Tenant Design Criteria Manual, Dated , West Oaks Mall
Transcription
Tenant Design Criteria Manual, Dated , West Oaks Mall
I INTRODUCTION This manual and tha accompanying tenant plan contain the information necessa~ for a Tenant’s architect and engineer to design and generate construction documents for a ratail store at West Oaks Mall. ! Section One is the project diractory listing all codes,city departments, utilities, and other pertinent information. Section Two contains color renderings and material samples for the common. Also included are interfor and exterior elevations of the Mail that illustrate the Mall’s common area% colors and architecture. I Section Three contains the storefront and store interior design criteria. The Mall colors and architecture shown in tha previous section should be taken into account when designing the storefront. Section Four contains the signage criteria. This section can ba sent diractly to the sign manufacturer. Section Five includes all mechanical, elecncal, and plumbing requirements. Section Six outlines the drawing requirements. Tha plans must conform to these requirements when submitted to Homatt for Landlord review. Section Seven describes the submittal process for both the Landlord and City of Ocoee review process. I Saction Eight is the architect’s checklist. This spans out all the requirements for the architect’s use. Section Nine contains the Food Court design and signage criteria I Section Ten contains all the architectural, mechanical, electrical, and plumbing details. The details referenced on the Tenant Plan (TP) are in this section. The Landlord will review the plans for compliance with the design criteria and the lease only. After Landlord review, 3 sets of plans must ba submitted to the City Of Ocoee Building Department (see Section one for the City address) for code compliance reviaw and building permit. The City building permit application must hava tha Landlord’s signature before it is submitted The Building Department has indicated that this raview will take thrae weeks, This permit time must be built into the store’s construction schadule. FIRE DEPARTMENT OCCUPANCY CLASSIFICATION: 125 NORTH BLUFORD AVE. OCOEE, FL 34761 (407) 656-7796 (SBCCI 310.1) MERCANTILE OCCUPANCY GROUP M COVERED MALL (SBCC1413) TYPE OF CONSTRUCTION: TYPE IV (UNPROTECTED BUT SPRINKLED) SBCCI TABLE 600 MINIMUM EXITS: TWO OR MORE EXIT POINTS REQUIRED OF SPACES GREATER THAN 2250 SQUARE FEET WHEN TRAVEL DISTANCE EXCEED 75 FT. WITHIN TENANT SPACE TO IT’S EXIT (SBCCI 413.4.5.1). IF THE EXIT IS THROUGH A STORAGE AREA A CONTINUOUS PATH OF EGRESS IS TO BE MAINTANED. UTILITIES: ELECTRIC FLORIDA POWER CORPORATION 1150 ORANGE AVE. WINTER PARK, FL 32789 (407) 629-1010 NATURAL GAS LAKE APOPKA NATURAL GAS DISTRICT 1500 E. HIGHWAY 50 SUITE 158 WINTER GARDEN FL. 34777 (407) 65&2734 TELEPHONE SOUTHERN BELL 500 N. ORAMGE AVE SUITE 400 0RL4ND0, FL 32801 (407) 351-8191 TOILETS TENANTS OVER 1500 SQUARE FEET MUST HAVE TWO BATHROOMS. I .:, I i’ l“’ i. 1 1, l“ [“ SECTION TWO WEST OAKS MALL OCOEE, FLORIDA ‘t i ., BASE BUILDING DATA [ [: 1’ 1.. 1“ 1 [ \ ., I I . . 4 ‘1 1“ 1. i 1 1 I 1, 1. 1’ [ 1’ 1.. 1’ I [ , ! ! 1. West OaksMallis located approximatiy 1Smiles northwestof Ortando internationalAirport at the lnte~~on of route SOand Clafi In Oooee, Florida. .,.. -+ ,..,, . L 1: + r--- xl .+. . . ,, +::: .. . .... L-- ) “1 ,t ).{------- ~ .,, . . . . :! .{ ,, :.... . . .. . . . . . THEATER : . . . . . \--—----. 1 ‘ “:0,””””” i +:-i:[l U-n FUTURE ------- ------- . ;! .: , - hi 2 LWL .-------j] ;q & -E-(3 ~*y~~~s -------. (3 N . -G + )(i)~’------y-- 8 Lii!E ----+ FUTURE : _-;, : . { * .; \.... , ..! ;... . t.. . 1: .; .; . I -’ . “ . ............... ....----M!3!3 f!!w d Plow Plan KEY Pi. 4N SECTION THREE STORE DESIGN CRITERIA PURPOSE Storefront Criteria sets forth the guidelines for storefront and interior design for all Tenant stores except those in the Food Court which are addressed The General elsewhere in this manual. LANDLORD REVIEW Tenants should understand that the storefront will be reviewed in context with previously reviewed neighboring storefronts and to make judgments for the benefit of the overall project. SITE VISIT The Tenant’s architect is required by the lease to make a site visit to verify the conditions and dimensions. The Landlord will not be responsible for omissions of architectural, mechanical, electrical, or plumbing within the tenant spaces. STOREFRONT AND CONTROL ZONE CRITERIA STOREFRONT ● The use of quality materials for the storefront and interior makes a strong statement to the customers and maintains consistency with the design image within the mall. Avoid materials that are easily damaged or difficult to maintain. . The lease line on some storefronts projects 2’0” beyond the bulkhead. All storefronts in these areas must follow the Ieaseline creating a 3D architectural ‘popout’ storefront, The TP Plan included with this design manual will reference the detail which outlines the condition at your space. . The storefront shall be designed, fabricated and installed by the Tenant at its own expense, ● ● ● ● ● ● ● Totally open storefronts are prohibited. The maximum opening allowed is 50% of the storefront width with a strongly articulated entrance. The mall flooring must qdend from the Lease Line to the storefront closure line ending with a full tile. The tile can be purchased from the landlord at the site. Rolling grilles are discouraged. Tenants should investigate alternative closure methods. Key switches must be flush mounted at 12” A.F.F. and not face the mall. Tenant is required to install a 3M” metal reveal between the top of the storefront and the Landlords bulkhead. All fastners must be hidden. The lease line establishes a two foot ‘pop-out’ storefront. A section through the bulkhead is contained in the details at the back of this manual showing the relationship of the lease line to the bulkhead. The storefront cannot project past the lease line. The storefront must be self-supporting from the slab. The building structure is to be used for lateral bracing only. The Landlord has installed a one inch reveal at the demising required to have a 12” minimum line. Every Tenant is solid material zone continuos from floor to the bulkhead on both sides of the storefront abutting the neutral reveals. 9 All storefronts must have a minimum 4“ durable base. ● Entry doors cannot swing beyond the lease line. ● All storefront glass must be butt joint. No silicone will be permitted. ACCEPTABLE STOREFRONT MATERIALS METAL Brushed or stainless steel Polished or brushed brass or bronze, Brushed or polished aluminum. Baked enamel. CERAMIC TILE, MASONRY, AND STONE ● . . Polished or honed granite Marble. Other stone, polished or honed. I ‘] . 