Test Report Test of pre-insulated flexible bonded pipes Typ CALPEX
Hausadresse
IMA Materialforschung und Anwendungstechnik GmbH
Wilhelmine-Reichard-Ring 4  01109 Dresden  Germany
Geschäftsführer
Prof. Dr.-Ing. Wilhelm Hanel (Sprecher)
E-Mail [email protected]
Postanschrift PF 80 01 44  01101 Dresden  Germany
Prof. Dr.-Ing. Thomas Fleischer
E-Mail [email protected]
Telefon +49(0)351 8837-0
Telefax +49(0)351 8804313
E-Mail [email protected]
Internet www.ima-dresden.de
Sitz der Gesellschaft: Dresden
Registergericht: Amtsgericht Dresden HRB 5995
USt.-IdNr.: DE 155293995
Test Report
Test of pre-insulated flexible bonded pipes
Typ CALPEX-Cyclopentan-PUR
Manufacturer: Brugg Rohrsystem AG

DAP-PL-1062-00
Test Report No.: B223/10.2
Order No.: 402130007
Issued by the Plastics Department
Laboratory for Plastic Testing
Seite 1 von 6
Test report
Task: Test of preinsulated bonded pipes
Test Report No.: B223/10.2
Subject of the test:
Pre-insulated flexible bonded pipes, DN 50 (63/126)
Manufacturer:
Brugg Rohrsystem AG
Industriestraße 39
5314 Kleindöttingen
Schweiz
Customer:
Brugg Rohrsystem AG
Industriestraße 39
5314 Kleindöttingen
Schweiz
Delivery of the test objects:
03.05.2010
Period of tests:
05 bis 06/2010
Person in charge:
Dipl.-Ing. Döring
Distribution:
1 x Brugg Rohrsystem AG
2 x IMA Dresden
Dresden, 15.06.2010
IMA Materialforschung und
Anwendungstechnik GmbH
sign. Prof. Dr.-Ing. Ridzewski
Head of Department Plastics
The test results refer exclusively to the specimen under test.
The publication of parts of this test report and any reference to tests for advertising purposes is subject to written permission by IMA
Materialforschung und Anwendungstechnik GmbH in any case.
Opinions and interpretations are not part of the accreditation. The results contained in this report may only be published or passed on to
third parties with reference to the IMA Materialforschung und Anwendungstechnik GmbH.
*Meinungen und Interpretationen sind nicht Bestandteil der Akkreditierung.
Seite 2 von 6
Test report
Task: Test of preinsulated bonded pipes
Test Report No.: B223/10.2
Inhaltsverzeichnis
1.
Task definition ..........................................................................................................4
2.
Test object................................................................................................................4
3.
Testing procedure and results - PUR-foam investigations ........................................4
3.1
Foam density............................................................................................................4
3.2
Ratio of open to closed-cells.....................................................................................4
3.3
Water absorption ......................................................................................................5
3.4
Thermal conductivity.................................................................................................5
Seite 3 von 6
Test report
Task: Test of preinsulated bonded pipes
Test Report No.: B223/10.2
1.
Task definition
On the pre-insulated flexible bonded pipe DN 50 (63/126) the following properties are to be tested:
- Thermal conductivity
- Foam density
- Ratio of open to closed-cells
- Water absorption
The tests are to be carried out in accordance with EN 15632 and EN 253.
2.
Test object
- Pre-insulated flexible bonded pipe: DN 50, (63/126), L = 4 m
- Typ: CALPEX-Cyclopentan-PUR
- Manufacturing: 26.04.2010
- Delivery of the sample to IMA GmbH: 03.05. 2010
- Storage of the sample material before the test: Room climate
3.
Testing procedure and results - PUR-foam investigations
3.1
Foam density
For the determination of the foam density, the test specimens were taken from the pipe, distributed
over the circumference. The density measurement was carried out according to EN 253.
- Test equipment: Electronic analytical balance (IMA 9904 286), Slide gauge Mahr (IMA 102 3011)
- Specimen dimensions: 30 mm x 30 mm x 20 mm
- Specimen number: 3 items (taken distributed over the circumference)
- Tester: Mrs. Stein
Test parameter
Density
Pipe
CALPEXCyclopentan-PUR
specimen 1
[kg/m³]
57,1
Test individual values
specimen 2
specimen 3
[kg/m³]
[kg/m³]
57,0
54,2
Average
value
[kg/m³]
56,1
3.2
Ratio of open to closed-cells
For the determination of the closed-cellularity (percentage content of closed to open cells) according
to EN 253, the test specimens were taken from the pipe assembly, distributed over the circumference.
Test equipment: Pycnometer (Micrometrics: IMA102 3011)
Specimen dimensions: 25 mm x 25 mm x 25 mm
Specimen number: 3 items (taken distributed over the circumference)
Tester: Mr. Lehmann
Seite 4 von 6
Test report
Task: Test of preinsulated bonded pipes
Test Report No.: B223/10.2
Test parameter
Ratio of open to
closed cells
Pipe
CALPEXCyclopentan-PUR
Test individual values
specimen 1
specimen 2
specimen 3
[%]
[%]
[%]
98,4
98,8
Average
value
[%]
96,1
97,9
3.3
Water absorption
The Water absorption was determined according to EN 15632.
Test equipment: Electronic analytical balance (IMA 9904 286), Slide gauge Mahr (IMA 102 3011)
Specimen dimensions: 25 mm x 25 mm x 25 mm
Specimen number: 3 items (taken distributed over the circumference)
Test temperature: 100°C
Test time: 90 minutes
Tester: Mrs. Stein
Test parameter
Water
absorption
Pipe
CALPEXCyclopentan-PUR
3.4
Test individual values
specimen 1
specimen 2
specimen 3
[%]
[%]
[%]
4,7
5,2
4,8
Average
value
[%]
Requirement
of
EN 253
4,9
10
Thermal conductivity
The determination of thermal conductivity at the pre-insulated pipe 63/126 was carried out based on
EN 253.
- Testing apparatus: Test-Equipment for measuring thermal conductivity in preinsulated pipes
according to EN 253:2009, Annex F
- Manufacturer: IMA Dresden
- Temperature measurement: 2 x 6 thermocouples
- End apparatus: calibrated endcaps; correction according to van Rinsum (x=0,8 m)
- Length of specimen: 2000 mm,
- PEX-Service pipe: D1 = 52,29 mm, D2 = 63,76 mm, s = 6,23 mm
- Thermal insulated: PUR- foam; Foam density:ρ= 56,1 kg/m³
- PE- Casing pipe: D3 = 118,45 mm, D4 = 125,70 mm; s = 3,62 mm
- Tester: Mr. Lehmann
Seite 5 von 6
Test report
Task: Test of preinsulated bonded pipes
Test Report No.: B223/10.2
Results: CALPEX-Cyclopentan-PUR:
Heat
flow-
Temperature
Difference in
rate φ
hot
cold
sample surface
temperature
Mean
temperature
of sample
Thermal conductivity
rate φ
[W]
T1 [°C]
T4 [°C]
T1 - T4 [K]
Tm [°C]
λPUR [W/(m⋅⋅K)]
21,23
73,26
26,45
46,71
49,57
0,0215
21,75
74,27
26,54
47,73
50,06
0,0216
23,24
77,48
26,96
50,52
51,85
0,0218
λ50 = 0,0216
W/(m⋅⋅K)
sign. Dipl.-Ing. Klaus-Dieter Döring
Person in charge