LA400 - Oregon City Garage Door
Transcription
LA400 - Oregon City Garage Door
INSTALLATION/OPERATION MANUAL MODEL LA400 MEDIUM DUTY SWING GATE OPERATOR Radio Receiver Built on Board 315MHz 2 YEAR WARRANTY Serial # Primary Arm Serial # Secondary Arm Serial # Control Box Installation Date TABLE OF CONTENTS Introduction 2-5 Loop Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31 Photo/Edge Inputs (P6-7-8 and 9) . . . . . . . . . . . . . . . . . . . . . . .32 Safety Accessories for Secondary Entrapment Protection . . . . .33 Carton Inventory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 Additional Items Needed for Installation . . . . . . . . . . . . . . . . . . .3 Operator Dimensions and Specifications . . . . . . . . . . . . . . . . . . .3 UL325 Classifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 Safety Installation Information . . . . . . . . . . . . . . . . . . . . . . . . . . .5 Overview of Typical Installation Operation Reset Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34 Remote Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34 Manual Release . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34 6-10 Maintenance Left-Hand Gate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 Right-Hand Gate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 Dual Gate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 Safety Precautions for Swing and Ornamental “Grill Type Gates” . . . . . . . . . . . . . . . . . . . . . . . . . . .8 Warning Sign Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8 Before Installation Check Your Gate . . . . . . . . . . . . . . . . . . . . . . .9 Mounting Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10 Installation Basic Control Board Layout Wiring Diagram Troubleshooting Repair Parts LA400 Swing Gate Accessories Warranty Policy and Service 11-18 WARNING Mechanical CAUTION WARNING WARNING Electrical CAUTION WARNING CAUTION When you see these Safety Symbols and Signal Words on the following pages, they will alert you to the possibility of serious injury or death if you do not comply with the warnings that accompany them. The hazard may come from something mechanical or from electric shock. Read the warnings carefully. When you see this Signal Word on the following pages, it will alert you to the possibility of damage to your gate and/or the gate operator if you do not comply with the cautionary statements that accompany it. Read them carefully. 19-20 AVERTISSEMENT Step 1: Watertight Connector Nut . . . . . . . . . . . . . . . . . . . . . . .19 Step 2: Insert Operator Cable . . . . . . . . . . . . . . . . . . . . . . . . . . .19 Step 3: Connect Operator to Control Board . . . . . . . . . . . . . . . .20 21-22 Control Wiring ATTENTION Adjusting/Running the Operator 23 24-26 IMPORTANT NOTE • BEFORE attempting to install, operate or maintain the operator, you must read and fully understand this manual and follow all safety instructions. • DO NOT attempt repair or service of your commercial door and gate operator unless you are an Authorized Service Technician. ATTENTION AVERTISSEMENT AVERTISSEMENT Connect Transformer to Control Board . . . . . . . . . . . . . . . . . . .21 Earth Ground Rod Installation (Optional) . . . . . . . . . . . . . . . . . .22 AVERTISSEMENT ATTENTION TOOLS NEEDED FOR INSTALLATION During assembly, installation and adjustment of the operator the tools listed below will be needed. • Wrench or Socket Set • Phillips Head Screwdriver • C Clamps • Level • Small Screwdriver • T25 Torx Head Screwdriver Step 1: Set Dip Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24 Step 2: Program Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25 Step 3: Set Force/Bi-part/Timer . . . . . . . . . . . . . . . . . . . . . . . . .26 Optional Control and Safety Device Wiring 37 38 39-40 41-42 43 44 INTRODUCTION WARNING Power Wiring AVERTISSEMENT 35-36 Battery Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36 Step 1: Manual Release . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11 Step 2A: Determine Position of the Pull-to-Open Bracket . . . . .12 Step 2B: Determine Position of the “Optional” Push-to-Open Bracket (Not Provided) . . . . . . . . . . . . . . . . . . . .12 Step 3: Determine Mounting Location . . . . . . . . . . . . . . . . . . . .13 Step 4: Assemble Gate Post Bracket (Pull-to-Open) . . . . . . . . . .13 Step 5: Attach Bracket to Arm . . . . . . . . . . . . . . . . . . . . . . . . . .14 Step 6: Position Operator on Gate . . . . . . . . . . . . . . . . . . . . . . .14 Step 7: Test Gate Travel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15 Step 8: Secure Gate Post Bracket to Gate Post . . . . . . . . . . . . .16 Step 9: Secure Gate Bracket to Gate . . . . . . . . . . . . . . . . . . . . . .16 Step 10: Warning Sign Placement . . . . . . . . . . . . . . . . . . . . . . .17 Step 11: Open the Control Box . . . . . . . . . . . . . . . . . . . . . . . . . .18 Step 12: Select Mounting Holes . . . . . . . . . . . . . . . . . . . . . . . . .18 Step 13: Mount Control Box . . . . . . . . . . . . . . . . . . . . . . . . . . . .18 Motor Wiring 34 27-33 To Add or Reprogram a Remote Control . . . . . . . . . . . . . . . . . .27 Dip Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28 Wire Stop Button (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . .29 2 ADVERTENCIA Carton Inventory CONTROL BOX LA400 - CONT HARDWARE KIT DESCRIPTION Post Bracket Pull to Open Bracket Hex Bolt 5/16"-18 X 1-1/2" Square Neck Carriage Bolt 3/8"-16 X 6" Hex Nut 3/8"-16 Hex Nut 5/16"-18 Flat Washer 5/16" Flat Washer 3/8" Lock Washer 5/16" Lock Washer 3/8" Gate Mounting Bracket Hairpin Clip Pin Hex Bolt 3/8"-16 X 1-1/2" Bolt 2-3/4" DESCRIPTION Control Box Hardware Bag QTY 1 1 5 2 2 5 5 5 5 5 1 4 2 1 2 MISCELLANEOUS Linear Actuator Arm Motor Cable - Six Conductor Warning Sign Battery Plug-In Transformer QTY 1 1 9' (2.7 m) 2 2 1 LA400-S (SECOND LINEAR ACTUATOR ARM) Extension Cable - Six Conductor 40' (12.2 m) Junction Box - IP56 1 Phillips Head Mounting Screws 4 Anchors 4 Terminal Block - Twelve Connectors 1 NOTE: Carton inventory is based on a Single Operator. For Primary (Gate 1) and Secondary (Gate 2) installation the carton inventory is doubled except for control box. Additional Items Needed for Installation Permanent fasteners for warning sign Earth Ground Rod (Optional) Power Wire: 120Vac (Stranded Copper Wire) Power Wire: 24Vac Transformer (Stranded Copper Wire) Wire Gauge Length Wire Gauge Length OR 16 100' (30 m) 14 500' (152 m) 10 1000' (305 m) 12 1000' (305 m) Operator Dimensions and Specifications Operating Cycles 100 per day Main Supply (Motor) 24Vdc Current Consumption 2A Power Consumption 48 Watts Battery Charger Supply 26Vac, 29VA or 36Vdc, 40VA Solar Panel Supply (Optional) See Accessories Maximum Gate Width 16 ft. (4.9 m) Maximum Gate Weight 550 Lbs. (249.5 kg) Protection Class NEMA 3R Travel Speed 14-18 seconds for a 90 degree opening Rated Operating Time 4 Minutes Temperature -20˚C to + 50˚C -4˚F to + 122˚F Main Supply (Control) Dedicated Circuit 120V~/60Hz Absorbed Power 0.75 Watts Protection Fuse Battery ATC 20A 14" (35.6 cm) 10" 6" (25.4 cm) (15.2 cm) Weight: 13.2 lbs. (6 kg.) 36.3" (92.1 cm) 4.00" (10.2 cm) .475" DIA. (1.2 cm DIA.) 37.4" (95.0 cm) 4.50" .250" (11.2 cm) (0.635 cm) 3 UL325 Model Classifications The LA400 is intended for use with vehicular swing gates. The operator can be used in Class I, Class II and Class III applications. CLASS I – RESIDENTIAL VEHICULAR GATE OPERATOR A vehicular gate operator (or system) intended for use in a home of one-to four single family dwelling, or a garage or parking area associated therewith. CLASS II – COMMERCIAL/GENERAL ACCESS VEHICULAR GATE OPERATOR A vehicular gate operator (or system) intended for use in a commercial location or building such as a multi-family housing unit (five or more single family units) hotel, garages, retail store or other building servicing the general public. CLASS III – INDUSTRIAL/LIMITED ACCESS VEHICULAR GATE OPERATOR A vehicular gate operator (or system) intended for use in a industrial location or building such as a factory or loading dock area or other locations not intended to service the general public. UL325 ENTRAPMENT PROTECTION REQUIREMENTS SAFETY ACCESSORY SELECTION All UL325 compliant LiftMaster gate operators will accept external entrapment protection devices to protect people from motorized gate systems. UL325 requires that the type of entrapment protection correctly matches each gate application. Below are the four types of entrapment protection systems recognized by UL325 for use on this operator. Gate Operator Entrapment Protection UL325 Swing and Gate Barrier Installation (Arm) Operator ENTRAPMENT PROTECTION TYPES Type A: Inherent obstruction sensing system, self-contained within the operator. This system must sense and initiate the reverse of the gate within two seconds of contact with a solid object. Type B1: Connections provided for a non-contact device, such as a photoelectric eye can be used as a secondary protection. Type B2: Connections provided for a contact sensor. A contact device such as a gate edge can be used for secondary protection. Type E: Built-in