Domekt Cf 700 v

Transcription

Domekt Cf 700 v
DOMEKT
The photo is intended for informational purposes only, exact details may vary.
Domekt CF 700 V
(kompakt RECU 700VCF)
Maximal air flow, m³/h
665
Panel thickness, mm
45
Unit weight, kg
95
Supply voltage, V
1~230
Maximal operating current, A
A
HE 12 / HW 3,8
Thermal efficiency
of heat recovery, %
87
Reference flow rate, m³/s
0,13
Reference pressure difference, Pa
50
SPI, W/(m³/h)
47
C5.1
665 m³/h
0,31
Filters dimensions B×H×L, mm
390×300×46-M5
Electric power input of the fan drive
at reference flow rate, W
72
Electric power input of the fan drive
at maximum flow rate, W
177
Electric air heater capacity, kW / ∆t, °C
Control panel
2 / 11,9
KOMFOVENT C5.1
Temperature efficiency
Winter
Summer
Outside temperature, °C
-23
-15
-10
-5
0
30
After heat exchanger*, °C
15,6
16,4
16,8
17,3
18,2
23,4
* indoor +22°C, 20 % RH
Acoustic data
Hot water duct air heater (DH)**
A-weighted sound power level Lwa, dB(A)
at reference flow rate
Winter
Supply inlet
47
Supply outlet
67
Exhaust inlet
52
Exhaust outlet
67
Casing
47
A-weighted sound pressure level LPA, dB(A)
10 m² normally isolated room, distance from casing – 3 m.
Surroundings
36
Water temperature in/out, °C
90/70
80/60
70/50
60/40
Capacity, kW
1,4
1,4
1,4
1,4
Flow rate, dm³/h
63
63
63
62
Pressure drop, kPa
1
1
1
1
2,9
1,9
15,6/22
Temperature in/out, °C
4,8
Maximal capacity, kW
3,8
½
Connection, ”
360×320×270
Dimensions, mm
DH-200
Hot water duct heater type
** option
Performance
500
Shown as left (L1)
Air flow rate (m3/s)
0 0,030,060,09 0,120,150,180,21
D
Shown as right (R1)
SPI 0,28
200
SPI 0,21
370
SPI 0,35
300
0
A
D
A
B
C
D
1145
1040
400
100
A
C
B
outdoor intake
supply air
extract indoor
exhaust air
SPI 0,14
455
155
490
160
92
1020
155
Temperature efficiency
97
B
A
С
87
82
100 200300 400500 600700 800
Air flow rate (m3/h)
D=15 mm
700
0 100200300400500600 700800
Air flow rate (m3/h)
Temp. efficiency (%)
C
B
90
Static pressure (Pa)
Unit with standard equipment
410
200 (4×)
D
455
Indoor and outdoor ∆T=13°C re: Ecodesign 1254/2014.
60
UAB AMALVA reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.
If data of performance do not correspond to data in the selection software, please refer to data shown in software.
KK2-16-10

Similar documents

kompakt - komfovent

kompakt - komfovent ‡ -HĪHOL XU]ąG]HQLH PRQWRZDQH MHVW Z SRPLHV]F]HQLX R GXĪHM ZLOJRWQRĞFL Z SU]\SDGNX QLVNLFK WHPSHUDWXU ]HZQĊWU]Q\FKPRĪHQDVWąSLüZ\NURSOHQLHZLOJRFLQDREXGRZLHFHQWUDOL ‡ : ZDUXQ...

More information