Installation

Transcription

Installation
HydroZone Installation Manual
Hydronic Comfort Zoning System
4, 8, and 12 Zone Capacity
Installation Information
Thermostat Installation
Electrical
Startup Procedures
Wiring Schematics
IM1550EW 11/10
HYDROZONE INSTALLATION MANUAL
Table of Contents
Model Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
General Installation Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Electrical Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Wiring Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-12
Thermostat Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Controller Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-20
System Startup and Checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Parts Lists . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
HYDROZONE INSTALLATION MANUAL
Model Nomenclature
1-2
HZ
3-4
04
5
A
6
9
7
S
8
N
Model Type
HZ = HydroZone Control Panel
Future
N = None
Number of Zones
04 = 4 Zone
08 = 8 Zone
12 = 12 Zone
Controller
N = Standard with Controller
E = 12 Zone Expansion - No Controller
Zone Output Voltage
A = 24 VAC (Zone Valves)
9 = 115 VAC (Zone Pumps)
Vintage
A = Current
Zone
Thermostat
Zone
Thermostat
HydroZone Controller
Outdoor Air
Sensor
Backup
Heat - W
Cal
ls -
Pum
Load
Plumbing
Y1 a
p/V
alv
es
HP
Zo
ne
nd
Accessory
Box
Y2
Source
Plumbing
Radiant Floor
Tank
Sensor
GeoTank
Envision Air Handler
4
HYDROZONE INSTALLATION MANUAL
General Installation Information
Safety Considerations
HydroZone Control Panel
Installing and servicing heating and air conditioning
equipment can be hazardous due to system electrical
components. Only trained and qualified service personnel
should install, repair or service heating and air conditioning
equipment. When working on equipment, observe
precautions in the literature, tags and labels attached to the
unit, and other safety precautions that may apply.
Locate the HydroZone panel in an indoor area that
has enough space for service personnel to perform
maintenance or repair. Provide sufficient room to make
electrical connection(s). The HydroZone is not approved for
outdoor installation and, therefore, must be installed inside
the structure being conditioned. Do not locate the control
panel in areas where ambient conditions are not maintained
within 45°F to 95°F and are greater than 75% relative
humidity. The HydroZone control panel should be mounted
on or as close to the unit as possible by using the sheet
metal screws provided. See the HydroZone Control Panel
Mounting illustration for mounting hole locations.
Follow all safety codes. Wear safety glasses and work
gloves.
WARNING: Before performing service or
maintenance operations on the system, turn
off main power switches to the indoor unit.
Turn off accessory heater power switch if
applicable. Electrical shock could cause
serious personal injury.
Note: Use longer screws (not provided) to penetrate
through drywall into stud.
Delivery Information
When the equipment is received, all items should be
carefully checked against the bill of lading to be sure
all crates and cartons have been received. Examine the
contents for shipping damage, removing them from the
cartons if necessary. If any damage is noted, the carrier
should make the proper notation on the delivery receipt,
acknowledging the damage.
Installation and Design Steps
1. Decide which areas of a home or office will comprise
each of the individual zones. A maximum of twelve
individual zones can be chosen. If more zones are
necessary, a 12 zone expansion is available.
2. Calculate loads using software or other recognized
methodology.
3. Use software to determine the equipment size and
performance based on the total heating and cooling
demands of the building, not the sum of the individual
zone demands.
4. Find the peak heating and cooling demands and the
peak GPM or CFM required for each of the zones.
5. Lay out and size the radiant tubing or supply air
ductwork. Care should be taken to avoid under sizing
either the buffer tank, radiant tubing and spacing,
supply air systems, return air systems, or diffusers.
6. Decide where to locate the thermostats.
7. Install the unit, storage tank and the HydroZone system.
5
HYDROZONE INSTALLATION MANUAL
Dimensional Data
HZ04, HZ08, and HZ12 Dimensions
21.00
1.80
3.09
3.78
4.27
8.00
7.61
16.00
6.75
15.25
12.75
10.63
21.25
HZ00 Dimensions
7.50
3.33
4.51
6.50
7.68
6.71
3.79
3.87
7.68
6
HYDROZONE INSTALLATION MANUAL
4 Zone 24V Valve (1 transformer included)
OAT Sensor
4 Zone 115V Pump
GeoTank Sensor
Electrical Ratings
HCZ04AA*N
Voltage:
115
Phase:
1
Phase:
1
Frequency:
60Hz
Frequency:
60Hz
Total FLA:
9.3
Total FLA:
0.65
Maximum Fuse Size:
15 - HACR breaker or time delay fuse
Maximum Fuse Size:
3
Comments:
Maximum current per pump must not
exceed 2.15 amps.
Comments:
Maximum VA load per valve must not
exceed 10 VA or 0.42 amps at 24VAC.
Com
Com
Clg
Com
e
tu r
Fu
OAT
OAT
Model:
115
Tank
HZ04A9*N
Voltage:
PB3
Tank
Model:
Brown (
Brown (
8 Zone 24V Valve (2 transformers included)
8 Zone 115V Pump
Yellow (
Yellow (
115
Phase:
1
Phase:
1
Frequency:
60Hz
Frequency:
60Hz
Total FLA:
17.9
Total FLA:
1.3
Maximum Fuse Size:
30 - HACR breaker or time delay fuse
Maximum Fuse Size:
6
Comments:
Maximum current per pump must not
exceed 2.15 amps.
