- GPM Hydraulic Consulting, Inc.
Transcription
- GPM Hydraulic Consulting, Inc.
CONSULTING REPORT TO: FROM: Al Smiley GPM Hydraulic Consulting Inc. RE: In-Plant Hydraulic Systems DATE: July 7 – 8, 2005 Reason for Consult I was called in to analyze each hydraulic system and to make specific recommendations and adjustments for improving the machine operations. A detailed report follows on each system, which includes the information gathered during the consult. North Side Debarker Pump PVQ 10 Vickers, 4.6 GPM pressure compensating, externally drained, piston pump. The pump volume is used to direct oil to the cylinders when raising the conveyor. Normal bypassing out of the case drain line should be .05-.15 GPM. Pressure Adjustments The setting of the compensator determines the maximum pressure at the pump outlet port. A relief valve is used as a safety back up in the event the compensator were to fail. The relief valve will also absorb pressure spikes. The compensator was set to 1100 PSI and the relief valve to 1400 PSI. One of the adjustments on the manifold below the accumulator is a pressure-reducing valve. The setting of this valve determines the pressure to the cylinders when raising. The valve should only be set high enough to hold the conveyor in the raised position. On other conveyors of this design, the valve is normally set to 600 - 700 PSI. Speed Adjustments One of the cartridge valves on the manifold will determine the flow from the pump when raising the conveyor. Another valve is used to determine the flow rate from the accumulator to the cylinders when raising. Oil Temperature – 226° F Filters, Breathers and Gauges The gauge at the return filter read 50 PSI. This means that the pressure has built up to the internal check valve’s spring setting. The return oil is flowing through the internal check valve and back to tank. This filter should be changed as soon as possible. The breather cap is extremely dirty and oily. This should be replaced. The gauge located on the accumulator manifold is bad. This gauge will indicate the setting of the pressure in the accumulator. Once replaced, this gauge should read 0 PSI prior to working on or around the infeed conveyor. The manifold contains an automatic, hydraulic accumulator dump valve. This valve should open when the pump is turned off. This allows the pressurized oil in the accumulator to bleed down to 0 PSI. Accumulator The nitrogen pre-charge in this accumulator was checked and found to be 450 PSI. The precharge is normally approximately 100 PSI below the pressure required to hold the conveyor in the raised position. Additional Actions and Recommendations The high oil temperature, 226 ° F, was caused by the relief valve being set below the pump compensator setting. Dennis and I properly set the compensator to 1100 PSI and the relief valve to 1400 PSI. Due to the extreme high oil temperature, the oil has broken down and should be changed. Prior to changing the oil, the reservoir should be cleaned to remove this sludge and contamination. This high temperature has also caused varnish to develop in the pump, valves and cylinders. I recommend using an additive by Mobil, called Mobil Sol A. You can contact your local Mobil supplier or call 1-800-662-4525 for this product. The seals on the cylinders are leaking, most probably due to the high oil temperature. Log Turner, Bed Lift and Shift Infeed Spike Rolls Pump The pump is a 37 GPM, variable displacement, externally drained pump with a maximum pressure of 3000 PSI. At the time of the consult a new pump had just been installed. Normal flow rate out of the case drain line should be 1/3 – 1 ¾ GPM. Pressure Adjustments The setting of the pump compensator determines the maximum system pressure. Upon initially inspecting the unit the compensator was set at 2950 PSI. After the system accumulators were properly pre-charged, the setting was lowered to 2600 PSI. There is no relief valve in this system. If the compensator were to fail then the pump would deliver maximum volume until the weak point ruptures. A relief valve should be installed as a safety back up. Oil Temperature The temperature gauge on the unit is defective and should be replaced. When shooting the reservoir with a heat gun 135° F was indicated. Accumulators There are two accumulators located upstairs near the machine. One accumulator supplies the Log Turner cylinders. A block located at the accumulator base contains a check valve and automatic dump valve. The check valve will prevent the accumulator from discharging oil to the Lift, Shift and Infeed Spike Rolls positioners. The precharge on this accumulator was found to be 900 PSI. Accumulators should be pre-charged to ½ 2/3rds the pump compensator setting (2600 PSI). An attempt was made to increase the pre-charge to 1300 PSI. Only 1200 PSI could be reached due to the pressure in the nitrogen bottle. The other accumulator supplies oil to