UX SERIES - Decentralized Parallel Modular UPS series

Transcription

UX SERIES - Decentralized Parallel Modular UPS series
The UX modular online UPS series, featured with DSP control, decentralized parallel structure,
Modular N+X Parallel Redundancy, touch-screen LCD display, Hot swappable, programmable battery
voltage, intelligent charge modes with settable charge current, Megatec/Modbus protocol, is an ideal
solution to your PC, workstation, server, bank, industrial equipment, Internet data center, telecom, IT
equipments or other mission-critical application, which is demanding for a thorough protection.
Features
http://www.upsonic.net
Decentralized Parallel Structure with Hot-swappable feature
Modular N+X Parallel Redundancy
DSP-controlled Technology
Unity Input Power Factor with Low Input Current Distortion
& High Efficiency
Fit into standard 19" Rack Frame
Touch-screen LCD display for user's friendly operation
High Power Density up to 200KVA per rack for space saving
InvestasYouGrow
Compact in size, only 3U height
Superior MTBF and MTTR
Emergency Power Off device can be operated on site
or remotely
Common Battery
Programmable Battery Voltage
Intelligent Charge Modes with smart charge current
adjustment
Megatec/Mod Bus protocol supported
Powerful charger built in Modular and UPS frame
Versatile communication interfaces provided for
different applications
Matching battery modular also available
UX SERIES - Decentralized
Parallel Modular UPS series
UMX-50K / UMX-100K
UTX-60K / UTX-100K / UTX-200K
DSP-controlled Technology
With advanced DSP control, the UX Series decentralized parallel modular series offers maximum power density in the UPS filed.
UX Frame (200KVA)
UX Decentralized
Parallel Modular UPS Series
UX Frame (60KVA)
UMX-50K / UMX-100K
UTX-60K / UTX-100K / UTX-200K
Compact in size, only 3U height
It is very compact and high-efficient
comparing with current offers in the
markets.
Fit into standard 19" Rack Frame
Using standard 19" Rack Frame, the
UX Series 3U module with special rear
configuraron may be easily fitted in.
Modular N+X Parallel Redundancy
Thanks for its N+X parallel redundancy technology used, the UX series may freely set the modules
connected to N+X according to the protection level required by the equipment connected.
Superior MTBF and MTTR
Superior MTBF (Meantime before failure) and
MTTR (Meantime to Repair) design minimizes
service and maintenance costs and no skilled
personnel on site is required, and only simply
exchanges the module for an easy fault recovery.
Decentralized Parallel Structure with
Hot-swappable feature
Decentralized parallel structure reduces
the Single points of failure as well as
minimizes service and maintenance
costs.
Unity Input Power Factor with Low Input Current Distortion & High Effíciency
Thanks for DSP Control technology ¡mplemented, the UPS may reach Unity Power factor,
low input currentTHD as well as high output efficiency.
Emergency Power Off device can be operated on site or remotely
Versatile communkation interfaces provided for different applications
Besides RS232 interface for the module itself, the UPS can be monitored and controlled vía RS485, dry
contact card or Ethernet (SNMP) card installed in the two intelligent slots.
InvestasYouGrow
Thanks for the ability of true modular UPS systems to
easily scale power. It is possible to add power as the data
center power requirements grow, which eliminates the
high initial investment cost of purchasing power capacity
that is not required at the first stage of investment.
High Power Density up to 200KVA
per rack for space saving
With smallest
footprint, the
UX series
reaches highest
power density up to
200KVA per rack
for space saving.
Intelligent Charge Modes with smart charge current adjustment
The UPS provides 3-mode charge methods, one is boost charge, another is equalized charge and the other is
floating charge according to the status of the battery, enhance extends the life of the battery. Charge current
can be adjusted according to battery capacity installed.
Common Battery
Common battery design enables several modules ¡n parallel to use one battery
bank to save unnecessary extra wiring and investment to the batteries.
Programmable Battery Voltage
The battery voltage can be set from 192Vdc to
240Vdc for UMX series and from 384Vdc to
480Vdc for UTX series according to the
demand of battery runtime.
Powerful charger built in Modular and UPS frame
Each module has a built-in powerful charger at 6A to
escálate the total charge capacity up to máximum 60A.
