Technical Manual UFM SP V5
Transcription
Technical Manual UFM SP V5
Technical Manual UFM SP V5 Promess Montage- und Prüfsysteme GmbH Nunsdorfer Ring 29 D-12277 Berlin Phone: +49 (0) 30 / 628872-0 Fax: +49 (0) 30 / 628872-59 Email : [email protected] www.promessmontage.de Copyright Copyright by Promess Montage- und Prüfsysteme GmbH Nunsdorfer Ring 29 D-12277 Berlin Federal Republic of Germany 2 1 Correct usage ......................................................................................................................................... 4 2 Transport ................................................................................................................................................. 5 3 Safety Measures ..................................................................................................................................... 5 3.1 Hazard Analysis ................................................................................................................................. 8 3.2 Safety of Electromechanical Joining Units ...................................................................................... 10 4 Loading the ram by torque and radial forces ....................................................................................11 5 Lubrication advice ................................................................................................................................13 6 6.1 6.2 6.3 6.4 Strain Gauge amplifier .........................................................................................................................15 Calibrating the Strain Gauge Amplifier ............................................................................................ 17 Strain Gauge Amplifier PDM-S (Digital) .......................................................................................... 18 Connectors PDM-S .......................................................................................................................... 19 LED Functions PDM-S ..................................................................................................................... 20 7.1 7.2 7.3 PROMESS Bus ......................................................................................................................................21 Bus Terminator. ............................................................................................................................... 22 Cable Shield Connections ............................................................................................................... 23 Node - Address ................................................................................................................................ 24 7 8 Software installation ............................................................................................................................26 9 Communication PC - Application module .........................................................................................26 Connection Ethernet module ........................................................................................................... 26 Ethernet Communication ................................................................................................................. 27 Assignment IP address Ethernet Module ........................................................................................ 29 Assign IP Adress PC ....................................................................................................................... 31 Assign IP Adress PC Windows 7 ..................................................................................................... 32 No Ethernet module found ............................................................................................................... 34 9.1 9.2 9.3 9.4 9.5 9.6 10 Firmware Update ..................................................................................................................................35 10.1 Version 5.00 to V5.2x ...................................................................................................................... 36 10.2 .............................................................................................................................................................. 39 From Version 5.03........................................................................................................................................ 40 11 Installation of CPR V4 Manager ..........................................................................................................44 11.1 COM Test......................................................................................................................................... 48 12 PLC Interface ........................................................................................................................................49 12.1 Reference motion after start-up ....................................................................................................... 49 12.2 Reference motion without a request ................................................................................................ 