1 ‘1 (,’ 1 i (’ 1... / 1. I 1 \ 1 , . WOOD Hardwoods, painted or natural stained. ● GLASS ● c . . Clear-tempered butt glass with polished or beveled edges minimum 3\B” thick Window panes. Glass tile. Glass block. LAMINATE Solid core. Note that code limits plastic to a maximum 20% of the storefront. ● PAINT ● Zolotone or equal only UNACCEPTABLE STOREFRONT MATERIALS ● . ● . ● ● . . . ● . . ● Simulated metals including laminates Anodized aluminum Textured or colored acrylic (imitation stained glass or mirror) Glass mirror Vinyl or paper wallcovering Simulated stone Pegboard Distressed wood Masonite Cork Shingles Simulated wood Painted gypboard (Zolatone or polymix will be judged on a case-by-case basis) I CONTROL ZONE The front six foot (60”) area inside the lease line is designated tenants, except food court, must comply with this criteria. . c . . ● as the control zone. All The first six feet (60”) of ceiling must be drywall. All lighting must be incandescent recessed fixtures. No fluorescent fixtures will be allowed in the control zone. Sprinkler heads must be concealed heads. Floor materials must have butt joining. Vinyl transition strips are not allowed. STORE INTERIOR Every portion of the demised premises visible to the public is subject to review and approval by the Landlord. CEILING ACCEPTABLE CEILING MATERIALS ● Gypsum wall board Q 2x2’ acoustical tile. ● ● Semi-recessed sprinkler heads are required in all ceiling areas except the control zone. Concealed or fine line spline. UNACCEPTABLE CEILING MATERIALS ● 2)X4’ acoustical ceiling tile LIGHTING ● Tenant will provide all lighting within the leased premises. c Track lighting shall match the ceiling color. ● All fixtures must be 2’x2’. No 2)X4’fixtures will be allowed. ● No strobe or flashing lights ara permitted. ● No lighting will be allowed outside the leased premises. FLOOR AND SLAB ● No vinyl flooring is allowed in the sales area. ● Carpet shall meat the following standards: 1. ~ Fiber I Yarn Weight Stitches 100% DuPont Antron Ill continuous filament nylon 280z. persquare yard 72 per inch 1 ‘ ,, ● Sealed concrete isallowed asaminimum finish instorage areas. / . Sales area flooring must match the height of the mall common area ‘1 \ !’ 1. s, [“” 1. 1. i i. 1 \I SECTION FOUR SIGNAGE This section should be coDied and aiven to the sian manufacturer Signage communicates the store name and identity to the customers in the mall. High quality, distinctive signage gives the shopper an easy way to identify the store and together with the storefront, interior design, and merchandise presentation forms the visual presentation to the customer. Sianaae Criteria ● Each Tenant is allowed one sign per storefront elevation. ✎ The wording of tha sign is limited to the name of the atore as listed in the lease. ● Maximum tatter height is 16 inches ✎ The length of the sign cannot exceed 70% of the storefront length. ● The sign cannot extand more than 5 inches beyond the lease line. ✎ Logos will be reviewad on an individual basis. ✎ Flashing or moving signs will not be allowed. ● All signs must have a local disconnect. ✎ All signs shall have a timeclock to control the sign. ✎ All neon signs must have P-K housings. Atxxorxiate ● sian tvDes Backlit reverse channel letters pin mounted a maximum of one inch from a nonreflective background ● Exposed neon tubing. Double stroke neon is prefered. ● Routed face with intamally illuminated letters ● Dimensional letters with gold or silver leaf. 1, l“’ 1., J 1 I ( -. s Edge lit sandblasted glass . Silk screened canopy or awnings. . Etched or frosted glass. . Pin-mounted non-illuminated individual letters. . Vinyl or silk-screened letters maybe applied to the interior surface of the storefront glass at 30 inches above the finished floor. Maximum height of the letters is 2 inches . Fiber optic signs Inamxorxiate ● sian twes Typical plex-faced channel letters are discouraged. The tenant is encouraged to explore different signage types. ● Flashing, moving or rotating. ● Vacuum formed luminous letters ● Styrofoam or paper signs. ✎ Hanging banners. ● Neon on a reflective surface. ✎ Non-recessed box or cabinet signs. ✎ Temporary signs All signage will ba reviewed on a case by case basis. If there is any question whether your proposed sign meets the criteria, call the Tenant Coordinator at (312) 551-5356 or fax a drawing to (312) 551-5064 prior to submittal. Installation Requirements 1 .,1’ . All mounting attachments shall have concealed fastenings. Manufacturer’s labels, stamps, and U.L. labels shall not be visible from the mall. . Alocalconcealed . Allneon signs musthave glass s!andoff posts ● Allwires, raceways, andcrossovars must be concealed. disconnect must beprovided ateach location I 1’ s“ 1,, I I 1 I ● All illuminated signage must conform to the electrical and local codes. ✎ Sign contractor will repair any damage to the Landlord’s neutral surface or mall flooring. ● Sign contractor must secure any necessaV permits prior to installation. . Sign manufacturer must submit 4 sets of sign drawings forapproval. The drawings must include a storefront elevation, dimensions, colors, attachment method, and section through the sign showing the wiring. SECTION FIVE STORE TECHNICAL CRITERIA ARCHITECTURAL STRUCTURE . The landlord will provide the slab in all spaces except the Food Court and designated restaurant spaces. The slab will be four inches with wire mesh. All sawcutting for utilities is by Tenant at Tenant’s expense . The Landlord will provide a 5x5’ blockout araa in each space which will contain the sanitary sewer stub. Should Tenant dasire to lo&te the toilet in an area other than the blockout area the Tenant shall, at it’s expense, remove ,the existing concrete, relocate the sanitary stub, and replace the concrete. . The roof structure is shown in the Details. Any penetrations, flashing, and patching will be by Landlord’s roofer at Tenant’s expense. FLOOR PLAN ● . A second exit will be required for all tenants over 2250 square feet or a travel distance greater than 75 feet. All spaces abutting a service corridor will require a second exit regardless of size. If the second exit is through a storage area a continuous path of egress must be maintained. This can be accomplished by striping the floor. The material and dimensions are subject to Ctty approval, WALLS AND PARTITIONS . Landlord will provide 3 5\8” metal studs on the centerline of all demising and corridor walls. Tenant shall furnish 5\8” fire core gypboard, at their expense, on all stud walls which shall be sealed smoketight around all penetrations and the deck above. . The calculation of the square footage of the space is taken from the centerline of all intenor partitions and shaftwalls and from the outside face of all etierior walls. ● The Tenant shall provide a 3x7’ service door connecting to all interior service corridors. The door shall be equipped with hardware required by code and be recessed to a depth equal to the width of the door. This door shall be a Class ‘B’ labeled, painted hollow metal door and shall compfy with local code. A sprinkler head must be provided in the alcove. ● The Landlord will install a 3’x7’ hollow metal door and frame, including butt hinges, latching hardware with a blank lock cylinder on the intenor and a removable core lock cylinder the exterior. ● Tenants whose normal operations generate moderate to high noise levels (i.e., pet shops, game rooms, record shops, stereo and video centers, etc.) shall insulate their demising walls and ceiling against noise transmission. A detail on the required insulation is included in this manual. STOREFRONTS . Vertical neutral surfaces and neutral piers by the Landlord. Tenant shall construct a complete storefront to the full height of the opening. The Tenant shall provide a 3\4° reveal between the storefront and the Landlord bulkhead. . The storefront shall be self suppoding. The mall structure may be used for veticel bracing only. All attachments w“II be inspected and approved by the Landlord’s field personnel. The storefront or storefront sign cannot be suspended from the mall bulkhead. . All rolling grilles, if approved by Landlord, must have a second means of egress from the inside. There must be a manual release or another means for someone trapped inside the store to raise the grille and escape. INTERIOR FINISHES ● All floor finish materials shall correspond exactly with the level of the finished mall floor at the lease line. ✎ The mall flooring must extend into the closure line of the store. ● If an expansion joint