 50 LE Static Pressure (in. wg) 5 5 Static Pressure (Pa) 86 75 5 63 200 P CUBE 300 1.5 P 46 (1168) 400 2.0 1H 1¾ (44) 500 P 2H P /2 H 11 (746) 3H (994) 293⁄8 URV P H *391⁄8 HP /2 71 5 2.5 600 RPM (Belt) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m 100 DO 0 0.0 0 5 10 15 20 Volume (cfm x 1000) 0 5 10 15 20 25 30 3 Volume (m /hr x 1000) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. Motor HP Fan RPM 0.5 0.75 1 CUBE ^Approximate Weight Damper Size Roof/Wall Opening Static Pressure in Inches wg 1.25 1.5 1.75 440 (200) 36 x 36 (914 x 914) 38½ x 38½ (978 x 978) 2 2.25 2.5 2.75 360HP 420 1 440 11⁄2 505 2 555 595 3 635 695 5 755 781 71⁄2 824 865 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 6407 0.90 9.6 7003 1.03 10.8 8765 1.52 15.3 10029 1.97 17.2 10996 2.40 18.9 11934 2.87 21 13321 3.70 24 14688 4.68 28 15275 5.15 30 16232 6.00 31 17129 6.89 33 7539 1.57 14.3 9046 2.06 16.2 10129 2.50 17.7 11157 3.00 19.5 12662 3.86 23 14086 4.86 27 14693 5.34 29 15689 6.20 29 16631 7.11 32 MAXIMUM BHP AT A GIVEN RPM = (RPM/434)3 MAXIMUM RPM = 865 TIP SPEED (ft/min) = RPM x 9.425 MAXIMUM MOTOR FRAME SIZE = 213T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/7.25 7766 2.08 15.4 9094 2.57 16.8 10276 3.09 18.2 11902 3.98 22 13434 5.01 26 14086 5.51 28 15137 6.40 27 16105 7.32 30 7488 2.49 16.1 9171 3.12 17.8 11053 4.07 20 12734 5.14 25 13410 5.64 27 14511 6.54 28 15544 7.50 29 7329 2.95 17.3 10026 4.09 20 11922 5.23 24 12681 5.75 27 13869 6.69 29 14933 7.64 29 8393 3.92 19.6 10973 5.24 23 11831 5.81 26 13127 6.78 28 14315 7.79 29 9593 5.10 22 10852 5.79 24 12290 6.82 26 13565 7.87 28 9149 5.51 23 11354 6.79 25 12738 7.89 27 9683 6.48 24 11789 7.83 25 10197 7.50 23 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 45 Roof Upblast/Sidewall Exhaust Size-360XP: CUBE 585⁄8 6 (1489) 7 1400 1/ 2 5 HP 3H EM C SYST THIS 13 T OF 00 LEF 10 HE 95 95 OT 2 TT 0 760 EL 1 O NO TS 200 5 87 EC Static Pressure (Pa) 400 CUBE HP 600 3 1 (1168) 800 4 P HP /2 11 1¾ (44) 1000 2H (746) 90 14 (994) Static Pressure (in. wg) P *391⁄8 46 URVE 5 1200 293⁄8 RPM (Belt) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m HP D 0 0 0 2 4 6 8 10 12 Volume (cfm x 1000) 0 5 10 15 20 3 Volume (m /hr x 1000) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. Motor HP Fan RPM 1 1.25 1.5 2 CUBE ^Approximate Weight Damper Size Roof/Wall Opening Static Pressure in Inches wg 2.5 3 440 (200) 36 x 36 (914 x 914) 38½ x 38½ (978 x 978) 3.5 4 4.5 5 360XP 700 1 760 11⁄2 870 2 955 1025 3 1095 1163 5 1231 1300 1395 71⁄2 1490 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 3210 0.81 10.5 4020 1.05 11.1 5243 1.53 13.6 6081 1.97 15.4 6722 2.38 17.1 7351 2.85 19.2 7945 3.36 21 8528 3.91 23 9113 4.54 26 9910 5.50 29 10699 6.61 33 3225 1.01 11.1 4740 1.57 12.7 5679 2.04 15.4 6396 2.47 16.5 7050 2.95 18.4 7669 3.47 21 8278 4.05 23 8881 4.69 25 9693 5.67 28 10496 6.78 32 4112 1.55 12.3 5216 2.08 14.2 6001 2.54 16.2 6724 3.03 17.8 7386 3.57 19.9 8011 4.15 22 8635 4.82 24 9477 5.83 27 10294 6.96 31 MAXIMUM BHP AT A GIVEN RPM = (RPM/748)3 MAXIMUM RPM = 1490 TIP SPEED (ft/min) = RPM x 7.069 MAXIMUM MOTOR FRAME SIZE = 213T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/7.25 3949 1.98 13.0 5035 2.55 14.5 5930 3.13 16.4 6712 3.73 18.6 7422 4.35 21 8125 5.04 23 9009 6.08 26 9871 7.27 30 3264 2.18 13.4 4905 3.07 15.4 5867 3.75 17.3 6711 4.45 19.4 7502 5.21 22 8490 6.30 25 9429 7.52 29 4700 3.54 16.5 5824 4.40 18.5 6764 5.24 21 7905 6.48 24 8907 7.73 27 4551 4.04 18.0 5867 5.15 20 7193 6.48 23 8340 7.89 26 4286 4.52 20 6348 6.37 23 7673 7.90 26 5143 5.87 23 6881 7.78 26 5830 7.34 27 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 46 Roof Upblast/Sidewall Exhaust Size-420: CUBE 653⁄8 2.0 (1661) 5 RPM (Belt) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m E URV MC STE SY HIS FT TO EF EL TH TO CT 30 28 5 0 5 SE T 5 0 LE Static Pressure (in. wg) Static Pressure (Pa) 0 60 NO 0 5 52 38 35 24 DO 0.0 0 0.5 100 0 44 HP CUBE 1/2 200 1.0 P 1H P H (1321) 3/4 1¾ (44) 300 P P 2H /2 H 11 351⁄4 (895) HP /2 71 P 1.5 (1137) 52 HP 3H 400 *443⁄4 4 8 12 16 20 24 28 Volume (cfm x 1000) 0 10 20 30 40 3 Volume (m /hr x 1000) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. Motor HP Fan RPM 0 0.125 0.25 9353 0.31 6.5 10416 0.43 7.2 11904 0.64 8.3 12966 0.82 9.4 14879 1.24 11.9 16367 1.65 14.4 17643 2.07 17.2 18706 2.47 17.7 22319 4.19 23 24020 5.23 26 25508 6.26 29 7846 0.37 6.0 9104 0.50 6.7 10785 0.73 7.7 11959 0.94 8.8 14037 1.38 11.2 15629 1.81 13.5 16982 2.24 16.1 18103 2.65 17.1 21817 4.41 22 23553 5.46 25 25069 6.51 29 5075 0.35 5.5 7304 0.53 6.1 9418 0.78 7.1 10781 1.00 8.0 13050 1.46 10.1 14731 1.91 12.4 16148 2.37 14.9 17316 2.81 16.0 21220 4.61 22 23030 5.68 25 24604 6.75 29 CUBE ^Approximate Weight Damper Size Roof/Wall Opening 578 (262) 42 x 42 (1067 x 1067) 44½ x 44½ (1130 x 1130) Static Pressure in Inches wg 0.375 0.5 0.75 1 1.25 1.5 1.75 420 220 1/2 245 3/4 280 1 305 11⁄2 350 2 385 415 3 440 5 525 565 71⁄2 600 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 7419 0.77 6.6 9272 1.02 7.3 11925 1.52 9.4 13791 1.99 11.7 15303 2.45 13.8 16532 2.89 14.7 20560 4.78 21 22417 5.88 25 24027 6.96 28 MAXIMUM BHP AT A GIVEN RPM = (RPM/303)3 MAXIMUM RPM = 600 TIP SPEED (ft/min) = RPM x 11.06 MAXIMUM MOTOR FRAME SIZE = 213T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/8.99 10562 1.54 8.6 12701 2.05 10.7 14363 2.53 13.0 15691 2.98 14.6 19904 4.88 20 21806 6.02 24 23451 7.15 28 9246 1.92 8.5 12028 2.56 10.9 13652 3.07 12.8 18497 5.10 19.1 20544 6.25 23 22295 7.38 27 10151 2.82 10.6 16795 5.20 18.1 19112 6.43 21 21023 7.63 25 14802 5.16 17.6 17437 6.50 21 19561 7.75 24 15398 6.38 21 17884 7.77 24 15479 7.47 26 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 47 Roof Upblast/Sidewall Exhaust Size-480: CUBE 743⁄16 1.8 (1884) 350 1.4 RPM (Belt) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m HP 1.6 5 400 RV E CU EM ST SY HIS FT TO EF EL 0 TH TO CT 5 25 22 0 5 0 SE DO 0 5 28 LE Static Pressure (Pa) 36 31 T 0.0 0 0 49 0.2 5 0.4 50 42 Static Pressure (in. wg) P 0.6 P 100 0.8 2H 1/ CUBE 150 1.0 P (1473) 200 1.2 H 3/4 1¾ (44) 58 250 P 2H P /2 H 11 P (914) 300 1H 36 HP /2 71 3H *481⁄8 (1222) NO 20 5 10 15 20 25 30 Volume (cfm x 1000) 0 5 10 15 20 25 30 35 40 45 50 3 Volume (m /hr x 1000) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. Motor HP Fan RPM 0 0.125 11016 0.33 5.5 12240 0.45 6.3 13770 0.65 7.5 15300 0.89 9.0 17442 1.31 11.1 19278 1.77 12.9 22032 2.64 16.8 24174 3.49 21 26010 4.35 22 28152 5.51 25 29988 6.66 28 8924 0.39 4.9 10490 0.53 5.8 12261 0.73 7.0 13988 0.98 8.5 16332 1.43 10.6 18274 1.90 12.5 21153 2.79 16.5 23373 3.65 20 25266 4.52 21 27464 5.70 24 29342 6.86 27 0.25 CUBE ^Approximate Weight Damper Size Roof/Wall Opening 675 (306) 48 x 48 (1219 x 1219) 50½ x 50½ (1283 x 1283) Static Pressure in Inches wg 0.375 0.5 0.625 0.75 1 1.25 1.5 480 180 1/2 200 3/4 225 1 250 11⁄2 285 2 315 3 360 395 5 425 460 71⁄2 490 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 7688 0.52 5.3 10132 0.76 6.6 12248 1.04 8.2 14991 1.52 10.0 17116 2.01 11.8 20222 2.93 16.1 22572 3.81 20 24521 4.69 21 26776 5.89 24 28697 7.06 27 MAXIMUM BHP AT A GIVEN RPM = (RPM/246)3 MAXIMUM RPM = 490 TIP SPEED (ft/min) = RPM x 12.63 MAXIMUM MOTOR FRAME SIZE = 213T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/11.72 9988 1.03 7.9 13240 1.55 9.6 15719 2.08 11.3 19142 3.05 15.3 21605 3.94 19.2 23679 4.85 20 26064 6.07 23 28051 7.26 26 11154 1.52 9.2 14033 2.09 10.4 17848 3.10 14.7 20621 4.07 18.5 22764 4.98 19.4 25219 6.22 22 27291 7.43 25 11996 2.03 10.2 16410 3.12 13.7 19343 4.11 17.6 21766 5.09 18.7 24373 6.37 22 26497 7.59 25 14749 3.08 12.7 18035 4.13 16.6 20556 5.12 17.7 23399 6.46 21 25704 7.75 24 14722 3.97 14.9 17922 5.09 15.6 21163 6.52 18.5 23674 7.85 22 18582 6.42 18.7 21437 7.84 