6078 La Plaza Mall – Sunglass Hut – McAllen_TX

Transcription

6078 La Plaza Mall – Sunglass Hut – McAllen_TX
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A Subsidiary of the Luxottica Group
4000 Luxottica Place
Mason, Ohio 45040
REMODEL
2.0 PREMIUM
K
CONSULTANT PROJECT # 150343
Shremshock Architects, Inc.
7400 W. Campus Rd. Suite 150 New Albany, OH 43054
t: 614 545 4550 | f: 614 545 4555 | shremshock.com
Gerald S. Shremshock, Architect
Timothy J. Shremshock, Architect
J
SEAL
FOR
LA PLAZA MALL
H
STORE # 6078
2220 S. 10TH STREET
SPACE #Q14-C
McALLEN, TX 78503
G
IF REQ'D, STOCKROOM SHELVING TO BE UNDER
SEPARATE PERMIT, SUBMITTED BY SHELVING
MANUFACTURER.
SIGNAGE AND SPRINKLER PLAN TO BE SUBMITTED
UNDER SEPARATE COVER
DRAWING INDEX
DRAWING DESCRIPTION
SUNGLASS HUT
SPACE:#Q14-C
LEVEL 1 OF 1
E
RESTROOMS
USER: JGRAY
PLOTTED: 7/16/2015 - 4:03 PM
C:\TempScan\AcPublish_1732\G-001_06078.dwg
LAYOUT: G-001
D
G-001
COVER SHEET
G-002
RESPONSIBILITY & DOOR SCHEDULE
A-101
DEMOLITION / LEASE PLAN
A-102
FLOOR PLAN
A-103
FINISH / FIXTURE PLAN
A-104
REFLECTED CEILING PLAN
A-201
ELEVATIONS
A-301
NOT USED
A-401
STOREFRONT ELEVATION
A-501
NOT USED
A-502
GENERAL DETAILS
A-503
FRAMING DETAILS
A-504
FRAMING DETAILS
A-505
NOT USED
A-701
ARCHITECTURAL SPECIFICATIONS
A-702
ARCHITECTURAL SPECIFICATIONS
THIS PROJECT IS A TENANT BUILD OUT OF A EXISTING
MERCANTILE SPACE IN AN EXISTING INTERIOR CENTER.
NORTH
PROJECT CONTACTS
C
Project Manager
B
M-101 MECHANICAL PLAN & LEGEND
M-501 MECHANICAL DETAILS & ABBREVIATIONS
M-MERCANTILE
IIB
A
TENANT SEPARATION WALLS:
SALES/NON-SALES WALLS:
CEILING:
COLUMNS:
1 HR
0 HR
0 HR
0 HR
SALES AREA:
NON-SALES AREA:
TOTAL:
436/30 = 15
21/300 = 1
16
EXITS REQUIRED:
EXITS PROVIDED:
1
1
SHREMSHOCK ARCHITECTS
7400 W. CAMPUS RD. SUITE 150
NEW ALBANY, OH 43054
CONTACT: JASON RICHARDSON
PHONE: 614-545-4550
E-MAIL: [email protected]
SYMBOLS LEGEND
A1
SECTION ID
SHEET NUMBER
A-301
A1
A-401
-
-
-
NOT REQUIRED
NOT REQUIRED
NOT REQUIRED
SUNGLASS HUT
LA PLAZA MALL
M-701 FIRE PROTECTION SPECIFICATIONS
Architect
LUXOTTICA
4000 LUXOTTICA PLACE
MASON, OH 45040
CONTACT: SHEILA HULL
PHONE: 513-765-3847
E-MAIL: [email protected]
USE GROUP:
CONSTRUCTION TYPE:
SEISMIC CATEGORY:
DRINKING FOUNTAIN:
PUBLIC ACCESS:
SERVICE SINK:
M-301 MECHANICAL SCHEDULES
SIMON PROPERTY GROUP
225 WEST WASHINGTON ST.
INDIANAPOLIS, IN 46204
CONTACT: LUCRETIA SAPPINGTON
PHONE: 317-263-7125
E-MAIL: [email protected]
Store Planner
IBC 2012
IPC 2012
NEC 2011
IMC 2012
IECC 2009
TAS
WATER CLOSETS:
LAVATORIES:
Landlord
LUXOTTICA
4000 LUXOTTICA PLACE
MASON, OH 45040
CONTACT: SCOTT YOUNG
PHONE: 940-445-3122
E-MAIL: [email protected]
BUILDING CODE:
PLUMBING CODE:
ELECTRICAL CODE:
MECHANICAL CODE:
ENERGY CODE:
ACCESSIBILITY:
ROOM
NAME
DETAIL ID
SHEET NUMBER
101
NAME
NUMBER
M-702
MECHANICAL SPECIFICATIONS
E-101
POWER PLAN
E-102
LIGHTING PLAN & LIGHTING LEGEND
E-501
ELECTRICAL DETAILS & ABBREVIATIONS
E-601
ELECTRICAL SINGLE LINE DIAGRAM AND PANEL SCHEDULES
E-701
ELECTRICAL SPECIFICATIONS
E-702
ELECTRICAL SPECIFICATIONS
2200 S. 10TH STREET
McALLEN, TX 78503
SPACE #Q14-C
2.0 TYPE: PREMIUM
AREA CALCULATIONS
A1
MEP Consultant
Purchasing Coordinator
A
LUXOTTICA
4000 LUXOTTICA PLACE
MASON, OH 45040
CONTACT: DAWN SPARKS
PHONE: 513-765-3947
E-MAIL: [email protected]
1
A1
SHREMSHOCK ENGINEERING, INC.
7400 W. CAMPUS RD. SUITE 150
NEW ALBANY, OH 43054
CONTACT: JEROMY PERRY
PHONE: 614-545-4550
E-MAIL: [email protected]
2
3
ELEVATION ID
SHEET NUMBER
A-201
A-201
FLOOR
0'-0"
4
LOCATION
ELEVATION
STOREFRONT FRONTAGE:
SHEET NUMBER
ELEVATION ID
A7
NORTH
1
1
5
6
SALES AREA
STOCK ROOM:
435 SF
21 SF
TOTAL:
LEASE TOTAL
456 SF
446 SF
8
SGH STORE #: 6078
DRAWN BY: ALW
REVIEWED BY: MLH/JMA
AUTHORIZED FOR:
22 LF
COVER
SHEET
G-001
MATERIAL NUMBER
7
LA PLAZA MALL
F
BUILDING CODE
AT
LANDLORD NOTES
REV. 1
MALL KEY PLAN
9
10
11
12
13
14
4
5
6
ABBREVIATIONS
K
AMERICANS WITH DISABILITIES ACT
ACCESSIBILITIES GUIDELINES
ABOVE FINISH FLOOR
CENTERLINE
CEILING
CERAMIC TILE
COLUMN
CONCRETE
CONTINUOUS
DIAMETER
DIMENSION
DETAIL
DRAWINGS
ELECTRICAL CONTRACTOR
EXISTING
EXPOSED
EQUAL
FIXTURE CONTRACTOR
GYPSUM BOARD
GENERAL CONTRACTOR
A.F.F.
CL.
CLG.
CT.
COL.
CONC.
CONT.
DIA.
DIM.
DTL.
DWGS.
E.C.
EX. OR (E)
EXP.
EQ.
F.C.
G.B.
G.C.
J
G.A.T.
M.C.
N.I.C.
O.C.
OPP.
O/
P.C.
REQ.
R.
SCH.
SIM.
TYP.
U.N.O.
V.I.F.
VERT.
W.C.
WD.
W.R.
A1
H
B1
NOMINAL SIZE
MATERIAL
FINISH
MATERIAL
FINISH
FIRE RATING
HDWR.
(E)ROLLING GRILLE
ENTRY
SEE PLANS
EXISTING
EXISTING
EXISTING
EXISTING
-
A
CLOSET
2'-8"W. x 7'-0"H.
x 1 3/4"
HOLLOW METAL
P-3
HOLLOW METAL
P-3
-
- EXISTING TO REMAIN
EXISTING TO REMAIN
B
- UNFINISHED DOOR AND FRAME SUPPLIED, INSTALLED AND FINISHED BY G.C. (U.N.O.)
PUSH: HAGER HINGE CO.: #40R, 4"W x 16"H, FINISH US26D
PULLS: HAGER HINGE CO.: #4L, WROUGHT DOOR PULL 1" DIA. x 12"H, FINISH US26D
DOOR CLOSER: CORBIN RUSSWIN DC4610 SERIES PARALLEL ARM WITH HOLD OPEN.
HINGES: BOMMER 1 1/2 PAIR PER LEAF, 4-1/2" x 4-1/2", NO. BB5004N STANDARD WEIGHT, AVERAGE FREQUENCY, FULL
MORTISE, BALL BEARING HINGE, FINISH: STAINLESS STEEL
KICKPLATE: STANLEY DOOR SYSTEM; FULL WIDTH x 10"H x 1/8" STAINLESS STEEL INSTALLED 1" FROM BOTTOM OF DOOR
FLOOR MOUNTED STOP: IVES MODEL #FS13US26 CAST BRASS, CHROME PLATED (OR EQUAL)
SILENCERS: G.C. TO SELECT
F
USER: JGRAY
PLOTTED: 7/16/2015 - 4:03 PM
D
B1
A1
SE
D
7'-0"
C1
D1
VERIFYING EXISTING DOOR HARDWARE TYPE AT LOCATIONS WHERE EXISTING EXTERIOR/ENTRANCE DOORS ARE TO REMAIN.
ANY NON-GENERIC/BRANDED DOOR HARDWARE TO BE IDENTIFIED AND REPLACEMENT MUST BE COORDINATED WITH
LUXOTTICA PROJECT MANAGER.
A1
SCALE:
DOOR SCHEDULE
1
2
3
4
NOTE:
VERIFY ALL ITEMS IN THIS SCHEDULE FOR ACCURACY PRIOR TO BEGINNING CONSTRUCTION. REPORT
ANY DISCREPANCIES TO THE PROJECT MANAGER IMMEDIATELY.
11
REMARKS
BUILDING PERMIT
T
PERMIT APPLIED FOR BY TENANT / OBTAINED AND PAID FOR BY CONTRACTOR
TEMPORARY BARRICADES (WITH GRAPHIC)
T
T
TEMPORARY CONSTRUCTION WINDOW VINYL
-
-
G.C. TO COORDINATE WITH LANDLORD AND BOSTON BARRICADE
DIVISION 03 - CONCRETE
FURN. INST.
REMARKS
CONCRETE SLAB
E
G.C. TO VERIFY AS REQUIRED, NOTIFY P.M. OF CONDITION OF SLAB
B
DIVISION 05 - METALS
FURN. INST.
STRUCTURAL STEEL
E
TENANT SEPARATION WALL
E
DIVISION 08 - OPENINGS
12
13
14
1.
THE CONTRACTOR SHALL HAVE EVIDENCE OF CURRENT WORKER'S COMPENSATION INSURANCE ON FILE IN
COMPLIANCE WITH LOCAL CODES.
2.
BEFORE COMMENCEMENT OF WORK, THE CONTRACTOR SHALL SHOW EVIDENCE OF ALL INSURANCE
REQUIREMENTS.
3.
THE CONTRACTOR SHALL BE FAMILIAR WILL ALL LANDLORD REQUIREMENTS AND SHALL BE RESPONSIBLE FOR
COMPLIANCE WITH REQUIREMENTS. THE CONTRACTOR SHALL INVESTIGATE LOCAL CODES AND PROCEDURES AND
SHALL COMPLY WITH REQUIREMENTS.
4.
SIGN CONTRACTOR TO OBTAIN SIGN PERMITS FROM BUILDING DEPARTMENT AS APPLICABLE.
5.
CONTRACTOR SHALL CONTACT LANDLORD REPRESENTATIVE BEFORE CONSTRUCTION COMMENCES.
6.
ALL CONDUIT, EQUIPMENT AND MATERIALS SHALL BE IN FULL ACCORDANCE WITH THE LATEST SAFETY RULES AND
REGULATION OF ALL AUTHORITIES AND AGENCIES HAVING JURISDICTION.
REMARKS
FURN. INST.
REMARKS
THE CONTRACTOR SHALL MAINTAIN FOR THE ENTIRE DURATION OF THE WORK ALL EXITS, EXIT LIGHTING, FIRE
PROTECTION DEVICES AND ALARMS IN CONFORMANCE WITH ALL APPLICABLE CODES AND ORDINANCES.
9. DURING ALL PHASES OF WORK DO NOT DISTURB THE DELIVERIES AND FUNCTIONS OF ADJACENT AND NEIGHBORING
TENANTS.
FURN. INST.
REMARKS
STOREFRONT SYSTEM
-
-
N/A
ROLLING GRILLE
E
E
10. EACH CONTRACTOR SHALL LEAVE THE SITE IN A NEAT, CLEAN AND ORDERLY CONDITION UPON THE COMPLETION OF
THEIR WORK ON A DAILY BASIS. AREA OF WORK TO BE DUSTED, SWEPT AND MOPPED TO SAME CONDITION AS
START OF WORK. ALL WASTE OR EXCESS MATERIALS SHALL BE REMOVED FROM THE SITE PROMPTLY. THE G.C.
SHALL BE RESPONSIBLE FOR THE REMOVAL AND DISPOSAL OF ALL TRASH, INCLUDING TRASH GENERATED FROM
OWNER FURNISHED ITEMS AND BY OWNERS CONTRACTORS FOR THE DURATION OF THE PROJECT.
DOOR LOCK CORES AND KEYS
T
T/G
COORDINATE LOCKSMITH IF NOT COMPATIBLE WITH TENANT KEY SYSTEM
11. ALL EXISTING WORK NOT IN THIS SCOPE OF WORK SHALL BE MAINTAINED IN ITS ORIGINAL CONDITION, U.N.O.
DIVISION 09 - FINISHES
FURN. INST.
REMARKS
12. PROTECT WORK FROM DAMAGE RESULTING FROM THIS WORK.
TENANT SEPARATION PARTITIONS (GYPSUM WALLBOARD)
E
E/G
G.C. TO VERIFY, PATCH/REPAIR AS REQUIRED
STOREFRONT BULKHEAD
E
E/G
G.C. TO VERIFY, PATCH/REPAIR AS REQUIRED
CEILING
E/G
E/G
STOREFRONT TILE
-
-
CERAMIC TILE FLOORING
T
G
GROUT
G
G
MALL FLOORING
E
E
ALUMINUM BASE MOULDING (HPL-06)
T
T
MILLWORKER TO COORDINATE WITH G.C.
WALK-OFF MAT (RECESSED)
-
-
N/A
DIVISION 10 - SPECIALTIES
FURN. INST.
REMARKS
SIGNAGE
E
E
(E) STOREFRONT SIGNAGE TO REMAIN
17. NO MATERIAL SUBSTITUTIONS WILL BE ALLOWED UNLESS NOTED OTHERWISE OR SUBMITTED IN WRITING TO AND
APPROVED BY THE OWNER'S REPRESENTATIVE.
AWNING
-
-
N/A
18. ANY WOOD CONSTRUCTION SHALL BE FIRE RETARDANT TREATED, U.N.O.
DIVISION 12 - FURNISHINGS
FURN. INST.
REMARKS
MILLWORK FLOOR FIXTURES
T
T
G.C. TO COORDINATE WITH VENDOR
U-RAIL GRAPHIC HANGING SYSTEM (TBD)
T
G
LOOSE FIXTURES/PROPS
T
T
G.C. TO COORDINATE WITH VENDOR. G.C. TO UNBOX/ UNWRAP AND STORE IN B.O.H.
MISCELLANEOUS EQUIPMENT
T
G
SEE EQUIPMENT SCHEDULE
GRAPHICS GRID
-
-
N/A
TOILET ACCESSORIES
-
-
N/A
DIVISION 21 - FIRE SUPPRESSION
FURN. INST.
REMARKS
SPRINKLER SYSTEM MODIFICATIONS
G
COORDINATE WITH LANDLORD AND TENANT. LAYOUT TO ALIGN WITH LIGHT FIXTURES
21. G.C. SHALL COORDINATE WORK PERFORMED BY OTHER CONTRACTORS. ANY DISCREPANCIES SHALL BE BROUGHT
TO THE OWNER'S ATTENTION (VERBALLY AND DOCUMENTED IN WRITING) BEFORE PROCEEDING WITH WORK.
FIRE SPRINKLER MAIN
E
REMARKS
22. SHOULD A CONFLICT EXIST BETWEEN THE CONSTRUCTION DOCUMENTS AND/OR THE SPECIFICATIONS, THE
OWNER'S REPRESENTATIVE SHALL BE INFORMED (VERBALLY AND DOCUMENTED IN WRITING) OF THIS DISCREPANCY
IMMEDIATELY, AT WHICH TIME OWNER'S REPRESENTATIVE SHALL PROVIDE DIRECTION ON HOW TO PROCEED.
Shremshock Architects, Inc.
7400 W. Campus Rd. Suite 150 New Albany, OH 43054
t: 614 545 4550 | f: 614 545 4555 | shremshock.com
Gerald S. Shremshock, Architect
Timothy J. Shremshock, Architect
SEAL
14. G.C. SHALL BE RESPONSIBLE FOR COORDINATION WITH OWNERS REPRESENTATIVE TO PROVIDE A TIMELY ARRIVAL
OF ALL MATERIALS, EQUIPMENT AND OTHER SUCH ITEMS TO BE UTILIZED ON THIS PROJECT. G.C. SHALL NOTIFY
OWNER'S REPRESENTATIVE IN WRITING WITHIN 5 DAYS OF DATE OF APPROVED WORK AUTHORIZATION OF THOSE
ITEMS THAT MAY BY READILY AVAILABLE. IF NOTIFICATION IS NOT PROVIDED TO THE OWNER'S REPRESENTATIVE,
THE CONTRACT ACCEPTS RESPONSIBILITY FOR THE PROPER ORDERING AND FOLLOW-UP OF SPECIFIED ITEMS AND
WILL PURSUE WHATEVER MEANS NECESSARY AT NO ADDITIONAL COST TO OWNER.
N/A
1/8" GROUT JOINTS TYP.
15. CONTRACTOR TO ENSURE AVAILABILITY OF ALL SPECIFIED ITEMS SO AS NOT TO CREATE A HARDSHIP TO THE
OWNER AND NOT DELAY PROGRESS OF THE WORK. NO EXTENSION OF TIME SHALL BE PERMITTED.
G
16. CONTRACTOR SHALL BE RESPONSIBLE TO RECEIVE, INVENTORY, STORE, AND SECURE ANY OWNER FURNISHED
ITEMS SUPPLIES AND DELIVERED TO THE JOBSITE, OR OTHER AGREED UPON LOCATION, AND FORWARD THE
RECEIVING DOCUMENTS TO THE OWNER.
19. G.C. SHALL VISIT THE SITE PRIOR TO SUBMITTAL OF BID TO DETERMINE CONDITIONS AFFECTING THE WORK. ANY
ITEMS WHICH ARE NOT COVERED IN THE BID DOCUMENTS OR ANY PROPOSED SUBSTITUTIONS SHALL BE LISTED
SEPARATELY AND QUALIFIED IN THE CONTRACTOR'S BID. SUBMITTAL OF BID SHALL SERVE AS EVIDENCE OF
KNOWLEDGE OF EXISTING CONDITIONS AND ANY MODIFICATIONS WHICH ARE REQUIRED TO MEET THE INTENT OF
THE DRAWINGS AND SPECIFICATIONS. FAILURE TO VISIT THE SITE DOES NOT RELIEVE THE CONTRACTOR OR
RESPONSIBILITY IN PERFORMANCE OF WORK.
20. ALL CONTRACTORS, SUBCONTRACTORS, VENDORS AND MATERIAL SUPPLIES SHALL BE RESPONSIBLE FOR
REVIEWING THE COMPLETE SET OF DOCUMENTS AS SHOWN IN THE SHEET INDEX. FAILURE TO REVIEW
CONSTRUCTION DOCUMENTS WILL NOT RELIEVE ANY CONTRACTORS, SUBCONTRACTORS, VENDORS OR MATERIAL
SUPPLIES FOR PERFORMING WORK OR PROVIDING MATERIALS REQUIRED FOR THE COMPLETION OF THIS PROJECT
AS DEFINED WITHIN THE DOCUMENTS AT TIME OF BID.
-
-
WATER METER
-
-
23. INSPECT SITE AND VERIFY FIELD DIMENSIONS BEFORE COMMENCING WITH CONSTRUCTION. NOTIFY OWNER'S
REPRESENTATIVE AND LANDLORD IMMEDIATELY IF THERE ARE ANY DISCREPANCIES.
GAS METER
-
-
24. DO NOT SCALE DRAWINGS. WRITTEN DIMENSIONS TAKE PRECEDENCE OVER SCALED DRAWINGS.
PLUMBING FIXTURES
-
-
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING
FURN. INST.
25. ARCHITECTURAL DRAWINGS TAKE PRECEDENCE OVER OTHER DRAWINGS FOR LAYOUT DIMENSIONS AND NUMBER
OF ITEMS PROVIDED. UPON DISCOVERY OF DISCREPANCIES BETWEEN ARCHITECTURAL DRAWINGS AND
ENGINEERING DRAWINGS, OWNER SHALL BE IMMEDIATELY NOTIFIED IN WRITING.
AIR CURTAIN
-
-
EXHAUST FANS AND VENTING
-
-
HVAC UNIT
E
-
HVAC CONTROLS
E
G
ENERGY MANAGEMENT SYSTEM (EMS)
-
-
HVAC DISTRIBUTION DUCTWORK, DIFFUSERS
E/G
G
CURBS & SUPPORTS FOR CONDENSING UNITS
E
-
29. COLUMN CENTER LINE (OR GRID LINES) ARE SHOWN FOR DIMENSIONS. VERIFY EXACT LOCATION IN FIELD.
SMOKE EVACUATION SYSTEM & CONTROLS
-
-
30. OWNER'S REPRESENTATIVE AND TENANT ARE THE SAME FOR PURPOSES OF THESE DRAWINGS.
DUCT SMOKE DETECTORS
-
-
DIVISION 26 - ELECTRICAL
FURN. INST.
ELECTRICAL SERVICE, CONDUIT, WIRING
E
ELECTRIC METER, SEPARATE
E
REMARKS
26. IF ANY ERRORS OR OMISSIONS APPEAR IN THE CONTRACT DOCUMENTS, CONTRACTOR SHALL NOTIFY OWNER IN
WRITING OF SUCH ERRORS OR OMISSIONS.
27. DIMENSIONS SHOWN ON PLANS ARE TO FACE OF CMU, CONCRETE COLUMNS OR GRID LINES AND FACE OF
GYPSUM BOARD UNLESS NOTED OTHERWISE.
REUSE AND RELOCATE EXISTING THERMOSTAT
28. THE CONTRACTOR SHALL REVIEW ALL CONSTRUCTION DOCUMENTS, VERIFY ALL DIMENSIONS AND FIELD
CONDITIONS AND CONFIRM WORK IS BUILDABLE AS SHOWN. ANY CONFLICTS OR OMISSIONS, ETC. SHALL BE
IMMEDIATELY REPORTED TO THE ARCHITECT FOR CLARIFICATION PRIOR TO PERFORMANCE OF ANY WORK IN
QUESTION.
AIR BALANCING TO BE COMPLETED BY GC
REMARKS
31. ALL OPENINGS, FLASHING, COUNTER FLASHING, AND EXPANSION JOINTS SHALL BE WATERTIGHT IN EXTERIOR
STORES.
G
120/208V, 3PH, 4W, 100A FUSED DISCONNECT TO REMAIN AS IS. GC TO REPLACE IF EXISTING
FUSED DISCONNECT NOT IN GOOD WORKING ORDER.
32. ALL OPEN JOINTS, PENETRATIONS AND OTHER OPENINGS IN THE BUILDING ENVELOPE SHALL BE SEALED, CAULKED,
GASKETED OR WEATHER-STRIPPED TO LIMIT AIR LEAKAGE IN EXTERIOR STORES.
G
EXISTING ELECTRICAL METER TO REMAIN AS IS, GC TO COORDINATE WITH LANDLORD'S
REPRESENTATIVE AND LOCAL UTILITY COMPANY.
33. ALL SAW CUTTING AND CORING LOCATIONS SHALL BE REVIEWED AND COORDINATED WITH THE LANDLORD PRIOR TO
CUTTING/ CORING.
(1) 120/208V, 3PH, 4W, 100A, MCB. GC TO PROVIDE CIRCUIT BREAKERS AND ANY MODIFIICATION
TO PANEL BOARD AS INDICATED IN PANEL SCHEDULE.
34. G.C. IS RESPONSIBLE FOR MAINTAINING REQUIRED FIRE RATINGS AND FIRE PROOFING IN ALL INSTANCES.
ELECTRICAL PANEL
G
G
TRACK CURRENT LIMITING PANEL
-
-
EMERGENCY LIGHTING
G
G
EXIT SIGNS
G
G
GC TO PROVIDE JUNCTION BOX TO TIE INTO LANDLORD'S FIRE ALARM SYSTEM, HORN AND STROBES.
ALL FIRE ALARM SYSTEM DEVICES BE BY 'EDWARDS EST' ALL FIRE ALARM WORK TO BE DONE BY
LANDLORD APPROVED CONTRACTOR 'GLOBAL RISK CONSULTANTS' AT TENANT CONTRACTOR'S
EXPENSE.
G
G
LIGHT FIXTURES
G
G
LAMPS
G
G
SOUND SYSTEM AND SPEAKERS
T
G
G.C. TO COORDINATE WITH VENDOR
TENANT TELEPHONE EQUIPMENT
T
G
G.C. TO COORDINATE WITH VENDOR
TELEPHONE CONDUIT TO SPACE
E
-
TELEPHONE WIRING TO SPACE
E
-
SECURITY - FACILITY/HARDWARE & WIRING/VECTOR (ALARMS)
T
T
G.C. TO COORDINATE WITH VENDOR
SECURITY - PRODUCT/HARDWARE & WIRING/- A1 (CAMERAS)
T
T
G.C. TO COORDINATE WITH VENDOR
TRAFFIC COUNTER
T
T
G.C. TO COORDINATE WITH VENDOR
7
35. GC TO COVER THE STOREFRONT WINDOWS AND DOORS WITH KRAFT PAPER FROM THE TIME THE BARRICADE IS
REMOVED UNTIL THE STORE OPENS.
36. GC TO SCHEDULE A PRE-TURNOVER CLEANING FOR WEDNESDAY MORNING AND A FINAL DETAIL CLEANING TUESDAY
MORNING AT 9:00 AM PRIOR TO OPENING.
FIRE ALARM SYSTEM
6
CONSULTANT PROJECT # 150343
13. WHEN CONTRACTOR ACCEPTS DELIVERY OF ALL ITEMS NOTED ON PLANS WHETHER IN CONTRACT OR NOT IN
CONTRACT, THE G.C. SHALL BE RESPONSIBLE FOR LOSS AND/OR DAMAGE TO THESE ITEMS.
WATER AND SEWER STUB
5
A Subsidiary of the Luxottica Group
4000 Luxottica Place
Mason, Ohio 45040
8. PROVIDE ADDITIONAL EXIT SIGNS AND FIRE EXTINGUISHERS IN TYPE , NUMBER, AND LOCATION AS DIRECTION BY
THE AUTHORITIES HAVING JURISDICTION.
SEE PLANS
E
3'-0"
NO
TU
7'-0"
NO
TU
(E)
1.
3'-0"
2'-8"
7'-0"
B
SE
D
PER PLAN
10
GENERAL NOTES
DIVISION 01 - GENERAL
FURN. INST.
PER PLAN
P:\SGH\150343 SGH-La Plaza Mall Mcallen, TX\G-002_06078.dwg
LAYOUT: G-002
E
C
9
7.
LOCATION
A
A
ITEM
FRAME INFORMATION
G.C. TO REPLACE ANY MISSING OR DAMAGED HARDWARE
G
T = TENANT/OWNER
G = GENERAL CONTRACTOR
L = LANDLORD
E = EXISTING
GYPSUM CEILING TILE
MECHANICAL CONTRACTOR
NOT IN CONTRACT
ON CENTER
OPPOSITE
OVER
PLUMBING CONTRACTOR
REQUIRED
RADIUS
SCHEDULED
SIMILAR
TYPICAL
UNLESS NOTED OTHERWISE
VERIFY IN FIELD
VERTICAL
WATER CLOSET
WOOD
WATER RESISTANT
DOOR INFORMATION
MARK
8
RESPONSIBILITY SCHEDULE
FURNISHED
BY
A.D.A.A.G.
7
LA PLAZA MALL
3
AT
2
INSTALLED
BY
1
8
37. TIMECLOCK TO BE SET TO "ON" 30 MINUTES PRIOR TO MALL OPENING AND 30 MINUTES AFTER MALL CLOSE.
38. INSTRUCTIONS FOR MODIFYING THE TIMECLOCK OPERATION TO BE LEFT WITH THE STORE AND DETAILED
MANAGEMENT AT TURNOVER.
39. GC IS RESPONSIBLE TO ACCEPT DELIVERY OF ALL PROPS - UN-BOX, SORT AND COUNT. THE SUPERINTENDENT
SHOULD GIVE A CHECK-IN SHEET NOTING ALL DISCREPANCIES TO THE PROJECT MANAGER UPON ARRIVAL FOR THE
PUNCHLIST.
40. ALL CARDBOARD SHOULD BE REMOVED FROM THE SITE PRIOR TO TURNOVER, HOWEVER, THE PROPS SHOULD BE
LEFT IN THE PLASTIC TO PROTECT FROM DAMAGE/DUST.
SUNGLASS HUT
LA PLAZA MALL
2200 S. 10TH STREET
McALLEN, TX 78503
SPACE #Q14-C
2.0 TYPE: PREMIUM
SGH STORE #: 6078
DRAWN BY: ALW/CHC/EDS
REVIEWED BY: MLH/JMA
AUTHORIZED FOR:
RESPONSIBILITY &
DOOR SCHEDULE
G-002
9
10
11
12
13
14
1
2
3
4
5
6
7
8
9
10
11
12
1.
K
TENANT TO SUPPLY GRAPHICS. COORDINATE WITH
LANDLORD BARRICADE SIGNAGE REQUIREMENTS
13'-3"± A.F.F.
14
GENERAL NOTES
ELEVATION SHOWN IS A REPRESENTATION OF INTENT. ACTUAL VINYL
GRAPHIC IS TO BE SUBMITTED BY BOSTON BARRICADE TO LANDLORD
FOR REVIEW BY EX PEDITOR TO PRODUCTION AND INSTALLATION.
TURN IN
BARRICADE
13
2.
TURN IN
BARRICADE
3.
T.O. BARRICADE
4.
5.
J
6.
7.
TAKE ALL NECESSARY PRECAUTIONS TO ENSURE THE SAFETY OF THE PUBLIC
AND/OR WORKERS ON THE JOB AND TO PREVENT ACCIDENTS OR INJURY TO ANY
PERSON ON, ABOUT, OR ADJACENT TO THE PREMISES. COMPLY WITH ALL LAWS,
ORDINANCES, CODES, RULES AND REGULATIONS RELATIVE TO SAFETY AND THE
PREVENTION OF ACCIDENTS.
THIS DEMOLITION PLAN IS TO BE USED IN CONJUNCTION WITH THE ENTIRE SET OF
WORKING DRAWINGS. DO NOT REMOVE OR DEMOLISH ANYTHING WITHOUT
VERIFYING AND COORDINATING WITH ALL GENERAL TRADES AS TO HOW THEY
RELATE TO THE OVERALL PROJECT.
ALL CONTRACTORS SHALL BE RESPONSIBLE FOR DEMOLISHING AND REMOVING
EXISTING CONSTRUCTION WHICH WILL INTERFERE WITH THEIR NEW WORK AND ANY
TEMPORARY BRACING OR PERMANENT SUPPORT STRUCTURES.
WHEN EXISTING ELECTRICAL SERVICE, POWER, AND LIGHTING IS REMOVED, STUB
BACK AND CAP AS REQUIRED IN AREAS BETWEEN EXISTING CONDITIONS AND NEW
WORK.
ANY EXISTING ROOFTOP AIR CONDITIONING UNIT, ROOF CURBS AND ALL
ASSOCIATED DUCTWORK, GRILLES, DIFFUSERS, HANGER, CONTROL WIRING,
ELECTRICAL WIRING, CONDUITS, AND CONDUIT HANGERS, IF APPLICABLE PER
PROJECT STORE SITE, TO REMAIN UNLESS NOTED OTHERWISE ON PLANS. REFER
TO MECHANICAL DRAWINGS.
IN ACCORDANCE WITH THE DRAWINGS, THOSE ITEMS WHICH ARE REMOVED, AND
ARE NOT RELOCATED OR REUSED, SHALL BE DISPOSED OF BY THE G.C.
PROVIDE AND INSTALL TEMPORARY BARRICADE. COORDINATE REQUIREMENTS
WITH LANDLORD.
A Subsidiary of the Luxottica Group
4000 Luxottica Place
Mason, Ohio 45040
CONSULTANT PROJECT # 150343
Shremshock Architects, Inc.
7400 W. Campus Rd. Suite 150 New Albany, OH 43054
t: 614 545 4550 | f: 614 545 4555 | shremshock.com
Gerald S. Shremshock, Architect
Timothy J. Shremshock, Architect
SEAL
TEMPORARY BARRICADE
H
0'-0" A.F.F.
FINISH FLOOR
1.
BOSTON BARRICADE SHALL CONSTRUCT A TEMPORARY BARRICADE PER LL
REQUIREMENTS.
2.
BARRICADE IS TO BE 100% COMPLETE AND READY FOR GRAPHICS TO BE
INSTALLED NOT MORE THAN TWO DAYS AFTER CONSTRUCTION START. G.C. TO
CONTACT OWNERS REPRESENTATIVE UPON COMPLETION TO COORDINATE
GRAPHICS INSTALLATION.
3.
G.C. IS RESPONSIBLE FOR MAINTAINING BARRICADE DURING CONSTRUCTION.
BARRICADE PROVIDED
BY BOSTON BARRICADE
4'-0"±
(UNFOLDED)
4'-0"±
(UNFOLDED)
22'-1"±
4. REMOVE BARRICADE WHEN 100% OF STOREFRONT IS COMPLETE ON THE EVENING
BEFORE G.C.'S PUNCHLIST IS COMPLETED, PRIOR TO OWNER VERIFICATION, AND
AFTER LANDLORD APPROVAL IS RECEIVED. CARE IS TO BE TAKEN WHEN
DISASSEMBLING AND REMOVING BARRICADE. ON INTERIOR SIDE (STORE SIDE),
PAPER WINDOWS WITH WHITE CONSTRUCTION PAPER OVER GLAZING ONLY. TRIM
1/2" OFF EDGES AND TAPE CONTINUOUSLY AROUND PERIMETER WITH WHITE TAPE.
G.C. IS TO RESTORE NEUTRAL PIER(S), MALL FLOORING AND BULKHEAD TO A 'LIKE
NEW' CONDITION AND FINISH.
G
G1
SCALE:
BARRICADE ELEVATION
F
20'-8"
ADJACENT
TENANT (N.I.C.)
E
1
12
TYP.
6.
NOT USED
7.
EXISTING MILLWORK & VALANCE LIGHTING TO BE REMOVED.
5'-6"
13. NOT USED.
14. NOT USED.
-
15. EXISTING TENANT SEPARATION WALL TO REMAIN.
16. EXISTING THERMOSTAT TO BE REMOVED.
17. EXISTING ELECTRICAL PANEL AND WALL TO BE REMOVED.
8
EXISTING SOFFIT TO REMAIN & BE REWORKED. SEE SHEET
A-104 FOR NEW CONDITION.
22'-1"
5
9
10
G1
19. NOT USED.
A-101
20. NOT USED.
1
12
7
22. (E) INSULATED ROOF DRAIN AT ±14'-11 1/2" AFF TO REMAIN
MALL
COMMON AREA
2
21
25
21. (E) ELECTRICAL CONDUIT RACK AT ±15'-0" AFF TO REMAIN
15'-0"
11
C
REMOVE EXISTING CASHWRAP, FLOOR CASEWORK, AND ASSOCIATED ELECTRICAL &
DATA HOOK-UP. REMOVE WIRING/ CONDUIT BACK TO SOURCE.
12. REMOVE EXISTING TRACK.
22
12
15
5.
11. SALVAGE EXISTING SPRINKLER HEADS FOR RELOCATION. REFER TO SHEET A-104
FOR NEW LOCATIONS.
3
23. (E) RTU AND SUPPLY/RETURN TRUNKS TO REMAIN
24. (E) SPRINKLER MAIN AND PIPES TO REMAIN
18
TYP.
25. (E) TENANT DUCTWORK AT ±13'-8" TO REMAIN / BE REWORKED. SEE MECHANICAL
SHEETS
24
B
10"
LAYOUT: A-101
P:\SGH\150343 SGH-La Plaza Mall Mcallen, TX\A-101_06078.dwg
PLOTTED: 7/16/2015 - 4:03 PM
USER: JGRAY
FROM LEASE
LINE
25
23
ADJACENT
TENANT (N.I.C.)
EXISTING ROLLING GRILLE ENTRY DOOR TO REMAIN. G.C. TO HAVE DOOR VENDOR
SERVICE AND CLEAN ROLLING GRILL.
10. REMOVE EXISTING GYP. BD. CEILING, LIGHT FIXTURES, ACCESS PANEL, EXIT SIGNS,
SPRINKLER HEADS, AND MECHANICAL DIFFUSERS ABOVE IN THIS AREA REFER TO
SHEET A-104 FOR NEW CONDITIONS AND RELOCATIONS.
-
16
4'-0"
1
3.
9. REMOVE EXISTING FLOORING MATERIAL. PATCH AND PREPARE FLOOR AS REQ'D TO
PROVIDE SMOOTH FLOOR FOR NEW FLOORING PER PLAN ON SHEET A-103. CAP
EXISTING MECHANICAL, PLUMBING AND ELECTRICAL SERVICES FLUSH WITH EXISTING
SLAB AS REQ'D.
7
D
BARRICADE BY BOSTON BARRICADE. REFER TO VENDOR SHOP DRAWINGS
8. EXISTING STOREFRONT SIGNAGE TO REMAIN.
9"
15
2.
4. NOT USED.
4"
20'-4"
LEASE LINE
AT
-
1.
17
1
12
7
SGH STORE #: 6078
15
DRAWN BY: ALW
GRAPHICAL KEY
REVIEWED BY: MLH/JMA
EXIST. TO BE REMOVED U.N.O.
EXIST. TO REMAIN U.N.O.
AUTHORIZED FOR:
DEMOLITION / LEASE PLAN
NORTH
A
A1
A-101
DEMOLITION / LEASE PLAN
1
2
SUNGLASS HUT
LA PLAZA MALL
2200 S. 10TH STREET
McALLEN, TX 78503
SPACE #Q14-C
2.0 TYPE: PREMIUM
-
ADJACENT
TENANT (N.I.C.)
SCALE:
LA PLAZA MALL
KEY NOTES
3
4
5
6
7
8
9
10
11
12
13
14
2
3
4
5
6
7
8
ACCESSORY
ID
DESCRIPTION
MODEL #
MANUFACTURER
1
GRAB BAR
B-5806x42
BOBRICK
2
GRAB BAR
B-5806x36
BOBRICK
3
VERTICAL GRAB BAR
B-5806x18
BOBRICK
4
MIRROR
B-165 1836
BOBRICK
ABOVE LAV. REFER TO G6/A-502
5
MIRROR
B-165 2460
BOBRICK
RESTROOM DOOR
K
J
6
TOILET TISSUE DISPENSER
B-5543
BOBRICK
7
UTILITY HOOK
B-2116
BOBRICK
8
HOOK STRIP
B-232x24
BOBRICK
9
MOP HOLDER
B-223x24
BOBRICK
REMARKS
NON-LOCKING
10
EQUIPMENT
NAME
DESCRIPTION
MODEL #
MANUFACTURER
LOCKERS(#)
EMPLOYEE LOCKERS
36168/
36368
LOCKERS.COM
SAFE
SMALL DROP SLOT SAFE
UC-025K
SENTRYSAFE
MICRO
MICROWAVE OVEN
M01108SST
AVANTI
FRIDGE
REFRIGERATOR
RM3316B
AVANTI
XxYxZ
PIPP SHELVING
STORAGE SHELVING
11
REMARKS
COLOR: GRAY, LOCKS: 33390, # =
NUMBER OF 12" WIDE UNITS
BOLTED TO FLOOR BY G.C.
KT1024
SIMPLE HUMAN
11
LAVATORY FAUCET
7803.101
AMERICAN STANDARD
X = WIDTH, Y = DEPTH, Z = HEIGHT,
SEE A7/A-502
PIPP
STAPLES #180969
TOILET ACCESSORY SCHEDULE
EQUIPMENT SCHEDULE
SCALE:
9.
10.
11.
D
E
S
U
OT
GRAB BAR
(E)
GRAB BAR
(E)
T
O
N
1'-7"
MIN.
4'-0"
4'-0"
7"-9"
3'-4"
3'-4"
N
3'-0"
3'-0"
GRAB BAR
(E)
G
3'-4"
6'-2"
3'-0"
MIN
CL
2'-0" 12"
MIN MIN
6'-0"
PLAN VIEW
1'-4" MIN
1'-6" MAX
MIRROR
(E)
MIRROR
(N)
TOILET TISSUE
DISPENSER
(N)
UTILITY
HOOK
(N)
HOOK
STRIP
(N)
D
E
S
U
MOP
HOLDER
(N)
14
COORDINATE CORE DRILLING WITH MALL OPERATIONS MANAGER PRIOR TO
BEGINNING WORK.
PREPARE THE FLOOR SLAB AND PROCURE MATERIALS REQUIRED AT THE ENTRANCE
TO PRODUCE A FLUSH CONDITION BETWEEN THE TENANT STORE CLOSURE LINE
AND THE EXISTING MALL FLOORING.
INSTALL ALL FINISH FLOORING (I.E.: CARPET, WOOD, TILE) AND ALL FINISH WALL
MATERIALS BEHIND AND UNDER ALL MILLWORK.
ADEQUATE ACCESS PANELS OR DOORS SHALL BE INCORPORATED INTO TENANT
WORK FOR INSPECTION SERVICE AND REPLACEMENT OF BOTH LANDLORD AND
TENANT EQUIPMENT, COORDINATE PLACEMENT WITH LANDLORD'S ON-SITE
REPRESENTATIVE.
PROVIDE 3/4" FIRE RETARDANT PLYWOOD BEHIND ALL ELECTRICAL AND TELEPHONE
PANELS, PAINT TO MATCH WALL COLOR FINISH PRIOR TO HARDWARE
INSTALLATION.
PROVIDE EXPANSION BETWEEN ALL NEW WALLS AND THE EXISTING ROOF
STRUCTURE ABOVE.
PATCH/REPAIR ALL SURFACES (WALLS, FLOOR, CEILING, ETC.) AFFECTED BY
DEMOLITION WORK.
TRANSITIONS BETWEEN DISSIMILAR FLOOR MATERIALS TO BE SMOOTH AND
FLUSH. REFER TO SHEET A-502 FOR FOR APPLICABLE FLOOR TRANSITION
DETAILS.
ALL FINISH MATERIALS SHALL BE INSTALLED PER MANUFACTURER'S STANDARD
WRITTEN DETAILS AND SPECIFICATIONS. REFER TO SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
PROVIDE A LEVEL 4 GYP. BD. FINISH ON ALL NEW AND EXISTING WALLS.
SEAL CONTROL JOINTS IN CONCRETE FLOORS.
A Subsidiary of the Luxottica Group
4000 Luxottica Place
Mason, Ohio 45040
CONSULTANT PROJECT # 150343
Shremshock Architects, Inc.
7400 W. Campus Rd. Suite 150 New Albany, OH 43054
t: 614 545 4550 | f: 614 545 4555 | shremshock.com
Gerald S. Shremshock, Architect
Timothy J. Shremshock, Architect
SEAL
KEY NOTES
1. LEASE LINE.
2. NOT USED.
3. EXISTING TENANT SEPARATION WALL TO REMAIN. G.C. SHALL PATCH/ REPAIR GYP BD.
AS REQUIRED. MAINTAIN REQUIRED RATING.
PAPER TOWEL
DISPENSER
(N)
4. CONCRETE MUST BE LEVEL AND CLEAN OF ANY FOREIGN MATERIALS PRIOR TO
INSTALLING NEW FINISHED FLOORING. G.C. TO PERFORM MOISTURE BARRIER TEST
BEFORE INSTALLING ANY FLOORING - REFER TO SPECIFICATIONS FOR MOISTURE
TEST PROCEDURES
5. LINE OF SOFFIT ABOVE.
6. ELECTRICAL DISTRIBUTION EQUIPMENT. REFER TO ELECTRICAL DRAWINGS.
G4
SCALE:
4.
8.
J8
1'-0"
2.
7.
J4
3'-6"
1.
3.
COLOR: BLACK
13
GENERAL NOTES
6.
PAPER TOWEL DISPENSER
H
12
5.
10
SCALE:
9
4'-0"
1
7. NOT USED.
TOILET ACCESSORY MOUNTING HEIGHTS
8. NOT USED.
9. NOT USED.
10. TECH RACK & SECURITY SHELVES FOR EQUIPMENT/MUZAK. REFER TO D1/A-502 SIM.
11. 3'-6" CLEAR FLOOR SPACE IN FRONT OF ELECTRICAL PANELS
13. NOT USED.
14. PHONE BOARD. SEE D1/A-502
-
15. NOT USED.
20'-8"
16. SHORT WALL 9'-0" A.F.F. G.C. TO SEAL WALL CAVITY ABOVE WITH PLYWOOD AS
NECESSARY
4"
AT
20'-4"
ADJACENT
TENANT (N.I.C.)
E
1
9"
3
LA PLAZA MALL
12. NOT USED.
F
PLOTTED: 7/16/2015 - 4:03 PM
USER: JGRAY
B
D
-
1
SALES
3
ADJACENT
TENANT (N.I.C.)
100
E1
4
A-401
22'-1"
16'-312"
HOLD
5
912"
HOLD
A
FE
6
1
LEASE LINE
OVERHEAD LINEWORK
WALL CONSTRUCTION
WALL INFILL CONSTRUCTION TO MATCH EXISTING
EXISTING WALL CONSTRUCTION
SAFE
11
10"
B
A
14
CLOSET
3
-
1
A1
101
4'-014"±
14'-318"
V.I.F.
HOLD
SUNGLASS HUT
LA PLAZA MALL
GRAPHICAL KEY
2'-014"
V.I.F.
10
4'-43 4"±
15'-0"
1'-6"
MALL COMMON
AREA (N.I.C.)
HOLD
B
SIM.
C
5'-107 8"
16
B1
P:\SGH\150343 SGH-La Plaza Mall Mcallen, TX\A-102_06078.dwg
LAYOUT: A-102
5'-6"
(E)
A1
-
2200 S. 10TH STREET
McALLEN, TX 78503
SPACE #Q14-C
2.0 TYPE: PREMIUM
SGH STORE #: 6078
DOOR WITH TYPE AND SIZE - SEE G-002 & D4/A-502
DRAWN BY: ALW
(E)
A1
ADJACENT
TENANT (N.I.C.)
EXISTING DOOR WITH TYPE AND SIZE - SEE G-002
REVIEWED BY: MLH/JMA
AUTHORIZED FOR:
X
A
NORTH
FE
PARTITION TYPE - SEE A8/A-503
FIRE EXTINGUISHER. FOR EXACT LOCATIONS AND REQUIREMENTS
CONSULT WITH LOCAL FIRE DEPARTMENT INSPECTOR
A1
SCALE:
A-102
FLOOR PLAN
1
FLOOR PLAN
2
3
4
5
6
7
8
9
10
11
12
13
14
1
2
3
P-3
FLOOR
GR-01
K
T-02
CERAMIC TILE
ATLAS CONCORDE
ATLAS CONCORDE EVOLVE
COLOR: EVOLVE IRON
FINISH: MATTE
SIZE: 60x60 - 23 5/8”x23 5/8”
GROUT SPACING: 1/8"
P-6
7
8
9
10
11
ACRYLIC PAINT
BENJAMIN MOORE
REGAL SELECT
COLOR: 2126-30 ANCHOR GRAY
SHEEN: FLAT
C-01
12
1.
PROVIDE AND INSTALL FIRE EXTINGUISHERS AS DIRECTED BY THE FIRE MARSHAL.
(SUGGESTED LOCATIONS ON PLAN. IF EXISTING AND NOT CURRENT, CONTACT P.M.
2.
EXAMINE ALL SURFACES TO BE PAINTED UNDER THIS CONTRACT AND SEE THAT THE
WORK OF OTHER TRADES HAVE BEEN LEFT OR INSTALLED IN A SATISFACTORY
CONDITION TO RECEIVE PAINT OR SPECIFIED FINISH.
3. MAINTAIN ALL FINISHES IN THE STORE, WALLS, FLOOR AND CEILING PRIOR TO
TURNOVER. TOUCH-UP ALL CORNER BEADS, WALLS, CEILING AND FLOORING AS
REQUIRED PRIOR TO TURNOVER AND ANY DAMAGE CAUSED BY OTHER TRADES
INCLUDING MILLWORKER.
4.
SEE SHEET A-201 FOR SALES ELEVATIONS AND FINISH DESIGNATIONS.
5.
G.C. TO CLEAN EXISTING FLOORING TO 'LIKE NEW' CONDITION.
VINYL BASE
JOHNSONITE
4" H. x 1/8" THICK
COLOR: 38-PEWTER
CONSULTANT PROJECT # 150343
Shremshock Architects, Inc.
KEY NOTES
1.
NOT USED
2.
BACK OF HOUSE TECH RACK & SECURITY SHELVES FOR EQUIPMENT/MUZAK. REFER
TO A-502
3.
TYPICAL CLOSET FINISHES: FLOOR: VT-01, BASE: VB-01, WALLS: P-2, NON-SALES
DOORS: P-3, CEILING: OPEN-PAINT P-6.
WALL
ACRYLIC PAINT
BENJAMIN MOORE
REGAL SELECT
COLOR: 2132-10 BLACK
SHEEN: EGGSHELL
P-2
A Subsidiary of the Luxottica Group
4000 Luxottica Place
Mason, Ohio 45040
7400 W. Campus Rd. Suite 150 New Albany, OH 43054
t: 614 545 4550 | f: 614 545 4555 | shremshock.com
Gerald S. Shremshock, Architect
Timothy J. Shremshock, Architect
24" X 24" SUSPENDED CEILING
US GYPSUM
MARS CLIMAPLUS SQUARE EDGE
COLOR: WHITE 050
ACT GRID: 15/16" GRID - DX/DXL (SALES) - WHITE
DECOMETAL LAMINATE APPLIED TO WOOD BASE.
FORMICA
FINISH: BRUSHED ALUMINIUM
H
14
(E) GYPSUM BOARD
C-02
P-1
13
GENERAL NOTES
CEILING
BASE
VB-01
6
STOREFRONT
VINYL TILE
ARMSTRONG COMMERCIAL FLOORING
STANDARD EXCELON IMPERIAL TEXTURE
COLOR: 51861 SOFT WARM GRAY
SIZE: 12" x 12" x 1/8"
HPL-06
5
ACRYLIC PAINT
BENJAMIN MOORE
REGAL SELECT
COLOR: 2132-10 BLACK
SHEEN: SEMI-GLOSS
GROUT FOR CERAMIC TILE
LATTICRETE
COLOR:45 RAVEN
VT-01
J
4
SEAL
4. NOT USED
ACRYLIC PAINT
BENJAMIN MOORE
REGAL SELECT
COLOR: PM-1 SUPER WHITE
SHEEN: EGGSHELL
5.
