Heating-Cooling Catalog GB 20-12
Transcription
Heating-Cooling Catalog GB 20-12
Heating and Cooling Catalog About Actaris Actaris is a world leader in the design and manufacture of meters and associated systems for the management of water, heat, electricity and gas consumption. With a strong experience of more than 130 years, the history of Actaris started in 1872 by the set up of a workshop for gas meters which became in 1881 "La Compagnie des Compteurs" including water and electricity activities. In 1970, the company is taken over by Schlumberger who sold it in 2001, the year of creation of Actaris. Sales offices Water manufacturing sites Heat manufacturing sites Partners 2 Actaris innovative products and systems integrating the latest technologies are specially designed to satisfy the needs of energy and water suppliers, services companies and industrial organisations. The group is active in more than 30 countries with a strong presence in Europe, Africa, Asia and South America. Metrology Classes according to EN 1434 and MID < Flow Meter Tolerance +5% +2% Qp Qi Qs ( Qi = Qp / 100 EFM = ± 2 + 0.02 Qs = 2 x Qp -2% -5% Error Class 2 Most Common Class 1 ≥ 100 m3/h Class 2 Qp Q ) Class 3 < Calculator Tolerance < Sensors Tolerance +1.5% +3.5% +0.5% +0.5% ΔΘmin ΔΘmax ΔΘmin -0.5% -0.5% -1.5% -3.5% ( EC = ± 0.5 + ΔΘmin ΔΘ ) ΔΘmax ( ES = ± 0.5 + 3 ΔΘmin ΔΘ ) < Complete meter ( ECM = ± 3 + 4 Qp ΔΘmin + 0.02 Q ΔΘ ) Environment Condition Classes < Class A < Class B < Class C • Indoor usage • Residential applications • Low relative humidity conditions • Normal electromagnetic conditions • Outdoor usage • Residential applications • Normal relative humidity conditions • Normal electromagnetic conditions • Indoor usage • Industrial application • Normal relative humidity conditions • High electromagnetic conditions 3 < Temperature Sensors Installation • Sensor pockets must be installed in the supply and return pipe of the circuit where the flow is fitting. • Do not install sensor pockets on a high point of the network. • Install the sensor pocket downstream of the flow meter. • Pockets must be mounted with an angle between 45° and 90°. • Temperature sensors are paired delivered. Always mount them matched one to one (same ID number). 4 Heating Application Cooling Application < Temperature sensors installation best practices for Heating application < Temperature sensors installation best practices for Cooling and Combined applications • Sensor pockets and connected sleeves must be installed head upwards. • To prevent water condensation, sensor pockets and connected sleeves must be installed head downwards. • To prevent rusted terminals, head temperature sensors should be potted with resin. • Never use oil or grease to lubricate pockets. Use silicon instead. < Integral-V MaXX - Compact Heat Meter Nominal Diameter Max. Min. Start flow Body Pipe Nominal flow Qp DN flow Qs flow Qi Qstart length connection pressure Temperature range m3/h mm m3/h L/h L/h mm bar °C 20 … 90 0.6 15 1.5 6 1.5 110 G 3/4 A 16 1.5 15 2.5 15 2.5 110 G 3/4 A 16 20 … 90 2.5 20 3.75 25 3.75 130 G1 A 16 20 … 90 Integral-V MaXX Energy Calculator Metrology exceeds PTB, DRIRE, OIML, EN 1434 Temperature range 20 … 90 °C / Option: 20 … 140 °C Temperature difference 3 … 70 °K / Option: 3 … 120 °K Temperature sensor type Pt100, 2 wire Display LCD - 7 digits Back-up memory EEPROM Power supply 3.6 V, 10 year Lithium battery Protection class IP54 Environmental class Class C acc. EN 1434 < High metrology performances Ambient temperature 5 … 55 °C < Optimised dimensions Pulse value 10 or 100 liters/pulse < Modular structure Options Boards < Pre-equipped