Fire-Rated Glazing Systems Product Guide
Transcription
Fire-Rated Glazing Systems Product Guide
Vetrotech Product Solutions OPENING FIRE PROTECTION ASSEMBLIES, RATINGS AND MARKINGS | IBC 2012 TABLE 716.5 Required Minimum Wall Fire Door & Assembly Fire Shutter Rating Assembly (hours) Rating (hours) Other fire barriers Fire partitions: Corridor walls 1 1 0.5 0.5 3 ⁄3b 1 ⁄3b 1 ¾ Exterior walls 2 ⁄3 1 1 ½ 1½ Smoke barriers 1 Fire Resistance Fire Protection Fire Resistance Fire Protection ≤ 25% of common wall KERALITE R, F or L 45 CONTRAFLAM 45 VDS HM 45 / VDS LITE 45 D-H-OH-45 KERALITE R, F or L 45 CONTRAFLAM 45 VDS HM 45 / VDS LITE 45 D-H-OH-45 KERALITE R, F or L 20 VDS HM 20 / VDS LITE 20 D-H-OH-20 KERALITE F or L 45 CONTRAFLAM 45 VDS HM 45 Doors VDS LITE 45 Doors D-H-45 KERALITE R, F or L 45 CONTRAFLAM 45 VDS HM 45 / VDS LITE 45 D-H-OH-45 PYROSWISS 20 VDS HM 20 Doors VDS LITE 20 Doors D-20 KERALITE R, F or L 20 VDS HM 20 / VDS LITE 20 D-H-OH-20 KERALITE F or L 90 VDS HM 90 Doors (TR) KERALITE-Ultra 90 CONTRAFLAM 90 VDS 90 Doors ¾ ⁄3b PYROSWISS 20 VDS HM 20 Doors VDS LITE 20 Doors Vetrotech, Pyroswiss®, Contraflam®, and VDS®: all devices and logos are registered trademarks of Vetrotech Saint-Gobain International AG. Keralite® is a registered trademark of Keraglass. August 2013. The information contained in this publication is correct at the time of going to print. Such information may be subject to change and products may be modified, supplemented or withdrawn by Vetrotech Saint-Gobain without prior notice. Vetrotech Saint-Gobain North America, Inc Auburn, WA, USA, www.vetrotechUSA.com Fire Protection Fire-Rated Glazing Marking Sidelight/Transom Panel D-20 KERALITE F or L 90 VDS HM 90 Doors (TR) KERALITE-Ultra 90 CONTRAFLAM 90 VDS 90 Doors 1 D-H-45 Minimum Sidelight /Transom Assembly Rating (hours) PYROSWISS 20 VDS HM 20 Doors VDS LITE 20 Doors KERALITE F or L 45 CONTRAFLAM 45 VDS HM 45 Doors VDS LITE 45 Doors 1 Fire-Rated Glazing Marking Door Vision Panele KERALITE F or L 45 CONTRAFLAM 45 VDS HM 45 Doors VDS LITE 45 Doors ¾ 1 Other fire partitions Door Vision Panel Size ≤100 sq.in.:c D-H-90 D-H-T-90 >100 sq.in.: D-H-W-90 D-H-T-90 ≤100 sq.in.:c D-H-90 D-H-T-90 >100 sq.in.: D-H-W-90 D-H-T-90 D-H-45 Not Permitted CONTRAFLAM 180 VDS 180 Not Permitted W-180 Not Permitted CONTRAFLAM 120 VDS 120 VDS 120 CW Not Permitted W-120 Fire Protection KERALITE R, F or L 45 CONTRAFLAM 45 VDS HM 45 / VDS LITE 45 D-H-OH-45 Fire Protection D-20 KERALITE R, F or L 45 CONTRAFLAM 45 VDS HM 45 / VDS LITE 45 Vetrotech Saint-Gobain USA 2108 B Street NW, #110 Auburn, WA 98001 253-333-0660 Toll-free: 888-803-9533 Fax: 253-333-5166 www.vetrotechusa.com D-H-OH-45 Fire Resistant Glass Solutions Fire-Rated Glazing Systems Product Guide Type of Assembly Vetrotech Product Solutions OPENING FIRE PROTECTION ASSEMBLIES, RATINGS AND MARKINGS | IBC 2012 TABLE 716.5 Required Minimum Wall Fire Door & Assembly Fire Shutter Rating Assembly (hours) Rating (hours) Other fire barriers Fire partitions: Corridor walls 1 1 0.5 0.5 3 ⁄3b 1 ⁄3b 1 ¾ Exterior walls 2 ⁄3 1 1 ½ 1½ Smoke barriers 1 Fire Resistance Fire Protection Fire Resistance Fire Protection ≤ 25% of common wall KERALITE R, F or L 45 CONTRAFLAM 45 VDS HM 45 / VDS LITE 45 D-H-OH-45 KERALITE R, F or L 45 CONTRAFLAM 45 VDS HM 45 / VDS LITE 45 D-H-OH-45 KERALITE R, F or L 20 VDS HM 20 / VDS LITE 20 D-H-OH-20 KERALITE F or L 45 CONTRAFLAM 45 VDS HM 45 Doors VDS LITE 45 Doors D-H-45 KERALITE R, F or L 45 CONTRAFLAM 45 VDS HM 45 / VDS LITE 45 D-H-OH-45 PYROSWISS 20 VDS HM 20 Doors VDS LITE 20 Doors D-20 KERALITE R, F or L 20 VDS HM 20 / VDS LITE 20 D-H-OH-20 KERALITE F or L 90 VDS HM 90 Doors (TR) KERALITE-Ultra 90 CONTRAFLAM 90 VDS 90 Doors ¾ ⁄3b PYROSWISS 20 VDS HM 20 Doors VDS LITE 20 Doors Vetrotech, Pyroswiss®, Contraflam®, and