Lovely and flexible | Fan Coil Units
GEA Flex-Geko
®
Solutions for all demands | Basic and Comfort
[21 °C]
32 dB(A)
Air Treatment
GEA Flex Fan Coil Units Heating, cooling, and ventilating –
fast and efficiently
Unlike radiators and classical flat radiators, fan coil units not
only can heat rooms, but can also cool and ventilate them.
With 2-litre units, seasonal switch-over from heating to cooling
operations is possible, and vice-versa (by reversing the medium
supply). The 4-litre units additionally offer connections for heating and cooling circulation systems, and therefore allow spontaneous change-over between the modes of operation.
Fan coil units actively direct the air to be treated through the
heat exchanger, with especially effective heating or cooling. They
bring room air to the desired temperature faster and operate
with smaller heating or cooling surfaces. Their enhanced heat
transfer enables lower feed temperatures during heating, and
higher feed temperatures during cooling. This minimises losses
and saves energy between the boiler or the chiller and the final
unit.
A choice of fan speeds, as well as valves to regulate the flow volume, enable flexible control of unit output. Adjustable air-outlet
grills, in addition, assure uniform distribution of temperatureComfortable climate-control solution:
controlled air in the room.
Heating and cooling in one unit
Test
e
6 02 2
VDI
(D)
units
e
d
Assuring desired room temperature with smaller
m-air hygie
o
n
ro
2
ted
by
I LH
RL
Te
s
01
104 -
IN
ene
i
g
y
of h VA
l
a
e
I
S
S W K ( CH )
Energy saving with lower feed temperatures
during heating, and with higher temperatures for
cooling
Flexible control
Recirculated-air units in accordance with VDI
6022
BE
PR-2008-0305-GB • We reserve the right to make changes without notice • Version: 09/2008
Our models in the Basic and Comfort Editions
The right version for
every requirement
The GEA Flex fan coil units are available in the Basic and Comfort Editions. Both of these variations are based on the same
equipment platform, and employ this platform with various system components. This enables numerous equipment configurations.
Purity and timeless design – the Basic variation
The Basic Edition model, with modest grey-white enclosure, contains high-quality technology and offers (according to version)
connections for hot and/or cold water, a three-speed fan, and an
air filter. Various valve types allow coordinated and precise heating and cooling. With its extremely user-friendly control system,
the GEA Flex fan coil unit is therefore the perfect starter model
for comfortable, decentral climate control of your rooms.
Greater expectations in many variations –
the Comfort Edition
The basic edition of the GEA Flex fan coil unit offers
reliable technology for many applications. This starter unit
is well suited for user-friendly heating and/or cooling, and
can be combined with various accessory components.
The Comfort Edition of the GEA Flex offers additional functions
and more features. It enables climate control of rooms in mixedair operation, and treatment of the air with finer filters. According
to the requirements, Comfort units offer hot and/or cold water connections. They can be equipped with additional electrical heating,
and with an integrated direct evaporator – which allows a combination with outdoor split-climate units. The enclosure is designed
for various air-intake and -outlet variations, and a light-grey band
makes the unit optically even slimmer.
Installation sizes and diversity of performance
Both GEA Flex variants, Basic and Comfort, are available in 8 installation sizes with a height beginning at 504 mm, and a uniform depth of 240 mm. The width will vary according to output,
between 840 and 1,890 mm. The 8 unit sizes allow a selection
that optimally matches the required output. The heating and
The Comfort Edition, with its distinctive light-grey band,
can climate-control rooms in mixed-air operation as well. It
can be equipped with an additional electrical heater if
required. Its various air-intake and -outlet directions
guarantee flow-optimised airflow routing for all applications.
cooling output ratings lie between 1 and 20 kW*. The circulating air volume coordinated to these output ratings varies between 150 and 1,800 m³/h.
* Heating: pumped hot water, 70/50°C, tL1 +20°C
* Cooling: pumped cold water, 6/12°C, tL1 +27°C, 46% relative humidity
PR-2008-0305-GB • We reserve the right to make changes without notice • Version: 09/2008
3
Equipped for virtually every use
With GEA Flex fan coil units, you can
flexibly plan for every application
As a result of their modular concept, GEA Flex fan coil units
can be employed for many and various applications. These
models are effective with wall or ceiling installation. They
function highly satisfactorily on a stand-alone basis with enclosure, or can be mounted virtually invisibly as base units,
with the required air outlets, behind a wall or above a suspended ceiling. The GEA MATRIX control system, integrated
as desired, adapts to each and every functionality. The operator control units – with or without integrated timer switches
– provide the interface to the user. The control units can be installed in the units themselves, or externally.