H.C. ACCESSIBLE CASHWRAP.
6.
NOT USED
7.
(54) PRODUCT STORAGE TRAYS. FURNISHED BY OWNER, INSTALLED BY G.C.
8. NOT USED
9. NEW UTILITY HOOK. REFER TO J4/A-102 FOR ADDITIONAL INFORMATION
10. NOT USED
11. NOT USED
G
12. NOT USED
13. NOT USED
14. START TILE (FULL TILE) CENTERED ON ENTRY AS SHOWN
G1
SCALE:
15. NOT USED
FINISH MATERIAL SCHEDULE
16. NOT USED
17. FIXTURE SHOWN IS IN THE LOCATION FOR STORE HOURS OF OPERATION AND
INSIDE TENANT LEASE LINE. TENANT TO MOVE FIXTURE INSIDE LINE OF ROLLING
GRILLE WHEN STORE IS CLOSED.
-
20'-8"
4"
AT
20'-4"
ADJACENT
TENANT (N.I.C.)
9"
E
STOR. PNL.
USER: JGRAY
PLOTTED: 7/16/2015 - 4:03 PM
C
01
TVSAFE
J9
3
5'-6"
EQ.
CL
H1 A-201 E1
MALL COMMON
AREA (N.I.C.)
H6
5
22'-1"
E6
T 02
GR 01
SUNGLASS HUT
LA PLAZA MALL
3'-6"
2
G9
14
7'-0"
9
02
T-
CT-1
15'-0"
3'-6"
2'-014"
EQ.
GO GO
CW 3.1R ACCESSORY
ADJACENT
TENANT (N.I.C.)
FS 1.0
100
SP 10.5L
3'-0"
SP 10.4(18)
SP 10.5R
4'-0"
3'-0"
SALES
D
-
7
SP 10.1C
10
.6
SP 14.0-3
SP 11.4(18)
SP 11.4(6) SP 11.5R
SP 11.5L
SP 11.1C SP 11.0C
SP 11.0C
17
7
B
10"
P:\SGH\150343 SGH-La Plaza Mall Mcallen, TX\A-103_06078.dwg
LAYOUT: A-103
SP
CAPACITY CALCULATIONS
101
ADJACENT
TENANT (N.I.C.)
A
NORTH
A1
FINISH/FIXTURE PLAN
1
2
3
4
5
2200 S. 10TH STREET
McALLEN, TX 78503
SPACE #Q14-C
2.0 TYPE: PREMIUM
-
CLOSET
SCALE:
6
LA PLAZA MALL
F
7
8
9
10
11
FIXTURE ID
THEME
CT-HC
CT-1
CT-2
FS 1.0
GO 1.0
SP 10.0C
SP 10.1C
SP 11.0C
SP 11.1C
STORY PANEL
12
SGH STORE #: 6078
FIXTURE QUANTITY
1
0
1
0
1
0
5
1
2
1
1
FIXTURE CAPACITY
0
0
0
0
52
144
108
54
108
54
-26
TOTAL
13
TOTAL FACINGS
0
0
0
0
52
0
540
54
216
54
-26
890
14
DRAWN BY: ALW
REVIEWED BY: MLH/JMA
AUTHORIZED FOR:
FINISH / FIXTURE PLAN
A-103
1
2
3
4
5
6
7
8
9
10
11
12
13
14
GENERAL NOTES
1.
2.
K
3.
4.
5.
6.
7.
J
8.
9.
REFER TO LIGHTING SPECIFICATIONS SCHEDULE FOR ADDITIONAL INFORMATION.
GRID LAYOUT FOR ACOUSTICAL CEILING TILE TO BE CENTRALLY LOCATED WITHIN
RETAIL SPACE AS INDICATED AT PLAN LAYOUT UNLESS SPECIFICALLY NOTED
OTHERWISE. REFER TO PLAN LAYOUT FOR EQUAL/EQUAL DIMENSIONS TO BE
MAINTAINED.
IT SHALL BE THE E.C.'S RESPONSIBILITY TO UNLOAD INVENTORY AND STORE
LIGHTING PACKAGE. THE E.C. SHALL ALSO SHIP ANY EXCESS MATERIALS BACK TO
THE ELECTRICAL PACKAGE DISTRIBUTOR.
E.C. SHALL RELAMP ALL FIXTURES PRIOR TO STORE OPENING BUT NOT DURING
HEAVY CONSTRUCTION PERIOD.
THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR AIMING TRACK HEADS PER SGH
STANDARDS. ELECTRICAL CONTRACTOR TO CONTACT LUXOTTICA PM FOR
FOCUSING DIRECTIVE IF NEEDED.
G.C. IS RESPONSIBLE TO PATCH/REPAIR ALL GYP.BD. CEILING SURFACES AFFECTED
BY DEMOLITION/NEW CONSTRUCTION.
EXISTING GYP.BD. CEILING SURFACES TO RECEIVE A FRESH COAT OF PAINT UPON
COMPLETION OF SCOPE OF CEILING WORK. LIGHTING INSTALLER IS RESPONSIBLE
TO TOUCH UP ANY AREAS DAMAGED BY THEIR WORK.
CENTER CEILING GRID & CEILING DEVICES U.N.O.
SPRINKLER HEADS SHOWN FOR REFERENCE ONLY. FIRE PROTECTION CONTRACTOR
TO DETERMINE ACTUAL AMOUNT AND LOCATION OF HEADS. SPRINKLER HEADS
SHOULD BE LOCATED SYMMETRICALLY IN THE CEILING AND SURFACE MOUNTED
WHEN APPLICABLE.
A Subsidiary of the Luxottica Group
4000 Luxottica Place
Mason, Ohio 45040
CONSULTANT PROJECT # 150343
Shremshock Architects, Inc.
7400 W. Campus Rd. Suite 150 New Albany, OH 43054
t: 614 545 4550 | f: 614 545 4555 | shremshock.com
Gerald S. Shremshock, Architect
Timothy J. Shremshock, Architect
SEAL
KEY NOTES
H
1.
LOCATION OF TRAFFIC COUNTER (SHOPPER TRAK). REFER TO E-102.
2.
PREFERRED SPEAKER LOCATION. SPEAKER TO MATCH CEILING COLOR.
3. LOCATION OF WIRELESS ACCESS POINT. REFER TO E-102.
4. LIGHT TRACK TO BE MOUNTED ON FACE OF EXISTING SOFFIT.
5.
END OF LIGHT TRACK TO ALIGN WITH EXISTING SOFFIT.
6.
SECURITY CAMERAS. REFER TO E-102
7. NOT USED
8.
START TILE SHOWN HATCHED
EXISTING SOFFIT TO BE REWORKED. VERTICAL FACE OF
G
NEW CONSTRUCTION TO ALIGN WITH ADJACENT EXISTING GYP. BD. SOFFIT.
10. EXISTING OVERHEAD ROLLING GRILLE DOOR.
-
20'-8"
4"
AT
20'-4"
ADJACENT
TENANT (N.I.C.)
E
D7
9"
A-502
PLOTTED: 7/16/2015 - 4:03 PM
USER: JGRAY
1
A3W A3W
A3W A3W A3W A3W
TW6'-0"
3
2
C4W
TW10'-0"
5'-6"
FIXTURE EXTENTS BELOW
OF
STOREFRONT OPENING
MALL COMMON
AREA (N.I.C.)
2
TW
TB
9
A3W
10"
A3B
-
ADJACENT
TENANT (N.I.C.)
101
2x2 LED RECESSED MOUNT
RETURN AIR GRILLE
B2
2x4 LED RECESSED MOUNT
B3
RECEPTACLE DUPLEX
OPEN
TO DECK
VARIES (P-6)
CLOSET
B1
EXHAUST FAN
5
B
RETURN AIR GRILLE
SUPPLY DIFFUSER
A3W A3W A3W A3W A3W A3W
S
S
C
4
1'-10"
C4W
TC
618"
C4W
S
A3W
6
AP
1
11"
TW4'-0"
S
C
SYMBOLS LEGEND / GRAPHICAL KEY
X1A
A3W A3W
100
8
A3W
22'-1"
SALES
TW12'-0"
10
C4W
15'-0"
C4W
C4W
(E) SOFFIT (P-2)
9'-11" AFF
5
-
A3W A3W A3W
S
C
A3W A3W A3W
ACT - C-02
11'-0" AFF
6
"
'-6
9
4'-0"
A3W A3WA3WA3W A3W
TW12'-0"
A3W A3W
A3W A3W
C
A3W
4'-0"
S
A3W A3W A3W A3W A3WA3W A3W A3W
A3W
ADJACENT
TENANT (N.I.C.)
B3
P:\SGH\150343 SGH-La Plaza Mall Mcallen, TX\A-104_06078.dwg
LAYOUT: A-104
S
C
D
-
2
4'-0"
6
X1
RECESSED ADJUSTABLE
DOWN LIGHT (BLACK)
EXIT LIGHT (WHITE)
X1B EXIT LIGHT (BLACK)
ADJUSTABLE TRACK HEAD
(WHITE)
ADJUSTABLE TRACK HEAD
(BLACK)
C1B
C4W
A
LIGHT TRACK w/ LENGTH
(BLACK)
RECESSED ADJUSTABLE
DOWN LIGHT
4'-1 LED STRIP SUSPENDED
AT 13'-0" A.F.F.
CONCEALED SPRINKLER HEAD
UPRIGHT SPRINKLER HEAD
X1AW EXIT LIGHT - CEILING MOUNTED
X1AB EXIT LIGHT - CEILING MOUNTED
LIGHT TRACK w/ LENGTH
C1W
C4B
X2
X3
X4
EXIT SIGN
EXIT & EMERGENCY LIGHT
COMBINATION
EMERGENCY LIGHT
REMOTE POWER SUPPLY
RECESSED ADJUSTABLE
DOWN LIGHT (WHITE)
RECESSED ADJUSTABLE
DOWN LIGHT (BLACK)
NORTH
A1
SCALE:
AP
WIRELESS ACCESS POINT
TC
TRAFFIC COUNTER
(E)
EXISTING
(R)
RELOCATION
S
C
SECURITY CAMERA
S
SPEAKER
2
SUNGLASS HUT
LA PLAZA MALL
2200 S. 10TH STREET
McALLEN, TX 78503
SPACE #Q14-C
2.0 TYPE: PREMIUM
SGH STORE #: 6078
DRAWN BY: ALW
REVIEWED BY: MLH/JMA
AUTHORIZED FOR:
REFLECTED
CEILING PLAN
A-104
REFLECTED CEILING PLAN
1
LA PLAZA MALL
F
3
4
5
6
7
8
9
10
11
12
13
14
1
2
3
4
5
6
7
8
9
10
11
12
13
14
GENERAL NOTES
ON BOTH SIDES
OF DOOR & FRAME
P 3
K
TURN IN
WALL
B.O. CEILING
11'-0" AFF
P
1
P
1
P
P
2
2
P
1
1.
REFER TO OWNER'S SIGNAGE STANDARD FOR ADDITIONAL SIGN INFORMATION.
SIGNAGE WORK TO BE SUBMITTED UNDER SEPARATE PERMIT.
2.
SEE SHEET A-103 FOR FINISH MATERIAL SCHEDULE
B.O. CEILING
11'-0" AFF
A Subsidiary of the Luxottica Group
4000 Luxottica Place
Mason, Ohio 45040
CONSULTANT PROJECT # 150343
B.O. SOFFIT
9'-11" AFF
T.O. LOW WALL
9'-0" AFF
Shremshock Architects, Inc.
7400 W. Campus Rd. Suite 150 New Albany, OH 43054
t: 614 545 4550 | f: 614 545 4555 | shremshock.com
Gerald S. Shremshock, Architect
Timothy J. Shremshock, Architect
J
HPL 06
FINISH FLOOR
0'-0" AFF
SP 14.0-3
HPL 06
H
ON BOTH SIDES
OF DOOR & FRAME
P 3
SP 10.0C
SP 10.5L
SP 10.0C
FINISH FLOOR
0'-0" AFF
SP 10.6
HPL 06
SP 11.5L
11.0C
SP 11.4(18)
SP 11.1C
11.0C
HPL 06
SP 11.5R
SP 11.4(6)
H6
H1
ELEVATION
SCALE:
G
P
ELEVATION
2
P
B.O. CEILING
11'-0" AFF
P
1
2
B.O. CEILING
11'-0" AFF
B.O. SOFFIT
9'-11" AFF
B.O. SOFFIT
9'-11" AFF
OPEN
TO MALL
F
STOR. PNL.
FINISH FLOOR
0'-0" AFF
FINISH FLOOR
0'-0" AFF
SP 10.6
SP 10.0C
SP 10.0C SP 10.1C SP 10.0C
AT
HPL 06
SP 10.8R
SP 10.4(18)
HPL 06
E
E6
E1
USER: JGRAY
PLOTTED: 7/16/2015 - 4:03 PM
P:\SGH\150343 SGH-La Plaza Mall Mcallen, TX\A-201_06078.dwg
LAYOUT: A-201
SCALE:
ELEVATION
SCALE:
LA PLAZA MALL
SCALE:
SEAL
ELEVATION
D
C
SIGNAGE MATRIX
B
TYPE
ID
QTY.
REMARKS
BARRICADE
LIFESTYLE GRAPHIC
1
BY BARRICADE
VENDOR
STOREFRONT
-
-
BY SIGN VENDOR
BLADE SIGN
SGH.BL-1
SGH.BL-2
-
BY SIGN VENDOR
CRASH GRAPHICS
SGH-CGL
-
BY SIGN VENDOR
SUNGLASS HUT
LA PLAZA MALL
2200 S. 10TH STREET
McALLEN, TX 78503
SPACE #Q14-C
2.0 TYPE: PREMIUM
SGH STORE #: 6078
DRAWN BY: ALW
REVIEWED BY: MLH/JMA
A
A6
A1
SCALE:
ELEVATION
1
SCALE:
2
3
4
5
ELEVATION
6
7
8
9
10
11
BACKWRAP
SGH.BW
-
BY MILLWORKER
IDENTIFICATION SIGN
SGH.ID
-
BY MILLWORKER
VINYL DOT PATTERN
-
-
BY SIGN VENDOR
12
13
14
AUTHORIZED FOR:
ELEVATIONS
A-201
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A Subsidiary of the Luxottica Group
4000 Luxottica Place
Mason, Ohio 45040
K
B.O. MALL CEILING
14'-3" A.F.F.
CONSULTANT PROJECT # 150343
B.O. BULKHEAD
13'-3" A.F.F.
(E) STOREFRONT
SIGN TO REMAIN
Shremshock Architects, Inc.
(E) STOREFRONT
CONSTRUCTION AND
FINISHES TO REMAIN.
G.C. TO PATCH &
REPAIR TO 'LIKE NEW'
CONDITION
J
7400 W. Campus Rd. Suite 150 New Albany, OH 43054
t: 614 545 4550 | f: 614 545 4555 | shremshock.com
Gerald S. Shremshock, Architect
Timothy J. Shremshock, Architect
T.O. STOREFRONT ENTRY
9'-11" A.F.F.
H
(E) STOREFRONT
CONSTRUCTION AND
FINISHES TO REMAIN.
G.C. TO PATCH &
REPAIR TO 'LIKE NEW'
CONDITION
G.C. TO PATCH & REPAIR
(E) STOREFRONT
CONSTRUCTION TO 'LIKE
NEW' CONDITION. PAINT
P-2 TO MATCH EXISTING
STOREFRONT COLOR
(E) FIRE
STROBE TO
REMAIN
(E) TENANT
STOREFRONT
OPENING W/ ROLLING
GRILLE TO REMAIN
G.C. TO PATCH & REPAIR
(E) STOREFRONT
CONSTRUCTION TO 'LIKE
NEW' CONDITION. PAINT
P-2 TO MATCH EXISTING
STOREFRONT COLOR
G
SEAL
LEASE LINE
LEASE LINE
(E) NEUTRAL PIER
TO REMAIN
(E) NEUTRAL PIER
TO REMAIN
F
(E) STOREFRONT
BASE TO REMAIN
(E) STOREFRONT
BASE TO REMAIN
G.C. TO HAVE DOOR VENDOR SERVICE
AND CLEAN ROLLING GRILLE.
18'-3 3/8"
1'-10 1/8"
AT
1'-11 5/8"
22'-1"
E
E1
USER: JGRAY
PLOTTED: 7/16/2015 - 4:03 PM
P:\SGH\150343 SGH-La Plaza Mall Mcallen, TX\A-401_06078.dwg
LAYOUT: A-401 (ALT)
SCALE:
LA PLAZA MALL
FIN. FLOOR
0'-0"
STOREFRONT ELEVATION
D
C
SUNGLASS HUT
LA PLAZA MALL
2200 S. 10TH STREET
McALLEN, TX 78503
SPACE #Q14-C
2.0 TYPE: PREMIUM
B
SGH STORE #: 6078
DRAWN BY: ALW
REVIEWED BY: MLH/JMA
AUTHORIZED FOR:
STOREFRONT
ELEVATION
A
A1
SCALE:
A-401
NOT USED
1
2
3
4
5
6
7
8
9
10
11
12
13
14
5
J-CHANNEL
G.C. TO MECHANICALLY
FASTEN (EVERY 12"-18")
THE TOP, BOTTOM, AND
ONE SIDE J-CHANNEL,
SLIDE MIRROR IN (WITH
MIRROR MASTIC) AND
ATTACH THE OTHER SIDE
J-CHANNEL. GC TO USE
ANCHORS AS REQUIRED
TO SECURELY FASTEN.
9
10
11
BOBRICK B-1651836
MIRROR WITH
STAINLESS STEEL
CHANNEL FRAME
PROVIDE IN-WALL
BLOCKING AS REQUIRED
DOOR
FLASH PATCH
BY G.C.
18"
MIRROR BY G.C.
J
J4
J9
DOOR MIRROR DETAIL
36"
FLOOR TRANSITION
VCT TO PORCELAIN TILE
37 8"
NOT USED
SCALE:
RESTROOM MIRROR DETAIL
LINE OF EXISTING
CONCRETE SLAB
PHONE BOARD/SECURITY ELEVATION
D
E
S
U
RESTROOM
RESTROOM
BRAILLE SIGN PER
1991 ADA REQ'TS
17-19"
4'-8"
9"
27" MIN
29" MIN
33"-36"
40" MAX
ANSI APPROVED
E.S. PLASTIC
NEMA RATED
SELF
EXTINGUISHING
ADHESIVE
MOUNTED
O
N
T
O
N
REFER TO CEILING PLAN
FOR ALL CEILING HEIGHTS.
FASTENING TO STRUCTURE ABOVE
TO COMPLY WITH LANDLORD AND
OR LOCAL BUILDING DEPARTMENT
REQUIREMENTS.
SCALE:
SUSPENDED GYP. BD. CEILING DETAIL
FRAMING AS
REQUIRED. REFER
TO SPECIFIC DETAILS
AND STRUCTURAL
DRAWINGS.
D
E
S
U
T
CONCEALED
CONTINUOUS HINGE
N
T
O
D
E
S
U
REFER TO CEILING PLAN
VARIES
5/8" GYP. BD.
2'-1114"
1'-05 8"
SCREWDRIVER
OPERATED LATCH.
VARIES
REFER TO CLG PLAN
1'-65 8"
1'-1114"
FRONT
3
SIDE
3
4"
SHELF SPACING AND BIN ARRANGEMENTS
A7
TYPICAL LAVATORY/SHELVING ELEVATION
3
DISABLED ACCESS SIGNAGE
4
5
SCALE:
6
A11
PIPP SHELVING
7
SUNGLASS HUT
LA PLAZA MALL
SGH STORE #: 6078
1'-6"
SCALE:
ATTACH WITH #8
SHEET METAL SCREWS.
2200 S. 10TH STREET
McALLEN, TX 78503
SPACE #Q14-C
2.0 TYPE: PREMIUM
3'-1114"
LAVATORY, REFER TO
PLUMBING DRAWINGS
2
G.C. IS TO PROVIDE A
ONE-HOUR FIRE RATED CEILING
SYSTEM (WHEN-REQUIRED).
BRACKET
D
E
S
U
A4
1
5/8" GYP.
BD. 'TYPE X'
METAL TRIM
A1
SCALE:
N
T
O
INSTALLATION ON VERTICAL WALL TO BE
SIMILAR. ALL FASTENER REQUIREMENTS
AND SPECIFICATIONS ARE THE SAME.
12" 12" 12" 12" 12" 12" 12"
O.C. O.C. O.C. O.C. O.C. O.C. O.C.
8'-0"
2'-0"
0.C.
INSULATE HOT WATER AND
DRAIN PIPING
1 1/2" CHANNEL
4'-0" O.C. MAX.
20 GA. METAL STUD
WITH 1 5/8" FLANGE
AND 1/2" LIPS. (MIN.)
STANDARD STORES
(LOW SEISMIC)
IBC SEISMIC DESIGN CATEGORIES A,B&C
ACOUSTICAL CEILING TILE
NOTE: ALL SIGNAGE SHALL CONFORM WITH ADA ACCESSIBILITY
GUIDELINES, INCLUDING BUT NOT LIMITED TO PROPORTION, COLOR
CONTRAST AND RELIEF AND GRADE 2 BRAILLE REQUIREMENTS.
BLUE
A
SCALE:
D
E
S
U
ALIGN
3'-0"
O
N
T
LINE OF EXISTING
CONCRETE SLAB
1/2" SHELF
VARIES
REFER TO PLAN
CL
PROVIDE LATEX LEVELING
COMPOUND AS REQUIRED TO
CREATE FLUSH CONDITION AT
THRESHOLD.
D11
7'-1118"
C
MIRROR, REFER TO
G6/A-502
1 1/2"
MAX
VARIES
SCALE:
METAL FURRING
CHANNEL CLIP
INTERMEDIATE DUTY SUSPENDED
GRID SYSTEM CROSS "T" MEMBER
@ 2'-0" OR 4'-0" O.C. (REFER TO
SPECIFIC CEILING TYPE).
D7
3'-0" WIDE X 2" DEEP X 3/4" THICK
WHITE MELAMINE SHELVING, FINISHED
ON ALL SURFACES WITH WHITE
DOUBLE SLOTTED BRACKETS &
STANDARDS. FASTEN SHELVES TO
BRACKETS
REFER TO G4/A-102 FOR
TOILET ACCESSORY
MOUNTING HEIGHTS,TYP.
VINYL TILE
24" O.C. MAX.
SPACING
WALL OR SOFFIT FRAMING AND
FINISHES. REFER TO SPECIFIC DETAILS.
HOLLOW METAL
JAMB / HEAD DETAIL
HANGER SPACING
4'-0" O.C. MAX.
INTERMEDIATE DUTY
SUSPENDED GRID SYSTEM
MAIN RUNNER @ 2'-0" O.C.
WALL MOLDING. SIZE TO MATCH
SIZE OF MAIN RUNNERS
HOLLOW METAL FRAME
D4
SCALE:
ALUMINUM THRESHOLD
FLOOR TRANSITION
CONCRETE TO VINYL
MINIMUM OF 3
TIGHT TURNS
AT ALL WIRES.
MINIMUM OF 3 TIGHT
TURNS AT ALL WIRES.
ACOUSTICAL
CEILING TILES
24" W. X 48" H.
PHONE BOARD
2'-0"
1'-6"
3"
10"
3'-0"
SAFE
SCALE:
REFER TO CEILING PLAN
VARIES
QUAD
OUTLET
TECH
RACK
G12
12 GA VERTICAL SUPPORT
WIRE @ 4'-0" O.C. EA. WAY.
AND MAX. 8" FROM ALL EDGES.
DSL
D1
34" MIN
LAYOUT: A-502
D
T
O
NOTE: PREPARE EXISTING CONCRETE
SLAB AS REQUIRED TO PROVIDE LEVEL
TRANSITION TO MALL FLOORING
12 GA VERTICAL
SUPPORT WIRE @
4'-0" O.C. EA. WAY.
AND MAX. 8" FROM
ALL EDGES.
8" MAX.
AT PERIMETER
CLEAR SPACE FOR
ELECTRICAL PANEL
12 PORT PATCH
PANEL
QUAD
OUTLET
BEHIND
TECH RACK
D
E
US
SEAL
LA PLAZA MALL
SEE WALL TYPE
FOR FRAMING
A66 PHONE BLOCK
P:\SGH\150343 SGH-La Plaza Mall Mcallen, TX\A-502_06078.dwg
FLOOR TRANSITION
TILE TO TILE
N
FLOOR TRANSITION
TILE TO MALL
CONFORM TO BASIC
MINIMUM REQUIREMENTS
ESTABLISHED IN ASTM
C636
5/8" GYPSUM BOARD
MONITOR
Shremshock Architects, Inc.
7400 W. Campus Rd. Suite 150 New Albany, OH 43054
t: 614 545 4550 | f: 614 545 4555 | shremshock.com
Gerald S. Shremshock, Architect
Timothy J. Shremshock, Architect
DOOR
(E) MALL FLOORING.
FIELD VERIFY TYPE.
FASTENING TO STRUCTURE
ABOVE TO COMPLY WITH
LANDLORD AND OR LOCAL
BUILDING DEPARTMENT
REQUIREMENTS.
40" MIN
60" MAX
E
THIN SET MORTAR BED
B.O. (E) ROOF DECK / STRUCTURE
OR (E) FLOOR DECK / STRUCTURE
24" W. x 18" D.
SHELVING RATED TO
100 LBS (TYP.) ON 24"
WHITE DOUBLE SLOTTED
STANDARDS.SCREW
SHELVES TO BRACKETS
MONITOR,
KEYBOARD AND
MOUSE ON SHELF
SCALE:
CONSULTANT PROJECT # 150343
AT
NOT USED
SCALE:
G9
F
PLOTTED: 7/16/2015 - 4:03 PM
SCALE:
A Subsidiary of the Luxottica Group
4000 Luxottica Place
Mason, Ohio 45040
TILE FLOORING PER
PLANS & SCHEDULE
1/8" THICK ZINC
TRANSITION STRIP
FURNISHED AND
INSTALLED BY TILE
CONTRACTOR.
G.C. TO ADJUST SETTING
BED AS REQUIRED TO
ACHIEVE FLUSH TRANSITION
G6
ELEVATION SHOWN IS FOR REFERENCE
ONLY. REFER TO PLAN SHEETS FOR ACTUAL
LOCATION OF SAFE, TECH RACK AND
PHONE BOARD.
USER: JGRAY
J12
NOTE: PREPARE EXISTING CONCRETE
SLAB AS REQUIRED TO PROVIDE LEVEL
TRANSITION TO MALL FLOORING
G4
T
O
NOTE: PREPARE EXISTING CONCRETE
SLAB AS REQUIRED TO PROVIDE LEVEL
TRANSITION TO MALL FLOORING
TILE FLOORING PER
PLANS & SCHEDULE
G
D
E
US
1/8" THICK ZINC
TRANSITION STRIP
FURNISHED AND
INSTALLED BY TILE
CONTRACTOR.
THIN SET MORTAR BED
412"
SCALE:
14
LINE OF EXISTING
CONCRETE SLAB
NOTE: PREPARE EXISTING CONCRETE
SLAB AS REQUIRED TO PROVIDE LEVEL
TRANSITION TO MALL FLOORING
LOCKING DEVICES
AUTOMATICALLY SECURE
MIRROR TO CONCEALED WALL
HANGER WHEN IT IS LOWERED
INTO FINAL POSITION, TYP.
G1
13
N
TILE FLOORING PER
PLANS & SCHEDULE
LINE OF EXISTING
CONCRETE SLAB
SCALE:
H
B
12
1/8" THICK ZINC
TRANSITION STRIP
FURNISHED AND
INSTALLED BY TILE
CONTRACTOR.
VINYL TILE
ATTACH WALL HANGER TO
IN-WALL BLOCKING W/ #8
X 1 1/2" F/H MTL SCREWS
WHERE REQUIRED, TYP.
SCALE:
8
1 "
4
T
7
36" MIN. TAPER
D
E
S
U
K
O
N
6
212"
4
US
ED
3
T
2
NO
1
SCALE:
8
9
10
4"
12
13
REVIEWED BY: MLH/JMA
AUTHORIZED FOR:
ACCESS PANEL WITH
METAL DOOR. FINISH
TO MATCH CEILING.
CEILING MOUNTED ACCESS PANEL
METAL FLUSH MOUNTED
11
DRAWN BY: ALW
GENERAL
DETAILS
A-502
14
1
2
3
4
5
6
7
8
9
10
11
12
13
14
LIGHT GAUGE FRAMING - CROSS
REFERENCE GUIDE
K
25 GA. ------ 18 MIL
22 GA. ------ 27 MIL
20 GA. ------ 33 MIL
18 GA. ------ 43 MIL
3/4
"
A Subsidiary of the Luxottica Group
4000 Luxottica Place
Mason, Ohio 45040
16 GA. ------ 54 MIL
14 GA. ------ 68 MIL
12 GA. ------ 97 MIL
CONSULTANT PROJECT # 150343
SCALE:
DETAIL AT
LATERAL BRACING SUPPORT
NOTE: CONSTRUCT WALL PER UL
ASSEMBLY REQUIREMENTS SHOWN
ON ARCHITECTURAL DRAWINGS.
INSTALL SLIP TRACK AND FIRE-SAFING
MATERIALS PER MANUFACTURER'S
RECOMMENDATIONS TO ACHIEVE
ONE HOUR FIRE RATING
F
18 GA DEEP LEG TRACK WITH 2"
FLANGE. (DEPTH TO MATCH VERTICAL
STUD DEPTH) ATTACH TO STRUCTURE
W/ (2) #12 SCREWS AT 16" O.C.
3/4"
MAX
SE
D
3/4"
MAX
NO
162T125-27
162T125-33
250T125-33
250T200-33
250T125-43
250T200-43
362T125-33
362T200-33
362T125-43
362T200-43
600T125-33
600T200-33
600T125-43
600T200-43
TYPICAL HAT (FURRING) CHANNELS
7/8", 25 GA. FURRING CHANNEL
7/8", 22 GA. FURRING CHANNEL
087F125-18
087F125-27
3 5/8" 20 GA. TRACK (TYP.)
I.C.B.O. # ESR 3016
FINISH FLOOR
0'-0"
A4
1
SCALE:
2
3
16"
28'-6"
16
16"
30'-0"
SEAL
STUD
DESIGNATION
STUD
DEPTH
FLANGE
WIDTH
362S162-33
3-5/8"
1-5/8"
362S162-43
3-5/8"
1-5/8"
362S162-54
3-5/8"
1-5/8"
STUD
DESIGNATION
STUD
DEPTH
FLANGE
WIDTH
362S162-33
3-5/8"
1-5/8"
SIM.
SE
D
6"
STUD
GAUGE
STUD
SPACING
20
16"
15'-0"
18
16"
16'-6"
16
16"
18'-0"
STUD
GAUGE
STUD
SPACING
MAXIMUM HEIGHT TO DIAGONAL BRACE
MAXIMUM HEIGHT TO DIAGONAL BRACE
15'-0"
16"
20
362S162-43
3-5/8"
1-5/8"
18
16"
16'-0"
362S162-54
3-5/8"
1-5/8"
16
16"
17'-0"
NOTES:
1. DESIGN BASED ON ALLOWABLE DEFLECTION OF L/360.
2. DESIGN BASED ON FY = 33 KSI FOR 3 5/8" & 6" STUDS LESS THAN 16 GAUGE.
FY = 50 KSI FOR 3 5/8", 16 GAUGE & 6", 16 GAUGE STUDS.
3. PROVIDE HORIZONTAL BRIDGING @ 4'-0" O.C. MAX PER MANUFACTURER'S RECOMMENDATIONS.
4. DESIGN BASED ON MINIMUM 5 PSF LATERAL LOAD, OR LATERAL SEISMIC LOAD, WHICHEVER CONTROLS.
5. TABLE IS VALID FOR (1) LAYER OF GYPSUM BOARD EACH FACE.
6. FOR STUD DESIGNATIONS REFER TO E8/A-503.
STUD SIZE MATRIX
SEISMIC DESIGN CATERGORIES A AND B
REFER TO DIAGONAL
BRACING ON SHEET A-504
PER PLAN
(1) LAYER 5/8" GYPSUM
BOARD (SEE FINISH
SCHEDULE FOR
APPLIED FINISH)
SCHEDULED CEILING
REFER TO CEILING PLAN
(1) LAYER 5/8" GYPSUM
BOARD (SEE FINISH
SCHEDULE FOR APPLIED
FINISH)
METAL STUDS ANCHORED
TO EXISTING CONSTRUCTION
AS REQUIRED
CONTINUOUS TOP
TRACK
SCHEDULED CEILING
REFER TO CEILING PLAN
(1) LAYER 5/8" GYPSUM
BOARD (SEE FINISH
SCHEDULE FOR APPLIED
FINISH)
G4
G4
G4
A-503
A-503
A-503
4 7/8"
A4
A-503
METAL STUD - REFER TO
METAL STUD SCHEDULE
FOR SIZE AND SPACING.
FOR 1 HOUR RATED WALL
USE MIN. 25 GA. GALV.
STEEL
(1) LAYER 5/8" "TYPE X"
GYP. BOARD
CONT. 3 5/8" METAL
BOTTOM RUNNER ATTACH
TO CONC. FLOOR SLAB
AS REQUIRED
SCHEDULED BASE
EACH SIDE
LINE OF FINISH FLOOR
C
A
COLUMN DETAIL
18
1-5/8"
METAL STUD - REFER TO
METAL STUD SCHEDULE
FOR SIZE AND SPACING
A4
A-503
SIM.
SCHEDULED BASE
LINE OF FINISH FLOOR
3 5/8" METAL
STUDS AT 16" O.C.
MAX.
METAL STUD - REFER
TO METAL STUD
SCHEDULE FOR SIZE
AND SPACING
4 7/8"
(1) LAYER 5/8"
"TYPE X" GYP.
BOARD
A4
A-503
CONT. 3 5/8" METAL
BOTTOM RUNNER
ATTACH TO CONC.
FLOOR SLAB AS
REQUIRED
SCHEDULED BASE
EACH SIDE
LINE OF FINISH FLOOR
3 5/8" METAL STUD CONSTRUCTION WITH 5/8" GYPSUM
BOARD EACH SIDE. EXTEND GYP. BD. IN NON-SALES TO
ROOF DECK ABOVE. GYP. BD. IN SALES AREA TO STOP
6" ABOVE ADJACENT CEILING
B
2 1/2" METAL STUD CONSTRUCTION WITH 5/8"
GYPSUM BOARD ON ROOM SIDE.
A
A1
REFER TO METAL STUD SIZE MATRIX ON
E11/A-503 OR SEISMIC SHEET IF USED.
3 5/8" METAL STUD CONSTRUCTION WITH 5/8" "TYPE X"
GYPSUM BOARD EACH SIDE TO 6" ABOVE ADJACENT CEILING.
3 5/8" METAL STUD CONSTRUCTION WITH 5/8" "TYPE X"
GYPSUM BOARD ON ONE SIDE TO 6" ABOVE ADJACENT
CEILING.
A8
FLOOR ATTACHMENT DETAIL
4
5
SCALE:
6
SUNGLASS HUT
LA PLAZA MALL
2200 S. 10TH STREET
McALLEN, TX 78503
SPACE #Q14-C
2.0 TYPE: PREMIUM
SGH STORE #: 6078
DRAWN BY: ALW
REVIEWED BY: MLH/JMA
.177 DIA. HILTI POWDER
ACTUATED FASTENER w/ 3/4'"
EMBEDMENT AT 24" O.C.
ICBO #ESR 1663
SCALE:
1-5/8"
6"
PLAN VIEW
#8 SCREWS EA. SIDE OF
STUD TO TRACK (TYP.)
A1
6"
600S162-54
EXISTING CONSTRUCTION
NO
TU
PLAN VIEW
METAL STUD FRAMING REFER
TO NOTES AND PLANS FOR
SIZE, GAUGE, AND SPACING
B
600S162-43
SCALE:
3 5/8" METAL STUDS
AT 16" O.C. MAX.
C
26'-6"
20
IN ADDITION, THE SPACING OF THE TOP AND BOTTOM WALL TRACK
CONNECTIONS TO THE EXISTING STRUCTURE SHALL BE REDUCED
TO 6" O.C. MAX., AND DIAGONAL SPACING SHALL BE REDUCED TO 32" O.C.
D4
DEFLECTION TRACK WALL
ATTACHMENT TO METAL DECK
20'-6"
16"
1-5/8"
DBL STUD
METAL STUD SCHEDULE
SECTION @ TOP
D4
16"
1-5/8"
E11
SEISMIC DESIGN CATEGORIES A & B
16
3-5/8"
6"
Shremshock Architects, Inc.
7400 W. Campus Rd. Suite 150 New Albany, OH 43054
t: 614 545 4550 | f: 614 545 4555 | shremshock.com
Gerald S. Shremshock, Architect
Timothy J. Shremshock, Architect
#8 SCREWS @ 8" O.C.
E8
A-503
19'-0"
NOTE: AT LOCATIONS WHERE A STUD WALL SUPPORTS BOTH SALES AND NON-SALES SHELVING,
THE STUDS SHOWN IN THE TABLE BELOW SHALL BE "DOUBLED UP" AS FOLLOWS:
UNLESS NOTED, LIGHT GAUGE FRAMING CONNECTIONS SHALL BE MADE
USING #8 SCREWS. SEE DETAIL A1/A-504 FOR DIAGONAL BRACING
CONNECTIONS.
AT LOCATIONS WHERE SHEATHING MATERIAL IS PLACED AGAINST THE
SCREW HEADS OF LIGHTGAUGE METAL FRAMING CONNECTIONS, PANCAKE
HEAD SCREWS SHALL BE USED SO THAT THE SHEATHING MATERIAL REMAINS
STRAIGHT AND SMOOTH.
(ONE HOUR FIRE-RATED)
18
362S162-54
SECTION @ BASE
PLOTTED: 7/16/2015 - 4:03 PM
1 5/8", 22 GA. TRACK w/ 1 1/4" LEG
1 5/8", 20 GA. TRACK w/ 1 1/4" LEG
2 1/2", 20 GA. TRACK w/ 1 1/4" LEG
2 1/2", 20 GA. TRACK w/ 2" LEG
2 1/2", 18 GA. TRACK w/ 1 1/4" LEG
2 1/2", 18 GA. TRACK w/ 2" LEG
3 5/8", 20 GA. TRACK w/ 1 1/4" LEG
3 5/8", 20 GA. TRACK w/ 2" LEG
3 5/8", 18 GA. TRACK w/ 1 1/4" LEG
3 5/8", 18 GA. TRACK w/ 2" LEG
6", 20 GA. TRACK w/ 1 1/4" LEG
6", 20 GA. TRACK w/ 2" LEG
6", 18 GA. TRACK w/ 1 1/4" LEG
6", 18 GA. TRACK w/ 2" LEG
17'-6"
16"
600S162-33
ROOF DECK
VERIFY HEIGHT IN FIELD
CONCRETE SLAB
USER: JGRAY
1200S162-54
1200S162-97
SCALE:
(1) #8 WAFERHEAD
SCREW IN EACH
FLANGE OF EACH
VERT STUD. INSTALL
PER MANUFACTURERS
RECOMMENDATIONS
(NON-RATED)
12", 16 GA. STUD w/ 1 5/8" FLANGE
12", 12 GA. STUD w/ 1 5/8" FLANGE
SECTION @ BASE
LAYOUT: A-503
D
SCALE:
P:\SGH\150343 SGH-La Plaza Mall Mcallen, TX\A-503_06078.dwg
1" DEFL.
GAP
SEE SCHEDULES
FOR FINISHES
AND STUD SIZES
1000S162-43
1000S162-54
LIGHT GAUGE FRAMING SCREW CONNECTIONS
3/4"
MAX
3/4"
MAX
1" DEFL. GAP
TU
E
18 GA DEEP LEG TRACK WITH 2"
FLANGE. (DEPTH TO MATCH VERTICAL
STUD DEPTH) ATTACH TO STRUCTURE
W/ (2) #12 SCREWS AT 16" O.C.
10", 18 GA. STUD w/ 1 5/8" FLANGE
10", 16 GA. STUD w/ 1 5/8" FLANGE
16"
20
LA PLAZA MALL
G4
800S162-43
800S162-54
1-5/8"
AT
G
8", 18 GA. STUD w/ 1 5/8" FLANGE
8", 16 GA. STUD w/ 1 5/8" FLANGE
1-5/8"
3-5/8"
MAXIMUM WALL HEIGHT
OR
MAXIMUM HEIGHT TO DIAGONAL BRACE
6"
MIN.
1 12" x 16 GA. COLD
ROLLED CHANNEL LATERAL BRACING
362S162-33
362S162-43
600S162-33
600S162-43
3-5/8"
362S162-43
STUD
SPACING
SECTION @ TOP
NOT USED
3 5/8", 20 GA. STUD w/ 1 5/8" FLANGE
3 5/8", 18 GA. STUD w/ 1 5/8" FLANGE
6", 20 GA. STUD w/ 1 5/8" FLANGE
6", 18 GA. STUD w/ 1 5/8" FLANGE
362S162-33
STUD
GAUGE
PLAN VIEW
H1
2 1/2", 20 GA. STUD w/ 1 5/8" FLANGE
2 1/2", 18 GA. STUD w/ 1 5/8" FLANGE
FLANGE
WIDTH
SECTION @ BASE
METAL STUD
FLANGE STUD
WIDTH THICKNESS
=1.625" =43 MIL (18 GA.)
=1 5/8"
NEW SSMA DESIGNATION
(STEEL STUD MANUFACTURERS
ASSOCIATION)
250S162-33
250S162-43
FORMER STANDARD DESIGNATION
STUD
DEPTH
STUD
DESIGNATION
TYPICAL STRUCTURAL STUDS AND TRACKS
FRAMING SCREWS (4) TYPICAL
2" x 2" 16 GA. CLIP
ANGLE 14" LESS
THAN STUD WIDTH
METAL STUD
6"
MIN.
H
SCALE:
"
1/2
STUD (S=STUD)
DEPTH (T=TRACK)
=3.625"
=3 5/8"
FIRST LEVEL STARTS @
4'-0" ABOVE FLOOR
J
"
3/4
3/4
"
"
3/4
-
SECTION @ TOP
8'-0" O.C. FULL WALL HEIGHT
3 5/8", 18 GA STRUCTURAL METAL STUD =
7
FRAMING
DETAILS
A-503
PARTITION TYPES
8
AUTHORIZED FOR:
9
10
11
12
13
14
1
K
2
3
4
5
6
7
8
9
(2)-1/4" DIA CONC ANCHORS
(KWIK BOLT TZ BY HILTI) WITH 1
3/4" EMBED
EXIST CONC
FLOOR SLAB
11
12
13
14
EXIST CONC
FLOOR SLAB
2"x2"x0'-6" LG, 12 GA
FRAMING CLIP W/(3)-#12
SCREWS EA LEG
(2)-1/4" DIA CONC
ANCHORS (KWIK
BOLT TZ BY HILTI)
WITH 1 3/4" EMBED
10
A Subsidiary of the Luxottica Group
4000 Luxottica Place
Mason, Ohio 45040
EXIST CONC
FLOOR SLAB
(3)-#12 SCREWS
D
E
S
U
T
NO
DIAG BRACE
2"x2"x1'-0" LG, 12 GA
FRAMING CLIP
J
CONSULTANT PROJECT # 150343
DIAG BRACE
PERPENDICULAR TO
ROOF BEAMS.
EXIST STL BM
2"x2"x0'-6" LG, 12 GA
FRAMING CLIP (CENTER
CLIP IN "UP" FLUTE OF
DECK).
(3)-#12 SCREWS
DIAG BRACE
Shremshock Architects, Inc.
7400 W. Campus Rd. Suite 150 New Albany, OH 43054
t: 614 545 4550 | f: 614 545 4555 | shremshock.com
Gerald S. Shremshock, Architect
Timothy J. Shremshock, Architect
BEFORE INSTALLING ANCHORS, CONTRACTOR
SHALL VERIFY WITH MALL MANAGEMENT THAT
ATTACHMENT SHOWN IS ACCEPTABLE.
SEAL
DIAG BRACE PARALLEL TO
ROOF BEAMS.
H
H1
SCALE:
TYPICAL DIAGONAL BRACE CONNECTION
COMP MTL DECK/ CONC SLAB ON STL BEAMS
G
EXIST JOIST CHORD
OR BEAM FLG
ATTACH TO EXIST STL
W/(3)-#12 SCREWS
EXIST MTL DECK OR
COMP CONC SLAB
(6)-#12 SCREWS AT
EACH ATTACHMENT
ATTACH TO EXIST STL
W/(3)-#12 SCREWS
EXIST MTL DECK OR
COMP CONC SLAB
DIAG BRACE
LAYOUT: A-504
P:\SGH\150343 SGH-La Plaza Mall Mcallen, TX\A-504_06078.dwg
EXIST BAR JOISTS OR
STEEL BEAMS @ 6'-0"
O.C. MAX
DIAGONAL PERPENDICULAR
TO EXIST BAR JOISTS OR
STEEL BEAMS
EXIST BAR JOISTS OR
STEEL BEAMS @ 6'-0"
O.C. MAX
PLOTTED: 7/16/2015 - 4:03 PM
CONTINUOUS
DIAG BRACE
E
USER: JGRAY
AT
DIAG BRACE
EXIST JOIST
CHORD OR
BEAM FLG
LA PLAZA MALL
F
#12 SCREWS (TYP)
(2) 2x2x0'-3", 12 GA
FRAMING CLIPS
D
#12 SCREWS, TYP
SEE VIEW B-B FOR
CONNECTION
DIAGONAL
BRACING
DIAGONAL
BRACING
DIAGONAL PARALLEL
TO EXIST BAR JOISTS
OR STEEL BEAMS
C
EXISTING
JOIST
SUNGLASS HUT
LA PLAZA MALL
CONTINUOUS
SEE VIEW B-B FOR
CONNECTION
6", 16 GA MTL STUD WITH
6", 16 GA DEEP LEG TRACK.
B
2200 S. 10TH STREET
McALLEN, TX 78503
SPACE #Q14-C
2.0 TYPE: PREMIUM
SGH STORE #: 6078
#12 SCREWS @ 6" O.C. MAX
AND 2" FROM EACH END
DRAWN BY: ALW
REVIEWED BY: MLH/JMA
2 x 2 x 12 GA x 6" LG FRAMING
CLIP, ONE SIDE OF DIAG,
W/(3)-#12 SCREWS EACH LEG.
AUTHORIZED FOR:
FRAMING
DETAILS
A
A1
SCALE:
A-504
TYPICAL DIAGONAL BRACING CONNECTION ATTACHMENT TO EXISTING BAR JOIST OR STEEL BEAM
1
2
3
4
5
6
7
8
9
10
11
12
13
14
K
B.
1.
3.
4.
5.
6.
7.
8.
H
9.
10.
C.
G
D.
F
E.
4
1. DRAWINGS AND SPECIFICATIONS ARE INTENDED TO BE COMPLIMENTARY. SPECIFIC INFORMATION
MAY BE FOUND IN EITHER OR BOTH.
2. THE TERM 'OWNER' AS STATED IN THE FOLLOWING SPECIFICATIONS AND CONSTRUCTION
DOCUMENTS, REFERS TO THE TENANT OF THIS SPACE ONLY AND DOES NOT REFER TO THE
LANDLORD OF THE PREMISES.
3. APPROVED VARIANCES TO THE PLANS AND SPECIFICATIONS ON ONE PROJECT SHALL NOT
CONSTITUTE AN APPROVAL OF LIKE VARIANCES ON SUBSEQUENT PROJECTS.
2.
J
3
5
B.
C.
D.
E.
THE CONTRACTOR SHALL FURNISH FULL TIME CONTINUOUS SUPERVISION. THE PROJECT
SUPERINTENDENT SHALL REMAIN ON SITE THROUGH THE MERCHANDISE DATE OR THE
COMPLETION OF THE PUNCHLIST WHICHEVER IS LAST TO OCCUR.
SUSPENSION OF ALL CEILING AND OVERHEAD FRAMING IS TO BE FROM STRUCTURAL MALL
BEAMS AND TOP CHORD OF TRUSSES ONLY, NOT FROM MALL DECK.
GENERAL CONTRACTOR IS RESPONSIBLE FOR INSTALLATION OF IN-WALL BLOCKING FOR ALL
ITEMS IN STORE. REVIEW DRAWINGS THOROUGHLY.
ALL OWNER-FURNISHED MATERIALS ARE FURNISHED TAILGATE DELIVERY ONLY. THE CONTRACTOR
IS RESPONSIBLE TO UNLOAD, EXAMINE, AND TRANSPORT MATERIALS FROM THE POINT OF
OFF-LOAD TO THE JOBSITE OR STORAGE AREA AS APPLICABLE. MATERIALS WILL BE DELIVERED
TO THE CLOSEST AVAILABLE TRUCK DOCK OR OTHER LOCATION AS DIRECTED BY THE LANDLORD.
THE CONTRACTOR IS RESPONSIBLE FOR DAMAGE, LOSS, THEFT, OR DESTRUCTION OF ALL
OWNER-FURNISHED MATERIALS. THE CONTRACTOR WILL BE BACK-CHARGED THE FULL COST OF
REPLACEMENT MATERIALS INCLUDING FREIGHT CHARGES.
THE GENERAL CONTRACTOR SHALL EMPLOY SUBCONTRACTORS WHO ARE EXPERIENCED AND WHO
EMPLOY EXPERIENCED TRADESMEN.
THE GENERAL CONTRACTOR SHALL NOT EMPLOY NOISY CONSTRUCTION TECHNIQUES OR
EQUIPMENT DURING MALL OR STORE HOURS.
THE CONTRACTORS SHALL WORK IN COOPERATION AND HARMONY WITH THE LANDLORD AND THE
ADJACENT TENANTS IN SCHEDULING WORK IN ORDER TO CAUSE THE LEAST INCONVENIENCE TO
PERSONNEL AND PROPERTY. IF SECURITY IS REQUIRED WHILE WORKING IN ADJACENT TENANTS
SPACE, THIS COST WILL BE THE SOLE RESPONSIBILITY OF THE CONTRACTOR.
THE CONTRACTOR SHALL NOT UTILIZE GAS-OPERATED EQUIPMENT IN OCCUPIED SHOPPING
CENTERS. THE CONTRACTOR SHALL WORK IN HARMONY WITH THE LANDLORD'S REQUIREMENTS
RELATING TO NOISE ABATEMENT AND SAFETY.
THE CONTRACTOR SHALL FURNISH DUMPSTERS AS REQUIRED FOR THE EXCLUSIVE USE BY STORE
PERSONNEL DURING MERCHANDISING. THE CONTRACTOR SHALL INCLUDE IN THE BID A MINIMUM
OF ONE 40-YARD DUMPSTER OR THE EQUIVALENT. IF THE SALES AREA EXCEEDS 8,000 SQUARE
FEET, THE CONTRACTOR SHALL INCLUDE ONE ADDITIONAL DUMPSTER.
F.
1. EXERCISE PROPER PRECAUTION TO VERIFY ALL EXISTING CONDITIONS AND LAYOUT OF WORK.
CONTRACTOR TO NOTIFY OWNER'S CONSTRUCTION MANAGER OF ANY DISCREPANCIES
IMMEDIATELY. CONTRACTOR IS RESPONSIBLE FOR ANY ERROR RESULTING FROM FAILURE TO
EXERCISE SUCH PRECAUTION. SUCH ERROR WILL NOT BE CONSIDERED SUBSEQUENTLY AS A
BASIS FOR EXTRA COMPENSATION.
