GE Security Aritech Fire Systems Products Catalogue

Transcription

GE Security Aritech Fire Systems Products Catalogue
GE
Security
Aritech Fire Systems Products Catalogue
g
In this catalogue you will find a wide range of
Fire Protection equipment from GE Security.
GE Security is a global technology leader dedicated
to supporting the needs of the rapidly growing
electronic security industry and to expanding
current technologies, products and services that
GE Security,
unrivalled expertise in
Fire Protection
create revenue growth opportunities for its
customers. As part of the GE family, GE Security
shares the spirit of innovation that has
distinguished GE for well over 100 years. GE
Security's commitment to the ongoing success of
its partners and affiliates means that we maintain
a sharp focus on product and service innovation,
world-class manufacturing practices and
operational excellence.
GE Security is a worldwide organisation with sales
and technical support operations in 27 countries,
and manufacturing and logistics operations in
Europe, the U.S. and China.
GE Security has expertise in all areas of electronic
security, including:
z
Intrusion and Fire Protection
z
Electronic Access and Facility Management
z
Key Management and Remote Access Systems
and Services
z
Fibre Optic Transmission and Reception
Equipment
z
CCTV, Digital Video and Surveillance Equipment
z
Video Multiplexing and Digital Storage
When you're looking for the finest in Fire
Protection products with leading-edge
technology and the backing of a world leader, you
need look no further than this catalogue.
Perimeter detection
Page : 3
DI322I
Ionisation detector, conventional
The 300 Series conventional fire detectors are the ideal solution for any
conventional installation. They are built specifically for use with the
Aritech FP400, FP500, FP600 and FP700 series conventional fire panels,
but can also be connected to most 3rd party industry standard
conventional control panels.
Specifications
Operating voltage
18 to 28 VDC
Current consumption
Quiescent at 24 VDC
30 A
Alarm at 24 VDC
< 100 mA
Radio-active source
Americium 241
Average activity
0.33 +/-0.04 Ci (12.1 +/- 1.5 kBq)
Remote alarm output
< 100 mA
Heat specification
Operating temperature
-10 to +60 °C
Storage temperature
-10 to +70 °C
Humidity (non-condensing)
0 - 95%
IP rating
IP43
Number of detectors per zone
20
Recommended protection
resistor
300 ohm
Head
45 mm x 99 mm
Base
24 mm x 103 mm
EN54 (BOSEC)
* Check current status with local
office
Ordering Information
DI322I
detectors
E An ultra-fine grid prevents the ingress of dust and
Dimensions (h x Ø)
Approvals*
E Full line consisting of Optical, Ionisation and Heat
Ionisation detector, conventional
KZ700
Universal fire detector base
KZ705
Universal fire detector base with earth connection
KZ705D Conventional fire detector base with diode
PA25/3L Low current remote LED indicator
insects in smoke detectors
E Attractive, low-profile design
E EN54 approved *
E Innovative base compensates for uneven surfaces
Page : 4
Optical detector, conventional, with field exchangeable optical block
DP331I
The 300 Series conventional fire detectors are the ideal solution for any
conventional installation. They are built specifically for use with the
Aritech FP400, FP500, FP600 and FP700 series conventional fire panels,
but can also be connected to most 3rd party industry standard
conventional control panels.
Specifications
Operating voltage
9 to 28 VDC
Current consumption
Quiescent at 24 VDC
85 A
Alarm at 24 VDC
< 100 mA
Radio-active source
Average activity
Remote alarm output
< 100 mA
Heat specification
Operating temperature
-10 °C to +70 °C
Storage temperature
-10 °C to +70 °C
Humidity (non-condensing)
95%
IP rating
IP43
Number of detectors per zone
20
Recommended protection
resistor
300 ohm
Head
45 mm x 99 mm
Base
24 mm x 103 mm
EN54 (BOSEC)
* Check current status with local
office
Ordering Information
DP331I
Optical detector, conventional, with field exchangeable optical block
KOB700 Replacement Optical Chamber for KL731/A & DP331I/1561 detectors
KZ700
KZ705
KZ705D
KZ705R
detectors
E An ultra-fine grid prevents the ingress of dust and
Dimensions (h x Ø)
Approvals*
E Full line consisting of Optical, Ionisation and Heat
Universal fire detector base
Universal fire detector base with earth connection
Conventional fire detector base with diode
Conventional 12 VDC fire detector base with relay
PA25/3L Low current remote LED indicator
insects in smoke detectors
E Attractive, low-profile design
E EN54 approved *
E Innovative base compensates for uneven surfaces
Conventional Fire Systems
Page : 5
DT313I
Temperature detector (fixed and rate-of-rise), conventional
The 300 Series conventional fire detectors are the ideal solution for any
conventional installation. They are built specifically for use with the
Aritech FP400, FP500, FP600 and FP700 series conventional fire panels,
but can also be connected to most 3rd party industry standard
conventional control panels.
Specifications
Operating voltage
18 to 28 VDC
Current consumption
Quiescent at 24 VDC
70 A
Alarm at 24 VDC
< 100 mA
Radio-active source
Average activity
Remote alarm output
< 100 mA
Heat specification
Max. & ROR to EN54p5
Operating temperature
-10 °C to +70 °C
Storage temperature
-10 °C to +80 °C
Humidity (non-condensing)
95%
IP rating
IP43
Number of detectors per zone
20
Recommended protection
resistor
300 ohm
Head
45 mm x 99 mm
Base
24 mm x 103 mm
EN54 (BOSEC)
* Check current status with local
office
Ordering Information
DT313I
detectors
E An ultra-fine grid prevents the ingress of dust and
Dimensions (h x Ø)
Approvals*
E Full line consisting of Optical, Ionisation and Heat
Temperature detector (fixed and rate-of-rise), conventional
KZ700
Universal fire detector base
KZ705
Universal fire detector base with earth connection
KZ705D Conventional fire detector base with diode
PA25/3L Low current remote LED indicator
insects in smoke detectors
E Attractive, low-profile design
E EN54 approved *
E Innovative base compensates for uneven surfaces
Conventional Fire Systems
Page : 6
KCT731
Calibration Tool for KL731/DP331I Fire Detectors
The KCT731 is a calibration tool to recalibrate the conventional
detectors after replacement of the field exchangeable optical block.
Specifications
Supply
2 x 9 V batteries
Dimensions (w x h x d)
104 x 195 x 63 mm
Ordering Information
KCT731 Calibration Tool for KL731/DP331I Fire Detectors
E Easy to use
E Simple "go/no-go" function
E Battery operated
Detector Bases & Accessories
Page : 7
KZ700
Universal fire detector base
The KZ700 is a 4 contact universal detector base. It has the ability to
compensate for uneven mounting surfaces. It is also available in black
for special applications in false ceilings.
Specifications
Dimensions
Diameter
104 mm
Height
24 mm
Ordering Information
KZ700 Universal fire detector base
KZ700B Universal fire detector base (for KL700/A and Dx300/1500) - Black
E Polarity sensitive
E Universal base fits conventional and analogue
detectors
E
E
E
E
Compensates for uneven surfaces
Remote indicator contact available
EN54 approved
Variant in black also available
Detector Bases & Accessories
Page : 8
KZ705
Universal fire detector base with earth connection
The KZ705 is a 5 contact universal detector base for use with the
KL700/Dx300 and KL700A/Dx1500 series detectors from GE-Interlogix.
In addition to the normal base and remote indication connectors, the
KZ705 also has an additional earth terminal connector to allow for
easy terminations of a possible cable screen.
Specifications
Dimensions (Ø x h)
100 x 29 mm
Operating Voltage
-
Current Consumption
-
Isolation Current
-
Isolation Resistance
-
Sounder Frequency
-
Sound Output
@ 3 mA
-
@ 5 mA
-
Environmental Characteristics
Operating Temperature
-10 to 70 °C
Storage Temperature
-10 to 70 °C
Relative Humidity (max)
95 % (non-cond.)
Ordering Information
KZ705 Universal fire detector base with earth connection
E Polarity sensitive
E Universal base fits conventional and analogue
detectors
E Additional earth terminal available
E Remote indicator contact available
Conventional Fire Systems
Page : 9
KZ705D
Conventional fire detector base with diode
The KZ705D is a 5 contact universal detector base for use with the
KL700/Dx300 series detectors from GE-Interlogix. In addition to the
normal base and remote indication connectors, the KZ705D also has
an additional earth terminal connector to allow for easy terminations
of a possible cable screen. The built in diode is specifically targeted at
systems using active end-of-line devices.
Specifications
Dimensions (Ø x h)
100 x 29 mm
Operating Voltage
-
Current Consumption
-
Isolation Current
-
Isolation Resistance
-
Sounder Frequency
-
Sound Output
@ 3 mA
-
@ 5 mA
-
Environmental Characteristics
Operating Temperature
-10 to 70 °C
Storage Temperature
-10 to 70 °C
Relative Humidity (max)
95 % (non-cond.)
Ordering Information
KZ705D Conventional fire detector base with diode
E
E
E
E
E
Polarity sensitive
Universal base for conventional detectors
Additional earth terminal available
Remote indicator contact available
Built in diode for active end-of-line systems
EOL-ACT
Active end-of-line device for use with FP400/KL700 fire panels
The EOL-ACT is designed for use with the NK700/FP400 fire panels from
GE-Interlogix. It is an active end-of-line device to allow the monitoring
of a conventional zone through a diode base (such as the KZ705D).
Ordering Information
EOL-ACT Active end-of-line device for use with FP400/KL700 fire panels
E Small
E Easy to install
Conventional Fire Systems
Page : 10
KZ705R
Conventional 12 VDC fire detector base with relay
The KZ705R is a 5 contact detector base for use with the KL731/DP331I
detectors from GE-Interlogix. In addition to the normal base and
remote indication connectors, the KZ705R also has an additional earth
terminal connector to allow for easy terminations of a possible cable
screen. A built in 12 V relay makes it ideal for use on low voltage
intrusion systems.
Specifications
Dimensions (Ø x h)
100 x 29 mm
Operating Voltage
12 V ± 10%
Current Consumption
12 A
Isolation Current
-
Isolation Resistance
-
Sounder Frequency
-
Sound Output
@ 3 mA
-
@ 5 mA
-
Environmental Characteristics
Operating Temperature
-10 °C to +70 °C
Storage Temperature
-10 °C to +70 °C
Relative Humdity
95 % (non cond.)
Ordering Information
KZ705R Conventional 12 VDC fire detector base with relay
E
E
E
E
Polarity sensitive
12 V relay for 4 wire systems
Additional earth terminal available
Remote indicator contact available
Detector Bases & Accessories
Page : 11
S700
Surface mount accessory for KZ700 and KZ705 series bases
The S700 is a base accessory designed for use with the KZ700 series
detector bases. It allows for a surface mount conduit and cable to
enter the base from the side. The KZ700 series base fits on top of this
accessory.
Specifications
Dimensions
Diameter
95 mm
Height
30 mm
Ordering Information
S700 Surface mount accessory for KZ700 and KZ705 series bases
E Surface mount accessory for KZ700 series bases
Conventional Fire Systems
Page : 12
DP721I
Photoelectric smoke detector with remote alarm LED output
700 series
The smoke detector continually monitors its own sensitivity and
operational status. Once a day, it performs a full diagnostic test which
includes dynamically testing the sensing chamber and internal
electronics.
Specifications
Operating voltage
8.5 - 33 V dc
Current consumption
Quiescent at 24 V dc
100 A; Max. 70 A average
In alarm at 24 V dc
60 mA
Alarm indication
White LED (red alarm)
Fault indication
Yellow LED
Remote alarm output
30 mA
RY contact rating
Relay models
2 A @ 30 V dc;1 A @ 120 V ac
Humidity
0 - 95%; Non-condensing
IP rating
IP 43
Operating temperature
-10°C - 60°C
Sensitivity
10%/m (+1.6%, -3.3%)
Reset voltage
2,5 V max
Reset time
1 sec
Dimensions
10 cm Ø, H = 5 cm
E Automatic Self Diagnostics : Dynamic full detector test,
Sensitivity test
E Manual Self Diagnostic routine with visual sensitivity
indication
Ordering Information
DP721I Photoelectric smoke detector with remote alarm LED output
DP721R Photoelectric smoke detector with C/O relay output
DB702 10 cm diameter base - 6 terminals
E
E
E
E
E
E
E
Field sensitivity testing without external meters
Field exchangeable and disposable optical chamber
High false alarm immunity
Floating background with drift compensation
Separate fire and trouble LED
12 - 24 V dc operation
Polarity insensitive
E Full range : optical, heat and optical/heat multi criteria
sensor
E EN 54 approved
Conventional Fire Systems
Page : 13
Photoelectric smoke and heat detector head with remote alarm LED
DP721T
700 series
Fitted with a field-exchangeable optical block. The smoke detector
continually monitors its own sensitivity and operational status. Once a
day, it performs a full diagnostic test which includes dynamically
testing the sensing chamber and internal electronics.
Specifications
Operating voltage
8.5 - 33 V dc FWR
Current consumption
Quiescent at 24 V dc
100 A; Max. 70 A average
In alarm at 24 V dc
60 mA
Alarm indication
White LED (red alarm)
Fault indication
Yellow LED
Remote alarm output
30 mA
RY contact rating
2 A @ 30 V dc;1 A @ 120 V ac
Humidity
0 - 95%; Non-condensing
IP rating
IP 43
Sensitivity
10%/m (+1.6%, -3.3%)
Reset voltage
2,5 V max
Reset time
1 sec
Dimensions
10 cm Ø, H = 5 cm
E Automatic Self Diagnostics : Dynamic full detector test,
Sensitivity test
Ordering Information
E Manual Self Diagnostic routine with visual sensitivity
DP721T
DP721RT
DP721RTA
DB702
Photoelectric smoke and heat detector head with remote alarm LED
Photoelectric smoke and heat detector with relay output
Photoelectric smoke and heat detector with relay output, autoreset
10 cm diameter base - 6 terminals
indication
E
E
E
E
E
E
E
Field sensitivity testing without external meters
Field exchangeable and disposable optical chamber
High false alarm immunity
Floating background with drift compensation
Separate fire and trouble LED
12 - 24 V dc operation
Polarity insensitive
E Full range : optical, heat and optical/heat multi criteria
sensor
E EN 54 approved
Conventional Fire Systems
Page : 14
DT713-5
57º C fixed and rate-of-rise heat detector
700 series
The smoke detector continually monitors its own sensitivity and
operational status. Once a day, it performs a full diagnostic test which
includes dynamically testing the sensing chamber and internal
electronics.
Specifications
Operating voltage
8.5 - 33 V dc FWR
Current consumption
Quiescent at 24 V dc
100 A; Max. 70 A average
In alarm at 24 V dc
60 mA
Alarm indication
Red LED
Fault indication
Yellow LED
Remote alarm output
30 mA
RY contact rating
2 A @ 30 V dc;1 A @ 120 V ac
Humidity
0 - 95%; Non-condensing
IP rating
IP 43
Heat specification
Max.
57º C ± 1.5º C
R.O.R.
8º C/min and > 40° C
Sensitivity
Reset voltage
2,5 V max
Reset time
1 sec
Dimensions
10 cm Ø, H = 5 cm
Ordering Information
DT713-5 57º C fixed and rate-of-rise heat detector
DT713-5R 57º C and R.O.R. heat detector, with relay output
DB702
10 cm diameter base - 6 terminals
E Automatic Self Diagnostics : Dynamic full detector test,
Sensitivity test
E Manual Self Diagnostic routine with visual sensitivity
indication
E
E
E
E
E
E
E
Field sensitivity testing without external meters
Field exchangeable and disposable optical chamber
High false alarm immunity
Floating background with drift compensation
Separate fire and trouble LED
12 - 24 V dc operation
Polarity insensitive
E Full range : optical, heat and optical/heat multi criteria
sensor
E EN 54 approved
Conventional Fire Systems
Page : 15
DT713-7
70º C fixed and R.O.R. heat detector
700 series
The smoke detector continually monitors its own sensitivity and
operational status. Once a day, it performs a full diagnostic test which
includes dynamically testing the sensing chamber and internal
electronics.
Specifications
Operating voltage
8.5 - 33 V dc FWR
Current consumption
Quiescent at 24 V dc
100 A; Max. 70 A average
In alarm at 24 V dc
60 mA
Alarm indication
Red LED
Fault indication
Yellow LED
Remote alarm output
30 mA
RY contact rating
2 A @ 30 V dc;1 A @ 120 V ac
Humidity
0 - 95%; Non-condensing
IP rating
IP 43
Heat specification
Max.
70º C ± 1.5º C
R.O.R.
8º C/min and > 40° C
Reset voltage
2,5 V max
Reset time
1 sec
Dimensions
10 cm Ø, H = 5 cm
E Automatic Self Diagnostics : Dynamic full detector test,
Sensitivity test
E Manual Self Diagnostic routine with visual sensitivity
indication
Ordering Information
DT713-7 70º C fixed and R.O.R. heat detector
DB702
10 cm diameter base - 6 terminals
E
E
E
E
E
E
E
Field sensitivity testing without external meters
Field exchangeable and disposable optical chamber
High false alarm immunity
Floating background with drift compensation
Separate fire and trouble LED
12 - 24 V dc operation
Polarity insensitive
E Full range : optical, heat and optical/heat multi criteria
sensor
E EN 54 approved
Conventional Fire Systems
Page : 16
DB702
10 cm diameter base - 6 terminals
700 series
Detector base for 700 series detectors
Ordering Information
DB702 10 cm diameter base - 6 terminals
DB702U 15 cm diameter base - 6 terminals
E Automatic Self Diagnostics : Dynamic full detector test,
Sensitivity test
E Manual Self Diagnostic routine with visual sensitivity
indication
E
E
E
E
E
E
E
Field sensitivity testing without external meters
Field exchangeable and disposable optical chamber
High false alarm immunity
Floating background with drift compensation
Separate fire and trouble LED
12 - 24 V dc operation
Polarity insensitive
E Full range : optical, heat and optical/heat multi criteria
sensor
E EN 54 approved
Conventional Fire Systems
Page : 17
DI650
Ionisation smoke detector
650 series
This elegant slim-line ionisation detector offers high performance and
wide operating voltage
Specifications
Size of detector (mm)
Height
42
Diameter
100
Size of detector + base (mm)
Height
50
Diameter
100
Supply voltage
9 - 33 V dc
Quiescent Current at 24 V
(typical)
28 A
Alarm indication
LED
Normal operating temp. range
(no icing)
-20 to + 60°C
Humidity (no condensation)
0-95% RH
Max. wind
10m/s
Remote alarm output current
17 mA
IP Rating
43
Ordering Information
DI650 Ionisation smoke detector
DI651 Integrating ionisation smoke dectector
DB860 Standard Base
E
E
E
E
E
E
E
E
E
Wide operating voltage
Advanced electronic technology
Flashing LED option
Polarity insensitive
Common base
Elegant slim-line design
EN54 approved
Magnetic test switch option
Proven detection performance
Conventional Fire Systems
Page : 18
DP652
Optical smoke detector
650 series
This elegant slim-line optical sensor provides high performance and
wide operating range.
