legend symbol description

Transcription

legend symbol description
GENERAL NOTES:
1. GENERAL SCOPE OF WORK
20. OPERATION AND MAINTENANCE MANUALS
1.1.
FURNISH ALL LABOUR, MATERIALS, EQUIPMENT, TOOLS AND SUPPORTS AS WELL AS SUPERVISION TO
20.1. SUBMIT 5 COPIES OF O&M MANUALS TO ENGINEER FOR REVIEW. ALSO INCLUDE 1 COPY IN PDF FORMAT
PROVIDE A COMPLETE INSTALLATION, TESTED AND IN WORKING ORDER, AS SHOWN ON THE DRAWINGS.
CONTRACTOR RED LINES AND O&M MANUAL. MANUALS SHALL INCLUDE SHOP DRAWINGS OF ALL NEW
1.2.
THE CONTRACTOR SHALL PERFORM THE WORK STIPULATED IN THE CONTRACT AND ANY OR ALL CONTRACT
EQUIPMENT, TEST AND BALANCING REPORTS, COMMISSIONING REPORTS, WARRANTIES, AND OPERATION,
CHANGES AND CHANGE DIRECTIVES, AND SHALL FURNISH, UNLESS OTHERWISE PROVIDED IN THE
MAINTENANCE PROCEDURES AND AS BUILT DRAWINGS.
CONTRACT, EVERYTHING NECESSARY FOR THE PROPER PERFORMANCE AND COMPLETION OF THE WORK.
1.3.
ALL WORK SHALL BE FULLY TESTED, COMMISSIONED AND IN GOOD WORKING ORDER AT TIME OF
21. TESTING, ADJUSTING AND BALANCING (T.A.B.)
HAND-OVER TO OWNER.
21.1. INCLUDE ALL TESTING, ADJUSTING AND BALANCING FOR AIR SYSTEMS INCLUDING, BUT NOT LIMITED TO,
1.4.
MAKE GOOD ANY DAMAGES TO EXISTING EQUIPMENT AND/OR SYSTEM(S). COORDINATE WORK AND
THE FOLLOWING:
WORKING HOURS WITH THE OWNER AND OTHER TRADES TO MINIMIZE DISRUPTION.
21.1.1.
ALL NEW HVAC EQUIPMENT
2. CODES, STANDARDS AND CERTIFICATIONS
21.1.2. ROOFTOP UNITS (RTU)
2.1.
ALL WORK SHALL CONFORM TO THE MOST RECENT ISSUES OF:
21.1.3.
MAKE-UP AIR UNIT, CO, NxOx SYSTEM, EXHAUST FANS.
2.1.1.
THE ONTARIO BUILDING CODE
21.1.4.
REPORT TO INCLUDE FLOWS, PRESSURES, VELOCITIES AND OTHER PERTINENT PERFORMANCE
2.1.2.
THE ONTARIO ELECTRICAL SAFETY CODE
DATA FOR AIR AND WATER. REPORT SHALL ALSO INCLUDE POWER, AMPS, VOLTAGES,
2.1.3.
THE MINISTRY OF THE ENVIRONMENT
PERFORMANCE CURVES, SETTINGS OF ALL SETPOINTS AND SAFETIES, AND ALL OTHER
2.1.4.
THE NATIONAL ELECTRICAL CODE
INFORMATION THAT MAY BE REQUESTED BY THE OWM START-UP FORMS, THE ENGINEER OR
2.1.5.
BYLAWS AND REGULATIONS ISSUED BY THE BUILDING AUTHORITY HAVING JURISDICTION
THE COMMISSIONING AGENT.
2.1.6.
AHRI
21.2 INCLUDE REPORT IN THE OPERATION AND MAINTENANCE MANUALS
2.1.7.
ASHRAE
21.3.
2.1.8.
ASME
SUBMISSION OF REPORT.
2.1.9.
SMACNA
21.4 BALANCING SHALL BE PERFORMED BY AN AABC OR NEBB CERTIFIED BALANCER
2.1.10. NFPA
22. REMOVE ALL ABANDONED PIPES, HANGERS, INSERTS, CONDUITS, DUCTS AND SERVICES.
2.1.11.
TSSA
FIRESTOP AND SEAL ALL AFFECTED AREAS.
2.1.12. CSA
2.1.13. CGA
23. SEAL AND FIRESTOP ALL WALL, FLOOR AND ROOF PENETRATIONS THROUGH FIRE RATED ASSEMBLIES.
REFER TO ARCHITECTURAL DRAWINGS FOR FIRE RATED ASSEMBLIES.
3. SPECIFICATIONS
3.1.
COMPLY WITH THE GENERAL SECTIONS AND APPLICABLE SECTIONS OF THE GENERAL CONTRACT
24. CONTRACTOR MUST ASSURE THAT ALL PIPING CROSSING PASSAGEWAY/GARAGE DOORS/ETC.. SHALL
SPECIFICATIONS.
BE INSTALLED ABOVE AS NOT TO REDUCE OR PREVENT PENETRATION UNLESS THE PIPING IS LOCATED
4. WARRANTY
AGAINST THE CEILING OF SUCH SPACE AND PERMITTED BY THE AUTHORITY HAVING JURISDICTION.
4.1.
WARRANT ALL LABOUR AND MATERIALS INCLUDED IN THIS CONTRACT FOR A PERIOD OF ONE YEAR FROM
DATE OF FINAL ACCEPTANCE. ASSUME FULL RESPONSIBILITY FOR LAYOUT OF ALL WORK AND FOR ANY
25. ALL NEW EQUIPMENT CONTROL PANELS MUST BE STANDALONE AND FULLY (7/24) PROGRAMMABLE.
DAMAGE CAUSED TO OWNER OR OTHERS BY IMPROPER CARRYING OUT OF THE WORK.
26. DUCT FLEXIBLE CONNECTIONS MUST BE INSTALLED AT INLETS AND OUTLETS OF SUPPLY AND EXHAUST
5. DRAWINGS
CONNECTIONS FOR FURNACES AND ENERGY RECOVERY VENTILATOR UNITS.
5.1.
DRAWINGS SHOW GENERAL INTENT OF THE WORK AND PROPOSED ROUTING ONLY.
5.2.
DO NOT SCALE DRAWINGS. CONTRACTOR SHALL CONFIRM ALL DIMENSIONS BY FIELD MEASURE BEFORE
27. CO-ORDINATE ALL DIMENSIONS WITH EQUIPMENT SHOP DRAWINGS.
PROCEEDING WITH THE WORK.
28. WELDING SHALL BE UNDERTAKEN BY A COMPANY CERTIFIED BY CANADIAN WELDING BUREAU UNDER
5.3.
CONTRACTOR SHALL BE RESPONSIBLE FOR IDENTIFYING POSSIBLE INTERFERENCES AND INFORMING THE
REQUIREMENTS OF DIVISION 1 OR DIVISION 2.1 OR W47.1.
ENGINEER PRIOR TO STARTING ANY WORK.
6. SITE CONDITIONS
6.1.
THE CONTRACTOR SHALL INFORM THE ENGINEER IN WRITING OF ANY ADDITIONAL DIFFICULTIES,
INTERFERENCES AND SITE CONSTRAINTS THAT MAY BE IDENTIFIED DURING THE CONSTRUCTION PERIOD.
6.2.
ALL NOISY WORK SHALL BE PERFORMED DURING NORMAL BUSINESS HOURS: BETWEEN 9AM AND 5PM,
MONDAY THROUGH FRIDAY.
6.3.
COORDINATE SITE ACCESS AND DELIVERIES WITH GENERAL CONTRACTOR.
29. MATERIALS AND WORK WHICH FAILS TO MEET SPECIFIED REQUIREMENTS WILL BE REJECTED BY THE
ENGINEER WHENEVER FOUND AT ANY TIME PRIOR TO FINAL ACCEPTANCE AND REGARDLESS OF
PREVIOUS INSPECTIONS. WHEN REJECTED, DEFECTIVE MATERIALS OR WORK SHALL BE PROMPTLY REMOVED,
REPLACED OR REPAIRED TO THE SATISFACTION OF THE ENGINEER AT NO EXPENSE TO THE OWNER.
PERMITS AND FEES:
1.
7. CLEANING
7.1.
CLEAN PREMISES DAILY AT THE END OF EACH WORK DAY.
7.2.
DO NOT ACCUMULATE EQUIPMENT, TOOLS, DEBRIS AND WASTE MATERIALS ON SITE. REMOVE FROM SITE
DAILY.
7.3.
COMPLETELY REMOVE ALL DEBRIS AND RUBBISH FROM SPACE ONCE WORK IS COMPLETE.
7.4.
ALL MATERIALS TO BE DISPOSED OF CONSTRUCTION SITE IN ACCORDANCE WITH ALL APPLICABLE
REGULATIONS.
8. OPEN FLAMES AND WELDING
8.1.
NO OPEN FLAMES OR WELDING IS PERMITTED WITHIN THE BUILDING WITHOUT WRITTEN PERMISSION BY
THE OWNER AND/OR THE ENGINEER.
8.2.
HOT WORK PERMIT MUST BE VISIBLE AT ALL TIMES.
8.3.
ADEQUATE NUMBER OF FIRE EXTINGUISHERS MUST BE PROVIDED DURING THE OPEN FLAME PROCESS.
2.
3.
10. MATERIALS
10.1. USE ONLY NEW CSA AND ULC CERTIFIED EQUIPMENT AND MATERIALS UNLESS OTHERWISE INDICATED.
10.2. ONLY FIRST CLASS WORKMANSHIP WILL BE ACCEPTED WITH RESPECT TO STANDARD PRACTICES, SAFETY,
ACCESSIBILITY, DURABILITY AND NEATNESS OF INSTALLATION WORK.
CONTROL WIRING
DOMESTIC COLD WATER PIPE (DCW)
DOMESTIC HOT WATER PIPE (DHW)
SAN
SANITARY PIPE (SAN) ABOVE GROUND
SAN
SANITARY PIPE (SAN) BELOW GROUND
G
NATURAL GAS PIPE (G)
V
VENT LINE
STORM LINE
ST
CO
UPTURNED CLEANOUT - BELOW GROUND
CO
HORIZONTAL CLEANOUT - ABOVE GROUND
TEMPERATURE SENSOR/THERMOSTAT
T
SUPPLY DIFFUSER
M
WATER METER
G
GAS METER
DRAIN C/W P-TRAP
INV.
INVERT
TYP.
TYPICAL
CO/NOX
CARBON MONOXIDE / NITROGEN DIOXIDE DETECTOR
VALVE
THE CONTRACTOR SHALL ENSURE THAT THE JURISDICTIONAL AUTHORITIES ARE NOTIFIED OF THE DATE
FOR THE COMMENCEMENT OF THE WORK AND THE DATES OF ACTIVITY OF THE WORK FOR WHICH
MUNICIPAL INSPECTORS ARE REQUIRED TO BE PRESENT. THE CONTRACTOR SHALL SEND A COPY OF ALL
CORRESPONDENCES TO THE ENGINEER.
FD
FLOOR DRAIN
FFD
FUNNEL FLOOR DRAIN
THE CONTRACTOR SHALL BE RESPONSIBLE SHOULD FAILURE OCCUR.
FIRE RATED DAMPER
AIR TERMINAL: TYPE
PROTECTION OF THE WORK AND ADJACENT PROPERTY:
2.
THE CONTRACTOR SHALL PROTECT THE WORK, THE SITE, AND ANY OTHER PROPERTY ADJACENT TO THE SITE
FROM DAMAGE WHICH MAY ARISE AS A RESULT OF ITS OPERATIONS UNDER THE CONTRACT AND SHALL BE
LIABLE FOR ANY DAMAGES WHICH MAY BE ACCESSIONED; AND THE CONTRACTOR SHALL BE RESPONSIBLE
FOR MAKING GOOD SUCH DAMAGES AT ITS EXPENSE IN THE MANNER DIRECTED BY AND TO SATISFACTION
OF ENGINEER.
THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE TO PROVIDE FOR AND BEAR THE COSTS OF
PREVENTATIVE MEASURES TO ACCOMMODATE THE FORCES OF NATURE, WHICH CAN RESULT IN FREEZING,
FLOODING, OVERHEATING, OR SIMILAR CIRCUMSTANCES, WHICH OCCUR UNTIL CONTRACT COMPLETION.
SCOPE OF WORK & PROJECT DESCRIPTION:
ALL WORK AS INDICATED IN DRAWINGS AND SPECIFICATIONS.
11. SHOP DRAWINGS
11.1. SUBMIT 4 COPIES OF SHOP DRAWINGS, UNLESS OTHERWISE INDICATED, FOR ENGINEER'S REVIEW.
11.2. SUBMIT SHOP DRAWINGS AND PRODUCT DATA FOR ENGINEER'S REVIEW COVERING ALL RELEVANT
DETAILS, DIMENSIONS AND PERFORMANCE.
11.3. SHOP DRAWINGS MUST BE REVIEWED, STAMPED AND SIGNED BY THE CONTRACTOR AND THE GENERAL
CONTRACTOR PRIOR TO SUBMITTING TO CONSULTANT / ENGINEER FOR REVIEW.
2.
CONTRACTOR SHALL PROVIDE HVAC EQUIPMENT, GAS PIPING, DUCTWORK, GRILLES, CONTROLS, PLUMBING
EQUIPMENT AND FIXTURE ROUGH-INs AS SHOWN ON DRAWINGS AND SPECIFICAITONS ON DRAWING M-1
THROUGH M-4.1.
12. CUTTING, PATCHING AND PAINTING REQUIREMENTS
12.1. PROVIDE CUTTING, PATCHING AND PAINTING FOR ALL OPENINGS. USE QUALIFIED TRADES FOR THIS
WORK. RESTORE FINISHES TO MATCH EXISTING SURROUNDINGS.
12.2. SUPPLY AND INSTALL APPROVED FIRESTOPS AS REQUIRED TO MAINTAIN FIRE RATING.
12.3. PIPING AND VENTS THROUGH WALL AND ROOF SHALL BE BY THE MECHANICAL DIVISION CONTRACTOR,
INCLUDING ALL PATCHING.
1.
THE CONTRACTOR SHALL HEREBY ASSUME THE DEFENSE OF, FULLY INDEMNITY AND HOLD HARMLESS THE
OWNER, ITS ENGINEER, AGENTS AND EMPLOYEES IN RESPECT OF THE AMOUNT OF ANY CLAIM, DEMAND,
LOSS, COST, EXPENSE (INCLUDING REASONABLE LEGAL EXPENSES), ACTION, SUIT, PROCEEDING, LIABILITY,
FINE, PENALTY, INTEREST, PAYMENT OR DAMAGE (COLLECTIVELY REFERRED AS "CLAIMS") BY WHOMSOEVER
(INCLUDING, WITHOUT LIMITATION, THE OWNER) WHICH IS MADE, SUSTAINED, BROUGHT OR PROSECUTED
IN ANY MANNER BASED UPON, OCCASIONED BY OR ATTRIBUTABLE TO ANY BREACH OF THE CONTRACT BY THE
CONTRACTOR, OR TO ANY WILLFUL MISCONDUCT, FAULT, OR NEGLIGENT ACT OR OMISSION OF THE
CONTRACTOR OR ANY PERSON, AGENT, CONSULTANT, FIRM OR CORPORATION FOR WHOSE ACTS THE
CONTRACTOR IS LIABLE AT LAW. FURTHER, THE CONTRACTOR SHALL PAY ANY AMOUNT OF CLAIMS INCURRED
BY THE OWNER ON ACCOUNT OF ANY INJURIES, INCLUDING DEATH OR DAMAGES, RECEIVED OR SUSTAINED
BY ANY PERSONS OR PROPERTY AND IF IT FAILS TO DO SO, THE OWNER MAY PAY SUCH CLAIMS AND DEDUCT
THE AMOUNT THEREOF FROM ANY MONIES DUE, OR TO BECOME DUE, TO THE CONTRACTOR, OR OTHERWISE
RECOVER SUCH AMOUNTS OR ANY BALANCE THEREOF FROM THE CONTRACTOR.
AIR VOLUME (CFM)
SIZE OR NECK DIA. (IN)
FLUSH MOUNTED INTERIOR/EXTERIOR NON-FREEZE HOSE BIBB.
GM
GAS METER
BFP
BACK FLOW PREVENTER
BBH
U/C
BASE BOARD HEATER
UNDER CUT DOOR GRILLE
'EF-1'
EXHAUST FAN
FFH
FAN FORCED HEATER
RETURN DUCT DOWN
INDEMNIFICATION:
14. PENETRATIONS THROUGH FLOORS AND WALLS
2. SUBJECT TO ANY SUPPLEMENTARY CONDITION WITH RESPECT TO THE PAYMENT OF LIQUIDATED DAMAGES, IF
14.1. UNLESS OTHERWISE SPECIFIED ON DRAWINGS, GLASS FIBRE FIRE RETARDANT INSULATION AND
APPLICABLE, NEITHER PARTY SHALL BE LIABLE TO THE OTHER PARTY FOR ANY CONSEQUENTIAL DAMAGES,
FIRESTOP CAULKING SHALL BE PACKED AROUND PIPE OPENINGS IN FLOORS AND WALLS AT TIME OF PIPE
INCLUDING, BUT NOT LIMITED TO, CLAIMS FOR LOSS OF PROFIT OR REPUTATION.
INSTALLATION. FIRESTOP CAULKING SHALL BE "3M FIRE BARRIER" FIRETEMP CAULK OR EQUIVALENT.
14.2. APPLY FIRESTOP SYSTEMS IN ACCORDANCE WITH 3M'S INSTRUCTIONS. ALL SYSTEMS SHALL MEET CSA
EMERGENCIES:
F-SYSTEM RATINGS FOR THE PARTICULAR FIRE RATING OF THE PENETRATED SURFACE.
14.3. FIRESTOPPING CONTRACTOR MUST BE A LICENSED 3M CERTIFIED INSTALLER (REFER TO LIST IN
1. THE ENGINEER HAS THE DISCRETIONARY AUTHORITY IN AN EMERGENCY TO STOP THE PROGRESS OF THE
SPECIFICATION PACKAGE).