50 12.3 Cycle start ........................................................................................................................................ 50 12.4 Emergency Stop during a motion .................................................................................................... 51 12.5 Emergency Stop during standstill process ...................................................................................... 51 12.6 Cycle Stop........................................................................................................................................ 52 12.7 Transfer of program number ............................................................................................................ 53 Pos : 1 /UFM SP/UFM V5/T echnisc hes H B V5/Besti mmungsgemäße Ver wendung @ 0 \mod_1297249097588_71.doc x @ 2579 @ 1 @ 1 3 1 Correct usage The press unit is designed and built for assembly operation tasks, e. g. for pressing in bearings, absorbers and shafts or to press in and caulk seals. Operations, other than the above, may not be performed on the machine. The permissible loads are determined by the performance data of the unit and must not be exceeded by any larger extent. Avoid the following situations in particular: Abrupt loads at high positioning velocities - “collisions”, Forces under normal operations that exceed the nominal load by more than 110%, Excessive loads through unpredicted operational conditions, exceeding the nominal load by 100%. Pos : 2 /Sei tenumbr uch @ 0\mod_1133348983396_71.doc x @ 306 @ @ 1 4 Pos : 3 /UFM SP/UFM V5/T echnisc hes H B V5/Transport @ 0\mod_1297249030870_71.doc x @ 2571 @ 1 @ 1 2 Transport The units are supplied packaged in standard cases. The belt drive protection is not mounted to facilitate the use of lifting equipment when unpacking the unit. Please follow the instructions below to remove the unit: Use a broad double belt, placed under the motor plate and around the mounting flange, to unload the press unit. ATTENTION: Do not put any loads on the proximity and limit switches when attaching the lifting device! There is also the possibility of using an eyebolt, attached to the thread of the ball screw, to unload the press unit. After the unit has been unloaded, inspect it for visible transport damages. The press unit and related servo amplifier may only be installed in appropriate and suitable locations. In particular, please observe all protection regulations. Should you require information concerning requirements about the admissible locations, please contact the manufacturer. After the installation of the press unit, please make sure you comply with the manufacturer's specific measures before operation: Mount the belt protection, prior to connecting the power cable. Only use the power cables supplied. Assemble the power amplifier with the supplied filters and choking coils according to the power amplifier manual instructions. Make sure all cables are correctly installed. Avoid laying power and data cables next to each other. Pos : 4 /UFM SP/UFM V5/T echnisc hes H B V5/Sic her heit @ 0 \mod_1297248864825_71.doc x @ 2563 @ 12 @ 1 3 Safety Measures The joining unit may only be used for its intended purpose. Use of the joining unit for other purposes may cause injuries to operating personnel and damage to the unit. The safety requirements for joining applications must be defined by the machine manufacturer who determines the manufacturing concept – assembly line, standalone stations, automatic mounting, manual operation – together with the plant operator. Based on these requirements, the safety concept can be developed for the plant or parts thereof. The joining units are to be fitted with safety components – brakes, speed monitoring, versatile safety switches – and their integration into the safety concept is determined on the basis of the required plant functionality. It is forbidden to operate the units with the safety functionality bypassed. Should operators to occasionally or always be required to enter the hazardous area due to technical reasons, a safety concept must be developed for the plant with these considerations in mind. For joining units operated without brakes, the die weight must not exceed the limits defined by PROMESS. The permissible weights are given in the specifications. If larger weights are required for processing reasons, brakes must be implemented 5 for the unit. Standard brakes can be used in normal cases or specially dimensioned brakes for larger weights. Typical Installation Conditions The typical installation conditions are described below (four typical solutions are given, other variants are possible): Machines with permanent protective equipment: The units are installed in a protected workroom with permanent safety equipment and doors that are monitored and locked. Access to the hazardous area is only possible through the monitored and locked doors. PROMESS provides mounting plates with integrated emergency off switches to be integrated in this concept. By using appropriate emergency stop switches together with suitable locking elements for the doors, safety functionality can be achieved with PI = e. Machines with Light Curtain The hazardous area is to be protected by a light curtain. In this operating mode, the safety function “Safety stop after actuating emergencystop device” must have PI = d. PROMESS