MONITOR / NOZZLE PACKAGES
MONITOR / NOZZLE PACKAGES
MONITOR / NOZZLE PACKAGES
SECTION INDEX
Foam Application Method.............................................................................. F2-F4
FootPrint™ Methodology............................................................................... F5-F6
Minimum Firewater Requirements for Foam Application Full Surface Protection......................................................................................... F7
Minimum Firewater Requirements for Foam Application 1% Foam Concentrate............................................................................................ F8
Minimum Firewater Requirements for Foam Application 3% Foam Concentrate....................................................................................... F9
“Big Foot” Trailer Mount 4,000 - 14,000 GPM......................................... F10-F12
Battler 2 x 10 Monitor / Nozzle.........................................................................F13
Ambassador 1 x 6 Monitor/Nozzle....................................................................F14
Ranger3™ ..............................................................................................................F15
Hired Gun Trailer - 2000 GPM............................................................................F16
Hired Gun Layout..................................................................................................F17
Patriot Ranger3™/ “Quick Action” Deck Gun, 1000-3000 GPM...................F18
Gear Operated 6” Monitor..................................................................................F19
Patriot 1- “Worm Gear” Deck Gun, 1000 GPM.............................................. F20
1.5 HC Ranger™ 250-1500 Deck Gun................................................................ F21
PRODUCTS 409-745-3232
F1
WWW.WILLIAMSFIRE.COM
120108
EMERGENCY 409-727-2347
MONITOR / NOZZLE PACKAGES
MONITOR / NOZZLE PACKAGES
Storage Tank Protection
Foam Application Method: High Volume Foam
Application
(Design Reference NFPA 11)
General High Volume Foam Monitors (fixed or transportable) are effective tools for protecting storage tanks containing flammable or combustible
liquids. Foam monitors can be considered as the primary means of fire suppression for full service foam application onto open floating roof
storage tanks, or onto “fixed roof” tanks of up to 60 ft. in diameter. For fixed roof storage tanks greater than 60 ft. diameter, foam monitors
can be considered as a viable backup system, to be used in the event that the primary foam fire protection system is rendered inoperable or
unavailable.
Cone Roof Tank
Covered Floating
Roof Tank
Open Floating
Roof Tank
Minimum Foam Application Rates Stated minimum foam application rates are based on the assumption that all foam reaches the interior of the tank, or “landing zone”.
Also, these minimum rates are for tanks 180 ft. in diameter or less. For tanks greater than 180 ft. diameter, consult with your Williams Fire
& Hazard Control, Inc® representative for current data regarding recommendations for minimum ThunderStorm® foam application rates
on specific fuels.
PRODUCTS 409-745-3232
F2
WWW.WILLIAMSFIRE.COM
120108
EMERGENCY 409-727-2347
MONITOR / NOZZLE PACKAGES
MONITOR / NOZZLE PACKAGES
Storage Tank Protection
High Volume Foam Monitors
Design Considerations
Minimum Application Densities
To use the chart, first look up the liquid’s flash point
and its water solubility. Determine their point of intersection and zone on the chart. Then refer to the data below
to determine the minimum application density. Examples
of common flammable liquids are listed in each category.
Flash point and solubility data on additional flammable
liquids can be found in the NFPA Hazardous Materials
Handbook and in other similar sources.
Type of Fuel
Foam
Minimum Application
Density, gpm/ft2
Combustible Liquids
(flash point <100˚ F)
F-601A ATC @ 1%
0.16
Flammable Liquids
(flash point >100˚ F)
F-601A ATC @ 1%
0.16
Crude Petroleum
F-601A ATC @ 1%
0.16
Gasohol
F-601A ATC @ 1%
0.16
Category B
F-601A ATC @ 3%
.13
Category C
F-601A ATC @ 3%
*.13
Category D
F-601A ATC @ 3%
*.13
Hydrocarbons - Category A
Water Miscibles - Category B,C,D
(Alcohols)
* Contact Williams Fire & Hazard Control, Inc® for recommendations regarding application densities for specific fuels — Telephone 409-727-2347
PRODUCTS 409-745-3232
F3
WWW.WILLIAMSFIRE.COM
120108
EMERGENCY 409-727-2347
MONITOR / NOZZLE PACKAGES
MONITOR / NOZZLE PACKAGES
Storage Tank Protection
High Volume Foam Monitors
Design Considerations
Determining Water/Foam Requirments
Calculating the area of a circle: πr2 = ft2
FT2 x *Application Rate = GPM Water/Foam Solution
GPM Water/Foam Sol. x % Concentrate = GPM Foam Concentrate.