2. SHOULD A CONTRACTOR FIND DISCREPANCIES IN, OR OMISSIONS FROM THE DRAWINGS OR
SPECIFICATIONS, OR SHOULD HE BE IN DOUBT AS TO THEIR MEANING, HE SHALL AT ONCE
NOTIFY THE OWNER'S CONSTRUCTION MANAGER.
3. GENERAL CONTRACTOR IS RESPONSIBLE FOR SUPPLYING OR RENTING ALL TOOLS, WELDERS,
GENERATORS, ETC. FOR COMPLETING PROJECT.
1.
ALL WORK, MATERIALS AND INSTALLATION SHALL BE IN STRICT ACCORDANCE WITH ALL
ORDINANCES, STATE AND LOCAL BUILDING CODES, LATEST EDITION, AND FOLLOW APPLICABLE
LANDLORD REQUIREMENTS.
2. DESIGN LOADS: LOADS AND CODE RESTRICTIONS FOR ALL DESIGN CONSIDERATIONS SHALL
CONFORM TO THE LOCAL AND STATE CODES, AND ALL GOVERNING CODES.
1.
F.
THE AMERICAN INSTITUTE OF ARCHITECTS DOCUMENT A201 "GENERAL CONDITIONS OF THE
CONTRACTOR FOR CONSTRUCTION" IS A PART OF THE CONTRACT DOCUMENTS.
6
SHALL BE FOUR INCH THICK CONCRETE SLAB REINFORCED WITH 6"x 6"W.W.F.; CONCRETE TO BE
3,500 PSI OR HIGHER PLACED OVER COMPACTED SAND AGGREGATE BASE. PLACE 10 MIL VAPOR
BARRIER AT THE MIDPOINT OF THE COMPACTED SAND/AGGREGATE BASE. THE SOIL SHALL BE INSECT
TREATED IF CUSTOMARY TO THE LOCALITY OR AS REQUIRED BY LANDLORD.
PROVIDE JOINT SEALANT IN ALL CONCRETE CONTROL JOINTS AS SPECIFIED IN DIVISION 7.
PROVIDE JOINT FILLER STRIPS WHERE APPLICABLE: ASTM D-1751, CELLULOSE FIBER.
VAPOR RETARDER, CLEAR 10 MIL POLYETHELENE SHEET.
SLAB FINISHES
1. FLOAT FINISH FOR INTERIOR STEPS, RAMPS AND SURFACES TO RECEIVE WATER PROOFING OR
OTHER DIRECT-APPLIED MATERIAL
2. TROWELED FINISH FOR FLOOR SURFACES AND FLOORS TO RECEIVE FLOOR COVERINGS, PAINT
OR OTHER THIN FILM FINISH COATINGS.
3. TROWEL AND FINE BROOM FINISH FOR SURFACES TO RECEIVE THINSET TILE.
4. NON-SLIP BROOM FINISH FOR EXTERIOR CONCRETE PLATFORMS, STEPS AND RAMPS.
ANHYDROUS CALCIUM CHLORIDE CONCRETE MOISTURE VAPOR EMISSION TEST KIT CONDUCTING THE
MOISTURE TEST
1.
: BEFORE YOU TEST, MAKE SURE YOU HAVE BASIC TOOLS FOR
CLEANING THE SLAB, INCLUDING A SCRAPER AND WIRE BRUSH. MAKE SURE YOU HAVE A
QUALITY GRAM SCALE AND A PROPER SUPPLY OF TEST KITS AND PROTECTIVE CONES. ENSURE
BUILDING CLIMATE IS BETWEEN 65 & 85 DEGREES FAHRENHEIT WITH RELATIVE HUMIDITY %
BETWEEN 40-60 FOR AT LEAST 48 HOURS PRIOR TO, AND DURING TESTING.
2.
: THE SLAB MUST BE CLEAN OF DEBRIS AND ADHESIVE RESIDUE.
SHOT BLAST SURFACE OR WIRE BRUSH SLAB CLEAN. REMOVE DUST THOROUGHLY. DO NOT
USE CHEMICALS OF ANY KIND TO CLEAN THE FLOOR. AVOID TEST LOCATIONS NEAR CRACKS OR
JOINTS, OR IN DIRECT SUNLIGHT. PREPARE 3 TEST SITES FOR THE FIRST 1,000 SQ. FT. AND
INCLUDE 1 MORE TEST FOR EACH ADDITIONAL 1,000 SQUARE FEET OF AREA.
3.
: READ THE WARNING LABEL ON PACKAGE AND THEN OPEN THE
CONTAINER BAG. SET THE ENTIRE TAPE SEALED DISH ON THE GRAM SCALE AND RECORD ITS
WEIGHT ON THE DISH LID AND ON THE TEST KIT BOOKLET. RECORD THE STARTING DATE AND
TIME AS WELL. ENSURE THAT THE SAME SCALE WILL BE AVAILABLE FOR RE-WEIGHING THE DISH,
OR THE VALIDITY OF THIS TEST WILL BE COMPROMISED.
4.
: REMOVE THE BLUE VINYL TAPE FROM THE DISH. BE CAREFUL NOT
TO LOSE THE TAPE AS YOU WILL NEED TO RESEAL THE DISH LATER. STORE THE DISH LID
CAREFULLY AND STICK THE TAPE ALONG THE SIDE OF THE PLASTIC. DOME TO KEEP IT SAFE.
SOME PEOPLE PREFER TO TAPE THE DISH'S LID TO THE INSIDE OF THE DOME WHERE IT CAN BE
READ THROUGH THE TOP. DO NOT TOUCH OR SPILL THE CALCIUM CHLORIDE.
5.
: PLACE THE OPEN DISH ON THE SLAB MAKING SURE THE CALCIUM CHLORIDE
INSIDE IS FAIRLY LEVEL. DO NOT SET THE KIT DIRECTLY OVER A CONTROL JOINT OR CRACK.
REMOVE THE WHITE PAPER ON THE DOME, AND CENTER THE DOME OVER THE DISH. THE ONLY
MOISTURE ABSORBED BY THE CALCIUM CHLORIDE MUST BE WITHIN THE 70 SQUARE INCH AREA
OF THE DOME THAT IS IN CONTACT WITH THE CONCRETE SLAB.
6.
: USING THE HANDLE OF YOUR WIRE BRUSH OR OTHER TOOL, FIRMLY
SQUASH THE GASKET UNDER THE FLANGES OF THE DOME. THE IDEAL INSTALLATION WILL SEAT
THE OUTER FLANGE OF THE DOME TO THE SLAB. THEN THE GASKET MATERIAL WILL MOVE TO
LINE UP WITH THE INSIDE EDGE OF THE DOME. PLACE YOUR HAND OVER THE DOME AND GENTLY
APPLY PRESSURE. THERE SHOULD BE NO LEAKS IN THE GASKET.
7.
: PLACE THE OPTIONAL SAFETY CONE OVER THE DOME AND LET THE
TEST REMAIN UNDISTURBED FOR 60 TO 72 HOURS. MOST MANUFACTURERS OF FLOORING
PRODUCTS RECOMMEND AT LEAST ONE KIT PER 1,000 SQUARE FEET. THE TEST ONLY
MEASURES A SMALL AREA OF SLAB SURFACE AND MOISTURE LEVELS CAN VARY GREATLY OVER
1,000 SQ. FT. TEST SEVERAL AREAS WHENEVER POSSIBLE.
8.
: AFTER 60 TO 72 HOURS, CUT OPEN THE DOME AND
CAREFULLY RETRIEVE THE DISH. REPLACE THE LID AND SEAL IT BACK UP WITH THE BLUE TAPE.
WEIGH THE DISH AGAIN ON THE SAME GRAM SCALE. RECORD THE ENDING WEIGHT, DATE, AND
TIME ON THE DISH LID AS WELL AS ON THE TEST KIT BOOKLET. FOLLOW THE INSTRUCTIONS IN
THIS BOOKLET TO COMPUTE THE MOISTURE VAPOR EMISSION RATE.
CALCULATING RESULTS: USE THE FOLLOWING EQUATION TO DETERMINE THE VAPOR EMISSION
VOLUME IN POUNDS PER 1,000 SQUARE FEET IN 24 HOURS. SEE FOOTNOTE.
EQUATION TO DETERMINE VAPOR
EMISSION IN POUNDS:
E
1.
2.
3.
4.
USER: JGRAY
PLOTTED: 7/16/2015 - 4:03 PM
P:\SGH\150343 SGH-La Plaza Mall Mcallen, TX\A-701_06078.dwg
LAYOUT: A-701
5.
D
6.
C
7.
8.
9.
10.
11.
B
12.
13.
WEIGHT GAIN X 118.932 =
WITHIN FIVE (5) DAYS OF COMMENCEMENT OF CONSTRUCTION, OR WITHIN TWO (2) DAYS
FOLLOWING COMPLETION OF DEMOLITION, THE CONTRACTOR SHALL CAREFULLY EXAMINE THE
SITE AND REPORT TO THE OWNER'S CONSTRUCTION MANAGER ANY DISCREPANCIES IN THE
LEASE-HOLD DIMENSIONS OR CONFLICTS BETWEEN THE PHYSICAL SPACE AND THE INTENT OF
THE WORKING DRAWINGS (G.C. TO PAY SPECIAL ATTENTION TO POP-UP CEILING AREAS, CEILING
HEIGHTS, AND AVAILABLE HEIGHT FOR ROLL-UP ENTRANCE GRILLES).
GENERAL CONTRACTOR IS TO CONTACT LANDLORD'S ON-SITE MANAGER PRIOR TO ANY
DEMOLITION WORK TO DETERMINE THE AVAILABILITY OF DUMPSTER PLACEMENT, NOISE AND
DUST ABATEMENT REQUIREMENTS, ETC.
GENERAL CONTRACTOR IS TO ARRANGE WITH THE LANDLORD A CONVENIENT TIME TO PERFORM
DEMOLITION WORK AND INSTALL TEMPORARY PROTECTED MEANS OF EGRESS FROM REQUIRED
EXITS, INCLUDING TEMPORARY LIGHTING AND SAFETY DEVICES, ALL IN ACCORDANCE WITH
GOVERNING STATE AND LOCAL CODE AND LANDLORD REQUIREMENTS.
GENERAL CONTRACTOR TO ERECT BARRICADE AT STOREFRONT PER LANDLORD'S
SPECIFICATIONS. GENERAL CONTRACTOR TO INSTALL OWNER SUPPLIED BARRICADE SIGN (IF
PROVIDED) AS SHOWN ON INSTRUCTIONS SENT WITH BID PACKAGES.
THE GENERAL CONTRACTOR SHALL REMOVE, REPAIR, RESTORE AND REPLACE WHERE NECESSARY
OR INDICATED ON THE DRAWINGS OR AS REQUIRED. CUT ALL NECESSARY OPENINGS FOR ANY
REQUIRED PURPOSE AND REPAIR, WHERE NECESSARY, AFTER CUTTING. INSOFAR AS POSSIBLE,
ALL PROTRUSIONS, MARKS, CRACKS OR OTHER EVIDENCE OF A DEFICIENT OR DAMAGED
CONDITION SHALL BE ELIMINATED UNLESS SPECIFICALLY NOTED OTHERWISE. ANY PARTS WHICH
ARE SPLIT, CRACKED, CHIPPED, SPALLED, BROKEN, MISSING, OR OUT OF LINE OR ADJUSTMENT,
MECHANICALLY OR STRUCTURALLY UNSAFE OR UNSOUND, BENT, TORN, OR OTHERWISE
DEFICIENT OR INJURED IN ANY MANNER, SHALL BE REMOVED, REPLACED, RESTORED, OR
SATISFACTORILY REPAIRED AS DIRECTED BY THE OWNER'S CONSTRUCTION MANAGER.
GENERAL CONTRACTOR IS RESPONSIBLE FOR THE REMOVAL AND DISPOSAL OF ALL LEASE-HOLD
IMPROVEMENTS INCLUDING, BUT NOT LIMITED TO: INTERIOR WALLS, CEILINGS, FLOOR
COVERINGS (ALL ADHESIVES), PLATFORMS, STORE-FRONTS, ETC. (UNLESS INDICATED
OTHERWISE ON ARCHITECTURAL DRAWINGS). ALL EXISTING UNUSED MECHANICAL, ELECTRICAL
AND/OR PLUMBING FIXTURES AND EQUIPMENT, INCLUDING ABANDONED ROOFTOP HVAC
EQUIPMENT AND CURBS (UNLESS INDICATED OTHERWISE ON MECHANICAL AND ELECTRICAL
DRAWINGS) AND/OR SKYLIGHTS ARE TO BE REMOVED AND THE ROOF PATCHED PER ITEM #12
BELOW: CAPPING IS
PERMITTED!
GENERAL CONTRACTOR IS RESPONSIBLE FOR THE REMOVAL AND DISPOSAL OF ALL LOOSE ITEMS
SUCH AS, BUT NOT LIMITED TO: TRADE FIXTURES, MISCELLANEOUS DECORATIONS, KITCHEN
EQUIPMENT, ETC.
ALL ABANDONED ELECTRICAL/TELEPHONE CONDUIT, PLUMBING LINES AND MECHANICAL
DUCTWORK MUST BE REMOVED TO THE POINT OF ORIGIN.
INFORM THE LANDLORD'S ON-SITE MANAGER OF ANY UTILITY NEEDING TO BE DISCONNECTED OR
CAPPED, PRIOR TO DOING SO.
GENERAL CONTRACTOR IS TO EXERCISE EXTREME CARE DURING DEMOLITION SO AS NOT TO
DAMAGE OR DISRUPT UTILITIES OR SPRINKLER LINES WHICH MIGHT PASS THROUGH THIS SPACE
TO SERVICE OTHER MALL SPACES OR OTHER TENANTS (G.C. WILL BEAR SOLE RESPONSIBILITY
FOR ANY SUCH DAMAGE OR DISRUPTION).
GENERAL CONTRACTOR IS RESPONSIBLE FOR ALL DEMOLITION WORK AND MUST INFORM
OWNER'S CONSTRUCTION MANAGER OF THE EXTENT OF SUCH WORK, PRIOR TO BIDDING.
GENERAL CONTRACTOR IS TO DETERMINE HIS RESPONSIBILITY FOR THE FLOOR SLAB AND
DEMISING WALL INSTALLATION OR MODIFICATIONS WITH LANDLORD AND OWNER'S
CONSTRUCTION MANAGER TO MEET ALL TENANT IMPROVEMENT CRITERIA AND RESPONSIBILITY
SET BY THE LANDLORD OR OWNER. GENERAL CONTRACTOR IS TO VERIFY THE ACTUAL
CONDITION OF THE PERIMETER DEMISING WALLS AND/OR FLOOR SLAB PRIOR TO BIDDING. BID
IS TO INCLUDE ALL WORK REQUIRED.
a.
b.
c.
d.
THE VAPRECISION ANHYDROUS CALCIUM CHLORIDE TEST KIT, INSTRUCTIONS, CALCULATIONS AND ALL
OTHER PRINTED INFORMATION ARE PROPERTY OF VAPRECISION TESTING SYSTEMS, COPYRIGHT 1994.
REVISED AUGUST 1999. THE VAPRECISION ANHYDROUS CALCIUM CHLORIDE TEST KIT CONFORMS TO
THE AMERICAN SOCIETY FOR TESTING & MATERIALS DOCUMENTATION ASTM E-1907-97 AND
ASTM-F_1869-98 AND IS ACTUALLY PICTURED IN THE ASTM E-1907 SPECIFICATION. ASTM DOCUMENTS
ARE THE COPYRIGHT PROPERTY OF ASTM, AND CAN BE PURCHASED EASILY FROM THEIR WEB SITE AT
WWW.ASTM.ORG.
: THE FORMULA ABOVE COMPLIES TO ASTM DOCUMENTATION AS OF 8/99 AND DEDUCTS THE
AREA OF THE CALCIUM CHLORIDE DISH IN CONTACT WITH THE SLAB. THERE IS A DEBATE REGARDING
THIS ISSUE. TO CALCULATE THE TEST RESULT WITHOUT DEDUCTING THE AREA OF THE DISH, USE
108.846 INSTEAD OF 118.932.
A. THE CONTRACTOR SHALL ACCOMPLISH ANY MISCELLANEOUS MASONRY WORK INDICATED ON THE
PLANS, OR NOT INDICATED ON THE PLANS YET INCIDENTAL TO THE ACCOMPLISHMENT OF OTHER
WORK. WHERE APPLICABLE, MASONRY WORK SHALL MATCH EXISTING WORK. FINISH BRICK WORK
SHALL BE NEATLY TOOTHED INTO EXISTING MASONRY IF APPLICABLE.
A. STRUCTURAL STEEL: REFER TO STRUCTURAL DRAWINGS (WHERE APPLICABLE.)
B. METAL STUDS: COLD-FORMED GALVANIZED STEEL STUDS SIZED AS INDICATED ON DRAWINGS, WHICH
CONFORM TO ASTM C955 & C1007 . INCLUDE ALL ACCESSORIES, SUCH AS BRIDGING, TRACK, ETC.
PROVIDE ALL MISCELLANEOUS BOLTS, CLIPS, ANCHORS, ANGLES, BRACKETS, SLEEVES, FASTENERS, AND
OTHER METAL ITEMS AS REQUIRED. WOOD STUDS MAY BE SUBSTITUTED WHERE PERMISSIBLE BY CODES.
1. COLD FORMED STEEL FRAMING SHALL CONFORM TO REQUIREMENTS OF THE LATEST EDITION OF ANSI
"SPECIFICATION FOR DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS"
2. STUDS SHALL BE INSTALLED SO THE ENDS ARE POSITIONED AGAINST THE INSIDE OF THE RUNNER
TRACK WEB PRIOR TO FASTENING AND SHALL BE ATTACHED TO BOTH FLANGES OF THE UPPER AND
LOWER RUNNER TRACKS.
3. FOR VERTICAL STUDS WHERE THERE IS NO SHEATHING ATTACHED (SUCH AS ABOVE THE CEILING,) OR
WHERE SHEATHING IS ATTACHED TO ONLY ONE FACE, PROVIDE STANDARD BRIDGING AT 48" O.C. MAX.
ATTACH PER MANUFACTURER'S SPECIFICATIONS.
C. DECORATIVE METALS: INSTALL OWNER PROVIDED DECORATIVE METAL SUCH AS STAINLESS STEEL,
PREFINISHED METAL, ETC. AS INDICATED ON DRAWINGS, PER MANUFACTURER'S RECOMMENDATIONS.
D. OWNER SUPPLIED METALS: G.C. IS RESPONSIBLE TO CONTACT VENDOR FOR ORDERING OF
PREFINISHED METAL STOREFRONT PANELS, CORNER GUARDS AT TILE FACED COLUMNS. REFER TO
INDIVIDUAL DETAILS FOR APPLICATION AND INSTRUCTIONS.
E. MISCELLANEOUS METALS: PROVIDE METAL SHAPES AND FABRICATIONS AS REQUIRED AND NOT INCLUDED
AS PART OF OTHER SECTIONS, WITH ANCHORS AND ACCESSORIES AS REQUIRED FOR COMPLETE
INSTALLATION. SUBMIT SHOP DRAWINGS FOR CUSTOM DATA, PRODUCT DATA FOR MANUFACTURED ITEMS
AND TEMPLATES FOR ANCHOR INSTALLATION BY OTHERS. STEEL SHAPES TO BE ASTM A36 STEEL.
A. PROVIDE NEW LUMBER, BEARING GRADE AND TRADEMARK OF ASSOCIATION UNDER WHICH IT WAS
PRODUCED.
B. LAYOUT, CUT, FIT AND ERECT FRAMING FOR ROUGH AND FINISHED WORK. INSTALL BLOCKING,
NAILERS, FURRING AND OTHER ROUGH AND FINISHED MATERIALS AS REQUIRED. BRACE, PLUMB
LEVEL MEMBERS IN TRUE ALIGNMENT AND RIGIDLY SECURE IN PLACE WITH SUFFICIENT NAILS, SCREWS
AND BOLTS AS NECESSARY.
C. USE FIRE RETARDANT LUMBER AND TRIM WHERE REQUIRED BY STATE OR LOCAL CODES, WHICH BEAR
THE MANUFACTURER'S STAMP OF AUTHENTICITY.
D. FURNISH AND INSTALL ALL GROUNDS OR BLOCKING REQUIRED TO RECEIVE STORE FIXTURES OR
OTHER WALL HUNG ELEMENTS, IF SHOWN ON DRAWINGS.
E. FURNISH AND INSTALL ALL ROUGH HARDWARE, ANCHORS, BOLTS, ETC., AS REQUIRED FOR
CARPENTRY WORK.
F. FINISH CARPENTRY: CONFORM TO ARCHITECTURAL WOODWORK INSTITUTE (AWI) QUALITY STANDARDS
OR WOODWORK INSTITUTE OF CALIFORNIA (WIC) "MANUAL OF MILLWORK" STANDARDS. PROVIDE
PRIMED WOOD WALL BASE - COPE ALL CORNERS, MITER ALL OUTSIDE CORNERS, COUNTER SINK AND
PUTTY ALL NAIL HOLES AND SAND SMOOTH.
A. THE CONTRACTOR IS RESPONSIBLE TO DETERMINE IF A NEW CONCRETE SLAB IS REQUIRED IN ALL OR
PART OF THE LEASED SPACE. SUCH FLOOR SLAB SHALL BE INSTALLED IN ACCORDANCE WITH ALL
REQUIREMENTS, LOCAL CODES, OR COMMON STANDARDS OF PRACTICE TO THE LOCALITY OF THE
PROJECT OR WHICHEVER IS STRICTER. IN THE ABSENCE OF THE ABOVE, THE CONTRACTOR SHALL
CONTACT THE OWNER FOR DIRECTION. MINIMUM REQUIREMENTS FOR THE FLOOR SLABS ON GRADE
1
2
3
POUNDS PER 1,000 SQUARE FEET IN 24 HOURS
POUNDS PER 1,000 SQUARE FEET IN 24 HOURS
A
4
5
9
10
11
12
6
7
13
14
(3)
E.
F.
C.
D.
1.
1.
:
GENERAL CONTRACTOR TO CONTACT LANDLORD'S ON-SITE MANAGER FOR SPECIFICATIONS
ON ROOF PATCHING OR NAME OF ROOFING CONTRACTOR TO CONTACT FOR REPAIRS.
:
GENERAL CONTRACTOR TO PROVIDE AND INSTALL RIGID AND/OR FULL BATT INSULATION AND
4 MIL POLYETHELENE (VISQUEEN) VAPOR RETARDER AT WALLS AND CEILING AS REQUIRED BY
LANDLORD AND CONSTRUCTION DRAWINGS.
1.
GENERAL: PROVIDE EXTERIOR AND INTERIOR JOINT SEALERS NOT PROVIDED ELSEWHERE;
TYPE SUITABLE FOR APPLICATION INDICATED WITH ACCESSORIES AS REQUIRED FOR
COMPLETE INSTALLATION.
2. INSTALLER QUALIFICATIONS: FIRM WITH MINIMUM FIVE YEAR'S SUCCESSFUL EXPERIENCE ON
PROJECTS OF SIMILAR TYPE AND SIZE, USING SPECIFIED PRODUCTS.
3. WARRANTY: REPAIR OR REPLACE JOINT SEALERS WHICH FAIL TO PERFORM AS INTENDED,
BECAUSE OF LEAKING, CRUMBLING, HARDENING, SHRINKAGE, BLEEDING, SAGGING,
STAINING OR LOSS OF ADHESION; WARRANTY PERIOD TWO YEARS.
4. EXTERIOR NON-TRAFFIC JOINTS: GE/SILPRUF, DOW/790-795 OR PECORA/854, LOW
MODULES SILICONE SEALANT.
5. TRAFFIC BEARING JOINTS: MAMECO/VULKEM 245 OR PECORA/NR-200 UREXPAN,
MULTI-COMPONENT POLYURETHANE, SELF-LEVELING JOINT SEALER.
6. MILDEW-RESISTANT SANITARY SEALANTS: GE/SANITARY SEALANT, DOW/BATHTUB CAULK, OR
PECORA/863 #345 WHITE; PROVIDE AT INTERIOR AREAS WHERE SEALANT WILL BE EXPOSED
TO WATER.
7. GENERAL INTERIOR JOINT SEALER: PECORA/AC-20 OR SONNEBORN/SONOLAC, ACRYLIC OR
LATEX EMULSION. MISCELLANEOUS MATERIALS: PRIMERS, SEALERS, JOINT CLEANERS, BOND
BREAKER TAPE
8. AND SEALANT BACKER RODS AS RECOMMENDED BY SEALANT MANUFACTURER FOR
APPLICATIONS INDICATED.
a. OVERSIZE BACKER ROD MINIMUM 30 % TO 50 %%% OF JOINT OPENING.
9. COLORS: AS INDICATED OR SELECTED BY OWNER'S PROJECT MANAGER FROM
MANUFACTURER'S FULL RANGE OF COLORS.
10. PREPARATION: CLEAN JOINT SURFACES IMMEDIATELY BEFORE INSTALLATION OF JOINT
SEALER AND PRIME OR SEAL JOINT SURFACES AS RECOMMENDED BY MANUFACTURER.
11. INSTALLATION: COMPLY WITH MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS AND
ASTM C1193.
b. EMPLOY INSTALLATION TECHNIQUES WHICH WILL ENSURE JOINT SEALERS ARE
DEPOSITED IN UNIFORM, CONTINUOUS RIBBONS WITHOUT GAPS OR AIR POCKETS,
WITH COMPLETE "WETTING" OF BOND SURFACES.
1.
2.
E.
EDGE SEALING: IMMEDIATELY AFTER CUTTING THE FINAL SIZES, AND APPLYING EDGE
TREATMENT; FACTORY SEAL EDGES OF MIRRORS WITH EDGE SEALER TO PREVENT
CHEMICAL OR ATMOSPHERIC PENETRATION OF GLASS COATING.
6. MISCELLANEOUS MATERIALS
a. SETTING BLOCK: NON-RUBBER OR NON-NEOPRENE BASED ELASTOMERIC MATERIAL
MANUFACTURED FOR SETTING SILVERED FLAT GLASS MIRRORS, COMPATIBLE WITH
ADHESIVE USED FOR PLACEMENT, WITH A TYPE A SHORE DUROMETER HARDNESS OF
85, PLUS OR MINUS 5. 1/8" WIDE X 1/4" HIGH X 4" LONG.
b. EDGE SEALER: COATING COMPATIBLE WITH GLASS COATING AND APPROVED BY MIRROR
MANUFACTURER FOR USE IN PROTECTING AGAINST SILVER DETERIORATION AT MIRROR
EDGES.
c. MIRROR MASTIC: PALMER PRODUCTS CORP., "MIRROR-MASTIC", (502) 893-3668,
(800) 431-6151, FAX (502) 895-9253.
d. DRYWALL AND PLYWOOD PAINT (POROUS SUBSTRATE PRIMER): PALMER PRODUCTS
CORP. "MIRROR-MASTIC BOND", (502) 893-3668, (800) 431-6151, FAX (502)
895-9253.
e.
NEW CONSTRUCTION - GENERAL CONTRACTOR TO FURNISH AND INSTALL 48" WIDE
REFLECTIVE BUBBLE INSULATION MADE WITH TWO LAYER REFLECTIVE METALIZED ALUMINUM
SEPARATED BY A 5/16" ENCLOSED AIR SPACE. INSTALL PER MANUFACTURERS
SPECIFICATIONS.
EXISTING CONSTRUCTION - GENERAL CONTRACTOR TO FURNISH AND INSTALL 24" WIDE .024
WHITE ALUMINUM TRIM COIL. INSTALL PER MANUFACTURERS SPECIFICATIONS.
7.
WEATHER BARRIER MEMBRANE (DUPONT TYVEK COMMERCIALWRAP)
MANUFACTURER: DUPONT; 4417 LANCASTER PIKE, CHESTNUT RUN PLAZA 728, WILMINGTON, DE
19805; 1-800-44-TYVEK (8-9835);
INSTALLATION SHALL BE IN ACCORDANCE WITH WEATHER BARRIER MANUFACTURER'S
INSTALLATION GUIDELINES AND RECOMMENDATIONS. SECURE USING WEATHER BARRIER
MANUFACTURER RECOMMENDED FASTENERS, SPACE 12-18 INCHES VERTICALLY ON CENTER
ALONG STUD LINE, AND 24 INCHES ON CENTER, MAXIMUM HORIZONTALLY.
8.
:
1. DOOR HARDWARE: REFER TO DOOR SCHEDULE FOR HARDWARE SPECIFICATIONS.
2. HOLLOW METAL FRAMES: K.D. MINIMUM 16 GAUGE. SIZE AND SHAPE PER DOOR SCHEDULE.
3. LABELED DOORS: WHERE REQUIRED, PROVIDE U.L. LABEL DOORS AND FRAMES PER
APPLICABLE STATE AND LOCAL BUILDING CODES. LABEL DOORS TO RECEIVE DOOR CLOSER.
4. FABRICATE AND ERECT TRUE, PLUMB AND SQUARE AS SPECIFIED AND AS DETAILED AND PER
MANUFACTURER'S RECOMMENDATIONS.
B.
:
1. GLASS
a. STOREFRONT GLASS TO BE HORIZONTALLY TEMPERED. SIZE AND NUMBER OF PIECES
AS SHOWN ON DRAWINGS. GLAZING CONTRACTOR TO PROVIDE AND INSTALL ALL
GLAZING CHANNELS, GASKETS, BLOCKING, ETC., REQUIRED FOR COMPLETE
INSTALLATION. PROVIDE NEAT, UNIFORM (1/4" WIDE UNLESS NOTED OTHERWISE) GAPS
BETWEEN GLASS PANES AND BETWEEN PANES AND ADJACENT VERTICAL SURFACES.
b. ARRISSED EDGE: EDGES TO BE DIAMOND GROUND 1/16" 45 DEGREE BEVEL AT FRONT
AND BACK FACES WITH ALL EXPOSED EDGES UNIFORMLY MACHINE POLISHED.
c. OWNER REQUIRES THAT STOREFRONT GLASS NOT BOW MORE THAN +/- 1/16" OUT OF
VERTICAL.
d. ALL GLASS TO BE SET IN GLAZING GASKETS THE SIZE AND SHAPE NECESSARY TO
ACCOMPLISH GOOD WORKMANSHIP. CAULKING NOT PERMITTED.
C.
:
1. QUALITY ASSURANCE
a. INSTALLER QUALIFICATIONS: AN EXPERIENCED INSTALLER WHO HAS COMPLETED MIRROR
GLAZING SIMILAR IN MATERIAL, DESIGN, AND EXTENT TO THAT INDICATED; WHOSE WORK
HAS RESULTED IN MIRROR INSTALLATIONS WITH A RECORD OF NOT LESS THAN 5 YEARS
OF SUCCESSFUL IN-SERVICE PERFORMANCE.
b. SOURCE LIMITATIONS FOR MIRRORS: OBTAIN MIRRORS FROM ONE
SUPPLIER/MANUFACTURER FOR EACH TYPE OF MIRROR INDICATED.
c. SOURCE LIMITATIONS FOR GLAZING ACCESSORIES: OBTAIN GLAZING ACCESSORIES
FROM ONE SOURCE FOR EACH TYPE OF ACCESSORY INDICATED.
d. GLAZING PUBLICATIONS: COMPLY WITH THE APPLICABLE RECOMMENDATIONS OF THE
FOLLOWING. WHERE RECOMMENDATIONS CONFLICT THE MORE STRINGENT SHALL APPLY.
e. GLASS ASSOCIATION OF NORTH AMERICA (GANA): "GLAZING MANUAL" AND THE MIRROR
DIVISION'S "MIRRORS, HANDLE WITH EXTREME CARE: TIPS FOR THE PROFESSIONAL ON
THE CARE AND HANDLING OF MIRRORS."
f. NATIONAL GLASS ASSOCIATION (NGA): "CUSTOM MIRRORS, FABRICATION AND
INSTALLATION.
2. DELIVERY, STORAGE, AND HANDLING.
a. PROTECT MIRRORS ACCORDING TO MIRROR MANUFACTURER'S WRITTEN INSTRUCTIONS
AND AS NEEDED TO PREVENT DAMAGE TO MIRRORS FROM CONDENSATION,
TEMPERATURE CHANGES DIRECT EXPOSURE TO SUN, OR OTHER CAUSES.
b. COMPLY WITH MIRROR MANUFACTURER'S WRITTEN INSTRUCTIONS FOR SHIPPING,
STORING, AND HANDLING MIRRORS AS NEEDED TO PREVENT DETERIORATION OF
SILVERING, DAMAGE TO EDGES, AND ABRASION OF GLASS SURFACES AND APPLIED
COATINGS. STORE INDOORS, PROTECTED FROM MOISTURE INCLUDING CONDENSATION.
3. PROJECTION CONDITIONS: ENVIRONMENTAL LIMITATIONS - DO NOT INSTALL MIRRORED
GLASS UNTIL AMBIENT TEMPERATURE AND HUMIDITY CONDITIONS ARE MAINTAINED AT
LEVELS INDICATED FOR FINAL OCCUPANCY.
4. SILVERED FLAT GLASS MIRROR MATERIAL: 6.0 MM THICK AND COMPLYING WITH ASTM C
1503, MIRROR SELECT QUALITY FOR USE IN VISUALLY DEMANDING APPLICATIONS
REQUIRING MINIMAL DISTORTIONS AND BLEMISHES.
5. FABRICATION
a. CUTOUTS: FABRICATE CUTOUTS FOR NOTCHES AND HOLES IN MIRRORS WITHOUT
MARRING VISIBLE SURFACES. LOCATE AND SIZE CUTOUTS SO THEY FIT CLOSELY
AROUND PENETRATIONS IN MIRRORS.
b. MIRROR EDGE TREATMENT: CUTTING AND POLISHING
(1) TYPICAL MIRRORS: FLAT EDGES WHERE THE CLEAN CUT "SQUARE" EDGE OF THE
GLASS IS FLAT AND SURFACES EDGES ARE SLIGHTLY ARRISSED. AFTER GRINDING
THE ARISSES, EDGES SHALL BE POLISHED TO A HIGH GLOSS SURFACE WHERE THE
SURFACE REFLECTIVITY IS SIMILAR IN APPEARANCE TO THE MAJOR SURFACE OF
THE GLASS.
(2) BEVELED EDGED MIRRORS: PROVIDE BEVELED EDGED MIRRORS WHERE THE
SURFACE EDGE OF THE GLASS IS BEVELED TO WIDTH INDICATED ON THE OWNER
FURNISHED DRAWINGS. THE ANGLE FORMED BY THE INTERSECTION OF THE PLANCE
OF THE BEVEL WITH THE MAJOR SURFACE FACE OF THE GLASS SHALL BE BETWEEN
3 TO 10 DEGREES. THE BEVELED SURFACE AND THE NOSE OF THE BEVEL SHALL BE
POLISHED TO A HIGH GLOSS SURFACE WHERE THE SURFACE REFLECTIVITY IS
SIMILAR IN APPEARANCE TO THE MAJOR SURFACE OF THE GLASS.
8
9
10
TOP AND BOTTOM ALUMINUM J CHANNELS: ALUMINUM EXTRUSIONS WITH A RETURN
DEEP ENOUGH TO PRODUCE A GLAZING CHANNEL TO ACCOMMODATE 6 MM THICK
MIRRORS AND HEAVY BODIED MIRROR MASTIC SPECIFIED AND IN A SINGLE PIECE. THE
ENDS OF THE BACK LIPS OF ALL CHANNELS SHALL BE FACTORY SNIPPED AND FILED SO
THAT THEY WILL NOT BE SEEN AFTER INSTALLATION.
(1) BOTTOM AND SIDE TRIM: C.R. LAURENCE CO. INC., 1/4" STANDARD "J" CHANNEL
(CATALOG NUMBER D636P POLISHED FINISH), (800) 421-6144, FAX (800)
262-3299. J-CHANNELS FORMED WITH FRONT LEG AND BACK LEG NOT LESS THAN
3/8" AND 7/8" IN HEIGHT, RESPECTIVELY.
D.
1.
2.
4.
5.
TOP TRIM: C.R. LAURENCE CO. INC., 1/4" DEEP NOSE "J" CHANNEL (CATALOG
NUMBER D645P POLISHED FINISH), (800) 421-6144, FAX (800) 262-3299.
J-CHANNELS FORMED WITH FRONT LEG AND BACK LEG NOT LESS THAN 5/8" AND
1-3/16" IN HEIGHT, RESPECTIVELY.
f. STUD FASTENERS: PROVIDE #6 GAGE DIAMETER, 1-5/8" LONG, PHILLIPS BUGLE HEAD,
SELF-DRILLING TYPE, FINE THREADED STEEL SCREW FASTENERS IN QUANTITY AS
REQUIRED FOR SUPPORT AND FASTENING OF WOOD TRIMS AND MIRRORS CHANNELS
TO DRYWALL STUD FRAMING AND SHEET METAL BACKER PLATES. HILTI KWI-PRO SELF
DRILL DRYWALL SCREWS, ORDERING NAME: 6" X 1'-5/8" PBH SD, ITEM #: 00086216;
HILTI CORPORATION (800) 879-8000.
g. PLASTIC WOOD FILLER: COMMERCIAL QUALITY WOOD FILLER SPECIFICALLY
MANUFACTURED TO ADVANCE THE FINAL BUILD AND SMOOTHNESS OF THE INSTALLED
WOOD TRIM SURFACE BY FILLING DENTS, SCRATCHES, MITER JOINTS, AND VOIDS
ABOVE COUNTERSUNK FASTENER HEADS. THE SELECTED FILLER SHALL BE EITHER
NEUTRAL OR TINTED TO MATCH THE COLOR OF THE WOOD TRIM.
h. PLYWOOD FASTENERS: PROVIDE MINIMUM #6 GAGE DIAMETER, PHILLIPS FLAT HEAD,
SHARP POINTED, COARSE THREADED, STEEL WOOD SCREW FASTENERS IN QUANTITY AS
REQUIRED. FURNISH PLYWOOD FASTENERS IN LENGTH AS REQUIRED TO SPAN THROUGH
WOOD MIRROR TRIM, AND MIRROR CHANNELS, PLUS 3/4"
i.
WOOD MIRROR TRIM
EXAMINATION
a. EXAMINE SUBSTRATES, OVER WHICH MIRRORS ARE TO BE MOUNTED, WITH INSTALLER
PRESENT, FOR COMPLIANCE WITH INSTALLATION TOLERANCES, SUBSTRATE
PREPARATION, AND OTHER CONDITIONS AFFECTING PERFORMANCE.
(1) VERIFY COMPATIBILITY AND SUITABILITY OF SUBSTRATES, INCLUDING
COMPATIBILITY OF MIRROR MASTIC WITH EXISTING FINISHES OR PRIMERS.
PROCEED WITH MIRRORED GLASS INSTALLATION ONLY AFTER UNSATISFACTORY
CONDITIONS HAVE BEEN CORRECTED AND SURFACES ARE DRY.
PREPARATION
a. COMPLY WITH MASTIC MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS FOR
PREPARATION OF SUBSTRATES.
(1) MIRROR, DRYWALL AND PLYWOOD SUBSTRATES SHALL BE FREE OF DUST, BE
CLEAN, AND DRY PRIOR TO APPLICATION OF MIRROR MASTIC AND DRYWALL AND
PLYWOOD PAINT. IF PLYWOOD OR DRYWALL SURFACES HAVE BEEN PAINTED PRIOR
TO APPLICATION OF THE SPECIFIED DRYWALL AND PLYWOOD PAINT THE EXISTING
PAINT SHALL BE SANDED THROUGH THE ORIGINAL SURFACE AND THE SUBSTRATE
CLEANED PRIOR TO THE APPLICATION OF DRYWALL AND PLYWOOD PAINT.
:
GENERAL: INSTALL MIRRORS WITH MIRROR GLAZING CHANNELS TO COMPLY WITH WRITTEN
INSTRUCTION OF MIRROR AND MIRROR GLAZING CHANNEL MANUFACTURERS, WITH
REFERENCED GANA AND NGA PUBLICATIONS, OWNER FURNISHED DRAWINGS, AND AS
SPECIFIED. MOUNT MIRRORS PLUMB, IN LINE AND IN A MANNER THAT AVOIDS DISTORTING
REFLECTED IMAGES
MIRROR CHANNEL INSTALLATION:
a. TO PLYWOOD: DRILL, DO NOT DIMPLE, BACK LIP OF CHANNEL TO RECEIVE FASTENERS
WITH HOLES PROPERLY SIZED AND SPACED TO RECEIVE FASTENERS. ATTACH MIRROR
CHANNELS BY SCREW ATTACHING MIRROR CHANNEL THROUGH THE BACK LIP OF THE
CHANNEL TO PLYWOOD SUBSTRATE IN ACCORDANCE WITH THE FASTENER
MANUFACTURERS WRITTEN INSTRUCTIONS. INSTALL THE WEB OF THE TOP CHANNEL 1/4"
HIGHER THAN THE HEIGHT OF THE MIRROR TO ALLOW THE RAISING OF THE MIRROR IN
TO THE TOP CHANNEL AND ITS SUBSEQUENT LOWERING INTO THE BOTTOM CHANNEL.
AFTER INSTALLING FASTENERS PLACE MASKING TAPE OVER THE ENTIRE LENGTH OF THE
BACK LIP OF THE CHANNEL COMPLETELY COVERING THE FASTENER HEADS TO PROTECT
THE MIRROR FROM BEING CHIPPED IN SETTING. ADHERE SETTING BLOCKS AT QUARTER
POINTS FOR BOTTOM MIRROR CHANNELS USING ONLY 2 SETTING BLOCKS PER MIRROR
PANEL.
b. TO DRYWALL: MARK THE LOCATIONS FOR THE STUD FASTENERS ON THE BACK LIP OF
EACH MIRROR CHANNEL AT EQUAL INTERVALS NOT OVER 8" ON CENTER, AND NOT
MORE THAN 3" FROM ENDS PRIOR TO DRILLING THE CHANNEL. DRILL AND COUNTERSINK,
DO NOT DIMPLE BACK LIP OF CHANNEL TO RECEIVE STUD FASTENERS AT MARKED
LOCATIONS WITH HOLES PROPERLY SIZED TO RECEIVE STUD FASTENERS. ATTACH
MIRROR CHANNELS BY SCREW ATTACHING MIRROR CHANNEL THROUGH THE BACK LIP
OF THE CHANNEL THROUGH DRYWALL, STUD FRAMING AND SHEET METAL BACKER PLATE
SUBSTRATES IN ACCORDANCE WITH THE FASTENERS MANUFACTURERS WRITTEN
INSTRUCTIONS.
(1) INSTALL THE WEB OF THE TOP CHANNEL 1/4" HIGHER THAN THE HEIGHT OF THE
MIRROR TO ALLOW THE RAISING OF THE MIRROR INTO THE TOP CHANNEL AND ITS
SUBSEQUENT LOWERING ONTO THE WEB OF THE BOTTOM CHANNEL. AFTER
INSTALLING FASTENERS PLACE MASKING TAPE OVER THE ENTIRE LENGTH OF THE
BACK LIP OF THE CHANNEL COMPLETELY COVERING THE FASTENER HEADS TO
PROTECT THE MIRROR FROM BEING CHIPPED IN SETTING. ADHERE SETTING BLOCKS
TO THE WEB OF THE BOTTOM MIRROR CHANNELS, LOCATED AT QUARTER POINTS,
USING 2 SETTING BLOCKS PER MIRROR PANEL.
WOOD TRIM & INSTALLATION
a. BEFORE INSTALLING MIRROR WOOD TRIM, EXAMINE SHOP-FABRICATED WORK FOR
COMPLETION AND COMPLETE WORK AS REQUIRED. PRIME TO ALL EXPOSED SURFACES
OF THE MIRROR WOOD TRIM WHICH WILL BE IN CONTACT WITH THE MIRROR BACKING
TO ELIMINATE INTERACTIONS BETWEEN THE RESINS IN THE WOOD AND THE MIRROR
BACKING.
b. INSTALL MIRROR WOOD TRIM PLUMB, LEVEL, TRUE AND STRAIGHT WITH NO
DISTORTIONS. SCRIBE AND CUT MIRROR WOOD TRIM TO FIT ADJOINING WORK, AND
REFINSH CUT SURFACES AND REPAIR DAMAGED FINISH AT CUTS. INSTALL WITH
MINIMUM NUMBER OF JOINTS POSSIBLE, USING FULL-LENGTH PIECES (FROM MAXIMUM
LENGTH OF WOOD TRIM AVAILABLE) TO GREATEST EXTENT POSSIBLE. DO NOT USE
PIECES LESS THAN 16" LONG, EXCEPT WHERE SHORTER SINGLE-LENGTH PIECES ARE
NECESSARY. SCARF RUNNING JOINTS. MITERS OVER 4" LONG SHALL BE SPLINED AND
GLUED.
PROTECTION AND CLEANING
a. PROTECT MIRRORS FROM BREAKAGE AND CONTAMINATING SUBSTANCES
RESULTING FROM CONSTRUCTION OPERATIONS. USING CLEAN WARM WATER,
CLEAN MIRRORS BY METHODS RECOMMENDED IN REFERENCED GLAZING
STANDARDS.
A Subsidiary of the Luxottica Group
4000 Luxottica Place
Mason, Ohio 45040
CONSULTANT PROJECT # 150343
Shremshock Architects, Inc.
7400 W. Campus Rd. Suite 150 New Albany, OH 43054
t: 614 545 4550 | f: 614 545 4555 | shremshock.com
Gerald S. Shremshock, Architect
Timothy J. Shremshock, Architect
SEAL
(2)
A.
4.5 X 118.932 = 8.3
64.5
TOTAL HOURS
OVERALL WIDTH (FACE OF GYPSUM BOARD ON DEMISING WALL TO FACE OF GYPSUM BOARD
ON DEMISING WALL).
OVERALL LENGTH (LEASE LINE TO INNER-FACE OF GYPSUM BOARD ON REAR WALL.)
ANY AND ALL COLUMN LOCATIONS - FREE STANDING OR PROJECTING.
AVAILABLE CLEAR HEIGHT FOR GRILLE AND CEILING AS DIMENSIONED ON DRAWINGS.
8
NUMERIC EXAMPLE W/ A 4.5 GAIN IN 64.5 HRS.
(ALWAYS ROUND TO THE NEAREST TENTH):
WEIGHT GAIN X 118.932 = POUNDS
TOTAL HOURS
A.
7
LA PLAZA MALL
A.
2
AT
1
SUNGLASS HUT
LA PLAZA MALL
2200 S. 10TH STREET
McALLEN, TX 78503
SPACE #Q14-C
2.0 TYPE: PREMIUM
SGH STORE #: 6078
DRAWN BY: ALW
REVIEWED BY: MLH/JMA
AUTHORIZED FOR:
ARCHITECTURAL
SPECIFICATIONS
A-701
11
12
13
14
3
E.
:
1.
GENERAL: INSTALL OWNER SUPPLIED EXTRUDED ALUMINUM STOREFRONT AND ENTRANCE
SYSTEM WITH DOORS, FRAMES, HARDWARE, AND ACCESSORIES AS REQUIRED FOR COMPLETE
WEATHERTIGHT INSTALLATION.
STANDARDS: COMPLY WITH ARCHITECTURAL ALUMINUM MANUFACTURERS
ASSOCIATION (AAMA) "ALUMINUM STORE FRONT AND ENTRANCE MANUAL."
CODES AND REGULATIONS: COMPLY WITH APPLICABLE CODES AND REGULATIONS.
SUBMITTALS: NOT REQUIRED.
INSTALLATION WARRANTY
MANUFACTURER: OLD CASTLE OR EQUAL , AS APPROVED BY OWNER.
STOREFRONT: EXTRUDED ALUMINUM ENTRANCE SYSTEM AS INDICATED ON DRAWINGS.
a. ALUMINUM TYPE: AS RECOMMENDED BY MANUFACTURER FOR APPLICATION INDICATED,
BUT NOT LESS THAN EXTRUDED ALUMINUM, ASTM B221, 6061 OR 6063 ALLOY AND T5
OR T6 TEMPER.
FINISH: SEE DRAWINGS
GLAZING: ASTM C1048, PROVIDE FULLY TEMPERED SELECT GLAZING QUALITY CLEAR FLOAT
GLASS; NOMINAL 1/2" SAFETY GLASS UNLESS OTHERWISE INDICATED.
a. APPLIED GLAZING FILM: SUPPLY & APPLY 3M FILM ON ALUMINUM FRAMED STOREFRONT
GLASS WHERE INDICATED ON DRAWINGS.
GLAZING ACCESSORIES: OF TYPE RECOMMENDED BY MANUFACTURER TO SUIT SECURITY
LOCATIONS AND APPLICATIONS FOR DRY GLAZING INSTALLATION.
MISCELLANEOUS MATERIALS:
a. STEEL REINFORCEMENT AND BRACKETS: MANUFACTURER'S STANDARD WITH MINIMUM 2
OZ. HOT-DIP ZINC COATING, ASTM A123, APPLIED AFTER FABRICATION.
b. BITUMINOUS PAINT: COLD-APPLIED MASTIC, SSPC PAINT 12, COMPOUNDED FOR 30 MIL
THICKNESS PER COAT.
c. FLASHING: INSTALL SUB-SILL FLASHING MEMBERS; MINIMUM 22 GAGE SHEET ALUMINUM
OF SIZES AND SHAPES INDICATED AND AS REQUIRED TO DRAIN WATER TO EXTERIOR;
MATCH ADJACENT ALUMINUM MEMBER FINISH.
d. ANCHORING DEVICES: CORROSION RESISTANT TYPE CAPABLE OF SUPPORTING ENTRANCE
SYSTEM AND SUPERIMPOSED DESIGN LOADS; DESIGN TO ALLOW ADJUSTMENTS OF
SYSTEM PRIOR TO BEING PERMANENTLY FASTENED IN PLACE.
FABRICATION:
a. ACCURATELY FIT TOGETHER JOINTS AND CORNERS; MATCH COMPONENTS ENSURING
CONTINUITY OF LINE AND DESIGN; ENSURE JOINTS AND CONNECTIONS ARE FLUSH, 1/64th
INCH MAX. AND WEATHERPROOF. NO CAULK AT ANY JOINTS OR CONNECTIONS. NO
EXCEPTIONS!
b. SEPARATE DISSIMILAR MATERIALS WITH BITUMINOUS PAINT OR PREFORMED SEPARATORS
WHICH WILL PREVENT CORROSION.
INSTALLATION: INSTALL ALUMINUM FRAMED STOREFRONT ASSEMBLIES, INCLUDING ENTRANCES,
IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS AND TO MEET DESIGN
REQUIREMENTS INDICATED, FOR WEATHERTIGHT INSTALLATION.
a. ENSURE ASSEMBLIES ARE PLUMB, LEVEL AND FREE OF WARP OR TWIST; MAINTAIN
DIMENSIONAL TOLERANCES AND ALIGNMENT WITH ADJACENT WORK.
b. USE SUFFICIENT ANCHORAGE DEVICES TO SECURELY AND RIGIDLY FASTEN ASSEMBLIES
TO BUILDING.
c. INSTALL HARDWARE IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS, USING
PROPER TEMPLATES. COORDINATE INSTALLATION OF CYLINDERS WITH SECTION 08700.
d. INSTALL SILL MEMBERS AND THRESHOLDS IN BED OF COMPOUND, JOINT FILLERS OR
GASKETS TO PROVIDE WEATHERTIGHT CONSTRUCTION.
e. GLASS INSTALLATION: COMPLY WITH GANA GLAZING MANUAL AND GLAZING
MANUFACTURER INSTRUCTIONS. DO NOT ALLOW GLASS TO TOUCH METAL SURFACES.