for communication The Integral-V MaXX is pre-equipped for communication. Different option boards can be plugged simply into the meter on site without breaking metrological seals and start working automatically. Available boards: < Board 1: M-Bus + 4 external Water meters < Board 2: E/V Repetition 5 < CF ECHO II - Ultrasonic Compact Meter Nominal Diameter Max. Nominal Permanent Accidential pressure max. temp. max. temp. mm m3/h L/h L/h mm bar °C °C 0.6 15 1.2 6 1.2 110 G 3/4 B 16 130 150 20 1.2 6 1.2 130 G1 B 16 130 150 20 1.2 6 1.2 190 G1 B 16 130 150 20 1.2 6 1.2 190 Flanges 25 130 150 2.5 < Ease of installation 3.5 < Pre-equipped for communication 6 Options Boards The CF ECHO II is pre-equipped for communication. Different option boards can be plugged simply into the meter and start working automatically. Pipe length connection m3/h < High metrology < Easy reading Start flow Body flow Qs flow Qi Qstart 1.5 < Advanced functions Min. flow Qp DN 10 15 15 3 15 3 110 G 3/4 B 16 130 150 20 3 15 3 130 G1 B 16 130 150 20 3 15 3 190 G1 B 16 130 150 20 3 15 3 190 Flanges 25 130 150 20 5 25 5 130 G1 B 16 130 150 20 5 25 5 190 G1 B 16 130 150 20 5 25 5 190 Flanges 25 130 150 25 5 25 5 260 G 11/4 B 16 130 150 25 7 35 7 260 G 11/4 B 16 130 150 25 7 35 7 260 Flanges 25 130 150 40 7 35 7 300 Flanges 25 130 150 25 12 60 12 260 G 11/4 B 16 130 150 25 12 60 12 260 Flanges 25 130 150 32 12 60 12 260 G 11/2 B 16 130 150 40 12 60 12 300 Flanges 25 130 150 50 12 60 12 270 Flanges 25 130 150 40 20 100 20 300 G2B 16 130 150 40 20 100 20 300 Flanges 25 130 150 50 20 100 20 270 Flanges 25 130 150 50 30 150 30 270 Flanges 25 130 150 Available boards: < Board 1: M-Bus + E/V Repetition < Board 2: M-Bus + 2 external Water meters < Board 3: Modem + 2 external Water meters < Board 4: LON + 2 external Water meters < Board 5: RF + 2 external Water meters CF ECHO II Calculator Temperature range 0 … 180 °C Temperature difference 3 … 160 °K Temperature sensor type Pt100 or Pt500, 2 wire Temperature sensor (Qp 0.6 to 2.5 m3/h) Direct immersion or pocket type probes integrated in the flow meter body Cable length to flow meter From 0.4 to 10 m (Typical 1.5, 3 m) Back-up memory EEPROM Display LCD - 7 digits Protection class IP64 Environmental class Class C acc. EN 1434 Ambient temperature 5 … 55 °C Optical interface According to EN 60870-5 Power supply Main - 230 V Standard life-time lithium battery (6 years typical) Long life-time lithium battery (12 years typical) CF ECHO II Testing Pulse Value (Qp)* cm3/impuls * Testing at certified laboratories. 6 0.6 1.5 2.5 3.5 6 10 15 5 10 20 25 50 100 100 < US ECHO II - Ultrasonic Flow Meter Nominal Diameter Max. Min. Start flow Body Pipe Nominal Permanent Accidential length connection pressure max. temp. max. temp. flow Qp DN flow Qs flow Qi Qstart m3/h mm m3/h L/h L/h mm bar °C °C 0.6 15 1.2 6 1.2 110 G 3/4 B 16 130 150 20 1.2 6 1.2 130 G1 B 16 130 150 20 1.2 6 1.2 190 G1 B 16 130 150 20 1.2 6 1.2 190 Flanges 25 130 150 15 3 15 3 110 G 3/4 B 16 130 150 20 3 15 3 130 G1 B 16 130 150 20 3 15 3 190 G1 B 16 130 150 20 3 15 3 190 Flanges 25 130 150 20 5 25 5 130 G1 B 16 130 150 20 5 25 5 190 G1 B 16 130 150 20 5 25 5 190 Flanges 25 130 150 25 5 25 5 260 G 11/4 B 16 130 150 25 7 35 7 260 G 11/4 B 16 130 150 25 7 35 7 260 Flanges 25 130 150 40 7 35 7 300 Flanges 25 130 150 1.5 2.5 3.5 6 10 15 25 12 60 12 260 G 11/4 B 16 130 150 25 12 60 12 260 Flanges 25 130 150 32 12 60 12 260 G 11/2 B 16 130 150 40 12 60 12 300 Flanges 25 130 150 50 12 60 12 270 Flanges 25 130 150 40 20 100 20 300 G2B 16 130 150 40 20 100 20 300 Flanges 25 130 150 50 20 100 20 270 Flanges 25 130 150 50 30 150 30 270 Flanges 25 130 150 Threaded version Flanged version < High accuracy < Robustness < Ease of installation Pulse Value (Qp) 0.6 1.5 2.5 3.5 6 10 15 Pulses (L/p)* 1, 2.5 1, 2.5 1, 2.5 1, 2.5, 10, 25 1, 2.5, 10, 25 1, 2.5, 10, 25 10, 25, 100, 250 Test Pulses (cm3/p) 5 10 20 25 50 100 100 < Ingress protection IP 66 / 67 or IP68 * Other available pulse value on request. 