Installation overview Darfon Electronics Corp.

Transcription

Installation overview Darfon Electronics Corp.
Installation overview
Darfon Electronics Corp.
In The Beginning – Layout is the key.
Darfon Electronics Corp.
In The Beginning – Layout is the key.
Junction Box
Communication
CAT 5 go with AC cable
String 1
10 AWG Cable
Extend to AC panel
Screw on wire connector
String 2
Darfon Electronics Corp.
In The Beginning – Layout is the key.
Rule 1: One PLC can support to 25 units of MIG240 maximum.(No more than 13 units
each in each side.)
Darfon Electronics Corp.
In The Beginning – Layout is the key.
Rule 2: Don't put PLC Box closed to each other, that means users need to put PLC
btw Mis strings.
Darfon Electronics Corp.
In The Beginning – Layout is the key.
Rule 3: Keep PLC closed to the microinverters. (No more than 10 m from the
first unit)
Darfon Electronics Corp.
In The Beginning – Layout is the key.
Rule 4: Commercial layout should be regular and arranged.
Darfon Electronics Corp.
To locate the MIG240 by sticker
The sticker would help installer to locate
MIs on a hand drawn map.
Darfon Electronics Corp.
AC Connector & Trunk Cable
240 Volt AC Single Phase
L1 to L2
211 to 264 VAC
L1, L2 to neutral
106 to 132 VAC
Darfon Electronics Corp.
AC Connector & Trunk Cable
Darfon Electronics Corp.
AC Connector & Trunk Cable
Darfon Electronics Corp.
AC Connector & Trunk Cable
For water proof of the end of trunk cable.
Into socket
Darfon Electronics Corp.
Communication System Installation
Maximum Distance = 400 meters
Notice: need for CAT5 wires
T-
T+
Darfon Electronics Corp.
Communication System Installation
Darfon Electronics Corp.
Communication System Installation
ID/Password: user/user
Browser
Darfon Electronics Corp.
Communication System Installation
Darfon Electronics Corp.
Communication System Installation
Darfon Electronics Corp.
Communication System Installation
00000000SN30401011
MIG240UL00A30401011
Darfon Electronics Corp.
Communication System Installation
Darfon Electronics Corp.
Troubleshooting - Different type of PV connector
White light: means no power from panel
Darfon’s MI should be connected with PV panel as below.
Darfon Electronics Corp.
Troubleshooting - Different type of PV connector
There are many different PV suppliers on the market in the world. Different panels
may have different type of connector. Such as Poly280 manufactured by schott
company, this panel with a female connector as anode, and male connector as
cathode. That will not fit with Darfon’s MIG240. We suggest customer to choose an
appropriate panel to fit with MIG240. The panel supplier must have other type that
could support MIG240.
Darfon Electronics Corp.
Troubleshooting - Verify that the AC voltage and frequency
Red light sparking:
Grid voltage or frequency is abnormal.
You have to check
1)The voltage of grid should be 240Vac and 60Hz.
If it’s out of the range showed as table 1, then
it’s the problem of power system, and all you
can do is waiting…
2)You have to check the connection between
trunk cable and grid. You have to make sure
the voltage between red wire and black wire
is closed to 240Vac.
240 Volt AC Single Phase
L1 to L2
211 to 264 VAC
L1, L2 to neutral
106 to 132 VAC
Darfon Electronics Corp.
Troubleshooting - Grounding
Independent
Independent
Connected at the AC Box
Darfon Electronics Corp.
Troubleshooting - Grounding
PLC box (Power line communication Box)
Green means power on
No light means power off
- Check if AC cable of PLC box is
connected well
Orange means RS485 between data
logger and PLC is good.
No light means no communication
between data logger and PLC Box
- Check the RS485 line is connected
well
Strength of the signal between PLC Box and inverter
This means weak signal
This means strong signal
This means no any signal
- Check the connection between PLC & Inverter
Darfon Electronics Corp.
Troubleshooting - Grounding
Maximum Distance = 400 meters
Notice: need for CAT5 wires
TT+
Darfon Electronics Corp.