Satisfies virtually all requirements:
Flex units with primary-air connection can be easily combined
with a central ventilation system. The control interfaces likewise
Flexible setup and installation variations
allow uncomplicated integration into the building-services man-
Integration possible behind walls or above
agement system.
suspended ceilings
The GEA MATRIX control system, adapted to
the required functionalities
rooms, and public facilities. Prominent hotel chains use them
Integration into the building-services management system via various interfaces
4
gladly owing to their quiet and reliable operation. With their
cost-effective operation and flexible application possibilities,
Combination with other fan coil units or GEA
products
GEA Flex fan coil units heat, cool, and ventilate offices, sales
GEA Flex fan coil units set standards for advanced climate-control solutions.
PR-2008-0305-GB • We reserve the right to make changes without notice • Version: 09/2008
Wall and ceiling models
Basic Edition
Already with the Basic Edition of GEA
Flex fan coil units, the most common requirements for climate control of rooms
can be quietly and reliably satisfi ed.
These robust units are highly effective
for typical flush-mounted applications.
The Basic Edition has been designed for
heating or cooling in recirculated-air
Only recirculated-air operation
mode. It is effective for all applications for
Basic model shown here:
which a standard flush-mounted situation
– without enclosure
exists: for example, under windows. The
– ceiling version
horizontal ceiling installation is ideally
– four-pipe system
suited, for example, for shops, workshops,
– valves mounted
and other rooms where floor space is at a
premium.
Wall and ceiling models
Comfort Edition
The Comfort Edition of GEA Flex fan coil
units satisfies requirements, for example,
in which mixed-air options are desired –
or where quiet heating and cooling are expected. They are also ideally suited for
cases in which exceptional installation situations prevail.
The many possible intake- and outlet-air
combinations, and the extremely quiet
fans, mean that Comfort Edition models
are something special. The possibility of
ordering these models with mixed-air operation, and/or with electrical heating, expands their application spectrum. In adRecirculated- or mixed-air operation
dition, the great diversity of accessories
Basic mixed-air model shown here:
and the availability of various control
– without enclosure
modules all mean that the Comfort Edi-
– wall version
tion satisfies practically all situations.
– four-pipe system
– valves mounted
PR-2008-0305-GB • We reserve the right to make changes without notice • Version: 09/2008
5
Whether at home, at work, or in a hotel: GEA fan coil units
reliably assure feel-good room climate. High-performance fans
take the room quickly to the desired temperature, and quietly
maintain it at the required level.
Basic or Comfort > the requirement decides
[One equipment platform] [8 installation sizes] [2- and 4-pipe systems]
[150 – 1,800 m³/h] [1 – 20 kW]
[Heating, cooling, and ventilation]
With high-performance functions for feel-good climate
6
PR-2008-0305-GB • We reserve the right to make changes without notice • Version: 09/2008
GEA Flex Fan Coil Units
Enclosures
1
Air intake on the narrow side; air outlet on the narrow
side. For recirculated-air operation with wall or ceiling
installation. Free air suction required approx. 10 cm
from the building. Without feet.
Air intake on the narrow side; air outlet on the front
side. For recirculated-air operation with wall or ceiling
installation. Free air suction required approx. 10 cm
1
from the building. Without feet.
Air intake on the front side; air outlet on the narrow
side. For recirculated-air operations with wall, ceiling,
or floor installation. For setup open in the room: with
optional back wall or narrow-side cover panel.
Intake-air opening with grill integrated into the
enclosure. Without feet.
4
Air intake on the front side; air outlet on the front side.
For recirculated-air operations with wall, ceiling, or
4
floor installation. Intake-air opening with grill
integrated into the enclosure. Without feet.
5
Air intake on the front side; air outlet on the narrow
side. For recirculated-air operations with wall, ceiling,
or floor installation. With feet – intake-air opening
without grill.
6
Air intake on the front side – air outlet on the front
side. For recirculated-air operations with wall, ceiling,
5
or floor installation. With feet. Intake-air opening
6
without grill.
7
Air intake on the front side – air outlet on the narrow
side. For recirculated- or mixed-air operations with
wall, ceiling, or floor installation. With feet. Mixed-air
intake opening integrated with grill. Intake of outside
air on the rear side, without grill.
8
Air intake on the front side – air outlet on the front
side. For recirculated- or mixed-air operations with
7
wall, ceiling, or floor installation. With feet. Mixed-air
8
intake opening integrated with grill. Intake of outside
air on the rear side, without grill.
4
1
5
6
7
PR-2008-0305-GB • We reserve the right to make changes without notice • Version: 09/2008
8
7
GEA MATRIX – intelligent control technology
Just the right turn for
the right room climate
If requested as option, the proven GEA MATRIX control unit will
be integrated into the GEA Flex fan coil units at the factory. Your
benefit: only completely tested equipment will be supplied to
your construction site.
