chapter 12: conversion and refurbishment
Transcription
chapter 12: conversion and refurbishment
CHAPTER 12: CONVERSION AND REFURBISHMENT CHAPTER 12: CONVERSION AND REFURBISHMENT CONTENTS 12.1 EXISTING ELEMENTS 12.2 NEW ELEMENTS CONNECTING TO EXISTING STRUCTURE Technical Manual V6: TS-011a-6.00-010413 CHAPTER 12 FUNCTIONAL REQUIREMENTS 12.1 EXISTING ELEMENTS Workmanship Design i. All workmanship must be completed by a technically competent i. Design and specifications should give clear indication of the design intent and demonstrate a satisfactory level of performance with ii. Any new work must meet the defined tolerances indicated in regards the renovation of components and the interaction of chapter 1 of this Manual, tolerances will not apply to existing finishes new elements. that have not been upgraded, altered or where the supporting ii. Specialist reports are required to confirm that existing elements will elements will not allow for the tolerances to be met. have an adequate level of structural stability as defined in the materials section, the reports must confirm the adequacy of the existing waterproof envelope. person in a workmanlike manner. Materials i. All new materials should be stored correctly in a manner which will not cause damage or deterioration of the product. ii. Materials, products and building systems shall be appropriate and suitable for their intended purpose. iii. The structure regardless of whether it is a new or existing element shall, Technical Manual V6: TS-011a-6.00-010413 unless specifically agreed otherwise with the warranty provider, have a life of not less than 60 years. Individual components and assemblies, not integral to the structure may have a lesser durability, but not in any circumstances under 15 years. iv. Existing elements that are to be retained must provide a waterproof envelope to the building and be structurally adequate. CHAPTER 12: CONVERSION AND REFURBISHMENT CHAPTER 12: CONVERSION AND REFURBISHMENT 12.1.1 Introduction Depending on the condition of the original It is not possible to cover every building type within The following guidance has been formulated to building, an expert survey may be required for this chapter and therefore the guidance is general assist both Site Audit Surveyors and Developers the elements below. If the survey concludes that and certainly will not apply in every scenario. It is on projects involving either the conversion or any of these elements are unable to meet the strongly recommended that early discussions are refurbishment of existing buildings. life expectancy of 60 years for structure and 15 undertaken to determine exact requirements and years for non-structural elements, they should be to enable a full review of the proposed strategy systematically replaced or repaired. and development. buildings. This could include the conversion of Existing buildings and structures can present Where new work is proposed, the new work should industrial or commercial buildings into housing; the particular problems both initially and on an on- follow the guidance for those elements in this conversion of an existing residential building into going basis. Therefore, it is essential that thorough Technical Manual. Where new work is applied flats; an additional storey to an existing building; and comprehensive survey work is undertaken to, or meets existing elements, consideration on the refurbishment of an existing residential building prior to new works commencing to understand how these areas will interact must be made. For or a façade retention project. both the current condition of any structure and the example, new cavity masonry which abuts an impact any proposed works may have. Although, existing solid wall construction. Conversions and refurbishments are projects that involve work to existing buildings or parts of existing The warranty includes cover for the retained initially this may be considered an unnecessary structural elements and waterproof envelope early expense, the savings in reconstruction costs Please note: of any existing building for the duration of the can greatly outweigh the cost of the preparatory The requirements of the Technical Audit are quite policy. The warranty Site Audit Surveyor will work. different from those undertaken for the purposes always undertake an Initial Assessment of the of compliance with Building Control and Planning Technical Manual V6: TS-011a-6.00-010413 existing fabric to ascertain in general terms if the Elements of the retained structure and proposed Legislation. If any such bodies have imposed proposal is capable of representing a standard works should not be considered in isolation, as restrictions on the areas above, we suggest that risk to the Underwriter. If deemed acceptable, the a solution for one problem may cause issues you contact the Technical Services Department development is then subject to a Technical Audit elsewhere. Past performance is no guarantee of before undertaking any works. process during construction and the following on-going adequate performance because guidance is intended to assist all parties in different expectations and changing living ensuring the relevant requirements are met, as conditions can all impact on both the actual well as providing an element of consistency in and perceived performance of a converted / approach. refurbished structure. CHAPTER 12 CHAPTER 12: CONVERSION AND REFURBISHMENT CHAPTER 12: CONVERSION AND REFURBISHMENT 12.1.2 Retained elements, foundations and Timber treatment against insect External doors and windows load-bearing structures; including floors, and fungal attack A condition survey should be provided by an walls and roof All retained timbers will need to be assessed, independent, competent and appropriately Any areas of cracking or suspected movement are logged and remedial treatment noted. Timbers, qualified Surveyor or specialist to confirm life to be assessed and remedial measures provided which are embedded should be exposed or expectancy of 15 years. Consideration must be by an appropriately qualified and experienced removed and replaced with masonry. Where this given to improving the thermal characteristics. Engineer. Any additional loads must be catered for. is not possible, core samples should be taken Consideration for the impact of any landscaping to assess the moisture content and remedial External and internal services and drainage works needs to be made. Spalling works considered. Any remedial treatment must Any services to be retained should be suitably masonry can be locally repaired, with units cut out be provided with a 10 year insurance backed tested and reported by a specialist. and replaced, or re-used with sound face showing. guarantee