GE Security Aritech Fire Systems Products Catalogue
Transcription
GE Security Aritech Fire Systems Products Catalogue
GE Security Aritech Fire Systems Products Catalogue g In this catalogue you will find a wide range of Fire Protection equipment from GE Security. GE Security is a global technology leader dedicated to supporting the needs of the rapidly growing electronic security industry and to expanding current technologies, products and services that GE Security, unrivalled expertise in Fire Protection create revenue growth opportunities for its customers. As part of the GE family, GE Security shares the spirit of innovation that has distinguished GE for well over 100 years. GE Security's commitment to the ongoing success of its partners and affiliates means that we maintain a sharp focus on product and service innovation, world-class manufacturing practices and operational excellence. GE Security is a worldwide organisation with sales and technical support operations in 27 countries, and manufacturing and logistics operations in Europe, the U.S. and China. GE Security has expertise in all areas of electronic security, including: z Intrusion and Fire Protection z Electronic Access and Facility Management z Key Management and Remote Access Systems and Services z Fibre Optic Transmission and Reception Equipment z CCTV, Digital Video and Surveillance Equipment z Video Multiplexing and Digital Storage When you're looking for the finest in Fire Protection products with leading-edge technology and the backing of a world leader, you need look no further than this catalogue. Perimeter detection Page : 3 DI322I Ionisation detector, conventional The 300 Series conventional fire detectors are the ideal solution for any conventional installation. They are built specifically for use with the Aritech FP400, FP500, FP600 and FP700 series conventional fire panels, but can also be connected to most 3rd party industry standard conventional control panels. Specifications Operating voltage 18 to 28 VDC Current consumption Quiescent at 24 VDC 30 A Alarm at 24 VDC < 100 mA Radio-active source Americium 241 Average activity 0.33 +/-0.04 Ci (12.1 +/- 1.5 kBq) Remote alarm output < 100 mA Heat specification Operating temperature -10 to +60 °C Storage temperature -10 to +70 °C Humidity (non-condensing) 0 - 95% IP rating IP43 Number of detectors per zone 20 Recommended protection resistor 300 ohm Head 45 mm x 99 mm Base 24 mm x 103 mm EN54 (BOSEC) * Check current status with local office Ordering Information DI322I detectors E An ultra-fine grid prevents the ingress of dust and Dimensions (h x Ø) Approvals* E Full line consisting of Optical, Ionisation and Heat Ionisation detector, conventional KZ700 Universal fire detector base KZ705 Universal fire detector base with earth connection KZ705D Conventional fire detector base with diode PA25/3L Low current remote LED indicator insects in smoke detectors E Attractive, low-profile design E EN54 approved * E Innovative base compensates for uneven surfaces Page : 4 Optical detector, conventional, with field exchangeable optical block DP331I The 300 Series conventional fire detectors are the ideal solution for any conventional installation. They are built specifically for use with the Aritech FP400, FP500, FP600 and FP700 series conventional fire panels, but can also be connected to most 3rd party industry standard conventional control panels. Specifications Operating voltage 9 to 28 VDC Current consumption Quiescent at 24 VDC 85 A Alarm at 24 VDC < 100 mA Radio-active source Average activity Remote alarm output < 100 mA Heat specification Operating temperature -10 °C to +70 °C Storage temperature -10 °C to +70 °C Humidity (non-condensing) 95% IP rating IP43 Number of detectors per zone 20 Recommended protection resistor 300 ohm Head 45 mm x 99 mm Base 24 mm x 103 mm EN54 (BOSEC) * Check current status with local office Ordering Information DP331I Optical detector, conventional, with field exchangeable optical block KOB700 Replacement Optical Chamber for KL731/A & DP331I/1561 detectors KZ700 KZ705 KZ705D KZ705R detectors E An ultra-fine grid prevents the ingress of dust and Dimensions (h x Ø) Approvals* E Full line consisting of Optical, Ionisation and Heat Universal fire detector base Universal fire detector base with earth connection Conventional fire detector base with diode Conventional 12 VDC fire detector base with relay PA25/3L Low current remote LED indicator insects in smoke detectors E Attractive, low-profile design E EN54 approved * E Innovative base compensates for uneven surfaces Conventional Fire Systems Page : 5 DT313I Temperature detector (fixed and rate-of-rise), conventional The 300 Series conventional fire detectors are the ideal solution for any conventional installation. They are built specifically for use with the Aritech FP400, FP500, FP600 and FP700 series conventional fire panels, but can also be connected to most 3rd party industry standard conventional control panels. Specifications Operating voltage 18 to 28 VDC Current consumption Quiescent at 24 VDC 70 A Alarm at 24 VDC < 100 mA Radio-active source Average activity Remote alarm output < 100 mA Heat specification Max. & ROR to EN54p5 Operating temperature -10 °C to +70 °C Storage temperature -10 °C to +80 °C Humidity (non-condensing) 95% IP rating IP43 Number of detectors per zone 20 Recommended protection resistor 300 ohm Head 45 mm x 99 mm Base 24 mm x 103 mm EN54 (BOSEC) * Check current status with local office Ordering Information DT313I detectors E An ultra-fine grid prevents the ingress of dust and Dimensions (h x Ø) Approvals* E Full line consisting of Optical, Ionisation and Heat Temperature detector (fixed and rate-of-rise), conventional KZ700 Universal fire detector base KZ705 Universal fire detector base with earth connection KZ705D Conventional fire detector base with diode PA25/3L Low current remote LED indicator insects in smoke detectors E Attractive, low-profile design E EN54 approved * E Innovative base compensates for uneven surfaces Conventional Fire Systems Page : 6 KCT731 Calibration Tool for KL731/DP331I Fire Detectors The KCT731 is a calibration tool to recalibrate the conventional detectors after replacement of the field exchangeable optical block. Specifications Supply 2 x 9 V batteries Dimensions (w x h x d) 104 x 195 x 63 mm Ordering Information KCT731 Calibration Tool for KL731/DP331I Fire Detectors E Easy to use E Simple "go/no-go" function E Battery operated Detector Bases & Accessories Page : 7 KZ700 Universal fire detector base The KZ700 is a 4 contact universal detector base. It has the ability to compensate for uneven mounting surfaces. It is also available in black for special applications in false ceilings. Specifications Dimensions Diameter 104 mm Height 24 mm Ordering Information KZ700 Universal fire detector base KZ700B Universal fire detector base (for KL700/A and Dx300/1500) - Black E Polarity sensitive E Universal base fits conventional and analogue detectors E E E E Compensates for uneven surfaces Remote indicator contact available EN54 approved Variant in black also available Detector Bases & Accessories Page : 8 KZ705 Universal fire detector base with earth connection The KZ705 is a 5 contact universal detector base for use with the KL700/Dx300 and KL700A/Dx1500 series detectors from GE-Interlogix. In addition to the normal base and remote indication connectors, the KZ705 also has an additional earth terminal connector to allow for easy terminations of a possible cable screen. Specifications Dimensions (Ø x h) 100 x 29 mm Operating Voltage - Current Consumption - Isolation Current - Isolation Resistance - Sounder Frequency - Sound Output @ 3 mA - @ 5 mA - Environmental Characteristics Operating Temperature -10 to 70 °C Storage Temperature -10 to 70 °C Relative Humidity (max) 95 % (non-cond.) Ordering Information KZ705 Universal fire detector base with earth connection E Polarity sensitive E Universal base fits conventional and analogue detectors E Additional earth terminal available E Remote indicator contact available Conventional Fire Systems Page : 9 KZ705D Conventional fire detector base with diode The KZ705D is a 5 contact universal detector base for use with the KL700/Dx300 series detectors from GE-Interlogix. In addition to the normal base and remote indication connectors, the KZ705D also has an additional earth terminal connector to allow for easy terminations of a possible cable screen. The built in diode is specifically targeted at systems using active end-of-line devices. Specifications Dimensions (Ø x h) 100 x 29 mm Operating Voltage - Current Consumption - Isolation Current - Isolation Resistance - Sounder Frequency - Sound Output @ 3 mA - @ 5 mA - Environmental Characteristics Operating Temperature -10 to 70 °C Storage Temperature -10 to 70 °C Relative Humidity (max) 95 % (non-cond.) Ordering Information KZ705D Conventional fire detector base with diode E E E E E Polarity sensitive Universal base for conventional detectors Additional earth terminal available Remote indicator contact available Built in diode for active end-of-line systems EOL-ACT Active end-of-line device for use with FP400/KL700 fire panels The EOL-ACT is designed for use with the NK700/FP400 fire panels from GE-Interlogix. It is an active end-of-line device to allow the monitoring of a conventional zone through a diode base (such as the KZ705D). Ordering Information EOL-ACT Active end-of-line device for use with FP400/KL700 fire panels E Small E Easy to install Conventional Fire Systems Page : 10 KZ705R Conventional 12 VDC fire detector base with relay The KZ705R is a 5 contact detector base for use with the KL731/DP331I detectors from GE-Interlogix. In addition to the normal base and remote indication connectors, the KZ705R also has an additional earth terminal connector to allow for easy terminations of a possible cable screen. A built in 12 V relay makes it ideal for use on low voltage intrusion systems. Specifications Dimensions (Ø x h) 100 x 29 mm Operating Voltage 12 V ± 10% Current Consumption 12 A Isolation Current - Isolation Resistance - Sounder Frequency - Sound Output @ 3 mA - @ 5 mA - Environmental Characteristics Operating Temperature -10 °C to +70 °C Storage Temperature -10 °C to +70 °C Relative Humdity 95 % (non cond.) Ordering Information KZ705R Conventional 12 VDC fire detector base with relay E E E E Polarity sensitive 12 V relay for 4 wire systems Additional earth terminal available Remote indicator contact available Detector Bases & Accessories Page : 11 S700 Surface mount accessory for KZ700 and KZ705 series bases The S700 is a base accessory designed for use with the KZ700 series detector bases. It allows for a surface mount conduit and cable to enter the base from the side. The KZ700 series base fits on top of this accessory. Specifications Dimensions Diameter 95 mm Height 30 mm Ordering Information S700 Surface mount accessory for KZ700 and KZ705 series bases E Surface mount accessory for KZ700 series bases Conventional Fire Systems Page : 12 DP721I Photoelectric smoke detector with remote alarm LED output 700 series The smoke detector continually monitors its own sensitivity and operational status. Once a day, it performs a full diagnostic test which includes dynamically testing the sensing chamber and internal electronics. Specifications Operating voltage 8.5 - 33 V dc Current consumption Quiescent at 24 V dc 100 A; Max. 70 A average In alarm at 24 V dc 60 mA Alarm indication White LED (red alarm) Fault indication Yellow LED Remote alarm output 30 mA RY contact rating Relay models 2 A @ 30 V dc;1 A @ 120 V ac Humidity 0 - 95%; Non-condensing IP rating IP 43 Operating temperature -10°C - 60°C Sensitivity 10%/m (+1.6%, -3.3%) Reset voltage 2,5 V max Reset time 1 sec Dimensions 10 cm Ø, H = 5 cm E Automatic Self Diagnostics : Dynamic full detector test, Sensitivity test E Manual Self Diagnostic routine with visual sensitivity indication Ordering Information DP721I Photoelectric smoke detector with remote alarm LED output DP721R Photoelectric smoke detector with C/O relay output DB702 10 cm diameter base - 6 terminals E E E E E E E Field sensitivity testing without external meters Field exchangeable and disposable optical chamber High false alarm immunity Floating background with drift compensation Separate fire and trouble LED 12 - 24 V dc operation Polarity insensitive E Full range : optical, heat and optical/heat multi criteria sensor E EN 54 approved Conventional Fire Systems Page : 13 Photoelectric smoke and heat detector head with remote alarm LED DP721T 700 series Fitted with a field-exchangeable optical block. The smoke detector continually monitors its own sensitivity and operational status. Once a day, it performs a full diagnostic test which includes dynamically testing the sensing chamber and internal electronics. Specifications Operating voltage 8.5 - 33 V dc FWR Current consumption Quiescent at 24 V dc 100 A; Max. 70 A average In alarm at 24 V dc 60 mA Alarm indication White LED (red alarm) Fault indication Yellow LED Remote alarm output 30 mA RY contact rating 2 A @ 30 V dc;1 A @ 120 V ac Humidity 0 - 95%; Non-condensing IP rating IP 43 Sensitivity 10%/m (+1.6%, -3.3%) Reset voltage 2,5 V max Reset time 1 sec Dimensions 10 cm Ø, H = 5 cm E Automatic Self Diagnostics : Dynamic full detector test, Sensitivity test Ordering Information E Manual Self Diagnostic routine with visual sensitivity DP721T DP721RT DP721RTA DB702 Photoelectric smoke and heat detector head with remote alarm LED Photoelectric smoke and heat detector with relay output Photoelectric smoke and heat detector with relay output, autoreset 10 cm diameter base - 6 terminals indication E E E E E E E Field sensitivity testing without external meters Field exchangeable and disposable optical chamber High false alarm immunity Floating background with drift compensation Separate fire and trouble LED 12 - 24 V dc operation Polarity insensitive E Full range : optical, heat and optical/heat multi criteria sensor E EN 54 approved Conventional Fire Systems Page : 14 DT713-5 57º C fixed and rate-of-rise heat detector 700 series The smoke detector continually monitors its own sensitivity and operational status. Once a day, it performs a full diagnostic test which includes dynamically testing the sensing chamber and internal electronics. Specifications Operating voltage 8.5 - 33 V dc FWR Current consumption Quiescent at 24 V dc 100 A; Max. 70 A average In alarm at 24 V dc 60 mA Alarm indication Red LED Fault indication Yellow LED Remote alarm output 30 mA RY contact rating 2 A @ 30 V dc;1 A @ 120 V ac Humidity 0 - 95%; Non-condensing IP rating IP 43 Heat specification Max. 57º C ± 1.5º C R.O.R. 8º C/min and > 40° C Sensitivity Reset voltage 2,5 V max Reset time 1 sec Dimensions 10 cm Ø, H = 5 cm Ordering Information DT713-5 57º C fixed and rate-of-rise heat detector DT713-5R 57º C and R.O.R. heat detector, with relay output DB702 10 cm diameter base - 6 terminals E Automatic Self Diagnostics : Dynamic full detector test, Sensitivity test E Manual Self Diagnostic routine with visual sensitivity indication E E E E E E E Field sensitivity testing without external meters Field exchangeable and disposable optical chamber High false alarm immunity Floating background with drift compensation Separate fire and trouble LED 12 - 24 V dc operation Polarity insensitive E Full range : optical, heat and optical/heat multi criteria sensor E EN 54 approved Conventional Fire Systems Page : 15 DT713-7 70º C fixed and R.O.R. heat detector 700 series The smoke detector continually monitors its own sensitivity and operational status. Once a day, it performs a full diagnostic test which includes dynamically testing the sensing chamber and internal electronics. Specifications Operating voltage 8.5 - 33 V dc FWR Current consumption Quiescent at 24 V dc 100 A; Max. 70 A average In alarm at 24 V dc 60 mA Alarm indication Red LED Fault indication Yellow LED Remote alarm output 30 mA RY contact rating 2 A @ 30 V dc;1 A @ 120 V ac Humidity 0 - 95%; Non-condensing IP rating IP 43 Heat specification Max. 70º C ± 1.5º C R.O.R. 8º C/min and > 40° C Reset voltage 2,5 V max Reset time 1 sec Dimensions 10 cm Ø, H = 5 cm E Automatic Self Diagnostics : Dynamic full detector test, Sensitivity test E Manual Self Diagnostic routine with visual sensitivity indication Ordering Information DT713-7 70º C fixed and R.O.R. heat detector DB702 10 cm diameter base - 6 terminals E E E E E E E Field sensitivity testing without external meters Field exchangeable and disposable optical chamber High false alarm immunity Floating background with drift compensation Separate fire and trouble LED 12 - 24 V dc operation Polarity insensitive E Full range : optical, heat and optical/heat multi criteria sensor E EN 54 approved Conventional Fire Systems Page : 16 DB702 10 cm diameter base - 6 terminals 700 series Detector base for 700 series detectors Ordering Information DB702 10 cm diameter base - 6 terminals DB702U 15 cm diameter base - 6 terminals E Automatic Self Diagnostics : Dynamic full detector test, Sensitivity test E Manual Self Diagnostic routine with visual sensitivity indication E E E E E E E Field sensitivity testing without external meters Field exchangeable and disposable optical chamber High false alarm immunity Floating background with drift compensation Separate fire and trouble LED 12 - 24 V dc operation Polarity insensitive E Full range : optical, heat and optical/heat multi criteria sensor E EN 54 approved Conventional Fire Systems Page : 17 DI650 Ionisation smoke detector 650 series This elegant slim-line ionisation detector offers high performance and wide operating voltage Specifications Size of detector (mm) Height 42 Diameter 100 Size of detector + base (mm) Height 50 Diameter 100 Supply voltage 9 - 33 V dc Quiescent Current at 24 V (typical) 28 A Alarm indication LED Normal operating temp. range (no icing) -20 to + 60°C Humidity (no condensation) 0-95% RH Max. wind 10m/s Remote alarm output current 17 mA IP Rating 43 Ordering Information DI650 Ionisation smoke detector DI651 Integrating ionisation smoke dectector DB860 Standard Base E E E E E E E E E Wide operating voltage Advanced electronic technology Flashing LED option Polarity insensitive Common base Elegant slim-line design EN54 approved Magnetic test switch option Proven detection performance Conventional Fire Systems Page : 18 DP652 Optical smoke detector 650 series This elegant slim-line optical sensor provides high performance and wide operating range. Specifications Size of detector (mm) Height 42 Diameter 100 Size of detector + base (mm) Height 50 Diameter 100 Supply voltage 9 - 33 V dc Quiescent Current at 24 V (typical) 40 A Alarm indication LED Normal operating temp. range (no icing) -20 to + 60°C Humidity (no condensation) 0-95% RH Max. wind Not affected Remote alarm output current 17 mA IP Rating 43 Ordering Information DP652 Optical smoke detector DB860 Standard Base E E E E E Polarity insensitive Common base Elegant slim-line design EN 54 approved Wide operating voltage Conventional Fire Systems Page : 19 DT654 Heat detector, R.O.R., 57º C A1R 650 series This elegant slim-line heat sensor has a wide operating temperature and is available in four ranges Specifications Size of detector (mm) Height 42 Diameter 100 Size of detector + base (mm) Height 50 Diameter 100 Supply voltage 9 - 33 V dc Quiescent Current at 24 V (typical) 45 A Alarm indication LED Normal operating temp. range (no icing) -20 to + 60°C Humidity (no condensation) 0-95% RH Max. wind Not affected Remote alarm output current 17 mA IP Rating 54 Ordering Information DT654 DT655 DT656 DT657 DB860 Heat detector, R.O.R., 57º C A1R Heat detector, 75º C BR Heat detector, 95º C CR Heat detector, 90º C CS Standard Base E E E E E E E E E Wide operating voltage Advanced electronic technology Flashing LED option Polarity insensitive Common base Elegant slim-line design EN54 approved Magnetic test switch option Proven detection performance Conventional Fire Systems Page : 20 DB860 Standard Base 650 series The base has been designed to enable detectors to be plugged in without any need for force - particularly useful when fitting to suspended ceilings. Ordering Information DB860 Standard Base DB860U Standard base 15 cm diameter E E E E E Backplate for Ingress Protection 860-950 860 series Conventional fire detectors Polarity insensitive Common base Elegant slim-line design EN 54 approved DB861 Ordering Information DB861 Backplate for Ingress Protection 860-950 E Can prevent most ingress into the base and detector Conventional Fire Systems Page : 21 DB806 Conduit box for 860 / 950 series bases An inexpensive and versatile accessory for surface mounting 860 and 950 series bases Ordering Information DB806 Conduit box for 860 / 950 series bases DB650 650 series relay base 650 series The relay base provides a volt-free contact for use in 4 wire control systems, and other applications Ordering Information DB650 650 series relay base E E E E DB650 For use with 4 wire control systems Automatic door closers Volt-free relay contacts Addressable Fire Systems Page : 22 DI1552 Ionisation Sensor The 1500 Series uses a microprocessor for measurement and communication. An enhanced protocol ensures the overall integrity and error free operation of the system, without compromising detection speed. All sensors are compatible with a standard base that makes them easily interchangeable and support the connection of a remote indicator. Specifications Operating voltage 22 to 38 VDC Current consumption Quiescent @ 38 VDC 200 A In Alarm < 11 mA Alarm indication (Dual LED) White OFF - Red ON Remote Alarm Output Available Environment Storage Temperature -10 to +70 °C Operating Temperature -10 to +60 °C Humidity (non-condensing) 0-95% IP rating IP42 Radioactive Source 0.33 ± 0.04 Ci Am 241 Dimensions (h x Ø) 45 x 99 mm Ordering Information DI1552 Ionisation Sensor KZ700 KZ705 KZ705AS KZ705I KZ705IAS Universal fire detector base Universal fire detector base with earth connection Analogue fire detector base with sounder Analogue fire detector base with isolator Analogue fire detector base with isolator and sounder PA25/3L Low current remote LED indicator E E E E E E Remote signalling capabilities Optical sensor with field exchangeable optical chamber Easy soft addressing (1-125) SMD technology Reliable communication protocol Full diagnostic self testing E Full range: Ionisation, Optical and Heat and Dual sensors (optical/heat) E Full range of supporting I/O units and accessories E EN54 Approved Addressable Fire Systems Page : 23 DP1561 Optical sensor with field exchangeable optical block The 1500 series detectors use a microprocessor for measurement and communication. An enhanced protocol ensures the overall integrity and error free operation of the system, without compromising detection speed. All sensors are compatible with a standard base that makes them easily interchangeable and support the connection of the PA25/3L remote indicator. Specifications Operating voltage 22 to 38 VDC Current consumption Quiescent @ 38 VDC 350 A In Alarm < 11 mA Alarm indication (Dual LED) Red Remote Alarm Output Available Environment Storage Temperature -10 to +70 °C Operating Temperature -10 to +60 °C Humidity (non-condensing) 0-95% IP rating IP42 Remote signalling capabilities DP1561 Optical sensor with field exchangeable optical block E E E E E E KOB700 Replacement Optical Chamber for KL731/A & DP331I/1561 detectors E Full range: Ionisation, Optical and Heat and Dual KZ700 KZ705 KZ705AS KZ705I KZ705IAS Universal fire detector base Universal fire detector base with earth connection Analogue fire detector base with sounder Analogue fire detector base with isolator Analogue fire detector base with isolator and sounder E Full range of supporting I/O units and accessories E EN54 Approved PA25/3L Low current remote LED indicator Radioactive Source NA Dimensions (h x Ø) 45 x 99 mm Ordering Information Optical sensor with field exchangeable optical chamber Easy soft addressing (1-125) SMD technology Reliable communication protocol Full diagnostic self testing sensors (optical/heat) Addressable Fire Systems Page : 24 DP1551T Dual Sensor (Optical/Heat) The 1500 Series uses a microprocessor for measurement and communication. An enhanced protocol ensures the overall integrity and error free operation of the system, without compromising detection speed. All sensors are compatible with a standard base that makes them easily interchangeable and support the connection of aremote indicator. Specifications Operating voltage 22 to 38 VDC Current consumption Quiescent @ 38 VDC 350 A In Alarm < 5 mA Alarm indication (Dual LED) Red Remote Alarm Output Available Environment Storage Temperature -10 to +70 °C Operating Temperature -10 to +70 °C Humidity (non-condensing) 0-95% IP rating IP42 Radioactive Source NA Dimensions (h x Ø) 51 x 99 mm Ordering Information DP1551T Dual Sensor (Optical/Heat) KZ700 KZ705 KZ705AS KZ705I KZ705IAS Universal fire detector base Universal fire detector base with earth connection Analogue fire detector base with sounder Analogue fire detector base with isolator Analogue fire detector base with isolator and sounder PA25/3L Low current remote LED indicator E E E E E E Remote signalling capabilities Optical sensor with field exchangeable optical chamber Easy soft addressing (1-125) SMD technology Reliable communication protocol Full diagnostic self testing E Full range: Ionisation, Optical and Heat and Dual sensors (optical/heat) E Full range of supporting I/O units and accessories E EN54 Approved Addressable Fire Systems Page : 25 DT1553 Heat Sensor The 1500 Series uses a microprocessor for measurement and communication. An enhanced protocol ensures the overall integrity and error free operation of the system, without compromising detection speed. All sensors are compatible with a standard base that makes them easily interchangeable and support the connection of aremote indicator. Specifications Operating voltage 22 to 38 VDC Current consumption Quiescent @ 38 VDC 250 A In Alarm < 11 mA Alarm indication (Dual LED) White OFF - Red ON Remote Alarm Output Available Environment Storage Temperature -10 to +80 °C Operating Temperature -10 to +70 °C Humidity (non-condensing) 0-95% IP rating IP42 Radioactive Source NA Dimensions (h x Ø) 45 x 99 mm Ordering Information DT1553 Heat Sensor KZ700 KZ705 KZ705AS KZ705I KZ705IAS Universal fire detector base Universal fire detector base with earth connection Analogue fire detector base with sounder Analogue fire detector base with isolator Analogue fire detector base with isolator and sounder PA25/3L Low current remote LED indicator E E E E E E Remote signalling capabilities Optical sensor with field exchangeable optical chamber Easy soft addressing (1-125) SMD technology Reliable communication protocol Full diagnostic self testing E Full range: Ionisation, Optical and Heat and Dual sensors (optical/heat) E Full range of supporting I/O units and accessories E EN54 Approved Addressable Fire Systems Page : 26 PG700 Fire sensor programmer The PG700 is a handheld device programmer and tester for the KL700A/Dx1500 series detectors. It is battery operated and allows the installer to perform installation tasks (such as device addressing) and maintenance tasks (such as device calibration) in the field without external assistance. Specifications Supply 2 x 9 V batteries Dimensions (w x h x d) 104 x 195 x 63 mm Ordering Information PG700 Fire sensor programmer E Easy to use E Battery operated E 4 User selectable programs -Device analogue value -Change Device Address -Sequential device addressing -KL731A Calibration Addressable Fire Systems Page : 27 KZ705I Analogue fire detector base with isolator The KZ705I is a detector base with built in isolator for use with the KL700A/Dx1500 series detectors from GE-Interlogix. The isolator protects the loop from short circuit conditions. A LED on the side of the base indicates the status of the isolator. Specifications Dimensions (Ø x h) 100 x 29 mm Operating Voltage 17 - 34 V Current Consumption 50 A Isolation Current 6 mA Isolation Resistance 140 Mohm Sounder Frequency - Sound Output @ 3 mA - @ 5 mA - Environmental Characteristics Operating Temperature -10 °C to +70 °C Storage Temperature -10 °C to +70 °C Relative Humidity (max) 95 % (non cond.) Ordering Information KZ705I Analogue fire detector base with isolator E E E E E Polarity sensitive Universal base for analogue detectors Additional earth terminal available Remote indicator contact available Built in isolator Addressable Fire Systems Page : 28 KZ705AS Analogue fire detector base with sounder The KZ705AS is a detector base with built in analogue addressable sounder for use with the KL700A/Dx1500 series detectors from GE-Interlogix. The sounder has its own address on the fire panel loop and works independent of the detector. It is fully controlled from the fire panel. Specifications Dimensions (Ø x h) 120 x 58 mm Operating Voltage 22 - 38 V Current Consumption 300 A Quiescent Isolation Current - Isolation Resistance - Sounder Frequency 1 kHz (Continuous) Sound Output @ 3 mA 85 dBA @ 5 mA 90 dBA Environmental Characteristics Operating Temperature -10 °C to +70 °C Storage Temperature -10 °C to +70 °C Relative Humidity (max) 95 % (non cond.) IP Rating IP21c Ordering Information KZ705AS Analogue fire detector base with sounder E E E E E E E Polarity sensitive Universal base for analogue detectors Additional earth terminal available Remote indicator contact available Built in sounder Up to 90 dBA sound output Low current consumption Addressable Fire Systems Page : 29 KZ705IAS Analogue fire detector base with isolator and sounder The KZ705IAS is a detector base with built in analogue addressable sounder and isolator for use with the KL700A/Dx1500 series detectors from GE-Interlogix. The sounder has its own address on the fire panel loop and works independent of the detector. It is fully controlled from the fire panel. The isolator protects the loop from short circuit conditions. Specifications Dimensions (Ø x h) 120 x 58 mm Operating Voltage 22 - 38 V Current Consumption 350 A Quiescent Isolation Current 6 mA Isolation Resistance 140 Mohm Sounder Frequency 1 kHz (Continuous) Sound Output @ 3 mA 85 dBA @ 5 mA 90 dBA Environmental Characteristics Operating Temperature -10 °C to +70 °C Storage Temperature -10 °C to +70 °C Relative Humidity (max) 95 % (non cond.) IP Rating IP21c Ordering Information KZ705IAS Analogue fire detector base with isolator and sounder E E E E E E E E Polarity sensitive Universal base for analogue detectors Additional earth terminal available Remote indicator contact available Built in sounder Up to 90 dBA sound output Low current consumption Built in isolator Addressable Fire Systems Page : 30 KAL410 Conventional Zone Monitor Unit - 1 Zone Allows the connection of one conventional zone to the analogue fire system loop. This zone is constantly monitored. Up to 20 conventional devices may be connected to this zone. Specifications Supply voltage 22-38 VDC Current consumption Quiescent @ 24 V 90 A Quiescent @ 35 V 105 A Alarm < 3 mA Aux. supply (24 VDC) quiescent 200 A + equip Aux. supply (24 VDC) alarm < 85 mA End-of-line resistor 4.7 kohm Relay contact rating NA Environmental Storage temperature -10 °C to +50°C Operating temperature -10 °C to +70°C Relative humidity 95 % (non condensing) Dimensions (L x W x H) 117 x 80 x 44 mm Ordering Information KAL410 Conventional Zone Monitor Unit - 1 Zone E E E E E E Easy numeric addressing Continuous supervision of the conventional zones Surface mount Local alarm indication Externally or loop powered Aesthetically pleasing E Part of family of I/O modules consisting of: -Conventional Zone Monitors -Digital Input Modules -Extinguishing Control Modules -Isolator Modules -Manual Call Points -Output Units -Retention Units -Supervised Output Units for sounder control Addressable Fire Systems Page : 31 KAL414C Conventional Zone Monitor Unit - 4 Zones Allows the connection of four conventional zones to the analogue fire system loop. These zones are constantly monitored. Up to 20 conventional devices may be connected to any zone. Specifications Supply voltage 22-38 VDC Current consumption Quiescent @ 24 V 110 A Quiescent @ 35 V 135 A Alarm < 5 mA Aux. Supply (24V DC) Quiescent 200 A + equip Aux. Supply (24V DC) Alarm < 360 mA End-of-line resistor 4.7 kOhm Relay contact rating NA Environmental Storage temperature -10 to +50°C Operating temperature -10 to +70°C Relative humidity (non-condensing) 0-95 % Dimensions (l x w x h) 163 x 107 x 36 mm Ordering Information KAL414C Conventional Zone Monitor Unit - 4 Zones E E E E E E E E E E E E E E E Easy numeric addressing Continuous supervision of the conventional zones Surface mount Local alarm indication Externally powered Aesthetically pleasing Part of a family of I/O modules consisting of: - Conventional Zone Monitors - Digital Input Modules - Extinguishing Control Modules - Isolator Modules - Manual Call Points - Output Units - Retention Units - Supervised Output Units for sounder control Addressable Fire Systems Page : 32 KAL426C Extinguishing Control Module The 400 Series modules consists of a complete range of interfaces developed for input/output control in the KSA700/FP1500 analogue fire systems from GE Interlogix. The KAL426 allows for the connection and control of one extinguishing area to the addressable fire panel loop. Specifications Supply voltage 22-38 VDC Current consumption Quiescent @ 24 V 110 A Quiescent @ 35 V 210 A Alarm < 10 mA Aux. supply (24 VDC) quiescent 120 mA Aux. supply (24 VDC) alarm <1A End-of-line resistor 4.7 kOhm Relay contact rating 2½ A Environmental Storage temperature -10 °C to +50°C Operating temperature -10 °C to +70°C Relative humidity 95 % (non condensing) Dimensions (L x W x H) 163 x 107 x 36 mm Ordering Information KAL426C Extinguishing Control Module E E E E E Aesthetically pleasing Easy numeric addressing Externally powered Supervised I/O Surface mount E Part of family of I/O modules consisting of: -Conventional Zone Monitors -Digital Input Modules -Extinguishing Control Modules -Isolator Modules -Manual Call Points -Output Units -Retention Units -Supervised Output Units for sounder control Addressable Fire Systems Page : 33 KAL430 Relay Module - 1 Relay Provides for one potential free relay output for the fire system loop. Each relay allows for COMMON, NORMALLY OPEN and NORMALLY CLOSED contacts. The output may be used to activate ventilation controls, warning signs, activation of other alarm devices etc. during fire situations. Specifications Supply voltage 22-38 VDC Current consumption Quiescent @ 24 V 70 A Quiescent @ 35 V 100 A Alarm < 3.5 mA Aux. 24 VDC quiescent 22 mA Aux. 24 VDC alarm < 50 mA End-of-line resistor NA Relay contact rating 2½A @ 250 VAC Environmental Storage temperature -10 °C to +50°C Operating temperature -10 °C to +70°C Relative humidity 95 % (non condensing) Dimensions (L x W x H) Ordering Information KAL430 Relay Module - 1 Relay 117 x 80 x 44 mm E E E E E E Easy numeric addressing Externally or loop powered Normally open / normally closed operation for I/O Surface mount Aesthetically pleasing Local status indication E Part of family of I/O modules consisting of: -Conventional Zone Monitors -Digital Input Modules -Extinguishing Control Modules -Isolator Modules -Manual Call Points -Output Units -Retention Units -Supervised Output Units for sounder control Addressable Fire Systems Page : 34 KAL434C Addressable Relay Module - 4 Relays Provides for four potential free relay outputs for the fire system loop. Each relay allows for COMMON, NORMALLY OPEN and NORMALLY CLOSED contacts. The outputs may be used to activate ventilation controls, warning signs, activation of other alarm devices etc. during fire situations. Specifications Supply voltage 22-38 VDC Current consumption Quiescent @ 24 V 110 A Quiescent @ 35 V 135 A Alarm 10 mA Aux. 24VDC Quiescent 100 A Aux. 24VDC Alarm 10 mA End-of-line resistor NA Relay contact rating 2½A @ 250 VAC Environmental Storage temperature -10 to +50°C Operating temperature -10 to +70°C Relative humidity (non-cond.) 0-95 % Dimensions (l x w x h) 163 x 107 x 36 mm Ordering Information KAL434C Addressable Relay Module - 4 Relays E E E E E E E E E E E E E E E Easy numeric addressing Externally powered Normally open / normally closed operation for I/O Surface mount Aesthetically pleasing Local status indication Part of a family of I/O modules consiting of: - Conventional Zone Monitors - Digital Input Modules - Extinguishing Control Modules - Isolator Modules - Manual Call Points - Output Units - Retention Units - Supervised Output Units for sounder control Addressable Fire Systems Page : 35 KAL440 Supervised Relay Module Allows for the supervision of a single, 24 Volt powered output contact on the fire system loop. This unit may be used to control for e.g. sounders in case of fire conditions, but may also be used to switch any output considered crucial enough to have the cable integrity between the unit and the switch point monitored. Specifications Supply voltage 22-38 VDC Current consumption Quiescent @ 24 V 110 A Quiescent @ 35 V 135 A Alarm < 3.6 mA Aux. 24 VDC quiescent 23 mA Aux. 24 VDC alarm 23 mA + equip End-of-line resistor 4.7 kohm Relay contact rating 1¼ A @ 250 VAC Environmental Storage temperature -10 °C to +50°C Operating temperature -10 °C to +70°C Relative humidity 95 % (non condensing) Dimensions (L x W x H) 117 x 80 x 44 mm Ordering Information KAL440 Supervised Relay Module E E E E E E Easy numeric addressing Externally powered Supervised 24 VDC Output Surface mount Aesthetically pleasing Local status indication E Part of family of I/O modules consisting of: -Conventional Zone Monitors -Digital Input Modules -Extinguishing Control Modules -Isolator Modules -Manual Call Points -Output Units -Retention Units -Supervised Output Units for sounder control Addressable Fire Systems Page : 36 KAL450 Addressable Manual Call Point The 400 Series modules consists of a complete range of interfaces developed for input/output control in the KSA700/FP1500 analogue fire systems from GE Interlogix. The KAL450 is an addressable manual call point for manual fire activation. Specifications Supply voltage 22-38 VDC Current consumption Quiescent @ 24 V 90 A Quiescent @ 35 V 120 A Alarm < 3.5 mA Aux. supply (24 VDC) quiescent NA Aux. supply (24 VDC) alarm NA End-of-line resistor NA Relay contact rating NA Environmental Storage temperature -10 °C to +70°C Operating temperature -10 °C to +50°C Relative humidity 95 % (non condensing) Ingress Protection IP20 Dimensions (L x W x H) 87 x 87 x 20 mm Weight 98 g Ordering Information KAL450 DM715 DM780 DM781 DM782 DM783 DM784 DM785 DM787 DM788 DM790 DM795 DM798 DM799 DM800 Addressable Manual Call Point EN54 universal glass for manual call point Terminal tray for MCP GS card Hinged transparent MCP protection cover BZB black bezel Test key Spacer box, red Surface mounting box with connectors, red Surface mount box without connectors, red Flush mount cradle with connectors Flush mount cradle, connectors & forkgrips Breakable seal for MCP Terminal tray ETT/3 with bezel 3 Resettable element for MCP DM700/KAL450 E E E E E E Easy numeric addressing Loop powered Local test facility Surface or flush mount Aesthetically pleasing Local status indication E Part of family of I/O modules consisting of: -Conventional Zone Monitors -Digital Input Modules -Extinguishing Control Modules -Isolator Modules -Manual Call Points -Output Units -Retention Units -Supervised Output Units for sounder control E Wide range of accessories Addressable Fire Systems Page : 37 KAL460 Digital Input Module Provides a remote input to the fire system loop. The input is constantly monitored and its status communicated to the fire control panel. The input may be activated by closing or opening a potential free contact, depending on the module configuration. This module may be used to monitor any contact by showing its status through the fire control panel e.g. the monitoring of pressure equipment and closure fire break doors. Specifications Supply voltage 22-38 VDC Current consumption Quiescent @ 24 V 110 A Quiescent @ 35 V 135 A Alarm < 10 mA Aux. 24 VDC quiescent 200 A Aux. 24 VDC alarm < 50 mA End-of-line resistor NA Relay contact rating NA Environmental Storage temperature -10 °C to +50°C Operating temperature -10 °C to +70°C Relative humidity 95 % (non condensing) Dimensions (L x W x H) Ordering Information KAL460 Digital Input Module 117 x 80 x 44 mm E E E E E E Easy numeric addressing Externally or loop powered Normally open / normally closed operation for I/O Surface mount Aesthetically pleasing Local status indication E Part of family of I/O modules consisting of: -Conventional Zone Monitors -Digital Input Modules -Extinguishing Control Modules -Isolator Modules -Manual Call Points -Output Units -Retention Units -Supervised Output Units for sounder control Addressable Fire Systems Page : 38 KAL470 Isolator Module The 400 series modules consist of a complete range of interfaces developed for input/output control in the KSA700/FP1500 analogue fire systems from GE Interlogix. The KAL470 is an isolator module in this series that isolates the faulty zone on a fire panel loop during short circuit conditions. The KAL470 does not use an address on the loop. Specifications Supply voltage 22-38 VDC Current consumption Quiescent @ 24 V 110 A Quiescent @ 35 V 135 A Alarm 10 mA Aux. supply (24 VDC) quiescent NA Aux. supply (24 VDC) alarm NA End-of-line resistor NA Relay contact rating NA Environmental Storage temperature -10 °C to +50°C Operating temperature -10 °C to +50°C Relative humidity 95 % (non condensing) Dimensions (L x W x H) Ordering Information KAL470 Isolator Module 75 x 45 x 28 mm E E E E Requires no device address Automatic reset Local status indication Surface mount E Part of family of I/O modules consisting of: -Conventional Zone Monitors -Digital Input Modules -Extinguishing Control Modules -Isolator Modules -Manual Call Points -Output Units -Retention Units -Supervised Output Units for sounder control Addressable Fire Systems Page : 39 KAL490 Retention Module - 1 Input / 1 Output Provides a remote input and a potential free voltage relay output to the fire system loop. The input signal is constantly monitored and its status displayed on the control panel, whilst the output is fail-to-safe. Auxiliary supply monitoring is also included. The module is used to for e.g. control and monitor doors such as fire break doors. The relay provides the door activation and the input monitors the door status. Specifications Supply voltage 22-38 VDC Current consumption Quiescent @ 24 V 110 A Quiescent @ 35 V 135 A Alarm 10 mA Aux. 24 VDC quiescent 200 A Aux. 24 VDC alarm < 50 mA End-of-line resistor NA Relay contact rating 1A @ 30 VAC/VDC Environmental Storage temperature -10 °C to +50°C Operating temperature -10 °C to +70°C Relative humidity 95 % (non condensing) Dimensions (L x W x H) 117 x 80 x 44 mm Ordering Information KAL490 Retention Module - 1 Input / 1 Output E E E E E E Easy numeric addressing Externally or loop powered Normally open / normally closed operation for I/O Surface mount Aesthetically pleasing Local status indication E Part of family of I/O modules consisting of: -Conventional Zone Monitors -Digital Input Modules -Extinguishing Control Modules -Isolator Modules -Manual Call Points -Output Units -Retention Units -Supervised Output Units for sounder control Addressable Fire Systems Page : 40 DP2051 Optical Sensor 2000 Series Equipped with a field-exchangeable optical block and has full certification, this optical sensor provides good looks as well as top features Specifications Operating voltage 17 - 28 V dc Current consumption at 24 V dc Quiescent < 150 A Alarm LED: 2 mA - 7-segment: 2 mA Alarm indication White LED (red alarm) Remote alarm output DP2051 / DT2053 - DP2061 / DT2063 4 mA DP2071 / DT2073 4 mA Humidity 0 - 95% non condensing Operating temperature -10°C - 70°C IP rating IP43 Dimensions Height 5 cm Diameter 10 cm Ordering Information DP2051 Optical Sensor DB2001 2000 series base, 2 terminals DB2016 Isolating base E E E E E E E E E E E E Remote test capabilities Remote signalling capabilities Optical sensor with field exchangeable optical chamber Easy numeric addressing (1-128) Enhanced communication protocol Full diagnostic self testing Polarity insensitive Full range: optical and heat Full range of I/0 units and accessories Isolator base EN54 approved VdS approved Addressable Fire Systems Page : 41 DP2061 Optical Sensor with remote LED output The DP2061 is equipped with a field-exchangeable optical block and has full certification. This optical sensor combines good looks with alarm and fault LEDs as well as a remote output. Specifications Operating voltage 17 - 28 VDC Current consumption @ 24 VDC Quiescent < 150 A Alarm 2 mA Alarm indication White LED (Red alarm) Remote alarm output 4 mA Humidity 0 - 95% non condensing Operating temperature -10 to +70°C IP rating IP43 Dimensions Height 5 cm Diameter 10 cm Ordering Information DP2061 Optical Sensor with remote LED output DB2002 2000 series base, 4 terminals DB2002U Standard Base 15 cm, 4 Terminals DB2016 Isolating base E E E E E E E E E E E E Remote test capabilities Remote signalling capabilities Optical sensor with field exchangeable optical chamber Easy numeric addressing (1-128) Enhanced communication protocol Full diagnostic self testing Polarity insensitive Full range of detectors available Full range of I/0 units and accessories Isolator base EN54 approved VdS approved Addressable Fire Systems Page : 42 DP2061T Optical and heat multi-sensor with remote LED output The DP2061T multi-sensor combines the smoke sensitivity of an optical smoke detector with the enhancement of heat sensing. Being able to operate in five modes, the DP2061T multi sensor can operate as an optical smoke sensor enhanced by heat detection (with two different smoke sensitivities), as a dual smoke and heat detector, each sensor operating independently, an optical sensor only, or a heat detector only. Specifications Operating voltage 17 to 28 VDC Current consumption @ 24 VDC Quiescent < 150 uA Alarm 2 mA Alarm indication White LED (Red alarm) Remote alarm output 4mA Humidity 0 - 95% non condensing Operating temperature -10°C to 70°C IP rating IP43 Dimensions Height 5 cm Diameter 10 cm E Optical smoke and heat detection E Five modes of operation: multisensor (2 sensitivities) , dual sensor, or independant smoke and heat Ordering Information DP2061T Optical and heat multi-sensor with remote LED output DB2001 DB2002 DB2002U DB2004 DB2016 2000 series base, 2 terminals 2000 series base, 4 terminals Standard Base 15 cm, 4 Terminals 2000 series deep base, 4 terminals Isolating base AI672 AI673 Optical Remote Indicator Optical and Accustical Remote Indicator E E E E E E E E E E E Independant control of detector modes Optical sensor with field exchangeable optical chamber Easy numeric addressing (1-128) Enhanced communication protocol Full diagnostic self testing Remote test capabilities Remote signalling capabilities Polarity insensitive Full range of sensors: optical and heat Full range of I/0 units, MCPs and accessories Isolator base option Addressable Fire Systems Page : 43 DP2071 Optical Sensor with 7-segment display 2000 Series Equipped with a field-exchangeable optical block and with full certification, this optical sensor provides good looks as well as top features. Fitted with an exclusive 7-segment display, the sensor provides comprehensive information. In addition to alarm signalling, information such as Fault, Pre-alarm, Maintenance Alarm (Clean me), Disabled Sensor, Sensor in Test, Error (double address, wrong sensor type) and Sensor Polled is provided. Specifications Operating voltage 17 - 28 V dc Current consumption at 24 V dc Quiescent < 150 A Alarm LED: 2 mA - 7-segment: 2 mA Alarm indication White LED (red alarm) Remote alarm output 4 mA DP2051 / DT2053 - DP2061 / DT2063 4 mA DP2071 / DT2073 4 mA Humidity 0 - 95% non condensing Operating temperature -10°C - 70°C IP rating IP43 Dimensions Height 5 cm Diameter 10 cm Ordering Information DP2071 DB2002 DB2002U DB2016 Optical Sensor with 7-segment display 2000 series base, 4 terminals Standard Base 15 cm, 4 Terminals Isolating base E E E E E E E E E E 7-segment display Remote test capabilities Remote signalling capabilities Optical sensor with field exchangeable optical chamber Easy numeric addressing (1-128) Enhanced communication protocol Full diagnostic self testing Polarity insensitive Full range: optical and heat Full range of I/0 units and accessories Addressable Fire Systems Page : 44 DT2053 2000 Series heat sensor 2000 series Fully certified, this heat sensor provides good looks as well as top features. Specifications Operating voltage 17 - 28 V dc Current consumption at 24 V dc Quiescent < 150 A Alarm LED: 2 mA - 7-segment: 2 mA Alarm indication Red LED Remote alarm output DP2051 / DT2053 - DP2061 / DT2063 4 mA DP2071 / DT2073 4 mA Humidity 0 - 95% non condensing Operating temperature -10°C - 70°C IP rating IP43 Dimensions Height 5 cm Diameter 10 cm Ordering Information DT2053 2000 Series heat sensor DB2001 2000 series base, 2 terminals DB2016 Isolating base E Remote test capabilities E Remote signalling capabilities E Optical sensor with field exchangeable optical chamber E Available in one LED, two LED and seven segment display E E E E E E E E E Easy numeric addressing (1-128) Enhanced communication protocol Full diagnostic self testing Polarity insensitive Full range: optical and heat Full range of I/0 units and accessories Isolator base EN54 approved VdS approved Addressable Fire Systems Page : 45 DT2063 2000 series heat sensor with remote LED output 2000 Series Fully certified, this heat sensor provides good looks as well as top features. Dual LED's indicate both alarm and fault. A remote output is also provided. Specifications Operating voltage 17 - 28 VDC Current consumption @ 24 VDC Quiescent < 150 A Alarm LED: 2 mA - 7-segment: 2 mA Alarm indication Red LED Remote alarm output 4 mA Humidity 0 - 95% non condensing Operating temperature -10 to +70°C IP rating IP43 Dimensions Height 5 cm Diameter 10 cm Ordering Information DT2063 2000 series heat sensor with remote LED output DB2002 2000 series base, 4 terminals DB2002U Standard Base 15 cm, 4 Terminals DB2016 Isolating base E Remote test capabilities E Remote signalling capabilities E Optical sensor with field exchangeable optical chamber E Available in one LED, two LED and seven segment display E E E E E E E E E Easy numeric addressing (1-128) Enhanced communication protocol Full diagnostic self testing Polarity insensitive Full range: optical and heat Full range of I/0 units and accessories Isolator base EN54 approved VdS approved Addressable Fire Systems Page : 46 DT2073 Heat Sensor with 7-segment Display and Remote LED Output 2000 Series Fitted with an exclusive 7-segment display, this detector provides comprehensive, on the spot information. In addition to alarm signalling, information such as Fault, Pre-alarm, Maintenance Alarm (Clean me), Disabled Sensor, Sensor in Test, Error (double address, wrong sensor type) and Sensor Polled is provided. Specifications Operating voltage 17 - 28 V dc Current consumption at 24 V dc Quiescent < 150 A Alarm LED: 2 mA - 7-segment: 2 mA Alarm indication Red LED Remote alarm output DP2051 / DT2053 - DP2061 / DT2063 4 mA DP2071 / DT2073 4 mA Humidity 0 - 95% non condensing Operating temperature -10°C - 70°C IP rating IP43 Dimensions Height 5 cm Diameter 10 cm Ordering Information E Remote test capabilities E Remote signalling capabilities E Optical sensor with field exchangeable optical chamber E Available in one LED, two LED and seven segment display DT2073 DB2002 DB2002U DB2016 Heat Sensor with 7-segment Display and Remote LED Output 2000 series base, 4 terminals Standard Base 15 cm, 4 Terminals Isolating base E E E E E E E E E Easy numeric addressing (1-128) Enhanced communication protocol Full diagnostic self testing Polarity insensitive Full range: optical and heat Full range of I/0 units and accessories Isolator base EN54 approved VdS approved Addressable Fire Systems Page : 47 DB2001 2000 series base, 2 terminals 2000 series 2 terminal base for DP2051 and DT2053 Ordering Information DB2001 2000 series base, 2 terminals E Remote test capabilities E Remote signalling capabilities E Optical sensor with field exchangeable optical chamber E Available in one LED, two LED and seven segment display E E E E E E E E E Easy numeric addressing (1-128) Enhanced communication protocol Full diagnostic self testing Polarity insensitive Full range: optical and heat Full range of I/0 units and accessories Isolator base EN54 approved VdS approved Addressable Fire Systems Page : 48 DB2002 2000 series base, 4 terminals 2000 series A four terminal base for all 2000 series detectors Ordering Information DB2002 2000 series base, 4 terminals DB2002U Standard Base 15 cm, 4 Terminals E Remote test capabilities E Remote signalling capabilities E Optical sensor with field exchangeable