isolation equipment

Transcription

isolation equipment
isolation equipment
isolation equipment
•Trent Range
•Classic Range
make the switch
I S O L AT I O N
EQUIPMENT
a complete range for every application
As well as our existing ‘Classic’ and ‘Stenton’ ranges, we now
offer our new family of switch disconnectors. The new ‘Trent’
range of isolators, changeovers and fuse combination units is
the most extensive ever offered by Craig and Derricott, and the
largest offered by any European Manufacturer.
Consistent design features throughout the complete range provides
seamless product integration, which is non function dependent.
Ranging from 25A to 1000A and
available in various enclosure
materials and colours.
Selecting an isolation solution from Craig &
Derricott combines excellent performance,
stylish appearance and our reputation for
high quality and total reliability.
• Largest selection in Europe
• Generous cable space in all ratings 25-1000A
• Sheet steel, polycarbonate, die-cast and
stainless steel enclosures
• Easy to install
Need something a bit different?
With our experience in design and manufacture we are able to offer our Bespoke Solutions service.
This enables our experts to provide the ideal solution to your non standard switching requirements.
From a one off to a large production run, we will provide the best solution cost effectively and on time.
introduction
t: +44(0)1543 375541
make the switch
email: [email protected]
Die-Cast enclosures (25A-40A)
General Description
CONSTRUCTION FORMATS
Craig & Derricott has been manufacturing die-cast enclosed
switchgear since 1944. In the Trent range we have incorporated all
of that experience in producing an outstanding product that
has become the standard benchmark against which all others
are compared.
Two purpose designed enclosures cover the complete
range. This includes lid and base mounting versions of the
disconnector interiors.
Continental Style Locking Handle
1L
Lid mounted interior
Base mounted interior
1B
Catalogue Numbers
Switch Disconnectors (0-1)
Rating
Format
Assembly
Form
Finished Red
Finished Grey
2P
DR252
DG252
3P
DR253
DG253
3P+NL*
DR253NL
DG253NL
DR253EB
DG253EB
4P
DR254
DG254
6P
DR256
DG256
6P+2 EB Aux
DR256EB
DG256EB
2P
DRM252
DGM252
(see right)
25A
25A
3P+2 EB Aux
1L
3P
DRM253
DGM253
3P+NL*
DRM253NL
DGM253NL
DRM253EB
DGM253EB
DRM254
DGM254
3P+2 EB Aux
2L
4P
DRM256
DGM256
DRM256EB
DGM256EB
2P
DR402
DG402
3P
DR403
DG403
3P+NL*
DR403NL
DG403NL
DR403EB
DG403EB
4P
DR404
DG404
6P
DR406
DG406
6P+2 EB Aux
DR406EB
DG406EB
2P
DRM402
DGM402
3P+2 EB Aux
1B
3P
DRM403
DGM403
3P+NL*
DRM403NL
DGM403NL
DRM403EB
DGM403EB
DRM404
DGM404
3P+2 EB Aux
4P
2B
6P
DRM406
DGM406
6P+2 EB Aux
DRM406EB
DGM406EB
(see page 2)
A
Die-Cast Padlocking Handle
2L
Lid mounted interior
Base mounted interior
2B
A
B
B
Padlocking
All versions allow the fitting of a
padlock in the ‘Off’ position.
Form 2 construction allows the use of a
single padlock, whilst Forms 1 & 3 will
accept up to three individual locks.
It is recommended that padlocking
devices with a minimum hasp diameter
of 6.4mm are used. This will limit the
movement of the handle away from the
‘Off’ position.
Form 2 can accommodate padlocking
in both the ‘Off’ & ‘On’ positions.
Please add /10 to the cat. No. if
required:- e.g. DRM403/10
Auxiliary Contacts
The ‘EB’ addition to the catalogue
numbers denotes the inclusion of 2 off
early break contacts.
In all cases these are factory fitted to
the isolator interior, and are not
available as a customer addition.
All auxiliary contacts are fully rated and
are designed to open before the main
contacts when switching ‘Off’.
By definition the contacts would be
late make when switching ‘On’.
RANGE
40A
6P
6P+2 EB Aux
Enclosure
Size
TRENT
40A
Catalogue No.
isolation equipment
TRENT
*Removeable link forms part of the isolating switch assembly.
still need more?
craigandderricott.com
isolation
equipment
1
isolation equipment
TRENT
Die-Cast enclosures (25A-40A)
Catalogue Numbers
CONSTRUCTION FORMATS
Changeover Disconnectors (1-0-2)
Rating
Format
Assembly
Form
Finished Red
Finished Grey
CODR252
CODG252
CODR253
CODG253
4P
CODR254
CODG254
2P
CODR402
CODG402
CODR403
CODG403
CODR404
CODG404
(see right)
2P
25A
3P
40A
Catalogue No.
3P
3L
3B
4P
Te c h n i c a l S p e c i f i c a t i o n
Enclosure
Size
(see below)
A
B
Continental Style Locking Handle
3L
Lid mounted interior
Base mounted interior
3B
Isolator Interiors - Data supplied against tests to BS EN 60947-3
Rating (A)
Application
Sym.
Unit
Rated thermal current
Rated insulation voltage
Rated impulse voltage
Ith
Ui
Uimp
A
V
kV
Rated operational current (AC)
A
Rated operational power (AC)
Conditional short circuit current
Minimum mechanical endurance
Icc
kW
kA
mm2
mm2
Nm
Connecting capacity
Category
400/415V - AC21A
400/415V - AC22A
400/415V - AC23A
3 x 400V - AC23
Cycles
Terminal type
Flexible cable
Stranded cable
Tightening torque
25A
40A
25
690
4.0
25.0
25.0
25.0
10.0
6.0
0.3 x 106
40
690
32.0
32.0
28.0
15.0
50.0*
0.5 x 106
2.5 - 6.0
2.5 - 6.0
1.6
10 max
10 max
2.0
*Fuse in circuit - GEC ‘TIS 40’
Enclosures
Material
Die-cast aluminium alloy LM24 (BS 1490)
Finish
Red
Grey
RAL 3020 semi-gloss (textured)
RAL 7035 semi-gloss (textured)
TRENT
Enclosure Dimensions
Entries
2 x M20 on bottom face as std.
Maximum no. of possible entries:Enclosure size A 6 (3 top + 3 bottom)
Enclosure size B 8 (3 top + 3 bottom
+ 1 on both sides)
Mounting
All fixings are internal and within the base
casting. Guide channels are provided to assist
with the fixing screw location.
Handle depth:- Forms 1&3 = 30mm, Form 2 = 34mm
RANGE
size
size
B
A
Hall Lane, Walsall Wood, Walsall, West Midlands WS9 9DP
isolation
equipment
2
Earthing
Terminals are provided on both lid and
base to allow full earth continuity to be
maintained.
f: +44(0)1543 361619
make the switch
t: +44(0)1543 375541
email: [email protected]
Flush Mounting enclosures (25A-63A)
General Description
Craig and Derricott have been manufacturing flush mounting
isolators for more than 60 years, and in that time the design has
evolved to give the features the installers and end users really need.
The assembly consists of a galvanised back box (c/w knockouts) and
stainless steel fascia plate which carries the isolating switch and
locking handle. The fascia plate comes in an attractive brushed finish,
resisting the fingerprint effect often associated with highly
polished surfaces.
Equally at home in kitchens, laboratories, food processing areas,
hospitals and many other areas, this is an elegant, low projection
isolation device.
Typical assembly showing the galvanised
back box and brushed stainless steel
fascia plate.
Catalogue Numbers
Switch Disconnectors (0-1)
Rating
25A
40A
63A
Format
Catalogue No.
Enclosure
Size
(see page 4)
2P
DF252
3P
DF253
3P+NL*
DF253NL
3P+2 EB Aux
DF253EB
4P
DF254
2P
DF402
A
A
B
B
A
3P
DF403
A
B
3P+NL*
DF403NL
B
3P+2 EB Aux
DF403EB
4P
DF404
B
B
2P
DF632
3P
DF633
3P+NL*
DF633NL
3P+2 EB Aux
DF633EB
4P
DF634
C
C
D
D
C
*Removeable link forms part of the isolating switch assembly.
Padlocking
All items allow the insertion of up to
four padlocks in the ‘Off’ position
It is recommended that padlocking
devices with a minimum hasp diameter
of 6.4mm are used. This will limit the
movement of the handle away from the
‘Off’ position.
isolation equipment
TRENT
Auxiliary Contacts
The ‘EB’ addition to the catalogue
numbers denotes the inclusion of 2 off
early break contacts.
In all cases these are factory fitted to
the isolator interior, and are not
available as a customer addition.
All auxiliary contacts are designed to
open before the main contacts when
switching ‘Off’.
By definition the contacts would be
late make when switching ‘On’.
Security
The fixing screws that secure the lid to
the back box are supplied with allen
key heads to give a degree of security.
Fixings with a higher degree of security
can be supplied to order.
TRENT
Installation
Whilst the joint between the isolating switch
and the stainless steel fascia plate is factory
sealed to IP65 min, when installed, the fascia
to mounting surface seal is the responsibility
of the installer.
A continuous bead of moisture resistant
mastic is a simple way of providing a seal,
and can improve the appearance of the final
assembly on an uneven surface.
