LA400 - Oregon City Garage Door

Transcription

LA400 - Oregon City Garage Door
INSTALLATION/OPERATION MANUAL
MODEL LA400
MEDIUM DUTY SWING GATE OPERATOR
Radio Receiver
Built on Board
315MHz
2 YEAR WARRANTY
Serial # Primary Arm
Serial # Secondary Arm
Serial # Control Box
Installation Date
TABLE OF CONTENTS
Introduction
2-5
Loop Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Photo/Edge Inputs (P6-7-8 and 9) . . . . . . . . . . . . . . . . . . . . . . .32
Safety Accessories for Secondary Entrapment Protection . . . . .33
Carton Inventory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Additional Items Needed for Installation . . . . . . . . . . . . . . . . . . .3
Operator Dimensions and Specifications . . . . . . . . . . . . . . . . . . .3
UL325 Classifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Safety Installation Information . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Overview of Typical Installation
Operation
Reset Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Remote Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Manual Release . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
6-10
Maintenance
Left-Hand Gate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Right-Hand Gate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Dual Gate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Safety Precautions for Swing and
Ornamental “Grill Type Gates” . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Warning Sign Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Before Installation Check Your Gate . . . . . . . . . . . . . . . . . . . . . . .9
Mounting Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Installation
Basic Control Board Layout
Wiring Diagram
Troubleshooting
Repair Parts
LA400 Swing Gate Accessories
Warranty Policy and Service
11-18
WARNING
Mechanical
CAUTION
WARNING
WARNING
Electrical
CAUTION
WARNING
CAUTION
When you see these Safety Symbols and Signal Words on the
following pages, they will alert you to the possibility of serious
injury or death if you do not comply with the warnings that
accompany them. The hazard may come from something
mechanical or from electric shock. Read the warnings carefully.
When you see this Signal Word on the following pages, it will
alert you to the possibility of damage to your gate and/or the gate
operator if you do not comply with the cautionary statements that
accompany it. Read them carefully.
19-20
AVERTISSEMENT
Step 1: Watertight Connector Nut . . . . . . . . . . . . . . . . . . . . . . .19
Step 2: Insert Operator Cable . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Step 3: Connect Operator to Control Board . . . . . . . . . . . . . . . .20
21-22
Control
Wiring
ATTENTION
Adjusting/Running the Operator
23
24-26
IMPORTANT NOTE
• BEFORE attempting to install, operate or maintain the operator,
you must read and fully understand this manual and follow all
safety instructions.
• DO NOT attempt repair or service of your commercial door and
gate operator unless you are an Authorized Service Technician.
ATTENTION
AVERTISSEMENT
AVERTISSEMENT
Connect Transformer to Control Board . . . . . . . . . . . . . . . . . . .21
Earth Ground Rod Installation (Optional) . . . . . . . . . . . . . . . . . .22
AVERTISSEMENT
ATTENTION
TOOLS NEEDED FOR INSTALLATION
During assembly, installation and adjustment of the operator the
tools listed below will be needed.
• Wrench or Socket Set
• Phillips Head Screwdriver
• C Clamps
• Level
• Small Screwdriver
• T25 Torx Head Screwdriver
Step 1: Set Dip Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Step 2: Program Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Step 3: Set Force/Bi-part/Timer . . . . . . . . . . . . . . . . . . . . . . . . .26
Optional Control and
Safety Device Wiring
37
38
39-40
41-42
43
44
INTRODUCTION
WARNING
Power Wiring
AVERTISSEMENT
35-36
Battery Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Step 1: Manual Release . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Step 2A: Determine Position of the Pull-to-Open Bracket . . . . .12
Step 2B: Determine Position of the “Optional”
Push-to-Open Bracket (Not Provided) . . . . . . . . . . . . . . . . . . . .12
Step 3: Determine Mounting Location . . . . . . . . . . . . . . . . . . . .13
Step 4: Assemble Gate Post Bracket (Pull-to-Open) . . . . . . . . . .13
Step 5: Attach Bracket to Arm . . . . . . . . . . . . . . . . . . . . . . . . . .14
Step 6: Position Operator on Gate . . . . . . . . . . . . . . . . . . . . . . .14
Step 7: Test Gate Travel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Step 8: Secure Gate Post Bracket to Gate Post . . . . . . . . . . . . .16
Step 9: Secure Gate Bracket to Gate . . . . . . . . . . . . . . . . . . . . . .16
Step 10: Warning Sign Placement . . . . . . . . . . . . . . . . . . . . . . .17
Step 11: Open the Control Box . . . . . . . . . . . . . . . . . . . . . . . . . .18
Step 12: Select Mounting Holes . . . . . . . . . . . . . . . . . . . . . . . . .18
Step 13: Mount Control Box . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Motor Wiring
34
27-33
To Add or Reprogram a Remote Control . . . . . . . . . . . . . . . . . .27
Dip Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Wire Stop Button (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
2
ADVERTENCIA
Carton Inventory
CONTROL BOX LA400 - CONT
HARDWARE KIT
DESCRIPTION
Post Bracket
Pull to Open Bracket
Hex Bolt 5/16"-18 X 1-1/2"
Square Neck Carriage Bolt 3/8"-16 X 6"
Hex Nut 3/8"-16
Hex Nut 5/16"-18
Flat Washer 5/16"
Flat Washer 3/8"
Lock Washer 5/16"
Lock Washer 3/8"
Gate Mounting Bracket
Hairpin Clip
Pin
Hex Bolt 3/8"-16 X 1-1/2"
Bolt 2-3/4"
DESCRIPTION
Control Box
Hardware Bag
QTY
1
1
5
2
2
5
5
5
5
5
1
4
2
1
2
MISCELLANEOUS
Linear Actuator Arm
Motor Cable - Six Conductor
Warning Sign
Battery
Plug-In Transformer
QTY
1
1
9' (2.7 m)
2
2
1
LA400-S (SECOND LINEAR ACTUATOR ARM)
Extension Cable - Six Conductor
40' (12.2 m)
Junction Box - IP56
1
Phillips Head Mounting Screws
4
Anchors
4
Terminal Block - Twelve Connectors
1
NOTE: Carton inventory is based on a Single Operator. For Primary (Gate 1) and Secondary (Gate 2) installation the carton
inventory is doubled except for control box.
Additional Items Needed for Installation
Permanent fasteners for warning sign
Earth Ground Rod (Optional)
Power Wire: 120Vac (Stranded Copper Wire)
Power Wire: 24Vac Transformer (Stranded Copper Wire)
Wire Gauge
Length
Wire Gauge
Length
OR
16
100' (30 m)
14
500' (152 m)
10
1000' (305 m)
12
1000' (305 m)
Operator Dimensions and Specifications
Operating Cycles
100 per day
Main Supply (Motor)
24Vdc
Current Consumption
2A
Power Consumption
48 Watts
Battery Charger Supply
26Vac, 29VA or 36Vdc, 40VA
Solar Panel Supply (Optional)
See Accessories
Maximum Gate Width
16 ft. (4.9 m)
Maximum Gate Weight
550 Lbs. (249.5 kg)
Protection Class
NEMA 3R
Travel Speed
14-18 seconds for a 90 degree opening
Rated Operating Time
4 Minutes
Temperature
-20˚C to + 50˚C
-4˚F to + 122˚F
Main Supply (Control) Dedicated Circuit
120V~/60Hz
Absorbed Power
0.75 Watts
Protection Fuse Battery
ATC 20A
14"
(35.6 cm)
10"
6"
(25.4 cm) (15.2 cm)
Weight: 13.2 lbs. (6 kg.)
36.3"
(92.1 cm)
4.00"
(10.2 cm)
.475" DIA.
(1.2 cm DIA.)
37.4"
(95.0 cm)
4.50"
.250"
(11.2 cm) (0.635 cm)
3
UL325 Model Classifications
The LA400 is intended for use with vehicular swing gates. The operator can be used in Class I, Class II and Class III applications.
CLASS I – RESIDENTIAL VEHICULAR GATE OPERATOR
A vehicular gate operator (or system) intended for use in a home of one-to four single family dwelling, or
a garage or parking area associated therewith.
CLASS II – COMMERCIAL/GENERAL ACCESS VEHICULAR GATE OPERATOR
A vehicular gate operator (or system) intended for use in a commercial location or building such as a
multi-family housing unit (five or more single family units) hotel, garages, retail store or other building
servicing the general public.
CLASS III – INDUSTRIAL/LIMITED ACCESS VEHICULAR GATE OPERATOR
A vehicular gate operator (or system) intended for use in a industrial location or building such as a
factory or loading dock area or other locations not intended to service the general public.
UL325 ENTRAPMENT PROTECTION
REQUIREMENTS
SAFETY ACCESSORY SELECTION
All UL325 compliant LiftMaster gate operators will accept external
entrapment protection devices to protect people from motorized
gate systems. UL325 requires that the type of entrapment
protection correctly matches each gate application. Below are the
four types of entrapment protection systems recognized by
UL325 for use on this operator.
Gate Operator Entrapment Protection
UL325
Swing and Gate Barrier
Installation
(Arm) Operator
ENTRAPMENT PROTECTION TYPES
Type A: Inherent obstruction sensing system, self-contained
within the operator. This system must sense and initiate
the reverse of the gate within two seconds of contact
with a solid object.
Type B1: Connections provided for a non-contact device, such as
a photoelectric eye can be used as a secondary
protection.
Type B2: Connections provided for a contact sensor. A contact
device such as a gate edge can be used for secondary
protection.
Type E: Built-in audio alarm. Examples include sirens, horns
or buzzers.
NOTE: UL requires that all installations must
have warning signs placed in plain view on
both sides of the gate to warn pedestrians of
the dangers of motorized gate systems.
Primary
Type
Secondary
Type
Class
I and II
A
A, B1 or
B2
Class III
A, B1 or B2
A, B1,
B2 or E
Class
The chart above illustrates the entrapment protection
requirements for each of the three UL325 classes.
In order to complete a proper installation you must satisfy the
entrapment protection chart shown above. That means that
the installation must have one primary means of entrapment
protection and one independent secondary means of
entrapment protection. Both primary and secondary
entrapment protection methods must be designed, arranged
or configured to protect against entrapments in both the open
and close directions of gate travel.
For Example: For a slide gate system that is installed on a
single-family residence (UL325 Class I) you must provide the
following: As your primary type of entrapment protection you
must provide Type A inherent (built into the operator)
entrapment sensing and at least one of the following as your
secondary entrapment protection: Type B1- Non-contact
sensors such as photoelectric eyes, Type B2- Contact sensors
such as gate edges.
Moving Gate Can Cause
Injury or Death
KEEP CLEAR! Gate may move at any
time without prior warning.
Do not let children operate the gate or
play in the gate area.
This entrance is for vehicles only.
Pedestrians must use separate entrance
4
Safety Installation Information
1. Vehicular gate systems provide convenience and security. Gate systems are comprised of many component parts. The gate operator is only
one component. Each gate system is specifically designed for an individual application.
2. Gate operating system designers, installers and users must take into account the possible hazards associated with each individual application.
Improperly designed, installed or maintained systems can create risks for the user as well as the bystander. Gate systems design and
installation must reduce public exposure to potential hazards.
3. A gate operator can create high levels of force in its function as a component part of a gate system. Therefore, safety features must be
incorporated into every design. Specific safety features include:
• Gate Edges
• Guards for Exposed Rollers
• Photoelectric Sensors
• Screen Mesh
• Vertical Posts
• Instructional and Precautionary Signage
4. Install the gate operator only when:
a. The operator is appropriate for the construction and the usage class of the gate.
b. All openings of a horizontal slide gate are guarded or screened from the bottom of the gate to a minimum of 4' (1.2 m) above the ground to
prevent a 2-1/4" (6 cm) diameter sphere from passing through the openings anywhere in the gate, and in that portion of the adjacent fence
that the gate covers in the open position.
c. All exposed pinch points are eliminated or guarded, and guarding is supplied for exposed rollers.
5. The operator is intended for installation only on gates used for vehicles. Pedestrians must be supplied with a separate access opening. The
pedestrian access opening shall be designed to promote pedestrian usage. Locate the gate such that persons will not come in contact with the
vehicular gate during the entire path of travel of the vehicular gate.
