Here - SFPE Great Plains
Transcription
Here - SFPE Great Plains
9/15/15 SFPE Great Plains Chapter Significant Changes to NFPA 72 Significant Changes to NFPA 72 – Impacting the Code Official, Designer and Contractor Who am I? Fire & Life Safety Interests… Inspector/Plans Examiner Deputy State Fire Marshal (MN) MN State Fire Chiefs Code Fire Alarm Systems Committee NFPA 72 Technical Committee Instructor for National Fire Academy technical fire prevention curriculum Appointed by MN Gov. Mark Dayton to Board of Architecture & Engineering (2013) Fire & Life Safety Interests… Fire Alarm Systems Fire & Life Safety Interests… Fire Alarm Systems School Fire Safety School Fire Safety Autism/Fire & Life Safety 1 9/15/15 Introductions Miscellaneous Information Restrooms Please introduce yourself: Current position? Years of experience in your industry? Years of experience dealing with or reviewing fire alarm systems? Breaks Roster Informal Participate Please ask questions ICC Preferred Provider This course has been approved by the International Code Council’s Preferred Provider Program for .6 continuing education hours. Please sign roster Agenda Please…. …turn off/silence cell phones and pagers. Learning Objectives/Goals Review the change in format from the Gain a better 2002/2007 and the 2010/2013 Review what is coming in the 2016/2019 editions Review CO alarm/detection requirements (NFPA 72/720) understanding of fire alarm systems Scope and layout of NFPA 72, 2013 Edition What’s coming in future editions That you learn something 2007 2010 2013 2 9/15/15 Fire Alarm System Components Fire Alarm Control Unit (FACU): Also called Fire Alarm Control Panel (FACP), Initiating Devices, Signal Types Alarm – warning of fire danger: Activated Activates by an initiating device, the notification appliances. Notification Appliances, Supervisory Circuits, Alarm Transmission & Monitoring. Alarm Signals Distinctive annunciation, Silencing accessible to authorized personnel only, Zones to be individually annunciated, Types: Manual pull stations, and smoke detectors, Water flow. Heat Signal Types Supervisory – action needed for a fire protection system: Activated by a supervisory device (tamper, low air, low temperature, etc.), Audible and visual signal at fire alarm control unit, annunciators, & monitoring station. Supervisory Signals Indicates a problem with a system monitored by the fire alarm system, Distinctive annunciation, Silencing accessible to authorized personnel only, Supervisory Signals Examples: Sprinkler system valve supervisory switch, pump running, phase reversal, etc. Duct smoke detectors, Elevator recall detectors, Stand-alone door hold-opens. Fire 3 9/15/15 Supervisory Signals Visible and audible indication of supervisory signals shall be automatically indicated within 90 seconds at the following locations: Fire alarm control panel Fire command center (when provided) Supervising station (when system is monitored) Signal Types Trouble – fault or abnormal condition that could impair the fire alarm system: Must be audibly and visually distinct from supervisory signals, Notification at the fire alarm control unit, annunciators, and monitoring station. Trouble Signals Indicates a problem with the fire alarm system itself, Silencing accessible to authorized personnel only. Trouble Signals Examples: Broken wire, Detector missing, Blown fuse, Dirty smoke detector. Terminology What Changed??? The term “alarm” refers to a single station device: Not part of a system, to alert the occupant, Examples: smoke alarms, CO alarms, Intended 2002 2007 2010 2013 The term “detector” refers to a device connected to a fire alarm system. A detector does not alert the occupant (horn/strobes do that) 4 9/15/15 New Format Applicable Codes & Standards NFPA 72 – National Fire Alarm and Signaling Code 2002/2007 editions had 11 chapters 2010/2013 editions have 29 chapters NFPA 70 – National Electrical Code Applicable Codes & Standards Americans With Disabilities Act Accessibility Guideline (ADAAG). Applicable Listings UL 217 – Single & Multi-Station Smoke Alarms. UL 268 – System Smoke Detectors. UL 268a – Duct Smoke Detectors. UL 539 – Single & Multi-Station Heat Alarms. UL 521 – System Heat Detectors. UL 864 – Fire Alarm Control Units. Look Applicable Listings for this listing inside FACU Applicable Listings UL 38 – Manual Signal Boxes. UL 1730 – Annunciation of Detectors. UL 464 – Audible Signal Appliances. UL 1971 – Hearing Impaired Signaling UL 985 – Household Fire Warning System Devices. UL 827 – Central Station Alarm Services. UL 1981 – Central Station Automation. UL 2075 – Gas Detectors & Sensors. Units. UL 1480 – Speakers & Amplifiers. UL 1481 – Power Supplies. UL 1638 – Visual Signals. 5 9/15/15 Editorial Remarks Asterisk (*) indicates annex material associated with the text Vertical line indicates new/changed material in the section Bullet indicates material removed [XXX-XXX] indicates committee responsible for definitions Terminology Changes “FIRE” removed or changed to “EMERGENCY” in most cases Example: “manual fire alarm box” is now “manual alarm box”. Where “FIRE” is integral to the meaning of the text, it was not changed Example: NFPA 72 Format NFPA 72 – 2010 National Fire Alarm and Signaling Code Introduction Chapters 1-3 (Administrative) Chapters 10-19 (Support) Chapters 20-29 (Systems) “fire department” NFPA 72 – Format Chapters 1-2-3 Administration Referenced Publications Definitions Chapters 4-9 Reserved Chapter 10 Fundamentals NFPA 72 – Format NFPA 72 – Format Chapter 11 Reserved Chapters 15-16 Chapter 12 Circuits and Pathways Chapter 17 Chapter 13 Reserved Chapter 18 Chapter 14 Inspection, Testing & Maintenance Chapters 19-20 Reserved Initiating Devices Notification Appliances Reserved 6 9/15/15 NFPA 72 – Format Chapter 21 NFPA 72 – Format Chapter 25 Emergency Control Functions and Interfaces (Previously Fire Safety Functions) Chapter 22 Reserved Chapter 23 Protected Premises Fire Alarm Systems Chapter 24 Emergency Communication Systems - New Reserved Chapter 26 Supervising Public Emergency Alarm Reporting Systems Chapter 28 Reserved NFPA 72 – Format Chapter 29 Single – Multiple Station Alarms and Household Fire Alarm Systems Annexes (Not enforceable language) A – Explanatory Material B – Engineering Guide for Automatic Fire Detector Spacing C – System Performance and Design Guide D – Speech Intelligibility Chapters 1-2-3 Administration Chapter 2 Chapter 3 Definitions NFPA 72 – Format Annexes (cont.) E – NEMA SB30 – Fire Service Annunciator and Interface F – Sample Ordinance G – Guide for Testing of Circuits H – Informational References I – Cross-Reference Table Chapter 1 – Section 1.4 Retroactivity Chapter 1 Referenced Stations Fire Alarm Systems Chapter 27 Publications Continues language that the standard only applies once adopted. Exception for conditions where the AHJ determines a distinct hazard It is necessary for the AHJ to research previous editions when applicable. 7 9/15/15 Distinct Hazard Most codes/standards have a “distinct hazard” clause. Gives the code official the authority to mandate compliance with “new” requirements. Use caution Use Be good judgment consistent Chapter 1 – Section 1.5 Equivalency Section 1.5 Nothing in the standard shall prevent the use of systems, methods, devices, or appliances of equivalent or superior quality, strength, fire resistance, effectiveness, durability and safety over those prescribed in the standard Fire alarm technology changes rapidly! Chapters 1-2-3 Chapter 1 (continued) 1.6.5 The values presented for measurements in this Code are expressed with a degree of precision appropriate for practical application and enforcement. It is not intended that the application or enforcement of these values be more precise than the precision expressed. Chapters 1-2-3 John’s Interpretation Use some common sense when measuring. There is no exact science regarding many of the dimensions listed in the standard (examples to come). Important New Definitions Acoustically Distinguishable Spaces Applicable to emergency communication systems Several new definitions for emergency New Definitions Managed Facilities-Based Voice Network Added to allow the continued use of DACTs with certain conditions Risk Analysis communication systems and the different types (one-way, in-building, wide area, etc.) Dedicated Function Fire Alarm Control Unit 8 9/15/15 Chapter 7 – Documentation Chapter 7 – Documentation NEW Chapter Minimum requirements for plan submittals Design documentation Shop drawings Completion documentation Inspection, testing and maintenance documentation Records retention documentation Chapter 7 – Documentation Section 7.7.2–A copy of the Record of Completion and other required final documentation is required to be maintained at the fire alarm control panel or other approved location. If not at the control panel, location is to be indicated at the main control panel. Material relocated from chapter 10 Fundamentals Chapter 7 – Documentation Document Storage Cabinet Fire Alarm Plan Symbols Section 7.2.3-Requires all symbols on fire alarm drawing plan submittals to comply with NFPA 170, Standard for Fire Safety and Emergency Symbols Chapter 7 – Documentation If the documents required to be stored at the FACP are in a separate cabinet or enclosure the cabinet shall be marked “FIRE ALARM DOCUMENTS” Chapter 10 - Fundamentals Protection of Fire Alarm Systems Primary/Secondary Power Supplies Annunciation and Annunciation Zoning Monitoring Integrity Documentation Impairments 9 9/15/15 Chapter 10 – Fundamentals Chapter contains requirements applicable to all fire alarm systems Exception-Household systems must comply with chapter 29 Section - 10.3 - Equipment 