walsall Explosion Protected Electrical Equipment

Transcription

walsall Explosion Protected Electrical Equipment
walsall
Walsall Ltd
Cornwallis Road, West Bromwich, West Midlands, B70 7DX. United Kingdom
Telephone: +44 (0) 121 500 6161 Fax: +44 (0) 121 500 6300
Email: [email protected] www.walsall-ltd.com
Walsall Asia Pacific Pte Ltd
10 Upper Aljunied Link, York International Industrial Building #02-05, Singapore 367904
Telephone: (65) 6858-5259 Fax : (65) 6858-6560
Email : [email protected] www.walsall-ltd.com
Please refer to website for a comprehensive list of worldwide partners
ATEX GOST
The information contained in this catalogue has been carefully compiled. Walsall Ltd does not accept any responsibility for loss caused by any error contained herein.
Cover photo courtesy of Royal Dutch Shell
Edition 2006/1
Design by Nexus Creative Ltd +44 (0)1905 821919 www.nexuscl.com
Explosion Protected Electrical Equipment
Your Local Distributor
Terminal Boxes
Local Control Stations and Panels
Power Switching
Motor Control
Distribution Boards
Lighting
Plugs and Sockets
Emergency Shutdown and Signalling Equipment
Installation Accessories
An Introduction to Walsall
CONTENTS
Walsall Conduits started designing and manufacturing electrical
equipment for hazardous areas in the 1930’s. In those days
the company concentrated on equipment for underground
applications, particularly coal mining. The products were
designated flameproof for what is now known as Group
1 applications.
Walsall has been involved in many worldwide projects
over the past few years, a sample of which are shown
below-
As petro-chemical and pharmaceutical operations were
developed through the later half of the 20th Century Walsall
designed and manufactured products for above ground
applications particularly in the fields of switch gear and motor
control gear.
Shell Bintulu - Far East - EEx d fluorescent lighting
In 2000 the company was renamed Walsall Ltd and began a
new phase of development by widening the product range
significantly.
Heathrow Airport - UK - EEx d wellglasses & panels
From inception to the present day Walsall products have
become specified in all parts of the world. The name Walsall
has become synonymous with hazardous area electrical
equipment and its products can be seen working everywhere
where explosive hazards exist.
Channel Tunnel - UK - EEx e,ia junction boxes
Walsall has always been known for the robustness of its
products. It is well known that Walsall products were built to
last and the company is still called out to help with installations
performing after more than 50 years. This philosophy of
building the strongest and safest equipment runs right through
the company’s operations.
PFD-Tengichevrol - Russia - EEx e,ia junction boxes & Eexd panels
All products are approved by the British Notified Bodies
Baseefa and SIRA , and the manufacturing facility is
ATEX/UL/GOST/ISO9001:2000 approved. The company is still
very much a designer and manufacturer of its own products.
Many of the manufacturing processes are vertically integrated
within the Walsall plant.
South Pars - Middle East - EEx d fluorescent lighting
This gives the company complete control of quality at each
stage of manufacturing and the facility to offer excellent levels
of service. Customising products and systems is now a
speciality of the operation.
Petrofac - Kashagan - Russia - EEx e,ia junction boxes
Shell Sarawak - Malaysia - EEx e,ia junction boxes
Shell Bonga - Nigeria - EEx e,ia junction boxes
BP Grangemouth - UK - EEx d control stations
Esso Fawley - UK - EEx de fluorescent lighting
Maersk Air - Europe - EEx de control stations (local)
Hong Kong Airport - Far East - EEx d fluorescent lighting
Bangkok Airport - FarEast - EEx d fluorescent lighting
PDO – Compressor upgrades - Oman - EEx de breakglass units & jb's
Buhasa upgrade – AbuDhabi (GASCO) - Middle East - EEx e,ia junction box
Hazardous Areas and the Specification of Electrical Equipment
Page 3 - 6
PFD-Sahakalin pipeline - Russia - EEx e,ia junction boxes
NIOEC-Compressor upgrade - Middle East - EEx d control stations & panels
Part 1
Terminal Boxes
Page 8 - 80
IOEC-Pumping stations - Middle East - EEx d control stations & panels
PCC-Methanol Plant - Middle East - EEx e,ia junction boxes
South Pars - Middle East - EEx d control stations & panels
Styrene Monomer Plant - Iran - EEx e,ia junction boxes
Part 2
Control in GRP, Stainless Steel and Aluminium Enclosures
Page 82 - 128
Part 3
Control in Cast Iron, Cast Stainless Steel and Cast Aluminium Enclosures
Page 130 - 150
Part 4
Power Switching
Page 152 - 170
Part 5
Motor Control
Page 172 - 182
Part 6
Distribution Boards
Page 184 - 186
Part 7
Lighting
Page 188 - 208
Part 8
Plugs and Sockets
Page 210 - 214
Part 9
Emergency Shutdown and Signalling Equipment
Page 216 - 226
Part 10
Installation Accessories
Page 228 - 236
MOL Danube Refinery - Hungary - EEx e,ia junction boxes
Ourhoud - Socket Panels - Algeria - EEx d/EExde Socket Panels
Bechtel - Karachaganak - Russia - EEx e,ia junction boxes
NPCC - Abu Dhabi - Middle East - EEx d Control Panels + Isolators
Conoco Phillips/Fluor Daniel - Bohai Phase II - US - EEx e HV terminal box
ABB - Offshore Khuff Gas Development - Middle East - EEx d Control Panels
A selection of specifiers, end-users and installers of Walsall
products includeShell, BP, Chevron, Agip, Maersk Oil & Gas, Elf, NIGC,
IOEC, NIOC, Pfizer, Glaxo, Petrobras, Woodside, ADNOC,
GASCO, ZADCO, Saudi Aramco, Texaco, Aker-Kvaerner,
Brown & Root, Costain, Conoco Philips , ABB, KBR,
Bechtel, PFD, Snamprogetti, Cegelec, Technip,
Mustang Engineering, Petronas, Marathon Oil & Gas,
Transco, BNFL, London Underground, Virgin, Ikea,
British Sugar……
ATEX GOST
2003/383
1
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
2
A Guide to the Selection of Electrical Equipment for Installation in
Hazardous Areas
A Guide to the Selection of Electrical Equipment for Installation in
Hazardous Areas
The information below is given as a guide to enable the users of this
catalogue to select the correct equipment for their application.
It should not be used to define the nature of hazardous areas, this is a
task for experienced professionals in the field of hazardous area definition.
Nor should it be used as replacement for the very detailed standards
which cover the installation of electrical equipment in hazardous areas.
THE CLASSIFICATION OF HAZARDOUS AREAS
Gases, Vapours, Mists and Dusts.
What conditions are required for an explosion?
Explosive atmospheres are caused by a mixture of gases, vapours,
mists dusts and air.
If the explosive atmosphere is caused by gases, vapours and mists
the hazardous area is coded G.
If the explosive atmosphere is caused by dusts the hazardous area is
coded D.
There are three elements required in order to create a hazardous area.
Explosion Groups
HAZARDOUS ATMOSPHERES
1.
2
3.
Air.
An flammable medium for example gases, vapours, mists
and dusts.
A source of ignition of sufficient energy and /or a rise in temperature.
GAS
OR
DUST
AIR
In the first instance equipment is divided into two groups depending
on its location above or below ground.
What is an explosive atmosphere?
An explosive atmosphere is created when air and an flammable medium
mix such that a rise in temperature or an electrical spark produces an
explosion.
Explosion protected electrical equipment is classified in terms of the
ignition temperature, the ignition capability and flame transmission
capacity of the explosive atmosphere in which it is designed to operate.
SPARK
Group I Electrical equipment for use below ground in areas
susceptible to firedamp.
Group II Electrical equipment for all other areas.
What is a potentially explosive atmosphere?
An atmosphere is defined as potentially explosive when in its normal
state it is not explosive but there exists the possibility that in abnormal
circumstances it will become explosive. For example in the case of
a gas leak or the vapourisation of a fluid leak.
Ignition Energy
An explosive atmosphere needs a minimum energy for ignition.
The energy produced by arcs and sparks are many times greater than this
minimum.
Self Ignition Temperature
An explosive atmosphere can self ignite if the local temperature rises
above the so-called self ignition temperature. This temperature is
different for different flammable mediums. Self ignition temperatures
for a range of commonly found flammable gasses and dust are given in
Table 1 and 2.
Table 1
Typical self ignition temperatures for Gases
Gas
Butane
Ethyl acetate
Acetylene
Ethylene
Carbon disulphide
Hydrogen
Acetone
Ammonia
Ethyle nitrate
Benzne
Industrial methane
Carbon monoxide
Table 2
Typical self ignition temperatures for Dusts
Dust
Cellulose
Cocoa
Flour
Lead
Lignite
Polyacrylonitrate
Soya meal
Zinc
3
Temp. +˚C
287
425
300
450
90
500
465
650
90
498
535
605
Temp. +˚C
Cloud
Layer
490
430
500
200
490
430
460
240
380
225
540
400
540
340
570
440
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Table 3
Examples of gases divided into gas groups
I
Methane
IIB
IIC
IIA
Town gas
Hydrogen
Acetone
Benzol
Ethylene
Acetylene
Acetic acid
Carbon disulphide
Methanol
Petrol
Diesel
Aviation fuel
Carbon monoxide
Heating oils
Acetaldehyde
Group II equipment is further divided into three sub groups
depending on the ignition and flame transmission characteristics
of the explosive hazard.
These sub-groups are designated IIA, IIB and IIC.
Zones - the probability of an explosive atmosphere occurring.
Zone 0 defines an area in which an explosive atmosphere caused
by a mixture of air and gases, vapours and mists is present
continuously for long periods or very frequently.
Zone 1 defines areas in which an explosive atmosphere caused
by a mixture air and gases, vapours and mists is expected to occur
occasionally.
Zone 2 defines areas in which an explosive atmosphere caused
by a mixture of air and gases, vapours and mists is unlikely and
if it should occur it will be for a short time and then only rarely.
Zone 20 defines an area in which an explosive atmosphere caused
by a cloud of combustible dust and air is present continuously for
long periods or very frequently.
Zone 21 defines areas in which an explosive atmosphere caused
by a cloud of combustible dust and air is expected to occur occasionally.
Table 4
Definition of zones
Zones
Type of Hazard
Probability of
Hazard
0
G
20
D
Continuous
1
G
21
D
Infrequent
2
G
22
D
Occasional
Zone 22 defines areas in which an explosive atmosphere caused
by a cloud of combustible dust and air is unlikely and if it should occur
it will be for a short time and then only rarely.
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
4
A Guide to the Selection of Electrical Equipment for Installation in
Hazardous Areas
A Guide to the Selection of Electrical Equipment for Installation in
Hazardous Areas
Table 5
Temperature Classes
Ignition Temperature
The ignition temperature is the lowest temperature on the surface at which
an explosive atmosphere will ignite.
Gases and dusts have been divided into temperature classes according to
their ignition temperatures so that electrical equipment can be further
sub-divided into six temperature classes T1 to T6.
The temperature classes are shown in Table 5.
Note. The maximum operating surface temperature of a piece of
electrical equipment must always be below the ignition temperature
of the explosive mixture, see Table 6 opposite.
Temperature
Class
T1
T2
T3
T4
T5
T6
Ingress Protection
Maximum Surface
Temperature ˚C
450
300
200
135
100
85
Because hazardous area electrical equipment is very often used in
hostile atmospheric environments the standards call for minimum
levels of protection against water and dust. For example the minimum
level set is IP54 however in the case of dust hazards the minimum level
ingress protection is set at IP64.
The range of IP levels are shown in Table 8 opposite
Table 8
IP Rating IPXY
X
0
1
2
3
4
5
6
Protected From
None
Solids <50mm diam
Solids <12.5mm diam
Solids <2.5mm diam
Solids <1.0mm diam
Dust protected
Dust tight
Y
0
1
2
3
4
5
6
Protected From
None
Water dripping vertically
Water dripping at 15 deg
Spray water at 60 deg
Splash water from any direction
Jet water from any direction
Powerful water jets from any
direction
7 Water when submerged for
limited time
8 Water when submerged for
indeterminate time
Table 6
Self ignition Temperatures and Temperature
Classes
Self Ignition
Temperature ˚C
85˚<T˚<100˚C
100˚<T˚<135˚C
135˚<T˚<200˚C
200˚<T˚<300˚C
300˚<T˚<450˚C
450˚<T˚
T6
(85˚)
Temperature class of the equipment
T4
T3
T2
T1
T5
(100˚) (135˚) (200˚) (300˚) (450˚)
EXPLOSION
READING THE LABEL
The ATEX standards call for the manufacturers of hazardous area
electrical equipment to label their products with the following information.
A typical label for a flood light is shown for reference in Table 9.
1.
Name of manufacturer
2.
Product type code
3.
Address of manufacturer
4.
Year of manufacture
5.
Marking in accordance with directive 94/9/EC
II 3 GD – group II location, category 3 equipment, for gas
and dust hazards
Table 9
Typical product label
3
1
6
6.
Equipment Categories.
Electrical equipment for hazardous areas is designed to comply
with different fault levels depending on the Zone in which the equipment
is to be installed. These fault levels are designated as Categories 1, 2 and
3. Their relationship with the zones, the potential for an explosive
atmosphere and the type of explosive atmosphere is shown in Table 7
opposite.
5
Table 7
Relationship between zones and equipment categories
Zones
Type of Hazard
Categories
0
G
20
D
1
1
G
21
D
2
2
G
22
D
3
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Marking in accordance with European standards
EEx nR II T – built and tested to European standards, type of
protection, explosion group, temperature class
7.
CE marking together with notified body registration number
8.
Notified testing body and reference number
9.
Serial number
10.
Technical data
11.
Ingress protection
5
11
7
8
2
10
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
4
9
6
PART 1.0
TERMINAL BOXES
Comprehensive ranges of EEx e, EEx i and EEx d terminal boxes in
fabricated stainless steel, mild steel and aluminium, glass reinforced
polyester, cast aluminium, cast iron and cast stainless steel.
1.1 SL Range
Page 9
Small EEx e and EEx i approved terminal boxes and enclosures without gland
plates in fabricated stainless and mild steel
1.2 FXL Range
Page 17
Medium to large EEx e and EEx i approved terminal boxes and enclosures
with the option of up to 4 gland plates and a detachable hinged cover,
fabricated in stainless and mild steel
1.3 XL Range
Page 31
Medium to large EEx e and EEx i approved terminal boxes and enclosures
with the option of up to 4 gland plates and a detachable hinged cover,
fabricated in stainless and mild steel
1.4 HVB Range
Page 45
High voltage terminal boxes rated at 3.3 and 6.6kV
1.5 AL Range
Page 47
Small EEx e and EEx i approved terminal boxes and enclosures
without gland plates in fabricated aluminium
1.6 GVU Junction Box
Page 55
EEx e Junction Box in Glass Reinforced Polyester with Pillar or MK Terminals
1.7 GL Range
Page 57
Small, medium and large EEx e and EEx i approved terminal boxes
and enclosures in glass reinforced polyester
1.8 E Range
Page 73
Small EEx d approved terminal boxes in cast iron
1.9 ASMT Range
Page 77
Medium and large EEx d approved terminal boxes and enclosures
in cast aluminium, cast iron and cast stainless steel
7
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
8
EEx e and EEx i Terminal Boxes - Stainless and Mild Steel
Type SL1 - 110mm x 110mm x 65mm
PART 1.1
SL RANGE
EEx e II and EE x ia IIC
Zones 0,1,2,21,22
T3,T4,T5,T6
Group II Cat 1,2
ATEX/GOST/UL
HAZARDOUS AREA SPECIFICATION
Small EEx e and EEx i approved terminal boxes and
enclosures without gland plates, fabricated from electro
polished stainless steel and powder coated mild steel.
The terminal boxes have ingress protection to IP66/67.
Type SL1 – 110mm x 110mm x 65mm
Page 10
Type SL2 – 120mm x 120mm x 80mm
Page 11
Type SL3 – 150mm x 120mm x 80mm
Page 12
Type SL4 – 150mm x 150mm x 90mm
Page 13
Type SL5 – 190mm x 150mm x 90mm
Page 14
Type SL6 – 190mm x 190mm x 100mm
Page 15
CUSTOMISING
As a vertically integrated manufacturer Walsall can customise
the SL range at each stage of the manufacturing process to
meet individual customer requirements.
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
II 2 GD,
II 1 GD T6,T5,T4,T3.
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5 (+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66/67 to EN60529:1992
Maximum 9 Watts. Except for dust applications
where the maximum is 4.5 Watts
ENCLOSURE SPECIFICATION
Dimensions
Material box
Finish
Weight empty
Cover fixing
Gasket
Earthing
Entries
External Mounting
Internal Mounting
110mm x 110mm x 65mm
1.5mm 316L, (1.4404) stainless steel or mild steel
Stainless steel – electropolished
Mild steel – Powder coated RAL 7032
1.2Kg
Captive M6 stainless steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
6mm brass internal/external earth stud as standard
Optional brass earth stud welded to cover
Direct through body
External lugs with 8mm clearance holes
DIN rail or mounting plate to suit
All Dimensions in mm
A GUIDE TO PHYSICAL TERMINAL CAPACITY
Verticle Rail
Horizontal Rail
WDU 2.5
1x14
1x14
WDU 4
1x11
1x11
A GUIDE TO ENTRY CAPACITY
WDU 6
1x8
1x8
Gland Size mm
Side A + B
Side C + D
WDU 10
1x6
1x6
20
3
3
25
2
2
32
0
0
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
ORDERING INFORMATION
Material
Stainless Steel
Mild Steel
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, mild steel powder coated
10mm internal/external stainless steel earth stud
9
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
EEx e Terminal Box
SLS11
SLM11
EEx e U Component Approved Enclosure
SLS12
SLM12
EEx ia Terminal Box
SLS13
SLM13
CES6
SL1MP
SSET
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
10
EEx e and EEx i Terminal Boxes - Stainless and Mild Steel
Type SL2 - 120mm x 120mm x 80mm
EEx e II and EE x ia IIC
Zones 0,1,2,21,22
T3,T4,T5,T6
EEx e and EEx i Terminal Boxes - Stainless and Mild Steel
Type SL3 - 150mm x 120mm x 80mm
Group II Cat 1,2
ATEX/GOST/UL
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
Weight empty
Cover fixing
Gasket
Earthing
Entries
External Mounting
Internal Mounting
Zones 0,1,2,21,22
T3,T4,T5,T6
Group II Cat 1,2
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5 (+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66/67 to EN60529:1992
Maximum 9 watts. Except for dust applications
where the maximum is 4.5 Watts
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5 (+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66/67 to EN60529:1992
Maximum 9 Watts. Except for dust applications
where the maximum is 4.5 Watts
ENCLOSURE SPECIFICATION
120mm x 120mm x 80mm
1.5mm 316L, (1.4404) stainless steel or mild steel
Stainless steel – electropolished
Mild steel – Powder coated RAL 7032
1.4Kg
Captive M6 stainless steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
6mm brass internal/external earth stud as standard
Optional brass earth stud welded to cover
Direct through body
External lugs with 8mm clearance holes
DIN rail or mounting plate to suit
Dimensions
Material box
Finish
Weight empty
Cover fixing
Gasket
Earthing
Entries
External Mounting
Internal Mounting
150mm x 120mm x 80mm
1.5mm 316L, (1.4404) stainless steel or mild steel
Stainless steel – electropolished
Mild steel – Powder coated RAL 7032.
1.6Kg
Captive M6 stainless steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
6mm brass internal/external earth stud as standard
Optional brass earth stud welded to cover
Direct through body
External lugs with 8mm clearance holes
DIN rail or mounting plate to suit
All Dimensions in mm
A GUIDE TO PHYSICAL TERMINAL CAPACITY
Verticle Rail
Horizontal Rail
WDU 2.5
1x16
1x16
WDU 4
1x13
1x13
All Dimensions in mm
A GUIDE TO ENTRY CAPACITY
WDU 6
1x9
1x9
Gland Size mm
Side A + B
Side C + D
WDU 10
1x7
1x7
20
6
6
A GUIDE TO PHYSICAL TERMINAL CAPACITY
25
3
3
32
2
2
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Verticle Rail
Horizontal Rail
WDU 2.5
1x22
1x16
WDU 4
1x18
1x13
A GUIDE TO ENTRY CAPACITY
WDU 6
1x13
1x9
Gland Size mm
Side A + B
Side C + D
WDU 10
1x10
1x7
20
8
6
25
4
3
32
2
2
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
ORDERING INFORMATION
ORDERING INFORMATION
Material
Stainless Steel
Mild Steel
EEx e Terminal Box
SLS21
SLM21
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, mild steel powder coated
10mm internal/external stainless steel earth stud
11
ATEX/GOST/UL
HAZARDOUS AREA SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material box
Finish
EEx e II and EE x ia IIC
EEx e U Component Approved Enclosure
SLS22
SLM22
EEx ia Terminal Box
SLS23
SLM23
CES6
SL2MP
SSET
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Material
Stainless Steel
Mild Steel
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, mild steel powder coated
10mm internal/external stainless steel earth stud
EEx e Terminal Box
SLS31
SLM31
EEx e U Component Approved Enclosure
SLS32
SLM32
EEx ia Terminal Box
SLS33
SLM33
CES6
SL3MP
SSET
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
12
EEx e and EEx i Terminal Boxes - Stainless and Mild Steel
Type SL4 - 150mm x 150mm x 90mm
EEx e II and EE x ia IIC
Zones 0,1,2,21,22
T3,T4,T5,T6
EEx e and EEx i Terminal Boxes - Stainless and Mild Steel
Type SL5 - 190mm x 150mm x 90mm
Group II Cat 1,2
ATEX/GOST/UL
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
Weight empty
Cover fixing
Gasket
Earthing
Entries
External Mounting
Internal Mounting
Zones 0,1,2,21,22
T3,T4,T5,T6
Group II Cat 1,2
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5 (+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66/67 to EN60529:1992
Maximum 11 Watts. Except for dust applications
where the maximum is 5.5 Watts
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5 (+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66/67 to EN60529:1992
Maximum 11 Watts. Except for dust applications
where the maximum is 5.5 Watts
ENCLOSURE SPECIFICATION
150mm x 150mm x 90mm
1.5mm 316L, (1.4404) stainless steel or mild steel
Stainless steel – electropolished
Mild steel – Powder coated RAL 7032
1.9Kg
Captive M6 stainless steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
6mm brass internal/external earth stud as standard
Optional brass earth stud welded to cover
Direct through body
External lugs with 8mm clearance holes
DIN rail or mounting plate to suit
Dimensions
Material box
Finish
Weight empty
Cover fixing
Gasket
Earthing
Entries
External Mounting
Internal Mounting
190mm x 150mm x 90mm
1.5mm 316L, (1.4404) stainless steel or mild steel
Stainless steel – electropolished
Mild steel – Powder coated RAL 7032
2Kg
Captive M6 stainless steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
6mm brass internal/external earth stud as standard
Optional brass earth stud welded to cover
Direct through body
External lugs with 8mm clearance holes
DIN rail or mounting plate to suit
All Dimensions in mm
A GUIDE TO PHYSICAL TERMINAL CAPACITY
Verticle Rail
Horizontal Rail
WDU 2.5
1x22
1x22
WDU 4
1x18
1x18
All Dimensions in mm
A GUIDE TO ENTRY CAPACITY
WDU 6
1x13
1x13
Gland Size mm
Side A + B
Side C + D
WDU 10
1x10
1x10
20
8
8
A GUIDE TO PHYSICAL TERMINAL CAPACITY
25
5
5
32
3
3
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Verticle Rail
Horizontal Rail
WDU 2.5
1x30
1x22
WDU 4
1x24
1x18
A GUIDE TO ENTRY CAPACITY
WDU 6
1x18
1x13
Gland Size mm
Side A + B
Side C + D
WDU 10
1x14
1x10
20
8
10
25
5
7
32
3
3
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
ORDERING INFORMATION
ORDERING INFORMATION
Material
Stainless Steel
Mild Steel
EEx e Terminal Box
SLS41
SLM41
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, mild steel powder coated
10mm internal/external stainless steel earth stud
13
ATEX/GOST/UL
HAZARDOUS AREA SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material box
Finish
EEx e II and EE x ia IIC
EEx e U Component Approved Enclosure
SLS42
SLM42
EEx ia Terminal Box
SLS43
SLM43
CES6
SL4MP
SSET
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Material
Stainless Steel
Mild Steel
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, mild steel powder coated
10mm internal/external stainless steel earth stud
EEx e Terminal Box
SLS51
SLM51
EEx e U Component Approved Enclosure
SLS52
SLM52
EEx ia Terminal Box
SLS53
SLM53
CES6
SL5MP
SSET
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
14
EEx e and EEx i Terminal Boxes - Stainless and Mild Steel
Type SL6 - 190mm x 190mm x 100mm
EEx e II and EE x ia IIC
Zones 0,1,2,21,22
T3,T4,T5,T6
Group II Cat 1,2
ATEX/GOST/UL
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5 (+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66/67 to EN60529:1992
Maximum 13 watts. Except for dust applications
where the maximum is 6.5 Watts
ENCLOSURE SPECIFICATION
Dimensions
Material box
Finish
Weight empty
Cover fixing
Gasket
Earthing
Entries
External Mounting
Internal Mounting
190mm x 190mm x 100mm
1.5mm 316L, (1.4404) stainless steel or mild steel
Stainless steel – electropolished
Mild steel – Powder coated RAL 7032
3Kg
Captive M6 stainless steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
6mm brass internal/external earth stud as standard
Optional brass earth stud welded to cover
Direct through body
External lugs with 8mm clearance holes
DIN rail or mounting plate to suit
All Dimensions in mm
A GUIDE TO PHYSICAL TERMINAL CAPACITY
Verticle Rail
Horizontal Rail
WDU 2.5
1x30
1x30
WDU 4
1x24
1x24
A GUIDE TO ENTRY CAPACITY
WDU 6
1x18
1x18
Gland Size mm
Side A + B
Side C + D
WDU 10
1x14
1x14
20
14
14
25
8
8
32
4
4
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
ORDERING INFORMATION
Material
Stainless Steel
Mild Steel
EEx e Terminal Box
SLS61
SLM61
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, mild steel powder coated
10mm internal/external stainless steel earth stud
15
EEx e U Component Approved Enclosure
SLS62
SLM62
EEx ia Terminal Box
SLS63
SLM63
CES6
SL6MP
SSET
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
16
EEx e and EEx i Terminal Boxes - Stainless and Mild Steel
Type FXL1 - 229mm x 152mm x 130mm
PART 1.2
FXL RANGE
EEx e II and EE x ia IIC
Zones 0,1,2,21,22
T3,T4,T5,T6
Group II Cat 1,2
HAZARDOUS AREA SPECIFICATION
Medium to large EEx e and EEx i approved terminal boxes
with an outward return cover sealing flange. There is an option
of up to 4 gland plates. The cover is detachable and hinged.
The enclosure is fabricated from electroplated stainless steel
or powder coated mild steel. The terminal boxes have
Ingress Protection to IP66, 67.
Type FXL1 – 229mm x 152mm x 130mm
Page 18
Type FXL2 – 260mm x 260mm x 150mm or 200mm
Page 19
Type FXL3 – 306mm x 306mm x 150mm or 200mm
Page 20
Type FXL4 – 380mm x 260mm x 150mm or 200mm
Page 21
Type FXL5 – 458mm x 382mm x 150mm or 200mm
Page 22
Type FXL6 – 480mm x 480mm x 150mm or 200mm
Page 23
Type FXL7 – 500mm x 350mm x 150mm or 200mm
Page 24
Type FXL8 – 620mm x 450mm x 150mm or 200mm
Page 25
Type FXL9 – 762mm x 508mm x 150mm or 200mm
Page 26
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
Type FXL10 – 914mm x 610mm x 200mm or 300mm Page 27
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5(+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66,67 to EN60529:1992
Maximum 15 Watts. Except for dust applications
where the maximum is 7.5 Watts
ENCLOSURE SPECIFICATION
Dimensions
Material box
Material gland plate
Finish
Weight empty
Cover fixing
Gasket
Earthing
Security
Entries
Mounting
229mm x 152mm x 130mm
1.5mm 316L, (1.4404) stainless steel or mild steel
2.5mm 316L, (1.4404) stainless steel or mild steel
Stainless steel – electropolished
Mild steel – Powder coated RAL 7032
3.4Kg
Fully detachable hinged cover with captive M6 stainless
steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Optional earth stud welded to gland plate
Padlockable hasp
Via gland plates 1-4 or direct through body
External lugs with 10mm clearance holes
Return flange sealing
All Dimensions in mm
Type FXL11 – 1177mm x 777mm x 210mm or 300mm Page 28
Type FXLX – 2000mm max x 1250mm max x 600mm max
A GUIDE TO PHYSICAL TERMINAL CAPACITY
Page 29
Verticle Rail
Horizontal Rail
CUSTOMISING
As a vertically integrated manufacturer Walsall can customise the
FXL range at each stage of the manufacturing process to meet
individual customer requirements
WDU 2.5
1x35
1x20
WDU 4
1x29
1x16
Gland Size mm
Side A + B
Side C + D
WDU 10
1x16
1x9
20
6
6
25
3
3
32
2
2
* More entries are available if direct entry is used
ORDERING INFORMATION
Gland Plate options
Material
Number
0
0
1
1
2
2
3
3
4
4
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, mild steel powdercoated
Brass padlock with 2 keys
10mm internal/external stainless steel earth stud
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
A GUIDE TO ENTRY CAPACITY FOR GLAND PLATES*
WDU 6
1x21
1x12
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
17
ATEX/GOST/UL
Location
B
B
AB
AB
BCD
BCD
ABCD
ABCD
CES6
XL1MP
BP2
SSET
EEx e Terminal Box
FXLS110
FXLM110
FXLS111
FXLM111
FXLS112
FXLM112
FXLS113
FXLM113
FXLS114
FXLM114
Product Codes
EEx e U Component Approved
FXLS120
FXLM120
FXLS121
FXLM121
FXLS122
FXLM122
FXLS123
FXLM123
FXLS124
FXLM124
Optional Extras
6mm earthing stud welded to gland plate
Rain canopy
Document wallet
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
EEx ia Terminal Box
FXLS130
FXLM130
FXLS131
FXLM131
FXLS132
FXLM132
FXLS133
FXLM133
FXLS134
FXLM134
GPS6
XL1RC
XL1DW
18
EEx e and EEx i Terminal Boxes - Stainless and Mild Steel
Type FXL2 - 260mm x 260mm x 150mm or 200mm
EEx e II and EE x ia IIC
Zones 0,1,2,21,22
T3,T4,T5,T6
Group II Cat 1,2
EEx e and EEx i Terminal Boxes - Stainless and Mild Steel
Type FXL3 - 306mm x 306mm x 150mm or 200mm
ATEX/GOST/UL
EEx e II and EE x ia IIC
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
Weight empty
Cover fixing
Gasket
Earthing
Security
Entries
Mounting
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5(+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66,67 to EN60529:1992
Maximum 15 Watts. Except for dust applications
where the maximum is 7.5 Watts
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
A GUIDE TO PHYSICAL TERMINAL CAPACITY
Verticle Rails
Horizontal Rails
WDU 4
2x34
2x34
WDU 6
2x25
2x25
Dimensions
Material box
Material gland plate
Finish
Weight empty
Cover fixing
Gasket
Earthing
Security
Entries
Mounting
Return flange sealing
All Dimensions in mm
A GUIDE TO ENTRY CAPACITY FOR GLAND PLATES*
WDU 10
2x20
2x20
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Enclosure Size
Gland Size mm
Side A+B
Side C+D
20
17
11
FXL2
25
11
6
32
5
2
20
28
16
306mm x 306mm x 150mm or 200mm
1.5mm 316L, (1.4404) stainless steel or mild steel
2.5mm 316L, (1.4404) stainless steel or mild steel
Stainless steel – electropolished
Mild steel – Powder coated RAL 7032
6.5Kg and 7.0Kg
Fully detachable hinged cover with captive M6 stainless
steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Optional earth stud welded to gland plate
Padlockable hasp
Via gland plates 1-4 or direct through body
External lugs with 10mm clearance holes
A GUIDE TO TERMINAL CAPACITY (WDU type)
FXL2D
25
15
9
32
11
8
ORDERING INFORMATION
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Verticle Rails
Horizontal Rails
WDU 2.5
2x51
2x51
WDU 4
2x42
2x42
WDU 6
2x31
2x31
Return flange sealing
All Dimensions in mm
A GUIDE TO ENTRY CAPACITY FOR GLAND PLATES*
WDU 10
2x24
2x24
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Enclosure Size
Gland Size mm
Side A+B
Side C+D
20
21
15
FXL3
25
12
9
32
6
4
20
32
23
FXL3D
25
18
12
32
12
9
* More entries are available if direct entry is used
ORDERING INFORMATION
Gland Plate options
Number
Location
0
0
1
B
1
B
2
AB
2
AB
3
BCD
3
BCD
4
ABCD
4
ABCD
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, mild steel powdercoated
Brass padlock with 2 keys
10mm internal/external stainless steel earth stud
19
ATEX/GOST/UL
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5(+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66,67 to EN60529:1992
Maximum 21 Watts. Except for dust applications
where the maximum is 10.5 Watts
* More entries are available if direct entry is used
Material
Group II Cat 1,2
ENCLOSURE SPECIFICATION
260mm x 260mm x 150mm or 200mm
1.5mm 316L, (1.4404) stainless steel or mild steel
2.5mm 316L, (1.4404) stainless steel or mild steel
Stainless steel – electropolished
Mild steel – Powder coated RAL 7032
5.5Kg and 6Kg
Fully detachable hinged cover with captive M6 stainless
steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Optional earth stud welded to gland plate
Padlockable hasp
Via gland plates 1-4 or direct through body
External lugs with 10mm clearance holes
WDU 2.5
2x42
2x42
T3,T4,T5,T6
HAZARDOUS AREA SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material box
Material gland plate
Finish
Zones 0,1,2,21,22
Product Code (150mm deep)
Product Code (200mm deep)
EEx e Terminal Box EEx e U Enclosure EEx ia Terminal Box EEx e Terminal Box EEx e U Enclosure EE ia Terminal Box
FXLS230
FXLS210D
FXLS220D
FXLS230D
FXLS220
FXLS210
FXLM230
FXLM210D
FXLM220D
FXLM230D
FXLM220
FXLM210
FXLS231
FXLS211D
FXLS221D
FXLS231D
FXLS221
FXLS211
FXLM231
FXLM211D
FXLM221D
FXLM231D
FXLM221
FXLM211
FXLS232
FXLS212D
FXLS222D
FXLS232D
FXLS222
FXLS212
FXLM222
FXLM232
FXLM212D
FXLM222D
FXLM232D
FXLM212
FXLS213
FXLS223
FXLS233
FXLS213D
FXLS223D
FXLS233D
FXLM213
FXLM223
FXLM233
FXLM213D
FXLM223D
FXLM233D
FXLS214
FXLS224
FXLS234
FXLS214D
FXLS224D
FXLS234D
FXLM214
FXLM224
FXLM234
FXLM214D
FXLM224D
FXLM234D
CES6
XL2MP
BP2
SSET
Optional Extras
6mm earthing stud welded to gland plate
Rain canopy
Document wallet
GPS6
XL2RC
XL2DW
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Material
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Gland Plate options
Number
Location
0
0
1
B
1
B
2
AB
2
AB
3
BCD
3
BCD
4
ABCD
4
ABCD
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, mild steel powdercoated
Brass padlock with 2 keys
10mm internal/external stainless steel earth stud
Product Code (150mm deep)
Product Code (200mm deep)
EEx e Terminal Box EEx e U Enclosure EEx ia Terminal Box EEx e Terminal Box EEx e U Enclosure EE ia Terminal Box
FXLS330
FXLS310D
FXLS320D
FXLS330D
FXLS320
FXLS310
FXLM330
FXLM310D
FXLM320D
FXLM330D
FXLM320
FXLM310
FXLS331
FXLS311D
FXLS321D
FXLS331D
FXLS321
FXLS311
FXLM331
FXLM311D
FXLM321D
FXLM331D
FXLM321
FXLM311
FXLS332
FXLS312D
FXLS322D
FXLS332D
FXLS322
FXLS312
FXLM322
FXLM332
FXLM312D
FXLM322D
FXLM332D
FXLM312
FXLS313
FXLS323
FXLS333
FXLS313D
FXLS323D
FXLS333D
FXLM313
FXLM323
FXLM333
FXLM313D
FXLM323D
FXLM333D
FXLS314
FXLS324
FXLS334
FXLS314D
FXLS324D
FXLS334D
FXLM314
FXLM324
FXLM334
FXLM314D
FXLM324D
FXLM334D
CES6
XL3MP
BP2
SSET
Optional Extras
6mm earthing stud welded to gland plate
Rain canopy
Document wallet
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
GPS6
XL3RC
XL3DW
20
EEx e and EEx i Terminal Boxes - Stainless and Mild Steel
Type FXL4 -380mm x 260mm x 150mm or 200mm
EEx e II and EE x ia IIC
Zones 0,1,2,21,22
T3,T4,T5,T6
Group II Cat 1,2
EEx e and EEx i Terminal Boxes - Stainless and Mild Steel
Type FXL5 - 458mm x 382mm x 150mm or 200mm
ATEX/GOST/UL
EEx e II and EE x ia IIC
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
Weight empty
Cover fixing
Gasket
Earthing
Security
Entries
Mounting
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5(+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66,67 to EN60529:1992
Maximum 21 Watts. Except for dust applications
where the maximum is 10.5 Watts
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
A GUIDE TO PHYSICAL TERMINAL CAPACITY
Verticle Rails
Horizontal Rails
WDU 4
2x49
2x35
WDU 6
2x36
2x26
Weight empty
Cover fixing
Gasket
Earthing
Security
Entries
Mounting
Return flange sealing
All Dimensions in mm
A GUIDE TO ENTRY CAPACITY FOR GLAND PLATES*
WDU 10
2x29
2x20
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Enclosure Size
Gland Size mm
Side A+B
Side C+D
20
17
18
FXL4
25
10
12
32
5
6
20
27
28
458mm x 382mm x 150mm or 200mm
1.5mm 316L, (1.4404) stainless steel or mild steel
2.5mm 316L, (1.4404) stainless steel or mild steel
Stainless steel – electropolished
Mild steel – Powder coated RAL 7032
10Kg and 11Kg
Fully detachable hinged cover with captive M6 stainless
steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Optional earth stud welded to gland plate
Padlockable hasp
Via gland plates 1-4 or direct through body
External lugs with 10mm clearance holes
A GUIDE TO PHYSICAL TERMINAL CAPACITY
FXL4D
25
15
15
32
11
11
ORDERING INFORMATION
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Verticle Rails
Horizontal Rails
WDU 2.5
3x81
3x66
WDU 4
3x67
3x55
WDU 6
3x50
3x40
Return flange sealing
All Dimensions in mm
A GUIDE TO ENTRY CAPACITY FOR GLAND PLATES*
WDU 10
3x39
3x33
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Enclosure Size
Gland Size mm
Side A+B
Side C+D
20
27
27
FXL5
25
17
17
32
9
9
20
40
40
FXL5D
25
24
24
32
17
17
* More entries are available if direct entry is used
ORDERING INFORMATION
GLAND PLATE OPTIONS
Number
Location
0
0
1
B
1
B
2
AB
2
AB
3
BCD
3
BCD
4
ABCD
4
ABCD
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, mild steel powdercoated
Brass padlock with 2 keys
10mm internal/external stainless steel earth stud
21
ATEX/GOST/UL
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5(+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66,67 to EN60529:1992
Maximum 29 Watts. Except for dust applications
where the maximum is 14.5 Watts
* More entries are available if direct entry is used
Material
Group II Cat 1,2
ENCLOSURE SPECIFICATION
Dimensions
Material box
Material gland plate
Finish
380mm x 260mm x 150mm or 200mm
1.5mm 316L, (1.4404) stainless steel or mild steel
2.5mm 316L, (1.4404) stainless steel or mild steel
Stainless steel – electropolished
Mild steel – Powder coated RAL 7032
6.5Kg and 7.0Kg
Fully detachable hinged cover with captive M6 stainless
steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Optional earth stud welded to gland plate
Padlockable hasp
Via gland plates 1-4 or direct through body
External lugs with 10mm clearance holes
WDU 2.5
2x60
2x43
T3,T4,T5,T6
HAZARDOUS AREA SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material box
Material gland plate
Finish
Zones 0,1,2,21,22
Product Code (150mm deep)
Product Code (200mm deep)
EEx e Terminal Box EEx e U Enclosure EEx ia Terminal Box EEx e Terminal Box EEx e U Enclosure EE ia Terminal Box
FXLS430
FXLS410D
FXLS420D
FXLS430D
FXLS420
FXLS410
FXLM430
FXLM410D
FXLM420D
FXLM430D
FXLM420
FXLM410
FXLS431
FXLS411D
FXLS421D
FXLS431D
FXLS421
FXLS411
FXLM431
FXLM411D
FXLM421D
FXLM431D
FXLM421
FXLM411
FXLS432
FXLS412D
FXLS422D
FXLS432D
FXLS422
FXLS412
FXLM422
FXLM432
FXLM412D
FXLM422D
FXLM432D
FXLM412
FXLS413
FXLS423
FXLS433
FXLS413D
FXLS423D
FXLS433D
FXLM413
FXLM423
FXLM433
FXLM413D
FXLM423D
FXLM433D
FXLS414
FXLS424
FXLS434
FXLS414D
FXLS424D
FXLS434D
FXLM414
FXLM424
FXLM434
FXLM414D
FXLM424D
FXLM434D
CES6
XL4MP
BP2
SSET
Optional Extras
6mm earthing stud welded to gland plate
Rain canopy
Document wallet
GPS6
XL4RC
XL4DW
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Material
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
GLAND PLATE OPTIONS
Number
Location
0
0
1
B
1
B
2
AB
2
AB
3
BCD
3
BCD
4
ABCD
4
ABCD
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, mild steel powdercoated
Brass padlock with 2 keys
10mm internal/external stainless steel earth stud
Product Code (150mm deep)
Product Code (200mm deep)
EEx e Terminal Box EEx e U Enclosure EEx ia Terminal Box EEx e Terminal Box EEx e U Enclosure EE ia Terminal Box
FXLS530
FXLS510D
FXLS520D
FXLS530D
FXLS520
FXLS510
FXLM530
FXLM510D
FXLM520D
FXLM530D
FXLM520
FXLM510
FXLS531
FXLS511D
FXLS521D
FXLS531D
FXLS521
FXLS511
FXLM531
FXLM511D
FXLM521D
FXLM531D
FXLM521
FXLM511
FXLS532
FXLS512D
FXLS522D
FXLS532D
FXLS522
FXLS512
FXLM522
FXLM532
FXLM512D
FXLM522D
FXLM532D
FXLM512
FXLS513
FXLS523
FXLS533
FXLS513D
FXLS523D
FXLS533D
FXLM513
FXLM523
FXLM533
FXLM513D
FXLM523D
FXLM533D
FXLS514
FXLS524
FXLS534
FXLS514D
FXLS524D
FXLS534D
FXLM514
FXLM524
FXLM534
FXLM514D
FXLM524D
FXLM534D
CES6
XL5MP
BP2
SSET
Optional Extras
6mm earthing stud welded to gland plate
Rain canopy
Document wallet
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
GPS6
XL5RC
XL5DW
22
EEx e and EEx i Terminal Boxes - Stainless and Mild Steel
Type FXL6 - 480mm x 480mm x 150mm or 200mm
EEx e II and EE x ia IIC
Zones 0,1,2,21,22
T3,T4,T5,T6
Group II Cat 1,2
EEx e and EEx i Terminal Boxes - Stainless and Mild Steel
Type FXL7 - 500mm x 350mm x 150mm or 200mm
ATEX/GOST/UL
EEx e II and EE x ia IIC
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
Weight empty
Cover fixing
Gasket
Earthing
Security
Entries
Mounting
Verticle Rails
Horizontal Rails
T3,T4,T5,T6
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5(+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66,67 to EN60529:1992
Maximum 30 Watts. Except for dust applications
where the maximum is 15 Watts
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5(+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66,67 to EN60529:1992
Maximum 21 Watts. Except for dust applications
where the maximum is 10.5 Watts
A GUIDE TO PHYSICAL TERMINAL CAPACITY
WDU 2.5
WDU 4
WDU 6
4x86
4x71
4x53
4x86
4x71
4x53
WDU 10
4x42
4x42
Weight empty
Cover fixing
Gasket
Earthing
Security
Entries
Mounting
Return flange sealing
All Dimensions in mm
A GUIDE TO ENTRY CAPACITY FOR GLAND PLATES*
Enclosure Size
FXL6
FXL6D
Gland Size mm
20
25
32
20
25
Side A+B
36
22
11
52
33
Side C+D
29
18
9
44
27
500mm x 350mm x 150mm or 200mm
1.5mm 316L, (1.4404) stainless steel or mild steel
2.5mm 316L, (1.4404) stainless steel or mild steel
Stainless steel – electropolished
Mild steel – Powder coated RAL 7032
10.5Kg and 11Kg
Fully detachable hinged cover with captive M6 stainless
steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Optional earth stud welded to gland plate
Padlockable hasp
Via gland plates 1-4 or direct through body
External lugs with 10mm clearance holes
A GUIDE TO PHYSICAL TERMINAL CAPACITY
32
23
18
Verticle Rails
Horizontal Rails
WDU 2.5
3x90
4x60
WDU 4
3x74
4x49
WDU 6
3x55
4x36
ORDERING INFORMATION
Return flange sealing
All Dimensions in mm
A GUIDE TO ENTRY CAPACITY FOR GLAND PLATES*
WDU 10
3x44
4x29
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
* More entries are available if direct entry is used
Enclosure Size
Gland Size mm
Side A+B
Side C+D
20
24
24
FXL7
25
16
16
32
8
8
20
36
36
FXL7D
25
21
21
32
15
15
* More entries are available if direct entry is used
ORDERING INFORMATION
GLAND PLATE OPTIONS
Number
Location
0
0
1
B
1
B
2
AB
2
AB
3
BCD
3
BCD
4
ABCD
4
ABCD
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, mild steel powdercoated
Brass padlock with 2 keys
10mm internal/external stainless steel earth stud
23
ATEX/GOST/UL
ENCLOSURE SPECIFICATION
Dimensions
Material box
Material gland plate
Finish
480mm x 480mm x 150mm or 200mm
1.5mm 316L, (1.4404) stainless steel or mild steel
2.5mm 316L, (1.4404) stainless steel or mild steel
Stainless steel – electropolished
Mild steel – Powder coated RAL 7032
10.4Kg and 11Kg
Fully detachable hinged cover with captive M6 stainless
steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Optional earth stud welded to gland plate
Padlockable hasp
Via gland plates 1-4 or direct through body
External lugs with 10mm clearance holes
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Material
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Group II Cat 1,2
HAZARDOUS AREA SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material box
Material gland plate
Finish
Zones 0,1,2,21,22
Product Code (150mm deep)
Product Code (200mm deep)
EEx e Terminal Box EEx e U Enclosure EEx ia Terminal Box EEx e Terminal Box EEx e U Enclosure EE ia Terminal Box
FXLS630
FXLS610D
FXLS620D
FXLS630D
FXLS620
FXLS610
FXLM630
FXLM610D
FXLM620D
FXLM630D
FXLM620
FXLM610
FXLS631
FXLS611D
FXLS621D
FXLS631D
FXLS621
FXLS611
FXLM631
FXLM611D
FXLM621D
FXLM631D
FXLM621
FXLM611
FXLS632
FXLS612D
FXLS622D
FXLS632D
FXLS622
FXLS612
FXLM622
FXLM632
FXLM612D
FXLM622D
FXLM632D
FXLM612
FXLS613
FXLS623
FXLS633
FXLS613D
FXLS623D
FXLS633D
FXLM613
FXLM623
FXLM633
FXLM613D
FXLM623D
FXLM633D
FXLS614
FXLS624
FXLS634
FXLS614D
FXLS624D
FXLS634D
FXLM614
FXLM624
FXLM634
FXLM614D
FXLM624D
FXLM634D
CES6
XL6MP
BP2
SSET
Optional Extras
6mm earthing stud welded to gland plate
Rain canopy
Document wallet
GPS6
XL6RC
XL6DW
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Material
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
GLAND PLATE OPTIONS
Number
Location
0
0
1
B
1
B
2
AB
2
AB
3
BCD
3
BCD
4
ABCD
4
ABCD
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, mild steel powdercoated
Brass padlock with 2 keys
10mm internal/external stainless steel earth stud
Product Code (150mm deep)
Product Code (200mm deep)