Specifications
Size of detector (mm)
Height
42
Diameter
100
Size of detector + base (mm)
Height
50
Diameter
100
Supply voltage
9 - 33 V dc
Quiescent Current at 24 V
(typical)
40 A
Alarm indication
LED
Normal operating temp. range
(no icing)
-20 to + 60°C
Humidity (no condensation)
0-95% RH
Max. wind
Not affected
Remote alarm output current
17 mA
IP Rating
43
Ordering Information
DP652 Optical smoke detector
DB860 Standard Base
E
E
E
E
E
Polarity insensitive
Common base
Elegant slim-line design
EN 54 approved
Wide operating voltage
Conventional Fire Systems
Page : 19
DT654
Heat detector, R.O.R., 57º C A1R
650 series
This elegant slim-line heat sensor has a wide operating temperature
and is available in four ranges
Specifications
Size of detector (mm)
Height
42
Diameter
100
Size of detector + base (mm)
Height
50
Diameter
100
Supply voltage
9 - 33 V dc
Quiescent Current at 24 V
(typical)
45 A
Alarm indication
LED
Normal operating temp. range
(no icing)
-20 to + 60°C
Humidity (no condensation)
0-95% RH
Max. wind
Not affected
Remote alarm output current
17 mA
IP Rating
54
Ordering Information
DT654
DT655
DT656
DT657
DB860
Heat detector, R.O.R., 57º C A1R
Heat detector, 75º C BR
Heat detector, 95º C CR
Heat detector, 90º C CS
Standard Base
E
E
E
E
E
E
E
E
E
Wide operating voltage
Advanced electronic technology
Flashing LED option
Polarity insensitive
Common base
Elegant slim-line design
EN54 approved
Magnetic test switch option
Proven detection performance
Conventional Fire Systems
Page : 20
DB860
Standard Base
650 series
The base has been designed to enable detectors to be plugged in
without any need for force - particularly useful when fitting to
suspended ceilings.
Ordering Information
DB860 Standard Base
DB860U Standard base 15 cm diameter
E
E
E
E
E
Backplate for Ingress Protection 860-950
860 series Conventional fire detectors
Polarity insensitive
Common base
Elegant slim-line design
EN 54 approved
DB861
Ordering Information
DB861 Backplate for Ingress Protection 860-950
E Can prevent most ingress into the base and detector
Conventional Fire Systems
Page : 21
DB806
Conduit box for 860 / 950 series bases
An inexpensive and versatile accessory for surface mounting 860 and
950 series bases
Ordering Information
DB806 Conduit box for 860 / 950 series bases
DB650
650 series relay base
650 series
The relay base provides a volt-free contact for use in 4 wire control
systems, and other applications
Ordering Information
DB650 650 series relay base
E
E
E
E
DB650
For use with 4 wire control systems
Automatic door closers
Volt-free relay contacts
Addressable Fire Systems
Page : 22
DI1552
Ionisation Sensor
The 1500 Series uses a microprocessor for measurement and
communication. An enhanced protocol ensures the overall integrity
and error free operation of the system, without compromising
detection speed. All sensors are compatible with a standard base that
makes them easily interchangeable and support the connection of a
remote indicator.
Specifications
Operating voltage
22 to 38 VDC
Current consumption
Quiescent @ 38 VDC
200 A
In Alarm
< 11 mA
Alarm indication (Dual LED)
White OFF - Red ON
Remote Alarm Output
Available
Environment
Storage Temperature
-10 to +70 °C
Operating Temperature
-10 to +60 °C
Humidity (non-condensing)
0-95%
IP rating
IP42
Radioactive Source
0.33 ± 0.04 Ci Am 241
Dimensions (h x Ø)
45 x 99 mm
Ordering Information
DI1552
Ionisation Sensor
KZ700
KZ705
KZ705AS
KZ705I
KZ705IAS
Universal fire detector base
Universal fire detector base with earth connection
Analogue fire detector base with sounder
Analogue fire detector base with isolator
Analogue fire detector base with isolator and sounder
PA25/3L
Low current remote LED indicator
E
E
E
E
E
E
Remote signalling capabilities
Optical sensor with field exchangeable optical chamber
Easy soft addressing (1-125)
SMD technology
Reliable communication protocol
Full diagnostic self testing
E Full range: Ionisation, Optical and Heat and Dual
sensors (optical/heat)
E Full range of supporting I/O units and accessories
E EN54 Approved
Addressable Fire Systems
Page : 23
DP1561
Optical sensor with field exchangeable optical block
The 1500 series detectors use a microprocessor for measurement and
communication. An enhanced protocol ensures the overall integrity
and error free operation of the system, without compromising
detection speed.
All sensors are compatible with a standard base that makes them
easily interchangeable and support the connection of the PA25/3L
remote indicator.
Specifications
Operating voltage
22 to 38 VDC
Current consumption
Quiescent @ 38 VDC
350 A
In Alarm
< 11 mA
Alarm indication (Dual LED)
Red
Remote Alarm Output
Available
Environment
Storage Temperature
-10 to +70 °C
Operating Temperature
-10 to +60 °C
Humidity (non-condensing)
0-95%
IP rating
IP42
Remote signalling capabilities
DP1561
Optical sensor with field exchangeable optical block
E
E
E
E
E
E
KOB700
Replacement Optical Chamber for KL731/A & DP331I/1561 detectors
E Full range: Ionisation, Optical and Heat and Dual
KZ700
KZ705
KZ705AS
KZ705I
KZ705IAS
Universal fire detector base
Universal fire detector base with earth connection
Analogue fire detector base with sounder
Analogue fire detector base with isolator
Analogue fire detector base with isolator and sounder
E Full range of supporting I/O units and accessories
E EN54 Approved
PA25/3L
Low current remote LED indicator
Radioactive Source
NA
Dimensions (h x Ø)
45 x 99 mm
Ordering Information
Optical sensor with field exchangeable optical chamber
Easy soft addressing (1-125)
SMD technology
Reliable communication protocol
Full diagnostic self testing
sensors (optical/heat)
Addressable Fire Systems
Page : 24
DP1551T
Dual Sensor (Optical/Heat)
The 1500 Series uses a microprocessor for measurement and
communication. An enhanced protocol ensures the overall integrity
and error free operation of the system, without compromising
detection speed. All sensors are compatible with a standard base that
makes them easily interchangeable and support the connection of
aremote indicator.
Specifications
Operating voltage
22 to 38 VDC
Current consumption
Quiescent @ 38 VDC
350 A
In Alarm
< 5 mA
Alarm indication (Dual LED)
Red
Remote Alarm Output
Available
Environment
Storage Temperature
-10 to +70 °C
Operating Temperature
-10 to +70 °C
Humidity (non-condensing)
0-95%
IP rating
IP42
Radioactive Source
NA
Dimensions (h x Ø)
51 x 99 mm
Ordering Information
DP1551T Dual Sensor (Optical/Heat)
KZ700
KZ705
KZ705AS
KZ705I
KZ705IAS
Universal fire detector base
Universal fire detector base with earth connection
Analogue fire detector base with sounder
Analogue fire detector base with isolator
Analogue fire detector base with isolator and sounder
PA25/3L
Low current remote LED indicator
E
E
E
E
E
E
Remote signalling capabilities
Optical sensor with field exchangeable optical chamber
Easy soft addressing (1-125)
SMD technology
Reliable communication protocol
Full diagnostic self testing
E Full range: Ionisation, Optical and Heat and Dual
sensors (optical/heat)
E Full range of supporting I/O units and accessories
E EN54 Approved
Addressable Fire Systems
Page : 25
DT1553
Heat Sensor
The 1500 Series uses a microprocessor for measurement and
communication. An enhanced protocol ensures the overall integrity
and error free operation of the system, without compromising
detection speed. All sensors are compatible with a standard base that
makes them easily interchangeable and support the connection of
aremote indicator.
Specifications
Operating voltage
22 to 38 VDC
Current consumption
Quiescent @ 38 VDC
250 A
In Alarm
< 11 mA
Alarm indication (Dual LED)
White OFF - Red ON
Remote Alarm Output
Available
Environment
Storage Temperature
-10 to +80 °C
Operating Temperature
-10 to +70 °C
Humidity (non-condensing)
0-95%
IP rating
IP42
Radioactive Source
NA
Dimensions (h x Ø)
45 x 99 mm
Ordering Information
DT1553
Heat Sensor
KZ700
KZ705
KZ705AS
KZ705I
KZ705IAS
Universal fire detector base
Universal fire detector base with earth connection
Analogue fire detector base with sounder
Analogue fire detector base with isolator
Analogue fire detector base with isolator and sounder
PA25/3L
Low current remote LED indicator
E
E
E
E
E
E
Remote signalling capabilities
Optical sensor with field exchangeable optical chamber
Easy soft addressing (1-125)
SMD technology
Reliable communication protocol
Full diagnostic self testing
E Full range: Ionisation, Optical and Heat and Dual
sensors (optical/heat)
E Full range of supporting I/O units and accessories
E EN54 Approved
Addressable Fire Systems
Page : 26
PG700
Fire sensor programmer
The PG700 is a handheld device programmer and tester for the
KL700A/Dx1500 series detectors. It is battery operated and allows the
installer to perform installation tasks (such as device addressing) and
maintenance tasks (such as device calibration) in the field without
external assistance.
Specifications
Supply
2 x 9 V batteries
Dimensions (w x h x d)
104 x 195 x 63 mm
Ordering Information
PG700 Fire sensor programmer
E Easy to use
E Battery operated
E 4 User selectable programs
-Device analogue value
-Change Device Address
-Sequential device addressing
-KL731A Calibration
Addressable Fire Systems
Page : 27
KZ705I
Analogue fire detector base with isolator
The KZ705I is a detector base with built in isolator for use with the
KL700A/Dx1500 series detectors from GE-Interlogix. The isolator
protects the loop from short circuit conditions. A LED on the side of the
base indicates the status of the isolator.
Specifications
Dimensions (Ø x h)
100 x 29 mm
Operating Voltage
17 - 34 V
Current Consumption
50 A
Isolation Current
6 mA
Isolation Resistance
140 Mohm
Sounder Frequency
-
Sound Output
@ 3 mA
-
@ 5 mA
-
Environmental Characteristics
Operating Temperature
-10 °C to +70 °C
Storage Temperature
-10 °C to +70 °C
Relative Humidity (max)
95 % (non cond.)
Ordering Information
KZ705I Analogue fire detector base with isolator
E
E
E
E
E
Polarity sensitive
Universal base for analogue detectors
Additional earth terminal available
Remote indicator contact available
Built in isolator
Addressable Fire Systems
Page : 28
KZ705AS
Analogue fire detector base with sounder
The KZ705AS is a detector base with built in analogue addressable
sounder for use with the KL700A/Dx1500 series detectors from
GE-Interlogix. The sounder has its own address on the fire panel loop
and works independent of the detector. It is fully controlled from the
fire panel.
Specifications
Dimensions (Ø x h)
120 x 58 mm
Operating Voltage
22 - 38 V
Current Consumption
300 A Quiescent
Isolation Current
-
Isolation Resistance
-
Sounder Frequency
1 kHz (Continuous)
Sound Output
@ 3 mA
85 dBA
@ 5 mA
90 dBA
Environmental Characteristics
Operating Temperature
-10 °C to +70 °C
Storage Temperature
-10 °C to +70 °C
Relative Humidity (max)
95 % (non cond.)
IP Rating
IP21c
Ordering Information
KZ705AS Analogue fire detector base with sounder
E
E
E
E
E
E
E
Polarity sensitive
Universal base for analogue detectors
Additional earth terminal available
Remote indicator contact available
Built in sounder
Up to 90 dBA sound output
Low current consumption
Addressable Fire Systems
Page : 29
KZ705IAS
Analogue fire detector base with isolator and sounder
The KZ705IAS is a detector base with built in analogue addressable
sounder and isolator for use with the KL700A/Dx1500 series detectors
from GE-Interlogix. The sounder has its own address on the fire panel
loop and works independent of the detector. It is fully controlled from
the fire panel. The isolator protects the loop from short circuit
conditions.
Specifications
Dimensions (Ø x h)
120 x 58 mm
Operating Voltage
22 - 38 V
Current Consumption
350 A Quiescent
Isolation Current
6 mA
Isolation Resistance
140 Mohm
Sounder Frequency
1 kHz (Continuous)
Sound Output
@ 3 mA
85 dBA
@ 5 mA
90 dBA
Environmental Characteristics
Operating Temperature
-10 °C to +70 °C
Storage Temperature
-10 °C to +70 °C
Relative Humidity (max)
95 % (non cond.)
IP Rating
IP21c
Ordering Information
KZ705IAS Analogue fire detector base with isolator and sounder
E
E
E
E
E
E
E
E
Polarity sensitive
Universal base for analogue detectors
Additional earth terminal available
Remote indicator contact available
Built in sounder
Up to 90 dBA sound output
Low current consumption
Built in isolator
Addressable Fire Systems
Page : 30
KAL410
Conventional Zone Monitor Unit - 1 Zone
Allows the connection of one conventional zone to the analogue fire
system loop. This zone is constantly monitored. Up to 20 conventional
devices may be connected to this zone.
Specifications
Supply voltage
22-38 VDC
Current consumption
Quiescent @ 24 V
90 A
Quiescent @ 35 V
105 A
Alarm
< 3 mA
Aux. supply (24 VDC)
quiescent
200 A + equip
Aux. supply (24 VDC) alarm
< 85 mA
End-of-line resistor
4.7 kohm
Relay contact rating
NA
Environmental
Storage temperature
-10 °C to +50°C
Operating temperature
-10 °C to +70°C
Relative humidity
95 % (non condensing)
Dimensions (L x W x H)
117 x 80 x 44 mm
Ordering Information
KAL410 Conventional Zone Monitor Unit - 1 Zone
E
E
E
E
E
E
Easy numeric addressing
Continuous supervision of the conventional zones
Surface mount
Local alarm indication
Externally or loop powered
Aesthetically pleasing
E Part of family of I/O modules consisting of:
-Conventional Zone Monitors
-Digital Input Modules
-Extinguishing Control Modules
-Isolator Modules
-Manual Call Points
-Output Units
-Retention Units
-Supervised Output Units for sounder control
Addressable Fire Systems
Page : 31
KAL414C
Conventional Zone Monitor Unit - 4 Zones
Allows the connection of four conventional zones to the analogue fire
system loop. These zones are constantly monitored. Up to 20
conventional devices may be connected to any zone.
Specifications
Supply voltage
22-38 VDC
Current consumption
Quiescent @ 24 V
110 A
Quiescent @ 35 V
135 A
Alarm
< 5 mA
Aux. Supply (24V DC)
Quiescent
200 A + equip
Aux. Supply (24V DC) Alarm
< 360 mA
End-of-line resistor
4.7 kOhm
Relay contact rating
NA
Environmental
Storage temperature
-10 to +50°C
Operating temperature
-10 to +70°C
Relative humidity
(non-condensing)
0-95 %
Dimensions (l x w x h)
163 x 107 x 36 mm
Ordering Information
KAL414C Conventional Zone Monitor Unit - 4 Zones
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
Easy numeric addressing
Continuous supervision of the conventional zones
Surface mount
Local alarm indication
Externally powered
Aesthetically pleasing
Part of a family of I/O modules consisting of:
- Conventional Zone Monitors
- Digital Input Modules
- Extinguishing Control Modules
- Isolator Modules
- Manual Call Points
- Output Units
- Retention Units
- Supervised Output Units for sounder control
Addressable Fire Systems
Page : 32
KAL426C
Extinguishing Control Module
The 400 Series modules consists of a complete range of interfaces
developed for input/output control in the KSA700/FP1500 analogue fire
systems from GE Interlogix. The KAL426 allows for the connection and
control of one extinguishing area to the addressable fire panel loop.
Specifications
Supply voltage
22-38 VDC
Current consumption
Quiescent @ 24 V
110 A
Quiescent @ 35 V
210 A
Alarm
< 10 mA
Aux. supply (24 VDC)
quiescent
120 mA
Aux. supply (24 VDC) alarm
<1A
End-of-line resistor
4.7 kOhm
Relay contact rating
2½ A
Environmental
Storage temperature
-10 °C to +50°C
Operating temperature
-10 °C to +70°C
Relative humidity
95 % (non condensing)
Dimensions (L x W x H)
163 x 107 x 36 mm
Ordering Information
KAL426C Extinguishing Control Module
E
E
E
E
E
Aesthetically pleasing
Easy numeric addressing
Externally powered
Supervised I/O
Surface mount
E Part of family of I/O modules consisting of:
-Conventional Zone Monitors
-Digital Input Modules
-Extinguishing Control Modules
-Isolator Modules
-Manual Call Points
-Output Units
-Retention Units
-Supervised Output Units for sounder control
Addressable Fire Systems
Page : 33
KAL430
Relay Module - 1 Relay
Provides for one potential free relay output for the fire system loop.
Each relay allows for COMMON, NORMALLY OPEN and NORMALLY
CLOSED contacts. The output may be used to activate ventilation
controls, warning signs, activation of other alarm devices etc. during
fire situations.
Specifications
Supply voltage
22-38 VDC
Current consumption
Quiescent @ 24 V
70 A
Quiescent @ 35 V
100 A
Alarm
< 3.5 mA
Aux. 24 VDC quiescent
22 mA
Aux. 24 VDC alarm
< 50 mA
End-of-line resistor
NA
Relay contact rating
2½A @ 250 VAC
Environmental
Storage temperature
-10 °C to +50°C
Operating temperature
-10 °C to +70°C
Relative humidity
95 % (non condensing)
Dimensions (L x W x H)
Ordering Information
KAL430 Relay Module - 1 Relay
117 x 80 x 44 mm
E
E
E
E
E
E
Easy numeric addressing
Externally or loop powered
Normally open / normally closed operation for I/O
Surface mount
Aesthetically pleasing
Local status indication
E Part of family of I/O modules consisting of:
-Conventional Zone Monitors
-Digital Input Modules
-Extinguishing Control Modules
-Isolator Modules
-Manual Call Points
-Output Units
-Retention Units
-Supervised Output Units for sounder control
Addressable Fire Systems
Page : 34
KAL434C
Addressable Relay Module - 4 Relays
Provides for four potential free relay outputs for the fire system loop.
Each relay allows for COMMON, NORMALLY OPEN and NORMALLY
CLOSED contacts. The outputs may be used to activate ventilation
controls, warning signs, activation of other alarm devices etc. during
fire situations.