20 18846 7.67 24 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 48 Direct Drive Specifications Model CUE Options and Accessories For Direct Drives UL/cUL Listed • Fans shall be Listed by Underwriters Laboratory for UL/cUL 705 for all electrical components. • Fans shall be Listed by Underwriters Laboratory for UL/cUL 762 for all electrical components and grease removal. Curb Extensions Spun aluminum exhaust fans shall be upblast centrifugal direct drive type. The fan wheel shall be centrifugal backward-inclined, constructed of aluminum and shall include a wheel cone carefully matched to the inlet cone for precise running tolerances. Wheels shall be statically and dynamically balanced. The fan housing shall be constructed of heavy-gauge aluminum with a rigid internal support structure. The windband shall be one-piece and 100% continuously welded to the one-piece aluminum curb cap. Motors shall be mounted out of the airstream on vibration isolators. Fresh air for motor cooling shall be drawn into the motor compartment through a ten-square-inch tube free of discharge contaminants. Motors and drives shall be readily accessible for maintenance. A disconnect switch shall be factory-installed and wired from the fan motor to a junction box within the motor compartment. A conduit chase shall be provided through the curb cap to the motor compartment for ease of electrical wiring. All fans shall bear the AMCA Sound and Air Performance seal. Each fan shall bear a permanently affixed manufacturer’s engraved metal nameplate containing the model number and individual serial number for future identification. A leakproof fan housing shall be constructed with a one-piece windband with an integral rolled bead for added strength. • Shall be mounted between roof curb and roof mounted fans to meet NFPA requirements of 40 inches (1016 mm) minimum discharge above the roof when mounted on a minimum 8-inch (203 mm) high roof curb. Grease Containers • Drain connection shall be constructed of aluminum and allow for single-point drainage of grease, water or other residues. • Grease trap shall include the drain connection and shall be constructed from polypropylene. The unit shall collect grease and water from the fan and extract the grease from the water for ease of grease disposal. Easy Clean Options • Hinge kit shall be constructed of heavy-gauge aluminum hinges and shall include hold-open cables for field installation. • Non-stick wheel shall be constructed of aluminum with a non-stick coating similar to Teflon® as manufactured by DuPont™. • Clean-Out Port shall have a hole on the outside of the windband and a grease repellent compression rubber fit, allowing access to entire wheel for cleaning. Windband Extension • Shall be constructed from heavy-gauge aluminum tube that raises the discharge an additional 36 inches (914 mm). Fans shall be model CUE or CUE-HP as manufactured by Greenheck Fan Corporation in Schofield, Wisconsin, USA. 49 Belt Drive Specifications Model CUBE Each fan shall bear a permanently affixed manufacturer’s engraved metal nameplate containing the model number and individual serial number for future identification. A leakproof fan housing shall be constructed with a one-piece windband with an integral rolled bead for added strength and shall be joined to the curb cap with a continuously welded seam. Fans shall be model CUBE, CUBE-HP or CUBE-XP as manufactured by Greenheck Fan Corporation in Schofield, Wisconsin, USA. Options and Accessories For Belt Drives UL/cUL Listed Spun aluminum exhaust fans shall be centrifugal belt-driven type. The fan wheel shall be centrifugal backward-inclined, constructed of aluminum and shall include a wheel cone carefully matched to the inlet cone for precise running tolerances. Wheels shall be statically and dynamically balanced. The fan housing shall be constructed of heavy-gauge aluminum