EEx e Terminal Box EEx e U Enclosure EEx ia Terminal Box EEx e Terminal Box EEx e U Enclosure EE ia Terminal Box
FXLS730
FXLS710D
FXLS720D
FXLS730D
FXLS720
FXLS710
FXLM730
FXLM710D
FXLM720D
FXLM730D
FXLM720
FXLM710
FXLS731
FXLS711D
FXLS721D
FXLS731D
FXLS721
FXLS711
FXLM731
FXLM711D
FXLM721D
FXLM731D
FXLM721
FXLM711
FXLS732
FXLS712D
FXLS722D
FXLS732D
FXLS722
FXLS712
FXLM722
FXLM732
FXLM712D
FXLM722D
FXLM732D
FXLM712
FXLS713
FXLS723
FXLS733
FXLS713D
FXLS723D
FXLS733D
FXLM713
FXLM723
FXLM733
FXLM713D
FXLM723D
FXLM733D
FXLS714
FXLS724
FXLS734
FXLS714D
FXLS724D
FXLS734D
FXLM714
FXLM724
FXLM734
FXLM714D
FXLM724D
FXLM734D
CES6
XL7MP
BP2
SSET
Optional Extras
6mm earthing stud welded to gland plate
Rain canopy
Document wallet
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
GPS6
XL7RC
XL7DW
24
EEx e and EEx i Terminal Boxes - Stainless and Mild Steel
Type FXL8 - 620mm x 450mm x 150mm or 200mm
EEx e II and EE x ia IIC
Zones 0,1,2,21,22
T3,T4,T5,T6
Group II Cat 1,2
EEx e and EEx i Terminal Boxes - Stainless and Mild Steel
Type FXL9 - 762mm x 508mm x 150mm or 200mm
ATEX/GOST/UL
EEx e II and EE x ia IIC
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
Weight empty
Cover fixing
Gasket
Earthing
Security
Entries
Mounting
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5(+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66,67 to EN60529:1992
Maximum 41.7 Watts. Except for dust applications
where the maximum is 20.5 Watts
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
A GUIDE TO PHYSICAL TERMINAL CAPACITY
Verticle Rails
Horizontal Rails
WDU 4
5x66
3x94
WDU 6
5x49
3x70
Dimensions
Material box
Material gland plate
Finish
Weight empty
Cover fixing
Gasket
Earthing
Security
Entries
Mounting
Return flange sealing
All Dimensions in mm
A GUIDE TO ENTRY CAPACITY FOR GLAND PLATES*
WDU 10
5x39
3x56
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Enclosure Size
Gland Size mm
Side A+B
Side C+D
20
29
38
FXL8
25
18
24
32
9
12
20
44
56
762mm x 508mm x 150mm or 200mm
2.0mm 316L, (1.4404) stainless steel or mild steel
2.5mm 316L, (1.4404) stainless steel or mild steel
Stainless steel – electropolished
Mild steel – Powder coated RAL 7032
22Kg and 24Kg
Fully detachable hinged cover with captive M6 stainless
steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Optional earth stud welded to gland plate
Padlockable hasp
Via gland plates 1-4 or direct through body
External lugs with 10mm clearance holes
A GUIDE TO PHYSICAL TERMINAL CAPACITY
FXL8D
25
27
36
32
18
24
ORDERING INFORMATION
Verticle Rails
Horizontal Rails
WDU 2.5
4x142
6x91
WDU 4
4x118
6x76
WDU 6
4x88
6x56
Return flange sealing
All Dimensions in mm
A GUIDE TO ENTRY CAPACITY FOR GLAND PLATES*
WDU 10
4x70
6x44
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Enclosure Size
Gland Size mm
Side A+B
Side C+D
20
38
38
FXL9
25
24
24
32
12
12
20
56
56
FXL9D
25
36
36
32
24
24
* More entries are available if direct entry is used
ORDERING INFORMATION
GLAND PLATE OPTIONS
Number
Location
0
0
1
B
1
B
2
AB
2
AB
3
BCD
3
BCD
4
ABCD
4
ABCD
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, mild steel powdercoated
Brass padlock with 2 keys
10mm internal/external stainless steel earth stud
25
ATEX/GOST/UL
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5(+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66,67 to EN60529:1992
Maximum 41.7 Watts. Except for dust applications
where the maximum is 20.5 Watts
* More entries are available if direct entry is used
Material
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Group II Cat 1,2
ENCLOSURE SPECIFICATION
620mm x 450mm x 150mm or 200mm
2.0mm 316L, (1.4404) stainless steel or mild steel
2.5mm 316L, (1.4404) stainless steel or mild steel
Stainless steel – electropolished
Mild steel – Powder coated RAL 7032
17Kg and 17.5Kg
Fully detachable hinged cover with captive M6 stainless
steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Optional earth stud welded to gland plate
Padlockable hasp
Via gland plates 1-4 or direct through body
External lugs with 10mm clearance holes
WDU 2.5
5x80
3x114
T3,T4,T5,T6
HAZARDOUS AREA SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material box
Material gland plate
Finish
Zones 0,1,2,21,22
Product Code (150mm deep)
Product Code (200mm deep)
EEx e Terminal Box EEx e U Enclosure EEx ia Terminal Box EEx e Terminal Box EEx e U Enclosure EE ia Terminal Box
FXLS830
FXLS810D
FXLS820D
FXLS830D
FXLS820
FXLS810
FXLM830
FXLM810D
FXLM820D
FXLM830D
FXLM820
FXLM810
FXLS831
FXLS811D
FXLS821D
FXLS831D
FXLS821
FXLS811
FXLM831
FXLM811D
FXLM821D
FXLM831D
FXLM821
FXLM811
FXLS832
FXLS812D
FXLS822D
FXLS832D
FXLS822
FXLS812
FXLM822
FXLM832
FXLM812D
FXLM822D
FXLM832D
FXLM812
FXLS813
FXLS823
FXLS833
FXLS813D
FXLS823D
FXLS833D
FXLM813
FXLM823
FXLM833
FXLM813D
FXLM823D
FXLM833D
FXLS814
FXLS824
FXLS834
FXLS814D
FXLS824D
FXLS834D
FXLM814
FXLM824
FXLM834
FXLM814D
FXLM824D
FXLM834D
CES6
XL8MP
BP2
SSET
Optional Extras
6mm earthing stud welded to gland plate
Rain canopy
Document wallet
GPS6
XL8RC
XL8DW
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Material
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
GLAND PLATE OPTIONS
Number
Location
0
0
1
B
1
B
2
AB
2
AB
3
BCD
3
BCD
4
ABCD
4
ABCD
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, mild steel powdercoated
Brass padlock with 2 keys
10mm internal/external stainless steel earth stud
Product Code (150mm deep)
Product Code (200mm deep)
EEx e Terminal Box EEx e U Enclosure EEx ia Terminal Box EEx e Terminal Box EEx e U Enclosure EE ia Terminal Box
FXLS930
FXLS910D
FXLS920D
FXLS930D
FXLS920
FXLS910
FXLM930
FXLM910D
FXLM920D
FXLM930D
FXLM920
FXLM910
FXLS931
FXLS911D
FXLS921D
FXLS931D
FXLS921
FXLS911
FXLM931
FXLM911D
FXLM921D
FXLM931D
FXLM921
FXLM911
FXLS932
FXLS912D
FXLS922D
FXLS932D
FXLS922
FXLS912
FXLM922
FXLM932
FXLM912D
FXLM922D
FXLM932D
FXLM912
FXLS913
FXLS923
FXLS933
FXLS913D
FXLS923D
FXLS933D
FXLM913
FXLM923
FXLM933
FXLM913D
FXLM923D
FXLM933D
FXLS914
FXLS924
FXLS934
FXLS914D
FXLS924D
FXLS934D
FXLM914
FXLM924
FXLM934
FXLM914D
FXLM924D
FXLM934D
CES6
XL9MP
BP2
SSET
Optional Extras
6mm earthing stud welded to gland plate
Rain canopy
Document wallet
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
GPS6
XL9RC
XL9DW
26
EEx e and EEx i Terminal Boxes - Stainless and Mild Steel
Type FXL10 - 914mm x 610mm x 200mm or 300mm
EEx e II and EE x ia IIC
Zones 0,1,2,21,22
T3,T4,T5,T6
Group II Cat 1,2
EEx e and EEx i Terminal Boxes - Stainless and Mild Steel
Type FXL11 - 1177mm x 777mm x 210mm or 300mm
ATEX/GOST/UL
EEx e II and EE x ia IIC
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
Weight empty
Cover fixing
Gasket
Earthing
Security
Entries
Mounting
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5(+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66,67 to EN60529:1992
Maximum 93.4 Watts. Except for dust applications
where the maximum is 46 Watts
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
A GUIDE TO PHYSICAL TERMINAL CAPACITY
Verticle Rails
Horizontal Rails
WDU 4
5x143
7x93
WDU 6
5x127
7x69
Dimensions
Material box
Material gland plate
Finish
Weight empty
Cover fixing
Gasket
Earthing
Security
Entries
Mounting
Return flange sealing
All Dimensions in mm
A GUIDE TO ENTRY CAPACITY FOR GLAND PLATES*
WDU 10
5x85
7x55
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Enclosure Size
Gland Size mm
Side A+B
Side C+D
20
72
72
FXL10
25
42
42
32
30
30
FXL10D
20
25
126
84
126
84
1177mm x 777mm x 210mm or 300mm
2.0mm 316L, (1.4404) stainless steel or mild steel
2.5mm 316L, (1.4404) stainless steel or mild steel
Stainless steel – electropolished
Mild steel – Powder coated RAL 7032
36Kg and 39Kg
Fully detachable hinged cover with captive M6 stainless
steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Optional earth stud welded to gland plate
Padlockable hasp
Via gland plates 1-4 or direct through body
External lugs with 10mm clearance holes
A GUIDE TO PHYSICAL TERMINAL CAPACITY
32
50
50
ORDERING INFORMATION
Verticle Rails
Horizontal Rails
WDU 2.5
6x224
9x145
WDU 4
6x187
9x120
WDU 6
6x139
9x90
Return flange sealing
All Dimensions in mm
A GUIDE TO ENTRY CAPACITY FOR GLAND PLATES*
WDU 10
6x111
9x71
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Enclosure Size
Gland Size mm
Side A+B
Side C+D
20
72
72
FXL11
25
42
42
32
30
30
20
126
126
FXL11D
25
84
84
32
50
50
* More entries are available if direct entry is used
ORDERING INFORMATION
GLAND PLATE OPTIONS
Number
Location
0
0
1
B
1
B
2
AB
2
AB
3
BCD
3
BCD
4
ABCD
4
ABCD
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, mild steel powdercoated
Brass padlock with 2 keys
10mm internal/external stainless steel earth stud
27
ATEX/GOST/UL
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5(+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66,67 to EN60529:1992
Maximum 100 Watts. Except for dust applications
where the maximum is 50 Watts
* More entries are available if direct entry is used
Material
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Group II Cat 1,2
ENCLOSURE SPECIFICATION
914mm x 610mm x 200mm or 300mm
2.0mm 316L, (1.4404) stainless steel or mild steel
2.5mm 316L, (1.4404) stainless steel or mild steel
Stainless steel – electropolished
Mild steel – Powder coated RAL 7032
31Kg and 34Kg
Fully detachable hinged cover with captive M6 stainless
steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Optional earth stud welded to gland plate
Padlockable hasp
Via gland plates 1-4 or direct through body
External lugs with 10mm clearance holes
WDU 2.5
5x172
7x112
T3,T4,T5,T6
HAZARDOUS AREA SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material box
Material gland plate
Finish
Zones 0,1,2,21,22
Product Code (150mm deep)
Product Code (200mm deep)
EEx e Terminal Box EEx e U Enclosure EEx ia Terminal Box EEx e Terminal Box EEx e U Enclosure EE ia Terminal Box
FXLS1030
FXLS1010D
FXLS1020D
FXLS1030D
FXLS1020
FXLS1010
FXLM1030
FXLM1010D
FXLM1020D
FXLM1030D
FXLM1020
FXLM1010
FXLS1031
FXLS1011D
FXLS1021D
FXLS1031D
FXLS1021
FXLS1011
FXLM1031
FXLM1011D
FXLM1021D
FXLM1031D
FXLM1021
FXLM1011
FXLS1032
FXLS1012D
FXLS1022D
FXLS1032D
FXLS1022
FXLS1012
FXLM1022
FXLM1032
FXLM1012D
FXLM1022D
FXLM1032D
FXLM1012
FXLS1013
FXLS1023
FXLS1033
FXLS1013D
FXLS1023D
FXLS1033D
FXLM1013
FXLM1023
FXLM1033
FXLM1013D
FXLM1023D
FXLM1033D
FXLS1014
FXLS1024
FXLS1034
FXLS1014D
FXLS1024D
FXLS1034D
FXLM1014
FXLM1024
FXLM1034
FXLM1014D
FXLM1024D
FXLM1034D
CES6
XL10MP
BP2
SSET
Optional Extras
6mm earthing stud welded to gland plate
Rain canopy
Document wallet
GPS6
XL10RC
XL10DW
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Material
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
GLAND PLATE OPTIONS
Number
Location
0
0
1
B
1
B
2
AB
2
AB
3
BCD
3
BCD
4
ABCD
4
ABCD
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, mild steel powdercoated
Brass padlock with 2 keys
10mm internal/external stainless steel earth stud
Product Code (150mm deep)
Product Code (200mm deep)
EEx e Terminal Box EEx e U Enclosure EEx ia Terminal Box EEx e Terminal Box EEx e U Enclosure EE ia Terminal Box
FXLS1130
FXLS1110D
FXLS1120D
FXLS1130D
FXLS1120
FXLS1110
FXLM1130
FXLM1110D
FXLM1120D
FXLM1130D
FXLM1120
FXLM1110
FXLS1131
FXLS1111D
FXLS1121D
FXLS1131D
FXLS1121
FXLS1111
FXLM1131
FXLM1111D
FXLM1121D
FXLM1131D
FXLM1121
FXLM1111
FXLS1132
FXLS1112D
FXLS1122D
FXLS1132D
FXLS1122
FXLS1112
FXLM1122
FXLM1132
FXLM1112D
FXLM1122D
FXLM1132D
FXLM1112
FXLS1113
FXLS1123
FXLS1133
FXLS1113D
FXLS1123D
FXLS1133D
FXLM1113
FXLM1123
FXLM1133
FXLM1113D
FXLM1123D
FXLM1133D
FXLS1114
FXLS1124
FXLS1134
FXLS1114D
FXLS1124D
FXLS1134D
FXLM1114
FXLM1124
FXLM1134
FXLM1114D
FXLM1124D
FXLM1134D
CES6
XL11MP
BP2
SSET
Optional Extras
6mm earthing stud welded to gland plate
Rain canopy
Document wallet
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
GPS6
XL11RC
XL11DW
28
EEx e and EEx i Terminal Boxes - Stainless and Mild Steel
Type FXLX - Extra Large Enclosures to 2000mm x 1250mm x 600mm
EEx e II and EE x ia IIC
Zones 0,1,2,21,22
T3,T4,T5,T6
Group II Cat 1,2
ATEX/GOST/UL
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5(+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66,67 to EN60529:1992
Maximum 100 Watts. Except for dust applications
where the maximum is 50 Watts
ENCLOSURE SPECIFICATION
Dimensions
Material box
Material gland plate
Finish
Weight empty
Cover fixing
Gasket
Earthing
Security
Entries
Mounting
2000mm max x 1250mm max x 600mm max
2.0mm 316L, (1.4404) stainless steel or mild steel
2.5mm 316L, (1.4404) stainless steel or mild steel
Stainless steel – electropolished
Mild steel – Powder coated RAL 7032
36Kg and 39Kg
Fully detachable hinged cover with captive M6 stainless
steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Optional earth stud welded to gland plate
Padlockable hasp
Via gland plates 1-4 or direct through body
External lugs with 10mm clearance holes
Return flange sealing
All Dimensions in mm
ORDERING INFORMATION
These enclosures are made to order and can be any size up to the
maximum dimensions given. Specification to be agreed between the
customer and Walsall sales.
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, mild steel powdercoated
Brass padlock with 2 keys
6mm eathing stud welded to gland plate
Rain canopy
Document wallet
10mm internal/external stainless steel earth stud
29
CES6
XLXMP
BP2
GPS6
XLXRC
XLXDW
SSET
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
High speed fully automatic cutting station
producing stainless steel enclosures.
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
30
EEx e and EEx i Terminal Boxes - Stainless and Mild Steel
Type XL1 - 229mm x 152mm x 130mm
PART 1.3
XL RANGE
EEx e II and EE x ia IIC
Zones 0,1,2,21,22
T3,T4,T5,T6
Group II Cat 1,2
ATEX/GOST/UL
HAZARDOUS AREA SPECIFICATION
Medium to large EEx e and EEx i approved terminal boxes
with edge sealing. There is an option of up to 4 gland plates.
The cover is detachable and hinged. The enclosure is fabricated
from electroplated stainless steel and powder coated mild steel.
The terminal boxes have Ingress Protection to IP66, 67, 68 and
have been deluge tested to DT501 99.
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
Type XL1 – 229mm x 152mm x130mm
Page 32
Type XL2 – 260mm x 260mm x 150mm or 200mm
Page 33
ENCLOSURE SPECIFICATION
Dimensions
Material box
Material gland plate
Finish
Type XL3 – 306mm x 306mm x 150mm or 200mm
Page 34
Type XL4 – 380mm x 260mm x 150mm or 200mm
Page 35
Type XL5 – 458mm x 382mm x 150mm or 200mm
Page 36
Type XL6 – 480mm x 480mm x 150mm or200mm
Page 37
Weight empty
Cover fixing
Type XL7 – 500mm x 350mm x 150mm or 200mm
Page 38
Gasket
Type XL8 – 620mm x 450mm x 150mm or 200mm
Page 39
Earthing
Type XL9 – 762mm x 508mm x 150mm or 200mm
Page 40
Type XL10 – 914mm x 610mm x 200mm or 300mm Page 41
Type XL11 – 1177mm x 777mm x 210mm or 300mm Page 42
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5(+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66,67 and 68 to EN60529:1992
Deluge test DT501 99
Maximum 15 Watts. Except for dust applications
where the maximum is 7.5 Watts
Security
Entries
Mounting
229mm x 152mm x 130mm
1.5mm 316L, (1.4404) stainless steel or mild steel
2.5mm 316L, (1.4404) stainless steel or mild steel
Stainless steel – electropolished
Mild steel – Powder coated RAL 7032
3.4Kg
Fully detachable hinged cover with captive M6 stainless
steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Optional earth stud welded to gland plate
Padlockable hasp
Via gland plates 1-4 or direct through body
External lugs with 10mm clearance holes
Edge sealing
All Dimensions in mm
Type XLX – 2000mm max x 1250mm max x 600mm max
Page 43
CUSTOMISING
As a vertically integrated manufacturer Walsall can customise
the XL range at each stage of the manufacturing process to
meet individual customer requirements
A GUIDE TO PHYSICAL TERMINAL CAPACITY
Verticle Rail
Horizontal Rail
WDU 2.5
1x35
1x20
WDU 4
1x29
1x16
20
6
6
25
3
3
32
2
2
* More entries are available if direct entry is used
ORDERING INFORMATION
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Gland Plate options
Number
0
0
1
1
2
2
3
3
4
4
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, mild steel powdercoated
Brass padlock with 2 keys
10mm internal/external stainless steel earth stud
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Gland Size mm
Side A + B
Side C + D
WDU 10
1x16
1x9
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Material
31
A GUIDE TO ENTRY CAPACITY FOR GLAND PLATES*
WDU 6
1x21
1x12
Location
B
B
AB
AB
BCD
BCD
ABCD
ABCD
CES6
XL1MP
BP2
SSET
EEx e Terminal Box
XLS110
XLM110
XLS111
XLM111
XLS112
XLM112
XLS113
XLM113
XLS114
XLM114
Product Codes
EEx e U Component Approved
XLS120
XLM120
XLS121
XLM121
XLS122
XLM122
XLS123
XLM123
XLS124
XLM124
Optional Extras
6mm earthing stud welded to gland plate
Rain canopy
Document wallet
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
EEx ia Terminal Box
XLS130
XLM130
XLS131
XLM131
XLS132
XLM132
XLS133
XLM133
XLS134
XLM134
GPS6
XL1RC
XL1DW
32
EEx e and EEx i Terminal Boxes - Stainless and Mild Steel
Type XL2 - 260mm x 260mm x 150mm or 200mm
EEx e II and EE x ia IIC
Zones 0,1,2,21,22
T3,T4,T5,T6
Group II Cat 1,2
EEx e and EEx i Terminal Boxes - Stainless and Mild Steel
Type XL3 - 306mm x 306mm x 150mm or 200mm
ATEX/GOST/UL
EEx e II and EE x ia IIC
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
Weight empty
Cover fixing
Gasket
Earthing
Security
Entries
Mounting
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5(+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66,67 and 68 to EN60529:1992
Deluge test DT501 99
Maximum 15 Watts. Except for dust applications
where the maximum is 7.5 Watts
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
A GUIDE TO PHYSICAL TERMINAL CAPACITY
Verticle Rails
Horizontal Rails
WDU 4
2x34
2x34
WDU 6
2x25
2x25
Dimensions
Material box
Material gland plate
Finish
Weight empty
Cover fixing
Gasket
Earthing
Security
Entries
Mounting
Edge sealing
All Dimensions in mm
A GUIDE TO ENTRY CAPACITY FOR GLAND PLATES*
WDU 10
2x20
2x20
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Enclosure Size
Gland Size mm
Side A+B
Side C+D
20
17
11
XL2
25
11
6
32
5
2
20
28
16
306mm x 306mm x 150mm or 200mm
1.5mm 316L, (1.4404) stainless steel or mild steel
2.5mm 316L, (1.4404) stainless steel or mild steel
Stainless steel – electropolished
Mild steel – Powder coated RAL 7032
6.5Kg and 7.0Kg
Fully detachable hinged cover with captive M6 stainless
steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Optional earth stud welded to gland plate
Padlockable hasp
Via gland plates 1-4 or direct through body
External lugs with 10mm clearance holes
A GUIDE TO TERMINAL CAPACITY (WDU type)
XL2D
25
15
9
32
11
8
ORDERING INFORMATION
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Verticle Rails
Horizontal Rails
WDU 2.5
2x51
2x51
WDU 4
2x42
2x42
WDU 6
2x31
2x31
Edge sealing
All Dimensions in mm
A GUIDE TO ENTRY CAPACITY FOR GLAND PLATES*
WDU 10
2x24
2x24
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Enclosure Size
Gland Size mm
Side A+B
Side C+D
20
21
15
XL3
25
12
9
32
6
4
20
32
23
XL3D
25
18
12
32
12
9
* More entries are available if direct entry is used
ORDERING INFORMATION
Gland Plate options
Number
Location
0
0
1
B
1
B
2
AB
2
AB
3
BCD
3
BCD
4
ABCD
4
ABCD
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, mild steel powdercoated
Brass padlock with 2 keys
10mm internal/external stainless steel earth stud
33
ATEX/GOST/UL
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5(+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66,67 and 68 to EN60529:1992
Deluge test DT501 99
Maximum 21 Watts. Except for dust applications
where the maximum is 10.5 Watts
* More entries are available if direct entry is used
Material
Group II Cat 1,2
ENCLOSURE SPECIFICATION
260mm x 260mm x 150mm or 200mm
1.5mm 316L, (1.4404) stainless steel or mild steel
2.5mm 316L, (1.4404) stainless steel or mild steel
Stainless steel – electropolished
Mild steel – Powder coated RAL 7032
5.5Kg and 6Kg
Fully detachable hinged cover with captive M6 stainless
steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Optional earth stud welded to gland plate
Padlockable hasp
Via gland plates 1-4 or direct through body
External lugs with 10mm clearance holes
WDU 2.5
2x42
2x42
T3,T4,T5,T6
HAZARDOUS AREA SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material box
Material gland plate
Finish
Zones 0,1,2,21,22
Product Code (150mm deep)
Product Code (200mm deep)
EEx e Terminal Box EEx e U Enclosure EEx ia Terminal Box EEx e Terminal Box EEx e U Enclosure EE ia Terminal Box
XLS230
XLS210D
XLS220D
XLS230D
XLS220
XLS210
XLM230
XLM210D
XLM220D
XLM230D
XLM220
XLM210
XLS231
XLS211D
XLS221D
XLS231D
XLS221
XLS211
XLM231
XLM211D
XLM221D
XLM231D
XLM221
XLM211
XLS232
XLS212D
XLS222D
XLS232D
XLS222
XLS212
XLM222
XLM232
XLM212D
XLM222D
XLM232D
XLM212
XLS213
XLS223
XLS233
XLS213D
XLS223D
XLS233D
XLM213
XLM223
XLM233
XLM213D
XLM223D
XLM233D
XLS214
XLS224
XLS234
XLS214D
XLS224D
XLS234D
XLM214
XLM224
XLM234
XLM214D
XLM224D
XLM234D
CES6
XL2MP
BP2
SSET
Optional Extras
6mm earthing stud welded to gland plate
Rain canopy
Document wallet
GPS6
XL2RC
XL2DW
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Material
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Gland Plate options
Number
Location
0
0
1
B
1
B
2
AB
2
AB
3
BCD
3
BCD
4
ABCD
4
ABCD
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, mild steel powdercoated
Brass padlock with 2 keys
10mm internal/external stainless steel earth stud
Product Code (150mm deep)
Product Code (200mm deep)
EEx e Terminal Box EEx e U Enclosure EEx ia Terminal Box EEx e Terminal Box EEx e U Enclosure EE ia Terminal Box
XLS330
XLS310D
XLS320D
XLS330D
XLS320
XLS310
XLM330
XLM310D
XLM320D
XLM330D
XLM320
XLM310
XLS331
XLS311D
XLS321D
XLS331D
XLS321
XLS311
XLM331
XLM311D
XLM321D
XLM331D
XLM321
XLM311
XLS332
XLS312D
XLS322D
XLS332D
XLS322
XLS312
XLM322
XLM332
XLM312D
XLM322D
XLM332D
XLM312
XLS313
XLS323
XLS333
XLS313D
XLS323D
XLS333D
XLM313
XLM323
XLM333
XLM313D
XLM323D
XLM333D
XLS314
XLS324
XLS334
XLS314D
XLS324D
XLS334D
XLM314
XLM324
XLM334
XLM314D
XLM324D
XLM334D
CES6
XL3MP
BP2
SSET
Optional Extras
6mm earthing stud welded to gland plate
Rain canopy
Document wallet
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
GPS6
XL3RC
XL3DW
34
EEx e and EEx i Terminal Boxes - Stainless and Mild Steel
Type XL4 - 380mm x 260mm x 150mm or 200mm
EEx e II and EE x ia IIC
Zones 0,1,2,21,22
T3,T4,T5,T6
Group II Cat 1,2
EEx e and EEx i Terminal Boxes - Stainless and Mild Steel
Type XL5 - 458mm x 382mm x 150mm or 200mm
ATEX/GOST/UL
EEx e II and EE x ia IIC
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
Weight empty
Cover fixing
Gasket
Earthing
Security
Entries
Mounting
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5(+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66,67 and 68 to EN60529:1992
Deluge test DT501 99
Maximum 21 Watts. Except for dust applications
where the maximum is 10.5 Watts
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
A GUIDE TO PHYSICAL TERMINAL CAPACITY
Verticle Rails
Horizontal Rails
WDU 4
2x49
2x35
WDU 6
2x36
2x26
Dimensions
Material box
Material gland plate
Finish
Weight empty
Cover fixing
Gasket
Earthing
Security
Entries
Mounting
Edge sealing
All Dimensions in mm
A GUIDE TO ENTRY CAPACITY FOR GLAND PLATES*
WDU 10
2x29
2x20
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Enclosure Size
Gland Size mm
Side A+B
Side C+D
20
17
18
XL4
25
10
12
32
5
6
20
27
28
458mm x 382mm x 150mm or 200mm
1.5mm 316L, (1.4404) stainless steel or mild steel
2.5mm 316L, (1.4404) stainless steel or mild steel
Stainless steel – electropolished
Mild steel – Powder coated RAL 7032
10Kg and 11Kg
Fully detachable hinged cover with captive M6 stainless
steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Optional earth stud welded to gland plate
Padlockable hasp
Via gland plates 1-4 or direct through body
External lugs with 10mm clearance holes
A GUIDE TO PHYSICAL TERMINAL CAPACITY
XL4D
25
15
15
32
11
11
ORDERING INFORMATION
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Verticle Rails
Horizontal Rails
WDU 2.5
3x81
3x66
WDU 4
3x67
3x55
WDU 6
3x50
3x40
Edge sealing
All Dimensions in mm
A GUIDE TO ENTRY CAPACITY FOR GLAND PLATES*
WDU 10
3x39
3x33
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Enclosure Size
Gland Size mm
Side A+B
Side C+D
20
27
27
XL5
25
17
17
32
9
9
20
40
40
XL5D
25
24
24
32
17
17
* More entries are available if direct entry is used
ORDERING INFORMATION
GLAND PLATE OPTIONS
Number
Location
0
0
1
B
1
B
2
AB
2
AB
3
BCD
3
BCD
4
ABCD
4
ABCD
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, mild steel powdercoated
Brass padlock with 2 keys
10mm internal/external stainless steel earth stud
35
ATEX/GOST/UL
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5(+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66,67 and 68 to EN60529:1992
Deluge test DT501 99
Maximum 29 Watts. Except for dust applications
where the maximum is 14.5 Watts
* More entries are available if direct entry is used
Material
Group II Cat 1,2
ENCLOSURE SPECIFICATION
380mm x 260mm x 150mm or 200mm
1.5mm 316L, (1.4404) stainless steel or mild steel
2.5mm 316L, (1.4404) stainless steel or mild steel
Stainless steel – electropolished
Mild steel – Powder coated RAL 7032
6.5Kg and 7.0Kg
Fully detachable hinged cover with captive M6 stainless
steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Optional earth stud welded to gland plate
Padlockable hasp
Via gland plates 1-4 or direct through body
External lugs with 10mm clearance holes
WDU 2.5
2x60
2x43
T3,T4,T5,T6
HAZARDOUS AREA SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material box
Material gland plate
Finish
Zones 0,1,2,21,22
Product Code (150mm deep)
Product Code (200mm deep)
EEx e Terminal Box EEx e U Enclosure EEx ia Terminal Box EEx e Terminal Box EEx e U Enclosure EE ia Terminal Box
XLS430
XLS410D
XLS420D
XLS430D
XLS420
XLS410
XLM430
XLM410D
XLM420D
XLM430D
XLM420
XLM410
XLS431
XLS411D
XLS421D
XLS431D
XLS421
XLS411
XLM431
XLM411D
XLM421D
XLM431D
XLM421
XLM411
XLS432
XLS412D
XLS422D
XLS432D
XLS422
XLS412
XLM422
XLM432
XLM412D
XLM422D
XLM432D
XLM412
XLS413
XLS423
XLS433
XLS413D
XLS423D
XLS433D
XLM413
XLM423
XLM433
XLM413D
XLM423D
XLM433D
XLS414
XLS424
XLS434
XLS414D
XLS424D
XLS434D
XLM414
XLM424
XLM434
XLM414D
XLM424D
XLM434D
CES6
XL4MP
BP2
SSET
Optional Extras
6mm earthing stud welded to gland plate
Rain canopy
Document wallet
GPS6
XL4RC
XL4DW
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Material
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
GLAND PLATE OPTIONS
Number
Location
0
0
1
B
1
B
2
AB
2
AB
3
BCD
3
BCD
4
ABCD
4
ABCD
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, mild steel powdercoated
Brass padlock with 2 keys
10mm internal/external stainless steel earth stud
Product Code (150mm deep)
Product Code (200mm deep)
EEx e Terminal Box EEx e U Enclosure EEx ia Terminal Box EEx e Terminal Box EEx e U Enclosure EE ia Terminal Box
XLS530
XLS510D
XLS520D
XLS530D
XLS520
XLS510
XLM530
XLM510D
XLM520D
XLM530D
XLM520
XLM510
XLS531
XLS511D
XLS521D
XLS531D
XLS521
XLS511
XLM531
XLM511D
XLM521D
XLM531D
XLM521
XLM511
XLS532
XLS512D
XLS522D
XLS532D
XLS522
XLS512
XLM522
XLM532
XLM512D
XLM522D
XLM532D
XLM512
XLS513
XLS523
XLS533
XLS513D
XLS523D
XLS533D
XLM513
XLM523
XLM533
XLM513D
XLM523D
XLM533D
XLS514
XLS524
XLS534
XLS514D
XLS524D
XLS534D
XLM514
XLM524
XLM534
XLM514D
XLM524D
XLM534D
CES6
XL5MP
BP2
SSET
Optional Extras
6mm earthing stud welded to gland plate
Rain canopy
Document wallet
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
GPS6
XL5RC
XL5DW
36
EEx e and EEx i Terminal Boxes - Stainless and Mild Steel
Type XL6 - 480mm x 480mm x 150mm or 200mm
EEx e II and EE x ia IIC
Zones 0,1,2,21,22
T3,T4,T5,T6
Group II Cat 1,2
EEx e and EEx i Terminal Boxes - Stainless and Mild Steel
Type XL7 - 500mm x 350mm x 150mm or 200mm
ATEX/GOST/UL
EEx e II and EE x ia IIC
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
Weight empty
Cover fixing
Gasket
Earthing
Security
Entries
Mounting
Verticle Rails
Horizontal Rails
T3,T4,T5,T6
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5(+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66,67 and 68 to EN60529:1992
Deluge test DT501 99
Maximum 30 Watts. Except for dust applications
where the maximum is 15 Watts
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5(+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66,67 and 68 to EN60529:1992
Deluge test DT501 99
Maximum 21 Watts. Except for dust applications
where the maximum is 10.5 Watts
A GUIDE TO PHYSICAL TERMINAL CAPACITY
WDU 2.5
WDU 4
WDU 6
4x86
4x71
4x53
4x86
4x71
4x53
WDU 10
4x42
4x42
Dimensions
Material box
Material gland plate
Finish
Weight empty
Cover fixing
Gasket
Earthing
Security
Entries
Mounting
Edge sealing
All Dimensions in mm
A GUIDE TO ENTRY CAPACITY FOR GLAND PLATES*
Enclosure Size
XL6
XL6D
Gland Size mm
20
25
32
20
25
Side A+B
36
22
11
52
33
Side C+D
29
18
9
44
27
500mm x 350mm x 150mm or 200mm
1.5mm 316L, (1.4404) stainless steel or mild steel
2.5mm 316L, (1.4404) stainless steel or mild steel
Stainless steel – electropolished
Mild steel – Powder coated RAL 7032
10.5Kg and 11Kg
Fully detachable hinged cover with captive M6 stainless
steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Optional earth stud welded to gland plate
Padlockable hasp
Via gland plates 1-4 or direct through body
External lugs with 10mm clearance holes
A GUIDE TO PHYSICAL TERMINAL CAPACITY
32
23
18
Verticle Rails
Horizontal Rails
WDU 2.5
3x90
4x60
WDU 4
3x74
4x49
WDU 6
3x55
4x36
ORDERING INFORMATION
Edge sealing
All Dimensions in mm
A GUIDE TO ENTRY CAPACITY FOR GLAND PLATES*
WDU 10
3x44
4x29
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
* More entries are available if direct entry is used
Enclosure Size
Gland Size mm
Side A+B
Side C+D
20
24
24
XL7
25
16
16
32
8
8
20
36
36
XL7D
25
21
21
32
15
15
* More entries are available if direct entry is used
ORDERING INFORMATION
GLAND PLATE OPTIONS
Number
Location
0
0
1
B
1
B
2
AB
2
AB
3
BCD
3
BCD
4
ABCD
4
ABCD
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, mild steel powdercoated
Brass padlock with 2 keys
10mm internal/external stainless steel earth stud
37
ATEX/GOST/UL
ENCLOSURE SPECIFICATION
480mm x 480mm x 150mm or 200mm
1.5mm 316L, (1.4404) stainless steel or mild steel
2.5mm 316L, (1.4404) stainless steel or mild steel
Stainless steel – electropolished
Mild steel – Powder coated RAL 7032
10.4Kg and 11Kg
Fully detachable hinged cover with captive M6 stainless
steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Optional earth stud welded to gland plate
Padlockable hasp
Via gland plates 1-4 or direct through body
External lugs with 10mm clearance holes
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Material
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Group II Cat 1,2
HAZARDOUS AREA SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material box
Material gland plate
Finish
Zones 0,1,2,21,22
Product Code (150mm deep)
Product Code (200mm deep)
EEx e Terminal Box EEx e U Enclosure EEx ia Terminal Box EEx e Terminal Box EEx e U Enclosure EE ia Terminal Box
XLS630
XLS610D
XLS620D
XLS630D
XLS620
XLS610
XLM630
XLM610D
XLM620D
XLM630D
XLM620
XLM610
XLS631
XLS611D
XLS621D
XLS631D
XLS621
XLS611
XLM631
XLM611D
XLM621D
XLM631D
XLM621
XLM611
XLS632
XLS612D
XLS622D
XLS632D
XLS622
XLS612
XLM622
XLM632
XLM612D
XLM622D
XLM632D
XLM612
XLS613
XLS623
XLS633
XLS613D
XLS623D
XLS633D
XLM613
XLM623
XLM633
XLM613D
XLM623D
XLM633D
XLS614
XLS624
XLS634
XLS614D
XLS624D
XLS634D
XLM614
XLM624
XLM634
XLM614D
XLM624D
XLM634D
CES6
XL6MP
BP2
SSET
Optional Extras
6mm earthing stud welded to gland plate
Rain canopy
Document wallet
GPS6
XL6RC
XL6DW
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Material
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
GLAND PLATE OPTIONS
Number
Location
0
0
1
B
1
B
2
AB
2
AB
3
BCD
3
BCD
4
ABCD
4
ABCD
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, mild steel powdercoated
Brass padlock with 2 keys
10mm internal/external stainless steel earth stud
Product Code (150mm deep)
Product Code (200mm deep)
EEx e Terminal Box EEx e U Enclosure EEx ia Terminal Box EEx e Terminal Box EEx e U Enclosure EE ia Terminal Box
XLS730
XLS710D
XLS720D
XLS730D
XLS720
XLS710
XLM730
XLM710D
XLM720D
XLM730D
XLM720
XLM710
XLS731
XLS711D
XLS721D
XLS731D
XLS721
XLS711
XLM731
XLM711D
XLM721D
XLM731D
XLM721
XLM711
XLS732
XLS712D
XLS722D
XLS732D
XLS722
XLS712
XLM722
XLM732
XLM712D
XLM722D
XLM732D
XLM712
XLS713
XLS723
XLS733
XLS713D
XLS723D
XLS733D
XLM713
XLM723
XLM733
XLM713D
XLM723D
XLM733D
XLS714
XLS724
XLS734
XLS714D
XLS724D
XLS734D
XLM714
XLM724
XLM734
XLM714D
XLM724D
XLM734D
CES6
XL7MP
BP2
SSET
Optional Extras
6mm earthing stud welded to gland plate
Rain canopy
Document wallet
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
GPS6
XL7RC
XL7DW
38
EEx e and EEx i Terminal Boxes - Stainless and Mild Steel
Type XL8 - 620mm x 450mm x 150mm or 200mm
EEx e II and EE x ia IIC
Zones 0,1,2,21,22
T3,T4,T5,T6
Group II Cat 1,2
EEx e and EEx i Terminal Boxes - Stainless and Mild Steel
Type XL9 - 762mm x 508mm x 150mm or 200mm
ATEX/GOST/UL
EEx e II and EE x ia IIC
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
Weight empty
Cover fixing
Gasket
Earthing
Security
Entries
Mounting
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5(+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66,67 and 68 to EN60529:1992
Deluge test DT501 99
Maximum 41.7 Watts. Except for dust applications
where the maximum is 20.5 Watts
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
A GUIDE TO PHYSICAL TERMINAL CAPACITY
Verticle Rails
Horizontal Rails
WDU 4
5x66
3x94
WDU 6
5x49
3x70
Dimensions
Material box
Material gland plate
Finish
Weight empty
Cover fixing
Gasket
Earthing
Security
Entries
Mounting
Edge sealing
All Dimensions in mm
A GUIDE TO ENTRY CAPACITY FOR GLAND PLATES*
WDU 10
5x39
3x56
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Enclosure Size
Gland Size mm
Side A+B
Side C+D
20
29
38
XL8
25
18
24
32
9
12
20
44
56
762mm x 508mm x 150mm or 200mm
2.0mm 316L, (1.4404) stainless steel or mild steel
2.5mm 316L, (1.4404) stainless steel or mild steel
Stainless steel – electropolished
Mild steel – Powder coated RAL 7032
22Kg and 24Kg
Fully detachable hinged cover with captive M6 stainless
steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Optional earth stud welded to gland plate
Padlockable hasp
Via gland plates 1-4 or direct through body
External lugs with 10mm clearance holes
A GUIDE TO PHYSICAL TERMINAL CAPACITY
XL8D
25
27
36
32
18
24
ORDERING INFORMATION
Verticle Rails
Horizontal Rails
WDU 2.5
4x142
6x91
WDU 4
4x118
6x76
WDU 6
4x88
6x56
Edge sealing
All Dimensions in mm
A GUIDE TO ENTRY CAPACITY FOR GLAND PLATES*
WDU 10
4x70
6x44
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Enclosure Size
Gland Size mm
Side A+B
Side C+D
20
38
38
XL9
25
24
24
32
12
12
20
56
56
XL9D
25
36
36
32
24
24
* More entries are available if direct entry is used
ORDERING INFORMATION
GLAND PLATE OPTIONS
Number
Location
0
0
1
B
1
B
2
AB
2
AB
3
BCD
3
BCD
4
ABCD
4
ABCD
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, mild steel powdercoated
Brass padlock with 2 keys
10mm internal/external stainless steel earth stud
39
ATEX/GOST/UL
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5(+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66,67 and 68 to EN60529:1992
Deluge test DT501 99
Maximum 41.7 Watts. Except for dust applications
where the maximum is 20.5 Watts
* More entries are available if direct entry is used
Material
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Group II Cat 1,2
ENCLOSURE SPECIFICATION
620mm x 450mm x 150mm or 200mm
2.0mm 316L, (1.4404) stainless steel or mild steel
2.5mm 316L, (1.4404) stainless steel or mild steel
Stainless steel – electropolished
Mild steel – Powder coated RAL 7032
17Kg and 17.5Kg
Fully detachable hinged cover with captive M6 stainless
steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Optional earth stud welded to gland plate
Padlockable hasp
Via gland plates 1-4 or direct through body
External lugs with 10mm clearance holes
WDU 2.5
5x80
3x114
T3,T4,T5,T6
HAZARDOUS AREA SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material box
Material gland plate
Finish
Zones 0,1,2,21,22
Product Code (150mm deep)
Product Code (200mm deep)
EEx e Terminal Box EEx e U Enclosure EEx ia Terminal Box EEx e Terminal Box EEx e U Enclosure EE ia Terminal Box
XLS830
XLS810D
XLS820D
XLS830D
XLS820
XLS810
XLM830
XLM810D
XLM820D
XLM830D
XLM820
XLM810
XLS831
XLS811D
XLS821D
XLS831D
XLS821
XLS811
XLM831
XLM811D
XLM821D
XLM831D
XLM821
XLM811
XLS832
XLS812D
XLS822D
XLS832D
XLS822
XLS812
XLM822
XLM832
XLM812D
XLM822D
XLM832D
XLM812
XLS813
XLS823
XLS833
XLS813D
XLS823D
XLS833D
XLM813
XLM823
XLM833
XLM813D
XLM823D
XLM833D
XLS814
XLS824
XLS834
XLS814D
XLS824D
XLS834D
XLM814
XLM824
XLM834
XLM814D
XLM824D
XLM834D
CES6
XL8MP
BP2
SSET
Optional Extras
6mm earthing stud welded to gland plate
Rain canopy
Document wallet
GPS6
XL8RC
XL8DW
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Material
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
GLAND PLATE OPTIONS
Number
Location
0
0
1
B
1
B
2
AB
2
AB
3
BCD
3
BCD
4
ABCD
4
ABCD
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, mild steel powdercoated
Brass padlock with 2 keys
10mm internal/external stainless steel earth stud
Product Code (150mm deep)
Product Code (200mm deep)
EEx e Terminal Box EEx e U Enclosure EEx ia Terminal Box EEx e Terminal Box EEx e U Enclosure EE ia Terminal Box
XLS930
XLS910D
XLS920D
XLS930D
XLS920
XLS910
XLM930
XLM910D
XLM920D
XLM930D
XLM920
XLM910
XLS931
XLS911D
XLS921D
XLS931D
XLS921
XLS911
XLM931
XLM911D
XLM921D
XLM931D
XLM921
XLM911
XLS932
XLS912D
XLS922D
XLS932D
XLS922
XLS912
XLM922
XLM932
XLM912D
XLM922D
XLM932D
XLM912
XLS913
XLS923
XLS933
XLS913D
XLS923D
XLS933D
XLM913
XLM923
XLM933
XLM913D
XLM923D
XLM933D
XLS914
XLS924
XLS934
XLS914D
XLS924D
XLS934D
XLM914
XLM924
XLM934
XLM914D
XLM924D
XLM934D
CES6
XL9MP
BP2
SSET
Optional Extras
6mm earthing stud welded to gland plate
Rain canopy
Document wallet
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
GPS6
XL9RC
XL9DW
40
EEx e and EEx i Terminal Boxes - Stainless and Mild Steel
Type XL10 - 914mm x 610mm x 200mm or 300mm
EEx e II and EE x ia IIC
Zones 0,1,2,21,22
T3,T4,T5,T6
Group II Cat 1,2
EEx e and EEx i Terminal Boxes - Stainless and Mild Steel
Type XL11 - 1177mm x 777mm x 210mm or 300mm
ATEX/GOST/UL
EEx e II and EE x ia IIC
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
Weight empty
Cover fixing
Gasket
Earthing
Security
Entries
Mounting
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5(+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66,67 and 68 to EN60529:1992
Deluge test DT501 99
Maximum 93.4 Watts. Except for dust applications
where the maximum is 46 Watts
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
A GUIDE TO PHYSICAL TERMINAL CAPACITY
Verticle Rails
Horizontal Rails
WDU 4
5x143
7x93
WDU 6
5x127
7x69
Dimensions
Material box
Material gland plate
Finish
Weight empty
Cover fixing
Gasket
Earthing
Security
Entries
Mounting
Edge sealing
All Dimensions in mm
A GUIDE TO ENTRY CAPACITY FOR GLAND PLATES*
WDU 10
5x85
7x55
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Enclosure Size
Gland Size mm
Side A+B
Side C+D
20
72
72
XL10
25
42
42
32
30
30
20
126
126
1177mm x 777mm x 210mm or 300mm
2.0mm 316L, (1.4404) stainless steel or mild steel
2.5mm 316L, (1.4404) stainless steel or mild steel
Stainless steel – electropolished
Mild steel – Powder coated RAL 7032
36Kg and 39Kg
Fully detachable hinged cover with captive M6 stainless
steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Optional earth stud welded to gland plate
Padlockable hasp
Via gland plates 1-4 or direct through body
External lugs with 10mm clearance holes
A GUIDE TO PHYSICAL TERMINAL CAPACITY
XL10D
25
84
84
32
50
50
ORDERING INFORMATION
Verticle Rails
Horizontal Rails
WDU 2.5
6x224
9x145
WDU 4
6x187
9x120
WDU 6
6x139
9x90
Edge sealing
All Dimensions in mm
A GUIDE TO ENTRY CAPACITY FOR GLAND PLATES*
WDU 10
6x111
9x71
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Enclosure Size
Gland Size mm
Side A+B
Side C+D
20
72
72
XL11
25
42
42
32
30
30
20
126
126
XL11D
25
84
84
32
50
50
* More entries are available if direct entry is used
ORDERING INFORMATION
GLAND PLATE OPTIONS
Number
Location
0
0
1
B
1
B
2
AB
2
AB
3
BCD
3
BCD
4
ABCD
4
ABCD
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, mild steel powdercoated
Brass padlock with 2 keys
10mm internal/external stainless steel earth stud
41
ATEX/GOST/UL
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5(+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66,67 and 68 to EN60529:1992
Deluge test DT501 99
Maximum 100 Watts. Except for dust applications
where the maximum is 50 Watts
* More entries are available if direct entry is used
Material
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Group II Cat 1,2
ENCLOSURE SPECIFICATION
914mm x 610mm x 200mm or 300mm
2.0mm 316L, (1.4404) stainless steel or mild steel
2.5mm 316L, (1.4404) stainless steel or mild steel
Stainless steel – electropolished
Mild steel – Powder coated RAL 7032
31Kg and 34Kg
Fully detachable hinged cover with captive M6 stainless
steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Optional earth stud welded to gland plate
Padlockable hasp
Via gland plates 1-4 or direct through body
External lugs with 10mm clearance holes
WDU 2.5
5x172
7x112
T3,T4,T5,T6
HAZARDOUS AREA SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material box
Material gland plate
Finish
Zones 0,1,2,21,22
Product Code (150mm deep)
Product Code (200mm deep)
EEx e Terminal Box EEx e U Enclosure EEx ia Terminal Box EEx e Terminal Box EEx e U Enclosure EE ia Terminal Box
XLS1030
XLS1010D
XLS1020D
XLS1030D
XLS1020
XLS1010
XLM1030
XLM1010D
XLM1020D
XLM1030D
XLM1020
XLM1010
XLS1031
XLS1011D
XLS1021D
XLS1031D
XLS1021
XLS1011
XLM1031
XLM1011D
XLM1021D
XLM1031D
XLM1021
XLM1011
XLS1032
XLS1012D
XLS1022D
XLS1032D
XLS1022
XLS1012
XLM1022
XLM1032
XLM1012D
XLM1022D
XLM1032D
XLM1012
XLS1013
XLS1023
XLS1033
XLS1013D
XLS1023D
XLS1033D
XLM1013
XLM1023
XLM1033
XLM1013D
XLM1023D
XLM1033D
XLS1014
XLS1024
XLS1034
XLS1014D
XLS1024D
XLS1034D
XLM1014
XLM1024
XLM1034
XLM1014D
XLM1024D
XLM1034D
CES6
XL10MP
BP2
SSET
Optional Extras
6mm earthing stud welded to gland plate
Rain canopy
Document wallet
GPS6
XL10RC
XL10DW
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Material
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
Stainless
Mild Steel
GLAND PLATE OPTIONS
Number
Location
0
0
1
B
1
B
2
AB
2
AB
3
BCD
3
BCD
4
ABCD
4
ABCD
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, mild steel powdercoated
Brass padlock with 2 keys
10mm internal/external stainless steel earth stud
Product Code (150mm deep)
Product Code (200mm deep)
EEx e Terminal Box EEx e U Enclosure EEx ia Terminal Box EEx e Terminal Box EEx e U Enclosure EE ia Terminal Box
XLS1130
XLS1110D
XLS1120D
XLS1130D
XLS1120
XLS1110
XLM1130
XLM1110D
XLM1120D
XLM1130D
XLM1120
XLM1110
XLS1131
XLS1111D
XLS1121D
XLS1131D
XLS1121
XLS1111
XLM1131
XLM1111D
XLM1121D
XLM1131D
XLM1121
XLM1111
XLS1132
XLS1112D
XLS1122D
XLS1132D
XLS1122
XLS1112
XLM1122
XLM1132
XLM1112D
XLM1122D
XLM1132D
XLM1112
XLS1113
XLS1123
XLS1133
XLS1113D
XLS1123D
XLS1133D
XLM1113
XLM1123
XLM1133
XLM1113D
XLM1123D
XLM1133D
XLS1114
XLS1124
XLS1134
XLS1114D
XLS1124D
XLS1134D
XLM1114
XLM1124
XLM1134
XLM1114D
XLM1124D
XLM1134D
CES6
XL11MP
BP2
SSET
Optional Extras
6mm earthing stud welded to gland plate
Rain canopy
Document wallet
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
GPS6
XL11RC
XL11DW
42
EEx e and EEx i Terminal Boxes - Stainless and Mild Steel
Type XLX - Extra Large Enclosures to 2000mm x 1250mm x 600mm
EEx e II and EE x ia IIC
Zones 0,1,2,21,22
T3,T4,T5,T6
Group II Cat 1,2
ATEX/GOST/UL
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5(+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66,67 and 68 to EN60529:1992
Deluge test DT501 99
Maximum 100 Watts. Except for dust applications
where the maximum is 50 Watts
ENCLOSURE SPECIFICATION
Dimensions
Material box
Material gland plate
Finish
Weight empty
Cover fixing
Gasket
Earthing
Security
Entries
Mounting
2000mm max x 1250mm max x 600mm max
2.0mm 316L, (1.4404) stainless steel or mild steel
2.5mm 316L, (1.4404) stainless steel or mild steel
Stainless steel – electropolished
Mild steel – Powder coated RAL 7032
36Kg and 39Kg
Fully detachable hinged cover with captive M6 stainless
steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Optional earth stud welded to gland plate
Padlockable hasp
Via gland plates 1-4 or direct through body
External lugs with 10mm clearance holes
Edge sealing
All Dimensions in mm
ORDERING INFORMATION
These enclosures are made to order and can be any size up to the
maximum dimensions given. Specification to be agreed between the
customer and Walsall sales.