GEA MATRIX is available in configuration levels 500, 2000, 3000,
or 4000, with adaptation to the various possible applications. A version can be supplied for hotel applications, for example: as well as
Comprehensive control possibilities:
a Basic version for cost-optimised budgets.
Control functions in various expansion stages
Most of the versions are provided as default with the two-cable GEA
Bus interfaces to other equipment units
MATRIX dual-cable bus system, through which all GEA MATRIX
Plug-and-play functionality
units can communicate with each other. As a result, it is simple to
Energy-optimised equipment operation
implement daytime and nighttime switching actions, or to control
Equipment ready to operate
pumps and collect error messages at a single point. GEA MATRIX
Highly competent service
can also be connected to higher-level bus systems.
Global add-on modules
LON interface
In addition, GEA MATRIX assures energy-optimized operation of
Service tool
GEA Flex fan coil units. A coordinated switch-over function, for
example, prevents heating and cooling circulation systems from
working against each other. By means of the summer compensation function, GEA MATRIX takes outside-temperature influences into account and prevents energy-intensive climate control.
Hardware and software are developed entirely at GEA. As a result
of close collaboration in the company, GEA engineers can systematically adjust the control system to match every component – and
in turn optimally exploit the possibilities of the fan coil units. GEA
support staff also profit from this arrangement by being able to
quickly and expertly react in case of any questions.
Numerous additional global modules are available as function expansions of the standard local connections. Examples here are: intra-group GEA MATRIX control units and clock modules, modules
for activation control of exhaust-air fans and chillers, expansion of
analogue or digital input and output signals, 0 … 10-V outputs for
valves, and integration into a LON bus system in accordance with
the LonWorks standard.
Starting with MATRIX 2000, all modules can be simply integrated
via the MATRIX.Net bus system. In addition, the service tools
MATRIX.PDA and MATRIX.PC can be used for parameterisation,
facility commissioning, maintenance, and data recording from the
MATRIX control system.
8
PR-2008-0305-GB • We reserve the right to make changes without notice • Version: 09/2008
Control unit for MATRIX 500
Control unit for MATRIX 2000
MATRIX OP5
MATRIX OP21
– Enclosure without display, pure white
– Recirculated-air mode,
IP 20 protection class
– D esired-temperature setting
– Fan-speed selection for permanent duty
– Button for temperature-reduction mode
– L ED for operation/malfunction/ext. influence
–Integrated room-temperature sensor
Same as the OP5 control unit, but with:
– Fan-speed selection switch for
permanent / automatic operation
– M ATRIX.Net data bus
Network connection for MATRIX
add-on modules via OP21 control unit
Control units for MATRIX 3000 and MATRIX 4000
MATRIX OP30 without buttons
MATRIX OP31 with temp.-reduction button
MATRIX OP44
– Enclosure without display, pure white
Same as the OP31 control unit, but with:
– Recirculated-air, IP 20 protection class
– S election switching for heating / cooling /
automatic operation
– D esired-temperature setting
– Fan-speed selection switch for permanent /
automatic operation
– L ED for operation/malfunction/ext. influence
– I ntegrated room-temperature sensor
– S election switching for recirculated-air /
mixed-air modes of operation
All units without display. Protective hood as
option.
MATRIX OP50 without clock
MATRIX OP51 with clock
MATRIX.IR infrared remote control unit
– Enclosure without display, pure white
– IP 20 enclosure protection class
– Functions as for the OP44 control unit, but:
Without operational/malfunction reports
Without report of external influence
Without integrated room sensor
– Operation by rotary navigator
– Black enclosure, similar to RAL 9004
– LCD display with plain text
– LCD display, 45 x 30 mm
– Status report by pictograms
– Effective range = approx. 20 m
– Recirculated-air / mixed-air modes of operation
– Integrated room-temperature sensor
GEA thermostat / compact switch units
CMS / CMT / CET series: extremely simple control units are also available for minimal control-function requirements
(for systems based on pumped hot water and pumped cold water). PR-2008-0305-GB • We reserve the right to make changes without notice • Version: 09/2008
9
Overview of systems and performance ratings
Basic Edition
Installed sizes Fan speeds 1 - 2 - 3
1 ... 8 Recirculated air Typ
Performance rating
GEA Flex-Geko
Air
flow
in m3 / h Heating rating
in kW Cooling
rating
in kW
min | max
min | max
min | max
Pumped hot water / pumped cold water
Heating with pumped hot water
U0W
Cooling with pumped cold water
1
UW0
Cooling with pumped cold water or heating
with pumped hot water (change over)
UWC
Cooling with pumped cold water and heating
with pumped hot water (4-pipe system)
UWW
180 | 1800
1 2.0 | 19.5
180 | 1800
1.1 | 10.7
180 | 1800
2.0 | 19.5
1.1 | 10.7
175 | 1780
0.7 | 7.0
1.1 | 9.1
Installed sizes 1 ... 8 Air
flow
in m3 / h Heating
rating
in kW Cooling
rating
in kW
Performance rating
min | max
min | max
min | max
1
1
See pages 12 and 13 for the output ratings in the individual fan-speed levels.