audio alarm. Examples include sirens, horns or buzzers. NOTE: UL requires that all installations must have warning signs placed in plain view on both sides of the gate to warn pedestrians of the dangers of motorized gate systems. Primary Type Secondary Type Class I and II A A, B1 or B2 Class III A, B1 or B2 A, B1, B2 or E Class The chart above illustrates the entrapment protection requirements for each of the three UL325 classes. In order to complete a proper installation you must satisfy the entrapment protection chart shown above. That means that the installation must have one primary means of entrapment protection and one independent secondary means of entrapment protection. Both primary and secondary entrapment protection methods must be designed, arranged or configured to protect against entrapments in both the open and close directions of gate travel. For Example: For a slide gate system that is installed on a single-family residence (UL325 Class I) you must provide the following: As your primary type of entrapment protection you must provide Type A inherent (built into the operator) entrapment sensing and at least one of the following as your secondary entrapment protection: Type B1- Non-contact sensors such as photoelectric eyes, Type B2- Contact sensors such as gate edges. Moving Gate Can Cause Injury or Death KEEP CLEAR! Gate may move at any time without prior warning. Do not let children operate the gate or play in the gate area. This entrance is for vehicles only. Pedestrians must use separate entrance 4 Safety Installation Information 1. Vehicular gate systems provide convenience and security. Gate systems are comprised of many component parts. The gate operator is only one component. Each gate system is specifically designed for an individual application. 2. Gate operating system designers, installers and users must take into account the possible hazards associated with each individual application. Improperly designed, installed or maintained systems can create risks for the user as well as the bystander. Gate systems design and installation must reduce public exposure to potential hazards. 3. A gate operator can create high levels of force in its function as a component part of a gate system. Therefore, safety features must be incorporated into every design. Specific safety features include: • Gate Edges • Guards for Exposed Rollers • Photoelectric Sensors • Screen Mesh • Vertical Posts • Instructional and Precautionary Signage 4. Install the gate operator only when: a. The operator is appropriate for the construction and the usage class of the gate. b. All openings of a horizontal slide gate are guarded or screened from the bottom of the gate to a minimum of 4' (1.2 m) above the ground to prevent a 2-1/4" (6 cm) diameter sphere from passing through the openings anywhere in the gate, and in that portion of the adjacent fence that the gate covers in the open position. c. All exposed pinch points are eliminated or guarded, and guarding is supplied for exposed rollers. 5. The operator is intended for installation only on gates used for vehicles. Pedestrians must be supplied with a separate access opening. The pedestrian access opening shall be designed to promote pedestrian usage. Locate the gate such that persons will not come in contact with the vehicular gate during the entire path of travel of the vehicular gate. 6. The gate must be installed in a location so that enough clearance is supplied between the gate and adjacent structures when opening and closing to reduce the risk of entrapment. Swinging gates shall not open into public access areas. 7. The gate must be properly installed and work freely in both directions prior to the installation of the gate operator. 8. Controls intended for user activation must be located at least six feet (6') away from any moving part of the gate and where the user is prevented from reaching over, under, around or through the gate to operate the controls. Outdoor or easily accessible controls shall have a security feature to prevent unauthorized use. 9. The Stop and/or Reset (if provided separately) must be located in the line-of-sight of the gate. Activation of the reset control shall not cause the operator to start. 10. A minimum of two (2) WARNING SIGNS shall be installed, one on each side of the gate where easily visible. 11. For a gate operator utilizing a non-contact sensor: a. Reference owner’s manual regarding placement of non-contact sensor for each type of application. b. Care shall be exercised to reduce the risk of nuisance tripping, such as when a vehicle trips the sensor while the gate is still moving. c. One or more non-contact sensors shall be located where the risk of entrapment or obstruction exists, such as the perimeter reachable by a moving gate or barrier. 12. For a gate operator utilizing a contact sensor such as an edge sensor: a. One or more contact sensors shall be located where the risk of entrapment or obstruction exists, such as at the leading edge, trailing edge and post mounted both inside and outside of a vehicular horizontal slide gate. b. One or more contact sensors shall be located at the bottom edge of a vehicular vertical lift gate. c. A hard wired contact sensor shall be located and its wiring arranged so the communication between the sensor and the gate operator is not subject to mechanical damage. d. A wireless contact sensor such as the one that transmits radio frequency (RF) signals to the gate operator for entrapment protection functions shall be located where the transmission of the signals are not obstructed or impeded by building structures, natural landscaping or similar obstruction. A wireless contact sensor shall function under the intended end-use conditions. e. One or more contact sensors shall be located on the inside and outside leading edge of a swing gate. Additionally, if the bottom edge of a swing gate is greater than 6" (152 mm) above the ground at any point in its arc of travel, one or more contact sensors shall be located on the bottom edge. f. One or more contact sensors shall be located at the bottom edge of a vertical barrier (arm). 5 OVERVIEW OF TYPICAL INSTALLATION Ou To prevent SERIOUS INJURY or DEATH; one or more non-contact sensors shall be located where the risk of entrapment or obstruction exists. CAUTION Left-Hand Gate e tsid WARNING y ert p Pro Warning Sign Hinge use Ca Antenna Control Box with Batteries n Ca te athat any e g Ga or De mov vin or may Mo Injury Gate ing. gate AR! warnate the P CLE prior oper KEE without ren . only nce time let child area cles entra vehi rate not gate Do in the is for sepa nce t use play entrans mus This stria Pede Post Bracket Gate Bracket Operator Power Cable f n o vel o i t a ec Tr DirGate AVERTISSEMENT ATTENTION rty pe ro eP id PVC Conduit (not provided) to protect the power cable and low voltage wire from lawn mowers and string trimmers. Ins Entrapment Sensors Right-Hand Gate Warning Sign Hinge esu aC yna n hta aC et ta e eD aG gn vom ro yam yru ivo tag .gninra etaG jnI M eht w r !RA o etar E epo irp tuo LC PE htiw EK n artnylno s . erd e et elcih aera e lihc te emit l t ara ev pes rof ag eht ton oD esu si ec n tsu nar i yalp m s tne nair sih tsed T eP ro e ecn Antenna Post Bracket Gate Bracket Operator Control Box with Batteries ADVERTENCIA PRECAUCIÓN Power Cable PVC Conduit (not provided) to protect the power cable and low voltage wire from lawn mowers and string trimmers. Entrapment Sensors NOTE: One or more non-contact sensors shall be located where the risk of entrapment or obstruction exists at either the opening or closing direction. Care shall be exercised to reduce the risk of nuisance tripping, such as when a vehicle, trips the sensor while the gate is still moving. 6 Dual Gate Typical Installation Junction Box erty ide s Out p Pro Extension Cable Warning Sign Entrapment Sensors Gate 2 Hinge use n Ca Ca te athat any e g Ga or De mov vin or may . Mo Injury Gatewarning gate the AR! r P CLEout prio operate KEE with ren . only ance time let child area cles entr vehi rate not gate Do in the is for sepa ance t use play entr mus Thisestrians Ped Control Box with Batteries Antenna f n oavel o i t ec Tr Dir ate 2 G Post Bracket Gate Bracket Gate 1 Power Cable of el n v o i ect 1 Tra r i D ate G ty de nsi I PVC Conduit (not provided) to protect the power cable and low voltage wire from lawn mowers and string trimmers. Entrapment Sensors 7 P er rop Safety Precautions for Swing and Ornamental “Grill Type Gates” WARNING WARNING To prevent SERIOUS INJURY or DEATH from a moving gate: • Entrapment protection devices MUST be installed to protect anyone who may come near a moving gate. • Locate entrapment protection devices to protect in BOTH the open and close gate cycles. • Locate entrapment protection devices to protect between moving gate and RIGID objects, such as posts. • A swinging gate shall NOT open into public access ways. CAUTION WARNING AVERTISSEMENT AVERTISSEMENT ATTENTION AVERTISSEMENT Warning Sign Placement WARNING WARNING To prevent SERIOUS INJURY or DEATH from a moving gate: • Install warning signs on EACH side of gate in PLAIN VIEW. • Permanently secure each warning sign in a suitable manner using fastening holes. CAUTION WARNING ADVERTENCIA ADVERTENCIA PRECAUCIÓN AVERTISSEMENT ADVERTENCIA AVERTISSEMENT Moving Gate Can Cause Injury or Death ATTENTION AVERTISSEMENT KEEP CLEAR! Gate may move at any time without prior warning. Do not let children operate the gate or play in the gate area. This entrance is for vehicles only. Pedestrians must use separate entrance 8 Before Installation Check Your Gate Gate and gate post MUST be plumb. Gate MUST be level Gate MUST NOT hit or drag across ground Remove ANY/ALL wheels from the bottom of the gate Gate MUST swing freely and be supported entirely by it’s hinges. Heavy duty, ball bearing type hinges are recommended. 