provides the required components to achieve this PI value as well as verification that this PI value has been achieved. Machines with two-hand actuation: The joining unit can be started using two-hand actuation. Systems with two-hand actuation require the same PI ratings as with machines with light curtains. The required equipment is provided by PROMESS. Machines without protective equipment: No special protective equipment is planned. In this rare case, the speed of the joining unit must be reliably limited to 10 mm/s. Damages resulting from inappropriate implementation of the required PI values will not be covered by PROMESS. The power amplifier may only be connected and started up by specially trained technicians. It is forbidden to switch off, bypass or remove the safety equipment. In particular, the protective hood of the belt drive may only be removed when the unit is disconnected from the power amplifier and fully de-energized. If the unit cannot be started due to technical faults or function problems in the protective equipment, the faulty component must be repaired or exchanged. It is strictly forbidden to operate the joining unit after the safety equipment has been manipulated and is no longer functioning properly. The unit may only be operated by personnel who have been instructed in its operation. If any faults occur during normal operation that cannot be eliminated using known and given strategies, technicians from the responsible departments must be informed. Before beginning any maintenance, repairs or troubleshooting work, the unit must be de-energized. 6 • • Set the main switch to “OFF” Remove the voltage plug Important! ANY SWITCHES IN THE “0” OR “CLOSED” POSITION MUST BE MARKED BY A WARNING SIGN. C AUT IO N: M AI NT E N ANC E, R E P AI R S AN D S ER V IC E W O R K UN DE RW AY , DO NO T SW IT CH O N ! If the unit has to be removed, first disconnect all of the power supplies. The PROMESS electromechanical joining unit can cause injury to operating personnel when not operated in the intended manner. Please observe the following guidelines: 7 1. 2. 3. 4. 5. 3.1 Never hold your hands in the work area The safety chain must be closed while operating the joining unit. Never operate the unit in areas where it is not intended to be used. Only authorized personnel is permitted to operate the unit. During repairs, support the die of the joining unit or drive the die to its lower stop. Hazard Analysis Risk assessment Frequency of exposition rare frequent Potential damages Probability of occurrence high 1 2 3 1 2 3 Countermeasures A B C D E F Category 1 Slight injuries, crushing or pinching of hand and fingers Category 2 Severe injuries, dismemberment of fingers, severe injuries to hand Category 3 Death Severe contusions to head 8 low Hazards from faulty functioning of mechanical elements Type of malfunction Possible injuries Guide: Wear, blockage after destruction None Axial bearing: Wear, destruction None Ball screw: Wear Destruction None Countermeasures Tearing of toothed belt After belt tears, brakes will not be able to stop die 1A 3F Category 1 and 10-fold safety against breakage under 2 normal operating conditions Release tooth wheel coupling 1A 3F Category 1 and The couplings are self-locking; thus, 2 loosening the screws will not release the coupling unless heavy vibrations or impacts occur at the machine Slippage of tooth wheel on Shaft, incorrect positioning, excessive force None Force sensor, destroyed from overloading None Cable breakage in force sensor None Cable breakage in limit switch None Cable breakage in motor resolver None Cable breakage in power cable None Pos : 5 /Sei tenumbr uch @ 0\mod_1133348983396_71.doc x @ 306 @ @ 1 9 Pos : 6 /UFM SP/UFM V5/T echnisc hes H B V5/Sic her heit el ektr omechanis cher F ügeeinhei ten @ 0\mod_1305792763628_71.doc x @ 2713 @ 2 @ 1 3.2 Safety of Electromechanical Joining Units The European Machinery Directive contains regulations pertaining to the safety of machines and plants that are valid throughout Europe. All of the standards and regulations relevant to this application are listed in Machinery Directive. • What is a machine? The Machinery Directive defines a machine as follows: “… an assembly of linked parts or components, at least one of which moves with the appropriate actuators, control and power circuits, etc. joined together for a specific application, in particular for the processing, treatment, moving or packaging of a material.” Thus, components and subassemblies are not machines: “An assembly of linked parts” is exempted from this application area when it is a component or a nearly finished machine (“quasi-machine”). (Source: Explanations 98-37-EU, chapter 58). Thus, the joining units from PROMESS are not machines but the stand-alone stations are. Responsibilities The safety requirements for the machine are to be defined by the machine manufacturer who determines the manufacturing concept – assembly line, standalone stations, automatic mounting, manual operation – together with the plant operator. Based on these requirements, the safety concept can be developed for the plant or parts thereof. The plant manufacturer is to stipulate the safety requirements of the various components to their respective suppliers and the suppliers are to describe