Technical datasheet Hilti Firestop Foam CFS

Transcription

Technical datasheet Hilti Firestop Foam CFS
Technical
Hilti Firestop Foam CFS-F FX
datasheet
Hilti Firestop Foam
CFS-F FX
European
technical approval
ETA No 10 / 109
Hilti Firestop Foam CFS-F FX | Issue 06/2010
Issue 06 / 2010
page 1
Hilti Firestop Foam CFS-F FX
Firestop Foam
CFS-F FX
Bauchemie
Piktos_neu.ai
Bauchemie
Piktos_neu.ai
01.10.2006
01.10.2006
45% 45%
30
30
30 30
Jahre
Jahre
years
years
Rauch- und
Gasdichtigkeit
Rauchund GasdichtigkeitSchallschutz
Schallschutz
Fields of Application
Technical Data
◼◼ Cable trays, single cables, tied cable bundles, small conduits
Colour
Foil pack volume / foam yield
325 ml / 2.1 liters (freely foamed)
◼◼ Plastic pipes
Application temperature of
pack / Storage and transport
temperatures
+10°C to +35°C / +5°C to +25°C
Curing times
Can be shaped after
approx. 5 min.
Can be cut after approx. 10 min.
Permanent firestop seals in small and medium-sized openings
(optimum size range: 100 x 100 mm to 300 x 300 mm)
◼◼ Openings accommodating pipes and cables
◼◼ Metal pipes (with combustible or non-combustible insulation)
(The seals must comply with ETA No 10 / 109.)
Wasserbeständigkeit
Wasserbeständigkeit
ElektischeElektische
CFS-F Wärmedämmend
FX Wärmedämmend
Dampfdichtigkeit
Dampfdichtigkeit
Red
Features and Benefits
35%
35%
Class
E
30
30
30 30
◼◼ 3-phase technology with optimum application characteristics
(easily shapeable foam)
Reaction to fire, classification
years
years
according to EN 13501-1
◼◼ Easily applied using the ergonomically-designed Hilti dispensers
Temperature resistance
of the cured foam
◼◼ Easy installation without need for formwork or other aids
◼◼ Safety first: CFS-F FX complies with the requirements of
international fire protection directives
◼◼ Neat and tidy application
◼◼ Very quick and easy to install – a reliable firestop seal with only
one product
Jahre
Jahre
– 30°C to + 60°C
Shelf life
9 months (at 23°C and stored
in a dry place)
At 23° C, 50% relative humidity
Wasserbeständigkeit
Wasserbeständigkeit
ElektischeElektische
Rauch- und
Gasdichtigkeit
Rauchund GasdichtigkeitSchallschutz
Schallschutz
◼◼ Easy subsequent installation of additional cables
◼◼ Outstanding sound insulation properties thanks to flexible foam
structure
◼◼ Smoketightness and firestopping with one system
The European Technical Approval
(ETA) can be obtained via your
ElektischeElektische
Wasserbeständigkeit
local Hilti Wasserbeständigkeit
contact.
Rauch- und
Gasdichtigkeit
Rauchund Gasdichtigkeit
Schallschutz
Schallschutz
Smoketight
Sound
insulation
Ordering
Order Description
Package content
CFS-F FX
incl. 1 mixing nozzle, instructions for use
Item Number
00000000
Order Description
Package content
MD2000 manual dispenser
Manual dispenser with 1 foil pack holder
00000000
ED3500 cordless powered
dispenser kit
Dispenser, C7/24 charger, SFB 121 battery, 3 round brushes,
protective glasses, blow-out pump, 2 foil pack holders,
packed in an impact-resistant plastic Hilti toolbox
00000000
ED3500 cordless powered dispenser
basic kit
Dispenser, 3 round brushes, protective glasses, blow-out pump,
2 foil pack holders, packed in an impact-resistant plastic Hilti toolbox
00000000
page 2
Item Number
Hilti Firestop Foam CFS-F FX | Issue 06/2010
Hilti Firestop Foam CFS-F FX
Installation instructions
Clean the opening to be sealed. The material around the opening must be dry, in sound
condition and free from dust or grease.