WORK WHENEVER SUCH STOPPAGE MAY BE NECESSARY TO ENSURE THE SAFETY OF LIFE, THE WORK, OR
14.4. MATERIALS SHALL BE ASBESTOS-FREE ELASTOMERIC MATERIALS, TESTED, LISTED AND LABELED BY ULC
NEIGHBORING PROPERTY OR TO AVOID THE DISRUPTION OF THE OWNERS' WORK AND SERVICES. THIS
IN ACCORDANCE WITH CAN 4-S115-M85, AND CAN/ULC-S101-M FOR INSTALLATION IN ULC DESIGNATED
INCLUDES AUTHORITY TO MAKE CHANGES IN THE WORK. IN SUCH A CASE, IF WORK HAS BEEN PERFORMED BY
FIRE STOPPING AND SMOKE SEAL SYSTEMS, TO PROVIDE A POSITIVE FIRE, WATER AND SMOKE SEAL AND
THE CONTRACTOR UNDER DIRECT ORDER OF THE ENGINEER, THE CONTRACTOR SHALL HAVE THE RIGHT TO
A FIRE RESISTANCE RATING (FLAME, HOSE STREAM AND TEMPERATURE) NOT LESS THAN THE FIRE RATING
CLAIM THE VALUE OF SUCH WORK.
FOR SURROUNDING CONSTRUCTION. MATERIALS SHALL BE COMPATIBLE WITH ABUTTING DISSIMILAR
MATERIALS AND FINISHES.
15. DIELECTRIC ISOLATION
15.1. PROVIDE ISOLATION WHEN USING DISSIMILAR MATERIALS, TO PREVENT GALVANIC ACTION.
DESCRIPTION
NEW WORK
THE CONTRACTOR SHALL APPLY FOR AND OBTAIN IN ITS OWN NAME, PERMITS, LICENSES, APPROVALS AND
SHALL PAY FEES AND GIVE NOTICES NECESSARY PRIOR TO COMMENCING WORK AND INCIDENTAL TO THE
DUE AND LAWFUL PERFORMANCE OF THE WORK, IN ACCORDANCE WITH THE SPECIFICATIONS.
1.
13. CORING REQUIREMENTS
13.1. FOR ALL CORING LESS THEN 3" DIA. CONTRACTOR SHALL BE RESPONSIBLE FOR SCANNING AREA PRIOR TO
CORING THROUGH FLOORS/CEILINGS.
13.2. FOR ALL CORING GREATER THEN 3" DIA. CONTRACTOR SHALL BE RESPONSIBLE FOR X-RAYING AREA PRIOR
TO CORING THROUGH FLOORS/CEILINGS.
SYMBOL
FRD
1.
9. FIRE EXTINGUISHERS
9.1.
PROVIDE IN ACCORDANCE WITH NFPA 10 AND AUTHORITY HAVING JURISDICTION.
9.2.
PROVIDE FIRE EXTINGUISHER AT EACH EXIT DOOR WAY OR AS INDICATED ON DRAWINGS.
9.3.
MAXIMUM TRAVEL DISTANCE TO EXTINGUISHER SHALL BE 75FT.
9.4.
EXTINGUISHER SHALL BE 10Lb (OR AS INDICATED), MULTI-PURPOSE DRY CHEMICAL, STORED PRESSURE
RECHARGEABLE TYPE, ULC LABELED FOR A, B AND C CLASS PROTECTION WITH SHUT-OFF NOZZLE AND
WALL MOUNTING KIT.
LEGEND
GENERAL NOTES:
SUPPLY DUCT DOWN
RETURN / EXHAUST DUCT UP
SUPPLY DUCT UP
X XXX
XX
AIR TERMINAL:TYPE
AIR VOLUME (L/S)
SIZE OR NECK DIA.(mm)
C/W
COMPLETE WITH
F.F.
FINISHED FLOOR
CTE
CONNECT TO EXISTING
DRAWING LIST
DWG NO.
DESCRIPTION
M-1.0
GENERAL NOTES, SPECIFICATIONS, LEGEND AND DRAWING LIST
M-1.1
PLUMBING, HVAC AND GAS PIPING NOTES
M-1.2
DETAILS
M-1.3
DETAILS
M-1.4
SCHEDULES
16. VIBRATION ISOLATION
16.1. PROVIDE AND INSTALL MINIMUM 3/4" THICK MSN ELASTOMERIC PADS W/MOUNTS UNDER FLOOR
MOUNTED HVAC EQUIPMENT AS PER MANUFACTURER RECOMMENDATIONS.
M-1.5
PLUMBING FIXTURE SCHEDULE AND CO/NOX SPECIFICATIONS
M-1.6
PLUMBING FIXTURE SCHEDULE
17. ELECTRICAL
17.1. ALL LOW VOLTAGE CONTROL WIRING (<50V) SHALL BE BY THIS DIVISION, TO ELECTRICAL DIVISION
STANDARDS.
M-2.0
GROUND FLOOR PLAN - PLUMBING AND DRAINAGE LAYOUT
M-2.1
SECOND FLOOR PLAN - PLUMBING PLUMBING AND DRAINAGE LAYOUT
M-2.2
ROOF PLAN - HVAC AND ROOF DRAIN LAYOUT
M-2.3
PART GROUND FLOOR PLANS - PLUMBING AND DRAINAGE
M-3.0
GROUND FLOOR PLAN - HVAC
M-3.1
SECOND FLOOR PLAN - HVAC
18. PRESSURE TESTING
18.1. ALL PIPING SYSTEMS SHALL BE PRESSURE TESTED TO 860 kPa OR 1.5 TIMES SYSTEM OPERATING
PRESSURE FOR A DURATION OF 24 HRS UNLESS OTHERWISE INDICATE.
19. AS BUILT DRAWINGS
19.1. MAINTAIN A RECORD OF ALL REVISIONS. PREPARE RECORD DRAWINGS IN A NEAT MANNER SHOWING ALL
DEVIATIONS IN WORK. ON COMPLETION OF WORK, SUBMIT TO THE ENGINEER ONE HARD COPY OF AS
BUILT DRAWINGS AND ELECTRONIC FORMAT DRAWINGS (IN AUTOCAD).
PIPING, PLUMBING, FIXTURES AND ACCESSORIES:
1. GENERAL
1.1.
MATERIAL AS INDICATED ON DRAWINGS. IF MATERIALS HAVE NOT BEEN INDICATED ON
DRAWINGS, THEN INSTALLATION SHALL ADHERE TO THIS SECTION.
1.2.
PROVIDE MATERIALS IN ACCORDANCE WITH THIS SECTION UNLESS OTHERWISE SPECIFIED.
1.3.
PROVIDE ALL MATERIALS AS REQUIRED INCLUDING PIPING, VALVES, FITTINGS, TRAPS,
HANGERS, SUPPORTS AND THERMAL INSULATION FOR COMPLETE SYSTEM INSTALLATION AND
OPERATION.
1.4.
PROVIDE MINIMUM PIPE INSULATION THICKNESSES IN ACCORDANCE WITH LATEST EDITION
OF ASHRAE STANDARD 90.1 UNLESS OTHERWISE INDICATED.
1.5.
PROVIDE ALL PLUMBING SYSTEMS, FIXTURES AND ACCESSORIES IN ACCORDANCE WITH OBC
AND LOCAL AUTHORITIES HAVING JURISDICTION.
PIPING, PLUMBING, FIXTURES AND ACCESSORIES:
HVAC: (CONT'D)
15.1.1.
CATCH BASIN SHALL BE PROVIDED COMPLETE WITH
8.6.
ACCEPTABLE BLANKET MINERAL FIBER SHALL BE JOHNS MANVILLE MICROLITE DUCT WRAP
15.1.1.1.
4" SIDE OUTLET
TYPE 100 OR EQUIVALENT.
15.1.1.2.
EPOXY CAST IRON BODY
8.7.
ACCEPTABLE RIGID MINERAL FIBERBOARD SHALL BE JOHNS MANVILLE 800 SERIES
15.1.1.3.
ANCHOR FLANGE
SPIN-GLASS TYPE OR EQUIVALENT.
15.1.1.4.
12.75"X12.75" SQUARE EPOXY COATED DUCTILE IRON HINGED GRATE
8.8.
SEAL ALL JOINTS WITH ULC LISTED SELF-ADHESIVE INSULATION TAPE FOR INDOOR DUCTS
15.1.1.5.
INTEGRAL TRAP WITH CLEANOUT PLUG
AND INSULATION.
15.1.1.6.
SEDIMENT BUCKET
8.9.
USE RIGID INSULATION AND DRYWALL TYPE CORNER BEADS IN AREAS WHERE INSULATION
15.1.1.7.
NO HUB OUTLET
IS EASILY SUSCEPTIBLE TO DAMAGE.
15.1.1.8.
SAFE LIVE LOAD OF 10,000LBS
15.2.6.
CONTRACTOR SHALL REFER TO MANUFACTURER INSTALLATION REQUIREMENTS.
9. ACOUSTIC INSULATION
15.2.7.
CATCH BASIN SHALL BE SIMILAR TO WATTS MODEL FD-430 SERIES OR APPROVED EQUAL.
9.1.
ACOUSTIC INSULATION SHALL BE PROVIDED WHERE INDICATED ON DRAWINGS AND IN
ALL RETURN AIR TRANSFER DUCTWORK AND WITHIN 15' OF EQUIPMENT FAN BLOWER.
2. THERMAL INSULATION
15.3. OIL INTERCEPTOR (INT-1)
9.2.
ACOUSTIC INSULATION SHALL BE 1/2" THICK INTERNAL LINING, C/W FACTORY APPLIED
2.1.
15.3.1.
OIL INTERCEPTOR SHALL BE FIBERGLASS REINFORCED PLASTICS PROVIDED COMPLETE
BLACK ACRYLIC POLYMER COATING, HAVING FLAME SPREAD RATING OF 25 OR LESS AND
WITH
ELASTOMERIC THERMAL INSULATION. C/W FLEXIBLE ELASTOMERIC THERMAL INSULATION
SMOKE DEVELOPMENT CLASSIFICATION OF 50 OR LESS.
15.3.1.1.
EXTENSION COLLAR AND ASSHTO M306 TRAFFIC LOAD RATED COVER
MESH COATING (FOR UV PROTECTION) FOR LOCATIONS WITH UV EXPOSURE.
9.3.
DUCT SIZES SHOWN ON DRAWINGS INDICATE CLEAR INSIDE DIMENSIONS.
15.3.1.2.
ACCESSWAYS, BAFFLES
2.2.
FOR ALL OTHER PROCESSES AND PLUMBING PIPES: UNLESS OTHERWISE INDICATED, PROVIDE
9.4.
ACCEPTABLE ACOUSTIC DUCT LINER SHALL BE JOHNS MANVILLE PERMACOTE LINACOUSTIC
15.3.2.
INTERCEPTOR SHALL ACCEPT THE FOLLOWING CAPACITIES AND ENSURE ACCURATE
AND INSTALL FIBERGLASS INSULATION WITH REINFORCED VAPOUR RETARDER FACING AND
STANDARD/HP OR EQUIVALENT.
OIL/SEDEMANT SEPARATION.
FACTORY APPLIED ADHESIVE CLOSURE SYSTEM. INSULATION SHALL BE JOHNS MANVILLE
9.5.
APPLY BLACK ACRYLIC POLYMER COATING TO ALL FIELD CUT EDGES AS PER SMACNA
15.3.3.
OIL - 66 GAL
MICRO-LOK AP-T PLUS OR EQUIVALENT.
STANDARDS.
15.3.4.
SOLID - 48 GAL
2.3.
MINIMUM PIPE THICKNESSES SHALL BE IN ACCORDANCE WITH LATEST EDITION OF ASHRAE
9.6.
ACCEPTABLE COATING SHALL BE JOHNS MANVILLE SUPERSEAL OR EQUIVALENT.
15.3.5.
TOTAL - 150 GAL
STD. 90.1.
15.3.6.
CONTRACTOR SHALL REFER TO MANUFACTURER INSTALLATION REQUIREMENTS.
2.4.
MINIMUM PIPE INSULATION SHALL BE 1" FOR ALL HOT WATER HEATING PIPES, CONDENSATE
10. FLEXIBLE CONNECTIONS
15.3.7.
OIL INTERCEPTOR SHALL BE SIMILAR TO GREENTURTLE MODEL OMC 150 OR APPROVED
LINE, DOMESTIC HOT AND COLD WATER PIPES UNLESS OTHERWISE INDICATED.
10.1. FLEXIBLE CONNECTIONS TO BE FIRE RESISTANT NEOPRENE COATED GLASS FABRIC.
EQUAL.
2.5.
DOMESTIC HOT WATER PIPES GREATER THAN 2" SHALL HAVE 1-1/2" THICK INSULATION.
PROVIDE FLEXIBLE CONNECTIONS AT ALL DUCTED HVAC UNITs, ERVs, FANs AND WHERE
15.3.8. PROVIDE EXTERNAL OIL STORAGE TANK.
2.6.
INDICATED ON DRAWINGS.
2.6.1.
RUN OUTS (<13FT LONG): 1-1/2";
11. GAS FIRED EQUIPMENT COMBUSTION AND VENTING (ROOFTOP UNIT AND UNIT HEATER)
2.6.2.
PIPE UP TO:
: 2"
11.1. GAS FIRED EQUIPMENT INSTALLATION AS PER MANUFACTURER RECOMMENDATION AND
: 2-1/2"
LOCAL APPLICABLE CODE.
HVAC:
: 3"
11.2.
INSTALLATION AND VENTING PROVISIONS MUST BE IN ACCORDANCE WITH CAN/CSA
: 3-1/2".
STANDARD B149.1, ANSI Z223.1-NFPA 54, AND LOCAL AUTHORITIES HAVING
1. DUCTWORK
JURISDICTION. SINGLE WALL TYPE B VENT PIPE MUST BE USED FOR HORIZONTAL
1.1.
DUCTWORK SHALL BE CONSTRUCTED TO ASHRAE/SMACNA STANDARDS.
2.7.
PROVIDE AND INSTALL PVC JACKET AND VAPOUR RETARDER (IF NOT PROVIDED ELSEWHERE)
VENTING, DOUBLE WALL TYPE B VENT TO BE USED FOR VERTICAL VENTING.
1.2.
DUCT SIZES ARE LISTED ON DRAWINGS. ALL DUCT SIZES SHOWN ARE CLEAR INSIDE
FOR INDOOR INSULATED PIPE APPLICATIONS. JACKETING SHALL BE JOHNS MANVILLE
11.3.
VENTING SUPPORT DISTANCES SHALL BE AS PER MANUFACTURER RECOMMENDATIONS.
DIMENSIONS.
ZESTON 300 SERIES OR EQUIVALENT.(NOT NECESSARY FOR USE WITH MICRO-LOK AP-T PLUS)
11.4.
ROOF/WALL
PENETRATION PIECES SHALL BE ULC LISTED AND PROVIDED BY THE VENT
1.3.
ALL
FLEXIBLE
DUCTWORK
TO
DIFFUSERS
SHALL
BE
ALUMINUM
SPIRAL,
MAXIMUM
LENGTH
2.8.
PROVIDE AND INSTALL ALUMINUM JACKET WITH A LAMINATED MOISTURE RETARDER FOR
MANUFACTURER.
10FT.
OUTDOOR INSULATED PIPE APPLICATIONS. SECURE JACKET USING METAL BANDS AT BUTT
11.5. WHERE EXPOSED TO WEATHER, THE CASING JOINTS SHALL BE SEALED TO PREVENT
1.4.
SEAL ALL NEW LOW PRESSURE DUCTS (<2IN.WC.) AND LOW PRESSURE DUCT
JOINT OVERLAPS AND BETWEEN JOINTS.
RAINWATER FROM ENTERING THE SPACE BETWEEN INNER AND OUTER WALLS.
MODIFICATIONS TO SMACNA SEAL CLASS 'C' USING SEALANT OR ALUMINUM TAPE; OR A
2.9.
INSTALL ALL INSULATION AND JACKETS AS PER MANUFACTURER RECOMMENDATIONS.
11.6. VENT SHALL TERMINATE IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS AND
COMBINATION THEREOF.
2.10. MAINTAIN UNINTERRUPTED CONTINUITY AND INTEGRITY OF VAPOUR RETARDER AND
LOCAL CODES.
FINISHES. HANGERS AND SUPPORTS TO BE OUTSIDE VAPOUR OF RETARDER.
11.7. MAXIMUM HORIZONTAL VENT LENGTHS AS PER MANUFACTURER RECOMMENDATION AND
2. FLEXIBLE DUCTS (LOW PRESSURE)
2.11. APPLY HIGH COMPRESSIVE STRENGTH INSULATION, SUITABLE FOR SERVICE, AT OVERSIZED
REQUIREMENTS.
2.1.
NON-COLLAPSIBLE, COATED MINERAL BASE PERFORATED FABRIC TYPE HELICALLY
SADDLES AND SHOES WHERE INSULATION SADDLES HAVE NOT BEEN PROVIDED
11.8. ALL ACCESSORIES (EXIT CONE, CONNECTORS AND DRAIN FITTINGS) WITH DIRECT OR
SUPPORTED BY AND MECHANICALLY BONDED TO STEEL WIRE WITH FACTORY APPLIED
2.12. INSULATION SHALL BE FOIL FACED.
INDIRECT CONTACT WITH CONDENSATE SHALL BE PROVIDED IN AL29-4C.
FLEXIBLE GLASS FIBRE ACOUSTIC INSULATION AND ENCASED IN ALUMINUM FOIL AND
2.13. INSULATION SHALL HAVE A FLAME SPREAD RATING OF 25 OR LESS AND A SMOKE
11.9. PROVIDE ENGINEERED SHOP DRAWINGS OF SYSTEM FOR APPROVAL.
MYLAR LAMINATE VAPOUR BARRIER.
DEVELOPMENT CLASSIFICATION OF 50 OR LESS.
11.10. ACCEPTABLE MANUFACTURER: DURAVENT, HEATFAB OR APPROVED EQUAL.
2.2.
MAXIMUM LENGTH SHALL BE 10FT.
2.3.
DO NOT USE FOR EXPOSED CEILING APPLICATIONS.
3. PIPE HANGERS AND SUPPORTS
12. PACKAGED ROOFTOP UNIT (RTU)
3.1.
PIPING HANGERS AND SUPPORTS SHALL BE SPACED IN ACCORDANCE WITH APPLICABLE
12.1. NATURAL GAS FIRED STAINLESS STEEL HEAT EXCHANGER C/W AUTOMATIC IGNITION,
3. ELBOWS
CODES AND AUTHORITIES HAVING JURISDICTION.
MINIMUM 80% EFFICIENCY.
3.1.
FOR LOW PRESSURE SYSTEM: ELBOWS SHALL HAVE RADIUS OF NOT LESS THAN DUCT
3.2.