Comments:
Black/White
Zone Stats 1-4
R
PB5
Note 3
C
Voltage:
C
115
Z4
Voltage:
Z3
HZ08AA*N
Z2
Model:
Z1
HZ08A9*N
R
Model:
Green/Yellow (GND)
Maximum VA load per valve must not
exceed 10 VA or 0.42 amps at 24VAC.
Black/White (26)
Yellow
Yel (Z1) Grn (Z3) Blk (C1)
Blue (Z2) Pink (Z4)
12 Zone 24V Valve (2 transformers included)
12 Zone 115V Pump
Model:
Yellow (25)
Model:
HZ12A9*N
ZB1
HZ12AA*N
P2
P1
4 3
2 1
4 3 2 1 C
C
115
Voltage:
115
Phase:
1
Phase:
1
Frequency:
60Hz
Frequency:
60Hz
Total FLA:
26.5
Total FLA:
1.3
Maximum Fuse Size:
45 - HACR breaker or time delay fuse
Maximum Fuse Size:
6
Comments:
Maximum current per pump must not
exceed 2.15 amps.
Comments:
Maximum VA load per
valve
must
not
Black
(9)
Black (10
)
Black
(8)
exceed 10 VA or 0.42
amps
at 24VAC.
White (L1)
White (L1) White (L1)
EA Seri es PCB
Voltage:
ER4
ER3
NO
NO
ER2
ER1
NO
NO
Black (6)
Bl
Black
Black
Black
Black (7)
White (5)
W
Transformer2
Yellow
Black
PB1
L1
G
WARNING: All wiring must comply with local and
state codes. Disconnect the power supply before
beginning to wire to prevent electrical shock or
equipment damage.
7
PB4
L2
L1
L2
24VAC
L2
115/60/1
L1
24V
Hydrozone
Power
L2
Zone Valves 1-4
Black
Main Power Block
White
All wiring must comply with local and state codes.
Disconnect the power supply before beginning to wire to
prevent electrical shock or equipment damage. All wiring
should be run back to the control panel. Keep wires a
minimum of 12 inches from any high voltage lines. See the
Wiring Schematics section for additional information.
L1
White
115V
Wiring Zone Valves or Pumps
L2
Transformer1
G
L1
115V
24V
Electrical Wiring
G
Black/White
Note 2
HYDROZONE INSTALLATION MANUAL
Wiring Schematics
OAT Sensor
Green (C4)
HZ
Com
Com
Com
Clg
OAT
OAT
Tank
RB
e
tu r
Fu
A+
B+
GND
OAT
TS
GND
Brown (18)
Brown (17)
Yellow (16)
Yellow (15)
Gray (C3)
C4
C3
C2
C1
V
P
O/B
C
R
HydroZone
Controller
C4 C3 C2 C1 P O C R
PB3
Tank
GeoTank Sensor
12 Zone 24VAC Valves
Blue (C2)
Yellow (C1)
Pink (P)
P1
Orange (O/B)
Black (C)
Red (R)
R
C
O
Note 3
Zone Stats 1-4
Zone Stats 5-8
P
Zone Stats 9-12
C1
C2
C3
C
C
Z12
Z11
Z10
R
Z9
R
PB9
C
C
Z8
Z7
Z6
R
Z5
R
PB7
C
C
Z4
Z3
Z2
R
Z1
R
PB5
C4
P2
Black/White (14)
Relay
Green/Yellow (GND)
Black/White
Black/White (26)
Black/White (34)
Yellow
Yellow (25)
Yellow (33)
Yel (Z1) Grn (Z3) Blk (C1)
Blue (Z2) Pink (Z4)
Yellow (13)
Black/White (12)
Yel (Z9) Grn (Z11) Blk (C3)
Blue (Z10) Pink (Z12 )
Yel (Z5 ) Grn (Z7) Blk (C2)
Blue (Z6) Pink (Z8)
Yellow (11)
ZB1
P2
ZB2
P1
4 3
2 1
NO
ER2
ER1
NO
NO
Black (6)
2 1
ER4
4 3 2 1 C
C
ER3
NO
ER2
ER1
NO
NO
NO
Black (20)
Black
Black
Black (10 )
White (L1)
Black(9)
Black (8)
P1
4 3
2 1
ER4
ER3
NO
NO
4 3 2 1 C
C
ER2
ER1
NO
NO
Note 1
Black (28)
Black
White (L1)
P2
EA Seri es PCB
ER3
NO
ZB3
P1
4 3
EA Series PCB
EA Seri es PCB
ER4
4 3 2 1 C
C
P2
Black
Black (7)
Black
Black (24)
White (L1)
White (L1)
Black
Black (23)
White (L1)
Black (22)
Black
Black
Black (32)
Black (21)
White (L1)
White (L1)
Black (31)
White (L1)
Black (30)
Black (29)
White (L1)
Optional con
used and hea
White (5)
White (19)
Relay Bo
Black
White (27)
Transformer2
Yellow
Black
L2
Zone Valves 9-12
24VAC
PB8
L1
L2
L1
PB1
L1
8
L2
L2
G
L1
24VAC
G
L2
24VAC
Note 2
G
L1
L2
Zone Valves 5-8
PB6
L1
L2
L1
L2
Note 2
L1
G
L2
G
L1
L2
PB4
L1
L2
L1
L2
Zone Valves 1-4
Black
115V
24V
115/60/1
L1
White
White
Hydrozone
Power
G
L2
Transformer1
G
L1
115V
24V
Black/White
Note 2
1. If an auxiliary
connect to P6
shown above
2. Wire zone va
PB4, PB6, an
3. Wire zone the
and PB9
4. Use HZAB or
HYDROZONE INSTALLATION MANUAL
Wiring Schematics cont.