optical chamber E Available in one LED, two LED and seven segment display E E E E E E E E E Easy numeric addressing (1-128) Enhanced communication protocol Full diagnostic self testing Polarity insensitive Full range: optical and heat Full range of I/0 units and accessories Isolator base EN54 approved VdS approved Addressable Fire Systems Page : 49 DB2016 Isolating base The DB2016 isolator base senses and isolates short circuit faults. A yellow LED indicates a short circuit condition. The detector in the base will still receive power in the event of a single short circuit. If every detector is fitted with an isolator base then no device will be lost in the event of a single short circuit. Ordering Information DB2016 Isolating base E Remote test capabilities E Remote signalling capabilities E Optical sensor with field exchangeable optical chamber E Available in one LED, two LED and seven segment display E E E E E E E E E Easy numeric addressing (1-128) Enhanced communication protocol Full diagnostic self testing Polarity insensitive Full range: optical and heat Full range of I/0 units and accessories Isolator base EN54 approved VdS approved Addressable Fire Systems Page : 50 IU2016 Loop Isolator 2000 series The Aritech Loop Isolator is designed to prevent an entire communication loop from being disabled in the event of a short circuit. The IU 2016 isolates that part of the loop containing the short from the remainder of the circuit. Specifications Operating voltage 17 - 28 V, comm. loop terminals Total standby current < 250 A Isolated current Average < 1.6 mA Transition pulse < 36 mA (5 ms duration) Operating temperature -10º C to 70º C Operating humidity range 0 - 95%; Non-condensing Line resistance Normal 0.55 Ohms Isolated > 33K Ohms Switching voltage Normal to isolated 13.8 V dc Isolated to normal 2.5 V dc Switching time Normal to isolated < 5 ms Isolated to normal < 0.5 ms (after fault correction) Ordering Information IU2016 Loop Isolator DB2003 Base for the IU2016 isolator E Complete isolation of loop short circuit E Automatic restore when fault is corrected E Module LED indicates location of fault Addressable Fire Systems Page : 51 Base for the IU2016 isolator Ordering Information DB2003 Base for the IU2016 isolator DB2003 Addressable Fire Systems Page : 52 DM2000 Manual call point, flying leads 2000 series The DM 2000 is a break glass design call point with a high strength plastic housing. The LED indicator provides visual confirmation of alarm initiation. The test key (included with each unit) facilitates functional testing of the call point. Specifications Operating voltage 17 - 28 V, @ comm.loop terminals Voltage modulation 4 - 9 V dc Standby current < 250 A LED indicator current 2.5 mA maximum Operating temperature -10º C to 70º C Operating humidity 0 - 95%; Non-condensing Dimensions (L x W x H) Flush mount 87 x 87 x 24 mm Surface mount 87 x 87 x 56 mm Ordering Information DM2000 DM2000Y DM2000B DM711 DM715 Manual call point, flying leads Manual call point flying leads - Yellow Manual call point flying leads - Blue Break glass, EN54, Aritech logo EN54 universal glass for manual call point E E E E E E Analogue addressable manual call point LED alarm indicator Tamper resistant break glass design Easy to test with self reset Fast response IP67 waterproof model available Addressable Fire Systems Page : 53 DM2000E Manual call point - Red IP67 waterproof, including backbox 2000 series The DM 2000E is a break glass design call point with a high strength plastic housing and IP67 waterproof. The LED indicator provides visual confirmation of alarm initiation. The test key (included with each unit) facilitates functional testing of the call point. Specifications Operating voltage 17 - 28 V, @ comm.loop terminals Voltage modulation 4 - 9 V dc Standby current < 250 A LED indicator current 2.5 mA maximum Operating temperature -10º C to 70º C Operating humidity 0 - 95%; Non-condensing Dimensions (L x W x H) Flush mount 87 x 87 x 24 mm Surface mount 87 x 87 x 56 mm Ordering Information DM2000E Manual call point - Red IP67 waterproof, including backbox DM711 Break glass, EN54, Aritech logo DM715 EN54 universal glass for manual call point E E E E E E Analogue addressable manual call point LED alarm indicator Tamper resistant break glass design Easy to test with self reset Fast response IP67 waterproof model available Addressable Fire Systems Page : 54 IO2014 Input Output unit - 4 inputs The 2000 Series loop powered Input/Output modules are designed to provide unlimited applications to input monitoring and output switching. These modules, combined with the powerful features of the 2000/1200 Series fire panels gives the user total versatility. The IO2014 is a unit that provides 4 inputs with selectable line supervision. Specifications Operating voltage 17 - 39 VDC Total standby current < 420 A Typical standby current < 350 A Operating temperature -10°C to +70°C Operating humidity range 0 - 95%, Non-condensing Outputs NA Inputs 4 Supervision Selectable 33 k resistor in series with switch Normal, Active, Open, Short No resistor in series with switch Open, Short EOL resistor 150 k , ¼ W, 5% E Wide range of I/O Modules : 2 input-1 output / 2 input-2 output / 4 input / 4 input - 4 output Ordering Information IO2014 Input Output unit - 4 inputs E E E E E E E Versatile input structure Supervised inputs Normally Open/Normally Closed operation Magnetic latched output relays Loop powered No external power required Easy numeric addressing Addressable Fire Systems Page : 55 IU2050 Single Input Module 2000 series The Aritech Analogue Addressable Single Input Module is designed for use with the FP 2000 Fire Panel to monitor normally open or normally closed contacts. It can typically be connected to conventional Manual Call Points, Pull Stations or Door Monitors and will report actuation within 1 second depending on the programming of the fire panel. Specifications Operating voltage 17 - 28 V, @ comm. loop terminals Voltage modulation 4-9 V dc Standby current < 250 A Operating temperature -20° C to 70° C Operating humidity 0 - 95%; Non-condensing EOL resistor 150 K, 1/4 W, 5% Ordering Information IU2050 Single Input Module E Analogue Addressable Single Input Module E Loop Powered E Supervised Input Addressable Fire Systems Page : 56 IU2055 Conventional Zone Monitor The IU2055 two-wire zone monitor is designed to provide an interface between conventional smoke detectors and the addressable series 2000/1200 fire panels. The IU2055 enables the adressable panel to monitor the presence and operation of up to 30 conventional detectors in standard operation mode, or up to 20 intrinsically safe series 870 conventional detectors in intrinscally safe configurations. Specifications Operating voltage At loop terminals 18 - 39 VDC At zone output terminals 14 - 18.5 VDC Operating current Standby < 15 mA Alarm < 35 mA Remote LED 4.5 mA Maximum zone load current 3.5 mA Maximum zone capacitance <1 F Maximum zone resistance < 30 Ohm Operating temperature -10° C to +70° C Operating humidity range 0 - 95%; Non-condensing End of line resistance 4.3 k Ohm, ¼ W, 5 % Zone impedances @ 24 V Short circuit < 30 Ohms Fire 180 - 300 Ohms Quiescent 2.7 - 4.3 K Ohms Open > 15 K Ohms E E E E E Monitors up to 30 conventional smoke detectors Zone supervised for open and short circuits Supports alarm verification and reset functions Loop powered Easy numeric addressing E Supports intrinsically safe applications for up to 20 Ordering Information IU2055 Conventional Zone Monitor series 870 detectors Addressable Fire Systems Page : 57 GBX2000 Galvanic barrier 2000 series A Galvanic barrier used with IU2055 zone monitor unit in intrinsic safe applications Ordering Information GBX2000 Galvanic barrier E Approved with the IU2055 zone monitor unit E Intrinsic safe operation when correctly installed IU2080 Indicating Circuit Controller 2000 series The Aritech Indicating Circuit Controller is designed for efficient, addressable control of sounders, bells and strobes in a fire detection system. The 3 A of output power available from the IU 2080 assures meeting all requirements for signaling devices on a fire alarm system. Specifications Operating voltage 17-28 V, at comm. loop terminals Total standby current <350 A, <200 A typical Maximum alarm current <3.5 mA at comm. loop Operating temperature -10º C to 70º C Operating humidity range 0 - 95%; Non-condensing Circuit impedance at 24 V Short circuit <3.3 K Quiescent 3.3 K - 13 K Open circuit <13 K Power supply low voltage detection 24 V; <20.4 V Standby current <11 mA @ 24 V dc Alarm current Supervisory voltage <72 mA @ 24 V dc (plus output circuit load current from ext. power supply) 2.2 V dc, inverted Circuit voltage in alarm 24 V dc Alarm current (fuse rating) 3A End of line resistor value 10 K, 1/4W, 5% Ordering Information IU2080 Indicating Circuit Controller E Versatile, addressable control for sounders, bells and strobes E Supervised output circuit E Programmable output E 24 V external power supply Addressable Fire Systems Page : 58 FD2705R 2000 series addressable reflective beam detector 5 - 50m 2000 series The FD 2705R and FD 2710R provides an integral, loop powered analogue addressable reflective beam detector up to 100m distance. It operates with 2000 series protocol with the FP1200 / 2000 Fire panels Specifications Supply voltage 17 - 30 V dc Range FD 2705R 5 - 50 m FD 2710R 50 - 100 m Lateral detection 7.5 m Current consumption Quiescent 5 mA Alarm 9 mA Fault 5 mA Optical wave length 880 nm Operating temperature -30°C to 55°C Size 210 x 130 x 120 mm IP rating IP50 Construction Flame retardent ABS Colour Gray-black Ordering Information FD2705R 2000 series addressable reflective beam detector 5 - 50m FD2710R 2000 series addressable reflective beam detector 50 - 100m E E E E E E E E E E E E E E Loop Powered 2000 series protocol Area coverage up to 600 m 2 per unit Range from 5 - 50 m and 50 - 100 m Up to ceiling heights of 25 m Low current consumption 3 selectable alarm thresholds Self check and automatic contamination compensation Automatic discrimination between fire and fault Retro operation through prism Vertical or horizontal mount Easy wiring and unique alignment Microprocessor controlled Conforms to BS 5839 part 5 and EN54 Warning Device Page : 59 AS2015 2000 series loop powered sounder 2000 series The AS2015 is a 2000 series addressable loop powered sounder for the FP1200 and FP2000 range of fire panels. The unit has a built in isolator and can be synchronized. Specifications Operating voltage 17-39 VDC Supply current not activated 240 A activated 3mA Sound output @ 1 meter 100 dB(A) Continuous tone 990 Hz Intermittent tone 990 Hz, On Off @ 1 Hz Two tone 990 Hz / 650 Hz @ 1 Hz Ordering Information AS2015 2000 series loop powered sounder AS2015W 2000 series loop powered sounder - white E E E E E E Loop powered Low current High output Built in isolators 3 tones FP1200 / 2000 fire panel operation Addressable Fire Systems Page : 60 DI950 Analogue addressable ionisation sensor 950 series This elegant slim-line ionisation sensor provides high-performance smoke detection Specifications Supply voltage (V dc) 17-28 Quiescent current 280 A Alarm indication Red LED Alarm LED current 2 mA Normal operating temperature (no icing) -20º to +60º C Rel. humidity (no condensation) 0-95 % Max. wind (continuous) 10 m/s Size of device in base (H x Ø mm) 50 x 100 Ordering Information DI950 Analogue addressable ionisation sensor E E E E Passive base address Programmable slide-in address card Aesthetic design EN 54,BOSEC,VdS,CNBOP approved DP951 Optical sensor 950 series This elegant slim-line optical sensor provides high performance analogue addressable features Specifications Supply voltage (V dc) 17-28 Quiescent current 340 A Alarm indication Clear LED (red in alarm) Alarm LED current 4 mA Normal operating temperature (no icing) -20º to +60º C Rel. humidity (no condensation) 0-95 % Max. wind (continuous) Not affected Size of device in base (H x Ø mm) 50 x 100 Ordering Information DP951 Optical sensor DB950 950 series standard base E E E E Passive base address Programmable slide-in address card Aesthetic design EN 54,BOSEC,VdS,CNBOP approved Addressable Fire Systems Page : 61 DT952 Analogue addressable temperature sensor 950 series This elegant slim-line analogue addressable heat sensor provides exact temperature information to the fire panel. Specifications Supply voltage (V dc) 17-28 Quiescent current 250 A Alarm indication Red LED Alarm LED current 2 mA Normal operating temperature (no icing) -20º to +60º C Rel. humidity (no condensation) 0-95 % Max. wind (continuous) Not affected in fixed temp. use Size of device in base (H x Ø mm) 50 x 100 Ordering Information DT952 Analogue addressable temperature sensor DB950 950 series standard base E E E E 950 series analogue addressable manual callpoint 950 series A manual call point operating with 950 series protocol. Ordering Information DM960 950 series analogue addressable manual callpoint Passive base address Programmable slide-in address card Aesthetic design EN 54,BOSEC,VdS,CNBOP approved DM960 Addressable Fire Systems Page : 62 DI970 Intrinsic safe analogue addressable ionisation detector 970 series An intrinsic safe ionisation detector, when used with the PT971/2 protocol simulator and GBX70 barrier Ordering Information DI970 PT971 PT972 GBX70 DB970 Intrinsic safe analogue addressable ionisation detector Intrinsic safe protocol translator Dual channel IS protocol translator Galvanic barrier (single channel) Detector base for 970 series intrinsic safe sensors E E E E Passive base address Programmable slide-in address card Aesthetic design EN 54,BOSEC,VdS,CNBOP approved DP971 Intrinsic safe optical detector 970 series An intrinsic safe optical detector, when used with the PT971/2 protocol translator and GBX70 barrier Ordering Information DP971 PT971 PT972 GBX70 DB970 Intrisic safe optical detector Intrinsic safe protocol translator Dual channel IS protocol translator Galvanic barrier (single channel) Detector base for 970 series intrinsic safe sensors E E E E Passive base address Programmable slide-in address card Aesthetic design EN 54,BOSEC,VdS,CNBOP approved Addressable Fire Systems Page : 63 DT972 Intrinsic safe heat detector 970 series An intrinsic safe heat detector, when used with the PT971/2 protocol translator and GBX70 barrier Ordering Information DT972 PT971 PT972 GBX70 DB970 Intrinsic safe heat detector Intrinsic safe protocol translator Dual channel IS protocol translator Galvanic barrier (single channel) Detector base for 970 series intrinsic safe sensors E E E E Intrinsic safe manual call point 970 series An intrinsic safe manual call point, when used with the PT971/2 protocol translator and GBX70 barrier. Ordering Information DM970 Intrinsic safe manual call point Passive base address Programmable slide-in address card Aesthetic design EN 54,BOSEC,VdS,CNBOP approved DM970 Addressable Fire Systems Page : 64 Intrinsic safe protocol translator PT971 970 series A protocol translator for the 970 series analogue addressable intrinsic safe sensors. This must be used with the GBX70 barrier Ordering Information PT971 Intrinsic safe protocol translator PT972 Dual channel IS protocol translator Galvanic barrier (single channel) 970 seris A galvanic barrier used in 970 series intrinsic safe applications. The GBX70 is used in conjuntion with the PT971 and PT972 protocol translators. Ordering Information GBX70 Galvanic barrier (single channel) GBX70 Addressable Fire Systems Page : 65 II950 950 series mini switch monitor unit 950 series This unit is designed to monitor the state of one or more single pole switches connected on a single pair of cables. Specifications Supply voltage 14-28 Vdc Current consumption Quiescent (20kOhm) 1 mA Alarm - Led /relay on 3.5 mA Switch on surge 3 mA Switch monitoring 9-11 Vdc Relay contact rating - Operating temperature -20/+70°C Relative humidity 0-95% Ingress protection IP54 Ordering Information II950 II950I 950 series mini switch monitor unit E Loop powered E Full line: Switch monitors, Zone monitors, Input/output unit, Output unit, Sounder circuit controller E LEDs for signalling of I/O and fault condition E Aesthetically pleasing II952 950 series switch monitor unit - surface mount 950 series This unit is designed to monitor the state of one or more single pole switches connected on a single pair of cables. The circuit will report open and short-circuit faults. Specifications Supply voltage 14-28 Vdc Current consumption Quiescent (20kOhm) 730 A Alarm Led /relay on 5.6 mA Switch on surge 2.5 mA Switch monitoring 9-11 Vdc Relay contact rating - Operating temperature -20/+70°C Relative humidity 0-95% Ingress protection IP54 Ordering Information II952 950 series switch monitor unit - surface mount II953 Switch monitor unit plus - surface mount E Loop powered E Full line: Switch monitors, Zone monitors, Input/output unit, Output unit, Sounder circuit controller E LEDs for signalling of I/O and fault condition E Aesthetically pleasing Addressable Fire Systems Page : 66 II955 950 series zone monitor unit - surface mount 950 series The zone monitor powers and controls the operation of a zone of conventional detectors. Specifications Supply voltage 14-28 Vdc Current consumption Quiescent (20kOhm) 4 mA Alarm 11-19 mA Led /relay on - Switch on surge 2.8 mA Switch monitoring - Relay contact rating - Operating temperature -20/+70°C Relative humidity 0-95% Ingress protection IP54 Ordering Information II955 950 series zone monitor unit - surface mount E Loop powered E Full line: Switch monitors, Zone monitors, Input/output unit, Output unit, Sounder circuit controller E LEDs for signalling of I/O and fault condition E