10.3.1 Equipment shall be listed for the purpose for which it is used. 10.3.2 Components shall be installed, tested and maintained in accordance with the manufacturer’s published instructions and this Code. 10.3.3 Devices receiving power from IDC or SLC shall be listed for use with control unit. Chapter 10 - Fundamentals Section 10.4.2-Devices and appliances shall be located and mounted so that accidental operation or failure is not caused by vibration or jarring. Section 10.4.3-Equipment shall be installed in locations where conditions do not exceed the voltage, temperature, and humidity limits specified in the manufacturer’s instructions. Chapter 10 - Fundamentals Chapter 10 - Fundamentals 10.4.5.1 Initiating Devices (manual and automatic) shall be selected and installed so as to minimize the possibility of nuisance alarms. Pay close attention to where initiating devices are being placed on plans. Chapter 10 - Fundamentals 10 9/15/15 Chapter 10 - Fundamentals Chapter 10 - Fundamentals Chapter 10 - Qualifications Chapter 10 – Fundamentals 10.5 Personnel Qualifications Revised and added requirements for personnel qualifications for: • System designers • System installers • Inspection/Testing/Maintenance Personnel • Supervising Station operators (added in 2010) • Inspectors/Plans Examiners – 2016 Edition Chapter 10 – Fundamentals System Designer Qualifications: The system designer must provide evidence of their qualifications/certifications when requested by the AHJ The system designer shall be identified on the design documents. System Designer Qualifications: Qualified • • • personnel include: People registered, licensed or certified by a state or local authority Personnel who are certified by a nationally recognized certification organization acceptable to the AHJ (NICET) Personnel who are factory trained and certified for fire alarm system design & acceptable to the AHJ. Chapter 10 – Fundamentals System Installer Qualifications: • People registered, licensed or certified by a state or local authority • Personnel who are certified by a nationally recognized certification organization acceptable to the AHJ (NICET) • Personnel who are factory trained and certified for fire alarm system design & acceptable to the AHJ. Installers shall provide evidence of their qualifications when requested by the AHJ. 11 9/15/15 Chapter 10 – Fundamentals Inspection, Testing, & Maintenance Personnel Qualified • • personnel include: Those who are factory trained and certified for the specific type and brand of system Personnel who are certified by a nationally recognized certification organization acceptable to the AHJ (NICET) Chapter 10 – Fundamentals Supervising Station Operators Operators in supervising station shall demonstrate competence in all tasks as required by chapter 26. Including… • Certified by the manufacturer of the receiving system or equipment or the alarm monitoring automation system. Chapter 10 -Fundamentals Language for 2016 Edition of NFPA 72 Establish a minimum standard for inspectors and plans examiners that inspect and review fire alarm/ECS systems Chapter 10 – Fundamentals Inspection, Testing, & Maintenance Personnel Qualified • • personnel include: Personnel who are registered, licensed, or certified by the state or local authority Personnel who are employed and qualified by an organization listed by a nationally recognized testing lab for the servicing of systems. Chapter 10 – Fundamentals Supervising Station Operators (Cont.) Operators in supervising station shall demonstrate competency in all tasks as required by chapter 26. Including… • Certified by an organization acceptable to the AHJ o Ex. Central Station Alarm Association • Licensed or certified by the state or local AHJ • Other training or certification approved by the AHJ AHJ/Plans Examiner Qualifications 2016 Edition Section 10.5.4.3-Code officials who perform plan review services shall meet one or more of the following: (1) Personnel who are registered, licensed, or certified by a state or local authority (2) Personnel who meet the requirements of NFPA 1031, Standard for Professional Qualifications for Fire Inspector and Plan Examiner (3) Personnel who are assigned to perform plan reviews and inspections by the authority having jurisdiction 12 9/15/15 Chapter 10 – Power Supplies Two separate power supplies required: Primary: Usually normal building power, • Can also be a generator. Secondary: • Usually storage batteries, • Can also be a generator (auto start). • Chapter 10 – Secondary Power Must include all loads, Must automatically provide power within 10 seconds: Loss Low of power, voltage conditions. Maximum loss of signal: 10 seconds. Both power supplies must be reliable. Chapter 10 – Secondary Power Supply Must be capable of operating the fire alarm system: 24 hours in “normal” (non-alarm) condition, Then for 5 minutes in alarm condition. Additional power supply requirements for Chapter 10 – Dedicated Branch Circuit A dedicated branch circuit shall be provided Location of dedicated circuit shall be permanently identified voice evacuation and monitoring stations. Chapter 10 - Changes Chapter 10 – Dedicated Branch Circuit System circuits shall be identified as follows: “FIRE ALARM” “EMERGENCY COMMUNICATIONS” “FIRE ALARM/ECS” for combination systems 2010 Edition 10.6 Signal Priority Signals need to be prioritized as follows: 1. 2. 3. 4. Emergency Communication System Fire Supervisory Trouble Note that ECS is not prioritized all the time, but based on a risk analysis • See definition of Risk Analysis in Chapter 3 13 9/15/15 Chapter 10 – 2013 Edition 10.7 Signal Priority Signals 1. 2. 3. 4. 5. need to be prioritized as follows: Emergency Communication System Fire Pre-Alarm/Carbon Monoxide Alarm Supervisory Trouble Chapter 10 – 2013 Edition Section 10.7.5-Carbon monoxide signals are permitted to take precedence over supervisory and trouble signals Section 10.7.6-Pre-alarm signals are permitted to take precedence over supervisory and trouble signals Chapter 10 - Fundamentals Chapter 10 - Fundamentals New Pre-Alarm signal language Pre-Alarm Condition-”An abnormal condition that poses an immediate threat to life, property or mission”. • Ex: Heat detector sending a signal to the panel when ceiling temperature reaches 130°F Intent is to give building owner/staff additional time to investigate possible issue before initiating devices reach alarm condition. New Pre-Alarm signal language Newer technology panels have pre-alarm capability • This is in addition to alarm, supervisory and trouble • This is different from alarm verification (will discuss later) Panel will notify building owner by text/email of condition about to happen Fire Alarm Signals Coded Alarm Signals Section 10.10.2-Fire alarm signals shall be distinctive in sound from other signals, shall comply with section 18.4.2.1 (T3 pattern), and shall not be used for other purposes. Section 10.12.1-Actuation of an alarm notification device shall occur within 10 seconds of activation of an initiating device. Section 10.12.2-Each round of a coded alarm signal shall consist of not less than three impulses. Coded alarms are typically used in areas/buildings where private notification is desired (hospitals, nursing homes, etc.) Ex. “Paging Dr. Firestone, Dr. Firestone, Building 4 West Wing” 14 9/15/15 Trouble Signals Trouble signals and their restoration to normal shall be indicated within 200 seconds. The trouble signal shall be located in an area where it is likely to be heard. Trouble Signals Visible and audible trouble signals and visible indication of their restoration to normal shall be indicated at the following locations: Fire alarm control panel Fire command center (when provided) Central, proprietary, or remote station service (when system is monitored) Trouble Signals Section 10.15.10.7-An audible trouble signal that has been silenced at the protected premises shall comply with the following: Signal shall automatically re-sound every 24 hours or less until fault condition is restored. The signal shall sound until it is manually silenced or acknowledged. The trouble signal shall be automatically retransmitted to the supervising station when provided Chapter 10 -Fundamentals 10.13.2 Alarm Signal Deactivation Requirement to deactivate both audible and visible signaling when silencing a fire alarm system. Silencing just the horns is a violation of ADA regulations. Trouble Signals Section 10.6.9.3 (13) Unless prohibited by the AHJ, supervising station alarm systems shall be arranged to delay transmission of primary power failure (trouble signals) for a period ranging from 60 minutes to 180 minutes. Chapter 10 - Fundamentals Protection of Control Equipment Automatic smoke detection is required at all fire alarm control panels, NAC power panels and supervising station transmission equipment if they are in a normally unoccupied location. Exception for fully sprinklered buildings has gone away 15 9/15/15 Initiating Devices FAQ: Can a heat detector be used when ambient conditions prohibit a smoke detector? Initiating Devices FAQ: Can a heat detector be used when ambient conditions prohibit a smoke detector? ANSWER: Yes; however, if ambient conditions are not suitable for a smoke detector, it often is not suitable for control equipment. Chapter 10 - Changes 10.18.3.2 Annunciators Annunciator location to be determined by the AHJ to facilitate efficient response by first responders. • Relocated from the notification appliance chapter (18) in the 2010 edition. Annunciator Annunciator Provides status information about a circuit, condition, or location: Lights, lamps, Alphanumeric displays. LED Annunciator Annunciators are available in three different