Central power supply system CPS 220 / CPS 220 SKÜ / CPS 220
Transcription
Central power supply system CPS 220 / CPS 220 SKÜ / CPS 220
Installation and maintenance manual Central power supply system CPS 220 / CPS 220 SKÜ / CPS 220 SV / CPS J-SV Installation and maintenance manual for central power supply system CPS 220 Content: page 1. General information 2 2. Safety advice 2 3. Battery notes 2 4. Type-references of CPS 220 main-stations and CPUS 220 sub-stations 3 5. Mechanical design of CPS 220 main-stations and CPUS 220 sub-stations 4 6. Technical data 4 7. Installation example 5 8. Mounting the CPS 220 6 9. Mounting of the batteries 6 10. Electrical connection of the system 10 11. Turning on the central battery system 11 12. Internal units 12.1 BUS-interface module - BIF 12.2 Relay interface - RIF 5 12.3 Light switch monitor - LSA 8.1 12.4 Staircase light switch connection - TLS 12.5 Channel staircase light switch connection - TLS 5 12.6 Event printer - optional function 12.7 Disk drive - optional function 12.8 Circuit modules 12.9 CPS 220 / SV / ... with Joker Technology 12.10 Isolation supervision and tests 12 13 15 18 20 21 22 24 31 34 13. External units 13.1 3-phase-monitor - DPÜ 13.2 Remote display tableau - MTB 13.3 Phase selection connector - PAS 13.4 Modules and sub-stations with BUS-Connection 35 36 37 38 14. CPS unit programming 14.1 General information 14.2 Test menu 14.3 System programming 14.4 CPS unit programming 14.5 Info menu 45 46 47 48 49 15. Control module with controller function 15.1 General information 15.2 Controller connection 15.3 Programming the Sub-station addresses 15.4 Programming the controller 15.5 Update timers for all connected stations 15.6 Automatic ISO supervision with failure display 52 52 52 53 53 53 16. Further modules for CPS 220-Systems 16.1 Continous light circuit modules – DSM/L- DSM-U 54 17. Fan monitoring in the optional "Priorit" fire protection cabinet 56 18. Recurring examinations 57 19. Appendix: Copyforms for system documentations 57 708 001 C 1 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 1. General information After unpacking the housings (battery and electronics housings) kindly check for complete delivery and whether there are any visible external damages. Furthermore, inform the forwarding agents at once about visible damages, as we do not accept complaints that reach us at a later time. ! Before starting the system take into consideration all references in the installation and maintainance manual! All guarantee claims cease in case of wrong installation or of any intervention on the products! Only original fuses are allowed to be used. The fuses on the outgoing side have are: Order no. 5 A - 080 005 Order no. 10 A - 080 006 In general original spare part must be used. Only printers of protection class II can be connected to the Centronics Interface of the control unit. ! A function test has to be initiated after each repair work on connected luminaires, in order to delete the failure messages displayed on the control module. (see 14.2.1) 2. Safety advice The manual contains information for trained and qualified electricians. The system has to be operated within the design parameters and only in functional, undamaged condition. ! National safety standards and legal requirements have to be observed. Fuses in the system have to be shifted only when the central is in a "blocked" mode. (see 14.4.4) The system has to be disconnected from the battery first and next from mains supply prior to any work being carried out on the luminaires or other system components! (see 11) 3. Battery notes The delivered batteries can be stored for max. 3 months without being charged! Prior to any test carried out the batteries must be charged for at least 24 hours. ! Old batteries have to be disposed as per national requirements. 708 001 C 2 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 4. CPS 220 central and CPUS 220 sub-central models CPS 220 / ... / ... 0 without circuit modules with max. 8 circuit modules types 2x3A or 1x6A (max 16 circuits) with max. 16 circuit modules types 2x3A or 1x6A (max 32 circuits) with max. 24 circuit modules types 2x3A or 1x6A (max 48 circuits) 16 32 48 SKÜ with circuit monitoring with individual lamp monitoring SV of each luminaire CPU ... 220 / ... / ... / Option F 30 (up to CPUS 220/.../32 in F 30 housing) 6 16 32 48 SKÜ SV S SB M MB CPUSB 220/ ... /6/F30 708 001 C with max. 3 circuit modules types 2x3A or 1x6A with max. 8 circuit modules types 2x3A or 1x6A (max 16 circuits) with max. 16 circuit modules types 2x3A or 1x6A (max 32 circuits) with max. 24 circuit modules types 2x3A or 1x6A (max 48 circuits) with circuit monitoring with individual lamp monitoring of each luminaire in sheet steel housing In sheet steel housing complete of 6 BUSfitted circuits (only together with SKÜ or SV systems) Backplate assembly unit (without housing) BUS-fitted backplat assembly unit complete with 6 circuits (only together with SKÜ or SV systems) recessed wall mounting panel F 30 (fire proof) (only together with SKÜ or SV systems) 3 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 5. Mechanical design of CPS 220 panels and CPUS 220 sub-stations 5.1. Rack with control module Operation BAT. operation Failure CPS 220/SV ISO INOTEC + CPS 220 01.07.95 12:00 OPERATION U BATT: 220V TEST I BATT +15.0A Charge failure Funktionstest g gggagbJSXHLXH BSKLHSX ÖHX ÖJ ÄJSK 'K 'K OS* KNL ÖJÖLJXL ÖÄJ ASX ÖÄAK ÖL A NHLXJKNLXKMJ ÄXMJJKL ÖÄLM XNHÖ XNJKXJ ÄJÖ AJK ÖLK ÖKL Ö - Printer CENTRONICS KEYBOARD UH 5AT 5.2. Rack (max. 3) for circuit modules SU6SKÜ SU/SKÜ 2x3A NetzSi 5AT SU6SKÜ SU/SKÜ 2x3A SU6SKÜ SU/SKÜ 2x3A SU6SKÜ SU/SKÜ 2x3A SU6SKÜ SU/SKÜ 2x3A SU6SKÜ SU/SKÜ 2x3A SU6SKÜ SU/SKÜ 2x3A SU6SKÜ SU/SKÜ 2x3A Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Batterie Ein Ein Ein Ein Ein Ein Ein Ein Störung Störung Störung Störung Störung Störung Störung Störung 10AT Si 5AT 10AT Si 5AT 10AT Si 5AT 10AT Si 5AT 10AT Si 5AT 10AT Si 5AT 10AT Si 5AT 10AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Ein Si 10AT Störung Ein Si 10AT Störung Ein Si 10AT Störung Ein Si 10AT Störung Ein Si 10AT Störung Ein Si 10AT Störung Ein Si 10AT Störung Ein Si 10AT Störung Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT 10AT Ladeteil 220V / 7,5A Ein INOTEC 5.3. Charger 3,0 A or 7,5 A (only with CPS 220 central) SU6SKÜ SU/SKÜ 2x3A Si 5A T Mains SU6SKÜ SU/SKÜ 2x3A Si 5A T SU6SKÜ SU/SKÜ 2x3A Si 5A T SU6SKÜ SU/SKÜ 2x3A SU6SKÜ SU/SKÜ 2x3A Si 5A T SU6SKÜ SU/SKÜ 2x3A Si 5A T Si 5A T SU6SKÜ SU/SKÜ 2x3A Si 5A T SU6SKÜ SU/SKÜ 2x3A Si 5A T Ba ttery Ein Ein Ein Ein Ein Ein Ein Ein Stör ung Stör ung Stör ung Stör ung Stör ung Stör ung Stör ung Stör ung 10AT T Si 5A 10AT T Si 5A 10AT T Si 5A 10AT T Si 5A 10AT T Si 5A 10AT T Si 5A 10AT T Si 5A 10AT T Si 5A Si 5A T Si 5A T Si 5A T Si 5A T Si 5A T Si 5A T Si 5A T Si 5A T Ein Si 10A T Stör ung Ein Si 10A T Stör ung Ein Si 10A T Stör ung Ein Si 10A T Stör ung Ein Si 10A T Stör ung Ein Si 10A T Stör ung Si 5A T Si 5A T Si 5A T Si 5A T Si 5A T Si 5A T 10AT Ein Si 10A T Stör ung Ein Si 10A/T 7,5A Charger 220V Si 5A T Stör ung Si 5A T ON INOTEC 6. Technical data Connection voltage: Protection class: Protection category: Temperature Range: 1 ~ N/PE, 230 V, 50/60 Hz 3 ~ N/PE, 230 V, 50/60 Hz I Battery housing: IP 20 Electronics housing: IP 54 * -5°C to +35°C Total connectable load and maximum battery discharge current acc. to type label information. *Protection category IP 54 for the electronics compartement is only achieved after replacing the rubber cable inlets against standard cable glands. 708 001 C 4 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 7. Installation example 708 001 C 5 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 8. Mounting of CPS system The electronics and battery housings are to be set on top of each other at the installation site and they are to be connected to each other with the enclosed M8 screws. After mounting is complete, the system has to be fixed to the wall. It is necessary to leave a clearing between the housing and the wall for the sake of ventilation. Three glands (with battery sets connected in parallel five) have to be mounted for battery cables and temperature measuring sensor (if delivered) between the electronics and the battery compartment. If the rd temperature measuring sensor is not included, the 3 hole has to be covered with a blind plug (enclosed in the package). 9. Mounting of the batteries Please check that the delivered batteries, pole connectors and battery cables are complete, and whether there are any mechanic damages. Remove the battery fuses F1 and F2 before connecting the batteries. Put the batteries into place according to the below shown figure. Connect the pole connectors. Safety caps are to be put on the poles. More information regarding maintenance and care of the maintenance free batteries can be found on the enclosed battery instruction sheet. The maintenance recommendations for batteries are an important part of the operation manual and have to be taken care of. Safety regulations regarding high dc-voltages must also be taken into consideration. The fuses F1 and F2 must be inserted only after the installation of the whole CPS system is complete. (see 11) Removing cover plate if required. 708 001 C 6 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 Battery size 17,6Ah, 25,8Ah, 32Ah, 44Ah, 52Ah , 70Ah and 73Ah Battery size 79 Ah, 89 Ah, 99 Ah and 120 Ah 708 001 C 7 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 Battery size 104Ah and 140Ah Battery size 149Ah 708 001 C 8 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 Battery size 199Ah 708 001 C 9 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 10. Electrical connection of the system 10.1. a) b) 10.2. Connection to mains X1 1-Phase Connect mains to the terminals PE, N, L - terminal section -X1 3 -Phases Connect mains to the terminals PE, N, L1, L2, L3 - terminal section -X1, (3-phases-monitor is built-in and preconnected to terminals SL+/SL-). Additional terminals are provided if substations are to be connected. 