Addendum Number 1
Transcription
Addendum Number 1
Addendum Number 1 January 22, 2016 To All Bidders: Subject: Addendum No. 1 BJCC Forum Lifeguard Tenant Fit-Out Project No. 157380 Attached is Addendum No. 1 for the above referenced bid package. Please incorporate the document as part of your original bid package. If you have any questions please contact Scott Heywood by phone at (205) 585-5535; or via email at [email protected] Sincerely, Scott Heywood, AIA Director, Alabama Office Attachments: Pre Bid Meeting Notes, Sign In Sheet, and Impacted Sheets Addendum Number 1 This Addendum No. 1 is being issued prior to the bid opening to include and describe certain revisions and/or clarifications for the BJCC Forum Lifeguard Tenant Fit-Out. The bid specifications and drawings previously distributed shall govern the work described herein, unless otherwise modified by this Addendum. It is the intent of the Owner to include the following revisions and/or clarifications in this Addendum as part of the original specifications. Each Bidder is requested to include any and all costs associated with this Addendum in his proposal. Bidders must acknowledge receipt of this Addendum with their proposals on the appropriate form included in the Proposal Section of the specifications. GENERAL INFORMATION The following is general information that modifies the original bid documents. 1. The bid opening location has been moved from the Executive Board Room to the Forum Meeting Room “M” which is located on the first floor of the Forum Building. Drawings Revised/Added per Addendum #1 Sheet No. Description GI0-00-01 GI0-00-02 GI1-00-01 GI1-07-01 AE1-07-03 AE1-07-04 AE7-00-01 MH0-00-01 MD1-07-01 MH1-07-01 EP1-07-01 EP6-00-01 EP7-00-01 Updated Impacted Sheets Added door type and hardware set Added phasing sheet Modified plan to show transformer closet Modified plan to show transformer closet Modified plan to show transformer closet Modified finish schedule to reflect new closet Modified air terminal box schedule Modified demo plan to reflect new closet Modified plan to reflect new closet Modified plan to reflect new transformer and disconnect Modified one line diagram Modified panel schedule END OF ADDENDUM #1 26/08 Page 2 of 2 ED-BID-W-103 Birmingham-Jefferson Civic Center Authority Forum Building Lifeguard Tenant Fit-Out PRE-BID CONFERENCE AGENDA January 12, 2016 at 10:00 AM GENERAL 1. Bid Date / Time / Location: Tuesday, February 09, 2016, at 10:00 pm CST BJCC Forum Meeting Room “M” 1st Floor Forum Building Birmingham, AL 2. Introduction of Attendees: BJCC – Owner Consultant’s Team and Responsibility – Ghafari Sub consultants – Jill Hicks Design, Davis Dumas 3. Eligibility: See BJCC Front End Documents in Project Manual 4. Addenda: Minutes of Pre-Bid and any pertinent discussed items shall be issued as Addendum following prebid conference. Any further addenda necessary after Pre-Bid will be issued to all. 5. Project Coordination / Communication: All correspondence between Owner / Contractor /Consultant or sub consultants shall come through the Consultant from Contractor to the Owner. 6. Existing Conditions / Constraints: Construction staging and delivery routes to be identified by Owner. 7. Minority and Women-Owned Participation See specifications for BCIA requirements. 8. Meetings: Owner / Consultant / Contractor (OAC) progress meeting to be held weekly. PROJECT SPECIFIC REQUIREMENT 9. Other: Drawings are available on BJCC website, dated 01/11/16 Pre-Bid meeting 01/12/16 at 10:00 am Sub Contractor Tour TBD Last day for Bidder Questions in email format to [email protected] , 5:00 pm 02/02/16. Bid opening 02/09/16 at BJCC Forum Room “M” 10:00 AM CST. 1 OWNER COMMENTS 1. Specific BJCC requirements reviewed are: No smoking, chewing or dipping allowed on the property Professional attire is required, meaning no shorts, tank tops No guns, alcohol, drugs allowed on the property No offensive language All employees should be identifiable as being with the contractor, t-shirts with company name for instance Noisy work is not allowed except for the hours of 6pm to 6am Fire alarm testing is typically conducted at 6am or 6pm Dumpster to be located in dock off alley and it is an area where the contractor working on the Sheraton Corridor Renovations also has a dumpster located Waste service provider should be made aware of tight conditions and will be responsible for any damage to the soffit during removal of containers The freight elevator must be used for transport of people and material Notify BJCC of any issues with pan handlers 2 parking deck access cards will be provided to the general contractor 2. Requirement for questions on the work: All questions must be in writing to Jerry Nelms and Shelia Montgomery Mills, BJCC Will be answered in an addendum Must be submitted on week prior to bid opening. Question cut-off is seven days prior to bid opening. 3. Project specific discussion: Demolition will be completed prior to work beginning, 7th Floor only 7th floor, specifically the dispatch area is most critical, and is Phase 1 Salvage existing lights to be removed and not reused; to be placed on the 4th floor of the Forum Existing lights are to be reused Additional lights are to be provided from a stockpile on 4th floor Plans to be submitted to the City of Birmingham today OSHA is located in the building, 10th floor BJCC will work with Simplex to silence all devices for fire alarm The floors will be open again prior to bid day for further inspections, date to be set later Bulk of work on 7th floor The carpet will be quick ship There is some VCT, again will be readily available Plans will be sent to Simplex to help expedite the fire alarm plan and permit process There are two alternates for additional work requested by the tenant The tax exempt process is the same as for schools. Certificates will be required for the general contractor and subcontractors. Some cabinets that are being removed and stored during demolition will be installed on 8th floor by the contractor Electrical emergency power is within the scope of work Data drops, without wires is included Tenant to contract with 3rd party for data/phone/security installation There is a $20,000 contingency to be included in the bid price Keep the blinds clean and not be damaged, pull up all the way before work begins Water supply to be capped, it should be above the ceiling or below the floor Bidders must hold an Alabama General Contractor’s license and write the number on the outside of the envelope 2 Deadline for completion of the 7th floor Phase 1 is set for April 15th, 2016 at this time Addendum will be issued on when the remainder of the project is to be complete There is consideration of separating the permit to help expedite the CO for dispatch 3 0 1' 2' 0 112"=1'-0" 1' 2' 0 3 1"=1'-0" 2' 4' 0 1 4"=1'-0" 2' 4' 0 3 2"=1'-0" 4' 8' 0 1 8"=1'-0" 4' 8 0 3 4"=1'-0" 8' 16' 0 1 16"=1'-0" 8' 16' 0 3 8"=1'-0" 16' 32' 0 32' 0 1 32' 64' 32"=1'-0" SHEET TITLE 01-04-16 DR01 Review 01-06-16 DR02 Demo Pricing 01-11-16 DR03 Construction 01-22-16 DR04 Addendum 1 01-04-16 DR01 Review 01-06-16 DR02 Demo Pricing 01-11-16 DR03 Construction 01-11-16 DR04 Addendum 1 ISSUED FOR BJCC FORUM BUILDING LIFEGUARD TENANT FIT-OUT 16' 1 16"=1'-0" 32"=1'-0" ELECTRICAL GHAFARI ASSOCIATES, LLC 2816 6TH AVENUE SOUTH BIRMINGHAM, AL 35233 USA TEL +1.205.585.5535 www.ghafari.com GENERAL EP0-00-01 ELECTRICAL GENERAL NOTES, SYMBOLS, ABBREVIATIONS GI0-00-01 COVER SHEET/GENERAL INFORMATION ED1-07-01 ELECTRICAL 7TH FLOOR PLAN