6. The gate must be installed in a location so that enough clearance is supplied between the gate and adjacent structures when opening and
closing to reduce the risk of entrapment. Swinging gates shall not open into public access areas.
7. The gate must be properly installed and work freely in both directions prior to the installation of the gate operator.
8. Controls intended for user activation must be located at least six feet (6') away from any moving part of the gate and where the user is
prevented from reaching over, under, around or through the gate to operate the controls. Outdoor or easily accessible controls shall have a
security feature to prevent unauthorized use.
9. The Stop and/or Reset (if provided separately) must be located in the line-of-sight of the gate. Activation of the reset control shall not cause the
operator to start.
10. A minimum of two (2) WARNING SIGNS shall be installed, one on each side of the gate where easily visible.
11. For a gate operator utilizing a non-contact sensor:
a. Reference owner’s manual regarding placement of non-contact sensor for each type of application.
b. Care shall be exercised to reduce the risk of nuisance tripping, such as when a vehicle trips the sensor while the gate is still moving.
c. One or more non-contact sensors shall be located where the risk of entrapment or obstruction exists, such as the perimeter reachable by a
moving gate or barrier.
12. For a gate operator utilizing a contact sensor such as an edge sensor:
a. One or more contact sensors shall be located where the risk of entrapment or obstruction exists, such as at the leading edge, trailing edge
and post mounted both inside and outside of a vehicular horizontal slide gate.
b. One or more contact sensors shall be located at the bottom edge of a vehicular vertical lift gate.
c. A hard wired contact sensor shall be located and its wiring arranged so the communication between the sensor and the gate operator is not
subject to mechanical damage.
d. A wireless contact sensor such as the one that transmits radio frequency (RF) signals to the gate operator for entrapment protection
functions shall be located where the transmission of the signals are not obstructed or impeded by building structures, natural landscaping or
similar obstruction. A wireless contact sensor shall function under the intended end-use conditions.
e. One or more contact sensors shall be located on the inside and outside leading edge of a swing gate. Additionally, if the bottom edge of a
swing gate is greater than 6" (152 mm) above the ground at any point in its arc of travel, one or more contact sensors shall be located on
the bottom edge.
f. One or more contact sensors shall be located at the bottom edge of a vertical barrier (arm).
5
OVERVIEW OF TYPICAL
INSTALLATION
Ou
To prevent SERIOUS INJURY or DEATH; one or more
non-contact sensors shall be located where the risk of
entrapment or obstruction exists.
CAUTION
Left-Hand Gate
e
tsid
WARNING
y
ert
p
Pro
Warning Sign
Hinge
use
Ca
Antenna
Control Box
with Batteries
n Ca
te athat any
e
g Ga or De
mov
vin
or
may
Mo Injury
Gate ing. gate
AR! warnate the
P CLE prior oper
KEE without ren .
only nce
time let child area cles entra
vehi rate
not gate
Do in the is for sepa
nce t use
play
entrans mus
This stria
Pede
Post Bracket
Gate Bracket
Operator
Power Cable
f
n o vel
o
i
t
a
ec Tr
DirGate
AVERTISSEMENT
ATTENTION
rty
pe
ro
eP
id
PVC Conduit (not provided) to
protect the power cable and low
voltage wire from lawn mowers
and string trimmers.
Ins
Entrapment Sensors
Right-Hand Gate
Warning Sign
Hinge
esu
aC
yna
n
hta aC et
ta e eD aG
gn
vom ro
yam yru ivo
tag .gninra etaG jnI M
eht
w r !RA
o
etar
E
epo irp tuo LC PE
htiw EK
n
artnylno s
. erd
e et elcih aera e lihc te emit
l
t
ara ev
pes rof ag eht ton oD
esu si ec
n
tsu nar i yalp
m s tne
nair sih
tsed T
eP
ro e
ecn
Antenna
Post Bracket
Gate Bracket
Operator
Control Box
with Batteries
ADVERTENCIA
PRECAUCIÓN
Power Cable
PVC Conduit (not provided) to
protect the power cable and
low voltage wire from lawn
mowers and string trimmers.
Entrapment Sensors
NOTE: One or more non-contact sensors shall be located where the risk of entrapment or obstruction exists at either the
opening or closing direction. Care shall be exercised to reduce the risk of nuisance tripping, such as when a vehicle, trips
the sensor while the gate is still moving.
6
Dual Gate Typical Installation
Junction Box
erty
ide
s
Out
p
Pro
Extension Cable
Warning Sign
Entrapment Sensors
Gate 2
Hinge
use
n Ca
Ca
te athat any
e
g Ga or De
mov
vin
or
may .
Mo Injury
Gatewarning gate
the
AR! r
P CLEout prio operate
KEE with
ren .
only ance
time let child area cles entr
vehi rate
not gate
Do in the is for sepa
ance t use
play
entr mus
Thisestrians
Ped
Control Box
with Batteries
Antenna
f
n oavel
o
i
t
ec Tr
Dir ate 2
G
Post Bracket
Gate Bracket
Gate 1
Power Cable
of el
n
v
o
i
ect 1 Tra
r
i
D ate
G
ty
de
nsi
I
PVC Conduit (not provided) to
protect the power cable and
low voltage wire from lawn
mowers and string trimmers.
Entrapment Sensors
7
P
er
rop
Safety Precautions for Swing and Ornamental “Grill Type Gates”
WARNING
WARNING
To prevent SERIOUS INJURY or DEATH from a moving gate:
• Entrapment protection devices MUST be installed to protect
anyone who may come near a moving gate.
• Locate entrapment protection devices to protect in BOTH the
open and close gate cycles.
• Locate entrapment protection devices to protect between
moving gate and RIGID objects, such as posts.
• A swinging gate shall NOT open into public access ways.
CAUTION
WARNING
AVERTISSEMENT
AVERTISSEMENT
ATTENTION
AVERTISSEMENT
Warning Sign Placement
WARNING
WARNING
To prevent SERIOUS INJURY or DEATH from a moving gate:
• Install warning signs on EACH side of gate in PLAIN VIEW.
• Permanently secure each warning sign in a suitable manner
using fastening holes.
CAUTION
WARNING
ADVERTENCIA
ADVERTENCIA
PRECAUCIÓN
AVERTISSEMENT
ADVERTENCIA
AVERTISSEMENT
Moving Gate Can Cause
Injury or Death
ATTENTION
AVERTISSEMENT
KEEP CLEAR! Gate may move at any
time without prior warning.
Do not let children operate the gate or
play in the gate area.
This entrance is for vehicles only.
Pedestrians must use separate entrance
8
Before Installation Check Your Gate
Gate and gate post MUST be plumb.
Gate MUST be level
Gate MUST NOT hit or drag across ground
Remove ANY/ALL wheels from the bottom of the gate
Gate MUST swing freely and be supported entirely by it’s hinges. Heavy duty, ball
bearing type hinges are recommended.
9
Mounting Options
Mounting locations vary depending on type and style of your gate. Minimum distance from the ground should not be less
than 4" from the bottom of the gate operator arm.
Optional:
= Gate post bracket mounting locations
= Gate bracket mount locations
Recommended:
= Gate post bracket mounting locations
= Gate bracket mount locations
10
INSTALLATION
Step 1: Manual Release
Insert the key into the lock and turn counter-clockwise 180°. Turn the release lever counter-clockwise 180°. The operator is
in manual mode.
Release Lever
11
Step 2A: Determine Position of the Pull-to-Open Bracket
The Pull-To-Open bracket can be assembled to work on a Left-Hand or a Right-Hand gate. Review the gate types below
and select the type of installation you will require.
NOTE: If the Pull-To-Open bracket is not assembled correctly you will damage the operator.
Right-Hand Gate
Left-Hand Gate
Left-Hand Gate
Right-Hand Gate
Step 2B: Determine Position of the “Optional” Push-to-Open Bracket
(Not provided. See Accessories.)
The Push-To-Open bracket can be assembled to work on a Left-Hand or a Right-Hand gate. Review the gate types below
and select the type of installation you will require.
Right-Hand Gate
Left-Hand Gate
Left-Hand Gate
Right-Hand Gate
12
Step 3: Determine Mounting Location
The gate post bracket assembly can be mounted several places on the gate post. Refer to the illustrations on page 10
for the ideal mounting location.
Refer to the illustrations below to determine the appropriate dimensions for the Pull-To-Open bracket.
NOTE: It may be necessary to add shims (angle iron, sheets of metal or wood) to the gate post to achieve the required
dimensions.
Gate Post
Gate Post
Gate Post
Gate Hinge Point
Gate Hinge Point
7" (18 cm)
Gate Hinge Point
7" (18 cm)
Operator
Hinge Point
7" (18 cm)
Operator
Hinge Point
7" (18 cm)
Operator
Hinge Point
7" (18 cm)
Gate Post
Gate Post
Gate Post
Gate Hinge Point
7" (18 cm)
Gate Hinge Point
Gate Hinge Point
7" (18 cm)
7" (18 cm)
Operator
Hinge Point
7" (18 cm)
Operator
Hinge Point
Operator
Hinge Point
7" (18 cm)
7" (18 cm)
7" (18 cm)
Step 4: Assemble Gate Post Bracket (Pull-to-Open)
Assemble Gate Post bracket by placing Pull-To-Open bracket on top of Post bracket. Insert bolt through both brackets
and secure with washer, lock washer and nut. Insert second bolt through both brackets and secure with washer, lock
washer and nut.
5/16" Hex Bolt
3/8" Hex Bolt
Pull-to-Open
Bracket
Pull-to-Open
Bracket
Post Bracket
Post Bracket
3/8" Washer
5/16" Washer
3/8" Lock Washer
5/16" Lock Washer
3/8" Nut
5/16" Nut
13
NOTE: All the illustrations on the following pages display a typical Left-Hand Gate installation.
Step 5: Attach Brackets to Arm
Attach gate post bracket to arm using hex bolt and lock nut with nylon insert. Attach gate bracket to arm using pin and
hairpin clip.
Hex Bolt
Pin
Gate Post
Bracket
Gate Bracket
Hairpin
Clip
Hairpin
Clip
Step 6: Position Operator on Gate
The gate post bracket assembly can be mounted several places on the gate post. Refer to the illustrations on page 10
for mounting options.
Place opener arm against gate post at the desired vertical position and temporarily secure Gate Post bracket with
C-clamp. Arm must be level.
Open gate to desired open position (no greater than 100°) and hold arm against gate. Mark mounting holes on gate
for reference.
Temporarily secure the gate bracket using a C-clamp.
14
Step 7: Test Gate Travel
Manually open and close the gate.
Ensure that the arm does not bind against the pull-to-open bracket.
Ensure that the piston does not bottom out.
1/2" (1.3 cm)
Do not allow piston to fully extend
or fully retract.
1/2" (1.3 cm)
NOTE: If gate does not open and close completely adjust the position of the gate bracket and mark new mounting holes.
15
Step 8: Secure Gate Post Bracket to Gate Post
Mark holes for gate post bracket.
Remove C-clamp and operator. Set aside and drill adequate holes in gate post.
Welder (Optional)
Secure gate post bracket to gate post using hardware. Keep arm level.
Lock Washers
Hex Nuts
Flat Washers
Carriage Bolts
Step 9: Secure Gate Bracket to Gate
Drill holes in gate or reinforcement (if necessary) large enough for the gate bracket mounting
hardware. Secure gate bracket to gate using hardware (not provided). Keep arm level.
Welder (Optional)
NOTE: Some installations may
require additional reinforcement
be installed on the gate.
Angle
Iron
Wood
Reinforcement Area
OR
Arm
Hex Nut
Flat Washer
Lock Washer
OR
Flat
Bar
Gate Bracket
Hex Bolt
Manually move the gate to verify gate opens and closes fully.
16
Step 10: Warning Sign Placement
Warning placards MUST be installed on both sides
of the gate and in plain view.
WARNING
To prevent SERIOUS INJURY or DEATH from a moving gate:
• Install warning signs on the front and back of the gate
in PLAIN VIEW.
• Permanently secure each warning sign in a suitable manner
using fastening holes.
CAUTION
Gate Post
Fence
Gate
Moving Gate Can Cause
Injury or Death
KEEP CLEAR! Gate may move at any
time without prior warning.