9 Mounting Options Mounting locations vary depending on type and style of your gate. Minimum distance from the ground should not be less than 4" from the bottom of the gate operator arm. Optional: = Gate post bracket mounting locations = Gate bracket mount locations Recommended: = Gate post bracket mounting locations = Gate bracket mount locations 10 INSTALLATION Step 1: Manual Release Insert the key into the lock and turn counter-clockwise 180°. Turn the release lever counter-clockwise 180°. The operator is in manual mode. Release Lever 11 Step 2A: Determine Position of the Pull-to-Open Bracket The Pull-To-Open bracket can be assembled to work on a Left-Hand or a Right-Hand gate. Review the gate types below and select the type of installation you will require. NOTE: If the Pull-To-Open bracket is not assembled correctly you will damage the operator. Right-Hand Gate Left-Hand Gate Left-Hand Gate Right-Hand Gate Step 2B: Determine Position of the “Optional” Push-to-Open Bracket (Not provided. See Accessories.) The Push-To-Open bracket can be assembled to work on a Left-Hand or a Right-Hand gate. Review the gate types below and select the type of installation you will require. Right-Hand Gate Left-Hand Gate Left-Hand Gate Right-Hand Gate 12 Step 3: Determine Mounting Location The gate post bracket assembly can be mounted several places on the gate post. Refer to the illustrations on page 10 for the ideal mounting location. Refer to the illustrations below to determine the appropriate dimensions for the Pull-To-Open bracket. NOTE: It may be necessary to add shims (angle iron, sheets of metal or wood) to the gate post to achieve the required dimensions. Gate Post Gate Post Gate Post Gate Hinge Point Gate Hinge Point 7" (18 cm) Gate Hinge Point 7" (18 cm) Operator Hinge Point 7" (18 cm) Operator Hinge Point 7" (18 cm) Operator Hinge Point 7" (18 cm) Gate Post Gate Post Gate Post Gate Hinge Point 7" (18 cm) Gate Hinge Point Gate Hinge Point 7" (18 cm) 7" (18 cm) Operator Hinge Point 7" (18 cm) Operator Hinge Point Operator Hinge Point 7" (18 cm) 7" (18 cm) 7" (18 cm) Step 4: Assemble Gate Post Bracket (Pull-to-Open) Assemble Gate Post bracket by placing Pull-To-Open bracket on top of Post bracket. Insert bolt through both brackets and secure with washer, lock washer and nut. Insert second bolt through both brackets and secure with washer, lock washer and nut. 5/16" Hex Bolt 3/8" Hex Bolt Pull-to-Open Bracket Pull-to-Open Bracket Post Bracket Post Bracket 3/8" Washer 5/16" Washer 3/8" Lock Washer 5/16" Lock Washer 3/8" Nut 5/16" Nut 13 NOTE: All the illustrations on the following pages display a typical Left-Hand Gate installation. Step 5: Attach Brackets to Arm Attach gate post bracket to arm using hex bolt and lock nut with nylon insert. Attach gate bracket to arm using pin and hairpin clip. Hex Bolt Pin Gate Post Bracket Gate Bracket Hairpin Clip Hairpin Clip Step 6: Position Operator on Gate The gate post bracket assembly can be mounted several places on the gate post. Refer to the illustrations on page 10 for mounting options. Place opener arm against gate post at the desired vertical position and temporarily secure Gate Post bracket with C-clamp. Arm must be level. Open gate to desired open position (no greater than 100°) and hold arm against gate. Mark mounting holes on gate for reference. Temporarily secure the gate bracket using a C-clamp. 14 Step 7: Test Gate Travel Manually open and close the gate. Ensure that the arm does not bind against the pull-to-open bracket. Ensure that the piston does not bottom out. 1/2" (1.3 cm) Do not allow piston to fully extend or fully retract. 1/2" (1.3 cm) NOTE: If gate does not open and close completely adjust the position of the gate bracket and mark new mounting holes. 15 Step 8: Secure Gate Post Bracket to Gate Post Mark holes for gate post bracket. Remove C-clamp and operator. Set aside and drill adequate holes in gate post. Welder (Optional) Secure gate post bracket to gate post using hardware. Keep arm level. Lock Washers Hex Nuts Flat Washers Carriage Bolts Step 9: Secure Gate Bracket to Gate Drill holes in gate or reinforcement (if necessary) large enough for the gate bracket mounting hardware. Secure gate bracket to gate using hardware (not provided). Keep arm level. Welder (Optional) NOTE: Some installations may require additional reinforcement be installed on the gate. Angle Iron Wood Reinforcement Area OR Arm Hex Nut Flat Washer Lock Washer OR Flat Bar Gate Bracket Hex Bolt Manually move the gate to verify gate opens and closes fully. 16 Step 10: Warning Sign Placement Warning placards MUST be installed on both sides of the gate and in plain view. WARNING To prevent SERIOUS INJURY or DEATH from a moving gate: • Install warning signs on the front and back of the gate in PLAIN VIEW. • Permanently secure each warning sign in a suitable manner using fastening holes. CAUTION Gate Post Fence Gate Moving Gate Can Cause Injury or Death KEEP CLEAR! Gate may move at any time without prior warning. Gate Travel Path Do not let children operate the gate or play in the gate area. This entrance is for vehicles only Pedestrians must use separate entrance Inside Property If you are installing a 2nd operator repeat installation steps 1-10 for the second gate before proceeding to the next page. 17 NOTE: It is recommended that the control box be mounted within 3' (.9 m) of Gate 1 or Gate 2. Step 11: Open the Control Box Remove screws and open the control box. Screws (4) Step 12: Select Mounting Holes Select holes to be used for mounting and knock out using a screwdriver and hammer. Knock Outs P2 R223 P1 CLOSE EDGE J19 Ø14GPØ89ØE Ø14LGØ89ØE Ø14SKØ89ØE K6 ALARM R2Ø7 J1 NO Z2Ø R227 C K5 MAGLOCK OPEN EDGE/ PHOTO NO L1 R224 C 1 S8 OFF OFF SINGLE NO NO LEARN XMITTER R1 10A 32V 2 GATE 1 1 2 3 4 5 R2 O N NC Z1 Z22 R92 U4 ON SAVE ON MAGLOCK DUAL MODE NC EDGE PHOTO NC Z9 OPEN PHOTO S1 F3 Knock Outs R91 BRN D1Ø GRN R94 K2 Z8 WHT CLOSE PHOTO DIAGNOSTIC YEL R93 BLU GATE 1 RED K1 Q9 Z12 SET OPEN LIMIT SET CLOSE LIMIT R9Ø ACCESSORY POWER Knock Outs LEARN LIMITS 24V TIMER RUNNING GATE 2 BIPART DELAY 24V FORCE R1Ø1 BRN COM OVLD SWITCHED ACCESSORY POWER Knock Outs CONTROL INPUTS TIMER TO SINGLE BUTTON CLOSE R1ØØ OVLD OPEN SINGLE BUTTON F4 GRN RESET ACCESSORY OVLD 10A 32V WHT STOP K4 YEL MIN MAX OFF MAX OFF MAX COM F5 BLU COM D21 RED D9 K3 D8 GATE 2 POWER R35 C12 D27 Z3 F7 Z4 Q22 C13 D22 LOOP INPUTS C4 SHADOW U3 INTERRUPT C11 R4 C2 R196 F6 24 VAC/ SOLAR INPUT J4 COM CHGR OVLD D15 F2 MOV2 R9 MOV1 F1 20A 32V D4 D1 C64 JMPR2 JMPR1 D2 U2 FUSE OPEN BATT 2 BATT 1 D6 DB1 Knock Outs Step 13: Mount Control Box Secure control box to mounting surface (post, wall, column, etc.) using appropriate hardware. Round Gate Post Square Gate Post Lock Washer (Not Provided) U Bolt (Not Provided) Screw Washer (Not Provided) Hex Nut (Not Provided) 18 NING WARNING MOTOR WIRING ON WARNING To reduce the risk of SEVERE INJURY or DEATH: • ANY maintenance to the operator or in the area near the operator MUST not be performed until disconnecting the electrical power and locking-out the power via the operator power switch. Upon completion of maintenance the area MUST be cleared and secured, at that time the unit may be returned to service. • Disconnect power at the fuse box BEFORE proceeding. Operator MUST be properly grounded and connected in accordance with local electrical codes. NOTE: The operator should be on a separate fused line of adequate capacity. • ALL electrical connections MUST be made by a qualified individual. SEMENT ION ENCIA • DO NOT install ANY wiring or attempt to run the operator without consulting the wiring diagram. We recommend that you install an optional reversing edge BEFORE proceeding with the control station installation. • ALL power wiring should be on a dedicated circuit and well protected. The location of the power disconnect should be visible and clearly labeled. • ALL power and control wiring MUST be run in separate conduit. • BEFORE installing power wiring or control stations be sure to follow ALL specifications and warnings described below. Failure to do so may result in SEVERE INJURY to persons and/or damage to operator. AVERTISSEMENT AVERTISSEMENT Step 1: Watertight Connector Nut Insert operator cable through watertight connector nut. Operator Cable Watertight Connector Nut Operator ADVERTENCIA Step 2: Insert Operator Cable Insert operator cable through watertight connector mounted in the bottom of the control box. ADVERTENCIA CIÓN P2 J19 J1 