Wave Cast - Industrial Solutions

Transcription

Wave Cast - Industrial Solutions
GE
Industrial Solutions
Wave Cast
Dry-type Transformers
Reliable. Efficient.
About GE
GE (NYSE: GE) works on things that matter. The best people and the best technologies taking on
the toughest challenges. Finding solutions in energy, health and home, transportation and
finance. Building, powering, moving and curing the world. Not just imagining. Doing. GE works.
For more information, visit the company's website at www.ge.com.
Industrial Solutions
Industrial Solutions, a GE heritage business, is leading the future of electrification with
advanced technologies that protect and control the distribution of electricity throughout a
facility's infrastructure. We provide customers, across various industries, with end-to-end
product and service solutions that ensure the reliability and protection of the electrical
infrastructure; from the substation, to a facility's critical equipment, and all the power
technologies in between.
Find more information at www.geindustrial.com
Honour
2013
2010 World's Most Innovative Companies
2013 World’s Most Admired Companies
2012 World’s Most Respected Companies
2012 Best Global Brand
2010 World’s Most Respected Companies
Wave Cast
Dry-type Transformers
Reliable. Efficient.
Content
General Introduction
GE
GE Industrial Solutions
Product Description
Wave Cast Transformers . . . . . . . . . . . . . . . . . . . . . 02
Certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 03
Product Introduction
Vacuum Cast Windings . . . . . . . . . . . . . . . . . . . . . . . 04
Winding Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . 05
Cores . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 06
Enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 06
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 07
Applicable Standards . . . . . . . . . . . . . . . . . . . . . . . . . 08
Configurations
IEC Transformer Technical Specifications . . . . . . 09
IEEE Transformer Technical Specifications . . . . . 13
Enclosures Technical Specifications . . . . . . . . . . . 16
Typical Incoming and Outgoing Connections . . 17
IP54 Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Typical Electrical Drawings . . . . . . . . . . . . . . . . . . . 20
Other Information
Testing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Packaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Handling & Transporting . . . . . . . . . . . . . . . . . . . . . . 23
Foundation Installation . . . . . . . . . . . . . . . . . . . . . . . 24
Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Wave Cast Dry-type Transformers
Wave Cast
Dry-type Transformers
Solutions
Product Description
Reliable. Efficient.
02
Wave Cast coil transformers from
Typical applications of cast coil
GE are characterized by high safety,
transformers include:
reliability, energy-savings, and convenient
●● Comercial buildings, hospitals,
maintenance. Advanced design of the
universities, residential areas
winding assembly establishes superior
●● Steel mills
performance to meet today’s exacting
●● Industrial critical power solutions
needs. Indoors or outdoors, they are
●● Wind mills
designed for use in the most demanding
●● Offshore drilling platforms
and diverse environments and in all
●● Pulp & paper mills
applications requiring reliable power.
●● Chemical plants
●● Cement & mining operations
●● Automotive industry
●● High rise buildings & waterfront
installations
Wave Cast Dry-type Transformers
Certification
GE has passed the entire routine and type test carried
out by third party laboratories, such as KEMA, CTQC
(China). The test approvals include C2 climate class,
E2 environment class, F1 fire behavior grade, 5S
short-circuit capability, typical lightning impulse and
temperature rise test.
IEC and ANSI requirements. GE designs
transformers boast high efficiency
and manufactures its cast coils to be
stemming from the technical
among the strongest in the industry.
specification. With low no-load loss
●● Impervious to adverse atmospheric
as well as total ownership cost (TOC)
transformers and in a manner similar
savings.
Cast coil transformers have several
coil transformers are optimal for use in
advantages over alternative transformer
harsh environments. The epoxy casting
technologies.
is extremely inert and renders the
●● Environmental safety. It is understood
windings impervious to moisture, dirt
and corrosive elements.
enhanced safety as they are free
●● Suitability for simple indoor installation
from flammable oil insulation. For
and convenient maintenance. Unlike
this reason, it is widely used in urban
the case with liquid-filled transformers,
power grids, commercial buildings,
indoor installations do not require an
hospitals and universities among other
automatic fire extinguishing system or
applications.
fire vault, oil checking or replacing, or
●● High capability of short-circuit
withstand. Because of the strong
protection provided by the vacuum
and load loss, there are energy savings
conditions. Unlike ventilated dry-type
to liquid-filled transformers, GE cast
that cast resin transformers provide
●● High efficiency. GE Wave Cast
Product Description
have proven this strength well beyond
a liquid confinement area. This benefits
long term maintenance.
●● Extended ratings. GE cast coil
cast epoxy encapsulated coils, Wave
transformers can be provided with the
Cast transformers are stronger than
highest self-cooled and fan-cooled
either liquid-filled or ventilated dry-
extended ratings of any transformers
type transformers. Short circuit tests
in their size class.
03
Wave Cast Dry-type Transformers
Vacuum Cast Windings
Tough epoxy provides strength.
Wave Cast vacuum cast windings are
Process control ensures that the coils are
Other advantages of vacuum cast
highly engineered components requiring
void-free and prevents partial discharges
construction include:
specific expertise in electrical, material,
within the resin material; or cracking of
●● Dielectric strength - Windings are
thermal and mechanical engineering. The
process of measuring, mixing, heating
and vacuum casting materials into the
windings is equally critical.
Cast coils are solid vacuum cast with
epoxy resin compound. The epoxy is
Product Introduction
applied under vacuum to hermetically seal
the windings in a highly durable epoxy.
and operating temperatures.
The principal advantage of solid vacuum
cast construction is that the cast coil
seals out harmful fumes, air and moisture,
preventing them from entering the
windings. The solid cast transformer
Quartz filler is included, which provides
achieves a maximum degree of resin
increased viscosity to the resin, better
impregnation during the casting process.
impregnation and increased capability to
withstand short circuits. The epoxy mixture
corona-free at twice the rated voltage.
●● Mechanical strength - Short circuit
capability meets and exceeds the
requirements of IEC60076-11:2004 and
IEEE standard C57.12.91-2001.
●● Thermal strength - Withstands
fluctuating operating temperatures
ranging from -40°C to 180°C without
damage to the epoxy insulation.
●● Insulation system - Tested to ANSI/
NEMA and IEC standards, turn-by-turn
is carefully designed to provide maximum
and layer-by-layer electrical insulation
strength and environmental protection
components (polyimide film) are
and yet minimize the temperature
recognized at 180°C.
differential through the coil thickness.
