installation

Transcription

installation
Expression
Art.nr 2900 6110
120705
IP24
Installations- och bruksanvisning....................................…....…..... Svenska sid 2.
Inkoppling skall utföras av behörig el-installatör. SPARA ANVISNINGEN! Efter installation
överlämnas denna till bastuns ägare eller till den ansvarige för bastun.
Installation and operating instructions................................…....... English page 5.
Wiring work should be carried out by a qualified electrician. SAVE THESE INSTRUCTIONS! After
installation, they should be given to the owner or operator of the sauna.
VARNING!
• Kontrollera före varje bastubad att inga olämpliga föremål finns i
basturummet eller på bastuaggregatet.
• Övertäckning av bastuaggregat medför brandfara.
• Beröring av aggregatets ovandel ger brännskador.
• Felaktig ventilation eller felaktig placering av aggregat kan under vissa
betingelser medföra torrdestillation med risk för brand.
• Bastuns golvmaterial skall vara av halkfritt material.
• Spola aldrig med slang inne i bastun.
• Det skall alltid vara minst 50 mm isolering direkt bakom träpanelen inne i
bastun (inget annat material som t ex spånplatta, gips etc. får
förekomma).
av bastuaggregat typ Expression i nisch, skall sensorn (C) placeras
250 mm från bakre vägg och 300 mm från tak.
Bild 9 - säkerhetsavstånd.
Minsta avstånd till inredning framför bastuaggregat.
Bild 10 - Bastu
(Bastuaggregat typ Expression och manöverpanel typ
CC/h1/EC50).
1 = bastuaggregat. 2 = termistor (sensor). 3 = manöverpanel CC 10/
CC 50/CC 300/h1/EC50. 4 = eventuell extern on/off-brytare. 5 = elcentral. 6 = reläbox RB30.
Kopplingschema, bild 24.
• Bastudörren skall, med ett lätt tryck, kunna öppnas utåt.
• Basturummet skall endast användas för bastubad.
• Det är ej tillåtet att montera mer än ett bastuaggregat i samma basturum,
Bild 11 - Bastu
• Doftessenser etc kan innebära risk för antändning om de hälls outspädda
Kopplingschema, bild 24.
såvida ej särskilda anvisningar för dubbelmontage efterföljs.
på stenmagasinet.
• Lämna aldrig små barn ensamma i bastun.
• Bastubad kan vara påfrestande för personer med svag hälsa. Rådgör
med läkare.
• Denna anvisning skall sparas.
(Bastuaggregat typ Expression och manöverpanel typ h1).
1 = bastuaggregat. 2 = termistor (sensor). 3 = manöverpanel h1. 4 =
eventuell extern on/off-brytare. 5 = el-central. 6 = reläbox RB30.
Bild 12, 13 – Expression + h1.
A = elrör. B = träpanel. C = isolering bakom manöverpanelen.
D = sensor. E = kapillärrör/ termistorledning. F = separat
manöverpanel h1. G = ventil.
Bild 13, 14 – Expression + CC/h1/EC50/TS.
A = elrör. B = träpanel. C = isolering bakom manöverpanelen.
D = sensor. E = kapillärrör/ termistorledning. F = separat
manöverpanel CC/h1/EC50/TS. G = ventil.
INSTALLATION
Strömstyrka och ledningsarea:
Bild 1.
Bastuaggregat Tylö Expression med separat manöverpanel h1 (CC10,
CC50, CC300, EC50, TS). Expression är ett golvstående aggregat.
Effekt
kW
10
Montering av bastuaggregat.
Bild 2 - borttagning av yttermantel
Manöverpanel typ h1.
Skjut den främre plåten uppåt. Lyft av yttermanteln för att komma åt
elanslutningen.
Bild 3 - montering av fötter.
Lägg tillbaka aggregatet i undre delen av emballaget. Montera de fyra
justerbara fötterna undertill.
Bild 4, 5 - elanslutning.
Spänning
volt
400V 3~
Strömstyrka
amp
16
Ledningsarea
mm²
2,5
Bruksanvisning: medföljer manöverpanelen.
Manuell och automatisk on/off. Max 24 timmars inkopplingstid, 24
timmars förvalstid.
Manöverpanel typ h1 styrs elektroniskt med möjlighet till
fjärrmanövrering från en eller flera platser. Ledningen mellan
bastuaggregat och manöverpanel skall vara skärmad (LiYCY).
Skärmningen ansluts till plint 12 i manöverpanelen, se
kopplingschema.
Låt aggregatet ligga kvar i förpackningen med fronten uppåt för att
underlätta installationen av elkablar. Emballaget fungerar även som
skydd mot repor på baksidan av aggregatet.
Alternativa placeringar.
Lossa skruvarna och öppna luckan.
Bild 10. På obegränsat område utanför basturummet.
Efter att elinstallationen är klar sätt tillbaka yttermanteln, bild 7.
Aggregatet placeras på samma vägg som inluftsventilen, bild 16.
Minimi-avstånd till sidovägg enligt tabell.
Bastuvolym
kW
min/max
m³
10
10 - 18
Min. avstånd till
sidovägg mm
normalmontage
”X”
200
nischmontage
”Y”
200
Min.
avstånd
till bakvägg mm
Min.
takhöjd i
bastun
mm
100
1900
Bruksanvisning: medföljer manöverpanelen.
EC 50-3. Manuell och automatisk on/off. Max 3 timmars inkopplingstid,
10 timmars förvalstid.
EC 50-12. Manuell och automatisk on/off. Max 12 timmars
inkopplingstid, 10 timmars förvalstid.
Manöverpanelerna typ CC.
