260 Application Brochure
Transcription
260 Application Brochure
- Application A 260-1 03/09 Boiler Control 260 Mechanical 260 Outdoor Sensor (S2) 070 Class 2 Transformer 24 V (ac) 120 V (ac) Z3 Z2 Z1 M M M T2 T3 T1 Boiler Sensor (S1) 082 Electrical 10A 10A P1 260 10A Do not apply power P1 = Boiler Pump S1 = Boiler Sensor 082 S2 = Outdoor Sensor 070 T1, ..., T3 = Thermostats U1 = tekmar Timer 033 (optional) Z1, ..., Z3 = Zone Valve Motor End Switches 9 10 11 12 13 14 15 16 17 18 Boiler DHW Power Boil Demand Demand L N P1 N DHW Boiler Pmp/Vlv UnO Com Boil Out Com Indr Sw S1 DHW Valve DHW Priority Advanced DHW during UnOcc Installer DHW Pump 1 2 3 4 5 6 7 8 Boiler Off Off Zone Valve Motor End Switches = Required Z1 = Optional Z2 U1 S2 P1 Z3 Class 2 Transformer = Not Used 24 V (ac) C 120 V (ac) L R N Note: This is only a concept drawing. The designer must determine whether this application will work in his system and must ensure compliance with code requirements. Necessary auxiliary equipment, isolation relays (for loads greater than the specified tekmar internal relay ratings), and other safety and limit devices must be added. 1 of 8 Copyright ©2009 A 260-1 03/09 A 260-1 03/09 System Operation The Boiler Control 260 provides partial or full outdoor reset to three (or more) boiler zones. The boiler is operated at the temperature required in order to satisfy the load. Heat Source Details The heat source can be either a high mass or low mass non-condensing or low temperature boiler. Piping Details Thermostat controlled zone valves are piped into the boiler loop. The boiler pump (P1) provides circulation through these zones when heat is required. Boiler Demand When heat is required in the boiler zones, the zone valve end switches send a Boiler Demand to the 260. The 260 turns on the boiler pump (P1). The boiler supply water temperature is based on the Characterized Heating Curve settings. The boiler is fired to satisfy the required boiler supply water temperature. Whenever the boiler is fired, the 260 aims to increase the boiler supply water temperature to at least the BOIL MIN setting. All control functions and specifications are listed in the Product Catalog I 000 and Data Brochure D 260. Control Systems tekmar Control Systems Ltd., Canada tekmar Control Systems, Inc., U.S.A. Head Office: 5100 Silver Star Road Vernon, B.C. Canada V1B 3K4 Tel. (250) 545-7749 Fax. (250) 545-0650 Web Site: www.tekmarcontrols.com Product design, software and literature are Copyright © 2009 by: tekmar Control Systems Ltd. and tekmar Control Systems, Inc. 2 of 8 All specifications are subject to change without notice. Printed in Canada. A 260-1 03/09. - Application A 260-2 03/09 Boiler Control 260 Mechanical 260 Outdoor Sensor (S2) 070 Class 2 Transformer 24 V (ac) 120 V (ac) A2 Z3 Z2 M M T3 A1 Z1 M T2 T1 M V1 DHW Tank P1 Boiler Sensor (S1) 082 10A 10A Electrical 260 10A Do not apply power A1 = DHW Aquastat A2 = DHW High Limit Aquastat P1 = Boiler Pump S1 = Boiler Sensor 082 S2 = Outdoor Sensor 070 T1, ..., T3 = Thermostats U1 = tekmar Timer 033 (optional) V1 = DHW Valve Z1, ..., Z3 = Zone Valve Motor End Switches DHW Valve DHW Priority Advanced DHW during UnOcc Installer DHW Pump Off Off 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Boiler DHW Power Boil Demand Demand L N P1 N DHW Boiler Pmp/Vlv UnO Com Boil Out Com Indr Sw S1 Boiler Zone Valve Motor End Switches = Required Z1 = Optional U1 S2 A2 P1 A1 M V1 Z2 = Not Used Z3 Class 2 Transformer 24 V (ac) C 120 V (ac) L R N Note: This is only a concept drawing. The designer must determine whether this application will work in his system and must ensure compliance with code requirements. Necessary auxiliary equipment, isolation relays (for loads greater than the specified tekmar internal relay ratings), and other safety and limit devices must be added. 