Check the foil pack holder for damage and
ensure that it functions correctly. Slide the foil
pack into the holder. Caution: Never use damaged foil packs and/or damaged or badly
soiled foil pack holders.
Remove the cap. Screw the mixing nozzle
all the way onto the foil pack and tighten it
securely. Check that the black mixing element
is in place inside the nozzle! Do not use damaged mixing nozzles. Do not, under any circumstances, modify or tamper with the mixing
nozzle. The foil pack should only be used together with the mixing nozzle supplied. A new
mixing nozzle must be used with each new foil
pack.
Insert the holder containing the foil pack
into the dispenser: Press the release button
on the dispenser, pull the piston rod back as
far as it will go and then insert the holder containing the foil pack into the dispenser.
The foil pack opens automatically when dispensing begins. Never pierce a hole in the foil
pack! This will cause the system to malfunction.
Discard the unevenly mixed initial quantity:
The foam dispensed by the first stroke of the
dispenser must be discarded, e.g. in the empty outer packaging material.
Apply the firestop foam in the opening to
be sealed. The mixed components of the
foam react and begin to expand approx. 30
seconds after application (at 23°C). Fill the
opening completely with firestop foam, including gaps between individual cables, etc.
The foam will harden in the mixing nozzle during pauses (i.e. > 1 minute at 23°C; > 20 seconds at 35°C). The mixing nozzle must
then be changed. Release the pressure from
the piston rod before changing the mixing
nozzle.
Use formwork made from an air-permeable
material (e.g. perforated cardboard)
when filling openings in ceilings.
The foam can be shaped or smoothed by
hand (if necessary) after approx. 5 minutes (at
23°C). Wear protective gloves! After approx.
10 minutes (at 23°C) the foam becomes hard
and it can then be cut.
NOTE:
After hardening, any projecting foam can be
trimmed off to the specified minimum depth.
Trimmed-off scraps of hardened foam can be
placed in the next opening and fresh foam applied around these.
Mount the installation identification
plate beside the correctly sealed opening,
if required.
Subsequent installation of cables or pipes
Additional cables or pipes can be installed in
the opening without difficulty. Do not exceed
the approved maximum number and size of
cables or pipes.
1. T
he cable or pipe may be pushed directly
through the foam. Where necessary, use a
suitable tool (screwdriver or drill bit, etc.) to
make a hole in the foam before pushing the
cable or pipe through. Do not damage existing cables.
2. Seal any remaining gaps carefully with
CFS-F FX
NOTE:
It is generally best to begin in the middle of
the opening, building up the foam by working
from bottom to top. In openings with access
from only one side, begin at the rear and work
toward the front.
Hilti Firestop Foam CFS-F FX | Issue 06/2010
page 3
Hilti Firestop Foam CFS-F FX
Cable penetration
Flexible wall | Rigid wall
Blank opening
Cable | Cable tray
Hilti Firestop Foam CFS-F FX may be used to form penetration seals of maximum opening size 400 x 400 mm (w x h) in:
Flexible walls / Drywalls (E), minimum thickness 112 mm (tE) with timber or steel studs lined on both faces with minimum
2 layers of 12.5 mm thick boards. For timber stud walls there must be a minimum distance of 100 mm between the seal and
any stud, and the cavity must be filled with minimum 100 mm insulation of Class A1 or A2 in accordance with EN 13501-1.
Rigid walls (E) (concrete, aerated concrete or masonry, minimum density of 650 kg/m3), minimum thickness 112 mm (tE).