24V-circuit - terminal section X2 The terminals SL+ and SL- are wire linked. If external 3-phase monitoring modules (DPÜ) are connected, the link has to be removed and the monitoring circuits are to be connected to the terminals SL+ and SL-. 10.3. External supervision: Data Bus - terminal section X2 External monitoring units are to be connected to the terminals R, T, G. 10.4. Other units - terminal section - X2 The units RIF 5, LSA 8.1, BIF and DPÜ are all connected at terminal section X2. A (optional) built-in SV-central (master control unit) has a wire-link between volt-free contact and terminals 1 and 2. If an external supervising unit (MTB) is installed, this can be conncected to the volt free contacts on the module RIF 5 (see 13.2) 10.5. Circuits to emergency luminaires - terminal section X3-X5 The circuits are to be connected to the terminals L, N, PE, on terminals in sections X3-X5: X3 PE, N-, L+ 1.1 - - - PE, N-, L+ 8.2 X4 PE, N-, L+ 9.1 - - - PE, N-, L+ 16.2 X5 PE, N-, L+ 17.1 - - - PE, N-, L+ 24.2 10.6. Battery connection - terminal section X6 The battery cables have to be connected to the fuses F1(+) and F2(-) on. Battery sets connected in parallel have to be connected to + and – on terminal section X0. No fuses are installed in CPUS subs. The terminals U+/U- terminal section X6 are installed when subcentrales are to be connected. X1 X2 X3 X4 X5 X6 F1F2 + - 8 7 9 0 1 6 5 4 2 3 X 708 001 C 10 0 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 10.7. Terminal operation N-isolation terminal open Do not open under load condition! Screew driver type 01 1. Push to open 2. Insert wire 3. Remove screw driver 11. Turn on the central battery system The following checks have to be carried out prior to switching mains supply on and the battery fuses are inserted: - isolation test of final end circuits according to the regulations - check the BUS and data cables for correct poling - check the connection of external units according to this manual - check the connection of the 24V-circuit (SL+/SL-) - check the pole connection of the battery assembly: 1. of every single battery, and 2. of the whole battery set (fuses F1 and F2) Powering-up the system - follow these steps: 1. Switch on power supply (turn on charger) 2. Insert the battery fuses Note: The fuses in the system are to be replaced only when the system is in blocked mode! (see 14.4.4) 708 001 C 11 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 12. Internal units 12.1. BUS-interface module - BIF The BUS interface (BIF) is the connecting point between the system (CPS) and the external BUS fitted units as, for example, LSA 8.1, RIF 5, DPÜ-B, MTB-B, MTB-D and BUS-sub-stations for CPS 220. The BIF module shields the system from external influences on the BUS cable. Connection The BUS cables are connected via the +24V, ⊥, +BUS terminals. The maximum length of the cables to the external modules is 1500m for 1,5 mm². Similarly, attention has to be paid to the connection of the BUS cables to the different units, i.e polaritychanges within the bus-line are not allowed. How to address the BUS-fitted units The relative address has to be set as follows at the unit's address switch: LSA 8.1 - max. 3 pcs. for RIF 5 for MTB for DPÜ Addr. 1, 2, 3 Addr. 7 Addr. 7 Addr. 1 - 31 (see 12.3) (see 12.2) (see 13.4.3) (see 13.4.2) Data line connection %,) ,127(& H[WHUQ 990 013 Internal wiring 708 001 C 12 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 12.2. Relay-interface - RIF 5 The unit carries the following function possibilities: - Remote switching gear (i.e. key switch) that can be programmed for: - maintained and non maintained emergency light on / off or - maintained emergency light on / off - Volt-free contacts for - operation - battery operation - failure - Battery sensor for temperature-controlled charging Messages: - Contact 1 and 2 open - Contact 2/4 closed - Contact 5/6 closed ¼ Sum-failure ¼ Operation ¼ Battery operation potentialfreie Kontakte 24V/1A (DC) 230V/0,5A (AC) Volt free contacts Fernschalter Remote switch 24V DC max. 100mA The RIF 5 module is factory-set with address 7. If the module is installed at a later time, address 7 has to be set. Temperaturfühler Temp. sensor Adresse 7 einstellen set address 7 Interne Verdrahtung, Firmenseitig internal wiring, factory set Relay contacts System status 708 001 C Operation Sum-failure Battery operation Failure 1-2 closed open closed Operation 3-4 closed open open Battery operation 5-6 open open closed 13 The remaining contacts are currently still without function ! INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 12.2.1. How to program the relay interface RIF 5 The RIF 5 module can be programmed at the control unit as follows: Push menu key Push system prog. key Push prog. control panel key push next key to continue until display shows: RIF/MTB-module is connected / not connected push change to choose connected push next key to continue until display shows: func. of remote switch push change key to choose EL+Main. are blocked or maintain is blocked push next key to continue in order to go back to the main menu 12.2.2. Passive RIF 5 To the simple duplication of the volt-free contacts of the RIF 5 further RIF 5 modules (passive RIF) can be connected to the controller. At all additional RIF 5 address 0 has to be set. At the passive RIF 5 only the function of the volt-free contacts is given. All other connection options are without function. It may be set to address 7 to a maximum of 1 RIF 5. 708 001 C 14 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 12.3. Light switch function - LSA 8.1 In order to be able to turn emergency- and standard mains luminaires ON and OFF via the same light switch the LSA 8.1 module can be used. Each of the 8 galvanically seperated channels can be used to monitor one light switch. If a switch is actuated any number of change-over device (SU/SV/SKÜ circuit modules) will be activated. The change-over devices are linked by software (programmed on the systems control unit). It is possible to assign two different channels to each circuit module. 12.3.1. How to program the LSA 8.1 The LSA 8.1 module can be programmed at the control unit as follows: Push menu key Push system prog. key Push prog. control panel key The system asks for number of LSA 8 modules push change key to choose between LSA 8 modules, … none, 1,2 or 3 … push next key LSA 8 /1 with / with out sub-circuit info push change key for selecting LSA 8/1 with or without sub-circuit info LSA 8/1 with display info on failed sub-dbs (Option for selective switching on – only with LSA 8/INV) Push change key with/none until display shows with Push next key in order to go back to the main menu Under paragraph 12.8.1.2 you can read how to program the change-over modules for LSA 8.1. If the LSA 8.1 modules are installed at a later time, the BUS cable has to be connected and the modules have to be set to the addresses 1 - 3. 12.3.2. Connection examples LSA 8.1 PE N L PE N L Netzleuchten General lighting PE N L Netzleuchten General lighting PE N L Netzleuchten General lighting Netzleuchten General lighting Interne Verdrahtung Internal wiring Note: Emergency luminaires connected to a CPS-system are supplied with mains via the change-over devices. 708 001 C 15 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 LSA 8.1 24V T T T T +24V +24V +24V +24V 9² 9² 9² 9² 9² 9² 9² 9² 9² 9² 9² 9² 9² 9² 9² 9² Interne Verdrahtung Internal wiring LSA 8.1 inverted L1 N PE UV 1 L1 L2 L3 N PE UV 2 Allgemeinbeleuchtung General lighting U< Allgemeinbeleuchtung General lighting 708 001 C 16 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 LSA 8.1 24V inverted UV 1 L3 L2 UV 2 L1 N L3 L2 L1 L1 N L1 DPÜ DPÜ gem. VDE 0108 gem. VDE 0108 L2 L3 ,127(& 12 14 L2 L3 ,127(& 12 14 11 11 9² 9² 9² 9² 9² 9² 9² 9² 708 001 C 17 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 12.4. Staircase light switch connection – TLS Both standard interior and emergency lighting luminaires can be controlled via the TLS. An integrated timer allows to activate the lights for any time between 1 - 15 min. An internal converter in the TLS module supplies the glow lamps in the lighting push-buttons with power. Max. 25 illuminated push-buttons, each with 0,8 mA glow lamps or 13 push-buttons with 1,5 mA glow lamps can be connected to T+ and T-. The length of the cable to the push-buttons is max 500m. For the power supply of the mains luminaires each TLS-module has a volt-free contact (terminals 29 and 30) with a maximum switching load of 5A at 230V. The emergency lighting luminaires are supplied via the change-over devices of the CPS system. further Mains luminaires further Push buttons TLS Ba ttery Si 3,15A T Maintained light On Push button PE N L All luminaires that are connected to the TLS can be programmed as maintained emergency light with the switch "maintained emergency light". 708 001 C 18 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 12.4.1. How to program the TLS module The TLS can be programmed at the control unit as follows: Push Menu key Push System Prog. key Push prog. control panel key push next key to continue until display shows TLS connection Push change key to choose between No TLS connected / 5-channel TLS / 1-channel TLS choose 1-channel TLS Push next key until display shows Number of 1-channel TLS Push change key to choose between none / 1 / 2 / 3 Push next key until display shows: TLS 1- time: 3 minutes Push change key to set time to 1 - 15 minutes Push next key until display shows TLS 2- time: Set TLS 2 as described above Push next key until display shows TLS 3- time: Set TLS 3 as described above Push next key in order to go back to the main menu For programming of change-over devices to TLS modules see paragraph 12.8.1.3. 708 001 C 19 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 12.5. 