Pressure differential transmitter DDS-M984… DDS
Transcription
Pressure differential transmitter DDS-M984… DDS
Pressure differential transmitterDDS-M984… DDS-MR984… Function Pressure differential transmitters of type series DDS 984 are used to measure differential, positive, and negative pressure in gaseous, non-aggressive media. They have 2 sensor pressure ranges and 2 output signals that can be selected alternatively by swapping a jumper. The pressure transducer converts the mechanical pressure reading into an electrical sensor signal. The piezo-resistive pressure transducer integrated into the DDS 984 pressure differential transmitter is configured so that the pressure to be read is applied to a thin mono-silicon membrane. This deflects the membrane. The membrane is equipped with resistors based on semi-conductor technology. These detect the mechanical deflection and generate an electrical output signal. The arrangement of the resistors at the same time results in temperature response compensation. High-gain process amplifiers convert the signal from the pressure transducer into the output signal. Within the specified error limits, the electrical output signal changes proportionally to the applied pressure. Possible applications include: • Building automation, air-conditioning and cleanroom technology • Valve and damper control • Filter, ventilator, and blower monitors • Airflow controls • Metric cable glands • Arbitrary installation orientation Technical Data Compressed medium: Air and non-aggressive media Power supply: •3-wire-design 18 – 30 V AC / DC •2-wire-design 18 – 30 V DC Output signal: •3-wire-design 0 – 10 V and 4 – 20 mA •2-wire-design 4 – 20 mA Maximum current draw: •Without display 160 mA •With LED display 210 mA Load (at 4 – 20 mA): 20 – 500 Ω Linearity and hysteresis error: ≤ ±1 % of sensor reading Operating temperature: 0 – 50 °C Storage temperature: -10 – +70 °C Long-term stability, type:≤ ±0,5 % – ±2,5 % of sensor reading/ year, depending on pressure range Repeatability accuracy: ≤ ±0,2 % of sensor reading Orientation dependency: ≤ ± 0,02 % of sensor reading/g Humidity: 0 – 95 % RH, non-condensing Switching output (npn): max. 30 V DC/100 mA 1) Output signal toggle: Linear/square root extraction Zero setting adjustment: Manual Response time settings:Short, 100 ms long, 1 s (default setting) Process ports: 6 mm hose flanges Electrical connection:Screw terminals for wires and cores up to 1.5 mm² Mounting:Screw mounted with sheetmetal screws Display, optional: Red LED display, 3.5-digit 1) Housing material:Switch housing with process port P2, ABS, light-gray; mounting bracket with process port P1, POM, white Housing dimensions: Approx. Ø 85 mm, H 58 mm Weight: Approx. 150 g Protection type iaw. EN605209: IP 54 with protective cover Cable grommet for protective cover: M 16 x 1,5 Polyamide threads Standards / conformity:EN 60770, EN 61326 2002/95/EWG (RoHS) Sensor method:Piezo-resistive pressure sensor for airflows 1) only on 3-wire design Sensor ventilation air conditioning | Data sheet No. 13251 | Version 09-2014 | 1 | 6 Pressure differential transmitter DDS-M984… DDS-MR984… Type name Series M16 cable gland Sensor range: see table Unit of measure: Pa Output signal K 0 – 10 V or 4 – 20mA, lin/square root extraction, with switching output 2 2-wire 4 – 20 mA, lin/square root extraction, without switching output, without display Display 0 without display 1 with LED display DDS-MR984.5._.3.K.1 Pressure ranges Type Sensor range 1 Sensor range 2 Positive pressure safety Burst pressure Temperature error DDS-MR984.5.X.3.K.1 -50 – 50 Pa - 20 kPa 40 kPa ≤ ± 5% of sensor reading DDS-MR984.5.W.3.K.1 -100 – 100 Pa - 20 kPa 40 kPa ≤ ± 5% of sensor reading DDS-MR984.5.2.3.K.1 0 – 100 Pa 0 – 250 Pa 20 kPa 40 kPa ≤ ± 5% of sensor reading DDS-MR984.5.3.3.K.1 0 – 250 Pa 0 – 500 Pa 20 kPa 40 kPa ≤ ± 5% of sensor