Products that perform…By people who care
Transcription
Products that perform…By people who care
Products that perform…By people who care ENGINEERING BULLETIN… FEB 2015 (Vol 1) Equipment : Magnetic Bearing Chiller Model : PROmetheus (DCLC-M) Description : New Product Development Dunham-Bush is developing the new series of energy efficient chiller using the oil free magnetic bearing technology, the PROmetheus series. The PROmetheus series is part of Dunham Bush successful R&D and continuous effort to develop and manufacture product of high efficiency and reliability. Some of the PROmetheus product series features are:- State of-the-art compressor technology Oil free with magnetic bearing High efficiency with superior IPLV Super quiet with low vibration HFC-134a refrigerant Easy maintenance The prototype unit has been supplied to a project in Miami USA. The unit has replaced an existing water cooled screw chiller as part of an upgrading and energy efficiency exercise. It has been running successfully since Aug 2014 with superior energy efficiency, low noise with less maintenance. The PROmetheus series is expected to be officially launch soon with capacity ranges from 120-600RT. ENGINEERING BULLETIN… FEB 2015 (Vol 1) Equipment : Inverter Rooftop Unit Model : Falcon (ACPSE-P) Description : New Product Development Dunham-Bush is also developing the new energy efficient rooftop series with inverter scroll technology.The new Falcon series is also part of Dunham-Bush continuous effort to develop and manufacture product of high efficiency and reliability. Some of the new Falcon product series features are:- Inverter scroll compressor technology High efficiency with superior IPLV Super quiet with low vibration HFC-410a refrigerant Energy saving features Dunham-Bush engineering and R&D team is developing the prototype unit to be display in an exhibition in June 2015. The new Falcon series will put Dunham-Bush ahead of the competitors with product of energy saving, high efficiency and reliability. The product is expected to be officially launch by this year. FEB 2015 (Vol 1) ENGINEERING BULLETIN… Equipment : Selection Software Model : SPEC Description : New Version of Selection Software As part of Dunham-Bush continuous improvement, we have released the new generation of SPEC selection software with new features and enhancements. In this new generation, the SPEC selection software is split into different versions, with each version assigned for dedicated product line. This will improve the updates and enhancements of each product lines as well as making it user friendly. The list of SPEC selection software version is listed below:SPEC VERSION SPEC SPEC – CINDY SPEC – ASHLEY SPEC – PHOEBE PRODUCT LINE Water Cooled Chiller Air Cooled Chiller Centrifugal Chiller AHU Packaged STATUS Active Active Active Next Release ENGINEERING BULLETIN… FEB 2015 (Vol 1) Equipment : Product Catalogue Model : RepNet Description : Online Catalogue from Website Did you know that as a SPEC user you are able to download the latest catalogue online from the Dunham-Bush website via the RepNet portal. All you need is your SPEC username and password. The RepNet portal is not only limited to catalogue but also other product literature such as IOM and brochures. All you need is to follow the following steps to retrieve your latest catalogue:- Step 1 – Click on RepNet tab on Dunham-Bush Website Step 2 – Enter your SPEC username & password ENGINEERING BULLETIN… Equipment : Product Catalogue Model : RepNet Description : Online Catalogue from Website Step 3 – Select your product category Step 4 – Select your product model FEB 2015 (Vol 1) ENGINEERING BULLETIN… Equipment : Product Catalogue Model : RepNet Description : Online Catalogue from Website Step 5 – Download your catalogue Step 6 – Download complete FEB 2015 (Vol 1) FEB 2015 (Vol 1) APPLICATION BULLETIN… Equipment : Air Cooled Split Unit Model : ACCS / EB Description : Refrigerant Piping Length & Elevation Continuous research and development (R&D) on Dunham-Bush air cooled split unit has resulted in the improvement of the maximum allowable equivalent length and elevation for the ACCS/EB Series for 50/60hz with R22/R407C refrigerant, as indicated in the table 2 below. This shall supersedes the table in page 13, IOM# MM0305F/MM0307A with