04
the epoxy over a wide range of ambient
Wave Cast Dry-type Transformers
Winding Assembly
Both high- and low-voltage
windings are made of copper
foil or foil strip and vacuum
cast in metal molds as separate
concentric cylinders.
High-voltage windings are wound using
foil strip technology. Multiple layers of
polyimide film (180°C system) or DUPONT
@MYLAR (155°C system) provide turn
insulation. Individual coil sections are
wound directly on the inner winding mold
and then connected in series by welding.
free assembly capable of withstanding
Why do we use foil strip windings?
high electrical stress.
They are used to reduce the electrical field
Low-voltage windings use foil conductor
density between layers. For example,
construction. A fiberglass mesh provides
the typical layer electrical field density of
support for the inside of the windings. Full-
1000KVA/10/0.4kV transformer (made of
width sheet conductor that has SCC layer
copper wire) is 2kV/mm, while the typical
insulation is wound onto the cylinder. Start
value for foil windings it is 0.3kV/mm.
and finish lead bars are TIG welded to the
The capability to withstand over-voltage,
foil conductor. Low-voltage windings are
such as lightning pulse and power, power
also vacuum cast in a metal mold using
frequency withstand voltage, are greatly
the same technique as the high-voltage
improved.
Product Introduction
Advanced total foil strip technology.
windings.
External molds are assembled and placed
in a vacuum chamber. Coils are preheated under high vacuum to remove
trapped moisture. A special mixture of
epoxy resin and quartz powder flows
into the mold through an opening in the
molding assembly. After pouring, the
molds are cured in a time-temperature
process controlled oven. The result is a
reliable, vacuum cast winding with an
unusually high strength, an essentially void
05
Wave Cast Dry-type Transformers
Cores
Construction ensures optimal
performance.
Additional protection against harsh
outdoor or indoor environments is
provided through electrostatically
Transformer cores utilize mitered step-
deposited dry powder paint baked onto
lap technology to optimize performance
a phosphate treated surface. The paint
and minimize sound levels. Cores
finish is neat, clean and highly resistant to
are constructed of non-aging, high
corrosion.
permeability, grain-oriented silicon steel
A variety of optional enclosures is
laminations without punched holes,
available: drip proof roofs, supplemental
Product Introduction
offering high magnetic permeability.
Core laminations are free of burrs and
stacked without gaps, resulting in the
lowest possible losses from magnetic
hysteresis and eddy currents. The core
clamping brackets are designed to provide
an even distribution of clamping forces
to the core yokes and legs, and are rigidly
braced to reduce sound levels and losses.
Other core construction benefits include:
●● Magnetic flux densities, kept well below
saturation point
●● Surfaces of the core, clamps and tie
rods are all treated against corrosion
filters, screens, hinged panels and special
Enclosures
Withstands the harshest indoor
and outdoor environments.
Enclosures are suitable for lifting, jacking,
rolling or skidding with provisions for
lifting the transformer from its base. The
standard indoor enclosures are from
IP20 to IP54 and NEMA 1, Category C
construction.
While core and coil technologies have
been enhanced to combat caustic
and humid environments, Wave Cast
transformers are further protected
by properly designed enclosures. GE
enclosures are custom fabricated using
heavy gauge sheet steel. Optional
aluminum and stainless steel enclosures
are available.
06
hardware. Other modifications can also be
made to extend the enclosure, add bottom
plates, add end sheets and/or include
special cutouts for specific applications.
Wave Cast Dry-type Transformers
Accessories
Temperature monitor and fan
controller
The controller can display the operating temperature of windings, start and shut off
the cooling fans and provides alarm/trip signal (normal open voltage-free contact),
ensuring effective monitoring and protection of the transformer.
The PT100 sensors are inserted into each LV winding to transmit temperature signals,
which can be displayed on the controller panel.
Main functionality:
●● Set alarms and trip temperature levels
●● Record the maximum temperature in non-volatile memory
●● Send audible over-temperature alarm, alarm signal and trip signal
●● Start and stop fans automatically or manually
●● Provide communication interface (optional)
Cross flow fan
The low noise cross flow fan reduces
the winding temperature, enhances the
overload ability, and prolongs the service
life of the transformer.
The rated power can be increased by 2540% when forced air-cooling is used.
Rollers
transformer or enclosure to facilitate
moving in two directions.
BWD-3K series temperature controller
Models
BWD-3K130
Functions
Cyclic Display Temperature, Auto Control Fan, Over Temperature Alarm,
Auto-Power-cut (Trip). Sensor Disorder Alarm
BWD-3K130A
Share the funcitons of BWD-3K130 and Equipped with RS232 or RS232 or
RS485 Interfaces that outputs the Temperature, Fan States and Sensor
States
BWD-3K130B
Share the functions of BWD-3K130 and Provide the outputs of three 4-20mA
Analog Currents or 1-5V Analog Voltages correspond to three temperature
values
BWD-3K130AB
Have the functions of both BWD-3K130A and BWD-3K130B
Product Introduction
Four rollers can be equipped under a
Enclosures
GE cast coil transformer enclosures are
available to meet or exceed IP20/IP21/
IP23/IP30/IP31/IP33/IP40/IP41/IP43 and
IP54 enclosure requirements typical for
indoor or outdoor usage.