and undertaken by a member of the Larger areas will require a schedule of repair to be Property Care Association, where guarantees must Drainage submitted and agreed. cover workmanship and materials. A CCTV survey should be undertaken to ensure the Damp proof courses and membranes Roof coverings the lengths of existing retained drainage do not All walls, floors and basements should include Coverings and support systems should be replaced have rodding access in accordance with current a DPC. Ground levels and ventilation should be unless a specialist report, which is compiled by requirements, additional access points should be checked before any remedial DPC treatments an independent, competent and appropriately provided. Inspection chambers and manholes are considered. However, where remedial qualified Surveyor, concludes that the system can located within habitable parts of the building will DPC treatments are required these need to provide a life span of at least 15 years. This should not normally be acceptable. Existing interceptors be appropriate to the type of construction, include the covering, battens, felt, flat roof decking, should be removed and any proposal to retain independently tested / approved and provided fascias, soffits, flashings, nails and clips, etc. existing septic tanks / cesspools will normally be integrity and design of any retained system. Where Technical Manual V6: TS-011a-6.00-010413 with a 10 year insurance backed guarantee. rejected. Installed by a member of the Property Care Weather resistance of walls, including claddings, Association, the guarantees must cover render, re-pointing, etc. Where some of the elements are new and workmanship and materials. The construction of The remedial works for the external walls must have replaced as part of the conversion / refurbishment any existing ground floor will need to be assessed regard for the exposure rating provided in BS 5628. no report is necessary. and details provided to the Site Audit Surveyor for Any retained cladding system must be surveyed consideration. to determine a minimum 15 year life expectancy. Provision of additional thermal insulation must also be considered. CHAPTER 12: CONVERSION AND REFURBISHMENT CHAPTER 12: CONVERSION AND REFURBISHMENT 12.1.3 Substructure Proposals for underpinning should be prepared by 12.1.3.2 Tanking of basements an expert and be in accordance with BS 8004. Where it is intended that any accommodation 12.1.3.1Foundations below ground level is to be habitable, then the An appraisal of the existing building and its design should be such that adequate resistance foundations should be carried out by a Structural to the passage of water / moisture to the inside Engineer. is achieved, following the guidance in BS 8102 (2009). This appraisal should address: Relevant matters include: •Settlement; •Heave; • Determine the position of water table; • Foundation depth and type; • Assess the drainage characteristics of soil; • Soil type; • Products which are used should have • Basement walls and floors; independent third party certificates and be • Trees adjacent to buildings. installed by an approved installer; • Increasing the height of the retaining walls; When carrying out the appraisal, the person should take into account any proposed increased • Reducing the ability of the floor above to Figure 1 - Typical traditional underpinning detail provide lateral support to the walls; Technical Manual V6: TS-011a-6.00-010413 loading on the structure, foundations or alterations • Lowering floor levels to increase ceiling heights; to existing load paths and any alterations to the • Alterations to the existing applied loadings; existing stability of the building. • Additional loading from adjacent structures. Where the existing foundations are inadequate Existing basement floors may be suitable if it can and the building has moved / cracked and / be shown that the slab is in the region of l00mm or the proposals are to increase the load on thick and is bearing on to a suitable inert hardcore. the foundations, a Structural Engineer should The proposals to tank the basement should design a suitable solution, which should then be address both the walls and the floor, in order to discussed with your Site Audit Surveyor prior to ensure the integrity of the basement area. implementation. Figure 2 - ‘Hit and miss’ underpinning sequence CHAPTER 12 CHAPTER 12: CONVERSION AND REFURBISHMENT CHAPTER 12: CONVERSION AND REFURBISHMENT It should not be assumed that a wall, which is Where the basement area is to be non-habitable, level to ensure that ground moisture does not dry at the time of the survey, would not cause such as storage, it should be designed to ensure enter the inside of the building. Consideration to a problem at a future date. Existing basements that the area is reasonably dry and well ventilated. the height of the ground floor must be made. should be provided with a new structural This is of particular importance where timber is waterproofing (tanking) system designed by a present in order to prevent the outbreak of wet/ Some types of wall are not suitable for treatment suitably qualified and experienced specialist. dry rot in the building. The measures to ensure that by a remedial damp proof course system. These The work should be carried out by a competent the storage areas are reasonably dry are not as include: Specialist Contractor who has been approved onerous as when designing a habitable basement. by the Site Audit Surveyor and a member of the In accordance with BS 8102 (2009), adequate • Walls of exceptional thickness, i.e., greater Structural Waterproofing Group. Land drainage to provision should be made to prevent surface and the external perimeter of the basement must be interstitial condensation within the basement. • Rubble filled walls; considered in order to reduce hydrostatic pressure than 600mm; • Random flint / granite walls or other similar to acceptable levels. Consideration must be given to: impermeable materials; Internal walls will also require tanking if either they • Appropriate ventilation; do not have an effective DPC located at the same • Adequate heating; level as the floor tanking membrane, or if they link • Appropriate insulation; Advice should be sought from the Property Care with an external wall which is in contact with the • Avoiding cold bridging; Association Member as to the suitability of their adjacent ground. • Treatment of hygroscopic salts contained proposed products / system. Products used in chemically injected systems should always hold • Mud walls (cob), wattle and daub; in walls and floors; Technical Manual V6: TS-011a-6.00-010413 Built-in structural timbers such as timber lintels shall • Removal of water vapour from kitchens be replaced, e.g., with concrete lintels if they are and bathrooms. sealed by tanking. 