the Bed Lift and Shift as well as the Infeed Spike Rolls. The pre-charge on this accumulator was found to be 400 PSI. The precharge was increased to 1200 PSI, which is all that was available in the nitrogen bottle. This accumulator also contains a check and dump valve block. This allows the accumulator to only supply the above-mentioned circuits. Additional Actions and Recommendations The original problem on this unit that the Bed was lifting too slow. Once the accumulator was properly charged, the operator indicated that he no longer received any alarms on the bed position. The flow meter in the case drain line is a 0 – 30 GPM meter. A smaller meter, 0 – 10 GPM, should be installed. The case drain flow was reading well below the lowest reading on the meter, 3 GPM. The hose out of the pressure filter is too long and rubbing. The hose should be replaced with a shorter hose or a “sleeve” installed at the contact point. Saw Box Pump The system is supplied with an Oilgear, 34 GPM piston type pump. The flow meter in the case drain line indicated a flow rate of 1 ½ GPM. This check was made when the oil temperature was at 166° F. Less bypassing will occur when the oil temperature drops. Normal flow for this pump should be 1/3 – 1 GPM. Pressure and Flow Adjustments The block on top of the pump has two adjustments; the pressure compensator and maximum volume stop. The compensator setting determines the maximum system pressure. A relief valve is used as a safety back up in the event the compensator fails closed. This would allow the pump volume to dump to tank preventing damage to the system. The volume stop on the Oilgear pump should be turned in 1½ turns to prevent the internal swash plate pin from shearing off. This adjustment was properly set on the pump. When initially surveying this unit, the oil temperature was 166° F. The tank line of the relief valve was found to be 179° F. This indicated that oil was flowing through the valve. Dennis and I set the compensator to 1550 PSI and the relief valve to 1850 PSI. The temperature of the unit was checked the next day and found to be 108° F. This heat problem was caused by improper pressure settings. Filters The filter dirt alarm in the filtering and cooling circuit indicated that the element was dirty. The element should be changed as soon as possible. Accumulator An Accumulator has been added to this system to increase the positioner speed. No accumulator dump valve is present in the system. An electrical solenoid or hydraulic dump valve should be installed to bleed the pressure down to 0 PSI prior to working on the system. THIS NEEDS TO BE DONE IMMEDIATELY. I also recommend that a manual valve be installed as a safety in the event the dump valve fails. Additional Actions and Recommendations Since this system has been operating at elevated temperatures the oil has been degraded. Varnish may have developed in the lines and proportional valve spool. A flushing compound, Mobil Sol A, may be required to remove the varnish. Install flushing valves or blocks to allow the oil to move through the lines. Once flushed, the oil should be drained and the reservoir cleaned. Chip – N – Saw Heads Pump The system is supplied with a 30 GPM, vane type, pressure compensating, externally drained vane pump. The case drain line is ported through a cooler prior to returning back to tank. This is an effective method of removing heat in this system. Pressures The compensator setting on the pump determines the maximum system pressure. The setting of the compensator is 1950 PSI. There was no schematic available to reference the recommended setting of the compensator. Oil Temperature - 125° F Accumulators There are two bladder accumulators in this system that supply oil at a high flow rate to the positioners. The precharge on one accumulator is 1000 PSI, on the other, 950 PSI. This is considered an adequate precharge with a compensator setting of 1950 PSI. Recommendations The block on top of the reservoir contains the pump isolation check valve, the pressure gauge and the accumulator dump valve. The dump valve will open when the pump is turned off directing the pressurized fluid in the accumulators back to the tank. Always check the pressure gauge to verify that the pressure has bled down to 0 PSI prior to working on or around the system. If the gauge does not read 0 PSI, then the accumulator is pressurized and the dump valve is stuck closed. Edger Pump The PVG 130C Oilgear pump has a maximum volume of 60 GPM and has a pressure compensator and a volume stop. The pump will deliver maximum volume, 60 GPM, until the compensator setting is reached. The compensator spool will then shift reducing the volume to only what is required to maintain the compensator setting. The setting of the volume stop determines the maximum flow rate out of the pump. Turning the adjustment clockwise reduces the maximum volume. Case Drain Flow The normal