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, mild steel powdercoated
Brass padlock with 2 keys
6mm eathing stud welded to gland plate
Rain canopy
Document wallet
10mm internal/external stainless steel earth stud
43
CES6
XLXMP
BP2
GPS6
XLXRC
XLXDW
SSET
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
44
High Voltage Terminal Box - Stainless Steel Enclosure
Type HVB - EEx e Terminal Box with High Voltage Terminals to 6.6kV
PART 1.4
HVB RANGE
EEx e II
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST/UL
HAZARDOUS AREA SPECIFICATION
High Voltage Terminal Box to 6.6kV manufactured from
fabricated stainless steel with electropolished finish. The
terminal boxes have Ingress Protection to IP66, 67 and 68
and have been deluge tested to DT501 99.
Type HVB3.3 – 977mm x 677mm x300mm
Page 46
Type HVB6.6 – 1250mm x 800mm x 300mm
Page 46
CUSTOMISING
As a vertically integrated manufacturer Walsall can customise
the HVB range at each stage of the manufacturing process to
meet individual customer requirements
Marking to 94/9/EC
Type of Protection
Temperature Class.
Area Classification
Certification No.
Ingress Protection
II 2 GD
EEx e II T6
-50˚C to +55˚C
Zones 1,2,21,22
Sira 00ATEX3206
IP66,67 68 to EN60529:1992
Deluge Test to DT501 99
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Weight
Cover Fixing
Gasket
Earthing
Security
Mounting
977mm x 677mm x 300mm
1250mm x 800mm x 300mm
2.0mm 316L (1.4404) Stainless Steel
Electro-polished
50 Kg
Fully detachable hinged cover with captive M6 stainless
steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta <-40˚C
10mm brass or stainless steel internal/external earth
Padlockable hasp
External lugs with 10mm
ENTRY SPECIFICATION
Entries direct into body or gland plates to customer specification
All Dimensions in mm
ELECTRICAL SPECIFICATION
Operating Voltage
Operating Current
6.6kV max
650 Amps max
Three equally spaced internal bus bars are mounted on insulators rated at 10kV.
The insulators are in turn installed on an epoxy glass laminate board that is fastened
onto mounting rails fixed to the standard enclosure fixing points. There are six
plastic cable support cleats mounted on GRP support rails for each bus bar
connection point.
ORDERING INFORMATION
Voltage Rating
3.3 kV
6.6 kV
45
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Product Code
HVB3.3
HVB6.6
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
46
EEx e and EEx i Terminal Boxes - Aluminium
Type AL1 - 110mm x 110mm x 65mm
PART 1.5
AL RANGE
EEx e II and EE x ia IIC
Zones 0,1,2,21,22
T3,T4,T5,T6
Group II Cat 1,2
ATEX/GOST/UL
HAZARDOUS AREA SPECIFICATION
Small EEx e and EEx i approved terminal boxes and
enclosures without gland plates, fabricated from powder
coated aluminum. The terminal boxes have ingress protection
to IP66/67.
Type AL1 – 110mm x 110mm x 65mm
Page 48
Type AL2 – 120mm x 120mm x 80mm
Page 49
Type AL3 – 150mm x 120mm x 80mm
Page 50
Type AL4 – 150mm x 150mm x 90mm
Page 51
Type AL5 – 190mm x 150mm x 90mm
Page 52
Type AL6 – 190mm x 190mm x 100mm
Page 53
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5(+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66/67 to EN60529:1992
Maximum 9 Watts. Except for dust applications
where the maximum is 4.5 Watts
Ingress protection
Power dissipation
ENCLOSURE SPECIFICATION
CUSTOMISING
As a vertically integrated manufacturer Walsall can customise
the AL range at each stage of the production process to
meet individual customer requirements
Dimensions
Material box
Finish
Weight empty
Cover fixing
Gasket
110mm x 110mm x 65mm
3.0mm Aluminium 1050A, H14
Powder coated RAL 7032
0.4Kg
Captive M6 stainless steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
6mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Direct through body
External lugs with 8mm clearance holes
DIN 20mm rail or mounting plate to suit
Earthing
Entries
External Mounting
Internal Mounting
All Dimensions in mm
A GUIDE TO PHYSICAL TERMINAL CAPACITY
Verticle Rail
Horizontal Rail
WDU 2.5
1x14
1x14
WDU 4
1x11
1x11
A GUIDE TO ENTRY CAPACITY
WDU 6
1x8
1x8
WDU 10
1x6
1x6
Gland Size mm
Side A + B
Side C + D
16
4
4
20
3
3
25
2
2
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
ORDERING INFORMATION
Material
Aluminium
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, aluminium
47
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
EEx e Terminal Box
AL11
EEx e U Component Approved Enclosure
AL12
EEx ia Terminal Box
AL13
CES6
AL1MP
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
48
EEx e and EEx i Terminal Boxes - Aluminium
Type AL2 - 120mm x 120mm x 80mm
EEx e II and EE x ia IIC
Zones 0,1,2,21,22
T3,T4,T5,T6
EEx e and EEx i Terminal Boxes - Aluminium
Type AL3 - 150mm x 120mm x 80mm
Group II Cat 1,2
ATEX/GOST/UL
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Entries
External Mounting
Internal Mounting
Group II Cat 1,2
Dimensions
Material box
Finish
Weight empty
Cover fixing
Gasket
150mm x 120mm x 80mm
3.0mm Aluminium 1050A, H14
Powder coated RAL 7032
0.5Kg
Captive M6 stainless steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50C
6mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Direct through body
External lugs with 8mm clearance holes
DIN 20mm rail or mounting plate to suit
Earthing
Entries
External Mounting
Internal Mounting
All Dimensions in mm
A GUIDE TO PHYSICAL TERMINAL CAPACITY
Verticle Rail
Horizontal Rail
WDU 2.5
1x16
1x16
WDU 4
1x13
1x13
All Dimensions in mm
A GUIDE TO ENTRY CAPACITY
WDU 6
1x9
1x9
WDU 10
1x7
1x7
Gland Size mm
Side A + B
Side C + D
20
6
6
A GUIDE TO PHYSICAL TERMINAL CAPACITY
25
3
3
32
2
2
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, aluminium
49
Verticle Rail
Horizontal Rail
WDU 2.5
1x22
1x16
WDU 4
1x18
1x13
A GUIDE TO ENTRY CAPACITY
WDU 6
1x13
1x9
WDU 10
1x10
1x7
Gland Size mm
Side A + B
Side C + D
20
8
6
25
4
3
32
2
2
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
ORDERING INFORMATION
Material
Aluminium
ATEX/GOST/UL
ENCLOSURE SPECIFICATION
120mm x 120mm x 80mm
3.0mm Aluminium 1050A, H14
Powder coated RAL 7032
0.45Kg
Captive M6 stainless steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
6mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Direct through body
External lugs with 8mm clearance holes
DIN 20mm rail or mounting plate to suit
Earthing
T3,T4,T5,T6
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5(+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66/67 to EN60529:1992
Maximum 9 Watts. Except for dust applications
where the maximum is 4.5 Watts.
Ingress protection
Power dissipation
ENCLOSURE SPECIFICATION
Dimensions
Material box
Finish
Weight empty
Cover fixing
Gasket
Zones 0,1,2,21,22
HAZARDOUS AREA SPECIFICATION
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5(+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66/67 to EN60529:1992
Maximum 9 watts. Except for dust applications
where the maximum is 4.5 Watts
Ingress protection
Power dissipation
EEx e II and EE x ia IIC
ORDERING INFORMATION
EEx e Terminal Box
AL21
EEx e U Component Approved Enclosure
AL22
EEx ia Terminal Box
AL23
CES6
AL2MP
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Material
Aluminium
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, aluminium
EEx e Terminal Box
AL31
EEx e U Component Approved Enclosure
AL32
EEx ia Terminal Box
AL33
CES6
AL3MP
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
50
EEx e and EEx i Terminal Boxes - Aluminium
Type AL4 - 150mm x 150mm x 90mm
EEx e II and EE x ia IIC
Zones 0,1,2,21,22
T3,T4,T5,T6
EEx e and EEx i Terminal Boxes - Aluminium
Type AL5 - 190mm x 150mm x 90mm
Group II Cat 1,2
ATEX/GOST/UL
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Entries
External Mounting
Internal Mounting
Group II Cat 1,2
Dimensions
Material box
Finish
Weight empty
Cover fixing
Gasket
190mm x 150mm x 90mm
3.0mm Aluminium 1050A, H14
Powder coated RAL 7032
0.7Kg
Captive M6 stainless steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
6mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Direct through body.
External lugs with 8mm clearance holes
DIN 20mm rail or mounting plate to suit
Earthing
Entries
External Mounting
Internal Mounting
All Dimensions in mm
A GUIDE TO PHYSICAL TERMINAL CAPACITY
Verticle Rail
Horizontal Rail
WDU 2.5
1x22
1x22
WDU 4
1x18
1x18
All Dimensions in mm
A GUIDE TO ENTRY CAPACITY
WDU 6
1x13
1x13
WDU 10
1x10
1x10
Gland Size mm
Side A + B
Side C + D
20
8
8
A GUIDE TO PHYSICAL TERMINAL CAPACITY
25
5
5
32
3
3
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, aluminium
51
Verticle Rail
Horizontal Rail
WDU 2.5
1x30
1x22
WDU 4
1x24
1x18
A GUIDE TO ENTRY CAPACITY
WDU 6
1x18
1x13
WDU 10
1x14
1x10
Gland Size mm
Side A + B
Side C + D
20
8
10
25
5
7
32
3
3
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
ORDERING INFORMATION
Material
Aluminium
ATEX/GOST/UL
ENCLOSURE SPECIFICATION
150mm x 150mm x 90mm
3.0mm Aluminium 1050A, H14
Powder coated RAL 7032
0.6Kg.
Captive M6 stainless steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
6mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Direct through body
External lugs with 8mm clearance holes
DIN 20mm rail or mounting plate to suit
Earthing
T3,T4,T5,T6
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5(+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66/67 to EN60529:1992
Maximum 9 Watts. Except for dust applications
where the maximum is 4.5 Watts
Ingress protection
Power dissipation
ENCLOSURE SPECIFICATION
Dimensions
Material box
Finish
Weight empty
Cover fixing
Gasket
Zones 0,1,2,21,22
HAZARDOUS AREA SPECIFICATION
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5(+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66/67 to EN60529:1992
Maximum 9 Watts. Except for dust applications
where the maximum is 4.5 Watts
Ingress protection
Power dissipation
EEx e II and EE x ia IIC
ORDERING INFORMATION
EEx e Terminal Box
AL41
EEx e U Component Approved Enclosure
AL42
EEx ia Terminal Box
AL43
CES6
AL4MP
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Material
Aluminium
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, aluminium
EEx e Junction Box
AL51
EEx e U Component Approved Enclosure
AL52
EEx ia Junction Box
AL53
CES6
AL5MP
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
52
EEx e and EEx i Terminal Boxes - Aluminium
Type AL6 - 190mm x 190mm x 100mm
EEx e II and EE x ia IIC
Zones 0,1,2,21,22
T3,T4,T5,T6
Group II Cat 1,2
ATEX/GOST/UL
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
II 2 GD,
II 1 GD T6,T5,T4,T3
EEx e II and EEx ia IIC
T6(-50˚C to +40˚C), T5(+55˚C), T4(+85˚C), T3(+120˚C)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99ATEX3199 and Sira 00ATEX3027U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66/67 to EN60529:1992
Maximum 9 watts. Except for dust applications
where the maximum is 4.5 Watts
Ingress protection
Power dissipation
ENCLOSURE SPECIFICATION
Dimensions
Material box
Finish
Weight empty
Cover fixing
Gasket
190mm x 190mm x 100mm
3.0mm Aluminium 1050A, H14
Powder coated RAL 7032
1.0Kg
Captive M6 stainless steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
6mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Direct through body
External lugs with 8mm clearance holes
DIN 20mm rail or mounting plate to suit
Earthing
Entries
External Mounting
Internal Mounting
All Dimensions in mm
A GUIDE TO PHYSICAL TERMINAL CAPACITY
Verticle Rail
Horizontal Rail
WDU 2.5
1x30
1x30
WDU 4
1x24
1x24
A GUIDE TO ENTRY CAPACITY
WDU 6
1x18
1x18
WDU 10
1x14
1x14
Gland Size mm
Side A + B
Side C + D
20
14
14
25
8
8
32
4
4
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
ORDERING INFORMATION
Material
Aluminium
Optional Extras
6mm earthing stud welded to cover
Equipment mounting plate, aluminium
53
EEx e Terminal Box
AL61
EEx e U Component Approved Enclosure
AL62
EEx ia Terminal Box
AL63
CES6
AL6MP
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
54
EEx e Junction Box With Pillar or MK Terminals - Glass Reinforced Polyester
Type GVU - 110mm x 110mm x 65mm
PART 1.6
GVU JUNCTION BOX
A small heavy duty GRP junction box with deep threaded
enteries designed to accommodate 4 + E pillar terminals or
5 + E MK type terminals. The boxes have ingress protection
to IP66.
EEx e II
Page 56
Type GVU/MK
110mm x 110mm x 90mm with MK terminals
Page 56
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
Type GVU/P
110mm x 110mm x 90mm with pillar terminals
Zones 1,2,21,22
II 2 GD
EEx e II T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
SIRA03ATEX3293
GOST ‘R’ POCC GB. гБ05.BO1131
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Weight
Cover fixing
Gasket
Mounting
110mm x 110mm x 65mm
Carbon loaded anti-static glass reinforced polyester UL94/V0
Moulded black
1.2 Kg
M6 allen head stainless steel screws
1.2 mm one piece solid nitrile rubber
Through 10mm holes moulded into base
ENTRY SPECIFICATION
1 x 20mm EEx e threaded hole at A,B,C and D as standard
All entries are fitted with EEx e stopping plugs as standard
25mm entries are available as an option
TERMINAL SPECIFICATION
Operating Voltage
Operating current
Terminal capacity
Pillar Type
420v
16amps
2
2.5mm
MK3/6 Type
420v
32amps
2
2.5mm
All Dimensions in mm
ORDERING INFORMATION
Enclosure Dimensions
110mm x 110mm x 65mm
110mm x 110mm x 65mm
55
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Terminal Type
Pillar
MK3/6
Number of Terminals
4+E
5+E
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Product Code
GVU/P
GVU/MK
56
EEx e and EEx i Terminal Boxes - Glass Reinforced Polyester
Type GL1 - 80mm x 75mm x 55mm
PART 1.7
GL RANGE
EEx e II and EE x ia IIC
Zones 0,1,2,21,22
T6
Group II Cat 1,2
ATEX/GOST/UL
HAZARDOUS AREA SPECIFICATION
Small to large EEx e and EEx i approved terminal boxes,
compression moulded from glass reinforced polyester.
The terminal boxes have Ingress Protection to IP66.
Type GL1 – 80mm x 75mm x 55mm
Page 58
Type GL2 – 110mm x 75mm x 55mm
Page 59
Type GL3 – 160mm x 75mm x 55mm
Page 60
Type GL4 – 190mm x 75mm x 55mm
Page 61
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
II 2 GD,
II 1 GD T6
EEx e II T6 and EEx ia IIC T6
-50ºC to +50ºC (T6), +55ºC (T5), +60ºC (T4)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99 ATEX 3200 and Sira 99 ATEX 3028U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66 to EN 60529:1992
Maximum 7.5 Watts at +40C and 1.6 Watts at +50˚C
Except for dust applications where the maxima
are 3.3 Watts at +40˚C and 0.8 Watts at +50˚C
ENCLOSURE SPECIFICATION
Type GL5 – 122mm x 120mm x 90mm
Page 62
Type GL6 – 220mm x 120mm x 90mm
Page 63
Type GL7 – 160mm x 160mm x 90mm
Page 64
Type GL8 – 260mm x 160mm x 90mm
Page 65
Type GL9 – 360mm x 160mm x 90mm
Page 66
Type GL10 – 560mm x 160mm x 90mm
Page 67
Type GL11 – 255mm x 250mm x 120mm
Page 68
Type GL12 – 400mm x 250mm x 120mm
Page 69
Type GL13 – 405mm x 400mm x 120mm
Page 70
Type GL14 – 405mm x 400mm x 165mm
Page 71
Dimensions
Material
Finish
Weight empty
Cover fixing
Gasket
Earthing
Entry
Mounting
80mm x 75mm x 55mm
Carbon loaded, anti-static glass reinforced polyester UL 94/V0
Moulded self colour black. Other colours available on request
0.35 Kg
Captive M6 stainless steel allen head screws. Optional hinges
Silicon rubber
Optional 6mm brass internal/external earth stud
Optional internal earth continuity plate in galvanised
steel, brass or stainless steel
Through threaded hole in body
Integral 4.5mm clearance holes moulded into the body
All Dimensions in mm
A GUIDE TO PHYSICAL TERMINAL CAPACITY
Horizontal Rail
A GUIDE TO ENTRY CAPACITY
MK 3
1x5
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Gland Size mm
Side A + B
Side C + D
16
2
1
20
1
1
25
0
0
CUSTOMISING
As a vertically integrated manufacturer Walsall can customise
the GL range at each stage of the production process to meet
individual customer requirements.
ORDERING INFORMATION
Description
Enclosure only
Enclosure with steel earth plate
Enclosure with brass earth plate
Enclosure with stainless steel earth plate
Optional Extras
Internal/ External 6mm brass earth stud
Equipment mounting plate, coated mild steel
Cover hinge each
57
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
EEx e Terminal Box
GL101
GL111
GL121
GL131
EEx e U Component Approved Enclosure
GL102
GL112
GL122
GL132
EEx ia Terminal Box
GL103
GL113
GL123
GL133
GL/ES
GL1/MP
GL/CH
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
58
EEx e and EEx i Terminal Boxes - Glass Reinforced Polyester
Type GL2 - 110mm x 75mm x 55mm
EEx e II and EE x ia IIC
Zones 0,1,2,21,22
T6
Group II Cat 1,2
EEx e and EEx i Terminal Boxes - Glass Reinforced Polyester
Type GL3 - 160mm x 75mm x 55mm
ATEX/GOST/UL
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
Entry
Mounting
Zones 0,1,2,21,22
T6
Group II Cat 1,2
II 2 GD,
II 1 GD T6
EEx e II T6 and EEx ia IIC T6
-50ºC to +50ºC (T6), +55ºC (T5), +60ºC (T4)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99 ATEX 3200 and Sira 99 ATEX 3028U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66 to EN 60529:1992
Maximum 8.0 Watts at +40˚C and 2.0 Watts at +50˚C
Except for dust applications where the maxima
are 4.0 Watts at +40˚C and 1.0 Watts at +50˚C
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
II 2 GD,
II 1 GD T6
EEx e II T6 and EEx ia IIC T6
-50ºC to +50ºC (T6), +55ºC (T5), +60ºC (T4)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99 ATEX 3200 and Sira 99 ATEX 3028U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66 to EN 60529:1992
Maximum 9.0 Watts at +40˚C and 3.0 Watts at +50˚C
Except for dust applications where the maxima
are 4.5 Watts at +40˚C and 1.5 Watts at +50˚C
ENCLOSURE SPECIFICATION
110mm x 75mm x 55mm
Carbon loaded, anti-static glass reinforced polyester UL 94/V0
Moulded self colour black. Other colours available on request
0.4 Kg
Captive M6 stainless steel allen head screws. Optional hinges
Silicon rubber
Optional 6mm brass internal/external earth stud
Optional internal earth continuity plate in galvanised
steel, brass or stainless steel
Through threaded hole in body
Integral 4.5mm clearance holes moulded into the body
Dimensions
Material
Finish
Weight empty
Cover fixing
Gasket
Earthing
Entry
Mounting
160mm x 75mm x 55mm
Carbon loaded, anti-static glass reinforced polyester UL 94/V0
Moulded self colour black. Other colours available on request
0.5 Kg
Captive M6 stainless steel allen head screws. Optional hinges
Silicon rubber
Optional 6mm brass internal/external earth stud
Optional internal earth continuity plate in galvanised
steel, brass or stainless steel
Through threaded hole in body
Integral 4.5mm clearance holes moulded into the body
All Dimensions in mm
A GUIDE TO PHYSICAL TERMINAL CAPACITY
All Dimensions in mm
A GUIDE TO ENTRY CAPACITY
MK 3
1x8
Horizontal Rail
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Gland Size mm
Side A + B
Side C + D
16
3
1
A GUIDE TO PHYSICAL TERMINAL CAPACITY
20
2
1
25
0
0
ORDERING INFORMATION
Horizontal Rail
A GUIDE TO ENTRY CAPACITY
MK 3
1x12
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Gland Size mm
Side A + B
Side C + D
16
5
1
20
4
1
25
0
0
ORDERING INFORMATION
Description
EEx e Terminal Box
GL201
GL211
GL221
GL231
Enclosure only
Enclosure with steel earth plate
Enclosure with brass earth plate
Enclosure with stainless steel earth plate
Optional Extras
Internal/ External 6mm brass earth stud
Equipment mounting plate, coated mild steel
Cover hinge each
59
ATEX/GOST/UL
HAZARDOUS AREA SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Weight empty
Cover fixing
Gasket
Earthing
EEx e II and EE x ia IIC
EEx e U Component Approved Enclosure
GL202
GL212
GL222
GL232
EEx ia Terminal Box
GL203
GL213
GL223
GL233
GL/ES
GL2/MP
GL/CH
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Description
Enclosure only
Enclosure with steel earth plate
Enclosure with brass earth plate
Enclosure with stainless steel earth plate
Optional Extras
Internal/ External 6mm brass earth stud
Equipment mounting plate, coated mild steel
Cover hinge each
EEx e Terminal Box
GL301
GL311
GL321
GL331
EEx e U Component Approved Enclosure
GL302
GL312
GL322
GL332
EEx ia Terminal Box
GL303
GL313
GL323
GL333
GL/ES
GL3/MP
GL/CH
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
60
EEx e and EEx i Terminal Boxes - Glass Reinforced Polyester
Type GL4 - 190mm x 75mm x 55mm
EEx e II and EE x ia IIC
Zones 0,1,2,21,22
T6
Group II Cat 1,2
EEx e and EEx i Terminal Boxes - Glass Reinforced Polyester
Type GL5 - 122mm x 120mm x 90mm
ATEX/GOST/UL
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
Entry
Mounting
Zones 0,1,2,21,22
T6
Group II Cat 1,2
II 2 GD,
II 1 GD T6
EEx e II T6 and EEx ia IIC T6
-50ºC to +50ºC (T6), +55ºC (T5), +60ºC (T4)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99 ATEX 3200 and Sira 99 ATEX 3028U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66 to EN 60529:1992
Maximum 9.4 Watts at +40˚C and 3.5 Watts at +50˚C
Except for dust applications where the maxima
are 4.7 Watts at +40˚C and 1.75 Watts at +50˚C
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
II 2 GD,
II 1 GD T6
EEx e II T6 and EEx ia IIC T6
-50ºC to +50ºC (T6), +55ºC (T5), +60ºC (T4)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99 ATEX 3200 and Sira 99 ATEX 3028U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66 to EN 60529:1992
Maximum 9.4 Watts at +40˚C and 3.5 Watts at +50˚C
Except for dust applications where the maxima
are 4.7 Watts at +40˚C and 1.75 Watts at +50˚C
ENCLOSURE SPECIFICATION
190mm x 75mm x 55mm
Carbon loaded, anti-static glass reinforced polyester UL 94/V0
Moulded self colour black. Other colours available on request
0.85 Kg
Captive M6 stainless steel allen head screws. Optional hinges
Silicon rubber
Optional 6mm brass internal/external earth stud
Optional internal earth continuity plate in galvanised
steel, brass or stainless steel
Through threaded hole in body
Integral 6.5mm clearance holes moulded into the body
Dimensions
Material
Finish
Weight empty
Cover fixing
Gasket
Earthing
Entry
Mounting
122mm x 120mm x 90mm
Carbon loaded, anti-static glass reinforced polyester UL 94/V0
Moulded self colour black. Other colours available on request
0.85 Kg
Captive M6 stainless steel allen head screws. Optional hinges
Silicon rubber
Optional 6mm brass internal/external earth stud
Optional internal earth continuity plate in galvanised
steel, brass or stainless steel
Through threaded hole in body
Integral 6.5mm clearance holes moulded into the body
All Dimensions in mm
All Dimensions in mm
A GUIDE TO PHYSICAL TERMINAL CAPACITY
A GUIDE TO ENTRY CAPACITY
MK 3
1x12
Horizontal Rail
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Gland Size mm
Side A + B
Side C + D
16
7
1
A GUIDE TO PHYSICAL TERMINAL CAPACITY
20
5
1
25
0
0
ORDERING INFORMATION
Horizontal Rail
WDU 2.5
1x14
WDU 4
1x12
A GUIDE TO ENTRY CAPACITY
WDU 6
1x9
WDU 10
1x6
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Gland Size mm
Side A + B
Side C + D
20
4
2
25
2
1
32
1
1
ORDERING INFORMATION
Description
EEx e Terminal Box
GL401
GL411
GL421
GL431
Enclosure only
Enclosure with steel earth plate
Enclosure with brass earth plate
Enclosure with stainless steel earth plate
Optional Extras
Internal/ External 6mm brass earth stud
Equipment mounting plate, coated mild steel
Cover hinge each
61
ATEX/GOST/UL
HAZARDOUS AREA SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Weight empty
Cover fixing
Gasket
Earthing
EEx e II and EE x ia IIC
EEx e U Component Approved Enclosure
GL402
GL412
GL422
GL432
EEx ia Terminal Box
GL403
GL413
GL423
GL433
GL/ES
GL4/MP
GL/CH
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Description
Enclosure only
Enclosure with steel earth plate
Enclosure with brass earth plate
Enclosure with stainless steel earth plate
Optional Extras
Internal/ External 6mm brass earth stud
Equipment mounting plate, coated mild steel
Cover hinge each
EEx e Terminal Box
GL501
GL511
GL521
GL531
EEx e U Component Approved Enclosure
GL502
GL512
GL522
GL532
EEx ia Terminal Box
GL503
GL513
GL523
GL533
GL/ES
GL5/MP
GL/CH
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
62
EEx e and EEx i Terminal Boxes - Glass Reinforced Polyester
Type GL6 - 220mm x 120mm x 90mm
EEx e II and EE x ia IIC
Zones 0,1,2,21,22
T6
Group II Cat 1,2
EEx e and EEx i Terminal Boxes - Glass Reinforced Polyester
Type GL7 - 160mm x 160mm x 90mm
ATEX/GOST/UL
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
Entry
Mounting
Zones 0,1,2,21,22
T6
Group II Cat 1,2
II 2 GD,
II 1 GD T6
EEx e II T6 and EEx ia IIC T6
-50ºC to +50ºC (T6), +55ºC (T5), +60ºC (T4)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99 ATEX 3200 and Sira 99 ATEX 3028U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66 to EN 60529:1992
Maximum 9.4 Watts at +40ºC and 3.5 Watts at +50ºC
Except for dust applications where the maxima
are 4.7 Watts at +40ºC and 1.75 Watts at +50ºC
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
II 2 GD,
II 1 GD T6
EEx e II T6 and EEx ia IIC T6
-50ºC to +50ºC (T6), +55ºC (T5), +60ºC (T4)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99 ATEX 3200 and Sira 99 ATEX 3028U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66 to EN 60529:1992
Maximum 10.4 Watts at +40˚C and 4.3 Watts at +50˚C
Except for dust applications where the maxima
are 5.2 Watts at +40˚C and 2.2 Watts at +50˚C
ENCLOSURE SPECIFICATION
220mm x 120mm x 90mm
Carbon loaded, anti-static glass reinforced polyester UL 94/V0
Moulded self colour black. Other colours available on request
1.0 Kg
Captive M6 stainless steel allen head screws. Optional hinges
Silicon rubber
Optional 6mm brass internal/external earth stud
Optional internal earth continuity plate in galvanised
steel, brass or stainless steel
Through threaded hole in body
Integral 6.5mm clearance holes moulded into the body.
