RW-OZ Series Water Reclamation Systems

Transcription

RW-OZ Series Water Reclamation Systems
BUILT IN THE USA
RW-OZ Series
Water Reclamation
Systems
ENGINEER GUIDE: OZONE SYSTEMS
RW-OZ Series
Skid-Mounted Water
Reclamation Systems
Water Control RW-OZ Series Water Reclamation Systems provide an innovative option for
drastically reducing building water and sewer usage, gaining multiple points towards LEED®
certification, and minimizing the negative environmental impact of new and existing commercial
facilities. These systems harvest and store rainwater, graywater, condensate, groundwater and
backwash water (as well as water from other select sources) – and then reuse it to provide clean,
nearly potable quality water to irrigation systems, toilets, urinals, cooling towers, washdown tanks,
and other non-potable applications. With over 40 years of experience in commercial water filtration
and conditioning, Water Control is a name you can count on for innovative, high quality solutions to
your "green" system challenges.
System Advantages:
·
·
·
·
·
·
May contribute toward multiple points under LEED® v4 program:
- “Integrative Process” (1 point)
-
-
-
-
-
“Outdoor Water Use Reduction” (Pre-requisite + 1-2 points)
“Indoor Water Use Reduction” (Pre-requisite + 2 – 7 points)
“Cooling Tower Water Use” (1 – 2 points)
“Rainwater Management” (1 – 3 points)
“Regional Priority” (up to 4 points)
Greatly reduces water and sewer usage: Reduced impact fees!
NO chemicals or additives required
Minimal system maintenance requirements
Guaranteed minimum disinfection levels
Cistern tanks remain clean!
System Flow*
(max GPM)
Dimensions**
(L X W X H)
Maximum
Cistern Size
(Gallons)***
Ozone
Generator
(g./hour)
Pressure Tank
Size****
RW-OZ-15
15
70" X 18" X 75"
10,000
8 g.
35 gal.
RW-OZ-35
35
70" X 18" X 75"
16,000
8 g.
35 gal.
RW-OZ-50
50
70" X 18" X 75"
25,000
12 g.
50 gal.
RW-OZ-100
100
91" X 18" X 75"
40,000+
24 g.
85 gal.
RW-OZ-150
150
91" X 34" X 75"
50,000+
30 g.
120 gal.
RW-OZ-200
200
91" X 34" X 75"
75,000+
30 g.
120 gal.
Model
*Max flow rated at 40 - 55 psi output pressure depending on model (see system drawings for details). Higher pressure
(booster) pumps available – call for details.
**Dimensions listed do not include pressure tank – see pages that follow for full details. All dimensions subject to change
without notice.
***Cistern tank sizes and types can vary by roof size and individual application -- please call for help with specific tank
selection. Larger (custom) systems are available.
****Pressure tank may not be required on some irrigation-only or recirc-only systems.
2
RW-OZ Series Details:
RW-OZ SERIES UNITS Turnkey water reuse systems, which arrive pre-plumbed
and pre-wired for easy installation and operation. A powerful ozone system aids
in removing contaminants as well as disinfecting and deodorizing. The onboard
purification process provides filtered, sanitized, odor-free water on-demand. No post
holding tank or sump pump is required on most applications. The system’s small
footprint takes only minimal space in the mechanical room.
THE OZONE RECIRCULATION SYSTEM Operated independently from the
filtration pump system and is controlled by an ORP feedback system to ensure
constant disinfection levels of minimum 0.05 mg/l. (approx.). The powerful ozone
re-circulation system serves to disinfect any contaminants, so that they may be easily
captured by the micro-pore filtration system. Ozone kills microbes, enzymes, and
bacteria so that there will be no build-up of organic growth, nor will there be a build-up
of odor-forming bacteria. Within minutes, ozone (O3) reverts back to oxygen (O2). This
results in sanitized, odor-free water, with no harmful byproducts or contaminants.
THE PRIMARY FILTRATION SYSTEM Pump (and an associated filtration
array) is designed for maximum water quality. The system receives ozone-treated,
reclaimed water from the holding tank (cistern) and processes this water to remove
all particulate matter of greater than twenty-five (25) microns. In addition, the filtration
system is self-cleaning (backwashing), requiring little or no maintenance. The system
provides water “on demand” so no post-holding tanks are required. The “AutoBypass”
feature automatically switches to fresh water when cistern water levels are low, ozone
concentrations are low, or the filtration system is backwashing.
INSTALLATION: After the cistern tank is in place, a plumber can typically install the
system in two days. An electrician simply connects required power to the unit. Once
installed, a simple, one-time factory startup is all it takes to get the system into service.