07
Wave Cast Dry-type Transformers
Applicable Standards
IEC Transformer
IEC 60076-1 Power transformers – Part 1: General
IEC 60076-2 Power transformers – Part 2: Temperature rise
IEC 60076-3 Power transformers – Part 3: Insulation levels, dielectric tests and external clearances in air
IEC 60076-4 Power transformers – Part 4: Guide to lightning impulse and switching impulse testing – Power transformers and reactors
IEC 60076-5 Power transformers – Part 5: Ability to withstand short-circuit
IEC 60076-8 Power transformers – Part 8: Application guide
IEC 60076-10 Power transformers – Part 10: Determination of sound levels
IEC 60076-10-1 Power transformers – Part 10-1: Determination of transformer and reactor sound levels – User guide
IEC 60076-11 Power transformers – Part 11: Dry-type transformers
IEC 60076-12 Power transformers – Part 12: Loading guide for dry-type power transformers
IEEE Transformer
IEEE Std C57.12.01 IEEE Standard General Requirements for Dry-Type Distribution and Power Transformers, Including Those with SolidCast and/or Resin Encapsulated Windings
Product Introduction
IEEE Std C57.12.91 IEEE Standard Test Code for Dry-Type Distribution and Power Transformers
08
Wave Cast Dry-type Transformers
IEC Transformer Technical Specifications
Standard insulation level
Conductors
Copper or Aluminum
Frequency (Hz)
50
Off-load tapping range
±2×2.5%, ±5%
Insulation class
F (155°C) or H (180°C)
Temperature rise
100K(F) or 125K(H)
Ambient temperature (°C)
Max. 40, Min. -25
Altitude (m above sea level)
≤ 1,000
Connection
Dyn5, Dyn11
Cooling
Voltage fluctuation
Highest voltage for
equipment Um
(r.m.s)
Rated short duration
separate source AC
withstand voltage
(r.m.s)
Rated lightning
impulse withstand
voltage (peak value)
kV
kV
kV
≤ 1.1
3
-
3.6
10
40
7.2
20
60
12
28
75
17.5
38
95
AN, AN/AF
24
50
125
±5%
36
70
170
Optional Accessories
(indicated on Checklist, page 25)
Special service conditions should be clearly stated
●● Coastal areas
●● Protective enclosures (GBN series)
●● Offshore installations
●● Fans for AF rating
●● High harmonic wave
●● Rollers for temporary moving on site
●● Used for convertors
●● Zero current transformers
●● Used for rectifier circuits
●● Surge arresters
Configurations
General data
●● Bar fuse for controller wiring from LV terminal
●● Space heaters & thermostat for space heaters
●● Lighting
●● Limit switch for enclosure doors
●● Electromagnetic lock for enclosure door
●● Flexible connector
09
Wave Cast Dry-type Transformers
IEC Transformer Technical Specifications
Typical outline for IP00 transformer
Lv Terminal
Neutral Terminal
Hook
Hv Terminal
Configurations
Height

10
High Voltage !
Cut Out Power Before
Approach.


High Voltage !
High Voltage !
Cut Out Power Before
Approach.
Cut Out Power Before
Approach.
Surface Hot !
Surface Hot !
Surface Hot !
Do Not Touch Immediately
After Power Off.
Do Not Touch Immediately
After Power Off.
Do Not Touch Immediately
After Power Off.
Wheels Distance
Width
Length
Wave Cast Dry-type Transformers
Voltage class 12 kV, copper windings
Rated Power
High-voltage
Tapping Range
Low-Voltage
Frequency
Vector Group
No-load Loss
Load Loss 75℃
Load Loss 120℃
Short-circuit Impedance
Noise LPA
Length
Width
Height
Weight
Distance Between Rollers
kVA
kV
/
V
Hz
/
W
W
W
%
dB
mm
mm
mm
kg
mm
250
315
400
730
2400
2780
4
46
1200
750
970
1200
660
890
2990
3400
4
46
1230
750
1040
1330
660
250
730
2400
2780
4
46
1250
750
1050
1100
660
500
630
1600
2000
2500
990
3520
4000
4
46
1260
750
1110
1500
660
800
1000
1250
10, 11
±2 ×2.5%, ±3X2.5%, ±4X2.5%, ±5%
400, 415, 433
50
Dyn11, Dyn5, YNyn0, YNd5*
1180
1350
1550
1800
2100
4250
5300
6100
7110
8500
4900
6000
7000
8180
9750
4
6
6
6
6
48
48
50
50
50
1310
1460
1470
1500
1580
750
750
920
920
920
1160
1170
1280
1400
1440
1750
2010
2310
2710
3190
660
660
820
820
820
2450
10400
12000
6
52
1760
920
1510
4060
820
3100
12800
14400
6
54
1850
920
1670
4870
820
3600
15400
17000
6
56
2010
1170
1740
5600
1070
315
400
500
1600
2000
2500
890
2990
3400
4
46
1310
750
1090
1280
660
990
3520
4000
4
46
1320
750
1200
1490
660
2450
10400
12000
6
52
1740
920
1810
3750
820
3100
12800
14400
6
54
1860
920
1840
4300
820
3600
15400
17000
6
56
2070
1170
1890
5500
1070
Rated Power
High-voltage
Tapping Range
Low-voltage
Frequency
Vector Group
No-load Loss
Load Loss 75℃
Load Loss 120℃
Short-circuit Impedance
Noise LPA
Length
Width
Height
Weight
Distance Between Rollers
kVA
kV
/
V
Hz
/
W
W
W
%
dB
mm
mm
mm
kg
mm
630
800
1000
1250
10, 11
±2 ×2.5%, ±3X2.5%, ±4X2.5%, ±5%
400, 415, 433
50
Dyn11, Dyn5, YNyn0, YNd5*
1180
1350
1550
1800
2100
4250
5300
6100
7110
8500
4900
6000
7000
8180
9750
4
6
6
6
6
48
48
50
50
50
1350
1520
1560
1610
1680
750
750
920
920
920
1300
1300
1380
1540
1640
1680
1850
2190
2560
3050
660
660
820
820
820
Configurations
Voltage class 12 kV, aluminum windings
Voltage class 24 kV, copper windings
Rated Power
High-voltage
Tapping Range
Low-voltage
Frequency
Vector Group
No-load Loss
Load Loss 75℃
Load Loss 120℃
Short-circuit Impedance
Noise LPA
Length
Width
Height
Weight
Distance Between Rollers
kVA
kV
/
V
Hz
/
W
W
W
%
dB
mm
mm
mm
kg
mm
315
400
500
970
3300
3800
6
46
1270
750
1230
1350
660
1150
4200
4850
6
46
1350
750
1300
1600
660
1350
5040
5790
6
48
1440
750
1380
1900
660
315
400
500
970
3300
3800
6
46
1440
750
1270
1200
660
1150
4200
4850
6
46
1500
750
1360
1450
660
1350
5040
5790
6
48
1580
750
1500
1850
660
630
800
1000
1250
20, 22
±2 ×2.5%, ±3X2.5%, ±4X2.5%, ±5%
400, 415, 433
50
Dyn11, Dyn5, YNyn0, YNd5*
1530
1750
2070
2400
5950
7190
8500
10050
6840
8260
9780
11500
6
6
6
6
48
50
50
50
1470
1540
1620
1710
920
920
920
920
1440
1520
1610
1700
2200
2600
3050
3600
820
820
820
820
1600
2000
2500
2790
12050
13870
6
52
1850
920
1750
4500
820
3240
14250
16400
6
54
1980
1170
1800
5400
1070
3870
18500
21280
6
56
2100
1170
1900
6400
1070
1600
2000
2500
2790
12050
13870
6
52
1890
920
1840
3970
820
3240
14250
16400
6
54
1980
1170
1900
4780
1070
3870
18500
21280
6
56
2040
1170
2040
5450
1070
Voltage class 24 kV, aluminum windings
Rated Power
High-voltage
Tapping Range
Low-voltage
Frequency
Vector Group
No-load Loss
Load Loss 75℃
Load Loss 120℃
Short-circuit Impedance
Noise LPA
Length
Width
Height
Weight
Distance Between Rollers
kVA
kV
/
V
Hz
/
W
W
W
%
dB
mm
mm
mm
kg
mm
630
800
1000
1250
20, 22
±2 ×2.5%, ±3X2.5%, ±4X2.5%, ±5%
400, 415, 433
50
Dyn11, Dyn5, YNyn0, YNd5*
1530
1750
2070
2400
5950
7190
8500
10050
6840
8260
9780
11500
6
6
6
6
48
50
50
50
1600
1650
1680
1770
920
920
920
920
1540
1720
1740
1750
1980
2410
2580
3130
820
820
820
820
*Special order, please contact GE.