*) Minsta tillåtna bastuvolym för nischmontage 4 m³.
Tylö bastuaggregat ansluts med vanlig standardledning (Fk eller EKK),
godkänd för fast installation. Kabel (EKK) eller elrör läggs på utsidan
av värmeisoleringen, se bild 12, 13, 14. Eventuell enkelledare (Fk)
skyddas i elrör (VP) fram till aggregatet eller av invändigt isolerad
böjlig metallslang.
Bild 6 - silicon.
För att säkerhetsställa att aggregatet står stadigt på sin plats skall man
applicera silicon på den angivna anläggningsytan (bild 6) under
fötterna.
Bild 8 - säkerhetsavstånd.
A = normalmontage. B = nischmontage. Minsta avstånd till sidovägg
(X, Y) se tabell. Minsta avstånd till bakvägg är 100mm. Vid montage
2
Manöverpanelerna typ EC50.
Monteras på obegränsat avstånd från basturummet.
EC50 panelerna styrs elektroniskt och finns i följande modeller.
Volym och minimiavstånd:
Effekt
Bild 11. På väggen inne i basturummet, max 760 mm ifrån golv.
Bruksanvisning: medföljer manöverpanelen.
Monteras på obegränsat avstånd från basturummet.
CC panelerna styrs elektroniskt och finns i följande modeller.
CC 10-3. Manuell och automatisk on/off. Max 3 timmars inkopplingstid,
10 timmars förvalstid.
CC 10-10. Manuell och automatisk on/off. Max 10 timmars
inkopplingstid, 10 timmars förvalstid.
CC 50-3. Manuell och automatisk on/off. Max 3 timmars inkopplingstid,
10 timmars förvalstid.
CC 50-12. Manuell och automatisk on/off. Max 12 timmars
inkopplingstid, 10 timmars förvalstid.
CC 300. Inbyggt veckour. Manuell och automatisk on/off. Max 24
timmars inkopplingstid, 24 timmars förvalstid.
Bild 24 Kopplingsschema.
1 = bastuaggregat. 2 = termistor (sensor). 3 = manöverpanel.
4 = eventuell extern on/off-brytare. 5 = RB 30
Kontrollera på aggregatets dataskylt att det ansluts till rätt spänning.
Den justerbara utluftsventilen ställs in så att - när bastun är uppvärmd
- den evakuerar en luftmängd av 6-8 m³ per person och timme.
Mekanisk till eller frånlufts ventilation av bastu kan leda till torrdestillation av träpanel med risk för brand.
Glöm inte att jorda!
Bild 16. Inluftsventilen placeras alltid direkt under
bastuaggregatet.
Manöverpanelerna typ TS
Inluftsventilen placeras rakt genom väggen mitt under aggregatet.
Ventilstorlek för en familjebastu ca. 125 cm², för större bastu
ca. 300 cm².
TS panelerna är termiskt styrda och har patenterad delad effekt.
Monteras utanpå eller infälld i vägg (bild 14). Vid infällt montage skall
det alltid finnas isolering bakom manöverpanelen. Kapillärrörslängd
1850 mm. Kan också erhållas med kapillärrörslängd 5000 mm.
Montering av sensor till manöverpanel TS (bild 17). A = kapillärrör.
B = hållare för sensor. C = plasthållare för kapillärrör.
D = sensor som monteras 300 mm från tak (bild 14, ej ovanför
bastuaggregatet).
Bild 18. Utluftsventilen skall aldrig utmynna
i det fria.
1 = bastuaggregat. 2 = manöverpanel.
Det skall vara maximalt avstånd mellan in- och utluftsventil, t ex
diagonal placering. Utluftsventilen skall sitta högt på väggen eller i
taket - och ha samma area som inluftsventilen.
Utlufsventilen skall alltid utmynna till det utrymme som dörr och
inluftsventil är placerade- den får aldrig utmynna direkt i det fria. Luften
som kommer ut från bastun förnyas kontinuerligt i det utanförliggande
rummet. Denna termiska ventilationsmetod fungerar oberoende av
närliggande lokalers eventuella under- eller övertryck.
Ett eventuellt tomrum ovanför bastutaket får inte vara helt inneslutet.
Tag upp minst ett ventilhål till tomrummet på samma vägg som
bastudörren.
Kontrollera på aggregatets dataskylt att det ansluts till rätt
spänning.
Alt. A: Utluftsventil genom bastuvägg (sett från ovan). Ventilen
placeras högt, nära taket.
Glöm inte att jorda!
Alt. B: Utluftsventil genom tomrummet ovanför bastuns tak (sett från
sidan).
Fjärrmanövrering.
Alt. C: Utluftsventil via trumma under taket inne i bastun (sett från
sidan). Utluftskanalen placeras i vinkeln mellan tak och vägg.
Trumman byggs t ex av träpanel och skall ha samma area som
utluftsventil.
Extra utrustning till manöverpanel typ TS.
Låsbart lock i transparent plast som monteras på manöverpanelen.
Finns i utföranden som förhindrar obehörig ändring av inställd tid och
temperatur, eller enbart temperatur.
Bild 27-29 Kopplingsscheman.
Inkoppling av manöverpaneler typ TS för fjärrmanövrering sker via
kontaktor.
Ovanliga spänningar eller fas-tal.
Vid inkoppling till andra spänningar eller fas-tal, som inte anges i
ovanstående kopplingsscheman, kontakta Tylö Kundservice.
Speciellt för ångbastu (Tylarium).
Undvik att placera utluftsventilen så att den utmynnar intill en kall
byggnadsdel. På så sätt elimineras risken för kondensbildning.