Aesthetically pleasing IO950 950 series single channel IO - surface mount 950 series This unit provides a loop-powered relay output, a monitored input and an un-monitored opto-coupled input. It can report fault, switch open and switch closed condition. It uses the standard housing. Specifications Supply voltage 14-28 Vdc Current consumption Quiescent (20kOhm) 1.2 mA Alarm - Led /relay on 6 mA Switch on surge 3.5 mA Switch monitoring 9-11 Vdc Relay contact rating 1A@30 Vac/dc Operating temperature -20/+70°C Relative humidity 0-95% Ingress protection IP54 Ordering Information IO950 950 series single channel IO - surface mount E Loop powered E Full line: Switch monitors, Zone monitors, Input/output unit, Output unit, Sounder circuit controller E LEDs for signalling of I/O and fault condition E Aesthetically pleasing Addressable Fire Systems Page : 67 IO955 950 series output unit - surface mount 950 series This unit provides a loop-powered relay output Specifications Supply voltage 14-28 Vdc Current consumption Quiescent (20kOhm) 720 A Alarm - Led /relay on 3.3 mA Switch on surge 3 mA Switch monitoring - Relay contact rating 1A@30 Vac/dc Operating temperature -20/+70°C Relative humidity 0-95% Ingress protection IP54 Ordering Information IO955 950 series output unit - surface mount E Loop powered E Full line: Switch monitors, Zone monitors, Input/output unit, Output unit, Sounder circuit controller E LEDs for signalling of I/O and fault condition E Aesthetically pleasing IO956 950 series sounder circuit controller - surface mount 950 series This unit is designed to control a zone of sounders powered by an external DC supply. Specifications Supply voltage 14-28 Vdc Current consumption Quiescent (20kOhm) 1.9 mA Alarm - Led /relay on 1.7 mA Switch on surge 2.6 mA Switch monitoring 9-11 Vdc Relay contact rating - Operating temperature -20/+70°C Relative humidity 0-95% Ingress protection IP54 Ordering Information E Loop powered E Full line: Switch monitors, Zone monitors, Input/output unit, Output unit, Sounder circuit controller IO956 950 series sounder circuit controller - surface mount E LEDs for signalling of I/O and fault condition E Aesthetically pleasing Addressable Fire Systems Page : 68 950 series loop isolator Ordering Information IU950 950 series loop isolator IU950 Addressable Fire Systems Page : 69 AS950 950 series loop powered sounder 950 Series Designed to operate with the 950 series analogue sensors and monitors, the AS950 loop sounders are addressed and utilise the same protocol using a very low current. Specifications Supply voltage 14 - 28 V dc Current consumption Quiescent 140 A at 24 V dc Switch on surge 1.24 mA for 3 sec. Operated at 85 dBA 3 mA +/- 0.25 mA Operated at 92 dBA 8 mA +/- 0.25 mA Drive frequency 500 - 550 Hz (continuous mode) Ingress protection IP43 Operating temperature -20 to 60 °C Dimension (dia. x depth) 115 x 25 mm (sounder only) Weight 115 x 33 mm (sounder with cap) 140 g (sounder only) 145 g (sounder with cap) Ordering Information AS950 950 series loop powered sounder AS950I Loop powered sounder, for use with isolator base AS950W Loop powered sounder, white cap E E E E E E Loop powered Low current consumption Aritech 950 and Apollo protocol compatible Continuous or pulsed tone Sound output 85 - 92 dBA at 1 metre Reduces wiring and installation cost Addressable Fire Systems Page : 70 AS955 950 series high output loop powered sounder 950 Series Designed to operate with the 950 series analogue sensors and monitors, the AS955 high output loop sounders are addressed and utilise the same protocol using a very low current. Specifications Supply voltage 14 - 28 V dc Current consumption Quiescent 140 A at 24 V dc Switch on surge 1.24 mA for 3 sec. Operated 4.5 mA +/- 0.25 mA Drive frequency 500 - 550 Hz (continuous mode) Ingress protection IP43 Operating temperature -20 to 60 °C Sound output 100 dB(A) Ordering Information AS955 950 series high output loop powered sounder E E E E E E Loop powered Low current consumption 950 series protocol Continuous or pulsed tone Sound output 100 dB(A) at 1 metre Reduces wiring and installation cost Addressable Fire Systems Page : 71 FD950 950 series loop-powered beam detector 950 Series A 950 series loop-powered beam detector with a range of up to 100m long and 15m wide. Ordering Information FD950 950 series loop-powered beam detector E E E E E E E Loop-powered 950 series compatible with FP1200 and FP2000 Four selectable alarm levels Drift compensation Remote interface Simple wiring Simple alignment Addressable Fire Systems Page : 72 DB950 950 series standard base 950 series A unique, patented addressing method provides simple, user-friendly and accurate identification of monitor location whereby a coded card, inserted in the base, is read by any monitor as it is plugged in. Ordering Information DB950 950 series standard base E E E E Passive base address Programmable slide-in address card Aesthetic design EN 54,BOSEC,VdS,CNBOP approved DB951 Base for IU 950 950 series This base is required for the IU950 isolator Ordering Information DB951 Base for IU 950 E E E E Passive base address Programmable slide-in address card Aesthetic design EN 54,BOSEC,VdS,CNBOP approved Addressable Fire Systems Page : 73 DB961 Isolating base (20 devices) The isolating base senses and isolates short circuit faults on 950 series loops and spurs. Up to 20 devices may be placed between any two isolator bases. Ordering Information DB961 Isolating base (20 devices) E E E E Passive base address Programmable slide-in address card Aesthetic design EN 54,BOSEC,VdS,CNBOP approved DB970 Detector base for 970 series intrinsic safe sensors Ordering Information DB970 Detector base for 970 series intrinsic safe sensors E E E E Passive base address Programmable slide-in address card Aesthetic design EN 54,BOSEC,VdS,CNBOP approved Addressable Fire Systems Page : 74 Coded cards, addresses 1 - 18 950 series Precoded Xpert address cards for use in DB9xx bases Ordering Information IU980 IU981 IU982 IU983 IU984 IU985 IU986 Coded cards, addresses 1 - 18 Coded cards, addresses 19 - 36 Coded cards addresses 37 - 54 Coded cards, addresses 55 - 72 Coded cards, addresses 73 - 90 Coded cards, addresses 91- 108 Coded cards, addresses 109 - 126 IU980 Conventional Fire Systems Page : 75 FP202 Conventional fire alarm panel with 2 zones The FP200 Series microprocessor controlled, conventional fire panels incorporate state of the art technology, reliability, ease of installation and maintenance in a basic package. They are compatible with conventional detectors such as the Aritech Series 300, Series 650 and Series 700 devices. The FP202 has 2 conventional zones. Specifications Supply Voltage 125/230 VAC @ 50/60 Hz Mains fuse (Type 5x20 mm) 0.5/0.25 A Total consumption < 20 W Nominal Output Voltage 24 VDC Batteries Recommended batteries 2 off 1.9 Ah, 12 V Fuse Rating 1A Maximum load current < 100 mA Zone Maximum Load 72 mA Maximum number of detectors 20 Ouput voltage 22 to 28 VDC End-of-line resitance 4k7 Ohm Manual call point resistance 100 Ohm, 2 W Outputs Fire alarm 24 VDC ± 15%, 300 mA Fault alarm (Fail-to-safe) 24 VDC ± 15%, 100 mA Environmental Working temperature +5 to +40°C Storage temperature -10 to +70°C Relative humidity 95 % (non-condencing) Physical Characteristics Size (w x h x d) 305 x 295 x 100 mm Weight without batteries 3 kg Ordering Information FP202 Conventional fire alarm panel with 2 zones E E E E E Modern, elegant design Compact models for 2, 4 and 6 zones Microprocessor controlled Multilingual keyboard 2 Access levels E Differentiation between alarms from manual call points and automatic detectors in the same zone E Acoustic indications for fire and fault E Optical indications for fire and fault by zone E Low maintenance E Compatible with all ranges of ARITECH conventional detectors Conventional Fire Systems Page : 76 FP204 Conventional fire alarm panel with 4 zones The FP200 Series microprocessor controlled, conventional fire panels incorporate state of the art technology, reliability, ease of installation and maintenance in a basic package. They are compatible with conventional detectors such as the Aritech Series 300, Series 650 and Series 700 devices. The FP204 has 4 conventional zones. Specifications Supply Voltage 125/230 VAC @ 50/60 Hz Mains fuse (Type 5x20 mm) 0.5/0.25 A Total consumption < 20 W Nominal Output Voltage 24 VDC Batteries Recommended batteries 2 off 1.9 Ah, 12 V Fuse Rating 1A Maximum load current < 100 mA Zone Maximum Load 72 mA Maximum number of detectors 20 Ouput voltage 22 to 28 VDC End-of-line resitance 4k7 Ohm Manual call point resistance 100 Ohm, 2 W Outputs Fire alarm 24 VDC ± 15%, 300 mA Fault alarm (Fail-to-safe) 24 VDC ± 15%, 100 mA Environmental Working temperature +5 to +40°C Storage temperature -10 to +70°C Relative humidity 95 % (non-condencing) Physical Characteristics Size (w x h x d) 305 x 295 x 100 mm Weight without batteries 3 kg Ordering Information FP204 Conventional fire alarm panel with 4 zones E E E E E Modern, elegant design Compact models for 2, 4 and 6 zones Microprocessor controlled Multilingual keyboard 2 Access levels E Differentiation between alarms from manual call points and automatic detectors in the same zone E Acoustic indications for fire and fault E Optical indications for fire and fault by zone E Low maintenance E Compatible with all ranges of ARITECH conventional detectors Conventional Fire Systems Page : 77 FP206 Conventional fire alarm panel with 6 zones The FP200 Series microprocessor controlled, conventional fire panels incorporate state of the art technology, reliability, ease of installation and maintenance in a basic package. They are compatible with conventional detectors such as the Aritech Series 300, Series 650 and Series 700 devices. The FP206 has 6 conventional zones. Specifications Supply Voltage 125/230 VAC @ 50/60 Hz Mains fuse (Type 5x20 mm) 0.5/0.25 A Total consumption < 20 W Nominal Output Voltage 24 VDC Batteries Recommended batteries 2 off 1.9 Ah, 12 V Fuse Rating 1A Maximum load current < 100 mA Zone Maximum Load 72 mA Maximum number of detectors 20 Ouput voltage 22 to 28 VDC End-of-line resitance 4k7 Ohm Manual call point resistance 100 Ohm, 2 W Outputs Fire alarm 24 VDC ± 15%, 300 mA Fault alarm (Fail-to-safe) 24 VDC ± 15%, 100 mA Environmental Working temperature +5 to +40°C Storage temperature -10 to +70°C Relative humidity 95 % (non-condencing) Physical Characteristics Size (w x h x d) 305 x 295 x 100 mm Weight without batteries 3 kg Ordering Information FP206 Conventional fire alarm panel with 6 zones E E E E E Modern, elegant design Compact models for 2, 4 and 6 zones Microprocessor controlled Multilingual keyboard 2 Access levels E Differentiation between alarms from manual call points and automatic detectors in the same zone E Acoustic indications for fire and fault E Optical indications for fire and fault by zone E Low maintenance E Compatible with all ranges of ARITECH conventional detectors Conventional Fire Systems Page : 78 FP402 Conventional fire alarm panel with 2 zones The FP400 series of conventional fire alarm and extinguishing control panels is the ideal solution for small to medium-sized installations. Very powerful and cost-effective, they are extremely simple to install and use due to their ergonomic, advanced design. The panels come in elegant, high-quality, conveniently sized, heavy-duty metal enclosures with space for batteries and finished in high-gloss paint. All panels have a high-quality keyboard with audible metallic click and good travel Specifications Supply Voltage (+10% - 15%) 230 / 110 VAC @ 50 / 60 Hz Current Consumption (panel only) Quiescent 75 mA Alarm 162 mA Batteries Capacity 2 x 2.3 Ah Fuse rating 2A Zone Nominal Voltage 24 VDC Maximum load 94 mA Max. number of detectors per 20 zone Maximum zone resistance 44 ohm Sounders Maximum load 250 mA Delay Selectable 0 - 9 min Relay Outputs (excluding sounders) 1 A @ 30 VDC Auxilliary Output 250 mA 24 VDC Resetable Output Maximum load 100 mA Reset time 3s Environment Working temperature -5°C to +40°C Relative humidity (non condencing) 95 % IP rating IP30 Physical Characteristics Size (mm) 297 (w) x 307 (h) x 105 (d) Weight (without batteries) 3.6 kg Expansion Module Slots 1 Ordering Information FP402 Conventional fire alarm panel with 2 zones RB404 SB404 Relay module, 4 potential free relays for NK700/Fx400 fire panels Relay module, 4 supervised relays for NK700/Fx400 fire panels EOL-ACT Active end-of-line device for use with FP400/KL700 fire panels BS122N Sealed Lead-Acid Battery - 12V 2.2Ah E E E E E E E E E E E E Modern, attractive design Microprocessor controlled From 2 up to 16 zones EN54 compliant with approvals pending 2 Access levels 2 Monitored sounder outputs One-man test capability 24 Volt resetable output External 'class change' facility Alarm output with potential free relay General fault output with potential free relay External watchdog Conventional Fire Systems Page : 79 FP408 Conventional fire alarm panel with 8 zones The FP400 series of conventional fire alarm and extinguishing control panels is the ideal solution for small to medium-sized installations. Very powerful and cost-effective, they are extremely simple to install and use due to their ergonomic, advanced design. The panels come in elegant, high-quality, conveniently sized, heavy-duty metal enclosures with space for batteries and finished in high-gloss paint. All panels have a high-quality keyboard with audible metallic click and good travel Specifications Supply Voltage (+10% - 15%) 230 / 110 VAC @ 50 / 60 Hz Current Consumption (panel only) Quiescent 137 mA Alarm 247 mA Batteries Capacity 2 x 7.5 Ah Fuse rating 5A Zone Nominal Voltage 24 VDC Maximum load 94 mA Max. number of detectors per 20 zone Maximum zone resistance 44 ohm Sounders Maximum load 250 mA Delay Selectable 0 - 9 min Relay Outputs (excluding sounders) 1 A @ 30 VDC Auxilliary Output 250 mA 24 VDC Resetable Output Maximum load 100 mA Reset time 3s Environment Working temperature -5°C to +40°C Relative humidity (non condencing) 95 % IP rating IP30 Physical Characteristics Size (mm) 420 (w) x 335 (h) x 110 (d) Weight (without batteries) 6.2 kg Expansion Module Slots 4 Ordering Information FP408 Conventional fire alarm panel with 8 zones RB404 SB404 Relay module, 4 potential free relays for NK700/Fx400 fire panels Relay module, 4 supervised relays for NK700/Fx400 fire panels EOL-ACT Active end-of-line device for use with FP400/KL700 fire panels BS127N Sealed Lead-Acid Battery - 12V 7.2Ah E E E E E E E E E E E E Modern, attractive design Microprocessor controlled From 2 up to 16 zones EN54 compliant with approvals pending 2 Access levels 2 Monitored sounder outputs One-man test capability 24 Volt resetable output External 'class change' facility Alarm output with potential free relay General fault output with potential free relay External watchdog Conventional Fire Systems Page : 80 FP412 Conventional fire alarm panel with 12 zones The FP400 series of conventional fire alarm and extinguishing control panels is the ideal solution for small to medium-sized installations. Very powerful and cost-effective, they are extremely simple to install and use due to their ergonomic, advanced design. The panels come in elegant, high-quality, conveniently sized, heavy-duty metal enclosures with space for batteries and finished in high-gloss paint. All panels have a high-quality keyboard with audible metallic click and good travel Specifications Supply Voltage (+10% - 15%) 230 / 110 VAC @ 50 / 60 Hz Current Consumption (panel only) Quiescent 137 mA Alarm 247 mA Batteries Capacity 2 x 7.5 Ah Fuse rating 5A Zone Nominal Voltage 24 VDC Maximum load 94 mA Max. number of detectors per 20 zone Maximum zone resistance 44 ohm Sounders Maximum load 250 mA Delay Selectable 0 - 9 min Relay Outputs (excluding sounders) 1 A @ 30 VDC Auxilliary Output 250 mA 24 VDC Resetable Output Maximum load 100 mA Reset time 3s Environment Working temperature -5°C to +40°C Relative humidity (non condencing) 95 % IP rating IP30 Physical Characteristics Size (mm) 420 (w) x 335 (h) x 110 (d) Weight (without batteries) 6.2 kg Expansion Module Slots 4 Ordering Information FP412 Conventional fire alarm panel with 12 zones E E E E E E E E E E E E Modern, attractive design Microprocessor controlled From 2 up to 16 zones EN54 compliant with approvals pending 2 Access levels 2 Monitored sounder outputs One-man test capability 24 Volt resetable output External 'class change' facility Alarm output with potential free relay General fault output with potential free relay External watchdog Conventional Fire Systems Page : 81 FP416 Conventional fire alarm panel with 16 zones The FP400 series of conventional fire alarm and extinguishing control panels is the ideal solution for small to medium-sized installations. Very powerful and cost-effective, they are extremely simple to install and use due to their ergonomic, advanced design. The panels come in elegant, high-quality, conveniently sized, heavy-duty metal enclosures with space for batteries and finished in high-gloss paint. All panels have a high-quality keyboard with audible metallic click and good travel Specifications Supply Voltage (+10% - 15%) 230 / 110 VAC @ 50 / 60 Hz Current Consumption (panel only) Quiescent 137 mA Alarm 247 mA Batteries Capacity 2 x 7.5 Ah Fuse rating 5A Zone Nominal Voltage 24 VDC Maximum load 94 mA Max. number of detectors per 20 zone Maximum zone resistance 44 ohm Sounders Maximum load 250 mA Delay Selectable 0 - 9 min Relay Outputs (excluding sounders) 1 A @ 30 VDC Auxilliary Output 250 mA 24 VDC Resetable Output Maximum load 100 mA Reset time 3s Environment Working temperature -5°C to +40°C Relative humidity (non condencing) 95 % IP