to the installation manual
Transcription
to the installation manual
Geothermal Installation Geothermal Installation Manual Manual Water To Water Water To Water January 2013 January 2012 Document Revision 1 Document Revision 1 January 2013 Rev. 1 ii Spectrum Manufacturing LLC Water to Water Heat Pump Table of Contents Table of Contents iii Getting Started with the Unit 1 Safety Considerations 3 Electrical 5 January 2013 Rev. 1 iii Spectrum Manufacturing LLC Water to Water Heat Pump Table Of Contents Condensate Drain Setup 16 Duct Work 17 System Piping 21 Importance of Water Quality 26 Desuperheater Installation 28 Smart Relay Features and Functions 30 January 2013 Rev. 1 iv Spectrum Manufacturing LLC Water to Water Heat Pump Table Of Contents Safety Guidelines and Functions 34 Maintenance Requirements 38 Troubleshooting Tips 39 Unit Components 44 January 2013 Rev. 1 v Spectrum Manufacturing LLC Water to Water Heat Pump Table Of Contents Unit Checkout Sheet 50 Strip Heat 51 Heating and Cooling Refrigeration 56 January 2013 Rev. 1 vi Spectrum Manufacturing LLC Water to Water Heat Pump Getting Started with the Unit Initial Inspection Moving and Storage January 2013 Rev. 1 1 Spectrum Manufacturing LLC Water to Water Heat Pump Getting Started With The Unit Model Configuration Nomenclature Tag Type Tag Capacity Tag WA Water to Air 024 2 Ton U Up-flow WW Water to Water 036 3 Ton D Down-flow HFC Hydronic Fan Coil 048 4 Ton H Horizontal DX Fan Coil 060 5 Ton S Split 072 6 Ton D Domestic HWG Tag Voltage Tag DXFC Tag Return Air Configuration Desuperheater L Left 1 Single Phase 1 Yes R Right 3 Three Phase 0 No Tag Heat Exchanger Tag Backup Heat Element Tag Warranty C Copper 0 None 10 10 Year N CuproNickel 1 5 KW 5 5 Year CD Copper Double Wall 2 10 KW ND CuproNickel Double Wall 3 15 KW 4 20 KW January 2013 Rev. 1 2 Spectrum Manufacturing LLC Water to Water Heat Pump Safety Considerations Pre-Installation Location January 2013 Rev. 1 3 Spectrum Manufacturing LLC Water to Water Heat Pump Safety Considerations Equipment Installation January 2013 Rev. 1 4 Spectrum Manufacturing LLC Water to Water Heat Pump Electrical Loop Pumping Flow Centers Electrical DHW Model Voltage Compressor External Loop Pump Pump FLA WW-024 WW-036 WW-048 WW-060 WW-072 240/1 Ø 240/1 Ø 240/1 Ø 240/1 Ø 240/1 Ø RLA LRA 11.7 58.3 15.3 Total Unit FLA Min Circuit Ampacity Max Fuse (MCA) Min AWG QTY FLA Total 0.4 2 1.8 3.6 15.7 19.6 25 12 83 0.4 2 1.8 3.6 19.3 24.1 35 10 21.2 99 0.4 3 1.8 5.4 27 33.8 45 10 27.1 118 0.4 3 1.8 5.4 32.9 41.1 50 8 29.7 150 0.4 4 1.8 7.2 37.3 46.6 60 8 Water to Water Electrical Data January 2013 Rev. 1 5 Spectrum Manufacturing LLC Water to Water Heat Pump Electrical Model HFC-024 HFC-036 HFC-048 HFC-060 HFC-072 Voltage 240/1 Ø 240/1 Ø 240/1 Ø 240/1 Ø 240/1 Ø Fan Blower Total Unit FLA Min. Circuit Ampacity (MCA) Min. Breaker Size Min AWG FLA HP 2.3 1/3 4.3 5.4 10 14 2.5 1/3 4.5 5.6 10 14 4.3 1/2 6.3 7.9 10 14 5.5 3/4 7.5 9.4 10 14 6.1 1 8.1 10.1 10 14 Hydronic Fan Coil Electrical Data January 2013 Rev. 1 6 Spectrum Manufacturing LLC Water to Water Heat Pump Electrical Legend Model WW Water to Water HFCH Hydronic Fan Coil Horizontal HFCV Hydronic Fan Coil Vertical Weight (lbs.) Shipping Weight Shipping Dimensions Refrigerant Charge WW 024 WW 036 WW048 WW 060 WW 072 4 Lbs 6 Oz HFCH 024 HFCH 036 HFCH 048 HFCH 060 HFCH 072 HFCV 024 HFCV 036 HFCV 048 HFCV 060 HFCV 072 Unit Weights/Refrigerant Charge January 2013 Rev. 1 7 Spectrum Manufacturing LLC Water to Water Heat Pump Electrical Wiring Diagram Ladder