CSRN-XHE 362-904

Transcription

CSRN-XHE 362-904
PACKAGED
362 - 904
®
CSRN-XHE 362-904
HIGH EFFICIENCY "ROOF TOP" AIR COOLED HEAT PUMP
• REDUCED ENERGY CONSUMPTION
• COMPACT DIMENSIONS
• ENERGY RECOVERY STANDARD (CONSTRUCTION
CONFIGURATION C)
Cooling
Heating
[kW]
[kW]
362
119
116
402
130
130
452
140
142
464
159
155
524
177
174
604
205
200
704
228
225
804
275
276
904
301
302
Performance data are referred to operation with 30% of fresh air intake and same
amount of air exhaust.
The CSRN-XHE series of autonomous roof-top air conditioners, air-air heat pump, is a turning point in this type
of unit. Intended for air conditioning of large surface areas with average traffic, such as supermarkets, shopping malls, trade fair pavilions, airports, stations, and manufacturing areas), it contains the very latest technology, featuring:
VERSATILITY OF USE The wide range of versions, options and accessories allow unique integration and
flexibility of choice, regardless of the intended use and the external climate.
EASE OF POSITIONING AND INSTALLATION The units are exceptionally compact, perfect for positioning on
especially crowded roofs. Attention to client needs and care for details has led to the creation of a machine
than can be quickly installed and immediately commissioned.
REDUCED OPERATING COSTS These are now guaranteed thanks to the high efficiency of the innovative
refrigeration circuit for operation at partial load, of the freecooling and of the heat recovery, standard on all
models equipped with air expulsion, of the optional electrostatic air filters.
CERTIFIED QUALITY SYSTEM UNI EN ISO 9001:2008
BT08A006GB-04
Size
REPLACE: BT08A006GB-02
CSRN-XHE 362 - 904 (R-410A)
PACKAGED
362 - 904
GENERAL DESCRIPTION
MAIN FUNCTIONS AND APPLICATIONS
The CSRN-XHE autonomous roof-top air conditioners are highefficiency air-air heat pumps with completely automatic operation.
Based on user settings, the unit provides complete air treatment
through ventilation, filtering, cooling, possible heating, complete or
partial addition of fresh air, possibility to control humidity. These
machines are extremely compact and resistant to atmospheric
agents, suitable for outdoor installation on a flat roof, on a platform or
on the ground. The distribution of treated air (to be handled by the
client) takes place via supply and return ducts and suitable
distribution devices such as air outlets or nozzles. They are therefore
perfect for air conditioning of large-volume rooms with average
traffic, such as large commercial surfaces, trade fair pavilions,
airports, stations, and production areas.
VERSATILITY OF USE
APPLICATIONS
VERSATILE POSITIONING: ON FLAT ROOF, ON PLATFORM
ON GROUND
The wide range of models and the possibility to choose the
constructive configurations make it possible to select the product that
is best suited to the needs of each installation and to integrate the
unit into various architectonic contexts. The selection of accessories
completes the possibility to customize the product according to the
needs of the client.
EXTREME COMPACTNESS
The original layout of the sections that make up the machine
substantially reduces its footprint, making it easier to position and
leaving more space available for parking, additional equipment
rooms or other uses. This also reduces the time required for the
positioning of the ducts on the various sides of the unit, since its
great compactness allows its complete rotation (which is very difficult
with traditional units with in-line extension).
REDUCTION OF CONSUMPTION AND OPERATING COSTS
BT08A006GB-03
The roof-top units of the XHE series were created with the objective
of always operating at maximum energy savings through an
extremely intelligent and advanced control of power provided only
when it is needed, especially during frequent conditions of operation
at partial load. The use of the free-cooling device and the adoption of
thermodynamic recovery on the expelled air make it possible to
further reduce operating costs. Since ventilation represents one of
the greatest factors of energy consumption, special attention has
been given to the efficiency of the ventilation system through careful
selection of components and limitations of internal pressure drops.
The limitation of the emissions of carbon dioxide and respect for the
environment are guiding thoughts of Clivet which, through the
implementation of modern technical solutions, pursues the reduction
of energy consumption.
EASY MAINTENANCE
The entire series is designed with highly reliable industrial
components that are easily accessible and available if maintenance
is required. It is also equipped with self-diagnosis and safety devices
that ensure its proper operation while at the same time protecting
users.
2
APPLICATION EXAMPLES
PACKAGED
362 - 904
GENERAL DESCRIPTION OF CONFIGURATIONS AVAILABLE IN CATALOGUE
The CSRN-XHE range of air conditioners can be extensively personalised and is available in two configurations.
Both configurations are capable of conditioning air flow rates with mixtures of return air and fresh air. The machines are extremely versatile, since they have three air flow modes: high, standard, and low. The units can be further personalized with the choice of accessories (optional) that are specially designed to meet various application
needs.
CB - MANUFACTURER VERSION B WITH MIXING, RECIRCULATION AND FRESH AIR CHAMBER
The standard constructional configuration, called version B, allows control of supply and return air flow and the
intake of fresh air for required refreshing by means of a manually operated shutter.
The version with optional setups is equipped with shutters with a servo-motor for constant adjustment of the
refresh air mixture:
- operation with a fixed percentage of refresh air with opening or closing of the shutter by means of an actuator
(ON-OFF) which intervenes when ventilation is active (optional)
- operation with variable percentage of refresh air with opening and closing of the shutters by means of
modulating actuators driven by the signal of the air quality probe (optional)
- operation with variable percentage of refresh air with opening and closing of the shutters by means of
modulating actuators, which intervene when the fresh air conditions are such that they allow lowering of internal
thermal loads simply by placing primary air in the room (free-cooling B) (optional).
CONFIGURATION B WITH FREE COOLING
VERSION B
CONFIGURATION B STANDARD OR WITH SHUTTER ON-OFF
OR WITH MODULATING SHUTTER
SUPPLY
+
-
RETURN
70%
SUPPLY
30%
+
-
70%
RETURN
30%
MAN
AUT
FRESH AIR
FRESH AIR
CC - MANUFACTURER VERSION C WITH MIXING, EXPULSION, HEAT RECOVERY AND FREE COOLING
BT08A006GB-03
When the machine is in optional constructive configuration (called version C), it allows automatic management of
the supply and return air flows, and the intake of fresh air for required refreshing. In addition, it is capable of
expelling the return air from the served room by means of dedicated fans and to recover the energy of the
expelled air.
The automatic adjustment of the shutters allows operation of the unit:
- with full recirculation
- with a mixture of re-circulation air and refresh air
- with all refresh air and total expulsion of return air (total free-cooling).
CONFIGURATION C WITH MODULATING SHUTTERS
EXHAUST AIR
- +
30%
SUPPLY
+
-
70%
RETURN
30%
FRESH AIR
3
PACKAGED
362 - 904
CONFIGURATION CODE
(1)
CSRN - XHE
C
(2)
452
( 3)
M
B
(4)
200
M
(5)
R
---
100
---
R
C
(1) CONSTRUCTIONAL CONFIGURATION
(5) INTAKE STATIC PRESSURE VALUE
recirculated/outside air mixing box (B)
free cooling version with extract/recirculated/fresh air intake box (C)
(6) AIR FLOW
Standard (S)
Standard air flow (SM)
Reduced air flow (RM)
Air flow high (HM)
(3) OUTLET STATIC PRESSURE VALUE
(7) INTAKE AIR FLOW
(4) RETURN
Standard air flow (SR)
Reduced air flow (RR)
Air flow high (HR)
(2) SUPPLY
Standard (S)
(6)
SM
(7)
SR
SM
SR
RM
RR
HM
HR
UPDATED ELECTRONIC CONTROL
The operation of the unit is fully automatic thanks to the Clivet Talk electronic
adjustment system. This is a modular device, of automatic origins, with high
speed and reliability and control logic specifically designed for this type of
product. The user interface is easy to use.
This allows better use of available resources, extending the life cycle of the
components and thus reducing maintenance costs. With the micro-processor
keypad, it is possible to perform daily/weekly programming of the set-point, as
well as start-up or shutdown of the machine.
The unit can also be connected to supervision systems using clean contacts or by
serial with the standards of communication most commonly available on the
market.
CONTROL LOGICS IN THE EVENT OF ALARM SIGNAL
Machine logics
BT08A006GB-03
(1)Complete shutdown
(2)Room kept de-pressurized
(3)Room kept pressurized
Vers. B with freecooling option
Description
Version B standard
Version C
Supply fan
Off
Off
Off
Return fan
-
-
Off
Fresh air Shutter
Open
Closed
Closed
Discharge camper
-
-
Closed
Recirculation shutter
-
Closed
Closed
Supply fan
-
-
Off
Return fan
-
-
On
Fresh air Shutter
-
-
Closed
Discharge camper
-
-
Open
Recirculation shutter
-
-
Closed
Supply fan
On
On
On
Off
Return fan
-
-
Fresh air Shutter
Open
Open
Open
Discharge camper
-
-
Closed
Recirculation shutter
-
Closed
Closed
The machine logic manages the signal from a fire detection unit, implementing one of the actions shown in the table which can be set as a parameter. If there is an
alarm signal and according to the set logic, the compressors are always shut off. The roof-top units may not be used as smoke extractors.
4
PACKAGED
362 - 904
ELECTRONIC EXPANSION VALVE
The electronic expansion valve is an essential component of the refrigerant circuit.
It offers a number of advantages as compared to the traditional thermostatic valve.
These include:
- reduction of overheating temperature (greater efficiency of refrigerant circuit)
- improved compressor working conditions (COP optimized)
- reduction of output temperature of the compressor
- reduction of pressure at condenser (less energy absorbed by compressors)
- adaptation to all load conditions and transitories without causing swinging at
partial loads
All this aids in increasing the efficiency of the load for any thermal load condition
and to extend the life cycle.
LOW EFFICIENCY
DANGER OF BREAKAGE OVERHEATING
HIGH EFFICIENCY
OPTIMAL OPERATION
LOW EFFICIENCY
P = Provided Power Variation
EEV= Electronic valve
TEV = Thermostatic valve
DANGER OF BREAKAGE PRESENCE OF LIQUID
FC - THERMAL FREE COOLING (CONSTRUCTION CONFIGURATION C)
BT08A006GB-03
As soon as external conditions allow it, the unit is capable of automatically activating
free-cooling mode, which, by keeping the compressors off and drawing in suitably
filtered fresh air, cools the served room.
The fresh air flow can be varied based on actual needs.
This operating mode is especially useful in spring and autumn or with high ambient
loads. It allows substantial reduction of the unit's energy consumption and wear of the
compressors.
OUTSIDE TEMPERATURE PROBE
The measurement of the temperature of outside air is an essential
parameter of heat adjustment. It takes place via a probe located
in a special compartment that connects the external environment
and the return duct (always in negative pressure).
Clivet has chosen this solution to ensure correct measurement of
temperature since the probe is constantly in contact with a
minimum flow of air. On request, the temperature probe can be
integrated with the optional humidity probe).
INTAKE DUCT
FRESH AIR
OUTSIDE TEMPERATURE PROBE
5
PACKAGED
362 - 904
VERY HIGH EFFICIENCY AT PARTIAL LOAD
In air conditioning projects, the choice of the unit is made based on the maximum load of the room to be served.
In practice, over the course of the year these operating conditions are limited to short periods of time, whereas
operation at partial loads is the actual normal operating condition. The need to adapt the power provided to the
load requested becomes essential in limiting energy consumption.
This is why we have decided to couple two scroll compressors of different power on a single refrigeration circuit,
thus obtaining very high efficiency.
The electronic control that the machine is equipped with divides compressor operation into three steps of power
(1/3, 2/3, 3/3). This limits the oscillation of the air temperature, and provides perfect adaptation to partial load,
offering substantial energy savings.
%%
WORKING
Tempo diTIME
lavoro
FOR
Per90%
il 90OF
% THE
del
TIME, LOAD IS
tempo
il
carico
LESS THAN 80% è
8
7
6
EER
5
4
inferiore al80%
100%
90%
80%
FOR
Per70%
il 70OF
% THE
del
TIME, LOAD IS
tempo il carico è
LESS THAN 50%
inferiore al50%
70%
60%
50%
40%
3
30%
2
20%
1
10%
0
0%
<20%
(1)
(2)
(1)
<30%
(3)
(2)
<40%
<50%
<60%
(3)
<70%
<80%
<90%
<100%
Carico termico
%%
THERMAL
LOAD
(1)
WITH THE
SMALL
COMPRESSOR
6.4 =TAGLIA
EER = 7.4
(1)OPERATION
FUNZIONAMENTO
CON
SOLO
COMPRESSORE
INFERIORE 6.4 = EER = 7.4
(2)
WITH THE
BIGSOLO
COMPRESSOR
4.9 = EER
= 5.9 SUPERIORE 4.9 = EER = 5.9
(2)OPERATION
FUNZIONAMENTO
CON
COMPRESSORE
TAGLIA
(3) OPERATION WITH BOTH COMPRESSORS 3.7 = EER = 4.8
(3) FUNZIONAMENTO CON ENTRAMBI I COMPRESSORI 3.7 = EER = 4.8
APPROXIMATE VALUES
VALORI INDICATIVI
SELF-ADAPTABILITY
Thanks to the automatic adjustment of the operating parameters based on the system load conditions, the unit is
capable of optimizing its own efficiency, reducing the resulting consumption and extending the life-cycle of the
components.
The temperature range to be maintained in the room can be set by the user (manual set-point) or managed by the
machine logic (automatic set-point). When AUTOMATIC,mode is set, the working set-points are calculated
automatically and dynamically by the thermal control device based on the outside temperature and other
parameters set during commissioning of the machine, thus avoiding thermal shock between the treated room and
the exterior.
BT08A006GB-03
COOLING SET POINT
AD
DE
E
ON
Z
ZONE
DEAD
HEATING SET POINT
EXTERNAL AIR TEMPERATURE
6
THE GRAPH SHOWS THE TREND OF THE
CURVES OF THE HOT SET POINT (BOTTOM
LINE) AND OF THE COLD SET POINT (UPPER
LINE) BASED ON THE OUTSIDE TEMPERATURE. THE HIGHLIGHTED TEMPERATURE VALUES ARE THOSE SET AS DEFAULT, BUT
THEY MAY BE CHANGED ACCORDING TO
CLIENT NEEDS.
PACKAGED
362 - 904
DEMAND LIMIT
[kW]
AVAILABLE POWER
The Demand Limit function is a logic that controls the machine's resources dedicated to limiting the input power
from the electrical mains (for example when there are special agreements between the user and the operator of
the electrical mains) or to selecting the thermal resources to be used based on special needs of the client.
The Demand Limit device can control and manage the available steps of thermal power by means of the receipt of
an external analogue signal, 0-10V/4-20mA.
The control logic does not act on the ventilation which is therefore always ensured.
The greater the input signal to the Demand Limit, the less the thermal power available for the system. In the
extreme condition of pilot signal at 100%, the system can also shut off the last power step.
AS THE DEMAND LIMIT SIGNAL INCREASES, THE
POWER STEPS ARE GRADUALLY DISABLED. WHEN
THE SIGNAL IS AT 100%, ALL AVAILABLE RESOURCES ARE DISABLED.
AUXILIARY ELECTRIC HEATING ELEMENTS
AUXILIARY ELECTRIC HEATING ELEMENTS
6
0
2
4
6
8
10
[V]
SIGNAL 0-10V DC
SFSTRV - FAN BREAKAWAY STARTING CURRENT REDUCING DEVICE.
A device which allows the fans to start up gradually and accelerate steadily until
the rated speed is reached. This electronic device is able to decrease the starting
torque of the motor, reducing the absorbed current on start-up, at the same time
protecting the motor and the transmission members (belts and bearings) from
heavy stresses, thus guaranteeing an extended life for the components. During
shut-off, the device allows the speed to be reduced gradually.
T
BT08A006GB-03
nominal operating point
THE BROKEN LINE INDICATES THE MOTOR
TORQUE AS SPEED INCREASES THE SOLID
LINE INDICATES THE MOTOR TORQUE AS
SPEED INCREASES WITH SOFT STARTER
RPM
I
nominal operating point
RPM
THE BROKEN LINE INDICATES THE NORMAL
CURRENT ABSORPTION ON INCREASE OF
THE FAN SPEED. THE SOLID LINE SHOWS THE
PLOT OF THE CURRENT ON INCREASE OF
FAN SPEED WITH SOFT STARTER.
7
PACKAGED
362 - 904
NEW GENERATION OF AXIAL FANS FOR THE EXTERNAL SECTION
The need for continuous improvement in machine performance has led to collaboration with specialized European
laboratories for the development of more efficient axial fans. The result of this research has made it possible to
develop an innovative winglet-type profile at the end of the blade. The adoption of the new profiles has made it
possible to obtain substantial results in noise limitation, with an average reduction of 6 dB(A), and energy savings,
with a reduction in consumption of 10%.
TRADITIONAL FAN
FAN WITH WINGLETS
DEVICE TO REDUCE CONSUMPTION OF FANS OF THE EXTERNAL SECTION
The device makes it possible to control the external axial fans, adjusting their speed of
rotation based on the condensation pressure. When fresh air temperature is low, a
minimum air flow rate is required to hold down the condensation pressure. Therefore,
at low fresh air temperatures, fan rotation speed is reduced, resulting in reduced
energy consumption (low temperature device).
In heat pump mode, this device reduces the speed of rotation of the fans when
external air temperatures are high (high temperature device).
BT08A006GB-03
ICE PROTECTION SYSTEM
ICE PROTECTION SYSTEM is a special measure for the refrigeration circuit that
reduces the risk of the formation of ice at the base of the external coil. A liquid undercooling circuit maintains the temperature of the lower part of the coil, preventing the
formation of a block of ice and avoiding risk of breakage due to freezing.
SMART MANAGEMENT OF DEFROSTS
During operation in heat-pump mode, the defrost cycles are managed with an advanced,
predictive logic that reduces both frequency and duration. The innovative control system
makes it possible to activate defrost cycles and to adjust their duration based on actual
needs, by measuring not only the outside temperature but also the gradient of evaporation
pressure. As a result, overall performance of the machine is improved and there is a
reduction in the negative effect that defrost cycles have on supply air temperatures.
8
PACKAGED
362 - 904
FILTRATION
Standard units are standard equipped with a suitable filtering
section composed of pleated filters, class G4, with an ample
surface. They are easily accessible for periodic maintenance.
PANELLING
The need to improve access to the internal parts of the machine for
the ordinary maintenance and at the same time the need to give
structural stiffness and increase thermal insulation has brought to the
adoption of "sandwich" type panels on all units.
The roof and the structure of the air treatment area are made with
such panels with dual steel walls with polyurethain foam and feature
seal gaskets alongside the ledge. The panels are hinged and feature
handles
and
closures
wi t h
adjustable
clamping.
RE1 - ENERGY RECOVERY OF EXPELLED AIR (VERSION C)
BT08A006GB-03
The energy contained in the expelled air is recovered by forcing the air flow to pass through the external
packaged finned heat exchanger. This makes it possible to reduce the electrical energy absorbed by the
compressors, to increase the overall efficiency of the unit and to extend its operating limits. This thermodynamic
recovery system does not increase electrical energy consumption for ventilation, as instead happens for recovery
with crossed or rotating flows. Greater use of electricity, caused by the enormous pressure drops on the air side in
recovery systems with crossed or rotating flows, often nullifies the amount of energy recovered and even exceeds
it in some cases.
9
PACKAGED
362 - 904
AIR FLOW: STANDARD
GENERAL TECHNICAL SPECIFICATIONS
Size
362
402
452
464
524
604
704
804
904
COOLING
Cooling capacity
Sensible capacity
Compressor power input
EER
HEATING
1
1
1
1
kW
kW
kW
118,6
84,7
27,2
4,36
129,7
93
31,6
4,11
139,6
97,7
36,4
3,84
158,7
115,6
34,8
4,56
177,4
127,6
42,3
4,19
205,2
150,8
47,5
4,32
227,8
165,5
57,1
3,99
275,2
204,4
60,4
4,56
300,6
220,2
69,5
4,32
Heat output
Compressor power input
COP
COMPRESSOR
2
2
2
kW
kW
116,1
21,8
5,32
130,3
25,4
5,12
142
28,7
4,95
154,8
28,3
5,47
173,5
33,8
5,14
200,4
37,2
5,38
224,5
43,9
5,12
275,5
49,2
5,6
302,3
55,5
5,45
Type of compressors
No. of Compressors
Std Capacity control steps
Refrigerant circuits
AIR HANDLING SECTION FANS (OUTLET)
3
Nr
Nr
Nr
Scroll
2
3
1
Scroll
2
3
1
Scroll
2
3
1
Scroll
4
6
2
Scroll
4
6
2
Scroll
4
4
2
Scroll
4
6
2
Scroll
4
6
2
Scroll
4
6
2
Type of fans
Number of fans
Number of impellers
Air flow
Installed unit power
Max outside static pressure
Max outside static pressure
FANS (RETURN)
4
Nr
Nr
l/s
kW
Pa
Pa
CFG
1
2
5555
7,5
300
570
CFG
1
2
6111
7,5
210
570
CFG
1
2
6666
9
210
570
CFG
1
2
8056
9
240
570
CFG
1
2
9028
11
210
570
CFG
1
2
10000
15
330
510
CFG
1
2
11111
18,5
300
570
CFG
1
2
12500
18,5
330
570
CFG
1
2
13889
22
270
570
Type of fans
Number of fans
Air flow
Installed unit power
Max outside static pressure
Max outside static pressure
EXTERNAL SECTION FANS
7
Nr
l/s
kW
Pa
Pa
CFG
1
4444
3
210
450
CFG
1
4888
3
120
450
CFG
1
5333
4
120
450
CFG
1
6444
4
150
420
CFG
1
7222
5,5
180
420
CFG
1
8000
7,5
240
450
CFG
1
8889
7,5
120
450
CFG
1
10000
7,5
120
450
CFG
1
11111
11
210
450
Type of fans
Number of fans
Fan diameter
Fan RPM
Standard air flow
Installed unit power
POWER SUPPLY
10
Nr
mm
rpm
l/s
kW
AX
2
800
880
11528
2
AX
2
800
880
11528
2
AX
2
800
880
11528
2
AX
4
800
880
23585
2
AX
4
800
880
23585
2
AX
4
800
880
23585
2
AX
4
800
880
23585
2
AX
6
800
880
33410
2
AX
6
800
880
33410
2
V
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
Standard power supply
5
6
8
9
BT08A006GB-03
Performance data are referred to operation with 30% of fresh air intake and same amount of air exhaust. (construction configuration C)
(1) Ambient temperature 27°C/19.5 WB external exchanger air intake 35°C
EER referred only to compressors
(2) ambient temperature 20°C DB. Outside temperature 7°C DB/6 WB
COP referred only to compressors
(3) SCROLL = scroll compressor
(4) CFG = centrifugal fan
(5) with standard electric motors
(6) with uprated electric motors
(7) Constructional configuration C
CFG = centrifugal fan
(8) with standard electric motors
(9) with uprated electric motors
(10) AX = axial-flow fan
10
PACKAGED
362 - 904
CONSTRUCTIONAL CONFIGURATION: MIXING BOX FOR RECYCLE /FRESH AIR (B)
ELECTRICAL DATA
Size
362
402
452
464
524
604
704
804
904
36,5
30,6
4,1
n.d.
75,8
44,9
30,6
4,1
n.d.
84,2
44,9
36,5
4,1
n.d.
90,1
30,6
15,2
30,6
15,2
4,1
n.d.
108,5
30,6
22,6
30,6
22,6
4,1
n.d.
123,3
30,6
30,6
30,6
30,6
4,1
n.d.
139,3
36,5
30,6
36,5
30,6
4,1
n.d.
151,1
44,9
30,6
44,9
30,6
4,1
n.d.
176,1
44,9
36,5
44,9
36,5
4,1
n.d.
187,9
L.R.A. - Compressor 1
A
225
L.R.A. - Compressor 2
A
173
L.R.A. - Compressor 3
A
L.R.A. - Compressor 4
A
F.L.I. FULL LOAD POWER INPUT AT MAX ADMISSIBLE CONDITION
272
173
-
272
225
-
173
95
173
95
173
118
173
118
173
173
173
173
225
173
225
173
272
173
272
173
272
225
272
225
27,3
17
1,9
n.d.
48,4
27,3
22,6
1,9
n.d.
54
17
8,9
17
8,9
1,9
n.d.
59,7
17
13,2
17
13,2
1,9
n.d.
68,3
17
17
17
17
1,9
n.d.
75,9
22,6
17
22,6
17
1,9
n.d.
87,1
27,3
16,9
27,3
16,9
1,9
n.d.
100,3
27,3
22,6
27,3
22,6
1,9
n.d.
111,5
F.L.A. - FULL LOAD CURRENT AT MAX ADMISSIBLE CONDITIONS
F.L.A. - Compressor 1
F.L.A. - Compressor 2
F.L.A. - Compressor 3
F.L.A. - Compressor 4
F.L.A. - Single External Fan
F.L.A. - Single supply fan
F.L.A. - Total
L.R.A. LOCKED ROTOR AMPERES
F.L.I. - Compressor 1
F.L.I. - Compressor 2
F.L.I. - Compressor 3
F.L.I. - Compressor 4
F.L.I. - Single External Fan
F.L.I. - Single supply fan
F.L.I. - Total
1
2
3
4
A
A
A
A
A
A
A
kW
kW
kW
kW
kW
kW
kW
22,6
17
1,9
n.d.
43,7
power supply: 400/3/50 Hz +/-6%
voltage unbalance: max 2 %
Values not including accessories
(1) n.d. = not defined
The input of the fan motors is shown in the performance tables of the fans
The installed motor must be determined taking into consideration the air flow rate and the usable static pressure
(2) value including all standard components of the unit control circuit included
This data does not take into consideration the motors of the zone treatment fans nor the accessories to obtain the overall F.L.A. value, add the total F.L.A. value to that of any accessories
(see electrical data of accessories) and that of the motors of the treatment area fans (see table of fan performance)
(3) n.d. = not defined
The input of the fan motors is shown in the performance tables of the fans
The installed motor must be determined taking into consideration the air flow rate and the usable static pressure
(4) value including all standard components of the unit control circuit included
This data does not take into consideration the motors of the zone treatment fans nor the accessories to obtain the overall F.L.I. value, add the total F.L.I. value to that of any accessories (see
electrical data of accessories) and that of the motors of the treatment area fans (see table of fan performance)
CONSTRUCTIONAL CONFIGURATION: FREE COOLING VERSION WITH EXTRACT/RECIRCULATED/FRESH AIR INTAKE BOX (C)
ELECTRICAL DATA
Size
362
402
452
464
524
604
704
804
904
36,5
30,6
4,1
n.d.
n.d.
75,8
44,9
30,6
4,1
n.d.
n.d.
84,2
44,9
36,5
4,1
n.d.
n.d.
90,1
30,6
15,2
30,6
15,2
4,1
n.d.
n.d.
108,5
30,6
22,6
30,6
22,6
4,1
n.d.
n.d.
123,3
30,6
30,6
30,6
30,6
4,1
n.d.
n.d.
139,3
36,5
30,6
36,5
30,6
4,1
n.d.
n.d.
151,1
44,9
30,6
44,9
30,6
4,1
n.d.
n.d.
176,1
44,9
36,5
44,9
36,5
4,1
n.d.
n.d.
187,9
L.R.A. - Compressor 1
A
225
L.R.A. - Compressor 2
A
173
L.R.A. - Compressor 3
A
L.R.A. - Compressor 4
A
F.L.I. FULL LOAD POWER INPUT AT MAX ADMISSIBLE CONDITION
272
173
-
272
225
-
173
95
173
95
173
118
173
118
173
173
173
173
225
173
225
173
272
173
272
173
272
225
272
225
27,3
17
1,9
n.d.
n.d.
48,4
27,3
22,6
1,9
n.d.
n.d.
54
17
8,9
17
8,9
1,9
n.d.
n.d.
59,7
17
13,2
17
13,2
1,9
n.d.
n.d.
68,3
17
17
17
17
1,9
n.d.
n.d.
75,9
22,6
17
22,6
17
1,9
n.d.
n.d.
87,1
27,3
16,9
27,3
16,9
1,9
n.d.
n.d.
100,3
27,3
22,6
27,3
22,6
1,9
n.d.
n.d.
111,5
F.L.A. - Compressor 1
F.L.A. - Compressor 2
F.L.A. - Compressor 3
F.L.A. - Compressor 4
F.L.A. - Single External Fan
F.L.A. - Single supply fan
F.L.A. - Single Inlet fan
F.L.A. - Total
L.R.A. LOCKED ROTOR AMPERES
F.L.I. - Compressor 1
F.L.I. - Compressor 2
F.L.I. - Compressor 3
F.L.I. - Compressor 4
F.L.I. - Single External Fan
F.L.I. - Single supply fan
F.L.I. - Single Inlet fan
F.L.I. - Total
1
1
2
3
3
4
A
A
A
A
A
A
A
A
kW
kW
kW
kW
kW
kW
kW
kW
22,6
17
1,9
n.d.
n.d.
43,7
BT08A006GB-03
F.L.A. - FULL LOAD CURRENT AT MAX ADMISSIBLE CONDITIONS
power supply: 400/3/50 Hz +/-6%
voltage unbalance: max 2 %
Values not including accessories
(1) n.d. = not defined
The input of the fan motors is shown in the performance tables of the fans
The installed motor must be determined taking into consideration the air flow rate and the usable static pressure
(2) value including all standard components of the unit control circuit included
This data does not take into consideration the motors of the zone treatment fans nor the accessories to obtain the overall F.L.A. value, add the total F.L.A. value to that of any accessories (see
electrical data of accessories) and that of the motors of the treatment area fans (see table of fan performance)
(3) n.d. = not defined
The input of the fan motors is shown in the performance tables of the fans
The installed motor must be determined taking into consideration the air flow rate and the usable static pressure
(4) value including all standard components of the unit control circuit included
This data does not take into consideration the motors of the zone treatment fans nor the accessories to obtain the overall F.L.I. value, add the total F.L.I. value to that of any accessories (see
electrical data of accessories) and that of the motors of the treatment area fans (see table of fan performance)
11
PACKAGED
362 - 904
ELECTRICAL INPUT OF OPTIONAL COMPONENTS
To obtain the electrical input of the unit including accessories, add the standard data in Electrical Data table to
those for the selected accessories.
SIZE
F.L.A. FULL LOAD CURRENT
F.L.A. EH20 - 24 kW electric heaters
F.L.A. EH24 - 36 kW electric heaters
F.L.A. EH28 - 48 kW electric heaters
F.L.A. EH72 - 72 kW electric heaters
F.L.A. EH33 - 96 kW electric heaters
F.L.A. HSE8 - Electrode boiler steam humidifier from 8 kg/h
F.L.A. HSE9 - Electrode boiler steam humidifier from 15 kg/h
F.L.A. FES - High efficiency H10 electrostatic air filter
F.L.I. FULL LOAD POWER
F.L.I. EH20 - 24 kW electric heaters
F.L.I. EH24 - 36 kW electric heaters
F.L.I. EH28 - 48 kW electric heaters
F.L.I. EH72 - 72 kW electric heaters
F.L.I. EH33 - 96 kW electric heaters
F.L.I. HSE8 – Electrode boiler steam humidifier from 8 kg/h
F.L.I. HSE9 - Electrode boiler steam humidifier from 15 kg/h
F.L.I. FES – High efficiency H10 electrostatic air filter
362
402
452
464
524
604
704
804
904
A
A
A
A
A
A
A
A
34.6
52.0
69.4
8.7
16.2
2.2
34.6
52.0
69.4
8.7
16.2
2.2
34.6
52.0
69.4
8.7
16.2
2.2
52.0
69.4
104.0
138.6
16.2
2.2
52.0
69.4
104.0
138.6
16.2
2.2
52.0
69.4
104.0
138.6
16.2
2.2
52.0
69.4
104.0
138.6
16.2
2.2
69.4
104.0
138.6
16.2
2.2
69.4
104.0
138.6
16.2
2.2
kW
kW
kW
kW
kW
kW
kW
kW
24
36
48
6
11.25
0.5
24
36
48
6
11.25
0.5
24
36
48
6
11.25
0.5
36
48
72
96
11.25
1
36
48
72
96
11.25
1
36
48
72
96
11.25
1
36
48
72
96
11.25
1
48
72
96
11.25
1.25
48
72
96
11.25
1.25
CALCULATION OF BREAKAWAY CURRENT (M.I.C.)
The calculation of the breakaway current (M.I.C.) is necessary in order to size the protection up the electrical line
from the unit. Its value depends on the selected configuration and the components selected (motor sizes). The
M.I.C. is obtained by summing the maximum breakaway current (L.R.A.) of the largest compressor and the input
current at the maximum admissible conditions (F.L.A.) of the remaining electrical components.