MAINTENANCE Primarily limited to periodic inspection and cleaning of simple
screens and pump baskets, which can be accomplished in a few minutes about once
a month.
QUALITY FEATURES Includes a powder-coated aluminum frame, stainless steel
self-cleaning filter housings, schedule 80 PVC & solid brass plumbing, heavy-duty
pumps, stainless steel hardware, and much more.
SYSTEM DESIGN AND SUPPORT Water Control's Technical Service Department
is here to help. We can provide you with everything from system sizing and layout
(AutoCAD™ or Revit™), to system delivery/setup/startup services, LEED® point
registration, and troubleshooting. Call or email us today to get started -- or contact
your local Water Control representative.
3
System Sizing
Water Control’s Technical Support Department is ready to serve. Our specialists can
help you with RW-OZ System and cistern sizing, roof drainage design, system CAD™ or
Revit™ designs, permitting, and LEED® point submittals.
To get started, please call or email us with the following information:
·
Application details (toilets, urinals, irrigation, cooling tower, etc…)
·
System peak flow requirements (GPM and pressure)
·
Water sources you are considering
·
Geographic location and average monthly rainfall statistics (rainwater only)
·
Roof area (sq ft) (rainwater only)
·
Estimated (peak) monthly water usage (total gallons) for the systems you wish to
supply
TO SIMPLIFY THIS PROCESS, PLEASE CONTACT US (OR YOUR LOCAL REP) TO
REQUEST A SYSTEM SIZING QUESTIONAIRE.
Contact Our Technical Support Department:
Phone: 1-866-405-1268 • Fax: 763-427-5665
Email:[email protected]
4
System Dimension Information*
NOTE: Additional space will be required for cistern tank (if located indoors).
System Dimensions: Model RW-OZ-15
RW-OZ-15 SPECIFICATIONS
System Dimensions: Model RW-OZ-35
DELIVERY FLOW RATE
15 GPM
OZONE GENERATOR
8 GRAM / HOUR
RECIRC PUMP
1 HP, 15 GPM @ 50 PSI
OZONE SUCTION
1 ¼ INCH FNPT
OZONE RETURN
1 ¼ INCH FNPT
DELIVERY PUMP
1 HP, 15 GPM @ 50 PSI
FILTER SUCTION
1 ½ INCH FNPT
SYSTEM OUTLET
1 ½ INCH FNPT
FRESH WATER INLET
1 INCH FNPT
BLADDER TANK SIZE
35 GALLONS
SYSTEM WEIGHT
680 LBS
RW-OZ-35 SPECIFICATIONS
DELIVERY FLOW RATE
35 GPM
OZONE GENERATOR
8 GRAM / HOUR
RECIRC PUMP
1 HP, 15 GPM @ 50 PSI
OZONE SUCTION
1 ¼ INCH FNPT
OZONE RETURN
1 ¼ INCH FNPT
DELIVERY PUMP
2 HP, 35 GPM @ 40 PSI
FILTER SUCTION
1 ½ INCH FNPT
SYSTEM OUTLET
1 ½ INCH FNPT
FRESH WATER INLET
1 ½ INCH FNPT
BLADDER TANK SIZE
35 GALLONS
SYSTEM WEIGHT
780 LBS
*System dimensions and designs may be subject to change without notice.
5
System Dimension Information*
NOTE: Additional space will be required for cistern tank (if located indoors).
RW-OZ-50 SPECIFICATIONS
System Dimensions: Model RW-OZ-50
DELIVERY FLOW RATE
50 GPM
OZONE GENERATOR
12 GRAM / HOUR
RECIRC PUMP
1 HP, 15 GPM @ 50 PSI
OZONE SUCTION
1 ¼ INCH FNPT
OZONE RETURN
1 ¼ INCH FNPT
DELIVERY PUMP
2 ½ HP, 50 GPM @ 40 PSI
FILTER SUCTION
2 INCH FNPT
SYSTEM OUTLET
2 INCH FNPT
FRESH WATER INLET
2 INCH FNPT
BLADDER TANK SIZE
50 GALLONS
SYSTEM WEIGHT
900 LBS
RW-OZ-100 SPECIFICATIONS
System Dimensions: Model RW-OZ-100
DELIVERY FLOW RATE
100 GPM
OZONE GENERATOR
24 GRAM / HOUR
RECIRC PUMP
1 HP, 15 GPM @ 50 PSI
OZONE SUCTION
1 ½ INCH FNPT
OZONE RETURN
1 ½ INCH FNPT
DELIVERY PUMP
5 HP, 100 GPM @ 49 PSI
FILTER SUCTION
2 INCH FNPT
SYSTEM OUTLET
2 INCH FNPT
FRESH WATER INLET
2 INCH FNPT
BLADDER TANK SIZE
85 GALLONS
SYSTEM WEIGHT
1200 LBS
*System dimensions and designs may be subject to change without notice.
