Three Phase Synchronous Generators
Transcription
Three Phase Synchronous Generators
Three Phase Synchronous Generators MJL SERIES 160 - 200 FRAME SIZES SIN.CT.029.0 GB STANDARDS The new MJL generator series is designed in compliance with: BS EN 60034; BS 4999-5000; VDE 0530; NEMA MG 1.22 and bears the CE marking. EXCITATION SYSTEM The generators are self-excited by means of a brushless type excitation system. The generators are equipped with an AVR type Mark V. The voltage stability is maintained within ±0,5% of the nominal value in steady condition with balanced and non distorting load. The Mark V operates at 50 and 60 Hz frequency and it is equipped with a radio interference filter. This regulator offers a low speed protection and over-excitation protection. Manual Voltage Regulation Available within ±5% of the rated value by means of a potentiometer placed inside the voltage regulator. Remote voltage sensing is possible by means of an external potentiometer, which can be supplied on request. VOLTAGE AND FREQUENCY Generators can operate at 50 and 60 Hz. Frame Size [mm] Connection 160 ÷ 200 Voltage [V] 50 Hz 60 Hz Series star 380 - 440 416 - 480 Parallel star 190 - 220 208 - 240 Series delta 220 - 254 240 - 277 WINDINGS The generators are supplied with 2/3 pitch winding to reduce the voltage harmonic content in application with non-linear loads. The no-load voltage waveform is sinusoidal with a residual harmonic less than 2%. The Total Harmonic Distortion (THD) is less than 2%. The Telephonic Harmonic Factor (THF) is less than 2% as defined by BS 4999 part 40. The Radio Interference suppression complies to grade N of VDE 0875. OVERLOADS The overloads (only for continuous duty) are: 10% for 1 hour; 15% for 10 minutes; 30% for 4 minutes; 50% for 2 minutes. These overloads must be followed by at least 6 hours of running at nominal load or less. INSULATION, IMPREGNATION AND PROTECTIVE TREATMENT OF WINDINGS The insulation is H class. Generators are impregnated with high grade resin and a further protective treatment is applied on the whole range, making the generators suitable for harsh environment conditions. PROTECTION DEGREE The standard protection degree is IP 23. ROTOR BALANCING, BEARINGS & OVERSPEED The rotors are dynamically balanced and are fitted with sealed-for-life ball bearings on single and double bearing configurations. The max overspeed allowed is 1,5 times the rated speed (referred to 50 Hz). Marelli Asia Pacific Sdn. Bhd. - Sales, Service and Distribution Centre MarelliGenerators ® INDUSTRIAL APPLICATION / LOW VOLTAGE Type Power rating [kVA] Temp. rise / Ambient temp. [°C] Continuous duty Stand by 125/40 105/40 163/27 150/40 ΔT cl. H ΔT cl. F Leads 4 poles Efficiency 4/4 pf = 0.8 125/40 [%] Inertia B3 Approx. J [kg m2] Weight B3 Approx. [kg] 400 V @ 50 Hz - 1.500 rpm IP23 MJL 160 XA4 MJL 160 SA4 MJL 160 SC4 MJL 160 MA4 MJL 160 MB4 12 12 12 12 12 13,5 16,0 23,0 28,0 32,0 12,5 15,0 20,4 25,5 29,1 15,0 17,5 25,0 30,5 34,8 14,0 16,5 24,0 29,5 33,7 84,0 84,1 84,9 87,5 87,0 0,106 0,128 0,165 0,205 0,230 106 117 136 152 168 MJL 200 SA4 MJL 200 SB4 MJL 200 MA4 MJL 200 MB4 12 12 12 12 42,0 50,0 60,0 75,0 37,1 45,0 53,0 68,7 46,0 55,0 66,0 82,0 44,5 53,0 61,0 79,0 87,2 88,2 88,7 90,0 0,369 0,424 0,488 0,615 247 254 278 325 4 poles 480 V @ 60 Hz - 1.800 rpm IP23 MJL 160 XA4 MJL 160 SA4 MJL 160 SC4 MJL 160 MA4 MJL 160 MB4 12 12 12 12 12 16,2 19,2 27,6 33,6 38,4 14,8 17,6 25,2 30,8 35,1 17,8 21,1 30,4 37,0 42,2 17,3 20,5 29,4 35,8 41,0 84,2 84,3 85,6 88,2 87,6 0,106 0,128 0,165 0,205 0,230 106 117 136 152 168 MJL 200 SA4 MJL 200 SB4 MJL 200 MA4 MJL 200 MB4 12 12 12 12 50,4 60,0 72,0 90,0 46,2 55,0 66,0 82,4 55,4 66,0 79,2 115,0 53,8 64,0 76,8 95,0 88,1 89,0 89,6 90,5 0,369 0,424 0,488 0,615 247 254 278 325 Ratings refer to following conditions: balanced non-deforming load, altitude 1.000 m a.s.f., minimum power factor 0,8 OPERATING CONDITIONS Single phase operation Three phase (12-wire) wound generators can be reconnected and derated to 66% for single phase operation (with a zig-zag connection). Transient ratings The voltage drop due to the application of full load at 0,8 power factor inductive on the generators varies between 16 and 20% of the rated voltage: the output voltage recovers to within 3% of the rated value in less than 0,3 seconds. Altitude The rated outputs refer to installation up to 1.000 m a.s.l. Above this level the following derating factors must be applied. Altitude [m a.s.l.] < 1.000 < 1.500 < 2.000 < 2.500 < 3.000 K factor 1,00 0,96 0,93 0,90 0,86 Ambient temperature The rated outputs given in this catalogue are based on a maximum ambient temperature of 40°C. When operating at different ambient temperatures the output rating can be obtained by applying the factors as in the following table. Ambient Temperature [°C] 30 35 40 45 50 55 K factor 1,04 1,00 1,00 0,96 0,93 0,90 Power factor The nominal power factor is 0.8 lagging. For different power factor values the following derating factors must be applied. Power Factor 1 0,8 0,7 0,6 0,5 0,3 0 K factor 1,00 1,00 0,93 0,88 0,84 0,82 0,80 MarelliGenerators ® DIMENSIONS SINGLE BEARING 160 FRAME SIZE 11.5 5 AVR L 340 100 240 CG SAE 3 SAE 4 SAE 5 α 164 N P WA WB Ø316 257 Z MA 0 -1,0 M Ø60 PA P N G 160 β Y 13 N°6 12 90 105 40 90 254 180 300 206 MJL 160 L CG SAE 5-4 CG SAE 3 CONNECTING COUPLING FLANGE SAE J620 6½ 7½ 8 10 11½ 4 • • • • • • • MA 571 225 225 MB 571 250 245 COUPLING [mm] FLANGE [mm] Y 3 SAE J620 PA MA • • • 6½ 7½ 8 10 11½ 215,90 241,30 263,52 314,32 352,42 220,02 222,25 244,48 295,28 333,38 SAE J617 5 16 DIMENSIONS [mm] SA SC 453 491 190 205 185 200 XA 453 180 175 40 14 5 NR Ø 6 8 6 8 8 9 9 11 11 11 β WA WB 60° 45° 60° 45° 45° 30,2 30,2 62,0 53,8 39,6 9.8 9.8 - SAE N J617 5 4 3 0 -0,13 314,32 361,95 409,58 P M 355 404 451 333,38 381,00 428,62 Z NR Ø 8 11 12 11 12 11 α 45° 30° 30° DOUBLE BEARING 160 FRAME SIZE AVR L 340 100 240 Ø308 Ø316 N°8 M10 .75 Ø285 G Ø266.70 Ø354 0 -0,13 48 k6 0 -1,0 51.5 45° N°6 5 13 75 90 110 90 254 180 300 16 206 MJL 160 L CG XA 533 185 40 14 M12 DIN 332 DIMENSIONS [mm] SA SC 533 571 195 210 160 14 h9 257 164 CG MA 651 230 MB 651 255 MarelliGenerators ® SINGLE BEARING 200 FRAME SIZE AVR 12 5 L 420 362 WA α CG 247 N P WB 67 0 -1.0 Ø375 PA MA M G Ø60 N P 392 Z 200 β 6 Y N°6 25 12 50 140 318 140 280 175 390 330 MJL 200 L CG SAE 5-4 CG SAE 3-2-1 COUPLING SAE J620 DIMENSIONS [mm] SB 645 290 295 SA 645 280 285 7½ 8 10 11½ 14 SAE J617 4 • • • • • 28 MA 735 310 305 MB 735 330 325 COUPLING [mm] CONNECTING FLANGE 5 70 18.5 5 3 2 • • • • • • 1 • SAE J620 PA MA 7½ 8 10 11½ 14 241,30 263,52 314,32 352,42 466,72 222,25 244,48 295,28 333,38 438,15 Y NR Ø 8 6 8 8 8 9 11 11 11 14 FLANGE [mm] β WA WB 45° 60° 45° 45° 45° 30.2 62.0 53.8 39.6 25.4 19.8 10.4 24.6 SAE N J617 5 4 3 2 1 0 -0,13 314,32 361,95 409,58 447,68 511,18 P M 440 440 451 489 552 333,38 381,00 428,62 466,72 530,22 Z NR Ø 8 12 12 12 12 11 11 11 11 11 α 45° 30° 30° 30° 30° DOUBLE BEARING 200 FRAME SIZE AVR L 67 420 CG 30° 0 -0.13 Ø381 0 -1.0 Ø375 Ø402 G Ø361,95 Ø432 18 h9 60 m6 392 N°12 M10 247 362 N°6 5 25 85 140 