GPM Foam Concentrate x Recommended Duration (NFPA 11) = Total Gallons of Concentrate required on scene
*Application Rate per Square Foot
NFPA 11 recommends a minimum 0.16 gpm/ft2 application rate for Type III.
Although 0.16 is a minimum much of the industry uses it as a standard.
Williams Fire & Hazard Control recognizes as the tank diameter increases, increasing the application rate must be considered.
Williams’ Recommended Type III Application Rates For Hydrocarbon Storage Tanks
0’
151’
201’
251’
300’
+
150’
200’
250’
300’
0.16
0.18
0.20
0.22
0.25
GPM/Ft2
GPM/Ft2
GPM/Ft2
GPM/Ft2
GPM/Ft2
Example calculation for a 150’ Storage tank:
75 x 75 x 3.14 = 17,662.5 ft2
17,662.5 x .16 = 2,826 gallons per minute required flow
(2,826 GPM would practically be rounded up to 3,000 GPM)
3,000 GPM x .01% concentrate = 30.0 gallons concentrate per minute
30.0 Gal/concentrate for 65 minutes = 1,950 total gallons concentrate required (minimum)
Add 100% for reserve inventory (if required)
Minimum Foam Application Durations
Combustible Liquids (flash point < 100˚ F) Flammable Liquids (flash point > 100˚ F) Crude Oils
Alcohols
=
=
=
=
50
65
65
65
minutes
minutes
minutes
minutes
Minimum Foam Concentrate Inventories
Calculation for minimum foam inventory is (where D = Tank Diameter):
Minimum Foam Inventory =
(D x D) x 0.785 x (Min Application Density) x (% Proportioning) x (Application Duration)
Example calculation for an 80’ Diameter Tank in Crude Oil Service:
(80 x 80) x 0.785 x 0.16 x .03 x 65
Add for 100% Reserve Inventory (if required)
Total Minimum Foam Inventory
PRODUCTS 409-745-3232
1568 gallons
+ 1568 gallons
3136 gallons
F4
WWW.WILLIAMSFIRE.COM
120108
EMERGENCY 409-727-2347
MONITOR / NOZZLE PACKAGES
MONITOR / NOZZLE PACKAGES
Storage Tank Protection
FootPrint™ Methodology
For US and Foreign Patent and Trademark information, please refer to page PI2
PRODUCTS 409-745-3232
F5
WWW.WILLIAMSFIRE.COM
120108
EMERGENCY 409-727-2347
MONITOR / NOZZLE PACKAGES
MONITOR / NOZZLE PACKAGES
Storage Tank Protection
FootPrint™ Methodology
US Patents
For use of FootPrint™ methodology,
®
please contact Williams Fire & Hazard Control, Inc
For US and Foreign Patent and Trademark information, please refer to page IP2
PRODUCTS 409-745-3232
F6
WWW.WILLIAMSFIRE.COM
120108
EMERGENCY 409-727-2347
MONITOR / NOZZLE PACKAGES
MONITOR / NOZZLE PACKAGES
Storage Tank Protection
Minimum Firewater Requirements for Foam Application Full Surface Protection
Tank Minimum Firewater Flow Rates (gpm)*
Diam
(Feet)
— Application Densities*** — Minimum Firewater Capacities Required
for 65 Minute Application (gallons)**
— Application Densities*** —
.16
.18
.20
.22
.25
.16
.18
.20
.22
.25
50
315
354
393
432
491
20475
23010
25545
28080
31915
60
453
509
566
622
707
29445
33085
36790
40430
45955
70
616
693
770
847
962
40040
45045
50050
55055
62530
80
804
905
1005
1106
1256
52260
58825
65325
71890
81640
90
1018
1145
1272
1399
1590
66170
74425
82680
90935
103350
100
1256
1413
1570
1727
1963
81640
91845
102050
112255
127595
110
1520
1710
1900
2090
2375
98800
111150
123500
135850
154375
120
1809
2035
2261
2487
2826
117585
132275
146965
161655
183690
130
2123
2389
2654
2919
3317
137995
155285
172510
189735
215605
140
2462
2770
3078
3385
3847
160030
180050
200070
220025
250055
150
3180
3533
3886
4416
206700
229645
252590
287040
160
3618
4020
4422
5024
235170
261300
287430
326560
170
4084
4538
4992
5672
265460
294970
324480
368680
180
4579
5089
5596
6359
297635
330785
363740
413335
190
5101
5668
6235
7085
331565
368420
405275
460525
200
5652
6280
6908
7850
367380
408200
449020
510250
210
6924
7617
8655
450060
495105
562575
220
7599
8359
9499
493935
543335
617435
230
8306
9136
10381
539890