Comfort-Edition
Fan speeds 1 - 2 - 3
Recirculated air / mixed air
Typ
Pumped hot water / pumped cold water
Heating with pumped hot water
U0W / M0W
Cooling with pumped cold water
1
UW0 / MW0
Cooling with pumped cold water or heating
with pumped hot water (change over)
UWC / MWC
Cooling with pumped cold water and heating
UWW / MWW
with pumped hot water (4-pipe system)
150 | 1820
1 1
1
1.7 | 19.6
150 | 1820
1.0 | 10.8
150 | 1820
1.7 | 19.6
1.0 | 10.8
145 | 1800
0.6 | 7.2
1.0 | 9.1
270 | 1820
2.1 | 12.4
Pumped hot water / pumped cold water / electrical heating
Electrical heating
U0E / M0E
1 Heating with pumped hot water + 1
U0F / M0F
220 | 1820
electrical booster heating
2.3 | 18.1
0.9 | 4.1
Cooling with pumped cold water or heating UWB / MWB
220 | 1820
1
with pumped hot water + electrical heating
2.3 | 18.1
0.9 | 4.1
1.2 | 9.6
Cooling with pumped cold water and heating with electrical heating
220 | 1820
0.9 | 4.1
1.2 | 9.6
Cooling and heating with cold and hot water
UWF
1
215 | 1800
(4-pipe system) + electrical heating
(only recirculated air)
0.9 | 7.2
0.9 | 4.1
1.2 | 7.6
UWE / MWE
1
Refrigerant: R410A / pumped hot water
Cooling with R410A refrigerant
1
UD0 / MD0
Cooling with R410A refrigerant and 1
UDW / MDW
heating with pumped hot water
270 | 1820
1.2 | 7.1
270 | 1800
1.0 | 4.9
1.0 | 7.2
Heating with pumped hot water: 70/50°C, tL1 +20°C;
cooling with pumped cold water: 6/12°C, tL1 +27°C, 46% relative humidity; refrigerant: R410A, to +10°C ·
See page 11 for data on the sound emission
*The “U”s in the “Type” column above stand for recirculated air. “M” stands for mixed air
10
PR-2008-0305-GB • We reserve the right to make changes without notice • Version: 09/2008
GEA Flex-Geko
Noise emission in dB(A)
Basic Edition – installed sizes
Fan speeds 1 - 2 - 3
1
2
3
4
5
6
7
8
m3 / h
180
190
330
380
400
520
570
590
Acoustic power level
Lw
33
33
33
35
35
36
36
36
Acoustic pressure level* Lp *
24
24
24
26
26
27
28
27
m3 / h
260
290
490
540
560
740
790
940
Acoustic power level
Lw
41
43
44
44
44
44
45
45
Acoustic pressure level* Lp *
33
34
35
35
35
35
36
37
m3 / h
490
520
860
960
990
1310
1410
1800
Acoustic power level
Lw
57
57
59
60
60
62
62
63
Acoustic pressure level* Lp *
48
49
51
51
51
54
53
54
3
4
5
6
7
8
300
430
460
590
At air flow of:
At air flow of:
At air flow of:
Fan speed 1
Fan speed 2
Fan speed 3
Comfort Edition – installed sizes
1
2
Fan speeds 1 - 2 - 3 - 4 - 5
At air flow of:
Fan speed 1
m3 / h
150
160
280
290
Acoustic power level
Lw
<30
<30
30
<30
<30
33
33
34
Acoustic pressure level* Lp *
21
<20
21 20
<20
24
24
25
m3 / h
270
280
470
490
520
750
770
970
Acoustic power level
Lw
42
42
43
41
42
46
46
46
Acoustic pressure level* Lp *
33
33
34
32
34
38
38
37
m3 / h
530
540
890
990
1010
1310
1420
1820
Acoustic power level
Lw
58
58
59
58
59
62
62
61