variations: LED-Device will indicate what zone is in alarm, AC power, trouble condition and possibly some control features (Silence, System Reset, etc.) LCD-Text display indicating status of the fire alarm. Most have common control functions and limited programming capabilities Graphic-Large boards with a footprint of the building often using LEDs indicating devices 16 9/15/15 LED Annunciator First Floor Rear Exit First Floor Corridor 2nd Floor Rear Exit 2nd Floor Corridor First Floor Mech Room First Floor Room 105 2nd Floor Electric Rm 2nd Floor Classroom Basement Rear Exit Basement Storage Basement AHU Basement Laundry LCD Annunciator ELEVATOR MACHINE ROOM - PENTHOUSE - R-44 DUCT SMOKE DETECTOR FIRE PRIORITY 2 ALARM ALARM ALARM ACK ALARM ACK SYSTEM SUPERVISORY SUPV ACK SUPERVISORY ALARM SYSTEM ALARM POWER TROUBLE SILENCED ON TRB ACK ALARM SILENCE SYSTEM RESET ACKNOWLEDGE Graphic Annunciator Fire Alarm Impairments Section 10.21.1-The system owner shall be notified when a fire alarm system (or portion of a system) is down for maintenance. Where required by the fire official, other measures acceptable to the fire code official shall also be implemented. The owner shall be notified when an impairment is completed or discontinued. Chapter 12 – Circuits and Pathways Section 12.2 - General Application Chapter 12 is a NEW chapter in 2010 General Chapter 12 has no requirements Pathway Class Designation Chapter 12 describes pathway Pathway Survivability classifications and pathway survivability levels Other chapters refer to Chapter 12 for reference. Terminology 17 9/15/15 Chapter 14 – Inspection, Testing and Maintenance Chapter 14 – Inspection, Testing & Maintenance Application General Inspection Testing Maintenance Records For a fire alarm system to be reliable, it must be: Properly Designed Properly Installed Properly Maintained Inspection, Testing and Maintenance Chapter 14 is the only chapter in the standard that applies to new and existing fire alarm system installations. It is the owner’s responsibility to ensure ITM is provided for the system. 18 9/15/15 Inspection, Testing & Maintenance Section 14.4.4.3.1-Sensitivity Testing: Smoke detector sensitivity shall be checked within one year after installation and every alternate year thereafter. If device is within marked range after 2nd test, calibration may be extended to not exceed every 5 years Inspection, Testing & Maintenance Section 14.4.4.3.7-Testing- Prohibits an unmeasured concentration of smoke or other aerosol into the detector. Sensitivity testing must be done in accordance with the manufacturer’s specifications Some detector manufacturers do not permit testing with aerosol products Testing a device with aerosol products when not approved by the manufacture can affect detector performance. Inspection, Testing and Maintenance Section 14.2.4.1 Notification-Before any ITM begins, the supervising station (when provided) and all building occupants shall be notified of the testing. Inspection, Testing & Maintenance Section 14.4.4.3.4-Approved options for sensitivity testing include: A calibrated test method manufacturer’s calibrated sensitivity test instrument Listed control equipment A smoke detector/control unit arrangement where the detector cause a signal at the panel Another calibrated sensitivity test method acceptable to the fire code official A Inspection, Testing and Maintenance Impairments related to ITM shall also follow the requirements in 10.21. System defects or malfunctions shall be corrected. If defects or malfunctions are not corrected at the conclusion of the ITM, the owner must be informed of the issue(s) in writing within 24 hours. Inspection, Testing and Maintenance Test methods-Fire alarm systems and associated equipment shall be tested in accordance with Table 14.4.3.2. 19 9/15/15 Inspection, Testing and Maintenance Section 14.6.1.2.1-Site Specific Software-Many of the new fire alarm systems have specific software applications that must be provided by the installing contractor. Acceptance Test and Completion FAQ-Can a magnet be used to test a smoke Inspection, Testing and Maintenance A copy of this software must be provided to the owner and stored on-site. The owner of the building is responsible for maintaining the records. If contractors do not have this information it can cause delays to any repairs that may be necessary. Acceptance Test and Completion ANSWER: A magnet cannot be used to test the detector? smoke detector itself. Chapter 14 requires smoke to enter the detector’s chamber. A magnet can be used on a smoke detector to test the fire alarm system; including activating notification, capturing elevator/recall, close fire rated doors, etc. Commissioning vs. Acceptance Testing Commissioning vs. Acceptance Testing Commissioning vs. Acceptance Testing What is the difference? Commissioning is a systematic process that provides documented confirmation to the building owner or company representative that the installed system meets the original plan submittal and complies with all applicable laws, codes and standards Refer to NFPA 3 for details 20 9/15/15 Commissioning vs. Acceptance Testing Chapter 17 – Initiating Devices Acceptance testing is the procedure where tests are performed on the installation typically involving the authority having jurisdiction where the entire system is tested and reviewed to ensure compliance with laws, codes, and standards. Chapter 17 – Initiating Devices Chapter 17 – Initiating Devices Application Smoke-Sensing Fire Detectors Purpose Radiant-Energy Sensing Fire Detectors Performance-Based Design Combination, Multi-Criteria and Multi- General Requirements Sensor Detectors Gas Detection Other Fire Detectors Requirements for Smoke and Heat Detectors Heat-Sensing Fire Detectors Chapter 17 – Initiating Devices Chapter 17 – Initiating Devices Sprinkler Water-flow Alarm Initiating Devices Covers the installation criteria for all sensors Detection of the operation of Other Automatic or devices that are used to provide recognition of a fire Chapter covers any device that provides an incoming signal to the fire alarm control panel Installation criteria for single & multiple station smoke alarms are found in chapter 29. Extinguishing Systems Manually Actuated Alarm-Initiating Devices Fire Extinguisher Electronic Monitoring Devices Supervisory Signal Initiating Devices 21 9/15/15 Chapter 17 – Initiating Devices It is important for the designer to understand basic fire chemistry when utilizing chapter 17. Fire and the products of combustion behave differently based on the size of the room, the ceiling layout, and the amount of combustible materials in the space. Fire Plume Gases and combustion products rise to ceiling. Flames expand vertically. Fire Plume Influences Ceiling Jet Horizontal obstructions Form as fire plumes Fire size spread outward Expand the fire horizontally Fire area Interior finishes Distance of fire from walls Ceiling height Detector Coverage Total Coverage-When required by laws, codes, or standards, …includes all rooms, hallways, storage areas, basements, attics, spaces above suspended ceilings Rare to require total coverage Partial/Selective-Where laws, codes, or standards require selected areas be covered Nonrequired-Devices installed to achieve a specific fire safety objective but not mandated by laws, codes or standards NFPA 72 (10) Section 17.5.3 Chapter 17 – Initiating Devices Frequently asked question: Where in Chapter 17 will I find requirements for where devices are required to be installed? ANSWER: Chapter 17 does not require a building owner to install detectors or any other initiating device. The model codes will mandate when and what type of initiating device is necessary. 22 9/15/15 Chapter 17 – Initiating Devices Performance-Based Design There are three areas in NFPA 72 where the designer is permitted to use a performance-based design. • Initiation • Notification • Maintenance Initiation and notification are most common The authority having jurisdiction shall ultimately determine if the PBD is appropriate. Chapter 17 – Initiating Devices Section 17.4.3-Initiating devices shall be supported independently of their attachment to the circuit conductor. Initiating Device Locations – 2013 Edition 17.4.5 Initiating devices shall be installed in all areas, compartments, or locations where required by other governing laws, codes, or standards. Chapter 17 – Initiating Devices Section 17.4.2-When subject to mechanical damage, an initiating device shall be protected. Guard shall be listed for use with that detector. Initiating Device Locations – 02/07 Edition 5.4.6 Initiating devices shall be installed in all areas, compartments, or locations where required by other NFPA codes and standards or as required by the authority having jurisdiction. Heat Detectors Two types of heat detectors: Spot-type Line-type 23 9/15/15 Chapter 17 – Initiating Devices 17.6.2.2.2 Heat Detector Markings All heat detectors need to be marked with operating temperature. Spot heat detectors also need to be marked with their Response Time Index (RTI). • RTI measures the sensitivity of the device. • Typically have an RTI less than 100, with 10 indicating a more rapid response. Heat Detectors Heat detectors are not considered life safety equipment. Heat detectors should be installed where conditions are not favorable for smoke detectors such as kitchens, garages, boiler rooms, etc. The maximum ceiling temperature in the area where the heat detector is installed must be 20 degrees or more below the operating temperature of the heat detector. Heat Detectors Heat Detectors & High Ceilings Chapter 17 – Initiating Devices Environmental Factors on Smoke Detectors Section 17.7.1.8-Unless