Megatec/Mod Bus protocol supported
The complete UPS system can"talkto"computer system via its Megatec or Mod Bus protocol
Touch-screen LCD display for
user's friendly operation
Optional control module with 5"touch-screen LCD
display provides multilingual messages with fruitful
UPS information on-screen or remotely.
Matching battery modular
alsoavailable
UPX Decentralized Parallel Modular UPS
UMX-50K
Model
Capacity (VA/W)
UPS Frame
4~100KVA / 3.2 ~80KW
4KVA / 3.2KW - 6KVA / 4.8KW - 10KVA / 8KW
UMX-Module
Phase
3Phase/4Wires + Ground or 1Phase 2 Wires + Ground
Rated Voltage
380/400Vac or 220/230VAC
Voltage Range
208-478VAC or 120VAC-276VAC
Frequency Range
Input
UMX-100K
4~50KVA / 3.2~40KW
40Hz-70Hz
Power Factor
≥0.99
Current THDi
≤5% (100% nonlinear load)
Max. voltage: +15% (optinal +5%, +10%, +25%)
Min. voltage: -45% (optional -20%, -30%)
Bypass Voltage Range
Frequency protection range: ±10%
Generator Input
Support
Phase
Single phase & Ground
220/230VAC
Rated Voltage
0.8
Power Factor
±2%
Voltage Regulation
Output
Frequency
Utility Frame
synchronized ton Mains, Inverter free run at 50/60±0.2Hz if out of set window
(±1%, ±2%, ±4%, ±5%, ±10% settable)
Battery Mode
(50/60Hz±0.2) Hz
3:1
Crest Factor
≤2% with linear load
≤5% with non linear load
THD
Pure Sinewave
Waveform
Efficiency
≥90% at normal mode
Voltage
192/216/240Vdc, battery quantity (optional)
Battery
30A Max. (charge current can be set
according to battery capacity installed)
UPS Frame
Charging Current
UMX Module
6A Max. (charge current can be set according to battery capacity installed)
Transfer Time
Utility to Battery: 0ms; Utility to bypass: 0ms
Overload
AC Mode
Load ≤110%: last 60min, ≤125%: last 1S, ≤150%: last 200ms,
≥150% shut down UPS immediately.
Bat. Mode
Load ≤110%: last 30S, ≤125%: last 1S, ≤150%: last 200ms,
≥150% shut down UPS immediately.
Input Breaker (4KVA:32A / 6KVA:40A / 10KVA:60A)
Bypass Mode
Protection
Short Circuit
Hold Whole System
Overheat
Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately
Battery Low
Alarm and Switch off
Self-diagnostics
Upon Power On and Software Control
Shut down UPS immediately
EPO (optional)
Battery
Advanced Battery Management
Noise Suppression
Alarms
Complies with EN62040-2
Audible & Visual
Line Failure, Battery Low, Overload, System Fault
Line Mode, Backup -mode, Eco Mode, Bypass Mode, Battery Low, Battery Bad,
Overload & UPS Fault
Status LED & LCD
Display
Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load Percentage,
Battery Voltage & Inner Temperature
Reading On the LCD
Communication Interface
RS232, RS485, Intelligent slot x 2, Dry Contact
UPS Frame
UPN Module
RS232
Operating Temperature
0°C~40°C
Storage Temperature
Environment
60A Max. (charge current can be set
according to battery capacity installed)
-25°C~+55°C
Humidity
0~95% non condensing
Altitude
<1500m
Noise
<50dB (at 1 meter)
Safety Conformance
CE - EN/IEC 62040-2, EN/IEC 62040-1-1
UMX Module
Model
Description
Dimension (WxHxD)
Net Weight (Kg)
UMX-M04
4KVA 3/1 Module
443x131x580mm 3U
21.0
UMX-M06
6KVA 3/1 Module
443x131x580mm 3U
23.0
UMX-M10
10KVA 3/1 Module
443x131x580mm 3U
25.0
UMX-B07
for 18pcs 7AH bat.
443x131x580mm 3U
52.0
UMX-B09
for 18pcs 9AH bat.
