Cerberus PRO – C-NET devices

Transcription

Cerberus PRO – C-NET devices
Aspirating smoke detection
FDnet/C-NET
FDnet/C-NET
Operating voltage
DC 19...30 V
DC 19...30 V
Sound level
– High 33 dB
– Medium 30 dB
– Low 26 dB
– High 37 dB
– Medium 33 dB
– Low 30 dB
– 3 alarm state indicators
– Fault indicator
– Bargraph for smoke
and airflow level
– 4 alarm state indicators
– Purge, dust, fault
indicator
– Bargraph for smoke
and airflow level
Area coverage
Up to 500 m²
Alarm threshold
– Prealarm and
– Info alarm, prealarm and
fire 1 (5 parameter sets)
fire 1 (10 parameter sets)
0.14...2.0% obs/m
0.03...2.0% obs/m
– Fire 2 (5 parameter sets) – Fire 2 (10 parameter sets)
6.0...20% obs/m
2.0...20% obs/m
Air inlet pipe
Planning Tool
ü
Communication protocol
Display
Cerberus PRO – C-NET devices
ü
ü
ü
The aspirating smoke detector continually takes air from
the monitored room using a connected pipe system with
defined aspirating holes.
Remote access
with CerberusRemote
Pipe length
Relay outputs
3x2 A / 30 V
4x2 A / 30 V
Terminals
0.2...2.5 mm²
(30 - 12 AWG)
0.2...2.5 mm²
(30 - 12 AWG)
Dimensions (WxHxD)
155x280x114 mm
155x280x114 mm
Operating current
– 150 mA nominal
– 250 mA in alarm
– 150 mA nominal
– 250 mA in alarm
Operating temperature
-20...+60 °C
-20...+60 °C
Relative humidity
5...95% rel.
(no condensation)
5...95%
(no condensation)
Protection category
IP30
IP30
Data sheet
A6V10331032
A6V10331032
Ethernet
Security module
(firewall)
NK8237
Tonality
Frequency pattern
Sweep from – to
1
Continuous
970 Hz
2
Intermittent
950 Hz
3
Sweep-down
1200 Hz – 500 Hz
4
Slow-whoop
Sweep-up, linear
500 Hz – 1200 Hz
5
Pulse tone
500 Hz
6
Intermittent
500 Hz
7
Continuous
500 Hz
8
Alternating
560 Hz
440 Hz
9
Intermittent
420 Hz
10
Slow-whoop
Sweep-up, linear
500 Hz – 1200 Hz
11
Intermittent
970 Hz
Adjustable FDS221 and
FDS229 sound intensity
level (typ. values in
[dBA/1m]*)
Pulse pattern
at 32 V
98
88
81
101
92
82
“Evacuate”
BS 5839 Part 1 1988
96
87
79
100
91
81
“Alert”
BS 5839 Part 1 1988
96
87
79
100
91
80
DIN-Tone
DIN33404 Part 3
97
88
81
101
92
82
NEN2575
(Netherlands)
94
85
75
97
88
75
Swedish Standard
SS 03 17 11, No. 1
“Imminent Danger”
93
84
75
96
87
75
Swedish Standard
SS 03 17 11, No. 6
“Local Warning”
94
85
76
97
88
76
Swedish Standard
SS 03 17 11, No. 4
“All clear”
94
85
75
98
89
76
“French fire sound”
NF S 32-001-1975
94
85
76
98
89
77
Australia “Alert”
AS 2220 -1978
96
89
81
100
93
82
Australia “Action”
AS 2220 -1978
99
89
82
102
92
83
ISO 8201
US Temporal Tone LF
1s
1s
Backbone (C-WEB/LAN)
Ethernet switch
FN2008-A1
Norm
at 12 V
1s
Cerberus Mobile
Ethernet switch
FN2008-A1
Ethernet switch
FN2008-A1
3.5 s
Ethernet switch
FN2008-A1
0.5 s
0.15 s
Manual call
point
FDM221
Alarm
sounder
FDS221
0.1s
C-NET
Sounder base
DBS720
FP120-Z1
Power supply
kit A (70 W)
Metric: 21 mm
ID...25 mm OD
– 30 m (single pipe length) – 60 m (single pipe length)
– 2x25 m (branched pipe – 4
x30 m (branched pipe
length)
length)
Danger
management
system from
Siemens
No.