occurs within the space the Tenant shall treat the joint in accordance with accepted design practices and code. ● Landlord guarantees a clearance height of 12’ W in each space. The Tenant architect shall field verify if additional clear height is needed. Any relocation of Landlord installed utilities or infrastmcture above this height will be at Tenant expense. . All ceiling material shall be Class “A” rated and the suspension conform to local code. system shall . Ceiling systems should be suppotied from the top chord of bar joists within the space. MECHANICAL ● . ● The Landlord has pre-selected a mechanical contractor to supply and install all Tenant roof top units (RTU). Tenant’s mechanical engineer specs any of the Carrier units listed in the Mechanical Details and the Landlords contractor will mount the unit onthecuti ineachspace. Thelo=tion oftiecu~s areshownonthe TP Plan which are included with this Print Package. The Mechanical. Details, at the end of this Manual, explain the complete program. The Tenanfs mechani=l contrador irresponsible forallducWoA within the space. A complete description of Landlord’s and Tenant’s contractors responsibilities are outlined in the Mechanical Details. The RTUandall related mechani@l wo*areat Tenant's expense. ELECTRICAL . ● Landlord will provide an electric distribution system of 480/277 volts, 3 phase, 60 cycle, 4 wire, to the electric meter rooms. The location of the electric rooms are shown in the electrical details at the end of this manual. Landlord shall provide disconnect switches, meter socket and connecting cables between the switch and the socket. Landlord will also provide an empty conduit to each tenant space with pull string. The wire from tha disconnect to the space and the distribution of the service within the space is by Tenant at Tenant’s expense. The electrical room number, conduit size, and service size are shown on the TP Plan, Q The electrical services are sized at 10 watts per square foot for retail tenants, 60 watts for the Food Court and restaurant spaces. Additional capacity is available and any upgrade of service size will be at Tenant’s expense. ● ● A complete electrical panel schedule is required on each set of electrical drawings. Electrical equipment and materials shall be new, shall be National Electrical Code Standard and shall bear the U.L. Label. All wire must be copper. All wiring must be in E.M.T. conduit, PLUMBING a Cold water will be provided to each tenant space. The size of the line and the approximate location are shown on the TP Plan. The water service will terminate in a valved connection. Tenant shall, at it’s expense, connect at the point of service, install an accessible water meter read in gallons, and extend sewice throughout the space. ● Landlord shall provide a sanita~ sewer stub to each tenant space. The stub w“ll be located in a 5x5’ ‘blockou~ which will have no concrete. (See Structure section for a more detailed description). ● Each space shall provide a handicapped toilet per The Florida Accessibility Code for Buildings. Spaces over 1500 sauara feet are rewired to have two toilets and two lavatories. A minimum of one watercioset, one lavatory, one 4 cleanout, and a floor drain with trap primer are required in each toilet. ● Landlord will provide a sanitary vent connection above each blockout. ● Landlord will provide a 4“ grease line to all Food Court and restaurant tenant spaces. Tenant shall connect all sinks and floor drains, except toilet sinks and drains, to the grease line in accordance with local codes. Any food Tenant outside the Food Court or designated restaurant areas must install a dedicated grease trap with necessaty plumbing and indicate it’s location on the plumbing plans. Tenant will be responsible for maintaining the dedicated grease traps. ● Natural oas will be available to the Food Cow-l and restaurant tenant soaces in the truck co;rt nearest the space. All piping and associated work for the ~~e”nsion” of the service from the manifold to the space is by Tenant, at Tenant expense, Tenant must then contact the Lake Apopka Natural Gas Oistrict for the establishment of service. TELEPHONE . Tenant must arrange telephone service with Southern Bell. (All the Utility phone numbers are listed in the Project Directory). . Landlord will supply a 1/2 empty telephone conduit to each space. FIRE Protection/LIFE . SAFETY Landlord will provide a blind flange in each space. Tenant shall design and install the sprinkler at Tenant expense. ● ● ● . All sprinkler heads in gypboard ceilings must be concealed and all sprinklers heads in drop ceilings must be semi-recessed. Tenant must furnish and install a minimum of one 2A-1OBC fire extinguisher in the space per code. Additional extinguishers may be required depending on contents and square footage. Food court tenants shall provide a minimum 40:BC extinguisher to ba used in conjunction with the hood suppression system. A completa life safety alarm, including stroba lights and speakers, must ba installed in each space. The Landlord will install the system and wiring from the tenant space to the mall fire alarm panel. Tha Tenant must install the system within the space using the Landlord’s designated fire alarm installation contractor at Tenant expense. Details of the system are in this manual. GENERAL . ● s Landlord will provide temporary electric service but the Tenant Contractor must notify Florida Power to have a mater installed as soon as possible. The RTU cannot be started until permanent power has been established in the space. Landlord will supply common dumpsters in each truckcourt for all tenant contractors use. Each Tenant Contractor must report to Homart before they begin construction. A Contractors Manual will be given to the contractor at this time which covers all Landlord regulations regarding Construtilon and all inspection and utility information. Final Plans Architectural . Two sepias are required for submittal - no bluelines ● Cover sheet must show Tenant Name Location plan Square footage Applicable codes (see project directory) Building data (also see project directory) . Floor Plan Dimensioned wall locations Dimensioned interior partitions Restroom with fixtures locations Floor finish materials . Fixture Plan . Storefront and Interior Elevations All storefront materials specified with samples All Interior elevations in the sales area Storefront signage shown . Sections and Details Longitudinal and transverse sections through storefront from slab to roof. Transverse section minimum of 1 Iv= 1 Foot. Sections of all demising walls Details of where the storefront meets neutral pier at floor level Details of any non-typical or special construction. . Reflected Ceiling Plan Ceiling heights Type of ceiling construction Suspension system Location and size of all lighting fixtures, supply and return diffusera, and access panels. . Schedules All storefront, interior, and door schedules. Plumbina Plans . Floor Plan Toilet facilities Location of any other plumbing fixtures Location of sewer connection Location of vent connection Connection to grease line, if applicable . Risers and Details Sanitary riser diagram showing drain, cleanout, and pipe sizes Domestic water with location of water meter with remote readout. Water Heater with relief valve and piping to floor drain Water meter location HVAC PLANS ● Ductwork layout RTU size and location Duct sizes Types of insulation Diffuser and grille schedule indicating CFM . Tenant Alr ConditioningSystems information RTU model number Tenant AiI% address and contact Tenant Air and Tenant mechanical contractors responsibilities . Exhaust Systems Cooking equipment location CFM information Equipment specs ● Cooking Hood Details Roof top fan and curb details Make-up details and specifications Fire extinguishing equipment Hood details [ 1“ 1’ I 1“ [ 1 1. r 1 1. 