Dimensions
Material
Finish
Weight empty
Cover fixing
Gasket
Earthing
Entry
Mounting
160mm x 160mm x 90mm
Carbon loaded, anti-static glass reinforced polyester UL 94/V0
Moulded self colour black. Other colours available on request
1.1 Kg
Captive M6 stainless steel allen head screws. Optional hinges
Silicon rubber
Optional 6mm brass internal/external earth stud
Optional internal earth continuity plate in galvanised
steel, brass or stainless steel
Through threaded hole in body
Integral 6.5mm clearance holes moulded into the body
All Dimensions in mm
A GUIDE TO PHYSICAL TERMINAL CAPACITY
Horizontal Rail
WDU 2.5
1x34
WDU 4
1x29
All Dimensions in mm
A GUIDE TO ENTRY CAPACITY
WDU 6
1x21
WDU 10
1x16
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Gland Size mm
Side A + B
Side C + D
20
6
2
A GUIDE TO PHYSICAL TERMINAL CAPACITY
25
5
1
32
3
1
ORDERING INFORMATION
Horizontal Rail
WDU 2.5
1x20
WDU 4
1x17
A GUIDE TO ENTRY CAPACITY
WDU 6
1x12
WDU 10
1x9
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Gland Size mm
Side A + B
Side C + D
20
8
6
25
3
2
32
2
1
ORDERING INFORMATION
Description
EEx e Terminal Box
GL601
GL611
GL621
GL631
Enclosure only
Enclosure with steel earth plate
Enclosure with brass earth plate
Enclosure with stainless steel earth plate
Optional Extras
Internal/ External 6mm brass earth stud
Equipment mounting plate, coated mild steel
Cover hinge each
63
ATEX/GOST/UL
HAZARDOUS AREA SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Weight empty
Cover fixing
Gasket
Earthing
EEx e II and EE x ia IIC
EEx e U Component Approved Enclosure
GL602
GL612
GL622
GL632
EEx ia Terminal Box
GL603
GL613
GL623
GL633
GL/ES
GL6/MP
GL/CH
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Description
Enclosure only
Enclosure with steel earth plate
Enclosure with brass earth plate
Enclosure with stainless steel earth plate
Optional Extras
Internal/ External 6mm brass earth stud
Equipment mounting plate, coated mild steel
Cover hinge each
EEx e Terminal Box
GL701
GL711
GL721
GL731
EEx e U Component Approved Enclosure
GL702
GL712
GL722
GL732
EEx ia Terminal Box
GL703
GL713
GL723
GL733
GL/ES
GL7/MP
GL/CH
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
64
EEx e and EEx i Terminal Boxes - Glass Reinforced Polyester
Type GL8 - 260mm x 160mm x 90mm
EEx e II and EE x ia IIC
Zones 0,1,2,21,22
T6
Group II Cat 1,2
EEx e and EEx i Terminal Boxes - Glass Reinforced Polyester
Type GL9 - 360mm x 160mm x 90mm
ATEX/GOST/UL
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
Entry
Mounting
Zones 0,1,2,21,22
T6
Group II Cat 1,2
II 2 GD,
II 1 GD T6
EEx e II T6 and EEx ia IIC T6
-50ºC to +50ºC (T6), +55ºC (T5), +60ºC (T4)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99 ATEX 3200 and Sira 99 ATEX 3028U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66 to EN 60529:1992
Maximum 12.0 Watts at +40˚C and 5.0 Watts at +50˚C
Except for dust applications where the maxima
are 6.0 Watts at +40˚C and 2.5 Watts at +50˚C
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
II 2 GD,
II 1 GD T6
EEx e II T6 and EEx ia IIC T6
-50ºC to +50ºC (T6), +55ºC (T5), +60ºC (T4)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99 ATEX 3200 and Sira 99 ATEX 3028U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66 to EN 60529:1992
Maximum 13.8 Watts at +40˚C and 6.2 Watts at +50˚C
Except for dust applications where the maxima
are 6.9 Watts at +40˚C and 3.1 Watts at +50˚C
ENCLOSURE SPECIFICATION
260mm x 160mm x 90mm
Carbon loaded, anti-static glass reinforced polyester UL 94/V0
Moulded self colour black. Other colours available on request
1.7 Kg
Captive M6 stainless steel allen head screws. Optional hinges
Silicon rubber
Optional 6mm brass internal/external earth stud
Optional internal earth continuity plate in galvanised
steel, brass or stainless steel
Through threaded hole in body
Integral 6.5mm clearance holes moulded into the body
Dimensions
Material
Finish
Weight empty
Cover fixing
Gasket
Earthing
Entry
Mounting
360mm x 160mm x 90mm
Carbon loaded, anti-static glass reinforced polyester UL 94/V0
Moulded self colour black. Other colours available on request
2.0 Kg
Captive M6 stainless steel allen head screws. Optional hinges
Silicon rubber
Optional 6mm brass internal/external earth stud
Optional internal earth continuity plate in galvanised
steel, brass or stainless steel
Through threaded hole in body
Integral 6.5mm clearance holes moulded into the body
All Dimensions in mm
A GUIDE TO PHYSICAL TERMINAL CAPACITY
Horizontal Rail
WDU 2.5
1x40
WDU 4
1x34
All Dimensions in mm
A GUIDE TO ENTRY CAPACITY
WDU 6
1x25
WDU 10
1x19
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Gland Size mm
Side A + B
Side C + D
20
14
6
A GUIDE TO PHYSICAL TERMINAL CAPACITY
25
6
2
32
4
1
ORDERING INFORMATION
Horizontal Rail
WDU 2.5
1x60
WDU 4
1x51
A GUIDE TO ENTRY CAPACITY
WDU 6
1x37
WDU 10
1x29
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Gland Size mm
Side A + B
Side C + D
20
20
6
25
9
2
32
6
1
ORDERING INFORMATION
Description
EEx e Terminal Box
GL801
GL811
GL821
GL831
Enclosure only
Enclosure with steel earth plate
Enclosure with brass earth plate
Enclosure with stainless steel earth plate
Optional Extras
Internal/ External 6mm brass earth stud
Equipment mounting plate, coated mild steel
Cover hinge each
65
ATEX/GOST/UL
HAZARDOUS AREA SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Weight empty
Cover fixing
Gasket
Earthing
EEx e II and EE x ia IIC
EEx e U Component Approved Enclosure
GL802
GL812
GL822
GL832
EEx ia Terminal Box
GL803
GL813
GL823
GL833
GL/ES
GL8/MP
GL/CH
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Description
Enclosure only
Enclosure with steel earth plate
Enclosure with brass earth plate
Enclosure with stainless steel earth plate
Optional Extras
Internal/ External 6mm brass earth stud
Equipment mounting plate, coated mild steel
Cover hinge each
EEx e Terminal Box
GL901
GL911
GL921
GL931
EEx e U Component Approved Enclosure
GL902
GL912
GL922
GL932
EEx ia Terminal Box
GL903
GL913
GL923
GL933
GL/ES
GL9/MP
GL/CH
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
66
EEx e and EEx i Terminal Boxes - Glass Reinforced Polyester
Type GL10 - 560mm x 160mm x 90mm
EEx e II and EE x ia IIC
Zones 0,1,2,21,22
T6
Group II Cat 1,2
EEx e and EEx i Terminal Boxes - Glass Reinforced Polyester
Type GL11 - 255mm x 250mm x 120mm
ATEX/GOST/UL
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
Entry
Mounting
Zones 0,1,2,21,22
T6
Group II Cat 1,2
II 2 GD,
II 1 GD T6
EEx e II T6 and EEx ia IIC T6
-50ºC to +50ºC (T6), +55ºC (T5), +60ºC (T4)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99 ATEX 3200 and Sira 99 ATEX 3028U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66 to EN 60529:1992
Maximum 13.8 Watts at +40˚C and 6.2 Watts at +50˚C
Except for dust applications where the maxima
are 6.9 Watts at +40˚C and 3.1 Watts at +50˚C
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
II 2 GD,
II 1 GD T6
EEx e II T6 and EEx ia IIC T6
-50ºC to +50ºC (T6), +55ºC (T5), +60ºC (T4)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99 ATEX 3200 and Sira 99 ATEX 3028U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66 to EN 60529:1992
Maximum 15.5 Watts at +40˚C and 6.4 Watts at +50˚C
Except for dust applications where the maxima
are 7.75 Watts at +40˚C and 3.2 Watts at +50˚C
ENCLOSURE SPECIFICATION
560mm x 160mm x 90mm
Carbon loaded, anti-static glass reinforced polyester UL 94/V0
Moulded self colour black. Other colours available on request
3.7 Kg
Captive M6 stainless steel allen head screws. Optional hinges
Silicon rubber
Optional 6mm brass internal/external earth stud
Optional internal earth continuity plate in galvanised
steel, brass or stainless steel
Through threaded hole in body
Integral 6.5mm clearance holes moulded into the body
Dimensions
Material
Finish
Weight empty
Cover fixing
Gasket
Earthing
Entry
Mounting
255mm x 250mm x 120mm
Carbon loaded, anti-static glass reinforced polyester UL 94/V0
Moulded self colour black. Other colours available on request
2.7 Kg
Captive M6 stainless steel allen head screws. Optional hinges
Silicon rubber
Optional 6mm brass internal/external earth stud
Optional internal earth continuity plate in galvanised
steel, brass or stainless steel
Through threaded hole in body
Integral 6.5mm clearance holes moulded into the body
All Dimensions in mm
A GUIDE TO PHYSICAL TERMINAL CAPACITY
Horizontal Rail
WDU 2.5
1x100
WDU 4
1x84
All Dimensions in mm
A GUIDE TO ENTRY CAPACITY
WDU 6
1x62
WDU 10
1x49
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Gland Size mm
Side A + B
Side C + D
20
34
6
A GUIDE TO PHYSICAL TERMINAL CAPACITY
25
16
2
32
10
1
ORDERING INFORMATION
Horizontal Rail
WDU 2.5
2x39
WDU 4
2x33
A GUIDE TO ENTRY CAPACITY
WDU 6
2x24
WDU 10
2x18
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Gland Size mm
Side A + B
Side C + D
20
17
14
25
10
8
32
5
4
ORDERING INFORMATION
Description
EEx e Terminal Box
GL1001
GL1011
GL1021
GL1031
Enclosure only
Enclosure with steel earth plate
Enclosure with brass earth plate
Enclosure with stainless steel earth plate
Optional Extras
Internal/ External 6mm brass earth stud
Equipment mounting plate, coated mild steel
Cover hinge each
67
ATEX/GOST/UL
HAZARDOUS AREA SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Weight empty
Cover fixing
Gasket
Earthing
EEx e II and EE x ia IIC
EEx e U Component Approved Enclosure
GL1002
GL1012
GL1022
GL1032
EEx ia Terminal Box
GL1003
GL1013
GL1023
GL1033
GL/ES
GL10/MP
GL/CH
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Description
Enclosure only
Enclosure with steel earth plate
Enclosure with brass earth plate
Enclosure with stainless steel earth plate
Optional Extras
Internal/ External 6mm brass earth stud
Equipment mounting plate, coated mild steel
Cover hinge each
EEx e Terminal Box
GL1101
GL1111
GL1121
GL1131
EEx e U Component Approved Enclosure
GL1102
GL1112
GL1122
GL1132
EEx ia Terminal Box
GL1103
GL1113
GL1123
GL1133
GL/ES
GL11/MP
GL/CH
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
68
EEx e and EEx i Terminal Boxes - Glass Reinforced Polyester
Type GL12 - 400mm x 250mm x 120mm
EEx e II and EE x ia IIC
Zones 0,1,2,21,22
T6
Group II Cat 1,2
EEx e and EEx i Terminal Boxes - Glass Reinforced Polyester
Type GL13 - 405mm x 400mm x 120mm
ATEX/GOST/UL
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
Entry
Mounting
Zones 0,1,2,21,22
T6
Group II Cat 1,2
II 2 GD,
II 1 GD T6
EEx e II T6 and EEx ia IIC T6
-50ºC to +50ºC (T6), +55ºC (T5), +60ºC (T4)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99 ATEX 3200 and Sira 99 ATEX 3028U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66 to EN 60529:1992
Maximum 15.5 Watts at +40˚C and 6.4 Watts at +50˚C
Except for dust applications where the maxima
are 7.75 Watts at +40˚C and 3.2 Watts at +50˚C
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
II 2 GD,
II 1 GD T6
EEx e II T6 and EEx ia IIC T6
-50ºC to +50ºC (T6), +55ºC (T5), +60ºC (T4)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99 ATEX 3200 and Sira 99 ATEX 3028U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66 to EN 60529:1992
Maximum 31.4 Watts at +40˚C and 11.2 Watts at +50˚C
Except for dust applications where the maxima
are 15.7 Watts at +40˚C and 5.6 Watts at +50˚C
ENCLOSURE SPECIFICATION
400mm x 250mm x 120mm
Carbon loaded, anti-static glass reinforced polyester UL 94/V0
Moulded self colour black. Other colours available on request
3.4 Kg
Captive M6 stainless steel allen head screws. Optional hinges
Silicon rubber
Optional 6mm brass internal/external earth stud
Optional internal earth continuity plate in galvanised
steel, brass or stainless steel
Through threaded hole in body
Integral 6.5mm clearance holes moulded into the body
Dimensions
Material
Finish
Weight empty
Cover fixing
Gasket
Earthing
Entry
Mounting
405mm x 400mm x 120mm
Carbon loaded, anti-static glass reinforced polyester UL 94/V0
Moulded self colour black. Other colours available on request
5.1 Kg
Captive M6 stainless steel allen head screws. Optional hinges
Silicon rubber
Optional 6mm brass internal/external earth stud
Optional internal earth continuity plate in galvanised
steel, brass or stainless steel
Through threaded hole in body
Integral 6.5mm clearance holes moulded into the body
All Dimensions in mm
A GUIDE TO PHYSICAL TERMINAL CAPACITY
Horizontal Rail
WDU 2.5
2x68
WDU 4
2x57
All Dimensions in mm
A GUIDE TO ENTRY CAPACITY
WDU 6
2x42
WDU 10
2x33
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Gland Size mm
Side A + B
Side C + D
20
32
14
A GUIDE TO PHYSICAL TERMINAL CAPACITY
25
18
8
32
9
4
ORDERING INFORMATION
Horizontal Rail
WDU 2.5
3x68
WDU 4
3x57
A GUIDE TO ENTRY CAPACITY
WDU 6
3x42
WDU 10
3x33
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Gland Size mm
Side A + B
Side C + D
20
32
29
25
18
16
32
9
9
ORDERING INFORMATION
Description
EEx e Terminal Box
GL1201
GL1211
GL1221
GL1231
Enclosure only
Enclosure with steel earth plate
Enclosure with brass earth plate
Enclosure with stainless steel earth plate
Optional Extras
Internal/ External 6mm brass earth stud
Equipment mounting plate, coated mild steel
Cover hinge each
69
ATEX/GOST/UL
HAZARDOUS AREA SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Weight empty
Cover fixing
Gasket
Earthing
EEx e II and EE x ia IIC
EEx e U Component Approved Enclosure
GL1202
GL1212
GL1222
GL1232
EEx ia Terminal Box
GL1203
GL1213
GL1223
GL1233
GL/ES
GL12/MP
GL/CH
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Description
Enclosure only
Enclosure with steel earth plate
Enclosure with brass earth plate
Enclosure with stainless steel earth plate
Optional Extras
Internal/ External 6mm brass earth stud
Equipment mounting plate, coated mild steel
Cover hinge each
EEx e Terminal Box
GL1301
GL1311
GL1321
GL1331
EEx e U Component Approved Enclosure
GL1302
GL1312
GL1322
GL1332
EEx ia Terminal Box
GL1303
GL1313
GL1323
GL1333
GL/ES
GL13/MP
GL/CH
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
70
EEx e and EEx i Terminal Boxes - Glass Reinforced Polyester
Type GL14 - 405mm x 400mm x 165mm
EEx e II and EE x ia IIC
Zones 0,1,2,21,22
T6
Group II Cat 1,2
ATEX/GOST/UL
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
Power dissipation
II 2 GD,
II 1 GD T6
EEx e II T6 and EEx ia IIC T6
-50ºC to +50ºC (T6), +55ºC (T5), +60ºC (T4)
Zones 0,1,2,21,22. Groups IIA, IIB, IIC
Sira 99 ATEX 3200 and Sira 99 ATEX 3028U
GOST ‘R’ POCC GB. гБ05.BO1131
IP66 to EN 60529:1992
Maximum 31.4 Watts at +40˚C and 11.2 Watts at +50˚C
Except for dust applications where the maxima
are 15.7 Watts at +40˚C and 5.6 Watts at +50˚C
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Weight empty
Cover fixing
Gasket
Earthing
Entry
Mounting
405mm x 400mm x 165mm
Carbon loaded, anti-static glass reinforced polyester UL 94/V0
Moulded self colour black. Other colours available on request
5.1 Kg
Captive M6 stainless steel allen head screws. Optional hinges
Silicon rubber
Optional 6mm brass internal/external earth stud
Optional internal earth continuity plate in galvanised
steel, brass or stainless steel
Through threaded hole in body
Integral 6.5mm clearance holes moulded into the body
All Dimensions in mm
A GUIDE TO PHYSICAL TERMINAL CAPACITY
Horizontal Rail
WDU 2.5
3x68
WDU 4
3x57
A GUIDE TO ENTRY CAPACITY
WDU 6
3x42
WDU 10
3x33
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
Gland Size mm
Side A + B
Side C + D
20
42
38
25
27
25
32
14
14
ORDERING INFORMATION
Description
Enclosure only
Enclosure with steel earth plate
Enclosure with brass earth plate
Enclosure with stainless steel earth plate
EEx e Terminal Box
GL1401
GL1411
GL1421
GL1431
Optional Extras
Internal/ External 6mm brass earth stud
Equipment mounting plate, coated mild steel
Cover hinge each
71
EEx e U Component Approved Enclosure
GL1402
GL1412
GL1422
GL1432
EEx ia Terminal Box
GL1403
GL1413
GL1423
GL1433
GL terminal boxes installed by
Maersk Oil and Gas
GL/ES
GL14/MP
GL/CH
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
72
EEx d IIC Terminal Box - Cast Iron
Type E115 - 117mm x 117mm x 70mm
PART 1.8
E RANGE
EEx d IIC
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
A range of small very robust EEx d IIB and EEx d IIC cast iron
terminal boxes suitable for MK type terminals. The terminal boxes
have Ingress Protection of IP66
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No
Ingress protection
Power dissapation
Type E115 – EEx d IIC 117mm x 117mm x 70mm
Page 74
Type E210 – EEx d IIB 145mm x 106mm x 65mm
Page 75
Type E220 – EEx d IIB 104mm diam x 59mm
Page 76
II 2 GD
EEx d IIC T6
-40˚C to +50˚C
Zones 1,2,21,22 Groups IIA, IIB, IIC
SIRA02ATEX1311
GOST ‘R’ POCC GB. гБ05. BO1131
IP66 to EN60529:1992
5 Watts
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Colour
Weight
Cover fixing
Gasket
Earthing
Mounting
117mm x 117mm x 70mm
Cast iron to 180BS1452:1977
Zinc rich epoxy powder primer plus epoxy powder top coat
Black
3.5 Kg
M6 allen head stainless steel screws
Nitrile rubber O ring
Base- internal and external EEx e brass clamps
Cover- internal EEx e brass clamp
Integral 8mm fixing holes in base
ENTRY SPECIFICATION
1 x 20mm EEx d entries at A, B, C, D as standard
All entries filled with EE x d stopping plugs as standard
25mm entries available as an option
All Dimensions in mm
ORDERING INFORMATION
Terminal Type
MK3/8
MK6/6
Number of Terminals
8
6
Product Code
E115001
E115002
For 25mm entries add /25 to product code eg. E115001/25
73
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
74
EEx d IIB Terminal Box - Cast Iron
Type E210 - 145mm x 106mm x 65mm
EEx d IIB
Zones 1,2,21,22
T6
EEx d IIB Circular Terminal Box - Cast Iron
Type E220 - 105mm diameter x 59mm
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
II 2 GD
EEx d IIB T6
-20˚C to +40˚C
Zones 1,2,21,22. Groups IIA, IIB
SIRA01ATEX1129
GOST ’R’ POCC GB. гБ05. B01131
IP66 to EN60529:1992
Marking to94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress Protection
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Weight
Cover fixing
Gasket
Earthing
Mounting
EEx d IIB
II 2 GD
EEx d IIB T6
-20˚C to +40˚C
Zones 1,2,21,22. Goup IIA, IIB
SIRA01 ATEX1130
GOST’R’ POCC GB. гБ05. B01131
IP66 to EN60529: 1992
ENCLOSURE SPECIFICATION
145mm x 106mm x 65mm
Cast iron to 180BSI1452:1997
Zinc rich epoxy powder primer and epoxy powder top coat
1.5 Kg
M6 allen head stainless steel screws
By grease
Internal and external EEx e brass clamps on base
Steel mounting strap. 8mm diameter fixing holes
Dimensions
Material
Finish
Colour
Weight
Cover fixing
Gasket
Earthing
Mounting
104mm diameter x 59mm
Cast iron to 180BSI1452:1997
Zinc rich epoxy powder primer and epoxy powder top coat
Black
2 Kgs
M6 allen stainless steel screws
By grease
Internal and external EEx e clamps on base
Steel mounting strap, 8mm fixing holes
ENTRY SPECIFICATION
ENTRY SPECIFICATION
1 x 20mm EEx d entries at A, B, C, D, E, F as standard
All entries filled with EE x d stopping plugs as standard
25mm entries available as an option
1 x 20mm EEx d entries at A, B, C, D as standard
All entries filled with EE x d stopping plugs as standard
25mm entries available as an option
All Dimensions in mm
All Dimensions in mm
ORDERING INFORMATION
Terminal Type
MK3/12
MK6/6
Number of Terminals
12
6
Product Code
E211
E212
For 25mm entries add /25 to product code eg. E214/25
75
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
ORDERING INFORMATION
Terminal Type
MK3/4
Number of Terminals
4
Product Code
E220
For 25mm entries add /25 to product code eg. E220/25
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
76
EEx d IIB Terminal Box - Cast Aluminium, Cast Iron & Cast Stainless Steel
Type ASMT130 - 210mm x 185mm x 152mm
PART 1.9
ASMT RANGE
EEx d IIB
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Medium to large EEx d IIB approved terminal boxes manufactured in
Cast Aluminium, Cast Iron and Cast Stainless Steel with a two pack
coating consisting of a specially formulated zinc rich epoxy primer
followed by a standard epoxy top coat. The terminal boxes have
Ingress Protection to IP66
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
Power dissipation
Cast Aluminium
Type ASMT130/AL – 210mm x 185mm x 152mm
Page 78
Type ASMT150/AL – 335mm x 310mm x 200mm
Page 79
Cast Iron
Page 78
Finish
Type ASMT150/CI – 335mm x 310mm x 200mm
Page 79
Type ASMT170/CI – 560mm x 560mm x 245mm
Page 80
Weight empty
Cover fixing
Gasket
Earthing
Mounting
Cast Stainless Steel
Type ASMT130/SS – 210mm x 185mm x 152mm
Page 78
Type ASMT150/SS – 335mm x 310mm x 200mm
Page 79
Type ASMT170/SS – 560mm x 560mm x 245mm
Page 80
II 2 GD
EEx d IIB T6
-20˚C to +40˚C
Zones 1,2,21,22 . Groups IIA, IIB
SIRA03ATEX1215 and SIRA03ATEX1187U
GOST’R’ POCC GB. гБ05. B01131
IP66 to EN60529:1992
Maximum 7.0 Watts at +40˚C
ENCLOSURE SPECIFICATION
Dimensions
Material
Type ASMT130/CI – 210mm x 185mm x 152mm
Zones 1,2,21,22
210mm x 185mm x 152mm
Cast aluminium LM6
Cast iron to 180BSI1452:1997
Cast stainless steel 316l (1.4404)
Zinc rich epoxy powder primer and epoxy powder top
coat black
Cast aluminium 6.0Kg, Cast iron 20Kg , Cast stainless 21Kg
Hinged with M6 allen head stainless steel screws
One piece closed cell 4mm neoprene
Base- internal and external EEx e brass clamp
Cover – internal EEx e brass clamps
2 steel mounting straps. 8mm diameter fixing holes
All Dimensions in mm
ENTRY SPECIFICATION
EEx d threaded holes through base
All entries are fitted with EEx d stopping plugs or cable glands as standard unless
otherwise specified
A GUIDE TO PHYSICAL TERMINAL CAPACITY
CUSTOMISING
As a vertically integrated manufacturer Walsall can customise the
ASMT range at each stage of the production process to meet
individual customer requirements.
Verticle Rail
Horizontal Rail
WDU 2.5
1x21
1x15
WDU 4
1x17
1x12
WDU 6
1x13
1x9
A GUIDE TO ENTRY CAPACITY
WDU 10
1x9
1x7
Gland Size mm
Side A + B
Side C + D
20
5
5
25
5
5
32
2
3
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
ORDERING INFORMATION
Material
Cast Aluminium
Cast Iron
Cast Stainless Steel
77
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
EEx d Terminal Box
ASMT130/AL
ASMT130/CI
ASMT130/SS
EEx e U Component Approved Enclosure
ASMT130U/AL
ASMT130U/CI
ASMT130U/SS
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
78
EEx d IIB Terminal Box - Cast Aluminium, Cast Iron & Cast Stainless Steel
Type ASMT150 - 335mm x 310mm x 200mm
EEx d IIB
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
EEx d IIB
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
Power dissipation
Finish
Weight empty
Cover fixing
Gasket
Earthing
Mounting
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
II 2 GD
EEx d IIB T6
-40ºC to +50ºC
Zones 1,2,21,22. Groups IIA, IIB
SIRA04ATEX1266X and SIRA00ATEX1188U (-20ºC)
TRL03ATEX11029X (-40ºC)
GOST’R’ POCC GB. гБ05. B01131
IP66 to EN60529:1992
Maximum 62 Watts at +50˚C
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Number
Ingress protection
Power dissipation
ENCLOSURE SPECIFICATION
Dimensions
Material
EEx d IIB Terminal Box - Cast Iron & Cast Stainless Steel
Type ASMT170 - 560mm x 560mm x 245mm
II 2 GD
EEx d IIB T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB
SIRA04ATEX1267X and SIRA00ATEX1189U (-20ºC)
TRL03ATEX11030X (-40ºC)
GOST’R’ POCC GB. гБ05. B01131
IP66 to EN60529:1992
Maximum 200 Watts at +50˚C
ENCLOSURE SPECIFICATION
335mm x 310mm x 200mm
Cast aluminium LM6
Cast iron to 180BSI1452:1997
Cast stainless steel 316L (1.4404)
Zinc rich epoxy powder primer and epoxy powder top
coat, black
Cast aluminium 17Kgs, Cast iron 50Kgs , cast stainless 52Kgs
Hinged with M6 allen head stainless steel screws
One piece closed cell 4mm neoprene
Base- internal and external EEx e brass clamps
Cover – internal EEx e brass clamp
2 steel mounting straps. 8mm diameter fixing holes
Dimensions
Material
Finish
Weight empty
Cover fixing
Gasket
Earthing
All Dimensions in mm
Mounting
560mm x 560mm x 245mm
Cast iron to 180BSI1452:1997
Cast stainless steel 316L
Zinc rich epoxy powder primer and epoxy powder top coat
Cast iron 190Kgs , cast stainless 195Kgs
Hinged with M10 allen head stainless steel screws
One piece closed cell 4mm neoprene
Base- internal and external EEx e brass clamps
Cover – internal EEx e brass clamp
2 steel U shaped mounting straps
10mm diameter fixing holes
All Dimensions in mm
ENTRY SPECIFICATION
EEx d threaded holes through base.
All entries are fitted with EEx d stopping plugs or cable glands as standard unless
otherwise specified.
ENTRY SPECIFICATION
EEx d threaded holes through base
All entries are fitted with EEx d stopping plugs or cable glands as standard unless
otherwise specified
A GUIDE TO PHYSICAL TERMINAL CAPACITY
Verticle Rails
Horizontal Rails
WDU 2.5
2x45
2x39
WDU 4
2x37
2x33
WDU 6
2x27
2x24
A GUIDE TO ENTRY CAPACITY
WDU 10
2x22
2x19
Gland Size mm
Side A + B
Side C + D
20
11
11
25
8
8
32
7
7
A GUIDE TO PHYSICAL TERMINAL CAPACITY
40
3
3
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
79
Verticle Rails
Horizontal Rails
WDU 2.5
4x78
4x78
WDU 4
4x33
4x33
WDU 6
4x24
4x24
WDU 10
4x19
4x19
Gland Size mm
Side A + B
Side C + D
20
12
12
25
12
12
32
6
6
40
6
6
50
3
3
Note: This is a guide to Physical Terminal Capacity only. Installers must ensure that the maximum power dissapation given above is not exceeded
ORDERING INFORMATION
Material
Cast Aluminium
Cast Iron
Cast Stainless Steel
50
3
3
A GUIDE TO ENTRY CAPACITY
ORDERING INFORMATION
EEx d Terminal Box
ASMT150/AL
ASMT150/CI
ASMT150/SS
EEx e U Component Approved Enclosure
ASMT150U/AL
ASMT150U/CI
ASMT150U/SS
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Material
Cast Iron
Cast Stainless Steel
EEx d Terminal Box
ASMT170/CI
ASMT170/SS
EEx e U Component Approved Enclosure
ASMT170U/CI
ASMT170U/SS
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
80
PART 2.0
CONTROL IN GRP, STAINLESS STEEL
AND ALUMINIUM ENCLOSURES
Comprehensive ranges of standard and customised EEx edm IIC one, two and
three function local control stations and customised multifunction control
panels in enclosures manufactured from glass reinforced polyester, fabricated
stainless steel and fabricated aluminium.
2.1 CF Range
Page 83
EEx e, EEx ed, and EEx em control functions and actuators
2.2 LCP Range
Page 89
Standard and customised EEx edm local control stations in
glass reinforced polyester enclosures
2.3 LCS Range
Page 101
Standard and customised EEx edm local control stations in
stainless steel enclosures
2.4 LCA Range
Page 111
Standard and customised EEx edm local control stations in
fabricated aluminium enclosures
2.5 GVU Range
Page 121
Standard EEx ed heavy duty local control stations in glass
reinforced polyester enclosures
2.6 GLCP Range
Page 125
Customised EEx edm control panels
in glass reinforced polyester enclosures
2.7 XLCP Range
Page 127
Customised EEx edm control panels in stainless steel enclosures
81
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
82
EEx edm Control Functions
Introduction
PART 2.1
CF RANGE
EEx edm IIC
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
INTRODUCTION
A comprehensive range of EEx e, EEx de and
EEx em control switches , contact blocks,
indicator lamps and measuring instruments for
installation in EEx approved enclosures
manufactured in glass reinforced polyester,
stainless steel and aluminium.
EEx edm control stations and control panels are made up from two sets of Ex approved components, control functions and enclosures.
Note a control function is defined as an electrical operating module (contact block) plus an actuator (pushbutton).
The switches, contact blocks, indicators and measuring instruments of the control function range use a variety of types of protection depending on
the application. For example switches and contact blocks, that naturally produce sparking during their operation, use type of protection ‘d’, whereas an
LED indicator lamp may use encapsulation as its method of protection and will therefore be of type ‘q’ or ‘m’.
Actuators must simply provide a suitable IP rating and must not leak in the event of a failure when mounted on the front of the enclosure.
Introduction
Page 84
Type CF 1 to 10 – EEx ed Control Switches
Page 85
Type CF 11 to 32 – EEx ed Push Buttons
Page 86
Type CF 33 to 37 – EEx em LED Indicators
Page 87
Type CF 38 – EEx e Ammeters
Page 88
Type MCBD/RCDD – EEx de MCB/RCD*
Page 88
*
These products will be introduced later in 2006 and are
included for advanced notice only
83
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
The enclosures, that are generally manufactured from glass reinforced polyester, stainless steel and aluminium are EEx e approved with a minimum
IP rating of 66 for gas and dust applications.
The method for engineering an approved control system is shown in the diagram below.
‘e’, ‘ed’, ‘em’
control functions
+
‘e’
enclosures
=
‘e’, ‘ed’, ‘em’, ‘edm’
control systems
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
84
EEx edm Control Functions
Type CF - EEx de Switches
EEx de IIC
Zones 1,2,21,22
EEx edm Control Functions
Type CF - EEx de Pushbuttons
T6
Group II Cat 2
ATEX/GOST
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
II 2 G
EEx de II T6
-40˚C or -20˚C to +50˚C
Zones 1,2,21,22 . Groups IIA, IIB, IIC
SIRA03ATEX1269U
Dimensions
Material
Weight
Contact
42mm x 42mm x 72mm
GRP
0.04 Kgs
Silver (gold optional)
Group II Cat 2
ATEX/GOST
II 2 G
EEx de II T6
-40˚C or -20˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
SIRA03ATEX1269U
42mm x 42mm x 46mm
GRP
0.04 Kgs
Silver (gold optional)
ELECTRICAL SPECIFICATION
ELECTRICAL SPECIFICATION
Operating Voltage
Operating Current
Terminal Capacity
T6
ENCLOSURE SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material
Weight
Contact
Zones 1,2,21,22
HAZARDOUS AREA SPECIFICATION
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
EEx de IIC
Operating Voltage
Operating Current
Terminal Capacity
270 Volts
16 Amps
2.5mmsq
270 Volts
16 Amps
2.5mmsq
42
4
ORDERING INFORMATION
72
42
ORDERING INFORMATION
Description
Double pole on – off
Double pole changeover
Single pole changeover
Two position
Three position - Centre off
Three position - Centre off
Three position - Centre off
Three position - Control Switch
Three position - Control Switch
Three position - Control Switch
CONTACT ARRANGEMENTS
Action
Contacts* Product Code
1
CF1
Engage - Engage
Engage - Engage
2
CF2
Engage - Engage - Engage
5
CF3
Engage - Engage
3
CF4
Engage - Engage - Engage
3
CF5
Engage - Engage - Spring
3
CF6
Spring - Engage - Spring
3
CF7
Spring - Engage - Spring
4
CF8
Spring - Engage - Spring
4
CF9
Spring - Engage - Spring
4
CF10
* See Contact Arrangements opposite
Notes: 1 For small rotary actuator add /A
2 For small key lockable rotary actuator add /AK (2 position only)
3 For large rotary actuator add /B
4 For large lockable rotary actuator add /BL
5 Individual labelling to be customer specified
85
1
3
5
20º
90º
20º
90º
20º
90º
160º
1-3 2-4 5-7 6-8
1-3 2-4 5-7 6-8
2
4
20º
90º
20º
90º
160º
1-3 2-4 5-7 6-8
1-3 2-4 5-7 6-8
1-3 2-4 5-7 6-8
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Description
Green pushbutton
Green pushbutton
Green pushbutton
Red pushbutton
Red pushbutton
Red pushbutton
Red mushroom pushbutton
Red mushroom pushbutton
Red mushroom pushbutton
Red mushroom pushbutton
Red mushroom pushbutton
Red mushroom pushbutton
Red mushroom pushbutton
Red mushroom pushbutton
Red mushroom pushbutton
Emergency mushroom pushbutton
Emergency mushroom pushbutton
Emergency mushroom pushbutton
Emergency mushroom pushbutton
Emergency mushroom pushbutton
Emergency mushroom pushbutton
Double green and red pushbutton
Action
Spring
Spring
Spring
Spring
Spring
Spring
Spring
Spring
Spring
latching pull release
latching pull release
latching pull release
latching key release
latching key release
latching key release
latching pull release
latching pull release
latching pull release
latching key release
latching key release
latching key release
Spring
Contacts
I n/o + I n/c
2n/o
2n/c
I n/o + I n/c
2n/o
2n/c
I n/o + I n/c
2n/o
2n/c
I n/o + I n/c
2n/o
2n/c
I n/o + I n/c
2n/o
2n/c
I n/o + I n/c
2n/o
2n/c
I n/o + I n/c
2n/o
2n/c
I n/o + I n/c
Product Code
CF11
CF12
CF13
CF14
CF15
CF16
CF17
CF18
CF19
CF20
CF21
CF22
CF23
CF24
CF25
CF26
CF27
CF28
CF29
CF30
CF31
CF32
* See Contact Arrangements opposite
Notes: 1 Button heads can be engraved with text as per customer requirement
2 Alternative button colours available on request.
46
42
CONTACT ARRANGEMENTS
Single
Double
8 1
8 1
5 4
5 4
I n/o + I n/c
I n/o + I n/c
Single
Single
8 1
8
1
5
4
5 4
2n/c
2n/o
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
86
EEx edm Control Functions
Type CF - EEx em LED Indicators
EEx em IIC
Zones 1,2,21,22
EEx edm Control Functions
Type CF - EEx e Ammeters
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Light source
EEx e II
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
II 2 G
EEx em II T6
-40˚C to +50˚C
Zones 1,2,21,22 . Groups IIA, IIB, IIC
SIRA04ATEX5056U
LED cluster
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Terminal capacity
II 2 G
EEx e II T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
SIRA02ATEX3380U
2.5mmsq
ENCLOSURE SPECIFICATION
Dimensions
Material
Weight
Contact
42mm x 42mm x 82mm
GRP
0.04 Kgs
Silver (gold optional)
ELECTRICAL SPECIFICATION
ELECTRICAL SPECIFICATION
Operating voltage
Operating current
Terminal Capacity
Max power diss.
AC 24-230 - 5% + 10%
0.005 Amps
2.5mmsq
1.2 Watts
Standard Meter Scales
Direct Operated
0 - 2 - 12 amps
0 - 5 - 30 amps
0 - 10 - 60 amps
4
Operated from current transformer with 1 amp secondary
0 - 60 - 360 amps
0 - 1 - 60 amps
0 - 80 - 480 amps
0 - 15 - 90 amps
0 - 100 - 600 amps
0 - 20 - 120 amps
0 - 150 - 900 amps
0 - 30 - 80 amps
0 - 200 - 1200 amps
0 - 40 - 240 amps
0 - 50 - 300 amps
ORDERING INFORMATION
82
Description
Ammeter
42
Scale
To be Specified
Product Code
CF38
EEx de Control Functions
Type MCBD/RCDD - EEx de MCB’s and RCD’s
OUTLINE SPECIFICATION
Marking to 94/9/EC
Type of protection
Area classification
Certification No.
MCB
ORDERING INFORMATION
Description
Indicator Lamp
Indicator Lamp
Indicator Lamp
Indicator Lamp
Indicator Lamp
87
II 2 G
EEx de II T6
Zones 1,2,21,22 . Groups IIA, IIB, IIC.
TBA
Colour
Red
Green
Amber
White
Blue
Product Code
CF33
CF34
CF35
CF36
CF37
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Terminal cross section Main 2 x 10mmsq
Rating
16 - 40Amps
Number of poles
2 or 3
RCD
Terminal cross section
Tripping current RCD
Rating
Number of poles
Main 2 x 10mmsq
30mA
25 - 63Amps
2 or 3
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
88
Local Control Station - Glass Reinforced Polyester Enclosure
Type LCP100 - EEx de 16 amp General Purpose Switch
PART 2.2
LCP RANGE
EEx de IIC
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Standard and customised EEx edm Local Control Stations in Glass
Reinforced Polyester Enclosures. The LCP Range offers very robust
local control stations. The minimum wall thickness of the enclosures is
6mm and all the actuators are metal clad with nickle plated brass
housings.
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
II 2 GD
EEx de II C T6
-40˚C to +50˚C
Zones 1,2,21,22 . Groups IIA, IIB, IIC
SIRA03ATEX3293 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
Standard Control Stations
Type LCP100 – 16amp General Purpose Switch
Page 90
Type LCP110 – Pushbutton
Page 91
Type LCP120 – Mushroom Pushbutton
Page 92
Type LCP130 – Emergency Pushbutton
Page 93
Type LCP140 – Position and Control Switch
Page 94
Type LCP150 – LED Indicator Lamp
Page 95
Type LCP160 – Ammeter
Page 96
Type LCP170 – Double Pushbuttons
Page 97
Type LCP180 – Double Pushbuttons
Page 98
Customised Control Stations
Type LCP200 – 2 Function Customised Control Stations
Page 99
Dimensions
Material
Finish
Weight
Cover fixing
Gasket
Security
Earthing
Mounting
110mm x 110mm x 125mm
Carbon loaded anti-static glass reinforced polyester UL94/V0
Moulded black
1.2 Kg
M6 allen head stainless steel screws
1.2 mm one piece solid nitrile rubber
Switches with an off position have a padlock ‘off’ ‘facility
as standard
Internal EEx e brass clamps on base
Through 7mm holes moulded into base
ENTRY SPECIFICATION
1x20mm EEx e threaded entry in base at A as standard.
The entry is fitted with a 20mm EEx e cable gland as standard.
25mm entries are available as an option.
ELECTRICAL SPECIFICATION
Type LCP300 – 3 Function Customised Control Stations Page 100
Walsall EEx de IIC switch. Certification No. SIRA 03ATEX1269U
Operating Voltage
Volts
230-270
Operating Current
Amps
16
Conductor Size
mmsq. Max
2.5
All Dimensions in mm
ORDERING INFORMATION
Description
Double pole off/on
Double pole changeover
Single pole changeover
Notes 1
2
3
89
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Action
Engage- Engage
Engage- Engage
Engage- Engage- Engage
20º
90º
20º
90º
20º
90º
160º
Contacts
Labelling
1-3 2-4 5-7 6-8
0 -
I
Off - On
1-3 2-4 5-7 6-8
1-3 2-4 5-7 6-8
Product Code
LCP101
LCP102
I
- II
LCP103
I
- 2
LCP104
I - 0 - II
LCP105
I -0- 2
LCP106
For 25 mm entries add/25 to Product Code e.g. LCP103/25
Alternative labelling to order.
Alternative handle colour to order.
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
90
Local Control Station - Glass Reinforced Polyester Enclosure
Type LCP110 - EEx de Single Pushbutton
EEx de IIC
Zones 1,2,21,22
T6
Group II Cat 2
Local Control Station - Glass Reinforced Polyester Enclosure
Type LCP120 - EEx de Single Mushroom Pushbutton
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No
Ingress protection
II 2 GD
EEx de IIC T6
-40˚C to +50˚C
Zones 1,2,21,22 . Groups IIA, IIB, IIC
SIRA99ATEX3199 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No
Ingress protection
T6
Group II Cat 2
ATEX/GOST
II 2 GD
EEx de IIC T6
-40˚C to +50˚C
Zones 1,2,21,22 . Groups IIA, IIB, IIC
SIRA03ATEX3293 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
110mm x 110mm x 113mm
Carbon loaded Glass reinforced polyester UL94/V0
Moulded black
1.2 Kg
M6 pan head stainless steel screws
1.2mm one piece solid nitrile rubber
Internal EEx e brass clamps on base
Through 7mm holes fixing strap
Dimensions
Material
Finish
Weight
Cover fixing
Gasket
Earthing
Mounting
ENTRY SPECIFICATION
110mm x 110mm x 121mm
Carbon loaded anti-static Glass reinforced polyester UL94/V0
Moulded black
1.2 Kg
M6 allen head stainless steel screws
1.2 mm one piece solid nitrile rubber
Internal EEx e brass clamps on base
Through 7mm holes moulded into base
ENTRY SPECIFICATION
1x20mm EEx e threaded hole base at A as standard
The entry is fitted with a 20mm EEx e cable gland as standard
25mm entries are available as an option
1x20mm EEx e threaded hole base at A as standard.
The entry is fitted with a 20mm EEx e cable gland as standard.
25mm entries are available as an option.
ELECTRICAL SPECIFICATION
ELECTRICAL SPECIFICATION
Walsall EEx de IIC contact block. Certification No. SIRA 03ATEX1269U
Operating Voltage
Volts
230-270
Zones 1,2,21,22
HAZARDOUS AREA SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Weight
Cover fixing
Gasket
Earthing
Mounting
EEx de IIC
Operating Current
Amps
16
Walsall EEx de IIC contact block. Certification No. SIRA 03ATEX1269U.
Conductor Size
mmsq. Max
2.5
Operating Voltage
Volts
230-270
Operating Current
Amps
16
Conductor Size
mmsq. Max
2.5
All Dimensions in mm
All Dimensions in mm
ORDERING INFORMATION
ORDERING INFORMATION
Description
Green Pushbutton
Description
Action
Contacts
8 1
8 1
91
Red Mushroom Pushbutton
Action
start
LCP112
I
LCP113
stop
LCP114
For 25 mm entries add/25 to Product Code e.g. LCP113/25
Alternative labelling to order.
Alternative button colours to order.
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Red Mushroom Pushbutton
Red Mushroom Pushbutton
Notes 1
2
3
Contacts
Labelling
Product Code
8 1
I
LCP121
5 4
Stop
LCP122
8 1
I
LCP123
5 4
Stop
LCP124
8 1
I
LCP125
5 4
Stop
LCP126
Spring
LCP111
Spring
5 4
Notes 1
2
3
0
Product Code
Spring
5 4
Red Pushbutton
Labelling
Pull release
Key release
For 25 mm entries add/25 to Product Code e.g. LCP123/25
Alternative labelling to order.
Alternative button colours to order.
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
92
Local Control Station - Glass Reinforced Polyester Enclosure
Type LCP130 - EEx de Single Emergency Pushbutton
EEx de IIC
Zones 1,2,21,22
T6
Group II Cat 2
Local Control Station - Glass Reinforced Polyester Enclosure
Type LCP140 - EEx de Position and Control Switch
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No
Ingress protection
II 2 GD
EEx de IIC T6
-40˚C to +50˚C
Zones 1,2,21,22 . Groups IIA, IIB, IIC
SIRA03ATEX3293 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No
Ingress protection
T6
Group II Cat 2
ATEX/GOST
II 2 GD
EEx de IIC T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
SIRA03ATEX3293 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
110mm x 110mm x 121mm
Carbon loaded anti-static Glass reinforced polyester UL94/V0
Moulded black
1.2 Kg
M6 allen head stainless steel screws
1.2 mm one piece solid nitrile rubber
Internal EEx e brass clamps on base
Through 7mm holes moulded into base
Dimensions
Material
Finish
Weight
Cover fixing
Gasket
Earthing
Mounting
ENTRY SPECIFICATION
110mm x 110mm x 123mm
Carbon loaded anti-static Glass reinforced polyester UL94/V0
Moulded black
1.2 Kg
M6 allen head stainless steel screws
1.2 mm one piece solid nitrile rubber
Internal EEx e brass clamps on base
Through 7mm holes moulded into base
ENTRY SPECIFICATION
1x20mm EEx e threaded hole base at A as standard
The entry is fitted with a 20mm EEx e cable gland as standard
25mm entries are available as an option
1x20mm EEx e threaded hole base at A as standard.
The entry is fitted with a 20mm EEx e cable gland as standard.
25mm entries are available as an option.
ELECTRICAL SPECIFICATION
ELECTRICAL SPECIFICATION
Walsall EEx de IIC switch. Certification No. SIRA 03ATEX1269U.
Walsall EEx de IIC contact block. Certification No. SIRA 03ATEX1269U
Operating Voltage
Volts
230-270
Zones 1,2,21,22
HAZARDOUS AREA SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Weight
Cover fixing
Gasket
Earthing
Mounting
EEx de IIC
Operating Current
Amps
16
Voltage
Volts
230-270
Conductor Size
mmsq. Max
2.5
Current
Amps
16
Conductor Size
mmsq. Max
2.5
All Dimensions in mm
ORDERING INFORMATION
All Dimensions in mm
Engage - Engage
20º
90º
Engage - Engage - Engage
20º
90º
160º
Action
Contacts
Labelling
3 Position Switch
with centre off
Product Code
3 Position Switch
with centre off
8 1
Red Mushroom Pushbutton
Action
3 Position Switch
with centre off
ORDERING INFORMATION
Description
Description
2 Position Switch
Emergency stop
Pull release
LCP131
5 4
3 Position Control Switch
Contacts
Engage - Engage - Spring
20º
90º
160º
Spring - Engage - Spring
20º
90º
160º
Spring - Engage - Spring
20º
90º
160º
Spring - Engage - Spring
20º
90º
160º
8 1
Red Mushroom Pushbutton
Emergency stop
Key release
LCP132
3 Position Control Switch
5 4
Note For 25 mm entries add/25 to Product Code e.g. LCP132/25
3 Position Control Switch
Notes 1
2
3
93
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Spring - Engage - Spring
20º
90º
160º
1-3 2-4 5-7 6-8
Labelling
0 -
Product Code
I
LCP141
I - 0 - II
LCP142
I - 0 - II
LCP143
I - 0 - II
LCP144
I - 0 - II
LCP145
I - 0 - II
LCP146
I - 0 - II
LCP147
1-3 2-4 5-7 6-8
1-3 2-4 5-7 6-8
1-3 2-4 5-7 6-8
1-3 2-4 5-7 6-8
1-3 2-4 5-7 6-8
1-3 2-4 5-7 6-8
For 25 mm entries add/25 to Product Code e.g. LCP141/25
Alternative labelling to order.
Add “K” to 2 position switch for key lock version.
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
94
Local Control Station - Glass Reinforced Polyester Enclosure
Type LCP150 - EEx em LED Indicator lamp
EEx em IIC
Zones 1,2,21,22
T6
Group II Cat 2
Local Control Station - Glass Reinforced Polyester Enclosure
Type LCP160 - EEx e Ammeter
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
II 2 G
EEx em IIC T6
-40˚C to + 50˚C
Zones 1,2,21,22 . Groups IIA, IIB, IIC
SIRA03ATEX3293 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Weight
Cover fixing
Gasket
Earthing
Mounting
EEx e II
II 2 GD
EEx e II T6
-40˚C to +50˚C
Zones 1,2,21,22 . Groups IIA, IIB, IIC
SIRA03ATEX3293 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
110mm x 110mm x 113mm
Carbon loaded anti-static Glass reinforced polyester UL94/V0
Moulded black
1.2 Kg
M6 allen head stainless steel screws
1.2mm one piece solid nitrile rubber
Internal EEx e brass clamps on base
Through 7mm holes moulded into base
Dimensions
Material
Finish
Weight
Cover fixing
Gasket
Earthing
Mounting
ENTRY SPECIFICATION
110mm x 110mm x 99mm
Carbon loaded anti-static Glass reinforced polyester UL94/V0
Moulded black
1.2 Kg
M6 allen head stainless steel screws
1.2 mm one piece solid nitrile rubber
Internal EEx e brass clamps on base
Through 7mm holes moulded into base
ENTRY SPECIFICATION
1x20mm EEx e threaded hole base at A as standard
The entry is fitted with a 20mm EEx e cable gland as standard
25mm entries are available as an option
1x20mm EEx e threaded hole base at A as standard.
The entry is fitted with a 20mm EEx e cable gland as standard.
25mm entries are available as an option.
ELECTRICAL SPECIFICATION
ELECTRICAL SPECIFICATION
Walsall EEx em IIC indicator lamp. Certification No. SIRA 04ATEX5056U
Voltage AC and DC
Volts (AC-5% +10%)
24 - 240
Current
Amps
0.005
Walsall EEx e II ammeter. Certification No. SIRA 02ATEX3380U.
Conductor Size
mmsq. Max
2.5
Voltage
Volts
240
All Dimensions in mm
Direct Operated
0 - 2 - 12 amps
0 - 5 - 30 amps
0 - 10 - 60 amps
Current
Amps
16
Conductor Size
mmsq. Max
2.5
Standard Meter Scales
Operated from current transformer with 1 amp secondary
0 - 60 - 360 amps
0 - 10 - 60 amps
0 - 80 - 480 amps
0 - 15 - 90 amps
0 - 100 - 600 amps
0 - 20 - 120 amps
0 - 150 - 900 amps
0 - 30 - 180 amps
0 - 200 - 1200 amps
0 - 40 - 240 amps
0 - 50 - 300 amps
All Dimensions in mm
ORDERING INFORMATION
Description
Green Indicator Lamp
Red Indicator Lamp
Amber Indicator Lamp
Clear Indicator Lamp
Blue Indicator Lamp
Product Code
LCP151
LCP152
LCP153
LCP154
LCP155
ORDERING INFORMATION
Description
Ammeter
Note For 25 mm entries add/25 to Product Code e.g. LCP160/25
Scale
To Be Specified
Product Code
LCP160
Note For 25 mm entries add/25 to Product Code e.g. LCP151/25
95
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
96
Local Control Station - Glass Reinforced Polyester Enclosure
Type LCP170 - EEx de Double Green and Red Pushbuttons
EEx de IIC
Zones 1,2,21,22
T6
Group II Cat 2
Local Control Station - Glass Reinforced Polyester Enclosure
Type LCP180 - EEx de Double Green and Mushroom Red Pushbuttons
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
II 2 GD
EEx de IIC T6
-40˚C to +50˚C
Zones 1,2,21,22 . Groups IIA, IIB, IIC
SIRA03ATEX3293 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No
Ingress protection
T6
Group II Cat 2
ATEX/GOST
II 2 GD
EEx de IIC T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
SIRA03ATEX3293 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
110mm x 110mm x 113mm
Carbon loaded anti-static Glass reinforced polyester UL94/V0
Moulded black
1.2 Kg
M6 allen head stainless steel screws
1.2mm one piece solid nitrile rubber
Internal EEx e brass clamps on base
Through 7mm holes moulded into base
Dimensions
Material
Finish
Weight
Cover fixing
Gasket
Earthing
Mounting
ENTRY SPECIFICATION
110mm x 110mm x 121mm
Carbon loaded anti-static Glass reinforced polyester UL94/V0
Moulded black
1.2 Kg
M6 allen head stainless steel screws
1.2mm one piece solid nitrile rubber
Internal EEx e brass clamps on base
Through 7mm holes moulded into base
ENTRY SPECIFICATION
1x20mm EEx e threaded hole base at A as standard
The entry is fitted with a 20mm EEx e cable gland as standard
25mm entries are available as an option
1x20mm EEx e threaded hole base at A as standard.
The entry is fitted with a 20mm EEx e cable gland as standard.
25mm entries are available as an option.
ELECTRICAL SPECIFICATION
ELECTRICAL SPECIFICATION
Walsall EEx de IIC contact block. Certification No. SIRA 03ATEX1269U
Voltage
Volts
240
Zones 1,2,21,22
HAZARDOUS AREA SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Weight
Cover fixing
Gasket
Earthing
Mounting
EEx de IIC
Current
AC21A(A)
16
Walsall EEx de IIC contact block. Certification No. SIRA 03ATEX1269U.
Conductor Size
mmsq. Max
2.5
Voltage
Volts
230-270
Current
AC21A(A)
16
Conductor Size
mmsq. Max
2.5
All Dimensions in mm
All Dimensions in mm
ORDERING INFORMATION
Description
Action
Contacts
8
Green Pushbutton
Spring
5
ORDERING INFORMATION
Description
Action
8
Contacts
Description
Action
8
Green Pushbutton
Red Pushbutton
Spring
5
Notes 1
2
3
97
Contact
labelling
Product Code
1
0 - I
LCP171
4
Stop - Start
LCP172
Spring
For 25 mm entries add/25 to Product Code e.g. LCP171/25
Alternative labelling to order.
Alternative button colours to order.
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Green Pushbutton
Spring
5
8
Green Pushbutton
Spring
5
Notes 1
2
3
Description
Red Mushroom
Pushbutton
Red Mushroom
Pushbutton
Red Mushroom
Pushbutton
Action
Contact
1
Spring
4
1
Pull Release
4
1
Key Ralease
4
labelling
Product Code
0 - I
LCP181
Stop - Start
LCP182
0 - I
LCP183
Stop - Start
LCP184
0 - I
LCP185
Stop - Start
LCP186
For 25 mm entries add/25 to Product Code e.g. LCP181/25
Alternative labelling to order.
Alternative button colours to order.
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
98
Customised Local Control Stations - Glass Reinforced Polyester Enclosure
Type LCP200 - EEx edm Two Function Customised Control Stations
EEx edm IIC
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
II 2 GD
EEx e, ed, em IIC T6
-40˚C to +50˚C
Zones 1,2,21,22 . Groups IIA, IIB, IIC
SIRA03ATEX3293. POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
Dimensions
Material
Finish
Weight
Cover fixing
Gasket
Security
Base
II 2 GD
EEx e, ed, em IIC T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
SIRA03ATEX3293. POCC. GB. гБ 05.BO1132
IP66 to EN60529:1991
CONTROL FUNCTIONS
As listed on pages 83 to 88
As listed on pages 83 to 88
ELECTRICAL SPECIFICATION
ELECTRICAL SPECIFICATION
230 – 270 Volts
16 Amps max
2.5mm sq. max
Operating Voltage
Operating Current
Terminal Capacity
ORDERING INFORMATION
230 – 270 Volts
16 Amps max
2.5mm sq. max
ORDERING INFORMATION
The first function specified in the order code occupies position X in the enclosure
and the second function position Y.
The first function specified in the order code occupies position X in the
enclosure, the second function Y and the third function position Z.
Ordering codes are built up as shown in the following examples.
Ordering codes are built up as shown in the following examples.
Example 1 Ammeter plus 2 pole changeover switch.
Example 1 Emergency stop with pull release plus green start plus green
indicator lamp
Product Code: LCP200 + CF37 + CF2
Product Code: LCP300 + CF26 + CF11 + CF34
Example 2 On/Off switch plus green indicator lamp.
Example 2 Double green and red pushbutton plus red indicator plus mushroom
pushbutton.
Product Code: LCP200 + CF1 + CF34
1. Labelling to be specified by customer.
2. For 25mm entries add /25 to enclosure code e.g. LCP200/25 + CF37 + CF2
Product Code: LCP300 + CF32 + CF33+ CF17
1. Labelling to be specified by customer.
2. For 25mm entries add /25 to enclosure code e.g. LCP300/25 + CF26 + CF11
+ CF34
ENCLOSURE INTERCONNECTIONS
1,2 and 3 function local control stations can be connected together to engineer
more complex systems. The interconnection is made via a specially approved
gland manufactured by Walsall Ltd.
ENCLOSURE INTERCONNECTIONS
All Dimensions in mm
99
ATEX/GOST
1x20mm EEx e threaded hole base at A as standard.
The entry is fitted with a 20mm EEx e cable gland as standard.
25mm entries are available as an option.