January 2013 Rev. 1 8 Spectrum Manufacturing LLC Water to Water Heat Pump Electrical Wiring Diagram Pictorial January 2013 Rev. 1 9 Spectrum Manufacturing LLC Water to Water Heat Pump Electrical Wiring Diagram Ladder Air Handler January 2013 Rev. 1 10 Spectrum Manufacturing LLC Water to Water Heat Pump Electrical Wiring Diagram Pictorial Air Handler January 2013 Rev. 1 11 Spectrum Manufacturing LLC Water to Water Heat Pump Electrical SelecTech Motor Connections January 2013 Rev. 1 12 Spectrum Manufacturing LLC Water to Water Heat Pump Electrical Control Connections Wall Stat Connections Function 24V 24 Volt G Fan Circulate Speed Y1 Fan Med-High Speed Y2 O Fan High Speed Reversing Valve (default is energized in Cooling) AUX Auxiliary Heat Com Common L Fault Light Wall Thermostat Connections Aqua Stat Connections Function 24V 24 Volt Y1 Compressor Operation Y2 C Compressor Second Stage Common NC Normally Closed-Energized in Heating NO Normally Open- Energized in Cooling Aqua Stat Connections Note: The Normally Open And Normally Closed terminals are to be used with a Heating and Cooling Aqua Stats or Controller, to avoid Overheating or Freezing the Tank. January 2013 Rev. 1 13 Spectrum Manufacturing LLC Water to Water Heat Pump Electrical Air Handler Connections 240 Volt Function Fan Breaker Line Voltage From Building Panel Motor Fan Blower Motor Opt. Load Pump Optional Pump Output For Pumping Water To the Air Handler GND Ground Air Handler Connections From Water to Water Heat Pump 24Volt Pan Function Condensate Pan Level Switch Aux Auxiliary Heat EMH Fan 1 Emergency Heat Fan Speed Low Fan 2 Fan Speed Med/High (or where the installer prefers) Fan 3 Fan Speed High (or where the installer prefers COM Common GND Ground Air Handler Connections January 2013 Rev. 1 14 Spectrum Manufacturing LLC Water to Water Heat Pump Electrical January 2013 Rev. 1 15 Spectrum Manufacturing LLC Water to Water Heat Pump Condensate Drain Setup January 2013 Rev. 1 16 Spectrum Manufacturing LLC Water to Water Heat Pump Duct Work Design Requirements Flex Duct Building Cavities and Ducts Static Losses January 2013 Rev. 1 17 Spectrum Manufacturing LLC Water to Water Heat Pump Duct Work Maximum Velocities Location Supply Main Ducts 900 FPM Branch Ducts 600 FPM Supply Outlet Face Velocity 700 FPM Return Grill Face Velocity 500 FPM Filter Grill Face Velocity 300 FPM Maximum Air Velocities Duct Connections Zonal Pressure Relief January 2013 Rev. 1 18 Spectrum Manufacturing LLC Water to Water Heat Pump Duct Work Duct Installation Insulation Air Tightness January 2013 Rev. 1 19 Spectrum Manufacturing LLC Water to Water Heat Pump Duct Work System Air Flow January 2013 Rev. 1 20 Spectrum Manufacturing LLC Water to Water Heat Pump System Piping Open Loop Systems (Ground Water) January 2013 Rev. 1 21 Spectrum Manufacturing LLC Water to Water Heat Pump System Piping January 2013 Rev. 1 22 Spectrum Manufacturing LLC Water to Water Heat Pump System Piping Closed Loop Systems (Ground Loop) January 2013 Rev. 1 23 Spectrum Manufacturing LLC Water to Water Heat Pump System Piping Pressurized Flow Center Installation Non-Pressurized Flow Center Installation January 2013 Rev. 1 24 Spectrum Manufacturing LLC Water to Water Heat Pump System Piping January 2013 Rev. 1 25 Spectrum Manufacturing LLC Water to Water Heat Pump Importance of Water Quality Antifreeze Overview January 2013 Rev. 1 26 Spectrum Manufacturing LLC Water to Water Heat Pump Importance of Water Quality Antifreeze Characteristics Antifreeze Charging January 2013 Rev. 