3 of 8 Copyright ©2009 A 260-2 03/09 A 260-2 03/09 System Operation The Boiler Control 260 provides partial outdoor reset to three (or more) boiler zones. The 260 also controls the supply of heat to an indirect fired Domestic Hot Water (DHW) tank. The boiler is operated at the temperature required in order to satisfy the loads. Heat Source Details The heat source can be either a high mass or low mass non-condensing boiler. Piping Details Thermostat controlled zone valves are piped into the boiler loop. The boiler pump (P1) provides circulation through these zones when heat is required. Heat is supplied to the DHW tank through a DHW valve (V1). DHW Demand When the DHW aquastat (A1) calls for heat, the 260 turns on the boiler pump (P1), opens the DHW valve (V1), and raises the boiler water temperature to at least 180°F (82°C). Boiler Demand When heat is required in the boiler zones, the zone valve end switches send a Boiler Demand to the 260. The 260 turns on the boiler pump (P1). The boiler supply water temperature is based on the Characterized Heating Curve settings. The boiler is fired to satisfy the required boiler supply water temperature. Whenever the boiler is fired, the 260 aims to increase the boiler supply water temperature to at least the BOIL MIN setting. All control functions and specifications are listed in the Product Catalog I 000 and Data Brochure D 260. Control Systems tekmar Control Systems Ltd., Canada tekmar Control Systems, Inc., U.S.A. Head Office: 5100 Silver Star Road Vernon, B.C. Canada V1B 3K4 Tel. (250) 545-7749 Fax. (250) 545-0650 Web Site: www.tekmarcontrols.com Product design, software and literature are Copyright © 2009 by: tekmar Control Systems Ltd. and tekmar Control Systems, Inc. 4 of 8 All specifications are subject to change without notice. Printed in Canada. A 260-2 03/09. - Application A 260-3 03/09 Boiler Control 260 Mechanical 260 Outdoor Sensor (S2) 070 Class 2 Transformer 24 V (ac) 120 V (ac) A2 Z3 Z2 M M T3 A1 Z1 M T2 T1 DHW Tank P2 Boiler Sensor (S1) 082 P1 10A 10A Electrical 260 10A Do not apply power A1 = DHW Aquastat A2 = DHW High Limit Aquastat P1 = Boiler Pump P2 = DHW Pump S1 = Boiler Sensor 082 S2 = Outdoor Sensor 070 T1, ..., T3 = Thermostats U1 = tekmar Timer 033 (optional) Z1, ..., Z3 = Zone Valve Motor End Switches DHW Valve DHW Priority Advanced DHW during UnOcc Installer DHW Pump Off Off 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Boiler DHW Power Boil Demand Demand L N P1 N DHW Boiler Pmp/Vlv UnO Com Boil Out Com Indr Sw S1 Boiler P1 Zone Valve Motor End Switches = Required U1 S2 A2 P2 Z1 = Optional A1 Z2 = Not Used Z3 Class 2 Transformer 24 V (ac) C 120 V (ac) L R N Note: This is only a concept drawing. The designer must determine whether this application will work in his system and must ensure compliance with code requirements. Necessary auxiliary equipment, isolation relays (for loads greater than the specified tekmar internal relay ratings), and other safety and limit devices must be added. 5 of 8 Copyright ©2009 A 260-3 03/09 A 260-3 03/09 System Operation The Boiler Control 260 provides partial or full reset to three (or more) boiler zones. The 260 also controls the supply of heat to an indirect fired Domestic Hot Water (DHW) tank. The boiler is operated at the temperature required in order to satisfy the loads. Heat Source Details The heat source can be either a high mass or low mass non-condensing or low temperature boiler. If using a low temperature boiler, refer to section C3 of the Data Brochure for additional information. Piping Details Thermostat controlled zone valves are piped into the boiler loop. The boiler pump (P1) provides circulation through these zones when heat is required. Heat is supplied to the DHW tank through a DHW pump (P2). DHW Demand When the DHW aquastat (A1) calls for heat, the 260 turns on the DHW pump (P2) and raises the boiler water temperature to at least 180°F (82°C). The control can provide DHW priority (refer to section C2 of the Data Brochure) by turning off the boiler pump (P1). Once the DHW demand is removed, the 260 performs a DHW Post Purge and possibly a Mixing Purge. Boiler Demand When heat is required in the boiler zones, the zone valve end switches send a Boiler Demand to the 260. The 260 turns on the boiler pump (P1). The boiler supply