Ø14GP 14GPØ89 89ØE Ø14LG 14LGØ89 89ØE Ø14SK 14SKØ89 89ØE R223 P1 L1 CLOSE EDGE K6 S8 LEARN XMITTER Z2Ø R227 K5 OPEN EDGE/ PHOTO NO 2 OFF OFF SINGLE NO NO 1 2 3 4 5 1 R2Ø7 NO C MAGLOCK O N ALARM ON SAVE ON MAGLOCK DUAL MODE NC EDGE NC PHOTO S1 L1 R224 C Z22 R92 U4 NC ON R2 Z1 OFF Z9 MAGLOCK LEARN XMITTER R1 OPEN PHOTO 10A 32V GATE 1 R91 F3 BRN D1Ø GRN Control Box R94 K2 24V Z8 WHT CLOSE PHOTO DIAGNOSTIC YEL R93 BLU GATE 1 RED K1 Q9 Z12 SET CLOSE LIMIT SET OPEN LIMIT R9Ø ACCESSORY POWER LEARN LIMITS GATE 2 24V COM OVLD CONTROL INPUTS TIMER TO CLOSE FORCE R1Ø1 BRN TIMER RUNNING OPEN R1ØØ SINGLE BUTTON F4 GRN RESET ACCESSORY OVLD 10A 32V WHT STOP K4 YEL OFF MAX COM F5 BLU COM D21 RED D9 K3 D8 GATE 2 POWER R35 C12 D27 Z3 F7 Z4 Q22 C13 D22 LOOP INPUTS C4 SHADOW U3 INTERRUPT C11 R196 F6 24 VAC/ SOLAR INPUT F2 MOV2 R9 MOV1 JMPR2 JMPR1 FUSE OPEN D2 U2 BATT 2 BATT 1 D6 DB1 F1 20A 32V D4 D1 C64 P2 Watertight Connector J19 Ø14GPØ89ØE Ø14LGØ89ØE Ø14SKØ89ØE J1 C2 COM CHGR OVLD D15 R4 J4 L1 1 2 3 4 5 S8 O N 1 LEARN XMITTER 2 Operator Cable S1 Watertight Connector Nut 19 Operator Cable Operator Step 3: Connect Operator to Control Board Extend cable and wires to “Gate 1” connector for single gate arm installation and connect as shown. Repeat for “Gate 2” connector and connect as shown. C Gate 1 NOTE: Wire connectors can be removed to simplify wiring. NC Z1 R1 10A 32V GATE 1 Brown F3 BRN D1Ø K2 Yellow M CO 1 CA EXIT HOUSE WHT 2 EXIT LL GRN White AUTO Green TELCO YEL Blue BLU Red RED K1 Q Z12 R9Ø ACCESSORY POWER Gate 2 24V ACCESSORY POWER NC Z1 BRN 24V GRN Brown F3 BRN Green White 10A 32V WHT P2 Yellow J19 J1 Ø14GPØ89ØE Ø14LGØ89ØE Ø14SKØ89ØE L1 P2 2 CLOSE EDGE Ø14GP 14GPØ89 89ØE Ø14LG 14LGØ89 89ØE Ø14SK 14SKØ89 89ØE NO S1 BLU R2Ø7 Z2Ø R227 C K5 MAGLOCK Red OPEN EDGE/ PHOTO NO YEL Blue R223 J19 K6 ALARM J1 LEARN XMITTER P1 1 2 3 4 5 S8 O N 1 L1 R224 C S8 Z1 LEARN XMITTER R1 10A 32V 2 1 2 3 4 5 OFF OFF SINGLE NO NO R2 GATE 1 O N 1 NC RED Z22 R92 U4 ON SAVE ON MAGLOCK DUAL MODE NC EDGE NC PHOTO K2 GRN Z9 OPEN PHOTO S1 R91 F3 BRN D1Ø GRN R94 K2 GATE 2 Z8 WHT CLOSE PHOTO DIAGNOSTIC YEL R93 BLU GATE 1 RED Z12 SET CLOSE LIMIT SET OPEN LIMIT K1 Q9 R9Ø ACCESSORY POWER LEARN LIMITS GATE 2 24V TIMER RUNNING COM OVLD OVLD SWITCHED ACCESSORY POWER CONTROL INPUTS 24V R1Ø1 BRN OPEN R1ØØ SINGLE BUTTON F4 GRN RESET ACCESSORY OVLD 10A 32V WHT STOP K4 YEL COM F5 BLU COM D21 RED POWER R35 D9 K3 D8 GATE 2 C12 D27 Z3 F7 Z4 Q22 C13 D22 LOOP INPUTS C4 SHADOW U3 C2 R196 R4 F6 24 VAC/ SOLAR INPUT J4 COM CHGR OVLD D15 R4 D15 INTERRUPT C11 F2 MOV2 R9 MOV1 JMPR1 D2 U2 FUSE OPEN BATT 2 BATT 1 D6 DB1 F1 20A 32V D4 D1 C64 JMPR2 Control Box Operator Cable “Gate 2” Operator Cable “Gate 1” Watertight Connector Nut Control Box Operator Cable NOTE: Never allow operator cable to drag on ground. 20 Operator C2 R196 WARNING POWER WIRING WARNING WARNING CAUTION CAUTION WARNING To AVOID damaging plug-in transformer, it MUST be enclosed in a suitable weatherproof enclosure and provided with proper weatherproof fixtures. To AVOID damaging gas, power or other underground utility lines, contact underground utility locating companies BEFORE digging. Connect Transformer to Control Board NOTE: All power wiring should be on a dedicated circuit and well protected. Calculated using NEC guidelines. Local codes and conditions must be reviewed for suitability of wire installation. The transformer can be plugged into a receptacle external to the control box. Run low voltage wire between the transformer and control box. This will create more space in the control box for accessories. AVERTISSEMENT AVERTISSEMENT AVERTISSEMENT Dedicated Outlet ATTENTION AVERTISSEMENT ATTENTION Control Box Transformer Operator ADVERTENCIA ADVERTENCIA ADVERTENCIA OR Connect 120Vac directly to the box and plug the transformer to the receptacle inside the control box. ADVERTENCIA PRECAUCIÓN Off Main Room Control Box Transformer Off On P2 CLOSE EDGE J19 K6 Ø14GP 14GPØ89 89ØE Ø14LG 14LGØ89 89ØE Ø14SK 14SKØ89 89ØE ALARM R2Ø7 J1 NO Z2Ø R227 C K5 MAGLOCK OPEN EDGE/ PHOTO NO L1 R224 C OFF OFF SINGLE NO NO LEARN XMITTER R1 2 1 2 3 4 5 Z22 R92 U4 ON SAVE ON MAGLOCK DUAL MODE NC EDGE NC PHOTO Z9 OPEN PHOTO S1 R91 F3 Off On Off Bathroon. S8 R2 10A 32V GATE 1 O N 1 NC Z1 BRN D1Ø GRN R94 K2 Z8 WHT CLOSE PHOTO DIAGNOSTIC YEL R93 BLU GATE 1 RED SET K1 Q9 OPEN LIMIT Z12 SET CLOSE LIMIT R9Ø ACCESSORY POWER LEARN LIMITS GATE 2 24V SWITCHED ACCESSORY POWER TIMER RUNNING CONTROL INPUTS 24V R1Ø1 BRN Off F4 GRN ACCESSORY OVLD 10A 32V WHT P2 K4 YEL J19 F5 BLU D21 RED Ø14GPØ89ØE Ø14LGØ89ØE Ø14SKØ89ØE R35 D9 K3 D8 GATE 2 C12 D27 Z3 F7 Z4 Q22 C13 D22 F6 F2 R9 MOV1 D4 D1 C64 JMPR2 JMPR1 D2 U2 Off D6 Off 1 FUSE OPEN S8 LEARN XMITTER 2 MOV2 DB1 21 L1 CHGR OVLD R196 1 2 3 4 5 C2 24 VAC/ SOLAR INPUT Main Dept. Manu. 2 Rm C4 U3 C11 D15 R4 J4 O N Eug. Dept. Manu. 1 Rm R1ØØ J1 Off Air (2) Conditioner Comp. Serve 1 R223 P1 Off On LA400 On On Air (1) Conditioner Off On On Comp. Serve 2 Off Conference Room 2 On Conference Room 1 Off Circuit Panel Conference Rm 2, 3 Off Refer. Bus 1, 2, 3 Off PRECAUCIÓN S1 WARNING EARTH GROUND ROD INSTALLATION (OPTIONAL) CAUTION To AVOID damaging gas, power or other underground utility NOTE: For proper operation, do not connect the lines, contact underground utility locating companies BEFORE earth ground rod to the green screw on the outlet digging. plate. 1. Install earth ground rod within 3' (0.9 m) of the operator. 2. Disconnect and remove the green/yellow ground wire connected to the screw terminal of the control board. 3. Attach earth ground rod wire to the screw terminal of the control board marked . Ensure the power wiring ground connection remains securely connected to the green screw on the outlet plate. AVERTISSEMENT R4 C2 24 VAC/ ATTENTION SOLAR INPUT J4 P2 J19 J1 Ø14GPØ89ØE Ø14LGØ89ØE Ø14SKØ89ØE NO L1 C S8 OFF OFF SINGLE NO NO LEARN XMITTER 2 1 2 3 4 5 1 O N NC ALARM ON SAVE ON MAGLOCK DUAL MODE NC EDGE NC PHOTO S1 BRN GRN MAGLOCK WHT R223 P1 YEL CLOSE EDGE J19 R2Ø7 BLU NO Z2Ø R227 C Z1 Z1 RED K5 OPEN EDGE/ PHOTO GATE 1 GATE 1 L1 R224 GRN 24V Z22 R92 U4 R2 Z9 LEARN XMITTER R1 OPEN PHOTO 10A 32V 2 ACCESSORY POWER R91 F3 D1Ø CONTROL INPUTS K2 DIAGNOSTIC 24V BLU GRN Z12 OPEN K1 Q9 SET OPEN LIMIT SET CLOSE LIMIT Ground Screw SINGLE BUTTON GATE 1 BRN RESET LEARN LIMITS WHT R9Ø GATE 2 ACCESSORY POWER YEL BLU R1Ø1 RED R1ØØ STOP TIMER RUNNING FORCE COM CONTROL INPUTS TIMER TO SINGLE BUTTON CLOSE COM OPEN POWER SINGLE BUTTON F4 GATE 2 RESET ACCESSORY OVLD 10A 32V STOP K4 OFF MAX COM F5 COM D21 POWER R35 D9 K3 D8 C12 D27 Z3 F7 Z4 Q22 C13 D22 LOOP INPUTS C4 SHADOW U3 INTERRUPT C11 R196 COM F6 24 VAC/ SOLAR INPUT D27 Z3 CHGR OVLD POWER D15 C2 GATE 2 F2 MOV2 R9 MOV1 D4 D1 C64 JMPR2 JMPR1 D2 U2 FUSE OPEN BATT 2 BATT 1 D6 DB1 F1 20A 32V R4 J4 FUSE OPEN FUSE OPEN Control Box ADVERTENCIA 3' (0.9 m) 12 Gauge Wire PRECAUCIÓN 8' (2.4 m) Earth Ground Installation (Optional) 22 WARNING CONTROL WIRING CAUTION To reduce the risk of FIRE or INJURY to persons use ONLY LiftMaster part #K74-30762 for replacement batteries. 24 VAC/ SOLAR INPUT J4 MOV2 AVERTISSEMENT P2 J19 J1 Ø14GPØ89ØE Ø14LGØ89ØE Ø14SKØ89ØE ATTENTION NO L1 C S8 OFF OFF SINGLE NO NO LEARN XMITTER 2 1 2 3 4 5 1 O N NC ON SAVE ON MAGLOCK DUAL MODE NC EDGE NC PHOTO S1 BRN GRN WHT R223 P1 YEL CLOSE EDGE J19 R2Ø7 BLU NO Z2Ø R227 C Z1 RED K5 OPEN EDGE/ PHOTO GATE 1 L1 R224 GRN 24V Z22 R92 U4 R2 Z9 LEARN XMITTER R1 OPEN PHOTO 10A 32V 2 ACCESSORY POWER R91 F3 D1Ø CONTROL INPUTS K2 DIAGNOSTIC 24V BLU OPEN GRN Z12 SINGLE BUTTON GATE 1 BRN K1 Q9 SET OPEN LIMIT SET CLOSE LIMIT RESET LEARN LIMITS WHT R9Ø GATE 2 YEL BLU RED STOP TIMER RUNNING COM CONTROL INPUTS TIMER TO SINGLE BUTTON CLOSE FORCE R1Ø1 COM OPEN POWER R1ØØ SINGLE BUTTON F4 GATE 2 RESET ACCESSORY OVLD 10A 32V STOP K4 OFF MAX COM F5 COM D21 POWER R35 D9 K3 D8 C12 D27 Z3 F7 Z4 Q22 C13 D22 LOOP INPUTS C4 SHADOW U3 INTERRUPT C11 POWER D15 C2 CHGR OVLD R196 COM F6 24 VAC/ SOLAR INPUT F2 MOV2 R9 MOV1 D4 D1 C64 JMPR2 JMPR1 D2 U2 BATT 2 FUSE OPEN BATT 1 D6 DB1 F1 20A 32V USE DEDICATED CIRCUIT CHARGING The 24Vac input can accept a charging transformer (26Vac, 29VA or 36Vdc, 40VA). ADVERTENCIA OR PRECAUCIÓN BATT 1 BATT1 Connector BATT2 Connector BATTERY The main source of power for the operator is the batteries. The batteries can be charged in circuit by using a charging transformer or solar panels. SOLAR PANEL KIT Optional Liftmaster solar panel(s) kit may be used to charge the batteries. (See Accessories) 23 ADJUSTING / RUNNING THE OPERATOR Step 1: Set Dip Switch 1. The Save switch must be set to the OFF position prior to programming or changing the switches. 