6
System Dimension Information*
NOTE: Additional space will be required for cistern tank (if located indoors).
RW-OZ-150 SPECIFICATIONS
System Dimensions: Model RW-OZ-150
DELIVERY FLOW RATE
150 GPM
OZONE GENERATOR
30 GRAM / HOUR
RECIRC PUMP
2 HP, 35 GPM @ 40 PSI
OZONE SUCTION
1 ½ INCH FNPT
OZONE RETURN
1 ½ INCH FNPT
DELIVERY PUMP
15 HP, 150 GPM @ 40 PSI
FILTER SUCTION
3 INCH FNPT
SYSTEM OUTLET
3 INCH FNPT
FRESH WATER INLET
3 INCH FNPT
BLADDER TANK SIZE
120 GALLONS
SYSTEM WEIGHT
1800 LBS
RW-OZ-200 SPECIFICATIONS
System Dimensions: Model RW-OZ-200
DELIVERY FLOW RATE
200 GPM
OZONE GENERATOR
30 GRAM / HOUR
RECIRC PUMP
2 HP, 35 GPM @ 40 PSI
OZONE SUCTION
1 ½ INCH FNPT
OZONE RETURN
1 ½ INCH FNPT
DELIVERY PUMP
15 HP, 200 GPM @ 40 PSI
FILTER SUCTION
4 INCH FNPT
SYSTEM OUTLET
3 INCH FNPT
FRESH WATER INLET
3 INCH FNPT
BLADDER TANK SIZE
120 GALLONS
SYSTEM WEIGHT
1800 LBS
*System dimensions and designs may be subject to change without notice.
7
Electrical Requirements
Water Control current & power requirements for all RW-OZ systems
ETL, UL, & CE approval and maximum over-current protection
Reference: CSA-C22.2 No. 236 -- UL 1995 Section 36 2/6/08
Pumps may be either 230V or 460V
Model
Pumping Systems
(Model 15-35 1 phase. All other units 3 phase.)
Voltage
Current
Power
Delivery
Pump
Circ
Pump
AMPS
KVA
Hp
Hp
Control and Ozone
Generation Systems
Voltage
Current
Power
AMPS
WATTS
RW-OZ-15
230
10.4
2.4
1
1
120
4.3
516
RW-OZ-35
230
10.4
2.9
2
1
120
4.3
516
RW-OZ-50
230/460
12.1/6.0
2.8
2½
1
120
6.5
780
RW-OZ-100
230/460
16.1/8.0
3.7
5
1
120
7.5
900
RW-OZ-150
230/460
41.8/20.9
9.6
15
2
120
7.5
900
RW-OZ-200
230/460
41.8/20.9
9.6
15
2
120
7.5
900
System Connection Sizes
Model
Ozone
Suction
Ozone
Return
Filter
Suction
System
Outlet
Fresh Water
Bypass Inlet
RW-OZ-15
1 ¼”
1 ¼”
1 ½”
1 ½”
1”
RW-OZ-35
1 ¼”
1 ¼”
1 ½”
1 ½”
1 ½”
RW-OZ-50
1 ¼”
1 ¼”
2”
2”
2”
RW-OZ-100
1 ½”
1 ½”
2”
2”
2”
RW-OZ-150
1 ½”
1 ½”
3”
3”
3”
RW-OZ-200
1 ½”
1 ½”
4”
3"
3"
*System dimensions and designs may be subject to change without notice.
8
Installation and System Flow
The drawings below represent typical RW-OZ system installations. Water Control can help with
“Site-Specific” designs upon request. System submittals provided by Water Control will show
plumbing sizes, flow, and tank details, so each system can be properly installed and set-up.
Standard Installation: RW-OZ System
Roof Drain
Graywater
From Showers
Solids
Separator
Reclaimed Water
Out To Fixtures
Fresh Water In
RPZ
Reclaimed Water Out To Irrigation
Submersible
Pump Panel
Waste To Drain Or Grade
Tank Vent
Reclaimed Water Out
RW-OZ-150
Overflow
(To Drain)
Priming Port
Reclaimed Water In
Filter Suction Line
Recirc Return Line
Ozone Suction Line
Float Switch
Submersible Pumps (On Platforms At Least 6" Off Bottom)
Standard Installation: RW-OZ-RC (recirc-only) System
Roof Drain
Graywater
From Showers
Reclaimed Water Out To Irrigation
Solids
Separator
Reclaimed Water
Out To Fixtures
Optional Fresh Water Make-Up
With Solenoid Valve & Air Gap
Submersible
Pump Panel
Waste To Drain Or Grade
Tank Vent
Booster Pumps
Reclaimed
Water Out
RW-OZ-35-RC
Booster Pump
Suction Line
Overflow
(To Drain)
Priming Port
Reclaimed Water In
Recirc Return Line
Ozone Suction Line
Float Switch
Submersible Pumps (On Platforms At Least 6" Off Bottom)
ACTUAL SYSTEMS WILL VARY. DO NOT PLUMB TO PRINT.