Specifications
Supply voltage
22-38 VDC
Current consumption
Quiescent @ 24 V
110 A
Quiescent @ 35 V
135 A
Alarm
10 mA
Aux. 24VDC Quiescent
100 A
Aux. 24VDC Alarm
10 mA
End-of-line resistor
NA
Relay contact rating
2½A @ 250 VAC
Environmental
Storage temperature
-10 to +50°C
Operating temperature
-10 to +70°C
Relative humidity (non-cond.) 0-95 %
Dimensions (l x w x h)
163 x 107 x 36 mm
Ordering Information
KAL434C Addressable Relay Module - 4 Relays
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
Easy numeric addressing
Externally powered
Normally open / normally closed operation for I/O
Surface mount
Aesthetically pleasing
Local status indication
Part of a family of I/O modules consiting of:
- Conventional Zone Monitors
- Digital Input Modules
- Extinguishing Control Modules
- Isolator Modules
- Manual Call Points
- Output Units
- Retention Units
- Supervised Output Units for sounder control
Addressable Fire Systems
Page : 35
KAL440
Supervised Relay Module
Allows for the supervision of a single, 24 Volt powered output contact
on the fire system loop. This unit may be used to control for e.g.
sounders in case of fire conditions, but may also be used to switch any
output considered crucial enough to have the cable integrity between
the unit and the switch point monitored.
Specifications
Supply voltage
22-38 VDC
Current consumption
Quiescent @ 24 V
110 A
Quiescent @ 35 V
135 A
Alarm
< 3.6 mA
Aux. 24 VDC quiescent
23 mA
Aux. 24 VDC alarm
23 mA + equip
End-of-line resistor
4.7 kohm
Relay contact rating
1¼ A @ 250 VAC
Environmental
Storage temperature
-10 °C to +50°C
Operating temperature
-10 °C to +70°C
Relative humidity
95 % (non condensing)
Dimensions (L x W x H)
117 x 80 x 44 mm
Ordering Information
KAL440 Supervised Relay Module
E
E
E
E
E
E
Easy numeric addressing
Externally powered
Supervised 24 VDC Output
Surface mount
Aesthetically pleasing
Local status indication
E Part of family of I/O modules consisting of:
-Conventional Zone Monitors
-Digital Input Modules
-Extinguishing Control Modules
-Isolator Modules
-Manual Call Points
-Output Units
-Retention Units
-Supervised Output Units for sounder control
Addressable Fire Systems
Page : 36
KAL450
Addressable Manual Call Point
The 400 Series modules consists of a complete range of interfaces
developed for input/output control in the KSA700/FP1500 analogue fire
systems from GE Interlogix. The KAL450 is an addressable manual call
point for manual fire activation.
Specifications
Supply voltage
22-38 VDC
Current consumption
Quiescent @ 24 V
90 A
Quiescent @ 35 V
120 A
Alarm
< 3.5 mA
Aux. supply (24 VDC)
quiescent
NA
Aux. supply (24 VDC) alarm
NA
End-of-line resistor
NA
Relay contact rating
NA
Environmental
Storage temperature
-10 °C to +70°C
Operating temperature
-10 °C to +50°C
Relative humidity
95 % (non condensing)
Ingress Protection
IP20
Dimensions (L x W x H)
87 x 87 x 20 mm
Weight
98 g
Ordering Information
KAL450
DM715
DM780
DM781
DM782
DM783
DM784
DM785
DM787
DM788
DM790
DM795
DM798
DM799
DM800
Addressable Manual Call Point
EN54 universal glass for manual call point
Terminal tray for MCP
GS card
Hinged transparent MCP protection cover
BZB black bezel
Test key
Spacer box, red
Surface mounting box with connectors, red
Surface mount box without connectors, red
Flush mount cradle with connectors
Flush mount cradle, connectors & forkgrips
Breakable seal for MCP
Terminal tray ETT/3 with bezel 3
Resettable element for MCP DM700/KAL450
E
E
E
E
E
E
Easy numeric addressing
Loop powered
Local test facility
Surface or flush mount
Aesthetically pleasing
Local status indication
E Part of family of I/O modules consisting of:
-Conventional Zone Monitors
-Digital Input Modules
-Extinguishing Control Modules
-Isolator Modules
-Manual Call Points
-Output Units
-Retention Units
-Supervised Output Units for sounder control
E Wide range of accessories
Addressable Fire Systems
Page : 37
KAL460
Digital Input Module
Provides a remote input to the fire system loop. The input is constantly
monitored and its status communicated to the fire control panel. The
input may be activated by closing or opening a potential free contact,
depending on the module configuration.
This module may be used to monitor any contact by showing its status
through the fire control panel e.g. the monitoring of pressure
equipment and closure fire break doors.
Specifications
Supply voltage
22-38 VDC
Current consumption
Quiescent @ 24 V
110 A
Quiescent @ 35 V
135 A
Alarm
< 10 mA
Aux. 24 VDC quiescent
200 A
Aux. 24 VDC alarm
< 50 mA
End-of-line resistor
NA
Relay contact rating
NA
Environmental
Storage temperature
-10 °C to +50°C
Operating temperature
-10 °C to +70°C
Relative humidity
95 % (non condensing)
Dimensions (L x W x H)
Ordering Information
KAL460 Digital Input Module
117 x 80 x 44 mm
E
E
E
E
E
E
Easy numeric addressing
Externally or loop powered
Normally open / normally closed operation for I/O
Surface mount
Aesthetically pleasing
Local status indication
E Part of family of I/O modules consisting of:
-Conventional Zone Monitors
-Digital Input Modules
-Extinguishing Control Modules
-Isolator Modules
-Manual Call Points
-Output Units
-Retention Units
-Supervised Output Units for sounder control
Addressable Fire Systems
Page : 38
KAL470
Isolator Module
The 400 series modules consist of a complete range of interfaces
developed for input/output control in the KSA700/FP1500 analogue fire
systems from GE Interlogix. The KAL470 is an isolator module in this
series that isolates the faulty zone on a fire panel loop during short
circuit conditions. The KAL470 does not use an address on the loop.
Specifications
Supply voltage
22-38 VDC
Current consumption
Quiescent @ 24 V
110 A
Quiescent @ 35 V
135 A
Alarm
10 mA
Aux. supply (24 VDC)
quiescent
NA
Aux. supply (24 VDC) alarm
NA
End-of-line resistor
NA
Relay contact rating
NA
Environmental
Storage temperature
-10 °C to +50°C
Operating temperature
-10 °C to +50°C
Relative humidity
95 % (non condensing)
Dimensions (L x W x H)
Ordering Information
KAL470 Isolator Module
75 x 45 x 28 mm
E
E
E
E
Requires no device address
Automatic reset
Local status indication
Surface mount
E Part of family of I/O modules consisting of:
-Conventional Zone Monitors
-Digital Input Modules
-Extinguishing Control Modules
-Isolator Modules
-Manual Call Points
-Output Units
-Retention Units
-Supervised Output Units for sounder control
Addressable Fire Systems
Page : 39
KAL490
Retention Module - 1 Input / 1 Output
Provides a remote input and a potential free voltage relay output to
the fire system loop. The input signal is constantly monitored and its
status displayed on the control panel, whilst the output is fail-to-safe.
Auxiliary supply monitoring is also included.
The module is used to for e.g. control and monitor doors such as fire
break doors. The relay provides the door activation and the input
monitors the door status.
Specifications
Supply voltage
22-38 VDC
Current consumption
Quiescent @ 24 V
110 A
Quiescent @ 35 V
135 A
Alarm
10 mA
Aux. 24 VDC quiescent
200 A
Aux. 24 VDC alarm
< 50 mA
End-of-line resistor
NA
Relay contact rating
1A @ 30 VAC/VDC
Environmental
Storage temperature
-10 °C to +50°C
Operating temperature
-10 °C to +70°C
Relative humidity
95 % (non condensing)
Dimensions (L x W x H)
117 x 80 x 44 mm
Ordering Information
KAL490 Retention Module - 1 Input / 1 Output
E
E
E
E
E
E
Easy numeric addressing
Externally or loop powered
Normally open / normally closed operation for I/O
Surface mount
Aesthetically pleasing
Local status indication
E Part of family of I/O modules consisting of:
-Conventional Zone Monitors
-Digital Input Modules
-Extinguishing Control Modules
-Isolator Modules
-Manual Call Points
-Output Units
-Retention Units
-Supervised Output Units for sounder control
Addressable Fire Systems
Page : 40
DP2051
Optical Sensor
2000 Series
Equipped with a field-exchangeable optical block and has full
certification, this optical sensor provides good looks as well as top
features
Specifications
Operating voltage
17 - 28 V dc
Current consumption at 24 V dc
Quiescent
< 150 A
Alarm
LED: 2 mA - 7-segment: 2 mA
Alarm indication
White LED (red alarm)
Remote alarm output
DP2051 / DT2053
-
DP2061 / DT2063
4 mA
DP2071 / DT2073
4 mA
Humidity
0 - 95% non condensing
Operating temperature
-10°C - 70°C
IP rating
IP43
Dimensions
Height
5 cm
Diameter
10 cm
Ordering Information
DP2051 Optical Sensor
DB2001 2000 series base, 2 terminals
DB2016 Isolating base
E
E
E
E
E
E
E
E
E
E
E
E
Remote test capabilities
Remote signalling capabilities
Optical sensor with field exchangeable optical chamber
Easy numeric addressing (1-128)
Enhanced communication protocol
Full diagnostic self testing
Polarity insensitive
Full range: optical and heat
Full range of I/0 units and accessories
Isolator base
EN54 approved
VdS approved
Addressable Fire Systems
Page : 41
DP2061
Optical Sensor with remote LED output
The DP2061 is equipped with a field-exchangeable optical block and
has full certification. This optical sensor combines good looks with
alarm and fault LEDs as well as a remote output.
Specifications
Operating voltage
17 - 28 VDC
Current consumption @ 24 VDC
Quiescent
< 150 A
Alarm
2 mA
Alarm indication
White LED (Red alarm)
Remote alarm output
4 mA
Humidity
0 - 95% non condensing
Operating temperature
-10 to +70°C
IP rating
IP43
Dimensions
Height
5 cm
Diameter
10 cm
Ordering Information
DP2061
Optical Sensor with remote LED output
DB2002 2000 series base, 4 terminals
DB2002U Standard Base 15 cm, 4 Terminals
DB2016 Isolating base
E
E
E
E
E
E
E
E
E
E
E
E
Remote test capabilities
Remote signalling capabilities
Optical sensor with field exchangeable optical chamber
Easy numeric addressing (1-128)
Enhanced communication protocol
Full diagnostic self testing
Polarity insensitive
Full range of detectors available
Full range of I/0 units and accessories
Isolator base
EN54 approved
VdS approved
Addressable Fire Systems
Page : 42
DP2061T
Optical and heat multi-sensor with remote LED output
The DP2061T multi-sensor combines the smoke sensitivity of an optical
smoke detector with the enhancement of heat sensing. Being able to
operate in five modes, the DP2061T multi sensor can operate as an
optical smoke sensor enhanced by heat detection (with two different
smoke sensitivities), as a dual smoke and heat detector, each sensor
operating independently, an optical sensor only, or a heat detector
only.
Specifications
Operating voltage
17 to 28 VDC
Current consumption @ 24 VDC
Quiescent
< 150 uA
Alarm
2 mA
Alarm indication
White LED (Red alarm)
Remote alarm output
4mA
Humidity
0 - 95% non condensing
Operating temperature
-10°C to 70°C
IP rating
IP43
Dimensions
Height
5 cm
Diameter
10 cm
E Optical smoke and heat detection
E Five modes of operation: multisensor (2 sensitivities) ,
dual sensor, or independant smoke and heat
Ordering Information
DP2061T Optical and heat multi-sensor with remote LED output
DB2001
DB2002
DB2002U
DB2004
DB2016
2000 series base, 2 terminals
2000 series base, 4 terminals
Standard Base 15 cm, 4 Terminals
2000 series deep base, 4 terminals
Isolating base
AI672
AI673
Optical Remote Indicator
Optical and Accustical Remote Indicator
E
E
E
E
E
E
E
E
E
E
E
Independant control of detector modes
Optical sensor with field exchangeable optical chamber
Easy numeric addressing (1-128)
Enhanced communication protocol
Full diagnostic self testing
Remote test capabilities
Remote signalling capabilities
Polarity insensitive
Full range of sensors: optical and heat
Full range of I/0 units, MCPs and accessories
Isolator base option
Addressable Fire Systems
Page : 43
DP2071
Optical Sensor with 7-segment display
2000 Series
Equipped with a field-exchangeable optical block and with full
certification, this optical sensor provides good looks as well as top
features. Fitted with an exclusive 7-segment display, the sensor
provides comprehensive information. In addition to alarm signalling,
information such as Fault, Pre-alarm, Maintenance Alarm (Clean me),
Disabled Sensor, Sensor in Test, Error (double address, wrong sensor
type) and Sensor Polled is provided.
Specifications
Operating voltage
17 - 28 V dc
Current consumption at 24 V dc
Quiescent
< 150 A
Alarm
LED: 2 mA - 7-segment: 2 mA
Alarm indication
White LED (red alarm)
Remote alarm output
4 mA
DP2051 / DT2053
-
DP2061 / DT2063
4 mA
DP2071 / DT2073
4 mA
Humidity
0 - 95% non condensing
Operating temperature
-10°C - 70°C
IP rating
IP43
Dimensions
Height
5 cm
Diameter
10 cm
Ordering Information
DP2071
DB2002
DB2002U
DB2016
Optical Sensor with 7-segment display
2000 series base, 4 terminals
Standard Base 15 cm, 4 Terminals
Isolating base
E
E
E
E
E
E
E
E
E
E
7-segment display
Remote test capabilities
Remote signalling capabilities
Optical sensor with field exchangeable optical chamber
Easy numeric addressing (1-128)
Enhanced communication protocol
Full diagnostic self testing
Polarity insensitive
Full range: optical and heat
Full range of I/0 units and accessories
Addressable Fire Systems
Page : 44
DT2053
2000 Series heat sensor
2000 series
Fully certified, this heat sensor provides good looks as well as top
features.
Specifications
Operating voltage
17 - 28 V dc
Current consumption at 24 V dc
Quiescent
< 150 A
Alarm
LED: 2 mA - 7-segment: 2 mA
Alarm indication
Red LED
Remote alarm output
DP2051 / DT2053
-
DP2061 / DT2063
4 mA
DP2071 / DT2073
4 mA
Humidity
0 - 95% non condensing
Operating temperature
-10°C - 70°C
IP rating
IP43
Dimensions
Height
5 cm
Diameter
10 cm
Ordering Information
DT2053 2000 Series heat sensor
DB2001 2000 series base, 2 terminals
DB2016 Isolating base
E Remote test capabilities
E Remote signalling capabilities
E Optical sensor with field exchangeable optical chamber
E Available in one LED, two LED and seven segment
display
E
E
E
E
E
E
E
E
E
Easy numeric addressing (1-128)
Enhanced communication protocol
Full diagnostic self testing
Polarity insensitive
Full range: optical and heat
Full range of I/0 units and accessories
Isolator base
EN54 approved
VdS approved
Addressable Fire Systems
Page : 45
DT2063
2000 series heat sensor with remote LED output
2000 Series
Fully certified, this heat sensor provides good looks as well as top
features. Dual LED's indicate both alarm and fault. A remote output is
also provided.
Specifications
Operating voltage
17 - 28 VDC
Current consumption @ 24 VDC
Quiescent
< 150 A
Alarm
LED: 2 mA - 7-segment: 2 mA
Alarm indication
Red LED
Remote alarm output
4 mA
Humidity
0 - 95% non condensing
Operating temperature
-10 to +70°C
IP rating
IP43
Dimensions
Height
5 cm
Diameter
10 cm
Ordering Information
DT2063
2000 series heat sensor with remote LED output
DB2002 2000 series base, 4 terminals
DB2002U Standard Base 15 cm, 4 Terminals
DB2016 Isolating base
E Remote test capabilities
E Remote signalling capabilities
E Optical sensor with field exchangeable optical chamber
E Available in one LED, two LED and seven segment
display
E
E
E
E
E
E
E
E
E
Easy numeric addressing (1-128)
Enhanced communication protocol
Full diagnostic self testing
Polarity insensitive
Full range: optical and heat
Full range of I/0 units and accessories
Isolator base
EN54 approved
VdS approved
Addressable Fire Systems
Page : 46
DT2073
Heat Sensor with 7-segment Display and Remote LED Output
2000 Series
Fitted with an exclusive 7-segment display, this detector provides
comprehensive, on the spot information. In addition to alarm signalling,
information such as Fault, Pre-alarm, Maintenance Alarm (Clean me),
Disabled Sensor, Sensor in Test, Error (double address, wrong sensor
type) and Sensor Polled is provided.
Specifications
Operating voltage
17 - 28 V dc
Current consumption at 24 V dc
Quiescent
< 150 A
Alarm
LED: 2 mA - 7-segment: 2 mA
Alarm indication
Red LED
Remote alarm output
DP2051 / DT2053
-
DP2061 / DT2063
4 mA
DP2071 / DT2073
4 mA
Humidity
0 - 95% non condensing
Operating temperature
-10°C - 70°C
IP rating
IP43
Dimensions
Height
5 cm
Diameter
10 cm
Ordering Information
E Remote test capabilities
E Remote signalling capabilities
E Optical sensor with field exchangeable optical chamber
E Available in one LED, two LED and seven segment
display
DT2073
DB2002
DB2002U
DB2016
Heat Sensor with 7-segment Display and Remote LED Output
2000 series base, 4 terminals
Standard Base 15 cm, 4 Terminals
Isolating base
E
E
E
E
E
E
E
E
E
Easy numeric addressing (1-128)
Enhanced communication protocol
Full diagnostic self testing
Polarity insensitive
Full range: optical and heat
Full range of I/0 units and accessories
Isolator base
EN54 approved
VdS approved
Addressable Fire Systems
Page : 47
DB2001
2000 series base, 2 terminals
2000 series
2 terminal base for DP2051 and DT2053
Ordering Information
DB2001 2000 series base, 2 terminals
E Remote test capabilities
E Remote signalling capabilities
E Optical sensor with field exchangeable optical chamber
E Available in one LED, two LED and seven segment
display
E
E
E
E
E
E
E
E
E
Easy numeric addressing (1-128)
Enhanced communication protocol
Full diagnostic self testing
Polarity insensitive
Full range: optical and heat
Full range of I/0 units and accessories
Isolator base
EN54 approved
VdS approved
Addressable Fire Systems
Page : 48
DB2002
2000 series base, 4 terminals
2000 series
A four terminal base for all 2000 series detectors
Ordering Information
DB2002 2000 series base, 4 terminals
DB2002U Standard Base 15 cm, 4 Terminals
E Remote test capabilities
E Remote signalling capabilities
E Optical sensor with field exchangeable optical chamber
E Available in one LED, two LED and seven segment
display
E
E
E
E
E
E
E
E
E
Easy numeric addressing (1-128)
Enhanced communication protocol
Full diagnostic self testing
Polarity insensitive
Full range: optical and heat
Full range of I/0 units and accessories
Isolator base
EN54 approved
VdS approved
Addressable Fire Systems
Page : 49
DB2016
Isolating base
The DB2016 isolator base senses and isolates short circuit faults. A
yellow LED indicates a short circuit condition. The detector in the base
will still receive power in the event of a single short circuit. If every
detector is fitted with an isolator base then no device will be lost in the
event of a single short circuit.