specifically approved and listed for specific environmental conditions, smoke detectors shall not be installed in the following locations: Where temperature is below 32°F Where temperature is above 100°F Where relative humidity is above 93% Air velocity > 300 ft./min. Environmental Conditions that Influence Detector Response Detection Air Velocity Humidity Temp. >300’/min >93% RH <32F >100F Ion X X X Photo O X X Beam O X X Air Sampling O X X X=May affect detector response O=Generally does not affect detector response 24 9/15/15 Environmental Factors on Smoke Detectors Factors to consider that may affect smoke detector response: Moisture Combustion Products and Fumes Atmospheric Contaminants Engine Exhaust Heating Elements and Abnormal Conditions Environmental Factors on Smoke Detectors Factors to consider that may affect smoke detector response: Combustion Products and Fumes fumes Cleaning fluids Cooking equipment Cutting/welding Fireplaces Ovens Environmental Factors on Smoke Detectors Factors to consider that may affect smoke detector response: Moisture Live steam Steam tables Showers Humidifiers Slop sink Humid outside air Water spray Environmental Factors on Smoke Detectors Factors to consider that may affect smoke detector response: Engine Exhaust engines Gas engines Gasoline forklifts Chemical Diesel Environmental Factors on Smoke Detectors Environmental Factors on Smoke Detectors Factors to consider that may affect smoke Factors to consider that may affect smoke detector response: detector response: Heating Elements with Abnormal Conditions Dust accumulation Improper exhaust Incomplete Combustion Electrical Noise and Mechanical Influences Vibration Radiation Intense light Electrostatic discharge 25 9/15/15 Chapter 17 – Changes Environmental Factors on Smoke Detectors Factors to consider that may affect smoke detector response: Airflow Gusts Excessive velocity Chapter 17 – Changes 17.7.1.11 Protection During Construction When smoke detectors are installed during construction, they need to be tested and calibrated or replaced. When detectors are not required during construction, they shall not be installed until after all the other construction trades have completed cleanup. 17.7.1.11 Protection During Construction When smoke detectors are installed during construction, they need to be tested and calibrated or replaced. When detectors are not required during construction, they shall not be installed until after all the other construction trades have completed cleanup. Chapter 17 – Initiating Devices Section 17.4.10*-If the intent is to initiate action when smoke/fire threatens a specific object or space, the detector shall be permitted to be installed in close proximity to that object or space. Chapter 17 – Initiating Devices There are some applications that do not require full area protection where there are ceilings in excess of 15 feet: Elevator landings Protection of fire alarm control units Detection should be placed on the wall above and within 60 in. from the top of the elevator door(s) or FACU See A.17.4.10 26 9/15/15 Chapter 17 – Changes 17.7.3.2.1 Smoke detector (or alarm) installation Wall mounting permitted within 12” of ceiling 4” dead space no longer in the code for smoke detectors • Exc. for sloped/peaked ceilings Wall-Mounted Smoke Alarms/Detectors Peaked Ceilings Sloped Ceilings Chapter 17 – Changes 17.7.3.2.3.1 Smoke Detector Spacing Code language modified to clarify nominal spacing of smoke detectors NFPA 72 (13) – “In the absence of specific performance-based design criteria, smooth ceiling smoke detector spacing shall be a nominal 30 feet.” OR Use the “0.7 Rule” 27 9/15/15 Detector Spacing - “The 0.7 Rule” The distance to the 30 ft. 15 ft. Does anyone know where the 30 foot spacing for corridor smoke detectors came from? 120 ft. 30 ft. 15 ft. 10 ft. corner is more than 15 ft. a2 + b2 = c2 152 = 225 225 + 225 = 450 √ 450 = 21.2 ft. 30 ft. x 0.7 = 21 ft. Corridor Spacing 15’ Corridor Spacing 30’ 30’ 30’ 15’ Corridor Spacing 10 ft. 120 ft. 10 ft. 120 ft. 15’ 30’ 30’ 30’ 15’ Conventional spacing method would require four (4) detectors. Detectors in Concealed Locations Section 17.4.7-When smoke detectors are required/installed in concealed locations, a remote alarm must be provided in a location acceptable to the AHJ. 20’ 40’ 40’ 20’ Using the 0.7 method, only three (3) detectors are needed. Duct Detectors Section 17.7.4.3- Detectors placed in air ducts or plenums shall not be used as a substitute for open area detection. 28 9/15/15 Smoke Detectors for Door Release NFPA 72 outlines two methods for controlling doors: Door and shutter release mechanisms that are integral to the door hold-open release mechanism (see section 21.8) Area smoke detectors Smoke Detectors for Door Release Section 17.7.5.6 (cont.) depth of wall section ≤ 24 in., one ceiling mounted smoke detector is required (on either side) If the depth of wall section is > 24 in. on both sides, two ceiling mounted smoke detectors are required Smoke Detectors for Door Release Service Section 17.7.5.6 If corridor is protected with smoke detection, no need for detection within 5 feet of door Specific installation requirements depend on the depth of wall section (see section 17.7.5.6.5) Smoke Detectors for Door Release-Scenario New Construction 125-unit Assisted Living Mixed use I-1/R-2 Smoke detectors If Smoke Detectors for Door Release Section 17.7.5.6.1-Smoke detectors that are part of an open area protection system covering the room, corridor, or enclosed space on each side of the smoke door and that are located and spaced as required by 17.7.3 shall be permitted to accomplish smoke door release service. Fire-rated corridor Fire door Kitchen Dwelling unit Smoke Detectors for Door Release Section 17.7.5.6.1-Smoke detectors that are part of an open area protection system covering the room, corridor, or enclosed space on each side of the smoke door and that are located and spaced as required by 17.7.3 shall be permitted to accomplish smoke door release service. 29 9/15/15 Smoke Detectors for Door Release New Construction 125-unit Assisted Living Mixed use I-1/R-2 Smoke detectors Fire-rated corridor Smoke Detectors for Door Release Service If separation between (multiple doorways is > 24 in., each doorway shall be treated separately Fire door Kitchen Dwelling unit Smoke Detectors in High Air Movement Areas Section 17.7.6.3.2-Smoke detectors shall Smoke Detectors in High Air Movement Areas Supply Air Smoke Detector not be located directly in the airstream of supply registers. Smoke Alarms/Detectors & Ceiling Fans Frequently asked question: Does NFPA 72 regulate the placement of smoke detectors in the proximity of ceiling fans? Smoke Alarms/Detectors & Ceiling Fans Frequently asked question: ANSWER: Yes and No; 72 regulates placement of smoke alarms/detectors in residential occupancies in section 29.8.3.4 #8. • 36” from ceiling fans Language does not apply to commercial (detector) installations. 30 9/15/15 Chapter 17 – Changes Manual Alarm Boxes 17.14 Manual Alarm Boxes 17.14.1.2 Manual alarm boxes used for purposes other than fire need appropriate signage and the color needs to be other than red. 17.14.1.3 Background needs to be contrasting color for manual fire alarm box locations. 17.14.1.4 Mounting height changed to correlate with ADA for operable part 42: - 48: above finished floor. Chapter 18 – Notification Appliances Chapter 18 – Notification Appliances Application General Audible Characteristics Visible Characteristics – public mode Visible Characteristics –private mode Graphic Visible Signaling Method Notification Signal The type of notification signal must match the evacuation scheme for the facility: Total evacuation, Zoned evacuation, Occupant relocation, Defend in place strategies. Notification zones shall be consistent with the emergency response or evacuation plan for the protected premises. Chapter 18 – Notification Appliances The use of the T3 pattern shall only be used where evacuation of the building or relocation inside the building is desired. The T3 signal shall not be used where occupants are practicing defend-in-place. 31 9/15/15 Notification Signals - Types Public Mode (most common): General evacuation signal, Private Mode: Attendant • • signal: No evacuation signal, Usually a coded voice message or chimes. Chapter 18 – Notification Appliances 18.3.3 Physical Construction 18.3.3.2 Notification appliances used for other purposes than fire cannot say “FIRE” on them. Chapter 18 – Notification Appliances 18.3.4.1-Audible or visual appliances subject to mechanical damage shall be protected against damage Covers must be listed for use with the appliance. Notification Appliances – Where Required NFPA 72 does not address where devices should be installed. It addresses how devices should be installed. Indoor/Outdoor Applications Section 18.3.3.1-Notification appliances must be listed for outdoor vs. indoor, high/low temperatures, high humidity, hazardous locations, etc. Audible Alarm Synchronization Section 18.4.2.4-The three-pulse temporal pattern must be synchronized throughout the evacuation zone. Separate patterns (lack of synchronization) is necessary to preserve the temporal pattern. 