dw-4000 - vertical installation
Transcription
dw-4000 - vertical installation
DW-4000 - VERTICAL INSTALLATION AR-PJ-01-DW4V AR-PJ-02-DW4V AR-PJ-03-DW4V AR-PJ-04-DW4V AR-PJ-05-DW4V AR-BS-01-DW4V AR-BS-02-DW4V AR-OC-01-DW4V AR-IC-01-DW4V AR-IC-02-DW4V AR-FO-01-DW4V AR-FO-02-DW4V AR-FO-03-DW4V AR-FO-04-DW4V AR-FO-05-DW4V AR-FO-06-DW4V AR-FO-07-DW4V AR-FO-08-DW4V 2" VERTICAL PANEL JOINT 3" VERTICAL JOINT PANELS OVER STRUCTURAL STEEL PANELS OVER METAL STUDS PANELS OVER CONCRETE BASE DETAIL - OVERHANG BASE DETAIL - FLUSH OUTSIDE CORNER W/ 2-PC EXTRUSION INSIDE CORNER WITH 1-PC EXTRUSION ENDWALL W/ 2-PC EXTRUSION SILL WITH EXTRUSION HEAD WITH EXTRUSION JAMB WITH EXTRUSION F.O. TWO PIECE HEAD F.O. HEAD WITH DRIP EDGE F.O. TWO PIECE JAMB F.O. ONE PIECE JAMB F.O. ONE PIECE SILL INDEX SHEET DW-4000 - VERTICAL INSTALLATION AR-SF-01-DW4V AR-SF-02-DW4V AR-SJ-01-DW4V AR-SJ-02-DW4V AR-SJ-03-DW4V AR-PR-01-DW4V AR-PR-02-DW4V AR-PR-03-DW4V AR-TL-01-DW4V AR-TL-02-DW4V AR-TL-03-DW4V AR-TL-04-DW4V AR-TL-05-DW4V AR-TL-06-DW4V AR-TL-07-DW4V AR-TL-08-DW4V AR-TL-09-DW4V AR-TL-10-DW4V WALL TO SOFFIT TRANSVERSE BENT SOFFIT STACK JOINT STACK JOINT W/ EXTRUSION STACK JOINT W/ EXTRUSION PARAPET COPING PARAPET W/ FLUSH TRIM PARAPET W/ PROFILED TRIM WALL PENETRATION SECTION 2" PANEL EXTRUSIONS 3" PANEL EXTRUSIONS EXTRUSION LAP STRIPS EXTRUSION AT FRAMED OPENINGS TRIM END LAP TRIM END LAP WITH HEM TRIM END LAP WITH LAP STRIP TRIM AT FRAMED OPENINGS ACCESSORIES INDEX SHEET DW-4000 - VERTICAL INSTALLATION DISCLAIMERS: THESE DETAILS ARE PROVIDED AS A GUIDELINE FOR PROPER PANEL AND ASSOCIATED COMPONENT INSTALLATION, AND ARE BASED ON INDUSTRY ACCEPTED PRACTICES. LOCATION OF VAPOR BARRIERS AND ASSOCIATED SEALANTS IN THESE DETAILS ARE BASED ON TYPICAL DESIGN PRACTICES FOR MOST U.S. CLIMACTIC ZONES. (THE PRIMARY VAPOR BARRIER IS PLACED ON THE "WARM" SIDE IN WINTER). FOR CLARITY, ALL DETAILS SHOWN WITH (1) 1 4"-14 HEX HEAD FASTENER WITH WASHER CONTACT KINGSPAN TECHNICAL SERVICES FOR SPECIFIC PROJECT FASTENING REQUIREMENTS PROJECTS LOCATED IN AREAS SUBJECT TO EXTREME COLD AND/OR HIGH SNOW LOADS MAY REQUIRE MODIFICATIONS TO THESE DETAILS - CONTACT KINGSPAN TECHNICAL SERVICES FOR SPECIFIC PROJECT