12.1.3.3 Damp proofing It should be ensured that continuity of tanking is Where an existing DPC cannot be identified or maintained around chimney breasts. To simplify is found to be defective, then a remedial DPC the problem, consideration should be given to the should be provided which should be backed by removal of the chimney breast in the basement an insurance backed guarantee, and installed by and providing adequate support at ground level to a Property Care Association Member. A suitable the retained chimney. DPC should be provided to existing walls, and be placed at least 150mm above external ground • Rat trap bond. current independent third party certificates. CHAPTER 12: CONVERSION AND REFURBISHMENT CHAPTER 12: CONVERSION AND REFURBISHMENT An alternative method of detecting any dry rot is by The root cause of fungal attack is dampness. For seeking the expertise of: example, dampness may be caused by the following: Hutton + Rostron: • Rain penetration; T: 01483 203221, •Condensation; F: 01483 202911 • Hygroscopic salts; W: www.handr.co.uk • Defective rainwater goods and roofs; • Bridging of existing DPCs, or no DPC; or • Defective renders; • Direct penetration of rainwater through solid Figure 3 - Typical chemical injected DPC 12.1.3.4 Treatment of timbers Ridout Associates: walls, particularly those facing prevailing winds; T: 01562 885135, • Leaking drains and internal plumbing; F: 01562 885312 • Incorrect external levels. W: www.ridoutassociates.co.uk Fungal attack is controlled by two sets of measures, Any remedial treatment shall be carried out by registered members of the British Wood Preserving Fungal attack covers wet rot and dry rot. Wood and Damp Proofing Association in accordance rotting fungi can be divided into two categories with their Code of Practice for Remedial Treatment according to their effects on the wood. These are: primary and secondary. Areas which have not been inspected should be clearly identified to enable a subsequent and associated technical leaflets. A 10-year Technical Manual V6: TS-011a-6.00-010413 insurance backed warranty shall also be provided. • Brown rot: causes the wood to become darker inspection to be carried out when the structure has In order to obtain insurance, it is necessary to in colour and crack along and across the been fully exposed. This could include rafter feet undertake detailed investigation of all timber grain when dry. Badly decayed wood will and wall plates which are particularly prone to rot. members to identify the presence of any insect crumble to dust, and the majority of wet rot and or fungal decay and treat the affected areas as dry rot instances fall within this group: appropriate. It is essential that the type of fungal • White rot: the wood becomes lighter in colour, eliminating sources of dampness and promoting attack is correctly identified as treatment methods and cracks along the grain. All white rots are the rapid drying out of the structure. Where the vary for dry rot and wet rot. wet rot. timber becomes wet and remains wet, e.g., the Primary measures consist of locating and moisture content exceeds 20%, then it is likely to decay, and by eliminating the source of dampness and drying of timbers below 20%, the fungus will normally stop growing and will eventually die. CHAPTER 12 CHAPTER 12: CONVERSION AND REFURBISHMENT CHAPTER 12: CONVERSION AND REFURBISHMENT Secondary measures consist of determining the 12.1.3.5 Existing concrete floors appropriate measures taken to rectify the cause full extent of the outbreak and a combination of: Where there is an existing concrete ground floor and damage. and this is to remain, the following should be • Where it can be shown that the existing identified: ground floor is structurally adequate but does not incorporate a (DPM), a DPM may be laid • Removing all decayed timbers; • Treating of walls to contain fungi within the wall • The thickness and condition of the existing over the existing slab e.g. 2/3 coat bitumen • Treating of sound timbers with preservative on a (only applicable to dry rot); slab. A minimum of 100mm concrete is normally paint or 1200 gauge polythene over which a expected. Slabs less than 100mm are more likely minimum 50mm, 1:3 screed should be laid. • Using preservative-treated replacement timbers localised basis where required; to be vulnerable to rising damp, especially if the The DPM should lap with the DPC. (pre-treated); concrete is of poor quality; • Introducing support measures such as isolating • If there are proposals to increase the load 12.1.3.6 Existing suspended timber floors timbers from walls and provision of ventilation on the existing slab, such as building a masonry Where it is proposed to keep the existing ground between timbers and the walls. wall, then the new wall should be built on an floor, the existing floorboards / finish should be lifted adequate foundation or the existing slab proved to ascertain the condition of the timber joists / for adequacy by calculation; wall plates and a report carried out by a Structural with damp brickwork and where ventilation and • Are there any gaps between the skirting and Engineer as well as a specialist relating to insect heating are inadequate. Therefore, particular floor suggesting settlement of the slab? Is the fill infestation and fungal attack. attention should be paid to cellars, basements and beneath the slab over 600mm? sub-floors and also behind paneling. • Are there any cracks in the floor slab due When deciding if an existing ground floor is to settlement? If the slab has settled it may be adequate, there are a number of areas which practical to re-level the floor with a new screed should be addressed, these include: or self-leveling compound. Before undertaking any works to a slab which has settled, it must be • An adequate DPC to walls / sleeper walls; ascertained whether the settlement has • All timbers must be free from rot and Technical Manual V6: TS-011a-6.00-010413 Dry rot commonly occurs when timber is in contact Figure 4 - Typical example of repairs to floor joists stopped. insect infestation; • Has the slab heaved? Clay heave can be • Adequate ventilation to the sub-floor, (please attributed to the swelling of the clay subsoil note, many sub-floor voids will require cleaning when there is a recovery of the desiccated out to achieve ventilation and reduce zone following the removal of a tree. Where a dampness); slab has heaved, further investigation is • Adequate foundations supporting sleeper walls; necessary to determine the reason for this and • Joists are of sufficient size and span; CHAPTER 12: CONVERSION AND REFURBISHMENT CHAPTER 12: CONVERSION AND REFURBISHMENT • Are any load-bearing internal walls built off The use of existing surface water drainage may be acceptable, providing that it can be shown to be floor joists; • Have joists been weakened by excessive carrying the water away from the building. notching or drilling; • Adequate trimming to hearth; 12.1.4 Superstructure • Adequate strutting of joist. 