M.I.C.
L.R.A.(C1) F.L.A.(C2)
F.L.A.(C3)
F.L.A.(C4)
F.L.A.(Fan Ext.) N (Fan Ext.)
F.L.A.(Fan Intake) F.L.A.(Fan Return)
L.R.A. (C1) = breakaway current of the larger size compressor (Tandem 1).
F.L.A. (C2) = input current of the smaller size compressor (Tandem 1).
F.L.A. (C3) = input current of the larger size compressor (Tandem 2).
F.L.A. (C4) = input current of the smaller size compressor (Tandem 2).
F.L.A.(Fan Ext.) = current absorbed by the fan of the external section.
No. (Fan Ext.) = number of fans of external section.
F.L.A.(Fan Intake) = input current of supply fan.
F.L.A.(Fan Return) = input current of return fan (only for version C).
Example of calculation of the M.I.C. for units size 464 configuration C with standard supply fan (9 kW) and standard return fan (4 kW):
BT08A006GB-03
M.I.C. = 173.0 + 15.2 + 30.6 + 15.2 + [4.1 x 4] + 19 + 8.3 = 277.7 A
12
PACKAGED
362 - 904
SOUND LEVELS
Air flow: standard
Sound Power Level (dB)
Size
Octave band (Hz)
Sound
pressure
level
Sound
power level
63
125
250
500 1000 2000 4000 8000
dB(A)
dB(A)
362
91
84
90
87
87
83
78
69
71
91
402
92
85
91
88
87
84
78
66
72
92
452
93
86
92
89
88
85
79
68
72
93
464
101
97
100
90
86
77
72
69
73
94
524
106
97
97
93
89
83
78
75
74
94
604
106
97
97
93
89
83
78
75
74
94
704
108
98
97
94
89
83
78
76
75
95
804
107
100
100
93
92
85
79
78
77
97
904
108
102
101
95
93
86
80
79
77
98
The sound levels are referred to units working at full load
in nominal conditions. The sound pressure level is referred
at a distance of 1 m. from the ducted unit surface working
in free field conditions.External static pressure 50 Pa.
(standard UNI EN ISO 3744)
Please note that when the unit is installed in conditions
other than nominal test conditions (e.g. near walls or
obstacles in general), the sound levels may undergo
substantial variations.
OPERATING LIMITS (COOLING)
THE LIMITS ARE INDICATIVE AND HAVE BEEN CALCULATED CONSIDERING:
- VALUES GENERAL AND NOT SPECIFICATIONS,
- STANDARD AIR FLOW-RATE,
- NON-CRITICAL POSITIONING AND CORRECT USE OF THE UNIT,
- OPERATION AT FULL LOAD
WITH UNIT OPERATING IN INTAKE OF OUTSIDE AIR CALCULATE THE TEMPERATURES OF MIXES WHICH ARE GENERATED FROM THE EXCHANGERS' INLET TO KNOW
THE LIMITS.
TO = TEMPERATURE OF AIR ENTERING THE EXTERNAL EXCHANGER D.B.(°C)
DB = DRY BULB
TA = INTERNAL EXCHANGER INLET AIR TEMPERATURE W.B. (°C)
WB = WET BULB
(1) THE DASHED AREA REFERS TO THE FIELD OF UNITS OPERATION
STANDARD
(2) IN THE CROSS-HATCHED AREA IS IDENTIFIED THE UTILITY FIELD FOR UNIT WITH
LOW TEMPERATURE DEVICE
30
Ta (W.B.)
25
(2)
20
(1)
15
10
5
0
5
10
15
20
25
30
35
40
45
50
To (D.B.)
30
25
To (D.B.)
20
(1)
15
(2)
10
5
0
-5
-15
-10
-5
0
Ta (W.B.)
5
10
15
20
THE LIMITS ARE INDICATIVE AND HAVE BEEN CALCULATED CONSIDERING:
- VALUES GENERAL AND NOT SPECIFICATIONS,
- STANDARD AIR FLOW-RATE,
- NON-CRITICAL POSITIONING AND CORRECT USE OF THE UNIT,
- OPERATION AT FULL LOAD
WITH UNIT OPERATING IN INTAKE OF OUTSIDE AIR CALCULATE THE TEMPERATURES OF MIXES WHICH ARE GENERATED FROM THE EXCHANGERS' INLET TO KNOW
THE LIMITS.
TO = TEMPERATURE OF AIR ENTERING THE INTERNAL EXCHANGER D.B.(°C)
DB = DRY BULB
TA = EXTERNAL EXCHANGER INLET AIR TEMPERATURE W.B. (°C)
WB = WET BULB
(1) THE DASHED AREA REFERS TO THE FIELD OF UNITS OPERATION
STANDARD
(2) INSIDE THE DOTTED AREA, THE UNIT CAN OPERATE ONLY FOR A LIMITED PERIOD OF TIME (MAX 1 HOUR)
IN EXTENDED OPERATING MODE, IN HEAT PUMP OPERATION WITH AN OUTSIDE AIR
TEMPERATURE OF LESS THAN 6°C, THE UNIT PERFORMS DEFROSTS BY REVERSING THE CYCLE, SO AS TO ELIMINATE THE ICE THAT FORMS ON THE SURFACES
OF THE OUTSIDE EXCHANGER; IN ADDITION, IN THE EVENT OF NEGATIVE TEMPERATURES, THE WATER RESULTING FROM THE DEFROSTS MUST BE DRAINED SO AS TO
AVOID THE ACCUMULATION OF ICE NEAR THE BASE OF THE UNIT. MAKE SURE THAT
THIS DOES NOT CONSTITUTE A DANGER FOR PEOPLE OR THINGS.
BT08A006GB-03
OPERATING LIMITS (HEATING)
13
PACKAGED
362 - 904
AIR FLOW: STANDARD
Size
362
402
452
464
524
604
704
804
904
5555
570
6111
570
6666
570
8056
570
9028
570
10000
510
11111
570
12500
570
13889
570
AIR HANDLING SECTION FANS (OUTLET)
Air flow
Max outside static pressure
l/s
Pa
COOLING PERFORMANCE
Size
Ta
(°C)
DB/WB
BT08A006GB-03
40
44
kWf
kWe
kWs
kWf
kWe
kWs
kWf
kWe
kWs
kWf
kWe
kWs
kWf
kWe
kWs
22 / 16
110,6
21,6
82,8
110,8
23,8
80,4
111,0
24,7
79,4
111,5
26,2
78,0
112,5
28,8
75,5
113,7
31,0
73,6
24 / 17
113,0
21,9
87,8
112,9
24,1
85,4
113,0
25,0
84,4
113,5
26,5
83,0
114,7
29,1
80,6
116,2
31,4
78,7
26 / 19
117,5
22,5
86,8
117,2
24,6
84,5
117,2
25,6
83,5
117,6
27,1
82,1
118,7
29,7
79,8
120,1
32,1
77,9
27 / 19,5
118,6
22,6
89,3
118,3
24,8
87,0
118,3
25,7
86,0
118,6
27,2
84,7
119,6
29,9
82,4
120,9
32,2
80,5
28 / 21
121,6
22,8
86,2
121,6
25,0
84,0
121,6
26,0
83,1
121,8
27,5
81,8
122,1
30,2
79,6
122,6
32,5
77,9
30 / 22
123,4
23,0
92,0
123,8
25,2
89,9
123,9
26,1
89,0
123,9
27,6
87,8
123,7
30,3
85,6
123,3
32,7
83,9
22 / 16
121,1
25,4
90,7
121,7
27,9
88,0
121,9
29,0
86,9
122,3
30,6
85,2
122,9
33,4
82,5
123,4
35,7
80,4
24 / 17
123,7
25,7
96,3
123,9
28,2
93,6
124,0
29,3
92,5
124,3
30,9
90,9
124,9
33,7
88,2
125,5
36,0
86,1
26 / 19
128,7
26,3
95,5
128,5
28,8
92,9
128,5
29,9
91,8
128,6
31,4
90,3
129,0
34,2
87,6
129,6
36,4
85,5
27 / 19,5
129,9
26,4
98,3
129,7
29,0
95,7
129,7
30,0
94,6
129,7
31,6
93,0
130,1
34,3
90,4
130,6
36,5
88,3
28 / 21
133,5
26,8
94,4
133,3
29,3
91,8
133,3
30,4
90,8
133,3
31,9
89,2
133,3
34,6
86,6
133,3
36,8
84,5
30 / 22
135,8
27,0
99,5
135,9
29,6
96,9
135,8
30,6
95,8
135,7
32,2
94,2
135,4
34,9
91,6
135,0
37,0
89,5
22 / 16
131,1
29,3
97,9
131,3
32,1
95,0
131,5
33,4
93,8
131,8
35,2
92,1
132,4
38,4
89,2
133,1
41,2
86,9
24 / 17
133,5
29,7
103,1
133,4
32,5
100,2
133,5
33,7
99,1
133,7
35,5
97,4
134,5
38,8
94,5
135,5
41,6
92,2
26 / 19
138,9
30,3
100,7
138,3
33,1
97,8
138,3
34,3
96,7
138,3
36,2
95,0
138,9
39,6
92,1
139,8
42,5
89,8
27 / 19,5
140,4
30,4
103,4
139,7
33,3
100,5
139,6
34,5
99,4
139,6
36,4
97,7
140,1
39,8
94,9
140,8
42,7
92,6
28 / 21
145,3
30,8
101,6
144,4
33,8
98,8
144,2
35,0
97,7
143,8
37,0
96,0
143,6
40,4
93,1
143,6
43,4
90,9
30 / 22
148,8
30,9
111,7
147,9
34,1
108,9
147,5
35,4
107,8
147,0
37,4
106,1
146,0
40,9
103,2
145,2
43,8
101,0
22 / 16
147,7
28,0
112,0
147,0
30,8
108,9
147,2
32,1
107,6
147,8
34,0
105,7
149,9
37,4
102,6
152,7
40,3
100,1
24 / 17
150,3
28,2
119,0
150,8
31,1
116,0
151,1
32,3
114,8
151,5
34,2
113,0
152,2
37,6
110,1
153,0
40,4
107,7
26 / 19
156,2
28,7
117,6
157,3
31,6
114,8
157,4
32,8
113,6
157,5
34,7
111,9
157,0
38,0
109,1
156,0
40,8
106,9
27 / 19,5
157,8
28,8
121,3
158,6
31,7
118,4
158,8
33,0
117,3
158,7
34,8
115,6
158,2
38,1
112,8
157,2
40,9
110,5
28 / 21
162,9
29,1
117,3
162,1
32,1
114,3
162,0
33,3
113,1
161,8
35,2
111,4
161,9
38,5
108,4
162,3
41,2
106,1
30 / 22
166,5
29,4
125,8
164,0
32,4
122,7
163,5
33,6
121,5
163,3
35,4
119,6
164,4
38,7
116,5
22 / 16
165,6
34,1
125,0
166,2
37,4
121,5
166,4
38,9
120,0
166,5
41,2
117,9
166,5
45,3
114,3
166,3
49,0
111,4
24 / 17
168,8
34,3
132,3
169,4
37,8
128,9
169,5
39,3
127,5
169,5
41,6
125,4
169,0
45,8
121,9
168,2
49,3
119,1
26 / 19
175,2
34,9
130,5
175,9
38,4
127,1
175,9
39,9
125,8
175,8
42,3
123,8
174,8
46,4
120,4
173,5
49,9
117,7
27 / 19,5
176,8
35,1
134,3
177,5
38,5
131,0
177,6
40,0
129,6
177,4
42,3
127,6
176,5
46,5
124,2
175,1
50,0
121,5
28 / 21
181,7
35,7
130,6
182,5
38,7
127,1
182,6
40,1
125,7
182,6
42,4
123,7
182,0
46,6
120,3
180,9
50,4
117,5
30 / 22
184,9
36,1
140,4
185,8
38,7
136,9
186,0
40,0
135,5
186,2
42,2
133,4
186,0
46,5
129,9
185,5
50,6
127,0
22 / 16
192,4
37,8
144,8
192,5
41,6
140,7
192,8
43,3
139,1
193,5
45,9
136,6
195,1
50,5
132,5
197,0
54,4
129,3
24 / 17
195,8
38,2
154,4
195,8
42,2
150,4
196,0
43,8
148,8
196,6
46,4
146,4
198,5
50,9
142,5
200,6
54,6
139,3
26 / 19
203,0
39,1
153,7
202,7
43,1
149,9
202,9
44,8
148,4
203,4
47,3
146,1
205,3
51,6
142,3
207,6
55,2
139,3
27 / 19,5
204,9
39,2
158,3
204,5
43,3
154,6
204,7
44,9
153,1
205,2
47,5
150,8
207,0
51,8
147,1
209,3
55,4
144,0
28 / 21
210,5
39,7
151,3
210,2
43,7
147,6
210,3
45,4
146,1
210,8
47,9
143,9
212,3
52,4
140,2
214,2
56,1
137,2
30 / 22
214,3
40,0
158,0
214,1
43,9
154,3
214,2
45,6
152,8
214,6
48,2
150,6
215,9
52,8
147,0
22 / 16
212,9
45,5
160,0
213,2
50,1
155,5
213,5
52,1
153,7
214,2
55,2
151,0
216,1
60,7
146,5
218,1
65,5
142,9
24 / 17
216,8
46,1
170,1
216,6
50,7
165,6
216,9
52,6
163,9
217,6
55,7
161,2
219,8
61,2
156,8
222,4
65,9
153,3
524
14
35
kWs
464
704
32
kWe
402
604
30
kWf
362
452
EXTERNAL EXCHANGER AIR INTAKE TEMPERATURE (ºC)
25
26 / 19
225,5
47,0
169,1
224,9
51,7
164,8
225,0
53,7
163,0
225,6
56,8
160,4
227,6
62,3
156,0
230,3
67,0
152,5
27 / 19,5
227,9
47,2
174,2
227,2
51,9
169,8
227,3
53,9
168,1
227,8
57,1
165,5
229,6
62,6
161,1
232,1
67,3
157,6
28 / 21
235,7
47,8
166,9
235,0
52,7
162,5
234,9
54,8
160,7
235,0
58,0
158,1
235,8
63,6
153,6
237,0
68,4
150,1
30 / 22
241,3
48,1
175,6
240,7
53,2
171,0
240,5
55,3
169,2
240,3
58,6
166,5
240,1
64,4
162,0
240,0
69,3
158,3
Ta = ambient air temperature D.B/W.B
DB = dry bulb
WB = wet bulb
kWf = Cooling capacity in kW
kWe = Compressor power input in kW
kWs = sensible cooling capacity (kW)
Performance data are referred to operation with 30% of fresh air intake and same amount of air exhaust. (construction configuration C)
the cooling capacities have not accounted for the heat dissipation of the centrifugal fan motors.
PACKAGED
362 - 904
AIR FLOW: STANDARD
COOLING PERFORMANCE
Size
804
904
Ta
(°C)
DB/WB
EXTERNAL EXCHANGER AIR INTAKE TEMPERATURE (ºC)
25
30
32
35
40
44
kWf
kWe
kWs
kWf
kWe
kWs
kWf
kWe
kWs
kWf
kWe
kWs
kWf
kWe
kWs
kWf
kWe
kWs
22 / 16
256,7
48,6
193,8
259,3
53,3
188,5
260,2
55,4
186,3
261,4
58,6
183,2
262,8
64,3
177,8
263,6
69,2
173,6
24 / 17
262,5
49,0
207,8
263,2
53,9
202,6
263,7
55,9
200,5
264,7
59,1
197,4
267,1
64,7
192,2
269,7
69,3
188,0
26 / 19
274,0
49,8
208,6
272,2
54,9
203,4
272,1
57,0
201,3
272,9
60,1
198,2
276,0
65,4
193,0
280,3
69,7
188,9
27 / 19,5
276,7
50,0
214,8
274,7
55,1
209,6
274,6
57,2
207,5
275,2
60,4
204,4
278,3
65,6
199,1
282,6
69,8
194,9
28 / 21
285,0
50,6
203,4
282,9
55,8
197,9
282,7
57,9
195,7
283,0
61,0
192,4
285,3
66,2
187,0
288,6
70,3
182,6
30 / 22
290,3
51,0
206,7
288,9
56,2
201,0
288,8
58,3
198,7
288,9
61,4
195,3
290,0
66,6
189,6
22 / 16
281,7
55,9
212,7
282,0
61,2
206,7
282,3
63,4
204,3
282,9
67,0
200,7
284,5
73,5
194,6
286,2
79,0
189,8
24 / 17
287,6
56,3
226,5
287,5
61,8
220,6
287,6
64,1
218,2
287,9
67,8
214,7
288,9
74,2
208,7
290,1
79,7
204,0
26 / 19
299,1
57,3
224,7
298,3
63,1
218,9
298,2
65,5
216,6
298,0
69,2
213,1
298,2
75,6
207,4
298,7
81,0
202,7
27 / 19,5
302,0
57,6
231,7
301,0
63,4
225,9
300,8
65,8
223,6
300,6
69,5
220,2
300,7
76,0
214,4
301,1
81,4
209,8
28 / 21
310,3
58,5
223,0
309,1
64,3
217,3
308,7
66,7
215,0
308,4
70,5
211,5
308,3
77,0
205,8
308,6
82,4
201,2
30 / 22
315,8
59,2
237,2
314,4
64,9
231,5
314,0
67,3
229,2
313,7
71,0
225,7
313,6
77,6
219,9
314,1
83,1
215,3
BT08A006GB-03
Ta = ambient air temperature D.B/W.B
DB = dry bulb
WB = wet bulb
kWf = Cooling capacity in kW
kWe = Compressor power input in kW
kWs = sensible cooling capacity (kW)
Performance data are referred to operation with 30% of fresh air intake and same amount of air exhaust. (construction configuration C)
the cooling capacities have not accounted for the heat dissipation of the centrifugal fan motors.
15
PACKAGED
362 - 904
AIR FLOW: STANDARD
Size
362
402
452
464
524
604
704
804
904
5555
570
6111
570
6666
570
8056
570
9028
570
10000
510
11111
570
12500
570
13889
570
AIR HANDLING SECTION FANS (OUTLET)
Air flow
Max outside static pressure
l/s
Pa
HEATING PERFORMANCE
Size
Ta
(°C)
DB/WB
RETURN AIR TEMPERATURE (D.B.)
10
kWt
15
kWe
-5 / -5,4
18
19
20
21
25
kWt
kWe
kWt
kWe
kWt
kWe
kWt
kWe
kWt
kWe
kWt
kWe
92,3
17,0
92,8
17,7
93,0
17,9
93,2
18,2
93,4
18,4
94,5
19,5
0 / -0,6
100,6
16,9
101,1
18,1
101,6
18,9
101,8
19,2
102,0
19,5
102,2
19,7
103,2
21,0
5 / 3,9
110,2
18,1
110,5
19,4
110,9
20,3
111,1
20,7
111,2
21,0
111,4
21,3
112,3
22,7
362
7 / 6,1
115,3
18,8
115,6
20,2
115,9
21,2
116,0
21,5
116,1
21,8
116,3
22,2
117,0
23,7
10 / 8,2
120,5
19,6
120,7
21,1
120,9
22,0
120,9
22,4
121,0
22,7
121,2
23,1
121,7
24,6
15 / 13
133,4
21,5
133,2
23,2
133,1
24,3
133,1
24,7
133,1
25,1
133,1
25,5
133,1
27,1
-5 / -5,4
100,2
18,1
103,3
19,5
104,8
20,4
105,3
20,7
105,7
21,0
106,1
21,3
107,5
22,6
0 / -0,6
111,8
19,4
113,2
20,9
114,1
21,8
114,4
22,2
114,7
22,5
115,0
22,9
116,3
24,4
5 / 3,9
123,0
20,9
123,8
22,6
124,4
23,6
124,6
24,0
124,8
24,4
125,0
24,8
126,1
26,4
7 / 6,1
128,6
21,8
129,4
23,5
129,9
24,7
130,1
25,0
130,3
25,4
130,5
25,9
131,3
27,6
10 / 8,2
134,0
22,6
135,1
24,5
135,6
25,7
135,8
26,1
135,9
26,5
136,1
27,0
136,6
28,7
15 / 13
146,5
24,8
149,0
27,0
149,8
28,4
149,9
28,9
150,1
29,4
150,1
29,8
149,8
31,7
-5 / -5,4
112,0
20,8
110,6
21,9
111,0
22,7
111,3
23,0
111,7
23,4
112,2
23,7
115,3
25,3
0 / -0,6
122,8
22,1
123,0
23,6
123,5
24,6
123,8
25,0
124,1
25,3
124,4
25,7
126,1
27,4
5 / 3,9
134,2
23,7
135,0
25,5
135,6
26,7
135,8
27,1
136,0
27,5
136,2
27,9
137,2
29,7
7 / 6,1
140,2
24,6
141,0
26,6
141,6
27,8
141,8
28,2
142,0
28,7
142,2
29,1
143,0
31,0
10 / 8,2
146,1
25,6
146,8
27,6
147,3
29,0
147,5
29,4
147,7
29,9
147,9
30,4
148,8
32,4
15 / 13
160,8
28,1
160,5
30,4
160,8
31,9
160,9
32,4
161,1
32,9
161,4
33,4
162,8
35,7
121,8
21,4
123,9
22,6
124,6
23,0
125,3
23,4
125,9
23,8
128,4
25,4
402
452
-5 / -5,4
0 / -0,6
133,3
21,3
134,6
23,1
135,6
24,3
135,9
24,7
136,3
25,1
136,7
25,5
138,5
27,3
5 / 3,9
146,8
23,1
147,3
25,0
147,9
26,3
148,1
26,7
148,3
27,2
148,6
27,6
149,7
29,5
464
7 / 6,1
153,0
24,0
153,8
26,0
154,4
27,4
154,6
27,8
154,8
28,3
155,0
28,8
155,9
30,8
10 / 8,2
158,7
24,9
160,1
27,1
160,8
28,5
161,1
29,0
161,3
29,5
161,5
30,0
162,3
32,1
15 / 13
171,1
27,1
175,1
29,7
176,7
31,4
177,1
31,9
177,5
32,5
177,8
33,0
178,2
35,3
136,2
25,8
134,2
26,8
133,8
27,1
133,6
27,5
133,4
27,9
134,5
29,5
-5 / -5,4
0 / -0,6
152,0
25,8
149,9
27,6
149,4
28,9
149,4
29,3
149,5
29,7
149,6
30,2
150,8
32,2
5 / 3,9
164,8
27,7
164,9
29,9
165,1
31,3
165,2
31,8
165,4
32,3
165,6
32,9
166,4
35,0
7 / 6,1
172,4
28,8
173,0
31,2
173,3
32,7
173,4
33,2
173,5
33,8
173,7
34,3
174,1
36,6
10 / 8,2
180,6
30,0
181,2
32,5
181,4
34,1
181,5
34,7
181,5
35,2
181,6
35,8
181,6
38,1
15 / 13
202,2
33,2
201,7
36,0
201,1
37,7
200,9
38,3
200,6
38,9
200,3
39,5
199,0
42,0
157,4
28,7
158,4
30,0
158,8
30,4
159,3
30,9
159,8
31,4
162,4
33,4
0 / -0,6
172,7
28,4
174,0
30,7
174,8
32,1
175,1
32,6
175,4
33,1
175,7
33,7
177,0
35,8
5 / 3,9
189,7
30,6
191,0
33,1
191,6
34,7
191,7
35,2
191,9
35,8
192,0
36,3
192,5
38,7
7 / 6,1
198,7
31,8
199,7
34,4
200,2
36,1
200,3
36,6
200,4
37,2
200,5
37,8
200,6
40,3
10 / 8,2
207,6
33,1
208,4
35,8
208,7
37,5
208,8
38,1
208,8
38,7
208,9
39,3
208,8
41,9
15 / 13
229,7
36,4
229,4
39,3
229,3
41,2
229,2
41,9
229,2
42,6
229,1
43,3
228,9
46,1
-5 / -5,4
179,0
31,9
179,1
33,9
179,5
35,2
179,6
35,7
179,8
36,2
179,9
36,7
180,8
38,8
0 / -0,6
195,2
33,9
195,9
36,2
196,4
37,8
196,6
38,3
196,9
38,9
197,1
39,5
198,2
41,9
5 / 3,9
213,0
36,3
213,8
39,0
214,5
40,8
214,7
41,5
215,0
42,1
215,2
42,8
216,5
45,5
7 / 6,1
222,6
37,7
223,4
40,6
224,0
42,5
224,3
43,2
224,5
43,9
224,8
44,6
226,0
47,5
10 / 8,2
232,3
39,2
233,0
42,3
233,6
44,3
233,8
45,0
234,1
45,7
234,4
46,5
235,6
49,6
15 / 13
256,5
43,0
256,8
46,5
257,2
48,8
257,4
49,6
257,6
50,4
257,8
51,3
258,9
54,7
524
BT08A006GB-03
-5 / -5,4
604
704
Ta = Outside air temperature (°C)
DB = dry bulb
WB = wet bulb
kWt = Heating capacity (kW)
with coils free of ice
kWe = Compressor power input in kW
Performance data are referred to operation with 30% of fresh air intake and same amount of air exhaust. (construction configuration C)
not all thermal yields take into account the heat dissipated by the fan motors
16
PACKAGED
362 - 904
AIR FLOW: STANDARD
HEATING PERFORMANCE
Size
Ta
(°C)
DB/WB
RETURN AIR TEMPERATURE (D.B.)
10
kWt
15
kWe
-5 / -5,4
804
19
20
21
25
kWt
kWe
kWt
kWe
kWt
kWe
kWt
kWe
kWt
kWe
kWt
kWe
211,1
38,5
210,1
39,8
210,0
40,2
210,1
40,7
210,2
41,3
212,1
43,7
0 / -0,6
236,6
38,0
236,9
40,6
237,4
42,3
237,6
42,9
237,8
43,5
238,0
44,2
239,1
46,9
5 / 3,9
261,2
40,5
262,4
43,7
263,0
45,7
263,1
46,4
263,2
47,1
263,4
47,8
263,7
50,8
7 / 6,1
274,8
42,4
275,3
45,7
275,5
47,8
275,5
48,5
275,5
49,2
275,6
50,0
275,5
53,0
10 / 8,2
288,7
44,5
287,9
47,8
287,4
49,9
287,3
50,7
287,2
51,4
287,1
52,2
286,7
55,4
15 / 13
324,1
50,6
317,6
53,5
314,8
55,7
314,0
56,4
313,4
57,2
312,9
58,0
311,7
61,6
237,0
42,9
236,6
44,4
236,8
45,0
237,0
45,5
237,4
46,1
239,9
48,7
0 / -0,6
261,8
43,1
261,5
45,9
261,9
47,8
262,1
48,4
262,4
49,1
262,7
49,8
264,4
52,7
5 / 3,9
287,8
46,3
288,0
49,5
288,3
51,7
288,5
52,4
288,6
53,2
288,8
54,0
289,6
57,3
7 / 6,1
302,5
48,2
302,3
51,6
302,3
53,9
302,3
54,7
302,3
55,5
302,4
56,3
302,7
59,7
10 / 8,2
317,7
50,2
316,6
53,8
316,2
56,2
316,0
57,0
315,9
57,8
315,8
58,7
315,6
62,2
15 / 13
356,7
55,7
352,2
59,5
350,2
62,0
349,6
62,9
349,0
63,8
348,5
64,7
347,0
68,6
-5 / -5,4
904
18
Ta = Outside air temperature (°C)
DB = dry bulb
WB = wet bulb
kWt = Heating capacity (kW)
with coils free of ice
kWe = Compressor power input in kW
Performance data are referred to operation with 30% of fresh air intake and same amount of air exhaust. (construction configuration C)
not all thermal yields take into account the heat dissipated by the fan motors
INTEGRATED HEATING CAPACITIES
Air temperature external exchanger inlet °C (D.B. / W.B.)
Heating capacity multiplication coefficient
-5 / -5.4
0,89
0 / -0.6
0,88
5 / 3.9
0,94
OTHERS
1
BT08A006GB-03
To obtain the integrated heating capacities (the real heating capacity considering the defrost cycles too), multiply the kWt value in the heating performance tables by the following coefficient.
DB = dry bulb
WB = wet bulb
In case of below zero air ambient temperature with a long period of heat pump operating mode it is necessary to help the evacuation of the water produced during the defrost cycle; this to
avoid the formation of ice in the unit basement. Pay attention that the evacuation will not create inconveniences to things or persons.