32 9/15/15 Chapter 18 – Notification Appliances Section 18.4.2.3-The signal shall be repeated for a period appropriate for complete evacuation of the building (when required), but for not less than 180 seconds. Sound Levels – Public Mode 15 dBA above average ambient sound; or, 5 dBA above average ambient sound level lasting 60 seconds If ambient sound level is greater than 105 dBA, visual notification appliance is required, Sound Levels – Public Mode 110 dBA is maximum allowed Protective Covers Protective covers used with notification appliances must be listed for the particular device. Unlisted equipment can degrade the effectiveness of the audible signal or visible strobe. The Distance Effect on Sound Pressure Level Distance from Appliance 10 ft. Sound Pressure Level nameplate value 20 ft. - 6 dBA 40 ft. - 12 dBA 80 ft. - 18 dBA 33 9/15/15 The Distance Effect on Sound Pressure Level The Distance Effect on Sound Pressure Level • Rule of Thumb is the output of an audible appliance is reduced by 6 dB if the distance between the appliance and the listener is doubled. Speaker Rated at 84 dBA at 10 feet Open Door Avg. Loss 8 dBA Typical Range 4-12 dBA Closed Door 17 dBA 10-24 dBA Sealed Door 28 dBA 22-34 dBA Stud Wall 39 dBA 32-42 dBA Source: NIST Handbook 119 “Quieting: A Practical Guide to Noise Control”: D.A. Robinson, Univ. of MA, “Sound Transmission Loss From Corridors to Rooms: Implications for Locating Fire Alarm Sounders” Sound Levels – Sleeping Areas 84 dBA 20 ft. 78 dBA 40 ft. 72 dBA 80 ft. 66 dBA Sound Levels – Private Mode The Walls and Doors Effect on Sound The Effect of Walls and Doors on Sound Transmission 10 ft. Section 18.4.4.2 10 dBA above average ambient sound, 5 dBA above maximum sound level having a duration of at least 60 seconds Section 18.4.4.2 When approved by the AHJ, audible signaling may be reduced or eliminated when visible signaling is provided. Sound Levels – Sleeping Areas Section 18.4.5 15 dBA above ambient average sound level, 5 dBA above maximum sound level (lasting 60 Section 18.4.5 15 dBA above ambient average sound level, 5 dBA above maximum sound level (lasting 60 75 dBA minimum measured at pillow level Whichever is greater. This will usually require an 75 dBA minimum measured at pillow level Whichever is greater. This will usually require an seconds), or appliance in the dwelling unit. seconds), or appliance in the dwelling unit. 34 9/15/15 Alert Tones in Sleeping Areas Alert Tones in Sleeping Areas-INCORRECT • Same for public and private operating mode • 70 dBA min. 1999 • 75 dBA since 2002 • Remember, NFPA 72 is not a retroactive document Apartment Fire Door Fire-rated corridor • It is necessary to research the standard in effect at the time New Requirement for Frequency of Alert Tone for Awakening Alert Tones in Sleeping Areas-CORRECT Apartment 520 Hz Square Wave Systems 75 dBA (Chapter 18) – effective January 1, 2014 (Chapter 29) – effective on adoption Household Fire Door Fire-rated corridor 520 Hz Sq. Wave New Requirement for Frequency of Alert Tone for Awakening New requirement effective 1/1/14: • Where audible appliances are provided in sleeping areas, they shall produce a low frequency signal that meets the following: • Alarm signal shall be square wave • Must have a frequency of 520 Hz • Installation issues? 3000 Hz Waking Effectiveness: High Risk Groups -School aged children: Thirteen percent of civilian fire fatalities in residential buildings were under the age of 10 1 -Alcohol/drug impaired: It’s suspected that over 27% of civilian fatalities in residential buildings are linked to alcohol, drug or chemical influence 1 -People with hearing loss: More than 34.5 million people in the US are hard of hearing 2 Sources: 1. 2. USFA, Civilian Fire Fatalities in Residential buildings 2008-2010 Report Working Effectiveness of alarms for adults who are hard of hearing, NFPA Dorothy Bruck; Ian Thomas, June 2007 35 9/15/15 Why the change? Background: Study done by Victoria (Australia) University Study tried to determine why people were not waking to the fire alarm signal Nearly 50% of the participants with mild to severe hearing loss slept through the 3000 Hz smoke alarm signal The higher 3000 Hz signal also was not as effective at waking children Why the change? Background: In the 1970s and early 1980s standard horns were replaced with low-current and more efficient high frequency horns. When this happened some stated they couldn’t hear the newer alarms as well. Both devices measured 85 decibels at 10 feet; The issue was the frequency, not the sound output. Why the change? People with hearing loss have trouble hearing high frequencies than low. The 520 Hz square wave signal awoke nearly 100% of the participants in the test. Low frequency signal is 6-10 times more effective than the high frequency devices Why the change? Due to the results from the Victoria University study, in 2006, the Fire Protection Research Foundation (FPRF) funded two additional research studies on the issue Focus was on the effectiveness of the 3000 Hz tone on high risk groups Waking effectiveness of alarms and adults who are hard of hearing Waking effectiveness of alarms for the alcohol impaired FPRF Study The studies tested six signals: 1. 2. 3. 4. 5. 6. 400 Hz Square wave signal 520 Hz Square wave signal 3000 Hz pure tone (standard) Bed shaker (under mattress) Pillow shaker Strobe light in T-3 pulse FPRF Conclusions The low frequency signal with a fundamental frequency of 520 Hz is the most effective signal for waking people. Low frequency signal woke 92% between 55 dBA and 75 dBA 3000 Hz signal woke 56% between 55 dBA and 75 dBA The low frequency signal is superior to bed/pillow shakers and strobe lights. 36 9/15/15 Low Frequency Appliances Sounder Base Activation In what occupancies will this apply? Notification Appliances-Audible Low frequency sounders will be required for new fire alarm system installations in: Hotel/motels Assisted living Dormitories Apartments Not required in: Hospitals* Nursing homes Prisons Child Care Centers Notification Appliance-Sleeping Area Section 18.4.8-If ceiling heights allow, wall- mounted audible appliances shall be not less than 90 inches above the floor, but not less than 6 inches below the finished ceiling. Notification Appliances-Visible Section 18.5.4-Wall mounted visible appliances shall be not less than 80 inches and not greater than 96 inches above the finished floor Performance-based design option for spacing and location Must be designed by a licensed engineer Number and placement depends on the room size and light output of the strobe 37 9/15/15 Visible Appliances-Wall Mounted Visible Appliances-Ceiling Mounted Visible Appliances-Sleeping Areas Visible Strobes Visible appliances are installed in one of two orientations: Wall mounted mounted Ceiling Strobes are listed for a certain orientation and cannot be used interchangeably. Wall mounted strobes cannot be mounted on the ceiling or vice versa. Incorrect Installations FAQ-Visible Strobes Why do some strobes have two separate candela ratings? What is the intensity of a strobe listed at “15/75” candela? 38 9/15/15 FAQ-Visible Strobes Why do some strobes have two separate candela ratings? What is the intensity of a strobe listed at “15/75” candela? ANSWER: The “15” candela indicates the rating when looking at the device from a 90 degree angle. The “75” candela indicates the rating when looking straight at the device. Visible Strobes-Other Considerations If there are interruptions in the corridor (fire doors, changes in elevation, etc.), these must be viewed as separate areas. Where more than two strobes are in the field of vision, devices must be synchronized so they flash simultaneously. Visible Alarm-Other Visible Strobes-Other Considerations Visible appliances must be provided in corridors. Corridors > 20 feet wide: Use room spacing requirements Corridors < 20 feet wide Minimum candela rating in corridors must be 15 cd and cannot exceed 100 feet apart. Visible Strobes-Other Considerations Why “more than two” and not “two or more? NFPA 72 Handbook: In 1996, the Code was modified to reduce the chances that visible notification appliances would induce seizures in persons with photosensitive epilepsy. The flash rate was adjusted so that two appliances (or groups of synchronized appliances) not flashing in unison cannot produce a flash rate that is considered dangerous. If more than two appliances or groups of synchronized appliances can be viewed at the same time, they must be synchronized. The option of spacing more than two appliances a minimum of 55 ft. (16.8) apart in large rooms in lieu of synchronization is no longer permitted by the Code. In 2007, the intent was clarified by noting that groups or zones of visible notification appliances may be synchronized and that it is the perceived composite flash rate that is important. Chapter 18 – Changes 18.4.10 Voice Intelligibility 18.4.10.1 Acoustically distinguishable spaces (ADS) are to be determined during design of a voice notification system. 18.4.10.2 ADS shall be identified by the system designer as needing or not needing voice intelligibility. 