www.LEUTRON.DE

Transcription

www.LEUTRON.DE
www.LEUTRON.DE
Lightning and surge
protection
We reserve the right to make alterations in style and form in line with technical
development. The illustrations are non-binding. We do not assume liability for mistakes
or printing errors.
All orders will only be accepted in General Terms and Conditions of Sale of the
Company of Leutron GmbH.
© Leutron GmbH, 1st. Edition 04/2012. P/N 98 01 44
Contents overview
n Surge protection for power supply systems.. . . . . . . . . . . . . 2
Crossreferences. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
SPD type 2 for AC power supplies (leakage-current free). . . . . . . . . . .
SPD type 3 for AC power supplies. . . . . . . . . . . . . . . . . . . . . . . . . .
Selection guide.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
AC power supply.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
DC power supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Lightning current arrester type 1 for DC power supplies. . . . . . . . . . . .
Lightning current arrester type 1 for AC power supplies.. . . . . . . . . . . 11
Combined arrester type 1 + 2 for AC power supplies. . . . . . . . . . . . . 19
SPD type 2 for DC power supplies. . . . . . . . . . . . . . . . . . . . . . . . . .
SPD type 2 for AC power supplies. . . . . . . . . . . . . . . . . . . . . . . . . 27Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
41
49
58
60
62
65
n Surge protection for measuring systems and automatic control devices . . . . 68
Crossreferences. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Pluggable SPD for high frequency MCR applications. . . . . . . . . . . . . . 97
One-piece SPD for MCR applications. . . . . . . . . . . . . . . . . . . . . . . 100
Selection guide.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Pluggable SPD for MCR applications. . . . . . . . . . . . . . . . . . . . . . . . 79
One-piece SPD with high discharge cappability for MCR applications. . 101
One-piece SPD with high discharge cappability and low protection level
Pluggable SPD with high discharge cappability for MCR applications. . . 79
Pluggable SPD with high discharge cappability and low protection level
for MCR applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
for MCR applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
One-piece SPD with low protection level for MCR applications. . . . . . . 113
n Surge protection for information technology
and telecommunication installations. . . . . . . . . . . . . . . . . . . .
SPD for communication networks. . . . . . . . . . . . . . . . . . . . . . . . .
SPD for telecommunication networks. . . . . . . . . . . . . . . . . . . . . .
Surge protective devices for LSA mounting.. . . . . . . . . . . . . . . . . .
120
124
130
133
n Surge protection for transmitting and receiving systems..
SPD for SAT/TV/Radio applications. . . . . . . . . . . . . . . . . . . . . . . .
SPD with BNC connector. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SPD with SMA connector. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SPD with N connector. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
154
158
159
161
162
SPD according to test category D1+C2.. . . . . . . . . . . . . . . . . . . . . 135
SPD according to test category C2+C1.. . . . . . . . . . . . . . . . . . . . . 138
Lambda/4 stubline SPD with N connector. . . . . . . . . . . . . . . . . . . .
SPD with DIN 7/16 connector. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Lambda/4 stubline SPD with DIN 7/16 connector. . . . . . . . . . . . . . .
SPD with FME connector. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
163
165
167
170
n EMC filter with integrated surge protection. . . . . . . . . . . . 172
Line filter up to 200 A. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
MCR technology with integrated low-pass filter. . . . . . . . . . . . . . . . 181
n Monitoring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Universal function tester for GDT, MOV and diodes, mixed circuits. . . .
Function tester for GDT and GDT based spark-gaps. . . . . . . . . . . . .
Function tester for MOV and overvoltage protection diodes.. . . . . . . .
192
196
197
198
Portable test equipment for GDT in LSA magazines.. . . . . . . . . . . . . 199
Pulse counter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200
n Rare-gas-filled insulation spark gaps. . . . . . . . . . . . . . . . 202
Flexible mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206
ATEX-certificated for explosion hazardous zones EX. . . . . . . . . . . . . 211
DIN rail mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212
n Protective devices for AC arresting. . . . . . . . . . . . . . . . . . 214
AC-current diverter up to AC 80 A with lightning protection. . . . . . . . 218
Standards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
Numeric product register. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 228
Dimension drawings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220Alphabetical product register. . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
Technical terms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 224
General Terms and Conditions of Sale. . . . . . . . . . . . . . . . . . . . . . 234
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection with a new design
The multi-pole combined modular arresters for protection against lightning
strikes and transient surge voltages now have an even more attractive
design. In addition to their outstanding technical properties, they are
pluggable and provide a clearly readable function control indication and
status display. The variable installation position – the base part can be
plugged in two directions – enables a flexible and cost-saving wiring.
Easy setup, secure operation:
2
nNew: Easy changing of the protection module thanks to a twopart design with a vibration-resistant locking
nRemote signalling using only one signalling contact – even with
4-pole devices
nRobust and maintenance-free due to the hermetically closed
rare-gas-filled isolating spark gap without internal or external
trigger electronics
Surge Protection
for Power Supply Systems
The new design developed together with product
design specialists allows for an easier handling.
Surge Protection
for Power Supply Systems
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
3
Two-piece pluggable surge protective
devices for AC power supply systems
New product line »Leutron Power«: Powerful and standardized
pluggable modules for almost every power supply system available.
nOptimized follow-on current extinguishing capability
Mechanical
status indicator:
State of the surge
protective device is
optically indicated
Locking
function: Release
of the latches by
ergonomically shaped grip
lugs
Protection against
mismating: Optimized
installation due to
arresters with coding
Remote signalling:
Combined remote
contact (changeover
contact) optionally
available
Turnable
plug-in modules:
The plug-in modules
can be twisted on the basic
module, thus, guaranteeing
always good readability
even with variable
wiring
4
Surge Protection
for Power Supply Systems
Two-piece pluggable surge protective
devices for DC power supply systems
Mechanical
function indicator:
State of the surge
protective device is
indicated optically
Arrester elements
available for 600 V and
1,000 V applications
Safety for
photovoltaic installations: Disconnection
function in case of
overloads optimized
for photovoltaic
installations
Remote signalling:
Combined remote
contact (changeover
contact) optionally
available
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
5
Cross reference list to select the appropriate products
This cross reference helps to find the new, appropriate
products on the basis of the previous product names.
Previous product nameNew product name
6
37 39 12
PP B TT 50/100/FM
96 02 07
CT-T1/3+1-350-FM
37 39 22
PP BC TT 25/100/FM
96 00 01
CT-T1+2/3+1-350-FM
37 39 32
PP BCD TT 25/100/FM
96 00 01
CT-T1+2/3+1-350-FM
37 39 42
PP B TNS 50/100/FM
96 02 07
CT-T1/3+1-350-FM
37 39 52
PP BC TNS 25/100/FM
96 00 01
CT-T1+2/3+1-350-FM
37 39 62
PP BCD TNS 25/100/FM
96 00 01
CT-T1+2/3+1-350-FM
37 39 72
PP B TNC 50/100/FM
96 02 09
CT-T1/3+0-350-FM
37 39 82
PP BC TNC 26/75/FM
96 00 03
CT-T1+2/3+0-350-FM
37 39 92
PP BCD TNC 25/75/FM
96 00 03
CT-T1+2/3+0-350-FM
37 41 15
PP B TNC 50/100/FM-350
96 02 09
CT-T1/3+0-350-FM
37 41 25
PP B TNS 50/100/FM-350
96 02 07
CT-T1/3+1-350-FM
37 41 35
PP B TT 50/100/FM-350
96 02 07
CT-T1/3+1-350-FM
38 05 24
EP D TNC 275
96 02 04
CT-T3/Y3-275
38 05 25
EP D TNC 275/FM
96 02 05
CT-T3/Y3-275-FM
38 05 30
EP D TNS 275
96 02 04
CT-T3/Y3-275
38 05 31
EP D TNS 275/FM
96 02 05
CT-T3/Y3-275-FM
38 05 35
EP D TT 275
96 02 04
CT-T3/Y3-275
38 05 36
EP D TT 275/FM
96 02 05
CT-T3/Y3-275-FM
38 05 38
EP D TT1+1 275
96 02 02
CT-T3/Y1-275
38 05 39
EP D TT1+1 275/FM
96 02 03
CT-T3/Y1-275-FM
38 05 50
EP D TN 24V/16A
96 01 86
CT-T3/Y1-24
38 05 51
EP D TN 24V/16A/FM
96 01 87
CT-T3/Y1-24-FM
38 05 53
EP D TN 48V/16A
96 01 90
CT-T3/Y1-48
38 05 54
EP D TN 48V/16A/FM
96 01 91
CT-T3/Y1-48-FM
38 05 56
EP D TN 60V/16A
96 01 94
CT-T3/Y1-60
38 05 57
EP D TN 60V/16A/FM
96 01 95
CT-T3/Y1-60-FM
38 05 59
EP D TN 120V/16A
96 01 98
CT-T3/Y1-120
38 05 60
EP D TN 120V/16A/FM
96 01 99
CT-T3/Y1-120-FM
38 05 62
EP D TN 230V/16A
96 02 02
CT-T3/Y1-275
38 05 63
EP D TN 230V/16A/FM
96 02 03
CT-T3/Y1-275-FM
38 09 28
EP C TN 275A
96 01 32
CT-T2/2+0-275-VA
38 09 29
EP C S TN 275A/FM
96 01 33
CT-T2/2+0-275-VA-FM
38 09 30
EP C S TNC 275A
96 01 28
CT-T2/3+0-275-VA
38 09 31
EP C S TNC 275A/FM
96 01 29
CT-T2/3+0-275-VA-FM
38 09 32
EP C S TNS 275A
96 01 26
CT-T2/3+1-275-VA
38 09 33
EP C S TNS 275A/FM
96 01 27
CT-T2/3+1-275-VA-FM
38 09 50
EP C S TN 330A
96 01 46
CT-T2/2+0-350-VA
38 09 51
EP C S TN 330A/FM
96 01 47
CT-T2/2+0-350-VA-FM
38 09 52
EP C S TNC 330A
96 01 42
CT-T2/3+0-350-VA
38 09 53
EP C S TNC 330A/FM
96 01 43
CT-T2/3+0-350-VA-FM
38 09 54
EP C S TNS 330A
96 01 40
CT-T2/3+1-350-VA
38 09 55
EP C S TNS 330A/FM
96 01 41
CT-T2/3+1-350-VA-FM
38 10 24
EP C S TT1+1 275
96 00 50
CT-T2/1+1-275
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Cross reference list
power supply systems
Previous product nameNew product name
Previous product nameNew product name
38 10 25
EP C S TT1+1 275/FM
96 00 51
CT-T2/1+1-275-FM
38 12 70
EP C S T 275
96 01 36
CT-T2/1+0-275-VA
38 10 30
EP C S TNC 275
96 00 44
CT-T2/3+0-275
38 12 75
EP C S T 2757/FM
96 01 37
CT-T2/1+0-275-VA-FM
38 10 35
EP C S TNC 275/FM
96 00 45
CT-T2/3+0-275-FM
38 13 00
EP C S T 440
96 00 80
CT-T2/1+0-440
38 10 40
EP C S TT 275
96 00 42
CT-T2/3+1-275
38 13 05
EP C S T 440/FM
96 00 81
CT-T2/1+0-440-FM
38 10 45
EP C S TT 275/FM
96 00 43
CT-T2/3+1-275-FM
38 13 10
EP C S T 550
96 00 94
CT-T2/1+0-550
38 10 50
EP C S TNS 275
96 00 42
CT-T2/3+1-275
38 13 15
EP C S T 550/FM
96 00 95
CT-T2/1+0-550-FM
38 10 55
EP C S TNS 275/FM
96 00 43
CT-T2/3+1-275-FM
38 20 22
EnerPro 220Tr/20kA
96 01 36
CT-T2/1+0-275-VA
38 11 31
PP B TT1+1 50/100/FM
96 02 15
CT-T1/1+1-350-FM
38 20 23
EnerPro 220Tr/20kA/Pk
96 01 37
CT-T2/1+0-275-VA-FM
38 11 33
PP BC TT1+1 25/100/FM
96 00 09
CT-T1+2/1+1-350-FM
38 50 10
PP BCD TNC 25/75/FM-350
96 00 03
CT-T1+2/3+0-350-FM
38 11 35
PP BCD TT1+1 25/100/FM
96 00 09
CT-T1+2/1+1-350-FM
38 50 30
PP BCD TNS 25/100/FM-350
96 00 01
CT-T1+2/3+1-350-FM
38 11 41
IP B TNC 60/100/FM
96 02 09
CT-T1/3+0-350-FM
38 50 50
PP BCD TT 25/100/FM-350
96 00 01
CT-T1+2/3+1-350-FM
38 11 71
IPK BC TNC 275/FM
96 00 03
CT-T1+2/3+0-350-FM
38 50 70
PP BCD TN 25/50/FM-350
96 00 07
CT-T1+2/2+0-350-FM
38 11 73
IPK BC TNS 275/FM
96 00 01
CT-T1+2/3+1-350-FM
38 50 90
PP BCD TT1+1 25/100/FM-350
96 00 09
CT-T1+2/1+1-350-FM
38 11 75
IPK BC TT 275/FM
96 00 01
CT-T1+2/3+1-350-FM
38 51 30
PP BC TNC 25/75/FM-350
96 00 03
CT-T1+2/3+0-350-FM
38 11 76
EP C TNC 275
96 01 28
CT-T2/3+0-275-VA
38 51 50
PP BC TNS 25/100/FM-350
96 00 01
CT-T1+2/3+1-350-FM
38 11 77
EP C TNC 275/FM
96 01 29
CT-T2/3+0-275-VA-FM
38 51 70
PP BC TT 25/100/FM-350
96 00 01
CT-T1+2/3+1-350-FM
38 11 78
EP C TNS 275
96 01 26
CT-T2/3+1-275-VA
38 51 90
PP BC TN 25/50/FM-350
96 00 07
CT-T1+2/2+0-350-FM
38 11 79
EP C TNS 275/FM
96 01 27
CT-T2/3+1-275-VA-FM
38 52 10
PP BC TT1+1 25/100/FM-350
96 00 09
CT-T1+2/1+1-350-FM
38 11 80
EP C TT 275
96 01 26
CT-T2/3+1-275-VA
38 53 10
IP BC TNC 25/75/FM-350
96 00 03
CT-T1+2/3+0-350-FM
38 11 81
EP C TT 275/FM
96 01 27
CT-T2/3+1-275-VA-FM
38 53 50
IP BC TNS 25/100/FM-350
96 00 01
CT-T1+2/3+1-350-FM
38 11 82
EP C TT1+1 275
96 01 34
CT-T2/1+1-275-VA
38 53 90
IP BC TT 25/100/FM-350
96 00 01
CT-T1+2/3+1-350-FM
38 11 83
EP C TT1+1 275/FM
96 01 35
CT-T2/1+1-275-VA-FM
38 54 30
IP BC TN 25/50/FM-350
96 00 07
CT-T1+2/2+0-350-FM
38 11 88
EP C TT1+1 350
96 01 48
CT-T2/1+1-350-VA
38 54 70
IP BC TT1+1 25/100/FM-350
96 00 09
CT-T1+2/1+1-350-FM
38 11 91
EP C TT1+1 350/FM
96 01 49
CT-T2/1+1-350-VA-FM
38 54 90
IPK BC TNC 350/FM
96 00 03
CT-T1+2/3+0-350-FM
38 12 11
PP B TN 50/100/FM
96 02 13
CT-T1/2+0-350-FM
38 55 10
IPK BC TNS 350/FM
96 00 01
CT-T1+2/3+1-350-FM
38 12 13
PP BC TN 25/50/FM
96 00 07
CT-T1+2/2+0-350-FM
38 55 30
IPK BC TT 350/FM
96 00 01
CT-T1+2/3+1-350-FM
38 12 15
PP BCD TN 25/50/FM
96 00 07
CT-T1+2/2+0-350-FM
38 55 40
EP C TN 350
96 01 46
CT-T2/2+0-350-VA
38 12 17
IP B TNC 25/75/FM
96 02 09
CT-T1/3+0-350-FM
38 55 50
EP C TN 350/FM
96 01 47
CT-T2/2+0-350-VA-FM
38 12 19
IP BC TNC 25/75/FM
96 00 03
CT-T1+2/3+0-350-FM
38 55 60
EP C TNC 350
96 01 42
CT-T2/3+0-350-VA
38 12 21
IP B TNS 25/100/FM
96 02 07
CT-T1/3+1-350-FM
38 55 70
EP C TNC 350/FM
96 01 43
CT-T2/3+0-350-VA-FM
38 12 23
IP BC TNS 25/100/FM
96 00 01
CT-T1+2/3+1-350-FM
38 55 80
EP C TNS 350
96 01 40
CT-T2/3+1-350-VA
38 12 25
IP B TT 25/100/FM
96 02 07
CT-T1/3+1-350-FM
38 55 90
EP C TNS 350/FM
96 01 41
CT-T2/3+1-350-VA-FM
38 12 27
IP BC TT 25/100/FM
96 00 01
CT-T1+2/3+1-350-FM
38 56 00
EP C TT 350
96 01 40
CT-T2/3+1-350-VA
38 12 29
IP B TT1+1 25/50/FM
96 02 15
CT-T1/1+1-350-FM
38 56 10
EP C TT 350/FM
96 01 41
CT-T2/3+1-350-VA-FM
38 12 31
IP BC TT1+1 25/100/FM
96 00 09
CT-T1+2/1+1-350-FM
38 56 40
EP C S TNC 350
96 00 58
CT-T2/3+0-350
38 12 37
IP B TN 25/50/FM
96 02 13
CT-T1/2+0-350-FM
38 56 50
EP C S TNC 350/FM
96 00 59
CT-T2/3+0-350-FM
38 12 39
IP BC TN 25/50/TN
96 00 07
CT-T1+2/2+0-350-FM
38 56 60
EP C S TNS 350
96 00 56
CT-T2/3+1-350
38 12 40
EP C S TN 275
96 00 48
CT-T2/2+0-275
38 56 70
EP C S TNS 350/FM
96 00 57
CT-T2/3+1-350-FM
38 12 41
EP C S TN 275/FM
96 00 49
CT-T2/2+0-275-FM
38 57 00
EP C S TT 350
96 00 56
CT-T2/3+1-350
38 12 47
EP C TN 275
96 01 32
CT-T2/2+0-275-VA
38 57 10
EP C S TT 350/FM
96 00 57
CT-T2/3+1-350-FM
38 12 48
EP C TN 275/FM
96 01 33
CT-T2/2+0-275-VA-FM
38 57 20
EP C S T 350
96 01 50
CT-T2/1+0-350-VA
38 12 54
EP D TN 275
96 02 02
CT-T3/Y1-275
38 57 30
EP C S T 350/FM
96 00 67
CT-T2/1+0-350-FM
38 12 55
EP D TN 275/FM
96 02 03
CT-T3/Y1-275-FM
39 10 22
EnerPro 230CG/10kA
96 01 32
CT-T2/2+0-275-VA
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
7
Network type
Description
Single-phase power supply
Three-phase power supply
L1
TN-S
Three-phase power supply
Separate N and PE
L2
L3
N
PE
L1
TT
Three-phase power supply
Separate N and PE
L2
L3
N
PE
L1
TN-C
Three-phase power supply
Common PEN
L2
L3
PEN
TN-S
Single-phase power supply
Separate N and PE
L1
N
PE
TT
TN-C
Single-phase power supply
Separate N and PE
Single-phase power supply
Common PEN
L1
N
PE
L1
PEN
* according to the lightning protection zones concept
8
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
L1
L2
L3
N
PE
L1
L2
L3
N
PE
L1
L2
L3
PEN
L1
N
PE
L1
N
PE
L1
PEN
selection guide
power supply systems
Adequate
SPD circuit type
Product example lightning current
arrester type 1, applicable at the
LPZ transition point 0A – 1*
Product example surge protector type 2, applicable at the LPZ
­transition point 0B – 1*
Product example terminal device
protection type 3 arrester, applicable at the LPZ transition point
1 – 2 or higher*
4 + 0 / 3 + 1
CT-T1+2/3+1-350-FM
(Item no. 96 00 01)
CT-T2/4+0-275-FM
(Item no. 96 00 55)
CT-T3/Y3-230-FM
(Item no. 96 02 05)
3 + 1
CT-T1+2/3+1-350-FM
(Item no. 96 00 01)
CT-T2/3+1-275-FM
(Item no. 96 00 43)
CT-T3/Y3-230-FM
(Item no. 96 02 05)
3 + 0
CT-T1+2/3+0-350-FM
(Item no. 96 00 03)
CT-T2/3+0-275-FM
(Item no. 96 00 45)
2 + 0 / 1 + 1
CT-T1+2/2+0-350-FM
(Item no. 96 00 07)
CT-T2/2+0-275-FM
(Item no. 96 00 49)
CT-T3/Y1-230-FM
(Item no. 96 02 03)
1 + 1
CT-T1+2/1+1-350-FM
(Item no. 96 00 09)
CT-T2/1+1-275-FM
(Item no. 96 00 51)
CT-T3/Y1-230-FM
(Item no. 96 02 03)
1 + 0
CT-T1+2/1+0-350-FM
(Item no. 96 00 11)
CT-T2/1+0-275-FM
(Item no. 96 00 53)
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
9
Surge protection for power supply systems
AC power supply
10
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for power supply systems
AC power supply
Lightning current arrester type 1 for AC power supplies
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
11
Surge protection for power supply systems
AC power supply
Lightning current arrester type 1 for AC power supplies
Example photo
CT-T1/3+1
Lightning current discharge arrester with raregas-filled spark gap for the use in three-phase
TT and TN-S systems. They provide extremely
high discharge cappabilities with at the same
time very low protection levels and they also do
not need any damageable internal or external
electronic trigger.
FM
L1
L2
n
n
Basic circuit diagram
n
PE
L3
n
Applicable at the boundaries LPZ 0A - 1
n
Test standard: IEC 61643-1 / EN 61643-11
n
Mounting on 35 mm DIN rail
n
Enclosure material: thermoplastic with the
colors yellow and black
N
Technical Data
CT-T1/3+1-350-FM
IEC category/EN type
Nominal voltage
Max. continous operating voltage AC
Type 1 / class I
UN
230/400 V
Uc
350 V~
Lightning impulse current (10/350) total
Itotal
100 kA
Lightning impulse current (10/350) L-N/N-PE/L-PEN
Iimp
25 / 100 / - kA
In
25 / 100 / - kA
Nominal discharge current (8/20) L-N/N-PE/L-PEN
Voltage protection level at limp
Up
≤ 2,5 kV
Follow current quenching capacity AC L-N (260V AC)
Ifi
10 kAeff
Follow current quenching capacity AC N-PE
Ifi
100 Aeff
Short-circuit withstand capability at max. back-up fuse
Ik
50 kAeff
Max. acceptable backup fuse (branch wiring)
250 A gL/gG
Max. acceptable backup fuse (V-type through wiring)
125 A gL/gG
Operating temperature range
n
Degree of protection according to IEC EN
60529: IP 20
n
Inflammability class according to UL 94 V0
n
Space required for installation: 144 mm
n
Remote changeover contact
TU
-40 - +80 °C
Min. conductor cross section at terminals
10mm² solid/flexible
Max. conductor cross section
50mm² stranded/35mm² fexible
Dimension (DIN 43880)
8 TE
Max. operating voltage remote contact
250 V AC/125 V DC
Order Data
Article-No.
96 02 07
Accessories
Product
CT-T1-350-M
CT-T1-NPE-M
Article-No.
96 02 37
96 02 38
Replacement protective plug for lightning current discharge arresters.
Product available in 2nd half year 2012
12
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for power supply systems
AC power supply
Lightning current arrester type 1 for AC power supplies
Example photo
CT-T1/3+0
Lightning current discharge arrester with raregas-filled spark gap for the use in three-phase
TNC systems. They provide extremely high
discharge cappabilities with at the same time very low protection levels and they also do not need
any damageable internal or external electronic
trigger.
FM
L1
L2
Basic circuit diagram
n
L3
n
Applicable at the boundaries LPZ 0A - 1
n
Test standard: IEC 61643-1 / EN 61643-11
n
Mounting on 35 mm DIN rail
n
Enclosure material: thermoplastic with the
colors yellow and black
n
n
PE N
Technical Data
n
Degree of protection according to
IEC EN 60529: IP 20
n
Inflammability class according to UL 94 V0
n
Space required for installation: 108 mm
n
Remote changeover contact
CT-T1/3+0-350-FM
IEC category/EN type
Type 1 / class I
Nominal voltage
Max. continous operating voltage AC
UN
230/400 V
Uc
350 V~
Lightning impulse current (10/350) total
Itotal
75 kA
Lightning impulse current (10/350) L-N/N-PE/L-PEN
Iimp
- / - / 75 (3L-PEN) kA
In
- / - / 75 (3L-PEN) kA
Nominal discharge current (8/20) L-N/N-PE/L-PEN
Voltage protection level at limp
Up
≤ 2,5 kV
Follow current quenching capacity AC L-N (260V AC)
Ifi
10 kAeff
Short-circuit withstand capability at max. back-up fuse
Ik
50 kAeff
Max. acceptable backup fuse (branch wiring)
250 A gL/gG
Max. acceptable backup fuse (V-type through wiring)
125 A gL/gG
Operating temperature range
TU
-40 - +80 °C
Min. conductor cross section at terminals
10mm² solid/flexible
Max. conductor cross section
50mm² stranded/35mm² fexible
Dimension (DIN 43880)
6 TE (108 mm)
Max. operating voltage remote contact
250 V AC/125 V DC
Max. operating current remote contact
1 A AC/200 mA DC
Order Data
Article-No.
96 02 09
Accessories
Product
CT-T1-350-M
Article-No.
96 02 37
Replacement protective plug for lightning current discharge arresters.
Product available in 2nd half year 2012
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
13
Surge protection for power supply systems
AC power supply
Lightning current arrester type 1 for AC power supplies
Example photo
CT-T1/2+0
Lightning current discharge arrester with raregas-filled spark gap for the use in single-phase
TN systems. They provide extremely high discharge cappabilities with at the same time very low
protection levels and they also do not need any
damageable internal or external electronic trigger.
FM
L1
L2
Basic circuit diagram
n
n
Applicable at the boundaries LPZ 0A - 1
n
Test standard: IEC 61643-1 / EN 61643-11
n
Mounting on 35 mm DIN rail
n
Enclosure material: thermoplastic with the
colors yellow and black
n
PE N
Technical Data
CT-T1/2+0-350-FM
IEC category/EN type
Nominal voltage
Max. continous operating voltage AC
Type 1 / class I
UN
230/400 V
Uc
350 V~
Lightning impulse current (10/350) total
Itotal
50 kA
Lightning impulse current (10/350) L-N/N-PE/L-PEN
Iimp
25 / - / - kA
In
25 / - / - kA
Nominal discharge current (8/20) L-N/N-PE/L-PEN
Voltage protection level at limp
Up
≤ 2,5 kV
Follow current quenching capacity AC L-N (260V AC)
Ifi
10 kAeff
Short-circuit withstand capability at max. back-up fuse
Ik
50 kAeff
Max. acceptable backup fuse (branch wiring)
250 A gL/gG
Max. acceptable backup fuse (V-type through wiring)
125 A gL/gG
Operating temperature range
n
Degree of protection according to
IEC EN 60529: IP 20
n
Inflammability class according to UL 94 V0
n
Space required for installation: 72 mm
n
Remote changeover contact
TU
-40 - +80 °C
Min. conductor cross section at terminals
10mm² solid/flexible
Max. conductor cross section
50mm² stranded/35mm² fexible
Dimension (DIN 43880)
4 TE
Max. operating voltage remote contact
250 V AC/125 V DC
Max. operating current remote contact
1 A AC/200 mA DC
Order Data
Article-No.
96 02 13
Accessories
Product
CT-T1-350-M
Article-No.
96 02 37
Replacement protective plug for lightning current discharge arresters.
Product available in 2nd half year 2012
14
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for power supply systems
AC power supply
Lightning current arrester type 1 for AC power supplies
Example photo
CT-T1/1+1
Lightning current discharge arrester with raregas-filled spark gap for the use in single-phase
TT and TN systems.They provide extremely
high discharge cappabilities with at the same
time very low protection levels and they also do
not need any damageable internal or external
electronic trigger.
FM
L
PE
n
Applicable at the boundaries LPZ 0A - 1
n
Test standard: IEC 61643-1 / EN 61643-11
n
Mounting on 35 mm DIN rail
n
Enclosure material: thermoplastic with the
colors yellow and black
Basic circuit diagram
n
N
Technical Data
n
Degree of protection according to
IEC EN 60529: IP 20
n
Inflammability class according to UL 94 V0
n
Space required for installation: 72 mm
n
Remote changeover contact
CT-T1/1+1-350-FM
IEC category/EN type
Type 1 / class I
Nominal voltage
Max. continous operating voltage AC
UN
230/400 V
Uc
350 V~
Lightning impulse current (10/350) total
Itotal
50 kA
Lightning impulse current (10/350) L-N/N-PE/L-PEN
Iimp
25 / 50 / - kA
In
25 / 50 / - kA
Nominal discharge current (8/20) L-N/N-PE/L-PEN
Voltage protection level at limp
Up
≤ 2,5 kV
Follow current quenching capacity AC L-N (260V AC)
Ifi
10 kAeff
Follow current quenching capacity AC N-PE
Ifi
100 Aeff
Short-circuit withstand capability at max. back-up fuse
Ik
50 kAeff
Max. acceptable backup fuse (branch wiring)
250 A gL/gG
Max. acceptable backup fuse (V-type through wiring)
125 A gL/gG
Operating temperature range
TU
-40 - +80 °C
Min. conductor cross section at terminals
10mm² solid/flexible
Max. conductor cross section
50mm² stranded/35mm² fexible
Dimension (DIN 43880)
4 TE
Max. operating voltage remote contact
250 V AC/125 V DC
Order Data
Article-No.
96 02 15
Accessories
Product
CT-T1-350-M
CT-T1-NPE-M
Article-No.
96 02 37
96 02 38
Replacement protective plug for lightning current discharge arresters.
Product available in 2nd half year 2012
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
15
Surge protection for power supply systems
AC power supply
Lightning current arrester type 1 for AC power supplies
Example photo
CT-T1/1+0
Lightning current discharge arrester with raregas-filled spark gap for the use between L - N
wire.They provide extremely high discharge cappabilities with at the same time very low protection
levels and they also do not need any damageable
internal or external electronic trigger.
FM
L
n
Applicable at the boundaries LPZ 0A - 1
n
Test standard: IEC 61643-1 / EN 61643-11
n
Mounting on 35 mm DIN rail
n
Enclosure material: thermoplastic with the
colors yellow and black
Basic circuit diagram
n
N/PEN
Technical Data
CT-T1/1+0-350-FM
IEC category/EN type
Nominal voltage
Max. continous operating voltage AC
Type 1 / class I
UN
230/400 V
Uc
350 V~
Lightning impulse current (10/350) total
Itotal
25 kA
Lightning impulse current (10/350) L-N/N-PE/L-PEN
Iimp
25 / - / - kA
Nominal discharge current (8/20) L-N/N-PE/L-PEN
Voltage protection level at limp
In
Up
25 / - / 25 kA
≤ 2,5 kV
Follow current quenching capacity AC L-N (260V AC)
Ifi
10 kAeff
Short-circuit withstand capability at max. back-up fuse
Ik
50 kAeff
Max. acceptable backup fuse (branch wiring)
250 A gL/gG
Max. acceptable backup fuse (V-type through wiring)
125 A gL/gG
Operating temperature range
n
Degree of protection according to IEC EN
60529: IP 20
n
Inflammability class according to UL 94 V0
n
Space required for installation: 36 mm
n
Remote changeover contact
TU
-40 - +80 °C
Min. conductor cross section at terminals
10mm² solid/flexible
Max. conductor cross section
50mm² stranded/35mm² fexible
Dimension (DIN 43880)
2 TE
Max. operating voltage remote contact
250 V AC/125 V DC
Max. operating current remote contact
1 A AC/200 mA DC
Order Data
Article-No.
96 02 17
Accessories
Product
CT-T1-350-M
Article-No.
96 02 37
Replacement protective plug for lightning current discharge arresters.
Product available in 2nd half year 2012
16
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for power supply systems
AC power supply
Lightning current arrester type 1 for AC power supplies
Example photo
CT-T1-FS
Lightning current cappable and rare-gas-filled
summation current spark gap for the use between N - PE wire.They provide extremely high
discharge cappabilities with at the same time
very low protection levels and they also do
not need any damageable internal or external
electronic trigger.
FM
L
n
Applicable at the LPZ transition point 0A-1
respectively 0A-2
Test standard: IEC 61643-1 / EN 61643-11
n
n
Enclosure material: thermoplastic with the
colors yellow and black
Basic circuit diagram
n
N/PEN
Technical Data
n
Mounting on 35 mm DIN rail
n
Degree of protection according to IEC EN
60529: IP 20
n
Inflammability class according to UL 94 V0
n
Space required for installation: 36 mm
CT-T1/0+1-FS-FM
IEC category/EN type
Type 1 / class I
Nominal voltage
UN
230 V
Max. continous operating voltage AC
Uc
260 V~
Lightning impulse current (10/350)
Iimp
100 kA
Lightning impulse current (10/350) L-N/N-PE/L-PEN
Iimp
- / 100 / - kA
In
- / 100 / - kA
Nominal discharge current (8/20) L-N/N-PE/L-PEN
Up
≤ 2,5 kV
Follow current quenching capacity AC N-PE
Ifi
100 Aeff
Short-circuit withstand capability at max. back-up fuse
Ik
50 kAeff
Voltage protection level at limp
Max. acceptable backup fuse (branch wiring)
250 A gL/gG
Max. acceptable backup fuse (V-type through wiring)
125 A gL/gG
Operating temperature range
TU
-40 - +80 °C
Min. conductor cross section at terminals
10mm² solid/flexible
Max. conductor cross section
50mm² stranded/35mm² fexible
Dimension (DIN 43880)
2 TE
Max. operating voltage remote contact
250 V AC/125 V DC
Max. operating current remote contact
1 A AC/200 mA DC
Order Data
Article-No.
96 02 33
Accessories
Product
CT-T1-NPE-M
Article-No.
96 02 38
Replacement protective plug for lightning current capable summation spark gaps.
Product available in 2nd half year 2012
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
17
Surge protection for power supply systems
AC power supply
18
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for power supply systems
AC power supply
Combined arrester type 1 + 2 for AC power supplies
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
19
Surge protection for power supply systems
AC power supply
Combined arrester type 1 + 2 for AC power supplies
Example photo
CT-T1+2/3+1
Lightning current discharge arrester with raregas-filled spark gap and very low protection level
< 1 kV for the use in three-phase TT and TN-S
systems. They provide extremely high discharge
cappabilities with at the same time very low
protection levels and they also do not need any
damageable internal or external electronic trigger.
FM
L1
L2
n
n
Basic circuit diagram
n
PE
L3
n
Applicable at the boundaries LPZ 0A - 2
n
Test standard: IEC 61643-1 / EN 61643-11
n
Mounting on 35 mm DIN rail
n
Enclosure material: thermoplastic with the
colors yellow and black
N
Technical Data
CT-T1+2/3+1-350-FM
IEC category/EN type
Nominal voltage
Max. continous operating voltage AC
Type 1 + 2 / class I + II
UN
230/400 V
Uc
350 V~
Lightning impulse current (10/350) total
Itotal
100 kA
Lightning impulse current (10/350) L-N/N-PE/L-PEN
Iimp
25 / 100 / - kA
In
25 / 100 / - kA
Nominal discharge current (8/20) L-N/N-PE/L-PEN
Voltage protection level at limp
Up
≤ 1,5 kV
Follow current quenching capacity AC L-N (260V AC)
Ifi
4 kAeff
Follow current quenching capacity AC N-PE
Ifi
100 Aeff
Short-circuit withstand capability at max. back-up fuse
Ik
50 kAeff
Max. acceptable backup fuse (branch wiring)
250 A gL/gG
Max. acceptable backup fuse (V-type through wiring)
125 A gL/gG
Operating temperature range
n
Degree of protection according to IEC EN
60529: IP 20
n
Inflammability class according to UL 94 V0
n
Space required for installation: 144 mm
n
Remote changeover contact
TU
-40 - +80 °C
Min. conductor cross section at terminals
10mm² solid/flexible
Max. conductor cross section
50mm² stranded/35mm² fexible
Dimension (DIN 43880)
8 TE
Max. operating voltage remote contact
250 V AC/125 V DC
Order Data
Article-No.
96 00 01
Accessories
Product
CT-T1+2-350-M
CT-T1-NPE-M
Article-No.
96 02 36
96 02 38
Replacement protective plug for combined lightning current discharge and surge arresters.
Product available in 2nd half year 2012
20
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for power supply systems
AC power supply
Combined arrester type 1 + 2 for AC power supplies
Example photo
CT-T1+2/3+0
Lightning current discharge arrester with raregas-filled spark gap and very low protection level
< 1 kV for the use in three-phase TNC systems.
They provide extremely high discharge cappabilities with at the same time very low protection
levels and they also do not need any damageable
internal or external electronic trigger.
FM
L1
L2
Basic circuit diagram
n
L3
n
Applicable at the boundaries LPZ 0A - 2
n
Test standard: IEC 61643-1 / EN 61643-11
n
Mounting on 35 mm DIN rail
n
Enclosure material: thermoplastic with the
colors yellow and black
n
n
PE N
Technical Data
n
Degree of protection according to IEC EN
60529: IP 20
n
Inflammability class according to UL 94 V0
n
Space required for installation: 108 mm
n
Remote changeover contact
CT-T1+2/3+0-350-FM
IEC category/EN type
Type 1 + 2 / class I + II
Nominal voltage
Max. continous operating voltage AC
UN
230/400 V
Uc
350 V~
Lightning impulse current (10/350) total
Itotal
75 kA
Lightning impulse current (10/350) L-N/N-PE/L-PEN
Iimp
- / - / 75 (3L-PEN) kA
In
- / - / 75 (3L-PEN) kA
Nominal discharge current (8/20) L-N/N-PE/L-PEN
Voltage protection level at limp
Up
≤ 1,5 kV
Follow current quenching capacity AC L-N (260V AC)
Ifi
4 kAeff
Short-circuit withstand capability at max. back-up fuse
Ik
50 kAeff
Max. acceptable backup fuse (branch wiring)
250 A gL/gG
Max. acceptable backup fuse (V-type through wiring)
125 A gL/gG
Operating temperature range
TU
-40 - +80 °C
Min. conductor cross section at terminals
10mm² solid/flexible
Max. conductor cross section
50mm² stranded/35mm² fexible
Dimension (DIN 43880)
6 TE
Max. operating voltage remote contact
250 V AC/125 V DC
Max. operating current remote contact
1 A AC/200 mA DC
Order Data
Article-No.
96 00 03
Accessories
Product
CT-T1+2-350-M
Article-No.
96 02 36
Replacement protective plug for combined lightning current discharge and surge arresters.
Product available in 2nd half year 2012
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
21
Surge protection for power supply systems
AC power supply
Combined arrester type 1 + 2 for AC power supplies
Example photo
CT-T1+2/2+0
Lightning current discharge arrester with raregas-filled spark gap and very low protection level
< 1 kV for the use in single-phase TN systems.
They provide extremely high discharge cappabilities with at the same time very low protection
levels and they also do not need any damageable
internal or external electronic trigger.
FM
L1
L2
Basic circuit diagram
n
n
Applicable at the boundaries LPZ 0A - 2
n
Test standard: IEC 61643-1 / EN 61643-11
n
Mounting on 35 mm DIN rail
n
Enclosure material: thermoplastic with the
colors yellow and black
n
PE N
Technical Data
CT-T1+2/2+0-350-FM
IEC category/EN type
Nominal voltage
Max. continous operating voltage AC
Type 1 + 2 / class I + II
UN
230/400 V
Uc
350 V~
Lightning impulse current (10/350) total
Itotal
50 kA
Lightning impulse current (10/350) L-N/N-PE/L-PEN
Iimp
25 / - / - kA
In
25 / - / - kA
Nominal discharge current (8/20) L-N/N-PE/L-PEN
Voltage protection level at limp
Up
≤ 1,5 kV
Follow current quenching capacity AC L-N (260V AC)
Ifi
4 kAeff
Short-circuit withstand capability at max. back-up fuse
Ik
50 kAeff
Max. acceptable backup fuse (branch wiring)
250 A gL/gG
Max. acceptable backup fuse (V-type through wiring)
125 A gL/gG
Operating temperature range
n
Degree of protection according to IEC EN
60529: IP 20
n
Inflammability class according to UL 94 V0
n
Space required for installation: 72 mm
n
Remote changeover contact
TU
-40 - +80 °C
Min. conductor cross section at terminals
10mm² solid/flexible
Max. conductor cross section
50mm² stranded/35mm² fexible
Dimension (DIN 43880)
4 TE
Max. operating voltage remote contact
250 V AC/125 V DC
Max. operating current remote contact
1 A AC/200 mA DC
Order Data
Article-No.
96 00 07
Accessories
Product
CT-T1+2-350-M
Article-No.
96 02 36
Replacement protective plug for combined lightning current discharge and surge arresters.
Product available in 2nd half year 2012
22
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for power supply systems
AC power supply
Combined arrester type 1 + 2 for AC power supplies
Example photo
CT-T1+2/1+1
Lightning current discharge arrester with raregas-filled spark gap and very low protection level
< 1 kV for the use in single-phase TT and TN
systems.They provide extremely high discharge
cappabilities with at the same time very low
protection levels and they also do not need any
damageable internal or external electronic trigger.
FM
L
PE
n
Applicable at the boundaries LPZ 0A - 2
n
Test standard: IEC 61643-1 / EN 61643-11
n
Mounting on 35 mm DIN rail
n
Enclosure material: thermoplastic with the
colors yellow and black
Basic circuit diagram
n
N
Technical Data
n
Degree of protection according to IEC EN
60529: IP 20
n
Inflammability class according to UL 94 V0
n
Space required for installation: 72 mm
n
Remote changeover contact
CT-T1+2/1+1-350-FM
IEC category/EN type
Type 1 + 2 / class I + II
Nominal voltage
Max. continous operating voltage AC
UN
230/400 V
Uc
350 V~
Lightning impulse current (10/350) total
Itotal
50 kA
Lightning impulse current (10/350) L-N/N-PE/L-PEN
Iimp
25 / 50 / - kA
In
25 / 50 / - kA
Nominal discharge current (8/20) L-N/N-PE/L-PEN
Voltage protection level at limp
Up
≤ 1,5 kV
Follow current quenching capacity AC L-N (260V AC)
Ifi
4 kAeff
Follow current quenching capacity AC N-PE
Ifi
100 Aeff
Short-circuit withstand capability at max. back-up fuse
Ik
50 kAeff
Max. acceptable backup fuse (branch wiring)
250 A gL/gG
Max. acceptable backup fuse (V-type through wiring)
125 A gL/gG
Operating temperature range
TU
-40 - +80 °C
Min. conductor cross section at terminals
10mm² solid/flexible
Max. conductor cross section
50mm² stranded/35mm² fexible
Dimension (DIN 43880)
4 TE
Max. operating voltage remote contact
250 V AC/125 V DC
Order Data
Article-No.
96 00 09
Accessories
Product
CT-T1+2-350-M
CT-T1-NPE-M
Article-No.
96 02 36
96 02 38
Replacement protective plug for combined lightning current discharge and surge arresters.
Product available in 2nd half year 2012
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
23
Surge protection for power supply systems
AC power supply
Combined arrester type 1 + 2 for AC power supplies
Example photo
CT-T1+2/1+0
Lightning current discharge arrester with raregas-filled spark gap and very low protection level
< 1 kV for the use between L - N wire. They provide extremely high discharge cappabilities with
at the same time very low protection levels and
they also do not need any damageable internal or
external electronic trigger.
FM
L
n
Applicable at the boundaries LPZ 0A - 2
n
Test standard: IEC 61643-1 / EN 61643-11
n
Mounting on 35 mm DIN rail
n
Enclosure material: thermoplastic with the
colors yellow and black
Basic circuit diagram
n
N/PEN
Technical Data
CT-T1+2/1+0-350-FM
IEC category/EN type
Nominal voltage
Max. continous operating voltage AC
Type 1 + 2 / class I + II
UN
230/400 V
Uc
350 V~
Lightning impulse current (10/350) total
Itotal
25 kA
Lightning impulse current (10/350) L-N/N-PE/L-PEN
Iimp
25 / - / - kA
Nominal discharge current (8/20) L-N/N-PE/L-PEN
Voltage protection level at limp
In
Up
25 / - / 25 kA
≤ 1,5 kV
Follow current quenching capacity AC L-N (260V AC)
Ifi
4 kAeff
Short-circuit withstand capability at max. back-up fuse
Ik
50 kAeff
Max. acceptable backup fuse (branch wiring)
250 A gL/gG
Max. acceptable backup fuse (V-type through wiring)
125 A gL/gG
Operating temperature range
n
Degree of protection according to IEC EN
60529: IP 20
n
Inflammability class according to UL 94 V0
n
Space required for installation: 36 mm
n
Remote changeover contact
TU
-40 - +80 °C
Min. conductor cross section at terminals
10mm² solid/flexible
Max. conductor cross section
50mm² stranded/35mm² fexible
Dimension (DIN 43880)
2 TE
Max. operating voltage remote contact
250 V AC/125 V DC
Max. operating current remote contact
1 A AC/200 mA DC
Order Data
Article-No.
96 00 11
Accessories
Product
CT-T1+2-350-M
Article-No.
96 02 36
Replacement protective plug for combined lightning current discharge and surge arresters.
Product available in 2nd half year 2012
24
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for power supply systems
AC power supply
Combined arrester type 1 + 2 for AC power supplies
Example photo
CT-T1-FS
Lightning current cappable and rare-gas-filled
summation current spark gap for the use between N - PE wire. They provide extremely high
discharge cappabilities with at the same time
very low protection levels and they also do
not need any damageable internal or external
electronic trigger.
FM
L
n
Applicable at the LPZ transition point 0A-1
respectively 0A-2
Test standard: IEC 61643-1 / EN 61643-11
n
n
Enclosure material: thermoplastic with the
colors yellow and black
Basic circuit diagram
n
N/PEN
Technical Data
n
Mounting on 35 mm DIN rail
n
Degree of protection according to IEC EN
60529: IP 20
n
Inflammability class according to UL 94 V0
n
Remote changeover contact
CT-T1/0+1-FS-FM
IEC category/EN type
Nominal voltage
UN
230 V
Max. continous operating voltage AC
Uc
260 V~
Lightning impulse current (10/350)
Iimp
100 kA
Lightning impulse current (10/350) L-N/N-PE/L-PEN
Iimp
- / 100 / - kA
In
- / 100 / - kA
Nominal discharge current (8/20) L-N/N-PE/L-PEN
Up
≤ 2,5 kV
Follow current quenching capacity AC N-PE
Ifi
100 Aeff
Short-circuit withstand capability at max. back-up fuse
Ik
50 kAeff
Voltage protection level at limp
Max. acceptable backup fuse (branch wiring)
250 A gL/gG
Max. acceptable backup fuse (V-type through wiring)
125 A gL/gG
Operating temperature range
TU
-40 - +80 °C
Min. conductor cross section at terminals
10mm² solid/flexible
Max. conductor cross section
50mm² stranded/35mm² fexible
Dimension (DIN 43880)
2 TE (36 mm)
Max. operating voltage remote contact
250 V AC/125 V DC
Max. operating current remote contact
1 A AC/200 mA DC
Order Data
Article-No.
96 02 33
Accessories
Product
CT-T1-NPE-M
Article-No.
96 02 38
Replacement protective plug for lightning current capable summation spark gaps.
Product available in 2nd half year 2012
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
25
Surge protection for power supply systems
AC power supply
26
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for power supply systems
AC power supply
SPD type 2 for AC power supplies
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
27
Surge protection for power supply systems
AC power supply
SPD type 2 for AC power supplies
Example photo
CT-T2/4+0
Fully pluggable surge protective arrester for the
use in three-phase TNS systems.
FM
L2
L3
N
Basic circuit diagram
L1
n
Test standard: IEC 61643-1 / EN 61643-11
n
Applicable at the boundaries LPZ 0B - 1 and
higher
Degree of protection according to IEC EN
n
60529: IP 20
PE
n
Mounting on 35 mm DIN rail
n
Enclosure material: thermoplastic with the
colors yellow and black
n
Inflammability class according to UL 94 V0
Optional remote changeover contact
n
Technical Data
CT-T2/4+0-150
CT-T2/4+0-150-FM
CT-T2/4+0-275
CT-T2/4+0-275-FM
IEC category/EN type
Type 2 / class II
Type 2 / class II
Type 2 / class II
Type 2 / class II
120 V
120 V
230 V
230 V
Nominal voltage
UN
Max. continous operating voltage AC
Uc
150 V~
150 V~
275 V~
275 V~
Nominal discharge current (8/20)
In
15 kA
15 kA
20 kA
20 kA
40 kA
40 kA
40 kA
40 kA
Protection level at In
Up
≤ 0,7 kV
≤ 0,7 kV
≤ 1,2 kV
≤ 1,2 kV
Protection level at 5 kA
Up
≤ 0,5 kV
≤ 0,5 kV
≤ 0,9 kV
≤ 0,9 kV
Max. impulse discharge current (8/20)
Short-circuit withstand capability at max. back-up fuse
Imax
Ik
Max. allowed prefuse
Operating temperature range
Min. conductor cross section at terminals
TU
25 kAeff
25 kAeff
25 kAeff
25 kAeff
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
Max. conductor cross section
35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible
Dimension (DIN 43880)
4 TE (72 mm)
4 TE (72 mm)
4 TE (72 mm)
4 TE (72 mm)
Max. operating voltage remote contact
250 V AC/125 V DC
250 V AC/125 V DC
Max. operating current remote contact
1 A AC/200 mA DC
1 A AC/200 mA DC
Order Data
Article-No.
Product available in 2nd half year 2012
28
96 00 40
96 00 41
96 00 54
96 00 55
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for power supply systems
AC power supply
Technical Data
CT-T2/4+0-350
CT-T2/4+0-350-FM
CT-T2/4+0-440
CT-T2/4+0-440-FM
IEC category/EN type
Type 2 / class II
Type 2 / class II
Type 2 / class II
Type 2 / class II
230 V
230 V
230 V
230 V
Nominal voltage
UN
Max. continous operating voltage AC
Uc
350 V~
350 V~
440 V~
440 V~
Nominal discharge current (8/20)
In
20 kA
20 kA
20 kA
20 kA
Max. impulse discharge current (8/20)
40 kA
40 kA
40 kA
40 kA
Protection level at In
Up
≤ 1,5 kV
≤ 1,5 kV
≤ 2,0 kV
≤ 2,0 kV
Protection level at 5 kA
Up
≤ 1,0 kV
≤ 1,0 kV
≤ 1,5 kV
≤ 1,5 kV
Short-circuit withstand capability at max. back-up fuse
Imax
Ik
Max. allowed prefuse
Operating temperature range
TU
Min. conductor cross section at terminals
25 kAeff
25 kAeff
25 kAeff
25 kAeff
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
Max. conductor cross section
35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible
Dimension (DIN 43880)
4 TE (72 mm)
4 TE (72 mm)
4 TE (72 mm)
4 TE (72 mm)
Max. operating voltage remote contact
250 V AC/125 V DC
250 V AC/125 V DC
Max. operating current remote contact
1 A AC/200 mA DC
1 A AC/200 mA DC
Order Data
Article-No.
96 00 68
96 00 69
96 00 82
96 00 83
Accessories
Product
CT-T2-350-M
CT-T2-275-M
Article-No.
96 01 85
96 01 84
Replacement protective plug for surge protection devices type 2.
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
29
Surge protection for power supply systems
AC power supply
SPD type 2 for AC power supplies
Example photo
CT-T2/3+1
Fully pluggable surge protective arrester for the
use in three-phase TT and TNS systems.
FM
L2
PE
L3
Basic circuit diagram
L1
n
Applicable at the boundaries LPZ 0B - 1 and
higher
n
Test standard: IEC 61643-1 / EN 61643-11
n
Degree of protection according to IEC EN
60529: IP 20
N
n
Mounting on 35 mm DIN rail
n
Enclosure material: thermoplastic with the
colors yellow and black
n
Inflammability class according to UL 94 V0
Optional remote changeover contact
n
Technical Data
CT-T2/3+1-150
CT-T2/3+1-150-FM
CT-T2/3+1-275
CT-T2/3+1-275-FM
IEC category/EN type
Type 2 / class II
Type 2 / class II
Type 2 / class II
Type 2 / class II
120 V
120 V
230 V
230 V
Nominal voltage
UN
Max. continous operating voltage AC
Uc
150 V~
150 V~
275 V~
275 V~
Nominal discharge current (8/20)
In
15 kA
15 kA
20 kA
20 kA
40 kA
40 kA
40 kA
40 kA
Protection level at In
Up
≤ 0,7 kV
≤ 0,7 kV
≤ 1,2 kV
≤ 1,2 kV
Protection level at 5 kA
Up
≤ 0,5 kV
≤ 0,5 kV
≤ 0,9 kV
≤ 0,9 kV
Protection level N-PE
Max. impulse discharge current (8/20)
Imax
Up
≤ 1,5 kV
≤ 1,5 kV
≤ 1,5 kV
≤ 1,5 kV
Follow current quenching capacity AC N-PE
Ifi
100 Aeff
100 Aeff
100 Aeff
100 Aeff
Short-circuit withstand capability at max. back-up fuse
Ik
Max. allowed prefuse
Operating temperature range
Min. conductor cross section at terminals
TU
25 kAeff
25 kAeff
25 kAeff
25 kAeff
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
Max. conductor cross section
35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible
Dimension (DIN 43880)
4 TE (72 mm)
4 TE (72 mm)
4 TE (72 mm)
4 TE (72 mm)
Max. operating voltage remote contact
250 V AC/125 V DC
250 V AC/125 V DC
Max. operating current remote contact
1 A AC/200 mA DC
1 A AC/200 mA DC
Order Data
Article-No.
Product available in 2nd half year 2012
30
96 00 28
96 00 29
96 00 42
96 00 43
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for power supply systems
AC power supply
Technical Data
CT-T2/3+1-350
CT-T2/3+1-350-FM
CT-T2/3+1-440
CT-T2/3+1-440-FM
IEC category/EN type
Type 2 / class II
Type 2 / class II
Type 2 / class II
Type 2 / class II
230 V
230 V
230 V
230 V
Nominal voltage
UN
Max. continous operating voltage AC
Uc
350 V~
350 V~
440 V~
440 V~
Nominal discharge current (8/20)
In
20 kA
20 kA
20 kA
20 kA
Max. impulse discharge current (8/20)
40 kA
40 kA
40 kA
40 kA
Protection level at In
Imax
Up
≤ 1,5 kV
≤ 1,5 kV
≤ 2,0 kV
≤ 2,0 kV
Protection level at 5 kA
Up
≤ 1,0 kV
≤ 1,0 kV
≤ 1,5 kV
≤ 1,5 kV
Protection level N-PE
Up
≤ 1,5 kV
≤ 1,5 kV
≤ 1,5 kV
≤ 1,5 kV
Follow current quenching capacity AC N-PE
Ifi
100 Aeff
100 Aeff
100 Aeff
100 Aeff
Short-circuit withstand capability at max. back-up fuse
Ik
Max. allowed prefuse
TU
Operating temperature range
Min. conductor cross section at terminals
25 kAeff
25 kAeff
25 kAeff
25 kAeff
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
Max. conductor cross section
35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible
Dimension (DIN 43880)
4 TE (72 mm)
4 TE (72 mm)
4 T 4 TE (72 mm) E
4 TE (72 mm)
Max. operating voltage remote contact
250 V AC/125 V DC
250 V AC/125 V DC
Max. operating current remote contact
1 A AC/200 mA DC
1 A AC/200 mA DC
Order Data
Article-No.