Security module
(firewall)
NK8237
Up to 800 m²
Metric: 21 mm
ID...25 mm OD
Customer network
The position and size of the aspirating holes are calculated
with the ‚FXS2055 ASD Asyst Tool‘ software.
Fire control panel
FC723
0.15 s
Fire control panel
FC724
Fire control panel
FC722
Cluster (C-WEB/SAFEDLINK)
DC 24 V
Fire terminal
FT724
Alarm indicator
FDCAI221
Heat detector
HI722 (max)
Smoke
detector
OP720
Input module
FDCI222
Floor repeater
display FT2011
Sounder interbase
with supplementary
optical indication
DBS729
Multi-sensor
fire detector
OH720
C-NET
Input/output
module
FDCIO222
Alarm sounder
with supplementary optical
indication
FDS229-R
SWING
radio gateway
FDCW241
SWING
radio neural
fire detector
FDOOT271
Extinguishing
control unit XC10
Fire control panel
FC724
ASA neural
fire detector
OOH740
ASA neural fire
and CO detector
OOHC740
Smoke
detector
OP720
www.siemens.com/cerberus
Manual release
Multi-sensor
fire detector
OH110
Sinorix
extinguishing
solution
0.4 s
0.6 s
Heat detector
HI720
(max + RoR)
Stub line
0.65 s
3.75 s
C-NET
0.25 s
Multi-sensor detector
OOH740-A9-Ex
0.5 s
Flame detector
FDF241-9
SWING
radio manual
call point
FDM273
ASA neural
fire detector
OOH740
0.1s
Fault transmission
Alarm transmission
Sounder
interbase DBS721
FDCC221S
Communication interface
0.6 s
Fire control panel
FC726
Floor repeater
terminal FT2010
Aspirating
smoke detectors
FDA221
FDA241
C-NET
Detection modes:
Ultra sense
Automatic discrimination
Robust
Powerful control panels, clever fire detectors and smart peripheral devices.
This is what our comprehensive Cerberus™ PRO family offers. The brief overview
below demonstrates the most important system components.
FDA241
Pipe system
FDA221
Alarm sounder tones
Cerberus PRO – enjoy protecting
0.5 s 1.5 s
Manual call
point
FDM223
Linear
smoke detector
FDL241-9
Line adapter (Ex)
FDCL221-Ex
*S
ound intensity ±2 dBA
Sound intensity depending on the angle, see 'Operating instruction 008109'
Mimic
display driver
FT2001-A1
Samples for all alarm sounder tones are available on the Cerberus PRO Web site.
www.siemens.com/cerberus
Robust or sensitive? The solution often lies somewhere in between.
Sensitive
Sensitive
Sensitive
Sensitive
Sensitive
PS6
PS9
Robust
PS10
High Sensitive Fast (PS9)
Robust
PS4
Fast Response (PS6)
Robust
PS2
Balanced CO (PS10)
Robust
Sensitive
Balanced (PS4)
Robust
PS7
Robust (PS2)
Robust
PS12
High Compensation (PS7)
Robust
PS5
Sensitive
Suppression CO (PS12)
Robust
PS8
Sensitive
Suppression (PS5)
Robust
Sensitive
High Suppression (PS8)
Application area
Application area
Application area
Application area
Application area
Application area
Application area
Application area
Application area
For operating conditions susceptible to heavy
optical deceptive phenomena. Examples include
dance floors in discotheques (deceptive phenomena: dry ice) or churches during special services
(deceptive phenomena: frankincense).
Difficult environments subject to heavy deceptive phenomena. Application examples include
canteen kitchens or manufacturing areas with
operational-related deceptive aerosols.
Difficult environments subject to heavy deceptive
phenomena. Application examples include manufacturing areas with operational-related aerosols.
Additional separate CO toxic gas detection and
environmental monitoring.