140 318 140 280 390 330 MJL 200 L CG SA 695 245 70 18,5 M20 DIN 332 6 200 64 DIMENSIONS [mm] SB 695 260 MA 785 270 28 MB 785 300 MarelliGenerators ® HEADQUARTERS ITALIAN BRANCHES Marelli Motori S.p.A. Milan Via Sabbionara, 1 36071 Arzignano (VI) - Italy (T) +39 0444 479.711 (F) +39 0444 479.888 www.marellimotori.com [email protected] Via Cesare Cantù, 29 20092 Cinisello Balsamo (MI) - Italy (T) +39 02 660.131.66 (F) +39 02 660.134.83 [email protected] Florence Via Panciatichi, 37/2 50127 Firenze - Italy (T) +39 055 431.838 (F) +39 055 433.351 [email protected] MARELLI MOTORI OVERSEAS COMPANIES GREAT BRITAIN CENTRAL EUROPE USA Marelli UK, Ltd Marelli Central Europe Gmbh Marelli USA, Inc Meadow Lane Loughborough Leicester LE111NB UK (T) +44 1509 615 518 (F) +44 1509 615 514 [email protected] Heilswannenweg 50 31008 Elze Germany 1620 Danville Road PO Box 410 Harrodsburg, KY 40330 USA (T) +1 859 734 2588 (F) +1 859 7340629 [email protected] ASIA PACIFIC SOUTH AFRICA Marelli Asia Pacific Sdn Bhd Marelli Electrical Machines South Africa (Pty) Ltd Lot PT 5038-5041 Jalan Teluk Datuk 28/40 Off Persiaran Sepang, Seksyen 28, 40400 Shah Alam, Selangor D.E. Malaysia (T) +60 3 5192 7213 (F) +60 3 5192 6293 [email protected] Unit 4, 55 Activia Rd - Activia Park Elandsfontein, 1406 Gauteng Republic of South Africa (T) +27 11 822 5566 (F) +27 11 828 8089 [email protected] SIN.CT.029.0 GB (T) +49 5068 462 400 (F) +49 5068 462 409 [email protected] MARELLI MOTORI reserves the right to change the design, technical specification and dimensions in order to update or improve its products, without prior notice Three Phase Synchronous Generators 160 - 900 FRAME SIZES INDUSTRIAL / MARINE APPLICATIONS SIN.CT.024.13 GB CONTENT Page THE COMPANY 4 POWER RANGE 4 STANDARDS 5 VOLTAGE AND FREQUENCY 5 AVAILABLE VOLTAGES (SPECIAL VOLTAGES) 5 WINDINGS 5 INSULATION, IMPREGNATION AND PROTECTIVE TREATMENT OF WINDING 5 RADIO INTERFERENCE 5 PROTECTION DEGREE 5 VENTILATION AND DIRECTION OF ROTATION 5 ROTOR BALANCING 5 VIBRATION 5 BEARINGS AND OVER SPEED 5 TESTING CAPABILITY 5 OPERATING CONDITIONS 6 EXCITATION SYSTEM 7 THREE PHASE SHORT CIRCUIT CURRENT 7 AUTOMATIC VOLTAGE REGULATOR SPECIFICATIONS 7 SELECTION GUIDE - INDUSTRIAL APPLICATION / LOW VOLTAGE 8 SELECTION GUIDE - INDUSTRIAL APPLICATION / MEDIUM VOLTAGE 10 SELECTION GUIDE - INDUSTRIAL APPLICATION / HIGH VOLTAGE 12 SELECTION GUIDE - MARINE APPLICATION / LOW VOLTAGE 14 SELECTION GUIDE - MARINE APPLICATION / LOW VOLTAGE / WITH EXCHANGER 16 DRAWINGS 18 DIMENSIONS 19 THE COMPANY Marelli Motori S.p.A. is an Italian manufacturer of electrical machines with a tradition dating back to 1891. Today Marelli Motori is recognized internationally as a leading supplier of generators and electric motors. MarelliGenerators is the company brand specifically designed to offer a complete selection of synchronous machines for low, medium and high voltage systems up to 15 kV. Fields of applications include conventional power, renewable energy and marine industry. A wide range of standard and customised solutions is provided for industrial gen-sets, cogeneration, telecommunication, UPS systems, offshore, Oil & Gas, shipboard power and hydropower plants. RELIABILITY Long life endurance of electrical components and housing. Windings are impregnated with high quality processes and additional protection is used against tough environmental conditions. The design ensures reliability under difficult operating conditions. PERFORMANCE The latest technologies and the highest quality materials are used to guarantee the best performances for any kind of application KNOW HOW & CAPABILITIES For special projects generators can be designed for specific application including: Nominal voltage from 380 to 15000 Volts. • • Polarities/speeds not mentioned in the following pages are available on request. • Single and double bearing solutions. • Ball, roller or sleeve bearings are available. • Anti condensation heaters are available. • Wide range of sensors to monitor stator winding and bearing temperatures. • Degree of protection up to IP55. • Auxiliary and neutral point terminal boxes. • Vibration sensors. • Neutral point current transformers (CT) are available (single core, double core or triple core). • Multicore voltage transformers. POWER RANGE INDUSTRIAL APPLICATION / LOW VOLTAGE INDUSTRIAL APPLICATION / MEDIUM VOLTAGE 10 8 8 poles poles 10 6 6 4 4 0 1000 2000 3000 4000 5000 0 2000 Nominal Output [kVA] INDUSTRIAL APPLICATION / HIGH VOLTAGE 6000 8000 10000 MARINE APPLICATION / LOW VOLTAGE 8 8 poles 10 poles 10 6 6 4 4 0 2000 4000 6000 8000 10000 0 1000 Nominal Output [kVA] 2000 3000 Nominal Output [kVA] 50 Hz 4000 Nominal Output [kVA] 60 Hz 4000 5000 STANDARDS All generators are designed in compliance with: EN 60034-1; BS 4999-5000; VDE 0530, NF 51-100; NF 51-111; OVE M-10; NEMA MG 1.22, and conform to EU rules and are CE marked. The marine ranges are type approved by DNV. On request MarelliMotori is able to supply UL/CSA certified generators (for the US market and the Canadian market). VOLTAGE AND FREQUENCY The generators in standard configuration can operate at 50 Hz and 60 Hz. Different voltages are available on request. Frame Size 160 ÷ 355 MA (12 leads generators) Connection Voltage at 50 Hz [V] Series star 380 ÷ 440 380 ÷ 480 Parallel star 190 ÷ 220 190 ÷ 240 Series delta 220 ÷ 254 220 ÷ 277 Star 380 ÷ 415 416 - 480 Delta 230 ÷ 240 240 - 277 Star 380 ÷ 415 416 - 480 Star (50Hz) 690 Contact Marelli Motori Contact Marelli Motori 690 355 MB (6 leads generator) 400 ÷ 630 (6 leads generators) 710* ÷ 900* (6 leads generators) Star (60Hz) *: For available voltage when operating at different frequency contact Marelli Motori. Voltage at 60 Hz [V] AVAILABLE VOLTAGES Special voltages are available on request in accordance with the table below. Please contact Marelli Motori for further informations. Frame Size 120V ÷ 380V 480V ÷ 690V 690V ÷ 1000V 1000V ÷ 7200V 7200V ÷ 11000V 11000V ÷ 15000V 160 200 ÷ 315 355 400 450 500 ÷ 630 710 ÷ 900 : Available voltage : Not applicable (for further detail please contact Marelli Motori) INSULATION, IMPREGNATION AND PROTECTIVE TREATMENT OF WINDING For low voltage class H. For medium and high voltage class F . Windings are impregnated with high quality materials and using the latest technologies including Vacuum Pressure Impregnation (VPI). A further protective treatment is applied , making the generators suitable for tough environmental conditions. Special degrees of protection and tropicalization are available on request. WINDINGS Generators up to frame 560 included for industrial application are constructed with 2/3 pitch winding to reduce the voltage harmonic content in applications with non-linear loads. The no-load voltage waveform is sinusoidal with Total Harmonic Distortion (THD) content less than 2%. RADIO INTERFERENCE Marelli Generators are equipped with devices in order to Class B Group 1 radio interference as defined by EN55O11. PROTECTION DEGREE The standard protection degree is IP 23. Higher protection degrees are available on request for