2. Set switch to Single for single gate installation. For Dual (Gate 1 and 2) installation set switch on Dual. NOTE: Save switch must be in the OFF position prior to programming or changing switches for the change to be saved. O N 1 2 3 4 5 OFF OFF SINGLE NO NO ON ON DUAL NC NC SAVE MAGLOCK MODE EDGE PHOTO S1 FACTORY DEFAULT SHOWN P2 CLOSE EDGE J19 J1 Ø14GPØ89ØE Ø14LGØ89ØE Ø14SKØ89ØE OPEN/EGE PHOTO L1 OFF OFF SINGLE NO NO 1 2 3 4 5 S8 LEARN XMITTER 2 O N 1 ON SAVE ON MAGLOCK DUAL MODE NC EDGE NC PHOTO OPEN PHOTO S1 CLOSE PHOTO GATE1 SET OPEN LIMIT SET CLOSE LIMIT LEARN LIMITS 24V GATE 2 SWITCHED ACCESSORY POWER GATE 1 AND GATE 2 GATE 1 24 1 2 3 4 5 1 2 3 4 5 OFF OFF SINGLE NO NO ON ON DUAL NC NC O N O N OFF OFF SINGLE NO NO OVLD ON ON DUAL NC NC Step 2: Program Limits (Ensure Save Switch is in the OFF position before beginning) DIAGNOSTIC 1. With the gate in the closed position, press the “LEARN LIMITS” button. The “SET OPEN LIMIT” LED will blink. GATE 1 SET T EN N OPEN T LIMIT SET CLOSE LIMIT LEARN LIMITS GATE 2 FORCE 2. Use the “Gate 1” buttons to move Gate 1 to the desired open position (not to exceed 100°). If you have gone beyond the desired open position you can jog the gate towards the close position by using the opposite Gate 1 button. Repeat if Gate 2 is present using the “Gate 2” buttons. LEARN LIMITS Button DIAGNOSTIC GATE 1 SET OPEN LIMIT SET CLOSE LIMIT LEARN LIMITS DIAGNOSTIC DIAGNOSTIC GATE 1 SET OPEN LIMIT SET CLOSE LIMIT LEARN LIMITS GATE 1 SET OPEN LIMIT SET CLOSE LIMIT GATE 2 LEARN LIMITS GATE 2 FORCE FORCE GATE 2 DIAGNOSTIC P2 CLOSE EDGE J19 J1 Ø14GP 14GPØ89 89ØE Ø14LG 14LGØ89 89ØE Ø14SK 14SKØ89 89ØE OPEN/EGE PHOTO L1 S8 LEARN XMITTER 2 OFF OFF SINGLE NO NO 1 2 3 4 5 1 O N FORCE ON SAVE ON MAGLOCK DUAL MODE EDGE NC PHOTO NC OPEN PHOTO S1 CLOSE PHOTO GATE1 SET OPEN LIMIT SET CLOSE LIMIT LEARN LIMITS 24V GATE 2 OVLD SINGLE BUTTON SWITCHED ACCESSORY POWER 3. Press the “LEARN LIMITS” button again to set the Open position. The “SET CLOSE LIMIT” LED will blink and beep once. 4. Use the “Gate 1” buttons to move Gate 1 to the desired close position. If you have gone beyond the desired closed position you can jog the gate towards the open position by using the opposite Gate 1 button. Repeat if Gate 2 is present using the “Gate 2” buttons. GATE 1 SET OPEN LIMIT SET S C CLO CLOSE L LIMIT LEARN LIMITS GATE 2 FORCE DIAGNOSTIC DIAGNOSTIC SET CLOSE LIMIT LEARN LIMITS SINGLE BUTTON O GATE 1 SET OPEN LIMIT SET S C CL CLOSE L LIMIT LEARN LIMITS GATE 2 SINGLE B O N 1 2 3 4 5 OFF OFF SINGLE NO NO S1 7. Set Save Switch to the ON position. 25 SET CLOSE LIMIT ON ON DUAL NC NC SAVE MAGLOCK MODE EDGE PHOTO LEARN LIMITS GATE 2 FORCE FORCE FORCE 6. Using the single button control on the board, run the gate(s) from the closed position to the open position. This will learn the forces. SET OPEN LIMIT GATE 2 DIAGNOSTIC 5. Press the “LEARN LIMITS” button again to set the Closed position. The “SET CLOSE LIMIT” LED will blink and beep. The limits are now set. GATE 1 GATE 1 SET OPEN LIMIT Step 3: Set Force / Bi-Part / Timer P2 CLOSE EDGE J19 BI-PART DELAY Control J1 Ø14GP 14GPØ89 89ØE Ø14LG 14LGØ89 89ØE Ø14SK 14SKØ89 89ØE OPEN/EGE PHOTO L1 OFF OFF SINGLE NO NO 1 2 3 4 5 S8 LEARN XMITTER 2 O N 1 ON SAVE ON MAGLOCK DUAL MODE EDGE NC PHOTO NC OPEN PHOTO S1 CLOSE PHOTO SET OPEN LIMIT FORCE Control 24V OVLD BIPART DELAY FORCE SWITCHED ACCESSORY POWER TIMER TO CLOSE TIMER TO CLOSE Control BI-PART DELAY FORCE TIMER TO CLOSE Z9 Z8 MIN FORCE CONTROL Set the force control such that the opener will complete a full cycle of gate travel but will reverse off an obstruction without applying an excessive amount of force. OFF MAX BI-PART DELAY Set the BI-PART DELAY to desired setting. The range is 0 to 8 seconds, 0 seconds is OFF. NOTE: Used for Dual Gate installations only. BI-PART DELAY FORCE Minimun Force MAX Maximum Force OFF MAX Your basic installation is now complete. 26 OFF MAX TIMER TO CLOSE ENABLE Set the TIMER TO CLOSE to desired setting. The range is 0 to 180 seconds, 0 seconds is OFF. TIMER TO CLOSE OFF MAX OPTIONAL CONTROL AND SAFETY DEVICES To Add or Reprogram a Remote Control 1. Press and release “LEARN XMITTER” button (LED will light up). 2. Press and hold remote button, the LED will flash, alarm will beep twice and the LED will go out. 3. Repeat steps 1 and 2 until all remote controls are programmed (50 remote controls maximum). NOTE: For highest level of security, we recommend the 315 MHz, Security✚® line of products. Refer to Accessories. R1 LEARN XMITTER Remote Control “LEARN XMITTER” Button P2 CLOSE EDGE J19 J1 Ø14GP 14GPØ89 89ØE Ø14LG 14LGØ89 89ØE Ø14SK 14SKØ89 89ØE OPEN/EGE PHOTO L1 OFF OFF SINGLE NO NO 1 2 3 4 5 S8 LEARN XMITTER 2 O N 1 ON SAVE ON MAGLOCK DUAL MODE NC EDGE NC PHOTO OPEN PHOTO S1 CLOSE PHOTO 24V OVLD To Erase All Codes To deactivate any unwanted remote controls, first erase all codes: Press and hold the “LEARN XMITTER” button on logic board until the learn indicator light goes out (approximately 6 seconds). All previous codes are now erased. Reprogram each remote control or keyless entry you wish to use. SWITCHED ACCESSORY POWER NOTICE: To comply with FCC and or Industry Canada (IC) rules, adjustment or modifications of this receiver and/or transmitter are prohibited, except for changing the code setting or replacing the battery. THERE ARE NO OTHER USER SERVICEABLE PARTS. Tested to Comply with FCC Standards FOR HOME OR OFFICE USE. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. 27 Dip Switch Settings SAVE SWITCH S1-1 This switch (S1-1) is used to save the settings for switches 2 through 5. NOTE: When setting switches, the save switch must be in the off position prior to setting or changing switches for the change to be saved. MAG DELAY ENABLE This switch (S1-2) enables the Maglock feature. On an open command there will be a .5 second delay before the motor starts, to allow the Maglock to release. MODE DUAL/SINGLE This switch (S1-3) sets the mode as Dual or Single (Refer to page 24). SAFETY INPUTS Swing gates allow four safety inputs. A DIP switch is required for determining between N/O and N/C edges and N/O and N/C eyes. EDGE INPUT Set switch (S1-4) to the following settings: N/O Edge (Active Close) = N/O dry contact edge or monitored edge NOTE: Monitored Edges should be set in the N/O position, as the activation condition is shorting the terminals. EYE INPUT This switch (S1-5) differentiates between N/O and N/C dry contact photoelectric eye inputs. NOTE: Pulsing Chamberlain (CPS-L) photoelectric eyes will automatically learn in N/O mode (See Accessories). O N O N OFF OFF SINGLE NO NO O N S1 1 2 3 4 5 1 2 3 4 5 OFF MAG DELAY ON 1 2 3 4 5 SAVE MAGLOCK MODE EDGE PHOTO O N 1 2 3 4 5 ON ON DUAL NC NC 1 2 3 4 5 O N OFF OFF SINGLE NO NO O N SAVE OFF SAVE ON ON MAG DELAY OFF FACTORY DEFAULT SHOWN J1 OFF OFF SINGLE NO NO 1 2 3 4 5 S8 LEARN XMITTER 2 O N 1 ON SAVE ON MAGLOCK DUAL MODE NC EDGE NC PHOTO OPEN PHOTO S1 CLOSE PHOTO GATE1 SET OPEN LIMIT SET CLOSE LIMIT LEARN LIMITS GATE 2 1 2 3 4 5 OPEN/EGE PHOTO O N CLOSE EDGE Ø14GPØ89ØE Ø14LGØ89ØE Ø14SKØ89ØE L1 1 2 3 4 5 P2 J19 24V OVLD SWITCHED ACCESSORY POWER O N OFF OFF SINGLE O N 28 1 2 3 4 5 EYE NO 1 2 3 4 5 OFF OFF SINGLE EDGE NO ON ON DUAL NC ON ON DUAL NC ON ON DUAL NC NC Wire Stop Button (Optional) A jumper wire is factory installed between the stop and common input. Stop (N/C) - Stop only (does not reset alarm). NOTE: Stop jumper is required for normal operation (the Stop LED will be lit except when the control board goes into Sleep Mode). Remove only if remotely mounted Stop button is added. CONTROL INPUTS OPEN SINGLE BUTTON P2 RESET J19 J1 Ø14GPØ89ØE Ø14LGØ89ØE Ø14SKØ89ØE STOP NO L1 C S8 OFF OFF SINGLE NO NO LEARN XMITTER 2 1 2 3 4 5 1 O N NC ON ON DUAL NC NC SAVE MAGLOCK MODE EDGE PHOTO COM S1 BRN COM GRN WHT R223 P1 YEL CLOSE EDGE J19 R2Ø7 BLU NO POWER Z2Ø R227 C Z1 RED K5 OPEN EDGE/ PHOTO GATE 1 L1 R224 GRN 24V Z22 R92 U4 R2 Z9 LEARN XMITTER R1 OPEN PHOTO 10A 32V OVLD 2 ACCESSORY POWER R91 F3 D1Ø CONTROL INPUTS K2 DIAGNOSTIC 24V BLU OPEN GRN SINGLE BUTTON GATE 1 BRN Z12 K1 Q9 SET OPEN LIMIT SET CLOSE LIMIT RESET LEARN LIMITS WHT R9Ø GATE 2 YEL BLU RED COM CONTROL INPUTS TIMER TO SINGLE BUTTON CLOSE FORCE R1Ø1 STOP TIMER RUNNING COM OPEN POWER R1ØØ SINGLE BUTTON F4 GATE 2 RESET ACCESSORY OVLD 10A 32V STOP K4 OFF MAX COM F5 COM D21 POWER R35 D9 K3 D8 C12 D27 Z3 F7 Z4 Q22 C13 D22 LOOP INPUTS C4 SHADOW U3 INTERRUPT C11 CHGR OVLD POWER D15 C2 R196 COM F6 24 VAC/ SOLAR INPUT SWITCHED ACCESSORY POWER F2 MOV2 R9 MOV1 F1 20A 32V D4 D1 C64 JMPR2 JMPR1 D2 U2 FUSE OPEN BATT 2 BATT 1 D6 DB1 29 OPEN Opens only or reverses a closing gate. SBC (SINGLE BUTTON CONTROL) INPUT This input will command the gate to OPEN / STOP / CLOSE / STOP in sequence. RESET CONTROL INPUT The control box has a factory installed internal reset button. These terminals are intended for use with a single reset button that is installed within line of sight of the gate. This input functions to reset the alarms. This input will NOT stop the gate. NOTE: All Control Inputs must be Normally Open (N.O.) dry contact type. CONTROL INPUTS OPEN OPEN COMMON SINGLE BUTTON RESET AND/OR STOP COM COM POWER SINGLE BUTTON P2 J19 J1 Ø14GPØ89ØE Ø14LGØ89ØE Ø14SKØ89ØE NO L1 COMMON C S8 OFF OFF SINGLE NO NO LEARN XMITTER 2 1 2 3 4 5 1 O N NC ON SAVE ON MAGLOCK DUAL MODE NC EDGE PHOTO NC S1 BRN AND/OR GRN WHT R223 P1 YEL CLOSE EDGE J19 R2Ø7 BLU NO Z2Ø R227 C Z1 RED K5 OPEN EDGE/ PHOTO GATE 1 L1 R224 GRN 24V Z22 R92 U4 R2 Z9 LEARN XMITTER R1 OPEN PHOTO 10A 32V 2 ACCESSORY POWER R91 F3 D1Ø CONTROL INPUTS K2 DIAGNOSTIC 24V BLU GRN OPEN Z12 SINGLE BUTTON GATE 1 BRN SET K1 Q9 OPEN LIMIT SET CLOSE LIMIT RESET LEARN LIMITS COMMON WHT R9Ø GATE 2 YEL BLU RED STOP TIMER RUNNING COM CONTROL INPUTS TIMER TO SINGLE BUTTON CLOSE FORCE R1Ø1 