Handle assembly showing the
multi-padlocking feature
still need more?
craigandderricott.com
RANGE
To maintain the sealing overall, an efficient
bond must be made using some form of
gasketing medium. This is particularly vital on
tiled surfaces where grout lines can channel
moisture down the wall.
isolation
equipment
3
isolation equipment
TRENT
Flush Mounting enclosures (25A-63A)
Te c h n i c a l S p e c i f i c a t i o n
isolator Interiors - Data supplied against tests to BS EN 60947-3
Rating (A)
Application
Rated thermal current
Rated insulation voltage
Rated impulse voltage
Sym.
Unit
Ithe
Ui
Uimp
A
V
kV
Rated operational current (AC)
A
Rated operational power (AC)
Conditional short circuit current
Minimum mechanical endurance
Icc
kW
kA
mm2
mm2
Nm
Connecting capacity
Category
25A
400/415V - AC21A
400/415V - AC22A
400/415V - AC23A
3 x 400V - AC23
Cycles
Terminal type
Flexible cable
Stranded cable
Tightening torque
40A
63A
25
690
4.0
25.0
25.0
25.0
10.0
6.0
0.3 x 106
40
690
4.0
40.0
40.0
40.0
18.5
6.0
0.3 x 106
63
690
4.0
63.0
63.0
63.0
22.0
8.0
0.3 x 106
2.5 - 6.0
2.5 - 6.0
1.6
10 - 16
10 - 25
1.8
16 - 50
16 - 50
2.4
Enclosures
Interior views of a typical assembly showing
the earthing terminals on both components
and the ‘knockouts’ in the back boxes.
Material
Fascia Plate - Stainless steel 304.
1.2mm thick. Brushed finish
Back Box - Sheet steel. 1.4 thick.
Galvanised finish
Entries
Knockouts in back box.
Sealing
Isolating switch to stainless steel fascia
plate - IP65
Mounting Screws
Stainless steel. (M5 x 16 with
‘Allen Key’ head).
Earthing
Separate earthing points on fascia plate
and back box.
TRENT
Enclosure Dimensions
depth
depth
RANGE
size
A
size
B
A: depth = 50mm
B: depth = 75mm
size
C
size
D
Hall Lane, Walsall Wood, Walsall, West Midlands WS9 9DP
isolation
equipment
4
C: depth = 75mm
D: depth = 100mm
f: +44(0)1543 361619
make the switch
t: +44(0)1543 375541
email: [email protected]
Polycarbonate enclosures (25A-63A)
General Description
CONSTRUCTION FORMATS
Switchgear housed in polycarbonate enclosures provides the end
user with several advantages; the most important is the flexibility to
position cable entries and mountings in locations that best suit the
specific site conditions.
Add to this the advantages of chemical resistance,
safe against UV attack, impact resistance, wide operating
temperature band etc., and the polycarbonate option
becomes the starting point for most industrial applications.
Craig and Derricott IP65 sealing as standard
on all assemblies.
Catalogue Numbers
Switch Disconnectors (0-1)
Rating
Format
Catalogue No.
2P
25A
40A
63A
Enclosure
Size
Form 1L
(see page 6)
DP252
3P
DP253
3P+NL*
DP253NL
3P+2 EB Aux
DP253EB
4P
DP254
6P
DP256
6P+2 EB Aux
DP256EB
2P
DP402
3P
DP403
3P+NL*
DP403NL
3P+2 EB Aux
DP403EB
4P
DP404
6P
DP406
6P+2 EB Aux
DP406EB
2P
DP632
3P
DP633
3P+NL
DP633NL
3P+2 EB Aux
DP633EB
4P
DP634
A
B
C
Typical assembly showing the ‘Form 1L’
arrangement, i.e. Lid mounted interior
with continental style moulded locking
handle assembly.
Padlocking
All items allow the insertion of up to
four padlocks in the ‘Off’ position
It is recommended that padlocking
devices with a minimum hasp diameter
of 6.4mm are used. This will limit the
movement of the handle away from
the ‘Off’ position.
Auxiliary Contacts
The ‘EB’ addition to the catalogue
numbers denotes the inclusion of 2 off
early break contacts.
In all cases these are factory fitted to
the isolator interior, and are not
available as a customer addition.
All auxiliary contacts are designed to
open before the main contacts when
switching ‘Off’.
By definition the contacts would be
late make when switching ‘On’.
Security
After installation the lid fixings may be
protected against tampering by utilising
the snap-in covers provided.
*Removeable link forms part of the isolating switch assembly.
TRENT
Catalogue Numbers
Changeover Disconnectors (1-0-2)
Rating
40A
Catalogue No.
2P
CODP252
3P
CODP253
4P
CODP254
2P
CODP402
3P
CODP403
4P
CODP404
(see page 2)
A
B
still need more?
Handle assembly showing the
multi-padlocking feature
craigandderricott.com
RANGE
25A
Enclosure
Size
Form 1L
Format
isolation equipment
TRENT
isolation
equipment
5
isolation equipment
TRENT
Polycarbonate enclosures (25A-63A)
Te c h n i c a l S p e c i f i c a t i o n
isolator Interiors - Data supplied against tests to BS EN 60947-3
Application
Rated thermal current
Rated insulation voltage
Rated impulse voltage
Sym.
Unit
Ithe
Ui
Uimp
A
V
kV
Rated operational current (AC)
A
Rated operational power (AC)
Conditional short circuit current
Minimum mechanical endurance
Icc
kW
kA
mm2
mm2
Nm
Connecting capacity
Enclosure Dimensions
Rating (A)
Category
400/415V - AC21A
400/415V - AC22A
400/415V - AC23A
3 x 400V - AC23
Cycles
Terminal type
Flexible cable
Stranded cable
Tightening torque
25A
40A
63A
25
690
4.0
25.0
25.0
25.0
10.0
6.0
0.3 x 106
40
690
4.0
40.0
40.0
40.0
18.5
6.0
0.3 x 106
63
690
4.0
63.0
63.0
63.0
22.0
8.0
0.3 x 106
2.5 - 6.0
2.5 - 6.0
1.6
10 - 16
10 - 25
1.8
16 - 50
16 - 50
2.4
Enclosures
Material
Polycarbonate
Entries
None - Supplied with plain sides
Finish
Grey
size
A
RAL 7035
Flammability
UL 94
V-2
Fixing centres:- 110(h) x 90(v) x M4 clear
Impact resistance
EN 50102 (+35OC / -25OC)
1K 08/1K 08
Cover gasket
PUR (Polyurethane)
Cover Screws
Stainless steel.
size
Enclosure interior showing the plain side
walls and base
B
Fixing centres:- 90(h) x 188(v) x M4 clear
TRENT
RANGE
size
C
Fixing centres:- 130(h) x 228(v) x M4 clear
Hall Lane, Walsall Wood, Walsall, West Midlands WS9 9DP
isolation
equipment
6
f: +44(0)1543 361619
make the switch
t: +44(0)1543 375541
email: [email protected]
Sheet Steel enclosures (32A-1000A)
Catalogue Numbers
General Description
The Trent range of enclosed switchgear
has been designed to meet today’s
vigorous market requirements for
products that are simple to install and
connect, and meet international
standards of performance and safety.
Switch disconnectors are available in
three forms - finished Red or Grey in
sheet steel, and a stainless option. All
three versions are offered in the same
sized cases per rating.
Sealing to IP65 is standard throughout
the range, including the fuse
combination units.
The steel enclosed items are detailed
here, but there are several other
options within the Trent range.
Please contact our sales staff or visit
our web site to obtain full details.