frame sizes 250 to 800 through the application of filter, air-to-air or air-to-water heat exchanger up to IP 55. VENTILATION AND DIRECTION OF ROTATION Generators are axially self-cooled and can run in both directions of rotation. Air inlet direction is: • Frame size 160 : Radial • Frame sizes 200 and higher: Axial + radial ROTOR BALANCING Rotors are dynamically balanced with a half key applied to the shaft extension in accordance with IEC 60034-14 to vibration grade normal A in standard configuration. Generators can be supplied with special vibration levels on request. VIBRATION Vibration level is in accordance with ISO 10816. Measurement, evaluation and limits of vibration severity are in accordance with IEC 60034-14. BEARINGS AND OVER SPEED Oversized bearings. The permissible over speed is 1,5 times the rated speed (referred to 50 Hz). Sleeve bearings from 400 to 900 frame sizes are available on request. TESTING CAPABILITY Marelli Motori has a high capability test room with the possibility of testing generators in their original mounting (vertical and horizontal) and for all designed voltages (up to 15000 V) and power (up to 10 MVA). Testing can be conducted at different frequency (50 Hz or 60 Hz) through a regenerative Active Front End System. Testing is carried out in compliance with all major international standards (IEC, IEEE), customer specifications, marine/navy rules. OPERATING CONDITIONS Overloads During continuous duty (S1), the following overloads are allowed : 10% for 1 hour 15% for 10 minutes 30% for 4 minutes 50% for 2 minutes These overloads must be occasional and followed by one hour of running at normal load or less. Stand-by ratings are based on continuous supply of loads for any utility power failure. No overloads are allowed in stand-by duty. Single phase operation Three phase (12-wire) wound generators can be reconnected and derated to 66% for single phase operation (with a zig-zag connection). Otherwise generators with dedicated (4-wire) single phase windings can be supplied on request. The following derating factors must be applied to the corresponding configurations Connection K factor (L - L) K factor (L - N) Star series 0,60 0,33 Delta series 0,50 - Star parallel 0,60 0,33 Zig - zag 0,66 0,33 Parallel operation All generators are provided with a amply sized damper cage and are suitable for parallel operation with other generators, when equipped with the paralleling unit. A power factor regulator is available on request. No-Load operation at reduced speed All regulators work to reduce the excitation current in order to protect the excitation system when the generator is being used at reduced speed. Transient ratings The voltage drop due to the application of full load at 0,8 power factor inductive on industrial 160 ÷ 400 frame size generators varies between 16% and 20% of the rated voltage: the output voltage recovers to within 3% of the rated value in less than 0,3 seconds. Altitude The rated outputs refer to installation up to 1.000 m a.s.l. Above this level the following derating factors must be applied. Altitude (m asl) < 1.000 < 1.500 < 2.000 < 2.500 < 3.000 K Factor 1,00 0,96 0,93 0,90 0,86 Ambient temperature The rated outputs given in this catalogue are based on a maximum ambient temperature of 40 °C. When operating at different ambient temperatures the output rating can be obtained by applying the factors as in the following table. Ambient Temperature [°C] 30 35 40 45 50 55 K Factor 1.04 1,00 1,00 0,96 0,93 0,9 Power factor The nominal power factor is 0,8 lagging. For different power factor values the following derating factors must be applied. Power Factor 1 0,8 0,7 0,6 0,5 0,3 0 K Factor 1,00 1,00 0,93 0,88 0,84 0,82 0,80 Special configurations The following derating factors must be applied to the corresponding configurations Special configuration Air to air heat exchanger Air to water heat exchanger1 Inlet filters IP43 inlet and outlet filters IP44 inlet and outlet filters K Factor 0,70 0,90 0,92 0,85 0,80 : for marine application refer to MJRM series 1 EXCITATION SYSTEM The generators are self-exciting, by means of a brushless type excitation system. The voltage is maintained within ±0,5% of the nominal value in steady state condition with a balanced and non distorting load. Auxiliary winding The excitation system of generators from frame size 200 to 450 is fed by an auxiliary winding which gives a better response to the variation in loads and sustains the power supply in the case of a short-circuit. Auxiliary winding on the 160 frame is available on request. Permanent Magnet Generators (PMG) The generators from frame size 225 mm and larger can be supplied with a Permanent Magnet Generator (PMG) if required, which gives an independent supply to the excitation system. PMG is advisable for use with generators in particular applications such as unbalanced loads and distorting loads. Manual voltage regulation Available within ±5% of the rated value by means of a potentiometer placed inside the voltage regulator. A remote voltage setting is possible by means of an external potentiometer, which can be supplied on request. Over-excitation protection Generators from frame sizes 160 to 450 are equipped with adjustable over-excitation protection which will protect the alternator in the event of over excitation when combined with an external protection system. THREE PHASE SHORT CIRCUIT CURRENT Generators with auxiliary windings or PMG ensure a three phase short-circuit current (Icc) higher than 3 times the rated current (In): Icc > 3 In. Generators from 500 frame size are supplied with an over excitation device which ensures a three phase short circuit current higher than 3 times the rated current. AUTOMATIC VOLTAGE REGULATOR (AVR) SPECIFICATIONS The generators are equipped with the following AVR set. Generator frame size MARK V MARK I ANALOGUE MGC I MGC II MARK X DIGITAL MEC 100 series M16FA655A M40FA640A M40FA610A M63FA310A M40FA644A Standard 160 ÷ 250 315 ÷ 450 500 ÷ 560 630 ÷ 800 - - On request - 160 ÷ 250 and 500 ÷ 630 - - 225 ÷ 560 400 ÷ 900 Single phase Three phase AVR supply Voltage sensing Auxiliary winding*, mains PMG Single phase Voltage remote control M71FA310A M710FA320A Auxiliary winding, mains, PMG Three phase Arrangement Radio interference suppressor Internal Arrangement for external filter Over-excitation device - Parallel operation with the mains - Arrangement for external device Internal Parallel operation with similar generators - Arrangement Internal - Field over-current, Field over-voltage, Generator over/under voltage, Generator over-current, Loss of sensing Standard protections Arrangement for VARICOMP Over-excitation Limiters Functions Over-excitation Under-frequency, Over/under-excitation Under-frequency - Auxiliary inputs PC interface, Soft start, Auxiliary inputs, Contact inputs, PC interface, Soft start, Auxiliary inputs, Contact inputs, DMS *: Auxiliary winding on the 160 frame is available on request. Analogue AVR (MARK and MGC series) The voltage regulators are the standard features for synchronous