5 channel staircase light switch connection - TLS 5 Both standard interior and emergency lighting luminaires can be controlled via the TLS. An integrated timer allows to activate the lights for any time between 1 - 15 min. Each of the 5 individual channels have terminals for the cables to the push-buttons and for the corresponding volt -free contacts. An internal converter in the TLS module supplies the glow lamps in the lighting pus-buttons with power. Max. 20 illuminated push-buttons, each with 0,8 mA glow lamps or 10 push-buttons with 1,5 mA glow lamps can be connected to ( 1/1 ....5/5 ). The length of the cable to the push-buttons is max 500m. For the power supply of the mains luminaires each TLS-module has a volt-free contact with a maximum switching load of 3A at 230V. The emergency lighting luminaries are supplied via the change-over devices of the CPS system. Channel 1 Channel 2 Channel 3 Channel 4 Channel 5 Push button 5 Push button 4 Push button 3 Push button 2 Taster 5 5 4 4 3 3 2 2 1 1 Relais Push button 1 5 5 4 4 3 3 2 2 1 1 Si 40mAT R el 5 R el 4 INOTEC TLS 5 990 022 R el 3 R el 2 R el 1 Logic Si Si 40mAT T5 40mAT T4 + + 24V 24V Si Si 40mAT T3 40mAT T2 + + B US B US BUS-connection T1 UBa tt - + 220V Battery 220V 12.5.1. How to program the TLS 5 module The TLS 5 can be programmed at the control unit as follows: Push menu key Push system prog. key Push prog. control panel key push next key until display shows TLS connection push change key to choose between No TLS connected / 5-channel TLS / 1-channel TLS choose 5-channel TLS push next key until display shows 5-channel TLS - time: 3 minutes push change key to set time to 1 - 15 minutes push next key in order to go back to the main menu For programming TLS modules settings see paragraph 12.8.1.4. 708 001 C 20 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 12.6. Event printer – optional function Operation BAT. operation Failure Funktionstest gg gggagbJSXHLXH gggagbJSXHLXH Funktionstest BSKLHSX ÖHX ÖJÄJSK 'K 'K OS* BSKLHSX ÖHX ÖJ ÄJSK 'K 'K OS* KNL ÖJÖLJXL ÖÄJ ASX ÖÄAK ÖL A KNL ÖJÖLJXL ÖÄJ ASX ÖÄAK ÖL A NHLXJKNLXKMJ ÄXMJJKL ÖÄLM NHLXJKNLXKMJ ÄXMJJKL ÖÄLM XNHÖ XNJKXJ ÄJÖ AJK ÖLK ÖKL Ö XNHÖ XNJKXJ ÄJÖ AJK ÖLK ÖKL Ö CPS 220/SV ISO INOTEC + CPS 220 01.07.95 12:00 OPERATION U BATT: 220V TEST I BATT +15.0A Charge failure Printer CENTRONICS KEYBOARD UH 5AT The printer is installed at the factory and lists all data that is registered in the log with exact date and time. 12.6.1. How to program the printer The printer can be controlled as follows at the control unit: 708 001 C Push menu key Push system prog. key Push prog. control panel key push next key until display shows built in printer push change key to choose Yes / No choose Yes push next key in order to go back to the main menu 21 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 12.7. Disk drive – optional function Operation BAT. operation Failure CPS 220/SV ISO INOTEC + CPS 220 01.07.95 12:00 OPERATION U BATT: 220V TEST I BATT +15.0A Charge failure - Printer CENTRONICS KEYBOARD UH 5AT The disk drive is factory installed. All events are registered with exact date and time on the DOS-formatted disk in order to keep a logbook. The data stored on the disk can be evaluated/printed via the included windows-based program. 12.7.1. How to program the disk drive Push menu key Push system prog. key Push prog. control panel key push next key until display shows disc drive push change key to choose Yes / No choose Yes push next key to go back to the main menu 12.7.2. How to install the disk drive program on your PC 1. 2. 3. 4. 5. Insert disk in drive A: or B: Select "Run" under the menu "File" in the "Program Manager" Write "A:\install.exe" or "B:\install.exe" in the dialogue box Confirm with "OK" Write the name of the folder where INODISC shall be installed in the dialogue box "Choose folder" and select "install" 6. Select "Yes" in the dialogue box "Install INODISC in folder C:\INODISC" in order to install the program, or select "NO" in order to choose a new folder. 7. Answer "Yes" at the dialogue box "Create folder C:\INODISC" 8. The program will be installed and the program box "INODISC 1.0" will be created 12.7.3. How to read the logbook in the program 1. Remove disk from the disk drive in the system and insert it in the PC's disk drive 2. Start the INODISC 1.0 program 3. Choose disk drive under the menu "Logbook", and "Open logbook".The logbook will be opened and a filed event is shown 4. With the keys W and Xone can move to the previous or next filed event 5. With the keys WI and IXone can go to the first or the last event stored 6. Each filed event is shown with exact date and time Program menus 708 001 C 22 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 Program menus 1. 2. 3. 4. 5 708 001 C FILE Format disk Printer settings End program "Alt+X" formats disk in DOS-format printer settings are done closes INODISC 1.0 LOGBOOK Open logbook Print report Close window "STRG+F4" Opens logbook prints the event shown closes current window REGISTRATIONS First Previous Next Last Go to shows first event shows previous event shows next event shows last event Chooses event according to event number DIALOGUE BOX Next to each other Under each other On top of each other Arrange symbols HELP Content F1 Use help with "Shift+F1" Info arranges open windows next to each other arranges open windows under each other arranges open windows on top of each other arranges the symbol shows contents of the help menu information on use information on INODISC version 23 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 12.8. Circuit modules 12.8.1. Circuit modules SU/SV 2x3A and SU/SV 1x6A The circuit modules are to be installed in the CPS 220 SV and CPUS 220 SV systems. A maximum of 12 luminaires can be connected to each circuit module. For each circuit the terminals L, N, PE are available on the terminal sections X3, X4, X5 SU6SKÜ SU/SKÜ 2x3A NetzSi 5AT SU6SKÜ SU/SKÜ 2x3A SU6SKÜ SU/SKÜ 2x3A SU6SKÜ SU/SKÜ 2x3A SU6SKÜ SU/SKÜ 2x3A SU6SKÜ SU/SKÜ 2x3A SU6SKÜ SU/SKÜ 2x3A SU6SKÜ SU/SKÜ 2x3A Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Batterie Ein Ein Ein Ein Ein Ein Ein Ein Störung Störung Störung Störung Störung Störung Störung Störung 10AT Si 5AT 10AT Si 5AT 10AT Si 5AT 10AT Si 5AT 10AT Si 5AT 10AT Si 5AT 10AT Si 5AT 10AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Ein Si 10AT Störung Ein Si 10AT Störung Ein Si 10AT Störung Ein Si 10AT Störung Ein Si 10AT Störung Ein Si 10AT Störung Ein Si 10AT Störung Ein Si 10AT Störung Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT 10AT Ladeteil 220V / 7,5A Ein INOTEC On the terminal sections X3, X4 and X5 the relative terminals are related to the modul's location. The assignment of the circuit modules to the terminal sections has to be carried out as follows: Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 SK 4.1 SK 6.1 SK 7.1 SK 4.2 SK 6.2 SK 7.2 Slot 8 X3 PE/L+1.1/N-1.1 X3 PE/L+1.2/N-1.2 Slot 9 Slot 10 Slot 11 Slot 12 Slot 13 Slot 14 Slot 15 SK 12.1 SK 14.1 SK 15.1 SK 12.2 SK 14.2 SK 15.2 Slot 16 X4 PE/L+9.1/N-9.1 X4 PE/L+9.2/N-9.2 Slot 17 Slot 18 Slot 19 Slot 20 Slot 21 Slot 22 Slot 23 SK 20.1 SK 22.1 SK 23.1 SK 20.2 SK 22.2 SK 23.2 Slot 24 X5 PE/L+17.1/N-17.1 X5 PE/L+17.2/N-17.2 708 001 C 24 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 12.8.1.1. How to program the SU/SV 2x3A and 1x6A modules push menu key push system Prog. key push circuit assignment key push programming circuit key until display shows programming circuit place 1 push programming circuit key until display shows place 1 connected push change key to choose between connected / disconnected choose connected push place assignment key until display shows SU/SV 2x3A SK 1/1 Status: active push change key to choose between active / not active choose active push next key until display shows Status: … -light push change key to choose between NM-light / M-light / switch. M-L choose NM-light (non maint./maintained emergency light) push next key until display shows L1 discon. push change key to choose between connected / disconnected if a luminaire (adressed 01) is installed, choose connected if no luminaire (adressed 01) is installed, choose disconnected push next key until next luminaire, carry one as above for all connected luminaire OR push update desti. text key to enter location enter max. 20 letters with keyboard after having entered destination push F3 to obtain display L2 selected the programming steps for L02 are as for luminaire L01 program all luminaires until you reach luminaire no. L12 the display shows then SU/SV 2x3A SK1/2 the programming steps for circuit 1/2 are as for circuit 1/1 all other circuits are to be programmed as 1/1 push finish key when all circuits have been programmed Prior to this an address has to be set on all connected emergency and escape route luminaires as per the relevant manual! 12.8.1.2. How to program the SU/SV module in connection with LSA 8.1 Before programming the SU/SV, the LSA 8.1 modules must already have been programmed in the control unit. (see 12.3.1) Two different channels of the LSA 8.1 can be assigned to each circuit change over module. 708 001 C push menu key push system prog. key push assignment key push programming circuit key until display shows programming circuit place 1 push programming circuit key until display shows place 1 connected push change key to choose between connected / disconnected choose connected push place assignment key until display of SU/SV 2x3A SK 1/1 status: active push change key to choose between active / not active choose active push next key until display shows status: … -light push change key to choose between NM-light / M-light / switch. M-L 25 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 choose switch. M-L push next key until display shows SU/SV 2x3A SK1/1 1. LSA-assignment push change key to choose none - LSA8/1 - LSA8/2 - LSA-8/3 choose relevant LSA-8 push next key until display shows LSA8/1 channel no. chan.: 1 push change key to choose between channel 1 - channel 8 select relevant channel push next key until display shows 2. LSA assignment program as for first LSA, see above In order to program the other circuit change-over modules repeat the above steps. 