Eco IR Mains Basin Tap Installation and Maintenance Guide

Transcription

Eco IR Mains Basin Tap Installation and Maintenance Guide
Eco IR Mains Basin Tap
Installation and Maintenance Guide
A basin mounted tap with pre-programmed infra-red sensor.
65
185
Dimensions
65
53
740
410
Ø
Connection Size: ½”
23
.8
Power Supply: 230V
Transformer: 6V
Minimum Working Pressure:
0.5 Bar
Maximum Working Pressure:
8 Bar
15mm
Maximum Temperature: 60°C
Degree of Protection:
IP44
Insulation Class:
Double Insulated
150
Specification
15mm
15mm
185
169
138
23
.8
92
150
Ø
58
740
410
53
15mm
15mm
15mm
169
138
58
Installation
Ensure the o-ring is positioned on the bottom of the Saracen IR Eco
Tap, and place the deck plate on the threaded shank.
15mm
180
92
Feed the connection cable though the chosen hole in the basin or
15mm
counter top, position the tap and use the plastic cushion lock washer
and nut to secure.
940
Connect the flexible hose provided to the threaded shank on the end
of the tap.
Mount the control box in a suitable location, which is a firm sound
surface, ensure the location allows for the flexible hose to reach from
the tap to the solenoid valve outlet.
1
940
15mm
180
15mm
Mark the position on the wall ready for mounting; drill suitable holes,
insert the rawl plugs and secure the control box using the screws
provided.
Secure and tighten the flexible hose from the tap connection to the
solenoid outlet.
Attached the other flexible hose provided to the inlet connection on the
solenoid valve and tighten to form a seal.
This flexible hose should be connected to the water supply pipe.
The controller is designed to take a 230V mains power supply and
convert it using the internal transformer to a 6V supply. The mains
power cable should have the live and neutral connected into a fused
spur.
Please note the control box is double insulated.
The controller is
supplied with a battery
back-up, the Saracen
IR Eco tap comes
supplied with 4 x
AA batteries, ensure
these are placed in
the battery box and
re-secure with the
screws.
Secure the cover onto
the control box using
the screws provided.
Deck plate
Wash basin
Faucet spout
Deck plate
Wash basin
Hose
Signal wire
Connect the signal wire Power cable
to the sensor wire from Control box
the tap.
Ensure both the wires
for the battery and the
mains power supplies
are connected.
Plastic cushion
Lock washer
Nut
Fixed shank
Sensor
Sealing nut
Water inlet
Hose
2
User Activation
Activation & Maintenance
Water will flow from the tap when hands are close to the IR eye and
will stop immediately upon leaving this area of vision.
If the IR sensor is activated for a period longer than 1 minute the water
supply will automatically stop but can be reactivated again
Sensing Range
The IR sensor is factory set to a sensing distance of 15cm. This
sensing distance can be adjusted as follows:
1. Switch off the power to the control by disconnecting the power
leads and wait 30 Secs
2. Reconnect the power cable
3. Immediately place your hand at a distance of less than 50mm from
the sensor while the red LED within the sensor is blinking
4. When the red LED stays on, draw your hand back to the desired
distance.
5. Wait until the red LED goes off and then remove your hand.
6. The set range is now stored in the memory of the sensor
Integral Strainers
The solenoid valve comes with an integral strainer on the inlet
water supply connection, to clean this isolate the water supply and
remove the hose from the inlet connection, remove the strainer and
rinse under clean running water, re-insert the strainer back into the
connection and tighten the hose to form a water tight seal, re-open the
water supply.
3
Batteries
If the batteries are dead the LED will flicker 3 times in 1 sec, if this
happens the batteries will need to be replaced.
1. Remove the cover from the control box.
2. Remove the battery box and open the cover to access the
batteries.
3. Replace all 4 AA batteries ensure the + and – are correct to the
indicators on the box.
4. Replace the cover on the battery box and reposition this in the
control box.
5. Finally replace the control box cover.
Control-box cover
Fixing screw
Battery box
AC220V power adapter
Solenoid valve
Control-box seating
Water inlet
Strainer
Sensor plug
Power cable
Water outlet
4
Aftercare
Saracen electronic taps have a high quality finish and should be
treated with care.
An occasional wipe with a mild detergent on a soft damp cloth
followed by a thorough rinse and wipe dry with a soft clean cloth is all
that is required.
Do not use an abrasive or chemical household cleaner as this may
cause damage to the surfaces.
When cleaning bathroom tiles the tap should be protected from any
splattering of harsh cleaners.
5
6
Pressures are not within the tolerance of the
solenoid valve
Debris or scale is blocking the solenoid
IR Sensor is picking up reflections from a mirror
or light
IR Sensor is blocked or dirty
1.
2.
3.
4.
Water continually runs from
the tap
Aerator on tap spout us clogged
1.
IR Sensor is blocked or dirty
4.
Water flow diminishes
Debris or scale is blocking the solenoid
3.
Battery or power has been disconnected
Pressures are not within the tolerance of the
solenoid valve
2.
1.
IR sensing range is too short
1.
Water does not flow from
the tap
A red LED keeps flashing
within the sensor
Cause
Problem
Clean the sensor with a soft dry cloth. Please note: The
sensor will automatically cut off after 1 min if there is
continual use
Remove the object which is causing the reflection
Remove the solenoid valve from the control box; access the
integral parts by removing the screws and flush the body
through with clean running water ensure the pin hole on the
diaphragm is free from scale and re-assemble.
Check pressures and put additional devices in place to
ensure the pressure is between 0.5-0.8Bar
Remove, rinse under clean running water and re-assemble
Check power source, power cable and replace the 4 x AA
batteries in the control box
Clean the sensor with a soft dry cloth. Please note: The
sensor will automatically cut off after 1 min if there is
continual use
Remove the solenoid valve from the control box, access the
integral components by removing the 4 screws. Flush the
body through with clean running water, ensure the pin hole
on the diaphragm is free from scale and re-assemble.
Check pressures and put additional devices in place to
ensure the pressure is between 0.5-8Bar
Alter the sensing range (refer to Activation and maintenance
senction)
Solution
Trouble Shooting
Wolseley UK
Warwickshire, CV31 3HH
For further information please call
01926 705000
or visit www.wolseley.co.uk
Wolseley UK reserves the right to make changes to the product which may
effect the accuracy of the information contained in this guide.
ZINS300220_001_07-14