COM OPEN POWER R1ØØ SINGLE BUTTON F4 GATE 2 RESET ACCESSORY OVLD 10A 32V STOP K4 OFF MAX COM F5 RESET COM D21 POWER R35 D9 K3 D8 C12 D27 Z3 F7 Z4 Q22 C13 D22 LOOP INPUTS C4 SHADOW U3 INTERRUPT C11 CHGR OVLD POWER D15 C2 R196 COM F6 24 VAC/ SOLAR INPUT F2 MOV2 R9 MOV1 D4 D1 C64 JMPR2 JMPR1 D2 U2 FUSE OPEN BATT 2 BATT 1 D6 DB1 F1 20A 32V OPEN INPUT AND EXIT LOOP These terminals are intended for use as a general open control. Accessories such as telephone entry systems, radio receivers (open only applications), exit loop detectors, keypads and 7-day timers may be wired to this input. PR ESE NC RE E LAY 2 SE NS FRE EQQ EXIT LOOP 30 A DE MA IN US Loop Inputs Shadow Loop Input Terminal and Common This input protects cars by preventing the gate from moving off of the open or close limit when the shadow loop input is active. NOTE: Shadow Loop is disabled when gate is moving. Interrupt Loop Input Terminal and Common This input functions to reverse a closing gate to the open limit. Latching this input will reset the timer to close. LOOP INPUTS NORMALLY OPEN SHADOW LOOP SHADOW NORMALLY OPEN INTERRUPT LOOP INTERRUPT COMMON LOOP COM CHGR OVLD F1 20A 32V FUSE OPEN BATT 2 BATT 1 P2 J19 Ø14GPØ89ØE Ø14LGØ89ØE Ø14SKØ89ØE J1 PR ESE NC RE E LAY 2 NO L1 C S8 OFF OFF SINGLE NO NO LEARN XMITTER 2 1 2 3 4 5 1 O N NC ON SAVE ON MAGLOCK DUAL MODE NC EDGE NC PHOTO SE NS S1 BRN GRN WHT R223 P1 YEL CLOSE EDGE J19 FRRE R2Ø7 BLU NO EQQ Z2Ø R227 C Z1 RED K5 OPEN EDGE/ PHOTO GATE 1 R224 GRN DE IN US Z9 LEARN XMITTER R1 MA 24V Z22 R92 U4 R2 OPEN PHOTO 10A 32V 2 ACCESSORY POWER R91 F3 D1Ø CONTROL INPUTS K2 DIAGNOSTIC 24V BLU A L1 OPEN GRN Z12 SINGLE BUTTON GATE 1 BRN K1 Q9 SET OPEN LIMIT SET CLOSE LIMIT RESET LEARN LIMITS WHT R9Ø GATE 2 YEL BLU R1Ø1 RED R1ØØ STOP TIMER RUNNING COM CONTROL INPUTS TIMER TO SINGLE BUTTON CLOSE FORCE COM OPEN POWER SINGLE BUTTON F4 GATE 2 NOTE: Additional enclosure required. Refer to loop detector manufacturer instructions for connections. RESET ACCESSORY OVLD 10A 32V LOOP INPUTS STOP K4 OFF MAX COM F5 COM D21 POWER R35 D9 K3 D8 C12 D27 Z3 F7 Z4 Q22 C13 D22 LOOP INPUTS C4 COM SHADOW U3 INTERRUPT C11 CHGR OVLD POWER D15 C2 R196 COM F6 24 VAC/ SOLAR INPUT F2 MOV2 R9 MOV1 F1 20A 32V D4 D1 C64 JMPR2 JMPR1 D2 U2 FUSE OPEN BATT 2 BATT 1 D6 DB1 31 Photo/Edge Inputs (P6-7-8 and 9) Terminal P6 – Close Safety Edge This input will reverse a closing gate. It will disable the Timer-to-Close if that feature has been enabled. Activating this input while the gate is opening will have no effect. Order part number LA400-BOX to enclose safety electronics. Terminal P8 – Open Safety Edge/Photo Eye (Entrapment) If an Open Edge device or a Retro-Reflective Photo Eye has been connected to Terminal P8, then this input will reverse an opening gate for 2 seconds then stop. Activating this input with an Open Edge device or a Retro-Reflective Photo Eye connected to Terminal P8 while the gate is closing will have no effect. If a Chamberlain Pulsing Photo Eye (See Accessories) has been connected to Terminal P8, then this input will pause an opening gate until the obstruction has been removed. Upon removing the obstruction, the gate will continue to open. Activating this input with a Chamberlain Pulsing Photo Eye (See Accessories) connected to Terminal P8 while the gate is closing will have no effect. Terminal P7 – Open Safety Photo Eye (Entrapment) This input will pause an opening gate until the obstruction has been removed. Upon removing the obstruction, the gate will continue to open. Activating this input while the gate is closing will have no effect. Terminal P9 – Close Safety Photo Eye This input will reverse a closing gate to the open limit. Activating this input while the gate is opening will have no effect. The Timer-to-Close will reactivate at the open limit. CLOSE EDGE P2 CLOSE EDGE J19 J1 Ø14GPØ89ØE Ø14LGØ89ØE Ø14SKØ89ØE OPEN EDGE PHOTO OPEN EDGE/ PHOTO NO L1 C S8 OFF OFF SINGLE NO NO LEARN XMITTER 2 1 2 3 4 5 1 O N NC ON SAVE ON MAGLOCK DUAL MODE NC EDGE NC PHOTO OPEN PHOTO S1 GRN WHT CLOSE PHOTO R223 W UE N CLOSE EDGE J19 R2Ø7 BLU Z2Ø R227 C Z1 RED K5 OPEN EDGE/ PHOTO GATE 1 UE L1 24V R224 GRN Z22 R92 U4 R2 Z9 LEARN XMITTER R1 OPEN PHOTO 10A 32V OVLD 2 ACCESSORY POWER R91 F3 D1Ø DIAGNOSTIC OPEN GRN SINGLE BUTTON GATE 1 BRN Z12 SWITCHED ACCESSORY POWER CONTROL INPUTS K2 24V BLU BL P1 YEL NO K1 Q9 SET OPEN LIMIT SET CLOSE LIMIT RESET LEARN LIMITS WHT R9Ø GATE 2 YEL BLU RED STOP TIMER RUNNING COM CONTROL INPUTS TIMER TO SINGLE BUTTON CLOSE FORCE R1Ø1 COM OPEN POWER R1ØØ SINGLE BUTTON F4 GATE 2 RESET ACCESSORY OVLD 10A 32V LOOP INPUTS STOP K4 OFF MAX COM F5 COM D21 POWER R35 D8 C12 D27 Z3 F7 Z4 Q22 C13 D22 LOOP INPUTS C4 COM SHADOW U3 R196 BROWN INTERRUPT C11 CHGR OVLD POWER D15 C2 OPEN PHOTO D9 K3 COM F6 24 VAC/ SOLAR INPUT F2 MOV2 R9 MOV1 F1 20A 32V D4 D1 C64 JMPR2 JMPR1 D2 U2 FUSE OPEN BATT 2 BLUE BATT 1 D6 DB1 BLUE BROWN CLOSE PHOTO BROWN BLUE BLUE BROWN 32 O BR O BR BL BRN WN Safety Accessories for Secondary Entrapment Protection The following devices are acceptable for Safety Accessories for secondary entrapment protection. These devices have been tested with the LA400 to meet the requirements of UL325 and UL991. PHOTO-ELECTRIC CONTROLS MODEL DESCRIPTION VOLTAGE CPS-LN4 Emitter, receiver and mounting brackets - 30' (9 m) Ranges +24Vdc CPS-RN4 Emitter with reflector and mounting brackets +24Vdc SENSING EDGES MODEL DESCRIPTION G65MG0204 Miller MG020 2-wire electric edge for gates. Sensitized on three sides. (Requires mounting channel. PIN:G65ME120C5) G65MG0205 Miller MG020 2-wire electric edge for gates. Sensitized on three sides. (Requires mounting channel. PIN:G65ME120C5) G65MGR205 Miller MGR20 2-wire electric edge in 5' (1.5 m) lengths for 2" (5 cm) round post. G65MGS205 Miller MGR20 2-wire electric edge in 5' (1.5 m) lengths for 2" (5 cm) square post. Maglock When enabled, the maglock output is activated (energized) while the gate is in motion. Fault Alarm P2 R223 P1 CLOSE EDGE J19 Ø14GPØ89ØE Ø14LGØ89ØE Ø14SKØ89ØE K6 ALARM J1 NO R2Ø7 Z2Ø R227 C K5 MAGLOCK * OPEN EDGE/ PHOTO NO Solenoid Lock (optional) L1 J18 R224 C S8 LEARN XMITTER 10A 32V 2 GATE 1 1 2 3 4 5 OFF OFF SINGLE NO NO R2 R1 O N 1 NC Z1 ON ON DUAL NC NC Z22 R92 U4 SAVE MAGLOCK MODE EDGE PHOTO Z9 OPEN PHOTO S1 F3 R91 BRN D1Ø GRN * R94 K2 Z8 WHT Maglock (optional) CLOSE PHOTO DIAGNOSTIC YEL R93 BLU GATE 1 RED K1 Q9 Z12 SET OPEN LIMIT SET CLOSE LIMIT R9Ø ACCESSORY POWER GATE 2 24V BRN TIMER RUNNING COM OVLD OVLD SWITCHED ACCESSORY POWER CONTROL INPUTS TIMER TO SINGLE BUTTON CLOSE R1ØØ OPEN SINGLE BUTTON F4 GRN RESET ACCESSORY OVLD 10A 32V WHT power supply or 300MA with 24Vac power supply. Accessory Power 24V BIPART DELAY FORCE R1Ø1 * Provides 24VDC. Do not exceed 500MA with 115Vac LEARN LIMITS STOP K4 YEL MIN MAX OFF MAX OFF MAX COM F5 BLU COM D21 RED D9 D8 GATE 2 POWER R35 K3 C12 D27 Z3 F7 Z4 Q22 C13 D22 LOOP INPUTS C4 SHADOW U3 INTERRUPT C11 C2 R196 F6 24 VAC/ SOLAR INPUT J4 COM CHGR OVLD D15 R4 F2 MOV2 R9 MOV1 D4 D1 C64 JMPR1 JMPR2 D2 U2 FUSE OPEN BATT 2 BATT 1 D6 DB1 F1 20A 32V Auxiliary Output Power for Optional Devices (2) +24Vdc Outputs have been provided for optional devices 33 OPERATION Reset Button The reset button is located on the outside of the control box and serves several functions. Obstruction/Entrapment Reset If gate encounters two consecutive obstructions, the control system will go into an entrapment alarm condition and the control board will require resetting. This is achieved by simply pushing the “Reset Button” located on the outside of the control box. Party Mode (Timer Defeat - Hold Open) Reset Control Box RESET When the “Timer to Close” feature is activated for normal daily operation and Button you wish to leave the gate(s) in the open postion for any extended period of time you can activate the “Party Mode” by pushing the “Reset Button” located on the outside of the electrical box. To exit this mode, simply give the gate(s) a command to run by using the remote control. This will close the gate(s) and return the operator to normal operation. RESET Remote Control Once the remote control has been programmed unit will operate as follows: When gate is in the closed position, activation of the remote control button will open the gate. During the open cycle another activation of the remote control will stop the gate and the next activation of the remote control will close the gate. When the gate is in the open position, activation of the remote control button will close the gate. During the close cycle another activation of the remote control will stop the gate and the next activation of the remote control will open the gate. Manual Release The drive mechanism can be released. The gate can then be operated manually (power failure). With a new drive mechanism, the release action may sometimes feel stiff/jerky. This is normal and has no effect on function. Release 1. Insert the key into the lock. 2. Turn the key counter-clockwise 180°. 3. Turn the release lever counter-clockwise 180°. 4. Done! Operator is in manual mode. Engage 1. Turn the release lever clockwise 180°. This engages the motor. 2. Turn the key clockwise 180°. This locks the release lever. 3. Remove the key and store in a safe place. 