Placering av termistor (sensor).
Bild 19. Rekommendationer för basturumsbygge.
Monteras 300mm från tak på vägg mellan inluft och utluft (ej ovanför
bastuaggregatet) .
A. Golvram, stolpar, stående reglar, takram.
B. Liggande reglar, takreglar, ventiler.
C. 50 mm mineralull som värmeisolering, ca 20 mm luftspalt mot
eventuell yttervägg.
D. 12 mm träpanel i väggar och tak. Bakom träpanelen skall det alltid
finnas minst 50 mm isolering, inget annat material som t ex spån
eller gipsplatta etc. får förekomma.
E. Helsvetsad halkfri plastmatta som skall vara uppvikt ca 50 mm
bakom träpanelen.
F. Inluftsventil som alltid skall vara helt öppen, kan på utsidan förses
med ett gälgaller.
Termistorledningen kan förlängas utanför bastun med skärmad
svagströmsledning (2-ledare).
Tips! Termometern i bastun placeras på sådan höjd, att temperaturen
överensstämmer med de exakta siffror h1 visar.
OBS! Täta eventuellt hål i väggen bakom termistorn.
Reläbox (RB).
Monteras utanför och på obegränsat avstånd från bastun. Reläboxen
får inte placeras närmare än 1 meter från h1.
Skärmad svagströmsledning (6-ledare).
Manöverledning mellan CC/h1/EC50 till reläbox skall vara skärmad
svagströmsledning (6-ledare). Skärmningen ansluts till plint 12 i
reläboxen.
G. Utluftsventil, förses med skjutbar lucka för justering av luftmängden.
H. Lavbräder, min 22 mm av kvistfri fur (asp, lind eller abachi som
alternativ).
I. Spygatt (bör finnas i alla offentliga bastur). Ett spygatt eller
avlopp får aldrig placeras under bastuaggregatet.
Belysning.
Bild 20. Skyddsräcke.
Anslut belysningen enligt kopplingschema.
Bastuagregatets stenar och överdel är mycket heta! För att reducera
risken för ofrivillig beröring, rekommenderar Tylö alltid att ett skyddsräcke monteras runt aggregatet. Bygg skyddsräcket som skisserna
visar.
Tillval: externbrytare
Det finns möjlighet att ansluta en externbrytare till manöverpanelen.
Se kopplingsschema som medföljer externbrytaren (Art.nr. 9090
8045).
Momentan slutning: Brytaren fungerar som av/på för varje tryck.
Konstant slutning: Panelen går så länge slutning finns dock aldrig
längre än inställd drifttid.
När aggregatet är på kommer indikeringslampan i externbrytaren att
lysa. Om panelen är programmerad för senare start blinkar
indikeringslampan.
BYGGANVISNING
Viktigt med rätt bastuventilation!
En felaktigt utförd ventilation i bastun kan ofta resultera i heta golv och
lavar, sönderbrända väggar och tak (temperaturskyddet i aggregatet
utlöser)! Följ därför noga våra anvisningar för bastuns ventilation.
Tips!
• Avlopp skall aldrig finnas i en bastu. Men alla offentliga bastur bör
ha ett spygatt (I, bild 19) som är kopplat till ett avlopp utanför bastun
(i en privat bastu behövs inget spygatt).
• Har bastun fönster i dörr eller vägg, skall dörr- resp fönsterfodrets
hela nedre list strykas med båtfernissa och skarven mellan glas och
list tätas med våtrumssilikon. På så sätt förhindras eventuellt
kondensvatten på glasytorna att tränga ner i skarven.
• Lackera tröskeln och dörrhandtagen ett par gånger med båtfernissa, så behålls träets finish och rengöringen av bastun blir så
mycket enklare. Bastulavar, dekorraster och ryggstöd inoljas på
båda sidor med Tylö bastuolja (speciellt viktigt i Tylarium).
OBS! Allt övrigt trä inne i bastun skall vara obehandlat.
• Använd golvtrall i bastun endast om golvet är halt. Golvtrallen är
opraktisk och medför onödigt lång upptorkningstid för vatten som
spills på golvet.
3
• Trästävan och skopan ytbehandlas med båtfernissa eller inoljas
med Tylö bastuolja. Då håller stävan tätt och träet blir vackert
konserverat. Låt aldrig trästävan stå kvar i bastun efter badet.
• Innan bastun för första gången tas i bruk, skall den värmas upp till
ca. 90°C och vara igång ungefär en timme. På så vis försvinner
"nylukten" från bastuaggregatet.
• Bastun skall städas regelbundet. Lavar och golv skuras med såpa,
som är ett milt, skonsamt och väldoftande rengöringsmedel.
ALLMÄN INFORMATION
Bild 21. Fyllning av stenmagasinet.
Använd endast sten av typ diabas (Tylö Bastusten), "vanlig" sten kan
skada aggregatet. Fyll stenmagasinet runt elementen från botten till
topp, ca 50 mm över aggregatets främre ovankant, utan att pressa
stenarna på plats.
Bild 22.
Placera aldrig stenar ovanpå sidoluftskamrarna. Övertäckning på detta
sätt hindrar luftcirkulationen, aggregatet blir överhettat och
temperaturskyddet utlöser.
Kontrollera stenmagasinet minst 1 gång per år.
Detta är speciellt viktigt för offentliga anläggningar och bastur som
används ofta. Gör så här: Tag bort all sten ur magasinet. Rengör från
småsten, grus och kalk på stenmagasinets botten. Lägg endast
tillbaka hel, felfri sten och ersätt vid behov med ny diabas-sten.
Temperaturskydd.