Switch Disconnectors (0-1)
Rating
63A
125A
160A
200A
250A
Accessories
Neutral Link blocks:-
Stand alone
63A - NL63
125A - NL125
160A - NL160
200A - NL200
250A - NL250
400A - NL400
400A
630A - NL630
630A
Outgoing Terminal Shields
(Switch Disconnectors):-
800A
63A, 125A & 160A Not required
200A - TS200
250A - TS250
400A - TS400
630A - TS630
800A - TS800
1000A - TS1000
Outgoing Terminal Shields
(Changeover Disconnectors):63A & 125A
250A - 800A
1000A
Not required
Factory fitted
Format
TP
TP&N
TP + EB
4P
6P
6P + EB
TP
TP&N
TP + EB
4P
6P
6P + EB
TP&N
4P
TP&N
4P
TP&N
4P
6P
TP&N
4P
6P
TP&N
4P
6P
TP&N
4P
6P
TP&N
4P
6P
SHEET STEEL
STAINLESS
RED
GREY
STEEL
(see page 11)
DR0633
DR0633NL
DR0633EB
DR0634
DR0636
DR0636EB
DR1253
DR1253NL
DR1253EB
DR1254
DR1256
DR1256EB
DR1603
DR1604
DR2003
DR2004
DR2503
DR2504
DR2506
DR4003
DR4004
DR4006
DR6303
DR6304
DR6306
DR8003
DR8004
DR8006
DR10003
DR10004
DR10006
DG0633
DG0633NL
DG0633EB
DG0634
DG0636
DG0636EB
DG1253
DG1253NL
DG1253EB
DG1254
DG1256
DG1256EB
DG1603
DG1604
DG2003
DG2004
DG2503
DG2504
DG2506
DG4003
DG4004
DG4006
DG6303
DG6304
DG6306
DG8003
DG8004
DG8006
DG10003
DG10004
DG10006
DS0633
DS0633NL
DS0633EB
DS0634
DS0636
DS0636EB
DS1253
DS1253NL
DS1253EB
DS1254
DS1256
DS1256EB
DS1603
DS1604
DS2003
DS2004
DS2503
DS2504
DS2506
DS4003
DS4004
DS4006
DS6303
DS6304
DS6306
DS8003
DS8004
DS8006
DS10003
DS10004
DS10006
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2A
2A
2A
2A
3
4
4
4
4
4
4
5
5
5
6
6
6
STAINLESS
case
Size
Changeover Disconnectors (1-0-2)
Auxiliary Contact Sets - (Suitable for both
Changeover & Standard Switch Disconnectors
Rating
Format
SHEET STEEL
STEEL
(see page 11)
63A & 125A (6 pole)
250A - 1000A (6 pole)
AUX2T
Supplied factory fitted only
63A
AUX2T6
125A
Fo r m a t s
250A
TP
Triple Pole
TP&N
Triple Pole & Switched Neutral *
400A
TP + EB
Triple Pole & Aux Contact Set
4P
Four Pole
6P
Six Pole
6P + EB
Six Pole & Aux Contact Set
630A
800A
TP
4P
TP
4P
TP&N
4P
TP&N
4P
TP&N
4P
TP&N
4P
CODR0633
CODR0634
CODR1253
CODR1254
CODR2503
CODR2504
CODR4003
CODR4004
CODR6303
CODR6304
CODR8003
CODR8004
CODG0633
CODG0634
CODG1253
CODG1254
CODG2503
CODG2504
CODG4003
CODG4004
CODG6303
CODG6304
CODG8003
CODG8004
CODS0633
CODS0634
CODS1253
CODS1254
CODS2503
CODS2504
CODS4003
CODS4004
CODS6303
CODS6304
CODS8003
CODS8004
1
1
2
2
3
3
4
4
5
5
5
5
RANGE
GREY
TRENT
RED
Supplied pre-packed as 2 NO + 2 N/C(EB)
63A - 1000A (3 & 4 pole)
case
Size
isolation equipment
TRENT
*If you require a non switched neutral, add the
stand alone neutral link blocks shown under accessories.
still need more?
craigandderricott.com
isolation
equipment
7
isolation equipment
TRENT
Sheet Steel enclosures (32A-1000A)
(Switch Disconnectors)
Data supplied against tests to BS EN 60947-3
Te c h n i c a l S p e c i f i c a t i o n
3&4P 6P 3&4P
Application
Sym. Unit
Category
63
63
125
125
160
200
250 400
630
800 1000
630
800 1000
Rated thermal current
Ith
A
63
63
125
125
160
200
250 400
Rated insulation voltage
Ui
V
690
690
800
690
800
800
800 1000 1000 1000 1000
Uimp
kV
8.0
4.0
8.0
4.0
8.0
8.0
8.0 12.0 12.0 12.0 12.0
Ie
A
400V - AC21A
63
56
125
114
160
200
250 400
630
800 1000
400V - AC22A
63
45
125
84
160
200
250 400
630
800 1000
400V - AC23A
63
48
125
82
160
160
250 400
630
800 1000
690V - AC21A
63
-
125
-
160
180
250 400
630
800 1000
690V - AC22A
50
-
100
-
125
160
200 315
500
630
800
690V - AC23A
32
-
80
-
80
80
160 250
315
500
630
110V - DC21A (II)
63
-
160
-
160
200
315 630
630
800 1000
110V - DC23A (I)
63
-
125
-
160
160
250 400
630
800 1000
230V - DC21A (I)
63
-
125
-
160
160
250 400
630
800 1000
230V - DC23A (I)
63
-
125
-
125
125
250 400
630
800 1000
3x400V - AC23A
30
22
55
37
70
70
132 220
355
450
560
3x690V - AC23A
30
-
75
-
75
75
160 250
370
450
630
Rated impulse voltage
Rated operational current (AC)
Rated operational current (DC)
Rated operational power
Ie
Pe
A
kW
Short circuit making capacity
Icm
kA
Peak value
5
-
8.5
-
10
10
14
26
26
34
42
Short circuit withstand (1 sec)
Icw
kA
RMS value
3
-
5
-
6
6
10
16
16
19
35
Minimum mechanical endurance
Cycles
Minimum electrical endurance
400V - AC23
Connecting capacity
30,000 30,000 30,000 30,000 30,000 30,000 20,000 10,000 10,000 10,000 10,000
1,500 1,500 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000
TRENT
-
Terminal type
mm
Cu. Width/Conn.
-
-
-
-
-
26/
M10
25/ 25/
M10 M10
30/
M10
mm2
Rigid cable
25
16-50
95
16-50
95
120
185
240
240 2x240
Nm
Tightening torque
2
2.4
4
2.4
4
13
18
24
24
40/
M14
45
500
60/
M16
80
Auxiliary Contacts
Add-on auxiliary contact sets containing 2 N/O + 2 N/C (EB) contacts are available for
all ratings apart from the 63A & 125A 6 pole options which have the auxiliaries supplied factory fitted.
RANGE
Ratings:- Add-on auxiliary sets
63A & 125A 6 pole
Ithe - 16A, (16A - Resistive loads, 4A - Inductive loads at 250V ac)
Ithe - 63A , (Fully rated as above)
Hall Lane, Walsall Wood, Walsall, West Midlands WS9 9DP
isolation
equipment
8
Rating (A)
3-6P
6p
f: +44(0)1543 361619
make the switch
t: +44(0)1543 375541
email: [email protected]
Sheet Steel enclosures (32A-1000A)
(Changeover Disconnectors)
Data supplied against tests to BS EN 60947-3
Te c h n i c a l S p e c i f i c a t i o n
Rating (A)
Application
Sym. Unit
Category
63
125
250
400
630
800
1000
Rated thermal current
Ith
A
63
125
250
400
630
800
1000
Rated insulation voltage
Ui
V
690
800
800
1000
1000
1000
1000
Uimp
kV
8.0
8.0
8.0
8.0
12.0
12.0
12.0
Ie
A
400V - AC21A
63
125
250
400
630
800
1000
400V - AC22A
63
125
250
250
630
800
1000
400V - AC23B
63
125
200
400
400
630
1000
690V - AC21A
63
125
250
400
630
800
1000
690V - AC22A
50
100
200
315
500
630
800
690V - AC23B
32
80
125
160
250
315
630
3x400V - AC23A
30
55
100
125
200
315
501
3x690V - AC23A
30
75
108
138
216
272
544
Rated impulse voltage
Rated operational current (AC)
Rated operational power
Pe
kW
Short circuit making capacity
Icm
kA
Peak value
5
8.5
12
12
20
20
32
Short circuit withstand (1 sec)
Icw
kA
RMS value
3
5
8
8
13
13
25
Minimum mechanical endurance
Cycles
30000
30000
10000
10000
10000
10000
10000
Minimum electrical endurance
400V - AC23
1500
1000
1000
1000
1000
500
500
Connecting capacity
-
Terminal type
mm
Cu. Width/Conn.
-
-
mm2
Rigid cable
25
95
240
240
2x240
2x240
-
Nm
Tightening torque
2
4
24
24
45
45
55
isolation equipment
TRENT
25/M10 25/M10 40/M12 40/M12 50/M14
Interior assembly showing a
typical chassis plate assembly
63A Switch Disconnector
Add-on auxiliary contact sets containing 2 N/O + 2 N/C (EB) contacts are available for all ratings.
Ratings:- Add-on auxiliary sets
63A & 125A 6 pole
Ithe - 16A, (16A - Resistive loads, 4A - Inductive loads at 250V ac)
Ithe - 63A , (Fully rated as above)
still need more?
craigandderricott.com
RANGE
Auxiliary Contacts
TRENT
View from below showing
the removable gland
plate in position
isolation
equipment
9
isolation equipment
TRENT
Sheet Steel enclosures (32A-1000A)
Catalogue Numbers
Accessories
Fuse Combination Units (0-1)
Stand alone
Rating
32A
63A
100A
160A
250A
315A
400A
630A
Format
Sheet Steel
Finished Red Finished Grey
TP&N
TP&N
TP&N
TP&N
TP&N
TP&N
TP&N
TP&N
SFDR0323
SFDR0633
SFDR1003
SFDR1603
SFDR2503
SFDR3153
SFDR4003
SFDR6303
HRC Fuse
Link*
SFDG0323
SFDG0633
SFDG1003
SFDG1603
SFDG2503
SFDG3153
SFDG4003
SFDG6303
(see page 11)
FL32
FL63
FL100
FL160
FL250
FL315
FL400
FL630
63A - NL63
125A - NL125
400A - NL400
630A - NL630
Outgoing
2
2
2
3
3
4
4
5
250A - NL250
Terminal Shields
63A & 100A Not required
160A - TSF160 250A - TSF250 315A - TSF315
400A - TSF400 630A - TSF630
Auxiliary Contact Sets:Supplied pre-packed as 2 NO + 2 N/C(EB)
63A - 100A
AUXSFM1
160A & 630A
AUXSFM2
*Fully rated BS88 HRC fuse links supplied fitted to all fuse combination units,
refs as shown are for replacements only.