1 27 Spectrum Manufacturing LLC Water to Water Heat Pump Desuperheater Installation Desuperheater Package January 2013 Rev. 1 28 Spectrum Manufacturing LLC Water to Water Heat Pump Desuperheater Installation Desuperheater Piping January 2013 Rev. 1 29 Spectrum Manufacturing LLC Water to Water Heat Pump Smart Relay Features and Functions Sequence of Operations January 2013 Rev. 1 30 Spectrum Manufacturing LLC Water to Water Heat Pump Smart Relay Features and Functions January 2013 Rev. 1 31 Spectrum Manufacturing LLC Water to Water Heat Pump Smart Relay Features and Functions Unit Checkout Sheet Short Cycle Protection January 2013 Rev. 1 32 Spectrum Manufacturing LLC Water to Water Heat Pump Smart Relay Features and Functions Component Delays Manual (24 Volt Disconnect Switch Inside Panel) Electronic Condensate Overflow Protection January 2013 Rev. 1 33 Spectrum Manufacturing LLC Water to Water Heat Pump Safety Guidelines and Functions High Pressure Low Pressure January 2013 Rev. 1 34 Spectrum Manufacturing LLC Water to Water Heat Pump Safety Guidelines and Functions Flow Switch Condensate Overflow Fault Retry Mode Soft Reset January 2013 Rev. 1 35 Spectrum Manufacturing LLC Water to Water Heat Pump Safety Guidelines and Functions Hard Lockout System Checkout Unit Startup January 2013 Rev. 1 36 Spectrum Manufacturing LLC Water to Water Heat Pump Safety Guidelines and Functions January 2013 Rev. 1 37 Spectrum Manufacturing LLC Water to Water Heat Pump Maintenance Requirements Annual Maintenance Lockouts January 2013 Rev. 1 38 Spectrum Manufacturing LLC Water to Water Heat Pump Troubleshooting Tips Troubleshooting Problem/Issue Entire unit will not run. Possible Cause Power supply is off Actions and Corrections Apply power and close disconnect. Circuit breaker reset circuit breaker. Voltage supply low If voltage is below minimum voltage specified on unit data plate, contact local power company. Thermostat/Aquastat Set the fan to On. The fan should run. Set thermostat to Cool and lowest temperature setting, the unit should run in the cooling mode. Set unit to Heat and the highest temperature setting, the unit should run in the heating mode. If neither the blower nor compressor run in all three cases, the thermostat or Aquastat could be wired incorrectly or faulty. To ensure correct wiring or faulty Aquastat, verify 24 volts is available on the low voltage terminal strip in the compressor section between "R" and "C", "Y" and "C", and, if in cooling mode, "O" and "C". When utilizing an air handler, and the blower does not operate, verify 24 volts between terminals "G" and "C". Replace the thermostat if defective. January 2013 Rev. 1 39 Spectrum Manufacturing LLC Water to Water Heat Pump Troubleshooting Tips Problem/Issue Compressor does not run. Possible Cause Wiring Actions and Corrections Check for loose or broken wires at compressor, capacitor, or contactor. Safety controls Check Smart Relay screen for faults. Capacitor Check capacitor and replace if defective. Compressor overload open If the compressor has cooled down and the overload will not reset, replace compressor. Compressor motor grounded Internal winding grounded to the compressor shell. Replace compressor. If compressor burnout has occurred, install suction filter dryer. Compressor windings open After compressor has cooled, check continuity of the compressor windings. If the windings are open, replace the compressor. PLC reads High Discharge pressure Pressure Check Unit too high Or HARD LOCKOUT HI PRESSURE January 2013 Rev. 1 In Cooling mode, check: Lack of or inadequate water flow Entering water temperature too warm Scaled or plugged condenser In Heating mode check: Lack of or inadequate air flow Blower is inoperative, clogged filter or restrictions in ductwork Refrigerant charge The unit is overcharged with refrigerant. Reclaim refrigerant, evacuate and recharge with factory recommended charge. High pressure Check for defective or improperly calibrated high pressure switch. 