RECOMMENDATIONS. ALL STRUCTURAL SUPPORTS ARE NOT BY KINGSPAN AND ARE SHOWN FOR CLARIFICATION PURPOSES ONLY. ARCHITECTURAL DISCLAIMER DW-4000 - VERTICAL INSTALLATION 1 FASTENING CLIP 4"-14 HEX HEAD FASTENER WITH WASHER 2" HORIZONTAL SUPPORT BY OTHERS FACE OF PANEL STANDARD INTERLOCK JOINT FINNED GASKET 1/16" GAP RECOMMENDED 24", 30" OR 36" MODULE STD. DIRECTION OF INSTALLATION FASTENING CLIP FOR CLARITY, ALL DETAILS SHOWN WITH (1) FASTENER WITH WASHER 1 4"-14 HEX HEAD CONTACT KINGSPAN TECHNICAL SERVICES FOR SPECIFIC PROJECT FASTENING REQUIREMENTS 2" VERTICAL PANEL JOINT DW-4000 - VERTICAL INSTALLATION 1 FASTENING CLIP 4"-14 HEX HEAD FASTENER WITH WASHER 3" GIRT LINE FACE OF PANEL STANDARD INTERLOCK JOINT FINNED GASKET 1/16" GAP RECOMMENDED 24", 30" OR 36" MODULE STD. DIRECTION OF INSTALLATION FASTENING CLIP FOR CLARITY, ALL DETAILS SHOWN WITH (1) FASTENER WITH WASHER 1 4"-14 HEX HEAD CONTACT KINGSPAN TECHNICAL SERVICES FOR SPECIFIC PROJECT FASTENING REQUIREMENTS 3" VERTICAL PANEL JOINT DW-4000 - VERTICAL INSTALLATION ALWAYS ATTACH VERTICAL PANELS TO HORIZONTALLY ORIENTED SUPPORTS HORIZONTAL GIRT VERTICAL PANELS HORIZONTAL GIRT HORIZONTAL ANGLE PANELS OVER STRUCTURAL STEEL DW-4000 - VERTICAL INSTALLATION VERTICAL STUDS ALWAYS ATTACH VERTICAL PANELS TO HORIZONTALLY ORIENTED SUPPORTS HORIZONTAL SUBGIRT SHEATHING OPTIONAL VERTICAL PANELS HORIZONTAL SUBGIRT HORIZONTAL SUBGIRT HORIZONTAL SUBGIRT PANELS OVER METAL STUDS DW-4000 - VERTICAL INSTALLATION PRECAST OR CMU WALL ALWAYS ATTACH VERTICAL PANELS TO HORIZONTALLY ORIENTED SUPPORTS HORIZONTAL SUBGIRT VERTICAL PANELS HORIZONTAL SUBGIRT HORIZONTAL SUBGIRT HORIZONTAL SUBGIRT PANELS OVER CONCRETE DW-4000 - VERTICAL INSTALLATION 2" OR 3" CONTINUOUS BUTYL SEALANT WITH MARRIAGE BEAD TO HORIZONTAL PANEL JOINT FASTENING CLIP STEEL FRAMING BY OTHERS (SET IN SEALANT) 1 1" 4" 4"-14 HEX HEAD FASTENER WITH WASHER ALUMINUM BASE EXTRUSION 1/4" DIA. WEEP HOLE 24" O.C. FIELD DRILLED FIELD CUT 6" SPLICE PLATE BASE DETAIL OVERHANG DW-4000 - VERTICAL INSTALLATION 2" OR 3" CONTINUOUS BUTYL SEALANT WITH MARRIAGE BEAD TO HORIZONTAL PANEL JOINT FASTENING CLIP 1 1" 4" 4"-14 HEX HEAD FASTENER WITH WASHER ALUMINUM BASE EXTRUSION 1/4" DIA. WEEP