96 00 56
96 00 57
Product
CT-T2-350-M
CT-T2-NPE-M
Article-No.
96 01 85
96 02 39
96 00 70
96 00 71
Accessories
Replacement protective plug for surge protection devices type 2.
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
31
Surge protection for power supply systems
AC power supply
SPD type 2 for AC power supplies
Example photo
CT-T2/3+0
Fully pluggable surge protective arrester for the
use in three-phase TNC systems.
FM
L2
Basic circuit diagram
L1
L3
n
Applicable at the boundaries LPZ 0B - 1 and
higher
n
Test standard: IEC 61643-1 / EN 61643-11
n
Degree of protection according to IEC EN
60529: IP 20
PEN
n
Mounting on 35 mm DIN rail
n
Enclosure material: thermoplastic with the
colors yellow and black
n
Inflammability class according to UL 94 V0
Optional remote changeover contact
n
Technical Data
CT-T2/3+0-150
CT-T2/3+0-150-FM
CT-T2/3+0-275
CT-T2/3+0-275-FM
IEC category/EN type
Type 2 / class II
Type 2 / class II
Type 2 / class II
Type 2 / class II
120 V
120 V
230 V
230 V
Nominal voltage
UN
Max. continous operating voltage AC
Uc
150 V~
150 V~
275 V~
275 V~
Nominal discharge current (8/20)
In
15 kA
15 kA
20 kA
20 kA
40 kA
40 kA
40 kA
40 kA
Protection level at In
Up
≤ 0,7 kV
≤ 0,7 kV
≤ 1,2 kV
≤ 1,2 kV
Protection level at 5 kA
Up
≤ 0,5 kV
≤ 0,5 kV
≤ 0,9 kV
≤ 0,9 kV
Max. impulse discharge current (8/20)
Short-circuit withstand capability at max. back-up fuse
Imax
Ik
Max. allowed prefuse
Operating temperature range
Min. conductor cross section at terminals
TU
25 kAeff
25 kAeff
25 kAeff
25 kAeff
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
Max. conductor cross section
35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible
Dimension (DIN 43880)
3 TE (54 mm)
3 TE (54 mm)
3 TE (54 mm)
3 TE (54 mm)
Max. operating voltage remote contact
250 V AC/125 V DC
250 V AC/125 V DC
Max. operating current remote contact
1 A AC/200 mA DC
1 A AC/200 mA DC
Order Data
Article-No.
Product available in 2nd half year 2012
32
96 00 30
96 00 31
96 00 44
96 00 45
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for power supply systems
AC power supply
Technical Data
CT-T2/3+0-350
CT-T2/3+0-350-FM
CT-T2/3+0-440
CT-T2/3+0-440-FM
IEC category/EN type
Type 2 / class II
Type 2 / class II
Type 2 / class II
Type 2 / class II
230 V
230 V
230 V
230 V
Nominal voltage
UN
Max. continous operating voltage AC
Uc
350 V~
350 V~
440 V~
440 V~
Nominal discharge current (8/20)
In
20 kA
20 kA
20 kA
20 kA
Max. impulse discharge current (8/20)
40 kA
40 kA
40 kA
40 kA
Protection level at In
Up
≤ 1,5 kV
≤ 1,5 kV
≤ 2,0 kV
≤ 2,0 kV
Protection level at 5 kA
Up
≤ 1,0 kV
≤ 1,0 kV
≤ 1,5 kV
≤ 1,5 kV
Short-circuit withstand capability at max. back-up fuse
Imax
Ik
Max. allowed prefuse
Operating temperature range
TU
Min. conductor cross section at terminals
25 kAeff
25 kAeff
25 kAeff
25 kAeff
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
Max. conductor cross section
35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible
Dimension (DIN 43880)
3 TE (54 mm)
3 TE (54 mm)
3 TE (54 mm)
3 TE (54 mm)
Max. operating voltage remote contact
250 V AC/125 V DC
250 V AC/125 V DC
Max. operating current remote contact
1 A AC/200 mA DC
1 A AC/200 mA DC
Order Data
Article-No.
96 00 58
96 00 59
96 00 72
96 00 73
Accessories
Product
CT-T2-350-M
CT-T2-275-M
Article-No.
96 01 85
96 01 84
Replacement protective plug for surge protection devices type 2.
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
33
Surge protection for power supply systems
AC power supply
SPD type 2 for AC power supplies
Example photo
CT-T2/2+0
Fully pluggable surge protective arrester for the
use in single-phase TN systems.
FM
Basic circuit diagram
L1
L2
n
Test standard: IEC 61643-1 / EN 61643-11
n
Applicable at the boundaries LPZ 0B - 1 and
higher
Degree of protection according to IEC EN
n
60529: IP 20
PEN
n
Mounting on 35 mm DIN rail
n
Enclosure material: thermoplastic with the
colors yellow and black
n
Inflammability class according to UL 94 V0
Optional remote changeover contact
n
Technical Data
CT-T2/2+0-150
CT-T2/2+0-150-FM
CT-T2/2+0-275
CT-T2/2+0-275-FM
IEC category/EN type
Type 2 / class II
Type 2 / class II
Type 2 / class II
Type 2 / class II
120 V
120 V
230 V
230 V
Nominal voltage
UN
Max. continous operating voltage AC
Uc
150 V~
150 V~
275 V~
275 V~
Nominal discharge current (8/20)
In
15 kA
15 kA
20 kA
20 kA
40 kA
40 kA
40 kA
40 kA
Protection level at In
Up
≤ 0,7 kV
≤ 0,7 kV
≤ 1,2 kV
≤ 1,2 kV
Protection level at 5 kA
Up
≤ 0,5 kV
≤ 0,5 kV
≤ 0,9 kV
≤ 0,9 kV
Max. impulse discharge current (8/20)
Short-circuit withstand capability at max. back-up fuse
Imax
Ik
Max. allowed prefuse
Operating temperature range
Min. conductor cross section at terminals
TU
25 kAeff
25 kAeff
25 kAeff
25 kAeff
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
Max. conductor cross section
35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible
Dimension (DIN 43880)
2 TE (36 mm)
2 TE (36 mm)
2 TE (36 mm)
2 TE (36 mm)
Max. operating voltage remote contact
250 V AC/125 V DC
250 V AC/125 V DC
Max. operating current remote contact
1 A AC/200 mA DC
1 A AC/200 mA DC
Order Data
Article-No.
Product available in 2nd half year 2012
34
96 00 34
96 00 35
96 00 48
96 00 49
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for power supply systems
AC power supply
Technical Data
CT-T2/2+0-350
CT-T2/2+0-350-FM
CT-T2/2+0-440
CT-T2/2+0-440-FM
IEC category/EN type
Type 2 / class II
Type 2 / class II
Type 2 / class II
Type 2 / class II
230 V
230 V
230 V
230 V
Nominal voltage
UN
Max. continous operating voltage AC
Uc
350 V~
350 V~
440 V~
440 V~
Nominal discharge current (8/20)
In
20 kA
20 kA
20 kA
20 kA
Max. impulse discharge current (8/20)
40 kA
40 kA
40 kA
40 kA
Protection level at In
Up
≤ 1,5 kV
≤ 1,5 kV
≤ 2,0 kV
≤ 2,0 kV
Protection level at 5 kA
Up
≤ 1,0 kV
≤ 1,0 kV
≤ 1,5 kV
≤ 1,5 kV
Short-circuit withstand capability at max. back-up fuse
Imax
Ik
Max. allowed prefuse
Operating temperature range
TU
Min. conductor cross section at terminals
25 kAeff
25 kAeff
25 kAeff
25 kAeff
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
Max. conductor cross section
35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible
Dimension (DIN 43880)
2 TE (36 mm)
2 TE (36 mm)
2 TE (36 mm)
2 TE (36 mm)
Max. operating voltage remote contact
250 V AC/125 V DC
250 V AC/125 V DC
Max. operating current remote contact
1 A AC/200 mA DC
1 A AC/200 mA DC
Order Data
Article-No.
96 00 62
96 00 63
96 00 76
96 00 77
Accessories
Product
CT-T2-350-M
CT-T2-275-M
Article-No.
96 01 85
96 01 84
Replacement protective plug for surge protection devices type 2.
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
35
Surge protection for power supply systems
AC power supply
SPD type 2 for AC power supplies
Example photo
CT-T2/1+1
Fully pluggable surge protective arrester for the
use in single-phase TT and TN systems.
FM
Basic circuit diagram
L1
PE
n
Applicable at the boundaries LPZ 0B - 1 and
higher
n
Test standard: IEC 61643-1 / EN 61643-11
n
Degree of protection according to IEC EN
60529: IP 20
N
n
Mounting on 35 mm DIN rail
n
Enclosure material: thermoplastic with the
colors yellow and black
n
Inflammability class according to UL 94 V0
Optional remote changeover contact
n
Technical Data
CT-T2/1+1-150
CT-T2/1+1-150-FM
CT-T2/1+1-275
CT-T2/1+1-275-FM
IEC category/EN type
Type 2 / class II
Type 2 / class II
Type 2 / class II
Type 2 / class II
120 V
120 V
230 V
230 V
Nominal voltage
UN
Max. continous operating voltage AC
Uc
150 V~
150 V~
275 V~
275 V~
Nominal discharge current (8/20)
In
15 kA
15 kA
20 kA
20 kA
Protection level at In
Up
≤ 0,7 kV
≤ 0,7 kV
≤ 1,2 kV
≤ 1,2 kV
Protection level at 5 kA
Up
≤ 0,5 kV
≤ 0,5 kV
≤ 0,9 kV
≤ 0,9 kV
Protection level N-PE
Up
≤ 1,5 kV
≤ 1,5 kV
≤ 1,5 kV
≤ 1,5 kV
Follow current quenching capacity AC N-PE
Ifi
100 Aeff
100 Aeff
100 Aeff
100 Aeff
Short-circuit withstand capability at max. back-up fuse
Ik
25 kAeff
25 kAeff
25 kAeff
25 kAeff
125 A gL/gG
125 A gL/gG
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
125 A gL/gG
Max. allowed prefuse
Operating temperature range
TU
Min. conductor cross section at terminals
1.5mm² solid/flexible
Max. conductor cross section
35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible
Dimension (DIN 43880)
2 TE (36 mm)
2 TE (36 mm)
Max. operating voltage remote contact
250 V AC/125 V DC
Max. operating current remote contact
1 A AC/200 mA DC
Max. impulse discharge current (8/20)
Imax
2 TE (36 mm)
2 TE (36 mm)
250 V AC/125 V DC
1 A AC/200 mA DC
40 kA
40 kA
96 00 50
96 00 51
Order Data
Article-No.
Product available in 2nd half year 2012
36
96 00 36
96 00 37
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for power supply systems
AC power supply
Technical Data
CT-T2/1+1-350
CT-T2/1+1-350-FM
CT-T2/1+1-440
CT-T2/1+1-440-FM
IEC category/EN type
Type 2 / class II
Type 2 / class II
Type 2 / class II
Type 2 / class II
230 V
230 V
230 V
230 V
Nominal voltage
UN
Max. continous operating voltage AC
Uc
350 V~
350 V~
440 V~
440 V~
Nominal discharge current (8/20)
In
20 kA
20 kA
20 kA
20 kA
Max. impulse discharge current (8/20)
40 kA
40 kA
40 kA
40 kA
Protection level at In
Imax
Up
≤ 1,5 kV
≤ 1,5 kV
≤ 2,0 kV
≤ 2,0 kV
Protection level at 5 kA
Up
≤ 1,0 kV
≤ 1,0 kV
≤ 1,5 kV
≤ 1,5 kV
Protection level N-PE
Up
≤ 1,5 kV
≤ 1,5 kV
≤ 1,5 kV
≤ 1,5 kV
Follow current quenching capacity AC N-PE
Ifi
100 Aeff
100 Aeff
100 Aeff
100 Aeff
Short-circuit withstand capability at max. back-up fuse
Ik
Max. allowed prefuse
TU
Operating temperature range
Min. conductor cross section at terminals
25 kAeff
25 kAeff
25 kAeff
25 kAeff
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
1,5
Max. conductor cross section
35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible
Dimension (DIN 43880)
2 TE (36 mm)
2 TE (36 mm)
2 TE (36 mm)
2 TE (36 mm)
Max. operating voltage remote contact
250 V AC/125 V DC
250 V AC/125 V DC
Max. operating current remote contact
1 A AC/200 mA DC
1 A AC/200 mA DC
Order Data
Article-No.
96 00 64
96 00 65
Product
CT-T2-350-M
CT-T2-NPE-M
Article-No.
96 01 85
96 02 39
96 00 78
96 00 79
Accessories
Replacement protective plug for surge protection devices type 2.
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
37
Surge protection for power supply systems
AC power supply
SPD type 2 for AC power supplies
Example photo
CT-T2/1+0
Fully pluggable surge protective arrester for the
use between L - N wires.
FM
Basic circuit diagram
L
n
Applicable at the boundaries LPZ 0B - 1 and
higher
n
Test standard: IEC 61643-1 / EN 61643-11
n
Degree of protection according to IEC EN
60529: IP 20
N/PEN
n
Mounting on 35 mm DIN rail
n
Enclosure material: thermoplastic with the
colors yellow and black
n
Inflammability class according to UL 94 V0
Optional remote changeover contact
n
Technical Data
CT-T2/1+0-75
CT-T2/1+0-75-FM
CT-T2/1+0-150
CT-T2/1+0-150-FM
IEC category/EN type
Type 2 / class II
Type 2 / class II
Type 2 / class II
Type 2 / class II
60 V
60 V
120 V
120 V
Nominal voltage
UN
Max. continous operating voltage AC
Uc
75 V~
75 V~
150 V~
150 V~
Nominal discharge current (8/20)
In
10 kA
10 kA
15 kA
15 kA
25 kA
25 kA
40 kA
40 kA
Protection level at In
Up
≤ 0,4 kV
≤ 0,4 kV
≤ 0,7 kV
≤ 0,7 kV
Protection level at 5 kA
Up
≤ 0,33 kV
≤ 0,33 kV
≤ 0,5 kV
≤ 0,5 kV
Max. impulse discharge current (8/20)
Short-circuit withstand capability at max. back-up fuse
Imax
Ik
Max. allowed prefuse
Operating temperature range
Min. conductor cross section at terminals
TU
25 kAeff
25 kAeff
25 kAeff
25 kAeff
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
1.5mm² solid/flexible
1.5mm² solid/flexible
1,51.5mm² solid/flexible
1.5mm² solid/flexible
Max. conductor cross section
35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible
Dimension (DIN 43880)
1 TE (18 mm)
1 TE (18 mm)
1 TE (18 mm)
1 TE (18 mm)
Max. operating voltage remote contact
250 V AC/125 V DC
250 V AC/125 V DC
Max. operating current remote contact
1 A AC/200 mA DC
1 A AC/200 mA DC
Order Data
Article-No.
Product available in 2nd half year 2012
38
96 00 24
96 00 25
96 00 38
96 00 39
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for power supply systems
AC power supply
Technical Data
CT-T2/1+0-275
CT-T2/1+0-275-FM
CT-T2/1+0-350
CT-T2/1+0-350-FM
IEC category/EN type
Type 2 / class II
Type 2 / class II
Type 2 / class II
Type 2 / class II
230 V
230 V
230 V
230 V
Nominal voltage
UN
Max. continous operating voltage AC
Uc
275 V~
275 V~
350 V~
350 V~
Nominal discharge current (8/20)
In
20 kA
20 kA
20 kA
20 kA
Max. impulse discharge current (8/20)
40 kA
40 kA
40 kA
40 kA
Protection level at In
Up
≤ 1,2 kV
≤ 1,2 kV
≤ 1,5 kV
≤ 1,5 kV
Protection level at 5 kA
Up
≤ 0,9 kV
≤ 0,9 kV
≤ 1,0 kV
≤ 1,0 kV
Short-circuit withstand capability at max. back-up fuse
Imax
Ik
Max. allowed prefuse
Operating temperature range
TU
Min. conductor cross section at terminals
25 kAeff
25 kAeff
25 kAeff
25 kAeff
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
Max. conductor cross section
35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible
Dimension (DIN 43880)
1 TE (18 mm)
1 TE (18 mm)
1 TE (18 mm)
1 TE (18 mm)
Max. operating voltage remote contact
250 V AC/125 V DC
250 V AC/125 V DC
Max. operating current remote contact
1 A AC/200 mA DC
1 A AC/200 mA DC
Order Data
Article-No.
96 00 52
96 00 53
96 00 66
96 00 67
Technical Data
CT-T2/1+0-440
CT-T2/1+0-440-FM
CT-T2/1+0-600
CT-T2/1+0-600-FM
IEC category/EN type
Type 2 / class II
Type 2 / class II
Type 2 / class II
Type 2 / class II
Nominal voltage
UN
230 V
230 V
400 V
400 V
Max. continous operating voltage AC
Uc
440 V~
440 V~
600 V~
600 V~
Nominal discharge current (8/20)
Max. impulse discharge current (8/20)
In
20 kA
20 kA
20 kA
20 kA
Imax
40 kA
40 kA
40 kA
40 kA
Protection level at In
Up
≤ 2,0 kV
≤ 2,0 kV
≤ 2,5 kV
≤ 2,5 kV
Protection level at 5 kA
Up
≤ 1,5 kV
≤ 1,5 kV
≤ 1,8 kV
≤ 1,8 kV
Ik
25 kAeff
25 kAeff
25 kAeff
25 kAeff
Short-circuit withstand capability at max. back-up fuse
Max. allowed prefuse
Operating temperature range
TU
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
Min. conductor cross section at terminals
1.5mm² solid/flexible
Max. conductor cross section
35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible
Dimension (DIN 43880)
1 TE (18 mm)
1 TE (18 mm)
1 TE (18 mm)
1 TE (18 mm)
Max. operating voltage remote contact
250 V AC/125 V DC
250 V AC/125 V DC
Max. operating current remote contact
1 A AC/200 mA DC
1 A AC/200 mA DC
Bestelldaten
Article-No.
96 00 80
96 00 81
96 00 94
96 00 95
Accessories
Product
CT-T2-350-M
CT-T2-150-M
Article-No.
96 01 85
96 01 83
Replacement protective plug for surge protection devices type 2.
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
39
Surge protection for power supply systems
AC power supply
SPD type 2 for AC power supplies
Example photo
CT-T2/0+1-FS
Type 2 surge cappable and rare-gas-filled
summation current spark gap for the use between N - PE wire. They provide extremely high
discharge cappabilities with at the same time
very low protection levels and they also do
not need any damageable internal or external
electronic trigger.
FM
L
n
Applicable at the boundaries LPZ 0B - 1 and
higher
Test standard: IEC 61643-1 / EN 61643-11
n
n
Degree of protection according to IEC EN
60529: IP 20
Basic circuit diagram
n
N/PEN
Technical Data
CT-T2/0+1-FS
CT-T2/0+1-FS-FM
IEC category/EN type
Type 2 / class II
Type 2 / class II
Nominal voltage
UN
230 V
230 V
Max. continous operating voltage AC
Uc
260 V~
260 V~
Nominal discharge current (8/20)
In
20 kA
20 kA
Imax
40 kA
40 kA
Up
≤ 1,5 kV
≤ 1,5 kV
Follow current quenching capacity AC N-PE
Ifi
100 Aeff
100 Aeff
Short-circuit withstand capability at max. back-up fuse
Ik
25 kAeff
25 kAeff
125 A gL/gG
125 A gL/gG
Max. impulse discharge current (8/20)
Protection level N-PE
Max. allowed prefuse
Operating temperature range
-40 - +80 °C
-40 - +80 °C
Min. conductor cross section at terminals
TU
1.5mm² solid/flexible
1.5mm² solid/flexible
Max. conductor cross section
35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible
Dimension (DIN 43880)
1 TE (18 mm)
1 TE (18 mm)
96 02 34
96 02 35
n
Mounting on 35 mm DIN rail
n
Enclosure material: thermoplastic with the
colors yellow and black
n
Inflammability class according to UL 94 V0
n
Optional remote changeover contact
Order Data
Article-No.
Accessories
Product
CT-T2-NPE-M
Article-No.
96 02 39
Replacement protective plug for lightning current capable summation spark gaps.
Product available in 2nd half year 2012
40
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for power supply systems
AC power supply
SPD type 2 for AC power supplies (leakage-current free)
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
41
Surge protection for power supply systems
AC power supply
SPD type 2 for AC power supplies (leakage-current free)
Example photo
CT-T2/4+0-VA
Fully pluggable and leakage-free surge protective
arrester for the use in three-phase TNS systems.
FM
L2
L3
N
Basic circuit diagram
L1
n
Applicable at the boundaries LPZ 0B - 1 and
higher
n
Enhanced arrestor lifetime due to absence of
leakage current
n
Test standard: IEC 61643-1 / EN 61643-11
PE
n
Mounting on 35 mm DIN rail
n
Degree of protection according to IEC EN
60529: IP 20
n
Inflammability class according to UL 94 V0
Optional remote changeover contact
n
Technical Data
CT-T2/4+0-275-VA
CT-T2/4+0-275-VA-FM
CT-T2/4+0-350-VA
CT-T2/4+0-350-VA-FM
IEC category/EN type
Type 2 / class II
Type 2 / class II
Type 2 / class II
Type 2 / class II
230 V
230 V
230 V
230 V
Nominal voltage
UN
Max. continous operating voltage AC
Uc
275 V~
275 V~
350 V~
350 V~
Nominal discharge current (8/20)
In
15 kA
15 kA
15 kA
15 kA
25 kA
25 kA
25 kA
25 kA
Protection level at In
Up
≤ 1,2 kV
≤ 1,2 kV
≤ 1,7 kV
≤ 1,7 kV
Protection level at 5 kA
Up
≤ 0,9 kV
≤ 0,9 kV
≤ 1,3 kV
≤ 1,3 kV
Max. impulse discharge current (8/20)
Short-circuit withstand capability at max. back-up fuse
Imax
Ik
Max. allowed prefuse
Operating temperature range
Min. conductor cross section at terminals
TU
25 kAeff
25 kAeff
25 kAeff
25 kAeff
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
Max. conductor cross section
35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible
Dimension (DIN 43880)
4 TE (72 mm)
4 TE (72 mm)
4 TE (72 mm)
4 TE (72 mm)
Max. operating voltage remote contact
250 V AC/125 V DC
250 V AC/125 V DC
Max. operating current remote contact
1 A AC/200 mA DC
1 A AC/200 mA DC
Order Data
Article-No.
96 01 38
96 01 39
96 01 52
96 01 53
Accessories
Product
CT-T2-350-VA-M
CT-T2-275-VA-M
Article-No.
96 01 97
96 01 96
Replacement protective plug for leakage-free surge protection devices type 2.
Product available in 2nd half year 2012
42
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for power supply systems
AC power supply
SPD type 2 for AC power supplies (leakage-current free)
Example photo
CT-T2/3+1-VA
Fully pluggable and leakage-free surge protective arrester for the use in three-phase TT and
TNS systems. Enhanced arrestor lifetime due to
absence of leakage current.
FM
L2
PE
L3
Basic circuit diagram
L1
n
Applicable at the boundaries LPZ 0B - 1 and
higher
n
Test standard: IEC 61643-1 / EN 61643-11
n
Degree of protection according to IEC EN
60529: IP 20
N
n
Mounting on 35 mm DIN rail
n
Inflammability class according to UL 94 V0
n
Optional remote changeover contacthöher
n
Prüfnormen: IEC 61643-1 / EN 61643-11
Technical Data
CT-T2/3+1-275-VA
CT-T2/3+1-275-VA-FM
CT-T2/3+1-350-VA
CT-T2/3+1-350-VA-FM
IEC category/EN type
Type 2 / class II
Type 2 / class II
Type 2 / class II
Type 2 / class II
230 V
230 V
230 V
230 V
Nominal voltage
UN
Max. continous operating voltage AC
Uc
275 V~
275 V~
350 V~
350 V~
Nominal discharge current (8/20)
In
15 kA
15 kA
15 kA
15 kA
25 kA
25 kA
25 kA
25 kA
Protection level at In
Up
≤ 1,2 kV
≤ 1,2 kV
≤ 1,7 kV
≤ 1,7 kV
Protection level at 5 kA
Up
≤ 0,9 kV
≤ 0,9 kV
≤ 1,3 kV
≤ 1,3 kV
Protection level N-PE
Max. impulse discharge current (8/20)
Imax
Up
≤ 1,5 kV
≤ 1,5 kV
≤ 1,5 kV
≤ 1,5 kV
Follow current quenching capacity AC N-PE
Ifi
100 Aeff
100 Aeff
100 Aeff
100 Aeff
Short-circuit withstand capability at max. back-up fuse
Ik
Max. allowed prefuse
Operating temperature range
TU
Min. conductor cross section at terminals
25 kAeff
25 kAeff
25 kAeff
25 kAeff
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
Max. conductor cross section
35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible
Dimension (DIN 43880)
4 TE (72 mm)
4 TE (72 mm)
4 TE (72 mm)
4 TE (72 mm)
Max. operating voltage remote contact
250 V AC/125 V DC
250 V AC/125 V DC
Max. operating current remote contact
1 A AC/200 mA DC
1 A AC/200 mA DC
Order Data
Article-No.
96 01 26
96 01 27
Product
CT-T2-275-VA-M
CT-T2-NPE-M
Article-No.
96 01 96
96 02 39
96 01 40
96 01 41
Accessories
Replacement protective plug for leakage-free surge protection devices type 2.
Product available in 2nd half year 2012
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
43
Surge protection for power supply systems
AC power supply
SPD type 2 for AC power supplies (leakage-current free)
Example photo
CT-T2/3+0-VA
Fully pluggable and leakage-free surge protective
arrester for the use in three-phase TNC systems.
FM
L2
Basic circuit diagram
L1
L3
n
Enhanced arrestor lifetime due to absence of
leakage current
n
Applicable at the boundaries LPZ 0B - 1 and
higher
n
Test standard: IEC 61643-1 / EN 61643-11
PEN
n
Mounting on 35 mm DIN rail
n
Degree of protection according to IEC EN
60529: IP 20
n
Inflammability class according to UL 94 V0
Optional remote changeover contact
n
Technical Data
CT-T2/3+0-275-VA
CT-T2/3+0-275-VA-FM
CT-T2/3+0-350-VA
CT-T2/3+0-350-VA-FM
IEC category/EN type
Type 2 / class II
Type 2 / class II
Type 2 / class II
Type 2 / class II
230 V
230 V
230 V
230 V
Nominal voltage
UN
Max. continous operating voltage AC
Uc
275 V~
275 V~
350 V~
350 V~
Nominal discharge current (8/20)
In
15 kA
15 kA
15 kA
15 kA
25 kA
25 kA
25 kA
25 kA
Protection level at In
Up
≤ 1,2 kV
≤ 1,2 kV
≤ 1,7 kV
≤ 1,7 kV
Protection level at 5 kA
Up
≤ 0,9 kV
≤ 0,9 kV
≤ 1,3 kV
≤ 1,3 kV
Max. impulse discharge current (8/20)
Short-circuit withstand capability at max. back-up fuse
Imax
Ik
Max. allowed prefuse
Operating temperature range
Min. conductor cross section at terminals
TU
25 kAeff
25 kAeff
25 kAeff
25 kAeff
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
Max. conductor cross section
35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible
Dimension (DIN 43880)
3 TE (54 mm)
3 TE (54 mm)
3 TE (54 mm)
3 TE (54 mm)
Max. operating voltage remote contact
250 V AC/125 V DC
250 V AC/125 V DC
Max. operating current remote contact
1 A AC/200 mA DC
1 A AC/200 mA DC
Order Data
Article-No.
96 01 28
96 01 29
96 01 42
96 01 43
Accessories
Product
CT-T2-350-VA-M
CT-T2-275-VA-M
Article-No.
96 01 97
96 01 96
Replacement protective plug for leakage-free surge protection devices type 2.
Product available in 2nd half year 2012
44
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for power supply systems
AC power supply
SPD type 2 for AC power supplies (leakage-current free)
Example photo
CT-T2/2+0-VA
Fully pluggable and leakage-free surge protective
arrester for the use in single-phase TN systems.
FM
Basic circuit diagram
L1
L2
n
Applicable at the boundaries LPZ 0B - 1 and
higher
n
Enhanced arrestor lifetime due to absence of
leakage current
n
Test standard: IEC 61643-1 / EN 61643-11
PEN
n
Mounting on 35 mm DIN rail
n
Degree of protection according to IEC EN
60529: IP 20
n
Inflammability class according to UL 94 V0
Optional remote changeover contact
n
Technical Data
CT-T2/2+0-275-VA
CT-T2/2+0-275-VA-FM
CT-T2/2+0-350-VA
CT-T2/2+0-350-VA-FM
IEC category/EN type
Type 2 / class II
Type 2 / class II
Type 2 / class II
Type 2 / class II
230 V
230 V
230 V
230 V
Nominal voltage
UN
Max. continous operating voltage AC
Uc
275 V~
275 V~
350 V~
350 V~
Nominal discharge current (8/20)
In
15 kA
15 kA
15 kA
15 kA
25 kA
25 kA
25 kA
25 kA
Protection level at In
Up
≤ 1,2 kV
≤ 1,2 kV
≤ 1,7 kV
≤ 1,7 kV
Protection level at 5 kA
Up
≤ 0,9 kV
≤ 0,9 kV
≤ 1,3 kV
≤ 1,3 kV
Max. impulse discharge current (8/20)
Short-circuit withstand capability at max. back-up fuse
Imax
Ik
Max. allowed prefuse
Operating temperature range
TU
Min. conductor cross section at terminals
25 kAeff
25 kAeff
25 kAeff
25 kAeff
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
Max. conductor cross section
35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible
Dimension (DIN 43880)
2 TE (36 mm)
2 TE (36 mm)
2 TE (36 mm)
2 TE (36 mm)
Max. operating voltage remote contact
250 V AC/125 V DC
250 V AC/125 V DC
Max. operating current remote contact
1 A AC/200 mA DC
1 A AC/200 mA DC
Order Data
Article-No.
96 01 32
96 01 33
96 01 46
96 01 47
Accessories
Product
CT-T2-350-VA-M
CT-T2-275-VA-M
Article-No.
96 01 97
96 01 96
Replacement protective plug for leakage-free surge protection devices type 2.
Product available in 2nd half year 2012
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
45
Surge protection for power supply systems
AC power supply
SPD type 2 for AC power supplies (leakage-current free)
Example photo
CT-T2/1+1-VA
Fully pluggable and leakage-free surge protective
arrester for the use in single-phase TT and TN
systems.
FM
Basic circuit diagram
L1
PE
n
Enhanced arrestor lifetime due to absence of
leakage current
n
Applicable at the boundaries LPZ 0B - 1 and
higher
n
Test standard: IEC 61643-1 / EN 61643-11
N
n
Mounting on 35 mm DIN rail
n
Degree of protection according to IEC EN
60529: IP 20
n
Inflammability class according to UL 94 V0
Optional remote changeover contact
n
Technical Data
CT-T2/1+1-275-VA
CT-T2/1+1-275-VA-FM
CT-T2/1+1-350-VA
CT-T2/1+1-350-VA-FM
IEC category/EN type
Type 2 / class II
Type 2 / class II
Type 2 / class II
Type 2 / class II
230 V
230 V
230 V
230 V
Nominal voltage
UN
Max. continous operating voltage AC
Uc
275 V~
275 V~
350 V~
350 V~
Nominal discharge current (8/20)
In
15 kA
15 kA
15 kA
15 kA
25 kA
25 kA
25 kA
25 kA
Protection level at In
Up
≤ 1,2 kV
≤ 1,2 kV
≤ 1,7 kV
≤ 1,7 kV
Protection level at 5 kA
Up
≤ 0,9 kV
≤ 0,9 kV
≤ 1,3 kV
≤ 1,3 kV
Protection level N-PE
Max. impulse discharge current (8/20)
Imax
Up
≤ 1,5 kV
≤ 1,5 kV
≤ 1,5 kV
≤ 1,5 kV
Follow current quenching capacity AC N-PE
Ifi
100 Aeff
100 Aeff
100 Aeff
100 Aeff
Short-circuit withstand capability at max. back-up fuse
Ik
Max. allowed prefuse
Operating temperature range
Min. conductor cross section at terminals
TU
25 kAeff
25 kAeff
25 kAeff
25 kAeff
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
Max. conductor cross section
35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible
Dimension (DIN 43880)
2 TE (36 mm)
2 TE (36 mm)
2 TE (36 mm)
2 TE (36 mm)
Max. operating voltage remote contact
250 V AC/125 V DC
1 A AC/200 mA DC
Max. operating current remote contact
1 A AC/200 mA DC
250 V AC/125 V DC
Order Data
Article-No.
96 01 34
96 01 35
Product
CT-T2-275-VA-M
CT-T2-NPE-M
Article-No.
96 01 96
96 02 39
96 01 48
96 01 49
Accessories
Replacement protective plug for leakage-free surge protection devices type 2.
Product available in 2nd half year 2012
46
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for power supply systems
AC power supply
SPD type 2 for AC power supplies (leakage-current free)
Example photo
CT-T2/1+0-VA
Fully pluggable and leakage-free surge protective
arrester for the use between L - N wires.
FM
Basic circuit diagram
L
n
Applicable at the boundaries LPZ 0B - 1 and
higher
n
Enhanced arrestor lifetime due to absence of
leakage current
n
Test standard: IEC 61643-1 / EN 61643-11
N/PEN
n
Mounting on 35 mm DIN rail
n
Degree of protection according to IEC EN
60529: IP 20
n
Inflammability class according to UL 94 V0
Optional remote changeover contact
n
Technical Data
CT-T2/1+0-275-VA
CT-T2/1+0-275-VA-FM
CT-T2/1+0-350-VA
CT-T2/1+0-350-VA-FM
IEC category/EN type
Type 2 / class II
Type 2 / class II
Type 2 / class II
Type 2 / class II
230 V
230 V
230 V
230 V
Nominal voltage
UN
Max. continous operating voltage AC
Uc
275 V~
275 V~
350 V~
350 V~
Nominal discharge current (8/20)
In
15 kA
15 kA
15 kA
15 kA
25 kA
25 kA
25 kA
25 kA
Protection level at In
Up
≤ 1,2 kV
≤ 1,2 kV
≤ 1,7 kV
≤ 1,7 kV
Protection level at 5 kA
Up
≤ 0,9 kV
≤ 0,9 kV
≤ 1,3 kV
≤ 1,3 kV
Max. impulse discharge current (8/20)
Short-circuit withstand capability at max. back-up fuse
Imax
Ik
Max. allowed prefuse
Operating temperature range
TU
Min. conductor cross section at terminals
25 kAeff
25 kAeff
25 kAeff
25 kAeff
125 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
Max. conductor cross section
35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible
Dimension (DIN 43880)
1 TE (18 mm)
1 TE (18 mm)
1 TE (18 mm)
1 TE (18 mm)
Max. operating voltage remote contact
250 V AC/125 V DC
250 V AC/125 V DC
Max. operating current remote contact
1 A AC/200 mA DC
1 A AC/200 mA DC
Order Data
Article-No.
96 01 36
96 01 37
96 01 50
96 01 51
Accessories
Product
CT-T2-350-VA-M
CT-T2-275-VA-M
Article-No.
96 01 97
96 01 96
Replacement protective plug for leakage-free surge protection devices type 2.
Product available in 2nd half year 2012
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
47
Surge protection for power supply systems
AC power supply
SPD type 2 for AC power supplies
Example photo
CT-T2/0+1-FS
Type 2 surge cappable and rare-gas-filled
summation current spark gap for the use between N - PE wire. They provide extremely high
discharge cappabilities with at the same time
very low protection levels and they also do
not need any damageable internal or external
electronic trigger.
FM
L
n
Applicable at the boundaries LPZ 0B - 1 and
higher
Test standard: IEC 61643-1 / EN 61643-11
n
n
Degree of protection according to IEC EN
60529: IP 20
Basic circuit diagram
n
N/PEN
Technical Data
CT-T2/0+1-FS
CT-T2/0+1-FS-FM
IEC category/EN type
Type 2 / class II
Type 2 / class II
Nominal voltage
UN
230 V
230 V
Max. continous operating voltage AC
Uc
260 V~
260 V~
Nominal discharge current (8/20)
In
20 kA
20 kA
Imax
40 kA
40 kA
Up
≤ 1,5 kV
≤ 1,5 kV
Follow current quenching capacity AC N-PE
Ifi
100 Aeff
100 Aeff
Short-circuit withstand capability at max. back-up fuse
Ik
25 kAeff
25 kAeff
125 A gL/gG
125 A gL/gG
Max. impulse discharge current (8/20)
Protection level N-PE
Max. allowed prefuse
Operating temperature range
-40 - +80 °C
-40 - +80 °C
Min. conductor cross section at terminals
TU
1.5mm² solid/flexible
1.5mm² solid/flexible
Max. conductor cross section
35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible
Dimension (DIN 43880)
1 TE (18 mm)
1 TE (18 mm)
1 TE (18 mm)
96 02 34
96 02 35
n
Mounting on 35 mm DIN rail
n
Enclosure material: thermoplastic with the
colors yellow and black
n
Inflammability class according to UL 94 V0
n
Optional remote changeover contact
Order Data
Article-No.
Accessories
Product
CT-T2-NPE-M
Article-No.
96 02 39
Replacement protective plug for lightning current capable summation spark gaps.
Product available in 2nd half year 2012
48
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for power supply systems
AC power supply
SPD type 3 for AC power supplies
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
49
Surge protection for power supply systems
AC power supply
SPD type 3 for AC power supplies
Example photo
CT-T3/Y1
Two-piece pluggable surge protection for singlephase terminal equipment and devices.
PE
Basic circuit diagram
L
N
12
11
14
L
PE
n
Mounting on 35 mm DIN rail
n
Enclosure material: thermoplastic with the
colors yellow and black
n
Inflammability class according to UL 94 V0
Optional remote changeover contact
n
n
Applicable at the boundaries LPZ 1 - 2 and
higher
n
Test standard: IEC 61643-1 / EN 61643-11
n
Degree of protection according to IEC EN
60529: IP 20
N
Technical Data
CT-T3/Y1-24
CT-T3/Y1-24-FM
CT-T3/Y1-48
CT-T3/Y1-48-FM
IEC category/EN type
Type 3 / class III
Type 3 / class III
Type 3 / class III
Type 3 / class III
24 V
24 V
48 V
48 V
Nominal voltage
UN
Max. continous operating voltage (DC/AC)
Uc
30 V
30 V
60 V
60 V
Nominal discharge current (8/20)
In
1 kA
1 kA
1 kA
1 kA
Total discharge current (8/20) L+N-PE
Combined surge generator impulse
Itotal
2 kA
2 kA
2 kA
2 kA
Uoc
2 kV
2 kV
2 kV
2 kV
4 kV
4 kV
4 kV
4 kV
Combined surge generator impulse L+N-PE
Protection level L-N
Up
≤ 0,18 kV
≤ 0,18 kV
≤ 0,35 kV
≤ 0,35 kV
Protection level L/N-PE
Up
≤ 0,63 kV
≤ 0,63 kV
≤ 0,73 kV
≤ 0,73 kV
Short-circuit withstand capability at max. back-up fuse
Ik
Max. allowed prefuse
Operating temperature range
Min. conductor cross section at terminals
TU
6 kAeff
6 kAeff
6 kAeff
6 kAeff
25 A gL/gG
25 A gL/gG
25 A gL/gG
25 A gL/gG
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
0,5mm² solid/flexible
0,5mm² solid/flexible
0,5mm² solid/flexible
0,5mm² solid/flexible
Max. conductor cross section
4mm² solid/ 2,5mm² flexible
4mm² solid/ 2,5mm² flexible
4mm² solid/ 2,5mm² flexible
4mm² solid/ 2,5mm² flexible
Dimension (DIN 43880)
1 TE (18 mm)
1 TE (18 mm)
1 TE (18 mm)
1 TE (18 mm)
Max. operating voltage remote contact
250 V AC/125 V DC
250 V AC/125 V DC
Max. operating current remote contact
1 A AC/200 mA DC
1 A AC/200 mA DC
Order Data
Article-No.
Product available in 2nd half year 2012
50
96 01 86
96 01 87
96 01 90
96 01 91
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for power supply systems
AC power supply
Technical Data
CT-T3/Y1-60
CT-T3/Y1-60-FM
CT-T3/Y1-120
CT-T3/Y1-120-FM
IEC category/EN type
Type 3 / class III
Type 3 / class III
Type 3 / class III
Type 3 / class III
60 V
60 V
120 V
120 V
Nominal voltage
UN
Max. continous operating voltage (DC/AC)
Uc
75 V
75 V
150 V
150 V
Rated load current
IL
25 A
25 A
25 A
25 A
Nominal discharge current (8/20)
Total discharge current (8/20) L+N-PE
Combined surge generator impulse
In
2 kA
2 kA
2 kA
2 kA
Itotal
4 kA
4 kA
4 kA
4 kA
Uoc
4 kV
4 kV
4 kV
4 kV
Combined surge generator impulse L+N-PE
Protection level L-N
Up
Protection level L/N-PE
Up
Short-circuit withstand capability at max. back-up fuse
Ik
Max. allowed prefuse
Operating temperature range
TU
8 kV
8 kV
8 kV
8 kV
≤ 0,40 kV
≤ 0,40 kV
≤ 0,64 kV
≤ 0,64 kV
≤ 0,73 kV
≤ 0,73 kV
≤ 0,80 kV
≤ 0,80 kV
6 kAeff
6 kAeff
6 kAeff
6 kAeff
25 A gL/gG
25 A gL/gG
25 A gL/gG
25 A gL/gG
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
Min. conductor cross section at terminals
0,5mm² solid/flexible
0,5mm² solid/flexible
0,5mm² solid/flexible
0,5mm² solid/flexible
Max. conductor cross section
4mm² solid/ 2,5mm² flexible
4mm² solid/ 2,5mm² flexible
4mm² solid/ 2,5mm² flexible
4mm² solid/ 2,5mm² flexible
Dimension (DIN 43880)
1 TE (18 mm)
1 TE (18 mm)
1 TE (18 mm)
1 TE (18 mm)
Max. operating voltage remote contact
250 V AC/125 V DC
250 V AC/125 V DC
Order Data
Article-No.
96 01 94
96 01 95
Technical Data
CT-T3/Y1-230
CT-T3/Y1-230-FM
IEC category/EN type
Type 3 / class III
Type 3 / class III
Nominal voltage
UN
230 V
230 V
Max. continous operating voltage (DC/AC)
Uc
255 V
255 V
Rated load current
IL
25 A
25 A
Nominal discharge current (8/20)
In
3 kA
3 kA
Itotal
5 kA
5 kA
Total discharge current (8/20) L+N-PE
Combined surge generator impulse
Uoc
Combined surge generator impulse L+N-PE
6 kV
6 kV
10 kV
10 kV
Protection level L-N
Up
≤ 1,25 kV
≤ 1,25 kV
Protection level L/N-PE
Up
≤ 1,50 kV
≤ 1,50 kV
Short-circuit withstand capability at max. back-up fuse
Ik
Max. allowed prefuse
Operating temperature range
TU
6 kAeff
6 kAeff
25 A gL/gG
25 A gL/gG
-40 - +80 °C
-40 - +80 °C
Min. conductor cross section at terminals
0,5mm² solid/flexible
0,5mm² solid/flexible
Max. conductor cross section
4mm² solid/ 2,5mm² flexible
4mm² solid/ 2,5mm² flexible
Dimension (DIN 43880)
1 TE (18 mm)
1 TE (18 mm)
Max. operating voltage remote contact
96 01 98
96 01 99
250 V AC/125 V DC
Order Data
Article-No.
96 02 02
96 02 03
Accessories
Product
CT-T3/Y1-230-M
CT-T3/Y1-24-M
Article-No.
96 02 44
96 02 40
Replacement protective plug for single-phase surge protection devices type 3.
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
51
Surge protection for power supply systems
AC power supply
SPD type 3 for AC power supplies
Example photo
CT-T3/Y3
Two-piece pluggable surge protection for threephase terminal equipment and devices.
Basic circuit diagram
L1 L1
L2 L2
L3 L3
12
11
14
PE
PE
n
Applicable at the boundaries LPZ 1 - 2 and
higher
n
Test standard: IEC 61643-1 / EN 61643-11
n
Degree of protection according to IEC EN
60529: IP 20
N N
Technical Data
CT-T3/Y3-230
CT-T3/Y3-230-FM
IEC category/EN type
Type 3 / class III
Type 3 / class III
Nominal voltage
UN
230 V
230 V
Max. continous operating voltage (DC/AC)
Uc
255 V
255 V
Rated load current
IL
25 A
25 A
Nominal discharge current (8/20)
In
3 kA
3 kA
Itotal
8 kA
8 kA
Uoc
6 kV
6 kV
Total discharge current (8/20) L1+L2+L3+N-PE
Combined surge generator impulse
Combined surge generator impulse L1+L2+L3+N-PE
16 kV
16 kV
Protection level L-N
Up
≤ 1 kV
≤ 1 kV
Protection level L/N-PE
Up
≤ 1,5 kV
≤ 1,5 kV
Ik
6 kAeff
6 kAeff
25 A gL/gG
25 A gL/gG
-40 - +80 °C
-40 - +80 °C
0,5mm² solid/flexible
Short-circuit withstand capability at max. back-up fuse
Max. allowed prefuse
Operating temperature range
TU
Min. conductor cross section at terminals
0,5mm² solid/flexible
Max. conductor cross section
4mm² solid/ 2,5mm² flexible
4mm² solid/ 2,5mm² flexible
Dimension (DIN 43880)
2 TE (36 mm)
2 TE (36 mm)
Max. operating voltage remote contact
n
Mounting on 35 mm DIN rail
n
Enclosure material: thermoplastic with the
colors yellow and black
n
Inflammability class according to UL 94 V0
Optional remote changeover contact
n
250 V AC/125 V DC
Order Data
Article-No.
96 02 04
96 02 05
Accessories
Product
CT-T3/Y3-230-M
Article-No.
96 02 45
Replacement protective plug for three-phase surge protection devices type 3.
Product available in 2nd half year 2012
52
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for power supply systems
AC power supply
SPD type 3 for AC power supplies
CombiPro S+
Pluggable combined overvoltage protection for
electrical and electronic devices with supply
voltage of 230 V. Application for analogue and
digital telephone lines, IT networks and SAT
aerials input.
n
SCHUKO plug for 230 V AC supply
n
With child protection
n
Power line control by green lamp ON
Basic circuit diagram
n
Applicable at the boundaries LPZ 1 - 2 and
higher
n
Test standard: IEC 61643-1 / EN 61643-11
n
Extremely quick response-time (25 ns)
n
Low protection level
Technical Data
CPS+ 230
CPS+ 230Tel/Net
CPS+ 230SAT
CPS+ 230TV
IEC category/EN type
Type 3 / class III
Type 3 / class III
Type 3 / class III
Type 3 / class III
230 V~
230 V~
230 V~
230 V~
Nominal alternating voltage
UN
Max. continous operating voltage AC
Uc
255 V~
255 V~
255 V~
255 V~
Rated load current
IL
16 A
16 A
16 A
16 A
Nominal discharge current (8/20)
Max. impulse discharge current (8/20)
In
Imax
Maximum allowed voltage
Uc
Protection level
Up
2,5 kA
2,5 kA
2,5 kA
2,5 kA
5 kA
5 kA
5 kA
5 kA
-V
180 V/6 V
70 V
70 V
1,5 kV
0,4 kV/0,09 kV
0,3 kV
0,3 kV
Installation dimensions (W × H × D)
65 x 100 x 35 mm
65 x 100 x 35 mm
65 x 100 x 35 mm
65 x 100 x 35 mm
Type of connection
%
Combo Jack RJ45
IEC
F
32 50 00
32 50 01
32 50 02
32 50 03
Order Data
Article-No.
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
53
Surge protection for power supply systems
AC power supply
SPD type 3 for AC power supplies
EnerPro D 230 SM
Universally useable device to protect equipment
and devices up to 16 A power consumption
against overvoltages. With test plug and acoustic
fault indication.
Basic circuit diagram
n
Applicable at the boundaries LPZ 1 - 2 and
higher
n
Test standard: IEC 61643-1 / EN 61643-11
n
Universal device for use in cable ducts and
holder boxes
Technical Data
EP D 230 SM
IEC category/EN type
Type 3 / class III
Nominal alternating voltage
UN
230 V~
Max. continous operating voltage AC
Uc
255 V~
Rated load current
IL
16 A
16 A gL/gG
Max. allowed prefuse
Protection level L-N
Up
≤ 0,95 kV
Protection level L/N-PE
Up
≤ 1,05 kV
Nominal discharge current (8/20)
Max. impulse discharge current (8/20)
In
Imax
Response time L-N/L,N-PE
2,5 kA
6 kA
≤ 25/≤ 100 ns
6 kA
Short-circuit withstand capability with 16 A back-up fuse
Operating temperature range
n
Class III 2-pole mini SPD (fine protection)
TU
-20 - +80 °C
Conductor cross section
3 x 1 mm²
Dimensions L x W x H
31 x 20 x 13,5 mm
Enclosure material / colour
polycarbonate (halogen-free) UL 94-V0 / yellow
Degree of protection (IEC EN 60529)
IP 20
Mounting on
under-floor systems, cable trys and device installation boxes
Order Data
Article-No.
36 20 30
Dimension drawing, see pages 220 to 223
54
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for power supply systems
AC power supply
SPD type 3 for AC power supplies
EnerPro D 230 KM
Surge arrester for installation systems and terminal equipment with acoustic fault indication.
Basic circuit diagram
n
Applicable at the boundaries LPZ 1 - 2 and
higher
n
Test standard: IEC 61643-1 / EN 61643-11
n
Universal device for use in cable ducts and
holder boxes
Technical Data
n
Class III 2-pole mini SPD (fine protection)
n
Protection against longitudinal and transverse
voltages for loads up to 16 A
EP D 230 KM
IEC category/EN type
Type 3 / class III
Max. continous operating voltage AC
Uc
255 V~
16 A gL/gG
Max. allowed prefuse
Rated load current
IL
Protection level L-N
Up
≤ 1,25 kV
Protection level L/N-PE
Up
≤ 1,5 kV
Response time L-N/L,N-PE
16 A
≤ 25/≤ 100 ns
Nominal discharge current (8/20)
Max. impulse discharge current (8/20)
In
3 kA
Imax
6 kA
TU
Operating temperature range
Combined surge generator impulse
Uoc
-15 - +60 °C
6 kV
Conductor length
ca. 100 mm
Dimensions L x W x H
36 x 24 x 9 mm
Enclosure material / colour
polycarbonate (halogen-free) UL 94-V0 / yellow
Mounting on
under-floor systems, cable trys and device installation boxes
Order Data
Article-No.
36 20 35
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
55
Surge protection for power supply systems
AC power supply
SPD type 3 for AC power supplies
NM 220V/5kA
Surge voltage protection module for the protection of single-phase 230 V equipment with max.
16 A power consumption.
PAS/EBB
Verbraucher
equipment
PE
L1
L1
PE
N
N
Basic circuit diagram
n
Applicable at the boundaries LPZ 1 - 2 and
higher
n
Test standard: IEC 61643-1 / EN 61643-11
n
Compact module for equipment installation
Technical Data
NM 220V/5kA
IEC category/EN type
Nominal alternating voltage
Type 3 / class III
UN
230 V~
Rated load current
IL
Protection level L-N
Up
≤ 1,0 kV
Protection level L/N-PE
Up
≤ 1,5 kV
Response time
tA
≤ 25 ns
Nom. discharge current (8/20 μs) line-earth
In
5 kA
Nominal discharge current (8/20 μs) line-line
In
2,5 kA
Max. current (8/20 μs) line-line
Ig
8 kA
Max. current (8/20 μs) line-earth
Ig
15 kA
Operating temperature range
n
Protection against longitudinal and transverse
voltages
No leakage current to PE (leakage-current
n
free)
TU
16 A
-20 - +85 °C
Mounting
2x M3-screws (25mm)
Type of connection
2.5 (screw-type terminals)
Max. conductor cross section
2,5 mm²
Order Data
Article-No.
36 05 22
Dimension drawing, see pages 220 to 223
56
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for power supply systems
AC power supply
SPD type 3 for AC power supplies
EnerPro 230 SDU
Two-pole surge arrester for the protection of
electronical devices, for the retrofitting of deep
220 V flush-mounted boxes.
Basic circuit diagram
n
Applicable at the boundaries LPZ 1 - 2 and
higher
n
Test standard: IEC 61643-1 / EN 61643-11
Technical Data
EnerPro 230 SDU
IEC category/EN type
Type 3 / class III
Nominal alternating voltage
UN
230 V~
Rated load current
IL
Protection level L-N
Up
≤ 1,25 kV
Protection level L/N-PE
Up
≤ 1,5 kV
Response time
tA
< 25 ns
Nominal discharge current (8/20)
In
2,5 kA
Max. impulse discharge current (8/20)
Operating temperature range
Imax
TU
n
Acoustic failure signal
n
Including disconnection mechanism
16 A
5 kA
-20 - +80 °C
Type of connection
3-adrig
Mounting type
Installation in 230V Flush sockets
Order Data
Article-No.
24 00 02
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
57
Surge protection for power supply systems
DC power supply
58
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for power supply systems
DC power supply
Lightning current arrester type 1 for DC power supplies
SPD type 2 for DC power supplies
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
59
Surge protection for power supply systems
DC power supply
Lightning current arrester type 1 for DC power supplies
PowerPro PV 800
When applied in PV installations, these devices
are placed inside the connection box of the solar
generator and on the DC side of the inverter.
Basic circuit diagram
+
PE
-
n
Two-pole DC combined modular arrester, class
I and II.
n
Applicable at the LPZ transition point 0A-1
and higher
n
Test standard: IEC 61643-1 / EN 61643-11
Technical Data
PP PV 800
IEC category/EN type
Type 1 + 2 / class I + II
Type 1 + 2 / class I + II
UocSTC
800 V=
800 V=
PV voltage
PP PV 800/FM
Max. continuous operating voltage DC
Uc
850 V=
850 V=
Protection level at In
Up
≤ 2,2 kV
≤ 2,2 kV
Protection level at 5 kA
Up
≤ 1,8 kV
≤ 1,8 kV
Response time
tA
≤ 25 ns
≤ 25 ns
Lightning impulse current (10/350 µs) per pole
Iimp
12,5 kA
12,5 kA
Max. impulse discharge current (8/20)
Imax
40 kA
40 kA
-40 - +80 °C
-40 - +80 °C
Min. conductor cross section at terminals
10 mm²
10 mm²
Max. conductor cross section
35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible
Max. connection torque for terminals
4,5 Nm
Enclosure material / colour
polycarbonate (halogen-free) UL 94-V0 / yellow
Degree of protection (IEC EN 60529)
IP 20
IP 20
Dimension (DIN 43880)
2 TE
2 TE
Operating temperature range
TU
n
Mounting on 35 mm DIN rail
n
Space required for installation: 36 mm (2 TE)
n
Optional remote signalling contact (FM)
4.5 Nm
FM contact / contact type
break contact
Switching capacity
250 V/2 A
Order Data
Article-No.
37 44 00
37 44 01
Accessories
Product
DAK 2x 16
Article-No.
17 01 10
Adapter to enable feed-through wiring (V-wiring) for all surge protection modules with only one clamp per
phase, such as PP PV 800 and 1000 and other SPDs for power supply systems.
Dimension drawing, see pages 220 to 223
60
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for power supply systems
DC power supply
Lightning current arrester type 1 for DC power supplies
PowerPro PV 1000
When applied in PV installations, these devices
are placed inside the connection box of the solar
generator and on the DC side of the inverter.