Ordering Information
DB2016 Isolating base
E Remote test capabilities
E Remote signalling capabilities
E Optical sensor with field exchangeable optical chamber
E Available in one LED, two LED and seven segment
display
E
E
E
E
E
E
E
E
E
Easy numeric addressing (1-128)
Enhanced communication protocol
Full diagnostic self testing
Polarity insensitive
Full range: optical and heat
Full range of I/0 units and accessories
Isolator base
EN54 approved
VdS approved
Addressable Fire Systems
Page : 50
IU2016
Loop Isolator
2000 series
The Aritech Loop Isolator is designed to prevent an entire
communication loop from being disabled in the event of a short circuit.
The IU 2016 isolates that part of the loop containing the short from the
remainder of the circuit.
Specifications
Operating voltage
17 - 28 V, comm. loop terminals
Total standby current
< 250 A
Isolated current
Average
< 1.6 mA
Transition pulse
< 36 mA (5 ms duration)
Operating temperature
-10º C to 70º C
Operating humidity range
0 - 95%; Non-condensing
Line resistance
Normal
0.55 Ohms
Isolated
> 33K Ohms
Switching voltage
Normal to isolated
13.8 V dc
Isolated to normal
2.5 V dc
Switching time
Normal to isolated
< 5 ms
Isolated to normal
< 0.5 ms (after fault correction)
Ordering Information
IU2016 Loop Isolator
DB2003 Base for the IU2016 isolator
E Complete isolation of loop short circuit
E Automatic restore when fault is corrected
E Module LED indicates location of fault
Addressable Fire Systems
Page : 51
Base for the IU2016 isolator
Ordering Information
DB2003 Base for the IU2016 isolator
DB2003
Addressable Fire Systems
Page : 52
DM2000
Manual call point, flying leads
2000 series
The DM 2000 is a break glass design call point with a high strength
plastic housing. The LED indicator provides visual confirmation of alarm
initiation. The test key (included with each unit) facilitates functional
testing of the call point.
Specifications
Operating voltage
17 - 28 V, @ comm.loop terminals
Voltage modulation
4 - 9 V dc
Standby current
< 250 A
LED indicator current
2.5 mA maximum
Operating temperature
-10º C to 70º C
Operating humidity
0 - 95%; Non-condensing
Dimensions (L x W x H)
Flush mount
87 x 87 x 24 mm
Surface mount
87 x 87 x 56 mm
Ordering Information
DM2000
DM2000Y
DM2000B
DM711
DM715
Manual call point, flying leads
Manual call point flying leads - Yellow
Manual call point flying leads - Blue
Break glass, EN54, Aritech logo
EN54 universal glass for manual call point
E
E
E
E
E
E
Analogue addressable manual call point
LED alarm indicator
Tamper resistant break glass design
Easy to test with self reset
Fast response
IP67 waterproof model available
Addressable Fire Systems
Page : 53
DM2000E
Manual call point - Red IP67 waterproof, including backbox
2000 series
The DM 2000E is a break glass design call point with a high strength
plastic housing and IP67 waterproof. The LED indicator provides visual
confirmation of alarm initiation. The test key (included with each unit)
facilitates functional testing of the call point.
Specifications
Operating voltage
17 - 28 V, @ comm.loop terminals
Voltage modulation
4 - 9 V dc
Standby current
< 250 A
LED indicator current
2.5 mA maximum
Operating temperature
-10º C to 70º C
Operating humidity
0 - 95%; Non-condensing
Dimensions (L x W x H)
Flush mount
87 x 87 x 24 mm
Surface mount
87 x 87 x 56 mm
Ordering Information
DM2000E Manual call point - Red IP67 waterproof, including backbox
DM711
Break glass, EN54, Aritech logo
DM715
EN54 universal glass for manual call point
E
E
E
E
E
E
Analogue addressable manual call point
LED alarm indicator
Tamper resistant break glass design
Easy to test with self reset
Fast response
IP67 waterproof model available
Addressable Fire Systems
Page : 54
IO2014
Input Output unit - 4 inputs
The 2000 Series loop powered Input/Output modules are designed to
provide unlimited applications to input monitoring and output
switching. These modules, combined with the powerful features of the
2000/1200 Series fire panels gives the user total versatility.
The IO2014 is a unit that provides 4 inputs with selectable line
supervision.
Specifications
Operating voltage
17 - 39 VDC
Total standby current
< 420 A
Typical standby current
< 350 A
Operating temperature
-10°C to +70°C
Operating humidity range
0 - 95%, Non-condensing
Outputs
NA
Inputs
4 Supervision Selectable
33 k resistor in series with
switch
Normal, Active, Open, Short
No resistor in series with
switch
Open, Short
EOL resistor
150 k , ¼ W, 5%
E Wide range of I/O Modules : 2 input-1 output / 2 input-2
output / 4 input / 4 input - 4 output
Ordering Information
IO2014 Input Output unit - 4 inputs
E
E
E
E
E
E
E
Versatile input structure
Supervised inputs
Normally Open/Normally Closed operation
Magnetic latched output relays
Loop powered
No external power required
Easy numeric addressing
Addressable Fire Systems
Page : 55
IU2050
Single Input Module
2000 series
The Aritech Analogue Addressable Single Input Module is designed for
use with the FP 2000 Fire Panel to monitor normally open or normally
closed
contacts. It can typically be connected to conventional Manual Call
Points, Pull Stations or Door Monitors and will report actuation within 1
second
depending on the programming of the fire panel.
Specifications
Operating voltage
17 - 28 V, @ comm. loop terminals
Voltage modulation
4-9 V dc
Standby current
< 250 A
Operating temperature
-20° C to 70° C
Operating humidity
0 - 95%; Non-condensing
EOL resistor
150 K, 1/4 W, 5%
Ordering Information
IU2050 Single Input Module
E Analogue Addressable Single Input Module
E Loop Powered
E Supervised Input
Addressable Fire Systems
Page : 56
IU2055
Conventional Zone Monitor
The IU2055 two-wire zone monitor is designed to provide an interface
between conventional smoke detectors and the addressable series
2000/1200 fire panels. The IU2055 enables the adressable panel to
monitor the presence and operation of up to 30 conventional detectors
in standard operation mode, or up to 20 intrinsically safe series 870
conventional detectors in intrinscally safe configurations.
Specifications
Operating voltage
At loop terminals
18 - 39 VDC
At zone output terminals
14 - 18.5 VDC
Operating current
Standby
< 15 mA
Alarm
< 35 mA
Remote LED
4.5 mA
Maximum zone load current
3.5 mA
Maximum zone capacitance
<1 F
Maximum zone resistance
< 30 Ohm
Operating temperature
-10° C to +70° C
Operating humidity range
0 - 95%; Non-condensing
End of line resistance
4.3 k Ohm, ¼ W, 5 %
Zone impedances @ 24 V
Short circuit
< 30 Ohms
Fire
180 - 300 Ohms
Quiescent
2.7 - 4.3 K Ohms
Open
> 15 K Ohms
E
E
E
E
E
Monitors up to 30 conventional smoke detectors
Zone supervised for open and short circuits
Supports alarm verification and reset functions
Loop powered
Easy numeric addressing
E Supports intrinsically safe applications for up to 20
Ordering Information
IU2055 Conventional Zone Monitor
series 870 detectors
Addressable Fire Systems
Page : 57
GBX2000
Galvanic barrier
2000 series
A Galvanic barrier used with IU2055 zone monitor unit in intrinsic safe
applications
Ordering Information
GBX2000 Galvanic barrier
E Approved with the IU2055 zone monitor unit
E Intrinsic safe operation when correctly installed
IU2080
Indicating Circuit Controller
2000 series
The Aritech Indicating Circuit Controller is designed for efficient,
addressable control of sounders, bells and strobes in a fire detection
system. The 3 A of output power available from the IU 2080 assures
meeting all requirements for signaling devices on a fire alarm system.
Specifications
Operating voltage
17-28 V, at comm. loop terminals
Total standby current
<350 A, <200 A typical
Maximum alarm current
<3.5 mA at comm. loop
Operating temperature
-10º C to 70º C
Operating humidity range
0 - 95%; Non-condensing
Circuit impedance at 24 V
Short circuit
<3.3 K
Quiescent
3.3 K - 13 K
Open circuit
<13 K
Power supply low voltage
detection
24 V; <20.4 V
Standby current
<11 mA @ 24 V dc
Alarm current
Supervisory voltage
<72 mA @ 24 V dc (plus output circuit load
current from ext. power supply)
2.2 V dc, inverted
Circuit voltage in alarm
24 V dc
Alarm current (fuse rating)
3A
End of line resistor value
10 K, 1/4W, 5%
Ordering Information
IU2080 Indicating Circuit Controller
E Versatile, addressable control for sounders, bells and
strobes
E Supervised output circuit
E Programmable output
E 24 V external power supply
Addressable Fire Systems
Page : 58
FD2705R
2000 series addressable reflective beam detector 5 - 50m
2000 series
The FD 2705R and FD 2710R provides an integral, loop powered
analogue addressable reflective beam detector up to 100m distance.
It operates with 2000 series protocol with the FP1200 / 2000 Fire
panels
Specifications
Supply voltage
17 - 30 V dc
Range
FD 2705R
5 - 50 m
FD 2710R
50 - 100 m
Lateral detection
7.5 m
Current consumption
Quiescent
5 mA
Alarm
9 mA
Fault
5 mA
Optical wave length
880 nm
Operating temperature
-30°C to 55°C
Size
210 x 130 x 120 mm
IP rating
IP50
Construction
Flame retardent ABS
Colour
Gray-black
Ordering Information
FD2705R 2000 series addressable reflective beam detector 5 - 50m
FD2710R 2000 series addressable reflective beam detector 50 - 100m
E
E
E
E
E
E
E
E
E
E
E
E
E
E
Loop Powered
2000 series protocol
Area coverage up to 600 m 2 per unit
Range from 5 - 50 m and 50 - 100 m
Up to ceiling heights of 25 m
Low current consumption
3 selectable alarm thresholds
Self check and automatic contamination compensation
Automatic discrimination between fire and fault
Retro operation through prism
Vertical or horizontal mount
Easy wiring and unique alignment
Microprocessor controlled
Conforms to BS 5839 part 5 and EN54
Warning Device
Page : 59
AS2015
2000 series loop powered sounder
2000 series
The AS2015 is a 2000 series addressable loop powered sounder for the
FP1200 and FP2000 range of fire panels. The unit has a built in isolator
and can be synchronized.
Specifications
Operating voltage
17-39 VDC
Supply current
not activated
240 A
activated
3mA
Sound output @ 1 meter
100 dB(A)
Continuous tone
990 Hz
Intermittent tone
990 Hz, On Off @ 1 Hz
Two tone
990 Hz / 650 Hz @ 1 Hz
Ordering Information
AS2015
2000 series loop powered sounder
AS2015W 2000 series loop powered sounder - white
E
E
E
E
E
E
Loop powered
Low current
High output
Built in isolators
3 tones
FP1200 / 2000 fire panel operation
Addressable Fire Systems
Page : 60
DI950
Analogue addressable ionisation sensor
950 series
This elegant slim-line ionisation sensor provides high-performance
smoke detection
Specifications
Supply voltage (V dc)
17-28
Quiescent current
280 A
Alarm indication
Red LED
Alarm LED current
2 mA
Normal operating temperature
(no icing)
-20º to +60º C
Rel. humidity (no condensation)
0-95 %
Max. wind (continuous)
10 m/s
Size of device in base (H x Ø mm) 50 x 100
Ordering Information
DI950 Analogue addressable ionisation sensor
E
E
E
E
Passive base address
Programmable slide-in address card
Aesthetic design
EN 54,BOSEC,VdS,CNBOP approved
DP951
Optical sensor
950 series
This elegant slim-line optical sensor provides high performance
analogue addressable features
Specifications
Supply voltage (V dc)
17-28
Quiescent current
340 A
Alarm indication
Clear LED (red in alarm)
Alarm LED current
4 mA
Normal operating temperature
(no icing)
-20º to +60º C
Rel. humidity (no condensation)
0-95 %
Max. wind (continuous)
Not affected
Size of device in base (H x Ø mm) 50 x 100
Ordering Information
DP951 Optical sensor
DB950 950 series standard base
E
E
E
E
Passive base address
Programmable slide-in address card
Aesthetic design
EN 54,BOSEC,VdS,CNBOP approved
Addressable Fire Systems
Page : 61
DT952
Analogue addressable temperature sensor
950 series
This elegant slim-line analogue addressable heat sensor provides
exact temperature information to the fire panel.
Specifications
Supply voltage (V dc)
17-28
Quiescent current
250 A
Alarm indication
Red LED
Alarm LED current
2 mA
Normal operating temperature
(no icing)
-20º to +60º C
Rel. humidity (no condensation)
0-95 %
Max. wind (continuous)
Not affected in fixed temp. use
Size of device in base (H x Ø mm) 50 x 100
Ordering Information
DT952 Analogue addressable temperature sensor
DB950 950 series standard base
E
E
E
E
950 series analogue addressable manual callpoint
950 series
A manual call point operating with 950 series protocol.
Ordering Information
DM960 950 series analogue addressable manual callpoint
Passive base address
Programmable slide-in address card
Aesthetic design
EN 54,BOSEC,VdS,CNBOP approved
DM960
Addressable Fire Systems
Page : 62
DI970
Intrinsic safe analogue addressable ionisation detector
970 series
An intrinsic safe ionisation detector, when used with the PT971/2
protocol simulator and GBX70 barrier
Ordering Information
DI970
PT971
PT972
GBX70
DB970
Intrinsic safe analogue addressable ionisation detector
Intrinsic safe protocol translator
Dual channel IS protocol translator
Galvanic barrier (single channel)
Detector base for 970 series intrinsic safe sensors
E
E
E
E
Passive base address
Programmable slide-in address card
Aesthetic design
EN 54,BOSEC,VdS,CNBOP approved
DP971
Intrinsic safe optical detector
970 series
An intrinsic safe optical detector, when used with the PT971/2 protocol
translator and GBX70 barrier
Ordering Information
DP971
PT971
PT972
GBX70
DB970
Intrisic safe optical detector
Intrinsic safe protocol translator
Dual channel IS protocol translator
Galvanic barrier (single channel)
Detector base for 970 series intrinsic safe sensors
E
E
E
E
Passive base address
Programmable slide-in address card
Aesthetic design
EN 54,BOSEC,VdS,CNBOP approved
Addressable Fire Systems
Page : 63
DT972
Intrinsic safe heat detector
970 series
An intrinsic safe heat detector, when used with the PT971/2 protocol
translator and GBX70 barrier
Ordering Information
DT972
PT971
PT972
GBX70
DB970
Intrinsic safe heat detector
Intrinsic safe protocol translator
Dual channel IS protocol translator
Galvanic barrier (single channel)
Detector base for 970 series intrinsic safe sensors
E
E
E
E
Intrinsic safe manual call point
970 series
An intrinsic safe manual call point, when used with the PT971/2
protocol translator and GBX70 barrier.
Ordering Information
DM970 Intrinsic safe manual call point
Passive base address
Programmable slide-in address card
Aesthetic design
EN 54,BOSEC,VdS,CNBOP approved
DM970
Addressable Fire Systems
Page : 64
Intrinsic safe protocol translator
PT971
970 series
A protocol translator for the 970 series analogue addressable intrinsic
safe sensors. This must be used with the GBX70 barrier
Ordering Information
PT971 Intrinsic safe protocol translator
PT972 Dual channel IS protocol translator
Galvanic barrier (single channel)
970 seris
A galvanic barrier used in 970 series intrinsic safe applications. The
GBX70 is used in conjuntion with the PT971 and PT972 protocol
translators.
Ordering Information
GBX70 Galvanic barrier (single channel)
GBX70
Addressable Fire Systems
Page : 65
II950
950 series mini switch monitor unit
950 series
This unit is designed to monitor the state of one or more single pole
switches connected on a single pair of cables.
Specifications
Supply voltage
14-28 Vdc
Current consumption
Quiescent (20kOhm)
1 mA
Alarm
-
Led /relay on
3.5 mA
Switch on surge
3 mA
Switch monitoring
9-11 Vdc
Relay contact rating
-
Operating temperature
-20/+70°C
Relative humidity
0-95%
Ingress protection
IP54
Ordering Information
II950
II950I 950 series mini switch monitor unit
E Loop powered
E Full line: Switch monitors, Zone monitors, Input/output
unit, Output unit, Sounder circuit controller
E LEDs for signalling of I/O and fault condition
E Aesthetically pleasing
II952
950 series switch monitor unit - surface mount
950 series
This unit is designed to monitor the state of one or more single pole
switches connected on a single pair of cables. The circuit will report
open and short-circuit faults.
Specifications
Supply voltage
14-28 Vdc
Current consumption
Quiescent (20kOhm)
730 A
Alarm
Led /relay on
5.6 mA
Switch on surge
2.5 mA
Switch monitoring
9-11 Vdc
Relay contact rating
-
Operating temperature
-20/+70°C
Relative humidity
0-95%
Ingress protection
IP54
Ordering Information
II952 950 series switch monitor unit - surface mount
II953 Switch monitor unit plus - surface mount
E Loop powered
E Full line: Switch monitors, Zone monitors, Input/output
unit, Output unit, Sounder circuit controller
E LEDs for signalling of I/O and fault condition
E Aesthetically pleasing
Addressable Fire Systems
Page : 66
II955
950 series zone monitor unit - surface mount
950 series
The zone monitor powers and controls the operation of a zone of
conventional detectors.
Specifications
Supply voltage
14-28 Vdc
Current consumption
Quiescent (20kOhm)
4 mA
Alarm
11-19 mA
Led /relay on
-
Switch on surge
2.8 mA
Switch monitoring
-
Relay contact rating
-
Operating temperature
-20/+70°C
Relative humidity
0-95%
Ingress protection
IP54
Ordering Information
II955 950 series zone monitor unit - surface mount
E Loop powered
E Full line: Switch monitors, Zone monitors, Input/output
unit, Output unit, Sounder circuit controller
E LEDs for signalling of I/O and fault condition
E Aesthetically pleasing
IO950
950 series single channel IO - surface mount
950 series
This unit provides a loop-powered relay output, a monitored input and
an un-monitored opto-coupled input. It can report fault, switch open
and switch closed condition. It uses the standard housing.