reading DDS-MR984.5.4.3.K.1 0 – 500 Pa 0 – 1,000 Pa 20 kPa 40 kPa ≤ ± 3.5% of sensor reading DDS-MR984.5.5.3.K.1 0 – 1 kPa 0 – 2.5 kPa 40 kPa 70 kPa ≤ ± 1% of sensor reading DDS-MR984.5.7.3.K.1 0 –5 kPa 0 – 10 kPa 60 kPa 120 kPa ≤ ± 1% of sensor reading DDS-MR984.5.9.3.K.1 0 – 25 kPa 0 – 50 kPa 300 kPa 500 kPa ≤ ± 1% of sensor reading DDS-MR984.5.B.3.K.1 0 – 100 kPa 0 – 250 kPa 1.2 MPa 2 MPa ≤ ± 1% of sensor reading 0 – 10 kPa 60 kPa 120 kPa ≤ ± 1 % of sensor reading DDS-MR984.5._.3.K.0 Without display, technical specs as above DDS-MR984.5._.3.2.0 2-wire 4 – 20 mA, no switching output, no display 2 | 6 | Sensor ventilation air conditioning | Data sheet No. 13251 | Version 09-2014 Pressure differential transmitter DDS-M984… DDS-MR984… Installation Klemmenbelegung Terminal assignments 3-Leiter-Ausführung 3-wire design All work (such as installation, electrical connection, startup, operation, and maintenance) must only be performed by sufficiently qualified tradesmen. The respectively applicable local rules and regulations (e.g. national building codes, electrical/ VDE regulations, etc.) must be observed. Installers and operating entities are required to sufficiently familiarize themselves before startup. Read the product description before operating the equipment. Verify that the product can be used for the relevant application without restrictions. We are not liable for printing errors and changes after printing. Appropriate use implies compliance with operating and installation instructions. We are not liable for losses due to inappropriate use. Unauthorized or inappropriate manipulations or modifications of the device render the operating permit, the product warranty and warranty claims null and void. npn 4 Load 3 0…10 V 4...20 mA 2 Load 24 V AC/DC 1 4 3 2 1 SA GO Y G switching output, npn ground or GND output signal 0 … 10 V/4 ... 20 mA power supply 24 V AC/DC 2-wire design Startup The 984 pressure differential transmitter can be operated with 24 V DC or AC. Hoses must not be kinked or damaged while being connected. Leaking hoses or hose connections cause malfunctions on the device or will cause incorrect sensor readings. Inside hose diameter: 5.5 mm for ideal clamping. Hose clamps should be used from 25 kPa. P1 = positive pressure measurements P2 = negative pressure measurements P1 & P2 = pressure differential measurements The pressure on P1 must always be higher than on P2 to obtain a correct 0 – 10 V signal. The output signal is connected to terminals „Out 0 – 10 V“. Note correct polarity. The load must be selected to avoid exceeding 10 mA output current. As a final step, the power supply is connected to the terminals labeled „In 24 V AC/DC“. Installation orientation The orientation error is eliminated with the self-compensating piezo sensor cell. The installation orientation is arbitrary. Simple zero point setting The output signal is calibrated to zero by pressing the M button while the transmitter is not under pressure. Switching output (not for 2-wire design) In addition to the analog output signal, the pressure differential transmitter includes an adjustable transistor switching output with a maximum switching rating of 35 V DC/100 mA. Pressure display (optional) In addition to the output signal, the pressure reading is displayed in Pascal with a red LED. Sensor ventilation air conditioning | Data sheet No. 13251 | Version 09-2014 | 3 | 6 Pressure differential transmitter DDS-M984… DDS-MR984… Configuration M = Mode S = Set Jumper function Inserted Open Sensor range Low High Response time Slow Fast Operating mode Linear Square root extraction Output signal 0 – 10 V 4 – 20 mA LED Pressure range toggle Volume flow measurement 2 pressure ranges are available for selection (see table) for an optimum adjustment of the pressure range. The lower, sensitive area is selected with an inserted jumper (default state). When