12.8.1.3. How to program the SU/SV module in connection with TLS Before programming the SU/SV, the TLS module must already have been programmed in the control unit. (see 12.4.1) push menu key push system prog. key push circuit assignment key push programming circuit key until display shows programming circuit place 1 push programming circuit key until display shows place 1 connected push change key to choose between connected / disconnected choose connected push place assignment key until display shows SU/SV 2x3A SK 1/1 status: active push change key to choose between active / not active choose active push next key until display shows status: … -light push change key to choose between NM-light / M-light / switch. M-L choose switch. M-L push next key until display shows LSA 8 LSA 8 has to be programmed as described in paragraph 12.8.1.2 push next key until display shows TLS assignment: none push change key to choose between none / TLS1 / TLS2 / TLS3 choose relevant TLS push next key In order to program the other circuit modules repeat the above steps. 708 001 C 26 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 12.8.1.4. How to program the SU/SV module in connection with TLS 5 Before programming the SU/SV, the TLS-5 module must already have been programmed in the control unit. (see 12.5.1) push menu key push system prog. key push circuit assignment key push programming circuit key until display shows programming circuit place 1 push programming circuit key until display shows place 1 connected push change key to choose between connected/disconnected choose connected push place assignment key until display shows SU/SV 2x3A SK 1/1 status: active push change key to choose between active / not active choose active push next key until display shows status: … -light push change key to choose between NM-light / M-light / switch. M-L choose switch. M-L push next key until display shows LSA 8 LSA 8 has to be programmed as described in paragraph 12.8.1.2 push next key until display shows TLS assignment: none push change key to choose between none / TLS1 / TLS2 / TLS3 / TLS4 / TLS5 choose relevant TLS channel push next key In order to program the other circuit modules repeat the above steps. 708 001 C 27 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 12.8.2. Circuit modules SU/SKÜ 2x3A and SU/SKÜ 1x6A The circuit modules can be installed in the CPS 220 SKÜ and CPUS 220 SKÜ systems. Maximum 12 monitored luminaires can be connected to each circuit change-over device. For each circuit the terminals L, N, PE are available on the terminal sections X3, X4, X5. SU6SV SU/SV 2x3A SU6SV SU/SV 2x3A SU6SV SU/SV 2x3A SU6SV SU/SV 2x3A Si 5AT Si 5AT Si 5AT NetzSi 5AT SU6SV SU/SV 2x3A Si 5AT SU6SV SU/SV 2x3A SU6SV SU/SV 2x3A SU6SV SU/SV 2x3A Si 5AT Si 5AT Si 5AT Batterie Ein Ein Ein Ein Ein Ein Ein Ein Störung Störung Störung Störung Störung Störung Störung Störung 10AT Si 5AT 10AT Si 5AT 10AT Si 5AT 10AT Si 5AT 10AT Si 5AT 10AT Si 5AT 10AT Si 5AT 10AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Ein Si 10AT Störung Ein Si 10AT Störung Ein Si 10AT Störung Ein Si 10AT Störung Ein Si 10AT Störung Ein Si 10AT Störung Ein Si 10AT Störung Ein Si 10AT Störung Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT 10AT Ladeteil 220V / 7,5A Ein INOTEC The relevant circuit modules are assigned to unique terminals on the terminal sections X3, X4 and X5. The assignment of the circuit modules to the terminal sections and the terminals has to be carried out as described on page 23. 12.8.2.1. 708 001 C How to program the SU/SKÜ modules push menu key push system prog. key push circuit assignment key push programming circuit key until display shows programming circuit place 1 push programming circuit key until display shows place 1 connected push change key to choose between connected / disconnected choose connected push place assignment key until display shows SU/SKÜ 2x3A SK 1/1 status: active push change key to choose between active / not active choose active push next key until display shows status: … -light push change key to choose between NM-light / M-light / switch. M-L choose NM-light (non maintained / maintained emergency light) push next key until display shows current tolerance 5% push change key to change settings of current deviation key ½ change is + (encreases tolerance) key ¾ change is - (decreases tolerance) push next key push edit destination key in order to enter luminaire location text of max. 20 letters with keyboard push F3 when text is complete the display shows then "next place" program the following places as above push end key in order to have the display showing Starting a new setting of SKÜ current? push Yes key Functiontest will be started with measurement of the value push No key The program goes back to the main menu 28 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 12.8.2.2. How to program the SU/SKÜ module in connection with LSA 8.1 As described in paragraph 12.8.1.2 12.8.2.3. How to program the SU/SKÜ module in connection with TLS As described in paragraph 12.8.1.3 12.8.2.4. How to program the SU/SKÜ module in connection with TLS 5 As described in paragraph 12.8.1.4 708 001 C 29 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 12.8.3. Circuit modules SU 2x3A and SU 1x6A The circuit modules can be installed in the CPS 220 and CPUS 220 centrals. Maximum 12 luminaires can be connected to each circuit. For each circuit module there is a set of L, N, PE terminals available on the terminal sections X3, X4 and X5. SU6SKÜ SU/SKÜ 2x3A NetzSi 5AT SU6SKÜ SU/SKÜ 2x3A SU6SKÜ SU/SKÜ 2x3A SU6SKÜ SU/SKÜ 2x3A SU6SKÜ SU/SKÜ 2x3A SU6SKÜ SU/SKÜ 2x3A SU6SKÜ SU/SKÜ 2x3A SU6SKÜ SU/SKÜ 2x3A Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Batterie Ein Ein Ein Ein Ein Ein Ein Ein Störung Störung Störung Störung Störung Störung Störung Störung 10AT Si 5AT 10AT Si 5AT 10AT Si 5AT 10AT Si 5AT 10AT Si 5AT 10AT Si 5AT 10AT Si 5AT 10AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Ein Si 10AT Störung Ein Si 10AT Störung Ein Si 10AT Störung Ein Si 10AT Störung Ein Si 10AT Störung Ein Si 10AT Störung Ein Si 10AT Störung Ein Si 10AT Störung Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT Si 5AT 10AT Ladeteil 220V / 7,5A Ein INOTEC The relevant circuit modules are assigned to unique terminals on the terminal sections X3, X4 and X5. The assignment of the circuit modules to the terminal sections and the terminals has to be carried out as described in paragraph 8.8.1. The function setting of each change-over device is done with a switch on the front plate (M = maintained em-light, NM = non maintained em-light). 708 001 C 30 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 12.9. CPS 220 / SV / ... with JOKER Technology 12.9.1. General Information Each J-SU/SV change-over device can supply and monitor up to 12 luminaires in three different modes (maintained-, non-maintained- or switched maintained - all in one mode or mixed modes) on one circuit. These switching modes are active in mains supply. A mains failure at the main distribution board or at any monitored supply will automatically switch all connected luminaires to battery operation, regardless of their mains switching mode. SU / SV - J 2x3A Failure NM - ON Si 5A T M - ON Failure Si 5A T NM - ON M - ON 12.9.2. Exit and safety-luminaires, modules with JOKER technologie Each module and luminaire suitable for Joker Technology is fitted with a switch (DL/BL = Maintained / Non-maintained mode) to set the luminaire switching mode for this component. Switching mode: 708 001 C Maintained: The switch on the electronic ballast or the monitoring module has to be set to the DL (M)-position. Non-maintained: The switch on the electronic ballast or the monitoring module has to be set to the BL (NM)-position. Switched Maintained: The switch on the electronic ballast or the monitoring module has to be set to the BL (NM)-position. The input LS/NS on the modules and electronic ballasts is used to switch this luminaire, along with the standard mains lighting ON or OFF. 31 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 12.9.3. Exit and safety-luminaires, modules with JOKER technologie For individual lamp monitoring and of fluorescent lamps, halogen lamps, bulbs and glow-wire lamps. With address switch for luminaire identification and sense-input to allow switching along with the general lighting. To be installed inside of luminaire. Technical data 230V 50/60 Hz Mains supply: 176 - 264V DC Battery supply: Load range: 5-120W (J-SV-Modul/S) 20-300W (J-SV-Modul.2/S) 2-30W (J-SV-Modul.3/S) 18-120W (J-SV-Modul.4/S) Ambient temp.: Housing: Wiring: -15°C ... +65°C Thermoplast up to 2,5mm² single solid wire or 1,5mm² soldered flex-wire to DIN EN 55015 EMC: Connection J-SV-Modul/S PE N L General lighting Light switch Adresse J-SV-Modul / S Eingang 01 DF 2 3 C 4 B 5 A 9 8 76 NS Temp.-Test L+ L+ Supply circuit from CPS 220 J/SV 9$& tc Tc=70°C max BL BL LS 851 002 DL DL 2–30 W NN- NL+ EVG Operation mode selection switch (NM) (M) J-EVG 4-13 SV/S and J-EVG 18 SV/S have to be connected as per above sketch. Input L+ N230V~ 230V~ 220V220V0V 0V 708 001 C Light switch LS / NS 230V~ 0V 230V~ 0V 230V~ 0V Output L+ N230V~ 0V 220V220V0V 0V 32 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 12.9.4. Programming the JOKER technology circuits For programming instructions of J-SU/SV 2x3A and J-SU/SV 1x6A see 12.8.1 708 001 C 33 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 12.10. Isolation supervision and tests The isolation supervision and test settings in the CPS 220 are integrated next to the control unit. When the system operates in mains power supply the battery circuit is supervised for isolation errors. At an isolation resistance <2,0 K /V the fault is shown on the display and a red LED "Failure" flashes to indicate this. Has the fault been cleared the system goes automatically back to "Normal Operation" and the red LED is turned off. Operation BATTERY Operation FAILURE CPS 220/SV INO TEC + CPS 220 01.07.95 12:00 OPERATION U BATT: 220V TEST I BATT +15.0A Charge failure PRINTER CENTRONICS ISO KEYBOARD UH 5AT All connected circuits are included in the isolation supervision when the central is in battery operation, i.e. when a function test or battery duration test is carried out and in case of power supply interruption. If an isolation fault occurs, it will be shown in the control unit and logged. After the fault has been cleared this entry can be deleted only by carrying out a new function test. The isolation supervision can be tested by pressing the keys Test + or Test -. An isolation fault is shown on the control units display. The isolation error is set back when the key is released. 