Te c h n i c a l S p e c i f i c a t i o n
(Fuse Combination Units)
Data supplied against tests to BS EN 60947-3
Rating (A)
32
63
125
250
400
630
800
Rated thermal current
Ith
A
32
63
100
160
250
315
400
630
Rated insulation voltage
Ui
V
800
800
800
800
800
1000
1000
1000
A4
B1-B2
B1-B4
B1-B4
C1-C3
12.0
Application
Sym. Unit
Fuse-link style
Rated impulse voltage
Rated operational current (AC)
Rated operational power
A
Uimp
kV
Ie
A
Pe
kW
Category
BS88 Type Ref
A1
A2-A3 A2-A3
1000
8.0
8.0
8.0
8.0
8.0
12.0
12.0
400V - AC21A
32
63
100
160
250
315
400
630
400V - AC22A
32
63
100
160
250
315
400
630
400V - AC23A
32
63
100
160
250
315
400
630
690V - AC21A
32
100
125
160
250
315
400
630
690V - AC22A
32
63
100
160
250
315
400
630
690V - AC23A
32
50
80
125
200
250
315
400
3x400V - AC23A
15
30
55
90
132
160
220
355
3x690V - AC23A
25
42
80
110
160
200
250
370
Short circuit withstand current
kA
RMS value
100
100
100
100
100
100
100
100
Short circuit making current
kA
RMS value
50
50
50
100
100
100
100
100
Maximum cut-off current
kA
Peak value
9.1
9.1
12.7
26.3
26.3
43.3
43.3
60.8
Maximum power dissipation
A2S
I2t (x 103)
42
42
120
478
478
1600
1600
4600
Mechanical endurance (Min.)
Cycles
Electrical endurance (Min.)
TRENT
Connecting capacity
400V - AC23
-
10,000 10,000 10,000 10,000 10,000 10,000 10,000 5,000
1,500
1,500
1,500
1,000
1,000
1,000
1,000
1,000
120
240
240
2x185
Terminal type
mm2
Rigid cable
16
16
50
120
mm
Cu. Width/Conn.
-
-
-
25/M8
Nm
Tightening torque
3
3
4
13
30/M10 30/M10 30/M10 40/M12
24
24
24
45
RANGE
Auxiliary Contacts
Add-on auxiliary contact sets containing 2 N/O + 2 N/C (EB) contacts are available for all ratings.
Ratings:- Add-on auxiliary sets
Ithe - 16A, (16A - Resistive loads, 4A - Inductive loads at 250V ac)
Hall Lane, Walsall Wood, Walsall, West Midlands WS9 9DP
isolation
equipment
10
case
Size
Neutral Link blocks:-
f: +44(0)1543 361619
make the switch
t: +44(0)1543 375541
email: [email protected]
Sheet Steel enclosures (32A-1000A)
Dimensions
(Applicable to all finishes and materials)
Dim E
All dimensions in mm
Dim
H
1
2
2A
3
4
5
Dim C
case sizes
6
Dim F
2.3
270 410 550 630 760 900 1000
W 285 290 300 460 550 580 740
A
200 340 480 560 690 830 930
B
215 220 230 390 480 510 670
C
25
25
E
58
93 118 143 203 203 203
F
188 228 268 353 493 493 493
25
25
50
4 Mounting
Holes Ø8.3
Dim H
130 190 190 330 380 390 455
Dim A
D
50 50
Dim B
Dim W
Dim D
isolation equipment
TRENT
55 CRS
Stainless steel grade 304
Cat Ref:
EFL/KIT (Set of four feet)
Ø6.5
Material:
30
E x t e r n a l M o u n t i n g Fe e t
The external feet can be attached for vertical
or horizontal fixings (as shown).
16 CRS
Internal mounting hole
35
Material:
Sheet steel:
Stainless steel:
Finish
Sheet steel (Grey):
Stainless steel:
Thickness
1.2
1.5
2.0
1.5
2.0
Grade
304
304
Iron Phosphate pre treatment + Powder coat
RAL 7035 (Light grey) textured finish.
Iron Phosphate pre treatment + Powder coat
RAL 3020 (Traffic Red) textured finish.
Finely grained surface (180 grit)
Hinges
Metal with quick release pins.
Gland Plates
All enclosures supplied with a 3mm thick removable gland
plate on the bottom face finished to match the enclosure
Chassis Plate
All assemblies are supplied with the switching element mounted
on a removable internal chassis plate. Material - 2mm galvanised
steel pre-drilled to accept optional components.
Spreader Boxes
To assist in accommodating oversized cables, bottom
mounting spreader boxes are available to special order.
Please contact our sales department for details.
still need more?
craigandderricott.com
RANGE
Sheet steel (Red):
Sizes 1, 2 & 2A
Sizes 3, 4 & 5
Size 6
Sizes 1 - 5
Size 6
Cabinet Locks
All metal locks supplied with one key per enclosure.
Enclosure Sizes 1 & 2
1 Lock
Enclosure Sizes 2A, 3, 4 & 5
2 Locks
Enclosure Size 6
3 Locks
TRENT
Enclosure Data
isolation
equipment
11
isolation equipment
TRENT
Stainless Steel enclosures (25A-40A)
General Description
There are various reasons why stainless steel enclosed
isolators are a necessity in today’s world. It may be for
protection against arduous environmental conditions,
resistance against chemical contamination, constant cleaning
when under strict hygiene regulations, and many more.
Whatever the reason, there will be a specific item to suit your
application in the following list. If you need something a little
special, then we will be pleased to discuss the variation with
you. Please call our sales team for assistance.
Along with excellent material specification, all items offer a
minimum of IP65 protection to ensure protection against
dust and liquids under pressure.
Catalogue Numbers
Continental Style Locking Handle
1L
Lid Mounted interior
Switch Disconnectors (0-1)
Rating
Format
Enclosure
Size
(see page 14)
2P
25A
Catalogue No.
1L
2L
DS252
DSM252
3P
DS253
DSM253
3P+NL*
DS253NL
DSM253NL
DS253EB
DSM253EB
DS254
DSM254
3P+2 EB Aux
A
4P
6P
DS256
DSM256
6P+2 EB Aux
DS256EB
DSM256EB
2P
DS402
DSM402
3P
DS403
DSM403
DS403NL
DSM403NL
DS403EB
DSM403EB
4P
DS404
DSM404
6P
DS406
DSM406
6P+2 EB Aux
DS406EB
DSM406EB
3P+NL*
40A
3P+2 EB Aux
B
*Removeable link forms part of the isolating switch assembly.
TRENT
RANGE
All metal padlocking facility
of a ‘Form 2L’ assembly
‘Form 1L’ assembly showing the
multi-padlocking moulded handle
Die-Cast Padlocking Handle
2L
Lid Mounted interior
Padlocking
All versions allow the fitting of a
padlock in the ‘Off’ position.
Form 2L construction allows the use of
a single padlock, whilst Form 1L will
accept up to four individual locks.
It is recommended that padlocking
devices with a minimum hasp diameter
of 6.4mm are used. This will limit the
movement of the handle away from the
‘Off’ position.
Form 2 can accommodate padlocking
in both the ‘Off’ & ‘On’ positions.
Please add /10 to the cat. no. if
required:- e.g. DSM403/10
Auxiliary Contacts
The ‘EB’ addition to the catalogue
numbers denotes the inclusion of 2 off
early break contacts.
In all cases these are factory fitted to
the isolator interior, and are not
available as a customer addition.
All auxiliary contacts are fully rated and
are designed to open before the main
contacts when switching ‘Off’.
By definition the contacts would be
late make when switching ‘On’.
Hall Lane, Walsall Wood, Walsall, West Midlands WS9 9DP
isolation
equipment
12
CONSTRUCTION FORMATS
f: +44(0)1543 361619
make the switch
t: +44(0)1543 375541
email: [email protected]
Stainless Steel enclosures (25A-40A)
NEW
Enclosures (Circular)
CIRCULAR HOUSING
Craig & Derricott have introduced many new innovative designs over
the years, but none could be so striking as the ‘Round’ stainless
steel enclosure.
Material
Stainless Steel (Grade 304) 1.5 thick.
Architecturally, the range lends itself well to modern building design,
but it’s aim is to provide less cavities and corners where dirt can
accumulate. This makes the assembly ideally suited to areas where
cleanliness and hygiene are vital requisites for installed equipment.
Gasket Material
Medium Grade EPDM
Switch Disconnectors (0-1)
Rating
Format
Enclosure
Size
(see page 14)
2P
25A
Finish
Polished
Ingress Protection
IP65
Earthing Points
Terminals are provided on both lid and
base to allow full earth continuity to
be maintained.
Mounting
All fixings are internal
Catalogue
No.
Entries
3 x Ø20 on flat lower face
DSR252
3P
DSR253
3P+NL*
DSR253NL
C
3P+2 EB Aux
DSR253EB
4P
DSR254
6P
DSR256
6P+2 EB Aux
DSR256EB
Changeover Disconnectors (1-0-2)
Rating
Format
Enclosure
Size
(see page 14)
2P
25A
Catalogue
No.