DEMOLITION GI0-00-02 GENERAL NOTES/OPENING SCHEDULES/PARTITION LEGEND ED1-08-01 ELECTRICAL 8TH FLOOR PLAN DEMOLITION GI1-00-01 CONSTRUCTION PHASING PLAN EL1-07-01 ELECTRICAL 7TH FLOOR PLAN LIGHTING GI1-01-01 CONSTRUCTION ACCESS PLAN EL1-08-01 ELECTRICAL 8TH FLOOR PLAN LIGHTING GI1-07-01 7TH FLOOR LIFE SAFETY PLAN EP1-07-01 ELECTRICAL 7TH FLOOR PLAN POWER & COMMUNICATIONS GI1-08-01 8TH FLOOR LIFE SAFETY PLAN EP1-08-01 ELECTRICAL 8TH FLOOR PLAN POWER & COMMUNICATIONS ARCHITECTURAL EP6-00-01 ELECTRICAL LIGHTING SCHEDULE AND ONE LINE DIAGRAM AE1-07-01 7TH FLOOR DEMOLITION PLAN EP7-00-01 ELECTRICAL PANEL SCHEDULES AE1-07-02 7TH FLOOR DEMOLITION CEILING PLAN AE1-07-03 7TH FLOOR NEW WORK PLAN AE1-07-04 7TH FLOOR CEILING PLAN FORUM BUILDING 2100 RICHARD ARRINGTON JR. BLVD. N. BIRMINGHAM, AL 35203 AE1-08-04 8TH FLOOR CEILING PLAN MECHANICAL DETAIL LOCATION IDENTIFICATION 8" (200) TTD ALTERNATE LOCATION MEASURED TO TOP OF RIM OR COUNTER (WHICHEVER IS HIGHER) FRONT VIEW 8" (203) MIN 11" (280) MIN FOLDING SEAT 3'-0" (915) MIN 2'-3" (685) MIN BF ACCESSIBLE SHOWER SEAT STANDARD SHOWER HEAD, VALVES AND CURTAIN ROD AE1-02-M1 AE1-02-M1 1 6" (150) MAX 500 750 1000 1 SEAT COVER DISPENSER 9" (230) MIN PAPER TOWEL DISPENSER TOWEL DISPENSER AND WASTE RECEPTACLE WASTE RECEPTACLE SOAP SANITARY DISH NAPKIN DISPENSER SOAP DISPENSER ELECTRIC HAND DRYER ACCESSORIES FIRE VALVE CABINET FIRE HOSE RACK OR VALVE FIRE EXTINGUISHER AND WALL BRACKET FIRE ALARM STROBE FIRE ALARM PULL BOX THERMOSTAT FIRE EQUIPMENT 33" (838) 4'-0" (1220) MAX ELECTRIC PANEL 36" (915) ELECTRICAL OUTLETS LOCATED NEAR LAVATORIES IN BF ACCESSIBLE TOILET ROOMS TO HIGHEST DISCONNECT 4'-6" (1370) BF ACCESSIBLE 4'-0" (1220) MAX TEMPERATURE SENSOR ALIGNED WITH STROBE WHEN ON SAME WALL 6'-6" (1980) 7'-6" (2285) OR AS NOTED 3'-6" (1065) 5'-0" (1525) 4'-0" (1220) MAX 3'-6" (1065) WHEN EXTINGUISHER GROSS WEIGHT EXCEEDS 40 LBS AHU ALT ALUM ANOD AP APC APPROX ARCH AWP B/B BC BD BF BLDG BLKG BLW BM BOT BRG BSMT BTWN BUR BACK TO BACK BOTTOM CHORD BOARD BARRIER FREE BUILDING BLOCKING BELOW BEAM BOTTOM BEARING BASEMENT BETWEEN BUILT-UP ROOF C/C C CB CFLG CI CJ CL CLG CLL CLO CLR CMU CO COL CONC CONN CONSTR CONSTR JT CONT CONTR COORD CPT CSMU CENTER TO CENTER COURSES CATCH BASIN COUNTER FLASHING CAST IRON CONTROL JOINT CENTERLINE CEILING CONTRACT LIMIT LINE CLOSET CLEAR CONCRETE MASONRY UNIT CLEAN OUT COLUMN CONCRETE CONNECT (ED, ION, ING) CONSTRUCTION CONSTRUCTION JOINT CONTINUOUS (ATION) CONTRACTOR COORDINATE CARPET CALCIUM SILICATE MASONRY UNIT CERAMIC TILE CURTAIN WALL OUTLETS AT BF ACCESSIBLE LAVATORIES LIGHT SWITCH ELECTRICAL CT CW 10' 20' 0 1"=20'-0" 20' 40' 0 1"=30'-0" 30' 60' 0 1"=40'-0" 40' CT R ED A A L HI C R ST COLUMN INDICATION 4 GD-1HR WINDOW IDENTIFICATION NUMBER Wall Tag COLUMN IDENTIFICATION LETTER OR NUMBER FOR NEW CONSTRUCTION 3 A ROOF OR RAMP PITCH INDICATION COLUMN IDENTIFICATION LETTER OR NUMBER FOR EXISTING CONSTRUCTION 12 MATERIAL OR WORK DIVISION INDICATION 3.1 EXISTING NEW ROOF OR RAMP SLOPE INDICATION SLOPE BUILDING SECTION REVISION INDICATION 1 MATCH LINE ZONE "A"- SEE SHEET AE-101 SHEET IDENTIFICATION NUMBER (INDICATES SHEET NUMBER WHERE SECTION IS DRAWN) ARCHITECT/ENGINEER ANCHOR BOLT ABOVE ALUMINUM COMPOSITE MATERIAL ACOUSTICAL ADDENDUM ADJACENT ABOVE FINISH FLOOR AUTHORITY HAVING JURISDICTION AIR HANDLING UNIT ALTERNATE ALUMINUM ANODIZED ACCESS PANEL ACOUSTICAL PANEL CEILING APPROXIMATE (LY) ARCHITECT ACOUSTICAL WALL PANELS ACOUS ADDM ADJ AFF AHJ HEIGHT OF DISPENSER OR OPERATING CONTROLS 4'-0" (1220) BF ACCESSIBLE 3'-3" (990) 1'-6" (455) MAX DRESSING MIRROR BF MIRROR (WHEN NOT ABOVE COUNTER OR LAVATORY) IN G H A M , WINDOW NUMBER INDICATION ELECTRIC WATER COOLERS A/E AB ABV ACM 2'-11" (890) MAX 5'-0" (1525) SHELF WITH MOP & BROOM HOLDERS RM 100'-0" (30480) ABBREVIATIONS TOILET PAPER DISPENSER TE DETAIL SECTION AE1-02-M1 2'-6" (760) WHEN MOUNTED BELOW GB BI 11" (280) MIN ELECTRIC WATER COOLER (HIGH-LOW) SHOWER ACCESSORIES LAVATORIES B O SPOT ELEVATION NEW DOOR INDICATION WALL SECTION AE1-02-M1 SC A 1 SIDE VIEW STANDARD & BF 1'-7" (485) FINISHED FLOOR MATCH LINE INDICATION FRAMED MIRROR STANDARD & BF 250 SECTION IDENTIFICATION NUMBER (SAME NUMBER ON SHEET WHERE DRAWN) 1 R . HEY W EL = 100'-0" (30480) 4 AE2-132 2 8" (205) MIN 9" (230) MIN 1'-5" (430)MIN 1'-7" (485) MAX 3'-4" (1015) 6'-0" (1830) OVERFLOW PROJECTION INTO CLEAR SPACE PERMITTED 9" (230) MIN 2'-3" (685) MIN 6" (152) MAX UP POSITION MIXING VALVE TT 1 AE2-200 1'-3" (380) S ELEVATION INDICATION -(FLOORS, ETC...) 2' PARTITION TYPE INDICATION SECTION LOCATION IDENTIFICATION FRONT APPROACH 5" (125) MAX SIDE APPROACH 3 1/2" (90) MAX 3'-3" (990) MAX WALL MOUNTED LAVATORY 3'-3" (990) MAX 3'-4" (1015) MIN 2'-10" (865) MAX TOP OF LAVATORY 1'-5" (430) MIN O F A LA 7012 DOOR INDICATION 1' FUTURE WORK O 100 6 6'-0" (1830) FRAMED MIRROR, INSTALL AT TOP OF LAVATORY ELEVATION IDENTIFICATION NUMBER(S) INDICATES DIRECTION OF VIEW OR VIEWS (SAME NUMBER ON SHEET WHERE DRAWN) WALL TE NEW WORK 1 DOOR IDENTIFICATION NUMBER (STARTS ALWAYS WITH ROOM NUMBER) 1:10 SHEET IDENTIFICATION NUMBER (INDICATES SHEET NUMBER WHERE ELEVATION IS DRAWN) SHOWER HEAD DEMOLITION WORK 1 DOOR NUMBER INDICATION 0 ELEVATION LOCATION IDENTIFICATION 1 TOILET ACCESSORIES 1 1"=1'-0" 0 TOILET ROOM A ROOM IDENTIFICATION NUMBER GRAPHIC SCALE SHEET IDENTIFICATION NUMBER (INDICATES SHEET NUMBER WHERE DETAIL IS TYPICALLY REFERENCED NOT ALL INCLUSIVE) 2'-6" (760) 1'-7" (485) 10" (250) 4'-0" (1220) KEYED NOTE SYMBOLS 100 SHEET IDENTIFICATION NUMBER (INDICATES SHEET NUMBER WHERE PLAN OR SECTION DETAIL IS DRAWN 1 VIEW NAME AE1-02-M1 NOT TO SCALE ACCESSIBLE CURTAIN ROD WALL 2'-6" (760) 8TH FLOOR HVAC PIPING PLAN ROOM NAME AE1-02-M1 TITLE IDENTIFICATION 3'-6" (1065) MIN (455) 1'-6" 3'-8" (1120) MAX 2'-10" (860) 2'-10" (860) (430) '-5" 2'-0" (610) (430) MAX 2'-6" (760) 3'-8" (1120) MAX 1'-5" 7TH FLOOR HVAC PIPING PLAN MP1-08-01 GI SND WATER CLOSETS & ACCESSORIES INSULATE EXPOSED PIPING C:\ghafari local cache\projectwise2015\dms87260\157380GI0-00-01.dwg MP1-07-01 D TTD OUTLET ACCESSIBLE STANDARD WALL SHEYWOOD 8TH FLOOR HVAC PLAN-NEW WORK RE TTD TOP OF SEAT 1'-5" (430) MIN 1'-7" (480) MAX 1'-6" (455) URINALS 0 7TH FLOOR HVAC PLAN-NEW WORK MH1-08-01 1 SECTION IDENTIFICATION NUMBER (SAME NUMBER ON SHEET WHERE REFERENCED) GB 3'-5" (1040) 1"=10'-0" 8TH FLOOR HVAC PLAN-DEMOLITION MH1-07-01 O GB 1 1/2" (38) CLEAR TO WALL, TYP 1'-0" (305) MIN GB 9" (230) MIN 1/25/2016 8:21:52 AM WALL 1'-0" (305) 3'-6" (1065) 3'-0" (915) URINAL SCREEN FLUSH VALVE (OPEN SIDE OF WC) FIRE EXTINGUISHER CABINET 7TH FLOOR HVAC PLAN-DEMOLITION MD1-08-01 MA PARTITION SANITARY NAPKIN RECEPTACLE MD1-07-01 A 5'-0" (1525) MIN CLEAR 3'-0" (915) INFORMATION PROVIDED APPLIES TO: WALL MOUNTED LAVATORIES BARRIER FREE LAVATORIES COUNTER MOUNTED LAVATORIES STANDARD LAVATORIES PARTIAL 7TH AND 8TH FLOOR PLANS ROOM NAME AND NUMBER INDICATION PLAN OR SECTION DETAIL IDENTIFICATION NUMBER (SAME NUMBER ON SHEET WHERE DRAWN) NORTH 5'-0" (1525) DIAMETER 1'-6" (455) WALL 4'-0" (1220) MAX WALL 3'-4" (1015) WALL BOTTOM EDGE OF MIRROR REFLECTIVE SURFACE PP1-07-01 TE PLAN IDENTIFICATION 2'-10" (865) WALL 1'-3" (380) MIN SCHEDULES, NOTES, LEGENDS, DETAILS, AND RISERS REFERENCE SYMBOLS SCALE: 1/8" = 1'-0" (1 :20) STANDARD PD1-07-01 MH0-00-01 HVAC SCHEDULES AND DETAILS DIMENSIONS ARE PROVIDED IN IMPERIAL FEET-INCH UNITS. SI MILLIMETER UNITS ARE PROVIDED IN PARENTHESIS. ACCESSIBLE post office box 530802 birmingham, alabama 35253 tele: 205-871-0484 AE7-00-01 FINISH SCHEDULE, FINISH NOTES, FINSH DETAILS, AND INTERIOR