Applications with deposits resulting from excessive
dust or dirt over a long-time period. Here, optical
detectors usually reach their limit quickly, resulting
in a reduced operational lifetime.
Difficult environmental conditions. Examples are
event locations or underground garages with moderate
deceptive phenomena and risks to individuals.
Standard applications. Rooms with moderate deceptive phenomena.
Rooms where an increased CO concentration in
the event of a fire is possible. Moderate deceptive
phenomena.
Rooms in which sensitive and quick detection is
essential such as rooms with high ceilings, warehouses with flammable material (increased risk
of fire) and application areas where the detectors
trigger an extinguishing system.
Rooms in which an especially high sensitivity to
smoldering and open fires is required. Examples
include museums with high ceilings, clean production halls or applications where adequate life
protection can only be ensured by the fastest
possible detection. Due to special thermal algorithms, usage at low temperatures is also possible.
Our world is undergoing changes that force us to think
in new ways: demographic change, urbanization, global
warming and resource shortages. Maximum efficiency
has top priority – and not only where energy is concerned.
In addition, we need to increase comfort for the well-being
of users. Also, our need for safety and security is constantly
growing. For our customers, success is defined by how well
they manage these challenges. Siemens has the answers.
“We are the trusted technology partner for
energy-efficient, safe and secure buildings and
infrastructure.”
Description
In this parameter set, the signal from the smoke
sensor will not be allowed to create a fire alarm
signal until a simultaneous increase in the thermal
signal is also detected. In the event of dry ice,
there is no temperature increase and the detector
will not create an unwanted alarm. With a rise
in temperature of only 8K (open fire), the optical
sensors will be further analyzed and if the signal
corresponds to a fire, an alarm will be triggered.
In addition, the detector will also trigger an alarm
as a rate-of-rise heat detector or if its static
temperature limit is exceeded.
Description
Highly robust behavior, therefore very suitable
for applications with deceptive phenomena such as
steam, heavy cigarette smoke or exhaust gases.
At the same time, the detector reacts with the
ASA parameter set quickly and reliably in case of
a real fire due to the dynamic influencing of the
parameters.
Description
Highly robust behavior, therefore very suitable
for applications with deceptive phenomena such
as steam, cigarette smoke, etc. At the same time,
the detector reacts with the ASA parameter set
quickly and reliably in case of a real fire due to the
dynamic influencing of the parameters. Sensitivity is also influenced by the CO concentration.
Separate CO alarming and control for the detection of unhealthy or dangerous carbon monoxide
buildup. Separate signaling of environmental
thermal thresholds.
Description
This parameter set is identical to the Robust setting
except that the drift compensation is extended.
This parameter set is therefore especially suited for
rooms in which a lot of dust and other deposits
can be expected to build up over a period of time.
The detector maintains the set detector sensitivity
and resistance to deceptive phenomena. The detector reacts quickly and reliably in case of a real fire.
Description
Designed for robust behavior. This ASA parameter
set is particularly suitable for applications with
deceptive phenomena such as cigarette smoke, dust
and exhaust gases. At the same time, the detector
reacts very quickly and reliably in case of a real fire.
Compared to the ‘Suppression (PS5)’ parameter set,
the ‘Robust (PS2)’ parameter set may be used to
improve detection speed on higher ceilings while
still retaining sufficient resistance to false alarms.
Description
For use in normal environments. This parameter set
has a balanced response characteristic; sensitive in
case of a fire but still tolerant of transient deceptive
phenomena. Due to its distinct dynamic, the detector
reacts quickly to open fires as well as smoldering
fires. This ASA parameter set reacts robustly to deceptive phenomena such as cigarette smoke or small
amounts of steam.
Description
Using the three criteria: smoke, heat and CO the
device is more sensitive to fires creating CO than
the parameter set ‘Balanced (PS4)’ without the
CO signal. The device is robust with deceptive
phenomena such as cigarette smoke or a small
amount of steam. This parameter also offers early
alarming in the event of fires generating a large
amount of CO, e.g. mattress fires.
Additional information
Description
This parameter set reacts in a fast and sensitive
manner. It is thus especially suited for rooms
without deceptive phenomena, where the priority
is on detecting fires as early as possible.