Basic circuit diagram
+
PE
-
n
Two-pole DC combined modular arrester, class
I and II.
n
Applicable at the LPZ transition point 0A-1
and higher
n
Test standard: IEC 61643-1 / EN 61643-11
Technical Data
PP PV 1000
IEC category/EN type
Type 1 + Type 2 (class I/class II)
Type 1 + Type 2 (class I/class II)
UocSTC
1000 V=
1000 V=
PV voltage
PP PV 1000/FM
Max. continuous operating voltage DC
Uc
1100 V=
1100 V=
Protection level at In
Up
≤ 4,2 kV
≤ 4,2 kV
Protection level at 5 kA
Up
≤ 3.5 kV
≤ 3.5 kV
Response time
tA
≤ 25 ns
≤ 25 ns
Lightning impulse current (10/350 µs) per pole
Iimp
12.5 kA
12.5 kA
Max. impulse discharge current (8/20)
Imax
40 kA
40 kA
-40 - +80 °C
-40 - +80 °C
Min. conductor cross section at terminals
10 mm²
10 mm²
Max. conductor cross section
35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible
Max. connection torque for terminals
4.5 Nm
Enclosure material / colour
polycarbonate (halogen-free) UL 94-V0 / yellow
Degree of protection (IEC EN 60529)
IP 20
IP 20
Dimension (DIN 43880)
3 TE
3 TE
Operating temperature range
TU
n
Optional remote signalling contact (FM)
n
Space required for installation: 54 mm (3 TE)
n
Mounting on 35 mm DIN rail
4.5 Nm
FM contact / contact type
break contact
Switching capacity
250 V/2 A
Order Data
Article-No.
37 44 02
37 44 03
Accessories
Product
DAK 2x 16
Article-No.
17 01 10
Adapter to enable feed-through wiring (V-wiring) for all surge protection modules with only one clamp per
phase, such as PP PV 800 and 1000 and other SPDs for power supply systems.
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
61
Surge protection for power supply systems
DC power supply
SPD type 2 for DC power supplies
Example photo
CT PV-T2/2-0
Fully pluggable surge protective device to be
used in photovoltaic systems. Suitable fuse-free
earthed photovoltaic applications with system
voltages up to 600 or 1000 V DC.
12
11 14
+
-
n
Mounting on 35 mm DIN rail
n
Enclosure material: thermoplastic with the
colors yellow and black
n
Inflammability class according to UL 94 V0
Optional remote changeover contact
n
Basic circuit diagram
n
Applicable at the boundaries LPZ 0B - 1 and
higher
n
Test standard: IEC 61643-1 / EN 61643-11
n
Degree of protection according to IEC EN
60529: IP 20
Technical Data
CT PV-T2/2-0/600
CT PV-T2/2-0/600-FM
CT PV-T2/2-0/1000
CT PV-T2/2-0/1000-FM
IEC category/EN type
Type 2 / class II
Type 2 / class II
Type 2 / class II
Type 2 / class II
≤ 600 V=
≤ 600 V=
≤ 1000 V=
≤ 1000 V=
Open-circuit voltage
UOC max.
Max. continuous operating voltage DC
Uc
600 V=
600 V=
1000 V=
1000 V=
Nominal discharge current (8/20)
In
15 kA
15 kA
15 kA
15 kA
30 kA
30 kA
30 kA
30 kA
Protection Level L+-L-
Up
3 kV
3 kV
5 kV
5 kV
Operating temperature range
TU
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
Max. impulse discharge current (8/20)
Imax
Min. conductor cross section at terminals
1.5mm² solid/flexible
Max. conductor cross section
35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible
Dimension (DIN 43880)
2 TE (36 mm)
2 TE (36 mm)
2 TE (36 mm)
2 TE (36 mm)
Max. operating voltage remote contact
250 V AC/125 V DC
250 V AC/125 V DC
Max. operating current remote contact
1 A AC/200 mA DC
1 A AC/200 mA DC
Order Data
96 02 20
96 02 21
Accessories
Product
CT PV-T2-600-M
CT PV-T2-1000-M
Article-No.
96 02 46
96 02 47
96 02 22
96 02 23
Example photo
Article-No.
Replacement protective plug for DC surge arresters typ 2.
Product available in 2nd half year 2012
62
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for power supply systems
DC power supply
SPD type 2 for DC power supplies
Example photo
CT PV-T2/2+1
Fully pluggable surge protective device to be
used in photovoltaic systems. Suitable fuse-free
earthed photovoltaic applications with system
voltages up to 600 or 1000 V DC.
12
11 14
+
PE
-
n
Mounting on 35 mm DIN rail
n
Enclosure material: thermoplastic with the
colors yellow and black
n
Inflammability class according to UL 94 V0
Optional remote changeover contact
n
Basic circuit diagram
n
Applicable at the boundaries LPZ 0B - 1 and
higher
n
Test standard: IEC 61643-1 / EN 61643-11
n
Degree of protection according to IEC EN
60529: IP 20
Technical Data
CT PV-T2/2+1/600
CT PV-T2/2+1/600-FM
CT PV-T2/2+1/1000
CT PV-T2/2+1/1000-FM
IEC category/EN type
Type 2 / class II
Type 2 / class II
Type 2 / class II
Type 2 / class II
≤ 600 V=
≤ 600 V=
≤ 1000 V=
≤ 1000 V=
Open-circuit voltage
UOC max.
Max. continuous operating voltage DC
Uc
600 V=
600 V=
1000 V=
1000 V=
Nominal discharge current (8/20)
In
15 kA
15 kA
15 kA
15 kA
30 kA
30 kA
30 kA
30 kA
Protection Level L+-L-
Up
3 kV
3 kV
5 kV
5 kV
Protection level L+/L--PE
Up
3 kV
3 kV
5 kV
5 kV
Operating temperature range
TU
Max. impulse discharge current (8/20)
Min. conductor cross section at terminals
Imax
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
Max. conductor cross section
35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible
Dimension (DIN 43880)
3 TE (54 mm)
3 TE (54 mm)
3 TE (54 mm)
3 TE (54 mm)
Max. operating voltage remote contact
250 V AC/125 V DC
250 V AC/125 V DC
Max. operating current remote contact
1 A AC/200 mA DC
1 A AC/200 mA DC
Order Data
Article-No.
96 02 24
96 02 25
Product
CT PV-T2-600-M
CT PV-T2-1000-M
Article-No.
96 02 46
96 02 47
96 02 26
96 02 27
Example photo
Accessories
Replacement protective plug for DC surge arresters typ 2.
Product available in 2nd half year 2012
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
63
Surge protection for power supply systems
DC power supply
SPD type 2 for DC power supplies
Example photo
CT PV-T2/2+GDT
Fully pluggable and leakage-free surge protective
arrester for the use in photovoltaic applications.
Suitable fuse-free earthed photovoltaic applications with system voltages up to 600 or 1000 V
DC.
12
11 14
+
PE
-
n
Degree of protection according to IEC EN
60529: IP 20
Inflammability class according to UL 94 V0
n
n
Optional remote changeover contact
Basic circuit diagram
n
Applicable at the boundaries LPZ 0B - 1 and
higher
n
Leakage current-free
n
Test standard: IEC 61643-1 / EN 61643-11
n
Mounting on 35 mm DIN rail
Technical Data
CT PV-T2/2+GDT/600
CT PV-T2/2+GDT/600-FM
CT PV-T2/2+GDT/1000
CT PV-T2/2+GDT/1000-FM
IEC category/EN type
Type 2 / class II
Type 2 / class II
Type 2 / class II
Type 2 / class II
≤ 600 V=
≤ 600 V=
≤ 1000 V=
≤ 1000 V=
Open-circuit voltage
UOC max.
Max. continuous operating voltage DC
Uc
600 V=
600 V=
1000 V=
1000 V=
Nominal discharge current (8/20)
In
15 kA
15 kA
15 kA
15 kA
30 kA
30 kA
30 kA
30 kA
Protection Level L+-L-
Up
3 kV
3 kV
5 kV
5 kV
Protection level L+/L--PE
Up
3 kV
3 kV
3,0 kV
3 kV
Operating temperature range
TU
Max. impulse discharge current (8/20)
Min. conductor cross section at terminals
Imax
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
1.5mm² solid/flexible
Max. conductor cross section
35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible 35mm² stranded/25mm² flexible
Dimension (DIN 43880)
3 TE (54 mm)
3 TE (54 mm)
3 TE (54 mm)
3 TE (54 mm)
Max. operating voltage remote contact
250 V AC/125 V DC
250 V AC/125 V DC
Max. operating current remote contact
1 A AC/200 mA DC
1 A AC/200 mA DC
Order Data
96 02 28
96 02 29
Product
CT PV-T2-600-M
CT PV-T2-GDT-M
Article-No.
96 02 46
96 02 48
Accessories
96 03 00
96 03 01
Example photo
Article-No.
Replacement protective plug for DC surge arresters typ 2.
Product available in 2nd half year 2012
64
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for power supply systems
Accessories
Accessories
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
65
Surge protection for power supply systems
Accessories
UAS 230-Tr
All-purpose acoustic signalling device with test
key for all surge protection devices with the nominal voltage of UN 230 V.
Basic circuit diagram
L
N
230V 50Hz
n
For monitoring of remote contacts of surge
protection devices
n
Mounting on 35 mm DIN rail
FM
FM
FM
Technical Data
UAS 230-Tr
Nominal alternating voltage
UN
230 V~
Max. continuous operating voltage DC
Uc
240 V=
Nominal current
IN
16 A
Max. power
530 (Relais) W
Coil resistance
26,9 Ω
Max. conductor cross section
Operating temperature range
50mm² mehr....
TU
-25 - +65 °C
Max. cross section of the remote signalling line
1,5 mm²
Degree of protection (IEC EN 60529)
IP 20
Enclosure material / colour
polycarbonate (halogen-free) UL 94-V0 / yellow
Mounting on
35 mm DIN rail (DIN EN 50 022)
Order Data
Article-No.
35 10 30
Dimension drawing, see pages 220 to 223
66
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for power supply systems
Accessories
All-purpose busbars
The all-purpose busbar is designed to connect
the earthing of all Leutron class II and III lightning
and surge voltage components which are placed
in a compact housing that can be snapped on
35 mm DIN rail (with multi-function terminals for
conductors and busbar connectors).
Basic circuit diagram
n
All-purpose busbar for multi-function terminals
n
For an optimal bridging of the grounding
terminals
n
Available in different lengths
Technical Data
KA1/2
KA1/4
KA1/6
KA1/8
Description
1 pole; 2 Kämme
1 pole; 4 Kämme
1 pole, 6 Kämme
1 pole; 8 Kämme
Net weight / pc
15 g
17 g
19 g
22 g
17 00 10
17 00 20
17 00 30
17 00 40
Order Data
Article-No.
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
67
The new arresters – interruption-free
and impedance-neutral plugging and
unplugging without interrupting the
signal
The two-part protection devices with a construction width of 17.5 mm cover
up to seven voltage types. Devices with a one-piece terminal block design
and a construction width of only 6.2 mm allow for a high packing density in
control cabinets.
Convincing application advantages thanks to a symbiosis of design
and optimized packing density – Leutron's new arresters for measuring
systems and automatic control devices
More versatile in use:
68
nOptimized basic modules for direct or indirect shield grounding
via gas discharge tubes
nOn pluggable surge protective devices the protection module can
be detached and replaced without interrupting the signal
nVersions for one pair of wires (1DA) with two signal lines and for
two pairs of wires (2DA) with four signal lines available
Surge protection
for measuring systems and automatic control devices
Leutron's two-piece arresters for measuring
systems and automatic control devices – for all
applications and voltage levels.
Surge protection
for measuring systems and
automatic control devices
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
69
Two-piece, pluggable surge arresters
New product line »Leutron Data«:
nVoltage levels from 50 V to 180 V DC available
nFrequency range: Dependent on the voltage level up to 25 MHz
Space-saving
installation width of only
18 mm required for up to
four single wires
Impedance-neutral
replacing of protection
modules
Contacting to
mounting rail with
lightning current carrying
capability
Wiring connection
up to 4 mm2 solid and
2,5 mm 2 flexible
Variable shield
grounding: Basic
modules for direct or
indirect shield grounding
via gas discharge tube
available
70
Surge protection
for measuring systems and automatic control devices
One-piece surge arresters
nVoltage levels from 50 V to 180 V DC available
nFrequency range: Dependent on the voltage level up to 25 MHz
Space-saving installation
width of only 6.2 mm
Contacting to
mounting rail with
lightning current carrying
capability
Wiring
connection up
to 4 mm2 solid and
2,5 mm 2 flexible
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
71
cross reference list to select the substituted Products
The cross reference list supports the selection of the new
MCR product line modules based on the previous wellknown products.
The new MCR product line, consist of a base part and a
pluggable module.
72
Substituted product nameSubstituted item number
DataPro2x1-SDSL-Tr
24 00 18
DP4x1-SDSL-Tr
24 00 20
DataPro2x1-24V-SDSL-Tr
24 00 24
DP2x1-12V/12V-0,3Ohm-Tr
26 12 12
DP2x1-24V/24V-0,3Ohm-Tr
26 24 24
DP2x1-36V/36V-0,3Ohm-Tr
26 36 36
DP2x1-RLC-Tr
27 00 00
IsoProData150V/150V-Tr
27 03 03
DP2x1-150V/150V-Tr
27 04 04
DP2x1-6V/6V-Tr
27 06 06
DP2x1-12V/12V-Tr
27 12 12
DP2x1-15V/15V-Tr
27 15 15
DP2x1-24V/24V-Tr
27 24 24
DP2x1-30V/30V-Tr
27 30 30
DP2x1-36V/36V-Tr
27 36 36
DP2x1-48V/48V-Tr
27 48 48
DP2x1-60V/60V-Tr
27 60 60
DP2x1-80V/80V-Tr
27 80 80
DP3x1-150V/150V-Tr
28 04 04
DP3x1-12V/12V-Tr
28 12 12
DP3x1-15V/15V-Tr
28 15 15
DP3x1-24V/24V-Tr
28 24 24
DP3x1-30V/30V-Tr
28 30 30
DP3x1-36V/36V-Tr
28 36 36
DP3x1-48V/48V-Tr
28 48 48
DP3x1-60V/60V-Tr
28 60 60
DP2x1-RLC/50V-Tr
28 70 50
IsoProData-Tr 27 30 02
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
cross reference list
for measuring systems and automatic control devices
ModulBasic
New MCR products, consisting of modul and basic part MP 1x2 5V-HF ST
MP Base 2x2-R
MP Base 2x2-R
MP 2x2 5V-HF ST
MP 1x2 24V-HF ST
MP Base 2x2-R
MP 1x2 GDT+12V-Ad-Ad-Pg ST MP Base 2x2-R
MP 1x2 GDT+24V-Ad-Ad-Pg ST MP Base 2x2-R
MP 1x2 GDT+36V Ad-Ad-Pg ST
MP Base 2x2-R
MP Base 2x2-R
MP 1x2 GDT+180V-Ad-Pg ST
MP 1x2 GDT+180V-Ad-Ad-Pg ST MP Base 2x2-R
MP 1x2 GDT+180V-Ad-Ad-Pg ST MP Base 2x2-R
MP Base 2x2-R
MP 1x2 GDT+5V-Ad-Ad-Pg ST
MP 1x2 GDT+12V-Ad-Ad-Pg ST MP Base 2x2-R
MP 1x2 GDT+24V-Ad-Ad-Pg ST MP Base 2x2-R
MP 1x2 GDT+24V-Ad-Ad-Pg ST MP Base 2x2-R
MP 1x2 GDT+36V-Ad-Ad-Pg ST MP Base 2x2-R
MP 1x2 GDT+36V-Ad-Ad-Pg ST MP Base 2x2-R
MP 1x2 GDT+48V-Ad-Ad-Pg ST MP Base 2x2-R
MP 1x2 GDT+60V-Ad-Ad-Pg ST MP Base 2x2-R
MP 1x2 GDT+180V-Ad-Ad-Pg ST MP Base 2x2-R
MP 2x2 GDT+180V-Ad-Ad-Pg ST MP Base 2x2-R
MP 2x2 GDT+12V-Ad-Ad-Pg ST MP Base 2x2-R
MP 2x2 GDT+24V-Ad-Ad-Pg ST MP Base 2x2-R
MP 2x2 GDT+24V-Ad-Ad-Pg ST MP Base 2x2-R
MP 2x2 GDT+36V-Ad-Ad-Pg ST MP Base 2x2-R
MP 2x2 GDT+36V-Ad-Ad-Pg ST MP Base 2x2-R
MP 2x2 GDT+48V-Ad-Ad-Pg ST MP Base 2x2-R
MP 2x2 GDT+60V-Ad-Ad-Pg ST MP Base 2x2-R
MP Base 2x2-R
MP 1x2 GDT+48V-Ad-Pg ST
MP 1x2 GDT ST
MP Base
Item number modulItem number basic
97 10 52
97 00 00
97 10 50
97 00 00
97 10 53
97 00 00
97 00 47
97 00 00
97 00 48
97 00 00
97 00 49
97 00 00
97 00 38
97 00 00
97 00 52
97 00 00
97 00 52
97 00 00
97 00 46
97 00 00
97 00 47
97 00 00
97 00 48
97 00 00
97 00 48
97 00 00
97 00 49
97 00 00
97 00 49
97 00 00
97 00 50
97 00 00
97 00 51
97 00 00
97 00 52
97 00 00
97 00 45
97 00 00
97 00 40
97 00 00
97 00 41
97 00 00
97 00 41
97 00 00
97 00 42
97 00 00
97 00 42
97 00 00
97 00 43
97 00 00
97 00 44
97 00 00
97 00 36
97 00 00
97 00 10
97 00 02
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
73
Interface / SignalConnectionProtected linesProtection deviceItem no.Page
74
-20 mA, 4-20 mA
(also with HART)
screw terminals
screw terminals
screw terminals
screw terminals
4
2
2
2
MP 2x2 GDT+24V-Ad-Pg ST
MP 1x2 GDT+24V-Ad-Ad ST
MP RK GDT+24V-Ad-Pg
MP RK 24V-Ad-Pg
97 00 27
97 00 20
97 10 13
97 10 34
88
86
108
118
4-20 mA
(also with HART) acc. to NAMUR-Empfehlung
recommendationNE 21 or acc. EN 61000-4-5,
Open-circuit voltage 1 kV Ad-Pg
screw terminals
screw terminals
screw terminals
LSA
LSA
4
2
2
2
20
MP 2x2 GDT+24V-Ad-Ad ST
MP 1x2 GDT+24V-Ad-Ad ST
MP RK GDT+24V-Ad-Ad
DP 1LSA-24
DP 10LSA-24V
97 00 13
97 00 20
97 10 06
24 00 34
24 00 27
84
86
106
138
147
3/4-Signal Measurement
screw terminals
4
MP 2x2 GDT+24V-Ad-Pg ST
97 00 27
88
ADVANT
screw terminals
screw terminals
screw terminals
4
2
2
MP 2x2 GDT+5V-Ad-Ad-Pg ST
MP 1x2 GDT+5V-Ad-Ad-Pg ST
MP RK GDT+5V-Ad-Ad-Pg
97 00 39
97 00 46
97 10 18
92
94
110
Binary signals
screw terminals
screw terminals
4
2
MP 2x2 GDT+XXV-Ad-Pg ST
MP 1x2 GDT+XXV-Ad-Pg ST
97 00 25 - 97 00 31
97 00 32 - 97 00 38
89
91
screw terminals
screw terminals
LSA
LSA
2
2
2
20
MP RK GDT+XXV-Ad-Pg
MP RK XXV-Ad-Pg
DP 1LSA-XX
DP 10LSA-24V
97 10 11 - 97 10 17
97 10 32 - 97 10 38
24 00 31 - 24 00 39
24 00 27
108
116
138
147
Bitbus
screw terminals
screw terminals
4
2
MP 2x2 5V-HF ST
MP 1x2 5V-HF ST
97 10 50
97 10 52
98
99
BLN
(Building Level Network)
screw terminals
screw terminals
screw terminals
screw terminals
screw terminals
screw terminals
4
4
2
2
2
2
MP 2x2 GDT+12V-Ad-Ad ST
MP 2x2 GDT+48V-Ad-Ad ST
MP 1x2 GDT+12V-Ad-Ad ST
MP 1x2 GDT+48V-Ad-Ad ST
MP RK GDT+12V-Ad-Ad
MP RK GDT+48V-Ad-Ad
97 00 12
97 00 15
97 00 19
97 00 22
97 10 05
97 10 08
84
85
86
87
106
107
CAN-Bus
(data line only)
screw terminals
screw terminals
4
2
MP 2x2 5V-HF ST
MP 1x2 5V-HF ST
97 10 50
97 10 52
98
99
C-Bus
(Honeywell)
Data Highway Plus
screw terminals
screw terminals
screw terminals
screw terminals
4
2
4
2
MP 2x2 5V-HF ST
MP 1x2 5V-HF ST
MP 2x2 GDT+12V-Ad-Ad ST
MP 1x2 GDT+12V-Ad-Ad ST
97 10 50
97 10 52
97 00 12
97 00 19
98
99
84
86
Delta Net Peer Bus
screw terminals
screw terminals
4
2
MP 2x2 5V-HF ST
MP 1x2 5V-HF ST
97 10 50
97 10 52
98
99
Device Net
(data line only)
screw terminals
screw terminals
4
2
MP 2x2 5V-HF ST
MP 1x2 5V-HF ST
97 10 50
97 10 52
98
99
Dupline
screw terminals
2
MP 1x2 GDT+24V-Ad-Ad ST
97 00 20
86
E-Bus
(Honeywell)
screw terminals
screw terminals
4
2
MP 2x2 GDT+48V-Ad-Ad ST
MP 1x2 GDT+48V-Ad-Ad ST
97 00 15
97 00 22
85
111
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Selection Guide
for measuring systems and automatic control devices
Interface / SignalConnectionProtected linesProtection deviceItem no.Page
EIB
screw terminals
4
MP 2x2 GDT ST
97 00 07
80
screw terminals
2
MP 1x2 GDT ST
97 00 10
81
screw terminals
2
MP RK GDT
97 10 03
102
LSA
20
TelPro LSA-3EH230F1E-10kA
24 01 23
136
Electro acoustic system (ELA)
screw terminals
screw terminals
screw terminals
screw terminals
screw terminals
screw terminals
LSA
LSA
4
2
2
4
2
2
2
20
MP 2x2 GDT ST
MP 1x2 GDT ST
MP RK GDT
MP 2x2 GDT+180V-Ad-Pg ST
MP 1x2 GDT+180V-Ad-Pg ST
MP RK GDT+180V-Ad-Pg
DP 1LSA-110
DP 10LSA-110
97 00 07
97 00 10
97 10 03
97 00 31
97 00 38
97 10 17
24 00 39
24 01 40
80
80
102
89
91
109
139
147
ET 200
screw terminals
screw terminals
4
2
MP 2x2 5V-HF ST
MP 1x2 5V-HF ST
97 10 50
97 10 52
98
99
Fieldbus Foundation
screw terminals
screw terminals
screw terminals
LSA
4
2
2
20
MP 2x2 GDT+24V-Ad-Ad ST
MP 1x2 GDT+24V-Ad-Ad ST
MP RK GDT+24V-Ad-Ad
DP 10LSA-24V
97 00 13
97 00 20
97 10 06
24 00 27
84
86
106
147
FIPIO / FIPWAY
screw terminals
screw terminals
screw terminals
4
2
2
MP 2x2 GDT+24V-Ad-Ad ST
MP 1x2 GDT+24V-Ad-Ad ST
MP RK GDT+24V-Ad-Ad
97 00 13
97 00 20
97 10 06
84
86
106
FIP I/O
screw terminals
screw terminals
4
2
MP 2x2 5V-HF ST
MP 1x2 5V-HF ST
97 10 50
97 10 52
98
99
FSK
screw terminals
screw terminals
4
2
MP 2x2 5V-HF ST
MP 1x2 5V-HF ST
97 10 50
97 10 52
98
99
Genius I/O Bus
screw terminals
screw terminals
screw terminals
4
2
2
MP 2x2 GDT+12V-Ad-Ad ST
MP 1x2 GDT+12V-Ad-Ad ST
MP RK GDT+12V-Ad-Ad
97 00 12
97 00 19
97 10 05
84
86
106
DC power supply +24/30 V DC
screw terminals
2
DP2x1-RLC/50V-Tr
28 70 50
188
IEC-Bus (RS 486)
screw terminals
screw terminals
4
2
MP 2x2 5V-HF ST
MP 1x2 5V-HF ST
97 10 50
97 10 52
98
99
Industrial Ethernet
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
8
8
8
8 x 8
8 x 8
16 x 8
24 x 8
32 x 8
40 x 8
48 x 8
8
DP RJ45-CAT6-48V-Tr
DP RJ45 f/f
DP 1xRJ45-PoE-Alu
DP 8xRJ45-6V-WG
DP 1x8RJ45-19“
DP 2x8RJ45-19“
DP 3x8RJ45-19“
DP 4x8RJ45-19“
DP 5x8RJ45-19“
DP 6x8RJ45-19“
CPS+ 230Tel/Net
24 00 05
24 00 11
24 00 21
19 40 50
19 40 13
19 40 23
19 40 33
19 40 43
19 40 53
19 40 63
32 50 01
124
125
126
127
128
128
128
129
129
129
53
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
75
Interface / SignalConnectionProtected linesProtection deviceItem no.Page
INTERBUS-INLINE (I/O)
screw terminals
screw terminals
screw terminals
4
2
2
MP 2x2 GDT+48V-Ad-Ad ST
MP 1x2 GDT+48V-Ad-Ad ST
MP RK GDT+48V-Ad-Ad
97 00 15
97 00 22
97 10 08
85
87
107
INTERBUS-Loop
screw terminals
2
MP RK 24V-Ad-Pg
97 10 34
118
screw terminals
4
MP 2x2 5V-HF ST
97 10 50
98
Interbus INLINE Fernbus
screw terminals
2
MP 1x2 5V-HF ST
97 10 52
99
K-Bus
screw terminals
4
MP 2x2 GDT+24V-Ad-Ad ST
97 00 13
84
screw terminals
2
MP 1x2 GDT+24V-Ad-Ad ST
97 00 20
screw terminals
2
MP RK GDT+24V-Ad-Ad
97 10 06
106
KBR-Energy bus
screw terminals
4
MP 2x2 5V-HF ST
97 10 50
98
screw terminals
2
MP 1x2 5V-HF ST
97 10 52
99
KNX-Bus
screw terminals
4
MP 2x2 GDT ST
97 00 07
80
screw terminals
2
MP 1x2 GDT ST
97 00 10
80
screw terminals
2
MP RK GDT
97 10 03
102
LSA
20
TelPro LSA-3EH230F1E-10kA
24 01 23
136
LON
- TP/XF 78
screw terminals
4
MP 2x2 GDT+5V-Ad-Ad ST
97 00 11
84
screw terminals
2
MP 1x2 GDT+5V-Ad-Ad ST
97 00 18
86
screw terminals
2
MP RK GDT+5V-Ad-Ad
97 10 04
106
- TP/FTT10 und TP/LPT10
screw terminals
4
MP 2x2 GDT+48V-Ad-Ad ST
97 00 15
85
screw terminals
2
MP 1x2 GDT+48V-Ad-Ad ST
97 00 22
87
screw terminals
2
MP RK GDT+48V-Ad-Ad
97 10 08
107
- TP/FTT 10
screw terminals
4
MP 2x2 5V-HF ST
97 10 50
98
screw terminals
2
MP 1x2 5V-HF ST
97 10 52
99
LUXMATE-Bus
screw terminals
4
MP 2x2 GDT+24V-Ad-Ad ST
97 00 13
84
screw terminals
2
MP 1x2 GDT+24V-Ad-Ad ST
97 00 20
86
screw terminals
2
MP RK GDT+24V-Ad-Ad
97 10 06
106
M-Bus
screw terminals
4
MP 2x2 GDT+48V-Ad-Ad ST
97 00 15
85
screw terminals
2
MP 1x2 GDT+48V-Ad-Ad ST
97 00 22
87
screw terminals
2
MP RK GDT+48V-Ad-Ad
97 10 08
107
MODBUS
screw terminals
4
MP 2x2 5V-HF ST
97 10 50
98
screw terminals
2
MP 1x2 5V-HF ST
97 10 52
99
MPI Bus
screw terminals
4
MP 2x2 5V-HF ST
97 10 50
98
screw terminals
2
MP 1x2 5V-HF ST
97 10 52
99
N1 LAN
screw terminals
4
MP 2x2 5V-HF ST
97 10 50
98
screw terminals
2
MP 1x2 5V-HF ST
97 10 52
99
N2 Bus
screw terminals
4
MP 2x2 5V-HF ST
97 10 50
98
(Johnson Controls, LON, FTT 10)
screw terminals
2
MP 1x2 5V-HF ST
97 10 52
99
screw terminals
4
MP 2x2 GDT+24V-Ad-Ad-Pg ST 97 00 41
118
Optocoupler Interface
76
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Selection Guide
for measuring systems and automatic control devices
Interface / SignalConnectionProtected linesProtection deviceItem no.Page
screw terminals
2
MP 1x2 GDT+24V-Ad-Ad-Pg ST 97 00 48
94
screw terminals
2
MP RK GDT+24V-Ad-Ad-Pg
97 10 20
110
Procontic SC31
screw terminals
2
MP 2x2 GDT+12V-Ad-Pg ST
97 00 26
88
(RS 232)
screw terminals
4
MP 2x2 5V-HF ST
97 10 50
98
Procontic T200
(RS 422)
PROFIBUS-DP/FMS
screw terminals
4
MP 2x2 5V-HF ST
97 10 50
98
screw terminals
2
MP 1x2 5V-HF ST
97 10 52
99
PROFIBUS-PA
screw terminals
4
MP 2x2 GDT+24V-Ad-Ad ST
97 00 13
84
screw terminals
2
MP 1x2 GDT+24V-Ad-Ad ST
97 00 20
86
screw terminals
2
MP RK GDT+24V-Ad-Ad
97 10 06
106
LSA
2
DP 1LSA-C24FS-PTC
24 00 66
145
PROFIBUS SIMATIC NET
screw terminals
4
MP 2x2 5V-HF ST
97 10 50
98
screw terminals
2
MP 1x2 5V-HF ST
97 10 52
99
PSM-EG-RS 422
screw terminals
4
MP 2x2 5V-HF ST
97 10 50
98
PSM-EG-RS 485
screw terminals
4
MP 2x2 5V-HF ST
97 10 50
98
screw terminals
2
MP 1x2 5V-HF ST
97 10 52
99
Rackbus (RS 485)
screw terminals
4
MP 2x2 5V-HF ST
97 10 50
98
screw terminals
2
MP 1x2 5V-HF ST
97 10 52
99
R-Bus
screw terminals
4
MP 2x2 GDT+5V-Ad-Ad ST
97 00 11
84
screw terminals
2
MP 1x2 GDT+5V-Ad-Ad ST
97 00 18
86
screw terminals
2
MP RK GDT+5V-Ad-Ad
97 10 04
106
RS 485
screw terminals
4
MP 2x2 5V-HF ST
97 10 50
98
screw terminals
2
MP 1x2 5V-HF ST
97 10 52
99
LSA
2
DP 1LSA-C24FS-PTC
24 00 66
145
RS 422, V11
screw terminals
4
MP 2x2 5V-HF ST
97 10 50
98
screw terminals
2
MP 1x2 5V-HF ST
97 10 52
99
S-Bus
screw terminals
4
MP 2x2 5V-HF ST
97 10 50
98
screw terminals
2
MP 1x2 5V-HF ST
97 10 52
99
SafetyBUS p
screw terminals
4
MP 2x2 5V-HF ST
97 10 50
98
screw terminals
2
MP 1x2 5V-HF ST
97 10 52
99
SDLC
screw terminals
4
MP 2x2 5V-HF ST
97 10 50
98
screw terminals
2
MP 1x2 5V-HF ST
97 10 52
99
screw terminals
4
MP 2x2 GDT+5V-Ad-Ad ST
97 00 11
84
Securilan-LON-Bus
(LONWORKS Technology
screw terminals
2
MP 1x2 GDT+5V-Ad-Ad ST
97 00 18
86
standard bus based on Echelon)
screw terminals
2
MP RK GDT+5V-Ad-Ad
97 10 04
106
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
77
Selection Guide
for measuring systems and automatic control devices
Interface / SignalConnectionProtected linesProtection deviceItem no.Page
SIGMASYS
Screw connecter 4
MP 2x2 GDT+48V-Ad-Ad ST 97 00 15
85
Screw connecter 2
MP 1x2 GDT+48V-Ad-Ad ST 97 00 22
87
(Siemens fire alarm systems)
Screw connecter 2
MP RK GDT+48V-Ad-Ad
97 10 08
110
Screw connecter 4
MP 2x2 GDT+48V-Ad-Pg ST 97 00 29
89
Screw connecter 2
MP 1x2 GDT+48V-Ad-Pg ST 97 00 36
91
Screw connecter 2
MP RK GDT+48V-Ad-Pg
97 10 15
109
SINEC L1
Screw connecter 4
MP 2x2 5V-HF ST
97 10 50
98
Screw connecter 2
MP 1x2 5V-HF ST
97 10 52
99
SINEC L2
Screw connecter 4
MP 2x2 5V-HF ST
97 10 50
98
Screw connecter 2
MP 1x2 5V-HF ST
97 10 52
99
Screw connecter 4
MP 2x2 GDT+12V-Ad-Pg ST 97 00 26
88
SS97 SIN/X (RS 232)
Screw connecter 2
MP 1x2 GDT+12V-Ad-Pg ST 97 00 33
90
Screw connecter 2
MP RK GDT+12V-Ad-Pg
97 10 12
108
SUCONET
Screw connecter 4
MP 2x2 GDT+5V-Ad-Ad ST
97 00 11
84
Screw connecter 2
MP 1x2 GDT+5V-Ad-Ad ST
97 00 18
86
Screw connecter 2
MP RK GDT+5V-Ad-Ad
97 10 04
106
Temperature measuring
Screw connecter 4
MP 2x2 GDT+5V-Ad-Pg ST
97 00 25
88
PT 100, PT 1000, Ni 1000, NTC, PTC
Screw connecter 2
MP 1x2 GDT+5V-Ad-Pg ST
97 00 32
90
Screw connecter 2
MP RK GDT+5V-Ad-Pg
97 10 11
108
TTL
Screw connecter 4
MP 2x2 GDT+12V-Ad-Pg ST 97 00 26
88
Screw connecter 2
MP 1x2 GDT+12V-Ad-Pg ST 97 00 33
90
Screw connecter 2
MP RK GDT+12V-Ad-Pg
97 10 12
108
TTY 4 - 20 mA
Screw connecter 4
MP 2x2 GDT+24V-Ad-Pg ST 97 00 27
88
Screw connecter 2
MP 1x2 GDT+24V-Ad-Pg ST 97 00 34
90
Screw connecter 2
MP RK GDT+24V-Ad-Pg
97 10 13108
Screw connecter 2
MP RK 24V-Ad-Pg
97 10 34118
78
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for measuring systems and automatic control devices
Pluggable SPD for MCR applications
Pluggable SPD with high discharge cappability for MCR applications
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
79
Surge protection for measuring systems and automatic control devices
Pluggable SPD for MCR applications
Pluggable SPD with high discharge cappability for MCR applications
Example photo
MP 2x2 GDT ST
Fully pluggable two-parts lightning current
discharge arrester for signal lines. The protective
module can be removed for test or maintenance
purposes without changeing the line impedance
and therefore influencing the signal level. The
base part can remain in the instalation without
manipulating or removing any wire.
1
2
5
6
10
9
Basic circuit diagram
*
3
4
7
8
11
12
n
Protective circuit for 4 signal lines without reference
to ground potential
n
Protective plug can be removed without changing
the line impedance or influencing the useful signal
n
Test standard: IEC 61643-21 / EN 61643-21
Technical Data
MP 2x2 GDT ST
IEC category/EN type
D1 / C2 / C1 / C3
Nominal voltage
UN
180 V
Max. continous operating voltage (DC/AC)
Uc
180/120 V
Nominal current
IN
2A
Iimp
2,5 kA
C2 nominal discharge current (8/20 µs) total (In)
In
20 kA
C2 nominal discharge current (8/20 µs) per line
In
10 kA
D1 lightning impulse current (10/350 μs) per wire
Prorection level line-line at Iimp D1
Up
≤ 550 V
Protection level line-earth at Iimp D1
Up
≤ 550 V
Protection level line-line at 1 kV/μs C3
Up
≤ 500 V
Protection level line-Pg at 1 kV/μs C3
Up
≤ 500 V
Series resistance per line
Max. operating frequency (3 dB)
0 Ω
fG
typ. 100 MHz
0.2-4.0/0.2-2.5 mm² / 24-12
Conductor cross section (solid/stranded/AWG)
Operating temperature range
n
Applicable at the boundaries LPZ 0A - 1 and higher
n
Mounting on 35 mm DIN rail
n
Enclosure material: thermoplastic
n
Space required for installation: 17.5 mm
TU
-40 - +80 °C
Inflammability class according to UL 94
V0
Degree of protection (IEC EN 60529)
IP 20
Order Data
Article-No.
97 00 07
Accessories
Product
MP Base 2x2
MP Base 2x2 GDT
Article-No.
97 00 03
97 00 04
Different base parts provide either direct or indirect earthing of the signal shielding: The MP Base 2x2
has the shield connectors 9/10 (GND) linked directly to the DIN rail and to the earth connector. The MP
Base 2x2 GDT has a gas discharge tube linked between the shield connectors 9/10 (GND) and the DIN
rail and erath connector. Therefore a galvanic insulation between the signal shield and the earth connection (PE) can be reached.
Product available in 2nd half year 2012
80
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for measuring systems and automatic control devices
Pluggable SPD for MCR applications
Pluggable SPD with high discharge cappability for MCR applications
Example photo
MP 1x2 GDT ST
Basic circuit diagram
Fully pluggable two-parts lightning current
discharge arrester for signal lines. The protective
module can be removed for test or maintenance
purposes without changeing the line impedance
and therefore influencing the signal level. The
base part can remain in the instalation without
manipulating or removing any wire.
1
2
5
6
n
Protective circuit for 2 signal lines without reference
to ground potential
n
Protective plug can be removed without changing
the line impedance or influencing the useful signal
n
Test standard: IEC 61643-21 / EN 61643-21
10
9
*
4
3
Technical Data
n
Applicable at the boundaries LPZ 0A - 1 and higher
n
Mounting on 35 mm DIN rail
n
Enclosure material: thermoplastic
n
Space required for installation: 17.5 mm
MP 1x2 GDT ST
IEC category/EN type
D1 / C2 / C1 / C3
Nominal voltage
UN
180 V
Max. continous operating voltage (DC/AC)
Uc
180/120 V
Nominal current
IN
2A
Iimp
2,5 kA
C2 nominal discharge current (8/20 µs) total (In)
In
20 kA
C2 nominal discharge current (8/20 µs) per line
In
10 kA
D1 lightning impulse current (10/350 μs) per wire
Prorection level line-line at Iimp D1
Up
≤ 550 V
Protection level line-earth at Iimp D1
Up
≤ 550 V
Protection level line-line at 1 kV/μs C3
Up
≤ 500 V
Protection level line-Pg at 1 kV/μs C3
Up
≤ 500 V
Series resistance per line
0Ω
Max. operating frequency (3 dB)
fG
0.2-4.0/0.2-2.5 mm² / 24-12
Conductor cross section (solid/stranded/AWG)
Operating temperature range
typ. 100 MHz
TU
-40 - +80 °C
Inflammability class according to UL 94
V0
Degree of protection (IEC EN 60529)
IP 20
Order Data
Article-No.
97 00 10
Accessories
Product
MP Base 2x2
MP Base 2x2 GDT
Article-No.
97 00 03
97 00 04
Different base parts provide either direct or indirect earthing of the signal shielding: The MP Base 2x2
has the shield connectors 9/10 (GND) linked directly to the DIN rail and to the earth connector. The MP
Base 2x2 GDT has a gas discharge tube linked between the shield connectors 9/10 (GND) and the DIN
rail and erath connector. Therefore a galvanic insulation between the signal shield and the earth connection (PE) can be reached.
Product available in 2nd half year 2012
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
81
Surge protection for measuring systems and automatic control devices
Pluggable SPD for MCR applications
82
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for measuring systems and automatic control devices
Pluggable SPD for MCR applications
Pluggable SPD with high discharge cappability
and low protection level for MCR applications
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
83
Surge protection for measuring systems and automatic control devices
Pluggable SPD for MCR applications
Pluggable SPD with high discharge cappability and low protection level for MCR applications
Example photo
MP 2x2 GDT/Ad-Ad ST
Fully pluggable two-parts combined surge
arrester for signal lines. The protective module
can be removed for test or maintenance purposes
without changeing the line impedance and therefore influencing the signal level. The base part
can remain in the instalation without manipulating
or removing any wire.
1
2
5
6
10
9
Basic circuit diagram
*
3
4
7
8
11
12
n
Protective circuit for 4 signal lines without reference
to ground potential
n
Protective plug can be removed without changing
the line impedance or influencing the useful signal
n
Test standard: IEC 61643-21 / EN 61643-21
n
Applicable at the boundaries LPZ 0A - 2 and higher
n
Mounting on 35 mm DIN rail
n
Enclosure material: thermoplastic
n
Space required for installation: 17.5 mm
Technical Data
MP 2x2 GDT+5V-Ad-Ad ST
MP 2x2 GDT+12V-Ad-Ad ST
MP 2x2 GDT+24V-Ad-Ad ST
IEC category/EN type
D1 / C2 / C1 / C3
D1 / C2 / C1 / C3
D1 / C2 / C1 / C3
MP 2x2 GDT+36V-Ad-Ad ST
D1 / C2 / C1 / C3
5V
12 V
24 V
36 V
Nominal voltage
UN
Max. continous operating voltage (DC/AC)
Uc
6/4 V
15/11 V
33/23 V
45/32 V
Nominal current
IN
0,5 A
0,5 A
0,5 A
0,5 A
Iimp
2,5 kA
2,5 kA
2,5 kA
2,5 kA
C2 nominal discharge current (8/20 µs) total (In)
In
20 kA
20 kA
20 kA
20 kA
C2 nominal discharge current (8/20 µs) per line
In
10 kA
10 kA
10 kA
10 kA
D1 lightning impulse current (10/350 μs) per wire
Prorection level line-line at Iimp D1
Up
≤ 25 V
≤ 26 V
≤ 52 V
≤ 68 V
Protection level line-earth at Iimp D1
Up
≤ 550 V
≤ 550 V
≤ 550 V
≤ 550 V
Protection level line-line at 1 kV/μs C3
Up
≤ 10 V
≤ 19 V
≤ 45 V
≤ 58 V
Protection level line-Pg at 1 kV/μs C3
Up
≤ 500 V
≤ 500 V
≤ 500 V
≤ 500 V
2,2 Ω
2,2 Ω
2,2 Ω
2,2 Ω
fG
typ. 1,0 MHz
typ. 3,0 MHz
typ. 6,0 MHz
typ. 8,0 MHz
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
TU
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
Series resistance per line
Max. operating frequency (3 dB)
Conductor cross section (solid/stranded/AWG)
Operating temperature range
Inflammability class according to UL 94
V0
V0
V0
V0
Degree of protection (IEC EN 60529)
IP 20
IP 20
IP 20
IP 20
97 00 11
97 00 12
97 00 13
97 00 14
Order Data
Article-No.
Product available in 2nd half year 2012
84
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for measuring systems and automatic control devices
Pluggable SPD for MCR applications
Technical Data
MP 2x2 GDT+48V-Ad-Ad ST
MP 2x2 GDT+60V-Ad-Ad ST
IEC category/EN type
D1 / C2 / C1 / C3
D1 / C2 / C1 / C3
MP 2x2 GDT+180V-Ad-Ad ST
D1 / C2 / C1 / C3
48 V
60 V
180 V
Nominal voltage
UN
Max. continous operating voltage (DC/AC)
Uc
54/38 V
70/49 V
180/120 V
Nominal current
IN
0,5 A
0,5 A
0,5 A
D1 lightning impulse current (10/350 μs) per wire
Iimp
2,5 kA
2,5 kA
2,5 kA
C2 nominal discharge current (8/20 µs) total (In)
In
20 kA
20 kA
20 kA
C2 nominal discharge current (8/20 µs) per line
In
10 kA
10 kA
10 kA
Prorection level line-line at Iimp D1
Up
≤ 80 V
≤ 110 V
≤ 270 V
Protection level line-earth at Iimp D1
Up
≤ 550 V
≤ 550 V
≤ 550 V
Protection level line-line at 1 kV/μs C3
Up
≤ 70 V
≤ 90 V
≤ 250 V
Protection level line-Pg at 1 kV/μs C3
Up
≤ 500 V
≤ 500 V
≤ 500 V
2,2 Ω
2,2 Ω
2,2 Ω
fG
typ. 10 MHz
typ. 12 MHz
typ. 25 MHz
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
TU
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
Series resistance per line
Max. operating frequency (3 dB)
Conductor cross section (solid/stranded/AWG)
Operating temperature range
Inflammability class according to UL 94
V0
V0
V0
Degree of protection (IEC EN 60529)
IP 20
IP 20
IP 20
97 00 15
97 00 16
97 00 17
Product
MP Base 2x2-R
MP Base 2x2-R GDT
Article-No.
97 00 00
97 00 01
Order Data
Article-No.
Accessories
Different base parts provide either direct or indirect earthing of the signal shielding: The MP Base 2x2-R
has the shield connectors 9/10 (GND) linked directly to the DIN rail and to the earth connector. The MP
Base 2x2-R GDT has a gas discharge tube linked between the shield connectors 9/10 (GND) and the DIN
rail and erath connector. Therefore a galvanic insulation between the signal shield and the earth connection (PE) can be reached.
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
85
Surge protection for measuring systems and automatic control devices
Pluggable SPD for MCR applications
Pluggable SPD with high discharge cappability and low protection level for MCR applications
Example photo
MP 1x2 GDT/Ad-Ad ST
Basic circuit diagram
Fully pluggable two-parts combined surge
arrester for signal lines. The protective module
can be removed for test or maintenance purposes
without changeing the line impedance and therefore influencing the signal level. The base part
can remain in the instalation without manipulating
or removing any wire.
1
2
5
6
n
Protective circuit for 2 signal lines without reference
to ground potential
n
Protective plug can be removed without changing
the line impedance or influencing the useful signal
n
Test standard: IEC 61643-21 / EN 61643-21
10
9
*
4
3
n
Applicable at the boundaries LPZ 0A - 2 and higher
n
Mounting on 35 mm DIN rail
n
Enclosure material: thermoplastic
n
Space required for installation: 17.5 mm
Technical Data
MP 1x2 GDT+5V-Ad-Ad ST
MP 1x2 GDT+12V-Ad-Ad ST
MP 1x2 GDT+24V-Ad-Ad ST
IEC category/EN type
D1 / C2 / C1 / C3
D1 / C2 / C1 / C3
D1 / C2 / C1 / C3
MP 1x2 GDT+36V-Ad-Ad ST
D1 / C2 / C1 / C3
5V
12 V
24 V
36 V
Nominal voltage
UN
Max. continous operating voltage (DC/AC)
Uc
6/4 V
15/11 V
33/23 V
45/32 V
Nominal current
IN
0,5 A
0,5 A
0,5 A
0,5 A
Iimp
2,5 kA
2,5 kA
2,5 kA
2,5 kA
C2 nominal discharge current (8/20 µs) total (In)
In
20 kA
20 kA
20 kA
20 kA
C2 nominal discharge current (8/20 µs) per line
In
10 kA
10 kA
10 kA
10 kA
D1 lightning impulse current (10/350 μs) per wire
Prorection level line-line at Iimp D1
Up
≤ 25 V
≤ 26 V
≤ 52 V
≤ 68 V
Protection level line-earth at Iimp D1
Up
≤ 550 V
≤ 550 V
≤ 550 V
≤ 550 V
Protection level line-line at 1 kV/μs C3
Up
≤ 10 V
≤ 19 V
≤ 45 V
≤ 58 V
Protection level line-Pg at 1 kV/μs C3
Up
≤ 500 V
≤ 500 V
≤ 500 V
≤ 500 V
2,2 Ω
2,2 Ω
2,2 Ω
2,2 Ω
fG
typ. 1,0 MHz
typ. 3,0 MHz
typ. 6,0 MHz
typ. 8,0 MHz
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
TU
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
Series resistance per line
Max. operating frequency (3 dB)
Conductor cross section (solid/stranded/AWG)
Operating temperature range
Inflammability class according to UL 94
V0
V0
V0
V0
Degree of protection (IEC EN 60529)
IP 20
IP 20
IP 20
IP 20
97 00 18
97 00 19
97 00 20
97 00 21
Order Data
Article-No.
Product available in 2nd half year 2012
86
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for measuring systems and automatic control devices
Pluggable SPD for MCR applications
Technical Data
MP 1x2 GDT+48V-Ad-Ad ST
MP 1x2 GDT+60V-Ad-Ad ST
IEC category/EN type
D1 / C2 / C1 / C3
D1 / C2 / C1 / C3
MP 1x2 GDT+180V-Ad-Ad ST
D1 / C2 / C1 / C3
48 V
60 V
180 V
Nominal voltage
UN
Max. continous operating voltage (DC/AC)
Uc
54/38 V
70/49 V
180/120 V
Nominal current
IN
0,5 A
0,5 A
0,5 A
D1 lightning impulse current (10/350 μs) per wire
Iimp
2,5 kA
2,5 kA
2,5 kA
C2 nominal discharge current (8/20 µs) total (In)
In
20 kA
20 kA
20 kA
C2 nominal discharge current (8/20 µs) per line
In
10 kA
10 kA
10 kA
Prorection level line-line at Iimp D1
Up
≤ 80 V
≤ 110 V
≤ 270 V
Protection level line-earth at Iimp D1
Up
≤ 550 V
≤ 550 V
≤ 550 V
Protection level line-line at 1 kV/μs C3
Up
≤ 70 V
≤ 90 V
≤ 250 V
Protection level line-Pg at 1 kV/μs C3
Up
≤ 500 V
≤ 500 V
≤ 500 V
2,2 Ω
2,2 Ω
2,2 Ω
fG
typ. 10 MHz
typ. 12 MHz
typ. 25 MHz
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
TU
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
Series resistance per line
Max. operating frequency (3 dB)
Conductor cross section (solid/stranded/AWG)
Operating temperature range
Inflammability class according to UL 94
V0
V0
V0
Degree of protection (IEC EN 60529)
IP 20
IP 20
IP 20
97 00 22
97 00 23
97 00 24
Product
MP Base 2x2-R
MP Base 2x2-R GDT
Article-No.
97 00 00
97 00 01
Order Data
Article-No.
Accessories
Different base parts provide either direct or indirect earthing of the signal shielding: The MP Base 2x2-R
has the shield connectors 9/10 (GND) linked directly to the DIN rail and to the earth connector. The MP
Base 2x2-R GDT has a gas discharge tube linked between the shield connectors 9/10 (GND) and the DIN
rail and erath connector. Therefore a galvanic insulation between the signal shield and the earth connection (PE) can be reached.
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
87
Surge protection for measuring systems and automatic control devices
Pluggable SPD for MCR applications
Pluggable SPD with high discharge cappability and low protection level for MCR applications
Example photo
MP 2x2 GDT/Ad-Pg ST
Fully pluggable two-parts combined surge
arrester for signal lines. The protective module
can be removed for test or maintenance purposes
without changeing the line impedance and therefore influencing the signal level. The base part
can remain in the instalation without manipulating
or removing any wire.
1
2
5
6
10
9
Basic circuit diagram
*
3
4
7
8
11
12
n
Protective circuit for 4 signal lines with common
ground
n
Protective plug can be removed without changing
the line impedance or influencing the useful signal
n
Test standard: IEC 61643-21 / EN 61643-21
n
Applicable at the boundaries LPZ 0A - 2 and higher
n
Mounting on 35 mm DIN rail
n
Enclosure material: thermoplastic
n
Space required for installation: 17.5 mm
Technical Data
MP 2x2 GDT+5V-Ad-Pg ST
MP 2x2 GDT+12V-Ad-Pg ST
MP 2x2 GDT+24V-Ad-Pg ST
IEC category/EN type
D1 / C2 / C1 / C3
D1 / C2 / C1 / C3
D1 / C2 / C1 / C3
MP 2x2 GDT+36V-Ad-Pg ST
D1 / C2 / C1 / C3
5V
12 V
24 V
36 V
Nominal voltage
UN
Max. continous operating voltage (DC/AC)
Uc
6/4 V
15/11 V
33/23 V
45/32 V
Nominal current
IN
0,5 A
0,5 A
0,5 A
0,5 A
Iimp
2,5 kA
2,5 kA
2,5 kA
2,5 kA
C2 nominal discharge current (8/20 µs) total (In)
In
20 kA
20 kA
20 kA
20 kA
C2 nominal discharge current (8/20 µs) per line
In
10 kA
10 kA
10 kA
10 kA
D1 lightning impulse current (10/350 μs) per wire
Prorection level line-line at Iimp D1
Up
≤ 29 V
≤ 50 V
≤ 102 V
≤ 135 V
Protection level line-earth at Iimp D1
Up
≤ 27 V
≤ 37 V
≤ 66 V
≤ 85 V
Protection level line-line at 1 kV/μs C3
Up
≤ 20 V
≤ 38 V
≤ 90 V
≤ 116 V
Protection level line-Pg at 1 kV/μs C3
Up
≤ 10 V
≤ 19 V
≤ 45 V
≤ 58 V
2,2 Ω
2,2 Ω
2,2 Ω
2,2 Ω
fG
typ. 1,0 MHz
typ. 3,0 MHz
typ. 6,0 MHz
typ. 8,0 MHz
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
TU
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
Series resistance per line
Max. operating frequency (3 dB)
Conductor cross section (solid/stranded/AWG)
Operating temperature range
Inflammability class according to UL 94
V0
V0
V0
V0
Degree of protection (IEC EN 60529)
IP 20
IP 20
IP 20
IP 20
97 00 25
97 00 26
97 00 27
97 00 28
Order Data
Article-No.
Product available in 2nd half year 2012
88
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for measuring systems and automatic control devices
Pluggable SPD for MCR applications
Technical Data
MP 2x2 GDT+48V-Ad-Pg ST
MP 2x2 GDT+60V-Ad-Pg ST
IEC category/EN type
D1 / C2 / C1 / C3
D1 / C2 / C1 / C3
MP 2x2 GDT+180V-Ad-Pg ST
D1 / C2 / C1 / C3
48 V
60 V
180 V
Nominal voltage
UN
Max. continous operating voltage (DC/AC)
Uc
54/38 V
70/49 V
180/120 V
Nominal current
IN
0,5 A
0,5 A
0,5 A
D1 lightning impulse current (10/350 μs) per wire
Iimp
2,5 kA
2,5 kA
2,5 kA
C2 nominal discharge current (8/20 µs) total (In)
In
20 kA
20 kA
20 kA
C2 nominal discharge current (8/20 µs) per line
In
10 kA
10 kA
10 kA
Prorection level line-line at Iimp D1
Up
≤ 160 V
≤ 220 V
≤ 520 V
Protection level line-earth at Iimp D1
Up
≤ 95 V
≤ 125 V
≤ 300 V
Protection level line-line at 1 kV/μs C3
Up
≤ 140 V
≤ 180 V
≤ 500 V
Protection level line-Pg at 1 kV/μs C3
Up
≤ 70 V
≤ 90 V
≤ 250 V
2,2 Ω
2,2 Ω
2,2 Ω
fG
typ. 10 MHz
typ. 12 MHz
typ. 25 MHz
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
TU
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
Series resistance per line
Max. operating frequency (3 dB)
Conductor cross section (solid/stranded/AWG)
Operating temperature range
Inflammability class according to UL 94
V0
V0
V0
Degree of protection (IEC EN 60529)
IP 20
IP 20
IP 20
97 00 29
97 00 30
97 00 31
Product
MP Base 2x2-R
MP Base 2x2-R GDT
Article-No.