NEW
CODSR252
C
3P
PRODUCT
CODSR253
4P
CODSR254
Te c h n i c a l S p e c i f i c a t i o n
Enclosures (Square)
Isolator Interiors - Data supplied against tests to BS EN 60947-3
Material
Stainless Steel (Grade 304) 1.2 thick.
Rating (A)
Application
Sym.
Unit
25A
40A
40
690
4.0
40.0
40.0
40.0
Rated operational
current (AC)
A
400/415V - AC21A
400/415V - AC22A
400/415V - AC23A
25
690
4.0
25.0
25.0
25.0
Rated operational
power (AC)
kW
3 x 400V - AC23A
10.0
18.5
6.0
6.0
Cycles
0.3 x 106
0.3 x 106
Terminal type
Flexible cable
Stranded cable
Tightening torque
2.5 - 6.0
2.5 - 6.0
1.6
10 - 16
10 - 25
1.8
Icc
kA
Minimum mechanical
endurance
Connecting capacity
mm2
mm2
Nm
still need more?
Entries
2 x M20 on bottom face as standard.
Alternative position to special order.
Earthing
Terminals are provided on both lid and
base to allow full earth continuity to
be maintained.
Mounting
All fixings are internal.
craigandderricott.com
RANGE
A
V
kV
Finish
Brushed (150 grit)
TRENT
Category
Rated thermal current
Ithe
Rated insulation voltage Ui
Rated impulse voltage
Uimp
Conditional short circuit
current
isolation equipment
NEW
TRENT
isolation
equipment
13
isolation equipment
TRENT
Stainless Steel enclosures (25A-40A)
Enclosure Dimensions
H = Handle projection:Form 1L = 31, Form 2L = 34
(Enclosures A & B only)
External Mounting Feet
size
Material:
Stainless steel grade 304
Cat Ref:
EFS/KIT (Set of four feet)
A
Internal
mounting
hole
The external feet can be
attached for vertical or
horizontal fixings (as shown).
size
B
TRENT
C
RANGE
Four fixing holes Ø 6.2
Hall Lane, Walsall Wood, Walsall, West Midlands WS9 9DP
isolation
equipment
14
Accessories
f: +44(0)1543 361619
make the switch
t: +44(0)1543 375541
email: [email protected]
‘ATEX S’ Range Zone 21 & 22
(category 2D)
NEW
How safe is your workspace?
From July 2006, the onus was placed upon companies to ensure that all equipment within their organisations is suitable for the
environment in which it is being used.
This was aimed particularly at areas where there may be a possibility of a combustible atmosphere being present, even for short
periods. i.e. less than 10 hours/year.
People normally think of such atmospheres as being gases, mists or vapours, however there are various industries where a
conductive, or non conductive dust mixed with air in the right proportion, can become explosive. It is these areas where the
Craig & Derricott ATEX Group II (Zone 21 and 22) equipment can be used to help you comply with Health & Safety regulations.
Typical industries where such
atmospheres may be generated :-
•
•
•
•
•
•
•
•
Grain Mills
Powder Coating Plant
Textiles
Chemicals
Cargo Handling
Woodworking
Pharmaceuticals
Waste Processing
There are differing degrees of protection against explosive dusts.
Zone 21 is defined as :“A place, in which an explosive atmosphere, in the form of a cloud of
combustible dust in air, is likely to occur occasionally during normal
operation”
...and Zone 22 :“A place in which an explosive atmosphere, in the form of a cloud of
combustible dust in air, is not likely to occur in normal operation but, if
it does occur, will persist for a short period only.”
Applicable Regulations / Specifications
• Directive 94/9/EC
• Directive 1999/92/EC
(“Manufacturers Directive”) Sets out the route equipment manufacturers must take to get their
products certified for use in hazardous environments.
(“Users Directive”) Defines the classifications for protection Zones, and the approach users
must take to ensure that the correct equipment is matched to specific hazardous environments.
isolation equipment
TRENT
Both of the above are classed as ‘ATEX’ directives, and are concerned solely with ensuring safety in the work place,
• DSEAR
Dangerous Substances and Explosive Atmospheres Regulations 2002
• BS EN 50014:1998
• BS EN 50281-1-1:1999
• BS EN 50281-1-2:1999
Electrical apparatus for potentially explosive atmospheres. General requirements
Electrical apparatus for use in the presence of combustible dust
Electrical apparatus for use in the presence of combustible dust. Electrical
apparatus protected by enclosures. Selection installation and maintenance.
Specification for degrees of protection provided by enclosures (IP code)
Specification for low-voltage switchgear and control gear.
Safety of machinery. Electrical equipment of machines. General requirements.
Low voltage switchgear & control gear assemblies.
Fire hazard testing, test methods.
•
•
•
•
•
BS
BS
BS
BS
BS
EN
EN
EN
EN
EN
60529:1992
60947-3:1999
60204-1:1998
60439-1
60695-2-11
NEW
PRODUCT
Safety Isolation Equipment (Switch Disconnectors)
TRENT
The need for local isolation for maintenance and safety, is as important in
Zoned areas as anywhere else. However when considering such an installation,
the equipment installed must be fully certified for use within such areas.
The Craig & Derricott ‘ATEX S’ range is fully certified for use in Zones 21 & 22
(Category 2D). The scope covers equipment rated at 50A - 630A,
all housed in sheet steel enclosures finished ‘Red’.
All items have the following features :• All interior load break switches have visible contact confirmation.
• Side operating handles lockable in the ‘Off’ position by inserting
up to three individual padlocks.
• Enclosures constructed from galvanised steel and
finished with a Red (RAL 3020) epoxy polyester finish.
• Removable gland plate on bottom face.
• Wall mounting - Supplied with 4 external fixing lugs.
• External/Internal earth connections.
• Cabinet lock - 8 mm male square (Key Supplied)
The example shown above
is the 6 pole 80A item (3S41 6008)
in a size ‘B’ enclosure
still need more?
craigandderricott.com
AT E X
• Sealing to IP 65 throughout.
isolation
equipment
15
isolation equipment
TRENT
‘ATEX S’ Range Zone 21 & 22
(category 2D)
NEW
Catalogue Numbers
Rating
Format
Catalogue No
A T E X
Enclosure
Size
(see page 17)
50A
80A
125A
160A
200A
400A
630A
3 Pole
3S41 3005
A
4 Pole
3S41 4005
A
3 Pole
3S41 3008
A
4 Pole
3S41 4008
A
6 Pole
3S41 6008
B
3 Pole
3S51 3012
B
4 Pole
3S51 4012
B
6 Pole
3S51 6020
B
3 Pole
3S51 3020
B
4 Pole
3S51 4020
B
3 Pole
3S51 3040
C
4 Pole
3S51 4040
C
3 Pole
3S51 3063
D
4 Pole
3S51 4063
D
NEW
PRODUCT
Te c h n i c a l S p e c i f i c a t i o n
Data supplied against tests to BS EN 60947-3
Current Rating (A)
Application
Sym. Unit
Category
Number of poles
80
80
125
160
200
400
630
3/4
6
3/4
6
3/4
3/4
3/4
Rated thermal current
Ith
A
50
80
80
125
160
200
400
630
Rated insulation voltage
Ui
V
690
690
800
800
800
800
800
800
415V - AC21A
50
63
80
125
160.0
200
315
500
415V - AC22A
50
63
80
125
160.0
200
315
500
415V - AC23A
25
40
80
125
160.0
200
315
-
3x400V - AC23A
25.0
30.0
40
60.0
80.0
100.0 160.0
270
kA rms Prospective current 100.0
100.0
100.0
100.0
50.0
35.0
50.0
35.0
Rated operational current (AC)
A
Rated operational power (AC)
TRENT
Fuse protected short
AT E X
Connecting capacity
kW
circuit withstand
50
80
50
125
160
200
400
630
Rated short time withstand (1s)
kA rms
2.5
2.5
7.0
7.0
7.0
7.0
9.0
26.0
Rated peak withstand (U=400V)
kA peak
3.75
3.75
11.9
11.9
11.9
11.9
40.0
54.6
kV
6.0
6.0
8.0
8.0
8.0
8.0
8.0
12.0
Rated implulse withstand
A gG
Uimp
Protective fuse
Voltage
Mechanical endurance (Min.)