HOLE 24" O.C. FIELD DRILLED FIELD CUT 6" SPLICE PLATE BASE DETAIL - FLUSH FILL VOID WITH COMPRESSIBLE FOAM CLOSURE STEEL FRAMING BY OTHERS (SET IN SEALANT) DW-4000 - VERTICAL INSTALLATION R O 2" 3" GIRT LINE SEALANT FIELD CUT PANELS TO SUIT " 2 2-PC SNAP-TOGETHER OUTSIDE CORNER EXTRUSION OUTSIDE CORNER WITH 2-PC EXTRUSION 31 1 3 4"-14 "LOW PROFILE" THROUGH FASTENER WITH WASHER AT GIRTS " 1 2 F.I.P. INSULATION (NOT BY KINGSPAN) DW-4000 - VERTICAL INSTALLATION F.I.P. INSULATION (NOT BY KINGSPAN) GIRT LINE SEALANT 1 4"-14 "LOW PROFILE" THROUGH FASTENER AT GIRTS 1 4"-14 "LOW PROFILE" THROUGH FASTENER WITH WASHER AT GIRTS INSIDE CORNER WITH 2-PC EXTRUSION R O 2" 2-PC INSIDE CORNER EXTRUSION 3" FIELD CUT PANELS TO SUIT DW-4000 - VERTICAL INSTALLATION ENDWALL EXTRUSION FIELD CUT PANEL TO SUIT CONDITION 1 4"-14 "LOW PROFILE" THROUGH FASTENER WITH WASHER AT GIRTS 2" OR 3" GIRT LINE 3" SEALANT ENDWALL EXTRUSION ENDWALL W/ 2-PC EXTRUSION DW-4000 - VERTICAL INSTALLATION WINDOW SYSTEM BY OTHERS WINDOW SILL EXTRUSION 13 4" SEALANT INSTALLER TO PLUG TOPS OF VERTICAL JOINTS WITH SEALANT STEEL FRAMING BY OTHERS CONTINUOUS BUTYL SEALANT WITH MARRIAGE BEAD TO HORIZONTAL PANEL JOINT FASTENING CLIP SILL WITH EXTRUSION DW-4000 - VERTICAL INSTALLATION 2" OR 3" CONTINUOUS BUTYL SEALANT WITH MARRIAGE BEAD TO HORIZONTAL PANEL JOINT FILL VOID WITH COMPRESSIBLE FOAM CLOSURE FASTENING CLIP 1 4"-14 HEX HEAD FASTENER WITH WASHER STEEL FRAMING BY OTHERS 1" ALUM. SOFFIT EXTRUSION 1/4" DIA. WEEP HOLE 24" O.C. FIELD DRILLED WINDOW SYSTEM BY OTHERS HEAD WITH EXTRUSION DW-4000 - VERTICAL INSTALLATION ENDWALL EXTRUSION FIELD CUT PANEL TO SUIT CONDITION 1 4"-14 "LOW PROFILE" THROUGH FASTENER WITH WASHER AT GIRTS 2" OR 3" GIRT LINE 3" SEALANT ENDWALL EXTRUSION WINDOW SYSTEM BY OTHERS JAMB WITH EXTRUSION DW-4000 - VERTICAL INSTALLATION CONTINUOUS BUTYL SEALANT W/ MARRIAGE BEAD TO VERTICAL PANEL JOINT 1 - 14 "LOW PROFILE" THROUGH FASTENER WITH WASHER INTERIOR CAP TRIM 4" POP RIVETS EXTERIOR CAP TRIM CONTINUOUS BUTYL SEALANT FRAMED OPENING (NOT BY KINGSPAN) FIELD DRILL 3 8" WEEP HOLES TO ALIGN WITH PANEL JOINTS DOOR/WINDOW FRAME (NOT BY KINGSPAN) EXPOSED SEALANT (NOT BY KINGSPAN) NOTE: SEE DETAIL