12.1.4.1 Structural repairs Prior to undertaking structural repairs, it is essential that the root cause of the structural defect has been remedied by underpinning, addition of adequate lateral restraint, buttressing, etc. Strengthening works to the structure may also be necessary to accommodate increased or modified loads. 12.1.4.2 Masonry walls To provide an acceptable level of protection against ingress of rain water, any retained solid masonry external walls should either: Figure 5 - Strengthening excessively notched joist Technical Manual V6: TS-011a-6.00-010413 • Be fully lined internally with an independent timber or metal stud wall; 12.1.3.7 Drainage • Be clad externally with a rain screen or other Where it is intended to use the existing below ground foul drainage system, a CCTV survey • Comply with the requirements of BS 5628. should be carried out to ascertain the condition of the drains and manholes. The survey should cover size, type of drain, falls and its adequacy to take the proposed discharge. An air or water test could protective measure; Figure 6 - Typical independent internal lining Where damage has occurred to walls, the cause needs to be investigated. Likely reasons for the damage include: • Ground movement – foundation failure, settlement, subsidence, chemical attack; • Thermal movement – thermal expansion of wall due to temperature changes; • Roof spread – pitched roofs not properly tied, spreading at eaves; • External and internal walls not bonded together; • Wall tie corrosion; • Lintels inadequate over openings; also be carried out. CHAPTER 12 CHAPTER 12: CONVERSION AND REFURBISHMENT CHAPTER 12: CONVERSION AND REFURBISHMENT • Sulphate attack – water soluble sulphates Where it is intended to provide buttressing walls to used on the party walls. This junction should be attack cement based mortar, normally in a wet support out of plumb and / or bulging walls, they exposed when undertaking a conversion and if environment, i.e., below ground level and should be designed by an Engineer. the bond is inadequate, a suitable stitching detail parapet walls; incorporated. Design by a Chartered Structural • Frost attack; In raised tie roofs (where no ceiling ties are • Bonding timbers present and subject to rot provided at eaves level), lateral spread of the brickwork just below eaves level may have and shrinkage; • Ineffective or no lateral support at floor and occurred because the roof has deflected. In such cases, it is necessary to prop the roof and to rebuild roof level; • Moisture ingress. the affected part of the wall. Cracking in masonry walls Bonding timbers Minor cracking can be defined as cracking These are common in Georgian buildings and which occurs in the mortar joints and which does were laid in the internal skin of the wall to reinforce not extend through the masonry components. it and to provide fixings for paneling, etc. With Providing that the crack is no wider than 4mm and the low compressive strength of lime mortar and there has been no lateral displacement of the wall, general timber decay, the bond timber compresses the wall can be re-pointed. under load. As the timber is on the inner skin, the compression causes bulging outwards which may Technical Manual V6: TS-011a-6.00-010413 Major cracking affects the structural integrity of the be apparent on the external face. Normally, bond wall and investigation should be undertaken to find timbers should be exposed during the conversion the cause of the problem. and removed in short lengths and replaced with bonded masonry. Walls out of plumb / bulging Where walls are more than 25mm out of plumb External and internal walls not bonded together or bulge more than 10mm within a storey height, A common defect in properties up to the 1920s a Structural Engineer should comment on the is the lack of bonding / tie of party walls to the stability. The wall may need to be rebuilt or external wall. strengthening works undertaken. Different bricks and bricklayers were often used, with the poorer quality materials and labour being Engineer may be required. Figure 7 - Typical examples of rectifying unbounded walls Arches and lintels The existing timber lintels can be retained if they support the structural walls and it can be shown that the lintel is adequate for its purpose, i.e., there is no sign of any structural movement, loads will not be increased and the timbers are free from rot and insect infestation; therefore the lintel can be retained. In order to ensure that a lintel is free from rot, a percentage of all lintels should be exposed at both ends and on the outer face for openings in external walls. Where movement has occurred and the timber lintel is inadequate, the lintel should be replaced with either a concrete or steel lintel. CHAPTER 12: CONVERSION AND REFURBISHMENT CHAPTER 12: CONVERSION AND REFURBISHMENT Where cracking has occurred in masonry Where wall ties have corroded to an extent that it is insect infestation, the partition can remain. Where arches, it will be necessary to rebuild the arched serious enough to threaten the stability of the wall or there are defects, i.e., the floor sags on the line of construction. In cases where failure has occurred building, a Structural Engineer should be appointed the partition and there is distortion of door heads, due to the low pitch of the arch, it may be to determine the necessary remedial works. then additional strengthening works should be necessary to incorporate a lintel. undertaken. 