Gate Travel
Path
Do not let children operate the gate or
play in the gate area.
This entrance is for vehicles only
Pedestrians must use separate entrance
Inside
Property
If you are installing a 2nd operator repeat installation steps 1-10 for the second gate before proceeding to the next page.
17
NOTE: It is recommended that the control box be mounted within 3' (.9 m) of Gate 1 or Gate 2.
Step 11: Open the Control Box
Remove screws and open the control box.
Screws (4)
Step 12: Select Mounting Holes
Select holes to be used for mounting and knock out using a screwdriver and hammer.
Knock Outs
P2
R223
P1
CLOSE
EDGE
J19
Ø14GPØ89ØE
Ø14LGØ89ØE
Ø14SKØ89ØE
K6
ALARM
R2Ø7
J1
NO
Z2Ø
R227
C
K5
MAGLOCK
OPEN EDGE/
PHOTO
NO
L1
R224
C
1
S8
OFF
OFF
SINGLE
NO
NO
LEARN
XMITTER
R1
10A 32V
2
GATE 1
1 2 3 4 5
R2
O
N
NC
Z1
Z22
R92
U4
ON SAVE
ON MAGLOCK
DUAL MODE
NC
EDGE
PHOTO
NC
Z9
OPEN
PHOTO
S1
F3
Knock Outs
R91
BRN
D1Ø
GRN
R94
K2
Z8
WHT
CLOSE
PHOTO
DIAGNOSTIC
YEL
R93
BLU
GATE 1
RED
K1 Q9
Z12
SET
OPEN
LIMIT
SET
CLOSE
LIMIT
R9Ø
ACCESSORY
POWER
Knock Outs
LEARN
LIMITS
24V
TIMER
RUNNING
GATE 2
BIPART
DELAY
24V
FORCE
R1Ø1
BRN
COM
OVLD
SWITCHED
ACCESSORY
POWER
Knock Outs
CONTROL
INPUTS
TIMER TO SINGLE
BUTTON
CLOSE
R1ØØ
OVLD
OPEN
SINGLE BUTTON
F4
GRN
RESET
ACCESSORY
OVLD
10A 32V
WHT
STOP
K4
YEL
MIN
MAX
OFF
MAX
OFF
MAX
COM
F5
BLU
COM
D21
RED
D9
K3
D8
GATE 2
POWER
R35
C12
D27 Z3
F7
Z4
Q22
C13
D22
LOOP
INPUTS
C4
SHADOW
U3
INTERRUPT
C11
R4
C2
R196
F6
24 VAC/
SOLAR
INPUT
J4
COM
CHGR
OVLD
D15
F2
MOV2
R9
MOV1
F1 20A 32V
D4
D1
C64
JMPR2
JMPR1
D2
U2
FUSE
OPEN
BATT 2
BATT 1
D6
DB1
Knock Outs
Step 13: Mount Control Box
Secure control box to mounting surface (post, wall, column, etc.) using appropriate hardware.
Round Gate
Post
Square Gate
Post
Lock Washer
(Not Provided)
U Bolt
(Not Provided)
Screw
Washer
(Not Provided)
Hex Nut
(Not Provided)
18
NING
WARNING
MOTOR WIRING
ON
WARNING
To reduce the risk of SEVERE INJURY or DEATH:
• ANY maintenance to the operator or in the area near the
operator MUST not be performed until disconnecting the
electrical power and locking-out the power via the operator
power switch. Upon completion of maintenance the area MUST
be cleared and secured, at that time the unit may be returned
to service.
• Disconnect power at the fuse box BEFORE proceeding.
Operator MUST be properly grounded and connected in
accordance with local electrical codes. NOTE: The operator
should be on a separate fused line of adequate capacity.
• ALL electrical connections MUST be made by a qualified
individual.
SEMENT
ION
ENCIA
• DO NOT install ANY wiring or attempt to run the operator
without consulting the wiring diagram. We recommend that
you install an optional reversing edge BEFORE proceeding with
the control station installation.
• ALL power wiring should be on a dedicated circuit and well
protected. The location of the power disconnect should be
visible and clearly labeled.
• ALL power and control wiring MUST be run in separate
conduit.
• BEFORE installing power wiring or control stations be sure to
follow ALL specifications and warnings described below.
Failure to do so may result in SEVERE INJURY to persons
and/or damage to operator.
AVERTISSEMENT
AVERTISSEMENT
Step 1: Watertight Connector Nut
Insert operator cable through watertight connector nut.
Operator
Cable
Watertight
Connector
Nut
Operator
ADVERTENCIA
Step 2: Insert Operator Cable
Insert operator cable through watertight connector mounted in the bottom of the control box.
ADVERTENCIA
CIÓN
P2
J19
J1
Ø14GP
14GPØ89
89ØE
Ø14LG
14LGØ89
89ØE
Ø14SK
14SKØ89
89ØE
R223
P1
L1
CLOSE
EDGE
K6
S8
LEARN
XMITTER
Z2Ø
R227
K5
OPEN EDGE/
PHOTO
NO
2
OFF
OFF
SINGLE
NO
NO
1 2 3 4 5
1
R2Ø7
NO
C
MAGLOCK
O
N
ALARM
ON SAVE
ON MAGLOCK
DUAL MODE
NC
EDGE
NC
PHOTO
S1
L1
R224
C
Z22
R92
U4
NC
ON
R2
Z1
OFF
Z9
MAGLOCK
LEARN
XMITTER
R1
OPEN
PHOTO
10A 32V
GATE 1
R91
F3
BRN
D1Ø
GRN
Control Box
R94
K2
24V
Z8
WHT
CLOSE
PHOTO
DIAGNOSTIC
YEL
R93
BLU
GATE 1
RED
K1 Q9
Z12
SET
CLOSE
LIMIT
SET
OPEN
LIMIT
R9Ø
ACCESSORY
POWER
LEARN
LIMITS
GATE 2
24V
COM
OVLD
CONTROL
INPUTS
TIMER TO
CLOSE
FORCE
R1Ø1
BRN
TIMER
RUNNING
OPEN
R1ØØ
SINGLE BUTTON
F4
GRN
RESET
ACCESSORY
OVLD
10A 32V
WHT
STOP
K4
YEL
OFF
MAX
COM
F5
BLU
COM
D21
RED
D9
K3
D8
GATE 2
POWER
R35
C12
D27 Z3
F7
Z4
Q22
C13
D22
LOOP
INPUTS
C4
SHADOW
U3
INTERRUPT
C11
R196
F6
24 VAC/
SOLAR
INPUT
F2
MOV2
R9
MOV1
JMPR2
JMPR1
FUSE
OPEN
D2
U2
BATT 2
BATT 1
D6
DB1
F1 20A 32V
D4
D1
C64
P2
Watertight
Connector
J19
Ø14GPØ89ØE
Ø14LGØ89ØE
Ø14SKØ89ØE
J1
C2
COM
CHGR
OVLD
D15
R4
J4
L1
1 2 3 4 5
S8
O
N
1
LEARN
XMITTER
2
Operator
Cable
S1
Watertight
Connector
Nut
19
Operator
Cable
Operator
Step 3: Connect Operator to Control Board
Extend cable and wires to “Gate 1” connector for single gate arm installation and connect as shown. Repeat
for “Gate 2” connector and connect as shown.
C
Gate 1
NOTE: Wire connectors can be
removed to simplify wiring.
NC
Z1
R1
10A 32V
GATE 1
Brown
F3
BRN
D1Ø
K2
Yellow
M
CO
1
CA
EXIT
HOUSE
WHT
2
EXIT
LL
GRN
White
AUTO
Green
TELCO
YEL
Blue
BLU
Red
RED
K1 Q
Z12
R9Ø
ACCESSORY
POWER
Gate 2
24V
ACCESSORY
POWER
NC
Z1
BRN
24V
GRN
Brown
F3
BRN
Green
White
10A 32V
WHT
P2
Yellow
J19
J1
Ø14GPØ89ØE
Ø14LGØ89ØE
Ø14SKØ89ØE
L1
P2
2
CLOSE
EDGE
Ø14GP
14GPØ89
89ØE
Ø14LG
14LGØ89
89ØE
Ø14SK
14SKØ89
89ØE
NO
S1
BLU
R2Ø7
Z2Ø
R227
C
K5
MAGLOCK
Red
OPEN EDGE/
PHOTO
NO
YEL
Blue
R223
J19
K6
ALARM
J1
LEARN
XMITTER
P1
1 2 3 4 5
S8
O
N
1
L1
R224
C
S8
Z1
LEARN
XMITTER
R1
10A 32V
2
1 2 3 4 5
OFF
OFF
SINGLE
NO
NO
R2
GATE 1
O
N
1
NC
RED
Z22
R92
U4
ON SAVE
ON MAGLOCK
DUAL MODE
NC
EDGE
NC
PHOTO
K2
GRN
Z9
OPEN
PHOTO
S1
R91
F3
BRN
D1Ø
GRN
R94
K2
GATE 2
Z8
WHT
CLOSE
PHOTO
DIAGNOSTIC
YEL
R93
BLU
GATE 1
RED
Z12
SET
CLOSE
LIMIT
SET
OPEN
LIMIT
K1 Q9
R9Ø
ACCESSORY
POWER
LEARN
LIMITS
GATE 2
24V
TIMER
RUNNING
COM
OVLD
OVLD
SWITCHED
ACCESSORY
POWER
CONTROL
INPUTS
24V
R1Ø1
BRN
OPEN
R1ØØ
SINGLE BUTTON
F4
GRN
RESET
ACCESSORY
OVLD
10A 32V
WHT
STOP
K4
YEL
COM
F5
BLU
COM
D21
RED
POWER
R35
D9
K3
D8
GATE 2
C12
D27 Z3
F7
Z4
Q22
C13
D22
LOOP
INPUTS
C4
SHADOW
U3
C2
R196
R4
F6
24 VAC/
SOLAR
INPUT
J4
COM
CHGR
OVLD
D15
R4
D15
INTERRUPT
C11
F2
MOV2
R9
MOV1
JMPR1
D2
U2
FUSE
OPEN
BATT 2
BATT 1
D6
DB1
F1 20A 32V
D4
D1
C64
JMPR2
Control Box
Operator
Cable
“Gate 2”
Operator
Cable
“Gate 1”
Watertight
Connector
Nut
Control Box
Operator
Cable
NOTE: Never allow operator cable to drag on ground.
20
Operator
C2
R196
WARNING
POWER WIRING
WARNING
WARNING
CAUTION
CAUTION WARNING
To AVOID damaging plug-in transformer, it MUST be enclosed
in a suitable weatherproof enclosure and provided with proper
weatherproof fixtures.
To AVOID damaging gas, power or other underground utility
lines, contact underground utility locating companies BEFORE
digging.
Connect Transformer to Control Board
NOTE: All power wiring should be on a dedicated circuit and well protected.
Calculated using NEC guidelines. Local codes and conditions must be reviewed for suitability of wire installation.
The transformer can be plugged into a receptacle external to the control box. Run low voltage wire between the
transformer and control box. This will create more space in the control box for accessories.
AVERTISSEMENT
AVERTISSEMENT
AVERTISSEMENT
Dedicated Outlet
ATTENTION
AVERTISSEMENT
ATTENTION
Control Box
Transformer
Operator
ADVERTENCIA
ADVERTENCIA
ADVERTENCIA
OR
Connect 120Vac directly to the box and plug the transformer to the receptacle
inside the control box.
ADVERTENCIA
PRECAUCIÓN
Off
Main
Room
Control Box
Transformer
Off
On
P2
CLOSE
EDGE
J19
K6
Ø14GP
14GPØ89
89ØE
Ø14LG
14LGØ89
89ØE
Ø14SK
14SKØ89
89ØE
ALARM
R2Ø7
J1
NO
Z2Ø
R227
C
K5
MAGLOCK
OPEN EDGE/
PHOTO
NO
L1
R224
C
OFF
OFF
SINGLE
NO
NO
LEARN
XMITTER
R1
2
1 2 3 4 5
Z22
R92
U4
ON SAVE
ON MAGLOCK
DUAL MODE
NC
EDGE
NC
PHOTO
Z9
OPEN
PHOTO
S1
R91
F3
Off
On
Off
Bathroon.