708 001 C 34 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 13. External units 13.1. 3-phase-monitor - DPÜ In order to supervise the mains power supply the DPÜ can be installed directly in the local power subdistribution boards. If a phase fails the DPÜ will interrupt the 24V-monitoring-circuit. This contact is wired to SL+/SL- on the terminal section X2 (remove wire link). If several local circuit fuses or sub-distribution boards are supervised, the DPÜs have to be connected in series. • • • • • • LED-indication for L1, L2, L3 phases in any order whatever detection of failed or low voltage in three-phase-systems suitable for single-phase monitoring to IEC 255, VDE 0435, part 303 for distribution board / panel mounting (DIN rail profiles) Technical data 230 V AC, 400 V AC 1,1 Un permanent Power consumption: ca. 3VA 50/60 Hz Nom.-frequency: Activation level: 0,85 Un 1 change-over contact Contacts: 30V DC, 1A / 230V AC, 0,5 A (resistor load) Imax contact : -20°C ... +60°C Ambient temp.: IP 20 (terminals) Protection: IP 40 (housing) Thermoplast Housing: up to 2,5mm² single solid wire Wiring: or 1,5mm² soldered flex-wire to DIN EN 55015 EMC: Nominal voltage : Tolerance: General lighting L1 L2 L3 N PE General lighting L1 L2 L3 N PE L1 N PE L1 L1 DPÜ L1 DPÜ L2 DPÜ L2 L3 ,127(& L2 L3 ,127(& L3 ,127(& Sub-db 2 Terminal rail X2 SL+/SL– Sub-db 1 General lighting Sub-db 3 Supply monitoring in single- and three-phase installation SL+ SL- All luminaires in non-maintained or switched maintained mode change to maintained mode if the power supply fails on DPÜ-monitored sub-distribution panels. The CPS-controller display shows “Failure sub DB”. 708 001 C 35 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 13.2. Remote display tableau - MTB The remote notifying tableau is to be connected to the RIF 5 module as shown in the drawing below. The maximum cable length allowed between the RIF 5 and MTB is 500m with a 0,8 mm² cable. Three LED`s and a switch are on the front of the MTB panel: Green LED: Yellow LED: Red LED: Switch ON: Switch OFF: operation battery operation sum-failure the corresponding panel is blocked the corresponding panel is not blocked 5HPRWHGLVSOD\WDEOHDX 2SHUDWLRQ %DW %DWRSHUDWLRQ 5HPRWHVZLWFK )DLOXUH ,127(& 9 2Q 2II 07% )6 )6 )6 13.2.1. How to program the RIF 5 module with the MTB The programming process for the remote display tableau in connection with the RIF 5 is described in paragraph 12.2.1. 708 001 C 36 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 13.3. Phase selection connector - PAS, optional The PAS comes with 20A/63A/100A. It switches to a remaining healthy phase if one or two supply phases fail and ensures mains power supply continuity to the CPS system. The emergency lighting system changes to emergency operation only after all three phases failed. The PAS has to be mains connected to the terminals L1, L2, L3, N and PE with three phases. The connecting cables to the CPS central are to be connected to L, N and PE. PE N L to CPS-system 708 001 C PE N L1 L2 L3 Main supply 37 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 13.4. Modules with BUS-Connection 13.4.1. General information It is possible to connect the RIF 5 and LSA 8.1 units to the CPS externally via a BUS cable. The electrical connection and the programming of those modules is described in paragraphs 12.2.1 for the RIF 5 and in paragraphs 12.3.1 for the LSA 8.1. Further BUS-suitable units are shown on the following pages. If the modules are used externally, they have to be addressed as described in paragraph 12.1. 708 001 C 38 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 13.4.2. 3-phase-monitor with BUS - DPÜ/B To monitor the mains supply directly on a local lighting sub-distribution board the DPÜs can be connected directly inside. If a phase fails the 24V-circuit is interrupted and a failure message "sub.-dist. Failure" is shown at the same time on the emergency systems control unit display. Pushing the button INFO on the control unit shows the user all failed sub.-dist. boards with location. The contact 1-2 has to be connected to the terminals SL+ / SL-. If the 24V-circuit shall use the same cable as the BUS-line, the connection of the DPÜ-B must be carried out as shown below. Wire link on last DPÜ/B.1 mandatory Address setting is mandatory. 13.4.2.1 708 001 C How to program the DPÜ/B push Menu key push system progr. key push prog. control panel key push next key until display shows number of DPÜ/B push change key to choose between none / 1-31 push next key until display shows DPÜ/B change destination push destination key in order to edit the location text push delete destin. text key - destinations will be deleted push change destin. text key - enter destination text via keyboard after text is completed push F3 and then continue key until the program asks you to enter the data for the next DPÜ B push next key after completed all data initiate test of DPÜ/B push yes key for testing the DPÜ/B push next key to go back to the main menu 39 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 13.4.3. BUS-fitted remote display tableau - MTB/B The BUS-suitable MTB-B has to be connected directly to the BIF module. The maximum cable length between BIF and MTB-B module is 500m with 0,8 mm². At the MTB-B the address 7 has to be programmed. Three volt-free contacts for external signalling are part of the MTB-B: Terminals 1 and 2 sum-failure contact open (n/o) Terminals 3 and 4 battery operation contact closed (n/c) Terminals 5 and 6 normal operation contact closed (n/c) 5HPRWHGLVSOD\WDEOHDX 2SHUDWLRQ %DW %DWRSHUDWLRQ 5HPRWHVZLWFK 2Q )DLOXUH 2II ,127(& % % %,) ,127(& 708 001 C )6 )6 H[WHUQ 990 013 13.4.3.1. 9 9 07% BIF in CPS or CPUS How to program the MTB/B push Menu key push system prog. key push prog. control panel key push next key until the display asks whether the RIF 5 Relay interface is connected push change key to choose between connected / not connected choose connected push next key to go back to the main menu 40 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 13.4.4. BUS-fitted remote display tableau with printer - MTB/D The BUS suitable MTB-D has to be connected directly to the BIF module. The maximum cable length between BIF and MTB-D is 100m at 1,5 mm². For the MTB-D the address 7 has to be programmed. Pushing the button "FT" on the MTB-D releases a function test on the connected emergency lighting system. ,127(& 3ULQWHU 3ULQWHU )DLOXUH 2SHUDWLRQ )XQNWLRQVWHVW %6./+6;g+;g-b-6. . .2 .1/g-g/-;/gb-$6;gb$.g .1/g-g/-;/gb-$6; gb$.g 1+/;-.1/;.0-b;0--./gb ;1+g;1-.;-b-g$-.g/.g. g %DW %DW 2SHUDWLRQ 5HPRWH 21 VZLWFK )DLOXUH )7 )77HVW 2II 07%' % % %,) ,127(& 708 001 C )6 )6 H[WHUQ 990 013 13.4.4.1. 9 9 9 BIF in CPS or CPUS How to program the MTB/D with printer push menu key push system prog. key push prog. control panel key push next key until the display asks whether there is an built in printer push change key to choose between Yes/No choose Yes push next key to go back to the main menu 41 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 13.4.5. Light switch function - LSA 8.1 The LSA 8.1 can be installed in an external local distribution board. Maximum three different LSA 8.1 can be connected to the control unit of the emergency lighting system. The addresses 1, 2 and 3 have to be set on the external LSA 8.1 modules. The connection of the LSA 8.1 via a BIF module is described in paragraph 12.1. For programming and wiring example see paragraph 12.3.1 / 12.3.2. 708 001 C 42 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 13.4.6. BUS-Sub-Stations – CPUSB It is possible to connect BUS-compatible sub-stations to the CPS 220 SV and SKÜ. Therefore a BIF- module has to be used. Connection of BUS- sub station - Power supply at the terminals L, N, PE: max. 10 mm² Battery power supply at the terminals B+ and B-. max. 10 mm² Final Circuits 1-6 at the corresponding terminals L, N, PE. BUS-cable at the terminals B, ⊥. Battery 220V via CPS main-station Mains 230V AC Netz N N Netz L L St.-Kreis1 N– L+ St.-Kreis2 N– L+ St.-Kreis3 N– L+ St.-Kreis4 N– L+ St.-Kreis5 N– L+ St.-Kreis6 N– L+ Batt. Batt. Internal Panel-BUS via BIF IB BB Adresse Stromkreis Stromkreis Stromkreis Platz 1 Platz 2 Platz 3 links mitte rechts 1.1 / 1.2 2.1 / 2.2 3.1 / 3.2 4.1 / 4.2 5.1 / 5.2 6.1 / 6.2 7.1 / 7.2 8.1 / 8.2 9.1 / 9.2 10.1 / 10.1 11.1 / 11.2 12.1 / 12.2 13.1 / 13.2 14.1 / 14.2 15.1 / 15.2 16.1 / 16.2 17.1 / 17.2 18.1 / 18.2 19.1 / 19.2 20.1 / 20.2 21.1 / 21.2 22.1 / 22.2 23.1 / 23.2 24.1 / 24.2 keine Funktion keine Funktion 1 8 0 7 9 3 5 6 Adresseinstellung Sic herheitstec hnik GmbH 2 INO TEC 4 0 1 2 3 4 5 6 7 8 9 Addressing of sub-stationsIt is necessary to assign an address to each CPUS B for identification at the control unit. Maximum 8 BUS compatible sub-stations can be connected to each CPS 220/SV/...or CPS 220/SKÜ/.....system. How to program the circuits is described in the paragraph 12.8. How to program the circuits with JOKER Technology see paragraph 12.9. 708 001 C 43 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 Assignment address/circuit at the controller unit Address 0 Circuits Address 1 Circuits Address 2 Circuits Address 3 Circuits Address 4 Circuits Address 5 Circuits Address 6 Circuits Address 7 Circuits Addresses 8 and 9 are not allowed! 1.1 4.1 7.1 10.1 13.1 16.1 19.1 22.1 to to to to to to to to 3.2 6.2 9.2 12.2 15.2 18.2 21.2 24.2 Sample: A project is equipped with two bus-substations and a CPS 220/SV/32. The 16 installed change-over devices (2x3 Amp or 1x6 Amp) occupy rack one (8 slots) and rack two (8 slots) of the CPS-220/SV/32. By this they use the addresses 1.1, 1.2 … 8.1, 8.2 (rack one) and 9.1, 9.2 ...16.1, 16.2 (rack two). The next free circuit numbers (17.1/17.2/18.1 and 18.2) should not be used and the first bus-sub station nd must be set to address “6” to use the circuits 19.1 to 21.2. The 2 CPUSB must be set to address 7 for circuits 22.1 to 24.2. 