which equipment is required to comply with these requirements. The component manufacturer is responsible for providing the safety equipment for the components as stipulated in the safety concept, providing verification of the PI values and providing the data required to calculate the PI values (MTTF,d, B 10 values, DC values etc.). To assist the machine manufacturer, PROMESS has defined the requisite safety equipment for typical machinery and safety concepts. Verification PROMESS is to provide proof of compliance with the regulations stipulated by the Machinery Directive in the DECLARATION OF INCORPORATION FOR PARTIALLY COMPLETED MACHINERY. PROMESS will provide a DECLARATION OF CONFORMITY for stand-alone stations. Pos : 7 /Sei tenumbr uch @ 0\mod_1133348983396_71.doc x @ 306 @ @ 1 10 Pos : 8 /UFM SP/UFM V5/T echnisc hes H B V5/Belas tbar kei t UFM @ 0\mod_1297248724102_71.doc x @ 2547 @ 1 @ 1 4 Loading the ram by torque and radial forces The ram can be loaded by torque and radial forces. The following spreadsheet shows in order of the press types the maximum allowable loads. The data for the radial forces are applies to a 50 % extended ram. When the ram is fully extended, the data has to be reduced by 50 %. In normal cases there are no excessive radial forces during press operations. However in cases of considerable misalignment or when these forces are generated by the process, radial forces might occur. (Example: testing of helical springs) Article Nr. UFM-Classic Force Max. allowable torque Max. allowable radial forces kN Nm N 374003 3 3 100 374005 5 10 200 374010 5 10 200 374012 12 22 200 374048 12 22 200 374125 20 37 500 374022 20 37 500 374023 20 37 500 374131 30 50 500 374130 30 50 500 374040 40 130 700 374043 40 130 700 374297 40 130 700 374060 60 200 700 374065 60 200 700 374181 80 270 700 374091 80 270 700 374111 100 350 700 374103 100 350 700 374120 100 350 700 374151 150 500 1000 374243 240 450 1500 374291 300 450 2000 11 Article Nr. UFM-Precision Force Max. allowable torque Max. allowable radial forces kN Nm N 365803 0,1 0,2 20 365802 0,2 0,2 20 364030 1 0,75 50 366030 3 3 100 366830 3 3 100 364020 1 90 50 378050 50 180 1000 378055 50 180 1000 UFM-Compact Pos : 9 /Sei tenumbr uch @ 0\mod_1133348983396_71.doc x @ 306 @ @ 1 12 Pos : 10 /UFM SP/UFM V5/Tec hnisc hes HB V5/Schmi erhi nweis e @ 0\mod_1297248656398_71.doc x @ 2539 @ 1 @ 1 5 Lubrication advice Preliminary Remarks All electro-mechanical presses from PROMESS must be re-lubricated. Overlubrication should be avoided, however, damage to the bearings due to overheating caused by over-lubrication is not to be expected. Over-lubrication as no negative consequences. Lubrication Points The following components are lubricated ex works: The gliding guides: The ball screw: The thrust bearing: Lubrication Points A and B, Lubrication Point C, Lubrication Point D. LUBRICATION POINTS A AND B: The lubrication points A and B consist of two opposite lubrication fittings in the centre of the press casing. LUBRICATION POINT C: Lubrication point C is located behind the seal cap M20*1,5. To re-lubricate the ball screw nut, complete the following steps: Remove the cover flap, manually move the spindle slowly downwards, until you see the lubrication opening on the now open drill hole. Please screw in the lubrication fitting Thread for lubrication fitting Type Preference series Thread UFM 03 / 05/ 12 / 20 / 30 M6 Thread extension UFM 40 / 60 / 80 / 175 /150 M8 * 1 UFM 40 / 60 / 80 / 330 /240 M8 * 1 M6 UFM 100 / 330 /200 M8 * 1 M6 UFM 150 / 400 / 145 M8 * 1 UFM 240 / 350 /120 M8 * 1 Now you can be re-lubricate with a lubrication press. LUBRICATION POINT D: The thrust bearing – especially on the units starting at 20kN nominal load – must be lubricated very carefully. As from the lubrication fitting to the rolling body running path also hollow spaces have to be filled, the following lubricant amounts are necessary: 13 LUBRICATION POINT E Please remove the frame cover. AMOUNT OF LUBRICANT FOR LUBRICATION For the amount and the necessary interval of lubrication please see the data sheet of your UFM. Lubricant A high-quality roll bearing lubricant must be used. PROMESS recommends the following lubricant brands: Klüber - ISOFLEX NBU 15, Klüber - ISOFLEX NCA 15, FAG ARCANOL and comparable types. Pos : 11 /Seitenumbruc h @ 0\mod_1133348983396_71.doc x @ 306 @ @ 1 14 Pos : 12 /UFM SP/UFM V5/Tec hnisc hes HB V5/DM S Verstär ker @ 1\mod_1367926991708_71.doc x @ 3820 @ 122222 @ 1 6 Strain Gauge amplifier The force sensor is operated using an analog strain gauge preamp. Technical data: Precision class: 0.2% Nominal sensitivity 0.28 to 3.6 mV/V Fine setting range of nominal sensitivity: ±20% Feed voltage of strain gauge bridge: 10 VDC Signal output: ± 10 VDC Temperature coefficient - Of zero point at 2 mV/V: < 0.05% - Of gain at 2 mV/V: < 0.07% Power supply: - Voltage range: 19 to 28 VDC - Current consumption: Approx. 