flow rate out of the case drain line for this pump at 2000 PSI is 2.59 GPM. Dennis and I removed the case drain line and timed the flow into a 5-gallon container. The flow rate was approximately 5.5 GPM. This indicates a badly worn pump. This high flow rate is also generating heat. Pressures The compensator in this system is set at 1800 PSI. The recommended setting on the manufacturer’s print is 1500 PSI. This was not adjusted due to the slow raise speed of the top head. No relief valve is installed in the system. Oil Temperature The tank was shot in various locations with a heat gun and found to be 142° - 150°. Filters and Breathers John said that the breather cap had been left off the unit for an extended period of time. This obviously allowed contamination to enter the reservoir. There is a pressure filter located upstairs near the accumulator. Due to the problem with the Top Head raise speed this filter should be changed, as the Top Head Bosch valve may be defective. Speed Problems The Top Head is raising too slow. All other positioners are operating at normal speed. The voltage to the Top Head proportional valve was checked and found to be slightly above 9 volts when raising. The LVDT indicator on the amplifier card illuminated to the near full stroke position when the head raised. This indicates that the Bosch valve is shifting properly. The valve spool however, may be badly worn allowing bypassing back to the tank. The cylinder seals bypassing may also cause the slow speed. This is difficult to check because the Bosch valve is mounted directly to the cylinder. The original print shows a counter balance valve and cylinder. This valve is not on the positioner assembly. The purpose of this valve is to hold the head in the raised position when the power is turned off. The valve will also maintain a back pressure in the rod side of the cylinder when lowering. Without this valve in the system, the head can free fall faster than oil is delivered by the system. This can cause cavitation and damage to the cylinder. It is recommended that the valve be installed in the system. Hoses The pressure line hose from the pump is too long and rubbing. A sleeve or protective guard should be installed to prevent premature failure. Accumulator The recommended nitrogen pre-charge for the accumulator is 900 PSI. The temperature of the accumulator was hotter in the lower half that the top half. This indicated that the accumulator is operating normally. This accumulator supplies oil to all the linear positioner circuits. Additional Actions and Recommendations The high oil temperature (142° - 150°) is caused by the excessive pump bypassing. The reservoir should be cleaned out and the return filter replaced. A new pump should then be installed. A relief valve should be added in this system as a safety back up for the pump compensator and as a shock absorber. The valve should be set 250 – 300 PSI above the compensator setting. Once the top head speed problem is corrected the compensator should be turned down to 1500 PSI. A gauge should be installed on the valve block located just below the accumulator. This gauge should be checked prior to working on the machine to verify that pressure in the accumulator has dropped to 0 PSI. Trimmer Pumps The trimmer power unit contains two pumps; one is used as a back up pump. The online pump at the time of the unit survey was the Continental PVR50 vane, pressurecompensating pump. The standby pump is an Oilgear piston, pressure compensating design. The pump also has a maximum volume stop. The exact volumes that the pumps deliver are not known due to incomplete part numbers. Pressures The setting of the PVR50 pump compensator is 1300 PSI. No schematic was available to indicate the desired compensator setting. The compensator should, however be set 200 PSI above the pressure required to move the maximum load. Oil Temperature - 106° F Hoses The pressure hose connected to the Continental pump is rubbing on the return line hose. The piston pump pressure line hose is rubbing on the drip pan. Maximum hose length should be 4 – 5’. The hoses should be shortened, if possible or protective sleeves installed to prevent premature failure. Additional Actions and Recommendations There is no relief valve installed as a safety back up. A relief valve should be connected downstream of the pump isolation hand valves. The valve should be set 250 – 300 PSI above the setting of the pump compensator. Green End Sorter Pumps The sorter unit has two pressure compensating pumps. One is used as a back up or spare pump. One pump is a vane and the other is a piston type. No part numbers could be seen to determine the pumps’ volumes. The vane pump should normally bypass 3 – 5% of its maximum volume through the case drain line. The piston pump should bypass slightly less, 1 – 3%. Pressures The setting of the online pump compensator determines the maximum system