12 Zone 24VAC Valves cont.
NSW/NDW
Synergy3D option
O
RB
O-C2
Y
Synergy 3D
C4 C3 C2 C1 P O C R
Relay C2
P5-4
Relay C2
P5-11
R
Y- C2
R- C2
Compressor 1
O- C1
O
Relay C1
R
P5-4
Y-C1
P1
Y
Synergy 3D
Relay C1
P5-11
R-C1
C
P5
Compressor 4
P
O
R
O-C4
C
Relay C4
P5-4
Relay C4
P5-11
O
Note1
P
Y
Synergy 3D
R
Y-C4
R-C4
C1
C2
O- C3
C3
Relay C3
C4
Relay C3
P2
ack/White (14)
Relay Board P6
Compressor 3
O
Y
Synergy 3D
Y-C3
P5-4
R-C3
P5-11
R
Yellow (13)
Note 4
PB2
C
Black/White (12)
Tank Pump
NO
R
Yellow (11)
3 2 1 C
115 or 230/60/1
Note 4
ER1
NO
Relay Board
NO
Water Heater
Note 1
O -C4
230/60/1
Relay 42
ck
Relay 41
Legend
Y-C4
R-C4
Factory Low voltage wiring
Factory Line voltage wiring
Field low voltage wiring
Field line voltage wiring
Optional block
DC Voltage PCB traces
Junction
Quick connect terminal
Optional connection if auxiliary heat is
used and heat pump 4 is not connected
PB8
Note 2
Notes
1. If an auxiliary water heater is used,
connect to P6 on the relay board as
shown above.
2. Wire zone valves or zone pumps to
PB4, PB6, and PB8
3. Wire zone thermostats to PB5, PB7,
and PB9
4. Use HZAB or field supplied contactor
L1
Thermistor
Light emitting diode - Green
Relay coil
T
G
P
2
3
1
Polarized connector
Wire nut
Field wire lug
Ground
Relay Contacts N.O., N.C.
Fuse
HZ - Hydrozone Control
RB - Relay Board
PB - Power Block
ZB - Zone Relay Board
HZAB - HydroZone Accessory Box
97P806-04
2/11/10
Thermostat Wiring
9
R
C
Y
R
C
Z1
PB5, 7, & 9
P6
Zone Thermostat
Black (29)
2
Compressor 2
HYDROZONE INSTALLATION MANUAL
Wiring Schematics cont.
HZ
Com
Com
Com
OAT Sensor
Clg
Tank
GeoTank Sensor
Tank
OAT
RB
e
tu r
Fu
Green (C4)
A+
B+
GND
OAT
TS
GND
Brown (18)
Brown (17)
Yellow (16)
Yellow (15)
C4 C3 C2 C1 P O C R
PB3
OAT
12 Zone 115V Pumps
Gray (C3)
C4
C3
C2
C1
V
P
O/B
C
R
HydroZone
Controller
Blue (C2)
Yellow (C1)
Pink (P)
Orange (O/B)
Black (C)
Red (R)
R
C
Note 3
Zone Stats 5-8
Zone Stats 1-4
Zone Stats 9-12
O
P
C1
C2
C3
C4
Rela
C
C
Z12
Z11
R
R
Z9
PB9
Black/White (14)
C
C
Z8
Z7
Z6
R
R
C
C
Z4
Z3
Z2
R
Z1
R
Z5
PB7
PB5
Z10
Yellow (13)
Green /Yellow (GND)
Black/White
Black/White (26)
Black/White (34)
Yellow
Yellow (25)
Yellow (33)
Yel (Z1) Grn (Z3) Blk (C1)
Blue (Z2) Pink (Z4)
Yel (Z5) Grn (Z7) Blk (C2)
Blue (Z6) Pink (Z8)
Black/White (12)
Yel (Z9)
Grn (Z11) Blk (C3)
Blue
Pink (Z12)
(Z10)
Yellow (11)
ZB1
P2
ZB2
P1
4 3
2 1
NO
ER2
ER1
NO
NO
2 1
ER4
4 3 2 1 C
C
ER3
NO
ER2
NO
NO
ER1
NO
ZB3
P2
P1
4 3
2 1
ER4
EA Series PCB
ER3
NO
P1
4 3
EA Series PCB
EA Series PCB
ER4
4 3 2 1 C
C
P2
4 3 2 1 C
C
ER3
NO
ER2
ER1
NO
NO
NO
Note 1
Black
Black
Black (10)
Black (6)
White (L1)
Black
Black (9)
White (L1)
Black (8)
Black
Black(7)
Black (24)
Black (20)
White (L1)
White (L1)
PB4
Transformer
Black
Black
Black
Black (23)
White (L1)
Black (22)
Black (32)
Black (21)
Black (28)
White (L1)
White (L1)
PB6
White (19)
G
G
Black(31)
White (L1)
Black (30)
Black (29)
White (L1)
PB8
White (27)
O
u
Black
G
10
L2
115/60/1
L1
L2
PB1
L1
Zone Pumps 5-8
L1
115/60/1
Note 2
L2
Hydrozone
Power
L2
115/60/1
L1
Zone Pumps 1-4
G
L2
Note 2
G
L1
L2
L1
L2
L1
L2
L1
L2
G
L1
L2
L1
L2
L1
L2
L1
L2
G
L1
White
R
Black
115V
24V
White (5)
Black
Note 2
Zone Pumps 9-12
115/60/1
HYDROZONE INSTALLATION MANUAL
Wiring Schematics cont.