ELEVATIONS NOTES: INSTALLATION DETAILS SHOWN ARE TYPICAL FOR ALL CONDITIONS WHERE EQUIPMENT, ACCESSORIES AND FIXTURES MAY OCCUR, UNLESS OTHERWISE NOTED OR DIMENSIONED ON THE DRAWINGS EQ Jill Hicks Design, LLC AE1-08-03 8TH FLOOR NEW WORK PLAN MOUNTING DETAILS EQ jh AE1-08-01 8TH FLOOR DEMOLITION PLAN AE1-08-02 8TH FLOOR DEMOLITION CEILING PLAN 80' 0 1"=50'-0" 50' 100' 0 1"=60'-0" D DEMO DEPT DET DF DIA DIAG DIM DL DN DR DWG DEPTH/DEEP DEMOLITION DEPARTMENT DETAIL DRINKING FOUNTAIN DIAMETER DIAGONAL DIMENSION DEAD LOAD DOWN DOOR DRAWING GA GAL GALV GB GC GDR GL GLZ GND GR GYP GYP BD GAUGE GALLON GALVANIZED GRAB BAR GENERAL CONTRACTOR GUARD RAIL GLASS GLAZING GROUND GRADE GYPSUM GYPSUM BOARD EA EJ EL ELEC ELEV EMER EMER SHR ENGR EOS EPDM EACH EXPANSION JOINT ELEVATION ELECTRICAL ELEVATOR EMERGENCY EMERGENCY SHOWER ENGINEER EDGE OF SLAB ETHYLENE PROPYLENE DIENE MONOMER EQUAL EQUIPMENT ELECTRICAL WATER COOLER EXISTING EXPANSION EXPANSION BOLT EXTERIOR H HB HM HMD HMF HORIZ HP HR HIGH HOSE BIB HOLLOW METAL HOLLOW METAL DOOR HOLLOW METAL FRAME HORIZONTAL HIGH POINT HOURS (FIRE-RESISTANT RATING) HEIGHT EQ EQUIP EWC EX, EXIST EXP EXP BT EXT 60' F/F FA FBD FD FDTN FE FEC FF FGL FHC FIN FIN FL FIN GR FIXT FLASH FLR FLR FIN FLUOR FR FRMG FRP FACE TO FACE FIRE ALARM FIBERBOARD FLOOR DRAIN FOUNDATION FIRE EXTINGUISHER FIRE EXTINGUISHER CABINET FACTORY FINISH FIBERGLASS FIRE HOSE CABINET FINISH (ED) FINISH FLOOR FINISH GRADE FIXTURE FLASHING FLOOR FLOOR FINISH FLUORESCENT FIRE RATING, FIRE RATED FRAMING FIBERGLASS REINFORCED PANEL FIRE-RETARDANT TREATED FOLDING SHOWER SEAT FOOT, FEET FOOTING FURRING FIRE VALVE CABINET FRT FSS FT FTG FURR FVC 120' 0 1"=80'-0" 80' HT ID IDF IE IN INFO INT INSUL INSIDE DIAMETER INTERMEDIATE DISTRIBUTION FRAME INVERT ELEVATION INCH, INCHES INFORMATION INTERIOR INSULATION, INSULATED JC JANITOR'S CLOSET km km2 KILOMETER SQUARE KILOMETER L LAV LF LL LLH LLV LP LT LTG LENGTH, LONG LAVATORY LINEAR FEET LIVE LOAD LONG LEG HORIZONTAL LONG LEG VERTICAL LOW POINT LIGHT LIGHTING m m2 MACH RM MARB MAS MAX MCR MDF MDF MECH MEZZ METER SQUARE METER MACHINE ROOM MARBLE MASONRY MAXIMUM MAIN COMMUNICATION ROOM MEDIUM DENSITY FIBERBOARD MAIN DISTRIBUTION FRAME MECHANICAL MEZZANINE MFR MH MIN MIR MKR BD mm mm2 MO MTD MTG MTL MANUFACTURER MANHOLE MINIMUM MIRROR MARKER BOARD MILLIMETER SQUARE MILLIMETER MASONRY OPENING MOUNTED MOUNTING METAL N NA NIC NOM NTS NORTH NOT APPLICABLE NOT IN CONTRACT NOMINAL NOT TO SCALE O/O OA OC OD OFCI OH OPNG ORD OS OUT TO OUT OVERALL ON CENTER OUTSIDE DIAMETER OWNER FURNISHED CONTRACTOR INSTALLED OWNER FURNISHED OWNER INSTALLED OPPOSITE HAND OPENING OVERFLOW ROOF DRAIN OVERFLOW SCUPPER PBD PH PL PLAM PLAS PLYWD PNL(S) PNT PREFAB PREFIN PRELIM PREP PROJ PSF PSI PT PTD PTR PVC PARTICLE BOARD PENTHOUSE PLATE PLASTIC LAMINATE PLASTER PLYWOOD PANEL(S) PAINT, PAINTED PREFABRICATED PREFINISHED PRELIMINARY PREPARATION PROJECT POUNDS PER SQUARE FOOT POUNDS PER SQUARE INCH PRESSURE TREATED PAPER TOWEL DISPENSER PAPER TOWEL RECEPTACLE POLYVINYL CHLORIDE QTY QUANTITY OFOI R RA RAD RB RCP RD REF REINF REQD RES REV RF RLG RM RO RTU RISER RETURN AIR RADIUS RESILIENT BASE REFLECTED CEILING PLAN ROOF DRAIN REFERENCE REINFORC (ING, ED, MENT) REQUIRED RESILIENT REVISION RESILIENT FLOORING RAILING ROOM ROUGH OPENING ROOF TOP UNIT SA SAB SUPPLY AIR SOUND ATTENUATION BLANKETS SALVAGE SEAT COVER DISPENSER SCHEDULE SOAP DISPENSER SADDLE SECTIONAL DOOR SECTION SQUARE FOOT SPRAYED FOAM INSULATION SPRAYED FIRE RESISTIVE MATERIALS SHOWER SHEET SHEATHING INTERNATIONAL SYSTEM OF UNITS SIMILAR SLIP JOINT SEALANT SANITARY NAPKIN DISPOSAL SANITARY NAPKIN VENDOR SPECIFICATION SPRINKLER SQUARE SQUARE INCH SQUARE YARD SERVICE SINK STAINLESS STEEL SOUND TRANSMISSION CLASS STANDARD STEEL STEEL JOIST STEEL STEEL JOIST STEEL PLATE STONE STORAGE SALV SCD SCHED SD SDL SE SECT SF SFI SFRM SHR SHT SHTHG SI SIM SJ SLNT SND SNV SPEC SPKLR SQ SQ IN SQ YD SS SST STC STD STL STL JST STL STL JST STL PL STN STOR STRUCT STRUCT STL SUSP SUSP CLG STRUCTURAL STRUCTURAL STEEL SUSPENDED SUSPENDED CEILING T TB TD TDR TYP TREAD TOWEL BAR TOWEL DISPENSER TOWEL DISPENSER/ RECEPTACLE TELEPHONE TEMPORARY TERRAZO THICKNESS, THICK THRESHOLD THROUGH TACKBOARD TEMPERED TEMPERED GLASS TOP OF BEAM TOP OF CONCRETE TOP OF STEEL TOILET TISSUE DISPENSER TOILET TISSUE JUMBO DISPENSER TYPICAL UG UL UNEX UNO UON UR UNDERGROUND UNDERWRITERS LABORATORY UNEXCAVATED UNLESS NOTED OTHERWISE UNLESS OTHERWISE NOTED URINAL VERT VEST VIF VR VTR VERTICAL VESTIBULE VERIFY IN FIELD VAPOR RETARDER VENT THROUGH ROOF W/ W/O W WC WCG WD WF WGL WH WP WR WWF WWM WITH WITHOUT WIDE, WIDTH WATER CLOSET WALL COVERING WOOD WIDE FLANGE WIRED GLASS WATER HEATER WORKING POINT WASTE RECEPTACLE WELDED WIRE FABRIC WELDED WIRE MESH TEL TEMP TER THK THRES THRU TK BD TMPD TMPD GL TOB TOC TOS TTD TTJ REV 01-22-16 DR04 Addendum 1 01-11-16 DR03 Construction 01-05-16 DR02 Demo Pricing DATE ISSUED FOR FORUM BUILDING TENANT FIT-OUT FOR LIFEGUARD AMBULANCE PROJECT # PROJECT MANAGER 157380.000 S.HEYWOOD DESIGNED BY DRAWN BY S. HEYWOOD QUALCHECK SHEET TITLE S. HEYWOOD COVER SHEET/ GENERAL INFORMATION GI0-00-01 SHEET NUMBER 160' 0 1"=100'-0" 100' 200' 0 1"=200'-0" 200' 400' 0 1"=400'-0" 400' 800' 0 1"=500'-0" 500' 1000' 0 1"=1000'-0" 1000' 2000' 0 3 2' 200 - DEMOLITION NOTES 101. 201. SEE SPECIFICATIONS FOR FURTHER INFORMATION ON DEMOLITION WORK. 203. WHERE EXISTING CONSTRUCTION IS FOUND TO CONTAIN ASBESTOS, NOTIFY THE OWNER AND THE ARCHITECT IN WRITING. REMOVAL, DISPOSAL AND REPLACEMENT OF THE ASBESTOS MATERIAL SHALL BE IN ACCORDANCE WITH FEDERAL, STATE AND LOCAL REGULATIONS. (REPLACE THE ASBESTOS MATERIAL WITH NEW MATERIAL AS APPROVED BY THE ARCHITECT.) 103. DIMENSIONS SHOWN ON NEW WORK PLANS ARE TO CENTERLINE OF COLUMNS, FACE OF FINISH (FOF) OF INTERIOR WALLS, TO FACE OF CONCRETE OR MASONRY WALLS (FOM), TO FACE OF FINISH (FOF) FOR EXTERIOR WALLS; UNLESS OTHERWISE NOTED OR DETAILED. 104. 204. THE CONTRACTOR SHALL VERIFY THAT EXIT EGRESS IS MAINTAINED FOR ALL OCCUPIED AREAS THROUGH-OUT DURATION OF WORK. 205. THESE DRAWINGS HAVE BEEN DEVELOPED FROM EXISTING DRAWINGS WHICH MAY NOT REFLECT ACTUAL FIELD CONDITIONS. THE CONTRACTOR SHALL VERIFY THESE DRAWINGS WITH THE EXISTING FIELD CONDITIONS AND NOTIFY THE ARCHITECT IMMEDIATELY OF INCONSISTENCIES BETWEEN THESE DRAWINGS AND ACTUAL CONDITIONS BEFORE PROCEEDING WITH CONSTRUCTION. SEE FLOOR PLANS FOR: RATED WALL DESIGNATIONS; DOOR DESIGNATIONS; PASS/VIEW WINDOW DESIGNATIONS; LOCATION OF LEAD LINED WALLS; DETAIL, SECTION AND ELEVATION MARKERS; AND ADDITIONAL NOTES. 105. ALL NEW WALLS TO HAVE SOUND ATTENUATION BATTS INSTALLED TO COMPLETELY FILL THE WALL CAVITY. NO VOIDS ARE ALLOWED. 107. 108. 3'-0" 3'-0" 2" 8 0 3 8' 16' 210. AFTER REMOVAL OF PIPE CHASES, PATCH HOLES IN EXISTING FLOORS OR WALLS TO REMAIN TO MEET ORIGINAL FIRE PROTECTION AND STRUCTURAL REQUIREMENTS. 218. WHERE ABOVE-CEILING WORK IS REQUIRED, THE EXISTING LAY-IN CEILINGS SHALL BE REMOVED AND REINSTALLED (UNLESS A NEW CEILING IS INDICATED). THE CONTRACTOR SHALL TAKE CARE NOT TO DAMAGE EITHER THE CEILING TILES OR THE GRID. ANY DAMAGED TILES OR GRID SHALL BE REPLACED WITH NEW MATERIAL. THE NEW MATERIALS SHALL MATCH THE EXISTING IN A UNIFORM MANNER FOR COLOR, TEXTURE, PATTERN, ETC. IF UNIFORMITY CAN NOT BE ACHIEVED, THE CONTRACTOR SHALL REPLACE THE ENTIRE CEILING WITHIN THAT SPACE WITH NEW MATERIAL. THE CONTRACTOR SHALL PROVIDE NEW MATERIAL AS APPROVED BY BOTH OWNER AND ARCHITECT. NEW CASED GYPSUM BOARD DOOR OPENING. FINISH ALL SIDES WITH PAINTED GYPSUM BOARD. 