Cycles
-
10,000 10,000 10,000 10,000 10,000 10,000 10,000 5,000
Terminal type
mm2 Min Cu cable section
4.0
6.0
16.0
25.0
25.0
25.0
mm
Max Cu cable section 16.0
35.0
35.0
120.0
120.0
120.0 3x150 3x300
Nm
Min tightening torque
5.0
9.0
9.0
9.0
2
4.0
9.0
70.0
20.0
120
20.0
Hall Lane, Walsall Wood, Walsall, West Midlands WS9 9DP
isolation
equipment
16
50
3/4
f: +44(0)1543 361619
make the switch
t: +44(0)1543 375541
email: [email protected]
‘ATEX S’ Range Zone 21 & 22
(category 2D)
NEW
Dimensions
▲
4 x M8 Fixing Lugs
(supplied loose)
Size
H
L
P
B
C
D
A
B
C
D
350
225
150
198
290
275
500
425
200 198/275*
465
425
700
500
250
385
565
625
700
500
300
313
565
625
*6 Pole 160A / 3&4 Pole 80A
Spare & Accessories
Cable Glands (ATEX) - Black Polyamide
Mounting hole
diameter
(mm)
Minimum
cable diameter
(mm)
Maximum
cable diameter
(mm)
Cable Gland
Locknut
12
3.5
6
3240 1012
3240 3012
16
5
8
3240 1016
3240 3016
16
6
10
3240 1017
-
20
8
13
3240 1020
3240 3020
20
10
15
3240 1021
-
25
13
19
3240 1025
3240 3025
32
18
25
3240 1032
3240 3032
40
24
32
3240 1040
3240 3040
50
29
38
3240 1050
3240 3050
63
36
44
3240 1063
3240 3063
Catalogue Numbers
isolation equipment
TRENT
NEW
PRODUCT
Cable Glands (ATEX) - Brass
Minimum
cable diameter
(mm)
Maximum
cable diameter
(mm)
Cable Gland
Locknut
10
1.5
5
3240 2010
3240 4010
12
4
8
3240 2012
3240 4012
Catalogue Numbers
6
11
3240 2016
3240 4016
20
7.5
13
3240 2020
3240 4020
25
12.5
18
3240 2025
3240 4025
32
17.5
25
3240 2032
3240 4032
40
24.5
33
3240 2040
3240 4040
50
33
43
3240 2050
3240 4050
63
42.5
55
3240 2063
3240 4063
still need more?
craigandderricott.com
AT E X
16
TRENT
Mounting hole
diameter
(mm)
isolation
equipment
17
isolation equipment
NEW
PRODUCT
TRENT
‘ATEX C’ Zone 22 (category 3D)
non-conductive dust
NEW
How safe is your workspace?
From July 2006, the onus was placed upon companies to ensure that all equipment within their organisations is suitable for the
environment in which it is being used.
This was aimed particularly at areas where there may be a possibility of a combustible atmosphere being present, even for short
periods. i.e. less than 10 hours/year.
People normally think of such atmospheres as being gases, mists or vapours, however there are various industries where a
conductive, or non conductive dust mixed with air in the right proportion, can become explosive. It is these areas where the
Craig & Derricott ATEX Group II (Zone 22) equipment can be used to help you comply with Health & Safety regulations.
Typical industries where such atmospheres may be generated :-
• Grain Mills
• Cargo Handling
• Powder Coating Plant
• Woodworking
• Textiles
• Pharmaceuticals
• Chemicals
• Waste Processing
There are differing degrees of protection against explosive dusts,
and Zone 22 is defined as :“A place in which an explosive atmosphere, in the form of a cloud of combustible dust in air, is not likely to occur
in normal operation but, if it does occur, will persist for a short period only.”
Applicable Regulations / Specifications
• Directive 94/9/EC
(“Manufacturers Directive”) Sets out the route equipment manufacturers must take to get their
products certified for use in hazardous environments.
(“Users Directive”) Defines the classifications for protection Zones, and the approach users must
take to ensure that he correct equipment is matched to specific hazardous environments.
• Directive 1999/92/EC
Both of the above are classed as ‘ATEX’ directives, and are concerned solely with ensuring safety in the work place,
• DSEAR
Dangerous Substances and Explosive Atmospheres Regulations 2002
•
•
•
•
•
Electrical apparatus for potentially explosive atmospheres. General requirements
Electrical apparatus for use in the presence of combustible dust
Specification for degrees of protection provided by enclosures (IP code)
Specification for low-voltage switchgear and controlgear.
Safety of machinery. Electrical equipment of machines. General requirements
BS
BS
BS
BS
BS
EN
EN
EN
EN
EN
50014:1998
50281-1-1:1999
60529:1992
60947-3:1999
60204-1:1998
Trent ATEX Switch Disconnectors (25A - 63A)
Craig & Derricott has been manufacturing enclosed switchgear for more
than 50 years. In the Trent range we have incorporated all of that
experience in producing an outstanding product that has now been
approved for use in explosive dust atmospheres.
TRENT
Two purpose designed die-cast enclosures are used to cover the 25A & 32A
items, whilst the 63A items are supplied in a quality sheet steel enclosure.
All items have a minimum ingress protection of IP65. The following table
lists two popular formats that will fulfil most applications, however, if you
specifically require an alternative arrangement, then contact our technical
sales staff who will advise on options available to us.
Rating
Format
Assembly
Form
(see right)
25A
AT E X
32A
63A
3P+2 EB Aux
6P+2 EB Aux
3P+2 EB Aux
6P+2 EB Aux
3P+2 EB Aux
6P+2 EB Aux
Catalogue No.
Finished Red
DRM253EBZ22
2L
2B
3B
DRM256EBZ22
DRM403EBZ22
DRM406EBZ22
DRM633EB22Z
DRM636EB22Z
Enclosure
Size
A
(see pages 19)
B
(see pages 19)
C
(see pages 20)
Sheet Steel Enclosure
3B
Base mounted interior (63A)
Hall Lane, Walsall Wood, Walsall, West Midlands WS9 9DP
isolation
equipment
18
Die-Cast Padlocking Handle
2L
Lid mounted interior (25A)
Base mounted interior (32A)
2B
f: +44(0)1543 361619
make the switch
t: +44(0)1543 375541
email: [email protected]
‘ATEX C’ Zone 22 (category 3D)
non-conductive dust
NEW
Pa d l o c k i n g
Auxiliary Contacts
All versions allow the fitting of a padlock in the ‘Off’ position.
Form 2 construction allows the use of a single
padlock, whilst Form 3 will accept 2 or more.
For Form 2 items it is recommended that padlocking
devices with a minimum hasp diameter of 6.4mm are
used. This will limit the movement of the handle away
from the ‘Off’ position.
Form 2 can accommodate padlocking in both the ‘Off’
& ‘On’ positions. Please add /10 to the cat. No. if
required:- e.g. DRM403EB22Z/10
The ‘EB’ addition to the catalogue numbers denotes the
inclusion of 2 off early break contacts.
In all cases these are factory fitted to the isolator interior.
Form 2 auxiliary contacts are fully rated and are designed
to open before the main contacts when switching ‘Off’.
By definition the contacts would be late make when
switching ‘On
Te c h n i c a l S p e c i f i c a t i o n
Rating (A)
Isolator Interiors - Data supplied against tests to BS EN 60947-3
63A
Application
Rated thermal current
Rated insulation voltage
Rated impulse voltage
Sym.
Unit
Ithe
Ui
Uimp
A
V
kV
Rated operational current (AC)
Rated operational power (AC)
Conditional short circuit current
Minimum mechanical endurance
Category
400/415V - AC21A
400/415V - AC22A
400/415V - AC23A
3 x 400V - AC23
A
Icc
Connecting capacity
kW
kA
Cycles
Terminal type
Flexible cable
Stranded cable
Tightening torque
mm2
mm2
Nm
25A
32A
3 Pole
6 Pole
25
690
4.0
25.0
25.0
25.0
10.0
6.0
0.3 x 106
40
690
32.0
32.0
28.0
15.0
50.0**
0.5 x 106
63
690
8.0
63.0
63.0
63.0
30.0
30 x 106
63
690
4.0
56.0
45.0
45.0
22.0
8.0
-
2.5 - 6.0
2.5 - 6.0
1.6
10 max
10 max
2.0
25
2.0
16 - 50
2.4
isolation equipment
TRENT
NEW
PRODUCT
**Fuse in circuit - GEC ‘TIS 40’
Enclosure Dimensions
*Handle depth:- Form 2 - 34mm
TRENT
size
A
Material
Die-cast aluminium alloy LM24 (BS 1490)
B
Finish
Red RAL 3020 semi-gloss (textured)
Entries
2 x M20 on bottom face as standard
AT E X
size
size C - see page 20
still need more?
craigandderricott.com
isolation
equipment
19
‘ATEX C’ Zone 22 (category 3D)
non-conductive dust
NEW
Enclosure Dimensions
Dim C
Dim E
C
Dim F
2.3
Dim H
4 Mounting
Holes Ø8.3
Dim A
isolation equipment
TRENT
NEW
M8 External
Earth
PRODUCT
Dim D
Dim B
Dim W
External mounting feet kit is available for this item.
Please contact our sales department for details.
Material
Sheet steel thickness 1.2 mm
Dim
H
W
D
A
B
C
E
F
(mm)
270
285
130
200
215
25
58
188
TRENT
Finish
Iron Phosphate pre treatment + Powder
coat RAL 3020 (Traffic Red) textured finish
Certification Details:-
(25A - 63A)
AT E X
Coding:
Ex II 3D
EX tD A22 IP65 T85°C
Complies in part or full with Standards:
BS EN 50014, BS EN 50281-1-1, BS EN 60529
BS EN 60947-3, BS EN 60204-1
(Must not be used in areas which exhibit conductive dust.)
Hall Lane, Walsall Wood, Walsall, West Midlands WS9 9DP
isolation
equipment
20
Entries
3mm thick removable gland plate on
bottom facer
f: +44(0)1543 361619
make the switch
t: +44(0)1543 375541
email: [email protected]
Isolators (20A-125A)
General Description
Craig & Derricott has been producing switch
disconnectors for more than 30 years. Combining our
switching expertise with the specific requirements of
the ventilation industry, led to the development of our
‘High Temperature Isolation’ range. Excellent switching
characteristics with high temperature environment
contact stability makes this the ideal product range.