12 Zone 115V Pumps cont.
To Heat Pumps
NSW/NDW
Synergy3D option
Compressor 2
O
RB
C4 C3 C2 C1 P O C R
Green (C4)
Gray (C3)
Blue (C2)
O-C2
Y
Synergy 3D
Relay C2
P5-4
Relay C2
P5-11
R
Y- C2
R- C2
Compressor 1
O- C1
O
Relay C1
R
P5-4
Y-C1
P1
Y
Synergy 3D
Relay C1
P5- 11
R-C1
C
P5
2
O
R
O-C4
C
Relay C4
P5-4
O
Relay C4
P5-11
Note1
P
Y
Synergy 3D
R
Y-C4
C1
R-C4
C2
O- C3
C3
Relay C3
Compressor 3
O
P2
Relay Board P6
Y
Synergy 3D
Relay C3
C4
C
Compressor 4
P
Y-C3
P5-4
R-C3
P5-11
R
Note 4
Black/White (12)
Yellow (11)
Tank Pump
NO
P1
115 or 230/60/1
R
C
4 3 2 1 C
ER1
NO
Water Heater
Note 1
Relay Board
O -C4
230/60/1
Relay 42
Black
k (30)
Note 4
PB2
NO
NO
ER2
Relay 41
Black (29)
Y-C4
Legend
R- C4
Factory Low voltage wiring
Factory Line voltage wiring
Field low voltage wiring
Field line voltage wiring
Optional block
DC Voltage PCB traces
Junction
Quick connect terminal
L2
L1
Note 2
9-12
Notes
1. If an auxiliary water heater is used,
connect to P6 on the relay board as
shown above.
2. Wire zone valves or zone pumps to
PB4, PB6, and PB8
3. Wire zone thermostats to PB5, PB7,
and PB9
4. Use HZAB or field supplied contactor
L1
Thermistor
Light emitting diode - Green
Relay coil
T
G
P
2
3
1
Polarized connector
Wire nut
Field wire lug
Ground
Relay Contacts N.O., N.C.
Fuse
HZ - Hydrozone Control
RB - Relay Board
PB - Power Block
ZB - Zone Relay Board
97P806-07
10/22/10
Thermostat Wiring
11
R
C
Y
R
C
Z1
PB5, 7, & 9
Optional connection if auxiliary heat is
used and heat pump4 is not connected
Zone Thermostat
P6
HYDROZONE INSTALLATION MANUAL
Wiring Schematics cont.
12 Zone 24VAC Valves
Zone Stats 5-8
C
Z10
R
R
C
C
Z8
Z7
Z6
R
Z5
R
C
C
Z4
Z3
Z2
R
Z1
R
PB9
C
PB7
PB5
Z12
Zone Stats 9-12
Z11
Zone Stats 1-4
Z9
Note 2
Green /Yellow (GND)
Black/White (26)
Black/White (34)
Yellow
Yellow (25)
Yellow (33)
Yel (Z1) Grn (Z3) Blk (C1)
Blue (Z2) Pink (Z4)
Yel (Z5) Grn (Z7) Blk (C2)
Blue (Z6) Pink (Z8)
Black/White (12)
Yel (Z9) Grn (Z11) Blk (C3)
Blue (Z10) Pink (Z12)
C
Black/White
P2
ZB2
P1
4 3
4 3 2 1 C
2 1 C
NO
ER2
ER1
NO
NO
Black (6)
2
4 3 2 1 C
1 C
ER4
ER3
NO
NO
ER2
NO
ER1
NO
Black
Black (10)
White (L1)
Black
Black (9)
White (L1)
Black (8)
PB2
P1
4 3
4 3 2 1 C
2 1 C
ER4
ER3
NO
NO
ER2
ER1
NO
NO
Black (28)
Black (20)
Black
P2
EA Series PCB
ER3
NO
ZB3
P1
4 3
EA Series PCB
EA Series PCB
ER4
P2
R
Yellow (11)
ZB1
Black
Black (7)
Black
Black (24)
White (L1)
White (L1)
Black
Black(23)
White (L1)
Black (22)
Black
Black (21)
White (L1)
White (L1)
PB6
PB4
Black
Black (32)
Black
Black(31)
White (L1)
Black (30)
Black (29)
White (L1)
PB8
White (5)
White (19)
L2
L1
L2
L1
L2
L1
24VAC
G
L2
Zone Valves 5-8
G
L1
L2
L1
L2
L1
L2
Note 1
Note 1
Zone Valves 9-12
24VAC
Black
White
Black
115V
24V
Factory Low voltage wiring
Factory Line voltage wiring
Field low voltage wiring
Field line voltage wiring
Optional block
DC Voltage PCB traces
Junction
Quick connect terminal
White
Notes
L1
115/60/1
L2
Hydrozone
Power
PB1
G
1. Wire 24VAC zone valves to PB4, PB6,
and PB8.
2. Wire zone thermostats to PB5, PB7,
and PB9.
L1
P
2
3
1
Polarized connector
Wire nut
Field wire lug
Ground
Relay Contacts N.O., N.C.
Fuse
HZ - Hydrozone Control
RB - Relay Board
PB - Power Block
ZB - Zone Relay Board
97P806-08
10/22/10
Thermostat Wiring
Zone Thermostat
Black/White
Thermistor
Light emitting diode - Green
Relay coil
T
G
12
R
C
Y
R
C
Z1
PB5, 7, & 9
Transformer1
Legend
115V
24V
Black/White
Yellow
G
L1
24VAC
G
L2
Zone Valves 1-4
Transformer2
Yellow
Note 1
L1
L2
L1
L2
L1
L2
L1
L2
G
L1
G
White (27)
HYDROZONE INSTALLATION MANUAL
Thermostat Installation
Locating the Thermostats
not place a thermostat on an outside wall. Follow the same
guidelines that apply with standard thermostat installation.