708 001 C 44 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 14. How to program the control unit 14.1. General information Operation BATTERY Operation FAILURE CPS 220/SV INO TEC + CPS 220 01.07.95 ISO 12:00 OPERATION U BATT: 220V TEST I BATT +15.0A Charge failure - PRINTER CENTRONICS KEYBOARD UH 5AT The control unit of the CPS 220 and CPUS 220 has a 4 line display each line with max. 20 letters. The LEDs to the left of the display indicate the sytems status: LED green LED yellow LED red LED red normal operation battery operation failure charging failure The 4 keys to the right of the display are used to program the control unit. It is possible to connect a printer with protection category II , to the centronics interface and a keyboard to the included port. In normal operation the display gives the following information: Battery voltage Battery current Date Time If no entry is affected for approx 1 min., the controller will switch back to the main menu. After activating the mains supply, the display shows the program version and the initializing of system and disk drive starts. After finishing the process the display shows the status for normal operation. 708 001 C 45 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 14.2. Test menu 14.2.1. How to start a function test - FT push functiontest key The function test will be started and shown on the display. The yellow LED indicates battery operation 14.2.2. How to start a battery test - DT push menu key push test menu key push start durationtest key The battery duration test will be started and it will be shown on the display. The yellow LED indicates battery operation. The batteries supply will be maintained until the first deep discharging protection level has been reached. 14.2.3. How to stop a battery test after one minute has passed from starting the DT push menu key push test menu key push stopp durationtest key the battery test will be stopped. 14.2.4. How to program new test times 14.2.4.1. 708 001 C How to program a new test time for FT (factory setting 7 days) push menu key push test menu key push new time of test key push new time of FT key the display will then show: automatical FT push change key to choose between Yes/No choose Yes push next key until display shows time of test FT test cycle: 1 day push change key to choose between 1-15 days push next key until display shows time of test FT 10:00 push change and continue to set the time push back key to go back to the main menu 46 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 14.2.4.2. 14.3. How to program a new test time for DT (factory setting 365 days) push menu key push test menu key push new time of test key push new time of DT key the display will then show automatical DT push change key to choose between Yes/No choose Yes push next key until display shows date for DT 01-08 (first of august) push change key and next input key to enter the date after input is completed the display will show time of DT 10:00 push change and next place to enter the time push back key after input is complete push main menu How to program the system 14.3.1. How to change the date push menu key push system prog. key push update new time key push change date key set the date using the next input and change keys push back key after input is complete to go back to the main menu 14.3.2. How to change the time push menu key push system prog. key push update new time key push change time key set the time using the next input and change keys push back key to go back to the main menu 14.3.3. How to change a weekday 708 001 C push menu key push system prog. key push update new time key push change weekday key push change key to set weekday push back to go back to main menu 47 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 14.4. How to program the CPS unit 14.4.1. How to connect to a SV-central push menu key push system prog. key push prog. control panel key push next key until display shows system connected to SV-device Yes / No push change key to choose Yes push next key to change system's address push change key to choose between address 1-32 push next key to go back to main menu 14.4.2. Manual reset push menu key push system prog. key push prog. control panel key push next key until display shows with / without manual reset push change key to choose with manual reset push next key to go back to the main menu 14.4.3. Battery operation delay time push menu key push system prog. key push prog. control panel key push next key until display shows with / without delay time push change key to choose with delay time push next key until display shows with delay time delay time: 1 min. push change key to choose between 1-15 minutes. push next key to go back to main menu 14.4.4. How to block the CPS central push menu key push system prog. key push prog. control panel key push next key until display shows CPS system is blocked / not blocked push change key to choose blocked push next key to go back to the main menu 14.4.5. Function remote switch 708 001 C push menu key push system prog. key push prog. control panel key push next key until display shows function of remote swit. push change key to select maintained or EL+Main. push next key to go back to the main menu 48 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 14.4.6. How to program the printer port push menu key push system progr. key push progr. CPS modul key push next key until display shows print-out of central configuration push Yes key to receive a print-out push No key to go back to main menu 14.4.7. Test deep discharge protection push menu key push system prog. key push prog. control panel key push next key until display shows Deep discharge protection test push Yes key Test is carried out push next key to go back to main menu 14.4.8. Menu options programmed by the factory 14.5. function of the control unit System- / Sub-station- / Controller-function battery information System identification number Information menu 14.5.1. System information 14.5.1.1. push menu key push information key push system information key push circuit information key the display will show place no.: 1 push information key the display will show information corresponding to place no.: 1 push back key to continue push next place key the display shows information as above carry on for all other places, to end push previous menu key to go back to the to sub-menu for system information or main menu 14.5.1.2. 708 001 C Circuit information Battery information push menu key push information key push system info key push battery information key the display will show time of last battery duration test xxx minutes push next key until display shows battery information push back key to go back to the to sub-menu for system information or main menu 49 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 14.5.1.3. Control unit information push menu key push information key push system information key push control panel info key until display shows program version - Ver.: A 11.H 12 (depending on actual version) push next key until display shows system number shunt unit version push previous menu key to go back to the to sub-menu for system information or main menu 14.5.2. Failure information push menu key push information key push failure info key until display shows failure information push print key in order to receive a print-out of actual failures of the complete CPS system installed push view key in order to see eventual errors on the display push next key in order to see the further faults after the last fault is shown, the program goes back to main menu 14.5.3. Disk information push menu key push information key push floppy / logbook key push floppy information key in order to see the information stored on the floppy push previous menu key in order to go back to the main menu key 14.5.4. Logbook 14.5.4.1. 708 001 C Delete logbook push menu key push information key push floppy / logbook key push logbook key push clear logbook key the display will show the following message Warning, all data will be lost push clear key in order to delete all data in the logbook push previous menu key in order to go back to the floppy/logbook sub-menu 50 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 14.5.4.2. push menu key push information key push floppy / logbook key push logbook key push display logbook key the display will show the last entry in the logbook push Ï and Ð keys you can scroll through the logbook all entries will be shown with date and time push previous menu key in order to go back to the floppy/logbook sub-menu 14.5.4.3. 708 001 C Print logbook - print all registrations push menu key push information key push floppy / logbook key push logbook key push print logbook key in order to initiate a print-out of the logbook push all items printing in order to receive a print-out of all events push abort printing key Display: print-out stopped push previous menu key in order to go back to the floppy/logbook sub-menu 14.5.4.4. Show logbook Print logbook - print a selection push menu key push information key push floppy / logbook key push logbook key push printing a part key the display will then show the text start print item: xxx push change key and next display address in order to enter the number of event where the print-out shall start from push print key the display asks then for how many events shall be printed use the keys Ï and Ð to enter the number of events to be printed 1-99 registrations can be selected push print key the selected registrations will be printed push abort printing key in order to stop the print-out the system goes back to the floppy/logbook sub-menu push previous menu key in order to go back to the main menu 51 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 15. Control module with controller function 15.1. General information Control modules with Controller Function (one Controller for max. 8 substations) Special features: 1. FT and BT starting at the same time for all connected stations. 2. The timers of all connected substations can work in line with the controller. 3. Blocking of FT and BT is possible on every sub-station 4. Data communication failures and other failures can be identified for each station 5. ISO-failure test for all main system, sub-stations and all connected luminaires and display of current and voltage 6. Remote display of failure info for all sub-stations via controller and RIF 5 / MTB 7. Remote blocking of all sub-stations via controller and RIF 5 / MTB Failure infos of sub-stations will not be logged in the logbook of the controller but in the sub-stations own control module logbook. 