dw-4000 - vertical installation

Transcription

dw-4000 - vertical installation
DW-4000 - VERTICAL INSTALLATION
AR-PJ-01-DW4V
AR-PJ-02-DW4V
AR-PJ-03-DW4V
AR-PJ-04-DW4V
AR-PJ-05-DW4V
AR-BS-01-DW4V
AR-BS-02-DW4V
AR-OC-01-DW4V
AR-IC-01-DW4V
AR-IC-02-DW4V
AR-FO-01-DW4V
AR-FO-02-DW4V
AR-FO-03-DW4V
AR-FO-04-DW4V
AR-FO-05-DW4V
AR-FO-06-DW4V
AR-FO-07-DW4V
AR-FO-08-DW4V
2" VERTICAL PANEL JOINT
3" VERTICAL JOINT
PANELS OVER STRUCTURAL STEEL
PANELS OVER METAL STUDS
PANELS OVER CONCRETE
BASE DETAIL - OVERHANG
BASE DETAIL - FLUSH
OUTSIDE CORNER W/ 2-PC EXTRUSION
INSIDE CORNER WITH 1-PC EXTRUSION
ENDWALL W/ 2-PC EXTRUSION
SILL WITH EXTRUSION
HEAD WITH EXTRUSION
JAMB WITH EXTRUSION
F.O. TWO PIECE HEAD
F.O. HEAD WITH DRIP EDGE
F.O. TWO PIECE JAMB
F.O. ONE PIECE JAMB
F.O. ONE PIECE SILL
INDEX SHEET
DW-4000 - VERTICAL INSTALLATION
AR-SF-01-DW4V
AR-SF-02-DW4V
AR-SJ-01-DW4V
AR-SJ-02-DW4V
AR-SJ-03-DW4V
AR-PR-01-DW4V
AR-PR-02-DW4V
AR-PR-03-DW4V
AR-TL-01-DW4V
AR-TL-02-DW4V
AR-TL-03-DW4V
AR-TL-04-DW4V
AR-TL-05-DW4V
AR-TL-06-DW4V
AR-TL-07-DW4V
AR-TL-08-DW4V
AR-TL-09-DW4V
AR-TL-10-DW4V
WALL TO SOFFIT
TRANSVERSE BENT SOFFIT
STACK JOINT
STACK JOINT W/ EXTRUSION
STACK JOINT W/ EXTRUSION
PARAPET COPING
PARAPET W/ FLUSH TRIM
PARAPET W/ PROFILED TRIM
WALL PENETRATION SECTION
2" PANEL EXTRUSIONS
3" PANEL EXTRUSIONS
EXTRUSION LAP STRIPS
EXTRUSION AT FRAMED OPENINGS
TRIM END LAP
TRIM END LAP WITH HEM
TRIM END LAP WITH LAP STRIP
TRIM AT FRAMED OPENINGS
ACCESSORIES
INDEX SHEET
DW-4000 - VERTICAL INSTALLATION
DISCLAIMERS:
THESE DETAILS ARE PROVIDED AS A GUIDELINE FOR PROPER PANEL AND ASSOCIATED
COMPONENT INSTALLATION, AND ARE BASED ON INDUSTRY ACCEPTED PRACTICES.
LOCATION OF VAPOR BARRIERS AND ASSOCIATED SEALANTS IN THESE DETAILS ARE BASED
ON TYPICAL DESIGN PRACTICES FOR MOST U.S. CLIMACTIC ZONES. (THE PRIMARY VAPOR
BARRIER IS PLACED ON THE "WARM" SIDE IN WINTER).
FOR CLARITY, ALL DETAILS SHOWN WITH (1) 1 4"-14 HEX HEAD FASTENER WITH WASHER CONTACT KINGSPAN TECHNICAL SERVICES FOR SPECIFIC PROJECT FASTENING REQUIREMENTS
PROJECTS LOCATED IN AREAS SUBJECT TO EXTREME COLD AND/OR HIGH SNOW LOADS MAY
REQUIRE MODIFICATIONS TO THESE DETAILS - CONTACT KINGSPAN TECHNICAL SERVICES
FOR SPECIFIC PROJECT RECOMMENDATIONS.