12.1.4.3 Internal walls Wall tie corrosion New door openings cut into an existing trussed Cavity walls have been constructed since 1850, but it Existing masonry partition should be overseen by a qualified was not until 1920 that this form of construction was Where a wall is adequately founded or supported Structural Engineer, as it can adversely affect the widely adopted. It is important when undertaking a on a beam which shows no signs of distress, it can triangulation of the truss. conversion to confirm the construction of the external remain providing there is no increase in load onto wall. In cases where headers are incorporated into the wall. Any increase in load should be justified 12.1.4.4 Timber floors above ground level the bond of the external brickwork, the Site Audit by calculation. However, masonry supported on Existing timber floor joists can be retained within Surveyor should investigate the wall construction, as timber beams should be avoided. the building, providing that they are adequate for many properties in the Victorian period were built their purpose. with either a 215mm outer leaf and cavity behind, or In older properties, it is possible that flitch beams a 215mm inner leaf, cavity and a half brick outer leaf and bessemer’s may be supporting masonry walls with snapped headers. and these should be examined by an appropriate expert to ascertain their capability to carry the load. Initial evidence of cavity wall failure can include The following points should be considered: • Joists are of sufficient size for the span; • Load on the floor is not being increased; Technical Manual V6: TS-011a-6.00-010413 cracking of bed joints in mortar (typically every Existing studwork • Joists have not been weakened by excessive sixth course). This is due to the expansion of the Many properties before 1880 have trussed internal wall tie as it corrodes. partitions, usually located approximately halfway • Ends of joists are free from rot; notching and / or drilling; back in the depth of the property. Often, these • All timbers to be treated for insect infestation Bulging of the external leaf could also indicate that walls are load-bearing and continue up through the ties have failed. the building and carry floor and roof loads on to • No masonry walls are built off timber joists; the foundations. • Appropriate strutting is provided. and wood rot; Where there is wall tie corrosion or inadequate ties, a specialist company should be employed If a timber partition is load-bearing, providing to provide a report which includes measures to it is adequate and the loads are not being overcome these defects. increased and the timber is free from rot and CHAPTER 12 CHAPTER 12: CONVERSION AND REFURBISHMENT CHAPTER 12: CONVERSION AND REFURBISHMENT Alterations to existing openings An appraisal of the existing building should be be provided to prove the adequacy of the building Where existing openings are to be filled with carried out by an experienced and qualified and foundations. masonry, the new work should be adequately Structural Engineer taking into account the bonded to the existing and weather resistance of proposals for the change of use. the wall maintained. However, if it is a party wall, then it should comply with the requirements for Concrete framed buildings Where the building is of concrete construction, This will include: additional reports are needed for: sound insulation. • Condition of the structural frame including •Carbonation; 12.1.4.5 Walls of special construction joints; •Chlorination. If it is intended to retain walls of special • Proposals to increase loadings on the structure construction such as wattle and daub, Tudor, mud walls (cob) etc., they should be altered so • Alterations to existing load paths; carbonation in association with inadequate depth as to form a non-structural element, e.g., by the • Alterations to stability systems; of cover to reinforcement and chlorine penetration, incorporation of an additional load-bearing wall • Changes in environmental exposure; due to de-icing salts and admixtures used to or framing which provides lateral support to the • Recommendations to cover additional reports accelerate the setting and hardening of concrete wall and supports all structural loads previously in temperatures at or below freezing point. and foundations; and testing by specialists. The two major causes of corrosion in concrete are supported by the wall. It will also be necessary to ensure that the wall provides an adequate barrier The floor loads on the building may decrease Carbonation involves a reaction of carbon dioxide to the passage of rainwater into the fabric or the as they will now be for domestic use only, where in the air with the free lime present in the concrete. inside of the building. previously they were for example, offices. Over a period of time, this reduces the pH level of Technical Manual V6: TS-011a-6.00-010413 the concrete. Unfortunately, due to the inherent risks and A statement from a qualified Structural Engineer planning conditions on these types of confirming, where appropriate, that the existing With a reduction in the alkalinity, and the presence developments, it must be noted that it may not be foundation design is acceptable for the new loads of both water and oxygen, corrosion of the possible for MDIS to provide warranty. subject to the building showing no signs of distress, embedded steel will occur. i.e., movement, cracking, etc., will be acceptable in 12.1.4.6 Concrete / steel framed structures such circumstances. Where the scheme involves converting a concrete Visual surveys on concrete structures are a starting point to gather information. However, care should or steel framed building into dwellings, the following Where the intention is to increase the load on the be taken as the concrete structure may not show guidance is given. existing structure, e.g., by the introduction of an any obvious signs of corrosion and yet corrosion of additional floor, then structural calculations should the reinforcement may be occurring. CHAPTER 12: CONVERSION AND REFURBISHMENT CHAPTER 12: CONVERSION AND REFURBISHMENT It is important that a second stage survey aggregate within the concrete itself. The chemical on avoidance have reduced the risk of problems in incorporates the following: reaction creates a gel material which absorbs new buildings to very small proportions. water, expands, and in turn creates tremendous • Chemical tests on the concrete structure to pressures in the pores of the concrete surface and Consequently, on any refurbishment project where ascertain if corrosion of the steelwork is or is subsequent cracking. For a damaging reaction to the existing structure is concrete frame, the Site likely to occur; occur, the following need to be present in sufficient Audit Surveyor will request copies of the following to quantities: identify the presence or otherwise of ASR: • Depth of carbonation can be assessed either on-site or in the laboratory and the depth of the reinforcement measured. This allows those areas • High alkali cement or a high cement content • Desk studies undertaken to identify materials of risk to be identified; - may also arise from salt contamination during • Chloride ion content can be taken by analysis batching / mixing; • Core sampling and detailed chemical testing. • Reactive aggregate - siliceous materials such of a drilled dust sample from the concrete. as flint and quartz as well as recycled used in original construction; If ASR is identified, the