2.
3.
4.
5.
6.
7.
8.
9.
J
10.
11.
H
12.
13.
G
4
E.
1.
2.
LAYOUT: A-702
D
3.
4.
USER: JGRAY
PLOTTED: 7/16/2015 - 4:03 PM
P:\SGH\150343 SGH-La Plaza Mall Mcallen, TX\A-701_06078.dwg
5.
6.
7.
C
B
A
:
CERAMIC TILE AS SPECIFIED IN FINISH SCHEDULE AND RESPONSIBILITY SCHEDULE. (IF
APPLICABLE)
INSTALL CERAMIC TILE USING RECOMMENDED METHODS OF THE TILE CONTRACTORS
ASSOCIATION OF AMERICA AND THE TILE COUNCIL OF AMERICA, INC.
INSTALL CERAMIC TILE USING GROUT AND JOINT SPACING SPECIFIED IN FINISH SCHEDULE.
ADHESIVE IS TO BE PROVIDED AND INSTALLED BY GENERAL CONTRACTOR (PER
MANUFACTURER'S SPECIFICATIONS).
CAREFULLY CLEAN ALL WORK AND REPLACE OR REPOINT ANY DAMAGED WORK AND LEAVE IN
PERFECT CONDITION. USE NO ACID, AGENT OR DEVICE THAT WILL MAR SURFACE. CONSULT
WITH OWNER'S CONSTRUCTION MANAGER FOR INSTRUCTIONS (DO NOT POLISH CERAMIC TILE).
CERAMIC TILES ARE TO BE SET WITHOUT TRIPPING HAZARD TO CUSTOMERS OR STAFF.
THE GENERAL CONTRACTOR IS RESPONSIBLE TO CORRECT RAISED CERAMIC TILES FOR THE
ENTIRE DURATION OF THE WARRANTY PERIOD AT THE DIRECTION OF THE OWNER'S
CONSTRUCTION MANAGER.
C.
:
1. FURNISH AND INSTALL CEILING SYSTEM COMPLETE WITH SUSPENSION SYSTEM AND RELATED
ACCESSORIES AS SHOWN ON DRAWINGS AND AS SPECIFIED.
2. SUSPENSION SYSTEMS SHALL BE ADEQUATE TO SUPPORT LIGHT FIXTURES, CEILING, GRILLES,
DIFFUSERS AND OTHER NORMAL ACCESSORIES. PROVIDE SYSTEM COMPONENTS FROM A
SINGLE MANUFACTURER.
3. INSTALL CEILING AND SUSPENSION SYSTEMS IN STRICT ACCORDANCE WITH ASTM C754, ASTM
C635 AND ASTM C636. FINISH CEILING SHALL BE LEVEL, WITH JOINTS SNUG AND SQUARE,
AND TILES OR PANELS IN PERFECT CONDITION.
4. MATERIALS AND FINISHES a. REFER TO DRAWINGS FOR LOCATION OF SPECIFIED MATERIALS
AND FINISHES WHEN APPLICABLE.
b. NON-SALES CEILING: AS SCHEDULED OR EQUAL. CLASS "A" RATING.
c. WHEN A ONE-HOUR FIRE-RATED CEILING ASSEMBLY IS REQUIRED BY LANDLORD, STATE
OR LOCAL CODES, THEN GENERAL CONTRACTOR IS TO CONFORM WITH UNDERWRITER'S
LABORATORIES DESIGN FOR A ONE-HOUR RATED ASSEMBLY AS SCHEDULED.
d. G.C. TO PROVIDE ONE BOX OF THE SPECIFIED CEILING TILES ON SITE FOR FUTURE USE.
5. SEISMIC ZONES: PROVIDE TO COMPLY WITH STATE AND LOCAL REQUIREMENTS FOR SEISMIC
BRACING OF CEILING SUSPENSION SYSTEM, WITH ASTM E580 AND AS DETAILED ON
DRAWINGS. COMPLY ALSO WITH AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE 7-02) AND
CEILING AND INTERIOR SYSTEMS CONSTRUCTION ASSOCIATION (CISCA) STANDARDS. CONSULT
LOCAL CODES FOR MINIMUM CEILING AREA REQUIREMENTS.
D.
1.
2.
:
GENERAL: G.C. TO INSTALL OWNER SUPPLIED VINYL FLOORING SYSTEM WITH ACCESSORIES AS
REQUIRED FOR COMPLETE FINISHED INSTALLATION.
PROJECT CONDITIONS: PRIOR TO INSTALLATION OF ANY FLOORING, GC MUST ENSURE THAT
THE JOBSITE AND SUB-FLOOR MEET THE REQUIREMENTS OF THE FOLLOWING INSTRUCTION.
a. G.C. TO PERFORM MOISTURE TEST ON ALL CONCRETE FLOORS AS DIRECTED BY NWFA
AND INSTALL BOSTIK MVP4 VAPOR BARRIER. MOISTURE CONTENT OF WOOD SUB-FLOOR
MUST NOT EXCEED 12% AND CONCRETE MOISTURE CONTENT MUST NOT EXCEED 3LBS.
b.
G.C. TO PROVIDE MOISTURE TEST REPORT TO CONSTRUCTION MANAGER
1
2
3
:
SEE FINISH SCHEDULE. BUTT BASE TO FLOOR AND WALL WITH NO GAPS.
FILL ALL CRACKS, JOINTS, ETC. IN SUB-FLOOR WITH CRACK FILLER APPROVED BY FLOORING
MANUFACTURER. INSTALL ALL MATERIALS WITH WATERPROOF TYPE ADHESIVES AS
RECOMMENDED BY FLOORING MANUFACTURER FOR MATERIALS AND SURFACES INVOLVED.
THIS SPECIFICATION DEFINES THE REQUIREMENTS FOR SURFACE PREPARATION,
COATING SYSTEMS, MINIMUM AND MAXIMUM DRY FILM THICKNESS, SPECIAL
APPLICATION INSTRUCTIONS WHEN NECESSARY AND INSPECTION FOR PAINTING OF
SPECIFIED SUBSTRATES.
2. IF INSTRUCTIONS CONTAINED IN THIS SPECIFICATION, BID DOCUMENTS OR THE
PAINTING SCHEDULE ARE AT VARIANCE WITH THE PAINT MANUFACTURER'S
INSTRUCTIONS OR THE APPLICABLE STANDARDS AND CODES PUBLISHED BY
SSPC OF OSHA, SURFACES SHALL BE PREPARED AND PAINT APPLIED TO MEET
THE HIGHER STANDARD, AS DETERMINED BY THE DESIGN AUTHORITY.
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR REQUESTING PROMPT
CLARIFICATION WHEN INSTRUCTIONS ARE LACKING, CONFLICTS OCCUR IN THE
SPECIFICATION AND/OR PAINT MANUFACTURER'S LITERATURE, OR THE
PROCEDURE SPECIFIED IS NOT CLEARLY UNDERSTOOD. IN THE EVENT, THE
CONTRACTOR FAILS TO RESOLVE THE CONFLICTS, WHICH MAY EXIST, HE SHALL
BE RESPONSIBLE FOR HANDLING THE DISCREPANCIES IN A MANNER AS
PRESCRIBED BY THE DESIGN AUTHORITY AT NO ADDITIONAL COST TO THE
OWNER.
4. ALL PERTINENT SAFETY REGULATIONS, BOTH THE OWNER'S AND
OSHA'S SHALL BE ADHERED TO RIGIDLY. IN ADDITION, ALL SAFETY
PRECAUTIONS NOTED ON THE MANUFACTURER'S PRODUCT DATA
SHEETS AND LABELS SHALL BE OBSERVED FOR BOTH MATERIALS
AND EQUIPMENT.
5. THE APPLICATION SHALL LEAVE NO SAGS, RUNS OR HOLIDAYS. ANY
DAMAGE IN ANY COAT SHALL BE REPAIRED TO CONFORM TO THIS
SPECIFICATION PRIOR TO FINAL INSPECTION.
6. WHERE REQUIRED, IMPERFECTIONS AND HOLES IN SURFACES TO BE
COATED SHALL BE CLEANED AND REPAIRED ACCORDING TO HIGHEST
INDUSTRY STANDARDS AND IN A MANNER APPROVED BY THE DESIGN AUTHORITY.
7. ALL MATERIALS SPECIFIED FROM BENJAMIN MOORE & CO., AND ARE
INTENDED TO ESTABLISH STANDARDS OF QUALITY AND GENERIC TYPES. COATING SUBSTITUTIONS
ARE PROHIBITED.
8. ALL COATING MATERIALS SHALL BE DELIVERED TO OTHER JOB SITE IN
THE ORIGINAL AND UNOPENED CONTAINERS, PLAINLY MARKED WITH
THE PROPER DESIGNATION OF THE PRODUCT, AS WELL AS THE
NAME OF THE MANUFACTURER. ALL COATING MATERIALS AT THE
JOB SITE SHALL BE SUBJECT TO INSPECTION BY THE OWNER'S REP.
9. ALL PAINTING MATERIALS SHALL BE STORED IN A CLEAN, DRY WELL VENTILATED PLACE,
PROTECTED FROM SPARKS, FLAME, DIRECT RAYS OF THE SUN, AND EXCESSIVE HEAT OR COLD.
THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR THE PROTECTION AND SAFETY OF THE
MATERIALS STORED BY G.C. AT THE JOB SITE.
10. PAINT ADDITIVES ARE PROHIBITED.
11. COLORS FOR INDIVIDUAL ITEMS SHALL BE AS SPECIFIED IN THE
FINISH PAINTING SCHEDULE, OF THIS SPECIFICATION AND/OR THE
PAINTING SCHEDULE SUBMITTED AS A PART OF THE SCOPE OF
WORK DOCUMENTS WITH THE SCOPE OF WORK SCHEDULE TAKING
PRECEDENCE. COLORS SHALL NOT BE SUBSTITUTED.
12. SURFACES NOT TO BE PAINTED SHALL BE PROTECTED DURING CLEANING & PAINTING
OPERATIONS.
13. BEFORE ANY SURFACE IS COATED, IT SHALL BE CLEANED CAREFULLY OF
ALL DUST, DIRT, GREASE, LOOSE RUST, MILL SCALE, OLD PAINT, ETC.
14. ALL CLEANED METAL SHALL BE PRIME COATED , AS SPECIFIED,
IMMEDIATELY AFTER CLEANING TO PREVENT NEW RUSTING OR
OXIDATION OF CLEANED SURFACES.
15. SURFACES
15.1 SURFACE PREPARATION (ALL METAL AND WOOD SURFACES)
a. SOLVENT CLEANING SSPC-SP1 - THIS IS A METHOD FOR REMOVING OIL, GREASE,
DRAWING AND CUTTING FLUIDS FROM THE SURFACE. A COMPLETE DESCRIPTION OF THE
PROCEDURES CAN BE FOUND IN STEEL STRUCTURES PANTING COUNCIL SPECIFICATION
"SSPC-SP-1 SOLVENT CLEANING"
b. EMULSIFIER SOLVENT CLEANING - ALL AREAS TO BE PAINTED SHOULD BE CLEANED
THOROUGHLY WITH A SOLUTION OF OIL AND GREASE EMULSIFIER. THIS CLEANER
EMULSIFIES ALL OF THE OILY SUBSTANCE CONVERTING IT TO SOAP AND FLOATS IF OUT
OF THE SURFACE. THOROUGHLY SCRUB ALL AREAS UNTIL SURFACE APPEARS CLEAN, AND
THE RINSE WELL WITH CLEAN WATER. THIS PROCESS SHOULD BE REPEATED TO ENSURE
THAT THERE ARE NO OTHER OILY CONTAMINANTS REMAINING.
15.2 WALLS AND COLUMNS - EGGSHELL FINISH
a. PRIMER: APPLY ONE (1) COAT OF SUPER SPEC LATEX ENAMEL UNDERCOATER & PRIMER
SEALER (PRODUCT # 253) AT A WET FILM THICKNESS OF 3.6 MILS PER COAT TO ACHIEVE
A DRY FILM THICKNESS OF 1.1 MILS PER COAT. (TINT PRIMER ONE SHADE LIGHTER THAN
FINISH COAT).
b. FINISH: APPLY TWO (2) COATS OF REGAL SELECT PREMIUM INTERIOR PAINT EGGSHELL
FINISH (549) AT A WET FILM THICKNESS OF 3.8 MILS PER COAT TO ACHIEVE A DRY FILM
THICKNESS OF 1.5 MILS PER COAT.
c. APPLICATION: BRUSH SMALL AREAS AND AROUND TRIM AND CEILING WITH PREMIUM
QUALITY NYLON/POLYESTER BRUSH. FIRST COAT MAY BE SPRAYED, BUT BACKROLL WITH
SOFT WOVEN COVER NO LARGER THAN ½” NAP TO MINIMIZE TEXTURE. SECOND COAT
SHALL BE APPLIED BY ROLLER ONLY.
15.3 CEILINGS AND SOFFITS - FLAT FINISH
a. PRIMER: APPLY ONE (1) COAT OF SUPER SPEC LATEX ENAMEL UNDERCOATER & PRIMER
SEALER (PRODUCT # 253) AT A WET FILM THICKNESS OF 3.6 MILS PER COAT TO ACHIEVE
A DRY FILM THICKNESS OF 1.1 MILS PER COAT. (TINT PRIMER ONE SHADE LIGHTER THAN
FINISH COAT).
b. FINISH: APPLY TWO (2) COATS OF REGAL SELECT PREMIUM INTERIOR PAINT FLAT FINISH
(547) AT A WET FILM THICKNESS OF 3.8 MILS PER COAT TO ACHIEVE A DRY FILM
THICKNESS OF 1.4 MILS PER COAT.
c. APPLICATION: BRUSH SMALL AREAS AND AROUND TRIM AND CEILING WITH PREMIUM
QUALITY NYLON/POLYESTER BRUSH. FIRST COAT MAY BE SPRAYED, BUT BACKROLL WITH
SOFT WOVEN COVER NO LARGER THAN ½” NAP TO MINIMIZE TEXTURE. SECOND COAT
SHALL BE APPLIED BY ROLLER ONLY.
15.4 WALL BASE, CASING, AND TRIM - SEMI GLOSS FINISH
a. PRIMER: APPLY ONE (1) COAT OF SUPER SPEC LATEX ENAMEL UNDERCOATER & PRIMER
SEALER (PRODUCT # 253) AT A WET FILM THICKNESS OF 3.6 MILS PER COAT TO ACHIEVE
:
FURNISH AND INSTALL ALL GYPSUM DRYWALL AND SYSTEMS COMPLETE WITH PARTITION
FRAMING, CEILING SUSPENSION SYSTEMS AND RELATED ACCESSORIES, PARTS, MATERIALS,
ETC. AS SHOWN ON DRAWINGS AND AS SPECIFIED. INSTALL ALL MATERIALS PER
MANUFACTURER'S SPECIFICATIONS AND RECOMMENDATIONS.
2. GYPSUM DRYWALL: U.S. GYPSUM 5/8" THICK FIRE CODE SHEETROCK (TYPE 'X') PANELS OF
STANDARD QUALITY. GENERAL CONTRACTOR MAY USE NON-RATED 5/8" THICK BOARD IN
AREAS OF STORE WHERE ALLOWED BY STATE AND LOCAL CODES. ALWAYS USE TYPE 'X' ON
DEMISING WALLS.
3. FASTENERS: DRYWALL SCREWS OF PROPER SIZE AND TYPE, PER MANUFACTURER'S
RECOMMENDATIONS.
4. METAL ACCESSORIES: U.S. GYPSUM OR GOLD BOND SYSTEM OF COMPONENTS AND JOINT
TAPE.
5. JOINT TREATMENT: U.S. GYPSUM OR GOLD BOND SYSTEM OF COMPONENTS AND JOINT TAPE.
6. METAL FRAMING: WHERE NOT SHOWN AND SPECIFIED TO BE COLD-FORMED METAL FRAMING IN
THE DRAWINGS, CONFORM TO ASTM C645 AND ASTM C754.
7. FINISHING: COMPLY WITH GYPSUM ASSOCIATION (GA) "LEVELS OF GYPSUM BOARD FINISH" - GA
LEVEL 4, THREE COAT FINISHING AND SANDING IS REQUIRED FOR SURFACES INDICATED TO BE
PAINTED, PROVIDE FLUSH, SMOOTH JOINTS AND SURFACES READY FOR APPLIED PAINT
FINISHES.
2.
7
F.
1.
A.
1.
B.
1.
6
IMMEDIATELY AFTER DEMOLITION AND/OR 1 WEEK PRIOR TO FLOOR INSTALLATION. IF THE
G.C. FAILS TO PROVIDE REPORT, ANY FLOOR FAILURE ATTRIBUTED TO MOISTURE, IT WILL
BE THE RESPONSIBILITY OF THE G.C. TO REPLACE (LABOR AND MATERIAL).
c. ALL WORK INVOLVING WATER OR MOISTURE SHOULD BE COMPLETED BEFORE FLOOR
INSTALLATION.
d. ROOM TEMPERATURE AND HUMIDITY OF INSTALLATION AREA SHOULD BE CONSISTENT
WITH NORMAL, YEAR-ROUND LIVING CONDITIONS FOR AT LEAST A WEEK BEFORE
INSTALLATION. ROOM TEMPERATURE OF 60 TO 70 DEGREE F AND HUMIDITY RANGE OF
40 TO 60% IS RECOMMENDED.
e. G.C. TO STORE FLOORING AT INSTALLATION SITE FOR 72 HOURS BEFORE INSTALLATION
TO ALLOW FLOORING TO ADJUST TO ROOM TEMPERATURE AND HUMIDITY. DO NOT
STORE DIRECTLY ON CONCRETE OR NEAR OUTSIDE WALLS. THIS FLOORING MAY NOT BE
ACCEPTABLE FOR FULL BATHROOM INSTALLATIONS BECAUSE OF MOISTURE ASSOCIATED
WITH SUCH LOCATIONS.
f. COMMENCEMENT OF WORK IS ACCEPTANCE OF CONDITIONS.
3. MANUFACTURERS: REFER TO FINISH SCHEDULE.
4. ADHESIVE: AS RECOMMENDED BY MANUFACTURER TO ENSURE MAXIMUM DURABILITY OVER
TIME; NONTOXIC, WATERPROOF TYPE SUITABLE FOR FLOORING, SUBSTRATE, AND ACCEPTABLE
TO APPLICABLE AUTHORITIES.
5. MOISTURE VAPOR PROTECTION: BOSTIK MVP4 MOISTURE BARRIER OR AS RECOMMENDED BY
MANUFACTURER; ONE-PART, TROWEL APPLIED, ELASTOMERIC, MOISTURE CURE URETHANE
MEMBRANE. APPLY WITH 3/16" X 5/32" V-NOTCH TROWEL IS RECOMMENDED.
6. VINYL BASE: PROVIDE 1/8" COVED BASE FOR HARD FLOOR SURFACES AND STRAIGHT (TOP SET)
BASE FOR CARPETED AREAS. PROVIDE PRE-MOULDED END STOPS AND EXTERNAL CORNERS.
COLOR, TYPE AND HEIGHT AS SHOWN ON THE DRAWINGS.
F
E
5
4
5
6
7
8
9
10
A DRY FILM THICKNESS OF 1.1 MILS PER COAT. (TINT PRIMER ONE SHADE LIGHTER THAN
FINISH COAT).
b. FINISH: APPLY TWO (2) COATS OF REGAL SELECT PREMIUM INTERIOR PAINT SEMI-GLOSS
FINISH (551) AT A WET FILM THICKNESS OF 3.8 MILS PER COAT TO ACHIEVE A DRY FILM
THICKNESS OF 1.4 MILS PER COAT.
c. APPLICATION: BRUSH APPLY WITH PREMIUM QUALITY NYLON/POLYESTER BRUSH. PRIMER
MAY BE SPRAYED. ALWAYS KEEP A WET EDGE DURING APPLICATION. A MAXIMUM OF ONE
PINT PER GALLON OF CLEAN WATER MAY BE ADDED FOR A DESIRED CONSISTENCY AND
FLOW.
15.5 METAL DOORS AND METAL DOOR JAMBS - SEMI GLOSS FINISH
a. PRIMER: APPLY ONE (1) COAT OF SUPER SPEC HP ACRYLIC METAL PRIMER (P04) AT A WET
FILM THICKNESS OF 4.0-4.5 MILS PER COAT TO ACHIEVE A DRY FILM THICKNESS OF
1.7-2.3 MILS PER COAT. (TINT PRIMER ONE SHADE LIGHTER THAN FINISH COAT).
b. FINISH: APPLY TWO (2) COATS OF REGAL SELECT PREMIUM INTERIOR PAINT SEMI-GLOSS
FINISH (551) AT A WET FILM THICKNESS OF 3.8 MILS PER COAT TO ACHIEVE A DRY FILM
THICKNESS OF 1.4 MILS PER COAT.
c. APPLICATION: FOR JAMBS: BRUSH APPLY WITH PREMIUM QUALITY
NYLON/POLYESTER BRUSH. ALWAYS KEEP A WET EDGE DURING APPLICATION. FOR DOORS,
A SOFT WOVEN COVER OF NO MORE THAN ½” IS RECOMMENDED
FOR A SMOOTH
APPEARANCE. A MAXIMUM OF ONE PINT PER GALLON OF CLEAN WATER MAY BE ADDED
FOR A DESIRED CONSISTENCY AND FLOW.
15.6 CONCRETE FLOOR SEALERS: PROVIDE AS INDICATED ON THE DRAWINGS OR, IF NOT
INDICATED THERE PROVIDE AS FOLLOWS FOR ALL EXPOSED CONCRETE AREAS WITHOUT A
SPECIFIED FINISH
a. INTERIOR CLEAR CONCRETE FLOOR SEALER (WATER-BASED) MP1#58, H&C SILICONE
ACRYLIC CONCRETE SEALER, APPLIED PER MANUFACTURER'S WRITTEN INSTRUCTIONS.
b. EXTERIOR CLEAR CONCRETE SEALER MP1#99, H&C CONCRETE & MASONRY WATER
PROOFING SEALER, APPLIED PER MANUFACTURER'S RECOMMENDATIONS.
15.7 NOTES AND CAUTIONS
a. ENSURE PROPER CONDITIONS FOR APPLICATION - BEFORE ANY SURFACE IS COATED, IT
SHALL BE CLEANED OF ALL DUST, DIRT, GREASE, LOOSE RUST, MILL SCALE, LOOSE PAINT,
ETC. IMPERFECTIONS AND HOLES IS SURFACES TO BE COATED SHALL BE CLEANED AND
FILLED IN AN APPROVED MANNER.
b. ALL PROJECTS SHOULD BE INSPECTED - AT VARIOUS STAGES OF SURFACE PREPARATION
AND COATING APPLICATION. INSPECTIONS SHOULD BE CARRIED OUT BY G.C. INSPECTION
& OWNERS REP. OR BY OUTSIDE INSPECTION FIRMS.
c. CLEAN ANY BOLTS AND PAINT THEM USING A BRUSH - COLORS SHOULD BE DEGREASED
BEFORE PRIMING. THE PRIMER AND TOPCOATS SHOULD BE APPLIED BY BRUSH TO
ACHIEVE COMPLETE AND UNIFORM COVERAGE.
d. MASK FAYING SURFACES AFTER PRIMING - IF FAYING SURFACES ARE TO BE PRIMED, THEY
MUST BE MASKED AFTER PRIMING TO PREVENT TOPCOATING OF THE FAYING SURFACES.
APPLICATION OF THE TOPCOAT TO A FAYING SURFACE MY LEAD TO LOOSENING OF
FRICTION JOINTS.
e. ENSURE ADEQUATE VENTILATION - ADEQUATE VENTILATION WHILE APPLYING AND CURING
COATINGS IS IMPORTANT FOR HEALTH AND SAFETY REASONS AND TO ENSURE PROPER
CURING OF THE COATING. WHEN APPLYING COATINGS IN CONFINED SPACES, SOLVENT
VAPORS MAY ACCUMULATE, LEADING TO INTOXICATION OF WORKERS OR FIRE AND
EXPLOSION. FLAMMABLE SOLVENTS AND THE ATOMIZED COATINGS ARE GENERALLY
HEAVIER THAN AIR AND TEND TO SETTLE IN THE LOWER AREAS OF CONFINED CONSIDER
THIS WHEN DESIGNING AND INSTALLING THE VENTILATION SYSTEM.
f. PAINT BEFORE INSTALLING HARDWARE.
G.
1. GENERAL: INSTALL VINYL WALL COVERING AND PROVIDE ACCESSORIES AS REQUIRED FOR
COMPLETE FINISHED INSTALLATION.
2. MAINTENANCE INSTRUCTIONS: FURNISH MANUFACTURER'S RECOMMENDED CLEANING
MATERIALS AND APPLICATION METHODS, INCLUDING PRECAUTIONS IN USE OF CLEANING
MATERIALS WHICH MAY BE DETRIMENTAL TO SURFACES.
3. MANUFACTURER: AS NOTED ON DRAWINGS.
4. TYPE: VINYL WALL COVERING CONFORMING TO FS DD-G-408, TYPE II VINYL WALL COVERING
WITH CLOTH BACKING, MINIMUM 24 TO 26 OZ.; WITH MAXIMUM 25 FLAME SPREAD AND
SMOKE DEVELOPED, ASTM E84 (UL CLASS A, UBC CLASS I).
5. ADHESIVE: NONTOXIC TYPE RECOMMENDED BY WALL COVERING MANUFACTURER TO SUIT
APPLICATION.
6. PRIMER: PROVIDE NON-STAINING, NON-TOXIC RELEASE COAT PRIMER AS RECOMMENDED BY
WALL COVERING MANUFACTURER.
a. PROVIDE PRIMER WHICH ALLOWS REMOVAL OF WALL COVERING FROM GYPSUM BOARD
WITHOUT DAMAGING PAPER FACING OF BOARD, AND WITHOUT PREMATURE SEPARATION
OF WALL COVERING FROM WALL.
7. EXAMINATION: ENSURE SURFACES TO RECEIVE WALL COVERING ARE CLEAN, TRUE AND FREE OF
IRREGULARITIES, DO NOT COMMENCE WITH WORK UNTIL SURFACES ARE SATISFACTORY.
a. ENSURE WALL SURFACE FLATNESS TOLERANCE DOES NOT VARY MORE THAN 1/8" IN
10'-0", NOR VARY AT A RATE GREATER THAN 1/16" PER RUNNING FOOT.
8. PREPARATION: COMPLY WITH MANUFACTURER'S RECOMMENDATIONS; FILL NICKS, GOUGES AND
OTHER MINOR IMPERFECTIONS OF SUBSTRATES WITH LATEX FILLER; SAND SMOOTH, FLUSH
WITH SURFACE; APPLY PRIME COAT IN ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS.
9. APPLICATION: HANDLE AND APPLY WALL COVERING IN ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS AND INSTALLATION INSTRUCTIONS; MIX AND APPLY ADHESIVE IN
ACCORDANCE WITH ADHESIVE MANUFACTURER'S RECOMMENDATIONS.
a. USE FABRIC PANELS IN EXACT ORDER AS CUT FROM ROLLS; USE ROLLS IN CONSECUTIVE
ORDER AS NUMBERED BY MANUFACTURER.
b. HORIZONTAL SEAMS AND CUTTING AT CORNERS ARE NOT ACCEPTABLE; CUT NO CLOSER
THAN 2" OF AN INSIDE CORNER, AND NOT CLOSER THAN 6" OF AN OUTSIDE CORNER.
c. FILL SPACES ABOVE AND BELOW WINDOWS, DOORS, AND SIMILAR AREAS IN SEQUENCE
FROM ROLL.
11
H.
1.
2.
3.
4.
5.
6.
7.
I.
1.
2.
J.
1.
2.
12
13
14
GENERAL: PROVIDE TOILET ACCESSORIES AS REQUIRED FOR COMPLETE FINISHED
INSTALLATION.
CODES AND REGULATIONS: COMPLY WITH STATE AND FEDERAL REQUIREMENTS FOR ENSURING
ACCESS FOR PERSONS WITH DISABILITIES.
MANUFACTURERS: AS NOTED ON DRAWINGS.
TYPES: STAINLESS STEEL ACCESSORIES AS INDICATED ON DRAWINGS; PROVIDE GRAB BARS
WITH CONCEALED MOUNTING, SIZES AND SHAPES AS INDICATED AND AS REQUIRED BY
APPLICABLE CODES AND REGULATIONS.
MATERIALS: STAINLESS STEEL, ASTM A666, COMMERCIAL GRADE, TYPE 302/304, NUMBER 4
SATIN FINISH, SATIN CHROME ACCEPTABLE WHERE STAINLESS STEEL IS NOT AVAILABLE FOR
ACCESSORY ITEM SCHEDULED; GAGES AS STANDARD WITH MANUFACTURER OF SPECIFIED
ITEMS.
a. FASTENERS, SCREWS, AND BOLTS: HOT DIP GALVANIZED; AS RECOMMENDED BY
ACCESSORY MANUFACTURER FOR COMPONENT AND SUBSTRATE.
b. CONCEALED SURFACES: PRETREAT AND CLEAN, SPRAY APPLY ONE COAT PRIMER AND
BAKED ENAMEL FINISH.
FABRICATION: WELD AND GRIND SMOOTH JOINTS OF FABRICATED COMPONENTS; FORM
EXPOSED SURFACES FROM ONE SHEET OF STOCK, FREE OF JOINTS.
a. FABRICATE UNITS WITH TIGHT SEAMS AND JOINTS, EXPOSED EDGES ROLLED; HANG
DOORS AND ACCESS PANELS WITH CONTINUOUS PIANO HINGES; PROVIDE CONCEALED
ANCHORAGE WHERE POSSIBLE.
b. PROVIDE STEEL ANCHOR PLATES AND ANCHOR COMPONENTS FOR INSTALLATION.
c. FORM SURFACES FLAT WITHOUT DISTORTION; MAINTAIN FLAT SURFACES WITHOUT
SCRATCHES AND WITHOUT DENTS; FINISH EXPOSED EDGES EASED, FREE OF SHARP
EDGES WHERE POTENTIAL EXISTS FOR PHYSICAL CONTACT.
d. HOT DIP GALVANIZE FERROUS METAL ANCHORS AND FASTENING DEVICES.
e. SHOP ASSEMBLE COMPONENTS; PACKAGE COMPLETE WITH ANCHORS AND FITTINGS.
INSTALLATION: COMPLY WITH MANUFACTURER RECOMMENDATIONS AND APPLICABLE CODES
AND REGULATIONS.
9
10
CONSULTANT PROJECT # 150343
Shremshock Architects, Inc.
7400 W. Campus Rd. Suite 150 New Albany, OH 43054
t: 614 545 4550 | f: 614 545 4555 | shremshock.com
Gerald S. Shremshock, Architect
Timothy J. Shremshock, Architect
SEAL
FIRE EXTINGUISHERS, CABINETS, AND ACCESSORIES AS REQUIRED BY APPLICABLE CODE.
a. COMPLY WITH NFPA 10, STANDARD FOR PORTABLE FIRE EXTINGUISHERS.
b. LISTED AND LABELED FOR TYPE, RATING, AND CLASSIFICATION BY AN INDEPENDENT
TESTING AGENCY ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION.
PRODUCTS
a. FIRE EXTINGUISHERS: PORTABLE MULTIPURPOSE DRY-CHEMICAL TYPE, UL RATED 4-A:
60-B:, 10-LB NOMINAL CAPACITY, IN ENAMELED STEEL CONTAINER.
b. FIRE EXTINGUISHER CABINETS: SIZED TO FIT FIRE EXTINGUISHER; APPROVED BY
ARCHITECT.
GENERAL: INSTALL STORAGE SHELVING AS INDICATED ON THE DRAWINGS; PROVIDE
ACCESSORIES AS REQUIRED FOR COMPLETE FINISHED INSTALLATION.
INSTALLATION: COMPLY WITH MANUFACTURER RECOMMENDATIONS AND INSTALLATION
INSTRUCTIONS. INSTALL UNITS AND ACCESSORIES AT LOCATIONS SHOWN IN ACCORDANCE
WITH MANUFACTURER'S RECOMMENDATIONS AND INSTALLATION INSTRUCTIONS, LEVEL, PLUMB,
SECURE AND AT PROPER HEIGHT
K.
1.
PROVIDE SIGNAGE AS INDICATED ON THE DRAWINGS. COMPLY WITH APPLICABLE PROVISIONS IN
ADA-ABA ACCESSIBILITY GUIDELINES AS APPLICABLE
2. ALL COLORS, TYPE, STYLE, FONT SIZE AND MATERIALS TO BE AS SHOWN ON DRAWINGS AND
AS SELECTED AND APPROVED BY OWNER.
3. LOCATE SIGNS WHERE INDICATED, USING MOUNTING METHODS OF TYPES DESCRIBED AND
COMPLYING WITH MANUFACTURER'S WRITTEN INSTRUCTIONS, EXCEPT WHERE MORE STRINGENT
REQUIREMENTS APPLY.
A. GENERAL CONTRACTOR IS RESPONSIBLE FOR ASSEMBLY AND PLACEMENT OF OFFICE AND
NON-SALES EQUIPMENT AND FURNITURE.
B. THE CONTRACTOR IS RESPONSIBLE TO UNCRATE, ASSEMBLE, AND PLACE TRADE FIXTURES AND
PRESENTATION ITEMS IN SALES AREA; FIXTURES TO BE LOCATED PER THE DIRECTION OF THE
OWNER.
A. ACCESS PANEL: FOR GYPSUM BOARD SOFFIT OR WALL (COLOR TO MATCH ADJACENT FINISH):
24" X 24" SURFACE MOUNTED, MODEL #AP24, AS MANUFACTURED BY INTEXFORMS INC. (916)
388-9933 OR OTHER WHICH MUST BE APPROVED BY OWNERS CONSTRUCTION MANAGER.
SUBSTITUTE WITH "B" LABEL FIRE PANEL, MODEL FW 5050, KEY LOCK, ONLY IF A RATED DOOR
IS REQUIRED PER CODES.
B. ACCESS PANELS: FOR HVAC EQUIPMENT ARE NORMALLY INDICATED ON THE HVAC AND
REFLECTED CEILING PLANS. IN ABSENCE OF DEFINED LOCATIONS, THE GENERAL CONTRACTOR
IS TO FURNISH AND INSTALL ACCESS PANELS AS NECESSARY TO FURNISH REASONABLE, SAFE
ACCESS TO SERVICE ALL SERVICEABLE COMPONENTS OF EACH PIECE OF EQUIPMENT.
ASSUMED ACCESS SHALL BE BY A TECHNICIAN(S) STANDING FIRMLY ON A LADDER. WHERE
ACCESS PANELS OR REMOVABLE DIFFUSERS CANNOT BE LOCATED IMMEDIATELY ADJACENT TO
THE EQUIPMENT,
C. THE GENERAL CONTRACTOR IS RESPONSIBLE TO ASSEMBLE ALL MISCELLANEOUS NON-SALES
AREA WALL STANDARDS, SHELVES, BRACKETS, ETC.
D. LAVATORY FIXTURES & ACCESSORIES: REFER TO MECHANICAL DRAWINGS, TOILET ROOM
DETAILS SHEET, AND RESPONSIBILITY SCHEDULE.
E. RESTORE LANDLORD'S STRUCTURAL STEEL FIREPROOFING TO MAINTAIN INTEGRITY OF SAME AND
FIREPROOF NEW STEEL AS REQUIRED.
F. CLEANING: THE G.C. IS RESPONSIBLE FOR 2 PROFESSIONAL CLEANINGS. ONE CLEANING TO BE
PRIOR TO THE PUNCH-LIST DATE. THE SECOND IS TO BE AFTER THE STORE IS MERCHANDISED
BEFORE THE OPENING DATE. STORE IS TO BE TURNED OVER IN A DUST-FREE, DIRT-FREE
CONDITION. CLEANING SHALL INCLUDE, BUT NOT BE LIMITED TO THE FOLLOWING:
1. STOREFRONT GLASS (INSIDE AND OUT)
2. MIRRORS
3. STOREFRONT METAL
4. SIGNS
5. LIGHT FIXTURES INCLUDING CANS, TRIM, TRACK AND TRACK HEADS
6. FLOORING (PER MANUFACTURER'S RECOMMENDATIONS)
7. VINYL RESILIENT FLOOR TILE CLEANED AND WAXED
8. PRESENTATION ITEMS, PROPS, AND TRADE FIXTURES
9. WOOD BASE
10. WALL COVERINGS
11. NON-SALES SHELVING, STORAGE PLATFORMS, ETC.
G.
- GENERAL: G.C. TO COORDINATE AWNING AND FRAME INSTALLATION WITH OWNER'S
PROJECT MANAGER. SUBCONTRACTOR TO PROVIDE BLOCKING AS REQUIRED. COORDINATE
WITH OWNER'S VENDOR.
8
A Subsidiary of the Luxottica Group
4000 Luxottica Place
Mason, Ohio 45040
LA PLAZA MALL
K
2
AT
1
SUNGLASS HUT
LA PLAZA MALL
2200 S. 10TH STREET
McALLEN, TX 78503
SPACE #Q14-C
2.0 TYPE: PREMIUM
SGH STORE #: 6078
DRAWN BY: ALW
REVIEWED BY: MLH/JMA
AUTHORIZED FOR:
ARCHITECTURAL
SPECIFICATIONS
A-702
11
12
13
14
3
4
5
6
HVAC LEGEND
J
INCLINED RISE IN DUCT
12"Ø
ROUND DUCTWORK. DIAMETER IN INCHES.
DROP
INCLINED DROP IN DUCT
20/12
RECTANGULAR DUCTWORK. SIZE IN
INCHES, FIRST NUMBER IS SIDE SHOWN.
TURNING VANES
SUPPLY OR OUTSIDE AIR DUCT
POINT OF CONNECTION - NEW TO
EXISTING
RETURN , RELIEF OR EXHAUST AIR DUCT.
MANUAL VOLUME DAMPER
DIFFUSER/GRILLE LABEL:
A - TYPE/DESIGNATION
B - NECK SIZE (INCHES)
C - AIRFLOW (CFM)
FIRE DAMPER
THERMOSTAT
C
T
H
1.
2.
3.
4.
5.
SENSOR
SD
RADIUS DUCTWORK ELBOW - ROUND OR
RECTANGULAR.
RECTANGULAR DUCTWORK BRANCH
TAKE-OFF WITH 45 DEGREE BRANCH
INLET.
CARBON DIOXIDE SENSOR
6.
DUCT SMOKE DETECTOR
7.
SHEET KEYNOTE REFERENCE
8.
9.
10.
ROUND
Ø
UC
UNDERCUT DOOR 3/4" FOR AIRFLOW
11.
ACCESS PANEL
HIGH EFFICIENCY TAP WITH DAMPER AND
FLEX DUCT (AT DIFFUSER CONNECTION).
SWITCH
S
ROUND DUCT BRANCH TAKE-OFF FROM
RECTANGULAR MAIN WITH CONICAL TAP.
RECESSED MOUNTED SPRINKLER HEAD
DUCTWORK SIZE TRANSITION.
EXISTING RETURN/SUPPLY CALL OUT
12.
13.
OPEN CEILING UPRIGHT SPRINKLER HEAD
(E)X X
XXX
SPIN-IN W/ DAMPER
X
SUPPLY OR OUTSIDE AIR DUCT UP
SUPPLY OR OUTSIDE AIR DUCT DOWN
X
XXX
X
RETURN AIR DUCT UP
14.
15.
16.
17.
DIFFUSER CALL OUT
NECK AND BRANCH DUCT SIZE
CFM FOR BALANCE PURPOSES
RETURN CALL OUT
NECK AND BRANCH DUCT SIZE
CFM FOR BALANCE PURPOSES
SPIN-IN W/O DAMPER
G
11
X
XXX
18.
19.
20.
21.
22.
23.
F
24.
-
-
E
(E)RTU 2
25.
ADJACENT
TENANT (N.I.C.)
(E) SUPPLY & RETURN TRUNKS
26.
4
27.
USER: JGRAY
PLOTTED: 7/16/2015 - 4:03 PM
3
D
29.
14/12
3
(E) INSULATED ROOF DRAIN
@ +/- 14'-11 1/2" A.F.F.
S1 12
500
33.
(E) ELECTRICAL CONDUIT
RACK @ +/- 15'-0" A.F.F.
S
AP
(E) ROOF DRAIN LEADS DOWN
THROUGH ROOF DECK
C
PIPES ENTER WALL @ +/5 14'-0" A.F.F.
35.
36.
37.
38.
MALL
COMMON AREA
100
POSSIBLE VENT STACK LEADS
THROUGH ROOF. BOTTOM OF
PIPE ENTERS REAR DEMISING
WALL @ +/- 12'-0" A.F.F.
34.
5
TC
SALES
(TYP) 6
5
30.
31.
32.
5
-
ADJACENT
TENANT (N.I.C.)
5
28.
S
12/14
P:\SGH\150343 SGH-La Plaza Mall Mcallen, TX\M-101_06078.dwg
LAYOUT: M-101 - RTU
14
900
12
13
14
GENERAL NOTES
HUMIDISTAT
90 DEGREE DUCTWORK ELBOW W/
TURNING VANES.
H
10
GENERAL CONTRACTOR SHALL RELOCATE EXISTING THERMOSTAT TO LOCATION AS SHOWN ON PLAN. EXTEND CONTROL WIRING FROM
THERMOSTAT TO HVAC UNIT AS REQUIRED. CLEAN AND ADJUST AS REQUIRED FOR PROPER OPERATION. REPAIR/REPLACE ANY DEFECTIVE PARTS
AND MAKE SYSTEM FULLY FUNCTIONAL. FIELD VERIFY EXACT LOCATION AND REQUIREMENTS PRIOR TO BID.
2.
: GENERAL CONTRACTOR TO REUSE EXISTING ROOF TOP UNIT. PROVIDE 3 SETS OF 2" FILTERS, CHANGE FILTER AFTER FINAL STORE
CLEANING AND AGAIN PRIOR TO AIR BALANCE. CLEAN COILS, REBALANCE FAN AND REPLACE BELTS, REPLACE/REPAIR ANY DEFECTIVE PARTS.
GREASE (IF REQUIRED) FAN BEARINGS. CHECK CONTROLS FOR PROPER OPERATION AND MOTOR FOR PROPER FAN PERFORMANCE. CLEAN AND/OR
REPLACE CONDENSATE LINE AS REQUIRED. FIELD VERIFY EXACT LOCATION AND REQUIREMENTS. VERIFY OUTSIDE AIR DAMPER IS IN GOOD
WORKING ORDER PRIOR TO CONSTRUCTION. BALANCE SUPPLY AND OUTSIDE AIR DAMPER TO CFM SPECIFIED.
3. GENERAL CONTRACTOR TO FURNISH AND INSTALL AIR DEVICES PER SCHEDULE ON SHEET M-301. EXTEND DUCTWORK TO AIR DEVICE AS SHOWN.
SEAL ALL JOINTS AIRTIGHT. BALANCE TO CFM AS INDICATED ON PLAN. R EFER TO DUCT MOUNTING DETAIL ON SHEET M-501.
4. CONNECT TO EXISTING SUPPLY AND RETURN AIR DUCT DROPS. CLEAN AND REPAIR EXISTING DUCTWORK AS REQUIRED TO ENSURE PROPER
OPERATION. PATCH AND REPAIR ANY UNUSED OPENING. PATCH AND REPAIR INSULATION IF REQUIRED. TRANSITION TO DUCT SIZE SHOWN.
5. EXISTING UTILITIES TO REMAIN. FIELD VERIFY EXISTING SIZE AND LOCATION.
6. SPRINKLER HEADS SHOWN FOR REFERENCE ONLY. LICENSED FIRE PROTECTION PROFESSIONAL TO DETERMINE ACTUAL AMOUNT AND LOCATION OF
HEADS. ALIGN SPRINKLER HEAD LOCATIONS WITH LIGHTS AND OTHER CEILING ELEMENTS. COORDINATE WITH LANDLORD AND TENANT.
IN-LINE 90 DEGREE DROP (RISE) IN DUCT
RISE
B
9
1.
RETURN AIR DUCT DOWN
RETURN AIR GRILLE
A
8
KEY NOTES
SUPPLY AIR DIFFUSER - HATCHED
PATTERN INDICATES BLOCKED
DIRECTIONAL AIR FLOW AS SHOWN.
K
7
ALL WORK MUST COMPLY WITH THE REQUIREMENTS OF LOCAL CODES AND ORDINANCES. WHERE INSPECTIONS
ARE REQUIRED BY AUTHORITIES HAVING JURISDICTION, WORK MUST NOT BE CONCEALED UNTIL INSPECTIONS AND
TESTING ARE COMPLETED AND ACCEPTED.
PRIOR TO BID, CONTRACTOR MUST BECOME THOROUGHLY FAMILIAR WITH THE REQUIREMENTS OF THE GENERAL
NOTES AS WELL AS ALL OTHER NOTES SHOWN ON THE CONTRACT DOCUMENTS. VISIT THE SITE TO ESTABLISH THE
EXISTING CONDITIONS PRIOR TO BID AND PRIOR TO ANY DUCT, PIPE OR EQUIPMENT FABRICATION. SYSTEMS MUST
BE ERECTED USING CONTRACTOR'S FIELD MEASUREMENTS FOR COORDINATION WITH EQUIPMENT, STRUCTURE,
FIRE PROTECTION AND ELECTRICAL CONDITIONS IN THE SPACE.
ALL CONTRACT DOCUMENTS ARE DIAGRAMMATIC AND INDICATE THE GENERAL ARRANGEMENTS OR GEOMETRICAL
RELATIONSHIPS OF EQUIPMENT AND SERVICES. THEY ARE NOT INTENDED TO SPECIFY OR SHOW EVERY OFFSET,
SEQUENCE, DEVICE, OPTION, FITTING, OR COMPONENT.
THE CONTRACT DOCUMENTS REFLECT A SYSTEM DESIGNED AROUND SPECIFIC REFERENCE PRODUCTS, THE
SELECTION OF WHICH HAS IMPACTED THE DESIGNS OF OTHER TRADES. IF ALTERNATE MANUFACTURERS ARE
SUBMITTED OR BID, IT IS THE RESPONSIBILITY OF THIS CONTRACTOR TO COORDINATE ALL DIFFERENCES AND
IMPACTS WITH ALL TRADES PRIOR TO BID, INCLUDING COSTS ASSOCIATED WITH REQUIRED CHANGES TO OTHER
TRADES. NO EXTRAS WILL BE ALLOWED FOR CHANGES REQUIRED TO OTHER TRADES IF ALTERNATE EQUIPMENT IS
BID OR INSTALLED AT THE CONTRACTOR'S OPTION.
EXISTING MECHANICAL INFORMATION IS BASED ON LIMITED EXISTING BUILDING DRAWINGS AND FIELD WORK. THE
CONTRACTOR SHALL FIELD VERIFY THE EXISTING CONDITIONS FOR ACCURACY. NO ADDITIONAL COMPENSATION
SHALL BE ALLOWED FOR REVISIONS TO THE DESIGN TO CORRECT FOR EXISTING CONDITIONS NOT AS INDICATED
ON THE PLANS.
CONTRACTOR SHALL NOTIFY OWNER, ARCHITECT AND ENGINEER OF ANY SITUATIONS THAT MODIFY OR INCREASE
THE SCOPE OF WORK FROM THAT IS DESCRIBED IN THE DOCUMENTS.
FIELD VERIFY EXACT CONDITIONS AND ROUTING OF WORK. CONTACT THE ENGINEER OR ARCHITECT IMMEDIATELY
SHOULD ANY CONFLICT ARISE.
CONTRACTOR TO VERIFY EXISTING CONDITIONS AND COORDINATE CONFLICTS PRIOR TO BIDDING.
ANYTHING NOT NOTED AS EXISTING IS TO BE FURNISHED AND INSTALLED AS PART OF THIS PROJECT.
INFORMATION AND COMPONENTS SHOWN ON DIAGRAMS OR DETAILS, BUT NOT SHOWN ON PLANS, AND VICE
VERSA, MUST BE PROVIDED AS IF EXPRESSLY REQUIRED BY BOTH.
REFER TO DRAWINGS, GENERAL NOTES OF OTHER DISCIPLINES, AND PROJECT SPECIFICATIONS FOR ADDITIONAL
PROJECT INFORMATION AND REQUIREMENTS. NOTIFY ENGINEER OF ANY CONFLICTS BETWEEN THE INFORMATION
PRESENTED AND FIELD CONDITIONS.
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING/PATCHING RELATED TO THEIR WORK.
IF THE SPACE ABOVE CEILING IS INDICATED TO BE A RETURN AIR PLENUM. CONSTRUCTION MATERIALS ABOVE
CEILING SHALL BE NONCOMBUSTIBLE, OR HAVE A MAXIMUM 25 FLAME SPREAD AND 50 SMOKE DEVELOPMENT
FINISH RATING. WIRING SHALL BE LABELED PLENUM RATED TYPE PER NFPA 70.
COORDINATE LOCATION AND ELEVATION OF MECHANICAL WORK WITH ALL DUCTWORK, LIGHT FIXTURES, AND
OTHER CEILING BUILT-IN FIXTURES. CONTACT ENGINEER OR ARCHITECT IMMEDIATELY SHOULD ANY CONFLICT ARISE.
REFER TO MALL CRITERIA MANUAL FOR ADDITIONAL STANDARDS AND REQUIREMENTS.
COORDINATE ALL THERMOSTAT/SENSOR LOCATIONS WITH FURNITURE LAYOUT AND ARCHITECTURAL PLANS.
CHANGES IN DUCT SIZES SHALL BE MADE BY UNIFORM TAPER SECTION WITH A MAXIMUM INCLUDED ANGLE OF
DIVERGENCE OF 15 DEGREE.
DUCT SIZE DIMENSIONS INDICATED REPRESENT INTERNAL FREE AREA. INCLUDE ADDITIONAL ALLOWANCE FOR
INSULATION.
ALL SUPPLY, AND MAKE-UP AIR DUCTWORK TO BE SHEET METAL CONSTRUCTION AND EXTERNALLY INSULATED.
BRANCH DUCTS SERVING DIFFUSERS SHALL BE SIZED TO MATCH DIFFUSER NECK SIZE INDICATED.
ALL ROUND DUCT ELBOWS SHALL BE LONG SWEEP, 1-1/2 TIMES THE CENTERLINE RADIUS.
IT IS THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR TO VISIT THE JOB SITE TO FAMILIARIZE THEMSELVES
WITH MAJOR ITEMS SUCH AS STRUCTURAL ELEMENTS, PLUMBING LOCATIONS, ELECTRICAL RUNS AND POINTS OF
CONNECTION TO EXISTING DUCT SYSTEMS. ADDITIONALLY, MECHANICAL CONTRACTOR SHALL VERIFY EXACT
LOCATIONS AND DIMENSIONS OF SUCH ITEMS AS HVAC EQUIPMENT, DUCTWORK, ETC. PRIOR TO COMMENCING
ANY WORK.