35 mA Operating temp. range: -25 to +60 C Storage temp. range: -40 to +70 C EN 60529 safety class: IP 65 • o o Simplified diagram / pin assignments 15 • Dimensions / connections Stromversorgung / supply voltage 2.Stabilisierung/ stabilization 1.Stabilisierung/ stabilization X 2.5 (UB) X 2.4 (0V) Speisespannung/ excitation voltage (+EX) X1.2 (-EX) X1.5 Verstärkung/ amplification Ausgang/ output (+SI) X1.3 X 2.2 (A+) (-SI) X1.4 Messsignal/ signal input X 2.3 (A-) V Ø Nullpunkt/ zero Jumper X 2.1 Test R test 200K Force sensor Kraftaufnehmer Gruppe Angewandte System Technik BA 626 XKC 041 XKC 032.01 16 6.1 Calibrating the Strain Gauge Amplifier If it is necessary to recalibrate the strain gauge preamplifier, proceed as follows: • Offset To eliminate an offset from the force sensor, adjust potentiometer R1. (See amplifier drawing.) Adjust the potentiometer until the digital value displayed in the sensor calibration dialog is approximately zero in the absence of a load. • Gain Click “Manual Method”. Before applying a load, set the speed to a very small value (e.g., 0.5 mm/s). Drive in small steps to approx. 80% of the rated capacity. Watch the force indicated by the reference sensor. Apply a load and adjust the amplifier using potentiometer R2 (gain) until the value shown on the joining unit agrees with the value shown on the reference sensor. With higher loads, avoid remaining in this position for a longer period of time. Relieve the unit from any loads during the calibration process. • Position of calibration potentiometer Zero point of potentiometer Slope potentiometer 17 Required starting position Repeat this step until you are certain that the system is properly calibrated. To calibrate the unit on a regular basis, PROMESS recommends creating a calibration program. This program may appear as follows: 6.2 Program step Function Description 1 Positioning Positioned just in front of reference sensor 2 Join on Signal Application of definite force 3 Holding time 2 s Reading of applied force 4 Positioning Unit is driven back Strain Gauge Amplifier PDM-S (Digital) The PMD-S is connected to the UFM Control by the PROMESS-Bus Precision class: 0.1% Nominal sensitivity 0.1 … 5 mV/V Speisespannung für DMS Brücke: 10 VDC Analogue bandwidth 10 kHz typ. (-3dB) Resolution A/D converter 24 bit Programmable filter 0.37 … 12.5 kHz Temperature drift +/- 0,6uV/°C typ, (static temperatures, in thermal equilibrium) Power supply: - Voltage range: 19 ... 36 VDC - Current consumption: ca. 3 W Operating temp. range: +5 ...+55 C Humidity: Not condensing Storage temp. range: -40 ...+70 C Housing Aluminium Druckguss EN 60529 safety class: IP 40 Dimensions: 125*80*57 mm (L*W*H) Height without connectors o o 18 6.3 Connectors PDM-S Connector Description Type Num. of poles Pin-assignement Power supply 24 VDC M12 * 1 Binder Serie 713 4 1 = 24 VDC 2 = NU 3 = 0 VDC 4 = NU Force F M16 * 0.75 Binder Serie 680 6 1 = Supply. 2 = Supply. + 3 = NU 4 = Signal + 5 = Signal 6 = NU Encoder ENC M12 * 1 Binder Serie 713 8 1=A+ 2=A3=B+ 4 = B5 = Z+ 6 = Z7 = 5 VDC 8 = GND PROMESS BUS BUS M12 * 1 Binder Serie 713 5 1 = NU 2 = Bus A 3 = NU 4 = Bus B 5 = Shield NU = Not used 19 6.4 LED Functions PDM-S LED State 24 V Green = 24 VDC OK / NOK Indicates the status of the Cycle of the assigned station. COM Permanent green = Communication OK Green flashing = Communication NOK 1 time red flashing, pause = hardware initialisation fault 2 times red flashing, pause = Doppelte Node Adresse im Bus. 3 times red flashing, pause = not connectet to the bus 4 times red flashing, pause = no bus token Possible causes: - The PDM is reconfigurating - Topology not porper - No other Node in the Bus Pos : 13 /Seitenumbruc h @ 0\mod_1133348983396_71.doc x @ 306 @ @ 1 20 Pos : 14 /UFM SP/UFM V5/Tec hnisc hes HB V5/Promess-Bus @ 0\mod_1343377001138_71.doc x @ 3581 @ 1222 @ 1 7 PROMESS Bus The PROMESS bus is based on the CTNet BUS from Control Techniques. This bus allows digital PROMESS PDM modules to be interconnected and also enables communications between UFM controllers. Bus master node 12 Bus terminator Bus slave node 13 Bus terminator Promess digital module node 23 Promess digital module node 22 In this example, the Promess Digital Modules transmit signals to the master power component (node 12) as well as to the slave power component (node 13). The power components can also transmit signals and variables to each other. 21 7.1 Bus Terminator. Make sure to correctly terminate the bus using terminating resistors. The bus data lines must be terminated using 82 Ω (0.25 W) at the SM Applications of the master and behind the last node in the bus. • Master Terminate the SM Applications of the master using terminals 6 and 8. Pin 8 Pin 6 22 • Terminator for PDM-S The bus on the Promess PDM-S digital module can be terminated using the DIP switch provided there. The location of the switch is shown in the figure below. Traco Power DIP terminator switch 7.2 Cable Shield Connections The cable shields should be connected to each other at the location where they emerge from the cable. Use them to create a short wire strand that connects the CTNet shield to the corresponding terminal. For reasons of safety, the CTNet shield must be grounded at one point. In case of a catastrophic failure, this ground connection prevents the cable shield from transmitting electrical current to another device in the CTNet network or within the cable itself. For EMC reasons, the ground line should only be connected at a single point. 