If two or more rooms are on a single zone, locate the
thermostat in a hallway or area where it can sense the
return air from all rooms.
The thermostats must be located in the room or zone that
each controls. Locate a thermostat about five feet above
the floor. Do not locate a thermostat where it may be
exposed to direct sunlight, drafts or direct supply air. Do
Four Zone Thermostat Location
Utility
Room
Bath
Dining
Kitchen
Bath
Master
Bedroom
Family
Room
Living Room
Bedroom
Bedroom
Zone 1 Main Living
Zone 2 Bedrooms
Zone 3 Master Suite
Not Zone 4 Basement
Shown
HydroZone Thermostat
Mounting and Wiring the Thermostat
Position the thermostat subbase against the wall so that
it is level and the thermostat wires protrude through the
middle of the subbase. Mark the position of the subbase
mounting holes and drill holes with a 3/16-inch bit. Install
supplied anchors and secure base to the wall. Thermostat
wire must be eight-conductor 18 AWG. Strip the wires
back 1/4 inch (longer strip lengths may cause shorts) and
insert the thermostat wires into the HydroZone connector
as shown to right. Tighten the screws to ensure tight
connections. The thermostat has the same type connectors,
requiring the same wiring. Caulk the hole in the wall where
the wires enter the thermostat.
Note: See the instructions enclosed in the thermostat for
detailed installation and operation information.
13
HYDROZONE INSTALLATION MANUAL
Controller Operation
The WaterFurnace HydroZone controller is a part of the
hydronic heat pump system. The WaterFurnace part
number for this product is HZC. This controller is a human
interface and water tank control device. The controller
displays and regulates the water tank temperature as
configured. A 2-1/2 in. x 2-1/2 in. LCD display and five push
button keys serve as the human interface. The five keys
are: the up and down keys (▲ and ▼) for changing the
selection or temperature, the right and left keys (◄ and ►)
for changing the selection or mode, and the enter key (■) is
for accepting and/or saving the selection.
Figure 1
Controller Operation
Adjusting Temperature
10. The date and time are now set. You can return to the
Main Menu by pressing the left arrow key to return to
the previous menu.
1.
To select a MODE, use the keypad arrows to scroll to
MODE. Then, press the enter button on the key pad to
enter the operating mode menu.
2. Select the desired mode by scrolling up or down, with
the arrows. Then press the enter button on the keypad
to enter into that mode.
3. You are now returned to the Main Menu and Figure 1 is
a similar view. NOTE: Outdoor air temperature is only
displayed if an outdoor air sensor is installed.
4. To increase the temperature set point, use the arrow up
button. To decrease the set point, use the arrow down
button. Five (5) seconds after the last button push, the
new setpoint is saved. Outdoor reset control is done in
the installer’s setup and cannot be adjusted from the
front screen.
Changing Modes
1. From the main screen select MODE.
2. Select the operating mode you need and press the
enter button ■.
NOTE: If selecting EMERGENCY HEAT, the backlight
color will change from blue to red indicating that
auxiliary heat is operating instead of the heat pump
compressor. Auxiliary/emergency heat is significantly
more expensive to operate than the heat pump
compressor, and should not be selected unless the
heat pump compressor is not operational.
Fahrenheit or Celsius
Setting Date And Time
1.
2.
3.
4.
5.
6.
7.
8.
9.
1.
From the Main Menu, scroll to MENU and press the
enter button ■ on the keypad.
2. Select FAHRENHEIT/CELSIUS.
3. Select which scale you prefer.
From the Main Menu, scroll to MENU and press the
enter button ■ on the keypad.
Select SET DATE.
SET MONTH by using the up and down arrows ▲▼.
Then press the enter button ■ on the keypad to save the
month.
SET DAY by using the up and down arrows ▲▼. Then
press the enter button ■ on the keypad to save the day.
SET YEAR by using the up and down arrows ▲▼. Then
press the enter button ■ on the keypad to save the
year.
Select SET TIME.
SET HOUR by using the up and down arrows ▲▼. Then
press the enter ■ button on the keypad to save the
hour.
SET MINUTE by using the up and down arrows ▲▼.
Then press the enter button ■ on the keypad to save
the minute.
If your area observes daylight savings time, select
AUTO DAYLIGHT SAVING; scroll to ON, then press the
enter button ■ to save. You will be returned to the SET
DATE AND TIME menu. Scroll to SET DATE AND TIME
and press the enter button ■ on the keypad.
Backlight on Time
This controller has a two color backlight feature. Anytime
a button is pressed, the blue backlight stays on for a
certain amount of time. A red backlight is visible if you
are selecting Emergency Heat mode. You can adjust the
amount of time the backlight stays on in the menu options.
1. From the Main Menu, scroll to MENU and press the
center button ■ on the keypad.
2. You can change the backlight on time by using the
up and down arrows ▲▼. BACKLIGHTING ON (all the
time), 15 sec., 30 sec., and NO BACKLIGHTING are
your choices. Press the enter ■ button to save the new
backlight on time.
14
HYDROZONE INSTALLATION MANUAL
Controller Operation cont.
Advanced Settings
Installer Information and Advanced
Features
Security Lockout
Safety Considerations
This controller has the option to set
security features to lockout everything
but the adjustment of the temperature
or a total keypad lockout.