IT IS THE CONTRACTOR'S RESPONSIBILITY TO ENSURE THAT THE MECHANICAL EQUIPMENT COMPONENTS ARE
INSTALLED AT LOCATIONS AND ELEVATIONS WHICH MAKE THEM READILY ACCESSIBLE FOR ROUTINE MAINTENANCE
WITHOUT REQUIRING ANY EXTRAORDINARY MEASURES.
THE OWNER RESERVES THE RIGHT TO CHECK CONSTRUCTION COMPLIANCE WITH PLANS AND SPECIFICATIONS.
SHOULD THE OWNER FIND CORRECTIVE WORK NECESSARY, HE WILL NOTIFY CONTRACTOR OF SUCH WORK IN
WRITING AND EXPECT COMPLIANCE PERFORMED WITH DUE DILIGENCE. IF ANY CORRECTIVE WORK IS DEEMED TO
BE NECESSARY, THE COST OF REINSPECTIONS WILL BE BORNE BY THE CONTRACTOR. IF WORK IS REQUIRED BY
OWNER IN ORDER TO IMPROVE, CHANGE OR CORRECT AIR CONDITIONING OPERATIONAL CONDITIONS DUE TO:
PART MALFUNCTION, WARRANTY OR OTHER INABILITY TO PROVIDE THE COMFORT CONDITIONS REQUIRED BY THE
STORE, CONTRACTOR SHALL BE DIRECTED BY TENANT TO ADDRESS THIS WORK IN A TIMELY MANNER. IF IT
BECOMES EVIDENT THAT THE CONTRACTOR CAN NOT ACCOMPLISH THE TASK, THEN AFTER 72 HOURS OF WRITTEN
NOTICE, THE OWNER MAY AT HIS DISCRETION TAKE OVER SUCH WORK AND BACK CHARGE THE CONTRACTOR FOR
ANY CORRECTIVE WORK THAT WAS REQUIRED DUE TO LACK OF PERFORMANCE, WORKMANSHIP AND/OR
ADHERENCE TO PLANS AND SPECIFICATIONS.
FIRE DAMPERS SHALL BE FURNISHED WITH INTERLOCKING HINGED BLADES. ALL DAMPERS SHALL BE UL APPROVED
AND LABELED AND SHALL MEET ALL REQUIREMENTS OF NFPA NO 90A. FURNISH WITH UL LABELED FUSIBLE LINKS
WITH TEMPERATURE RANGES TO CONFORM TO NFPA REQUIREMENTS.
ALL FIRE DAMPERS SHALL BE TYPE "B" WITH BLADES OUT OF THE AIRSTREAM AND RATED FOR USE IN DYNAMIC
SYSTEMS.
ALL ROOF PENETRATIONS, PATCHING AND FLASHING SHALL BE PERFORMED BY A LANDLORD APPROVED ROOFING
CONTRACTOR AT THIS CONTRACTOR'S EXPENSE. COORDINATE ROOF PENETRATIONS AND ROOFTOP EQUIPMENT
LOCATIONS WITH LANDLORD AND GENERAL CONTRACTOR.
NOTHING IS PERMITTED TO BE ATTACHED TO, SUSPENDED FROM, OR PENETRATE THE ROOF DECK. CONTRACTOR
MAY ATTACH TO OR SUSPEND FROM THE TOP CHORD OF THE JOIST OR THE STRUCTURAL STEEL WHICH EXISTS
ABOVE THE TENANT SPACE.
COORDINATE FINAL ROOFTOP UNIT LOCATIONS WITH LANDLORDS STRUCTURAL ENGINEER. ROOFTOP UNITS AND
MAKE-UP AIR UNIT TO BE LOCATED WITHIN STRUCTURAL BAY. PROVIDE 10' CLEARANCE FROM UNIT OUTSIDE AIR
INTAKE TO ANY EXHAUST/VENTS ON ROOF.
ALL ROOFTOP UNITS TO BE LOCATED ON FACTORY SUPPLIED ROOF CURBS. UNLESS NOTED OTHERWISE.
PROVIDE AND INSTALL ALL ROOFTOP UNIT EQUIPMENT WITH SPRING ISOLATORS ON ROOF CURB.
GENERAL CONTRACTOR TO LABEL ALL ROOFTOP EQUIPMENT WITH TENANT NAME, SPACE NUMBER AND EQUIPMENT
IDENTIFICATION (RTU-1, ETC.), PER MALL SPECIFICATIONS AND STANDARDS.
PITCH POCKETS ARE NOT PERMITTED ON THE ROOF FOR CONDENSATE DRAINS, POWER OR CONTROL WIRING. ALL
CONNECTIONS ARE TO BE MADE INSIDE THE EQUIPMENT CURB OR THROUGH PRE-MANUFACTURED PIPING CURB.
PROVIDE SAFE MEANS OF ACCESS HATCHES (24"x24") FOR ALL MECHANICAL EQUIPMENT LOCATED ABOVE A HARD
CEILING. COORDINATE W/ ARCHITECTURAL CEILING PLANS.
CONTRACTOR MUST REPLACE ALL AIR FILTERS IN HVAC UNITS WITH NEW CLEAN FILTERS BEFORE AIR BALANCING
AND PRIOR TO FINAL TURNOVER TO TENANT.
PROVIDE AND INSTALL ADJUSTABLE VOLUME CONTROL DEVICE FOR EACH SUPPLY AND DUCTED RETURN DIFFUSER
AND REGISTER.
ALL ROOFTOP UNIT CONNECTIONS (SUPPLY AND RETURN) TO BE WITH FLEXIBLE CONNECTORS.
REFER TO RESPONSIBILITY SCHEDULE ON SHEET G-002.
S1 12
500
T
(E) 8" DIAMETER SPRINKLER
MAIN @ 14'-0" A.F.F.
3
SEAL
SUNGLASS HUT
LA PLAZA MALL
2200 S. 10TH STREET
McALLEN, TX 78503
SPACE #Q14-C
2.0 TYPE: PREMIUM
-
STOCK ROOM
101
SGH STORE #: 6078
5
ADJACENT
TENANT (N.I.C.)
DRAWN BY: CH
(E) SPRINKLER PIPE
@ +/- 14'-0" A.F.F.
REVIEWED BY: JTP
AUTHORIZED FOR:
A
MECHANICAL PLAN
& LEGEND
PLAN NORTH
A1
M-101
MECHANICAL PLAN
2
Shremshock Engineering, Inc.
7400 W. Campus Rd. Suite 150 New Albany, OH 43054
t: 614 545 4550 | f: 614 545 4555 | shremshock.com
TX Registration Number: #F-9566
5
FE
B
1
CONSULTANT PROJECT # 150343
1
S
SCALE:
A Subsidiary of the Luxottica Group
4000 Luxottica Place
Mason, Ohio 45040
LA PLAZA MALL
2
AT
1
3
4
5
6
7
8
9
10
11
12
13
14
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A Subsidiary of the Luxottica Group
4000 Luxottica Place
Mason, Ohio 45040
THERMOSTAT SCHEDULE
K
MODE
HEAT
SPRINKLER SYSTEM NOTES
UNOCCUPIED
OCCUPIED
68F
60F
COOL
80F
73F
OCCUPIED MODE:
MONDAY-SATURDAY
8:00a.m.-9:00p.m.
SUNDAY
11:00a.m.-6:15p.m.
J
H
TAG
SERVICE
MOUNTING
MFR
S1
SUPPLY AIR
LAY-IN
TITUS
TMS
24" X 24"
R1
RETURN
AIR
LAY-IN
TITUS
355RL
24" X 24"
MODULE SIZE
FINISH
SEAL
DESIGN STANDARDS:
HARD CEILING AREA AT STOREFRONT: WHITE CONCEALED HEADS; RELIABLE MODEL 'G-4'; TYCO
'RF-11'
CEILING TILE AT RETAIL, OD, AND LENS PROCESS: RECESSED CHROME HEADS WITH WHITE TRIM
RINGS; RELIABLE MODEL "G-F1'; TYCO 'TY-L'
CEILING TILE AT LOUNGE, OFFICE, AND BACK OF HOUSE: CHROME HEADS WITH CHROME TRIM
RINGS; RELIABLE MODEL "G"; 'TY-L'
NOTES
STD. WHITE
FINISH
STD. WHITE
FINISH
Shremshock Engineering, Inc.
7400 W. Campus Rd. Suite 150 New Albany, OH 43054
t: 614 545 4550 | f: 614 545 4555 | shremshock.com
TX Registration Number: #F-9566
FOR EXISTING FIRE SPRINKLER SYSTEM:
CONTRACTOR SHALL REWORK AND MODIFY THE SYSTEM IF NECESSARY FOR THE NEW SPACE
CONFIGURATION. MODIFICATIONS SHALL BE DESIGNED AND INSTALLED BY A QUALIFIED FIRE
SPRINKLER CONTRACTOR, WHO SHALL PREPARE DESIGN/SHOP DRAWINGS OF THE SYSTEM AND
SUBMIT SUCH DRAWINGS TO THE LANDLORD AND BUILDING AND FIRE DEPARTMENTS FOR
APPROVAL PRIOR TO FABRICATION AND INSTALLATION. ALL WORK SHALL BE DONE IN
ACCORDANCE WITH NFPA, STANDARD 101, AND ANY OTHER STATE OR LOCAL CODES HAVING
JURISDICTION.
GRILLE, REGISTER AND DIFFUSER SCHEDULE
MODEL
No.
CONSULTANT PROJECT # 150343
FOR NEW FIRE SPRINKLER SYSTEM:
CONTRACTOR SHALL PROVIDE A COMPLETE FIRE PROTECTION SPRINKLER SYSTEM FOR THE ENTIRE
SPACE IN COMPLIANCE WITH ALL APPLICABLE CODES AND REGULATIONS AND THE LANDLORD'S
CRITERIA. THE CONTRACTOR SHALL HAVE DRAWINGS, SHOP DRAWINGS, APPLICATIONS AND
SUBMITTALS PREPARED BY A PROPERLY LICENSED PROFESSIONAL, WHO IS APPROVED BY THE
LANDLORD. ALL DRAWINGS AND CONSTRUCTION SHALL BE IN COMPLIANCE WITH ALL CODES,
REGULATIONS, INSURANCE ASSOCIATIONS AND RATING BUREAUS AND SHALL INCLUDE ALL
PERMITS, TESTS, SHUT DOWN FEES AND CERTIFICATIONS TO PROVIDE A COMPLETE IN PLACE
SYSTEM.
2
2
1. OPPOSED BLADE DAMPER
G
2. LAY IN FRAME FOR T-BAR CEILING
3. PROVIDE WITH RAPID MOUNT FRAME FOR DRY WALL CEILING
4. MOUNT HIGH ON WALL ABOVE CEILING TO PROVIDE TRANSFER AIR INTO SALES PLENUM
G11
SCALE:
SPRINKLER SYSTEM NOTES
EXISTING ROOFTOP HVAC UNIT SCHEDULE
TAG
MFR
MODEL
No.
NOMINAL
TONS
SEER
MIN OA
(CFM)
3
15
150
E
USER: JGRAY
PLOTTED: 7/16/2015 - 4:03 PM
P:\SGH\150343 SGH-La Plaza Mall Mcallen, TX\M-301_06078.dwg
LAYOUT: M-301 RTU
(E)RTU
CARRIER 50HCA04
COOLING DATA
ELECTRIC HEAT DATA
INPUT
(KW)
OUTPUT
(MBH)
VOLTAGE
(V/ɸ/Hz)
UNIT
MCA
UNIT
MOCP
6.5
-
208/3/60
30
30
SUPPLY
AIR
(CFM)
ESP (IN
WC)
MOTOR
(HP)
EAT
DB/WB
LAT
DB/WB
TOTAL
(MBH)
1000
0.8
0.6
75/67
-
35.5
SENSIBLE COOLING HEATING
(MBH)
STAGES STAGES
20.0
1
-
UNIT CHARACTERISTICS
AT
SUPPLY FAN DATA
NOTES/
OPERATING ACCESSORIES
WEIGHT (LBS)
-
-
LA PLAZA MALL
F
D
C
SUNGLASS HUT
LA PLAZA MALL
OUTSIDE AIR SCHEDULE
SPACE DESIGNATION
FLOOR AREA
(SF)
SPACE OUTSIDE AIR REQUIREMENTS
(ASHRAE 62.1)
OCCUPANCY
B
SALES FLOOR
464
8
CFM PER CFM PER
PERSON
SF
7.5
SERVICE
OUTSIDE AIR
(CFM)
(E)RTU
150
MINIMUM
CFM
145
0.12
MINIMUM OUTSIDE AIR
DELIVERED = 150 CFM
MINIMUM OUTSIDE AIR REQUIRED = 145
2200 S. 10TH STREET
McALLEN, TX 78503
SPACE #Q14-C
2.0 TYPE: PREMIUM
SGH STORE #: 6078
DRAWN BY: CHC
REVIEWED BY: JTP
AUTHORIZED FOR:
MECHANICAL SCHEDULES
A
A1
SCALE:
MECHANICAL SCHEDULES
1
2
A11
SCALE:
3
4
5
6
7
8
9
10
HVAC CALCULATIONS
11
12
M-301
13
14
1
2
3
4
5
6
7
8
9
10
11
12
13
14
ABBREVIATIONS
ABOVE
AIR CONDITIONER, AIR
CONDITIONING, ABOVE CEILING
AFF
ABOVE FINISHED FLOOR
ARCH
ARCHITECT, ARCHITECTURAL
ARI
AIR CONDITIONING & REFRIG
INSTITUTE
ASHRAE AMERICAN SOCIETY OF HEATING,
REFRIGERATION & AC ENGINEERS
K
J
H
G
B/F
BAS
BD
BLDG
BMS
BOD
BOP
BOS
BTU
BELOW FLOOR
BUILDING AUTOMATION SYSTEM
BACKDRAFT DAMPER
BUILDING
BUILDING MANAGEMENT SYSTEM
BOTTOM OF DUCT
BOTTOM OF PIPE
BOTTOM OF STRUCTURE
BRITISH THERMAL UNIT
CFH
CFM
CL
CLG
CO
CONN
COP
CW
°C
CUBIC FEET PER HOUR
CUBIC FEET PER MINUTE
CENTERLINE
CEILING
CLEANOUT
CONNECT, CONNECTION
CLEANOUT PLUG
COLD WATER
DEGREES CELSIUS
DB
dB
DDC
DEG
DIA (Ø)
DIM
DISC
DN
DWG
DX
DRY BULB
DECIBEL
DIRECT DIGITAL CONTROL
DEGREES
DIAMETER
DIMENSION
DISCONNECT
DOWN
DRAWING
DIRECT EXPANSION
EAT
EC
EDB
ELEV
ELEC
ESP
ETR
EWB
EWC
EWT
EXH
EX
ENTERING AIR TEMPERATURE
ELECTRICAL CONTRACTOR (DIV 15)
ENTERING DRY BULB
ELEVATION
ELECTRICAL
EXTERNAL STATIC PRESSURE
EXISTING TO REMAIN
ENTERING WET BULB
ELECTRICAL WATER COOLER
ENTERING WATER TEMPERATURE
EXHAUST
EXIST EXISTING
FA
FACP
FCO
FLA
FLEX
FP
FPM
FT
°F
FIRE ALARM
FIRE ALARM CONTROL PANEL
FLOOR CLEANOUT
FULL LOAD AMPS
FLEXIBLE
FIRE PROTECTION
FEET PER MINUTE
FOOT, FEET
DEGREES FAHRENHEIT
G
GA
GAL
GC
GFI
GPM
GRND
GAS
GAUGE
GALLON
GENERAL CONTRACTOR
GFIC GROUND FAULT INTERRUPTER
GALLONS PER MINUTE
GROUND
H
HORIZ
HP
HTG
HTR
HVAC
HW
HEIGHT
HORIZONTAL
HORSEPOWER, HEAT PUMP
HEATING
HEATER
HEATING, VENTILATING & A/C
HOT WATER
ID
IE
INSIDE DIAMETER
INVERT ELEVATION
KVA
KW
KWH
INCH, INCHES
WC INCHES OF WATER COLUMN
O/H
OA
OBD
OC
OD
KILOVOLT-AMPS
KILOWATTS
KILOWATT-HOUR
OSHA
L
LAT
LBS, #
LDB
LF
LP
LRA
LTG
LWB
LWT
INTERNALLY LINED
LEAVING AIR TEMPERATURE
POUNDS
LEAVING DRY BULB
LINEAR FEET
LOW PRESSURE
LOCKED ROTOR AMPS
LIGHTING
LEAVING WET BULB
LEAVING WATER TEMPERATURE
MAX
MBTU
MBH
MC
MAXIMUM
1000 BTU PER HOUR
1000 BTU PER HOUR
MECHANICAL CONTRACTOR (DIV
15)
MINIMUM CIRCUIT AMPACITY
MAIN CIRCUIT BREAKER
MOTORIZED DAMPER
MECHANICAL
MANUFACTURER
MINIMUM
MAXIMUM OVER CURRENT
PROTECTION
MEDIUM PRESSURE
MOUNTED
MAKE-UP AIR
MCA
MCB
MD
MECH
MFR
MIN
MOCP
MP
MTD
MUA
N/A
NEC
NEMA
NFPA
NIC
NTS
NOT APPLICABLE
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL MFR'S
ASSOC.
NATIONAL FIRE PROTECTION
ASSOC.
NOT IN CONTRACT
NOT TO SCALE
OVERHEAD
OUTSIDE AIR (VENTILATION AIR)
OPPOSED BLADE DAMPER
ON CENTER
OVERFLOW DRAINAGE, OUTSIDE
DIAMETER
OCCUPATIONAL SAFETY &HEALTH
ADMIN.
PD
PF
PH
PLBG
PNL
PSI
PRV
PVC
PRESSURE DROP
POWER FACTOR
PHASE
PLUMBING
PANEL
POUNDS PER SQUARE INCH
PRESSURE RELIEF VALVE
POLYVINYL CHLORIDE
RA
RCP
RD
RE:
RECIRC
REL
REQD
REV
REX
RH
RLA
RPM
RWC
RETURN AIR
REFLECTED CEILING PLAN,
ROOF DRAIN
REFERENCE, REFER TO
RECIRCULATE
RELOCATED
REQUIRED
REVISION, REVISE
REMOVE EXISTING
RELATIVE HUMIDITY
RUNNING LOAD AMPS
REVOLUTIONS PER MINUTE
RAIN WATER CONDUCTOR
SA
SAN
SD
SF
SMACNA
SUPPLY AIR
SANITARY
SMOKE DETECTOR
SQUARE FEET, SQUARE FOOT
SHEET METAL & A/C CONT NAT'L
ASSOC.
STATIC PRESSURE
SPECIFICATION
STANDARD
SP
SPEC
STD
TE
THRU
TP
TSP
TSTAT
TYP
TENANT EXHAUST (TOILET)
THROUGH
TOTAL PRESSURE
TOTAL STATIC PRESSURE
THERMOSTAT
TYPICAL
CONSULTANT PROJECT # 150343
U/F
U/G
U/S
UL
UON
UNDERFLOOR
UNDERGROUND
UNDERSLAB
UNDERWRITERS LABORATORIES,
INC.
UNLESS OTHERWISE NOTED
V
VA
VAV
VD
VERT
VTR
VOLT, VENT
VOLT-AMPERE, VALVE
VARIABLE AIR VOLUME
VOLUME DAMPER
VERTICAL
VENT THROUGH ROOF
W
W/
W/O
WB
WC
WATT, WIDTH
WITH
WITHOUT
WET BULB
WATER COLUMN
RECTANGULAR
DUCTWORK
F
A Subsidiary of the Luxottica Group
4000 Luxottica Place
Mason, Ohio 45040
Shremshock Engineering, Inc.
7400 W. Campus Rd. Suite 150 New Albany, OH 43054
t: 614 545 4550 | f: 614 545 4555 | shremshock.com
TX Registration Number: #F-9566
SEAL
ROUND
DUCTWORK
2" MINIMUM
COLLAR
RECTANGULAR
DUCTWORK
ROUND
DUCTWORK
E
AT
45° LATERAL FITTING
RECTANGULAR TO ROUND
"BUCKLEY FITTING"
LAYOUT: M-501 SPLIT
BRANCH DUCT HEIGHT
DIMENSION 2" LESS THAN
MAIN DUCT HEIGHT DIMENSION
D
D7
NOT USED
D11
SCALE:
C
DUCT BRANCH TAKE-OFF DETAIL
MAX. 12" TO
BRANCH
CONNECTION
VANES PRE-ASSEMBLED ON RUNNER PLATES (TYP.)
GALVANIZED SHEET
METAL DUCT
USE GALVANIZED VANES FOR GALVANIZED OR
ALUMINUM DUCTS (TYP.)
GALVANIZED ELBOW
PLATE SAME GAUGE AS DUCT (TYP.)
9"
P:\SGH\150343 SGH-La Plaza Mall Mcallen, TX\M-501_06078.dwg
PLOTTED: 7/16/2015 - 4:03 PM
RECTANGULAR TO
RETANGULAR
90° COMBINATION TEE WITH OVAL
TO ROUND TAP (IF BRANCH FLOW
IS 2/3 OF THRU FLOW)
SCALE:
USER: JGRAY
LA PLAZA MALL
ABV
A/C
IN
IN
METAL STRAP CLAMP
(TYPICAL) 2 PLACES
SUNGLASS HUT
LA PLAZA MALL
INSULATED FLEXIBLE
CONNECTION. (MAX. 5'-0")
IN VERTICAL ONLY. IF GRILL
IS TO BE USED AS LIFT
OUT GRILL, MIN. 3'-0".
VOLUME DAMPER
B
3-1/4"
1-1/2"
DUCT SIZE OVER 36"x36".
SQUARE ELBOW WITH TYPE "A"
DOUBLE THICKNESS VANES.
LOCATE DAMPER IN HARD
CEILING APPLICATIONS TO BE
ACCESSIBLE FROM FACE OF
DIFFUSER
DUCT SIZE 36"x36" OR UNDER.
2200 S. 10TH STREET
McALLEN, TX 78503
SPACE #Q14-C
2.0 TYPE: PREMIUM
SGH STORE #: 6078
SUPPLY AIR DIFFUSER
INSULATION WITH FOIL FACING
DRAWN BY: CHC
REVIEWED BY: JTP
SQUARE ELBOW WITH SINGLE
THICKNESS VANES.
AUTHORIZED FOR:
MECHANICAL DETAILS &
ABBREVIATIONS
A
A1
SCALE:
NOT USED
1
A7
SCALE:
2
3
4
5
6
TURNING VANE DETAIL
7
8
A11
SCALE:
9
10
DUCT MOUNTING DETAIL
11
12
M-501
13
14
1
2
3
4
5
6
7
8
9
10
11
12
13
14
O. CEILING GRID SYSTEMS SHALL NOT BE USED TO SUPPORT FIRE PROTECTION ITEMS, PIPING, OR ANY
E. WHERE POSSIBLE, REWORK THE EXISTING SPRINKLER SYSTEM TO MEET THE NEW REQUIREMENTS OF
OTHER EQUIPMENT. EACH UTILITY AND THE CEILING GRID SYSTEM SHALL BE A SEPARATE INSTALLATION
THIS DESIGN.
A. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL A FIRE
AND EACH SHALL BE INDEPENDENTLY SUPPORTED FROM THE BUILDING STRUCTURE. WHERE
F. PROVIDE AND INSTALL A VALVED TEST CONNECTION IN AN ACCESSIBLE LOCATION FOR THE SPRINKLER
PROTECTION SYSTEM, COMPLETE AS INDICATED ON THE DRAWINGS AND AS REQUIRED BY CODE AND
INTERFERENCE OCCURS, IN ORDER TO SUPPORT EQUIPMENT OR CEILING GRID SYSTEM, CONTRACTOR
SYSTEM AS REQUIRED OR REQUESTED BY THE LANDLORD, LOCAL INSPECTOR, OR INSURANCE
AS SPECIFIED HEREIN.
MUST INSTALL TRAPEZE TYPE HANGERS OR SUPPORTS WHICH SHALL NOT BE LOCATED WHERE THEY
CARRIER.
INTERFERE WITH ACCESS TO FIRE DAMPERS, VALVES, LIGHT FIXTURES, AND OTHER MECHANICAL OR
B. THE GENERAL CONTRACTOR, UNLESS OTHERWISE NOTED IS TO PROVIDE POWER WIRING FOR EACH
G. CONTRACTOR SHALL BE RESPONSIBLE FOR DAMAGE CAUSED BY LEAKS IN ANY OF THE EQUIPMENT
ELECTRICAL ITEMS.
ITEM OF ELECTRICAL EQUIPMENT AND MAKE FINAL CONNECTIONS TO MOTORS.
INSTALLED. ALL REPAIRS OR REPLACEMENT OF DAMAGES SHALL BE BY THIS CONTRACTOR AT THIS
P. INSTALL ALL SPRINKLER HEADS IN ROOMS IN AN ESTHETIC MANNER. SPRINKLER ARRANGEMENT SHALL
C. ALL FINISH PAINTING IS TO BE PERFORMED BY THE GENERAL CONTRACTOR, EXCEPT AS NOTED
CONTRACTOR'S EXPENSE.
BE PARALLEL AND PERPENDICULAR TO THE BUILDING WALLS. COORDINATE WITH ARCHITECT AND
ELSEWHERE. GENERAL CONTRACTOR, AT THIS CONTRACTOR'S EXPENSE, SHALL RESTORE TO ORIGINAL
H. PROPERLY COMPLETED AND SIGNED "SPRINKLER CONTRACTOR'S MATERIAL AND TEST CERTIFICATES"
TENANT.
CONDITION ANY PAINTING DEFACED DURING CONSTRUCTION AND AFTER ORIGINAL PAINTING.
SHALL BE FURNISHED TO THE LANDLORD, AND AUTHORITIES HAVING JURISDICTION.
Q. CONTRACTOR SHALL VERIFY THE LOCATION OF UTILITIES AND NOTE CONDITIONS WHICH WOULD
D. ALL WORK SHALL CONFORM TO CODES, RULES, AND REGULATIONS:
AFFECT THE WORK. ALL DISCREPANCIES SHALL THEN BE REPORTED TO THE LANDLORD'S TENANT
21 05 30 SPRINKLER PIPING SPECIALTIES
1.
NATIONAL ELECTRIC CODE.
COORDINATOR PRIOR TO THE BID AWARD.
21 05 00 FIRE PROTECTION GENERAL PROVISIONS
J
H
3.
CODE FOR SAFETY TO LIFE FROM FIRE IN BUILDINGS AND STRUCTURES, NFPA 101.
4.
FEDERAL OCCUPATIONAL SAFETY AND HEALTH STANDARDS.
5.
STATE MECHANICAL CODE.
6.
STATE BUILDING CODE
7.
STATE INDUSTRIAL COMMISSION REQUIREMENTS.
8.
LOCAL BUILDING CODE REQUIREMENTS.
9.
BUILDING INSURING AGENCY REQUIREMENTS.
10.
STATE PLUMBING CODE.
11.
NFPA.
E.
ALL PERMITS REQUIRED BY LAWS, ORDINANCES AND BUILDING CODES HAVING JURISDICTION SHALL
BE OBTAINED AT THE PROPER TIME BY AND AT THE EXPENSE OF THIS CONTRACTOR.
F.
CONTRACTOR SHALL OBTAIN ALL INSPECTIONS REQUIRED BY ALL LAWS, ORDINANCES AND PUBLIC
AUTHORITY HAVING JURISDICTION AND SHALL OBTAIN CERTIFICATES OF SUCH INSPECTIONS AND
SUBMIT SAME TO THE ARCHITECT AND SHALL PAY ALL FEES, CHARGES, ASSESSMENTS AND OTHER
EXPENSES IN CONNECTION THEREWITH.
G.
THE MATERIALS AND EQUIPMENT INSTALLED IN THE WORK SHALL MEET THE REQUIREMENTS OF THE
CONTRACT DOCUMENTS AND NO MATERIALS OR EQUIPMENT SHALL BE ORDERED UNTIL REVIEWED BY
THE ENGINEER, LANDLORD AND/OR ARCHITECT.
H.
G
I.
F
STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND VENTILATING SYSTEMS, NFPA
90A.
R.
S.
CONTRACTOR TO MAINTAIN ONE SET OF DRAWINGS ON THE JOB TO BE USED STRICTLY FOR
RECORDING ANY INSTALLATION DEVIATIONS FROM THE CONTRACT DRAWINGS.
T.
CONTRACTOR IS RESPONSIBLE FOR DAILY CLEAN-UP AND REMOVAL OF FIRE PROTECTION DEBRIS
FROM THE SITE WEEKLY. THE PREMISES SHALL BE KEPT IN A NEAT AND ORDERLY CONDITION.
U.
CONTRACTOR SHALL REVIEW AND FOLLOW ALL LANDLORD REQUIREMENTS. THE SUBMITTING OF A BID
AUTOMATICALLY IMPLIES THAT THESE REQUIREMENTS HAVE BEEN REVIEWED AND ARE IN THE BID
PRICE AND INFORM LANDLORD IN ADVANCE OF ANY DOWN TIME.
V.
ALL SLEEVES AND OPENINGS THROUGH FIRE RATED WALLS AND/OR FLOORS SHALL BE FIRE SEALED
WITH CALCIUM SILICATE, SILICONE "RTV" FOAM, "3M" FIRE RATED SEALANTS OR EQUAL, SO AS TO
RETAIN THEIR FIRE RATING.
A.
PROVIDE INSTRUCTION TO LANDLORD'S OPERATING PERSONNEL AS NECESSARY, SHOWING LOCATIONS
AND PROPER OPERATION OF MAJOR ITEMS OF EQUIPMENT AND SYSTEM COMPONENTS AND
B.
REFERRING TO THE OPERATING INSTRUCTION MANUAL DESCRIBED BELOW AS A GUIDE.
WITHIN 90 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD DRAWINGS OF THE ACTUAL
INSTALLATION SHALL BE PROVIDED TO THE BUILDING LANDLORD. RECORD DRAWINGS SHALL INCLUDE
AS A MINIMUM THE LOCATION AND PERFORMANCE DATA ON EACH PIECE OF EQUIPMENT.
K.
ANY REFERENCE TO TENANT OR TENANT'S CONSTRUCTION MANAGER OR FURNISHED BY ANY OF THE
ABOVE REFERS TO LUXOTTICA GROUP.
L.
REFER TO RESPONSIBILITY SCHEDULE ON SHEET G-002 FOR INFORMATION IN REGARD TO
RESPONSIBILITY OF WORK OR ITEMS WHICH MAY AFFECT BID.
C.
M. DEMOLITION
1.
N.
E
LAYOUT: M-701
P:\SGH\150343 SGH-La Plaza Mall Mcallen, TX\M-701_06078.dwg
PLOTTED: 7/16/2015 - 4:03 PM
USER: JGRAY
D
CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND LABOR PROVIDED UNDER THIS
CONTRACT AND SHALL MAKE GOOD, REPAIR OR REPLACE AT NO ADDITIONAL COST ANY
DEFECTIVE WORK, MATERIAL, OR EQUIPMENT DISCOVERED WITHIN 12 MONTHS FROM THE
DATE OF CERTIFICATE OF OCCUPANCY. THIS GUARANTEE SHALL EXTEND TO LABOR AND
MISCELLANEOUS MATERIALS REQUIRED FOR THE INSTALLATION OF EQUIPMENT. THE
CONTRACTOR IS RESPONSIBLE TO VERIFY, COORDINATE AND FOLLOW ALL PROPER HANDLING
AND INSTALLATION TECHNIQUES WITH MANUFACTURER(S) IN ORDER TO MAINTAIN
MANUFACTURER'S WARRANTY.
C
B
CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING THE EXACT HAZARD CLASSIFICATION, AS
WELL AS, THE QUANTITY, SPACING, AND PROTECTED AREA LIMITATION OF SPRINKLER HEADS.
CONTRACTOR SHALL FURTHER BE RESPONSIBLE FOR CONFIRMING HIS DETERMINATION WITH THE
LANDLORD'S INSURING AGENCY AND THE LOCAL FIRE AUTHORITY HAVING JURISDICTION OVER THE
PROJECT.
2
3
1.
SPRINKLERS (AS REQUIRED)
2.
VALVES (AS REQUIRED)
3.
TAMPER SWITCHES (AS REQUIRED)
4.
WATER FLOW SWITCHES (AS REQUIRED)
5.
HYDRAULIC CALCULATIONS (AS REQUIRED)
6.
CONNECTIONS TO LANDLORD'S FIRE ALARM SYSTEM
WHEN SUBMITTED FOR THE ARCHITECT'S REVIEW, SHOP DRAWINGS SHALL BEAR GENERAL
CONTRACTOR'S CERTIFICATION THAT THEY HAVE REVIEWED, CHECKED AND APPROVED THE SHOP
DRAWINGS, THAT THEY ARE IN HARMONY WITH THE REQUIREMENTS OF THE PROJECT AND WITH THE
PROVISIONS OF THE CONTRACT DOCUMENTS AND THAT THEY HAVE VERIFIED ALL FIELD
MEASUREMENTS AND CONSTRUCTION CRITERIA, MATERIALS, CATALOG NUMBER AND FIELD
MEASUREMENTS AND SIMILAR DATA. CONTRACTOR SHALL ALSO CERTIFY THAT THE WORK
REPRESENTED BY THE SHOP DRAWINGS IS RECOMMENDED BY CONTRACTOR AND THE CONTRACTOR'S
GUARANTEE WILL FULLY APPLY.
ALL CONTRACTORS SUBMITTING PROPOSALS FOR THIS WORK SHALL FIRST EXAMINE THE SITE AND ALL
CONDITIONS THEREIN. ALL PROPOSALS SHALL TAKE INTO CONSIDERATION ALL SUCH CONDITIONS AS
THEY MAY AFFECT THE WORK UNDER THIS CONTRACT. THE SUBMITTING OF A BID AUTOMATICALLY
IMPLIES THAT THIS EXAMINATION OF THE SITE HAS BEEN DONE.
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL TESTING OF SPRINKLER PIPING PER NFPA.
B.
TEST SPRINKLER PIPING WITH A HYDROSTATIC TEST AT 200 PSI FOR 2 HOURS WITH NO VISIBLE
LEAKAGE.
C.
TEST ALARMS, FLOW SWITCHES, AND TAMPERPROOF SWITCHES AND ADJUST AS NECESSARY.
D.
CONTRACTOR AND LANDLORD SHALL SIGN CERTIFICATES, INDICATING WITNESSING OF ALL TESTS
REQUIRED BY NFPA-13 FOR ABOVE GROUND PIPING.
E.
REPAIR ANY LEAKING JOINTS AND REPAIR ANY DAMAGE TO THE FACILITY THAT THE LEAK MAY HAVE
CREATED. CLEAN, PAINT, OR REPLACE ANY DAMAGED COVERINGS AS REQUIRED TO MEET THE
LANDLORD'S APPROVAL.
B.
ALL HANGER ASSEMBLIES SHALL BE UL AND FM APPROVED.
C. HANGER SPACING SHALL MEET NFPA-13 MINIMUM REQUIREMENTS.
21 05 26 INTERIOR PIPE TUBE AND FITTINGS AND SPRINKLER HEADS
A.
SPRINKLER HEADS:
1.
PROVIDE AN NFPA-13 APPROVED AUTOMATIC FIRE SPRINKLER SYSTEM IN BUILDING. SYSTEM SHALL BE
APPROVED BY THE LOCAL AND STATE FIRE MARSHAL'S OFFICE.
ALL SPRINKLER HEADS SHALL BE NEW, QUICK RESPONSE, U.L. LISTED, F.M. LISTED AND
APPROVED AUTOMATIC SPRAY TYPE AS MANUFACTURED BY STAR, RELIABLE,
SIMPLEX-GRINNELL, VIKING, OR CENTRAL SPRINKLER CO.
2.
F.
THE INSTALLING CONTRACTOR SHALL BE LICENSED AND CERTIFIED IN THE INSTALLATION OF
AUTOMATIC SPRINKLER SYSTEMS IN THIS STATE.
ALL SPRINKLER HEADS SHALL BE RATED FOR 165°F UNLESS INDICATED OTHERWISE ON
DRAWINGS OR REQUIRED BY LOCAL CODES.
3.
G.
CONTRACTOR SHALL OBTAIN AND PAY FOR ANY INSPECTION FEES, CHARGES, AND ANY OTHER
GOVERNMENTAL FEES APPLICABLE.
"SALES" AREA SPRINKLER HEADS ARE TO BE FULLY CONCEALED ADJUSTABLE SCREW TYPE WITH
WHITE COVER PLATE TO MATCH CEILING.
4.
H.
CONTRACTOR SHALL FILE ALL NECESSARY DRAWINGS, SPECIFICATIONS, CONTRACTOR'S MATERIAL
AND TEST CERTIFICATES.
"NON-SALES" AREA SPRINKLER HEADS ARE TO BE FULLY CONCEALED ADJUSTABLE SCREW TYPE
WITH WHITE COVER PLATE TO MATCH CEILING.
5.
I.
CONTRACTOR SHALL OBTAIN A CERTIFICATE OF INSPECTION AND APPROVAL AND SUBMIT TO THE
ARCHITECT PRIOR TO THE REQUEST FOR FINAL PAYMENT.
"NON-SALES" NO CEILING SPRINKLER HEADS ARE TO BE CHROME UPRIGHT, ADJUSTABLE
SCREW TYPE.
6.
J.
CONTRACTOR SHALL PROVIDE ALL PRODUCTS AND LABOR REQUIRED TO COMPLETE THE INSTALLATION
B.
OF ALL FIRE PROTECTION SPRINKLER SYSTEMS.
"MALL BULKHEAD" AREA SPRINKLER HEADS ARE TO BE FULLY CONCEALED ADJUSTABLE SCREW
TYPE WITH WHITE COVER PLATE TO MATCH CEILING.
K.
FIRE PROTECTION PIPING AND EQUIPMENT LAYOUT SHALL BE COORDINATED WITH ALL EQUIPMENT,
BOTH KNOWN AND UNKNOWN, AND EQUIPMENT INCLUDED UNDER OTHER DIVISIONS OF THE
SPECIFICATIONS.
L.
ALL FIRE PROTECTION PIPING SHALL BE INSTALLED AS CONCEALED WORK, WHERE APPLICABLE.
D.
WHERE APPLICABLE, LOCATE SPRINKLER HEADS IN CENTER OF CEILING TILE, USE ARMOVER ON ALL
SPRINKLER BRANCH LINES TO ACCOMPLISH EXACT LOCATION OF HEAD.
E.
SCHEDULE 40, BLACK STEEL PIPE, ASTM A-53 FOR FERROUS PIPING, WELDED AND SEAMLESS,
ANSI B-36-10-70 FOR WROUGHT STEEL PIPE.
2.
CAST IRON OR MALLEABLE IRON SCREWED FITTINGS FOR PIPES 2 INCHES AND SMALLER.
SCREWED OR CAST IRON FLANGED JOINTS FOR PIPES LARGER THAN 2 INCHES.
M. THE ARCHITECT RESERVES THE RIGHT TO CHANGE THE LOCATION OF ANY SPRINKLER HEAD DURING
THE SUBMITTAL PROCESS EVEN IF THE MOVE SHOULD REQUIRE ADDITIONAL HEADS.
3.
GALVANIZED OR BLACK MALLEABLE IRON WITH BRASS SEAT SCREWED UNIONS FOR PIPES 2
INCHES AND SMALLER.
N.
4.
VICTAULIC TYPE COUPLINGS ARE ACCEPTABLE, WHERE APPROVED BY CODE AND THE
LANDLORD.
5.
HANGERS SHALL COMPLY WITH LANDLORD AND CODE REQUIREMENTS.
FILL ANNULAR SPACE BETWEEN SLEEVE AND PIPE OR INSULATION ON ALL PENETRATIONS THROUGH
FIRE RATED WALLS. FIRESTOPPING MATERIALS SHALL BE UL CLASSIFIED AND MEET THE REQUIREMENTS
OF ASTM. THE METHOD OF INSULATION SHALL CONFORM TO UL FIRE RESISTANCE DIRECTORY.
4
5
6
7
SUNGLASS HUT
LA PLAZA MALL
2200 S. 10TH STREET
McALLEN, TX 78503
SPACE #Q14-C
2.0 TYPE: PREMIUM
PIPING:
1.
A
1
SEAL
F. NOTIFY THE LANDLORD IN WRITING FOR ANY SCHEDULING OF ANY TESTS OR DOWNTIME OF THE
MODIFY THE EXISTING SPRINKLER SYSTEM AND FURNISH ALL MATERIALS, LABOR, TOOLS,
EXISTING SPRINKLER SYSTEM.
ADMINISTRATION, TRANSPORTATION, INCIDENTALS AND APPURTENANCES WHICH ARE REQUIRED TO
COMPLETE IN EVERY DETAIL AND LEAVE IN WORKING ORDER ALL ITEMS OF WORK CALLED FOR HEREIN 21 05 25 SUPPORTS, ANCHORS, AND SEALS
OR SHOWN ON THE ACCOMPANYING DRAWINGS. CONTRACTOR IS RESPONSIBLE FOR CONNECTING TO
A. UL LISTED HANGERS, BEAM CLAMPS, HANGER RODS, PIPE ATTACHMENTS, AND PIPE SLEEVES SHALL
THE LANDLORD'S FIRE ALARM SYSTEM. COORDINATE WITH LANDLORD'S APPROVED FIRE ALARM AND
BE PER SP-58. EQUAL MANUFACTURERS TO BE SIMPLEX GRINNELL, B-LINE, OR MICHIGAN HANGERS.
SPRINKLER CONTRACTORS.
B. INCLUDE ANY MINOR ITEMS OF WORK NECESSARY TO PROVIDE A COMPLETE AND FULLY OPERATIVE
FIRE PROTECTION SYSTEM.
C.
THIS CONTRACTOR IS TO BECOME INFORMED OF THE EXACT DIMENSIONS OF FINISHED WORK WHERE
PIPES, DUCTS AND EQUIPMENT ARE TO BE PLACED AND WILL ARRANGE THE WORK ACCORDINGLY,
ASSUMING ALL RESPONSIBILITY FOR PROPER LOCATION AND COORDINATION OF THE WORK.
Shremshock Engineering, Inc.
7400 W. Campus Rd. Suite 150 New Albany, OH 43054
t: 614 545 4550 | f: 614 545 4555 | shremshock.com
TX Registration Number: #F-9566
CONTRACTOR SHALL SUBMIT FOR THE ARCHITECT'S AND LANDLORD REVIEW SIX (6) COMPLETE COPIES
OF THE CATALOG DATA AND/OR SHOP DRAWINGS FOR THE LISTED ITEMS OF EQUIPMENT AND ALL
COMPONENTS TO BE USED IN THE WORK, INCLUDING SPECIFIC PERFORMANCE DATA, MATERIAL
DESCRIPTION, RATING, CAPACITY, WORKING PRESSURE, MATERIAL GAUGE OF THICKNESS, BRAND
NAME, CATALOG NUMBER AND GENERAL TYPE. THE SUBMISSION SHALL BE COMPILED BY
CONTRACTOR AND REVIEWED BY ENGINEER BEFORE ANY OF THE EQUIPMENT IS ORDERED.
A.
21 05 13 COMMON WORK RESULTS FOR FIRE SUPPRESSION
A.
B.
PROVIDE ALL NECESSARY DRAINS. COORDINATE THE EXACT LOCATION WITH THE ARCHITECT AND
LANDLORD PRIOR TO ANY INSTALLATION.
CONTRACTOR SHALL BE RESPONSIBLE FOR THE DEMOLITION AND REMOVAL OF EXISTING
WORK. FIELD VERIFY AND COORDINATE ANY EXISTING EQUIPMENT REQUIRED TO BE LEFT INTACT
21 05 19 TESTS
AND PROTECT EQUIPMENT TO REMAIN DURING CONSTRUCTION.
WARRANTY AND GUARANTEE
1.
A.
21 05 16 SHOP DRAWINGS
CATALOG DATA FOR EQUIPMENT REVIEWED BY THE ARCHITECT SHALL NOT SUPERSEDE THE ENGINEER'S
CONTRACT DOCUMENTS. THE REVIEW OF THE ENGINEER SHALL NOT RELIEVE THE CONTRACTOR FROM
RESPONSIBILITY FOR DEVIATIONS FROM DRAWINGS OR SPECIFICATIONS, PROVIDING PROPER
CLEARANCE, FABRICATION PROCESS AND COORDINATION WITH OTHER TRADES.
J.
INSTALLATION WILL NOT BE CONSIDERED COMPLETE UNLESS AND UNTIL WRITTEN ACCEPTANCE IS
RECEIVED FROM THE STATE FIRE MARSHAL AND THE LANDLORD'S INSURING AGENCY.
LA PLAZA MALL
2.
CONSULTANT PROJECT # 150343
AT
K
A Subsidiary of the Luxottica Group
4000 Luxottica Place
Mason, Ohio 45040
C.
SPRINKLER SPACING SHALL NOT EXCEED 130 SQ. FT. IN "SALES" AREAS AND 100 SQ. FT. IN "STOCK"
AREAS. COMPLY WITH LANDLORD'S DESIGN CRITERIA. PIPE SIZING SHALL BE BASED ON NFPA
ORDINARY HAZARD.
D.
ALL SPRINKLER LINES SHALL BE INSTALLED CONCEALED, AVOIDING INTERFERENCE WITH OTHER
TRADES.
8
9
10
SGH STORE #: 6078
DRAWN BY: CHC
REVIEWED BY: JTP
AUTHORIZED FOR:
FIRE PROTECTION SPECIFICATIONS
M-701
11
12
13
14
3
4
5
6
7
K
PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL A
HEATING, VENTILATING, AIR CONDITIONING SYSTEM, COMPLETE AS INDICATED ON THE DRAWINGS,
AS REQUIRED BY CODE AND AS SPECIFIED HEREIN.
B.
THE GENERAL CONTRACTOR, UNLESS OTHERWISE NOTED IS TO PROVIDE POWER WIRING FOR EACH
ITEM OF ELECTRICAL EQUIPMENT AND MAKE FINAL CONNECTIONS TO MOTORS.
C.
ALL FINISH PAINTING IS TO BE PERFORMED BY THE GENERAL CONTRACTOR, EXCEPT AS NOTED
ELSEWHERE. GENERAL CONTRACTOR, AT THIS CONTRACTOR'S EXPENSE, SHALL RESTORE TO
ORIGINAL CONDITION ANY PAINTING DEFACED DURING CONSTRUCTION AND AFTER ORIGINAL
PAINTING.
D.
J
H
ALL WORK SHALL CONFORM TO CODES, RULES, AND REGULATIONS:
1.
NATIONAL ELECTRIC CODE.
2.
STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND VENTILATING SYSTEMS, NFPA
90A.
3.
CODE FOR SAFETY TO LIFE FROM FIRE IN BUILDINGS AND STRUCTURES, NFPA 101.
4.
FEDERAL OCCUPATIONAL SAFETY AND HEALTH STANDARDS.
5.
STATE MECHANICAL CODE.
6.
STATE BUILDING CODE
7.
STATE INDUSTRIAL COMMISSION REQUIREMENTS.
8.
LOCAL BUILDING CODE REQUIREMENTS.
9.
BUILDING INSURING AGENCY REQUIREMENTS.
10.
STATE PLUMBING CODE.
11.
NFPA.
23 05 01 HVAC BASIC MATERIALS AND METHOD
F.
CONTRACTOR SHALL OBTAIN ALL INSPECTIONS REQUIRED BY ALL LAWS, ORDINANCES AND PUBLIC
AUTHORITY HAVING JURISDICTION AND SHALL OBTAIN CERTIFICATES OF SUCH INSPECTIONS AND
SUBMIT SAME TO THE ARCHITECT AND SHALL PAY ALL FEES, CHARGES, ASSESSMENTS AND OTHER
EXPENSES IN CONNECTION THEREWITH.
C.
ALL DUCTWORK SHALL BE PLACED SO AS TO AVOID INTERFERENCE WITH PLUMBING PIPES, ELECTRIC
CONDUITS OR PIPES OF OTHER CONTRACTORS.
D.
ALL DUCTWORK MUST BE PROVIDED WITH SUFFICIENT DISTANCE FROM WALLS, PIPES AND OTHER
OBSTACLES TO PERMIT THE APPLICATION OF FULL THICKNESS OF INSULATION SPECIFIED.
E.
THIS CONTRACTOR SHALL PERFORM AN ACCURATE AND COMPLETE BALANCE OF AIR SYSTEMS AS
PART OF THIS CONTRACT, WHICH SHALL BE COMPLETED BEFORE FINAL ACCEPTANCE OF THE WORK
OF THIS CONTRACT. AIR BALANCE SHALL BE SUBCONTRACTED TO A CERTIFIED MEMBER OF
ASSOCIATED AIR BALANCE COUNCIL.
F.
VIBRATION ISOLATION DEVICES
1.
4.
CHECK HANGER ROD SIZE FOR ALLOWABLE LOADS AT THE ISOLATING DEVICE AND AT THE
UPPER AND LOWER ATTACHMENTS TO STRUCTURES, DUCTS, EQUIPMENT, ETC.
J.
CATALOG DATA FOR EQUIPMENT REVIEWED BY THE ARCHITECT SHALL NOT SUPERSEDE THE
ENGINEER'S CONTRACT DOCUMENTS. THE REVIEW OF THE ENGINEER SHALL NOT RELIEVE THE
CONTRACTOR FROM RESPONSIBILITY FOR DEVIATIONS FROM DRAWINGS OR SPECIFICATIONS,
PROVIDING PROPER CLEARANCE, FABRICATION PROCESS AND COORDINATION WITH OTHER TRADES.
5.
CONSULT MANUFACTURER FOR APPLICATION DATA.
K.
WHEN SUBMITTED FOR THE ARCHITECT'S REVIEW, SHOP DRAWINGS SHALL BEAR THE CONTRACTOR'S
CERTIFICATION THAT THE CONTRACTOR HAS REVIEWED, CHECKED AND APPROVED THE SHOP
DRAWINGS, THAT THEY ARE IN HARMONY WITH THE REQUIREMENTS OF THE PROJECT AND WITH THE
PROVISIONS OF THE CONTRACT DOCUMENTS AND THAT THE CONTRACTOR HAS VERIFIED ALL FIELD
MEASUREMENTS AND CONSTRUCTION CRITERIA, MATERIALS, CATALOG NUMBERS AND SIMILAR
DATA. CONTRACTOR SHALL ALSO CERTIFY THAT THE WORK REPRESENTED BY THE SHOP DRAWINGS
IS RECOMMENDED BY THE CONTRACTOR AND THE CONTRACTOR'S GUARANTEE WILL FULLY APPLY.
L.
ALL CONTRACTORS SUBMITTING PROPOSALS FOR THIS WORK SHALL FIRST EXAMINE THE SITE AND
ALL CONDITIONS THEREIN. ALL PROPOSALS SHALL TAKE INTO CONSIDERATION ALL SUCH
CONDITIONS AS MAY AFFECT THE WORK UNDER THIS CONTRACT. THE SUBMITTING OF A BID
AUTOMATICALLY IMPLIES THAT THIS EXAMINATION OF SITE HAS BEEN DONE.
LAYOUT: M-702
P:\SGH\150343 SGH-La Plaza Mall Mcallen, TX\M-702_06078.dwg
PLOTTED: 7/16/2015 - 4:04 PM
USER: JGRAY
D
P.
PROVIDE INSTRUCTION TO LANDLORD'S OPERATING PERSONNEL AS NECESSARY, SHOWING
LOCATIONS AND PROPER OPERATION OF MAJOR ITEMS OF EQUIPMENT AND SYSTEM COMPONENTS
AND REFERRING TO THE OPERATING INSTRUCTION MANUAL DESCRIBED BELOW AS A GUIDE.