17
PACKAGED
362 - 904
Size
AIR FLOW: REDUCED
362
402
452
464
524
604
704
804
904
4444
570
6389
510
7222
570
8056
570
8888
510
10000
570
11111
510
AIR HANDLING SECTION FANS (OUTLET)
Air flow
Max outside static pressure
l/s
Pa
4888
570
5333
570
COOLING PERFORMANCE
Size
Ta
(°C)
DB/WB
BT08A006GB-03
35
40
44
kWf
kWe
kWs
kWf
kWe
kWs
kWf
kWe
kWs
kWf
kWe
kWs
kWf
kWe
kWs
24 / 17
106,3
21,9
79,2
106,9
24,2
77,1
107,3
25,2
76,3
108,0
26,7
75,1
109,8
29,3
73,1
111,6
31,6
71,5
26 / 19
112,0
22,1
79,0
112,0
24,4
76,9
112,1
25,4
76,0
112,5
26,9
74,8
113,5
29,6
72,7
114,7
31,9
71,1
27 / 19,5
113,3
22,2
81,1
113,2
24,5
79,0
113,3
25,4
78,1
113,6
27,0
76,9
114,5
29,7
74,8
115,6
32,0
73,1
28 / 21
116,9
22,5
78,3
116,6
24,8
76,2
116,6
25,7
75,4
116,8
27,3
74,1
117,5
30,0
72,0
118,5
32,4
70,4
30 / 22
119,0
22,7
82,2
118,7
25,0
80,2
118,7
26,0
79,3
118,9
27,5
78,1
119,7
30,3
76,0
120,7
32,7
74,4
32 / 23,5
121,7
23,1
83,7
121,6
25,4
81,6
121,7
26,4
80,8
122,0
28,0
79,6
123,1
30,7
77,6
124,3
33,1
76,0
24 / 17
118,2
25,4
87,2
119,0
28,0
84,7
119,3
29,1
83,7
119,6
30,7
82,2
119,9
33,4
79,8
120,0
35,7
77,8
26 / 19
123,0
26,0
86,2
123,3
28,5
83,7
123,4
29,6
82,7
123,6
31,2
81,3
123,7
34,0
78,8
123,8
36,3
76,8
27 / 19,5
124,2
26,1
88,4
124,4
28,6
85,9
124,5
29,7
84,9
124,6
31,3
83,4
124,8
34,1
81,0
124,9
36,4
79,0
28 / 21
127,9
26,5
85,9
128,0
29,0
83,4
128,0
30,1
82,4
128,0
31,7
80,8
128,2
34,5
78,3
128,3
36,8
76,2
30 / 22
130,5
26,8
91,4
130,4
29,3
88,7
130,4
30,4
87,7
130,4
32,0
86,1
130,6
34,7
83,4
130,7
37,0
81,3
32 / 23,5
134,4
27,2
95,9
134,2
29,8
93,1
134,2
30,8
92,0
134,3
32,4
90,3
134,4
35,1
87,5
134,7
37,2
85,2
24 / 17
127,7
29,2
93,4
127,7
32,2
90,9
127,8
33,5
89,9
128,1
35,4
88,4
128,9
38,9
85,8
129,7
41,8
83,8
26 / 19
132,5
29,6
92,4
133,1
32,7
89,7
133,4
34,0
88,7
133,6
35,9
87,1
134,0
39,3
84,4
134,1
42,2
82,3
27 / 19,5
133,8
29,7
94,8
134,5
32,8
92,1
134,7
34,1
91,0
134,9
36,1
89,4
135,2
39,5
86,8
135,2
42,3
84,7
28 / 21
138,1
30,2
92,1
138,4
33,3
89,4
138,5
34,6
88,3
138,6
36,6
86,7
138,5
40,0
84,0
138,2
42,9
81,8
30 / 22
141,1
30,5
97,2
141,0
33,7
94,5
140,9
35,0
93,4
140,8
37,0
91,8
140,5
40,4
89,1
140,2
43,3
86,9
32 / 23,5
145,9
31,1
99,7
144,8
34,3
97,0
144,4
35,6
95,9
143,9
37,6
94,2
143,2
41,2
91,5
142,9
44,1
89,4
24 / 17
147,2
27,6
107,6
144,3
30,5
104,8
144,0
31,7
103,7
144,6
33,6
102,1
148,2
37,0
99,4
153,5
39,8
97,2
26 / 19
150,5
28,3
106,8
149,7
31,3
103,9
149,6
32,5
102,7
149,8
34,4
101,0
151,0
37,8
98,1
152,6
40,7
95,8
27 / 19,5
151,6
28,5
109,7
151,1
31,5
106,8
151,1
32,7
105,6
151,3
34,6
103,8
152,0
38,0
100,9
153,1
40,9
98,6
28 / 21
155,5
28,9
106,0
155,6
31,9
103,0
155,7
33,2
101,8
155,7
35,1
100,1
155,9
38,4
97,1
156,1
41,2
94,7
30 / 22
158,6
29,2
111,7
158,8
32,2
108,8
158,8
33,4
107,6
158,9
35,3
105,8
159,2
38,6
102,8
159,4
41,4
100,5
32 / 23,5
164,0
29,5
114,0
163,7
32,5
111,1
163,8
33,7
109,9
164,1
35,6
108,2
165,1
38,8
105,3
24 / 17
162,0
33,9
121,0
162,1
37,7
117,7
162,1
39,3
116,3
162,1
41,8
114,3
162,1
46,1
110,9
162,1
49,6
108,1
26 / 19
167,7
34,5
120,3
167,6
38,3
116,9
167,6
39,9
115,6
167,6
42,3
113,6
167,8
46,4
110,3
168,1
49,8
107,6
27 / 19,5
169,4
34,7
123,5
169,1
38,4
120,2
169,1
40,0
118,9
169,1
42,4
116,9
169,2
46,5
113,6
169,5
49,9
110,9
28 / 21
175,3
35,1
119,0
174,3
38,8
115,6
173,9
40,3
114,3
173,6
42,7
112,3
173,3
46,9
109,0
173,3
50,4
106,3
524
18
32
kWs
464
704
30
kWe
402
604
25
kWf
362
452
EXTERNAL EXCHANGER AIR INTAKE TEMPERATURE (ºC)
30 / 22
179,8
35,3
124,8
178,0
39,0
121,4
177,5
40,5
120,1
176,8
42,9
118,1
176,0
47,2
114,7
175,7
50,9
112,0
32 / 23,5
187,4
35,6
125,8
184,3
39,2
122,3
183,2
40,7
120,9
181,8
43,2
118,8
179,9
47,8
115,3
178,8
51,8
112,6
24 / 17
188,0
37,8
138,6
188,5
41,7
135,2
188,8
43,4
133,8
189,5
46,1
131,8
191,0
51,0
128,4
192,5
55,2
125,7
26 / 19
194,6
38,6
139,1
195,3
42,6
135,6
195,7
44,3
134,1
196,4
47,0
132,0
197,7
51,8
128,5
199,0
55,9
125,7
27 / 19,5
196,4
38,8
142,9
197,0
42,8
139,3
197,4
44,5
137,9
198,1
47,2
135,8
199,4
51,9
132,2
200,8
56,0
129,4
28 / 21
202,1
39,3
138,3
202,4
43,3
134,7
202,6
45,0
133,3
203,2
47,7
131,1
204,7
52,4
127,6
206,4
56,4
124,7
30 / 22
206,3
39,6
145,1
206,0
43,7
141,5
206,1
45,4
140,1
206,6
48,0
138,0
208,3
52,7
134,4
210,3
56,6
131,6
32 / 23,5
213,0
40,0
147,4
211,5
44,1
143,9
211,3
45,8
142,5
211,7
48,4
140,4
213,7
53,0
137,0
216,6
56,8
134,2
24 / 17
209,0
45,5
155,6
208,3
50,3
150,7
208,4
52,3
148,7
208,8
55,5
145,8
210,4
61,4
140,8
212,5
66,4
136,8
26 / 19
216,2
46,4
153,7
215,8
51,1
149,3
215,8
53,2
147,5
216,2
56,5
144,8
217,3
62,3
140,3
218,8
67,5
136,8
27 / 19,5
218,3
46,6
157,7
217,8
51,4
153,4
217,9
53,4
151,6
218,1
56,7
149,0
219,2
62,6
144,7
220,6
67,8
141,2
28 / 21
225,7
47,2
151,5
224,5
52,1
147,4
224,3
54,2
145,8
224,3
57,5
143,4
225,2
63,5
139,3
226,5
68,8
136,0
30 / 22
231,3
47,5
159,2
229,4
52,5
155,2
228,9
54,7
153,7
228,7
58,1
151,3
229,4
64,2
147,4
231,0
69,5
144,2
32 / 23,5
240,9
48,0
161,8
237,3
53,2
158,0
236,4
55,5
156,5
235,7
59,0
154,3
236,3
65,3
150,5
238,2
70,7
147,5
Ta = ambient air temperature D.B/W.B
DB = dry bulb
WB = wet bulb
kWf = Cooling capacity in kW
kWe = Compressor power input in kW
kWs = sensible cooling capacity (kW)
Performance data are referred to operation with 30% of fresh air intake and same amount of air exhaust. (construction configuration C)
the cooling capacities have not accounted for the heat dissipation of the centrifugal fan motors.
PACKAGED
362 - 904
AIR FLOW: REDUCED
COOLING PERFORMANCE
Size
804
904
Ta
(°C)
DB/WB
EXTERNAL EXCHANGER AIR INTAKE TEMPERATURE (ºC)
25
30
32
35
40
44
kWf
kWe
kWs
kWf
kWe
kWs
kWf
kWe
kWs
kWf
kWe
kWs
kWf
kWe
kWs
kWf
kWe
kWs
24 / 17
251,6
48,3
186,9
251,9
53,5
181,3
252,1
55,7
179,1
252,6
59,0
175,8
253,9
64,8
170,3
255,3
69,7
165,9
26 / 19
261,6
49,2
186,7
262,2
54,3
181,4
262,5
56,5
179,3
262,9
59,7
176,1
263,5
65,4
170,8
264,1
70,2
166,5
27 / 19,5
264,2
49,4
191,5
264,8
54,5
186,2
265,1
56,7
184,1
265,4
59,9
181,0
266,0
65,6
175,7
266,4
70,4
171,5
28 / 21
272,5
50,1
184,8
272,8
55,2
179,7
272,9
57,2
177,7
273,0
60,5
174,6
273,2
66,1
169,5
273,2
70,8
165,4
30 / 22
278,3
50,6
193,4
278,2
55,6
188,4
278,1
57,6
186,4
278,1
60,8
183,4
278,0
66,4
178,4
277,9
71,1
174,4
32 / 23,5
287,4
51,3
196,2
286,4
56,2
191,4
286,0
58,2
189,5
285,6
61,4
186,6
285,2
66,9
181,7
285,0
71,5
177,9
24 / 17
275,2
55,6
202,4
275,0
61,4
197,0
275,1
63,8
194,8
275,5
67,6
191,6
276,7
74,2
186,2
278,2
79,9
181,9
26 / 19
286,8
56,6
202,2
285,8
62,5
196,9
285,6
64,9
194,7
285,6
68,8
191,5
286,4
75,5
186,1
287,6
81,1
181,8
27 / 19,5
289,6
56,8
207,7
288,5
62,8
202,3
288,3
65,2
200,2
288,3
69,1
197,0
288,9
75,7
191,6
290,0
81,4
187,3
28 / 21
297,6
57,7
201,0
296,8
63,6
195,6
296,7
66,0
193,5
296,6
69,9
190,3
296,8
76,5
184,9
297,3
82,2
180,6
30 / 22
302,6
58,3
211,5
302,4
64,1
206,1
302,4
66,6
204,0
302,3
70,4
200,8
302,3
77,0
195,5
302,4
82,7
191,2
32 / 23,5
309,7
59,2
215,5
310,9
64,9
210,2
311,1
67,3
208,1
311,3
71,0
204,9
311,0
77,7
199,6
310,1
83,3
195,4
BT08A006GB-03
Ta = ambient air temperature D.B/W.B
DB = dry bulb
WB = wet bulb
kWf = Cooling capacity in kW
kWe = Compressor power input in kW
kWs = sensible cooling capacity (kW)
Performance data are referred to operation with 30% of fresh air intake and same amount of air exhaust. (construction configuration C)
the cooling capacities have not accounted for the heat dissipation of the centrifugal fan motors.
19
PACKAGED
362 - 904
AIR FLOW: REDUCED
Size
362
402
452
464
524
604
704
804
904
4444
570
4888
570
5333
570
6389
510
7222
570
8056
570
8888
510
10000
570
11111
510
AIR HANDLING SECTION FANS (OUTLET)
Air flow
Max outside static pressure
l/s
Pa
HEATING PERFORMANCE
Size
Ta
(°C)
DB/WB
RETURN AIR TEMPERATURE (D.B.)
10
15
18
19
20
21
25
kWt
kWe
kWt
kWe
kWt
kWe
kWt
kWe
kWt
kWe
kWt
kWe
kWt
kWe
-5 / -5,4
90,1
16,7
89,6
17,8
89,6
18,5
89,7
18,8
89,9
19,1
90,0
19,4
91,0
20,6
0 / -0,6
99,2
18,0
99,2
19,3
99,2
20,2
99,2
20,5
99,3
20,8
99,3
21,1
99,5
22,4
5 / 3,9
108,8
19,6
108,8
21,1
108,9
22,1
108,9
22,4
108,9
22,8
108,9
23,1
109,1
24,6
7 / 6,1
113,9
20,5
113,7
22,1
113,8
23,1
113,8
23,5
113,9
23,9
114,0
24,2
114,4
25,9
10 / 8,2
119,0
21,4
118,6
23,1
118,6
24,2
118,7
24,6
118,8
25,0
119,0
25,4
119,8
27,2
362
15 / 13
131,4
23,8
130,1
25,6
130,2
26,9
130,5
27,4
130,8
27,9
131,2
28,4
133,6
30,6
-5 / -5,4
98,8
19,1
101,4
20,7
102,6
21,7
103,0
22,0
103,3
22,4
103,6
22,7
104,5
24,2
0 / -0,6
110,9
20,8
112,2
22,5
112,9
23,6
113,2
24,0
113,5
24,4
113,7
24,8
114,7
26,5
5 / 3,9
121,9
22,7
122,6
24,6
123,1
25,8
123,2
26,2
123,4
26,6
123,6
27,1
124,4
28,9
402
7 / 6,1
127,3
23,7
127,8
25,7
128,2
27,0
128,3
27,4
128,4
27,8
128,6
28,3
129,1
30,2
10 / 8,2
132,4
24,7
132,9
26,8
133,1
28,2
133,2
28,6
133,3
29,1
133,4
29,5
133,7
31,5
15 / 13
143,8
27,3
144,7
29,7
144,9
31,2
144,8
31,7
144,8
32,2
144,7
32,7
144,1
34,6
-5 / -5,4
108,2
21,7
110,9
23,3
112,2
24,4
112,6
24,8
113,0
25,2
113,4
25,5
114,5
27,2
0 / -0,6
121,0
23,6
122,6
25,4
123,5
26,6
123,8
27,1
124,1
27,5
124,4
27,9
125,5
29,8
5 / 3,9
132,9
25,6
133,7
27,7
134,3
29,1
134,6
29,5
134,8
30,0
135,0
30,5
136,0
32,6
7 / 6,1
138,6
26,7
139,3
28,9
139,8
30,4
139,9
30,9
140,1
31,4
140,3
31,9
141,1
34,0
10 / 8,2
144,0
27,9
144,6
30,2
145,0
31,7
145,2
32,2
145,3
32,7
145,5
33,3
146,1
35,4
15 / 13
156,3
30,8
157,0
33,4
157,3
35,0
157,4
35,6
157,4
36,1
157,4
36,7
157,4
39,0
-5 / -5,4
117,6
21,1
118,3
22,8
119,7
24,0
120,3
24,4
121,0
24,9
121,7
25,3
125,6
27,4
0 / -0,6
130,7
22,9
131,7
24,9
132,5
26,2
132,8
26,6
133,1
27,1
133,5
27,5
134,9
29,5
5 / 3,9
143,5
24,9
144,4
27,1
144,9
28,6
145,1
29,0
145,3
29,5
145,5
30,1
146,4
32,2
7 / 6,1
150,0
26,1
150,6
28,4
151,1
29,9
151,3
30,4
151,6
30,9
151,8
31,4
152,9
33,7
10 / 8,2
156,4
27,2
156,5
29,6
157,1
31,2
157,4
31,7
157,7
32,3
158,0
32,9
159,8
35,4
15 / 13
171,4
30,1
170,2
32,7
171,1
34,5
171,6
35,1
172,3
35,8
173,1
36,5
177,8
39,6
-5 / -5,4
131,5
25,3
134,7
27,5
134,2
28,7
133,7
29,0
132,9
29,3
132,0
29,7
126,3
30,7
0 / -0,6
147,8
27,5
148,7
29,8
148,6
31,2
148,5
31,6
148,3
32,1
148,0
32,6
146,6
34,5
5 / 3,9
163,5
30,0
163,3
32,5
163,3
34,0
163,3
34,6
163,3
35,1
163,3
35,7
163,4
38,1
452
464
BT08A006GB-03
524
7 / 6,1
171,3
31,4
171,0
34,0
170,9
35,6
170,9
36,2
170,8
36,8
170,8
37,4
170,9
39,9
10 / 8,2
178,8
32,8
178,6
35,5
178,4
37,3
178,3
37,9
178,2
38,5
178,1
39,1
177,6
41,6
15 / 13
196,3
36,4
197,2
39,6
196,5
41,5
196,0
42,1
195,5
42,7
194,8
43,3
191,2
45,7
-5 / -5,4
154,1
28,0
154,6
30,3
155,2
31,7
155,4
32,2
155,7
32,7
155,9
33,2
157,2
35,3
0 / -0,6
170,5
30,4
171,1
32,8
171,6
34,4
171,7
34,9
171,9
35,5
172,1
36,1
173,0
38,4
5 / 3,9
187,6
33,1
188,0
35,8
188,2
37,5
188,3
38,1
188,3
38,8
188,4
39,4
188,8
42,0
604
704
7 / 6,1
196,6
34,6
196,7
37,4
196,7
39,3
196,8
39,9
196,8
40,6
196,8
41,2
196,8
44,0
10 / 8,2
205,5
36,1
205,3
39,2
205,2
41,1
205,1
41,8
205,1
42,4
205,0
43,1
204,8
46,0
15 / 13
227,1
40,1
226,1
43,5
225,4
45,7
225,2
46,4
224,9
47,2
224,7
47,9
223,6
51,1
-5 / -5,4
175,1
33,5
170,3
35,3
169,6
36,7
169,7
37,3
170,0
37,8
170,5
38,4
174,2
41,0
0 / -0,6
192,1
36,0
191,1
38,6
191,2
40,3
191,3
40,9
191,5
41,5
191,7
42,2
193,3
44,9
5 / 3,9
210,3
39,1
210,8
42,2
211,0
44,2
211,1
44,9
211,2
45,6
211,3
46,3
211,7
49,3
7 / 6,1
220,0
40,8
220,4
44,1
220,6
46,2
220,7
47,0
220,7
47,7
220,7
48,5
220,9
51,6
10 / 8,2
229,7
42,7
229,7
46,1
229,7
48,3
229,7
49,1
229,7
49,9
229,7
50,7
229,7
54,0
15 / 13
253,7
47,4
250,9
51,1
250,0
53,6
249,9
54,4
249,8
55,3
249,8
56,2
250,5
59,9
Ta = Outside air temperature (°C)
DB = dry bulb
WB = wet bulb
kWt = Heating capacity (kW)
with coils free of ice
kWe = Compressor power input in kW
Performance data are referred to operation with 30% of fresh air intake and same amount of air exhaust. (construction configuration C)
not all thermal yields take into account the heat dissipated by the fan motors
20
PACKAGED
362 - 904
AIR FLOW: REDUCED
HEATING PERFORMANCE
Size
804
904
Ta
(°C)
DB/WB
RETURN AIR TEMPERATURE (D.B.)
10
15
18
19
20
21
25
kWt
kWe
kWt
kWe
kWt
kWe
kWt
kWe
kWt
kWe
kWt
kWe
kWt
kWe
-5 / -5,4
208,8
37,4
207,5
39,8
208,1
41,5
208,5
42,1
209,0
42,8
209,7
43,4
213,4
46,3
0 / -0,6
232,2
40,4
231,4
43,3
232,2
45,3
232,7
46,0
233,3
46,8
234,0
47,6
238,0
50,9
5 / 3,9
258,2
44,2
257,2
47,5
257,3
49,7
257,5
50,5
257,8
51,3
258,1
52,1
260,0
55,7
7 / 6,1
272,5
46,4
271,0
49,9
270,5
52,2
270,4
53,0
270,3
53,8
270,3
54,7
270,5
58,1
10 / 8,2
286,9
48,8
284,9
52,4
283,6
54,8
283,1
55,6
282,7
56,4
282,2
57,2
280,3
60,6
15 / 13
323,3
54,9
319,3
59,0
315,5
61,3
313,9
62,1
312,2
62,9
310,4
63,6
302,0
66,6
-5 / -5,4
230,1
42,5
229,3
44,9
229,9
46,7
230,3
47,3
230,7
48,0
231,3
48,7
234,3
51,7
0 / -0,6
257,1
45,8
255,3
48,7
255,1
50,8
255,2
51,5
255,4
52,3
255,6
53,1
257,3
56,4
5 / 3,9
283,9
49,8
283,1
53,4
282,8
55,8
282,7
56,6
282,6
57,4
282,5
58,3
282,4
61,9
7 / 6,1
297,7
52,0
297,9
56,1
297,7
58,6
297,5
59,5
297,3
60,3
297,1
61,2
295,9
64,9
10 / 8,2
311,1
54,4
312,8
58,8
312,7
61,5
312,5
62,4
312,3
63,4
311,9
64,3
309,6
68,0
15 / 13
343,1
60,4
349,5
66,0
350,3
69,1
350,1
70,1
349,7
71,1
349,0
72,1
343,8
75,9
Ta = Outside air temperature (°C)
DB = dry bulb
WB = wet bulb
kWt = Heating capacity (kW)
with coils free of ice
kWe = Compressor power input in kW
Performance data are referred to operation with 30% of fresh air intake and same amount of air exhaust. (construction configuration C)
not all thermal yields take into account the heat dissipated by the fan motors
INTEGRATED HEATING CAPACITIES
Air temperature external exchanger inlet °C (D.B. / W.B.)
Heating capacity multiplication coefficient
-5 / -5.4
0,89
0 / -0.6
0,88
5 / 3.9
0,94
OTHERS
1
BT08A006GB-03
To obtain the integrated heating capacities (the real heating capacity considering the defrost cycles too), multiply the kWt value in the heating performance tables by the following coefficient.
DB = dry bulb
WB = wet bulb
In case of below zero air ambient temperature with a long period of heat pump operating mode it is necessary to help the evacuation of the water produced during the defrost cycle; this to
avoid the formation of ice in the unit basement. Pay attention that the evacuation will not create inconveniences to things or persons.
21
PACKAGED
362 - 904
AIR FLOW: HIGH
Size
362
402
452
464
524
604
704
804
904
6666
570
7222
570
7500
450
9722
570
10833
510
11667
570
12222
570
14722
570
15556
570
AIR HANDLING SECTION FANS (OUTLET)
Air flow
Max outside static pressure
l/s
Pa
COOLING PERFORMANCE
Size
Ta
(°C)
DB/WB
35
40
kWe
kWs
kWf
kWe
kWs
kWf
kWe
kWs
kWf
kWe
kWs
kWf
kWe
kWs
16 / 12
105,9
21,0
78,1
106,3
23,1
76,1
106,6
24,0
75,2
107,4
25,4
74,0
109,3
27,9
71,9
111,4
30,0
70,2
20 / 14
110,1
21,4
89,8
110,1
23,6
87,4
110,3
24,5
86,5
110,9
25,9
85,0
112,3
28,4
82,6
114,1
30,5
80,7
24 / 17
116,3
22,2
95,8
116,2
24,3
93,2
116,3
25,2
92,2
116,6
26,7
90,6
117,7
29,2
88,1
118,9
31,4
86,0
26 / 19
120,4
22,7
95,2
120,5
24,8
92,7
120,6
25,7
91,7
120,9
27,2
90,2
121,7
29,8
87,7
122,6
32,1
85,7
27 / 19,5
121,4
22,8
98,1
121,6
24,9
95,7
121,7
25,8
94,7
122,0
27,3
93,2
122,8
29,9
90,8
123,7
32,3
88,8
28 / 21
124,5
23,2
93,7
124,9
25,3
91,5
125,1
26,2
90,6
125,5
27,7
89,2
126,2
30,4
87,0
16 / 12
117,0
24,4
80,0
117,6
26,8
78,0
118,0
27,7
77,2
118,9
29,3
76,0
120,7
31,9
74,0
122,6
34,1
72,4
20 / 14
120,5
25,1
97,8
121,2
27,6
95,4
121,6
28,6
94,4
122,2
30,1
93,0
123,5
32,7
90,6
124,6
34,9
88,6
24 / 17
127,2
26,0
100,9
127,2
28,4
98,3
127,4
29,4
97,3
127,8
30,9
95,7
128,8
33,6
93,1
130,0
35,7
91,1
26 / 19
132,6
26,4
102,1
131,6
28,8
99,7
131,6
29,7
98,7
131,9
31,3
97,3
133,2
33,9
94,8
135,2
36,1
92,9
27 / 19,5
134,1
26,5
106,9
132,8
28,8
104,6
132,7
29,8
103,7
132,9
31,3
102,3
134,5
34,0
99,9
136,7
36,2
98,1
28 / 21
138,8
26,7
111,3
136,4
28,9
109,3
136,0
29,9
108,5
136,2
31,4
107,3
138,3
34,1
105,3
141,6
36,4
103,7
16 / 12
125,1
28,1
82,2
123,9
31,1
78,8
123,9
32,4
77,5
124,5
34,2
75,5
127,0
37,3
72,1
130,3
39,7
69,4
20 / 14
129,2
28,8
102,5
129,7
31,6
99,5
130,0
32,8
98,2
130,4
34,6
96,4
131,4
37,8
93,3
132,4
40,5
90,9
24 / 17
136,2
29,9
108,5
137,2
32,6
105,7
137,5
33,7
104,6
137,7
35,5
102,9
137,6
38,8
100,2
137,2
41,6
97,9
26 / 19
141,5
30,6
106,7
141,4
33,4
104,1
141,4
34,6
103,0
141,4
36,4
101,4
141,5
39,6
98,7
141,5
42,3
96,6
27 / 19,5
142,8
30,7
109,9
142,4
33,6
107,2
142,3
34,8
106,2
142,2
36,6
104,6
142,4
39,8
101,9
142,8
42,5
99,8
28 / 21
147,1
31,2
106,7
144,9
34,3
104,1
144,5
35,5
103,0
144,2
37,4
101,4
145,1
40,5
98,8
146,8
43,0
96,7
16 / 12
142,2
26,4
97,7
144,2
28,9
93,9
145,1
29,9
92,4
146,4
31,5
90,1
148,7
34,4
86,3
150,6
36,8
83,3
20 / 14
146,8
27,3
124,9
149,0
29,9
122,1
149,8
30,9
120,9
151,0
32,5
119,2
152,9
35,4
116,3
154,4
37,8
114,0
24 / 17
154,8
28,4
123,9
156,4
31,0
121,4
157,0
32,1
120,4
157,9
33,7
118,9
159,5
36,5
116,3
160,7
38,9
114,3
26 / 19
160,8
29,0
125,4
161,5
31,6
122,5
161,9
32,7
121,3
162,6
34,3
119,6
163,9
37,1
116,6
165,2
39,4
114,3
27 / 19,5
162,4
29,1
132,1
162,8
31,7
128,9
163,1
32,8
127,7
163,7
34,4
125,8
165,0
37,3
122,7
166,4
39,6
120,2
28 / 21
167,3
29,4
144,5
166,8
32,1
140,6
166,9
33,1
139,1
167,2
34,8
136,8
168,4
37,6
132,9
16 / 12
158,6
32,6
115,3
159,7
36,2
111,5
160,1
37,7
109,9
160,6
40,0
107,7
161,4
44,0
103,9
161,8
47,4
100,8
20 / 14
164,9
33,5
135,5
165,2
37,1
132,5
165,3
38,6
131,2
165,6
40,8
129,4
166,2
44,7
126,3
166,8
47,8
123,9
24 / 17
174,1
34,6
143,8
173,9
38,2
140,9
173,9
39,7
139,7
173,8
41,9
138,0
173,8
45,7
135,0
173,9
48,8
132,7
26 / 19
180,2
35,2
143,2
180,1
38,7
139,7
180,0
40,2
138,3
179,7
42,5
136,2
179,1
46,4
132,7
178,4
49,7
129,8
27 / 19,5
181,7
35,3
148,3
181,7
38,8
144,6
181,6
40,3
143,1
181,2
42,6
140,9
180,4
46,6
137,1
179,5
49,9
134,1
28 / 21
186,2
35,6
144,0
186,5
39,1
139,4
186,4
40,6
137,5
186,0
42,9
134,8
184,5
47,1
130,2
16 / 12
183,8
36,4
125,7
185,6
40,3
121,6
186,3
42,0
120,0
187,1
44,4
117,5
188,3
48,7
113,4
189,0
52,3
110,2
20 / 14
190,4
37,3
154,3
191,6
41,2
150,1
192,1
42,8
148,4
192,8
45,3
145,9
194,0
49,7
141,7
195,0
53,3
138,3
24 / 17
200,9
38,5
166,0
201,3
42,3
161,8
201,6
44,0
160,2
202,1
46,5
157,7
203,4
50,9
153,6
204,7
54,6
150,2
26 / 19
208,3
39,2
164,0
208,3
43,1
160,1
208,5
44,7
158,5
208,9
47,2
156,2
210,2
51,5
152,2
211,7
55,2
149,1
27 / 19,5
210,2
39,4
169,0
210,1
43,2
165,2
210,3
44,9
163,6
210,7
47,3
161,3
212,0
51,7
157,5
213,5
55,4
154,4
28 / 21
216,0
39,9
161,5
215,7
43,7
157,9
215,8
45,3
156,5
216,2
47,8
154,3
217,5
52,1
150,8
16 / 12
201,3
43,8
140,8
202,2
48,2
135,1
202,8
50,0
132,7
204,0
53,0
129,3
206,9
58,4
123,5
209,8
63,0
118,9
20 / 14
209,8
44,8
167,2
209,7
49,3
162,2
210,0
51,2
160,2
210,6
54,2
157,2
212,3
59,5
152,3
214,4
64,0
148,3
24 / 17
222,3
46,3
176,9
221,3
50,9
172,6
221,2
52,8
170,8
221,3
55,9
168,3
222,4
61,2
164,0
224,0
65,8
160,5
26 / 19
230,5
47,2
174,9
229,1
51,9
170,7
229,0
53,8
169,0
229,1
56,9
166,5
230,4
62,4
162,3
232,3
67,1
158,9
27 / 19,5
232,5
47,4
180,2
231,1
52,1
176,0
231,0
54,1
174,3
231,1
57,2
171,7
232,5
62,7
167,5
234,6
67,4
164,1
28 / 21
238,5
48,1
174,0
237,1
52,8
169,6
237,0
54,8
167,8
237,4
58,0
165,2
239,3
63,6
160,7
242,0
68,5
157,2
Ta = ambient air temperature D.B/W.B
DB = dry bulb
WB = wet bulb
kWf = Cooling capacity in kW
kWe = Compressor power input in kW
kWs = sensible cooling capacity (kW)
Performance data are referred to operation with 30% of fresh air intake and same amount of air exhaust. (construction configuration C)
the cooling capacities have not accounted for the heat dissipation of the centrifugal fan motors.
22
44
kWf
524
BT08A006GB-03
32
kWs
464
704
30
kWe
402
604
25
kWf
362
452
EXTERNAL EXCHANGER AIR INTAKE TEMPERATURE (ºC)
PACKAGED
362 - 904
AIR FLOW: HIGH
COOLING PERFORMANCE
Size
804
904
Ta
(°C)
DB/WB
EXTERNAL EXCHANGER AIR INTAKE TEMPERATURE (ºC)
25
30
32
35
40
44
kWf
kWe
kWs
kWf
kWe
kWs
kWf
kWe
kWs
kWf
kWe
kWs
kWf
kWe
kWs
kWf
kWe
kWs
16 / 12
247,6
46,9
128,3
249,2
51,7
121,9
249,9
53,7
119,4
250,9
56,8
115,6
252,6
62,3
109,2
253,9
67,0
104,1
20 / 14
256,8
47,9
202,3
257,5
52,7
196,2
258,0
54,8
193,7
258,8
57,9
190,0
260,6
63,4
183,9
262,5
68,1
179,0
24 / 17
271,2
49,3
224,9
271,7
54,2
219,1
271,9
56,2
216,8
272,3
59,3
213,3
273,2
64,8
207,4
274,1
69,4
202,8
26 / 19
281,2
50,2
220,2
282,2
55,0
214,5
282,4
57,0
212,3
282,5
60,1
208,9
282,0
65,5
203,2
281,0
70,0
198,7
27 / 19,5
283,8
50,5
227,0
285,0
55,2
221,4
285,2
57,2
219,1
285,1
60,3
215,8
284,2
65,6
210,2
282,7
70,1
205,7
28 / 21
291,5
51,1
220,3
293,7
55,8
214,8
293,9
57,7
212,6
293,5
60,7
209,3
291,0
66,0
203,9
16 / 12
267,8
53,9
192,9
269,4
59,2
185,9
270,1
61,5
183,1
271,3
65,1
178,9
273,6
71,3
171,9
275,6
76,7
166,3
20 / 14
277,7
55,2
223,4
277,7
60,7
217,0
278,0
63,0
214,4
278,9
66,5
210,5
281,2
72,7
204,1
283,8
77,8
199,0
24 / 17
293,4
56,8
239,1
292,3
62,6
233,2
292,2
64,9
230,8
292,5
68,5
227,2
294,1
74,7
221,3
296,3
79,7
216,5
26 / 19
304,4
57,6
237,9
303,4
63,5
232,0
303,3
65,9
229,7
303,2
69,6
226,2
303,8
76,0
220,3
304,8
81,2
215,6
27 / 19,5
307,2
57,8
246,0
306,4
63,7
240,1
306,2
66,2
237,8
306,1
69,9
234,2
306,4
76,3
228,3
307,0
81,6
223,6
28 / 21
315,9
58,2
234,9
315,7
64,3
228,9
315,5
66,8
226,5
315,2
70,6
222,9
314,3
77,2
216,9
313,5
82,8
212,2
BT08A006GB-03
Ta = ambient air temperature D.B/W.B
DB = dry bulb
WB = wet bulb
kWf = Cooling capacity in kW
kWe = Compressor power input in kW
kWs = sensible cooling capacity (kW)
Performance data are referred to operation with 30% of fresh air intake and same amount of air exhaust. (construction configuration C)
the cooling capacities have not accounted for the heat dissipation of the centrifugal fan motors.
23
PACKAGED
362 - 904
AIR FLOW: HIGH
Size
362
402
452
464
524
604
704
804
904
6666
570
7222
570
7500
450
9722
570
10833
510
11667
570
12222
570
14722
570
15556
570
AIR HANDLING SECTION FANS (OUTLET)
Air flow
Max outside static pressure
l/s
Pa
HEATING PERFORMANCE
Size
Ta
(°C)
DB/WB
RETURN AIR TEMPERATURE (D.B.)