1“ 1. / [. 1. \ ! I Electrical Plans . Floor Plan Location of all floor and wall outlets Location of transformer and panal boards Location of all other electrical equipment . Power Plan Wiring layout . Electrical Ceiling Plan Lighting fixture layout Emergency and exit light locations . Electrical riser diagram Feeder conduit and wire sizes Arrangement of panels, transformer, timeclock, etc. Wire sizes and conduit location to RUT ● Electrical panel schedule showing all loads in watts, mnnected and demand . Lighting fixture schedule Sorinkler Dlans Sprinkler shop drawings must be submitted with the set submitted for permit. The plans must be prepared and sealed by a licensed fire protection engineer registered in the State of Florida. ● Sprinkler shop drawings Location of all sprinkler heads with main and branch pipe sizes Temperature rating of all heads and hydraulic calculations Any ceiling construction (i.e., drop soffits, vaulted ceilings, etc.) that will effect sprinkler coverage Fire Alarm Plans Fire alarm plans must be submitted with the set submitted for permit Location of all strobes and speakers with wiring to Landlord supplied connection point. Sianaae Plans See signage requirements in Store DesignCriteriasection of this manual. I 1“ 1’ I 1 [ I 1. ,I [ I 1. I I I 1. I 1 1 i SECTION SEVEN CITY OF OCOEE PERMIT SUBMISSION REQUIREMENTS The City of Ocoee Building Department requires the following for all plans submitted for building permit . Three sets of Landlord approved plans which include sprinkler shop drawings and tire alarm drawings . All spaces over 1500 square feet must be sealed by a registered architect and engineer ● All Food Court and restuarant tenants must submit hood details, make-up air details and plans detailing extinguishing equipment. Hood systems must be approved by the Building Department prior to the fire suppressiontest. The City review will take about three weeks. This time should be built into the construction schedule to assure that the store will open by the lease required opening date. The City of Ocoee Building and Zoning Department is located at 150 N. Lakeshore Drive Ocoee, Florida 34761 (407) 656-2322 I 1’ I I [ 1 l.. 1. Plan Requirements A. Preliminary 1. Mimimum submittal requirements area floorplan, reflected ceiling plan, storefront elevation, sample board, and color rendering or photograph. One sepia is required for submittal B. Final plans Submittal must include complete architectural, mechanical, plumbing, and electrical as outlined on page of this manual. Two sepias are required for submittal C Sign Plans Signage must be shown on the architectural plans but a sepia and four bluelines of the sign manufacturers shop drawings must be submitted for approval. D. Sprinkler Plans Sprinkler plans must be sealed by a licensed fire protection engineer in the state of Florida and submitted to Ocoee Fire and Rescue for approval. 2. General I I [ I i I I [ I 1’ SECTION EIGHT [ I I I [. I I [. 1. I I !. I i WEST OAKS ARCHITECTS CHECKLIST PLAN SUBMllTALS PRELIMINARY REVIEW FINAL WORKING DRAWINGS ; SIGN DRAWINGS 4 SPRINKLER DRAWINGS FOOD RELATED TENANTS 2 BUILDING DEPARTMENT 3 SEPIA TO LANDLORD. WET REGISTERED SEPIAS, SEALED, ARCHITECT FROM THE STATE OF TEXAS TO LANDLORD. PRINTS, SIGN MANUFACTURES SHOP DRAWINGS TO lANDLORD. PREPARED AND STAMPED BY A LICENSED FIRE PROTECTION ENGINEER FROM TEXAS. SETS OF lANDLORDS APPROVED PLANS TO HEALTH DEPARTMENT. SETS OF HOMART APPROVED PLANS INCLUDING SPRINKLER AND FIRE AL4RM PIANS. PLEASE SUBMIT UPON PRELIMINARY REVIEW (ONE SEPIA) COLOR ELEVATION OR RENDERING OR PHOTOGRAPH (5X7MIN). ELEVATION TO BE AT W= I’SCALE. INCLUDE GRAPHICS AND SIGNAGE. MATERIAL SAMPLE BOARD WITH ALL MATERIALS lABELED. SUBMIT ARCHITECTS NAME FORM. GENERAL PLAN SUBMllTAL REQUIREMENTS (TW O SEPIAS) INCORPORATE TYP. NOTES SHT AO INTO FINAL PLAN SUBMITTAL ELEVATIONS & STOREFRONT PROVIDE FULLY DIMENSIONED STOREFRONT ELEVATION MATERIALS ALONG WITH SECTION THROUGH STOREFRONT. INDICATE [ I PROVIDE STORE ADDRESS AT UPPER RIGHT HAND CORNER OF LETTER HEIGHT SHALL BE EXACTLY 2 HIGH AND STOREFRONT. PERMANENT. COLOR BLACK. HELVETICA. STOREFRONT GLASS SHALL BE BUTT JOINT %“ GAP NO SILICONE ALLOWED. (BEVELED AND POLlSHED EDGES.) 4 MINIMUM DURABLE BASE EXPOSED TO MALL MAINTENANCE AT STOREFRONT. ALL LAMINATES SHALL CONTAIN COLOR THROUGHOUT MATERIAL. IAMINATES SHALL BE APPLIED OVER 3/8” MINIMUM PARTICLE BOARD SIIRSTRATE. ---. .—. ALL PRESSURE TREATED WOOD,SL4TWALL, ETC.MUSTBEBACKED BY 5B’SHEETROCK. PROVIDE 3/4” BIACK METAL REVEAL AROUND PERIMETER OF STOREFRONT. REVEAL SHALL BE FLUSH WITH STOREFRONT MATERIAL. TENANTSIDEOF STOREFRONT BULKHEAD SHALLBESEALED AIRTIGHT TODECKTOENSURE IHR.ENCLOSURE. STOREFRONT KEY SWITCHES SHALL BE FLUSH MOUNTED AND NOT LOCATED ON THE FRONT FACE OF TENANT STOREFRONT. SWITCH COVERS ARE TO MATCH ADJACENT STOREFRONT MATERIALS AND COLORS. MAXIMUM HEIGHT OF SWITCH 12 A.F.F. ROLL DOWN GRILLE SHALL BE COMPLETELY ENCLOSED IN GYPBOARD. ROLL DOWN GRILLE MUST HAVE THIS NOTE ‘THIS DOOR IS TO REMAIN OPEN DURING OCCUPANCY.” 1“ ! I I I 1. [ I 1. I I I I I 1 / I FLOOR PIAN ALL CONSTRUCTION MUST COMPLY WITH FLORIDA ACCESSIBILITY CODE FOR BUILDING CONSTRUCTION. SWING TYPE DOORS ARE PREFERRED, WITH A 3’-0 LEAF AND HAVE CONCEALED HOLD OPEN DOORS. MATCH MALL TILE AND GROUT TO CENTERLINE OF CLOSURE. BUIT VINYL STRIPS ARE NOT JOINT BETWEEN MATERIAL CHANGES. ALLOWED. (MALL TILE CAN BE PURCHASED FROM HOMART.) COUNTERSIFIXTURES MUST BE GREATER THAN OR EQUAL TO 4’ PAST POINT OF ENTRY, REGISTER MUST BE RECESSED INTO COUNTERS. TENANT DEMISING PARTITIONS MUST BE OF FIRECODE TYPE “X SHEETROCK, TAPED AND SEALED AIRTIGHT TO DECK ABOVE. SECOND EXIT WILL BE REQUIRED FOR TENANT SPACES OVER 2250 SQ. FT. X 75 FT. TRAVEL DISTANCE. EXIT DOORS SHALL BE RECESSED WHERE TENANT EXIT IS ADJACENT TO CORRIDORS. CLEAR PATH OF EGRESS MUST BE MARKED ON THE FLOOR. I [ I 1’ I I I 1“ I [’ I 1. I 1. I I I i ALL TENANT AREAS WITH REAR SERVICE DOOR EXITS MUST FURNISH AND INSTALL PANIC HARDWAREAND AIARM SYSTEMS ON DOOR AS WELL AS SPACE NUMBERS AND BUSINESS NAME TO BE 3“ IN HEIGHT. CONTINUE W TEMPERED MASONITE WAINSCOT AND METAL CORNER GUARD INTO RECESSED VESTIBULE AT TENANTS REAR EXIT. ALSO PROVIDE CORNER GUARDS AND SPRINKLER HEAD. EXIT AND EMERGENCY LIGHTS WILL BE REQUIRED FOR ALL TENANT SPACES. NO FREESTANDING SECURITY DEVICES SHALL BE INSTALLED OR PLACED AT TENANTS LEASELINE. SECURITY DEVICES MUST BE DESIGNED INTO THE OVERALL STORE DESIGN. REFLECTED CEILING HARD CEILING REQUIRED IN THE FIRST & PAST POINT OF ENTRY AT LOWER ELEVATION THUS EXIT SIGN (REQUIRED PER CODE) CANNOT BE SEEN FROM MALL. LAY-IN CEILING SHALL BE EITHER CONCEALED SPLINE OR 2’X2’ DONNE FINE LINE GRID IN PUBLIC AREAS. PROVIDE ACCESS PANELS TO ALL EQUIPMENT I.E. SMOKE DETECTOR, VAV BOXES, SIGNS, ETC. FLUORESCENT FIXTURES SHALL BE 2X2’ IN ALL CUSTOMER AREAS WITH PARABOLIC LENSES. FOOD COURT TENANTS SHALL PROVIDE HARD CEILING IN SALES AREA. I.E. PAINTED G.W. B., METAL IN PUBLIC AREAS. DROP IN PANELS SHALL ONLY BE PERMllTED IN THE FOOD PREPARATION AREA. SIGNAGE INDIVIDUAL PLEX FACE CHANNEL LEll_ERS ARE DISCOURAGED. THE SIGN SHALL NOT EXTEND MORE THAN 5 BEYOND THE FACE OF THE STOREFRONT AND SHALL BE NO HIGHER THAN 16. FIRE PROTECTION/SPRINKLERS PROVIDE CONCEALED SPRINKLER HEADS IN ENTRY AND SHOW WINDOWS. E4CH TENANT SHALL FURNISI+ AND INSTALL FIRE EXTINGUISHERS THROUGHOUT THE TENANT’S LEASED SPACE. THE REQUIREMENT IS ONE (1) EXTINGUISHER PER 3000 SQUARE FEET OF SPACE WITH A MAXIMUM SEPARATION OF 75 FEET WALKING DISTANCE. TYPE OF EXTINGUISHERS SHALL BE CIASS 4-A: 40 B:C DRY CHEMICAL. 