302. WHERE INDICATED ON THE NEW WORK PLANS, FURR OUT RATED WALL, RATED SMOKE WALL OR RATED METAL STUDS (OF ADEQUATE DEPTH AS REQUIRED FOR 6'-0" CLEAR CAULK PAINT NEW HM FRAME NEW BUILT-UP WOOD FRAME PAINTED NEW SOLID CORE WOOD DOUBLE DOOR NEW TEMPERED GLAZING DOOR NUMBER B. FIRESTOPPING OF PENETRATIONS AND JOINTS IN NEW RATED PARTITIONS. C. FIRESTOPPING OF NEW PENETRATIONS AND JOINTS IN EXISTING RATED ASSEMBLIES. DOUBLE RABBET HM DOOR FRAME PAINTED FRAME DOOR DOOR SIZE TYPE MAT'L FINISH MAT'L FINISH HARDWARE SET FIRE RATING EXISTING DOOR LOCATION SEE DEMO PLANS 2 NOTES 2 700A 6'-0" x 7'-0" D WOOD PAINT METAL PAINT 702 3'-0" x 7'-0" A WOOD PAINT METAL PAINT 7B 1 709 3'-0" x 7'-0" A WOOD PAINT METAL PAINT 7A 1 1 713 3'-0" x 7'-0" A WOOD PAINT METAL PAINT 7C 714 3'-0" x 7'-0" A WOOD PAINT METAL PAINT 7D 1 1 715 3'-0" x 7'-0" A WOOD PAINT METAL PAINT 717 3'-0" x 7'-0" A WOOD PAINT METAL PAINT 7F 1 718 3'-0" x 7'-0" A WOOD PAINT METAL PAINT 7H 1 719 3'-0" x 7'-0" A WOOD PAINT METAL PAINT 7G 1 805 3'-0" x 7'-0" A WOOD PAINT METAL PAINT 8G 1 806A 3'-0" x 7'-0" B WOOD PAINT METAL PAINT 819 3'-0" x 7'-0" A WOOD PAINT METAL PAINT 8F 1 820 3'-0" x 7'-0" B WOOD PAINT METAL PAINT 821 3'-0" x 7'-0" A WOOD PAINT METAL PAINT 8E 1 823 3'-0" x 7'-0" C 3/8" TEMPERED GLAZING 824 3'-0" x 7'-0" A WOOD PAINT METAL PAINT 8D 1 826 3'-0" x 7'-0" A WOOD PAINT METAL PAINT 8C 1 PAINTED WOOD TRIM TO MATCH EXISTING WINDOW PROFILE 827 3'-0" x 7'-0" A WOOD PAINT METAL PAINT 8B 1 829 3'-0" x 7'-0" A WOOD PAINT METAL PAINT 8A 1 848 3'-0" x 7'-0" A WOOD PAINT METAL PAINT 8H 1 1'-5" PAINTED WOOD TRIM TO MATCH EXISTING WINDOW PROFILE 2 PLACES S GYP BOARD 1. 2. FLOOR LEVEL SEE H2 FOR WOOD TRIM DIMENSIONS S1 SHEYWOOD 0 2" MIN. 8" CONT ACOUSTICAL SEALANT CONT SEALANT CONT ACOUSTICAL SEALANT 0 20' 40' 30' A L HI C R EXISTING DOOR TO BE INSTALLED AND PAINTED PER FINISH SCHEDULE UNDERCUT BOTH DOORS TO PROVIDE REQUIRED VENTILATION FOR TRANSFORMER THE CONTRACTOR SHALL CAREFULLY STUDY & COMPARE THE CONTRACT DOCUMENTS, THIS SCHEDULE, & SHALL AT ONCE REPORT TO THE ARCHITECT ANY ERROR, INCONSISTENCY OR OMISSIONS THAT HE MAY DISCOVER. 2. ALL FRAMES SHALL BE CAULKED CONTINUOUSLY TO THE WALL, COLOR TO BE CLEAR. 3. NON-RATED DOORS MAY BE UNDERCUT 5/8" MAXIMUM. DOORS IN RATED AND/ OR SMOKE WALLS SHALL NOT BE UNDERCUT. 4. WHEREVER THERE IS A CRACK LEFT BETWEEN THE BOTTOM OF THE DOOR FRAME & THE FINISH FLOOR, THE CONTRACTOR SHALL PROVIDE A "PENCIL-LINE CAULK" TO SEAL THIS CRACK (EXCEPT WHERE CARPET HIDES THE CRACK). 5. DOORS SCHEDULED TO HAVE A FIRE RATING LABEL SHALL HAVE A METAL LABEL PERMANENTLY AFFIXED TO BOTH THE DOOR AND TO THE DOOR FRAME. (A VINYL LABEL IS NOT ACCEPTABLE. AN EMBOSSED LABEL IN THE FRAME ITSELF IS ALSO NOT ACCEPTABLE). 6. ALL THRESHOLDS SHALL CONFORM TO THE REQUIREMENTS OF THE MOST CURRENT EDITION OF THE ANSI A117.1 HANDICAP CODE, THE AMERICANS WITH DISABILITIES ACT. 7. THE CONTRACTOR SHALL VERIFY THAT CLOSERS AND OTHER HARDWARE WILL ALLOW THE DOOR TO OPEN 180 DEGREES WHEN SUCH 180 DEGREE DOOR SWINGS ARE INDICATED ON THE FLOOR PLAN. 8. ALL EXISTING HARDWARE REMOVED FROM EXISTING DOORS IS PROPERTY OF BJCC. 9. GC TO REPLACE ALL DOORS AND FRAMES THAT DO NOT MEET THE SCHEDULED FIRE RATING TO MATCH EXISTING. 10. ALL KEYING BY BJCC. SEE H2 FOR WOOD TRIM DIMENSIONS REV WIDTH 3 3/4" 3 3/4" 3 3/4" 4 7/8" 4 7/8" 4 7/8" 5 1/4" 5 1/4" 5 1/4" 7 1/4" 7 1/4" 7 1/4" MARK GD02-0E GD02-0F GD02-0G GD03-0E GD03-0F GD03-0G GD04-0E GD04-0F GD04-0G GD06-0E GD06-0F GD06-0G 60' 0 1"=40'-0" 40' 80' 0 1"=50'-0" OF FASTENER MAX HT (5 PSF) MAX HT (10 PSF) FIRE ACOUSTIC PROPERTIES L/240 L/360 L/240 L/360 RATING STC INSUL THK TEST NO. 15' 5" 13' 5" 0 HR 0 0" 11' 10" 10' 5" 0 HR 0 0" 11' 6" 10' 1" 0 HR 0 0" 20' 6" 17' 11" 0 HR 40 0" USG-860808 14' 3" 12' 6" 0 HR 40 0" USG-860808 13' 9" 12' 0" 0 HR 40 0" USG-860808 22' 1" 19' 4" 0 HR 40 0" USG-860808 15' 2" 13' 3" 0 HR 40 0" USG-860808 14' 6" 12' 11" 0 HR 40 0" USG-860808 30' 5" 26' 7" 0 HR 40 0" USG-860808 20' 4" 17' 11" 0 HR 40 0" USG-860808 18' 10" 16' 9" 0 HR 40 0" USG-860808 50' DR04 Addendum 1 01-11-16 DR03 Construction 01-04-16 DR01 Review DATE ISSUED FOR EACH TO RECEIVE: BASE/HEAD STUD STUD STUD FINISH FINISH SIZE GAUGE SPACING SIDE A SIDE B 2 1/2" 16 16" 5/8" GWB 5/8" GWB 2 1/2" 20 24" 5/8" GWB 5/8" GWB 2 1/2" 25 24" 5/8" GWB 5/8" GWB 3 5/8" 16 16" 5/8" GWB 5/8" GWB 3 5/8" 20 24" 5/8" GWB 5/8" GWB 3 5/8" 25 24" 5/8" GWB 5/8" GWB 4" 16 16" 5/8" GWB 5/8" GWB 4" 20 24" 5/8" GWB 5/8" GWB 4" 25 24" 5/8" GWB 5/8" GWB 6" 16 16" 5/8" GWB 5/8" GWB 6" 20 24" 5/8" GWB 5/8" GWB 6" 25 24" 5/8" GWB 5/8" GWB 01-22-16 3 EA BALL BEARING BUTTS MATCH BUILDING STANDARD 1 EA MORTISE FIRE EXIT DEVICE MATCH BUILDING STANDARD 1 EA PERMANENT CYLINDER MATCH BUILDING STANDARD 1 EA CLOSER MATCH BUILDING STANDARD 1 EA WALL STOP MATCH BUILDING STANDARD FORUM BUILDING TENANT FIT-OUT FOR LIFEGUARD AMBULANCE EACH TO RECEIVE: PLAN 0 1"=30'-0" R ED A 1 HARDWARE SET 2 5/8" GYPSUM BOARD EA FACE 1"=20'-0" IN G H A M , 1 METAL STUD SOUND ATTENUATION BLANKET (EXCEPT 2 1/2" STUD WALL) 20' RM GENERAL DOOR NOTES CUT STUDS 1/2" SHORT OF TOP RUNNER TO ALLOW FOR DEFLECTION, DO NOT FASTEN GYP BD TO RUNNER BASE/HEAD 10' TE HARDWARE SET 1 1 OF FASTENER 5/8" FIRE RATED GYP BD EA FACE 1"=10'-0" BI DOOR NOTES LINE OF CEILING FIRE RATING 1 HR/UL DES U494 1 HR/UL DES U494 1 HR/UL DES U494 1 HR/UL DES U465 1 HR/UL DES U465 1 HR/UL DES U465 1 HR/UL DES U465 1 HR/UL DES U465 1 HR/UL DES U465 1 HR/UL DES U465 1 HR/UL DES U465 1 HR/UL DES U465 B O 7012 METAL STUD STUD SIZE 2 1/2" 2 1/2" 2 1/2" 3 5/8" 3 5/8" 3 5/8" 4" 4" 4" 6" 6" 6" R . HEY W STAIN PAINT 1 1/4" J2 CUT STUDS 1/2" SHORT OF TOP RUNNER TO ALLOW FOR DEFLECTION, DO NOT FASTEN GYP BD TO RUNNER MARK GD02-1D GD02-1E GD02-1F GD03-1D GD03-1E GD03-1F GD04-1D GD04-1E GD04-1F GD06-1D GD06-1E GD06-1F TT DOOR SCHEDULE LEGEND PAINTED WOOD TRIM TO MATCH EXISTING WINDOW PROFILE 3/8" TEMPERED GLAZING ACOUSTIC PROPERTIES STC INSUL THK TEST NO. 40 0" USG-860808 40 0" USG-860808 40 0" USG-860808 49 3" SA-870717 49 3" SA-870717 49 3" SA-870717 49 3" SA-870717 49 3" SA-870717 49 3" SA-870717 49 5" SA-870717 49 5" SA-870717 49 5" SA-870717 O O F A LA 1. LINE OF STRUCTURE STUD STUD FINISH SIDE FINISH SIDE MAX HT (5 PSF) MAX HT (10 PSF) GAUGE SPACING A B L/240 L/360 L/240 L/360 16 16" 5/8" GWB 5/8" GWB 15' 5" 13' 5" 20 24" 5/8" GWB 5/8" GWB 11' 10" 10' 5" 25 24" 5/8" GWB 5/8" GWB 11' 6" 10' 1" 16 16" 5/8" GWB 5/8" GWB 20' 6" 17' 11" 20 24" 5/8" GWB 5/8" GWB 14' 3" 12' 6" 16 16" 5/8" GWB 5/8" GWB 13' 9" 12' 0" 16 16" 5/8" GWB 5/8" GWB 22' 1" 19' 4" 20 24" 5/8" GWB 5/8" GWB 15' 2" 13' 3" 25 24" 5/8" GWB 5/8" GWB 14' 6" 12' 11" 16 16" 5/8" GWB 5/8" GWB 30' 5" 26' 7" 20 24" 5/8" GWB 5/8" GWB 20' 4" 17' 11" 25 24" 5/8" GWB 5/8" GWB 18' 10" 16' 9" - TE METAL STUDS PAINTED WOOD TRIM TO MATCH EXISTING WINDOW PROFILE J1 PLAN Jill Hicks Design, LLC post office box 530802 birmingham, alabama 35253 tele: 205-871-0484 7E PAINTED WOOD TRIM TO MATCH EXISTING WINDOW PROFILE METAL STUDS 3/8" TEMPERED GLAZING 2" MIN. jh ANY DAMAGE TO EXISTING RATED ASSEMBLIES OR FIRESTOPPING CAUSED BY THEIR WORK ACTIVITIES. 4'-6-1/2" GYP BOARD 6 1/2" 8" A. 404. EXISTING DOORS AND/OR FRAMES NOT MEETING RATING REQUIREMENTS OR BEARING PROPER LABELS AS SHOWN ON LIFE SAFETY PLAN SHALL BE REPLACED BY THE CONTRACTOR. COORDINATE WITH OWNER AND ARCHITECT, 5'-8-1/2" PAINTED WOOD TRIM TO MATCH EXISTING WINDOW PROFILE 2 PLACES 1 403. THE CONTRACTOR IS RESPONSIBLE FOR AND SHALL INCLUDE IN THE BASE BID THE FOLLOWING: CENTER, MINIMUM OF ONE PER SPACE, AND IN SUCH MULTIPLE LOCATIONS AS NECESSARY TO VIEW ALL SURFACES OF THE RATED AND/OR RATED SMOKE WALLS. THE CONTRACTOR SHALL VERIFY THAT ACCESS PANELS OF THE TYPE SPECIFIED ARE INSTALLED IN WALLS, NON-ACCESSIBLE TYPE CEILINGS AND SOFFITS WHERE ACCESSIBLE SERVICE AND ADJUSTMENT TO MECHANICAL, PLUMBING OR ELECTRICAL ITEMS MAY BE REQUIRED. ACCESS PANELS SHALL BE THE FIRE RATED TYPE EQUAL TO THE RATING OF THE WALL, SOFFIT OR CEILING IN WHICH THEY OCCUR. 