with a rigid internal support structure. The windband shall be one-piece and 100% continuously welded to the one-piece aluminum curb cap, including all sizes with UL/cUL 762. Motors shall be heavy-duty ball bearing type, carefully matched to the fan load, and furnished at the specified voltage, phase and enclosure. Drive frame assembly shall be constructed of heavy-gauge steel. Motors and drives shall be mounted on vibration isolators, out of the airstream where no steel-tosteel contact between rotating components and the base shall occur. Fresh air for motor cooling shall be drawn into the motor compartment through a tensquare-inch tube free of discharge contaminants. Motors and drives shall be readily accessible for maintenance. Precision ground and polished fan shafts shall be mounted in permanently sealed, lubricated pillow block ball bearings. Bearings shall be selected for a minimum L10 life in excess of 100,000 hours (L50 life of 500,000 hours) at maximum cataloged operating speed. Drives shall be sized for a minimum of 150% of driven horsepower. Pulleys shall be of the cast type, keyed and securely attached to the wheel and motor shafts. Motor pulleys shall be adjustable for final system balancing. A disconnect switch shall be factoryinstalled and wired from the fan motor to a junction box installed within the motor compartment. A conduit chase shall be provided through the base to the motor compartment for ease of electrical wiring. All fans shall bear the AMCA Sound and Air Performance seal. 50 • Fans shall be Listed by Underwriters Laboratory for UL/cUL 705 for all electrical components. • Fans shall be Listed by Underwriters Laboratory for UL/cUL 762 for all electrical components and grease removal. Curb Extensions • Shall be mounted between roof curb and roof mounted fans to meet NFPA requirements of 40 inches (1016 mm) minimum discharge above the roof when mounted on a minimum 8-inch (203 mm) high roof curb. Grease Containers • Drain connection shall be constructed of aluminum and allow for single-point drainage of grease, water or other residues. • Grease trap shall include the drain connection and shall be constructed from polypropylene. The unit shall collect grease and water from the fan and extract the grease from the water for ease of grease disposal. Easy Clean Options • Hinge kit shall be constructed of heavy-gauge aluminum hinges and shall include hold-open cables for field installation. • Non-stick wheel shall be constructed of aluminum with a non-stick coating similar to Teflon® as manufactured by DuPont™. • Clean-Out Port shall have a hole on the outside of the windband and a grease repellent compression rubber fit, allowing access to entire wheel for cleaning. Windband Extension • Shall be constructed from heavygauge aluminum tube that raises the discharge an additional 36 inches (914 mm). Belt Drive Specifications Model USGF Ultimate Steel Grease Fan Motors and drives shall be readily accessible for maintenance. Precision ground and polished 1-inch minimum diameter fan shafts shall be mounted in cast pillow block lubricatable ball bearings. Bearings shall be selected for a minimum L10 life in excess of 100,000 hours (L 50 life of 500,000 hours) at maximum cataloged operating speed. Dual drives shall be sized for a minimum of 150% of driven horsepower. Pulleys shall be of the cast type, keyed and securely attached to the wheel and motor shafts. Motor pulleys shall be adjustable for final system balancing. All fans shall have a dual belt and pulley system. A NEMA-3R disconnect switch shall be factory-installed and wired from the fan motor to a junction box installed outside the motor compartment. Spun steel exhaust fans shall be centrifugal beltdriven type. Fan wheel shall be centrifugal backwardinclined type. The wheel shall be constructed of steel and coated with a non-stick coating similar to