1 1“ 1’ I I [ I [ [ 1. 1. [ [ I I I I I FOOD COURT TENANTS SHALL PROVIDE 2 EXTINGUISHERS 2A:1 O B:C. REFER TO EXHIBIT D SECTION B. NO.6 REGARDING EXHAUST HOOD SPECIFICATIONS. FOOD COURT TENANTS SHALL PROVIDE 2 EXTlNGUlSHERS:2A: fiOBC. REFER TO EXHIBIT D SECTION B NO.6 REGARDING EXHAUST HOOD SPECIFICATIONS. AlARM SYSTEM PLANS MUST BE SUBMllTED WITH PERMIT SET. SPRINKLER DRAWINGS MUST BE PREPARED AND SEALED BY A LICENSED FIRE PROTECTION ENGINEER REGISTERED IN THE STATE OF FLORIDA ELECTRICAL SERVICE SIZE IS SHOWN ON T.P. PIAN. ALL VOLTAGE WIRE SHALL BE IN CONDUIT. PROVIDE ELECTRICAL RISER DIAGRAM AND COMPLETE ELECTRICAL PANEL SCHEDULE. SHOW ALL LOADS IN WAITS. LANDLORD PROVIDES METER BASE AND DISCONNECT, FUSES BY TENANT. TENANT FUSES SHALL BE BUSSMANN CURRENT LIMITING TIME DELAY, TYPE LPS ANDIOR NPE KRPC AS REQUIRED. NO COMBUSTIBLES ABOVE CLG. I.E. TRANSFORMERS, WATER .. —.--—HEATtRS. MECHANICAL LANDLORD’S PREAPPROVED CONTRACTOR TO SUPPLY HVAC UNITS. FLEX DUCT NOT TO EXCEED 60 IN LENGTH. (NOTE ON PLANS.) REFER TO TP PLAN FOR TOILET EXHAUST TAP SIZE. PLUMBING 314” VALVED WATER TAP SIZE. 11/2? IN FOOD COURT. PROVIDE DETAILS AND ISOMETRIC SHOWING CLEAN OUT AND FLOOR DRAIN WITH LOCATION, CONNECTION TO LANDLORD VENT, WATER HEATER DETAIL WITH RELIEF VALVE AND PIPING TO FLOOR DRAIN, GAS PIPING SYSTEM PIPE SIZES AND MATERIALS ETC. INSTAHEATERS ANDIOR EQUAL ARE ACCEPTABLE IN NON-FOOD SPACES. PROVIDE WATER METER TO BE READ IN GALLONS ACCESSIBLE TO lANDLORD PERSONNEL. NO P.V.C. PIPING ALLOWED ABOVE GRADE. [ [ i FOOD COURT I I I I [ i [ I I i I I I i I 1 ALL FOOD PREPARATION TENANTS ARE REQUIRED TO FURNISH AND INSTALL CORROSION RESISTANT, NONABSORBENT, SMOOTH EASILY CLEANABLE AND DURABLE MATERIALS IN FOOD PREPARATION AND SERVING AREAS. ALL FOOD PREPARATION TENANTS WILL BE REQUIRED TO FURNISH AND INSTALL A SEPARATE HAND WASHING SINK IN THE FOOD PREPARATION AREA AND A MINIMUM OF ONE (1) UTILITY SINK WITHIN THE LEASED PREMISES. PROVIDE GREASE INTERCEPTOR. ALL FOOD PREPARATION TENANTS ARE REQUIRED TO FURNISH AND INSTALL A FOUR COMPARTMENT SINK. FOOD COURT TENANT MUST MAINTAIN A NEGATIVE PRESSURE IN SPACE. MUST MAKE UP 90% OF EXHAUSTED AIR. TENANT SHALL INSTALL A ONE (1) HOUR RATED WALL EXTEND TO DECK AND ONE (1) HOUR RATED DOOR BETWEEN THE SERVICE AREA AND THE FOOD’ PREPAmTION AREA. THE DOOR SHALL BE SELF-CLOSING TO SHIELD THE BACK ROOM FROM PUBLIC VIEW. THE CEILING THROUGHOUT” FOOD ESTABLISHMENT, INCLUDING PREPARATION, SERVING AND STORAGE AREAS, ALONG WITH HALLWAYS, RESTROOMS, AND STAIRWAYS MUST BE OF AN APPROVED CONSTRUCTION WHEREBY THE FINISHED SURFACE IS SMOOTH, WASHABLE, EASILY CLEANABLE, IMPERVIOUS, AND LIGHT IN COLOR. COUNTER HEIGHT AND TRAY RAIL MUST MEET AMERICAN WITH DISABILITIES ACT. ALL FOOD COURT TENANTS SHALL SUBMIT COOKING HOOD DETAILS, MAKE-UP AIR UNIT DETAILS AND FIRE EXTINGUISHING EQUIPMENT, ETC. HARD SURFACE LE.; CERAMIC TILE NO VINYL TILE. GENERAL REQUIREMENTS NO GAS POWERED EQUIPMENT IS PERMllTED IN THE CENTER OR TENANT SPACES BY TENANT CONTRACTOR. FLAME SPREAD RATINGS ON TENANT STOREFRONTS AND INTERIORS ARE REQUIRED ON TENANTS FINAL WORKING DRAWINGS. EXIT AND EMERGENCY LIGHTS WILL BE REQUIRED FOR ALL TENANT SPACES. NO COMBUSTIBLES OF ANY KIND INCLUDING FIRE TREATED LUMBER CAN BE EXPOSED ABOVE THE CEILING LINE. ALL MATERIALS USED IN THE CONSTRUCTION OF THIS SPACE MUST BE ASBESTOS FREE. ANY WELDING REQUIRES NOTIFICATION TO HOMART LOCAL AUTHORITY AND THE FIRE DEPARTMENT PRIOR TO COMMENCEMENT. TENANTS WITH SAFES OR ANY HEAVY EQUIPMENT MUST PROVIDE ENGINEERINGFOR FLOOR LOAD. REFER TO EXHIBITS. COORDINATE DELlVERYWITH ON-SITEHOMARTAUTHORITY. [ I I I [ I I 1. I 1 I I I ANY ROOF PENETRATIONS SHALL BE BY LANDLORDS PREAPPROVED ROOFING CONTRACTOR AT TENANTS SOLE EXPENSE UPON NOTIFICATION AND APPROVAL BY LANDLORD. [ I I [ i I I [ [“ [ 1. I I I SECTION NINE FOOD COURT CRITERIA ● ● . ● ● I Counter fronts must be of a hard durable finish. Counters tops should be Corian or equal. Match landlord food court tile at the counter base. The serving area floor must be ceramic or quarry tile. Vinyl tile can be used in the prep area, Slabs will not ba provided in the Food Court spaces. The slab is to be provided by the tenant contractor at tenant expense. Natural gas is located in the truck murts on each side of the Food Court. The gas pipe must be run from the manifold in the truck court at Tenant expense. The meter is by the utility. . All construction must be in compliance with the Florida Accessibility Code for Building Construction, 1994 and all other codes outlined in the Introduction to this manual. . Food odors must be exhausted to tha atmosphere through a Tenant furnished and installed up-blast exhaust fan equal to Penn ventilator Co. Fume-X fan, in accordance with applicablecode. The fan unit shell be modified by the addition of a venturi type duct adapter to ensure a minimum discharge velocity of 2000 F.P.M. The exhaust fan will be equippad with a residue trough which be maintained by the tenant. The distance of each exhaust fan from any air intake shall be that which the local code allows. All penetrations are by Landlords roofer at Tenant expense. . There must be an electrical interlock to run the exhaust fan and make -up air unit simultaneously with the lights. . Makeup air systams for all tenant exhaust must be accomplished by a tenant furnished and installed maka up air system. [ I 1 All Tenant Food Court spaces will be furnished with a 4“ grease line tap, a 4 sanitary sewer line tap, vent mnnection and a 2“ domestic mld water line valved tap. [ ,. I ● I I I [ I I [’ I 1. I 1 I [ I I I I ● Exhaust discharge outlets and rooftop equipment shall be mushroom type with roof locations as approved by Landlord. The automatic extinguishing equipment shall be installed in accordance with the National Fire Protection Association Standard 96, latest edition, Section 10. The extinguishing system shall be Underwriters Laboratories approved C02 or preengineered system with the following features: a) protection of the hood and duct, b) surface protectionfor deep fat fryer, griddle, broiler and range c) automatic devices for shutting down fuel or power supply to appliances d) provided with a simple means to manually activate the fire extinguishing equipment. . The slab will not ba provided in each Food Court space. The tenant contractor will be responsible for pouring tha slab aftar the plumbing is installed. . The signbandwill be providedby the Landlord.Tenant signage will be brass front reverse channel letter signs mounted on the Landlord furnished sign band on the storefront. See the corresponding details (FI and F2) in this manual for the mmplete criteria. ● All food tenants must submit plans to the: Department of Hotels and Restaurants in Orlando (407) 423-6985 [ I I I I I I [ [“ 1“ 1. I 1. I I I i FOOD COURT SIGNAGE s Food Court signage will consist of individual dimensional backlit (halo effect) channel letters mounted on the Landlord providad sign band. ● . ● s Letters will be a minimum of one inch (l”) thick with a polished brass face and returns. The letter cannot extend further than five inches (S’) from the face of the signband. Backlit illumination to be provided by neon ranging from 3200K to 3700K. Neon tubes are to be completely concealed within the channel letter. Ballasts and transformers are to be concealed from public view with access provided from the tenants ceiling. Sign shop drawings are to be submitted to tha Landlord for approval Priorto fabrication. . Signage is to be controlled by a clock timer and illuminated during the hours that the mall is open. [ I I I I SECTION TEN DETAILS TABLE OF CONTENTS ARCHITECTURAL [ I 1 I [ I Al A2 A3 A4 A5 A6 A7 A8 A9 AlO Al 1 A12 Al 3 A14 Al 5 A16 A17 A18 Al 9 A20 A21 FOOD COURT FCI FC2 FC3 FC4 i I I STOREFRONT ELEVATION NEUTRAL PIER ELEVATION NEUTRAL PIER PLAN VIEW NEUTRAL PIER AT COLUMN NEUTRAL PIER AT COURTESY PHONE NEUTRAL PIER AT DEPT. STORE NEUTRAL PIER AT CORRIDOR SERVICE CORRIDOR PLAN ELEVATION DETAIL AT ARCH NEUTRAL PIER AT COURT ELLIPSE BULKHEAD SECTION A BULKHEAD SECTION B BULKHEAD SECTION C BULKHEAD SECTION AT CORNICE BULKHEAD SECTION AT COLUMN BULKHEAD SECTION AT BRACKET BULKHEAD SECTION CENTER COURT DEMISING PARTITION AT CORRIDOR TYPICAL DEMISING PARTITION TYPICAL FLOOR TRANSITION DETAILS SERVICE CORRIDOR PLAN VIEW .