7'-0" 7'-0" CLEAR CAULK 1 1/4" METAL STUDS 3/4" 402. THE COST TO REPAIR ANY EXISTING DEFICIENCIES IN FIREPROOFING AND/OR FIRESTOPPING WILL BE ASSIGNED FROM THE APPLICABLE PROJECT ALLOWANCES. D 7'-0" GHAFARI ASSOCIATES, LLC 2816 6TH AVENUE SOUTH BIRMINGHAM, AL 35233 USA TEL +1.205.585.5535 www.ghafari.com O 7'-0" 64' MA C:\ghafari local cache\projectwise2015\dms87260\157380GI0-00-02.dwg 32' 32"=1'-0" A 1/24/2016 2:37:57 PM 0 1 GI METAL STUDS CONT SEALANT 32' 401. THE CONTRACTOR SHALL SCHEDULE A MEETING WITH THE OWNER, ARCHITECT, AND RELEVANT SUBCONTRACTORS AFTER THE REMOVAL OF ALL FINISH CEILINGS AND BEFORE BEGINNING DEMOLITION WORK, TO SURVEY THE CONSTRUCTION AND INTEGRITY OF EXISTING FIRE AND/OR SMOKE RATED WALL AND FLOOR ASSEMBLIES. ALL CONDITIONS ARE TO BE DOCUMENTED, AND A PLAN WILL BE PREPARED AND IMPLEMENTED BY THE CONTRACTOR TO MAKE ANY REPAIRS NECESSARY TO BRING EXISTING ASSEMBLIES, FIRESTOPPING OF PENETRATIONS, AND JOINTS TO THE RATINGS INDICATED ON THE LIFE SAFETY PLAN. 309. DO NOT PAINT OVER METAL GRILLES OR TILE. 1 3/4" H2 16' DOOR SCHEDULE METAL STUDS H1 0 400 - FIRESTOPPING NOTES 305. THE CONTRACTOR SHALL PROVIDE ACCESS PANELS IN GYPSUM BOARD CEILINGS AND IN HARD SURFACE SOFFITS SO THAT THE ARCHITECT AND THE STATE AND LOCAL OFFICIALS CAN INSPECT RATED AND/OR RATED SMOKE WALLS. THESE ACCESS PANELS SHALL BE GYP BOARD PAINTED WOOD TRIM TO MATCH EXISTING WINDOW PROFILE 32' 1 16"=1'-0" 308. UNLESS NOTED, PROVIDE GYPSUM BOARD ON METAL STUD FRAMING SOFFITS OVER ALL WALL CABINETS. 304. WHERE A NEW GYPSUM BOARD PARTITION IS A CONTINUATION OF AN EXISTING PARTITION OR COLUMN FURRING, THE FINISH FACE OF THE NEW PARTITION SHALL ALIGN WITH THE EXISTING FACE. PROVIDE A CONTROL JOINT AT THESE LOCATIONS. 2" GYP BOARD 1/4" REVEAL 16' 32"=1'-0" 307. CAULK AT JUNCTURE OF INTERIOR FACES OF DOOR FRAMES, VIEW WINDOW FRAMES, EXTERIOR WINDOW FRAMES, CABINET WORK, CASEWORK, RECESSED TOILET ACCESSORIES, SURFACE BE MOUNTED TOILET ACCESSORIES, ETC., WITH ADJACENT MATERIALS EVEN THOUGH JOINT MAY NOT VISIBLE. 303. REFER TO ARCHITECTURAL SHEETS FOR INTERIOR FITOUT DETAILS. 220. WHERE FLOORING IS SCHEDULED TO BE REMOVED, ALL RESIDUAL ADHESIVE AND ALL REMNANTS OF PRIOR FLOORING MATERIAL MUST BE REMOVED TO PROVIDE A SMOOTH, CLEAN SURFACE FOR THE INSTALLATION OF SCHEDULED FLOORING. D GYP BOARD 3/8" CHAMFER 0 3 RE C DOUBLE RABBET HM DOOR FRAME PAINTED 16' INDICATED ON THE FLOOR PLANS. CEILING IN ORDER TO PROVIDE FOR RECESSED iTEMS IN THE WALL. DO NOT DISTURB OR INTERFERE WITH THE INTEGRITY OF THE RATED WALL, RATED SMOKE WALL OR RATED SHAFT WALL. 219. THE CONTRACTOR SHALL KEEP PREMISES FREE FROM ACCUMULATION OF WASTE MATERIALS AT ALL TIMES. AT THE COMPLETION OF WORK ALL WASTE MATERIAL, RUBBISH, TOOL, CONSTRUCTION EQUIPMENT MACHINERY AND SURPLUS MATERIALS SHALL BE REMOVED FROM SITE. UNDERCUT DOORS FOR VENTILATION B 8' 8"=1'-0" 306. PIPING LOCATED ABOVE GRADE AND INSIDE THE BUILDING SHALL BE CONCEALED IN FURRED SPACES WITH THE EXCEPTION OF PIPING IN STAIRWAYS, EQUIPMENT ROOMS AND THE POWERHOUSE. THE CONTRACTOR SHALL COORDINATE WITH OTHER TRADES TO PROVIDE FURRING FOR PIPING INSTALLED IN FINISHED AREAS. THE CONTRACTOR SHALL GAIN APPROVAL FROM THE ARCHITECT PRIOR TO BELOW UNLESS DIMENSIONED, DETAILED OR NOTED OTHERWISE. 216. THE CONTRACTOR SHALL REPLACE OR REPAIR ANY EXISTING-TO-REMAIN FINISHES, ETC., WHICH ARE DAMAGED DURING DEMOLITION (I.E. - CEILING GRID, CEILING TILE, WALL COVERINGS, FLOOR COVERINGS, CORNER GUARDS, WALL GUARDS, HANDRAILS, CHAIR RAIL, MOLDINGS, ETC.). 2" NEW SOLID CORE WOOD DOOR A 0 1 16"=1'-0" 301. 209. WHERE IN-WALL DEMOLITION OR NEW WORK IS INDICATED IN EXISTING-TO-REMAIN WALLS, THE EXISTING SUBSTRATE SHALL BE REPAIRED TO MATCH ADJACENT SURFACES AND TO RECEIVE THE SCHEDULED FINISH. 2" 2" 4' 4"=1'-0" 217. FOR EXTENT AND LOCATION OF CHANNELING AND CORING OF EXISTING STRUCTURAL SLAB REFER TO MEP DRAWINGS. CARE SHOULD BE TAKEN NOT TO CUT ANY SLAB REINFORCING. COORDINATE WORK WITH ARCHITECT AND OWNER. PAINT NEW HM FRAME PAINT EXISTING SOLID CORE WOOD DOOR 0 1 215. REFER TO CIVIL, MECHANICAL, PLUMBING, FIRE PROTECTION COMMUNICATIONS AND ELECTRICAL DRAWINGS FOR EXTENT OF DEMOLITION OF BUILDING UTILITY SYSTEMS. 3'-0" 2" PAINT EXISTING HM FRAME 8' 208. REMOVE EXISTING CONSTRUCTION AS INDICATED OR AS REQUIRED TO INSTALL NEW WORK AS SHOWN ON DRAWINGS. TYPICAL WALL REMOVAL INCLUDES MECHANICAL,PLUMBING, COMMUNICATIONS, INFORMATION SYSTEMS AND ELECTRICAL SYSTEMS CONTAINED THEREIN. REMOVE EQUIPMENT, SUPPORTS, DOORS, WINDOWS, FRAMES, FINISHES AND OTHER FIXTURES CONTAINED AS PART OF WALL. PATCH ADJOINING WALLS, FLOOR, AND DECK; AND PREPARE SURFACES TO RECEIVE NEW SCHEDULED FINISH. 214. THE EXISTING BUILDING ENVELOPE SHALL BE MAINTAINED IN A WATER TIGHT CONDITION AT ALL TIMES THROUGHOUT ALL PHASES OF CONSTRUCTION. 2" 4' 8"=1'-0" 213. THE CONTRACTOR SHALL BRACE ALL EXISTING STRUCTURES AND ALL STRUCTURAL ELEMENTS AS NECESSARY DURING DEMOLITION. ARE SHOWN AS DASHED AND ON THE DEMOLITION FLOOR PLANS. REFER TO DEMOLITION DRAWINGS FOR EXTENT OF RELATED WORK. ALL PENETRATIONS AND TOP OF WALL JOINTS IN NON-RATED WALLS ARE TO BE SEALED WITH ACOUSTIC SEALANT. 2" 0 3 212. THE CONTRACTOR SHALL NOT CUT STRUCTURAL WORK IN A MANNER RESULTING IN A REDUCTION OF LOAD CARRYING CAPACITY OR LOAD/DEFLECTION RATIO. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT OF ALL STRUCTURAL CUTS PRIOR TO EXECUTION SO THAT APPROVAL CAN BE OBTAINED FROM THE ARCHITECT AND THE STRUCTURAL ENGINEER. 207. EXISTING-TO-REMAIN PARTITIONS, DOORS, WINDOWS, PLUMBING FIXTURES, CASEWORK, EQUIPMENT, ETC., SEE FINISH PLANS FOR INTERIOR FINISHES, ACCENT WALLS, FLOORING PATTERNS, FLOORING TRANSITIONS, LOCATIONS OF WALL PROTECTIONS AND TOILET ACCESSORIES. 4' 211. WHERE NEW FINISHES ARE CALLED FOR ON EXISTING SURFACES, REMOVE THE EXISTING FINISH AND PREPARE SURFACE TO RECEIVE THE NEW SCHEDULED FINISH. 206. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT IMMEDIATELY IF ANY WORK INDICATED IN THE CONTRACT DOCUMENTS CANNOT BE PERFORMED DUE TO EXISTING FIELD CONDITIONS. 106. FOR FURTHER DIMENSIONING, SEE LARGE SCALE PLANS, SECTIONS, EXTERIOR ELEVATIONS, INTERIOR ELEVATIONS AND DETAILS. 2' 2"=1'-0" 300 - INTERIOR FIT-OUT NOTES 202. DEMOLITION WORK SHALL BE EXECUTED IN CONFORMANCE WITH ALL CODES AND ORDINANCES AS SET FORTH BY ALL GOVERNING AUTHORITIES. 102. DO NOT SCALE DRAWINGS. IF DIMENSIONS ARE IN QUESTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING CLARIFICATION FROM THE ARCHITECT BEFORE CONTINUING WITH CONSTRUCTION. 0 1 100 - GENERAL NOTES THE COMPLETE SET OF CONTRACT DOCUMENTS FOR THIS WORK CONSISTS OF ONE VOLUME OF DRAWINGS AND ONE VOLUME OF SPECIFICATIONS. THESE VOLUMES MUST NOT BE SEPARATED BY ANYONE FOR ANY REASON. THE ARCHITECT AND THE OWNER DISCLAIM ANY RESPONSIBILITY OF ASSUMPTIONS MADE BY AN INCOMPLETE SET OF SPECIFICATIONS INCLUDING ALL SECTIONS LISTED IN THE TABLE OF CONTENTS AND DRAWINGS INCLUDING ALL SHEETS LISTED IN THE INDEX OF DRAWINGS. 