10
kWt
15
kWe
-5 / -5,4
18
19
20
21
25
kWt
kWe
kWt
kWe
kWt
kWe
kWt
kWe
kWt
kWe
kWt
kWe
92,2
16,2
92,4
16,8
92,5
17,0
92,6
17,2
92,6
17,5
92,8
18,4
0 / -0,6
102,2
16,3
101,9
17,3
102,0
18,0
102,1
18,2
102,2
18,5
102,4
18,7
103,1
19,9
5 / 3,9
111,3
17,3
111,7
18,5
112,0
19,3
112,1
19,6
112,3
19,9
112,4
20,2
113,1
21,5
362
7 / 6,1
115,5
17,9
116,7
19,2
117,2
20,1
117,4
20,4
117,5
20,7
117,7
21,0
118,1
22,3
10 / 8,2
119,4
18,4
121,5
19,9
122,4
20,9
122,6
21,2
122,7
21,5
122,8
21,8
122,9
23,2
15 / 13
127,6
19,7
133,2
21,7
134,9
22,8
135,2
23,2
135,4
23,6
135,4
24,0
134,2
25,4
101,9
18,6
102,8
19,4
103,1
19,6
103,4
19,9
103,7
20,2
105,2
21,4
-5 / -5,4
402
0 / -0,6
112,4
18,6
113,3
19,9
113,9
20,8
114,2
21,1
114,4
21,4
114,7
21,7
115,8
23,1
5 / 3,9
123,8
20,0
124,5
21,4
125,0
22,4
125,2
22,7
125,4
23,1
125,6
23,4
126,5
24,9
7 / 6,1
129,5
20,7
130,2
22,3
130,7
23,3
130,9
23,6
131,1
24,0
131,3
24,4
132,0
26,0
10 / 8,2
135,1
21,4
135,8
23,1
136,3
24,2
136,5
24,6
136,6
25,0
136,8
25,4
137,5
27,0
15 / 13
148,1
23,3
149,0
25,3
149,5
26,5
149,7
27,0
149,8
27,4
150,0
27,8
150,5
29,6
113,4
21,6
114,7
22,4
115,3
22,8
116,0
23,1
116,8
23,4
120,7
25,0
0 / -0,6
123,6
21,5
124,6
22,9
125,7
23,9
126,1
24,3
126,5
24,6
127,0
25,0
129,3
26,7
5 / 3,9
135,1
22,9
136,2
24,6
136,9
25,7
137,2
26,1
137,5
26,5
137,8
26,9
139,1
28,6
7 / 6,1
141,3
23,7
142,2
25,5
142,8
26,7
143,0
27,1
143,2
27,5
143,5
27,9
144,4
29,7
10 / 8,2
147,4
24,6
148,1
26,5
148,6
27,7
148,8
28,1
149,0
28,6
149,1
29,0
149,8
30,9
15 / 13
162,5
26,9
162,6
29,0
162,8
30,4
162,8
30,8
162,9
31,3
163,0
31,8
163,5
33,8
128,8
20,9
129,8
21,9
129,7
22,2
129,3
22,4
128,6
22,7
123,6
23,7
0 / -0,6
133,6
20,3
135,5
22,0
137,0
23,1
137,5
23,5
138,1
23,9
138,6
24,3
141,1
25,9
5 / 3,9
145,6
21,8
146,4
23,5
148,0
24,7
148,7
25,2
149,5
25,6
150,4
26,1
155,0
28,1
-5 / -5,4
452
-5 / -5,4
464
7 / 6,1
152,0
22,6
153,3
24,4
154,9
25,7
155,6
26,2
156,3
26,6
157,1
27,1
160,9
29,2
10 / 8,2
158,4
23,4
160,9
25,4
162,4
26,7
162,9
27,2
163,4
27,7
163,9
28,2
165,9
30,2
15 / 13
174,2
25,3
181,9
28,1
183,0
29,5
182,8
30,0
182,3
30,5
181,5
30,9
175,4
32,5
130,0
24,3
131,1
25,3
132,1
25,8
133,3
26,2
134,8
26,7
143,5
28,8
-5 / -5,4
524
0 / -0,6
150,2
24,6
149,5
26,2
150,3
27,4
150,8
27,9
151,3
28,3
152,0
28,8
155,8
30,8
5 / 3,9
166,2
26,3
166,8
28,3
167,3
29,7
167,5
30,1
167,8
30,6
168,0
31,1
169,3
33,2
7 / 6,1
174,1
27,3
174,8
29,4
175,3
30,8
175,5
31,3
175,6
31,8
175,8
32,3
176,5
34,5
10 / 8,2
181,7
28,2
182,3
30,5
182,7
32,0
182,9
32,5
183,0
33,1
183,2
33,6
183,9
35,8
15 / 13
199,3
30,7
198,6
33,3
199,0
34,9
199,2
35,5
199,6
36,1
199,9
36,7
202,1
39,2
158,4
27,4
160,8
28,7
161,4
29,2
161,9
29,7
162,3
30,1
163,0
31,9
BT08A006GB-03
-5 / -5,4
0 / -0,6
169,4
26,9
176,4
29,5
178,5
31,0
178,8
31,4
179,0
31,9
178,9
32,4
177,0
34,2
5 / 3,9
187,6
29,1
193,9
31,8
195,5
33,3
195,6
33,8
195,6
34,3
195,4
34,8
192,7
36,8
7 / 6,1
197,3
30,3
202,6
33,0
203,9
34,6
204,0
35,1
204,0
35,6
203,8
36,2
201,3
38,3
10 / 8,2
207,0
31,5
211,1
34,2
212,1
35,8
212,2
36,4
212,1
36,9
212,0
37,5
210,1
39,7
15 / 13
230,9
34,4
230,8
37,1
231,0
38,9
231,2
39,5
231,3
40,1
231,5
40,8
232,3
43,5
176,2
33,0
175,4
34,2
175,8
34,6
176,4
35,1
177,4
35,6
184,0
38,0
0 / -0,6
195,5
33,1
196,0
35,3
196,6
36,8
196,9
37,3
197,1
37,9
197,4
38,4
198,8
40,7
5 / 3,9
212,4
35,3
215,3
38,0
216,3
39,7
216,6
40,3
216,7
40,9
216,8
41,5
216,6
44,0
7 / 6,1
222,6
36,6
224,9
39,5
225,9
41,3
226,1
41,9
226,3
42,6
226,5
43,2
226,7
45,9
10 / 8,2
233,4
38,0
234,3
41,0
235,0
42,9
235,3
43,6
235,5
44,3
235,8
45,0
237,2
47,9
15 / 13
262,4
41,8
256,1
44,7
255,6
46,9
256,0
47,7
256,7
48,5
257,6
49,3
264,2
53,0
604
-5 / -5,4
704
24
Ta = Outside air temperature (°C)
DB = dry bulb
WB = wet bulb
kWt = Heating capacity (kW)
with coils free of ice
kWe = Compressor power input in kW
Performance data are referred to operation with 30% of fresh air intake and same amount of air exhaust. (construction configuration C)
not all thermal yields take into account the heat dissipated by the fan motors
PACKAGED
362 - 904
AIR FLOW: HIGH
HEATING PERFORMANCE
Size
Ta
(°C)
DB/WB
RETURN AIR TEMPERATURE (D.B.)
10
kWt
15
kWe
-5 / -5,4
804
19
20
21
25
kWt
kWe
kWt
kWe
kWt
kWe
kWt
kWe
kWt
kWe
kWt
kWe
212,0
36,3
213,9
37,8
214,5
38,3
215,1
38,8
215,7
39,3
217,9
41,6
0 / -0,6
240,4
36,7
241,0
39,1
241,6
40,7
241,8
41,2
242,0
41,8
242,2
42,4
243,4
44,9
5 / 3,9
267,3
39,3
267,0
42,1
267,0
43,9
267,0
44,5
267,1
45,1
267,2
45,8
267,8
48,6
7 / 6,1
279,5
40,7
279,2
43,6
279,2
45,6
279,3
46,2
279,4
46,9
279,5
47,6
280,0
50,5
10 / 8,2
290,4
42,1
290,6
45,2
290,8
47,3
290,9
48,0
291,0
48,7
291,1
49,5
291,8
52,5
15 / 13
313,2
45,4
315,6
49,2
316,8
51,6
317,2
52,4
317,5
53,2
317,9
54,1
319,1
57,5
233,6
41,8
235,4
43,3
236,3
43,8
237,2
44,4
238,2
45,0
243,4
47,6
0 / -0,6
260,6
42,1
262,3
44,7
263,6
46,4
264,1
47,0
264,6
47,7
265,1
48,3
267,5
51,2
5 / 3,9
289,7
45,0
290,5
48,0
291,1
50,0
291,3
50,7
291,5
51,5
291,7
52,2
292,5
55,3
7 / 6,1
304,9
46,7
304,8
49,9
304,9
52,0
305,0
52,8
305,0
53,5
305,1
54,3
305,7
57,6
10 / 8,2
320,1
48,4
318,7
51,9
318,3
54,1
318,3
54,9
318,3
55,7
318,3
56,5
318,8
60,0
15 / 13
357,1
53,1
351,6
56,9
349,9
59,4
349,6
60,3
349,4
61,2
349,4
62,1
350,7
65,9
-5 / -5,4
904
18
Ta = Outside air temperature (°C)
DB = dry bulb
WB = wet bulb
kWt = Heating capacity (kW)
with coils free of ice
kWe = Compressor power input in kW
Performance data are referred to operation with 30% of fresh air intake and same amount of air exhaust. (construction configuration C)
not all thermal yields take into account the heat dissipated by the fan motors
INTEGRATED HEATING CAPACITIES
Air temperature external exchanger inlet °C (D.B. / W.B.)
Heating capacity multiplication coefficient
-5 / -5.4
0,89
0 / -0.6
0,88
5 / 3.9
0,94
OTHERS
1
To obtain the integrated heating capacities (the real heating capacity considering the defrost cycles too), multiply the kWt value in the heating performance tables by the following coefficient.
DB = dry bulb
WB = wet bulb
In case of below zero air ambient temperature with a long period of heat pump operating mode it is necessary to help the evacuation of the water produced during the defrost cycle; this to
avoid the formation of ice in the unit basement. Pay attention that the evacuation will not create inconveniences to things or persons.
PRESSURE DROPS OF OPTIONAL COMPONENTS
SIZE
PRESSURE DROP
CHW2 2 rows hot water coil
GH03 Gas re-heating module from 96 kW
GH05 Gas re-heating module from 150 kW
GH06 Gas re-heating module from 200 kW
GH08 Gas re-heating module from 300 kW
CPHG Hot gas re-heating coil
F7
High efficiency F7 air filter
FES
High efficiency H10 electrostatic air filter
HWS Water to waste evaporating wet-deck humidifier
Pa
Pa
Pa
Pa
Pa
Pa
1 Pa
Pa
Pa
362
402
452
464
524
604
704
804
904
28
90
90
90
20
140
40
21
32
95
95
95
22
160
40
23
35
100
100
100
24
180
40
25
30
85
85
85
120
18
100
40
18
36
90
90
90
130
20
120
40
20
42
95
95
95
140
22
140
40
22
50
100
100
100
150
24
160
40
24
47
95
95
140
22
140
40
21
55
100
100
150
24
160
40
23
BT08A006GB-03
To obtain the performance required of the supply fans, add the value of desired static pressure to the value in Pa
shown in the table of pressure drops of the optional components.
The values shown are to be considered approximate for units operating power in normal use with standard air flow rate.
(1)Pressure drops with filters with average dirtiness
25
PACKAGED
362 - 904
PERFORMANCES OF SUPPLY AIR FANS
EXTERNAL STATIC PRESSURE (Pa)
Air flow
l/s
AIR FLOW: STANDARD
120
150
180
210
240
270
300
330
360
390
420
450
510
570
5555
5555
5555
5555
5555
5555
5555
5555
5555
5555
5555
5555
5555
5555
362
Fan RPM
rpm
718
742
766
790
814
837
860
883
905
927
949
971
1013
1054
Motor shaft input power
kW
4,96
5,22
5,48
5,75
6,02
6,29
6,57
6,85
7,14
7,42
7,71
8,01
8,6
9,2
Sound pressure level
dB
86
87
87
87
87
88
88
88
88
89
89
89
90
91
F.L.I. - Single supply fan
kW
7,5
7,5
7,5
7,5
7,5
7,5
7,5
9
9
9
9
9
11
11
A
14,9
14,9
14,9
14,9
14,9
14,9
14,9
19,0
19,0
19,0
19,0
19,0
21,0
21,0
F.L.A.
Transmission code (fan)
PF 2A 250
PF 2A 224
Transmission code (motor)
Air flow
PV 2A 177
402
l/s
6111
6111
6111
6111
6111
6111
6111
6111
6111
6111
6111
6111
6111
6111
Fan RPM
rpm
767
790
812
834
856
878
899
920
941
962
982
1003
1042
1081
Motor shaft input power
kW
6,32
6,6
6,88
7,17
7,46
7,76
8,06
8,36
8,67
8,97
9,28
9,6
10,24
10,9
Sound pressure level
dB
88
89
89
89
89
89
89
90
90
90
91
91
91
92
F.L.I. - Single supply fan
kW
7,5
7,5
7,5
7,5
9
9
9
9
11
11
11
11
11
11
A
14,9
14,9
14,9
14,9
19,0
19,0
19,0
19,0
21,0
21,0
21,0
21,0
21,0
21,0
F.L.A.
Transmission code (fan)
PF 2A 250
Transmission code (motor)
Air flow
PF 2A 236
PF 2A 224
PV 2A 156
PV 2A 177
452
l/s
6666
6666
6666
6666
6666
6666
6666
6666
6666
6666
6666
6666
6666
6666
Fan RPM
rpm
820
841
862
882
902
922
942
962
982
1001
1020
1040
1077
1114
Motor shaft input power
kW
7,95
8,26
8,56
8,87
9,19
9,51
9,83
10,15
10,48
10,81
11,14
11,47
11,65
12,3
Sound pressure level
dB
90
90
90
91
91
91
91
91
92
92
92
92
93
93
F.L.I. - Single supply fan
kW
9
9
9
9
11
11
11
11
11
11
15
15
15
15
A
19,0
19,0
19,0
19,0
21,0
21,0
21,0
21,0
21,0
21,0
28,5
28,5
28,5
28,5
F.L.A.
Transmission code (fan)
PF 2A 280
PF 2A 250
Transmission code (motor)
Air flow
PF 2A 315
PV 2A 177
PF 2A 224
PF 2A 236
464
l/s
8056
8056
8056
8056
8056
8056
8056
8056
8056
8056
8056
8056
8056
8056
Fan RPM
rpm
680
705
730
756
781
806
831
856
881
905
930
954
1002
1049
Motor shaft input power
kW
6,9
7,3
7,7
8,2
8,6
9,1
9,5
10
10,5
11,1
11,6
12,2
12,7
13,8
Sound pressure level
dB
86
86
86
87
87
88
88
89
89
90
90
91
92
93
F.L.I. - Single supply fan
kW
9
9
9
9
9
11
11
11
11
15
15
15
15
15
A
19,0
19,0
19,0
19,0
19,0
21,0
21,0
21,0
21,0
28,5
28,5
28,5
28,5
28,5
F.L.A.
Transmission code (fan)
PF 2A 315
PF 2A 280
Transmission code (motor)
Air flow
PF3A300
PV 2A 177
PF 3A 280
PF 3A 180
PF3A300 PF3A280
PF 3A 200
524
l/s
9028
9028
9028
9028
9028
9028
9028
9028
9028
9028
9028
9028
9028
9028
Fan RPM
rpm
731
754
776
799
821
844
866
889
911
934
956
978
1022
1065
Motor shaft input power
kW
9,1
9,5
10
10,4
10,9
11,4
11,9
12,2
12,4
12,9
13,4
13,9
15,1
16,2
Sound pressure level
dB
88
88
89
89
89
89
90
90
91
91
92
92
93
93
F.L.I. - Single supply fan
kW
11
11
11
11
15
15
15
15
15
15
15
15
18,5
18,5
A
21.0
21,0
21,0
21,0
28,5
28,5
28,5
28,5
28,5
28,5
28,5
28,5
35,0
35,0
F.L.A.
Transmission code (fan)
PF 2A 300
Transmission code (motor)
Air flow
PF 3A 300
PV 2A 177
PF 3A 170
PF 3A 180
PF 3A 280
PF 3A 190
PF 3A 200
604
l/s
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
Fan RPM
rpm
792
812
833
853
873
894
914
935
955
975
995
1016
1056
-
Motor shaft input power
kW
11,9
12,1
12,3
12,8
13,3
13,7
14,2
14,8
15,3
15,8
16,4
16,9
18,1
-
Sound pressure level
dB
90
90
91
91
91
91
92
92
92
93
93
93
94
-
F.L.I. - Single supply fan
kW
15
15
15
15
15
15
15
15
18,5
18,5
18,5
18,5
18,5
-
A
28,5
28,5
28,5
28,5
28,5
28,5
28,5
28,5
35,0
35,0
35,0
35,0
35,0
-
F.L.A.
Transmission code (fan)
PF 3A 315
Transmission code (motor)
Air flow
704
PF 3A 170
l/s
11111
11111
PF 3A 180
11111
11111
PF 3A 300
PF 3A 190
11111
PF 3A 280
PF 3A 200
11111
11111
-
11111
11111
11111
11111
11111
11111
11111
Fan RPM
rpm
855
873
891
910
928
946
965
983
1001
1020
1038
1056
1093
1129
Motor shaft input power
kW
14,9
15,4
15,9
16,4
16,9
17,4
18
18,5
19
19,6
20,2
20,8
21,9
23,2
Sound pressure level
dB
93
93
93
93
93
94
94
94
94
94
94
95
95
96
F.L.I. - Single supply fan
kW
18,5
18,5
18,5
18,5
18,5
18,5
18,5
22
22
22
22
22
30
30
A
35,0
35,0
35,0
35,0
35,0
35,0
35,0
41,0
41,0
41,0
41,0
41,0
57,0
57,0
F.L.A.
Transmission code (fan)
PF3A300
Transmission code (motor)
Air flow
804
BT08A006GB-03
PF 2A 236
PV 2A 156
PF 3A 280
PF 3A 170
PF 3A 300
PF 3A 180
PF 3A 280
PF 3A 300
PF 3A 200
PF 3A 224
l/s
12500
12500
12500
12500
12500
12500
12500
12500
12500
12500
12500
12500
12500
12500
Fan RPM
rpm
742
761
780
798
816
835
853
871
889
907
925
943
978
1012
Motor shaft input power
kW
14,2
14,7
15,2
15,8
16,4
16,9
17,5
18,1
18,7
19,3
20
20,6
21,9
23,2
Sound pressure level
dB
90
90
91
91
91
91
92
92
92
92
92
93
93
94
F.L.I. - Single supply fan
kW
18,5
18,5
18,5
18,5
18,5
18,5
18,5
18,5
22
22
22
22
30
30
A
35,0
35,0
35,0
35,0
35,0
35,0
35,0
35,0
41,0
41,0
41,0
41,0
57,0
57,0
F.L.A.
Transmission code (fan)
PF 3A 355
Transmission code (motor)
Air flow
PF 3A 180
PF 3A 315
PF 3A 190
PF 3A 300
PF 3A 180
PF 5A 315
PF 3A 190
PF 5A 224
904
l/s
13889
13889
13889
13889
13889
13889
13889
13889
13889
13889
13889
13889
13889
13889
Fan RPM
rpm
794
811
828
845
862
878
895
911
928
944
961
977
1009
1041
Motor shaft input power
kW
18,3
18,9
19,5
20,1
20,7
21,3
21,9
22,5
23,2
23,8
24,5
25,2
26,5
27,9
Sound pressure level
dB
93
93
93
93
93
93
93
94
94
94
94
94
95
95
F.L.I. - Single supply fan
kW
22
22
22
22
22
22
30
30
30
30
30
30
30
30
A
41,0
41,0
41,0
41,0
41,0
41,0
57,0
57,0
57,0
57,0
57,0
57,0
57,0
57,0
F.L.A.
Transmission code (fan)
PF 3A 355
PF 3A 315
PF 5A 355
Transmission code (motor)
PF 3A 200
PF 3A 190
PF 5A 224
PF 5A 315
PF 5A 200
PF 5A 224
The performance takes into account the pressure drops in the unit (pressure drops in treatment coil, standard filters, etc.).
To determine the performance required by the fans, it is necessary to add the desired usable static pressure to the pressure drops of any accessories (e.g. hot water coils, gas module,
additional filter section, etc.).
The value of absorbed electrical power has already been corrected by a factor that takes into account the losses in transmission and a minimum tolerance on the number of revs of the fan.
26
PACKAGED
362 - 904
INTAKE AIR FLOW: STANDARD AIR FLOW
PERFORMANCES OF RETURN AIR FANS
EXTERNAL STATIC PRESSURE (Pa)
l/s
60
90
120
150
180
210
240
270
300
330
360
390
420
450
4444
4444
4444
4444
4444
4444
4444
4444
4444
4444
4444
4444
4444
4444
362
Fan RPM
rpm
472
504
536
567
598
628
658
687
715
743
770
796
822
848
Motor shaft input power
kW
1,91
2,1
2,3
2,5
2,71
2,92
3,14
3,36
3,58
3,81
4,05
4,28
4,52
4,76
Sound pressure level
dB
81
81
81
82
82
82
82
83
83
84
84
84
85
85
F.L.I. - Single supply fan
kW
3
3
3
3
3
3
4
4
4
4
5,5
5,5
5,5
5,5
A
6,5
6,5
6,5
6,5
6,5
6,5
8,3
8,3
8,3
8,3
11,2
11,2
11,2
11,2
F.L.A.
Transmission code (fan)
PF 1A 400
PF 1A 315
Transmission code (motor)
Air flow
PF 1A 280
PF 1A 400
PV 1A 156
PV 1A 250
402
l/s
4888
4888
4888
4888
4888
4888
4888
4888
4888
4888
4888
4888
4888
Fan RPM
rpm
510
539
568
597
626
653
681
708
735
761
786
812
836
861
Motor shaft input power
kW
2,47
2,68
2,89
3,11
3,33
3,56
3,79
4,03
4,27
4,52
4,76
5,02
5,27
5,53
Sound pressure level
dB
83
83
83
84
84
84
84
84
85
85
85
86
86
86
F.L.I. - Single supply fan
kW
3
3
3
4
4
4
4
5,5
5,5
5,5
5,5
5,5
5,5
7,5
A
6,5
6,5
6,5
8,3
8,3
8,3
8,3
11,2
11,2
11,2
11,2
11,2
11,2
14,9
F.L.A.
Transmission code (fan)
PF 1A 355
PF 1A 315
Transmission code (motor)
Air flow
PF 1A 450
4888
PF 1A 400
PV 1A 156
PV 1A 250
452
l/s
5333
5333
5333
5333
5333
5333
5333
5333
5333
5333
5333
5333
5333
5333
Fan RPM
rpm
548
575
602
628
655
681
706
732
757
781
805
829
853
876
Motor shaft input power
kW
3,14
3,36
3,59
3,82
4,06
4,31
4,55
4,81
5,06
5,32
5,59
5,86
6,13
6,4
Sound pressure level
dB
85
85
85
85
85
86
86
86
86
86
87
87
87
88
F.L.I. - Single supply fan
kW
4
4
4
5,5
5,5
5,5
5,5
5,5
5,5
7,5
7,5
7,5
7,5
7,5
A
8,3
8,3
8,3
11,2
11,2
11,2
11,2
11,2
11,2
14,9
14,9
14,9
14,9
14,9
F.L.A.
Transmission code (fan)
PF 1A 355
Transmission code (motor)
Air flow
PF 1A 315
PF 1A 450
PF 1A 400
PV 1A 156
PV 1A 250
464
l/s
-
6444
6444
6444
6444
6444
6444
6444
6444
6444
6444
6444
6444
-
Fan RPM
rpm
-
507
539
571
602
634
665
696
727
757
787
817
846
-
Motor shaft input power
kW
-
3,1
3,4
3,7
4,1
4,4
4,8
5,2
5,6
6
6,5
6,9
7,4
-
Sound pressure level
dB
-
80
80
81
82
82
83
84
85
85
86
87
87
-
F.L.I. - Single supply fan
kW
-
4
4
4
5,5
5,5
5,5
5,5
7,5
7,5
7,5
7,5
7,5
-
8,3
8,3
8,3
11,2
11,2
11,2
11,2
14,9
14,9
14,9
14,9
14,9
-
F.L.A.
A
Transmission code (fan)
-
PF 1A 315
Transmission code (motor)
-
PV 1A 139
Air flow
PF 2A 300
-
PV 2A 156
PV 2A 177
-
524
l/s
7222
7222
7222
7222
7222
7222
7222
7222
7222
7222
7222
7222
7222
-
Fan RPM
rpm
517
546
574
608
630
658
686
715
742
770
798
825
852
-
Motor shaft input power
kW
3,8
4,1
4,5
4,8
5,2
5,5
5,9
6,3
6,7
7,2
7,6
8,1
8,6
-
Sound pressure level
dB
82
83
83
83
84
84
84
85
86
86
87
88
88
-
F.L.I. - Single supply fan
kW
5,5
5,5
5,5
5,5
5,5
7,5
7,5
7,5
7,5
7,5
9
9
9
-
A
11,2
11,2
11,2
11,2
11,2
14,9
14,9
14,9
14,9
14,9
19,0
19,0
19,0
-
F.L.A.
Transmission code (fan)
PF 2A 400
PF 2A 355
Transmission code (motor)
Air flow
PF 2A 300
PF 2A 280
PV 2A 164
-
PV 2A 177
-
604
l/s
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
Fan RPM
rpm
560
585
611
636
662
687
713
738
764
789
814
839
864
889
Motor shaft input power
kW
5
5,4
5,7
6,1
6,4
6,8
7,2
7,6
8,1
8,5
9
9,5
10
10,5
90
Sound pressure level
dB
85
85
85
85
86
86
86
87
87
87
88
88
89
F.L.I. - Single supply fan
kW
7,5
7,5
7,5
7,5
7,5
7,5
7,5
9
9
9
11
11
11
11
A
14,9
14,9
14,9
14,9
14,9
14,9
14,9
19,0
19,0
19,0
21,0
21,0
21,0
21,0
F.L.A.
Transmission code (fan)
PF 2A 355
PF 2A 315
Transmission code (motor)
Air flow
PF 2A 280
PF 2A 250
PV 2A 164
704
l/s
8889
8889
8889
8889
8889
8889
8889
8889
8889
8889
8889
8889
8889
Fan RPM
rpm
609
632
655
678
701
724
746
769
792
815
838
861
884
8889
906
Motor shaft input power
kW
6,7
7,1
7,4
7,8
8,2
8,6
9
9,5
9,9
10,4
10,9
11,3
11,8
12,2
91
Sound pressure level
dB
87
87
87
88
88
88
88
88
89
89
89
90
90
F.L.I. - Single supply fan
kW
7,5
7,5
7,5
9
9
9
11
11
11
11
15
15
15
15
A
14,9
14,9
14,9
19,0
19,0
19,0
21,0
21,0
21,0
21,0
28,5
28,5
28,5
28,5
F.L.A.
Transmission code (fan)
PF 2A 355
PF 2A 315
Transmission code (motor)
Air flow
PF 2A 280
PF 3A 315
PV 2A 164
PF 3A 190
804
l/s
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
Fan RPM
rpm
533
556
580
603
626
649
672
695
718
740
762
784
806
10000
827
Motor shaft input power
kW
6,4
6,8
7,2
7,7
8,1
8,6
9
9,5
10
10,5
11,1
11,6
11,7
12,2
89
Sound pressure level
dB
85
85
85
85
85
86
86
86
87
87
87
88
88
F.L.I. - Single supply fan
kW
7,5
7,5
7,5
9
9
9
11
11
11
11
15
15
15
15
A
14,9
14,9
14,9
19,0
19,0
19,0
21,0
21,0
21,0
21,0
28,5
28,5
28,5
28,5
F.L.A.
Transmission code (fan)
PF 2A 355
Transmission code (motor)
Air flow
PV 2A 156
PF 2A 315
PV 2A 164
PF 3A 355
PV 2A 177
PF 3A 190
PF 3A 200
904
l/s
11111
11111
11111
11111
11111
11111
11111
11111
11111
11111
11111
11111
11111
Fan RPM
rpm
578
599
620
642
663
684
704
725
746
766
787
807
827
847
Motor shaft input power
kW
8,5
8,9
9,4
9,8
10,3
10,8
11,3
11,8
12,1
12,4
12,9
13,4
14
14,6
Sound pressure level
dB
88
88
88
88
88
88
88
88
89
89
89
89
90
90
F.L.I. - Single supply fan
kW
11
11
11
11
11
11
15
15
15
15
15
15
15
15
A
21,0
21,0
21,0
21,0
21,0
21,0
28,5
28,5
28,5
28,5
28,5
28,5
28,5
28,5
F.L.A.
Transmission code (fan)
Transmission code (motor)
PF 2A 400
PF 2A 355
PV 2A 177
PF 3A 355
PF 3A 180
BT08A006GB-03
Air flow
11111
PF 3A 315
PF 3A 170
PF 3A 180
The value of absorbed electrical power has already been corrected by a factor that takes into account the losses in transmission and a minimum tolerance on the number of revs of the fan.
27
PACKAGED
362 - 904
AIR FLOW: REDUCED
PERFORMANCES OF SUPPLY AIR FANS
EXTERNAL STATIC PRESSURE (Pa)
Air flow
l/s
120
150
180
210
240
270
300
330
360
390
420
450
510
570
4444
4444
4444
4444
4444
4444
4444
4444
4444
4444
4444
4444
4444
4444
362
Fan RPM
rpm
638
667
696
724
752
779
805
831
856
881
905
929
975
1020
Motor shaft input power
kW
2,99
3,21
3,44
3,66
3,89
4,13
4,36
4,61
4,85
5,09
5,35
5,6
6,11
6,63
Sound pressure level
dB
82
83
83
83
84
84
85
85
86
86
86
87
88
88
F.L.I. - Single supply fan
kW
4
4
4
4
5,5
5,5
5,5
5,5
5,5
7,5
7,5
7,5
7,5
7,5
A
8,3
8,3
8,3
8,3
11,2
11,2
11,2
11,2
11,2
14,9
14,9
14,9
14,9
14,9
F.L.A.
Transmission code (fan)
PF 1A 250
Transmission code (motor)
Air flow
PF 2A 250
PV 1A 139
PF 2A 200
PV 2A 156
402
l/s
4888
4888
4888
4888
4888
4888
4888
4888
4888
4888
4888
4888
4888
4888
Fan RPM
rpm
681
708
735
761
786
812
836
861
885
908
931
954
998
1041
Motor shaft input power
kW
3,8
4,03
4,27
4,52
4,77
5,02
5,28
5,53
5,79
6,06
6,33
6,6
7,14
7,7
Sound pressure level
dB
84
84
85
85
85
86
86
86
87
87
88
88
89
89
F.L.I. - Single supply fan
kW
5,5
5,5
5,5
5,5
5,5
5,5
5,5
7,5
7,5
7,5
7,5
7,5
9
9
A
11,2
11,2
11,2
11,2
11,2
11,2
11,2
14,9
14,9
14,9
14,9
14,9
19,0
19,0
F.L.A.
Transmission code (fan)
PF 2A 280
PF 2A 250
Transmission code (motor)
Air flow
PF 2A 224
PF 2A 200
PV 2A 156
452
l/s
5333
5333
5333
5333
5333
5333
5333
5333
5333
5333
5333
5333
5333
5333
Fan RPM
rpm
727
752
777
801
825
849
872
895
918
940
962
984
1026
1067
Motor shaft input power
kW
4,77
5,02
5,28
5,55
5,81
6,08
6,36
6,63
6,92
7,19
7,48
7,77
8,35
8,94
Sound pressure level
dB
86
86
86
87
87
87
88
88
88
88
89
89
90
90
F.L.I. - Single supply fan
kW
7,5
7,5
7,5
7,5
7,5
7,5
7,5
7,5
7,5
7,5
9
9
9
9
A
14,9
14,9
14,9
14,9
14,9
14,9
14,9
14,9
14,9
14,9
19,0
19,0
19,0
19,0
F.L.A.
Transmission code (fan)
PF 2A 250
Transmission code (motor)
Air flow
PF 2A 224
PF 2A 250
PV 2A 156
PF 2A 224
PV 2A 177
464
l/s
6389
6389
6389
6389
6389
6389
6389
6389
6389
6389
6389
6389
6389
6389
Fan RPM
rpm
598
630
662
693
724
755
785
815
845
873
902
930
984
-
Motor shaft input power
kW
4,1
4,5
4,9
5,3
5,7
6,1
6,5
7
7,5
8
8,5
9
10
-
Sound pressure level
dB
82
82
83
84
85
85
86
87
87
88
88
89
90
-
F.L.I. - Single supply fan
kW
5,5
5,5
5,5
5,5
7,5
7,5
7,5
7,5
9
9
9
11
11
-
A
11,2
11,2
11,2
11,2
14,9
14,9
14,9
14,9
19,0
19,0
19,0
21,0
21,0
-
F.L.A.
Transmission code (fan)
PF 2A 300
PF 2A 250
Transmission code (motor)
Air flow
PF 2A 236
PF 2A 250
PV 2A 156
PV 2A 177
524
l/s
7222
7222
7222
7222
7222
7222
7222
7222
7222
7222
7222
Fan RPM
rpm
639
667
695
723
751
779
806
833
860
887
914
Motor shaft input power
kW
5,4
5,8
6,2
6,6
7
7,4
7,9
8,4
8,9
9,4
9,9
Sound pressure level
dB
84
84
85
85
86
87
87
88
88
89
89
F.L.I. - Single supply fan
kW
7,5
7,5
7,5
7,5
7,5
9
9
9
11
11
A
14,9
14,9
14,9
14,9
14,9
19,0
19,0
19,0
21,0
21,0
F.L.A.