~.,.. ,,.,. FRONT ELEVATION FOOD COURT FOOD COURT FRONT SECTION FOOD COURT NEUTRAL PIER PLAN FOOD COURT SIGNAGE I I I ! I I I I l“” I 1. I 1. I [ I (’ I i / MECHANICAL Ml M2 M3 M4 M5 M6 M6A M7 M8 M9 Ml O Ml 1 M12 TENANT HVAC SYSTEM TENANT HVAC SYSTEM TENANT HVAC SYSTEM TENANT HVAC SYSTEM TYPICAL ROOF TOP INTERFACE CONDUIT CONNECTOR TENANT AND LANDLORD HVAC CONTRACTOR RESPONSIBILITIES TENANT ELEC. & MECH CONTRACTOR RESPONSIBILITIES ADAPTA CURB ISOMETRIC ADAPTA CURB SHOP PLAN ROOF TOP UNIT SHOP PLAN ROOF TOP UNIT SHOP PLAN ANTENNA ROOF PENETRATION ELECTRICAL El E2 E3 E4 PANEL SCHEDULE ELECTRICAL ROOM FLOOR PLAN ELECTRIC METER RISER DIAGRAM ELECTRICAL ROOM LOCATIONS PLUMBING P1 P2 P3 P4 P5 P6 TENANT PLUMBING RISER PLUMBING RISER AT FOOD COURT TYPICAL BLOCKOUT FLOOR DRAIN PENETRATIONS BELOW SLAB INTERFACE EXHAUST CONNECTION MISC. S1 COLUMN SCHEDULE S2 COLUMN SCHEDULE KI -K3 KIOSK CRITERIA FAI FIRE ALARM SYSTEM FA2 FIRE AIARM SYSTEM t I ,. ! I I I 1 (“ [ [ I 1 I I I i i = — t= L . 12’0’ ILEuTRALcWNEL SEE DETAILA2 1 ONE FOOT(12’) OF OPAQUE MATERIAL $YUOFEFFKMNT IEUEVATKMNI Al I TENAM TO PROWDE 3/4” X3/4” MEW CIUNNEL P~lR10 FROM NEUTR4L NEii7,iPE,Fi—- /—. —— 4== – I II II \ i 1’ I TEN4NTTO PROMOCA 12? DPAOUESURFACE ( NAROTILE ETC... ) AOJACENl ;~~;&CWNEl =-iHORN / STROBE BY cONTRACTORREFER TO ELECTRICAL <jw_x5&nJTAL 1 II =1- PflR W CONTRACT — COURTW TELEPHONESY IANOLORO-INSTALLEOBY CONTRACTOR REFER TO ELECTRICALORAWTNGS _ UNE OF STUO BEYOND % WNTM+ENCE ---1- (TAMPER PROOF) RECEPTACLEBY CONTRACTOR REFERTO ELECTRICJJ. NIEIJTIML PER H4EYATIONS lJk\T(NIK\ mill— A2 I [ ( I i I I I !lh=P’” (3- I S/& GYPSUM BOARD BY Tmwrl II 6 MEW. STUOS FIRE TRC4TE0 WOOO BLOCKINGBY LANOLORO C/L [ / / I ‘1 I I i I I IIMll I UIEfTOIIK\ -/ I 1 1/i? x5/8 MErA!_ CHANNELNEUTRALPEIR BY CONTRACTOR ~ r INIEUURALPm WANIVIEW lYPlcAL A3 .1 1- I --- .-->.&. ““ .—-. .— -- . . .- - ..- ( I I 1 I I I [ RfFER TO STRUCTURM FOR COLUMNS12[ l— o-msuuBomo MO FRAAIINC Al COLUMM sYlmANl . TENANT 1’ {’ [ ~I — I I 4 SPACE n . . C/L / / ( I I ! I I ffllll I UJEMNiK\ \ \ L NEM-IRAL PER PLAN VIEW ATGOLLMN 1 4,4 .—. — -. .—. I ( 1 I I I I 1$~1 I ~iu 1,1 JuNCliON BOX SY LANDLORDRWSR I I 1“ I i ! * ‘ ~TO ‘“””” ‘“”NGs FIRS TRSATEOm BLWKING S7 CONTRACTOR CUSTOMERSfFWCE PHONE OR -.. HORN/SIROBE SY UNULORD; IN%ALEO EY CONTPAL70R-RO_ER TO IISCIRl@L ORAWINCS c/L / / \ L -/ ([ I I I 1. E UJ1310RK\ 1111111 NEUTRAL PER ELEVATIONS atCOURTESYPldCNE/ STROBE A5 \ I I I I I I I 1“ 1“ I I i I I 1“ c T FINISH OY CONTRACTOR SERVICE CORRIDOR VESTIBULE I I —“~’. 1<+-~ : El DEPARTMENT STORE CONCOURSE — ti. . 05/ - EASE LINE I II TENANT SPACE I I LJ REFER TO OETNL l/AJ+l.3 FOR SIMILARNOTES ANO DIMENSIONS UNLESS OTHERWISE NOTEO WEIN atDEPARTMENT SV’CMFE CXMXNJRSE /46 ~[j~&L NEUTRALPm PLAN I I I I I I I I I I 1 I I I / / MALL COMMON AREA 1 I I / i UE$TOIIK\ mflll NEURAL PIER atCmwmm vEm’mME A7 I I I I I I I I [ I I I 1 I I [ I / UJIJTOllK\ fllll 1 15 ? mSPm 2tw/w f 2T-1/1b- { C4Bmfl Wml –s m ExmwJlsm o /-----“ ““f / _D&wl BwN$-m TO SIRWTURAlOR4MNC SPlcs FOCO F1 D CfnRT WFwucx Cxml=mm PLAN A8 I I I I ( 1. 1. I I !. I I= ~’”’” I I I Z75’’” RH ~ MECWANII%CifFUSfRS I [ I I I i {. k-” 1. SiHIS1ffi IWR FUN DETAIL hT 1. I I 1, B IXM?TCLLI= I W.V-# 1 I ~ NEUTRAL ~ lilDTO!lK\ filill PER PLAN atmMFm IELUF%E AI() 1 [ I I I I I I [ I c IL J ( TOPOF SIEEl EFZRTOSIWXU@l 3. a 17.< + a w-d +$ I-J 3/s GwYJu @3Mo LINECf CTXJMNBCfCtiD I I / LEAS LINF I n a 2wY -k? w m- * nlKREcavPs WS. UE I!WLKWAD SE=CTUON B UJWORK\ IIW Al 2 I i ! I I [ Zs2T I I I wALIEf#Ro LEASE \ I I I I LINE \ NI I ! I @JIJKHmD SECT!ONc1 llJ[\TOIIK\ mIIL A13 . I I I I I 1. 1A I I 1. ! [ BW’G=EAD&EGm3Nl i I 11.lEfTi)lK\ ((Ml— at TYPICAL CORNICE A14 4 I I I I I I I I [ i ! I I ! +- ? IWLKEADSECTION WTOflK\ Ml ~ at COLUMN Al 5 I I I I \ I I 1 I i I I I I I 1 I \ UIUTOM MN / .J1 2 IEWWEADSECTION at BRACKET Al 6 -. I 1. I I I I I I I I I I I I I I I I 1 ..— c MAM=K.ADSECTION lUE\lOliK\ m~ll ~ARCHBETWEEN MARKET AXIS AND CENTER COURT A17 I I I I I I i I I i \ SIX omJL / \ / / 7 \ / \ / F A20 fumnotd WALL mm To STRUCTURE W IANOLORD CLASS“A” CEILINGSC31W (HEIGHTvm~s) BY TENANT TEtW4’T TO PROWDE CONTINUOL FIRE STOP K RfOUIRED 6Y LO(X COG+ 3-5/Ef MCTAL STUDS TO UJD&SSR.S~ STRUCTURC REQUIRED TO PROVIOEAND INSTALLA MmL RUNNERTO M41N1AJN PROPERSPACING FORA RATEOINSULATION. TEFIANT MAY BE 5/S TYPE “f GYP.BOARD FULL HEIGHl SY IANOLORD ~ TENANTSPACE I 5/~ lwE “x- GYP.BOARO FULL HEIGHT SY TENANT (St% TO STRUCTURE) KVICE CORRIDOR UTILITY ROOM I i 1/4-X 4’& HIGH TEMPERED H#O&~wOmWAJNSCOT I I 1. I I I TENANT SHALL CONTINUE 1 4HARDSOARO INTO RESESSEk msnws FINISH FLOOR SY TENANT 4“-cr I < ,,3 ~~ . .,,.& Ul[\TOIK\ mill DEMOSONGPARTITION AT SEmmxz CxNFwWDm lKIT.Ea TENANT PENETRATIONSIN &A&&S BE SEALED A18 I I \ / \ / \ II ‘– i ‘ENwT MAY= I I I \ f T ~ ‘1 REWIRSO “O PWMDE AM 0C3TAEJ I UETU RUNNERTO LUNTAJNPROPERSPACINO 1’ “ORA RATEOINSULATION. ---1 I I II PAR’MWN WALLm TO STRUCWRSBY LANOLORO CUSS “A” CEilJNGS6KM (WONT Vkws) m TsNAKT TENAM TO PROMOECONTINUI flRf STOP #S RIOUIREO sv Lo@l. Cm IAETK STWS TO 3-5/~ UNOERSIOEOf SIRUCIURS ~-- ~ TENANT SPACE I I 1. ! \ ‘34 d SEE OETNLAso 1“ I / s/r TYPs “f &P.BoARo ruLINsicHT sYLANoLoRo 5/8 TIPS “r o’?P.Bomo PULL HCK3NTSYTSNANT (SSU TO ST’RVCTURf) SEVICE CORRIDOR UTIIJTY < ROOM I l/4”X &@ HIGH TSUPEREO NAROE04R0wANSCOT SY IAWOLORO TSKANTSNML CD+411NUf. 1/4” l#R~ INTO RESESSEO Esnsw FINISH FLOOR SY TENANT c-c — .....:,+:.,3. ..- ,,. ...’., ...* < . .:* MQIEi TENMT PENSTP.AnONS IN WUL I#JST SE sEAlfo SY Tsw. i lDlEMlmw3 WNRmnlml ~ UJUTOIIK$ ((hillTENANT/TENANTUWOGAIL 1 i -f Al 9 I I I I I I I I I I I I I I I I I NOTE TNS LANDLORD APPROVED OETAILS BELOW ARS STRONGLY RECOMMENDED FOR TYPICAL TENANT FLTRANs$TION .. . . CONDITION% SRAss TEMA2Z0 %%uF r TO OPf w CO+ACRETE I fLR TILE TO CARPET TRANSITION — TILE BY TENANT \ @.8 ASS TCRA2Z0 OIVIDfR STRIP OV YENANT . . fl.AsH PAICNAS RtOOTO PROV 10t ~ GRAOUU WX’[ [ I :20 WXI DOW10 CO~ fLR I THIN SET ECOh SY TENANT L4NCAHE PLOORN LANOLORO TILE TO CONCRETE TRANSITION I TENiNl . . THIN. SET 8E0 J SY ~ANT . . . . . . . . ,.’ . . . ,. ~CONCRETE FLOORSV LANO@RO TILE TO VINYL TILE TRANSITION I U’YIWXL FL(XM% TRWWTKNN DHAL$ UDTOIM rnflu A20 I I I I I I I I [ I n 7 / / LEASELINE / I I I i El CCWON m UOTON\ filll SIERV’KXCnFmm(xl PLANVIEW A21 I /-- TENANT @ I / SIGNAGE rsE’D’TA*LABovE @ \ I ( I I I I ) 1 T-z.l lw > 1-24 Wy —- CWJCR mm niw COUNTER BY TENANT m -TmJMimf T-24 yliim?m?lo WmsfS. WE I I I UJ(310flK\ I IELEVATKMI FCWDCXNRTTENANT FRONT m~u TYPICAL FCI I I I I I I I I TENANTSiGNAGE BEYOMl LOSZ LNE t 1 LEASELNE 1 ~ TLED LOW WALL TEN)J4TCDINTERN.LC. . I =—- ~XTENl W WORD I I I I I / UMT(Mmill FINISH BY TENANT FCKXDCKWIT SUCNHEFRONT SEGTUON FC2 TI ..