following possible remedial Where concrete repairs are necessary, they should aggregates; works will need to be assessed by the project’s be carried out by a Specialist Contractor. • Moisture – exposure to rain or condensation. Design Engineer and details put to Site Audit High alumina cement concrete (HACC) If any one of these factors is absent then the ASR Where HACC has been used in a building and cannot take place. Once cracking occurs, the • Critical examination of the robustness of the intentions are to keep the existing structure, structure can deteriorate further as water entering consideration should be given to: the cracks generates reinforcement corrosion and • Measures to the amount of water available to this, in conjunction with the freeze / thaw cycle, the structure - any weatherproofing or cladding can result in additional cracking and so on. should not impair the ability of the structure to dry naturally; Surveyors for consideration: Technical Manual V6: TS-011a-6.00-010413 • The structure being free from obvious signs of deterioration; the reinforcement; • The building being weather tight; Affected concrete often exhibits surface cracking • Limited strengthening of the structure; • Structural calculations being provided to show in the pattern of a star and heavily loaded sections • Partial or full demolition followed by re-building. that the floors and roof can solely carry the may exhibit cracks along the line of the main loads imposed on them. reinforcement. Furthermore, any alterations to the weatherproof envelope will need to be considered to ensure Alkali silica reaction (ASR) Defects in structures attributable to performance that the concrete elements are not exposed to ASR occurs when the strongly alkaline cement of concrete are relatively rare in the UK. Increased additional sources of moisture. begins to dissolve susceptible sand and awareness of ASR and the publication of guidance CHAPTER 12 CHAPTER 12: CONVERSION AND REFURBISHMENT CHAPTER 12: CONVERSION AND REFURBISHMENT Steel framed buildings the environment intends to remain dry, no further In addition to this, the Engineer should comment In addition to any structural reports, a visual treatment of the steel will be required. on the following: out to assess the extent of any corrosion of the Where the proposals involve the steelwork in a ‘wet’ • Determine age of the building and framework. environment such as kitchens and bathrooms, it should be adequately protected. • Assess how its construction has faired; inspection of the steel frame should be carried Where corrosion is present, accurate measurements materials used; • Justify the loadings by calculation; can be made using an ultrasonic gauge. Data Bimetallic corrosion • Identify areas where additional testing collected can then compare the thickness of steel This should be considered in the existing and sections against the original steelwork drawings, proposed structure. British Standards and Historical Structural Steelwork and / or opening up is necessary. If the proposed loads remain unchanged or Handbook to ascertain if the structural frame is Bimetallic corrosion occurs where two different are reduced, as will probably be the case, and adequate for the proposed loads. metals are in electrical contact and are bridged by it can be shown that the existing structure has water or water containing other chemicals to form not suffered any deterioration due to corrosion or Exterior steelwork should be inspected. Where an electrolyte. A current passes through the solution deflection of structural members, etc., the building corrosion is visible, the steel can be grit blasted, from the base metal to the noble metal and as a may only require localised structural alterations. cleaned and recoated. consequence, the noble metal remains protected and the base metal suffers increased corrosion. Perimeter steelwork in direct contact with the outer Where the intention is to increase loads, carry out major structural alterations, or the existing building Technical Manual V6: TS-011a-6.00-010413 leaf of the building can be prone to corrosion, Where there is a possibility of this occurring or if it is under designed, a Structural Engineer should particularly in older properties. A sign indicating has already occurred, advice should be taken from comment on this and provide calculations to justify that this has happened is the displacement of a specialist on how to deal with it. the proposals. the steelwork caused by corrosion. During the Cast iron, wrought iron and mild steel structures 12.1.4.7 Filler joist floors conversion process, the appropriate repairs / Many older buildings which are converted into Many buildings of late Victorian and Edwardian replacement should be carried out. dwellings, e.g., warehouses, cotton mills, etc. were period were built with floors constructed of built using cast iron, wrought iron or mild steel. clinker concrete supported by embedded iron Interior steelwork normally corrosion of When the intention is to keep the existing structural or steel joists. The concrete produced with clinker unprotected steelwork within the interior of a elements, an appraisal of the existing building is aggregate was porous and therefore provided building is low with only superficial rusting. necessary. poor corrosive protection to the metal. the external masonry due to the expansion of Providing that a visual inspection confirms this and CHAPTER 12: CONVERSION AND REFURBISHMENT CHAPTER 12: CONVERSION AND REFURBISHMENT The clinker also contains particles of un-burnt Roof structure Adequate ventilation should be provided as or partially burnt coke or coal which contain It is essential that the roof structure has adequate appropriate. substantial proportions of sulphur. As the concrete strength, stiffness and dimensional accuracy is porous, the sulphur oxidises to form Sulphur appropriate for the new roof covering. All Where it is intended to re-use existing roofing tiles Dioxide (SO2) and if moisture is present, this then strengthening work should be designed by a or slates, they should have a life span of at least 15 forms Sulphuric Acid (H2SO4). Where floors have Structural Engineer. years. Common problems encountered include: In the case of replacement roof coverings where been subject to the weather for any length of time, severe corrosion of the embedded iron or steelwork is likely to have occurred. no extra load is incurred, it may still be necessary • Excessive spans of rafters, purlins, binder to strengthen the roof structure if the roof has When considering a conversion in a building deflected. which has filler joist floors, it is important to firstly • Inadequate ties between rafters and ceiling