23 Node - Address • SM – Applications These settings are made using the UFM software under: “Service / Station Settings / PROMESS-BUS” The following addresses can be assigned: Function 12 Slave 13 Slave 14 Slave 15 PDM-S Traco Power • Node Address Master OFF 1 2 3 4 5 6 DIP switch ON 7.3 24 DIP Function 0ff On 5 MBit 2.5 MBit 1 Node address binary-coded as bit 1 2 Node address binary-coded as bit 2 3 Baudrate 4 Not used 5 Boot loader Start 6 Default parameters Load DIP 1 (Bit 1) DIP 2 (Bit 2) Node Address PROMESS Bus off off 22 on off 23 off on 24 on on 25 All switch changes do not take effect until first switching the unit off and then switching it back on. Pos : 15 /Seitenumbruc h @ 0\mod_1133348983396_71.doc x @ 306 @ @ 1 25 Pos : 16 /UFM SP/UFM V5/Tec hnisc hes HB V5/Ins tallation Software / Kommuni kati on UFM PC @ 0 \mod_1305802993105_71.doc x @ 2761 @ 11222222 @ 1 8 Software installation Place the disk or CD-ROM in the appropriate drive. Go to the Windows start button (bottom far left), select 'Execute' and then type “Setup”. Follow the on-screen instructions to install the program. 9 Communication PC - Application module The communication can be done using the delivered Ethernet module. 9.1 Connection Ethernet module Cable No. 11592001 Pin Ethernet X2 21 22 23 24 18 App. Mod 5 3 2 4 1 SM Applikation Module X1 Power Suppl. 11 12 13 24V 0V GND X2 (RS 422) (Pin) (extern.) 21 22 23 24 RX+ TX+ TX- RX- 14 NC 25 26 NC NC Stromaufnahme: max. 90 mA 27 NC 28 GND Cable: Cat 5 Crossover Ethernet Module X4 RS485 (RJ45) X5 RS485 (RJ45) 1 4 1 +24VDC NC RX/TX 0V 5 0V 7 8 RX/TX NC 2 3 NC RX/TX 0V 5 0V 7 8 RX/TX NC 2 3 4 +24VDC Cat 5 Switch X3 Ethernet 10/100 Mbit 6 NC 6 NC PC Cable Cat 5 Unidrive SP 26 PC 9.2 Ethernet Communication To communicate by Ethernet, you have to assign a common IP address to the PROMESS Ethernet Module and your PC! Which address is assigned to the Ethernet Module? Change the IP address of the Ethernet module: => 9.3 The address is assigned by PROMESS and you can find it in the delivery protocol of the unit. In the state of delivery the IP address is in the range: 192.168.x.x range: Which address should you assign to your PC? 192.168.x.x To connect to an Ethernet Moduls, that is in delivery state, assign a IP adrerss in the 192.168.x.x range and 255.255.0.0 as subnet mask. Change IP Address PC: => 9.4 Windows XP / 9.5 Windows 7 Promess recommends the installation of a Sub net, in case of using more then one press. 27 Ethernet Point to point connection with only one press unit. Ethernet Switch 28 Ethernet Ethernet Ethernet Ethernet Sub Net mit mehreren Fügeeinheiten und Switch 9.3 Assignment IP address Ethernet Module To assign a IP address to the Ethernet Module you need to have a functional TCP/IP network connection on your PC. If you have not assigned a fixed IP address please do this as described in chapter 9.4 (windows XP), chapter 9.5 (Windows 7) To assign a new IP address to the Ethernet Module, please run the program “Detector” in the PROMESS / Ethernet installation folder. The Lantronix Detector opens. Please click the “binocular” button to search for connected Ethernet Modules in the network. This following window displays the IP adresses off all PROMESS Ethernet Modules, that are running in your network. Wählen sie anhand der IP Adresse oder der Hardware - Adresse (MAC Adresse) das Modul, dessen IP Adresse sie ändern möchten und klicken sie anschließend auf die Schaltfläche „IP“. 29 Choose by IP or Mac address the module you like to change. Then click the button “IP” The MAC address you can find at the name plate of the Ethernet module. Enter the IP address you would like to use in the future and if necessary the subnet mask. When done, please reset the Ethernet module, by interrupting the power supply. 30 9.4 Assign IP Adress PC Open the „Network and Dial-up Connections“ in your “Windows Control Panel“. and open the properties of the LAN connection you like to use. Click on Internet Protocol (TCP/IP) and then on „Properties“ 31 Enter the IP adress and the Subnet mask 9.5 Assign IP Adress PC Windows 7 Open the „Network and Dial-up Connections“ in your “Windows Control Panel“. and open the properties of the LAN connection you like to use 32 The property window of the connection opens.: Klick on Internet Protocol version 4 (TCP/IPv4) and then „properties“. The following window opens: Enter the IP adress and the Subnet mask . If necessary ask your Network administrator for the right settings. 33 Permissible address range Frequently used network masks 10.0.0.0–10.255.255.255 255.0.0.0 172.16.0.0–172.31.255.255 255.255.0.0 192.168.0.0–192.168.255.255 255.255.255.0 169.254.0.0–169.254.255.255 immer 255.255.0.0 In case your PC has more then one network device, please choose “Advanced” and enter “1” for Inteface Metric. 