Specifications
Supply voltage
14-28 Vdc
Current consumption
Quiescent (20kOhm)
1.2 mA
Alarm
-
Led /relay on
6 mA
Switch on surge
3.5 mA
Switch monitoring
9-11 Vdc
Relay contact rating
1A@30 Vac/dc
Operating temperature
-20/+70°C
Relative humidity
0-95%
Ingress protection
IP54
Ordering Information
IO950 950 series single channel IO - surface mount
E Loop powered
E Full line: Switch monitors, Zone monitors, Input/output
unit, Output unit, Sounder circuit controller
E LEDs for signalling of I/O and fault condition
E Aesthetically pleasing
Addressable Fire Systems
Page : 67
IO955
950 series output unit - surface mount
950 series
This unit provides a loop-powered relay output
Specifications
Supply voltage
14-28 Vdc
Current consumption
Quiescent (20kOhm)
720 A
Alarm
-
Led /relay on
3.3 mA
Switch on surge
3 mA
Switch monitoring
-
Relay contact rating
1A@30 Vac/dc
Operating temperature
-20/+70°C
Relative humidity
0-95%
Ingress protection
IP54
Ordering Information
IO955 950 series output unit - surface mount
E Loop powered
E Full line: Switch monitors, Zone monitors, Input/output
unit, Output unit, Sounder circuit controller
E LEDs for signalling of I/O and fault condition
E Aesthetically pleasing
IO956
950 series sounder circuit controller - surface mount
950 series
This unit is designed to control a zone of sounders powered by an
external DC supply.
Specifications
Supply voltage
14-28 Vdc
Current consumption
Quiescent (20kOhm)
1.9 mA
Alarm
-
Led /relay on
1.7 mA
Switch on surge
2.6 mA
Switch monitoring
9-11 Vdc
Relay contact rating
-
Operating temperature
-20/+70°C
Relative humidity
0-95%
Ingress protection
IP54
Ordering Information
E Loop powered
E Full line: Switch monitors, Zone monitors, Input/output
unit, Output unit, Sounder circuit controller
IO956 950 series sounder circuit controller - surface mount
E LEDs for signalling of I/O and fault condition
E Aesthetically pleasing
Addressable Fire Systems
Page : 68
950 series loop isolator
Ordering Information
IU950 950 series loop isolator
IU950
Addressable Fire Systems
Page : 69
AS950
950 series loop powered sounder
950 Series
Designed to operate with the 950 series analogue sensors and
monitors, the AS950 loop sounders are addressed and utilise the same
protocol using a very low current.
Specifications
Supply voltage
14 - 28 V dc
Current consumption
Quiescent
140 A at 24 V dc
Switch on surge
1.24 mA for 3 sec.
Operated at 85 dBA
3 mA +/- 0.25 mA
Operated at 92 dBA
8 mA +/- 0.25 mA
Drive frequency
500 - 550 Hz (continuous mode)
Ingress protection
IP43
Operating temperature
-20 to 60 °C
Dimension (dia. x depth)
115 x 25 mm (sounder only)
Weight
115 x 33 mm (sounder with cap)
140 g (sounder only)
145 g (sounder with cap)
Ordering Information
AS950
950 series loop powered sounder
AS950I Loop powered sounder, for use with isolator base
AS950W Loop powered sounder, white cap
E
E
E
E
E
E
Loop powered
Low current consumption
Aritech 950 and Apollo protocol compatible
Continuous or pulsed tone
Sound output 85 - 92 dBA at 1 metre
Reduces wiring and installation cost
Addressable Fire Systems
Page : 70
AS955
950 series high output loop powered sounder
950 Series
Designed to operate with the 950 series analogue sensors and
monitors, the AS955 high output loop sounders are addressed and
utilise the same protocol using a very low current.
Specifications
Supply voltage
14 - 28 V dc
Current consumption
Quiescent
140 A at 24 V dc
Switch on surge
1.24 mA for 3 sec.
Operated
4.5 mA +/- 0.25 mA
Drive frequency
500 - 550 Hz (continuous mode)
Ingress protection
IP43
Operating temperature
-20 to 60 °C
Sound output
100 dB(A)
Ordering Information
AS955 950 series high output loop powered sounder
E
E
E
E
E
E
Loop powered
Low current consumption
950 series protocol
Continuous or pulsed tone
Sound output 100 dB(A) at 1 metre
Reduces wiring and installation cost
Addressable Fire Systems
Page : 71
FD950
950 series loop-powered beam detector
950 Series
A 950 series loop-powered beam detector with a range of up to 100m
long and 15m wide.
Ordering Information
FD950 950 series loop-powered beam detector
E
E
E
E
E
E
E
Loop-powered
950 series compatible with FP1200 and FP2000
Four selectable alarm levels
Drift compensation
Remote interface
Simple wiring
Simple alignment
Addressable Fire Systems
Page : 72
DB950
950 series standard base
950 series
A unique, patented addressing method provides simple, user-friendly
and accurate identification of monitor location whereby a coded card,
inserted in the base, is read by any monitor as it is plugged in.
Ordering Information
DB950 950 series standard base
E
E
E
E
Passive base address
Programmable slide-in address card
Aesthetic design
EN 54,BOSEC,VdS,CNBOP approved
DB951
Base for IU 950
950 series
This base is required for the IU950 isolator
Ordering Information
DB951 Base for IU 950
E
E
E
E
Passive base address
Programmable slide-in address card
Aesthetic design
EN 54,BOSEC,VdS,CNBOP approved
Addressable Fire Systems
Page : 73
DB961
Isolating base (20 devices)
The isolating base senses and isolates short circuit faults on 950 series
loops and spurs. Up to 20 devices may be placed between any two
isolator bases.
Ordering Information
DB961 Isolating base (20 devices)
E
E
E
E
Passive base address
Programmable slide-in address card
Aesthetic design
EN 54,BOSEC,VdS,CNBOP approved
DB970
Detector base for 970 series intrinsic safe sensors
Ordering Information
DB970 Detector base for 970 series intrinsic safe sensors
E
E
E
E
Passive base address
Programmable slide-in address card
Aesthetic design
EN 54,BOSEC,VdS,CNBOP approved
Addressable Fire Systems
Page : 74
Coded cards, addresses 1 - 18
950 series
Precoded Xpert address cards for use in DB9xx bases
Ordering Information
IU980
IU981
IU982
IU983
IU984
IU985
IU986
Coded cards, addresses 1 - 18
Coded cards, addresses 19 - 36
Coded cards addresses 37 - 54
Coded cards, addresses 55 - 72
Coded cards, addresses 73 - 90
Coded cards, addresses 91- 108
Coded cards, addresses 109 - 126
IU980
Conventional Fire Systems
Page : 75
FP202
Conventional fire alarm panel with 2 zones
The FP200 Series microprocessor controlled, conventional fire panels
incorporate state of the art technology, reliability, ease of installation
and maintenance in a basic package. They are compatible with
conventional detectors such as the Aritech Series 300, Series 650 and
Series 700 devices. The FP202 has 2 conventional zones.
Specifications
Supply Voltage
125/230 VAC @ 50/60 Hz
Mains fuse (Type 5x20 mm)
0.5/0.25 A
Total consumption
< 20 W
Nominal Output Voltage
24 VDC
Batteries
Recommended batteries
2 off 1.9 Ah, 12 V
Fuse Rating
1A
Maximum load current
< 100 mA
Zone
Maximum Load
72 mA
Maximum number of
detectors
20
Ouput voltage
22 to 28 VDC
End-of-line resitance
4k7 Ohm
Manual call point resistance
100 Ohm, 2 W
Outputs
Fire alarm
24 VDC ± 15%, 300 mA
Fault alarm (Fail-to-safe)
24 VDC ± 15%, 100 mA
Environmental
Working temperature
+5 to +40°C
Storage temperature
-10 to +70°C
Relative humidity
95 % (non-condencing)
Physical Characteristics
Size (w x h x d)
305 x 295 x 100 mm
Weight without batteries
3 kg
Ordering Information
FP202 Conventional fire alarm panel with 2 zones
E
E
E
E
E
Modern, elegant design
Compact models for 2, 4 and 6 zones
Microprocessor controlled
Multilingual keyboard
2 Access levels
E Differentiation between alarms from manual call points
and automatic detectors in the same zone
E Acoustic indications for fire and fault
E Optical indications for fire and fault by zone
E Low maintenance
E Compatible with all ranges of ARITECH conventional
detectors
Conventional Fire Systems
Page : 76
FP204
Conventional fire alarm panel with 4 zones
The FP200 Series microprocessor controlled, conventional fire panels
incorporate state of the art technology, reliability, ease of installation
and maintenance in a basic package. They are compatible with
conventional detectors such as the Aritech Series 300, Series 650 and
Series 700 devices. The FP204 has 4 conventional zones.
Specifications
Supply Voltage
125/230 VAC @ 50/60 Hz
Mains fuse (Type 5x20 mm)
0.5/0.25 A
Total consumption
< 20 W
Nominal Output Voltage
24 VDC
Batteries
Recommended batteries
2 off 1.9 Ah, 12 V
Fuse Rating
1A
Maximum load current
< 100 mA
Zone
Maximum Load
72 mA
Maximum number of
detectors
20
Ouput voltage
22 to 28 VDC
End-of-line resitance
4k7 Ohm
Manual call point resistance
100 Ohm, 2 W
Outputs
Fire alarm
24 VDC ± 15%, 300 mA
Fault alarm (Fail-to-safe)
24 VDC ± 15%, 100 mA
Environmental
Working temperature
+5 to +40°C
Storage temperature
-10 to +70°C
Relative humidity
95 % (non-condencing)
Physical Characteristics
Size (w x h x d)
305 x 295 x 100 mm
Weight without batteries
3 kg
Ordering Information
FP204 Conventional fire alarm panel with 4 zones
E
E
E
E
E
Modern, elegant design
Compact models for 2, 4 and 6 zones
Microprocessor controlled
Multilingual keyboard
2 Access levels
E Differentiation between alarms from manual call points
and automatic detectors in the same zone
E Acoustic indications for fire and fault
E Optical indications for fire and fault by zone
E Low maintenance
E Compatible with all ranges of ARITECH conventional
detectors
Conventional Fire Systems
Page : 77
FP206
Conventional fire alarm panel with 6 zones
The FP200 Series microprocessor controlled, conventional fire panels
incorporate state of the art technology, reliability, ease of installation
and maintenance in a basic package. They are compatible with
conventional detectors such as the Aritech Series 300, Series 650 and
Series 700 devices. The FP206 has 6 conventional zones.
Specifications
Supply Voltage
125/230 VAC @ 50/60 Hz
Mains fuse (Type 5x20 mm)
0.5/0.25 A
Total consumption
< 20 W
Nominal Output Voltage
24 VDC
Batteries
Recommended batteries
2 off 1.9 Ah, 12 V
Fuse Rating
1A
Maximum load current
< 100 mA
Zone
Maximum Load
72 mA
Maximum number of
detectors
20
Ouput voltage
22 to 28 VDC
End-of-line resitance
4k7 Ohm
Manual call point resistance
100 Ohm, 2 W
Outputs
Fire alarm
24 VDC ± 15%, 300 mA
Fault alarm (Fail-to-safe)
24 VDC ± 15%, 100 mA
Environmental
Working temperature
+5 to +40°C
Storage temperature
-10 to +70°C
Relative humidity
95 % (non-condencing)
Physical Characteristics
Size (w x h x d)
305 x 295 x 100 mm
Weight without batteries
3 kg
Ordering Information
FP206 Conventional fire alarm panel with 6 zones
E
E
E
E
E
Modern, elegant design
Compact models for 2, 4 and 6 zones
Microprocessor controlled
Multilingual keyboard
2 Access levels
E Differentiation between alarms from manual call points
and automatic detectors in the same zone
E Acoustic indications for fire and fault
E Optical indications for fire and fault by zone
E Low maintenance
E Compatible with all ranges of ARITECH conventional
detectors
Conventional Fire Systems
Page : 78
FP402
Conventional fire alarm panel with 2 zones
The FP400 series of conventional fire alarm and extinguishing control
panels is the ideal solution for small to medium-sized installations. Very
powerful and cost-effective, they are extremely simple to install and
use due to their ergonomic, advanced design. The panels come in
elegant, high-quality, conveniently sized, heavy-duty metal enclosures
with space for batteries and finished in high-gloss paint. All panels
have a high-quality keyboard with audible metallic click and good
travel
Specifications
Supply Voltage (+10% - 15%)
230 / 110 VAC @ 50 / 60 Hz
Current Consumption (panel only)
Quiescent
75 mA
Alarm
162 mA
Batteries
Capacity
2 x 2.3 Ah
Fuse rating
2A
Zone
Nominal Voltage
24 VDC
Maximum load
94 mA
Max. number of detectors per 20
zone
Maximum zone resistance
44 ohm
Sounders
Maximum load
250 mA
Delay
Selectable 0 - 9 min
Relay Outputs (excluding
sounders)
1 A @ 30 VDC
Auxilliary Output
250 mA
24 VDC Resetable Output
Maximum load
100 mA
Reset time
3s
Environment
Working temperature
-5°C to +40°C
Relative humidity (non
condencing)
95 %
IP rating
IP30
Physical Characteristics
Size (mm)
297 (w) x 307 (h) x 105 (d)
Weight (without batteries)
3.6 kg
Expansion Module Slots
1
Ordering Information
FP402
Conventional fire alarm panel with 2 zones
RB404
SB404
Relay module, 4 potential free relays for NK700/Fx400 fire panels
Relay module, 4 supervised relays for NK700/Fx400 fire panels
EOL-ACT Active end-of-line device for use with FP400/KL700 fire panels
BS122N Sealed Lead-Acid Battery - 12V 2.2Ah
E
E
E
E
E
E
E
E
E
E
E
E
Modern, attractive design
Microprocessor controlled
From 2 up to 16 zones
EN54 compliant with approvals pending
2 Access levels
2 Monitored sounder outputs
One-man test capability
24 Volt resetable output
External 'class change' facility
Alarm output with potential free relay
General fault output with potential free relay
External watchdog
Conventional Fire Systems
Page : 79
FP408
Conventional fire alarm panel with 8 zones
The FP400 series of conventional fire alarm and extinguishing control
panels is the ideal solution for small to medium-sized installations. Very
powerful and cost-effective, they are extremely simple to install and
use due to their ergonomic, advanced design. The panels come in
elegant, high-quality, conveniently sized, heavy-duty metal enclosures
with space for batteries and finished in high-gloss paint. All panels
have a high-quality keyboard with audible metallic click and good
travel
Specifications
Supply Voltage (+10% - 15%)
230 / 110 VAC @ 50 / 60 Hz
Current Consumption (panel only)
Quiescent
137 mA
Alarm
247 mA
Batteries
Capacity
2 x 7.5 Ah
Fuse rating
5A
Zone
Nominal Voltage
24 VDC
Maximum load
94 mA
Max. number of detectors per 20
zone
Maximum zone resistance
44 ohm
Sounders
Maximum load
250 mA
Delay
Selectable 0 - 9 min
Relay Outputs (excluding
sounders)
1 A @ 30 VDC
Auxilliary Output
250 mA
24 VDC Resetable Output
Maximum load
100 mA
Reset time
3s
Environment
Working temperature
-5°C to +40°C
Relative humidity (non
condencing)
95 %
IP rating
IP30
Physical Characteristics
Size (mm)
420 (w) x 335 (h) x 110 (d)
Weight (without batteries)
6.2 kg
Expansion Module Slots
4
Ordering Information
FP408
Conventional fire alarm panel with 8 zones
RB404
SB404
Relay module, 4 potential free relays for NK700/Fx400 fire panels
Relay module, 4 supervised relays for NK700/Fx400 fire panels
EOL-ACT Active end-of-line device for use with FP400/KL700 fire panels
BS127N Sealed Lead-Acid Battery - 12V 7.2Ah
E
E
E
E
E
E
E
E
E
E
E
E
Modern, attractive design
Microprocessor controlled
From 2 up to 16 zones
EN54 compliant with approvals pending
2 Access levels
2 Monitored sounder outputs
One-man test capability
24 Volt resetable output
External 'class change' facility
Alarm output with potential free relay
General fault output with potential free relay
External watchdog
Conventional Fire Systems
Page : 80
FP412
Conventional fire alarm panel with 12 zones
The FP400 series of conventional fire alarm and extinguishing control
panels is the ideal solution for small to medium-sized installations. Very
powerful and cost-effective, they are extremely simple to install and
use due to their ergonomic, advanced design. The panels come in
elegant, high-quality, conveniently sized, heavy-duty metal enclosures
with space for batteries and finished in high-gloss paint. All panels
have a high-quality keyboard with audible metallic click and good
travel
Specifications
Supply Voltage (+10% - 15%)
230 / 110 VAC @ 50 / 60 Hz
Current Consumption (panel only)
Quiescent
137 mA
Alarm
247 mA
Batteries
Capacity
2 x 7.5 Ah
Fuse rating
5A
Zone
Nominal Voltage
24 VDC
Maximum load
94 mA
Max. number of detectors per 20
zone
Maximum zone resistance
44 ohm
Sounders
Maximum load
250 mA
Delay
Selectable 0 - 9 min
Relay Outputs (excluding
sounders)
1 A @ 30 VDC
Auxilliary Output
250 mA
24 VDC Resetable Output
Maximum load
100 mA
Reset time
3s
Environment
Working temperature
-5°C to +40°C
Relative humidity (non
condencing)
95 %
IP rating
IP30
Physical Characteristics
Size (mm)
420 (w) x 335 (h) x 110 (d)
Weight (without batteries)
6.2 kg
Expansion Module Slots
4
Ordering Information
FP412 Conventional fire alarm panel with 12 zones
E
E
E
E
E
E
E
E
E
E
E
E
Modern, attractive design
Microprocessor controlled
From 2 up to 16 zones
EN54 compliant with approvals pending
2 Access levels
2 Monitored sounder outputs
One-man test capability
24 Volt resetable output
External 'class change' facility
Alarm output with potential free relay
General fault output with potential free relay
External watchdog
Conventional Fire Systems
Page : 81
FP416
Conventional fire alarm panel with 16 zones
The FP400 series of conventional fire alarm and extinguishing control
panels is the ideal solution for small to medium-sized installations. Very
powerful and cost-effective, they are extremely simple to install and
use due to their ergonomic, advanced design. The panels come in
elegant, high-quality, conveniently sized, heavy-duty metal enclosures
with space for batteries and finished in high-gloss paint. All panels
have a high-quality keyboard with audible metallic click and good
travel
Specifications
Supply Voltage (+10% - 15%)
230 / 110 VAC @ 50 / 60 Hz
Current Consumption (panel only)
Quiescent
137 mA
Alarm
247 mA
Batteries
Capacity
2 x 7.5 Ah
Fuse rating
5A
Zone
Nominal Voltage
24 VDC
Maximum load
94 mA
Max. number of detectors per 20
zone
Maximum zone resistance
44 ohm
Sounders
Maximum load
250 mA
Delay
Selectable 0 - 9 min
Relay Outputs (excluding
sounders)
1 A @ 30 VDC
Auxilliary Output
250 mA
24 VDC Resetable Output
Maximum load
100 mA
Reset time
3s
Environment
Working temperature
-5°C to +40°C
Relative humidity (non
condencing)
95 %
IP rating
IP30
Physical Characteristics
Size (mm)
420 (w) x 335 (h) x 110 (d)
Weight (without batteries)
6.2 kg
Expansion Module Slots
4
Ordering Information
FP416 Conventional fire alarm panel with 16 zones
E
E
E
E
E
E
E
E
E
E
E
E
Modern, attractive design
Microprocessor controlled
From 2 up to 16 zones
EN54 compliant with approvals pending
2 Access levels
2 Monitored sounder outputs
One-man test capability
24 Volt resetable output
External 'class change' facility
Alarm output with potential free relay
General fault output with potential free relay
External watchdog
Conventional Fire Systems
Page : 82
RB404
Relay module, 4 potential free relays for NK700/Fx400 fire panels
The RB404 relay expander module provides 4 additional voltage free
relays on the GE Security NK700/FP400/FEC400 conventional fire
panels ranges. It allows for these relays to be allocated to individual
detection zones, or for programming the activation of different relays
depending on the status of one or more zones. Up to 4 of these
modules may be used on every fire panel.