generators of MarelliMotori. These regulators are suitable for low and medium voltage machines. The regulators are fully insulated in order to maintain high reliability also with severe ambient conditions (high level of humidity, dust, salt atmosphere), and in case of high vibrations level. The regulators can work both for single and 3-phase operations. Digital AVR (MEC100 series) MEC100 series regulators are microprocessor-based devices for the excitation control of MarelliMotori synchronous generators. The full-function and full-protection control system ensures high performances with suitable accuracy in a wide range of applications. A proprietary user-friendly software is provided with the equipment for commissioning and monitoring purposes. The MEC100 series includes models with embedded optional features like the Diode Monitoring functions. The MEC100 complies also with the DNV rules. Other AVRs may be installed on request. SELECTION GUIDE - INDUSTRIAL APPLICATION / LOW VOLTAGE Type Leads 400V / 50Hz Power rating [kVA] Temp. rise / Ambient temp. [°C] Continuous duty Stand by 125/40 105/40 80/40 163/27 150/40 ΔT cl. H 4 poles ΔT cl. F ΔT cl. B Efficiency 4/4 pf = 0,8 125/40 [%] 400 V @ 50 Hz - 1500 rpm 480V / 60Hz Power rating [kVA] Temp. rise / Ambient temp. [°C] Continuous duty Stand by 125/40 105/40 80/40 163/27 150/40 ΔT cl. H ΔT cl. F ΔT cl. B Efficiency 4/4 pf = 0,8 125/40 Inertia B3 Weight B3 Approx. J Approx. [%] [kg m2] [kg] 480V @ 60Hz - 1800 rpm IP23 MJB 160 SA4 MJB 160 SB4 MJB 160 SC4 MJB 160 MA4 MJB 160 MB4 12 12 12 12 12 17,0 20,0 23,0 28,0 32,0 15,6 18,4 21,1 25,7 29,4 13,6 16,0 18,4 22,4 25,6 18,7 22,0 25,3 30,8 35,2 18,0 21,2 24,4 29,7 33,9 85,6 87,4 87,5 88,2 88,3 21,4 24,7 29,9 34,2 40,0 19,6 22,6 27,4 31,4 36,7 17,1 19,8 23,9 27,4 32,0 23,5 27,2 32,9 37,6 44,0 22,7 26,2 31,7 36,3 42,4 86,4 88,2 88,3 89,2 89,1 0,11 0,12 0,14 0,16 0,17 120 130 140 165 175 MJB 200 SA4 MJB 200 SB4 MJB 200 MA4 MJB 200 MB4 12 12 12 12 42,0 48,0 62,0 72,0 38,5 44,0 57,0 66,0 33,6 38,4 49,6 57,6 46,2 52,8 68,2 80,0 44,5 50,9 65,7 76,5 88,5 88,7 90,1 90,5 51,0 59,5 76,0 87,0 46,8 54,6 69,7 79,8 40,8 47,6 60,8 69,6 56,1 65,4 83,6 96,5 54,1 63,1 80,6 92,0 89,5 89,3 90,7 90,9 0,28 0,30 0,36 0,43 215 220 260 300 MJB 225 SA4 MJB 225 SB4 MJB 225 MA4 MJB 225 LA4 12 12 12 12 85,0 92,0 105 132 78,0 84,4 96,2 121 68,0 73,6 84,0 106 93,5 101 116 145 90,1 97,5 111 140 91,0 91,5 91,8 92,2 108 114 131 158 98,7 104 120 145 86,1 90,9 105 127 118 125 144 174 114 120 139 168 91,5 92,0 92,6 93,0 0,63 0,70 0,79 0,92 345 350 390 420 MJB 250 MA4 MJB 250 MB4 MJB 250 LA4 MJB 250 LB4 12 12 12 12 165 185 220 250 150 170 200 230 132 150 175 200 180 205 240 275 175 195 235 265 92,9 93,0 93,2 93,4 205 230 270 300 190 215 250 275 164 184 216 240 225 255 295 330 215 245 285 320 93,6 93,6 93,9 93,9 1,4 1,7 1,9 2,1 530 590 660 710 MJB 315 SA4 MJB 315 SB4 MJB 315 MA4 MJB 315 MB4 12 12 12 12 300 350 410 450 275 320 375 415 240 280 330 360 330 385 450 500 320 370 435 475 93,1 93,4 93,7 94,0 370 425 500 550 340 390 460 505 296 340 400 440 405 470 550 610 390 450 530 585 93,8 94,0 94,2 94,8 3,7 4,2 4,8 5,7 830 920 1060 1200 MJB 355 SA4 MJB 355 SB4 MJB 355 MA4 MJB 355 MB4 12 12 12 6 510 570 680 800 470 520 625 730 410 455 545 640 560 625 750 880 540 605 720 850 94,0 94,6 94,7 95,0 625 695 825 960 575 640 760 880 500 556 660 768 690 765 910 1055 665 735 875 1020 94,5 95,1 95,1 95,3 8,0 9,3 11,7 13,1 1250 1550 1800 2050 MJB 400 MA4 MJB 400 MB4 MJB 400 LA4 MJB 400 LB4 6 6 6 6 930 1050 1150 1300 850 960 1055 1190 745 840 920 1040 1025 1155 1265 1430 985 1115 1220 1380 95,2 95,3 95,6 95,8 1175 1320 1420 1625 1080 1210 1305 1490 940 1056 1136 1300 1295 1450 1560 1790 1245 1400 1505 1725 95,7 95,7 96,0 96,3 16,3 17,0 19,3 22,5 2250 2300 2550 2800 MJB 450 MB4 MJB 450 LA4 MJB 450 LB4 6 6 6 1500 1650 1875 1375 1510 1720 1200 1320 1500 1650 1815 2065 1590 1750 1990 95,9 96,0 96,2 1800 1980 2250 1650 1815 2065 1440 1584 1800 1980 2180 2475 1910 2100 2385 96,3 96,3 96,4 29,0 34,0 38,0 3200 3600 4000 MJB 500 SC4 MJB 500 MB4 MJB 500 LA4 6 6 6 2000 2200 2500 1835 2020 2290 1600 1760 2000 2200 2420 2750 2120 2330 2650 96,1 96,2 96,4 2400 2640 3000 2200 2420 2750 1920 2112 2400 2640 2905 3300 2545 2800 3180 96,5 96,5 96,7 46,7 52,5 61,5 4000 4400 5100 MJB 560 MA4 MJB 560 LA4 6 6 2650 3200 2430 2935 2120 2560 2915 3520 2810 3390 96,4 96,5 3050 3680 2800 3375 2440 2945 3355 4050 3235 3900 96,5 96,6 83,0 95,0 5200 6300 MJB 630 MB41 MJB 630 LA41 6 6 3300 3600 3025 3300 2640 2880 3565 3890 3465 3780 96,4 96,5 3795 4140 3480 3795 3040 3315 4100 4470 3985 4345 96,7 96,8 140 158 7500 8000 MJB 710 SC42 MJB 710 MB42 6 6 4000 4300 3670 3940 3200 3440 4320 4645 4200 4515 96,2 96,4 4400 4730 4035 4340 3520 3785 4750 5110 4620 4965 96,5 96,7 on request on request on request on request : 690 V recommended : 690 V only. For different voltage please contact MarelliMotori. These generators are dedicated for 50 Hz or 60 Hz. For available voltage and performance when operating at different frequency contact MarelliMotori. Ratings refer to following conditions: balanced non-deforming load, altitude 1000 m a.s.l., minimum power factor 0,8. 1 2 SELECTION GUIDE - INDUSTRIAL APPLICATION / LOW VOLTAGE Type Leads 6 poles 400V / 50Hz Power rating [kVA] Temp. rise / Ambient temp. [°C] Continuous duty 125/40 105/40 80/40 ΔT cl. H ΔT cl. F ΔT cl. B Efficiency 4/4 pf = 0,8 125/40 [%] 400 V @ 50 Hz - 1000 rpm 480V / 60Hz Power rating [kVA] Temp. rise / Ambient temp. [°C] Continuous duty 125/40 105/40 80/40 ΔT cl. H ΔT cl. F ΔT cl. B Efficiency 4/4 pf = 0,8 125/40 [%] Inertia B3 Weight B3 Approx. J [kg m2] Approx. 480 V @ 60 Hz - 1200 rpm [kg] IP23 MJB 400 SA6 MJB 400 SB6 MJB 400 SC6 MJB 400 MA6 MJB 400 MB6 MJB 400 LA6 MJB 400 LB6 6 6 6 6 6 6 6 400 450 500 620 700 800 970 365 410 460 570 640 735 890 320 360 400 500 560 640 780 92,7 93,0 93,7 94,1 94,3 94,6 94,8 500 565 625 775 875 1000 1215 460 520 575 715 805 920 1120 400 455 500 620 700 800 975 93,0 93,4 94,0 94,4 94,6 94,9 95,1 11,8 14,1 16,8 17,9 19,4 20,9 24,2 1450 1600 1800 2000 2260 2530 2750 MJB 450 MB6 MJB 450 LA6 MJB 450 LB6 6 6 6 1040 1200 1360 950 1100 1250 835 960 1090 94,6 95,2 95,4 1300 1500 1700 1200 1380 1560 1040 1200 1360 95,5 95,7 95,6 49,9 55,0 61,4 3200 3600 3900 MJB 500 MA6 MJB 500 MB6 MJB 500 MC6 MJB 500 LA6 6 6 6 6 1400 1540 1600 1680 1275 1400 1465 1530 1120 1235 1280 1345 95,1 95,2 95,2 95,4 1750 1925 2000 2100 1600 1770 1840 1930 1400 1540 1600 1680 95,7 95,8 95,8 96,0 64,7 73,6 80,2 88,9 4150 4600 4900 5300 MJB 560 SC6 MJB 560 MA6 MJB 560 LA6 6 6 6 1870 2080 2360 1700 1900 2150 1500 1665 1890 95,9 96,0 96,2 2150 2400 2700 1980 2200 2480 1720 1920 2160 96,4 96,5 96,7 115 115 135 4900 5400 6500 MJB 630 SD6 MJB 630 MA6 MJB 630 MC6 6 6 6 2450 2750 3000 2250 2500 2750 1960 2200 2400 95,7 95,7 96,0 2740 3100 3350 2520 2850 3100 2195 2480 2680 96,2 96,2 96,4 170 190 210 6900 7900 8100 MJB 710 SC61 MJB 710 MA61 6 6 3500 3800 3200 3500 2800 3040 96,0 96,7 3850 4180 3550 3850 3080 3345 96,5 96,7 on request on request on request on request 8 poles 400 V @ 50 Hz - 750 rpm 480 V @ 