593840
674765
240
9044
9948
11304
587860
646620
734760
250
9813
10794
12266
637845
701610
797290
260
10614
11675
13267
689910
758875
862355
270
11446
12590
14307
743990
818350
929955
280
12309
13540
15386
800085
880100
1000090
290
13204
14525
16505
858260
944125
1072825
300
14130
15543
17663
918450
1010295
1148095
PRODUCTS 409-745-3232
F7
WWW.WILLIAMSFIRE.COM
120108
EMERGENCY 409-727-2347
MONITOR / NOZZLE PACKAGES
MONITOR / NOZZLE PACKAGES
Storage Tank Protection
Minimum Requirements for 1% Foam Concentrate Full Surface Protection Using High Volume Monitors*
Tank
Diam
(Feet)
50 Minutes
(Flash Point > 100˚ F)
65 Minutes
(Flash Point < 100˚ F)
— Application Densities ** — — Application Densities ** —
.16
.18
.20
.22
.25
.16
.18
.20
.22
.25
50
160
180
200
220
250
205
235
260
285
320
60
230
255
285
315
355
295
335
370
405
460
70
310
350
385
425
485
405
455
505
555
630
80
405
455
505
555
630
525
590
655
720
820
90
510
575
640
700
795
665
745
830
910
1035
100
630
710
785
865
985
820
920
1025
1125
1280
110
760
855
950
1045
1190
990
1115
1235
1360
1545
120
905
1020
1135
1245
1415
1180
1325
1470
1620
1840
130
1065
1195
1330
1460
1660
1380
1555
1730
1900
2160
140
1235
1385
1540
1695
1925
1605
1805
2005
2205
2505
150
1590
1770
1945
2210
2070
2300
2530
2875
160
1810
2010
2215
2515
2355
2615
2875
3270
170
2045
2270
2500
2840
2655
2950
3245
3690
180
2290
2545
2800
3180
2980
3310
3610
4135
190
2555
2835
3120
3545
3320
3685
4055
4610
200
2830
3140
3455
3925
3675
4082
4495
5105
210
3465
3810
4330
4505
4955
5630
220
3800
4180
4750
4940
5435
6175
230
4155
4570
5195
5400
5940
6750
240
4525
4975
5655
5880
6470
7350
250
4910
5400
6135
6380
7020
7975
260
5310
5840
6635
6900
7590
8625
270
5725
6295
7155
7440
8185
9300
280
6155
6770
7695
8055
8805
10005
290
6605
7265
8255
8585
9445
10760
300
7065
7775
8835
9185
10105
11485
Formula: (Tank Diameter)2 x 0.785 x Application Density x 0.01 x Duration (in minutes)
Based on NFPA 11, Hydrocarbon Fuels
*Does not include post extinguishment suppression
**Application Densities indicated as gpm/ft2
PRODUCTS 409-745-3232
F8
WWW.WILLIAMSFIRE.COM
120108
EMERGENCY 409-727-2347
MONITOR / NOZZLE PACKAGES
MONITOR / NOZZLE PACKAGES
Storage Tank Protection
Minimum Requirements for 3% Foam Concentrate Full Surface Protection Using High Volume Monitors*
Tank
Diam
(Feet)
50 Minutes
(Flash Point > 100˚ F)
65 Minutes
(Flash Point < 100˚ F)
— Application Densities ** — — Application Densities ** —
.16
.16
.18
.20
.22
.25
.16
.18
.20
.22
.25
50
480
540
600
660
750
615
705
780
855
960
60
690
765
855
945
1065
885
1005
1110
1215
1380
70
930
1050
1155
1275
1455
1215
1365
1515
1665
1830
80
1215
1365
1515
1665
1890
1575
1770
1965
2160
2460
90
1530
1725
1920
2100
2385
1995
2235
2490
2730
3105
100
1890
2130
2355
2595
2955
2460
2760
3075
3375
3840
110
2280
2565
2850
3135
3570
2970
3345
3705
4080
4635
120
2715
3060
3405
3735
4245
3540
3975
4410
4860
5520
130
3195
3585
3990
4380
4980
4140
4665
5190
5700
6480
140
3705
4155
4620
5085
5775
4815
5415
6015
6615
7515
150
4770
5310
5835
6630
6210
6900
7590
8675
160
5430
6030
6645
7545
7065
7845
8625
9810
170
6135
6810
7500
8520
7965
8850
9735
11070
180
6870
7635
8400
9540
8940
9930
10830
12405
190
7665
8505
9360
10635
9960
11055
12165
13830
200
8490
9420
10365
11775
11025
12246
13485
15315
210
10395
11430
12990
13515
14865
16890
220
11400
12540
14250
14820
16305
18525
230
12465
13710
15585
16200
17820
20250
240
13575
14925
16965
17650
19410
22050
250
14730
16200
18405
19140
21048
23925
260
15930
17520
19905
20700
22770
25875
270
17175
18885
21465
22320
24555
27900
280
18465
20310
23085
24165
26415
30015
290
19815
21795
24765
25755
28322
32184
300
21195
23325
26505
27555
30315
34455