4. Done! Back in automatic mode. 34 MAINTENANCE NING WARNING IMPORTANT SAFETY INSTRUCTIONS ION SSEMENT WARNING To reduce the risk of SEVERE INJURY or DEATH: 1. READ AND FOLLOW ALL INSTRUCTIONS. 2. NEVER let children operate or play with gate controls. Keep the remote control away from children. 3. ALWAYS keep people and objects away from the gate. NO ONE SHOULD CROSS THE PATH OF THE MOVING GATE. 4. Test the gate operator monthly. The gate MUST reverse on contact with a rigid object or stop when an object activates the non-contact sensors. After adjusting the force or the limit of travel, retest the gate operator. Failure to adjust and retest the gate operator properly can increase the risk of INJURY or DEATH. AVERTISSEMENT 10. SAVE THESE INSTRUCTIONS. AVERTISSEMENT TION UCIÓN CHECK AT LEAST ONCE EVERY DESCRIPTION TASK MONTH External entrapment protection systems Check for proper operation ● Gate warning signs Make sure they are present Manual disconnect Check and operate Gate Inspect for wear or damage ● ● Accessories Check all for proper operation ● Electrical Inspect all wire connections ● Frame bolts Check for tightness ● Total unit Inspect for wear or damage 3 MONTHS 6 MONTHS 12 MONTHS ● ADVERTENCIA Complete Check Out TENCIA 5. Use the emergency release ONLY when the gate is not moving. 6. KEEP GATES PROPERLY MAINTAINED. Read the owner’s manual. Have a qualified service person make repairs to gate hardware. 7. The entrance is for vehicles ONLY. Pedestrians MUST use separate entrance. 8. Disconnect ALL power BEFORE performing ANY maintenance. 9. ALL maintenance MUST be performed by a LiftMaster professional. WARNING ● CAUTION ADVERTENCIA To reduce the risk of FIRE or INJURY to persons, use ONLY LiftMaster part #K74-30762 for replacement batteries. NOTES: 1. Disconnect power before servicing. 2. Severe or high cycle usage will require more frequent maintenance checks. 3. Inspection and service should always be performed anytime a malfunction is observed or suspected. 4. When servicing, please do some “house cleaning” of the operator and the area around the operator. Pick up any debris in the area. Clean the operator as needed. 5. It is suggested that while at the site voltage readings be taken at the operator. Using a Digital Voltmeter, verify that the incoming voltage to the operator it is within ten percent of the operators rating. AVERTISSEMENT 35 ATTENTION WARNING WARNING CAUTION WARNING To avoid SERIOUS personal INJURY or DEATH from electrocution, DISCONNECT electrical power to operator BEFORE proceeding. To reduce the risk of FIRE or INJURY to persons, use ONLY LiftMaster part #K74-30762 for replacement batteries. Battery Replacement 1. Disconnect power to operator. 2. Open the control box cover. 3. Remove all quick connect terminals in use to the control board. Remember location of all wire connections for reinstallation. 4. Remove control board and mounting plate. 5. Disconnect terminals leads to both batteries. 6. Replace both batteries and connect red wires to the positive (+) terminals (red). Connect black wires to the negative (-) terminals (black). 7. Install control board and mounting plate. 8. Reconnect all quick connect terminals to the control board. 9. Close cover of control box. 10. Reconnect power to operator. AVERTISSEMENT AVERTISSEMENT AVERTISSEMENT ATTENTION ADVERTENCIA ADVERTENCIA Batteries Control Board and Mounting Plate ADVERTENCIA PRECAUCIÓN 36 BASIC CONTROL BOARD LAYOUT 19 20 26 17 1 P2 R223 P1 CLOSE EDGE J19 Ø14GPØ89ØE Ø14LGØ89ØE Ø14SKØ89ØE K6 ALARM 14 J1 NO Z2Ø R227 C K5 MAGLOCK 13 OPEN EDGE/ PHOTO NO L1 J18 S8 OFF OFF SINGLE NO NO LEARN XMITTER R1 10A 32V 2 GATE 1 1 2 3 4 5 Z1 O N 1 R2 ON ON DUAL NC NC Z22 R92 U4 SAVE MAGLOCK MODE EDGE PHOTO Z9 OPEN PHOTO S1 F3 3 R224 C NC 18 2 R2Ø7 4 R91 BRN D1Ø GRN R94 K2 Z8 WHT 12 CLOSE PHOTO DIAGNOSTIC YEL 5 R93 BLU GATE 1 RED K1 Q9 Z12 SET OPEN LIMIT SET CLOSE LIMIT R9Ø ACCESSORY POWER 11* TIMER RUNNING BRN BIPART DELAY FORCE R1Ø1 6* 24V GATE 2 24V COM OVLD OVLD SWITCHED ACCESSORY POWER CONTROL INPUTS TIMER TO SINGLE BUTTON CLOSE R1ØØ OPEN WHT 7 RESET ACCESSORY OVLD 10A 32V 22 SINGLE BUTTON F4 GRN 10 LEARN LIMITS STOP K4 YEL MIN MAX OFF MAX OFF MAX COM F5 BLU COM D21 RED D9 D8 GATE 2 POWER R35 K3 C12 D27 Z3 F7 Z4 Q22 C13 D22 LOOP INPUTS C4 SHADOW U3 R4 21 F6 24 VAC/ SOLAR INPUT J4 F2 MOV2 R9 MOV1 D1 C64 JMPR2 JMPR1 BATT 2 BATT 1 D6 DESCRIPTION Connector P1 Connector P6 Connector P8 Connector P7 Connector P9 Connector P12 Connector P10 Connector P11 Connector P5 Connector P16 Connector P13 Connector P17 Connector P14 FUSE OPEN D2 U2 9 F1 20A 32V D4 DB1 ITEM 1 2 3 4 5 6 7 8 9 10 11 12 13 COM CHGR OVLD R196 C2 8 INTERRUPT C11 D15 23 FUNCTION Antenna Input Close Edge Open Edge/Photo Open Photo Close Photo Switched Accessory Power* Control Inputs Loop Inputs 24Vac/Solar Input Gate 2 Accessory Power* Gate 1 Maglock/Solenoid 24 ITEM 14 15 16 17 18 19 20 21 22 23 24 25 26 *See page 40 for max current draw 37 25 DESCRIPTION Connector P15 Connector Connector Dip Switch Pushbutton Pushbuttons Pushbutton Pushbuttons Pushbutton Potentiometer Potentiometer Potentiometer Connector 16 15 FUNCTION Alarm Battery 1 Battery 2 S1 Learn Xmitter - Program Remote Gate 1 - Jog Learn Limit Learn Limits Gate 2 - Jog Learn Limit Single Button Force Bi-Part Delay Timer to Close Receiver WIRING DIAGRAM 1. ANTENNA INPUT 2. CLOSE EDGE 3. OPEN EDGE/PHOTO EYE 4. OPEN PHOTO EYE 5. CLOSE PHOTO EYE 6. 24VDC ACCESSORY OUTPUT 7. CONTROL INPUTS/EXIT LOOP 8. LOOP INPUTS, SAFETY/SHADOW 9. TRANSFORMER INPUT/SOLAR INPUT (OPTIONAL) 10. SECOND - OPERATOR ARM CONNECTION 11. 24VDC ACCESSORY OUTPUT 12. MASTER OPERATOR ARM CONNECTION Fault Alarm ANTENNA CONNECTION 1 Solenoid Lock (optional) P2 R223 P1 14 J1 K5 MAGLOCK 17 NO J18 LEARN XMITTER 10A 32V 2 GATE 1 SET CLOSE LIMIT SET OPEN LIMIT R9ÿ BRN R1ÿÿ GRN F4 21 YEL FORCE 24 BIPART DELAY COM OVLD OVLD CONTROL INPUTS TIMER TO SINGLE BUTTON CLOSE OPEN (EXIT LOOP) OPEN SINGLE BUTTON RESET STOP RESET MAX OFF MAX OFF MAX 25 STOP COMMON (+24VDC) COMMON (+24VDC) COM COM D21 RED C12 D27 Z3 F7 Z4 Q22 7 D9 D8 GATE 2 10 POWER R35 K3 C13 D22 LOOP INPUTS C4 SHADOW SHADOW LOOP U3 F2 MOV2 R9 MOV1 JMPR2 JMPR1 D2 U2 GROUND BLACK BLUE 9 YELLOW NOTE: Yellow/green wire must be disconnected when earth ground rod is installed. BATT 2 8 BATT 1 D6 DB1 FUSE OPEN 16 15 RED YELLOW/GREEN F1 20A 32V D4 D1 C64 BLACK 24 VAC/ SOLAR INPUT J4 F6 RED (OR OPTIONAL EARTH GROUND WIRE) COMMON (+24VDC) COM CHGR OVLD R196 C2 INTERRUPT LOOP INTERRUPT C11 D15 R4 PHOTO SWITCHED ACCESSORY POWER SINGLE BUTTON MIN OR 24VDC OUTPUT SWITCHED OFF IN LOW POWER MODE F5 BLU RED CPS-LN4 6 24V 22 TIMER RUNNING 23 K4 PHOTO 5 PHOTO 20 ACCESSORY OVLD 10A 32V WHT OR OR LEARN LIMITS GATE 2 R1ÿ 1 YE L B LU GATE 2 CLOSE PHOTO GATE 1 K1 Q9 24V W HT PHOTO R93 ACCESSORY POWER GRN CPS-LN4 4 OR 19 BLU BRN Z9 OPEN PHOTO Z8 DIAGNOSTIC Z12 EDGE EDGE Z22 R92 U4 R91 RED 12 11 SAVE MAGLOCK MODE EDGE PHOTO OR R94 YEL RED ON ON DUAL NC NC 18 K2 WHT YE L GATE 1 D1ÿ GRN B LU CPS-LN4 OR R224 S1 F3 BRN GRN 1 2 3 4 5 OFF OFF SINGLE NO NO S8 R2 R1 O N 1 NC Z1 EDGE 3 OPEN EDGE/ PHOTO L1 C W HT EDGE Z2ÿ R227 C Maglock (optional) BRN OR R2ÿ 7 NO 13 2 CLOSE EDGE J19 K6 ALARM 13. MAGLOCK/SOLENOID OUTPUT 14. FAULT ALARM OUTPUT 15. BATTERY INPUT #1 16. BATTERY INPUT #2 17. DIP SWITCH, S1 18. LEARN XMITTER 19. MASTER GATE JOG 20. LIMIT SET 21. SECOND GATE JOG 22. SBC (SINGLE BUTTON CONTROL) 23. FORCE SET 24. BIPART DELAY SET 25. TIMER TO CLOSE SET NOTE: Batteries must be connected to operate. OR To protect against fire and electrocution: • DISCONNECT power and battery BEFORE installing or servicing operator. • Replace ONLY with fuse of same type and rating. 38 TROUBLESHOOTING FAULT POSSIBLE CAUSE FIX OPERATOR IS DEAD No LED lights are on. 1) No voltage to board. 2) Bad control board. ➤ Battery must be >23V, AC or Solar needs to be connected. ➤ Replace control board. OPERATOR DOES NOT RUN Unit does not respond to any commands. 1) 2) 3) 4) Low/disconnected battery. Remote not programmed. STOP connection loose/disconnected. Constant Open Command (Check LED’s). 5) Limits not programmed correctly. 6) Bad control board. ➤ Voltage must be >23V at battery connection. ➤ See Programming Remote instructions. ➤ Check STOP connections. ➤ Clear all Open/Safety devices from obstruction. MOTOR DOES NOT RUN Relays “click” when radio or SBC signal is given, but the operator does not move. 1) Low Battery. 2) Cable wiring between control box and operator arm disconnected or loose. 3) Batteries not connected. 4) Bad motor. 5) Bad control board. ➤ Voltage must be >23V at battery connection. ➤ Check wiring on control board to arm, replace wire if needed. GATE STOPS AND REVERSES (Force Reversal) 1) 2) 3) 4) ➤ Clear gate from obstruction. ➤ See Force Adjustment section. ➤ Service/replace gate hardware. ➤ See Installation section of operator arm. RPM REVERSAL 1) Obstructed Arm (bottoms out). 2) Bad RPM Sensor. 3) Too much mA pulled off board. ➤ Check for obstruction on arm, verify arm is not bottomed out. ➤ Replace arm. ➤ Move accessories to separate power source. Use reference chart on next page to determine max mA draw for circuit board. GATE STOPS Gate starts to run, then stops and does not reverse. 