rating IP30 Physical Characteristics Size (mm) 420 (w) x 335 (h) x 110 (d) Weight (without batteries) 6.2 kg Expansion Module Slots 4 Ordering Information FP416 Conventional fire alarm panel with 16 zones E E E E E E E E E E E E Modern, attractive design Microprocessor controlled From 2 up to 16 zones EN54 compliant with approvals pending 2 Access levels 2 Monitored sounder outputs One-man test capability 24 Volt resetable output External 'class change' facility Alarm output with potential free relay General fault output with potential free relay External watchdog Conventional Fire Systems Page : 82 RB404 Relay module, 4 potential free relays for NK700/Fx400 fire panels The RB404 relay expander module provides 4 additional voltage free relays on the GE Security NK700/FP400/FEC400 conventional fire panels ranges. It allows for these relays to be allocated to individual detection zones, or for programming the activation of different relays depending on the status of one or more zones. Up to 4 of these modules may be used on every fire panel. Specifications Relay rating Voltage 250 VAC / 30 VDC Current 10 A Delay setting 0 to 9 minutes Ordering Information RB404 Relay module, 4 potential free relays for NK700/Fx400 fire panels E 4 Potential free relays E Up to 4 modules may be housed inside the fire panel cabinet E Programmable with basic boolen functions E Power supplied from fire panel bus E Output delay setting per relay Conventional Fire Systems Page : 83 SB404 Relay module, 4 supervised relays for NK700/Fx400 fire panels The SB404 expander module provides 4 additional supervised relays that provide 24 VDC outputs on the GE Security NK700/FP400/FEC400 conventional fire panels ranges. These relays may be configured to power sounders or as standard 24 VDC supervised outputs for other devices. Relays may be allocated to individual detection zones, or for programming the activation of different relays depending on the status of one or more zones. Up to 4 of these modules may be used on every fire panel. Specifications Auxiliary supply 24 VDC Relay Rating Voltage 250 VAC / 30 VDC Current 5A Delay setting 0 to 9 minutes Ordering Information SB404 Relay module, 4 supervised relays for NK700/Fx400 fire panels E 4 Supervised relays E Up to 4 modules may be housed inside the fire panel cabinet E Programmable with basic boolen functions E Output delay setting per relay E Configurable for sounder control or as supervised outputs Conventional Fire Systems Page : 84 FEC403 Conventional extinguishing control panel with 3 zones The FP400 series of conventional fire alarm and extinguishing control panels is the ideal solution for small to medium-sized installations. Very powerful and cost-effective, they are extremely simple to install and use due to their ergonomic, advanced design. The panels come in elegant, high-quality, conveniently sized, heavy-duty metal enclosures with space for batteries and finished in high-gloss paint. All panels have a high-quality keyboard with audible metallic click and good travel Specifications Supply Voltage (+10% - 15%) 230 / 110 VAC @ 50 / 60 Hz Batteries Capacity 2 x 7 Ah Fuse rating 2A Zone Maximum load 94 mA Max. number of detectors per 20 zone Maximum zone resistance 44 ohm Sounders Maximum load 250 mA Delay Selectable 0 - 9 min Relay Outputs (excluding sounders) 1 A @ 30 VDC Extinguishing Relay Outputs Maximum load 350 mA Fuse rating 1A Auxilliary Output 250 mA 24 VDC Resetable Output Maximum Load 100 mA Reset time 3s Environment Working temperature -5°C to +40°C Relative humidity (non condencing) 95 % IP rating IP30 Physical Characteristics Size (mm) 420 (w) x 335 (h) x 110 (d) Weight (without batteries) 6.2 kg Ordering Information FEC403 Conventional extinguishing control panel with 3 zones E E E E E E E E E E E E E Modern, attractive design Microprocessor controlled 3 zone (1 ext. area) and 6 zone (2 ext. areas) available Automatic extinguishing agent release control 2 Access levels Supervised general sounder output Supervised extinguishing inputs and outputs One-man test capability 24 Volt resetable output External 'class change' facility Alarm output with potential free relay General fault output with potential free relay External watchdog Conventional Fire Systems Page : 85 FEC406 Conventional extinguishing control panel with 6 zones The FP400 series of conventional fire alarm and extinguishing control panels is the ideal solution for small to medium-sized installations. Very powerful and cost-effective, they are extremely simple to install and use due to their ergonomic, advanced design. The panels come in elegant, high-quality, conveniently sized, heavy-duty metal enclosures with space for batteries and finished in high-gloss paint. All panels have a high-quality keyboard with audible metallic click and good travel Specifications Supply Voltage (+10% - 15%) 230 / 110 VAC @ 50 / 60 Hz Batteries Capacity 2 x 7 Ah Fuse rating 2A Zone Maximum load 94 mA Max. number of detectors per 20 zone Maximum zone resistance 44 ohm Sounders Maximum load 250 mA Delay Selectable 0 - 9 min Relay Outputs (excluding sounders) 1 A @ 30 VDC Extinguishing Relay Outputs Maximum load 350 mA Fuse rating 1A Auxilliary Output 250 mA 24 VDC Resetable Output Maximum Load 100 mA Reset time 3s Environment Working temperature -5°C to +40°C Relative humidity (non condencing) 95 % IP rating IP30 Physical Characteristics Size (mm) 420 (w) x 335 (h) x 110 (d) Weight (without batteries) 6.2 kg Ordering Information FEC406 Conventional extinguishing control panel with 6 zones E E E E E E E E E E E E E Modern, attractive design Microprocessor controlled 3 zone (1 ext. area) and 6 zone (2 ext. areas) available Automatic extinguishing agent release control 2 Access levels Supervised general sounder output Supervised extinguishing inputs and outputs One-man test capability 24 Volt resetable output External 'class change' facility Alarm output with potential free relay General fault output with potential free relay External watchdog Conventional Fire Systems Page : 86 FP604 4-zone Conventional Fire Panel The FP 604 fire panel is designed using the latest technologies and is compatible with most brands of conventional fire detectors. The FP 604 is a 4-zone panel which is extendable up to 6 zones. Specifications Supply voltage 230 V (± 10% - 50 Hz ± 5%) Total current 12 V dc (no charge), 80 mA quiescent Total current 24 V dc (no charge), 90 mA quiescent Auxiliary output 100 mA - 12 V dc Battery back-up for 72 hrs 1 x 12 V - 7.2 Ah battery Battery charger fuse 2A Battery charger voltage 13.8 V Bells - Fire Brigade fuse 315 mA Dimensions 390 x 315 x 85 mm Ordering Information FP604 4-zone Conventional Fire Panel ZI602 Two zone extension board, including 6 outputs RC606 Set of 6 bi-stable magnetic latch relays E E E E E E E E E E E E E E One man maintenance Alarm verification Individual zone alarm outputs One 12 V back-up battery 12 V dc auxiliary output 4 - 6 zones Mixed zone capability Head removal option Sirens output 12 or 24 V dc Microprocessor based EN 54 p2/4 approved LPCB certified Optional third source Optional digital dialler Conventional Fire Systems Page : 87 Two zone extension board, including 6 outputs ZI602 This board extends the FP604 from 4 zones to 6 zones. It also provides 6 outputs for the 6 zones. Ordering Information ZI602 Two zone extension board, including 6 outputs Set of 6 bi-stable magnetic latch relays A set of 6 relays for the ZI602 zone extension board Ordering Information RC606 Set of 6 bi-stable magnetic latch relays RC606 Conventional Fire Systems Page : 88 FP708 Fire panel equipped with 8 zones FP700 series A set of four conventional fire panels. The FP708 and FP708C are 8 zone non-expandable fire panels. The FP740 and FP740C are 8 zone expandable to 40 zones. The FP708C and FP740C have an alarm counter. All panels can use the full range of LON700 output boards. Specifications Dimensions (W x H x D) 444 x 340 x110 mm Weight (no batteries) 5.5 kg Supply voltage (see engineering 230 V ac; 1,5 A; 50 Hz guide) Quiescent current @20 devices/zone 210 mA (8 zones) Batteries for 24 hrs (in housing) 7.2 Ah Batteries for 72 hrs 17 Ah Battery charger rating 1.4 A max Nominal battery charger voltage 27,6 V @ 25°C Auxiliary output 1 21 - 29,4 V dc; 1.2 A max. Auxiliary output 2 11.5 - 12.5 V dc; 0.4 A max. Total 24 V output (no charging) 3,5 A max Sounder/warning 0,5 A, 19-31 V dc, polarity reversal Evacuation/Fire brigade 0,5 A, 19-31 V dc, polarity reversal Fault and Fire protection relay rating 2 A, @ 42 V RS 232 port 19200 baud, DB9, 1 start, 8 data, 1 stop, no parity Ordering Information FP708 FP708C FP740 FP740C Fire panel equipped with 8 zones Fire panel equipped with 8 zones including alarm counter Fire panel equipped with 8 zones expandable up to 40 zones Fire panel equipped with 8 zones exp. to 40 including alarm counter E E E E E E E E E E E Fully modular LON based network One-man maintenance Alarm verification 700 series detectors Clean Me® detection Various output boards EN54 approved and BOSEC certified Modular up to 40 zones Full line of repeaters Microprocessor based Local and remote control Conventional Fire Systems Page : 89 FR708 Repeater 8 zones, 24 VDC input FR700 series The repeaters provide different solutions - 24 volt input and 230 volt input using the PS700 power supply. The FR708 is 8 zones non expandable and the FR740 is 8 zones expandable to 40 zones. The FR700 repeaters connect to the FP700 fire panel with the LON 700 bus. The FR708V230 and FR740V230 include a card cage for LON board expansion and have a PS700 power supply. Ordering Information FR708 FR708V230 FR740 FR740V230 Repeater 8 zones, 24 VDC input Repeater 8 zones with card cage and PS700 PSU (230V input) Repeater 8 zones, expandable up to 40 zones, 24 VDC input Repeater 8 zones, exp to 40 zones with card cage and PS700 PSU (230V) E E E E E E E Fully modular Echelon based network Various output boards Modular up to 40 zones Full line of repeaters Microprocessor based Local and remote control Conventional Fire Systems Page : 90 8 zone indicator LED extension board fire/fault FP700 series This zone indicator extension board is used to expand the FP740 and FR740 front panel indications. Ordering Information ZE708 8 zone indicator LED extension board fire/fault ZE708 LON700 Devices Page : 91 8 zone input extension board The ZI708 is an eight zone input expansion board for LON700 compatible systems. It allows for the connection of up to 8 conventional fire detector zones and is compatible with most industry standard conventional detectors. Ordering Information ZI708 8 zone input extension board ZI708 Conventional Fire Systems Page : 92 Synoptic driver for 80 LEDs and common signals LON 700 series A LON700 output board to display LED's. It can be self-standing as well as plugging into a card cage. Specifications Dimensions mm (L x W x D) 150x30x60 Weight 200 g Operating temp °C -5°C - +40 Operating voltage Vdc 19 - 30 Current consumption max quiesent mA 30 power consumption per LED 40 (mW) Bus Connection FP1200/FP2000 (with LON2000) *** FP700 (direct connection) *** Bus Cable Cat 5 Total number of repeaters FP1200/FP2000 15 FP700 8 Ordering Information FM740 Synoptic driver for 80 LEDs and common signals FM740 LON700 Devices Page : 93 LON700 output board with 24 open collector outputs OCB724 The OCB724 is a 24 way open collector board used in a LON700 system. Ordering Information OCB724 LON700 output board with 24 open collector outputs LON700 output board with 8 relays The RB708 is an eight way relay board used in LON700 systems. Specifications Number of outputs 8 Relay contact rating Switching current 2A Switching volage 42V ac/dc Switching power 60W Ordering Information RB708 LON700 output board with 8 relays RB708 LON700 Devices Page : 94 LON700 output board with 8 supervised outputs The SOB708 provides eight supervised outputs that can be used in LON700 systems. Specifications Number of outputs 8 Output type polarity reversal End of line resistor 5.6 Kohm Output current per output 500mA Total current for all outputs 2A Open circuit >27 Kohm Normal 1.2 - 18 Kohm Short circuit < 470 ohm Ordering Information SOB708 LON700 output board with 8 supervised outputs SOB708 Conventional Fire Systems Page : 95 FB708 FP700 black box with 7 slot card cage LON700 series The FB708 and FB740 'black boxes' allow for the distribution of LON700 input / output units. When used with the NC700 or FM740, the FB7xx is connected to the FP700 / FP2000 firepanels with the LON700 bus. Ordering Information FB708 FP700 black box with 7 slot card cage FB740 FP700 black box with 11 slot card cage and PS700 NC700 LON700 interface board E E E E E E E Fully modular Echelon based network Various output boards Microprocessor based Local and remote control For fire panel distributed systems 7 slot card cage or 11 slot card cage with power supply LON700 Devices Page : 96 LON700 interface board NC700 The NC700 is an interface board to connect a LON700 bus from a fire panel to a FB7xx 'black box'. Ordering Information NC700 LON700 interface board Plug-in power supply 3.5 A The PS700 power supply can be used to extend the power output in LON700 systems. Ordering Information PS700 Plug-in power supply 3.5 A PS700 Addressable Fire Systems Page : 97 FP1501 Analogue addressable fire detection panel - 1 loop The FP1501 1 loop analogue addressable fire alarm control panel is the ideal solution for small to medium-sized installations. Very powerful and cost-effective, it is extremely simple to install and use due to is ergonomic, advanced design. The panel is supplied in an elegant, high-quality, conveniently sized, heavy-duty enclosure. It has a high-quality keyboard with audible metallic click and good travel. Specifications Supply Voltage 110 VAC @ 50 Hz or 230 VAC @ 50 Hz (+10% -15%) Current Consumption 175 mA Quiescent / 241 mA in alarm with no devices connected Batteries Capacity 2 x 12 V - 7 AH (SLA type) Fuse Rating 3A Charger Rating 350 mA @ 27.6 VDC @ 20 °C (Temperature compensated -3 V / °C) Loop characteristics per loop Capacity 250 addresses per loop Maximum Load 400 mA / 26 VDC to 32 VDC Maximum Electrical Characteristics 44 Ohm / 500 nF approximately 2 km of 1.5 mm2 diameter cable Sounders (reverse polarity supervision) Maximum Load Delays Relay Outputs (potential free) 250 mA each (2 Sounder outputs available) / 18 VDC to 24 VDC 10 seconds to 600 seconds, software adjustable in 10 second intervals 1 A @ 30 VDC 24 V Auxiliary Output Maximum Load 250 mA @ 18 VDC to 28 VDC Environment Working Temperature -5°C to +40 °C Relative Humidity 0-95% non-condensing IP Rating IP30 Physical Characteristics Size 420 mm (w) x 335 (h) x 110 (d) Weight 6.2 kg without batteries / 10.7 kg with 2 x 7 Ah batteries Ordering Information FP1501 Analogue addressable fire detection panel - 1 loop E E E E E E E E E E E E E E E E E One and two loop control panels 4 x 40 characters LCD display 20 Display zones EN54 approved 2 User access levels 2 Monitored sounder outputs 2 Programmable voltage free relays 24 Volt auxiliary output I/O programming capabilities with Boolean functions Day/night sensitivity settings Coincidence within zones Installation test capability Full networking capabilities up to 10 nodes 2-wire RS485 communications network Industry standard RS232 communications port Easy up/download programming from a standard PC Graphic PC software Addressable Fire Systems Page : 98 FP1502 Analogue addressable fire detection panel - 2 loops The FP1500 series analogue addressable fire alarm control panels is the ideal solution for small to medium-sized installations. Very powerful and cost-effective, they are extremely simple to install and use due to their ergonomic, advanced design. The panels are supplied in an elegant, high-quality, conveniently sized, heavy-duty metal enclosure and are finished in a high-gloss paint. All panels have a high-quality keyboard with audible metallic click and good travel. The batteries for the system may be housed inside the cabinet. Specifications Supply Voltage 110 VAC @ 50 Hz or 230 VAC @ 50 Hz (+10% -15%) Current Consumption 175 mA Quiescent / 241 mA in alarm with no devices connected Batteries Capacity 2 x 12 V - 7 AH (SLA type) Fuse Rating 3A Charger Rating 350 mA @ 27.6 VDC @ 20 °C (Temperature compensated -3 V / °C) Loop characteristics per loop Capacity 250 addresses per loop Maximum Load 400 mA / 26 VDC to 32 VDC Maximum Electrical Characteristics 44 Ohm / 500 nF approximately 2 km of 1.5 mm2 diameter cable Sounders (reverse polarity supervision) Maximum Load Delays Relay Outputs (potential free) 250 mA each (2 Sounder outputs available) / 18 VDC to 24 VDC 10 seconds to 600 seconds, software adjustable in 10 second intervals 1 A @ 30 VDC 24 V Auxiliary Output Maximum Load 250 mA @ 18 VDC to 28 VDC Environment Working Temperature -5°C to +40 °C Relative Humidity 0-95% non-condensing IP Rating IP30 Physical Characteristics Size 420 mm (w) x 335 (h) x 110 (d) Weight 6.2 kg without batteries / 10.7 kg with 2 x 7 Ah batteries Ordering Information FP1502 Analogue addressable fire detection panel - 2 loops E E E E E E E E E E E E E E E E E One and two loop control panels 4 x 40 characters LCD display 20 Display zones EN54 approved 2 User access levels 2 Monitored sounder outputs 2 Programmable voltage free relays 24 Volt auxiliary output I/O programming capabilities with Boolean functions Day/night sensitivity settings Coincidence within zones Installation test capability Full networking capabilities up to 10 nodes 2-wire RS485 communications network Industry standard RS232 communications port Easy up/download programming from a standard PC Graphic PC software Addressable Fire Systems Page : 99 NC785 RS485 