Formula: (Tank Diameter)2 x 0.785 x Application Density x 0.03 x Duration (in minutes)
Based on NFPA 11, Hydrocarbon Fuels
*Does not include post extinguishment suppression
**Application Densities indicated as gpm/ft2
PRODUCTS 409-745-3232
F9
WWW.WILLIAMSFIRE.COM
120108
EMERGENCY 409-727-2347
MONITOR / NOZZLE PACKAGES
MONITOR / NOZZLE PACKAGES
Monitor / Nozzle Packages
Product Detail:
“Big Foot” Trailer Mount 4,000 - 14,000 GPM
The Williams “Big Foot “ Multi-Flow High-Volume Monitor is designed for the
extinguishment of massive petrochemical fires. The nozzle is constructed of all corrosion resistant materials, such as anodized aluminum, stainless steel, and composite
plastics, and is capable of flows ranging from 4,000 - 14,000 GPM. The nozzle is
available with six separate stems in increments of 2,000 GPM each. The nozzle is
the self educting type, incorporating patented Hydro-Foam™ technology. Foam concentrate is supplied via remote jet ratio controllers, or
foam solution can be delivered from an independent proportioning system directly to the water inlets. The nozzle is constant flow, with straight
stream to full fog capabilities.
The trailer meets all applicable DOT regulations and is constructed of deep channel carbon steel. Ballast tanks are an integral part of the
trailer, providing stability and traction to counteract nozzle reaction forces. The internal water inlet manifold is constructed of 10” I.D. stainless
steel. Eight (8) ea., 5” storz (6” optional) inlet connections with caps are provided for water-foam solution supply. The full system capacity of
14,000 gpm requires a total of ten (10) 5” storz inlets. Each connection is protected from back flow using a six inch (6”) full flow wafer check
valve. Two (2) ea., 4” inlets are provided (one each side) for foam concentrate supply. The tandem axle trailer has a gross vehicle weight rating
(GVWR) of 14,000 lbs. Mechanical/hydraulic surge brakes are activated via a heavy duty coupler terminating in a pintle hook connection. The
tongue is connected rigidly to the trailer using an A-frame arrangement for maximum stability. Non-skid designed upper decking. Stabilizing
jacks are provided at four points, providing maximum stability.
An operators panel is located aft of the nozzle. The elevated operating position provides a full view of fire ground operations. All controls
are manual gear operated and utilize state-of-the-art hydraulic systems to control vertical travel (+15º to +45º), horizontal traverse (from 15º
right/left of center), and nozzle fog/straight stream pattern.
Standard Trim and Accessories:
•
•
•
•
•
•
•
•
•
•
•
2
4
4
1
1
1
1
1
1
1
1
ea.- Concentrate “Jumper” Hose 4” x 10 ft. coupled storz
ea.- Jet Ratio Controllers 2.0 JP60
ea.- Drum Kits for Jet Ratio Controllers
ea.- Jet pump selection char t
ea.- nozzle flow char t
ea.- 4000 GPM stem
ea.- 6000 GPM stem
ea.- 8000 GPM stem
ea.- 10,000 GPM upgrade option
ea.-12,000 GPM upgrade option
ea.-14,000 GPM upgrade option
Big Foot- Trailer Mount
Nominal Flow @ 100 PSI
12,000 gpm
Nominal Range @ 100 PSI (straight stream)
@ 4,000 GPM
330 ft.
@ 6,000 GPM
350 ft.
@ 8,000 GPM
360 ft.
@ 10,000 GPM
390 ft.
@ 12,000 GPM
400 ft.
@ 14,000 GPM
430 ft.
Water Inlets (standard)
Eight (8) 5” storz
Foam Concentrate Inlet
Two (2) 4” storz
K- Factor, Maximum Flow
1400
For US and Foreign Patent and Trademark information, please refer to page IP2
PRODUCTS 409-745-3232
F10
WWW.WILLIAMSFIRE.COM
120108
EMERGENCY 409-727-2347
MONITOR / NOZZLE PACKAGES
MONITOR / NOZZLE PACKAGES
Hydro-Foam™ Technology
“Big Foot” Trailer Mount 4,000 - 14,000 GPM
5” Storz Inlet
(Optional)
*Two Optional inlets required for flows from 10,000 gpm to 14,000 gpm.