R.
D.
GENERAL CONTRACTOR SHALL REVIEW AIR BALANCE REPORT PRIOR TO SUBMISSION OF REPORT TO
ENGINEER AND ARCHITECT. IF ENGINEER OR ARCHITECT REVIEW THE AIR BALANCE REPORT MULTIPLE
TIMES DUE TO THE CONTRACTOR NOT FOLLOWING THESE GUIDELINES OR SENDING A PRELIMINARY
REPORT FOR REVIEW IN LIEU OF THE FINAL REPORT, THE CONTRACTOR WILL BE BACKCHARGED FOR
ALL REVIEWS BEYOND THE FIRST.
VERIFY CONTROLS DURING BALANCING, INCLUDING HUMIDITY CONTROLS WHERE APPLICABLE.
LIST OF MAJOR EQUIPMENT USED IN PROJECT ACCOMPANIED BY CONTRACTOR PURCHASE
ORDER NUMBERS AND SUPPLIERS NAMES AND ADDRESSES.
4.
ONE COPY OF EACH SHOP DRAWING GROUPED BY TYPES OF EQUIPMENT (I.E., ROOFTOP
UNITS, FANS, ETC.)
5.
SECTION FOR EACH SYSTEM INCLUDING:
C. EXPOSED ROUND AND RECTANGULAR DUCTWORK SHALL HAVE NO INSULATION.
a.
BRIEF DESCRIPTION OF SYSTEM OPERATION WITH LOCATION OF MAJOR COMPONENTS.
D.
b.
HVAC SYSTEM MAINTENANCE AND CALIBRATION INFORMATION, INCLUDING WIRING
DIAGRAMS AND SCHEMATICS.
SUBMIT A COMPLETED COPY TITLED "HVAC OPERATING INSTRUCTION MANUAL" ON THE BINDING
EDGE OF BINDER TO ARCHITECT FOR APPROVAL. AFTER ARCHITECT'S REVIEW AND ANY
CORRECTIONS REQUIRED ARE COMPLETED, SUBMIT A COPY OF THE MANUAL TO THE LANDLORD.
ANY REFERENCE TO TENANT OR TENANT CONSTRUCTION MANAGER, OR FURNISHED BY ANY OF THE
ABOVE, REFERS TO LUXOTTICA.
TRADE NAMES, MANUFACTURERS AND SHOP DRAWINGS
WHERE TRADE NAMES AND MANUFACTURERS ARE USED ON THE DRAWINGS OR IN THE
SPECIFICATIONS, THE EXACT EQUIPMENT SHALL BE USED. THE USE OF ANY UNAUTHORIZED
EQUIPMENT SHALL BE SUBJECT TO REMOVAL AND REPLACEMENT AT THE CONTRACTOR'S
EXPENSE.
CONTRACTOR SHALL SUBMIT ONLY SUBSTITUTION REQUESTS TO TENANT CONSTRUCTION
MANAGER FOR APPROVAL. SUBMISSIONS SHALL BE MADE EARLY ENOUGH IN PROJECT TO
ALLOW FOUR (4) WORKING DAYS FOR TENANT CONSTRUCTION MANAGER'S REVIEW WITHOUT
CAUSING DELAYS OR CONFLICTS TO THE JOB'S PROGRESS. SUBMITTALS SHALL BEAR THE
STAMP OF THE CONTRACTOR AND THE SUB-CONTRACTOR SHOWING THAT HE HAS REVIEWED
AND CONFIRMED THAT THE SUBMITTALS ARE IN CONFORMANCE WITH THE CONTRACT
DRAWINGS AND SPECIFICATIONS OR INDICATE WHERE EXCEPTIONS HAVE BEEN TAKEN.
DEMOLITION
1.
4
C.
AFTER CORRECTING BALANCE OF ALL AIR SYSTEMS TO WITHIN 10% OF DESIGNED VALUES, SUBMIT
FINAL AIR BALANCE REPORTS TO ARCHITECT, ENGINEER, AND LUXXOTICA. FINAL BALANCE REPORT
MUST INDICATE AIR VALUES WITHIN 10% OF DESIGN, OR MUST STATE THE REASON THAT THE
APPROPRIATE BALANCE COULD NOT BE ACHIEVED.
3.
2.
3
B.
ALL AIR DISTRIBUTION SYSTEMS ARE TO BE BALANCED IN ACCORDANCE WITH GENERALLY ACCEPTED
ENGINEERING STANDARDS BY A NEBB CERTIFIED VENDOR. DUCTED AIR RATES ARE TO BE MEASURED
AND ADJUSTED TO DELIVER FINAL FLOW RATES WITHIN 10% OF DESIGN RATES. GENERAL
CONTRACTOR TO DO ALL ADJUSTMENTS REQUIRED TO BALANCE THE SYSTEM WITHIN THE DESIGN
PARAMETERS. UNITS RPMS ARE TO BE ADJUSTED FIRST TO GET THE UNIT TO THE LOWEST RPMS TO
DELIVER THE REQUIRED CFM TO THE DIFFUSERS, THEN THE DAMPERS TO THE DIFFUSERS ARE TO BE
ADJUSTED TO BALANCE THE SYSTEM. GENERAL CONTRACTOR IS TO PROVIDE ALL LABOR AND
MATERIALS REQUIRED TO BALANCE THE SYSTEM.
INDEX
B
2
A.
2.
1.
U.
23 05 93 TESTING, ADJUSTING AND BALANCING FOR HVAC
TITLE PAGE: TITLE OF JOB, LANDLORD/TENANT, ADDRESS, DATE, SUBMISSION, CONTRACTOR
AND ENGINEER.
S. REFER TO RESPONSIBILITY SCHEDULE ON SHEET G-002 FOR INFORMATION IN REGARD TO
RESPONSIBILITY OF WORK OR ITEMS WHICH MAY AFFECT BID.
T.
12
13
14
J.
FLEXIBLE SUPPLY AIR DUCTWORK WITH 1" THICK FIBERGLASS BLANKET INSULATION WITH METALIZED
FILM VAPOR BARRIER OUTER JACKET. FLEXIBLE DUCT IN RETURN AIR PLENUM TO BE CLEARLY
LABELED "CLASS 1" EVERY FOUR FEET. FLEXIBLE DUCT LENGTH MAY NOT EXCEED FIVE FEET.
INSULATION SHALL HAVE MIN. INSTALLED R-VALUE OF 4.2.
K.
METAL DUCTWORK - NO FIBERGLASS DUCT ALLOWED.
L.
DUCT CONSTRUCTION SHALL BE AS FOLLOWS:
1.
EXCEPT WHERE OTHERWISE INDICATED, CONSTRUCT ALL LOW PRESSURE DUCT IN
ACCORDANCE WITH THE LATEST EDITION OF SMACNA STANDARDS WITH THE FOLLOWING
PRESSURE CLASSIFICATIONS:
a.
SUPPLY DUCTS: 2" W.G. POSITIVE.
b.
RETURN AND EXHAUST DUCTS: 2" W.G. NEGATIVE.
2.
SEAL ALL LOW PRESSURE DUCTS PER SMACNA CLASS B AND ALL MEDIUM PRESSURE DUCTS
TO SMACNA CLASS A.
3.
REGARDLESS OF ABOVE DUCT CONSTRUCTION AND SEALANT PRESSURE CLASSIFICATIONS,
MAXIMUM DUCT AIR LEAKAGE WILL NOT EXCEED 5% AS REQUIRED FOR FINAL AIR BALANCE
APPROVAL.
6
7
CONSULTANT PROJECT # 150343
Shremshock Engineering, Inc.
7400 W. Campus Rd. Suite 150 New Albany, OH 43054
t: 614 545 4550 | f: 614 545 4555 | shremshock.com
TX Registration Number: #F-9566
SEAL
M. ROUND DUCTWORK SHALL BE GALVANIZED STEEL WITH SPIRAL LOCK SEAM CONSTRUCTION FOR ALL
SIZES 12" DIAMETER AND LARGER. ROUND DUCTWORK SIZES 10" DIAMETER AND SMALLER MAY BE
SNAP-LOCK CONSTRUCTION. ALL SNAP-LOCK SEAMS SHALL BE SEALED AS DESCRIBED IN THESE
SPECIFICATIONS. ROUND FITTINGS SHALL BE GALVANIZED STEEL WITH SPOT WELDED AND BONDED
CONSTRUCTION. DUCTWORK SHALL BE AS MANUFACTURED BY UNITED MCGILL, SEMCO, OR
APPROVED EQUAL.
N.
ALL JOINTS AND SEAMS SHALL BE SEALED WITH 2" WIDE, GLASS- FIBER FABRIC REINFORCED TAPE.
JOINTS ALSO SHALL BE RIVETED OR CONNECTED WITH SHEET METAL SCREWS. LIQUID SEALANTS BY
UNITED MCGILL CORP., DOW CORNING, MIRACLE ADHESIVES AND SUREBOND INC. WILL BE
ACCEPTED IN LIEU OF TAPE.
23 07 00 HVAC INSULATION
A.
DUCT INSULATION AND APPURTENANCES SHALL HAVE A FLAME SPREAD RATING NOT EXCEEDING
TWENTY-FIVE (25) AND A SMOKE DEVELOPED RATING NOT EXCEEDING FIFTY (50).
B.
RECTANGULAR AND ROUND SUPPLY, RETURN, AND OUTSIDE AIR DUCTWORK CONCEALED FROM
VIEW SHALL HAVE FLEXIBLE FIBERGLASS DUCT WRAP LAMINATED TO FOIL REINFORCED KRAFT VAPOR
BARRIER FACING WITH 2" STAPLING FLANGE AND MIN. INSTALLED R-VALUE OF 4.2. OR AS REQUIRED
BY LOCAL CODES. OWENS-CORNING COMMERCIAL GRADE FIBERGLASS DUCT WRAP TYPE 100.
ALL DUCTWORK IN UNCONDITIONED SPACES SHALL HAVE INSULATION DUCT WRAP WITH A MINIMUM
INSTALLED R-VALUE OF 5.0. CONDITIONED SPACES SHALL HAVE INSULATION DUCT WRAP WITH A
MINIMUM INSTALLED R-VALUE OF 4.2. IN ALL CASES THE INSULATING VALUES SHALL BE IN
ACCORDANCE WITH LOCAL CODES.
E.
INSULATION SHALL NOT BE APPLIED UNTIL THE GENERAL CONSTRUCTION HAS PROGRESSED
SUFFICIENTLY TO INSURE AGAINST PHYSICAL OR MOISTURE DAMAGE TO THE INSULATION. ALL
INSULATION DAMAGED THROUGH FAILURE TO OBSERVE THIS DIRECTIVE SHALL BE REPLACED AT
THIS CONTRACTOR'S EXPENSE.
F.
HANGER RODS MUST BE PERPENDICULAR TO DUCTWORK BEFORE INSULATION IS INSTALLED.
23 33 00 DAMPERS
A.
RECTANGULAR DUCT GALVANIZED STEEL MANUAL BALANCE AND MOTORIZED DAMPER 6" WIDE 16
GAUGE OPPOSED BLADES, CHANNEL FRAME WITH BRACED CORNERS, CONCEALED LINKAGE, TEFLON
FILLED BEARINGS, 3/8" DIAMETER AXLE, 6" LONG CONTROL SHAFT. MOTORIZED DAMPER TO HAVE
REPLACEABLE BUTYL RUBBER SEALS INSTALLED ALONG THE TOP, BOTTOM AND SIDES OF THE
FRAME, AS WELL AS, ALONG ALL SIDES OF EACH BLADE.
B.
ROUND GALVANIZED STEEL MANUAL BALANCE DAMPER WITH SINGLE 16 GAUGE BLADE, CHANNEL
FRAME, STAINLESS STEEL SLEEVE BEARINGS PRESSED INTO FRAME, 3/8" DIAMETER AXLE EXTENDED
6" FOR CONTROL SHAFT, BLADE STOP.
C. EQUIP DAMPERS WITH LOCKING QUADRANTS.
D. INSTALL BALANCE DAMPERS WHERE SHOWN ON THE DRAWINGS AND ELSEWHERE AS NECESSARY TO
OBTAIN PROPER SYSTEM BALANCE.
E.
CHECK DAMPERS FOR PROPER OPERATION BEFORE AND AFTER INSTALLATION.
F.
DAMPERS SHALL BE RUSKIN. EQUAL PRODUCT BY AMERICAN WARMING AND VENTILATING, LOUVERS
AND DAMPERS, OR PREFCO MAY BE FURNISHED AT THE CONTRACTOR'S OPTION.
23 37 13 AIR DISTRIBUTION DEVICES
A.
SQUARE CEILING SUPPLY AIR DIFFUSER - STEEL SQUARE CEILING DIFFUSER, CONCENTRIC CONE
FACE, ROUND NECK, VOLUME CONTROL DAMPER, TITUS MODEL TMS.
B.
CEILING RETURN AIR GRILLE - STEEL CEILING GRILLE, TITUS MODEL 355RL.
C. FINISHES - FURNISH ALL AIR DISTRIBUTION DEVICES WITH PRIME COATED AND WHITE BAKED
ENAMEL FINISH COAT UNLESS SPECIFIED OTHERWISE.
D.
COORDINATE AIR DISTRIBUTION DEVICE LOCATIONS WITH ALL AFFECTED CONTRACTORS BEFORE
INSTALLING DUCTWORK. SIGNIFICANT DEVIATIONS IN LOCATIONS FROM THOSE SHOWN ON THE
DRAWINGS MUST BE APPROVED BY ARCHITECT BEFORE INSTALLATION.
E.
SUSPEND CEILING AIR DEVICES FROM STRUCTURE ON WIRE HANGERS OR FROM RIGID DUCTWORK.
CEILING MUST NOT BE USED TO SUPPORT AIR DISTRIBUTION DEVICES.
F.
SECURELY FASTEN SIDE WALL AIR DEVICES TO RIGID DUCTWORK OR STRUCTURE.
G.
AIR DISTRIBUTION DEVICES FURNISHED AND INSTALLED BY THE GENERAL CONTRACTOR SHALL BE
TITUS OR EQUAL TO MODEL SHOWN ON SHEET M-301.
G. INSTALL ALL INSULATION ACCORDING TO MANUFACTURER'S RECOMMENDATIONS.
H.
INSULATION SHALL BE APPLIED OVER FLANGES, JOINTS AND SEAMS IN PIPING AND DUCTWORK.
I.
ALL JOINTS AND SEAMS IN INSULATION SHALL BE PROPERLY SEALED TO MAINTAIN VAPOR BARRIER
INTEGRITY.
J.
INSULATION SHALL BE OWENS-CORNING. EQUAL PRODUCT BY ARMSTRONG, CERTAINTEED,
SCHULLER OR KNAUF MAY BE FURNISHED AT THE CONTRACTOR'S OPTION.
SUNGLASS HUT
LA PLAZA MALL
23 31 13 HVAC AIR DISTRIBUTION AND RETURN SYSTEMS
A.
2200 S. 10TH STREET
McALLEN, TX 78503
SPACE #Q14-C
2.0 TYPE: PREMIUM
PROVIDE AND INSTALL DUCTWORK AND PLENUMS OF SIZE AND LOCATION AS SHOWN ON
DRAWINGS. ALL DUCTS FOR AIR VELOCITIES LESS THAN 2000 FPM AND STATIC PRESSURE IN DUCT
2" OR LESS SHALL BE CONSTRUCTED OF GALVANIZED SHEET METAL. THE GAUGE OF STEEL USED IN
ALL DUCTS SHALL BE AS FOLLOWS:
SGH STORE #: 6078
1.
WHERE GREATER RECTANGULAR DIMENSION IS 12" OR LESS USE 26 GAUGE.
2.
WHERE GREATER RECTANGULAR DIMENSION IS FROM 12" THROUGH 30" USE 24 GAUGE.
DRAWN BY: CHC
3.
WHERE GREATER RECTANGULAR DIMENSION IS FROM 31" THROUGH 54" USE 22 GAUGE.
REVIEWED BY: JTP
4.
WHERE GREATER RECTANGULAR DIMENSION IS FROM 55" THROUGH 84" USE 20 GAUGE.
AUTHORIZED FOR:
B. TRANSVERSE JOINTS AND BRACING TO CONFORM TO "HVAC DUCT CONSTRUCTION STANDARDS CONTRACTOR SHALL BE RESPONSIBLE FOR THE DEMOLITION AND REMOVAL OF EXISTING
METAL AND FLEXIBLE" (CURRENT SMACNA).
WORK. FIELD VERIFY AND COORDINATE ANY EXISTING EQUIPMENT REQUIRED TO BE LEFT INTACT
C. ALL DUCTS SHALL BE RIGID AND SHALL BE CROSS-BROKEN, PROPERLY STIFFENED WITH SUITABLE
AND PROTECT EQUIPMENT TO REMAIN DURING CONSTRUCTION.
BRACES, TOES, OR ANGLES TO KEEP THEM TRUE TO SHAPE AND PREVENT BUCKLING. ALL VERTICAL
DUCTS SHALL BE OF STRONG ENOUGH CONSTRUCTION TO CARRY 100 LBS. SUSPENDED LOAD
FROM HANGERS WITHOUT BUCKLING. SOLDER ALL JOINTS WHERE NECESSARY TO INSURE TIGHT
WORK. SEAMS OF ALL DUCTS AND JOINTS SHALL BE HAMMERED TO A SMOOTH SURFACE ON THE
INSIDE.
5
A Subsidiary of the Luxottica Group
4000 Luxottica Place
Mason, Ohio 45040
O. DUCT TRANSITIONS SHALL NOT EXCEED 30 DEGREES SLOPE EXCEPT AS SPECIFICALLY NOTED
OTHERWISE.
1.
Q. WITHIN 90 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD DRAWINGS OF THE ACTUAL
INSTALLATION SHALL BE PROVIDED TO THE BUILDING LANDLORD. RECORD DRAWINGS SHALL
INCLUDE AS A MINIMUM THE LOCATION AND PERFORMANCE DATA ON EACH PIECE OF EQUIPMENT,
GENERAL CONFIGURATION OF DUCT DISTRIBUTION SYSTEM INCLUDING SIZES, AND THE AIR DESIGN
FLOW RATES.
1
EXAMINE DEAD LOAD AND OPERATING LOAD CONDITIONS WHEN SELECTING DEVICES, ADJUST
FOR PROPER ALIGNMENT AND LOADING. AVOID "GROUNDING" THE ISOLATOR.
CONTRACTOR SHALL SUBMIT SHOP DRAWINGS PER THE DOCUMENTS PROVIDED BY THE
TENANT/CONTRACTOR.
O. COMPILE WRITTEN MANUAL OF OPERATING INSTRUCTIONS INCLUDING COPIES OF SHOP DRAWINGS
AND A LISTING OF EQUIPMENT SUPPLIERS. ASSEMBLE IN 8-1/2" X 11" HARD BACKED INDEXED
BINDER. MATERIAL SHALL BE AS FOLLOWS:
A
3.
I.
N.
C
VIBRATION ISOLATION DEVICES SHALL BE FURNISHED AND INSTALLED WITH SUPPORTS
BETWEEN VIBRATING EQUIPMENT AND THE STRUCTURE (FANS, AIR HANDLERS, ETC.) BY THIS
CONTRACTOR.
VIBRATING EQUIPMENT HUNG FROM STRUCTURE SHALL BE ISOLATED WITH RUBBER AND
SPRING DEVICES, VIBRATING EQUIPMENT SUPPORTED FROM FLOOR OR DECK SHALL BE
ISOLATED WITH HOUSED SPRING MOUNT DEVICES.
2.
THE MATERIALS AND EQUIPMENT INSTALLED IN THE WORK SHALL MEET THE REQUIREMENTS OF THE
CONTRACT DOCUMENTS AND NO MATERIALS OR EQUIPMENT SHALL BE ORDERED UNTIL REVIEWED
BY THE ENGINEER, LANDLORD AND/OR ARCHITECT.
M. CONTRACTOR SHALL VERIFY LOCATION OF UTILITIES AND NOTE CONDITIONS WHICH WOULD AFFECT
THE WORK. ALL DISCREPANCIES SHALL THEN BE REPORTED PRIOR TO THE BID AWARD.
E
THIS CONTRACTOR IS TO BECOME INFORMED OF THE EXACT DIMENSIONS OF FINISHED WORK
WHERE PIPES, DUCTS AND EQUIPMENT ARE TO BE PLACED AND WILL ARRANGE THE WORK
ACCORDINGLY, ASSUMING ALL RESPONSIBILITY FOR PROPER LOCATION AND COORDINATION OF THE
WORK.
B. IN THE ERECTION OF THE DUCTWORK, SPECIAL CARE SHALL BE USED PROVIDING SUPPORT.
ALL PERMITS REQUIRED BY LAWS, ORDINANCES AND BUILDING CODES HAVING JURISDICTION SHALL
BE OBTAINED AT THE PROPER TIME BY AND AT THE EXPENSE OF THIS CONTRACTOR.
F
11
D. CONSTRUCTION INCLUDING HANGERS AND SUPPORTING SYSTEMS OF ALL DUCTWORK SHALL ALSO
ASIDE FROM NORMAL INTERIM INSPECTIONS OF WORK IN PLACE, TENANT SHALL HAVE AN
BE IN ACCORDANCE WITH "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE"
INDEPENDENT CONTRACTOR INSPECT THE FINISHED INSTALLATION UPON COMPLETION FOR
(CURRENT SMACNA).
COMPLIANCE WITH THE PLANS, SPECIFICATIONS AND CODES. THE INSTALLING CONTRACTOR
E. FLEXIBLE CONNECTIONS SHALL BE INSTALLED ON THE OUTLET AND INTAKE OF AIR HANDLING UNITS
WILL BE RESPONSIBLE TO BRING ALL ITEMS REPORTED BY THE INDEPENDENT CONTRACTOR UP
AND FANS. THESE CONNECTIONS SHALL BE AT LEAST 6" LONG, MADE OF NFPA 90A APPROVED
TO PLANS AND SPECIFICATION REQUIREMENTS.
FLAMEPROOF FABRIC.
W. WARRANTY AND GUARANTEE
F. FURNISH AND INSTALL VOLUME CONTROLLER AND EXTRACTOR AT ALL BRANCH TAKEOFFS IN SUPPLY
AND RETURN FROM MAIN DUCTS TO ALL BRANCH DUCTS WHERE SHOWN. UNIT SHALL BE OF TWO
1.
CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND LABOR PROVIDED UNDER THIS
GAUGES HEAVIER THAN THE DUCT.
CONTRACT AND SHALL MAKE GOOD, REPAIR OR REPLACE AT NO ADDITIONAL COST ANY
DEFECTIVE WORK, MATERIAL, OR EQUIPMENT DISCOVERED WITHIN 12 MONTHS FROM THE
G. PROVIDE MANUAL ADJUSTING LEVER FOR EACH UNIT. UNITS SHALL MOVE FROM FULL OPEN TO
DATE OF CERTIFICATE OF OCCUPANCY. THIS GUARANTEE SHALL EXTEND TO LABOR AND
FULLY CLOSED POSITION TO CONTROL AIR DIRECTION AND VOLUME.
MISCELLANEOUS MATERIALS REQUIRED FOR THE INSTALLATION OF EQUIPMENT FURNISHED
H. FURNISH AND INSTALL TURNING VANES IN ALL ELBOWS OF RECTANGULAR DUCTS. THE BLADES TO
THROUGH TENANT NATIONAL ACCOUNTS REPRESENTATIVE, BUT SHALL NOT OVERLAP WITH
BE HOLLOW-FORMED DOUBLE THICKNESS VANES.
WARRANTY PROVIDED BY MANUFACTURER. THE CONTRACTOR IS RESPONSIBLE TO VERIFY,
I. INSTALL SUPPLY AND RETURN REGISTERS, GRILLES AND DIFFUSERS AS SHOWN ON THE DRAWINGS
COORDINATE AND FOLLOW ALL PROPER HANDLING AND INSTALLATION TECHNIQUES WITH
AND SCHEDULE.
MANUFACTURER(S) IN ORDER TO MAINTAIN MANUFACTURER'S WARRANTY.
A.
E.
H.
10
1.
G. PIPING AND EQUIPMENT LAYOUT IS SCHEMATIC. EXACT LOCATIONS ARE DETERMINED BY
STRUCTURAL AND OTHER CONDITIONS. DESIGN OF SYSTEM MAY NOT BE CHANGED. ONLY EXACT
LOCATION OF PIPING AND DUCTS MAY BE REVISED TO SUIT CONSTRUCTION CONDITIONS AND AID
IN COORDINATION WITH WORK OF OTHER CONTRACTORS.
G
9
V. FINAL HVAC INSPECTIONS
23 05 00 GENERAL PROVISIONS FOR HVAC
A.
8
LA PLAZA MALL
2
AT
1
8
9
10
11
MECHANICAL SPECIFICATIONS
M-702
12
13
14
3
4
5
6
7
8
9
10
11
KEY NOTES
1.
2.
K
A-16
16
ADJACENT
TENANT (N.I.C.)
STUB-UP
(TYPICAL)
A-14
16
STUB-UP
(TYPICAL)
3.
A-17
A-37/39/41
13
13
4.
14
J
ADJACENT
TENANT (N.I.C.)
H
101
TECH RACK
A-13
29
IG
V
5
T
J
8.
9.
c
25
11
3
18
(E)RTU
6
6.
7.
1,IG
5
STOCK ROOM
G
MALL COMMON
AREA (N.I.C.)
4
A-1
A-5
USB CHARGING
STATION
5.
13
16
A-18
8
17
(EX.) RTU
STUB-UP
(TYPICAL)
SALES
10.
11.
100
12.
13.
23
TIME CLOCK AND
9
CONTACTORS
A-15
14.
15.
16.
13
13
A-7
IG
A-23
PANEL 'A'
17.
-
10
7
8
A-22 16
PHONE
STUB-UP
(TYPICAL)
18.
STUB-UP
(TYPICAL)
A-20
ADJACENT
TENANT (N.I.C.)
19.
16
20.
F
PLAN NORTH
21.
22.
23.
F1
SCALE:
POWER PLAN
24.
25.
26.
E
27.
28.
29.
12
LAYOUT: E-101
P:\SGH\150343 SGH-La Plaza Mall Mcallen, TX\E-101_06078.dwg
PLOTTED: 7/16/2015 - 4:04 PM
14
GENERAL NOTES
FURNISH AND INSTALL FLOOR MOUNTED RECEPTACLE. SEE DIMENSION PLAN THIS
SHEET FOR LOCATION.
FURNISH AND INSTALL FLOOR MOUNTED POWER/DATA COMBINATION.
CONTRACTOR SHALL FURNISH AND INSTALL (1) 1-1/4" CONDUIT WITH CAT6 CABLE
PULLED BACK TO RACK FOR DATA OUTLET, SEE DIMENSION PLAN THIS SHEET FOR
LOCATION. ON DEDICATED 24 HOUR CIRCUIT. REFER TO DETAIL ON SHEET E-501
DETAIL 'A8'
CONDUIT FOR CASH REGISTER POWER CIRCUIT. COORDINATE INSTALLATION
REQUIREMENTS WITH CONSTRUCTION MANAGER AND MILLWORK CONTRACTOR .
CHECK LENGTH OF SCREWS BEFORE ATTACHING OUTLETS TO MILLWORK. VERIFY
SCREWS ARE NOT TOO LONG AND WILL NOT DAMAGE OTHER SIDE OF MILLWORK
WHEN TIGHTENED. TRENCH AND PATCH FLOOR AS REQUIRED, COORDINATE
LOCATION IN FIELD WITH LANDLORD'S REPRESENTATIVE AND OWNER'S FIELD
REPRESENTATIVE PRIOR TO ROUGH-IN.
PROVIDE 1" CONDUIT FOR POWER BELOW FLOOR. COORDINATE TRENCH
LOCATIONS IN FIELD WITH LANDLORD'S REPRESENTATIVE. REPAIR FLOOR TO
MATCH EXISTING CONDITIONS.
PROVIDE 1-1/4" CONDUIT FOR TELE/DATA BELOW FLOOR. COORDINATE TRENCH
LOCATIONS IN FIELD WITH LANDLORD'S REPRESENTATIVE. REPAIR FLOOR TO
MATCH EXISTING CONDITIONS. EXTEND CONDUIT FOR TELE/DATA TO TELE/DATA
DISTRIBUTION EQUIPMENT.
EXTEND CONDUIT TO TELE/DATA DISTRIBUTION EQUIPMENT.
FURNISH AND INSTALL 2'X4' TELEPHONE BOARD WITH SURFACE MOUNTED QUAD
RECEPTACLE. EXTEND TELEPHONE SERVICE TO BOARD AND TERMINATE WITH A66
BLOCK.
REFER TO ELEVATION SHEET A-502 FOR MORE INFOMATION.
FURNISH AND INSTALL TIME CLOCK AND CONTACTORS REFER TO ONE LINE
DIAGRAM FOR ADDITIONAL INFORMATION. SEE LIGHTING CONTROL DETAIL ON
E-501.
ELECTRICAL DISTRIBUTION EQUIPMENT. SEE ONE LINE DIAGRAM ON SHEET E-601.
FURNISH AND INSTALL (1) DUPLEX RECEPTACLE ON DEDICATED CIRCUIT MOUNTED
AT 2'-6" A.F.F. (TO CENTER OF DEVICE) FOR FRAME WARMER.
RECEPTACLE MOUNTED ON CEILING FOR SHOW WINDOW AS REQUIRED BY N.E.C.
FURNISH AND INSTALL RECEPTACLE FOR POWER OF DISPLAY CASES BELOW BASE
OF MILLWORK SO CORDS AND RECEPTACLE ARE CONCEALED BEHIND FIXTURES.
COORDINATE EXACT LOCATION WITH MILLWORK VENDOR.
MECHANICAL EQUIPMENT: PROVIDE FEEDERS AND DISCONNECTS PER
MECHANICAL EQUIPMENT FEEDER/CONNECTION SCHEDULE ON SHEET E-601.
WATER HEATER. SEE EQUIPMENT CONNECTION SCHEDULE ON SHEET E-601.
CONTROL CIRCUIT THROUGH LIGHTING SWITCH BANK. SEE DETAIL ON SHEET
E-501.
FURNISH AND INSTALL GFI DUPLEX RECEPTACLE ADJACENT TO UNIT IF NOT
EXISTING/FURNISHED WITH EQUIPMENT. CIRCUIT AS INDICATED, FURNISH
WEATHER PROOF ENCLOSURES AND COVERS AS REQUIRED.
JUNCTION BOX INSTALLED FLUSH WITHIN DRYWALL. EXTEND 1/2" CONDUIT TO
ABOVE CEILING TO HVAC UNIT FOR THERMOSTAT/REMOTE SENSOR.
DUCT SMOKE DETECTOR/REMOTE TEST STATION: DUCT MOUNTED SMOKE
DETECTOR IS EXISTING. CONTRACTOR SHALL INTERLOCK SMOKE DETECTOR WITH
HVAC UNIT, REMOTE TEST ALARM STATION AND FIRE ALARM SYSTEM (IF
APPLICABLE). MAKE ALL FINAL CONNECTIONS AS REQUIRED FOR A COMPLETE
SYSTEM. HVAC UNIT TO SHUT DOWN UPON ACTIVATION OF SMOKE DETECTOR.
COORDINATE WITH LANDLORD TO AVOID CONFLICTS IN FIELD.
INSTALL A DELIVERY BUZZER SYSTEM AS SHOWN, INCLUDING PUSH-BUTTON AT
REAR DOOR, TRANSFORMER AND BUZZERS AS INDICATED. COORDINATE ALL
REQUIREMENTS WITH TENANT AS TO LOCATIONS. REFER TO DETAIL ON SHEET
E-501 FOR ADDITIONAL INFORMATION.
AIR CURTAIN.
AIR CURTAIN SPEED CONTROL.
PROVIDE FIRE ALARM JUNCTION BOX. COORDINATE FINAL TIE-IN AND TESTING OF
FIRE ALARM SYSTEM. FIELD VERIFY EXACT LOCATION AND REQUIREMENTS PRIOR
TO BID.
PROVIDE FIRE ALARM MANUAL PULL STATION AND CONNECT TO PANEL. FIELD
VERIFY EXACT LOCATION AND REQUIREMENTS.
PROVIDE FIRE ALARM HORN/STROBE, AND CONNECT TO LANDLORD'S MAIN FIRE
ALARM SYSTEM. FIELD VERIFY EXACT LOCATION AND REQUIREMENTS.
PROVIDE FIRE ALARM STROBE AND CONNECT TO LANDLORD'S MAIN FIRE ALARM
SYSTEM. FIELD VERIFY EXACT LOCATION AND REQUIREMENTS.
PROVIDE FIRE ALARM CEILING MOUNTED SMOKE DETECTOR AND CONNECT TO
PANEL. FIELD VERIFY EXACT LOCATION AND REQUIREMENTS.
PROVIDE FIRE ALARM REMOTE ANNUNCIATOR PANEL,AND CONNECT TO PANEL.
FIELD VERIFY EXACT LOCATION AND REQUIREMENTS.
PROVIDE 8" X 8" X 4" DEEP FLUSH-MOUNTED JUNCTION BOX WITH BUSHED-HOLE
SCREW COVER, CENTER AT 16" AFF BEHIND TECH RACK, FOR CAT 6 CABLES.
TERMINATE COMMUNICATIONS CONDUITS AT BOX AND EXTEND CABLES TO TECH
RACK.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
USER: JGRAY
13
REFER TO MECHANICAL PLAN FOR LOCATION OF MECHANICAL EQUIPMENT. FIELD
VERIFY EXACT LOCATIONS. PROVIDE AND INSTALL ALL CONVENIENCE RECEPTACLES,
SAFETY SWITCHES, WIRING, OR OTHER EQUIPMENT TO ENSURE A COMPLETE AND
OPERABLE HVAC SYSTEM.
ALL WALL MOUNTED RECEPTACLES, SWITCHES, AND COVERPLATES SHALL MATCH
WALL, REFER TO SHEET A-201 FOR FINISHES. THE CEILING RECEPTACLES AND
COVERPLATES SHALL MATCH CEILING.
CONDUIT FOR DATA/TELEPHONE OUTLETS SHALL HAVE NO MORE THAN THREE 90°
BENDS. IF THE CONDUIT RUN REQUIRES MORE THAN THREE 90° BENDS, PROVIDE
A PULL/JUNCTION BOX AFTER EACH SET OF THREE 90° BENDS.
LABEL ALL COVERPLATES ON INSIDE FACE OF PLATE WITH CIRCUIT NUMBER AND
PANEL DESIGNATION. I.E. "A-1". CIRCUIT SHALL BE WRITTEN WITH PERMANENT
MARKER IN A CONTRASTING COLOR.
ALL TELEPHONE/DATA CABLING TO BE RUN IN CONDUIT TO 6" ABOVE CEILING.
PROVIDE 6' OF EXTRA CABLING AT ALL TELEPHONE/DATA TERMINATIONS. ALL
CABLING SHALL BE PLENUM RATED. RUN PHONE/DATA CABLING (CAT 6)
COMPLETELY IN CONDUIT IF LOCAL CODES/MUNICIPALITIES REQUIRE IT (FIELD
VERIFY). ALL CABLING SHALL BE ROUTED AWAY FROM ALL ELECTRIC EQUIPMENT
(WITHIN 18") AND SECURED TO STRUCTURE ABOVE. ALL TELEPHONE/DATA CABLING
FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR.
ALL MOUNTING HEIGHTS FROM THE CENTERLINE OF THE BOX TO THE FINISHED
FLOOR ARE AS FOLLOWS, UNLESS NOTED OTHERWISE ON PLAN: SWITCHES-48",
ELECTRICAL/TELEPHONE/DATA OUTLETS-18", THERMOSTATS-5'-0", TOP OF
PANELBOARD-6'-6".
ALL ROOF PENETRATIONS TO BE COORDINATED WITH THE LANDLORD'S DESIGNATED
ROOFING CONTRACTOR.
FLEXIBLE CONDUIT SHALL BE USED FOR ALL FINAL CONNECTIONS TO MILLWORK,
INTERIOR LIGHTING FIXTURES, AND EQUIPMENT. MAXIMUM LENGTH OF FLEXIBLE
CONDUIT SHALL BE 6'-0".
CONDUIT AND OUTLETS FOR SECURITY, DATA, TELEPHONE, AND ELECTRIC MAY
REQUIRE REMOVAL OF CONCRETE SLAB OR ROUTING OF CONDUIT UNDER FLOOR
IN SPACE BELOW. ALL WORK TO BE COORDINATED WITH THE LANDLORD
DISCONNECT SWITCHES SHALL BE GENERAL DUTY IN APPROPRIATE NEMA
ENCLOSURES. A LINE VOLTAGE, HORSEPOWER RATED DISCONNECT SWITCH SHALL
BE INSTALLED ADJACENT TO EACH MOTOR.
TRANSFORMER NEUTRALS SHALL BE SECURELY GROUNDED TO THE BUILDING STEEL
AND COLD WATER PIPING PER THE N.E.C. AND LOCAL CODE REQUIREMENTS.
INSTALL TRANSFORMERS ON VIBRATION ISOLATION PADS.
ELECTRICAL EQUIPMENT EXPOSED TO WEATHER MUST BE WEATHERPROOF.
ALL TEMPORARY WIRING SHALL BE REMOVED WHEN PERMANENT POWER IS
AVAILABLE.
IF INSTALLATION VARIES FROM THE CONTRACT DRAWINGS, THE GENERAL
CONTRACTOR WILL BE RESPONSIBLE FOR OBTAINING "AS BUILT" DRAWINGS FROM
THE SUBCONTRACTORS AND SUBMITTING SAME TO SUNGLASS HUT.
CONTRACTOR SHALL PURCHASE AT SGH NATIONAL ACCOUNT AGREED PRICING,
ALL DISCONNECT SWITCHES, ELECTRIC DISTRIBUTION PANEL, CIRCUIT BREAKERS
AND FUSES. CONTACT SUNGLASS HUT'S NATIONAL ACCOUNT REPRESENTATIVE
FOR PRICING INFORMATION AND INCLUDE IN BID.
SEE ARCHITECTURAL ELEVATIONS FOR ADDITIONAL INFORMATION ON PLACEMENT
OF OUTLETS AND SWITCHES.
FOR ALL CASHWRAP MILLWORK ELECTRIC, DATA, AND TELEPHONE OUTLETS, REFER
TO THE DETAILS ON SHEET E-501.
ALL DATA/PHONE CABLING MUST BE PROPERLY IDENTIFIED WITH NUMBER AND/OR
COLOR SYSTEM AT BOTH ENDS.
ANY PENETRATIONS THROUGH FIRE-RESISTANT/RATED WALLS, PARTITIONS,
FLOORS, AND CEILINGS SHALL BE FIRESTOPPED USING APPROVED UL METHODS
TO MAINTAIN THE FIRE RESISTANCE RATING.
RECEPTACLE CIRCUITS UP TO 100'-0" IN LENGTH SHALL UTILIZE #12 CONDUCTORS
MINIMUM. RECEPTACLE CIRCUITS FROM 101'-0" TO 150'-0" IN LENGTH SHALL
UTILIZE #10 CONDUCTORS MINIMUM. RECEPTACLE CIRCUITS FROM 151'-0" TO
250'-0" IN LENGTH SHALL UTILIZE #8 CONDUCTORS MINIMUM. RECEPTACLE
CIRCUITS ABOVE 250'-0" IN LENGTH SHALL UTILIZE #6 CONDUCTORS MINIMUM.
ELECTRICAL CONTRACTOR SHALL PROVIDE JUNCTION BOX AND RACEWAY FOR
THERMOSTATS AT 60" A.F.F. THERMOSTATS AND TEMPERATURE SENSORS
INSTALLED AND WIRED BY MECHANICAL CONTRACTOR. COORDINATE EXACT
LOCATIONS WITH MECHANICAL CONTRACTOR. TYPICAL OF ALL.
DUCTWORK AND PIPING SHALL NOT BE ROUTED OVER ELECTRIC PANEL.
IT IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO REVIEW ALL
ARCHITECTURAL, MECHANICAL, PLUMBING, STRUCTURAL, FIRE ALARM AND FIRE
PROTECTION AND ELECTRICAL DRAWINGS AND NOTES TO ENSURE THAT ALL
ELECTRICAL REQUIREMENTS ARE MET.
ALL WORK SHALL BE IN STRICT ACCORDANCE WITH NATIONAL ELECTRICAL CODE
AND ALL LOCAL CODES AND ORDINANCES.
GC'S ELECTRICIAN TO PULL ALL LOW VOLTAGE TELEPHONE AND DATA LINES
INCLUDING INSTALLATION OF DEVICES. PUNCH DOWN OF LINE(S) AT THE TERMINAL
BOARD IS BY OTHERS.
REFER TO SHEET E-501 FOR ABBREVIATIONS AND SYMBOLS
REFER TO SHEET G-002 FOR RESPONSIBILITY SCHEDULE.
A Subsidiary of the Luxottica Group
4000 Luxottica Place
Mason, Ohio 45040
CONSULTANT PROJECT # 150343
Shremshock Engineering, Inc.
7400 W. Campus Rd. Suite 150 New Albany, OH 43054
t: 614 545 4550 | f: 614 545 4555 | shremshock.com
TX Registration Number: #F-9566
SEAL
LA PLAZA MALL
2
AT
1
D
C
SUNGLASS HUT
LA PLAZA MALL
2200 S. 10TH STREET
McALLEN, TX 78503
SPACE #Q14-C
2.0 TYPE: PREMIUM
B
SGH STORE #: 6078
DRAWN BY: EDS
REVIEWED BY: KAH
AUTHORIZED FOR:
POWER PLAN
A
A1
SCALE:
E-101
NOT USED
1
2
3
4
5
6
7
8
9
10
11
12
13
14
2
3
4
5
6
7
8
9
10
11
KEY NOTES
1.
2.
3.
K
4.
5.
6.
7.
8.
9.
J
10.
LIGHTING SPECIFICATIONS
MARK
TYPE SUPPLIER
A3W
B3 EM
H
A3W
CONTECH
LIGHTING
B3 EM PHILIPS
C4W
TW4'-0"
RP
X1A
PRODUCT TYPE
DESCRIPTION
WATT #LP LAMP
LED TRACK HEAD - GIMBAL RING, WHITE, PROVIDE FACTORY STICKER
LIMITING LAMP TO 13 WATTS (WHITE)
4' LED STRIP FIXTURE 'FLUXSTRAM' 3500K, 3100 LUMENS W/
EMERGENCY PACK
RECESSED ADJASTABLE-1 LIGHT ACCENT/DOWNLIGHT LED SOURCE
(WHITE)
#LED12P30SD30KNFL
(1) 75W PAR 30 LAMP
CTL830-P (WHITE)
13
-
LF-4-FR-31-35-U-DZT-EM
31
N/A
LED INCLUDED
C4W
CONTECH
LIGHTING
RAN7530X1-P-HB24
(WHITE)
13
1
TW
CONTECH
LIGHTING
LT-(2, 4, 6, 8)-P
N/A
N/A
N/A
RP
DUAL
LIGHT
LG-2-S
300
N/A
N/A
EMERGENCY 250 WATT REMOTE POWER PACK TO BE USED WITH
FIXTURE TYPES B1, B3 OR C1 SERIES
X1A
LIGHT
ALARMS
LED INCLUDED
SEMI RECESSED EXTRUDED ALUMINUM EDGE LIT EXIT SIGN WITH RED
LETTERS FOR CEILING OR WALL MOUNTING. RED LED INCLUDED.
SPLEDWRCD
#LED12P30SD30KNFL
LED FIXTURE
N/A
3
11.
12.
13.
14.
15.
16.
12
13
14
GENERAL NOTES
CIRCUIT VIA MASTER LIGHTING SWITCH BANK. SEE LIGHTING CONTROL DETAIL ON
E-501.
CIRCUIT SIGN LIGHTING THROUGH TIME CLOCK.
FURNISH AND INSTALL JUNCTION BOX AND DISCONNECT TOGGLE TYPE SWITCH
WITH MINIMUM 12" WHIP PER N.E.C. LOCATE ABOVE CEILING NEAR ACCESS PANEL
IN CONCEALED LOCATION. CIRCUIT THROUGH TIMECLOCK/CONTACTOR. SEE
ARCHITECTURAL SHEETS FOR SIGN LOCATION.
FURNISH AND INSTALL GANGED SWITCH FOR LOCAL LIGHTING SWITCHES. PROVIDE
COMMON FACEPLATE OR MULTIPLE FACEPLATES OF EQUAL WIDTHS. SEE LIGHTING
CONTROL DETAIL ON E-501.
CONNECT EMERGENCY FIXTURE TO EMERGENCY/NIGHT LIGHTING CIRCUIT (A-2) PER
NEC 700-12(A) AND LIFE SAFETY CODE.
EMERGENCY FIXTURE TO BE SERVED BY LOCAL LIGHTING CIRCUIT AHEAD OF ALL
SWITCHING.PER NEC 700-12(A) AND LIFE SAFETY CODE.
FURNISH AND INSTALL CEILING MOUNTED OCCUPANCY SENSOR.
FURNISH AND INSTALL WALL MOUNTED OCCUPANCY SENSOR
FURNISH AND INSTALL CONDUIT FROM TECK RACH TO 24" ABOVE CEILING FOR
TERMINATION AT TRAFFIC COUNTER PROVIDE CAT6 DATA CABLE WITH MINIMUM
6FT COILED AND LABELED CABLE AT BOTH ENDS.
FURNISH AND INSTALL CONDUIT FROM TECH RACK TO 24" ABOVE CEILING FOR
TERMINATION AT WIRELESS POWER INJECTOR BRICK/WIRELESS ACCESS POINT
PROVIDE CAT6 DATA CABLE WITH MINIMUM 6FT COILED AND LABELED CABLE AT
BOTH ENDS.
SECURITY CAMERA FOR CCTV SYSTEM. REFER TO DETAIL ON SHEET E-501 FOR
INSTALLATION REQUIREMENTS.
PROVIDE ADDITIONAL STRUCTURAL SUPPORT AS REQUIRED FOR MOUNTING OF
REMOTE POWER PACK (78lbs).
FURNISH AND INSTALL LIGHTING OVERRIDE SWITCH IN MASTER SWITCH BANK (SEE
A8/E-501).
FURNISH AND INSTALL TRACK LIGHTING CURRENT LIMITING BREAKERS ON TRACK.
AIR CURTAIN
18"x18" CORIAN ACCESS PANEL
1.
2.
3.
4.
5.
6.
7.
8.
9.
G
10.
11.
12.
13.
14.
15.
16.
A Subsidiary of the Luxottica Group
4000 Luxottica Place
Mason, Ohio 45040
CONSULTANT PROJECT # 150343
Shremshock Engineering, Inc.
7400 W. Campus Rd. Suite 150 New Albany, OH 43054
t: 614 545 4550 | f: 614 545 4555 | shremshock.com
TX Registration Number: #F-9566
SEAL
AT
F
EMERGENCY (EM) LUMINAIRES THAT ARE NOT POWERED FROM INVERTER SHALL BE
CIRCUITED WITH AN "UNSWITCHED HOT" TO PROVIDE CONTINUOUS POWER TO
BATTERY PACK EVEN WHEN LUMINAIRE IS OFF.
ALL NIGHT-LIGHT (NL) LUMINAIRES SHALL BE CIRCUITED AHEAD OF ANY SWITCHING
IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO UNLOAD INVENTORY AND
STORE LIGHTING PACKAGE. THE CONTRACTOR SHALL ALSO SHIP ANY EXCESS
MATERIALS BACK TO THE ELECTRICAL PACKAGE DISTRIBUTOR.
EXIT LIGHTS AT THE STOREFRONT SHALL BE CEILING MOUNTED AND CENTERED
OVER OPENINGS. EXIT/EMERGENCY LIGHTS AT DOOR TO NON-SALES AREAS SHALL
BE CEILING MOUNTED AND CENTERED ABOVE DOOR. IF PLAN LOCATIONS ARE NOT
ACCEPTABLE, IMMEDIATELY CONTACT SGH PROJECT MANAGER FOR DIRECTION.
WHERE DRYWALL CEILINGS ARE USED IN THE SALES AREA, CONTRACTOR SHALL
ARRANGE CIRCUITS TO AVOID THE USE OF JUNCTION BOXES IN INACCESSIBLE
LOCATIONS. THE USE OF JUNCTION BOXES ABOVE DRYWALL CEILINGS SHALL BE
LIMITED TO LOCATIONS NEAR ACCESS FRAMES USED FOR DIFFUSERS AND RETURN
AIR GRILLES OR ACCESS PANELS AS LOCATED ON PLANS. IF PLAN LOCATION IS
NOT ACCEPTABLE, IMMEDIATELY CONTACT SGH PROJECT MANAGER FOR
DIRECTION.
LIGHTING CIRCUITS UP TO 100'-0" IN LENGTH SHALL UTILIZE #12 CONDUCTORS
MINIMUM. LIGHTING CIRCUITS FROM 101'-0" TO 150'-0" IN LENGTH SHALL UTILIZE
#10 CONDUCTORS MINIMUM. LIGHTING CIRCUITS FROM 151'-0" TO 250'-0" IN
LENGTH SHALL UTILIZE #8 CONDUCTORS MINIMUM. LIGHTING CIRCUITS ABOVE
251'-0" IN LENGTH SHALL UTILIZE #6 CONDUCTORS MINIMUM.
LIGHTING SHALL BE CIRCUITED EXACTLY AS SHOWN ON PLANS. CIRCUITING SHALL
BE THRU-WIRING WHEREVER POSSIBLE. MULTIPLE CONNECTIONS TO A SINGLE
LIGHT FIXTURE FOR VOLTAGE DROP CONDITIONS OR AS A RESULT OF A FIELD
CONDITION ARE ACCEPTABLE. LIGHTING FIXTURES SHALL BE MANUFACTURED TO
ACCOMMODATE THRU-WIRING, ANY RELATED COSTS FOR MULTIPLE CONNECTIONS
SHALL BE INCLUDED IN BID.
CONTRACTOR'S BID SHALL INCLUDE THE INSTALLATION OF ALL LUMINAIRES AND
ASSOCIATED LAMPS FURNISHED BY SGH. CONTRACTOR IS RESPONSIBLE TO
ENSURE THE ADJUSTABILITY OF ALL DIRECTIONAL FIXTURES AFTER INSTALLATION
AND SHALL AIM THE FIXTURES PER DIRECTION FROM G.C. LIGHT FIXTURE
SPECIFICATIONS MAY VARY, IF THIS IS THE CASE, CONTRACTOR SHALL CALL THE
LIGHTING DISTRIBUTOR FOR EXACT SPECIFICATION OF LIGHTING FIXTURES. IF THE
CEILING SYSTEMS ARE FIRE RATED, CONTRACTOR SHALL CLOSELY COORDINATE
FIXTURE REQUIREMENTS WITH SGH.
EMERGENCY AND EXIT LUMINAIRES SHALL BE INSTALLED AND CIRCUITED PER LOCAL
AND LATEST NATIONAL ELECTRICAL CODES. ALL EMERGENCY AND EXIT FIXTURES
SHALL BE DUAL-VOLTAGE WITH BATTERY BACKUP (120/277 VOLT INPUT). INSTALL
A CENTRAL BATTERY SYSTEM WHERE THE USE OF INDIVIDUAL BATTERY UNITS ARE
PROHIBITED BY LOCAL CODES. IF PLAN LOCATION IS NOT ACCEPTABLE,
IMMEDIATELY CONTACT SGH PROJECT MANAGER FOR DIRECTION.