97 00 00
97 00 01
Order Data
Article-No.
Accessories
Different base parts provide either direct or indirect earthing of the signal shielding: The MP Base 2x2-R
has the shield connectors 9/10 (GND) linked directly to the DIN rail and to the earth connector. The MP
Base 2x2-R GDT has a gas discharge tube linked between the shield connectors 9/10 (GND) and the DIN
rail and erath connector. Therefore a galvanic insulation between the signal shield and the earth connection (PE) can be reached.
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
89
Surge protection for measuring systems and automatic control devices
Pluggable SPD for MCR applications
Pluggable SPD with high discharge cappability and low protection level for MCR applications
Example photo
MP 1x2 GDT/Ad-Pg ST
Basic circuit diagram
Fully pluggable two-parts combined surge
arrester for signal lines. The protective module
can be removed for test or maintenance purposes
without changeing the line impedance and therefore influencing the signal level. The base part
can remain in the instalation without manipulating
or removing any wire.
1
2
5
6
n
Protective circuit for 2 signal lines with common
ground
n
Protective plug can be removed without changing
the line impedance or influencing the useful signal
n
Test standard: IEC 61643-21 / EN 61643-21
10
9
*
4
3
n
Applicable at the boundaries LPZ 0A - 2 and higher
n
Mounting on 35 mm DIN rail
n
Enclosure material: thermoplastic
n
Space required for installation: 17.5 mm
Technical Data
MP 1x2 GDT+5V-Ad-Pg ST
MP 1x2 GDT+12V-Ad-Pg ST
MP 1x2 GDT+24V-Ad-Pg ST
IEC category/EN type
D1 / C2 / C1 / C3
D1 / C2 / C1 / C3
D1 / C2 / C1 / C3
MP 1x2 GDT+36V-Ad-Pg ST
D1 / C2 / C1 / C3
5V
12 V
24 V
36 V
Nominal voltage
UN
Max. continous operating voltage (DC/AC)
Uc
6/4 V
15/11 V
33/23 V
45/32 V
Nominal current
IN
0,5 A
0,5 A
0,5 A
0,5 A
Iimp
2,5 kA
2,5 kA
2,5 kA
2,5 kA
C2 nominal discharge current (8/20 µs) total (In)
In
20 kA
20 kA
20 kA
20 kA
C2 nominal discharge current (8/20 µs) per line
In
10 kA
10 kA
10 kA
10 kA
D1 lightning impulse current (10/350 μs) per wire
Prorection level line-line at Iimp D1
Up
≤ 29 V
≤ 50 V
≤ 102 V
≤ 135 V
Protection level line-earth at Iimp D1
Up
≤ 27 V
≤ 37 V
≤ 66 V
≤ 85 V
Protection level line-line at 1 kV/μs C3
Up
≤ 20 V
≤ 38 V
≤ 90 V
≤ 116 V
Protection level line-Pg at 1 kV/μs C3
Up
≤ 10 V
≤ 19 V
≤ 45 V
≤ 58 V
2,2 Ω
2,2 Ω
2,2 Ω
2,2 Ω
fG
typ. 1,0 MHz
typ. 3,0 MHz
typ. 6,0 MHz
typ. 8,0 MHz
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
TU
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
Series resistance per line
Max. operating frequency (3 dB)
Conductor cross section (solid/stranded/AWG)
Operating temperature range
Inflammability class according to UL 94
V0
V0
V0
V0
Degree of protection (IEC EN 60529)
IP 20
IP 20
IP 20
IP 20
97 00 32
97 00 33
97 00 34
97 00 35
Order Data
Article-No.
Product available in 2nd half year 2012
90
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for measuring systems and automatic control devices
Pluggable SPD for MCR applications
Technical Data
MP 1x2 GDT+48V-Ad-Pg ST
MP 1x2 GDT+60V-Ad-Pg ST
IEC category/EN type
D1 / C2 / C1 / C3
D1 / C2 / C1 / C3
MP 1x2 GDT+180V-Ad-Pg ST
D1 / C2 / C1 / C3
48 V
60 V
180 V
Nominal voltage
UN
Max. continous operating voltage (DC/AC)
Uc
54/38 V
70/49 V
180/120 V
Nominal current
IN
0,5 A
0,5 A
0,5 A
D1 lightning impulse current (10/350 μs) per wire
Iimp
2,5 kA
2,5 kA
2,5 kA
C2 nominal discharge current (8/20 µs) total (In)
In
20 kA
20 kA
20 kA
C2 nominal discharge current (8/20 µs) per line
In
10 kA
10 kA
10 kA
Prorection level line-line at Iimp D1
Up
≤ 160 V
≤ 220 V
≤ 520 V
Protection level line-earth at Iimp D1
Up
≤ 95 V
≤ 125 V
≤ 300 V
Protection level line-line at 1 kV/μs C3
Up
≤ 140 V
≤ 180 V
≤ 500 V
Protection level line-Pg at 1 kV/μs C3
Up
≤ 70 V
≤ 90 V
≤ 250 V
2,2 Ω
2,2 Ω
2,2 Ω
fG
typ. 10 MHz
typ. 12 MHz
typ. 25 MHz
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
TU
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
Series resistance per line
Max. operating frequency (3 dB)
Conductor cross section (solid/stranded/AWG)
Operating temperature range
Inflammability class according to UL 94
V0
V0
V0
Degree of protection (IEC EN 60529)
IP 20
IP 20
IP 20
97 00 36
97 00 37
97 00 38
Product
MP Base 2x2-R
MP Base 2x2-R GDT
Article-No.
97 00 00
97 00 01
Order Data
Article-No.
Accessories
Different base parts provide either direct or indirect earthing of the signal shielding: The MP Base 2x2-R
has the shield connectors 9/10 (GND) linked directly to the DIN rail and to the earth connector. The MP
Base 2x2-R GDT has a gas discharge tube linked between the shield connectors 9/10 (GND) and the DIN
rail and erath connector. Therefore a galvanic insulation between the signal shield and the earth connection (PE) can be reached.
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
91
Surge protection for measuring systems and automatic control devices
Pluggable SPD for MCR applications
Pluggable SPD with high discharge cappability and low protection level for MCR applications
Example photo
MP 2x2 GDT/Ad-Ad-Pg ST
Fully pluggable two-parts combined surge
arrester for signal lines. The protective module
can be removed for test or maintenance purposes
without changeing the line impedance and therefore influencing the signal level. The base part
can remain in the instalation without manipulating
or removing any wire.
1
2
5
6
10
9
Basic circuit diagram
*
3
4
7
8
11
12
n
Protective circuit for 4 signal lines with common
ground
n
Protective plug can be removed without changing
the line impedance or influencing the useful signal
n
Test standard: IEC 61643-21 / EN 61643-21
n
Applicable at the boundaries LPZ 0A - 2 and higher
n
Mounting on 35 mm DIN rail
n
Enclosure material: thermoplastic
n
Space required for installation: 17.5 mm
Technical Data
MP 2x2 GDT+5V-Ad-Ad-Pg ST
MP 2x2 GDT+12V-Ad-Ad-Pg ST
MP 2x2 GDT+24V-Ad-Ad-Pg ST
IEC category/EN type
D1 / C2 / C1 / C3
D1 / C2 / C1 / C3
D1 / C2 / C1 / C3
D1 / C2 / C1 / C3
5V
12 V
24 V
36 V
MP 2x2 GDT+36V-Ad-Ad-Pg ST
Nominal voltage
UN
Max. continous operating voltage (DC/AC)
Uc
6/4 V
15/11 V
33/23 V
45/32 V
Nominal current
IN
0,5 A
0,5 A
0,5 A
0,5 A
Iimp
2,5 kA
2,5 kA
2,5 kA
2,5 kA
C2 nominal discharge current (8/20 µs) total (In)
D1 lightning impulse current (10/350 μs) per wire
In
20 kA
20 kA
20 kA
20 kA
C2 nominal discharge current (8/20 µs) per line
In
10 kA
10 kA
10 kA
10 kA
Prorection level line-line at Iimp D1
Up
≤ 25 V
≤ 26 V
≤ 52 V
≤ 68 V
Protection level line-earth at Iimp D1
Up
≤ 27 V
≤ 37 V
≤ 66 V
≤ 85 V
Protection level line-line at 1 kV/μs C3
Up
≤ 10 V
≤ 19 V
≤ 45 V
≤ 58 V
Protection level line-Pg at 1 kV/μs C3
Up
≤ 10 V
≤ 19 V
≤ 45 V
≤ 58 V
2,2 Ω
2,2 Ω
2,2 Ω
2,2 Ω
fG
typ. 1,0 MHz
typ. 3,0 MHz
typ. 6,0 MHz
typ. 8,0 MHz
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
TU
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
Series resistance per line
Max. operating frequency (3 dB)
Conductor cross section (solid/stranded/AWG)
Operating temperature range
Inflammability class according to UL 94
V0
V0
V0
V0
Degree of protection (IEC EN 60529)
IP 20
IP 20
IP 20
IP 20
97 00 39
97 00 40
97 00 41
97 00 42
Order Data
Article-No.
Product available in 2nd half year 2012
92
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for measuring systems and automatic control devices
Pluggable SPD for MCR applications
Technical Data
MP 2x2 GDT+48V-Ad-Ad-Pg ST
MP 2x2 GDT+60V-Ad-Ad-Pg ST
IEC category/EN type
D1 / C2 / C1 / C3
D1 / C2 / C1 / C3
D1 / C2 / C1 / C3
48 V
60 V
180 V
MP 2x2 GDT+180V-Ad-Ad-Pg ST
Nominal voltage
UN
Max. continous operating voltage (DC/AC)
Uc
54/38 V
70/49 V
180/120 V
Nominal current
IN
0,5 A
0,5 A
0,5 A
D1 lightning impulse current (10/350 μs) per wire
Iimp
2,5 kA
2,5 kA
2,5 kA
C2 nominal discharge current (8/20 µs) total (In)
In
20 kA
20 kA
20 kA
C2 nominal discharge current (8/20 µs) per line
In
10 kA
10 kA
10 kA
Prorection level line-line at Iimp D1
Up
≤ 80 V
≤ 110 V
≤ 270 V
Protection level line-earth at Iimp D1
Up
≤ 95 V
≤ 125 V
≤ 300 V
Protection level line-line at 1 kV/μs C3
Up
≤ 70 V
≤ 90 V
≤ 250 V
Protection level line-Pg at 1 kV/μs C3
Up
≤ 70 V
≤ 90 V
≤ 250 V
2,2 Ω
2,2 Ω
2,2 Ω
fG
typ. 10 MHz
typ. 12 MHz
typ. 25 MHz
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
TU
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
Series resistance per line
Max. operating frequency (3 dB)
Conductor cross section (solid/stranded/AWG)
Operating temperature range
Inflammability class according to UL 94
V0
V0
V0
Degree of protection (IEC EN 60529)
IP 20
IP 20
IP 20
97 00 43
97 00 44
97 00 45
Product
MP Base 2x2-R
MP Base 2x2-R GDT
Article-No.
97 00 00
97 00 01
Order Data
Article-No.
Accessories
Different base parts provide either direct or indirect earthing of the signal shielding: The MP Base 2x2-R
has the shield connectors 9/10 (GND) linked directly to the DIN rail and to the earth connector. The MP
Base 2x2-R GDT has a gas discharge tube linked between the shield connectors 9/10 (GND) and the DIN
rail and erath connector. Therefore a galvanic insulation between the signal shield and the earth connection (PE) can be reached.
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
93
Surge protection for measuring systems and automatic control devices
Pluggable SPD for MCR applications
Pluggable SPD with high discharge cappability and low protection level for MCR applications
Example photo
MP 1x2 GDT/Ad-Ad-Pg ST
Basic circuit diagram
Fully pluggable two-parts combined surge
arrester for signal lines. The protective module
can be removed for test or maintenance purposes
without changeing the line impedance and therefore influencing the signal level. The base part
can remain in the instalation without manipulating
or removing any wire.
1
2
5
6
n
Protective circuit for 2 signal lines with common
ground
n
Protective plug can be removed without changing
the line impedance or influencing the useful signal
n
Test standard: IEC 61643-21 / EN 61643-21
10
9
*
4
3
n
Applicable at the boundaries LPZ 0A - 2 and higher
n
Mounting on 35 mm DIN rail
n
Enclosure material: thermoplastic
n
Space required for installation: 17.5 mm
Technical Data
MP 1x2 GDT+5V-Ad-Ad-Pg ST
MP 1x2 GDT+12V-Ad-Ad-Pg ST
MP 1x2 GDT+24V-Ad-Ad-Pg ST
IEC category/EN type
D1 / C2 / C1 / C3
D1 / C2 / C1 / C3
D1 / C2 / C1 / C3
D1 / C2 / C1 / C3
5V
12 V
24 V
36 V
MP 1x2 GDT+36V-Ad-Ad-Pg ST
Nominal voltage
UN
Max. continous operating voltage (DC/AC)
Uc
6/4 V
15/11 V
33/23 V
45/32 V
Nominal current
IN
0,5 A
0,5 A
0,5 A
0,5 A
Iimp
2,5 kA
2,5 kA
2,5 kA
2,5 kA
C2 nominal discharge current (8/20 µs) total (In)
D1 lightning impulse current (10/350 μs) per wire
In
20 kA
20 kA
20 kA
20 kA
C2 nominal discharge current (8/20 µs) per line
In
10 kA
10 kA
10 kA
10 kA
Prorection level line-line at Iimp D1
Up
≤ 25 V
≤ 26 V
≤ 52 V
≤ 68 V
Protection level line-earth at Iimp D1
Up
≤ 27 V
≤ 37 V
≤ 66 V
≤ 85 V
Protection level line-line at 1 kV/μs C3
Up
≤ 10 V
≤ 19 V
≤ 45 V
≤ 58 V
Protection level line-Pg at 1 kV/μs C3
Up
≤ 10 V
≤ 19 V
≤ 45 V
≤ 58 V
2,2 Ω
2,2 Ω
2,2 Ω
2,2 Ω
fG
typ. 1,0 MHz
typ. 3,0 MHz
typ. 6,0 MHz
typ. 8,0 MHz
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
TU
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
Series resistance per line
Max. operating frequency (3 dB)
Conductor cross section (solid/stranded/AWG)
Operating temperature range
Inflammability class according to UL 94
V0
V0
V0
V0
Degree of protection (IEC EN 60529)
IP 20
IP 20
IP 20
IP 20
97 00 46
97 00 47
97 00 48
97 00 49
Order Data
Article-No.
Product available in 2nd half year 2012
94
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for measuring systems and automatic control devices
Pluggable SPD for MCR applications
Technical Data
MP 1x2 GDT+48V-Ad-Ad-Pg ST
MP 1x2 GDT+60V-Ad-Ad-Pg ST
IEC category/EN type
D1 / C2 / C1 / C3
D1 / C2 / C1 / C3
D1 / C2 / C1 / C3
48 V
60 V
180 V
MP 1x2 GDT+180V-Ad-Ad-Pg ST
Nominal voltage
UN
Max. continous operating voltage (DC/AC)
Uc
54/38 V
70/49 V
180/120 V
Nominal current
IN
0,5 A
0,5 A
0,5 A
D1 lightning impulse current (10/350 μs) per wire
Iimp
2,5 kA
2,5 kA
2,5 kA
C2 nominal discharge current (8/20 µs) total (In)
In
20 kA
20 kA
20 kA
C2 nominal discharge current (8/20 µs) per line
In
10 kA
10 kA
10 kA
Prorection level line-line at Iimp D1
Up
≤ 80 V
≤ 110 V
≤ 270 V
Protection level line-earth at Iimp D1
Up
≤ 95 V
≤ 125 V
≤ 300 V
Protection level line-line at 1 kV/μs C3
Up
≤ 70 V
≤ 90 V
≤ 250 V
Protection level line-Pg at 1 kV/μs C3
Up
≤ 70 V
≤ 90 V
≤ 250 V
2,2 Ω
2,2 Ω
2,2 Ω
fG
typ. 10 MHz
typ. 12 MHz
typ. 25 MHz
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
TU
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
Series resistance per line
Max. operating frequency (3 dB)
Conductor cross section (solid/stranded/AWG)
Operating temperature range
Inflammability class according to UL 94
V0
V0
V0
Degree of protection (IEC EN 60529)
IP 20
IP 20
IP 20
97 00 50
97 00 51
97 00 52
Product
MP Base 2x2-R
MP Base 2x2-R GDT
Article-No.
97 00 00
97 00 01
Order Data
Article-No.
Accessories
Different base parts provide either direct or indirect earthing of the signal shielding: The MP Base 2x2-R
has the shield connectors 9/10 (GND) linked directly to the DIN rail and to the earth connector. The MP
Base 2x2-R GDT has a gas discharge tube linked between the shield connectors 9/10 (GND) and the DIN
rail and erath connector. Therefore a galvanic insulation between the signal shield and the earth connection (PE) can be reached.
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
95
Surge protection for measuring systems and automatic control devices
Pluggable SPD for MCR applications
96
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for measuring systems and automatic control devices
Pluggable SPD for MCR applications
Pluggable SPD for high frequency MCR applications
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
97
Surge protection for measuring systems and automatic control devices
Pluggable SPD for MCR applications
Pluggable SPD for high frequency MCR applications
Example photo
MP 2x2 HF ST
Fully pluggable two-parts combined surge arrester for
signal lines for high frequency applications such as bus
systems or video transmission. The protective module
can be removed for test or maintenance purposes
without changeing the line impedance and therefore
influencing the signal level. The base part can remain
in the instalation without manipulating or removing any
wire.
1
2
5
6
10
9
Basic circuit diagram
*
3
4
7
8
11
12
n
Protective circuit for 4 signal lines without reference
to ground potential
n
Protective plug can be removed without changing
the line impedance or influencing the useful signal
n
Test standard: IEC 61643-21 / EN 61643-21
Technical Data
MP 2x2 5V-HF ST
IEC category/EN type
D1 / C2 / C1 / C3
D1 / C2 / C1 / C3
MP 2x2 24V-HF ST
Nominal voltage
UN
5V
24 V
Max. continous operating voltage (DC/AC)
Uc
6/4 V
33/23 V
Nominal current
IN
0,5 A
0,5 A
Iimp
2,5 kA
2,5 kA
C2 nominal discharge current (8/20 µs) total (In)
In
20 kA
20 kA
C2 nominal discharge current (8/20 µs) per line
In
10 kA
10 kA
D1 lightning impulse current (10/350 μs) per wire
Prorection level line-line at Iimp D1
Up
≤ 25 V
≤ 52 V
Protection level line-earth at Iimp D1
Up
≤ 27 V
≤ 66 V
Protection level line-line at 1 kV/μs C3
Up
≤ 10 V
≤ 45 V
Protection level line-Pg at 1 kV/μs C3
Up
≤ 10 V
≤ 45 V
2,2 Ω
2,2 Ω
typ. 70 MHz
typ. 70 MHz
Series resistance per line
Max. operating frequency (3 dB)
fG
Conductor cross section (solid/stranded/AWG)
Operating temperature range
TU
n
Applicable at the boundaries LPZ 0A - 2 and higher
n
Mounting on 35 mm DIN rail
n
Enclosure material: thermoplastic
n
Space required for installation: 17.5 mm
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
-40 - +80 °C
-40 - +80 °C
Inflammability class according to UL 94
V0
V0
Degree of protection (IEC EN 60529)
IP 20
IP 20
97 10 50
97 10 51
Product
MP Base 2x2
MP Base 2x2 GDT
Article-No.
97 00 03
97 00 04
Order Data
Article-No.
Accessories
Different base parts provide either direct or indirect earthing of the signal shielding: The MP Base 2x2
has the shield connectors 9/10 (GND) linked directly to the DIN rail and to the earth connector. The MP
Base 2x2 GDT has a gas discharge tube linked between the shield connectors 9/10 (GND) and the DIN
rail and erath connector. Therefore a galvanic insulation between the signal shield and the earth connection (PE) can be reached.
Product available in 2nd half year 2012
98
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for measuring systems and automatic control devices
Pluggable SPD for MCR applications
Pluggable SPD for high frequency MCR applications
MP 1x2 HF ST
Basic circuit diagram
1
2
5
6
Example photo
Fully pluggable two-parts combined surge arrester for
signal lines for high frequency applications such as bus
systems or video transmission. The protective module
can be removed for test or maintenance purposes
without changeing the line impedance and therefore
influencing the signal level. The base part can remain
in the instalation without manipulating or removing any
wire.
n
Protective circuit for 2 signal lines without reference
to ground potential
n
Protective plug can be removed without changing
the line impedance or influencing the useful signal
n
Test standard: IEC 61643-21 / EN 61643-21
10
9
*
4
3
Technical Data
MP 1x2 5V-HF ST
IEC category/EN type
D1 / C2 / C1 / C3
D1 / C2 / C1 / C3
MP 1x2 24V-HF ST
Nominal voltage
UN
5V
24 V
Max. continous operating voltage (DC/AC)
Uc
6/4 V
33/23 V
Nominal current
IN
0,5 A
0,5 A
Iimp
2,5 kA
2,5 kA
C2 nominal discharge current (8/20 µs) total (In)
In
20 kA
20 kA
C2 nominal discharge current (8/20 µs) per line
In
10 kA
10 kA
D1 lightning impulse current (10/350 μs) per wire
Prorection level line-line at Iimp D1
Up
≤ 25 V
≤ 52 V
Protection level line-earth at Iimp D1
Up
≤ 27 V
≤ 66 V
Protection level line-line at 1 kV/μs C3
Up
≤ 10 V
≤ 45 V
Protection level line-Pg at 1 kV/μs C3
Up
≤ 10 V
≤ 45 V
2,2 Ω
2,2 Ω
typ. 70 MHz
typ. 70 MHz
Series resistance per line
Max. operating frequency (3 dB)
fG
Conductor cross section (solid/stranded/AWG)
Operating temperature range
TU
n
Applicable at the boundaries LPZ 0A - 2 and higher
n
Mounting on 35 mm DIN rail
n
Enclosure material: thermoplastic
n
Space required for installation: 17.5 mm
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
-40 - +80 °C
-40 - +80 °C
Inflammability class according to UL 94
V0
V0
Degree of protection (IEC EN 60529)
IP 20
IP 20
97 10 52
97 10 53
Product
MP Base 2x2
MP Base 2x2 GDT
Article-No.
97 00 03
97 00 04
Order Data
Article-No.
Accessories
Different base parts provide either direct or indirect earthing of the signal shielding: The MP Base 2x2
has the shield connectors 9/10 (GND) linked directly to the DIN rail and to the earth connector. The MP
Base 2x2 GDT has a gas discharge tube linked between the shield connectors 9/10 (GND) and the DIN
rail and erath connector. Therefore a galvanic insulation between the signal shield and the earth connection (PE) can be reached.
Product available in 2nd half year 2012
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
99
Surge protection for measuring systems and automatic control devices
One-piece SPD for MCR applications
100
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for measuring systems and automatic control devices
One-piece SPD for MCR applications
One-piece SPD with high discharge cappability for MCR applications
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
101
Surge protection for measuring systems and automatic control devices
One-piece SPD for MCR applications
One-piece SPD with high discharge cappability for MCR applications
Example photo
MP RK GDT
Terminal blocks with integrated surge protection
can optimize the used space in a control cabinet
and at the same time provide high level protection for terminal equipment and devices.
1
1p
2
2p
Basic circuit diagram
n
Protective circuit for 2 signal lines without
reference to ground potential
n
Applicable at the boundaries LPZ 0B - 1 and
higher
n
Test standard: IEC 61643-21 / EN 61643-21
Technical Data
MP RK GDT
IEC category/EN type
C2 / C1 / C3
Nominal voltage
UN
180 V
Max. continous operating voltage (DC/AC)
Uc
180/120 V
Nominal current
IN
2,0 A
C2 nominal discharge current (8/20 µs) total (In)
In
10 kA
C2 nominal discharge current (8/20 µs) per line
In
5 kA
Protection level line-line at In C2
Up
≤ 500 V
Protection level line-earth at In C2
Up
≤ 500 V
Protection level line-line at 1 kV/μs C3
Up
≤ 500 V
Protection level line-Pg at 1 kV/μs C3
Up
≤ 500 V
Series resistance per line
Max. operating frequency (3 dB)
0Ω
fG
typ. 100 MHz
0.2-4.0/0.2-2.5 mm² / 24-12
Conductor cross section (solid/stranded/AWG)
Operating temperature range
n
Mounting on 35 mm DIN rail
n
6.2 mm DIN rail module
n
Earthing via DIN rail or connector
TU
-40 - +80 °C
Inflammability class according to UL 94
V0
Degree of protection (IEC EN 60529)
IP 20
Enclosure material / colour
PA6 / yellow
Order Data
Article-No.
Product available in 2nd half year 2012
102
97 10 03
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for measuring systems and automatic control devices
One-piece SPD for MCR applications
One-piece SPD with high discharge cappability for MCR applications
IsoProData-Tr
One-piece lightning current discharge arrester for
signal lines with a discharge capabillity for use
the at the building entry.
Basic circuit diagram
1
1p
2
n
Protective circuit for 2 signal lines without
reference to ground potential
n
Applicable at the boundaries LPZ 0A - 1 and
higher
n
Lightning current 5 kA (10/350 µs) per wire
2p
Technical Data
n
Test standard: IEC 61643-21 / EN 61643-21
n
Space required for installation: 17.5 mm
n
Mounting on 35 mm DIN rail
n
Degree of protection according to IEC EN
60529: IP 20
IsoProData-Tr
IEC category/EN type
D1 / C2 / C1 / C3
Nominal direct voltage
UN
150 V=
Max. continuous operating voltage DC
Uc
170 V=
Max. continous operating voltage AC
Uc
120 V~
Nominal current
IN
1,5 A
Leakage current at Uc DC
IL
≤ 0.001 µA
Response time
tA
≤ 50 ns
In
20 kA
D1 lightning impulse current (10/350 µs) in total
C2 nominal discharge current (8/20 µs)
Itotal
10 kA
D1 lightning impulse current (10/350 μs) per wire
Iimp
5 kA
Protection level, residual voltage line-earth at In resp. 1 kV/µs Up
≤ 800 V
Capacitance, line-earth
< 0.005 nF
C
Risol
Insulation resistance
Operating temperature range
TU
>10 GΩ
-25 - +85 °C
Max. conductor cross section
16 massiv or 6 Litze mit Aderendhülse mm²
Installation dimensions (W × H × D)
17,5 x 87 x 58 mm
Enclosure material / colour
polycarbonate (halogen-free) UL 94-V0 / yellow
Order Data
Article-No.
27 30 02
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
103
Surge protection for measuring systems and automatic control devices
One-piece SPD for MCR applications
104
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for measuring systems and automatic control devices
One-piece SPD for MCR applications
One-piece SPD with high discharge cappability
and low protection level for MCR applications
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
105
Surge protection for measuring systems and automatic control devices
One-piece SPD for MCR applications
One-piece SPD with high discharge cappability and low protection level for MCR applications
Example photo
MP RK GDT/Ad-Ad
Terminal blocks with integrated surge protection
can optimize the used space in a control cabinet
and at the same time provide high level protection for terminal equipment and devices.
1
1p
2
2p
n
Mounting on 35 mm DIN rail
n
6.2 mm DIN rail module
n
Earthing via DIN rail or connector
Basic circuit diagram
n
Protective circuit for 2 signal lines without
reference to ground potential
n
Applicable at the boundaries LPZ 0B - 2 and
higher
n
Test standard: IEC 61643-21 / EN 61643-21
Technical Data
MP RK GDT+5V-Ad-Ad
MP RK GDT+12V-Ad-Ad
MP RK GDT+24V-Ad-Ad
MP RK GDT+36V-Ad-Ad
IEC category/EN type
C2 / C1 / C3
C2 / C1 / C3
C2 / C1 / C3
C2 / C1 / C3
5V
12 V
24 V
36 V
Nominal voltage
UN
Max. continous operating voltage (DC/AC)
Uc
6/4 V
15/11 V
33/23 V
45/32 V
Nominal current
IN
0,5 A
0,5 A
0,5 A
0,5 A
C2 nominal discharge current (8/20 µs) total (In)
In
10 kA
10 kA
10 kA
10 kA
C2 nominal discharge current (8/20 µs) per line
In
5 kA
5 kA
5 kA
5 kA
≤ 13 V
≤ 25 V
≤ 59 V
≤ 75 V
Protection level line-line at In C2
Up
Protection level line-earth at In C2
Up
≤ 500 V
≤ 500 V
≤ 500 V
≤ 500 V
Protection level line-line at 1 kV/μs C3
Up
≤ 10 V
≤ 19 V
≤ 45 V
≤ 58 V
Protection level line-Pg at 1 kV/μs C3
Up
Series resistance per line
Max. operating frequency (3 dB)
fG
Conductor cross section (solid/stranded/AWG)
Operating temperature range
Inflammability class according to UL 94
TU
≤ 500 V
≤ 500 V
≤ 500 V
≤ 500 V
2,2 Ω
2,2 Ω
2,2 Ω
2,2 Ω
typ. 1 MHz
typ. 3,0 MHz
typ. 6,0 MHz
typ. 8,0 MHz
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
V0
V0
V0
V0
Degree of protection (IEC EN 60529)
IP 20
IP 20
IP 20
IP 20
Enclosure material / colour
PA6 / yellow
PA6 / yellow
PA6 / yellow
PA6 / yellow
97 10 04
97 10 05
97 10 06
97 10 07
Order Data
Article-No.
Product available in 2nd half year 2012
106
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for measuring systems and automatic control devices
One-piece SPD for MCR applications
Technical Data
MP RK GDT+48V-Ad-Ad
MP RK GDT+60V-Ad-Ad
MP RK GDT+180V-Ad-Ad
IEC category/EN type
C2 / C1 / C3
C2 / C1 / C3
C2 / C1 / C3
Nominal voltage
UN
48 V
60 V
180 V
Max. continous operating voltage (DC/AC)
Uc
54/38 V
70/49 V
180/120 V
Nominal current
IN
0,5 A
0,5 A
0,5 A
C2 nominal discharge current (8/20 µs) total (In)
In
10 kA
10 kA
10 kA
5 kA
5 kA
5 kA
Protection level line-line at In C2
C2 nominal discharge current (8/20 µs) per line
Up
In
≤ 90 V
≤ 120 V
≤ 320 V
Protection level line-earth at In C2
Up
≤ 500 V
≤ 500 V
≤ 500 V
Protection level line-line at 1 kV/μs C3
Up
≤ 70 V
≤ 90 V
≤ 250 V
Protection level line-Pg at 1 kV/μs C3
Up
≤ 500 V
≤ 500 V
≤ 500 V
2,2 Ω
2,2 Ω
2,2 Ω
fG
typ. 10 MHz
typ. 12 MHz
typ. 25 MHz
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
TU
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
Series resistance per line
Max. operating frequency (3 dB)
Conductor cross section (solid/stranded/AWG)
Operating temperature range
Inflammability class according to UL 94
V0
V0
V0
Degree of protection (IEC EN 60529)
IP 20
IP 20
IP 20
Enclosure material / colour
PA6 / yellow
PA6 / yellow
PA6 / yellow
97 10 08
97 10 09
97 10 10
Order Data
Article-No.
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
107
Surge protection for measuring systems and automatic control devices
One-piece SPD for MCR applications
One-piece SPD with high discharge cappability and low protection level for MCR applications
Example photo
MP RK GDT/Ad-Pg
Terminal blocks with integrated surge protection
can optimize the used space in a control cabinet
and at the same time provide high level protection for terminal equipment and devices.
1
1p
2
2p
n
Mounting on 35 mm DIN rail
n
6.2 mm DIN rail module
n
Earthing via DIN rail or connector
Basic circuit diagram
n
Protective circuit for 2 signal lines with common ground
n
Applicable at the boundaries LPZ 0B - 2 and
higher
n
Test standard: IEC 61643-21 / EN 61643-21
Technical Data
MP RK GDT+5V-Ad-Pg
MP RK GDT+12V-Ad-Pg
MP RK GDT+24V-Ad-Pg
MP RK GDT+36V-Ad-Pg
IEC category/EN type
C2 / C1 / C3
C2 / C1 / C3
C2 / C1 / C3
C2 / C1 / C3
5V
12 V
24 V
36 V
Nominal voltage
UN
Max. continous operating voltage (DC/AC)
Uc
6/4 V
15/11 V
33/23 V
45/32 V
Nominal current
IN
0,5 A
0,5 A
0,5 A
0,5 A
C2 nominal discharge current (8/20 µs) total (In)
In
10 kA
10 kA
10 kA
10 kA
C2 nominal discharge current (8/20 µs) per line
In
5 kA
5 kA
5 kA
5 kA
≤ 26 V
≤ 50 V
≤ 118 V
≤ 150 V
Protection level line-line at In C2
Up
Protection level line-earth at In C2
Up
≤ 13 V
≤ 25 V
≤ 59 V
≤ 75 V
Protection level line-line at 1 kV/μs C3
Up
≤ 20 V
≤ 38 V
≤ 90 V
≤ 116 V
Protection level line-Pg at 1 kV/μs C3
Up
Series resistance per line
Max. operating frequency (3 dB)
fG
Conductor cross section (solid/stranded/AWG)
Operating temperature range
Inflammability class according to UL 94
TU
≤ 10 V
≤ 19 V
≤ 45 V
≤ 58 V
2,2 Ω
2,2 Ω
2,2 Ω
2,2 Ω
typ. 1 MHz
typ. 3,0 MHz
typ. 6,0 MHz
typ. 8,0 MHz
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
V0
V0
V0
V0
Degree of protection (IEC EN 60529)
IP 20
IP 20
IP 20
IP 20
Enclosure material / colour
PA6 / yellow
PA6 / yellow
PA6 / yellow
PA6 / yellow
97 10 11
97 10 12
97 10 13
97 10 14
Order Data
Article-No.
Product available in 2nd half year 2012
108
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for measuring systems and automatic control devices
One-piece SPD for MCR applications
Technical Data
MP RK GDT+48V-Ad-Pg
MP RK GDT+60V-Ad-Pg
MP RK GDT+180V-Ad-Pg
IEC category/EN type
C2 / C1 / C3
C2 / C1 / C3
C2 / C1 / C3
Nominal voltage
UN
48 V
60 V
180 V
Max. continous operating voltage (DC/AC)
Uc
54/38 V
70/49 V
180/120 V
Nominal current
IN
0,5 A
0,5 A
0,5 A
C2 nominal discharge current (8/20 µs) total (In)
In
10 kA
10 kA
10 kA
5 kA
5 kA
5 kA
Protection level line-line at In C2
C2 nominal discharge current (8/20 µs) per line
Up
In
≤ 180 V
≤ 240 V
≤ 600 V
Protection level line-earth at In C2
Up
≤ 90 V
≤ 120 V
≤ 320 V
Protection level line-line at 1 kV/μs C3
Up
≤ 140 V
≤ 180 V
≤ 500 V
Protection level line-Pg at 1 kV/μs C3
Up
≤ 70 V
≤ 90 V
≤ 250 V
2,2 Ω
2,2 Ω
2,2 Ω
fG
typ. 10 MHz
typ. 12 MHz
typ. 25 MHz
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
TU
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
Series resistance per line
Max. operating frequency (3 dB)
Conductor cross section (solid/stranded/AWG)
Operating temperature range
Inflammability class according to UL 94
V0
V0
V0
Degree of protection (IEC EN 60529)
IP 20
IP 20
IP 20
Enclosure material / colour
PA6 / yellow
PA6 / yellow
PA6 / yellow
97 10 15
97 10 16
97 10 17
Order Data
Article-No.
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
109
Surge protection for measuring systems and automatic control devices
One-piece SPD for MCR applications
One-piece SPD with high discharge cappability and low protection level for MCR applications
Example photo
MP RK GDT/Ad-Ad-Pg
Terminal blocks with integrated surge protection
can optimize the used space in a control cabinet
and at the same time provide high level protection for terminal equipment and devices.
1
1p
2
2p
n
Mounting on 35 mm DIN rail
n
6.2 mm DIN rail module
n
Earthing via DIN rail or connector
Basic circuit diagram
n
Protective circuit for 2 signal lines with common ground
n
Applicable at the boundaries LPZ 0B - 2 and
higher
n
Test standard: IEC 61643-21 / EN 61643-21
Technical Data
MP RK GDT+5V-Ad-Ad-Pg
MP RK GDT+12V-Ad-Ad-Pg
MP RK GDT+12V-Ad-Ad-Pg
MP RK GDT+36V-Ad-Ad-Pg
IEC category/EN type
C2 / C1 / C3
C2 / C1 / C3
C2 / C1 / C3
C2 / C1 / C3
5V
12 V
24 V
36 V
Nominal voltage
UN
Max. continous operating voltage (DC/AC)
Uc
6/4 V
15/11 V
33/23 V
45/32 V
Nominal current
IN
0,5 A
0,5 A
0,5 A
0,5 A
C2 nominal discharge current (8/20 µs) total (In)
In
10 kA
10 kA
10 kA
10 kA
C2 nominal discharge current (8/20 µs) per line
In
5 kA
5 kA
5 kA
5 kA
≤ 13 V
≤ 25 V
≤ 59 V
≤ 75 V
Protection level line-line at In C2
Up
Protection level line-earth at In C2
Up
≤ 13 V
≤ 25 V
≤ 59 V
≤ 75 V
Protection level line-line at 1 kV/μs C3
Up
≤ 10 V
≤ 19 V
≤ 45 V
≤ 58 V
Protection level line-Pg at 1 kV/μs C3
Up
Series resistance per line
Max. operating frequency (3 dB)
fG
Conductor cross section (solid/stranded/AWG)
Operating temperature range
Inflammability class according to UL 94
TU
≤ 10 V
≤ 19 V
≤ 45 V
≤ 58 V
2,2 Ω
2,2 Ω
2,2 Ω
2,2 Ω
typ. 1 MHz
typ. 3,0 MHz
typ. 6,0 MHz
typ. 8,0 MHz
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
V0
V0
V0
V0
Degree of protection (IEC EN 60529)
IP 20
IP 20
IP 20
IP 20
Enclosure material / colour
PA6 / yellow
PA6 / yellow
PA6 / yellow
PA6 / yellow
97 10 18
97 10 19
97 10 20
97 10 21
Order Data
Article-No.
Product available in 2nd half year 2012
110
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for measuring systems and automatic control devices
One-piece SPD for MCR applications
Technical Data
MP RK GDT+48V-Ad-Ad-Pg
MP RK GDT+60V-Ad-Ad-Pg
MP RK GDT+180V-Ad-Ad-Pg
IEC category/EN type
C2 / C1 / C3
C2 / C1 / C3
C2 / C1 / C3
Nominal voltage
UN
48 V
60 V
180 V
Max. continous operating voltage (DC/AC)
Uc
54/38 V
70/49 V
180/120 V
Nominal current
IN
0,5 A
0,5 A
0,5 A
C2 nominal discharge current (8/20 µs) total (In)
In
10 kA
10 kA
10 kA
5 kA
5 kA
5 kA
Protection level line-line at In C2
C2 nominal discharge current (8/20 µs) per line
Up
In
≤ 90 V
≤ 120 V
≤ 320 V
Protection level line-earth at In C2
Up
≤ 90 V
≤ 120 V
≤ 320 V
Protection level line-line at 1 kV/μs C3
Up
≤ 70 V
≤ 90 V
≤ 250 V
Protection level line-Pg at 1 kV/μs C3
Up
≤ 70 V
≤ 90 V
≤ 250 V
2,2 Ω
2,2 Ω
2,2 Ω
fG
typ. 10 MHz
typ. 12 MHz
typ. 25 MHz
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
TU
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
Series resistance per line
Max. operating frequency (3 dB)
Conductor cross section (solid/stranded/AWG)
Operating temperature range
Inflammability class according to UL 94
V0
V0
V0
Degree of protection (IEC EN 60529)
IP 20
IP 20
IP 20
Enclosure material / colour
PA6 / yellow
PA6 / yellow
PA6 / yellow
97 10 22
97 10 23
97 10 24
Order Data
Article-No.
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
111
Surge protection for measuring systems and automatic control devices
One-piece SPD for MCR applications
112
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for measuring systems and automatic control devices
One-piece SPD for MCR applications
One-piece SPD with low protection level for MCR applications
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
113
Surge protection for measuring systems and automatic control devices
One-piece SPD for MCR applications
One-piece SPD with low protection level for MCR applications
Example photo
MP RK/Ad-Ad
Terminal blocks with integrated surge protection
can optimize the used space in a control cabinet
and at the same time provide high level protection for terminal equipment and devices.
1
1p
2
2p
n
Mounting on 35 mm DIN rail
n
6.2 mm DIN rail module
n
Earthing via DIN rail or connector
Basic circuit diagram
n
Protective circuit for 2 signal lines without
reference to ground potential
n
Applicable at the boundaries LPZ 1 - 2 and
higher
n
Test standard: IEC 61643-21 / EN 61643-21
Technical Data
MP RK 5V-Ad-Ad
MP RK 12V-Ad-Ad
MP RK 24V-Ad-Ad
MP RK 36V-Ad-Ad
IEC category/EN type
C1 / C3
C1 / C3
C1 / C3
C1 / C3
5V
12 V
24 V
36 V
Nominal voltage
UN
Max. continous operating voltage (DC/AC)
Uc
6/4 V
15/11 V
33/23 V
45/32 V
Nominal current
IN
2,0 A
2,0 A
2,0 A
2,0 A
C1 nominal discharge current (8/20μs) total
In
0,8 kA
0,8 kA
0,6 kA
0,4 kA
C1 nominal discharge current (8/20μs) per line
In
0,4 kA
0,4 kA
0,3 kA
0,2 kA
Protection level line-line at In C1
Up
≤ 13 V
≤ 25 V
≤ 48 V
≤ 70 V
Protection level line-line at 1 kV/μs C3
Up
Series resistance per line
Max. operating frequency (3 dB)
fG
Conductor cross section (solid/stranded/AWG)
Operating temperature range
Inflammability class according to UL 94
TU
≤ 10 V
≤ 19 V
≤ 45 V
≤ 58 V
0Ω
0Ω
0Ω
0Ω
typ. 1,0 MHz
typ. 3,0 MHz
typ. 6,0 MHz
typ. 8,0 MHz
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
V0
V0
V0
V0
Degree of protection (IEC EN 60529)
IP 20
IP 20
IP 20
IP 20
Enclosure material / colour
PA6 / yellow
PA6 / yellow
PA6 / yellow
PA6 / yellow
Installation width
6,2 mm
6,2 mm
6,2 mm
6,2 mm
Mounting on
35 mm DIN rail (EN 60715)
35 mm DIN rail (EN 60715)
35 mm DIN rail (EN 60715)
35 mm DIN rail (EN 60715)
97 10 25
97 10 26
97 10 27
97 10 28
Order Data
Article-No.
Product available in 2nd half year 2012
114
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for measuring systems and automatic control devices
One-piece SPD for MCR applications
Technical Data
MP RK 48V-Ad-Ad
MP RK 60V-Ad-Ad
MP RK 180V-Ad-Ad
IEC category/EN type
C1 / C3
C1 / C3
C1 / C3
Nominal voltage
UN
48 V
60 V
180 V
Max. continous operating voltage (DC/AC)
Uc
54/38 V
70/48 V
180/120 V
Nominal current
IN
2,0 A
2,0 A
2,0 A
C1 nominal discharge current (8/20μs) total
In
0,3 kA
0,24 kA
0,2 kA
In
0,15 kA
0,12 kA
0,1 kA
Protection level line-line at In C1
C1 nominal discharge current (8/20μs) per line
Up
≤ 90 V
≤ 110 V
≤ 300 V
Protection level line-line at 1 kV/μs C3
Up
≤ 70 V
≤ 90 V
≤ 250 V
0Ω
0Ω
0Ω
fG
typ. 10 MHz
typ. 12 MHz
typ. 25 MHz
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
TU
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
Series resistance per line
Max. operating frequency (3 dB)
Conductor cross section (solid/stranded/AWG)
Operating temperature range
Inflammability class according to UL 94
V0
V0
V0
Degree of protection (IEC EN 60529)
IP 20
IP 20
IP 20
Enclosure material / colour
PA6 / yellow
PA6 / yellow
PA6 / yellow
Installation width
6,2 mm
6,2 mm
6,2 mm
Mounting on
35 mm DIN rail (EN 60715)
35 mm DIN rail (EN 60715)
35 mm DIN rail (EN 60715)
97 10 29
97 10 30
97 10 31
Order Data
Article-No.
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
115
Surge protection for measuring systems and automatic control devices
One-piece SPD for MCR applications
One-piece SPD with low protection level for MCR applications
Example photo
MP RK/Ad-Pg
Terminal blocks with integrated surge protection
can optimize the used space in a control cabinet
and at the same time provide high level protection for terminal equipment and devices.
1
1p
2
2p
n
Mounting on 35 mm DIN rail
n
6.2 mm DIN rail module
n
Earthing via DIN rail or connector
Basic circuit diagram
n
Protective circuit for 2 signal lines with common ground
n
Applicable at the boundaries LPZ 1 - 2 and
higher
n
Test standard: IEC 61643-21 / EN 61643-21
Technical Data
MP RK 5V-Ad-Pg
MP RK 12V-Ad-Pg
MP RK 24V-Ad-Pg
MP RK 36V-Ad-Pg
IEC category/EN type
C1 / C3
C1 / C3
C1 / C3
C1 / C3
5V
12 V
24 V
36 V
Nominal voltage
UN
Max. continous operating voltage (DC/AC)
Uc
6/4 V
15/11 V
33/23 V
45/32 V
Nominal current
IN
2,0 A
2,0 A
2,0 A
2,0 A
C1 nominal discharge current (8/20μs) total
In
0,8 kA
0,8 kA
0,6 kA
0,4 kA
C1 nominal discharge current (8/20μs) per line
In
0,4 kA
0,4 kA
0,3 kA
0,2 kA
Up
≤ 26 V
≤ 50 V
≤ 96 V
≤ 140 V
Protection level line-line at In C1
Protection level line-earth at In C1
Up
≤ 13 V
≤ 25 V
≤ 48 V
≤ 70 V
Protection level line-line at 1 kV/μs C3
Up
≤ 20 V
≤ 38 V
≤ 90 V
≤ 116 V
Protection level line-Pg at 1 kV/μs C3
Up
Series resistance per line
Max. operating frequency (3 dB)
fG
Conductor cross section (solid/stranded/AWG)
Operating temperature range
Inflammability class according to UL 94
TU
≤ 10 V
≤ 19 V
≤ 45 V
≤ 58 V
0Ω
0Ω
0Ω
0Ω
typ. 1,0 MHz
typ. 3,0 MHz
typ. 6,0 MHz
typ. 8,0 MHz
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
V0
V0
V0
V0
Degree of protection (IEC EN 60529)
IP 20
IP 20
IP 20
IP 20
Enclosure material / colour
PA6 / yellow
PA6 / yellow
PA6 / yellow
PA6 / yellow
97 10 32
97 10 33
97 10 34
97 10 35
Order Data
Article-No.
Product available in 2nd half year 2012
116
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for measuring systems and automatic control devices
One-piece SPD for MCR applications
Technical Data
MP RK 48V-Ad-Pg
MP RK 60V-Ad-Pg
MP RK 180V-Ad-Pg
IEC category/EN type
C1 / C3
C1 / C3
C1 / C3
Nominal voltage
UN
48 V
60 V
180 V
Max. continous operating voltage (DC/AC)
Uc
54/38 V
70/49 V
180/120 V
Nominal current
IN
2,0 A
2,0 A
2,0 A
C1 nominal discharge current (8/20μs) total
In
0,3 kA
0,24 kA
0,2 kA
In
0,15 kA
0,12 kA
0,1 kA
Protection level line-line at In C1
C1 nominal discharge current (8/20μs) per line
Up
≤ 180 V
≤ 220 V
≤ 600 V
Protection level line-earth at In C1
Up
≤ 90 V
≤ 110 V
≤ 300 V
Protection level line-line at 1 kV/μs C3
Up
≤ 140 V
≤ 180 V
≤ 500 V
Protection level line-Pg at 1 kV/μs C3
Up
≤ 70 V
≤ 90 V
≤ 250 V
0Ω
0Ω
0Ω
fG
typ. 10 MHz
typ. 12 MHz
typ. 25 MHz
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
TU
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
Series resistance per line
Max. operating frequency (3 dB)
Conductor cross section (solid/stranded/AWG)
Operating temperature range
Inflammability class according to UL 94
V0
V0
V0
Degree of protection (IEC EN 60529)
IP 20
IP 20
IP 20
Enclosure material / colour
PA6 / yellow
PA6 / yellow
PA6 / yellow
97 10 36
97 10 37
97 10 38
Order Data
Article-No.
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
117
Surge protection for measuring systems and automatic control devices
One-piece SPD for MCR applications
One-piece SPD with low protection level for MCR applications
Example photo
MP RK/Ad-Ad-Pg
Terminal blocks with integrated surge protection
can optimize the used space in a control cabinet
and at the same time provide high level protection for terminal equipment and devices.
1
1p
2
2p
n
Mounting on 35 mm DIN rail
n
6.2 mm DIN rail module
n
Earthing via DIN rail or connector
Basic circuit diagram
n
Protective circuit for 2 signal lines with common ground
n
Applicable at the boundaries LPZ 1 - 2 and
higher
n
Test standard: IEC 61643-21 / EN 61643-21
Technical Data
MP RK 5V-Ad-Ad-Pg
MP RK 12V-Ad-Ad-Pg
MP RK 24V-Ad-Ad-Pg
MP RK 36V-Ad-Ad-Pg
IEC category/EN type
C1 / C3
C1 / C3
C1 / C3
C1 / C3
5V
12 V
24 V
36 V
Nominal voltage
UN
Max. continous operating voltage (DC/AC)
Uc
6/4 V
15/11 V
33/23 V
45/32 V
Nominal current
IN
2,0 A
2,0 A
2,0 A
2,0 A
C1 nominal discharge current (8/20μs) total
In
0,8 kA
0,8 kA
0,6 kA
0,4 kA
C1 nominal discharge current (8/20μs) per line
In
0,4 kA
0,4 kA
0,3 kA
0,2 kA
Up
≤ 13 V
≤ 25 V
≤ 48 V
≤ 70 V
Protection level line-line at In C1
Protection level line-earth at In C1
Up
≤ 13 V
≤ 25 V
≤ 48 V
≤ 70 V
Protection level line-line at 1 kV/μs C3
Up
≤ 10 V
≤ 19 V
≤ 45 V
≤ 58 V
Protection level line-Pg at 1 kV/μs C3
Up
Series resistance per line
Max. operating frequency (3 dB)
fG
Conductor cross section (solid/stranded/AWG)
Operating temperature range
Inflammability class according to UL 94
TU
≤ 10 V
≤ 19 V
≤ 45 V
≤ 58 V
0Ω
0Ω
0Ω
0Ω
typ. 1,0 MHz
typ. 3,0 MHz
typ. 6,0 MHz
typ. 8,0 MHz
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
V0
V0
V0
V0
Degree of protection (IEC EN 60529)
IP 20
IP 20
IP 20
IP 20
Enclosure material / colour
PA6 / yellow
PA6 / yellow
PA6 / yellow
PA6 / yellow
97 10 39
97 10 40
97 10 41
97 10 42
Order Data
Article-No.
Product available in 2nd half year 2012
118
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for measuring systems and automatic control devices
One-piece SPD for MCR applications
Technical Data
MP RK 48V-Ad-Ad-Pg
MP RK 60V-Ad-Ad-Pg
MP RK 180V-Ad-Ad-Pg
IEC category/EN type
C1 / C3
C1 / C3
C1 / C3
Nominal voltage
UN
48 V
60 V
180 V
Max. continous operating voltage (DC/AC)
Uc
54/38 V
70/49 V
180/120 V
Nominal current
IN
2,0 A
2,0 A
2,0 A
C1 nominal discharge current (8/20μs) total
In
0,3 kA
0,24 kA
0,2 kA
C1 nominal discharge current (8/20μs) per line
In
0,15 kA
0,12 kA
0,1 kA
Protection level line-line at In C1
Up
≤ 90 V
≤ 110 V
≤ 300 V
Protection level line-earth at In C1
Up
≤ 90 V
≤ 110 V
≤ 300 V
Protection level line-line at 1 kV/μs C3
Up
≤ 70 V
≤ 90 V
≤ 250 V
Protection level line-Pg at 1 kV/μs C3
Up
≤ 70 V
≤ 90 V
≤ 250 V
0Ω
0Ω
0Ω
fG
typ. 10 MHz
typ. 12 MHz
typ. 25 MHz
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
0.2-4.0/0.2-2.5 mm² / 24-12
TU
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
Series resistance per line
Max. operating frequency (3 dB)
Conductor cross section (solid/stranded/AWG)
Operating temperature range
Inflammability class according to UL 94
V0
V0
V0
Degree of protection (IEC EN 60529)
IP 20
IP 20
IP 20
Enclosure material / colour
PA6 / yellow
PA6 / yellow
PA6 / yellow
97 10 43
97 10 44
97 10 45
Order Data
Article-No.
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
119
Comprehensive protection
of all communication networks
For an unobstructed data transmission it is vital to protect the communication
networks against surge voltages. Leutron’s products reliably protect server
rooms, workstations, IT and telephone installations against surge voltages –
protection concepts for large-scale as well as for small installations are
offered.
Leutron offers an optimum protection for the communication networks
of its clients.
Enhanced availability in complex
communication environments:
120
nAll-purpose protection devices for all communication networks
due to different interfaces and various bandwidths
(up to 10 G Ethernet)
nThe overvoltage is limited to non-hazardous values with protection
levels adapted to the protection-needing equipment
n
Plug-and-play units for IT installations improve the operational
availability
Surge protection
for information technology and telecommunication installations
Well-proven protection of telecommunication
installations – scalable in size and layout
Surge protection
for information technology and
telecommunication installations
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
121
Protection of data networks,
e.g. Ethernet and LAN
RJ45 socket for different
interfaces
Mounting on rail
Protection for LAN up
to Cat. 6 (Gbit Ethernet)
122
Suitable for PoE
(Power over Ethernet)
Surge protection
for information technology and telecommunication installations
SSCT (LSA) mounting technology
Approval for use in
Telekom installations
Arrester
magazines with GDT
(gas discharge tubes)
up to 10 DA or with fine
protection terminal
available
Cascadable
on backmount
frames for widespread
communication
installations, e.g.
telecommunication
distributors
2-pole gas-filled surge
arrester (GDT) with failsafe characteristic
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
123
Surge protection for information technology and telecommunication
SPD for communication networks
DataPro RJ45-CAT6
Compact surge protective module for the protection of data networks, and network devices such
as hubs, switches, server and desktop computer.
The adaptor plug style provides an easy application in cable ducts or directly at the terminal
equipment.
Schirm
shield
Basic circuit diagram
RJ 45
n
Suitable for Cat. 6 / class E applications (up to
Gbit Ethernet)
n
Applicable at the boundaries LPZ 0B - 2 and
higher
n
Test standard: IEC 61643-21 / EN 61643-21
Schirm
shield
Technical Data
n
All 8 signal lines (4 pair of wires) are protected
simultaneously.
n
RJ45 SPD for PoE (Power over Ethernet)
n
Mounting on 35 mm DIN rail
DP RJ45-CAT6-48V-Tr
IEC category/EN type
C2 / C1 / C3
Nominal direct voltage
UN
48 V=
Max. continuous operating voltage DC
Uc
48 V
Operating current
1.000 mA
C2 nominal discharge current line-line
In
0,15 kA
C2 nominal discharge current (8/20 µs) total (In)
In
10 kA
Protection level at In (line-line)
Up
150 V
Protection level at In (line-earth)
Up
550 V
Max. frequency
fG
250 MHz
Response time
tA
1 ns
Terminal input/output
RJ45, shielded
Degree of protection (IEC EN 60529)
IP 20
Housing material
Metall
Order Data
Article-No.