Tylö-aggregaten har inbyggt temperaturskydd i kopplingsdosan nedtill
på aggregatet. Temperaturskyddet utlöses automatiskt om risk för
överhettning uppstår. Har skyddet utlöst är det oftast beroende på
felaktig ventilation, felaktig placering av aggregatet eller felaktigt fyllt
stenmagasin. Fackman anlitas för att återställa temperaturskyddet.
Bild 23.
Badkastning skall alltid ske med skopa på stenarna, aldrig med slang
eller hinkvis. OBS! Stenarna skall vara ordentligt varma.
Väldoftande bastubad kan erhållas genom att använda doftessenser.
Stänk några droppar essens i doftbehållaren.
För att erhålla en behaglig grundfuktighet i bastun fyll den inbyggda
luftfuktaren med vatten innan bastun kopplas på.
A. Doftbehållare
B. Luftfuktare
BADREGLER
• Duscha alltid innan du går in i bastun.
• Tag med dig en handduk att sitta på inne i basturummet. Stanna så
länge du tycker att det är skönt, av och till går du ut och svalkar dig
med en uppfriskande dusch.
• Visa hänsyn mot andra bastubadare. Bada inte i högre temperaturer än att alla kan uppskatta det.
• Små barn tycker också om att bada bastu. Låt dem plaska med en
balja vatten nere vid golvet eller nedre laven, där temperaturen är
låg, men håll dem under uppsikt.
• Avsluta alla bastubad med en lång sval dusch.
• Klä aldrig på dig direkt efter bastubadet, då börjar du svettas på nytt.
Sitt kvar naken utanför bastun och koppla av, njut en kall dryck och
känn hur gott du mår! Klä på dig först när kroppen har blivit avkyld
och hudens porer tillslutna.
Traditionella bastubad - torrbastu och våtbastu - kan
du bada med alla Tylö bastuaggregat.
Torrbastu och våtbastu är badformer som har sitt ursprung långt
tillbaka i historien. Dessa heta bastubad njuts bäst i temperaturer
mellan 70-90°C.
Vid torra bastubad förekommer ingen vattenbegjutning av
stenmagasinet och den relativa luftfuktigheten (RH) är endast 5-10%.
Våtbastu får du genom badkastning - då och då öser du en skopa
vatten över de heta stenarna, luftfuktigheten ökar markant (RH 1025%) - du känner hur värmevågorna vibrerar i luften och bearbetar
huden. Några droppar Tylö Bastudoft i vattnet som du häller på
stenarna, ger en uppfriskande och behaglig känsla i näsa och luftrör.
Prova gärna att avsluta bastubadet med en intensivare badkastning
som sticker till litet extra på kroppen. Våtbastu är den populäraste
badformen och den de flesta förknippar med begreppet traditionella
bastubad.
Viktigt! Använd vanligt dricksvatten - salt eller bräckt vatten skadar
värmeelementen. Spola aldrig vatten på eller i aggregatet.
Badkastning skall ske med skopa på stenarna. Anordningar som ger
kontinuerlig vattenbegjutning på bastuaggregatet är inte heller tillåtna.
Rengör vid behov doftbehållaren och luftfuktaren. Lyft av den och skölj
under rinnande vatten.
BRUKSANVISNING
Expression och TS
Temperaturinställning.
Siffrorna anger en stigande värmeskala. Pröva dig fram till den
badtemperatur som passar dig bäst. Ställ först in t ex läge 4. Önskar
du varmare eller svalare, justerar du uppåt eller nedåt tills du funnit din
idealtemperatur (i regel 70-90°C). Sedan kan du låta
temperaturinställningen alltid stå kvar i detta läge.
Tidsinställning på manöverpanel TS 16-3(B),
TS 30-03 och bastuaggregat Expression.
De första siffrorna 1-2-3 anger inkopplingstiden, de följande 9 siffrorna
är förvalstiden.
Vid direkt inkloppling: Vrid förbi den första 3:an och därefter tillbaka
till önskad inkopplingstid (1, 2 eller 3 timmar).
Timern stänger automatiskt av i läge 0.
Automatisk inkoppling: Vrid till markering 9 och därefter tillbaka till
önskad förvalstid (= tid innan aggregatet automatiskt kopplas på).
Timern stänger automatiskt av i läge 0.
Du kan närsomhelst vrida fram eller tillbaka, t ex för att manuellt
stänga av bastun (vrida till läge 0) eller för att ändra redan gjord
inställning.
Tidsinställning på manöverpanel TS 30-012.
Siffrorna 1-12 på timern är inkopplingstid. Bastuaggregatet är inkopplat
det antal timmar som ratten ställts in på och stänger automatiskt av i
läge 0.
Du kan närsomhelst ändra inställd tid och även stänga av bastun
manuellt genom att vrida till läge 0.
4
Vid eventuella problem kontakta inköpsstället.
© Eftertryck, helt eller delvis, är förbjudet utan Tylös skriftliga tillstånd.
Rätt till ändringar i material, konstruktion och design förbehålls.
Fig. 9 – Minimum safety distances.
WARNING!
• Make sure that there are no non-unsuitable object on top of the heater or
in the sauna room before starting the sauna heater.
• Do not cover the sauna heater. This creates a fire hazard.
• Do not touch the top of the heater. This will cause severe burns.
• Incorrect ventilation or an incorrectly located sauna heater can, under certain
circumstances, cause excessive drying of the wood in the sauna and create a
fire hazard.
• Cover sauna floors with a non-slip material.
• Never hose down the sauna.
• There must always be at least 50 mm insulation directly behind the wood
panelling in the sauna (no other material may be used, such as particle board,
plaster, etc).