1. From the Main Menu, scroll to
MENU and press the enter button ■
on the keypad.
2. Select LOCK/UNLOCK.
3. The selection will bring you to the
Enter Pin Number screen.
4. Using the up and down arrows ▲▼,
select a pin number to lock out the
thermostat. The right arrow ► moves you to the next
pin digit.
5. Once you’ve entered the 4-digit pin number, press the
enter button ■ to save the pin. The screen will display
LOCKED and return to the main Screen.
6. Once you return to the Main Screen, in the upper left
of the screen will alternate between LOCKED and the
date and time.
7. Once unlocked, you will have to reset a pin number
again to lockout the thermostat again.
8. In the event the pin number is lost, the default is 9999.
Improper wiring or installation may damage the controller.
Wiring must conform to local and national electrical codes.
Introduction
The controller is a low-voltage controller which maintains
geo storage tank temperature by controlling the operation
of multiple hydronic heat pumps system. Batteries are not
required; temperature and mode settings are preserved
with the power off. The controller is not a power stealing
device and MUST have both R and C connected.
HydroZone Installation
1. Turn off all power to unit.
2. Separate the front and back pieces of the HZ0.
3. Mount the base of the HZ0.
4. Connect wires to proper terminal on the pump relay.
(see wiring schematic 97P806-01 on page 4).
5. Replace the cover on the base.
6. Turn on power to the unit.
Main Screen
After exiting from the setup mode, controller displays the main screen.
OPERATION, displays the current controller setup selection. They are OUTDOOR, TC AUTO, and TC MANUAL MODE. If the
operation mode is outdoor reset or tank control auto, the MODE should display OFF, ON, or EHEAT. If the operation mode
is tank control manual, the MODE should display OFF, HEAT, COOL, or EMHT. OUTPUT shall display the current status of the
outputs (WARM WEATHER SHUTDOWN, STANDBY, C1, C2, C3, C4, or AUX). STANDBY mode is active when the controller
is satisfied and waiting for a call. C1, C2, C3, and C4 will be off and O will stay in its previous state. If the outputs are off due
to a warm weather shutdown condition, the proper message should be displayed.
Tank setpoint temperature
Outdoor air temperature
Current mode of operation
Current tank temperature
OFF, ON, EMERGENCY
SET DATE, SET TIME,
BACKLIGHTING, F/C, LOCK/
UNLOCK, SERVICE CONTACT INFO
Current compressor outputs
15
HYDROZONE INSTALLATION MANUAL
Controller Operation cont.
Mode Select Display and Thermostat Controls
Manual Tank Display
Outdoor Reset or Tank Auto Control
OPERATING MODE
SELECTION
OPERATING MODE
SELECTION
OFF
HEATING ONLY
COOLING ONLY
EMERGENCY HEAT
OFF
ON
EMERGENCY HEAT
SELECTION ∇∆
⊲ PREVIOUS
SELECTION ∇∆
⊲ PREVIOUS
ENTER ◙
Maximum water
temperature needed for
minimum OAT
ENTER ◙
Change setpoint,
temperature, or mode
selection
Lowest design water
temperature
Enter or save selection
Lowest design outside air
temperature
Change selection or mode
Change setpoint
temperature or mode
selection
Highest design outside air
temperature
16
HYDROZONE INSTALLATION MANUAL
Controller Operation cont.
OAT
OAT Sensor
Compressor 2
O
Y
R
RB
Green (C4)
HZ
Brown (GND)
Brown (OAT)
Yellow (TS)
Yellow (GND)
A+
B+
GND
OAT
TS
GND
HydroZone
Controller
C4
C3
C2
C1
V
P
O/B
C
R
Gray (C3)
Blue (C2)
Yellow (C1)
Pink (P)
O-C2
Synergy 3D
Relay C2
P5-4
Relay C2
P5-11
Y-C2
Compressor 1
R-C2
C
O-C1
O
Relay C1
Y
Relay C1
R
Y-C1
P1
Synergy 3D
R-C1
Orange (O/B)
P5-4
C
P5
Black (C)
P5-11
P
Red (R)
Compressor 4
Yellow (1)
R
O-C4
O
C
Relay C4
Y
Relay C4
O
Note1
P
Black/White (2)
R
Y- C4
Synergy 3D
R-C4
Y1
P5-4
Y2
O-C3
Y3
Relay C3
Y4
Relay C3
O
Y- C3
Y
P2
Relay Board P6
Relay Board
NSW/NDW
Synergy3D option
OAT
Tank
Tank
Future
R
Future
To Heat Pumps
C4 C3 C2 C1 P O C R
PB3
C
GeoTank Sensor
Wiring Schematic
P5-11
Compressor 3
R-C3
R
Synergy 3D
O-C4
P5-4
Yellow (3)
Relay 42
P5- 11
Relay 41
Y-C4
P6
R-C4
Legend
HydroZone Accessory
Control Box
Optional connection if auxiliary heat is
used and heat pump 4 is not connected
NO
Notes
1. If an auxiliary water heater is used, connect to P6 on the
relay board as shown above.
Tank Pump
115 or 230/60/1
HydroZone Accessory
Control Box
NO
Factory Low voltage wiring
Factory Line voltage wiring
Field low voltage wiring
Field line voltage wiring
Optional block
DC Voltage PCB traces
Junction
Quick connect terminal
P
Water Heater
230/60/1
T
Thermistor
G
Light emitting diode - Green
Relay coil
2
3
1
L1
Field wire lug
Ground
HZ RB PB ZB -
These options are intended to be used by the installer. End
users are not advised to change or modify any of these
settings. Doing so may make your equipment stop working
properly and/or may void the warranty of the controller
as well as the equipment hooked up to the controller. To
access the installer setting menu, the mode must be set
to OFF. Then, press both the up and down arrow keys at
the same time for at least 5 seconds to enter the installer
screen. After initial power-up, you re-enter installer setup. If
no selection is made within 30 seconds, the controller will
return to the main screen.