immediate effect. The new revised IOM may be downloaded through the RepNet portal. Table 1: Old Piping Length & Elevation Max. Allowable Piping Model Length (L) ACCS 68-1520 75 ft [22.9m] Elevation Difference Between Two Units 30 ft [9.2 m] Table 2: New Piping Length & Elevation Max. Allowable Piping Model Length (L) ACCS 68-570 125 ft [38.1m] ACCS 640-1520 100 ft [30.5m] Elevation Difference Between Two Units 65 ft [19.8 m] 55 ft [16.8 m] FEB 2015 (Vol 1) APPLICATION BULLETIN… Equipment : Air Handling Unit Model : CS3 Description : Thermal Break Application Thermal Break feature consists of casing construction with frames of extruded aluminium profiles joined by nylon corner pieces, and sandwich panel with PVC strip in between inner and outer layer. The unit construction with no direct metal to-metal contact between paneling and framework thus minimizing cabinet condensate. Thermal break featured AHU prevents the unit external condensation that causes AHU to 'sweat' or condensate easily. One may ask with the application of thermal break featured AHU, does it mean that the AHU is no longer 'sweating‘ at all, no matter whether it is located outdoor or indoor with warm or even cold ambient air? The answer is… NO…! It does not mean that the AHU is no longer 'sweat’ or condensate when thermal break construction is applied. It depends on some parameters such as the ambient air temperature (T-amb) of the AHU room and the AHU internal cold air temperature (T-in) after cooling coil. Although thermal break construction can reduce the effect of condensation as compare to conventional construction. T-amb T-in T-in = Off coil temperature T-amb = Outside AHU temperature APPLICATION BULLETIN… FEB 2015 (Vol 1) Equipment : Air Handling Unit Model : CS3 Description : Thermal Break Application Cabinet external condensation curves for the Conventional Steel/Aluminium is shown on the Psychometric Chart below. 3 curves are plotted to represent the internal cold temperatures, which is normally the off-cooling coil temperature i.e. 490F, 550F and 600F. Any ambient air condition (where AHU is located) above the curve, condensation occurs on external cabinet. On the contrary, it the ambient air condition below the curve, condensation will not form on the AHU external cabinet. Chart 1: Conventional Casing APPLICATION BULLETIN… FEB 2015 (Vol 1) Equipment : Air Handling Unit Model : CS3 Description : Thermal Break Application Thermal break casing are able to improve the cabinet external condensation curves as shown on the Psychometric Chart below. These will reduce the condensation effect on some applications. However, it may not prevent condensation in some critical applications. Therefore, a study of the parameters (T-in, T-amb) plotted on the Psychometric Chart shall be take into consideration to ensure no condensation will occurs especially on critical applications. Some of the examples of critical applications are:1) 2) Ducted Return Air Application High Percentage Fresh Air Application Chart 2: Thermal Break Casing FEB 2015 (Vol 1) DUNHAM-BUSH WORLWIDE… United Kingdom China Vietnam Malaysia Singapore Dubai Thailand Indonesia South Africa Malaysia China Lot 5755-6, Kidamai Industrial Park, Bukit Angkat 43000, Kajang Selangor Darul Ehsan Tel: +603-89249000 Fax: +603-87395020 No 1 Dunham-Bush Rd Laishan District, Yantai, Shandong Province, China 264003 Tel: +86-535-6588999 Fax: +86-535-6581999 United Kingdom No 8, Downley Road, Havant, Hampshire, England PO9 2JD Tel: +44-2392477700 Fax: +44-2392450396 South Africa Singapore Indonesia 57, Sovereign Drive Route 21 Corporate Park Irene, Pretoria South Africa Tel: +27-123454202 Fax: +27-123454203 2 Kallang Pudding Road, #07-07, Mactech Building Singapore 349307 Tel: +65-68422012 Fax: +65-68422013 The Vida Building 7th Floor Jl. Raya Pejuangan No. 8 Kebon Jeruk Jakarta 11530, Indonesia Tel: +62-2129778100 Fax: +62-2129778001 Thailand Vietnam 10th Floor, Nam A Bank Tower, 201-203 Cach Mang Thang 8 Street, District 3, Ho Chi Minh City, Vietnam Tel: +84-862903108 Fax: +84-862903109 27th 1, Qhouse Lumpini, Floor, south Sathorn Road, Tungmahamek, Sathorn, Bangkok, Thailand 10120 Tel: +66-026103749 Fax: +66-026103601 UAE Office # 2606, Fortune Executive Towers, Cluster T1, Jumeirah Lake Tower Dubai,UAE Tel: +971- 44439207 Fax: +971-44439208