3 x entries maximum as required by control functions specified.
Cover
CONTROL FUNCTIONS
Operating Voltage
Operating Current
Terminal Capacity
Group II Cat 1,2,3
ENTRY SPECIFICATION
1x20mm EEx e threaded hole base at A as standard
The entry is fitted with a 20mm EEx e cable gland as standard
25mm entries are available as an option
2 x entries maximum as required by control functions specified
Cover
T6
220mm x 110mm
Carbon loaded anti-static Glass reinforced polyester UL94/V0
Moulded black
1.2 Kg
M6 allen head stainless steel screws
1.2 mm one piece solid nitrile rubber
Switches with an off position have a padlock ‘off’ ‘facility
as standard
Internal EEx e brass clamps on base
Through 7mm holes moulded into base
Earthing
Mounting
ENTRY SPECIFICATION
Base
Zones 1,2,21,22
ENCLOSURE SPECIFICATION
220mm x 110mm
Carbon loaded anti-static Glass reinforced polyester UL94/V0
Moulded black
1.2 Kg
M6 allen head stainless steel screws
1.2mm one piece solid nitrile rubber
Switches with an off position have a padlock ‘off’ ‘facility
as standard
Internal EEx e brass clamps on base
Through 7mm holes moulded into base
Earthing
Mounting
EEx edm IIC
HAZARDOUS AREA SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Weight
Cover fixing
Gasket
Security
Customised Local Control Stations - Glass Reinforced Polyester Enclosure
Type LCP300 - EEx edm Three Function Customised Control Stations
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
1,2 and 3 function local control stations can be connected together to engineer more
complex systems. The interconnection is made via a specially approved gland
manufactured by Walsall Ltd.
All Dimensions in mm
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
100
Local Control Station - Stainless Steel Enclosure
Type LCS100 - EEx de 16 amp General Purpose Switch
PART 2.3
LCS RANGE
EEx de IIC
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Standard and Customised EEx edm Local Control Stations in
Stainless Steel Enclosures.The LCS Range offers very robust local
control stations in fabricated stainless steel enclosures. All the
actuators are metal clad with nickel plated brass housings.
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
II 2 GD
EEx de II C T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC.
SIRA99ATEX3199 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
Standard Control Stations
Type LCS100 – 16amp General Purpose Switch
Page 102
Type LCS110 – Pushbutton
Page 103
Type LCS120 – Mushroom Pushbutton
Page 104
Type LCS130 – Emergency Pushbutton
Page 105
Type LCS140 – Position and Control Switch
Page 106
Type LCS150 – LED Indicator Lamp
Page 107
Type LCS160 – Ammeter
Page 108
ENCLOSURE SPECIFICATION
Dimensions
Material box
Finish
Weight empty
Cover fixing
Gasket
Earthing
Entries
External Mounting
110mm x 110mm x 152mm
1.5mm 316L, (1.4404) stainless
Stainless steel – electropolished
1.2Kg
Captive M6 stainless steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
6mm brass internal/external earth stud as standard
Optional brass earth stud welded to cover
Direct through body
External lugs with 8mm clearance
Customised Control Stations
Type LCS200 – 2 Function Customised Control Stations Page 109
Type LCS300 – 3 Function Customised Control Stations Page 110
ENTRY SPECIFICATION
1x20mm EEx e threaded hole base at A as standard.
The entry is fitted with a 20mm EEx e cable gland as standard.
25mm entries are available as an option.
ELECTRICAL SPECIFICATION
Walsall EEx de IIC switch. Certification No. SIRA 03ATEX1269U
Operating Voltage
Volts
230-270
Operating Current
AC21A(A)
16
Conductor Size
mmsq. Max
2.5
All Dimensions in mm
ORDERING INFORMATION
Description
Double pole off/on
Double pole changeover
Single pole changeover
Notes 1
2
101
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Action
Engage- Engage
Engage- Engage
Engage- Engage- Engage
20º
90º
20º
90º
20º
90º
160º
Contacts
Labelling
1-3 2-4 5-7 6-8
0 -
I
Off - On
1-3 2-4 5-7 6-8
1-3 2-4 5-7 6-8
Product Code
LCS101
LCS102
I
- II
LCS103
I
- 2
LCS104
I - 0 - II
LCS105
I -0- 2
LCS106
For 25 mm entries add/25 to Product Code e.g. LCS103/25
Alternative labelling to order.
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
102
Local Control Station - Stainless Steel Enclosure
Type LCS110 - EEx de Pushbutton
EEx de IIC
Zones 1,2,21,22
T6
Local Control Station - Stainless Steel Enclosure
Type LCS120 - EEx de Mushroom Pushbutton
Group II Cat 2
ATEX/GOST
II 2 GD
EEx de IIC T6
-40˚C to +50˚C
Zones 1,2,21,22 . Groups IIA, IIB, IIC
SIRA99ATEX3199 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No
Ingress protection
ENCLOSURE SPECIFICATION
Dimensions
Material box
Finish
Weight empty
Cover fixing
Gasket
Earthing
Entries
External Mounting
T6
Group II Cat 2
ATEX/GOST
II 2 GD
EEx de IIC T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
SIRA99ATEX3199 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
110mm x 110mm x 139mm
1.5mm 316L, (1.4404) stainless
Stainless steel – electropolished
1.2Kg
Captive M6 stainless steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
6mm brass internal/external earth stud as standard
Optional brass earth stud welded to cover
Direct through body
External lugs with 8mm clearance
Dimensions
Material box
Finish
Weight empty
Cover fixing
Gasket
Earthing
Entries
External Mounting
ENTRY SPECIFICATION
110mm x 110mm x 146mm
1.5mm 316L, (1.4404) stainless
Stainless steel – electropolished
1.2Kg
Captive M6 stainless steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
6mm brass internal/external earth stud as standard
Optional brass earth stud welded to cover
Direct through body
External lugs with 8mm clearance
ENTRY SPECIFICATION
1x20mm EEx e threaded hole base at A as standard
The entry is fitted with a 20mm EEx e cable gland as standard
25mm entries are available as an option
1x20mm EEx e threaded hole base at A as standard.
The entry is fitted with a 20mm EEx e cable gland as standard.
25mm entries are available as an option.
ELECTRICAL SPECIFICATION
ELECTRICAL SPECIFICATION
Walsall EEx de IIC contact block. Certification No. SIRA 03ATEX1269U
Operating Voltage
Volts
230-270
Zones 1,2,21,22
HAZARDOUS AREA SPECIFICATION
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No
Ingress protection
EEx de IIC
Operating Current
AC21A(A)
16
Walsall EEx de IIC contact block. Certification No. SIRA 03ATEX1269U.
Operating Voltage
Volts
230-270
Conductor Size
mmsq. Max
2.5
Operating Current
AC21A(A)
16
Conductor Size
mmsq. Max
2.5
All Dimensions in mm
All Dimensions in mm
ORDERING INFORMATION
ORDERING INFORMATION
Description
Green Pushbutton
Description
Action
Contacts
8 1
8 1
103
0
LCS111
start
I
LCS112
Red Mushroom Pushbutton
Action
stop
Red Mushroom Pushbutton
LCS114
For 25 mm entries add/25 to Product Code e.g. LCS112/25
Alternative labelling to order
Alternative button colours to order
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Red Mushroom Pushbutton
Notes 1
2
3
Contacts
Labelling
Product Code
8 1
I
LCS121
5 4
Stop
LCS122
8 1
I
LCS123
5 4
Stop
LCS124
8 1
I
LCS125
5 4
Stop
LCS126
Spring
Pull release
LCS113
Spring
5 4
Notes 1
2
3
Product Code
Spring
5 4
Red Pushbutton
Labelling
Key release
For 25 mm entries add/25 to Product Code e.g. LCS121/25
Alternative labelling to order.
Alternative button colours to order.
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
104
Local Control Station - Stainless Steel Enclosure
Type LCS130 - EEx de Emergency Pushbutton
EEx de IIC
Zones 1,2,21,22
T6
Local Control Station - Stainless Steel Enclosure
Type LCS140 - EEx de Position and Control Switch
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No
Ingress protection
EEx de IIC
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
II 2 GD
EEx de IIC T6
-40˚C to + 50˚C
Zones 1,2,21,22 . Groups IIA, IIB, IIC
SIRA99ATEX3199 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No
Ingress protection
II 2 GD
EEx de IIC T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
SIRA99ATEX3199 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material box
Finish
Weight empty
Cover fixing
Gasket
Earthing
Entries
External Mounting
Dimensions
Material box
Finish
Weight empty
Cover fixing
Gasket
Earthing
110mm x 110mm x 146mm
1.5mm 316L, (1.4404) stainless
Stainless steel – electropolish
1.2Kg
Captive M6 stainless steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
6mm brass internal/external earth stud as standard
Optional brass earth stud welded to cover
Direct through body
External lugs with 8mm clearance
Entries
External Mounting
110mm x 110mm x 148`mm
1.5mm 316L, (1.4404) stainless
Stainless steel – electropolished
1.2Kg
Captive M6 stainless steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
6mm brass internal/external earth stud as standard
Optional brass earth stud welded to cover
Direct through body
External lugs with 8mm clearance
ENTRY SPECIFICATION
1x20mm EEx e threaded hole base at A as standard.
The entry is fitted with a 20mm EEx e cable gland as standard.
25mm entries are available as an option.
ENTRY SPECIFICATION
1x20mm EEx e threaded hole base at A as standard
The entry is fitted with a 20mm EEx e cable gland as standard
25mm entries are available as an option
ELECTRICAL SPECIFICATION
Walsall EEx de IIC switch. Certification No. SIRA 03ATEX1269U.
ELECTRICAL SPECIFICATION
Voltage
Volts
230-270
Walsall EEx de IIC contact block. Certification No. SIRA 03ATEX1269U
Current
AC21A(A)
16
Conductor Size
mmsq. Max
2.5
All Dimensions in mm
Operating Voltage
Volts
230-270
Operating Current
AC21A(A)
16
Conductor Size
mmsq. Max
2.5
ORDERING INFORMATION
All Dimensions in mm
Engage - Engage
20º
90º
Engage - Engage - Engage
20º
90º
160º
Action
Contacts
Labelling
3 Position Switch
with centre off
Product Code
3 Position Switch
with centre off
8 1
Red Mushroom Pushbutton
Action
3 Position Switch
with centre off
ORDERING INFORMATION
Description
Description
2 Position Switch
Emergency stop
Pull release
LCS131
5 4
3 Position Control Switch
Contacts
Engage - Engage - Spring
20º
90º
160º
Spring - Engage - Spring
20º
90º
160º
Spring - Engage - Spring
20º
90º
160º
Spring - Engage - Spring
20º
90º
160º
8 1
Red Mushroom Pushbutton
Emergency stop
Key release
LCS132
3 Position Control Switch
5 4
Note For 25 mm entries add/25 to Product Code e.g. LCS131/25
3 Position Control Switch
Notes 1
2
3
4
105
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Spring - Engage - Spring
20º
90º
160º
1-3 2-4 5-7 6-8
Labelling
0 -
Product Code
I
LCS141
I - 0 - II
LCS142
I - 0 - II
LCS143
I - 0 - II
LCS144
I - 0 - II
LCS145
I - 0 - II
LCS146
I - 0 - II
LCS147
1-3 2-4 5-7 6-8
1-3 2-4 5-7 6-8
1-3 2-4 5-7 6-8
1-3 2-4 5-7 6-8
1-3 2-4 5-7 6-8
1-3 2-4 5-7 6-8
For 25 mm entries add/25 to Product Code e.g. LCS141/25
Alternative labelling to order.
Alternative handle colours to order.
Add “K” to 2 position switch for key lock version.
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
106
Local Control Station - Stainless Steel Enclosure
Type LCS150 - EEx em LED Indicator lamp
EEx em IIC
Zones 1,2,21,22
T6
Local Control Station - Stainless Steel Enclosure
Type LCS160 - EEx e Ammeter
Group II Cat 2
ATEX/GOST
II 2 G
EEx em IIC T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
SIRA99ATEX3199 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
ENCLOSURE SPECIFICATION
Dimensions
Material box
Finish
Weight empty
Cover fixing
Gasket
Earthing
Entries
External Mounting
T6
Group II Cat 2
ATEX/GOST
II 2 GD
EEx e II T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
SIRA99ATEX3199 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
110mm x 110mm x 137mm
1.5mm 316L, (1.4404) stainless
Stainless steel – electropolished
1.2Kg
Captive M6 stainless steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
6mm brass internal/external earth stud as standard
Optional brass earth stud welded to cover
Direct through body
External lugs with 8mm clearance
Dimensions
Material box
Finish
Weight empty
Cover fixing
Gasket
Earthing
Entries
External Mounting
110mm x 110mm x 133mm
1.5mm 316L, (1.4404) stainless
Stainless steel – electropolished
1.2Kg
Captive M6 stainless steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
6mm brass internal/external earth stud as standard
Optional brass earth stud welded to cover
Direct through body
External lugs with 8mm clearance
ENTRY SPECIFICATION
ENTRY SPECIFICATION
1x20mm EEx e threaded hole base at A as standard.
The entry is fitted with a 20mm EEx e cable gland as standard.
25mm entries are available as an option.
1x20mm EEx e threaded hole base at A as standard
The entry is fitted with a 20mm EEx e cable gland as standard
25mm entries are available as an option
ELECTRICAL SPECIFICATION
ELECTRICAL SPECIFICATION
Walsall EEx e II ammeter Certification No. SIRA 02ATEX3380U.
Walsall EEx em IIC indicator lamp. Certification No. SIRA 04ATEX5056U
Voltage AC and DC
Volts (AC-5%+10%)
24 - 230
Zones 1,2,21,22
HAZARDOUS AREA SPECIFICATION
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
EEx e II
Current
AC21A(A)
0.005
Conductor Size
mmsq. Max
2.5
Voltage
Volts
240
All Dimensions in mm
Direct Operated
0 - 2 - 12 amps
0 - 5 - 30 amps
0 - 10 - 60 amps
Current
AC21A(A)
16
Conductor Size
mmsq. Max
2.5
Standard Meter Scales
Operated from current transformer with 1 amp secondary
0 - 60 - 360 amps
0 - 10 - 60 amps
0 - 80 - 480 amps
0 - 15 - 90 amps
0 - 100 - 600 amps
0 - 20 - 120 amps
0 - 150 - 900 amps
0 - 30 - 180 amps
0 - 200 - 1200 amps
0 - 40 - 240 amps
0 - 50 - 300 amps
All Dimensions in mm
ORDERING INFORMATION
Notes 1
107
Description
Green Indicator Lamp
Red Indicator Lamp
Amber Indicator Lamp
Clear Indicator Lamp
Blue Indicator Lamp
For 25 mm entries add/25 to Product Code e.g. LCS151/25
Product Code
LCS151
LCS152
LCS153
LCS154
LCS155
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
ORDERING INFORMATION
Note 1
Current Rating
Ammeter
For 25 mm entries add/25 to Product Code e.g. LCS160/25
Scale
To Be Specified
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Product Code
LCS160
108
Customised Local Control Stations - Stainless Steel Enclosure
Type LCS200 - EEx edm Two Function Customised Control Stations
EEx edm IIC
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
External Mounting
Internal Mounting
II 2 GD
EEx e, ed, em IIC T6
-40˚C to + 50˚C
Zones 1,2,21,22 . Groups IIA, IIB, IIC
SIRA03ATEX3293. POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
165mm x 110mm
1.5mm 316L, (1.4404) stainless or mild steel
Stainless steel – electropolished
1.2Kg
Captive M6 stainless steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
10mm brass internal/external earth stud as standard
Optional brass earth stud welded to cover
External lugs with 10mm clearance
Optional mounting plate to suit
Dimensions
Material box
Finish
Weight empty
Cover fixing
Gasket
Earthing
External Mounting
Internal Mounting
Base
230mm x 110mm
1.5mm 316L, (1.4404) stainless or mild steel
Stainless steel – electropolished
1.2Kg
Captive M6 stainless steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
10mm brass internal/external earth stud as standard
Optional brass earth stud welded to cover
External lugs with 10mm clearance
Optional mounting plate to suit
ELECTRICAL SPECIFICATION
230 – 270 Volts
16 Amps max
2.5mm sq. max
Operating Voltage
Operating Current
Terminal Capacity
ORDERING INFORMATION
230 – 270 Volts
16 Amps max
2.5mm sq. max
ORDERING INFORMATION
The first function specified in the order code occupies position X in the enclosure
and the second function position Y.
The first function specified in the order code occupies position X in the
enclosure, the second function Y and the third function position Z.
Ordering codes are built up as shown in the following examples.
Ordering codes are built up as shown in the following examples.
Ammeter plus 2 pole changeover switch.
Example 1 Emergency stop with pull release plus green start plus green
indicator lamp
Product Code: LCS200 + CF12 + CF7
Product Code: LCS300 + CF12 + CF7 + CF35
On/Off switch plus green indicator lamp.
Example 2 Double green and red pushbutton plus red indicator plus mushroom
pushbutton.
Product Code: LCS200 + CF25
1. Labelling to be specified by customer.
2. For 25mm entries add /25 to enclosure code e.g. LCS200/25 + CF12 + CF7
Product Code: LCS300 + CF25 + CF31+ CF10
1. Labelling to be specified by customer.
2. For 25mm entries add /25 to enclosure code e.g. LCS300/25 + CF12 + CF7
+ CF35
ENCLOSURE INTERCONNECTIONS
1,2 and 3 function local control stations can be connected together to engineer more
complex systems. The interconnection is made via a specially approved gland
manufactured by Walsall Ltd.
ENCLOSURE INTERCONNECTIONS
All Dimensions in mm
109
II 2 GD
EEx e, ed, em IIC T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
SIRA03ATEX3293. POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
As listed on pages 83 - 88
ELECTRICAL SPECIFICATION
Example 2
ATEX/GOST
CONTROL FUNCTIONS
As listed on pages 83 - 88
Example 1
Group II Cat 2
1x20mm EEx e threaded hole base at A and B as standard
All entries are fitted with EEx e stopping plugs as standard
25mm entries are available as an option
3 x entries maximum as required by control functions specified
Cover
CONTROL FUNCTIONS
Operating Voltage
Operating Current
Terminal Capacity
T6
ENTRY SPECIFICATION
1x20mm EEx e threaded hole base at A as standard
The entry is fitted with a 20mm EEx e cable gland as standard
25mm entries are available as an option
2 x entries maximum as required by control functions specified
Cover
Zones 1,2,21,22
ENCLOSURE SPECIFICATION
ENTRY SPECIFICATION
Base
EEx edm IIC
HAZARDOUS AREA SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material box
Finish
Weight empty
Cover fixing
Gasket
Earthing
Customised Local Control Stations - Stainless Steel Enclosure
Type LCS300 - EEx edm Three Function Cutomised Control Stations
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
1,2 and 3 function local control stations can be connected together to engineer more
complex systems. The interconnection is made via a specially approved gland
manufactured by Walsall Ltd.
All Dimensions in mm
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
110
Local Control Station - Aluminium Enclosure
Type LCA100 - EEx de 16 amp General Purpose Switch
PART 2.4
LCA RANGE
EEx de IIC
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Standard and Customised EEx edm Local Control Stations in
Aluminium Enclosures.The LCS Range offers very robust local control
stations in fabricated Aluminium enclosures. All the actuators are metal
clad with nickel plated brass housings.
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
II 2 GD
EEx de II C T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
SIRA03ATEX3293 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
Standard Control Stations
Type LCA100 – 16amp General Purpose Switch
Page 112
Type LCA110 – Pushbutton
Page 113
Type LCA120 – Mushroom Pushbutton
Page 114
Type LCA130 – Emergency Pushbutton
Page 115
Type LCA140 – Position and Control Switch
Page 116
Type LCA150 – LED Indicator Lamp
Page 117
Type LCA160 – Ammeter
Page 118
ENCLOSURE SPECIFICATION
Dimensions
Material box
Finish
Weight empty
Cover fixing
Gasket
Earthing
Entries
External Mounting
Internal Mounting
110mm x 110mm x 152mm
3.0mm Aluminium 1050A, H14
Powder coated RAL 7032
0.4Kg
Captive M6 stainless steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Direct through body
External lugs with 8mm clearance
Optional mounting plate to suit
Customised Control Stations
Type LCA200 – 2 Function Customised Control Stations Page 119
ENTRY SPECIFICATION
Type LCA300 – 3 Function Customised Control Stations Page 120
1x20mm EEx e threaded hole base at A as standard.
All entries are fitted with EEx e stopping plugs as standard
25mm entries are available as an option
ELECTRICAL SPECIFICATION
Walsall EEx de IIC switch. Certification No. SIRA 03ATEX1269U
Operating Voltage
Volts
230-270
Operating Current
AC21A(A)
16
Conductor Size
mmsq. Max
2.5
All Dimensions in mm
ORDERING INFORMATION
Description
Double pole off/on
Double pole changeover
Single pole changeover
Notes 1
2
111
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Action
Engage- Engage
Engage- Engage
Engage- Engage- Engage
20º
90º
20º
90º
20º
90º
160º
Contacts
Labelling
1-3 2-4 5-7 6-8
0 -
I
Off - On
1-3 2-4 5-7 6-8
1-3 2-4 5-7 6-8
Product Code
LCA101
LCA102
I
- II
LCA103
I
- 2
LCA104
I - 0 - II
LCA105
I -0- 2
LCA106
For 25 mm entries add/25 to Product Code e.g. LCA103/25
Alternative labelling to order.
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
112
Local Control Station - Aluminium Enclosure
Type LCA110 - EEx de Pushbutton
EEx de IIC
Zones 1,2,21,22
T6
Local Control Station - Aluminium Enclosure
Type LCA120 - EEx de Mushroom Pushbutton
Group II Cat 2
ATEX/GOST
II 2 GD
EEx de II T6
-40˚C to + 50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
SIRA99ATEX3199 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No
Ingress protection
ENCLOSURE SPECIFICATION
Dimensions
Material box
Finish
Weight empty
Cover fixing
Gasket
Earthing
Entries
External Mounting
Internal Mounting
T6
Group II Cat 2
ATEX/GOST
II 2 GD
EEx de II T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
SIRA03ATEX3293 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
110mm x 110mm x 139mm
1.5mm Aluminium 1050A, H14
Powder coated RAL 7032
0.4Kg
Captive M6 stainless steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Direct through body
External lugs with 8mm clearance
Optional mounting plate to suit
Dimensions
Material box
Finish
Weight empty
Cover fixing
Gasket
Earthing
Entries
External Mounting
Internal Mounting
110mm x 110mm x 146mm
3.0mm Aluminium 1050A, H14
Powder coated RAL 7032
0.4Kg
Captive M6 stainless steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Direct through body
External lugs with 8mm clearance
Optional mounting plate to suit
ENTRY SPECIFICATION
ENTRY SPECIFICATION
1x20mm EEx e hole at A as standard.
All entries are fitted with EEx e stopping plugs as standard
25mm entries are available as an option
1x20mm EEx e hole at A as standard
All entries are fitted with EEx e stopping plugs as standard
25mm entries are available as an option
ELECTRICAL SPECIFICATION
ELECTRICAL SPECIFICATION
Walsall EEx de IIC contact block. Certification No. SIRA 03ATEX1269U.
Walsall EEx de IIC contact block. Certification No. SIRA 03ATEX1269U
Operating Voltage
Volts
230-270
Zones 1,2,21,22
HAZARDOUS AREA SPECIFICATION
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No
Ingress protection
EEx de IIC
Operating Current
AC21A(A)
16
Conductor Size
mmsq. Max
2.5
Operating Voltage
Volts
230-270
Operating Current
AC21A(A)
16
Conductor Size
mmsq. Max
2.5
All Dimensions in mm
All Dimensions in mm
ORDERING INFORMATION
ORDERING INFORMATION
Description
Green Pushbutton
Description
Action
Contacts
8 1
8 1
113
0
LCA111
start
I
LCA112
Red Mushroom Pushbutton
Action
stop
Red Mushroom Pushbutton
LCA114
For 25 mm entries add/25 to Product Code e.g. LCA111/25
Alternative labelling to order.
Alternative button colours to order.
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Red Mushroom Pushbutton
Notes 1
2
3
Contacts
Labelling
Product Code
8 1
I
LCA121
5 4
Stop
LCA122
8 1
I
LCA123
5 4
Stop
LCA124
8 1
I
LCA125
5 4
Stop
LCA126
Spring
Pull release
LCA113
Spring
5 4
Notes 1
2
3
Product Code
Spring
5 4
Red Pushbutton
Labelling
Key release
For 25 mm entries add/25 to Product Code e.g. LCA121/25
Alternative labelling to order.
Alternative button colours to order.
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
114
Local Control Station - Aluminium Enclosure
Type LCA130 - EEx de Emergency Pushbutton
EEx de IIC
Zones 1,2,21,22
T6
Local Control Station - Aluminium Enclosure
Type LCA140 - EEx de Position and Control Switch
Group II Cat 2
ATEX/GOST
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Apparatus standard
Certification No
Ingress protection
EEx de IIC
II 2 GD
EEx de II T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
EN 50014:1998 and EN 50019: 1995
SIRA03ATEX3293 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No
Ingress protection
II 2 GD
EEx de II T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
SIRA03ATEX3293 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material box
Finish
Weight empty
Cover fixing
Gasket
Earthing
Entries
External Mounting
Internal Mounting
Dimensions
Material box
Finish
Weight empty
Cover fixing
Gasket
Earthing
110mm x 110mm x 146mm
3.0mm Aluminium 1050A, H14
Powder coated RAL 7032
0.4Kg
Captive M6 stainless steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Direct through body
External lugs with 8mm clearance
Optional mounting plate to suit
Entries
External Mounting
Internal Mounting
110mm x 110mm x 148mm
3.0mm Aluminium 1050A, H14
Powder coated RAL 7032
0.4Kg
Captive M6 stainless steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Direct through body
External lugs with 8mm clearance
Optional mounting plate to suit
ENTRY SPECIFICATION
1x20mm EEx e hole at A as standard.
All entries are fitted with EEx e stopping plugs as standard
25mm entries are available as an option
ENTRY SPECIFICATION
1x20mm EEx e hole at A as standard
All entries are fitted with EEx e stopping plugs as standard
25mm entries are available as an option
ELECTRICAL SPECIFICATION
Walsall EEx de IIC switch. Certification No. SIRA 03ATEX1269U.
Voltage
Volts
230-270
ELECTRICAL SPECIFICATION
Walsall EEx de IIC contact block. Certification No. SIRA 03ATEX1269U
Operating Voltage
Volts
230-270
Operating Current
AC21A(A)
16
All Dimensions in mm
Action
Engage - Engage
20º
90º
Engage - Engage - Engage
20º
90º
160º
Contacts
Labelling
Product Code
3 Position Switch
with centre off
LCA131
3 Position Switch
with centre off
8 1
Red Mushroom Pushbutton
Description
2 Position Switch
3 Position Switch
with centre off
Action
Emergency stop
Pull release
3 Position Control Switch
20º
90º
160º
Spring - Engage - Spring
20º
90º
160º
Spring - Engage - Spring
20º
90º
160º
Spring - Engage - Spring
20º
90º
160º
8 1
Emergency stop
Key release
LCA132
5 4
Note For 25 mm entries add/25 to Product Code e.g. LCA131/25
3 Position Control Switch
3 Position Control Switch
Notes 1
2
3
4
115
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Contacts
Engage - Engage - Spring
5 4
Red Mushroom Pushbutton
Conductor Size
mmsq. Max
2.5
All Dimensions in mm
ORDERING INFORMATION
Conductor Size
mmsq. Max
2.5
ORDERING INFORMATION
Description
Current
AC21A(A)
16
Spring - Engage - Spring
20º
90º
160º
1-3 2-4 5-7 6-8
Labelling
0 -
Product Code
I
LCA141
I - 0 - II
LCA142
I - 0 - II
LCA143
I - 0 - II
LCA144
I - 0 - II
LCA145
I - 0 - II
LCA146
I - 0 - II
LCA147
1-3 2-4 5-7 6-8
1-3 2-4 5-7 6-8
1-3 2-4 5-7 6-8
1-3 2-4 5-7 6-8
1-3 2-4 5-7 6-8
1-3 2-4 5-7 6-8
For 25 mm entries add/25 to Product Code e.g. LCA141/25
Alternative labelling to order.
Alternative handle colours to order.
Add “K” to 2 position switch for key lock version.
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
116
Local Control Station - Aluminium Enclosure
Type LCA150 - EEx em LED Indicator lamp
EEx em IIC
Zones 1,2,21,22
T6
Local Control Station - Aluminium Enclosure
Type LCA160 - EEx e Ammeter
Group II Cat 2
ATEX/GOST
II 2 G
EEx em II T6
-40˚C to +50˚C
Zones 1,2,21,22 . Groups IIA, IIB, IIC
SIRA03ATEX3293 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
ENCLOSURE SPECIFICATION
Dimensions
Material box
Finish
Weight empty
Cover fixing
Gasket
Earthing
Entries
External Mounting
Internal Mounting
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
EEx de IIC
II 2 GD
EEx de II T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
SIRA03ATEX3293 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
110mm x 110mm x 137mm
3.0mm Aluminium 1050A, H14
Powder coated RAL 7032
0.4Kg
Captive M6 stainless steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Direct through body
External lugs with 8mm clearance
Optional mounting plate to suit
Dimensions
Material box
Finish
Weight empty
Cover fixing
Gasket
Earthing
Entries
External Mounting
Internal Mounting
110mm x 110mm x 133mm
3.0mm Aluminium 1050A, H14
Powder coated RAL 7032
0.4Kg
Captive M6 stainless steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Direct through body
External lugs with 8mm clearance
Optional mounting plate to suit
ENTRY SPECIFICATION
ENTRY SPECIFICATION
1x20mm EEx e hole at A as standard.
All entries are fitted with EEx e stopping plugs as standard
25mm entries are available as an option
1x20mm EEx e hole at A as standard
All entries are fitted with EEx e stopping plugs as standard
25mm entries are available as an option
ELECTRICAL SPECIFICATION
ELECTRICAL SPECIFICATION
Walsall EEx e II ammeter. Certification No. SIRA 02ATEX3380U.
Walsall EEx em IIC indicator lamp. Certification No. SIRA 04ATEX5056U
Voltage AC and DC
Volts (AC-5%+10%)
24 - 230
Current
AC21A(A)
0.005
Conductor Size
mmsq. Max
2.5
Voltage
Volts
240
Current
AC21A(A)
16
Conductor Size
mmsq. Max
2.5
All Dimensions in mm
All Dimensions in mm
Direct Operated
0 - 2 - 12 amps
0 - 5 - 30 amps
0 - 10 - 60 amps
Standard Meter Scales
Operated from current transformer with 1 amp secondary
0 - 60 - 360 amps
0 - 10 - 60 amps
0 - 80 - 480 amps
0 - 15 - 90 amps
0 - 100 - 600 amps
0 - 20 - 120 amps
0 - 150 - 900 amps
0 - 30 - 180 amps
0 - 200 - 1200 amps
0 - 40 - 240 amps
0 - 50 - 300 amps
ORDERING INFORMATION
Description
Green Indicator Lamp
Red Indicator Lamp
Amber Indicator Lamp
Clear Indicator Lamp
Blue Indicator Lamp
Notes
117
Product Code
LCA151
LCA152
LCA153
LCA154
LCA155
ORDERING INFORMATION
Note 1
Current Rating
Ammeter
For 25 mm entries add/25 to Product Code e.g. LCA160/25
Scale
To Be Specified
Product Code
LCA160
For 25 mm entries add/25 to Product Code e.g. LCS151/25
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
118
Customised Local Control Stations - Aluminium Enclosure
Type LCA200 - EEx edm Two Function Customised Control Stations
EEx edm IIC
Zones 1,2,21,22
T6
Group II Cat 1,2,3
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
External Mounting
Internal Mounting
EEx edm IIC
Zones 1,2,21,22
T6
Group II Cat 1,2,3
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
II 2 GD
EEx e, ed, em IIC T6
-40˚C to +50˚C
Zones 1,2,21,22 . Groups IIA, IIB, IIC
SIRA03ATEX3293. POCC. GB. гБ 05.BO1132
IP66 to EN60529:1991
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
ENCLOSURE SPECIFICATION
Dimensions
Material box
Finish
Weight empty
Cover fixing
Gasket
Earthing
Customised Local Control Stations - Aluminium Enclosure
Type LCA300 - EEx edm Three Function Customised Control Stations
II 2 GD
EEx e, ed, em IIC T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
SIRA03ATEX3293. POCC. GB. гБ 05.BO1132
IP66 to EN60529:1991
GVU2 ENCLOSURE SPECIFICATION
165mm x 110mm
3mm Aluminium 1050A, H14
Powder coated RAL 7032
0.4Kg
Captive M6 stainless steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
External lugs with 10mm clearance
Optional mounting plate to suit
Dimensions
Material box
Finish
Weight empty
Cover fixing
Gasket
Earthing
External Mounting
Internal Mounting
230mm x 110mm
3.0mm Aluminium 1050A, H14
Powder coated RAL 7032
0.4Kg
Captive M6 stainless steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
External lugs with 10mm clearance
Optional mounting plate to suit
ENTRY SPECIFICATION
ENTRY SPECIFICATION
Base
Base
1x20mm EEx e hole at A and B as standard
All entries are fitted with EEx e stopping plugs as standard
25mm entries are available as an option
2 x entries maximum as required by control functions specified
Cover
1x20mm EEx e hole at A and B as standard
All entries are fitted with EEx e stopping plugs as standard
25mm entries are available as an option
3 x entries maximum as required by control functions specified
Cover
CONTROL FUNCTIONS
CONTROL FUNCTIONS
As listed on pages 83 -88
As listed on pages 83 -88
ELECTRICAL SPECIFICATION
ELECTRICAL SPECIFICATION
Operating Voltage
Operating Current
Terminal Capacity
Operating Voltage
Operating Current
Terminal Capacity
230 – 270 Volts
16 Amps max
2.5mm sq. max
230 – 270 Volts
16 Amps max
2.5mm sq. max
ORDERING INFORMATION
ORDERING INFORMATION
The first function specified in the order code occupies position X in the
enclosure, the second function Y and the third function position Z.
The first function specified in the order code occupies position X in the enclosure
and the second function position Y.
Ordering codes are built up as shown in the following examples.
Ordering codes are built up as shown in the following examples.
Ex 1
Ex 1
Ammeter plus 2 pole changeover switch.
Product Code: LCA200 + CF12 + CF7
Ex 2
Emergency stop with pull release plus green start plus green indicator lamp
Product Code: LCA300 + CF12 + CF7 + CF35
Ex 2
On/Off switch plus green indicator lamp.
Double green and red pushbutton plus red indicator plus mushroom
pushbutton.
Product Code: LCA300 + CF25 + CF31+ CF10
Product Code: LCA200 + CF25
1. Labelling to be specified by customer.
2. For 25mm entries add /25 to enclosure code e.g. LCA200/25 + CF12 + CF7
1. Labelling to be specified by customer.
2. For 25mm entries add /25 to enclosure code e.g. LCA300/25 + CF12 + CF7
+ CF35
ENCLOSURE INTERCONNECTIONS
1,2 and 3 function local control stations can be connected together to engineer more
complex systems. The interconnection is made via a specially approved gland
manufactured by Walsall Ltd.
119
ENCLOSURE INTERCONNECTIONS
All Dimensions in mm
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
1,2 and 3 function local control stations can be connected together to engineer more
complex systems. The interconnection is made via a specially approved gland
manufactured by Walsall Ltd.
All Dimensions in mm
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
120
Local Control Station - Glass Reinforced Polyester Enclosure
Type GVU/E030 - EEx de Single Pushbutton
PART 2.5
GVU RANGE
EEx de IIC
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
EEx ed Heavy Duty Local Control Stations in Glass Reinforced
Polyester Enclosures. The GVU Range offers very robust local control
stations. The minimum wall thickness of the enclosures is 6mm and
all the actuators are shrouded in Heavy Duty GRP.
Type GVU/E030 – Single Pushbutton
Page 122
Type GVU/E030 – Double Pushbutton
Page 123
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No
Ingress protection
II 2 GD
EEx de IIC T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
SIRA03ATEX3293 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Weight
Cover fixing
Gasket
Earthing
Mounting
110mm x 110mm x 115mm
Carbon loaded Glass reinforced polyester UL94/V0
Moulded black
1.2 Kg
M6 pan head stainless steel screws
1.2 mm one piece solid nitrile rubber
Internal EEx e brass clamps on base
Through 7mm holes fixing strap
ENTRY SPECIFICATION
1x20mm EEx e threaded hole base at A as standard.
The entry is fitted with a 20mm EEx e cable gland as standard.
25mm entries are available as an option.
ELECTRICAL SPECIFICATION
Walsall EEx de IIC contact block. Certification No. SIRA 03ATEX1269U
Operating Voltage
Volts
230-270
Operating Current
Amps
16
Conductor Size
mmsq. Max
2.5
All Dimensions in mm
ORDERING INFORMATION
Description
Shrouded green pushbutton
Shrouded red pushbutton
Shrouded red pushbutton with stayput
Exposed red pushbutton
Mushroom pushbutton with stayput
Notes 1
2
3
121
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Labelling
Start
Stop
Stop
Stop
Emergency Stop
Product Code
E030160
E030161
E030162
E030163
E030164
For 25 mm entries add/25 to Product Code e.g. E030160/25
Alternative labelling to order.
Alternative button colours to order.
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
122
Local Control Station - Glass Reinforced Polyester Enclosure
Type GVU/E030 - EEx de Double Pushbutton
EEx de IIC
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No
Ingress protection
II 2 GD
EEx de IIC T6
-40˚C to + 50˚C
Zones 1,2,21,22 . Groups IIA, IIB, IIC
SIRA03ATEX3293 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Weight
Cover fixing
Gasket
Earthing
Mounting
110mm x 110mm x 113mm
Carbon loaded Glass reinforced polyester UL94/V0
Moulded black
1.2 Kg
M6 pan head stainless steel screws
1.2mm one piece solid nitrile rubber
Internal EEx e brass clamps on base
Through 7mm holes fixing strap
ENTRY SPECIFICATION
1x20mm EEx e threaded hole base at A as standard.
The entry is fitted with a 20mm EEx e cable gland as standard.
25mm entries are available as an option.
ELECTRICAL SPECIFICATION
Walsall EEx de IIC contact block. Certification No. SIRA 03ATEX1269U
Operating Voltage
Volts
230-270
Operating Current
Amps
16
Conductor Size
mmsq. Max
2.5
CNC machining of GRP
enclosures
All Dimensions in mm
ORDERING INFORMATION
Description
Shrouded green and shrouded red
Shrouded green and shrouded red with stayput
Shrouded green and exposed red with stayput
Shrouded green and mushroom red with stayput
Notes 1
2
3
123
Labelling
Start/Stop
Start/Stop
Start/Stop
Start/Stop
Product Code
E030165
E030166
E030167
E030168A
For 25 mm entries add/25 to Product Code e.g. E030165/25
Alternative labelling to order.
Alternative button colours to order.
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
CNC compression moulding
of GRP enclosures
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
124
Customised Control Panels - Glass Reinforced Polyester Enclosure
Type GLCP - EEx edm Control Panel
PART 2.6
GLCP RANGE
EEx edm IIC
Zones 1,2,21,22
T6, T5
Group II Cat 2
ATEX/GOST
The EEx edm approved control functions listed on pages 83-88 can be installed
in EEx e approved enclosures moulded from glass reinforced polyester to engineer
a wide range of customised EEx edm approved control panels.
EEx edm IIC customised control panels in glass reinforced
poyester enclosures.
Type GLCP11 – 255mm x 250mm x 120mm
Page 126
Type GLCP12 – 400mm x 250mm x 120mm
Page 126
Type GLCP13 – 405mm x 400mm x 120mm
Page 126
Type GLCP14 – 405mm x 400mm x 165mm
Page 126
CUSTOMISING
As a vertically integrated manufacturer Walsall can customise
the GLCP range at each stage of the manufacturing process
to meet individual customer requirements.
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Certification No.
Ingress protection
II 2 GD
EEx e de em IIC T6
-40˚C to +40˚C, 50˚C
SIRA99ATEX3200 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
Dimensions
Type GLCP11 255mm x 250mm x 120mm
Type GLCP12 400mm x 250mm x 120mm
Type GLCP13 405mm x 400mm x 120mm
Type GLCP14 405mm x 400mm x 165mm
Carbon loaded, anti-static glass reinforced polyester UL 94/V0
Moulded self colour black. Other colours available on request
Captive M6 stainless steel allen head screws. Optional hinges
Silicon rubber
Optional 6mm brass internal/external earth stud
Optional internal earth continuity plate in galvanised
steel, brass or stainless steel
Through threaded hole in body
Integral 6.5mm clearance holes moulded into the body
Material
Finish
Cover fixing
Gasket
Earthing
Entry
Mounting
Drawing shows typical enclosure e.g GLCP13
ENTRY SPECIFICATION
Entries are to customer requirements. The table below gives a guide to the gland
capacity for the more commonly used gland sizes. For other gland sizes or mixed
sizes consult Walsall Technical Sales
Enclosure
Gland Size mm
Sides A & B
Sides C & D
20
17
14
GLCP11
25 32
10
5
8
4
20
32
14
GLCP12
25 32
18
9
8
4
20
32
29
GLCP13
25 32
18
9
16
8
20
42
38
GLCP14
25 32
27 14
25 14
PANEL LAYOUTS
Enclosure
GLCP11
No. of horizontal rails.
2
No. of functions per rail
3
GLCP12
2 or 4
5 or 3
GLCP13
4
5
GLCP14
4
5
Note that meters take up two horizontally adjacent positions.
If terminals are required in the layout, allowances must be made by calculating the
width of the terminal block and deducting this length from the available rail capacity.
All Dimensions in mm
ORDERING INFORMATION
The information given above is for guidance only. In practice customised control
panels are specified jointly between the customer and Walsall Technical Sales.
Following an initial discussion, drawings are produced by Walsall for approval by
the customer. Orders can be placed and accepted using the drawings for
reference.
125
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
126
Customised Control Panels - Stainless Steel Enclosure
Type XLCP - EEx edm Customised Control Panel
PART 2.7
XLCP RANGE
EEx edm IIC
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
The EEx edm approved control functions listed on pages 83-88 can be installed
in EEx e approved enclosures fabricated from sheet stainless steel to engineer a wide
range of customised EEx edm approved control panels.
EEx edm IIC customised control panels in stainless steel
enclosures.
Type XLCP3 – 306mm x 306mm x 150mm
Page 128
Type XLCP5 – 458mm x 382mm x 150mm
Page 128
Type XLCP6 – 480mm x 480mm x 150mm
Page 128
Type XLCP9 – 762mm x 508mm x 150mm
Page 128
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Certification No.
Ingress protection
ENCLOSURE SPECIFICATION
Dimensions
CUSTOMISING
As a vertically integrated manufacturer Walsall can customise
the XLCP range at each stage of the manufacturing process
to meet individual customer requirements.
II 2 GD
EEx e ed em II T6
-40˚C to +40˚C or +50˚C
SIRA99ATEX3199 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
Material box
Material gland plate
Finish
Cover fixing
Gasket
Earthing
Security
Entries
Mounting
XLCP3 306mm x 306mm x 150mm
XLCP5 458mm x 382mm x 150mm
XLCP6 480mm x 480mm x 150mm
XLCP9 762mm x 508mm x 150mm
1.5mm 316L, (1.4404) stainless
2.5mm 316L, (1.4404) stainless
Stainless steel – electropolished
Fully detachable hinged cover with captive M6 stainless
steel hexagon head slotted screws
One piece fire resistant closed cell neoprene for Ta -40˚C
One piece silicon rubber for Ta -50˚C
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover
Optional earth stud welded to gland plate
Padlockable hasp
Via gland plates 1-4 or direct through body
External lugs with 10mm clearance holes
Drawing shows typical enclosure e.g XLCP6
ENTRY SPECIFICATION
Entries are to customer requirements. The table below give a guide to the gland
capacityfor the more commonly used gland sizes. For other gland sizes or mixed
sizes consult Walsall Technical Sales.
Enclosure
Gland Size mm
Sides A & B
Sides C & D
20
21
15
XL3
25
12
9
Number of Gland plates
Location
32
6
4
0
-
XL5
25
17
17
20
27
27
1
B
32
9
9
2
AB
20
36
29
3
BCD
XL6
25
22
18
32
11
9
20
38
38
XL9
25
24
24
32
12
12
4
ABCD
PANEL LAYOUTS. (See diagrams opposite).
XL5
XL6
XL9
Enclosure
XL3
No. of horizontal rails.
2
4
4
7
No. of functions per rail
3
4
5
6
Note that meters take up two horizontally adjacent positions.
If terminals are required in the layout, allowances must be made by calculating the
width of the terminal block and deducting this length from the available rail capacity.
All Dimensions in mm
ORDERING INFORMATION
The information given above is for guidance only. In practice customised control
panels are specified jointly between the customer and Walsall Technical Sales.
Following an initial discussion, drawings are produced by Walsall for approval by
the customer. Orders can be placed and accepted using the drawings for
reference.
127
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
128
PART 3.0
CONTROL IN CAST IRON,
CAST STAINLESS STEEL,
AND CAST ALUMINUM
ENCLOSURES
Comprehensive ranges of EE x d IIC standard local control stations and
customised control panels in enclosures manufactured from cast iron,
cast aluminium and cast stainless steel.
3.1 CD Range
Page 131
EEx d control actuators
3.2 E11 Range
Page 135
EEx d local control stations in cast iron enclosures
3.3 ASMCP Range
Page 145
EEx d Customised control panels in cast iron, cast aluminium
and cast stainless steel enclosures
3.4 COMBINED EEx d AND EEx edm CONTROL SYSTEMS
Page 149
EEx d Customised control panels in cast iron, cast aluminium and cast
stainless steel enclosures combined with EEx edm terminal and control panels
129
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
130
EEx d Control Actuators
Introduction
PART 3.1
CD RANGE
EEx d IIB
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
INTRODUCTION
A comprehensive range of EEx d switch/pushbutton
actuators, indicator lens and viewing windows for installation
in EEx d approved enclosures manufactured in cast iron,
cast aluminium and cast stainless steel.
Introduction
Page 132
Type CD – Switch handles and actuators
Page 133
Type CD – Push Button actuators
Page 133
Type CD – Indicator lens
Page 134
Type CD – Viewing windows
Page 134
Standard ie not Ex approved, electrical equipment can be installed in enclosures with ‘d’ type protection. These enclosures are normally cast from
iron, aluminium or stainless steel. In order to operate the installed electrical equipment actuators are required that are fixed to the outside surface of
the ‘d’ enclosures and which pass through the walls of the enclosure to engage the equipment within. These actuators must incorporate a ‘d’ flamepath
that passes through the wall of the enclosure and are therefore special purpose devices designed and approved to EEx d IIC type protection.
The Walsall range of ‘d’ actuators includes rotational shafts and handles for switch applications, spring operated vertical shafts and operators
for pushbutton applications, metal clad toughed glass indicator lenses and metal clad toughened glass viewing windows for observing instrumentation
and measuring devices.
