cobalt w

Transcription

cobalt w
COBALT W
Water/water cooled chillers and heat pumps
172÷1527 kW
General information
Water-cooled water chillers with hermetic screw compressors and tube bundle heat exchangers. Designed for
installation indoors.
Configuration
/A: High performance unit
/LC: Motoevaporator
/DC: Unit with recovery condenser
/DS: Unit with desuperheater
/LN: Low-noise unit
/SLN: Super low-noise unit
COBALT W
INDEX
TECHNICAL FEATURES
3
VERSIONS4
ACCESSORY VERSIONS
4
ACCESSORIES5
TECHNICAL DATA COBALT W
6
TECHNICAL DATA COBALT W /A
9
TECHNICAL DATA COBALT W /LC
12
ELECTRICAL DATA COBALT W 14
ELECTRICAL DATA COBALT W /A
14
ELECTRICAL DATA COBALT W /LC
15
OPERATING LIMITS - COOLING - COBALT W COBALT W/A
16
OPERATING LIMITS - RECOVERY - COBALT W COBALT W/A
16
OPERATING LIMITS - COOLING - COBALT W /LC
17
COOLING CAPACITY - COBALT W
18
COOLING CAPACITY - COBALT W /A
21
COOLING CAPACITY - COBALT W /LC
24
RECOVERY CAPACITY - COBALT W /DC
27
SOUND LEVEL - COBALT W /A /LC - STANDARD UNIT
30
SOUND LEVEL - COBALT W /A /LC - LOW NOISE UNIT
31
SOUND LEVEL - COBALT W /A /LC - SUPER LOW NOISE UNIT
32
DIMENSIONAL DATA
33
INSTALLATION GUIDELINES
75
2
Swegon reserves the right to alter specifications.
www.swegon.com
COBALT W
TECHNICAL FEATURES
--alarm history.
• Power supply [V/f/Hz]: 400/3~/50 ±5%.
COMPRESSORS
CONTROL AND SAFETY DEVICES
Semi-hermetic screw compressors with continuous capacity
reduction from 50% to 100% which maximizes energy efficiency in all operating conditions. Machine start-up and shutdown occur with a 25% capacity reduction and by switching
the electric winding ”delta-star”.
Each compressor is equipped with a crankcase heater and
lubrication is provided by the difference between delivery and
intake pressure; the units with more compressors have separate refrigerant circuits.
The engine has a full electronic protection with temperature
sensors placed directly in the windings and on compressor
delivery line.
The compressor is installed on rubber anti-vibration mounts to
prevent vibration transmission to the unit.
EVAPORATOR AND CONDENSER
Sleeve tube bundle type with dry expansion evaporator; optimized for operation with R134a, enhance the COP value of the
unit, reducing the refrigerant load and the overall dimensions.
• manual reset high pressure controller;
• automatic reset high pressure safety switch with limited trip
controlled by the microprocessor;
• automatic reset low pressure safety switch with limited trip
controlled by the microprocessor;
• high pressure safety valve;
• anti-freeze probe on evaporator outlet;
• cooled water temperature control probe on evaporator outlet;
• compressor overtemperature protection;
• compressor cooling device with fluid injection;
• forced capacity reduction at high pressure.
TESTING
The units are factory-tested and supplied complete with oil
and refrigerant.
The evaporator is insulated with closed cell foam and is equipped with antifreeze protection temperature probe.
COOLING CIRCUIT
Each cooling circuit consists of: compressor delivery valve,
shut-off valve on fluid line, feeding plug, fluid sight glass,
dehydrating filter, electronic thermostatic expansion valve,
compressor cooling device with fluid injection, high pressure
switches (the low pressure control is provided by the pressure
transducers), safety valve.
ELECTRICAL PANEL
The electrical board consists of:
•
•
•
•
main disconnect switch;
fuses for main and auxiliary power circuit protection;
compressor remote switches;
microprocessor to control the following functions:
--control of ingoing water temperature;
--anti-freeze protection;
--compressor operation timers;
--automatic rotation of compressor start-up sequence;
--alarm signals;
--alarm reset;
--cumulative alarm contact for remote signaling;
--forced capacity reduction according to pressure limits;
--alarm history recording;
• display of:
--outgoing water temperature;
--currently set temperature and differential;
--alarm description;
--hour counter for operation, compressor and unit start-ups;
Swegon reserves the right to alter specifications.
www.swegon.com
3
COBALT W
VERSIONS
COBALT W /LC:
motoevaporator
The unit is not equipped with the water-cooled condenser
and therefore it can not be connected to a remote air-cooled
condenser.
The fluid receiver and the solenoid valve of the fluid line are
available as accessories. The unit is supplied without refrigerant
charge but pre-charged with nitrogen.