9.6 No Ethernet module found If you can not find any Ethernet Module using „Find“ in the program „UdpChangeIP“, this might be caused by the fact, that the address of your PC and your Ethernet Module are not in the same network. The IP Adress of your Ethernet Module, whenit was shipped, is documented in the protocol you have got with the shipment. Make sure, that you set the address of your PCcorresponding to this address. If the Ethernet Module is not anymore in the state of delivery and you do not know the address, go ahead as follows: If possible, connect the PC and the module directly. Open the properties of your PC Ethernet network connection. Enter a abritary IP addres out of the 4 permitted ranges. The IP addres has to start with 192.168.x.x, 169.254.x.x, 172.16.x.x or 10.x.x.x. As Subnet mask use 255.255.0.0. or 255.0.0.0 for 10.x.x.x networks Open the program „UdpChangeIP“and click on „Find“. If there is no Ethernet Module found, change the IP addres to the next range and open „UdpChangeIP“again. If there is no Ethernet module in all ranges, it must be damaged. Please contact Promess for the exchange. Pos : 17 /Seitenumbruc h @ 0\mod_1133348983396_71.doc x @ 306 @ @ 1 34 Pos : 18 /UFM SP/UFM V5/Tec hnisc hes HB V5/UFM Firmware U pdate @ 0\mod_1328520238078_71.doc x @ 3193 @ 122 @ 1 10 Firmware Update Before you update the UFM firmware please make sure which Promess Ethernet Module you are using. From version V5.03 the Ethernet Module is delivered with a different internal software version. This version enables a faster communication to the PC (baud rate 115200 bit/S) as well as updating the UFM firmware without the need of using the CPR manager. Who to recognize the new version? • PC software UFM Behind the IP address of the station there is a little star. (baud rate 115200 bit/S), or a star in brackets (baud rate 38400 bit/S) • In the cabinet At the front view of the Ethernet module underneath the Promess logo you can see a green sticker. New Old 35 10.1 Version 5.00 to V5.2x Before starting a firmware update, make sure that the CPR Manager is installed and correctly configured on your PC. (See CPR Manager section) Before continuing with the “Update”, press the Emergency Stop button on your system and close all running programs on your PC. Start the “Winflash.exe” program in the installation directory “UFM_NC.EXE”. The start window appears. Click “Next”. Choose the following in the next window: “Download a compiled program” => “Next” “Search” for the file “CTNet0_Node_12.bin” that you used to perform the update. You can find the file in the installation directory of the UFM software. 36 Click “Next”. Choose “CT-RTU (Unidrive SP)” as the connection protocol and “Slot 2” under “Settings”. Under “Change Communications Settings”, adapt the COM interface (hardware) to the interface defined in the Redirector. Use 38.4 Kbit/s as the baud rate. 37 => “Next” => “Next” To start the “Download”, click the red button. It is absolute necessary to close the UFM software. While an update is running, you can click “Cancel” if necessary to abort the process. 38 End the update process by clicking “Finish”. After a successful update please reset the drive by switching off and on 10.2 39 From Version 5.03 Before continuing with the “Update”, press the Emergency Stop button on your system and close all running programs on your PC. Start the “Winflash.exe” program in the installation directory “UFM_NC.EXE”. The start window appears. Click “Next”. Choose the following in the next window: “Download a compiled program” => “Next” 40 “Search” for the file “CTNet0_Node_12.bin” that you used to perform the update. You can find the file in the installation directory of the UFM software. Click “Next”. Choose „CT-TCP/IP“ as the connection protocol and “Slot 2” under “Settings”. Enter the IP address of the station you like to update.. Choose slot 2 (Slot des Applikationsmoduls) Under “Change Communications Settings”, adapt the COM interface (hardware) to the interface defined in the Redirector. Use 38.4 Kbit/s as the baud rate. 41 Adjust if necessary the „Advanced…“ settings. Enter 3001 as TCP Server Port => “Next” => “Next” 42 To start the “Download”, click the red button. It is absolute necessary to close the UFM software. While an update is running, you can click “Cancel” if necessary to abort the process. End the update process by clicking “Finish”. After a successful update please reset the drive by switching off and on Pos : 19 /Seitenumbruc h @ 0\mod_1133348983396_71.doc x @ 306 @ @ 1 43 Pos : 20 /UFM SP/UFM V5/Tec hnisc hes HB V5/Ins tallation C PR M anager @ 0\mod_1305797695176_71.doc x @ 2730 @ 12 @ 1 11 Installation of CPR V4 Manager In order to update the firmware in the NC module, the CPR Manager must be installed on your PC. Changes on the PC to operate CPR Manager: 1. 2. 3. 4. x86 (32 bit): Windows XP, 2003 Server, Vista, 7, and 2008 Server x64 (64 bit): Windows Vista, 7, and 2008 Server Microsoft .NET Framework v4.0 30 MB free space on hard drive Proceed as follows: • Please install “CPR Manager” • Follow the installation instructions. Access the configuration of the CPR Manager under Programs: The following window appears: 44 To define the COM port that you want to use, choose “Add and Remove”. In the next window, choose a COM port not used on your computer such as COM10. Exit the window with “OK”. 45 Choose the COM you have created: Clear the “Buffer Writes” option. Next, search for any connected Ethernet modules by choosing the “Search” option in the “Device” menu. 46 Next, choose the IP address that you would like to connect to. Double-click the selection. Next, change the TCP port value to 3001. To save the settings, choose “Save Settings” in the “Com Port” menu or click the Save icon. 47 11.1 COM Test Click the “COM … Tests” tab to open it. Click “Open” to test the connection. If your settings are correct, you will see that you are connected to the chosen address. Stop the test with “Close”. If your PC is connected to several stations, enter the addresses of the additional stations. Next, save the new settings. Pos : 21 /Seitenumbruc h @ 0\mod_1133348983396_71.doc x @ 306 @ @ 1 48 Pos : 22 /UFM SP/UFM V5/Tec hnisc hes HB V5/SPS Schnittstelle @ 0\mod_1305797708296_71.doc x @ 2739 @ 1222222 @ 1 12 PLC Interface 1 Remarks The interface is designed to ensure a complete handshake, so that times do not have to be programmed or considered for the signal transmission. 