PIPE HANGERS SHALL BE GRINNELL ADJUSTABLE CLEVIS TYPE OR EQUIVALENT.
12.1.1. FLAME ROLLOUT
WIDTH. BARBER-COLEMAN "AIRTURNS", HART & COOLEY "DUCTURNS" TURNING VANES OR
3.3.
EXTERIOR SUPPORTS SHALL BE S.S. GRINNELL OR EQUIVALENT
12.2. DX (R-410 REFRIGERANT) COOLING, SCROLL COMPRESSORS, CRANKCASE HEATER
DUCTMATE TURNING VANES SHALL BE PROVIDED IN ELBOWS OF LESSER RADIUS IN ALL
12.2.1. HIGH PRESSURE SWITCH
DUCTWORK.
4. PRESSURE TESTING
12.2.2.
THERMOSTATIC EXPANSION VALVE
4.1.
ALL PIPING SYSTEMS SHALL BE HYDROSTATICALLY PRESSURE TESTED TO A MINIMUM OF 860
12.3. CONSTANT VOLUME AIRFLOW C/W STARTERS TO MATCH HP
kPa OR 1-1/2 TIMES SYSTEM OPERATING PRESSURE (WHICHEVER IS GREATER) FOR A PERIOD 4. VIBRATION ISOLATION
12.4. ACCESSORIES: UNIT TO BE COMPLETE WITH COIL GAURD, CONDENSATE DRAIN TRAP,
4.1.
PROVIDE AND INSTALL MINIMUM 19mm THICK NSN ELASTOMERIC PADS W/ MOUNTS UNDER
OF 24 HOURS UNLESS OTHERWISE INDICATED.
DISCONNECT SWITCH, LIQUID & DISCHARGE SERVICE VALVES, BAROMETRIC RELIEF
FLOOR MOUNTED HVAC EQUIPMENT AS PER MANUFACTURER RECOMMENDATIONS.
DAMPERS AND EXHAUST HOOD, ECONOMIZER C/W DIFFERENTIAL ENTHALPY CONTROL AND
PROVIDE AND INSTALL NEOPRENE OR SPRING W/ ELASTOMERIC WASHER OR SPRING W/
5. DRAINAGE WASTE AND VENT PIPING
(AS REQUIRED) MOTORIZED INTAKE DAMPER, MERV-8 DISPOSABLE AIR FILTERS,
ELASTOMERIC ELEMENT HANGERS FOR CEILING SUSPENDED EQUIPMENT, DUCTWORK AND
5.1.
ABOVE GROUND SANITARY, STORM AND VENT LINES LESS THAN 3" SHALL BE TYPE DWV TO
STANDARD ROOF CURB.
ACCESSORIES.
ASTM B306 WITH CAST BRASS OR WROUGHT COPPER FITTINGS TO CAN/CSA B125.
12.5. ALL INFORMATION SHALL BE AS SCHEDULED ON DWG. M-1.4 OR APPROVED EQUAL.
5.2.
JOINTS FOR COPPER TUBE/ PIPE SHALL BE TIN/ANTIMONY (95%/5%) SOLDER.
12.6. CONTRACTOR SHALL REFER TO MANUFACTURER INSTALLATION REQUIREMENTS.
5. BALANCING DAMPERS
5.3.
PROVIDE TRAP PRIMERS WHERE REQUIRED.
12.7. ALL EQUIPMENT MUST MEET THE REQUIREMENTS OF THE LATEST EDITION OF ASHRAE 90.1.
5.1.
BALANCING DAMPERS SHALL BE MANUALLY OPERATED OPPOSED BLADE OR SPLITTER TYPE.
5.4.
ABOVE GROUND SANITARY, STORM AND VENT LINES 3" AND LARGER SHALL BE CAST IRON
SPLITTER DAMPERS SHALL BE COMPLETE WITH CONTROL ROD, PIVOT BRACKET AND BALL
HUB AND SPIGOT PIPE IN ACCORDANCE WITH THE LATEST EDITION OF THE OBC FOR SOIL
13. FAN-FORCED HEATERS (FFH-1)
JOINT FITTING WITH LOCKING SETSCREW.
AND WASTE. JOINTS SHALL BE CAULKED WITH WHITE OAKUM AND SECURED WITH MOLTEN
13.1. PROVIDE CAPACITIES AS INDICATED ON PLAN.
5.2.
SPLITTER DAMPERS SHALL BE INSTALLED ON ALL BRANCH DUCT CONNECTIONS (OR
LEAD NOT LESS THEN 1" DEEP.
13.2. UNITS SHALL BE PROVIDED WITH SINGLE-POLE BUILT-IN THERMOSTAT KIT AND LOW
TAKE-OFFS) FROM DUCTS.
5.5.
BURIED SANITARY, STORM AND VENT SHALL BE MINIMUM 3" CAST IRON TO CAN/CSA-B70,
VOLTAGE RELAY.
5.3.
OPPOSED BLADE DAMPERS SHALL BE USED FOR ALL DIFFUSER/GRILLE BALANCING
JOINTS FOR CAST IRON SHALL BE HUB AND SPIGOT.
13.3. POWER REQUIREMENTS: 208V/1PH/60Hz
DAMPERS (WHERE INDICATED).
5.6.
PROVIDE AND INSTALL BACK WATER VALVE ON ALL FLOOR DRAIN.
13.4. FINISH: WHITE
13.5. SURFACE MOUNTED AND WALL RECESSED (PER DRAWING)
6. FIRE RATED DAMPERS (FRD)
6. DOMESTIC COLD AND HOT WATER PIPE
13.6. FAN-FORCED HEATERS SHALL BE STELPRO WF OR APPROVED EQUAL.
6.1.
6.1.
TYPE L COPPER TO ASTM B88M.
13.7. CONTRACTOR SHALL REFER TO MANUFACTURER INSTALLATION REQUIREMENTS.
HORIZONTAL OR VERTICAL INSTALLATION,
ULC RATED (AS PER ENCLOSURE FIRE
6.2.
JOINTS SHALL BE TIN/SILVER OR TIN/ANTIMONY (95%/5%) SOLDER AND NON-CORROSIVE
RESISTANCE RATING).
FLUX. ALL SOLDER SHALL BE LEAD FREE.
14. UNIT HEATER (UH-1)
6.2.
FRD SHALL BE RUSKIN MODEL DIBD2 STYLE B (OR EQUAL FOR DUCT HEIGHTS NOT
6.3.
PROVIDE ISOLATION VALVES FOR EACH NEW FIXTURE. VALVES SHALL BE BY PASS BALL
14.1. PROVIDE CAPACITIES AS INDICATED ON SCHEDULE.
EXCEEDING 305mm, AND DIBD2 STYLE A (OR EQUAL) FOR DUCT HEIGHTS EXCEEDING
VALVES WITH THREADED/SOLDERED ENDS, RATED FOR 400 CWP.
14.2. UNITS SHALL BE PROVIDED WITH SINGLE-POLE BUILT-IN THERMOSTAT KIT AND LOW
305mm.
6.4.
TYPE K COPPER PIPE TO ASTM B88M SHALL BE USED FOR BURIED DCW PIPE.
VOLTAGE RELAY.
6.3.
PROVIDE ACCESS DOORS AT EACH FRD UNLESS FRONTAL ACCESS TO FRD IS AVAILABLE.
6.5.
CONTRACTOR SHALL ENSURE THAT BACKFLOW PREVENTER IS INSTALLED AND PIPING ARE
14.3. POWER REQUIREMENTS: 115V/1PH/60HZ
CLEARLY MARKED AS NON-POTABLE WATER.
14.4. FINISH: BEIGE
7. DIFFUSER/GRILLES/REGISTERS
14.5. CEILING MOUNTED (PER DRAWING)
7.1.
TYPE A - SUPPLY GRILLE C/W DAMPER. EH PRICE / 520D/F/L/A. SIZE AS INDICATED ON
7. LARGE SANITARY AND VENT
14.6. UNIT HEATER SHALL BE PROVIDED COMPLETE WITH HORIZONTAL CONCENTRIC FLUE
DRAWING.
7.1.
SHALL BE MINIMUM 3" CAST IRON TO CAN/CSA-B70.
VENTING KIT.
7.2.
TYPE B - RETURN GRILLE C/W DAMPER. EH PRICE / 530D/F/L/A. SIZE AS INDICATED ON
7.2.
JOINTS FOR CAST IRON SHALL BE HUB AND SPIGOT
14.7. UNIT HEATER SHALL BE SIMILAR TO LENNOX TUA OR APPROVED EQUAL.
DRAWING.
14.8. CONTRACTOR SHALL REFER TO MANUFACTURER INSTALLATION REQUIREMENTS.
7.3.
TYPE C - EXHAUST GRILLE C/W DAMPER. EH PRICE / 530D/F/L/A. SIZE AS INDICATED ON
8. VALVES (CW)
DRAWING.
8.1.
NEW VALVES UP TO 50MM (2 ) OR LESS SHALL BE BRASS OR BRONZE BALL VALVES WITH
15. CONTROLS
7.4.
ALL DIFFUSER/GRILLE/REGISTER COLOURS SHALL BE CONFIRMED AT THE SHOP DRAWING
(NPT)THREADED ENDS, FULL PORT, 1034KPA, (150PSIG) 600 WOG RATING. TFE SEATS,
15.1. CONTRACTOR SHALL PROVIDE A FULLY PROGRAMMABLE CONTROL (THERMOSTAT) PER
STAGE WITH THE INTERIOR DESIGNER.
DOUBLE O-RING DESIGN, OR TEFLON PACKING, CHROME PLATED SOLID BRONZE BALL, ULC
ROOFTOP UNIT AND UNIT HEATER. EACH CONTROL SYSTEM SHALL BE COMPLETE WITH
LISTED AND FM APPROVED. KITZ #58, TOYO #5044A
MULTI-STAGE AND SIMULTANEOUS HEATING AND COOLING, OCCUPIED/UNOCCUPIED
8. THERMAL INSULATION FOR DUCTS
8.2.
ALL VALVES 65MM,(2-1/2) OR GREATER,860KPA,(125PSIG)/200WOG RATING, SHALL HAVE
OVERRIDE, TOUCHSCREEN LCD DISPLAY, 24/7 SCHEDULING, ECONOMIZER, FRESH AIR
8.1.
BLANKET OR RIGID THERMAL INSULATION ON INDOOR DUCTS SHALL BE PROVIDED AND
FLANGE CONNECTIONS.
MOTORIZED ISOLATION DAMPER CONTROL, ETC... TO PROVIDE A COMPLETE AND
INSTALLED AS FOLLOWS UNLESS OTHERWISE INDICATED:
8.3.
ACCEPTABLE MANUFACTURER: KITZ, TOYO, AMERICAN VALVE OR APPROVED EQUAL.
OPERATIONAL SYSTEM.
8.1.1.
INSULATE FULL LENGTH OF FRESH AIR SUPPLY DUCTS.
15.2. PROVIDE ASSISTANCE TO GENERAL/MECHANICAL CONTRACTOR AS INDICATED IN THE
8.1.2.
INSULATE FIRST 10FT OF EXHAUST DUCTS FROM EXTERIOR WALL OR ROOF.
9. BURIED SANITARY, STORM AND VENT
TENDER DOCUMENTS.
8.1.3.
INSULATE FULL LENGTH OF SUPPLY AND RETURN DUCTS THAT ARE ROUTED THROUGH A
9.1.
SHALL BE MINIMUM 3" CAST IRON TO CAN/CSA-B70 OR PVC PLASTIC (XFR RATED).
15.3. ROOFTOP UNIT THERMOSTAT SHALL BE SIMILAR TO LENNOX - COMMERCIAL TOUCHSCREEN
NON-CONDITIONED SPACE.
9.2.
JOINTS SHALL BE HUB AND SPIGOT
THERMOSTAT OR APPROVED EQUAL.
8.1.4.
THERMAL INSULATION IS NOT REQUIRED ON SUPPLY AND RETURN DUCTS CONFINED
9.3.
PROVIDE TRAP PRIMERS WHERE REQUIRED.
WITHIN A CONDITIONED SPACE (INCLUDING RETURN PLENUM CEILINGS).
9.4.
PROVIDE BACKWATER VALVE ON ALL FLOOR DRAINS AND WHERE INDICATED ON DRAWINGS.
8.1.5.
ACOUSTICALLY LINED INTERIOR DUCTS NEED NOT TO BE THERMALLY INSULATED.
8.1.6.
USE RIGID INSULATION AND DRYWALL TYPE CORNER BEADS IN AREAS WHERE
10. FLOW CONTROL ROOF DRAIN (RD)
INSULATION IS EASILY SUSCEPTIBLE TO DAMAGE.
10.1. MIFAB SERIES R1100-F LACQUERED CAST IRON ROOF DRAIN WITH ANCHOR FLANGE, CAST
8.2.
INSULATION SHALL BE FOIL FACED HAVING FLAME SPREAD RATING OF 25 OR LESS AND A
IRON WATERPROOFING MEMBRANE CLAMP RING WITH INTEGRAL GRAVEL STOP, ACCUFLOW
SMOKE DEVELOPMENT CLASSIFICATION OF 50 OR LESS.
PARABOLIC WEIR (MAXIMUM FLOW OF 17.5GPM) F1 SLOTS, AND STANDARD SELF-LOCKING
8.3.
THERMAL INSULATION SHALL BE 1-1/2" THICK BLANKET MINERAL FIBER OR 1" THICK RIGID
POLYDOME STRAINER, WITH A FREE AREA OF 43 SQUARE INCHES.
MINERAL FIBERBOARD FOR WARM AIR DUCTS AND DUCTS BETWEEN OUTSIDE WALLS AND
10.2. COORDINATE SELECTION WITH ROOF MEMBRANE.
MIXING PLENUMS.
10.3. ROOF DRAIN SHALL BE MIFAB R1 100-F OR EQUAL.
8.4.
THERMAL INSULATION FOR COLD AIR DUCTS SHALL BE 1-1/2" THICK RIGID INSULATION,
OR 2" THICK BLANKET MINERAL FIBRE.
11. FLOOR DRAINS
8.5.
VAPOUR-RETARDER MEMBRANE SHALL BE INSTALLED WITH INSULATION ON COLD,
11.1. CAST OR DUCTILE IRON SIZE AS INDICATED ON DRAWING.
DUAL-TEMP AND FRESH AIR AIR SUPPLY DUCTS.
11.2. DRAIN SHALL BE ZURN OR EQUAL.
11.3. PROVIDE PRIMING AT EACH FLOOR DRAIN FROM NEAREST LAVATORY OR WATER CLOSET.
12. CLEAN-OUTS AND VENTING
12.1. PROVIDE IN ACCORDANCE WITH OBC CHAPTER 7 AND AS INDICATED ON DRAWINGS.
13. AUTOMATIC ELECTRONIC TRAP PRIMMER
13.1. (FLUSH) WALL MOUNTED NEMA 2 STAINLESS STEEL ENCLOSURE
13.2. FACTORY ASSEMBLED BRONZE BALL VALVE, WATER HAMMER ARRESTOR, SOLENOID VALVE,
ATMOSPHERIC VACUUM BREAKER AND A TYPE l COPPER MANIFOLD C/W COMPRESSION
FITTING.
13.3. ELECTRONIC SINGLE POINT POWER CONNECTION 120V 1AMP DRAW, MANUAL OVERRIDE
SWITCH POINT POWER STEEL ACCESS PANEL.
13.4. ALL FLOOR DRAINs AND/OR DRY P-TRAPs SHALL BE PROVIDE WITH A PRIMING SYSTEM.
14. FIXTURES:
14.1. PROVIDE ALL NEW FIXTURES (AS INDICATED).
14.2. NEW FIXTURES SHALL BE BARRIER FREE AND CSA APPROVED.
14.3. FIXTURES SHALL MEET WATER EFFICIENCY REQUIREMENTS AS INDICATED IN OBC CHAPTER 7.
15. PROVIDE FIXTURES AS INDICATED BELOW:
15.1. CATCH BASIN/AREA DRAIN (CB-1)
GAS PIPING:
1. PIPE
1.1.
STEEL PIPE: TO ASTM A53, GRADE B, SCHEDULE 40, SEAMLESS AS FOLLOWS:
1.1.1.
NPS 1/2 TO 2, SCREWED.
1.1.2.
NPS 2 1/2 AND OVER, PLAIN END.
1.1.3.
COPPER TUBE: TO ASTM B75M.
1.2.
JOINING MATERIAL
1.2.1.
SCREWED FITTINGS: PULVERIZED LEAD PASTE.
1.2.2.
WELDED FITTINGS: TO CSA W47.1.
1.2.3.
FLANGE GASKETS: NONMETALLIC FLAT.
1.2.4.
SOLDERED: TO ASTM B32, TIN ANTIMONY 5/5.
2. FITTINGS
2.1.
STEEL PIPE FITTINGS, SCREWED, FLANGED OR WELDED:
2.1.1.
MALLEABLE IRON: SCREWED, BANDED, CLASS 150.
2.1.2.
STEEL PIPE FLANGES AND FLANGED FITTINGS: TO ANSI/ASME B16.5.
2.1.3.
WELDING: BUTT-WELDING FITTINGS.
2.1.4.
UNIONS: MALLEABLE IRON, BRASS TO IRON, GROUND SEAT, TO ASTM A47M.
2.1.5.
BOLTS AND NUTS: TO ANSI B18.2.1.
2.1.6.
NIPPLES: SCHEDULE 40, TO ASTM A53.
2.2.
COPPER PIPE FITTINGS, SCREWED, FLANGED OR SOLDERED:
2.2.1.
CAST COPPER FITTINGS: TO ANSI B16.18.
2.2.2.
WROUGHT COPPER FITTINGS: TO ANSI/ASME B16.22.
3. VALVES
3.1.
PROVINCIAL CODE APPROVED, LUBRICATED PLUG TYPE.
4. INSTALLATION
4.1.
INSTALL IN ACCORDANCE WITH APPLICABLE PROVINCIAL CODES.
4.2.
INSTALL IN ACCORDANCE WITH CAN/CGA B149.1.
4.3.
ASSEMBLE PIPING USING FITTINGS MANUFACTURED TO ANSI STANDARDS.
4.4.
CONNECT TO EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTION
UNLESS OTHERWISE INDICATED.
4.5.
SLOPE PIPING DOWN IN DIRECTION OF FLOW TO LOW POINTS.
4.6.
INSTALL DRIP POINTS:
4.6.1.
