DC303 - Smar
Transcription
DC303 - Smar
• Discrete I/O connected direct onto Profibus-PA • Input and Output Function Blocks, including Flexible Function Block (FFB) for logic execution • Power, Control and I/O integrated in the same hardware • Mix Profibus with conventional devices •Reduce wiring cost DC303 Description Until all types of devices are available with Profibus-PA systems, they will have to be a hybrid nature accepting both Profibus and conventional signals. A mixed traditional and Profibus environment is inevitable during the transition to a Profibus technology. DC303 Remote I/O makes integration of Profibus and conventional I/O easy. Discrete devices such as pressure switches, push buttons, on/off valves, pumps and conveyors are integrated to the system over the Profibus-PA field-level network using DC303. It is a single integrated easy to use piece of equipment including power, control, networking and I/O under one compact device requiring less panel space than other solutions. The DC303 is an integral part of SYSTEM302 but also integrates into other systems supporting Profibus. Easy Installation The DC303 Remote I/O units can be distributed into the field where they are mounted close to the conventional devices without the need to run the conventional wiring to the control room. The unit may be installed close to the sensors and actuators, thereby eliminating long wire runs and associated marshalling panels and cable trays for the conventional I/O, with subsequent savings further reducing overall system cost. Use DC303 to make it possible to distribute I/O at various locations in the field and connect them via Profibus-PA. DC303 is ideal to connect motor control centers, variable speed drives, and electrical actuators and motor operated valves to Profibus-PA. The DC303 is a simple low-cost DIN-rail mounted unit. It can optionally be supplied preinstalled in an enclosure ready for field mounting. Easy Configuration The DC303 is fully configured through the SYSTEM302 or any other Profibus configuration tool based on EDDL or FDT/DTM. Function Blocks The DC303 has 16 Discrete Input (DI) blocks and 8 Discrete Output (DO) blocks. Conventional discrete I/O now works together with pure Profibus devices on the same network and in the same loop. Output function blocks include standard Profibus-PA safety mechanism in case of failures. Inputs and outputs are isolated from each other and the Profibus network in groups of eight channels. LEDs are used to indicate active outputs and inputs. 2 Description DC303 Function blocks PHY DISCRETE INPUT DISCRETE OUTPUT TRD Block This block contains data that is specific to the hardware that is associated with the resource. The DI block takes the manufacture's discrete input data, selected by channel number, and makes available to other function block at its output. The DO block converts the value in SP_D to something useful for the hardware found at the CHANNEL selection. Transducer block that allows the inputs and outputs to interface with discrete function blocks, and allows setting the FFB to provide logic such as AND, OR, XOR, NOT etc. as well as SR flip-flops, RS flip-flops, Timer On Delay, Timer Off Delay, Timer Pulse, Counter Up, Counter Down. Based on structured text language, provides an easy way to generate the logic implementation. Technical Characteristics General Communication Profibus-PA on 31.25 Kbit/s voltage mode in compliance with IEC 61158-2. Current consumption 150 mA from Vdc power supply. quiescent Turn-on Current 400 mA during the first 20 s after power Turn-on Time Approximately 10 seconds. Update Time Approximately 60 ms. The update time is related to the update of the inputs and outputs. Output Impedance Non-intrinsic safety from 7.8 kHz - 39 kHz should be greater or equal to 3 kΩ. Intrinsic safety output impedance (assuming an IS barrier in the power supply) from 7.8 kHz - 39 kHz should be greater or equal to 400 Ω. Function Blocks Up to 16 Discrete Input Function Blocks (DIs) and up to 8 Discrete Output Function Blocks (DOs). The DC303 has a Built-in Flexible Function Block (FFB) for logic execution such as: AND, OR, XOR and NOT. Functions as: Timer On-Delay, Timer Off-Delay, Timer Pulse, Pulse Counter Down (CTD), Pulse Counter Up (CTU), Flip-Flop RS and Flip-Flop SR. Vibration Effect Meets SAMA PMC 31.1. Temperature Limits Housing Operation: -40 to 85ºC (-40 to 185 ºF). Storage: -40 to 110ºC (-40 to 230 ºF). Housing Shell and Base: Polycarbonate, 10% Glass Filled; Terminals: Pressure Plate /Terminal Screws: Zinc Plated, Yellow Chromated Steel; Temperature rating: 110ºC (230 ºF) UL94VO; Protection: it has IP20 rating (finger protected) and meets VBG4 and other European accident prevention requirements. It can optionally be supplied preinstalled in an enclosure ready for field mounting. Configuration Via Profibus Communication using tools based on EDDL or FDT/DTM. Mounting Using DIN rail (TS35-DIN EN 50022 or TS32-DIN EN50035 or TS15-DIN EN50045. 