ACCESSORY VERSIONS
COBALT W /DC:
unit with recovery condenser
Available for all models, enables the full recovery of condensation heat.
In addition to COBALT W / COBALT W A standard version, the
unit has a heat recovery condenser on each cooling line used
exclusively for the production of domestic hot water.
The recovery water temperature and the recovery safety valve
disablement are controlled automatically by the microprocessor.
COBALT W /DS:
Potenza
Potenza
EER
EER
ESEER
ESEER
EER
EER
ESEER
ESEER
AA
172
172
5,26
5,26
5,97
5,97
4,43
4,43
5,40
5,40
STD
STD
ACCESSORIES
193
193
5,05
5,05
5,86
5,86
4,49
4,49
5,57
5,57
210
210
5,21
5,21
5,91
5,91
4,54
4,54
5,54
5,54
EER at 100% load
241
241
5,05
5,05
5,85
5,85
4,55
4,55
5,61
5,61
270
270
5,13
5,13
5,89
5,89
4,50
4,50
5,50
5,50
299
299
5,05
5,05
5,79
5,79
4,52
4,52
5,51
5,51
EER
EER
5,50
5,50
5,00
5,00
4,50
4,50
4,00
4,00
3,50
3,50
3,00
3,00
100
100
200
200
300
300
400
400
500
500
600
600
700
700
800
800
900
900
Cobalt W
W
Cobalt
1000 1100 1200 1300 1400 1500 1600
1000 1100 1200 1300 1400 1500 1600
Cobalt W /A
W /A
Cobalt
Cooling capacity [kW]
ESEER
ESEER
ESEER
6,50
6,50
6,00
6,00
5,50
5,50
5,00
5,00
4,50
4,50
4,00
4,00
100
100
200
200
300
300
400
400
500
500
600
600
700
700
Cobalt W
W
Cobalt
800
800
900
900
1000 1100 1200 1300 1400 1500 1600
1000 1100 1200 1300 1400 1500 1600
Cobalt W/A
W/A
Cobalt
Cooling capacity [kW]
unit with desuperheater
Available for all models, enables the partial recovery of condensation heat.
Dato che l'EER è sempre maggiore o uguale a 5.05, l'intera gamma ricade in Clas
Dato che l'EER è sempre maggiore o uguale a 5.05, l'intera gamma ricade in Clas
l' ff
ff
l'l'efficienza è ancora maggiora ad i carichi parziali (ESEER). l'efficienza è ancora maggiora ad i carichi parziali (ESEER). èè
dd
hh
ll ((
))
In addition to the components of COBALT W / COBALT W A
standard version, the unit has a heat recovery condenser (up to
20%) on each cooling line used for the production of domestic
hot water, (10% COBALT W A).
COBALT W /LN:
Low-noise unit
In addition to the components of COBALT W version, the unit
has soundproof housing consisting of a hard external hook in
galvanized painted steel sheet, insulated internally with soundproof material and a high impedance material interposed;
COBALT W /SLN:
Super low-noise unit
In addition to COBALT W /LN version, the unit has the compressor delivery and intake pipes insulated with high impedance soundproof material.
COBALT W /A:
high performance unit
The increased interest of customers in energy savings and the
standards more and more stringent concerning the environmental impact of industrialized products have led The company
to create a new range of high efficiency water/ water cooled
chillers.
Available for all standard units.
The values of
​​ EER and ESEER are diagrammed below and compared with the standard range. It is noted that even at part
load energy efficiency is kept at high values​​.
4
334
334
5,27
5,27
5,96
5,96
4,65
4,65
5,67
5,67
Swegon reserves the right to alter specifications.
www.swegon.com
COBALT W
REFRIGERANT CIRCUIT ACCESSORIES
• pressure relief valve for condensation control;
• dual set point (high/low temperature) with a single electronic expansion valve. The unit evaporator is sized according
to high temperature operation. The set point can be changed from the keyboard or the digital input, in this case it
must be specified in the order;
• high and low pressure switches are available for all models;
The intake and delivery pressures are detected by transducers, which allow the relative values to be read on the
control display.
• compressor intake valves;
• solenoid valve on the fluid line;
• kit for evaporator low water temperatures.
within +3°C and -8°C. It consists in a higher thermal insulation
of the exchanger and piping, a specific calibration of the low
pressure switches and of the anti-freeze alarm, and dimensioning check of the mechanical thermostatic valve.
If it is not included in the set-up, the “Check condensation”
accessory must be added.
ELECTRICAL ACCESSORIES
• Bacnet, LonWorks, Ethernet, Modbus, SNMP, FTP, HTTP
serial interface.