The process for defining the elements of a complete ‘d’ system is shown below.
Standard Electrical
Equipment
131
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
+
‘d’
actuators
+
‘d’
enclosure
=
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
‘d’
control systems
132
EEx d Control Actuators
Type CD - Switch and Pushbutton Actuators
EEx d IIB
Zones 1,2,21,22
T6
EEx d Control Actuators
Type CD - Indicator Lens and Viewing Windows
Group II Cat 2
ATEX/GOST
The following EEx d approved pushbutton and switch actuators, are available for mounting on the external surface of EEx d enclosures in order to operate
the electrical equipment assembled internally.
EEx d IIB
Zones 1,2,21,22
INDICATOR LENS
HAZARDOUS AREA SPECIFICATION
HAZARDOUS AREA SPECIFICATION
II 2 GD
EEx d IIC T6
-40˚C to + 50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
SIRA02ATEX1307 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
PRODUCT SPECIFICATION
Flamepath
Handle
Shroud
Locking
Group II Cat 2
ATEX/GOST
The following EEx d approved indicator lamp lens and viewing windows are available for mounting on the external surface of EEx d enclosures in order to
observe the electrical equipment assembled internally.
SWITCH ACTUATORS
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
T6
II 2 GD
EEx d IIC T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
SIRA02ATEX1313 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
PRODUCT SPECIFICATION
Brass housing with clear toughened glass lens held in position with cement and
Brass shaft in brass housing of minimum length of 20mm
Polycarbonate
Polycarbonate
Positions as required
threaded ring.
ORDERING INFORMATION
ORDERING INFORMATION
Description
Black switch handle with black surround for on/off, changeover, and position switching.
Red handle with yellow surround for switch disconnecting, locking in off position
Heavy Duty handle for switching 100amps or more
Product Code
CD1
CD2
CD3
Note: Labeling to order.
Description
Viewing lens
Note: Labeling to order.
VIEWING WINDOWS
HAZARDOUS AREA SPECIFICATION
PUSHBUTTON ACTUATORS
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
II 2 GD
EEx d IIC T6
-40˚C to + 50˚C
Zones 1,2,21,22 . Groups IIA, IIB, IIC
SIRA02ATEX1307 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
PRODUCT SPECIFICATION
Brass shaft in brass housing of minimum length of 20mm
Polycarbonate
Polycarbonate
Cast Housing in Iron, Aluminium or Stainless Steel
with 10mm borosilicate glass
ORDERING INFORMATION
Description
70mm x 70mm
200mm x 100mm
ORDERING INFORMATION
Description
Green pushbutton with spring action.
Red pushbutton with spring action.
Red pushbutton with lever release.
Red mushroom pushbutton with lever release.
Emergency mushroom pushbutton with lever release.
133
II 2 GD
EEx d II T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
SIRA02ATEX1307 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1991
PRODUCT SPECIFICATION
Material
Flamepath
Handle
Shroud
Product Code
CD9
Product Code
CD10
CD11
Product Code
CD4
CD5
CD6
CD7
CD8
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
134
Local Control Station - Cast Iron Enclosure
Type E110 - EEx d IIC General Purpose 20amp switch
PART 3.2
E11 RANGE
EEx d IIC
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
EEx d IIC Local Control Stations in Cast Iron Enclosures.
A comprehensive range of one and two function EEx d local control
stations in very robust cast iron enclosures.
Type E110 – General Purpose 20 Amp Switch
Page 136
Type E116 – Pushbutton
Page 137
Type E116 – Emergency Stop Pushbutton
Page 138
Type E116 – Double Pushbuttons
Page 139
Type E113 – Ammeter
Page 140
Type E114 – Indicator Lamp
Page 141
Type E118 – Photocell
Page 142
Type E110 – Fuse Unit
Page 143
Multiple Assemblies
Page 144
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
II 2 GD
EEx d IIC T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
SIRA02ATEX1307 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Colour
Weight
Cover fixing
Gasket
Plastic components
Operator flamepath
Security
Earthing
Mounting
117mmx117mmx143mm
Cast iron to 180BSI1452:1997
Zinc rich epoxy powder primer and epoxy powder top coat
Black
5.1 Kg
M6 allen head stainless steel screws
Nitrile O ring
Polycarbonate
Brass shaft in a brass housing
Switches with an off position have a padlock ‘off’ ‘facility
as standard
Internal and external EEx e brass clamps on base
Through 10mm holes cast into base
ENTRY SPECIFICATION
1x20mm EEx d threaded hole at A and B as standard.
All entries are fitted with EEx d stopping plugs as standard
25mm entries are available as an option
ELECTRICAL SPECIFICATION
Switch: 2 and 4 pole rotary cam switch to IEC60 947.
Voltage
Volts
380-440
Current
AC21A (A)
20
Power
AC23A(Kw)
7.5
AC-3A(Kw)
7.5
Conductor Size
mmsq. Max.
2.5
All Dimensions in mm
ORDERING INFORMATION
Current Rating
20 amps
20 amps
20 amps
For 25 mm entries add/25 to Product Code e.g. E110006/25
135
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Switch Position
Off-On
1 - Off - 2
1-2
Poles
4
2
2
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Product Code
E110006
E110003
E110002
136
Local Control Station - Cast Iron Enclosure
Type E116 - EEx d IIC Push Button
EEx d IIC
Zones 1,2,21,22
T6
Local Control Station - Cast Iron Enclosure
Type E116 - EEx d IIC Emergency Stop Pushbutton
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
Mounting
II 2 GD
EEx d IIC T6
-40˚C to + 50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
SIRA02ATEX1312 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
T6
Group II Cat 2
ATEX/GOST
II 2 GD
EEx d IIC T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
SIRA02ATEX1312 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
117mmx117mmx147mm
Cast iron to 180BSI1452:1997
Zinc rich epoxy powder primer and epoxy powder top coat
Black
5.1 Kg
M6 allen head stainless steel screws
Nitrile O ring
Polycarbonate
Brass shaft in brass housing, nitrile O ring seal
Internal and external EEx e brass clamps on base
Earth on cover
Through 10mm holes cast into base
Dimensions
Material
Finish
Colour
Weight
Cover fixing
Gasket
Plastic components
Operator flamepath
Earthing
Mounting
ENTRY SPECIFICATION
117mm x 117mm x 147mm
Cast iron to 180BSI1452:1997
Zinc rich epoxy powder primer and epoxy powder top coat
Black
5.1 Kg
M6 allen head stainless steel screws
Nitrile O ring
Polycarbonate
Brass shaft in brass housing with nitril O ring seal
Internal and external EEx e brass clamps on base
Earth on cover
Through 10mm holes cast into base
ENTRY SPECIFICATION
1x20mm EEx d threaded hole at A and B as standard
All entries are fitted with EEx d stopping plugs as standard
25mm entries are available as an option
1x20mm EEx d threaded hole at A and B as standard.
All entries are fitted with EEx d stopping plugs as standard
25mm entries are available as an option
ELECTRICAL SPECIFICATION
ELECTRICAL SPECIFICATION
Contactors to IEC 60 947. BS EN 60 947
Contactor to IEC 60 947 . BS EN 60 947
Voltage
Volts
220-240
415
Zones 1,2,21,22
HAZARDOUS AREA SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Colour
Weight
Cover fixing
Gasket
Plastic components
Operator flamepath
Earthing
EEx d IIC
Current
AC15 (A)
3
2
Conductor Size
mmsq. Max
2.5
2.5
Voltage
Volts
220-240
415
All Dimensions in mm
Current
AC15 (A)
3
2
Conductor Size
mmsq. Max
2.5
2.5
All Dimensions in mm
ORDERING INFORMATION
Description
Shrouded Green Pushbutton
Shrouded Red Pushbutton
Exposed Red Pushbutton
For 25 mm entries add/25 to Product Code e.g. E116001/25
137
Label
start
stop
stop
Contacts
1 n/o and 1n/c
1 n/o and 1n/c
1 n/o and 1n/c
Product Code
E116001
E116002
E116003
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
ORDERING INFORMATION
Description
Single mushroom head emergency ‘stop’ with latching
For 25 mm entries add/25 to Product Code e.g. E110006/25
Contacts
1 n/o & 1 n/c
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Product Code
E116010
138
Local Control Station - Cast Iron Enclosure
Type E113 - EEx d IIC Ammeter
Local Control Station - Cast Iron Enclosure
Type E116 - EEx d IIC Double Pushbuttons
EEx d IIC
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
II 2 GD
EEx d IIC T6
-40˚C to + 50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
SIRA02ATEX1312 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
Mounting
T6
Group II Cat 1,2,3
ATEX/GOST
II 2 GD
EEx d IIC T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
SIRA02ATEX1309 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1991
ENCLOSURE SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Colour
Weight
Cover fixing
Gasket
Plastic components
Operator flamepath
Earthing
Zones 1,2,21,22
HAZARDOUS AREA SPECIFICATION
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
EEx d IIC
Dimensions
Material
Finish
Colour
Weight
Cover fixing
Gasket
Glass
Earthing
117mm x 117mm x 147mm
Cast iron to 180BSI1452:1997
Zinc rich epoxy powder primer and epoxy powder top coat
Black
5.1Kg
M6 allen head stainless steel screws
Nitrile O ring
Polycarbonate
Brass shaft in brass housing., nitrile O ring seal
Internal and external EEx e brass clamps on base
Earth on cover
Through 10mm holes cast into base
Mounting
117mm x 117mm x 138mm
Cast iron to 180BSI1452:1997
Zinc rich epoxy powder primer and epoxy powder top coat
Black
5.1 Kg
M6 allen head stainless steel screws
Nitrile O ring
Toughened Borosilicate
Internal and external EEx e brass clamps on base
Earth on cover
Through 10mm holes cast into base
ENTRY SPECIFICATION
ENTRY SPECIFICATION
1x20mm EEx d threaded hole at A and B as standard.
All entries are fitted with EEx d stopping plugs as standard
25mm entries are available as an option
1x20mm EEx d threaded hole at A and B as standard
All entries are fitted with EEx d stopping plugs as standard
25mm entries are available as an option
ELECTRICAL SPECIFICATION
ELECTRICAL SPECIFICATION
Moving iron ammeter with adjustable red secondary pointer and overload scale.
Contactors to IEC 60 947. BS EN 60 947
Voltage
Volts
220-240
414
Current
AC15 (A)
3
2
Voltage
Volts
To 300
Conductor Size
mmsq. Max
2.5
2.5
Current (direct)
Amps
30
Current (transformer)
Amps
1
Conductor Size
mmsq. Max
4.0
All Dimensions in mm
METER SCALES
All Dimensions in mm
ORDERING INFORMATION
Description
Shrouded Green ’start’ and shrouded red ‘stop’
Shrouded Green ’start’ and exposed red ‘stop’
Shrouded Green ’start’ and shrouded red latching ‘stop’
Shrouded Green ’start’ and exposed red latching ‘stop’
Contacts (each)
1 n/o & 1 n/c
1 n/o & 1 n/c
1 n/o & 1 n/c
1 n/o & 1 n/c
Product Code
E116005
E116006
E116009
E116007
For 25 mm entries add/25 to Product Code e.g. E116005/25
139
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Direct operated
0 - 2 - 12 amps
0 - 5 - 30 amps
0 - 30 - 180 amps
Operated from current transformer with 1 amp secondary
0 - 80 - 480 amps
0 - 40 - 240 amps
0 - 15 - 90 amps
0 - 100 - 600 amps
0 - 50 - 300 amps
0 - 20 - 120 amps
0 - 150 - 900 amps
0 - 60 - 360 amps
0 - 30 - 180 amps
0 - 200 - 1200 amps
ORDERING INFORMATION
Description
Ammeter
For 25 mm entries add/25 to Product Code e.g. E113001/25
Meter Scales
To be specified
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Product Code
E113001
140
Local Control Station - Cast Iron Enclosure
Type E118 - EEx d IIC Photocell
Local Control Station - Cast Iron Enclosure
Type E114 - EEx d IIC Single and Twin Indicator Lamps
EEx d IIC
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Apparatus standard
Certification No.
Ingress protection
EEx d IIC
II 2 GD
EEx d II T6
-40˚C to + 50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
EN 50014:1998 and EN 50018: 1995
SIRA02ATEX1310
IP66 to EN60529:1992
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
II 2 GD
EEx d IIC T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
SIRA02ATEX1314 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Colour
Weight
Cover fixing
Gasket
Glass
Earthing
Dimensions
Material
Finish
Colour
Weight
Cover fixing
Gasket
Glass
Earthing
117mm x 117mm x 138mm
Cast iron to 180BSI1452:1997
Zinc rich epoxy powder primer and epoxy powder top coat
Black
5.1Kg
M6 allen head stainless steel screws
Nitrile O ring
Toughened
Internal and external EEx e brass clamps on base
Earth on cover
Through 10mm holes cast into base
Mounting
Mounting
117mm x 117mm x 138mm
Cast iron to 180BSI1452:1997
Zinc rich epoxy powder primer and epoxy powder top coat
Black
5.1Kg
M6 allen head stainless steel screws
Nitrile O ring
Toughened
Internal and external EEx e brass clamps on base
Earth on cover
Through 10mm holes cast into base
ENTRY SPECIFICATION
ENTRY SPECIFICATION
1x20mm EEx d threaded hole at A and B as standard.
All entries are fitted with EEx d stopping plugs as standard
25mm entries are available as an option
1x20mm EEx d threaded hole at A and B as standard
All entries are fitted with EEx d stopping plugs as standard
25mm entries are available as an option
ELECTRICAL SPECIFICATION
ELECTRICAL SPECIFICATION
Photocell: Sealed silicon photo diode.
Lamps. Transformer operated 6.5 Volts, 0.15 Amps, MES type
Voltage
Volts
240
Conductor Size
mmsq. Max
2.5
2.5
2.5
Voltage
Volts
110-120
200-250
380-440
Temperature Range
˚C
-20˚C to +60˚C
Power Consumption
watts
0.25
All Dimensions in mm
Conductor
mmsq
2.5
All Dimensions in mm
ORDERING INFORMATION
Description
Single Green
Single Red
Single Amber
Single White
Product Code
E114001
E114002
E114003
E114004
Description
Green and Red
Green and Amber
Green and White
Product Code
E114005
E114006
E114007
Description
Red and Amber
Red and White
Amber and White
Product Code
E114008
E114009
E114010
ORDERING INFORMATION
Description
Photocell
For 25 mm entries add/25 to Product Code e.g. E118001/25
Product Code
E118001
For 25 mm entries add/25 to Product Code e.g. E114004/25
141
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
142
Local Control Station - Cast Iron Enclosure
Type E110 - EEx d IIC Fuse Unit
EEx d IIC
Zones 1,2,21,22
T6
Multiple Assemblies
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
Individual units in the range should be fixed through the external fixing strap provided
when mounted individually. When two or more units are directly connected together
it is a condition of the certification that they are supplied as a factory built
assembly on steel back plates as shown below.
Any combination of the listed individual units can be joined together in 2, 3 or 4
gang configurations.
These assemblies can be mounted either horizontally or vertically.
II 2 GD
EEx d IIC T6
-40˚C to + 50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
SIRA02ATEX1308 POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Colour
Weight
Cover fixing
Gasket
Earthing
Mounting
117mm x 117mm x 116mm
Cast iron to 180BSI1452:1997
Zinc rich epoxy powder primer and epoxy powder top coat
Black
5.1Kg
M6 allen head stainless steel screws
Nitrile O ring
Internal and external EEx e brass clamps on base
Earth on cover
Through 10mm holes cast into base
ENTRY SPECIFICATION
1x20mm EEx d threaded hole at A and B as standard
All entries are fitted with EEx d stopping plugs as standard
25mm entries are available as an option
ELECTRICAL SPECIFICATION
Fuse: 16 Amp fuse links
Voltage
Volts
240
Current
Amps
16
Conductor Size
mmsq. Max
2.5
All Dimensions in mm
ORDERING INFORMATION
Description
Single pole and neutral
Double pole
For 25 mm entries add/25 to Product Code e.g. E112001/25
143
Product Code
E112001
E112002
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
144
Customised Control Panels - Cast Aluminium Enclosure
Type ASMCP/AL - EEx d Customised Control Panels
PART 3.3
ASMCP RANGE
EEx d IIB
EEx d IIB Customised Control Panels in cast Iron, cast aluminum and
cast stainless steel enclosures.
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
The EEx d approved actuators listed can be used to operate standard (not EEx
approved) electrical and electronic equipment installed in EEx d approved
enclosures of cast aluminium to engineer customised EEx d approved control
systems. Two sizes of enclosures are available.
The type of equipment that can be installed in the enclosures is limited by the
volume of the equipment and the maximum power dissipation permitted.
HAZARDOUS AREA SPECIFICATION
Type ASMCP/AL - Customised control panels in cast aluminium
enclosures
Page 146
Type ASMCP/CI - Customised control panels in cast iron
enclosures
Page 147
Ingress protection
Power dissipation
Type ASMCP/SS - Customised control panels in cast
stainless steel enclosures
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
II 2 GD
EEx d IIB T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB
SIRA04ATEX1266X. SIRA03ATEX1215
POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
7.0 Watts at +40˚C, 62 Watts at +50˚C
Page 148
ENCLOSURE SPECIFICATION
Dimensions
CUSTOMISING
As a vertically integrated manufacturer Walsall can customise
the ASMCP range at each stage of the manufacturing
process to meet individual customer requirements.
ASMCP130/AL - 210mm x 185mm x 152mm
ASMCP150/AL – 335mm x 310mm x 200mm
Cast aluminium LM6
Epoxy powder coated black
ASMCP130/AL 6.0Kg
ASMCP150/AL 17Kg
M8 allen head stainless steel screws
One piece closed cell 4mm neoprene
Base- internal and external EEx e brass clamps
Cover – internal EEx e brass clamp
2 steel mounting straps. 8mm diameter fixing holes
Material
Finish
Weight empty
Cover fixing
Gasket
Earthing
Mounting
ENTRY SPECIFICATION
Entries are to customer requirements. The table below give a guide to the gland
capacity for the more commonly used gland sizes. For other gland sizes or mixed
sizes consult Walsall Technical Sales.
All entries are fitted with an EEx d approved stopping plug or cable gland.
Enclosure
Gland Size mm
Sides A & B
Sides C & D
20
5
5
ASMCP130/AL
25
5
5
32
2
3
20
11
11
ASMCP150/AL
25
32
8
7
8
7
All Dimensions in mm
40
3
3
PANEL LAYOUTS.
Enclosure
No. of horizontal rails.
No.of Actuators Permitted in Cover
ASMCP130/AL ASMCP150/AL
1
2
2
12
ORDERING INFORMATION
The information given above is for guidance only. In practice customised control
panels are specified jointly between the customer and Walsall Technical Sales.
Following an initial discussion, drawings are produced by Walsall for approval by
the customer. Orders can be placed and accepted using the drawings for
reference.
145
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
146
Customised Control Panels - Cast Iron Enclosure
Type ASMCP/CI - EEx d Customised Control Panels
EEx d IIB
Zones 1,2,21,22
T6
Customised Control Panels - Cast Stainless Steel Enclosure
Type ASMCP/SS - EEx d Customised Control Panels
Group II Cat 2
ATEX/GOST
The EEx d approved actuators listed can be used to operate standard (not EEx
approved) electrical and electronic equipment installed in EEx d approved
enclosures of cast iron to engineer customised EEx d approved control
systems. Three sizes of enclosures are available.
The type of equipment that can be installed in the enclosures is limited by the
volume of the equipment and the maximum power dissipation permitted.
Ingress protection
Power dissipation
Material
Finish
Weight empty
Cover fixing
Gasket
Earthing
Mounting
II 2 GD
EEx d IIB T6
-40˚C to + 50˚C
Zones 1,2,21,22. Groups IIA, IIB
SIRA04ATEX1266X. SIRA03ATEX1215. SIRA04ATEX1267X
POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
7.0 Watts at +40˚C, 62 watts at +50˚C, 200 Watts at +50˚C
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
Power dissipation
ASMCP130/CI - 210mm x 185mm x 152mm
ASMCP150/CI – 335mm x 310mm x 200mm
ASMCP170/CI - 560mm x 560mm x 245mm
Cast Iron
2 pack Epoxy coated to customer spec
ASMCP130/CI 20Kg
ASMCP150/CI 51Kg
ASMCP170/CI 175Kg
M8 allen head stainless steel screws
One piece closed cell 4mm neoprene
Base- internal and external EEx e brass clamps
Cover – internal EEx e brass clamp
2 steel mounting straps. 8mm diameter fixing holes
Dimensions
Material
Finish
Weight empty
Cover fixing
Gasket
Earthing
Mounting
20
11
11
ASMCP150/CL
25 32 40
8
7
3
8
7
3
25
12
12
ASMCP170/CL
32 32 40
12
6
6
12
6
6
All Dimensions in mm
50
3
3
II 2 GD
EEx d IIB T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB
SIRA04ATEX1266X. SIRA03ATEX1215. SIRA04ATEX1267X
POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
7.0 Watts at +40˚C, 62 Watts at +50˚C, 200 Watts at +50˚C
ASMCP130/SS - 210mm x 185mm x 152mm
ASMCP150/SS– 335mm x 310mm x 200mm
ASMCP170/SS - 560mm x 560mm x 245mm
Cast Stainless Steel 316
Self colour
ASMCP130/SS 21Kg
ASMCP150/SS 52Kg
ASMCP170/SS 195Kg
M8 allen head stainless steel screws
One piece closed cell 4mm neoprene
Base- internal and external EEx e brass clamps
Cover – internal EEx e brass clamp
2 steel mounting straps. 8mm diameter fixing holes
Entries are to customer requirements. The table below give a guide to the gland
capacity for the more commonly used gland sizes. For other gland sizes or mixed
sizes consult Walsall Technical Sales.
All entries are fitted with an EEx d approved stopping plug or cable gland.
Enclosure
Gland Size mm
Sides A & B
Sides C & D
ASMCP130/SS
20 25 32
5
5
2
5
5
3
20
11
11
ASMCP150/SS
25 32 40
8
7
3
8
7
3
25
12
12
ASMCP170/SS
32 32 40
12
6
6
12
6
6
All Dimensions in mm
50
3
3
PANEL LAYOUTS.
PANEL LAYOUTS.
Enclosure
ASMCP130/CI ASMCP150/CI ASMCP170/CI
4
No. of horizontal rails.
1
2
No.of Actuators Permitted in Cover
2
12
16
147
ATEX/GOST
ENTRY SPECIFICATION
Entries are to customer requirements. The table below give a guide to the gland
capacity for the more commonly used gland sizes. For other gland sizes or mixed
sizes consult Walsall Technical Sales.
All entries are fitted with an EEx d approved stopping plug or cable gland.
ASMCP130/CL
20 25 32
5
5
2
5
5
3
Group II Cat 2
ENCLOSURE SPECIFICATION
ENTRY SPECIFICATION
Enclosure
Gland Size mm
Sides A & B
Sides C & D
T6
HAZARDOUS AREA SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Zones 1,2,21,22
The EEx d approved actuators listed can be used to operate standard (not EEx
approved) electrical and electronic equipment installed in EEx d approved
enclosures of cast stainless steel to engineer customised EEx d approved control
systems. Three sizes of enclosures are available.
The type of equipment that can be installed in the enclosures is limited by the
volume of the equipment and the maximum power dissipation permitted.
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
EEx d IIB
Enclosure
ASMCP130/SS ASMCP150/SS ASMCP170/SS
No. of horizontal rails.
1
2
4
2
12
16
No.of Actuators Permitted in Cover
ORDERING INFORMATION
ORDERING INFORMATION
The information given above is for guidance only. In practice customised control
panels are specified jointly between the customer and Walsall Technical Sales.
Following an initial discussion, drawings are produced by Walsall for approval by
the customer. Orders can be placed and accepted using the drawings for
reference.
The information given above is for guidance only. In practice customised control
panels are specified jointly between the customer and Walsall Technical Sales.
Following an initial discussion, drawings are produced by Walsall for approval by
the customer. Orders can be placed and accepted using the drawings for
reference.
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
148
PART 3.4
COMBINED
EEx d AND EEx edm
CONTROL SYSTEMS
Enclosures of different protection concepts may be combined to form
more complex systems which efficiently utilise the benefits of each.
For example a common combination is that of an electrical device
that can only be housed in an EEx d enclosure is connected to an
EEx e enclosure which houses the incoming and outgoing cables.
This reduces the size of the EEx d enclosure and helps with the
installation wiring which is direct into an EEX e enclosure without
flamepaths to concern the installer. The interconnection is via an
approved line bush/es which provides an EEx d path through the
wall of both enclosures, see diagram opposite.
APPROVE
LINE B
Photograph of typical interconnected systems shown opposite.
CUSTOMISING
As a vertically integrated manufacturer Walsall can customise
combined systems at each stage of the manufacturing
process to meet individual customer requirements.
Frame work for mounting multiple assemblies of
EEx e/ EEx d control panels and terminal enclosures
are available for customers specification.
149
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
150
PART 4.0
POWER SWITCHING
A comprehensive range of changeover switches to 63 amps, 4 and 6 pole switch
disconnectors to 315 amps and fused switches to 125 amps as standard all housed in
EEx d approved enclosures in cast iron and cast aluminium. Other variations in operating
current and number of poles and auxiliaries are available to order.
4.1 RS Range
Page 153
EEx d Changeover switches to 63 amps as standard
4.2 SD Range
Page 157
EEx d Switch Disconnectors to 315 amps as standard
4.3 SF Range
Page 167
EEx d Fused Switch Disconnectors to 125 amps as standard
151
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
152
Power Switching - Cast Iron Enclosure
Type RS - EEx d 20, 25, 32 Amps Changeover Switch
PART 4.1
RS RANGE
EEx d IIB
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
EEx d 4 pole change over switches rated from 20 Amps to 63 Amps
in cast iron enclosures.
Type RS20 – 20 Amps 4 Pole Changeover Switch
Page 154
Type RS25 – 25 Amps 4 Pole Changeover Switch
Page 154
Type RS32 – 32 Amps 4 Pole Changeover Switch
Page 154
Type RS63 – 63 Amps 4 Pole Changeover Switch
Page 155
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
II 2 GD
EEx d IIB T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB
SIRA02ATEX1332. GOST ‘R’ POCC GB. гБ05 BO1132
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Colour
Weight
Cover fixing
Gasket
Security
Earthing
Mounting
168mm x 145mm x 138mm
Cast iron to 180BSI1452:1997
Zinc rich epoxy powder primer and epoxy powder top coat
Black
6 Kg
M6 allen head stainless steel screws
By grease
Switches with an off position have a padlock ‘off’ ‘facility
as standard
Internal and external EEx e brass clamps on base
Earth on cover
Two steel mounting straps with 8.0mm fixing holes
ENTRY SPECIFICATION
1x20mm EEx d threaded hole at A, B and C as standard.
All entries are fitted with EEx d stopping plugs as standard
25mm entries are available as an option
ELECTRICAL SPECIFICATION
Switch: 4 pole rotary cam switch to IEC60947-3
Voltage
Volts
380-440
380-440
380-440
Current
AC21A (A)
20
25
32
Power
AC23A(Kw)
5.5
7.5
11
AC-3(Kw)
3.7
5.5
7.5
Conductor Size
mmsq. Max.
2.5
6.0
6.0
All Dimensions in mm
ORDERING INFORMATION
Current Rating
20 amps
20 amps
25 amps
25 amps
32 amps
32 amps
For 25 mm entries add/25 to Product Code e.g. RS20C/25
153
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Switch Position
1 - Off - 2
1-2
1 - Off - 2
1-2
1 - Off - 2
1-2
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Product Code
RS20C
RS20
RS25C
RS25
RS32C
RS32
154
Power Switching - Cast Iron Enclosure
Type RS - EEx d 63 Amps Changeover Switch
EEx d IIB
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
II 2 GD
EEx d IIB T6
-40˚C to + 50˚C
Zones 1,2,21,22. Groups IIA, IIB
SIRA02ATEX1332. GOST ‘R’ POCC GB. гБ05. BO1132
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Colour
Weight
Cover fixing
Gasket
Security
Earthing
Mounting
220mm x 185mm x 161mm
Cast iron to 180BSI1452:1997
Zinc rich epoxy powder primer and epoxy powder top coat
Black
11Kg
M6 allan head stainless steel screws
By grease
Switches with an off position have a padlock ‘off’ ‘facility
as standard
Internal and external EEx e brass clamps on base
Earth on cover
Two steel straps with 8.0mm fixing holes
ENTRY SPECIFICATION
1x20mm EEx d threaded hole at A, B and C as standard
All entries are fitted with EEx d stopping plugs as standard
25mm entries are available as an option
ELECTRICAL SPECIFICATION
Switch: 4 pole rotary cam switch to IEC60947-3
Voltage
Volts
690
Current
AC21A (A)
63
Power
AC23A(Kw)
22
AC-3(Kw)
18.5
Conductor Size
mmsq. Max.
16
All Dimensions in mm
ORDERING INFORMATION
Current Rating
63 amps
63 amps
For 25 mm entries add/25 to Product Code e.g. E110006/25
155
Switch Position
1 - Off - 2
1- 2
Product Code
RS63C
RS63
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
156
Power Switching - Cast Iron Enclosure
Type SD - EEx d 20-32 Amps 4 Pole Switch Disconnector
PART 4.2
SD RANGE
EEx d IIB
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
EEx d switch disconnectors (to IEC60947-3) in a choice of
cast aluminum or cast iron enclosures, with current ratings
from 20 Amps to 315 Amps. The standard versions have 4 or
6 poles and 2 auxiliaries. Other configurations can be
engineered.
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
II 2 GD
EEx d IIB T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB
SIRA02ATEX1332 GOST’R’ POCC GB. гБ05. B01132
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
Type SD204 – 20Amps 4 Pole Switch Disconnector
Page 158
Type SD254 – 25Amps 4 Pole Switch Disconnector
Page 158
Type SD324 – 32Amps 4 Pole Switch Disconnector
Page 158
Type SD256 – 25Amps 6 Pole Switch Disconnector
Page 159
Type SD326 – 32Amps 6 Pole Switch Disconnector
Page 159
Type SD634 – 63Amps 4 Pole Switch Disconnector
Page 160
Type SD636 – 63Amps 6 Pole Switch Disconnector
Page 161
Type SD804 – 80Amps 4 Pole Switch Disconnector
Page 162
Type SD806 – 80Amps 6 Pole Switch Disconnector
Page 163
Dimensions
Material
Finish
Colour
Weight
Cover fixing
Gasket
Security
Earthing
Mounting
Type SD1004 – 100Amps 4 Pole Switch Disconnector Page 162
Type SD1006 – 100Amps 6 Pole Switch Disconnector Page 163
Type SD1254 – 125Amps 4 Pole Switch Disconnector Page 164
Type SD1256 – 125Amps 6 Pole Switch Disconnector Page 165
Type SD1604 – 160Amps 4 Pole Switch Disconnector Page 164
168mm x 145mm x 138mm
Cast iron to 180BSI1452:1997
Zinc rich epoxy powder primer and epoxy powder top coat
Black
11 Kg
M6 allen head stainless steel screws
By grease
Switches have a padlock ‘off’ ‘facility as standard
Internal and external EEx e brass clamps on base
Earth on cover
Two steel mounting straps with 8.0mm fixing holes
ENTRY SPECIFICATION
1x20mm EEx d threaded hole at A and B as standard.
All entries are fitted with EEx d stopping plugs as standard
25mm entries are available as an option
ELECTRICAL SPECIFICATION
Switch: 4 pole switch disconnector to IEC 60947-3 with 2 n/o early break auxiliaries
as standard.
Voltage
Volts
380-440
380-440
380-440
Current
AC21A (A)
20
25
32
Power
AC23A(Kw)
5.5
7.5
11.0
AC-3(Kw)
3.7
5.5
7.5
Conductor Size
mmsq. Max.
2.5
6.0
6.0
All Dimensions in mm
Type SD1606 – 160Amps 6 Pole Switch Disconnector Page 165
Type SD2004 – 200Amps 4 Pole Switch disconnector Page 164
Type SD2006 – 200Amps 6 Pole Switch disconnector Page 165
Type SD2504 – 250Amps 4 Pole Switch Disconnector Page 166
Type SD2506 – 250Amps 6 Pole Switch Disconnector Page 166
Type SD3154 – 315Amps 4 Pole Switch Disconnector Page 166
Type SD3156 – 315Amps 6 Pole Switch Disconnector Page 166
157
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
ORDERING INFORMATION
Current Rating
20 amps
25 amps
32 amps
For 25 mm entries add/25 to Product Code.
Switch Position
0-1
0-1
0-1
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Product Code
SD204
SD254
SD324
158
Power Switching - Cast Aluminium or Cast Iron Enclosure
Type SD - EEx d 25-32 Amps 6 Pole Switch Disconnector
EEx d IIB
Zones 1,2,21,22
T6
Group II Cat 2
Power Switching - Cast Iron Enclosure
Type SD - EEx d 63 Amps 4 Pole Switch Disconnector
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
Finish
Colour
Weight
Cover fixing
Gasket
Security
Earthing
Mounting
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
II 2 GD
EEx d IIB T6
-40˚C to + 50˚C
Zones 1,2,21,22. Groups IIA, IIB
SIRA03ATEX1215 GOST’R’ POCC GB. гБ05. B01132
IP66 to EN60529:1992
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
ENCLOSURE SPECIFICATION
Dimensions
Material
EEx d IIB
II 2 GD
EEx d IIB T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB
SIRA02ATEX1332
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
210mm x 185mm x 153mm
Cast iron to 180BSI1452:1997
Cast aluminium to LM6
Zinc rich epoxy powder primer and epoxy powder top coat
Black
Cast iron 20Kg, Cast aluminium 8Kg
M6 allen head stainless steel screws
By grease
Switches have a padlock ‘off’ ‘facility as standard
Internal and external EEx e brass clamps on base
Earth on cover
Two steel mounting straps with 8.0mm fixing holes
Dimensions
Material
Finish
Colour
Weight
Cover fixing
Gasket
Security
Earthing
Mounting
220mmx185mmx161mm
Cast iron to 180BSI1452:1997
Zinc rich epoxy powder primer and epoxy powder top coat
Black
11 Kg
M6 allen head stainless steel screws
By grease
Switches have a padlock ‘off’ ‘facility as standard
Internal and external EEx e brass clamps on base
Earth on cover
Two steel mounting straps with 8.0mm fixing holes
ENTRY SPECIFICATION
ENTRY SPECIFICATION
1x20mm EEx d threaded hole at A, B and C as standard.
All entries are fitted with EEx d stopping plugs as standard
25mm entries are available as an option
1x20mm EEx d threaded hole at A, B and C as standard
All entries are fitted with EEx d stopping plugs as standard
ELECTRICAL SPECIFICATION
ELECTRICAL SPECIFICATION
Switch: Switch disconnector to IEC 60947-3 with 2 n/o early break auxiliaries.
Switch: 6 pole switch disconnector to IEC 60947-3 with 2 n/o early break
auxiliaries as standard
Voltage
Volts
380-440
380-440
380-440
Current
AC21A (A)
20
25
32
Power
AC23A(Kw)
5.5
7.5
11.0
AC-3(Kw)
3.7
5.5
7.5
Voltage
Volts
380-440
Conductor Size
mmsq. Max.
2.5
6.0
6.0
Current
AC21A (A)
63
Power
AC23A(Kw)
22
AC-3(Kw)
18.5
Conductor Size
mmsq. Max.
16
All Dimensions in mm
All Dimensions in mm
ORDERING INFORMATION
Current Rating
25 amps
32 amps
25 amps
32 amps
For 25 mm entries add/25 to Product Code.
159
Enclosure Material
Cast Iron
Cast Iron
Cast Aluminium
Cast Aluminium
Switch Position
0-1
0-1
0-1
0-1
Product Code
SDI256
SDI326
SDA256
SDA326
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
ORDERING INFORMATION
Notes:
Current Rating
Switch Position
63 amps
0-1
For 25 mm entries add/25 to Product Code.
Other entry configurations and sizes are available please ask Walsall sales for information.
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Product Code
SD634
160
Power Switching - Cast Aluminum or Cast Iron Enclosure
Type SD - EEx d 63 Amps 6 Pole Switch Disconnector
EEx d IIB
Zones 1,2,21,22
T6
Group II Cat 2
Power Switching - Cast Aluminium or Cast Iron Enclosure
Type SD - EEx d 80-100 Amps 4 Pole Switch Disconnector
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
II 2 GD
EEx d IIB T6
-40˚C to + 50˚C
Zones 1,2,21,22. Groups IIA, IIB
SIRA04ATEX1266X. GOST ‘R’ POCC GB.
IP66 to EN60529:1992
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
гБ05. BO1132
Colour
Weight
Cover fixing
Gasket
Security
Earthing
Mounting
Dimensions
Material
Colour
Weight
Cover fixing
Gasket
Security
Earthing
Mounting
ATEX/GOST
II 2 GD
EEx d IIB T6
-20˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB
SIRA03ATEX1215 GOST ‘R’ POCC GB. гБ05. BO1132
IP66 to EN60529:1992
ENTRY SPECIFICATION
1x20mm EEx d threaded hole at A, B and C as standard
All entries are fitted with EEx d stopping plugs as standard
25mm entries are available as an option
1x25mm EEx d threaded hole at A, B and C as standard.
All entries are fitted with EEx d stopping plugs as standard
32mm entries are available as an option
ELECTRICAL SPECIFICATION
ELECTRICAL SPECIFICATION
Switch: 6 pole switch disconnector to IEC 60947-3 with 2 n/o early break auxiliaries
as standard
Current
AC21A (A)
63
Group II Cat 2
210mm x 185mm x 153mm
Cast iron to 180BSI1452:1997
Cast aluminium to LM6
Cast iron - zinc rich epoxy powder primer and
epoxy powder top coat
Cast aluminium - epoxy powder coat
Black
Cast iron 20 Kg. Cast aluminium 8 Kg
M6 allen head stainless steel screws
By grease
Switches have a padlock ‘off’ ‘facility as standard
Internal and external EEx e brass clamps on base
Earth on cover
Two steel mounting straps with 8.0mm fixing holes
Finish
ENTRY SPECIFICATION
Voltage
Volts
380-440
T6
ENCLOSURE SPECIFICATION
210mm x 185mm x 153mm
Cast iron to 180BSI1452:1997
Cast aluminium to LM6
Cast iron- zinc rich epoxy powder primer and
epoxy powder top coat
Cast aluminium – epoxy powder coat
Black
Cast iron 20Kg Cast aluminium 8Kg
M6 allen head stainless steel screws
By grease
Switches have a padlock ‘off’ ‘facility as standard
Internal and external EEx e brass clamps on base
Earth on cover
Two steel mounting straps with 8.0mm fixing holes
Finish
Zones 1,2,21,22
HAZARDOUS AREA SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material
EEx d IIB
Power
AC23A(Kw)
22
AC-3(Kw)
18.5
Switch: 4 pole switch disconnector to IEC60947 with 2 n/o early break auxiliaries
as standard.
Conductor Size
mmsq. Max.
16
Voltage
Volts
380-440
380-440
All Dimensions in mm
Current
AC21A (A)
80
100
Power
AC23A(Kw)
30
37
AC-3(Kw)
22
30
Conductor Size
mmsq. Max.
35
35
All Dimensions in mm
ORDERING INFORMATION
Current Rating
80 amps
100 amps
80 amps
100 amps
ORDERING INFORMATION
Current Rating
63 amps
63 amps
Enclosure Material
Cast Iron
Cast Aluminium
Switch Position
0-1
0-1
Product Code
SDI636
SDA636
For 25 mm entries add/25 to Product Code.
161
Notes:
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Enclosure Material
Cast Iron
Cast Iron
Cast Aluminium
Cast Aluminium
Switch Position
0-1
0-1
0-1
0-1
Product Code
SDI804
SDI1004
SDA804
SDA1004
For 32 mm entries add/32 to Product Code.
Other entry configurations and sizes are available please ask Walsall sales for information.
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
162
Power Switching - Cast Aluminium or Cast Iron Enclosure
Type SD - EEx d 80-100 Amps 6 Pole Switch Disconnector
EEx d IIB
Zones 1,2,21,22
T6
Group II Cat 2
Power Switching - Cast Aluminium or Cast Iron Enclosure
Type SD - EEx d 125-200 Amps 4 Pole Switch Disconnector
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
II 2 GD
EEx d IIB T6
-20˚C to + 50˚C
Zones 1,2,21,22. Groups IIA, IIB
SIRA04ATEX1266X. GOST ‘R’ POCC GB. гБ05. BO1132
IP66 to EN60529:1992
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
Colour
Weight
Cover fixing
Gasket
Security
Earthing
Mounting
Dimensions
Material
Colour
Weight
Cover fixing
Gasket
Security
Earthing
Mounting
ATEX/GOST
II 2 GD
EEx d IIB T6
-20˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB
SIRA04ATEX1266X. GOST ‘R’ POCC GB. гБ05. BO1132
IP66 to EN60529:1992
ENTRY SPECIFICATION
1x25mm EEx d threaded hole at A, B and C as standard
All entries are fitted with EEx d stopping plugs as standard
32mm entries are available as an option
1x25mm EEx d threaded hole at A, B and C as standard.
All entries are fitted with EEx d stopping plugs as standard
32mm entries are available as an option
ELECTRICAL SPECIFICATION
ELECTRICAL SPECIFICATION
Switch: 6 poles witch disconnector to IEC60947 with 2 n/o early break auxiliaries
as standard
Current
AC21A (A)
80
100
Group II Cat 2
335mm x 310mm x 200mm
Cast iron to 180BSI1452:1997
Cast aluminium to LM6
Cast iron - zinc rich epoxy powder primer and
epoxy powder top coat
Cast aluminium – epoxy powder coat
Black
Cast iron 50Kg. Cast aluminium 18Kg
M6 allen head stainless steel screws
By grease
Padlock ‘off’ ‘facility as standard
Internal and external EEx e brass clamps on base
Earth on cover
Two steel mounting straps with 10mm fixing holes
Finish
ENTRY SPECIFICATION
Voltage
Volts
380-440
380-440
T6
ENCLOSURE SPECIFICATION
335mm x 310mm x 200mm
Cast iron to 180BSI1452:1997
Cast aluminium to LM6
Cast iron - zinc rich epoxy powder primer and
epoxy powder top coat
Cast aluminium – epoxy powder coat
Black
Cast iron 50Kg. Cast aluminium 18Kg
M6 allen head stainless steel screws
By grease
Switches have a padlock ‘off’ ‘facility as standard
Internal and external EEx e brass clamps on base
Earth on cover
Two steel mounting straps with 10mm fixing holes
Finish
Zones 1,2,21,22
HAZARDOUS AREA SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material
EEx d IIB
Power
AC23A(Kw)
30
37
AC-3(Kw)
22
30
Switch: 4 and 6 pole switch disconnector to IEC 60947 -3 with 2 n/o early break
auxiliaries as standard.
Conductor Size
mmsq. Max.
35
35
Voltage
Volts
380-440
380-440
380-440
All Dimensions in mm
Current
AC21A (A)
125
160
200
Power
AC23A(Kw)
45
55
75
AC-3(Kw)
37
45
55
Conductor Size
mmsq. Max.
95
95
185
All Dimensions in mm
ORDERING INFORMATION
Current Rating
125 amps
160amps
200 amps
125 amps
160 amps
200 amps
ORDERING INFORMATION
Current Rating
80 amps
100 amps
80 amps
100 amps
Notes:
163
Enclosure Material
Cast Iron
Cast Iron
Cast Aluminium
Cast Aluminium
Switch Position
0-1
0-1
0-1
0-1
Product Code
SDI806
SDI1006
SDA806
SDA1006
For 32 mm entries add/32 to Product Code.
Other entry configurations and sizes are available please ask Walsall sales for information.
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Notes:
Enclosure Material
Cast Iron
Cast Iron
Cast Iron
Cast Aluminium
Cast Aluminium
Cast Aluminium
Switch Position
O-1
O-1
O-1
O-1
O-1
O-1
Product Code
SDI1254
SDI1604
SDI2004
SDA1254
SDA1604
SDA2004
For 32 mm entries add/32 to Product Code.
Other entry configurations and sizes are available please ask Walsall sales for information.
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
164
Power Switching - Cast Aluminium or Cast Iron Enclosure
Type SD - EEx d 125-200 Amps 6 Pole Switch Disconnector
EEx d IIB
Zones 1,2,21,22
T6
Group II Cat 2
Power Switching - Cast Aluminium or Cast Iron Enclosure
Type SD - EEx d 250-315amps 4 & 6 Pole Switch Disconnector
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
II 2 GD
EEx d IIB T6
-20˚C to + 50˚C
Zones 1,2,21,22. Groups IIA, IIB
SIRA04ATEX1266X. GOST ‘R’ POCC GB. гБ05. BO1132
IP66 to EN60529:1992
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
Colour
Weight
Cover fixing
Gasket
Security
Earthing
Mounting
Dimensions
Material
Finish
Colour
Weight
Cover fixing
Gasket
Security
Earthing
Mounting
ENTRY SPECIFICATION
ATEX/GOST
II 2 GD
EEx d IIB T6
-20˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB
SIRA04ATEX1266X. GOST ‘R’ POCC GB. гБ05. BO1132
IP66 to EN60529:1992
335mm x 310mm x 200mm
Cast iron to 180BSI1452:1997
Cast aluminium to LM6
Cast iron - zinc rich epoxy powder primer and
epoxy powder top coat
Cast aluminium – epoxy powder coat
Black
Cast iron 50 Kg. Cast aluminium 18 Kg
M6 allen head stainless steel screws
By grease
Padlock ‘off’ ‘facility as standard
Internal and external EEx e brass clamps on base
Earth on cover
Two steel mounting straps with 10mm fixing holes
1x25mm EEx d threaded hole at A, B and C as standard.
All entries are fitted with EEx d stopping plugs as standard
32mm entries are available as an option
ELECTRICAL SPECIFICATION
ELECTRICAL SPECIFICATION
Switch: 4 and 6 pole switch disconnector to IEC 60947 -3 with 2 n/o early break
auxiliaries as standard
Current
AC21A (A)
125
160
200
Group II Cat 2
ENTRY SPECIFICATION
1x25mm EEx d threaded hole at A, B and C as standard
All entries are fitted with EEx d stopping plugs as standard
32mm entries are available as an option
Voltage
Volts
380-440
380-440
380-440
T6
ENCLOSURE SPECIFICATION
335mm x 310mm x 200mm
Cast iron to 180BSI1452:1997
Cast aluminium to LM6
Cast iron - zinc rich epoxy powder primer and
epoxy powder top coat
Cast aluminium – epoxy powder coat
Black
Cast iron 50Kg. Cast aluminium 18Kg
M6 allen head stainless steel screws
By grease
Padlock ‘off’ ‘facility as standard
Internal and external EEx e brass clamps on base
Earth on cover
Two steel mounting straps with 10mm fixing holes
Finish
Zones 1,2,21,22
HAZARDOUS AREA SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material
EEx d IIB
Power
AC23A(Kw)
45
55
75
AC-3(Kw)
37
45
55
Switch: 4 and 6 pole switch disconnector to IEC 60947 -3 with 2 n/o early break
auxiliaries as standard.