60 Hz - 900 rpm IP23 MJB 400 SA8 MJB 400 SB8 MJB 400 SC8 MJB 400 MA8 MJB 400 MB8 MJB 400 LA8 MJB 400 LB8 6 6 6 6 6 6 6 240 310 360 430 510 600 740 220 285 330 395 465 550 680 195 250 290 345 410 480 595 91,5 92,0 92,3 92,5 93,0 93,2 93,5 300 400 450 540 640 750 925 275 365 410 495 585 685 850 240 320 360 435 515 600 740 92,0 92,5 92,8 93,0 93,5 93,7 94,0 13,5 16,2 19,1 20,6 22,4 24,1 25,4 1450 1600 1800 2000 2260 2530 2750 MJB 500 SA8 MJB 500 SC8 MJB 500 MB8 MJB 500 LA8 6 6 6 6 820 1020 1270 1400 750 935 1165 1275 660 820 1020 1120 94,5 95,0 95,1 95,2 1025 1275 1590 1680 940 1170 1455 1530 820 1020 1275 1345 95,1 95,5 95,6 95,9 55,1 74,2 82,2 95,0 3200 3800 4700 5400 MJB 560 SC8 MJB 560 MB8 MJB 560 LA8 6 6 6 1480 1750 2025 1350 1600 1850 1185 1400 1620 95,4 95,6 95,9 1775 2075 2400 1620 1900 2200 1420 1660 1920 95,8 95,9 96,1 115 130 155 5100 5700 6700 MJB 630 MC8 MJB 630 LA8 6 6 2200 2450 2000 2250 1760 1960 95,5 96,1 2350 2820 2150 2580 1880 2260 96,2 96,5 195 240 8300 9200 MJB 710 SA81 MJB 710 SC81 MJB 710 MA81 MJB 710 MB81 6 6 6 6 2750 3100 3600 3700 2500 2850 3300 3400 2200 2480 2880 3000 96,2 96,5 96,6 96,7 2850 3250 3750 4000 2600 3000 3450 3750 2280 2600 3000 3200 96,5 96,8 96,9 96,9 on request on request on request on request on request on request on request on request 10 poles 400 V @ 50 Hz - 600 rpm 480 V @ 60 Hz - 720 rpm IP23 MJB 500 SA10 MJB 500 SC10 MJB 500 MB10 MJB 500 LA10 6 6 6 6 595 745 870 965 550 685 800 885 480 600 700 775 93,9 94,2 94,7 95,0 740 935 1050 1210 680 860 965 1110 595 750 840 970 94,4 94,7 95,2 95,5 63,8 81,6 89,7 106 3300 3900 4800 5600 MJB 630 SC10 MJB 630 MA10 MJB 630 MB10 MJB 630 LA10 6 6 6 6 1200 1430 1690 1750 1100 1320 1550 1600 960 1145 1355 1400 95,0 95,4 95,5 95,7 1380 1650 1945 2010 1260 1510 1780 1840 1105 1320 1560 1610 95,5 95,9 96,0 96,2 180 200 230 260 7300 8500 8700 9400 MJB 710 SC101 MJB 710 MA101 MJB 710 MB101 MJB 710 LB101 6 6 6 6 2470 2960 3160 3420 2270 2715 2900 3130 1980 2370 2530 2740 96,2 96,4 96,4 96,6 2770 3320 3550 3825 2530 3050 3250 3510 2220 2660 2840 3060 96,4 96,6 96,6 96,8 on request on request on request on request on request on request on request on request : 690 V recommended. These generators are dedicated for 50 Hz or 60 Hz. For available voltage and performance when operating at different frequency contact MarelliMotori. Ratings refer to following conditions: balanced non-deforming load, altitude 1000 m a.s.l., minimum power factor 0,8. 1 SELECTION GUIDE - INDUSTRIAL APPLICATION / MEDIUM VOLTAGE 3000V / 50Hz Type Leads 105/40 ΔT cl. F 4 poles 6000V / 50Hz Power rating [kVA] Temp. rise / Ambient temp. [°C] Continuous duty 80/40 105/40 80/40 ΔT cl. B ΔT cl. F ΔT cl. B 3000 V - 6000 V @ 50 Hz - 1500 rpm 4160V / 60Hz 105/40 ΔT cl. F 4160 V - 6600 V @ 60 Hz - 1800 rpm IP23 MJH 400 MA4 MJH 400 LA4 MJH 400 LB4 6 6 6 600 840 1020 520 730 890 550 740 920 480 650 810 700 960 1180 610 840 1030 660 900 1120 575 785 975 MJH 450 MB4 MJH 450 LA4 MJH 450 LB4 6 6 6 1050 1200 1300 910 1040 1130 1000 1120 1250 870 970 1090 1130 1250 1400 980 1090 1220 1100 1200 1330 960 1045 1160 MJH 500 MA4 MJH 500 MB4 MJH 500 LA4 MJH 500 LB4 6 6 6 6 1450 1700 1850 1950 1260 1480 1610 1700 1350 1500 1750 1900 1170 1300 1520 1650 1660 2000 2150 2250 1440 1740 1870 1960 1500 1650 1900 2200 1305 1440 1655 1915 MJH 560 MA4 MJH 560 LA4 MJH 560 LB4 6 6 6 2300 2550 2800 2000 2220 2440 2250 2450 2750 1960 2130 2400 2450 2800 3050 2130 2440 2650 2500 2750 3000 2175 2395 2610 MJH 630 MB4 MJH 630 LA4 MJH 630 LB4 6 6 6 2900 3200 3600 2520 2780 3130 2900 3200 3550 2520 2750 3090 3150 3500 3700 2750 2050 3220 3150 3500 3700 2745 3045 3220 MJH 710 SC4 MJH 710 MB4 MJH 710 LA4 MJH 710 LB4 6 6 6 6 4200 4800 5500 6000 3650 4180 4780 5220 4200 4800 5500 6000 3650 4180 4780 5220 4500 5000 5800 6600 3920 4350 5050 5750 4500 5000 5800 6600 3920 4350 5050 5750 MJH 800 6 9000 7830 9000 7830 on request on request on request on request 6 poles 3000 V - 6000 V @ 50 Hz - 1000 rpm 4160 V - 6600 V @ 60 Hz - 1200 rpm IP23 MJH 400 LA6 MJH 400 LB6 MJH 450 MB6 MJH 450 LA6 MJH 450 LB6 6 6 6 6 6 620 660 680 750 840 540 575 590 655 735 540 570 515 650 730 470 500 780 570 640 710 760 680 860 970 620 665 715 750 845 650 700 625 800 890 570 610 MJH 500 MA6 MJH 500 MB6 MJH 500 LA6 6 6 6 930 1100 1240 810 960 1080 800 960 1100 700 840 960 1070 1270 1430 935 1105 1245 970 1160 1330 845 1010 1160 MJH 560 SC6 MJH 560 MB6 MJH 560 LA6 6 6 6 1620 1950 2150 1410 1700 1875 1500 1800 2000 1305 1570 1740 1800 2100 2200 1570 1830 1915 1680 2000 2050 1465 1740 1785 MJH 630 MA6 MJH 630 LA6 MJH 630 LB6 6 6 6 2250 2500 2700 1960 2175 2350 2100 2300 2500 1830 2005 2175 2300 2600 2700 2005 2265 2350 2150 2350 2500 1875 2045 2175 MJH 710 SC6 MJH 710 MA6 MJH 710 MB6 MJH 710 LA6 MJH 710 LB6 6 6 6 6 6 3450 4250 4650 4850 5150 3005 3700 4050 4220 4485 3300 4100 4500 4700 5000 2875 3570 3915 4090 4350 3500 4300 4700 4900 5200 3045 3745 4090 4265 4525 3350 4100 4500 4700 5000 2915 3570 3915 4090 4350 MJH 800 MA6 MJH 800 MB6 MJH 800 LA6 MJH 800 LB6 6 6 6 6 6100 6800 7400 8000 5310 5920 6440 6960 6000 6700 7400 8000 5220 5830 6440 6960 6200 6800 7500 8000 5395 5920 6525 6960 6100 6700 7500 8000 5310 5830 6525 6960 Ratings refer to following conditions: balanced non-deforming load, altitude 1000 m a.s.l., minimum power factor 0,8. All generators are dedicated for 50 Hz or 60 Hz. MJH 900 10 6600V / 60Hz Power rating [kVA] Temp. rise / Ambient temp. [°C] Continuous duty 80/40 105/40 80/40 ΔT cl. B ΔT cl. F ΔT cl. B For available power and speed contact Marelli Motori 700 775 SELECTION GUIDE - INDUSTRIAL APPLICATION / MEDIUM VOLTAGE 3000V / 50Hz Type Leads 105/40 ΔT cl. F 8 poles 6000V / 50Hz Power rating [kVA] Temp. rise / Ambient temp. [°C] Continuous duty 80/40 105/40 80/40 ΔT cl. B ΔT cl. F ΔT cl. B 3000 V - 6000 V @ 50 Hz - 750 rpm 4160V / 60Hz 105/40 ΔT cl. F 6600V / 60Hz Power rating [kVA] Temp. rise / Ambient temp. [°C] Continuous duty 80/40 105/40 80/40 ΔT cl. B ΔT cl. F ΔT cl. B 4160 V - 6600 V @ 60 Hz - 900 rpm IP23 MJH 400 LA8 MJH 400 LB8 6 6 440 510 385 445 380 440 335 385 510 585 445 510 470 540 410 470 MJH 500 MA8 MJH 500 MB8 MJH 500 LA8 MJH 500 LB8 6 6 6 6 780 920 1050 1150 680 805 915 1005 680 790 920 1050 595 690 805 915 900 1060 1220 1300 785 925 1065 1135 820 970 1100 1200 715 845 960 1045 MJH 560 MB8 MJH 560 LA8 6 6 1350 1550 1175 1350 1250 1440 1090 1255 1550 1720 1350 1500 1500 1650 1305 1440 MJH 630 MB8 MJH 630 LA8 MJH 630 LB8 6 6 6 1750 1850 2000 1525 1610 1740 1600 1700 1800 1395 1480 1570 1840 1950 2120 1600 1700 1850 1750 1850 2000 1525 1610 1740 MJH 710 SA8 MJH 710 SC8 MJH 710 MA8 MJH 710 MB8 MJH 710 LB8 6 6 6 6 6 2600 3200 3900 4350 4600 2265 2785 3395 3785 4005 2400 3000 3750 4200 4500 2090 2610 3265 3655 3915 2730 3330 4150 4600 4750 2380 2900 3620 4000 4140 2600 3200 4000 4500 4650 2260 2780 3480 3910 4050 MJH 800 MB8 MJH 800 LA8 6 6 4900 5800 4265 5050 4800 5700 4180 4960 5100 6100 4440 5300 5000 6000 4350 5200 10 poles 3000 V - 6000 V @ 50 Hz - 600 rpm 4160 V - 6600 V @ 60 Hz - 720 rpm IP23 MJH 500 SA10 MJH 500 MA10 MJH 500 MB10 MJH 500 LA10 6 6 6 6 460 