Acoustic pressure level* Lp *
50
49
51
50
51
54
53
53
At air flow of:
At air flow of:
Fan speed 3
Fan speed 5
* Conditions for measurement of acoustic pressure level Lp:
Measuring interval = 5 m. Room volume = 100 m³. Reverberation period = 0.5 s. Directional factor = 4 (quarter-sphere sound emission)
PR-2008-0305-GB • We reserve the right to make changes without notice • Version: 09/2008
11
Performance ratings
Basic Edition
1
Capacity stage
Basic Edition
Installed size
1
Min. fan-speed level = 1 2
3
4
5
6
7
8
2 pipes
Air flow
m3 / h
180
190
330
380
400
520
570
590
Heating
U0W / UWC
kW
2.0
2.3
3.6
4.3
4.7
5.6
6.3
6.8
Cooling UW0 / UWC
kW
1.1
1.2
1.9
2.4
2.7
3.0
3.4
3.7
4 pipes
Air flow
m3 / h
175
185
325
370
390
515
565
585
Heating
UWW
kW
0.7
1.1
1.8
2.3
2.5
3.2
3.7
3.9
Cooling
UWW
kW
1.1
1.2
2.0
2.4
2.5
3.3
3.7
3.8
1310
1410
1800
10.5
11.6
14.3
5.2 5.9
7.2
Max. fan-speed level = 3
2 pipes
Air flow
m3 / h
490
520
860
960
990
Heating
U0W / UWC
kW
3.8
4.6
6.7
7.9
8.8
Cooling UW0 / UWC
kW
1.9
2.3
3.4
4.1
4.6
4 pipes
Air flow
m3 / h
485
515
850
945
975
1300
1395
1780
Heating
UWW
kW
1.4
1.9
3.0
3.7
4.2
5.3
5.9
7.1
Cooling
UWW
kW
1.9
2.2
3.5
4.2
4.4
5.7
6.3
7.2
7
8
Basic Edition
2
Capacity stage
Installed size
1
Min. fan-speed level = 1 2
3
4
5
6
2 pipes
Air flow
m3 / h
175
185
325
370
390
515
565
585
Heating
U0W / UWC
kW
2.2
2.6
4.2
5.0
5.4
6.7
7.4
7.9
Cooling UW0 / UWC
kW
1.2
1.5
2.3
2.8
3.2
3.5
4.1
4.5
4 pipes
Air flow
m3 / h
170
185
310
345
370
500
545
570
Heating
UWW
kW
0.9
1.2
1.9
2.2
2.5
3.0
3.4
3.7
Cooling
UWW
kW
1.1
1.4
2.1
2.6
2.9
3.3
3.7
4.1
1300
1395
1780
13.1 14.6 17.9
6.8 7.7
Max. fan-speed level = 3
2 pipes
Air flow
m3 / h
485
515
850
945
975
Heating
U0W / UWC
kW
4.7
5.6
8.5
9.9 10.8
Cooling UW0 / UWC
kW
2.4
3.1
4.4
5.4
4 pipes
Air flow
m3 / h
470
505
815
890
920
1255
1350
1700
Heizen
UWW
kW
1.6
2.2
3.3
3.9
4.4
5.1
5.8
7.0
Cooling
UWW
kW
2.2
2.9
4.2
5.0
5.6
6.4
7.3
9.1
7
8
Basic Edition
3
Capacity stage
Installed size
1
Min. fan-speed level = 1 6.0 2
3
4
5
6
9.6
2 pipes
Air flow
m3 / h
170
185
310
345
370
500
545
570
Heating
U0W / UWC
kW
2.4
2.6
4.4
5.0
5.4
6.8
7.6
8.1
Cooling UW0 / UWC
kW
1.3
1.5
2.5
2.9
3.3
3.5
4.1
4.6
890
920
1255
1350
1700
14.3 15.8 19.5
7.6 8.6 10.7
Max. fan-speed level = 3
2 pipes
Air flow
m3 / h
470
505
815
Heating
U0W / UWC
kW
5.2
6.0
9.4
Cooling UW0 / UWC
kW
2.9
3.3
5.2
10.6
11.6
6.0
6.5 Heating with pumped hot water: 70/50°C, tL1 +20°C; cooling with pumped cold water: 6/12°C, tL1 +27°C, 46% relative humidity
12
PR-2008-0305-GB • We reserve the right to make changes without notice • Version: 09/2008
Comfort Edition Comfort Edition
1
Capacity stage
Performance ratings
Installed size
1
Min. fan-speed level = 1 2
3
4
5
6
7
8
2 pipes
Air flow
m3 / h
150
160
280
290
300
430
460
590
Heating
U0W / UWC
kW
1.7
2.0