39 9/15/15 Audibility vs. Intelligibility Audibility – Can you hear the signal? Intelligibility – Can you understand the signal? Voice Alarm Messages Voice messages shall not be required to meet the audibility requirements for public mode signaling, but shall meet intelligibility requirements. Chapter 14 does not require voice signals to be measured for audibility. Sound produced from a voice system is modulated and a meaningful measurement cannot be determine. Voice Alarm Systems Voice Alarm Systems-Office Building Areas that may not require voice Private office intelligibility (18.4.10.2.1): Private office bathrooms; Mechanical/elevator equipment rooms or similar areas; Elevator cars Kitchen/storage rooms/closets Private Voice Alarm Systems-Office Building Private office Private office Intelligibility Required Here Private office Bathroom Private office Private office Private office Private office All areas (common area, private office, and bathrooms are considered an “acoustically distinguishable space” or ADS. Private office Bathroom Private office Private office Private office Private office Private office Private office Bathroom Voice Alarm Systems-Office Building Private office Private office Private office Private office Private office Private office Bathroom Bathroom Common work area/cubicles Private office Private office Common work area/cubicles Private office Common work area/cubicles Private office Not necessarily required in Private Offices or bathrooms Private office Private office Private office Private office Private office Bathroom 40 9/15/15 Voice Alarm – Nightclub Example Chapter 18 – Changes 18.5.2 Light Color and Pulse Characteristics 18.5.2.4 Strobes for FIRE are to be clear or nominally white 18.5.2.5 Strobes for other than fire, or combination use strobes, are to be clear, white or other color Chapter 21-Emergency Control Functions/Interfaces Chapter 21 Emergency Control Functions & Interfaces Previously titled “Fire Safety Functions” New Chapter-Relocated from Protected Premises Fire Alarm Systems Application General Elevator Recall for Firefighters’ Service Elevator Shutdown First Responders Use of Elevators Chapter 21 Elevators for Occupant- Controlled Evacuation HVAC Systems Door Release Service Electrically/Magnetically Locked Doors Exit Marking Audible Notification Systems Chapter 21 – Changes 21.5 First Responders Use of Elevators All elevator conditions are to be continuously monitored and displayed at fire service interface 21.6 Elevators for Occupant-Controlled Evacuation All elevator conditions are to be continuously monitored Status indicators to indicate availability 41 9/15/15 Chapter 23 Chapter 23 (cont.) Protected Premises FA Systems In-Building Fire Emergency Voice/Alarm Application Communications Prerecorded (Digital) Voice and Tone Fire Alarm General System Features System Performance & Integrity Performance for Initiating Device Circuits Performance for Signaling Line Circuits Performance for Notification Appliance Circuits System Requirements Chapter 23 (cont.) Suppression System Actuation Off-Premises Signals Guard’s Tour Supervisory Service Suppressed Signal Systems Protected Premises Fire Safety Functions Special Requirements for Low- Power Radio (Wireless) Systems Protected Premises Fire Alarm Systems Dedicated Function Fire Alarm Systems New term in the 2007 Edition “A protected premises fire alarm system installed specifically to perform fire safety function(s) where a building fire alarm system is not required” Intended to address “systems” where notification appliances and/or detectors are not required by model codes Systems Two-Way Communication Service Signal Annunciation Protected Premises Fire Alarm Systems 23.3.2 Features of non-required systems shall be established by the system designer based on the goals and objectives of the system owner. 23.3.2.1-Non-required protected premises systems and components shall meet the requirements of this Code. Protected Premises Fire Alarm Systems Dedicated Function Fire Alarm Systems Where codes, standards, or AHJs require monitoring of specific functions, but do not require a building fire alarm system, a dedicated function fire alarm system is appropriate. • Elevator recall • Sprinkler system • HVAC detectors Other functions of the fire alarm system are not required. 42 9/15/15 Protected Premises Fire Alarm Systems Section 23.8.1.2-Systems may have a pre-signal feature when approved by the authority having jurisdiction. A pre-signal feature must meet the following criteria: • FA sounds only in offices, control rooms, fire brigade stations or other constantly attended location (no general evacuation throughout) • Transmission to supervising station (when required) shall commence upon activation from the initial fire alarm signal Protected Premises Fire Alarm Systems Section 23.8.1.3-Fire alarm systems may utilize positive alarm sequencing (PAS) when approved by the AHJ PAS must comply with the following: FA signal must be acknowledged within 15 seconds of when the signal is received If signal is not acknowledged within 15 seconds, notification signal and general evacuation shall commence. Protected Premises Fire Alarm Systems Pre-signal features (cont.): • Requires human action to activate the general fire alarm (manual pull) • Pre-signal should only be considered in limited cases when approved by the AHJ Protected Premises Fire Alarm Systems PAS must comply with the following (cont.): If signal is acknowledged, a delay of the evacuation signal of up to 180 seconds begins for staff to investigate the source of the alarm signal. If FA system is not reset after 180 seconds ends, notification appliances commence and general evacuation shall begin. Protected Premises Fire Alarm Systems Protected Premises Fire Alarm Systems PAS must comply with the following (cont.): If a second automatic fire detector is actuated during the investigation (180 second) phase, notification appliances and general evacuation shall be activated. If any other FA initiating device is actuated (manual pull), notification signals and evacuation shall be activated The FA system shall provided a means for bypassing the PAS Pull Station-Section 23.8.5.1.2*-New Language Where connected to a supervising station, FA systems employing automatic detection or water-flow monitoring shall include a manual alarm box to initiate a signal at the supervising station. • Not required for elevator recall control and supervisory control (duct detectors) dedicated function fire alarm systems. 43 9/15/15 Protected Premises Fire Alarm Systems Annex Material-23.8.5.1.2 Pull station is intended to provide a backup means of communication with supervising station when system is out of service. Because system is out of service, pull station should be placed on a separate circuit that will not be placed on test with the main FA system. Should be located around FACP or sprinkler riser. Protected Premises Fire Alarm Systems Alarm verification (cont.) Only applicable to smoke detectors The feature may be a part of individual smoke detectors or part of the fire alarm control panel. See additional requirements in section 23.8.5.4.1 Protected Premises Fire Alarm Systems Section 23.8.5.4-Fire alarm systems equipped with alarm verification features shall be permitted. Alarm verification feature-A feature of automatic smoke detection and alarm systems to reduce unwanted alarms where smoke detectors report alarm conditions for a minimum period of time, or confirm alarm conditions within a given period of time period after being reset in order to be accepted as a valid alarm signal. Protected Premises Fire Alarm Systems Valve Supervisory Where codes, standards or AHJs require monitoring of sprinkler water-flow and valve supervisory switches, these functions can be accomplished by one of the following: • • Protected Premises Fire Alarm Systems 23.8.6.2 Notification Appliances This section exempts visible signals and evacuation signaling in the following locations: • • • Exit stairwells Exit passageways Elevator cars Dedicated Function Fire Alarm System -ORBuilding Fire Alarm System Low-Power Fire Alarm Systems Low-power (wireless) fire alarm systems: Special requirements found in section 23.18 (10) or 23.16 (13) Numerous applications: • Historic buildings • Industrial (corrosives) • Remote/Non-continuous properties • FA alterations in existing buildings 44 9/15/15 Combination Wireless System Wireless Applications • • • • • Chapter 24-Emergency Communication Systems Industrial Hotels Historic Multi-family Housing Colleges & Universities Chapter 24 Emergency Communication Systems (ECS) Application Purpose General One-Way Emergency Communication Systems Two-Way In-Building Emergency Communication Systems Emergency Communication Systems Emergency Communication Systems Chapter was new in 2010 edition Air Force Civil Engineering Chapter contains materials related to: Emergency Voice Alarm Communication Systems Mass Notification Systems came to NFPA looking for guidance on mass notification systems (MNS) Project was Technical assigned to NFPA 72 committee developed At the time there were no national standards/guidelines that addressed installation of these systems. 45 9/15/15 Emergency Communication Systems Section 24.3.1-Emergency communication systems shall be capable of reproduction of prerecorded, synthesized, or live messages with voice intelligibility Microphone Use Section 24.3.2.1*-All users of systems that are equipped with a microphone for live voice announcements shall be provided with posted instructions Can require alternate or additional languages is recommended speakers be distributed around the building rather than high power output of a few speakers. It Emergency Communication Systems 24.3.4 Ancillary Functions Emergency Communication Systems may be used for ancillary functions such as: • General paging • Background music • Non-emergency functions Primary function (emergency notification) must take precedence and cannot be compromised Emergency Communication Systems 24.3.5 Survivability Systems for relocation or partial evacuation require Level 2 or Level 3 Systems not used for relocation or partial evacuation can use any Level (0-3) Two-Way In-Building Wired Emergency Communication Systems require Level 2 or Level 3 Area of Refuge Emergency Communication Systems require Level 2 or Level 3 Emergency Communication Systems Combining fire/emergency communication systems with other systems is permitted. A fire alarm interface must be provided to ensure the fire/emergency signal takes precedence. Emergency Communication Systems 24.4.1.2.1-Voice evacuation messages shall be preceded and followed by a minimum of two cycles of the emergency evacuation signal specified in section 18.4.2 (T3 pattern). Goal is to get people’s attention with the T3 pattern and then move into the voice instructions. 