For US and Foreign Patent and Trademark information, please refer to page IP2
PRODUCTS 409-745-3232
F11
WWW.WILLIAMSFIRE.COM
120108
EMERGENCY 409-727-2347
MONITOR / NOZZLE PACKAGES
MONITOR / NOZZLE PACKAGES
Hydro-Foam™ Technology
(8) 5” Water Supply
Hoses
(4)
“Big Foot” Hose Lay - For up to 8,000 GPM
For US and Foreign Patent and Trademark information, please refer to page IP2
PRODUCTS 409-745-3232
F12
WWW.WILLIAMSFIRE.COM
120108
EMERGENCY 409-727-2347
MONITOR / NOZZLE PACKAGES
MONITOR / NOZZLE PACKAGES
Monitor / Nozzle Packages
Product:
Battler 2 x 10 Monitor / Nozzle
Description:
The “Battler” Monitor/Nozzle Trailer Unit is capable of large volume
discharge to elevations never before attained by conventional equipment to provide fire suppression, cooling, personnel protection, toxic gas
dispersion and more. Discharge flow rates from 2000-10,000 USGPM
(7571-37854 LPM) can be water or Hydro-Foam™ for extinguishing
liquids. All this and the operator is still afforded the freedom of smooth,
rapid horizontal and vertical movement and unsurpassed articulation
of 360˚ that only the “Battler” can provide, raising this monitor/nozzle
“above” all others.
Advancing the Fire Fighter’s Ability with
Equipment and Knowledge.
This “Hybrid” nozzle has the unique capability to perform as an automatic pressure or fixed gallonage nozzle. During automatic operation
the nozzle will respond to varying flows to maintain a nearly constant tip pressure, thus maximizing effective range for a given discharge flow.
Once the nozzle reaches the fixed gallonage set point (2000-10,000 GPM), it performs as a conventional fixed gallonage nozzle. This is desirable
for foam proportioning operations on storage tank fires or other hazards requiring specific application rates. This nozzle is capable of HydroFoam™ proportioning at rates up to 10,000 GPM @ 1% (8000 GPM @ 3%) using remote jet pump technology. The single 10” stainless steel
waterway construction provides minimum friction loss, maximum efficiency, and years of trouble-free service. The “user-friendly” gear operated
controls provide full monitor articulation of 360˚ rotation and down to +15˚ and up to +75˚ vertical travel with a minimal of input effort. Pattern
control from straight stream to full fog is accomplished via a full wrap-around handle attached to the outer sleeve.
Standard Features:
Dual Mode Automatic/Fixed Operation
Fixed Gallonage plugs: 2K, 4K, 6K, 8K, 10K
Hydro-Foam™ Capable Nozzle
Efficient Single 10” SS Monitor
Dual Handwheel Controls for Pan & Tilt
Wrap-around handle design for pattern control
Tandem axle trailer
Integral 12” stainless steel manifold
Five 5” clappered storz inlets w/caps
2.0” ball fixed height hydraulic surge coupler
Large operator’s deck surface (8’ x 11’)
Anti-skid grip surface
Four point trailer jacks plus tongue jack
Standard grade Red Finish
Options:
6” clappered storz inlets in lieu of standard (nine)
2.0JP60 Jet Pump w/Metering Valve & Stinger (four)
4-2.5” FNST x 4.0” MNPSH Siamese Jet Pump Manifold
15’ x 4” ID Non-collapsible Jet Pump Supply Hose
2.5’ ” FNST x 2-1.5” MNST Gated Wyes for Jet Pump Feed (two)
European adjustable tow bar
European lighting package
Radio remote controlled electric/hydraulic/monitor controls
Premium (show grade) paint & finish
For US and Foreign Patent and Trademark information, please refer to page IP2
PRODUCTS 409-745-3232
F13
WWW.WILLIAMSFIRE.COM
120108
EMERGENCY 409-727-2347
MONITOR / NOZZLE PACKAGES
MONITOR / NOZZLE PACKAGES
Ambassador 1 x 6 Monitor/Nozzle
Advancing the Fire Fighter’s Ability with
Equipment and Knowledge.
Description:
This “Hybrid” nozzle has the unique capability to perform as an automatic
pressure or fixed gallonage nozzle. During automatic operation the nozzle will
respond to varying flows to maintain a nearly constant tip pressure, thus maximizing effective range for a given discharge flow. Once the nozzle reaches the fixed
gallonage set point (1000-6000 GPM), it performs as a conventional fixed gallonage nozzle. This is desirable for foam proportioning operations on storage tank
fires or other hazards requiring specific application rates. This nozzle is capable of Hydro-Foam™ proportioning at rates up to 6000 GPM @
3% (3000 GPM @ 6%) using remote jet pump technology. The extensive “Ambassador” options list allows this nozzle to be Hydro-Chem™
capable with PKW flow rates from 25 lbs/s to 100 lbs/s. The single 8” full flow stainless steel waterway construction provides minimum friction
loss, maximum efficiency, and years of trouble-free service. The standard tiller-bar control provides full monitor articulation of 360˚ rotation
and down to -15˚ and up to +75˚ vertical travel. Pattern control from straight stream to full fog is accomplished via a full wrap-around handle
attached to the outer sleeve.