Contact WCC for other installation configurations.
9
Standard Sytem Sample Specification
(Full spec available in AIA™ format):
System shall be a Water Control model RW-OZ-_____ (or equal) Water Reclamation
System, designed to provide a maximum of _____ GPM of filtered, algae/odor/pathogenfree reclaimed water to non-potable fixtures/systems such as urinals, toilets, irrigation
systems, washdown tanks, and/or cooling towers at _____psi (minimum).
System shall be mounted on a powder-coated aluminum skid and shall include ozone
generator/injection system, control system (in NEMA 3R enclosure), properly sized
pressure pump, stainless 25 micron basket filter system with AutoClean function and
optional backwash sludge interceptor, pressure tank, cistern suction basket strainer,
cistern float switch, filter pressure gauges, ORP assembly and fresh water bypass
equipment.
Ozone generator shall utilize on-board Oxygen Reduction Potential (ORP) sensor to
maintain constant disinfection levels in cistern tank. Should tank water level drop, or
ozone concentration fall below 0.05 mg/l, system shall automatically initiate fresh water
bypass, whereby potable water shall be supplied to fixtures. System controller shall
incorporate ozone pressure gauge, ozone flow meter, and hours indicator, as well as
indicator lights and alarm dry contacts for fresh water bypass and extended system
bypass due to low ORP (to indicate when service is required). Ozone generator shall
be constructed of modular components for easy removal/repair/refurbishment and shall
include mechanical room air quality monitor for shut down in case of ozone leakage.
System shall include a quantity of ____ model ____ in-line separators for pre-filtration of
dirt, moss, leaves, insects, hair, foam and other wastes from reclaimed water prior to
entering tank. Separators shall be capable of serving ____sq.ft. roof area or ____ GPM
flow each.
CONTRACTOR SHALL PROVIDE THE FOLLOWING:
·
Reduced pressure zone backflow preventer on potable water bypass supply line (refer
to state codes for requirements).
·
Mechanical room floor drain for filter backwash effluent, from 25 micron AutoClean
filter.
·
Electrical supply and reclaimed water system piping.
MANUFACTURER SHALL PROVIDE THE FOLLOWING:
·
System setup and startup, as well as contractor/owner training services.
·
Complete system submittals, including O&M manual with wiring diagrams.
·
One-year limited warranty.
10
Available Options
Disinfection-Only Systems (use suffix "RC" after standard OZ system model number)
Packaged
systems for tank recirculation/disinfection only (no delivery system or freshwater bypass). Option for remote freshwater make-up valve. (See page 9 for system schematic.)
Fiberglass storage tanks
Corrugated galvanized steel storage tanks
Polyethylene storage tanks
Air-gap tank systems:
Booster pumps:
Ultrasonic tank level sensors
Waterflow sensors/totalizers
Injector pumps:
Post AutoClean-filter filtration
Downspout separators
Integrated commercial softening systems
600 - 50,000 gallons (vinyl-ester liner included for ozone resistance)
(below grade only)
700-700,000 gallons with water-tight membrane liner (above grade only)
500 - 2,500 gallons (below grade)
100 - 6,500 gallons (above grade)
Potable make-up water supply systems for areas where direct potable water connections are not allowed, or when multiple make-up water sources are desired.
On-board, remote, or submersible high-pressure pumps for large/multi-story facilities.
Up to 26' depth.
With digital gallon/GPM readout.
Inject food-grade dye or chlorine residual into water, prior to delivery.
Additional bag filtration at 10, 5, 2, or 1 micron porosity.
Pre-filtration of large debris from system.
Reclaim nearly 70% of regeneration wastewater with an integrated Water Control commercial softening system.
Ozone destructors
Allow cistern venting indoors or in areas where off-gassing is not desired.
Please call for information on these or any other options.
Contact Our Technical Support Department:
Phone: 1-866-405-1268 • Fax: 763-427-5665
Email:[email protected]
11
BUILT IN THE USA
Water Control Corporation
7150 143rd Ave NW • Ramsey, MN 55303
Phone: 866-405-1268 • Fax: 763-427-5665
www.watercontrolinc.com
© Water Control Corp. 0414
12