ALL STRUCTURAL SUPPORTS ARE NOT BY KINGSPAN AND ARE SHOWN FOR CLARIFICATION
PURPOSES ONLY.
ARCHITECTURAL
DISCLAIMER
DW-4000 - VERTICAL INSTALLATION
1
FASTENING CLIP
4"-14 HEX HEAD
FASTENER WITH WASHER
2"
HORIZONTAL SUPPORT
BY OTHERS
FACE OF PANEL
STANDARD INTERLOCK
JOINT FINNED GASKET
1/16" GAP RECOMMENDED
24", 30" OR 36" MODULE STD.
DIRECTION OF INSTALLATION
FASTENING CLIP
FOR CLARITY, ALL DETAILS SHOWN WITH (1)
FASTENER WITH WASHER
1
4"-14
HEX HEAD
CONTACT KINGSPAN TECHNICAL SERVICES
FOR SPECIFIC PROJECT FASTENING REQUIREMENTS
2" VERTICAL
PANEL JOINT
DW-4000 - VERTICAL INSTALLATION
1
FASTENING CLIP
4"-14 HEX HEAD
FASTENER WITH WASHER
3"
GIRT LINE
FACE OF PANEL
STANDARD INTERLOCK
JOINT FINNED GASKET
1/16" GAP RECOMMENDED
24", 30" OR 36" MODULE STD.
DIRECTION OF INSTALLATION
FASTENING CLIP
FOR CLARITY, ALL DETAILS SHOWN WITH (1)
FASTENER WITH WASHER
1
4"-14
HEX HEAD
CONTACT KINGSPAN TECHNICAL SERVICES
FOR SPECIFIC PROJECT FASTENING REQUIREMENTS
3" VERTICAL
PANEL JOINT
DW-4000 - VERTICAL INSTALLATION
ALWAYS ATTACH VERTICAL PANELS
TO HORIZONTALLY ORIENTED
SUPPORTS
HORIZONTAL
GIRT
VERTICAL
PANELS
HORIZONTAL
GIRT
HORIZONTAL
ANGLE
PANELS OVER
STRUCTURAL STEEL
DW-4000 - VERTICAL INSTALLATION
VERTICAL
STUDS
ALWAYS ATTACH VERTICAL PANELS
TO HORIZONTALLY ORIENTED
SUPPORTS
HORIZONTAL
SUBGIRT
SHEATHING
OPTIONAL
VERTICAL
PANELS
HORIZONTAL
SUBGIRT
HORIZONTAL
SUBGIRT
HORIZONTAL
SUBGIRT
PANELS OVER METAL
STUDS
DW-4000 - VERTICAL INSTALLATION
PRECAST OR
CMU WALL
ALWAYS ATTACH VERTICAL PANELS
TO HORIZONTALLY ORIENTED
SUPPORTS
HORIZONTAL
SUBGIRT
VERTICAL
PANELS
HORIZONTAL
SUBGIRT
HORIZONTAL
SUBGIRT
HORIZONTAL
SUBGIRT
PANELS OVER
CONCRETE
DW-4000 - VERTICAL INSTALLATION
2" OR 3"
CONTINUOUS BUTYL SEALANT
WITH MARRIAGE BEAD TO
HORIZONTAL PANEL JOINT
FASTENING CLIP
STEEL FRAMING
BY OTHERS
(SET IN SEALANT)
1
1"
4"
4"-14 HEX HEAD
FASTENER WITH
WASHER
ALUMINUM BASE
EXTRUSION
1/4" DIA. WEEP HOLE
24" O.C. FIELD DRILLED
FIELD CUT 6" SPLICE
PLATE
BASE DETAIL OVERHANG
DW-4000 - VERTICAL INSTALLATION
2" OR 3"
CONTINUOUS BUTYL SEALANT
WITH MARRIAGE BEAD TO
HORIZONTAL PANEL JOINT
FASTENING CLIP
1
1"
4"
4"-14 HEX HEAD
FASTENER WITH
WASHER
ALUMINUM BASE
EXTRUSION
1/4" DIA. WEEP HOLE
24" O.C. FIELD DRILLED
FIELD CUT 6" SPLICE
PLATE
BASE DETAIL - FLUSH
FILL VOID WITH