Expert advice
Description
This parameter set allows for the fastest possible
detection for both open and smoldering fires. It is
therefore intended for use in clean environments
with no deceptive phenomena.
The high thermal influence from open fires transports the dark smoke particles that are typical
for this kind of fire quickly to the ceiling. Due to
the backward scattering and the “Fast Response”
setting, the detector is sensitive. This makes
the detector a perfect replacement in situations
where ionization detectors would normally have
been considered optimal.
This parameter set is often used when the system
is set in unmanned mode (e.g. at night).
Expert advice
“High Suppression” has clear advantages over
traditional concepts where smoke detection is
turned off completely and replaced by thermal
detection during events where dry ice is used.
This parameter set allows much faster detection
than switching to purely thermal detection. This
enhances safety at critical times where visibility
is reduced and large numbers of people are in
attendance. Further options include the ability
to switch between parameter sets so that a more
sensitive detection mode can be used when no
dry ice is likely. The detector complies with the
norm EN 54-5 and in some jurisdictions heat
detector spacing may be applicable.
Complies with the norm EN 54-5
Complies with the norm EN 54-5, EN 54-7
Complies with the norm EN 54-5, EN 54-7
Complies with the norm EN 54-5, EN 54-7
Complies with the norm EN 54-5, EN 54-7
Complies with the norm EN 54-5, EN 54-7
Complies with the norm EN 54-5, EN 54-7
Complies with the norm EN 54-5, EN 54-7
Complies with the norm EN 54-5, EN 54-7
Application examples
Application examples
Application examples
Application examples
Application examples
Application examples
Multi-purpose halls, theater stages, churches,
dance floors in discotheques
Canteen kitchens, production areas with
operational-related deceptive phenomena
Production areas with operational-related
deceptive phenomena
Paper mills, carpenters workshops, textile production,
recycling plants
Event locations, conference rooms, smoking rooms,
gastronomy, industry, production, underground
garages
Offices, open-plan offices, hallways, hotel rooms,
out of hours use in harsh environment areas
Application examples
Application examples
Application examples
Same as for ‘Balanced (PS4)’, but with increased
sensitivity to smoldering fires creating CO gas
High-ceilinged rooms, storage rooms/warehouses
with flammable material, IT rooms and control of
extinguishing systems
Hospital rooms, museums, operating rooms,
cold storage, high-ceilinged rooms, when highly
sensitive detection is of great importance
Specifications are subject to change without notice.
© Siemens Switzerland Ltd, 2015 • Order no. 0-92314-en • 01507
The information in this document contains general descriptions of technical options available, which do not always
have to be present in individual cases. The required features should therefore be specified in each individual case at
the time of closing the contract. The document contains a general product overview. Availability can vary by country.
For detailed product information, please contact the company office or authorized partners.
Siemens Switzerland Ltd
Building Technologies Division
International Headquarters
Gubelstrasse 22
6301 Zug
Switzerland
Tel +41 41 724 24 24
Cerberus PRO Planning Tool
C-NET devices
Cerberus PRO
fire detectors
Sounder base DBS720
Sound level: 88 dBA/1 m
Detector base DB721
Detector base DB722
Flame detector base FDFB291
Art. no.: S54319-F11-A1
Art. no.: S54319-F19-A1
Art. no.: A5Q00003310
Art. no.: S54319-F5-A1
Cluster
(C-WEB/SAFEDLINK)
Shared properties FT2010 and FT2011:
–B
acklit display with plain text
(6 lines of 40 characters each)
–P
ower supply and communication
(individual addressed) via C-NET,
additional DC 24 V feed possible
– 207x282x79 mm (HxWxD)
–M
ax. 8 FT2010/FT2011 per FC721/FC722
–M
ax. 16 FT2010/FT2011 per FC724
– Max. 50 FT2010/FT2011 per FC726
Fire control panel
FC724
Conventional
Art. no.: A5Q00003941
or
Fire control panel
FC723
Linear smoke detector base
FDLB291
Addressable
Single action DMA1104D
Protection category: IP54
Double action DMA1103D
Protection category: IP54
Art. no.: A5Q00005925
Art. no.: A5Q00004470
Manual call point
DM1103 (Ex)
Infrared flame detector
unit collective “Ex” DF1101-Ex
Art. no.: BPZ:5222870001
Art. no.: BPZ:5162220001
or
Fire control panel
FC722
Flame detector
FDF241-9
– For inside and outside
applications
– Three infrared sensors
Linear smoke detector
FDL241-9
Art. no.: S54329-F8-A1
Art. no.: A5Q00003006
Art. no.: A5Q00002298
Safety barrier SB3
Fire control panel FC722
ASA neural fire
detector OOH740
Two optical sensors,
two heat sensors,
seven parameter sets
Art. no.:
A5Q00014104
Art. no.: S54320-F7-A3
ASA neural fire and
CO detector OOHC740
Two optical sensors,
two heat sensors, one
carbon monoxide sensor, nine parameter sets
Multi-sensor fire
detector OH720
Combined optical and
thermal sensors, two
parameter sets
Smoke detector
OP720
Two parameter sets
Heat detector
HI722 (max)
One parameter set (static)
Art. no.: S54310-F1-A1
Art. no.: S54310-F3-A1
Heat detector HI720
(max + RoR)
Two parameter sets
(rate of rise and static)
up
to
1
00
m
Base for infrared flame
detectors DF119x
DFB1190
Input/output module
“transponder”
FDCIO223
Air sampling
smoke detection kit
FDBZ290
Art. no.:
S24218-B102-A1
Art. no.:
S54319-S32-A1
Detector base DB721
Art. no.: S54319-F11-A1
Art. no.: S54320-F8-A3
Base attachment wet
BA721
Detector base seal RS720
Art. no.: S54319-F8-A1
Short-distance
filter 7 – 10 m
DLF1191-AA
Art. no.: BPZ:3950450001
Art. no.: BPZ:4933030001
Art. no.: S54319-F29-A1
Floor repeater display FT2011-A1
Long-distance reflector
DLR1191 (Prism)
For distances between
20 and 100 meters.
ASA neural fire
detector OOH740
Art. no.: S54320-F7-A3
Art. no.: BPZ:4787710001
Designation plate FDBZ291
Art. no.: A5Q00017706
Art. no.:
S54370-F6-A1
Art. no.: S54319-F9-A1
Alarm indicator FDAI92
Art. no.: S54370-F3-A1
Mimic display driver FT2001-A1
LED flat cable 24 LEDs F50F410
Additional frame AI330
Art. no.: A5Q00014417
Art. no.: BPZ:5291410001
Art. no.: BPZ:3169430001
Alarm indicator
FDAI91
Alarm indicator
FDAI93
Art. no.:
S54370-F9-A1
Art. no.:
S54370-F5-A1
Base attachment BA720
Protection cage
DBZ1194
Ball and socket joint MWV1
Art. no.: BPZ:4677110001
Art. no.: BPZ:3674840001
Short-distance
filter 5 – 8 m
DLF1191-AB
Art. no.: BPZ:4933160001
Art. no.: S54319-F20-A1
Line adapter (Ex)
FDCL221-Ex
Art. no.:
S54329-F4-A1
Output module (230 V)
FDA221
FCA1209-Z1
Art. no.: S54333-F15-A1
The output module is
FDA241
directly connected with the
monitored output line and
Art. no.: S54333-F17-A1
provides one potential-free
contact. It is an output
Accessories:
module for the control of
Communication interface ventilation‚ air conditioning‚
elevators‚ etc.
FDCC221S
Adapter FDUD491
Detector tester for heat detectors RE7T
Line tester FDUL221
Art. no.: S54319-F18-A1
Art. no.: S54370-S3-A1
Art. no.: A5Q00004397
Detector exchanger DX791
Detector tester for linear smoke detectors RE10
Telescope rod FDMU291
Art. no.: S54319-F6-A1
Art. no.: BPZ:3685190001
Art. no.: A5Q00004996
Multi-line separator module
FDCL221-M
Up to 9 stubs
The multi-line separator has
altogether nine integrated line
separators with one individual
addressing each and one LED
indicator per separator. It can
be connected to two separate
C-NET loops.