Controller Setup
Options to select from:
1. Outdoor Reset - This control mode uses the outdoor
reset algorithm to continuously adjust the set point.
The set up menu allows selection of Maximum
Tank Temperature at a corresponding outdoor air
17
Hydrozone Control
Relay Board
Power Block
Zone Relay Board
Relay ContactsN.O., N.C.
Fuse
97P806-01
Installer Settings
Polarized connector
Wire nut
10/14/09
HYDROZONE INSTALLATION MANUAL
Controller Operation cont.
temperature (OAT), and Minimum Tank Temperature at
its corresponding OAT. An outdoor air sensor must be
installed.
be changed from the main screen by pushing the UP or
DOWN buttons.
Selecting ENTER shall take the screen to the
CONTROLLER SETUP screen.
Set point A is the maximum tank temperature set
point:
Tank temperature (TANK_A) range is 100°F to 130°F,
and default as 120°F.
Outdoor air temperature (OAT) range is 0°F to 20°F,
and default as 0°F.
Set point B is the minimum tank temperature set point:
Tank temperature (TANK_B) range is 70°F to 90°F, and
default as 80°F.
Outdoor air temperature (OAT) range is 40°F to 60ºF,
and default as 60°F.
This option will maintain the temperature with a tighter
deadband and automatically switch the heat pump
between heating and cooling to maintain the setpoint.
The factory default is 120°F heating and 5°F dead
band.
All these temperature setting are with increments of
1°F. The dead band is 2°F to 15°F with Increments of
1°F.
Tank Temperature Set point is calculated internally by
the outdoor reset algorithm, and updated every 30
minutes if this setup is selected.
Warm Weather Shutdown:
If the warm weather shutdown is selected, the
controller will check the outdoor air temperature
sensor every 30 minutes. If the temperature is higher
than the set temperature selected for 50 continuous
hours, then the HydroZone Controller will enter the
warm weather shutdown mode. If the temperature
drops below the selected setpoint for 5 continuous
hours, the controller will exit the warm weather
shutdown mode and return back to normal. Warm
weather shutdown selections are None, 45, 50, 55, 60,
and 65. The factory default is None.
3. Tank Control Manual - There shall be no automatic
changeover from heating to cooling or vice versa.
Heating and cooling modes must be selected manually.
If heating fixed is selected, the default temperature
for tank setpoint is 120°F with a 10°F deadband. The
set range is 80°F to 130°F, with Increments of 1°F. The
dead band is 2°F to 15°F with Increments of 1°F. The
factory defaults are 120°F heating and 5°F dead band,
80°F cooling and 5°F dead band, and warm weather
shutdown is None. When the selection is moved to
WARM WEATHER SHUTDOWN…, ENTER shall take the
screen to the WARM WEATHER SHUTDOWN screen.
When ENTER is selected, the installer shall be taken to
the COOLING screen.
2. Tank Control Auto - Default temperature for tank
setpoint is 120°F with a 5°F deadband. The set range is
40°F to 130°F, with Increments of 1°F. The dead band
is 2°F to 5°F with Increments of 1°F. The setpoint can
18
HYDROZONE INSTALLATION MANUAL
Controller Operation cont.
If no heating is selected, the screen shall go to the
COOLING screen.
Output
If cooling fixed is selected, the default temperature for
tank setpoint is 80°F with a 10°F deadband. The set
range is 40°F to 85°F, with Increments of 1°F. The dead
band is 2°F to 15°F with Increments of 1°F.
Factory
Defaults
Setup Configuration Options
C1
Single
Dual1 Stage1
Single
C2
Single
Dual1 Stage2
Off
Off
C3
Single
Dual2 Stage1
Off
Off
C4/W
Single
Dual2 Stage2
Aux
Off
Off
If AUX is selected in stage 4, ENTER would take the user
to “ADDITIONAL DEAD BAND FOR AUX HEAT” screen and
then to “MAXIMUM OAT FOR AUX HEAT” screen.
The “ADDITIONAL DEAD BAND FOR AUX HEAT” would
enable the installer to select how much extra dead band
should be added on top of the heat dead band before
auxiliary heat would come on. The range is between 5° and
15°F.
In the “MAXIMUM OAT FOR AUX HEAT” the installer can
select between NONE or a certain outdoor air temperature.
If the installer selects a certain temperature for OAT, the
AUX heat shall not come on if the outdoor air temperature
is above that temperature. The range is between 0°F and
40°F.
Staging
The controller can control up to four stages of compressors
or three compressors and one auxiliary heat. How the unit
stages the outputs will be determined by how the outputs
are configured. When selecting a dual capacity unit, the
next available stage will automatically become dual stage 2.
Example: If DUAL 1 STG 1 has been selected for C1 then C2
will automatically be DUAL 1 STG 2.
Staging Screen
Staging Setup of 1 Dual
Compressor and 1 Single
with Aux Enabled
STAGING
STAGING
C1 SINGLE / DUAL1 STG1
C2 OFF / SINGLE / DUAL1 STG2
C3 OFF / SINGLE / DUAL2 STG1
C4 OFF / SINGLE / DUAL2 STG2 /
AUX
C1
C2
C3
C4
WANT TO CHANGE?