3 DC303 Technical Characteristics Inputs The input senses the DC input voltage and converts it into a True (ON) or False (OFF) logic signal.It has 1 optically isolated group of 16 inputs to detect 24 Vdc. Architecture Number of Inputs: 16. Isolation Optical Isolation up to: 5000 Vac. External Power Voltage Source for Inputs: 18 - 30 Vdc; Typical Consumption per group: 120 mA (all inputs ON); Power indicator: Green LED. Inputs ON State Level (True Logic): 15 - 30 Vdc; OFF State Level (False Logic): 0 - 5 Vdc; Typical Impedance: 3.9 KΩ; Status display: Red LED. Switching Information Wiring Time from "0" to "1": 30 µs; Time from "1" to "0": 50 µs. One wire: 14 AWG (2 mm 2); Two wires: 20 AWG (0.5 mm 2). Outputs The outputs are designed with open collector NPN transistors that are able to drive relays, solenoids and other DC loads with up to 0.5 A per output. All channels within a group share the same ground whereas groups are isolated from each other and from the Profibus network. Architecture Number of Outputs: 8. Isolation Optical Isolation up to: 5000 Vac. External Power Voltage Source for Outputs: 20 - 30 Vdc; Maximum Consumption 35 mA; Power indicator: Green LED. Outputs Maximum Switched Voltage: 30 Vdc; Maximum Saturation Voltage: 0.55 V @ 0.5 A; Maximum Current per Output: 0.5 A; Status Display: Red LED; Indicator Logic: ON when the transistor is on; Maximum Leakage Current: 100 µA @ 35 Vdc. Independent Protection per Output Thermal Shutdown: 165 ºC; Thermal Hysteresis: 15 ºC; Overcurrent Protection: 1.3 A @ 25 Vdc maximum; Clamp Diode. Switching Information Time from "0" to "1": 250 µs; Time from "1" to "0": 3 µs. Wiring One wire: 14 AWG (2 mm2); Two wires: 20 AWG (0.5 mm2). 4 Spare Parts NAME Main Electronic Board I/O Board Interface Board Housing CODE 400-1221 400-1223 400-1222 400-1224 Ordering Code MODEL Description DC303 1 group of 16 24 Vdc optically isolated inputs. 1 group of 8 optically isolated open collector outputs. 5 DC303 Dimensions DC303 140.0 14.4 44.5 R2 60.5 12 9 8 8 8 12 12 12 21.5 21.5 21.5 38.3 90.0 38.3 10 8.5 8,5 127.5 6 4 - 20 mA Outputs 7 rete isc e In D iscret D t Ou FOUNDATION TM H1 I.S. Fiber Optic Ring DC302 (Remote I/O) DF100 4 - 20 mA Inputs Channel 1 Intrinsic Safety Barrier FOUNDATION TM FISCO Communication Server Channel 8 DFI302 Redundant Controller Communication Server All-in-one Station PA Maintenance and Asset Management DP DFI302 PROFIBUS DP and PA et ern Eth Maintenance DFI302 Redundant Controller Communication Server Operation HI302 HART/FOUNDATION TM Fieldbus Engineering DFI302 DeviceNet 4 - 20 mA Router or Firewall Corporate Network Internet I.S. Discrete I/O DFI302 (Cotroller with I/O modules) 4 - 20 mA I.S. Discrete I/O DFI302 AS-i Auto Tuning Advanced Control - MES (Manufacturing Execution System) - ERP (Enterprise Resource Planning) - CRM (Customer Relationship Management Communication Server Alarm and Asset Management Maintenance Modbus TCP Modbus RTU Matrix Printer Package Units Legacy Systems CLP F&G ESD Internet Communication Server Laser Printer Server Server SYSTEM302 Architecture DC303 Main Smar Products DC303 Pressure 4-20 mA LD290 Pressure, Level and Flow Density/Concentration LD400 LD1.0 DT301 RD400 LD301 LD291 DT302 LD302 LD292 DT303 LD303 LD293 Pressure Transmitter Level Gauge Economic Capacitive Pressure Transmitter Pressure Transmitter Pressure Transmitter with high performance Intelligent Density / Concentration Transmitter Level Transmitter Position FY301 FY400 FY302 FY303 Valve Positioner Valve Positioner with auto tuning FY301 TP301 FY302 TP302 FY303 TP303 Valve Positioner with remote sensor Temperature PositionTransmitter Junction Box 4-20 mA TT301 4-20 mA TT411 TT302 TT303 Temperature Transmitter TT421 Panel Mounting Temperature Transmitter Head Mouting Temperature Transmitter Configurators HART® Configurator Interface CONF401 HART® Configurator Interface DDCON 100 3 Ways Junction Box JM1 4 Ways Junction Box JM400 Interfaces HART® Configurator for Palm HPC301 8 HART-RS232 Interface HI311 HART-USB Interface Hi321 Main Smar Products DC303 Converters FP302 FP303 Fieldbus to Pneumatic Signal Converter FI302 IF302 IF303 Current to Fieldbus Converter FI303 Fieldbus to Current Converter HART® / Fieldbus HART® / Current Interface HI302 Converter HCC301 Controllers DeviceNet TM DeviceNet Programmable Logical Controller LC700 Interface Universal Fieldbus DFI302 Digital Controller CD600Plus Systems DeviceNet DeviceNet TM ProcessView Process Visualization Tool Studio302 System302 Management Tool DeviceNet Syscon System Configurator TM AssetView On Line Plant Asset Management Tool TM Equipment Database Plant Information Management 9 LogicView IEC61131 Programming Tool TM smar www.smar.com Specifications and information are subject to change without notice. Up-to-date address information is available on our website. web: www.smar.com/contactus.asp DC3 0 3 CE © Copyright 2012 - Smar International - all rights reserved. - August/2013