Diamondback Flyer
Transcription
Diamondback Flyer
Experience the full product offering of G&W Single and Three Phase Solid Dielectric Reclosers Available in overhead, substation and padmount applications. Unmatched safety, reliable performance, automation ready. Diamondback Underground Distribution Switchgear Three-Phase Solid-Dielectric, Load Break Switch 29.3kV, 630A, Six Internal Voltage Sensors Submersible, maintenance-free construction built to the most rigorous industry standards. Available in solid dielectric or SF6. FEATURES: • Automation ready System Automation and Smart Grid Solutions • Maintenance-free solid-dielectric technology Lazer Automation provides standard or customized peer-to-peer solutions and is 100 percent scalable on a model-based platform. - No SF6 or gas monitoring required • Encapsulated 1000:1 CT, +/-1 % accuracy • Six internal voltage sensors (VS), +/-3 % accuracy • Mechanical open and close operations • Compact Size System Protection Equipment • Light Weight construction (99kg / 218 lbs) • Reversible alley-arm/ center mount frame options High continuous current ratings with current limitation and ultra-high speed operation. Mitigates Arc Flash and Arc Blast. • Lockout ring handle to prevent operation • Dead Line Operation on battery backup • Wildlife protectors (option) • Spare auxiliary contacts (option) Transmission and Distribution Cable Accessories • NEMA 2-hole, NEMA 4-hole, or clamp style aerial lug options Terminations and joints designed and manufactured to accommodate any new cable or existing cable systems. t Mechanical open/close handle G&W Electric Company 305 W. Crossroads Pkwy Bolingbrook, IL 60440 USA Tel 708.388.5010 Fax 708.388.0755 gwelec.com ISO 9001:2008 Certified ISO 14001:2004 Certified APPLICATIONS: RATINGS: • Basic distribution load break switching to complex loop schemes - Manual or Automated Switching - Fault Passage Indication - Sectionalizing SOURCE RECLOSER DIAMONDBACK LBS USED AS SECTIONALIZER - Tie Switch - Automatic Transfer - Loop Scheme LOAD 1 LOAD 2 Application Example: Diamondback Applied as a Sectionalizer 1. A fault occurs between Diamondback and Load 2 2. The recloser starts reclosing sequence: trips open, closes, trips open 3. The Diamondback opens after 2nd overcurrent trip 4. The recloser closes and restores power on the line between the recloser and Diamondback Maximum Voltage 29.3kV Continuous Current 630A Frequency 50/60 Hz Power Frequency Withstand Voltage, Wet 60kV Power Frequency Withstand Voltage, Dry 50kV Lightning Impluse Withstand Voltage 150kV Short-Circut Current, 3 seconds 12.5kA (RMS) Making Current Peak 32.5kA Mechanical Operations 5000 times Temperature Range CONTROL: PNC Technologies - Model FTU-P200 -30°C to +50°C The Diamondback has been tested and designed Measurement & Status Monitoring Distribution Automation Ready to comply with the IEEE C37.74 and IEC 62271-103 The FTU-P200 control is equipped to control Integrate the FTU-P200 control into SCADA or standards (formerly known as IEC 60265-1:1998). and monitor measurement and status of the distribution automation systems with ease. RS232/ Diamondback load break switch. Instantaneous and RS485 serial port and Ethernet port connectivity are demand metering are available with programmable available. Communications protocols include the user integration intervals. configurable mapping of DNP 3.0 protocol, and the • Voltage, Current, and Phase Angle IEC 60870-5-101 and IEC 60870-5-104 protocols. - Six voltage inputs and three current inputs - Fault Passage Indication Data Acquisition - Over/under Voltage Analyze grid performance with event and fault - Over/under Frequency recording. - Phase Sync Fail Detection • Fault waveform recording - Open Line Detection - 128 samples/cycle • Power Quality Monitoring (PQM) - Waveform Evaluation Software - COMTRADE file format - Sag, Swell, Interruption detection • Harmonics (up to 31st) • THD (Total Harmonic Distortion) • Auto Sectionalizing • Sequence of Events (SOE) and Event History p PNC FTU P200 Automated Controller