Conductor Size
mmsq. Max.
95
95
185
Voltage
Volts
380-440
380-440
All Dimensions in mm
Current
AC21A (A)
200
315
Power
AC23A(Kw)
90
110
AC-3(Kw)
55
75
Conductor Size
mmsq. Max.
185
185
All Dimensions in mm
ORDERING INFORMATION
Current Rating
250 amps
250 amps
315 amps
315 amps
250 amps
250 amps
315 amps
315 amps
ORDERING INFORMATION
Current Rating
125 amps
160amps
200 amps
125 amps
160 amps
200 amps
Notes:
165
Enclosure Material
Cast Iron
Cast Iron
Cast Iron
Cast Aluminium
Cast Aluminium
Cast Aluminium
Switch Position
O-1
O-1
O-1
O-1
O-1
O-1
Product Code
SDI1256
SDI1606
SDI2006
SDA1256
SDA1606
SDA2006
For 32 mm entries add/32 to Product Code.
Other entry configurations and sizes are available please ask Walsall sales for information.
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Notes:
Enclosure Material
Cast Iron
Cast Iron
Cast Iron
Cast Iron
Cast Aluminum
Cast Aluminum
Cast Aluminum
Cast Aluminum
Switch Position
O-1
O-1
O-1
O-1
O-1
O-1
O-1
O-1
Poles
4
6
4
6
4
6
4
6
Product Code
SDI2504
SDI2506
SDI3154
SDI3156
SDA2504
SDA2506
SDA3154
SDA3156
For 32 mm entries add/32 to Product Code.
Other entry configurations and sizes are available please ask Walsall sales for information.
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
166
Power Switching - Cast Aluminium or Cast Iron Enclosure
Type SF - EEx d 20-63 Amp 4 & 6 Pole Fused Switch Disconnector
PART 4.3
SF RANGE
EEx d IIC
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
EEx d fused switch disconnectors (to IEC60947-3) in a
choice of cast aluminum or cast iron enclosures, with current
ratings from 20 Amps to 125 Amps. The standard versions
have 4 or 6 poles and 2 auxiliaries. Other configuations can
be engineered.
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
II 2 GD
EEx d IIB T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB
SIRA02ATEX1332 GOST’R’ POCC GB. гБ05. B01132
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
Type SF254 – 20 Amps 4 Pole Fused Switch Disconnector
Page 168
Dimensions
Material
Type SF256 – 25 Amps 6 Pole Fused Switch Disconnector
Page 168
Finish
Type SF324 – 32 Amps 4 Pole Fused Switch Disconnector
Page 168
Type SF326 – 32 Amps 6 Pole Fused Switch Disconnector
Page 168
Type SF634 – 63 Amps 4 Pole Fused Switch Disconnector
Page 168
Type SF636 – 63 Amps 6 Pole Fused Switch Disconnector
Page 168
Type SF804 – 80 Amps 4 Pole Fused Switch Disconnector
Page 169
Type SF806 – 80 Amps 6 Pole Fused Switch Disconnector
Page 169
Type SF1004 – 100 Amps 4 Pole Fused Switch Disconnector
Page 169
Type SF1006 – 100 Amps 6 Pole Fused Switch Disconnector
Page 169
Type SF1254 – 125 Amps 4 Pole Fused Switch Disconnector
Page 169
Type SF1256 – 125 Amps 6 Pole Fused Switch Disconnector
Page 169
Colour
Weight
Cover fixing
Gasket
Plastic components
Operator flamepath
Security
Earthing
Mounting
210mm x 185mm x 153mm
Cast iron to 180BSI1452:1997
Cast aluminium to LM6
Cast iron - zinc rich epoxy powder primer and
epoxy powder top coat
Cast aluminium – epoxy powder coat
Black
Cast iron 20Kg. Cast aluminium 8Kg
M6 allen head stainless steel screws
By grease
Polycarbonate
Brass shaft in brass housing
Switches have a padlock ‘off’ ‘facility as standard
Cover interlock (cover may not be opened unless switch is in
the off position)
Internal and external EEx e brass clamps on base
Earth on cover
Two steel mounting straps with 8.0mm fixing holes
ENTRY SPECIFICATION
1x20mm EEx d threaded hole at A, B and C as standard.
All entries are fitted with EEx d stopping plugs as standard
25mm entries are available as an option
ELECTRICAL SPECIFICATION
Fuses: European standard fuses to IEC 269.1&2
Switch: Switch disconnector to IEC 60947-3 with 2 n/o early break auxiliaries.
Voltage
Volts
380-440
380-440
380-440
Current
AC21A (A)
25
32
63
Power
AC23A(Kw)
7.5
11.0
22
AC-3(Kw)
5.5
7.5
18.5
Conductor Size
mmsq. Max.
6
6
16
All Dimensions in mm
ORDERING INFORMATION
Notes:
167
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Current Rating
Switch Position
20 amps
0-1
25 amps
0-1
0-1
32 amps
0-1
63 amps
0-1
20 amps
0-1
25 amps
0-1
32 amps
63 amps
0-1
For 25 mm entries add/25 to Product Code e.g. SF254/25
Poles
4
4
4
4
6
6
6
6
Product Code Aluminum
SFA204
SFA254
SFA324
SFA634
SFA206
SFA256
SFA326
SFA636
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Product Code Iron
SFI204
SFI254
SFI324
SFI634
SFI204
SFI256
SFI326
SFI636
168
Power Switching - Cast Aluminium or Cast Iron Enclosure
Type SF - EEx d 80-125 Amps 4 & 6 Pole Fused Switch Disconnector
EEx d IIC
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
II 2 GD
EEx d IIB T6
-40˚C to + 50˚C
Zones 1,2,21,22. Groups IIA, IIB
SIRA04ATEX1266X GOST’R’ POCC GB. гБ05. B01132
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Colour
Weight
Cover fixing
Gasket
Security
Earthing
Mounting
335mm x 310mm x 200mm
Cast iron to 180BSI1452:1997
Cast aluminium to LM6
Cast iron - zinc rich epoxy powder primer and
epoxy powder top coat
Cast aluminium – epoxy powder coat
Black
Cast iron 50Kg Cast aluminium 18Kg
M6 allen head stainless steel screws
By grease
Switches have a padlock ‘off’ ‘facility as standard
Cover interlock (cover may not be opened unless switch is
in the off position)
Internal and external EEx e brass clamps on base
Earth on cover
Two steel mounting straps with 10mm fixing holes
ENTRY SPECIFICATION
Switch disconnectors on route to
1x25mm EEx d threaded hole at A, B and C as standard
All entries are fitted with EEx d stopping plugs as standard
32mm entries are available as an option
Kazakhstan
ELECTRICAL SPECIFICATION
Fuses: European standard fuses to IEC 269.1&2
Switch: Switch disconnector to IEC 60947-3 with 2 n/o early break auxiliaries
Voltage
Volts
380-440
380-440
380-440
Current
AC21A (A)
80
100
125
Power
AC23A(Kw)
30
37
45
AC-3(Kw)
22
30
37
Conductor Size
mmsq. Max.
35
35
50
All Dimensions in mm
ORDERING INFORMATION
Notes:
169
Current Rating
Switch Position
0-1
80 amps
0-1
100 amps
0-1
125 amps
0-1
80 amps
0-1
100 amps
0-1
125 amps
For 32 mm entries add/32 to Product Code. eg SF1004/32
Poles
4
4
4
6
6
6
Product Code Aluminum
SFA804
SFA1004
SFA1254
SFA806
SFA1006
SFA1256
Product Code Iron
SFI804
SFI1004
SFI1254
SFI806
SFI1006
SFI1256
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
170
PART 5.0
MOTOR CONTROL
A comprehensive range of EEx d DOL and STAR - DELTA motor starters and starter/isolators
in a choice of cast iron and cast aluminum enclosures with ratings up to 30 kW.
5.1 DOL Range
Page 173
EEx d IIB Direct-on-line Starters and Starter/ Isolators to 30kW
5.2 SDS Range
Page 179
EEx d IIB Star-Delta and Starters and Starter/ Isolators to 30kW
171
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
172
Motor Control - Cast Iron Enclosure
Type DOL - EEx d 5.5 - 7.5 Amps DOL Starter
PART 5.1
DOL RANGE
EEx d IIB
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
EEx d IIB Direct-on-line Starters and Starter/Isoloators in a choice
of cast iron and cast aluminium enclosures from 5.5kW to 30kW.
All have a choice of coil voltages and overload currents.
Type DOL5.5
– 5.5 kW Direct on Line Starter
Page 174
Type DOL7.5
– 7.5 kW Direct on Line Starter
Page 174
Type DOL11
– 11kW
Direct on Line Starter
Page 175
Type DOL15
– 15 kW Direct on Line Starter
Page 175
Type DOL22
– 22 kW Direct on Line Starter
Page 176
Type DOL30
– 30 kW Direct on Line Starter
Page 176
Type DOLSD5.5
– 5.5 kW Starter Isolator
Page 177
Type DOLSD7.5
– 7.5 kW Starter Isolator
Page 177
Type DOLSD11
– 11 kW Starter Isolator
Page 177
Type DOLSD15
– 15 kW Starter Isolator
Page 177
Type DOLSD22
– 22 kW Starter Isolator
Page 177
Type DOLSD30
– 30 kW Starter Isolator
Page 177
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
II 2 GD
EEx d IIB T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB
SIRA02ATEX1332
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Colour
Weight
Cover fixing
Gasket
Earthing
Mounting
220mm x 185mm x 161mm
Cast iron to 180BSI1452:1997
Zinc rich epoxy powder primer and epoxy powder top coat
Black
11 Kg
M6 allen head stainless steel screws
By grease
Internal and external EEx e brass clamps on base
Earth on cover
Two steel straps with 8.0mm fixing holes
ENTRY SPECIFICATION
1x20mm EEx d threaded hole at A, B and C as standard.
All entries are fitted with EEx d stopping plugs as standard
25mm entries are available as an option
ELECTRICAL SPECIFICATION
Contactor: 1 and 3 phase, 50/60 Hz contactors to IEC947-4 with push
button operators fitted with thermal overload protection and coil voltages as
specified below.
kW
5.5
7.5
Contactor Ratings
Amps (AC3) Volts
12
415
16
415
Conductor Size
mmsq. Max.*
2.5
2.5
Coil Voltages
60Hz
50Hz
110
110
220
120
460
380
415
440
480
Overloads
Amps
Amps
0.14-0.23
2.00-3.30
0.20-0.33
3.00-5.00
0.30-0.50
4.50-7.50
0.45-0.75
6.00-10.00
0.60-1.00
9.00-15.00
0.90-1.50 14.00-23.00
1.40-2.30
All Dimensions in mm
* For flexible cable. For solid cable multiply by 1.6
ORDERING INFORMATION To order use the following sequence of letters and numbers.
DOL 5.5 3 415 1.4/2.3
TYPE
RATING
PHASES
COIL
VOLTAGE
OVERLOAD
CURRENT
Note: For 25 mm entries add/25 to Product Code
173
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
174
Motor Control - Cast Aluminium or Cast Iron Enclosure
Type DOL - EEx d 11-15kW DOL Starter
EEx d IIB
Zones 1,2,21,22
T6
Motor Control - Cast Aluminium or Cast Iron Enclosure
Type DOL - EEx d 22-30 kW DOL Starter
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
Finish
Colour
Weight
Cover fixing
Gasket
Plastic components
Operator flamepath
Earthing
Mounting
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
II 2 GD
EEx d IIB T6
-20˚C to + 50˚C
Zones 1,2,21,22. Groups IIA, IIB
SIRA03ATEX1215X. GOST ‘R’ POCC GB. гБ05. BO1132
IP66 to EN60529:1991
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
ENCLOSURE SPECIFICATION
Dimensions
Material
EEx d IIB
II 2 GD
EEx d IIB T6
-20˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB
SIRA04ATEX1266X GOST ‘R’ POCC GB. гБ05. BO1132
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
210mm x 185mm x 153mm
Cast iron to 180BSI1452:1997
Cast aluminium to LM6
Cast iron- Zinc rich epoxy powder primer and
epoxy powder top coat
Cast aluminium- epoxy powder coat
Black
Cast iron 20Kg, cast aluminium 8Kg
M6 allen head stainless steel screws.
By grease
Polycarbonate
Brass shaft in brass housing
Internal and external EEx e brass clamps on base
Earth on cover
Two steel mounting straps with 8.0mm fixing holes
Dimensions
Material
Finish
Colour
Weight
Cover fixing
Gasket
Earthing
Mounting
335mm x 310mm x 200mm
Cast iron to 180BSI1452:1997
Cast aluminium to LM6
Cast iron- Zinc rich epoxy powder primer and
epoxy powder top coat
Cast aluminium- epoxy powder coat
Black
Cast iron 50 Kg , cast aluminium 18 Kg
M6 allen head stainless steel screws
By grease
Internal and external EEx e brass clamps on base
Earth on cover
Two steel mounting straps with 10mm fixing holes
ENTRY SPECIFICATION
ENTRY SPECIFICATION
1x25mm EEx d threaded hole at A, B and C as standard.
All entries are fitted with EEx d stopping plugs as standard
32mm entries are available as an option
1x25mm EEx d threaded hole at A, B and C as standard
All entries are fitted with EEx d stopping plugs as standard
32mm entries are available as an option
ELECTRICAL SPECIFICATION
Contactor: 3 phase, 50/60 Hz contactors to IEC947-4 with push button operators,
fitted with thermal overload protection and coil voltages as specified below.
ELECTRICAL SPECIFICATION
Contactor: 3 phase, 50/60 Hz contactors to IEC947-4 with push button operators,
fitted with thermal overload protection and coil voltages as specified below.
kW
11
15
Contactor Ratings
Amps (AC3)
21
30
Volts
415
415
Conductor Size
mmsq. Max.*
2.5
6
Coil Voltages
60Hz
50Hz
110
110
220
120
460
380
415
440
480
Overloads
Amps
14-23
17-26
20-33
All Dimensions in mm
kW
22
30
Volts
415
415
Conductor Size
mmsq. Max.*
16
16
Coil Voltages
60Hz
50Hz
110
110
220
120
460
380
415
440
480
500
690
Overloads
Amps
28-42
35-50
46-65
* For flexible cable. For solid cable multiply by 1.6
* For flexible cable. For solid cable multiply by 1.6
ORDERING INFORMATION To order use the following sequence of letters and numbers.
ORDERING INFORMATION To order use the following sequence of letters and numbers.
DOL 15 3 415 20/33
TYPE
Note1:
175
Contactor Ratings
Amps (AC3)
48
55
RATING
PHASES
COIL
VOLTAGE
DOL 22 3 415 35/50
OVERLOAD
CURRENT
For 25 mm entries add/25 to Product Code
For Enclosures in cast aluminum add A to product code and I for Cast Iron Enclosures
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
All Dimensions in mm
TYPE
Note1:
RATING
PHASES
COIL
VOLTAGE
OVERLOAD
CURRENT
For 25 mm entries add/25 to Product Code
For Enclosures in cast aluminum add A to product code and I for Cast Iron Enclosures
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
176
Motor Control - Cast Aluminium or Cast Iron Enclosure
Type DOLSD - EEx d 5.5-30kW DOL Starter/Isolator
EEx d IIB
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
II 2 GD
EEx d IIB T6
-20˚C to + 50˚C
Zones 1,2,21,22. Groups IIA, IIB
SIRA042ATEX1266X. GOST ‘R’ POCC. GB. гБ05. BO1132
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Weight
Cover fixing
Gasket
Earthing
Mounting
335mm x 310mm x 200mm
Cast iron to 180BSI1452:1997
Cast aluminium to LM6
Cast iron- Zinc rich epoxy powder primer and
epoxy powder top coat
Cast aluminium- epoxy powder coat
Cast iron 50Kg , cast aluminium 18Kg
M6 allen head stainless steel screws
By grease
Internal and external EEx e brass clamps on base
Earth on cover
Two steel mounting straps with 10mm fixing holes
ENTRY SPECIFICATION
1x25mm EEx d threaded hole at A, B and C as standard.
All entries are fitted with EEx d stopping plugs as standard
32mm entries are available as an option
ELECTRICAL SPECIFICATION
Contactor: 3 phase, 50/60 Hz contactors to IEC947-4 with push button
operators, fitted with thermal overload protection and coil voltages as specified below
Isolator: Switch disconnector to IEC 60947-3 with2 n/o early break auxiliaries
as standard.
kW
5.5
7.5
11
15
22
30
Contactor Ratings
Amps (AC3)
12
16
21
30
48
55
Volts
415
415
415
415
415
415
Conductor Size
mmsq. Max.*
2.5
2.5
2.5
6
16
16
Coil Voltages
50Hz
60Hz
110
110
220
120
460
380
415
440
480
Overloads
Amps
Amps
0.14-0.23
6-10
0.20-0.33
9-15
0.30-0.50
14-23
0.45-0.75
17-26
0.60-1.00
20-33
0.90-1.50
28-42
1.40-2.30
35-50
2.0-3.3
46-65
3-5
60-82
4.5-7.5
70-95
All Dimensions in mm
* For flexible cable. For solid cable multiply by 1.6
ORDERING INFORMATION To order use the following sequence of letters and numbers.
DOL/SD 22 3 415 35/50
TYPE
Note1:
177
RATING
PHASES
COIL
VOLTAGE
OVERLOAD
CURRENT
For 25 mm entries add/25 to Product Code
For Enclosures in cast aluminum add A to product code and I for Cast Iron Enclosures
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
178
Motor Control - Cast Aluminium or Cast Iron Enclosure
Type SDS - EEx d 11-30kW Star Delta Starter
PART 5.2
SDS RANGE
EEx d IIB
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
EEx d IIB Star Delta and Starter/Isolators in a choice
of cast iron and cast aluminium enclosures from 5.5kW to 30kW.
All have a choice of coil voltages and overloads currents.
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
Type SDS11 – 11kw Star-Delta Starter
Page 180
Type SDS15 – 15kw Star-Delta Starter
Page 180
Type SDS22 – 22kw Star-Delta Starter
Page 180
Dimensions
Material
Type SDS30 – 30kw Star-Delta Starter
Page 180
Finish
Type SDSI11 – 11kw Star-Delta Starter Isolator
Page 181
Type SDSI15 – 15kw Star-Delta Starter Isolator
Page 181
Type SDSI22 – 22kw Star-Delta Starter Isolator
Page 181
Type SDSI30 – 30kw Star-Delta Starter Isolator
Page 181
Colour.
Weight
Cover fixing
Gasket
Plastic components
Operator flamepath
Earthing
II 2 GD
EEx d IIB T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB
SIRA04ATEX1266X. GOST ‘R’ POCC GB. гБ05 BO1132
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
Mounting
335mm x 310mm x 200mm
Cast iron to 180BSI1452:1997
Cast aluminium to LM6
Cast iron- Zinc rich epoxy powder primer and
epoxy powder top coat
Cast aluminium- epoxy powder coat
Black
Cast iron 50 Kg , cast aluminium 18 Kg
M6 allen head stainless steel screws
By grease
Polycarbonate
Brass shaft in brass housing
Internal and external EEx e brass clamps on base
Earth on cover
Two steel mounting straps with 10mm fixing holes
ENTRY SPECIFICATION
1x25mm EEx d threaded hole at A, B and C as standard.
All entries are fitted with EEx d stopping plugs as standard
32mm entries are available as an option
ELECTRICAL SPECIFICATION
Contactor: 3 phase, 50/60 Hz contactors to IEC947-4 with push button operators,
fitted with thermal overload protection and coil voltages as specified below.
kW
11
15
22
30
Contactor Ratings
Amps (AC3)
21
30
48
58
Volts
415
415
415
415
Coil Voltages
Conductor Size
60Hz
mmsq. Max.* 50Hz
2.5
10/120 110
6
380/415 240
460
16
440
480
16
Overloads
Amps
17-26
20-30
28-42
35-50
46-65
60-82
70-95
All Dimensions in mm
* For flexible cable. For solid cable multiply by 1.6
ORDERING INFORMATION To order use the following sequence of letters and numbers.
SDS 15 415 28/45
TYPE
Note1:
179
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
RATING
COIL OVERLOAD
VOLTAGE CURRENT
For 25 mm entries add/25 to Product Code
For Enclosures in cast aluminum add A to product code and I for Cast Iron Enclosures
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
180
Motor Control - Cast Aluminium or Cast Iron Enclosure
Type SDSI - EEx d 11- 30kW Star Delta Starter/Isolator
EEx d IIB
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
II 2 GD
EEx d IIB T6
-20˚C to + 50˚C
Zones 1,2,21,22. Groups IIA, IIB
SIRA04ATEX1266X GOST ‘R’ POCC GB гБ05 BO1132
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Weight
Cover fixing
Gasket
Plastic components
Operator flamepath
Earthing
Mounting
335mm x 310mm x 200mm
Cast iron to 180BSI1452:1997
Cast aluminium to LM6
Cast iron- Zinc rich epoxy powder primer and
epoxy powder top coat
Cast aluminium- epoxy powder coat
Cast iron 50Kg , cast aluminium 18Kg
M6 allen head stainless steel screws
By grease
Polycarbonate
Brass shaft in brass housing
Internal and external EEx e brass clamps on base
Earth on cover
Two steel mounting straps with 10mm fixing holes
ENTRY SPECIFICATION
1x25mm EEx d threaded hole at A, B and C as standard
All entries are fitted with EEx d stopping plugs as standard
32mm entries are available as an option
EEx d control panels designed and
manufactured for a major process
ELECTRICAL SPECIFICATION
installation in Abu Dhabi
Contactor: 3 phase, 50/60 Hz contactors to IEC947-4 with push button
operators, fitted with thermal overload protection and coil voltages as specified below
Isolator: Switch disconnector to IEC 60947-3 with 2 n/o early break auxiliaries
as standard
kW
11
15
22
30
Contactor Ratings
Amps (AC3)
21
30
48
58
Volts
415
415
415
415
Coil Voltages
Conductor Size
mmsq. Max.* 50Hz
60Hz
2.5
10/120 110
6
380/415 240
16
460
440
16
480
Overloads
Amps
17-26
20-30
28-42
35-50
46-65
60-82
70-95
All Dimensions in mm
* For flexible cable. For solid cable multiply by 1.6
ORDERING INFORMATION To order use the following sequence of letters and numbers.
SDSI 15 415 28/45
TYPE
Note1:
181
RATING
COIL OVERLOAD
VOLTAGE CURRENT
For 25 mm entries add/25 to Product Code
For Enclosures in cast aluminum add A to product code and I for Cast Iron Enclosures
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
182
PART 6.0
DISTRIBUTION BOARDS
183
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Type DBD150- 63Amp switched distribution board with 16Amp MCBs
Page 185
Type DBD170- 100Amp switched distribution board with 16Amp MCBs
Page 186
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
184
Distribution Board - Cast Aluminium and Cast Iron Enclosures
Type DBD150 – EEx d 63 amps switched distribution box with 16amp MCBs
EEx d IIB
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
II 2 GD
EEx d IIB T6
-40˚C to + 50˚C
Zones 1,2,21,22 . Groups IIA, IIB
SIRA04ATEX1226X POCC. GB. гБ 05.BO1132
IP66 to EN60529:1992
Maximum 62 watts at +50C
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
Power dissipation
ENCLOSURE SPECIFICATION
Dimensions
Material
Weight empty
Cover fixing
Gasket
Earthing
Mounting
Dimensions
Material
Finish
Weight empty
Cover fixing
Gasket
Earthing
Mounting
ENTRY SPECIFICATION
MCBs
30 x 1 pole
18 x 2 pole
12 x 3 pole
ELECTRICAL SPECIFICATION
Switch Disconnector
MCBs
Incoming and outgoing terminals
Wiring
ATEX/GOST
II 2 GD
EEx d IIB T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB
SIRA04ATEX1227X POCC. GB. гБ 05.BO1132
IP66 to EN60529:1991
Maximum 200 Watts at +50˚C
560mm x 560mm x 245mm
Cast aluminium LM6
Cast iron to 180BSI1452:1997
Aluminium - epoxy powder coated RAL 7032
Iron- Zinc rich epoxy powder primer
and epoxy powder top coat
Aluminium 65Kgs, cast iron 190Kgs
Hinged with M10 allen head stainless steel screws
One piece closed cell 4mm neoprene
Base- internal and external EEx e brass clamps
Cover – internal EEx e brass clamp
2 steel U shaped mounting straps. 10mm diameter fixing holes
Entries Side A
1 x M32 + 6 x M20
1 x M32 + 6 x M20
1 x M32
Entries Side C
12 x M20
6 x M20
6 x M20
Entries Side D
12 x M20
6 x M20
6 x M20
ELECTRICAL SPECIFICATION
1x 63 amp 4 pole incoming switch
disconnector to IEC60947-3
1,2 and 3 pole 16 amp MCBs to IEC898
WDU type as appropriate
Not wired as standard
Optional wiring service available
Switch Disconnector
MCBs
Incoming and outgoing terminals
Wiring
All Dimensions in mm
ORDERING INFORMATION
185
Group II Cat 2
All entries EEx d threaded and fitted with EEx d stopping plugs or glands
as appropriate
Entries Side A
1 x M25 + 9 x M20
1 x M25 + 6 x M20
1 x M25 + 4 x M20
MCBs
9 x 1 pole
6 x 2 pole
4 x 3 pole
Notes:
T6
ENTRY SPECIFICATION
All entries EEx d threaded and fitted with EEx d stopping plugs or glands as
appropriate
Switch Amps
63
63
63
Zones 1,2,21,22
ENCLOSURE SPECIFICATION
335mm x 310mm x 200mm
Cast aluminium LM6
Cast iron to 180BSI1452:1997
Aluminium - epoxy powder coated RAL 7032
Iron - Zinc rich epoxy powder primer
and epoxy powder top coat, black
Cast aluminium 17Kgs, Cast iron 50Kgs
M6 allen head stainless steel screws
One piece closed cell 4mm neoprene
Base- internal and external EEx e brass clamps
Cover – internal EEx e brass clamp
2 steel mounting straps. 10mm diameter fixing holes
Finish
EEx d IIB
HAZARDOUS AREA SPECIFICATION
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
Power dissipation
Distribution Board - Cast Iron Enclosures
Type DBD170 – EEx d 100 amps switched distribution box with 16amp MCBs
1x 100 Amp 4 pole
incoming switch disconnector to IEC60947-3
1,2 and 3 pole 16 amp MCBs to IEC898
WDU type as appropriate
Not wired as standard
Optional wiring service available
All Dimensions in mm
ORDERING INFORMATION
Entries
1 x M25 + 9 x M20
1 x M25 + 6 x M20
1 x M25 + 4 x M20
16amp MCBs
9 x 1 pole
6 x 2 pole
4 x 3 pole
Incoming Terminals
4 x WDU16 + 1 x WPE16
4 x WDU16 + 1 x WPE16
4 x WDU16 + 1 x WPE16
Outgoing Terminals
9 x WDU2.5 + 9 x WPE2.5
12 x WDU2.5 + 6 x WPE2.5
12 x WDU2.5 + 4 x WPE2.5
Product Code
DBD150/91
DBD150/62
DBD150/43
Switch Amps
100
100
100
Entries
1 x M32 + 30 x M20
1 x M32 + 18 x M20
1 x M32 + 12 x M20
16amp MCBs
30 x 1 pole
8 x 2 pole
12 x 3 pole
Incoming Terminals
4 x WDU35 + 1 x WPE35
4 x WDU35 + 1 x WPE35
4 x WDU35 + 1 x WPE35
Outgoing Terminals
36 x WDU2.5 + 36 x WPE2.5
36 x WDU2.5 + 18 x WPE2.5
36 x WDU2.5 + 12 x WPE2.5
Product Code
DBD170/301
DBD170/182
DBD170/123
For cast aluminium add /AL to product code e.g. DBD150/91/AL.
For cast iron add /CI to product code e.g. DBD150/91/CI
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
186
PART 7.0
LIGHTING
7.1 Fluorescent Lighting Fittings
Page 189
Single and twin standard and emergency luminaires approved
to ‘d’, ‘de’, ‘edq’ and ‘nA’ for lamps ranging from 8 Watts to 58 Watts
7.2 High Intensity Discharge Lighting Fittings
Page 199
Wellglass* and floodlight luminaires approved to ‘d*’, ‘de’ and ‘nR’
for all types of high intensity discharge lamps ranging from 70 Watts to 400 Watts
7.3 Walkway and Portable Lighting
Page 205
Bulkhead and hand lamp EEx de luminaires ranging from 13 to 60 Watts
*
187
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
These products will be introduced later in 2006 and are included for advanced notice only
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
188
Fluorescent Lighting
Type Calstar - EEx d Fluorescent Fitting for 18 to 58 Watt Lamps
PART 7.1
FLUORESCENT
LIGHTING FITTINGS
EEx d IIB, IIC
Zones 1,2,21,22
T5, T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
II 2 GD
EEx d IIB and IIC
(T6) -20˚C to + 40˚C
(T5) -20˚C to + 55˚C
(T4) -20˚C to + 70˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
SIRA02ATEX1107 GOST’R’ POCC GB. гБ05. B01132
IP67 to EN60529:1992
ENCLOSURE SPECIFICATION
Type Calstar
– EEx d Single and Twin Fluorescent Fittings
for 18-58W lamps
Type Calstar
– EEx de Single and Twin Emergency Fluorescent
Fittings for 18-58W lamps
Type Calstar
Type E152
Page 194
Page 195
– EEx nA Single and Twin Fluorescent
Fittings for 18-58W Lamps
Type N162
Cover fixing
Gasket
Earthing
Mounting
ENTRY SPECIFICATION
1 x 20mm EEx d threaded hole at A and B. Both are fitted with an EEx d
stopping plug.
– EEx edq Single, Twin and Triple Fluorescent
Recessed Fittings for 18-58W lamps
Type N161
Page 193
– EEx edq Single and Twin Fluorescent Emergency
Fittings for 18-36W lamps
Type E 181
Page 192
Finish
All cast metal parts – light metal alloy
Overtube – borosilicate glass
Reflector – 1.2mm mild steel
Cast metal parts - Epoxy powder coat RAL7032
Reflector – epoxy powder coat – white
M6 allen head stainless steel screws
Nitrile O ring
Internal and external earths
Two stainless steel removable mounting brackets supplied as
standard
– EEx edq Single and Twin Fluorescent Fittings
for 18-58W lamps
Type E148
Page 191
– EEx de single Emergency Exit Fluorescent
Fittings for 8W Lamps
Material
Page 190
Page 196
– EEx nA Single and Twin Fluorescent Emergency
Fittings for 18-36W Lamps
ELECTRICAL SPECIFICATION
Control gear
Page 197
Operating voltage
Operating current
Power factor
Terminals
Lamps
High frequency electronic ballast complying with all European
standards relating to safety, operation and EMC (Immunity)
220 – 254 Volts 50/60Hz
0.5 Amps max
0.98
2.5mm sq. connection block. Suitable for through wiring
Bi-pin Flourescent tube 26mm T8 or 25mm T12
All Dimensions in mm
ORDERING INFORMATION
Wattage
1 x 18 watts
2 x 18 watts
1 x 36 watts
2 x 36 watts
1 x 58 watts
2 x 58 watts
GAS GROUPS IIA AND IIB
Length
Weight
600mm
5.0kg
600mm
5.2kg
7.0kg
1200mm
7.2kg
1200mm
8.0kg
1500mm
8.3kg
1500mm
Product Code
500/0103
500/0121
500/0109
500/0127
500/0115
500/0133
Wattage
1 x 18 watts
2 x 18 watts
1 x 36 watts
2 x 36 watts
1 x 58 watts
2 x 58 watts
GAS GROUPS IIC
Length
Weight
5.0kg
600mm
5.2kg
600mm
7.0kg
1200mm
7.2kg
1200mm
8.0kg
1500mm
8.3kg
1500mm
Product Code
600/0103
600/0121
600/0109
600/0127
600/0115
600/0133
Notes: Add WG to part number if wire guard required
189
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
190
Fluorescent Lighting
Fluorescent Lighting
Type Calstar - EEx de Emergancy Fluorescent Fitting for 18 to 58 Watt Lamps
Type Calstar - EEx de Emergency Fluorescent Exit Fitting for 8 Watt Lamps
EEx de IIB, IIC
Zones 1,2,21,22
T5, T6
Group II Cat 2
ATEX/GOST
Area classification
Certification No.
Ingress protection
II 2 GD
EEx de IIB and IIC
(T6) -20˚C to + 40˚C
(T5) -20˚C to + 55˚C
(T4) -20˚C to + 70˚C
Zones 1,2,21,22 . Groups IIA, IIB, IIC
SIRA02ATEX1107 GOST’R’ POCC GB. гБ05. B01132
IP67 to EN60529:1992
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
ENCLOSURE SPECIFICATION
Material
Finish
Cover fixing
Gasket
Earthing
Battery Housing
Mounting
Zones 1,2,21,22
T5, T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
EEx de IIC
II 2 GD
EEx de IIC
(T6) -20˚C to +40˚C
(T5) -20˚C to + 55˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
SIRA02ATEX1107 GOST’R’ POCC GB. гБ 05. B01132
IP67 to EN60529:1992
ENCLOSURE SPECIFICATION
All cast metal parts – light metal alloy
Overtube – borosilicate glass
Reflector – 1.2mm mild steel
Cast metal parts - Epoxy powder coat RAL7032
Reflector – epoxy powder coat – white
M6 allen head stainless steel screws
Nitrile O ring
Internal and external earths
Aluminium tube with EEx e glands
Two stainless steel removable mounting brackets supplied as
standard
Material
Finish
Cover fixing
Gasket
Earthing
Battery Tube
Mounting
ENTRY SPECIFICATION
Pictograms supplied as standard
All cast metal parts – light metal alloy
Overtube – borosilicate glass
Reflector – 1.2mm mild steel
Cast metal parts - Epoxy powder coat RAL7032
Reflector – epoxy powder coat – white
M6 allen head stainless steel screws
Nitrile O ring
Internal and external earths
Aluminium tube with EEx e glands
Two stainless steel removable mounting brackets supplied as
standard
ENTRY SPECIFICATION
1 x 20mm EEx d threaded hole at A and B
One entry is used for the battery and the other is fitted with an EEx d stopping plug
1 x 20mm EEx d threaded hole at A and B
One entry is used for the battery and the other is fitted with an EEx d stopping plug.
ELECTRICAL SPECIFICATION
ELECTRICAL SPECIFICATION
Control gear
High frequency electronic ballast and
emergency module complying with all
European standards relating to safety,
operation and EMC (Immunity)
220 – 254 Volts 50/60Hz
0.5 Amps max
0.98
Maintained and non-maintained
3 hours in both modes
24 hours from fully discharged state
Protection against deep discharge
and reverse battery polarity
2.5mm sq. connection block suitable for
through wiring
Bi-pin Flourescent tube 26mm T8, 25mm T12
Operating voltage
Operating current
Power factor
Emergency operation
Emergency operating time
Recharge time
Protection
Terminals
Lamp
Control gear
High frequency electronic ballast complying with all
European standards relating to safety, operation and
EMC (Immunity)
Operating voltage
220 – 254 Volts 50/60Hz
Operating current
0.5 Amps max
Power factor
0.98
Emergency operation
Maintained and non–maintained
Emergency operating time 3 hours in both modes
Recharge time
24 hours from fully discharged state
Terminals
2.5mm sq. connection block suitable for through wiring
Lamp
Bi-Pin fluorescent tubes, T5
A set of 3 pictograms as indicated opposite are supplied
Pictograms
as standard
All Dimensions in mm
All Dimensions in mm
ORDERING INFORMATION
Wattage
1 x 18 watts
2 x 18 watts
1 x 36 watts
2 x 36 watts
1 x 58 watts
2 x 58 watts
GAS GROUPS IIA AND IIB
Length
Weight
600mm
6.0kg
600mm
6.2kg
8.0kg
1200mm
8.2kg
1200mm
9.0kg
1500mm
9.3kg
1500mm
Product Code
550/0103
550/0121
550/0109
550/0127
550/0115
550/0133
Wattage
1 x 18 watts
2 x 18 watts
1 x 36 watts
2 x 36 watts
1 x 58 watts
2 x 58 watts
GAS GROUPS IIC
Length
Weight
6.0kg
600mm
6.2kg
600mm
8.0kg
1200mm
8.2kg
1200mm
9.0kg
1500mm
9.3kg
1500mm
Product Code
650/0103
650/0121
650/0109
650/0127
650/0115
650/0133
ORDERING INFORMATION
Wattage
1 x 8 watts
Length
300mm
Weight
4.0kg
Product Code
650/0211
Note: Fitting complete with lamp
Note: Add WG to part number if wire guard required
191
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
192
Fluorescent Lighting
Fluorescent Lighting
Type E152 - EEx edq Fluorescent Fitting for 18 to 58 Watt Lamps
Type E148 - EEx edq Emergency Fluorescent Fitting for 18 to 36 Watt Lamps
EEx edq IIC
Zones 1,2,21,22
T4
Group II Cat 2
ATEX
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
EEx edq IIC
Zones 1,2,21,22
T4
Group II Cat 2
ATEX
HAZARDOUS AREA SPECIFICATION
II 2 G, II 2 D T80C
EEx edq IIC T4
(T4) -20˚C to +60˚C
(T4) -20˚C to +50˚C for 1 x 58 Watt and 2 x 58 Watt
Zones 1,2,21,22 . Groups IIA, IIB, IIC
PTB 97 ATEX2223,2224,2225
IP66 to EN60529:1992
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
II 2 GD
EEx edq IIC T4
(T4) -20˚C to +55˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
PTB05 ATEX2066
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
ENCLOSURE SPECIFICATION
Material
Material
Diffuser fixing
Isolating switch
Gasket
Mounting
Body – Glass reinforced polyester
Diffuser – polycarbonate
Reflector – glass reinforced polyester
Hinged with central locking, key provided as standard
Isolates all poles of power supply when luminaire is opened
EPDM
Brackets as required fixed to body through bushes
moulded into body. See drawing
Diffuser fixing
Gasket
Mounting
ENTRY SPECIFICATION
ENTRY SPECIFICATION
1 x 20mm entry at A, B and C. Supplied with 2 EEx e cable glands
and 1 EEx e stopping plug
1 x 20mm entry at A, B and C. Supplied with 2 EEx e cable glands
and 1 EEx e stopping plug.
ELECTRICAL SPECIFICATION
Control gear
Operating voltage
Frequency
Operating current
Power factor
Terminals
Lamp
Body and Battery housing– Glass reinforced polyester
Battery housing - separate
Diffuser – polycarbonate
Reflector – glass reinforced polyester
Hinged with central locking. Key supplied as standard
EDPM
Brackets as required fixed to body through bushes
moulded into body. See drawing
ELECTRICAL SPECIFICATION
EEx edq approved high frequency electronic ballast
220 – 254 Volts AC, DC
0 or 50/60Hz
0.5 Amps max
0.98
L1 + N +PE up to 6mm sq max
Bi-pin flourescent tubes 26mm T8 and 38mm T12
Control gear
Operating voltage
Operating current
Power factor
Emergency operation
Emergency operating time
Battery
Recharge time
Lamp
Terminals
All Dimensions in mm
EEx edq approved high frequency electronic
ballast and emergency module
220 – 254 Volts 50/60Hz
0.5 Amps
0.98
Maintained and non–maintained
3 hours in both modes
NiCd
24 hours from fully discharged state
Bi-pin Flourescent tube 25mm T8
Li = N =PE 6mm sq max, for through wiring
6x2.5 mm sq. max.
All Dimensions in mm
ORDERING INFORMATION
Wattage
1 x 18 watts
2 x 18 watts
1 x 36 watts
2 x 36 watts
1 x 58 watts
2 x 58 watts
Mounting Accessories
Hook (pair)
Bracket (pair)
Spare Key
193
Length
600mm
600mm
1200mm
1200mm
1500mm
1500mm
Weight
7.5kg
8.0kg
10.2kg
10.7kg
13.5kg
14.0kg
Product Code
E15221
E15222
E15241
E15242
E15261
E15262
ORDERING INFORMATION
Wattage
2 x 18 watts
2 x 18 watts
2 x 36 watts
2 x 36 watts
Mounting Accessories
Hook (pair)
Bracket (pair)
Spare Key
H15
B15
KIS
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Emergency Duration
1 hour
3 hour
1 hour
3 hour
Length
600mm
600mm
1200mm
1200mm
Weight
8.9kg
9.3kg
12.6kg
13.0kg
Product Code
E1482214
E1482237
E1484214
E1484237
H15
B15
KIS
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
194
Flourescent Lighting
Fluorescent Lighting
Type E181 - EEx edq Recessed Fluorescent Fitting for 18 to 58 Watt Lamps
Type N161 - EEx nA Fluorescent Fitting for 18 to 58 Watt Lamps
EEx edq IIC
Zones 1,2,21,22
T4, T5
Group II Cat 2
ATEX
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
EEx nA IIC
Zones 2,22
T4
Group II Cat 3
ATEX
HAZARDOUS AREA SPECIFICATION
II 2 G, II 2 D T5 (75C)
EEx edq IIC T4
(T4) -20˚C to + 50˚C for 1 or 2 lamp options
(T4) -20˚C to + 40˚C for 3 lamp options
Zones 1,2,21,22 . Groups IIA, IIB, IIC
IBExU 02 ATEX1018
IP65 to EN60529:1992
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
II 3 G, II 3 D T80C – 100C
EEx nA IIC T4
-20˚C to +40˚C
Zones 2,22. Groups IIA, IIB, IIC
TUV 00ATEX1541
IP65 to EN60529:1992
ENCLOSURE SPECIFICATION
ENCLOSURE SPECIFICATION
Material
Diffuser fixing
Gasket
Isolating Switch
Mounting
Material
Body – Powder coated mild steel
Diffuser – Toughened glass with hinge
Reflector – Powder coated mild steel
Hinged with central locking
EDMP
Isolating power supply when luminaire is opened, with indicator
Brackets as required fixed to body through bushes fitted into
body. See drawing
Diffuser fixing
Gasket
Earthing
Mounting
Body – Glass reinforced polyester
Diffuser – polycarbonate
Reflector – glass reinforced polyester
Plastic clips. SS clips on request
EPDM
Internal
There are closed knock-outs in the housing for
direct ceiling mounting
Sealing gaskets are supplied as standard
For mounting accessories see below
ENTRY SPECIFICATION
ENTRY SPECIFICATION
1 x 20mm entry at A, B and C. Supplied with 2 EEx e cable glands
and 1 EEx e stopping plug.
1 x 20mm entry at A, B and C. Supplied with 2 EEx e cable glands
and 1 EEx e stopping plug
ELECTRICAL SPECIFICATION
Control gear
Operating voltage
Frequency
Operating current
Power factor
Terminals
ELECTRICAL SPECIFICATION
Control gear
Operating voltage
Frequency
Operating current
Power factor
Terminals
Lamp
EEx edq approved high frequency electronic ballast
220 – 254 volts AC/DC
50/60Hz or 0
0.5 Amps max
0.98
Li + N +PE 6mm sq max
Bi-Pin fluorescent tubes, 26mm T8 and 38mm T12
Lamp
High frequency electronic ballast
220 – 254 Volts AC, DC
0 or 50/60Hz
0.5 Amps max
0.98
2x2.5mm sq terminals.as standard
For through wiring up to 5x2.5mm sq terminals
Bi-Pin fluorescent tubes, 26mm T8
All Dimensions in mm
All Dimensions in mm
ORDERING INFORMATION
ORDERING INFORMATION
Lamp(s)
1 x 18 watts
2 x 18 watts
3 x 18 watts
Mounting Accessories
Hook (pair)
Bracket (pair)
Frame
195
Weight
11kg
11kg
13kg
Product Code
E18121
E18122
E18123
Lamp(s)
1 x 36 watts
2 x 36 watts
3 x 36 watts
Weight
19kg
19kg
21kg
Product Code
E18141
E18142
E18143
Lamp(s)
1 x 58 watts
2 x 58 watts
3 x 58 watts
Weight
22kg
22kg
24kg
Product Code
E18161
E18162
E18163
Wattage
1 x 18 watts
2 x 18 watts
1 x 36 watts
2 x 36 watts
1 x 58 watts
2 x 58 watts
Mounting Accessories
Hook (pair)
Bracket (pair)
E15
E15B
E15F
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Length
600mm
600mm
1200mm
1200mm
1500mm
1500mm
Weight
2.2kg
2.9kg
4.3kg
2.9kg
5.1kg
6.3kg
Temp. Class
T4
T4
T4
T4
T4
T4
Product Code
N16121
N16122
N16141
N16142
N16161
N16162
N15
N15B
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
196
Fluorescent Lighting
Type N162 - EEx nA Emergency Fluorescent Fitting for 18 to 36 Watt Lamps
EEx nA
Zones 2,22
T4
Group II Cat 3
ATEX
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
II 3 G
EEx nA T4
0˚C to + 40˚C
Zones 2,22. Groups IIA, IIB, IIC
TUV 00ATEX1541
IP65 to EN60529:1992
ENCLOSURE SPECIFICATION
Material
Diffuser fixing
Gasket
Earthing
Mounting
Body – Glass reinforced polyester
Diffuser – polycarbonate
Reflector – glass reinforced polyester
Plastic clips. SS clips on request
EPDM
Internal
There are closed knock-outs in the housing for
direct ceiling mounting
Sealing gaskets are supplied as standard
For mounting accessories see below
ENTRY SPECIFICATION
1 x 20mm entry at A, B and C. Supplied with 2 EEx e cable glands
and 1 EEx e stopping plug
ELECTRICAL SPECIFICATION
Control gear
Operating voltage
Frequency
Operating current
Power factor
Terminals
Lamp
Emergency Gear
Battery
Protection
Visual monitoring
Recharging time
High frequency electronic ballast
220 – 254 Volts AC, DC
0 or 50/60Hz
0.5 Amps max
0.98
2x2.5mm sq terminals.as standard
For through wiring up to 5x2.5mm sq terminals
Bi-Pin fluorescent tubes, 26mm T8
3 hour operation
Maintained or non-maintained operation
Single lamp version – maintained operation as standard
Twin lamp version – maintained operation, two lamps in
mains operation, one in emergency operation
NiCd type
Deep discharge protection
Battery status shown by LED
24 hours
All Dimensions in mm
ORDERING INFORMATION
Wattage
1 x 18 watts
2 x 18 watts
1 x 36 watts
2 x 36 watts
Mounting Accessories
Hook (pair)
Bracket (pair)
197
Length
600mm
600mm
1200mm
1200mm
Weight
4.2kg
4.7kg
6.9kg
7.4kg
Temp. Class
T4
T4
T4
T4
Product Code
N16221
N16222
N16241
N16242
N15
N15B
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
198
Wellglass Lighting
Type ORBeX - EEx de Wellglass for HID Lamps to 250 Watts
PART 7.2
HIGH INTENSITY
DISCHARGE FITTINGS
EEx de IIC
Zones 1,2,21,22
T4, T5
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
II 2 G
EEx de IIC
(T5) -20˚C to +40˚C
(T4) -20˚C to +50˚C
Zones 1,2,21,22 . Groups IIA, IIB, IIC
TBA
IP66/67 to EN60529:1992
ENCLOSURE SPECIFICATION
Type ORBeX
– EEx de Well Glass
for HID Lamps to 250 Watts
Page 200
Dimensions
Material
Type HORIZON - EEx de Floodlight
for HID Lamps to 400 Watts
Type FLN150
– Ex nR Floodlight
for HID Lamps to 150 Watts
Type FLN250
Page 202
– Ex nR Floodlight
for HID Lamps to 250 Watts
Type FLN400
Page 201
Page 203
– Ex nR Floodlight
for HID Lamps to 400 Watts
Finish
Weight
Glass dome fixing
Gasket
Earthing
Mounting
Wiring
Fastenings
320 diam. x 425mm
All cast metal parts – light metal alloy
Glass dome – borosilicate glass
Reflector – high purity aluminium
Cast metal parts - Epoxy powder coat RAL7032
16.3 Kg
Machined thread on housing and dome collar
Nitrile O ring
Internal and external earths
Two x M10 eye bolts, ceiling bracket or swivel bracket
Direct into EEx e wiring box
Stainless steel
ENTRY SPECIFICATION
Page 203
1 x 20mm EEx e threaded entry at A and B.