3.2
3.5
3.7
4.9
5.4
6.8
Cooling UW0 / UWC
kW
1.0
1.1
1.7
2.0
2.1
2.6
2.9
3.7
4 pipes
Air flow
m3 / h
145
155
275
285
295
425
455
575
Heizen
UWW
kW
0.6
1.0
1.7
1.9
2.1
2.9
3.2
3.9
Cooling
UWW
kW
0.9
1.0
1.8
2.0
2.0
2.8
3.2
3.7
Max. fan-speed level = 5
2 pipes
Air flow
m3 / h
530
540
890
990
1010
1310
1420
1820
Heating
U0W / UWC
kW
3.9
4.7
6.8
8.1
8.8 10.5 11.7 14.4
Cooling UW0 / UWC
kW
2.0
2.4
3.4
4.1
4.7 5.2 5.9 7.3
4 pipes
Air flow
m3 / h
525
535
880
980
1000
1295
1405
1800
Heating
UWW
kW
1.4
2.0
3.1
3.7
4.2
5.3
5.9
7.2
Cooling
UWW
kW
2.0
2.3
3.5
4.3
4.5
5.7
6.4
7.3
7
8
Comfort Edition
2
Capacity stage
Installed size
1
Min. fan-speed level = 1 2
3
4
5
6
2 pipes
Air flow
m3 / h
145
155
275
285
295
425
455
575
Heating
U0W / UWC
kW
1.9
2.2
3.7
4.0
4.3
5.7
6.2
7.8
Cooling UW0 / UWC
kW
1.0
1.3
2.1
2.3
2.6
3.0
3.5
4.4
4 pipes
Air flow
m3 / h
145
155
265
280
290
415
445
545
Heating
UWW
kW
0.8
1.0
1.7
2.0
2.1
2.7
3.0
3.6
Cooling
UWW
kW
1.0
1.2
1.9
2.2
2.4
2.7
3.1
4.0
Max. fan-speed level = 5
2 pipes
Air flow
m3 / h
525
535
880
980
1000
Heating
U0W / UWC
kW
5.0
5.8
8.8 10.1 11.0
Cooling UW0 / UWC
kW
2.5
3.1
4.5 5.5 6.1
4 pipes
Air flow
m3 / h
510
525
845
950
Heating
UWW
kW
1.7
2.2
3.3
4.0
4.5
5.1
5.8
7.0
Cooling
UWW
kW
2.3
3.0
4.3
5.2
5.8
6.4
7.4
9.1
7
8
Comfort Edition
3
Capacity stage
Installed size
1
Min. fan-speed level = 1 2
3
4
1295
975
13.1
1405
6.8 1245
14.6 18.1
7.8 9.6
1360
5
6
1800
1710
2 pipes
Air flow
m3 / h
145
155
265
280
285
415
445
545
Heating
U0W / UWC
kW
2.0
2.2
3.8
4.1
4.3
5.7
6.4
7.7
Cooling UW0 / UWC
kW
1.2
1.3
2.2
2.4
2.6
3.1
3.4
4.4
Max. fan-speed level = 5
2 pipes
Air flow
m3 / h
510
525
845
950
970
1245
1360
1710
Heating
U0W / UWC
kW
5.5
6.2
9.6 11.1 12.0 14.2 15.9
19.6
Cooling UW0 / UWC
kW
3.0
3.4
5.3 6.2 6.7 7.6 8.7
10.8
Heating with pumped hot water: 70/50°C, tL1 +20°C; cooling with pumped cold water: 6/12°C, tL1 +27°C, 46% relative humidity.
Models with different output ratings are available upon request for systems with electrical heating and direct evaporators.
PR-2008-0305-GB • We reserve the right to make changes without notice • Version: 09/2008
13
Base units – dimensions and weights (mass)
Recirculated air
mm
Comfort
Mixed air
mm
mm
Height
Height
Width
1
470
596
2
470
3
GEA Flex-Geko
mm
Basic
weight
kg
Comfort
weight
kg
Depth
Max
Max
761
225 ... 237
13
18
596
911
225 ... 237
14
22
470
596
1061
225 ... 237
18
27
4
470
596
1211
225 ... 237
21
32
5
470
596
1361
225 ... 237
24
36
6
470
596
1511
225 ... 237
28
42
7
470
596
1661
225 ... 237
30
46
8
470
596
1881
225 ... 237
35
52
Installation
sizes
Wall units
225
471
Recirculated air – Basic and
Comfort
225 (228**)
35
108
471
125
Mixed air – Comfort Edition
The dimensions of the recirculated-air unit with 125-mm supporting feet are the same as those of the mixed-air
unit.