\ I I I I I I I [ 1“ I I I I 1. I.ANOLORD BON70 KT)L $TW FRMNG GYPSUM EOAQD BY T[NW FOOD GWRT UJENOilK\ m~u NEUTRAL PLAN PEER FC3 I I I I I I I I [ I I I I I I FOOD COURT SIGNAGE ● Food Court signage will consist of individual dimensional backlit (halo effect) channel letters mounted on the Landlord provided sign band. ● Letters will be a minimum of one inch (17 thick w4tha polished brass face and returns. The letter cannot extend further than five inches (57 from the face of the signband. ● Backlit illumination to be provided by neon ranging from 3200K to 3700K. Neon tubes are to be completely concealed wittin the channel letter. ● Ballasts and transformers are to be concealed from public view with access provided from the tenants ceiling. ● Sign shop drawings are to be submitted to the Landlord for approval prior to fabrication. ● Signage is to be controlled by a clock timer and illuminated durfrm the hours that the mall is open. 5. MAX — 1- pOLISHED BRASS FACE b 1 TYPICAL SECTION REVERSE CHANNEL LETTER I I I ( I I I } ADAPIER 1 #%%!%%&l I I 1 I“’ I r ~NSTAUEDUf PaE4PPawEo acHAmcAL AT TEHAHl% ExPEwE. PRAWA~BASE I [ 1 ( ( ( HN -E YoumEDAHm J WTEHAHT L2QITS SYTENAHT %%%!wla BEmHAnsmfun I TMnsmoll 6fTEHAm k DETIECTWAND ASSOCIATEO Wa NTEWACE 10 U SYSm RJR= HVACCONTRACTOR WALLEO EY TENAN= ( OETECTOR MUSTHAVE REMOTE VtSUAL RESET KEY MOUNTEO AT EYE HEIGHT IN TENAHT SALE ~ AT TEHANT EXPEHSE I \ I I ( I WTOM mflu UVPUWL ROOF TOP ONTIEFWAGE M5 ! I I I I \ 1“ 1’ 1“ I 1. I I I T & B CONDUIT CONNECTORS STEEL, NYLON INSUIATED STRAIGHT THE TB-5332 AND TB-5333 CONECTORS CONNECTORS ARE TO BE USED: TB-5332 1!2”USED FOR CONTROL WIRING TB-53333\4” USED FOR POWER WIRING THESE ARE INSTALLED ON THE ADAPTERS USED FOR 3 -121Y2 TON UNITS. ON THE 15 AND181K2 TON UNITS HVAC ADAPTERS ARE NOT USED. CARRIER SUPPLIES KNOCKOUTS ON THESE UNITS FOR THE CONTROL AND POWER WIRING. .1 I I ( I i“ 1“ I [’ .1. I I I { RAL C ~s TENANT’S 1. GENERAL CONTRACTOR Insure the subs follow their S’ RES BILI SHALIJ ouftined responsibilitiesas specified in the subsequent sections of this package. 2. In the event of any discrepancybefweenHVAC equipmentsubmitted for this project and, equipment specified by Tenant’s archiiect, the ‘General Contractor shall notify TENANT AIR CONDITIONING SYSTEMSas soon as possible. 3. As a part of the preliminaryHVAC installation,and prior to approval of final start-up, the following informationshall be providedto TENANT AIR CONDITIONING SYSTEMS or to start-up Cordractoc 3-A. Is poweron in shop? All breakeis, d-nnects 3-B. IS low voltage wiringpulledfrom T%tat locationto unit controlbox? T’efat locking cover, if required,must be mounted. 3-C. All fire stats and time lock or nightset-back T’stats musl be wired. 3-D. Check to make sure that eledhcel penetrationof roof of adapter-frame are made using watertightcouplingsprovided(see M-6). and fuses must be ins4alledand wired When you are raady for start-up contact: EQUIPMENT SUPPLIER TENANT AIR CONDITIONING SYSTEMS 3003 South I-IMov Street Chattanooga,TN 37407 (615) 624-5758 or 1-800-251-3001 DAVE CANTER, PRESIDENT f I I ImN!m EM CTRICAL CONTRACTORS’ RESPONSIBILITIES TENANT’S ELECTRICAL CONTWCTOR SHALU 1. Eledrical pewer to HVAC unit to be atubt%d out through adapter frame or unit a minimum of 6 feet. (See M-8). “NOTE Final connections to unit @ic&ding dismsnect, fuses and associated tirfrvJ) on roof to be made by Tenant% electrical contrador at tenant’s expanse. Tenant !0 coordinate access to roof through Tenant Coordinator. Electrical centrauor will be required to checJr in and OM on the roof. If tenant does not follow check-in procedure and is found on roof, he will be considered liable for any roof damages. 2. Provide and install Horizontal Jundion Box and necessary conduil for control tire. 3. Penetrations through adapter-frame should be made using watertight couplings which are supplied and wewed into the adapter-frame. (See M-8). “NOTE HVAC Unit base pan mual not be penetrated for electrical supply unless an area has been designated for such by the MANUFACTURER. 4. Elecmcal penetrations are not pannitfed through side of curb or mof without prior approval by Landlor#s Tenant Coordinator and work will be performed by Landlord’s designated contrador at tenant’s expense. s. See attached sheets for mrred locations of penelrafiona. (See M-4-5). 6. Run control wire (18 GA18 w“re, color coded) behveen HVAC unil and thermostat. Subbed out through adapter frame or unit a minimum of 6 feet if responsible. “NOTE HVAC Unit will not be started if penetrations are incared. MECHANICAL TENANT’S MECHANICAL ~ IJMTOM Control tire to be TENANT’s CONTRACTORS, CONTWCTOR RESPONSIBILITIES SHAW 1. Insure that ducSsizing and installation are per ASHRAE standatis. 2. Atfati suypply and return dud to Tenant Air supplied HVAC unit base curb (15 thru 25 ton) or witha umnetion which will not permit air IOSS,a~ w’11minimize adapter-frame (3 thru 12 +/2 ton). noise transfer. 3. Provide and install smoke centrol wires and conduit fmm J-box to the rOOflOpunit. (These wires are not to be connected to either moflop unit or pigtailed w“res at J-box). 4, Run control wire (18GA18 wire, color coded) between HVAC unit and thermostat, stubbed oti through adapter frame or unit a minimum of 6 feel (if responsible). control wire to be TENANT% ANIDIMEKX+J. M7 CUNITRACTORS FESPQNSIBILOTOES IMll FORTHE TENA!WHVACSYSTEM ELEGTROWU= ,.- (P 1 I I TEMPORARY+=:2% COVER , A ( l.. I I I BASE CURB ~ ~ , 4 Y16’ ● ~ 1. *- --l ( i--’40 V4” 0.0. Unl [ 7? 0.0. nr !/4’ 14” PA Jr 18M. OS. Pm _ ,7 n V4” l,IJ. u L . -~ 7’ 1; Is 7A’ Smu ADAPT-AWRB SIi=NW PLAN “ UJ[\lOllK\ mill— M9 This page applies to installationof: CARRIER ~~: SIDE VIEW 7 elowtcd pwmlllod & 9*mtr.l10n8 ~ Wo.gh will MM ----’ ~ .- POvubdby 5oTJo~ 3 TON 50TJO0550TJO0650TJO0750TJO0850TJO0950TJ01250TJ014- 4 TON 5 TON 6 TON 7.5 TON 8.5 TON 10 TON 12.5 TON PM Wklng mu-l wwlwrm.d b. h conduit ‘s USE 3/4” 6 1/2” WATERTICNTCONNECI’I (PROVIDED) FOR ELECTRICAL, & COtiTRQ WIBE PRtEI’RATIONS BY TLNANT‘ S ELWPRICAL CONTRACltIR STUBBED On MIMMJ140F6F T. (SEEM-S) UMTONmu b ROOF TOP L9NUT SHOP FwUNl 34,6675S.61Q=TON IVllo I ] I ( 0.0, n v4* Electrlc entrance [Hold duct back 5 3/16) 74 V4C 1.0. — Iw I I I I I I ! ! 1. 15 ton 50TJ016 50TJ020 18.6 ton 50TJ024 20ton 50TJ028 25ton This page applies to installation of Carrier mdels: f * ENul 2224’ l-- w MT-III 12w 0, w 0. t- I L-t_ ~ PLAN VIEW Localton of disconnect ewltch I I ! . ~nockoute provided by manufacturer ? UJE$TOllK\ ffll!ll ROOF T(NPUNOT SHOP PWNI Iq w20 bND25TON Mll ~ S’QT w~ ,.. . . . .. ... . . . .’. .4 . ..’. mm hAnAL w4~ SEN6 ?0 CCUUT -V 8Y TENANT .. ~ALwTENAwsRu6m ?Qr Rfl.lL2Vf lENAN? of ACOUIRINO A SCPCRA7C APPROVAL FOR ALL ROOF PENETRATIONS. 2.1 m@ERws7wN*@N m&P* 3 ) H!OWR ?ANS AM nEaulRco rOR CERTAIN AREAS Oe WE ROOF vERWV WITH LANOLOnO. ALL ROOF WORK TO BE PERFORMED B’f LANDLORD’S ROOFER AT TENANT’S EXPENSE UlOIO!K\ fllll i ROOF W5NJEURATOON DETAIL FOR ROOF AT’ENINA M12 1 I 1“ I [ I I ! i I [ I I i 1. ~ UJUTollK\ mflll I NOTE SCHEDULE TO BE COMPLETED BY TENANT. COMPLETED TENANT SCHEDULE IS SUBJECT TO APPROVAL BY LANDLORD. THIS SCHEDULE MUST APPEAR ON TENANT’S FINAL PLANS. 1 ELECTRICAL PANEL El I I i I Im .— I I I I OT-A I I I I II 1 I 5s1 4wcwo#D I Tenant meter base and disconnect ! i I [. I 1. typical layout . t ! / UMOIK! — fillll 11” I ELECTRICAL RW3M FUXNRIPLAN f E2 ~ I I I 1 I I i I I I I ! \ I I I CONDUIT TO TENANT SPACE WILL GO BELOW SLAB FROM ELECTRIC ROOM TO THE TENANT SPACE Conduit to tenant space. Conductor by tenant Meter by flortda Power Co. Fusas by tenant I I’O-rm m.W I H.&u UIWORK\ mlu TYPICAL IELEYXRIGAL METER ROCIMRISERDUW3AM E3 I I I I I I I I 1: I 1. I I I I i \ 1. I I I electric elecric room #4 . room #3 . . . . . . . :: :! .