pressure. At the time of the survey the piston pump was used to operate the bays. The compensator setting on the piston pump is 1500 PSI. Filters There is a leak at the return filter that is dripping at approximately 1 drop per second. This will result in a loss of 405 gallons per year. The filter indicator is damaged and should be replaced. Additional Actions and Recommendations There is no relief valve in this system as a safety back up in the event the compensator was to stick. This could cause the pressure to build extremely high until the weak point in the system ruptures. A relief should be installed and set 250 – 300 PSI above the compensator setting. The system was designed with a single solenoid directional valve was to allow the pump to compensate at a lower pressure (500 PSI) when not operating the bays. This decreases the heat and electric motor amp draw when in the idle mode. Consideration should be given to re-connecting the valve to operate the system more efficiently with the piston pump. Green Lumber Stacker - Unscrambler and Even Ending Rolls Pumps Two pressure-compensating pumps are used on this unit. One pump supplies the Unscrambler conveyor, the other pump the Even Ending Rolls. No part number is visible on either pump, however the pumps appeared to be in the 37 – 57 GPM range. Case drain flow should be 1 – 3% of the maximum pump volume. At this time the even ending rolls pump is bypassing 9 GPM. This indicates that the pump is badly worn and should be changed if this unit is not converted to an electric drive within the next month. Pressures The setting of the pump compensators determines the maximum system pressures. These pressures could not be recorded, as there were no gauges located at the pumps. There is a relief valve located near the Unscrambler hydraulic motor. This valve is used to absorb shock when starting and stopping the conveyor. The valve should be set 200 PSI above the pressure required to drive the conveyor fully loaded. There is a relief valve located in a block underneath the even ending rolls valves. Dennis and I attempted to set this valve, however the pressure never changed. This valve should be changed and set 250 – 300 PSI above the pump compensator setting. Speed Controls There are inline flow controls that are used to set the unscrambler and even ending rolls’ speeds. The valves are located near the unscrambler hydraulic motor. Oil Temperature - 186° F Filters The return filter element on the unit needs to be replaced. Additional Actions and Recommendations The unit is running excessively hot. This is caused by the high bypassing of the Even Ending Rolls pump. Since the relief valve in the Even Ending Rolls circuit could not be adjusted it may be bypassing some oil as well as generating heat. If this unit is to be kept in service the oil needs to be drained and the reservoir cleaned. The return filter element should be replaced and the Even Ending Rolls pump replaced. A relief valve needs to be installed as a safety back up in the Unscrambler circuit. This valve can be of the “sandwich” design and mounted underneath the directional valve. Stacker – Forks Drive Pumps The pump on the right side is a hydrostatic pump that supplies oil to drive the forks in and out. This circuit is known as a closed loop drive. The ports of the pump are connected to the ports on the hydraulic motor. Some oil will be lost to leakage over the pump case drain line. A charge pump is necessary to supply oil to the charge pump to make up for the leakage. This charge pump is located inside the main pump assembly. When in the idle mode the charge pump volume will be ported through the charge pump relief at 320 PSI. The flow meter in the case drain line will indicate the charge pump flow when in idle. The meter read 5.5 GPM during the survey. A DC voltage is applied to the servo valve on the pump to drive the forks. A positive DC signal will stroke the pump swash plate on one side of the center to drive the motor in one direction. A negative DC voltage strokes the pump in the opposite direction for reversing the motor. There is a “tear drop” manual actuator on top of the servo valve housing. If the motor will not drive properly the actuator can be moved to stroke the pump. If the motor operates normally then the servo coil may be bad or there may be a faulty electric supply signal. Pressures As previously mentioned the charge pump relief is set at 320 PSI. This pressure will be read on both gauges when in the idle mode. The system has a shuttle valve and shuttle relief mounted in one block. The shuttle valve spool will shift when driving the motor directing oil in the suction side of the loop back to tank through the shuttle relief. Since the charge pump delivers more oil than the pump needs at it’s suction, pressure should build up. Once the shuttle relief valve setting is reached the excess oil will return to the