expansion kit for KSA701/FP1500 fire panels The NC785 RS485 expander allows for an easy upgrade to the KSA701/FP1500 series addressable fire panels. Each module adds an additional industry standard RS485 communication port to the panel. This port could be used for communications with other network nodes in the fire panel network. Specifications Number of ports 1 Communications medium RS485 Technical specifications Maximum cable length 1200 m Communication speed 9600 baud Cable CAT5 - twisted with screen Termination resistance 150 Ohm Ordering Information NC785 RS485 expansion kit for KSA701/FP1500 fire panels E Industry standard RS485 communications E No hardware configuration required Addressable Fire Systems Page : 100 FR1500 Analogue addressable LCD Repeater/Emulator (AC Powered) The FP1500 Series analogue addressable fire alarm panels are the ideal solution for small to medium-sized installations. Very powerful and cost-effective, they are easy to install and use due to their ergonomic, advanced design. The FR1500 LCD repeater is supplied in the same enclosure as the FP1500. Specifications Supply Voltage AC Version 110 VAC @ 50 Hz or 230 VAC @ 50 Hz (+10% -15%) DC Version 24 VDC Current Consumption 175 mA Quiescent / 200 mA in alarm Battery Charger (AC Version only) Capacity 2 x 12 V - 7 AH (SLA type) Fuse Rating 3A Charger Rating 350 mA @ 27.6 VDC @ 20 °C (Temperature compensated -3 V / °C) Environment Working Temperature -5°C to +40 °C Relative Humidity 0-95% non-condensing IP Rating IP30 Physical Characteristics Size 420 mm (w) x 335 (h) x 110 (d) Weight 6.2 kg without batteries / 10.7 kg with 2 x 7 Ah batteries RS232 and RS485 standard Communication Ports Ordering Information FR1500 Analogue addressable LCD Repeater/Emulator (AC Powered) E E E E E E E E Modern, attractive design 4 x 40 characters LCD display 20 Display zones EN54 compliant with approvals pending 3 User access levels 24 VDC or 230 VAC models available Panel networking Full system control Addressable Fire Systems Page : 101 MODGSM GSM Modem for KSA700/FP1500 Series Fire Panels The MODGSM modem may be used in KSA701/FP1500, KSA702 and KSA705 fire panel from GE-Interlogix. It is ideal for use as a standard modem for making and receiving calls from and to the fire panel, but may also be used for GSM messaging. Specifications GSM Band 900/1800 MHz Services Data, SMS, Voice and Fax AT Commands GSM 07.07 and 07.05 Output Power (max) GSM900 2W GSM1800 1W Input Voltage 5 to 32 V Current @ 5V Avarage 330 mA Peak 1.8 A SIM Interface 3V / 5V Dimensions (h x w x d) 98 x 54 x 25 mm Weight 130 g Environmental Temperature Storage - 25 °C to + 70 °C Operating - 20 °C to + 55 °C Ordering Information MODGSM GSM Modem for KSA700/FP1500 Series Fire Panels E E E E Dual-Band 900/1800 MHz Data and SMS services Remote control by AT commands Wide input voltage range Addressable Fire Systems Page : 102 Graphic Software for KSA700/FP1500 Fire Systems (1 panel-2 loops) PCG-Graphic102 The PCG-Config series consists of 3 software applications. The individual software formats allows the graphic package to grow with the installation. PCG-Config102 operates with a single panel and allows for the configuration of all devices up to a maximum of two loops. Specifications Hardware requirements Communication RS232, modem and/or TCP/IP Display SVGA or higher resolution Hard disk 2 Gb with 650 Mb free space Keyboard Required Pointing device Required Printer System printer required for printing Processor 1 GHz or higher Pentium III-compatible CPU RAM 256 Mb or more Removable media 1.44 Mb stiffy and CD-ROM or DVD drive Software requirements Operating system Windows '98 or Windows 2000 Ordering Information E Bi-directional communication with single panels and networked fire systems PCG-Graphic102 Graphic Software for KSA700/FP1500 Fire Systems (1 panel-2 loops) E E E E E E E E E Local or remote connection via modem or TCP/IP Large selection of user configurable icons Visualises device alarms and status of in- and outputs Event texts retrieval from the panel Configurator and operator contol levels Navigation buttons allowed Event logs with reporting facilities Basic drawing package included Imports bmp & drw format graphics Addressable Fire Systems Page : 103 PCG-GraphicNW Graphic Software for KSA700/FP1500 Fire Systems (multi-panel) The PCG-Config series consists of 3 software applications. The individual software formats allows the graphic package to grow with the installation. PCG-ConfigNW allows for monitoring on networked systems with multiple panels. Specifications Hardware requirements Communication RS232, modem and/or TCP/IP Display SVGA or higher resolution Hard disk 2 Gb with 650 Mb free space Keyboard Required Pointing device Required Printer System printer required for printing Processor 1 GHz or higher Pentium III-compatible CPU RAM 256 Mb or more Removable media 1.44 Mb stiffy and CD-ROM or DVD drive Software requirements Operating system Windows '98 or Windows 2000 Ordering Information E Bi-directional communication with single panels and networked fire systems PCG-GraphicNW Graphic Software for KSA700/FP1500 Fire Systems (multi-panel) E E E E E E E E E Local or remote connection via modem or TCP/IP Large selection of user configurable icons Visualises device alarms and status of in- and outputs Event texts retrieval from the panel Configurator and operator contol levels Navigation buttons allowed Event logs with reporting facilities Basic drawing package included Imports bmp & drw format graphics Addressable Fire Systems Page : 104 FP1216EN Analogue addressable fire panel 2 - 4 loops, 16 zones The FP1216EN is a versatile, cost effective analogue addressable fire panel with 2 to 4 loops and powerfull I/O features. It supports all the LON700 devices and repeaters, and can be optionally upgraded to provide full networking. The FP1216EN is truly user friendly and provides a generous 8 x 40 graphic, backlit display. I/O control is done via the powerful FP2000/FP1200 series boolean I/O programing module. Extensive maintenance features are provided standard. The FP1216EN supports both 2000 and 900 series sensors and I/O units. Specifications Supply voltage 230 V ac (+10/-15%) Min. supply current @ 24 VDC 50 Hz 220 VA 0.2 A Battery charger rating @ 27.6 VDC 1.6 A Total supply rating @ 27.6 VDC 4A Relay rating @ 24 VDC 2A Weight (no batteries) 7.5 kg Dimensions (h x w x d) 440 x 444 x 125 mm Ordering Information FP1216EN Analogue addressable fire panel 2 - 4 loops, 16 zones FR2000 LCD repeater with emulator functions FP-RIM1270 LC2002 LON2000 MOD2000 NC2011 NC2051 NE2011 NE2051 Rim surround for the 780 and 1200N series fire panel boxes 2-loop extension board for FP1200 / FP2000 fire panels LON700 driver for FP1200 / FP2000 Modem kit ARCNET RS485 network card with single RS485 interface ARCNET network card with single optical interface board RS485 network extension board Fibre optic network extension board PCG-N PCG-S PCC2000 PCM2000 Graphics package network application with copy protection key Graphics package with copy protection key Programming and configuration software Maintenance and support software with copy protection key E E E E E E E One man maintenance Soak test On-line diagnostics and statistics Power supply for 72 hour autonomy Floating background for 2000 series sensors Coincidence within and in between zones Start-up default mode E Upload/download, remote maintenance and graphic PC software E E E E E I/O programming including Boolean functions EN 54 p2 & 4 approved Bosec certified 2 or 4 class A loops Full range of LON700 devices Addressable Fire Systems Page : 105 FP2416 Analogue addressable fire panel 2 - 4 loops, 16 zones FP2000 Series A versatile, powerful analogue addressable fire panel, 2 to 4 loops, 16 displayed zones with extensive I/O features. The fire panel can operate within a 31 panel network and can communicate with global repeaters and PC grahics. It also supports all the LON700 devices and repeaters using a seperate two wire bus. The FP2000 series is truly user-friendly, and provides a generous 8 x 40 backlit graphic display. I/O control is done via the powerful FP2000/FP1200 series boolean I/O programing module. Extensive maintenance features are provided standard. The FP2000 series supports both 2000 and 900 series sensors and I/O units. Specifications Supply voltage 1 190 - 270 V ac Supply voltage 2 40- 60 Hz 160 VA max. 21 - 27 V dc Current consumption Quiescent @ 24 V dc (equipped loop) 500 mA Alarm current @ 24 V dc 600 mA Available auxiliary current in alarm 3.4 A Battery charger rating @ 27.5 V dc 3A Total supply rating @ 27.5 V dc 4A Relay rating @ 24 V dc 2A Weight (no batteries) 11 kg Dimensions (mm) (H x W x D) 609 x 441 x 109 Ordering Information FP2416 FR2000 LC2002 NC2011 NC2051 NE2011 NE2051 LON2000 LON700 FRL700 MOD2000 PCM2000 PCC2000 PCG Series PR2000 Analogue addressable fire panel 2 - 4 loops, 16 zones LCD repeater with emulator functions 2-loop extension board for FP1200 / FP2000 fire panels ARCNET RS485 network card with single RS485 interface ARCNET network card with single optical interface board RS485 network extension board Fibre optic network extension board LON700 driver for FP1200 / FP2000 2 wire repeaters LCD repeater Modem kit Maintenance and support software with copy protection key Programming and configuration software PC Graphic Software Packages for Aritech Fire Sytems Internal printer E E E E E E E E E E E E One man maintenance Graphic maintenance Maintenance warning Service reminder signal Soak test On-line diagnostics and statistics Floating background Day/night sensitivity setting Coincidence within and in between zones Automatic timed and manual on/off zones Start-up default mode Service switch E Upload/download, remote maintenance and graphic PC software E E E E E E I/O programming including Boolean functions ARCNET panel networking EN54 approved, certified Bosec, VdS, NFA2P Networkable "black box" and "global zone" system Full range of repeater panels Full range of LON700 devices Addressable Fire Systems Page : 106 FP2432 Analogue addressable fire panel 2 - 4 loops, 16 - 32 zones FP2000 Series A versatile, powerful analogue addressable fire panel, 2 to 4 loops, 16 to 32 displayed zones with extensive I/O features. The fire panel can operate within a 31 panel network and can communicate with global repeaters and PC grahics. It also supports all the LON700 devices and repeaters using a seperate two wire bus. The FP2000 series is truly user-friendly, and provides a generous 8 x 40 backlit graphic display. I/O control is done via the powerful FP2000/FP1200 series boolean I/O programing module. Extensive maintenance features are provided standard. The FP2000 series supports both 2000 and 900 series sensors and I/O units. Specifications Supply voltage 1 190 - 270 V ac Supply voltage 2 40- 60 Hz 160 VA max. 21 - 27 V dc Current consumption Quiescent @ 24 V dc (equipped loop) 500 mA Alarm current @ 24 V dc 600 mA Available auxiliary current in alarm 3.4 A Battery charger rating @ 27.5 V dc 3A Total supply rating @ 27.5 V dc 4A Relay rating @ 24 V dc 2A Weight (no batteries) 11 kg Dimensions (mm H x W x D) 609 x 441 x 109 Ordering Information FP2432 FR2000 LC2002 ZE2016 NC2011 NC2051 NE2011 NE2051 LON2000 LON700 FRL700 MOD2000 PCM2000 PCC2000 PCG Series Analogue addressable fire panel 2 - 4 loops, 16 - 32 zones LCD repeater with emulator functions 2-loop extension board for FP1200 / FP2000 fire panels 16-zone LED extension fire and fault LED ARCNET RS485 network card with single RS485 interface ARCNET network card with single optical interface board RS485 network extension board Fibre optic network extension board LON700 driver for FP1200 / FP2000 2 wire repeaters LCD repeater Modem kit Maintenance and support software with copy protection key Programming and configuration software PC Graphic Software Packages for Aritech Fire Sytems E E E E E E E E E E E E One man maintenance Graphic maintenance Maintenance warning Service reminder signal Soak test On-line diagnostics and statistics Floating background Day/night sensitivity setting Coincidence within and in between zones Automatic timed and manual on/off zones Start-up default mode Service switch E Upload/download, remote maintenance and graphic PC software E E E E E E I/O programming including Boolean functions ARCNET panel networking EN54 approved, certified Bosec, VdS, NFA2P Networkable "black box" and "global zone" system Full range of repeater panels Full range of LON700 devices Addressable Fire Systems Page : 107 FP2864 Analogue addressable fire panel, 2 - 8 loops, 16 - 64 zones The FP2864 is a versatile, powerful analogue addressable fire panel, 2 to 8 loops, 16 to 64 displayed zones with extensive I/O features. It can operate within a 31 panel network and can communicate with global repeaters and PC grahics. It also supports all the LON700 devices and repeaters using a seperate two wire bus.The panel is truly user-friendly, and provides a generous 8 x 40 backlit graphic display. I/O control is done via the powerful 2000/1200 series boolean I/O programing module. Extensive maintenance features are provided standard. The FP2864 supports 2000, 1500 and 900 series sensors and I/O units. Specifications Supply voltage 1 190 - 270 VAC Supply voltage 2 40 - 60 Hz 160 VA max. 21 - 27 VDC Current consumption Quiescent @ 24 VDC (equipped loop) 800 mA Alarm current @ 24 VDC 1A Available auxiliary current in 3 A alarm Battery charger rating @ 27.5 VDC 3A Total supply rating @ 27.5 VDC 4A Relay rating @ 24 VDC 2A Weight (no batteries) 15 kg Dimensions (H x W x D) 804 x 441 x 109 mm Ordering Information FP2864 Analogue addressable fire panel, 2 - 8 loops, 16 - 64 zones BUS2000 ESPA2000 LC1502 LON2000 LON2000R MOD2000 NC2011 NC2051 NE2011 NE2051 PR2000 RB2016 RE2004 ZE2016 2000 Series bus termination board ESPA protocol hardware key 2-loop extension board for 1200/2000 series fire panels LON700 driver for FP1200 / FP2000 LON driver for FP1200/2000 - closed loop systems Modem kit ARCNET RS485 network card with single RS485 interface ARCNET network card with single optical interface board RS485 network extension board Fibre optic network extension board Internal printer Relay extension board for 1200/2000 series fire panels 2000 Series Memory Expansion Kit 16-zone LED extension fire and fault LED PCM2000 PCC2000 Maintenance and support software with copy protection key Programming and configuration software PCG-N PCG-S Graphics package network application with copy protection key Graphics package with copy protection key E E E E E E E E E E E E One man maintenance Graphic maintenance Maintenance warning Service reminder signal Soak test On-line diagnostics and statistics Floating background Day/night sensitivity setting Coincidence within and in between zones Automatic timed and manual on/off zones Start-up default mode Service switch E Upload/download, remote maintenance and graphic PC software E E E E E E I/O programming including Boolean functions ARCNET panel networking EN54 approved, certified Bosec, VdS, NFA2P Networkable "black box" and "global zone" system Full range of repeater panels Full range of LON700 devices Addressable Fire Systems Page : 108 FB2400 Analogue addressable fire panel 2 - 4 loops, 'black box' FP2000 series The FB2400 / FB2800 'black box' system allows a cost-effective network of fire panels to be interconnected to a global repeater using the FP2000 series arcnet network. The FB black boxes have all the features of the FP2000 series of fire panels, but have no display / keyboard. All controls and display is done via the global repeater. Specifications Supply voltage 1 190 - 270 V ac Supply voltage 2 40- 60 Hz 160 VA max. 21 - 27 V dc Current consumption Quiescent @ 24 V dc (equipped loop) 500 mA Alarm current @ 24 V dc 600 mA Available auxiliary current in alarm 3.4 A Battery charger rating @ 27.5 V dc 3A Total supply rating @ 27.5 V dc 4A Relay rating @ 24 V dc 2A Weight (no batteries) 11 kg Dimensions (mm) (H x W x D) 609 x 441 x 109 Ordering Information FB2400 Analogue addressable fire panel 2 - 4 loops, 'black box' FB2800 Analogue addressable fire panel 2 - 8 loops, 'black box' E E E E E E E E E E E E One man maintenance Graphic maintenance Maintenance warning Service reminder signal Soak test On-line diagnostics and statistics Floating background Day/night sensitivity setting Coincidence within and in between zones Automatic timed and manual on/off zones Start-up default mode Service switch E Upload/download, remote maintenance and graphic PC software E E E E I/O programming including Boolean functions ARCNET panel networking Networkable "black box" and "global zone" system Full range of repeater panels Addressable Fire Systems Page : 109 2-loop extension board for FP1200 / FP2000 fire panels LC2002 FP1200 / FP2000 series Specifications Current consumption Quiescent @ 24 V dc (Fully equipped loop) + 150 mA (252 detectors) Ordering Information LC2002 2-loop extension board for FP1200 / FP2000 fire panels 16-zone LED extension fire and fault LED The ZE2016 allows the extension of the zones of the Fx2x32 and Fx2x64 fire panels and repeaters by 16 additional zones. Ordering Information ZE2016 16-zone LED extension fire and fault LED ZE2016 Addressable Fire Systems Page : 110 LON700 driver for FP1200 / FP2000 LON2000 FP1200 / FP2000 series A LON700 driver that connects FP1200 / FP2000 fire panels to LON700 devices Ordering Information LON2000 LON700 driver for FP1200 / FP2000 ARCNET RS485 network card with single RS485 interface The NC2011 is an interface board to connect an RS485 copper network directly into the 1200/2000 series fire panels. It is supplied with one NE2011 pre installed. Ordering Information