Input module FDCI221
– 1 monitored input
Art. no.: S54312-F1-A1
Art. no.: A5Q00002369
Extinguishing panel standard
XC1001-A
The XC10 combined extinguishing
and detection panel can be fully
integrated into all Cerberus PRO
systems via the FDCIO222 as an
independent unit. All relevant
incidents are forwarded to the
connected control panels. The
extinguishing control unit XC10
and the connected extinguishing
valves must have a separate power
supply. For XC10 variants please
see separate XC10 Planning Tool.
Test lamp for flame detectors ‘Ex’ StabexHF
Scorpion controller SCORP 8000
Art. no.: BPZ:3680300001
Art. no.: BPZ:4620910001
Art. no.: S54333-C91-A1
Testifire 1001-045 ST test kit RE8ST
Test lamp for flame detectors LE3
Scorpion ASD head unit SCORP 2001
Art. no.: S54370-S23-A1
Art. no.: BPZ:3669510001
Art. no.: S54333-S90-A1
Relay outputs:
– 4 potential-free working/rest contacts
Fire
damper
4 isolated
control outputs
Rain hood DFZ1190
Detector heating DLH1191A
Art. no.: BPZ:5302660001
Art. no.: BPZ:4787970001
Fire
control
Contact loading:
– AC 250 V/4 A
– DC 30 V/4 A
Art. no.: A5Q00002369
Input module FDCI222
– 4 monitored inputs
4 isolated
control inputs
Art. no.: A5Q00001984
Short-distance reflector
DLR1193
For distances between
10 and 30 meters.
FP120-Z1
Power supply kit A (70 W)
The standalone power supply
converts the mains voltage to
system voltage and charges
the batteries.
Art. no.: BPZ:4787840001
Input/output module
“transponder” FDCIO223
The module has two inputs/outputs
and is used for
– connecting conventional detectors
– connecting detectors by means
of safety barriers in explosionprotected areas
– controlling alarm devices
(flashing lights, sirens)
– for monitored control
(e.g. fire dampers)
Housing FDCH221
IP65
Art. no.: S54312-F3-A1
Conventional line
Conventional
detectors
Testifire 2001-045 STCO test kit RE8STCO
2 inputs or
2 outputs
– requires DC 24 V power supply unit
Art. no.: S54370-S24-A1
Art. no.: S24218-B102-A1
Alarm equipment
(audible/visible)
Sounder base DBS720
Sound level: 88 dBA/1 m
Art. no.: S54319-F5-A1
Detector base DB721
Art. no.: S54319-F11-A1
or
Detector base DB722
Sounder base FDB221
Art. no.: S54319-F19-A1
Art. no.: A5Q00001664
or
Manual call points and accessories
Sounder base flat FDB222
Art. no.: S54319-F1-A1
Manual call point
FDM221
Standard, available in
different colors.
Sounder interbase
(C-NET) DBS721
Sound level: 87 dBA/1 m
Art. no.: S54372-F13-A1
(Picture shows product
with blanking plate BPZ20)
Art. no.: S54390-C1-A1
Sounder interbase
with supplementary
optical indication
(C-NET) DBS729
Sound level: 87 dBA/1 m
Alarm sounder
FDS221-W
Sound level: 99 dBA/1 m
Alarm sounder
FDS221-R
Sound level: 99 dBA/1 m
Art. no.: A5Q00006711
Art. no.: A5Q00004117
Alarm sounder with
supplementary optical
indication FDS229-R
Sound level: 99 dBA/1 m
Alarm sounder with
supplementary optical
indication FDS229-A
Sound level: 99 dBA/1 m
Art. no.: A5Q00023093
Art. no.: A5Q00023092
Manual call point
FDM225
Resettable, available in
red and can be used for
flush mounting.
Alarm indicator
(addressable)
FDCAI221
Manual call point with
resettable plastic
element FDM225-RP
Art. no.: S54370-F10-A1
Art. no.: A5Q00012020
Art. no.: S54372-F14-A1
Manual call point with
resettable plastic
element incl. back box
FDM226-RP
Manual call point
FDM231-RP
Standard, available in red.