40 Spectrum Manufacturing LLC Water to Water Heat Pump Troubleshooting Tips Problem/Issue PLC reads: Low Pressure Check Unit, or Possible Cause Suction pressure too low HARD LOCKOUT LOW PSI. Actions and Corrections In Cooling mode, check: Lack of or inadequate air flow Entering water temperature too cold Blower is inoperative, clogged filter or restrictions in ductwork In Heating mode check: Lack of or inadequate water flow Entering water temperature too cold Scaled or plugged condenser Check refrigerant charge. Always charge to nameplate. Unit Short Cycles Insufficient cooling January 2013 Rev. 1 Refrigerant charge The unit is low on refrigerant. Check for refrigerant leaks. Repair, evacuate and recharge with factory recommended charge. Low pressure switch Check for defective low pressure switch. TXV Bulb may be defective/severed, TXV valve stuck shut, or moisture in the refrigerant system TXV bulb and TXV control diaphragm can be replaced after removing the charge, replacing the control device and bulb, and properly recharging the unit to nameplate value. Unit oversized Adjust deadband on aquastats Wiring and controls Loose connections in the wiring or a defective compressor contactor. Unit undersized Recalculate heating and or cooling loads. 41 Spectrum Manufacturing LLC Water to Water Heat Pump Troubleshooting Tips Problem/Issue Insufficient heating Possible Cause Loss of conditioned air by leaks Actions and Corrections Check for leaks in duct work or look for entering ambient air through doors or windows. Airflow Lack of adequate air flow or improper distribution of air. Replace dirty filter. Refrigerant charge Low on refrigerant charge causing poor operation. Compressor Check for defective compressor. If discharge is too low and suction pressure is too high, compressor is not pumping properly. Replace compressor. Reversing valve Defective reversing valve creates a bypass of refrigerant from discharge to suction side of compressor. Replace reversing valve. Operating pressures Compare unit operating pressures to a pressure/ temperature chart for the refrigerant used. TXV Check TXV for restriction or defect. Replace if necessary. Moisture, noncondensables The refrigerant system may be contaminated with moisture or noncondensables. Reclaim refrigerant, evacuate and recharge with factory recommended charge. NOTE: A liquid line dryer may be required. Loss of conditioned air by leaks Check for leaks in duct work or entering ambient air through doors or windows. PLC Reads: HARD LOCKOUT FLOW SWITCH Inadequate or no water flow Check for water flow. Check flow switch by temporarily bypassing it. Make sure all air is purged from lines. Make sure flow center is purged and functional. Check for proper flow direction. PLC Reads: HARD LOCKOUT PAN LEVEL Pan level switch Check condensate drain for blockage. Make sure condensate drain is properly installed. Check Pan level switch by temporarily bypassing it. Make sure unit is on a level surface. PLC Reads: HARD LOCKOUT CURRENT SENS Current sensor Refer to compressor does not run. Check