4' 4"=1'-0" CT 2' TE 1' A 0 1"=1'-0" SC 2' ST 1' 2" 0 112"=1'-0" 100' 0 1"=60'-0" 60' WIDTH 3 3/4" 3 3/4" 3 3/4" 4 7/8" 4 7/8" 4 7/8" 5 1/4" 5 1/4" 5 1/4" 7 1/4" 7 1/4" 7 1/4" 120' 0 1"=80'-0" 6 EA BALL BEARING BUTTS MATCH BUILDING STANDARD 1 EA STOREROOM LOCKSET MATCH BUILDING STANDARD PROJECT # 1 EA PERMANENT CYLINDER MATCH BUILDING STANDARD PROJECT MANAGER 1 EA AUTOMATIC FLUSHBOLT MATCH BUILDING STANDARD DESIGNED BY 1 EA COORDINATOR MATCH BUILDING STANDARD DRAWN BY S. HEYWOOD 2 EA CLOSER MATCH BUILDING STANDARD S. HEYWOOD 2 EA OVERHEAD STOP MATCH BUILDING STANDARD QUALCHECK SHEET TITLE 157380.000 S.HEYWOOD GENERAL NOTES/ OPENING SCHEDULES GI0-00-02 SHEET NUMBER 80' 160' 0 1"=100'-0" 100' 200' 0 1"=200'-0" 200' 400' 0 1"=400'-0" 400' 800' 0 1"=500'-0" 500' 1000' 0 1"=1000'-0" 1000' 2000' 0 1' 2' 112"=1'-0" 0 1' 2' 0 3 1"=1'-0" 2' 4' 0 1 4"=1'-0" 2' 4' 0 3 2"=1'-0" 4' 8' 0 1 8"=1'-0" 4' 8 0 3 4"=1'-0" OFFICE 707 OFFICE 702 8' 0 1 COPY 701 CLOSET 700A RECEPTION 700 PHASE TWO 16' 16"=1'-0" ADMN 712 OFFICE 714 OFFICE 715 8' 16' OFFICE 716 0 3 8"=1'-0" OFFICE 717 16' 32' 0 16' 32' 1 16"=1'-0" 32"=1'-0" 0 1 32' 64' 32"=1'-0" GHAFARI ASSOCIATES, LLC 2816 6TH AVENUE SOUTH BIRMINGHAM, AL 35233 USA TEL +1.205.585.5535 www.ghafari.com OFFICE 718 OFFICE 706 OPEN OFFICE 704 BREAK 703 DISPATCH 720 BREAK 713 OFFICE 705 PHASE ONE DISPATCH 2 719 jh STORAGE 709 PASSAGE 708 Jill Hicks Design, LLC post office box 530802 birmingham, alabama 35253 tele: 205-871-0484 FILES 710 STORAGE 711 A B O D SC R . HEY W O ST TT MA O O F A LA A TE GI BI TE RM IN G H A M , R ED A A L TE RE S CT 7012 HI C R SEVENTH FLOOR PHASING PLAN SCALE: 1/16"=1'-0" OFFICE 831 CONFERENCE 832 OFFICE 833 OFFICE 834 OFFICE 835 OFFICE 836 OFFICE 837 OFFICE 838 OFFICE 839 OFFICE 840 OFFICE 841 OFFICE 842 STG 801 OFFICE 821 OFFICE 810 OFFICE 809 OFFICE 851 VEST 843 OFFICE 808 OFFICE 807 OFFICE 803 PASSAGE 852 COFFEE 857A SERVER 802 OFFICE 844 OFFICE 846 OFFICE 853 OFFICE 829 RECEPTION 828A PASSAGE 828 PASSAGE 816 OFFICE 811 C:\ghafari local cache\projectwise2015\dms87260\157380GI1-00-01.dwg OFFICE 812 OFFICE 813 OFFICE 814 OFFICE 826 OFFICE 817 OFFICE 825 OFFICE 818 OFFICE 847 STG 805 OFFICE 824 TRAINING 823 OFFICE 861 OFFICE 854 PASSAGE 820 OFFICE 827 ADMN 857 OFFICE 804 PASSAGE 815 OFFICE 822 CONFERENCE 860 RECEPTION 800 PASSAGE 842 OFFICE 830 OFFICE 845 DOWN OFFICE 858 PASSAGE 850 UP CLASSROOM 806 OFFICE 862 OFFICE 856 OFFICE 848 PHASE TWO PASSAGE 859 OFFICE 855 01-22-16 REV DATE DR04 Addendum 1 ISSUED FOR OFFICE 863 STG 819 WORK/COPY 849 DOWN DOWN UP UP SHEYWOOD FORUM BUILDING TENANT FIT-OUT FOR LIFEGUARD AMBULANCE 1/24/2016 3:01:24 PM PROJECT # PROJECT MANAGER PHASING GENERAL NOTES 157380.000 S.HEYWOOD DESIGNED BY 1. PHASE ONE AND PHASE TWO TO BE PERMITTED SEPARATELY. DRAWN BY S. HEYWOOD 2. PHASE ONE MUST HAVE A CERTIFICATE OF OCCUPANCY BY APRIL 15, 2016. QUALCHECK SHEET TITLE S. HEYWOOD 3. ALL WORK ASSOCIATED WITH A GIVEN PHASE, EVEN IF OUTSIDE PHASE LIMITS, TO BE COMPLETED AND FINISHED PRIOR TO THE COMPLETION DATE OF THE GIVEN PHASE. CONSTRUCTION PHASING PLAN EIGHTH FLOOR PHASING PLAN GI1-00-01 SCALE: 1/16"=1'-0" SHEET NUMBER NORTH 0 1"=10'-0" 10' 20' 0 1"=20'-0" 20' 40' 0 1"=30'-0" 30' 60' 0 1"=40'-0" 40' 80' 0 1"=50'-0" 50' 100' 0 1"=60'-0" 60' 120' 0 1"=80'-0" 80' 160' 0 1"=100'-0" 100' 200' 0 1"=200'-0" 200' 400' 0 1"=400'-0" 400' 800' 0 1"=500'-0" 500' 1000' 0 1"=1000'-0" 1000' 2000' This record drawing has been prepared, in part, based upon information furnished by others. While this information is believed to be reliable, the Architect/Engineer assumes no responsibility for the accuracy of this record drawing or for any errors or omissions that may have been incorporated into it as a result of incorrect information provided to the Architect/Engineer. Those relying on this record document are advised to obtain independent verification of its accuracy. NORTH 0 1' 2' 112"=1'-0" 0 1' 2' 0 3 1"=1'-0" 2' 4' 0 1 4"=1'-0" 2' 4' 0 3 2"=1'-0" 4' 8' 0 1 8"=1'-0" 4' 8 0 3 4"=1'-0" 8' 16' 0 1 16"=1'-0" 8' 16' 0 3 8"=1'-0" 16' 32' 0 16' 32' 1 16"=1'-0" 32"=1'-0" 0 1 32' 64' 32"=1'-0" PARTITION LEGEND EXISTING TO BE REMOVED GHAFARI ASSOCIATES, LLC 2816 6TH AVENUE SOUTH BIRMINGHAM, AL 35233 USA TEL +1.205.585.5535 www.ghafari.com EXISTING TO REMAIN NON-RATED FULL HEIGHT WALL 35 8" MTL. STUDS 16 Ga. @ 16" o.c. UNLESS NOTED OTHERWISE. FACE LAYER 5 8" TYPE "X" GYP. BOARD, EACH SIDE. SEE SHEET GI0-00-02 FOR FURTHER INFORMATION. OFFICE 707 OFFICE 702 BUSINESS: 11,130 SF/100= 112 OCC COPY 701 F ADMN 712 CLOSET 700A RECEPTION 700 OFFICE 714 OFFICE 715 OFFICE 716 OFFICE 717 OFFICE 718 SMOKE BARRIER - 1HR F F Jill Hicks Design, LLC F F F F F BREAK 703 OPEN OFFICE 704 jh CONSTRUCT IN ACCORDANCE WITH U.L. DESIGN : U465 UNLESS NOTED OTHERWISE. F OFFICE 706 BREAK 713 OFFICE 705 ONE-HOUR FIRE DISPATCH 720 post office box 530802 birmingham, alabama 35253 tele: 205-871-0484 CONSTRUCT IN ACCORDANCE WITH U.L. DESIGN : U465 UNLESS NOTED OTHERWISE. F DISPATCH 2 719 F F F F TWO-HOUR FIRE F CONSTRUCT IN ACCORDANCE WITH U.L. DESIGN : U411 UNLESS NOTED OTHERWISE. F STORAGE 709 P F TWO-HOUR FIRE-SMOKE F PASSAGE 708 CONSTRUCT IN ACCORDANCE WITH U.L. DESIGN : U411 UNLESS NOTED OTHERWISE. FILES 710 F F F F STORAGE 711 SYMBOLS LEGEND F EXIT LIGHTS F PULL STATION FEC FIRE EXTINGUISHER CABINET RE GI S HOLD OPENS HO B O 7012 FIRE EXTINGUISHER FX R . HEY W D FIRE HOSE CABINET TT O FHC O MA A FIRE ALARM STROBE BI TE CT P SC F ST F O F A LA A P TE RM IN G H A M , R ED A A L TE F HI C R BUILDING INFORMATION EXISTING BUILDING INFORMATION: Construction Type: IBC Type I-B, Fully Sprinkled NFPA-220 Type I (2,2,2) Renovated 7th Floor Area = 11,130 sf Total 7th Floor Area = 37,530 sf = = 14,440 sf 37,530 sf MAJOR USE OCCUPANCY: HIGH RISE BUSINESS OCCUPANT LOAD: SEE PLAN ASSEMBLY UNCONCENTRATED: 10,270 SF/15= 685 OCC Exiting Information: See Plan Max. Travel Distance: 300'-0" Sprinkled APPLICABLE CODES THESE DOCUMENTS , TO THE BEST OF GHAFARI'S KNOWLEDGE AND EXPERIENCE, CONFORM TO THE REQUIREMENTS OF THE MOST RESTRICTIVE APPLICABLE CODE AS SHOWN BELOW: SEVENTH FLOOR LIFE SAFETY PLAN C:\ghafari local cache\projectwise2015\dms87260\157380GI1-07-01.dwg CITY OF BIRMINGHAM: INTERNATIONAL BUILDING CODE INTERNATIONAL EXIST: BUILDING CODEINTERNATIONAL MECHANICAL CODE INTERNATIONAL PLUMBING CODE NATIONAL ELECTRICAL CODE INTERNATIONAL FIRE CODE NFPA 101, LIFE SAFETY CODE HANDICAPPED CODE, ANSI - A117.1 AMERICANS WITH DISABILITY ACT ACCESSIBILITY GUIDELINES CITY OF BIRMINGHAM TECHNICAL CODES Fire-Resistance Rating Requirements for Building Elements NFPA 220 Type I (2,2,2) IBC (2009) Type I, B SCALE: 3/32"=1'-0" CONSTRUCTION TYPE Most Stringent NORTH Hourly Ratings BUILDING ELEMENTS Structural Frame Including columns, girders trusses. OTHER INFORMATION: Typ. Detail Hourly Ratings Hourly Ratings 2 UL or GA Design # 2 2 Existg. 