15.2. Controller connection All connected sub-stations need to be linked to the controller via a R-T-G line. Looping from one sub-station to the next ones is allowed. The max. cable length allowed with 1.5mm² is 2000m. 15.3. Programming the Sub-station addresses All connected sub-stations must have an individual address ( 1 - 8 ). To do this the sub-station control modules must be programmed as follows: push menu key push system prog. key push prog. control panel key push next key until display shows system connection to SV- Central push change key to choose YES / NO Choose YES push next key select address with change key push next key to go back to main menu 708 001 C 52 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 15.4. Programming the controller A mandatory requirement to use a control module in CONTROLLER function is to select "NO" when programming the step "system connected to SV-central" push menu key push system prog. key push prog. control panel key push next key until display shows Module as controller push change key to choose YES / NO choose YES push next key until display shows Number of Sub-stations push change key and set total sub-station number (max. 8) push next key until display shows blocking of all sub-stations valid push change key to choose YES / NO YES All connected sub.-stations can be blocked at the same time NO Only main station can be blocked push next key to go back to main menu 15.5. Update timers for all connected stations push menu key push system prog. Key push prog. control panel key push set time key carry on as described in 10.3.1 - 10.3.3 push next key until display shows update of all system timers push change key to choose YES / NO choose YES Display shows: Delete FT and DT on all connected systems choose NO all sub-station take the preselected FT- and DT-times from the controller. 15.6. Automatic ISO supervision with failure display The controller offers the possibility to do a detail-test resulting in a display info with the faulty sub-station and the final circuit push menu key push system prog. key push next key until display shows Automatic ISO-detection - Yes / No push change key and choose Yes the ISO test starts Display info: Faulty substations / circuits will be flagged up on the display push next key carry on with the test As long as new ISO-faults exist they will be displayed, after last fault is displayed push next key to go back to main menu 708 001 C 53 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 16. Further modules for CPS 220 systems 16.1. Continuous light circuit modules - DSM/L – DSM/U DSM modules can be installed in order to switch mains luminaires and emergency luminaires together. DSM-U modules are to be installed in the local distribution boards, DSM-L modules are to be installed in luminaires that are already present. The connection of the DSM modules to the CPS 220 system has to be made as shown in the drawing below. When mains is present on terminals LS and NS, the connected emergency luminaires (terminals 0+/0-) are turned off. Actuating the switch contact turn all mains and emergency luminaires on. If the local mains sub.distribution board fails, will also cause the connected emergency staircase luminaires to be turned on, in this case the DSM module has a phase monitor function. The circuits of the CPS system with DSM modules have to be programmed as maintained light, see paragraphs 12.8.1.1 / 12.8.2.1 / 12.8.3. If the CPS system switches over to emergency light operation, all connected emergency luminaires will be supplied from the batteries, no matter of the type of switching mode. DSM / L.1 Maintained circuit switch module for luminaire installation: Technical data Mains supply: Battery supply: Contact: Max. load: Ambient temp.: Housing: Wiring: EMC: 230V 50/60 Hz 176 - 264V DC 1 n/o 600W -15°C ... +50°C Thermoplast up to 2,5mm² single solid wire or 1,5mm² soldered flex-wire to DIN EN 55015 PE N L General lighting Light switch UN: DSM / L.1 LS 890 412 220 V DC 230 V A C NS Temp.-Test AC 230V 50 / 60Hz DC 176 - 264 V tc Tc=70°C max ta: -15 bis 50°C EMC:gem. EN 55015 Geeignet für Anlagen gem. DIN VDE 0108 / 10.89 Ausgang 600 W max Eingang NN- INO TEC L+ L+ Emergency luminaire O+ O- Supply IN L+ CPS Central 708 001 C 54 Sense-Input OUT N- LS / NS O+ O- 230V~ 230V~ 0V 230V~ 0V 230V~ 220V- 230V~ 220V- 220V- 0V 220V- 0V 230V~ 0V 0V 0V 0V INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 DSM / U.1 Maintained circuit switch module for panel mounting / DIN-rail mounting Technical data Mains supply: Battery supply: Contact: Max. load: Ambient temp.: Housing: Wiring: EMC: 230V 50/60 Hz 176 - 264V DC 1 n/o 600W -15°C ... +40°C Thermoplast up to 2,5mm² single solid wire or 1,5mm² soldered flex-wire to DIN EN 55015 PE N L General lighting Light switch Emergency luminaires O- A usgang O+ NS Schalteing LS DSM / U.1 890 413 O+ / O- LS / NS AC Ein DC L+ / N- NNL+ Eingang L+ CPS 708 001 C 55 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 17. Fan monitoring in the optional "Priorit" fire protection cabinet Type: NL91.172.084 / NL31.172.084, dim. 1970x1002x780mm The function of the exhaust fan in the optionally available "Priorit" fire protection cabinet F30 / F90 is checked by means of a differential pressure guardian. At a change of the adjusted differential pressure the volt free change-over contact changes. The volt free change-over contact is connected to terminal section X11: - 708 001 C 1 – NC (normally-closed) 2 – NO (normally-open) 3 – COM (incoming line) 56 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 18. Recurring examinations 18.1. General Electric plants must be tested regularly. 18.2. Electric plants for safety purposes 18.2.1. Inspection a) Testing of the preparing-values of the protection devices through inspection: annual b) Testing of the load connected to the power source for safety purposes with regard to the capacity of the power source: annual 18.2.2. Testing and measuring a) function test of the change-over devices: annual b) capacity test for the battery: annual c) function test of isolation monitoring systems: semi-annual 18.3. Battery inspection and –monitoring According to DIN EN 50272-2 batteries and their operating units have to be checked regularly for proper function and safety. The following checks must be done: Charger voltage values Voltage of every single battery block and the whole battery Electrolyte density and filling level (if necessary) Cleanness and consistence Correct fit of pole connectors Ventilation Plugs and valves Battery temperature ! Defective battery blocks have to be replaced directly! Divergent or special inspection- and monitoring points as well as their test cycles are to be taken from the operating instructions of the respective battery manufacturer. 18.4. Reports to recurring inspection 18.4.1. Test report The recurring tests and results are to be documented in logbooks. The documentation is to be kept for at least 4 years. 18.4.2. Battery test report Minimal information, which hast to be logged in the test report of the annual battery checks: Room temperature Charge voltage Charge current Discharge current Voltage of every single battery block … at the beginning and the end of battery operation The annual test report is the basis for eventual guarantee claims. 19. Appendix Copyforms for system documentation 708 001 C 57 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 Terminals CPS 220 Project: Panel: X1 PE PE N N L L Mains(L, N, PE) Throughwiring to further sub-stations (L, N, PE) X2 24 V - monitoring loop, external phase monitor SL + SL – R T G Data cable for external supervision RIF 5 installed RIF 5 not installed +24V/⊥ 1 2 3 4 5 6 7 8 9 10 FS+ FS– T+ T– RIF 5 L1 N1 L2 N2 L3 N3 L4 N4 L5 N5 L6 N6 L7 N7 L8 N8 LSA 8.1 1 - 3 pcs. Temperature sensor battery (if required) installed not installed installed not installed installed not installed Channel 1 Channel 1 Channel 1 Channel 2 Channel 2 Channel 2 Channel 3 Channel 3 Channel 3 Channel 4 Channel 4 Channel 4 Channel 5 Channel 5 Channel 5 Channel 6 Channel 6 Channel 6 Channel 7 Channel 7 Channel 7 Channel 8 Channel 8 Channel 8 X3 1.1 ↓ 8.2 Terminal X 3 Circuit 1.1 - 8.2 For details see following pages Total current X 3 Terminal X 4 Circuit 9.1 - 16.2 For details see following pages Total current X 4 Terminal X 5 Circuit 17.1 - 24.2 For details see following pages Total current X 5 X4 + 9.1 ↓ 16.2 + X5 17.1 ↓ 24.2 = X6 U+ Battery connection Total current Panel U– 708 001 C 58 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 Terminals CPUS 220 Project: Panel: X1 PE PE N N L L Mains(L, N, PE) Throughwiring to further sub-stations (L, N, PE) X2 24 V - monitoring loop, external phase monitor SL + SL – R T G Data cable for external supervision RIF 5 installed RIF 5 not installed +24V/⊥ RIF 5 LSA 8.1 1 - 3 pcs. 1 2 3 4 5 6 7 8 9 10 FS+ FS– T+ T– L1 N1 L2 N2 L3 N3 L4 N4 L5 N5 L6 N6 L7 N7 L8 N8 Temperature sensor battery (if required) installed not installed installed not installed installed not installed Channel 1 Channel 1 Channel 1 Channel 2 Channel 2 Channel 2 Channel 3 Channel 3 Channel 3 Channel 4 Channel 4 Channel 4 Channel 5 Channel 5 Channel 5 Channel 6 Channel 6 Channel 6 Channel 7 Channel 7 Channel 7 Channel 8 Channel 8 Channel 8 X3 1.1 ↓ 8.2 Terminal X 3 Circuit 1.1 - 8.2 For details see following pages Total current X 3 Terminal X 4 Circuit 9.1 - 16.2 For details see following pages Total current X 4 Terminal X 5 Circuit 17.1 - 24.2 For details see following pages Total current X 5 + X4 9.1 ↓ 16.2 + X5 17.1 ↓ 24.2 = X6 U+ U+ U– U– 708 001 C Battery-supply sub-station Total current sub-station Throughwiring to further CPUS (+,-) 59 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 Connection plan Circuit CPS Terminal strip X 3 Project: Panel: CPUS 220: Terminal strip Slot NM intern 1) al M 2) LSA 8 TLS Joker 3) 4) 5) Cableno. X3 Terminal 1/1 1.1 N- L+ PE 1/2 1.2 N- L+ PE 2/1 2.1 N- L+ PE 2/2 2.2 N- L+ PE 3/1 3.1 N- L+ PE 3/2 