COMPRESSIBLE
FOAM CLOSURE
STEEL FRAMING
BY OTHERS
(SET IN SEALANT)
DW-4000 - VERTICAL INSTALLATION
R
O
2"
3"
GIRT LINE
SEALANT
FIELD CUT
PANELS TO SUIT
"
2
2-PC SNAP-TOGETHER OUTSIDE
CORNER EXTRUSION
OUTSIDE CORNER
WITH 2-PC EXTRUSION
31
1
3
4"-14 "LOW PROFILE"
THROUGH
FASTENER WITH
WASHER AT GIRTS
"
1
2
F.I.P. INSULATION
(NOT BY KINGSPAN)
DW-4000 - VERTICAL INSTALLATION
F.I.P. INSULATION
(NOT BY KINGSPAN)
GIRT LINE
SEALANT
1
4"-14 "LOW PROFILE"
THROUGH
FASTENER AT GIRTS
1
4"-14 "LOW PROFILE"
THROUGH
FASTENER WITH
WASHER AT GIRTS
INSIDE CORNER
WITH 2-PC EXTRUSION
R
O
2"
2-PC INSIDE CORNER
EXTRUSION
3"
FIELD CUT
PANELS TO SUIT
DW-4000 - VERTICAL INSTALLATION
ENDWALL EXTRUSION
FIELD CUT PANEL
TO SUIT CONDITION
1
4"-14 "LOW PROFILE"
THROUGH FASTENER
WITH WASHER AT
GIRTS
2" OR 3"
GIRT LINE
3"
SEALANT
ENDWALL EXTRUSION
ENDWALL W/ 2-PC
EXTRUSION
DW-4000 - VERTICAL INSTALLATION
WINDOW SYSTEM BY OTHERS
WINDOW SILL EXTRUSION
13 4"
SEALANT
INSTALLER TO PLUG
TOPS OF VERTICAL
JOINTS WITH SEALANT
STEEL FRAMING
BY OTHERS
CONTINUOUS BUTYL SEALANT
WITH MARRIAGE BEAD TO
HORIZONTAL PANEL JOINT
FASTENING CLIP
SILL WITH EXTRUSION
DW-4000 - VERTICAL INSTALLATION
2" OR 3"
CONTINUOUS BUTYL SEALANT
WITH MARRIAGE BEAD TO
HORIZONTAL PANEL JOINT
FILL VOID WITH
COMPRESSIBLE
FOAM CLOSURE
FASTENING CLIP
1
4"-14 HEX HEAD
FASTENER WITH
WASHER
STEEL FRAMING
BY OTHERS
1"
ALUM. SOFFIT
EXTRUSION
1/4" DIA. WEEP HOLE
24" O.C. FIELD DRILLED
WINDOW SYSTEM BY OTHERS
HEAD WITH
EXTRUSION
DW-4000 - VERTICAL INSTALLATION
ENDWALL EXTRUSION
FIELD CUT PANEL
TO SUIT CONDITION
1
4"-14 "LOW PROFILE"
THROUGH FASTENER
WITH WASHER AT
GIRTS
2" OR 3"
GIRT LINE
3"
SEALANT
ENDWALL EXTRUSION
WINDOW SYSTEM BY OTHERS
JAMB WITH EXTRUSION
DW-4000 - VERTICAL INSTALLATION
CONTINUOUS BUTYL SEALANT W/
MARRIAGE BEAD TO VERTICAL
PANEL JOINT
1
- 14 "LOW PROFILE"
THROUGH FASTENER
WITH WASHER
INTERIOR CAP TRIM
4"
POP RIVETS
EXTERIOR CAP TRIM
CONTINUOUS
BUTYL SEALANT
FRAMED OPENING
(NOT BY KINGSPAN)
FIELD DRILL 3 8" WEEP HOLES
TO ALIGN WITH PANEL JOINTS
DOOR/WINDOW FRAME
(NOT BY KINGSPAN)
EXPOSED SEALANT
(NOT BY KINGSPAN)
NOTE: SEE DETAIL AR-TL-06-DW4V, AR-TL-07-DW4V, AND AR-TL-08-DW4V
FOR TYPICAL TRIM LAP INSTRUCTIONS
F.O. TWO-PIECE HEAD
DW-4000 - VERTICAL INSTALLATION
CONTINUOUS BUTYL SEALANT W/