• Sauna doors must always open outwards. All that should be needed to open
the sauna door is just a little light pressure.
• Do not use the sauna for any purpose other than sauna bathing.
• Do not install more than one sauna heater in a sauna room, unless you follow
exactly the special instructions for twin-heater installations.
• Sauna fragrances, etc. may ignite if poured undiluted into the stone
compartment.
• Never leave young children unattended in the sauna.
• Sauna bathing is not always suitable for persons in poor health. Consult your
doctor for advice.
• Store this information in a safe place.
Minimum distance to sauna fittings in front of a sauna heater.
Fig. 10 – Sauna
(Sauna heater type Expression and control panel type
CC/h1/EC50).
1 = sauna heater. 2 = thermistor (sensor). 3 = control panel CC 10/
CC 50/ CC 300/ h1/EC50. 4 = external power switch (if any). 5 =
distribution box. 6 = relay box RB30.
Fig. 11 – Sauna
(Sauna heater type Expression and control panel type h1).
1 = sauna heater. 2 = thermistor (sensor). 3 = control panel h1. 4 = external
power switch (if any). 5 = distribution box. 6 = relay box RB30.
Fig. 12,13 – Expression + h1.
A = electric conduit. B = wooden panel. C = insulation behind control
panel. D = sensor. E = capillary tube/thermistor wire. F = separate control
panel h1. G = vent.
Fig. 13,14 – Expression + CC/h1/EC50/TS.
A = electric conduit. B = wooden panel. C = insulation behind control
panel. D = sensor. E = capillary tube/thermistor wire. F = separate control
panel CC/h1/EC50/TS. G = vent.
Amperage and conductor area:
kW
INSTALLATION
10
Fig. 1.
Sauna heater Tylö Expression with separate control panel h1 . (CC10,
CC50, CC300, EC50, TS). Expresssion is a floor standing heater
230- 240V
3~
230240V~
400- 415V
3~
400415V 2N~
200208V~
200208V 3~
amp
mm²
amp
mm²
amp
mm²
amp
mm²
amp
mm²
amp
mm²
27
10
47*
16*
16
2,5
-
-
-
-
31
10
Control panel h1
Installing the sauna heater.
Pic 2 - How to remove the front cover
Instructions: included with the control panel.
Manual and automatic on/off. A maximum of 24 hours' running time, 24
hours' pre-set time.
Slide the front cover upwards. Lift of the outer cover to access the
electrical connection.
Control panel type h1 is electronically controlled, and can have a
remote control at one or more locations. The control cable
between the sauna heater and the control panel must be a
shielded cable (LiYCY). Connect the shielding to plinth 12 in the
h1, see the wiring diagram.
Alternative placement
The control panel is mounted on the wall inside the sauna room,
no more than 760 mm above floor level (fig. 11) or outside the
sauna at any distance from it (fig. 10).
Pic 3 - Mounting feet.
Place the heater in the bottom part of the packaging. Mount the four
adjustable feet underneath
Pic 4, 5 - Electrical connection
Leave the heater in the packaging with the front facing uppwards to
facilitate the installation of electrical wiring. The packaging also
protects the back cover from scrathes.
Losen the screws and open the hatch
After installation is complete replace the outer cover, fig. 7.
The sauna heater should be placed on the same wall as the air inlet, see
figure 16. Observing the regulations for the minimum distance to the side
wall.
Volume and minimum installation distances:
kW
10
Sauna
volume
min/max
m³
10 – 18
Min. distance from side wall
(mm)
standard
recess
installation
installation
“X”
“Y”
200
Minimum distance to
rear wall (mm).
200
Minimum ceiling
height
in sauna (mm)
100
1900
*) Saunas with a heater installed in a recess must have a minimum volume of 4 cu.m.
CC control panels
Instructions: included with the control panel.
Can be installed at any distance from the sauna room.
CC panels are electronically operated and are available in the following
models:
CC 10-3. Manual and automatic on/off. A maximum of three hours'
running time, 10 hours' pre-set time.
CC 10-10. Manual and automatic on/off. A maximum of 10 hours'
running time, 10 hours' pre-set time.
CC 50-3. Manual and automatic on/off. A maximum of three hours'
running time, 10 hours' pre-set time.
CC 50-12. Manual and automatic on/off. A maximum of 12 hours'
running time, 10 hours' pre-set time.
CC 300. Built-in weekly timer. Manual and automatic on/off. A
maximum of 24 hours' running time, 24 hours' pre-set time.
Figs. 24-26 Wiring diagrams.
Tylö sauna heaters are connected by a standard cable (Fk or EKK)
approved for permanent installation. The cable (EKK) or conduit is laid on
the outside of any heating insulation; see figs. 12, 13 and 14. A single-core
cable (Fk) should be protected by a plastic conduit up to the heater, or in
flexible metal conduit with internal insulation.
(With sauna heater Expression and control panel CC/h1/EC50).
1 = sauna heater. 2 = thermistor (sensor). 3 = control panel. 4 =
external on/off switch (if any). 5 = relay box.
Fig. 6 - Silicone.
TS panels are thermally operated and have a patented divided output.
They can either be surface-mounted or recessed for a flush fit (fig. 14). It is
essential to fit insulation behind control panels recessed into the wall. The
standard length of the capillary tube is 1850 mm, but a 5000 mm capillary
tube is also available.
Installing a sensor for a TS control panel (fig. 17). A = capillary tube. B =
sensor holder. C = plastic holder for capillary tube. D = sensor that is
installed 300mm below the ceiling (fig. 14, not above the sauna heater).
To make sure the unit is firmly in place silicon shall be applied at
the specified contact surface (fig. 6) under the feet.