The critical role these switches perform is to maintain
the power to vital equipment such as ventilation fans,
allowing safe evacuation of a business or public area.
Often, these devices are mounted local to the extraction
fans and, as an assembly, it is essential they comply with
the stringent thermal requirements of BS EN 12101 - 2003.
kills more people than fire.
“ Smoke
A well known fact, and it’s the job of the
ventilation designer to ensure this doesn’t
happen - and to do this effectively
he will need continuous power.
”
The complete range are housed in metal enclosures.
The user can therefore be assured that there will be
no distortion affecting the connecting cables and
its supports.
Electrical Characteristics
Rating (A)
Application
Enclosure material/size
(See page 23)
Rated thermal current
Rated insulation voltage
Rated operational current (AC)
Rated operational power (AC)
Conditional short circuit current
Minimum mechanical endurance
Connecting capacity
Sym.
Unit
Ithe
Ui
A
V
Ie
A
Icc
kW
kA
Cycles
mm2
mm2
Category
400/415V - AC21A
400/415V - AC22A
400/415V - AC23A
3 x 400/415V - AC23A
Terminal type
Flexible cable
Stranded cable
20A
Sheet Steel
32A
Die-Cast
63A
Sheet Steel
125A
Sheet Steel
A
B
C
D
A
20.0
690
20.0
20.0
20.0
10.0
50.0*
>0.5 x 106
32.0
690
32.0
32.0
32.0
15.0
50.0*
>0.5 x 106
2.5
2.5
6.0
6.0
isolation equipment
Fire Rated - (High Temperature)
63.0
125.0
690
690
63.0
125.0
63.0
125.0
100.0
18.6
55.0 (AC23B)
50.0*
50.0*
>0.5 x 106 >0.5 x 106
25.0
25.0
50.0
50.0
20A item housed in red finished
sheet steel enclosure. The circular
locking handle allows for the insertion
of up to 3 padlocks in the ‘Off’ position.
still need more?
craigandderricott.com
RANGE
▲
32A item enclosed within a heavy
duty die-cast aluminium enclosure.
Can be supplied padlockable in both
‘On’ & ‘Off’ positions to special order.
CLASSIC
▲
*Max size BS 88 fuse in circuit 20A-32A, 32A-32A, 63A-63A, 125A-125A
isolation
equipment
21
isolation equipment
Fire Rated - (High Temperature)
Isolators (20A-125A)
Specification
Within BS EN 12101-3 :2002 (Smoke and heat control systems.) which is the specification for powered
smoke and heat exhaust ventilators, there are several classes of duty. These define specifically the
temperature gradient and upper limit for the test as well as the time period over which the test will last.
Within the range of this equipment are the following classes:F200 200OC for 120 minutes
F300 300OC for 60 minutes
The specification calls for dynamic tests designed to check the performance of complete ventilation
assemblies. The associated isolator is required to maintain the essential supply throughout the duration of
the test. To ensure the capability of this equipment Craig & Derricott test laboratory has taken the
temperature and time limits up to 300OC for 5 hours successfully on selected items.
Catalogue References
Rating
Format
Assembly
Form
2P
3P
20A
3P + 2EB Aux
3P + NL
4P
RT2031/2EB/CP/SEHT
Lid
mounted
in die-cast
aluminium
enclosure
RY3041/2EB/HPHT
RDB6321/HPHT
4P
6P
RTB6341/HPHT/NL
CLASSIC
4P
6P
6P + 2EB Aux
B
32A 2 x M20
63A Undrilled bottom gland plate
125A Undrilled bottom gland plate
F300
C
F300
D
RYB6361/HPHT
RS1BD11/HPHT
3P + NL
F300
RQB6341/HPHT
RYB6371/2EB/HPHT
3P + 2EB Aux
20A 2 x Ø20 plain holes
RTB6341/HPHT
2P
Base
mounted
in sheet
steel
enclosure
• Cable Entries
RTB6351/2EB/HPHT
6P + 2EB Aux
3P
• Padlockable in the ‘Off’ position
• Finished in RAL 3020 ( Traffic
Red) textured powder coat finish
RQ3021/HPHT
2P
3P + NL
A
RT3031/2EB/HPHT
6P + 2EB Aux
Base
mounted
in sheet
steel
enclosure
• Sealing to IP65
F400
RT3021/HPHT
RT3021/HPHT/NL
U n i v e r s a l Fe a t u r e s
• Positive mode contacts.
RQ2021/CP/SEHT
RY3031/HPHT
3P
(see above) (see page 23)
RT2021/CP/SEHT/NL
6P
3P + 2EB Aux
Enclosure
Size
RT2021/CP/SEHT
RD3011/HPHT
3P + NL
Temp.
Class
RD2011/CP/SEHT
Lid
mounted
in sheet
steel
enclosure
2P
4P
125A
(Finished Red)
RY2031/CP/SEHT
3P + 2EB Aux
63A
Catalogue Ref.
6P
3P
32A
RS1BT21/HPHT
RS1BT31/2EB/HPHT
RS1BT21/HPHT/NL
RS1BQ21/HPHT
RS1BY31/HPHT
RS1BY41/2EB/HPHT
RANGE
32A die-cast & 125A sheet steel examples
Hall Lane, Walsall Wood, Walsall, West Midlands WS9 9DP
isolation
equipment
22
F400 400OC for 120 minutes
f: +44(0)1543 361619
make the switch
t: +44(0)1543 375541
email: [email protected]
Isolators (20A-125A)
Enclosure Dimensions
A
*Handle projection:- 30mm
B
isolation equipment
Fire Rated - (High Temperature)
C
CLASSIC
D
RANGE
still need more?
craigandderricott.com
isolation
equipment
23
isolation equipment
Die-Cast - enclosures (20A-40A)
General Description
Craig & Derricott has been manufacturing die-cast enclosed switchgear
for more than 60 years. In the Classic range we have incorporated all of
that experience and produced a range of traditional isolator assemblies.
A purpose designed enclosure is used to cover the complete range,
which includes lid mounted items in the 40A range and multipole base
mounting items in the 20A. Added to these are the ‘Flagged’ items
which are designed to provide that extra degree of visual assurance.
With locking handle options and sealing throughout to IP65, the
‘Classic’ range of die-cast isolators is the choice for quality and reliability.
Continental Style Locking Handle Form 1
1L
Lid mounted interior
Base mounted interior
1B
Catalogue Numbers
Padlocked Enclosed Switches (0-1)
Rating
Format
Assembly
Form
Catalogue No.
Finished Red
(see right)
6P + 2EB Aux
20A
MYB41/2EB/CP/LMD
8P
MOB41/CP/LMD
10P
MWB51/CP/LMD
1B
10P + 2EB Aux
MWB61/2EB/CP/LMD
12P
MUB61/CP/LMD
14P
MMB71/CP/LMD
Switch Disconnectors (0-1)
Rating
Format
Die-Cast Padlocking Handle Form 2
2L
Lid mounted interior
Assembly
Form
Catalogue No.
Finished Red
(see right)
40A
2P
3P
3P + 2EB Aux
4P
2P
3P
3P + 2EB Aux
4P
1L
2L
RD4011/CP/MD
RT4021/CP/MD
RT4031/2EB/CP/MD
RQ4021/CP/MD
RD4011/HPD
RT4021/HPD
RT4031/2EB/HPD
RQ4021/HPD
CLASSIC
Switch Disconnectors- Flagged (0-1)
Rating
Format
Assembly
Form
(see right)
2P
RANGE
40A
Catalogue No.
Finished Red
RD4011/FLD
3P
RT4021/FLD
3P + 2EB Aux
RT4031/2EB/FLD
4P
2L
RQ4021/FLD
6P
RY4031/FLD
6P + 2EB Aux
RY4041/2EB/FLD
Padlocking
All versions allow the fitting of a padlock
in the ‘Off’ position.
Form 2 construction allows the use of a
single padlock, whilst Form 1 will accept
up to three individual locks.
It is recommended that padlocking devices
with a minimum hasp diameter of 6.4mm
are used. This will limit the movement of
the handle away from the ‘Off’ position.
Form 2 can accommodate padlocking in
both the ‘Off’ & ‘On’ positions. Please add
/10 to the cat. No. if required:-e.g.
RT4021/HPD/10
Auxiliary Contacts
The ‘EB’ addition to the catalogue
numbers denotes the inclusion of 2 off
early break contacts.In all cases these
are factory fitted to the isolator interior,
and are not available as a customer
addition.
All auxiliary contacts are fully rated and
are designed to open before the main
contacts when switching ‘Off’.
By definition the contacts would be late
make when switching ‘On’.
Neutral Links
Add /NL to the part numbers as shown.
e.g. RT4021/HPD/NL
Hall Lane, Walsall Wood, Walsall, West Midlands WS9 9DP
isolation
equipment
24
CONSTRUCTION FORMATS
f: +44(0)1543 361619
make the switch
t: +44(0)1543 375541
email: [email protected]
‘ F l a g ’ Switch Disconnectors
The design of the ‘Flag’ isolator option gives added
conformation to the switch condition.