11
Wave Cast Dry-type Transformers
IEC Transformer Technical Specifications
Voltage class 40.5 kV, copper windings
Rated Power
High-voltage
Tapping Range
Low-voltage
Frequency
Vector Group
No-load Loss
Load Loss 75℃
Load Loss 120℃
Short-circuit Impedance
Noise LPA
Length
Width
Height
Weight
Distance Between Rollers
kVA
kV
/
V
Hz
/
W
W
W
%
dB
mm
mm
mm
kg
mm
400
500
1370
4700
5400
6
48
1520
920
1530
1750
820
630
800
2000
2500
1620
5780
6650
6
48
1540
920
1650
2000
820
1000
1250
1600
33, 35
±2 ×2.5%, ±3X2.5%, ±4X2.5%, ±5%
400, 415, 433
50
Dyn11, Dyn5, YNyn0, YNd5*
1860
2160
2430
2830
3240
6690
7930
9090
11000
13500
7690
9120
10450
12730
15500
6
6
6
6
6
48
50
50
50
52
1590
1640
1770
1850
1950
920
920
920
920
920
1710
1740
1800
1820
1900
2550
2900
3400
4100
5000
820
820
820
820
820
3820
15870
18240
6
54
1960
1270
2040
5580
1070
4450
19000
21850
6
56
2140
1270
2170
6600
1070
400
500
630
2000
2500
1370
4700
5400
6
48
1740
920
1450
1900
820
1620
5780
6650
6
48
1760
920
1560
2200
820
3820
15870
18240
6
54
2090
1270
2080
5200
1070
4450
19000
21850
6
56
2150
1270
2190
6000
1070
Configurations
Voltage class 40.5 kV, aluminum windings
Rated Power
High-voltage
Tapping Range
Low-voltage
Frequency
Vector Group
No-load Loss
Load Loss 75℃
Load Loss 120℃
Short-circuit Impedance
Noise LPA
Length
Width
Height
Weight
Distance Between Rollers
kVA
kV
/
V
Hz
/
W
W
W
%
dB
mm
mm
mm
kg
mm
800
1000
1250
1600
33, 35
±2 ×2.5%, ±3X2.5%, ±4X2.5%, ±5%
400, 415, 433
50
Dyn11, Dyn5, YNyn0, YNd5*
1860
2160
2430
2830
3240
6690
7930
9090
11000
13500
7690
9120
10450
12730
15500
6
6
6
6
6
48
50
50
50
52
1760
1770
1820
1890
2010
920
920
920
920
920
1740
1830
1850
1890
1900
2400
2700
3100
3600
4200
820
820
820
820
820
Voltage class 40.5 kV, copper windings
Rated Power
High-voltage
Tapping Range
Low-voltage
Frequency
Vector Group
No-load Loss
Load Loss 75℃
Load Loss 120℃
Short-circuit Impedance
Noise LPA
Length
Width
Height
Weight
kVA
kV
/
kV
Hz
/
W
W
W
%
dB
mm
mm
mm
kg
1000
1250
1600
2700
9500
10900
6
53
1890
920
1700
3600
3130
11240
12900
6
54
2010
920
1800
4300
3700
13450
15500
6
55
2130
920
1900
5100
Distance Between Rollers
mm
820
820
820
*Special order, please contact GE.
12
2000
3150
4000
5000
33, 35
±2 ×2.5%, ±3X2.5%, ±4X2.5%, ±5%
3.15, 6, 6.3, 10, 10.5, 11
50
Dyn11, Dyn5, YNyn0, YNd5*
4230
4860
6000
7000
8300
15800
18900
21300
25600
30500
18240
21800
24500
29500
34900
7
7
8
8
8
55
55
58
62
63
2190
2310
2430
2500
2760
1270
1270
1270
1270
1675
1960
2050
2130
2260
2300
5900
7000
7800
9200
11500
1070
2500
1070
1070
1475
1475
6300
9900
35500
40900
8
63
2850
1675
2550
13200
8000
11300
40000
46000
9
65
3000
1675
2740
16000
1475
1475 (W)
2040 (L)
10000
12800
48000
55000
9
65
3150
1675
2900
19000
1475
2040 (L)
Wave Cast Dry-type Transformers
IEEE Transformer Technical Specifications
Standard insulation level
Low-frequency
Basic lightning impulse
voltage
insulation level (crest)
insulation levels (r.m.s)
Conductors
Copper or Aluminum
Frequency (Hz)
60
Off-load tapping range
±2×2.5%, ±5%
kV
Insulation class
F (155°C) or H (180°C)
Temperature rise
100K(F) or 115K(H)
Ambient temperature (°C)
Max. 40, Min. -25
Altitude (m above sea level)
≤ 1,000
Connection
Dyn5, Dyn11
15
34
95
Cooling
AA, AA/FA
25
50
110
Voltage fluctuation
±5%
34.5
70
150
Optional Accessories
(indicated on Checklist, page 25)
Nominal Voltage
kV
kV
1.2
4
10
2.5
10
20
5
12
30
8.7
19
45
Special service conditions should be clearly stated
●● Coastal areas
●● Protective enclosure (GBN series)
●● Offshore installations
●● Fans for AF rating
●● High harmonic content
●● Rollers for temporary moving on site
●● Used for convertors
●● Zero current transformers
●● Used for rectifier circuits
●● Surge arresters
Configurations
General data
●● Bar fuse for controller wiring from LV terminal
●● Space heaters & thermostat for space heaters
●● Lighting
●● Limit switch for enclosure doors
●● Electromagnetic lock for enclosure door
●● Flexible connector
13
Wave Cast Dry-type Transformers
IEEE Transformer Technical Specifications
Voltage class 15 kV, copper windings
Rated Power
High-voltage
Tapping Range
Low-voltage
Frequency
Vector Group
No-load Loss
Load Loss 75℃
Load Loss 120℃
Short-circuit Impedance
Noise LPA
Length
Width
Height
Weight
Distance Between Rollers
kVA
kV
/
V
Hz
/
W
W
W
%
dB
mm
mm
mm
kg
mm
225
300
400
1100
1920
2200
4
46
1220
750
970
1010
660
1300
2500
2800
4
46
1290
750
1050
1250
660
1450
3150
3650
4
46
1310
750
1110
1450
660
500
630
750
1000
1250
13.2, 13.8
±2 ×2.5%, ±3X2.5%, ±4X2.5%, ±5%
220, 400, 480
60
Dyn11, Dyn5, YNyn0, YNd5*
1600
1700
1850
2000
2400
3750
4600
5700
6500
7300
4300
5300
6400
7500