AR-TL-06-DW4V, AR-TL-07-DW4V, AND AR-TL-08-DW4V FOR TYPICAL TRIM LAP INSTRUCTIONS F.O. TWO-PIECE HEAD DW-4000 - VERTICAL INSTALLATION CONTINUOUS BUTYL SEALANT W/ MARRIAGE BEAD TO VERTICAL PANEL JOINT 1 4" - 14 "LOW PROFILE" THROUGH FASTENER WITH WASHER POP RIVETS EXTERIOR CAP TRIM CONTINUOUS BUTYL SEALANT FRAMED OPENING (NOT BY KINGSPAN) DOOR/WINDOW FRAME (NOT BY KINGSPAN) DRIP FLASHING EXPOSED SEALANT (NOT BY KINGSPAN) NOTE: SEE DETAIL AR-TL-06-DW4V, AR-TL-07-DW4V, AND AR-TL-08-DW4V FOR TYPICAL TRIM LAP INSTRUCTIONS F.O. HEAD WITH DRIP EDGE DW-4000 - VERTICAL INSTALLATION FRAMED OPENING (NOT BY KINGSPAN) DOOR/WINDOW FRAME (NOT BY KINGSPAN) 1 4" - 14 "LOW PROFILE" THROUGH FASTENER CONTINUOUS BUTYL SEALANT INTERIOR CAP TRIM EXPOSED SEALANT (NOT BY KINGSPAN) CONTINUOUS BUTYL SEALANT POP RIVETS POP RIVETS EXTERIOR CAP TRIM NOTE: SEE DETAIL AR-TL-06-DW4V, AR-TL-07-DW4V, AND AR-TL-08-DW4V FOR TYPICAL TRIM LAP INSTRUCTIONS F.O. TWO PIECE JAMB DW-4000 - VERTICAL INSTALLATION FRAMED OPENING (NOT BY KINGSPAN) FIELD BEND (AS REQUIRED) 1 DOOR/WINDOW FRAME (NOT BY KINGSPAN) 4" - 14 "LOW PROFILE" FASTENER (AS REQUIRED) 1 4" - 14 "LOW PROFILE" THROUGH FASTENER WITH WASHER CONTINUOUS BUTYL SEALANT CONTINUOUS BUTYL SEALANT EXPOSED SEALANT (NOT BY KINGSPAN) CONTINUOUS BUTYL SEALANT POP RIVETS CAP TRIM NOTE: SEE DETAIL AR-TL-06-DW4V, AR-TL-07-DW4V, AND AR-TL-08-DW4V FOR TYPICAL TRIM LAP INSTRUCTIONS F.O. ONE PIECE JAMB DW-4000 - VERTICAL INSTALLATION EXPOSED SEALANT (NOT BY KINGSPAN) CONTINUOUS BUTYL SEALANT WINDOW FRAME (NOT BY KINGSPAN) FIELD BEND (AS REQUIRED) CONTINUOUS BUTYL SEALANT W/ MARRIAGE BEAD TO VERTICAL PANEL JOINT EXTERIOR CAP TRIM POP RIVETS 1 4" - 14 "LOW PROFILE" THROUGH FASTENER WITH WASHER 1 4" - 14 "LOW PROFILE" FASTENER (AS REQUIRED) FRAMED OPENING (NOT BY KINGSPAN) NOTE: SEE DETAIL AR-TL-06-DW4V, AR-TL-07-DW4V, AND AR-TL-08-DW4V FOR TYPICAL TRIM LAP INSTRUCTIONS F.O. ONE PIECE SILL DW-4000 - VERTICAL INSTALLATION 2" OR 3" CONTINUOUS BUTYL SEALANT WITH MARRIAGE BEAD TO HORIZONTAL PANEL JOINT FASTENING CLIP STEEL FRAMING BY OTHERS 1 4"-14 HEX HEAD FASTENER WITH WASHER 1" ALUM. SOFFIT EXTRUSION 1/4" DIA. WEEP HOLE @ 24" O.C. FIELD DRILLED FIELD CUT 6" SPLICE PLATE WALL TO SOFFIT 11 2" FILL VOID WITH COMPRESSIBLE FOAM CLOSURE DW-4000 - VERTICAL INSTALLATION MALE LEG AT VERTICAL JOINT FRAMING BY OTHERS CONTINUOUS MENDING PLATE CONTINUOUS BUTYL TUBE SEALANT MARRIED TO LINER SIDE JOINT GASKET. 