Transmission code (fan)
PF 2A 280
Transmission code (motor)
Air flow
7222
-
7222
7222
940
991
1041
10,4
11,5
12,2
90
91
92
11
11
15
15
21,0
21,0
28,5
28,5
PF 2A 250
PV 2A 156
-
PF 2A 315
PV 2A 177
PV 2A 250
604
l/s
8056
8056
8056
8056
8056
8056
8056
8056
8056
8056
8056
8056
8056
8056
Fan RPM
rpm
686
711
736
762
787
812
837
862
886
911
936
960
1008
1055
Motor shaft input power
kW
7
7,4
7,8
8,3
8,7
9,2
9,7
10,2
10,7
11,2
11,7
12,3
12,8
14
Sound pressure level
dB
86
86
87
87
87
88
88
89
90
90
91
91
92
93
F.L.I. - Single supply fan
kW
9
9
9
9
9
11
11
11
11
15
15
15
15
15
A
19,0
19,0
19,0
19,0
19,0
21,0
21,0
21,0
21,0
28,5
28,5
28,5
28,5
28,5
F.L.A.
Transmission code (fan)
PF 2A 315
PF 2A 280
Transmission code (motor)
Air flow
704
PF 3A 355
PV 2A 177
PF3A315 PF3A300 PF3A280
PF 3A 224
PF 3A 200
l/s
8888
8888
8888
8888
8888
8888
8888
8888
8888
8888
8888
8888
8888
8888
Fan RPM
rpm
730
753
776
799
822
845
868
890
913
936
958
981
1025
-
Motor shaft input power
kW
8,9
9,3
9,7
10,2
10,7
11,2
11,7
11,9
12,2
12,7
13,2
13,7
14,9
-
Sound pressure level
dB
88
88
88
89
89
89
90
90
91
91
92
92
93
-
F.L.I. - Single supply fan
kW
11
11
11
11
11
15
15
15
15
15
15
15
15
-
A
21,0
21,0
21,0
21,0
21,0
28,5
28,5
28,5
28,5
28,5
28,5
28,5
28,5
-
PF3A280
-
10000
10000
10000
F.L.A.
Transmission code (fan)
PF 2A 300
Transmission code (motor)
PV 2A 177
Air flow
804
BT08A006GB-03
PF 2A 224
PF3A315
PF 3A 180
l/s
10000
10000
10000
10000
Fan RPM
rpm
639
662
684
Motor shaft input power
kW
8,5
9
9,5
Sound pressure level
dB
86
86
F.L.I. - Single supply fan
kW
11
11
A
21,0
21,0
F.L.A.
Transmission code (fan)
10000
PF 3A 190
10000
10000
10000
PF 3A 200
10000
707
729
752
774
796
817
838
859
880
921
961
10
10,5
11
11,6
11,9
12,2
12,7
13,3
13,9
15
16,3
86
87
87
87
88
88
89
89
89
90
91
91
11
11
11
15
15
15
15
15
15
15
18,5
18,5
21,0
21,0
21,0
28,5
28,5
28,5
28,5
28,5
28,5
28,5
35,0
35,0
PF 3A 355
PV 2A 187
PF 3A 190
10000
-
10000
PF 2A 355
Transmission code (motor)
Air flow
PF 3A 300
PF 3A 315
PF 3A 200
PF 3A 300
PF 3A 190
PF3A200
904
l/s
11111
11111
11111
11111
11111
11111
11111
11111
11111
11111
11111
11111
11111
11111
Fan RPM
rpm
683
704
724
745
766
786
806
826
846
866
885
905
943
-
Motor shaft input power
kW
11
11,5
11,8
12
12,5
13,1
13,6
14,2
14,7
15,3
15,9
16,5
17,8
-
Sound pressure level
dB
88
88
88
89
89
89
89
90
90
90
91
91
92
-
F.L.I. - Single supply fan
kW
15
15
15
15
15
15
15
15
15
18,5
18,5
18,5
18,5
-
A
28,5
28,5
28,5
28,5
28,5
28,5
28,5
28,5
28,5
35,0
35,0
35,0
35,0
-
F.L.A.
Transmission code (fan)
Transmission code (motor)
PF 3A 355
PF 3A 170
PF 3A 180
PF 3A 315
PF 3A 190
PF 3A 180
PF 3A 300
PF 3A 190
-
The performance takes into account the pressure drops in the unit (pressure drops in treatment coil, standard filters, etc.).
To determine the performance required by the fans, it is necessary to add the desired usable static pressure to the pressure drops of any accessories (e.g. hot water coils, gas module,
additional filter section, etc.).
The value of absorbed electrical power has already been corrected by a factor that takes into account the losses in transmission and a minimum tolerance on the number of revs of the fan.
28
PACKAGED
362 - 904
INTAKE AIR FLOW: REDUCED AIR FLOW
PERFORMANCES OF RETURN AIR FANS
60
90
120
150
180
210
240
270
300
330
360
390
420
450
l/s
-
3555
3555
3555
3555
3555
3555
3555
3555
3555
3555
3555
3555
3555
Fan RPM
rpm
-
451
489
526
562
597
630
663
694
725
755
783
811
839
Motor shaft input power
kW
-
1,27
1,44
1,61
1,79
1,97
2,16
2,35
2,55
2,75
2,95
3,16
3,36
3,58
Sound pressure level
dB
-
76
77
78
78
79
79
80
81
81
82
83
83
84
F.L.I. - Single supply fan
kW
-
2,2
2,2
2,2
2,2
2,2
3
3
3
4
4
4
4
4
A
-
4,8
4,8
4,8
4,8
4,8
6,5
6,5
6,5
8,3
8,3
8,3
8,3
8,3
Air flow
362
F.L.A.
Transmission code (fan)
-
Transmission code (motor)
-
Air flow
PF 1A 355
PF 1A 315
PF 1A 300
PF 1A 250
PV 1A 139
PV 1A 156
402
l/s
3911
3911
3911
3911
3911
3911
3911
3911
3911
3911
3911
3911
3911
-
Fan RPM
rpm
441
512
512
547
580
613
645
676
706
735
764
792
819
-
Motor shaft input power
kW
1,42
1,77
1,77
1,96
2,15
2,35
2,55
2,75
2,96
3,17
3,39
3,6
3,83
-
Sound pressure level
dB
78
79
79
79
80
80
81
81
82
82
83
83
84
-
F.L.I. - Single supply fan
kW
2,2
2,2
2,2
3
3
3
3
3
4
4
4
4
4
-
A
4,8
4,8
4,8
6,5
6,5
6,5
6,5
6,5
8,3
8,3
8,3
8,3
8,3
-
F.L.A.
Transmission code (fan)
PF 1A 355
Transmission code (motor)
Air flow
PF 1A 315
PV 1A 139
l/s
4267
4267
PF 1A 280
PF 1A 250
PV 1A 156
4267
4267
4267
4267
4267
4267
4267
-
4267
4267
4267
4267
4267
452
Fan RPM
rpm
471
504
537
569
600
631
661
691
719
747
775
802
828
853
Motor shaft input power
kW
1,78
1,97
2,16
2,36
2,56
2,77
2,99
3,2
3,42
3,65
3,88
4,11
4,34
4,58
Sound pressure level
dB
80
80
81
81
81
82
82
82
83
83
84
84
85
85
F.L.I. - Single supply fan
kW
3
3
3
3
3
3
4
4
4
4
5,5
5,5
5,5
5,5
A
6,5
6,5
6,5
6,5
6,5
6,5
8,3
8,3
8,3
8,3
11,2
11,2
11,2
11,2
F.L.A.
Transmission code (fan)
PF 1A 400
PF 1A 315
Transmission code (motor)
Air flow
PF 1A 280
PF 1A 400
PV 1A 156
PV 1A 250
464
l/s
-
-
5111
5111
5111
5111
5111
5111
5111
5111
5111
5111
5111
5111
Fan RPM
rpm
-
-
492
532
571
609
647
683
719
754
788
821
853
884
Motor shaft input power
kW
-
-
2,1
2,4
2,8
3,1
3,5
3,8
4,2
4,6
5,1
5,5
6
6,4
Sound pressure level
dB
-
-
76
78
79
80
81
82
83
84
85
85
86
87
F.L.I. - Single supply fan
kW
-
-
3
3
3
4
4
4
5,5
5,5
5,5
7,5
7,5
7,5
A
-
-
6,5
6,5
6,5
8,3
8,3
8,3
11,2
11,2
11,2
14,9
14,9
14,9
-
-
F.L.A.
Transmission code (fan)
Transmission code (motor)
PF 1A 355
PF 1A 315
PF 2A 300
-
-
l/s
5778
5778
5778
5778
5778
5778
5778
5778
5778
5778
5778
5778
5778
5778
Fan RPM
rpm
446
481
517
552
587
622
656
690
723
756
788
819
850
880
Motor shaft input power
kW
2,2
2,5
2,7
3,1
3,4
3,7
4,1
4,5
4,9
5,3
5,8
6,2
6,7
7,1
Sound pressure level
dB
77
78
79
79
80
81
82
83
84
85
85
86
87
87
F.L.I. - Single supply fan
kW
4
4
4
4
4
4
5,5
5,5
5,5
5,5
7,5
7,5
7,5
7,5
A
8,3
8,3
8,3
8,3
8,3
8,3
11,2
11,2
11,2
11,2
14,9
14,9
14,9
14,9
Air flow
524
F.L.A.
Transmission code (fan)
PF 1A 355
Transmission code (motor)
Air flow
PV 1A 156
PF 2A 280
PV 2A 177
PF 1A 300
PF 2A 280
PV 1A 139
PV 2A 156
PV 2A 177
604
l/s
6444
6444
6444
6444
6444
6444
6444
6444
6444
6444
6444
6444
6444
6444
Fan RPM
rpm
481
513
544
576
607
639
670
701
732
762
792
822
851
880
Motor shaft input power
kW
2,9
3,2
3,5
3,8
4,1
4,5
4,9
5,3
5,7
6,1
6,6
7
7,5
8
Sound pressure level
dB
80
80
81
81
82
83
83
84
85
85
86
87
87
88
F.L.I. - Single supply fan
kW
4
4
4
4
5,5
5,5
5,5
5,5
7,5
7,5
7,5
7,5
9
9
A
8,3
8,3
8,3
8,3
11,2
11,2
11,2
11,2
14,9
14,9
14,9
14,9
19,0
19,0
F.L.A.
Transmission code (fan)
PF 1A 315
Transmission code (motor)
PV 1A 139
Air flow
PF 2A 300
PF 2A 280
PV 2A 156
PV 2A 177
704
l/s
7111
7111
7111
7111
7111
7111
7111
7111
7111
7111
7111
7111
7111
-
Fan RPM
rpm
517
545
574
603
631
660
689
717
745
773
801
829
856
-
Motor shaft input power
kW
3,7
4
4,4
4,7
5,1
5,4
5,8
6,2
6,6
7,1
7,5
8
8,5
-
Sound pressure level
dB
82
82
83
83
84
84
84
85
86
86
87
88
88
-
F.L.I. - Single supply fan
kW
5,5
5,5
5,5
5,5
5,5
7,5
7,5
7,5
7,5
7,5
9
9
9
-
A
11,2
11,2
11,2
11,2
11,2
14,9
14,9
14,9
14,9
14,9
19,0
19,0
19,0
-
F.L.A.
Transmission code (fan)
PF 2A 355
PF 2A 300
Transmission code (motor)
Air flow
PF 2A 280
PV 2A 164
-
PV 2A 177
-
804
l/s
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
Fan RPM
rpm
458
488
516
545
573
601
629
656
682
708
734
759
784
808
Motor shaft input power
kW
3,6
4
4,4
4,7
5,1
5,6
6
6,4
6,9
7,4
7,9
8,4
8,9
9,4
Sound pressure level
dB
80
80
81
81
81
82
83
83
84
84
85
86
86
87
F.L.I. - Single supply fan
kW
5,5
5,5
5,5
5,5
5,5
7,5
7,5
7,5
7,5
9
9
9
11
11
A
11,2
11,2
11,2
11,2
11,2
14,9
14,9
14,9
14,9
19,0
19,0
19,0
21,0
21,0
8889
F.L.A.
Transmission code (fan)
PF 2A 400
Transmission code (motor)
PV 2A 164
Air flow
PF 2A 355
PF 2A 315
PV 2A 177
904
l/s
8889
8889
8889
8889
8889
8889
8889
8889
8889
8889
8889
8889
8889
Fan RPM
rpm
493
519
546
572
597
623
648
673
698
722
746
770
793
816
Motor shaft input power
kW
4,8
5,1
5,5
5,9
6,4
6,8
7,2
7,7
8,2
8,7
9,2
9,7
10,2
10,8
88
Sound pressure level
dB
82
82
83
83
83
84
84
85
85
86
86
87
87
F.L.I. - Single supply fan
kW
5,5
5,5
7,5
7,5
7,5
7,5
7,5
9
9
9
11
11
11
11
A
11,2
11,2
14,9
14,9
14,9
14,9
14,9
19,0
19,0
19,0
21,0
21,0
21,0
21,0
F.L.A.
Transmission code (fan)
Transmission code (motor)
PF 2A 400
BT08A006GB-03
EXTERNAL STATIC PRESSURE (Pa)
PF 2A 355
PV 2A 164
PF 2A 315
PF 2A 300
PV 2A 177
The value of absorbed electrical power has already been corrected by a factor that takes into account the losses in transmission and a minimum tolerance on the number of revs of the fan.
29
PACKAGED
362 - 904
AIR FLOW: HIGH
PERFORMANCES OF SUPPLY AIR FANS
EXTERNAL STATIC PRESSURE (Pa)
Air flow
l/s
120
150
180
210
240
270
300
330
360
390
420
450
510
570
6666
6666
6666
6666
6666
6666
6666
6666
6666
6666
6666
6666
6666
6666
362
Fan RPM
rpm
824
844
865
885
906
926
946
965
985
1004
1024
1043
1080
1117
Motor shaft input power
kW
8,01
8,31
8,62
8,93
9,24
9,56
9,88
10,21
10,53
10,86
11,2
11,53
11,7
12,36
Sound pressure level
dB
90
90
90
91
91
91
91
91
92
92
92
92
93
93
F.L.I. - Single supply fan
kW
9
9
9
9
11
11
11
11
11
11
15
15
15
15
A
19,0
19,0
19,0
19,0
21,0
21,0
21,0
21,0
21,0
21,0
28,5
28,5
28,5
28,5
F.L.A.
Transmission code (fan)
PF 2A 280
PF 2A 250
Transmission code (motor)
Air flow
PF 2A 236
402
7222
7222
7222
7222
7222
7222
7222
7222
7222
7222
7222
7222
7222
Fan RPM
rpm
869
889
908
927
946
965
983
1002
1020
1039
1057
1075
1110
1145
Motor shaft input power
kW
9,79
10,11
10,44
10,77
11,11
11,45
11,79
11,87
11,96
12,3
12,63
12,97
13,66
14,36
Sound pressure level
dB
92
92
92
92
92
92
93
93
93
93
93
93
94
94
F.L.I. - Single supply fan
kW
11
11
11
11
15
15
15
15
15
15
15
15
15
15
A
21,0
21,0
21,0
21,0
28,5
28,5
28,5
28,5
28,5
28,5
28,5
28,5
28,5
28,5
Transmission code (fan)
PF 2A 250
Transmission code (motor)
PV 2A 177
Air flow
PF 2A 355
PF 2A 236
7222
PF 2A 300
PF 2A 250
PF 2A 224
PF 2A 236
452
l/s
7500
7500
7500
7500
7500
7500
7500
7500
7500
7500
7500
7500
-
-
Fan RPM
rpm
905
923
942
960
979
997
1015
1033
1050
1068
1086
1103
-
-
Motor shaft input power
kW
11
11,33
11,68
11,76
11,85
12,19
12,53
12,87
13,21
13,56
13,91
14,26
-
-
Sound pressure level
dB
93
93
93
93
93
93
93
94
94
94
94
94
-
-
F.L.I. - Single supply fan
kW
15
15
15
15
15
15
15
15
15
15
15
15
-
-
A
28,5
28,5
28,5
28,5
28,5
28,5
28,5
28,5
28,5
28,5
28,5
28,5
-
-
-
-
F.L.A.
Transmission code (fan)
PF 2A 355
Transmission code (motor)
Air flow
PF 2A 224
PF 2A 236
464
rpm
770
791
812
833
854
875
896
917
938
Motor shaft input power
kW
11
11,4
11,9
12,1
12,3
12,8
13,3
13,8
14,3
Sound pressure level
dB
90
90
90
90
91
91
91
91
92
F.L.I. - Single supply fan
kW
15
15
15
15
15
15
15
15
A
28,5
28,5
28,5
28,5
28,5
28,5
28,5
28,5
PF 3A 355
Transmission code (motor)
9722
9722
PF 3A 315
9722
9722
PF 3A 300
PF 3A 190
9722
PF 2A 236
Fan RPM
Air flow
9722
PF 2A 224
9722
Transmission code (fan)
9722
PF 2A 315
l/s
F.L.A.
9722
9722
-
-
9722
9722
9722
9722
959
979
1000
1041
1082
14,8
15,4
15,9
17
18,2
92
92
93
93
94
15
18,5
18,5
18,5
18,5
18,5
28,5
35,0
35,0
35,0
35,0
35,0
PF 3A 280
PF 3A 300
PF 3A 180
PF 3A 280
PF 3A 200
524
l/s
10833
10833
10833
10833
10833
10833
10833
10833
10833
10833
10833
10833
10833
10833
Fan RPM
rpm
832
851
870
889
907
926
945
964
983
1001
1020
1039
1076
-
Motor shaft input power
kW
13,8
14,3
14,8
15,3
15,8
16,3
16,8
17,3
17,8
18,4
19
19,5
20,7
-
Sound pressure level
dB
92
92
92
92
93
93
93
93
94
94
94
94
95
-
F.L.I. - Single supply fan
kW
15
15
15
18,5
18,5
18,5
18,5
18,5
18,5
22
22
22
22
-
A
28,5
28,5
28,5
35,0
35,0
35,0
35,0
35,0
35,0
41,0
41,0
41,0
41,0
-
F.L.A.
Transmission code (fan)
PF 3A 315
Transmission code (motor)
Air flow
PF 3A 180
604
l/s
11667
Fan RPM
rpm
Motor shaft input power
kW
Sound pressure level
F.L.I. - Single supply fan
F.L.A.
PF 3A 190
11667
888
906
923
941
958
17
17,5
18
18,5
19,1
dB
94
94
94
94
94
kW
18,5
18,5
18,5
22
A
35,0
35,0
35,0
41,0
PF3A315
PF 3A 280
PF 3A 200
11667
Transmission code (motor)
Air flow
PF 3A 300
11667
Transmission code (fan)
704
11667
11667
PF 3A 190
-
PF 3A 200
-
11667
11667
11667
11667
11667
11667
11667
11667
976
993
1010
1028
1045
1063
1080
1115
1150
19,6
20,1
20,7
21,3
21,8
22,4
23
24,2
25,5
94
95
95
95
95
95
95
96
96
22
22
22
22
22
22
30
30
30
30
41,0
41,0
41,0
41,0
41,0
41,0
57,0
57,0
57,0
57,0
PF 3A 300
PF 3A 280
PF 3A 190
PF 3A 315
PF 3A 200
PF3A300
PF 3A 236
l/s
12222
12222
12222
12222
12222
12222
12222
12222
12222
12222
12222
12222
12222
12222
Fan RPM
rpm
922
939
955
972
988
1005
1022
1038
1055
1072
1088
1105
1138
1172
Motor shaft input power
kW
19,3
19,8
20,3
20,9
21,4
21,9
22,5
23,1
23,6
24,2
24,8
25,4
26,7
27,9
Sound pressure level
dB
95
95
95
95
95
95
95
96
96
96
96
96
97
97
F.L.I. - Single supply fan
kW
22
22
22
22
22
30
30
30
30
30
30
30
30
30
A
41,0
41,0
41,0
41,0
41,0
57,0
57,0
57,0
57,0
57,0
57,0
57,0
57,0
57,0
F.L.A.
Transmission code (fan)
PF 3A 300
Transmission code (motor)
Air flow
804
BT08A006GB-03
PF 2A 224
l/s
F.L.A.
PF 3A 190
PF 3A 280
PF 3A 200
PF 3A 190
PF 3A 315
PF 3A 200
PF 3A 300
PF 3A 236
l/s
14722
14722
14722
14722
14722
14722
14722
14722
14722
14722
14722
14722
14722
14722
Fan RPM
rpm
839
855
871
887
902
918
934
950
965
981
996
1012
1042
1073
Motor shaft input power
kW
21,7
22,3
22,9
23,5
24,2
24,8
25,5
26,1
26,8
27,4
28,1
28,8
30,2
31,7
Sound pressure level
dB
94
94
94
94
94
94
95
95
95
95
95
95
96
96
F.L.I. - Single supply fan
kW
30
30
30
30
30
30
30
30
30
30
30
30
37
37
A
57,0
57,0
57,0
57,0
57,0
57,0
57,0
57,0
57,0
57,0
57,0
57,0
66,0
66,0
F.L.A.
Transmission code (fan)
PF 5A 355
PF 5A 315
Transmission code (motor)
Air flow
PF 5A 200
PF 5A 224
904
l/s
15556
15556
15556
15556
15556
15556
15556
15556
15556
15556
15556
15556
15556
15556
Fan RPM
rpm
865
881
896
911
926
941
956
971
986
1000
1015
1030
1059
1088
Motor shaft input power
kW
24,7
25,3
26
26,6
27,3
27,9
28,6
29,3
29,9
30,6
31,3
32
33,5
35
Sound pressure level
dB
95
95
95
95
95
95
96
96
96
96
96
96
97
97
F.L.I. - Single supply fan
kW
30
30
30
30
30
30
30
30
37
37
37
37
37
37
A
57,0
57,0
57,0
57,0
57,0
57,0
57,0
57,0
66,0
66,0
66,0
66,0
66,0
66,0
F.L.A.
Transmission code (fan)
Transmission code (motor)
30
PF 2A 315
PV 2A 177
PF 5A 355
PF 5A 200
PF 5A 224
PF 5A 315
PF 5A 200
PF 5A 224
The performance takes into account the pressure drops in the unit (pressure drops in treatment coil, standard filters, etc.).
To determine the performance required by the fans, it is necessary to add the desired usable static pressure to the pressure drops of any accessories (e.g. hot water coils, gas module,
additional filter section, etc.).
The value of absorbed electrical power has already been corrected by a factor that takes into account the losses in transmission and a minimum tolerance on the number of revs of the fan.
PACKAGED
362 - 904
INTAKE AIR FLOW: HIGH AIR FLOW
PERFORMANCES OF RETURN AIR FANS
Air flow
l/s
60
90
120
150
180
210
240
270
300
330
360
390
420
450
5333
5333
5333
5333
5333
5333
5333
5333
5333
5333
5333
5333
5333
5333
362
Fan RPM
rpm
539
566
593
620
646
672
698
723
748
773
797
821
845
868
Motor shaft input power
kW
3,07
3,29
3,51
3,75
3,98
4,22
4,47
4,72
4,98
5,24
5,5
5,77
6,04
6,31
Sound pressure level
dB
85
85
85
85
85
85
86
86
86
86
87
87
87
88
F.L.I. - Single supply fan
kW
4
4
4
5,5
5,5
5,5
5,5
5,5
5,5
5,5
7,5
7,5
7,5
7,5
A
8,3
8,3
8,3
11,2
11,2
11,2
11,2
11,2
11,2
11,2
14,9
14,9
14,9
14,9
F.L.A.
Transmission code (fan)
PF 1A 355
Transmission code (motor)
Air flow
PF 1A 315
PF 1A 450
PF 1A 400
PV 1A 156
PV 1A 250
l/s
5778
5778
5778
5778
5778
5778
5778
5778
5778
5778
5778
5778
5778
Fan RPM
rpm
578
603
628
652
677
701
725
749
773
796
819
842
864
5778
887
Motor shaft input power
kW
3,84
4,08
4,32
4,57
4,82
5,08
5,34
5,61
5,88
6,15
6,43
6,71
7
7,28
402
Sound pressure level
dB
87
87
87
87
87
87
87
87
87
88
88
88
88
89
F.L.I. - Single supply fan
kW
5,5
5,5
5,5
5,5
5,5
7,5
7,5
7,5
7,5
7,5
7,5
7,5
7,5
7,5
A
11,2
11,2
11,2
11,2
11,2
14,9
14,9
14,9
14,9
14,9
14,9
14,9
14,9
14,9
F.L.A.
Transmission code (fan)
PF 1A 315
Transmission code (motor)
Air flow
PF 1A 450
PF 1A 400
PV 1A 156
PV 1A 250
452
l/s
6000
6000
6000
6000
6000
6000
6000
6000
6000
6000
6000
6000
-
-
Fan RPM
rpm
599
623
647
671
695
718
742
765
788
810
833
855
-
-
Motor shaft input power
kW
4,29
4,54
4,79
5,05
5,31
5,57
5,84
6,12
6,4
6,68
6,96
7,25
-
-
Sound pressure level
dB
88
88
88
88
88
88
88
88
88
88
89
89
-
-
F.L.I. - Single supply fan
kW
5,5
5,5
5,5
5,5
5,5
7,5
7,5
7,5
7,5
7,5
7,5
7,5
-
-
A
11,2
11,2
11,2
11,2
11,2
14,9
14,9
14,9
14,9
14,9
14,9
14,9
-
-
-
-
F.L.A.
Transmission code (fan)
PF 1A 315
Transmission code (motor)
PV 1A 156
Air flow
PF 1A 450
PF 1A 400
PV 1A 250
-
-
464
l/s
7778
7778
7778
7778
7778
7778
7778
7778
7778
7778
7778
7778
7778
7778
Fan RPM
rpm
545
571
597
623
649
676
702
728
754
780
806
832
857
883
Motor shaft input power
kW
4,6
5
5,3
5,6
6
6,4
6,8
7,2
7,6
8,1
8,5
9
9,5
10
Sound pressure level
dB
84
84
85
85
85
85
86
86
86
87
88
88
89
89
F.L.I. - Single supply fan
kW
5,5
5,5
5,5
7,5
7,5
7,5
7,5
7,5
9
9
9
11
11
11
A
11,2
11,2
11,2
14,9
14,9
14,9
14,9
14,9
19,0
19,0
19,0
21,0
21,0
21,0
F.L.A.
Transmission code (fan)
PF 2A 355
Transmission code (motor)
PV 2A 156
Air flow
PF 2A 315
PF 2A 280
PF 2A 250
PV 2A 164
524
l/s
8667
8667
8667
8667
8667
8667
8667
8667
8667
8667
8667
8667
8667
Fan RPM
rpm
594
617
641
664
688
711
735
758
782
805
829
852
875
8667
899
Motor shaft input power
kW
6,2
6,6
6,9
7,3
7,5
8,1
8,5
8,9
9,4
9,8
10,3
10,8
11,3
11,8
90
Sound pressure level
dB
86
87
87
87
87
87
87
88
88
88
89
89
90
F.L.I. - Single supply fan
kW
7,5
7,5
7,5
7,5
9
9
9
11
11
11
11
11
15
15
A
14,9
14,9
14,9
14,9
19,0
19,0
19,0
21,0
21,0
21,0
21,0
21,0
28,5
28,5
F.L.A.
Transmission code (fan)
PF 2A 315
Transmission code (motor)
Air flow
PF 2A 300
PV 2A 156
PF 3A 315
PV 2A 177
PF 3A 190
604
l/s
9333
9333
9333
9333
9333
9333
9333
9333
9333
9333
9333
9333
9333
Fan RPM
rpm
632
654
676
698
719
741
763
785
807
828
850
872
894
915
Motor shaft input power
kW
7,6
8
8,4
8,8
9,2
9,6
10
10,5
10,9
11,4
11,9
12,1
12,3
12,8
Sound pressure level
dB
88
88
88
89
89
89
89
89
89
90
90
90
91
91
F.L.I. - Single supply fan
kW
9
9
9
9
11
11
11
11
15
15
15
15
15
15
A
19,0
19,0
19,0
19,0
21,0
21,0
21,0
21,0
28,5
28,5
28,5
28,5
28,5
28,5
F.L.A.
Transmission code (fan)
PF 2A 315
PF 2A 280
Transmission code (motor)
Air flow
9333
PF 3A 315
PV 2A 164
PF 3A 180
PF 3A 190
704
l/s
9778
9778
9778
9778
9778
9778
9778
9778
9778
9778
9778
9778
9778
9778
Fan RPM
rpm
659
680
700
721
742
763
784
805
825
846
867
888
909
929
Motor shaft input power
kW
8,7
9,1
9,5
9,9
10,3
10,8
11,2
11,6
11,9
12,1
12,5
13
13,5
14
Sound pressure level
dB
89
89
89
89
90
90
90
90
90
91
91
91
91
92
F.L.I. - Single supply fan
kW
11
11
11
11
11
11
15
15
15
15
15
15
15
15
A
21,0
21,0
21,0
21,0
21,0
21,0
28,5
28,5
28,5
28,5
28,5
28,5
28,5
28,5
F.L.A.
Transmission code (fan)
PF 2A 300
Transmission code (motor)
PV 2A 164
Air flow
PF 3A 315
PF 3A 170
PF 3A 300
PF 3A 180
PF 3A 190
804
l/s
11778
11778
11778
11778
11778
11778
11778
11778
11778
11778
11778
-
-
-
Fan RPM
rpm
603
623
644
664
684
703
723
743
762
782
801
-
-
-
Motor shaft input power
kW
9,9
10,3
10,8
11,3
11,8
12
12,3
12,8
13,3
13,9
14,4
-
-
-
Sound pressure level
dB
89
89
89
89
89
89
89
89
90
90
90
-
-
-
F.L.I. - Single supply fan
kW
11
11
11
15
15
15
15
15
15
15
15
-
-
-
A
21.0
21.0
21.0
28,5
28,5
28,5
28,5
28,5
28,5
28,5
28,5
-
-
-
PF 3A 315
-
-
-
PF 3A 170
-
-
-
F.L.A.
Transmission code (fan)
PF 2A 355
Transmission code (motor)
PV 2A 164
Air flow
PF 3A 355
PF 3A 170
PF 3A 180
904
l/s
12444
12444
12444
12444
12444
12444
12444
12444
-
-
-
-
-
-
Fan RPM
rpm
632
651
671
690
709
728
746
765
-
-
-
-
-
-
Motor shaft input power
kW
11,5
11,8
12
12,5
13
13,5
14
14,5
-
-
-
-
-
-
Sound pressure level
dB
90
90
90
90
90
90
90
90
-
-
-
-
-
-
F.L.I. - Single supply fan
kW
15
15
15
15
15
15
15
15
-
-
-
-
-
-
A
28,5
28,5
28,5
28,5
28,5
28,5
28,5
28,5
-
-
-
-
-
-
PF 3A 355
-
-
-
-
-
-
PF 3A 180
-
-
-
-
-
-
F.L.A.
Transmission code (fan)
Transmission code (motor)
PF 3A 400
PF 3A 180
PF 3A 190
BT08A006GB-03
EXTERNAL STATIC PRESSURE (Pa)
The value of absorbed electrical power has already been corrected by a factor that takes into account the losses in transmission and a minimum tolerance on the number of revs of the fan.
31
PACKAGED
362 - 904
HIGH CUSTOMIZATION OF UNIT
Constructive configuration B is equipped with a recirculation air and fresh air mixture chamber, and a single
ventilation section for both supply and return.
Constructive configuration C is equipped with a recirculation air and fresh air mixture chamber, a ventilation
section dedicated to supply and a ventilation section dedicated to return/expulsion. Both constructive
configurations B and C can be customized with the selection of a flow rate with three possible values: standard,
high, or reduced, based on design needs.
EXCLUSIVE OPTIONAL ACCESSORIES OF THE CONFIGURATION B
FCB - FREE-COOLING THERMAL VERSION B
The configuration with thermal free-cooling for version B allows operation with a variable percentage of refresh
air, with opening or closing of the shutters on fresh air and on recirculation air by means of modulating actuators,
which intervene when the conditions of fresh air are such that it allows lowering of the internal thermal loads
simply by placing primary air in the room. Conditions of adjustment are identified by comparing the outside
temperature with that of the served room. In spring or autumn, or in applications where there are high room loads,
the configuration with free-cooling makes it possible to substantially reduce the energy consumption of the units
and the wear of the compressors.
In heat-pump operating mode, the free-heating logic is used. With the same principle as free-cooling, it makes use
of the energy contained in the fresh air to increase the thermal load of the served room without the aid of the
compressors.
The component requires a system for extraction and expulsion of air from the served room, outside the unit (to be provided by the client).
FCEB - FREE-COOLING ENTHALPIC VERSION B
The configuration with enthalpic free-cooling for version B allows operation with a variable percentage of refresh
air, with opening or closing of the shutters on fresh air and on recirculation air by means of modulating actuators,
which intervene when the conditions of fresh air are such that it allows lowering of the internal thermal loads
simply by placing primary air in the room. Conditions of adjustments are determined by the comparison not only of
the temperature but also of the humidity between the exterior and the served room.