Specifications
Relay rating
Voltage
250 VAC / 30 VDC
Current
10 A
Delay setting
0 to 9 minutes
Ordering Information
RB404 Relay module, 4 potential free relays for NK700/Fx400 fire panels
E 4 Potential free relays
E Up to 4 modules may be housed inside the fire panel
cabinet
E Programmable with basic boolen functions
E Power supplied from fire panel bus
E Output delay setting per relay
Conventional Fire Systems
Page : 83
SB404
Relay module, 4 supervised relays for NK700/Fx400 fire panels
The SB404 expander module provides 4 additional supervised relays
that provide 24 VDC outputs on the GE Security NK700/FP400/FEC400
conventional fire panels ranges. These relays may be configured to
power sounders or as standard 24 VDC supervised outputs for other
devices. Relays may be allocated to individual detection zones, or for
programming the activation of different relays depending on the status
of one or more zones. Up to 4 of these modules
may be used on every fire panel.
Specifications
Auxiliary supply
24 VDC
Relay Rating
Voltage
250 VAC / 30 VDC
Current
5A
Delay setting
0 to 9 minutes
Ordering Information
SB404 Relay module, 4 supervised relays for NK700/Fx400 fire panels
E 4 Supervised relays
E Up to 4 modules may be housed inside the fire panel
cabinet
E Programmable with basic boolen functions
E Output delay setting per relay
E Configurable for sounder control or as supervised
outputs
Conventional Fire Systems
Page : 84
FEC403
Conventional extinguishing control panel with 3 zones
The FP400 series of conventional fire alarm and extinguishing control
panels is the ideal solution for small to medium-sized installations. Very
powerful and cost-effective, they are extremely simple to install and
use due to their ergonomic, advanced design. The panels come in
elegant, high-quality, conveniently sized, heavy-duty metal enclosures
with space for batteries and finished in high-gloss paint. All panels
have a high-quality keyboard with audible metallic click and good
travel
Specifications
Supply Voltage (+10% - 15%)
230 / 110 VAC @ 50 / 60 Hz
Batteries
Capacity
2 x 7 Ah
Fuse rating
2A
Zone
Maximum load
94 mA
Max. number of detectors per 20
zone
Maximum zone resistance
44 ohm
Sounders
Maximum load
250 mA
Delay
Selectable 0 - 9 min
Relay Outputs (excluding
sounders)
1 A @ 30 VDC
Extinguishing Relay Outputs
Maximum load
350 mA
Fuse rating
1A
Auxilliary Output
250 mA
24 VDC Resetable Output
Maximum Load
100 mA
Reset time
3s
Environment
Working temperature
-5°C to +40°C
Relative humidity (non
condencing)
95 %
IP rating
IP30
Physical Characteristics
Size (mm)
420 (w) x 335 (h) x 110 (d)
Weight (without batteries)
6.2 kg
Ordering Information
FEC403 Conventional extinguishing control panel with 3 zones
E
E
E
E
E
E
E
E
E
E
E
E
E
Modern, attractive design
Microprocessor controlled
3 zone (1 ext. area) and 6 zone (2 ext. areas) available
Automatic extinguishing agent release control
2 Access levels
Supervised general sounder output
Supervised extinguishing inputs and outputs
One-man test capability
24 Volt resetable output
External 'class change' facility
Alarm output with potential free relay
General fault output with potential free relay
External watchdog
Conventional Fire Systems
Page : 85
FEC406
Conventional extinguishing control panel with 6 zones
The FP400 series of conventional fire alarm and extinguishing control
panels is the ideal solution for small to medium-sized installations. Very
powerful and cost-effective, they are extremely simple to install and
use due to their ergonomic, advanced design. The panels come in
elegant, high-quality, conveniently sized, heavy-duty metal enclosures
with space for batteries and finished in high-gloss paint. All panels
have a high-quality keyboard with audible metallic click and good
travel
Specifications
Supply Voltage (+10% - 15%)
230 / 110 VAC @ 50 / 60 Hz
Batteries
Capacity
2 x 7 Ah
Fuse rating
2A
Zone
Maximum load
94 mA
Max. number of detectors per 20
zone
Maximum zone resistance
44 ohm
Sounders
Maximum load
250 mA
Delay
Selectable 0 - 9 min
Relay Outputs (excluding
sounders)
1 A @ 30 VDC
Extinguishing Relay Outputs
Maximum load
350 mA
Fuse rating
1A
Auxilliary Output
250 mA
24 VDC Resetable Output
Maximum Load
100 mA
Reset time
3s
Environment
Working temperature
-5°C to +40°C
Relative humidity (non
condencing)
95 %
IP rating
IP30
Physical Characteristics
Size (mm)
420 (w) x 335 (h) x 110 (d)
Weight (without batteries)
6.2 kg
Ordering Information
FEC406 Conventional extinguishing control panel with 6 zones
E
E
E
E
E
E
E
E
E
E
E
E
E
Modern, attractive design
Microprocessor controlled
3 zone (1 ext. area) and 6 zone (2 ext. areas) available
Automatic extinguishing agent release control
2 Access levels
Supervised general sounder output
Supervised extinguishing inputs and outputs
One-man test capability
24 Volt resetable output
External 'class change' facility
Alarm output with potential free relay
General fault output with potential free relay
External watchdog
Conventional Fire Systems
Page : 86
FP604
4-zone Conventional Fire Panel
The FP 604 fire panel is designed using the latest technologies and is
compatible with most brands of conventional fire detectors. The FP 604
is a 4-zone panel which is extendable up to 6 zones.
Specifications
Supply voltage
230 V (± 10% - 50 Hz ± 5%)
Total current 12 V dc (no charge), 80 mA
quiescent
Total current 24 V dc (no charge), 90 mA
quiescent
Auxiliary output
100 mA - 12 V dc
Battery back-up for 72 hrs
1 x 12 V - 7.2 Ah battery
Battery charger fuse
2A
Battery charger voltage
13.8 V
Bells - Fire Brigade fuse
315 mA
Dimensions
390 x 315 x 85 mm
Ordering Information
FP604 4-zone Conventional Fire Panel
ZI602 Two zone extension board, including 6 outputs
RC606 Set of 6 bi-stable magnetic latch relays
E
E
E
E
E
E
E
E
E
E
E
E
E
E
One man maintenance
Alarm verification
Individual zone alarm outputs
One 12 V back-up battery
12 V dc auxiliary output
4 - 6 zones
Mixed zone capability
Head removal option
Sirens output 12 or 24 V dc
Microprocessor based
EN 54 p2/4 approved
LPCB certified
Optional third source
Optional digital dialler
Conventional Fire Systems
Page : 87
Two zone extension board, including 6 outputs
ZI602
This board extends the FP604 from 4 zones to 6 zones. It also provides
6 outputs for the 6 zones.
Ordering Information
ZI602 Two zone extension board, including 6 outputs
Set of 6 bi-stable magnetic latch relays
A set of 6 relays for the ZI602 zone extension board
Ordering Information
RC606 Set of 6 bi-stable magnetic latch relays
RC606
Conventional Fire Systems
Page : 88
FP708
Fire panel equipped with 8 zones
FP700 series
A set of four conventional fire panels. The FP708 and FP708C are 8
zone non-expandable fire panels. The FP740 and FP740C are 8 zone
expandable to 40 zones. The FP708C and FP740C have an alarm
counter. All panels can use the full range of LON700 output boards.
Specifications
Dimensions (W x H x D)
444 x 340 x110 mm
Weight (no batteries)
5.5 kg
Supply voltage (see engineering 230 V ac; 1,5 A; 50 Hz
guide)
Quiescent current @20
devices/zone
210 mA (8 zones)
Batteries for 24 hrs (in housing)
7.2 Ah
Batteries for 72 hrs
17 Ah
Battery charger rating
1.4 A max
Nominal battery charger voltage 27,6 V
@ 25°C
Auxiliary output 1
21 - 29,4 V dc; 1.2 A max.
Auxiliary output 2
11.5 - 12.5 V dc; 0.4 A max.
Total 24 V output (no charging)
3,5 A max
Sounder/warning
0,5 A, 19-31 V dc, polarity reversal
Evacuation/Fire brigade
0,5 A, 19-31 V dc, polarity reversal
Fault and Fire protection relay
rating
2 A, @ 42 V
RS 232 port
19200 baud, DB9, 1 start, 8 data, 1 stop, no parity
Ordering Information
FP708
FP708C
FP740
FP740C
Fire panel equipped with 8 zones
Fire panel equipped with 8 zones including alarm counter
Fire panel equipped with 8 zones expandable up to 40 zones
Fire panel equipped with 8 zones exp. to 40 including alarm counter
E
E
E
E
E
E
E
E
E
E
E
Fully modular
LON based network
One-man maintenance
Alarm verification
700 series detectors Clean Me® detection
Various output boards
EN54 approved and BOSEC certified
Modular up to 40 zones
Full line of repeaters
Microprocessor based
Local and remote control
Conventional Fire Systems
Page : 89
FR708
Repeater 8 zones, 24 VDC input
FR700 series
The repeaters provide different solutions - 24 volt input and 230 volt
input using the PS700 power supply. The FR708 is 8 zones non
expandable and the FR740 is 8 zones expandable to 40 zones. The
FR700 repeaters connect to the FP700 fire panel with the LON 700 bus.
The FR708V230 and FR740V230 include a card cage for LON board
expansion and have a PS700 power supply.
Ordering Information
FR708
FR708V230
FR740
FR740V230
Repeater 8 zones, 24 VDC input
Repeater 8 zones with card cage and PS700 PSU (230V input)
Repeater 8 zones, expandable up to 40 zones, 24 VDC input
Repeater 8 zones, exp to 40 zones with card cage and PS700 PSU (230V)
E
E
E
E
E
E
E
Fully modular
Echelon based network
Various output boards
Modular up to 40 zones
Full line of repeaters
Microprocessor based
Local and remote control
Conventional Fire Systems
Page : 90
8 zone indicator LED extension board fire/fault
FP700 series
This zone indicator extension board is used to expand the FP740 and
FR740 front panel indications.
Ordering Information
ZE708 8 zone indicator LED extension board fire/fault
ZE708
LON700 Devices
Page : 91
8 zone input extension board
The ZI708 is an eight zone input expansion board for LON700
compatible systems. It allows for the connection of up to 8
conventional fire detector zones and is compatible with most industry
standard conventional detectors.
Ordering Information
ZI708 8 zone input extension board
ZI708
Conventional Fire Systems
Page : 92
Synoptic driver for 80 LEDs and common signals
LON 700 series
A LON700 output board to display LED's. It can be self-standing as well
as plugging into a card cage.
Specifications
Dimensions mm (L x W x D)
150x30x60
Weight
200 g
Operating temp °C
-5°C - +40
Operating voltage Vdc
19 - 30
Current consumption
max quiesent mA
30
power consumption per LED 40
(mW)
Bus Connection
FP1200/FP2000 (with
LON2000)
***
FP700 (direct connection)
***
Bus Cable
Cat 5
Total number of repeaters
FP1200/FP2000
15
FP700
8
Ordering Information
FM740 Synoptic driver for 80 LEDs and common signals
FM740
LON700 Devices
Page : 93
LON700 output board with 24 open collector outputs
OCB724
The OCB724 is a 24 way open collector board used in a LON700
system.
Ordering Information
OCB724 LON700 output board with 24 open collector outputs
LON700 output board with 8 relays
The RB708 is an eight way relay board used in LON700 systems.
Specifications
Number of outputs
8
Relay contact rating
Switching current
2A
Switching volage
42V ac/dc
Switching power
60W
Ordering Information
RB708 LON700 output board with 8 relays
RB708
LON700 Devices
Page : 94
LON700 output board with 8 supervised outputs
The SOB708 provides eight supervised outputs that can be used in
LON700 systems.
Specifications
Number of outputs
8
Output type
polarity reversal
End of line resistor
5.6 Kohm
Output current per output
500mA
Total current for all outputs
2A
Open circuit
>27 Kohm
Normal
1.2 - 18 Kohm
Short circuit
< 470 ohm
Ordering Information
SOB708 LON700 output board with 8 supervised outputs
SOB708
Conventional Fire Systems
Page : 95
FB708
FP700 black box with 7 slot card cage
LON700 series
The FB708 and FB740 'black boxes' allow for the distribution of LON700
input / output units. When used with the NC700 or FM740, the FB7xx is
connected to the FP700 / FP2000 firepanels with the LON700 bus.
Ordering Information
FB708 FP700 black box with 7 slot card cage
FB740 FP700 black box with 11 slot card cage and PS700
NC700 LON700 interface board
E
E
E
E
E
E
E
Fully modular
Echelon based network
Various output boards
Microprocessor based
Local and remote control
For fire panel distributed systems
7 slot card cage or 11 slot card cage with power supply
LON700 Devices
Page : 96
LON700 interface board
NC700
The NC700 is an interface board to connect a LON700 bus from a fire
panel to a FB7xx 'black box'.
Ordering Information
NC700 LON700 interface board
Plug-in power supply 3.5 A
The PS700 power supply can be used to extend the power output in
LON700 systems.
Ordering Information
PS700 Plug-in power supply 3.5 A
PS700
Addressable Fire Systems
Page : 97
FP1501
Analogue addressable fire detection panel - 1 loop
The FP1501 1 loop analogue addressable fire alarm control panel is the
ideal solution for small to medium-sized installations. Very powerful
and cost-effective, it is extremely simple to install and use due to is
ergonomic, advanced design. The panel is supplied in an elegant,
high-quality, conveniently sized, heavy-duty enclosure. It has a
high-quality keyboard with audible metallic click and good travel.
Specifications
Supply Voltage
110 VAC @ 50 Hz or 230 VAC @ 50 Hz (+10% -15%)
Current Consumption
175 mA Quiescent / 241 mA in alarm with no devices
connected
Batteries
Capacity
2 x 12 V - 7 AH (SLA type)
Fuse Rating
3A
Charger Rating
350 mA @ 27.6 VDC @ 20 °C (Temperature
compensated -3 V / °C)
Loop characteristics per loop
Capacity
250 addresses per loop
Maximum Load
400 mA / 26 VDC to 32 VDC
Maximum Electrical
Characteristics
44 Ohm / 500 nF approximately 2 km of 1.5 mm2
diameter cable
Sounders (reverse polarity
supervision)
Maximum Load
Delays
Relay Outputs (potential free)
250 mA each (2 Sounder outputs available) / 18 VDC
to 24 VDC
10 seconds to 600 seconds, software adjustable in 10
second intervals
1 A @ 30 VDC
24 V Auxiliary Output
Maximum Load
250 mA @ 18 VDC to 28 VDC
Environment
Working Temperature
-5°C to +40 °C
Relative Humidity
0-95% non-condensing
IP Rating
IP30
Physical Characteristics
Size
420 mm (w) x 335 (h) x 110 (d)
Weight
6.2 kg without batteries / 10.7 kg with 2 x 7 Ah
batteries
Ordering Information
FP1501 Analogue addressable fire detection panel - 1 loop
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
One and two loop control panels
4 x 40 characters LCD display
20 Display zones
EN54 approved
2 User access levels
2 Monitored sounder outputs
2 Programmable voltage free relays
24 Volt auxiliary output
I/O programming capabilities with Boolean functions
Day/night sensitivity settings
Coincidence within zones
Installation test capability
Full networking capabilities up to 10 nodes
2-wire RS485 communications network
Industry standard RS232 communications port
Easy up/download programming from a standard PC
Graphic PC software
Addressable Fire Systems
Page : 98
FP1502
Analogue addressable fire detection panel - 2 loops
The FP1500 series analogue addressable fire alarm control panels is
the ideal solution for small to medium-sized installations. Very powerful
and cost-effective, they are extremely simple to install and use due to
their ergonomic, advanced design.
The panels are supplied in an elegant, high-quality, conveniently sized,
heavy-duty metal enclosure and are finished in a high-gloss paint. All
panels have a high-quality keyboard with audible metallic click and
good travel.
The batteries for the system may be housed inside the cabinet.
Specifications
Supply Voltage
110 VAC @ 50 Hz or 230 VAC @ 50 Hz (+10% -15%)
Current Consumption
175 mA Quiescent / 241 mA in alarm with no devices
connected
Batteries
Capacity
2 x 12 V - 7 AH (SLA type)
Fuse Rating
3A
Charger Rating
350 mA @ 27.6 VDC @ 20 °C (Temperature
compensated -3 V / °C)
Loop characteristics per loop
Capacity
250 addresses per loop
Maximum Load
400 mA / 26 VDC to 32 VDC
Maximum Electrical
Characteristics
44 Ohm / 500 nF approximately 2 km of 1.5 mm2
diameter cable
Sounders (reverse polarity
supervision)
Maximum Load
Delays
Relay Outputs (potential free)
250 mA each (2 Sounder outputs available) / 18 VDC
to 24 VDC
10 seconds to 600 seconds, software adjustable in 10
second intervals
1 A @ 30 VDC
24 V Auxiliary Output
Maximum Load
250 mA @ 18 VDC to 28 VDC
Environment
Working Temperature
-5°C to +40 °C
Relative Humidity
0-95% non-condensing
IP Rating
IP30
Physical Characteristics
Size
420 mm (w) x 335 (h) x 110 (d)
Weight
6.2 kg without batteries / 10.7 kg with 2 x 7 Ah
batteries
Ordering Information
FP1502 Analogue addressable fire detection panel - 2 loops
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
One and two loop control panels
4 x 40 characters LCD display
20 Display zones
EN54 approved
2 User access levels
2 Monitored sounder outputs
2 Programmable voltage free relays
24 Volt auxiliary output
I/O programming capabilities with Boolean functions
Day/night sensitivity settings
Coincidence within zones
Installation test capability
Full networking capabilities up to 10 nodes
2-wire RS485 communications network
Industry standard RS232 communications port
Easy up/download programming from a standard PC
Graphic PC software
Addressable Fire Systems
Page : 99
NC785
RS485 expansion kit for KSA701/FP1500 fire panels
The NC785 RS485 expander allows for an easy upgrade to the
KSA701/FP1500 series addressable fire panels. Each module adds an
additional industry standard RS485 communication port to the panel.