Teflon® as manufactured by DuPont™. Wheel shall include a wheel cone carefully matched to the inlet cone for precise running tolerances. Wheels shall be statically and dynamically balanced. The fan housing shall be constructed of 16-gauge steel with a rigid internal support structure and shall be leakproof. The fan housing shall be constructed with a one-piece windband with an integral rolled bead for added strength and shall be joined to the curb cap with a continuously welded seam. The fan windband shall have a Clean-Out Port, a 4-inch diameter hole on the outside of the fan’s windband with a grease repellent compression rubber fit, allowing access to entire wheel for cleaning. Motors shall be heavy-duty ball bearing type, carefully matched to the fan load, and furnished at the specified voltage, phase and enclosure. Drive frame assembly shall be constructed of heavygauge galvanized steel. Motors and drives shall be mounted on heavy-duty true vibration isolators, out of the airstream. Fresh air for motor cooling shall be drawn into the motor compartment through a tensquare-inch tube free of discharge contaminants. All fans shall bear the AMCA Sound and Air Performance seal. Each fan shall bear a permanently affixed manufacturer’s engraved metal nameplate containing the model number and individual serial number for future identification. Fans shall be Listed by Underwriters Laboratory for UL/cUL 762 Listed for all electrical components and grease removal. Hinged base shall be constructed of heavy-gauge hinges and shall include hold-open cables for field installation. Grease trap shall include the drain connection. The unit shall collect grease and water from the fan and extract the grease from the water for ease of grease disposal. Fans shall be model USGF as manufactured by Greenheck Fan Corporation in Schofield, Wisconsin, USA. 51 Belt Drive Specifications Model CWB Motor pulleys shall be adjustable for final system balancing. A disconnect switch shall be factory installed and wired from the fan motor to a junction box installed within the motor compartment. A conduit chase shall be provided through the base to the motor compartment for ease of electrical wiring. All fans shall bear the AMCA Sound and Air Performance seal. Each fan shall bear a permanently affixed manufacturer’s engraved metal nameplate containing the model number and individual serial number for future identification. Spun aluminum exhaust fans shall be centrifugal belt-driven type. The fan wheel shall be centrifugal backward-inclined, constructed of aluminum and shall include a wheel cone carefully matched to the inlet cone for precise running tolerances. Wheels shall be statically and dynamically balanced. The fan housing shall be constructed of heavy-gauge aluminum with a rigid internal support structure. The windband shall be welded to the one-piece curb cap and on all sizes with UL/cUL 762. Motors shall be heavy-duty ball bearing type, carefully matched to the fan load, and furnished at the specified voltage, phase and enclosure. Drive frame assembly shall be constructed of heavy-gauge steel. Motors and drives shall be mounted on vibration isolators, out of the airstream where no steel-to-steel contact between rotating components and the base shall occur. Fresh air for motor cooling shall be drawn into the motor compartment through a ten-square-inch tube free of discharge contaminants. Motors and drives shall be readily accessible for maintenance. Precision ground and polished fan shafts shall be mounted in permanently sealed, lubricated pillow block ball bearings. Bearings shall be selected for a minimum L10 life in excess of 100,000 hours (L 50 life of 500,000 hours) at maximum catalogued operating speed. Drives shall be sized for a minimum of 150% of driven horsepower. Pulleys shall be of the cast type, keyed and securely attached to the wheel and motor shafts. 