CPU Facility Card - ses

Transcription

CPU Facility Card - ses
2401-CCPPUU FFaacciilliittyy CCaarrdd
P
P
L
C
PL
LC
C IIInnnttteeegggrrraaattteeeddd
The 2401 control unit manages the entire F&G/ESD 2400 system, aimed for both
detection and activation of F&G field signals through I/O modules.
The system is set up by dedicated boards in order to detect:
• Flame presence
• Smoke presence
• Combustible, Toxic Gas presence, etc.
• Digital signals, pushbuttons, etc.
• Field signal activation like Electric Valves, Horns, Lamp, synoptic panels etc.
The system F&G/ESD 2400, set up by the 2401-CPU Facility Card and by multiplechannel Input/Output boards (supervised or not) is designed for different redundancy
levels from a single signal to all boards, depending on the different safety
requirements needed on each plant.
Programming the 2401-CPU Facility Card using the information necessary to
manage present signals configures in system. These informations are:
• Type and number of signals to be detected
• Number of detection cards (smoke, gas, flame)
• Number of digital I/O cards
The configuration information for the entire system and the application software,
which execute the logical output activation are stored in a temporary RAM
The system control and management are based on a 16-bit 80186 microprocessor,
carrying out, briefly and these functions:
• Management of the serial communications with all of the I/O 2400 controller
• Management of the activation logic through an equation-based programming
• Ensures the safe control of the equipment through redundancy management
The system structure is designed to manage different safety levels, therefore it
includes the 2401-CPU Facility Card redundancy as well as the redundancy of any
I/O signal it should manage. The board is provided with a clock/calendar (with
internal battery) which maintains updated date and time on event printouts and
diagnostics. The 2401-CPU Facility Card is provided with a basic software on RAM
(with battery back-up), including a multitasking operating system which allows the
application software (stored in a buffered 196 kb RAM) to best use the system
resources. The 2401-CPU Facility Card is based on a 16 bit INTEL Microprocessor
80186 with 64/128 Kbytes of EPROM for firmware and operating system and 512
Kbytes Ram for working include 192 Kbytes Ram for application program.
The facility is equipped with resident software “firmware” containing a multitasking
operating system which optimised the microprocessor features.
Four serial lines are provided as follow:
The first one is RS485-FD (double), in Redundant configuration at baud-rate 38400
used for the communication with I/O cards. The 2401-CPU Facility Card manages
the signals from/to I/O cards, connected in system, acquiring all the Alarm and Fault
status an executed all the Causes and Effects logic written in application program and generates the respective outputs
of commands. At prefixed time of 1 hour the CPU executes troubleshooting programs, which test the status of all
system functions, generating event message for a printing out any status-changed conditions.
The second one is RS485-FD (double), in Redundant configuration at baud-rate 9600 used for the communication with
the 2405/2405C Digital Control Panel. This/these Panel control all the Addressable Devices installed in system, is
possible to connect up to 32 Digital Control Panel in different configurations of work access level.
The third one is RS232-C at 9600-N-8-1, will allow communication with a Host Computer as supervisory system in
MODBUS® RTU Slave protocol.
The fourth one is RS232-C at 38400-N-8-1, dedicated to the communication with programming system, it is based on
PC on which a dedicated software, realised by SES-ASA ENGINEERING
Protection, necessary for the configuration and the
programming of the logic. After download program, the system has been configured. This serial line will be available
to send the event and diagnostic message to the printer/PC at 9600-N-8-1. All the printed messaged will contain the
exact timing date, for each type of event. If selected system without printer is active like MODBUS® RTU Slave
protocol.
The system can provide a Redundant 2401-CPU in “Master & Slave” configuration.
I
2401-CPU Facility Card
P
P
L
C
PL
LC
C IIInnnttteeegggrrraaattteeeddd
TECHNICAL DATA
Power Supply (Line Isolated)
Power Supply (Line I/O)
Power Consumption 24Vdc ISO
Power Consumption 24Vdc I/O
: 24 VDC Nom. (20÷30VDC)
: 24 VDC Nom. (20÷30VDC)
: 6 W Max in Alarm condition
: 0,2 W Max in Alarm condition
Isolation
Number of Field Devices per Module
Addressable Loop Scan Time
: 1500 Volts RMS between (I/O) and (ISO)
: Up to 95 I/O addressable devices
: < 5 Seconds
Watchdog/Running Mode
: K1 Relay Energized, SPST
Max. - 1A @ 30VDC - 0,3A @ 125/250VAC –
Communication lines
2400 I/O Cards
2405/2405C Digital Control Panel
MODBUS™
PC/PRINTER/MODBUS™
: 2 lines RS-485 Full-Duplex in Redundant mode (Internal)
: 2 lines RS-485 Full-Duplex in Redundant mode (External)
: 1 lines RS-232-C 9600,N,8,1
: 1 lines RS-232-C 9600,N,8,1
Operating Temperature
Storage Temperature
Humidity
Weight
: 0°C ÷ 70°C (+32°F ÷ +158°F)
: -40°C ÷ 85°C (-40°F ÷ +185°F)
: 0 ÷ 95% non-condensing
: 960 gr.