This port could be used for communications with other network nodes
in the fire panel network.
Specifications
Number of ports
1
Communications medium
RS485
Technical specifications
Maximum cable length
1200 m
Communication speed
9600 baud
Cable
CAT5 - twisted with screen
Termination resistance
150 Ohm
Ordering Information
NC785 RS485 expansion kit for KSA701/FP1500 fire panels
E Industry standard RS485 communications
E No hardware configuration required
Addressable Fire Systems
Page : 100
FR1500
Analogue addressable LCD Repeater/Emulator (AC Powered)
The FP1500 Series analogue addressable fire alarm panels are the
ideal solution for small to medium-sized installations. Very powerful
and cost-effective, they are easy to install and use due to their
ergonomic, advanced design. The FR1500 LCD repeater is supplied in
the same enclosure as the FP1500.
Specifications
Supply Voltage
AC Version
110 VAC @ 50 Hz or 230 VAC @ 50 Hz (+10% -15%)
DC Version
24 VDC
Current Consumption
175 mA Quiescent / 200 mA in alarm
Battery Charger (AC Version only)
Capacity
2 x 12 V - 7 AH (SLA type)
Fuse Rating
3A
Charger Rating
350 mA @ 27.6 VDC @ 20 °C (Temperature
compensated -3 V / °C)
Environment
Working Temperature
-5°C to +40 °C
Relative Humidity
0-95% non-condensing
IP Rating
IP30
Physical Characteristics
Size
420 mm (w) x 335 (h) x 110 (d)
Weight
6.2 kg without batteries / 10.7 kg with 2 x 7 Ah
batteries
RS232 and RS485 standard
Communication Ports
Ordering Information
FR1500 Analogue addressable LCD Repeater/Emulator (AC Powered)
E
E
E
E
E
E
E
E
Modern, attractive design
4 x 40 characters LCD display
20 Display zones
EN54 compliant with approvals pending
3 User access levels
24 VDC or 230 VAC models available
Panel networking
Full system control
Addressable Fire Systems
Page : 101
MODGSM
GSM Modem for KSA700/FP1500 Series Fire Panels
The MODGSM modem may be used in KSA701/FP1500, KSA702 and
KSA705 fire panel from GE-Interlogix. It is ideal for use as a standard
modem for making and receiving calls from and to the fire panel, but
may also be used for GSM messaging.
Specifications
GSM Band
900/1800 MHz
Services
Data, SMS, Voice and Fax
AT Commands
GSM 07.07 and 07.05
Output Power (max)
GSM900
2W
GSM1800
1W
Input Voltage
5 to 32 V
Current @ 5V
Avarage
330 mA
Peak
1.8 A
SIM Interface
3V / 5V
Dimensions (h x w x d)
98 x 54 x 25 mm
Weight
130 g
Environmental Temperature
Storage
- 25 °C to + 70 °C
Operating
- 20 °C to + 55 °C
Ordering Information
MODGSM GSM Modem for KSA700/FP1500 Series Fire Panels
E
E
E
E
Dual-Band 900/1800 MHz
Data and SMS services
Remote control by AT commands
Wide input voltage range
Addressable Fire Systems
Page : 102
Graphic Software for KSA700/FP1500 Fire Systems (1 panel-2 loops)
PCG-Graphic102
The PCG-Config series consists of 3 software applications. The
individual software formats allows the graphic package to grow with
the installation. PCG-Config102 operates with a single panel and allows
for the configuration of all devices up to a maximum of two loops.
Specifications
Hardware requirements
Communication
RS232, modem and/or TCP/IP
Display
SVGA or higher resolution
Hard disk
2 Gb with 650 Mb free space
Keyboard
Required
Pointing device
Required
Printer
System printer required for printing
Processor
1 GHz or higher Pentium III-compatible CPU
RAM
256 Mb or more
Removable media
1.44 Mb stiffy and CD-ROM or DVD drive
Software requirements
Operating system
Windows '98 or Windows 2000
Ordering Information
E Bi-directional communication with single panels and
networked fire systems
PCG-Graphic102 Graphic Software for KSA700/FP1500 Fire Systems (1 panel-2 loops)
E
E
E
E
E
E
E
E
E
Local or remote connection via modem or TCP/IP
Large selection of user configurable icons
Visualises device alarms and status of in- and outputs
Event texts retrieval from the panel
Configurator and operator contol levels
Navigation buttons allowed
Event logs with reporting facilities
Basic drawing package included
Imports bmp & drw format graphics
Addressable Fire Systems
Page : 103
PCG-GraphicNW
Graphic Software for KSA700/FP1500 Fire Systems (multi-panel)
The PCG-Config series consists of 3 software applications. The
individual software formats allows the graphic package to grow with
the installation. PCG-ConfigNW allows for monitoring on networked
systems with multiple panels.
Specifications
Hardware requirements
Communication
RS232, modem and/or TCP/IP
Display
SVGA or higher resolution
Hard disk
2 Gb with 650 Mb free space
Keyboard
Required
Pointing device
Required
Printer
System printer required for printing
Processor
1 GHz or higher Pentium III-compatible CPU
RAM
256 Mb or more
Removable media
1.44 Mb stiffy and CD-ROM or DVD drive
Software requirements
Operating system
Windows '98 or Windows 2000
Ordering Information
E Bi-directional communication with single panels and
networked fire systems
PCG-GraphicNW Graphic Software for KSA700/FP1500 Fire Systems (multi-panel)
E
E
E
E
E
E
E
E
E
Local or remote connection via modem or TCP/IP
Large selection of user configurable icons
Visualises device alarms and status of in- and outputs
Event texts retrieval from the panel
Configurator and operator contol levels
Navigation buttons allowed
Event logs with reporting facilities
Basic drawing package included
Imports bmp & drw format graphics
Addressable Fire Systems
Page : 104
FP1216EN
Analogue addressable fire panel 2 - 4 loops, 16 zones
The FP1216EN is a versatile, cost effective analogue addressable fire
panel with 2 to 4 loops and powerfull I/O features. It supports all the
LON700 devices and repeaters, and can be optionally upgraded to
provide full networking. The FP1216EN is truly user friendly and
provides a generous 8 x 40 graphic, backlit display. I/O control is done
via the powerful FP2000/FP1200 series boolean I/O programing
module. Extensive maintenance features are provided standard. The
FP1216EN supports both 2000 and 900 series sensors and I/O units.
Specifications
Supply voltage
230 V ac (+10/-15%)
Min. supply current @ 24 VDC
50 Hz
220 VA
0.2 A
Battery charger rating @ 27.6
VDC
1.6 A
Total supply rating @ 27.6 VDC
4A
Relay rating @ 24 VDC
2A
Weight (no batteries)
7.5 kg
Dimensions (h x w x d)
440 x 444 x 125 mm
Ordering Information
FP1216EN
Analogue addressable fire panel 2 - 4 loops, 16 zones
FR2000
LCD repeater with emulator functions
FP-RIM1270
LC2002
LON2000
MOD2000
NC2011
NC2051
NE2011
NE2051
Rim surround for the 780 and 1200N series fire panel boxes
2-loop extension board for FP1200 / FP2000 fire panels
LON700 driver for FP1200 / FP2000
Modem kit
ARCNET RS485 network card with single RS485 interface
ARCNET network card with single optical interface board
RS485 network extension board
Fibre optic network extension board
PCG-N
PCG-S
PCC2000
PCM2000
Graphics package network application with copy protection key
Graphics package with copy protection key
Programming and configuration software
Maintenance and support software with copy protection key
E
E
E
E
E
E
E
One man maintenance
Soak test
On-line diagnostics and statistics
Power supply for 72 hour autonomy
Floating background for 2000 series sensors
Coincidence within and in between zones
Start-up default mode
E Upload/download, remote maintenance and graphic PC
software
E
E
E
E
E
I/O programming including Boolean functions
EN 54 p2 & 4 approved
Bosec certified
2 or 4 class A loops
Full range of LON700 devices
Addressable Fire Systems
Page : 105
FP2416
Analogue addressable fire panel 2 - 4 loops, 16 zones
FP2000 Series
A versatile, powerful analogue addressable fire panel, 2 to 4 loops, 16
displayed zones with extensive I/O features. The fire panel can operate
within a 31 panel network and can communicate with global repeaters
and PC grahics. It also supports all the LON700 devices and repeaters
using a seperate two wire bus. The FP2000 series is truly user-friendly,
and provides a generous 8 x 40 backlit graphic display. I/O control is
done via the powerful FP2000/FP1200 series boolean I/O programing
module. Extensive maintenance features are provided standard. The
FP2000 series supports both 2000 and 900 series sensors and I/O units.
Specifications
Supply voltage 1
190 - 270 V ac
Supply voltage 2
40- 60 Hz
160 VA max.
21 - 27 V dc
Current consumption
Quiescent @ 24 V dc (equipped
loop)
500 mA
Alarm current @ 24 V dc
600 mA
Available auxiliary current in
alarm
3.4 A
Battery charger rating @ 27.5 V
dc
3A
Total supply rating @ 27.5 V dc
4A
Relay rating @ 24 V dc
2A
Weight (no batteries)
11 kg
Dimensions (mm) (H x W x D)
609 x 441 x 109
Ordering Information
FP2416
FR2000
LC2002
NC2011
NC2051
NE2011
NE2051
LON2000
LON700
FRL700
MOD2000
PCM2000
PCC2000
PCG Series
PR2000
Analogue addressable fire panel 2 - 4 loops, 16 zones
LCD repeater with emulator functions
2-loop extension board for FP1200 / FP2000 fire panels
ARCNET RS485 network card with single RS485 interface
ARCNET network card with single optical interface board
RS485 network extension board
Fibre optic network extension board
LON700 driver for FP1200 / FP2000
2 wire repeaters
LCD repeater
Modem kit
Maintenance and support software with copy protection key
Programming and configuration software
PC Graphic Software Packages for Aritech Fire Sytems
Internal printer
E
E
E
E
E
E
E
E
E
E
E
E
One man maintenance
Graphic maintenance
Maintenance warning
Service reminder signal
Soak test
On-line diagnostics and statistics
Floating background
Day/night sensitivity setting
Coincidence within and in between zones
Automatic timed and manual on/off zones
Start-up default mode
Service switch
E Upload/download, remote maintenance and graphic PC
software
E
E
E
E
E
E
I/O programming including Boolean functions
ARCNET panel networking
EN54 approved, certified Bosec, VdS, NFA2P
Networkable "black box" and "global zone" system
Full range of repeater panels
Full range of LON700 devices
Addressable Fire Systems
Page : 106
FP2432
Analogue addressable fire panel 2 - 4 loops, 16 - 32 zones
FP2000 Series
A versatile, powerful analogue addressable fire panel, 2 to 4 loops, 16
to 32 displayed zones with extensive I/O features. The fire panel can
operate within a 31 panel network and can communicate with global
repeaters and PC grahics. It also supports all the LON700 devices and
repeaters using a seperate two wire bus. The FP2000 series is truly
user-friendly, and provides a generous 8 x 40 backlit graphic display.
I/O control is done via the powerful FP2000/FP1200 series boolean I/O
programing module. Extensive maintenance features are provided
standard. The FP2000 series supports both 2000 and 900 series
sensors and I/O units.
Specifications
Supply voltage 1
190 - 270 V ac
Supply voltage 2
40- 60 Hz
160 VA max.
21 - 27 V dc
Current consumption
Quiescent @ 24 V dc (equipped
loop)
500 mA
Alarm current @ 24 V dc
600 mA
Available auxiliary current in
alarm
3.4 A
Battery charger rating @ 27.5 V
dc
3A
Total supply rating @ 27.5 V dc
4A
Relay rating @ 24 V dc
2A
Weight (no batteries)
11 kg
Dimensions (mm H x W x D)
609 x 441 x 109
Ordering Information
FP2432
FR2000
LC2002
ZE2016
NC2011
NC2051
NE2011
NE2051
LON2000
LON700
FRL700
MOD2000
PCM2000
PCC2000
PCG Series
Analogue addressable fire panel 2 - 4 loops, 16 - 32 zones
LCD repeater with emulator functions
2-loop extension board for FP1200 / FP2000 fire panels
16-zone LED extension fire and fault LED
ARCNET RS485 network card with single RS485 interface
ARCNET network card with single optical interface board
RS485 network extension board
Fibre optic network extension board
LON700 driver for FP1200 / FP2000
2 wire repeaters
LCD repeater
Modem kit
Maintenance and support software with copy protection key
Programming and configuration software
PC Graphic Software Packages for Aritech Fire Sytems
E
E
E
E
E
E
E
E
E
E
E
E
One man maintenance
Graphic maintenance
Maintenance warning
Service reminder signal
Soak test
On-line diagnostics and statistics
Floating background
Day/night sensitivity setting
Coincidence within and in between zones
Automatic timed and manual on/off zones
Start-up default mode
Service switch
E Upload/download, remote maintenance and graphic PC
software
E
E
E
E
E
E
I/O programming including Boolean functions
ARCNET panel networking
EN54 approved, certified Bosec, VdS, NFA2P
Networkable "black box" and "global zone" system
Full range of repeater panels
Full range of LON700 devices
Addressable Fire Systems
Page : 107
FP2864
Analogue addressable fire panel, 2 - 8 loops, 16 - 64 zones
The FP2864 is a versatile, powerful analogue addressable fire panel, 2
to 8 loops, 16 to 64 displayed zones with extensive I/O features. It can
operate within a 31 panel network and can communicate with global
repeaters and PC grahics. It also supports all the LON700 devices and
repeaters using a seperate two wire bus.The panel is truly
user-friendly, and provides a generous 8 x 40 backlit graphic display.
I/O control is done via the powerful 2000/1200 series boolean I/O
programing module. Extensive maintenance features are provided
standard. The FP2864 supports 2000, 1500 and 900 series sensors and
I/O units.
Specifications
Supply voltage 1
190 - 270 VAC
Supply voltage 2
40 - 60 Hz
160 VA max.
21 - 27 VDC
Current consumption
Quiescent @ 24 VDC
(equipped loop)
800 mA
Alarm current @ 24 VDC
1A
Available auxiliary current in 3 A
alarm
Battery charger rating @ 27.5
VDC
3A
Total supply rating @ 27.5 VDC
4A
Relay rating @ 24 VDC
2A
Weight (no batteries)
15 kg
Dimensions (H x W x D)
804 x 441 x 109 mm
Ordering Information
FP2864
Analogue addressable fire panel, 2 - 8 loops, 16 - 64 zones
BUS2000
ESPA2000
LC1502
LON2000
LON2000R
MOD2000
NC2011
NC2051
NE2011
NE2051
PR2000
RB2016
RE2004
ZE2016
2000 Series bus termination board
ESPA protocol hardware key
2-loop extension board for 1200/2000 series fire panels
LON700 driver for FP1200 / FP2000
LON driver for FP1200/2000 - closed loop systems
Modem kit
ARCNET RS485 network card with single RS485 interface
ARCNET network card with single optical interface board
RS485 network extension board
Fibre optic network extension board
Internal printer
Relay extension board for 1200/2000 series fire panels
2000 Series Memory Expansion Kit
16-zone LED extension fire and fault LED
PCM2000
PCC2000
Maintenance and support software with copy protection key
Programming and configuration software
PCG-N
PCG-S
Graphics package network application with copy protection key
Graphics package with copy protection key
E
E
E
E
E
E
E
E
E
E
E
E
One man maintenance
Graphic maintenance
Maintenance warning
Service reminder signal
Soak test
On-line diagnostics and statistics
Floating background
Day/night sensitivity setting
Coincidence within and in between zones
Automatic timed and manual on/off zones
Start-up default mode
Service switch
E Upload/download, remote maintenance and graphic PC
software
E
E
E
E
E
E
I/O programming including Boolean functions
ARCNET panel networking
EN54 approved, certified Bosec, VdS, NFA2P
Networkable "black box" and "global zone" system
Full range of repeater panels
Full range of LON700 devices
Addressable Fire Systems
Page : 108
FB2400
Analogue addressable fire panel 2 - 4 loops, 'black box'
FP2000 series
The FB2400 / FB2800 'black box' system allows a cost-effective
network of fire panels to be interconnected to a global repeater using
the FP2000 series arcnet network. The FB black boxes have all the
features of the FP2000 series of fire panels, but have no display /
keyboard. All controls and display is done via the global repeater.
Specifications
Supply voltage 1
190 - 270 V ac
Supply voltage 2
40- 60 Hz
160 VA max.
21 - 27 V dc
Current consumption
Quiescent @ 24 V dc (equipped
loop)
500 mA
Alarm current @ 24 V dc
600 mA
Available auxiliary current in
alarm
3.4 A
Battery charger rating @ 27.5 V
dc
3A
Total supply rating @ 27.5 V dc
4A
Relay rating @ 24 V dc
2A
Weight (no batteries)
11 kg
Dimensions (mm) (H x W x D)
609 x 441 x 109
Ordering Information
FB2400 Analogue addressable fire panel 2 - 4 loops, 'black box'
FB2800 Analogue addressable fire panel 2 - 8 loops, 'black box'
E
E
E
E
E
E
E
E
E
E
E
E
One man maintenance
Graphic maintenance
Maintenance warning
Service reminder signal
Soak test
On-line diagnostics and statistics
Floating background
Day/night sensitivity setting
Coincidence within and in between zones
Automatic timed and manual on/off zones
Start-up default mode
Service switch
E Upload/download, remote maintenance and graphic PC
software
E
E
E
E
I/O programming including Boolean functions
ARCNET panel networking
Networkable "black box" and "global zone" system
Full range of repeater panels
Addressable Fire Systems
Page : 109
2-loop extension board for FP1200 / FP2000 fire panels
LC2002
FP1200 / FP2000 series
Specifications
Current consumption
Quiescent @ 24 V dc (Fully
equipped loop)
+ 150 mA (252 detectors)
Ordering Information
LC2002 2-loop extension board for FP1200 / FP2000 fire panels
16-zone LED extension fire and fault LED
The ZE2016 allows the extension of the zones of the Fx2x32 and
Fx2x64 fire panels and repeaters by 16 additional zones.
Ordering Information
ZE2016 16-zone LED extension fire and fault LED
ZE2016
Addressable Fire Systems
Page : 110
LON700 driver for FP1200 / FP2000
LON2000
FP1200 / FP2000 series
A LON700 driver that connects FP1200 / FP2000 fire panels to LON700
devices
Ordering Information
LON2000 LON700 driver for FP1200 / FP2000
ARCNET RS485 network card with single RS485 interface
The NC2011 is an interface board to connect an RS485 copper network
directly into the 1200/2000 series fire panels. It is supplied with one
NE2011 pre installed.
Ordering Information
NC2011 ARCNET RS485 network card with single RS485 interface
NE2011 RS485 network extension board
NC2011
Addressable Fire Systems
Page : 111
ARCNET network card with single optical interface board
NC2051
The NC2051 is an interface board to connect a fiber optic network
directly into the 1200/2000 series fire panels. It is supplied with one
NE2051 pre installed.