SERM - MOTORIZED FRESH AIR SHUTTER ON/OFF
Opening or closing of the fresh air shutter is controlled by an ON-OFF actuator which, with the machine running,
opens the shutter to a preset value while, with the machine shut down, closes the shutter, thus avoiding the
"chimney effect" of the ducts with heat loss to the exterior.
SERMD - MODULATING MOTORIZED FRESH AIR SHUTTER
The configuration with motorized shutter with modulating adjustment for configuration B allows operation with a
variable percentage of refresh air with opening or closing of the shutter by means of an actuator driven by a 0-10V
signal based on concentrations of CO2 or CO2+VOC detected by the air quality probe.
This configuration can be selected only in combination with the air quality probe.
BT08A006GB-03
EXCLUSIVE OPTIONAL ACCESSORIES OF THE CONFIGURATION C
FCE - ENTHALPIC FREE COOLING
The configuration with enthalpic free-cooling is the optional version of version C. This device allows operation with
a variable percentage of refresh air, with opening or closing of the shutters on fresh air and on recirculation air by
means of modulating actuators, which intervene when the conditions of fresh air are such that it allows lowering of
the internal thermal loads simply by placing primary air in the room.
Conditions of adjustments are determined by the comparison not only of the temperature but also of the humidity
between the exterior and the served room.
CANT- APPLICATION WITH FABRIC DUCTS
This option allows the fans to start up gradually and means the unit can be
adapted to most of the appliances which use fabric ducts to convey the air.
Using the soft starter and special technical design features allows the
stress on the fabric ducts when the machine starts up to be reduced to a
minimum.
This option is supplied with the unit in constructive configuration C and a soft starter device.
32
PACKAGED
362 - 904
OPTIONAL ACCESSORIES COMMON TO CONFIGURATIONS B AND C
EH - ELECTRIC HEATERS.
This option is advisable for cold climates. Available in various powers, it
allows heating of the served room. The electrical heating elements are
managed by a thermal control device with two power settings.
The fins are made of aluminium, with a size suitable to ensure high
efficiency and maintain low power density on the surfaces to limit
overheating. The low temperature of the heating elements increases their
lifespan and limits the effect of air ionization.
In heat pump mode, the heating elements may be automatically activated
to preheat the inlet air to the main coil, for example during operation with
high percentages of fresh air.
This extends the operating limits of the machine. The electrical heating
elements can be used to boost the yield of the heat pump.
The thermal control device is capable of simultaneously activating the preheating and integration functions. Also, the electrical heating elements can
be used to reduce the time required for defrosting.
COMBINATIONS ELECTRIC HEATERS.
362
Size
402
452
464
524
604
704
804
904
24kW
36kW
48kW
72kW
96kW
This operation involves variation of the main electrical data of the machine.
hot water coil and electric heaters cannot be mounted at the same time
OPERATING LIMITS (Heating)
30
25
To (D.B.)
20
(1)
15
10
5
(2)
0
Delta T
-5
-15
-10
-5
0
5
10
15
THE LIMITS ARE INDICATIVE AND HAVE BEEN CALCULATED CONSIDERING:
- VALUES GENERAL AND NOT SPECIFICATIONS,
- STANDARD AIR FLOW-RATE,
- NON-CRITICAL POSITIONING AND CORRECT USE OF THE UNIT,
- OPERATION AT FULL LOAD
TO = D.B: TEMPERATURE OF INLET AIR MIXTURE (°C)
DB = DRY BULB
TA = EXTERNAL EXCHANGER INLET AIR TEMPERATURE W.B. (°C)
WB = WET BULB
(1) THE DASHED AREA REFERS TO THE FIELD OF UNITS OPERATION
STANDARD
(2) EXTENSION OF THE FIELD OF OPERATION WITH PREHEATING HEATING ELEMENTS. TO OBTAIN THE LOWER LIMIT CURVE, CONSIDER AS
THE TEMPERATURE DIFFERENCE (DELTA T) THE VALUE SHOWN IN THE
TABLE “EXTENSION OF OPERATING LIMITS WITH PRE-HEATING ELEMENTS”.
20
EXTENSION OF OPERATING LIMITS WITH PRE-HEATING ELEMENTS
The pre-heating elements make it possible to increase the temperature of the air mixture entering treatment (temperature To) and make it
possible to work with lower temperature limits of the mixture entering the internal heat exchanger, extending the operating range of the machine in winter operation.
The table of extension of limits of operation shows the temperature differences (Delta T) to be subtracted from the lower limits of the temperature of the air entering the internal heat exchanger (To) in order to obtain the new limit of operation.
24 kW
36 kW
48 kW
72 kW
96 kW
5555
6111
6666
8055
3.6
3.2
3.0
-
5.3
4.9
4.4
3.7
7.1
6.5
5.9
4.9
7.4
9.8
524
604
704
804
9028
10000
11111
12500
-
3.3
3.0
2.7
1.9
4.4
4.0
3.6
3.2
6.6
5.9
5.3
4.7
8.8
7.9
7.1
6.3
904
13889
-
1.7
2.8
4.3
5.7
Temperature differential (Delta T) of
the air that passes through the
electrical heating elements [°C]
Air flow rate [l/s]
362
402
452
464
Size
BT08A006GB-03
Ta (W.B.)
33
PACKAGED
362 - 904
CHW2 - TWO-ROW HOT WATER COIL
Option recommended for very cold climates since it allows heating of the served room. The battery is equipped
with a thermostat for the anti-freeze function. The anti-freeze function is always active, even when the unit is in
standby. If necessary, it forces opening of the valve to the maximum allowable value for allow passage of water in
the coil and to prevent the formation of ice.
In heat pump mode, the hot water coil may allow both pre-heating of the inlet air to the main coil, as well as
integration of the capacity provided by the heat pump. As an alternative, it may intervene in complete substitution
of the thermal capacity provided by the compressors.
This is possible by setting a turning point, i.e. a temperature limit of the fresh air below which use of the
compressors is blocked, and the water coil is used as the sole resource. If the water coil provides pre-heating of
the air, the control logic reduces its power to a preset value, which keeps the compressors from working with
condensation temperatures that are too high. If instead the water coil is used as the main resource (e.g. because
the compressors are not available), the maximum power will be provided.
HOT WATER COIL PRESSURE DROP: AIR SIDE
65
464-704
60
804-904
THE AIR SIDE PRESSURE DROPS ARE RELATIVE
TO THE MEDIUM AIR TEMPERATURE OF 20°C
AND ARE TO BE ADDED TO THE PRESSURE
DROPS DUE TO DUCTS, TERMINAL DEVICES AND
ANY OTHER COMPONENT THAT CAUSES A DROP
IN WORKING DISCHARGE HEAD.
Q [L/S] = AIR FLOW RATE
55
50
[Pa]
45
362-452
40
35
30
25
20
15
4000
5000
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
16000
Q [l/s]
HOT WATER COIL PRESSURE DROP: WATER SIDE
PRESSURE DROPS ON THE WATER SIDE
ARE CALCULATED CONSIDERING AN AVERAGE WATER TEMPERATURE OF 65°C
Q[L/S]= WATER-FLOW RATE
This option reduces the available static pressure (air side).
BT08A006GB-03
The component requires connection to the hot water plumbing system (to be provided for by the client).
3WVM - MODULATING 3-WAY VALVE
To be used in conjunction with the hot water coil (optional). It is controlled by the on-board microprocessor by
means of a 0-10V signal and allows fully automatic adjustment of the hot water coil. The valve with modulating
actuator is provided already installed and wired on the machine.
PRESSURE DROP MODULATING THREE-WAY VALVE
Q[l/s]= WATER-FLOW RATE
34
PACKAGED
362 - 904
PERFORMANCES OF HOT WATER COIL (2 ROWS)
Ti/To (°C)
Size
80,0 / 65,0 70,0 / 55,0 60,0 / 40,0 80,0 / 65,0 70,0 / 55,0 60,0 / 40,0 80,0 / 65,0 70,0 / 55,0 60,0 / 40,0
Ta (°C)
362
239,4
201,8
151,8
269,8
227,3
170,4
114,4
219,3
182,0
132,4
247,1
205,1
148,6
14
175,0
143,4
101,1
203,4
166,5
117,0
229,3
187,6
131,4
16
168,3
136,8
94,6
195,6
158,8
109,4
220,5
178,9
122,7
18
161,5
130,1
88,1
187,8
151,1
101,8
211,8
170,3
114,2
20
154,9
123,7
81,6
180,1
143,6
94,2
203,1
161,6
105,6
Ta (°C)
4889
Ta (°C)
Ta (°C)
Ta (°C)
Ta (°C)
Ta (°C)
Ta (°C)
Ta (°C)
6111
7222
5
219,8
185,3
139,6
254,9
214,8
161,3
284,1
239,3
179,1
10
201,3
167,2
121,8
233,5
193,8
140,6
260,3
215,9
156,2
14
186,7
152,9
107,7
216,7
177,3
124,3
241,5
197,5
138,1
16
179,6
145,8
100,7
208,3
169,1
116,2
232,2
188,3
129,1
18
172,4
138,8
93,7
200,1
160,9
108,1
223,0
179,3
120,0
20
165,3
131,9
86,8
191,8
152,8
100,1
213,9
170,1
111,0
5333
6667
7500
5
233,0
196,4
147,7
269,8
227,3
170,4
291,0
245,1
183,4
10
213,4
177,2
128,8
247,1
205,1
148,6
266,6
221,2
159,8
14
198,0
162,0
113,9
229,3
187,6
131,4
247,4
202,3
141,3
16
190,4
154,5
106,5
220,5
178,9
122,7
237,9
192,9
132,1
18
182,8
147,1
99,1
211,8
170,3
114,2
228,5
183,6
122,8
20
175,3
139,7
91,7
203,1
161,6
105,6
219,1
174,4
113,6
6389
8056
9722
5
308,1
260,7
198,6
360,2
304,5
230,9
407,5
344,2
260,4
10
283,1
236,2
174,1
331,0
276,0
202,5
374,8
311,9
228,1
14
263,6
216,8
154,7
308,2
253,3
179,9
348,7
286,3
202,5
16
253,9
207,1
145,0
296,9
242,0
168,5
335,8
273,6
189,8
18
244,2
197,5
135,3
285,5
230,8
157,2
323,1
260,9
177,1
20
234,5
188,0
125,6
274,3
219,6
145,9
310,3
248,2
164,2
7222
9028
10833
5
334,8
283,2
215,2
388,3
328,1
248,6
436,8
368,9
278,6
10
307,7
256,6
188,7
357,1
297,3
217,7
401,8
334,3
244,1
14
286,5
235,5
167,6
332,3
272,9
193,4
373,8
306,8
216,5
16
275,9
225,1
157,1
320,0
260,8
181,2
360,0
293,1
202,9
18
265,4
214,6
146,6
307,8
248,7
169,0
346,3
279,5
189,2
20
254,9
204,1
136,0
295,7
236,6
156,8
332,7
265,9
175,5
8056
10000
11667
5
360,2
304,5
230,9
414,9
350,5
265,1
457,8
386,5
291,6
10
331,0
276,0
202,5
381,7
317,6
232,2
420,8
350,2
255,5
14
308,2
253,3
179,9
355,1
291,5
206,1
391,8
321,5
226,6
16
296,9
242,0
168,5
342,0
278,6
193,1
377,4
307,1
212,2
18
285,5
230,8
157,2
329,0
265,6
180,2
363,0
292,9
198,0
20
274,3
219,6
145,9
316,0
252,7
167,0
348,7
278,6
183,5
8889
11111
12222
5
384,4
324,8
246,1
443,8
374,8
283,0
471,3
397,9
299,9
10
353,2
294,4
215,5
408,3
339,7
248,1
433,3
360,6
262,9
14
328,9
270,2
191,5
379,9
311,7
220,0
403,4
330,9
233,1
16
316,8
258,2
179,5
365,9
297,9
206,0
388,6
316,2
218,3
18
304,7
246,2
167,3
352,0
284,0
192,2
373,8
301,5
203,5
20
292,7
234,2
155,2
338,1
270,2
178,2
359,0
286,8
188,7
10000
12500
14722
5
459,3
387,3
290,5
532,4
448,7
335,0
591,7
498,3
371,1
10
421,7
350,4
253,7
489,3
405,8
292,7
543,8
450,8
324,0
14
392,4
321,2
224,7
455,1
372,2
258,8
505,8
413,1
286,5
16
377,8
306,5
210,0
438,1
355,2
242,0
486,9
394,4
267,8
18
363,0
292,3
195,5
420,9
338,3
225,1
468,1
376,1
249,0
20
348,6
277,9
181,0
404,2
321,7
208,4
449,3
357,0
230,2
Qo (l / s)
904
kWt
131,1
Qo (l / s)
804
kWt
6667
156,7
Qo (l / s)
704
kWt
173,8
Qo (l / s)
604
kWt
188,7
Qo (l / s)
524
kWt
5556
206,0
Qo (l / s)
464
kWt
5
Qo (l / s)
452
kWt
10
Qo (l / s)
402
kWt
4444
11111
13889
BT08A006GB-03
kWt
Qo (l / s)
15555
5
492,8
415,2
310,8
570,0
480,2
358,1
612,7
515,9
383,9
10
452,8
375,8
271,5
523,9
434,1
312,5
563,1
466,8
335,1
14
420,9
344,5
240,3
487,3
398,1
276,4
523,8
427,6
296,2
16
405,3
328,7
224,7
469,1
380,1
258,5
504,3
408,3
276,9
18
389,7
313,4
209,1
450,9
362,0
240,3
484,8
389,1
257,6
20
374,3
298,1
193,5
432,6
344,0
222,2
465,4
369,9
238,0
Ta = air temperature entering the air handling coil (°C)
Ti/To = water temperature inlet/outlet (°C)
Qo = air flow (l/s)
kWt = Heating capacity (kW)
35
PACKAGED
362 - 904
GH - GAS BURNER
This option is advisable for very cold climates. The gas module is
available in various powers and allows heating of the served room.
Perfect for situations in which climatic conditions make heat pump
operation inconvenient or even unsuitable.
The gas module must be capable of working as an alternative to the
heat pump. Therefore it must be sized with the same thermal power as
the design.
Thanks to the technology of condensation with premixing and very highefficiency modulation (up to 105% based on the net calorific value),
consumption is extremely limited and further reduced during operation
at partial loads. Emissions into the atmosphere are minimal, completely free of nitrogen monoxide and with a low
content of CO2 which remains constant in the entire working range, as opposed to atmospheric burners.
The heating module includes a condensation hot air generator with modulating adjustment, fuelled with methane
gas or LPG, and is complete with a steel flue pipe kit and all safety and adjustment devices. The flue pipe kit
requires assembly and is to be installed at the worksite. The module is provided standard set up for methane gas.
A kit is provided for changeover to LPG.
COMBINATIONS GAS MODULE
Size
362
402
452
464
524
604
704
804
904
96kW
150kW
200kW
300kW
This option reduces the available static pressure (air side).
The component requires a supply of gas (gas connection to be provided by the client). Note the presence of the flue pipe and the need to
comply with legal requirements in positioning the machine.
GAS CONNECTION DIAGRAM
(1) MAIN BURNER GAS SOLENOID VALVE
(2) PRESSURE STABILIZER
(3) GAS SAFETY SOLENOID VALVE
(4) GAS FILTER (SMALL SECTION)
(5) ANTI-VIBRATION JOINT
(6) GAS FILTER (LARGE SECTION)
(7) GAS BIBCOCK
(8) PILOT BURNER GAS SOLENOID VALVE
BT08A006GB-03
INCLUDED
GAS CONSUMPTION
96 kW
Size
description
Nominal power
efficiency
produced condensation
gas connection diameter
flue pipe diameter
supply pressure G20 methane
gas consumption
supply pressure G31
gas consumption
36
PROVIDED BY THE
kW
%
l/h
mm
mbar
3
m /h
mbar
3
m /h
min
31,5
105
150 kW
max
93,4
95,3
min
46,3
105,2
max
145
93,5
200 kW
min
55,7
105,1
max
197
91,6
300 kW
min
92,6
105,2
max
290
93,5
2,6
3,87
4,9
7,74
UNI ISO 7/1-1" M
UNI ISO 7/1-1" M
UNI ISO 7/1-1" M
UNI ISO 7/1-1" M
100
3,17
10,37
1,9
6,21
130
130
20 (Min.17 Max.25)
4,66
16,4
5,61
22,75
37 (Min.25 Max.45)
2,79
9,83
3,36
13,63
130
9,32
32,8
6,72
27,26
PACKAGED
362 - 904
HSE - STEAM HUMIDIFIER WITH IMMERGED ELECTRODES
This device is perfect for the winter period when it is necessary to add humidity
to the room without cooling the air flow. The modulating automatic adjustment
makes it possible to adapt the production of steam and the related operating
costs to meet actual needs.
Available in different powers, the device is suitable for use with unsoftened
water of medium conductivity. It is complete with water filling solenoid valve,
disposable cylinder, water drainage solenoid valve, distribution nozzle,
electronic control card with functions of verification of water level, verification
of conductivity, anti-foam, manual override of water drainage.
To ensure the utmost hygiene, the cylinder is automatically drained after a
certain period of inactivity. The device includes an automatically activated antifreeze device. A supply probe is used to monitor the humidity level. It is
installed and wired on-board the machine.
COMBINATIONS ELECTRODE BOILER STEAM HUMIDIFIER
Size
This operation involves variation of the main electrical data of the machine.
This accessory requires the presence of a water circuit and drain on board the machine. Provided by the customer
HWS - WATER TO WASTE EVAPORATING WET-DECK HUMIDIFIER
This option is recommended when quick, efficient humidification of the served
room is required. Humidification of the air mixture occurs by passing the air
flow through a honeycomb package that is kept humid at all times by a series
of nozzles that inject water in small drops. The reserve of water for treatment
is taken directly from the water mains.
During operation, the pure water vapour is mixed with the air currents. The
remaining part, enriched with mineral salts, is collected in the tub and
eliminated. The constant exchange of water ensures cleaning of the
evaporation septum and provides maximum limitation of the formation and
proliferation of Legionnaire's Disease. With this option, energy consumption
for water evaporation is limited.
Whenever the packaged humidifier is active, in addition to humidifying,
adiabatic cooling of the air takes place, which is constantly compensated for
by the thermal control device. Direct connection to the plumbing system
eliminates the need for special water treatment and easy control of the
humidification process by means of the measuring and adjusting device of the
water flow rate provided standard.
MEASURING
DEVICE ADJUSTER
MANUAL SHUT-OFF
VALVE
This accessory requires the presence of a water circuit and drain on board the machine. Provided by the customer
MAXIMUM RATE OF STEAM RELEASED BY THE WET DECK HUMIDIFIER
Size
362
402
452
464
524
604
704
804
904
Ta (°C) D.B.
Ta (°C) W.B.
Kg/h
Kg/h
Kg/h
Kg/h
Kg/h
Kg/h
Kg/h
Kg/h
Kg/h
30
35
40
15.1
17.6
19.8
115
144
175
127
158
193
138
173
210
167
209
254
187
234
285
207
259
315
230
288
350
259
324
394
288
360
438
BT08A006GB-03
SOLENOID VALVE
This option reduces the available static pressure (air side).
Ta D.B.= dry bulb temperature of inlet air to the wet deck.
Ta W.B.= wet bulb temperature of inlet air to the wet deck.
Approximate values of the maximum rate of steam released by the wet deck humidifier to the air to obtain controlled thermal and humidity conditions in supply.
The data refer to a unit with standard air flow rate in supply.
37
PACKAGED
362 - 904
AIR FILTERING
This is an essential function for proper maintenance of conditions of well-being and hygiene in the served rooms.
For this reason it is the subject of precise standards based on the specific applications. The units are standard
equipped with filters with an efficiency of G4 on the treatment section. They have an ample surface and low
pressure drops. The second filtering stage is available through innovative, high-efficiency filters, electro-static,
automatically controlled, class H10.
Thanks to the minimum pressure drops and the possibility to wash them, they substantially reduce consumption
and hence ventilation costs, while at the same time ensuring excellent performance. As an alternative the more
traditional high-efficiency F7 rigid pocket filters are available.
F7 - HIGH EFFICIENCY F7 AIR FILTER
The multi-dihedral filters with rigid pockets, class F7, are filtering components
that are in addition to the standard G4 filters, for more effective filtering. They
are widely used in civil air conditioning systems and in industrial applications
that require suitable performance concerning fine dusts and particles with
dimensions greater than µm.
Class F7 filters are made of fibreglass paper, pleated with constant calibrated
spacing, mounted on frames with a sturdy structure in extruded moulded
polyester; the ample filtering surface reduces air side pressure drops. Class F7
filters must be replaced after reaching their limits of dirtiness with scheduled
periodic maintenance. It is possible to provide as an accessory the dirty filters
differential switch, which informs the user that the admissible limit of dirtiness
has been reached so as not to excessively reduce the air flow rate with
respect to the nominal value.
This option reduces the available static pressure (air side).
FES - AIR FILTER, ELECTRO-STATIC, HIGH-EFFICIENCY, H10
BT08A006GB-03
Class H10 high-efficiency filters are additional filtering components with an
active electrostatic system. Solid or liquid particles contained in the air flow are
trapped by and electrical field.
The air flow through the filter is affected in two main phases: release of an
electrical charge to the particles (ionization), and capture of the particles by
electrostatic deposit (captivation).
On a periodic basis, the filters must be washed to remove the captured
particles.
The filters are capable of trapping fine dusts, some types of viruses and microorganisms (anti-bacterial action) with very modest pressure drops. The range
of use normally includes fine powders that measure less than 1 µm. Typical
pollutants are cigarette smoke (0.5÷0.3 µm), oily vapours (1÷0.2 µm), PM10
(particles < 10 µm), PM2.5 (particles < 2.5µm), PM1 (particles < 1µm), etc.
Dirtiness of the electric filter is signalled by a sensor that makes it possible to
schedule periodic maintenance, which can be easily performed by washing in
water with a special non-aggressive detergent for aluminium.
The greater initial cost, as compared to a traditional pocket filter, is recovered quickly since the electrostatic filters
last for the entire life of the machine, whereas pocket filters require periodic replacement.
FLOW OF CONTAMINATED AIR
IONIZATION
This option reduces the available static pressure (air side).
This operation involves variation of the main electrical data of the machine.
38
CAPTIVATION
PACKAGED
362 - 904
COMPARISON OF OPERATING COSTS: A CASE STUDY
The high-efficiency electrostatic filters allow very rapid return of the initial investment as compared with a
traditional filtering system, thanks to the reduction of electrical consumption of the ventilation sections and the
greatly reduced maintenance costs, since the filters do not require periodic replacement.
A typical case study shows how return on investment occurs in just a few months. In the heavy-duty use of a
shopping centre, this occurs by the second year with respect to a traditional system with pocket, F7, highefficiency second stage filtering.
This also greatly reduces environmental impact, both due to more rational use of energy, and because no special
waste is produced, such as the used traditional pocket filters.
150
(1) COST FOR PURCHASE AND OPERATION
OF THE SECOND FILTERING STAGE, TRADITIONAL TYPE, WITH POCKETS, EFFICIENCY F7
(1)
100
Earning as a
ofpartire
19th
Guadagno
month
dal 19° mese
(2) COST FOR PURCHASE AND OPERATION
OF THE SECOND FILTERING STAGE, ELECTROSTATIC TYPE, WITH POCKETS, EFFICIENCY H10
Risparmio
Saving
[%]
unitstandard
standard
cost for
Percentage
Costi
percentuali
riferiti
a unità
[%]
Analysis
of costs
(electrostatic
filters- -filtri
pocket
filters)
Analisi dei
costi (filtri
elettrostatici
a tasche)
IN ORDER, THE PERCENTAGE OF COST INCREASES ARE PRESENTED FOR A STANDARD
UNIT WITH SINGLE FILTERING STAGE OF G4
EFFICIENCY.OPERATION INCLUDES GREATER
COSTS FOR VENTILATION AND MAINTENANCE. PERFORMANCE OF ELECTROSTATIC
FILTER:
- -25% ON VENTILATION COSTS
- -90% ON COSTS OF MAINTENANCE
(2)
50
EXAMPLE BASED ON MEDIUM SIZED UNITS
USED ON A SHOPPING CENTRE THAT IS
OPEN 12 HOURS A DAY, 6 DAYS A WEEK, AND
SUBJECT TO ROUTINE MAINTENANCE 3
TIMES A YEAR
0
0
1
2
3
4
5
6
Time
[years]
Tempo
[anni]
The values are to be considered approximate.
The H10 class electrostatic filters and the F7 pocket filters cannot be included simultaneously on the machine.
PSAF - DIFFERENTIAL PRESSURE SWITCH FOR DIRTY AIR FILTERS
BT08A006GB-03
It makes it possible to detect and signal (with a suitable alarm) when the
dirtiness of the air filter reaches its maximum level.
This provides the machine operator with information on when filter
maintenance is required. The detection signal is installed in the unit. It is
already connected to the electrical panel and pre-calibrated in the factory.
Calibration can be modified by a specialized service centre during the
commissioning phase.
39
PACKAGED
362 - 904
CPHG - HOT GAS RE-HEATING COIL
This option is recommended during the summer when dehumidification of the room is required. The flow of air to
enter the room may contain a higher level of humidity than desired. The dehumidification process is used to
reduce it. The air flow is first cooled in the treatment coil with separation of condensation. It is then freely postheated to maintain the desired condition of comfort in the room served.
The post-heating coil is located behind the treatment coil and is activated by drawing a flow of hot gas down the
line from the compressors through the action of a dedicated solenoid valve.
The process starts working based on the humidity set-point established by the user. With respect to traditional
devices, such as electrical heating elements or hot water coils, the use of the post-heating coil does not consume
any energy. It also lowers the condensation temperature, which provides two positive effects: the power absorbed
by the compressors is considerably reduced, and at the same time the cooling power is increased with greater
EER.
TREATMENT COIL
HUMID AIR
RE-HEATING COIL
COLD AIR
TREATED AIR
HUMIDITY
CONDENSATE DISCHARGE
COMPRESSORS
TO THE CONDENSER
BT08A006GB-03
ELECTRONIC EXPANSION
VALVE
40
This option reduces the available static pressure (air side).
PACKAGED
362 - 904
PERFORMANCE HOT GAS RE-HEATING COIL
outdoor air temperature °C
25
27
30
32
35
25
27
30
32
35
25
27
30
32
35
kWt
kWt
kWt
4444
kWt
kWt
kWt
kWt
kWt
5556
kWt
kWt
kWt
kWt
kWt
6667
kWt
kWt
10
34,0
36,6
40,6
43,3
47,4
38,8
41,8
46,4
49,5
54,2
41,7
45,0
50,0
53,4
58,5
12
31,3
33,9
37,9
40,6
44,7
35,7
38,7
43,3
46,4
51,0
38,4
41,7
46,7
50,0
55,1
14
28,6
31,2
35,2
37,9
41,9
32,6
35,6
40,2
43,3
47,9
35,1
38,4
43,3
46,6
51,7
16
26,0
28,6
32,5
35,2
39,2
29,6
32,6
37,1
40,2
44,8
31,9
35,1
40,0
43,3
48,3
18
23,3
25,9
29,8
32,5
36,5
26,6
29,6
34,0
37,1
41,7
28,6
31,8
36,7
40,0
44,9
20
20,7
23,3
27,2
29,8
33,8
23,6
26,5
31,0
34,0
38,6
25,4
28,6
33,4
36,7
41,6
362
Ta (°C)
Qo (l / s)
402
Ta (°C)
Qo (l / s)
4889
35,9
38,8
43,0
45,9
50,2
40,9
44,2
49,1
52,4
57,3
45,0
48,6
54,0
57,6
63,1
12
33,1
35,9
40,1
43,0
47,3
37,7
40,9
45,8
49,0
54,0
41,4
45,0
50,3
53,9
59,4
14
30,3
33,1
37,3
40,1
44,4
34,5
37,7
42,5
45,7
50,6
37,9
41,4
46,7
50,3
55,7
16
27,5
30,2
34,4
37,2
41,5
31,3
34,4
39,2
42,4
47,3
34,4
37,8
43,1
46,7
52,1
18
24,7
27,4
31,6
34,4
38,6
28,1
31,2
36,0
39,2
44,1
30,8
34,3
39,6
43,1
48,5
20
21,9
24,6
28,8
31,6
35,8
24,9
28,0
32,8
36,0
40,8
27,4
30,8
36,0
39,5
44,9
Ta (°C)
5333
37,8
40,8
45,3
48,3
52,9
43,0
46,4
51,6
55,1
60,3
46,0
49,6
55,1
58,9
64,5
34,8
37,8
42,3
45,3
49,8
39,6
43,0
48,1
51,5
56,8
42,3
45,9
51,4
55,1
60,7
14
31,9
34,8
39,2
42,2
46,8
36,2
39,6
44,6
48,1
53,3
38,7
42,3
47,7
51,4
56,9
16
28,9
31,8
36,2
39,2
43,7
32,9
36,2
41,2
44,6
49,8
35,1
38,6
44,0
47,7
53,2
18
26,0
28,9
33,2
36,2
40,7
29,5
32,8
37,8
41,2
46,3
31,5
35,0
40,4
44,0
49,5
20
23,0
25,9
30,3
33,2
37,7
26,1
29,4
34,4
37,8
42,9
27,9
31,4
36,8
40,4
45,8
Ta (°C)
6389
50,2
54,1
60,2
64,2
70,4
55,9
60,4
67,2
71,7
78,6
64,4
69,6
77,4
82,7
90,6
46,1
50,0
56,0
60,1
66,2
51,4
55,8
62,5
67,1
73,9
59,1
64,3
72,0
77,3
85,2
14
42,0
46,0
51,9
55,9
62,0
46,9
51,3
57,9
62,4
69,2
53,9
59,0
66,7
71,9
79,8
16
38,0
42,0
47,9
51,9
57,9
42,4
46,8
53,4
57,9
64,6
48,7
53,8
61,5
66,6
74,4
18
34,1
38,0
43,9
47,8
53,8
37,9
42,3
48,9
53,3
60,0
43,6
48,6
56,3
61,4
69,1
20
30,2
34,1
39,9
43,8
49,7
33,6
37,9
44,5
48,8
55,4
38,5
43,6
51,1
56,2
63,8
Ta (°C)
7222
Ta (°C)
Ta (°C)
Ta (°C)
Ta (°C)
10833
54,0
58,3
64,8
69,2
75,9
61,7
66,6
74,1
79,1
86,7
68,6
74,1
82,4
88,0
96,5
12
49,6
53,9
60,4
64,7
71,3
56,6
61,5
69,0
74,0
81,5
62,9
68,4
76,7
82,2
90,7
14
45,3
49,5
55,9
60,3
66,8
51,6
56,5
63,9
68,9
76,4
57,3
62,8
71,0
76,6
85,0
16
41,0
45,2
51,6
55,9
62,4
46,7
51,5
58,9
63,8
71,3
51,8
57,2
65,4
70,9
79,3
18
36,7
40,9
47,2
51,5
57,9
41,8
46,6
53,9
58,8
66,2
46,3
51,7
59,9
65,3
73,6
20
32,5
36,7
43,0
47,2
53,6
36,9
41,7
49,0
53,8
61,2
40,9
46,3
54,4
59,8
68,0
8056
10000
11667
10
57,7
62,3
69,3
73,9
81,0
65,5
70,7
78,7
84,0
92,1
71,5
77,3
86,0
91,8
100,7
12
53,0
57,5
64,5
69,1
76,2
60,1
65,3
73,2
78,5
86,6
65,6
71,3
80,0
85,8
94,6
14
48,3
52,8
59,7
64,4
71,4
54,8
60,0
67,8
73,1
81,1
59,8
65,5
74,1
79,9
88,6
16
43,7
48,2
55,0
59,6
66,6
49,5
54,7
62,5
67,7
75,7
54,0
59,7
68,2
74,0
82,7
18
39,1
43,6
50,4
55,0
61,9
44,3
49,4
57,2
62,4
70,3
48,3
53,9
62,4
68,1
76,8
20
34,6
39,1
45,8
50,3
57,1
39,1
44,3
52,0
57,1
64,9
42,7
48,3
56,7
62,4
70,9
8889
11111
12222
10
61,1
66,0
73,4
78,4
85,9
69,5
75,1
83,6
89,3
97,9
73,4
79,3
88,3
94,3
103,4
12
56,1
61,0
68,3
73,3
80,8
63,8
69,4
77,8
83,5
92,0
67,3
73,2
82,1
88,1
97,2
14
51,2
56,0
63,3
68,2
75,7
58,2
63,7
72,0
77,7
86,2
61,4
67,2
76,0
82,0
91,0
16
46,3
51,1
58,3
63,2
70,6
52,6
58,0
66,4
72,0
80,4
55,4
61,2
70,0
75,9
84,9
18
41,4
46,2
53,4
58,3
65,6
47,0
52,5
60,7
66,3
74,7
49,6
55,3
64,1
70,0
78,8
20
36,6
41,4
48,5
53,3
60,6
41,5
47,0
55,2
60,7
69,0
43,7
49,5
58,2
64,0
72,8
10000
12500
14722
10
78,5
84,6
93,7
99,9
109,3
89,6
96,6
107,1
114,2
124,9
98,5
106,2
117,8
125,6
137,5
12
72,4
78,4
87,5
93,7
103,0
82,7
89,6
100,0
107,1
117,8
90,8
98,5
110,0
117,8
129,6
14
66,4
72,3
81,4
87,5
96,8
75,8
82,6
93,0
100,0
110,6
83,2
90,8
102,3
110,0
121,7
16
60,4
66,3
75,3
81,4
90,6
68,9
75,7
86,0
93,0
103,5
75,6
83,1
94,5
102,2
113,9
18
54,4
60,3
69,2
75,3
84,4
62,0
68,8
79,0
86,0
96,5
68,1
75,6
86,9
94,5
106,1
20
48,4
54,3
63,2
69,2
78,3
55,2
61,9
72,1
79,0
89,5
60,7
68,1
79,3
86,9
98,4
Qo (l / s)
904
9028
10
Qo (l / s)
804
9722
12
Qo (l / s)
704
8056
10
Qo (l / s)
604
7500
12
Qo (l / s)
524
6667
10
Qo (l / s)
464
7222
10
Qo (l / s)
452
6111
11111
13889
BT08A006GB-03
Size
15555
10
83,6
90,1
99,9
106,5
116,5
95,3
102,7
113,9
121,5
132,9
101,7
109,6
121,6
129,7
141,9
12
77,1
83,6
93,3
99,8
109,8
87,8
95,2
106,4
113,9
125,3
93,7
101,6
113,5
121,6
133,7
14
70,7
77,1
86,7
93,2
103,1
80,5
87,8
98,9
106,3
117,7
85,8
93,7
105,5
113,5
125,6
16
64,3
70,6
80,2
86,7
96,5
73,1
80,4
91,4
98,9
110,1
78,0
85,8
97,6
105,5
117,5
18
57,9
64,2
73,7
80,2
90,0
65,9
73,1
84,0
91,4
102,6
70,3
78,0
89,7
97,6
109,5
20
51,5
57,8
67,3
73,7
83,4
58,7
65,9
76,7
84,0
95,2
62,6
70,2
81,8
89,7
101,6
Ta = outlet air temperature from the treatment coil and entering the post-heating coil
Qo = air flow rate (l/s)
kWt = thermal power provided (kW)
The post-heating coil is supplied with hot gas released between the supply of the compressor and the condensation coil. Since the temperature of the hot condensation gas is related to the outside air temperature, the approximate powers of the post-heating coil are expressed based on the outside air temperature.