46 9/15/15 Voice Alarm in Sleeping Areas In occupancies where sleeping accommodations are provided, a low-frequency tone shall be provided in the sleeping areas that complies with chapter 18. In areas where sleeping accommodations are provided, but message is communicated to those awake (public, common areas, etc.), low frequency is not required. Emergency Communication Systems 24.4 One Way Emergency Communication Systems 24.4.1 In Building Fire Emergency Voice Alarm Communication Systems 24.4.2 In-Building Mass Notification Systems 24.4.3 Wide Area Mass Notification Systems 24.4.4 Distributed Recipient Mass Notification Systems Emergency Communication Systems 24.5 Two-way In Building Emergency Communication Systems 24.5.1 Two-Way In Building Wired ECS 24.5.2 Two Way Radio ECS 24.5.3 Area of Refuge/Area of Rescue Assistance ECS 24.5.4 Elevator ECS Two-Way ECS Two-way ECS systems are divided into two categories: Systems intended to be used by building occupants; and, Systems that are intended to be used by firefighters, police, and other emergency services personnel Chapter 26-Supervising Station FA Systems 47 9/15/15 Chapter 26 Chapter 26 Layout Supervising Station Fire Alarm Systems Application General Alarm Systems for Central Station Service Proprietary Supervising Station Systems Remote Supervising Station Systems Communication Methods for Supervising Station Alarm Systems Supervising Station Fire Alarm Systems Three options for monitoring a fire alarm system Central Station Proprietary Supervising Station Remote Supervising Station • Remote Station represents roughly 85-90% of all monitored fire alarm systems (Source: AFAA) Supervising Station FA Systems Remote Supervising Station Fire Alarm Systems Monitored off premises • Fire or police station or public safety communications center • Other location acceptable to the AHJ Must monitor alarm and supervisory signals No requirement to monitor trouble signals Supervising Station FA Systems Central Station Service Fire Alarm Systems All alarm functions under a single contract • Installation, monitoring, retransmission, testing and inspection, runner service Defined responses to all three signals • Section 26.3.4 Complex requirements for monitoring facilities Requirement for system documentation Supervising Station FA Systems Proprietary Supervising Station Fire Alarm Systems Contiguous or Non-Contiguous entity and protected premises under the same ownership Must monitor all three signals Defined responses to all three signals Monitoring 48 9/15/15 Fire Alarm Signal (Pre)Verification 2010 Edition-Allows monitoring companies to verify alarm signals for Remote Station Service only before dispatching when approved by the AHJ IAFC introduced proposal to NFPA 72 to require verification on all fire alarm signals. IAFC proposal was modified was allowed only for remote station when approved by AHJ but verification cannot be more than 90 seconds. It Fire Alarm Signal (Pre)Verification 2013 Edition-Alarm signal verification was expanded to allow for all three types of supervising stations (when approved by the AHJ). Language changed from “Alarm Signal Verification” to “Alarm Signal Preverification” Fire Alarm Signal (Pre)Verification 2016 Edition-All language dealing with preverification of alarm signals was removed from NFPA 72. Rationale: • • Requirements are too confusing for code officials 911 call centers are not equipped to handle “possible calls” Confusing ? Caution: Do not confuse (smoke) alarm verification (chapter 23) with alarm signal pre-verification by the supervising station. Smoke Alarm Verification involves smoke detectors and/or fire alarm control panels and their response to alarm signals Alarm Signal Pre-Verification is referring to the supervising station’s role in responding to fire alarm signals from the protected premises. Confusing ? 2010/2013/2016 Editions Signals (Chapter 10) alarm verification (Chapter 23) Pre-verification of fire alarm signals (Chapter 26) Confusing ? 2010/2013/2016 Editions Pre-Alarm Pre-Alarm Smoke Smoke Signals (Chapter 10) alarm verification (Chapter 23) Pre-verification of fire alarm signals (Chapter 26) • Pre-verification of alarm signals will be going away in the 2016 edition. 49 9/15/15 Supervising Station Alarm Systems 26.2.1 Alarm Signal Disposition All alarms are required to be immediately transmitted to the communication center • Exception for pre-arranged test signals and alarm signal pre-verification This is not a new requirement but needs to be reiterated due to widespread noncompliance. Supervising Station Alarm Systems Section 26.3.7.1.2-The central station shall Supervising Station Alarm Systems 26.2.4 Alarm Signal Content-When required by the AHJ, alarm signals transmitted to a supervising station shall be by addressable device or zone identification (“Point ID”) Supervising Station Alarm Systems Section 26.3.7.1.2-The central station shall perform the following actions upon receipt of an alarm signal: perform the following actions upon receipt of an alarm signal: Immediately retransmit the alarm Immediately retransmit the alarm to the communications center Dispatch a runner/technician to the protected premises to arrive within 2 hours Immediately notify the subscriber Provide notice to the subscriber or AHJ, when required Supervising Station Alarm Systems Section 26.2.5.2-Any signal received at the supervising station not repaired to normal condition within 24 hours shall be redisplayed to the supervising station Supervising station must then notify the subscriber Exception: to the communications center… • The term “immediately” in this context is intended to mean without unreasonable delay. • Routine handling should not take longer than 90 seconds to transmit to the supervising station. Supervising Station Alarm Systems Section 26.2.7.4-The supervising station shall notify the AHJ prior to terminating service. Scheduled impairments 50 9/15/15 Communication Methods Requirements found in section 26.6 (both 2010 and 2013) Section contains approved methods for transmitting the fire alarm signal from the protected premises to the supervising station Chapter 26 – Changes 2007 Communication Methods: Active Multiplex 1-Way Radio DACTs Direct Connect McCulloh Private Microwave 2-Way Radio Other Technologies Chapter 26 – Changes 2010 Communication Methods Active Multiplex 1-Way Radio DACTs Direct Connect McCulloh Private Microwave 2-Way Radio Other Technologies Chapter 26 – Supervising Station 26.6.2 Communication Methods 26.6.2 General 26.6.3.2.1 DACTs 26.6.3.3 Radio • 26.6.3.3.2 One-Way Radio • 26.6.3.3.1 Two-Way Radio Chapter 26 – Changes 2010 Communication Methods DACTs 1-Way Radio 2-Way Radio Other Technologies Supervising Station FA Systems 2010 Edition Section 26.6.3.1.4.1-Where only one communications technology is used, any failure of the communication path shall be annunciated at the supervising station within 5 minutes of the failure. The transmission path shall be monitored 51 9/15/15 Supervising Station FA Systems 2010 Edition Section 26.6.3.1.4.2-Where two or more transmission methods are used (DACTs), the following requirements shall be met: Both transmission methods shall be monitored. Failure of any of the communications path shall be annunciated at the supervising station and the protected premises at intervals of not more than every 24 hours. Supervising Station FA Systems 2013 Edition (cont.)-For single transmission technology, failure of the communications path shall be annunciated at the supervising station and the protected premises at intervals of not more than every 60 minutes. Why the change from 5 minutes to 60 minutes? More FA are utilizing IP to monitor system and when IT departments shut down internet for service it was initiating trouble signals at panel. Supervising Station FA Systems Supervising Station FA Systems 2013 Edition Section 26.6.3.1.5-Where a single transmission path is used, the following requirements shall be met: The transmission method shall be monitored. of any of the communications path shall be annunciated at the supervising station and the protected premises at intervals of not more than every 60 minutes. Failure Supervising Station FA Systems 2013 Edition Section 26.6.3.1.6-Where multiple transmission paths are used (DACTs), the following requirements shall be met: Both transmission methods shall be monitored. Failure of any of the communications path shall be annunciated at the supervising station and the protected premises at intervals of not more than every 6 hours. Office Burn Video Section 26.6.3.1.10-The maximum duration between the initiation of an alarm signal at the protected premises, transmission of the signal, and receipt of the signal at the supervising station shall not exceed 90 seconds. 