Fig. 8 – Minimum safety distances.
A = standard installation. B = recess installation. Please refer to the table
for minimum distances to side wall (X,Y). Minimum distance to rear wall
is 100mm. When installing Expression sauna heater in a recess, the
sensor (C) should be placed 250 mm from the rear wall of the recess and
300mm below the ceiling.
6
TS-type control panels
Extra equipment for the TS control panel.
Locking cover in transparent plastic to fit over the control panel. Available
in designs to prevent unauthorised interference with time and temperature
settings, or temperature only.
Figs. 27–29 Wiring diagrams.
(With sauna heater Expression and control panel TS).
1 = sauna heater. 2 = control panel.
Check the heater’s type identification plate to ensure that the heater is
connected to the right voltage. Don’t forget – The installation must be
earthed!
Remote control operation.
TS control panels use contactors for remote control operation.
Placement of the thermistor (sensor).
Must be placed 300mm below ceiling on the wall between air inlet
and outlet (not above the sauna heater).
The thermistor wire can be lengthened outside of the sauna with a partially
enclosed low-voltage cable (2-core).
The thermometer in the sauna should be placed at a height so that the
temperature corresponds exactly to the numbers displayed on the CC
50/CC 100/ CC 300/ h1.
Note: If necessary seal the hole in the wall behind the thermistor.
Relay box (RB).
(No relay box is used for SE and MPE heaters).
Installed outside the sauna at any distance from it. The relay box may not
be placed closer than one metre from the CC 10/ CC 50/ CC 100/ CC 300/
h1.
Partially enclosed low-voltage cable (6-core).
The control cable between the CC/h1/EC50 and the relay box must be a
partially enclosed low-voltage cable (6-core). Connect the shielding cable
to plinth 12 in the relay box.
Lighting.
Connect the lighting according to the wiring diagram.
Remote control operation.
CC/h1 control panels are already prepared for remote-control operation
from one or more locations.
Option: external on/off-switch.
It is possible to connect an optional external switch to the h1 panel.
See wiring diagram delivered with the external switch (Art.no. 9090
8045).
Momentary connection: switches on and off respectively each time it is
pressed.
Constant connection: the panel is activated for as long as the
connection is maintained, up to the maximum running time that has
been set.
When the heater is on, the indicator lamp on the external switch lights
up. If the panel has been programmed to start at a later time, the
indicator lamp flashes.
Unusual voltages or number of phases.
Before connecting the heater to a different voltage or number of phases
than those described in the wiring diagram, contact Tylö Customer Service.
BUILDING INSTRUCTIONS
The importance of correct sauna ventilation.
Incorrect sauna ventilation can result in hot floors and benches, scorched
walls and ceilings (the temperature limit control is triggered)! So we do urge
you to follow our instructions for sauna ventilation carefully.
Adjust the air outlet to evacuate 6–8 cu.m. of air per person, per hour,
when the sauna is in operation.
Mechanical sauna ventilation is not to be recommended, as the forced air
supply can cause a fire hazard through the wooden panelling drying out.
Fig. 16. Inlet vent always directly below the heater.
The inlet vent should be driven straight through the wall directly below the
centre of the heater. The cross-section of the vent for a family sauna is
approx. 125 Sq.cm., for larger saunas approx. 300 sq.cm.
wall or in the ceiling, and should have the same cross-section area as the
inlet vent.
Spent air should always be led back into the same room from which it is
drawn into the sauna – it must never be discharged directly into the open
air. In this way, the air flowing from the sauna is continually being
replenished in the room outside. This thermal ventilation method always
works, no matter whether the pressure in adjacent rooms is negative or
positive.
If there is a gap above the sauna ceiling, do not seal it. To ventilate a cavity
above the sauna, drill or cut at least one ventilation hole into the cavity
through the wall on which the sauna door is located.
Alt. A: Outlet vent through the sauna wall (seen from above). The vent is
placed high up, near the ceiling.
Alt. B: Outlet vent through the cavity above the sauna ceiling (seen from
the side).
Alt. C: Outlet vent through a drum under the ceiling in the sauna (seen
from the side). The outlet duct should be placed at an angle between the
ceiling and the wall. The drum can be built of wooden panelling and have
the same area as the outlet vent.
Fig. 19. Recommendations for sauna construction:
A. Floor frame, corner posts, studs, ceiling frame.
B. Battens, rafters, vents.
C. 50 mm mineral wool as heat insulation, approx. 20 mm air gap between
insulation and outer wall.
D. 12 mm wooden panel in walls and ceilings. There should always be at
least 50 mm of insulation behind the wooden panel; no other material,
such as particle board or plaster, may be used.
E. Bonded, non-slip plastic floor-covering, extending approx. 50 mm up
the walls behind the wooden panelling.
F. Inlet vents should always be fully open. May be fitted with a shuttered
vent on the outside.
G. Outlet vent, can be fitted with a sliding hatch to adjust through-flow.
H. Benches of at least 22 mm thick knot-free pine (alternatively aspen,
lime or obeche).
I. Drainage channel (recommended in public saunas). Never place a
drainage channel or drain under the sauna heater.
Fig. 20. Heater guard.
The stones and the top of the sauna heater get very hot! In order to reduce
the risk of accidental contact, Tylö always recommend that a heater guard
be fixed as shown in the sketches.
Some words of advice:
• There should never be a drain in a sauna. However, all public saunas
should have a drainage channel (I, fig. 19) connected to a drain out-side
the sauna (no drainage channel is needed in a private sauna).