MARRIAGE BEAD TO VERTICAL
PANEL JOINT
1
4" - 14 "LOW PROFILE"
THROUGH FASTENER
WITH WASHER
POP RIVETS
EXTERIOR CAP TRIM
CONTINUOUS
BUTYL SEALANT
FRAMED OPENING
(NOT BY KINGSPAN)
DOOR/WINDOW FRAME
(NOT BY KINGSPAN)
DRIP FLASHING
EXPOSED SEALANT
(NOT BY KINGSPAN)
NOTE: SEE DETAIL AR-TL-06-DW4V, AR-TL-07-DW4V, AND AR-TL-08-DW4V
FOR TYPICAL TRIM LAP INSTRUCTIONS
F.O. HEAD WITH DRIP
EDGE
DW-4000 - VERTICAL INSTALLATION
FRAMED OPENING
(NOT BY KINGSPAN)
DOOR/WINDOW FRAME
(NOT BY KINGSPAN)
1
4" - 14 "LOW PROFILE"
THROUGH FASTENER
CONTINUOUS BUTYL SEALANT
INTERIOR CAP TRIM
EXPOSED SEALANT
(NOT BY KINGSPAN)
CONTINUOUS BUTYL SEALANT
POP RIVETS
POP RIVETS
EXTERIOR CAP TRIM
NOTE: SEE DETAIL AR-TL-06-DW4V, AR-TL-07-DW4V, AND AR-TL-08-DW4V
FOR TYPICAL TRIM LAP INSTRUCTIONS
F.O. TWO PIECE JAMB
DW-4000 - VERTICAL INSTALLATION
FRAMED OPENING
(NOT BY KINGSPAN)
FIELD BEND
(AS REQUIRED)
1
DOOR/WINDOW FRAME
(NOT BY KINGSPAN)
4" - 14 "LOW PROFILE"
FASTENER (AS REQUIRED)
1
4" - 14 "LOW PROFILE"
THROUGH FASTENER
WITH WASHER
CONTINUOUS BUTYL SEALANT
CONTINUOUS BUTYL SEALANT
EXPOSED SEALANT
(NOT BY KINGSPAN)
CONTINUOUS BUTYL SEALANT
POP RIVETS
CAP TRIM
NOTE: SEE DETAIL AR-TL-06-DW4V, AR-TL-07-DW4V, AND AR-TL-08-DW4V
FOR TYPICAL TRIM LAP INSTRUCTIONS
F.O. ONE PIECE JAMB
DW-4000 - VERTICAL INSTALLATION
EXPOSED SEALANT
(NOT BY KINGSPAN)
CONTINUOUS BUTYL
SEALANT
WINDOW FRAME
(NOT BY KINGSPAN)
FIELD BEND
(AS REQUIRED)
CONTINUOUS BUTYL SEALANT W/
MARRIAGE BEAD TO VERTICAL
PANEL JOINT
EXTERIOR CAP TRIM
POP RIVETS
1
4"
- 14 "LOW PROFILE"
THROUGH FASTENER
WITH WASHER
1
4" - 14 "LOW PROFILE"
FASTENER (AS REQUIRED)
FRAMED OPENING
(NOT BY KINGSPAN)
NOTE: SEE DETAIL AR-TL-06-DW4V, AR-TL-07-DW4V, AND AR-TL-08-DW4V
FOR TYPICAL TRIM LAP INSTRUCTIONS
F.O. ONE PIECE SILL
DW-4000 - VERTICAL INSTALLATION
2" OR 3"
CONTINUOUS BUTYL SEALANT
WITH MARRIAGE BEAD TO
HORIZONTAL PANEL JOINT
FASTENING CLIP
STEEL FRAMING
BY OTHERS
1
4"-14 HEX HEAD
FASTENER WITH
WASHER
1"
ALUM. SOFFIT
EXTRUSION
1/4" DIA. WEEP HOLE @
24" O.C. FIELD DRILLED
FIELD CUT 6" SPLICE
PLATE
WALL TO SOFFIT
11 2"
FILL VOID WITH
COMPRESSIBLE
FOAM CLOSURE
DW-4000 - VERTICAL INSTALLATION
MALE LEG AT VERTICAL
JOINT
FRAMING BY OTHERS
CONTINUOUS
MENDING PLATE
CONTINUOUS BUTYL
TUBE SEALANT MARRIED
TO LINER SIDE JOINT
GASKET.