Penetration seal (A) /services (C)
Classification
E = Integrity
I = Insulation
Seal depth (tA)
(mm)
Other criteria
Description
Small sheathed cables ≤ ∅ 21 mm
Tied cable bundle ≤ ∅ 100 mm
EI 120
≥ 200
EI 60 ; E 120
≥ 112
EI 90 ; E 120
≥ 200
EI 60 ; E 120
≥ 150
Minimum distances:
min S1 = 0 mm (cable tray to seal edge)
min S2 = 50 mm (cable to cable tray)
min S2 = 33 mm (cable to cable bundle)
min S2 = 0 mm (cable to cable)
EI 120 U/U
≥ 200
EI 90 U/U; E 120
≥ 112
Plastic conduit ≤ ∅ 16 mm
EI 120 U/U
≥ 112
Blank, no services
EI 120
≥ 200
All sheathed cables ≤ ∅ 80 mm
Steel conduit ≤ ∅ 16 mm
Framing details see specific drawings
below.
Cable, cable bundle in flexible wall, rigid wall
W(
W(
(
(
&
W$
Z
&
W$
V
V
V
$
$
K
V
$
&
&
rigid wall
flexible wall
Cables on cable tray in flexible wall, rigid wall
W(
W(
(
W$
(
&
W$
Z
&
V
V
$
$
flexible wall
page 4
$
V
K
V
rigid wall
Hilti Firestop Foam CFS-F FX | Issue 06/2010
Hilti Firestop Foam CFS-F FX
Blank opening in flexible wall, rigid wall
W(
W(
(
(
Z
W$
W$
$
$
$
flexible wall
K
rigid wall
Aperture framing, seal frames
W(
(
tE
(
E
W$
tA
$
A
(
Hilti Firestop Foam CFS-F FX | Issue 06/2010
Z
E1
Z
$
K
•PP
$
K
Z$
page 5
Hilti Firestop Foam CFS-F FX
Cable penetration
Floor
Conduits | Tubes
Cable | Cable tray
Hilti Firestop Foam CFS-F FX may be used to form penetration seals of maximum opening size 400 x 400 mm (w x h) in:
Rigid floors (E) (concrete, minimum density 2200 kg/m3), minimum thickness 150 mm (tE).
Penetration seal (A) /services (C)
Classification
E = Integrity
I = Insulation
Seal depth (tA)
(mm)
Other criteria
Description
Small sheathed cables ≤ ∅ 21 mm
Tied cable bundle ≤ ∅ 100 mm,
single cable ≤ ∅ 21 mm
EI 120
≥ 250
EI 60
≥ 150
All sheathed cables ≤ ∅ 80 mm
EI 60; E 120
≥ 150
Medium sheathed cables ∅ 21 – 50 mm
EI 120
≥ 250
Minimum distances:
min S1 = 0 mm (cable tray to seal edge)
min S2 = 50 mm (cable to cable tray)
min S2 = 33 mm (cable to cable bundle)
min S2 = 0 mm (cable to cable)
Large sheathed cables ≤ ∅ 80 mm
EI 90; E 120
≥ 200
EI 60; E 120
≥ 150
EI 120 U/U
≥ 150
Steel conduit ≤ ∅ 16 mm
Steel and plastic conduits ≤ ∅ 16 mm
Cable, cable bundle in floor
Framing floor
Z
(
$
W$
V
W(
&
V
V
K
V
$
(
$
W$
(
W(
&
Cables tray in floor
(
W$
$
Z
&
V
V
W(
$
page 6
V
K
V
Hilti Firestop Foam CFS-F FX | Issue 06/2010
Hilti Firestop Foam CFS-F FX
Pipe penetration
Flexible wall | Rigid wall
Plastic pipe
Metal pipe
Hilti Firestop Foam CFS-F FX may be used to form penetration seals of maximum opening size 400 x 400 mm (w x h) in:
Flexible walls / Drywalls (E), minimum thickness 150 mm (tE) with timber or steel studs lined on both faces with minimum
2 layers of 12.5 mm thick boards. For timber stud walls there must be a minimum distance of 100 mm between the seal and
any stud, and the cavity must be filled with minimum 100 mm insulation of Class A1 or A2 in accordance with EN 13501-1.