443x131x580mm 3U
60.0
Dimension (WxHxD) mm
Net Weight
*Battery Module fo UPNX Series
UMX UPS Frame
Model
Description
Application
UMX-20K
20KVA UPS Frame
UMX-30K
30KVA UPS Frame
for max. 5 x 6KVA Modules
UMX-50K
50KVA UPS Frame
for max. 5 x 10KVA Modules
UMX-100K
40/60/100KVA UPS Frame
for max. 10 x 4/6/10KVA Modules
for max. 5 x 4KVA Modules
600x1400x840
138kgs
150kgs
600x2000x840
213kgs
UPX Decentralized Parallel Modular UPS
UTX-60K
Model
Capacity
(VA/W)
UPS Frame
UTX-100K
10~60KVA/9~54KW
UTX-Module
10KVA/9KW, 15KVA/13.5KW, 20KVA/18KW
Phase
Input
3 Phase 4 Wires and Ground
Rated Voltage
380 / 400 /415 Vac
Voltage Range
208~478Vac
Frequency Range
40Hz-70Hz
Power Factor
≥0.99
Current THDi
≤3% (100% nonlinear load)
Max. voltage: +15% (optional +5%, +10%, +25%)
Min. voltage: -45% (optional -20%, -30%)
Frequency protection range: ±10%
Bypass Voltage Range
Generator Input
Support
3 Phase 4 Wires and Ground
Phase
380/400/415Vac
Rated Voltage
0.9
Power Factor
±2%
Voltage Regulation
Output
Frequency
Utility Frame
±1%, ±2%, ±4%, ±5%, ±10% of the rated frequency (optional)
Battery Mode
50/60±0.2%Hz
3:1
Crest Factor
≤2% with linear load
≤5% with non linear load
THD
Pure Sinewave
Waveform
Efficiency
≥92% at normal mode
384V / 408V / 432V / 456V / 480V DC; battery quantity (optional)
Voltage
Battery
Charging
Current
18A Max. (charge current can be
set according to battery capacity
installed)
UPS Frame
30A Max. (charge current can be
set according to battery capacity
installed)
Utility to Battery: 0ms; Utility to bypass: 0ms
Overload
AC Mode
Load≤ 110%: last 60min, ≤125%: last 10min, ≤150%: last 1min, ≥150%: shut down UPS Immediately
Bat. Mode
Load≤ 110%: last 10min, ≤125%: last 1min, ≤150%: last 1sec, ≥150%: shut down UPS Immediately
Bypass Mode
Breaker (10KVA: 20A / 15KVA: 32A / 20KVA:40A)
Hold Whole System
Short Circuit
Overheat
Line Mode: Switch to Bypass / Backup Mode: Shut down UPS immediately
Alarm and Switch off
Battery Low
Self-diagnostics
Upon Power On and Software Control
EPO (optional)
Shut down UPS immediately
Battery
Advanced Battery Management
Complies with EN62040-2
Noise Suppression
Alarms
60A Max. (charge current can be
set according to battery capacity
installed)
6A Max. (charge current can be set according to battery capcity installed)
UTX Module
Transfer Time
Protection
UTX-200K
10~200KVA/9~180KW
10~100KVA/9~90KW
Line Failure, Battery Low, Overload, System Fault
Audible & Visual
Line Mode, Eco Mode, Bypass Mode, Battery Low, Battery Bad, Overload & UPS Fault
Status LED & LCD
Input Voltage, Input Frequency, Output Voltage, Output Frequency,
Load Percentage, Battery Voltage & Inner Temperature
Reading On the LCD
Communication UPS Frame
Interface
RS232, RS485, Inteligent slot x2, Dry Contact
0°C~40°C
Operating Temperature
Storage Temperature
Environment
Humidity
0~95% non condensing
Altitude
< 1500m
<60dB (at 1 meter)
Noise
Safety Conformance
CE, EN/IEC 62040-2, EN/IEC 62040-1-1
UTX Module
Model
Dimension (WxHxD)
Description
Net Weight (Kg)
UTX-M10
10KVA 3/3 Module
443x131x580mm 3U
26.0
UTX-M15
15KVA 3/3 Module
443x131x580mm 3U
30.0
UTX-M20
20KVA 3/3 Module
443x131x580mm 3U
31.0
UPNX UPS Frame
Model
UTX-60K
UTX-100K
UTX-200K
Dimension (WxHxD) mm
Net Weight
600x1400x840
145kgs
for max. 5 x 10/15/20KVA
Modules
600x1400x840
170kgs
for max. 10 x 10/15/20KVA
Modules
600x2000x840
230kgs
Description
30/45/60KVA UPS
Frame
Application
for max. (3+1) x 10/15/20KVA
Modules
50/75/100KVA UPS
Frame
100/150/200KVA UPS
Frame