24 00 05
Dimension drawing, see pages 220 to 223
124
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for information technology and telecommunication
SPD for communication networks
DataPro RJ45 (f/f)
Compact surge protective module for the protection of data networks, and network devices such
as hubs, switches, server and desktop computer.
The adaptor plug style provides an easy application in cable ducts or directly at the terminal
equipment.
Schirm
shield
Basic circuit diagram
RJ 45
n
Suitable for Cat. 5 / class D applications (up to
Gbit Ethernet)
n
Applicable at the boundaries LPZ 0B - 2 and
higher
n
Test standard: IEC 61643-21 / EN 61643-21
Schirm
shield
Technical Data
n
Compatible to 10Base T / 100Base T
n
All 8 signal lines (4 pair of wires) are protected
simultaneously.
DP RJ45 f/f
IEC category/EN type
C2 / C1 / C3
Nominal direct voltage
UN
6 V=
Max. continuous operating voltage DC
Uc
8 V=
C2 nominal discharge current (8/20 µs)
In
2,5 kA
Protection level at In (8/20 µs)
Up
35 V
Max. frequency
fG
100 MHz
Operating temperature range
TU
-40 - +80 °C
Terminal input/output
RJ45, shielded
Degree of protection (IEC EN 60529)
IP 20
Housing material
Metall
Order Data
Article-No.
24 00 11
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
125
Surge protection for information technology and telecommunication
SPD for communication networks
DataPro-1xRJ45-PoE-Alu
Compact surge protective module for the protection of data networks, and network devices such
as hubs, switches, server and desktop computer.
The adaptor plug style provides an easy application in cable ducts or directly at the terminal
equipment.
Schirm
shield
Basic circuit diagram
RJ 45
n
Suitable for Cat. 5 / class D applications (up to
Gbit Ethernet)
n
Applicable at the boundaries LPZ 0B - 2 and
higher
n
Test standard: IEC 61643-21 / EN 61643-21
Schirm
shield
Technical Data
n
Compatible to 10Base T / 100Base T
n
RJ45 SPD for PoE (Power over Ethernet)
n
All 8 signal lines (4 pair of wires) are protected
simultaneously.
DP 1xRJ45-PoE-Alu
IEC category/EN type
C2 / C1 / C3
Nominal operating voltage
UN
48 V=
Max. continuous operating voltage DC
Uc
60 V
Operating current
650 mA
Nominal discharge current (8/20 μs) line-line
In
0,5 kA
Nom. discharge current (8/20 μs) line-earth
In
2,0 kA
Protection level line-line at 1 kV/μs C3
Up
≤ 180 V
Protection level line-Pg at 1 kV/μs C3
Up
≤ 600 V
Max. frequency
fG
≤ 100 MHz
Terminal input/output
RJ45, shielded
Degree of protection (IEC EN 60529)
IP 20
Housing material
Metall
Order Data
Article-No.
24 00 21
Dimension drawing, see pages 220 to 223
126
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for information technology and telecommunication
SPD for communication networks
DataPro-8xRJ45-6V-WG
Compact surge protective module in a wall
housing for the protection of data networks and
network devices such as hubs, switches, server
and desktop computer.
Basic circuit diagram
IN
OUT
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
n
Applicable at the boundaries LPZ 1 - 2 and
higher
n
RJ45 wall housing for eight ports
n
Suitable for Cat. 5 / class D applications (up to
Gbit Ethernet)
Technical Data
n
Compatible to 10Base T / 100Base T
n
Test standard: IEC 61643-21 / EN 61643-21
n
All 8 signal lines (4 pair of wires) are protected
simultaneously.
DP 8xRJ45-6V-WG
IEC category/EN type
C2 / C1 / C3
Nominal direct voltage
UN
6 V=
Max. continuous operating voltage DC
Uc
8,1 V=
Nominal current per line (In)
100 mA
C1 nominal discharge current (8/20μs) per line
In
200 A
Imax
2,5 kA
C1 protection level line-line at ln
Up
≤ 45 V
C1 protection level line-earth at In
Up
≤ 350 V
C3 protection level line-line at 1kV/μs
Up
≤ 40 V
C3 protection level line-earth at 1 kV/μs (Up)
Up
≤ 350 V
Response time line-line; line-shield
tA
≤ 1 ns
Response time line-PE; PE-shield
tA
< 100 ns
Max. frequency
fG
100 MHz
Operating temperature range
TU
-40 - +80 °C
C2 Total discharge current (8/20μs) line-earth (PE)
Terminal input/output
8 x RJ45, shielded
Degree of protection (IEC EN 60529)
IP 20
Housing material
stainless steel
Order Data
Article-No.
19 40 50
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
127
Surge protection for information technology and telecommunication
SPD for communication networks
DataPro x8RJ45-19“
Compact surge protective module in 19“ housing
with only 1 HE (45 mm) for the protection of data
networks and network devices such as hubs,
switches, server and desktop computer. Easy
installation and wiring in all 19“ distribution and
server racks possible.
Basic circuit diagram
IN
OUT
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
n
Compatible to 10Base T / 100Base T
n
Test standard: IEC 61643-21 / EN 61643-21
n
Additional modules for the protection of up to
24 ports can be installed optionally
n
All 8 signal lines (4 pair of wires) are protected
simultaneously.
n
Applicable at the boundaries LPZ 1 - 2 and
higher
n
Fully shielded 19“ housing can be equipped
with up to 24 RJ45 protection ports.
n
Suitable for Cat. 5 / class D applications (up to
Gbit Ethernet)
Technical Data
DP 1x8RJ45-19“
DP 2x8RJ45-19“
DP 3x8RJ45-19“
IEC category/EN type
C2 / C1 / C3
C2 / C1 / C3
C2 / C1 / C3
6 V=
6 V=
6 V=
Nominal direct voltage
UN
Max. continuous operating voltage DC
Uc
Nominal current per line (In)
C1 nominal discharge current (8/20μs) per line
C2 Total discharge current (8/20μs) line-earth (PE)
C1 protection level line-line at ln
8,1 V=
8,1 V=
8,1 V=
100 mA
100 mA
100 mA
In
200 A
200 A
200 A
Imax
2,5 kA
2,5 kA
2,5 kA
Up
≤ 45 V
≤ 45 V
≤ 45 V
C1 protection level line-PE at In
Up
≤ 350 V
≤ 350 V
≤ 350 V
C3 protection level line-line at 1kV/μs
Up
≤ 40 V
≤ 40 V
≤ 40 V
C3 protection level line-PE at 1kV/μs
Up
≤ 350 V
≤ 350 V
≤ 350 V
Response time line-line; line-shield
tA
< 1 ns
< 1 ns
< 1 ns
Response time line-PE; PE-shield
tA
< 100 ns
< 100 ns
< 100 ns
Max. frequency
fG
100 MHz
100 MHz
100 MHz
Operating temperature range
TU
Terminal input/output
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
8 x RJ45, shielded
16 x RJ45, shielded
24 x RJ45, shielded
Degree of protection (IEC EN 60529)
IP 20
IP 20
IP 20
Housing material
Stainless steel
Stainless steel
Stainless steel
19 40 13
19 40 23
19 40 33
Order Data
Article-No.
Dimension drawing, see pages 220 to 223
128
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for information technology and telecommunication
SPD for communication networks
DataPro x8RJ45-19“ (32,40,48 Ports)
Compact surge protective module in 19“ housing
with only 1 HE (45 mm) for the protection of data
networks and network devices such as hubs,
switches, server and desktop computer. Easy
installation and wiring in all 19“ distribution and
server racks possible.
Basic circuit diagram
IN
OUT
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
n
Compatible to 10Base T / 100Base T
n
Test standard: IEC 61643-21 / EN 61643-21
n
Additional modules for the protection of up to
48 ports can be installed optionally
n
All 8 signal lines (4 pair of wires) are protected
simultaneously.
n
Applicable at the boundaries LPZ 1 - 2 and
higher
n
Fully shielded 19“ housing can be equipped
with up to 48 RJ45 protection ports.
n
Suitable for Cat. 5 / class D applications (up to
Gbit Ethernet)
Technical Data
DP 4x8RJ45-19‘‘
DP 5x8RJ45-19“
DP 6x8RJ45-19“
IEC category/EN type
C2 / C1 / C3
C2 / C1 / C3
C2 / C1 / C3
6 V=
6 V=
6 V=
Nominal operating voltage
UN
Max. permissible rated direct voltage
Uc
Nominal current per line (In)
C1 nominal discharge current (8/20μs) per line
C2 Total discharge current (8/20μs) line-earth (PE)
C1 protection level line-line at ln
8,1 V
8,1 V
8,1 V
100 mA
100 mA
100 mA
In
200 A
200 A
200 A
Imax
2,5 kA
2,5 kA
2,5 kA
Up
≤ 45 V
≤ 45 V
≤ 45 V
C1 protection level line-PE at In
Up
≤ 350 V
≤ 350 V
≤ 350 V
C3 protection level line-line at 1kV/μs
Up
≤ 40 V
≤ 40 V
≤ 40 V
C3 protection level line-PE at 1kV/μs
Up
≤ 350 V
≤ 350 V
≤ 350 V
Response time line-line; line-shield
tA
< 1 ns
< 1 ns
< 1 ns
Response time line-PE; PE-shield
tA
< 100 ns
< 100 ns
< 100 ns
Max. frequency
fG
100 MHz
100 MHz
100 MHz
Operating temperature range
TU
Terminal input/output
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
32 x RJ45, shielded
40 x RJ45, shielded
48 x RJ45, shielded
Degree of protection (IEC EN 60529)
IP 20
IP 20
IP 20
Housing material
Stainless steel
Stainless steel
Stainless steel
19 40 43
19 40 53
19 40 63
Order Data
Article-No.
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
129
Surge protection for information technology and telecommunication
SPD for telecommunication networks
DataPro-ISDN-aP
Overvoltage protection for RJ45 for ISDN S0
interface.
RJ45- 8/ 4
6
protected side
unprotected side
Basic circuit diagram
3
4
n
For ISDN interfaces
n
Applicable at the boundaries LPZ 0B - 2 and
higher
n
RJ45 socket
5
Technical Data
DataPro ISDN-aP
IEC category/EN type
C2 / C1 / C3
Nominal direct voltage
UN
50 V=
Max. continuous operating voltage DC
Uc
± 6,2 V=
Nominal current
IN
1,5 A
C2 nominal discharge current (8/20 µs) total (In)
In
5 kA
Protection level at In (line-line)
Up
≤ 36 V
Protection level at In (line-earth)
Up
≤ 460 V
Response time
tA
≤ 500/≤ 100 ns
Insertion loss in a 100 Ω system, typical
0.1 dB bis 10 MHz
Max. operating frequency (3 dB)
fG
80 MHz
Capacitance/1 MHz, typ.
C
≤ 25/ ≤ 15 pF
TU
-40 - +80 °C
Operating temperature range
n
2-stage, (5-point) coarse and fine protective
circuit
n
Without coding
n
Test standard: IEC 61643-21 / EN 61643-21
Type of connection
screw-type terminals / RJ45
Degree of protection (IEC EN 60529)
IP 20
Order Data
Article-No.
24 00 13
Dimension drawing, see pages 220 to 223
130
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for information technology and telecommunication
SPD for telecommunication networks
DataPro-TAE/NFN-aP
Surge protective device in a housing for surface
mounting for the protection of analog telecommunication wires such as analog TAE or DSL
interfaces.
TAE / NFN - Cod e
a2
protected side
unprotected side
N
b2
E
F
W
L1
Basic circuit diagram
N
n
For analog telephone lines
n
Fax, modem, answering machine
n
Emergency dialling devices
n
Applicable at the boundaries LPZ 0B - 2 and
higher
L2
Technical Data
n
TAE connector, code NFN
n
Standard of the Deutsche Telekom
n
Test standard: IEC 61643-21 / EN 61643-21
n
2-stage, (5-point) coarse and fine protective
circuit
DataPro-TAE/NFN-aP
IEC category/EN type
C2 / C1 / C3
Nominal direct voltage
UN
60 V=
Max. continuous operating voltage DC
Uc
185 V=
Nominal current
IN
1,5 A
C2 nominal discharge current (8/20 µs) total (In)
In
5 kA
Protection level at In (line-line)
Up
≤ 300 V
Protection level at In (line-earth)
Up
≤ 450 V
Response time (line-line)/(ground-ground)
tA
≤ 10 / ≤ 50 ns
Max. operating frequency (3 dB)
fG
1,5 MHz
Resistance per path
R
1Ω
Operating temperature range
TU
-40 - +80 °C
Type of connection
screw-type terminals / TAE
Degree of protection (IEC EN 60529)
IP 20
Order Data
Article-No.
24 00 04
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
131
Surge protection for information technology and telecommunication
Surge protective devices for LSA mounting
132
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for information technology and telecommunication
Surge protective devices for LSA mounting
Surge protective devices for LSA mounting
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
133
Surge protection for information technology and telecommunication
Wiring Diagrams for LSA Technology
• LSA surge voltage magazines with 10 or 20 gas-filled surge
arresters (coarse protection)
• Applicable at the LPZ transition point 0A-2 and higher, depending
on type
• The magazines can be connected to both the connection and the
disconnection module
1 DA
IN
1
2
3
4
5
6
7
8
9
10
10 DA
OU T
• Surge voltage protection connector (coarse and fine protection) DP
1LSA or DP 10LSA to equip the LSA disconnection module (white) of
the construction form 2
• Applicable at the LPZ transition point 0A-1 and higher, depending
on type
• The surge voltage protection connectors are only pluggable to the
disconnection module
• Earthing by a grounding bar, which is
1 DA
connected to the backmount frame via
the disconnection module
unprotected
IN
b2
a ' 1p
FS
10 DA
OU T
b' 2p
protected (p)
a1
example: DP 1LSA-12
134
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for information technology and telecommunication
Surge protective devices for LSA mounting
SPD according to test category D1+C2
TelPro LSA 2/10-2E 8x6
LSA surge voltage protection for two-electrode
arresters (8x6 mm) for LSA (IDC) connection and
disconnection modules.
a1 '
1p
b1'
2p
a7'
13p
OU T
b7'
14p
a8 '
15p
OU T
b8'
16p
a9'
17p
OU T
b9'
18p
a10'
19p
OU T
b10'
20p
OU T
For 10 pair s
a1
1
IN
b1
2
a7
13
IN
b7
14
a8
15
IN
b8
16
a9
17
IN
b9
18
a1 0
19
IN
b10
20
n
Integrated fail-safe function
Basic circuit diagram
n
Empty and filled magazines
n
Magazines are fitted with 20 gas-filled surge
arresters (GDT) each
Technische Daten
Nennansprechspannung DC
UagN
Ansprechstoßspannung bei 1kV/µs
Uas
TelPro LSA 2/10-2E 8x6
TelPro LSA-2EH230-10kA
TelPro LSA-2EH230F-10kA
TelPro LSA-2EL230-20kA
- V=
230 V=
230 V=
230 V=
-V
< 650 V
< 650 V
< 550 V
NennableitwechselstromIwn
-A
10 A
10 A
20 A
D1 Blitzstoßstrom (10/350µs)
- kA
2,5 kA
2,5 kA
5 kA
Iimp
C2 Nennableitstoßstrom (8/20)
C3 Schutzpegel Ader-PE bei 1kV/µs
Kapazität Ader-Erde
In
- kA
10 kA
10 kA
20 kA
Up
-V
≤ 650 V
≤ 650 V
≤ 550 V
C
- nF
≤ 1,5 pF at 1MHz nF
≤ 1,5 pF at 1MHz nF
≤ 1,5 pF at 1MHz nF
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
24 01 06
24 01 13
24 01 14
24 01 15
BetriebstemperaturbereichTU
Bestelldaten
Artikel-Nr.
Technische Daten
Nennansprechspannung DC
Ansprechstoßspannung bei 1kV/µs
TelPro LSA-2EH350-10kA
TelPro LSA-2EH90-10kA
UagN
350 V=
90 V=
Uas
< 800 V
< 550 V
20 A
10 A
Iimp
2,5 kA
2,5 kA
In
10 kA
10 kA
≤ 800 V
≤ 550 V
≤ 1,5 at 1MHz nF
≤ 1,5 at 1MHz nF
-40 - +80 °C
-40 - +80 °C
24 01 16
24 01 17
NennableitwechselstromIwn
D1 Blitzstoßstrom (10/350µs)
C2 Nennableitstoßstrom (8/20)
C3 Schutzpegel Ader-PE bei 1kV/µs
Kapazität Ader-Erde
Up
C
BetriebstemperaturbereichTU
Bestelldaten
Artikel-Nr.
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
135
Surge protection for information technology and telecommunication
Surge protective devices for LSA mounting
SPD according to test category D1+C2
TelPro LSA 2/10-3E 8x13
LSA surge voltage protection for three-electrode
arresters (8x13 mm or 8x10 mm) for LSA (IDC)
connection and disconnection modules.
a1 '
1p
b1'
2p
a7'
13p
OU T
b7'
14p
a8 '
15p
OU T
b8'
16p
a9'
17p
OU T
b9'
18p
a10'
19p
OU T
b10'
20p
OU T
For 10 pair s
a1
1
IN
b1
2
a7
13
IN
b7
14
a8
15
IN
b8
16
a9
17
IN
b9
18
a1 0
19
IN
b10
20
Basic circuit diagram
n
Empty and filled magazines
n
Magazines are fitted with 10 gas-filled surge
arrester (GDT) each
n
Integrated fail-safe function
Technische Daten
Nominal DC sparkover voltage
Impulse sparkover voltage at 1 kV/μs
Nominal alternating discharge current
UagN
Uas
TelPro LSA 2/10-3E 8x13
TelPro LSA 2/10-3EH230E-10kA
TelPro LSA-3EH230F1E-10kA
TelPro LSA-3EL230E-20kA
- V=
230 V=
230 V=
230 V=
-V
< 650 V
< 650 V
< 550 V
Iwn
-A
10 A
10 A
20 A
D1 lightning impulse current (10/350 µs) in total
Itotal
- kA
5 kA
5 kA
10 kA
D1 lightning impulse current (10/350 μs) per wire
Iimp
- kA
2,5 kA
2,5 kA
5 kA
C2 nominal discharge current (8/20 µs) total In
- kA
10 kA
10 kA
20 kA
C2 nominal discharge current (8/20 µs) per line
In
- kA
5 kA
5 kA
10 kA
C3 protection level line-line at 1kV/μs
Up
-V
≤ 500 V
≤ 500 V
≤ 500 V
C3 protection level line-PE at 1kV/μs
Up
-V
≤ 500 V
≤ 500 V
≤ 500 V
≤ 1,5 at 1MHz nF
Capacitance, line-earth
Operating temperature range
C
TU
- nF
≤ 1,5 at 1MHz nF
-40 - +80 °C
-40 - +80 °C
24 01 18
24 01 19
≤ 1,5 at 1MHz nF
-40 - +80 °C
Bestelldaten
Artikel-Nr.
Technische Daten
Nominal DC sparkover voltage
UagN
24 01 23
TelPro LSA-3EL230F1E-20kA
TelPro LSA-3EH90E-10kA
TelPro LSA-3EH90F1E-10kA
230 V=
90 V=
90 V=
Impulse sparkover voltage at 1 kV/μs
Uas
< 550 V
< 550 V
< 550 V
Nominal alternating discharge current
Iwn
20 A
10 A
10 A
D1 lightning impulse current (10/350 µs) in total
Itotal
10 kA
5 kA
5 kA
D1 lightning impulse current (10/350 μs) per wire
Iimp
C2 nominal discharge current (8/20 µs) total C2 nominal discharge current (8/20 µs) per line
In
2,5 kA
2,5 kA
10 kA
10 kA
10 kA
5 kA
5 kA
C3 protection level line-line at 1kV/μs
Up
≤ 500 V
≤ 450 V
≤ 500 V
C3 protection level line-PE at 1kV/μs
Up
≤ 500 V
≤ 450 V
≤ 500 V
Capacitance, line-earth
Operating temperature range
In
5 kA
20 kA
C
TU
≤ 1,5 at 1MHz nF
≤ 1,5 at 1MHz nF
≤ 1,5pF at 1MHz nF
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
24 01 25
24 01 26
24 01 27
24 01 24
Order Data
Article-No.
Dimension drawing, see pages 220 to 223
136
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for information technology and telecommunication
Surge protective devices for LSA mounting
SPD according to test category D1+C2
TelPro LSA 2/10-2E 8x20
LSA surge voltage protection for two-electrode
arresters (8x20 mm) for LSA (IDC) connection and
disconnection modules.
a1 '
1p
b1'
2p
a7'
13p
OU T
b7'
14p
a8 '
15p
OU T
b8'
16p
a9'
17p
OU T
b9'
18p
a10'
19p
OU T
b10'
20p
OU T
For 10 pair s
a1
1
IN
b1
2
a7
13
IN
b7
14
a8
15
IN
b8
16
a9
17
IN
b9
18
a1 0
19
IN
b10
20
Basic circuit diagram
n
Empty and filled magazines
n
Magazines are fitted with 20 gas-filled surge
arresters (GDT) each
n
Integrated fail-safe function
Technical Data
Nominal DC sparkover voltage
UagN
Impulse sparkover voltage at 1 kV/μs
Uas
TelPro LSA 2/10-2E 8x20
TelPro LSA-2EY90-20kA
TelPro LSA 2EY230-20kA
TelPro LSA-2EY350-20kA
- V=
90 V=
230 V=
350 V=
-V
< 550 V
< 550 V
< 700 V
Nominal alternating discharge current
Iwn
-A
20 A
20 A
20 A
D1 lightning impulse current (10/350 µs)
Iimp
- kA
5 kA
5 kA
5 kA
C2 nominal discharge current (8/20 µs)
C3 protection level line-PE at 1kV/μs
Capacitance, line-earth
Operating temperature range
In
- kA
20 kA
20 kA
20 kA
Up
-V
≤ 550 V
≤ 550 V
≤ 700 V
C
- nF
≤ 1,5 at 1MHz nF
≤ 1,5 at 1MHz nF
≤ 1,5 at 1MHz nF
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
24 01 28
24 01 31
24 01 29
24 01 32
TU
Order Data
Article-No.
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
137
Surge protection for information technology and telecommunication
Surge protective devices for LSA mounting
SPD according to test category C2+C1
DataPro 1LSA
Surge voltage protective module for one pair
of wires for measuring and control systems, in
LSA (IDC) disconnection modules. The protective
module provides coarse and fine protection in
LSA systems (construction form 2). Surge voltage
protection connector for 1DA, with fail-safe
contact.
a1
a ' 1p
Basic circuit diagram
IN
OU T
FS
b2
n
Versions for various voltage levels
n
Two-step, coarse and fine protection
n
Fail-safe thermal overload protection
b' 2p
DP 1LSA-5
DP 1LSA-12
DP 1LSA-15
DP 1LSA-24
Nominal direct voltage
Technical Data
UN
5 V=
12 V=
15 V=
24 V=
Max. continuous operating voltage DC
Uc
6 V=
14 V=
19 V=
29 V=
Nominal alternating voltage
UN
3 V~
8 V~
12 V~
15 V~
Max. continous operating voltage AC
Uc
4 V~
10 V~
12 V~
20 V~
150 mA
150 mA
150 mA
100 mA
C2 nominal discharge current (8/20 µs)
In
5 kA
5 kA
5 kA
5 kA
Max. discharge current (8/20μs)
In
10 kA
10 kA
10 kA
10 kA
Nominal operating current at 25°C
Protection level at 1kV/μs (line-PG)
Residual voltage at 1 kV/μs (line-PG)
Up
≤ 15 V
≤ 28 V
≤ 40 V
≤ 60 V
Ures
≤ 12 V
≤ 22 V
≤ 31 V
≤ 46 V
Response time
tA
≤ 1 ns
≤ 1 ns
≤ 1 ns
≤ 1 ns
Capacitance, line-earth
C
≤ 4,5 nF
≤ 2,5 nF
≤ 2 nF
≤ 1,4 nF
Series impedance per line at 25°C
R
10 Ω
15 Ω
22 Ω
27 Ω
Max. transmission frequency (fg)
fg
1,6 MHz
2,4 MHz
3,1 MHz
4,2 MHz
via grounding bar and isolation
unit on LSA backmount frame
via grounding bar and isolation
unit on LSA backmount frame
via grounding bar and isolation
unit on LSA backmount frame
via grounding bar and isolation
unit on LSA backmount frame
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
self-extinguishing thermoplastic
(POCAN) UL 94 V0, grey
self-extinguishing thermoplastic
(POCAN) UL 94 V0, grey
self-extinguishing thermoplastic
(POCAN) UL 94 V0, grey
self-extinguishing thermoplastic
(POCAN) UL 94 V0, grey
24 00 31
24 00 32
24 00 33
24 00 34
Earthing (Grounding) by
Operating temperature range
Enclosure material / colour
TU
Order Data
Article-No.
Dimension drawing, see pages 220 to 223
138
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for information technology and telecommunication
Surge protective devices for LSA mounting
Technical Data
UN
Nominal direct voltage
DP 1LSA-30
DP 1LSA-48
DP 1LSA-60
DP 1LSA-110
30 V=
48 V=
60 V=
110 V=
Max. continuous operating voltage DC
Uc
33 V=
80 V=
100 V=
180 V=
Nominal alternating voltage
UN
21 V~
24 V~
48 V~
110 V~
Max. continous operating voltage AC
Uc
Nominal operating current at 25°C
23 V~
56 V~
70 V~
123 V~
100 mA
150 mA
150 mA
150 mA
C2 nominal discharge current (8/20 µs)
In
5 kA
5 kA
5 kA
5 kA
Max. discharge current (8/20μs)
In
10 kA
10 kA
10 kA
10 kA
Up
≤ 70 V
≤ 240 V
≤ 300 V
≤ 600 V
Protection level at 1kV/μs (line-PG)
Ures
≤ 54 V
≤ 130 V
≤ 180 V
≤ 230 V
Response time
tA
≤ 1 ns
≤ 25 ns
≤ 25 ns
≤ 25 ns
Residual voltage at 1 kV/μs (line-PG)
Capacitance, line-earth
C
≤ 1 nF
≤ 300 nF
≤ 250 nF
≤ 100 nF
Series impedance per line at 25°C
R
27 Ω
4,7 Ω
4,7 Ω
4,7 Ω
Max. transmission frequency (fg)
fg
4,5 MHz
5 MHz
5 MHz
10 MHz
via grounding bar and isolation
unit on LSA backmount frame
via grounding bar and isolation
unit on LSA backmount frame
via grounding bar and isolation
unit on LSA backmount frame
via grounding bar and isolation
unit on LSA backmount frame
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
self-extinguishing thermoplastic
(POCAN) UL 94 V0, grey
self-extinguishing thermoplastic
(POCAN) UL 94 V0, grey
self-extinguishing thermoplastic
(POCAN) UL 94 V0, grey
self-extinguishing thermoplastic
(POCAN) UL 94 V0, grey
24 00 36
24 00 37
24 00 38
24 00 39
Earthing (Grounding) by
Operating temperature range
Enclosure material / colour
TU
Order Data
Article-No.
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
139
Surge protection for information technology and telecommunication
Surge protective devices for LSA mounting
SPD according to test category C2+C1
DataPro 1LSA with PTC
Surge protection device for data and signal lines
in measuring systems and automatic control
devices. Surge voltage protection connector for 1
DA, with surge current protection via PTC thermistors and fail-safe contact for LSA (IDC)
disconnection modules.
PT C
Basic circuit diagram
a1
a ' 1p
IN
OU T
FS
n
Carse and fine protection
n
Surge current protection via PTC thermistors
n
Suitable for DC and AC application
n
Fail-safe thermal overload protection
PT C
b2
b' 2p
DP 1LSA-5-PTC
DP 1LSA-12-PTC
DP 1LSA-15-PTC
DP 1LSA-24-PTC
Nominal direct voltage
Technical Data
UN
5 V=
12 V=
15 V=
24 V=
Max. continuous operating voltage DC
Uc
6 V=
14 V=
19 V=
29 V=
Nominal alternating voltage
UN
3 V~
8 V~
12 V~
15 V~
Max. continous operating voltage AC
Uc
4 V~
10 V~
12 V~
20 V~
150 mA
150 mA
150 mA
150 mA
C2 nominal discharge current (8/20 µs)
In
5 kA
5 kA
5 kA
5 kA
Max. discharge current (8/20μs)
In
10 kA
10 kA
10 kA
10 kA
Nominal operating current at 25°C
Protection level at 1kV/μs (line-PG)
Residual voltage at 1 kV/μs (line-PG)
Response time
Up
≤ 15 V
≤ 28 V
≤ 40 V
≤ 60 V
Ures
≤ 12 V
≤ 22 V
≤ 31 V
≤ 46 V
tA
≤ 1 ns
≤ 1 ns
≤ 1 ns
≤ 1 ns
thermical fail-safe (short-circuit
spring) and PTC
thermical fail-safe (short-circuit
spring) and PTC
thermical fail-safe (short-circuit
spring) and PTC
thermical fail-safe (short-circuit
spring) and PTC
Thermal overload protection
Capacitance, line-earth
C
≤ 4,5 nF
≤ 2,5 nF
≤ 2 nF
≤ 1,4 nF
Series impedance per line at 25°C
R
9 - 11 Ω
9 - 11 Ω
9 - 11 Ω
9 - 11 Ω
Max. transmission frequency (fg)
fg
1,6 MHz
2,4 MHz
3,1 MHz
4,2 MHz
via grounding bar and isolation
unit on LSA backmount frame
via grounding bar and isolation
unit on LSA backmount frame
via grounding bar and isolation
unit on LSA backmount frame
via grounding bar and isolation
unit on LSA backmount frame
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
self-extinguishing thermoplastic
(POCAN) UL 94 V0, grey
self-extinguishing thermoplastic
(POCAN) UL 94 V0, grey
self-extinguishing thermoplastic
(POCAN) UL 94 V0, grey
self-extinguishing thermoplastic
(POCAN) UL 94 V0, grey
24 00 40
24 00 41
24 00 42
24 00 43
Earthing (Grounding) by
Operating temperature range
Enclosure material / colour
TU
Order Data
Article-No.
Dimension drawing, see pages 220 to 223
140
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for information technology and telecommunication
Surge protective devices for LSA mounting
Technical Data
UN
Nominal direct voltage
DP 1LSA-48-PTC
DP 1LSA-60-PTC
DP 1LSA-110-PTC
48 V=
60 V=
110 V=
Max. continuous operating voltage DC
Uc
80 V=
100 V=
180 V=
Nominal alternating voltage
UN
24 V~
48 V~
110 V~
Max. continous operating voltage AC
Uc
Nominal operating current at 25°C
56 V~
70 V~
123 V~
150 mA
150 mA
150 mA
C2 nominal discharge current (8/20 µs)
In
5 kA
5 kA
5 kA
Max. discharge current (8/20μs)
In
10 kA
10 kA
10 kA
≤ 240 V
≤ 300 V
≤ 600 V
Protection level at 1kV/μs (line-PG)
Residual voltage at 1 kV/μs (line-PG)
Response time
Up
Ures
≤ 130 V
≤ 180 V
≤ 230 V
tA
≤ 25 ns
≤ 25 ns
≤ 25 ns
thermical fail-safe (short-circuit
spring) and PTC
thermical fail-safe (short-circuit
spring) and PTC
thermical fail-safe (short-circuit spring) and PTC
Thermal overload protection
Capacitance, line-earth
C
≤ 300 nF
≤ 250 nF
≤ 100 nF
Series impedance per line at 25°C
R
9 - 11 Ω
9 - 11 Ω
9 - 11 Ω
Max. transmission frequency (fg)
fg
5 MHz
5 MHz
10 MHz
via grounding bar and isolation
unit on LSA backmount frame
via grounding bar and isolation
unit on LSA backmount frame
via grounding bar and isolation unit on LSA backmount frame
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
via grounding bar and isolation
unit on LSA backmount frame
via grounding bar and isolation
unit on LSA backmount frame
via grounding bar and isolation unit on LSA backmount frame
24 00 44
24 00 45
24 00 46
Earthing (Grounding) by
Operating temperature range
Enclosure material / colour
TU
Order Data
Article-No.
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
141
Surge protection for information technology and telecommunication
Surge protective devices for LSA mounting
SPD according to test category C2+C1
DataPro 1LSA-180FS
Lightning and surge protection for telephone
installations. Pluggable module for LSA (IDC)
disconnection modules. Surge voltage protection
connector for 1 DA, for ADSL, ISDN Uk0 or a/b
lines, with fail-safe contact.
a1
a ' 1p
Basic circuit diagram
IN
OU T
FS
b2
b' 2p
Technical Data
DP 1LSA-180FS
Nominal direct voltage
UN
110 V=
Max. continuous operating voltage DC
Uc
180 V=
Uc
127 V~
Max. continous operating voltage AC
Nominal DC sparkover voltage at 100V/s
C3 protection level at 1 kV/μs (line-PG)
UagN
Up
Nominal operating current at 25°C
C2 nominal discharge current (8/20 µs)
Max. impulse discharge current (8/20)
230 ±20% V=
≤450 V
150 mA
In
Imax
Alternating discharge current 9 cycles, 50Hz (Iw)
5 kA
10 kA
50 A
Response time line1-line2-PG
tA
Self-capacitance line-earth at 1 MHz
C
≤ 3 pF
Max. transmission frequency (fg)
fg
50 MHz
Thermal overload protection
thermical fail-safe (short-circuit spring)
Earthing (Grounding) by
Operating temperature range
Enclosure material / colour
≤ 50 ns
via grounding bar and isolation unit on LSA backmount frame
TU
-40 - +80 °C
self-extinguishing thermoplastic (POCAN) UL 94 V0, grey
Order Data
Article-No.
24 00 47
Dimension drawing, see pages 220 to 223
142
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for information technology and telecommunication
Surge protective devices for LSA mounting
SPD according to test category C2+C1
DataPro 1LSA-T110FS-PTC
Surge voltage and surge current protection for
communication and data transmission lines.
Pluggable module for LSA (IDC) disconnection
modules. Surge voltage protection connector
for 1 DA with surge current protection via PTC
thermistors, for analogue, ISDN and ADSL lines.
Integrated coarse and fine protection and fail-safe
contact.
PT C
a1
a ' 1p
Basic circuit diagram
TIS P
IN
OU T
FS
PT C
b2
b' 2p
Technical Data
DP 1LSA-T110FS-PTC
Nominal direct voltage
UN
110 V=
Max. continuous operating voltage DC
Uc
180 V=
Nominal operating current at 25°C
150 mA
C2 nominal discharge current (8/20 µs)
In
5 kA
Max. discharge current (8/20μs)
In
10 kA
Voltage protection level at isn (ln) (L-PE, L1-L2)
Residual voltage at 1 kV/μs (line-PG, line-line)
Up
≤ 300 V
Ures
≤ 300 V
Response time
tA
≤ 5 ns
Transversal Capacitance
C
≤ 60 pF
Series impedance per line at 25°C
R
9 - 11 Ω
Max. transmission frequency (fg)
fg
> 20 MHz
Thermal overload protection
thermical fail-safe (short-circuit spring) and PTC
Earthing (Grounding) by
via grounding bar and isolation unit on LSA backmount frame
Operating temperature range
Enclosure material / colour
TU
-40 - +80 °C
self-extinguishing thermoplastic (POCAN) UL 94 V0, grey
Order Data
Article-No.
24 00 48
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
143
Surge protection for information technology and telecommunication
Surge protective devices for LSA mounting
SPD according to test category C2+C1
DataPro 1LSA-TK180FS
Lightning and surge protection for telephone
installations. Pluggable module for LSA (IDC)
disconnection modules. Surge voltage protection
connector for 1 DA with fail-safe contact (only
coarse protection) for analogue, ISDN and ADSL
lines.
a1
a ' 1p
Basic circuit diagram
IN
FS
b2
OU T
b' 2p
Technical Data
DP 1LSA-TK180FS
Nominal direct voltage
UN
110 V=
Max. continuous operating voltage DC
Uc
180 V=
Nominal DC sparkover voltage at 100V/s
C3 protection level at 1 kV/μs (line-PG)
UagN
Up
Nominal operating current at 25°C
C2 nominal discharge current (8/20 µs)
Max. impulse discharge current (8/20)
230 ±20% V=
≤ 600 V
1000 mA
In
Imax
Alternating discharge current 9 cycles, 50Hz (Iw)
5 kA
10 kA
40 A
Response time (line-line)/(ground-ground)
tA
Self-capacitance line-earth at 1 MHz
C
≤ 5 pF
Max. transmission frequency (fg)
fg
> 30 MHz
≤ 50 ns
Thermal overload protection
thermical fail-safe (short-circuit spring)
Earthing (Grounding) by
via grounding bar and isolation unit on LSA backmount frame
Operating temperature range
Enclosure material / colour
TU
-40 - +80 °C
self-extinguishing thermoplastic (POCAN) UL 94 V0, grey
Order Data
Article-No.
24 00 49
Dimension drawing, see pages 220 to 223
144
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for information technology and telecommunication
Surge protective devices for LSA mounting
SPD according to test category C2+C1
DP 1LSA-CxxFS-PTC
Surge voltage protector for data and signal lines
in measuring systems and automatic control
devices. Surge voltage protection connector for 1
DA with surge current protection via PTC thermistors and fail-safe contact for higher frequency
transmission range for measuring systems and
automatic control devices, for LSA (IDC) disconnection modules.
PT C
Basic circuit diagram
a1
IN
a ' 1p
OU T
FS
PT C
b2
n
Surge current protection via PTC thermistors
n
High impulse discharge current of 10 kA
(8/20 µs)
n
Suitable for DC and AC application
b' 2p
DP 1LSA-C5FS-PTC
DP 1LSA-C12FS-PTC
DP 1LSA-C15FS-PTC
DP 1LSA-C24FS-PTC
Nominal direct voltage
Technical Data
UN
5 V=
12 V=
15 V=
24 V=
Max. continuous operating voltage DC
Uc
6 V=
14 V=
19 V=
29 V=
Nominal alternating voltage
UN
o.A. V~
8 V~
12 V~
15 V~
Max. continous operating voltage AC
Uc
o.A. V~
10 V~
12 V~
20 V~
150 mA
150 mA
150 mA
150 mA
C2 nominal discharge current (8/20 µs)
In
5 kA
5 kA
5 kA
5 kA
Max. discharge current (8/20μs)
In
10 kA
10 kA
10 kA
10 kA
Nominal operating current at 25°C
Protection level at In (line-line)
Up
≤ 11 V
≤ 22 V
≤ 31 V
≤ 46 V
Protection level at 1kV/μs (line-PG)
Up
≤ 600 V
≤ 600 V
≤ 600 V
≤ 600 V
Response time a-b
tA
Response time a,b to PG
≤ 1 ns
≤ 1 ns
≤ 1 ns
≤ 1 ns
100 ns
< 100 ns
< 100 ns
< 100 ns
Transversal Capacitance
C
≤ 30 pF
≤ 30 pF
≤ 30 pF
≤ 30 pF
Series impedance per line at 25°C
R
9 - 11 Ω
9 - 11 Ω
9 - 11 Ω
9 - 11 Ω
Max. transmission frequency (fg)
fg
≤ 30 MHz
≤ 30 MHz
≤ 30 MHz
≤ 30 MHz
Thermal overload protection
thermical fail-safe (short-circuit
spring) and PTC
thermical fail-safe (short-circuit
spring) and PTC
thermical fail-safe (short-circuit
spring) and PTC
thermical fail-safe (short-circuit
spring) and PTC
Earthing (Grounding) by
via grounding bar and isolation
unit on LSA backmount frame
via grounding bar and isolation
unit on LSA backmount frame
via grounding bar and isolation
unit on LSA backmount frame
via grounding bar and isolation
unit on LSA backmount frame
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
24 00 63
24 00 64
24 00 65
24 00 66
Operating temperature range
TU
Order Data
Article-No.
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
145
Surge protection for information technology and telecommunication
Surge protective devices for LSA mounting
Technical Data
DP 1LSA-C48FS-PTC
DP 1LSA-C60FS-PTC
Nominal direct voltage
UN
48 V=
60 V=
Max. continuous operating voltage DC
Uc
80 V=
100 V=
Nominal alternating voltage
UN
24 V~
48 V~
Max. continous operating voltage AC
Uc
56 V~
70 V~
150 mA
150 mA
Nominal operating current at 25°C
C2 nominal discharge current (8/20 µs)
In
5 kA
5 kA
Max. discharge current (8/20μs)
In
10 kA
10 kA
Protection level at In (line-line)
Up
≤ 130 V
≤ 180 V
Protection level at 1kV/μs (line-PG)
Up
≤ 600 V
≤ 600 V
Response time a-b
tA
≤ 25 ns
≤ 25 ns
< 100 ns
<100 ns
Response time a,b to PG
Transversal Capacitance
C
≤ 30 pF
≤ 30 pF
Series impedance per line at 25°C
R
9 - 11 Ω
9 - 11 Ω
Max. transmission frequency (fg)
fg
≤ 30 MHz
≤ 30 MHz
Thermal overload protection
thermical fail-safe (short-circuit
spring) and PTC
thermical fail-safe (short-circuit spring) and PTC
Earthing (Grounding) by
via grounding bar and isolation
unit on LSA backmount frame
via grounding bar and isolation unit on LSA backmount frame
-40 - +80 °C
-40 - +80 °C
24 00 61
24 00 62
Operating temperature range
TU
Order Data
Article-No.
146
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for information technology and telecommunication
Surge protective devices for LSA mounting
SPD according to test category C2+C1
DataPro 10LSA
Pluggable surge arrester for telecommunication
lines with 10 pair of wires (DA) for LSA (IDC)
disconnection modules.
a1'
1p
OU T
b1'
2p
a7 '
13p
OU T
b7'
14p
a8 '
15p
OU T
b8'
16p
a9 '
17p
OU T
b9'
18p
a10'
19p
OU T
b10'
20p
For 10 DA
SI D
S ID
FS
SI D
FS
S ID
FS
SI D
FS
FS
for 10 pair s
a1
1
IN
b1
2
a7
13
IN
b7
14
a8
15
IN
b8
16
a9
17
IN
b9
18
a10
19
IN
b10
20
n
Surge voltage protection against longitudinal
and transverse voltages
n
PTC surge current protection at DP 10LSAPTC-110 and DP 10LSA-PTC12V
Basic circuit diagram
n
Surge arrester for telecommunications
n
Protection for up to 10 pair of wires (DA)
n
Integrated coarse and fine protection
DP 10LSA-12V
DP 10LSA-24V
DP 10LSA-110
Nominal direct voltage
Technical Data
UN
12 V=
24 V=
110 V=
Max. continuous operating voltage DC
Uc
14 V=
29 V=
180 V=
Uc
10 V~
21 V~
Ures
≤ 22 V
≤ 46 V
≤ 250 V
150 mA
150 mA
145 mA
Max. continous operating voltage AC
Residual voltage 1kV/μs
Nominal operating current at 25°C
C2 nominal discharge current (8/20 µs)
Max. impulse discharge current (8/20)
In
Imax
5 kA
5 kA
5 kA
10 kA
10 kA
10 kA
Protection level at In
Up
≤ 28 V
≤ 60 V
220 V
Response time
tA
≤ 1 ns
≤ 1 ns
< 1 ns
≤2s
≤2s
<2 s
Thermal fail-safe response time at 230VAC/23A and ambient
TA
temperature 25°C
Capacitance, line-earth
C
< 2,5 nF
< 1,4 nF
< 0,1 nF
Serial inductive impedance at 25°C
L
47 µH
47 µH
47 µH
Series impedance per line at 25°C
R
15 Ω
27 Ω
3-6 Ω
Max. transmission frequency (fg)
fg
< 2,4 MHz
≤ 4,2 MHz
≤ 1,2 MHz
Montagewanne 0der Montagestange der Trennleiste
Montagewanne 0der Montagestange der Trennleiste
Montagewanne 0der Montagestange der Trennleiste
Earthing (Grounding) by
Operating temperature range
Enclosure material / colour
TU
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
Thermoplastic: grey or yellow
Thermoplastic: grey or yellow
Thermoplastic: grey or yellow
24 00 25
24 00 27
24 01 40
Order Data
Article-No.
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
147
Surge protection for information technology and telecommunication
Surge protective devices for LSA mounting
SPD according to test category C2+C1
DataPro 10LSA-PTC
Surge voltage arrester with surge current protection via PTC thermistors.
Designed for telecommunication lines as a pluggable module with 10 pair of
wires (DA) for LSA (IDC) disconnection modules.
a1'
1p
OU T
a7 '
13p
b1'
2p
OU T
b7'
14p
a8 '
15p
OU T
b8'
16p
a9 '
17p
OU T
b9'
18p
a10'
19p
OU T
b10'
20p
For 10 DA
SI D
S ID
FS
SI D
FS
S ID
FS
SI D
FS
FS
for 10 pair s
a1
1
IN
b1
2
a7
13
IN
b7
14
a8
15
IN
b8
16
a9
17
IN
b9
18
a10
19
IN
b10
20
n
Surge voltage protection against longitudinal
and transverse voltages
n
PTC surge current protection at DP 10LSAPTC-110 and DP 10LSA-PTC12V
Basic circuit diagram
n
Surge arrester for telecommunications
n
Protection for up to 10 pair of wires (DA)
n
Integrated coarse and fine protection
DP 10LSA-PTC-12V
DP 10LSA-PTC-24V
DP 10LSA-PTC 110
Nominal direct voltage
Technical Data
UN
12 V=
24 V=
110 V=
Max. continuous operating voltage DC
Uc
14 V=
29 V=
180 V=
Max. continous operating voltage AC
Residual voltage 1kV/μs
Uc
10 V~
21 V~
180 V~
Ures
≤ 22 V
≤ 46 V
≤ 250 V
Nominal operating current at 25°C
C2 nominal discharge current (8/20 µs)
Max. impulse discharge current (8/20)
In
Imax
150 mA
150 mA
145 mA
5 kA
5 kA
5 kA
10 kA
10 kA
10 kA
Protection level at In
Up
≤ 28 V
≤ 60 V
220 V
Response time
tA
≤ 1 ns
≤ 1 ns
≤ 1 ns
Capacitance, line-earth
C
< 2,5 nF
Series impedance per line at 25°C
R
9 - 11 Ω
< 1,4 nF
< 0,1 nF
9 - 11 Ω
9 - 11 Ω
Max. transmission frequency (fg)
fg
< 2,4 MHz
≤ 4,2 MHz
≤ 2 MHz
Operating temperature range
TU
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
Thermal overload protection
thermical fail-safe (short-circuit
spring) and PTC
thermical fail-safe (short-circuit
spring) and PTC
thermical fail-safe (short-circuit spring) and PTC
Dimensions L x W x H
110 x 22 x 72 mm
110 x 22 x 72 mm
110 x 22 x 72 mm
Earthing (Grounding) by
via grounding bar and isolation
unit on LSA backmount frame
via grounding bar and isolation
unit on LSA backmount frame
via grounding bar and isolation unit on LSA backmount frame
Enclosure material / colour
Thermoplastic: grey or yellow
Thermoplastic: grey or yellow
Thermoplastic: grey or yellow
24 00 26
24 00 28
24 01 42
Order Data
Article-No.
Dimension drawing, see pages 220 to 223
148
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for information technology and telecommunication
Surge protective devices for LSA mounting
LSA Connection Module
Each module can hold 10 DA at the cable and
allocation side for a permanent connection. LSA
magazines filled with gas-filled surge arresters
can be plugged in.
The connection module is grey.
Basic circuit diagram
n
Corresponds with IEC 60352-4 and DIN
41611-6
n
Wiring with two wires of same diameter is
possible
Technical Data
LSA 2/10-AN
Withstand voltage
2 kV
Volume resistance
< 10 mΩ
Conductor diameter, solid wire
Insulation resistance
External diameter of insulation
n
Amply dimensioned elastic arrangement of the
wiring
0,4-0,8 AWG 26-20 mm
Ris
5x 10.000 MΩ
0,7-1,5 mm
Order Data
Article-No.
24 01 00
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
149
Surge protection for information technology and telecommunication
Surge protective devices for LSA mounting
LSA Disconnection Module
Each module can hold 10 DA at the cable and
allocation side. To be equipped with surge voltage
protection connectors (coarse and fine protection)
DP 1LSA or DP 10LSA. Applicable at the LPZ
transition point 1-2 and higher.
The disconnection module is white.
Technical Data
LSA 2/10-TR
Withstand voltage
2 kV
Volume resistance
< 10 mΩ
Insulation resistance
Ris
5x 10.000 MΩ
Conductor cross-section
0,4 -0,8 mm
External diameter of insulation
0,7-1,5 mm
Order Data
Article-No.
24 01 02
Dimension drawing, see pages 220 to 223
150
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for information technology and telecommunication
Surge protective devices for LSA mounting
LSA Ground Module
To connect 38 earthing connectors and shields.
Order Data
LSA 2/10-ER38-rot
Article-No.
24 01 04
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
151
Surge protection for information technology and telecommunication
Surge protective devices for LSA mounting
Further LSA parts
LSA 2/10 KSR (24 01 08)
Hinged label holder for LSA 2/10 connection
modules and surge ­voltage protection magazines.
LSA DIN ADAPT (24 01 37)
Hat rail adapter: Metal line with M5 screw thread
(without screw)
152
LSA 2/10 AD (24 01 09)
Magazine cover for protection against dust and
unwanted contact. Transparent for visual inspection of the arresters in the magazine.
LSA 2/10-ES (24 01 33)
Pluggable grounding rail: For 10DA connection
modules serving as a connection between LSA
backmount frame and surge voltage protection
connector.
LSA 2/10-MW10-25/22 (24 01 10)
LSA backmount frame 10x 10DA (modular),
25 mm grid / depth 22 mm, easily detachable upon individual requirement, available
up to a size of 78 connection modules
LSA 2/10 KS-120 (24 01 36)
SA edge protection profile for backmount frame, 20 mm length
Order Data
LSA 2/10 KSR
LSA 2/10 AD
LSA 2/10-MW10-25/22
LSA DIN ADAPT
Article-No.
24 01 08
24 01 09
24 01 10
24 01 37
Order Data
LSA 2/10 KS-120
LSA 2/10-ES
Article-No.
24 01 36
24 01 33
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for information technology and telecommunication
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
153
Everything for the protection of
transmission and receiving systems
Due to an expansion of its product range Leutron now offers devices
that cover all established interfaces and frequency ranges. Transmitting
and receiving systems with broadband and narrowband signals up to 6
GHz as well as base stations for mobile communications and broadcasting
systems can be protected. The protective devices combine a very low
protection level with an optimum transmission of the wanted signal.
Special solutions for uncommon interfaces are available on request.
Fault-free transmitting and
receiving operation:
154
nProtective devices with gas-filled surge protectors, impedanceadjusted for frequency ranges up to 6 GHz – simultaneous
transmission of a DC supply voltage possible
n
Protective devices for radio installations with narrowband
signals with Lambda/4 Stubline technology. This results in a
high damping of the interfering noise, whilst the wanted signal
transmitted without disturbance
is
Surge protection
for transmitting and receiving systems
High-quality protective devices for base
stations for mobile communications with high
capacity of absorbing interference energy.
Surge protection
for transmitting and
receiving systems
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
155
Aerial system protection through
Lambda/4 Stubline
Applications for different installation types:
nGSM and UMTS installations
nTri-band systems
nTerrestrial trunked radio (TETRA)
Versions for N and DIN
7/16 connectors
High damping values
Bandpass filter, adjusted
to the application
156
Surge protection
for transmitting and receiving systems
Surge protection for coaxial
interfaces
Versions for different interfaces:
nBNC connectors
nFME connectors
nSMA connectors
nN connectors
nDIN 7/16 connectors
Protection
for different
voltage levels
Versions up to 6 GHz
available
Mounting on mounting
plate or as adapter plug/
socket
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
157
Surge protection for transmitting and receiving systems
SPD for SAT/TV/Radio applications
DataPro-SAT and Radio/TV
Surge protection device for radio and television
equipment for the use directly at the building
entry.
F
n
high performance antenna protection
n
Applicable at the building entry at the boudaries LPZ 0A-1 and higher
n
equipped with GDT surge voltage protector
n
Easy installation
Basic circuit diagram
F
n
Test standard: IEC 61643-21 / EN 61643-21
Technical Data
DataPro-SAT
IEC category/EN type
D1 / C2 / C1 / C3
DataPro-Radio/TV
D1 / C2 / C1 / C3
Plug connector
F connector (acc. to IEC 60169-24)
TV/Radio connector (acc. to IEC 60169-2)
Max. permissible rated direct voltage
Uc
75 V
75 V
Nominal current
IN
4A
4A
Iimp
2,5 kA
2,5 kA
In
10 kA
10 kA
Up
600 V
600 V
ImpedanceZ
75 Ω
75 Ω
Insertion loss
fE
4 dB
4 dB
Frequency range
fO
0 - 2.150 MHz
0 - 862 MHz
Response time
tA
≤ 100 ns
≤100 ns
Operating temperature range
TU
-40 - +80 °C
-40 - +80 °C
Degree of protection (IEC EN 60529)
IP 20
IP 20
Installation dimensions (W × H × D)
40 x 44 x 22 mm
40 x 44 x 42 mm
Mounting type
wall mounting
wall mounting
21 00 20
21 00 30
D1 lightning impulse current (10/350 µs)
C2 nominal discharge current (8/20 µs)
Protection level at 1kV/μs
Order Data
Article-No.
Dimension drawing, see pages 220 to 223
158
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for transmitting and receiving systems
SPD with BNC connector
DataPro Koax-8V-BNC
Lightning and surge protection for coaxial signal
lines with BNC connector for the use at the
building entry.
FME
BNC
Basic circuit diagram
n
High performance surge protector
n
Applicable at the building entry at the boudaries LPZ 0A-1 and higher
n
For video surveillance cameras
n
Connector according to IEC 61169-8
Technical Data
DataPro Koax-8V-BNC
IEC category/EN type
D1 / C2 / C1 / C3
D1 / C2 / C1 / C3
Plug connector
BNC (m/f)
BNC (m/f)
Max. continuous operating voltage DC
Uc
Max. power
DataPro Koax-8V-BNC-75 Ohm
8 V=
8 V=
0,7 W
0,7 W
Series restistance (DC resistance) per line
Z
10 Ω
10 Ω
Surge impedance
Z
50 Ω
75 Ω
Response time fine protection
tA
≤ 2 ns
≤ 2 ns
In
5 kA
5 kA
C2 nominal discharge current (8/20 µs)
Max. impulse discharge current (8/20)
Imax
10 kA
10 kA
D1 lightning impulse current (10/350 µs)
Iimp
1 kA
1 kA
C2 protection level line-shield at ln
Up
≤ 20 V
≤ 20 V
C3 protection level line-shield at 1kV/μs
Up
≤ 13 V
≤ 13 V
C3 protection level line-shield-PE at 1kV/μs (Up)
Up
≤ 600 V
≤ 600 V
Frequency range
fO
Return loss
Operating temperature range
TU
Degree of protection (IEC EN 60529)
n
Grounding via connected earthing wire
0.75 mm², L=ca.30 mm
n
Test standard: IEC 61643-21 / EN 61643-21
0 - 60 MHz
0 - 60 MHz
at 40 kHZ: > 20 dB
at 40 kHZ: > 20 dB
- 25 - +85 °C
-25 - +85 °C
IP 20
IP 20
54 43 46
54 43 40
Order Data
Article-No.
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
159
Surge protection for transmitting and receiving systems
SPD with BNC connector
DataPro Koax BNC
Surge protection device for coaxial signal lines
with BNC connectors and very high frequencies.
The discharge current arrester can be mounted in
and earthed in a mounting plate.