2 Acknowledgement The output signal "Ack." is used to confirm "System ready" and to acknowledge the detection of a PLC signal. Signal description Signal Function Meaning Reference motion Input Start of reference motion Cycle start Input Cycle start OK Output Part OK and cycle end NOK Output Part NOK and cycle end Ack Output Acknowledgement signal Reference request Output Reference request from the NC module OK/NOK Outputs Program interruption / cycle stop 12.1 Reference motion after start-up Reference request ACK Reference motion start Description After a start-up of the NC module, the reference request and Ack are set The PLC sets the signal reference motion, The NC module acknowledges the signal by resetting the Ack signal, The PLC resets the signal start reference motion, when the signal reference request has been reset by the NC module, The NC module confirms that the signal start reference motion has been reset, by setting the Ack signal. If the signal start reference motion is cancelled during execution of the command, the PC stops the reference motion and the signal reference request remains set. 49 12.2 Reference motion without a request Reference request Ack Reference motion Description The PLC sets the signal reference motion, The NC module confirms the signal by resetting the Ack signal and setting the signal reference request, The PLC resets the signal start reference motion, when the signal reference request has been reset, The NC module confirms that the signal start reference motion has been reset by setting the Ack signal. If the signal start reference motion is cancelled during execution of the command, the PC stops the reference motion and the signal reference request remains set. 12.3 Cycle start Home request ts Life Bit Start Ack 4 1 2 5 OK 3 NOK Description tprg ta tb The PLC sets the start signal The NC module confirms the signal by resetting the Ack signal and resetting OK or NOK The PLC detects the cycle end through the signal OK or NOK The NC module confirms the start-signal reset, by setting the Ack signal If the signal start is cancelled during the program cycle, the NC module stops the motion and the signals Ack, OK and NOK are set. 50 12.4 Emergency Stop during a motion Emergency-Stop Ack Start Ref-request Description In the case of an Emergency Stop, the Emergency Stop chain is opened, The press unit reacts by stopping the motion, The PLC resets the start signal, when an Emergency Stop situation is detected, After clearing the Emergency Stop situation, the PC confirms the flank change of the Emergency Stop signal after the start-signal has been reset, 12.5 Emergency Stop during standstill process Emergency-Stop Ack Description In the case of an Emergency Stop, the Emergency Stop chain is opened, The NC module confirms by resetting the Ack, Closing of the Emergency Stop chain is responded to by setting the Ack. 51 12.6 Cycle Stop Ref. request. ts L Bit 4 1 Start 5 2 Quit 3 OK NOK 6 tb Cycle stop tsch ta ta >= 10ms, tb >= 20ms, tsch = Duration of program step to cycle stop ts = Save data in database Description The PLC sets the start signal when live bits are present and no reference request is present. The NC module acknowledges the signal by resetting the acknowledgement. The PLC recognizes the cycle stop from the OK or NOK signal plus Quit or from the signal cycle stop. (This signal is only available via the bus system or the expansion module) The PLC resets the start signal. Setting the start signal again continues the cycle. The outputs OK or NOK plus Quit are reset. 52 12.7 Transfer of program number I Start I Reference start I Prog. Bit 1 I Prog. Bit 2 1 I StrobeI Prog. Prog.Bit non 2 4 O Prog. Bit 1 O Prog. Bit 2 3 O Strobe Prog. O Prog. Bit n tb tload ta 5 ta >= 10ms, tb >= 20ms, tload = Program load time Description: Assignment of binary coded program number Set strobe for transfer Reflection of program number Strobe acknowledgement after program loaded Reset strobe of PLC and NC module === Ende der Liste für T extmar ke Inhalt === 53 Index A L Acknowledgement 49 Assign IP Adress PC 31 Lubrication advice 13 B No Ethernet module found 34 bus terminator 22 P C PLC interface 49 COM Test 48 Connection Ethernet module 26 Correct usage 4 Cycle Stop 52 R N Radial forces, max. load 11 Reference motion without a request 50 S E Safety measures 5 Signal description PLC interface 49 Signal flow cycle start 50 Signal flow reference motion after start-up 49 Software installation 26 Strain gauge amplifier 15 Strain Gauge Amplifier PDM-S (Digital) 18 Emergency Stop during a motion 51 Emergency Stop during standstill process 51 Ethernet Communication 27 F Firmware Update 35 H T Hazard analysis 8 Torque, max. load 11 Transfer of program number 53 Transport 5 I IP address Ethernet Module 29 IP Adresse PC Windows 7 32 54