560 660 730 400 490 575 640 400 480 570 650 350 420 500 570 530 650 760 850 460 570 660 740 470 580 690 760 410 500 600 660 MJH 630 SA10 MJH 630 MA10 MJH 630 MB10 MJH 630 LA10 MJH 630 LB10 6 6 6 6 6 950 1100 1300 1500 1700 830 960 1130 1300 1480 900 1000 1200 1350 1450 780 870 1050 1170 1260 1030 1200 1400 1600 1800 900 1050 1220 1400 1570 970 1130 1350 1500 1700 850 980 1170 1300 1480 MJH 710 SA10 MJH 710 MA10 MJH 710 LA10 MJH 710 LB10 6 6 6 6 2000 2400 2700 3400 1740 2090 2350 2960 1800 2200 2400 3200 1570 1920 2100 2780 2100 2500 2800 3740 1830 2170 2440 3250 1950 2350 2640 3520 1700 2050 2300 3060 MJH 800 SA10 MJH 800 MA10 MJH 800 LA10 6 6 6 3700 4100 4800 3220 3570 4180 3500 3900 4500 3050 3400 3920 4000 4500 5250 3480 3900 4570 3800 4280 4900 3300 3730 4260 Ratings refer to following conditions: balanced non-deforming load, altitude 1000 m a.s.l., minimum power factor 0,8. All generators are dedicated for 50 Hz or 60 Hz. MJH 900 For available power and speed contact Marelli Motori 11 SELECTION GUIDE - INDUSTRIAL APPLICATION / HIGH VOLTAGE Type Leads 4 poles 11000V / 50Hz Power rating [kVA] Temp. rise / Ambient temp. [°C] Continuous duty 105/40 80/40 ΔT cl. F ΔT cl. B 11000 V @ 50 Hz - 1500 rpm 13800V / 60Hz Power rating [kVA] Temp. rise / Ambient temp. [°C] Continuous duty 105/40 80/40 ΔT cl. F ΔT cl. B 13800 V @ 60 Hz - 1800 rpm MJH 450 LA4 6 900 780 - - MJH 500 MA4 MJH 500 LA4 MJH 560 MA4 MJH 560 LA4 6 6 6 6 1300 1500 1850 2100 1130 1300 1610 1830 1400 1600 2000 2250 1220 1395 1740 1960 MJH 630 SC4 MJH 630 MA4 MJH 630 LB4 6 6 6 2500 2850 3250 2175 2480 2830 2700 3000 3400 2350 2610 2960 MJH 710 SC4 MJH 710 MA4 MJH 710 LB4 6 6 6 3600 4600 5500 3130 4000 4780 4000 5250 5500 3480 4570 4785 MJH 800 MA4 6 9000 7830 on request on request 6 poles 11000 V @ 50 Hz - 1000 rpm 13800 V @ 60 Hz - 1200 rpm IP23 MJH 450 LA6 MJH 450 LB6 6 6 560 620 490 540 - - MJH 500 MA6 MJH 500 MB6 MJH 500 LA6 6 6 6 680 820 950 600 715 830 820 980 1150 720 860 1000 MJH 560 MB6 MJH 560 LA6 6 6 1450 1650 1270 1440 1700 1900 1480 1650 MJH 630 MB6 MJH 630 MC6 6 6 1700 2000 1480 1740 1950 2150 1700 1875 MJH 710 SC6 MJH 710 MA6 MJH 710 MB6 MJH 710 LA6 MJH 710 LC6 6 6 6 6 6 2600 3000 3600 4000 4500 2270 2610 3130 3480 3920 2750 3150 3750 4250 4600 2400 2750 3260 3700 4000 MJH 800 MA6 MJH 800 MB6 MJH 800 LA6 MJH 800 LB6 6 6 6 6 5500 6000 6600 7000 3490 5220 5740 6100 5750 6300 6800 7200 5000 5480 5920 6260 Ratings refer to following conditions: balanced non-deforming load, altitude 1000 m a.s.l., minimum power factor 0,8. All generators are dedicated for 50 Hz or 60 Hz. MJH 900 12 IP23 For available power and speed contact Marelli Motori SELECTION GUIDE - INDUSTRIAL APPLICATION / HIGH VOLTAGE Type Leads 8 poles 11000V / 50Hz Power rating [kVA] Temp. rise / Ambient temp. [°C] Continuous duty 105/40 80/40 ΔT cl. F ΔT cl. B 11000 V @ 50 Hz - 750 rpm 13800V / 60Hz Power rating [kVA] Temp. rise / Ambient temp. [°C] Continuous duty 105/40 80/40 ΔT cl. F ΔT cl. B 13800 V @ 60 Hz - 900 rpm IP23 MJH 500 SA8 MJH 500 MA8 MJH 500 MB8 MJH 500 LA8 6 6 6 6 480 580 680 780 420 500 600 680 570 690 820 930 500 605 715 810 MJH 560 MB8 MJH 560 LA8 6 6 1100 1250 960 1090 1200 1300 1050 1130 MJH 630 MC8 MJH 630 LA8 MJH 630 LB8 6 6 6 1350 1500 1650 1170 1300 1440 1450 1600 1750 1260 1400 1520 MJH 710 SA8 MJH 710 SC8 MJH 710 MA8 MJH 710 MB8 MJH 710 LB8 6 6 6 6 6 1900 2400 3000 3500 3700 1660 2090 2610 3050 3220 2000 2500 3150 3900 4100 1740 2170 2750 3400 3570 MJH 800 MB8 MJH 800 LA8 MJH 800 LB8 6 6 6 4000 4400 5500 3480 3830 4780 4300 4700 5700 3740 4090 4960 10 poles 11000 V @ 50 Hz - 600 rpm 13800 V @ 60 Hz - 720 rpm IP23 MJH 500 SA10 MJH 500 MA10 MJH 500 MB10 MJH 500 LA10 6 6 6 6 340 410 490 550 300 360 430 480 400 490 580 650 350 430 500 570 MJH 630 SA10 MJH 630 MA10 MJH 630 MB10 MJH 630 LA10 MJH 630 LB10 6 6 6 6 6 760 850 1050 1130 1230 660 740 910 980 1070 830 960 1140 1280 1450 725 840 990 1110 1260 MJH 710 SA10 MJH 710 MA10 MJH 710 LA10 MJH 710 LB10 6 6 6 6 1530 1870 2050 2700 1330 1630 1780 2350 1660 2000 2240 2950 1440 1740 1950 2570 MJH 800 SA10 MJH 800 MA10 MJH 800 LA10 6 6 6 3300 3700 4200 2870 3220 3650 3250 3650 4100 2830 3180 3570 Ratings refer to following conditions: balanced non-deforming load, altitude 1000 m a.s.l., minimum power factor 0,8. All generators are dedicated for 50 Hz or 60 Hz. MJH 900 For available power and speed contact Marelli Motori 13 SELECTION GUIDE - MARINE APPLICATION / LOW VOLTAGE Type Leads 4 poles 380V to 690V/ 50Hz Power rating [kVA] Temp. rise / Ambient temp. [°C] Continuous duty 95/50 70/50 ΔT cl. F ΔT cl. B Efficiency 4/4 pf = 0,8 95/50 [%] 380 V to 690 V @ 50 Hz - 1500 rpm 380V to 690V / 60Hz Power rating [kVA] Temp. rise / Ambient temp. [°C] Continuous duty 95/50 70/50 ΔT cl. F ΔT cl. B Efficiency 4/4 pf = 0,8 95/50 [%] Inertia B3 Weight B3 Approx. J [kg m2] Approx. 380 V to 690 V @ 60 Hz - 1800 rpm [kg] IP23 MJBM 160 SA4 MJBM 160 SB4 MJBM 160 SC4 MJBM 160 MA4 MJBM 160 MB4 12 12 12 12 12 14,8 17,4 20,1 24,4 27,9 12,7 14,9 17,3 20,9 23,9 80,9 82,3 83,9 85,5 86,1 17,6 20,5 24,1 28,9 33,5 15,1 17,6 20,7 24,8 28,7 81,4 82,5 83,9 86,0 86,7 0,11 0,12 0,14 0,16 0,17 120 130 140 165 175 MJBM 200 SA4 MJBM 200 SB4 MJBM 200 MA4 MJBM 200 MB4 12 12 12 12 36,5 42,0 54,0 63,0 31,3 36,1 46,4 54,1 86,0 87,2 88,3 89,5 44,5 52,0 64,0 76,0 38,2 44,6 54,9 65,2 86,7 87,3 88,4 89,6 0,28 0,30 0,36 0,43 215 220 260 300 MJBM 225 SA4 MJBM 225 SB4 MJBM 225 MA4 MJBM 225 LA4 12 12 12 12 74,0 80,0 92,0 115 65,0 70,0 85,0 105 89,0 89,4 90,2 91,2 91,0 99,0 112 136 78,0 85,0 96,0 117 89,2 89,5 90,4 91,3 0,63 0,70 0,79 0,92 345 350 390 420 MJBM 250 MA4 MJBM 250 MB4 MJBM 250 LA4 MJBM 250 LB4 12 12 12 12 145 160 190 220 130 140 170 195 91,8 92,1 92,3 92,6 165 190 220 245 145 165 190 215 92,3 92,5 92,7 92,8 1,4 1,7 1,9 2,1 530 590 660 710 MJBM 315 SA4 MJBM 315 SB4 MJBM 315 MA4 MJBM 315 MB4 12 12 12 12 260 305 355 390 230 270 310 340 92,0 92,5 93,1 93,5 310 355 420 460 270 305 365 395 92,6 93,2 93,7 94,2 3,7 4,2 4,8 5,7 830 920 1060 1200 MJBM 355 SA4 MJBM 355 SB4 MJBM 355 MA4 MJBM 355 MB4 12 12 12 6 445 495 595 695 390 435 520 605 93,6 93,9 94,5 94,8 515 590 690 815 445 510 600 700 94,0 94,5 94,9 95,1 8,0 9,3 11,7 13,1 1250 1550 1800 2050 MJBM 400 MA4 MJBM 400 MB4 MJBM 400 LA4 MJBM 400 LB4 MJBM 400 LC4 6 6 6 6 6 810 915 1005 1135 1160 705 800 875 990 1010 94,8 95,2 95,3 95,6 95,8 975 1090 1205 1345 1400 840 940 1035 1155 1220 95,0 95,4 95,6 95,8 96,0 16,3 17,0 19,3 22,5 23,7 2250 2300 2550 2800 3000 MJBM 450 MB4 MJBM 450 LA4 MJBM 450 LB4 6 6 6 1310 1440 1635 1140 1255 1425 95,6 96,6 96,8 1505 1655 1875 1310 1440 1630 96,4 96,8 97,0 29,0 34,0 38,0 3200 3600 4000 MJBM 500 SC4 MJBM 500 MA4 MJBM 500 MB4 MJBM 500 MC4 MJBM 500 LA4 MJBM 500 LB4 6 6 6 6 6 6 1740 1800 1930 2000 2200 2200 1515 1570 1680 1740 1915 1915 95,7 95,7 95,9 96,0 96,1 96,2 2100 2200 2250 2360 2730 2730 1830 1910 1960 2060 2380 2380 95,9 96,0 96,1 96,2 96,3 96,4 46,7 50,5 52,5 54,3 61,5 63,5 4000 4200 4400 4600 5100 5200 MJBM 560 MA4 MJBM 560 LA4 6 6 2450 2950 2135 2570 96,3 96,5 2750 3300 2390 2875 96,5 96,6 83,0 95,0 5200 6300 MJBM 630 SC41 MJBM 630 MB41 MJBM 630 LA41 6 6 6 2700 3050 3500 2350 2655 3045 96,4 96,5 96,6 3000 3300 3700 2610 2875 3220 96,5 96,6 96,7 117 140 158 6700 7500 8000 MJBM 710 SC42 MJBM 710 MB42 6 6 3680 3950 3205 3440 96,3 96,5 4050 4350 3520 3780 96,4 96,6 MJBM 800 on request on request on request on request For available power and speed contact Marelli Motori : 690 V recommended. 