Rigid walls (E) (concrete, aerated concrete or masonry, minimum density of 650 kg/m3), minimum thickness 112 mm (tE).
Penetration seal (A) /
services (C)
Pipe insulation (D)
Classification
E = Integrity
I = Insulation
Minimum seal
depth (tA) (mm)
Other criteria
Description
Steel pipe
≤ ∅ 33.7 mm (dc)
(pipe wall thickness
2.6 – 14.2 mm (tc))
Mineral wool
(Rockwool RS 800)
tD = 30 mm / LD = 500 mm
EI 120 C/U
≥ 150
Steel pipe
∅ 33.7 – 114.3 mm (dc)
(pipe wall thickness
2.6/3.6 – 14.2 mm (tc))
Mineral wool
(Rockwool RS 800)
tD = 40 mm / LD = 500 mm
Minimum distances:
min S1 = 0 mm
(between pipe and seal edge)
min S2 = 0 mm
(linear arrangement)
min S2 = 40 mm
(in a cluster)
Steel pipe
∅ 33.7 – 114.3 mm (dc)
(pipe wall thickness
2.6/3.6 – 14.2 mm (tc))
Combustible insulation
(synthetic rubber
Armaflex)
tD = 19 mm / LD = 500 mm
EI 90 C/U; E 120
≥ 150
Installed with 2 layers Hilti
Firestop Bandage CFS-B on
both sides (according to ETA
CFS-B (A2))
Copper pipe
∅ 28 – 88.9 mm (dc)
(pipe wall thickness
1.0/2.0 – 14.2 mm (tc))
Mineral wool
(Rockwool RS 800)
tD = 40 mm / LD = 500 mm
EI 60 C/U; E 120
≥ 150
Combustible insulation
(synthetic rubber
Armaflex)
tD = 19 mm /LD = 500 mm
EI 60 C/U ; E 120
≥ 150
Installed with 2 layers Hilti
Firestop Bandage CFS-B on
both sides (according to ETA
CFS-B (A2))
PVC-U pipe (EN 1452-1,
DIN 8061/8062) ∅ 50 mm
(dc) (pipe wall thickness
3.7 – 5.8 mm (tc))
–
EI 120 U/C
≥ 150
PE pipe (EN 1519-1, DIN
8074/8075) ∅ 50 mm (dc)
(pipe wall thickness
2.9 – 4.6 mm (tc))
–
Minimum distances:
min S1 = 30 mm
(between pipe and seal edge)
min S2 = 55 mm
(between pipes)
Metal pipe, mineral wool insulation in flexible wall, rigid wall
W(
W(
W'
(
W$
&
W'
W&
(
W$
&
Z
$
W&
G&
G&
V
V
K
$
$
'
'
flexible wall
Hilti Firestop Foam CFS-F FX | Issue 06/2010
rigid wall
page 7
Hilti Firestop Foam CFS-F FX
Metal pipe, combustible insulation in flexible wall, rigid wall
W(
W(
(
W'
W'
W&
&
W$
(
&
W$
Z
G&
G&
$
$
$ '
/'
/'
$
W&
V
V
K
$
$ '
/'
/'
flexible wall
rigid wall
Plastic pipe in flexible wall, rigid wall
W(
W(
(
W$
&
Z
(
W&
W$
W&
$
$
$
flexible wall
V
G&
G&
page 8
&
V
K
rigid wall
Hilti Firestop Foam CFS-F FX | Issue 06/2010
Hilti Firestop Foam CFS-F FX
Pipe penetration
Floor
Plastic pipe
Metal pipe
Hilti Firestop Foam CFS-F FX may be used to form penetration seals of maximum opening size 400 x 400 mm (w x h) in:
Rigid floors (E) (concrete, minimum density of 2200 kg/m3), minimum thickness 150 mm (tE).