8400
4
6
6
6
6
48
48
50
50
50
1320
1470
1470
1520
1590
750
750
920
920
920
1180
1170
1280
1360
1430
1650
1920
2200
2600
3150
660
660
820
820
820
1500
2000
2500
3000
9570
11000
6
52
1710
920
1540
3750
820
3400
12200
14100
6
54
1770
920
1550
4200
820
4100
15200
17500
6
56
1850
1170
1640
5000
1070
1500
2000
2500
3000
9570
11000
6
52
1760
920
1750
3500
820
3400
12200
14100
6
54
1790
920
1770
3800
820
4100
15200
17500
6
56
1890
1170
1800
4600
1070
1500
2000
2500
2900
10900
12500
6
52
1670
920
1700
3600
820
3800
12600
14500
6
54
1830
1170
1760
4700
1070
4600
14500
16500
6
56
2000
1170
1820
5700
1070
Configurations
Voltage class 15 kV, aluminum windings
Rated Power
High-voltage
Tapping Range
Low-voltage
Frequency
Vector Group
No-load Loss
Load Loss 75℃
Load Loss 120℃
Short-circuit Impedance
Noise LPA
Length
Width
Height
Weight
Distance Between Rollers
kVA
kV
/
V
Hz
/
W
W
W
%
dB
mm
mm
mm
kg
mm
225
300
400
1100
1920
2200
4
46
1260
750
1170
950
660
1300
2500
2800
4
46
1310
750
1210
1150
660
1450
3150
3650
4
46
1320
750
1220
1300
660
225
300
400
950
2900
3350
6
46
1250
750
1190
900
660
1000
3750
4300
6
46
1280
750
1240
1100
660
1300
4350
5000
6
46
1310
750
1290
1450
660
500
630
750
1000
1250
13.2, 13.8
±2 ×2.5%, ±3X2.5%, ±4X2.5%, ±5%
220, 400, 480
60
Dyn11, Dyn5, YNyn0, YNd5*
1600
1700
1850
2000
2400
3750
4600
5700
6500
7300
4300
5300
6400
7500
8400
4
6
6
6
6
48
48
50
50
50
1400
1560
1580
1670
1710
750
750
920
920
920
1340
1350
1380
1540
1680
1550
1800
2000
2300
2800
660
660
820
820
820
Voltage class 25 kV, copper windings
Rated Power
High-voltage
Tapping Range
Low-voltage
Frequency
Vector Group
No-load Loss
Load Loss 75℃
Load Loss 120℃
Short-circuit Impedance
Noise LPA
Length
Width
Height
Weight
Distance Between Rollers
kVA
kV
/
V
Hz
/
W
W
W
%
dB
mm
mm
mm
kg
mm
*Special order, please contact GE.
14
500
630
750
1000
1250
23
±2 ×2.5%, ±3X2.5%, ±4X2.5%, ±5%
220, 480
60
Dyn11, Dyn5, YNyn0, YNd5*
1500
1750
2000
2300
2600
4900
5650
6350
7400
9570
5600
6500
7300
8500
11000
6
6
6
6
6
48
48
50
50
50
1410
1470
1580
1590
1620
750
920
920
920
920
1350
1390
1420
1610
1650
1650
1900
2400
2900
3100
660
820
820
820
820
Wave Cast Dry-type Transformers
Voltage class 25 kV, aluminum windings
Rated Power
High-voltage
Tapping Range
Low-voltage
Frequency
Vector Group
No-load Loss
Load Loss 75℃
Load Loss 120℃
Short-circuit Impedance
Noise LPA
Length
Width
Height
Weight
Distance Between Rollers
kVA
kV
/
V
Hz
/
W
W
W
%
dB
mm
mm
mm
kg
mm
225
300
400
950
1950
2200
6
46
1430
750
1320
1050
660
1200
2175
2500
6
46
1490
750
1340
1250
660
1300
3480
4000
6
46
1500
750
1360
1350
660
500
630
750
1000
1250
23
±2 ×2.5%, ±3X2.5%, ±4X2.5%, ±5%
220, 480
60
Dyn11, Dyn5, YNyn0, YNd5*
1500
1750
2000
2400
2800
4900
5650
6350
6790
7830
5600
6500
7300
7800
9000
6
6
6
6
6
48
48
50
50
50
1530
1570
1590
1650
1790
750
920
920
920
920
1410
1480
1520
1680
1690
1600
1750
2100
2550
3000
660
820
820
820
820
1500
2000
2500
3400
10100
11600
6
52
1830
920
1820
3400
820
4200
11750
13500
6
54
1980
1170
1840
4450
1070
5000
12600
14500
6
56
2040
1170
1980
5400
1070
Rated Power
High-voltage
Tapping Range
Low-voltage
Frequency
Vector Group
No-load Loss
Load Loss 75℃
Load Loss 120℃
Short-circuit Impedance
Noise LPA
Length
Width
Height
Weight
Distance Between Rollers
kVA
kV
/
V
Hz
/
W
W
W
%
dB
mm
mm
mm
kg
mm
500
630
1800
4350
5000
6
48
1530
920
1620
2100
660
2300
5400
6200
6
48
1690
920
1630
2400
820
750
1000
1250
1500
34.5
±2 ×2.5%, ±3X2.5%, ±4X2.5%, ±5%
400, 480
60
Dyn11, Dyn5, YNyn0, YNd5*
2500
2800
3300
4000
6090
8250
9570
11300
7000
9500
11000
13000
6
6
6
6
50
50
50
52
1740
1770
1820
1880
920
920
920
920
1640
1730
1820
1840
2680
3000
3600
4300
820
820
820
820
2000
2500
4600
12650
14500
6
54
1940
1270
1930
5000
1070
5400
14350
16500
6
56
2060
1270
1940
6050
1070
750
2000
2500
5000
12650
14500
6
54
2130
1270
1950
4900
1070
5400
14350
16500
6
56
2150
1270
2170
5500
1070
Configurations
Voltage class 34.5 kV, copper windings
Voltage class 34.5 kV, aluminum windings
Rated Power
High-voltage
Tapping Range
Low-voltage
Frequency
Vector Group
No-load Loss
Load Loss 75℃
Load Loss 120℃
Short-circuit Impedance
Noise LPA
Length
Width
Height
Weight
Distance Between Rollers
kVA
kV
/
V
Hz
/
W
W
W
%
dB
mm
mm
mm
kg
mm
500
630
2000
3150
3600
6
48
1770
920
1550
2000
820
2100
4780
5500
6
48
1800
920
1720
2100
820
1000
1250
1500
34.5
±2 ×2.5%, ±3X2.5%, ±4X2.5%, ±5%
400, 480
60
Dyn11, Dyn5, YNyn0, YNd5*
2500
2800
3300
4200
6090
7400
9570
11300
7000
8500
11000
13000
6
6
6
6
50
50
50
52
1810
1820
1880
1980
920
920
920
920
1750
1780
1850
1930
2500
2900
3400
4000
820
820
820
820
*Special order, please contact GE.