ties; investigate if the floors have been subject to damp • Insufficient number of collar ties at purlin level; conditions and whether any significant corrosion • Decay of rafter feet and valley beams; has taken place. • Settlement of purlin supports; Weather resistance of walls and cladding • Lateral spread of raised-tie roofs. Existing solid brick or stone walls are unlikely to and ceiling joists; Particular attention should also be made during 12.1.4.9 Claddings be acceptable as weather resisting, although Technical Manual V6: TS-011a-6.00-010413 the conversion to ensure that the floor remains Roof coverings consideration of the exposure category of the dry and this could include providing a temporary Systematic replacement of all roof coverings, building and porosity of the masonry will be given, covering if removal of the existing roof is necessary. including associated support systems such as i.e., do existing non-Gypsum based internal linings battens, felt, flat roof decking, fascias, soffits and allow for greater insulation and evaporation than flashings should be carried out, unless it can be Gypsum Plasters alone? It is anticipated that in all shown that the existing roof covering is adequate. buildings, at least one of the additional treatments 12.1.4.8 Timber roofs Surveying roof timbers noted, will be required and this must include All roof timbers should be surveyed by a specialist Fixing of slates, tiles and the condition of existing and any necessary treatment carried out. fixings, e.g., nails and clips should be examined if the intention is to keep the roof covering. Particular attention should be given to rafter feet, appropriate insulation. However, all solid masonry wall situations will require a Specialist’s Report to identify the extent of wall plates and valley timbers as these often show A specialist report will be required to confirm the signs of rot. adequacy of the existing roof covering and to any necessary remedial treatment. determine whether timber treatment is required. CHAPTER 12 CHAPTER 12: CONVERSION AND REFURBISHMENT CHAPTER 12: CONVERSION AND REFURBISHMENT External treatments These include: Existing claddings can be retained if it can be shown that: • Increased risk of damp penetration caused by filling of cavities with insulation; • Independent metal or timber framed systems - • Maintaining the robustness of the external and these should not be fixed to the existing internal wall surfaces by the provision of • The system is maintaining the integrity of masonry walls, but fixed at the ‘head and adequate mechanical protection over base’ to avoid direct contact. Ventilation should insulation materials, e.g., externally applied • It is adequately fixed and the expected life the building; be provided to avoid build up of condensation insulation systems with render coat mechanical span of the fixings, where appropriate is in between the masonry and the inner lining system; protection; excess of 15 years; • New internal walls – these would normally be • Avoidance of cold bridges around openings • The cladding material is free from any defects; formed in block work and must be adequately and where structural elements extend through • Adequate provision for movement has founded and where necessary tied to the thickness of the building envelope; retained and new elements of structure. • Repeating thermal bridging must be been allowed. considered, e.g., internal metal framed walls If the above situations cannot be satisfied, then a Control of damp penetration should be used in conjunction with thermally new external cladding or render system will need Measures should be taken to ensure that thermal insulated plaster board. to be installed. insulation in cavities does not encourage the passage of damp from the ground or from the Internal treatments exterior of the building to the inside of the building. An alternative to preventing moisture penetration Technical Manual V6: TS-011a-6.00-010413 by using externally applied claddings and renders Thermal insulation of walls and claddings are internally applied methods. Various methods exist to upgrade the thermal insulation of existing walls and floors. Regardless Systems are available that are installed on of the methods adopted, it is essential that risks the inside of existing walls to prevent moisture associated with increased thermal insulation are penetration reaching the internal accommodation. minimised, including: • Surface condensation caused by improvements to draught proofing of the building; • Interstitial condensation caused by moisture laden air passing from the dwelling to within the fabric of the structure and condensing on cooler surfaces; CHAPTER 12: CONVERSION AND REFURBISHMENT CHAPTER 12: CONVERSION AND REFURBISHMENT 12.1.4.10Render application finishes Plastering work must comply with an independent Rendering for conversion / refurbishment third party and the chemical damp proof course Where the condition and bond of the existing Plaster for conversions / refurbishment must meet manufacturer’s recommendations. render can be shown to be adequate, it can Where the condition and bond of the existing Recommended plasters usually incorporate remain subject to the following exceptions: plaster can be shown to be adequate, it can adhesives to increase resistance to the passage remain with the exception of the following: of hygroscopic salts from the wall into the plaster. • If the render bridges the DPC; They should not, however, act as a vapour barrier. • Above door and window openings where it is • Where rising damp is present; Gypsum plaster should not be used in conjunction necessary to examine the type and condition • Where a chemical damp proof course is installed; with chemically injected damp proof courses. of the lintels; • At the junction of external walls and party walls to see if they are properly bonded; • Above openings to examine the make up and • Where there are signs of structural movement The plaster should not bridge the damp proof course or be in contact with the ground floor slab. required. condition of lintels; • Where there is a possibility of bond timbers Final redecoration should not be carried out until residual moisture has disappeared. Matt emulsion which may have decayed; • Where the wall is solid and the plaster is in the building and further investigation is paint is recommended for use during this period. Gypsum based. Internally drilled holes which are concealed by Where a chemically injected damp proof course skirting boards, etc., should not be plugged. Other is installed it is necessary to remove the plaster, visible holes and external holes should be plugged. Technical Manual V6: TS-011a-6.00-010413 1m above the DPC