Manual call point
FDM224
IP44 or IP64, with direct
operation available in
different colors.
Manual call point
FDM223
IP44 or IP64, with indirect
alarm actuation, available in different colors.
Manual call point
FDM224H
Heavy Duty, IP44 or IP64,
with direct alarm
actuation.
Manual call point
FDM223H
Heavy Duty, IP44 or IP64,
with indirect alarm
actuation.
Art. no.: A5Q00002451
Manual call point
complete
Art. no.: S54311-F11-A1
Art. no.: S54311-F8-A1
Manual call point with
glass plate
FDM225-RG
Manual call point with
glass plate incl. back box
FDM226-RG
Electronic switching
unit incl. key FDMK231
FDME231
Art. no.: A5Q00013434
Art. no.: A5Q00013435
Art. no.: S54311-B14-A1
Electronic switching
unit FDME224
Electronic switching
unit FDME223
Electronic switching
unit FDME224
Electronic switching
unit FDME223
Art. no.: A5Q00009392
Art. no.: A5Q00003087
Art. no.: A5Q00009392
Art. no.: A5Q00003087
Housing:
Housing:
C-NET
Housing red
with key FDMH291-R
Housing red
FDMH292-R
Housing red
FDMH292-R
Art. no.: A5Q00005525
Art. no.: A5Q00005525
The C-NET is a modern, multi-purpose bus system.
It allows rapid, fail-safe communication between
the Cerberus PRO bus elements and the fire
control panel.
Housing yellow
Housing red FDMH293-R
Housing yellow FDMH293-Y
Housing green FDMH293-G
Housing blue FDMH293-B
Housing orange FDMH293-O
Housing red FDMH297-R Art. no.: A5Q00002217
with key FDMH291-Y
Art. no.: A5Q00004023
Art. no.: A5Q00004908
Art. no.: A5Q00004911
Art. no.: A5Q00004909
Art. no.: S54311-F2-A1
Art. no.: S54311-B7-A1
Backbone (C-WEB/LAN) Network for connecting clusters
Cluster (C-WEB/SAFEDLINK)Network for connecting panels
C-NET
Network for connecting Cerberus PRO addressable devices
C-NET-Ex
Network for connecting Cerberus PRO addressable Ex devices
Sealing element FDBZ295
(only together with base FDB221)
BP720 Blanking plate
(only for DBS721 and DBS729)
Housing green
with key FDMH291-G
Art. no.: S54319-F10-A1
Art. no.: S54372-B12-A1
Art. no.: A5Q00004981
Designation plate FDBZ291
Base attachment wet FDB295
Housing blue
with key FDMH291-B
Art. no.: A5Q00002621
Art. no.: S54319-F2-A1
Art. no.: A5Q00004980
Accessories:
Accessories:
Accessories:
Accessories (for FDM224 and FDM223):
Back box FDMH295-R
Protective cover
FDMC295
Back box red
FDMH231-S-R
Protection seal DMZ1197-AD Art. no.: BPZ:5470680001 Protection seal
Protective cover DMZ1197-AC Art. no.: BPZ:5223550001 DMZ1197-AD
Art. no.: A5Q00013440
Art. no.: S54311-B12-A1
Locking plug M20 (1 hole)
Art. no.: A5Q00013437
Back box with holes and
grommet FDMH295-S
Screwed cable gland
M20 x 1.5
Designation plate DBZ1193A
Accessories:
Art. no.: A5Q00013438
Art. no.: A5Q00001603
Art. no.: BPZ:4864330001
Protective cover
FDMC291
Protective cover
FDMC295
Art. no.: A5Q00004478
Art. no.: A5Q00001644
Art. no.: A5Q00013440
Art. no.: A5Q00004479
Detector locking device FDBZ293
Art. no.: S54319-F9-A1
Art. no.: A5Q00005035
Base FDB271
Art. no.:
S54319-F12-A1
Neural radio
fire detector
FDOOT271
Radio manual call point
FDM273
Art. no.:
S54313-F1-A1
Art. no.: S54323-B109-A1
Base attachment FDB291
Detector locking device LP720
SWING devices
are communicating
via multi-band
(433/868 MHz)
multi-hop mesh
technology
Housing red‚ with glass
and key FDMH273-R
Art. no.: A5Q00004979
Legend for the designation of fire detectors:
Radio gateway FDCW241
The radio gateway FDCW241 enables to bidirectionally
connect up to 30 battery-powered SWING radio devices.