tank. This allows some oil in the loop to return to tank for filtering and cooling. The tank line of the shuttle relief should be warm or hot when operating. On this unit the line is cool. This means that the shuttle relief is set higher than the charge pump relief or the shuttle valve spool is stuck closed. The pump manufacturer’s original specifications should be checked as to the shuttle relief setting. Normally the valve is 50 – 100 PSI below the charge pumps relief setting. To set the shuttle relief, operate the forks at as slow of a speed as possible. Rotate the shuttle relief valve setting counterclockwise until the pressure starts dropping on the lowpressure side of the loop. Adjust until the desired setting is reached. There are crossport relief valves on the pump. These valves should be set 400 PSI above the pressure required to drive the forks. When driving the forks the pressure initially spiked to 2000 PSI then dropped to 1200 PSI. Considering that a higher pressure will be required to move the forks initially a setting of 2000 PSI would be a starting point. To set the valves, the flow to the motor must be blocked. Stroke the pump forward and set the appropriate valve. Reverse the pump and set the opposite valve. Filters The charge pump pressure filter has a connection for oil flowing into the canister but no outlet port. This filter is used to filter the charge pump flow to the servo valve. The original pump manufacturer’s literature should be checked and this filter reconnected properly. There is a pressure filter in the main loop. This filter should be charged a minimum of every three months. Additional Actions and Recommendations There is a good deal of shock as the forks operate. This is partly caused by the improper pipe clamps installed in the system. These clamps need to be replaced with a hydraulic clamp such as those made by Stauff. Stacker – Hoist and Accessory Circuits Pumps Two pressure compensating piston type pumps are used to supply the Hoist and Accessory circuits. There was no part numbers visible on the pumps, however they appeared to be in the 37 – 57 GPM range. The expected flow rate out of the pump’s case drain lines should be 1/3 – 1 ½ GPM. Both pumps were considerably above this level. The pump on the left side of the skid is bypassing in excess of 10 GPM. This high flow rate slows the system down and heats the oil considerably. The center pump’s case drain flow is 3 GPM. Normally a pump should be changed when the case flow is 10% of the maximum pump volume. The flow rate on this pump is borderline at this time. Pressures There was no gauge in the pump’s line on the left side. A gauge with a manual shut off valve should be installed. Once installed the compensator on the pump should be set 200 PSI above the maximum pressure to move the load. The setting of the center pump’s compensator is 1700 PSI. Filters and Breathers The filters need visual bypass indicators for monitoring the condition of the element. The breather cap on this unit is dirty and needs to be changed. Oil Temperature The oil temperature is estimated at 170° F. The temperature gauge was not readable however the reservoir wall was shot with a heat gun. Additional Actions and Recommendations The high oil temperature is caused primarily by the high flow rate of oil exhausting out of the left side pump’s case drain line. It was mentioned that the filters on this unit have never been changed. To remove the varnish in the piping and valves add a 5 – 10% solution of Mobil Sol A or a comparable product to existing oil. Run the mixture for 24 – 72 hours. Then drain the oil and clean the reservoir. Secondly, install all new filter elements in the system. With the dirt alarms on the filters monitor the elements conditions. Change them as necessary or after the first 50 hours. The pump on the left side of the skid should then be changed. The manifold block on top of the reservoir contains several cartridge valves. To effectively troubleshoot when a problem occurs, a schematic is need for the system and manifold block. There are several adjustments on the back of the block. One or more of these may be relief valves that may need to be set. The left side pump circuit needs a relief valve installed as a safety back up in the event the compensator fails. The center pump may need one as well depending on exactly what the cartridge valves are in the manifold. The clamps for the piping are not the proper type. This causes excessive shock and leakage in the system. Clamps made by Stauff or another manufacturer should be installed. Planer Feed Table Pump The 57 GPM, bi-directional, externally drained, piston pump drives the Infeed Table in forward and reverse. The voltage to the servo valve coil determines the direction and amount of flow the pump delivers. A mechanical actuator on the servo valve can be moved to determine if the problem is electrical or hydraulic. If