Penetration seal (A) /
services (C)
Pipe insulation (D)
Classification
E = Integrity
I = Insulation
Minimum seal
depth (tA) (mm)
Other criteria
Description
Steel pipe
≤ ∅ 33.7 mm (dc)
(pipe wall thickness
2.6 – 14.2 mm (tc))
Mineral wool
(Rockwool RS 800)
tD = 30 mm / LD = 500 mm
EI 120 C/U
≥ 150
Steel pipe
∅ 33.7 – 114.3 mm (dc)
(pipe wall thickness
2.6/3.6 – 14.2 mm (tc))
Mineral wool
(Rockwool RS 800)
tD = 40 mm / LD = 500 mm
Minimum distances:
min S1 floor = 20 mm
(between pipe and seal edge)
min S2 floor = 15 mm
(linear arrangement)
min S2 floor = 20 mm
(in a cluster)
Steel pipe
∅ 114.3 – 168 mm (dc)
(pipe wall thickness 3.6 –
14.2 / 14,0 – 14.2 mm (tc))
Mineral wool
(Rockwool RS 800)
tD = 40 mm / LD = 500 mm
EI 120 C/U
≥ 150
Steel pipe
∅ 33.7 – 114.3 mm (dc)
(pipe wall thickness
2.6 – 3.6 mm (tc))
Combustible insulation
(synthetic rubber
Armaflex)
tD = 19 mm / LD = 500 mm
EI 120 C/U
≥ 150
Installed with 2 layers Hilti
Firestop Bandage CFS-B on
both sides (according to ETA
CFS-B (A2))
Copper pipe
∅ 28 – 88.9 mm (dc)
(pipe wall thickness
1.0/2.0 – 14.2 mm (tc))
Mineral wool
(Rockwool RS 800)
tD = 40 mm / LD = 500 mm
EI 120 C/U
≥ 150
Installed with 2 layers Hilti
Firestop Bandage CFS-B on
both sides (according to ETA
CFS-B (A2))
Combustible insulation
(synthetic rubber
Armaflex)
tD = 19 mm /LD = 500 mm
EI 90 C/U; E 120
≥ 150
Installed with 2 layers Hilti
Firestop Bandage CFS-B on
both sides (according to ETA
CFS-B (A2))
PVC-U pipe (EN 1452-1,
DIN 8061/8062)
∅ 50 mm (dc)
(pipe wall thickness
3.7 – 5.6 mm (tc))
–
EI 120 U/C
≥ 150
Minimum distances:
min S1 = 50 mm
(between pipe and seal edge)
min S2 = 65 mm
(between pipes)
PVC-U pipe (EN 1452-1,
DIN 8061/8062)
∅ 50 mm (dc)
(pipe wall thickness
3.7 mm (tc))
–
EI 120 U/C
≥ 150
PE pipe (EN 1519-1, DIN
8074/8075) ∅ 50 mm (dc)
(pipe wall thickness
2.9 – 4.6 mm (tc))
–
EI 120 U/C
≥ 150
Hilti Firestop Foam CFS-F FX | Issue 06/2010
page 9
Hilti Firestop Foam CFS-F FX
Metal pipe with mineral wool insulation in floor
( W$
Z
$
$
W(
V
V
K
&
W&
W'
'
G&
Metal pipe, combustible insulation in floor
/' (
W$
Z
$
$
W(
/'
$
&
'
V
V
K
$
W&
G&
W'
Plastic pipe in floor
(
W$
&
$
Z
V
W(
$
V
K
W&
G&
page 10
Hilti Firestop Foam CFS-F FX | Issue 06/2010
Hilti Firestop Foam CFS-F FX
Mixed penetration
Flexible wall | Rigid wall | Floor
Hilti Firestop Foam CFS-F FX may be used to form penetration seals of maximum opening size 400 x 400 mm (w x h) in:
Flexible walls / Drywalls (E), minimum thickness 150 mm (tE) with timber or steel studs lined on both faces with minimum
2 layers of 12.5 mm thick boards. For timber stud walls there must be a minimum distance of 100 mm between the seal and
any stud, and the cavity must be filled with minimum 100 mm insulation of Class A1 or A2 in accordance with EN 13501-1.