1 4"-14 HEX HEAD FASTENER WITH WASHER FASTENING CLIP FACTORY TRANSVERSE BEND SHORT LEG 4'-0 MAXIMUM, TOTAL LENGTH 10'-0 MAX. TRANSVERSE BENT SOFFIT DW-4000 - VERTICAL INSTALLATION 2" OR 3" ZERO PROFILE HORIZONTAL JOINT FLASHING FOR DRAINAGE DO NOT CAULK HERE ALLOW TO DRAIN 5 " 8 STEEL FRAMING BY OTHERS INSTALLER TO PLUG TOPS OF VERTICAL JOINTS WITH SEALANT FASTENING CLIP STACK JOINT CONTINUOUS BUTYL SEALANT MARRIED TO SIDE JOINT GASKET. 5" MIN. BEARING SILICONE SEALANT & BACKER ROD DW-4000 - VERTICAL INSTALLATION 1 4" - 14 "LOW PROFILE" THROUGH FASTENER 1 4"-14 HEX HEAD FASTENER WITH WASHER FIELD DRILL 3 8" WEEP HOLES (NOT BY KINGSPAN) CONTINUOUS BUTYL SEALANT W/ MARRIAGE BEAD TO VERTICAL PANEL JOINT FILL VOID WITH COMPRESSIBLE FOAM CLOSURE TWO PIECE STACK EXTRUSION CONTINUOUS BUTYL SEALANT W/ MARRIAGE BEAD TO VERTICAL PANEL JOINT STACK JOINT W/ EXTRUSION 5" MIN. BEARING FASTENING CLIP DW-4000 - VERTICAL INSTALLATION 2" OR 3" FASTENING CLIP CONTINUOUS BUTYL SEALANT 1 31 4" 1" STEEL FRAMING BY OTHERS SEALANT HORIZONTAL JOINT EXTRUSION W/ WEEP HOLES @ 24" O.C. STACK JOINT W/ EXTRUSION BREAK-FORMED SPLICE PLATES BED SEALED IN SILICONE CONTINUOUS BUTYL SEALANT MARRIED TO SIDE JOINT GASKET. 5" MIN. BEARING 4"-14 HEX HEAD FASTENER WITH WASHER DW-4000 - VERTICAL INSTALLATION PARAPET COPING EXTRUSION SILICONE TUBE SEALANT TYP. STITCH TEKS TO TIE FLASHING IN PLACE FABRICATED METAL FLASHING EXTENSION 33 4" 15 8" STAINLESS STEEL SCREW PAINTED TO MATCH PANEL. 12" O.C. FASTENING CLIP CONTINUOUS BUTYL SEALANT WITH MARRIAGE BEAD TO HORIZONTAL PANEL JOINT 1 4"-14 HEX HEAD FASTENER WITH WASHER 2" OR 3" PARAPET COPING DW-4000 - VERTICAL INSTALLATION SEALANT MARRIAGE BEAD TO VERTICAL PANEL JOINT FASTENING CLIP PARAPET BLOCKING (NOT BY KINGSPAN) CONTINUOUS BUTYL SEALANT 1 4" - 14 HEX HEAD FASTENERS WITH WASHER PARAPET CAP FLASHING FASTENER TO PARAPET BACKER (NOT BY KINGSPAN) WRAP MEMBRANE ADHERE TO EXTERIOR PANEL FACE (NOT BY KINGSPAN) 1 