1) Low battery. 2) Gate met an obstruction. ➤ Voltage must be >23V at battery connection. ➤ Clear gate from obstruction. GATE OPENS BUT DOES NOT CLOSE 1) Constant Open Command (Check LED’s). 2) Timer to Close not set. 3) Accessory device wired to Open Only command. ➤ Clear all Open/Safety devices from obstruction. Audible beeps (3 times) when command is given. 1) Battery Low >23.5V ➤ Operator will resume normal operation once battery voltage reaches 24V. GATE’S DO NOT OPEN/CLOSE IN SYNC 1) Bi-Part Delay not set. 2) Limits not programmed correctly. 3) Incorrect Arm Installation ➤ See Bi-Part Delay section for adjustment instructions. ➤ See Programming Limits section for instructions. ➤ See Installation section for instructions. GATE DOES NOT AUTOMATICALLY CLOSE Auto Close Timer not closing gate. 1) Timer to Close not turned on. 2) Gate has opened on Obstruction Reversal. 3) Operator in “Party Mode”. 4) Constant Open Command (Check LED’s). ➤ See Timer to Close section for instructions. ➤ Check DIAG code, clear obstruction. ACCESSORY DEVICE NOT WORKING PROPERLY 1) 2) 3) 4) ➤ Check for proper installation of accessory. ➤ Turn applicable switches on. ➤ Check proper installation of wires. ➤ Replace accessory device. Gate met an obstruction. Force set too low. Bad gate hardware. Incorrect Arm installation. Not installed properly. Enabling Switch not turned on. Loose/disconnected wires. Bad accessory device ➤ See Programming Limits instructions. ➤ Replace control board. ➤ Connect batteries. ➤ Replace motor. ➤ Replace control board. ➤ See Timer to Close section for adjustment instructions. ➤ Rewire desired accessory device to Single Button Input. ➤ Use Remote/SBC to resume normal operation. ➤ Clear all Open/Safety devices from obstruction. 39 MAX CURRENT DRAW 115 power to control box - 500mA accessory power, 150mA switched accessory power. 24V power to control box depending on wire gauge and distance - 300mA accessory power, 75mA switched accessory power. Solar power to control box - 0mA accessory, 50mA switched accessory power. DIAGNOSTIC CODES # OF BLINKS 1 2 3 4 5 6 7 8 9 10 MEANING No Stop Switch Connected Gate 1 Arm Disengaged Gate 2 Arm Disengaged Both Gate Arms Disengaged RPM Reversal Force Reversal Processor Reset ROM Check Failed RAM Check Failed EEPROM Check Failed - Reset Limits 40 REPAIR PARTS Refer to the parts lists below for replacement parts available for your operator. If optional modifications and/or accessories are included with your operator, certain components may be added or removed from these lists. CONTROL BOX LA400-CONT ITEM 1 2 3 4 5 6 7 8 Not Shown PART # K001A6039 K75-15480 DESCRIPTION QTY Control Board 1 Control Box & Cover with Gasket 1 Control Board Bracket 1 Reset Switch 1 Antenna 1 Battery 2 Transformer 1 Alarm 1 ATC Fuse Kit Includes 20 Amp (1), 15 Amp (2) 390 MHz Receiver Module 315 MHz Receiver Module K75-30764 K23-19380 K74-19499 K74-30762 K74-30763 K76-19446 K74-30941 K001A5747-2 K001A5747 8 2 7 3 4 6 1 5 41 ACTUATOR ARM KITS ITEM 1 2 3 4 Not Shown PART # DESCRIPTION 41ASWG-442SA 41ASWG-438SA 41ASWG-0014SA 41ASWG-489 41ASWG-0119 K77-19130 Release Lever Motor with Limit Switch Harness Rear Connector Cable 24V with Connector Release Key Hardware Bag Complete With: Gate bracket, Post bracket, Extension bracket and Hardware 2 1 3 4 42 QTY 1 1 1 1 1 1 LA400 SWING GATE ACCESSORIES Push to Open Bracket Used to allow the gate operator to push the gate open. 50-19503 SOLKIT12V OPEN OPEN 377LM SOLKIT12V (Single Panel) SOLKIT12V-2P (Two Panels): Kit contains: Battery management module, outdoor battery case (battery not included), solar panel(s). When power is not close by, solar may be the right option. For more information, please contact customer service or see pre-sale solar application guide. SECURITY✚® Keyless Entry : Enables homeowner to operate gate by entering a password on a specially designed keyboard. Also can add a temporary password for visitors or service persons. This temporary password can be limited to a programmable number of hours or entries. LM202 Vehicle Detecting Driveway Probe: One piece outdoor buried vehicle motion detector with sensing probe is housed in a small relay type housing. Provides for free exit. GC824-12 Gate Solenoid Lock: Heavy all steel construction. Failsafe operation keeps gate locked if power is lost. Can be welded onto gate or post. 24Vdc operation, solenoid-activated release. Can be released in case of an emergency. Requires separate power supply (Model ARMPS). GC838 Magnetic Gate Lock: Incredible 1,200 Lb. holding force. Operates on 12 or 24Vdc. Low power consumption. Universal mounting holes for ease of installation. Automatically releases when power is lost. Requires separate power supply (Model ARMPS). 50-19509 6" Post Mounting Kit for control box 50-19511 4" Post Mounting Kit for control box 50-19512 2 1/2" Post Mounting Kit for control box GCPSN4 Commercial Protector System®: Maximum range is 45' 24V. Includes mounting hardware and electrical interface box. CPS-LN4 Commercial Protector System® (Direct Connect): Maximum range is 45' 24V. Includes mounting hardware. OPEN 02101 OPEN OPEN OPEN 1-Button Station: Steel enclosure wired station will allow for a Open, Close, Stop command of the gate. OPEN 370LM 3-Button Mini-Remote Control with SECURITY✚® : With key ring and fastening strip. 373LM 3-Button SECURITY✚® Remote Control : Includes visor clip. 86LM OPEN Remote Antenna Mounting Kit: Kit contains antenna bracket and 15' (4.6 m) of cable. Recommended for increasing the effective range of remote controls. 43 WARRANTY POLICY AND SERVICE LIFTMASTER® TWO YEAR LIMITED WARRANTY The Chamberlain Group, Inc. warrants to the first purchaser of this product, for the structure in which this product is originally installed, that it is free from defect in materials and/or workmanship for a period of two years from the date of purchase. The proper operation of this product is dependent on your compliance with the instructions regarding installation, operation, maintenance and testing. Failure to comply strictly with those instructions will void this limited warranty in its entirety. If, during the limited warranty period, this product appears to contain a defect covered by this limited warranty, call 1-800-528-2806, toll free, before dismantling this product. Then send this product, pre-paid and insured, to our service center for warranty repair. You will be advised of shipping instructions when you call. Please include a brief description of the problem and a dated proof-of-purchase receipt with any product returned for warranty repair. Products returned to Seller for warranty repair, which upon receipt by Seller are confirmed to be defective and covered by this limited warranty, will be repaired or replaced (at Seller’s sole option) at no cost to you and returned pre-paid. Defective parts will be repaired or replaced with new or factory-rebuilt parts at Seller’s sole option. ALL IMPLIED WARRANTIES FOR THE PRODUCT, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED IN DURATION TO THE TWO YEAR LIMITED WARRANTY PERIOD SET FORTH ABOVE, AND NO IMPLIED WARRANTIES WILL EXIST OR APPLY AFTER SUCH PERIOD. Some States do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. THIS LIMITED WARRANTY DOES NOT COVER NON-DEFECT DAMAGE, DAMAGE CAUSED BY IMPROPER INSTALLATION, OPERATION OR CARE (INCLUDING, BUT NOT LIMITED TO ABUSE, MISUSE, FAILURE TO PROVIDE REASONABLE AND NECESSARY MAINTENANCE, UNAUTHORIZED REPAIRS OR ANY ALTERATIONS TO THIS PRODUCT), LABOR CHARGES FOR REINSTALLING A REPAIRED OR REPLACED UNIT, OR REPLACEMENT OF BATTERIES. THIS LIMITED WARRANTY DOES NOT COVER ANY PROBLEMS WITH, OR RELATING TO, THE GARAGE DOOR OR GARAGE DOOR HARDWARE, INCLUDING BUT NOT LIMITED TO THE DOOR SPRINGS, DOOR ROLLERS, DOOR ALIGNMENT OR HINGES. THIS LIMITED WARRANTY ALSO DOES NOT COVER ANY PROBLEMS CAUSED BY INTERFERENCE. ANY SERVICE CALL THAT DETERMINES THE PROBLEM HAS BEEN CAUSED BY ANY OF THESE ITEMS COULD RESULT IN A FEE TO YOU. UNDER NO CIRCUMSTANCES SHALL SELLER BE LIABLE FOR CONSEQUENTIAL, INCIDENTAL OR SPECIAL DAMAGES ARISING IN CONNECTION WITH USE, OR INABILITY TO USE, THIS PRODUCT. IN NO EVENT SHALL SELLER’S LIABILITY FOR BREACH OF WARRANTY, BREACH OF CONTRACT, NEGLIGENCE OR STRICT LIABILITY EXCEED THE COST OF THE PRODUCT COVERED HEREBY. NO PERSON IS AUTHORIZED TO ASSUME FOR US ANY OTHER LIABILITY IN CONNECTION WITH THE SALE OF THIS PRODUCT. Some states do not allow the exclusion or limitation of consequential, incidental or special damages, so the above limitation or exclusion may not apply to you. This limited warranty gives you specific legal rights, and you may also have other rights which vary from state to state. HOW TO ORDER REPAIR PARTS OUR LARGE SERVICE ORGANIZATION SPANS AMERICA FOR INSTALLATION AND SERVICE INFORMATION, CALL OUR TOLL FREE NUMBER 1-800-528-2806 www.liftmaster.com WHEN ORDERING REPAIR PARTS PLEASE SUPPLY THE FOLLOWING INFORMATION: PART NUMBER DESCRIPTION MODEL NUMBER ADDRESS ORDER TO: THE CHAMBERLAIN GROUP, INC. Technical Support Group 6050 S. Country Club Road Tucson, AZ 85706 01-19244E © 2008, The Chamberlain Group, Inc. All Rights Reserved