Rigid walls (E) (concrete, aerated concrete or masonry, minimum density of 650 kg/m3), minimum thickness 112 mm (tE).
Hilti Firestop Foam CFS-F FX may be used to form penetration seals of maximum opening size 400 x 400 mm (w x h) in:
Rigid floors (E) (concrete, minimum density of 2200 kg/m3), minimum thickness 150 mm (tE).
Mixed penetration | cable | bundle | tray | metal | plastic pipe
Penetration seal (A) /
services (C)
Pipe insulation (D)
All sheathed cables ≤ ∅ 80 mm
(e.g. power, control, signal,
telecommunication, data,
optical fibre cables)
Tied cable bundle (≤ 100 mm),
maximum diameter of single
cable ∅ 21 mm
Classification
E = Integrity
I = Insulation
Minimum seal
depth (tA) (mm)
Other criteria
Description
EI 60 / E 120
≥ 150
Cable support construction
perforated metal cable tray
minimum distances:
min S1 = 0 mm
(cable to seal edge)
min S2 = 35 mm
(between cable and pipe)
min S1 = 0 mm (between metal
pipe and seal edge)
min S2 = 0 mm (between metal
pipe and linear arrangement)
min S2 = 40 mm
(cluster arrangement)
min S1 = 30 mm (between
plastic pipe and seal edge)
min S2 = 55 mm (between
plastic pipe and metal pipe)
Steel conduits or tubes
∅ 16 mm
Steel pipe ∅ 33.7 – 114.3 (dc)
(pipe wall thickness
2.6/3.6 – 14.2 mm)
Mineral wool
(Rockwool RPS 800)
tD = 40 mm / LD = 500 mm
Copper pipe
∅ 28 – 88.9 mm (dc)
(pipe wall thickness
1.0/2.0 – 14.2 mm)
Mineral wool
(Rockwool RPS 800)
tD = 40 mm / LD = 500 mm
Steel pipe
∅ 33.7 – 114.3 mm (dc)
(pipe wall thickness
2.6/3.6 – 14.2 mm)
Combustible insulation
(synthetic rubber
Armaflex)
tD = 19 mm /LD = 500 mm
Copper pipe
∅ 28 – 88.9 mm (dc)
(pipe wall thickness
1.0/2.0 – 14.2 mm)
Combustible insulation
(synthetic rubber
Armaflex)
tD = 19 mm /LD = 500 mm
Installed with 2 layers Hilti
Firestop Bandage CFS-B on
both sides (according to ETA
CFS-B (A2))
PE pipe (EN 1519-1,
DIN 8074/8075) ∅ 50 mm (dc)
(pipe wall thickness (tc)
2.9 – 4.6 mm)
PVC-U pipe (EN 1452-1,
DIN 8061/8062) ∅ 50 mm (dc)
(pipe wall thickness (tc)
3.7 – 5.6 mm)
Mixed penetration
W(
W(
(
W$
(
W$
$
$
&
&
$
$
&
&
&
&
&
&
&
flexible wall
Hilti Firestop Foam CFS-F FX | Issue 06/2010
rigid wall
&
Z
& &
V
( W$
W(
V
V
$
$
V
V
K
V
V
floor
page 11
Hilti Firestop Foam CFS-F FX
Bauchemie Piktos_neu.ai
05.11.2007
Characteristics of CFS-F FX
Additional Attributes
45%
05.11.2007
30
30
Jahre
years
Bauchemie Bauchemie
Piktos_neu.ai
Piktos_neu.ai
05.11.2007
Hilti Firestop products are comprehensively tested and individually tailored to
45%
45%
the technical requirements of a building’s mechanical and electric installations.