4" - 14 "LOW PROFILE" FASTENER CONTINUOUS CLEAT MEMBRANE ROOF & PARAPET BACKER (NOT BY KINGSPAN) PARAPET W/ FLUSH TRIM DW-4000 - VERTICAL INSTALLATION WRAP MEMBRANE (NOT BY KINGSPAN) SEALANT MARRIAGE BEAD TO VERTICAL PANEL JOINT PARAPET BLOCKING (NOT BY KINGSPAN) CONTINUOUS BUTYL SEALANT FASTENING CLIP 1 4" - 14 HEX HEAD FASTENERS WITH WASHER WRAP MEMBRANE ADHERE TO EXTERIOR PANEL FACE (NOT BY KINGSPAN) FASTENER TO PARAPET BACKER (NOT BY KINGSPAN) PARAPET CAP FLASHING POP RIVET PARAPET W/ PROFILED TRIM MEMBRANE ROOF & PARAPET BACKER (NOT BY KINGSPAN) DW-4000 - VERTICAL INSTALLATION 'A' TRIM BACKER ROD AND SEALANT (NOT BY KINGSPAN) PENETRATION (NOT BY KINGSPAN) 'A' ELEVATION POP RIVET FASTENER (AS REQUIRED) SEALANT (NOT BY KINGSPAN) FLASHING SEALANT (NOT BY KINGSPAN) BACKER ROD AND SEALANT (NOT BY KINGSPAN) PENETRATION (NOT BY KINGSPAN) SECTION 'A-A' NOTES: 1. DO NOT ALIGN PENETRATIONS AT PANEL JOINT LOCATIONS. 2. FLASHING AT PENETRATIONS TO BE FIELD FABRICATED FROM FLATSTOCK SHEETS AS NECESSARY WALL PENETRATION SECTION DW-4000 - VERTICAL INSTALLATION 2" PANEL 2-PC CORNER BASE DIE #13264 2" PANEL BASE EXTRUSION DIE #11372 6" SPLICE PLATE DIE #13262 CORNER CAP DIE #13263 2" PANEL ENDWALL EXTRUSION RECEIVER DIE #11487 STACK EXTRUSION CAP ENDWALL EXTRUSION CAP CAP DIE #11488 2" PANEL STACK EXTRUSION BASE 2" PANEL HORIZONTAL JOINT EXTRUSION DIE #11298 2" PARAPET COPING EXTRUSION 2" PANEL SOFFIT EXTRUSION DIE #11423 SILL EXTRUSION DIE #KE6143 2" PANEL EXTRUSION DW-4000 - VERTICAL INSTALLATION 3" PANEL BASE EXTRUSION DIE #11366 3" PANEL ENDWALL EXTRUSION RECEIVER DIE #12714 ENDWALL EXTRUSION CAP CAP DIE #11488 3" PANEL 2-PC CORNER BASE 2-PC CORNER CAP DIE #13263 STACK EXTRUSION CAP 3" PANEL STACK EXTRUSION BASE 3" PANEL HORIZONTAL JOINT EXTRUSION DIE #12861 3" PANEL SOFFIT EXTRUSION SILL EXTRUSION DIE #KE6143 3" PANEL EXTRUSION 3" PANEL PARAPET COPING EXTRUSION DW-4000 - VERTICAL INSTALLATION LAP STRIP FOR TWO PIECE JAMB EXTRUSION LAP STRIP FOR BASE EXTRUSION LAP STRIPS FOR OUTSIDE CORNER EXTRUSION LAP STRIP FOR PARAPET EXTRUSION EXTRUSION LAP STRIPS LAP STRIPS FOR INSIDE CORNER EXTRUSION LAP STRIP FOR SOFFIT EXTRUSION DW-4000 - VERTICAL INSTALLATION FIELD CUT/NOTCH