1
4"-14 HEX HEAD
FASTENER WITH
WASHER
FASTENING CLIP
FACTORY TRANSVERSE BEND
SHORT LEG 4'-0 MAXIMUM, TOTAL LENGTH 10'-0 MAX.
TRANSVERSE BENT
SOFFIT
DW-4000 - VERTICAL INSTALLATION
2" OR 3"
ZERO PROFILE HORIZONTAL
JOINT FLASHING FOR
DRAINAGE
DO NOT CAULK HERE
ALLOW TO DRAIN
5 "
8
STEEL FRAMING
BY OTHERS
INSTALLER TO PLUG
TOPS OF VERTICAL
JOINTS WITH SEALANT
FASTENING CLIP
STACK JOINT
CONTINUOUS BUTYL
SEALANT MARRIED
TO SIDE JOINT
GASKET.
5" MIN. BEARING
SILICONE SEALANT &
BACKER ROD
DW-4000 - VERTICAL INSTALLATION
1
4" - 14 "LOW PROFILE"
THROUGH FASTENER
1
4"-14 HEX HEAD
FASTENER WITH
WASHER
FIELD DRILL 3 8" WEEP
HOLES
(NOT BY KINGSPAN)
CONTINUOUS
BUTYL SEALANT W/
MARRIAGE BEAD
TO VERTICAL
PANEL JOINT
FILL VOID WITH
COMPRESSIBLE
FOAM CLOSURE
TWO PIECE STACK
EXTRUSION
CONTINUOUS BUTYL
SEALANT W/
MARRIAGE BEAD TO
VERTICAL
PANEL JOINT
STACK JOINT W/
EXTRUSION
5" MIN. BEARING
FASTENING CLIP
DW-4000 - VERTICAL INSTALLATION
2" OR 3"
FASTENING CLIP
CONTINUOUS BUTYL
SEALANT
1
31 4"
1"
STEEL FRAMING
BY OTHERS
SEALANT
HORIZONTAL JOINT
EXTRUSION W/ WEEP
HOLES @ 24" O.C.
STACK JOINT W/
EXTRUSION
BREAK-FORMED
SPLICE PLATES BED
SEALED IN SILICONE
CONTINUOUS BUTYL
SEALANT MARRIED
TO SIDE JOINT
GASKET.
5" MIN. BEARING
4"-14 HEX HEAD
FASTENER WITH
WASHER
DW-4000 - VERTICAL INSTALLATION
PARAPET COPING EXTRUSION
SILICONE TUBE SEALANT TYP.
STITCH TEKS TO TIE
FLASHING IN PLACE
FABRICATED METAL
FLASHING EXTENSION
33 4"
15 8"
STAINLESS STEEL SCREW PAINTED
TO MATCH PANEL. 12" O.C.