1. INDICATE AREA BETWEEN FIREWALLS. SEE DRAWING: EXISTING 2. PROVIDE SITE PLAN SHOWING LAYOUT OF BUILDING FROM ALL PROPERTY LINES. SEE DRAWING: EXISTING 3. PROVIDE SITE UTILITY PLAN INDICATING LOCATION AND SIZES FOR ALL UTLITIES INCLUDING WATER, SEWER, STORM, AND ELECTRICAL. SEE DRAWING: EXISTING 4. PROVIDE LIFE SAFETY PLAN SHOWING EXITS AND FIRE RATINGS FOR ALL EXIT ACCESS CORRIDORS AND SHAFTS. SEE DRAWING: __GI1-07-01/GI1-08-01 5. INDICATE TRAVEL DISTANCE FROM EACH TENANT SPACE IN FEET. SEE DRAWING: __GI1-07-01/GI1-08-01_ 6. PROVIDE INTERIOR PARTITIONS FOR ALL RATED AND NON-RATED PARTITION TYPES. SEE DRAWING: ______GI0-00-02________ 7. INDICATE ALL DUCTWORK THAT CROSSES FIRE RATED WALLS AND INDICATE FIRE DAMPERS. SEE DRAWING: 8. PROVIDE HVAC PLANS WITH ALL DUCT SIZES AND CFM PER OUTLET WITH AIR BALANCE TABLE. SEE DRAWING: _MH1-07-01/MH1-08-01_ 9. INDICATE ON HVAC DRAWINGS ALL EXHAUST AND RELIEF FANS WITH CFM REQUIREMENTS. SEE DRAWING: _MH1-07-01/MH1-08-01_ 10. INDICATE BUILDING EXHAUST SEPARATE FROM TOILET EXHAUST. SEE DRAWING: EXISTING 11. SUBMIT OUTSIDE AIR CALCULATIONS SHOWING COMPLIANCE WITH ASHRAE 62-89. SEE DRAWING: EXISTING 12. SUBMIT MATERIAL DATA SAFETY SHEETS IF THE BUILDING STORES CHEMICALS OR GASES. SEE DRAWING: N/A 13. PROVIDE PLUMBING DRAWINGS SHOWING NONPRESSURE PIPING. SEE DRAWING: PP1-07-01________ 14. PROVIDE ISOMETRIC OF DRAINAGE WASTE AND VENT SYSTEM. SEE DRAWING: PP1-07-01 15. PROVIDE PLUMBING FIXTURE SCHEDULE. SEE DRAWING: PD1-07-01 16. INDICATE ON PLANS EXISTING FIXTURES AND/OR FIXTURES TO BE REMOVED. SEE DRAWING: PD1-07-01 17. INDICATE EXISTING WET COLUMNS AND/OR EXISTING CONNECTIONS TO THE EXISTING SEWER SYSTEM. SEE DRAWING: EXISTING 18. PROVIDE SITE PLAN WHEN APPLICABLE FOR NEW CONSTRUCTION AND ADDITIONS INDICATING CONNECTIONS OF WATER AND GAS LINES TO RESPECTIVE MAINS. SEE DRAWING: NA 19. PROVIDE GAS ISOMETRIC FOR ALL GAS PIPING. SEE DRAWING: NA ______ 20. INDICATE LONGEST RUN OF PIPING FROM GAS METER TO FARTHEST OUTLET. SEE DRAWING: NA ______ 21. PROVIDE TOTAL BTU'S OF THE NEW AND EXISTING GAS PIPING SYSTEM. SEE DRAWING: NA 22. PROVIDE DOOR SCHEDULE WITH FIRE RATING AND HARDWARE. SEE DRAWING: GI0-00-02___ 23. PROVIDE METHODS OF PROTECTION FOR PENETRATIONS THROUGH FIRE RATED PARTITIONS AND FLOORS. SEE DRAWING: EXISTING Bearing Walls Exterior 2 2 2 Existg. Interior 2 2 2 Existg. Non-Bearing Walls & Partitions 0 Interior Floor Construction Including supporting beams & joists. 2 SHEYWOOD Roof Construction Including supporting beams & joists. 0 0 2 2 1 Existg. 1 Existg. 1 Existg. 1/24/2016 2:19:08 PM Nonbearing walls and partitions Exterior <5' 1 1 1 Existg. >5' <10' 1 1 1 Existg. > 10' <30' 1 1 1 Existg. 0 > 30' 0 0 Existg. NC (Non Combustible) NA (Not Applicable) - does not apply to this structure. Design is based on the more stringent of the above requirements. Building is Protected with A.S.S Per NFPA 13 2009 EDITION 2009 EDITION 2009 EDITION 2009 EDITION 2008 EDITION 2009 EDITION 2008 EDITION 1994 EDITION REV 01-22-16 DR04 Addendum 1 01-11-16 DR03 Construction 01-04-16 DR01 Review DATE ISSUED FOR 2010 EDITION 2010 EDITION ALL PARTITIONS OUTSIDE OF THE "LIMITS OF CONSTRUCTION" AND INDICATED AS "RATED" ARE EXISTING AND DO NOT REQUIRE ANY MODIFICATIONS UNDER THIS CONTRACT FOR THEIR INDICATED RATINGS. NOTE: DURING ALTERATIONS, THE EXISTING FIRE PROTECTION SYSTEMS SUCH AS FIRE ALARM AND SPRINKLER SYSTEMS, SHALL BE MAINTAINED OPERATIONAL AT ALL TIMES WITH LIMITED TIME FOR AN OUTAGE. IF OUTAGES EXCEED 4 HOURS, THE BJCC SHALL BE NOTIFIED AND A FIRE WATCH SHALL BE ESTABLISHED PER NFPA REQUIREMENTS. EXISTING FORUM BUILDING TENANT FIT-OUT FOR LIFEGUARD AMBULANCE NOTE: DURING ALTERATIONS ALL REQUIRED EXIT COMPONENTS SHALL BE MAINTAINED FOR UNOBSTRUCTED EGRESS AND LEFT DEBRIS FREE WHEN UNATTENDED AND AT THE END OF EACH WORK DAY. NOT IN SCOPE PROJECT # PROJECT MANAGER ______ 157380.000 S.HEYWOOD DESIGNED BY _____ DRAWN BY S. HEYWOOD QUALCHECK SHEET TITLE S. HEYWOOD SEVENTH FLOOR LIFE SAFETY PLAN NC (Non Combustable) N/A (Not Applicable) - Does not apply to this structure. Design is based on the more stringent of the above requirements. GI1-07-01 SHEET NUMBER 0 1"=10'-0" 10' 20' 0 1"=20'-0" 20' 40' 0 1"=30'-0" 30' 60' 0 1"=40'-0" 40' 80' 0 1"=50'-0" 50' 100' 0 1"=60'-0" 60' 120' 0 1"=80'-0" 80' 160' 0 1"=100'-0" 100' 200' 0 1"=200'-0" 200' 400' 0 1"=400'-0" 400' 800' 0 1"=500'-0" 500' 1000' 0 1"=1000'-0" 1000' 2000' This record drawing has been prepared, in part, based upon information furnished by others. While this information is believed to be reliable, the Architect/Engineer assumes no responsibility for the accuracy of this record drawing or for any errors or omissions that may have been incorporated into it as a result of incorrect information provided to the Architect/Engineer. Those relying on this record document are advised to obtain independent verification of its accuracy. Renovated 8th Floor Area Total 8th Floor Area 0 1' 2' 112"=1'-0" 0 1' 2' 0 3 1"=1'-0" 2' 4' 0 1 4"=1'-0" 2' 4' 0 3 2"=1'-0" 4' 8' 0 1 8"=1'-0" 4' 8 0 3 4"=1'-0" 8' 16' 0 1 16"=1'-0" 8' 16' 0 3 8"=1'-0" 16' 32' 0 16' 32' 1 16"=1'-0" 32"=1'-0" 0 1 32' 64' 32"=1'-0" NOT IN SCOPE ALIGN GHAFARI ASSOCIATES, LLC 2816 6TH AVENUE SOUTH BIRMINGHAM, AL 35233 USA TEL +1.205.585.5535 www.ghafari.com 7 12 1 RECEPTION 700 700A CLOSET 700A ADMN 712 OFFICE 716 OFFICE 717 1 8 ALIGN 702 ALIGN OFFICE 715 1 4 OFFICE 706 OFFICE 714 GD03-0E ALIGN 1 1 OFFICE 705 AE7-00-01 GD03-0E DISPATCH 720 10 BREAK 11 713 2 9 jh GD03-0E ALIGN 713 12 5 OFFICE 718 Jill Hicks Design, LLC post office box 530802 birmingham, alabama 35253 tele: 205-871-0484 ALIGN 4 BREAK 703 OPEN OFFICE 704 ALIGN COPY 701 GD03-0E 717 OFFICE 702 1 2 8 GD03-0E 715 OFFICE 707 GD03-0E ALIGN GD03-0E GD03-0E 7 714 1'-0" 9'-7" clr 718 2'-6" clr 10'-6" 10 4 AE7-00-01 9 DISPATCH 2 719 5'-0" clr 719 4 STORAGE 709 709 PASSAGE 708 11 FILES 710 D A SC B O O ST R . HEY W GI TE RM IN G H A M , R ED A A L TE RE HI C R REV 01-22-16 DR04 Addendum 1 01-11-16 DR03 Construction 01-04-16 DR01 Review DATE ISSUED FOR SHEYWOOD FORUM BUILDING TENANT FIT-OUT FOR LIFEGUARD AMBULANCE SEVENTH FLOOR NEW WORK PLAN SCALE: 1/8"=1'-0" NORTH PROJECT # NEW CONSTRUCTION KEY NOTES PROJECT MANAGER NEW CONSTRUCTION GENERAL NOTES 157380.000 S.HEYWOOD DESIGNED BY 7 CENTER NEW WALL ON EXISTING EXTERIOR WINDOW MULLIONS. 1. SEE FINISH PLANS FOR ALL NEW FINISH WORK. DRAWN BY S. HEYWOOD 2 8 CENTER NEW WALL ON EXISTING COLUMN. 2. ALL NEW AND EXISTING WALLS MUST MEET FIRE RATING REFLECTED ON LIFE SAFETY PLANS. QUALCHECK SHEET TITLE S. HEYWOOD EXISTING PLASTIC LAMINATE MILLWORK TO REMAIN. CLEAN THOROUGHLY AND REPLACE ANY NON-WORKING HARDWARE: HINGES, PULLS, DRAWER GLIDES, ETC. TO MATCH EXISTING. 3 NOT USED THIS SHEET 9 NEW PLASTIC LAMINATE MILLWORK; SEE ELEVATIONS. 1 FULL HEIGHT GYP BD WALL, SEE PARTITION DETAILS. 3. SEE SHEET GI0-00-02 FOR WALL PARTITION TYPES. SEVENTH FLOOR NEW WORK PLAN 4. ALL EXISTING WINDOW BLINDS TO REMAIN; PROTECT DURING CONSTRUCTION AND CLEAN UPON COMPLETION OF WORK. 4 INFILL OPENING WITH 5 8" GYB BD (BOTH SIDES) ON 3 5 8" 20 GA. METAL STUDS @ 16" OC. 10 REFINISH TENANT ENTRY DOORS AND WOOD SURROUND. FINISH TO MATCH EXISTING. 5. REMOVE ALL MISC PICTURE HOOKS, NAILS, AND SURFACE MOUNTED WOOD BLOCKING. FILL HOLES OR PATCH AS NECESSARY FOR SMOOTH PAINT FINISH. 5 EXISTING CARD ACCESS SYTEM TO REMAIN; COORDINATE WITH TENANT AND BUILDING OWNER. 11 FURR OUT COLUMN ENCLOSURE TO ACCOMMODATE NEW ELECTRICAL PANEL; COORDINATE DEPTH WITH SPECIFIED PANEL. 6 NOTE NOT USED; THIS SHEET. 12 FRAME @ AT COLUMN SIDE WALL AS REQ'D TO ACCOMODATE A SMOOTH DRYWALL FINISH @ WEST WALL OF CLOSET. 6. NOTE: DOORS NOT LABELED ARE EXISTING TO REMAIN. PAINT DOORS & FRAMES PER FINISH SCHEDULE. AE1-07-03 7. ALL DOOR LOCKSET RE-KEYING WILL BE COMPLETED BY OWNER. SHEET NUMBER 0 1"=10'-0" 10' 20' 0 1"=20'-0" 20' 40' 0 1"=30'-0" 30' 60' 0 1"=40'-0" 40' 80' 0 1"=50'-0" 50' 100' 0 1"=60'-0" 60' 120' 0 1"=80'-0" 80' 160' 0 1"=100'-0" 100' 200' 0 1"=200'-0" 200' 400' 0 1"=400'-0" 400' 800' 0 1"=500'-0" 500' 1000' 0 1"=1000'-0" 1000' 2000' This record drawing has been prepared, in part, based upon information furnished by others. While this information is believed to be reliable, the Architect/Engineer assumes no responsibility for the accuracy of this record drawing or for any errors or omissions that may have been incorporated into it as a result of incorrect information provided to the Architect/Engineer. Those relying on this record document are advised to obtain independent verification of its accuracy. 