41
PACKAGED
362 - 904
PAQC - AIR QUALITY SENSOR FOR CO2 P.P.M. CONTROL
This option is recommended for areas with highly variable rates of traffic. The
probe measure the amount of CO2 in the environment and sends the machine
a 0/10V proportional signal. Based on the received signal, the machine
manages the input of the correct amount of refresh air, preventing wasted
energy and money due to a treatment of fresh air in excess of actual needs.
The probe is installed and wired on board the machine and is located in the
unit's supply duct.
In units in constructive configuration B, the probe must be combined with the
modulating fresh air shutter accessory for efficient adjustment of the intake of
fresh air.
PAQCV - AIR QUALITY SENSOR FOR CO2 AND VOC P.P.M. CONTROL
The option is recommended in areas with tobacco smoke, formaldehyde (from
solvents, deodorants, glues, paints, detergents), food preparation, etc. The
probe measure the amount of CO2 and VOC (volatile organic compounds) in
the environment and sends the machine a 0/10V proportional signal. Based on
the received signal, the machine manages the input of the correct amount of
refresh air, preventing wasted energy and money due to a treatment of fresh
air in excess of actual needs.
The probe is installed and wired on board the machine and is located in the
unit's supply duct.
In units in constructive configuration B, the probe must be combined with the
modulating fresh air shutter accessory for efficient adjustment of the intake of
fresh air.
MHP - HIGH AND LOW PRESSURE GAUGES
It allows measurement of the pressure of the refrigerant at the supply and
return of the compressors, making these parameters easier to check by
technicians assigned to operate the machine.
The two liquid pressure gauges and corresponding pressure sockets are
installed on the machine in an easily accessible location.
BT08A006GB-03
CREFB - DEVICE FOR REDUCTION OF FAN CONSUMPTION ECOBREEZE
This option is recommended for substantial reduction in the consumption of electrical
energy for ventilation and to limit noise emissions in the external section of the
machine. The Eco-Breeze logic makes it possible to run the external axial fans with
variable rotation speed based on the condensation pressure. When fresh air
temperature is low, a minimum air flow rate is required to hold down the condensation
pressure. Therefore, at low fresh air temperatures, fan rotation speed is reduced,
resulting in reduced electricity consumption and noise emission (summer operation).
In operation in heat pump mode with low outside temperature, ventilation is reduced to
the external coil so as not to exceed the evaporation pressure limits for correct
operation of the unit, with the added benefit of reduced electrical consumption and
noise.
The Eco-Breeze option uses special fans driven by brushless electric motors with complete electronic control and
very high efficiency.
2000
1800
90%
1600
80%
40%
30%
20%
10%
%
1200
Input power [W]
50%
3 ph motor
Efficiency
60%
EcoBreeze
1400
70%
1000
800
600
400
Traditional fans
200
0
1500
EcoBreeze
2000
2500
3000
3500
Air Performance [l/s]
42
4000
4500
5000
PACKAGED
362 - 904
PM - PHASE MONITOR
The phase monitor makes it possible to check the correct connection of the phases and their imbalance in units
powered with a tri-phase system. If the connection of the phases is not correct, or the limit is exceeded for
imbalance between phases, the monitor acts on the control circuit, which orders shutdown of the machine.
PFCP - POWER FACTOR CORRECTION CAPACITORS (COSFI > 0.9)
The component is necessary to lower the phase difference between current and voltage
in the electromagnetic components of the machine, such as asynchronous motors. By re
-phasing it is possible to reduce the intensity of the line current by reducing a part of the
power of the mains (reactive power).
This leads to an economic benefit which the energy provider grants to the final user.
The component makes it possible to bring the cosfi power factor to values which on
average are greater than 0.9.
MOB - SERIAL PORT RS485 WITH MODBUS PROTOCOL
It allows serial connection of supervision systems, using ModBus as the communication
protocol. It allows access to the complete list of operating variables, controls and alarms.
LON - SERIAL PORT RS485 WITH LONWORKS PROTOCOL
It allows serial connection of supervision systems, using LonWorks as the
communication protocol. It allows access to a list of operating variables, control and
alarms compliant with the Echelon standard.
RCMRX - REMOTE CONTROL WITH REMOTE MICROPROCESSOR CONTROL
Roof-top connection
Cable
120
Device which allows complete control of the
machine from a remote location. It is easily wallmounted, and has the same appearance and
functions as the user interface on board the unit
(user-friendly software). To be connected during
commissioning of the machine at a maximum
distance of 100 m.
power supply
150
separately supplied accessories
Clivet Management System (CMS) is a Clivet supervision
system that allow to schedule and manage all the installed
Clivet conditioning units, optimizing their functional working and
the others systems in order to reduce the energy consumption.
Thanks to the simple use of the software and to the
tridimensional graphic interface, it is possible to change
complex activities of system operating into simple activities
made by the customer. Clivet management system let to
visualize the maintenance state of the conditioning units,
valuate and manage the alarms. The user makes operation on
the supervision workstation or on the PLC (Programmable Logic
Controller) interface display. The exchange data between
workstation, units, control electronic devices, remote managing
electronic devices is made on serial bus networks by
communication standard protocol RS485, or on local network
LAN (Local Area Network) Ethernet TCP/IP.
The control software let to verify the conditioning unit and to
make the on-line assistance directly from Clivet factory using
the telephone network.
BT08A006GB-03
CMS - CLIVET MANAGEMENT SYSTEM (CMS)
43
PACKAGED
362 - 904
CSRN-XHE OPTIONS
OPTION
DESCRIPTION
VERSION B
VERSION C
Active energy recovery of expelled air
-
●
Versions
RE1
FC
Thermal free cooling
○
●
FCE
Enthalpy free cooling
○
○
CB
Configuration with mixing and recycling box and ambient air intake
●
-
CC
Configuration with exhaust air fan and mixing box
-
●
Configurations
CREFP
Device for fan consumption reduction of the external section with variable speed (phase-cutting)
○
○
CREFB
Device for reduction of fan consumption EcoBreeze
○
○
CHW2
2 rows hot water coil
○
○
3WVM
Modulating three-way valve
○
○
EH
Electric heaters
○
○
GH
Gas burner
○
○
Refrigerant Circuit
EVE
Electronic expansion valve
●
●
MHP
High and low pressure gauges
○
○
CPHG
Hot gas re-heating coil
○
○
FPG4
Pleated air filter class G4 (EN779 norm)
●
●
High efficiency F7 air filter
○
○
High efficiency H10 electrostatic air filter
○
○
PSAF
Differential pressure switch for dirty air filters
○
○
Ducting Circuit
F7
FES
HSE
Electrode boiler steam humidifier
○
○
HWS
Water to waste evaporating wet-deck humidifier
○
○
SERM
On/off motorized air outlet damper
○
-
SERMD
Modulating air outlet damper
○*
●
SFSTRV
Fan breakaway starting current reducing device.
*
*
Application with fabric ducts
-
○
CANT
Electric Circuit
Remote control with remote microprocessor control
○
○
MOB
Serial port RS485 with MODBUS protocol
○
○
LON
Serial port RS485 with LONWORKS protocol
○
○
Air quality sensor for CO2 p.p.m. control
○
○
Air quality sensor for CO2 and VOC p.p.m. control
○
○
Phase monitor
○
○
Power factor correction capacitors (cosfi > 0.9)
○
○
RCMRX
PAQC
PAQCV
BT08A006GB-03
PM
PFCP
●
Standard component.
○
-
Optional component.
Component not included.
○* Component not necessary with selection of air quality probe; component not necessary with option free-cooling B.
*
standard for sizes 362-402-452; optional for sizes from 464 to 904
separately supplied accessories
44
PACKAGED
362 - 904
FUNCTIONAL CLEARANCES
When placing the unit, it is necessary to comply with the functional spaces indicated in the dimensions.
Compliance with fictional spaces is essential to:
- ensure proper operation of the unit
- allow maintenance technicians easy access to the equipment compartments
- protect authorized operators and exposed persons.
If several units are placed near one another, the functional spaces between machines must be doubled.
DIMENSIONAL DRAWING
SIZE 362 – 452 CONSTRUCTION VERSION B
DIMENSIONAL DRAWING(1)
4810
3
2
2
546
M
620 *
5
20
17
311
6
4
60
300
1877
2730 *
3970
21
R
113
8
1
905
9
620 *
H1
1500**
201
R
2250
297
M
22
W1
W2
1250
2180
2280
60
630
4
7
10
1500**
15
11
16
12
13
18
14
2
1500**
14
W3
AE
6
7
WEIGHT DISTRIBUTION
CONSTRUCTIONAL CONFIGURATION: RECIRCULATED/OUTSIDE AIR MIXING BOX (B)
Size
W1
W2
W3
W4
Shipping weight
kg
kg
kg
kg
kg
362
402
452
482
504
608
699
2293
486
509
613
705
2313
497
521
627
722
2367
(1) REMOVABLE PANEL FOR ACCESS TO THE COMPRESSOR
COMPARTMENT
(2) ELECTRICAL PANEL
(3) MICROPROCESSOR KEYBOARD
(4) POWER INPUT
(5) HUMIDIFIER INLET CONNECTIONS
(6) CONDENSATE DISCHARGE
(7) FUNCTIONAL CLEARANCES
(8) WATER INLET INTEGRATING COIL Ø 1 1/2"
(9) WATER OUTLET INTEGRATING COIL Ø 1 1/2"
(10) RE-HEATING COIL (OPTIONAL)
(11) TREATMENT COIL
(12) WATER HEATING COIL (OPTIONAL)
(13) ELECTRONIC AIR FILTERS / F7 BAG FILTERS (OPTIONAL)
(14) G4 AIR FILTERS
(15) OUTLET CENTRIFUGAL FAN
(16) MOTOR WITH SUPPLY TRANSMISSION
(17) LIFTING BRACKETS (REMOVABLE, IF REQUIRED, AFTER
POSITIONING THE UNIT)
(18) FRESH AIR SHUTTER
(20) RECIRCULATION SHUTTER (OPTIONAL)
(21) ACCESS TO FANS/MOTORS AND TRANSMISSIONS
(22) ACCESS FOR INSPECTION OF COILS, FILTERS, HEATING
ELEMENTS
R = AIR INTAKE FROM OUTSIDE
M=OUTLET AIR
AE = FRESH AIR INTAKE
H1 = WALL ON TWO SIDES MAX.
(*) VIBRATION MOUNTS POSITION
(**) SUGGESTED CLEARANCE
BT08A006GB-03
H1
W4
The presence of optional accessories may result in a substantial variation of the weights shown in the table.
45
PACKAGED
362 - 904
DIMENSIONAL DRAWING
SIZE 362 – 452 CONSTRUCTION VERSION B GAS MODULE 96 kW - 200 kW
DIMENSIONAL DRAWING(2)
5962
25 26
24
2
3
28
M
29
890
27
R
20
2
219
2250
872
M
R
4
1
619 *
113
17
6
2062 *
2062 *
379 *
60
298
1500 **
5121
21
7
W3
W2
375
4
H1
1500
10
15
1506
2180
2280
60
H1
22
W1
5
**
11
16
23
13
18
14
W4
W5
26
6
14
AE
1500 **
2
W6
7
BT08A006GB-03
WEIGHT DISTRIBUTION
46
CONSTRUCTIONAL CONFIGURATION: RECIRCULATED/OUTSIDE AIR MIXING BOX (B)
Size
362
402
452
W1
kg
438
442
450
W2
kg
446
449
458
W3
kg
447
450
459
W4
kg
461
464
473
W5
kg
474
477
487
W6
Shipping weight
kg
461
464
473
kg
2726
2746
2800
(1) REMOVABLE PANEL FOR ACCESS TO THE COMPRESSOR
COMPARTMENT
(2) ELECTRICAL PANEL
(3) MICROPROCESSOR KEYBOARD
(4) POWER INPUT
(5) HUMIDIFIER INLET CONNECTIONS
(6) CONDENSATE DISCHARGE
(7) FUNCTIONAL CLEARANCES
(10) RE-HEATING COIL (OPTIONAL)
(11) TREATMENT COIL
(13) ELECTRONIC AIR FILTERS / F7 BAG FILTERS (OPTIONAL)
(14) G4 AIR FILTERS
(15) OUTLET CENTRIFUGAL FAN
(16) MOTOR WITH SUPPLY TRANSMISSION
(17) LIFTING BRACKETS (REMOVABLE, IF REQUIRED, AFTER
POSITIONING THE UNIT)
(18) FRESH AIR SHUTTER
(20) RECIRCULATION SHUTTER (OPTIONAL)
(21) ACCESS TO FANS/MOTORS AND TRANSMISSIONS
(22) ACCESS FOR INSPECTION OF COILS, FILTERS, HEATING
ELEMENTS
(23) GAS MODULE
(24) DISCHARGE WASTE GAS (PROVIDED UN-ASSEMBLED)
(25) INTAKING AIR BURNER
(26) GAS BURNER COMPARTMENT
(27) GAS MODULE SUPPLY (1" GAS)
(28) SAFETY THERMOSTAT INSPECTION COMPARTMENT
(29) SUPPLY TEMPERATURE PROBE INSPECTION COMPARTMENT
R = AIR INTAKE FROM OUTSIDE
M=OUTLET AIR
AE = FRESH AIR INTAKE
H1 = WALL ON TWO SIDES MAX.
(*) VIBRATION MOUNTS POSITION
(**) SUGGESTED CLEARANCE
PACKAGED
362 - 904
DIMENSIONAL DRAWING
SIZE 362 – 452 CONSTRUCTION VERSION C
DIMENSIONAL DRAWING(3)
4810
3
2
2
546
M
R
8
6
R
5
19
20
17
311
1
620 *
905
9
60
300
1877
2730 *
3970
4
113
201
ES
2250
297
M
620 *
H1
1250
2180
60
630
4
21
22
W1
W2
1500**
2280
7
10
1500**
15
11
16
12
13
18
14
2
AE
6
7
WEIGHT DISTRIBUTION
CONSTRUCTIONAL CONFIGURATION: FREE COOLING VERSION WITH EXTRACT/
RECIRCULATED/FRESH AIR INTAKE BOX (C)
Size
W1
W2
W3
W4
Shipping weight
kg
kg
kg
kg
kg
362
402
452
552
528
624
696
2399
556
532
629
702
2419
570
546
645
719
2480
(1) REMOVABLE PANEL FOR ACCESS TO THE COMPRESSOR
COMPARTMENT
(2) ELECTRICAL PANEL
(3) MICROPROCESSOR KEYBOARD
(4) POWER INPUT
(5) HUMIDIFIER INLET CONNECTIONS
(6) CONDENSATE DISCHARGE
(7) FUNCTIONAL CLEARANCES
(8) WATER INLET INTEGRATING COIL Ø 1 1/2"
(9) WATER OUTLET INTEGRATING COIL Ø 1 1/2"
(10) RE-HEATING COIL (OPTIONAL)
(11) TREATMENT COIL
(12) WATER HEATING COIL (OPTIONAL)
(13) ELECTRONIC AIR FILTERS / F7 BAG FILTERS (OPTIONAL)
(14) G4 AIR FILTERS
(15) SUPPLY AND RETURN CENTRIFUGAL FANS
(16) MOTORS WITH RETURN AND SUPPLY TRANSMISSION
(17) LIFTING BRACKETS (REMOVABLE, IF REQUIRED, AFTER
POSITIONING THE UNIT)
(18) FRESH AIR SHUTTER
(19) DISCHARGE DAMPER
(20) RECIRCULATION SHUTTER
(21) ACCESS TO FANS/MOTORS AND TRANSMISSIONS
(22) ACCESS FOR INSPECTION OF COILS, FILTERS, HEATING
ELEMENTS
R = AIR INTAKE FROM OUTSIDE
M=OUTLET AIR
AE = FRESH AIR INTAKE
ES = AIR EXPULSION
H1 = WALL ON TWO SIDES MAX.
(*) VIBRATION MOUNTS POSITION
(**) SUGGESTED CLEARANCE
BT08A006GB-03
14
W3
1500**
H1
W4
The presence of optional accessories may result in a substantial variation of the weights shown in the table.
47
PACKAGED
362 - 904
DIMENSIONAL DRAWING
SIZE 362 – 452 CONSTRUCTION VERSION C GAS MODULE 96 kW - 200 kW
DIMENSIONAL DRAWING(4)
5962
25 26
24
2
3
28
20
M
29
890
27
R
ES
2
219
2250
872
M
R
19
6
2062 *
113
1
619 *
4
17
2062 *
60
379 *
1500 **
5121
21
7
4
H1
1500**
10
15
60
375
2280
W3
W2
1506
2180
H1
22
W1
5
298
11
16
23
13
14
18
26
BT08A006GB-03
W4
W5
W6
6
AE
14
1500 **
2
7
WEIGHT DISTRIBUTION
CONSTRUCTIONAL CONFIGURATION: FREE COOLING VERSION WITH EXTRACT/
RECIRCULATED/FRESH AIR INTAKE BOX (C)
362
402
452
W1
kg
467
471
481
W2
kg
471
474
484
W3
kg
459
462
472
W4
kg
476
479
489
W5
kg
487
491
501
W6
Shipping weight
kg
472
475
486
kg
2832
2852
2913
Size
(1) REMOVABLE PANEL FOR ACCESS TO THE COMPRESSOR
COMPARTMENT
(2) ELECTRICAL PANEL
(3) MICROPROCESSOR KEYBOARD
(4) POWER INPUT
(5) HUMIDIFIER INLET CONNECTIONS
(6) CONDENSATE DISCHARGE
(7) FUNCTIONAL CLEARANCES
(10) RE-HEATING COIL (OPTIONAL)
(11) TREATMENT COIL
(13) ELECTRONIC AIR FILTERS / F7 BAG FILTERS (OPTIONAL)
(14) G4 AIR FILTERS
(15) SUPPLY AND RETURN CENTRIFUGAL FANS
(16) MOTORS WITH RETURN AND SUPPLY TRANSMISSION
(17) LIFTING BRACKETS (REMOVABLE, IF REQUIRED, AFTER POSITIONING THE UNIT)
(18) FRESH AIR SHUTTER
(19) DISCHARGE DAMPER
(20) RECIRCULATION SHUTTER
(21) ACCESS TO FANS/MOTORS AND TRANSMISSIONS
(22) ACCESS FOR INSPECTION OF COILS, FILTERS, HEATING
ELEMENTS
(23) GAS MODULE
(24) DISCHARGE WASTE GAS (PROVIDED UN-ASSEMBLED)
(25) INTAKING AIR BURNER
(26) GAS BURNER COMPARTMENT
(27) GAS MODULE SUPPLY (1" GAS)
(28) SAFETY THERMOSTAT INSPECTION COMPARTMENT
(29) SUPPLY TEMPERATURE PROBE INSPECTION COMPARTMENT
R = AIR INTAKE FROM OUTSIDE
M=OUTLET AIR
AE = FRESH AIR INTAKE
ES = AIR EXPULSION
H1 = WALL ON TWO SIDES MAX.
(*) VIBRATION MOUNTS POSITION
(**) SUGGESTED CLEARANCE
The presence of optional accessories may result in a substantial variation of the weights shown in the table.
48
PACKAGED
362 - 904
DIMENSIONAL DRAWING
SIZE 464 – 704 CONSTRUCTION VERSION B
DIMENSIONAL DRAWING(5)
5890
3
2
1680
870
138
185
M
R
640
828
1
2
18
2272
5
M
8
660
AE
9
R
2158
2361 *
385 *
1970
2361 *
4
198
6
17
661
693 *
65
1
1
17
65
2185
6
5800
2296
2000*
H1
7
8-9 6
7
AE
W2
W1
1500**
H1
W3
18
14 13
1200**
21
10
11 12
16
2
W6
W5
20
W4
15
WEIGHT DISTRIBUTION
CONSTRUCTIONAL CONFIGURATION: RECIRCULATED/OUTSIDE AIR MIXING BOX (B)
Size
W1
W2
W3
W4
W5
W6
Shipping weight
kg
kg
kg
kg
kg
kg
kg
464
524
604
704
498
473
472
484
465
500
2893
511
486
485
498
478
514
2973
556
529
528
541
520
559
3233
568
540
539
553
531
571
3303
(1) REMOVABLE PANEL FOR ACCESS TO THE COMPRESSOR
COMPARTMENT
(2) ELECTRICAL PANEL
(3) MICROPROCESSOR KEYBOARD
(4) POWER INPUT
(5) HUMIDIFIER INLET CONNECTIONS
(6) CONDENSATE DISCHARGE
(7) FUNCTIONAL CLEARANCES
(8) WATER INLET INTEGRATING COIL Ø 2"
(9) WATER OUTLET INTEGRATING COIL Ø 2"
(10) RE-HEATING COIL (OPTIONAL)
(11) TREATMENT COIL
(12) WATER HEATING COIL (OPTIONAL)
(13) ELECTRONIC AIR FILTERS / F7 BAG FILTERS (OPTIONAL)
(14) G4 AIR FILTERS
(15) OUTLET CENTRIFUGAL FAN
(16) MOTOR WITH SUPPLY TRANSMISSION
(17) LIFTING BRACKETS (REMOVABLE, IF REQUIRED, AFTER
POSITIONING THE UNIT)
(18) FRESH AIR SHUTTER
(20) ACCESS TO FANS/MOTORS AND TRANSMISSIONS
(21) ACCESS FOR INSPECTION OF COILS, FILTERS, HEATING
ELEMENTS
R = AIR INTAKE FROM OUTSIDE
M=OUTLET AIR
AE = FRESH AIR INTAKE
H1 = WALL ON TWO SIDES MAX.
(*) VIBRATION MOUNTS POSITION
(**) SUGGESTED CLEARANCE
BT08A006GB-03
6
The presence of optional accessories may result in a substantial variation of the weights shown in the table.
49
PACKAGED
362 - 904
DIMENSIONAL DRAWING
SIZE 464 – 704 CONSTRUCTION VERSION B GAS MODULE 96 kW - 200 kW
DIMENSIONAL DRAWING(6)
5890
18
2030
2
24 25
M
5
3
2
2030
1
536
27
26
R
R
660
152
2272
M
1015
23
4
64
64
2185
385 *
2361 *
459
2361 *
2000**
W1
3976
13
18
(1) REMOVABLE PANEL FOR ACCESS TO THE COMPRESSOR
COMPARTMENT
(2) ELECTRICAL PANEL
(3) MICROPROCESSOR KEYBOARD
(4) POWER INPUT
(5) HUMIDIFIER INLET CONNECTIONS
(6) CONDENSATE DISCHARGE
(7) FUNCTIONAL CLEARANCES
(10) RE-HEATING COIL (OPTIONAL)
(11) TREATMENT COIL
(13) ELECTRONIC AIR FILTERS / F7 BAG FILTERS (OPTIONAL)
(14) G4 AIR FILTERS
(15) OUTLET CENTRIFUGAL FAN
(16) MOTOR WITH SUPPLY TRANSMISSION
(17) LIFTING BRACKETS (REMOVABLE, IF REQUIRED, AFTER
POSITIONING THE UNIT)
(18) FRESH AIR SHUTTER
(20) ACCESS TO FANS/MOTORS AND TRANSMISSIONS
(21) ACCESS FOR INSPECTION OF COILS, FILTERS, HEATING
ELEMENTS
(22) GAS MODULE (TO BE CONNECTED TO THE UNIT DURING
INSTALLATION)
(23) DISCHARGE WASTE GAS (PROVIDED UN-ASSEMBLED)
(24) INTAKING AIR BURNER
(25) GAS BURNER COMPARTMENT
(26) GAS MODULE SUPPLY (1" GAS)
(27) CONDENSATE DISCHARGE GAS MODULE
R = AIR INTAKE FROM OUTSIDE
M=OUTLET AIR
AE = FRESH AIR INTAKE
H1 = WALL ON TWO SIDES MAX.
(*) VIBRATION MOUNTS POSITION
(**) SUGGESTED CLEARANCE
11
20
15
16
2
W4
H1
W5
W7
W8
22
W10
W9
WEIGHT DISTRIBUTION
BT08A006GB-03
CONSTRUCTIONAL CONFIGURATION: RECIRCULATED/OUTSIDE AIR MIXING BOX (B)
Size
kg
kg
kg
kg
kg
kg
kg
Size
464
524
604
704
498
473
472
484
465
500
2893
511
486
485
498
478
514
2973
556
529
528
541
520
559
3233
568
540
539
553
531
571
3303
96kW
150-200kW
94
W7
kg
86
W8
kg
83
90
W9
kg
134
146
W10
kg
147
160
Shipping weight
kg
450
490
The presence of optional accessories may result in a substantial variation of the weights shown in the table.
50
255 *
46
1200**
6
W1
W2
W3
W4
W5
W6
Shipping weight
1235 *
W3
21
W6
255 *
7
AE
W2
10
17
64
H1
6
14
1500**
1
2185
693 *
5800
7
1
64
6
148
17
PACKAGED
362 - 904
DIMENSIONAL DRAWING
SIZE 464 – 704 CONSTRUCTION VERSION B GAS MODULE 300 kW
DIMENSIONAL DRAWING(7)
5890
5169
23
18
5
2272
25
M
2
M
26
25
152
2030
3
1230
24
2
1
R
4
64
2185
7
W1
2361 *
2000**
385 *
2361 *
6
693 *
6
AE
2185
17
255 *
2356 *
255 *
5097
7
W3
18
14 13
21
6
10 11
20
15
2
W6
64
46
H1
5800
W2
1
64 1
64
459
148
17
445
27
536
2030
R
W4
16
W5
W8
W7
1500**
1200**
H1
22
22
W9
W10
(1) REMOVABLE PANEL FOR ACCESS TO THE COMPRESSOR COMPARTMENT
(2) ELECTRICAL PANEL
(3) MICROPROCESSOR KEYBOARD
(4) POWER INPUT
(5) HUMIDIFIER INLET CONNECTIONS
(6) CONDENSATE DISCHARGE
(7) FUNCTIONAL CLEARANCES
(10) RE-HEATING COIL (OPTIONAL)
(11) TREATMENT COIL
(13) ELECTRONIC AIR FILTERS / F7 BAG FILTERS (OPTIONAL)
(14) G4 AIR FILTERS
(15) OUTLET CENTRIFUGAL FAN
(16) MOTOR WITH SUPPLY TRANSMISSION
(17) LIFTING BRACKETS (REMOVABLE, IF REQUIRED, AFTER POSITIONING THE UNIT)
(18) FRESH AIR SHUTTER
(20) ACCESS TO FANS/MOTORS AND TRANSMISSIONS
(21) ACCESS FOR INSPECTION OF COILS, FILTERS, HEATING ELEMENTS
(22) GAS MODULE (TO BE CONNECTED TO THE UNIT DURING INSTALLATION)
(23) DISCHARGE WASTE GAS (PROVIDED UN-ASSEMBLED)
(24) INTAKING AIR BURNER
(25) GAS BURNER COMPARTMENT
(26) GAS MODULE SUPPLY (1" GAS)
(27) CONDENSATE DISCHARGE GAS MODULE
R = AIR INTAKE FROM OUTSIDE
M=OUTLET AIR
AE = FRESH AIR INTAKE
H1 = WALL ON TWO SIDES MAX.
(*) VIBRATION MOUNTS POSITION
(**) SUGGESTED CLEARANCE
WEIGHT DISTRIBUTION
Size
W1
W2
W3
W4
W5
W6
Shipping weight
kg
kg
kg
kg
kg
kg
kg
464
524
604
704
498
473
472
484
465
500
2893
511
486
485
498
478
514
2973
556
529
528
541
520
559
3233
568
540
539
553
531
571
3303
BT08A006GB-03
CONSTRUCTIONAL CONFIGURATION: FREE COOLING VERSION WITH EXTRACT/RECIRCULATED/
FRESH AIR INTAKE BOX (C)
300kW
Size
W7
kg
182
W8
kg
173
W9
kg
270
W10
kg
295
Shipping weight
kg
920
The presence of optional accessories may result in a substantial variation of the weights shown in the table.
51
PACKAGED
362 - 904
DIMENSIONAL DRAWING
SIZE 464 – 704 CONSTRUCTION VERSION C
DIMENSIONAL DRAWING(8)
5890
3
2
1680
870
M
ES
2
18
M
R
640
828
1
138
185
8
660
5
2272
AE
9
R
2158 19
2361 *
385 *
1970
4
198
6
17
661
2361 *
65
1
ES
1
17
65
2185
693 *
6
5800
2296
2000*
H1
7
8-9 6
7
W2
W1
1500**
AE
H1
W3
18
14 13
(1) REMOVABLE PANEL FOR ACCESS TO THE COMPRESSOR
COMPARTMENT
(2) ELECTRICAL PANEL
(3) MICROPROCESSOR KEYBOARD
(4) POWER INPUT
(5) HUMIDIFIER INLET CONNECTIONS
(6) CONDENSATE DISCHARGE
(7) FUNCTIONAL CLEARANCES
(8) WATER INLET INTEGRATING COIL Ø 2"
(9) WATER OUTLET INTEGRATING COIL Ø 2"
(10) RE-HEATING COIL (OPTIONAL)
(11) TREATMENT COIL
(12) WATER HEATING COIL (OPTIONAL)
(13) ELECTRONIC AIR FILTERS / F7 BAG FILTERS (OPTIONAL)
(14) G4 AIR FILTERS
(15) SUPPLY AND RETURN CENTRIFUGAL FANS
(16) MOTORS WITH RETURN AND SUPPLY TRANSMISSION
(17) LIFTING BRACKETS (REMOVABLE, IF REQUIRED, AFTER
POSITIONING THE UNIT)
(18) FRESH AIR SHUTTER
(19) DISCHARGE DAMPER
(20) ACCESS TO FANS/MOTORS AND TRANSMISSIONS
(21) ACCESS FOR INSPECTION OF COILS, FILTERS, HEATING
ELEMENTS
R = AIR INTAKE FROM OUTSIDE
M=OUTLET AIR
AE = FRESH AIR INTAKE
ES = AIR EXPULSION
H1 = WALL ON TWO SIDES MAX.
