Mod Con™ VWH Hot Water Supply Boiler

Transcription

Mod Con™ VWH Hot Water Supply Boiler
Mod Con ™ VWH
Hot Water Supply Boiler
Advanced Heating
& Hot Water Systems
An Intelligent Design that Delivers
Highly Efficient Water Heating with
up to 98% Thermal Efficiency
Construction Features
Heat Exchanger
Integrated
Control System
*Note: Thermal
efficiency tested with
low temperature
return
• Built-in sequencer for up
to 8 boilers
• Digital display with LED
status indicators
• Integrated Control allows only the
amount of heated energy required
• 24 volt monitor for system safeties
• Dual flame sensing (Flame probe /
Spark Ignition Probe)
Heat Exchanger
Bears the ASME
“H” Stamp
TP Ma
SCAQMD Rule 1146.2
Additional Features
Optional Equipment
• Superior Condensate collection
system (Patent Pending) Easy to
service with overflow protection
• PVC – CPVC – Stainless
Steel Venting
• Vents up to 200 feet combined
• Stack units for increased output
in small footprint
• Adjustable Legs
• Direct Vent Sealed Combustion
• Models Available for Natural
or LP Gas
• Easy access for wiring or field
service of combustion heat
exchanger
• High limit manual reset /Low water
cut-off (standard equipment)
• Removable front cover allows easy
access to burner assembly
• High and Low Gas
Pressure Switch
• Alarm
• Venting Kit
• Caster Wheel Kit
• Zero clea rance to all
c ombus t ib le sur f aces
• Factory installed AGA/ASME
rated relief valve.
• PC monitoring for history
– system operation (optional)
• Self diagnostic electronic control
with digital readout to monitor
system parameters.
• 5-year limited warranty
d
n Amer i c
n Amer i c
•H
eI
a
eI
• All Stainless Steel Construction
• No Gaskets, Welded Construction.
ASME Approved
• 150 PSI Relief Rated
• Easy to Service
P
• HT Mad
• Modulating Burner with
up to a 5 to 1 turndown
• Gas Valve (Tested to UL,
FM, CSA Standards)
• Up to 98% Thermal Efficiency*
• High Grade NIT Burner
• Low Nox Operation
• Gas Conversion available
• Whisper Quiet Operation
• Reliable Spark Ignition
a
Combustion System
• PC Software for
History and System
monitoring
• Condensate
Neutralizer Kit
Stainless Steel
Heat Exchanger
Pressure
Relief
Valve
Inlet Nipple
Low Water
Sensor
Outlet Nipple
Drain Valve
Gas
Valve
Temperature &
Pressure Gauge
Eco High Limit
Condensate
Collection
System
Gas Line
Combustion
Blower
Adjustable
Leveling Feet
Dimensional Information
FRONT
(ALL MODELS)
POWER
SWITCH
DISPLAY PANEL
HOT WATER
OUTLET
RIGHT SIDE
(ALL MODELS)
ACCESS PANEL
(CONTROL BOARD)
ACCESS PANEL
(ELECTRICAL)
COLD WATER
INLET
J
A
G
B
C
D
E
H
CONDENSATE
DISCHARGE
GAS LINE
F
LEFT SIDE
(ALL MODELS)
REAR
(ALL MODELS)
EXHAUST
O
AIR INTAKE
N
K
P
L
M
MODE
A
B
C
D
E
F
G
H
J
K
L
M
N
MOD CON 500 VWH
20"
14-3/4"
6-1/4"
13-1/4"
14 -1/2"
33-1/4"
5-1/8"
20-1/2"
36"
43-3/4"
46"
48"
8-1/4"
25-1/2" 10-1/2"
20"
20"
6-1/4"
16-1/4"
18-3/4"
43-1/2"
20"
20-1/2"
36"
62-1/4" 68-1/2 "
73"
8-1/4"
25-1/2" 10-1/2"
MOD CON 700 VWH
MOD CON 850 VWH
O
P
NOTE: ALL DIMENSIONS ARE APPROXIMATE AND HEIGHTS DO NOT INCLUDE ADJUSTABLE LEGS.
Gross
Output
Btuh
470,000
Net I=B=R
Btuh
Thermal
Effieciency
Boiler
Water
Supply/Return
Connection
Gas
Conn.
Vent
Dia.
MOD CON 500 VWH
Btuh
Input
Range
100,000 - 500,000
409,000
98%
4.2 Gal.
2”
1- 1/2”
4”
MOD CON 700 VWH
170,000 - 700,000
686,000
572,600
97%
5.8 Gal.
2”
2”
6”
MOD CON 850 VWH
170,000 - 850,000
799,000
695,000
97%
5.8 Gal.
2”
2”
6”
MODEL
Low
Fan
Speed
1950
Fan Speed
at Ignition
505 lbs.
High
Fan
Speed
7200
580 lbs.
5700
2200
3000
580 lbs.
6800
2200
3000
Ship.
Wt.
3000
Preferred Piping (Zoning with Valves) Space Heating Mode
Volume Water Heating using MOD CON boiler
Volume Water Heating using MOD CON boiler
Drawing VWH 1/1 MC
Drawing VWH 2/1V MC
vacuum breaker
(where required by code)
vacuum breaker
(where required by code)
constant
circulation
Drawing VWH 2/2 V MC
ASEE 1017 rated anti-scald valve
(recommended)
cold water
(2 boilers supplying 2 storage tanks)
recirculation line
Volume Water Heating using MOD CON boiler
cold water
required
system/
pipe
sensor
expansion
tank
follower
address = 1
MOD CON 2
flow switch
condensate
drainage
System/pipe sensor
(used if aquastat cannot
be placed on tank)
vacuum breaker
(where required by code)
mechanical aquastat
(both tanks)
wired in series
(preferred)