AT LOW POINTS IN PIPING SYSTEM.
4.6.2.
AT EACH CONNECTION TO EQUIPMENT.
4.7.
4.8.
4.9.
4.10.
4.11.
4.12.
4.13.
USE ECCENTRIC REDUCERS AT PIPE SIZE CHANGE INSTALLED TO PROVIDE POSITIVE
DRAINAGE.
PROVIDE CLEARANCE FOR ACCESS AND FOR MAINTENANCE.
REAM PIPES, CLEAN SCALE AND DIRT, INSIDE AND OUT.
INSTALL PIPING TO MINIMIZE PIPE DISMANTLING FOR EQUIPMENT REMOVAL.
INSTALL VALVES WITH STEMS UPRIGHT OR HORIZONTAL UNLESS OTHERWISE APPROVED
BY ENGINEER.
INSTALL VALVES AT BRANCH TAKE-OFFS TO ISOLATE EACH PIECE OF EQUIPMENT, AND
AS INDICATED.
CONTRACTOR SHALL APPLY YELLOW PAINT TO ALL GAS PIPING.
5. TESTING
5.1.
TEST SYSTEM IN ACCORDANCE WITH CAN/CGA B149.1 AND REQUIREMENTS OF
AUTHORITIES HAVING JURISDICTION.
5.2.
PURGE AFTER PRESSURE TEST IN ACCORDANCE WITH CAN/CGA B149.1
HANGERS ROD.
610 FRAME & COVER
SECURED IN
CONCRETE
HEAVY DUTY CLEVIS HANGER
METAL FRAME &
COVER
F.F.EL:
249.15
EXTENSION COLLAR AS
REQUIRED
BUILDING OVERHANG
SUPPORT & LOCK NUTS
TANK TOP VENTS TO BE
CONNECTED TO
VENTING SYSTEM
300
UNION
FLOW CONTROL VALVE
100 INLET
UNION
BACK WATER VALVE
100 OUTLET
FIBERGLASS INSULATION
MIN. 50mm THICK
ADJACENT BUILDING
FLASHING
50mm CLEARANCE
THIMBLE
200
APPROVED VENT CAP
711
16GA. GALV. SADDLE
HANGER ROD SIZES
UP TO 50mm
64mm - 75mm
100mm - 125mm
FLUE VENT
1830 MIN.
813mm (W) x 1575mm (L)
x 711mm (H)
305 MIN.
250mm
INSULATION AS SPECIFIED
PIPE SIZE
PROCEPTOR
400
MIN.
PITCH FLUE PIPE DOWN TOWARD
OUTLET 1/4" PER FOOT OF RUN TO
ALLOW FOR CONDENSATE DRAINAGE
MIN. 6" PEA GRAVEL BED
(OR APPROVED BACKFILL
COMPACTED TO 98% SPD)
150mm - 300mm
1575
HANGER ROD
DIAMETER
10mm
13mm
16mm
22mm
2032
HANGER SPACING
PIPE
SIZE
25mm 30mm 40mm 50mm 65mm 75mm 100mm 125mm 150mm 200mm 250mm 300mm
MAXIMUM
2100
SPACING
2400
2700
3000
3300
3600
4200
4800
5100
5700
6600
CAST-IN-PLACE ANTI-BUOYANCY
SLAB FOR HIGH WATER TABLE
CONDITIONS. 3000PSI CONCRETE
READY MIX. POUR AROUND BASE OF
UNIT (16 CU. FT. MINIMUM - BASED
ON CONCRETE DENSITY OF 130
LBS/CU. FT.)
NOTES:
1. PEA GRAVEL TO 3FT HORIZONTALLY AROUND TANK (OR
APPROVED EQUIVALENT COMPACTED TO 98% SPD).
2. METAL FRAME AND COVER TO BE RATED FOR VEHICLE TRAFFIC
LOADING CONDITIONS.
6900
FLOOR SLAB
SEALANT
BACKER ROD
& SEALANT
DUCT OR PIPE
STRAINER BODY
REMOVABLE
STAINLESS STEEL STRAINER
13 RIGID FIBREGLASS
INSULATION
FINISHED FLOOR LINE
SLOPE
200 MIN.
(TYPICAL)
CLEANOUT COVER FRAME
FINISHED FLOOR LINE
BRASS SCREW PLUG
SLOPE
SHEET METAL SLEEVE
(SCHEDULE 10 STEEL)
WALL (TYPE VARIES - FOR
CAVITY WALL USE SPLIT
SLEEVE)
SEALANT. CONNECT TO
STUD WITH "L" BRACKET
IF NECESSARY (BOTH
SIDES)
C.I. CONNECTOR
SUITE DRAIN &
P-TRAP SIZE
FERRULE
DUCT
(LONG SWEEP)
PVC
P-TRAP
SLEEVE
TO MAIN LINE (SIZE
INDICATED IN PLAN)
CLEANING EYE
GASKET BY MECH. CONTRACTOR
MECHANICAL EQUIPMENT
TOP OF WOOD BLOCKING TO BE
LEVEL. USE UNTREATED WOOD
SOLID ROD TIE BAR
TO CONNECT STRAIGHT
PIPE TO ELBOW ONLY.
CONNECTING FROM STRAIGHT
PIPE TO STRAIGHT PIPE IS NOT
ACCEPTABLE.
PRE-FIN. METAL FLASHING
EXISTING GOOSE NECK
EXHAUST DUCT.
BIRDSCREEN AND
BURGLAR BARS
FILL VOID IN DUCT TO ROOF LINE
WITH MINERAL WOOL INSULATION
SOLID ROD
TIE BAR
(TYPICAL)
TYPICAL ROOF CONSTRUCTION
254mm
BUILD PARTITION
AROUND AND CAULK
WATER-PROOFING
(FOR TOILETS)
ATTACH BASE ELBOW TO ANCHOR TO
ADJACENT STRUCTURE
BRACING AT 90 DEG. ELBOW
STEEL DECK
ROOF
RISER CLAMP
(TYPICAL)
VAPOUR BARRIER
BARS AND STEEL PLATE FRAME
TO BE SUPPLIED BY
MISCELLANEOUS METAL
CONTRACTOR AND INSTALLED
BY MECH. CONTRACTOR
PRIMED 3mm THICK BENT STEEL PLATE WELDED
TO STEEL DECK. CHECK EQUIPMENT SPECS.
BRACING AT 45 DEG. ELBOW
CLEANOUT
PLUG
ROOF OPENING SUPPORT - SEE
STRUCTURAL DRAWINGS
BRACING AT CLEANOUT
JOINT
COUPLING
(TYPICAL)
BRACING AT LINE JOINT
CL
INSTALL ROOF DRAIN AS
PER MANUFACTURER'S
RECOMMENDATIONS AND
ARCA STANDARDS
STAINLESS STEEL GRAVEL STOP,
TIE TO DOME WITH PLASTIC TIE.
ANGLE AT JOIST
PANEL POINT
SEAL ROOF MEMBRANE
TO DRAIN FLANGE ALL
AROUND OPENING
ROOF MEMBRANE
HANGER ROD
GAS LINE
VIBRATION
ISOLATORS (4)
CONCENTRIC AIR VENT
SHUT OFF
GAS COCK
ROOF DECK
ROOF INSULATION TAPERED
TO DRAIN (600 DIAMETER)
UNDER DECK
CLAMP
DIRT POCKET
INSULATE PIPE AND
DRAIN PAN
GASKETS
UNION
RIGID
CONDUIT
SENSOR OR THERMOSTAT PER SCHEDULE.
LOCKING METAL GUARD OVER THERMOSTAT.
NOTE:
SUPPORT UNIT AS INSTRUCTED BY MANUFACTURER,
ALLOW FOR CONCRETE DECK, STEEL BEAM AND JOIST.
INSTALL AT LOCATION
INDICATED ON THE PLAN
WATERTIGHT NEOPRENE GASKET
NOTES:
NOTES:
CURBS AND FANS SHALL BE
FROM SAME MANUFACTURER.
ALUMINUM VENT CONE URETHANE FOAM
INSULATION VENT PIPE EXTENDER
DETAIL FOR REFERENCE
ONLY. SPECIFIED UNIT
MAY HAVE DIFFERENT DUCT
ARRANGEMENT. VERIFY
WITH UNIT SHOP
DRAWINGS.
SPUN ALUMINUM
HOUSING
VIBRATION
ELIMINATORS
MINIMUM 200mm HIGH FLASHING AND
COUNTERFLASHING
GAS SUPPLY
FUSED DISCONNECT
SWITCH SUPPLIED BY
DIV. 16
ALUMINUM BIRDSCREEN
SECURE FAN TO CURB
W/ S.M. SCREWS 300
OC ALL AROUND
SPUN ALUMINUM
COMPONENTS
FOAM RUBBER GASKET
TO UNDERSIDE OF FAN
CURB CAP
ROOF STRUCTURE
BACK DRAFT DAMPER
OR MOTORIZED DAMPER
DUCT EXTENSION WITH
WIRE MESH SCREEN
COVERING OPENING
25mm PIPE
INSULATION.
MINIMUM 5' FROM
ROOF
SUPPLY
AIR
DUCT
RETURN
AIR
DUCT
ROOF CURB
P
TO POWER SUPPLY
CONTROL WIRING TO
INDOOR THERMOSTAT
CIRCULATING
PUMP
BV
TO SYSTEM (SEE
DRAWINGS FOR
CONTINUATION)
CONDENSATE
TRAP AND DRAIN
DHWR
DHW
SLIP-FIT
CLEAN-OUT PLUG
DCW
T
3
REMOTE
READOUT
AHU
SLIP-FIT CLEAN-OUT PLUG
WITH 6 mm ~ VENT HOLE
1
WATTS, MODEL: 50-007-QT. UPON
INSTALLATION IT SHALL BE REGISTERED
WITH LOCAL UTILITY COMPANY.
NC
2
NO
NO
EXP-1
REFERENCE NOTES:
3
M
FLOOR
DCW LINE.
MUNICIPALITY STANDARDS C/W REMOTE
READ-OUT.
T&P RV
50mm
MIN.
BFP
DIELECTRIC UNION (TYP.)
PROVIDE NEW DOMESTIC HOT
WATER HEATER C/W,
THERMOMETER, RELATED
ACCESSORIES AND PIPING. REFER
TO EQUIPMENT SCHEDULE FOR
MORE INFO.
DRAIN LINE - SEE
PLANS FOR SIZE.
PROVIDE NEW 100MM CONCRETE
HOUSEKEEPING PAD. REFER TO
ARCHITECTURAL DRAWINGS FOR
MORE INFO.
HWT
NEW THERMAL EXPANSION TANK
(EXP-1) TO BE INSTALLED ON
DOMESTIC COLD WATER PIPING
SERVING DOMESTIC HOT WATER
TANKS
DIELECTRIC
UNION
(TYP.)
FF
2
1
TRAP EQUAL TO
AHU EXTERNAL
STATIC PRESSURE
ROOF TOP UNIT SCHEDULE
MANUFACTURER
BASE UNIT NOMINAL
& MODEL
WEIGHT CAPACITY
( OR APPROVED
(kg)
(TONS)
EQUAL)
TAG
RTU-1
(15-TONS)
-
DOMESTIC
WATTS
EXP-1
HOT
WATER
MODEL
DRY
TANK
QTY WEIGHT VOLUME
(kg)
(L)
DETA 5
10
1
103
66
420
-
RTU-5
(3-TONS)
MANUF.
498
-
RTU-4
(7.5 TONS)
SYSTEM
INPUT
(kW)
15
626
-
RTU-3
(10-TONS)
TAG
HEATING
OUTPUT
(kW)
82
NET TOTAL
(kW)
MINIMUM
OUTDOOR AIR
FLOW
(L/S)
SUPPLY FAN
COOLING
NET SENSIBLE
(kW)
54.5
39.75
FLOW
(L/S)
E.S.P.
(PA)
2832
FAN MOTOR
(hp)
250
ELECTRICAL
REMARKS
FLA
(A)
-
3.6
MCA
(A)
MOCP
(A)
33.0
-
40
7.5
498
-
10
229
3
53
66
34
54
43
54
27
35.6
26.93
27.6
21.04
35.6
26.93
11.26
8.73
1888
250
1416
250
1888
250
566
250
-
3.6
3.6
-
-
-
3.6
-
-
3.6
20.0
-
25
13.0
15
18.0
20
7.0
-
15
BP-1
BP-2
BP-3
BP-4
BP-5
BP-6
BP-7
BP-8
EH PRICE
EH PRICE
EH PRICE
EH PRICE
EH PRICE
EH PRICE
EH PRICE
EH PRICE
MODEL
7.5
53
43
27.6
21.04
1416
250
3.6
-
-
13.0
15
575/3/60
RTU-7
(7.5 TONS)
-
420
7.5
53
43
27.6
21.04
1416
250
3.6
-
-
13.0
15
575/3/60
LGB - 6
--
--
170
AS SHOWN ON DRAWING
LGB - 6
--
205
AS SHOWN ON DRAWING
LGB - 6
--
213
--
170
AS SHOWN ON DRAWING
--
86
NOTES
BASIS OF DESIGN
- C/W ELECTRONIC
MODULATING CONTROLS,
TRANSFORMERS,
THERMOSTATS AND ALL
ASSOCIATED CONTROL WIRE.
- C/W ELECTRONIC
MODULATING CONTROLS,
TRANSFORMERS,
THERMOSTATS AND ALL
ASSOCIATED CONTROL WIRE.
- C/W ELECTRONIC
MODULATING CONTROLS,
TRANSFORMERS,
THERMOSTATS AND ALL
ASSOCIATED CONTROL WIRE.
- C/W ELECTRONIC
MODULATING CONTROLS,
TRANSFORMERS,
THERMOSTATS AND ALL
ASSOCIATED CONTROL WIRE.
- C/W ELECTRONIC
MODULATING CONTROLS,
TRANSFORMERS,
THERMOSTATS AND ALL
ASSOCIATED CONTROL WIRE.
- C/W ELECTRONIC
MODULATING CONTROLS,
TRANSFORMERS,
THERMOSTATS AND ALL
ASSOCIATED CONTROL WIRE.
- C/W ELECTRONIC
MODULATING CONTROLS,
TRANSFORMERS,
THERMOSTATS AND ALL
ASSOCIATED CONTROL WIRE.
- C/W ELECTRONIC
MODULATING CONTROLS,
TRANSFORMERS,
THERMOSTATS AND ALL
ASSOCIATED CONTROL WIRE.
--
171
AS SHOWN ON DRAWING
EXHAUST FAN SCHEDULE
AIR FLOW MIN.
(L/S)
95
AS SHOWN ON DRAWING
LGB - 8
--
OIL INTERCEPTOR
TAG
LOCATION
MANUFACTURER
MODEL
FLOW
RATE
(L/S)
INT-1
SERVICE
DEPARTMENT
123
PROCEPTOR BY
GREENTURTLE
OMC-150
-
INLET /
OUTLET
(mm)
LXWXH
(mm)
100
1575 x 813 x 915
TAG
LOCATION
EF-1
WEIGHT
(kg)
FLOW
(L/s)
STATIC
PRESSURE
(Pa)
* C/W EPOXY COATED NON-SKID BODY
COVER, FABRICATED STEEL BODY AND
NO HUB CONNECTIONS
MANUFACTURER
MODEL
OVERALL
WIDTH
(mm)
NOZZLE
WIDTH
(mm)
MOUNTING
WIDTH
(mm)
OHAC-1
VESTIBULE
100
POWERED AIRE
CED 1-60E
1549.4
1524
1526
WASHROOM - WC 1
107
GREENHECK
SP-A110
8
42
62.3
950
51 WATTS
CEILING MOUNTED FAN C/W BACKDRAFT DAMPER, HANGING HARDWARE
C/W WALL SWITCH
EF-2
WASHROOM - WC 2
108
GREENHECK
SP-A110
8
42
62.3
950
51 WATTS
CEILING MOUNTED FAN C/W BACKDRAFT DAMPER, HANGING HARDWARE
C/W WALL SWITCH
EF-3
TECH. WC 120
GREENHECK
SP-A110
8
42
62.3
950
51 WATTS
CEILING MOUNTED FAN C/W BACKDRAFT DAMPER, HANGING HARDWARE
C/W WALL SWITCH
EF-4
WC - 203
GREENHECK
SP-A110
8
42
62.3
950
51 WATTS
CEILING MOUNTED FAN C/W BACKDRAFT DAMPER, HANGING HARDWARE
C/W H-O-A STARTER AND 24/7 TIMER
EF-5
WC - 204
GREENHECK
SP-A110
8
42
62.3
950
51 WATTS
CEILING MOUNTED FAN C/W BACKDRAFT DAMPER, HANGING HARDWARE
C/W WALL SWITCH
EF-6
ON ROOF ABOVE
SERVICE PART
WASHROOM
GREENHECK
GB-091
28
260
62.3
1000
187
ROOF MOUNTED CENTRIFUGAL EXHAUST FAN, GRAVITY BACK DRAFT DAMPER, ROOF
CURB, AND ALUMINUM BIRD SCREEN
C/W H-O-A STARTER AND REVERSE ACTING THERMOSTAT
EF-7
ON ROOF
GREENHECK
USGF-180
86.2
2217
31
1275
1-1/2
ROOF MOUNTED CENTRIFUGAL EXHAUST FAN, GRAVITY BACK DRAFT DAMPER, ROOF
CURB, AND ALUMINUM BIRD SCREEN
C/W H-O-A STARTER AND REVERSE ACTING THERMOSTAT
EF-8
ON ROOF
GREENHECK
USGF-180
86.2
2217
31
1275
1-1/2
ROOF MOUNTED CENTRIFUGAL EXHAUST FAN, GRAVITY BACK DRAFT DAMPER, ROOF
CURB, AND ALUMINUM BIRD SCREEN
C/W H-O-A STARTER AND REVERSE ACTING THERMOSTAT
EF-9
ON LOW ROOF
GREENHECK
USGF-140
56.7
994
31
1210
1/3
ROOF MOUNTED CENTRIFUGAL EXHAUST FAN, GRAVITY BACK DRAFT DAMPER, ROOF
CURB, AND ALUMINUM BIRD SCREEN
C/W H-O-A STARTER AND REVERSE ACTING THERMOSTAT
EF-10
ON ROOF
BY OTHERS
EF-11
ELECTRICAL ROOM 122
GREENHECK
-
-
142
31
-
-
CEILING MOUNTED FAN C/W BACKDRAFT DAMPER, HANGING HARDWARE
C/W H-O-A STARTER AND 24/7 TIMER
EF-12
MECHANICAL ROOM 123
GREENHECK
-
-
142
31
-
-
CEILING MOUNTED FAN C/W BACKDRAFT DAMPER, HANGING HARDWARE
C/W H-O-A STARTER AND 24/7 TIMER
EF-13
IT 205
BROAN
S50U
4.5
23.6
25
820
51 WATTS
CEILING MOUNTED FAN C/W BACKDRAFT DAMPER, HANGING HARDWARE
C/W WALL SWITCH
INSTALLATION SPECIFICATIONS DONE BY OTHERS.