water temperature is based on the Characterized Heating Curve settings. The boiler is fired to satisfy the required boiler supply water temperature. Whenever the boiler is fired, the 260 aims to increase the boiler supply water temperature to at least the BOIL MIN setting. All control functions and specifications are listed in the Product Catalog I 000 and Data Brochure D 260. Control Systems tekmar Control Systems Ltd., Canada tekmar Control Systems, Inc., U.S.A. Head Office: 5100 Silver Star Road Vernon, B.C. Canada V1B 3K4 Tel. (250) 545-7749 Fax. (250) 545-0650 Web Site: www.tekmarcontrols.com Product design, software and literature are Copyright © 2009 by: tekmar Control Systems Ltd. and tekmar Control Systems, Inc. 6 of 8 All specifications are subject to change without notice. Printed in Canada. A 260-3 03/09. - Application A 260-4 03/09 Boiler Control 260 Mechanical 260 Outdoor Sensor (S2) 070 Class 2 Transformer 24 V (ac) 120 V (ac) A2 R1 Z1 R2 T1 R3 T2 Z2 A1 T3 Z3 P1 DHW Tank Boiler Sensor (S1) 082 Electrical 10A 10A 260 10A Do not apply power A1 = DHW Aquastat A2 = DHW High Limit Aquastat P1 = DHW Pump R1, ..., R3 = Relay 003 S1 = Boiler Sensor 082 S2 = Outdoor Sensor 070 T1, ..., T3 = Thermostats U1 = tekmar Timer 033 (optional) Z1, ..., Z3 = Zone Pumps DHW Priority DHW during UnOcc Return Advanced T3 Installer DHW Pump 9 10 11 12 13 14 15 16 17 18 Boiler DHW Power Boil Demand Demand L N P1 N DHW Boiler Pmp/Vlv UnO Com Boil Out Com Indr Sw T1 T2 DHW Valve 1 2 3 4 5 6 7 8 Off Off 7 8 1 2 R1 4 3 S1 Z1 7 8 1 2 6 5 Boiler U1 S2 A1 R2 4 3 A2 Z2 7 8 1 2 = Required 6 5 6 5 R3 P1 4 3 Z3 = Optional Class 2 Transformer = Not Used 24 V (ac) C 120 V (ac) L R N Note: This is only a concept drawing. The designer must determine whether this application will work in his system and must ensure compliance with code requirements. Necessary auxiliary equipment, isolation relays (for loads greater than the specified tekmar internal relay ratings), and other safety and limit devices must be added. 7 of 8 Copyright ©2009 A 260-4 03/09 A 260-4 03/09 System Operation The Boiler Control 260 provides partial or full reset to three (or more) boiler zones. The 260 also controls the supply of heat to an indirect fired Domestic Hot Water (DHW) tank. The boiler is operated at the required temperature in order to satisfy the loads. Heat Source Details The heat source can be either a high mass or low mass non-condensing or low temperature boiler. If using a low temperature boiler, refer to section C3 of the Data Brochure for additional information. Piping Details Thermostat controlled zone pumps are piped into the boiler loop. Heat is supplied to the DHW tank through a DHW pump (P1). DHW Demand When the DHW aquastat (A1) calls for heat, the 260 turns on the DHW pump (P1) and raises the boiler water temperature to at least 180°F (82°C). The control can provide DHW priority (refer to section C2 of the Data Brochure) by turning off the Boil P1 contact and not allowing any of the boiler zones to operate. Once the DHW demand is removed, the 260 performs a DHW Post Purge and possibly a Mixing Purge. Boiler Demand When heat is required in the boiler zones, the zone pump relays send a Boiler Demand to the 260. The boiler supply water temperature is based on the Characterized Heating Curve settings. The boiler is fired to satisfy the required boiler supply water temperature. Whenever the boiler is fired, the 260 aims to increase the boiler supply water temperature to at least the BOIL MIN setting. All control functions and specifications are listed in the Product Catalog I 000 and Data Brochure D 260. Control Systems tekmar Control Systems Ltd., Canada tekmar Control Systems, Inc., U.S.A. Head Office: 5100 Silver Star Road Vernon, B.C. Canada V1B 3K4 Tel. (250) 545-7749 Fax. (250) 545-0650 Web Site: www.tekmarcontrols.com Product design, software and literature are Copyright © 2009 by: tekmar Control Systems Ltd. and tekmar Control Systems, Inc. 8 of 8 All specifications are subject to change without notice. Printed in Canada. A 260-4 03/09.