S8
R2
10A 32V
GATE 1
O
N
1
NC
Z1
BRN
D1Ø
GRN
R94
K2
Z8
WHT
CLOSE
PHOTO
DIAGNOSTIC
YEL
R93
BLU
GATE 1
RED
SET
K1 Q9
OPEN
LIMIT
Z12
SET
CLOSE
LIMIT
R9Ø
ACCESSORY
POWER
LEARN
LIMITS
GATE 2
24V
SWITCHED
ACCESSORY
POWER
TIMER
RUNNING
CONTROL
INPUTS
24V
R1Ø1
BRN
Off
F4
GRN
ACCESSORY
OVLD
10A 32V
WHT
P2
K4
YEL
J19
F5
BLU
D21
RED
Ø14GPØ89ØE
Ø14LGØ89ØE
Ø14SKØ89ØE
R35
D9
K3
D8
GATE 2
C12
D27 Z3
F7
Z4
Q22
C13
D22
F6
F2
R9
MOV1
D4
D1
C64
JMPR2
JMPR1
D2
U2
Off
D6
Off
1
FUSE
OPEN
S8
LEARN
XMITTER
2
MOV2
DB1
21
L1
CHGR
OVLD
R196
1 2 3 4 5
C2
24 VAC/
SOLAR
INPUT
Main Dept.
Manu. 2 Rm
C4
U3
C11
D15
R4
J4
O
N
Eug. Dept.
Manu. 1 Rm
R1ØØ
J1
Off
Air (2)
Conditioner
Comp.
Serve 1
R223
P1
Off
On
LA400
On
On
Air (1)
Conditioner
Off
On
On
Comp.
Serve 2
Off
Conference
Room 2
On
Conference
Room 1
Off
Circuit Panel
Conference
Rm 2, 3
Off
Refer.
Bus 1, 2, 3
Off
PRECAUCIÓN
S1
WARNING
EARTH GROUND ROD
INSTALLATION (OPTIONAL)
CAUTION
To AVOID damaging gas, power or other underground utility
NOTE: For proper operation, do not connect the
lines, contact underground utility locating companies BEFORE
earth ground rod to the green screw on the outlet
digging.
plate.
1. Install earth ground rod within 3' (0.9 m) of the
operator.
2. Disconnect and remove the green/yellow ground wire connected to the screw terminal of the control board.
3. Attach earth ground rod wire to the screw terminal of the control board marked . Ensure the power wiring ground
connection remains securely connected to the green screw on the outlet plate.
AVERTISSEMENT
R4
C2
24 VAC/
ATTENTION
SOLAR
INPUT
J4
P2
J19
J1
Ø14GPØ89ØE
Ø14LGØ89ØE
Ø14SKØ89ØE
NO
L1
C
S8
OFF
OFF
SINGLE
NO
NO
LEARN
XMITTER
2
1 2 3 4 5
1
O
N
NC
ALARM
ON SAVE
ON MAGLOCK
DUAL MODE
NC
EDGE
NC
PHOTO
S1
BRN
GRN
MAGLOCK
WHT
R223
P1
YEL
CLOSE
EDGE
J19
R2Ø7
BLU
NO
Z2Ø
R227
C
Z1
Z1
RED
K5
OPEN EDGE/
PHOTO
GATE 1
GATE 1
L1
R224
GRN
24V
Z22
R92
U4
R2
Z9
LEARN
XMITTER
R1
OPEN
PHOTO
10A 32V
2
ACCESSORY
POWER
R91
F3
D1Ø
CONTROL
INPUTS
K2
DIAGNOSTIC
24V
BLU
GRN
Z12
OPEN
K1 Q9
SET
OPEN
LIMIT
SET
CLOSE
LIMIT
Ground Screw
SINGLE BUTTON
GATE 1
BRN
RESET
LEARN
LIMITS
WHT
R9Ø
GATE 2
ACCESSORY
POWER
YEL
BLU
R1Ø1
RED
R1ØØ
STOP
TIMER
RUNNING
FORCE
COM
CONTROL
INPUTS
TIMER TO SINGLE
BUTTON
CLOSE
COM
OPEN
POWER
SINGLE BUTTON
F4
GATE 2
RESET
ACCESSORY
OVLD
10A 32V
STOP
K4
OFF
MAX
COM
F5
COM
D21
POWER
R35
D9
K3
D8
C12
D27 Z3
F7
Z4
Q22
C13
D22
LOOP
INPUTS
C4
SHADOW
U3
INTERRUPT
C11
R196
COM
F6
24 VAC/
SOLAR
INPUT
D27 Z3
CHGR
OVLD
POWER
D15
C2
GATE 2
F2
MOV2
R9
MOV1
D4
D1
C64
JMPR2
JMPR1
D2
U2
FUSE
OPEN
BATT 2
BATT 1
D6
DB1
F1 20A 32V
R4
J4
FUSE
OPEN
FUSE
OPEN
Control Box
ADVERTENCIA
3' (0.9 m)
12 Gauge Wire
PRECAUCIÓN
8' (2.4 m)
Earth Ground
Installation (Optional)
22
WARNING
CONTROL WIRING
CAUTION
To reduce the risk of FIRE or INJURY to persons use ONLY
LiftMaster part #K74-30762 for replacement batteries.
24 VAC/
SOLAR
INPUT
J4
MOV2
AVERTISSEMENT
P2
J19
J1
Ø14GPØ89ØE
Ø14LGØ89ØE
Ø14SKØ89ØE
ATTENTION
NO
L1
C
S8
OFF
OFF
SINGLE
NO
NO
LEARN
XMITTER
2
1 2 3 4 5
1
O
N
NC
ON SAVE
ON MAGLOCK
DUAL MODE
NC
EDGE
NC
PHOTO
S1
BRN
GRN
WHT
R223
P1
YEL
CLOSE
EDGE
J19
R2Ø7
BLU
NO
Z2Ø
R227
C
Z1
RED
K5
OPEN EDGE/
PHOTO
GATE 1
L1
R224
GRN
24V
Z22
R92
U4
R2
Z9
LEARN
XMITTER
R1
OPEN
PHOTO
10A 32V
2
ACCESSORY
POWER
R91
F3
D1Ø
CONTROL
INPUTS
K2
DIAGNOSTIC
24V
BLU
OPEN
GRN
Z12
SINGLE BUTTON
GATE 1
BRN
K1 Q9
SET
OPEN
LIMIT
SET
CLOSE
LIMIT
RESET
LEARN
LIMITS
WHT
R9Ø
GATE 2
YEL
BLU
RED
STOP
TIMER
RUNNING
COM
CONTROL
INPUTS
TIMER TO SINGLE
BUTTON
CLOSE
FORCE
R1Ø1
COM
OPEN
POWER
R1ØØ
SINGLE BUTTON
F4
GATE 2
RESET
ACCESSORY
OVLD
10A 32V
STOP
K4
OFF
MAX
COM
F5
COM
D21
POWER
R35
D9
K3
D8
C12
D27 Z3
F7
Z4
Q22
C13
D22
LOOP
INPUTS
C4
SHADOW
U3
INTERRUPT
C11
POWER
D15
C2
CHGR
OVLD
R196
COM
F6
24 VAC/
SOLAR
INPUT
F2
MOV2
R9
MOV1
D4
D1
C64
JMPR2
JMPR1
D2
U2
BATT 2
FUSE
OPEN
BATT 1
D6
DB1
F1 20A 32V
USE DEDICATED CIRCUIT
CHARGING
The 24Vac input can accept a charging transformer (26Vac, 29VA
or 36Vdc, 40VA).
ADVERTENCIA
OR
PRECAUCIÓN
BATT 1
BATT1
Connector
BATT2
Connector
BATTERY
The main source of power for the operator is the
batteries. The batteries can be charged in circuit by
using a charging transformer or solar panels.
SOLAR PANEL KIT
Optional Liftmaster solar panel(s) kit may be used to charge the
batteries. (See Accessories)
23
ADJUSTING / RUNNING THE OPERATOR
Step 1: Set Dip Switch
1. The Save switch must be set to the OFF position prior to programming or changing the switches.
2. Set switch to Single for single gate installation. For Dual (Gate 1 and 2) installation set switch on Dual.
NOTE: Save switch must be in the OFF position prior to programming or changing switches for the change to be saved.
O
N
1 2 3 4 5
OFF
OFF
SINGLE
NO
NO
ON
ON
DUAL
NC
NC
SAVE
MAGLOCK
MODE
EDGE
PHOTO
S1
FACTORY DEFAULT SHOWN
P2
CLOSE
EDGE
J19
J1
Ø14GPØ89ØE
Ø14LGØ89ØE
Ø14SKØ89ØE
OPEN/EGE
PHOTO
L1
OFF
OFF
SINGLE
NO
NO
1 2 3 4 5
S8
LEARN
XMITTER
2
O
N
1
ON SAVE
ON MAGLOCK
DUAL MODE
NC
EDGE
NC
PHOTO
OPEN
PHOTO
S1
CLOSE
PHOTO
GATE1
SET
OPEN
LIMIT
SET
CLOSE
LIMIT
LEARN
LIMITS
24V
GATE 2
SWITCHED
ACCESSORY
POWER
GATE 1 AND GATE 2
GATE 1
24
1 2 3 4 5
1 2 3 4 5
OFF
OFF
SINGLE
NO
NO
ON
ON
DUAL
NC
NC
O
N
O
N
OFF
OFF
SINGLE
NO
NO
OVLD
ON
ON
DUAL
NC
NC
Step 2: Program Limits (Ensure Save Switch is in the OFF position
before beginning)
DIAGNOSTIC
1. With the gate in the closed position, press the “LEARN LIMITS” button.
The “SET OPEN LIMIT” LED will blink.
GATE 1
SET
T
EN
N
OPEN
T
LIMIT
SET
CLOSE
LIMIT
LEARN
LIMITS
GATE 2
FORCE
2. Use the “Gate 1” buttons to move Gate 1
to the desired open position (not to
exceed 100°). If you have gone beyond
the desired open position you can jog
the gate towards the close position by
using the opposite Gate 1 button. Repeat
if Gate 2 is present using the “Gate 2”
buttons.
LEARN LIMITS Button
DIAGNOSTIC
GATE 1
SET
OPEN
LIMIT
SET
CLOSE
LIMIT
LEARN
LIMITS
DIAGNOSTIC
DIAGNOSTIC
GATE 1
SET
OPEN
LIMIT
SET
CLOSE
LIMIT
LEARN
LIMITS
GATE 1
SET
OPEN
LIMIT
SET
CLOSE
LIMIT
GATE 2
LEARN
LIMITS
GATE 2
FORCE
FORCE
GATE 2
DIAGNOSTIC
P2
CLOSE
EDGE
J19
J1
Ø14GP
14GPØ89
89ØE
Ø14LG
14LGØ89
89ØE
Ø14SK
14SKØ89
89ØE
OPEN/EGE
PHOTO
L1
S8
LEARN
XMITTER
2
OFF
OFF
SINGLE
NO
NO
1 2 3 4 5
1
O
N
FORCE
ON SAVE
ON MAGLOCK
DUAL MODE
EDGE
NC
PHOTO
NC
OPEN
PHOTO
S1
CLOSE
PHOTO
GATE1
SET
OPEN
LIMIT
SET
CLOSE
LIMIT
LEARN
LIMITS
24V
GATE 2
OVLD
SINGLE
BUTTON
SWITCHED
ACCESSORY
POWER
3. Press the “LEARN LIMITS”
button again to set the Open
position. The “SET CLOSE
LIMIT” LED will blink and
beep once.
4. Use the “Gate 1” buttons to move
Gate 1 to the desired close
position. If you have gone beyond
the desired closed position you
can jog the gate towards the open
position by using the opposite
Gate 1 button. Repeat if Gate 2 is
present using the “Gate 2”
buttons.