2 : 690 V only. For different voltage please contact MarelliMotori. These generators are dedicated for 50 Hz or 60 Hz. For available voltage and performance when operating at different frequency contact MarelliMotori. Ratings refer to following conditions: balanced non-deforming load, minimum power factor 0,8. For pitch winding details contact Marelli Motori. 1 MJBM 900 14 For available power and speed contact Marelli Motori SELECTION GUIDE - MARINE APPLICATION / LOW VOLTAGE Type Leads 6 poles 380V to 690V/ 50Hz Power rating [kVA] Temp. rise / Ambient temp. [°C] Continous duty 95/50 70/50 ΔT cl. F ΔT cl. B Efficiency 4/4 pf = 0,8 95/50 [%] 380 V to 690 V @ 50 Hz - 1000 rpm 380V to 690V / 60Hz Power rating [kVA] Temp. rise / Ambient temp. [°C] Continous duty 95/50 70/50 ΔT cl. F ΔT cl. B Efficiency 4/4 pf = 0,8 95/50 [%] Inertia B3 Weight B3 Approx. J [kg m˛] Approx. 380 V to 690 V @ 60 Hz - 1200 rpm [kg] IP23 MJBM 400 SA6 MJBM 400 SB6 MJBM 400 SC6 MJBM 400 MA6 MJBM 400 MB6 MJBM 400 LA6 MJBM 400 LB6 6 6 6 6 6 6 6 350 390 435 540 610 700 845 305 340 380 470 535 610 740 92,7 93,0 93,7 94,1 94,3 94,6 94,8 415 465 515 640 725 825 1000 360 400 445 550 625 710 860 92,9 93,9 93,9 94,3 94,5 94,8 95,0 11,8 14,1 16,8 17,9 19,4 20,9 24,2 1450 1600 1800 2000 2260 2530 2750 MJBM 450 MB6 MJBM 450 LA6 MJBM 450 LB6 6 6 6 890 1040 1180 775 905 1030 94,6 95,2 95,4 1050 1230 1400 915 1075 1220 95,1 95,7 95,9 49,9 55,0 61,4 3200 3600 3900 MJBM 500 SC6 MJBM 500 MA6 MJBM 500 MB6 MJBM 500 MC6 MJBM 500 LA6 6 6 6 6 6 1200 1300 1400 1450 1680 1045 1135 1220 1265 1465 95,0 95,2 95,2 95,3 95,4 1450 1600 1700 1800 2000 1265 1395 1480 1570 1740 95,5 95,1 95,2 95,2 95,4 64,7 64,7 73,6 80,2 88,9 3800 4150 4600 4900 5100 MJBM 560 MA6 MJBM 560 LA6 6 6 1800 2000 1570 1740 96,0 96,2 2050 2400 1785 2090 96,0 96,2 115 135 5400 6500 MJBM 630 SB6 MJBM 630 SC6 MJBM 630 MA6 MJBM 630 MB6 MJBM 630 LA6 MJBM 630 LB6 6 6 6 6 6 6 2100 2200 2400 2500 2700 2900 1830 1915 2090 2175 2350 2525 95,6 95,7 95,7 95,8 96,5 96,6 2500 2600 2900 3000 3200 3400 2175 2265 2525 2610 2785 2960 96,2 96,3 96,3 96,4 96,8 96,8 170 180 190 200 230 245 7000 7200 7900 8000 8100 8300 MJBM 710 SC61 MJBM 710 MA62 MJBM 710 LA62 MJBM 710 LB62 6 6 6 6 3200 3750 3900 4200 2785 3265 3395 3655 96,0 96,7 96,8 96,8 3600 4000 4200 4500 3135 3480 3655 3915 96,3 96,7 96,8 96,9 on request on request on request on request on request on request on request on request MJBM 800 __62 6 5800 5000 97,1 6200 5400 97,1 on request on request 13,5 16,2 19,1 20,6 22,4 24,1 25,4 55,1 74,2 82,2 95,0 130 155 170 195 240 270 on request on request on request on request on request 1450 1600 1800 2000 2260 2530 2750 3200 3800 4700 5400 5700 6700 7100 8000 9200 9400 on request on request on request on request on request 63,8 81,6 89,7 106 230 310 on request on request on request on request on request on request 3300 3900 4800 5600 8700 9700 on request on request on request on request on request on request 8 poles MJBM 400 SA8 MJBM 400 SB8 MJBM 400 SC8 MJBM 400 MA8 MJBM 400 MB8 MJBM 400 LA8 MJBM 400 LB8 MJBM 500 SA8 MJBM 500 SC8 MJBM 500 MB8 MJBM 500 LA8 MJBM 560 MA8 MJBM 560 LA8 MJBM 630 SC8 MJBM 630 MB8 MJBM 630 LA8 MJBM 630 LB8 MJBM 710 SC81 MJBM 710 MA81 MJBM 710 MD81 MJBM 710 LB82 MJBM 800 __82 380 V to 690 V @ 50 Hz - 750 rpm 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 poles MJBM 500 SA10 MJBM 500 SC10 MJBM 500 MB10 MJBM 500 LA10 MJBM 630 MB10 MJBM 630 LB10 MJBM 710 SC101 MJBM 710 MA101 MJBM 710 MB101 MJBM 710 LB101 MJBM 710 LC102 MJBM 800 __102 210 270 315 375 450 520 650 830 1000 1100 1300 1500 1800 1750 2200 2450 2600 2400 2850 3200 3600 5400 185 235 275 330 395 455 570 725 870 960 1135 1305 1570 1525 1915 2135 2265 2090 2480 2785 3135 4700 91,6 92,1 92,4 92,6 93,1 93,3 93,6 94,6 95,1 95,2 95,3 95,6 95,9 95,4 95,9 96,1 96,2 96,4 96,5 96,6 96,7 96,9 380 V to 690 V @ 50 Hz - 600 rpm 6 6 6 6 6 6 6 6 6 6 6 6 520 650 760 840 1400 1800 2150 2400 2850 3400 3850 4800 455 570 665 735 1220 1570 1875 2090 2480 2960 3350 4100 94,0 94,3 94,8 95,1 95,6 95,8 95,9 95,9 96,4 96,4 96,5 96,6 380 V to 690 V @ 60 Hz - 900 rpm 250 330 370 450 520 620 760 950 1150 1300 1500 1900 2150 2000 2500 2800 3125 2750 3300 3800 4200 5700 220 290 325 395 455 540 665 830 1005 1135 1305 1655 1875 1740 2175 2440 2720 2395 2875 3310 3655 5000 91,9 92,4 92,7 92,9 93,4 93,6 93,9 95,0 95,4 95,5 95,8 95,6 95,9 96,2 96,5 96,6 96,7 96,7 96,8 96,9 97,1 97,1 IP23 380 V to 690 V @ 60 Hz -720 rpm 645 810 910 1050 1600 2200 2500 2800 3300 3900 4200 5200 565 705 795 915 1395 1915 2175 2440 2875 3395 3655 4500 94,5 94,7 95,2 95,5 95,9 96,2 96,3 96,3 96,7 96,7 96,8 96,9 IP23 : 690 V recommended. These generators are dedicated for 50 Hz or 60 Hz. For available voltage and performance when operating at different frequency contact MarelliMotori. : 690 V only. For different voltage please contact MarelliMotori. These generators are dedicated for 50 Hz or 60 Hz. For available voltage and performance when operating at different frequency contact MarelliMotori. Ratings refer to following conditions: balanced non-deforming load, minimum power factor 0,8. For pitch winding details contact Marelli Motori. 1 2 15 SELECTION GUIDE - MARINE APPLICATION / LOW VOLTAGE / WITH EXCHANGER Type Leads 4 poles 380V to 690V / 50Hz Power rating [kVA] Temp. rise / Ambient temp. [°C] Water inlet temperature 36°C Continuous duty - Air to water exchanger 95/50 70/50 ΔT cl. F ΔT cl. B 380 V to 690 V @ 50 Hz - 1500 rpm 380V to 690V / 60Hz Power rating [kVA] Temp. rise / Ambient temp. [°C] Water inlet temperature 36°C Continuous duty - Air to water exchanger 95/50 70/50 ΔT cl. F ΔT cl. B 380 V to 690 V @ 60Hz - 1800 rpm MJRM 250 MA4 MJRM 250 MB4 MJRM 250 LA4 MJRM 250 LB4 12 12 12 12 130 145 170 200 115 130 150 175 150 170 200 220 135 150 175 200 MJRM 315 SA4 MJRM 315 SB4 MJRM 315 MA4 MJRM 315 MB4 12 12 12 12 230 270 320 350 210 230 280 300 280 320 380 410 245 280 330 360 MJRM 355 SA4 MJRM 355 SB4 MJRM 355 MA4 MJRM 355 MB4 12 12 12 6 400 450 540 630 350 400 470 550 460 530 620 730 400 460 540 640 MJRM 400 MB4 MJRM 400 LA4 MJRM 400 LB4 6 6 6 820 970 1020 715 850 890 1040 1120 1260 900 975 1100 MJRM 450 MB4 MJRM 450 LA4 MJRM 450 LB4 6 6 6 1210 1325 1510 1050 1150 1310 1700 1900 2025 1480 1660 1760 MJRM 500 SC4 MJRM 500 MA4 MJRM 500 MB4 MJRM 500 MC4 MJRM 500 LA4 MJRM 500 LB4 6 6 6 6 6 6 1700 1740 1900 2100 2200 2200 1480 1520 1660 1830 1920 1920 2110 2260 2450 2550 2800 2800 1840 1970 2135 2220 2440 2440 MJRM 560 MA4 MJRM 560 LA4 6 6 2350 2650 2050 2310 2850 3060 2480 2660 MJRM 630 SA41 MJRM 630 MA41 MJRM 630 LA41 6 6 6 2700 3000 3500 2350 2610 3050 3000 3300 3700 2610 2870 3220 MJRM 710 SC42 MJRM 710 MB42 6 6 3600 3800 3140 3310 4000 4300 3480 3750 6 poles MJRM 