SYSTEM STANDARDS CONFORM
-
CE marked according to CEE directive - 89/336 CEE EMC - 93/68 CEE LVD EMC certification according to EN61000-6-4 Level 4 (+/-4KV)
Radiated Conducted Emission certification according to IEC 1000-4-4
Conducted Susceptibility, Fast Transient/Burst certification according to EN 50082-2, EN 61000-6-2
Conform EN-54 EN-61508 (SIL2)
ORDERING INFORMATION
2401 Master
→ code 034560
2401 Slave
→ code 034560
2400 SW PLC Program
→ code ............
2490 Hand Held Monitor
→ code 034571
2405 Addr. Digital Display
→ code 034601
2405C Addr. Digital Display → code 034599
2406 Addressable Loop Contr. → code 034629
2409 Conventional Loop Cont. → code 034565
2402 HC Gas 0÷22mA
2403 HC Gas Pellistor
2404 TX Gas 0÷22mA
2407 OX Gas 0÷22mA
2408 Flame 0÷22mA
2411 Digital Inputs
2420 Supervised Outputs
2422 Digital Outputs
→ code 034561
→ code 034619
→ code 034562
→ code 034563
→ code 034564
→ code 034566
→ code 034567
→ code 034568
Connector 32DZ
→ code 026026
T.B. bfm-he 10/10
→ code 028076
Flat-cable 10/10 L=30 F. → code ............
Connector 9pins M.
→ code ………
Blank Panel 5TE
→ code 080555
* Master Rack 19”
→ code 081043
**Exp. Rack 19”
→ code 081045
* Master Rack Include BUS-2480 & BUS-2481 on Rack 19” with N°12 I/O slots (like 2406) N°2 CPU-2401 slots
** Expansion Rack Include BUS-2480 on rack 19” with N°16 I/O slots (like 2406)
OVERVIEW FG-ESD-2400
II
2401-CPU Facility Card
P
P
L
C
PL
LC
C IIInnnttteeegggrrraaattteeeddd
LOGIC DIAGRAM CONNECTION
DCS
DCS
SCADA
SCADA
MODBUS RTU MODBUS RTU
PROTOCOL
PROTOCOL
SERIAL LINE OR PC/PRINTER
SERIAL LINE
REDUNDANT EXTERNAL SERIAL LINE
EMERGENCY
ACTION
LED's
CLOCK
16 MHz
uP
80186
16 BIT
SIO 1
BUFFER
LED's
DL
RUN
64K / 128K
EPROM
SIO 2
REAL TIME
CLK. BATT.
BACK UP
SIO 3
256 K
CMOS
RAM
RUN
EN
RELAY
O
P
T
O
I
S
O
L
A
T
O
R
RS232
A
+5L
+5S
BATTERY
BACK UP
CIRCUIT
REPORT
PRINTER
S
EL
RI
I N
AE
L
SERIAL LINE
Relay
RS232
PARALLEL BUS
DATA EXCHANGE BETWEEN FACILITIES
256 K
CMOS
RAM
P.B.EN.
RS485
EXTERNAL
LINE 1
RS485
EXTERNAL
LINE 2
PARALLEL BUS DATA EXCHANGE (ON BUS-2481)
WATCH DOG
CIRCUIT
DC
DC
RS485
INTERNAL
LINE 1
SIO 4
RS485
INTERNAL
LINE 2
A
CPU-2401 Facility Card
PROGRAMMING &
CONFIGURATION PC
WATCH DOG
CIRCUIT
LED's
CLOCK
16 MHz
uP
80186
16 BIT
SIO 1
BUFFER
LED's
DL
RUN
64K / 128K
EPROM
SIO 2
REAL TIME
CLK. BATT.
BACK UP
SIO 3
256 K
CMOS
RAM
RUN
EN
RELAY
RS232
Relay
RS232
A
PARALLEL BUS
DATA EXCHANGE BETWEEN FACILITIES
+5L
+5S
BATTERY
BACK UP
CIRCUIT
S
EL
RI
I N
AE
L
RS485
EXTERNAL
LINE 1
RS485
EXTERNAL
LINE 2
O
P
T
O
I
S
O
L
A
T
O
R
256 K
CMOS
RAM
P.B.EN.
EMERGENCY
ACTION
SIO 4
A
CPU-2401 Facility Card
DC
DC
RS485
INTERNAL
LINE 1
RS485
INTERNAL
LINE 2
REDUNDANT
INTERNAL
SERIAL LINE
(ON BUS-2480)
III
2401-CPU Facility Card
P
P
L
C
PL
LC
C IIInnnttteeegggrrraaattteeeddd
FIELD WIRING INFORMATION’S
This drawing shows the typical arrangement for the connection of devices
Specification subject to change without notice DOCUMENT SES-DS-2401-E-R1
2
Legal Seat : Via G. Galilei N. 5 - 20091 Bresso (MI) - Italy
Factory: Via C. Romani N.8/10 - 20091 Bresso (MI) – Italy
Tel.: +39 02 610371 Fax.: +39 02 66507091
www.ses-enser.com - [email protected]
IV