• If the sauna has a window in the door or wall, treat the lower moulding
with boat varnish and seal the joint between the glass and the moulding
with a water-resistant silicone sealant. This prevents any condensation
on the glass from seeping into the wood.
• Varnish the threshold and door handles a few times with boat varnish to
maintain the finish and simplify cleaning the sauna. Benches, decorative
edging and back supports should be oiled on both sides with Tylö sauna
oil (this is particularly important in the Tylarium). Note: All other wood in
the sauna should be untreated.
• Install floor decking only if the floor is slippery. Floor decking is impractical and prolongs the drying time for any water spilt on the floor.
• Treat the bucket and ladle with boat varnish, or oil them with Tylö sauna
oil. The bucket will remain watertight and the wood will be beautifully
preserved. Never leave the wooden bucket in the sauna after a sauna
bath.
• Before you enjoy your first sauna bath, heat the sauna room up to 90°C
and leave the heater to run for about 1 hour. This will rid the room of that
“new” smell.
• Clean your sauna regularly. Scrub the benches and floor with soft soap.
It is a mild, gentle detergent and leaves a pleasant fragrance.
General Information
Fig. 21. Filling the stone compartment.
Only use stones of the dolerite type (Tylö sauna stones), as “ordinary”
stones can damage the unit. Fill the stone compartment around the
elements from bottom to top, stacking the stones approx. 50 mm above the
front edge at the top of the unit. Do not press the stones into place.
Fig. 18. The outlet vent should never discharge directly
into the open air.
Position the air inlet and outlet vents as far away from one another as
possible (diagonally opposite). The outlet vent should be located high on a
7
Fig. 22.
Never place stones above the side air chambers. This prevents air
circulation, the unit becomes overheated and the temperature limit control
is triggered.
Check the stone compartment at least once a year.
This is especially important for public saunas and saunas in frequent use.
Remove all stones from the compartment. Clean any small stones, grit,
gravel and chalky deposits from the bottom of the stone compartment. Use
only stones which are whole and intact, replacing them when necessary
with new dolerite stones.
Temperature limit control.
Tylö sauna heaters have a temperature limit control built into the terminal
box on the heater. This is activated automatically if there is any risk of
overheating. More often than not, the cut-off is triggered because of
incorrect sauna ventilation or an incorrectly located sauna heater. Call an
expert to reset the temperature limit control.
Fig. 23.
Sprinkling water on the stones
Must always be done with a ladle onto the stones, never with a hose or
bucket. Note: The stones must be hot.
Fragrant sauna bath can be obtained by using fragrances. Splash a
few drops of essence in the fragrance dispenser.
In order to obtain a pleasant because moisture in the sauna fill the
internal humidifier with water before the sauna is switched on.
A. Fragrance dispenser
B. Humidifier
If neccessary, clean fragrance dispenser and humidifier . Lift it off and
rinse under running water.
OPERATING INSTRUCTIONS
Expression and TS
Temperature setting.
The numbers indicate a rising temperature scale. Experiment to find the
temperature that suits you best. Begin for example by turning the
thermostat dial to position 4. If you later find that you would prefer a higher
or lower temperature, adjust the dial up or down until you find the ideal
bathing temperature for you (usually 70–90°C). Once you have found the
right temperature, you can leave the dial on this setting.
HOW TO GET THE MOST
OUT OF YOUR SAUNA
• Always shower before going into the sauna.
• Take a towel in with you to sit on. Stay inside the sauna only as long as
it feels pleasant. Go out now and then to cool off and freshen up with a
quick shower.
• Show consideration for other bathers. Don’t set the temperature higher
than is pleasant for all those using the sauna.
• Young children love saunas. Let them splash about in a tub of water on
the floor or the lower benches where it is somewhat cooler. But
remember to keep an eye on them at all times.
• Round off your sauna with a long, cool shower.
• Never get dressed right after your sauna. This will only cause you to
perspire. Relax, treat yourself to a cold drink and enjoy a sensation of
true well-being. Don’t get dressed until your body has cooled down and
your pores have closed once again.
You can enjoy traditional dry and wet saunas with provide continuous
water sprinkling are not permissible.
You can enjoy traditional dry and wet saunas with all
Tylö heaters.
Dry and wet saunas are bathing forms whose history is shrouded in the
mists of time. These hot baths are best enjoyed at temperatures between
70ºC and 90ºC.
In dry saunas, where the stones are not sprinkled with water, the relative
humidity (RH) is as low as 5–10%.
In wet saunas, when water is ladled on the hot stones from time to time,
the relative humidity rises steeply to 10–25%, and you can feel how the
quivering waves of heat massage their way into your skin. A few drops of
Tylö Sauna Fragrance added to the water poured over the stones give a
pleasantly invigorating sensation, clearing nasal cavities and helping you
breathe more easily. A great way to round off any sauna is to experience
the pleasant tingling sensation when you pour a little extra water over the
stones. Wet saunas are considered by most people to be the traditional
way to enjoy a sauna, and they are the most popular too.
Important! Use ordinary drinking water. Salt-water, swimming pool or spa
water will damage the heating elements. Never hose down the heater.
Water sprinkling must always be done with a ladle onte the stones.
Devices that provide continuous water sprinkling are not permissible.
Timer settings with control panels TS 16-3(B),
TS 30-03 and sauna heater Expression.
The first figures, 1–2–3, indicate the length of time the sauna will operate.
The following 9 figures are used to pre-set start-up times.
For immediate operation: First turn the dial past the first figure 3 and then
back again to the figure corresponding to the length of time you wish the
heater to run for (1, 2 or 3 hours). The timer turns the heater off
automatically when the 0 position is reached.