15
Wave Cast Dry-type Transformers
Enclosures Technical Specifications
10kV, 11kV, 13.2kV, 13.8kV Enclosure
20kV, 22kV, 23kV Enclosure
Enclosure Nominal Dimensions (mm)
kVA
Configurations
160
Cable entry or bar top entry
Enclosure Nominal Dimensions (mm)
Bar side entry
Height
Width
Depth
Height
Width
Depth
2200
1600
1200
2200
1800
1200
315
Cable entry or bar top entry
Bar side entry
Height
Width
Depth
Height
Width
Depth
2200
1800
1400
2200
2000
1400
200
2200
1600
1200
2200
1800
1200
400
2200
1800
1400
2200
2000
1400
250
2200
1600
1200
2200
1800
1200
500
2200
2000
1400
2200
2200
1400
315
2200
1600
1200
2200
1800
1200
630
2200
2000
1600
2200
2200
1600
400
2200
1600
1200
2200
1800
1200
800
2200
2000
1600
2200
2200
1600
500
2200
1600
1200
2200
1800
1200
1000
2200
2200
1600
2200
2400
1600
630
2200
1800
1400
2200
2000
1400
1250
2200
2200
1600
2200
2400
1600
800
2200
1800
1400
2200
2000
1400
1600
2400
2400
1600
2400
2400
1600
1000
2200
2000
1400
2200
2200
1400
2000
2400
2600
1800
2400
2600
1800
1250
2200
2000
1400
2200
2200
1400
2500
2400
2600
1800
2400
2600
1800
3150
2600
2800
1800
2600
2800
1800
1600
2200
2200
1400
2200
2400
1400
2000
2200
2400
1600
2200
2400
1600
2500
2200
2400
1600
2200
2600
1600
3150
2400
2600
1600
2400
2600
1600
33kV, 34.5kV, 35kV Enclosure
Enclosure Nominal Dimensions (mm)
kVA
630
16
kVA
Cable entry or bar top entry
Bar side entry
Height
Width
Depth
Height
Width
Depth
2200
2400
1800
2200
2400
1800
800
2200
2400
1800
2200
2400
1800
1000
2400
2600
1800
2400
2600
1800
1250
2400
2600
1800
2400
2600
1800
1600
2600
2800
1800
2600
2800
1800
2000
2600
2800
2000
2600
2800
2000
2500
2600
3000
2000
2600
3000
2000
3150
2800
3000
2000
2800
3000
2000
4000
2800
3200
2400
2800
3200
2400
5000
3000
3600
2400
3000
3600
2400
6300
3200
3600
2400
3200
3600
2400
8000
3400
3800
2400
3400
3800
2400
10000
3600
3800
2400
3600
3800
2400
Wave Cast Dry-type Transformers
Typical Incoming and Outgoing Connections
Cable incoming and outgoing from the top or bottom
(Unit: mm)
Hv Top Incoming
Lv Top Outgoing

Surface Hot !


W-50
W
4-Ø19
FIXING HOLES
D-40
D
D+100
Configurations
H
H+18
High voltage !
Cut out power before
approach.
Do NOT touch immediately
after power off.

Cable incoming from the top or bottom and bus bar outgoing from the top
Typical Outgoing From The Top
17
Wave Cast Dry-type Transformers
Typical Incoming and Outgoing Connections
Configurations
Cable incoming from the top or bottom and bus bar outgoing from the side
Typical Outgoing From The Side
Typical cable flanged dimension
(Unit: mm)
HV/LV Entry Flange
a
b
a
6
-M
10
FW
FW+40
18
290
270
250
Cable Entry Flange Dimensions
Wheel Distance
FW
a
b
660
480
170
160
820
580
200
200
1070
680
230
240
Wave Cast Dry-type Transformers
IP54 Enclosure
●● Fans forced ventilate (Rittal)
●● Stainless bolts/screws/washers
●● Stainless locker (Southco)
●● Silicon rubber seal
●● IP4X louvers
Configurations
●● Outdoor paint
19
Wave Cast Dry-type Transformers
Typical Electrical Drawing
L1
Input
PX
N
L1
TEMPERATURE CONTROLLER
N
FT
FU1
FT
8
11
alarm
9
10
COM.
11
12
Sensor.