current sensor by temporarily bypassing it. Troubleshooting Tips January 2013 Rev. 1 42 Spectrum Manufacturing LLC Water to Water Heat Pump Troubleshooting Tips January 2013 Rev. 1 43 Spectrum Manufacturing LLC Water to Water Heat Pump Unit Components Compressor (Copeland) Flow Switch High Pressure Switch Low Pressure Switch Low Voltage Breaker High Voltage Breakers January 2013 Rev. 1 44 Spectrum Manufacturing LLC Water to Water Heat Pump Unit Components Master Contactor Reversing Valve Smart Relay Terminals Transformer Remote Fan Coil Components Pump Relay January 2013 Rev. 1 45 Spectrum Manufacturing LLC Water to Water Heat Pump Unit Components High Voltage Breaker Blower Motor (Selectech) Electric Heater Terminals January 2013 Rev. 1 46 Spectrum Manufacturing LLC Water to Water Heat Pump Unit Components Unit Dimensions January 2013 Rev. 1 47 Spectrum Manufacturing LLC Water to Water Heat Pump Unit Components January 2013 Rev. 1 48 Spectrum Manufacturing LLC Water to Water Heat Pump Unit Components January 2013 Rev. 1 49 Spectrum Manufacturing LLC Water to Water Heat Pump Unit Checkout Sheet Customer Data Name: Date: Address: Phone: Make: Model: Serial #: Refrigerant Charge (OZ): Compressor RLA: Compressor LRA: Blower FLA/HP: Maximum Fuse Size (A): Maximum Circuit Ampacity (A): Operating Conditions EAT/LAT EWT/LWT January 2013 Rev. 1 Cooling Mode / Heating Mode / / / 50 Spectrum Manufacturing LLC Water to Water Heat Pump Strip Heat Model KS-05-1 KS-10-1 KS-15-1 KS-20-1 KW 4.8 9.6 14.4 19.2 Amps 20 40 60 80 Max Overcurrent Protection Single Multi-Feed Feed Min. CFM SCCR Min. Supply Ampacity 300 10 KA 250V MAX. 30 N/A 30 A 760 10KA 250V MAX. 50 N/A 50 A 1140 10 KA 250V MAX. 80 #1 30 A #2 50 A 80 A 1520 10 KA 250V MAX. 100 #1 30 A #2 50 A 100 A 240 Volts Single Phase Note: When using multi-feed, metal jumpers in the screw connection terminals must be removed January 2013 Rev. 1 51 Spectrum Manufacturing LLC Water to Water Heat Pump Strip Heat January 2013 Rev. 1 52 Spectrum Manufacturing LLC Water to Water Heat Pump Strip Heat January 2013 Rev. 1 53 Spectrum Manufacturing LLC Water to Water Heat Pump Strip Heat January 2013 Rev. 1 54 Spectrum Manufacturing LLC Water to Water Heat Pump Strip Heat January 2013 Rev. 1 55 Spectrum Manufacturing LLC Water to Water Heat Pump Heating and Cooling Refrigeration When the Compressor (1) is energized, it starts to pump refrigerant through the system. Because of the compressor increasing the pressure of the refrigerant, it therefore increases the temperature and has compressed it into a high pressure HOT vapor, (Superheated Gas) Then, in systems equipped with a Desuperheater (2), (hot water generator) the high pressure vapor will go through and release some of its superheat into the home's Potable Water. The hot vapor then goes to the Reversing valve (3). In the Heating Cycle, the reversing valve will direct the hot vapor to a Water to Refrigerant Heat Exchanger (4) (Condenser), where it will be condensed to a liquid. This Heat Exchanger is typically connected to an insulated storage tank inside the home. As it travels through the Heat Exchanger, the hot vapor will release its stored heat into the Water from the storage tank. This is considered condensing, (the action of changing a vapor or gas, to a liquid). At the end point of the Water to Refrigerant Heat Exchanger (Condenser), the refrigerant is a high pressure sub-cooled liquid. Sub-cooling is the cooling of liquid refrigerant below its condensing temperature. The high pressure liquid then