— 4 THE TP PLAN WHICH CAME WITH THIS PRINT PACKAGE REFERENCES WHICH ROOM SERVICESTHE --b ~..j;...ll electric room #2 . .:o\ 1, ---,: ~... ___ ----+~o __, r---- . ‘AYFERS ( ,: ~, . . . . . ..1 :... !; .;1. electric ,+$ # 1 room ‘L&g “ . . . s .: , N electric room #7 EMGTRUGAL R(XW ILCEATK3NS UJUTOIIK$ mill~ E4 I I I [ I I I 1-1/4” (UNW3 OTNERWS NOED) BY UNDLORD b \ 7 C4PPED VENT STUB BV IANDISRD lEt4#J4T TO Pf?c#~r=wm!& Tu %J..$j$;/~ 3/4” CCXD WAIER PROWDE WAIER MUER TO BE RCAO IN CUBIC fEET I I I ,..E+~> vENlav 4“ CAP W (P.o.c.) I 4“ COMUON W TNRCUW ROOF BY UNDLORO LANDLDRO TENAwr I \ INSIOE TENANT’SLEbSE LINE > ) (ML WORKNNE BY TENbNT < [. Noms I I ML OOUESTICNOT MO CX)ID WAIEt PIPING WTNIN lEUWl sPwEloeE INsulAIEo wrlHl” TNKxflBcRouss ALL SEP.WCE JUXEl lYPE ~ AROUND lNSUIAllOU. ML W41TMYPIPETO=WIR04. ML DDMSllC WATERPIPiNG TO ~ I I i P.v.c. PIPING Is m L ~ lUSING. PElwllm. lE?@NTSIO P~DEWAIER MflER READIN CUMC FEET. 11.LlEN40’S LDCX’EOON MU LSEOONDFLOOR UUSTP~DE A WA~PROf MD4SRAJ4EUNH FINiSN FLOOR ND lURN-UP # ON EKN WALLAT AL PLUMBINGAREAS WITNINSPXE. IF REWIRED w mm~~ LoCA. AulHoRm TENAh-rlsmiwwlm PfmENlofls ( I I I PLWWUNGRHER TENANT UIUTOflK\ mflll (uYFWN PI FOOD COURT TENANTS I I I I I I I I I I I I I P.v.c.WINGIs NOTpmwnso< I I SECONOFLOOR I 1 PLUMENNIG RMER AT FOOD I lJIBTOllK\ mill~ 1- COLDWAIER CA&w/9&l-off OINSRWZ NOTSO) 9vwlDwRo (P.f-w \ h ~1< 10TSi~C04.DWAISR PRoWOsOFoRRsslAURANTTsNAMt. VAM AM CAP BY MmLoRO (P.o.c.) & COMMON VENT TNROUCH “ 2- C4PPSDw SUB sv fANOWRO TSNANTTO PRovlos 7 mo TEE FOR FuTuRs TEw. PROMOS WAIER ktE1’SR10 BE READ IN CUBIC FEET _G;---<wmm_wmm_ 4“ CAP Sf UNDLORO (P.o.c.) \ INSIOE THLAhTS LEASE UNE (ML WORK 00NE UY TSNANT ) ){ + 4“ GRSASS WASIS aY WOLORD AU FOOOCOURT ANO REsTuwMIENANrswmmw MEMBME UNMR MUSIMKAW~ mm FLOORANDTURN-UPc ON w WALLAT ML PLumwo AR!XS WllHIN SPACE l!= RfOUIRCO 6f LOfX AulHcfm, INSML B4XFL0W PR~ I 1’EN4NTsn MEM P2 I 1 I I I I I I [ I 1 i I I I I [ I I .--- w- r ~ ~m .. / UT MOW IM RW91110 Vtlll STACK sow IILNIOLORO.(Sft OtTAtl ?2) ‘ =&53 - ALffRK41[ Loallom fm Clfcr. n.n.n. RILlff VUVt OWN HUSTBC PIPIO 10 fl~ 08Aln. FWSIOf OWN WI UNOtRKOTwATER HSA7[XAKO01611 PANTO F103$ OAAIM. ~~ ~, .“,,. . ..9s.. .. ---- —ANO TdNKDRAI1VAIVfS PIPSO 10 uITHIN 6- OF ltiwl, s floos own. “’:l:;:%N}wlT TENANT TO PROVIOEcOMPACTEDOACKFrLL v. [ I I I I I I I I I 1 I I I I ! I I UIUTOllK\ mllll 1 CtmJAiClu CR OwRfw nEmHTIW6ETUKIJT E~llNG FLKHNC CtUM (BY KN4NT) P&CR ORNN(BY lENANl) uD@RANEWATER-FWXIING CUTmsnw w c.c$if tlaf THRUExISTNG w FROKC RECISSFOR As siow ‘M AMIGi7(aJTIN F1.U (EY W* (SJPPcRlt-RAUNG BYmANl) & FLOORPENETRATIONS !FL.cm DRAM P4 $.. a I I I +iizc4--::; I I I I I SEE TENANT PLAN FORSRE ~ TENAh7 ELECTNIC AND WMPNONE CONDWS 70 STUS UP *AR COLUMN OR PERMETER EXIT C~R WALL 26~ TSNANT SPACEANO CAPPEO AS@E FLOOR SLAS AND SECURED TO WALL COLUMN WITH 2 NCi.S STRAP. CAP IS PW ANO CEMENTED TO AVOIOPROSLEM WITN DESRIS?4S!0S PIPS. P.V.C. MUST SE CUT SELOW TNS FU41SNSLAS AND METAL CONOIAT ~ TO * L&=, ND P.V.C ASWE SLAs ., ;., ,,:: / +==!! I . . ::.......... I J .. . ~:;;” ~= . SAND BED — SV LANDLORO I I I I I \TENANT t- 4“ CAST BON SANITARYLD4E SY LANDL~ : , I AU CONTINUATION DP SAMTARY PIPINI SV TENANT MUST E CAST 2?DN SAN. STuBOUT FOR FUTURE cJO~N~T~N I [ i I UMOMm[u EELCIW EuJ3LJ’mmY ONTERFACYE P5 [ J 1“ I I I I 1. I I 1 I I I I I I ~—. I _J h- %%fl%%hD ------$~ji;:iiii:---TOILET EXHAUST FAN BY TF34ANT: 2CFWSQ. fl. OF TOILET ROOM ARCA SO ff+ VHICK’KR IS GREATER FOR W3WWWUWWEU EXWWSU DUCT [ - lUE!TOilK\ mllll CONNECTION P6 I I I i I I I I I I I I I I [ ! I (XXJJMN W+EWLE I wow I mw SI I I I I I I I I [ [ 1. I I I I I II I }! 1[ 11 I I I I I I I I 1 I I I I I I I I I I I I I I I 1. I I I I I I I I I 1 I I I t 10 10 I ~nl ~n 10 I 1 t , , 71 ! I I I I I I I=EPPPl I I I I I m I 31 I w I 1= I I t , t . .- 7 lr -pa 8 m- pip . -----19 Wsml 20 WSX40 9 WSX31 10 W&al 11 WSX31 21 lW p4p0 22 WSX31 23 T.S. MxlW 12 wml 24 m me I ii Wsm51 32 T.S. Sx8xW” ?3 T.S. SxSxlG? 34 wax4a 3s 10’ pip [ i I UJE$TOIIK$ ffllll ~ I cxMMmNfMMmuLE I S2 I I I I I I [ 1. [ ( 1. I I I I I [ 1. I .. “w t .— - --ml WI*- \ - UAsflss ~m-gg Sllsusl I I I PERMANENT KIOSK CRITERIA [ INTRODUCTION I This design criteria has been formulated to provide guidanos to the Tenant and the Tenant’s design team in developing a viable kiosk design. I The Landlord reserves the right to disapprove any kiosk design that do not comply with the oritefia established in this manual. I DESCRIPTION OF LANDLORD’S WORK 1 FLOOR I Landlord shall provide a finished mail floor in and surrounding the kiosk area. The finished floor shall be consistent in elevation and materials with the surrounding mall common area. No penetrations of the floor material is ( permitted. The kiosk construction shall not damage or remove the Landlords floor structure 1. or finish materials. UTILITIES I The Landlord shall provide a duplex receptacle floor box with a telephone outlet. Each floor box will have a 20 amp service. Any upgrade to this service is at I Tenant expense. Kiosk locations in the food court will also be provided with sewer and water. I DESCRIPTION OF TENANT WORK [ These design requirements represent the standards for the design of the tenants i leased premises. I KIOSK CWTERL4 I UMOM mllll K2 , I I I I ! GENERAL DESIGN CRITERIA ● ● ● ● I I I 1. ● ● Each permanent sided kiosk shall be cmstructed kiosk will OCCUPY a 10x15(150 by Tenant square at Tenant’s foot) area. A four expense. The kiosk must fully utilize, but not exceed, the floor area allocated. All counters are designed and provided by tha Tenant The kiosk structure will be limited to counter units with no overhead obstructions that inhibit the visibility of any inline mall tenant. See detail KI The counter shall be designed in accordance with The Americans with Disabilities Act (ADA) and the Florida Accessibilities Code. All locking devices must be flush mounted. The Tenant shall install lighting within the casework and on overhead light tracks. Tracks must not block the sightlinessto the inlina tenants and are subject to Landlord approval. I ● The kiosk must have a dark ceramic tile base. ● All glass within 18 of the floor must be temperad. If permitted by code, all other glass may be safety plate. I I [ I I I I KIOSK lUEW)lK\ mill — CWTERIA K3 I I I 1. I I ! I I 1. I I I LANDLORD AND TENANT CONTRACTOR FMF AIJW&RE sP!f)rwBILulEs___ GENER13L NIITES 1 ALL T[NANT H. V.A.C. UNITS TO HAVC A DUCT DETECTOR ON SUPPLY DUCTS, UNITS GREATER THAN 1S,000 C.F.M. SHALL HAVE DETECTORS ON BOTH SUPPLY AND RETURN nllcrs. 2 3 C. 4 5 6 INSTALLATION OF CONTROL MODULE(S) AND SPEAKER/STROBE(S> D. FINAL CONNECTIONS, PROGRAMING AND START-lJP TENANT’S CONTRACTOR SHALL BE RESPONSIBLE FOR H.V.A.C, UNIT SHUTDOWN EQUIPMENT SHALL BE LOCATED IN TENANT’S CEILING SPACE AND SHALL BE ACCESSIBLE. ANY ACCESS PANELS REQUIRED ARE THE RESPONSIBILITY OF THE TENANT. FOEID TENANTS WITH COOKING HOOD FIRE SUPPRESSION SYSTEM WILL BE REQUIRED TO HAVE THESE SYSTEMS MONITORED BY THE FIRE ALARM I I 1. / I I CONTACT MERIT ELECTRIC AT 1-800-539-3900 TO ORDER EQUIPMENT FIFEALARMSN’STEMS FAI I I [ EIREALARM WIRING DIAGRAM CONDUIT TO ADJA ENT I I I ,V > I I I L I I 1“ I I I ❑ I I FIRE ALARM INSTALLATION BY I LANDLORD’S CONTRACTOR, MERIT I ELECTRIC, AT TENANT EXPENSE I FOREAQARMW’STEMS 1. FA2 U.Mlolw milll ~ I “NANTSPA+ JUNCTION BOX IN REAR OF TENANT SPACE BY MALL CONTRACTOR r \ SUPPLY [ AIR DUCT ,l— --l TO ADDITIONAL /f_(lF REQUIRED) 3/4’ L CONDUIT WITH PULL DUCT DETECTORS TRING BY TENANT CONTRACTOR TO ADDITIONAL AS REQUIRED SPfAKER/STROBE ;::~;j::; HOOD SYSTEt4 ___@=/I? TENANT FIRE GENERAL ALARM RISER NOTES CONTROL MODULE FOR H.V.A.C. UNIT SHUTDOWN NOTIFIER CMX-1 a FIRE ALARM SPEAKER/STROBE WHEELLOCK E7025-LSM-24-W UNIT & CONNECTION TO HOOD SUPPRESSION SYSTEM (TENANTS WITH ANSUL SYSTEMS ONLY> I