Nexus 850 prisliste.
Transcription
Nexus 850 prisliste.
Montagevejledning Frese blandeventil MixCon Anvendelse: Tekniske data: MixCon er en skoldningssikret blandeventil for varmt og koldt vand. Ved koldtvandsbrud lukker ventilen for varmtvandstilgangen inden 4 sekunder. Blandevandstemperaturen indstilles ved at dreje plastgrebet mod "+" for højere temperatur og mod "-" for lavere temperatur. 91697 vers. 2 August 07 Messing ABS, sort. Rustfri stål. Voks. EPDM. Trykklasse Max. tryk: Min. tryk: Max. trykforhold: eller 10 bar. 0,2 bar. 5:1 (varmt:koldt koldt:varmt) Temperatur Blandevandstemperatur: Varmtvandstemperatur: Koldtvandstemperatur: 30-60°C 50-80°C 05-30°C Varm Kold For optimal skoldningssikring skal blandetemperaturen ligge min. 10°C under varmtvandstemperaturen. Godkendelse: Mix VA-godkendt. Produktprogram/Målskema Dim. DN 20 DN 20 DN 20 Trykfaldsdiagram Tilslutning DN20/M/M/M* Ø15/Cu-rør Ø22/Cu-rør Frese nr. 47-2643 47-2677 47-2688 VVS nr. H1 [mm] H[mm] L[mm] Vægt [g] 723413.006 132 70 520 54 723414.005 139 88 690 61 723414.002 140 90 645 62 * 3/4" galv. rør Tilbehør til nippel/nippel Kontraventil Ø15 Ø22 Tryk kPa 100 Frese nr. 38-0835 38-0834 VVS nr. 723414.815 723414.822 Kontraventilen skal monteres i koldt- og varmtvandstil-gangen, når MixCon installeres i brugsvandsinstallationer. 10 H Dim Alle MixCon blandeventiler er individuelt testet og produceret i henhold til kvalitetsstyringssystemet ISO 9001 for at sikre ensartet kvalitet og funktionalitet. Ventilhus: Greb: Fjedre: Element: O-ringe: Dim. Ventilens indstilling låses ved at afmontere grebet og dreje det 180°. Derefter monteres grebet igen. Montagevejledning Frese blandeventil MixCon H1 H1 Dim. L Dim. L Snittegning af kontraventil 1 0,1 1 Flow l/s Temp. varm: Temp. kold: Temp. blandet: 50°C 12°C 40°C H Mountinginstruction Frese Mixing Valve MixCon Mountinginstruction Frese Mixing Valve MixCon Application Technical data: MixCon is a fail-safe mixing valve for hot and cold water. Valve body: Control handle: Springs: Element: O-rings: Pressure range: Max. pressure: Min. pressure: Max. Pressure ratio: If the cold water fails the valve shuts off the hot water supply within 4 seconds. 91697 vers. 2 August 07 Hot Cold 30-60°C 50-80°C 05-30°C The optimum protection against scalding is achieved if the mixed water temperature is at least 100C below the hot water temperature. Approval: Approved by the Danish VA-Authorities Mix Productprogramme/Dimensions Dim. DN 20 DN 20 DN 20 Connection DN20/fem/fem/fem* Ø15/Cu-tube Ø22/Cu-tube Frese no. H1 [mm] H[mm] L[mm] Weight [g] 47-2643 132 70 54 520 47-2677 139 88 61 690 47-2688 140 90 62 645 Pressure Trykfaldsdiagram drop graph * 3/4" galvanized pipe Accessories for male/male Non-return cartridge Ø15 Ø22 Frese no. 38-0835 38-0834 Non-return cartridge must be mounted on the hot and cold inlet, when installed in domestic water installations. 10 H Dim Pressure kPa 100 Dim. All MixCon mixing valves are tested separately and produced in accordance with the ISO 9001 Quality System to ensure uniform quality and functionality. 10 bar. 0,2 bar. 5:1 (Hot:cold or cold:hot) Temperature Mixed water temperature: Hot water temperature: Cold water temperature: The mixed water temperature is set by turning the plastic control handle towards "+" to obtain higher temperatures, and towards "-" to obtain lower temperatures. The temperature setting of the valve is locked by dismantling the handle and turning it 180°. Then replace the handle. Brass CW602N ABS, black Stainless steel Wax EPDM. H1 H1 Dim. L Dim. L Section view of Non-return cartridge 1 0.1 1 Flow l/s Hot water temperature: 50°C Cold water temperature: 12°C Mixed water temperature: 40°C H