GATE 1
SET
OPEN
LIMIT
SET
S
C
CLO
CLOSE
L
LIMIT
LEARN
LIMITS
GATE 2
FORCE
DIAGNOSTIC
DIAGNOSTIC
SET
CLOSE
LIMIT
LEARN
LIMITS
SINGLE
BUTTON
O
GATE 1
SET
OPEN
LIMIT
SET
S
C
CL
CLOSE
L
LIMIT
LEARN
LIMITS
GATE 2
SINGLE B
O
N
1 2 3 4 5
OFF
OFF
SINGLE
NO
NO
S1
7. Set Save Switch to the ON position.
25
SET
CLOSE
LIMIT
ON
ON
DUAL
NC
NC
SAVE
MAGLOCK
MODE
EDGE
PHOTO
LEARN
LIMITS
GATE 2
FORCE
FORCE
FORCE
6. Using the single button control on the board, run
the gate(s) from the closed position to the open
position. This will learn the forces.
SET
OPEN
LIMIT
GATE 2
DIAGNOSTIC
5. Press the “LEARN LIMITS” button
again to set the Closed position. The
“SET CLOSE LIMIT” LED will blink and
beep. The limits are now set.
GATE 1
GATE 1
SET
OPEN
LIMIT
Step 3: Set Force / Bi-Part / Timer
P2
CLOSE
EDGE
J19
BI-PART DELAY
Control
J1
Ø14GP
14GPØ89
89ØE
Ø14LG
14LGØ89
89ØE
Ø14SK
14SKØ89
89ØE
OPEN/EGE
PHOTO
L1
OFF
OFF
SINGLE
NO
NO
1 2 3 4 5
S8
LEARN
XMITTER
2
O
N
1
ON SAVE
ON MAGLOCK
DUAL MODE
EDGE
NC
PHOTO
NC
OPEN
PHOTO
S1
CLOSE
PHOTO
SET
OPEN
LIMIT
FORCE
Control
24V
OVLD
BIPART
DELAY
FORCE
SWITCHED
ACCESSORY
POWER
TIMER TO
CLOSE
TIMER TO
CLOSE
Control
BI-PART
DELAY
FORCE
TIMER TO
CLOSE
Z9
Z8
MIN
FORCE CONTROL
Set the force control such that the
opener will complete a full cycle of
gate travel but will reverse off an
obstruction without applying an
excessive amount of force.
OFF
MAX
BI-PART DELAY
Set the BI-PART DELAY to desired
setting. The range is 0 to 8 seconds,
0 seconds is OFF.
NOTE: Used for Dual Gate installations
only.
BI-PART
DELAY
FORCE
Minimun
Force
MAX
Maximum
Force
OFF
MAX
Your basic installation is now complete.
26
OFF
MAX
TIMER TO CLOSE ENABLE
Set the TIMER TO CLOSE to desired
setting. The range is 0 to 180
seconds, 0 seconds is OFF.
TIMER TO
CLOSE
OFF
MAX
OPTIONAL CONTROL AND SAFETY DEVICES
To Add or Reprogram a Remote Control
1. Press and release “LEARN XMITTER” button (LED will light up).
2. Press and hold remote button, the LED will flash, alarm will beep twice and the LED will go out.
3. Repeat steps 1 and 2 until all remote controls are programmed (50 remote controls maximum).
NOTE: For highest level of security, we recommend the 315 MHz, Security✚® line of products. Refer to Accessories.
R1
LEARN
XMITTER
Remote Control
“LEARN XMITTER” Button
P2
CLOSE
EDGE
J19
J1
Ø14GP
14GPØ89
89ØE
Ø14LG
14LGØ89
89ØE
Ø14SK
14SKØ89
89ØE
OPEN/EGE
PHOTO
L1
OFF
OFF
SINGLE
NO
NO
1 2 3 4 5
S8
LEARN
XMITTER
2
O
N
1
ON SAVE
ON MAGLOCK
DUAL MODE
NC
EDGE
NC
PHOTO
OPEN
PHOTO
S1
CLOSE
PHOTO
24V
OVLD
To Erase All Codes
To deactivate any unwanted remote controls, first
erase all codes:
Press and hold the “LEARN XMITTER” button on
logic board until the learn indicator light goes out
(approximately 6 seconds). All previous codes are
now erased. Reprogram each remote control or
keyless entry you wish to use.
SWITCHED
ACCESSORY
POWER
NOTICE: To comply with FCC and or Industry Canada (IC) rules, adjustment or modifications of this
receiver and/or transmitter are prohibited, except for changing the code setting or replacing the
battery. THERE ARE NO OTHER USER SERVICEABLE PARTS.
Tested to Comply with FCC Standards FOR HOME OR OFFICE USE. Operation is subject to the
following two conditions: (1) this device may not cause harmful interference, and (2) this device
must accept any interference received, including interference that may cause undesired operation.
27
Dip Switch Settings
SAVE SWITCH S1-1
This switch (S1-1) is used to save the settings for switches 2 through 5.
NOTE: When setting switches, the save switch must be in the off position prior to setting or changing switches for the
change to be saved.
MAG DELAY ENABLE
This switch (S1-2) enables the Maglock feature. On an open command there will be a .5 second delay before the motor
starts, to allow the Maglock to release.
MODE DUAL/SINGLE
This switch (S1-3) sets the mode as Dual or Single (Refer to page 24).
SAFETY INPUTS
Swing gates allow four safety inputs. A DIP switch is required for determining between N/O and N/C edges and N/O and
N/C eyes.
EDGE INPUT
Set switch (S1-4) to the following settings:
N/O Edge (Active Close) = N/O dry contact edge or monitored edge
NOTE: Monitored Edges should be set in the N/O position, as the activation condition is shorting the terminals.
EYE INPUT
This switch (S1-5) differentiates between N/O and N/C dry contact photoelectric eye inputs.
NOTE: Pulsing Chamberlain (CPS-L) photoelectric eyes will automatically learn in N/O mode (See Accessories).
O
N
O
N
OFF
OFF
SINGLE
NO
NO
O
N
S1
1 2 3 4 5
1 2 3 4 5
OFF
MAG DELAY
ON
1 2 3 4 5
SAVE
MAGLOCK
MODE
EDGE
PHOTO
O
N
1 2 3 4 5
ON
ON
DUAL
NC
NC
1 2 3 4 5
O
N
OFF
OFF
SINGLE
NO
NO
O
N
SAVE
OFF
SAVE
ON
ON
MAG DELAY
OFF
FACTORY DEFAULT SHOWN
J1
OFF
OFF
SINGLE
NO
NO
1 2 3 4 5
S8
LEARN
XMITTER
2
O
N
1
ON SAVE
ON MAGLOCK
DUAL MODE
NC
EDGE
NC
PHOTO
OPEN
PHOTO
S1
CLOSE
PHOTO
GATE1
SET
OPEN
LIMIT
SET
CLOSE
LIMIT
LEARN
LIMITS
GATE 2
1 2 3 4 5
OPEN/EGE
PHOTO
O
N
CLOSE
EDGE
Ø14GPØ89ØE
Ø14LGØ89ØE
Ø14SKØ89ØE
L1
1 2 3 4 5
P2
J19
24V
OVLD
SWITCHED
ACCESSORY
POWER
O
N
OFF
OFF
SINGLE
O
N
28
1 2 3 4 5
EYE NO
1 2 3 4 5
OFF
OFF
SINGLE
EDGE NO
ON
ON
DUAL
NC
ON
ON
DUAL
NC
ON
ON
DUAL
NC
NC
Wire Stop Button (Optional)
A jumper wire is factory installed between the stop and common input.
Stop (N/C) - Stop only (does not reset alarm).
NOTE: Stop jumper is required for normal operation (the Stop LED will be lit except when the control board goes into
Sleep Mode). Remove only if remotely mounted Stop button is added.
CONTROL
INPUTS
OPEN
SINGLE BUTTON
P2
RESET
J19
J1
Ø14GPØ89ØE
Ø14LGØ89ØE
Ø14SKØ89ØE
STOP
NO
L1
C
S8
OFF
OFF
SINGLE
NO
NO
LEARN
XMITTER
2
1 2 3 4 5
1
O
N
NC
ON
ON
DUAL
NC
NC
SAVE
MAGLOCK
MODE
EDGE
PHOTO
COM
S1
BRN
COM
GRN
WHT
R223
P1
YEL
CLOSE
EDGE
J19
R2Ø7
BLU
NO
POWER
Z2Ø
R227
C
Z1
RED
K5
OPEN EDGE/
PHOTO
GATE 1
L1
R224
GRN
24V
Z22
R92
U4
R2
Z9
LEARN
XMITTER
R1
OPEN
PHOTO
10A 32V
OVLD
2
ACCESSORY
POWER
R91
F3
D1Ø
CONTROL
INPUTS
K2
DIAGNOSTIC
24V
BLU
OPEN
GRN
SINGLE BUTTON
GATE 1
BRN
Z12
K1 Q9
SET
OPEN
LIMIT
SET
CLOSE
LIMIT
RESET
LEARN
LIMITS
WHT
R9Ø
GATE 2
YEL
BLU
RED
COM
CONTROL
INPUTS
TIMER TO SINGLE
BUTTON
CLOSE
FORCE
R1Ø1
STOP
TIMER
RUNNING
COM
OPEN
POWER
R1ØØ
SINGLE BUTTON
F4
GATE 2
RESET
ACCESSORY
OVLD
10A 32V
STOP
K4
OFF
MAX
COM
F5
COM
D21
POWER
R35
D9
K3
D8
C12
D27 Z3
F7
Z4
Q22
C13
D22
LOOP
INPUTS
C4
SHADOW
U3
INTERRUPT
C11
CHGR
OVLD
POWER
D15
C2
R196
COM
F6
24 VAC/
SOLAR
INPUT
SWITCHED
ACCESSORY
POWER
F2
MOV2
R9
MOV1
F1 20A 32V
D4
D1
C64
JMPR2
JMPR1
D2
U2
FUSE
OPEN
BATT 2
BATT 1
D6
DB1
29
OPEN
Opens only or reverses a closing gate.
SBC (SINGLE BUTTON CONTROL) INPUT
This input will command the gate to OPEN / STOP / CLOSE / STOP in sequence.
RESET CONTROL INPUT
The control box has a factory installed internal reset button. These terminals are intended for use with a single reset
button that is installed within line of sight of the gate. This input functions to reset the alarms. This input will NOT stop
the gate.
NOTE: All Control Inputs must be Normally Open (N.O.) dry contact type.
CONTROL
INPUTS
OPEN
OPEN
COMMON
SINGLE BUTTON
RESET
AND/OR
STOP
COM
COM
POWER
SINGLE
BUTTON
P2
J19
J1
Ø14GPØ89ØE
Ø14LGØ89ØE
Ø14SKØ89ØE
NO
L1
COMMON
C
S8
OFF
OFF
SINGLE
NO
NO
LEARN
XMITTER
2
1 2 3 4 5
1
O
N
NC
ON SAVE
ON MAGLOCK
DUAL MODE
NC
EDGE
PHOTO
NC
S1
BRN
AND/OR
GRN
WHT
R223
P1
YEL
CLOSE
EDGE
J19
R2Ø7
BLU
NO
Z2Ø
R227
C
Z1
RED
K5
OPEN EDGE/
PHOTO
GATE 1
L1
R224
GRN
24V
Z22
R92
U4
R2
Z9
LEARN
XMITTER
R1
OPEN
PHOTO
10A 32V
2
ACCESSORY
POWER
R91
F3
D1Ø
CONTROL
INPUTS
K2
DIAGNOSTIC
24V
BLU
GRN
OPEN
Z12
SINGLE BUTTON
GATE 1
BRN
SET
K1 Q9
OPEN
LIMIT
SET
CLOSE
LIMIT
RESET
LEARN
LIMITS
COMMON
WHT
R9Ø
GATE 2
YEL
BLU
RED
STOP
TIMER
RUNNING
COM
CONTROL
INPUTS
TIMER TO SINGLE
BUTTON
CLOSE
FORCE
R1Ø1
COM
OPEN
POWER
R1ØØ
SINGLE BUTTON
F4
GATE 2
RESET
ACCESSORY
OVLD
10A 32V
STOP
K4
OFF
MAX
COM
F5
RESET
COM
D21
POWER
R35
D9
K3
D8
C12
D27 Z3
F7
Z4
Q22
C13
D22
LOOP
INPUTS
C4
SHADOW
U3
INTERRUPT
C11
CHGR
OVLD
POWER
D15
C2
R196
COM
F6
24 VAC/
SOLAR
INPUT
F2
MOV2
R9
MOV1
D4
D1
C64
JMPR2
JMPR1
D2
U2
FUSE
OPEN
BATT 2
BATT 1
D6
DB1
F1 20A 32V
OPEN INPUT AND EXIT LOOP
These terminals are intended for use as a general open control. Accessories such as
telephone entry systems, radio receivers (open only applications), exit loop detectors,
keypads and 7-day timers may be wired to this input.