Standard Features:
Dual Mode Automatic/Fixed Operation
Fixed Gallonage plugs:1K,2K,3K,4K,5K,6K
Hydro-Foam™ Capable Nozzle
Efficient Single 8” SS Monitor
Tiller-bar control
Wrap-around handle design for pattern control
Tandem axle trailer
Integral 8” carbon steel manifold
Five 5” non-clappered storz inlets w/caps
2.0” ball fixed height hydraulic surge coupler
Anti-skid grip surface
Four point trailer jacks plus tongue jack
Standard grade Red Finish
Options:
Hydro-Chem™ Tip conversion
Choke tubes (25, 50, 75 & 100 lbs./s)
Dry chemical manifolds (4,6,7, & 10 inlets)
*See Pages J10-J12
1.5JP30 Jet Pump w/stinger (one)
2.0JP60 Jet Pump w/stinger (three)
3-2.5” FNST x 3.0” MNPSH Siamese
1-2.5” FNST x 3-1.5” MNST Wye
10” SS integral manifold w/6-5” Storz inlets
Internal 5” clappers
European adjustable tow bar
European lighting package
Gear operated monitor controls (vertical & horizontal)
Radio remote controlled electric/hydraulic/gear monitor controls
1-5” x 2-5” Jumbo Siamese (recommended w/std 8” manifold)
Premium (show grade) paint & finish
3” x 15’ Dry Chemical Hose
3” Valved Siamese w/extra hoses for 100 lbs./s “PKW™”
For US and Foreign Patent and Trademark information, please refer to page IP2
PRODUCTS 409-745-3232
F14
WWW.WILLIAMSFIRE.COM
120108
EMERGENCY 409-727-2347
MONITOR / NOZZLE PACKAGES
MONITOR / NOZZLE PACKAGES
Monitor / Nozzle Packages
Product:
Ranger3™
Description:
“The Ranger™”, featuring “Smart Nozzle” Technology, was designed for
today’s Industrial fire fighting and protection needs. Hazards involving flammable
liquids in storage and liquids under pressure have met their match with the New
Millennium Equipment from Williams Fire & Hazard Control, Inc®.
The “Ranger™” monitor/nozzle combination is capable of not only selfeducting foam concentrate, but can do so while maintaining a nearly constant
pressure (+/- 10%) and a constant foam percentage (1% or 3% selectable) regardless of the flow rate. Discharge flow rates from 1000-3000
USGPM (3800-11356 LPM) can be water only, Hydro-Foam™ (using jet pumps or automatic constant/selectable metering) or Hydro-Chem™
for extinguishing liquids and gases under pressure. All this and the operator is still afforded the freedom of smooth, rapid horizontal and vertical
movement that only the “Ranger™” can provide, raising this monitor/nozzle “above” all others.
This “Hybrid” nozzle has the unique capability to perform as an automatic pressure or fixed gallonage nozzle. During automatic
operation the nozzle will respond to varying flows to maintain a nearly constant tip pressure, thus maximizing effective range for a
given discharge flow. Once the nozzle reaches the fixed gallonage set point (1000-3000 GPM), it performs as a conventional fixed gallonage nozzle. This is desirable for foam proportioning operations on storage tank fires or other hazards requiring specific application
rates. This nozzle is capable of Hydro-Foam™ proportioning at rates up to 3000 GPM @ 3%. It can automatically maintain a nearly
constant foam percentage (1% or 3%) throughout the entire flow range while self-educting. It can optionally be configured to proportion foam from remote locations using jet pump technology (thus forfeiting the constant/selectable metering feature). The extensive “Ranger™” options list allows this nozzle to be Hydro-Chem™ capable (without Hydro-Foam™ capability) with “PKW™” flow
rates from 25 lbs/s to 50 lbs/s. The single 6” full flow stainless steel waterway construction provides minimum friction loss, maximum
efficiency, and years of trouble-free service. The standard tiller-bar control provides full monitor articulation of 360˚ rotation and down to
-15˚ and up to +75˚ vertical travel. Pattern control from straight stream to full fog is accomplished via a full wrap-around handle attached to
the outer sleeve.