Ordering Information
NC2051 ARCNET network card with single optical interface board
NE2051 Fibre optic network extension board
RS485 network extension board
The NE2011 is a RS485 network extension board for the NC2011 to
allow dual bus and closed ring networks.
Ordering Information
NE2011 RS485 network extension board
NE2011
Addressable Fire Systems
Page : 112
Fibre optic network extension board
FP1200 / FP2000 series
An extension board for the NC2051 to allow a fibre optic ring bus
Ordering Information
NE2051 Fibre optic network extension board
NE2051
LON700 Devices
Page : 113
FRL700
LCD repeater
The LON700 LCD repeater is a smart and compact, cost-effective
solution for fire panel repeaters. It is also available as an FBP700 fire
brigade panel for Dutch and Scandinavian norms.
Specifications
Dimensions (l x w x d)
240 x 320 x 60 mm
Weight
1.5 kg
Operating temp °C
-5°C to +40°C
Operating voltage
15 - 30 VDC
Current consumption
Max. quiesent
100 mA
Bus Connection
two wire LON700
Bus Cable
CAT 5
Total number of repeaters
700/1200/2000 Series
15
Ordering Information
FRL700 LCD repeater
E
E
E
E
E
2 wire connection between fire panel and repeaters
Up to 1500 metre bus length
24 Volt power supply
Cost effective repeater solutions
Easily installed, simple operation
E 4 x 20 charater LCD display, common LED's, push
button control
E LON700 module
Addressable Fire Systems
Page : 114
FR2000
LCD repeater with emulator functions
FP1200 / FP2000 series
A powerful LCD repeater that can be used as a local or global repeater
on a FP1200 / FP2000 fire panel network. Fire panels can be emulated
from the FR2000. An 80 x 40 backlit graphic display and full indication
and control keyboard is provided standard.
Specifications
Supply voltage
230 V ac (+10/-15%)
Min. supply current @ 24 V dc
50 Hz
50 VA
0.15 A
Battery charger rating @ 27.6 V
dc
0.3 A
Total supply rating @ 27.6 V dc
1A
Relay rating @ 24 V dc
2A
Weight (no batteries)
7.5 kg
Dimensions (mm H x W x D)
365 x 444 x 111
Ordering Information
FR2000
NE2011
NE2051
FP-RIM1270
LCD repeater with emulator functions
RS485 network extension board
Fibre optic network extension board
Rim surround for the 780 and 1200N series fire panel boxes
E 8 x 40 character graphic display
E Arcnet network connection to FP1200/FP2000 series
firepanels
E
E
E
E
Global repeater function
Comprehensive control and display functions
Fire panel emulation function
Dual RS232 ports
Addressable Fire Systems
Page : 115
FR2032
Repeater / emulator 16 - 32 zones or panels
FP1200 / FP2000 series
A repeater / emulator with 16, expandable to 32, displayed fire and
fault zones, used in FP1200 / FP2000 networked systems. The repeater
is connected on the arcnet network and can operate in a local or
global repeater mode. An 80 x 40 backlit graphic display and full
indication and control keyboard is provided standard.
Specifications
Supply voltage
21 - 28 V dc
Current consumption
300 mA max
Weight
11 kg
Dimensions (mm H x W x D)
609 x 441 x 109
Ordering Information
FR2032
NE2011
NE2051
ZE2016
Repeater / emulator 16 - 32 zones or panels
RS485 network extension board
Fibre optic network extension board
16-zone LED extension fire and fault LED
E 8 x 40 character graphic display
E Arcnet network connection to FP1200 / FP2000 series
firepanels
E
E
E
E
E
Global repeater function
Comprehensive control and display functions
16 zones fire and fault expandable to 32 zones
24 Volt operation
Emulation functions
Addressable Fire Systems
Page : 116
FR2064
Repeater/emulator 16 - 64 zones or panels
A repeater/emulator with 16 fire and fault zones, expandable to 64,
used in 1200/2000 series networked systems. The repeater is
connected on the arcnet network and can operate in a local or global
repeater mode. An 80 x 40 character, backlit graphic display and full
indication and control keyboard is provided standard.
Specifications
Supply voltage 1
Supply voltage 2
160 VA max.
21 - 27 VDC
Current consumption
Quiescent @ 24 VDC
(equipped loop)
300 mA
Alarm current @ 24 VDC
Available auxiliary current in
alarm
Battery charger rating @ 27.5
VDC
Total supply rating @ 27.5 VDC
Relay rating @ 24 VDC
Weight (no batteries)
15 kg
Dimensions (H x W x D)
804 x 441 x 109 mm
Ordering Information
FR2064
Repeater/emulator 16 - 64 zones or panels
BUS2000
ESPA2000
LON2000
LON2000R
MOD2000
NE2011
NE2051
PR2000
ZE2016
2000 Series bus termination board
ESPA protocol hardware key
LON700 driver for FP1200 / FP2000
LON driver for FP1200/2000 - closed loop systems
Modem kit
RS485 network extension board
Fibre optic network extension board
Internal printer
16-zone LED extension fire and fault LED
E 8 x 40 character graphic display
E Arcnet network connection to FP1200 / FP2000 series
firepanels
E
E
E
E
E
Global repeater function
Comprehensive control and display functions
Emulation function
16 to 64 zones fire and fault displayed
24 volt operation
Addressable Fire Systems
Page : 117
UN2011
FP1200 / FP2000 arcnet to RS232 converter
FP1200 / FP2000 series
The unversal node allows the fire panel arcnet network to be extended
to computer software applications either locally with the RS232
interface, or remotely using the MOD2000. It has a 230 volt power
supply and battery charger self contained in the unit.
Specifications
Input voltage
230 V ac, 50 Hz, 10 VA
Battery type
12 V 1,2 Ah
Fault relay
2 A @ 24 V dc, 50 W dc
Weight
5 kg
Dimensions mm (H x W x D)
400 x 300 x 65
Operating remperature
0 - 40 °C
Ordering Information
UN2011 FP1200 / FP2000 arcnet to RS232 converter
MOD2000 Modem kit
E FP1200 / FP2000 arcnet to RS232 interface
E Allows computer applications to operate on the fire
panel network
E 230V operation and battery charger
E Can be extended with MOD2000 for remote operation
E 'Black box' operation
Addressable Fire Systems
Page : 118
MOD2000
Modem kit
FP1200 / FP2000 series
An internal modem for the FP1200 / FP2000 fire panels or a UN2011
universal node. The modem has the autonomy of the fire panel power
supply, and has extended telephone line protectection. The MOD2000
can also be used with a computer.
Ordering Information
MOD2000 Modem kit
E
E
E
E
MOD2000
For fire panel and universal node operation
Internal installation
Autonomous power supply
Addressable Fire Systems
Page : 119
PCC2000
Programming and configuration software
PCC2000 allows easy, menu driven, programming of all the panel's
features and settings. Common texts can be easily copied while
sensors, zones and areas increment or follow automatically. Boolean
logic programming becomes simple as inputs and outputs are
continuously displayed for the programmer's convenience.
Specifications
Processor
486 66 MHz
RAM
12 Mb
Display adapter
VGA
Hard disk space
20 MB
Pointing device
MS Mouse
Graphical environment
Windows 98, 2000, XP
Communications ports
1 x RS232
1 x Parallel
Ordering Information
PCC2000 Programming and configuration software
E Provide communication with single fire panels and
networked fire systems, both locally or remote via
modem
E
E
E
E
Windows 98, 2000 and XP compatible
For use with 2000/1200 series panels
Menu driven
Full or partial up- and download
Addressable Fire Systems
Page : 120
PCM2000
Maintenance and support software with copy protection key
PCM2000 allows local and remote maintenance facilities for 1200/2000
series fire panels. Amongst others, it allows for full panel emulation,
data retrieval and central alarm monitoring.
Specifications
Processor
Pentium 133Mhz (or better)
RAM
32 Mb (or more)
Display Adapter
VGA
Hard Disk Space
20 MB
Pointing Device
Bus or P/S2 Mouse
Graphical Environment
Windows 98, NT or 2000
Communications ports
Depending on Drivers Printer port (for key)
1 Parallel
Ordering Information
PCM2000 Maintenance and support software with copy protection key
E Provide communication with single fire panels and
networked fire systems, both locally or remote via
modem
E
E
E
E
E
E
E
E
Windows 95, 98 and NT compatible
For use with FP2000, FP1200
Full panel emulation
Data retrieval
Central station
History log
Address book
Dynamic Link Library (DLL) for third party integration
Addressable Fire Systems
Page : 121
PCG-S
Graphics package with copy protection key
2 Packages allow the graphic package to grow with the installation.
The basic version PCG-S operates with a single panel, while the PCG-N
supports a network. Upgrades do not require rework on the existing
database, drawings, etc.
Specifications
Item
Recommended
Processor
Pentium II 266 MHz (or better)
RAM
64 Mb (or more)
Display adapter
SVGA or better
Hard disk space
200 MB
Pointing device
MS Mouse, Bus or P/S2
Graphical environment
Windows NT
Communication ports
1 x RS-232 - Depending on drivers
1 x Parallel - Printer port (for key)
Ordering Information
PCG-S Graphics package with copy protection key
E Provide bi-directional communication with single fire
panels and networked fire systems, both locally and
remote via modem
E
E
E
E
E
E
E
E
E
E
E
E
Windows 2000 and NT compatible
For use with FP2000, FP1200, FP1100 and FP700
Constructed around Sybase SQL Anywhere
Large selection of icons
Visualises inputs & outputs
Information page per point
Get texts from panel
Several operator levels and passwords
Operator configurable
Multiple navigation buttons
Event logs
Basic drawing package included
E Imports .bmp & .wmf drawings from virtually any
package
E Hardware key protected
Content
DI322I
DP331I
DT313I
KCT731
KZ700
KZ705
KZ705D
EOL-ACT
KZ705R
S700
DP721I
DP721T
DT713-5
DT713-7
DB702
DI650
DP652
DT654
DB860
DB861
DB806
DB650
DI1552
DP1561
DP1551T
DT1553
PG700
KZ705I
KZ705AS
KZ705IAS
KAL410
KAL414C
KAL426C
KAL430
KAL434C
KAL440
KAL450
KAL460
KAL470
KAL490
DP2051
DP2061
DP2061T
DP2071
Ionisation detector, conventional
Page : 3
Optical detector, conventional, with field exchangeable optical block
Page : 4
Temperature detector (fixed and rate-of-rise), conventional
Page : 5
Calibration Tool for KL731/DP331I Fire Detectors
Page : 6
Universal fire detector base
Page : 7
Universal fire detector base with earth connection
Page : 8
Conventional fire detector base with diode
Page : 9
Active end-of-line device for use with FP400/KL700 fire panels
Page : 9
Conventional 12 VDC fire detector base with relay
Page : 10
Surface mount accessory for KZ700 and KZ705 series bases
Page : 11
Photoelectric smoke detector with remote alarm LED output
Page : 12
Photoelectric smoke and heat detector head with remote alarm LED
Page : 13
57º C fixed and rate-of-rise heat detector
Page : 14
70º C fixed and R.O.R. heat detector
Page : 15
10 cm diameter base - 6 terminals
Page : 16
Ionisation smoke detector
Page : 17
Optical smoke detector
Page : 18
Heat detector, R.O.R., 57º C A1R
Page : 19
Standard Base
Page : 20
Backplate for Ingress Protection 860-950
Page : 20
Conduit box for 860 / 950 series bases
Page : 21
650 series relay base
Page : 21
Ionisation Sensor
Page : 22
Optical sensor with field exchangeable optical block
Page : 23
Dual Sensor (Optical/Heat)
Page : 24
Heat Sensor
Page : 25
Fire sensor programmer
Page : 26
Analogue fire detector base with isolator
Page : 27
Analogue fire detector base with sounder
Page : 28
Analogue fire detector base with isolator and sounder
Page : 29
Conventional Zone Monitor Unit - 1 Zone
Page : 30
Conventional Zone Monitor Unit - 4 Zones
Page : 31
Extinguishing Control Module
Page : 32
Relay Module - 1 Relay
Page : 33
Addressable Relay Module - 4 Relays
Page : 34
Supervised Relay Module
Page : 35
Addressable Manual Call Point
Page : 36
Digital Input Module
Page : 37
Isolator Module
Page : 38
Retention Module - 1 Input / 1 Output
Page : 39
Optical Sensor
Page : 40
Optical Sensor with remote LED output
Page : 41
Optical and heat multi-sensor with remote LED output
Page : 42
Optical Sensor with 7-segment display
Page : 43
DT2053
DT2063
DT2073
DB2001
DB2002
DB2016
IU2016
DB2003
DM2000
DM2000E
IO2014
IU2050
IU2055
GBX2000
IU2080
FD2705R
AS2015
DI950
DP951
DT952
DM960
DI970
DP971
DT972
DM970
PT971
GBX70
II950
II952
II955
IO950
IO955
IO956
IU950
AS950
AS955
FD950
DB950
DB951
DB961
DB970
IU980
FP202
FP204
2000 Series heat sensor
Page : 44
2000 series heat sensor with remote LED output
Page : 45
Heat Sensor with 7-segment Display and Remote LED Output
Page : 46
2000 series base, 2 terminals
Page : 47
2000 series base, 4 terminals
Page : 48
Isolating base
Page : 49
Loop Isolator
Page : 50
Base for the IU2016 isolator
Page : 51
Manual call point, flying leads
Page : 52
Manual call point - Red IP67 waterproof, including backbox
Page : 53
Input Output unit - 4 inputs
Page : 54
Single Input Module
Page : 55
Conventional Zone Monitor
Page : 56
Galvanic barrier
Page : 57
Indicating Circuit Controller
Page : 57
2000 series addressable reflective beam detector 5 - 50m
Page : 58
2000 series loop powered sounder
Page : 59
Analogue addressable ionisation sensor
Page : 60
Optical sensor
Page : 60
Analogue addressable temperature sensor
Page : 61
950 series analogue addressable manual callpoint
Page : 61
Intrinsic safe analogue addressable ionisation detector
Page : 62
Intrisic safe optical detector
Page : 62
Intrinsic safe heat detector
Page : 63
Intrinsic safe manual call point
Page : 63
Intrinsic safe protocol translator
Page : 64
Galvanic barrier (single channel)
Page : 64
950 series mini switch monitor unit
Page : 65
950 series switch monitor unit - surface mount
Page : 65
950 series zone monitor unit - surface mount
Page : 66
950 series single channel IO - surface mount
Page : 66
950 series output unit - surface mount
Page : 67
950 series sounder circuit controller - surface mount
Page : 67
950 series loop isolator
Page : 68
950 series loop powered sounder
Page : 69
950 series high output loop powered sounder
Page : 70
950 series loop-powered beam detector
Page : 71
950 series standard base
Page : 72
Base for IU 950
Page : 72
Isolating base (20 devices)
Page : 73
Detector base for 970 series intrinsic safe sensors
Page : 73
Coded cards, addresses 1 - 18
Page : 74
Conventional fire alarm panel with 2 zones
Page : 75
Conventional fire alarm panel with 4 zones
Page : 76
FP206
FP402
FP408
FP412
FP416
RB404
SB404
FEC403
FEC406
FP604
ZI602
RC606
FP708
FR708
ZE708
ZI708
FM740
OCB724
RB708
SOB708
FB708
NC700
PS700
FP1501
FP1502
NC785
FR1500
MODGSM
PCG-Graphic102
PCG-GraphicNW
FP1216EN
FP2416
FP2432
FP2864
FB2400
LC2002
ZE2016
LON2000
NC2011
NC2051
NE2011
NE2051
FRL700
FR2000
Conventional fire alarm panel with 6 zones
Page : 77
Conventional fire alarm panel with 2 zones
Page : 78
Conventional fire alarm panel with 8 zones
Page : 79
Conventional fire alarm panel with 12 zones
Page : 80
Conventional fire alarm panel with 16 zones
Page : 81
Relay module, 4 potential free relays for NK700/Fx400 fire panels
Page : 82
Relay module, 4 supervised relays for NK700/Fx400 fire panels
Page : 83
Conventional extinguishing control panel with 3 zones
Page : 84
Conventional extinguishing control panel with 6 zones
Page : 85
4-zone Conventional Fire Panel
Page : 86
Two zone extension board, including 6 outputs
Page : 87
Set of 6 bi-stable magnetic latch relays
Page : 87
Fire panel equipped with 8 zones
Page : 88
Repeater 8 zones, 24 VDC input
Page : 89
8 zone indicator LED extension board fire/fault
Page : 90
8 zone input extension board
Page : 91
Synoptic driver for 80 LEDs and common signals
Page : 92
LON700 output board with 24 open collector outputs
Page : 93
LON700 output board with 8 relays
Page : 93
LON700 output board with 8 supervised outputs
Page : 94
FP700 black box with 7 slot card cage
Page : 95
LON700 interface board
Page : 96
Plug-in power supply 3.5 A
Page : 96
Analogue addressable fire detection panel - 1 loop
Page : 97
Analogue addressable fire detection panel - 2 loops
Page : 98
RS485 expansion kit for KSA701/FP1500 fire panels
Page : 99
Analogue addressable LCD Repeater/Emulator (AC Powered)
Page : 100
GSM Modem for KSA700/FP1500 Series Fire Panels
Page : 101
Graphic Software for KSA700/FP1500 Fire Systems (1 panel-2 loops)
Page : 102
Graphic Software for KSA700/FP1500 Fire Systems (multi-panel)
Page : 103
Analogue addressable fire panel 2 - 4 loops, 16 zones
Page : 104
Analogue addressable fire panel 2 - 4 loops, 16 zones
Page : 105
Analogue addressable fire panel 2 - 4 loops, 16 - 32 zones
Page : 106
Analogue addressable fire panel, 2 - 8 loops, 16 - 64 zones
Page : 107
Analogue addressable fire panel 2 - 4 loops, 'black box'
Page : 108
2-loop extension board for FP1200 / FP2000 fire panels
Page : 109
16-zone LED extension fire and fault LED
Page : 109
LON700 driver for FP1200 / FP2000
Page : 110
ARCNET RS485 network card with single RS485 interface
Page : 110
ARCNET network card with single optical interface board
Page : 111
RS485 network extension board
Page : 111
Fibre optic network extension board
Page : 112
LCD repeater
Page : 113
LCD repeater with emulator functions
Page : 114
FR2032
FR2064
UN2011
MOD2000
PCC2000
PCM2000
PCG-S
Repeater / emulator 16 - 32 zones or panels
Page : 115
Repeater/emulator 16 - 64 zones or panels
Page : 116
FP1200 / FP2000 arcnet to RS232 converter
Page : 117
Modem kit
Page : 118
Programming and configuration software
Page : 119
Maintenance and support software with copy protection key
Page : 120
Graphics package with copy protection key
Page : 121
www.gesecurity.net
IPSCAT-2005-12-6 15:44:32
As a company of innovation, GE Security reserves the right to change product specifications without notice. For the latest product
specifications, visit GE Security online or contact your GE Security sales representative.