FASTENING CLIP
CONTINUOUS BUTYL SEALANT
WITH MARRIAGE BEAD TO
HORIZONTAL PANEL JOINT
1
4"-14 HEX HEAD
FASTENER WITH
WASHER
2" OR 3"
PARAPET COPING
DW-4000 - VERTICAL INSTALLATION
SEALANT MARRIAGE BEAD TO
VERTICAL PANEL JOINT
FASTENING CLIP
PARAPET BLOCKING
(NOT BY KINGSPAN)
CONTINUOUS
BUTYL SEALANT
1
4" - 14 HEX HEAD
FASTENERS WITH WASHER
PARAPET CAP
FLASHING
FASTENER TO PARAPET
BACKER (NOT BY KINGSPAN)
WRAP MEMBRANE
ADHERE TO EXTERIOR
PANEL FACE
(NOT BY KINGSPAN)
1
4" - 14 "LOW PROFILE"
FASTENER
CONTINUOUS CLEAT
MEMBRANE ROOF &
PARAPET BACKER
(NOT BY KINGSPAN)
PARAPET W/ FLUSH
TRIM
DW-4000 - VERTICAL INSTALLATION
WRAP MEMBRANE
(NOT BY KINGSPAN)
SEALANT MARRIAGE BEAD TO
VERTICAL PANEL JOINT
PARAPET BLOCKING
(NOT BY KINGSPAN)
CONTINUOUS
BUTYL SEALANT
FASTENING CLIP
1
4" - 14 HEX HEAD
FASTENERS WITH WASHER
WRAP MEMBRANE
ADHERE TO EXTERIOR
PANEL FACE
(NOT BY KINGSPAN)
FASTENER TO PARAPET
BACKER (NOT BY KINGSPAN)
PARAPET CAP
FLASHING
POP RIVET
PARAPET W/ PROFILED
TRIM
MEMBRANE ROOF &
PARAPET BACKER
(NOT BY KINGSPAN)
DW-4000 - VERTICAL INSTALLATION
'A'
TRIM
BACKER ROD AND
SEALANT
(NOT BY KINGSPAN)
PENETRATION
(NOT BY KINGSPAN)
'A'
ELEVATION
POP RIVET
FASTENER
(AS REQUIRED)
SEALANT
(NOT BY KINGSPAN)
FLASHING
SEALANT
(NOT BY KINGSPAN)
BACKER ROD AND
SEALANT
(NOT BY KINGSPAN)
PENETRATION
(NOT BY KINGSPAN)
SECTION 'A-A'
NOTES: 1. DO NOT ALIGN PENETRATIONS AT PANEL JOINT LOCATIONS.
2. FLASHING AT PENETRATIONS TO BE FIELD FABRICATED FROM
FLATSTOCK SHEETS AS NECESSARY
WALL PENETRATION
SECTION
DW-4000 - VERTICAL INSTALLATION
2" PANEL 2-PC
CORNER BASE
DIE #13264
2" PANEL BASE
EXTRUSION DIE #11372
6" SPLICE PLATE DIE
#13262
CORNER CAP DIE
#13263
2" PANEL ENDWALL
EXTRUSION RECEIVER
DIE #11487
STACK EXTRUSION
CAP
ENDWALL EXTRUSION CAP
CAP DIE #11488
2" PANEL STACK
EXTRUSION BASE
2" PANEL HORIZONTAL
JOINT EXTRUSION DIE
#11298
2" PARAPET COPING
EXTRUSION
2" PANEL SOFFIT
EXTRUSION DIE #11423
SILL EXTRUSION DIE #KE6143
2" PANEL EXTRUSION
DW-4000 - VERTICAL INSTALLATION
3" PANEL BASE
EXTRUSION DIE #11366
3" PANEL ENDWALL
EXTRUSION RECEIVER
DIE #12714
ENDWALL EXTRUSION CAP
CAP DIE #11488
3" PANEL 2-PC
CORNER BASE
2-PC CORNER CAP
DIE #13263
STACK EXTRUSION
CAP
3" PANEL STACK
EXTRUSION BASE
3" PANEL HORIZONTAL
JOINT EXTRUSION DIE
#12861
3" PANEL SOFFIT
EXTRUSION
SILL EXTRUSION DIE #KE6143
3" PANEL EXTRUSION
3" PANEL PARAPET COPING
EXTRUSION
DW-4000 - VERTICAL INSTALLATION
LAP STRIP FOR TWO PIECE
JAMB EXTRUSION