Enclosures – dimensions and weights (mass)
Recirculated air
mm
Comfort
Mixed air
mm
mm
Basic
weight
kg
Comfort
weight
kg
mm
Height
Height
Width
Depth
Max
Max
1
504
629
840
240
9
9
2
504
629
990
240
10
10
3
504
629
1140
240
11
11
4
504
629
1290
240
12
12
5
504
629
1440
240
13
13
6
504
629
1590
240
14
14
7
504
629
1740
240
15
15
8
504
629
1890
240
16
16
Installation
sizes
Enclosures
Basic and Comfort Editions
Recirculated-air wall unit
240
1
504
Without feet; without intakeair grill
240
5
504
629
125
The dimensions of the recirculated-air unit with 125-mm supporting feet are the same as those of the mixed-air
unit.
With feet; without intake-air
grill
240
7
504
104
629
125
With feet; with intake-air grill
Enclosures
Comfort Edition
Enclosures
Comfort Edition
Recirculated-air wall unit
4
240
Mixed-air wall unit
240
6
120
240
7
240
8
120
120
504
504
92
504
629
629
125
125
Without feet; with intake-air grill
in the enclosure
14
104
With feet; without intake-air grill
With feet; with intake-air grill
Air outlet on narrow side
504
104
629
125
With feet; with intake-air grill
Air outlet on front side
PR-2008-0305-GB • We reserve the right to make changes without notice • Version: 09/2008
GEA Flex-Geko Enclosures without supporting feet
Intake-air and outlet-air variations
Wall and ceiling models
Comfort
•
I Basic
Δ RecirculatedO utlet-air grill O utlet-air grill
air-units
of plastic of aluminium
For views, see page 7
Adjustable Not adjustable
Intake narrow side | Outlet narrow side
1
4
Intake narrow side | Outlet front side
2
Intake front side
| Outlet narrow side
3
Intake front side | Outlet front side
4
Intake front side | Outlet narrow side | With cover panel
3
Intake front side | Outlet narrow side | With rear-wall panel
3
Enclosures with supporting feet
Intake-air and outlet-air variations
Wall and ceiling models
Comfort
•
I Basic
Δ Mixed-air RecirculatedO utlet-air grill O utlet-air grill
units
air-units
of plastic of aluminium
For views, see page 7
Adjustable Not adjustable
5
Intake front side | Outlet narrow side | Without intake grill
Intake front side | Outlet front side 6
| Without intake grill
7
Intake front side | Outlet narrow side | With intake grill
Intake front side
| Outlet front side 8
| With intake grill
Accessories
Accessories
Air-intake side
Wall and ceiling models
Comfort
•
I Basic
Outlet-air side
Wall and ceiling models
Δ
Comfort
•
I Basic
Δ
Intake-air box with primary-air fittings
Outlet-air box with primary-air fittings, not insulated
Intake-air box with round intake fittings
Outlet-air box with primary-air fittings, insulated
DN 200 enclosure cover for round fittings
Outlet-air box with round outlet-air fittings, not insulated
Intake-air bend
Outlet-air box with round outlet-air fittings, insulated
Intake-air sailcloth fittings
DN 200 enclosure cover for round fittings
Connection piece for intake-air sailcloth fittings
Air-outlet bend, not insulated
Intake-air telescopic fittings
Air-outlet bend, insulated
Intake-air noise suppressor for recirculated-air
Outlet-air sailcloth fittings
Intake-air noise suppressor for mixed-air units
Telescopic outlet-air fittings
Built-in wall frame for fresh-air fittings
Outlet-air noise-suppressor fittings
Weather-protection grill, RAL 9002, painted
Built-in wall frame for weather-protection grill
Spare filter, G1
Spare filter, G2, G3
Image brochure
Application brochures
Product brochures
Data & Facts and operation manuals
(available only as PDF)
You are on this level of our documentation structure. You can order at no charge
from the first 3 levels as printed copies, under:
[email protected].
You can download all brochures as PDF files from the following Internet site:
www.gea-airtreatment.com.
PR-2008-0305-GB • We reserve the right to make changes without notice • Version: 09/2008
15
Customer proximity, sales structures
Reachable always and everywhere!
GEA Happel Belgium N. V.
B-1130 Brussels
Tel. +32 / 2 / 2406161
D
EVISS Ltd.
BG-7000 Rousse
Tel . +359 / 82 / 81000
BIH GEA Klimatechnik
GmbH & Co KG
RS-11070 Novi Beograd
Tel. +381 / 11 / 3193955
BY
GEA Klimatechnik UAB
LT-01141 Vilnius
Tel. +370 / 5 / 2106060
CH ATC Klimatec Schweiz AG
CH-3065 Bolligen-Station
Tel. +41 / 31 / 9171919
CZ
GEA Klimatizace spol. s r.o.