CONTRACTOR TO INSTALL UNITS AS PER MANUFACTURER'S INSTRUCTION.
ALL ROOF MOUNTED FANS SHALL BE INSTALLED ON ROOF CURB, SUPPLIED WITH FAN; SEE DETAIL 14/M.1.3.
NOTES
* PROVIDE UNIT MOUNTED THERMOSTAT AND
UNIT MOUNTED DISCONNECT SWITCH.
TAG
LOCATION
MANUFACTURER
MODEL
QTY
DRY WEIGHT
(kg)
CAPACITY
(Liters)
RECOVERY
RATE
(L/S)
TEMPERATURE
RISE
HWT-1
MECHANICAL ROOM
123
AO SMITH
BTH-120(A) Mxi
1
220
227
0.15
56
UH-1
MANUFACTURER
LENNOX
MODEL
LF24-100A
QTY
3
64
INPUT
29.3
23.6
3657.6
VOLTAGE
115/1/60
FLUE
DIAMETER
(mm)
ELECTRICAL
(V/Hz)
REMARKS
FLOOR MOUNTED ON PAD
C/W VENT KIT AND CONDENSATE KIT
120/60
MAKE UP AIR UNIT SCHEDULE
UNIT HEATER SCHEDULE
MIN
MOUNTING
HEIGHT
OUTPUT
(mm)
REMARKS
HOT WATER HEATER SCHEDULE
LOCATION
GAS HEATING
CAPACITY (kW)
MOTOR
MODEL
NOTES
TAG
WEIGHT
(kg)
FAN
RPM
MANUFACTURER
OVERHEAD AIR CURTAIN DOOR
TAG
REFRIGERANT: 410A
UNIT TO BE COMPLETE WITH ROOF CURB (14"), POWER EXHAUST, HAIL GUARD, CONDENSATE TRAP, CONTROL INTERFACE. S.S.
HEAT EXCHANGER.
COMPLETE WITH CONTROLLER OF SAME MANUFACTURER OF UNIT: 'RTAM MODULE FOR VAV SYSTEMS'.
UNIT SHALL BE COMPLIANT WITH ASHREA 90.1-2010
BALANCE OUTSIDE AIR TO 600 CFM (283 L/S)
GAS BURNER SHALL BE FULLY MODULATED. S.S. HEAT EXCHANGER.
REFRIGERANT: 410A
UNIT TO BE COMPLETE WITH ROOF CURB (14"), POWER EXHAUST, HAIL GUARD, CONDENSATE TRAP, CONTROL INTERFACE. S.S.
HEAT EXCHANGER.
COMPLETE WITH CONTROLLER OF SAME MANUFACTURER OF UNIT: 'RTAM MODULE FOR VAV SYSTEMS'.
UNIT SHALL BE COMPLIANT WITH ASHREA 90.1-2010
BALANCE OUTSIDE AIR TO 600 CFM (283 L/S)
GAS BURNER SHALL BE FULLY MODULATED. S.S. HEAT EXCHANGER.
PROVIDE ALL SENSORS AND ACCESSORIES FOR A FULLY FUNCTIONAL CONTROL SYSTEM.
CONTRACTOR TO INCLUDE TWO (2) DAYS FOR UNIT MANUFACTURER SETUP AND START UP OF SYSTEM AND CONTROLS.
CONTRACTOR TO INSTALL UNITS AS PER MANUFACTURER'S INSTRUCTION.
ALL CONTROL CONNECTIONS AND SETUP SHALL BE AS PER MANUFACTURER'S INSTRUCTION.
170
AS SHOWN ON DRAWING
LGB - 8
575/3/60
REFRIGERANT: 410A
UNIT TO BE COMPLETE WITH ROOF CURB (14"), HUMIDITY CONTROL SYSTEM, HAIL GUARD, CONDENSATE TRAP, CONTROL
INTERFACE. S.S. HEAT EXCHANGER.
COMPLETE WITH CONTROLLER OF SAME MANUFACTURER OF UNIT.
TO BE COMPLETE WITH MICROMETL DIFFUSER: CNKT-543C-**FX; DIFFUSER SHALL BE HEAVY GAUGE, SUITABLE FOR GYM USE.
UNIT SHALL BE COMPLIANT WITH ASHREA 90.1-2010
BALANCE OUTSIDE AIR TO 300 CFM (142 L/S)
GAS BURNER SHALL BE FULLY MODULATED. S.S. HEAT EXCHANGER.
420
AIR FLOW MAX.
(L/S)
AS SHOWN ON DRAWING
LGB - 6
575/3/60
REFRIGERANT: 410A
UNIT TO BE COMPLETE WITH ROOF CURB (14"), POWER EXHAUST, HAIL GUARD, CONDENSATE TRAP, CONTROL INTERFACE. S.S.
HEAT EXCHANGER.
COMPLETE WITH CONTROLLER OF SAME MANUFACTURER OF UNIT: 'RTAM MODULE FOR VAV SYSTEMS'.
UNIT SHALL BE COMPLIANT WITH ASHREA 90.1-2010
BALANCE OUTSIDE AIR TO 1000 CFM (472 L/S)
GAS BURNER SHALL BE FULLY MODULATED. S.S. HEAT EXCHANGER.
13.3
AS SHOWN ON DRAWING
LGB - 6
575/3/60
REFRIGERANT: 410A
UNIT TO BE COMPLETE WITH ROOF CURB (14"), POWER EXHAUST, HAIL GUARD, CONDENSATE TRAP, CONTROL INTERFACE. S.S.
HEAT EXCHANGER.
COMPLETE WITH CONTROLLER OF SAME MANUFACTURER OF UNIT: 'RTAM MODULE FOR VAV SYSTEMS'.
UNIT SHALL BE COMPLIANT WITH ASHREA 90.1-2010
BALANCE OUTSIDE AIR TO 600 CFM (283 L/S)
GAS BURNER SHALL BE FULLY MODULATED. S.S. HEAT EXCHANGER.
REMARKS
LOCATION
LGB - 6
REFRIGERANT: 410A
UNIT TO BE COMPLETE WITH ROOF CURB (14"), POWER EXHAUST, HAIL GUARD, CONDENSATE TRAP, CONTROL INTERFACE.
COMPLETE WITH CONTROLLER OF SAME MANUFACTURER OF UNIT: 'RTAM MODULE FOR VAV SYSTEMS'.
UNIT SHALL BE COMPLIANT WITH ASHREA 90.1-2010
BALANCE OUTSIDE AIR TO 250 CFM (118 L/S)
GAS BURNER SHALL BE FULLY MODULATED. S.S. HEAT EXCHANGER.
575/3/60
-
BYPASS BOX - SCHEDULE
MANUFACTURER
REFRIGERANT: 410A
UNIT TO BE COMPLETE WITH ROOF CURB (14"), POWER EXHAUST, HAIL GUARD, CONDENSATE TRAP, CONTROL INTERFACE.
COMPLETE WITH CONTROLLER OF SAME MANUFACTURER OF UNIT: 'RTAM MODULE FOR VAV SYSTEMS'.
UNIT SHALL BE COMPLIANT WITH ASHREA 90.1-2010
BALANCE OUTSIDE AIR TO 300 CFM (142 L/S)
GAS BURNER SHALL BE FULLY MODULATED. S.S. HEAT EXCHANGER.
575/3/60
RTU-6
(7.5 TONS)
INSTALL PER MANUFACTURER RECOMMENDATION.
CHARGE TANK TO THE DOMESTIC WATER PRESSURE PRIOR TO CONNECTION;
100 PSI RELIEF VALVE ON WATER HEATER
TAG
VOLTAGE
(V/ /HZ)
10
RTU-2
(10-TONS)
EXPANSION TANK SCHEDULE
CAPACITY
AIR
FLOW
(L/S)
UNIT DIMENSIONS
(LxWxH)
(mm)
897
996 x 513 x 818
SUPPLY FAN
REMARKS
GAS FIRED UNIT HEATER C/W VERTICAL FLUE VENTING KIT
UNIT TO BE C/W HANGING BRACKETS KIT & THERMOSTAT.
GAS HEATING
TAG
LOCATION
MANUFACTURER
MODEL
AIR
(L/S)
ESP
"WC
(PA)
TSP
"WC
(PA)
MIN.
O/A
(l/s)
FUEL
TYPE
(kW)
OUTPUT
MUA-1
ON ROOF
REZNOR
RPBL-400
1888
125
500
-
NG
95.2
ELECT. SERVICE
MOTOR
(HP)
WEIGHT
(kg)
V/PH/Hz
1
552
575/3/60
NOTES
1.
PLUMBING FIXTURE SCHEDULE
OPERATION PARAMETERS
1.1.
PROVIDING CONTINUOUS MONITORING IN AMBIENT AIR AND TWO FACTORY-SET ALARM LEVELS AND
OUTPUTS.
PIPE SIZES (mm)
TAG
FIRST ALARM
(TWA)
SECOND ALARM
(STEL)
SENSOR LOCATION
CARBON
MONOXIDE (CO)
25 PPM
100 PPM
800 - 1200MM ABOVE THE FLOOR
AS PER OBC
NITROGEN
DIOXIDE (NO )
0.72 PPM
2 PPM
300MM BELOW THE CEILING
AS PER OBC
--
AMERICAN STANDARD CADET PRESSURE-ASSISTED ELONGATED #2462.016.020 LOW CONSUMPTION TOILET, 381 MM HIGH, WHITE VITREOUS CHINA WITH EVERCLEAN ANTIMICROBIAL SURFACE
WHICH INHIBITS THE GROWTH OF STAIN AND ODOR CAUSING BACTERIA MOLD AND MILDEW, FLOOR MOUNTED, SIPHON JET FLUSH ACTION, 6 L (1.6 US GAL) PER FLUSH, RAISED SANITARY BAR, 305 MM X 254
MM (12" X 10") WATER SURFACE AREA, TWO PIECE, 'SPEED CONNECT' TANK ASSEMBLY, UNBOLTED TANK COVER, 305 MM (12") ROUGH-IN, ELONGATED BOWL, 54 MM (2-1/8") FULLY GLAZED INTERNAL
TRAPWAY, FLOOR OUTLET, BOLT CAPS. CENTOCO #500STSCC.001 TOILET SEAT, HEAVY DUTY, FOR ELONGATED BOWL, OPEN FRONT, WHITE SOLID PLASTIC, LESS COVER, REINFORCED STAINLESS STEEL
WC (203), WC (204), TECH. WM'S CHECK HINGES, METAL FLAT WASHERS STAINLESS STEEL POSTS AND NUTS. MCGUIRE #LFH166LKN3, TOILET SUPPLY, CHROME PLATED POLISHED BRASS, HEAVY DUTY ANGLE STOPS, 13 MM (1/2") I.P.S.
WC (134),
INLET X 76 MM (3") LONG RIGID HORIZONTAL NIPPLES, V.P. LOOSE KEYS, ESCUTCHEON AND FLEXIBLE COPPER RISER. PROVIDE FLOOR FLANGE, (SAME MATERIAL AS THE CONNECTING PIPE DRAIN), WITH ALL
TECH. MEN'S WC (131)
BRASS BOLTS AND WITH RUBBER GASKET.
--
WC-1
GROUND FLOOR
TECH. WC 121, WC1 (107),
WC2 (108)
LOW-LEVEL ALARM
SIGNAL IS SENT FROM RELAY OUT TO FAN STARTER AND DAMPER CONTROL. LOW ALARM INDICATORS
LIGHT FOR POINT IN ALARM UNTIL HAZARDOUS GAS CONCENTRATION LEVELS ARE REDUCED TO BELOW
SET POINT ALARM LEVELS
WALL HUNG BASIN
SINGLE LEVER FAUCET
HIGH LEVEL ALARM
L-1
TECH. MEN'S WC (131),
TECH. WC 121,
WC1 (107), WC2 (108),
DIESEL ENGINE EMISSIONS ( NITROGEN DIOXIDE )
LOW LEVEL ALARM
IF THE NO2 REMOTE SENSOR DETECTS A .72 PPM CONCENTRATION OF GAS THE FAN STARTER SHOULD
BE ACTIVATED THROUGH THE SAME RELAY AS WELL AS ANY DAMPERS.
HIGH LEVEL ALARM
2.
L-2
GAS MONITORING TRANSMITTERS: HONEYWELL ANALYTICS E3SM-E3SCO & E3SM-E3NO2
2.1
2.2
THE TRANSMITTER WILL BE CAPABLE OF SENDING SIGNAL THROUGH A MODBUS OUTPUT OR AN
ONBOARD DPDT RELAYS (5A, 30 VDC OR 250 VAC (RESISTIVE LOAD)) WILL BE ACTIVATED AT
PROGRAMMABLE SET POINTS. AN LCD DISPLAY WILL PROVIDE LOCAL GAS CONCENTRATION READINGS.
2.4
U-1
WALL HUNG URINAL
FOR FLUSHOMETER
EXPOSED
MANUAL
TRANSMITTER WILL BE CAPABLE OF OPERATING WITHIN RELATIVE HUMIDITY RANGES OF 5-95%
ELECTROCHEMICAL SENSOR FOR CARBON MONOXIDE AND NITROGEN DIOXIDE. TO BE CALIBRATED
SEMI-ANNUALLY AS PER MANUFACTURER'S INSTRUCTIONS.
SENSOR SHALL HAVE A CONTINUOUS SELF-TEST FOR SENSOR CELL LIFE VALIDATION OF OPERATION
SIMILAR TO HONEYWELL REFLEX TECHNOLOGY.
2.5
LED INDICATOR LIGHTS FOR POWER, ALARM 1 AND ALARM 2 LEVELS. FOR LOCAL ACTIVATION OF
AUDIBLE ALARMS, THE TRANSMITTER SHALL HAVE AN ON-BOARD DEVICE ABLE TO GENERATE AN
AUDIBLE OUTPUT OF 85 DBA @ 10 FT (3M). INDOOR REMOTE MOUNTED STROBE TO BE PROVIDED WITH
WHITE CANDELA.
2.6
TRANSMITTER IN CAR WASH BAY TO INCLUDE AN ECLAB WATERPROOF ENCLOSURE.
3.
CONTROL PANEL: VA301C
3.1
3.2
S-1
3.3
THE CONTROLLER MUST INCLUDE A SELF-TEST FUNCTION THAT ALLOWS FOR THE
ACTIVATION/DEACTIVATION OF ALL THE PROGRAMMED OUTPUTS BY SIMULATING A CONTINUOUS 5%
INCREASE/DECREASE VALUE UNTIL THE MAXIMUM/MINIMUM VALUE IS REACHED.
3.4
THE CONTROLLER MUST INCLUDE A REAL-TIME CLOCK THAT ENABLES OPERATION OF THE OUTPUTS
FOR A SPECIFIC TIMEFRAME.
3.5
THE CONTROLLER MUST ALSO INCLUDE AN ENERGY SAVING FEATURE THAT ALLOWS FOR OUTPUT
OPERATION ON ALARMS SET AT THE MAX, MIN OR AVERAGE VALUE OF A SPECIFIC GROUP OF
TRANSMITTERS. THIS FEATURE MUST ALSO ALLOW FOR THE ACTIVATION OF OUTPUTS UPON A CERTAIN
COUNTERTOP MOUNT SINK
SINGLE LEVER FAUCET
TOOL ROOM (120)
S-2
COUNTERTOP MOUNT SINK
SINGLE LEVER FAUCET
LUNCH ROOM (130)
THE CONTROL PANEL MUST BE CAPABLE OF COMMUNICATING DIGITALLY WITH THE NETWORKED
TRANSMITTERS AND RELAY MODULES THROUGH THREE RS-485 MODBUS COMMUNICATION BUSES.
EACH COMMUNICATION BUS MUST BE CAPABLE OF ACCEPTING A COMBINATION OF UP TO 32
ADDRESSABLE TRANSMITTERS, RELAY MODULES, OR ANNUNCIATOR PANELS AT A MAXIMUM DISTANCE
OF 2,000 FEET. THE POWER SUPPLY SHALL BE OF EITHER 24 VAC OR 24 VDC
THE CONTROLLER WILL MANAGE FOUR INTERNAL DPDT RELAYS AT FULLY PROGRAMMABLE ALARM
LEVELS (AND WITHIN PROGRAMMABLE TIME DELAYS) AND BE CAPABLE OF ACTIVATING MULTIPLE
RELAY MODULES OF EIGHT RELAYS EACH. THE RELAY RATING WILL BE NO LOWER THAN 5 A, 30 VDC
OR 250 VAC (RESISTIVE LOAD).