52 A leakproof fan housing shall be constructed with a one-piece windband with an integral rolled bead for added strength. Fan shall be provided with a mounting plate, which is attached and sealed to the wall prior to locating the entire unit. Fans shall be model CWB or CWB-HP as manufactured by Greenheck Fan Corporation in Schofield, Wisconsin, USA. Options and Accessories For Belt Drives UL/cUL Listed • Fans shall be Listed by Underwriters Laboratory for UL/cUL 705 for all electrical components. • Fans shall be Listed by Underwriters Laboratory for UL/cUL 762 for all electrical components and grease removal. Easy Clean Options • Non-stick wheel shall be constructed of aluminum with a non-stick coating similar to Teflon® as manufactured by DuPont™. Direct Drive Specifications Model CW A leakproof fan housing shall be constructed with a one-piece windband with an integral rolled bead for added strength. Fan shall be provided with a mounting plate, which is to be attached and sealed to the wall prior to locating the entire unit. Fans shall be model CW or CW-HP as manufactured by Greenheck Fan Corporation in Schofield, Wisconsin, USA. Options and Accessories For Direct Drives UL/cUL Listed Spun aluminum exhaust fans shall be upblast centrifugal direct drive type. The fan wheel shall be centrifugal backward-inclined, constructed of aluminum and shall include a wheel cone carefully matched to the inlet cone for precise running tolerances. Wheels shall be statically and dynamically balanced. The fan housing shall be constructed of heavy-gauge aluminum with a rigid internal support structure. Motors shall be mounted out of the airstream on vibration isolators. Fresh air for motor cooling shall be drawn into the motor compartment through a ten-square-inch tube free of discharge contaminants. Motors and drives shall be readily accessible for maintenance. A disconnect switch shall be factory-installed and wired from the fan motor to a junction box within the motor compartment. A conduit chase shall be provided through the curb cap to the motor compartment for ease of electrical wiring. All fans shall bear the AMCA Sound and Air Performance seal. Each fan shall bear a permanently affixed manufacturer’s engraved metal nameplate containing the model number and individual serial number for future identification. • Fans shall be Listed by Underwriters Laboratory for UL/cUL 705 for all electrical components. • Fans shall be Listed by Underwriters Laboratory for UL/cUL 762 for all electrical components and grease removal. Easy Clean Options • Non-stick wheel shall be constructed of aluminum with a non-stick coating similar to Teflon® as manufactured by DuPont™. 53 Vari-Green Specifications Vari-Green Control – Indoor Air Quality – Temperature / Humidity Control to be a packaged indoor air quality control designed to regulate fan speed based on level of temperature and/or relative humidity in a space. Control shall include a Proportional Integral Derivative (PID) feedback loop and shall have labeled terminal strips for easy wiring. Fan shall be direct drive including an electronic commutation (EC) Vari-Green Motor. Control package shall be Vari-Green Indoor Air Quality – Temperature / Humidity Control. Vari-Green® Motor Motor to be an electronic commutation (EC) motor specifically designed for fan applications. AC induction type motors are not acceptable. Examples of unacceptable motors are: Shaded Pole, Permanent Split Capacitor (PSC), Split Phase, Capacitor Start and 3 phase induction type motors. Motors shall be permanently lubricated with heavy-duty ball bearings to match the fan load and prewired to the specific voltage and phase. Internal motor circuitry shall convert AC power supplied to the fan to DC power to operate the motor. Motor shall be speed controllable down to 20% of full speed (80% turndown). Speed shall