7 < CF 51 / CF 55 - Calculators CF 51 CF 51 Calculator Metrology exceeds PTB, DRIRE, OIML, EN 1434 Temperature range 0 … 180 °C Temperature difference 3 … 160 °K Temperature sensor type Pt100 or Pt500, 2 wire Display LCD - 7 digits Back-up memory EEPROM Power supply (optional) 6 or 12 year Lithium battery - 230 V main power supply Protection class IP64 Environmental class Class C acc. EN 1434 Ambient temperature 5 … 55 °C Pulse value (programmable) 1 / 2.5 / 10 / 25 / 100 / 250 / 1000 L < Plug and play communication options boards Optical interface According to EN 60870-5 < Bonus calculator CF 55 Calculator < Peak values Metrology exceeds PTB, DRIRE, OIML, EN 1434 Temperature range 0 … 180 °C < Modular design < 2 wire CF 55 Approved Temperature difference 3 … 160 °K Technical Temperature difference 1 … 160 °K Temperature sensor type Pt100 or Pt500, 4 wire Display LCD - 7 digits Back-up memory EEPROM Power supply (optional) 6 or 12 year Lithium battery - 230 V main power supply Protection class IP64 Environmental class Class C acc. EN 1434 Ambient temperature 5 … 55 °C Pulse value L/imp or imp/L 1, 2.5, 10, 25, 100, 250, 1000 L/imp or 2.5, 4.5, 7.5, 10, 25 imp/L Optical interface According to EN 60870-5 Options Boards < Complex tariff < Powerful datalogger The CF 51 and CF 55 are pre-equipped for communication. Different option boards can be plugged simply into the meter and start working automatically. < Plug and play communication options boards Available boards: < 4 wire 8 < M-Bus + E/V Repetition < M-Bus + 2 external Water meters < Modem + 2 external Water meters < 2 x M-Bus + 2 external Water meters (available for CF 55) < LON + 2 external Water meters < RF + 2 external Water meters < CF 800 - Highly accurate and versatile communicating calculator for high end applications Technical characteristics Metrology exceeds PTB, DRIRE, OIML, EN 1434 Temperature range 0 … 180 °C Approved Temperature difference 3 … 160 °K Technical Temperature difference 1 … 160 °K Temperature sensor type Pt100 or Pt500, 4 wire shielded Display LCD - 7 digits Back-up memory EEPROM Power supply 230 VAC +10% -15% Interchangeable backup battery 3 V 2.5 Ah Protection class IP52 Environmental class Class C acc. EN 1434 Ambient temperature 5 … 55 °C Electronic circuit Microprocessor Optical interface According to EN 60870-5 Standard output Communication capacity Energy/Volume Repetition Option1 COMIO LON WORK, M-Bus, RF or Modem < High level of accuracy 4 Analogic Outputs and < Reliability 2 Relay Outputs or 2 water meters input and Communication Bus (MBus IEC 870 or MBus RS 485 C) Options Boards The CF 800 is pre-equipped for communication. Different option boards can be plugged simply into the meter and start working automatically. < Comfort < Wide range of communication systems < High end applications Available boards: < Slot 1 LON WORK or M-Bus or RF or Modem < Slot 2 • 4 Analogic Output • 2 Relay Output or 2 water meters input • Communication Bus (MBus IEC 870 or MBus RS 485 C) The configuration of all communication boards is easy and simple using the CFCS-Software and the optical interface. 