VENT
SH-1
SHOWER FLOOR SHOWER VALVE
AND HEAD
TECH MEN'S WC (131)
MS-1
AMERICAN STANDARD MURRO WITH EVERCLEAN #0954.004EC/0059.020EC BASIN, 540 MM X 520 MM X (21-1/4" X 20-1/2" X 6-1/2") DEEP, VITREOUS CHINA, FOR CARRIER WITH CONCEALED ARMS,
REAR OVERFLOW, RECESSED SELF-DRAINING FAUCET LEDGE, SEMI-PEDESTAL P-TRAP COVER. . CHICAGO FAUCETS #420-ABCP SINGLE LEVER FAUCET, CHROME PLATED, 4" (102MM) CENTERSET, LEAD
FREE CAST BRASS BODY, CERAMIC 1/4 TURN CARTRIDGE, 5.7 LPM (1.5 GPM) NON-AERATING LAMINAR OUTLET, 131 MM (5-3/16") PROJECTION REACH, LEVER HANDLE, VOLUME CONTROL, ADJUSTABLE HOT
LIMIT STOP. LAWLER #TMM-1070, POINT OF USE MECHANICAL WATER MIXING VALVE, BRONZE BODY, TEMPERATURE ADJUSTING DIAL, 10 MM (3/8") INLETS AND OUTLET COMPRESSION FITTINGS, HIGH
TEMPERATURE THERMOSTATIC LIMIT STOP (AUTOMATIC SHUTS DOWN FLOW OF WATER WHEN TEMPERATURE REACHES 48 DEG.C (118 DEG.F) WITH AUTOMATIC RESET, SHUT-OFF WITH AUTOMATIC RESET
WHEN TEMPERATURE EXCEEDS 120F (48.8C), INTEGRAL CHECKS, OFFER TEMPERATURE RANGE FROM FULL COLD THROUGH 46
(114.8
PROVIDE TEE, ADAPTORS AND FLEX. COPPER TUBING TO SUIT
INSTALLATION. PROVIDE TEMPERED WATER TO HOT SIDE OF FAUCET. MCGUIRE #155AC OPEN GRID DRAIN, CHROME PLATED CAST BRASS ONE PIECE TOP, 17 GA. (1.5MM) TUBULAR 32 MM (1-1/4")
TAILPIECE. MCGUIRE #LFH170BVRB, FAUCET SUPPLIES, CHROME PLATED POLISHED BRASS, COMMERCIAL DUTY 1/4 TURN BALL VALVE ANGLE STOPS, 13 MM (1/2") I.D. INLET X 127 MM (5") HORIZONTAL
EXTENSION TUBES, COMBINATION V.P. LOOSE KEY HANDLE, ESCUTCHEON AND STAINLESS STEEL BRAIDED FLEXIBLE RISER. MCGUIRE #8872C P-TRAP, HEAVY CAST BRASS ADJUSTABLE BODY, WITH SLIP
NUT, 32 MM (1-1/4") SIZE, SHALLOW WALL FLANGE AND SEAMLESS TUBULAR WALL BEND. WATTS #WCA-411-CA-481, BASIN CARRIER, CONCEALED ARMS, WALL FLANGES TO ATTACH TO BACKING PLATE
SECURED IN WALL WITH LOCKING DEVICE AND LEVELLING SCREWS, HEAVY GAUGE STEEL UPRIGHTS WITH INTEGRAL WELDED FEET. FOR ONE UNIT: 102 MM (4") FOR TWO TO SIX UNITS IN A ROW: 152 MM (6")
FINISHED METAL STUD WALL TO BACK OF PIPE SPACE.
AMERICAN STANDARD LUCERNE #0355.012 BASIN, 521 MM X 464 MM X 308 MM (20-1/2" X 18-1/4" X 12-1/8") DEEP, VITREOUS CHINA, FOR CARRIER WITH CONCEALED ARMS, FRONT OVERFLOW,
SELF-DRAINING FAUCET LEDGE, CONTOURED BACK AND SIDE SPLASH SHIELD. CHICAGO FAUCETS #420-ABCP SINGLE LEVER FAUCET, CHROME PLATED, 4" (102MM) CENTERSET, LEAD FREE CAST BRASS
BODY, CERAMIC 1/4 TURN CARTRIDGE, 5.7 LPM (1.5 GPM) NON-AERATING LAMINAR OUTLET, 131 MM (5-3/16") PROJECTION REACH, LEVER HANDLE, VOLUME CONTROL, ADJUSTABLE HOT LIMIT STOP. LAWLER
WALL HUNG BASIN
#TMM-1070, POINT OF USE MECHANICAL WATER MIXING VALVE, BRONZE BODY, TEMPERATURE ADJUSTING DIAL, 10 MM (3/8") INLETS AND OUTLET COMPRESSION FITTINGS, HIGH TEMPERATURE
SINGLE LEVER FAUCET
THERMOSTATIC LIMIT STOP (AUTOMATIC SHUTS DOWN FLOW OF WATER WHEN TEMPERATURE REACHES 48 DEG.C (118 DEG.F) WITH AUTOMATIC RESET, SHUT-OFF WITH AUTOMATIC RESET WHEN
TEMPERATURE EXCEEDS 120F (48.8C), INTEGRAL CHECKS, OFFER TEMPERATURE RANGE FROM FULL COLD THROUGH 46
(114.8
PROVIDE TEE, ADAPTORS AND FLEX. COPPER TUBING TO SUIT
WC (203), WC (204), TECH. WM'S INSTALLATION. PROVIDE TEMPERED WATER TO HOT SIDE OF FAUCET. MCGUIRE #155AC OPEN GRID DRAIN, CHROME PLATED CAST BRASS ONE PIECE TOP, 17 GA. (1.5MM) TUBULAR 32 MM (1-1/4")
WC (134)
TAILPIECE. MCGUIRE #LFH165LKN3, FAUCET SUPPLIES, CHROME PLATED POLISHED BRASS, HEAVY DUTY ANGLE STOPS, 10 MM (3/8") I.P.S. INLET X 76 MM (3") LONG RIGID HORIZONTAL NIPPLES, V.P.
LOOSE KEYS, ESCUTCHEON AND FLEXIBLE COPPER RISER. MCGUIRE #8872C P-TRAP, HEAVY CAST BRASS ADJUSTABLE BODY, WITH SLIP NUT, 32 MM (1-1/4") SIZE, SHALLOW WALL FLANGE AND SEAMLESS
TUBULAR WALL BEND. WATTS #WCA-411, BASIN CARRIER, CONCEALED ARMS, WALL FLANGES TO ATTACH TO BACKING PLATE SECURED IN WALL WITH LOCKING DEVICE AND LEVELLING SCREWS, HEAVY
GAUGE STEEL UPRIGHTS WITH INTEGRAL WELDED FEET. FOR ONE UNIT: 102 MM (4") FOR TWO TO SIX UNITS IN A ROW: 152 MM (6") FINISHED METAL STUD WALL TO BACK OF PIPE SPACE.
TECH. MEN'S WC (131)
2.3
DRAIN
TOILET - FLOOR MOUNTED
VITREOUS CHINA
TANK TYPE
GASOLINE ENGINE EMISSIONS ( CARBON MONOXIDE )
IF HAZARDOUS NO2 GAS CONCENTRATIONS ARE NOT CLEARED AFTER 30 MINUTES OR NO2 GAS
CONCENTRATIONS CONTINUE TO INCREASE TO 2 PPM VENTILATION INTERNAL HORN IS TO SOUND AND
ALARM CONTACTS SHOULD CONTINUE TO OPERATE THE EXHAUST FANS UNTIL HAZARDOUS GAS
CONCENTRATION LEVELS ARE REDUCED TO BELOW SET POINT ALARM LEVELS
DHW
AMERICAN STANDARD CADET RIGHT HEIGHT PRESSURE-ASSISTED ELONGATED #2467.016.020 LOW CONSUMPTION TOILET, 419 MM HIGH, WHITE VITREOUS CHINA WITH EVERCLEAN
ANTIMICROBIAL SURFACE WHICH INHIBITS THE GROWTH OF STAIN AND ODOR CAUSING BACTERIA MOLD AND MILDEW, FLOOR MOUNTED, SIPHON JET FLUSH ACTION, 6 L (1.6 US GAL) PER FLUSH, RAISED
SANITARY BAR, 305 MM X 254 MM (12" X 10") WATER SURFACE AREA, TWO PIECE, 'SPEED CONNECT' TANK ASSEMBLY, UNBOLTED TANK COVER, 305 MM (12") ROUGH-IN, ELONGATED BOWL, 54 MM (2-1/8")
FULLY GLAZED INTERNAL TRAPWAY, FLOOR OUTLET, BOLT CAPS. PROVIDE BOLTED TANK COVER IF REQUIRED - TO MEET LOCAL CODES. PROVIDE TRIP LEVER ON OPEN SIDE OF TOILET (WIDE SIDE) IF
REQUIRED - TO MEET LOCAL CODES.CENTOCO #820STS.001 TOILET SEAT, HEAVY DUTY, FOR ELONGATED BOWL, OPEN FRONT, WHITE SOLID PLASTIC, WITH COVER, REINFORCED STAINLESS STEEL CHECK
HINGES, METAL FLAT WASHERS STAINLESS STEEL POSTS AND NUTS. MCGUIRE #LFH166N3, TOILET SUPPLY, CHROME PLATED POLISHED BRASS, HEAVY DUTY ANGLE STOPS, 13 MM (1/2") I.P.S. INLET X 76
MM (3") LONG RIGID HORIZONTAL NIPPLES, WHEEL HANDLES, ESCUTCHEON AND FLEXIBLE COPPER RISER. PROVIDE FLOOR FLANGE, (SAME MATERIAL AS THE CONNECTING PIPE DRAIN), WITH ALL BRASS
BOLTS AND WITH RUBBER GASKET.
TOILET - FLOOR MOUNTED
VITREOUS CHINA
TANK TYPE
WC-2
IF NOT CLEARED AFTER 30 MINUTES OR CARBON MONOXIDE (CO) GAS CONCENTRATION LEVELS
CONTINUE TO RISE THEN, WHILE VENTILATION CONTINUES TO OPERATE, THE INTERNAL HORN WILL BE
ENERGIZED.
SPECIFICATION
DCW
CO/NOX GAS DETECTION SYSTEM
GAS
FIXTURE
AMERICAN STANDARD WASHBROOK FLOWISE #6590.001 URINAL, VITREOUS CHINA, OPERATES IN THE RANGE OF 0.5 L TO 3.8 L (0.125 US GAL TO 1.0 US GAL) PER FLUSH, WALL HUNG, EXTENDED SIDES
FOR PRIVACY, WASHDOWN ACTION, FLUSHING RIM, 19 MM (3/4") DIA. TOP SPUD, ELONGATED RIM, INTEGRAL P-TRAP, OUTLET CONNECTION 51 MM (2"), 2 WALL HANGERS, #7301242-100 CHROME PLATED,
NON-METALLIC STRAINER. SLOAN ROYAL #186-0.5-CP, EXPOSED MANUAL FLUSHOMETER FOR TOP SPUD URINAL, CHROME PLATED, 1.9 L (0.5 US GAL) FACTORY SET FLOW, QUIET ACTION 'PERMEX'
DIAPHRAGM TYPE WITH DUAL FILTER BY-PASS, NON-HOLD OPEN FEATURE, A.D.A TRIPLE SEAL OSCILLATING HANDLE, V.P. SMOOTH DESIGN STOP CAP ON BACK-CHECK ANGLE STOP (SCREWDRIVER OPERATED),
FLUSH TUBE FOR 292 MM (11-1/2") ROUGH-IN, HIGH PRESSURE VACUUM BREAKER. WATTS #CA-321, URINAL CARRIER, MOUNTED ON CONCRETE FLOOR, EPOXY COATED WITH HEAVY GAUGE STEEL
UPRIGHTS WITH WELDED FEET SUPPORTS AND WITH TOP AND BOTTOM UNIVERSAL STEEL HANGER PLATES WITH PLATED HARDWARE, HEAVY GAUGE EPOXY COATED STEEL OFFSET UPRIGHTS. FOR ONE UNIT:
102 MM (4") FOR TWO TO SIX UNITS IN A ROW: 152 MM (6") FINISHED METAL STUD WALL TO BACK OF PIPE SPACE. WATTS #WUCO URINAL WALL ACCESS CLEANOUT, TWO PIECE EXPANDABLE PLUG WITH
102MM (4") DIAMETER STAINLESS STEEL ACCESS COVER, SECURED WITH VANDAL PROOF STAINLESS STEEL SCREW.
--
FRANKE COMMERCIAL #LBS6808-1/1 SINGLE BOWL COUNTERTOP MOUNT SINK, 1 HOLE, 521 MM (20-1/2") X 508 MM (20") X 203 MM (8") DEEP, COUNTER MOUNTED, BACKLEDGE, 18-10 TYPE 302 20 GA.
(0.9MM) STAINLESS STEEL, SELF-RIMMING, SATIN FINISH RIM AND BOWLS, MOUNTING KIT PROVIDED, FULLY UNDERCOATED TO REDUCE CONDENSATION AND RESONANCE, FACTORY APPLIED RIM SEAL, 3-1/2"
(89MM) CRUMB CUP WASTE ASSEMBLY WITH 1-1/2" (38 MM) TAILPIECE. CHICAGO FAUCETS #430-ABCP SINGLE LEVER FAUCET, CHROME PLATED, CENTER HOLE ONLY, LEAD FREE CAST BRASS BODY, 5.7
LPM (1.5 GPM) AERATOR OUTLET, LONG CAST SPOUT 229 MM (9") PROJECTION REACH, LEVER HANDLE, VOLUME CONTROL, ADJUSTABLE HOT LIMIT STOP. MCGUIRE #LFH165LKN3, FAUCET SUPPLIES,
CHROME PLATED POLISHED BRASS, HEAVY DUTY ANGLE STOPS, 10 MM (3/8") I.P.S. INLET X 76 MM (3") LONG RIGID HORIZONTAL NIPPLES, V.P. LOOSE KEYS, ESCUTCHEON AND FLEXIBLE COPPER RISER.
MCGUIRE #8912CB P-TRAP, HEAVY CAST BRASS ADJUSTABLE BODY, WITH SLIP NUT, 38 MM (1-1/2") SIZE, BOX FLANGE AND SEAMLESS TUBULAR WALL BEND.
FRANKE COMMERCIAL #LBS6808-1/1 SINGLE BOWL COUNTERTOP MOUNT SINK, 1 HOLE, 521 MM (20-1/2") X 508 MM (20") X 203 MM (8") DEEP, COUNTER MOUNTED, BACKLEDGE, 18-10 TYPE 302 20 GA.
(0.9MM) STAINLESS STEEL, SELF-RIMMING, SATIN FINISH RIM AND BOWLS, MOUNTING KIT PROVIDED, FULLY UNDERCOATED TO REDUCE CONDENSATION AND RESONANCE, FACTORY APPLIED RIM SEAL, 3-1/2"
(89MM) CRUMB CUP WASTE ASSEMBLY WITH 1-1/2" (38 MM) TAILPIECE. CHICAGO FAUCETS #430-ABCP SINGLE LEVER FAUCET, CHROME PLATED, CENTER HOLE ONLY, LEAD FREE CAST BRASS BODY, 5.7
LPM (1.5 GPM) AERATOR OUTLET, LONG CAST SPOUT 229 MM (9") PROJECTION REACH, LEVER HANDLE, VOLUME CONTROL, ADJUSTABLE HOT LIMIT STOP. MCGUIRE #LFH165LKN3, FAUCET SUPPLIES,
CHROME PLATED POLISHED BRASS, HEAVY DUTY ANGLE STOPS, 10 MM (3/8") I.P.S. INLET X 76 MM (3") LONG RIGID HORIZONTAL NIPPLES, V.P. LOOSE KEYS, ESCUTCHEON AND FLEXIBLE COPPER RISER.
MCGUIRE #8912CB P-TRAP, HEAVY CAST BRASS ADJUSTABLE BODY, WITH SLIP NUT, 38 MM (1-1/2") SIZE, BOX FLANGE AND SEAMLESS TUBULAR WALL BEND.
STERN WILLIAMS TRIESTE #54 SHOWER FLOOR, 915 MM (36") X 915 MM (36") X 102 MM (4"), PRECAST TERRAZZO, THRESHOLD, 25 MM (1") GALVANIZED-BONDERIZED STEEL TILING FLANGE ON THREE
SIDES, INTEGRAL CAST BRASS FLOOR DRAIN 2" (50MM) WITH S.S. STRAINER.. INSTALLED ON LEVEL GROUND OR BED OF MORTAR. CHICAGO FAUCETS #SH-PB1-02-000 SHOWER VALVE, SOLID BRASS
BODY, PRESSURE BALANCING, WASHERLESS CERAMIC DRIP-FREE DISC VALVE CARTRIDGE, METAL WALL ESCUTCHEON, 9.5 LPM (2.5 GPM) MAXIMUM FLOW RATE '620A' BALL JOINT SHOWERHEAD WITH ARM AND
FLANGE. PROVIDE P-TRAP, SAME MATERIAL AS THE CONNECTING PIPE DRAIN.
STERN WILLIAMS #MTB-2424 SQUARE SERVICE / MOP SINK, 610 MM (24") X 610 MM (24") X 254 MM (10") DEEP, FLOOR MOUNTED, TERRAZZO COMPOSED OF PEARL GRAY MARBLE CHIPS AND PORTLAND
CEMENT GROUND SMOOTH, SEALED TO RESIST STAIN, CAST BRASS DRAIN WITH STAINLESS STEEL STRAINER, 3"(75MM) OUTLET. CHICAGO FAUCETS #897-369VP-XK WALL MOUNTED TWO HANDLE
MANUAL FAUCET, CHROME PLATED, 8" (203MM) CENTERSET, SOLID BRASS EXPOSED BODY, CERAMIC 1/4 TURN CARTRIDGES, UNRESTRICTED HOSE END OUTLET, 200 MM (7-7/8") FROM WALL TO OUTLET
SERVICE/MOP SINK TWO HANDLE REACH, INTEGRAL ATMOSPHERIC VACUUM BREAKER, METAL RED AND BLUE INDEX BUTTONS 60 MM (2-3/8") LONG LEVER HANDLES WITH VANDAL RESISTANT SCREW. WALL BRACE SUPPORT. STERN WILLIAMS
MANUAL FAUCET
A-20 BUMPER GUARD ANODIZED ALUMINUM CAP STERN WILLIAMS T-35 HOSE AND WALL HOOK 36" (914MM) LONG HOSE WITH 3/4" (19MM) CHROME COUPLING, STAINLESS STEEL WALL BRACKET. STERN
WILLIAMS T-40 MOP HANGER STAINLESS STEEL #4 FINISH, 24" (610MM) LONG WITH 3 RUBBER SPRING LOADED CLIPS. STERN WILLIAMS BP BACK SPLASH PANEL 20 GAUGE TYPE 304 STAINLESS STEEL.
STERN WILLIAMS TC-3 GASKET 3" (76MM) FOR XHCI, PLASTIC AND STEEL PIPE. PROVIDE P-TRAP, SAME MATERIAL AS THE CONNECTING PIPE DRAIN.
FD-1
FLOOR DRAIN FINISHED AREA
WATTS #FD-100-7-5-1 FLOOR DRAIN - EPOXY COATED, 8-1/8" (206MM) DIAMETER, CAST IRON BODY, REVERSIBLE FLASHING CLAMP WITH PRIMARY AND SECONDARY WEEPHOLES, TRAP PRIMER
CONNECTION WITH PLUG. WATTS -5-1 5" (127MM) DIAMETER, NICKEL BRONZE, ADJUSTABLE, HEAVY DUTY, ROUND STRAINER.