YES
NO
OPTION ◄►
ENTER ◙
WANT TO CHANGE?
YES
NO
OPTION ◄►
ENTER ◙
If “NONE” is selected, the AUX heat can come on at any
time regardless of the outdoor air temperature. An outdoor
air sensor must be installed for this option.
DUAL1 STG1
DUAL1 STG2
SINGLE
AUX
ADDITIONAL DEAD
BAND FOR AUX
5°
MAXIMUM OAT FOR AUX
HEAT
40°
19
HYDROZONE INSTALLATION MANUAL
Controller Operation cont.
Lead/Lag
When the installer selects ENTER from any of the BRAND
NAME, MODEL NUMBER, SERIAL NUMBER, CONTRACTOR
NAME, and CONTRACTOR PHONE screens, the main INPUT
DEALER INFO screen is shown. In order to save the dealer
information in the permanent memory, the installer shall
select SAVE from the main INPUT DEALER INFO screen
and hit ENTER. The following screen is shown summarizing
the information the installer has inserted in the previous
screens.
If only C1 is selected in the staging, the lead/lag will be
selected as “NO”, and can not be changed.
Each compressor output will have an accumulator to keep
track of total run time. If any accumulator ran up to the
maximum count, all the accumulators shall be reset. Total
run time will be reset when lead/lag “NO” is selected. The
default setting is “NO”.
• First On – Compressor stage with least amount of accumulated run time.
• First Off – Compressor stage with most amount of
accumulated run time.
Factory Defaults
When YES is selected for RESTORE FACTORY DEFAULTS,
the controller will restore the factory defaults configuration.
Factory default control option is tank control manual. The
factory defaults are 120°F heating, 5°F dead band, and
warm weather shutdown None.
Service Contact Information
Input dealer info.
INPUT DEALER INFO
DEALER INFO
BRAND NAME
BRAND NAME:
MODEL NUMBER
USE ∇∆ TO SCORLL
THRU CHARACTERS
SERIAL NUMBER
WATER FURNACE
CONTRACTOR NAME
-------------
CONTRACTOR PHONE
SAVE
SELECT OPTION ∇∆
⊲ PREVIOUS
◙
ENTER
CHANGE LETTER ∇∆
⊲ PREVIOUS
ENTER
◙
20
HYDROZONE INSTALLATION MANUAL
System Startup and Checkout
System Checkout
1.
2.
3.
4.
5.
6. Set all zone thermostats to heating mode
7. Increase heating set point to 1° above the actual zone
temperature on all thermostats.
8. First stage heating should energize after a delay.
Output LEDs on ZB1-3 should be on.
9. Verify zone valve is operating or pump is running.
10. Instruct the owner/operator of correct thermostat and
system operation.
11. Fill out and forward all warranty registration papers to
WaterFurnace.
The HydroZone controller needs to be set to manual
heating and cooling for the following start-up
procedures.
Set all of the zone thermostats to the cooling mode.
Reduce the cooling set point to 1° above the actual
zone temperature on all thermostats.
First stage cooling should energize after a delay.
Output LEDs on ZB1-3 should be on.
Verify zone valve is operating or pump is running.
Parts Lists
Part
Number
HydroZone Controller Parts List
Specification
HZC
HydroZone Control Only
Part Number
Quantity
HZ0
HydroZone Control with signal isolation board - 0 Zone
(24V only)
Description
96P697-01
1
Mass Label Sheet
12P546-01
1
8 Position Terminal Block
45C394-01
1
Control Box
HZ04AANN
HydroZone Control with signal isolation board - 4 Zone
24V output (valve)
HZ04A9NN
HydroZone Control with signal isolation board - 4 Zone
115V output (pump)
45C394-02
1
Control Box Cover
HZ08AANN
HydroZone Control with signal isolation board - 8 Zone
24V output (valve)
11P813-00
1
Wire Kit
91P001A18
6
Screw #6-32 X 5/8
HZ08A9NN
HydroZone Control with signal isolation board - 8 Zone
115V output (pump)
17P554-01
1
HydroZone Controller
HZ12AANN
HydroZone Control with signal isolation board - 12 Zone
24V output (valve)
HZ12A9NN
HydroZone Control with signal isolation board - 12 Zone
115V output (pump)
HZ12AAEN
12 Zone expansion and not equipped with the HydroZone
Control or relay board - 24V output (valve)
HZ12A9EN
12 Zone expansion and not equipped with the HydroZone
Control or relay board - 115V output (pump)
HZAB
HydroZone Accessory Box (water heater or pump control)
L37-346
3/4" SWT Zone valve motorized sweat (Qty 1)
L37-347
1" SWT Zone valve motorized sweat (Qty 1)
TSU02*
Outdoor Air Sensor (required with “Outdoor Reset
Control”)
NOTES: HZ0 is for tank control only with no zones.
21
17P555-01
1
Low Voltage Relay Board
91P001A43
4
Screw #10-24 X 3/8
91P008A12
1
Nut #10-32
HYDROZONE INSTALLATION MANUAL
Notes
22
Manufactured by
WaterFurnace International, Inc.
9000 Conservation Way
Fort Wayne, IN 46809
www.waterfurnace.com
IM1550EW
11/10
Product: Type:
Size:
Document:
HydroZone
Hydronic Comfort Zoning System
4, 8, and 12 Zone Capacity
Installation Manual
©2010 WaterFurnace International, Inc., 9000 Conservation Way, Fort Wayne, IN 46809-9794. WaterFurnace has a policy of continual product research and development and
reserves the right to change design and specifications without notice.