400 SA6 MJRM 400 SB6 MJRM 400 SC6 MJRM 400 MA6 MJRM 400 MB6 MJRM 400 LA6 MJRM 400 LB6 MJRM 450 MB6 MJRM 450 LA6 MJRM 450 LB6 MJRM 500 SC6 MJRM 500 MA6 MJRM 500 MB6 MJRM 500 MC6 MJRM 500 LA6 MJRM 560 MA6 MJRM 560 LA6 MJRM 630 SB6 MJRM 630 SC6 MJRM 630 MA6 MJRM 630 MB6 MJRM 630 LA6 MJRM 630 LB6 MJRM 710 SC61 MJRM 710 MA62 MJRM 710 LA62 MJRM 710 LB62 MJRM 800 __62 380 V to 690 V @ 50 Hz - 1000 rpm 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 320 350 390 490 550 630 760 800 940 1060 1200 1300 1400 1450 1680 1800 2000 2100 2200 2400 2500 2700 2900 3200 3750 3900 4200 5800 280 300 340 430 480 550 660 700 820 930 1050 1130 1220 1270 1470 1570 1740 1830 1920 2100 2180 2350 2530 2780 3260 3400 3650 5000 380 V to 690 V @ 60 Hz - 1200 rpm 370 420 460 580 650 740 900 950 1110 1260 1450 1600 1700 1800 2000 2050 2400 2500 2600 2900 3000 3200 3400 3600 4000 4200 4500 6200 325 370 405 505 570 640 780 830 970 1100 1260 1400 1480 1570 1740 1790 2090 2175 2260 2520 2610 2780 2960 3130 3480 3650 3920 5400 : 690 V recommended. : 690 V only. For different voltage please contact MarelliMotori. These generators are dedicated for 50 Hz or 60 Hz. For available voltage and performance when operating at different frequency contact MarelliMotori. Ratings refer to following conditions: balanced non-deforming load, minimum power factor 0,8. For pitch winding details contact Marelli Motori. For MJRM generator series please consider additional derating factor:38 °C water inlet temperature: 0,99; 40 °C water inlet temperature: 0,98. 1 2 16 SELECTION GUIDE - MARINE APPLICATION / LOW VOLTAGE / WITH EXCHANGER Type Leads 8 poles MJRM 400 SA8 MJRM 400 SB8 MJRM 400 SC8 MJRM 400 MA8 MJRM 400 MB8 MJRM 400 LA8 MJRM 400 LB8 MJRM 500 SA8 MJRM 500 SC8 MJRM 500 MB8 MJRM 500 LA8 MJRM 560 MA8 MJRM 560 LA8 MJRM 630 SC8 MJRM 630 MB8 MJRM 630 LA8 MJRM 630 LB8 MJRM 710 SC81 MJRM 710 MA81 MJRM 710 MD81 MJRM 710 LB82 MJRM 800 __82 380 V to 690 V @ 50 Hz - 750 rpm 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 poles MJRM 500 SA10 MJRM 500 SC10 MJRM 500 MB10 MJRM 500 LA10 MJRM 630 MB10 MJRM 630 LB10 MJRM 710 SC101 MJRM 710 MA101 MJRM 710 MB101 MJRM 710 LB101 MJRM 710 LC102 MJRM 800 __102 380V to 690V / 50Hz Power rating [kVA] Temp. rise / Ambient temp. [°C] Water inlet temperature 36°C Continuous duty - Air to water exchanger 95/50 70/50 ΔT cl. F ΔT cl. B 190 245 285 340 400 470 590 830 1000 1100 1300 1500 1800 1750 2200 2450 2600 2400 2850 3200 3600 5400 380 V to 690 V @ 60 Hz - 900 rpm 170 215 250 300 350 410 515 725 870 960 1130 1300 1570 1530 1920 2140 2260 2100 2480 2780 3130 4700 380 V to 690 V @ 50 Hz - 600 rpm 6 6 6 6 6 6 6 6 6 6 6 6 470 590 680 760 1400 1800 2150 2400 2850 3400 3850 4800 380V to 690V / 50Hz Power rating [kVA] Temp. rise / Ambient temp. [°C] Water inlet temperature 36°C Continuous duty - Air to water exchanger 95/50 70/50 ΔT cl. F ΔT cl. B 230 300 330 400 470 560 690 950 1150 1300 1500 1900 2150 2000 2500 2800 3125 2750 3300 3800 4200 5700 200 260 290 350 410 490 600 830 1000 1135 1300 1660 1875 1740 2175 2440 2720 2400 2870 3300 3650 5000 380 V to 690 V @ 60 Hz - 720 rpm 410 515 600 660 1220 1570 1875 2100 2480 2960 3350 4100 580 730 820 950 1600 2200 2500 2800 3300 3900 4200 5200 500 640 710 830 1400 1920 2180 2440 2880 3400 3660 4500 : 690 V recommended. These generators are dedicated for 50 Hz or 60 Hz. For available voltage and performance when operating at different frequency contact MarelliMotori. Ratings refer to following conditions: balanced non-deforming load, minimum power factor 0,8. For pitch winding details contact Marelli Motori. For MJRM generator series please consider additional derating factor:38 °C water inlet temperature: 0,99; 40 °C water inlet temperature: 0,98. 1 MJRM 900 For available power and speed contact Marelli Motori 17 DRAWINGS B3 - DOUBLE BEARING 1 B2 - SINGLE BEARING B20 - DOUBLE BEARING 1 1 1 (1) Dimensions for optional PMG 18 DIMENSIONS [mm] Dimension MJB 160 COMPACT SB SC MA MB 160 257 300 328 547 592 451 - SA H HS AB AF L D max L1 D1 Dimension SA H HS AB AF L D max L1 D1 Dimension MJB 225 SB MA 225 412 446 460 790 745 492 805 850 492 905 MB SA 1366 1528 H H1 HS AB AB1 AF L D max L1 D1 MJB 500 MA 500 SC 1920 970 2170 970 Dimension SA MJB 710 MA 710 SC 672 685 780 432 LB MJB 315 SB MA 315 555 600 632 SA 998 945 MB 1105 711 1050 1052 1212 624 MJB 400 MA MB 400 Dimensions available on request 675 800 Dimensions available on request 800 1200 1400 883 1370 1570 780 SB LA LB MB MJB 450 LA 450 MB LA 800 MJB 800 MB LA 800 MA LB 740 900 1600 1517 1777 1770 1807 1987 LA 900 1970 710 354 MJB 250 MB LA 250 468 505 502 MB 552 MJB 560 MJB 630 MA LA SA SB MA MB 560 630 Dimensions available on request 870 948 1100 1280 Dimensions available on request 900 2020 2035 2135 Dimensions available on request 1070 2270 2305 2405 2160 2360 1070 1200 MB 867 1000 1720 MJB 200 SB MA 200 323 405 410 SA 615 532 690 SA MB 632 627 918 711 Dimension MA 552 700 1298 MJB 160 SC 160 257 300 328 451 858 620 670 1136 SB 587 MA 845 MJB 355 SB MA 355 SA H H1 HS AB AB1 AF L D max L1 D1 LA SA H H1 Dimensions available on request HS 1170 1500 AB 1500 2100 AB1 Dimensions available on request AF L Dimensions available on request Dimension available on request D max L1 2450 2650 2900 3100 3300 D1 1413 D (max) dimension shown refers to biggest adaptor/coupling LA 2460 LB COUPLING Adaptor 5 160 4 200 3 4 3 2 1 4 225 3 2 3 250 2 1 3 Sizes [mm] 315 2 1 1/2 0 1 355 1/2 0 1 400 1/2 0 00 0 450 00 0 500 00 560 00 6 1/2 7 1/2 8 10 11 1/2 14 16 18 21 Available Most common 19 HEADQUARTERS ITALIAN BRANCHES Marelli Motori S.p.A. Milan Via Sabbionara, 1 36071 Arzignano (VI) - Italy (T) +39 0444 479.711 (F) +39 0444 479.888 www.marellimotori.com [email protected] Via Cesare Cantù, 29 20092 Cinisello Balsamo (MI) - Italy (T) +39 02 660.131.66 (F) +39 02 660.134.83 [email protected] Florence Via Panciatichi, 37/2 50127 Firenze - Italy (T) +39 055 431.838 (F) +39 055 433.351 [email protected] MARELLI MOTORI OVERSEAS COMPANIES GREAT BRITAIN CENTRAL EUROPE USA Marelli UK, Ltd Marelli Central Europe Gmbh Marelli USA, Inc Meadow Lane Loughborough Leicester LE111NB UK (T) +44 1509 615 518 (F) +44 1509 615 514 [email protected] Heilswannenweg 50 31008 Elze Germany (T) +49 5068 462 400 (F) +49 5068 462 409 [email protected] 1620 Danville Road PO Box 410 Harrodsburg, KY 40330 USA (T) +1 859 734 2588 (F) +1 859 7340629 [email protected] ASIA PACIFIC SOUTH AFRICA SPAIN Marelli Asia Pacific Sdn Bhd Marelli Electrical Machines South Africa (Pty) Ltd Representative Office Lot PT 5038-5041 Jalan Teluk Datuk 28/40 Off Persiaran Sepang, Seksyen 28, 40400 Shah Alam, Selangor D.E. Malaysia (T) +60 3 5192 7213 (F) +60 3 5192 6293 [email protected] Unit 4, 55 Activia Rd - Activia Park Elandsfontein, 1406 Gauteng Republic of South Africa (T) +27 11 822 5566 (F) +27 11 828 8089 [email protected] Barcelona Spain (T) +34 6644641219 [email protected] SIN.CT.024.13 GB MARELLI MOTORI reserves the right to change the design, technical specification and dimensions in order to update or improve its products, without prior notice