Art. no.: S54370-F11-A1
Manual call point
complete
Housings with glass and key (FDM224 and FDM223):
Sounder accessories
Manual call point
FDM243H
Heavy Duty, IP66, with
direct alarm actuation.
SWING
radio fire detection
Art. no.: A5Q00013436
Electronic switching
unit FDME221
Shared characteristics:
– 11 different tones, incl. “Evacuate”
as specified in DIN 33404-3
– Different volume and sound programmable for prealarm and main alarm
– Loop-powered
Manual call point
FDM226
Resettable and IP66,
available in red.
Housings:
Characteristics:
– Use of all cable types (shielded or unshielded)
– Integration of star-shaped cable networks without
modifications to cable network
– Acoustic and visual signaling on the loop
– Up to 40 T-taps
– Up to 252 bus elements on one loop
– Cable lengths up to 3.3 km with up to 252 bus
elements
– 2-wire loop
– Power supply to all bus elements via the C-NET
(except transponder FDCIO223, LaserFOCUS,
extinguishing control unit XC10, ASD FDA221,
FDA241)
– Integrated isolator in every loop participant
Input/output module FDCIO222
– 4 monitored inputs
4 isolated
control inputs
Mid-distance reflector
DLR1192
For distances between
30 and 65 meters.
Art. no.: S54400-S122-A1
Art. no.: S54312-F6-A1
Input/output module FDCIO222
Detector tester for smoke detectors RE6
Relay outputs:
– 1 output
– Relay output DC 30 V/2 A rated
– Can be configured as monitored, but
a separate DC 24 V power supply is
required
Art. no.: S54312-F2-A1
Test equipment
Art. no.: A5Q00004011
Input/output module FDCIO221
– 1 monitored input
Fire
control
Art. no.: BPZ:4788490001
Line separator FDCL221
Only required to separate
2 adjacent stubs
Art. no.: S54329-F5-A1
Art. no.:
S54319-F1-A1
Power supply kit
FP120-Z1
Art. no.: A5Q00004439
Detector locking device LP720
Manual call point
FDM223-Ex
Detector base flat,
addressable FDB222
Art. no.: S54400-B124-A1
Detector heating
FDBH291
Art. no.: A5Q00002621
Art. no.:
A5Q00001664
Aspirating
smoke detectors
Art. no.: S54310-F2-A1
Mounting bracket MV1
Art. no.:
S54370-F4-A1
Alarm indicator
FDAI93-Ex
Art. no.: BPZ:5165360001
Art. no.: S54310-F4-A1
Detector base accessories
Detector base
addressable FDB221
Multi-sensor detector OOH740-A9-Ex
Art. no.: BPZ:4837000001
Floor repeater
terminal
FT2010-A1
Alarm indicator
FDAI92-Ex
Art. no.: S54329-F8-A1
Multi-sensor detector
OOH740-A9-Ex
Fire control panel
FC726
Ex zone
C-NET-Ex
Cerberus PRO
control panels
Back nut M20
Art. no.: A5Q00006735
Accessories:
Accessories:
Switching unit with
indirect alarm actuation
FDME273
Protection seal
DMZ1197-AD
Art. no.: S54323-B108-A1
Art. no.:
BPZ:5470680001
Art. no.:
BPZ:5470680001
Protective cover
DMZ1197-AC
Protective cover
DMZ1197-AC
Protective cover
DMZ1197-AC
Art. no.: 5223550001
Art. no.:
BPZ:5223550001
Art. no.:
BPZ:5223550001
Screwed cable gland
M20 x 1.5
Screwed cable gland
M20 x 1.5
Art. no.: A5Q00004478
Art. no.: A5Q00004478
Battery
BAT3.6-10
Art. no.:
S54370-Z11-A1