-
-
-
-
FFD
FUNNEL FLOOR DRAIN FINISHED
AREA
WATTS #FD-100-C-A5-1-7-G-1 FLOOR DRAIN - EPOXY COATED, 8-1/8" (206MM) DIAMETER, CAST IRON BODY, REVERSIBLE FLASHING CLAMP WITH PRIMARY AND SECONDARY WEEPHOLES, TRAP PRIMER
CONNECTION WITH PLUG, NO HUB OUTLET. WATTS -A5-1-G-1 5" (127MM) DIAMETER, NICKEL BRONZE, ADJUSTABLE, ROUND STRAINER, 4" X 9" (102MM X 229MM) OVAL NICKEL BRONZE FUNNEL.
-
-
-
-
HB
HYDRANT - NON-FREEZE WALL
HYDRANT WITH CHROME FACE,
INEGRAL VACUUM BREAKER
WATTS #HY-420 HYDRANT, 3/4" (19MM) DIAMETER HOSE CONNECTION, 3/4" (19MM) FEMALE X 1" (25MM) MALE PIPE CONNECTION, NON-FREEZE HYDRANT, ALL BRONZE HEAD, SEAT CASTING AND INTERNAL
WORKING PARTS, WALL MOUNT, BRONZE WALL CASING, CHROME PLATED FACE, INTEGRAL VACUUM BREAKER, LOOSE KEY.
-
-
-
-
NFHB
HYDRANT - NON-FREEZE WALL
HYDRANT WITH NB FACE,
INTEGRAL VACUUM BREAKER
WATTS #HY-725 HYDRANT, 3/4" (19MM) DIAMETER HOSE CONNECTION, 3/4" (19MM) FEMALE X 1" (25MM) MALE PIPE CONNECTION, NON-FREEZE HYDRANT, ALL BRONZE HEAD, SEAT CASTING AND INTERNAL
WORKING PARTS, WALL MOUNT, CONCEALED, BRONZE WALL CASING, CHROME PLATED FACE, INTEGRAL VACUUM BREAKER, NICKEL BRONZE BOX AND DOOR, LOOSE KEY.
-
-
-
-
AD
FLOOR DRAIN - FLOOR DRAIN
WITH 8" (203mm) ROUND
ADJUSTABLE COLLAR & HEAVY
DUTY GRATE
WATTS #FD-320-4-7 FLOOR DRAIN - EPOXY COATED, 8-1/8" (206MM) DIAMETER, CAST IRON BODY, BODY COLLAR WITH WEEPHOLES, TRAP PRIMER CONNECTION WITH PLUG, ANCHOR FLANGE, NO HUB
OUTLET. WATTS -4 7-7/8" (200MM) DIAMETER, EPOXY COATED DUCTILE IRON, HEEL-PROOF, ROUND GRATE.
-
-
-
-
CO
CLEANOUT - FLOOR CLEANOUT
WITH ROUND TOP
WATTS #CO-200-R-34G CLEANOUT - EPOXY COATED, 7" (178MM) DIAMETER, CAST IRON BODY, WITH 5" (127MM) ROUND, ADJUSTABLE, GASKETED, NICKEL BRONZE TOP, REMOVABLE, GAS TIGHT,
GASKETED, ABS PLUG WITH NEOPRENE GASKET, NO HUB OUTLET.
-
-
-
-
TD-1
TRENCH DRAIN - 6" WIDE
TRENCH SYSTEM
WATTS #D-DI TRENCH DRAIN - UV STABILIZED TALC-FILLED POLYPROPYLENE CHANNELS WITH INTEGRAL 4" (102MM) NO HUB BOTTOM OUTLET(S), PRE-SLOPED TRENCH, 6" (152MM) WIDE, 48" (1219MM)
LONG, INCLUDING FRAME CONNECTORS, GRATE LOCKDOWNS AND CONSTRUCTION COVERS, DUCTILE IRON FRAME,FRAMED ANCHORED GRATE, DUCTILE IRON GRATE, CLASS C.
-
-
-
-
TD-2
TRENCH DRAIN - 6" WIDE
TRENCH SYSTEM
WATTS #D-DI-B6 TRENCH DRAIN - UV STABILIZED TALC-FILLED POLYPROPYLENE CHANNELS WITH INTEGRAL 4" (102MM) NO HUB BOTTOM OUTLET(S), PRE-SLOPED TRENCH, 6" (152MM) WIDE, 48" (1219MM)
LONG, INCLUDING FRAME CONNECTORS, GRATE LOCKDOWNS AND CONSTRUCTION COVERS, DUCTILE IRON FRAME,FRAMED ANCHORED GRATE, DUCTILE IRON GRATE, CLASS C, 6" X 24" X 24" (152MM X 610MM
X 610MM) CATCH BASIN.
-
-
-
-
TD-3
TRENCH DRAIN - 6" WIDE
TRENCH SYSTEM
WATTS #D-DI-B6 TRENCH DRAIN - UV STABILIZED TALC-FILLED POLYPROPYLENE CHANNELS WITH INTEGRAL 4" (102MM) NO HUB BOTTOM OUTLET(S), PRE-SLOPED TRENCH, 6" (152MM) WIDE, 48" (1219MM)
LONG, INCLUDING FRAME CONNECTORS, GRATE LOCKDOWNS AND CONSTRUCTION COVERS, DUCTILE IRON FRAME,FRAMED ANCHORED GRATE, DUCTILE IRON GRATE, CLASS C, 6" X 24" X 24" (152MM X 610MM
X 610MM) CATCH BASIN.
-
-
-
-
TD-4
TRENCH DRAIN - 6" WIDE
TRENCH SYSTEM
WATTS #D-DI-B6 TRENCH DRAIN - UV STABILIZED TALC-FILLED POLYPROPYLENE CHANNELS WITH INTEGRAL 4" (102MM) NO HUB BOTTOM OUTLET(S), PRE-SLOPED TRENCH, 6" (152MM) WIDE, 48" (1219MM)
LONG, INCLUDING FRAME CONNECTORS, GRATE LOCKDOWNS AND CONSTRUCTION COVERS, DUCTILE IRON FRAME,FRAMED ANCHORED GRATE, DUCTILE IRON GRATE, CLASS C, 6" X 24" X 24" (152MM X 610MM
X 610MM) CATCH BASIN.
-
-
-
-
INTERCEPTOR - OIL INTERCEPTOR
WATTS #WO-350 INTERCEPTOR - EPOXY COATED INSIDE AND OUTSIDE, FABRICATED STEEL BODY, EPOXY COATED NON-SKID COVER, COVER SECURING BOLTS, STAINLESS STEEL CALIBRATED ORIFICE
ON FLOOR OR RECESSED
PLATE, CODE APPROVED DEEP SEAL TRAP, 50 GPM, NO HUB CONNECTIONS.
INSTALLATION
-
-
-
-
A TOTAL OF 128 GROUPS CAN BE ASSIGNED.
3.6
RATINGS AND CERTIFICATIONS
CONFORMS TO N ORDINARY LOCATIONS INTERNATIONAL ELECTRICAL COD: IEC NO.61010
EMI/RFI COMPLIES WITH EMC DIRECTIVE 89/336/EEC
CSA CERTIFICATION
4.
4.1
4.2
4.3
4.4
INSTALLATION
PROVIDE ALL NECESSARY LABOUR AND MATERIALS INDICATED ON THE DRAWINGS AND SPECIFIED
HEREIN FOR A COMPLETE, OPERATING SYSTEM.
DRAWINGS SHOWING WORK ARE DIAGRAMMATIC ONLY. EXAMINE THE SITE; TAKE ALL RELEVANT
INFORMATION INCLUDING ACCURATE MEASUREMENTS BEFORE ORDERING MATERIALS AND
COMMENCING WORK.
SHOP DRAWINGS AND INSTALLATION DETAILS: SUBMIT SHOP DRAWINGS FOR ALL EQUIPMENT AND
MATERIALS SPECIFIED HEREIN, INCLUDING MONITORING PANEL AND GAS DETECTION TRANSMITTERS.
VERIFICATION: AFTER INSTALLATION, TEST OF EQUIPMENT TO DEMONSTRATE OPERATION OF
FUNCTIONS DESCRIBED ABOVE UNDER SEQUENCE OF OPERATION BY MANUFACTURES CERTIFIED
SERVICE TECHNICIAN. A CERTIFICATE OF COMPLIANCE WITH MANUFACTURERS' INSTALLATION
GUIDELINES SHALL BE ISSUED TO THE OWNERS UPON COMPLETION.
OI
PLUMBING FIXTURE SCHEDULE
TAG
TSP-1
TSP-2
CB-1
CB-2
CB-3
FIXTURE
PIPE SIZES
SPECIFICATION
DCW
DHW
DRAIN
VENT
TRAP SEAL PRIMERS
MECHANICAL
SMS INC. #PRO1-500 PPP PRIME-PRO TRAP SEAL PRIMER VALVE, LEAD-FREE BRASS BODY, SERVING INDIVIDUAL OR REMOTE AREA DRAINS (PRIMER AUTOMATICALLY ACTIVATED WHEN THERE IS A
PRESSURE DROP IN THE SYSTEM) WITH 1/2" (12.7MM) NPT CONNECTIONS WITH STAINLESS STEEL SCREEN AND INTEGRAL NEOPERL CHECK VALVE. (FOR 2, 3 OR 4 DRAINS PROVIDE PRIMER UNIT WITH
DISTRIBUTION UNIT ASSEMBLY #DU-4).
-
-
-
-
TRAP SEAL PRIMERS
ELECTRONIC - SERVING 4 TO 30
DRAINS
SMS INC. #PT-12 -PTD #PT SERIES (SURFACE MOUNTED) ELECTRONIC TRAP PRIMING MANIFOLD, MODIFIED MANIFOLD TO 3/4" (18MM) DIA. SUPPLY PIPE, THE UNIT SHALL SUPPLY A MINIMUM OF 0.3L
(10 OZ.) OF WATER OPENING, 24 HOUR PERIOD OR AS SELECTED WITH ADJUSTABLE RECYCLE TIMER ON A 24 HOUR PERIOD BASED ON A SYSTEM PRESSURE OF 60 PSI (412KPA). FACTORY ASSEMBLED WITH A
BRONZE BODY BALL VALVE, WATER HAMMER ARRESTOR, SOLENOID VALVE, ATMOSPHERIC VACUUM BREAKER AND A TYPE L COPPER MANIFOLD C/W COMPRESSION FITTING. ELECTRONIC SINGLE POINT POWER
CONNECTION 120V 1AMP DRAW, MANUAL OVERRIDE SWITCH , PROVIDE ACCESS PANEL , 12 OPENING MANIFOLD (UP TO 3.5L (120OZ.) PER MANIFOLD. DEPTH OF CABINET DRY WALL - 4" (102MM) FIRE RATED 6" (150MM)
-
-
-
-
G
REDUCING STATION
17
7
PIPE UP
GAS SERVICE BY LOCAL UTILITY
COMPANY, CAPACITY 2,600 CFH
G
G
1
G
C
(ABOVE)
'WC-1'
DRAIN FROM
ABOVE
CO
SAN
CO
PIPES DROP TO
ACCOMMODATE
LOW ROOF
SAN
PIPES RISE UP TO
HIGH LEVEL AFTER
LOW ROOF
16
(ABOVE)
SLOPE @ 1%
SAN
'WC-2'
(ABOVE)
(ABOVE) FD
'U-1'
(ABOVE)
3
BFP G
A
'L-1'
(ABOVE)
10
FFD
'S-2'
(ABOVE)
CO
'CB-1'
'WC-2'
(ABOVE)
13
SAN
'L-1'
SAN
2
'SH-1'
(ABOVE)
'S-1'
CO
D
'L-1'
3
'WC-1'
DRAIN FROM
ABOVE
'TD-4'
SAN
V
'HWT-1' REFER TO
16
DETAIL 18, ON
DRAWING M-1.4
'CB-2'
6
F
SAN
SAN
SAN
ST
SLOPE @ 1%
ST
FD
'L-2'
(ABOVE)
6
SAN
CO
TO ROOF
SLOPE @ 1%
2
14
ST
'L-1'
CO
ST
TO SEPTIC TANK BY
OTHERS. REFER TO SITE
SERVICE PLAN
G
16
CO
V
5
SAN
SAN
SAN
SAN
SAN
SAN
SAN
ST
18
12
11
SAN
E
'WC-1'
3
CO
16
V
FD
15
B
'SH-1'
(ABOVE)
SLOPE @ 1%
SAN
'TD-1'
CO
'TD-2'
4
'WC-2'
(ABOVE)
V
'WC-2'
(ABOVE)
'L-2'
(ABOVE)
CO
'L-2'
(ABOVE)
INT-1
CO
SAN
SLOPE @ 1%
SAN
SAN
16
V
CO
H
V
ST
8
V
(ABOVE)
CO
ST
(ABOVE)
J
EF-10
16
16
BELOW
SLAB
TO ROOF
ST
'TD-3'
AND DHW
K
LOW ROOF DRAIN
ABOVE (TYP. OF 3)
ST
'CB-3'
CO
6
6
L
'S-2'
(ABOVE)
DHW UP TO
SERVE 'S-2'
CO
DRAWING NOTES:
N
M
1 NEW DOMESTIC COLD WATER METER, CONNECT BELOW GRADE EXTERIOR TO UTILITY
SERVICE. REFER TO DETAIL 16 ON DWG. M-1.3 FOR INSTALLATION DETAIL.
2
SLAB.
3
4 OIL INTERCEPTOR. REFER TO DETAIL 2 ON DRAWING M-1.2. PROVIDE OIL STORAGE
TANK. COORDINATE WITH OWNER FOR TANK CAPACITY. INSTALL TANKS AS PER
MANUFACTURER REQUIREMENTS.
5
LOCATION.
6 PROVIDE FLUSH MOUNTED INTERIOR/EXTERIOR NON-FREEZE HOSE BIBB.
7
8
DRAWING M-1.3
9 SANITARY LINE UP TO SERVICE 'L-1' AND 'WC-1' ON HIGH LEVEL/MEZZANINE LEVEL. SEE
DRAWING M-3.1 FOR CONTINUATION.
GENERAL NOTES:
1.
CONTRACTOR TO CLEAN ALL DEBRIS AND RUBBISH GENERATED FROM THIS WORK.
2.
ALL PENETRATIONS THROUGH FIRE RATED DEMISING WALLS AND ROOF DECK
SHALL BE FIRE STOPPED AND SEALED.
3.
COORDINATE WITH ALL TRADES FOR NEW PLUMBING FIXTURE AND PIPING
INSTALLATION.
ROOM.
12
(L-1) IN THE TECH WASHROOM.
THE TECH WASHROOM.
5.
AUTOMATIC PRIMING SYSTEM. TSP REFER TO PLUMBING SCHEDULES.
GROUND FLOOR PLAN - PLUMBING AND DRAINAGE
11
13
4.
6.
10 PROVIDE AUTOMATIC ELECTRONIC TRAP SEAL PRIMER.
ALL PLUMBING VENT PIPING SHALL BE INSIDE WALLS AND INSTALLED IN
ACCORDANCE WITH THE LATEST EDITION OF THE OBC (PART 7). UNLESS
OTHERWISE INDICATED.
7.
CONTRACTOR TO COORDINATE ALL TRADES TO ENSURE NO INTERFERENCE OF NEW
SYSTEMS. (SHEET METAL, PLUMBING, ETC.).
8.
ALL DOMESTIC COLD AND HOT WATER PIPE SHALL BE INSULATED.
14
15
(L-1) IN WASHROOM CLOSET WC1 AND WC2.
16
17 PROVIDE BOLLARD PROTECTION FOR GAS METER.
18 CONNECT TO EXISTING STORM SERVICE LINE AT THIS APPROXIMATE LOCATION.
1
2
3
4
5
6
7
8
9
10
BELOW UP TO ROOF
11 12
13
14
15
11
A
B
16
10
8
ST
CO
ST
ST
17R
ST
DN
STAIR DN
No1 9R@189
C
ST
STORAGE
ROOM
4
3
ST
RD
ST
ST
E
ST
FROM ROOF
DRAIN ABOVE
ST
'L-2'
FD
'SH-1'
211
'WC-2'
WM'S
LOCKER1RM
209 ST
210 ST
ST
9
'U-1' 'U-1'
2 LUNCH
ROOM
5
TO ROOF
5
6
8
WM'S WC
'S-2'
7
FD
FROM ROOF
DRAIN ABOVE
3
6
213
D
12
ST
ST
ST
CO
ROOF (TYP.)
ADMIN
FROM ROOF
DRAIN ABOVE
201
ST
'SH-1'
212
FD
207
'WC-2'
2
TO ROOF
MEN'S WC
CORRIDOR
208
12
'L-1''L-1'
MEN'S
LOCKER RM
A
B
FROM ROOF
DRAIN ABOVE
STORAGE
ROOM
CUSTOMER
LOUNGE
214
200
F
ST
F
OPEN TO SERVICE
DEPARTMENT BELOW
DRIVE-THROUGH ROOF
BELOW
ST
MEETING
ROOM
202
G
ST
RD
3
ST
OPEN TO AUDI
FROM ROOF SHOWROOM BELOW
DRAIN ABOVE
3
'WC-2'
2
1
WC
204 4
203
ROOF (TYP.)
2
1
H
'L-2'
'L-2'
ST
J
FD WC
'WC-2'
FD
4
TO ROOF (TYP.)
ST
UPPER PARTS
STORAGE
ST
215
RD
K
L
CO
4
FROM ROOF
DRAIN ABOVE
'S-2'
1
OPEN TO PARTS
DELIVERY
BELOW
GEN.MGR
M
206
N
GENERAL NOTES:
1.
CONTRACTOR TO COORDINATE ALL TRADES TO
ENSURE NO INTERFERENCE OF NEW SYSTEMS. (SHEET
METAL, PLUMBING, ETC.)
KEY NOTES:
1
2
3
SANITARY SERVING 'WC-2'.
4
SANITARY SERVING 'L-2'.
5
SANITARY SERVING 'U-1'.
6
7
8
SANITARY SERVING 'SH-1'.
9
SANITARY SERVING 'S-2'.
10 SANITARY SERVING 'L-1'.
11
12
SECOND FLOOR PLAN - PLUMBING AND DRAINAGE
1
2
3
4
5 6
7
8
B
9
10
11 12
13
14
15
PROVIDE SUPPORTS FOR
ALL GAS PIPING ON ROOF.
SEE DETAIL ON DRAWING
10/M-1.3. (TYP.)
