Product Manual

Transcription

Product Manual
AUS
LUXOMAT ® PD3-2C Micro
Installation and Operating Instruction for B.E.G. - Motion detectors PD3-2C-FC Micro
1. Mounting preparations
2. Installation of the LUXOMAT®
PD3-2C-FC Micro
Work on the 230 V mains supply
may only be carried out by qualified
professionals or by instructed persons
under the direction and supervision
of qualified skilled electrical personnel in accordance with electrotechnical regulations.
68 mm
The detector has
been designed
and developed
specifically for installation in suspended
ceilings.
Having connected up the cables in accor­
dance with regulations, the detector is
inserted into the opening as shown in the
drawing above and fixed into position with
the assistance of the spring clips.
5. Putting into operation / Settings
5
10
20
TEST
Potentiometer 1 - Follow-up time for light control
The time can be set infinitely variably at between
15 seconds and 30 minutes.
ymbol TEST: Test mode
S
(Every movement switches on the light for a period of
1 second, switching it off for a period of 2 seconds
after that regardless of the level of brightness.)
30
Potentiometer 2 - Adjusting range sensitivity
max. For sensitivity adjustment of the detector, both in the
min.
120 60 50
A
40
30
15
5 10
40
50
30
60 16 10 15
5
90
10
2
5
120
1
TEST 15 30
2000
1200
600
200
40
interior and the exterior range, the PD3-2C-FC Micro
is equipped with an additional knob (see pictures)
for excluding sources of interference, e.g. bad
weather conditions or draught air.
Max:for interior use
(recognition of the slightest movements)
Min:for exterior use
(exclusion of sources of interference)
Potentiometer 3 - Follow-up time for HVAC
The time can be set infinitely variably at between
5 and 120 minutes. There is a period of delay prior
to switch-on at between 5 - 10 minutes for times set
in excess of 60 minutes.
Potentiometer 4 - Twilight-switch for light control
The switch-on value for the light can be set at
between 10 and 2000 Lux. Using the rotary control,
the luminance set points can be set as desired.
Symbol :
Night-time operation
Symbol
Position potentiometers
4. Connections
5
4
1
2
3
A circular opening of
diameter 68 mm must
be cut into ceiling.
Disconnect supply before installing!
1 30s 15s
3. Hardware configuration
N R
L‘ L
Potentiometer
1
Time channel 1
2
Range
3Time channel 2
4
Lux channel 1
5
Sound sensitivity
6. Technical data PD3-2C
7. Trouble shooting
Sensor and power supply in one case
Power supply: 230 V~ ±10 %
Power consumption: < 1W
Ambient temperature: -25°C to +50°C
Degree of protection /class: IP20, with accessory IP23 / II
Settings: locally
Area of coverage: circular 360°
Range of coverage Ø H 2.50 m / T = 18°C:
seated 4 m / tangential 10 m / radial 6 m
Recommended height for mounting: 2 - 3 m
Lux values - Potentiometer: 10 - 2000 Lux
• Channel 1 for light-connection
Type of contact: NOC/with pretravel tungsten contact
Contact load: 2300 W, 230 V~, cos ϕ=1 /
1150 VA cos ϕ= 0.5
Time-settings: 15 sec. - 30 min. / Test
• Channel 2 for HVAC
Contact load: 230 V~, 3 A cos ϕ=1
Time-settings: 5 min. - 120 min. with time delay of 5 - 10 min.
for follow-up time > 60 min.
Dimensions H x Ø [mm] 84 x 80
Visible portion when built into ceiling: 18 x 80 mm
1. Lamp does not light up
Declaration of Conformity: The product complies with
the low voltage recommendation 2006/95/EC and the
EMV recommendation 2004/108/EC.
LUXOMAT® PD3 connected in parallel to a manual override switch:
Connect switch correctly
Lamp may be defect:
Replace lamps
No mains connection/power:
Check connection and mains fuse by qualified electrician
Incorrect setting of CDS twilight threshold:
Correct setting of CDS threshold
Lens of sensor unit obstructed by dirt or other objects:
Clean lens, remove objects
2. Lamp turns ON too late or detection range too small
LUXOMAT® PD3 is mounted too high:
See table of mounting heights.
Correct mounting if required.
3. Lamp stays ON continuously
Continuous thermal activity detected ie fan, central heating ducts, animals within detection area:
Remove heatsource. Check proper function of LUXOMAT®
PD3 by covering the fresnel-lens. After expiry of delay
timer, PD3 has to turn OFF lighting.
4. Unintended switching of light
Movement of heat source within detection area:
Check on presence of animals, fans or heaters
: Daytime / Night-time operation
Potentiometer 5 - Adjusting sound sensitivity
max. Max:
highest sensitivity
Min:microphone switched off
Intermediate values to be adjusted accordingly to
local conditions.�������������������������������������
������������������������������������
Lighting of the LED means the noisedetector is functioning and triggers the timer again.
The microphone is active for 9 seconds after the last
movement and time delay completed.
min.
8. Range of Coverage
9. Article / Part nr. / Accessory
2.50 m
Type
FC
PD3-2C Micro
96510
Accessory:
BSK Ball basket guard
FC-Covering IP23
3
10
m
2
1
360°0 m
4.0
1
2
R2: 3A NO
230 VAC ±10% 50-60 Hz
quer
zum across
Melder gehen
walking
frontal
zum
Melder gehen
walking
towards
Unterkriechschutz
seated
6m
10 m
92199
92206
10. Wiring diagrams
12. PD3 - Dimensions

3A

5
15
M1
E1
230VAC
50-60Hz
7m
~6 m
T1
R L' N L L NO NO
Slave /
Remote
84.5


6m
5
74
L
N
64
Standard mode with slave device
13. Installation examples
R
N
L
L΄΄ NO NO
C1
R
C2
N
L


18 m

PD3-2C
 Micro
Slave



6m
optional
T1 = Light ON/OFF (see point 14 also)
Slave for enlargement of detection area
11. LED function displays
~6 m
6m
2000 Lux
1
1200
2
600
200
40
12 m
LED’s
1 - Red flashes on each detected sound
6m
4m
2-R
ed
- flashes 60 sec. during initialisation period
- flashes on each detected movement
- flashes quickly, if duration “ON” active by terminal R
6m
6m
14. Functions of pushbutton
The table below shows the logical behavior of both channels (light + HVAC).
Brightness-state 230 VAC on Terminal R
Channel 1 for light-connection
Channel 2 for HVAC
bright
no change
no change
1-2 sec.
(slave signal)
> 10 sec.
OFF -> ON or ON -> OFF
no change
(as long as motion + Follow-up time )
no change
OFF -> ON
OFF -> ON
getting dark
release button
OFF -> OFF
OFF -> ON
will stay-on (as long as motion +
Follow-up time)
dark
no change
no change
0-1 sec. or 2-10 sec.
1-2 sec.
(slave signal)
> 10 sec.
Release button
will stay-on (as long as
motion + Follow-up time)
OFF -> ON or ON -> OFF
no change
(as long as motion + Follow-up time )
OFF -> ON
OFF -> ON
OFF -> ON
will stay-on (as long as motion +
Follow-up time)
OFF -> ON
will stay-on (as long as
motion + Follow-up time)
When a channel or slave-hold (pushbutton > 10 sec.) gets deactivated, it is possible to reactivate the channel
by sound/motion for 10 sec. This possibility is independent of brightness-state. So even if the lightchannel is in
bright condition. (light level > setpoint)
MAN 6891– 090511-1
0-1 sec. or 2-10 sec.