CONTRACTOR SHALL MAKE ALL FINAL CONNECTIONS AS REQUIRED FOR A FULLY
COMPLETE AND OPERABLE SYSTEM.
SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT LOCATION AND
QUANTITY OF LIGHTING FIXTURES.
CONTRACTOR IS RESPONSIBLE FOR ALL REFLECTED CEILING PLAN NOTES ON
ARCHITECTURAL DRAWINGS.
LOW VOLTAGE WIRING: THE GC IS RESPONSIBLE TO DETERMINE IF LOW VOLTAGE
WIRING IS REQUIRED BY EITHER LL OR BUILDING DEPARTMENT TO BE ENCASED IN
CONDUIT, IF SO, CONDUIT TO BE PROVIDED AND INSTALLED BY GC'S ELECTRICIAN.
REFER TO SHEET E-501 FOR SYMBOLS LEGEND.
REFER TO RESPONSIBILITY SCHEDULE ON SHEET G-002.
CONTRACTOR SHALL RELAMP ALL FIXTURES PRIOR TO STORE OPENING BUT NOT
DURING HEAVY CONSTRUCTION PERIOD.
E
E1
SCALE:
LA PLAZA MALL
1
LIGHTING FIXTURE SCHEDULE
D
11
TW12'-0"
C4W
STOCK
ROOM
6
101
AP
C4W
SALES
100
S
TC
NL/EM
C4W
C4W
9
SUNGLASS HUT
LA PLAZA MALL
2
2200 S. 10TH STREET
McALLEN, TX 78503
SPACE #Q14-C
2.0 TYPE: PREMIUM
TW10'-0"
A-6
RP
S
C
3 A-4
X1A
TW4'-0"
C4W
5
TW6'-0"
NL/EM
-
A3W
A3W A3W
10
(TYP)
MALL COMMON
AREA (N.I.C.)
1
C4W
A3W A3W A3W A3W
A3W A3W
4
12
B
A3W A3W
A-10
A3W
A3W
1
A3W A3W
5
A3W A3W A3W
A3W
A3W A3WA3WA3W A3W
A3W A3W A3W A3W A3WA3W A3W A3W
S
P:\SGH\150343 SGH-La Plaza Mall Mcallen, TX\E-102_06078.dwg
ADJACENT
TENANT
B3
PLOTTED: 7/16/2015 - 4:04 PM
C
S
S
C
(TYP)
USER: JGRAY
-
SPEAKER
(TYPICAL)
TW12'-0"
LAYOUT: E-102
ADJACENT
TENANT
A3W A3W A3W
S
C
A3W A3W A3W A3W A3W A3W
SGH STORE #: 6078
S
S
C
DRAWN BY: EDS
EM
A-12
A
REVIEWED BY: RAP
-
AUTHORIZED FOR:
ADJACENT
TENANT
A9
A1
SCALE:
LIGHTING PLAN
& LIGHTING LEGEND
PLAN NORTH
LIGHTING PLAN
1
SCALE:
2
3
4
5
6
7
8
E-102
NOT USED
9
10
11
12
13
14
2
3
4
5
6
7
8
9
10
11
12
13
ELECTRICAL SYMBOLS
IG
@ 16"
120 VOLT IG DUPLEX RECEPTACLE
@ 16"
120 VOLT DOUBLE DUPLEX (QUAD) RECEPTACLE
@ 16"
120 VOLT SIMPLEX RECEPTACLE
@ 16"
208V OR 120/208V RECEPTACLE
@ 16"
JUNCTION BOX
T
THERMOSTAT
SN
HVAC SENSOR
ZD
ZONE DAMPER
TELEPHONE OUTLET BOX
@ 16"
DATA OUTLET BOX
@ 16"
@ 16"
TELEPHONE OUTLET - FLOOR MOUNTED
DATA OUTLET BOX - FLOOR MOUNTED
DATA/TELEPHONE - FLOOR MOUNTED
VC
WALL MOUNTED VOLUME CONTROL
@ 48"
VS
WALL MOUNTED VARIABLE SPEED CONTROLLER
@ 48"
K
KEYPAD
P
TC
TRAFFIC COUNTER
AP
WIRELESS ACCESS POINT
FABP
FIRE ALARM BOOSTER PANEL
FAAP
FIRE ALARM ANNUNCIATOR PANEL (REMOTE)
S
CEILING MOUNTED PHOTO/IONIZATION DETECTOR
H
CEILING MOUNTED HEAT DETECTOR
S
PHOTO/IONIZATION DETECTOR-DUCT MOUNTED
V
ALARM HORN WITH VISUAL INDICATOR
V
VISUAL ALARM INDICATOR WITH NO HORN
B
ALARM BELL
S
FIRE ALARM SPEAKER WITH VISUAL INDICATOR
S
FIRE ALARM SPEAKER
F
MANUAL PULL STATION
PS
PRESSURE SWITCH
TS
TAMPER SWITCH
R
FIRE ALARM RELAY
FA
FIRE ALARM JUNCTION BOX
D
H
MAGNETIC DOOR HOLDER-WALL OR FLOOR
MOUNTED AS INDICATED
PUSHBUTTON
G
GLASS BREAK SENSOR
WALL SWITCH - NUMBER INDICATES 2, 3 OR 4
POLE; LETTER INDICATES FIXTURE(S) TO BE
CONTROLLED BY SWITCH
S
C
SECURITY CAMERA
@ 48"
S
CEILING MOUNTED SPEAKER
O
S
OCCUPANCY SENSOR
@ 48"
O
S
OCCUPANCY SENSOR - CEILING MOUNTED
DOUBLE REMOTE HEAD
DS
DAYLIGHT SENSOR
TRACK HEAD
DD
DIMMING SENSOR
WALL MOUNTED FIXTURE
V
VACANCY SENSOR
EM/NL WALL MOUNTED FIXTURE
CURRENT LIMITER - NUMBER INDICATES AMPERAGE
OF BREAKER
RECESSED CAN LIGHT
TS
TIMER SWITCH
@ 48"
D
DIMMER SWITCH
@ 48"
@ 80"
SEAL
DEDICATED QUAD
RECEPTACLE
1.
F6
SCALE:
CEILING MOUNTED EXIT SIGN
F11
NOT USED
SCALE:
MAGNETIC COMBINATION MOTOR STARTER OR
CONTACTOR DISCONNECT SWITCH
WALL MOUNTED EMERGENCY LIGHT
C
E
R
CEILING MOUNTED
EXISTING
RELOCATED
S
LAYOUT: E-501
P:\SGH\150343 SGH-La Plaza Mall Mcallen, TX\E-501_06078.dwg
PLOTTED: 7/16/2015 - 4:04 PM
USER: JGRAY
AWG
B
C
BREAKER
BUILDING
BUILDING MANAGEMENT SYSTEM
C
CONDUIT
CABLE TELEVISION SYSTEM
CLOSED CIRCUIT TELEVISION
CIRCUIT
CEILING
HEATER
HEATING, VENTILATING & A/C
HERTZ
KILOVOLT-AMPS
KILOWATTS
KILOWATT-HOUR
MAX
MCA
MCB
MH
MIN
MOCP
dB
DECIBEL
DIA (OR Ø) DIAMETER
DISC
DISCONNECT
DN
DOWN
DWG
DRAWING
DPST
DOUBLE POLE SINGLE THROW
ETR
EWC
EXH
EX, EXIST
LOCKED ROTOR AMPS
LIGHTING
M
MTD
MAXIMUM
MINIMUM CIRCUIT AMPACITY
MAIN CIRCUIT BREAKER
MANHOLE, METAL HALIDE
MINIMUM
MAXIMUM OVER CURRENT
PROTECTION
MOUNTED
N/A
NEC
NEMA
NFPA
NIC
N.O.
NTS
EXISTING TO REMAIN
ELECTRICAL WATER COOLER
EXHAUST
EXISTING
F
OC
OSHA
P
PF
PH
PVC
SCALE:
REFLECTED CEILING PLAN,
REVISION, REVISE
REMOVE EXISTING
RUNNING LOAD AMPS
ROOM
NOT APPLICABLE
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL MFR'S ASSOC.
NATIONAL FIRE PROTECTION ASSOC.
NOT IN CONTRACT
NORMALLY OPEN
NOT TO SCALE
NOT USED
1
DVD-R
QUADRUPLEX
RECEPTACLE
SQUARE FEET, SQUARE FOOT
SINGLE POLE SINGLE THROW
THROUGH
TYPICAL
U
UL
UON
UPS
V
VA
MONITOR
UNDERWRITERS LABORATORIES, INC.
UNLESS OTHERWISE NOTED
UNINTERRUPTABLE POWER SUPPLY
1.
CAMERA
(QUANTITY
ON PLAN)
VOLT
VOLT-AMPERE
WATT
FIRE ALARM
FIRE ALARM CONTROL PANEL
FULL LOAD AMPS
FOOT, FEET
REFER TO ARCH DETAILS
ON SHEET A-502 AND
RESPONSIBILITY SCHEDULE
ON SHEET G-002 FOR
ADDITIONAL INFORMATION.
EXTEND CABLE TO PROPOSED HEAD END EQUIPMENT
LOCATION. PROVIDE ENOUGH EXCESS CABLE TO
REACH ANY WALL IN BACK ROOM. COIL AND MARK
CABLE AS CCTV. HEAD END EQUIPMENT LOCATION
MUST BE WITHIN 10' OF THE 'NETWORK SWITCH
ACCESS'.
W
W
2.
FOR CAMERAS, PROVIDE WHITE PLENUM RATED CAT 6
CABLING. COIL 5' OF CABLING AT EACH CAMERA
LOCATION FOR CONNECTIONS.
3.
PROVIDE RJ-45 CONNECTORS AT CAMERA LOCATIONS
ONLY. CONNECTORS NOT NEEDED AT THE HEAD END
EQUIPMENT LOCATION.
A6
ABBREVIATIONS AND SYMBOLS
1
2
SCALE:
3
4
5
FURNISH AND INSTALL
ANNUNCIATING DEVICES,
SEE SHEET E-101 FOR
LOCATION AND QUANTITY.
GENERAL
SALES (a)
(SPST)
DISPLAY CASE
RECEPTACLES (c)
(SPST)
NOTE:
GENERAL CONTRACTOR TO
LABEL LIGHT SWITCHES.
POWER CONTACTOR AND TC1 FROM CIRCUIT A-15
CONTACTOR CONTROLLED BY TIMECLOCK
A-4
SPARE
SPARE
SPARE
C2
6
SEE SHEET E-101 FOR ACTUAL NUMBER OF DEVICES, AND ADDITIONAL NOTES.
ALL MATERIALS SHALL BE NEW AND BEAR UL LABELS.
SUPPLY SHOP DRAWINGS FOR FIRE ALARM SYSTEM TO LOCAL AUTHORITY FOR
APPROVAL PRIOR TO INSTALLATION.
4. FURNISH AND INSTALL ALL LABOR AND MATERIALS REQUIRED FOR A COMPLETE
INSTALLATION AS INDICATED.
5. ALL WORK SHALL COMPLY WITH THE REQUIREMENTS OF NEC, NFPA, STATE AND
LOCAL CODES.
1.
SALES
SALES
SALES
SALES
SALES
SALES
TRACK LIGHTS
AREA DISPLAY CASES
AREA DISPLAY CASES
AREA DISPLAY CASES
AREA DISPLAY CASES
AREA DISPLAY CASES
SUNGLASS HUT
LA PLAZA MALL
NOTES:
 ALL CONTACTORS ARE NORMALLY OPEN,
ELECTRICALLY HELD CLOSED, WITH THE
NUMBER OF POLES AS SHOWN.
 SUPPLY POWER TO CONTACTORS THRU
A-15 IN ALL CASES.
 LOCATE CONTACTORS AND TIME CLOCK
ADJACENT TO PANEL 'A'.
UPON ALARM SIGNAL FROM ANY INITIATING DEVICE THE FIRE ALARM PANEL SHALL:
A. INITIATE AN ALARM SIGNAL AT TENANT'S PANEL AND LANDLORD'S MAIN FIRE
ALARM SYSTEM.
B. SHUT DOWN TENANT'S HVAC SYSTEM (IF APPLICABLE)
C. INITIATE MALL'S AND TENANT'S HORN/STROBES.
D. ACTIVATE THE TENANT ZONE SMOKE CONTROL EXHAUST SYSTEM AND THE
MALL OUTSIDE AIR SUPPLY. (IF APPLICABLE)
E. NOTIFY LOCAL FIRE DEPARTMENT OF FIRE EMERGENCY LOCATION.
2200 S. 10TH STREET
McALLEN, TX 78503
SPACE #Q14-C
2.0 TYPE: PREMIUM
SGH STORE #: 6078
DRAWN BY: EDS
REVIEWED BY: KAH
AUTHORIZED FOR:
ELECTRICAL DETAILS
& ABBREVIATIONS
SCALE:
7
A-6
A-14
A-16
A-18
A-20
A-22
SPARE
SPARE
1.
2.
3.
A8
CCTV SYSTEM
STOREFRONT SIGN
POWER CONTACTOR FROM CIRCUIT
A-15 THRU SWITCH 'c'
3
T
THRU
TYP
V
'C2'
2
S
SF
SPST
V
GENERAL CONTRACTOR SHALL CONTRACT
WITH MALL APPROVED FIRE ALARM
CONTRACTOR 'GLOBAL RISK
CONSULTANT'S' FOR FINAL CONNECTION
TO LANDLORD'S MAIN FIRE ALARM
SYSTEM. VERIFY EXACT LOCATION AND
REQUIREMENTS WITH MALL OPERATIONS
MANAGER.
R
RCP
REV
REX
RLA
RM
J
A-10
C1
D6
POWER FACTOR
PHASE
POLYVINYL CHLORIDE
A1
SCALE:
FIRE ALARM JUNCTION BOX.
SEE SHEET E-101 FOR
LOCATION AND ADDITIONAL
NOTES
ON CENTER
OCCUPATIONAL SAFETY &HEALTH
ADMIN.
V
N
E
A
KVA
KW
KWH
LRA
LTG
D
FA
FACP
FLA
FT
H
L
C
CATV
CCTV
CKT
CLG
B
GAS, GROUND
GENERAL CONTRACTOR
GROUND FAULT INTERRUPTER
GROUND
K
BKR
BLDG
BMS
CHECK LENGTH OF SCREWS BEFORE ATTACHING
OUTLETS TO MILLWORK. VERIFY SCREWS ARE NOT
TOO LONG, SO AS NOT TO DAMAGE OTHER SIDE OF
CASHWRAP WHEN SCREWS ARE TIGHTENED.
1 REGISTER
CASHWRAP ELEVATION
FURNISH AND INSTALL DUCT MOUNTED
SMOKE DETECTORS FOR HVAC
EQUIPMENT AND TIE INTO TENANT'S FIRE
ALARM SYSTEM.
O
G
HTR
HVAC
HZ
ONE (1) 1-1/4" DIA. RIGID CONDUIT FOR
TELE/DATA STUBBED BELOW CASHWRAP
BASE. PROVIDE 2 CAT6 CABLES.
MASTER LIGHTING SWITCH BANK
ABBREVIATIONS
D
ONE (1) 1" DIA. RIGID CONDUIT FOR
POWER STUBBED BELOW CASHWRAP
BASE (FRAME WARMER)
ONE (1) 1" DIA. RIGID CONDUIT FOR
POWER (IG) STUBBED BELOW CASHWRAP
BASE (1 CIRCUIT)
WALL MOUNTED EXIT SIGN
REMOTE EMERGENCY POWER PACK
G
GC
GFI, GFCI
GRND
CKT#1
GENERAL DETAIL NOTES:
EQUIPMENT DISCONNECT SWITCH
ABOVE FINISHED CEILING
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AMPERES
AMERICAN NAT'L STANDARDS INST.
ARCHITECT, ARCHITECTURAL
AMERICAN SOCIETY OF HEATING,
REFRIGERATION & AC ENGINEERS
AMERICAN WIRE GAUGE
DEDICATED QUAD
RECEPTACLE
DEVICE LOCATIONS
EM/NL RECESSED CAN LIGHT
NON-MAGNETIC MANUAL MOTOR STARTER
AFC
AFF
AFG
AMP
ANSI
ARCH
ASHRAE
CKT#2
CUT HOLES AS REQUIRED
AT REAR OF BASE FOR
FLEX CONDUIT
MOTION DETECTOR
COMBINATION EMERGENCY AND EXIT LIGHT
A
DEDICATED DUPLEX RECEPTACLE
J J J
THREE PHASE MOTOR
MAGNETIC STARTER OR CONTACTOR
@ 80"
SINGLE REMOTE HEAD
SINGLE PHASE MOTOR
E
Shremshock Engineering, Inc.
7400 W. Campus Rd. Suite 150 New Albany, OH 43054
t: 614 545 4550 | f: 614 545 4555 | shremshock.com
TX Registration Number: #F-9566
BURGULAR SYSTEM PANEL
DOOR CONTACT
S
OPEN
CONSULTANT PROJECT # 150343
DATA OUTLET
DC
XX
TRASH
CKT#1
CHIME/BELL TRANSFORMER
B
JUNCTION BOXES IN
CASHWRAP SHALL BE
PRE-INSTALLED BY THE
MILLWORK MANUFACTURER
SUPPLIES
PRINTER
DATA OUTLET
WATER FLOW SWITCH
D
BAGS
@ 60"
@ 48"
WF
BURG
A Subsidiary of the Luxottica Group
4000 Luxottica Place
Mason, Ohio 45040
EQUIPMENT LOCATIONS
M
S
TELEPHONE
FRAME WARMER
CASH
DRAWER
REMOTE ANNUNCIATOR/TEST STATION
CHIME/BELL
G
F
FIRE ALARM CONTROL PANEL
ALARM HORN
DATA/TELEPHONE OUTLET BOX
H
FACP
A
120 VOLT DUPLEX RECEPTACLE FLOOR MOUNTED
J
RECEIPT PRINTER
MONITOR
TRANSFORMER (XFMR)
120 VOLT DUPLEX RECEPTACLE
CEILING MOUNTED
SF = STOREFRONT
J
LIGHTING/POWER PANELBOARD
AT
K
120 VOLT DUPLEX RECEPTACLE
WP = WEATHERPROOF
GFI = GROUND FAULT INTERRUPTER
14
LA PLAZA MALL
1
A11
FIRE ALARM SYSTEM
8
9
SCALE:
10
E- 501
LIGHTING CONTROL DIAGRAM
11
12
13
14
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A Subsidiary of the Luxottica Group
4000 Luxottica Place
Mason, Ohio 45040
K
CONSULTANT PROJECT # 150343
MECHANICAL EQUIPMENT FEEDER/CONNECTION SCHEDULE
J
FEEDERS
ITEM
VOLTAGE
HP
KW
M.C.A.
(E)RTU
208V
3PH
---
---
30.0
WIRE
COND
3#10
THHN
1#10 G
3/4"
Shremshock Engineering, Inc.
TYPE OF
CONN
DISC
SW
BRANCH
BREAKER
REMARKS
THRU DISC.
SWITCH
30A
30A-3P
SEE
NOTE #1
7400 W. Campus Rd. Suite 150 New Albany, OH 43054
t: 614 545 4550 | f: 614 545 4555 | shremshock.com
TX Registration Number: #F-9566
NOTE:
1. EXISTING WITH UNIT.
2. DISCONNECT IS TO BE FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR
SEAL
H
G
G1
F
LANDLORD
EXISTING
NEW
TENANT
LANDLORD PROVIDE 1-1/4 "C.
FIELD VERIFY PRIOR TO BID.
AT
GENERAL CONTRACTOR TO PROVIDE
J-BOX AS REQUIRED TO EXTEND
1-1/4" C. TO PANEL BOARD.
E
GENERAL CONTRACTOR TO PROVIDE
4#4 THHN AND 1#8 GROUND AND
#8 ISOLATED GROUND IN 1-1/4"C.
FROM PANEL TO SWITCHBOARD.
USER: JGRAY
PLOTTED: 7/16/2015 - 4:04 PM
P:\SGH\150343 SGH-La Plaza Mall Mcallen, TX\E-601_06078.dwg
LAYOUT: E-601
EXISTING ELECTRICAL
METER TO REMAIN AS IS.
COORDINATE WITH
LANDLORD'S
REPRESENTATIVE AND
LOCAL UTILITY COMPANY.
PANEL 'A'
120/208V
3PH, 4W
100A MCB
42 CKT
EXISTING 100A FUSED
DISCONNECT TO
REMAIN. IF NOT IN
GOOD CONDITIONS
GENERAL CONTRACTOR
TO PROVIDE NEW 100A
DISCONNECT SWITCH.
PROVIDE WITH (3) 70A
REPLACEMENT FUSES.
D
LA PLAZA MALL
EQUIPMENT SCHEDULES
LEASE LINE
SCALE:
C-1 C-2
ZONE ZONE
"SF" "C"
TC
FINISH FLOOR
APPROX. DISTANCE
30'-0"
C
1.
2.
3.
4.
B
5.
6.
7.
8.
9.
10.
HVAC CIRCUIT BREAKERS TO BE "HACR" TYPE WHERE REQUIRED BY EQUIPMENT NAMEPLATE PER N.E.C.
TENANTS ELECTRICAL CONTRACTOR SHALL FIELD VERIFY EXACT K.A.I.C. RATING OF LANDLORD'S DISTRIBUTION
EQUIPMENT. FURNISH AND INSTALL TENANTS ELECTRICAL SYSTEM TO MATCH.
ELECTRICAL CONTRACTOR SHALL BALANCE ALL PANELS AND ELECTRICAL EQUIPMENT, UNDER LOAD CONDITIONS,
TO ±7% BETWEEN PHASES: A/B, B/C, A/C REGARDLESS OF CIRCUITING INDICATED.
ELECTRICAL CONTRACTOR SHALL MAINTAIN PROPER CLEARANCE FOR ELECTRICAL EQUIPMENT PER N.E.C.
ARTICLE 110.26. FIELD VERIFY EXACT MOUNTING SPACE AVAILABLE IN ELECTRICAL ROOM/ AREA PRIOR TO
INSTALLATION OF ELECTRICAL EQUIPMENT.
ELECTRICAL CONTRACTOR SHALL MAKE ALL FINAL ELECTRICAL CONNECTIONS FOR A COMPLETE ELECTRICAL
DISTRIBUTION SYSTEM.
TENANT'S NAME AND SPACE SHALL BE ENGRAVED ON A BAKELITE PLATE WITH 1" HIGH LETTERS. SCREW FASTEN
TO THE METER SOCKET AND DISCONNECT SWITCH AT THE SERVICE DISTRIBUTION POINT.
ALL CONNECTIONS TO LANDLORD'S SERVICE EQUIPMENT SHALL BE AS DIRECTED BY LANDLORD'S SITE
REPRESENTATIVE. TENANT ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL TERMINATION EXPENSES.
SYSTEM SHALL BE GROUNDED TO THE MAIN BUILDING'S GROUNDING SYSTEM.
ELECTRICAL CONTRACTOR SHALL INCLUDE IN BID ALL WORK AND MODIFICATIONS REQUIRED TO COMPLY WITH
LANDLORDS TENANT CRITERIA, ENERGY CODES, NATIONAL, STATE AND LOCAL CODES.
ALL EQUIPMENT TO BE SUPPLIED AND INSTALLED PER RESPONSIBILITY SCHEDULE AS SHOWN ON THIS SHEET.
SUNGLASS HUT
LA PLAZA MALL
2200 S. 10TH STREET
McALLEN, TX 78503
SPACE #Q14-C
2.0 TYPE: PREMIUM
SGH STORE #: 6078
DRAWN BY: EDS
REVIEWED BY: KAH
AUTHORIZED FOR:
ELECTRICAL SINGLE LINE
DIAGRAM AND PANEL
SCHEDULES
A
A9
A1
SCALE:
ELECTRICAL SINGLE LINE DIAGRAM
1
2
3
SCALE:
4
5
6
7
8
E-601
PANEL SCHEDULES AND LOAD SUMMARY
9
10
11
12
13
14
3
4
P.
26 05 00 COMMON WORK RESULTS FOR ELECTRICAL
A.
THE FOLLOWING TERMS SHALL APPLY TO ALL WORK DONE UNDER THIS CONTRACT:
1.
K
2.
3.
4.
5.
J
6.
B.
10.
11.
G
12.
13.
C.
F
E
USER: JGRAY
PLOTTED: 7/16/2015 - 4:04 PM
P:\SGH\150343 SGH-La Plaza Mall Mcallen, TX\E-701_06078.dwg
LAYOUT: E-701 (208v)
E.
ELECTRICAL EQUIPMENT FURNISHED BY OTHER TRADES OR BY TENANT AND SPECIFIED IN OR SHOWN ON
CONTRACT DOCUMENTS SHALL BE INSTALLED AND CONNECTED BY GENERAL CONTRACTOR, EXCEPT AS
OTHERWISE NOTED. PROVIDE BRANCH CIRCUIT CONNECTIONS TO ELECTRICALLY OPERATED EQUIPMENT
FURNISHED BY OTHERS AS SPECIFIED IN OR SHOWN ON THE CONTRACT DOCUMENTS. TEMPORARY
WIRING FOR OTHER CONTRACTORS SHALL BE INSTALLED BY THE GENERAL CONTRACTOR WHO SHALL BE
ENTIRELY RESPONSIBLE TO THE TENANT FOR THE SAFE AND SATISFACTORY OPERATION OF SAID
TEMPORARY WIRING. CONTRACTOR REQUIRING SUCH TEMPORARY WIRING SHALL PAY FOR ALL DAMAGE
TO PROPERTY RESULTING FROM ITS USE. COMPLY WITH LATEST REQUIREMENTS OF OCCUPATIONAL
SAFETY AND HEALTH ACT (OSHA). PROVIDE PERSONNEL GROUND FAULT PROTECTION ON ALL TEMPORARY
POWER AND LIGHTING CIRCUITS 30 AMPERES OR LESS. GROUND FAULT CIRCUIT INTERRUPTERS ON
CONSTRUCTION CIRCUITS ARE NOT REQUIRED WHERE CIRCUIT IS A PERMANENT CIRCUIT TO BE A PART
OF THE COMPLETED BUILDING. HOWEVER, CONTRACTOR SHALL PROVIDE APPROVED CORD SETS
INCORPORATING GFCI PROTECTION FOR PERSONNEL. SEE THE LOCALLY ADOPTED EDITION OF THE N.E.C.
ALL FINISH PAINTING IS TO BE PERFORMED BY GENERAL CONTRACTOR EXCEPT THAT THIS CONTRACTOR
SHALL RESTORE TO ORIGINAL CONDITION ANY PAINTING DEFACED BY THIS CONTRACTOR AFTER ORIGINAL
PAINTING.
ANY ACCESS PANELS REQUIRED, BUT NOT SPECIFIED OR SHOWN ON DRAWINGS, SHALL BE FURNISHED
BY GENERAL CONTRACTOR WITH DESIGN TO BE APPROVED BY ARCHITECT BEFORE STARTING
INSTALLATION.
H.
THE DRAWINGS AND SPECIFICATIONS ARE INTENDED TO SUPPLEMENT EACH OTHER AND ANY MATERIAL
OR LABOR CALLED FOR IN ONE SHALL BE PROVIDED EVEN THOUGH NOT SPECIFICALLY MENTIONED IN
BOTH. ANY MATERIAL OR LABOR WHICH IS NEITHER SHOWN ON THE DRAWINGS NOR CALLED FOR IN THE
SPECIFICATIONS, BUT WHICH IS NECESSARY TO COMPLETE THE WORK OR WHICH IS USUALLY INCLUDED
IN WORK OF SIMILAR CHARACTER, SHALL BE PROVIDED AS PART OF CONTRACT.
5.
6.
7.
K.
B
L.
O.
WHERE TRADE NAMES AND MANUFACTURERS ARE USED ON THE DRAWINGS OR IN THE SPECIFICATIONS,
THE EXACT EQUIPMENT SHALL BE USED AS A MINIMUM FOR THE BASE BID. MANUFACTURERS
CONSIDERED AS AN EQUAL OR BETTER IN ALL ASPECTS TO THAT SPECIFIED WILL BE SUBJECT TO
APPROVAL IN WRITING, THROUGH SHOP DRAWING SUBMITTAL PROCESS, BY TENANT'S CONSTRUCTION
MANAGER PRIOR TO ACCEPTANCE. THE USE OF ANY UNAUTHORIZED EQUIPMENT SHALL BE SUBJECT TO
REMOVAL AND REPLACEMENT AT THE CONTRACTOR'S EXPENSE.
1
2
3
THIS CONTRACTOR SHALL INCLUDE, AND WILL BE HELD RESPONSIBLE FOR, THE REMOVAL OF ALL
EXISTING CONDUIT, FIRE ALARM SYSTEM, SWITCH GEAR, PITCH POCKETS AND EQUIPMENT, ETC. UNLESS
SPECIFICALLY NOTED OTHERWISE. CONTRACTOR MUST VERIFY WITH THE LANDLORD ALL PRESUMED
ABANDONED EQUIPMENT, CONDUIT AND SWITCH GEAR PRIOR TO REMOVAL. PITCH POCKETS SHALL BE
REMOVED AND THE ROOF PATCHED, AS REQUIRED BY THE LANDLORD. ALL EXTRANEOUS ITEMS IN THE
SPACE OR ON THE ROOF NOT APPLICABLE TO THE NEW WORK MUST BE REMOVED AND
ROOF/WALL/FLOOR PATCHED/REPAIRED TO LIKE NEW CONDITION. EXISTING ABANDONED CONDUIT OR
EQUIPMENT IN THE FLOOR, EMBEDDED IN CONCRETE, OR OTHERWISE INACCESSIBLE, ARE TO BE CUT OFF
AND SEALED BELOW OR WITHIN FLOOR OR WALL LEVEL WHEN THEY ARE NOT TO BE REUSED IN THIS
PROJECT. IF REQUIRED BY LANDLORD OR CODES, ABANDONED CONDUIT MUST BE REMOVED TO POINT
OF ORIGIN. CONFIRM EXTENT OF DEMOLITION PRIOR TO BID AND INCLUDE IN PROPOSAL.
U.
ALL SLEEVES AND OPENINGS THROUGH FIRE RATED WALLS AND/OR FLOORS SHALL BE FIRE SEALED WITH
CALCIUM SILICATE, SILICONE "RTV" FOAM, "3M" FIRE RATED SEALANTS OR EQUAL, SO AS TO RETAIN
THEIR FIRE RATING.
V.
SLEEVES IN BEARING AND MASONRY WALLS, FLOORS AND PARTITIONS SHALL BE STANDARD WEIGHT
STEEL PIPE FINISHED WITH SMOOTH EDGES. FOR OTHER THAN MASONRY PARTITIONS, THROUGH
SUSPENDED CEILINGS, OR FOR CONCEALED VERTICAL CONDUIT, SLEEVES SHALL BE NO. 22 U.S.G.
GALVANIZED STEEL MINIMUM.
W.
HANGERS SHALL INCLUDE ALL MISCELLANEOUS STEEL SUCH AS ANGLE IRON, WIRE, UNISTRUT, C-CLAMPS
WITH RETAINING CLIPS, CHANNELS, HANGER RODS, ETC., NECESSARY FOR THE INSTALLATION OF WORK.
X.
HANGERS SHALL BE FASTENED TO BUILDING STEEL, CONCRETE, OR MASONRY, BUT NOT TO OTHER
CONDUIT OR PIPING. HANGERS UPPER ATTACHMENT MUST BE SUPPORTED FROM THE TOP OF THE BAR
JOIST. HANGING FROM METAL DECK IS NOT PERMITTED. WHERE INTERFERENCES OCCUR, IN ORDER TO
SUPPORT CONDUIT, THE CONTRACTOR MUST INSTALL TRAPEZE TYPE HANGERS OR SUPPORTS WHICH
SHALL BE LOCATED WHERE THEY DO NOT INTERFERE WITH ACCESS TO FIRE DAMPERS, VALVES, JUNCTION
BOXES, ACCESS DOORS, OTHER EQUIPMENT SERVICE REQUIREMENTS AND/OR OTHER TRADES. HANGER
TYPES AND INSTALLATION METHODS ARE SUBJECT TO LANDLORD CRITERIA.
Y.
UPON COMPLETION OF THE WORK, GENERAL CONTRACTOR SHALL FURNISH TO THE ARCHITECT A
CERTIFICATE OF INSPECTION AND APPROVAL FROM THE ABOVE DEPARTMENT BEFORE FINAL PAYMENT ON
CONTRACT WILL BE ALLOWED.
Z.
TEST ALL WIRING AND CONNECTIONS FOR CONTINUITY AND GROUNDS BEFORE ANY EQUIPMENT IS
CONNECTED. WHEN DIRECTED BY ARCHITECT, DEMONSTRATE BY PROPER VOLTAGE MEGGER TEST OF
INSULATION RESISTANCE OF ANY CONDUCTORS AND REPLACE ALL CONDUCTORS WHICH FAIL SAID TESTS
UNTIL ALL CONDUCTORS ARE FREE FROM INSULATION FAULTS.
AG. GENERAL CONTRACTOR SHALL SUBMIT SHOP DRAWINGS PER THE DOCUMENTS PROVIDED BY THE
TENANT.
AH. MANUFACTURER'S CATALOG CUTS MAY BE SUBMITTED FOR STANDARD CATALOG LIGHTING FIXTURES
AND OTHER EQUIPMENT. CATALOG CUTS MAY BE MARKED UP TO MEET THE PROJECT SPECIFICATIONS.
CUTS SHALL BE MARKED TO INDICATE MODEL NUMBER, SIZE, TYPE, COLOR, RATING, ETC., OF THE ITEM
TO BE FURNISHED.
AI.
AK. SHOULD DEFECTS DEVELOP WITHIN GUARANTEE PERIOD, GENERAL CONTRACTOR SHALL, UPON NOTICE
OF SAME, REMEDY SUCH DEFECTS AND HAVE DAMAGES TO OTHER WORK OR FURNISHINGS CAUSED BY
DEFECTS OR WORK OR CORRECTIONS TO SAME REPAIRED AND/OR REPLACED AT THIS EXPENSE TO
CONDITION BEFORE SUCH DEFECTS OR DAMAGE.
4
5
6
7
10
11
G.
1.
2.
3.
4.
5.
TITLE PAGE: TITLE OF JOB, LANDLORD, OWNER ADDRESS, DATE OF SUBMISSION, CONTRACTOR,
AND ENGINEER.
INDEX
LIST OF MAJOR EQUIPMENT USED IN PROJECT ACCOMPANIED BY CONTRACTOR PURCHASE ORDER
NUMBERS AND SUPPLIERS' NAMES AND ADDRESSES.
H.
ONE COPY OF EACH SHOP DRAWING GROUPED BY TYPES OF EQUIPMENT, I.E., LIGHTING FIXTURES,
PANELBOARDS, ETC.
SECTION FOR EACH SYSTEM, INCLUDING:
a. BRIEF DESCRIPTION OF SYSTEM OPERATION WITH LOCATION OF MAJOR COMPONENTS.
b. LIST OF ITEMS IN SYSTEM REQUIRING PERIODIC SERVICE. REQUIRES SEPARATE SECTION FOR
EACH OF: ELECTRICAL DISTRIBUTION SYSTEM FROM THE SERVICE ENTRANCE TO EACH LIGHTING
AND POWER PANEL AND OTHER SYSTEMS (I.E. CONTROL SYSTEMS AND ANY OTHER GENERAL
I.
CONTRACTOR SYSTEM LISTED IN THESE SPECIFICATIONS.)
AM. OWNER SHALL PROVIDE A COMPLETE 12-MONTH WARRANTY FOR ALL PARTS ON EQUIPMENT PROVIDED
BY TENANT AND TENANT'S VENDORS. THIS CONTRACTOR SHALL NOT BEAR ADDITIONAL WARRANTIES
BEYOND A COMPLETE WORKING SYSTEM, AND AS SUCH, NO ADDITIONAL MONIES SHOULD BE INCLUDED
J.
IN THE BID.
AN. AT THE END OF THE PROJECT, THIS CONTRACTOR SHALL CLEAN ALL EQUIPMENT, INCLUDING LIGHT
FIXTURES, TO THE SATISFACTION OF OWNER. ALL DUST, DIRT, DEBRIS, PAINT AND FOREIGN MATTER
SHALL BE REMOVED FROM ALL EQUIPMENT.
26 05 19 LOW VOLTAGE ELECTRICAL POWER CONDUCTORS
A.
SWITCHES SHALL BE QUICK-MAKE, QUICK-BREAK. THE OPERATING HANDLE SHALL BE AN INTEGRAL
PART OF THE BOX, NOT THE COVER. PROVISIONS FOR PADLOCKING THE SWITCH IN THE "OFF"
POSITION WITH AT LEAST THREE LOCKS SHALL BE PROVIDED. SWITCHES SHALL HAVE A DUAL
COVER INTERLOCK TO PREVENT UNAUTHORIZED OPENING OF THE SWITCH DOOR WHEN THE
HANDLE IS IN THE "ON" POSITION, AND TO PREVENT CLOSING OF THE SWITCH MECHANISM WITH
THE DOOR OPEN. THE HANDLE POSITION SHALL INDICATE WHETHER THE SWITCH IS "ON" OR "OFF".
SWITCHES SHALL BE FURNISHED IN NEMA 1 GENERAL PURPOSE ENCLOSURE EXCEPT ALL
SWITCHES LOCATED OUTDOORS SHALL BE NEMA 3R WEATHERPROOF (WP). NEMA 3R ENCLOSURE
SHALL BE MANUFACTURED FROM GALVANIZED STEEL. ENCLOSURES SHALL HAVE A GRAY BAKED
ENAMEL FINISH, ELECTRODEPOSITED, ON CLEANED, PHOSPHATIZED STEEL.
L.
ALL FUSES SHALL BE BUSSMANN, SIZES AS NOTED ON DRAWINGS.
M.
ALL FUSES SHALL BE UL LISTED, CURRENT-LIMITING TYPE, MINIMUM 200,000 AMPS
INTERRUPTING CAPACITY.
N.
FUSES 1 AMP AND ABOVE SHALL BE BUSSMANN "LOW PEAK" RK-1. 250 VOLT FUSES SHALL BE
USED ON 208/120 VOLT SYSTEMS.
R.
FURNISH AND INSTALL CIRCUIT BREAKER TYPE POWER, HEATING AND LIGHTING PANELBOARD AS
SHOWN ON THE DRAWINGS.
CONDUCTORS MAY BE STRANDED FOR SIZES #10 AWG AND LARGER. CONDUCTORS SIZE
#12 AND SMALLER SHALL BE SOLID (NOT STRANDED).
S.
PANELBOARD SHALL BE LISTED UNDER UL 67 AND SHALL HAVE APPROPRIATE LABELING. ALL
BUSSING SHALL BE SOLID COPPER.
ON ALL 20 AMP BRANCH CIRCUITS, CONDUCTORS LARGER THAN #10 AWG SHALL BE REDUCED
TO #10 AWG WITHIN 10 FEET OF PANELBOARD AND DEVICES IN JUNCTION BOXES ON RATED
TERMINAL STRIPS.
T.
PANELBOARD FOR USE ON 208Y/120V VOLT SYSTEM SHALL HAVE A MINIMUM INTEGRATED
EQUIPMENT SHORT CIRCUIT CURRENT RATING OF 10,000 AMPS RMS SYMMETRICAL. EXACT
RATING SHALL BE DETERMINED BY AVAILABLE FAULT CURRENT FROM UTILITY. GENERAL
CONTRACTOR SHALL FURNISH PANELS BASED ON UTILITY COMPANY INFORMATION. ALL LUG
CONNECTIONS SHALL BE 75 DEGREE RATED.
U.
PANELBOARD FRONT ASSEMBLY SHALL INCLUDE A HINGED DOOR WITH A FLUSH MOUNTED
CYLINDER LOCK TYPE SPRING LOADED LATCH. ALL LOCKS SHALL BE KEYED ALIKE. DOOR SHALL
INCLUDE A TYPED CIRCUIT DIRECTORY CARD MOUNTED IN A FRAME WITH A CLEAR PLASTIC
PROTECTIVE COVER.
V.
PANELBOARD SHALL HAVE A FULL CAPACITY SOLID COPPER NEUTRAL SUBASSEMBLY.
W.
PANELBOARD SHALL INCLUDE A SOLID COPPER GROUND BUS SUBASSEMBLY, SIMILAR IN
CONSTRUCTION TO THE NEUTRAL SUBASSEMBLY, FACTORY MOUNTED AND BONDED TO THE BOX.
X.
PANELBOARD SHALL INCLUDE (WHERE SPECIFIED) A SOLID COPPER ISOLATED GROUND BUS
SUBASSEMBLY, SIMILAR IN CONSTRUCTION TO THE NEUTRAL SUBASSEMBLY, FACTORY SUPPLIED
FIELD INSTALLED.
Y.
INTERIOR LABELING SHALL INCLUDE A CONNECTION DIAGRAM AND LABELS INDICATING PROPER
TORQUE AND WIRE TYPES FOR MAIN INPUT CONNECTIONS AND BOTH LINE AND LOAD SIDE
CIRCUIT BREAKER CONNECTIONS.
Z.
CIRCUIT BREAKERS SHALL BE QUICK MAKE, QUICK BREAK, THERMAL MAGNETIC TRIP (ENCLOSURE
COMPENSATED), MOLDED CASE TYPE, UL LISTED. 15 AND 20 AMP SINGLE POLE BREAKERS SHALL
CARRY THE UL "SWD" MARKING. LINE SIDE TERMINALS SHALL BE BOLTED TO MAIN BUSBARS.
BREAKER RATINGS SHALL BE PER DRAWINGS.
PHASE A
PHASE B
PHASE C
NEUTRAL
GROUND
ISOLATED
GROUND
BLACK
RED
BLUE
WHITE
GREEN
GREEN/
YELLOW STRIPE
CIRCUIT BREAKER/FUSE AND WIRE SIZE COMBINATIONS NOT SHOWN ABOVE SHALL BE APPROVED
BY THE ENGINEER PRIOR TO INSTALLATION.
26 05 26 GROUNDING AND BONDING
A.
FURNISH AND INSTALL A COMPLETE GROUNDING SYSTEM IN COMPLIANCE WITH ALL
REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE.
B.
A SEPARATE EQUIPMENT GROUNDING CONDUCTOR, MINIMUM SIZE PER NEC TABLE 250.122,
SHALL BE INSTALLED IN CONDUIT ALONG WITH ALL FEEDERS, BRANCH CIRCUITS AND CONTROL
CIRCUITS. CONDUCTOR INSULATION SHALL BE GREEN.
C.
CONDUIT SYSTEM SHALL BE ELECTRICALLY CONTINUOUS. ALL ENCLOSURES AND NON-CURRENT
CARRYING METALS TO BE GROUNDED. ALL LOCK NUTS MUST CUT THROUGH ENAMELED OR
PAINTED SURFACES ON ENCLOSURES. WHERE ENCLOSURES AND NON-CURRENT CARRYING
METALS ARE ISOLATED FROM THE CONDUIT SYSTEM, USE BONDING JUMPERS WITH APPROVED
CLAMPS.
ALL RECEPTACLES SHALL BE BONDED TO A GROUND CONDUCTOR USING A #12 AWG MINIMUM
BONDING JUMPER BETWEEN RECEPTACLE TERMINAL AND GROUND CONDUCTOR. METAL-TO-METAL
CONTACT BETWEEN THE DEVICE YOKE AND THE OUTLET BOX IS NOT ACCEPTABLE FOR EITHER
SURFACE MOUNTED BOXES OR FLUSH TYPE BOXES.
BOND ALL STRUCTURAL STEEL TO EARTH, GROUND RODS OR PLATES, OR WATER SYSTEM.
H.
BOND ALL ROOF MOUNTED EQUIPMENT TO ACCEPTABLE GROUNDS PER THE N.E.C.
AC. MANUFACTURER: GENERAL ELECTRIC TYPE AQ FOR 208Y/120V APPLICATIONS. EQUAL EQUIPMENT
BY SQUARE D, SIEMENS, OR CUTLER HAMMER WILL BE ACCEPTED.
AF. TEST AND MAKE CORRECTIONS/ADJUSTMENTS FOR PHASE BALANCING.
(ELECTRICAL SPECIFICATIONS CONTINUED ON SHEET E-702)
ALL CONDUCTORS SHALL BE COPPER. ALUMINUM CONDUCTORS ARE
C.
COORDINATE WORK PROVIDED BY LANDLORD PRIOR TO BID AND INCLUDE THE COST OF ANY
SUCH WORK AS DIRECTED BY LANDLORD. WIRING OF METERING EQUIPMENT SHALL BE BY
GENERAL CONTRACTOR AS DIRECTED BY THE ELECTRIC COMPANY.
D.
METERING EQUIPMENT SHALL BE FURNISHED BY GENERAL CONTRACTOR AND INSTALLED TO THE
MALLS REQUIREMENTS.
E.
DISCONNECT SWITCHES SHALL BE HEAVY-DUTY TYPE, UL LISTED.
8
9
SGH STORE #: 6078
DRAWN BY: EDS
PERMITTED.
10
SUNGLASS HUT
LA PLAZA MALL
2200 S. 10TH STREET
McALLEN, TX 78503
SPACE #Q14-C
2.0 TYPE: PREMIUM
GENERAL CONTRACTOR SHALL FURNISH ALL LABOR, MISC. MATERIALS AND EQUIPMENT
NECESSARY TO INSTALL ALL OF THE ELECTRICAL SERVICE FROM THE LANDLORD'S ELECTRICAL
SERVICE ROOM INCLUDING (AS INDICATED ON SHEET E4.0) BUT NOT LIMITED TO THE SECONDARY
CABLES, CONDUIT, PULL WIRE AND GROUND ROD AND SLEEVE AS REQUIRED. COORDINATE
REQUIREMENTS WITH LANDLORD PRIOR TO BID. THE GENERAL CONTRACTOR SHALL COORDINATE
INSTALLATION OF THE DISCONNECT SWITCHES AND PANELBOARD WITH THIS WORK.
B.
SEAL
AB. NAMEPLATES AS SCHEDULED ON DRAWINGS SHALL INDICATE FUNCTION OF EACH DEVICE.
NAMEPLATES SHALL BE LAMINATED PHENOLIC WITH A WHITE SURFACE AND BLACK CORE. USE
1/16" THICK MATERIAL FOR PLATES UP TO 2" X 4". FOR LARGER SIZES, USE 1/8" THICK MATERIAL
26 05 29 DISTRIBUTION
A.
Shremshock Engineering, Inc.
7400 W. Campus Rd. Suite 150 New Albany, OH 43054
t: 614 545 4550 | f: 614 545 4555 | shremshock.com
TX Registration Number: #F-9566
AA. TERMINALS FOR CONNECTION OF THE FEEDER TO THE PANELBOARD MAINS TO MAIN BREAKER
SHALL BE UL RECOGNIZED AS SUITABLE FOR THE TYPE OF CONDUCTORS SPECIFIED.
AD. PANELBOARD SHALL BE INSTALLED WITH TOP CIRCUIT BREAKER AT 6'-0" ABOVE FLOOR, FLUSH OR
THE GROUNDING ELECTRODE CONDUCTOR FOR SEPARATELY DERIVED SYSTEMS, SUCH AS
SURFACE MOUNTED.
DRY-TYPE TRANSFORMERS, SHALL BE RUN IN NON-METALLIC (PVC) CONDUIT TO MINIMIZE GROUND
IMPEDANCE.
AE. ALL CONNECTIONS AT PANEL AND SWITCHES ARE TO BE MADE, ALL SPLICES COMPLETE, ALL
FUSES IN PLACE, AND ALL CIRCUITS CONTINUOUS FROM POINT OF SERVICE CONNECTION TO IT'S
LIGHTING FIXTURES SHALL BE GROUNDED BY THE USE OF A PIGTAIL FASTENED ON BARE METAL
FINAL DESTINATION, AND ALL COVERS AND PLATES INSTALLED AND FINAL ELECTRICAL INSPECTION
THAT IS FREE OF PAINT.
PRIOR TO THE TIME OF FINAL INSPECTION BY OWNER CONSTRUCTION MANAGER.
G.
CONSULTANT PROJECT # 150343
CONTROL FUSES FOR MOTOR STARTERS, CONTACTORS, AND CONTROL PANEL TRANSFORMERS
SHALL BE BUSSMANN FNQ-R SIZED AT 500% RATED CURRENT.
CONDUCTORS USED FOR EMERGENCY LIGHTING CIRCUITS SHALL BE #10 AWG, MINIMUM,
AND SHALL BE RUN IN SEPARATE CONDUIT USED FOR NO OTHER PURPOSE.
PERMITTED.
A Subsidiary of the Luxottica Group
4000 Luxottica Place
Mason, Ohio 45040
SWITCHES SHALL BE RATED FOR AC. FUSIBLE SWITCHES MUST ACCEPT CLASS R FUSES AND
HAVE PROVISIONS TO REJECT ALL FUSES EXCEPT CLASS R. THE UL LISTED SHORT CIRCUIT RATING
OF THE SWITCHES SHALL BE 200,000 RMS SYMMETRICAL AMPERES WHEN CLASS R FUSES ARE
USED.
TYPED LIST OF ALL SPARES SHALL ALSO BE INCLUDED.
THE FOLLOWING COLOR CODE SHALL BE USED:
F.
ALL SWITCHES SHALL HAVE SWITCH BLADES WHICH ARE FULLY VISIBLE IN THE "OFF" POSITION
WHEN THE SWITCH DOOR IS OPEN. SWITCHES SHALL HAVE REMOVABLE ARC SUPPRESSORS
WHERE NECESSARY TO PERMIT EASY ACCESS TO LINE SIDE LUGS. LUGS SHALL BE FRONT
REMOVABLE AND UL LISTED FOR 75 DEGREES C., ALUMINUM OR COPPER WIRES.
Q.
C.
E.
DISCONNECT SWITCHES SHALL BE BY SQUARE D, SIEMENS, CUTLER HAMMER, OR GENERAL
ELECTRIC.
FURNISH SPARE FUSES TO THE TENANT IN THE FOLLOWING QUANTITIES: 10% OF TOTAL PROJECT
QUANTITY (BUT NOT LESS THAN THREE (3) FOR EACH TYPE AND RATING OF FUSES).
ALUMINUM CONDUCTORS ARE
D.
14
P.
B.
D.
13
NAMEPLATES SHALL INDICATE FUNCTION OF EACH DEVICE. NAMEPLATES SHALL BE LAMINATED
PHENOLIC WITH A WHITE SURFACE AND BLACK CORE. USE 1/16" THICK MATERIAL FOR
NAMEPLATES UP TO 2"x4" AND USE 1/8" THICK MATERIAL FOR LARGER SIZES. ALL NAMEPLATES
SHALL BE FURNISHED AND INSTALLED BY GENERAL CONTRACTOR. GENERAL CONTRACTOR TO
COORDINATE WITH THE LOCAL BUILDING AUTHORITY OR BUILDING INSPECTOR ON WHICH ITEMS
SHOULD HAVE A NAMEPLATE.
MINIMUM WIRE SIZES FOR 20A BRANCH CIRCUITS SHALL BE ADJUSTED FOR DISTANCE, MEASURED
FROM THE PANELBOARD CIRCUIT BREAKER TO THE FURTHEST OUTLET,
O.