VDS®: all devices and logos are registered trademarks of Vetrotech Saint-Gobain International AG. Keralite® is a registered trademark of Keraglass. August 2013. The information contained in this publication is correct at the time of going to print. Such information may be subject to change and products may be modified, supplemented or withdrawn by Vetrotech Saint-Gobain without prior notice. Vetrotech Saint-Gobain North America, Inc Auburn, WA, USA, www.vetrotechUSA.com Fire Protection Fire-Rated Glazing Marking Sidelight/Transom Panel D-20 KERALITE F or L 90 VDS HM 90 Doors (TR) KERALITE-Ultra 90 CONTRAFLAM 90 VDS 90 Doors 1 D-H-45 Minimum Sidelight /Transom Assembly Rating (hours) PYROSWISS 20 VDS HM 20 Doors VDS LITE 20 Doors KERALITE F or L 45 CONTRAFLAM 45 VDS HM 45 Doors VDS LITE 45 Doors 1 Fire-Rated Glazing Marking Door Vision Panele KERALITE F or L 45 CONTRAFLAM 45 VDS HM 45 Doors VDS LITE 45 Doors ¾ 1 Other fire partitions Door Vision Panel Size ≤100 sq.in.:c D-H-90 D-H-T-90 >100 sq.in.: D-H-W-90 D-H-T-90 ≤100 sq.in.:c D-H-90 D-H-T-90 >100 sq.in.: D-H-W-90 D-H-T-90 D-H-45 Not Permitted CONTRAFLAM 180 VDS 180 Not Permitted W-180 Not Permitted CONTRAFLAM 120 VDS 120 VDS 120 CW Not Permitted W-120 Fire Protection KERALITE R, F or L 45 CONTRAFLAM 45 VDS HM 45 / VDS LITE 45 D-H-OH-45 Fire Protection D-20 KERALITE R, F or L 45 CONTRAFLAM 45 VDS HM 45 / VDS LITE 45 Vetrotech Saint-Gobain USA 2108 B Street NW, #110 Auburn, WA 98001 253-333-0660 Toll-free: 888-803-9533 Fax: 253-333-5166 www.vetrotechusa.com D-H-OH-45 Fire Resistant Glass Solutions Fire-Rated Glazing Systems Product Guide Type of Assembly Vetrotech Product Solutions OPENING FIRE PROTECTION ASSEMBLIES, RATINGS AND MARKINGS | IBC 2012 TABLE 716.5 (cont.) Fire-Resistant Glass Solutions Type of Assembly More than 30 Years of Experience Vetrotech Saint-Gobain is the world’s leading producer of fire-resistant glass products. With innovative research and development as well as state-of-the-art production technologies, Vetrotech creates solutions of the highest quality, consistency and complexity. Our products comply with the strictest impact safety requirements. Our solutions are created for multi-functional applications and meet the aesthetic demands of modern architecture. Fire walls and fire barriers having a required fire-resistance rating greater than 1 hour Required Minimum Wall Fire Door & Assembly Fire Shutter Rating Assembly (hours) Rating (hours) For more information, quotes or factory tours, contact us at: (888) 803-9533 Looking for a fire-resistant solution? The on-line product selector is an automated way to find your perfect solution. Scan this code to use the on-line product selector. Or go to: www.vetrotechusa.com Fire barriers having a required fire-resistance rating of 1 hour: Enclosures for shafts, exit access stairways, exit access ramps, interior exit stairways, interior exit ramps and exit passageway walls Minimum Sidelight /Transom Assembly Rating (hours) Fire-Rated Glazing Marking Sidelight/Transom Panel Tempered Glass—PYROSWISS® 4 3 Not Permitted Not Permitted Not Permitted 4 Not Permitted W-240 3 3a Not Permitted Not Permitted Not Permitted CONTRAFLAM 180 VDS 180 Not Permitted W-180 Glass Ceramic—KERALITE® KERALITE F or L 90 VDS HM 90 Doors (TR) ≤100 sq.in.:c D-H-90 KERALITE-Ultra 90 CONTRAFLAM 90 VDS 90 Doors >100 sq.in.: D-H-W-90 D-H-T-90 Not Permitted CONTRAFLAM 120 VDS 120 VDS 120 CW Not Permitted W-120 Interlayer Glass—CONTRAFLAM® KERALITE F or L 90 VDS HM 90 Doors (TR) ≤100 sq.in.:c D-H-90 KERALITE-Ultra 90 CONTRAFLAM 90 VDS 90 Doors >100 sq.in.: D-H-W-90 D-H-T-90 Not Permitted CONTRAFLAM 90 VDS 90/120 VDS 90/120 CW Not Permitted W-90 sprinklered: KERALITE F or L 90 VDS LITE 90 Doors VDS HM 90 Doors ≤100 sq.in.:c,d D-H-90 non-sprinklered: KERALITE F or L 90 ≤100 sq.in.:c,d D-H-90 KERALITE-Ultra CONTRAFLAM 90 VDS 90 Doors >100 sq.in.:c,d D-H-T-90 or D-H-T-W-90 sprinklered: KERALITE F or L 60 VDS LITE 60 Doors VDS HM 60 Doors ≤100 sq.in.:c,d D-H-60 non-sprinklered: KERALITE F or L 60 ≤100 sq.in.:c,d D-H-60 KERALITE-Ultra CONTRAFLAM 60 VDS 60 Doors >100 sq.in.:c,d D-H-T-60 or D-H-T-W-60 2 1 ½ Shaft, exit enclosures and exit passageway walls Fire-Rated Glazing Marking Door Vision Panele A tempered glass product made of thermally tempered safety glass to withstand fire exposure without the transmission of fire to the non-fire side. Pyroswiss glass products also prevent the passage of smoke, flames, or hot gases. 1½ Global Resources, Local Support Vetrotech fire-resistant glass is manufactured and fabricated under license by authorized SaintGobain facilities located throughout Europe, Asia and North America. Door Vision Panel Size Fire-Rated Products 2 1 1 ½ 1 ½ 1 c c Fire Protection Fire Resistance Fire Protection Fire Resistance Clear, fire-rated safety glass-ceramics with improved human impact safety. Interlayer glass products are made of laminated or tempered safety glass and filled with a transparent, intumescent interlayer. Contraflam products activate when exposed to fire, preventing the passage of smoke, flames and gas while reducing the transmission of radiated and conducted heat for up to 180 minutes. Steel Framing—VDS® Not Permitted CONTRAFLAM 120 VDS 120 VDS 120 CW Not Permitted W-120 Our VDS framing systems are special thermally broken steel profile systems used in conjunction with fire and safety-rated glazing products. VDS framing provides a barrier to radiant and conducted heat transfer. Photo on the cover - Fire Testing An actual fire test is shown on the cover. All fire-rated building materials must be tested and listed with an independent testing agency. Vetrotech Saint-Gobain products are frequently tested and listed at Underwriters Laboratories (UL). Not Permitted CONTRAFLAM 60 VDS 60 VDS 60 CW Not Permitted W-60 a. Two doors, each with a fire protection rating of 1 1/2 hours, installed on opposite sides of the same opening in a fire wall, shall be deemed equivalent in fire protection rating to one 3-hour fire door. b. For testing requirements, see Section 716.6.3. c. Fire-resistance-rated glazing tested to ASTM E 119 in accordance with Section 716.2 shall be permitted, in the maximum size tested. d. Except where the building is equipped throughout with an automatic sprinkler and the fire-rated glazing meets the criteria established in Section 716.5.5. e. Under the column heading “Fire-rated glazing marking door vision panel, “ W refers to the fire-resistance rating of the glazing, not the frame. Vetrotech Product Solutions OPENING FIRE PROTECTION ASSEMBLIES, RATINGS AND MARKINGS | IBC 2012 TABLE 716.5 (cont.) Fire-Resistant Glass Solutions Type of Assembly More than 30 Years of Experience Vetrotech Saint-Gobain is the world’s leading producer of fire-resistant glass products. With innovative research and development as well as state-of-the-art production technologies, Vetrotech creates solutions of the highest quality, consistency and complexity. Our products comply with the strictest impact safety requirements. Our solutions are created for multi-functional applications and meet the aesthetic demands of modern architecture. Fire walls and fire barriers having a required fire-resistance rating greater than 1 hour Required Minimum Wall Fire Door & Assembly Fire Shutter Rating Assembly (hours) Rating (hours) For more information, quotes or factory tours, contact us at: (888) 803-9533 Looking for a fire-resistant solution? The on-line product selector is an automated way to find your perfect solution. Scan this code to use the on-line product selector. Or go to: www.vetrotechusa.com Fire barriers having a required fire-resistance rating of 1 hour: Enclosures for shafts, exit access stairways, exit access ramps, interior exit stairways, interior exit ramps and exit passageway walls Minimum Sidelight /Transom Assembly Rating (hours) Fire-Rated Glazing Marking Sidelight/Transom Panel Tempered Glass—PYROSWISS® 4 3 Not Permitted Not Permitted Not Permitted 4 Not Permitted W-240 3 3a Not Permitted Not Permitted Not Permitted CONTRAFLAM 180 VDS 180 Not Permitted W-180 Glass Ceramic—KERALITE® KERALITE F or L 90 VDS HM 90 Doors (TR) ≤100 sq.in.:c D-H-90 KERALITE-Ultra 90 CONTRAFLAM 90 VDS 90 Doors >100 sq.in.: D-H-W-90 D-H-T-90 Not Permitted CONTRAFLAM 120 VDS 120 VDS 120 CW Not Permitted W-120 Interlayer Glass—CONTRAFLAM® KERALITE F or L 90 VDS HM 90 Doors (TR) ≤100 sq.in.:c D-H-90 KERALITE-Ultra 90 CONTRAFLAM 90 VDS 90 Doors >100 sq.in.: D-H-W-90 D-H-T-90 Not Permitted CONTRAFLAM 90 VDS 90/120 VDS 90/120 CW Not Permitted W-90 sprinklered: KERALITE F or L 90 VDS LITE 90 Doors VDS HM 90 Doors ≤100 sq.in.:c,d D-H-90 non-sprinklered: KERALITE F or L 90 ≤100 sq.in.:c,d D-H-90 KERALITE-Ultra CONTRAFLAM 90 VDS 90 Doors >100 sq.in.:c,d D-H-T-90 or D-H-T-W-90 sprinklered: KERALITE F or L 60 VDS LITE 60 Doors VDS HM 60 Doors ≤100 sq.in.:c,d D-H-60 non-sprinklered: KERALITE F or L 60 ≤100 sq.in.:c,d D-H-60 KERALITE-Ultra CONTRAFLAM 60 VDS 60 Doors >100 sq.in.:c,d D-H-T-60 or D-H-T-W-60 2 1 ½ Shaft, exit enclosures and exit passageway walls Fire-Rated Glazing Marking Door Vision Panele A tempered glass product made of thermally tempered safety glass to withstand fire exposure without the transmission of fire to the non-fire side. Pyroswiss glass products also prevent the passage of smoke, flames, or hot gases. 1½ Global Resources, Local Support Vetrotech fire-resistant glass is manufactured and fabricated under license by authorized SaintGobain facilities located throughout Europe, Asia and North America. Door Vision Panel Size Fire-Rated Products 2 1 1 ½ 1 ½ 1 c c Fire Protection Fire Resistance Fire Protection Fire Resistance Clear, fire-rated safety glass-ceramics with improved human impact safety. Interlayer glass products are made of laminated or tempered safety glass and filled with a transparent, intumescent interlayer. Contraflam products activate when exposed to fire, preventing the passage of smoke, flames and gas while reducing the transmission of radiated and conducted heat for up to 180 minutes. Steel Framing—VDS® Not Permitted CONTRAFLAM 120 VDS 120 VDS 120 CW Not Permitted W-120 Our VDS framing systems are special thermally broken steel profile systems used in conjunction with fire and safety-rated glazing products. VDS framing provides a barrier to radiant and conducted heat transfer. Photo on the cover - Fire Testing An actual fire test is shown on the cover. All fire-rated building materials must be tested and listed with an independent testing agency. Vetrotech Saint-Gobain products are frequently tested and listed at Underwriters Laboratories (UL). Not Permitted CONTRAFLAM 60 VDS 60 VDS 60 CW Not Permitted W-60 a. Two doors, each with a fire protection rating of 1 1/2 hours, installed on opposite sides of the same opening in a fire wall, shall be deemed equivalent in fire protection rating to one 3-hour fire door. b. For testing requirements, see Section 716.6.3. c. Fire-resistance-rated glazing tested to ASTM E 119 in accordance with Section 716.2 shall be permitted, in the maximum size tested. d. Except where the building is equipped throughout with an automatic sprinkler and the fire-rated glazing meets the criteria established in Section 716.5.5. e. Under the column heading “Fire-rated glazing marking door vision panel, “ W refers to the fire-resistance rating of the glazing, not the frame.