Configurations
13
trip
~
7
01
6
02
5
03
4
04
K51
K52
K71
K72
3
2
05
COOLING FANS
M1~4
MICRO-POSITION SWITCH
TERMINAL BLOCK:
01-02: NORMAL-OPEN CONTACT FOR ALARM
03-04: NORMAL-OPEN CONTACT FOR TRIP
K51-K52: NORMAL-CLOSE CONTACT WHEN DOOR
OPEN (OPTIONAL)
K71-K72: NORMAL-OPEN CONTACT WHEN DOOR
OPEN (OPTIONAL)
MICRO-POSITION SWITCH
LWX5-1~4
LWX5-5~8
K51
K52
20
01
02
03
04
05
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
DOOR OPEN SIGNAL OUTPUT (OPTIONAL)
TEMPERATURE ALARM AND TRIP SIGNAL OUTPUT
POWER INPUT
Power
K71
K72
Wave Cast Dry-type Transformers
Testing
Tests are performed in accordance with IEC60076-11:2004 or IEEE C57.12.91-2001.
Routine tests
Type tests
Each cast coil transformer undergoes a
A type test is performed in the event of
complete set of routine tests to ensure
a new design or an important design
reliability.
modification in order to confirm that
●● Measurement of winding resistance
the quality of the transformer remains
●● Measurement of voltage ratio and
compliant to related standards. Type tests
phase displacement check
can be carried out according to request.
●● Measurement of insulation resistance
Wave Cast has passed the following tests
●● Measurement of short circuit
●● Temperature-rise test
impedance and load losses
●● Measurement of no-load losses and
current
●● Separate-source AC voltage withstand
voltage test
●● Lightning impulse test
●● Short-circuit test at KEMA Holland on
2.5MVA transformer
●● All routine, type and special tests at
CTQC witnessed by KEMA on 1600kVA
●● Induced AC withstand voltage test
11/0.4kV copper winding transformer,
●● Measurement of partial discharge
and 2000kVA 20/0.4kV aluminumwinding transformer. (KEMA report)
●● All routine, type and special tests at
●● Sound level measurement
●● Short-circuit withstand test
CTQC (China Transformer Quality Center)
on 2MVA distribution transformer
●● All routine, type and special tests at
CTQC on 10MVA power transformer
●● The C2 climatic class, E2 environmental
class, F1 fire behavior class tests at
CTQC
Other Information
Special tests
●● Vibration test withstands the
acceleration ag of the horizontal 0.6g
and vertical 0.3g at Tongji University
21
Wave Cast Dry-type Transformers
Other Information
Packaging
22
Wave Cast Dry-type Transformers
Handling and Transporting
Handling a transformer
Transporting by fork-lift truck
Hoisting hanger
Steel cable
≤60°
Enclosure
Joint hinge
Fork-lift truck
Transformer
Enclosure center & Forks center Enclosure center
Enclosure
Fork-lift truck
Enclosure
1. Four (4) hoisting joint hinges are installed on the upper clamps
Fork-lift truck
(channel-section) of transformer.
2. It is suggested to hoist the body integrally by 4 steel cables.
3. The angle between steel cables should not be more than 60
Fork end (over the enclosure center)
degrees.
Handling a transformer
1. The fork shall be symmetrically placed under the enclosure
base to avoid inclining and overturning.
inclining and overturning.
3. The speed must be slow.
≤60°
Storage
1. Transformers in storage and during non-running periods must
Other Information
2. The fork end shall be over the enclosure center to avoid
be kept dry and away from severe moisture.
2. The relative humidity of the surrounding air must be less than
93%. No drops of water should be present on the surface of
the coils.
3. For further details, refer to the Wave Cast Operating and
Handling transformer with enclosure
Maintenance Manual .
1. The 4 lifting pads are fixed on the base of the enclosure.
2. It is suggested to hoist the enclosure by 4 steel cables and
spreader bar (or similar tools) as shown above.
3. The angle between steel cables should not be more than 60
degrees.
23
Wave Cast Dry-type Transformers
Foundation Installation
(Unit: mm)
Enclosure
Enclosure
Concrete
Concrete
Cable trench
(If applicable)
4-ø22
Fix holes
Channel steel
(inserted in concrete foundation)
Channel steel
(inserted in concrete foundation)
Fix holes
100
100
Fix holes
100
Concrete
Enclosure bottom
24
Fix holes
Transformer support channel steel
100
Other Information
Cable trench
(If applicable)
Fix holes
Wave Cast Dry-type Transformers
Checklist
RFQ Transformer Checklist
Project Name:
RFQ No.:
units
Phase Number*
□ Three phase
Capacity*
Frequency*
□ 50Hz
□ 60Hz
Applicable standard*
□ IEC 60076-11
□ IEEE C57.12.01
Winding material*
□ Copper
□ Aluminum
Rated voltage
(No-load voltage)*
High Voltage
Connection Symbol *
□ Dyn11
□ Dyn5
□ Yyn0
Short circuit impedance*
□ 4%
□ 6%
□ Others:
Insulation class*
□F
□H
□ Others:
Temperature rise
□ IEC standards
□ IEEE standards □ Others:
kV
□ Off-circuit tap changing
Tap Changing method
□ On-load tap changing
Low Voltage
kV
□ Others:
Tapping range:
□ ±2×2.5%
□ ±5%
□ Others:
Tapping range:
□ ±4×2.5%
□ ±3×2.5%
□ Others:
□ front
□ side
On-load tap changer location
Temperature control device
□ No.
Cooling*
□ Air natural (AN)
□ Air forced (AF)
Controller/fans voltage
□ 220V AC (1 phase 50Hz)
□ 110V AC (1 phase 60Hz)
Service condition
KVA
□ Yes, BWD-3K130 □ with RS485 interface
□ with 4-20mA output
□ Others:
Altitude*
□ not more than 1000 meter
□ Others
meter
Max.. temp.*
□ 40℃
□ Others
℃
Min. temp
□ -5℃ (Indoors)
□ -30℃ (Outdoors)
Indoor/outdoor*
□ Indoor
□ Outdoor
Environmental*
□ Normal
□ Corrosive area (coast, offshore etc.)
Enclosure protection class*
□ IP00
□ IP20
□ IP21
Enclosure material*
□ Steel sheet
□ A1 alloy sheet
□ Stainless steel sheet
□ RAL 7032
□ RAL 7035
Enclosure color
Incoming type (HV)*
Outgoing type (LV)*
□ Cable incoming
□ Top input
Shippment (TR & enclosure)
□ Shipping together
Rollers (temporary move)
□ Yes.
□ Others:
□ Customer templet
□ Others:
□ Busbar incoming
□ Bottom input
□ Cable outgoing
□ Top output
□ ANSI 61
□ IP23
□ Side input
□ Others:
□ Busbar outgoing
□ Bottom output □ Side output
Other Information
Quantity*
□ Others:
□ Shipping separately
□ No.