PR
ESE
NC
RE E
LAY
2
SE
NS
FRE
EQQ
EXIT LOOP
30
A
DE
MA
IN
US
Loop Inputs
Shadow Loop Input Terminal and Common
This input protects cars by preventing the gate from moving off of the open or close limit when the shadow loop input
is active.
NOTE: Shadow Loop is disabled when gate is moving.
Interrupt Loop Input Terminal and Common
This input functions to reverse a closing gate to the open limit. Latching this input will reset the timer to close.
LOOP
INPUTS
NORMALLY OPEN
SHADOW LOOP
SHADOW
NORMALLY OPEN
INTERRUPT LOOP
INTERRUPT
COMMON LOOP
COM
CHGR
OVLD
F1 20A 32V
FUSE
OPEN
BATT 2
BATT 1
P2
J19
Ø14GPØ89ØE
Ø14LGØ89ØE
Ø14SKØ89ØE
J1
PR
ESE
NC
RE E
LAY
2
NO
L1
C
S8
OFF
OFF
SINGLE
NO
NO
LEARN
XMITTER
2
1 2 3 4 5
1
O
N
NC
ON SAVE
ON MAGLOCK
DUAL MODE
NC
EDGE
NC
PHOTO
SE
NS
S1
BRN
GRN
WHT
R223
P1
YEL
CLOSE
EDGE
J19
FRRE
R2Ø7
BLU
NO
EQQ
Z2Ø
R227
C
Z1
RED
K5
OPEN EDGE/
PHOTO
GATE 1
R224
GRN
DE
IN
US
Z9
LEARN
XMITTER
R1
MA
24V
Z22
R92
U4
R2
OPEN
PHOTO
10A 32V
2
ACCESSORY
POWER
R91
F3
D1Ø
CONTROL
INPUTS
K2
DIAGNOSTIC
24V
BLU
A
L1
OPEN
GRN
Z12
SINGLE BUTTON
GATE 1
BRN
K1 Q9
SET
OPEN
LIMIT
SET
CLOSE
LIMIT
RESET
LEARN
LIMITS
WHT
R9Ø
GATE 2
YEL
BLU
R1Ø1
RED
R1ØØ
STOP
TIMER
RUNNING
COM
CONTROL
INPUTS
TIMER TO SINGLE
BUTTON
CLOSE
FORCE
COM
OPEN
POWER
SINGLE BUTTON
F4
GATE 2
NOTE: Additional enclosure required. Refer to
loop detector manufacturer instructions for
connections.
RESET
ACCESSORY
OVLD
10A 32V
LOOP
INPUTS
STOP
K4
OFF
MAX
COM
F5
COM
D21
POWER
R35
D9
K3
D8
C12
D27 Z3
F7
Z4
Q22
C13
D22
LOOP
INPUTS
C4
COM
SHADOW
U3
INTERRUPT
C11
CHGR
OVLD
POWER
D15
C2
R196
COM
F6
24 VAC/
SOLAR
INPUT
F2
MOV2
R9
MOV1
F1 20A 32V
D4
D1
C64
JMPR2
JMPR1
D2
U2
FUSE
OPEN
BATT 2
BATT 1
D6
DB1
31
Photo/Edge Inputs (P6-7-8 and 9)
Terminal P6 – Close Safety Edge
This input will reverse a closing gate. It will disable the Timer-to-Close if that feature has been enabled. Activating this
input while the gate is opening will have no effect.
Order part number LA400-BOX to enclose safety electronics.
Terminal P8 – Open Safety Edge/Photo Eye (Entrapment)
If an Open Edge device or a Retro-Reflective Photo Eye has been connected to Terminal P8, then this input will reverse
an opening gate for 2 seconds then stop. Activating this input with an Open Edge device or a Retro-Reflective Photo
Eye connected to Terminal P8 while the gate is closing will have no effect.
If a Chamberlain Pulsing Photo Eye (See Accessories) has been connected to Terminal P8, then this input will pause an
opening gate until the obstruction has been removed. Upon removing the obstruction, the gate will continue to open.
Activating this input with a Chamberlain Pulsing Photo Eye (See Accessories) connected to Terminal P8 while the gate
is closing will have no effect.
Terminal P7 – Open Safety Photo Eye (Entrapment)
This input will pause an opening gate until the obstruction has been removed. Upon removing the obstruction, the gate
will continue to open. Activating this input while the gate is closing will have no effect.
Terminal P9 – Close Safety Photo Eye
This input will reverse a closing gate to the open limit. Activating this input while the gate is opening will have no effect.
The Timer-to-Close will reactivate at the open limit.
CLOSE
EDGE
P2
CLOSE
EDGE
J19
J1
Ø14GPØ89ØE
Ø14LGØ89ØE
Ø14SKØ89ØE
OPEN EDGE
PHOTO
OPEN EDGE/
PHOTO
NO
L1
C
S8
OFF
OFF
SINGLE
NO
NO
LEARN
XMITTER
2
1 2 3 4 5
1
O
N
NC
ON SAVE
ON MAGLOCK
DUAL MODE
NC
EDGE
NC
PHOTO
OPEN
PHOTO
S1
GRN
WHT
CLOSE
PHOTO
R223
W
UE N
CLOSE
EDGE
J19
R2Ø7
BLU
Z2Ø
R227
C
Z1
RED
K5
OPEN EDGE/
PHOTO
GATE 1
UE
L1
24V
R224
GRN
Z22
R92
U4
R2
Z9
LEARN
XMITTER
R1
OPEN
PHOTO
10A 32V
OVLD
2
ACCESSORY
POWER
R91
F3
D1Ø
DIAGNOSTIC
OPEN
GRN
SINGLE BUTTON
GATE 1
BRN
Z12
SWITCHED
ACCESSORY
POWER
CONTROL
INPUTS
K2
24V
BLU
BL
P1
YEL
NO
K1 Q9
SET
OPEN
LIMIT
SET
CLOSE
LIMIT
RESET
LEARN
LIMITS
WHT
R9Ø
GATE 2
YEL
BLU
RED
STOP
TIMER
RUNNING
COM
CONTROL
INPUTS
TIMER TO SINGLE
BUTTON
CLOSE
FORCE
R1Ø1
COM
OPEN
POWER
R1ØØ
SINGLE BUTTON
F4
GATE 2
RESET
ACCESSORY
OVLD
10A 32V
LOOP
INPUTS
STOP
K4
OFF
MAX
COM
F5
COM
D21
POWER
R35
D8
C12
D27 Z3
F7
Z4
Q22
C13
D22
LOOP
INPUTS
C4
COM
SHADOW
U3
R196
BROWN
INTERRUPT
C11
CHGR
OVLD
POWER
D15
C2
OPEN
PHOTO
D9
K3
COM
F6
24 VAC/
SOLAR
INPUT
F2
MOV2
R9
MOV1
F1 20A 32V
D4
D1
C64
JMPR2
JMPR1
D2
U2
FUSE
OPEN
BATT 2
BLUE
BATT 1
D6
DB1
BLUE
BROWN
CLOSE
PHOTO
BROWN
BLUE
BLUE
BROWN
32
O
BR
O
BR
BL
BRN
WN
Safety Accessories for Secondary Entrapment Protection
The following devices are acceptable for Safety Accessories for secondary entrapment protection. These devices have
been tested with the LA400 to meet the requirements of UL325 and UL991.
PHOTO-ELECTRIC CONTROLS
MODEL
DESCRIPTION
VOLTAGE
CPS-LN4
Emitter, receiver and mounting brackets - 30' (9 m) Ranges
+24Vdc
CPS-RN4
Emitter with reflector and mounting brackets
+24Vdc
SENSING EDGES
MODEL
DESCRIPTION
G65MG0204
Miller MG020 2-wire electric edge for gates. Sensitized on three sides. (Requires mounting channel.
PIN:G65ME120C5)
G65MG0205
Miller MG020 2-wire electric edge for gates. Sensitized on three sides. (Requires mounting channel.
PIN:G65ME120C5)
G65MGR205
Miller MGR20 2-wire electric edge in 5' (1.5 m) lengths for 2" (5 cm) round post.
G65MGS205
Miller MGR20 2-wire electric edge in 5' (1.5 m) lengths for 2" (5 cm) square post.
Maglock
When enabled, the maglock output is activated (energized) while the gate
is in motion.
Fault Alarm
P2
R223
P1
CLOSE
EDGE
J19
Ø14GPØ89ØE
Ø14LGØ89ØE
Ø14SKØ89ØE
K6
ALARM
J1
NO
R2Ø7
Z2Ø
R227
C
K5
MAGLOCK
*
OPEN EDGE/
PHOTO
NO
Solenoid Lock
(optional)
L1
J18
R224
C
S8
LEARN
XMITTER
10A 32V
2
GATE 1
1 2 3 4 5
OFF
OFF
SINGLE
NO
NO
R2
R1
O
N
1
NC
Z1
ON
ON
DUAL
NC
NC
Z22
R92
U4
SAVE
MAGLOCK
MODE
EDGE
PHOTO
Z9
OPEN
PHOTO
S1
F3
R91
BRN
D1Ø
GRN
*
R94
K2
Z8
WHT
Maglock
(optional)
CLOSE
PHOTO
DIAGNOSTIC
YEL
R93
BLU
GATE 1
RED
K1 Q9
Z12
SET
OPEN
LIMIT
SET
CLOSE
LIMIT
R9Ø
ACCESSORY
POWER
GATE 2
24V
BRN
TIMER
RUNNING
COM OVLD
OVLD
SWITCHED
ACCESSORY
POWER
CONTROL
INPUTS
TIMER TO SINGLE
BUTTON
CLOSE
R1ØØ
OPEN
SINGLE BUTTON
F4
GRN
RESET
ACCESSORY
OVLD
10A 32V
WHT
power supply or 300MA with 24Vac power supply.
Accessory
Power
24V
BIPART
DELAY
FORCE
R1Ø1
* Provides 24VDC. Do not exceed 500MA with 115Vac
LEARN
LIMITS
STOP
K4
YEL
MIN
MAX
OFF
MAX
OFF
MAX
COM
F5
BLU
COM
D21
RED
D9
D8
GATE 2
POWER
R35
K3
C12
D27 Z3
F7
Z4
Q22
C13
D22
LOOP
INPUTS
C4
SHADOW
U3
INTERRUPT
C11
C2
R196
F6
24 VAC/
SOLAR
INPUT
J4
COM
CHGR
OVLD
D15
R4
F2
MOV2
R9
MOV1
D4
D1
C64
JMPR1
JMPR2
D2
U2
FUSE
OPEN
BATT 2
BATT 1
D6
DB1
F1 20A 32V
Auxiliary Output Power for Optional Devices
(2) +24Vdc Outputs have been provided for optional devices
33
OPERATION
Reset Button
The reset button is located on the outside of the control box and serves several functions.
Obstruction/Entrapment Reset
If gate encounters two consecutive obstructions, the control system will go into an entrapment alarm condition and the
control board will require resetting. This is achieved by simply pushing the “Reset Button” located on the outside of the
control box.
Party Mode (Timer Defeat - Hold Open)
Reset
Control Box
RESET
When the “Timer to Close” feature is activated for normal daily operation and
Button
you wish to leave the gate(s) in the open postion for any extended period of
time you can activate the “Party Mode” by pushing the “Reset Button” located
on the outside of the electrical box. To exit this mode, simply give the gate(s)
a command to run by using the remote control. This will close the gate(s) and
return the operator to normal operation.
RESET
Remote Control
Once the remote control has been programmed unit will operate as follows:
When gate is in the closed position, activation of the remote control button will open the gate. During the open cycle
another activation of the remote control will stop the gate and the next activation of the remote control will close the gate.