Standard Features List:
Options:
Dual Mode Automatic/Fixed Operation
Fixed Gallonage plugs: 1K, 2K, 3K
Hydro-Foam™ Constant/Selectable
1% or 3% Nozzle
Efficient Single 6” SS Monitor
Tiller-bar control
Wrap-around handle design for pattern control
Tandem axle trailer
Integral 8” carbon steel manifold
Three 5” non-clappered storz inlets w/caps
2.0” ball fixed height hydraulic surge coupler
Anti-skid grip surface
Four point trailer jacks plus tongue jack
Standard grade Red Finish
Hydro-Chem™ Tip conversion
Choke tubes (25 or 50 lbs/s)
Dry chemical manifolds (4 inlet or 7 inlet)
*See Pages J10-J12
1.5JP30 Jet Pump w/stinger (one)
2.0JP60 Jet Pump w/stinger (one)
3-2.5” FNST x 3.0” MNPSH Siamese
(Jet to Monitor Supply)
1-2.5’” FNST x 3-1.5” MNST Wye
(Jet Pump Supply)
8” SS integral manifold w/3-5” Storz inlets
8” SS integral manifold w/2-6” Storz inlets
Internal 5” or 6”clappers
European adjustable tow bar
European lighting package
Gear operated monitor controls
(vertical & horizontal)
Radio remote controlled electric/hydraulic/gear
monitor controls
Premium (show grade) paint & finish
2.5” x 10’’ Dry Chemical Hose
For US and Foreign Patent and Trademark information, please refer to page IP2
PRODUCTS 409-745-3232
F15
WWW.WILLIAMSFIRE.COM
120108
EMERGENCY 409-727-2347
MONITOR / NOZZLE PACKAGES
MONITOR / NOZZLE PACKAGES
Monitor / Nozzle Packages
Product:
“Hired Gun” Trailer - 2000 GPM
Description:
This Trailer Mounted System delivers 2000 gpm of water or foam solution @
100 psi. Hard anodized nozzle with fog/straight stream adjustment. Foam solution
is proportioned through one matched Jet Ratio Controller. Monitor is constructed
of 6” stainless steel epoxy coated, gear operated, with pressure gauge. Dual
handwheel control, horizontal and vertical positions. Heavy duty trailer includes:
diamond plate deck; tool box; and trailer hitch. Water inlet trim includes; 5” storz
clappered dual inlet siamese; 5” x 10 ft. hose coupled storz. Trailer is equipped with adjustable jacks for stability.
2” BALL COUPLER STANDARD
(ELECTRIC OR SURGE BRAKES OPTIONAL)
Hired Gun
Trailer Mount
Nominal Flow @ 100 PSI
2000 gpm
Nominal Range @ 100 PSI
(straight stream)
235 ft.
Water Inlet
5” storz
Foam Concentrate Inlet
2.5” NH (F) Swivel
Horizontal Rotation
360º
Ver tical Travel
0º to 85º
Propor tioning
1% or 3%
K-Factor
200
For US and Foreign Patent and Trademark information, please refer to page IP2
PRODUCTS 409-745-3232
F16
WWW.WILLIAMSFIRE.COM
120108
EMERGENCY 409-727-2347
MONITOR / NOZZLE PACKAGES
MONITOR / NOZZLE PACKAGES
Monitor / Nozzle Packages
1. USE ONE JET RATIO CONTROLLER (2.0 JP60) FOR 3% @ 2000 GPM.
2. USE TWO JET RATIO CONTROLLERS (2.0 JP60) FOR 6% @ 2000
GPM.
NOTE:
JET RATIO
CONTROLLER
(2.0) JP60
1.5” INLET X 2.5”
DISCHARGE
CLAPPERED JUMBO
SIAMESE
Typical Hired Gun Layout
For US and Foreign Patent and Trademark information, please refer to page IP2
PRODUCTS 409-745-3232
F17
WWW.WILLIAMSFIRE.COM
120108
EMERGENCY 409-727-2347
MONITOR / NOZZLE PACKAGES
MONITOR / NOZZLE PACKAGES
Hydro-Chem™ Monitor / Nozzle Package
Product:
Patriot Ranger3™
“Quick Action” Deck Gun, 1000-3000 GPM
Description:
Hydro-Chem™ Monitor system includes: fog/straight stream constant pressure/
variable flow nozzle delivering from 1000 to 3000 gpm of foam solution @ 100 psi and
40 lb./sec of dry chemical (nominal flow). Foam solution is proportioned through one
matched Jet Ratio Controller. Monitor is constructed of stainless steel with red epoxy
finish. Nozzle is constructed of hard anodized aluminum alloy with stainless steel trim.
Equipped with quick action handle for fast, positive control. System includes: valved dry
chemical six inlet manifold; dry chemical inlet hose.