NC2011 ARCNET RS485 network card with single RS485 interface NE2011 RS485 network extension board NC2011 Addressable Fire Systems Page : 111 ARCNET network card with single optical interface board NC2051 The NC2051 is an interface board to connect a fiber optic network directly into the 1200/2000 series fire panels. It is supplied with one NE2051 pre installed. Ordering Information NC2051 ARCNET network card with single optical interface board NE2051 Fibre optic network extension board RS485 network extension board The NE2011 is a RS485 network extension board for the NC2011 to allow dual bus and closed ring networks. Ordering Information NE2011 RS485 network extension board NE2011 Addressable Fire Systems Page : 112 Fibre optic network extension board FP1200 / FP2000 series An extension board for the NC2051 to allow a fibre optic ring bus Ordering Information NE2051 Fibre optic network extension board NE2051 LON700 Devices Page : 113 FRL700 LCD repeater The LON700 LCD repeater is a smart and compact, cost-effective solution for fire panel repeaters. It is also available as an FBP700 fire brigade panel for Dutch and Scandinavian norms. Specifications Dimensions (l x w x d) 240 x 320 x 60 mm Weight 1.5 kg Operating temp °C -5°C to +40°C Operating voltage 15 - 30 VDC Current consumption Max. quiesent 100 mA Bus Connection two wire LON700 Bus Cable CAT 5 Total number of repeaters 700/1200/2000 Series 15 Ordering Information FRL700 LCD repeater E E E E E 2 wire connection between fire panel and repeaters Up to 1500 metre bus length 24 Volt power supply Cost effective repeater solutions Easily installed, simple operation E 4 x 20 charater LCD display, common LED's, push button control E LON700 module Addressable Fire Systems Page : 114 FR2000 LCD repeater with emulator functions FP1200 / FP2000 series A powerful LCD repeater that can be used as a local or global repeater on a FP1200 / FP2000 fire panel network. Fire panels can be emulated from the FR2000. An 80 x 40 backlit graphic display and full indication and control keyboard is provided standard. Specifications Supply voltage 230 V ac (+10/-15%) Min. supply current @ 24 V dc 50 Hz 50 VA 0.15 A Battery charger rating @ 27.6 V dc 0.3 A Total supply rating @ 27.6 V dc 1A Relay rating @ 24 V dc 2A Weight (no batteries) 7.5 kg Dimensions (mm H x W x D) 365 x 444 x 111 Ordering Information FR2000 NE2011 NE2051 FP-RIM1270 LCD repeater with emulator functions RS485 network extension board Fibre optic network extension board Rim surround for the 780 and 1200N series fire panel boxes E 8 x 40 character graphic display E Arcnet network connection to FP1200/FP2000 series firepanels E E E E Global repeater function Comprehensive control and display functions Fire panel emulation function Dual RS232 ports Addressable Fire Systems Page : 115 FR2032 Repeater / emulator 16 - 32 zones or panels FP1200 / FP2000 series A repeater / emulator with 16, expandable to 32, displayed fire and fault zones, used in FP1200 / FP2000 networked systems. The repeater is connected on the arcnet network and can operate in a local or global repeater mode. An 80 x 40 backlit graphic display and full indication and control keyboard is provided standard. Specifications Supply voltage 21 - 28 V dc Current consumption 300 mA max Weight 11 kg Dimensions (mm H x W x D) 609 x 441 x 109 Ordering Information FR2032 NE2011 NE2051 ZE2016 Repeater / emulator 16 - 32 zones or panels RS485 network extension board Fibre optic network extension board 16-zone LED extension fire and fault LED E 8 x 40 character graphic display E Arcnet network connection to FP1200 / FP2000 series firepanels E E E E E Global repeater function Comprehensive control and display functions 16 zones fire and fault expandable to 32 zones 24 Volt operation Emulation functions Addressable Fire Systems Page : 116 FR2064 Repeater/emulator 16 - 64 zones or panels A repeater/emulator with 16 fire and fault zones, expandable to 64, used in 1200/2000 series networked systems. The repeater is connected on the arcnet network and can operate in a local or global repeater mode. An 80 x 40 character, backlit graphic display and full indication and control keyboard is provided standard. Specifications Supply voltage 1 Supply voltage 2 160 VA max. 21 - 27 VDC Current consumption Quiescent @ 24 VDC (equipped loop) 300 mA Alarm current @ 24 VDC Available auxiliary current in alarm Battery charger rating @ 27.5 VDC Total supply rating @ 27.5 VDC Relay rating @ 24 VDC Weight (no batteries) 15 kg Dimensions (H x W x D) 804 x 441 x 109 mm Ordering Information FR2064 Repeater/emulator 16 - 64 zones or panels BUS2000 ESPA2000 LON2000 LON2000R MOD2000 NE2011 NE2051 PR2000 ZE2016 2000 Series bus termination board ESPA protocol hardware key LON700 driver for FP1200 / FP2000 LON driver for FP1200/2000 - closed loop systems Modem kit RS485 network extension board Fibre optic network extension board Internal printer 16-zone LED extension fire and fault LED E 8 x 40 character graphic display E Arcnet network connection to FP1200 / FP2000 series firepanels E E E E E Global repeater function Comprehensive control and display functions Emulation function 16 to 64 zones fire and fault displayed 24 volt operation Addressable Fire Systems Page : 117 UN2011 FP1200 / FP2000 arcnet to RS232 converter FP1200 / FP2000 series The unversal node allows the fire panel arcnet network to be extended to computer software applications either locally with the RS232 interface, or remotely using the MOD2000. It has a 230 volt power supply and battery charger self contained in the unit. Specifications Input voltage 230 V ac, 50 Hz, 10 VA Battery type 12 V 1,2 Ah Fault relay 2 A @ 24 V dc, 50 W dc Weight 5 kg Dimensions mm (H x W x D) 400 x 300 x 65 Operating remperature 0 - 40 °C Ordering Information UN2011 FP1200 / FP2000 arcnet to RS232 converter MOD2000 Modem kit E FP1200 / FP2000 arcnet to RS232 interface E Allows computer applications to operate on the fire panel network E 230V operation and battery charger E Can be extended with MOD2000 for remote operation E 'Black box' operation Addressable Fire Systems Page : 118 MOD2000 Modem kit FP1200 / FP2000 series An internal modem for the FP1200 / FP2000 fire panels or a UN2011 universal node. The modem has the autonomy of the fire panel power supply, and has extended telephone line protectection. The MOD2000 can also be used with a computer. Ordering Information MOD2000 Modem kit E E E E MOD2000 For fire panel and universal node operation Internal installation Autonomous power supply Addressable Fire Systems Page : 119 PCC2000 Programming and configuration software PCC2000 allows easy, menu driven, programming of all the panel's features and settings. Common texts can be easily copied while sensors, zones and areas increment or follow automatically. Boolean logic programming becomes simple as inputs and outputs are continuously displayed for the programmer's convenience. Specifications Processor 486 66 MHz RAM 12 Mb Display adapter VGA Hard disk space 20 MB Pointing device MS Mouse Graphical environment Windows 98, 2000, XP Communications ports 1 x RS232 1 x Parallel Ordering Information PCC2000 Programming and configuration software E Provide communication with single fire panels and networked fire systems, both locally or remote via modem E E E E Windows 98, 2000 and XP compatible For use with 2000/1200 series panels Menu driven Full or partial up- and download Addressable Fire Systems Page : 120 PCM2000 Maintenance and support software with copy protection key PCM2000 allows local and remote maintenance facilities for 1200/2000 series fire panels. Amongst others, it allows for full panel emulation, data retrieval and central alarm monitoring. Specifications Processor Pentium 133Mhz (or better) RAM 32 Mb (or more) Display Adapter VGA Hard Disk Space 20 MB Pointing Device Bus or P/S2 Mouse Graphical Environment Windows 98, NT or 2000 Communications ports Depending on Drivers Printer port (for key) 1 Parallel Ordering Information PCM2000 Maintenance and support software with copy protection key E Provide communication with single fire panels and networked fire systems, both locally or remote via modem E E E E E E E E Windows 95, 98 and NT compatible For use with FP2000, FP1200 Full panel emulation Data retrieval Central station History log Address book Dynamic Link Library (DLL) for third party integration Addressable Fire Systems Page : 121 PCG-S Graphics package with copy protection key 2 Packages allow the graphic package to grow with the installation. The basic version PCG-S operates with a single panel, while the PCG-N supports a network. Upgrades do not require rework on the existing database, drawings, etc. Specifications Item Recommended Processor Pentium II 266 MHz (or better) RAM 64 Mb (or more) Display adapter SVGA or better Hard disk space 200 MB Pointing device MS Mouse, Bus or P/S2 Graphical environment Windows NT Communication ports 1 x RS-232 - Depending on drivers 1 x Parallel - Printer port (for key) Ordering Information PCG-S Graphics package with copy protection key E Provide bi-directional communication with single fire panels and networked fire systems, both locally and remote via modem E E E E E E E E E E E E Windows 2000 and NT compatible For use with FP2000, FP1200, FP1100 and FP700 Constructed around Sybase SQL Anywhere Large selection of icons Visualises inputs & outputs Information page per point Get texts from panel Several operator levels and passwords Operator configurable Multiple navigation buttons Event logs Basic drawing package included E Imports .bmp & .wmf drawings from virtually any package E Hardware key protected Content DI322I DP331I DT313I KCT731 KZ700 KZ705 KZ705D EOL-ACT KZ705R S700 DP721I DP721T DT713-5 DT713-7 DB702 DI650 DP652 DT654 DB860 DB861 DB806 DB650 DI1552 DP1561 DP1551T DT1553 PG700 KZ705I KZ705AS KZ705IAS KAL410 KAL414C KAL426C KAL430 KAL434C KAL440 KAL450 KAL460 KAL470 KAL490 DP2051 DP2061 DP2061T DP2071 Ionisation detector, conventional Page : 3 Optical detector, conventional, with field exchangeable optical block Page : 4 Temperature detector (fixed and rate-of-rise), conventional Page : 5 Calibration Tool for KL731/DP331I Fire Detectors Page : 6 Universal fire detector base Page : 7 Universal fire detector base with earth connection Page : 8 Conventional fire detector base with diode Page : 9 Active end-of-line device for use with FP400/KL700 fire panels Page : 9 Conventional 12 VDC fire detector base with relay Page : 10 Surface mount accessory for KZ700 and KZ705 series bases Page : 11 Photoelectric smoke detector with remote alarm LED output Page : 12 Photoelectric smoke and heat detector head with remote alarm LED Page : 13 57º C fixed and rate-of-rise heat detector Page : 14 70º C fixed and R.O.R. heat detector Page : 15 10 cm diameter base - 6 terminals Page : 16 Ionisation smoke detector Page : 17 Optical smoke detector Page : 18 Heat detector, R.O.R., 57º C A1R Page : 19 Standard Base Page : 20 Backplate for Ingress Protection 860-950 Page : 20 Conduit box for 860 / 950 series bases Page : 21 650 series relay base Page : 21 Ionisation Sensor Page : 22 Optical sensor with field exchangeable optical block Page : 23 Dual Sensor (Optical/Heat) Page : 24 Heat Sensor Page : 25 Fire sensor programmer Page : 26 Analogue fire detector base with isolator Page : 27 Analogue fire detector base with sounder Page : 28 Analogue fire detector base with isolator and sounder Page : 29 Conventional Zone Monitor Unit - 1 Zone Page : 30 Conventional Zone Monitor Unit - 4 Zones Page : 31 Extinguishing Control Module Page : 32 Relay Module - 1 Relay Page : 33 Addressable Relay Module - 4 Relays Page : 34 Supervised Relay Module Page : 35 Addressable Manual Call Point Page : 36 Digital Input Module Page : 37 Isolator Module Page : 38 Retention Module - 1 Input / 1 Output Page : 39 Optical Sensor Page : 40 Optical Sensor with remote LED output Page : 41 Optical and heat multi-sensor with remote LED output Page : 42 Optical Sensor with 7-segment display Page : 43 DT2053 DT2063 DT2073 DB2001 DB2002 DB2016 IU2016 DB2003 DM2000 DM2000E IO2014 IU2050 IU2055 GBX2000 IU2080 FD2705R AS2015 DI950 DP951 DT952 DM960 DI970 DP971 DT972 DM970 PT971 GBX70 II950 II952 II955 IO950 IO955 IO956 IU950 AS950 AS955 FD950 DB950 DB951 DB961 DB970 IU980 FP202 FP204 2000 Series heat sensor Page : 44 2000 series heat sensor with remote LED output Page : 45 Heat Sensor with 7-segment Display and Remote LED Output Page : 46 2000 series base, 2 terminals Page : 47 2000 series base, 4 terminals Page : 48 Isolating base Page : 49 Loop Isolator Page : 50 Base for the IU2016 isolator Page : 51 Manual call point, flying leads Page : 52 Manual call point - Red IP67 waterproof, including backbox Page : 53 Input Output unit - 4 inputs Page : 54 Single Input Module Page : 55 Conventional Zone Monitor Page : 56 Galvanic barrier Page : 57 Indicating Circuit Controller Page : 57 2000 series addressable reflective beam detector 5 - 50m Page : 58 2000 series loop powered sounder Page : 59 Analogue addressable ionisation sensor Page : 60 Optical sensor Page : 60 Analogue addressable temperature sensor Page : 61 950 series analogue addressable manual callpoint Page : 61 Intrinsic safe analogue addressable ionisation detector Page : 62 Intrisic safe optical detector Page : 62 Intrinsic safe heat detector Page : 63 Intrinsic safe manual call point Page : 63 Intrinsic safe protocol translator Page : 64 Galvanic barrier (single channel) Page : 64 950 series mini switch monitor unit Page : 65 950 series switch monitor unit - surface mount Page : 65 950 series zone monitor unit - surface mount Page : 66 950 series single channel IO - surface mount Page : 66 950 series output unit - surface mount Page : 67 950 series sounder circuit controller - surface mount Page : 67 950 series loop isolator Page : 68 950 series loop powered sounder Page : 69 950 series high output loop powered sounder Page : 70 950 series loop-powered beam detector Page : 71 950 series standard base Page : 72 Base for IU 950 Page : 72 Isolating base (20 devices) Page : 73 Detector base for 970 series intrinsic safe sensors Page : 73 Coded cards, addresses 1 - 18 Page : 74 Conventional fire alarm panel with 2 zones Page : 75 Conventional fire alarm panel with 4 zones Page : 76 FP206 FP402 FP408 FP412 FP416 RB404 SB404 FEC403 FEC406 FP604 ZI602 RC606 FP708 FR708 ZE708 ZI708 FM740 OCB724 RB708 SOB708 FB708 NC700 PS700 FP1501 FP1502 NC785 FR1500 MODGSM PCG-Graphic102 PCG-GraphicNW FP1216EN FP2416 FP2432 FP2864 FB2400 LC2002 ZE2016 LON2000 NC2011 NC2051 NE2011 NE2051 FRL700 FR2000 Conventional fire alarm panel with 6 zones Page : 77 Conventional fire alarm panel with 2 zones Page : 78 Conventional fire alarm panel with 8 zones Page : 79 Conventional fire alarm panel with 12 zones Page : 80 Conventional fire alarm panel with 16 zones Page : 81 Relay module, 4 potential free relays for NK700/Fx400 fire panels Page : 82 Relay module, 4 supervised relays for NK700/Fx400 fire panels Page : 83 Conventional extinguishing control panel with 3 zones Page : 84 Conventional extinguishing control panel with 6 zones Page : 85 4-zone Conventional Fire Panel Page : 86 Two zone extension board, including 6 outputs Page : 87 Set of 6 bi-stable magnetic latch relays Page : 87 Fire panel equipped with 8 zones Page : 88 Repeater 8 zones, 24 VDC input Page : 89 8 zone indicator LED extension board fire/fault Page : 90 8 zone input extension board Page : 91 Synoptic driver for 80 LEDs and common signals Page : 92 LON700 output board with 24 open collector outputs Page : 93 LON700 output board with 8 relays Page : 93 LON700 output board with 8 supervised outputs Page : 94 FP700 black box with 7 slot card cage Page : 95 LON700 interface board Page : 96 Plug-in power supply 3.5 A Page : 96 Analogue addressable fire detection panel - 1 loop Page : 97 Analogue addressable fire detection panel - 2 loops Page : 98 RS485 expansion kit for KSA701/FP1500 fire panels Page : 99 Analogue addressable LCD Repeater/Emulator (AC Powered) Page : 100 GSM Modem for KSA700/FP1500 Series Fire Panels Page : 101 Graphic Software for KSA700/FP1500 Fire Systems (1 panel-2 loops) Page : 102 Graphic Software for KSA700/FP1500 Fire Systems (multi-panel) Page : 103 Analogue addressable fire panel 2 - 4 loops, 16 zones Page : 104 Analogue addressable fire panel 2 - 4 loops, 16 zones Page : 105 Analogue addressable fire panel 2 - 4 loops, 16 - 32 zones Page : 106 Analogue addressable fire panel, 2 - 8 loops, 16 - 64 zones Page : 107 Analogue addressable fire panel 2 - 4 loops, 'black box' Page : 108 2-loop extension board for FP1200 / FP2000 fire panels Page : 109 16-zone LED extension fire and fault LED Page : 109 LON700 driver for FP1200 / FP2000 Page : 110 ARCNET RS485 network card with single RS485 interface Page : 110 ARCNET network card with single optical interface board Page : 111 RS485 network extension board Page : 111 Fibre optic network extension board Page : 112 LCD repeater Page : 113 LCD repeater with emulator functions Page : 114 FR2032 FR2064 UN2011 MOD2000 PCC2000 PCM2000 PCG-S Repeater / emulator 16 - 32 zones or panels Page : 115 Repeater/emulator 16 - 64 zones or panels Page : 116 FP1200 / FP2000 arcnet to RS232 converter Page : 117 Modem kit Page : 118 Programming and configuration software Page : 119 Maintenance and support software with copy protection key Page : 120 Graphics package with copy protection key Page : 121 www.gesecurity.net IPSCAT-2005-12-6 15:44:32 As a company of innovation, GE Security reserves the right to change product specifications without notice. For the latest product specifications, visit GE Security online or contact your GE Security sales representative.