Basic circuit diagram
n
Surge protection device for extremly high
freqeuncies up to 6 GHz
n
Applicable at the boundaries LPZ 0B - 1 and
higher
n
Connector according to IEC 61169-8
Technical Data
DP Koax BNC 50Ohm
IEC category/EN type
C2 / C1 / C3
Plug connector
BNC (m/f)
Surge impedance
Z
Frequency range
fO
Return loss
Max. impulse discharge current (8/20)
150 - 250 V
In
Imax
Max. transmission capacity
Operating temperature range
Degree of protection (IEC EN 60529)
50 Ω
0 - 6000 MHz
≥ 20 dB
Breakdown voltage (100V/s)
C2 nominal discharge current (8/20 µs)
n
Earthing via metal housing
n
Test standard: IEC 61643-21 / EN 61643-21
5 kA
10 kA
25 W
TU
-40 - +85 °C
IP 67
Order Data
Article-No.
54 43 30
Dimension drawing, see pages 220 to 223
160
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for transmitting and receiving systems
SPD with SMA connector
AntPro 5,8GHz-SMA
Surge protection device for coaxial signal lines
with SMA connectors.The very high frequency
range of up to 6 GHz enables the use in wireless
LAN and similar applications.The discharge
current arrester can be mounted in and earthed
in a mounting plate.
Basic circuit diagram
n
Surge protection device for extremly high
freqeuncies up to 6 GHz
n
Applicable at the boundaries LPZ 0B - 1 and
higher
n
Connector according to IEC 61169-8
n
Earthing via metal housing
Technical Data
AntPro 5,8GHz-SMA
AntPro 5,8GHz-R-SMA
IEC category/EN type
C2 / C1 / C3
C2 / C1 / C3
Plug connector
SMA (m/f)
R-SMA (f/m)
50 Ω
50 Ω
Surge impedance
Z
Frequency range
fO
Return loss
Breakdown voltage (100V/s)
C2 nominal discharge current (8/20 µs)
Max. impulse discharge current (8/20)
In
Imax
Max. transmission capacity
Operating temperature range
TU
0 - 6000 MHz
0 - 6000 MHz
≥ 20 dB
≥ 20 dB
150 - 250 V
150 - 250 V
5 kA
5 kA
10 kA
10 kA
25 W
25 W
-40 - +85 °C
-40 - +85 °C
04 58 00
04 58 02
n
Test standard: IEC 61643-21 / EN 61643-21
n
Mounting with angle bracket or in mounting
plate possible
n
Second version with inverse polarity (inner
conductor is socket instead of plug)
Order Data
Article-No.
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
161
Surge protection for transmitting and receiving systems
SPD with N connector
AntPro Koax-GSM-N/230
AntPro Koax-GSM-N was designed for the coarse
protection of highly sensitive electronical HF
amplifiers, e.g., for GSM aerial systems with GSM
aerial cable RG213/U (max. 180 W at max. 1
GHz, Ø 10.5 mm).
Basic circuit diagram
n
High performance surge arrester for broadband applications with frequency ranges from
DC up to 2.5 GHz.
n
Applicable at the boundaries LPZ 0B - 1 and
higher
Technical Data
AntPro Koax-GSM-N/230
AntPro Koax-GSM-N-230(f/f)
IEC category/EN type
C2 / C1 / C3
C2 / C1 / C3
Plug connector
N (m/f)
N (f/f)
Surge impedance
Z
Frequency range
fO
50 Ω
50 Ω
0 - 2500 MHz
0 - 2500 MHz
Return loss
dBtyp.: 1GHz: 30 dB/2,5 GHz: 23
dBtyp.: 1GHz: 30 dB/2,5 GHz: 23
Insertion loss
dBtyp.:1GHz<0,1dB/2,5 GHz<0,2
dBtyp.:1GHz<0,1dB/2,5 GHz<0,2
DC spark-over voltage
230 V
230 V
C2 nominal discharge current (8/20 µs)
In
15 kA
15 kA
Max. impulse discharge current (8/20)
Imax
20 kA
20 kA
Insulation resistance
Risol
≥ 5 GΩ
≥ 5 GΩ
Vertical resistance inner conductor
R
≤ 2 mΩ
≤ 2 mΩ
Vertical resistance outer conductor
R
≤ 0,5 mΩ
≤ 0,5 mΩ
-30 - +100 °C
-30 - +100 °C
IP 67
IP 67
04 00 01
04 00 04
Operating temperature range
Degree of protection (IEC EN 60529)
TU
n
Connector according to IEC 61169-8
n
Test standard: IEC 61643-21 / EN 61643-21
n
The f/f version can be mounted in a mounting
plate or with an angle bracket.
Order Data
Article-No.
Dimension drawing, see pages 220 to 223
162
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for transmitting and receiving systems
Lambda/4 stubline SPD with N connector
AntPro Lambda/4 N
Surge protective device in maintenance-free
Lamba/4 style with band-pass filter characteristic.
Therefore a very good transmission characteristic
combined with high attenuation of the disturbances can be reached. Remote antenna power
supply is not possible because of the short-circuit
characteristic for low-frequency signals.
Basic circuit diagram
n
High performance Lambda/4 Stubline for
antenna protection without interruption of the
useful signal
n
Suitable for TETRA and GSM installations
n
Applicable at the building entry at the boudaries LPZ 0A-1 and higher
n
Connector according to IEC 61169-16
n
Test standard: IEC 61643-21 / EN 61643-21
Technical Data
AntPro Lambda/4 N 0.51GHz
AntPro Lambda/4 N 0.8GHz
IEC category/EN type
D1 / C2 / C1 / C3
D1 / C2 / C1 / C3
D1 / C2 / C1 / C3
Plug connector
N (m/f)
N (m/f)
N (m/f)
Surge impedance
Z
Frequency range
fO
AntPro Lambda/4 N 2.0GHz
50 Ω
50 Ω
50 Ω
380 - 512 MHz
800 - 900 MHz
1700 - 2300 MHz
Return loss
< - 23 dB
< - 23 dB
< - 20,5 dB
Insertion loss
< 0,1 dB
< 0,1 dB
< 0,1 dB
min. 50 kA
min. 50 kA
min. 50 kA
Max. impulse discharge current (8/20)
Imax
Vertical resistance inner conductor
R
≤ 1,5 mΩ
≤ 1,5 mΩ
≤ 1,5 mΩ
Vertical resistance outer conductor
R
≤ 1 mΩ
≤ 1 mΩ
≤ 1 mΩ
TU
Operating temperature range
Degree of protection (IEC EN 60529)
-30 - +100 °C
-30 - +100 °C
-30 - +100 °C
IP 67
IP 67
IP 67
04 00 20
04 00 22
04 00 23
Order Data
Article-No.
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
163
Surge protection for transmitting and receiving systems
Lambda/4 stubline SPD with N connector
AntPro Lambda/4 N (f/f)
Surge protective device in maintenance-free
Lamba/4 style with band-pass filter characteristic.
Therefore a very good transmission characteristic
combined with high attenuation of the disturbances can be reached. Remote antenna power
supply is not possible because of the short-circuit
characteristic for low-frequency signals.
Basic circuit diagram
n
High performance Lambda/4 Stubline for
antenna protection without interruption of the
useful signal
n
Applicable at the building entry at the boudaries LPZ 0A-1 and higher
Technical Data
AntPro Lambda/4 N 0.51GHz (f/f) AntPro Lambda/4 N 2.0GHz (f/f)
IEC category/EN type
D1 / C2 / C1 / C3
D1 / C2 / C1 / C3
Plug connector
N (f/f)
N (f/f)
Surge impedance
Z
Frequency range
fO
50 Ω
50 Ω
380 - 512 MHz
1700 - 2300 MHz
Return loss
< - 23 dB
< - 20,5 dB
Insertion loss
< 0,1 dB
< 0,1 dB
min. 50 kA
min. 50 kA
Max. impulse discharge current (8/20)
Imax
Vertical resistance inner conductor
R
≤ 1,5 mΩ
≤ 1,5 mΩ
Vertical resistance outer conductor
R
≤ 1 mΩ
≤ 1 mΩ
-30 - +100 °C
-30 - +100 °C
IP 67
IP 67
04 00 21
04 00 24
Operating temperature range
Degree of protection (IEC EN 60529)
n
Suitable for TETRA and GSM installations
n
Connector according to IEC 61169-16
n
Test standard: IEC 61643-21 / EN 61643-21
n
Mounting with angle bracket or in mounting
plate possible
TU
Order Data
Article-No.
Dimension drawing, see pages 220 to 223
164
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for transmitting and receiving systems
SPD with DIN 7/16 connector
DataPro Koax 7/16
DataPro Koax 7/16 was developed for the coarse
protection of highly sensitive RF amplifiers with
DIN 7/16 connectors such as amplifiers for GSM
antenna systems.
Basic circuit diagram
n
High performance surge arrester for broadband applications with frequency ranges from
DC up to 2.5 GHz.
n
Applicable at the boundaries LPZ 0B - 1 and
higher
Technical Data
DP Koax 7/16
IEC category/EN type
C2 / C1 / C3
Plug connector
DIN 7/16 (m/f)
Surge impedance
Z
Frequency range
fO
n
Connector according to IEC 61169-4
n
Test standard: IEC 61643-21 / EN 61643-21
50 Ω
0 - 2500 MHz
Return loss
typ.: 1GHz - 32dB; 2GHz - 23dB; 2,2GHz - 23dB; 2,5GHz - 20dB; 2,7GHz - 17 dB
Insertion loss
typ.: 2,2GHz <0,1dB; 2,5GHz <0,2 dB
DC spark-over voltage
230 V
C2 nominal discharge current (8/20 µs)
In
15 kA
Max. impulse discharge current (8/20)
Imax
20 kA
Insulation resistance
Risol
Vertical resistance inner conductor
Vertical resistance outer conductor
≤ 0,4 mΩ
R
≤ 0,2 mΩ
TU
Operating temperature range
Degree of protection (IEC EN 60529)
≥ 10 GΩ
R
-55 - +155 °C
IP 67
Order Data
Article-No.
10 10 00
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
165
Surge protection for transmitting and receiving systems
SPD with DIN 7/16 connector
DataPro Koax 7/16 (f/f)
DataPro Koax 7/16 was developed for the coarse
protection of highly sensitive RF amplifiers with
DIN 7/16 connectors such as amplifiers for GSM
antenna systems.
Basic circuit diagram
n
High performance surge arrester for broadband applications with frequency ranges from
DC up to 2.5 GHz.
n
Applicable at the boundaries LPZ 0B - 1 and
higher
Technical Data
DP Koax 7/16 (f/f)
IEC category/EN type
C2 / C1 / C3
Plug connector
DIN 7/16 (f/f)
Surge impedance
Z
Frequency range
fO
n
Connector according to IEC 61169-4
n
Test standard: IEC 61643-21 / EN 61643-21
n
Mounting with angle bracket or in mounting
plate possible
50 Ω
0 - 2500 MHz
Return loss
typ.: 1GHz - 32dB; 2GHz - 23dB; 2,2GHz - 23dB; 2,5GHz - 20dB; 2,7GHz – 17 dB
Insertion loss
typ.: 2,2GHz <0,1dB; 2,5GHz <0,2 dB
DC spark-over voltage
230 V
C2 nominal discharge current (8/20 µs)
In
15 kA
Max. impulse discharge current (8/20)
Imax
20 kA
Insulation resistance
Risol
Vertical resistance inner conductor
Vertical resistance outer conductor
Operating temperature range
Degree of protection (IEC EN 60529)
≥ 10 GΩ
R
≤ 0,4 mΩ
R
≤ 0,2 mΩ
TU
-55 - +155 °C
IP 67
Order Data
Article-No.
10 10 01
Dimension drawing, see pages 220 to 223
166
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for transmitting and receiving systems
Lambda/4 stubline SPD with DIN 7/16 connector
AntPro Lambda/4 7/16 TRI
Surge protective device in maintenance-free
Lamba/4 style with band-pass filter characteristic.
Therefore a very good transmission characteristic
combined with high attenuation of the disturbances can be reached. Remote antenna power
supply is not possible because of the short-circuit
characteristic for low-frequency signals.
Basic circuit diagram
n
High performance Lambda/4 Stubline for
antenna protection without interruption of the
useful signal
n
Suitable for 800/900 MHz and 1800/1900
MHz-GSM and UMTS systems
Technical Data
n
Connector according to IEC 61169-4
n
Applicable at the building entry at the boudaries LPZ 0A-1 and higher
n
Test standard: IEC 61643-21 / EN 61643-21
AntPro Lambda/4 7/16 TRI
IEC category/EN type
D1 / C2 / C1 / C3
Plug connector
DIN 7/16 (m/f)
Surge impedance
Z
Frequency range
fO
50 Ω
806 - 960 / 1710 - 2200 MHz
Return loss
typ.: <-23dB / 806-859 MHz; <-27dB / 860-960 MHz; <-27dB / 1710-1990 MHz; <-23 dB / 2000-2200 MHz
Insertion loss
< 0,1 dB
Max. impulse discharge current (8/20)
Imax
Max. transmission capacity
min. 50 kA
W≤ 1,8 kW / 1 GHz
Vertical resistance inner conductor
Vertical resistance outer conductor
Operating temperature range
R
≤ 0,4 mΩ
R
≤ 0,2 mΩ
TU
Degree of protection (IEC EN 60529)
-55 - +150 °C
IP 67
Order Data
Article-No.
04 00 30
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
167
Surge protection for transmitting and receiving systems
Lambda/4 stubline SPD with DIN 7/16 connector
AntPro Lambda/4 7/16 TRI (f/f)
Surge protective device in maintenance-free
Lamba/4 style with band-pass filter characteristic.
Therefore a very good transmission characteristic
combined with high attenuation of the disturbances can be reached. Remote antenna power
supply is not possible because of the short-circuit
characteristic for low-frequency signals.
Basic circuit diagram
n
High performance Lambda/4 Stubline for antenna
protection without interruption of the useful signal
n
Suitable for 800/900 MHz and 1800/1900 MHzGSM and UMTS systems
n
Connector according to IEC 61169-4
Technical Data
n
Applicable at the building entry at the boudaries LPZ
0A-1 and higher
n
Test standard: IEC 61643-21 / EN 61643-21
n
Mounting with angle bracket or in mounting plate
possible
AntPro Lambda/4 7/16 TRI (f/f)
IEC category/EN type
D1 / C2 / C1 / C3
Plug connector
DIN 7/16 (f/f)
Surge impedance
Z
Frequency range
fO
50 Ω
806 - 960 / 1710 - 2200 MHz
Return loss
typ.: <-23 dB / 806-859 MHz; <-27 dB / 860-960 MHz; <-27dB / 1710-1990 MHz; <-23 dB / 2000-2200 MHz
Insertion loss
< 0,1 dB
Max. impulse discharge current (8/20)
Imax
Max. transmission capacity
Vertical resistance inner conductor
Vertical resistance outer conductor
Operating temperature range
Degree of protection (IEC EN 60529)
min. 50 kA
W≤ 1,8 kW / 1 GHz
R
≤ 0,4 mΩ
R
≤ 0,2 mΩ
TU
-55 - +150 °C
IP 67
Order Data
Article-No.
04 00 31
Dimension drawing, see pages 220 to 223
168
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for transmitting and receiving systems
Lambda/4 stubline SPD with DIN 7/16 connector
AntPro -7/16
Surge protective device in maintenance-free
Lamba/4 style with band-pass filter characteristic.
Therefore a very good transmission characteristic
combined with high attenuation of the disturbances can be reached. Remote antenna power
supply is not possible because of the short-circuit
characteristic for low-frequency signals.
Basic circuit diagram
n
High performance Lambda/4 Stubline for
antenna protection without interruption of the
useful signal
n
Suitable for TETRA installations
(380 - 470 MHz)
Technical Data
n
Applicable at the building entry at the boudaries LPZ 0A-1 and higher
n
Connector according to IEC 61169-4
n
Test standard: IEC 61643-21 / EN 61643-21
AntPro Lambda 7/16 0.42GHz
IEC category/EN type
D1 / C2 / C1 / C3
Plug connector
DIN 7/16 (f/f)
Surge impedance
Z
Frequency range
fO
Return loss
50 Ω
380 - 512 MHz
< -23 dB
Insertion loss
fE
< 0,1 dB
Max. impulse discharge current (8/20)
Imax
min. 50 kA
Max. power transfer
Pmax
5000 W
Vertical resistance inner conductor
R
≤ 0,4 mΩ
Vertical resistance outer conductor
R
≤ 0,2 mΩ
Operating temperature range
TU
Degree of protection (IEC EN 60529)
-55 - +150 °C
IP 67
Order Data
Article-No.
04 04 25
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
169
Surge protection for transmitting and receiving systems
SPD with FME connector
DataPro FME-AD
Surge voltage protection for sensitive GSM
modems with FME antenna connector.The set
contains an dischrage current arrester with SMA
connector and a freqeuncy range up to 6 GHz
and adapters for FME connectors.
Basic circuit diagram
n
High performance surge arrester for broadband applications with frequency ranges from
DC up to 2 GHz.
n
Applicable at the boundaries LPZ 0B - 1 and
higher
Technical Data
DP FME-AD
IEC category/EN type
C2 / C1 / C3
Plug connector
FME (m/m)
Surge impedance
Z
Frequency range
fO
Return loss
Max. impulse discharge current (8/20)
150 - 250 V
In
Imax
Max. transmission capacity
Operating temperature range
50 Ω
0 - 2000 MHz
≥ 20 dB
Breakdown voltage (100V/s)
C2 nominal discharge current (8/20 µs)
n
Test standard: IEC 61643-21 / EN 61643-21
n
Mounting with angle bracket or in mounting
plate possible
5 kA
10 kA
25 W
TU
-40 - +80 °C
Order Data
Article-No.
16 05 20
Dimension drawing, see pages 220 to 223
170
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Surge protection for transmitting and receiving systems
Notes
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
171
Filter with integrated surge protection
For protection against overvoltages and harmonics Leutron offers EMC
filters which are combined with a surge protection. These devices
suppress harmonics and transient surges, hence, allowing equipment
to operate smoothly even in high-interference environments. With
the enhancement of its product range Leutron now offers protective
devices for the area of measuring systems and automatic control, thus
covering the complete field of industrial applications.
Leutron guarantees reliable signals due to EMC filters.
EMC filters combined with harmonized surge
protection:
172
nProtection against transient overvoltages and harmonics
nLeakage-current free
nLow residual voltages mean reduced stress for the system to be
protected
nOutstanding differential-mode and common-mode damping of the
filters
EMC filters with
Integrated surge protection
The EMC filters convince with their compact
construction and the optimally harmonised
protection components filter and surge
protection.
EMC filters with
integrated surge protection
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
173
Filters with integrated
surge protection up to 200 A
Robust and shielded
design
Versions up to a
nominal current of 200 A
available
For one phase and three
phase mains supplies
174
Harmonics filter,
combined with surge
protection
EMC filters with
Integrated surge protection
Filters with integrated surge
protection for measuring and
control equipment
Integrated surge
protection
Low-pass filter with
threshold frequency of
30 to 600 kHz
Mounting on DIN rail
For two or
three single wires
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
175
EMC filter with integrated surge protection
Line filter up to 200A
EnerPro Filter for mounting rail
For overvoltage protection at single-pole TN
systems with very sensitive electronical devices.
Suitable for the application in single-phase TN
Systems. The new protective circuit with filter
contains an optimal decoupling between its
coarse protection (varistors) and its fine protection (varistors).
Basic circuit diagram
n
Applicable at the boundaries LPZ 0B - 2 and
higher
n
All leakage current-afflicted elements are
galvanically isolated from earth by a gas-filled
surge arrester (GDT).
Technical Data
EPF 230V/16A-Tr
EPF 230V/25A-Tr
IEC category/EN type
Type 2 + 3 / class II + III
Type 2 + 3 / class II + III
UN
230 V~
230 V~
Nominal alternating voltage
Max. continous operating voltage AC
Uc
275 V~
275 V~
Protection level at 5 kA (8/20 µs)
Up
≤ 1,4 kV
≤ 1,4 kV
Protection level at In (8/20 µs)
Up
≤ 2 kV
≤ 2 kV
Response time L-N/L,N-PE
Nominal impulse discharge current (10 x 8/20)
Max. impulse discharge current (1x 8/20 µs)
In
Imax
Max. acceptable fuse or back-up fuse
Operating temperature range
TU
≤ 25 ns
≤ 25 ns
15 kA
15 kA
25 kA
25 kA
16 A gL/gG
25 A gL/gG
-40 - +80 °C
-40 - +80 °C
Max. conductor cross section
50mm² stranded/35mm² fexible
50mm² stranded/35mm² fexible
Recommended conductor cross section
25 mm²
25 mm²
Max. connection torque for terminals
4,5 Nm
4,5 Nm
Enclosure material / colour
polycarbonate (halogen-free) UL 94-V0 / yellow
Degree of protection (IEC EN 60529)
IP 20
Mounting on
35 mm DIN rail (DIN EN 50 022)
35 mm DIN rail (DIN EN 50 022)
Installation dimensions (W × H × D)
88 x 107 x 67 mm
88 x 107 x 67 mm
25 30 16
25 30 17
n
Test standard: IEC 61643-1 / EN 61643-11
IP 20
Order Data
Article-No.
Dimension drawing, see pages 220 to 223
176
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
EMC filter with integrated surge protection
Line filter up to 200A
EnerPro Filter up to 35 A, two-pole
For overvoltage protection at single-pole TN
systems with very sensitive electronical devices.
Suitable for the application in single-phase TN
systems.
n
Test standard: IEC 61643-1 / EN 61643-11
n
Maximum impulse discharge current of 20 kA
(8/20µs)
Basic circuit diagram
n
Applicable at the boundaries LPZ 0B - 2 and
higher
n
The low-pass filter eliminates high-frequency
electromagnetic interferences caused by
lightning or switching actions in the network.
Technical Data
EPF 60V/16A-S
EPF 48V/25A-S
EPF 230V/16A-S
EPF 230V/35A-S
IEC category/EN type
Type 2 + 3 / class II + III
Type 2 + 3 / class II + III
Type 2 + 3 / class II + III
Type 2 + 3 / class II + III
60 V=
48 V=
- V=
- V=
Nominal direct voltage
UN
Max. continuous operating voltage DC
Uc
70 V=
70 V=
- V=
- V=
Nominal alternating voltage
UN
42 V~
42 V~
230 V~
230 V~
Max. continous operating voltage AC
Uc
50 V~
50 V~
275 V~
275 V~
Voltage protection level (1kV/μs)
Up
≤ 1,5 kV
≤ 1,0 kV
≤ 1,4 kV
≤ 1,4 kV
Protection level at In (8/20 µs); worst case
Up
≤ 2,5 kV
≤ 1,5 kV
≤ 2 kV
≤ 2 kV
Response time L-N/L,N-PE
Nominal discharge current (8/20)
Max. impulse discharge current (8/20)
In
Imax
Max. acceptable fuse or back-up fuse
Operating temperature range
TU
≤ 25 ns
≤ 25 ns
≤ 25 ns
≤ 25 ns
15 kA
15 kA
15 kA
15 kA
20 kA
20 kA
20 kA
20 kA
16 A gL/gG
25 A gL/gG
16 A gL/gG
35 A gL/gG
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
Max. conductor cross section
4 mm²
4 mm²
solid. 10/ flexible. 6 mm²
solid. 10/ flexible. 6 mm²
Recommended conductor cross section
2,5 mm²
2,5 mm²
Enclosure material / colour
aluminium / silver
aluminium / silver
aluminium / silver
aluminium / silver
Dimensions L x W x H
211 x 71 x 106 mm
211 x 71 x 106 mm
211 x 71 x 106 mm
211 x 71 x 106 mm
Degree of protection (IEC EN 60529)
IP 20
IP 20
IP 20
IP 20
25 30 22
25 30 53
25 30 20
25 30 85
Order Data
Article-No.
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
177
EMC filter with integrated surge protection
Line filter up to 200A
Technical Data
EPF 230V/16A-W
IEC category/EN type
Type 2 + 3 / class II + III
Nominal direct voltage
UN
- V=
Max. continuous operating voltage DC
Uc
- V=
Nominal alternating voltage
UN
230 / 400 V~
Max. continous operating voltage AC
Uc
275 / 480 V~
Voltage protection level at 5kA (8/20µs) or 1kV/µs
Up
≤ 1,4 kV
Protection level at In (8/20 µs)
Up
≤ 2 kV
Response time L-N/L,N-PE
Nominal discharge current (8/20)
Max. impulse discharge current (8/20)
≤ 25 ns
In
Imax
Max. acceptable back-up fuse or circuit-breaker (MCB)
Operating temperature range
15 kA
20 kA
16 A gL/gG
TU
-40 - +80 °C
Max. conductor cross section
solid. 10/ flexible. 6 mm²
Enclosure material / colour
Aluminium / silver
Dimensions L x W x H
211 x 106 x 72 mm
Degree of protection (IEC EN 60529)
IP 20
Mounting on
Mounting plate
Order Data
Article-No.
178
25 30 25
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
EMC filter with integrated surge protection
Line filter up to 200A
EnerPro Filter up to 35 A, four-pole
For overvoltage protection at single-pole TN
systems with very sensitive electronical devices.
Suitable for the application in three-phase
230/400 V TN systems.
Basic circuit diagram
n
Applicable at the boundaries LPZ 0B - 2 and
higher
n
Leakage current-free
n
Test standard: IEC 61643-1 / EN 61643-11
n
Protects foundation earthing electrode against
AC-caused corrosion
n
To protect the supply of sensible equipment
and installations
n
Maximum impulse discharge current of 20 kA
(8/20µs)
Technical Data
EPF 230/400V/16A-W
EPF 230/400V/25A-W
EPF 230/400V/35A-W
IEC category/EN type
Type 2 + 3 / class II + III
Type 2 + 3 / class II + III
Type 2 + 3 / class II + III
230 / 400 V~
230 / 400 V~
230 / 400 V~
Nominal alternating voltage
UN
Max. continous operating voltage AC
Uc
275 / 480 V~
480 V~
275 / 480 V~
Voltage protection level at 5kA (8/20µs) or 1kV/µs
Up
≤ 1,4 kV
≤ 1,4 kV
≤ 1,4 kV
Protection level at In (8/20 µs); worst case
Up
Response time L-N/L,N-PE
Response time
tA
Nominal discharge current (8/20)
Max. impulse discharge current (8/20)
≤ 2 kV
≤ 2 kV
≤ 25 ns
≤ 25 ns
< 25 ns
< 25 ns
< 25 ns
In
15 kA
15 kA
15 kA
Imax
20 kA
25 kA
20 kA
Max. acceptable back-up fuse or circuit-breaker (MCB)
Operating temperature range
≤ 2 kV
≤ 25/ ≤ 50 ns
TU
16 A gL/gG
25 A gL/gG
35 gL / gG A
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
Max. conductor cross section
solid. 10/ flexible. 6 mm²
solid. 10/ flexible. 6 mm²
solid. 10/ flexible. 6 mm²
Dimensions L x W x H
209 x 106 x 71 mm
211 x 106 x 72 mm
209 x 106 x 71 mm
Enclosure material / colour
Aluminium / silver
Aluminium / silver
Aluminium / silver
Degree of protection (IEC EN 60529)
IP 20
IP 20
IP 20
Mounting on
mounting plate
Mounting plate
Mounting plate
25 30 45
25 30 80
25 31 00
Order Data
Article-No.
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
179
EMC filter with integrated surge protection
Line filter up to 200A
EnerPro Filter up to 200 A, 4-pole
For overvoltage protection at single-pole TN
systems with very sensitive electronical devices.
Suitable for the application in three-phase
230/400 V TN systems.
Basic circuit diagram
n
Applicable at the boundaries LPZ 0B - 2 and
higher
n
4-pole
n
Leakage current-free
n
Test standard: IEC 61643-1 / EN 61643-11
n
Protects foundation earthing electrode against
AC-caused corrosion
n
To protect the supply of sensible equipment
and installations
Technical Data
EPF 230/400V/63A-E
EPF 230/400V/100A-E
EPF 230/400V/200A-E
IEC category/EN type
Type 2 + 3 / class II + III
Type 2 + 3 / class II + III
Type 2 + 3 / class II + III
UN
230 / 400 V~
230 / 400 V~
230 / 400 V~
Max. continous operating voltage AC
Uc
275 / 480 V~
275 / 480 V~
275 / 480 V~
Voltage protection level at 5kA (8/20µs) or 1kV/µs
Up
≤ 1,4 kV
≤ 1,4 kV
≤ 1,4 kV
Protection level at In (8/20 µs); worst case
Up
≤ 2 kV
≤ 2 kV
≤ 2 kV
≤ 25 ns
≤ 25 ns
≤ 25 ns
15 kA
15 kA
15 kA
Nominal alternating voltage
Response time L-N/L,N-PE
Nominal discharge current (8/20)
Max. impulse discharge current (8/20)
In
Imax
25 kA
25 kA
25 kA
63 A gL/gG
100 A gL/gG
200 A gL/gG
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
Max. conductor cross section
solid 25-95/flexible. 35-95 mm²
solid 25-95/flexible. 35-95 mm²
solid 25-95/flexible. 35-95 mm²
Max. connection torque for terminals
4,5 Nm
4,5 Nm
4,5 Nm
Dimensions L x W x H
240 x 106 x 110 mm
420 x 380 x 170 mm
420 x 380 x 170 mm
Enclosure material / colour
Aluminium / silver
Aluminium / silver
Aluminium / silver
Degree of protection (IEC EN 60529)
IP 20
IP 20
IP 20
Mounting on
Mounting plate
Mounting plate
Mounting plate
25 31 30
25 31 40
25 31 60
Max. acceptable back-up fuse or circuit-breaker (MCB)
Operating temperature range
TU
Order Data
Article-No.
Dimension drawing, see pages 220 to 223
180
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
EMC filter with integrated surge protection
MCR technology with integrated low-pass filter
MCR Technology with integrated low-pass filter
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
181
EMC filter with integrated surge protection
MCR technology with integrated low-pass filter
IsoProData 150V/150V-Tr
EMC filter for data and signal lines combined with
surge protection enables smooth operation of
sensitive electronic equipment in rough environment.
Basic circuit diagram
1
1p
2
n
Signal and data line protection with low-pass filter
n
Protective circuit for 2 signal lines without reference
to ground potential
n
Lightning current 5 kA (10/350 µs) per wire
n
Applicable at the boundaries LPZ 0A - 2 and higher
2p
Technical Data
IsoProData 150V/150V-Tr
IEC category/EN type
C1 / C2 / C3 / D1
Nominal direct voltage
UN
150 V=
Max. continuous operating voltage DC
Uc
160 V=
Max. continous operating voltage AC
Uc
112 V~
Nominal current
IN
1,5 A
Leakage current at Uc DC
IL
≤ 5 µA
Series restistance (DC resistance) per line
Z
0,3 Ω
Series inductance, typ. (L)
130 µH
Response time
tA
≤ 2 ns
C2 nominal discharge current (8/20 µs)
In
20 kA
D1 lightning impulse current (10/350 µs) in total
Itotal
10 kA
D1 lightning impulse current (10/350 μs) per wire
Iimp
5 kA
Protection level, residual voltage line-earth at In
resp. 1 kV/µs
Up
≤ 250 V
Capacitance, line-earth
C
<1 nF
Max. operating frequency (< 3 dB)
fG
600 kHz
Operating temperature range
TU
-25 - +85 °C
Max. conductor cross section
n
Mounting on 35 mm DIN rail
n
Degree of protection according to
IEC EN 60529: IP 20
n
Space required for installation: 17.5 mm
16 mm² massiv or 6 mm² Litze with wirecap
Order Data
Article-No.
27 03 03
Dimension drawing, see pages 220 to 223
182
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
EMC filter with integrated surge protection
MCR technology with integrated low-pass filter
DataPro2x1 for DIN rail
EMC filter for data and signal lines combined with
surge protection enables smooth operation of
sensitive electronic equipment in rough environment.
Basic circuit diagram
1
1p
2
n
Signal and data line protection with low-pass filter
n
Protective circuit for 2 signal lines with common
ground
n
Maximum nominal current 500 mA
n
Applicable at the boundaries LPZ 0B - 2 and higher
2p
n
Mounting on 35 mm DIN rail
n
Degree of protection according to IEC EN 60529: IP
20
n
Space required for installation: 17.5 mm
Technische Daten
DP2x1-6V/6V-Tr
DP2x1-12V/12V-Tr
DP2x1-15V/15V-Tr
DP2x1-24V/24V-Tr
IEC-Prüfklasse/EN-Type
C1 / C2 / C3
C1 / C2 / C3
C1 / C2 / C3
C1 / C2 / C3
NenngleichspannungUN
6 V=
12 V=
15 V=
24 V=
Höchste Dauerspannung DC
Uc
7 V=
13,6 V=
17 V=
28 V=
Höchste Dauerspannung AC
Uc
5 V~
10 V~
12 V~
20 V~
NennstromIN
0,5 A
0,5 A
0,5 A
0,5 A
C2 Nennableitstoßstrom (8/20) gesamt
In
20 kA
20 kA
20 kA
20 kA
C2 Nennableitstoßstrom (8/20) pro Ader
In
10 kA
10 kA
10 kA
10 kA
Up
≤9V
≤ 18 V
≤ 23 V
≤ 36 V
Leckstrom bei Umax
IL
≤ 5 µA
≤ 5 µA
≤ 5 µA
≤ 5 µA
Grenzfrequenz (< 3 dB)
fG
Schutzpegel bei In (Ader-Erde)
GleichstromwiderstandR
600 kHz
600 kHz
600 kHz
600 kHz
4,6 Ω
4,6 Ω
4.6 Ω
4.6 Ω
Längsinduktivität, typ. (L)
28 µH
28 µH
28 µH
28 µH
AnsprechzeittA
≤ 2 ns
≤ 2 ns
≤2 ns
≤ 2 ns
Kapazität Ader-Erde
4 nF
<2,3 nF
≤ 1.5 nF
≤ 1.3 nF
BetriebstemperaturbereichTU
C
-25 - +85 °C
-25 - +85 °C
-25 - +85 °C
-25 - +85 °C
Max. Anschlussdrahtquerschnitt
2,5 massiv or 1,5 Litze with
wircap mm²
2,5 massiv or 1,5 Litze with
wircap mm²
2,5 massiv or 1,5 Litze with
wircap mm²
2,5 massiv or 1,5 Litze with
wircap mm²
Gehäusematerial/Farbe
polycarbonate (halogen-free) UL
94-V0 / yellow
polycarbonate (halogen-free) UL
94-V0 / yellow
polycarbonate (halogen-free) UL
94-V0 / yellow
polycarbonate (halogen-free) UL
94-V0 / yellow
27 06 06
27 12 12
27 15 15
27 24 24
Bestelldaten
Artikel-Nr.
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
183
EMC filter with integrated surge protection
MCR technology with integrated low-pass filter
Technical Data
DP2x1-30V/30V-Tr
DP2x1-36V/36V-Tr
DP2x1-48V/48V-Tr
DP2x1-60V/60V-Tr
IEC category/EN type
C1 / C2 / C3
C1 / C2 / C3
C1 / C2 / C3
C1 / C2 / C3
30 V=
36 V=
48 V=
60 V=
Nominal direct voltage
UN
Max. continuous operating voltage DC
Uc
33 V=
40 V=
53 V=
64 V=
Max. continous operating voltage AC
Uc
22 V~
29 V~
37 V~
45 V~
Nominal current
IN
0,5 A
0,5 A
0,5 A
0,5 A
C2 nominal discharge current (8/20 µs) total (In)
In
20 kA
20 kA
20 kA
20 kA
C2 nominal discharge current (8/20 µs) per line
In
10 kA
10 kA
10 kA
10 kA
≤ 55 V
≤ 72 V
≤ 90 V
Up
≤ 45 V
Leakage current at Umax.
IL
≤ 5 µA
Max. operating frequency (< 3 dB)
fG
600 kHz
600 kHz
600 kHz
600 kHz
DC resistance
R
4.6 Ω
4.6 Ω
4.6 Ω
4.6 Ω
28 µH
28 µH
28 µH
28 µH
tA
≤ 2 ns
Protection level at In (line-earth)
Series inductance, typ. (L)
Response time
Capacitance, line-earth
≤ 1 nF
≤ 1 nF
≤ 0.8 nF
≤ 0.7 nF
-25 - +85 °C
-25 - +85 °C
-25 - +85 °C
-25 - +85 °C
Max. conductor cross section
2,5 massiv or 1,5 Litze with
wircap mm²
2,5 massiv or 1,5 Litze with
wircap mm²
2,5 massiv or 1,5 Litze with
wircap mm²
2,5 massiv or 1,5 Litze with
wircap mm²
Enclosure material / colour
Polycarbonate (halogen-free) UL
94-V0 / yellow
Polycarbonate (halogen-free) UL
94-V0 / yellow
Polycarbonate (halogen-free) UL
94-V0 / yellow
Polycarbonate (halogen-free) UL
94-V0 / yellow
Article-No.
27 30 30
27 36 36
27 48 48
27 60 60
Technical Data
DP2x1-80V/80V-Tr
DP2x1-150V/150V-Tr
IEC category/EN type
C1 / C2 / C3
C1 / C2 / C3
Operating temperature range
C
TU
Order Data
Nominal direct voltage
UN
80 V=
150 V=
Max. continuous operating voltage DC
Uc
85 V=
160 V=
Max. continous operating voltage AC
Uc
60 V~
112 V~
Nominal current
IN
0,5 A
0,5 A
C2 nominal discharge current (8/20 µs) total (In)
In
20 kA
20 kA
C2 nominal discharge current (8/20 µs) per line
In
10 kA
10 kA
Up
≤ 140 V
≤ 250 V
Leakage current at Uc DC
IL
≤ 5 µA
Max. operating frequency (< 3 dB)
fG
600 kHz
600 kHz
DC resistance
R
4,6 Ω
4.4 Ω
≤ 28 µH
28 µH
≤ 1 nF
≤ 1 nF
-25 - +85 °C
-25 - +85 °C
Max. conductor cross section
2,5 massiv or 1,5 Litze with
wircap mm²
2,5 massiv or 1,5 Litze with wircap mm²
Enclosure material / colour
Polycarbonate (halogen-free) UL
94-V0 / yellow
Polycarbonate (halogen-free) UL 94-V0 / yellow
Degree of protection (IEC EN 60529)
IP 20
IP 20
27 80 80
27 04 04
Protection level at In (line-earth)
Series inductance, typ. (L)
Capacitance, line-earth
Operating temperature range
C
TU
Bestelldaten
Article-No.
184
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
EMC filter with integrated surge protection
MCR technology with integrated low-pass filter
DataPro3x1 for DIN rail
Basic circuit diagram
EMC filter for data and signal lines combined with
surge protection enables smooth operation of
sensitive electronic equipment in rough environment.
1
1p
2
2p
n
Signal and data line protection with low-pass filter
n
Protective circuit for 3 signal lines with common
ground
n
Maximum nominal current 500 mA
n
Applicable at the boundaries LPZ 0B - 2 and higher
p
n
Mounting on 35 mm DIN rail
n
Degree of protection according to IEC EN 60529: IP
20
n
Space required for installation: 17.5 mm
Technical Data
DP3x1-12V/12V-Tr
DP3x1-15V/15V-Tr
DP3x1-24V/24V-Tr
DP3x1-30V/30V-Tr
IEC category/EN type
C1 / C2 / C3
C1 / C2 / C3
C1 / C2 / C3
C1 / C2 / C3
12 V=
15 V=
24 V=
30 V=
Nominal direct voltage
UN
Max. continuous operating voltage DC
Uc
13,6 V=
17 V=
28 V=
33 V=
Max. continous operating voltage AC
Uc
12 V~
12 V~
20 V~
22 V~
Nominal current
IN
0,5 A
0,5 A
0,5 A
0,5 A
C2 nominal discharge current (8/20 µs) total (In)
In
20 kA
20 kA
20 kA
20 kA
C2 nominal discharge current (8/20 µs) per line
In
10 kA
10 kA
10 kA
10 kA
Up
≤ 18 V
≤ 23 V
≤ 36 V
≤ 45 V
Leakage current at Umax DC
IL
≤ 5 µA
≤ 5 µA
≤ 5 µA
≤ 5 µA
Max. operating frequency (< 3 dB)
fG
600 kHz
600 kHz
600 kHz
600 kHz
DC resistance
R
4.6 Ω
4.6 Ω
4.6 Ω
4.6 Ω
28 µH
28 µH
28 µH
28 µH
C
≤ 2.3 nF
≤ 1,5 nF
≤ 1.3 nF
≤ 1 nF
Protection level at In (line-earth)
Series inductance, typ. (L)
Capacitance, line-earth
Operating temperature range
TU
-25 - +85 °C
-25 - +85 °C
-25 - +85 °C
-25 - +85 °C
Max. conductor cross section
2,5 massiv or 1,5 Litze with
wircap mm²
2,5 massiv or 1,5 Litze with
wircap mm²
2,5 massiv or 1,5 Litze with
wircap mm²
2,5 massiv or 1,5 Litze with
wircap mm²
Enclosure material / colour
Polycarbonate (halogen-free) UL
94-V0 / yellow
Polycarbonate (halogen-free) UL
94-V0 / yellow
Polycarbonate (halogen-free) UL
94-V0 / yellow
Polycarbonate (halogen-free) UL
94-V0 / yellow
Degree of protection (IEC EN 60529)
IP 20
IP 20
IP 20
IP 20
28 12 12
28 15 15
28 24 24
28 30 30
Order Data
Article-No.
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
185
EMC filter with integrated surge protection
MCR technology with integrated low-pass filter
Technical Data
DP3x1-36V/36V-Tr
DP3x1-48V/48V-Tr
DP3x1-60/60V-Tr
DP3x1-150V/150V-Tr
IEC category/EN type
C1 / C2 / C3
C1 / C2 / C3
C1 / C2 / C3
C1 / C2 / C3
Nominal direct voltage
UN
36 V=
48 V=
60 V=
150 V=
Max. continuous operating voltage DC
Uc
40 V=
53 V=
64 V=
160 V=
Max. continous operating voltage AC
Uc
29 V~
37 V~
45 V~
112 V~
Nominal current
IN
0,5 A
0,5 A
0,5 A
0,5 A
C2 nominal discharge current (8/20 µs) total (In)
In
20 kA
20 kA
20 kA
20 kA
C2 nominal discharge current (8/20 µs) per line
In
10 kA
10 kA
10 kA
20 kA
Up
≤ 55 V
≤ 72 V
≤ 90 V
≤ 250 V
Protection level at In (line-earth)
Leakage current at Umax DC
IL
≤ 5 µA
≤ 5 µA
≤ 5 µA
≤ 5 µA
Max. operating frequency (< 3 dB)
fG
600 kHz
600 kHz
600 kHz
600 kHz
DC resistance
R
Series inductance, typ. (L)
4.6 Ω
4.6 Ω
4.4 Ω
28 µH
28 µH
28 µH
≤ 1 nF
≤ 0.8 nF
≤ 0.7 nF
≤ 1 nF
-25 - +85 °C
-25 - +85 °C
-25 - +85 °C
-25 - +85 °C
Conductor cross section
2.5 mm² flexible with sleeve
2.5 mm² flexible with sleeve
2.5 mm² flexible with sleeve
2.5 mm² flexible with sleeve
Enclosure material / colour
Polycarbonate (halogen-free) UL
94-V0 / yellow
Polycarbonate (halogen-free) UL
94-V0 / yellow
Polycarbonate (halogen-free) UL
94-V0 / yellow
Polycarbonate (halogen-free) UL
94-V0 / yellow
Degree of protection (IEC EN 60529)
IP 20
IP 20
IP 20
IP 20
28 36 36
28 48 48
28 60 60
28 04 04
Capacitance, line-earth
Operating temperature range
C
4.6 Ω
28 µH
TU
Order Data
Article-No.
186
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
EMC filter with integrated surge protection
MCR technology with integrated low-pass filter
DataPro2x1 0,3Ohm-Tr
EMC filter for data and signal lines combined with
surge protection enables smooth operation of sensitive
electronic equipment in rough environment.Lightning
current and surge voltage protection for particularly
long signal and bus lines. Thanks to the extremely low
volume resistance (impedance only 0.3Ω) no noteworthy signal losses occur. It is a combined arrester
to protect two single wires. Applicable at the LPZ
transition point 0A-1 and higher.
Basic circuit diagram
1
1p
2
n
Signal and data line protection with low-pass filter
n
Very low volume resistance
n
Protective circuit for 2 signal lines with common
ground
n
Maximum operating current 1.5 A
2p
n
Applicable at the boundaries LPZ 0A - 2 and higher
n
Mounting on 35 mm DIN rail
n
Degree of protection according to
IEC EN 60529: IP 20
n
Space required for installation: 17.5 mm
Technical Data
DP 2x1-12V/12V-0,3Ω -Tr
DP 2x1-24V/24V-0,3Ω -Tr
DP 2x1-30V/30V-0,3Ω-Tr
DP 2x1-36V/36V-0,3Ω -Tr
IEC category/EN type
C1 / C2 / C3 / D1
C1 / C2 / C3 / D1
C1 / C2 / C3 / D1
C1 / C2 / C3 / D1
12 V=
24 V=
30 V=
36 V=
Nominal direct voltage
UN
Max. continuous operating voltage DC
Uc
28 V=
33 V=
35 V=
40 V=
Max. continous operating voltage AC
Uc
20 V~
22 V~
25 V~
29 V~
Nominal current
IN
1,5 A
1,5 A
1,5 A
1,5 A
Series restistance (DC resistance) per line
Z
0,3 Ω
0,3 Ω
0,3 Ω
0,3 Ω
28 µH
28 µH
28 µH
28 µH
Series inductance, typ. (L)
Response time fine protection
tA
≤ 2 ns
≤ 2 ns
≤ 2 ns
≤ 2 ns
C2 nominal discharge current (8/20 µs)
In
10 kA
10 kA
10 kA
10 kA
D1 lightning impulse current (10/350 µs) in total
Itotal
5 kA
5 kA
5 kA
5 kA
D1 lightning impulse current (10/350 μs) per wire
Iimp
2,5 kA
2,5 kA
2,5 kA
2,5 kA
≤ 18 V
≤ 36 V
≤ 42 V
≤ 55 V
Protection level, residual voltage line-earth at In
resp. 1 kV/µs
Up
Capacitance, line-earth
C
≤ 2,3 nF
≤ 1,3 nF
≤ 1,1 nF
≤ 1 nF
Max. operating frequency (< 3 dB)
fG
<600 kHz
< 600 kHz
< 600 kHz
<600 kHz
Insulation resistance
Operating temperature range
Type of connection
Risol
TU
>10 GΩ
> 10 GΩ
> 10 GΩ
>10 GΩ
-25 - +85 °C
-25 - +85 °C
-25 - +85 °C
-25 - +85 °C
2.5 mm² flexible with sleeve
2.5 mm² flexible with sleeve
2.5 mm² flexible with sleeve
2.5 mm² flexible with sleeve
26 12 12
26 24 24
26 30 30
26 36 36
Order Data
Article-No.
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
187
EMC filter with integrated surge protection
MCR technology with integrated low-pass filter
DataPro2x1-RLC/50V-Tr
For overvoltage protection at single-pole TN
systems with very sensitive electronical devices.
Surge voltage protector for electronical equipment with an operating voltage of up to 50 V DC,
with an impulse current withstand strength of 20
kA (8/20µs). The devices was designed to protect
sensitive electronic equipment.
Basic circuit diagram
n
Signal and data line protection with low-pass
filter
n
Protective circuit for 2 signal lines without
reference to ground potential
n
Maximum nominal current 100 mA
Technical Data
n
Applicable at the boundaries LPZ 0B - 2 and
higher
n
Mounting on 35 mm DIN rail
n
Space required for installation: 17.5 mm (1 TE)
DP 2x1-RLC/50V-Tr
IEC category/EN type
C1 / C2 / C3
Max. continuous operating voltage DC
Uc
50 V=
Nominal current
IN
0,1 A
C2 nominal discharge current (8/20 µs) total (In)
In
20 kA
C2 nominal discharge current (8/20 µs) per line
In
10 kA
Protection level at 1 kV/µs (1p-2p)
Up
≤ 60 V
Protection level at 1 kV/µs (1p,2p-PE)
Up
≤ 650 V
Response time 1p-2p, 2-PE (bei 1 kV/µs)
tA
≤ 2/25 ns
Operating temperature range
TU
-25- +85 °C
Max. conductor cross section
2.5 mm² flexible with sleeve
Enclosure material / colour
Polycarbonate (halogen-free) UL 94-V0 / yellow
Protection circuit casting compound
Polyurethan, flexibel
Degree of protection (IEC EN 60529)
IP 20
Dimension (DIN 43880)
1 TE (17.5 mm)
Order Data
Article-No.
28 70 50
Dimension drawing, see pages 220 to 223
188
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
EMC filter with integrated surge protection
MCR technology with integrated low-pass filter
DataPro2x1-RLC-Tr
EMC filter for data and signal lines combined with
surge protection enables smooth operation of
sensitive electronic equipment in rough environment.
1p
2
2p
Basic circuit diagram
protected side
unprotected side
1
n
Signal and data line protection with low-pass filter
n
Operating voltage up to 150 V DC
n
Protective circuit for 2 signal lines with common
ground
n
Maximum nominal current 500 mA
Technische Daten
DP 2x1-RLC-Tr
IEC-Prüfklasse/EN-Type
C1 / C2 / C3
NenngleichspannungUN
150 V=
Höchste Dauerspannung DC
Uc
170 V=
Höchste Dauerspannung AC
Uc
120 V~
NennstromIN
0,5 A
C2 Nennableitstoßstrom (8/20) gesamt
In
20 kA
C2 Nennableitstoßstrom (8/20) pro Ader
In
10 kA
Leckstrom bei Umax DC
IL
≤ 0,001 µA
Grenzfrequenz (< 3 dB)
fG
100 kHz
GleichstromwiderstandR
4,3 Ω
Längsinduktivität, typ. (L)
185 µH
Kapazität Ader-Erde
C
Schutzniveau Ader-Erde bei 1kV/µs und In
n
Nominal impulse discharge current 20 kA (8/20µs)
n
Mounting on 35 mm DIN rail
n
Degree of protection according to
IEC EN 60529: IP 20
n
Space required for installation: 17.5 mm
≤ 2,2 nF
≤ 800 V
BetriebstemperaturbereichTU
-25 - +85 °C
Max. Anschlussdrahtquerschnitt
2.5 mm² flexible with sleeve
Einbaumaße (DIN 43880)
1 TE (17.5 mm)
Bestelldaten
Artikel-Nr.
27 00 00
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
189
EMC filter with integrated surge protection
MCR technology with integrated low-pass filter
DataPro2-2MB-Tr
EMC filter for data and signal lines combined with
surge protection enables smooth operation of
sensitive electronic equipment in rough environment.
L1
Basic circuit diagram
1
2
1P
n
Signal and data line protection with low-pass
filter
n
Applicable for transmission rates of 2 MBit/s
(ISDN, PCM)
n
Maximum nominal current 500 mA
2P
L2
Technical Data
DP2-2MB-Tr
IEC category/EN type
C1 / C2 / C3
Nominal direct voltage
UN
150 V=
Max. continuous operating voltage DC
Uc
170 V=
Max. continous operating voltage AC
Uc
120 V~
Nominal current
IN
0,5 A
C2 nominal discharge current (8/20 µs) total (In)
In
10 kA
C2 nominal discharge current (8/20 µs) per line
In
5 kA
Protection level line-earth at 1 kV/µs
Up
≤ 600 V
Max. frequency
fG
8 MHz
Operating temperature range
TU
-25 - +85 °C
DC resistance per path
n
Applicable at the boundaries LPZ 0B - 2 and
higher
n
Mounting on 35 mm DIN rail
n
Space required for installation: 17.5 mm (1 TE)
R
0,5 Ω
Signal tranismission rate
bis 2 Mbit/s
Conductor cross section
2.5 mm² flexible with sleeve
Dimension (DIN 43880)
1 TE
Order Data
Article-No.
24 00 17
Dimension drawing, see pages 220 to 223
190
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
EMC filter with integrated surge protection
Notes
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
191
Smooth operation guaranteed
The measuring and testing devices are applied to check the sparkover
voltage of lightning or surge protectors. These periodical tests of the
protective function are demanded by the standards to ensure a steady
and error-free operation.
Down-time caused by overload of the surge protection can be
eliminated by periodical reviews – with measuring and testing
devices from Leutron.
Tested for safety – manually or
automatically:
192
n
Manual measurement with the arrester tester, the varistor tester
or the combined tester
n
F ully automatic measurement with the portable test equipment
for SSCT magazines
nA
vailable adaptors for all types of gas-filled surge protectors
monitoring
Due to their robust design Leutron's measuring
and testing devices are perfectly suited for
regular mobile use.
monitoring
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
193
Portable test equipment
for SSCT (LSA) magazines
Variable adapters
for different types of
magazines
PC interface for remote
control and
data archiving
Robust and mobile
set-up in an easy to
handle aluminium case
194
Fully automated
test of SSCT (LSA)
magazines for overvoltage
protection
monitoring
kombitester
Combined tester
nTo test the sparkover voltage of lightning or surge protectors,
e.g. MOV and gas discharge tubes
Shipment in robust
carrying case
Combined
tester for gas
discharge tubes,
isolating spark gaps and
varistors with a sparkover
voltage of up to
1,100 V
Various adapters and
measuring leads available
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
195
Monitoring
Universal function tester for GDT, MOV and diodes as well as mixed circuits
H65
For the testing of spark over voltage of lightning
and surge voltage arresters, e.g. metal oxide varistors (MOV) and gas-filled surge arrester (GDT) or
individually MOV and GDT. It is a mobile, easy-tohandle and microprocessor operated digital meter
with a large LCD display for maintenance.
n
Digital measuring instrument with large LCD
display
n
9V battery operation or net work power unit
n
Measuring adapter (optional) for all popular
GDTs
Technical Data
H65
Voltage measurement range
40 - 1100 V
Test current
0,8 - 1,11 mA
Display division
1V
Rate-of-Rise (voltage)
1000 V/s
Battery
9 V IEC 22 (compound battery)
External AC/DC adapter
8 - 11 V DC / 200mA
Typical current consumption display
ca. 1 mA
Typical current consumption during measuring activity
Operating temperature range
n
Automatic fixing of indicated value
n
Scope of delivery includes: 1 carrying case, 1
test leads (2 pieces 1m each), 2 test terminals, 1 external power supply 230V
20 - 200 mA
TU
-10 - +35 °C
Dimensions L x W x H
180 x 90 x 30 mm
Enclosure material / colour
self-extinguishing plastic / Black
Order Data
Article-No.
196
87 01 50
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Monitoring
Function tester for GDT and GDT based spark-gaps
H35
For the testing of spark over voltage of lightning
and surge voltage arresters based on expulsiontype spark gap. Mobile, easy-to-handle digital
meter with a large LCD display for maintenance.
n
Digital measuring instrument with large LCD
display
n
9V battery operation or net work power unit
n
Measuring adapter (optional) for all popular
GDTs
Technical Data
H35
Measured value display
LCD, digital, 3,5 stellig in V
Measuring range
40 - 1000 V
Max. testing voltage
1200 V
Test current
0,1 mA
Testing period
min. 1s up to measuring value is seen
Display division
1V
Rate-of-Rise (voltage)
20
Battery
9V IEC 22 (compound battery)
Test terminals (4mm banana jack)
Minuspol: black / Pluspol: red
External AC/DC adapter
8 - 11 V DC/300mA
Typical current consumption in stand-by position
0,2 mA
Typical current consumption during measuring activity
Operating temperature range
n
Automatic fixing of indicated value
n
Scope of delivery includes: 1 carrying case, 1
test leads (2 pieces 1m each), 2 test terminals, 1 external power supply 230 V
35 mA
TU
-10 - +35 °C
Enclosure material / colour
self-extinguishing plastic / black
Dimensions L x W x H
180 x 90 x 30 mm
Order Data
Article-No.