5 C:\ghafari local cache\projectwise2015\dms87260\157380AE1-07-03.dwg 5 BI CT 7012 S 1/24/2016 2:13:38 PM TT MA STORAGE 711 O O F A LA A TE 0 1' 2' 112"=1'-0" 0 1' 2' 0 3 1"=1'-0" 2' 4' 0 1 4"=1'-0" 2' 4' 0 3 2"=1'-0" 4' 8' 0 1 8"=1'-0" 4' 8 0 3 4"=1'-0" 8' 16' 0 1 16"=1'-0" 8' 16' 0 3 8"=1'-0" 16' 32' 0 16' 32' 1 16"=1'-0" 32"=1'-0" 0 1 32' 64' 32"=1'-0" NOT IN SCOPE GHAFARI ASSOCIATES, LLC 2816 6TH AVENUE SOUTH BIRMINGHAM, AL 35233 USA TEL +1.205.585.5535 www.ghafari.com 1 jh Jill Hicks Design, LLC post office box 530802 birmingham, alabama 35253 tele: 205-871-0484 1 1 1 A SC ST D C:\ghafari local cache\projectwise2015\dms87260\157380AE1-07-04.dwg SCALE: 1/8"=1'-0" 1/24/2016 2:15:18 PM SHEYWOOD NORTH EXISTING ACOUSTICAL CLG. GRID AND TILES TO REMAIN, REPLACE CUT TILES AS REQUIRED DUE TO DEMOLITION/NEW LAYOUT REFLECTED CEILING PLAN GENERAL NOTES CT RM IN G H A M , R ED A A L HI C R 01-22-16 DR04 Addendum 1 01-11-16 DR03 Construction 01-04-16 DR01 Review DATE ISSUED FOR PROJECT # PROJECT MANAGER 1. ALL CEILINGS HEIGHTS EXISTING TO REMAIN: @ 9'-0" AFF UNLESS NOTED OTHERWISE. 157380.000 S.HEYWOOD DESIGNED BY 2. ALL EXISTING CEILING GRID TO REMAIN. REPLACE CUT OR DAMAGED TILES AS REQUIRED BY NEW CONSTRUCTION. DRAWN BY QUALCHECK SHEET TITLE 3. ALL 2X4 FIXTURES TO BE RELOCATED EXISTING. RELOCATE FROM AREAS OF DEMOLITION OR FROM OWNER'S STOCKPILE. EXISTING CAN LIGHT TO REMAIN J. HICKS S. HEYWOOD SEVENTH FLOOR CEILING PLAN EXISTING 2 X 4 LIGHT TO REMAIN R TE FORUM BUILDING TENANT FIT-OUT FOR LIFEGUARD AMBULANCE SEVENTH FLOOR CEILING PLAN NO CEILING WORK THIS ROOM. BI TE GI REV 1 B O O RE S REFLECTED CEILING PLAN KEY NOTES R . HEY W 7012 1 REFLECTED CEILING LEGEND TT MA O O F A LA A TE RELOCATED 2 X 4 LIGHT FIXTURE; SEE ELEC FIXTURES TO BE RELOCATED FROM AREAS OF DEMOLITION OR FROM OWNER'S STOCKPILE AE1-07-04 SHEET NUMBER 0 1"=10'-0" 10' 20' 0 1"=20'-0" 20' 40' 0 1"=30'-0" 30' 60' 0 1"=40'-0" 40' 80' 0 1"=50'-0" 50' 100' 0 1"=60'-0" 60' 120' 0 1"=80'-0" 80' 160' 0 1"=100'-0" 100' 200' 0 1"=200'-0" 200' 400' 0 1"=400'-0" 400' 800' 0 1"=500'-0" 500' 1000' 0 1"=1000'-0" 1000' 2000' 0 1' 2' 112"=1'-0" 0 1' 2' 0 3 1"=1'-0" 2' 4' 0 1 4"=1'-0" 2' 4' 0 3 2"=1'-0" 4' 8' 0 1 8"=1'-0" 4' 8 0 3 4"=1'-0" 8' 16' 0 1 16"=1'-0" 8' 16' 0 3 8"=1'-0" 16' 32' 0 16' 32' 1 16"=1'-0" 32"=1'-0" 0 1 32' 64' 32"=1'-0" GHAFARI ASSOCIATES, LLC 2816 6TH AVENUE SOUTH BIRMINGHAM, AL 35233 USA TEL +1.205.585.5535 www.ghafari.com jh Jill Hicks Design, LLC post office box 530802 birmingham, alabama 35253 tele: 205-871-0484 RECEPTION #828A SC: 3/8" = 1'-0" B O D SC R . HEY W O ST TT MA O O F A LA A TE A 9 GI 3 FINISH LEGEND TE RM IN G H A M , R ED A A L HI C R N/A 10 1 BI TE RE S CT 7012 DISPATCH 2 #719 SC: 3/8" = 1'-0" FINISH SCHEDULE N/A DETAIL RESILIENT TILE TO CARPET C:\ghafari local cache\projectwise2015\dms87260\157380AE7-00-01.dwg 4 NOT TO SCALE REV 7 01-22-16 DR04 Addendum 1 01-11-16 DR03 Construction 01-04-16 DR01 Review DATE ISSUED FOR SECTION STANDARD MILLWORK SC: 3/4" = 1'-0" 11 BREAK ROOM #713 SC: 3/8" = 1'-0" DETAIL RESILIENT TILE TO SEALED CONCRETE 5 NOT TO SCALE SHEYWOOD FORUM BUILDING TENANT FIT-OUT FOR LIFEGUARD AMBULANCE PROJECT # 1/24/2016 2:16:39 PM PROJECT MANAGER 157380.000 S.HEYWOOD DESIGNED BY DRAWN BY 1 QUALCHECK SHEET TITLE J. HICKS S. HEYWOOD FINISH SCHEDULE FINISH NOTES FINISH DETAILS INTERIOR ELEVATIONS 2 FINISH NOTES 6 N/A 0 1"=10'-0" 10' 20' 0 1"=20'-0" 20' 40' 0 1"=30'-0" 30' 60' 0 1"=40'-0" 40' WOOD BASE (WD-1) NOT TO SCALE 80' 0 1"=50'-0" 50' 100' 0 1"=60'-0" 60' 120' 0 1"=80'-0" 8 80' SECTION MILLWORK WITH SINK 12 SC: 3/4" = 1'-0" 160' 0 1"=100'-0" 100' 200' 0 1"=200'-0" 200' 400' 0 1"=400'-0" AE7-00-01 BREAK ROOM #713 SC: 3/8" = 1'-0" 400' 800' 0 1"=500'-0" 500' 1000' 0 1"=1000'-0" 1000' 2000' SHEET NUMBER 0 1' 2' 11 2"=1'-0" 0 1' 2' 0 3 1"=1'-0" 2' 4' 0 1 4"=1'-0" DUCTWORK LEGEND 2' 4' 0 3 2"=1'-0" 4' 8' 0 1 8"=1'-0" 4' 8 0 3 4"=1'-0" 8' 16' 0 1 16"=1'-0" 8' 0 3 AIR TERMINAL BOXES (7TH FLOOR TS) GENERAL NOTES 16' 8"=1'-0" 16' 32' 0 16' 32' 1 16"=1'-0" 32"=1'-0" 0 1 32' 64' 32"=1'-0" AIR TERMINAL BOXES (8TH FLOOR TS) GHAFARI ASSOCIATES, LLC 2816 6TH AVENUE SOUTH BIRMINGHAM, AL 35233 USA TEL +1.205.585.5535 www.ghafari.com jh Jill Hicks Design, LLC post office box 530802 birmingham, alabama 35253 tele: 205-871-0484 AIR TERMINAL BOXES (7TH FLOOR TN) AIR TERMINAL BOXES (8TH FLOOR TN) AIR DEVICE LEGEND M:\215210\HVAC\215210 SDLN.dwg REV 01-22-16 DR04 Addendum #1 01-11-16 DR03 Construction 01-04-16 DR01 Review DATE ISSUED FOR CEILING DIFFUSER DETAIL NO SCALE BRYSON EUWER FORUM BUILDING TENANT FIT-OUT FOR LIFEGUARD AMBULANCE PROJECT # 1/25/2016 7:48:03 AM PROJECT MANAGER DESIGNED BY DRAWN BY QUALCHECK 157380.000 S.HEYWOOD SAMMY DAVIS B.EUWER SAMMY DAVIS SHEET TITLE HVAC SCHEDULES AND DETAILS MH0-00-01 SHEET NUMBER 0 1"=10'-0" 10' 20' 0 1"=20'-0" 20' 40' 0 1"=30'-0" 30' 60' 0 1"=40'-0" 40' 80' 0 1"=50'-0" 50' 100' 0 1"=60'-0" 60' 120' 0 1"=80'-0" 80' 160' 0 1"=100'-0" 100' 200' 0 1"=200'-0" 200' 400' 0 1"=400'-0" 400' 800' 0 1"=500'-0" 500' 1000' 0 1"=1000'-0" 1000' 2000' 0 1' 2' 11 2"=1'-0" 0 1' 2' 0 3 1"=1'-0" 2' 4' 0 1 4"=1'-0" 2' 4' 0 3 2"=1'-0" 4' 8' 0 1 8"=1'-0" 4' 8 0 3 4"=1'-0" 8' 16' 0 1 16"=1'-0" 8' 16' 0 3 8"=1'-0" 16' 32' 0 16' 32' 1 "=1'-0" 16 32"=1'-0" 0 1 32' 64' 32"=1'-0" GHAFARI ASSOCIATES, LLC 2816 6TH AVENUE SOUTH BIRMINGHAM, AL 35233 USA TEL +1.205.585.5535 www.ghafari.com jh Jill Hicks Design, LLC post office box 530802 birmingham, alabama 35253 tele: 205-871-0484 M:\215210\HVAC\215210 HVAC.dwg REV 01-22-16 DR04 Addendum #1 01-11-16 DR03 Construction 01-04-16 DR01 Review DATE ISSUED FOR BRYSON EUWER FORUM BUILDING TENANT FIT-OUT FOR LIFEGUARD AMBULANCE PROJECT # 157380.000 S.HEYWOOD 1/22/2016 2:53:34 PM PROJECT MANAGER DESIGNED BY SAMMY DAVIS DRAWN BY B.EUWER QUALCHECK SHEET TITLE SAMMY DAVIS 7TH FLOOR HVAC PLAN MD1-07-01 SHEET NUMBER 0 1"=10'-0" 10' 20' 0 1"=20'-0" 20' 40' 0 1"=30'-0" 30' 60' 0 1"=40'-0" 40' 80' 0 1"=50'-0" 50' 100' 0 1"=60'-0" 60' 120' 0 1"=80'-0" 80' 160' 0 1"=100'-0" 100' 200' 0 1"=200'-0" 200' 400' 0 1"=400'-0" 400' 800' 0 1"=500'-0" 500' 1000' 0 1"=1000'-0" 1000' 2000' 0 1' 2' 112"=1'-0" 0 1' 2' 0 3 1"=1'-0" 2' 4' 0 1 4"=1'-0" 2' 4' 0 3 2"=1'-0" 4' 8' 0 1 8"=1'-0" 4' 8 0 3 4"=1'-0" 8' 16' 0 1 16"=1'-0" 8' 16' 0 3 8"=1'-0" 16' 32' 0 16' 32' 1 "=1'-0" 16 32"=1'-0" 0 1 32' 64' 32"=1'-0" GHAFARI ASSOCIATES, LLC 2816 6TH AVENUE SOUTH BIRMINGHAM, AL 35233 USA TEL +1.205.585.5535 www.ghafari.com OFFICE 707 OFFICE 702 CLOSET 700A COPY 701 ADMN 712 OFFICE 714 OFFICE 715 OFFICE 716 OFFICE 717 OFFICE 718 RECEPTION 700 jh Jill Hicks Design, LLC OFFICE 706 post office box 530802 birmingham, alabama 35253 tele: 205-871-0484 BREAK 703 OPEN OFFICE 704 DISPATCH 720 BREAK 713 OFFICE 705 DISPATCH 2 719 STORAGE 709 PASSAGE 708 FILES 710 STORAGE 711 M:\215210\HVAC\215210 HVAC.dwg REV 01-22-16 DR04 Addendum #1 01-11-16 DR03 Construction 01-04-16 DR01 Review DATE ISSUED FOR BRYSON EUWER FORUM BUILDING TENANT FIT-OUT FOR LIFEGUARD AMBULANCE PROJECT # 157380.000 S.HEYWOOD 1/25/2016 7:32:41 AM PROJECT MANAGER DESIGNED BY SAMMY DAVIS DRAWN BY B.EUWER QUALCHECK SHEET TITLE SAMMY DAVIS 7TH FLOOR HVAC PLAN MH1-07-01 SHEET NUMBER 0 1"=10'-0" 10' 20' 0 1"=20'-0" 20' 40' 0 1"=30'-0" 30' 60' 0 1"=40'-0" 40' 80' 0 1"=50'-0" 50' 100' 0 1"=60'-0" 60' 120' 0 1"=80'-0" 80' 160' 0 1"=100'-0" 100' 200' 0 1"=200'-0" 200' 400' 0 1"=400'-0" 400' 800' 0 1"=500'-0" 500' 1000' 0 1"=1000'-0" 1000' 2000' 01/22/2016 01/22/2016 01/22/2016