PIPING FROM
BELOW
3
A
16
ROOF HEIGH POINT
G
G
G
G
G
G
G
G
G
G
G
G
RD
G
EF-9
SLOPE
RD
RD
VENT THRU
ROOF
G
G
RTU-6
SLOPE
1
MUA-1
G
DUCT DROPS LOCATED
IN-BETWEEN BEAMS
G
G
G
G
R.D.
EF-8
G
RTU-3
R.D.
RTU-4
EF-10
G
RD
RD
ROOF HEIGH POINT
G
G
G
BEAMS (TYP.)
EF-7
DUCT DROPS LOCATED
IN-BETWEEN BEAMS
ROOF HEIGH POINT
RTU-1
4
2
G
G
G
F
7.5 TON
G
G
G
G
G
SLOPE
1200x500 SUPPLY
DUCT DOWN
SLOPE
15 TON (350 MBH)
PROVIDE 100mm HIGH
CONCRETE PAD (TYP.)
DUCT DROPS LOCATED
IN-BETWEEN BEAMS
G
G
G
R.D.
G
G
G
NECK
D
3 TON
115 MBH
RD
R.D.
G
R.D.
R.D.
E
VENT THRU
ROOF
RD
R.D.
G
VENT THRU
ROOF
EF-6
G
G
8400
G
SLOPE
G
PROVIDE 100mm HIGH
CONCRETE PAD FOR ALL
ROOF TOP UNITS (TYP.)
RTU-5
G
G
G
G
GAS LINE
DROPS TO
LOWER ROOF
G
G
SLOPE
0.000
NECK
G
GAS LINE
RISES FROM
LOWER ROOF
G
G
HEIGH POINT
SLOPE
C
3
VENT THRU
ROOF (TYP.)
H
10 TON
G
7.5 TON
J
LADDER AND ROOF
HATCH ABOVE
10 TON
VENT THRU
ROOF
RTU-7
G
DUCT DROPS LOCATED
IN-BETWEEN BEAMS
NECK
DUCT DROPS LOCATED
IN-BETWEEN BEAMS
SLOPE
SLOPE
DUCT DROPS LOCATED
IN-BETWEEN BEAMS
SLOPE
RTU-2
SLOPE
7.5 TON
RD
K
L
RD
R.D.
SLOPE
1
HEIGH POINT
ROOF HEIGH POINT
N
M
GENERAL NOTES:
1.
CONTRACTOR TO COORDINATE ALL TRADES TO ENSURE
NO INTERFERENCE OF NEW SYSTEMS. (SHEET METAL,
PLUMBING, ETC.)
2.
CONTRACTOR TO PROVIDE NEW ROOF TO
UNITS, EXHAUST FANS, DUCTWORK AND ACCESSORIES
AS INDICATED.
3.
CONTRACTOR TO PROVIDE ACOUSTICAL LINING IN ALL
SUPPLY DUCTS AND RETURN DUCTS FROM RTUs, FOR
THE FIRST 5 FEET, (1524mm) (MINIMUM).
4.
CONTRACTOR TO PROVIDE THERMAL INSULATION ON
ALL EXHAUST DUCTS, FOR THE FIRST 10 FEET (3048mm)
FROM THE OUTSIDE.
5.
ALL DUCT OPENINGS AND GOOSENECKS SHALL BE MIN
24" (600mm) ABOVE ROOF LEVEL.
6.
ALL EXHAUST OPENINGS SHALL BE EQUIPPED WITH BIRD
SCREEN.
KEY NOTES:
1
700x400 GOOSENECK FROM BELOW C/W BIRDSCREEN.
2
750x450 GOOSENECK FROM BELOW C/W BIRDSCREEN.
3
4
ROOF PLAN - HVAC AND ROOF DRAIN LAYOUT
EXHAUST FAN 'EF-4' BY EQUIPMENT SUPPLIER.
6
7
6
7
10
104
UP
R19@189
G
WC 1
A
OFFICE
109
FD
SAN
2
'L-1'
9
E
'WC-1'
SAN
SAN
G
C
10
106
CO
11 12
G
G
G
17R
UP
TOOL ROOM
SAN
119
THROUGH ROOF
2
SAN
'WC-1'
1
STAIR NO 2
KEY ROOM
STORAGE
'WC-2'
8
2
110
'L-1'
(ABOVE)
SAN
118
111
(ABOVE)
WC 2
FD
SAN
108
J
1
'S-1'
'L-1'
'L-2'
(ABOVE)
UP
'L-2'
(ABOVE)
WORKBAY AREA
DN
UP TO ROOF
E
18
WASHROOM - WC-1 (107) AND WC-2 (108)
13
14
PLUMBING AND DRAINAGE UP TO WC (203) AND WC (204)
TOOL ROOM 120 / TECH. WC 121
15
3
'L-1'
(ABOVE)
11
G
B
G
G
ELECTRICAL
ROOM
G BFP
M
4
MECHANICAL
ROOM
'SH-1'
(ABOVE)
(ABOVE)
FFD
'S-2'
(ABOVE)
122
G
121
1
(ABOVE)
CO
'WC-2'
(ABOVE)
G
SAN
TO ROOF
DRAWING NOTES:
CO
'U-1'
(ABOVE)
SAN
GENERAL NOTES:
1.
CONTRACTOR TO CLEAN ALL DEBRIS AND RUBBISH GENERATED FROM THIS WORK.
2.
ALL PENETRATIONS THROUGH FIRE RATED DEMISING WALLS AND ROOF DECK
SHALL BE FIRE STOPPED AND SEALED.
3.
COORDINATE WITH ALL TRADES FOR NEW PLUMBING FIXTURE AND PIPING
INSTALLATION.
SLAB.
2
3
'HWT-1'
11
D
G
4.
4 PROVIDE AUTOMATIC ELECTRONIC TRAP SEAL PRIMER.
5
ROOM.
5.
AUTOMATIC PRIMING SYSTEM.
6
(L-1) IN THE TECH WASHROOM.
6.
ALL PLUMBING VENT PIPING SHALL BE INSIDE WALLS AND INSTALLED IN
ACCORDANCE WITH THE OBC (PART 7). UNLESS OTHERWISE INDICATED.
7
THE TECH WASHROOM.
10
WORKBAY AREA
8
9
(L-1) IN WASHROOM CLOSET WC1 AND WC2.
MECHANICAL ROOM 123 - PLUMBING AND DRAINAGE
10
11
WALL.
SAN
120
'L-2'
(ABOVE)
19R
'SH-1'
(ABOVE)
SAN
UP TO ROOF
SLOPE @ 1%
F&I
TECH.WC
5
(ABOVE)
107
(ABOVE)
SAN
SLOPE @ 1%
SAN
'WC-2'
(ABOVE)
'WC-1'
10
7
FD
'WC-2'
(ABOVE)
6
2
3
4
5
6
7
8
9
10
11 12
13
F
C
FFH-1
3.0 kW
T
VOID
AUDI EXCLUSIVE
VOID
---
FRD
T
SLOPE
B
104
94
T
17R
UP
T
57
UP
R19@189
1
DUCT UP TO ROOF
TRENCH DRAIN
B
105
TOOL ROOM
PROVIDE NEW 2kW FFH C/W
INTEGRATED THERMOSTAT. 119
208V/1PH.
COORDINATE WITH DIV.16
(CEILING MOUNTED)
FFH-1
3.0 kW
STAIR NO 2
118
T
TO RTU-1
U/C
38
'EF-2'
350x250
G
200x200
108
WORKBAY AREA
CO/NOX
DETECTOR
43
TO UH-1 UP AT
HIGH LEVEL
T
43
SERVICE
DEPARTMENT
SERVICE
DRIVE-THROUGH
109
'BP-8'
123
117
TRENCH DRAIN
5
600x300
103
STORAGE
111 U/C
'BP-7'
BD
38
B
1
B
24
38
B
B
24
T
200x250
TO UH-1 UP AT
HIGH LEVEL
CORRIDOR
300x200
300x200
DN
PARTS MGR
UP TO
RTU-4
CO/NOX
DETECTOR
126
'BP-5'
T
DN
RETAIL PARTS
112
28
127
GATE
TECH.PARTS
125
F.F.E.+306.15
(TYP. OF 6)
WORKBAY AREA
DN
BOUTIQUE
113
116
OFFICE
T
300x200
115
SER.MGR
200x250
TRENCH DRAIN
17R
OFFICE
H
124
WRITE-UP
TO RTU-2
T
124B
UP
350x250
350x250
19R
N
F
500x250
J
100
D
UPPER GLAZING.
REFER TO BLDG
ELAVATIONS
4
VESTIBULE
FRD
----
C
B
450x350
SALES
'BP-6'
T
--600x300
T
110
K
F
WC600x300
2
B
KEY ROOM
B
T
CO/NOX
DETECTOR
WORKBAY AREA
OFFICE
102
2
122
107 OF 10)
(TYP.
FULL HEIGHT
GLAZED
SCREEN
101
'EF-12'
1
F&I
RECEPTION
'EF-11'
121
TO UH-1 UP AT
HIGH LEVEL
(TYP. OF 3)
AUDI
SHOWROOM
ELECTRICAL
ROOM
B
120
T
350x250
B
M
MECHANICAL
ROOM
3
CO/NOX
DETECTOR
300x250
E
M
FRD
'EF-3'
DUCT UP TO ROOF
106
'EF-1'
FRD
2
TECH.WC
WC 1
U/C
16
3
STAIR NO.1
NVD
15
600x300
TO UH-1 UP AT
HIGH LEVEL
A
14
BBH (1.5 kW)
1
TO UH-1 UP AT
HIGH LEVEL
B
33
125C
TO UH-1 UP AT
HIGH
LEVEL
T
CO/NOX
DETECTOR
TO UH-1 UP AT
T HIGH LEVEL
6
L
PARTS
DELIVERY
128
T
114
UH-1
TO HIGH LEVEL
F.F.E.+306.15
SLOPE
B
33
T
TO UH-1 UP AT
HIGH LEVEL
M
VOID
BBH (1.5 kW)
BBH (1.5 kW)
B
BBH (1.5 kW)
57
OHAC-1
OVER HEAD AIR
CURTAIN DOOR
7
(TYP.)
B
57
GENERAL NOTES:
1.
B
57
2.
GROUND FLOOR PLAN - HVAC
CONTRACTOR TO COORDINATE ALL TRADES TO ENSURE
NO INTERFERENCE OF NEW SYSTEMS. (SHEET METAL,
PLUMBING, ETC.)
KEY NOTES:
1
CONTRACTOR TO UNDERCUT DOOR 20mm.
2
PROVIDE ELECTRICAL ROOM VENTILATION SYSTEM
ACTIVATED BY REVERSE ACTING THERMOSTAT.
CONTRACTOR TO PROVIDE NEW ROOF TOP UNITS, CAV
BY PASS FAN POWERED TERMINAL UNITS, EXHAUST
FANS, DUCTWORK, DIFFUSERS, GRILLES, BALANCING
DAMPERS, FIRE DAMPERS, THERMOSTATS, CONTROL
WIRING, AND ACCESSORIES AS INDICATED.
3.
CONTRACTOR TO BALANCE DUCT SYSTEM AS
INDICATED.
4.
PROVIDE ACCESS PANEL FOR ALL CAV BY PASS BOXES
WHERE REQUIRED (GWB CEILING).
EXHAUST FAN ([email protected]"SP) SHALL BE
INTERLOCKED WITH AIR INTAKE GRILLE (600/300 IN
SIZE) MOTORIZED DAMPER AND EXHAUST AIR OUTLET
LOUVER (600/300 IN SIZE) MOTORIZED DAMPER C/W
120/24V TRANSFORMER FOR ALL MOTORIZED DAMPER.
CONTRACTOR SHALL COORDINATE FINAL LOCATION WITH
ELECTRICAL EQUIPMENT (TRANSFORMER AND SWITCH
GEAR) ON SITE.
3
FIRE RATED DAMPER AT HIGH LEVEL.
5.
PROVIDE ACCESS PANEL IN DUCTWORK FOR ALL FIRE
DAMPERS.
4
250x200 SUPPLY AND 300x200 RETURN DUCTWORK FROM
ABOVE.
6.
ALL ELECTRICAL HEATERS TO BE SUPPLIED AND
INSTALLED BY ELECTRICAL DIVISION.
5
600x300 SUPPLY AND 700x300 RETURN DUCTWORK FROM
ABOVE.
6
CONTRACTOR TO PROVIDE UNIT HEATER WITH VENTING
(FRESH/EXHAUST AIR), GAS PIPING, SUPPORTS,
CONTROLS, AND ELECTRICAL. REFER TO DETAIL 12 ON
DWG 1.3 FOR INSTALLATION.
7
ELECTRIC BASEBOARD HEATER (BBH) TO BE SUPPLIED
AND INSTALLED BY DIV.16.
1
2
3
A
4
5
6
7
236
71
B
B
(TYP. OF 3)
B
10
11 12
14
15
E
DUCT UP TO ROOF
47
A
150
16
24
200x150
200
A
E
118
A
250x250
150
(TYP. OF 2)
4
A
B
G
----
(TYP. OF 6)
SLOT RETURN
GRILLES
(TYP. OF 3)
400x400 UP TO
'EF-9' ON ROOF
T
750x450 EXHAUST DUCT
TERMINATING AT 450mm
ABOVE FINISHED FLOOR
47
B
47
UH-1
300x300 UP TO
'EF-6' ON ROOF
MD
4
2
G
3
BD
500x400
BD
500x400
UP TO 'EF-10'
ON ROOF
8
UH-1
G
200
BD
700x400
-
---
BD
900x500
800x800 UP TO
'EF-8' ON ROOF
H
9
350x250
B
G
250x250
C
UH-1
150x150
200
200x200
4
9
C
300x250
850x400
C
1300
900x300
236
450x200
(TYP. OF 6)
1
57
1
UH-1
UH-1
G
B
200
G
350x200
FRD
G
DUCT UP TO
ROOF
U/C
300x250
1
750x450
'BP-3'
U/C
950x350
450x300
'EF-4'
5
750x400
6
FRD
550x300
1
G
'BP-2'
C
T
4
F
TO 'EF-7'
ON ROOF
BD
4
'BP-4'
D
G
11
1
500x350
(TYP. OF 2)
'EF-5'
950x350
G
450x200
MD
200x200
300x250
'BP-1'
450x300
450x350
B
4
7
(TYP.)
G
T
750x400
J
G
G
1000x450
F
G
G
500x350
10
G
200x150
236
500x350
BD
250x200
G
33
(TYP. OF 6)
250x250
900x700
250x150
200x150
76
C
350x250
900x350
(TYP. OF 2)
450x350
U/C
U/C
750x450
B
G
450x350
UH-1
E
G
200x150
200x150
350x350
DUCT FROM
BELOW AND UP
TO ROOF
G
G
E
1
G
47
G
600x300
E
G
----
750x450
650x350
C
G
(TYP.)
400x300
B
K
13
BBH (1.5 kW)
C
G
9
TERMINATION CAP, REFER TO DETAIL 3 ON
DWG M-1.2 FOR INSTALLATION
(TYPICAL)
2-SLOT LINEAR
DIFFUSERS (TYP.)
A
8
BELOW UP TO ROOF
(TYP. OF 3)
T
G
G
G
G
G
MD
G
G
L
1
2
TO UH-1 AT LOW LEVEL
A
T 250x250
700x400
75
250x250
TERMINATION CAP, REFER
TO DETAIL 3 ON DWG
M-1.2 FOR INSTALLATION
(TYPICAL)
UH-1
200x200
400x300
M
'EF-13'
750x450 EXHAUST DUCT
TERMINATING AT 450mm
ABOVE FINISHED FLOOR
(TYP.)
N
BBH (1.5 kW)
BBH (1.5 kW)
BBH (1.5 kW)
B
71
C
283
450x200
(TYP. OF 6)
A
236
2-SLOT LINEAR
DIFFUSERS (TYP.)
B
71
B
71
GENERAL NOTES:
KEY NOTES:
1.
CONTRACTOR TO PROVIDE NEW A/C UNITS, FANS,
DUCTWORK, DIFFUSERS, GRILLES, BALANCING
DAMPERS, FIRE DAMPERS, CEILING FANS,
THERMOSTATS AND ACCESSORIES AS INDICATED.
1
CONTRACTOR TO PROVIDE UNIT HEATER WITH VENTING
(FRESH/EXHAUST AIR), GAS PIPING, SUPPORTS,
CONTROLS, AND ELECTRICAL. REFER TO DETAIL 12 ON
DWG 1.3 FOR INSTALLATION.
2.
CONTRACTOR TO BALANCE DUCT SYSTEM AS
INDICATED.
2
700x400 DUCTWORK C/W MOTORIZED DAMPER UP
THROUGH ROOF. INTERLOCK WITH 'EF-7'.
3.
NATURAL GAS LINE SHALL BE CLEARLY INDICATED AS
PER CAN/CSA-B149.1-05. PROVIDE PRESSURE
REGULATOR FOR EACH PIECE OF EQUIPMENT IF NOT
PROVIDED BY THE MANUFACTURER.
3
750x450 DUCTWORK C/W MOTORIZED DAMPER UP
THROUGH ROOF. INTERLOCK WITH ROOF MOUNTED
EXHAUST FAN 'EF-9'.
4
750x400 SUPPLY AND 950x350 RETURN DUCTWORK
FROM ROOF TOP UNITS. SEE DRAWING M-2.2 FOR
CONTINUATION.
5
TAIL PIPE EXHAUST C/W ALL DUCTWORK SHALL BE
SUPPLIED AND INSTALLED BY OWNER, EQUIPMENT
SUPPLIER. 200 CFM FOR EACH BAY.
6
600x300 SUPPLY AND 700x300 RETURN DUCT DOWN TO
GROUND FLOOR. SEE DRAWING M-3.0 FOR
CONTINUATION.
7
BY-PASS BOX. SEE DRAWING M-1.4 FOR DETAILS.
8
1200x500 SUPPLY DUCTWORK UP TO ROOF MOUNTED
MUA-1.
9
350x200 SUPPLY AND 350x250 RETURN DUCTWORK
FROM BELOW.
10 1200x350 SUPPLY AND 900x700 RETURN DUCTWORK
FROM ROOF TOP UNIT 'RTU-1'.
11 500x350 SUPPLY AND 700x300 RETURN DUCTWORK
FROM ROOF TOP UNIT 'RTU-5'.
SECOND FLOOR PLAN - HVAC