CZ-46312 Liberec
Tel. +420 / 48 / 5225-303
D
GEA Happel
Klimatechnik GmbH
D-44625 Herne
Tel. +49 / 2325 / 468-00
D
D
GEA Happel
Wieland GmbH
D-44625 Herne
Tel. +49 / 2325 / 468-754
GEA Deichmann
Umwelttechnik GmbH
D-36179 Bebra
Tel. +49 / 6622 / 504-0
GEA Delbag-Luftfilter
Vertriebsgesellschaft mbH
D-10709 Berlin
Tel. +49 / 30 / 43592-3
DK
GEA Klimateknik ApS
DK-2610 Rødovre
Tel . +45 / 38 / 887070
E
GEA Air Treatment
Marketing Services Int.
GmbH – oficina España
E-28036 Madrid
Tel. +34 / 91 / 3837701
EST GEA Klimatechnik UAB
LT-01141 Vilnius
Tel. +370 / 5 / 2106060
F
GEA LVZ, a.s.
CZ-46312 Liberec
Tel. +420 / 48 / 5225-111
CZ
GEA Delbag
Lufttechnik GmbH
D-44625 Herne
Tel. +49 / 2325 / 468-700
F
GEA Delbag
Filtration de l‘air
F-77450 Montry
Tel. +33 / 1 / 60043355
GEA Happel France sarl
F-59436 Roncq Cedex
Tel. +33 / 3 / 20689020
FIN OY TEKNOCALOR AB
FIN-01300 Vantaa
Tel. + 358 / 10 / 8201100
GB
GEA Denco Ltd.
UK-HR4 8DS Hereford
Tel. +44 / 1432 / 277 277
H
HR
IE
GEA Klimatechnika Kft
H-1037 Budapest
Tel. +36 / 1 / 4393200
P
Nónio, Lda.
P-1269-090 Lisboa
Tel. +351 / 21 / 3826160
GEA Klima-rashladna
tehnika d.o.o.
HR-10000 Zagreb
Tel. +385 / 1 / 6064900
PL
GEA Klimatyzacja Sp. z o.o.
PL-54610 Wroclaw
Tel. +48 / 71 / 3737952
RO
GEA Klimatechnik s.r.l.
RO-300222 Timisoara
Tel. +40 / 356 / 423703
Aspect Environmental Ltd.
Ardee, Co. Louth Ireland
Tel. +353 / 41 / 6858983
IS
Rafn Jensson
IS-110 Reykjavik
Tel. +354 / 56 / 780-30
L
GEA Happel Luxembourg
L-4940 Bascharage
Tel. +352 / 26 / 502970
LT
LV
GEA Klimatechnik UAB
LT-01141 Vilnius
Tel. +370 / 5 / 2106060
GEA Klimatechnik UAB
LT-01141 Vilnius
Tel. +370 / 5 / 2106060
MWE GEA Klimatechnik
GmbH & Co KG
RS-110 70 Novi Beograd
Tel. +381 / 11 / 3193955
RUS GEA Klimatechnik
GmbH & Co KG
RU-105094 Moskva
Tel. +7 / 495 / 9566674
S
SK
GEA EXOS Ventilation AB
S-74528 Enköping
Tel. +46 / 171 / 85530
GEA Klimatizácia s.r.o.
SK-83104 Bratislava
Tel. +421 / 7 / 44457917
SLO GEA Klimatizacijska
Tehnika d.o.o.
SI-1000 Ljubljana
Tel. +386 / 1 / 2573850
SRB GEA Klimatechnik
GmbH & Co KG
RS-11070 Novi Beograd
Tel. +381 / 11 / 3193955
TR
N
GEA Klimaprodukter AS
N-0484 Oslo
Tel. +47 / 220 / 27990
NL
GEA Happel Nederland B.V. UA
NL-2909 LL
Capelle a/d Ijssel
UAE
Tel. +31 / 10 / 2350606
GEA ISISAN
TR-80700
Balmumcu Istanbul
Tel. +90 / 212 / 2757171
GEA Ukraina t.o.v.
UA-01135 Kyiv
Tel. +38 / 044 / 4619356
GEA Air Treatment
Middle East
UAE-Dubai
Tel. +971 / 4 / 887 3881
Test
e
ro
om
- a i r hy g
6022
ie
(D )
ne
d
The complete addresses are available on the
Internet under: www.gea-air-eco2nomy.com.
e
gien
of hy
Seal SWKI V(CAH)
VDI
Te
s
10 4-
ted
01
by
I LH
www.gea-air-eco2nomy.com
BE
PR - 2008-0305-GB • Subject to modification
Issue 09/2008 • Copyright GEA Air Treatment