(*) VIBRATION MOUNTS POSITION
(**) SUGGESTED CLEARANCE
1200**
21
6
10
11 12
16
2
W6
W5
20
W4
BT08A006GB-03
15
WEIGHT DISTRIBUTION
CONSTRUCTIONAL CONFIGURATION: FREE COOLING VERSION WITH EXTRACT/
RECIRCULATED/FRESH AIR INTAKE BOX (C)
Size
W1
W2
W3
W4
W5
W6
Shipping weight
kg
kg
kg
kg
kg
kg
kg
464
524
604
704
500
493
492
522
503
502
3013
513
506
505
536
517
516
3093
557
548
548
581
560
559
3353
568
560
559
594
572
571
3423
The presence of optional accessories may result in a substantial variation of the weights shown in the table.
52
PACKAGED
362 - 904
DIMENSIONAL DRAWING
SIZE 464 – 704 CONSTRUCTION VERSION C GAS MODULE 96 kW - 200 kW
DIMENSIONAL DRAWING(9)
5890
2
2030
3
M
24 25
18
M
5
2
2272
ES
2030
1
536
27
26
R
R
660
152
19
1015
23
4
64
64
2185
385 *
2361 *
459
2361 *
2000**
W1
17
64
255 *
3976
1235 *
255 *
46
7
AE
W3
13
18
1200**
21
6
11
20
15
16
2
W6
1
H1
W2
10
ES
2185
6
14
1500**
1
693 *
5800
7
64
6
148
17
W4
H1
W5
W7
W8
22
W10
W9
(1) REMOVABLE PANEL FOR ACCESS TO THE COMPRESSOR COMPARTMENT
(2) ELECTRICAL PANEL
(3) MICROPROCESSOR KEYBOARD
(4) POWER INPUT
(5) HUMIDIFIER INLET CONNECTIONS
(6) CONDENSATE DISCHARGE
(7) FUNCTIONAL CLEARANCES
(10) RE-HEATING COIL (OPTIONAL)
(11) TREATMENT COIL
(13) ELECTRONIC AIR FILTERS / F7 BAG FILTERS (OPTIONAL)
(14) G4 AIR FILTERS
(15) SUPPLY AND RETURN CENTRIFUGAL FANS
(16) MOTORS WITH RETURN AND SUPPLY TRANSMISSION
(17) LIFTING BRACKETS (REMOVABLE, IF REQUIRED, AFTER POSITIONING THE UNIT)
(18) FRESH AIR SHUTTER
(19) DISCHARGE DAMPER
(20) ACCESS TO FANS/MOTORS AND TRANSMISSIONS
(21) ACCESS FOR INSPECTION OF COILS, FILTERS, HEATING ELEMENTS
(22) GAS MODULE (TO BE CONNECTED TO THE UNIT DURING INSTALLATION)
(23) DISCHARGE WASTE GAS (PROVIDED UN-ASSEMBLED)
(24) INTAKING AIR BURNER
(25) GAS BURNER COMPARTMENT
(26) GAS MODULE SUPPLY (1" GAS)
(27) CONDENSATE DISCHARGE GAS MODULE
R = AIR INTAKE FROM OUTSIDE
M=OUTLET AIR
AE = FRESH AIR INTAKE
ES = AIR EXPULSION
H1 = WALL ON TWO SIDES MAX.
(*) VIBRATION MOUNTS POSITION
(**) SUGGESTED CLEARANCE
WEIGHT DISTRIBUTION
Size
W1
W2
W3
W4
W5
W6
Shipping weight
kg
kg
kg
kg
kg
kg
kg
Size
464
524
604
704
500
493
492
522
503
502
3013
513
506
505
536
517
516
3093
557
548
548
581
560
559
3353
568
560
559
594
572
571
3423
96kW
150-200kW
94
W7
kg
86
W8
kg
83
90
W9
kg
134
146
W10
kg
147
160
Shipping weight
kg
450
490
BT08A006GB-03
CONSTRUCTIONAL CONFIGURATION: FREE COOLING VERSION WITH EXTRACT/
RECIRCULATED/FRESH AIR INTAKE BOX (C)
The presence of optional accessories may result in a substantial variation of the weights shown in the table.
53
PACKAGED
362 - 904
DIMENSIONAL DRAWING
SIZE 464 – 704 CONSTRUCTION VERSION C GAS MODULE 300 kW
DIMENSIONAL DRAWING(10)
5890
5169
23
18
5
2272
M
19
25
2
M
26
25
152
2030
3
1230
24
2
R
4
64
64
459
2185
7
2361 *
2000**
385 *
W1
2361 *
693 *
5800
64
6
AE
1
64
17
255 *
2356 *
46
5097
18
21
6
10 11
20
15
2
W4
16
W5
W8
W7
1500**
1200**
H1
22
22
W10
W9
(1) REMOVABLE PANEL FOR ACCESS TO THE COMPRESSOR COMPARTMENT
(2) ELECTRICAL PANEL
(3) MICROPROCESSOR KEYBOARD
(4) POWER INPUT
(5) HUMIDIFIER INLET CONNECTIONS
(6) CONDENSATE DISCHARGE
(7) FUNCTIONAL CLEARANCES
(10) RE-HEATING COIL (OPTIONAL)
(11) TREATMENT COIL
(13) ELECTRONIC AIR FILTERS / F7 BAG FILTERS (OPTIONAL)
(14) G4 AIR FILTERS
(15) SUPPLY AND RETURN CENTRIFUGAL FANS
(16) MOTORS WITH RETURN AND SUPPLY TRANSMISSION
(17) LIFTING BRACKETS (REMOVABLE, IF REQUIRED, AFTER POSITIONING THE UNIT)
(18) FRESH AIR SHUTTER
(19) DISCHARGE DAMPER
(20) ACCESS TO FANS/MOTORS AND TRANSMISSIONS
(21) ACCESS FOR INSPECTION OF COILS, FILTERS, HEATING ELEMENTS
(22) GAS MODULE (TO BE CONNECTED TO THE UNIT DURING INSTALLATION)
(23) DISCHARGE WASTE GAS (PROVIDED UN-ASSEMBLED)
(24) INTAKING AIR BURNER
(25) GAS BURNER COMPARTMENT
(26) GAS MODULE SUPPLY (1" GAS)
(27) CONDENSATE DISCHARGE GAS MODULE
R = AIR INTAKE FROM OUTSIDE
M=OUTLET AIR
AE = FRESH AIR INTAKE
ES = AIR EXPULSION
H1 = WALL ON TWO SIDES MAX.
(*) VIBRATION MOUNTS POSITION
(**) SUGGESTED CLEARANCE
WEIGHT DISTRIBUTION
BT08A006GB-03
CONSTRUCTIONAL CONFIGURATION: FREE COOLING VERSION WITH EXTRACT/
RECIRCULATED/FRESH AIR INTAKE BOX (C)
Size
W1
W2
W3
W4
W5
W6
Shipping weight
kg
kg
kg
kg
kg
kg
kg
464
524
604
704
500
493
492
522
503
502
3013
513
506
505
536
517
516
3093
557
548
548
581
560
559
3353
568
560
559
594
572
571
3423
300kW
Size
W7
kg
182
W8
kg
173
W9
kg
270
W10
kg
295
Shipping weight
kg
920
The presence of optional accessories may result in a substantial variation of the weights shown in the table.
54
255 *
7
W3
14 13
W6
ES
2185
H1
6
W2
1
148
17
445
27
536
2030
R
ES
1
PACKAGED
362 - 904
DIMENSIONAL DRAWING
SIZE 804 – 904 CONSTRUCTION VERSION B
DIMENSIONAL DRAWING(11)
8024
2
3
1868
1203
9
730
R
740
18
2
M
2272
148
185
1
AE
828
8
5
M
R
4
3107
675 *
3093 *
614
2700
3093 *
198
17
64
17
1075 *
1 64
2185
6
7935
1
2296
2000**
H1
8-9 6
7
W1
W2
1500**
AE
7
H1
W3
1500**
18
14 13
21
6
10
11 12
20
16
2
W6
W4
W5
WEIGHT DISTRIBUTION
CONSTRUCTIONAL CONFIGURATION: RECIRCULATED/OUTSIDE AIR MIXING BOX (B)
Size
W1
W2
W3
W4
W5
W6
Shipping weight
kg
kg
kg
kg
kg
kg
kg
804
904
802
766
765
782
753
805
4673
818
782
780
797
769
821
4768
(1) REMOVABLE PANEL FOR ACCESS TO THE COMPRESSOR COMPARTMENT
(2) ELECTRICAL PANEL
(3) MICROPROCESSOR KEYBOARD
(4) POWER INPUT
(5) HUMIDIFIER INLET CONNECTIONS
(6) CONDENSATE DISCHARGE
(7) FUNCTIONAL CLEARANCES
(8) WATER INLET INTEGRATING COIL Ø 2"
(9) WATER OUTLET INTEGRATING COIL Ø 2"
(10) RE-HEATING COIL (OPTIONAL)
(11) TREATMENT COIL
(12) WATER HEATING COIL (OPTIONAL)
(13) ELECTRONIC AIR FILTERS / F7 BAG FILTERS (OPTIONAL)
(14) G4 AIR FILTERS
(15) OUTLET CENTRIFUGAL FAN
(16) MOTOR WITH SUPPLY TRANSMISSION
(17) LIFTING BRACKETS (REMOVABLE, IF REQUIRED, AFTER POSITIONING THE UNIT)
(18) FRESH AIR SHUTTER
(20) ACCESS TO FANS/MOTORS AND TRANSMISSIONS
(21) ACCESS FOR INSPECTION OF COILS, FILTERS, HEATING ELEMENTS
R = AIR INTAKE FROM OUTSIDE
M=OUTLET AIR
AE = FRESH AIR INTAKE
H1 = WALL ON TWO SIDES MAX.
(*) VIBRATION MOUNTS POSITION
(**) SUGGESTED CLEARANCE
BT08A006GB-03
15
The presence of optional accessories may result in a substantial variation of the weights shown in the table.
55
PACKAGED
362 - 904
DIMENSIONAL DRAWING
SIZE 804 – 904 CONSTRUCTION VERSION B GAS MODULE 150 kW - 200 kW
DIMENSIONAL DRAWING(12)
8024
2780
AE
5
3
18
M
2
2780
1
1 52
2272
M
536
26
27
R
R
660
2
24 25
1015
23
4
64
64
64
2937
676 *
3092 *
3092
*
17
6
459
1
1
17
64
2185
255 *
1235 *
2 55 *
148
17
46
1075 *
3976
7935
2000**
H1
6
7
W1
W2
1500**
14
AE
7
H1
W3
1500**
18
13
21
6
10
11
20
16
2
W6
W4
W5
15
W7
W8
22
W10
W9
(1) REMOVABLE PANEL FOR ACCESS TO THE COMPRESSOR COMPARTMENT
(2) ELECTRICAL PANEL
(3) MICROPROCESSOR KEYBOARD
(4) POWER INPUT
(5) HUMIDIFIER INLET CONNECTIONS
(6) CONDENSATE DISCHARGE
(7) FUNCTIONAL CLEARANCES
(10) RE-HEATING COIL (OPTIONAL)
(11) TREATMENT COIL
(13) ELECTRONIC AIR FILTERS / F7 BAG FILTERS (OPTIONAL)
(14) G4 AIR FILTERS
(15) OUTLET CENTRIFUGAL FAN
(16) MOTOR WITH SUPPLY TRANSMISSION
(17) LIFTING BRACKETS (REMOVABLE, IF REQUIRED, AFTER POSITIONING THE UNIT)
(18) FRESH AIR SHUTTER
(20) ACCESS TO FANS/MOTORS AND TRANSMISSIONS
(21) ACCESS FOR INSPECTION OF COILS, FILTERS, HEATING ELEMENTS
(22) GAS MODULE (TO BE CONNECTED TO THE UNIT DURING INSTALLATION)
(23) DISCHARGE WASTE GAS (PROVIDED UN-ASSEMBLED)
(24) INTAKING AIR BURNER
(25) GAS BURNER COMPARTMENT
(26) GAS MODULE SUPPLY (1" GAS)
(27) CONDENSATE DISCHARGE GAS MODULE
R = AIR INTAKE FROM OUTSIDE
M=OUTLET AIR
AE = FRESH AIR INTAKE
H1 = WALL ON TWO SIDES MAX.
(*) VIBRATION MOUNTS POSITION
(**) SUGGESTED CLEARANCE
WEIGHT DISTRIBUTION
CONSTRUCTIONAL CONFIGURATION: RECIRCULATED/OUTSIDE AIR MIXING BOX (B)
BT08A006GB-03
Size
W1
W2
W3
W4
W5
W6
Shipping weight
kg
kg
kg
kg
kg
kg
kg
804
904
802
766
765
782
753
805
4673
818
782
780
797
769
821
4768
150-200kW
Size
W7
kg
111
W8
kg
107
W9
kg
173
W10
kg
189
Shipping weight
kg
580
The presence of optional accessories may result in a substantial variation of the weights shown in the table.
56
PACKAGED
362 - 904
DIMENSIONAL DRAWING
SIZE 804 – 904 CONSTRUCTION VERSION B GAS MODULE 300 kW
DIMENSIONAL DRAWING(13)
8024
5169
23
18
5
2
M
M
536
2780
1
2272
26
25
27
R
R
17
64
64
4
64
459 6
2937
676 *
3092
*
3092
*
1075 *
6
W1
W2
AE
W3
7
17
255 *
2356 *
255 *
46
5097
H1
1500**
18
14 13
1500**
2000**
7
2185
H1
7935
1 64
1
445
3
25
152
AE
148
2780
1230
24
2
21
6
10
11
20
16
2
W6
(1) REMOVABLE PANEL FOR ACCESS TO THE COMPRESSOR COMPARTMENT
(2) ELECTRICAL PANEL
(3) MICROPROCESSOR KEYBOARD
(4) POWER INPUT
(5) HUMIDIFIER INLET CONNECTIONS
(6) CONDENSATE DISCHARGE
(7) FUNCTIONAL CLEARANCES
(10) RE-HEATING COIL (OPTIONAL)
(11) TREATMENT COIL
(13) ELECTRONIC AIR FILTERS / F7 BAG FILTERS (OPTIONAL)
(14) G4 AIR FILTERS
(15) OUTLET CENTRIFUGAL FAN
(16) MOTOR WITH SUPPLY TRANSMISSION
(17) LIFTING BRACKETS (REMOVABLE, IF REQUIRED, AFTER POSITIONING
THE UNIT)
(18) FRESH AIR SHUTTER
(20) ACCESS TO FANS/MOTORS AND TRANSMISSIONS
(21) ACCESS FOR INSPECTION OF COILS, FILTERS, HEATING ELEMENTS
(22) GAS MODULE (TO BE CONNECTED TO THE UNIT DURING INSTALLATION)
(23) DISCHARGE WASTE GAS (PROVIDED UN-ASSEMBLED)
(24) INTAKING AIR BURNER
(25) GAS BURNER COMPARTMENT
(26) GAS MODULE SUPPLY (1" GAS)
(27) CONDENSATE DISCHARGE GAS MODULE
R = AIR INTAKE FROM OUTSIDE
M=OUTLET AIR
AE = FRESH AIR INTAKE
H1 = WALL ON TWO SIDES MAX.
(*) VIBRATION MOUNTS POSITION
(**) SUGGESTED CLEARANCE
W4
W5
W7
W8
15
22
22
W9
W10
WEIGHT DISTRIBUTION
Size
W1
W2
W3
W4
W5
W6
Shipping weight
kg
kg
kg
kg
kg
kg
kg
804
904
802
766
765
782
753
805
4673
818
782
780
797
769
821
4768
BT08A006GB-03
CONSTRUCTIONAL CONFIGURATION: RECIRCULATED/OUTSIDE AIR MIXING BOX (B)
300kW
Size
W7
kg
214
W8
kg
203
W9
kg
317
W10
kg
346
Shipping weight
kg
1080
The presence of optional accessories may result in a substantial variation of the weights shown in the table.
57
PACKAGED
362 - 904
DIMENSIONAL DRAWING
SIZE 804 – 904 CONSTRUCTION VERSION C
DIMENSIONAL DRAWING(14)
8024
2
3
1868
1203
9
R
18
2
M
2272
148
730
ES
740
1
185
19
AE
828
8
5
M
R
4
3107
675 *
3093 *
614
2700
3093 *
198
17
1075 *
64
17
ES 1
64
2185
6
7935
1
2296
2000**
H1
8-9 6
7
W1
W2
1500**
AE
7
H1
W3
1500**
18
14 13
21
6
10
11 12
20
16
2
W6
W4
W5
BT08A006GB-03
15
WEIGHT DISTRIBUTION
CONSTRUCTIONAL CONFIGURATION: FREE COOLING VERSION WITH
EXTRACT/RECIRCULATED/FRESH AIR INTAKE BOX (C)
Size
W1
W2
W3
W4
W5
W6
Shipping weight
kg
kg
kg
kg
kg
kg
kg
804
904
804
793
791
834
807
806
4835
819
808
807
851
823
822
4930
(1) REMOVABLE PANEL FOR ACCESS TO THE COMPRESSOR
COMPARTMENT
(2) ELECTRICAL PANEL
(3) MICROPROCESSOR KEYBOARD
(4) POWER INPUT
(5) HUMIDIFIER INLET CONNECTIONS
(6) CONDENSATE DISCHARGE
(7) FUNCTIONAL CLEARANCES
(8) WATER INLET INTEGRATING COIL Ø 2"
(9) WATER OUTLET INTEGRATING COIL Ø 2"
(10) RE-HEATING COIL (OPTIONAL)
(11) TREATMENT COIL
(12) WATER HEATING COIL (OPTIONAL)
(13) ELECTRONIC AIR FILTERS / F7 BAG FILTERS (OPTIONAL)
(14) G4 AIR FILTERS
(15) SUPPLY AND RETURN CENTRIFUGAL FANS
(16) MOTORS WITH RETURN AND SUPPLY TRANSMISSION
(17) LIFTING BRACKETS (REMOVABLE, IF REQUIRED, AFTER
POSITIONING THE UNIT)
(18) FRESH AIR SHUTTER
(19) DISCHARGE DAMPER
(20) ACCESS TO FANS/MOTORS AND TRANSMISSIONS
(21) ACCESS FOR INSPECTION OF COILS, FILTERS, HEATING
ELEMENTS
R = AIR INTAKE FROM OUTSIDE
M=OUTLET AIR
AE = FRESH AIR INTAKE
ES = AIR EXPULSION
H1 = WALL ON TWO SIDES MAX.
(*) VIBRATION MOUNTS POSITION
(**) SUGGESTED CLEARANCE
The presence of optional accessories may result in a substantial variation of the weights shown in the table.
58
PACKAGED
362 - 904
DIMENSIONAL DRAWING
SIZE 804 – 904 CONSTRUCTION VERSION C GAS MODULE 150 kW - 200 kW
DIMENSIONAL DRAWING(15)
8024
2780
AE
5
3
18
2780
ES
1 52
19
1
M
2
2272
M
536
26
27
R
R
660
2
24 25
1015
23
4
64
64
2937
676 *
3092 *
3092
64
459
*
17
6
1
ES
1
2185
17
64
255 *
1235 *
2 55 *
148
17
46
1075 *
3976
7935
2000**
H1
6
7
W1
W2
1500**
14
AE
7
H1
W3
1500**
18
13
21
6
10
11
20
W6
W4
W5
15
W7
W8
22
W10
W9
WEIGHT DISTRIBUTION
CONSTRUCTIONAL CONFIGURATION: FREE COOLING VERSION WITH
EXTRACT/RECIRCULATED/FRESH AIR INTAKE BOX (C)
Size
W1
W2
W3
W4
W5
W6
Shipping weight
kg
kg
kg
kg
kg
kg
kg
804
904
804
793
791
834
807
806
4835
819
808
807
851
823
822
4930
(1) REMOVABLE PANEL FOR ACCESS TO THE COMPRESSOR
COMPARTMENT
(2) ELECTRICAL PANEL
(3) MICROPROCESSOR KEYBOARD
(4) POWER INPUT
(5) HUMIDIFIER INLET CONNECTIONS
(6) CONDENSATE DISCHARGE
(7) FUNCTIONAL CLEARANCES
(10) RE-HEATING COIL (OPTIONAL)
(11) TREATMENT COIL
(13) ELECTRONIC AIR FILTERS / F7 BAG FILTERS (OPTIONAL)
(14) G4 AIR FILTERS
(15) SUPPLY AND RETURN CENTRIFUGAL FANS
(16) MOTORS WITH RETURN AND SUPPLY TRANSMISSION
(17) LIFTING BRACKETS (REMOVABLE, IF REQUIRED, AFTER POSITIONING THE UNIT)
(18) FRESH AIR SHUTTER
(19) DISCHARGE DAMPER
(20) ACCESS TO FANS/MOTORS AND TRANSMISSIONS
(21) ACCESS FOR INSPECTION OF COILS, FILTERS, HEATING
ELEMENTS
(22) GAS MODULE (TO BE CONNECTED TO THE UNIT DURING
INSTALLATION)
(23) DISCHARGE WASTE GAS (PROVIDED UN-ASSEMBLED)
(24) INTAKING AIR BURNER
(25) GAS BURNER COMPARTMENT
(26) GAS MODULE SUPPLY (1" GAS)
(27) CONDENSATE DISCHARGE GAS MODULE
R = AIR INTAKE FROM OUTSIDE
M=OUTLET AIR
AE = FRESH AIR INTAKE
ES = AIR EXPULSION
H1 = WALL ON TWO SIDES MAX.
(*) VIBRATION MOUNTS POSITION
(**) SUGGESTED CLEARANCE
BT08A006GB-03
16
2
150-200kW
Size
W7
kg
111
W8
kg
107
W9
kg
173
W10
kg
189
Shipping weight
kg
580
The presence of optional accessories may result in a substantial variation of the weights shown in the table.
59
PACKAGED
362 - 904
DIMENSIONAL DRAWING
SIZE 804 – 904 CONSTRUCTION VERSION C GAS MODULE 300 kW
DIMENSIONAL DRAWING(16)
8024
5169
23
18
5
M
26
536
2780
ES
2272
19
1
2
M
25
27
R
R
17
64
64
4
64
459 6
2937
676 *
3092
*
3092
*
1075 *
6
W1
W2
AE
W3
7
64
17
255 *
2356 *
255 *
46
5097
H1
1500**
18
14 13
1500**
2000**
7
ES 1
2185
H1
7935
1
445
3
25
152
AE
148
2780
1230
24
2
21
6
10
11
20
16
2
W6
W4
W5
W7
W8
15
22
22
W9
W10
WEIGHT DISTRIBUTION
CONSTRUCTIONAL CONFIGURATION: FREE COOLING VERSION WITH
EXTRACT/RECIRCULATED/FRESH AIR INTAKE BOX (C)
BT08A006GB-03
Size
W1
W2
W3
W4
W5
W6
Shipping weight
kg
kg
kg
kg
kg
kg
kg
804
904
804
793
791
834
807
806
4835
819
808
807
851
823
822
4930
(1) REMOVABLE PANEL FOR ACCESS TO THE COMPRESSOR
COMPARTMENT
(2) ELECTRICAL PANEL
(3) MICROPROCESSOR KEYBOARD
(4) POWER INPUT
(5) HUMIDIFIER INLET CONNECTIONS
(6) CONDENSATE DISCHARGE
(7) FUNCTIONAL CLEARANCES
(10) RE-HEATING COIL (OPTIONAL)
(11) TREATMENT COIL
(13) ELECTRONIC AIR FILTERS / F7 BAG FILTERS (OPTIONAL)
(14) G4 AIR FILTERS
(15) SUPPLY AND RETURN CENTRIFUGAL FANS
(16) MOTORS WITH RETURN AND SUPPLY TRANSMISSION
(17) LIFTING BRACKETS (REMOVABLE, IF REQUIRED, AFTER
POSITIONING THE UNIT)
(18) FRESH AIR SHUTTER
(19) DISCHARGE DAMPER
(20) ACCESS TO FANS/MOTORS AND TRANSMISSIONS
(21) ACCESS FOR INSPECTION OF COILS, FILTERS, HEATING
ELEMENTS
(22) GAS MODULE (TO BE CONNECTED TO THE UNIT DURING
INSTALLATION)
(23) DISCHARGE WASTE GAS (PROVIDED UN-ASSEMBLED)
(24) INTAKING AIR BURNER
(25) GAS BURNER COMPARTMENT
(26) GAS MODULE SUPPLY (1" GAS)
(27) CONDENSATE DISCHARGE GAS MODULE
R = AIR INTAKE FROM OUTSIDE
M=OUTLET AIR
AE = FRESH AIR INTAKE
ES = AIR EXPULSION
H1 = WALL ON TWO SIDES MAX.
(*) VIBRATION MOUNTS POSITION
(**) SUGGESTED CLEARANCE
300kW
Size
W7
kg
214
W8
kg
203
W9
kg
317
W10
kg
346
Shipping weight
kg
1080
The presence of optional accessories may result in a substantial variation of the weights shown in the table.
60
PACKAGED
362 - 904
STANDARD UNIT SPECIFICATIONS
STRUCTURE
The basement is assembled with a painted galvanized steel frame. The internal
structure is made of “ALUZINK” bent galvanized steel . The alloy that protects
the Aluzink allow an excellent corrosion proofing thanks to the galvanic protection typical of the combination aluminium-zinc.
PANELLING
Panels of the compressor panel in steel sheet metal, painted using polyester
powders, colour RAL 9001 and covered on the inside with ashlared soundabsorbent material.
Sandwich panels in the air treatment section with dual walls in steel sheet metal
with polyurethane insulation (40 kg/m3), thickness of outer sheet metal 6/10 mm
galvanized and painted using polyester powders colour RAL 9001, polyurethane
thickness with thermal conductivity coefficient 0.022W/mK, thickness of internal
sheet metal 5/10 mm hot galvanized. The panel is also provided with a PVC
profile for thermal insulation and a EPDM rubber gasket that ensures the hermetic seal.
All panelling can easily be removed to allow complete accessibility to internal
components.
INTERNAL EXCHANGER
Direct expansion finned exchanger, made from copper pipes in staggered rows
and mechanically expanded to the fin collars. The fins are made from aluminium
with a corrugated surface and adequately distanced to ensure the maximum
heat exchange efficiency.
EXTERNAL EXCHANGER
Direct expansion finned exchanger, made from copper pipes in staggered rows
and mechanically expanded to the fin collars. The fins are made from aluminium
with a corrugated surface and adequately distanced to ensure the maximum
heat exchange efficiency.
Correct power supply to the expansion valve is ensured by the under-cooling
circuit. This circuit also prevents the formation of ice at the base of the heat
exchanger during winter operation.
FAN
INTERNAL SECTION
Centrifugal fan with double intake, blades curved forward to achieve maximum
performance and silence. Statically and dynamically balanced as per standards
ISO 1940 degree 6.3. Fastened to rubber anti-vibration devices. The screw,
rotor and frame are made of galvanized sheet metal (semdzimir) the shaft is
made of C40 steel. Connection to electric motor with belt and pulleys.
EXTERNAL SECTION
Helical fans with shaped aluminium blades, directly coupled to the three-phase
electric motor, with built-in thermal overload protection, minimum IP 54 construction. Mounted in aerodynamic housings to increase efficiency and minimise
noise levels, and fitted with safety grills.
REFRIGERANT CIRCUIT
The circuit is complete with:
- refrigerant charge
- sight glass with moisture indicator
- high pressure switch
- low pressure switch
- filter dryer
- electronic expansion valve
- non-return valve
- 4-way reverse cycle valve
- liquid receiver
- liquid separator
- high pressure safety valve
- low pressure safety valve
FILTRATION
Pleated filter for greater filtering surface, made up of galvanized plate frame with
galvanized and electric-welded protective mesh, and regenerable filtering media
made from polyester fibre sized with synthetic resins. G4 efficiency according to
CEN-EN 779 standard (Eurovent class EU4/5 - average efficiency 90.1% ASHRAE 52-76 Atm). Self-extinguishing (resistance to fire class 1 - DIN 53438).
ELECTRICAL PANEL
The electrical panel is situated inside the units and is accessed through a hinged door that is opened by a special key
The Power Section includes:
- main door lock isolator switch
- compressor circuit breaker
- compressor power supply remote control switch
- fan motor thermal protections of internal section and external section
- circuit breaker to protect auxiliary circuit
Microprocessor control section:
- treated air temperature control
- compressor overload
- centralised alarms with remote signalling
- self-diagnosis system with immediate display of the error code
- demand limit
- clean contacts for remote ON-OFF, cumulative alarm, fan status, compressor
status, summer/winter mode
- control keypad, including:
display of the parameter index
display of the set values and the error codes
menu button to display the parameter index
ALARM button to access the alarm management functions
status button to display the status list
unit operation or ventilation only selection button
On/Off and manual reset button for overload device activation
UP and DOWN buttons to increase and decrease the values
Selected function signal LED
Compressor timer / operation signal LED
RETURN FAN (Constructional configuration C)
Centrifugal fan with double intake, blades curved forward to achieve maximum
performance and silence. Statically and dynamically balanced as per standards
ISO 1940 degree 6.3. Fastened to rubber anti-vibration devices. The screw,
rotor and frame are made of galvanized sheet metal (semdzimir) the shaft is
made of C40 steel. Connection to electric motor with belt and pulleys.
TEST
Unit manufactured according to the ISO 9001 quality standards and subject to
functional testing at the end of the production line
ACCESSORIES
- copper / copper evaporator coils
- copper / copper condenser coils
- water heating coil
- modulating three-way valve
- hot gas re-heating coil
- Copper / copper hot gas re-heating coil
- electrode boiler steam humidifier
- water to waste evaporating wet-deck humidifier
- Heating module with modulating condensing gas burner
- Electric heaters.
- Air quality sensor for CO2 p.p.m. control
- Air quality sensor for CO2 and VOC p.p.m. control
- bag filters section F7 class
- High efficiency electrostatic filters additional section
- differential pressure switch for dirty air filters
- free-cooling with temperature comparison only
(standard for version C)
- free-cooling with independent comparison of temperature and absolute humidity
- Variable fan speed control for operation at low ambient temperature
ECOBreeze
- fan breakaway starting current reducing device.
standard for sizes 362-402-452; optional for sizes from 464 to 904
- Application with fabric ducts (only for C version)
- high and low pressure gauges
- phase monitor
- power factor correction capacitors (cosfi > 0.9)
- serial port RS485 with MODBUS protocol
- serial port RS485 with LONWORKS protocol
- Remote control with remote microprocessor control (separately supplied accessories)
BT08A006GB-03
COMPRESSOR
Scroll compressor complete with: overload thermal protection, high refrigerant
discharge temperature, rubber antivibration mounts, oil charge.
A oil heater is automatically switched on at the compressor shut-down to prevent oil dilution by the refrigerant.
The compressors are connected in tandem on a single refrigerator circuit. They
have bi-phase equalization of the oil and are equipped with cut-off bibcocks
TRAY
Condensation collection basin in aluminium alloy 1050 H24 with anticondensation insulation, welded and equipped with siphoned drain tube
61
PACKAGED
362 - 904
CLIVET SPA
Feltre (BL) ITALY
Tel. + 39 0439 3131
Fax + 39 0439 313300
[email protected]
CLIVET UK LTD
Fareham (Hampshire) U.K.
Tel. + 44 (0) 1489 572238
Fax + 44 (0) 1489 573033
[email protected]
CLIVET SAS
Verrierès le Buisson - FRANCE
Tel. + 33 (0)1 69 20 25 75
Fax + 33 (0)1 69 20 60 76
[email protected]
CLIVET ESPAÑA S.A.
Madrid - SPAIN
Tel. + 34 91 6658280
Fax + 34 91 6657806
[email protected]
CLIVET GmbH
Norderstedt - GERMANY
Tel. +49 (0) 40 32 59 57-0
Fax +49 (0) 40 32 59 57-194
[email protected]
CLIVET NEDERLAND B.V.
Amersfoort - Netherlands
Tel. + 31 (0) 33 7503420
Fax + 31 (0) 33 7503424
[email protected]
CLIVET RUSSIA
Moscow - RUSSIA
Tel. +74956462009
Fax +74956462009
[email protected]
CLIVET MIDEAST FZC
Dubai - UAE
Tel. +97 14 3518501
Fax +97 14 3518502
[email protected]
CLIVET TF AIR SYSTEMS (P) LTD.
Malur - INDIA
Tel. +91 8151 232683/5
Fax +91-8151-232684
[email protected]
The data contained in this bulletin is not binding and may be changed by the manufacturer without prior notice. All reproduction, even partial, is prohibited.
© Copyright - CLIVET S.p.A. - Feltre (BL) - Italy