When the gate is in the open position, activation of the remote control
button will close the gate. During the close cycle another activation of the
remote control will stop the gate and the next activation of the remote
control will open the gate.
Manual Release
The drive mechanism can be released. The gate can then be operated manually (power failure). With a new drive
mechanism, the release action may sometimes feel stiff/jerky. This is normal and has no effect on function.
Release
1. Insert the key into the lock.
2. Turn the key counter-clockwise 180°.
3. Turn the release lever counter-clockwise 180°.
4. Done! Operator is in manual mode.
Engage
1. Turn the release lever clockwise 180°. This engages the motor.
2. Turn the key clockwise 180°. This locks the release lever.
3. Remove the key and store in a safe place.
4. Done! Back in automatic mode.
34
MAINTENANCE
NING
WARNING
IMPORTANT SAFETY INSTRUCTIONS
ION
SSEMENT
WARNING
To reduce the risk of SEVERE INJURY or DEATH:
1. READ AND FOLLOW ALL INSTRUCTIONS.
2. NEVER let children operate or play with gate controls.
Keep the remote control away from children.
3. ALWAYS keep people and objects away from the gate.
NO ONE SHOULD CROSS THE PATH OF THE MOVING
GATE.
4. Test the gate operator monthly. The gate MUST
reverse on contact with a rigid object or stop when an
object activates the non-contact sensors. After
adjusting the force or the limit of travel, retest the
gate operator. Failure to adjust and retest the gate
operator properly can increase the risk of INJURY or
DEATH.
AVERTISSEMENT
10. SAVE THESE INSTRUCTIONS.
AVERTISSEMENT
TION
UCIÓN
CHECK AT LEAST ONCE EVERY
DESCRIPTION
TASK
MONTH
External entrapment
protection systems
Check for proper operation
●
Gate warning signs
Make sure they are present
Manual disconnect
Check and operate
Gate
Inspect for wear or damage
●
●
Accessories
Check all for proper operation
●
Electrical
Inspect all wire connections
●
Frame bolts
Check for tightness
●
Total unit
Inspect for wear or damage
3 MONTHS
6 MONTHS
12 MONTHS
●
ADVERTENCIA
Complete Check Out
TENCIA
5. Use the emergency release ONLY when the gate is
not moving.
6. KEEP GATES PROPERLY MAINTAINED. Read the
owner’s manual. Have a qualified service person
make repairs to gate hardware.
7. The entrance is for vehicles ONLY. Pedestrians MUST
use separate entrance.
8. Disconnect ALL power BEFORE performing ANY
maintenance.
9. ALL maintenance MUST be performed by a
LiftMaster professional.
WARNING
●
CAUTION
ADVERTENCIA
To reduce the risk of FIRE or INJURY to persons, use ONLY
LiftMaster part #K74-30762 for replacement batteries.
NOTES:
1. Disconnect power before servicing.
2. Severe or high cycle usage will require more frequent maintenance checks.
3. Inspection and service should always be performed anytime a malfunction is observed or suspected.
4. When servicing, please do some “house cleaning” of the operator and the area around the operator. Pick up any debris
in the area. Clean the operator as needed.
5. It is suggested that while at the site voltage readings be taken at the operator. Using a Digital Voltmeter, verify that the
incoming voltage to the operator it is within ten percent of the operators rating.
AVERTISSEMENT
35
ATTENTION
WARNING
WARNING
CAUTION
WARNING
To avoid SERIOUS personal INJURY or DEATH from
electrocution, DISCONNECT electrical power to operator
BEFORE proceeding.
To reduce the risk of FIRE or INJURY to persons, use ONLY
LiftMaster part #K74-30762 for replacement batteries.
Battery Replacement
1. Disconnect power to operator.
2. Open the control box cover.
3. Remove all quick connect terminals in use to the control board. Remember location of all wire connections for
reinstallation.
4. Remove control board and mounting plate.
5. Disconnect terminals leads to both batteries.
6. Replace both batteries and connect red wires to the positive (+) terminals (red). Connect black wires to the
negative (-) terminals (black).
7. Install control board and mounting plate.
8. Reconnect all quick connect terminals to the control board.
9. Close cover of control box.
10. Reconnect power to operator.
AVERTISSEMENT
AVERTISSEMENT
AVERTISSEMENT
ATTENTION
ADVERTENCIA
ADVERTENCIA
Batteries
Control Board and
Mounting Plate
ADVERTENCIA
PRECAUCIÓN
36
BASIC CONTROL BOARD LAYOUT
19
20
26
17
1
P2
R223
P1
CLOSE
EDGE
J19
Ø14GPØ89ØE
Ø14LGØ89ØE
Ø14SKØ89ØE
K6
ALARM
14
J1
NO
Z2Ø
R227
C
K5
MAGLOCK
13
OPEN EDGE/
PHOTO
NO
L1
J18
S8
OFF
OFF
SINGLE
NO
NO
LEARN
XMITTER
R1
10A 32V
2
GATE 1
1 2 3 4 5
Z1
O
N
1
R2
ON
ON
DUAL
NC
NC
Z22
R92
U4
SAVE
MAGLOCK
MODE
EDGE
PHOTO
Z9
OPEN
PHOTO
S1
F3
3
R224
C
NC
18
2
R2Ø7
4
R91
BRN
D1Ø
GRN
R94
K2
Z8
WHT
12
CLOSE
PHOTO
DIAGNOSTIC
YEL
5
R93
BLU
GATE 1
RED
K1 Q9
Z12
SET
OPEN
LIMIT
SET
CLOSE
LIMIT
R9Ø
ACCESSORY
POWER
11*
TIMER
RUNNING
BRN
BIPART
DELAY
FORCE
R1Ø1
6*
24V
GATE 2
24V
COM OVLD
OVLD
SWITCHED
ACCESSORY
POWER
CONTROL
INPUTS
TIMER TO SINGLE
BUTTON
CLOSE
R1ØØ
OPEN
WHT
7
RESET
ACCESSORY
OVLD
10A 32V
22
SINGLE BUTTON
F4
GRN
10
LEARN
LIMITS
STOP
K4
YEL
MIN
MAX
OFF
MAX
OFF
MAX
COM
F5
BLU
COM
D21
RED
D9
D8
GATE 2
POWER
R35
K3
C12
D27 Z3
F7
Z4
Q22
C13
D22
LOOP
INPUTS
C4
SHADOW
U3
R4
21
F6
24 VAC/
SOLAR
INPUT
J4
F2
MOV2
R9
MOV1
D1
C64
JMPR2
JMPR1
BATT 2
BATT 1
D6
DESCRIPTION
Connector P1
Connector P6
Connector P8
Connector P7
Connector P9
Connector P12
Connector P10
Connector P11
Connector P5
Connector P16
Connector P13
Connector P17
Connector P14
FUSE
OPEN
D2
U2
9
F1 20A 32V
D4
DB1
ITEM
1
2
3
4
5
6
7
8
9
10
11
12
13
COM
CHGR
OVLD
R196
C2
8
INTERRUPT
C11
D15
23
FUNCTION
Antenna Input
Close Edge
Open Edge/Photo
Open Photo
Close Photo
Switched Accessory Power*
Control Inputs
Loop Inputs
24Vac/Solar Input
Gate 2
Accessory Power*
Gate 1
Maglock/Solenoid
24
ITEM
14
15
16
17
18
19
20
21
22
23
24
25
26
*See page 40 for max current draw
37
25
DESCRIPTION
Connector P15
Connector
Connector
Dip Switch
Pushbutton
Pushbuttons
Pushbutton
Pushbuttons
Pushbutton
Potentiometer
Potentiometer
Potentiometer
Connector
16 15
FUNCTION
Alarm
Battery 1
Battery 2
S1
Learn Xmitter - Program Remote
Gate 1 - Jog Learn Limit
Learn Limits
Gate 2 - Jog Learn Limit
Single Button
Force
Bi-Part Delay
Timer to Close
Receiver
WIRING DIAGRAM
1. ANTENNA INPUT
2. CLOSE EDGE
3. OPEN EDGE/PHOTO EYE
4. OPEN PHOTO EYE
5. CLOSE PHOTO EYE
6. 24VDC ACCESSORY OUTPUT
7. CONTROL INPUTS/EXIT LOOP
8. LOOP INPUTS, SAFETY/SHADOW
9. TRANSFORMER INPUT/SOLAR INPUT (OPTIONAL)
10. SECOND - OPERATOR ARM CONNECTION
11. 24VDC ACCESSORY OUTPUT
12. MASTER OPERATOR ARM CONNECTION
Fault Alarm
ANTENNA
CONNECTION
1
Solenoid Lock
(optional)
P2
R223
P1
14
J1
K5
MAGLOCK
17
NO
J18
LEARN
XMITTER
10A 32V
2
GATE 1
SET
CLOSE
LIMIT
SET
OPEN
LIMIT
R9ÿ
BRN
R1ÿÿ
GRN
F4
21
YEL
FORCE
24
BIPART
DELAY
COM OVLD
OVLD
CONTROL
INPUTS
TIMER TO SINGLE
BUTTON
CLOSE
OPEN (EXIT LOOP)
OPEN
SINGLE BUTTON
RESET
STOP
RESET
MAX
OFF
MAX
OFF
MAX
25
STOP
COMMON (+24VDC)
COMMON (+24VDC)
COM
COM
D21
RED
C12
D27 Z3
F7
Z4
Q22
7
D9
D8
GATE 2
10
POWER
R35
K3
C13
D22
LOOP
INPUTS
C4
SHADOW
SHADOW LOOP
U3
F2
MOV2
R9
MOV1
JMPR2
JMPR1
D2
U2
GROUND
BLACK
BLUE
9
YELLOW
NOTE: Yellow/green wire must
be disconnected when earth
ground rod is installed.
BATT 2
8
BATT 1
D6
DB1
FUSE
OPEN
16
15
RED
YELLOW/GREEN
F1 20A 32V
D4
D1
C64
BLACK
24 VAC/
SOLAR
INPUT
J4
F6
RED
(OR OPTIONAL EARTH GROUND WIRE)
COMMON (+24VDC)
COM
CHGR
OVLD
R196
C2
INTERRUPT LOOP
INTERRUPT
C11
D15
R4
PHOTO
SWITCHED
ACCESSORY
POWER
SINGLE BUTTON
MIN
OR
24VDC OUTPUT
SWITCHED OFF
IN LOW POWER MODE
F5
BLU
RED
CPS-LN4
6
24V
22
TIMER
RUNNING
23
K4
PHOTO
5
PHOTO
20
ACCESSORY
OVLD
10A 32V
WHT
OR
OR
LEARN
LIMITS
GATE 2
R1ÿ 1
YE L
B LU
GATE 2
CLOSE
PHOTO
GATE 1
K1 Q9
24V
W HT
PHOTO
R93
ACCESSORY
POWER
GRN
CPS-LN4
4
OR
19
BLU
BRN
Z9
OPEN
PHOTO
Z8
DIAGNOSTIC
Z12
EDGE
EDGE
Z22
R92
U4
R91
RED
12
11
SAVE
MAGLOCK
MODE
EDGE
PHOTO
OR
R94
YEL
RED
ON
ON
DUAL
NC
NC
18
K2
WHT
YE L
GATE 1
D1ÿ
GRN
B LU
CPS-LN4
OR
R224
S1
F3
BRN
GRN
1 2 3 4 5
OFF
OFF
SINGLE
NO
NO
S8
R2
R1
O
N
1
NC
Z1
EDGE
3
OPEN EDGE/
PHOTO
L1
C
W HT
EDGE
Z2ÿ
R227
C
Maglock
(optional)
BRN
OR
R2ÿ 7
NO
13
2
CLOSE
EDGE
J19
K6
ALARM
13. MAGLOCK/SOLENOID OUTPUT
14. FAULT ALARM OUTPUT
15. BATTERY INPUT #1
16. BATTERY INPUT #2
17. DIP SWITCH, S1
18. LEARN XMITTER
19. MASTER GATE JOG
20. LIMIT SET
21. SECOND GATE JOG
22. SBC (SINGLE BUTTON CONTROL)
23. FORCE SET
24. BIPART DELAY SET
25. TIMER TO CLOSE SET
NOTE: Batteries must be connected
to operate.