87 00 10
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
197
Monitoring
Function tester for MOV and overvoltage protection diodes
H45
For testing of the spark-over voltage of lightningand surge voltage arresters. Digital measuring
device with large LCD display. Mobile and easyto-handle, usable for the service area.
n
Digital measuring instrument with large LCD
display
n
9V battery operation or net work power unit
n
comprehensive accessories included
Technical Data
H45
Measured value display
LCD, digital, 3,5 stellig in V
Measuring range
40 - 1100 V
Max. testing voltage
1200 V
Test current
800-120 mA
Display division
1V
Testing period
min. 1s bis sich Messwert einstellt
Battery
9 V IEC 6F22 / NEMA-1604-A (Alcaline comound battery)
External AC/DC adapter
230V AC / 8 -12 VDC / 200mA
Typical current consumption in stand-by position
0,2 mA
Typical current consumption during measuring activity
20 - 200 mA
Typical current consumption display
200 mA
Test terminals (4mm banana jack)
Operating temperature range
n
Automatic fixing of indicated value
n
Scope of delivery includes: 1 carrying case, 1
test leads (2 pieces 1m each), 2 test terminals, 1 external power supply 230V
Minuspol: black / Pluspol: red
TU
-10 - +35 °C
Dimensions L x W x H
180 x 90 x 30 mm
Enclosure material / colour
self-extinguishing plastic / black
Order Data
Article-No.
198
16 02 00
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Monitoring
Portable test equipment for GDT in LSA magazines
A46
For the testing of GDT equipped LSA magazines.
The test equipment is embedded in a metal case
which has additional space for accessories like
network adapters and test adapters for different
arrester magazines.
n
PC connection
n
Individual tester can be stored in a PC or
printed via included software
n
Other test adapters are available on request
n
Mobile device in aluminium protection case
Technical Data
A46
Slow ramp (CCITT/VDE)
100 V/s
Fast ramp
1000 V/s
Measuring range
5-800 V
Test current
0,05 mA
Auflösung, intern
12 bit = 0,2 V
Display resolution
1V
Accuracy
+/- 1 V +1 % rel.
Resolution
0,2
Battery
9 V IEC 22
External AC/DC adapter
8-5 V / 50 mA
Typical current consumption in stand-by position
5 mA
Typical current consumption during measuring activity
30 mA
Max. usable positions
30 pos
Order Data
Article-No.
87 01 00
Each GDT in the magazine is tested on both
polarities, and the static dc sparkover voltage is
compared with the tolerance values.
The A45 allows for an accurate measuring of
the dc sparkover voltage, by detecting the first
sparkover with a linear ramp. It is important to
measure on both polarities in order to prevent
damages to the gas-filled surge arrester.
A quality assessment system can be set up with
the software PRO-TEST.
The A46 can operate entirely remote controlled
from a PC via its serial interface. A special
optocoupler-based cable is necessary to provide
an interference protection for the PC.
The whole testing of the magazine takes place
automatically, including the comparison of the
measured values with the tolerance values and
the fault detection. The test of a complete magazine filled with 20 GDTs takes about 13 seconds.
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
199
Monitoring
Pulse counter
Pulse counter
For the potential-free measurement of discharge
currents of surge protective devices. Easy snapon installation on the earth conductor with the
help of an two-piece ring core.
n
Pulse counting assembly in 1.5 TE DIN railmounted device
n
including twisted sensor cable (lenght 1 m)
n
Batteries are included in the delivery scope
Technical Data
LC 1
Ansprechwelle für Stoßströme (Anstiegszeit ≥ 8µs)
> 1 kA
Impulsfolge
<1s
LCD display
0 - 99
Supply
Operating temperature range
n
Push button to adjust the meter reading (e.g.
after battery change)
9 V-battery
TU
-10 - +50 C°
Mounting on
35 mm DIN rail
Enclosure material / colour
Thermoplast, yellow
Degree of protection (IEC EN 60529)
IP 20
Lenght of connection cable (sensor)
max. 1 m
Dimension (L x B x H)
63 x 27 x 90 mm
Sensor
max. conductor cross section 25 mm²
Order Data
Article-No.
200
87 00 05
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Monitoring
Notes
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
201
The strengths of Leutron since 1947
The long experience and, therefore, the lead in research and development
makes Leutron one of the leading manufacturers of isolation spark gaps.
Intelligently designed components, compact constructions and an ideal
choice of rare-gas fillings are only some elements that, in their totality,
provide an optimal protection for various applications in the areas of
electronics and electrical engineering.
Robust and powerful protection against direct lightning strikes –
Leutron's isolation spark gaps.
Gas-filled isolating spark gaps for more
safety:
202
nLow DC and AC voltage protection level
n
Very high ignition constancy even in demanding environments
nMaintenance-free due to automatic signalization in case of an
overload
nIdeally suited for application in explosion-hazard environments
nImproved operator protection due to low sparkover voltage
isolating spark gaps
filled with rare-gas
Secure application
even in explosion-hazard environments
isolating spark gaps
filled with rare-gas
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
203
Isolation spark gap
for mounting on DIN rail
nHigh discharge capacity up to 100 kA (10/350 µs), class H
n Low sparkover voltage
Hermetically
closed, gas-filled
isolation spark gap
Fail-safe
characteristic: The
double fail-save limits the
surface temperature in
case of a fault
Optional remote signalling
on request
204
isolating spark gaps
filled with rare-gas
Isolation spark gaps
for areas in danger of explosion: ATEX
nHigh discharge capacity up to 100 kA (10/350 µs), class H
n Low sparkover voltage
Fail-safe
characteristic: The
double fail-safe limits
the surface temperature in
case of a fault
Hermetically closed,
gas-filled isolation
spark gap
Degree of protection
IP 67 (according to IEC
EN 60529), suited for
outdoor application
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
205
Rare-gas-filled insulation spark gaps
Flexible Mounting
TSF 100 and 500
Rare-gas-filled spark gap for the lightning
protection equipotential bonding, the insulation
of electrically separated parts and the bridging of
insulating flanges of gas pipelines.For internal or
similar applications.
Basic circuit diagram
PE 1
n
High-quality industrial ceramics
n
Rare-gas filled, hermetically sealed
n
Free from radioactive substances
n
High lightning current discharge capacity of
100 kA (10/350 µs)
PE 2
Technical Data
TSF 100
TSF 500
IEC category/EN type
Class H
Class H
100 ±20% V=
500 ±15% V=
Nominal DC sparkover voltage at 100V/s
UagN
n
High reliability, robust
n
Stable performance, long service life
n
Fail-safe characteristic
n
Test standard EN 50164-3
Nominal AC sparkover voltage (50 Hz)
Uaw
70 ±20% V
350 ±15% V
Typical impulse sparkover voltage
Uas
650 V
950 V
Max. impulse sparkover voltage
Uas
950 V
1300 V
100 kA
100 kA
100 kA
100 kA
100 / 1 A
100 / 1 A
200 / 0,5 A
200 / 0,5 A
<70V / <20A V
<230V / <100A V
Insulation resistance at 10V, 100V
> 1 GΩ
>1 GΩ
Self-capacitance at 1 kHz
6 pF
4 pF
Test category/climatic category
DIN IEC 60068-1 / 40/90/21
DIN IEC 60068-1 / 40/90/21
Relative humidity
10%...95% rh
10%...95% rh
Degree of protection
IP 67
IP 67
-40 - +80 °C
-40 - +80 °C
M8 bolt/nut (NIROSTA stainless steel)
M8 bolt/nut (NIROSTA stainless steel)
44 90 69
48 78 01
Lightning impulse current discharge capacity
Iimp (10/350 µs)
Nominal impulse discharge current (10 x 8/20)
5x Nominal alternating discharge current at
50Hz, 1s, 3min pause
Ipeak
In
Iwn
Nominal alternating discharge current (50 Hz)
Spark-gap extinguishing conditions
Operating temperature range
Terminals
Vex
TU
Order Data
Article-No.
Accessories
Product
TSF-H1
Article-No.
44 91 75
For solid fixation of isolation spark gaps TSF100 and TSF500 at the installation.
Dimension drawing, see pages 220 to 223
206
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Rare-gas-filled insulation spark gaps
Flexible Mounting
TSF 50 SWISS
Rare-gas-filled spark gap for the lightning
protection equipotential bonding, the insulation
of electrically separated parts and the bridging of
insulating flanges of gas pipelines.
Basic circuit diagram
PE 1
n
High-quality industrial ceramics
n
Rare-gas filled, hermetically sealed
n
Fault indication via LED
n
Test key to check the indicator function
n
Extremely low sparkover voltage of
50 V AC /100 V DC
PE 2
Technical Data
n
Stable performance, long service life
n
Fail-safe characteristic
n
Test standard EN 50164-3
TSF 50 SWISS
IEC category/EN type
Class 1L
Nominal DC sparkover voltage at 100V/s
UagN
100 ±20 V=
Nominal AC sparkover voltage (50 Hz)
Uaw
50 ±20 V
Typical impulse sparkover voltage
Uas
650 V
Max. impulse sparkover voltage
Uas
950 V
Max. impulse current (10/350µs)
Iimp
Insulation resistance at 10V, 100V
Capacitance at 1 MHz
25 kA
> 1 GΩ
C
6 pF
Relative humidity
10-95% rh
Degree of protection (IEC EN 60529)
IP 66
Terminals
M8 srew terminals
Dimensions (Ø × L)
60 x 137 mm
Order Data
Article-No.
44 91 30
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
207
Rare-gas-filled insulation spark gaps
Flexible Mounting
SGO 70 und 350
Rare-gas-filled spark gap for the lightning
protection equipotential bonding, the insulation
of electrically separated parts and the bridging
of insulating flanges of gas pipelines. Weatherresistant, moulded metal/ceramic isolating spark
gap with terminal lugs for M8 screw connection.
Waterproof moulded in polyurethan diecast.
Basic circuit diagram
PE 1
n
High-quality industrial ceramics
n
Rare-gas filled, hermetically sealed
n
Free from radioactive substances
n
High lightning current discharge capacity of
100 kA (10/350 µs)
PE 2
Technical Data
SGO 70
SGO 350
IEC category/EN type
Class H
Class H
100 ±20% V=
500 ±15% V=
Nominal DC sparkover voltage at 100V/s
UagN
Nominal AC sparkover voltage (50 Hz)
Uaw
70 ±20% V
350 ±15% V
Typical impulse sparkover voltage
Uas
650 V
950 V
Max. impulse sparkover voltage
Uas
950 V
1300 V
100 kA
100 kA
100 kA
100 kA
100 / 1 A
100 A
Lightning impulse current discharge capacity
Iimp (10/350 µs)
Nominal impulse discharge current (10 x 8/20)
5x Nominal alternating discharge current at
50Hz, 1s, 3min pause
Ipeak
In
Iwn
Nominal alternating discharge current (50 Hz)
Alternating current critical load (50 Hz) Iwgr
Insulation resistance at 10V, 100V
Spark-gap extinguishing conditions
200 / 0,5s A
200/0,5s A
4.000 / 0,25 A/s
4.000 / 0,25 A/s
>1 GΩ
>1 GΩ
<70V/ <20A V
< 230 V
Self-capacitance at 1 kHz
9 pF
7 pF
Test category/climatic category
DIN IEC 60068-1 / 40/90/21
DIN IEC 60068-1 / 40/90/21
Relative humidity
10%...95% rh
10%...95% rh
Degree of protection
IP 67
IP 67
-40 - +80 °C
-40 - +80 °C
47 21 17
47 22 13
Operating temperature range
Vex
TU
n
Extremely low sparkover voltage
n
Highly riliable, robust and waterproof
n
Fail-safe characteristic
n
Stable performance, long service life
n
Test standard EN 50164-3
Order Data
Article-No.
Dimension drawing, see pages 220 to 223
208
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Rare-gas-filled insulation spark gaps
Flexible Mounting
TA 100 und 500 C
Rare-gas-filled spark gap for the lightning
protection equipotential bonding, the insulation
of electrically separated parts and the bridging of
insulating flanges of gas pipelines.The product is
for outdoor use where a high level of protection
against lightning and other climatic influences as
well as mechanical stress is needed.
PE 1
Basic circuit diagram
PE 2
n
High-quality industrial ceramics
n
Rare-gas filled, hermetically sealed
n
Free from radioactive substances
n
High discharge capacity up to 100 kA
n
Highly riliable, robust and waterproof
Technical Data
TA 100 C
TA 500 C
IEC category/EN type
Class H
Class H
100 ±20% V=
500 ±15% V=
Nominal DC sparkover voltage at 100V/s
UagN
Nominal AC sparkover voltage (50 Hz)
Uaw
70 ±20% V
350 ±15% V
Typical impulse sparkover voltage
Uas
650 V
950 V
Max. impulse sparkover voltage
Uas
950 V
1300 V
100 kA
100 kA
100 kA
100 kA
100 A
100 A
Lightning impulse current discharge capacity
Iimp (10/350 µs)
Nominal impulse discharge current (10 x 8/20)
5x Nominal alternating discharge current at
50Hz, 1s, 3min pause
Ipeak
In
Iwn
200 / 0,5 A
200/0,5 A
Alternating current critical load (50 Hz) Iwgr
4.000 / 0,25 A/s
4.000 / 0,25 A/s
Spark-gap extinguishing conditions
Vex
<70V / <20A V
< 230V/<100A V
Insulation resistance at 10V, 100V
>1 GΩ
>1 GΩ
Self-capacitance at 1 kHz
9 pF
7 pF
Test category/climatic category
DIN IEC 60068-1 / 40/90/21
DIN IEC 60068-1 / 40/90/21
Relative humidity
10%...95% rh
10%...95% rh
Degree of protection
IP 67
IP 67
-40 - + 80 °C
-40 - +80 °C
48 78 14
48 78 27
Nominal alternating discharge current (50 Hz)
Operating temperature range
TU
n
Extremely low sparkover voltage
n
Stable performance, long service life
n
Fail-safe characteristic
n
Test standard EN 50164-3
Order Data
Article-No.
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
209
Rare-gas-filled insulation spark gaps
Flexible Mounting
SGO 70 and 350 QA
Rare-gas-filled spark gap for the lightning
protection equipotential bonding, the insulation
of electrically separated parts and the bridging
of insulating flanges of gas pipelines.Waterproof
isolating spark-gap for underground installation
(soil). Moulded in PU diecast, with cables.
1m isol.
1m isol .
PE 1
PE 2
Basic circuit diagram
n
High-quality industrial ceramics
n
Rare-gas filled, hermetically sealed
n
Free from radioactive substances
n
High discharge capacity up to 100 kA
n
Extremely low sparkover voltage
Technical Data
SGO 70 QA
IEC category/EN type
Class H
Class H
100 ±20% V=
500 ±15% V=
Nominal DC sparkover voltage at 100V/s
UagN
SGO 350 QA
Nominal AC sparkover voltage (50 Hz)
Uaw
70 ±20% V
350 ±15% V
Typical impulse sparkover voltage
Uas
650 V
950 V
Max. impulse sparkover voltage
Uas
950 V
1300 V
Lightning impulse current discharge capacity I
imp (10/350 µs)
Nominal impulse discharge current (10 x 8/20)
5x Nominal alternating discharge current at
50Hz, 1s, 3min pause
100 kA
Ipeak
In
Iwn
100 kA
100 kA
100/1 A
100/1 A
200 / 0,5 A
200 / 0,5s A
Alternating current critical load (50 Hz) Iwgr
4.000 / 0,25 A/s
4.000 / 0,25 A/s
Spark-gap extinguishing conditions
Vex
Nominal alternating discharge current (50 Hz)
< 70V / <20A V
< 230V/< 100A V
Insulation resistance at 10V, 100V
>1 GΩ
>1 GΩ
Self-capacitance at 1 kHz
9 pF
7 pF
Test category/climatic category
DIN IEC 60068-1 / 40/90/21
DIN IEC 60068-1 / 40/90/21
Relative humidity
10%...95% rh
10%...95% rh
IP 67
IP 67
-40 - +80 °C
-40 - +80 °C
47 21 04
47 21 11
Degree of protection
Operating temperature range
TU
n
Highly reliable, stable functioning
n
Fail-safe characteristic
n
Including 2m connection cables with 25mm²
n
SNAM execution
n
Test standard EN 50164-3
Order Data
Article-No.
Dimension drawing, see pages 220 to 223
210
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Rare-gas-filled insulation spark gaps
ATEX-certificated for explosion hazardous zones
TC 100 and 500 A
ATEX approved Ex-protection category. Lightningprotective equipotential bonding in hazardous
areas, e.g. insulating flanges at gas pipelines, at
ca-thodic corrosion protection and protection of
pressure transmitters.
FS 1
1
M10 Bolzen
M10 thread bolt
M10 Buchse
M10 nut
FS 2
2
PE 1
PE 2
n
High reliability, robust
n
Stable performance, long service life
n
Fail-safe behaviour (twofold)
n
Patented product
n
Test standard EN 50164-3
Basic circuit diagram
n
High-quality industrial ceramics
n
Rare-gas filled, hermetically sealed
n
Free from radioactive substances
n
Extremely low sparkover voltage
n
High discharge capacity up to 100 kA
Technical Data
TC 100 A
TC 500 A
IEC category/EN type
Class H
Class H
100 ±20% V=
500 ±15% V=
Nominal DC sparkover voltage at 100V/s
UagN
Nominal AC sparkover voltage (50 Hz)
Uaw
70 ±20% V
350 ±15% V
Typical impulse sparkover voltage
Uas
650 V
950 V
Max. impulse sparkover voltage
Uas
950 V
1300 V
100 kA
100 kA
10x 100 kA
100 kA
100/s A
100 A
Lightning impulse current discharge capacity
Iimp (10/350 µs)
Ipeak
Nominal impulse discharge current (10 x 8/20)
5x Nominal alternating discharge current at
50Hz, 1s, 3min pause
In
Iwn
Nominal alternating discharge current (50 Hz)
200/0,5s A
200 / 0,5s A
< 70V / < 20A V
< 230 V/ 100A V
Insulation resistance at 10V, 100V
>1 GΩ
>1 GΩ
Self-capacitance at 1 kHz
20 pF
20 pF
Test category/climatic category
DIN IEC 60068-1 / 40/90/21
DIN IEC 60068-1 / 40/90/21
Relative humidity
10%...95% rh
10%...95% rh
Degree of protection
IP 67
IP 67
ATEX protection class
Ex II 2G EEx m II T3 ( ZELM 02 ATEX 0095X) EX II 2G EEx m II T3 (ZELM 02 ATEX 0095x)
Spark-gap extinguishing conditions
Operating temperature range
Vex
TU
-40 - +90 °C
- 40 - +90 °C
48 78 30
48 78 50
Order Data
Article-No.
Accessories
Product
K1/150
K1/300
IF3
IF1
Article-No.
49 51 06
49 51 08
82 30 16
82 30 11
Connectors are made of hot-dip galvanized steel
and have a 20mm drill hole for Installation.
Connecting cable set K1 for TC 100A and TC
500A spark gaps
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
211
Rare-gas-filled insulation spark gaps
DIN rail mounting
TSF for DIN rail mountig
Rare-gas-filled spark gap for the lightning
protection equipotential bonding, the insulation
of electrically separated parts and the bridging of
insulating flanges of gas pipelines.
Basic circuit diagram
PE 1
n
AC spark-over voltage : 70 V
n
DC spark-over voltage : 100 V bzw. 500 V
n
DC impulse spark-over voltage (1kV/µs): 650 V
n
Lightning impulse current resistance
(10/350µs): 100 kA
PE 2
Technical Data
TSF 50-Tr
TSF 100-Tr
TSF 500-Tr
IEC category/EN type
Class 1L
Class H
Class H
100 ±20% V=
500 ±20% V=
Nominal DC sparkover voltage at 100V/s
UagN
Nominal AC sparkover voltage (50 Hz)
Uaw
70 ±20% V
350 ±20% V
Typical impulse sparkover voltage
Uas
650 V
950 V
Max. impulse sparkover voltage
Uas
950 V
1300 V
25 kA
100 kA
100 kA
25 kA
100 kA
100 kA
100 A
100/1 A
200 A / 0,5s A
200/0,5s A
Lightning impulse current discharge capacity
Iimp (10/350 µs)
Nominal impulse discharge current (10 x 8/20)
5x Nominal alternating discharge current at
50Hz, 1s, 3min pause
Ipeak
In
50 ±15% V
Iwn
Nominal alternating discharge current (50 Hz)
n
Mounting on 35 mm DIN rail
n
Test standard EN 50164-3
n
Degree of protection according to
IEC EN 60529: IP 20
Alternating current critical load (50 Hz) Iwgr
4.000 A / 0,25s A/s
4000/0,25 A/s
Spark-gap extinguishing conditions
Vex
<70V / < 20A V
< 230 V/ < 100 A V
Insulation resistance at 10V, 100V
>1 GΩ
>1 GΩ
> 1 GΩ
Self-capacitance at 1 kHz
6 pF
6 pF
4 pF
Test category/climatic category
DIN IEC 60068-1 /
40/90/21
DIN IEC 60068-1 /
40/90/21
DIN IEC 60068-1 / 40/90/21
10%...95% rh
10%...95% rh
10%-95% rh
-40 - +80 °C
-40 - +80 °C
-40 - +80 °C
50mm² stranded /35mm²
flexible
50mm² stranded /35mm²
50mm² stranded /35mm² flexible
flexible
44 90 76
44 90 80
Relative humidity
Operating temperature range
Max. conductor cross section
TU
Order Data
Article-No.
44 90 85
Dimension drawing, see pages 220 to 223
212
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Rare-gas-filled insulation spark gaps
DIN rail mounting
TF for mounting rail
Protects measuring transformers; lightning and
surge voltage protector for 1A respectively 5A
cores in current transformers.
I 1 / n 1 (x 1 )
Thermoschalter
Basic circuit diagram
n
K1
n
Very high impulse and AC current resistivity
n
No blow-out vents, thus, not requiring any
safety clearance to other installations
n
High insulation resistance Risol: >10 GΩ
n
Very long service life
Pk
Technical Data
n
Lightning impulse current discharge capacity
100 kA (10/350µs)
n
Rremote signal contact (PK)
TF 100Tr/Th-Pk
TF 500-Tr
TF 500Tr/Th-Pk
TF 2000Tr/Th-Pk
DC spark-over voltage (Uag)
Uag
100 ±20% V=
500 ±20% V=
500 ±20% V=
2000 (-10% / +20%) V=
AC spark-over voltage
Uaw
70 ±20% V~
350 ±20% V~
350 ±20% V~
1414 (-10% /+-20%) V~
< 3.000 V
Impulse sparkover voltage at 1 kV/μs
Uas
typ. 650 / max. 900 V
typ. 1000 / max. 1300 V
typ. 1000 / max. 1300 V
Impulse sparkover voltage at 1 kV/ns (100 MHz)
Uas
typ. 1600 / max. 1900 V
typ. 2800 / max. 3000 V
typ. 2800 / max. 3000 V
CapacitanceC
≤ 18 nF
≤ 6 nF
≤ 16 [pF] nF
<=16 nF
Insulation resistance at 10 V
≥ 1 GΩ
≥ 1 GΩ
≥ 1 GΩ
≥ 1 GΩ
10x 100 kA
10x 100 kA
10x 100 kA
10 x 100 kA
1x 100 kA
1x 100 kA
1x 100 kA
1 x 60 kA
50 As
50 As
50 As
30 As
2500 kJ/Ω
2500 kJ/Ω
2500 kJ/Ω
900 kJ/Ω
20x 60 kA
20x 60 kA
20x 60 kA
20 x 60 kA
Lightning impulse current Iimp (10/45 µs)
+ half-wave 1.6 kA (DIN 48810) (Q)
10 As
10 As
10 As
10 As
Lightning impulse current Iimp (10/45µs)
+ half-wave 1.6 kA (DIN 48810)
100 kJ/Ω
100 kJ/Ω
100 kJ/Ω
100 kJ/Ω
100 A
100 A
100 A
100 A
Ris
Nominal discharge current (8/20)
In
Lightning impulse current (10/350 µs)
(Iimp) + long-time current 200 A/0.5 s/100 As
W/R
Lightning impulse current (10/350 µs)
(Iimp)+long-time current 200 A/0.5 s/100 As
Ipeak
Lightning impulse current (10/350 µs)
(Iimp)+ long-time current 200 A/0.5 s/100 As
Lightning impulse current Iimp (10/45 µs)
+ half-wave 1.6 kA (DIN 48810)
Ipeak
5x Nominal alternating discharge current
at 50Hz, 1s, 3min pause
Iwn
Operating temperature range
TU
-40 - +75 °C
-40 - +75 °C
-40 - +75 °C
-40 - +75 °C
Conductor cross section
25 mm²
25 mm²
25 mm²
25 mm²
Max. connection torque for terminals
4,5 Nm
4,5 Nm
4,5 Nm
4,5 Nm
53 43 72
53 43 98
53 43 85
55 04 11
Order Data
Article-No.
Dimension drawing, see pages 220 to 223
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
213
Smaller, more compact and most efficient
Extended metal structures like gas pipelines are endangered by induced
AC voltages from high-voltage overhead lines and suchlike. These voltages
can cause corrosion and pitting and, therefore, have to be diverted.
Leutron's PLPro is the most compact and, at the same time, most robust
solution available for such problems.
The application of Leutron's worldwide tried and tested technology
saves time and money.
Protection of outdoor installations:
214
nMonitoring possible by remote measurement of the current flow
nLightning current carrying capacity up to lightning protection
level LPL 1
nNo interference with detection signals on pipelines
nCascadable, i.e., adaptable to the value of the current to divert
nReliable diversion of harmful AC voltages in metal structures
Protective devices
for AC arresting
Leutron's protective devices are
maintenance-free due to enclosed arresters
Protective devices
for AC arresting
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
215
AC current diverter for 80 A for the
protection of cathodic corrosion
protection systems (CCPS) of pipelines
nHigh discharge capacity up to 100 kA (10/350 µs), class H
n Low sparkover voltage
Cascadable to divert
higher currents
216
Lightning
current up to 100 kA
(10/350 µs), suited for
lightning protection level
LPL 1
Arresters
up to 80 A AC
No interference
with detection signals
on pipelines due to a
bandpass filter
Integrated current
transformer to monitor
the diverted current
continuously
Connection terminal up to
150 mm2
Protective devices
for AC arresting
Reference: V&C Kathodischer
Korrosionsschutz Ges.m.b.H., Austria
»For a number of years we now use Leutron's PLPro system to
divert alternating currents. The systems installed so far operate
smoothly, and we never received any complaints from customers.
At the insulating flanges of our cathodic corrosion protection
systems we very often apply ATEX certified isolation spark gaps
TC 100 A. They too work to the satisfaction of our customers. So
far no malfunction or break-down occurred.«
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
217
Protective devices for AC arresting
AC-current diverter up to AC 80A with lightning protection
PLPro
With an active cathodic corrosion protection the
installation is permanently protected against
the electrochemical process of corrosion. For
that matter a grid supplied rectifier is inserted
between the installation (e.g. a pipeline) and an
anode that serves as earth electrode. By connecting two or three PLPro units in parallel the overall
current can be elevated up to 80 respectively
120 A.
Basic circuit diagram
n
AC discharge current: 40 or 80 A
n
Several PLPro devices can be connected in
parallel to raise the total discharge current
nMaintenance-free, without liquids
n
No disturbance of search signals
Technical Data
Rated voltage (P-E)
Max. continuous diverting current 50Hz (P-E)
Short-time discharge current for 1s/50Hz (P-E)
PLPro-40A-iV
PLPro-80A-iV
Umax
25 V=
25 V=
IA
40 A~
80 A~
Imax
400 A~
400 A~
Leakage current (P-E)
IL
≤ 1 mA
≤ 1 mA
Nominal discharge current (8/20 µs) (P-E)
In
10x 100 kA
10x 100 kA
100 kA
100 kA
-40 - +80 °C
-40 - +80 °C
Lightning impulse current (10/350)
Operating temperature range
Iimp
TU
Terminals (P/E)
min. 16 / max. 150 mm²
min. 16/max. 150 mm²
Current transformer
100:1 A
100:1 A
25 mm²
max. 2,5 mm²
-20 - +45 °C
-20 - +45 °C
Mounting type
Wall mounting
Wall mounting
Dimensions L x W x H
400 x 300 x 132 mm
600 x 400 x 132 mm
Degree of protection (IEC EN 60529)
IP 65
IP 65
55 04 40
55 04 41
Terminals (current transformer i1, i2)
Current transformer: operating temperature
T
n
Monitoring of discharge current with integrated current transformer possible
n
Integrated lightning and surge current protection up to 100 kA (10/350 µs)
n
Safety switch for discharging the capacitors
Order Data
Article-No.
Dimension drawing, see pages 220 to 223
218
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Standards
Test Standards/application standards
Test Standards
Application standards
DIN EN 61643-11
VDE 0675-6-11:2007-08
DIN EN 62305-1
VDE 0185-305-1:2011-10
Low-voltage surge protective devices - Part 11: Surge protective devices connected to low-voltage power systems - Requirements and tests (IEC616431:1998 + corrigendum 1998, modified); German version EN 61643-11:2002
+ A11:2007
Protection against lightning - Part 1: General principles (IEC 62305-1:2010,
modified); German version EN 62305-1:2011
IEC 61643-1:2005-03
Protection against lightning - Part 2: Risk management (IEC 62305-2:2006);
German version EN 62305-2:2006
Low-voltage surge protective devices - Part 11: Surge protective devices
connected to low-voltage power systems - Requirements and test methods
DIN EN 61643-21
VDE 0845-3-1:2010-03
Low voltage surge protective devices - Part 21: Surge protective devices
connected to telecommunications and signalling networks - Performance
requirements and test methods (IEC61643-21:2000 + Corrigendum 2001 +
A1:2008, modified); German version EN 61643-21:2001 + A1:2009
IEC 61643-21 (2009-04) Ed. 1.1
IEC 61643-21:2000 + A1:2008
DIN EN 62305-2
VDE 0185-305-2: 2006-10
DIN EN 62305-3
VDE 0185-305-3: 2011-10
Protection against lightning - Part 3: Physical damage to structures and life
hazard (IEC 62305-3:2010, modified); German version EN 62305-3:2011
DIN EN 62305-4
VDE 0185-305-4:2011-10
Protection against lightning - Part 4: Electrical and electronic systems within
structures (IEC 62305-4:2010, modified); German version EN 62305-4:2011
Low voltage surge protective devices - Part 21: Surge protective devices
connected to telecommunications and signalling networks - Performance
requirements and testing methods
IEC 62305-1 (2010-12) Ed. 2.0
DIN EN 50164-3
VDE 0185-203:2009-09
Protection against lightning - Part 2: Risk management
Lightning Protection Components (LPC) - Part 3: Requirements for isolating
spark gaps; German version EN 50164-3:2006 + A1:2009
DIN EN 60715:2001-09
Dimensions of low-voltage switchgear and controlgear - Standardized mounting on rails for mechanical support of electrical devices in switchgear and
controlgear installations (IEC 60715:1981 + A1:1995); German version EN
60715:2001
Protection against lightning - Part 1: General principles
IEC 62305-2 (2010-12) Ed. 2.0
IEC 62305-3 (2010-12) Ed. 2.0
Protection against lightning - Part 3: Physical damage to structures and life
hazard
IEC 62305-4 (2010-12) Ed. 2.0
Protection against lightning - Part 4: Electrical and electronic systems within
structures
DIN EN 60529
VDE 0470-1:2000-09
Degrees of protection provided by enclosures (IP code) (IEC 60529:1989 +
A1:1999); German version EN 60529:1991 + A1:2000
IEC 60529 (2001-02) Ed. 2.1
Degrees of protection provided by enclosures (IP Code)
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
219
dimension drawing
220
CT Product line
EnerPro 230 SDU
MP RK Product line
CPS+ Product line
PP PV 800 and PP PV 1000
DataPro (DP) Product line
EnerPro D 230 SM
CT PV Product line
DataPro RJ45-CAT6-48V-Tr
EnerPro D 230 KM
Busbar KA
DataPro RJ45 f/f
NM 22V/5kA
MP Product line
DataPro-1xRJ45PoE-Alu
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
dimension drawing
DataPro 8xRJ45-6V-WG
TelPro LSA – SSCT magazines
DataPro 10LSA (10 SSCT)
DataPro 1x8 to 3x8RJ45-19“
TelPro LSA – SSCT magazines
SSCT disconnection module LSA 2/10-TR
DataPro 4x8 to 6x8RJ45-19“
TelPro LSA – SSCT magazines
SSCT connection module LSA 2/10-AN
DataPro ISDN-aP
LSA – SSCT Connector fine and coarse protection
SSCT ground module LSA 2/10-ER38-rot
DataPro-TAE/NFN-aP
LSA – SSCT Connector coarse protection
LSA – SSCT frame
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
221
dimension drawing
222
SSCT ground bar
DataPro BNC 50 Ohm
DataPro Koax 7/16
SSCT magazine cover
AntPro 5,8GHz SMA
AntPro Lambda 7/16 0.42GHz
SSCT backmount frame
AntPro Koax-GSM-N/230 (f/f)
DataPro Koax 7/16 (f/f)
DataPro-SAT and DataPro-Radio/TV
AntPro Lambda/4 N 0.51GHz
AntPro Lambda/4 7/16 TRI
DataPro Koax-8V-BNC
AntPro Lambda/4 N 0.51GHz (f/f)
AntPro Lambda/4 7/16 TRI (f/f)
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
dimension drawing
EnerProFilter 230-Tr, EMC Filter
TSF 50 SWISS
EPF, EMC Filter (single-phase)
SGO 70 and 350
EPF, EMC Filter (three-phase) up to 35 A
TA 100C and 500C
EPF, EMC Filter (three-phase) from 63 A
SGO 70QA and 350QA
TSF 100 and 500
TC 100A and 500A
PLPro 40A-IV
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
223
Technical terms
A
Active Parts
Active parts are conductors and conductive parts of equipment that
are alive under normal operational conditions.
Aging
Aging is the alteration of the original conductivity. It is caused by
disturbance pulses, normal operation or unfavourable environmental
conditions.
Approach (today: Separation Distance)
An approach is a too narrow distance between the lightning protection installation and conductive installations or electrical installations
with a risk of a flashover or breakdown at lightning strikes.
Arc Voltages Ubo
The arc voltage is the instantaneous value of the voltage over a
discharge path during an arc discharge process.
Arresters
Equipment that in general consists of voltage-controlled resistors
and/or spark gaps. Both items can be used separately or connected
in series or in parallel. Arresters protect other electrical equipment or
installations against unacceptable high surge voltages.
Asymmetrical Interference
“Asymmetrical” means that the interference source or drain is related
to the ground. It exists a capacitive or galvanic connection to the
protective conductor.
Asymmetrical Voltage, Common-Mode Voltage
Average voltage between every conductor and a specified reference
point, usually reference earth or ground.
B
C
224
D
Direct or Close-up Strikes
Direct and close-up strikes cause surge voltages with an energy
content that contains a considerable part of the total energy of a
lightning discharge.
Disconnection Device
If an arrester fails to operate, the disconnection device separates it
from the power grid to avoid a fire hazard and to report the defective
arrester. Note: It is not the task of the disconnection device to ensure
the protective measure „Protection at indirect contact“.
Disturbance Voltage, symmetrical
The symmetrical disturbance voltage is a disturbance voltage
between two wires of a conductor (e.g. at a double-circuit line) or
between the terminals of an electrical installation for such a line.
E
Earth
Earth signifies the ground or the soil.
Earthing (noun)
Earthing refers to the total of all means and measures for earthing.
Earthing (verb)
To earth means to connect a conductive part, e.g. the lightning protection installation, via an earth-termination system to the earth.
Earthing Conductor
The earthing conductor connects the installation which has to be
earthed with the earthing electrode, as far as the earthing conductor
runs above soil or insulated in the soil.
Burst
A burst consists of repeatedly occurring pulses within a certain time
period.
Earthing Electrode
An earthing electrode is a conductor buried into the ground with an
electrically conductive connection to the earth. Parts of connectors
that run to the earthing electrode which are lying non-insulated in the
ground are part of the earthing electrode as well.
Combined Arrester
The combined arrester is a surge-voltage protection device consisting
of lightning current arrester and surge arrester.
Electromagnetic Compatibility (EMC)
The electromagnetic compatibility of a device or a system is its capability of a satisfactory operation in its electromagnetic environment,
without causing unacceptable electromagnetic disturbances to other
installations in this environment.
Combined Impulse
A combined impulse is generated by a combination wave generator
which generates a no-load impulse voltage (1.2/50), respectively, a
short-circuit impulse current (8/20). The voltage, the amplitude of the
current and the waveforms are determined by the generator and the
impedance of the SPD. The ratio of the peak values of the no-load
voltage and the short-circuit current is 2 Ω. This value is called the
fictitious impedance Zf. The short-circuit current is referred to as Ics.
Uoc is the no-load voltage of the generator.
Electromagnetic Interference
The electromagnetic interference refers to a quality loss in operational behaviour, a malfunction or the breakdown of an electrical or
electronically device caused by an electromagnetic disturbance.
Critical Discharge Current iSG
The critical discharge current is a current pulse of the waveform 8/20
μs which just about triggers the disconnection device and which does
not yet lead to a mechanical damage of the arrester.
Endurance Test
In an endurance test the surge arrester has to undergo load tests,
that simulate loads frequently occurring in practice.
Electrostatic Discharge (e.s.d.)
An electrostatic discharge is the transfer of electric charges between
objects with different electrostatic potentials, which takes place at
approximation or contact.
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Technical terms
Equipotential Bonding (Potential Equalization)
Potential equalization means to remove potential differences (at the
operation of consumer‘s electrical installations), e.g. between the protective conductor of the electrical power installation and the pipes for
the water, gas and heating supply, as well as between the individual
pipes. The equipotential bonding at lightning effects requires measures beyond the specifications of VDE 0190. Therefore, the lightning
protection installation is connected to other conductive installations
via conductors or isolation spark gaps and, if necessary, to active
parts of electrical installations via surge protection devices. These
measures are called “lightning protection potential equalization”.
Impulse Sparkover Voltage of a Surge Protection Device
Highest voltage value between the electrodes of the spark gap of a
surge protection device, just before the sparkover occurs.
Impulse Voltage (1.2/50)
This impulse voltage has a front time (between 10 % and 90 % of its
peak value) of 1,2 μs and a time to half-value of 50 μs (at Uoc = 6
kV).
Equipotential Bonding Bar
This bar connects protective conductors, potential equalization conductors and, where applicable, functional earthing conductors with
the earthing conductor and the earth electrodes.
F
G
I
Follow-on Current If
The follow-on current flows through the SPD after the diverting process. It is supplied from the grid and differs fundamentally from the
continuous operating current.
Foundation Earthing Electrode
The foundation earthing electrode is a conductor that is embedded
into the concrete foundation of a construction.
Gas-filled Surge Arrester (GDT)
A gas-filled surge arrester is a discharge path filled with another gas
than air, normally rare gas.
Ground Resistance
The ground resistance is the resistance between the earthing system
and the reference earth. The amount of the ground resistance depends on the interaction of the individual earthing electrodes.
Impulse Current (8/20)
This impulse current has a front time of 8 μs and a time to half-value
of 20 μs.
Impulse Withstand Voltage Ust
The impulse withstand voltage is the peak value of the highest
pulse voltage of a predefined waveform and polarity, which does not
result in a breakdown under predefined test conditions. The impulse
withstand voltage is equal to or higher as the rated impulse withstand
voltage.
Insertion Loss
The insertion loss of an SPD is, at a given frequency, the ratio of the
voltages at a supply network point immediately downstream to the
SPD before and after the insertion of this SPD. The value is given in
decibel.
Insulation Resistance Riso
The insulation resistance is the resistance of the surge arrester in the
non-conductive state.
Interference Suppression
Interference suppression comprises all measures to abate or avoid
electromagnetic interferences.
Isolation Spark Gap
The isolation spark gap is a spark gap to isolate conductive parts of
an installation. When the spark gap is triggered by a lightning strike,
the parts are temporarily conducted (lightning-protection equipotential bonding).
L
Lightning Current Arrester
The lightning current arrester is a surge-voltage protection device
which is capable of carrying direct lightning currents.
Impulse Discharge Current
Discharge current that flows through the arrester after it is triggered.
It is given as a peak value. The nominal impulse discharge current is
the peak value of an impulse current of the pulse form 8/20 μs.
Lightning Impulse Current Discharge (Lightning Impulse
Current)
The 10/350 μs lightning impulse current has a front time of 10 μs
and a time to half-value of 350 μs.
Lightning Impulse Current Iimp
The lightning impulse current Iimp is defined by its peak value Imax,
its charge Q and the specific energy W/R with a 10/350 μs waveform.
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
225
Technical terms
Potential Equalization Conductor
The potential equalization conductor is a conductive link to achieve
potential equalization.
Lightning Protection Installation
The lightning protection installation is the sum of all equipment for
the external and internal lightning protection of the installation to be
protected.
Potential Equalization Installation
The potential equalization installation is the total of all interconnected potential equalization conductors, including all other conductive
parts which work in the same way, e.g. housings or other conductive
installations. The potential equalization installation can either be the
earth-termination system or part of it.
Lightning Surge Voltage
The lightning surge voltage is a surge voltage caused by a lightning
discharge.
Longitudinal Voltage Drop
The longitudinal voltage drop is a means (instead of the insertion loss)
to evaluate overvoltage arresters for d.c. voltages or low operating
frequencies up to a maximum of 400 Hz. The longitudinal voltage
drop is measured along the current path or paths at nominal current
and, where applicable, operating frequency.
M
Main Supply Short-Circuit Current IK
The main supply short-circuit current is the short-circuit current
which results from the impedance of the test network and the connecting cables at the installation point of the test object.
Measured Limiting Voltage
Maximum voltage that is measured at the terminals of an SPD while
pulses with a preset form and amplitude are applied.
N
Power-Frequency Withstand Voltage
The power-frequency withstand voltage is the r.m.s. value of the
highest sinusoidal voltage at system frequency, which does not result
in a breakdown under predefined test conditions.
Protection Level Up
The protection level is a parameter which characterizes the performance of an SPD to limit the voltage between its terminals. The
protection level is chosen from a list of standard values and has to
exceed the highest value of the measured limiting voltages.
Protection Path
The parts of an SPD can be connected as “conductor against
conductor” or “neutral conductor against earth”, or a combination of
these possibilities. These methods of connection are called protection
paths.
Pulse
A pulse is a rapid, temporary change of a physical parameter followed
by a fast change back to the original value.
R
Nominal Alternating Discharge Current Iwn
The nominal alternating discharge current is the alternating current
with frequencies between 15 and 62 Hz (primarily 50 Hz), which the
test object is dimensioned for in a specific test procedure.
Rate of Rise
The rate of rise is the average change rate of a parameter between
two certain values, e.g. between 10 % and 90 % of the peak value.
Nominal Impulse Discharge Current In
The nominal impulse discharge current is the peak value of a current
with the waveform 8/20 that flows through a surge protection device.
It is used to classify the test for class II surge protection devices.
Rated Voltage of an Arrester Uc
Maximum acceptable root-mean-square value of the power-frequency a.c. voltage that can be permanently applied to the terminals of
the arrester.
Nominal Load Current IL
The nominal load current is the maximum continuous, alternating
or direct current which can flow from the output of an SPD to the
connected load.
Nominal Voltage UN
The nominal voltage, as a rounded voltage value, specified by the
manufacturer of an electrical apparatus to identify it and to specify
the voltage range for which it is designed.
O
Overvoltage Category
The overvoltage category is the classification of a piece of electrical
equipment to the expected overvoltages.
226
P
The test is carried out according to the test procedure of the operation duty test. It is used to classify the test for class I surge protection
devices.
Reference Earth
Reference earth is the reference ground (especially the earth’s surface) that is so far apart from the earthing electrodes that, if a current
is diverted into the ground, no relevant voltage differences occur
between the points of this area.
Remote Signalling Contact
Remote signalling contacts belong to a circuit which is separated
from the main circuit of the SPD. The disconnection device of the SPD
and/or an operation indication are part of the same circuit.
Remote Strikes
Remote strikes cause surges with a considerable smaller energy
content compared to close-up strikes.
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Technical terms
Residual Current Protective Device (RCD)
Residual current protective devices disconnect the circuit if the residual current against earth exceeds a certain value.
Transverse Voltage
The transverse voltage is the interference voltage which occurs
between two conductors of the same circuit.
Residual Voltage Ures
The residual voltage is the peak value of the voltage that appears between the terminals of an SPD during the flow of a discharge current
or immediately after it.
Triggering Current of the Disconnection Device
The triggering current of the disconnection device is the root-meansquare value of the current through the arrester, which causes the
disconnection device to operate within 30 seconds.
Short-circuit Withstand Capability
The short-circuit withstand capability is the highest unaffected shortcircuit current the surge protection device can withstand.
Triggering
Triggering is referred to, if either the peak value of the ohmic component of the current through the arrester reaches 5 mA or a voltage
drop caused by the rise of the peak value of the current through the
arrester exceeds 5 mA.
S
Sparkover Voltage
The sparkover voltage is the highest instantaneous value of the voltage at the terminals of an arrester, just before it is triggered.
Specialist in Lightning Protection
A specialist in lightning protection has a professional training,
knowledge and expertise as well as knowledge of the corresponding
regulations that allow him to assess the work assigned to him as well
as to identify possible dangers. (To judge the professional training,
one can also consider several years of working in the corresponding
field.)
Status Display
The status display indicates the state of operation of an SPD.
Surge Voltage
A surge voltage is a voltage that puts people and/or technical equipment like conductors and devices at risk. It can permanently (overvoltage) or temporarily (surge voltage) occur between conductor and
earth in error-free installations (in disconnected conductors as well).
Surge-voltage Protection Device (SPD
A surge-voltage protection device limits transient surges and diverts
impulse currents. It includes at least one non-linear component.
T
Temperature Range
The temperature range describes the lowest and highest temperatures that are allowed at or inside the housing. For devices without
self-heating this range refers to the ambient temperature. For devices
with self-heating it indicates the maximum operating temperature
range.
TOV Characteristics
The TOV characteristics describe the behaviour of an SPD to which a
temporary overvoltage (TOV) is applied for a certain period of time.
Transient
A transient is a non-periodic and very short positive or negative
change of voltage or current between two steady states.
transient
A transient behaviour describes the behaviour of a phenomenon or
value which changes between two consecutive steady states in a very
short time in comparison to the considered timescale.
V
W
Varistors
A varistor is a bipolar non-linear resistor with symmetrical voltagecurrent characteristics. Its resistance decreases with increasing
voltage.
Withstand Voltage
The withstand voltage is the maximum voltage that can be applied
to a current-limiting component of an SPD without affecting it. This
voltage can be equal to the highest continuous operating voltage Uc
of the SPD or higher, depending on the components inside the SPD.