Jahre
years
years
In addition to their superior behaviour in passive fire protection, Hilti
Firestop
products also meet the requirements in building technology that continue to gain
significance and also help the designer and installer in meeting these additional
requirements. The assessment of fitness for use has been made in accordance
with EOTA ETAG No 026 – Part 2.
Rauch- und Gasdichtigkeit
Schallschutz
Dampfdichtigkeit
Wärmedämmend
30 30
30 30
Wasserbeständigkeit
Jahre
Rauch- und GasdichtigkeitRauchund Schallschutz
Gasdichtigkeit
Wasserbeständigkeit
Dampfdichtigkeit
Elektische
Wasserbeständigkeit
Elektische
Dampfdichtigkeit
Wärmedämmend
Air-seal/Luftdichtheit
Elektische
Schallschutz
Wärmedämmend
Charecteristics
Assessment of charecteristics
Norm, standard, test
Health and the environment
Air permeability
(gas thightness)
∆ p 50 Pa ⇒ 0.0007 q/A [m3/(h x m2)]
(174 mm thickness of layer)
Air-seal/Luftdichtheit
m2)]
∆ p 250 Pa ⇒ 0.0007 q/A
[m3/(h xAir-seal/Luftdichtheit
Permeability regarding gases N2,
CO2, CH4: tested
EN 1026
Dangerous substances
below any respective occupational
FM
exposure limits as far as such limits exist
Material safety data sheet
Safety in use
Resistance to impact / movement /
Mechanical resistance and stability /
Adhesion
Soft body impact: Energy 1200 Nm
Hard body impact: Energy 10 Nm
Protection against noise
(Air borne sound insulation)
Rw (C; Ctr) = 47 (–1; –6) dB
Dn,e,w (C; Ctr) = 54 (–0; –5) dB
EN ISO 140-3
EN ISO 20140-10
EN ISO 717-1
Durability and serviceability
Category Y2 (suitable for penetration seals
intended for use at temperatures between
– 20 ° C and + 70 ° C) no exposure to rain
or UV
EOTA Technical Report TR024
ETAG 026-2
APPROVED
British Standard
BS 476
FM
FM
APPROVED
Factory Mutual
C
British Standard
BS 476
FM FM
APPROVED
Factory Mutual
US
British Standard
BS 476
FM
Factory Mutual
EOTA Technical Report
A1
C TR001,
US
C
US
fullfills requirements of zones Type I, II, III
and IV
maximum opening 400 x 400 mm
May be coated with acrylic dispersion, alkyd
resin, polyurethan / acrylic and epoxy resin)
Reaction to fire
Class E
EN 13501-1
Service
With more than 20 years of experience worldwide, Hilti is one of the leading suppliers of
firestop ­systems. We actively help you manage your firestop projects better by providing:
• Quick engineering judgements
• Extensive technical literature
• On-site training and demonstration
• Sophisticated jobsite logistics
• Assurance of conformity with specific application requirements
• International network of Hilti firestop specialists
Our network of experienced sales representatives, field engineers, firestop specialists
and customer service representatives is just a phone call away (use the local toll-free
Hilti number).
page 12
Hilti Firestop Foam CFS-F FX | Issue 06/2010
Hilti Firestop Foam CFS-F FX
Hilti Firestop Foam CFS-F FX | Issue 06/2010
page 13
Hilti Firestop Foam CFS-F FX
page 14
Hilti Firestop Foam CFS-F FX | Issue 06/2010
Hilti Firestop Foam CFS-F FX
Hilti Firestop Foam CFS-F FX | Issue 06/2010
page 15
Hilti = registered trademark of Hilti Corp., Schaan I W 0000 0510 0-en I 2 Printed in Liechtenstein I © 2010 I Right of technical and programme changes reserved S. E. & O.
Hilti Firestop Foam CFS-F FX
Hilti. Outperform. Outlast.
Hilti
| 9494 Schaan | Liechtenstein | P +423-234 2111 | F +423-234 2965Hilti| www.hilti.com
pageCorporation
16
Firestop Foam CFS-F FX
| Issue 06/2010