be controlled by either a potentiometer dial mounted on the motor or by a 0-10 VDC signal. Motor shall be a minimum of 85% efficient at all speeds. Vari-Green® Control - Remote Dial Remote Dial shall be a Vari-Green Control specifically designed to provide 0-10 volt DC signal to Greenheck’s Vari-Green Motor. Vari-Green Control - Two Speed Two speed control shall be a Vari-Green Control specifically designed to allow the Vari-Green Motor to operate at two discrete speeds. Two speed control shall include two dials that may be set at any point between 0 and 10 volts DC and an integral transformer capable of reducing 115/208-240 volt AC power to 24 volt AC power. Vari-Green Control – Indoor Air Quality – VOC (Volatile Organic Compound) Control to be a packaged indoor air quality control designed to regulate fan speed based on level of VOC concentration in a space. Control shall include a Proportional Integral Derivative (PID) feedback loop and shall have labeled terminal strips for easy wiring. Fan shall be direct drive including an electronic commutation (EC) Vari-Green Motor. Control package shall be Vari-Green Indoor Air Quality – VOC Control. Vari-Green Control – Constant Pressure Control to be a packaged constant pressure control designed to regulate fan speed based on demand. Control shall include a Proportional Integral Derivative (PID) feedback loop and shall have all components prewired to labeled terminal strips for easy wiring. System shall include the appropriate pressure tap and preset pressure transducer. Fan shall be direct drive including an electronic commutation (EC) Vari-Green Motor. Control package shall be Vari-Green Constant Pressure Control. Indoor installations shall include pressure tap (duct or room) and control box with integral pressure transducer. Outdoor installations shall include duct pressure tap, pressure transducer, and control box. Control box shall be prewired and in a NEMA-3R weather tight enclosure for mounting outdoors near the fan location. LEED information Greenheck became one of the first manufacturers in the Air Movement and Control industry to join the LEED/green movement when they joined the United States Green Building Council (USGBC) in 2005. Greenheck has been actively researching qualification requirements for our products to meet LEED credits and prerequisites. 54 The Vari-Green® motor significantly helps qualification efforts for the Energy and Atmosphere credits and prerequisites; specifically credit one, Optimize Energy Performance and prerequisite two, Minimum Energy Performance. Severe Duty Specifications Smoke Control Seismic Fan wheel shall be centrifugal backward-inclined, constructed of steel and shall include a wheel cone carefully matched to the inlet cone for precise running tolerances. Fans shall meet International Building Code (IBC) 2006, 2009 and the California Office of Statewide Health Planning and Development (OSHPD) requirements for seismic certifications as listed. • Dual drives shall be sized for a minimum of 150% • OSP - 0148.10 of driven horsepower. • A NEMA-3R disconnect switch shall be factoryinstalled and wired from the fan motor to a junction box installed outside the motor compartment. • Fans shall be Listed by Underwriters Laboratory for UL/cUL 705 for electrical components and UL/ cUL Listed for Emergency Smoke Control Systems [500°F (260°C) for 4 hours and 1,000°F (538°C) for 15 minutes]. • All Greenheck seismically certified models shall Fans shall be Greenheck model CUBE and USGF as specified on pages 50 and 51 with smoke control rated construction option and manufactured by Greenheck Fan Corporation in Schofield, Wisconsin, USA. High Wind Fans shall meet all Greenheck wind load standards and shall contain the following third-party certifications: • Miami-Dade NOA 12-0120.13 • • • • • (CUBE, CUE, CW, CWB) NOA - 12-0501.04 (USGF) Licensed