Other special requirements
Note: Required fields are indicated by * .
If the transformer cubicle is connected to the HV and LV breaker, the interface drawings for HV&LV and Plan Arrangement should be provided, including
the contents described as follows:
1. The shape and dimension of HV/LV cubicle(enclosure dimension)
2. Size, quantity, location, and phase sequence of Busbar or cable
3. The dimension, quantity and location of the connection holes which connect to transformer cubicle
4. The arrangement mode and alignment mode of HV/LV cubicles with transformer cubicles
Standard package is vacuum bag wrap inside wooden box and equipped with shock watch to monitor transportation impact.
If change the shippment mode after manufacturing, all the addition cost caused by those change are borne by the customers.
25
Greater China
Shanghai
4F, Building 2, CTP, No.1 Hua Tuo Rd. Zhang Jiang Hi-Tech
Park, Shanghai, China 201203
T : +86 21 3877 7888
F : +86 21 3877 7600
Taiwan
6F, No. 8, Min Sheng E. Rd., Sec. 3, Taipei 10480
T : +886 2 2183 7000
F : +886 2 2516 6829
South East Asia
Malaysia
Level 6, 1 Sentral, Jalan Travers, Kuala Lumpur Sentral
Kuala Lumpur, Malaysia 50470
T : +603 2273 9788
F : +603 2273 7988
Philippines
8F Net Cube Building, 30th Street, Corner 3rd Avenue,
Crescent West Park, Global City Taguig 1634
T : +63 2 877 7000
F : +63 2 846 0629
Indonesia
BRI II Tower, 27th floor, Jl. Jend. Sudirman No. 44-46
Jakarta 10210
T: +62 21 573 0430
F: +62 21 574 7089
Thailand
25th floor, CRC Tower, All Seasons Place, 87/2 Wireless
Road, Lumpini, Pathumwan, Bangkok 10330
T : +66 2 648 0240
F : +66 2 648 0200
Vietnam
Floors 6 & 7 - The Crescent CR3
111 Ton Dat Tien Street, Tan Phu Ward, District 7
Ho Chi Minh City
T : + 84 8 54137000
F : + 84 8 54137040 / 54137050
Singapore
240 Tanjong Pagar Road, #06-00 GE Tower
Singapore 088540
T : +65 6326 3718
F : +65 6326 3015
India
India
Plot No. 42/1 & 45/14, Electronic City-Phase II
Bangalore-560100
T: (080) 41434000
F: (080) 41434199
Australia & New Zealand
125-127 Long Street, Smithfield, Sydney, NSW 2164
T : +61 2 8788 6911
F : +61 2 8788 7224
North Asia
Japan
11F, Akasaka Park Bldg.,5-2-20, Akasaka, Minato-ku
Tokyo 107-6111
T : +81 3 3588 5288
F : +81 3 3585 3010
Korea
22, Daewangpangyo-ro 712 beon-gil, Bundang-gu,
Seongnam-si, Gyeonggi-do, 463-400, Korea
T: +82-31-620-6000
F: +82-31-620-7070
Europe & Middle East
Spain
Avenida Camara de la Industria 9
28938 Móstoles - Madrid
T: +34 685 37 91
Belgium
Nieuwevaart 51, B-9000 Gent
T: +32 (0)9 265 21 11
Finland
Kuortaneenkatu 2, FI-00510 Helsinki
T: +358 (0)10 394 3760
France
Paris Nord 2, 13, rue de la Perdrix
F-95958 Roissy CDG Cédex
T: +33 (0)800 912 816
Poland
Ul. Odrowaza 15, 03-310 Warszawa
T: +48 22 519 76 00
and
Ul. Leszczyńska 6, Bielsko-Biała 43-300
T: +48 33 828 62 33
Italy
Centro Direzionale Colleoni
Via Paracelso 16, Palazzo Andromeda B1
I-20864 Agrate Brianza (MB)
T: +39 039 637 3701
Netherlands
Parallelweg 10, Nl-7482 CA Haaksbergen
T: +31 (0)53 573 03 03
Germany
Robert-Bosch Str. 2a, 50354 Hürth-Efferen
T: +49 (0) 2233/ 9719-0
Portugal
Rua Camilo Castelo Branco, 805, Apartado 2770
4401-601 Vila Nova de Gaia
T: +351 22 374 60 00
United Arab Emirates
Injaz Building, 3rd Floor
Dubai Internet City, PO Box 11549, Dubai
T: +971 4 4546912
Latin America
Latin America Headquarters
790 N.W. 107th Avenue, Suite 200, Miami, Fl 33172 USA
T: +1 305 551 5155
Chile
Vespucio Norte, Avenida Presidente Eduardo Frei
Montalva 6001, Edificio N° 66
Comuna: Conchalí, Sector el Cortijo, Santiago
T: (56 2) 928-4700
Brazil
Av. María Coelho Aguiar, 215, Bloco C - 6.Andar
Jd.São Luiz, 05804-900, São Paulo
T: +55 11 36141900
Mexico
Av. Churubusco 3900 Nte, Col. Industrial Benito Juárez
Monterrey, N.L. 64517
T: (01-800) 800-1968
North America
USA
41 Woodford Avenue, Plainville CT, USA 06062
and 12305 Kurland Drive, Houston, TX USA 77034
T: +1 800-431-7867
2000 Centre Green Way Suite 200 Cary, NC 27513
T: +1 919-238-6620
Canada
2300 Meadowvale Blvd. Mississauga, ON L5N 5P9
T: 1-800-GE1-STOP
Hungary
Vaci ut 81-83. H-1139 Budapest
T: +36 1 447 6050
Russia
27/8, Electrozavodskaya street, Moscow, 107023
T: +7 495 937 11 11
South Africa
Unit 4, 130 Gazelle Avenue, Corporate Park Midrand 1685
P.O. Box 76672 Wendywood 2144
T: +27 11 238 3000
United Kingdom
2 The Arena, Downshire Way
Bracknell, Berkshire RG12 1PU
T: +44 (0) 800 587 1239
Turkey
Windowist Tower Eski Büyükdere Cad. No: 26 Kat: 5
Maslak 34467, Sarıyer, İstanbul
T: +90 212 214 76 91
F: +90 212 214 77 30
GE
Industrial Solutions
You may be interested in other MV Seco-family products
For more information, please visit www.geindustrial.com
For more information, please visit
www.geindustrial.com
Printing Code: IN201406D05EN
© Copyright GE Industrial Solutions 2014