Patriot Ranger3™
Deck Gun “Quick Action”
Nominal Flow @ 100 PSI
1000, 2000 or 3000 gpm
K-Factors @ 100 psi
Variable 100, 200, 300
Nominal Range of dry chemical
100 ft.
Foam Concentrate Inlet
2.5” NPT (M)
Dry Chemical Inlet Nozzle
2” NPT (M) Valved
Water Inlet
6” 150# flange
Ver tical Travel
0º to +80º
Horizontal Rotation
360º
For US and Foreign Patent and Trademark information, please refer to page IP2
PRODUCTS 409-745-3232
F18
WWW.WILLIAMSFIRE.COM
120108
EMERGENCY 409-727-2347
MONITOR / NOZZLE PACKAGES
MONITOR / NOZZLE PACKAGES
Monitor / Nozzle Packages
Product:
Gear Operated 6” Monitor
Description:
This Fixed Mounted System delivers from 1000 to 3000 gpm of water or foam solution @ 100 psi. Hard anodized constant pressure/variable flow nozzle with fog/straight
steam adjustment. For remote application, 1% or 3% foam solution is proportioned
through one matched Jet Ratio Controller. Worm gear operated 6” waterway monitor
is constructed of stainless steel with stainless steel swivels. Dual handwheels control
horizontal and vertical positions.
Patriot Ranger3™
Nominal Flow @100 psi
1000, 2000 or 3000 gpm
Water inlet
6” Flange
Foam Concentrate Inlet
2.5” NPT(M)
Horizontal Rotation
360º
Ver tical Travel
0º to +90º
Propor tioning without jet
1% or 3%
K-Factor (@ 100 psi)
100, 200 or 300
PRODUCTS 409-745-3232
F19
WWW.WILLIAMSFIRE.COM
120108
EMERGENCY 409-727-2347
MONITOR / NOZZLE PACKAGES
MONITOR / NOZZLE PACKAGES
Hydro-Chem™ Monitor / Nozzle Package
Product:
Patriot 1- “Worm Gear” Deck Gun, 1000 GPM
Description:
Hydro-Chem™ Monitor system, includes fog/straight stream nozzle, delivering 1000 gpm of foam solution @ 100 psi and 20 lb./sec of dry chemical (nominal
flow). Foam solution is proportioned through one 1.5 JP30 Jet Ratio Controller. Dual
handwheel 4” monitor is fabricated of stainless steel with red epoxy finish. “Dual
Wafer” Nozzle is constructed of hard anodized aluminum alloy with stainless steel
trim. System includes: valved dry chemical four inlet manifold; dry chemical inlet hose,
1.5” x 15 ft.
Patriot 1 Deck Gun
“Worm Gear”
Nominal flow @ 100 PSI
1000 gpm
K-Factor
100
Nominal Range of dry chemical
100 ft.
Foam Concentrate Inlet
2” NPT (M)
Dry Chemical Inlet Nozzle
1.5” Valved
Water Inlet
4” 150# flange
Ver tical Travel
-10º to +90º
Horizontal Rotation
360º
For US and Foreign Patent and Trademark information, please refer to page IP2
PRODUCTS 409-745-3232
F20
WWW.WILLIAMSFIRE.COM
120108
EMERGENCY 409-727-2347
MONITOR / NOZZLE PACKAGES
MONITOR / NOZZLE PACKAGES
Hydro-Chem™ Monitor / Nozzle
Package
Product:
1.5 HC Ranger™ 250-1500 Deck Gun
Description:
Hydro-Chem™ Monitor System, includes fog/straight stream constant
pressure/variable flow nozzle, delivering from 250 gpm to 1500 gpm of foam
solution @ 100 psi and 20 lb./sec of dry chemical (nominal flow). Foam solution
is proportioned through one matched Jet Ratio Controller. Monitor is constructed of stainless steel with red epoxy finish. “Big Body Nozzle”
is constructed of hard anodized aluminum alloy with stainless steel trim. Equipped with “quick action” handle for fast, positive control. System
includes: valved dry chemical four inlet manifold; dry chemical inlet hose, 1.5” X15 ft.
Patriot Ranger™ Deck Gun
Nominal Flows
Variable (250-1500 GPM)
Nominal Flow @ 100 PSI
1500 gpm
K-Factor
150
Nominal Range of dry chemical
100 ft.
Dry Chemical Inlet Nozzle
1.5” Valved
Water Inlet
4” 150# flange
Ver tical Travel
-25º to +80º
Horizontal Rotation
360º
For US and Foreign Patent and Trademark information, please refer to page IP2
PRODUCTS 409-745-3232
F21
WWW.WILLIAMSFIRE.COM
120108
EMERGENCY 409-727-2347