level or 600mm above any apparent salt line / dampness, whichever is the higher. Re-plastering work should be delayed as long as possible in order to encourage rapid evaporation of residual moisture and the building should be well ventilated during the drying period. CHAPTER 12 FUNCTIONAL REQUIREMENTS 12.2 NEW ELEMENTS CONNECTING TO EXISTING STRUCTURES Workmanship Design i. All workmanship must be within defined tolerances as defined i. Design and specifications shall provide a clear indication of the in Chapter 1 of this Manual. design intent and demonstrate a satisfactory level of performance. ii. All work to be carried out by a technically competent person in ii. There should be a Party Wall Agreement in accordance with the Party Wall Act (please note that this requirement will be relevant where the applicant is not the owner of the adjoining property). a workmanlike manner. Materials: iii. The separating wall between the new and existing building must meet i. All materials should be stored correctly in a manner which will not iv. The existing foundations and wall structure must be suitable to support cause damage or deterioration of the product. relevant requirements of the Building Regulations. ii. All materials, products and building systems shall be appropriate and any proposed increased loading resulting from the construction of the new dwelling. suitable for their intended purpose. Technical Manual V6: TS-011a-6.00-010413 iii. The structure shall, unless specifically agreed otherwise with the v. The junction of the new walls to the existing walls must ensure that warranty provider, have a life of not less than 60 years. Individual components and assemblies, not integral to the structure, may have vi. An effective damp proof course should be present in the existing wall, a lesser durability but not in any circumstances less than 15 years. linked to the new damp proof course and damp proof membrane of the new home. dampness cannot track back into the new home or the existing home. vii. At the junction of the existing and new structures, detailing should allow for differential movement without cracking. Any settlement should be limited to 2mm - 3mm, which would not normally adversely affect the roof covering. viii.The materials used for construction must meet the relevant Building Regulations and other statutory requirements, British Standards and Euro-Codes. CHAPTER 12: CONVERSION AND REFURBISHMENT CHAPTER 12: CONVERSION AND REFURBISHMENT 12.2.1 Introduction 12.2.3 Separating walls The existing wall should also be appraised to A number of residential developments are The separating wall between the new and existing determine that it is structurally stable and suitable attached to existing buildings. The existing building must meet relevant requirements of the to support additional loadings. elements that form part of the new structure must Building Regulations. 12.2.5 meet the Functional Requirements of the warranty. New wall junctions The details below give some guidance on the Confirmation should be provided where the The junction of the new walls to the existing walls minimum information and standards required to existing wall is to be upgraded to meet current must ensure that dampness cannot track back into meet the Functional Requirements. Building Regulations, in particular, meeting the the new home or the existing home. relevant sound insulation and fire separation 12.2.2 Party Wall Agreement requirements. The structural integrity of the existing The detailing of this junction is critical to ensure There should be a Party Wall Agreement in wall and its resistance to ground moisture should that moisture ingress does not occur between accordance with the Party Wall Act (Please also meet current standards. the new walls and existing. Typical details that are note that this requirement will be relevant where acceptable are indicated in Figure 8 and Figure 9. the applicant is not the owner of the adjoining 12.2.4 property). The existing foundations and wall structure must Existing foundations be suitable to support any proposed increased It is highly likely that improvements to an existing loading resulting from the construction of the new wall are required to meet the requirements of the dwelling. warranty. This may include underpinning, injected Technical Manual V6: TS-011a-6.00-010413 damp proof courses and internal linings. A signed Foundations to the existing wall should be exposed Party Wall Agreement provides evidence that the and assessed for suitability to support additional adjacent building owner consents to any potential loadings. It is important to protect existing alterations. foundations at all times and care must be taken not to ‘undermine’ existing foundations when Further guidance on the Party Wall Act can clearing the site or reducing levels. be found on the Planning Portal website www.planningportal.gov.uk Where existing foundations require underpinning, a design by a Chartered Structural Engineer A Party Wall Act Agreement is not required if the should be provided and approved by the Site Audit Developer owns the adjacent building which will Surveyor prior to work commencing on-site. be connected to the new development. Figure 8 - Bonding new walls to existing solid masonry wall CHAPTER 12 CHAPTER 12: CONVERSION AND REFURBISHMENT CHAPTER 12: CONVERSION AND REFURBISHMENT • A slate DPC is considered as acceptable if the existing wall incorporates an independent wall lining system to the inner face of the new dwelling. The new DPC should lap the existing DPC by at least 100mm. 12.2.7 Existing and new structure junctions At the junction of the existing and new structures, detailing should allow for differential movement without cracking. Any settlement should be limited to 2mm - 3mm, which would not normally adversely affect the roof covering. Typical details of bonding new walls to existing are Figure 9 - Bonding new walls to existing cavity masonry wall 12.2.6 Damp proof course An effective damp proof course should be present Technical Manual V6: TS-011a-6.00-010413 in the existing wall, linked to the new damp proof course and damp proof membrane of the new home. Acceptable existing DPC’s are considered as: • A continuous felt or proprietary damp proof course material; • A chemical injected DPC supported by an insurance back guarantee; indicated in Figures 8 and 9. In order to prevent excessive differential movement, the new dwelling should have the same foundation type as the existing dwelling foundation type. Where the foundation types are different, e.g., new dwelling pile and beam / existing dwelling, traditional strip foundation, the new dwelling should be completely independent to the existing dwelling.