the system operates normally when moving the manual actuator then ether the servo valve coil is bad or there is another electrical problem. The servo valve also has an Allen head null adjustment located under the flat head screw on the pilot section of the valve. If the motors are drifting then the valve may need to be nulled. To null, disconnect the cable and slowly rotate the Allen head until the drifting stops. The pump assembly contains a charge pump mounted on the back end. The charge pump supplies make up oil to the pump suction as well as oil to the servo valve for stroking the pump. When in idle, the charge pump pressure will build to the charge pump relief valve setting, approximately 400 PSI. The oil will then return to tank through the case drain line of the main pump. A flow meter in this line will indicate this flow rate. Pressures As mentioned in the pump section the charge pump relief setting is 400 PSI. A separate block contains a shuttle valve, shuttle valve relief and two crossport reliefs. The shuttle valve and relief will allow some of the oil that exhausts out of the motors to return to the tank. The shuttle relief should be 60 – 80 PSI below the charge pump relief setting to verify that the shuttle relief is set below the charge pump relief, feel the tank of the block. This line should be hot or warm when driving the motors. If not, turn the shuttle relief counterclockwise until the pressure on the suction side reads 320 – 340 PSI. When driving the motors the pressure is 900 – 1500 PSI. The crossport relief valves are used to limit the maximum pressure in the forward and reverse directions. These are normally set at 2500 PSI as recommended by the manufacturer. To set the valves, the hoses to the motors should be removed and pipe plugs inserted in the crossport block. Stroke the pump at a low volume and set the specific valve until 2500 PSI is read on the gauge. Then stroke the pump in the opposite direction and adjust the other crossport to 2500 PSI. There are relief valves mounted at the outlet port of the flow divider. These valves should be set 200 – 400 PSI above the pressure required to drive the largest size board. To determine the load pressure, install a gauge at the inlet of the relief, if possible. Once the load pressure is known turn the pump off and lockout the system. Remove the hoses to the motors and install pipe plugs. Stroke the pump at slow speed in the forward direction and adjust each valve to the appropriate setting. Filtering, Coolers and Breathers There are two inline filters that remove contamination from the motors to the pump. These elements should be changed as dictated by an oil analysis or every 3 months. The cooler fins need to be “combed” and cleaned. This is essential, as hydrostatic drives tend to normally run hot. The breather cap on the reservoir is very dirty and should be changed immediately. A manual hand pump is used to refill the reservoir. At this time the pump suction pipe is stuck down inside the 55-gallon drum. The outside air has contaminated the oil in the drum. When not being used the drum should be sealed. The oil should also be filtered prior to pumping it into the tank with a 10-micron filter. There is a suction filter connected in the charge pump suction line. Eaton, the pump manufacturer, recommends the filter have a 10-micron rating and is of the non-bypassing type. If this filter becomes contaminated, the charge pump can cavitate causing eventual cavitations of the main pump. Oil Temperature - 135° F Motor Case Drain Temperatures - 159° - 160° F Hoses Several hoses were too long and rubbing. Upon examining the hoses wear points exist, and in one case, the wire of the hose is exposed. Normal hose length should be 3 –4 feet. This system needs to be re-piped to eliminate these potential leak points. Planer Mill Sorter Pump The pump is a 45 GPM, pressure compensating, Vickers piston type pump. The setting of the compensator determines the maximum system pressure 1500 PSI. The flow out of the case drain line can be checked to determine pump wear. Normal bypassing for this pump is ½ - 1 ½ GPM. When the flow rate reaches 4.5 GPM the pump should be changed. Oil Temperature 134° - 139° F was indicated when the reservoir was shot with a heat gun. Leaks Oil is leaking at the return filter gasket. Additional Actions and Recommendations The original design of the system was to vent the pump compensator when the bays were not operating. This was done with a single solenoid directional valve. The valve is still mounted on the reservoir but is not connected in the system. The temperature of this system is approaching 140° F. Oil will start breaking down above that temperature. By reconnecting the directional valve, the pump will compensate at a lower pressure. This will reduce heat and electrical energy when in the idle mode. This system does not have a relief valve as a safety