AS FOLLOWS:
LESS THAN 100 FT - #12
BETWEEN 101 AND 150 FEET - #10
BETWEEN 151 AND 250 FEET - #8
OVER 251 FEET - #6
12
K.
CONDUCTORS SHALL BE COPPER. UNLESS NOTED OTHERWISE ON THE DRAWINGS, THE MINIMUM
COPPER WIRE SIZES FOR WET AND DRY AREAS AS DEFINED BY THE N.E.C. SHALL BE AS FOLLOWS:
20 AMP CKT BKR OR FUSE = #12 AWG, THHN/THWN
30 AMP CKT BKR OR FUSE = #10 AWG, THHN/THWN
40 AMP CKT BKR OR FUSE = #8 AWG, THHN/THWN
50 AMP CKT BKR OR FUSE = #8 AWG, THHN/THWN
100 AMP CKT BKR OR FUSE = #3 AWG, THHN/THWN
125 AMP CKT BKR OR FUSE = #1 AWG, THHN/THWN
200 AMP CKT BKR OR FUSE = #3/0 AWG, THHN/THWN
PROVIDE INSTRUCTION TO TENANT'S OPERATING PERSONNEL AS NECESSARY, SHOWING LOCATIONS AND
PROPER OPERATION OF MAJOR ITEMS OF EQUIPMENT AND SYSTEM COMPONENTS AND REFERRING TO
THE OPERATING INSTRUCTION MANUAL DESCRIBED BELOW AS A GUIDE.
AJ. GENERAL CONTRACTOR SHALL GUARANTEE THIS WORKMANSHIP AND MATERIALS, EXCEPT FOR
TENANT-SUPPLIED MATERIALS, FOR A PERIOD OF ONE YEAR FROM THE DATE OF ACCEPTANCE (IN
WRITING) OF THE INSTALLATION BY TENANT'S CONSTRUCTION MANAGER/ENGINEERING MANAGER AND
LEAVE THIS WORK IN PERFECT ORDER AT COMPLETION.
9
F.
AL. COMPILE TWO (2) WRITTEN MANUALS OF OPERATING INSTRUCTIONS INCLUDING COPIES OF SHOP
DRAWINGS AND A LISTING OF EQUIPMENT SUPPLIERS. ASSEMBLE IN 8-1/2" X 11" HARD BACKED INDEXED
BINDER. MATERIAL SHALL BE AS FOLLOWS:
GENERAL CONTRACTOR SHALL PROVIDE SLEEVES TO PROTECT EQUIPMENT OR FACILITIES IN THE
INSTALLATION. EACH SLEEVE SHALL EXTEND THROUGH IT'S RESPECTIVE FLOOR, WALL OR PARTITION AND
SHALL BE CUT FLUSH WITH EACH SURFACE EXCEPT SLEEVES THAT PENETRATE THE FLOOR, WHICH SHALL
EXTEND 2" ABOVE THE FLOOR.
AF. THE MATERIALS AND EQUIPMENT INSTALLED IN THE WORK SHALL MEET THE REQUIREMENTS OF THE
CONTRACT DOCUMENTS.
UNLESS SPECIFICALLY NOTED OTHERWISE, MATERIALS, PRODUCTS, AND EQUIPMENT, INCLUDING ALL
COMPONENTS THEREOF, SHALL BE NEW, UNDERWRITERS LABORATORIES LISTED AND LABELED AND SIZED
IN CONFORMITY WITH REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, STATE AND LOCAL CODES,
WHICHEVER IS MORE STRINGENT.
ALL ELECTRICAL WORK SHALL BE INSPECTED BY THE GOVERNMENTAL AGENCY HAVING JURISDICTION,
INCLUDING LOCAL INSPECTION AUTHORITIES.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF THE DEMOLITION OF
EXISTING WORK. COORDINATE ANY EXISTING EQUIPMENT TO BE LEFT INTACT AND ADVISE TENANT'S
CONSTRUCTION MANAGER AT TIME OF BID.
AE. AT COMPLETION OF PROJECT AND BEFORE FINAL APPROVAL, THE CONTRACTOR SHALL MAKE ANY FINAL
CORRECTIONS TO DRAWINGS AND CERTIFY THE ACCURACY OF EACH PRINT BY SIGNATURE THEREON. ONE
COPY OF DRAWINGS STAMPED "DO NOT REMOVE" SHALL BE PLACED IN DRAWING TUBE LOCATED NEXT TO
THE ELECTRICAL PANELS (SEE ARCHITECTURAL DRAWINGS FOR LOCATION). A SECOND AS-BUILT SET
SHALL BE SENT TO OWNER OFFICES.
WHERE THE DRAWINGS OR SPECIFICATIONS CALL FOR ITEMS WHICH EXCEED CODES, THE LANDLORD OR
TENANT CRITERIA, THE CONTRACTOR IS RESPONSIBLE FOR FURNISHING AND INSTALLING THE SYSTEM
WITH THE MOST STRINGENT REQUIREMENTS AS DESIGNED AND DESCRIBED ON THESE DRAWINGS,
UNLESS NOTED OTHERWISE.
N.
8
FOR ANY PHASED STORE CONSTRUCTION, THIS CONTRACTOR IS TO INCLUDE IN THIS BID ALL NECESSARY
ELECTRICAL SERVICE CHANGES REQUIRED TO KEEP THE OPERATING PHASE OF THE STORE'S ELECTRIC
SERVICE IN OPERATION. CONTRACTOR MUST SCHEDULE WITH TENANT'S CONSTRUCTION MANAGER AND
LANDLORD (IN WRITING) ONE WEEK PRIOR TO ANY SHUT DOWN OF THE P.O.S., CASH REGISTERS,
ELECTRICAL, TELEPHONE OR FIRE ALARM SYSTEMS. ADVISE GENERAL CONTRACTOR AND TENANT AT TIME
OF BID IF ANY CONFLICTS EXIST.
AD. GENERAL CONTRACTOR SHALL MAINTAIN ONE COPY OF DRAWINGS ON THE JOB SITE TO RECORD
DEVIATIONS FROM CONTRACT DRAWINGS, SUCH AS:
1.
LOCATION OF JUNCTION BOXES AND RECEPTACLES.
2. REVISIONS, ADDENDUMS, AND CHANGE ORDERS.
3. SIGNIFICANT DEVIATIONS MADE NECESSARY BY FIELD CONDITIONS, APPROVED EQUIPMENT
SUBSTITUTIONS, AND CONTRACTOR'S COORDINATION WITH OTHER TRADES.
GENERAL CONTRACTOR SHALL INQUIRE INTO AND COMPLY WITH ALL APPLICABLE CODES, ORDINANCES,
AND REGULATIONS. THIS CONTRACTOR SHALL INCLUDE ANY CHANGES REQUIRED BY CODES IN THE BID
AND IF THESE CHANGES ARE NOT INCLUDED IN THE BID, THEY MUST BE QUALIFIED AS A SEPARATE LINE
ITEM IN THE BID. AFTER CONTRACT IS ISSUED, NO ADDITIONAL COST DUE TO CODE ISSUES SHALL BE
REIMBURSED BY TENANT TO THE CONTRACTOR.
ALL PERMITS REQUIRED BY LAWS, ORDINANCES AND BUILDING CODES HAVING JURISDICTION SHALL BE
OBTAINED AT PROPER TIME BY AND AT THE EXPENSE OF THE GENERAL CONTRACTOR.
GENERAL CONTRACTOR SHALL SUBMIT ONLY SUBSTITUTION REQUESTS TO TENANT'S CONSTRUCTION
MANAGER FOR APPROVAL. SUBMISSIONS SHALL BE MADE EARLY ENOUGH IN PROJECT TO ALLOW SEVEN
(7) WORKING DAYS FOR TENANT'S CONSTRUCTION MANAGER'S REVIEW WITHOUT CAUSING DELAYS OR
CONFLICTS TO THE JOB'S PROGRESS. SUBMITTALS SHALL BEAR THE STAMP OF THE GENERAL
CONTRACTOR AND/OR SUB-CONTRACTOR SHOWING THAT THEY HAVE REVIEWED AND CONFIRMED THAT
THE SUBMITTALS ARE IN CONFORMANCE WITH THE CONTRACT DRAWINGS AND SPECIFICATIONS OR
INDICATE WHERE EXCEPTIONS HAVE BEEN TAKEN.
AC. THE ARCHITECT RESERVES THE RIGHT TO DIRECT REMOVAL AND REPLACEMENT OF ANY ITEM WHICH, IN
THEIR OPINION, SHALL NOT PRESENT AN ORDERLY OR REASONABLY NEAT OR WORKMANLIKE
APPEARANCE, PROVIDED THAT SUCH ITEM CAN BE PROPERLY INSTALLED IN SUCH ORDERLY WAY BY
METHODS USUAL IN SUCH WORK, OR WHICH DOES NOT COMPLY WITH CONTRACT DRAWINGS OR
SPECIFICATIONS. SUCH REMOVALS OR REPLACEMENTS SHALL BE DONE BY CONTRACTOR WHEN SO
DIRECTED IN WRITING BY ARCHITECT AND AT CONTRACTOR'S EXPENSE.
THE NATIONAL ELECTRICAL CODE.
STATE, CITY, AND COUNTY BUILDING CODES AND ORDINANCES.
NATIONAL BOARD OF FIRE UNDERWRITERS.
CERTAIN CODES AND STANDARDS AS SET UP BY VARIOUS TECHNICAL SOCIETIES SUCH AS UL,
NEMA, NECA, IEEE, ASTM, IES, IPCEA, AND ANSI.
THIS WORK SHALL BE GOVERNED ALSO BY LOCAL INSPECTOR'S REQUIREMENTS.
FEDERAL OCCUPATIONAL SAFETY AND HEALTH ACT STANDARDS.
AMERICANS WITH DISABILITIES ACT.
M.
7
AB. ELECTRICAL DRAWINGS ARE INTENDED TO INDICATE APPROXIMATE LOCATIONS OF SWITCHES,
RECEPTACLES, LIGHTING FIXTURES AND OTHER ITEMS OF VARIOUS ELECTRICAL SYSTEMS OF PROJECT.
EXACT LOCATIONS AND ROUGH-IN DIMENSIONS FOR ALL WORK AND EQUIPMENT SHALL BE OBTAINED
FROM ARCHITECT OR ARCHITECT'S REPRESENTATIVE AS WORK PROGRESSES. SHOULD THE GENERAL
CONTRACTOR FAIL TO PROPERLY OBTAIN SUCH LOCATIONS OR DIMENSIONS, THE ARCHITECT SHALL
CHANGE THIS WORK AT THE GENERAL CONTRACTORS EXPENSE WHEN REQUESTED BY ARCHITECT.
ARCHITECT RESERVES THE RIGHT TO MAKE MINOR CHANGES IN LOCATION OF ELECTRICAL WORK OR
EQUIPMENT PRIOR TO ROUGHING IN WITH NO ADDITIONAL COST TO TENANT. TENANT'S CONSTRUCTION
MANAGER RESERVES THE RIGHT TO RELOCATE ANY OUTLETS OR FIXTURES BEFORE THEY ARE INSTALLED
WITHOUT ADDITIONAL COST.
ALL WORK SHALL BE DONE IN ACCORDANCE WITH:
1.
2.
3.
4.
J.
S.
6
AA. ELECTRICAL LAYOUTS ARE SCHEMATIC. EXACT LOCATIONS ARE DETERMINED BY EXACT LOCATION OF
EQUIPMENT, ETC., AND MAY BE REVISED TO SUIT THE CONSTRUCTION CONDITIONS AND AID IN
COORDINATION WITH WORK OF OTHER CONTRACTORS. WHERE DRAWINGS, EXISTING SITE CONDITIONS,
SPECIFICATIONS OR OTHER TRADES CONFLICT OR ARE UNCLEAR, ADVISE THE GENERAL CONTRACTOR IN
WRITING PRIOR TO SUBMITTAL OF BID. THE GENERAL CONTRACTOR IS RESPONSIBLE TO ADVISE TENANT'S
CONSTRUCTION MANAGER IN WRITING OF ANY VARIATIONS TO CONTRACT DOCUMENTS PRIOR TO
SUBMISSION OF THE BID. OTHERWISE, TENANT'S CONSTRUCTION MANAGER'S INTERPRETATION OF
CONTRACT DOCUMENTS OR CONDITIONS SHALL BE FINAL WITH NO ADDITIONAL COMPENSATION
PERMITTED.
GENERAL CONTRACTOR SHALL DO ALL CUTTING, CHASING, OR CHANNELING AND PATCHING REQUIRED
FOR ANY WORK UNDER THIS DIVISION. CUTTING SHALL HAVE PRIOR APPROVAL BY TENANT'S
CONSTRUCTION MANAGER AND THE LANDLORD. PATCHING IS TO BE "AS NEW CONDITION".
G.
C
A
TEMPERATURE CONTROL WIRING THAT IS FURNISHED BY OTHERS PRE-WIRED IN UNITS.
TELEPHONES AND FINAL CONNECTION OF WIRING THERETO.
INTERNAL WIRING OF EQUIPMENT FURNISHED AND PRE-WIRED BY OTHERS.
SECURITY SYSTEM FURNISHED AND INSTALLED BY SECURITY CONTRACTOR.
ALL ELECTRICAL WORK SHALL BE INSTALLED SO AS TO BE READILY ACCESSIBLE FOR OPERATING,
SERVICING, MAINTAINING AND REPAIRING. THIS CONTRACTOR IS RESPONSIBLE FOR PROVIDING
SUFFICIENT SERVICE ACCESS TO ALL EQUIPMENT.
I.
R.
T.
TEMPORARY SERVICE AS REQUIRED.
PRIMARY DISTRIBUTION BY ELECTRIC COMPANY.
EMERGENCY AND EXIT LIGHTING SYSTEMS.
CONDUIT AND CABLES FOR TELEPHONE AND DATA SYSTEMS AS SHOWN ON THE DRAWINGS.
ELECTRICAL PANEL AND BRANCH CIRCUIT WIRING.
WIRING DEVICES AND PLATES.
LIGHTING FIXTURES AND LAMPS, INSTALLATION AND WIRING.
LIGHTING CONTROLS.
ELECTRICAL CONNECTIONS TO EQUIPMENT FURNISHED BY OTHERS, SIGNS, CORNICE LIGHTING,
CASE LIGHTING, ETC., AS SHOWN ON DRAWINGS.
INSTALLATION OF CONDUIT AND CABLES FOR SOUND SYSTEM AS SHOWN ON DRAWINGS.
SMOKE/FIRE ALARM WIRING, DEVICES AND CONDUIT, AS SHOWN OR DESCRIBED ON DRAWINGS OR
AS NECESSARY TO MEET LANDLORD, STATE, LOCAL, INSURANCE AND FIRE DEPARTMENT
REQUIREMENTS.
INSTALLATION OF CONDUITS STUBBED TO ABOVE CEILING FOR HVAC. ALSO, ANY ADDITIONAL
CONDUIT FOR HVAC CONTROL EQUIPMENT WHERE PLENUM RATED CABLES ARE NOT PERMITTED.
THE GENERAL CONTRACTOR SHALL PAY FOR ALL ELECTRICITY PRIOR TO STORE MERCHANDISING,
AND INCLUDE COST IN BID.
F.
D
Q.
WORK WHICH SHALL BE PERFORMED BY OTHERS, UNLESS NOTED OTHERWISE, INCLUDES THE
FOLLOWING:
1.
2.
3.
4.
D.
ANY REFERENCE TO TENANT OR TENANT'S CONSTRUCTION MANAGER OR FURNISHED BY ANY OF
THE ABOVE REFERS TO SUNGLASS HUT.
DRAWINGS AND GENERAL PROVISIONS OF CONTRACT, INCLUDING GENERAL AND SUPPLEMENTARY
CONDITIONS AND ALL OTHER SPECIFICATIONS SECTIONS, APPLY TO THIS AND THE OTHER SECTIONS
OF DIVISION 26 THROUGH 28.
THE CONTRACTOR FOR THIS WORK IS REQUIRED TO READ THE SPECIFICATIONS AND REVIEW
DRAWINGS FOR ALL DIVISIONS OF WORK AND IS RESPONSIBLE FOR THE COORDINATION OF THIS
WORK AND THE WORK OF THE SUBCONTRACTORS WITH ALL DIVISIONS OF WORK. IT IS THIS
CONTRACTOR'S RESPONSIBILITY TO PROVIDE THE SUBCONTRACTORS WITH A COMPLETE SET OF BID
DOCUMENTS.
THIS CONTRACTOR IS RESPONSIBLE FOR SCHEDULING THE COMPLETION AND INSPECTION OF THIS
WORK AND THE WORK OF THE SUBCONTRACTORS TO COMPLY WITH THE OWNER SCHEDULE AND
THE PROJECT COMPLETION DATE.
THIS CONTRACTOR SHALL VISIT THE SITE PRIOR TO SUBMITTAL OF BID TO DETERMINE CONDITIONS
AFFECTING THE WORK. ANY ITEMS WHICH ARE NOT COVERED IN THE BID DOCUMENTS OR ANY
PROPOSED SUBSTITUTIONS SHALL BE LISTED SEPARATELY AND QUALIFIED IN THE CONTRACTOR'S
BID. SUBMITTAL OF BID SHALL SERVE AS EVIDENCE OF KNOWLEDGE OF EXISTING CONDITIONS AND
ANY MODIFICATIONS WHICH ARE REQUIRED TO MEET THE INTENT OF THE DRAWINGS AND
SPECIFICATIONS. FAILURE TO VISIT THE SITE DOES NOT RELIEVE THE CONTRACTOR OF
RESPONSIBILITY IN PERFORMANCE OF WORK.
REFER TO RESPONSIBILITY SCHEDULE ON THE ARCHITECTURAL DRAWINGS FOR INFORMATION IN
REGARD TO RESPONSIBILITY OF WORK OR ITEMS WHICH MAY AFFECT BID.
PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL NEW
COMPLETE ELECTRICAL SYSTEM AS INDICATED ON DRAWINGS, AS REQUIRED BY CODE AND AS SPECIFIED
HEREIN, IN DIVISIONS 26, 27, AND 28. WORK SHALL INCLUDE, BUT NOT BE LIMITED TO, THE FOLLOWING:
1.
2.
3.
4.
5.
6.
7.
8.
9.
H
5
LA PLAZA MALL
2
AT
1
REVIEWED BY: KAH
AUTHORIZED FOR:
ELECTRICAL
SPECIFICATIONS
11
12
13
14
3
B.
26 05 33 RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS
A.
K
B.
J
D.
RECESSED OUTLET BOXES SHALL BE STAMPED STEEL SUITABLE FOR THE DEVICE INSTALLED.
SURFACE MOUNTED OUTLET BOXES SHALL BE CAST IRON SUITABLE FOR THE DEVICE INSTALLED.
F.
RACEWAY AND ENCLOSURE SIZES SHALL BE AS SHOWN ON DRAWINGS OR, IF NOT SHOWN, SHALL
BE SIZED TO COMPLY WITH N.E.C. FILL REQUIREMENTS FOR CONDUCTORS ENCLOSED.
J.
G
K.
L.
M.
F
N.
O.
P.
E
USER: JGRAY
PLOTTED: 7/16/2015 - 4:04 PM
P:\SGH\150343 SGH-La Plaza Mall Mcallen, TX\E-701_06078.dwg
LAYOUT: E-702 (208v)
Q.
D
R.
S.
T.
C
U.
B
B.
SINGLE POLE SWITCHES: 20AMP - 120-277V: HUBBELL "HBL1221PL"
DOUBLE POLE SWITCHES: 20AMP - 120-277V: HUBBELL "HBL1222PL"
DUPLEX RECEPTACLES: 20AMP - 125V: HUBBELL "HBL5362"
DUPLEX RECEPTACLES - BLACK: 20AMP - 125V: HUBBELL "HBL5362BLK"
ISOLATED GROUND RECEPTACLES: 20AMP - 125V: HUBBELL "IG5362"
GFCI RECEPTACLES: 20AMP - 125V: HUBBELL "GF5362A"
FLOOR BOX - MODEL S1PFB NON-METALLIC ROUND FLOOR BOX
POKE-THRU - MODEL S1PTFIT THRU-FLOOR FITTING (DUAL CHANNEL)
SUB PLATE - MODEL S1SP SUB-PLATE(STYLE LINE/GFCI)
COVER - MODEL S1TFCAL (ALUMINUM FINISH).
ALL DEVICE COVER PLATES SHALL BE PASS AND SEYMOUR SERIES "RP" OR EQUAL BY EAGLE
ELECTRIC MFG. CO.
OTHER EQUIVALENT DEVICES WITH MATCHING COVER PLATES MAY BE FURNISHED AS APPROVED
BY OWNER.
FLEXIBLE METAL CONDUIT (FMC) SHALL BE USED ONLY FOR CONNECTIONS INSIDE CASEWORK AND E.
AS THE FINAL CONNECTION TO RECESSED FIXTURES, MOTORS, AND ELECTRICAL EQUIPMENT THAT
MAY GENERATE VIBRATION THROUGH THE CONDUIT SYSTEM. FMC SHALL BE UL APPROVED, AND
BOTH THE CONDUIT AND FITTINGS SHALL BE LISTED FOR GROUNDING. FMC SHALL BE KEPT TO SIX
FEET (6'-0") MAXIMUM LENGTH AND SHALL BE MINIMUM ONE-HALF INCH (1/2") ELECTRICAL TRADE
SIZE. WHEN CONNECTED TO HARD CONDUIT, THE FMC MUST BE THE SAME SIZE AS THE HARD
F.
CONDUIT IT IS CONNECTED TO. AN EQUIPMENT GROUNDING CONDUCTOR MUST BE INSTALLED IN
ALL RUNS OF FMC.
LIQUID-TIGHT FLEXIBLE METAL CONDUIT (LFMC) AND LIQUID-TIGHT FITTINGS SHALL BE USED IN
AREAS EXPOSED TO THE WEATHER OR EXCESSIVE MOISTURE AS THE FINAL CONNECTION TO
MOTORS, AND ELECTRICAL EQUIPMENT THAT MAY GENERATE VIBRATION THROUGH THE CONDUIT
SYSTEM. LFMC SHALL BE UL APPROVED, AND BOTH THE CONDUIT AND FITTINGS SHALL BE LISTED
FOR GROUNDING. LFMC SHALL BE KEPT TO SIX FEET (6'-0") MAXIMUM LENGTH AND SHALL BE
MINIMUM ONE-HALF INCH (1/2") ELECTRICAL TRADE SIZE. WHEN CONNECTED TO HARD CONDUIT,
THE LFMC MUST BE THE SAME SIZE AS THE HARD CONDUIT IT IS CONNECTED TO. AN EQUIPMENT
GROUNDING CONDUCTOR MUST BE INSTALLED IN ALL RUNS OF LFMC.
CONDUIT SHALL GENERALLY BE CONCEALED WHERE POSSIBLE. NO CONDUIT SHALL BE RUN IN
SLAB, EXCEPT AS REQUIRED FOR FLOOR-MOUNTED DEVICES. PROVIDE PROPERLY LABELED PULL
STRING IN ALL EMPTY CONDUITS.
ALL CONDUIT FITTINGS SHALL BE GALVANIZED MALLEABLE IRON OR STEEL. CONNECTORS AND
COUPLINGS SHALL BE THREADED OR CUPPED SET SCREW TYPE, CONCRETE TIGHT. CONDUIT
BODIES SHALL BE MALLEABLE IRON, THREADED FOR HEAVYWALL CONDUIT AND CUPPED SET
SCREW TYPE FOR EMT, WITH CADMIUM FINISH AND CADMIUM PLATED SHEET STEEL COVERS.
SYNTHETIC RUBBER GASKETS SHALL BE USED UNDER BODY COVERS EXPOSED TO WEATHER. EMT
CONNECTORS SHALL BE INSULATED THROAT TYPE.
INSTALL EXPANSION FITTINGS AT ALL LOCATIONS WHERE CONDUITS CROSS BUILDING EXPANSION
JOINTS OR TRAVERSE FROM ONE INDEPENDENT STRUCTURE TO ANOTHER. INSTALL WHEREVER
CONDUITS TRAVERSE STRUCTURES HAVING SEPARATE FOUNDATIONS OR WHERE EXISTING
BUILDINGS ARE JOINED TO A NEW STRUCTURE.
DURING ROUGHING-IN, CAP ALL CONDUITS WHICH MAY BECOME FOULED WITH FOREIGN MATERIAL.
W.
NO MORE THAN THREE (3) 90 DEGREE BENDS WILL BE ALLOWED IN ANY ONE CONDUIT RUN.
WHERE MORE BENDS ARE NECESSARY IN ANY SINGLE RUN, A PULL BOX SHALL BE INSTALLED. ALL
CONDUIT EXCEPT IN CONCRETE SLAB OR EARTH SHALL BE ROUTED PARALLEL OR PERPENDICULAR
TO THE LINES OF THE BUILDING, AND NO OUT-OF-PLUMB OR DIAGONAL LINES WILL BE ACCEPTED.
26 09 23 LIGHTING CONTROLS
1
2
3
FURNISH AND INSTALL CONTACTORS, CONTROL RELAYS, PUSHBUTTON STATIONS, SELECTOR
SWITCHES, PILOT LIGHTS, FUSES AND SIMILAR CONTROL AUXILIARIES AS SHOWN ON DRAWINGS
AND/OR REQUIRED TO PROVIDE PROPER CONTROL AND ISOLATION BETWEEN VARIOUS
AUTOMATIC CONTROLLERS AND EQUIPMENT SHOWN ON THE DRAWINGS.
ALL CIRCUIT BREAKERS FEEDING MOTOR LOADS SHALL BE HACR TYPE.
H.
EQUIPMENT SHALL BE SAME MAKE AS MOTOR STARTERS. PUSHBUTTON STATIONS, SELECTOR
SWITCHES, PILOT LIGHTS: HEAVY DUTY, OIL TIGHT, STANDARD SIZE, WITH TRANSFORMER TYPE
PILOT LIGHTS, FLUSH MOUNTED WHERE PRACTICAL.
I.
ALL OVERLOAD DEVICES, INCLUDING EQUIPMENT FURNISHED UNDER OTHER CONTRACTS, SHALL
BE SET AND ADJUSTED TO SUIT THE LOAD CONDITIONS.
C.
INSTALL LIGHTING FIXTURES AS SHOWN ON THE DRAWINGS.
LAMPS SHALL BE MANUFACTURED BY PHILIPS, OSRAM/SYLVANIA OR GENERAL ELECTRIC. ALL LAMP
TYPES SHALL BE BY THE SAME MANUFACTURER.
D.
FIXTURES ARE TO BE PROVIDED COMPLETE WITH BALLASTS, SOCKET, LAMPS, END AND TRIP
PLATES AND ALL MOUNTING ACCESSORIES REQUIRED FOR A COMPLETE FIXTURE INSTALLATION.
E.
INCANDESCENT AND HIGH INTENSITY DISCHARGE RECESSED LIGHTING FIXTURES TO BE FURNISHED
WITH THERMAL CUT OUTS AS REQUIRED BY THE NEC.
F.
USE RAPID-START HIGH-POWER-FACTOR ELECTRONIC BALLASTS AND T8 LAMPS, UNLESS NOTED
OTHERWISE. FURNISH SPECIAL LOW TEMPERATURE BALLASTS FOR EXTERIOR MOUNTED FIXTURES.
G.
UNLESS OTHERWISE NOTED, ALL LENSES ON FLUORESCENT FIXTURES ARE TO BE ACRYLIC AND A
MINIMUM OF 0.125 IN. THICK.
H.
ALL RECESSED HID FIXTURES SHALL CARRY A ULR LISTING. THEY SHALL HAVE A THERMAL CUT OUT
ON BOTH THE BALLAST AND THE FIXTURE ITSELF.
I.
USE STEEL WIRE HANGERS FASTENED TO THE BUILDING STRUCTURE TO SUPPORT RECESSED
FIXTURES AT EACH CORNER. (FOUR CORNER SUSPENDED). FIXTURES TO FIT TIGHT AGAINST
CONSTRUCTION TO ELIMINATE LIGHT LEAKS.
4
WALL-MOUNTED FIXTURES SHALL BE MOUNTED PLUMB WITH BUILDING LINES AND INSTALLED WITH
PROPER BOX AND COVER HARDWARE.
SURFACE-MOUNTED FIXTURES SHALL COVER MOUNTING HARDWARE. USE A CANOPY THAT IS NO
LONGER THAN THE LENGTH AND WIDTH OF THE FIXTURE AND AT A HEIGHT THAT IS NO HIGHER
THAN REQUIRED TO MOUNT FIXTURE ABSOLUTELY VERTICAL. CANOPY FINISH SHALL MATCH
FIXTURE FINISH.
11
F.
ALL NEW MATERIAL AND EQUIPMENT SHALL MEET THE REQUIREMENTS OF THE FOLLOWING
STANDARDS:
TELECOMMUNICATIONS INDUSTRY ASSOC./ELECTRONIC INDUSTRIES ALLIANCE (TIA/EIA):
a.
TIA/EIA 568A.1, 2, AND 3 TELECOMMUNICATION CABLING STANDARD.
b.
TIA/EIA 569 TELECOMMUNICATION PATHWAYS AND SPACES.
c.
TIA/EIA 606 ADMINISTRATION OF INFRASTRUCTURE
d. TIA/EIA 607 GROUNDING AND BONDING
e. COMPLY WITH TIA/EIA 568, 569, AND BIC STANDARDS.
f.
COMPLY WITH NFPA 70.
12
13
14
WIRING METHOD: INSTALL HORIZONTAL CABLING IN RACEWAY WITHIN RACKS AND ENCLOSURES,
AND EXCEPT IN ACCESSIBLE CEILING SPACES AND IN GYPSUM BOARD PARTITIONS WHERE CABLE
WIRING METHOD MAY BE USED. CONCEAL RACEWAY AND CABLING EXCEPT IN UNFINISHED
SPACES. IN ACCESSIBLE CEILINGS, USE APPROPRIATELY SIZED J-HOOKS TO SUPPORT THE
CABLING EVERY FOUR FEET (MAXIMUM).
G.
INSTALL CABLE USING TECHNIQUES, PRACTICES, AND METHODS THAT ARE CONSISTENT WITH
CATEGORY 6 RATING OF COMPONENTS AND THAT INSURE CATEGORY 6 PERFORMANCE OF
COMPLETED AND LINKED SIGNAL PATHS, END TO END.
H.
DO NOT BEND CABLE IN HANDLING OR IN INSTALLING TO SMALLER RADII THAN MINIMUMS
RECOMMENDED BY MANUFACTURER.
I.
HORIZONTAL CABLES: LABEL CABLES AT THE WORK AREA END AND AT THE CLOSET END WITH THE
PATCH PANEL PORT NUMBER. LABEL EACH CABLE WITHIN 3 INCHES OF EACH TERMINATION,
WHERE IT IS ACCESSIBLE IN A CABINET OR JUNCTION OR OUTLET BOX, AND ELSEWHERE AS
INDICATED.
D.
THE CONTRACTOR SHALL BEAR ALL COSTS OF PERMITS, INSPECTIONS TESTS, AND/OR
APPROVALS.
WORKSTATION: LABEL CABLES WITHIN OUTLET BOXES AND NEATLY TYPED ON THE INTEGRAL LABEL
IN THE FACEPLATE WITH THE PATCH PANEL PORT NUMBER.
K.
E.
THE CONTRACTOR SHALL PROVIDE ON-SITE PERSONNEL TO TROUBLESHOOT AND REPAIR ANY
PROBLEMS THAT ARISE DURING CUTOVER AS THEY RELATE TO THEIR INSTALLED SYSTEM.
WARRANTY PERIOD FOR COMMUNICATIONS CONNECTIVITY (INCLUDING ALL COPPER):
MANUFACTURER'S STANDARD, BUT NOT LESS THAN 25 YEARS FROM DATE OF CONTRACT
COMPLETION.
F.
AFTER COMPLETION, A WARRANTY SHALL BE FURNISHED FOR ALL COMPONENTS, PARTS, AND
ASSEMBLIES AGAINST DEFECTS IN MATERIALS AND WORKMANSHIP. WARRANTY SERVICES SHALL
BE PROVIDED BY A CERTIFIED, FACTORY TRAINED REPRESENTATIVE OF THE EQUIPMENT
MANUFACTURER FOR A MINIMUM OF ONE YEAR OR AS SPECIFIED IN EACH INDIVIDUAL SECTION.
27 05 10 TELEPHONE AND DATA CONDUIT SYSTEM
23 31 11 DIGITAL ADDRESSABLE FIRE ALARM SYSTEM
6
7
Shremshock Engineering, Inc.
7400 W. Campus Rd. Suite 150 New Albany, OH 43054
t: 614 545 4550 | f: 614 545 4555 | shremshock.com
TX Registration Number: #F-9566
SEAL
A. INSTALLATION OF FIRE ALARM SYSTEM SHALL BE UNDER A SEPARATE PERMIT. ALL REQUIRED FIRE
ALARM DEVICES, CONDUITS, WIRES, BACKBOXES, ETC. SHALL BE INSTALLED AT TENANT
CONTRACTOR'S EXPENSE UNDER A SEPARATE PERMIT BY MALL FIRE/LIFE SAFETY CONTRACTOR.
INDICATE ON PLANS THAT IF REQUIRED, A VARIANCE WILL BE PROVIDED.
(END OF ELECTRICAL SPECIFICATIONS)
A.
FURNISH AND INSTALL A SYSTEM OF CONDUIT RACEWAYS, OUTLET BOXES, PULL WIRES, AND
TERMINAL BOARDS AS SHOWN ON THE DRAWINGS UNLESS OTHERWISE NOTED ON PLANS.
TELEPHONE SWITCHING APPARATUS, CONDUCTORS, INSTRUMENTS, MISCELLANEOUS EQUIPMENT
AND APPURTENANCES ARE NOT PART OF THIS CONTRACT AND WILL BE PROVIDED AND INSTALLED
BY OTHERS.
B.
CONDUITS FOR TELEPHONE WALL OUTLETS AND DATA WIRING SHALL BE A MINIMUM OF 1" UNLESS
NOTED OTHERWISE.
C.
FURNISH AND INSTALL A 3/4" THICK, FIRE-TREATED, PLYWOOD TELECOM BACKBOARD AT
LOCATION SHOWN ON THE DRAWINGS. PAINT WITH FIRE RETARDANT "P-1B" OR AS DIRECTED BY
TENANT'S CONSTRUCTION MANAGER. THE PLYWOOD BACKBOARD SHALL BE SECURELY ATTACHED
TO THE BUILDING WALLS TO SUPPORT RELAY PANEL, TERMINAL BLOCKS AND OTHER HARDWARE
WEIGHING APPROXIMATELY 10 POUNDS PER SQUARE FOOT.
D.
ALL CONDUIT RUNS FOR DATA AND TELEPHONE SHALL BE CONTINUOUS WITH NO JUNCTION BOXES
EXCEPT AS NOTED ON DRAWINGS. THIS INCLUDES BUT IS NOT LIMITED TO RUNS BETWEEN
TELEPHONE BOARD, MANAGER'S OFFICE, SOUND SYSTEM, CASHWRAPS AND TELEPHONE SETS.
E.
INSTALL PULL STRING IN EMPTY CONDUITS. ALL CONDUITS SHALL BE LABELED FOR PURPOSE
DESIGNATED.
F.
FURNISH AND INSTALL GROUND ROD AND #6 GROUND WIRE FROM TELECOM BACKBOARD TO
SERVICE ENTRANCE GROUND AND GROUND ROD PER TELEPHONE COMPANY'S REQUIREMENTS.
G.
OUTLET BOXES TO BE 4" SQUARE MINIMUM WITH SINGLE DEVICE COVER AND TELEPHONE PLATE.
27 05 15 INTERIOR COMMUNICATIONS PATHWAYS
A.
INTERIOR COMMUNICATIONS PATHWAYS SHALL BE INSTALLED BY THE GENERAL CONTRACTOR AND
BY THE TELECOMMUNICATIONS CONTRACTOR AS SPECIFIED HEREIN.
B.
CONDUITS SHALL BE INSTALLED, AS DETAILED IN DRAWINGS. THESE CONDUITS SHALL BE
INSTALLED BY THE GENERAL CONTRACTOR.
27 11 00 HORIZONTAL CABLING AND CONNECTIVITY
A.
PROVIDE A 10/100/1000 MBPS FULL-DUPLEX TRANSMISSION ETHERNET NETWORK OVER 4-PAIR,
CATEGORY 6 UTP HORIZONTAL CABLING. THE SYSTEM SHALL BE A CERTIFIED SOLUTION BY THE
CONNECTIVITY MANUFACTURER. THE HORIZONTAL INFRASTRUCTURE SHALL SUPPORT BOTH VOICE
AND DATA APPLICATIONS.
B.
THIS SECTION INCLUDES WIRE, CABLE, CONNECTING DEVICES, INSTALLATION, AND TESTING FOR
WIRING SYSTEMS TO BE USED AS SIGNAL PATHWAYS FOR VOICE, VIDEO, AND DATA
TRANSMISSION. THE SYSTEM SHALL INCLUDE BUT NOT BE LIMITED TO THE FOLLOWING:
1.
MOUNTING ELEMENTS
2. UNSHIELDED TWISTED-PAIR CABLE.
3. PATCH, STATION, AND CROSS CONNECT CORDS
4. JACKS AND FACEPLATES
5. TERMINATION AND PATCH PANELS
C.
MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE PRODUCTS BY ONE
OF THE FOLLOWING:
1.
2.
D.
SUNGLASS HUT
LA PLAZA MALL
HORIZONTAL CABLES FOR VOICE/DATA/VIDEO INFRASTRUCTURE:
1.
2.
3.
4.
5.
6.
E.
COPPER CABLES (UTP):
a.
BERK-TEK, INC.
b. BELDEN
c. MOHAWK
d. GENERAL
e. UNIPRISE
MODULAR JACKS AND FACEPLATES:
a. LEVITON
b. HUBBELL
c. ORTRONICS
d. PANDUIT
e. UNIPRISE
LISTED AS COMPLYING WITH CATEGORY 6 OF TIA/EIA.
CONDUCTORS: SOLID COPPER.
UTP CABLE: COMPLY WITH TIA/EIA. FOUR THERMOPLASTIC-INSULATED, INDIVIDUALLY TWISTED
PAIR OF CONDUCTORS; NO. 2 AWG, COLOR-CODED; ENCLOSE IN A JACKET.
CABLE RATING: PLENUM - LISTED FOR USE IN AIR-HANDLING SPACES,
NON-PLENUM IN ALL OTHER AREAS.
COLOR CODING: BLUE FOR DATA, YELLOW FOR VOICE AND WHITE FOR VIDEO
2200 S. 10TH STREET
McALLEN, TX 78503
SPACE #Q14-C
2.0 TYPE: PREMIUM
WORKSTATION OUTLETS: SINGLE JACK CONNECTOR ASSEMBLIES MOUNTED IN FACEPLATE.
1.
2.
3.
4.
SGH STORE #: 6078
FACEPLATE: HIGH IMPACT PLASTIC; COLOR TO BE WHITE.
MOUNTING: FLUSH, UNLESS OTHERWISE INDICATED.
LABELING: SHALL HAVE INTEGRAL LABEL WITH LABEL COVER.
JACK SPACES: AS INDICATED ON THE DRAWINGS WITH ANY NECESSARY BLANKS.
BLANKS SHALL MATCH FACEPLATE COVER.
DRAWN BY: EDS
REVIEWED BY: KAH
AUTHORIZED FOR:
ELECTRICAL
SPECIFICATIONS
STEM-MOUNTED FIXTURES SHALL BE MOUNTED SO AS TO BE ABSOLUTELY VERTICAL AND
HORIZONTAL. INSTALL AND SUPPORT AS SHOWN ON DRAWINGS.
5
A Subsidiary of the Luxottica Group
4000 Luxottica Place
Mason, Ohio 45040
CONSULTANT PROJECT # 150343
J.
ALL FIXTURES TO BE LISTED AND LABELED BY UNDERWRITERS LABORATORIES AND ALL BALLASTS
TO BE CBM CERTIFIED BY ETL.
C.
L.
10
FURNISH NEW AND UN-DETERIORATED MATERIALS OF A QUALITY NOT LESS THAN WHAT IS
SPECIFIED. ALL NEW MATERIAL SHALL HAVE MANUFACTURER'S NAME, MODEL NUMBER, OR OTHER
IDENTIFICATION MARKING.
26 51 00 INTERIOR LIGHTING
WHERE LIGHTING CONTACTORS ARE INDICATED ON THE DRAWINGS, THEY WILL BE FURNISHED AND
INSTALLED BY THE GENERAL CONTRACTOR COMPLETE WITH CONDUIT. THE GENERAL CONTRACTOR
WILL BE RESPONSIBLE TO INSTALL THE CONTACTORS AND PULL ALL WIRES AS DETAILED ON THESE J.
DRAWINGS AND CIRCUITED EXACTLY AS DIAGRAMMED ON THE ELECTRICAL DETAIL DRAWINGS. NO
VARIATIONS TO THE CIRCUITING ARE ALLOWED.
K.
26 27 26 WIRING DEVICES
INSTALL ALL WIRING DEVICES, INCLUDING SWITCHES, RECEPTACLES AND POWER RECEPTACLES,
TELEPHONE OUTLET BOXES, COVER PLATES AND BLANK OUTLET PLATES AS SHOWN OR
DESCRIBED ON DRAWINGS.
PROTECTIVE RELAYS SHALL HAVE ADJUSTABLE TIME DELAY RELAY IN CIRCUIT TO AVOID NUISANCE
SHUT DOWNS. TIME MARK OR SIMILAR EQUIPMENT IS ACCEPTABLE, IF PROTECTION IS NOT PART
OF STARTER. DO NOT RELY ON PROPERLY SIZED FUSES AND MOTOR STARTER OVERLOAD
HEATERS ALONE TO AVOID SINGLE PHASING BURNOUTS.
G.
A.
EXPOSED CONDUIT WILL BE PERMITTED IN ELECTRIC ROOMS, AND SIMILAR UNFINISHED SPACES,
OVERHEAD IN AREAS WITHOUT CEILINGS AND ELSEWHERE AT THE DISCRETION OF THE ARCHITECT. B.
9
PROVIDE ALL MATERIALS, LABOR, TOOLS, TRANSPORTATION INCIDENTALS AND APPURTENANCES
TO COMPLETE IN EVERY DETAIL AND LEAVE IN WORKING ORDER ALL WORK CALLED FOR HEREIN.
1.
COLOR OF DEVICES AND PLATES SHALL MATCH WALL. THE DEVICES SHALL BE OF THE TYPES AND
RATINGS LISTED, OR EQUALS BY ARROW-HART, GENERAL ELECTRIC OR PASS AND SEYMOUR.
WEATHERPROOF GFCI RECEPTACLES SHALL BE INSTALLED WHERE SHOWN ON DRAWINGS OR AS
REQUIRED BY CODE. DEVICES SHALL BE OF THE FOLLOWING SPECIFICATIONS, UNLESS
OTHERWISE INDICATED SPECIFICALLY ON PLANS.
A.
A
SWITCH HEIGHT 48" FROM FINISHED FLOOR TO CENTERLINE OF OUTLET.
CONVENIENCE OUTLETS:
a.
SALES: 16" FROM FINISHED FLOOR TO BOTTOM OF OUTLET.
b. NON-SALES: 16" FROM FINISHED FLOOR TO BOTTOM OF OUTLET
TELEPHONE OUTLETS SHALL BE LOCATED AS NOTED ON DRAWINGS.
PULL OR JUNCTION BOXES SHALL BE PROVIDED IN ALL RACEWAY SYSTEMS AT MAXIMUM OF 100
FOOT INTERVALS AND WHERE REQUIRED TO AVOID EXCESSIVE NUMBER OF BENDS, TO FACILITATE
WIRE PULLING OR TO PROVIDE ACCESS TO RACEWAY SYSTEM. BOXES AND COVERS SHALL BE
F.
WIRING DEVICES, UNLESS OTHERWISE PROPERLY AUTHORIZED, SHALL BE SAME MANUFACTURERS
GALVANIZED STEEL OF CODE GAUGE SIZE. TO THE EXTENT POSSIBLE, AVOID THE USE OF
ONLY; NO ADDITIONAL MANUFACTURERS SHALL BE PERMITTED UNLESS SPECIFICALLY
JUNCTION BOXES IN INACCESSIBLE LOCATIONS. THE USE OF JUNCTION BOXES ABOVE DRYWALL
AUTHORIZED BY TENANT OR TENANT'S REPRESENTATIVE.
CEILINGS SHALL BE LIMITED TO LOCATIONS NEAR ACCESS FRAMES USED FOR DIFFUSERS AND
RETURN AIR GRILLES OR ACCESS PANELS AS LOCATED ON PLANS. JUNCTION AND PULL BOXES
G. LOW VOLTAGE CONTROL DEVICES SHALL BE AS NOTED ON DRAWINGS OR AS REQUIRED.
MUST BE LABELED WITH CIRCUIT NUMBER IDENTIFICATION AND SYSTEM TYPE ON COVER.
26 29 13 MOTOR CONTROLLERS
RACEWAYS AND ENCLOSURES SHALL BE ADEQUATELY SUPPORTED FROM BUILDING STRUCTURE
WITH APPROVED SUPPORT RODS AND/OR CLAMPS.
A. GENERAL CONTRACTOR SHALL FURNISH AND INSTALL ALL MOTOR CONTROLS, INCLUDING
STARTERS, SAFETY DEVICES AND REMOTE CONTROL STATIONS, UNLESS FURNISHED BY
ALL CONDUIT SHALL BE RIGID HEAVYWALL GALVANIZED STEEL OR THIN WALL EMT WHERE
EQUIPMENT MANUFACTURER IN PRE-WIRED ASSEMBLIES.
PERMITTED BY CODE OR AS HEREINAFTER SPECIFIED. PVC SCHEDULE 80 CONDUIT MAY BE USED
UNDER FLOOR SLAB. ROMEX, BX OR AC, ETC., ARE NOT PERMITTED.
B. FURNISH AND INSTALL MANUAL MOTOR STARTERS WITH OVERLOAD RELAYS IN EACH LINE
CONDUCTOR FOR ALL FRACTIONAL HORSEPOWER MOTORS NOT EQUIPPED WITH BUILT-IN
MINIMUM SIZE OF CONDUIT SHALL BE 1/2" FOR INDIVIDUAL LIGHTING FIXTURE CONNECTIONS OR
RUNNING OVERCURRENT PROTECTION, NOT REQUIRING AUTOMATIC CONTROLLERS.
TO INDIVIDUAL LIGHT SWITCHES (IF ACCEPTABLE BY THE LANDLORD AND LOCAL CODE OFFICIALS)
AND 3/4" FOR ALL OTHER LOCATIONS. IF HVAC CONTROL WIRING IS REQUIRED TO BE RUN IN
C. MANUAL MOTOR STARTERS SHALL INCLUDE OVERLOAD RELAYS IN ALL LINE POLES SIZED TO TRIP
CONDUIT, IT SHALL BE A MINIMUM OF 1/2", UNLESS NOTED OTHERWISE ON DRAWINGS. ALL
SWITCH AT 125% OF MOTOR FULL LOAD RUNNING CURRENT, NEON PILOT LIGHTS, AND NEMA
IN/UNDER FLOOR CONDUIT SHALL BE OF MINIMUM 1" SIZE.
ENCLOSURES, AS MANUFACTURED BY GENERAL ELECTRIC, ALLEN BRADLEY, CUTLER HAMMER,
SIEMENS, OR SQUARE-D.
EMT THIN WALL CONDUIT MAY BE USED INSIDE HOLLOW PARTITIONS, AND ABOVE SUSPENDED
CEILINGS AND EXPOSED ABOVE 8'-0" ABOVE FINISHED FLOOR OR ABOVE PANELBOARDS. EMT
D. FURNISH AND INSTALL AUTOMATIC MOTOR STARTERS FOR ONE (1) HP OR LARGER SINGLE PHASE
CONDUIT MAY NOT BE USED BURIED IN EARTH OR FILL, IN OR UNDER CONCRETE FLOOR OR IN
AND THREE PHASE MOTORS OR MOTORIZED EQUIPMENT FURNISHED WITHOUT STARTERS,
POURED CONCRETE CONSTRUCTION.
REQUIRING AUTOMATIC STARTERS FOR CONTROL REGARDLESS OF HORSEPOWER RATING. ALL
THREE PHASE STARTERS SHALL HAVE ANTI-SINGLE PHASING, UNDERVOLTAGE PROTECTION, AND
PVC CONDUIT USED UNDER FLOOR SLABS SHALL HAVE RIGID GALVANIZED STEEL ELLS AND
PHASE REVERSAL PROTECTION RELAYS EITHER INCLUDED IN STARTERS OR WIRED TO STARTER
METALLIC CONDUIT ABOVE FLOOR SLAB.
CONTROL CIRCUIT.
V.
A.
A.
D.
E.
8
27 00 00 GENERAL REQUIREMENTS
DUPLEX RECEPTACLES SHALL BE A MINIMUM OF 20 AMPERE RATING.
ALL ELECTRICAL CONDUCTORS SHALL BE ENCLOSED IN CONTINUOUS GROUNDED RACEWAY
SYSTEM EXCEPT AS OTHERWISE NOTED (I.E. LOW-VOLTAGE PLENUM-RATED WIRE).
I.
7
C.
INSTALL BOXES RIGIDLY FROM BUILDING STRUCTURE AND SUPPORT INDEPENDENTLY OF THE
CONDUIT SYSTEM. ALSO PROVIDE SUITABLE BOX EXTENSIONS TO EXTEND BOXES TO FINISHED
FACES OF FLOORS, CEILINGS, WALLS ETC. ALL OUTLET BOXES TO BE PROVIDED WITH CADDY
"QUICK-MOUNT BOX SUPPORT" TO MINIMIZE THE DEFLECTION THAT OCCURS WHEN
PLUGGING/UNPLUGGING INTO THESE DEVICES.
NO OTHER CIRCUITS ARE TO BE RUN IN SAME CONDUIT FEEDING ISOLATED GROUND
RECEPTACLES.
6
UNLESS OTHERWISE NOTED ON DRAWINGS OR OTHERWISE REQUIRED BY THE NATIONAL
ELECTRICAL CODE, ACCESSIBILITY CODES OR LOCAL CODES, OUTLET HEIGHTS SHALL BE
AS FOLLOWS:
3.
EXTERIOR BOXES SHALL BE CAST RUST-RESISTING METAL WITH GASKETED COVERS.
H.
5
1.
2.
ALL OUTLET BOXES SHALL BE GALVANIZED PRESSED STEEL OF THE STANDARD KNOCKOUT TYPE.
NO ROUND OUTLET BOXES SHALL BE PERMITTED, EXCEPT AS SPECIFICALLY NOTED ON DRAWINGS.
CONCEALED BOXES SHALL NOT BE LESS THAN 4" SQUARE AND 1-1/2" DEEP, WITH PLASTER RINGS.
ALL KNOCKOUT BOXES, UPON WHICH LIGHTING FIXTURES ARE TO BE INSTALLED, SHALL BE
EQUIPPED WITH 3/8" FIXTURE STUDS.
G.
H
FURNISH AND INSTALL OUTLET BOXES FOR ALL DEVICES AS REQUIRED, (RECEPTACLES, LIGHTING
FIXTURES, MOTORS, SYSTEMS EQUIPMENT CONNECTIONS, SPECIAL OUTLETS AND AS OTHERWISE
REQUIRED).
C.
E.
4
LA PLAZA MALL
2
AT
1
8
9
10
11
12
13
14