9 < Temperature Sensors Pt100/Pt500 according to EN 60751 Direct immersion temperature sensors TDF50 up to 120°C - 2 wire Pipe size Cable length Application DN 15…20 1.7 m Heating/Cooling TDF50 Pocket temperature sensors THF50 pocket sensor up to 120°C - 2 wire Pipe size Cable length Application DN 15…50 1.7, 2.5 or 5 m Heating/Cooling PS123-100 pocket sensor 105 mm up to 150°C - 2 wire Pipe size Cable length Application DN 50…80 10 m Heating/Cooling PS125-100 pocket sensor 140 mm up to 150°C - 2 wire Pipe size Cable length Application DN 100…200 10 m Heating/Cooling THF50 Pocket temperature head sensors THF105 pocket sensor up to 180°C - 2 wire Pipe size Cable length Application DN 50…80 no cable, 3, 5 or 10 m Heating THF140 pocket sensor up to 180°C - 2 wire PS125-100 Pipe size Cable length Application DN 100…200 no cable, 3, 5 or 10 m Heating THF230 pocket sensor up to 180°C - 2 wire Pipe size Cable length Application DN 200…400 no cable, 5 or 10 m Heating PH142-3 pocket sensor 140 mm up to 180°C - 4 wire Pipe size Cable length Application DN 100…200 no cable Heating DN 100…200 10 or 30 m Heating/Cooling PH142-4 pocket sensor 230 mm up to 180°C - 4 wire THF140 10 Pipe size Cable length Application DN 200…400 no cable Heating DN 200…400 10 or 30 m Heating/Cooling < Heating and cooling meter connection kits < Direct Immersion Kits Kits for Direct Immersion Pipe size Type Distance pipe length Meter connection DN15 DI-A 110 3/4" DI-B 110 3/4" DI-A 130 1" DI-B 130 1" DN20 Type DI-A Kits for Pocket Sensor Pipe size Type Distance pipe length Meter connection DN15 PS-A 110 3/4" PS-B - 3/4" PS-Y - 3/4" PS-A 130 1" PS-B - 1" PS-Y - 1" PS-C 260 1" 1/4 PS-D - 1" 1/4 PS-G 260 Flanges PS-H - - DN32 PS-F - 1" 1/2 DN40 PS-E 300 2" PS-F - 2" PS-G 300 Flanges PS-H - - PS-G 270 Flanges PS-H - - PS-G 300 Flanges DN20 DN25 DN50 DN65 < Pocket Sensor Kits Type PS-A PS-H - - DN80 PS-G 300 Flanges PS-H - - DN100 PS-G 360 Flanges DN 100…200 PS-H - - DN 250…400 PS-H - - Type Ball valve with DI entry Type PS-C DI-A DI-B PS-A PS-B PS-Y PS-C PS-D PS-E PS-F PS-G PS-H Type PS-E T Piece 2 x Ball valve Pocket and welding piece 2 x Pocket and welding piece Connector set Connector set with pocket Distance pipe Type PS-H 11 < Mechanical flow meters for Heating application Woltmag WVC P16 Meter Woltmag WVC P16 / Must be installed horizontally Nominal diameter (DN) mm 50 65 80 inches 2" 2" 1/2 3" 4" Maximum flow rate (Qmax) m3/h 30 50 80 120 Nominal flow rate (Qn) m3/h 15 25 40 60 Accuracy ±2% from m3/h 2.5 5 7 10 Accuracy ±5% from m3/h 0.6 0.8 0.8 1 Max. admissible temperature Max. admissible pressure 130 bar 20 Minimum scale interval graduated L 1 Minimum scale interval read L 0.5 m3 Indicating range Woltex WEC P16 Meter Nominal diameter (DN) °C 100 999999.99 Woltex WEC P16 / May be installed in any position mm 50 65 80 100 125 150 200 inches 2" 2" 1/2 3" 4" 5" 6" 8" 10" Maximum flow rate (Qmax) m3/h 30 50 80 120 200 300 500 800 Nominal flow rate (Qn) m3/h 15 25 40 60 100 150 250 400 Accuracy ±2% from m3/h 3 5 8 15 20 25 41.6 66 Accuracy ±5% from m3/h 1.2 2 3.2 8 8 10.5 18 30 Max. admissible temperature Max. admissible pressure °C 250 130 bar 20 Minimum scale interval graduated L 1 Minimum scale interval read L 0.5 5 999999.99 9999999.9 Indicating range m3 10 Important notice In case of temperature higher than 90°C, it is recommended to consult the local safety regulation related to the acceptance of GREY IRON for the envelopes of containers. For this purpose, we indicate below the volume of the envelope of these products. DN Volume (dm3) 50 1.7 65 3.9 < Woltex flow meter for Cooling application Nominal diameter (DN) 80 4.3 100/125 7.7 150 8 200 13.5 250 22 (may be installed in any position) mm 50 65 80 100 125 150 200 250 300 400 inches 2" 2" 1/2 3" 4" 5" 6" 8" 10" 12" 16" 20" Nominal flow rate Qn m3/h 