LAP STRIP FOR BASE EXTRUSION
LAP STRIPS FOR OUTSIDE CORNER
EXTRUSION
LAP STRIP FOR PARAPET EXTRUSION
EXTRUSION LAP
STRIPS
LAP STRIPS FOR INSIDE CORNER
EXTRUSION
LAP STRIP FOR SOFFIT EXTRUSION
DW-4000 - VERTICAL INSTALLATION
FIELD CUT/NOTCH JAMB
EXTRUSION AT HEAD AND
JAMB (NOT BY KINGSPAN)
SEALANT END DAM
TWO PIECE HEAD
EXTRUSION CAP
3
EXPOSED SEALANT
(NOT BY KINGSPAN)
N
O
PIE
CE
A
HE
EX
D
TW
2
TWO PIECE HEAD EXTRUSION BASE W/
FIELD DRILL 3 8
(NOT BY KINGSPAN)
1
TWO PIECE JAMB
EXTRUSION BASE
6
EXPOSED SEALANT
(NOT BY KINGSPAN)
TWO PIECE JAMB EXTRUSION
IO
US
TR
4
FIELD CUT/NOTCH JAMB
EXTRUSION
(NOT BY KINGSPAN)
5
N
SIO
U
R
TWO PIECE JAMB
EXTRUSION CAP
TWO PIECE JAMB
EXTRUSION CAP
T
L
SIL
EX
EXTRUSION AT
FRAMED OPENINGS
EXTRUSION INSTALLATION SEQUENCE:
1
TWO PIECE JAMB EXTRUSION BASE
2
TWO PIECE HEAD EXTRUSION BASE
3
TWO PIECE HEAD EXTRUSION CAP
4
TWO PIECE JAMB EXTRUSION CAP
5
SILL EXTRUSION
6
EXTERIOR SEALANTS AS REQUIRED
DW-4000 - VERTICAL INSTALLATION
3"
P
N.
MI LA
M
I
TR
(2) BEADS
BUTYL SEALANT
3"
N. AP
I
L
M
IM
TR
TRIM END LAP
DW-4000 - VERTICAL INSTALLATION
FIELD NOTCH HEM(S)
AS REQUIRED
(NOT BY KINGSPAN)
3"
N. AP
I
L
M
IM
TR
(2) BEADS
BUTYL SEALANT
3"
N. AP
I
M
L
IM
TR
TRIM END LAP WITH
HEM
DW-4000 - VERTICAL INSTALLATION
(2) BEADS
BUTYL SEALANT
8" LONG LAP STRIP
1 "
. 4
M
NO AP
G
TRIM END LAP WITH
LAP STRIP
DW-4000 - VERTICAL INSTALLATION
FIELD NOTCH AND OVERLAP
TRIMS, POP RIVET AND SEAL AS
NECESSARY (NOT BY KINGSPAN)
FIELD MITER AND OVERLAP
TRIMS, POP RIVET AS
NECESSARY (NOT BY KINGSPAN)
SEALANT END DAM
2
INTERIOR HEAD TRIM
WITH TABS BENT DOWN
IM
TR
D
M
OR
RI
I
TR
P
A
A
HE
T
A
C
EXTERIOR CAP TRIM AT JAMB
I
OR
RI
E
NT
P
CA
D
EA
H
AT
TE
EX
5
EXTERIOR HEAD TRIM W/
FIELD DRILL 3 8
(NOT BY KINGSPAN)
1
INTERIOR JAMB TRIM
6
EXPOSED SEALANT
(NOT BY KINGSPAN)
3
SILL TRIM WITH TABS
BENT UP
RIM
R
4
EXTERIOR JAMB TRIM
FIELD CUT/NOTCH CAP
TRIM AT CORNERS TO
ALLOW FOR LAP
(NOT BY KINGSPAN)
ILL
RIO
TE
X
E
FIELD CUT/NOTCH CAP
TRIM AT CORNERS TO
ALLOW FOR LAP
(NOT BY KINGSPAN)
PT
CA
TRIM AT FRAMED
OPENINGS
S
AT
FIELD MITER AND OVERLAP
TRIMS, POP RIVET AND SEAL AS
NECESSARY (NOT BY KINGSPAN)
TRIM INSTALLATION SEQUENCE:
1
INTERIOR JAMB TRIM
2
INTERIOR HEAD TRIM WITH TABS DOWN
3
SILL TRIM WITH TABS UP
4
EXTERIOR JAMB TRIM
5
EXTERIOR HEAD TRIM
6
EXTERIOR SEALANTS AS REQUIRED
DW-4000 - VERTICAL INSTALLATION
FASTENING CLIP
2" FASTENING CLIP
PART # 8100.2100
3" FASTENING CLIP
PART # 8100.3100
ACCESSORIES