The flag, which is directly driven off the switch shaft,
is visable through a window in the enclosure lid.
A green ‘Off’ flag is visible when the isolator is open
and a red ‘On’ flag, when closed.
The photograph to the right shows clearly that
Craig & Derricott are always prepared to offer the
user a purpose designed and finished products to
meet specific applications.
If you have a unique requirement, please speak to our
technical sales staff who will be pleased to assist.
Te c h n i c a l S p e c i f i c a t i o n
Standard finish
Flag isolator and
Bespoke finish to
meet customers
precise needs.
Isolator Interiors - Data supplied against tests to BS EN 60947-3
Rating (A)
Application
Sym.
Unit
Rated thermal current
Rated insulation voltage
Ith
Ui
A
V
Rated operational current (AC)
Ie
A
Rated operational power (AC)
Conditional short circuit current
Minimum mechanical endurance
Icc
kW
kA
Connecting capacity
mm2
mm2
Nm
Category
20A
40A
400/415V - AC21A
400/415V - AC22A
400/415V - AC23A
3 x 400V/415V - AC23
20
690
50.0*
>0.5 x 106
40
690
32.0
32.0
28.0
15.0
50.0**
>0.5 x 106
2 x 4.0
2 x 4.0
0.8
10 max
10 max
2.0
Cycles
Terminal type
Flexible cable
Stranded cable
Tightening torque
isolation equipment
Die-Cast - enclosures (20A-40A)
* Fuse in circuit - GEC ‘YBC 32’ (32A / BS 88-2) **Fuse in circuit - GEC ‘TIS 40’ (40A / BS 88-2)
Enclosure Dimensions
Enclosures
*Handle depth:- Forms 1 = 30mm, Form 2 = 34mm
Material
Die-cast aluminium alloy LM24 (BS 1490)
▲
▲
*
Entries
2 x M20 on bottom face as standard.
Maximum no. of possible entries:Enclosure
8 (3 top + 3 bottom
+ 1 on both sides)
Earthing
Terminals are provided on both lid and
base to allow full earth continuity to be
maintained.
still need more?
craigandderricott.com
RANGE
Mounting
All fixings are internal and within the
base casting. Guide channels are
provided to assist with the fixing
screw location.
CLASSIC
Finish
Red
RAL 3020 semi-gloss (textured)
isolation
equipment
25
isolation equipment
STENTON Range
Moulded enclosures (25A-63A)
Specification
The Stenton range of switch disconnectors is designed to meet today’s vigorous market requirements for a
product that is simple, and hence cost effective, to install and meets internationally accepted standards for
performance and safety.
To provide the installer with the maximum of choice when designing his installation, the interior switch
disconnectors are supplied separately from the moulded housings. Add this sealing to IP66 and the range
becomes a truly universal product.
Each housing is supplied complete with a captive handle assembly and neutral and earth continuity terminals.
63A
40A
25A
Side view of enclosure showing the
contoured lid which ensures easy
access to the isolating switch terminals
Catalogue Numbers
Switch Disconnectors (0-1)
Cat. Ref.
Description
DE25
25A moulded enclosure complete with locking
handle, earth and neutral link.
DI252
25A 2 pole disconnector interior
DI253
25A 3 pole disconnector interior
DI253EB
25A 3 pole + 2EB aux disconnector interior
CLASSIC STENTON
DI254
25A 4 pole disconnector interior
DI256
25A 6 pole disconnector interior
DI256EB
DE40
25A 6 pole + 2EB aux disconnector interior
40A moulded enclosure complete with locking
handle, earth and neutral link.
DI402
40A 2 pole disconnector interior
DI403
40A 3 pole disconnector interior
DI403EB
40A 3 pole + 2EB aux disconnector interior
DI404
40A 4 pole disconnector interior
DI406
40A 6 pole disconnector interior
DI406EB
40A 6 pole + 2EB aux disconnector interior
DE63
63A moulded enclosure complete with locking
handle, earth and neutral link.
DI632
63A 2 pole disconnector interior
DI633
63A 3 pole disconnector interior
DI633EB
63A 3 pole + 2EB aux disconnector interior
DI634
63A 4 pole disconnector interior
DI636
63A 6 pole disconnector interior
DI636EB
63A 6 pole + 2EB aux disconnector interior
Auxiliary Contacts
The ‘EB’ addition to the catalogue
numbers denotes the inclusion of 2 off
early break contacts.
In all cases these are factory fitted to
the isolator interior, and are not
available as a customer addition.
All auxiliary contacts are fully rated and
are designed to open before the main
contacts when switching ‘Off’.
By definition the contacts would be late
make when switching ‘On’.
Padlocking
All versions allow the fitting of three
padlocks in the ‘Off’ position.
It is recommended that padlocking
devices with a minimum hasp diameter
of 6.4mm are used. This will limit the
movement of the handle away from the
‘Off’ position.
Hall Lane, Walsall Wood, Walsall, West Midlands WS9 9DP
isolation
equipment
26
Typical interior assembly showing
‘plug-in’ interior isolating switch and
earth and neutral continuity terminals
f: +44(0)1543 361619
make the switch
t: +44(0)1543 375541
email: [email protected]
Moulded enclosures (25A-63A)
Conformity
All items meet the requirements of the ‘EC 73/23/EEC Directive’ (The Low Voltage Directive as amended by
93/68/EEC) and are designed and tested to BS EN 60947-3.
Catalogue Numbers
Frame Thermal
Size Rating
(Ithe)
(Rated frequency: 50 to 60Hz)
Rated
Maximum
Insulation
Voltage (Ui) Protection Fuse
25A
30A
690V
40A
50A
690V
63A
70A
690V
gL - aM
Normal
Operating
Voltage (Ue)
25A
690V
40A
690V
80A
690V
AC21A
AC22A
230V - 7.5kW
400V - 15.0kW
500V - 18.5kW
230V - 15.0kW
400V - 22.0kW
500V - 30.0kW
230V - 22.0kW
400V - 37.0kW
500V - 45.0kW
230V - 7.5kW
400V - 11.0kW
500V - 15.0kW
230V - 11.0kW
400V - 22.0kW
500V - 22.0kW
230V - 22.0kW
400V - 30.0kW
500V - 37.0kW
230V - 4.5kW
400V - 10.0kW
500V - 12.0kW
230V - 7.5kW
400V - 18.5kW
500V - 22.0kW
230V - 15.0kW
400V - 22.0kW
500V - 30.0kW
2.5 - 6.0
10.0 - 25.0
16.0 - 50
Mounting Position
No Restrictions
Enclosure Materials
Base
Material ABS Grade Polylac PA766
Colour
Black 2
Ingress Protection (BS EN 60529 : 1992)
Degree of protection - IP66
Lid
Locking Facilities
Locking in the ‘Off’ position only. Up to 3 x Ø6.4
hasp padlocks in all handles.
Material
Colour
ABS Grade Polylac PA766
Red
Handle Material
Colour
ABS Grade Polylac PA766
Yellow
Enclosure Dimensions
Construction
Height
Width
Depth
(A)
(B)
(C)
Vertical
Fixing
(D)
130.0
160.0
235.0
105.0
130.0
165.0
110.0
130.0
165.0
104.0
134.0
195.0
Horizontal Mounting
Fixing
Holes
(E)
(F)
92.0
117.0
170.0
4.2
4.2
5.2
still need more?
Inside view of enclosure lid
showing the handle interlock
and ‘O’ ring seal which ensures
the excellent IP66 sealing.
craigandderricott.com
CLASSIC STENTON
25A
40A
63A
Connection
Cable Standard (mm )
2
Mechanical Endurance
25A - 100,000 ops
40A - 100,000 ops
63A - 50,000 ops
Rating
AC23A
isolation equipment
STENTON Range
isolation
equipment
27
isolation equipment
C O N TA C T
craig & derricott
Yo u r p r o j e c t n o t e s
Remember,
for more information, support and our
complete product range...
C O N TA C T S
visit
craigandderricott.com
Hall Lane, Walsall Wood, Walsall, West Midlands WS9 9DP
isolation
equipment
28
f: +44(0)1543 361619
make the switch
t: +44(0)1543 375541
email: [email protected]
C O N TA C T
craig & derricott
The new Craig & Derricott
Craig and Derricott is now more
than 62 years new; with new
products, new lean manufacturing,
new systems, and ambitious service
levels. We have witnessed a huge
turnaround in customer satisfaction,
by providing a unique level of
customer service and support.
You the customer are our lifeblood.
Many of our customers have been
placing regular orders with us for
decades. Thank you!
Performance, reliability, our bespoke
products and classic designs are
established product features, which
have built the reputation which we
hold today.
However you cannot stand still, and having a progressive
attitude towards product development is key in today’s
marketplace. Therefore, in reaction to customer and
industry demand, we have launched a completely new
range of world class and competitively priced products!
I am immensely proud of Craig and Derricott, and the
effort put in by each employee to get us where we are
today. This is very much reflected in the experience you
will undoubtedly have when buying from us.
C O N TA C T S
isolation
equipment
I hope we can be of service to you soon.
Tara Valerie Derricott - Chairman
t: +44(0)1543 375541
f: +44(0)1543 361619
email:
[email protected]
website:
www.craigandderricott.com
make the switch