For automatic operation: Turn the dial to the figure 9 and then back to the
desired pre-set time (in other words, the number of hours before the heater
automatically switches itself on). The timer turns off automatically when the
0 position is reached.
You may turn the dial forwards or backwards whenever you wish, for
example, to switch off the sauna manually (turn to 0) or to change a setting
you have already made.
Timer settings with control panels TS 30-012.
The figures 1–12 on the timer indicate the operating time. The heater
remains in operation for the number of hours the switch is set to, and
automatically switches itself off when the 0 position is reached.
You may change the time setting whenever you wish and also switch off
the sauna by turning the dial to 0.
8
www.tylo.com
In the event of any problems, please contact the retailer where you
purchased the equipment.
© This publication many not be reproduced, in part or in whole, without the written permission of Tylö.
Tylö reserves the right to make changes in materials, construction and design.
CC
CC 100
INFO
MENU
TEMP
OFF
ON
LIGHT
EC50
h1
TS
2
4
3
2
0
5
6
1
7
3
1
0
TIME
9
8
TS
5
1
2
4
3
TEMP
1
2
3
4
SIL
ICO
6
5
NE
A
A = min. 400mm
B = min. 200mm
Min.
100 mm
X
A
B
Max.
250 mm
7
8
Y
Y
C
Min.
20
mm
Max.
1000 mm
9
B
50-150cm
300mm
50-150cm
300mm
2
2
3
4
3
4
5
5
Max
760
mm
6
6
1
1
10
11
Expression + CC/h1/EC50
Expression + h1
A
300
mm
E
A
300
mm
B
D
C
D
B
F
C
F
E
F
Max
760
mm
12
Expression + h1
G
G
13
14
Expression + CC/h1/EC50/TS
B
A
C
D
15
A
18
17
16
B
C
A
B
D
G
C
A
A
B
F
E
A
Sauna
H
I
19
Alt A
Alt B
A = min. 200 mm
B = min. 400 mm
Max 400 mm
Min 20 mm
A
A
B
B
A
B
20
21
22
23
A B
400 - 415 - 440 V 3N~
10
24 12 == Expression
thermistor (sensor)
5
3
11 12 13 14 15 16
4*
A B 11 12 13 14 15 16 17 18 19 20 21
3 = CC/h1/EC50
4 = external switch
5 = RB 30
2
5
G
5
L L L N A B C D U V W Z X Y
1 2 3
1 2 3 4 5 6
4
40 41 B B
1
G
U V W Z X Y
1 2 3 4 5 6
2
1
200-240 V~
3
5
3 x 1.5 mm²
6 x 0.2 mm²
5 x TAB
3 x 0.2 mm²
2 x 0.5 mm²
4 x TAB
3 x 1.5 mm²
L1 L2 L3 N
400-440 V 3N~
4* See wiring diagram delivered
with the External Switch
1.5 mm²
WARNING! THIS APPLIANCE MUST BE EARTHED!
400- -208
415- -230
440- V
2N~
200
240
V 3~
10
25 12 == Expression
thermistor (sensor)
5
3
11 12 13 14 15 16
3 = CC/h1/EC50
4 = external switch
5 = RB 30
4*
A B 11 12 13 14 15 16 17 18 19 20 21
2
5
G
5
L L L N A B C D U V W Z X Y
1 2 3 4 5 6
1 2 3
4
40 41 B B
1
G
U V W Z X Y
1 2 3 4 5 6
2
1
200-240 V~
3
5
3 x 1.5mm²
4 x TAB
3 x 1.5 mm²
3 x 0.2 mm² (AWG 24)
2 x 0.5 mm² (AWG 20)
7 x TAB
6 x 0.2 mm² (AWG 24)
200-240 V 3~
4* See wiring diagram delivered
with the External Switch
1.5 mm²
WARNING! THIS APPLIANCE MUST BE EARTHED!
200 - 208 - 230 - 240 V~
26
1 = Expression 10
2 = thermistor (sensor)
3 = CC/h1/EC50
4 = external switch
5 = RB 30
5
4*
A B 11 12 13 14 15 16 17 18 19 20 21
2
5
G
5
L L L N A B C D U V W Z X Y
1 2 3 4 5 6
1 2 3
4
40 41 B B
1
1
G
U V W Z X Y
1 2 3 4 5 6
2
200-240 V~
3
5
3 x TAB
3 x 1.5 mm²
3
11 12 13 14 15 16
3 x 0.2 mm² (AWG 24)
2 x 0.5 mm² (AWG 20)
7 x TAB
3 x 1.5mm²
6 x 0.2 mm² (AWG 24)
200-240 V~
4* See wiring diagram delivered
with the External Switch
1.5 mm²
WARNING! THIS APPLIANCE MUST BE EARTHED!
400 - 415 - 440 V 3~
10
27 12 == Expression
TS 16-3
2
G
L L L U V W
1 2 3 1 2 3
400-440 V 3~
G
2
L L L N U V W
1 2 3
1 2 3
1
Y6
X5
Z4
W3
V2
U1
10
29 12 == Expression
TS 30-03, TS 30-012
10
28 12 == Expression
TS 16-3 B
G
WARNING! THIS APPLIANCE MUST BE EARTHED!
400-440 V 3~
2
G
1
Y6
X5
Z4
W3
V2
U1
Max 500 W
2.5 mm²
2
2
L L L A B C D
1 2 3
U V W Z X Y
1 2 3 4 5 6
G
WARNING! THIS APPLIANCE MUST BE EARTHED!
400-440 V 3~
1
Y6
X5
Z4
W3
V2
U1
WARNING! THIS APPLIANCE MUST BE EARTHED!
G