15 25 40 60 100 150 250 400 600 1 000 1 500 Max. flow rate Qmax m3/h 30 50 80 120 200 300 500 800 1 200 2 000 3 000 Accuracy ± 2% class B: Qt from m3/h 3 5 8 12 20 30 50 80 120 200 300 Accuracy ± 5% class B: Qmin from m3/h 0.45 0.75 1.2 1.8 3 4.5 7.5 12 18 30 45 50 50 - - Max. admissible temperature °C Max. admissible pressure (LP version) bar Max. admissible pressure (HP version) bar Min. scale interval Indicating range 12 L m3 500 50 20 - - - 50 - 50 50 5 50 9999999.9 99999999 < Optimag electromagnetic flow meter for Cooling application Converter characteristics Installation Integral or remote (cable length: 200m max) Power supply 90 to 250 V ac 50-60 Hz: standard 17 to 45 V ac 50-60 Hz: optional 20 to 55 V dc: optional Housing protection degree & material IP 67 - aluminium alloy housing / stainless steel cable glands Display Alphanumerical - 2 lines, 16 digits - backlit Instant flow-rate and totalization Totalization: forward, reverse, net Bi-directional flow-rate Yes Auto-zero Yes 3 programmable outputs Open collectors pulses (max.frequency 1 KHz) 0/4-20 mA powered Open collector output for flow direction OR Flow-rate OR Totalization alarm 1 programmable output Remote auto-zero OR Totalizer reset and preset OR Serial communication RS 485 standard Self-diagnostic functions Erroneous settings - empty pipe detection Working temperature range -15°C + 60°C Outputs locking (i.e. when washing) Measuring tube characteristics Available sizes DN 50 to 1000 Protection degree IP 65 standard - IP 68 on request Electrodes Aisi 316 standard Lining PTFE up to DN 125, hard rubber from DN 150 Max. water temperature Remote converter: 110°C up to DN 125, 70°C for DN ≥150 Max. admissible pressure Matching PN version (PN 10-16-25-40 available) Min. fluid conductivity 30 microS/cm Nominal diameter (DN) mm 50 65 80 100 125 inches 2” 2” 1/2 3” 4” 5” 6” Min. flow rate ±1% m3/h 1.5 2.5 3.5 5.5 9 12 Min. flow rate ±0.5% m3/h 2 3.5 5.5 8.5 13 20 Max. flow rate m3/h 50 80 120 200 300 500 Length compact PN10/16 mm 140 160 160 160 200 300 Length ISO PN10/16 mm 200 200 200 250 250 300 End connections Nominal diameter (DN) Min. flow rate ±1% 150 Flanges PN10/16 200 250 300 350 400 450 500 600 700 800 900 inches mm 8” 10” 12” 14” 16” 18” 20” 24” 28” 32” 36” 1000 40” m3/h 22 35 50 70 90 114 140 200 280 360 460 570 Min. flow rate ±0.5% m3/h 35 50 75 108 130 173 210 300 415 540 690 850 Max. flow rate m3/h 800 1 200 2 000 2 500 3 000 4 000 5 000 7 000 10 000 12 000 16 000 20 000 Length compact PN10 mm 300 300 300 350 400 450 500 600 700 800 900 1 000 Length compact PN16 mm 300 300 300 350 412 466 516 616 716 816 916 1 016 Length ISO PN10/16 mm 350 450 500 - 600 - 800 - - - - - End connections Flanges PN10 or 16 13 < Remote meter reading with M-Bus protocol CF Echo II + 2 water meters Water meters equipped with M-Bus module Integral-V MaXX CF 55 + US Echo II Other meter with M-Bus output Modems MBus/RS232 Converter 14 MbusRead software < Mobile Radio Frequency meter reading Water meters equipped with RF module CF Echo II + 2 water meters CF Echo II CF 55 + US Echo II Other meter with pulse output and Actaris RF radio 15 < Heating and Cooling test benches • Available from DN15 up to DN500 • Gravimetric or volumetric • Fully automatic HE-0037.0-GB-12.06 - © Copyright 2006, Actaris. All Rights Reserved. - Actaris reserves the right to change these specifications without prior notice. Photos: M. Khalfi. • Manual For more information, please contact your local agency. Actaris Water & Heat International 125, avenue de Paris t e l +33 1 69 93 67 60 91301 Massy cedex - France t e l +33 1 69 93 68 59 www.actaris.com fax +33 1 69 93 68 68