enters the Expansion Valve (5). This device reduces the pressure from the high side to the low side in a refrigeration system. This is accomplished by metering the liquid refrigerant into the evaporator coil. This rapid decrease in pressure lowers the temperature of the refrigerant considerably. In the Heating Cycle of a Water to Water Heat Pump, the Evaporator (6) is also a water to refrigerant heat exchanger. This Heat Exchanger is typically connected to a ground loop. The refrigerant at the start point of the evaporator is in a low pressure, cold, vapor and liquid mixture. As it travels through the evaporator (water to refrigerant heat exchanger) it begins to collect heat from the ground water that is also traveling through the coil. As the refrigerant absorbs heat, it will start to vaporize (changing from a liquid to a gaseous state). When it has left the evaporator, the refrigerant is a 100% saturated vapor. At this point, it will enter the compressor to begin the cycle again. January 2013 Rev. 1 56 Spectrum Manufacturing LLC Water to Water Heat Pump Heating and Cooling Refrigeration When the Compressor (1) is energized, it starts to pump refrigerant through the system. Because of the compressor increasing the pressure of the refrigerant, it therefore increases the temperature and has compressed it into a high pressure HOT vapor, (Superheated Gas). Then, in systems equipped with a Desuperheater (2), (hot water generator) the high pressure vapor will go through and release some of its superheat into the home's Potable Water. The hot vapor then goes to the Reversing Valve (3). In the Cooling Cycle, the reversing valve directs the hot vapor to the Water to Refrigerant Heat Exchanger (4) (Condenser) that is connected to the ground water, where it will be condensed to a liquid. As it travels through the Heat Exchanger, the hot vapor will release its stored heat into the Water from the ground. This is considered condensing, (the action of changing a vapor or gas, to a liquid). At the end point of the Water To Refrigerant Heat Exchanger (Condenser) the refrigerant is a high pressure sub-cooled liquid. Sub-cooling is the cooling of liquid refrigerant below its condensing temperature. The high pressure liquid then enters the Expansion Valve (5). This device reduces the pressure from the high side to the low side in a refrigeration system, by metering the liquid refrigerant into the evaporator coil. This rapid decrease in pressure lowers the temperature of the refrigerant considerably. In the Cooling Cycle of a Water to Water Heat Pump, the Evaporator (6) is also a Water To Refrigerant Heat Exchanger. Because we have directed the HOT vapor to the Ground Water Heat Exchanger for the condensing cycle, the storage tank in the home is now connected to the Evaporator Coil (also a Water to Refrigerant Heat Exchanger). The refrigerant at the start point of the evaporator is in a low pressure, cold, vapor and liquid mixture. As it travels through the evaporator (water to refrigerant heat exchanger) it begins to collect heat from the water that has come from storage tank. As the refrigerant absorbs heat it will start to vaporize (changing from a liquid to a gaseous state). When it has left the evaporator, the refrigerant is a 100% saturated vapor. At this point it will enter the compressor to begin the cycle again. January 2013 Rev. 1 57 Spectrum Manufacturing LLC Water to Water Heat Pump Heating and Cooling Refrigeration January 2013 Rev. 1 58 Spectrum Manufacturing LLC Water to Water Heat Pump