Abbreviations
CCP
Cathodic Corrosion Protection
CCPS Cathodic Corrosion Protection System
EBS
Equipotential Bonding Strip
ESD
Electrostatic Discharge
FM
Remote Signalling Contact (Changeover Contact)
FS
Fail-safe
GDT
Gas-Filled Surge Arrester
LEMP Lightning Electromagnetic Impulse
LPL
Lightning Protection Level
LPMS LEMP Protection Measures System
LPS
Lightning Protection System
LPZ
Lightning Protection Zone
MBC Miniature Circuit Breaker
MOV Metalloxyd Varistor
Potential-free Contact (Break Contact)
PK
RCD Residual Current Device
SEMP Switching Electromagnetic Pulse
SPD
Surge Protective Device
SSCT Solderless and Screwless Connection Technology
SVE
Surge Voltage Protection Equipment
SVP
Surge Voltage Protector
Technical Connection Requirements for Electrical Power
TAB
Installations
Temporary Overvoltage
TOV
VDEW Vereinigung deutscher Elektrizitätswerke e.V. (German
Association for the Power Supply Industry)
VdS
Verband der Sachversicherer (Property Insurer Association)
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
227
Product Register
Numeric
Item no. Product name
Item no. Product name
Page
Item no. Product name
Page
140
25 30 85 EPF 230V/35A-S
177
04 00 01 AntPro Koax-GSM-N/230
162
24 00 42 DP 1LSA-15-PTC 04 00 04 AntPro Koax-GSM-N-230(f/f)
162
24 00 43 DP 1LSA-24-PTC 140
25 31 00 EPF 230/400V/35A-W
179
04 00 20 AntPro Lambda/4 N 0.51GHz
163
24 00 44 DP 1LSA-48-PTC 141
25 31 30 EPF 230/400V/63A-E
180
04 00 21 AntPro Lambda/4 N 0.51GHz (f/f)
164
24 00 45 DP 1LSA-60-PTC 141
25 31 40 EPF 230/400V/100A-E
180
04 00 22 AntPro Lambda/4 N 0.8GHz
163
24 00 46 DP 1LSA-110-PTC
141
25 31 60 EPF 230/400V/200A-E
180
04 00 23 AntPro Lambda/4 N 2.0GHz
163
24 00 47 DP 1LSA-180FS 142
26 12 12 DP 2x1-12V/12V-0,3Ω -Tr
187
04 00 24 AntPro Lambda/4 N 2.0GHz (f/f)
164
24 00 48 DP 1LSA-T110FS-PTC 143
26 24 24 DP 2x1-24V/24V-0,3Ω -Tr
187
04 00 30 AntPro Lambda/4 7/16 TRI
167
24 00 49 DP 1LSA-TK180FS
144
26 30 30 DP 2x1-30V/30V-0,3Ω-Tr
187
04 00 31 AntPro Lambda/4 7/16 TRI (f/f)
168
24 00 61 DP 1LSA-C48FS-PTC
146
26 36 36 DP 2x1-36V/36V-0,3Ω -Tr
187
04 04 25 AntPro Lambda 7/16 0.42GHz
169
24 00 62 DP 1LSA-C60FS-PTC
146
27 00 00 DP 2x1-RLC-Tr
189
04 58 00 AntPro 5,8GHz-SMA
161
24 00 63 DP 1LSA-C5FS-PTC 145
27 03 03 IsoProData 150V/150V-Tr
182
04 58 02 AntPro 5,8GHz-R-SMA
161
24 00 64 DP 1LSA-C12FS-PTC
145
27 04 04 DP2x1-150V/150V-Tr
184
10 10 00 DP Koax 7/16
165
24 00 65 DP 1LSA-C15FS-PTC
145
27 06 06 DP2x1-6V/6V-Tr 183
10 10 01 DP Koax 7/16 (f/f)
166
24 00 66 DP 1LSA-C24FS-PTC
145
27 12 12 DP2x1-12V/12V-Tr
183
16 02 00 H45
198
24 01 00 LSA 2/10-AN 149
27 15 15 DP2x1-15V/15V-Tr
183
16 05 20 DP FME-AD
170
24 01 02 LSA 2/10-TR 150
27 24 24 DP2x1-24V/24V-Tr
183
151
27 30 02 IsoProData-Tr 103
17 00 10 KA1/2
67
24 01 04 LSA 2/10-ER38-rot 17 00 20 KA1/4
67
24 01 06 TelPro LSA 2/10-2E 8x6
135
27 30 30 DP2x1-30V/30V-Tr
184
17 00 30 KA1/6
67
24 01 08 LSA 2/10 KSR
152
27 36 36 DP2x1-36V/36V-Tr
184
17 00 40 KA1/8
67
24 01 09 LSA 2/10 AD 152
27 48 48 DP2x1-48V/48V-Tr
184
17 01 10 DAK 2x 16
60
24 01 10 LSA 2/10-MW10-25/22 152
27 60 60 DP2x1-60V/60V-Tr
184
19 40 13 DP 1x8RJ45-19“
128
24 01 12 LSA-Anlegewerkzeug
152
27 80 80 DP2x1-80V/80V-Tr
184
19 40 23 DP 2x8RJ45-19“
128
24 01 13 TelPro LSA-2EH230-10kA 135
28 04 04 DP3x1-150V/150V-Tr
186
19 40 33 DP 3x8RJ45-19“
128
24 01 14 TelPro LSA-2EH230F-10kA
135
28 12 12 DP3x1-12V/12V-Tr
185
19 40 43 DP 4x8RJ45-19‘‘
129
24 01 15 TelPro LSA-2EL230-20kA
135
28 15 15 DP3x1-15V/15V-Tr
185
19 40 50 DP 8xRJ45-6V-WG
127
24 01 16 TelPro LSA-2EH350-10kA
135
28 24 24 DP3x1-24V/24V-Tr
185
19 40 53 DP 5x8RJ45-19“
129
24 01 17 TelPro LSA-2EH90-10kA 135
28 30 30 DP3x1-30V/30V-Tr
185
19 40 63 DP 6x8RJ45-19“
129
24 01 18 TelPro LSA 2/10-3E 8x13
136
28 36 36 DP3x1-36V/36V-Tr
186
21 00 20 DataPro-SAT 158
24 01 19 TelPro LSA 2/10-3EH230E-10kA
136
28 48 48 DP3x1-48V/48V-Tr
186
21 00 30 DataPro-Radio/TV
158
24 01 23 TelPro LSA-3EH230F1E-10kA 136
28 60 60 DP3x1-60/60V-Tr 186
24 00 02 EnerPro 230 SDU
57
24 01 24 TelPro LSA-3EL230E-20kA 136
28 70 50 DP 2x1-RLC/50V-Tr 188
24 01 25 TelPro LSA-3EL230F1E-20kA 136
32 50 00 CPS+ 230
53
32 50 01 CPS+ 230Tel/Net
53
24 00 04 DataPro-TAE/NFN-aP
228
Page
131
24 00 05 DP RJ45-CAT6-48V-Tr
124
24 01 26 TelPro LSA-3EH90E-10kA
136
24 00 11 DP RJ45 f/f
125
24 01 27 TelPro LSA-3EH90F1E-10kA
136
32 50 02 CPS+ 230SAT
53
24 00 13 DataPro ISDN-aP
130
24 01 28 TelPro LSA 2/10-2E 8x20 137
32 50 03 CPS+ 230TV
53
24 00 17 DP2-2MB-Tr
190
24 01 29 TelPro LSA 2EY230-20kA 137
35 10 30 UAS 230-Tr
66
24 00 21 DP 1xRJ45-PoE-Alu
126
24 01 31 TelPro LSA-2EY90-20kA 137
36 05 22 NM 220V/5kA
56
24 00 25 DP 10LSA-12V
147
24 01 32 TelPro LSA-2EY350-20kA
137
36 20 30 EP D 230 SM
54
24 00 26 DP 10LSA-PTC-12V 148
24 01 33 LSA 2/10-ES
152
36 20 35 EP D 230 KM
55 24 00 27 DP 10LSA-24V
147
24 01 36 LSA 2/10 KS-120
152
37 44 00 PP PV 800
60
24 00 28 DP 10LSA-PTC-24V 148
24 01 37 LSA DIN ADAPT 152
37 44 01 PP PV 800/FM
60
24 00 31 DP 1LSA-5
138
24 01 40 DP 10LSA-110
147
37 44 02 PP PV 1000
61
24 00 32 DP 1LSA-12 138
24 01 42 DP 10LSA-PTC 110
148
37 44 03 PP PV 1000/FM
61
24 00 33 DP 1LSA-15 138
25 30 16 EPF 230V/16A-Tr 176
44 90 69 TSF 100
206
24 00 34 DP 1LSA-24 138
25 30 17 EPF 230V/25A-Tr 176
44 90 76 TSF 50-Tr
212
24 00 36 DP 1LSA-30 139
25 30 20 EPF 230V/16A-S
177
44 90 80 TSF 100-Tr
212
24 00 37 DP 1LSA-48 139
25 30 22 EPF 60V/16A-S 177
44 90 85 TSF 500-Tr
212
24 00 38 DP 1LSA-60 139
25 30 25 EPF 230V/16A-W
178
44 91 30 TSF 50 SWISS
207
24 00 39 DP 1LSA-110 139
25 30 45 EPF 230/400V/16A-W
179
44 91 75 TSF-H1
206
24 00 40 DP 1LSA-5-PTC
140
25 30 53 EPF 48V/25A-S
177
47 21 04 SGO 70 QA
210
24 00 41 DP 1LSA-12-PTC 140
25 30 80 EPF 230/400V/25A-W
179
47 21 11 SGO 350 QA
210
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Product Register
Numeric
Item no. Product name
Page
Item no. Product name
Page
47 21 17 SGO 70
208
96 00 52 CT-T2/1+0-275
39
96 01 51 CT-T2/1+0-350-VA-FM
Item no. Product name
Page
47
47 22 13 SGO 350 208
96 00 53 CT-T2/1+0-275-FM
39
96 01 52 CT-T2/4+0-350-VA
42
48 78 01 TSF 500
206
96 00 54 CT-T2/4+0-275
28
96 01 53 CT-T2/4+0-350-VA-FM
42
48 78 14 TA 100 C
209
96 00 55 CT-T2/4+0-275-FM
28
96 01 83 CT-T2-150-M
39
48 78 27 TA 500 C
209
96 00 56 CT-T2/3+1-350
31
96 01 84 CT-T2-275-M
33
48 78 30 TC 100 A 211
96 00 57 CT-T2/3+1-350-FM
31
96 01 85 CT-T2-350-M
31
48 78 50 TC 500 A
211
96 00 58 CT-T2/3+0-350
33
96 01 86 CT-T3/Y1-24
50
49 51 06 K1/150
211
96 00 59 CT-T2/3+0-350-FM
33
96 01 87 CT-T3/Y1-24-FM
50
49 51 08 K1/300 211
96 00 62 CT-T2/2+0-350
35
96 01 90 CT-T3/Y1-48
50
53 43 72 TF 100Tr/Th-Pk 213
96 00 63 CT-T2/2+0-350-FM
35
96 01 91 CT-T3/Y1-48-FM
50
53 43 85 TF 500Tr/Th-Pk 213
96 00 64 CT-T2/1+1-350
37
96 01 94 CT-T3/Y1-60
51
53 43 98 TF 500-Tr 213
96 00 65 CT-T2/1+1-350-FM
37
96 01 95 CT-T3/Y1-60-FM
51
54 43 30 DP Koax BNC 50Ohm
160
96 00 66 CT-T2/1+0-350
39
96 01 96 CT-T2-275-VA-M
42
54 43 40 DataPro Koax-8V-BNC-75 Ohm
159
96 00 67 CT-T2/1+0-350-FM
39
96 01 97 CT-T2-350-VA-M
42
54 43 46 DataPro Koax-8V-BNC
159
96 00 68 CT-T2/4+0-350
29
96 01 98 CT-T3/Y1-120
51
55 04 11 TF 2000Tr/Th-Pk
213
96 00 69 CT-T2/4+0-350-FM
29
96 02 02 CT-T3/Y1-230
51
55 04 40 PLPro-40A-iV
218
96 00 70 CT-T2/3+1-440
31
96 01 99 CT-T3/Y1-120-FM
51
55 04 41 PLPro-80A-iV
218
96 00 71 CT-T2/3+1-440-FM
31
96 02 03 CT-T3/Y1-230-FM
51
82 30 11 IF1
211
96 00 72 CT-T2/3+0-440
33
96 02 04 CT-T3/Y3-230
52
82 30 16 IF3
211
96 00 73 CT-T2/3+0-440-FM
33
96 02 05 CT-T3/Y3-230-FM
52
87 00 05 LC 1
200
96 00 76 CT-T2/2+0-440
35
96 02 07 CT-T1/3+1-350-FM
12
87 00 10 H35
197
96 00 77 CT-T2/2+0-440-FM
35
96 02 09 CT-T1/3+0-350-FM
13
87 01 00 A46
199 96 00 78 CT-T2/1+1-440
37
96 02 13 CT-T1/2+0-350-FM
14
87 01 50 H65
196
96 00 79 CT-T2/1+1-440-FM
37
96 02 15 CT-T1/1+1-350-FM
15
96 00 01 CT-T1+2/3+1-350-FM
20
96 00 80 CT-T2/1+0-440
39
96 02 17 CT-T1/1+0-350-FM
16
96 00 03 CT-T1+2/3+0-350-FM
21
96 00 81 CT-T2/1+0-440-FM
39
96 02 20 CT PV-T2/2-0/600
62
96 00 07 CT-T1+2/2+0-350-FM
22
96 00 82 CT-T2/4+0-440
29
96 02 21 CT PV-T2/2-0/600-FM
62
96 00 09 CT-T1+2/1+1-350-FM
23
96 00 83 CT-T2/4+0-440-FM
29
96 02 22 CT PV-T2/2-0/1000
62
96 00 11 CT-T1+2/1+0-350-FM
24
96 00 94 CT-T2/1+0-600
39
96 02 23 CT PV-T2/2-0/1000-FM
62
96 00 24 CT-T2/1+0-75
38
96 00 95 CT-T2/1+0-600-FM
39
96 02 24 CT PV-T2/2+1/600
63
96 00 25 CT-T2/1+0-75-FM
38
96 01 26 CT-T2/3+1-275-VA
43
96 02 25 CT PV-T2/2+1/600-FM
63
96 00 28 CT-T2/3+1-150
30
96 01 27 CT-T2/3+1-275-VA-FM
43
96 02 26 CT PV-T2/2+1/1000
63
63
96 00 29 CT-T2/3+1-150-FM
30
96 01 28 CT-T2/3+0-275-VA
44
96 02 27 CT PV-T2/2+1/1000-FM
96 00 30 CT-T2/3+0-150
32
96 01 29 CT-T2/3+0-275-VA-FM
44
96 02 28 CT PV-T2/2+GDT/600
64
96 00 31 CT-T2/3+0-150-FM
32
96 01 32 CT-T2/2+0-275-VA
45
96 02 29 CT PV-T2/2+GDT/600-FM
64
96 00 34 CT-T2/2+0-150
34
96 01 33 CT-T2/2+0-275-VA-FM
45
96 02 33 CT-T1/0+1-FS-FM
17
96 00 35 CT-T2/2+0-150-FM
34
96 01 34 CT-T2/1+1-275-VA
46
96 02 34 CT-T2/0+1-FS
40
96 00 36 CT-T2/1+1-150
36
96 01 35 CT-T2/1+1-275-VA-FM
46
96 02 35 CT-T2/0+1-FS-FM
40
96 00 37 CT-T2/1+1-150-FM
36
96 01 36 CT-T2/1+0-275-VA
47
96 02 36 CT-T1+2-350-M
20
96 00 38 CT-T2/1+0-150
38
96 01 37 CT-T2/1+0-275-VA-FM
47
96 02 37 CT-T1-350-M
12
96 00 39 CT-T2/1+0-150-FM
38
96 01 38 CT-T2/4+0-275-VA
42
96 02 38 CT-T1-NPE-M
12
96 00 40 CT-T2/4+0-150
28
96 01 39 CT-T2/4+0-275-VA-FM
42
96 02 39 CT-T2-NPE-M
31
96 00 41 CT-T2/4+0-150-FM
28
96 01 40 CT-T2/3+1-350-VA
43
96 02 40 CT-T3/Y1-24-M
51
96 00 42 CT-T2/3+1-275
30
96 01 41 CT-T2/3+1-350-VA-FM
43
96 02 44 CT-T3/Y1-230-M
51
96 00 43 CT-T2/3+1-275-FM
30
96 01 42 CT-T2/3+0-350-VA
44
96 02 45 CT-T3/Y3-230-M
52
96 00 44 CT-T2/3+0-275
32
96 01 43 CT-T2/3+0-350-VA-FM
44
96 02 46 CT PV-T2-600-M
62
96 00 45 CT-T2/3+0-275-FM
32
96 01 46 CT-T2/2+0-350-VA
45
96 02 47 CT PV-T2-1000-M
62
96 00 48 CT-T2/2+0-275
34
96 01 47 CT-T2/2+0-350-VA-FM
45
96 02 48 CT PV-T2-GDT-M
64
96 00 49 CT-T2/2+0-275-FM
34
96 01 48 CT-T2/1+1-350-VA
46
96 00 50 CT-T2/1+1-275
36
96 01 49 CT-T2/1+1-350-VA-FM
46
96 00 51 CT-T2/1+1-275-FM
36
96 01 50 CT-T2/1+0-350-VA
47
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
229
Product Register
Numeric
Item no. Product name
Item no. Product name
Page
96 03 00 CT PV-T2/2+GDT/1000
64
97 10 04 MP RK GDT+5V-Ad-Ad
96 03 01 CT PV-T2/2+GDT/1000-FM
64
97 10 05 MP RK GDT+12V-Ad-Ad
106
97 00 00 MP Base 2x2-R
85 97 10 06 MP RK GDT+24V-Ad-Ad
106
97 00 01 MP Base 2x2-R GDT
85
97 10 07 MP RK GDT+36V-Ad-Ad
106
97 00 03 MP Base 2x2
80
97 10 08 MP RK GDT+48V-Ad-Ad
107
97 00 04 MP Base 2x2 GDT
80
97 10 09 MP RK GDT+60V-Ad-Ad
107
97 00 07 MP 2x2 GDT ST
80
97 10 10 MP RK GDT+180V-Ad-Ad
107
97 00 10 MP 1x2 GDT ST
81
97 10 11 MP RK GDT+5V-Ad-Pg
108
97 00 11 MP 2x2 GDT+5V-Ad-Ad ST
84
97 10 12 MP RK GDT+12V-Ad-Pg
108
97 00 12 MP 2x2 GDT+12V-Ad-Ad ST
84
97 10 13 MP RK GDT+24V-Ad-Pg
108
97 00 13 MP 2x2 GDT+24V-Ad-Ad ST
84
97 10 14 MP RK GDT+36V-Ad-Pg
108
97 00 14 MP 2x2 GDT+36V-Ad-Ad ST
84
97 10 15 MP RK GDT+48V-Ad-Pg
109
97 00 15 MP 2x2 GDT+48V-Ad-Ad ST
85
97 10 16 MP RK GDT+60V-Ad-Pg
109
97 00 16 MP 2x2 GDT+60V-Ad-Ad ST
85
97 10 17 MP RK GDT+180V-Ad-Pg
109
97 00 17 MP 2x2 GDT+180V-Ad-Ad ST
85
97 10 18 MP RK GDT+5V-Ad-Ad-Pg
110
97 00 18 MP 1x2 GDT+5V-Ad-Ad ST
86
97 10 19 MP RK GDT+12V-Ad-Ad-Pg
110
97 00 19 MP 1x2 GDT+12V-Ad-Ad ST
86
97 10 20 MP RK GDT+12V-Ad-Ad-Pg
110
97 00 20 MP 1x2 GDT+24V-Ad-Ad ST
86
97 10 21 MP RK GDT+36V-Ad-Ad-Pg
110
97 00 21 MP 1x2 GDT+36V-Ad-Ad ST
86
97 10 22 MP RK GDT+48V-Ad-Ad-Pg
111
97 00 22 MP 1x2 GDT+48V-Ad-Ad ST
87
97 10 23 MP RK GDT+60V-Ad-Ad-Pg
111
97 00 23 MP 1x2 GDT+60V-Ad-Ad ST
87
97 10 24 MP RK GDT+180V-Ad-Ad-Pg
111
97 00 24 MP 1x2 GDT+180V-Ad-Ad ST
87
97 10 25 MP RK 5V-Ad-Ad
114
97 00 25 MP 2x2 GDT+5V-Ad-Pg ST
88
97 10 26 MP RK 12V-Ad-Ad
114
97 00 26 MP 2x2 GDT+12V-Ad-Pg ST
88
97 10 27 MP RK 24V-Ad-Ad
114
97 00 27 MP 2x2 GDT+24V-Ad-Pg ST
88
97 10 28 MP RK 36V-Ad-Ad
114
97 00 28 MP 2x2 GDT+36V-Ad-Pg ST
88
97 10 29 MP RK 48V-Ad-Ad
115
97 00 29 MP 2x2 GDT+48V-Ad-Pg ST
89
97 10 30 MP RK 60V-Ad-Ad
115
97 00 30 MP 2x2 GDT+60V-Ad-Pg ST
89
97 10 31 MP RK 180V-Ad-Ad
115
97 00 31 MP 2x2 GDT+180V-Ad-Pg ST
89
97 10 32 MP RK 5V-Ad-Pg
116
97 00 32 MP 1x2 GDT+5V-Ad-Pg ST
90
97 10 33 MP RK 12V-Ad-Pg
117
97 00 33 MP 1x2 GDT+12V-Ad-Pg ST
90
97 10 34 MP RK 24V-Ad-Pg
118
97 00 34 MP 1x2 GDT+24V-Ad-Pg ST
90
97 10 35 MP RK 36V-Ad-Pg
118
97 00 35 MP 1x2 GDT+36V-Ad-Pg ST
90
97 10 36 MP RK 48V-Ad-Pg
117
97 00 36 MP 1x2 GDT+48V-Ad-Pg ST
91
97 10 37 MP RK 60V-Ad-Pg
117
97 00 37 MP 1x2 GDT+60V-Ad-Pg ST
91
97 10 38 MP RK 180V-Ad-Pg
117
97 00 38 MP 1x2 GDT+180V-Ad-Pg ST
91
97 10 39 MP RK 5V-Ad-Ad-Pg
118
97 00 39 MP 2x2 GDT+5V-Ad-Ad-Pg ST
92
97 10 40 MP RK 12V-Ad-Ad-Pg
118
97 00 40 MP 2x2 GDT+12V-Ad-Ad-Pg ST
92
97 10 41 MP RK 24V-Ad-Ad-Pg
118
97 00 41 MP 2x2 GDT+24V-Ad-Ad-Pg ST
92
97 10 42 MP RK 36V-Ad-Ad-Pg
118
97 00 42 MP 2x2 GDT+36V-Ad-Ad-Pg ST
92
97 10 43 MP RK 48V-Ad-Ad-Pg
119
97 00 43 MP 2x2 GDT+48V-Ad-Ad-Pg ST
93
97 10 44 MP RK 60V-Ad-Ad-Pg
119
97 00 44 MP 2x2 GDT+60V-Ad-Ad-Pg ST
93
97 10 45 MP RK 180V-Ad-Ad-Pg
119
97 00 45 MP 2x2 GDT+180V-Ad-Ad-Pg ST
93
97 10 50 MP 2x2 5V-HF ST
98
106
97 00 46 MP 1x2 GDT+5V-Ad-Ad-Pg ST
94
97 10 51 MP 2x2 24V-HF ST
98
97 00 47 MP 1x2 GDT+12V-Ad-Ad-Pg ST
94
97 10 52 MP 1x2 5V-HF ST
99
97 00 48 MP 1x2 GDT+24V-Ad-Ad-Pg ST
94
97 10 53 MP 1x2 24V-HF ST
99
97 00 49 MP 1x2 GDT+36V-Ad-Ad-Pg ST
94
97 00 50 MP 1x2 GDT+48V-Ad-Ad-Pg ST
95
97 00 51 MP 1x2 GDT+60V-Ad-Ad-Pg ST
95
97 00 52 MP 1x2 GDT+180V-Ad-Ad-Pg ST
97 10 03 MP RK GDT
230
Page
95
102
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Product Register
Alphabetical
Product nameItem no.
Page
Product nameItem no.
Page
Product nameItem no.
Page
96 00 53
39
CT-T2/3+1-275
96 00 42
30
A46
87 01 00
199
CT-T2/1+0-275-FM
AntPro 5,8GHz-R-SMA
04 58 02
161
CT-T2/1+0-275-VA
96 01 36
47
CT-T2/3+1-275-FM
96 00 43
30
AntPro 5,8GHz-SMA
04 58 00
161
CT-T2/1+0-275-VA-FM
96 01 37
47
CT-T2/3+1-275-VA
96 01 26
43
AntPro Koax-GSM-N/230
04 00 01
162
CT-T2/1+0-350
96 00 66
39
CT-T2/3+1-275-VA-FM
96 01 27
43
AntPro Koax-GSM-N-230(f/f) 04 00 04
162
CT-T2/1+0-350-FM
96 00 67
39
CT-T2/3+1-350
96 00 56
31
AntPro Lambda 7/16 0.42GHz
04 04 25
169
CT-T2/1+0-350-VA
96 01 50
47
CT-T2/3+1-350-FM
96 00 57
31
AntPro Lambda/4 7/16 TRI
04 00 30
167
CT-T2/1+0-350-VA-FM
96 01 51
47
CT-T2/3+1-350-VA
96 01 40
43
AntPro Lambda/4 7/16 TRI (f/f)
04 00 31
168
CT-T2/1+0-440
96 00 80
39
CT-T2/3+1-350-VA-FM
96 01 41
43
AntPro Lambda/4 N 0.51GHz
04 00 20
163
CT-T2/1+0-440-FM
96 00 81
39
CT-T2/3+1-440
96 00 70
31
AntPro Lambda/4 N 0.51GHz (f/f) 04 00 21
164
CT-T2/1+0-600
96 00 94
39
CT-T2/3+1-440-FM
96 00 71
31
AntPro Lambda/4 N 0.8GHz
04 00 22
163
CT-T2/1+0-600-FM
96 00 95
39
CT-T2/4+0-150
96 00 40
28
AntPro Lambda/4 N 2.0GHz
04 00 23
163
CT-T2/1+0-75
96 00 24
38
CT-T2/4+0-150-FM
96 00 41
28
AntPro Lambda/4 N 2.0GHz (f/f)
04 00 24
164
CT-T2/1+0-75-FM
96 00 25
38
CT-T2/4+0-275
96 00 54
28
CPS+ 230
32 50 00
53
CT-T2/1+1-150
96 00 36
36
CT-T2/4+0-275-FM
96 00 55
28
CPS+ 230SAT
32 50 02
53
CT-T2/1+1-150-FM
96 00 37
36
CT-T2/4+0-275-VA
96 01 38
42
CPS+ 230Tel/Net
32 50 01
53
CT-T2/1+1-275
96 00 50
36
CT-T2/4+0-275-VA-FM
96 01 39
42
96 00 51
36
CT-T2/4+0-350
96 00 68
29
CPS+ 230TV
32 50 03
53
CT-T2/1+1-275-FM
CT PV-T2/2+1/1000
96 02 26
63
CT-T2/1+1-275-VA
96 01 34
46
CT-T2/4+0-350-FM
96 00 69
29
CT PV-T2/2+1/1000-FM
96 02 27
63
CT-T2/1+1-275-VA-FM
96 01 35
46
CT-T2/4+0-350-VA
96 01 52
42
CT PV-T2/2+1/600
96 02 24
63
CT-T2/1+1-350
96 00 64
37
CT-T2/4+0-350-VA-FM
96 01 53
42
CT PV-T2/2+1/600-FM
96 02 25
63
CT-T2/1+1-350-FM
96 00 65
37
CT-T2/4+0-440
96 00 82
29
CT PV-T2/2+GDT/1000
96 03 00
64
CT-T2/1+1-350-VA
96 01 48
46
CT-T2/4+0-440-FM
96 00 83
29
CT PV-T2/2+GDT/1000-FM
96 03 01
64
CT-T2/1+1-350-VA-FM
96 01 49
46
CT-T2-150-M
96 01 83
39
CT PV-T2/2+GDT/600
96 02 28
64
CT-T2/1+1-440
96 00 78
37
CT-T2-275-M
96 01 84
33
CT PV-T2/2+GDT/600-FM
96 02 29
64
CT-T2/1+1-440-FM
96 00 79
37
CT-T2-275-VA-M
96 01 96
42
CT PV-T2/2-0/1000
96 02 22
62
CT-T2/2+0-150
96 00 34
34
CT-T2-350-M
96 01 85
31
CT PV-T2/2-0/1000-FM
96 02 23
62
CT-T2/2+0-150-FM
96 00 35
34
CT-T2-350-VA-M
96 01 97
42
CT PV-T2/2-0/600
96 02 20
62
CT-T2/2+0-275
96 00 48
34
CT-T2-NPE-M
96 02 39
31
CT PV-T2/2-0/600-FM
96 02 21
62
CT-T2/2+0-275-FM
96 00 49
34
CT-T3/Y1-120
96 01 98
51
CT PV-T2-1000-M
96 02 47
62
CT-T2/2+0-275-VA
96 01 32
45
CT-T3/Y1-120-FM
96 01 99
51
CT PV-T2-600-M
96 02 46
62
CT-T2/2+0-275-VA-FM
96 01 33
45
CT-T3/Y1-230
96 02 02
51
CT PV-T2-GDT-M
96 02 48
64
CT-T2/2+0-350
96 00 62
35
CT-T3/Y1-230-FM
96 02 03
51
96 02 44
51
CT-T1/0+1-FS-FM
96 02 33
17
CT-T2/2+0-350-FM
96 00 63
35
CT-T3/Y1-230-M
CT-T1/1+0-350-FM
96 02 17
16
CT-T2/2+0-350-VA
96 01 46
45
CT-T3/Y1-24
96 01 86
50
CT-T1/1+1-350-FM
96 02 15
15
CT-T2/2+0-350-VA-FM
96 01 47
45
CT-T3/Y1-24-FM
96 01 87
50
CT-T1/2+0-350-FM
96 02 13
14
CT-T2/2+0-440
96 00 76
35
CT-T3/Y1-24-M
96 02 40
51
CT-T1/3+0-350-FM
96 02 09
13
CT-T2/2+0-440-FM
96 00 77
35
CT-T3/Y1-48
96 01 90
50
CT-T1/3+1-350-FM
96 02 07
12
CT-T2/3+0-150
96 00 30
32
CT-T3/Y1-48-FM
96 01 91
50
CT-T1+2/1+0-350-FM
96 00 11
24
CT-T2/3+0-150-FM
96 00 31
32
CT-T3/Y1-60
96 01 94
51
CT-T1+2/1+1-350-FM
96 00 09
23
CT-T2/3+0-275
96 00 44
32
CT-T3/Y1-60-FM
96 01 95
51
CT-T1+2/2+0-350-FM
96 00 07
22
CT-T2/3+0-275-FM
96 00 45
32
CT-T3/Y3-230
96 02 04
52
CT-T1+2/3+0-350-FM
96 00 03 21
CT-T2/3+0-275-VA
96 01 28
44
CT-T3/Y3-230-FM
96 02 05
52
CT-T1+2/3+1-350-FM
96 00 01
20
CT-T2/3+0-275-VA-FM
96 01 29
44
CT-T3/Y3-230-M
96 02 45
52
CT-T1+2-350-M
96 02 36
20
CT-T2/3+0-350
96 00 58
33
DAK 2x 16
17 01 10
60
CT-T1-350-M
96 02 37
12
CT-T2/3+0-350-FM
96 00 59
33
DataPro ISDN-aP
24 00 13
130
CT-T1-NPE-M
96 02 38
12
CT-T2/3+0-350-VA
96 01 42
44
DataPro Koax-8V-BNC
54 43 46
159
CT-T2/0+1-FS
96 02 34
40
CT-T2/3+0-350-VA-FM
96 01 43
44
DataPro Koax-8V-BNC-75 Ohm
54 43 40
159
CT-T2/0+1-FS-FM
96 02 35
40
CT-T2/3+0-440
96 00 72
33
DataPro-Radio/TV
21 00 30
158
CT-T2/1+0-150
96 00 38
38
CT-T2/3+0-440-FM
96 00 73
33
DataPro-SAT 21 00 20
158
CT-T2/1+0-150-FM
96 00 39
39
CT-T2/3+1-150
96 00 28
30
DataPro-TAE/NFN-aP
24 00 04
131
CT-T2/1+0-275
96 00 52
39
CT-T2/3+1-150-FM
96 00 29
30
DP 10LSA-110
24 01 40
147
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
231
Product Register
Alphabetical
Product nameItem no.
232
Page
Product nameItem no.
Page
Product nameItem no.
Page
27 04 04
184
LSA 2/10-ER38-rot 24 01 04
151
DP 10LSA-12V
24 00 25
147
DP2x1-150V/150V-Tr
DP 10LSA-24V
24 00 27
147
DP2x1-15V/15V-Tr
27 15 15
183
LSA 2/10-ES
24 01 33
152
DP 10LSA-PTC 110
24 01 42
148
DP2x1-24V/24V-Tr
27 24 24
183
LSA 2/10-MW10-25/22 24 01 10
152
DP 10LSA-PTC-12V 24 00 26
148
DP2x1-30V/30V-Tr
27 30 30
184
LSA 2/10-TR 24 01 02
150
DP 10LSA-PTC-24V 24 00 28
148
DP2x1-36V/36V-Tr
27 36 36
184
LSA DIN ADAPT 24 01 37
152
DP 1LSA-110 24 00 39
139
DP2x1-48V/48V-Tr
27 48 48
184
LSA-Anlegewerkzeug
24 01 12
152
DP 1LSA-110-PTC
24 00 46
141
DP2x1-60V/60V-Tr
27 60 60
184
MP 1x2 24V-HF ST
97 10 53
99
DP 1LSA-12 24 00 32
138
DP2x1-6V/6V-Tr 27 06 06
183
MP 1x2 5V-HF ST
97 10 52
99
DP 1LSA-12-PTC 24 00 41
140
DP2x1-80V/80V-Tr
27 80 80
184
MP 1x2 GDT ST
97 00 10
81
DP 1LSA-15 24 00 33
138
DP3x1-12V/12V-Tr
28 12 12 185
MP 1x2 GDT+12V-Ad-Ad ST
97 00 19
86
DP 1LSA-15-PTC 24 00 42
140
DP3x1-150V/150V-Tr
28 04 04
186
MP 1x2 GDT+12V-Ad-Ad-Pg ST
97 00 47
94
DP 1LSA-180FS 24 00 47
142
DP3x1-15V/15V-Tr
28 15 15
185
MP 1x2 GDT+12V-Ad-Pg ST
97 00 33
90
DP 1LSA-24 24 00 34
138
DP3x1-24V/24V-Tr
28 24 24
185
MP 1x2 GDT+180V-Ad-Ad ST
97 00 24
87
DP 1LSA-24-PTC 24 00 43
140
DP3x1-30V/30V-Tr
28 30 30
185
MP 1x2 GDT+180V-Ad-Ad-Pg ST 97 00 52
95
DP 1LSA-30 24 00 36
139
DP3x1-36V/36V-Tr
28 36 36
186
MP 1x2 GDT+180V-Ad-Pg ST
97 00 38
91
DP 1LSA-48 24 00 37
139
DP3x1-48V/48V-Tr
28 48 48
186
MP 1x2 GDT+24V-Ad-Ad ST
97 00 20
86
28 60 60
186
MP 1x2 GDT+24V-Ad-Ad-Pg ST
97 00 48
94
DP 1LSA-48-PTC 24 00 44
141
DP3x1-60/60V-Tr DP 1LSA-5
24 00 31
138
EnerPro 230 SDU
24 00 02
57
MP 1x2 GDT+24V-Ad-Pg ST
97 00 34
90
DP 1LSA-5-PTC
24 00 40
140
EP D 230 KM
36 20 35
55
MP 1x2 GDT+36V-Ad-Ad ST
97 00 21
86
DP 1LSA-60 24 00 38
139
EP D 230 SM
36 20 30
54
MP 1x2 GDT+36V-Ad-Ad-Pg ST
97 00 49
94
DP 1LSA-60-PTC 24 00 45
141
EPF 230/400V/100A-E
25 31 40
180
MP 1x2 GDT+36V-Ad-Pg ST
97 00 35
90
DP 1LSA-C12FS-PTC
24 00 64
145
EPF 230/400V/16A-W
25 30 45
179
MP 1x2 GDT+48V-Ad-Ad ST
97 00 22
87
DP 1LSA-C15FS-PTC
24 00 65
145
EPF 230/400V/200A-E
25 31 60
180
MP 1x2 GDT+48V-Ad-Ad-Pg ST
97 00 50
95
DP 1LSA-C24FS-PTC
24 00 66
145
EPF 230/400V/25A-W
25 30 80
179
MP 1x2 GDT+48V-Ad-Pg ST
97 00 36
91
DP 1LSA-C48FS-PTC
24 00 61
146
EPF 230/400V/35A-W
25 31 00
179
MP 1x2 GDT+5V-Ad-Ad ST
97 00 18
86
DP 1LSA-C5FS-PTC 24 00 63
145
EPF 230/400V/63A-E
25 31 30
180
MP 1x2 GDT+5V-Ad-Ad-Pg ST
97 00 46
94
DP 1LSA-C60FS-PTC
24 00 62
146
EPF 230V/16A-S
25 30 20
177
MP 1x2 GDT+5V-Ad-Pg ST
97 00 32
90
DP 1LSA-T110FS-PTC 24 00 48
143
EPF 230V/16A-Tr 25 30 16
176
MP 1x2 GDT+60V-Ad-Ad ST
97 00 23
87
DP 1LSA-TK180FS
24 00 49
144
EPF 230V/16A-W
25 30 25
178
MP 1x2 GDT+60V-Ad-Ad-Pg ST
97 00 51
95
DP 1x8RJ45-19“
19 40 13
128
EPF 230V/25A-Tr 25 30 17
176
MP 1x2 GDT+60V-Ad-Pg ST
97 00 37
91
DP 1xRJ45-PoE-Alu
24 00 21
126
EPF 230V/35A-S
25 30 85
177
MP 2x2 24V-HF ST
97 10 51
98
DP 2x1-12V/12V-0,3Ω -Tr
26 12 12
187
EPF 48V/25A-S
25 30 53
177
MP 2x2 5V-HF ST
97 10 50
98
97 00 07
80
DP 2x1-24V/24V-0,3Ω -Tr
26 24 24
187
EPF 60V/16A-S 25 30 22
177
MP 2x2 GDT ST
DP 2x1-30V/30V-0,3Ω-Tr
26 30 30
187
H35
87 00 10
197
MP 2x2 GDT+12V-Ad-Ad ST
97 00 12
84
DP 2x1-36V/36V-0,3Ω -Tr
26 36 36
187
H45
16 02 00
198
MP 2x2 GDT+12V-Ad-Ad-Pg ST
97 00 40
92
DP 2x1-RLC/50V-Tr 28 70 50
188
H65
87 01 50
196
MP 2x2 GDT+12V-Ad-Pg ST
97 00 26
88
DP 2x1-RLC-Tr
27 00 00
189
IF1
82 30 11
211
MP 2x2 GDT+180V-Ad-Ad ST
97 00 17
85
DP 2x8RJ45-19“
19 40 23
128
IF3
82 30 16
211
MP 2x2 GDT+180V-Ad-Ad-Pg ST 97 00 45
93
DP 3x8RJ45-19“
19 40 33
128
IsoProData 150V/150V-Tr
27 03 03
182
MP 2x2 GDT+180V-Ad-Pg ST
97 00 31
89
DP 4x8RJ45-19‘‘
19 40 43
129
IsoProData-Tr 27 30 02
103
MP 2x2 GDT+24V-Ad-Ad ST
97 00 13
84
DP 5x8RJ45-19“
19 40 53
129
K1/150
49 51 06
211
MP 2x2 GDT+24V-Ad-Ad-Pg ST
97 00 41
92
DP 6x8RJ45-19“
19 40 63
129
K1/300 49 51 08
211
MP 2x2 GDT+24V-Ad-Pg ST
97 00 27
88
DP 8xRJ45-6V-WG
19 40 50
127
KA1/2
17 00 10
67
MP 2x2 GDT+36V-Ad-Ad ST
97 00 14
84
DP Koax BNC 50Ohm
54 43 30
160
KA1/4
17 00 20
67
MP 2x2 GDT+36V-Ad-Ad-Pg ST
97 00 42
92
DP FME-AD
16 05 20
170
KA1/6
17 00 30
67
MP 2x2 GDT+36V-Ad-Pg ST
97 00 28
88
DP Koax 7/16
10 10 00
165
KA1/8
17 00 40
67
MP 2x2 GDT+48V-Ad-Ad ST
97 00 15
85
DP Koax 7/16 (f/f)
10 10 01
166
LC 1
87 00 05
200
MP 2x2 GDT+48V-Ad-Ad-Pg ST
97 00 43
93
DP RJ45 f/f
24 00 11
125
LSA 2/10 AD 24 01 09
152
MP 2x2 GDT+48V-Ad-Pg ST
97 00 29
89
DP RJ45-CAT6-48V-Tr
24 00 05
124
LSA 2/10 KS-120
24 01 36
152
MP 2x2 GDT+5V-Ad-Ad ST
97 00 11
84
DP2-2MB-Tr
24 00 17
190
LSA 2/10 KSR
24 01 08
152
MP 2x2 GDT+5V-Ad-Ad-Pg ST
97 00 39
92
DP2x1-12V/12V-Tr
27 12 12
183
LSA 2/10-AN 24 01 00
149
MP 2x2 GDT+5V-Ad-Pg ST
97 00 25
88
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
Product Register
Alphabetical
Product nameItem no.
Page
Product nameItem no.
Page
MP 2x2 GDT+60V-Ad-Ad ST
97 00 16
85
PLPro-40A-iV
MP 2x2 GDT+60V-Ad-Ad-Pg ST
97 00 44
93
PLPro-80A-iV
55 04 41
218
MP 2x2 GDT+60V-Ad-Pg ST
97 00 30
89
PP PV 1000
37 44 02
61
MP Base 2x2
97 00 03
81
PP PV 1000/FM
37 44 03
61
MP Base 2x2 GDT
97 00 04
81
PP PV 800
37 44 00
60
MP Base 2x2-R
97 00 00
85
PP PV 800/FM
37 44 01
60
MP Base 2x2-R GDT
97 00 01
85
SGO 350 47 22 13
208
MP RK 12V-Ad-Ad
97 10 26
114
SGO 350 QA
47 21 11
210
MP RK 12V-Ad-Ad-Pg
97 10 40
118
SGO 70
47 21 17
208
MP RK 12V-Ad-Pg
97 10 33
116
SGO 70 QA
47 21 04
210
MP RK 180V-Ad-Ad
97 10 31
115
TA 100 C
48 78 14
209
MP RK 180V-Ad-Ad-Pg
97 10 45
119
TA 500 C
48 78 27
209
MP RK 180V-Ad-Pg
97 10 38
117
TC 100 A 48 78 30
211
MP RK 24V-Ad-Ad
97 10 27
114
TC 500 A
48 78 50
211
MP RK 24V-Ad-Ad-Pg
97 10 41
118
TelPro LSA 2/10-2E 8x20 24 01 28
137
MP RK 24V-Ad-Pg
97 10 34
116
TelPro LSA 2/10-2E 8x6
24 01 06
135
24 01 18
136
55 04 40
218
MP RK 36V-Ad-Ad
97 10 28
114
TelPro LSA 2/10-3E 8x13 MP RK 36V-Ad-Ad-Pg
97 10 42
118
TelPro LSA 2/10-3EH230E-10kA 24 01 19
136
MP RK 36V-Ad-Pg
97 10 35
116
TelPro LSA 2EY230-20kA 24 01 29
137
MP RK 48V-Ad-Ad
97 10 29
115
TelPro LSA-2EH230-10kA 24 01 13
135
MP RK 48V-Ad-Ad-Pg
97 10 43
119
TelPro LSA-2EH230F-10kA
24 01 14
135
MP RK 48V-Ad-Pg
97 10 36
117
TelPro LSA-2EH350-10kA
24 01 16
135
MP RK 5V-Ad-Ad
97 10 25
114
TelPro LSA-2EH90-10kA 24 01 17
135
MP RK 5V-Ad-Ad-Pg
97 10 39
118
TelPro LSA-2EL230-20kA
24 01 15
135
MP RK 5V-Ad-Pg
97 10 32
116
TelPro LSA-2EY350-20kA
24 01 32
137
MP RK 60V-Ad-Ad
97 10 30
115
TelPro LSA-2EY90-20kA 24 01 31
137
MP RK 60V-Ad-Ad-Pg
97 10 44
119
TelPro LSA-3EH230F1E-10kA 24 01 23
136
MP RK 60V-Ad-Pg
97 10 37
117
TelPro LSA-3EH90E-10kA
24 01 26
136
MP RK GDT
97 10 03
102
TelPro LSA-3EH90F1E-10kA
24 01 27
136
MP RK GDT+12V-Ad-Ad
97 10 05
106
TelPro LSA-3EL230E-20kA 24 01 24
136
MP RK GDT+12V-Ad-Ad-Pg
97 10 19
110
TelPro LSA-3EL230F1E-20kA 24 01 25
136
MP RK GDT+12V-Ad-Ad-Pg
97 10 20
110
TF 100Tr/Th-Pk 53 43 72
213
MP RK GDT+12V-Ad-Pg
97 10 12
108
TF 2000Tr/Th-Pk
55 04 11
213
MP RK GDT+180V-Ad-Ad
97 10 10
107
TF 500-Tr 53 43 98
213
MP RK GDT+180V-Ad-Ad-Pg
97 10 24
111
TF 500Tr/Th-Pk 53 43 85
213
MP RK GDT+180V-Ad-Pg
97 10 17
109
TSF 100
44 90 69
206
MP RK GDT+24V-Ad-Ad
97 10 06
106
TSF 100-Tr
44 90 80
212
MP RK GDT+24V-Ad-Pg
97 10 13
108
TSF 50 SWISS
44 91 30
207
MP RK GDT+36V-Ad-Ad
97 10 07
106
TSF 500
48 78 01
206
MP RK GDT+36V-Ad-Ad-Pg
97 10 21
110
TSF 500-Tr
44 90 85
212
MP RK GDT+36V-Ad-Pg
97 10 14
108
TSF 50-Tr
44 90 76
212
MP RK GDT+48V-Ad-Ad
97 10 08
107
TSF-H1
44 91 75
206
MP RK GDT+48V-Ad-Ad-Pg
97 10 22
111
UAS 230-Tr
35 10 30
66
MP RK GDT+48V-Ad-Pg
97 10 15
109
MP RK GDT+5V-Ad-Ad
97 10 04
106
MP RK GDT+5V-Ad-Ad-Pg
97 10 18
110
MP RK GDT+5V-Ad-Pg
97 10 11
108
MP RK GDT+60V-Ad-Ad
97 10 09
107
MP RK GDT+60V-Ad-Ad-Pg
97 10 23
111
MP RK GDT+60V-Ad-Pg
97 10 16
109
NM 220V/5kA
36 05 22
56
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
233
general terms and conditions of sale
General Terms and Conditions of Sale of the Company of Leutron GmbH
Effective: February 2008
I. Scope
1. Our General Terms and Conditions of Sale apply to all - including future legal relationships between the parties to the Contract. Agreements to the
contrary are only valid if confirmed by us in writing.
5. We only accept drafts or cheques in payment and not in lieu of payment after separate agreement. Our account is not settled until the date on which the
funds are available to us without having to make allowance for charge-back
claims. Collection charges, discount charges or bill charges including interest
shall in all cases be borne by the Purchaser and are payable immediately.
2. We are not bound by any contrary or contradictory General Terms and
Conditions of the other party to the Contract - hereinafter referred to as the
Purchaser - even if we do not expressly object to them.
6. The Purchaser may only offset against a claim which is undisputed or legally
binding. He may only exercise a right of retention to the extent that his counterclaim is based on the same contractual relationship.
3. Our Terms and Conditions only reply in respect of Companies as defined in
§ 310 Section 1 BGB [Civil Code].
7. One-off costs such as for example tooling and development costs are invoiced at 50% directly upon receipt of order. The remaining 50% of the said
costs are due upon delivery of the first series production components.
4. Should any provision contained in our General Terms and Conditions of Sale
prove to be or become invalid the validity of all remaining provisions shall not
be thereby affected.
II. Tender and Tender Documentation
1. Our tender is subject to confirmation in the absence of anything to the
contrary ensuing from the offer.
2. We can accept orders within a period of 6 weeks. The said period commences upon receipt of order.
3. Our written Confirmation of Order is definitive in respect of supply of goods
or services. Assurances regarding characteristics, supplements or ancillary
agreements must be in writing to take legal effect.
4. Our sales staff are not authorised to enter into verbal ancillary agreements
or to give assurances extending beyond the content of the written Contract.
IV. Product Information and Design Modifications
1. The Purchaser undertakes to provide us with a comprehensive description
of every aspect and detail of the conditions under which the goods supplied
shall be used.
2. We reserve the right to introduce design modifications in the interests of
technical progress provided the latter do not involve any changes in the function of the goods.
V. Delivery Period
1. Information regarding delivery periods is unbinding unless the delivery date
has been exceptionally agreed as „binding“.
5. We retain title and intellectual property rights to all diagrams, drawings,
calculations and other documentation. Prior to transmission thereof to third
parties the Purchaser requires our express written permission.
2. The delivery period shall commence with the date of confirmation of order
but not however prior to provision of items required to be furnished by the
Purchaser i.e. supporting documentation, official approvals and releases including receipt of any agreed payment, opening of any letter of credit required or
evidence of arrangement of any collateral agreed.
6. In the case of series production or special custom designs we reserve the
right to apply an over or under-delivery rate of 10%. The resultant over or
under-delivery shall be invoiced accordingly.
3. The delivery period shall be deemed met if the goods have left the Leinfelden-Echterdingen warehouse facility within the delivery period.
7. We are entitled to make part deliveries if this may be considered reasonable
for the customer.
III. Prices and Terms of Payment
1. If nothing to the contrary emerges from the Confirmation of Order our prices
are „ex stock“ or „ex works“ and exclusive of shipping and handling charges,
customs or excise duty, packaging and are liable to the prevailing rate of statutory VAT.
2. Minimum value of goods per order is EUR 250.00 net.
234
date of invoice. Part invoices shall be presented for part deliveries. Payment
terms shall run separately for each part invoice.
Statutory provisions apply in the event of payment arrears.
4. Should any unforeseen impediments outside our control arise which despite
the requisite care required given the particular circumstances of the case we
are not in a position to avert - irrespective of whether the said impediments
occur with us or at subcontractors - including force majeure (e.g. war or natural catastrophe) or delays in the supply of essential raw materials or other
circumstances for which we are not responsible - we are entitled to withdraw
from the Supply Contract either wholly or in part or alternatively to extend the
delivery period by the duration of the impediment. We shall be entitled to the
same rights in the event of strikes and lockouts at our premises or those of our
upstream suppliers. We shall immediately notify our customers of any such
circumstances.
3. We reserve the right to adjust our prices accordingly if subsequent to conclusion of the Contract cost reductions or cost increases, in particular as a
consequence of collective wage agreements, changes in the cost of materials
or currency fluctuations take place. Evidence of the above shall be made
available to the Purchaser on request.
5. In the event of delay in delivery the Purchaser may, following the expiry of
an appropriate period of grace to no effect, withdraw from the Contract; in
the event of the practical impossibility of supply of goods on our part he is
also entitled to do so without notice. A period of 14 days shall be deemed
appropriate and in the case of special custom-made products this shall be a
minimum of 1 month.
4. If nothing to the contrary emerges from the Confirmation of Order the net
purchase price shall be due for payment (without deduction) within 8 days from
Delayed delivery shall equate to impossibility if delivery does not follow after 1
month or 6 weeks in the case of special custom-made products.
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
general terms and conditions of sale
Claims for damages (including any consequential loss) shall be excluded irrespective of Section 6; the same shall apply in the case of reimbursement of
expenses.
6. The liability disclaimer provision under Section 5 shall not apply if any exclusion or restriction of liability is agreed in respect of injury to life, physical injury
or damage to health which is due to intentional or negligent dereliction of duty
on the part of the user or intentional or negligent dereliction of duty on the part
of any legal representative or vicarious agent of the user; nor shall it apply
if any exclusion or limitation of liability is agreed for other forms of damage
caused by any intentional or grossly negligent dereliction of duty on the part of
any legal representative or vicarious agent of the user.
If we culpably infringe any essential contractual obligation or any cardinal obligation liability shall not be excluded but shall be limited to typical foreseeable
contractual damage.
In the event of reimbursement of expenses the above shall apply accordingly.
7. If any commercial fixed date transaction has been agreed the liability limitations arising from Sections 5 and Section 6 shall not apply; the same applies if
the Purchaser is in a position to claim that as a consequence of the delay for
which we are responsible his interest in performance of the Contract ceases
to apply.
8. In the case of call orders calls shall be notified to us in a timely manner
to enable orderly manufacture and supply and at least 6 weeks prior to the
desired delivery date. Call orders must be called forward within 12 months
from the date of order if no other fixed deadlines have been agreed. If call
does not follow or not completely within 12 months from the date of order or on
the agreed call terms the Purchaser shall be deemed in default of acceptance.
9. Should the Purchaser fall into acceptance arrears or infringe duties of cooperation we are entitled to claim compensation for loss incurred by us including any additional expenses. In such event risk of accidental destruction or
loss or accidental deterioration of the item of purchase shall transfer to the
Purchaser if the latter is in default of acceptance.
VI. Transfer of Risk, Packaging Costs and Insurance
1. Upon handover to the forwarding agent or carrier and at the latest upon
leaving our premises risk of accidental destruction or loss and accidental deterioration transfers to the Purchaser. Incoterms 2000 „ex works/ab Werk“
Clause (German version) applies.
2. Should handover be delayed due to any circumstance for which the
Purchaser is responsible or as a consequence of the latter‘s instructions
risk shall transfer to the Purchaser with effect from the date of notification of
readiness for despatch. At the express written request of the Purchaser we
undertake to insure goods stored with us at the Purchaser‘s cost. This also
applies in those cases where a delivery period has not been expressly agreed
with the proviso that risk transfers to the Purchaser 7 calendar days following
notification of readiness for despatch.
3. If the Purchaser wishes we shall cover delivery by transport insurance; costs
in this regard shall be borne by the Purchaser.
4. Transportation and all other packaging shall not be returned subject to requirements of the German Packaging Ordinance. Pallets are excluded. The
Purchaser undertakes to arrange disposal of packaging materials at his own
cost.
5. Delivered items shall be received and accepted by the Purchaser even if
they display minor imperfections irrespective of his rights under the terms of
§§ 433 ff. BGB.
VII. Reservation of Title
1. Up to the point of full settlement of the purchase price including all subsidiary claims and prior to settlement of all other claims arising from the business
association goods delivered shall remain our property. Up until that point the
Purchaser is not entitled to pledge the goods to third parties or to assign them
as security. The Purchaser shall store the reserved goods for us at no charge.
2. In the event of processing and combination of reserved title goods with other
goods by the Purchaser we shall acquire joint title to the new item in the ratio
of the invoiced value of the reserved title goods to the combined material entity.
The joint title rights accordingly ensuing shall be considered as reserved title
goods as defined in Clause 1.
3.The Purchaser is entitled to sell the reserved title goods in the due process
of sale provided he is not in payment arrears in respect of our purchase price
claims.
4. The Purchaser hereby assigns to us at this point in time all claims accruing
to him as a result of resale of the reserved title goods vis-à-vis third parties. If
the reserved title goods are sold following processing, combination or amalgamation assignment of the claim arising from resale shall apply only up to the
extent of the value of the reserved title goods invoiced to the Purchaser by the
Vendor. This shall also apply if the reserved title goods are resold together with
other goods which similarly do not belong to the Vendor.
5. The Purchaser is also authorised to collect the claim even following assignment. We may restrict the said collection authorisation on the basis of justifiable interest or revoke the same on due cause found, in particular in the event
of payment arrears. We may require that the Purchaser shall notify us of the
claims assigned to him and of related debtors plus all information necessary
for collection and surrender to us all associated documentation and disclose
the said assignment to his debtors.
6. We undertake to release the securities due to us on the basis of the above
provisions at our discretion upon the Purchaser‘s request to the extent that
their realisable value exceeds the claim secured by 20% or more.
7. The Purchaser hereby declares his consent that the persons authorised
by us in connection with assignment of the reserved title goods may enter
the property or building on or in which the items are situated in order to take
possession of the reserved title goods.
8. The Purchaser shall immediately inform us in respect of any confiscation,
compulsory enforcement or other third party intervention adversely affecting
our rights of ownership. The Purchaser shall bear the costs of measures to
remedy third party interference in particular of any possible intervention procedures.
VIII. Guarantee and Liability
1. Should there be any defect for which we are responsible we are entitled to
decide between rectification and replacement at our own discretion. A precondition in such an event is that the defect is not immaterial. In the event
of rectification we undertake to bear the costs of transportation, labour and
materials provided these are not increased due to the fact that the goods supplied have not been moved to a location other than the place of performance.
Should one of or both forms of remedy prove impossible or disproportionate
we are entitled to refuse it.
We may refuse to effect a remedy for as long as the Purchaser fails to meet his
payment obligations towards us to an extent equating to the fault-free portion
of the goods or services.
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
235
general terms and conditions of sale
2. Should rectification or replacement fail to be made within an appropriate
period - with due consideration of our supply options - or if rectification and
and/or replacement should fail the Purchaser may demand a reduction of remuneration (abatement) or withdraw from the Contract.
3. The Purchaser‘s rights in the event of defect assume that the latter has met
his obligation under § 377 HGB [Civil Code] to inspect and submit complaints
upon receipt of the goods in a timely manner.
4. If nothing to the contrary emerges under Section 6 below further claims on
the part of the Purchaser, irrespective of legal grounds (in particular claims
arising from infringement of main and ancillary contractual obligations, reimbursement of expenses with the exception of those defined in § 439 II BGB,
impermissible act and any other tortious liability) are excluded; this applies in
particular to damage not occurring to the item supplied itself including compensation claims for lost profit; also included are claims which do not result
from the faulty nature of the purchased item.
10. Contract work completed by us on the basis of drawings, sketches or other
information provided to us is carried out at the Purchaser´s risk in respect of
patent, pattern and trademark legislation. If execution of such orders involves
infringement of third party industrial property rights the Purchaser shall bear
the cost of all damages incurred by us.
IX. Liability for Collateral Obligations
If through any fault on our part the item supplied cannot be used as stated
under the terms of the Contract or if damage occurs as a consequence of
omitted or faulty implementation of suggestions and consultations prior to and
subsequent to conclusion of the Contract including other contractual collateral
obligations to the exclusion of further claims on the part of the Purchaser the
provisions of Clauses VIII and X shall apply accordingly.
X. Withdrawal by the Purchaser and other Liabilities on our part
5. The above provisions also apply in the case of delivery of another item or a
lesser quantity.
6. The liability disclaimer provision under Section 4 shall not apply if any exclusion or restriction of liability agreed for injury to life, physical injury or damage
to health is due to intentional or negligent dereliction of duty on the part of
the user or intentional or negligent dereliction of duty on the part of any legal
representative or vicarious agent of the user; nor shall it apply if any exclusion
or limitation of liability is agreed for other forms of damage caused by any
intentional or grossly negligent dereliction of duty on the part of any legal
representative or vicarious agent of the user.
If we culpably infringe any essential contractual obligation or any „cardinal“
obligation liability shall not be excluded but shall be limited to typical foreseeable contractual damage; in other respects it is excluded under Section 4.
The liability disclaimer additionally does not apply in those cases where under
product liability legislation in the event of defects in the goods supplied there is
liability in the case of personal injury or damage to property relating to privately
used items.
Nor does it apply in the case of assumption of a guarantee and assurance of a
characteristic feature if a defect covered thereby activates our liability.
In the event of reimbursement of expenses the above shall apply accordingly.
7. No guarantee is assumed in the event of damage attributable to inappropriate use, faulty assembly by the Purchaser or third parties, natural wear
and tear, incorrect or negligent treatment, improper modifications carried out
without our prior consent or servicing work by the Purchaser or third parties.
8. Claims for remedy, damages and replacement use shall be time-barred one
year from the date of purchase of the item concerned.
This does not apply to any item used in accordance with its customary purpose
for a building and has caused faultiness in the latter in which case time-barring
is after 5 years.
Claims for abatement of price and exercise of any right of withdrawal are
excluded if the claim for remedy is time-barred.
In the event of operation of Sentence 3 however the Purchaser may only refuse
payment of the purchase price to the extent that he would be entitled to do
so as a consequence of withdrawal or abatement; in the event of withdrawal
exclusion and subsequent payment refusal we are entitled to withdraw from
the Contract.
9. Claims arising from manufacturer redress remain unaffected by this Section.
236
1. The following provisions shall apply in the event of infringements over and
above liability for defect and shall neither exclude nor limit statutory right of
withdrawal.
Similarly, lawful or contractual claims due to us shall be neither excluded nor
limited.
2. The Purchaser may withdraw from the Contract if the overall performance is
definitively impractical, the same applying to incapacity.
The Purchaser may also withdraw from the entire Contract if in the event of
an order for similar items implementation of part of the supply is impossible in
terms of numerical quantity due to our representation obligation and if he has
no interest in partial supply; if this is not the case the Purchaser may abate the
consideration accordingly; the right of withdrawal shall not apply in the case of
immaterial infringement of obligation.
3. Should there be any delay in performance and provided the Purchaser
grants us an appropriate period to complete performance following justification
of the delay and should the said period fail to be observed the Purchaser shall
be entitled to withdraw. In the event of partial delay in performance Section 1
Sentence 2 shall apply accordingly.
If prior to delivery the Purchaser requires in any aspect alternative execution of
the item supplied the delivery period shall be interrupted until the date of agreement regarding execution and if necessary extended by the time necessary
for alternative execution.
4. Withdrawal shall be excluded if the Purchaser is solely or to a large extent
predominantly responsible for the circumstance entitling him to withdrawal or
if the circumstance for which we are responsible occurs at the point in time of
default in acceptance on the part of the Purchaser.
In the event of impracticality we retain in the above cases our claim to consideration as defined in § 326 Section 2 BGB [Civil Code].
5. Further claims on the part of the Purchaser, irrespective of legal grounds (in
particular claims arising from default at the point of conclusion of the Contract,
infringement of main and ancillary contractual obligations, reimbursement of
expenses, impermissible act and any other tortious liability) are excluded; this
applies in particular to damage not occurring to the item supplied itself including compensation claims for lost profit; also included are claims which do not
result from the faulty nature of the purchased item.
This shall not apply if the cause of damage is due to intent or gross negligence
on our part, our legal representatives or vicarious agents. Nor shall this apply
if the damage arises from culpable injury to life, physical injury or damage to
health.
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
To a similarly lesser degree liability in the event of assumption of a guarantee
is excluded if an obligation infringement covered thereby activates our liability.
If we culpably infringe any essential contractual obligation or any „cardinal“
obligation liability shall not be excluded but shall be limited to typical foreseeable contractual damage.
XI. Place of Performance and Jurisdiction
1. Place of performance of both parts arising from all legal relationships is
70771 Leinfelden-Echterdingen.
2. In respect of the legal relationship between the Purchaser and us the laws
of the Federal Republic of German apply. UN Sale of Goods legislation (CISG)
is expressly excluded.
3. Legal venue for all disputes arising form the contractual relationship is
Leinfelden-Echterdingen. We are also entitled to file an action at the domicile
of the Purchaser.
Leutron GmbH · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de
237
Surge protection for power supply systems
Surge protection for measuring systems and automatic control devices
Surge protection for information technology and telecommunication
Surge protection for transmitting and receiving systems
EMC filter with integrated surge protection
Monitoring
Rare-gas-filled insulation spark gaps
Leutron GmbH
lightning and surge Protection
Humboldtstrasse 30/32
D-70771 Leinfelden-Echterdingen
germany
Phone:+49-(0)711-94771-0
Fax:+49-(0)711-94771-70
[email protected]
www.leutron.de
www.LEUTRON.DE
Protective devices for AC arresting

Similar documents

Short Form Catalogue 2016

Short Form Catalogue 2016 Multi-pole lightning current arrester type 1 (class I) for 3-phase TN-S systems. The arresters can be installed at the transition 0A to 1 accord-ing to the lightning protection zones concept. The S...

More information

WWW .Leutron .de - El

WWW .Leutron .de - El Surge protection for measuring systems and automatic control devices Pluggable SPD with high discharge cappability for MCR applications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

More information