back up. If the compensator spool were to stick closed, pressure would build until the weak point ruptures. A relief valve should be installed immediately down stream of the pump. Planer Hold Down Rolls Pump A 5 – 6 GPM, pressure compensating, piston pump supplies oil to the hold down roll cylinders. The setting of the pump compensator determines the infeed hold down pressure. There was not a gauge at the pump outlet port to read the compensator setting. The flow out of the case drain line for this pump should be .05 - .15 GPM. A severe increase in this flow rate indicates a worn pump. Pressures The compensator on the pump should be set to the pressure required at the infeed hold down rolls. A pressure-reducing valve on the manifold is used to limit the pressure to the outfeed roll. The reducing valve is set to 750 PSI. Oil Temperature - 129° F Accumulators Two piston accumulators are mounted on the reservoir. The larger accumulator is used to supply additional volume for raising and lowering the rolls. The precharge on this accumulator should be ½ - 2/3rds the pump compensator setting. The smaller accumulator is used to absorb shock in the rolls circuit. The nitrogen precharge should be 100 PSI below the compensator setting. Hoses Several hoses on this unit are too long and rubbing. Protective sleeves should be installed or shorter hoses should be made. Additional Actions and Recommendations A gauge should be installed to read the pressure at the outlet port of the pump. This gauge should be checked to make sure the pressure has bled down to 0 PSI before working on or around the feedrolls. To make sure that the pressure has bled down from both accumulators the manual overrides on the end of directional valve solenoids can be actuated. All personnel should be clear of the rolls when this is done. The breather cap-mounting base is split allowing sawdust and other contamination into the reservoir. This needs replacing as soon as possible. Planer Mill Stacker Pump The system is supplied by a 20 GPM, Oilgear piston pump. The block on top of the pump contains the compensator. The compensator setting determines the maximum system pressure. Normal bypassing out of the case drain line of this pump is approximately 1 GPM. A severe increase in this flow rate indicates a badly worn pump. Pressures The compensator adjustment is set to 1500 PSI. A relief valve is located in a block on top of the reservoir. The relief valve should be set 250 – 300 PSI above the compensator setting. To properly set the valves perform the following procedure: 1. 2. 3. 4. Turn the relief valve fully counterclockwise. Turn the compensator fully clockwise. Turn the relief clockwise until 1800 PSI is read on the gauge. Turn the compensator counterclockwise until 1500 PSI is indicated on the gauge. Oil Temperature 132° - 134° F when shooting the reservoir with a heat gun. Filter and Cooler The visual dirt alarm on the filter is bad and needs replacing. The cooler fins have some dirt build up and should be cleaned. Strapper Pump A 20 GPM variable displacement, pressure compensating Rexroth pump supplies oil to operate the strapper actuators. A “load sensing” spool is mounting on top of the compensator valve. The “X” port of the load-sensing spool is connected to a vent solenoid valve. When the solenoid valve is open the load sensing spool will shift at 500 PSI allowing the pump volume to be reduced to near 0. The pump will only deliver enough oil to maintain the load sensing spring setting, 500 PSI. When necessary to operate the strapper, the vent solenoid energizes. Pressure can now build to the setting of the compensator, 1450 PSI. Once this setting is reached the pump volume is automatically reduced to only what the system needs. The pump has a maximum volume stop on the end of the housing. If this adjustment is turned clockwise, the pump will deliver a lower volume of oil. On this application, this adjustment should be all the way out allowing the pump to deliver maximum volume when needed. Pressures Refer to the pump description for the setting and operation of the compensator and load sensing springs. Return Filter A red button on top of the filter housing will pop up when the element is dirty. The element momentarily pops up when the top squeeze cylinders retract. This may be caused by the filter being sized too small or the element may be nearly contaminated. Additional Actions and Recommendations There is no relief valve in the system for protection in the event the pump compensator fails closed. A relief should be installed and set 250 – 300 PSI above the pump compensator setting. The easiest location to install the relief may be underneath the top or side squeeze directional valves. A longer bolt kit will be needed. Consult Summary Several reoccurring problems were found during the two-day survey of the units. The first is improper pressure settings, which results in