JAMB EXTRUSION AT HEAD AND JAMB (NOT BY KINGSPAN) SEALANT END DAM TWO PIECE HEAD EXTRUSION CAP 3 EXPOSED SEALANT (NOT BY KINGSPAN) N O PIE CE A HE EX D TW 2 TWO PIECE HEAD EXTRUSION BASE W/ FIELD DRILL 3 8 (NOT BY KINGSPAN) 1 TWO PIECE JAMB EXTRUSION BASE 6 EXPOSED SEALANT (NOT BY KINGSPAN) TWO PIECE JAMB EXTRUSION IO US TR 4 FIELD CUT/NOTCH JAMB EXTRUSION (NOT BY KINGSPAN) 5 N SIO U R TWO PIECE JAMB EXTRUSION CAP TWO PIECE JAMB EXTRUSION CAP T L SIL EX EXTRUSION AT FRAMED OPENINGS EXTRUSION INSTALLATION SEQUENCE: 1 TWO PIECE JAMB EXTRUSION BASE 2 TWO PIECE HEAD EXTRUSION BASE 3 TWO PIECE HEAD EXTRUSION CAP 4 TWO PIECE JAMB EXTRUSION CAP 5 SILL EXTRUSION 6 EXTERIOR SEALANTS AS REQUIRED DW-4000 - VERTICAL INSTALLATION 3" P N. MI LA M I TR (2) BEADS BUTYL SEALANT 3" N. AP I L M IM TR TRIM END LAP DW-4000 - VERTICAL INSTALLATION FIELD NOTCH HEM(S) AS REQUIRED (NOT BY KINGSPAN) 3" N. AP I L M IM TR (2) BEADS BUTYL SEALANT 3" N. AP I M L IM TR TRIM END LAP WITH HEM DW-4000 - VERTICAL INSTALLATION (2) BEADS BUTYL SEALANT 8" LONG LAP STRIP 1 " . 4 M NO AP G TRIM END LAP WITH LAP STRIP DW-4000 - VERTICAL INSTALLATION FIELD NOTCH AND OVERLAP TRIMS, POP RIVET AND SEAL AS NECESSARY (NOT BY KINGSPAN) FIELD MITER AND OVERLAP TRIMS, POP RIVET AS NECESSARY (NOT BY KINGSPAN) SEALANT END DAM 2 INTERIOR HEAD TRIM WITH TABS BENT DOWN IM TR D M OR RI I TR P A A HE T A C EXTERIOR CAP TRIM AT JAMB I OR RI E NT P CA D EA H AT TE EX 5 EXTERIOR HEAD TRIM W/ FIELD DRILL 3 8 (NOT BY KINGSPAN) 1 INTERIOR JAMB TRIM 6 EXPOSED SEALANT (NOT BY KINGSPAN) 3 SILL TRIM WITH TABS BENT UP RIM R 4 EXTERIOR JAMB TRIM FIELD CUT/NOTCH CAP TRIM AT CORNERS TO ALLOW FOR LAP (NOT BY KINGSPAN) ILL RIO TE X E FIELD CUT/NOTCH CAP TRIM AT CORNERS TO ALLOW FOR LAP (NOT BY KINGSPAN) PT CA TRIM AT FRAMED OPENINGS S AT FIELD MITER AND OVERLAP TRIMS, POP RIVET AND SEAL AS NECESSARY (NOT BY KINGSPAN) TRIM INSTALLATION SEQUENCE: 1 INTERIOR JAMB TRIM 2 INTERIOR HEAD TRIM WITH TABS DOWN 3 SILL TRIM WITH TABS UP 4 EXTERIOR JAMB TRIM 5 EXTERIOR HEAD TRIM 6 EXTERIOR SEALANTS AS REQUIRED DW-4000 - VERTICAL INSTALLATION FASTENING CLIP 2" FASTENING CLIP PART # 8100.2100 3" FASTENING CLIP PART # 8100.3100 ACCESSORIES