OR
To protect against fire and electrocution:
• DISCONNECT power and battery BEFORE
installing or servicing operator.
• Replace ONLY with fuse of same type and rating.
38
TROUBLESHOOTING
FAULT
POSSIBLE CAUSE
FIX
OPERATOR IS DEAD
No LED lights are on.
1) No voltage to board.
2) Bad control board.
➤ Battery must be >23V, AC or Solar needs to be connected.
➤ Replace control board.
OPERATOR DOES NOT
RUN
Unit does not respond to
any commands.
1)
2)
3)
4)
Low/disconnected battery.
Remote not programmed.
STOP connection loose/disconnected.
Constant Open Command
(Check LED’s).
5) Limits not programmed correctly.
6) Bad control board.
➤ Voltage must be >23V at battery connection.
➤ See Programming Remote instructions.
➤ Check STOP connections.
➤ Clear all Open/Safety devices from obstruction.
MOTOR DOES NOT RUN
Relays “click” when radio
or SBC signal is given, but
the operator does not
move.
1) Low Battery.
2) Cable wiring between control box and
operator arm disconnected or loose.
3) Batteries not connected.
4) Bad motor.
5) Bad control board.
➤ Voltage must be >23V at battery connection.
➤ Check wiring on control board to arm, replace wire if needed.
GATE STOPS AND
REVERSES
(Force Reversal)
1)
2)
3)
4)
➤ Clear gate from obstruction.
➤ See Force Adjustment section.
➤ Service/replace gate hardware.
➤ See Installation section of operator arm.
RPM REVERSAL
1) Obstructed Arm (bottoms out).
2) Bad RPM Sensor.
3) Too much mA pulled off board.
➤ Check for obstruction on arm, verify arm is not bottomed out.
➤ Replace arm.
➤ Move accessories to separate power source. Use reference chart on
next page to determine max mA draw for circuit board.
GATE STOPS
Gate starts to run, then
stops and does not
reverse.
1) Low battery.
2) Gate met an obstruction.
➤ Voltage must be >23V at battery connection.
➤ Clear gate from obstruction.
GATE OPENS BUT DOES
NOT CLOSE
1) Constant Open Command
(Check LED’s).
2) Timer to Close not set.
3) Accessory device wired to Open Only
command.
➤ Clear all Open/Safety devices from obstruction.
Audible beeps (3 times)
when command is given.
1) Battery Low >23.5V
➤ Operator will resume normal operation once battery voltage
reaches 24V.
GATE’S DO NOT
OPEN/CLOSE IN SYNC
1) Bi-Part Delay not set.
2) Limits not programmed correctly.
3) Incorrect Arm Installation
➤ See Bi-Part Delay section for adjustment instructions.
➤ See Programming Limits section for instructions.
➤ See Installation section for instructions.
GATE DOES NOT
AUTOMATICALLY CLOSE
Auto Close Timer not
closing gate.
1) Timer to Close not turned on.
2) Gate has opened on Obstruction
Reversal.
3) Operator in “Party Mode”.
4) Constant Open Command
(Check LED’s).
➤ See Timer to Close section for instructions.
➤ Check DIAG code, clear obstruction.
ACCESSORY DEVICE NOT
WORKING PROPERLY
1)
2)
3)
4)
➤ Check for proper installation of accessory.
➤ Turn applicable switches on.
➤ Check proper installation of wires.
➤ Replace accessory device.
Gate met an obstruction.
Force set too low.
Bad gate hardware.
Incorrect Arm installation.
Not installed properly.
Enabling Switch not turned on.
Loose/disconnected wires.
Bad accessory device
➤ See Programming Limits instructions.
➤ Replace control board.
➤ Connect batteries.
➤ Replace motor.
➤ Replace control board.
➤ See Timer to Close section for adjustment instructions.
➤ Rewire desired accessory device to Single Button Input.
➤ Use Remote/SBC to resume normal operation.
➤ Clear all Open/Safety devices from obstruction.
39
MAX CURRENT DRAW
115 power to control box - 500mA accessory power, 150mA switched
accessory power.
24V power to control box depending on wire gauge and distance - 300mA
accessory power, 75mA switched accessory power.
Solar power to control box - 0mA accessory, 50mA switched accessory
power.
DIAGNOSTIC CODES
# OF BLINKS
1
2
3
4
5
6
7
8
9
10
MEANING
No Stop Switch Connected
Gate 1 Arm Disengaged
Gate 2 Arm Disengaged
Both Gate Arms Disengaged
RPM Reversal
Force Reversal
Processor Reset
ROM Check Failed
RAM Check Failed
EEPROM Check Failed - Reset Limits
40
REPAIR PARTS
Refer to the parts lists below for replacement parts available for your operator. If optional modifications and/or
accessories are included with your operator, certain components may be added or removed from these lists.
CONTROL BOX LA400-CONT
ITEM
1
2
3
4
5
6
7
8
Not Shown
PART #
K001A6039
K75-15480
DESCRIPTION
QTY
Control Board
1
Control Box & Cover
with Gasket
1
Control Board Bracket
1
Reset Switch
1
Antenna
1
Battery
2
Transformer
1
Alarm
1
ATC Fuse Kit Includes
20 Amp (1), 15 Amp (2)
390 MHz Receiver Module
315 MHz Receiver Module
K75-30764
K23-19380
K74-19499
K74-30762
K74-30763
K76-19446
K74-30941
K001A5747-2
K001A5747
8
2
7
3
4
6
1
5
41
ACTUATOR ARM KITS
ITEM
1
2
3
4
Not Shown
PART #
DESCRIPTION
41ASWG-442SA
41ASWG-438SA
41ASWG-0014SA
41ASWG-489
41ASWG-0119
K77-19130
Release Lever
Motor with Limit Switch Harness
Rear Connector
Cable 24V with Connector
Release Key
Hardware Bag
Complete With: Gate bracket, Post
bracket, Extension bracket and Hardware
2
1
3
4
42
QTY
1
1
1
1
1
1
LA400 SWING GATE ACCESSORIES
Push to Open Bracket
Used to allow the gate operator to
push the gate open.
50-19503
SOLKIT12V
OPEN
OPEN
377LM
SOLKIT12V (Single Panel)
SOLKIT12V-2P (Two Panels):
Kit contains: Battery management module,
outdoor battery case (battery not included),
solar panel(s). When power is not close by,
solar may be the right option. For more
information, please contact customer service
or see pre-sale solar application guide.
SECURITY✚® Keyless Entry
:
Enables homeowner to operate gate by entering
a password on a specially designed keyboard.
Also can add a temporary password for visitors
or service persons. This temporary password
can be limited to a programmable number of
hours or entries.
LM202
Vehicle Detecting Driveway Probe:
One piece outdoor buried vehicle motion
detector with sensing probe is housed in a
small relay type housing. Provides for free exit.
GC824-12
Gate Solenoid Lock:
Heavy all steel construction. Failsafe operation
keeps gate locked if power is lost. Can be
welded onto gate or post. 24Vdc operation,
solenoid-activated release. Can be released
in case of an emergency. Requires separate
power supply (Model ARMPS).
GC838
Magnetic Gate Lock:
Incredible 1,200 Lb. holding force. Operates
on 12 or 24Vdc. Low power consumption.
Universal mounting holes for ease of
installation. Automatically releases when
power is lost. Requires separate power supply
(Model ARMPS).
50-19509
6" Post Mounting Kit for control box
50-19511
4" Post Mounting Kit for control box
50-19512
2 1/2" Post Mounting Kit for control box
GCPSN4
Commercial Protector System®:
Maximum range is 45' 24V. Includes mounting
hardware and electrical interface box.
CPS-LN4
Commercial Protector System® (Direct
Connect):
Maximum range is 45' 24V. Includes mounting
hardware.
OPEN
02101
OPEN
OPEN
OPEN
1-Button Station:
Steel enclosure wired station will allow for
a Open, Close, Stop command of the gate.
OPEN
370LM
3-Button Mini-Remote Control
with SECURITY✚®
:
With key ring and fastening strip.
373LM
3-Button SECURITY✚® Remote
Control
:
Includes visor clip.
86LM
OPEN
Remote Antenna Mounting Kit:
Kit contains antenna bracket and 15' (4.6 m)
of cable. Recommended for increasing the
effective range of remote controls.
43
WARRANTY POLICY AND SERVICE
LIFTMASTER® TWO YEAR LIMITED WARRANTY
The Chamberlain Group, Inc. warrants to the first purchaser of this product, for the structure in which this product is originally
installed, that it is free from defect in materials and/or workmanship for a period of two years from the date of purchase. The proper
operation of this product is dependent on your compliance with the instructions regarding installation, operation, maintenance and
testing. Failure to comply strictly with those instructions will void this limited warranty in its entirety.
If, during the limited warranty period, this product appears to contain a defect covered by this limited warranty, call 1-800-528-2806,
toll free, before dismantling this product. Then send this product, pre-paid and insured, to our service center for warranty repair. You
will be advised of shipping instructions when you call. Please include a brief description of the problem and a dated proof-of-purchase
receipt with any product returned for warranty repair. Products returned to Seller for warranty repair, which upon receipt by Seller are
confirmed to be defective and covered by this limited warranty, will be repaired or replaced (at Seller’s sole option) at no cost to you
and returned pre-paid. Defective parts will be repaired or replaced with new or factory-rebuilt parts at Seller’s sole option.
ALL IMPLIED WARRANTIES FOR THE PRODUCT, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED IN DURATION TO THE TWO YEAR LIMITED
WARRANTY PERIOD SET FORTH ABOVE, AND NO IMPLIED WARRANTIES WILL EXIST OR APPLY AFTER SUCH PERIOD. Some
States do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. THIS LIMITED
WARRANTY DOES NOT COVER NON-DEFECT DAMAGE, DAMAGE CAUSED BY IMPROPER INSTALLATION, OPERATION OR CARE
(INCLUDING, BUT NOT LIMITED TO ABUSE, MISUSE, FAILURE TO PROVIDE REASONABLE AND NECESSARY MAINTENANCE,
UNAUTHORIZED REPAIRS OR ANY ALTERATIONS TO THIS PRODUCT), LABOR CHARGES FOR REINSTALLING A REPAIRED OR
REPLACED UNIT, OR REPLACEMENT OF BATTERIES.
THIS LIMITED WARRANTY DOES NOT COVER ANY PROBLEMS WITH, OR RELATING TO, THE GARAGE DOOR OR GARAGE DOOR
HARDWARE, INCLUDING BUT NOT LIMITED TO THE DOOR SPRINGS, DOOR ROLLERS, DOOR ALIGNMENT OR HINGES. THIS
LIMITED WARRANTY ALSO DOES NOT COVER ANY PROBLEMS CAUSED BY INTERFERENCE. ANY SERVICE CALL THAT
DETERMINES THE PROBLEM HAS BEEN CAUSED BY ANY OF THESE ITEMS COULD RESULT IN A FEE TO YOU.
UNDER NO CIRCUMSTANCES SHALL SELLER BE LIABLE FOR CONSEQUENTIAL, INCIDENTAL OR SPECIAL DAMAGES ARISING IN
CONNECTION WITH USE, OR INABILITY TO USE, THIS PRODUCT. IN NO EVENT SHALL SELLER’S LIABILITY FOR BREACH OF
WARRANTY, BREACH OF CONTRACT, NEGLIGENCE OR STRICT LIABILITY EXCEED THE COST OF THE PRODUCT COVERED HEREBY.
NO PERSON IS AUTHORIZED TO ASSUME FOR US ANY OTHER LIABILITY IN CONNECTION WITH THE SALE OF THIS PRODUCT.
Some states do not allow the exclusion or limitation of consequential, incidental or special damages, so the above limitation or
exclusion may not apply to you. This limited warranty gives you specific legal rights, and you may also have other rights which vary
from state to state.
HOW TO ORDER REPAIR PARTS
OUR LARGE SERVICE ORGANIZATION
SPANS AMERICA
FOR INSTALLATION AND SERVICE INFORMATION,
CALL OUR TOLL FREE NUMBER
1-800-528-2806
www.liftmaster.com