P.E. calculations shall be available for fan per ASCE 7-05 Minimum Design Loads for Buildings and Other Structures for exposure Class C, 60 foot building height, and a type II building. Fan shall be tested in accordance with ASTM E-330-02 Structural Performance of Exterior Windows, Doors, Skylights and Curtain Walls by Uniform Static Air Pressure Difference and Florida Building Code Test Protocol TAS-201, 202 and 203 at the ASCE 7-05 calculated design pressure. Licensed P.E. calculations for attachment of fan to curb shall be available for ASCE 7-05 determined design pressure. All calculations and testing shall be done by a state licensed P.E. and a certified test lab. be tested to the most severe seismic event on the Spectral Response Map per IBC Figures 1613.5 (1-2). Testing shall be performed under the worst case scenario, using the highest mapped seismic load, highest level occupancy category, worst case site class, and highest code mandated importance factor. • Fans shall be shake table tested in accordance with ICC ES AC-156, in which the fans are physically subjected to the same or greater forces as experienced during a seismic event. • For applications which are not covered by California OSHPD standards, Greenheck seismic model CUBE and CUE shall be certified by a thirdparty engineering firm to IBC 2009, 2012 and ASCE 7-05 standards. • Greenheck seismic model CUBE and CUE has been certified to IBC 2009, 2012, ASCE 7-05 and California OSHPD standards through engineering calculations and shake table testing of all models by independent third-party engineering firms. Fans shall be Greenheck model CUBE, CUE, CW, CWB and USGF as specified on pages 49-53 with seismic rated construction option and manufactured by Greenheck Fan Corporation in Schofield, Wisconsin, USA. Fans shall be Greenheck model CUBE, CUE CW, CWB and USGF as specified on pages 49, 50 and 51 with high wind-resistant construction option and manufactured by Greenheck Fan Corporation in Schofield, Wisconsin, USA. 55 Quick Delivery and Quick Build Programs Greenheck Fan Corporation offers an extensive selection of Quick Delivery (QD) and Quick Build (QB) offerings. The QD program is Greenheck’s stock program and the QB program offers configurable fans in one, three, five, or ten days. Hundreds of in stock ventilation products and accessories are available for shipment to your jobsite in less than 24 hours from our strategically located warehouses throughout the world. The Greenheck Stock and Quick Build catalog is a great resource for specific options and accessories available with QD and QB fans. Model Size CUE 099 through 121, 141 through 180 CW 065 through 095, 101, 121 and 141 CUBE 101 through 121, 141 through 200, 240 & 300 CWB 141 and 180 HP CUBE 141HP, 180HP and 240HP all CUE, CW 060 through 200 CUBE 099, 131, 220, 360 through 480 CWB 099 through 131, 161, 200 through 300 High Pressure CUE, CW 141HP through 180HP High Pressure CUBE 101HP, 161HP, 200HP, 220HP, 300HP & 360HP High Pressure CWB 101HP through 300HP Best Available Program In Stock 1 Day Extended Pressure 161XP through 360XP CUBE Building Value in Air Greenheck delivers value to mechanical engineers by helping them solve virtually any air quality challenges their clients face with a comprehensive selection of top quality, innovative airrelated equipment. We offer extra value to contractors by providing easy-to-install, competitively priced, reliable products that arrive on time. And building owners and occupants value the energy efficiency, low maintenance and quiet dependable operation they experience long after the construction project ends. Our Commitment As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties. P.O. Box 410 • Schofield, WI 54476-0410 • Phone (715) 359-6171 • greenheck.com Prepared to Support Green Building Efforts 00.F&V.1003 R4 8-2013 IP Copyright © 2013 Greenheck Fan Corp.