52 9/15/15 Chapter 26 – Changes 26.6.3.1.15 Secondary Power Secondary power supplies for communication methods need to match the requirements for secondary power for the rest of the fire alarm system (24 hours). Caution: Many power supplies for the communication method will not meet this requirement. Chapter 26 – DACTS Definition: Digital Alarm Communicator Transmitter (DACT) A system component at the protected premises to which initiating devices or groups of devices are connected. The DACT seizes the connected telephone line, dials a preselected number to connect to a DACR, and transmits signals indicating status change of the initiating device (NFPA 72) Redundancy is a Good Thing…Right? Active vs. Passive Methods Active = More Reliable The communications method indicates at the supervising station quickly when the communications pathway is interrupted Ex: Cell, Radio, IP Communications Passive = Less Reliable The communications method does not indicate when it is down; discovery is only when attempts are made to use it Ex: DACTs DACT Background & History First introduced in the 1980s. Determined (twice!) by TC to be unreliable. DACT proponents were successful on the third attempt to get into the standard, but with precautions for redundancy. Uses plain-old telephone service (POTS) phone lines DACT Background & History Regulated by phone company Regulated by NFPA 72 Regulated by NFPA 72 53 9/15/15 DACT Background & History DACTs are to be connected to the public DACT Background & History DACTs need to do the switched telephone network ahead of any customer owned equipment following when sending a signal: Must be ahead for any private-branch exchange (PBX) phone networks Seize the telephone line any other uses of the phone line No public telephone lines Disconnect Connection needs to be on a loop start POTS (plain old telephone service) telephone line. Ground start is not permitted. Fire panel should not have to dial “9” to get an outside line. No requirement for a dedicated phone line. DACT Background & History RJ31X Jack Set Up Transmission channels for RJ31X JACK LINES TO BUILDING LINES FROM STREET DACTs First channel must be a loop start POTS (copper) telephone line. Second channel could be either another telephone line, cellular telephone service, radio, or IP. FACU & DACT Phone Co. Termination Point DIGITAL Supervising Station DACT Background & History DACT Background & History Original concept of redundancy Use two end-to-end copper POTS telephone lines Connect to the fire alarm system via a RJ-31X jack To the phone company • Line 1 Line 2 To the phone company Original intent was to have phone lines on opposite ends 54 9/15/15 DACT Requirements Frequently Asked Question Section A DACT must have means to reset and retry if the first attempt to dial out is unsuccessful. Additional attempts shall be made to redial and transmit the fire alarm signal Can non-traditional phone service (fiber-optic or broadband) be used with a DACT? A minimum of 5 attempts and a maximum of 10. Frequently Asked Question Chapter 26 – DACTs Can non-traditional phone service (fiber- optic or broadband) be used with a DACT? ANSWER: Yes, as long as the service is Using telephone company fiber optic Regular telephone company fiber optic lines fiber optic lines is the same as end-to-end copper lines All equipment is telephone company owned PROBLEM: Standby power supplies are generally only 8 hours, not 24 hours provided through a managed facilitiesbased voice network (MFVN) CODEC Fiber-optic Connection Phone Company Exterior Phone Connection Line 1 Line 2 Option 1 To Phone Comp. (MFVN) Chapter 26 – DACTs Option 2 Cable company broadband Cable company telephone service CODEC is usually compatible with telephone company standards PROBLEM: Some equipment may be customer owned PROBLEM: Standby power supplies are generally 8 hours, not 24 hours 55 9/15/15 Broadband Connection Cable Company Only 1 transmission line from the protected premises Broadband Connection Cable Company Cable box inside protected premises Cable box inside protected premises Exterior cable box attached to building Exterior cable box attached to building Line 1 Line 1 To Cable Comp. (MFVN) Line 2 Exterior cable box Exterior cable box Chapter 26 – DACTs Using VoIP telephonic pathways Service similar to “Vonage”, “Magic Jack”, or “Ooma”. PROBLEM: Lines are generally not compatible with telephone company equipment. PROBLEM: Equipment is customer owned. PROBLEM: Standby power is generally nonexistent. To Cable Comp. (MFVN) Line 2 Chapter 26 – DACTs Using VoIP telephonic pathways Service similar to “Vonage”, “Magic Jack”, or “Ooma”. PROBLEM: Lines are generally not compatible with telephone company equipment. PROBLEM: Equipment is customer owned. PROBLEM: Standby power is generally nonexistent. Chapter 26 – The Future of DACTs? The second line on a DACT must be a different technology (i.e. radio, IP) Exc. When approved by AHJ If there are two telephone lines on a DACT, time tests must be every 6 hours. 56 9/15/15 Chapter 26 – DACTs With each passing day, more and more communications services migrate to broadband and IP-based services, leaving the public switched telephone network and plain-old telephone service as relics of a bygone era. AT&T Filing to the FCC, 21 Dec. 2009 Chapter 26 – Alternatives Radio IP-DACTs FAQ-Does an IP-DACT have to meet the AES Intellinet GSM Alarm Net same requirements as a DACT? IP Communications Firelite “IP-DACT” “IP-DACT” Honeywell Cellular cellular communicator Chapter 27 IP-DACTs FAQ-Does an IP-DACT have to meet the same requirements as a DACT? ANSWER: No; IP-DACTs connect to the DACT output of the FACP and convert the outgoing signal to IP. As such, they are considered to use IP technology in their connection to the IP network. They are therefore subject to the performance based design requirements of section 26.6.3.1 (not section 26.6.3.2 for DACTs) Public Emergency Alarm Reporting Systems Primarily used in the NE part of the country Chapter provides requirements for publicly accessible alarm boxes installed throughout a community • Boxes are connected to a receiving location that is owned and operated by the public authority. 57 9/15/15 Chapter 29 Smoke Alarms & Household FA Systems Single & Multiple Station Alarms and Household Fire Alarm Systems Application Purpose Basic Requirements Assumptions Detection and Notification Power Supplies Chapter 29 – Changes Section 29.3.8.1 Chapter 29 TC took a different approach than Chapter 18 TC on low frequency smoke alarms Smoke alarms with low frequency are only required for those with mild to severe hearing loss. Must have a square wave frequency of 520 Hz. This was clarified in the 2007 edition of NFPA 72: “Outside of each separate dwelling unit sleeping area, within 21 feet of any door to a sleeping room, with distance measured along path of travel” (29.5.1.1) Equipment Performance Installation Optional Functions Maintenance and Tests Markings and Instructions Correct smoke alarm location? Is this in the “immediate vicinity” of the sleeping room? (NFPA 72 (02) 11.5.1.1) Bedroom Chapter 29 – Changes 29.5.1.3 Large Areas in One & Two Family Homes Areas Bedroom in One and Two Family Homes over 1,000 sq. ft. require additional smoke alarms 58 9/15/15 Chapter 29 – Changes 29.7.9.2 Alarm Signal Verification This section permits verification of signals for Remote monitoring only prior to notifying the communication center as long as verification takes no longer than 90 seconds. Household Fire Warning Equipment Section 29.8.3.4 #4 Smoke alarms shall not be installed within 10 feet of stationary cooking appliances unless listed for close proximity to cooking appliances Smoke alarms installed between 10-20 feet must have a silencing button Nest Smoke Alarm Household Fire Warning Equipment Section 29.8.1.4 #5(b) Continues language requiring smoke alarms in one & two family dwellings to be replaced after 10 years or when they fail to operability test. Household Fire Warning Equipment Section 29.8.3.4 (cont.) Smoke alarms/detectors shall not be installed within 3 feet of bathrooms with a shower/tub Smoke alarms/detectors shall not be installed within 3 feet of ceiling fans NFPA 72 and NFPA 720 NFPA 720 Carbon monoxide detectors installed as part of a building wide detection system shall be installed as follows: • On the ceiling in the same room as permanently installed fuel-burning appliances • Centrally located on every habitable level and in every HVAC zone of the building • A performance-based design system 59 9/15/15 NFPA 72 and NFPA 720 NFPA 720 Single/multiple station carbon monoxide alarms shall be installed as follows: • Outside of each separate dwelling unit sleeping area in the immediate vicinity of the bedrooms • On every occupied level of a dwelling unit, including basements (not including attics or crawl spaces) • Other locations where required by applicable laws, codes or standards NFPA 72 and NFPA 720 NFPA 720 maintenance CO detection systems: Must be tested annually CO alarms: Must be tested in accordance with the manufacturer’s instructions at least monthly. NFPA 72 and NFPA 720 NFPA 720 Each CO alarm/detector shall be located on the wall, ceiling or other location as specified in the manufacturer’s installation instructions. Chapter 29 & NFPA 720 Proposal for the 2019 edition is to add NFPA 720 (CO detection and warning systems) into NFPA 72 (NFPA 720 would discontinue). Discussion also includes removing chapter 29 from NFPA 72 and creating a separate standard for single/multiple station smoke/CO alarms Rational for change: single & multiple station smoke/CO alarms are not “fire alarm systems” Proposal is to create a new NFPA standard for single & multiple station smoke alarms and carbon monoxide alarms (currently in NFPA 720). Stay tuned… NFPA 72 Task Group An NFPA 72 task group is working with the Fire Protection Research Foundation and Oklahoma State University Goal is to develop a new set of guidelines for code officials and designers when working on projects where the occupants have sensory related conditions. Finally… In closing, what changes would you like to see in NFPA 72? Work on the 2019 edition will begin soon. If you have suggestions please e-mail me. 60 9/15/15 Contact Information SFPE Great Plains Chapter [email protected] 952-261-5854 Thank you for hosting this E-mail is preferred option so I can attach code sections, if necessary Will do my best to get back to you in less than 24 hours. event! 61