Entry is fitted with an EEx e stopping plug.
ELECTRICAL SPECIFICATION
Control gear
Operating voltage
Operating current
Power factor
Terminals
Lampholder
Lamps
Magnetic choke with associated electronic igniter
220 – 254 Volts 50/60Hz
1.2 Amps
0.98 with pf correction capacitor
L1 + N + PE. 6.0mm max
E27 or E40
High pressure Sodium, Metal Halide and Mercury Vapour lamps
All Dimensions in mm
ORDERING INFORMATION
Temp. Class
T5
T4
T5
T5
T4
T5
T5
T4
Lamp
125 watt mercury
250 watt mercury
100 watt metal halide
150 watt metal halide
250 watt metal halide
100 watt sodium
150 watt sodium
250 watt sodium
MOUNTING DEVICES
1 pair x 10mm eye bolts in galvanised steel
Ceiling Bracket
Swivel Bracket in galvanised steel
199
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
ORB/EB
ORB/CB
ORB/SB
Accessories
External reflector
Protective guard
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Product Code
ORB/125HM
ORB/250HM
ORB/100HI
ORB/150HI
ORB/250HI
ORB/100HS
ORB/150HS
ORB/250HS
ORB/ER
ORB/WG
200
Floodlighting
Floodlighting
Type HORIZON - EEx de Floodlight for HID Lamps to 400 Watts
Type FLN150 - Ex nR Floodlight for HID Lamps to 150 Watts
EEx ed IIC
Zones 1,2,21,22
T3, T4
Group II Cat 1,2,3
ATEX/GOST
Zones 2,22
T5
Group II Cat 3
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
Ex nR II
II 2 GD
EEx de IIC
To be advised
Zones 1,2,21,22. Groups IIA, IIB, IIC
TBA
IP67 to EN60529:1991
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
II 3 GD
Ex nR II
T5 -40˚C to +48˚C. lamp upright
T5 -40˚C to +41˚C. lamp up
T5 -40˚C to +43˚C. lamp down
Zones 2,22.
SIRA 05ATEX4057
IP65 to EN60529:1992
ENCLOSURE SPECIFICATION
ENCLOSURE SPECIFICATION
Material
All cast metal parts – light metal alloy
Glass – borosilicate glass
Reflector – pure aluminium
Cast metal parts - Epoxy powder coat RAL7032
25.0Kg
Permanently fixed into frame
M6 allen head stainless steel screws
Lockable screw for lamping
Internal and external earths
Stainless steel swivel bracket
Stainless steel
Finish
Weight
Glass
Frame fixing
Lamping
Earthing
Mounting
Fastenings
Dimensions
Material
Finish
Cover fixing
Weight
Gasket
Earthing
Mounting
ENTRY SPECIFICATION
1 x 20mm EEx e threaded entry at A and B
Each entry is fitted with an EEx d stopping plug
150 Watts – 440mm x 380mm x 190mm
Body and cover. Aluminium 3.0 mm
or CR4 mild steel1.5mm
Glass – Toughened glass
Reflector – Smooth polished or hammer aluminium
Epoxy powder coated - black
Fully detachable hinged cover
with captive M6 stainless steel
Hexagon head slotted screws
15 kgs
One piece silicon rubber
Internal and external earths
5mm stainless steel stirrup bracket
ENTRY SPECIFICATION
2 x 20mm entries at A as standard
ELECTRICAL SPECIFICATION
Control gear
Operating voltage
Operating current
Power factor
Terminals
Lampholder
Lamps
Magnetic choke with associated electronic igniter
220 – 254 Volts 50/60Hz
1.8 Amps max
0.98 with pf correction capacitor
L1 + N + PE. 6.0mm max
E40
High pressure Sodium, Metal Halide and
Mercury Vapour lamps
ELECTRICAL SPECIFICATION
All Dimensions in mm
Control gear
Operating voltage
Operating current
Power factor
Terminals
Lampholder
Lamps
Magnetic choke with associated electronic igniter
220 – 254 Volts 50/60Hz
0.6 Amps
0.98 with pf correction capacitor
MK6/6
E40
Tubular High Pressure Sodium and Metal Halide lamps
All Dimensions in mm
ORDERING INFORMATION
Lamp
125 watt mercury
250 watt mercury
400 watt mercury
150 watt metal halide
250 watt metal halide
400 watt metal halide
150 watt sodium
250 watt sodium
400 watt sodium
201
ORDERING INFORMATION
Temp. Class
T4
T3
T3
T4
T3
T3
T4
T3
T3
Product Code
HZ125/HM
HZ250/HM
HZ400/HM
HZ150/HI
HZ250/HI
HZ400/HI
HZ150/HS
HZ250/HS
HZ400/HS
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Lamp
150 watts metal halide
150 watts high pressure sodium
Product Code
FLN150HI
FLN150HS
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
202
Floodlighting
Type FLN250/400 - Ex nR Floodlight for 250 and 400 Watt HID Lamps
Ex nR II
Zones 2,22
T3
Group II Cat 3
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
II 3 GD
Ex nR II
250 Watts T3 -40˚C to + 50˚C lamp upright
T3 - 40˚C to + 48˚C lamp down
T3 - 40˚C to + 53˚C lamp up
400 Watts T3 -40˚C to + 45˚C lamp upright
T3 - 40˚C to + 48˚C lamp down
T3 - 40˚C to + 47˚C lamp up
Zones 2, 22
SIRA 05ATEX4057
IP65 to EN60529:1992
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Cover fixing
Weight
Gasket
Earthing
Mounting
575mm x 505mm x 190mm
Body and cover. Aluminium 3.0mm or CR4 mild steel 1.5mm
Glass – Toughened glass
Reflector – Smooth polished or hammer aluminium
Epoxy powder coated - black
Fully detachable hinged cover with captive M6 stainless steel
Hexagon head slotted screws
25Kg
One piece silicon rubber
Internal and external earths
5mm stainless steel stirrup bracket
ENTRY SPECIFICATION
2 x 20mm entries at A as standard
ELECTRICAL SPECIFICATION
Control gear
Operating voltage
Operating current
Power factor
Terminals
Lampholder
Lamps
Magnetic choke with associated electronic igniter
220 – 254 Volts 50/60Hz
1.5 Amps
0.98 with pf correction capacitor
MK6/6
E40
Tubular High Pressure Sodium, Metal Halide lamps
All Dimensions in mm
ORDERING INFORMATION
Lamp
250 watts metal halide
400 watts metal halide
250 watts high pressure sodium
400 watts high pressure sodium
203
Product Code
FLN250HI
FLN400HI
FLN250HS
FLN400HS
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
204
Bulkhead Lighting
Type 300 - EEx de Bulkhead Fitting for 13 Watt Compact Fluorescent
and 60 watt GLS
PART 7.3
WALKWAY AND
PORTABLE LIGHTING
EEx de IIC
Type E8310
– EEx de Bulk Head Luminaires for 13w Compact
Fluorescent and 60w GLS Lamps
Page 206
– EEx de Handlamp for 60w
Page 207
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
Type 300
Zones 1,2,21,22
II 2 GD
EEx de IIC
Compact fluorescent vertically mounted (T5) - 20˚C to +54˚C
Compact fluorescent horizontally mounted (T6) -20˚C to + 49˚C
GLS lamp vertically mounted (T4) -20˚C to + 41˚C
GLS lamp horizontally mounted (T3) -20˚C to + 66˚C
Zones 1,2,21,22 . Groups IIA, IIB, IIC
SIRA02ATEX1107 GOST’R’ POCC GB. гБ05. B01132
IP67 to EN60529:1992
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Weight
Cover fixing
Gasket
Earthing
Mounting
303mm x 160mm
All cast metal parts – light metal alloy
Overtube – borosilicate glass
Reflector – 1.2mm mild steel
Cast metal parts - Epoxy powder coat RAL7032
Reflector – epoxy powder coat – white
2.5 Kg
M6 allen head stainless steel screws
Nitrile O ring
Internal earths
Two stainless steel mounting brackets supplied as standard
ENTRY SPECIFICATION
1 x 20mm EEx e threaded entry at A and B.
Each entry is fitted with an EEx e stopping plug.
ELECTRICAL SPECIFICATION
Control gear
Operating voltage
Operating current
Power factor
Terminals
Lamp
High frequency electronic ballast
220 – 254 Volts 50/60Hz
Compact fluorescent 0.08 Amps, GLS 0.25 Amps
0.98
2.5mm sq. connection block
13 Watt compact fluorescent or 60 Watt GLS
All Dimensions in mm
ORDERING INFORMATION
Lamp(s)
1 x 13 watts compact fluorescent
1 x 60 watts GLS
205
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Product Code
300/CLF
300/GLS
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
206
Handlamp
Type E8310 - EEx ed Handlamp for 60 Watt
EEx ed II
Zones 1,2,21,22
T3, T4
Group II Cat 2
ATEX
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
II 2 GD
EEx ed II
60 Watts. T4 -20˚C to + 40˚C
Zones 1,2,21,22
PTB01ATEX2144
IP65 to EN60529:1992
SPECIFICATION
Dimensions
Material
Weight
Wire gaurd
416mm x 141mm
Rubber handle with glass globe
2.3Kg
Standard
ELECTRICAL SPECIFICATION
Voltage
220V - 230V AC/DC
120V AC/DC
24V - 42V AC/DC (T2)
416
ø141
All Dimensions in mm
ORDERING INFORMATION
Lamp
60 watts OSRAM
207
Product Code
E8310
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
208
PART 8.0
PLUGS AND SOCKETS
209
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Type DXN
– EEx de Switched Plugs and Sockets to 63 Amps
Page 211
Type BX
– EEx d Metal clad Plugs and Sockets to 32 Amps
Page 212
Type SPXL – EEx de Multi Socket Outlets in Stainless steel
Page 213
Type SPGL – EEx de Multi Socket Outlets in Glass Reinforced Polyester
Page 214
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
210
Plugs and Sockets
Plugs and Sockets
Type DXN - EEx de Switched Plugs and Sockets to 63 Amps
Type BX - EEx d Metal Clad Plugs and Switched Sockets to 230 Amps
EEx de IIC
Zones 1,2,21,22
T6
Group II Cat 2
ATEX
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification Nos
Ingress protection
EEx d IIB
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
II 2 GD
EEx de II T6
T6 -40˚C to +40˚C for maximum current rating of 60 Amps
T5 -40˚C to +40˚C for 63 Amps
Zones 1,2,21,22. Groups IIA, IIB, IIC
20 Amps LCIE 00ATEX6010X
32 Amps LCIE 99ATEX6027X
63 Amps LCIE 02ATEX 6029X
IP66,67 to EN60529:1992
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Apparatus standard
Certification No.
Ingress protection
II 2 GD
EEx d IIB T6
-20˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB
EN 50014:1998 and EN 50018: 1995
SIRA02ATEX1332 GOST’R’ POCC GB. гБ05. B01132
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
ENCLOSURE SPECIFICATION
Casing Material
Casing Finish
Contacts
Security
Mounting
Dimensions
Material
Finish
Glass reinforced polyester
Moulded black
Silver nickel butt type contacts with added metallic braid
Plug is detached only after the circuit is broken within the
de enclosure
Mounting boxes are provided to facilitate wall mounting
of the socket
Weight
Cover fixing
Earthing
Security
ENTRY SPECIFICATION
Mounting
Entry is via integral 20mm EEx e glands as standard, 25mm (25A), 32mm (32A),
40mm (63A)
220mm x 185mm x 161mm
Cast iron to 180BSI1452:1997 and brass
Cast iron components - Zinc rich epoxy powder primer
and epoxy powder top coat
Brass components – machined self colour
10.5 Kg
M6 allen head stainless steel screws
Internal and external EEx e brass clamps on base
Earth on cover
Mechanical locking of plug in socket
Plug cannot be removed when switch is in the ON position
Two steel mounting straps with 8mm fixing holes
ENTRY SPECIFICATION
1 x 20mm EEx d threaded hole at A,B and C
Each entry is fitted with an EEx d stopping plug.
25mm entries are available as an option
ELECTRICAL SPECIFICATION
Voltage
Volts
380-440
380-440
Current
AC21A (A)
20
32
Power
AC23A(Kw)
5.5
11
AC-3(Kw)
3.7
7.5
Conductor Size
mmsq. Max.
2.5
6.0
All Dimensions in mm
ORDERING INFORMATION
Current Rating
20 Amps
20 Amps
20 Amps
20 Amps
32 Amps
32 Amps
32 Amps
32 Amps
63 Amps
63 Amps
63 Amps
63 Amps
211
Pin Configuration
2p
spne
3pe
3pne
2p
spne
3pe
3pne
2p
spne
3pe
3pne
voltage
24v
240v
400v
400v
24v
240v
400v
400v
24v
240v
400v
400v
Plug with handle, socket with wall box
DXN1A
DXN1B
DXN1C
DXN1D
DXN3A
DXN3B
DXN3C
DXN3D
DXN6A
DXN6B
DXN6C
DXN6D
Plug with handle, socket with handle
DXN1E
DXN1F
DXN1G
DXN1H
DXN3E
DXN3F
DXN3G
DXN3H
DXN6E
DXN6F
DXN6G
DXN6H
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
ORDERING INFORMATION
Current rating
20 Amps
32 Amps
Switch Position
on-off
on-off
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Product Code
BX203
BX323
212
Plugs and Sockets
Plugs and Sockets
Type SPXL - EEx de Multi Socket Outlet in Stainless Steel Enclosure
Type SPGL - EEx de Multi Socket Outlet in Glass Reinforced Polyester Enclosure
EEx de IIC
Zones 1,2,21,22
T5, T6
Group II Cat 2
ATEX
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of Protection
Temperature class
Certification No.
Ingresss Protection
Finish
Cover Fixing
Gasket
Earthing
Security
Entries
Mounting
Zones 1,2,21,22
T6
Group II Cat 2
ATEX
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
II 2 GD
EEx de IIC
T6 -40˚C to + 40˚C for operating current of 60 Amps
SIRA99ATEX3199X
IP66,67 To EN60529:1992
II 2 GD
EEx de II
T6 -40˚C to + 40˚C for operating current of 60 Amps
Zones 1,2,21,22 . Groups IIA, IIB, IIC
SIRA99ATEX3200X
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material
EEx de IIC
Dimensions
As specified
Base and Cover 1.5mm 316L (1.4404) Stainless steel
Gland Plates 2.5mm 316L (1.4004) stainless steel
Electropolished
Fully detachable hinged cover with captive M6 stainless
steel hexagon slotted screws
One piece fire resistant closed cell neoprene
10mm brass internal/external earth stud as standard
Optional earth stud welded to cover and gland plates
Padlockable Hasp
Via gland plates or direct through body
External lugs with 10mm clearance holes
255mm x 250mm x 120mm
400mm x 405mm x 120mm
Carbon loaded anti-static Glass reinforced polyester UL94/V0
Moulded black
M6 allen head captive stainless steel screws. Optional hinges
Silicon rubber
Optional 6mm external/internal Internal earth stud
Optional internal earth continuity plate in galvanised
steel, brass or stainless steel
Through 6.5 mm clearance holes moulded into base
Material
Finish
Cover fixing
Gasket
Earthing
Mounting
ELECTRICAL SPECIFICATION
One or two DXN Type sockets on each of 3 sides of the enclosure.
Socket Type
ELECTRICAL SPECIFICATION
One or two DXN Type sockets on each of 3 sides of the enclosure
Socket Type
DXN1
DXN3
DXN6
Operating Voltage
Volts
500
750
750
DXN1
DXN3
DXN6
Operating Current
Amps
20
32
60
Operating Voltage
Volts
500
750
750
Operating Current
Amps
20
32
60
Dimensions to specification
ORDERING INFORMATION
ORDERING INFORMATION
Ordering is subject to customer specification. The size of the enclosure will depend
on the number of sockets specified. Please consult Walsall sales for a design and
quotation that will form the basis for the order.
213
Dimensions to specification
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Ordering is subject to customer specification. The size of the enclosure will depend
on the number of sockets specified. Please consult Walsall sales for a design and
quotation that will form the basis for the order.
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
214
PART 9.0
EMERGENCY SHUTDOWN
AND SIGNALLING EQUIPMENT
A comprehensive range of high specification fire alarms, Xenon beacons, Sounders and Loud
speakers, status/indicator lamps, the majority of which use glass reinforced polyester enclosures.
Type E0302
– EEx de Manual Call Point with Break Glass in a glass reinforced
polyester enclosure
Page 217
Type E0303
– EEx de Manual Call Point with Switch in a glass reinforced
polyester enclosure
Type E0304
– EEx de Manual Call Point with Pushbutton in a glass reinforced
polyester enclosure
Page 219
Type E0301
– EEx de Manual Call Point with Break Glass in a
cast iron enclosure
Page 220
Type BU
– EEx de Xenon beacon*
Page 221
Type SU
– EEx de Sounder*
Page 222
Type BSU
– EEx de Combined beacon and sounder*
Page 223
Type LU
– EEx de Loud speaker*
Page 224
Type E501
– EEx d Single Status/Indicator Lamp in a cast iron enclosure Page 225
Type E502
– EEx d Double Status/Indicator Lamp in a cast iron enclosure Page 226
*
215
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Page 218
These products will be introduced later in 2006 and are included for advanced notice only
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
216
Emergency Shutdown and Signalling Equipment
Type E0302 - EEx de IIC Manual Call point with Break Glass in GRP
EEx de IIC
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Apparatus standard
Certification No
Ingress protection
EEx de IIC
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
II 2 GD
EEx de IIC T6
-40˚C to + 50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
EN 50014:1998 and EN 50019: 1995
SIRA03ATEX3293
IP66 to EN60529:1992
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Apparatus standard
Certification No
Ingress protection
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Weight
Cover fixing
Gasket
Other plastic components
Operator flamepath
Glass
Earthing
Mounting
Emergency Shutdown and Signalling Equipment
Type E0303 - EEx de IIC Manual Call point with Switch in GRP
II 2 GD
EEx de IIC T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
EN 50014:1998 and EN 50019: 1995
SIRA03ATEX3293
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
125mm x 110mm x 105mm
Glass reinforced polyester
Moulded red
1.2Kg
M6 allen head stainless steel screws
1.2mm one piece solid nitrile rubber
Polycarbonate
Brass shaft in a brass housing
2.5mm Standard
Internal EEx e brass clamps on base
Through 10mm holes moulded into base
Dimensions
Material
Finish
Weight
Cover fixing
Gasket
Other plastic components
Operator flamepath
Glass
Earthing
Mounting
ENTRY SPECIFICATION
125mm x 110mm x 105mm
Glass reinforced polyester
Moulded red
1.2 Kg
M6 allen head stainless steel screws
1.2mm one piece solid nitrile rubber
Polycarbonate
Brass shaft in a brass housing
2.5mm Standard
Internal EEx e brass clamps on base
Through 10mm holes moulded into base
ENTRY SPECIFICATION
1 x 20mm EEx e threaded hole base at A as standard.
All entries are fitted with EEx e stopping plugs as standard
25mm entries are available as an option
1 x 20mm EEx e threaded hole base at A as standard.
All entries are fitted with EEx e stopping plugs as standard
25mm entries are available as an option
ELECTRICAL SPECIFICATION
ELECTRICAL SPECIFICATION
Walsall Contact Block Certification number SIRA03ATEX1269U
Voltage
Volts
230 - 270
Current
Amps
16
Walsall Contact Block Certification number SIRA03ATEX1269U
Conductor Size
mmsq. Max
2.5
Voltage
Volts
230 - 270
When used with monitored fire alarm systems as defined in BS 5839 ‘series’ and /or
‘end of line’ resistors can be incorporated.
Maximum allowable resistor power dissipation is 0.5 Watts at 24 Volts.
To comply with certification requirements the resistor(s) must be fitted at the time of
manufacture.
Current
Amps
16
Conductor Size
mmsq. Max
2.5
When used with monitored fire alarm systems as defined in BS 5839 ‘series’ and /or
‘end of line’ resistors can be incorporated.
Maximum allowable resistor power dissipation is 0.5 watts at 24 volts.
To comply with certification requirements the resistor(s) must be fitted at the time of
manufacture.
All Dimensions in mm
All Dimensions in mm
ORDERING INFORMATION
ORDERING INFORMATION
Description
Fire Alarm without Resistors
Fire Alarm with Series Resistors
Fire Alarm with end of the line Resistors
Fire Alarm with series & end of the line Resistors
217
Switch Position
Resistor (s)
1N/O & 1N/C
To be specified
1N/O & 1N/C
To be specified
1N/O & 1N/C
To be specified
1N/O & 1N/C
For 25 mm entries add/25 to Product Code e.g. E030212/25
Product Code
E030210
E030211
E030212
E030213
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Description
Fire Alarm without Resistors
Fire Alarm with Series Resistors
Fire Alarm with end of the line Resistors
Fire Alarm with series & end of the line Resistors
Switch Position
Resistor (s)
1N/O & 1N/C
To be specified
1N/O & 1N/C
To be specified
1N/O & 1N/C
To be specified
1N/O & 1N/C
For 25 mm entries add/25 to Product Code e.g. E030312/25
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Product Code
E030310
E030311
E030312
E030313
218
Emergency Shutdown and Signalling Equipment
Type E0304 - EEx de IIC Manual Call point with Pushbutton in GRP
EEx de IIC
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
II 2 GD
EEx de IIC T6
-40˚C to + 50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
EN 50014:1998 and EN 50019: 1995
SIRA03ATEX3293
IP66 to EN60529:1992
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Apparatus standard
Certification No.
Ingress protection
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Weight
Cover fixing
Gasket
Other plastic components
Operator flamepath
Glass
Earthing
Mounting
EEx d IIC
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Apparatus standard
Certification No
Ingress protection
Emergency Shutdown and Signalling Equipment
Type E0301- EEx d IIC Manual Call point with Break Glass in Cast Iron
II 2 GD
EEx d IIC T6
-40˚C to +50˚C
Zones 1,2,21,22. Groups IIA, IIB, IIC
EN 50014:1998 and EN 50018: 1995
SIRA02ATEX1307
IP66 to EN60529:1992
ENCLOSURE SPECIFICATION
Dimensions
Material
Finish
Colour
Weight
Cover fixing
Gasket
Plastic components
Operator flamepath
Earthing
125mm x 110mm x 105mm
Glass reinforced polyester
Moulded red
1.2Kg
M6 allen head stainless steel screws
1.2mm one piece solid nitrile rubber
Polycarbonate
Brass shaft in a brass housing
2.5mm Standard
Internal EEx e brass clamps on base
Through 10mm holes moulded into base
Mounting
117mm x 117mm x 143mm
Cast iron to 180BSI1452:1997
Zinc rich epoxy powder primer and epoxy powder top coat
Red
5.1 Kg
M6 allen head stainless steel screws
Nitrile O ring
Polycarbonate
Brass shaft in brass housing. nitrile O ring seal
Internal and external EEx e brass clamps on base
Earth on cover
Through 10mm holes cast into base
ENTRY SPECIFICATION
ENTRY SPECIFICATION
1 x 20mm EEx e threaded hole base at A as standard
All entries are fitted with EEx e stopping plugs as standard
25mm entries are available as an option
1 x 20mm EEx d threaded hole at A and B as standard.
All entries are fitted with EEx d stopping plugs as standard
25mm entries are available as an option
ELECTRICAL SPECIFICATION
ELECTRICAL SPECIFICATION
Walsall Contact Block Certification number SIRA03ATEX1269U
Contactors to IEC 60 947 , BS EN 60 947.
Voltage
Volts
230 - 270
Current
Amps
16
Conductor Size
mmsq. Max
2.5
Voltage
Volts
230-270
414
All Dimensions in mm
When used with monitored fire alarm systems as defined in BS 5839 ‘series’ and /or
‘end of line’ resistors can be incorporated.
Maximum allowable resistor power dissipation is 0.5 Watts at 24 Volts.
To comply with certification requirements the resistor(s) must be fitted at the time of
manufacture.
Conductor Size
mmsq. Max
2.5
2.5
All Dimensions in mm
When used with monitored fire alarm systems SERIES and or END OF LINE resistors
can be fitted.
ORDERING INFORMATION
ORDERING INFORMATION
Description
Switch Position
Fire Alarm without Resistors
1N/O & 1N/C
Fire Alarm with Series Resistors
1N/O & 1N/C
Fire Alarm with end of the line Resistors
1N/O & 1N/C
Fire Alarm with series & end of the line Resistors
1N/O & 1N/C
Note: For 25 mm entries add/25 to Product Code e.g. E030412/25
219
Current
AC15 (A)
3
2
Resistor (s)
To be specified
To be specified
To be specified
Product Code
E030410
E030411
E030412
E030413
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Description
Switch Position
Fire Alarm without Resistors
1N/O & 1N/C
Fire Alarm with Series Resistors
1N/O & 1N/C
Fire Alarm with end of the line Resistors
1N/O & 1N/C
Fire Alarm with series & end of the line Resistors
1N/O & 1N/C
Note: For 25 mm entries add/25 to Product Code e.g. E030110/25
Resistor (s)
To be specified
To be specified
To be specified
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Product Code
E030110
E030111
E030112
E030113
220
Emergency Shutdown and Signalling Equipment
Type VANTAGE - EEx de Xenon Beacon
EEx de IIC
Zones 1,2,21,22
T6
Emergency Shutdown and Signalling Equipment
Type VANTAGE - EEx de Sounder
Group II Cat 2
ATEX/GOST
Voltage
Temperature class
Material
Mounting
Initiation
Type of Protection
System details
Lens colour
Wire Gaurd
Zones 1,2,21,22
5J, 10J, 15J, 20J and 30J (Xenon) customer selectable
at installation stage
12V DC, 24V DC, 110V AC, and 240V AC
Board voltage selectable at installation stage
-55˚C to + 70˚C
Glass reinforced polyester
Back strap or stirrup mounting
Telephone or relay
EEx d(e) IIC T6 2GD IP67, IP68
Self mounting PCB with H.A.R.T compatibility
Unit monitors flash timings, flash duration, flash intensity
and initiation circuit
Red, yellow, blue, amber, green, clear
Optional
Rating
Tones
Voltage
Group II Cat 2
ATEX/GOST
Temperature class
Material
Mounting
Type of Protection
System details
120dba @ 1 metre
Up to 42 tones, customer selectable
12V DC, 24V DC, 110V AC, and 240V AC
Board voltage selectable at installation stage.
-55˚C to +70˚C
Glass reinforced polyester
Back strap or stirrup mounting
EEx d(e) IIC T6 2GD IP67, 68
Self mounting PCB with H.A.R.T compatibility.
Unit monitors tone frequency, tone duration, tone intensity
and initiation circuit.
Customer selects voltage at installation point, and can alter
this rating at any time in the future.
The unit has a volume control function which can
reduce the dB(A) output accordingly.
All Dimensions in mm
ORDERING INFORMATION
All Dimensions in mm
ORDERING INFORMATION
Description
5 joule Xenon beacon
10 joule Xenon beacon
15 joule Xenon beacon
20 joule Xenon beacon
25 joule Xenon beacon
30 joule Xenon beacon
221
T6
OUTLINE SPECIFICATION
OUTLINE SPECIFICATION
Rating
EEx de IIC
Product Code
VB5
VB10
VB15
VB20
VB25
VB30
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Description
105 dB sounder
110 dB sounder
115 dB sounder
120 dB sounder
Product Code
VS105
VS110
VS115
VS120
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
222
Emergency Shutdown and Signalling Equipment
Type VANTAGE - EEx de Combined Sounder and Beacon
EEx de IIC
Zones 1,2,21,22
T6
Group II Cat 2
Emergency Shutdown and Signalling Equipment
Type VANTAGE - EEx de Loud Speaker Unit
ATEX/GOST
Voltage
Temperature class
Material
Mounting
Initiation
Type of Protection
System details
Lens colour
Wire Gaurd
Zones 1,2,21,22
T6
Group II Cat 2
ATEX/GOST
OUTLINE SPECIFICATION
BEACON OUTLINE SPECIFICATION
Rating
EEx de IIC
5J, 10J, 15J, 20J and 30J (Xenon) customer selectable
at installation stage
12V DC, 24V DC, 110V AC, and 240V AC
Board voltage selectable at installation stage.
-55˚C to +70˚C
Glass reinforced polyester
Back strap or stirrup mounting
Telephone or relay
EEx d(e) IIC T6 2GD IP67, IP68
Self mounting PCB with H.A.R.T compatibility
Unit monitors flash timings, flash duration, flash intensity
and initiation circuit
Customer selects both voltage and joule rating at installation
point, and can alter these ratings at any time in the future.
Red, yellow, blue, amber, green, clear
Optional
Rating
Frequency
Voltage
Temperature class
Material
Mounting
Type of Protection
System details
120dB(A @ 25W @ 1 metre.
Other tapings via integral transformer @8, 15, 20 Watts
400Hz to 8kHz.
12V DC, 24V DC, 110V AC, and 240V AC
Board voltage selectable at installation stage
-55˚C to +70˚C
Glass reinforced polyester
Back strap or stirrup mounting
EEx d(e) IIC T6 2GD IP67, 68
Self monitoring PCB with H.A.R.T compatibility
Unit monitors initiation circuit
Option of 5 customer recordable messages, to suit their own
needs and languages (e.g.: “evacuate zone 4” in Polish)
SOUNDER OUTLINE SPECIFICATION
Raing
Tones
Voltage
Temperature class
Material
Mounting
Type of Protection
System details
120dB(A) @ 1 metre
Up to 42 tones, customer selectable
12V DC, 24V DC, 110V AC, and 240V AC
Board voltage selectable at installation stage
-55˚C to +70˚C
Glass reinforced polyester
Back strap or stirrup mounting
EEx d(e) IIC T6 2GD IP67, 68
Self mounting PCB with H.A.R.T compatibility
Unit monitors tone frequency, tone duratation, tone intensity
and initiation circuit
Customer selects voltage at installation point, and can alter
this rating at any time in the future
The unit has a volume control function which can
reduce the dba output accordingly
All Dimensions in mm
All Dimensions in mm
ORDERING INFORMATION
ORDERING INFORMATION
Note: Customer to specify combination of VB and VS
223
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Description
20watt Loud speaker
25watt Loud speaker
Product Code
VL20
VL25
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
224
Emergency Shutdown and Signalling Equipment
Type E501 - EEx d IIC Single Status/Indicator Lamp
EEx d IIC
Zones 1,2,21,22
T6
Emergency Shutdown and Signalling Equipment
Type E502
E2501D
- EEx
- EEx
d IIC
d IIC
Double
Status
Status/Indicator
Lamp
Lamp
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
II 2 GD
EEx d IIC T6
-20˚C to + 50˚C (T6)
-20˚C to + 85˚C (T5)
Zones 1,2,21,22 . Groups IIA, IIB, IIC
SIRA02ATEX1058 GOST’R’ POCC GB. гБ05. B01132
IP67 to EN60529:1991
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
Dimensions
Material
ATEX/GOST
II 2 GD
EEx d IIC T6
-20˚C to +50˚C (T6)
-20˚C to + 85˚C (T5)
Zones 1,2,21,22. Groups IIA, IIB, IIC
SIRA02ATEX1058 GOST’R’ POCC GB. гБ05. B01132
IP67 to EN60529:1991
ENTRY SPECIFICATION
1 x 20mm EEx d threaded entry at A and B
Each entry is fitted with an EEx d stopping plug
1 x 20mm EEx d threaded entry at A.
Each entry is fitted with an EEx d stopping plug.
ELECTRICAL SPECIFICATION
ELECTRICAL SPECIFICATION
220 – 254 Volts 50/60Hz
0.15 Amps max
2 x 2.5mm sq. connection block
15 Watt incandescent
BC type
Operating voltage
Operating current
Terminals
Lamp
Lampholder
220 – 254 Volts 50/60Hz
0.15 Amps max.
2 x 2.5mm sq. connection block
15 Watts incandescent
BC type
All Dimensions in mm
ORDERING INFORMATION
Description
EEx d miniature wellglass
EEx d miniature wellglass
EEx d miniature wellglass
EEx d miniature wellglass
EEx d miniature wellglass
Group II Cat 2
Double - 82mm diam x 319mm
All cast metal parts – cast iron
Overtube – coloured borosilicate glass
Cast metal parts - Epoxy powder coat RAL7032
2.0 Kg
Threaded junction
Nitrile O ring
Internal and external earths.
Two 8mm holes cast into base
Finish
Weight
Cover fixing
Gasket
Earthing
Mounting
ENTRY SPECIFICATION
Operating voltage
Operating current
Terminals
Lamp
Lampholder
T6
ENCLOSURE SPECIFICATION
Single - 90mm diam x 159mm
All cast metal parts – cast iron
Overtube – coloured borosilicate glass
Cast metal parts - Epoxy powder coat RAL7032
2.0 Kg
Threaded junction
Nitrile O ring
Internal and external earths
Two 8mm holes cast into base
Finish
Weight
Cover fixing
Gasket
Earthing
Mounting
Zones 1,2,21,22
HAZARDOUS AREA SPECIFICATION
ENCLOSURE SPECIFICATION
Dimensions
Material
EEx d IIC
All Dimensions in mm
ORDERING INFORMATION
Glass Colour
White
Red
Green
Blue
Amber
Product Code
E501001
E501002
E501003
E501004
E501005
Description
EEx d miniature wellglass
EEx d miniature wellglass
EEx d miniature wellglass
EEx d miniature wellglass
EEx d miniature wellglass
Glass Colour
White - Red
Red - Green
Green - Amber
Blue - White
Amber - Red
Product Code
E502001
E502002
E502003
E502004
E502005
Note: Alternative colour arrangements can be specified by customer.
225
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
208
226
PART 10.0
INSTALLATION ACCESSORIES
Type SP
– EEx d and EEx e Stopping Plugs
Page 229
Type ESKE e
- EEx e Cable Glands
Page 230
Type ESKE i
– EEx i Cable Glands
Page 231
Type OSNJ.A2F
– EEx d Cable Glands for Non Armoured Cable
Page 232
Type WEID.E1WF
– EEx d Cable Glands for Single Wire Armoured Cable Page 233
Type BD
– EEx e Breather Drains
Type WDU and WPE – EEx e and EEx i Wiring Terminals
227
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Page 234
Page 235
228
Installation Accessories
Type SP - EEx d and EEx e Stopping Plugs
EEx e II and EEx d IIC
Zones 1,2,21,22
-20C to +70C
Installation Accessories
Type ESKE-e - EEx e Increased Safety Cable Glands
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of Protection
Temperature Class
Area Classification
Certification No.
Ingress Protection
EEx e II
Zones 1,2,21,22
-20C to +75C
Group II Cat 2
ATEX
HAZARDOUS AREA SPECIFICATION
II 2 GD
EEx d IIC and EEx e II
Ta -20˚C to +70˚C
Zones 1, 2, 21, 22 Groups IIA, IIB, IIC
Sira 04ATEX1365U
IP66 to EN60529:1992
Marking to 94/9/EC
Type of protection
Temperature classi
Area classification
Certification No.
Ingress protection
PRODUCT SPECIFICATION
II 2 GD
EEx e II
-20˚C to +75˚C
Zones 1, 2,21, 22
PTB05ATEX1068X
IP66,67,68 to EN60529:1992
PRODUCT SPECIFICATION
EEx e plugs are constructed from polyamide 66 or brass. They comprise of a male
threaded shaft with a lipped head which includes a hexagon head recess to allow
for fitting and removal. Beneath the head is a nitrile O ring which when compressed
provides a seal to the plug. The standard range of threads is M16 to M75 x 1.5,
however ET – BS31:1940(1979), NPT – ANSI/ASME:1983, BSP – BS21:1985 and
PG – DIN 40430:1971 are also available.
Material
Gasket
Colour
Polyamide
EDPM
Fitting and cap RAL 9005
EEx d plugs are constructed from brass, steel, or stainless steel and have two
design options, a threaded shaft with an hexagonal head or a threaded shaft with
an hexagonal head recess to allow for fitting and removal of the plug. The standard
range of threads is M16 to M75 x 1.5., however ET – BS31:1940(1979),
NPT – ANSI/ASME:1983, BSP – BS21:1985 and PG – DIN 40430:1971 are also
available.
All Dimensions in mm
ORDERING INFORMATION
Thread
M16
M20
M25
M32
M40
M50
M63
M75
Notes
229
ORDERING INFORMATION
Type EEx e Polyamide
Product Code
SPE16
SPE20
SPE25
SPE32
SPE40
SPE50
SPE63
SPE75
1 For Stainless steel add /SS to product code ie. SPD16/SS
2 Thread adaptors are available to order.
3 Other thread types to order
Type EEx e Brass
Product Code
SPE16B
SPE20B
SPE25B
SPE32B
SPE40B
SPE50B
SPE63B
SPE75B
Type EEx d Brass
Product Code Hex Head
Product Code Hex Recessed
SPD16
SPD20
SPD25
SPD32
SPD40
SPD50
SPD63
SPD75
SPDR16
SPDR20
SPDR25
SPDR32
SPDR40
SPDR50
SPDR63
SPDR75
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Thread size mm
M16 x 1.5
M20 x 1.5
M25 x 1.5
M32 x 1.5
M40 x 1.5
M50 x 1.5
M63 x 1.5
Thread Length mm
9
Cable Diam.
4.9
Total Length
31.37
10
10
12
12
14
15
6.13
7.17
13.21
17.28
23.35
31.48
36.45
38.47
42.51
52.65
59.72
64.78
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Product Code
ESKE- e 16
ESKE- e 20
ESKE- e 25
ESKE- e 32
ESKE- e 40
ESKE- e 50
ESKE- e 63
230
Installation Accessories
Type ESKE-i - EEx i Intrinsically Safe Cable Glands
EEx i IIC
Zones 1,2,21,22
-20C to +75C
Installation Accessories
Type OSNJ A2F - EEx d Cable Glands for Non Armoured Cable
Group II Cat 2
ATEX
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
EEx d IIC
Zones 1,2,21,22
-40C to +100C
Group II Cat 2
ATEX
HAZARDOUS AREA SPECIFICATION
II 2 GD
EEx i IIC
-20˚C to +75˚C
Zones 1,2,21,22
PTB05ATEX1068X
IP66,67,68 to EN60529:1992
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
II 2 GD
EEx d II C For housings with an internal
volume equal to or less than 2000 cubic mm
-40˚C to +100˚C
Zones 1,2,21,22
PTB02ATEX1460X
IP66,67 to EN60529:1992
PRODUCT SPECIFICATION
PRODUCT SPECIFICATION
Material
Gasket
Colour
Polyamide
EDPM
Fitting RAL 9005, Cap nut RAL 5012
Material
Gasket
Brass nickel plated. Stainless steel on request
EDPM
All Dimensions in mm
All Dimensions in mm
ORDERING INFORMATION
Thread size mm
M16 x 1.5
M20 x 1.5
M20 x 1.5
M20x 1.5
M25 x 1.5
M25x 1.5
M32 x 1.5
M32 x 1.5
M40 x 1.5
M40 x 1.5
M50 x 1.5
M50 x 1.5
M63 x 1.5
M63 x 1.5
M75 x 1.5
M75 x 1.5
ORDERING INFORMATION
Thread size mm
M16 x 1.5
M20 x 1.5
M25 x 1.5
M32 x 1.5
M40 x 1.5
M50 x 1.5
M63 x 1.5
Thread Length mm
9
Cable Diam.
4.9
Total Length
31.37
10
10
12
12
14
15
6.13
7.17
13.21
17.28
23.35
31.48
36.45
38.47
42.51
52.65
59.72
64.78
Product Code
ESKE- i 16
ESKE- i 20
ESKE- i 25
ESKE- i 32
ESKE- i 40
ESKE- i 50
ESKE- i 63
Notes
231
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
Thread Length mm
15
Cable Diam.
3.6
15
15
15
15
15
15
15
15
15
15
15
15
15
20
20
6.1-10
10-13
13.1-15
15.1-16
16.1-18
18.1-22
22.1-26
26.1-28
28.1-32
32.1-34
34.1-40
40.1-44
44.1-50
54.1-56
56.1-60
Product Code
OSNJ A2F - 16a
OSNJ A2F - 16b
OSNJ A2F - 20a
OSNJ A2F - 20b
OSNJ A2F - 25a
OSNJ A2F - 25b
OSNJ A2F - 32a
OSNJ A2F - 32b
OSNJ A2F - 40a
OSNJ A2F - 40b
OSNJ A2F - 50a
OSNJ A2F - 50b
OSNJ A2F - 63a
OSNJ A2F - 63b
OSNJ A2F - 75a
OSNJ A2F - 75b
1 Available in Stainless Steel add /SS to product code eg. OSNJ A2F -16a/SS
2 Available with earth tag and shroud
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
232
Installation Accessories
Type WEID.E1WF - EEx d Cable Glands for Single Wire Armoured Cable
EEx d IIC
Zones 1,2,21,22
-40C to +100C
Group II Cat 2
ATEX
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
EEx e II
Zones 1,2,21,22
-50C to +120C
Group II Cat 2
ATEX/GOST
HAZARDOUS AREA SPECIFICATION
II 2 GD
EEx d II C
-40˚C to +100˚C
Zones 1,2,21,22
Nemko02ATEX500X
IP66,67 to EN60529:1992
Marking to 94/9/EC
Type of protection
Temperature class
Area classification
Certification No.
Ingress protection
PRODUCT SPECIFICATION
Material
Gasket
Installation Accessories
Type BD - EEx e Breather Drains
II 2 GD
EEx e II
Ta –20˚C to +60˚C (Nylon)
Ta -50˚C to +120˚C (Brass)
Ta -50˚C to +120˚C (Stainless)
Zones 1,2,21,22 Groups IIA, IIB, IIC
SIRA 02 ATEX M207
IP66
PRODUCT SPECIFICATION
Brass nickel plated. Stainless steel on request
EDPM
Double compression for inner/outer jacket of cable
A drain plug is is manufactured with a range of male threads. To suit most
applications, the head of increased diameter enables improved sealing, and with
the inclusion of an “O” ring or the use of a washer, will achieve IP66. The head has
a series of interconnecting holes, thus enabling drainage to occur. The unique filter
is fixed inside the main bore and facilitates a slow drainage and prevents ingress.
Fastened by means of an allen key (10mm) the drain plug should be fitted at the
lowest point of the enclosure.
EEx e breather drains are constructed from brass, nylon or stainless steel.
ORDERING INFORMATION
Thread
M20
M25
1/2” NPT
Type EEx e Nylon
BDN20
BDN25
BDN1/2
Type EEx e Brass
BDB20
BDB25
BDB1/2
Type EEx e Stainless Steel
BDS20
BDS25
BDS1/2
All Dimensions in mm
ORDERING INFORMATION
Thread size mm
M16 x 1.5
M20 x 1.5
M20 x 1.5
M25x 1.5
M25 x 1.5
M32x 1.5
M32 x 1.5
M40 x 1.5
M40 x 1.5
M50 x 1.5
M50 x 1.5
M63 x 1.5
M63 x 1.5
M63 x 1.5
M75 x 1.5
M75 x 1.5
Notes
233
Cable Diam. mm
8-15.1
Cable Diam. Below cable sheath mm
5-11
13-17.5
17.6-19.5
17.5-22
22.1-26
22-28
28.1-32
30-35
35.1-40
38-45
41.5-50
48-53
53.1-56
56.1-60
56-62
62.1-66
8-15.1
8-15.1
13-19.5
13-19.5
17.5-26
17.5-26
22-32
22-32
30-40
30-40
38-53
38-53
38-53
49-53
49-53
Product Code
WEID.E1WF- 16
WEID.E1WF- 20a
WEID.E1WF- 20b
WEID.E1WF- 25a
WEID.E1WF- 25b
WEID.E1WF- 32a
WEID.E1WF- 32b
WEID.E1WF- 40a
WEID.E1WF- 40b
WEID.E1WF- 50a
WEID.E1WF- 50b
WEID.E1WF- 63a
WEID.E1WF- 63b
WEID.E1WF- 63c
WEID.E1WF- 75a
WEID.E1WF- 75b
1 Available in Stainless Steel add /SS to product code eg. WEID.E1WF-16/SS
2 Available with earth tag and shroud
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
234
Installation Accessories
Type WDU and WPE - EEx e and EEx i Wiring Terminals
EEx e II and EEx i IIC
Zones 1,2,21,22
T6
Group II Cat 2
Terms of Sale and Delivery
ATEX
All deliveries are subject to our “General Terms of Sale and Delivery”.
All data is subject to alteration and drawing are subject to modification.
Illustrations may not be to scale. All prices can be found in a seperate
list. This catalogue is valid from April 2006 and replaces any previous
information. The seperate price list supersedes any previously issued
prices or pricelists.
Walsall Ltd fits Weidmuller component approved EEx terminals types WDU beige,
WDU blue and WPE earth terminals as standard. Unless otherwise specified these
terminals will always be used in all Walsall products.
Lists of the most popular sizes encountered are given below. These are not
exhaustive but reflect the vast majority used by Walsall and those generally carried
in stock. If terminals outside these ranges are required they are readily available.
ORDERING INFORMATION
Size
2.5mmsq.
4.0mmsq.
6.0mmsq.
10mmsq.
16mmsq.
35mmsq.
70/95mmsq.
120/150mmsq.
235
EEx e
Beige
WDU 2.5
WDU 4
WDU 6
WDU 10
WDU 16
WDU 35
WDU 70/95
WDU 120/150
EEx i
Blue
WDU 2.5 blue
WDU 4 blue
WDU 6 blue
WDU 10 blue
WDU 16 blue
WDU 35 blue
WDU 70/95 blue
WDU 120/150 blue
EEx e,i
Earth
WPE 2.5
WPE 4
WPE 6
WPE 10
WPE 16
WPE 35
WPE 70/95
WPE 120/150
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
236
Notes
237
Notes
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
tel: +44 (0)121 500 6161 fax: +44 (0)121 500 6300 [email protected] www.walsall-ltd.com
238