extremely high oil temperatures. This was the case on the Saw Box and North Side Debarker. This is a common problem in mills because pressures are randomly adjusted in an attempt to increase the speed of the machine. In both cases the relief valve was set below the pump compensator. This causes the entire pump volume to dump over the relief valve when not being used to moving the load. Hydraulic systems are designed to normally operate below 140° F. When a high oil temperature exists in a system with a compensating pump and relief valve, the first thing that should be done is to properly set the pressures. In the case of the Saw Box, the oil temperature dropped from 166° F to 108° F once this was done. On other systems, high oil temperature was caused by excessive case drain flow of the pumps. The Edger and Stacker units exhibited this problem. The first recommendation here is to install a flow meter in the case drain line of all pump. This will allow the flow to be to be checked quickly and easily. The bypassing of any pump will gradually increase over time. Several factors will cause the flow to increase prematurely: poor filter maintenance, high oil temperature and pressure settings being too high. If a regular filter maintenance program is not in place, then one should be started. The best method of establishing a schedule is to have the oil analyzed by a qualified company. Based on the fluid cleanliness (or lack thereof) a filter change out schedule can be developed. If oil analysis is not done, then as a general rule, change the elements every 3 months. An even better method however is to have visual dirt alarms and checking them monthly. Many of the system filters lacked dirt alarms or if they had them they were not working. A fluid cleanliness level of 17/13 should be maintained in non-servo systems. On systems using servo and proportional valves a 14/11 standard should be met. The reservoir of any hydraulic system should be cleaned out once a year. Use a lint free cloth when wiping the reservoir down. The systems that have run above 140° F for an extended period of time need to be cleaned immediately. Varnish and sludge will be present in the reservoir, lines and valves. In several sections of this report I recommend the use of a Mobil product called Mobil Sol A. This flushing solvent will remove the varnish and gummy deposits in the system. Product and flushing procedure data sheets are included with this report on Mobil Sol A. Several breathers were found to be fully contaminated or not properly mounted. If the breather plugs up then dirty air will enter through a return line gasket, mounting bolt, etc. The breather on the unit should filter the air to a 10 – 40 micron level. Breathers should be changed a minimum of once a year. Many systems using pressure-compensating pumps are installed without a relief valve as a safety backup. If there is no relief in the system and the compensator fails to shift, pressure will build up until the weak point ruptures. The weak point may be a blown hose, O-ring, the physical structure of the machine, or the electric motor overload. A relief valve should be installed on all units that utilize pressure-compensating pumps. Many units had hoses that were over 4’ in length. Most of these hoses were rubbing on another hose, reservoir, beam, etc. This will result in premature failure of the hose and mill downtime. Proper hydraulic plumbing is to connect a hose out of the pump to the pipe header. A hose should be connected off the header prior to connecting to the valve or cylinder. The exception to this rule is if the cylinder is operating a vertical load. A valve called a velocity fuse should be connected at the cylinder before the hose is attached. This will prevent free falling of the load in the event the hose ruptures. Several leaks were found during the two-day visit. When a leak occurs, there is a reason for it. This may be caused by high oil temperature, improper clamping or worn seals and gaskets. A leak that drips once per second will cause a loss of 405 gallons in a year’s time. Once the problems on the units are corrected regular preventative maintenance checks should be made. I have included our standard Hydraulic Preventative Maintenance Checklist with this report. Although all the checks will not apply to all systems a thorough P.M. of the unit will be done when completed. I would recommend making these checks once a month to insure system reliability. I would like to thank everyone who assisted me during my visit especially John Love, Dale Dyals, Dennis Cumbee, Richard Hayes and Willie Taylor. I hope the information contained in this report will assist you in improving your hydraulic maintenance and increase your operating efficiency. Please do not hesitate to call if I or anyone here at GPM can help you in any way. Sincerely, C.A. (Al) Smiley, Jr. President GPM Hydraulic Consulting, Inc.