MOD CON 1
constant
circulation
pipe sensor
(used if sensor cannot
be placed on tank)
condensate
drainage
hot water supply
Superstor Ultra
coil booster tank
master
address = 0
flow switch
Superstor Ultra
coil booster tank
flow switch
expansion
tank
constant
circulation
Indirect/
tank
sensor
preferred
location
System/Pipe Sensor
(used if not located at tank)
Indirect/
tank
sensor
preferred
recirculation line
ASEE 1017 rated anti-scald valve
(recommended)
hot water supply
(2 boilers supplying 1 storage tank)
cold water
recirculation line
ASEE 1017 rated anti-scald valve
(recommended)
hot water supply
(1 boiler supplying 1 storage tank)
master
address = 0
MOD CON 1
flow switch
constant
circulation
follower
address = 1
expansion
tank
Superstor Ultra
coil booster tank
Superstor Ultra
coil booster tank
mechanical aquastat
(both tanks)
wired in series
(preferred)
ASEE 1017 rated anti-scald valve
(recommended)
vacuum breaker
(where required by code)
cold water
Drawing VWH 3/2 V MC
recirculation line
(3 boilers supplying 2 storage tanks)
hot water supply
Volume Water Heating using MOD CON boiler
MOD CON 2
flow switch
required
system/
pipe
sensor
condensate
drainage
constant
circulation
master
address = 0
MOD CON 1
flow switch
constant
circulation
follower
address = 1
MOD CON 2
flow switch
constant
circulation
follower
address = 2
flow switch
required system/pipe sensor
Superstor Ultra
coil booster tank
Superstor Ultra
coil booster tank
system/pipe sensor
(used if aquastat cannot
be placed on tank)
condensate
drainage
MOD CON 3
Efficiency
Condensing Technology, with up to 98% Efficiency, means lower energy cost to you!
MOD CON VWH 500 Fuel Savings
at 1 Year  75%  80%  85%
Mod Con 850 Efficiency Curve
98
96
94
92
90
88
86
84
40
60
100
140
160
Return Water Temperature (°F )
HTP @ 20%
HTP @ 60%
MOD CON VWH 500 Fuel Savings
at 3 Years  75%  80%  85%
HTP @ 100%
Mod Con 500 Efficiency Curve
99
97
95
93
91
89
87
40
60
100
140
160
(based on running hours, calculated using FTC-published average energy costs, Jan.
2009; $1.21 per therm) The cost of fuel in some areas of the country has increased by
almost 40% in just one year. The highly efficient modulating output of the Mod Con
VWH will provide a maximum payback on fuel savings. As the charts below illustrate,
savings can result in a payback period in less than three years when compared to the
conventional technology of other Hot Water Supply Boilers. The Mod Con VWH could
save you as much as 50% on your present fuel bills.
Return Water Temperature (°F )
HTP @ 20%
HTP @ 60%
HTP @ 100%
MOD CON VWH Recovery Ratings with Storage Tanks
The chart below provides you with the first hour ratings as compared to commercial direct fired storage water heaters.
This chart will help you determine the exact size of the storage tank required for the new or retro-fit application.
ModCon 500 VWH
Delta T
Gallons
Per Hour
First
Hour
Rating
With
119
Gallon
40°F
50°F
60°F
70°F
80°F
90°F
100°F
110°F
120°F
130°F
140°F
1414
1131
943
808
707
628
566
514
471
435
404
859
872
884
897
910
923
935
948
961
974
986
© 2016 HTP Inc.
www.htproducts.com
Minimum Storage Tank Sizes For The Mod Con VWH Models
Mod Con
500
Mod Con
850
Mod Con
1000
Mod Con
1700
119 Gal.
175 Gal.
200 Gal.
350 Gal.
ModCon 850 VWH
First
Hour
Rating
With
175
Gallon
First
Hour
Rating
With
200
Gallon
Delta T
883
902
920
939
958
977
995
1014
1033
1052
1070
894
915
937
958
979
1001
1022
1044
1065
1087
1108
40°F
50°F
60°F
70°F
80°F
90°F
100°F
110°F
120°F
130°F
140°F
Gallons
Per Hour
First
Hour
Rating
With
119
Gallon
First
Hour
Rating
With
175
Gallon
First
Hour
Rating
With
200
Gallon
2404
1923
1602
1374
1202
1068
961
874
801
740
687
1449
1467
1486
1505
1524
1542
1561
1580
1599
1617
1636
1459
1481
1502
1524
1545
1566
1588
1609
1631
1652
1674
1502
1534
1566
1599
1631
1663
1695
1727
1759
1791
1824
A LO O K
INS IDE
LP-277 Rev. 8/2016

Similar documents

Double Stack

Double Stack • High and Low Gas Pressure Switch Kit with Manual Reset (Part # 7350P-600) • U.L. 353 Compliant Low Water Cut-Off Interface Kit with Manual Reset (Part # 7350P-601) • Alarm System (Part # 7350P...

More information

Double Stack

Double Stack An Intelligent Design that Delivers Highly Efficient Hydronic Heating with 94.1% Thermal Efficiency

More information