the jumper is pulled, the higher, less sensitive range is active. A jumper is used to toggle between the measurement metric „Pressure“ (linear) and „Air volume“ (square root extraction). The air volume is proportional to the root of the pressure differential between the two hose connections (pressure differential method). Adjustable response time The response time can be adjusted in 2 levels to suppress brief pressure surges and turbulence, e.g. in the air duct. The response time is long when the jumper is inserted (default state). Remove the jumper when the fast response time is desired. V out 10 8 6 4 Output signal toggle The 3-wire output signal version can be toggled. The default output signal is 0 – 10 V; it can be switched to 4 – 20 mA by removing the jumper. The 2-wire version is only available with the 4 – 20 mA output signal.. 2 0 0 20 40 60 Sensor range 80 100 %P Adjusting the switching output (3-wire without display) This functions is used to set the switching output to „interconnected“ for a pressure defined by you. Apply the pressure or the pressure differential at which the switching output should interconnect. Then press button „S“ for 5 sec until the LED blinks rapidly (= switching point saved). The LED lights up as soon as the defined pressure is reached or exceeded. 4 | 6 | Sensor ventilation air conditioning | Data sheet No. 13251 | Version 09-2014 Pressure differential transmitter DDS-M984… DDS-MR984… Programming (versions with display) Sensor ventilation air conditioning | Data sheet No. 13251 | Version 09-2014 | 5 | 6 70.5 65.5 55 50 ø 10 60 Masszeichnungen Masszeichnungen Masszeichnungen Pressure differential transmitter DDS-M984… DDS-MR984… ø10 18 11 7.7 ø 4.5 40 Kanalans Climaset® Dimensioned Befestigungswinkel drawing 6401 Befestigungswinkel 6402 984 mit Kabelverschraubung M16x1,5 984 mit Kabelverschraubung M16x1,5 984 mit Kabelverschraubungø 4M16x1,5 DDS...984... Mounting bracket 6481 Befestigungswinkel 6481 ø5 7 ø4 ø6 10 46 71 19.5 10 7.7 11 ø 16 65.5 21.5 ø5 10 40 60 ø10 18 2 90.5 ø5 40 60 65 50 65 50 ø6 70.5 65.5 ø6 55 50 65 50 60 ø6 0 ø5 0 ø 4.5 40 Befestigun Climaset® 6550/6556 7.5 18 7.5 18 Kanalans Climaset® 19 Befestigungswinkel 6482 21.8 7.5 18 Befestigungswinkel Kanalanschluss für 6481 21.8 gswinkel 6402 57.5 21.8 57.5 57.5 40 Mounting bracket 6482 59 40 ø6 59 8 ø4 .5 .5 2 65.5 100 21.5 ø5 46 71 10 19.5 10 ø 16 ø5 40 60 80 40 60 90.5 ø5 ø6 ø4 8 ø4 .5 .5 0 8 ø4 .5 .5 7 18.5 59 2 40 60 10 ø 6.5 60∞ 19 Kanalanschluss für Duct connection für Kanalanschluss Duct connection für Kanalanschluss Befestigungswinkel 6401 Befestigungswinkel 6402 ® Befestigungswinkel 6401 Befestigungswinkel 6402 Befestigungswinkel 6401 Befestigungswinkel 640 ® ® nipples 6552 nipples 6551 Mounting bracket 6401 Mounting bracket 6402 Climaset 6550/6556 Climaset 6550/6556Climaset 6555/6557 gswinkel 6482 2 ø4 øø 46 40 40 ø4 7.7 60∞ 40 ø4 100 ø5 21.5 10 10 21.5 ø5 40 60 10 40 60 40 Kanalanschluss für ® Befestigungswinkel 6481 Climaset Befestigungswinkel 6482 Befestigungswinkel 6481 Befestigungswinkel 6482 6555/6557 Befestigungswinkel 6481 Befestigungswinkel 648 2 7 7 ø5 ø5 ø5 ø 3.4 18.5 7 18.5 Oppermann Regelgeräte GmbH | Im Spitzhau 1 | 70771 Leinfelden-Echterdingen, Germany ø 16 40 80 2 ø6 ø 3.4 ø6 10 11 40 Kanalanschluss für Climaset® 6555/6557 6482 40 60 ø 16 ø5 ø10 ø 4.5 7.7 ø10 11 18 11 Rubber feedthroughs 6553 ø 4.5 ø 6.5 18 7.7 10 60 18 ø5 ø10 ø 4.5 10 60 60 21.5 ø 25 ø 16 60∞ 80 90.5 65.5 Specifications subject to change. 5 1 ø 6.5 19.5 0 65.5 6 | 6 | Sensor ventilation air conditioning | Data sheet No. 13251 | Version 09-2014 2 .5 602 90.5 90.5 40 ø 25 60 | Fax +49 711 7280527 | [email protected] | www.oppermann-regelgeraete.de 40 Phone +49 711 72723560 2 60 65.5 40 60 0 ø5 70.5 65.5 70.5 65.5 ø4 55 70.5 50 65.5 ø 16 80 100 55 50 0 ø5 0 ø 5 ø 50 0 ø6 ø4 ø5 55 50 0 18.5 ø6 ø5 ø 3.4 6482 ø 16 ø 25