3.2 N- L+ PE 4/1 4.1 N- L+ PE 4/2 4.2 N- L+ PE 5/1 5.1 N- L+ PE 5/2 5.2 N- L+ PE 6/1 6.1 N- L+ PE 6/2 6.2 N- L+ PE 7/1 7.1 N- L+ PE 7/2 7.2 N- L+ PE 8/1 8.1 N- L+ PE 8/2 8.2 N- L+ PE 1) NM= Non-maintained light 2) M = Maintained light 3) LSA 8.1 = Light switch monitor (1 - 3 ) 4) TLS = Staircase lightswitch (1 - 3 ) 5) Joker = Joker-Circuit 708 001 C Name Current (A) Area Total current 60 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 Connection plan circuit CPS Terminal strip X 4 Project: CPS 220: CPUS 220: Terminal strip Slot NM intern 1) al M 2) LSA 8 TLS Joker 3) 4) 5) Cableno.. X4 Terminal 1/1 9.1 N- L+ PE 1/2 9.2 N- L+ PE 2/1 10.1 N- L+ PE 2/2 10.2 N- L+ PE 3/1 11.1 N- L+ PE 3/2 11.2 N- L+ PE 4/1 12.1 N- L+ PE 4/2 12.2 N- L+ PE 5/1 13.1 N- L+ PE 5/2 13.2 N- L+ PE 6/1 14.1 N- L+ PE 6/2 14.2 N- L+ PE 7/1 15.1 N- L+ PE 7/2 15.2 N- L+ PE 8/1 16.1 N- L+ PE 8/2 16.2 N- L+ PE 1) NM= Non-maintained light 2) M = Maintained light 3) LSA 8.1 = Light switch monitor (1 - 3 ) 4) TLS = Staircase lightswitch (1 - 3 ) 5) Joker = Joker-Circuit 708 001 C Name Current (A) Area Total current 61 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 Connection plan circuit CPS Terminal strip X 5 Project: CPS 220: CPUS 220: Terminal strip Slot NM intern 1) al M 2) LSA 8 TLS Joker 3) 4) 5) Cableno.. X5 Terminal 1/1 17.1 N- L+ PE 1/2 17.2 N- L+ PE 2/1 18.1 N- L+ PE 2/2 18.2 N- L+ PE 3/1 19.1 N- L+ PE 3/2 19.2 N- L+ PE 4/1 20.1 N- L+ PE 4/2 20.2 N- L+ PE 5/1 21.1 N- L+ PE 5/2 21.2 N- L+ PE 6/1 22.1 N- L+ PE 6/2 22.2 N- L+ PE 7/1 23.1 N- L+ PE 7/2 23.2 N- L+ PE 8/1 24.1 N- L+ PE 8/2 24.2 N- L+ PE 1) NM= Non-maintained light 2) M = Maintained lightt 3) LSA 8.1 = Light switch monitor (1 - 3 ) 4) TLS = Staircase lightswitch (1 - 3 ) 5) Joker = Joker-Circuit 708 001 C Name Current (A) Area Total current 62 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 Connection plan, final end circuits CPS - Terminal strip X 3 Project: CPS 220: CPUS 220 NM 1) M 2) LSA 3) TLS 4 Joker 5) Operation mode: Area: Terminal strip X3 1.1 - 8.2 Name: Cable-No..: JokerCircuit-No.. function Location 1 2 3 Current (A) (max. 20 characters) 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 NM Luminaire 1 M SM NM Luminaire 2 M SM NM Luminaire 3 M SM NM Luminaire 4 M SM NM Luminaire 5 M SM NM Luminaire 6 M SM NM Luminaire 7 M SM NM Luminaire 8 M SM NM Luminaire 9 M SM NM Luminaire 10 M SM NM Luminaire 11 M SM NM Luminaire 12 M SM Total current 1) = Non-maintained light Joker-Function M = Maintained light NM = Non-maintained light 3) LSA 8.1 = Light switch monitor (1 - 3 ) M = Maintained light 4) TLS = Staircase lightswitch (1 - 3 ) SM = Switched maintained light 5) Joker = Joker-circuit 2) NM 708 001 C 63 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 Connection plan, final end circuits CPS - Terminal strip X 4 Project: CPS 220: CPUS 220 NM 1) M 2) LSA 3) TLS 4 Joker 5) Operation mode: Area: Terminal strip X4 9.1 - 16.2 Name: Cable-No..: Circuit-No.. Jokerfunction Location 1 2 3 Current (A) (max. 20 characters) 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 NM Luminaire 1 M SM NM Luminaire 2 M SM NM Luminaire 3 M SM NM Luminaire 4 M SM NM Luminaire 5 M SM NM Luminaire 6 M SM NM Luminaire 7 M SM NM Luminaire 8 M SM NM Luminaire 9 M SM NM Luminaire 10 M SM NM Luminaire 11 M SM NM Luminaire 12 M SM Total current 1) NM = Non-maintained light Joker-Function 2) M = Maintained light NM = Non-maintained light 3) LSA 8.1 = Light switch monitor (1 - 3 ) M = Maintained light 4) TLS = Staircase lightswitch (1 - 3 ) SM = Switched maintained light 5) Joker = Joker-circuit 708 001 C 64 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 Connection plan, final end circuitsCPS - Terminal strip X 5 Project: CPS 220: CPUS 220 NM 1) M 2) LSA 3) TLS 4 Joker 5) Operation mode: Area: Terminal strip X5 17.1 - 24.2 Name: Cable-No..: Circuit-No. Jokerfunction Location 1 2 3 Current (A) (max. 20 characters) 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 NM Luminaire 1 M SM NM Luminaire 2 M SM NM Luminaire 3 M SM NM Luminaire 4 M SM NM Luminaire 5 M SM NM Luminaire 6 M SM NM Luminaire 7 M SM NM Luminaire 8 M SM NM Luminaire 9 M SM NM Luminaire 10 M SM NM Luminaire 11 M SM NM Luminaire 12 M SM Total current 1) NM = Non-maintained light Joker-Function 2) M = Maintained light NM = Non-maintained light 3) LSA 8.1 = Light switch monitor (1 - 3 ) M = Maintained light 4) TLS = Staircase lightswitch (1 - 3 ) SM = Switched maintained light 5) Joker = Joker-circuit 708 001 C 65 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 Terminals - sub central CPUS B Address: N N L L Í Î Í Î Mains NNL+ L+ Î Î Circuit 1 Circuit ref. Control module 1/1 N NL+ L+ Î Î Circuit 2 Circuit ref. Control module 1/2 N NL+ L+ Î Î Circuit 3 Circuit ref. Control module 2/1 N NL+ L+ Î Î Circuit 4 Circuit ref. Control module 2/2 N NL+ L+ Î Î Circuit 5 Circuit ref. Control module 3/1 N NL+ L+ Î Î Circuit 6 Circuit ref. Control module 3/2 B B +24V + 24V ⊥ ⊥ Í Î Í Î Í Î BUS-connections Batt. + Batt. + Batt. Batt. - Í Î Í Î Battery-supply Sub-station (+, –) PE PE PE PE PE 708 001 C 0 Throughwiring to further sub-stations (L, N, PE) Throughwiring to further CPUS-B (+, –) PE - connections 66 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 Terminals - sub central CPUS B Address: N N L L Í Î Í Î Mains NNL+ L+ Î Î Circuit 1 Circuit ref. Control module 4/1 N NL+ L+ Î Î Circuit 2 Circuit ref. Control module 4/2 N NL+ L+ Î Î Circuit 3 Circuit ref. Control module 5/1 N NL+ L+ Î Î Circuit 4 Circuit ref. Control module 5/2 N NL+ L+ Î Î Circuit 5 Circuit ref. Control module 6/1 N NL+ L+ Î Î Circuit 6 Circuit ref. Control module 6/2 B B +24V + 24V ⊥ ⊥ Í Î Í Î Í Î BUS-connections Batt. + Batt. + Batt. Batt. - Í Î Í Î Battery-supply Sub-station (+, –) PE PE PE PE PE 708 001 C 1 Throughwiring to further sub-stations (L, N, PE) Throughwiring to further CPUS-B (+, –) PE - connections 67 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 Terminals - sub central CPUS B Address: N N L L Í Î Í Î Mains NNL+ L+ Î Î Circuit 1 Circuit ref. Control module 7/1 N NL+ L+ Î Î Circuit 2 Circuit ref. Control module 7/2 N NL+ L+ Î Î Circuit 3 Circuit ref. Control module 8/1 N NL+ L+ Î Î Circuit 4 Circuit ref. Control module 8/2 N NL+ L+ Î Î Circuit 5 Circuit ref. Control module 9/1 N NL+ L+ Î Î Circuit 6 Circuit ref. Control module 9/2 B B +24V + 24V ⊥ ⊥ Í Î Í Î Í Î BUS-connections Batt. + Batt. + Batt. Batt. - Í Î Í Î Battery-supply Sub-station (+, –) PE PE PE PE PE 708 001 C 2 Throughwiring to further sub-stations (L, N, PE) Throughwiring to further CPUS-B (+, –) PE - connections 68 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 Terminals - sub central CPUS B Address: N N L L Í Î Í Î Mains NNL+ L+ Î Î Circuit 1 Circuit ref. Control module 10/1 N NL+ L+ Î Î Circuit 2 Circuit ref. Control module 10/2 N NL+ L+ Î Î Circuit 3 Circuit ref. Control module 11/1 N NL+ L+ Î Î Circuit 4 Circuit ref. Control module 11/2 N NL+ L+ Î Î Circuit 5 Circuit ref. Control module 12/1 N NL+ L+ Î Î Circuit 6 Circuit ref. Control module 12/2 B B +24V + 24V ⊥ ⊥ Í Î Í Î Í Î BUS-connections Batt. + Batt. + Batt. Batt. - Í Î Í Î Battery-supply Sub-station (+, –) PE PE PE PE PE 708 001 C 3 Throughwiring to further sub-stations (L, N, PE) Throughwiring to further CPUS-B (+, –) PE - connections 69 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 Terminals - sub central CPUS B Address: N N L L Í Î Í Î Mains NNL+ L+ Î Î Circuit 1 Circuit ref. Control module 13/1 N NL+ L+ Î Î Circuit 2 Circuit ref. Control module 13/2 N NL+ L+ Î Î Circuit 3 Circuit ref. Control module 14/1 N NL+ L+ Î Î Circuit 4 Circuit ref. Control module 14/2 N NL+ L+ Î Î Circuit 5 Circuit ref. Control module 15/1 N NL+ L+ Î Î Circuit 6 Circuit ref. Control module 15/2 B B +24V + 24V ⊥ ⊥ Í Î Í Î Í Î BUS-connections Batt. + Batt. + Batt. Batt. - Í Î Í Î Battery-supply Sub-station (+, –) PE PE PE PE PE 708 001 C 4 Throughwiring to further sub-stations (L, N, PE) Throughwiring to further CPUS-B (+, –) PE - connections 70 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 Terminals - sub central CPUS B Address: N N L L Í Î Í Î Mains NNL+ L+ Î Î Circuit 1 Circuit ref. Control module 16/1 N NL+ L+ Î Î Circuit 2 Circuit ref. Control module 16/2 N NL+ L+ Î Î Circuit 3 Circuit ref. Control module 17/1 N NL+ L+ Î Î Circuit 4 Circuit ref. Control module 17/2 N NL+ L+ Î Î Circuit 5 Circuit ref. Control module 18/1 N NL+ L+ Î Î Circuit 6 Circuit ref. Control module 18/2 B B +24V + 24V ⊥ ⊥ Í Î Í Î Í Î BUS-connections Batt. + Batt. + Batt. Batt. - Í Î Í Î Battery-supply Sub-station (+, –) PE PE PE PE PE 708 001 C 5 Throughwiring to further sub-stations (L, N, PE) Throughwiring to further CPUS-B (+, –) PE - connections 71 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 Terminals - sub central CPUS B Address: N N L L Í Î Í Î Mains NNL+ L+ Î Î Circuit 1 Circuit ref. Control module 19/1 N NL+ L+ Î Î Circuit 2 Circuit ref. Control module 19/2 N NL+ L+ Î Î Circuit 3 Circuit ref. Control module 20/1 N NL+ L+ Î Î Circuit 4 Circuit ref. Control module 20/2 N NL+ L+ Î Î Circuit 5 Circuit ref. Control module 21/1 N NL+ L+ Î Î Circuit 6 Circuit ref. Control module 21/2 B B +24V + 24V ⊥ ⊥ Í Î Í Î Í Î BUS-connections Batt. + Batt. + Batt. Batt. - Í Î Í Î Battery-supply Sub-station (+, –) PE PE PE PE PE 708 001 C 6 Throughwiring to further sub-stations (L, N, PE) Throughwiring to further CPUS-B (+, –) PE - connections 72 INOTEC Sicherheitstechnik GmbH 29.08.2007 Installation and maintenance manual for central power supply system CPS 220 Terminals - sub central CPUS B Address: N N L L Í Î Í Î Mains NNL+ L+ Î Î Circuit 1 Circuit ref. Control module 22/1 N NL+ L+ Î Î Circuit 2 Circuit ref. Control module 22/2 N NL+ L+ Î Î Circuit 3 Circuit ref. Control module 23/1 N NL+ L+ Î Î Circuit 4 Circuit ref. Control module 23/2 N NL+ L+ Î Î Circuit 5 Circuit ref. Control module 24/1 N NL+ L+ Î Î Circuit 6 Circuit ref. Control module 24/2 B B +24V + 24V ⊥ ⊥ Í Î Í Î Í Î BUS-connections Batt. + Batt. + Batt. Batt. - Í Î Í Î Battery-supply Sub-station (+, –) PE PE PE PE PE 708 001 C 7 Throughwiring to further sub-stations (L, N, PE) Throughwiring to further CPUS-B (+, –) PE - connections 73 INOTEC Sicherheitstechnik GmbH 29.08.2007