• power factor correction cosφ ≥ 0.9 under nominal operating
conditions; supplied as standard
• remote user terminal (in addition to the standard one);
• remote signal variable set point (0-1V, 0-10V, 0-4mA,020mA);
• Operation voltage-free contacts;
• Automatic circuit breakers;
• Maximum and minimum voltage relè;
• Power supply 415/3/50
• Absorbed current limit;
• Relè Management PSM;
• Electronic soft-starter;
• Automatic circuit breakers for compressors;
• SMARTLINK.
MISCELLANEOUS ACCESSORIES
•
•
•
•
Rubber antivibration mounts;
Spring anti-vibration mounts;
Packaging in wooden crates;
Supplied pre-assembled.
DOUBLE SET-POINT
The microprocessor enables you to set two set temperatures
for the production of cold and hot water. Unless specified otherwise in the order, the default values are 12/7 °C and 15/10
°C for chiller mode and 40/45 °C and 35/40 °C for heat pump
mode. The set temperatures must, in any case, remain within
the operating ranges of the unit.
Use either the keypad or the digital input to switch between
the first and second set. For series that do not permit the
simultaneous selection of “Select summer/winter mode with
digital input” and “Double set point with digital input”, summer/winter mode can be selected only on the keypad while the
double set point still uses the digital input, as per our standard
“BRINE KIT” ACCESSORY
It is applied if the evaporator output temperature is included
Swegon reserves the right to alter specifications.
www.swegon.com
5
COBALT W
TECHNICAL DATA COBALT W
Unit size
Cooling (Gross values)
Nominal cooling capacity
Total power input for cooling
EER
ESEER
Efficiency class
Cooling (EN 14511 values)
Nominal cooling capacity
EER
ESEER
Efficiency class
Compressors
Type
Quantity/Cooling circuits
Capacity steps
Total oil load
Refrigerant total load
Evaporator
Water flow
Pressure drop
Condenser
Water flow
Pressure drop
Noise levels
Noise power level
Noise pressure level
Noise power level (LN version)
Noise pressure level (LN version )
Noise power level (SLN version)
Noise pressure level (SLN version )
Basic version dimensions and weights
Length
Depth
Height
Operating weight
18.1
20.1
22.1
24.1
27.1
31.1
35.1
36.2
38.2
41.2
42.1
45.2
kW
kW
172
39
4,43
5,40
C
193
43
4,49
5,57
C
210
46
4,54
5,54
C
241
53
4,55
5,61
C
270
60
4,50
5,50
C
299
66
4,52
5,51
C
334
72
4,65
5,67
B
346
78
4,45
5,43
C
368
81
4,54
5,50
C
389
86
4,53
5,53
C
407
90
4,52
5,51
C
427
93
4,58
5,59
C
(1),(5) kW
(1),(5)
(5)
171
4,27
4,81
C
192
4,30
4,89
C
209
4,35
4,85
C
240
4,38
4,95
C
269
4,34
4,84
C
298
4,34
4,78
C
333
4,48
4,97
C
345
4,29
4,78
C
367
4,39
4,86
C
388
4,38
4,87
C
405
4,37
4,84
C
425
4,41
4,88
C
1
1
1
1
1
2
2
2
1
2
14
32
16
32
16
30
16
34
15
40
28
62
30
62
32
62
20
74
32
60
(1)
(1)
(1)
n°/n°
n°
l
kg
(1)
(2)
l/h 29.579 33.190 36.113 41.445 46.432 51.419 57.438 59.501 63.285 66.896 69.991 73.431
kPa
35
51
49
44
43
52
40
48
43
47
47
52
(1)
l/h 36.251 40.585 44.076 50.559 56.750 62.803 69.785 72.880 77.214 81.668 85.469 89.458
kPa
29
29
32
30
33
37
38
29
29
29
31
32
(3)
(4)
(3)
(4)
(3)
(4)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
84
67
80
63
73
56
84
67
80
63
73
56
84
67
80
63
73
56
87
70
82
65
76
59
89
72
84
67
78
61
91
74
87
70
80
63
93
75
88
70
81
63
89
71
85
67
78
60
87
69
83
65
76
58
87
69
83
65
75
57
97
79
93
75
86
68
87
69
82
64
76
58
mm
mm
mm
kg
3.410
900
1.370
1.224
3.410
900
1.370
1.318
3.410
900
1.370
1.297
2.440
1.200
1.460
1.471
2.440
1.200
1.460
1.596
2.440
1.200
1.460
1.669
3.430
1.250
1.400
1.648
3.630
1.250
1.580
2.097
3.630
1.250
1.600
2.192
3.630
1.250
1.600
2.285
3.530
1.260
1.420
1.779
3.630
1.250
1.600
2.243
(1) Water temperature at evaporator inlet-outlet 12-7°C; water temperature at condenser inletoutlet 30-35°C;
(2) Water temperature at evaporator inlet-outlet 12-7°C
(3) Calculated according to ISO 3744 under nominal operating conditions.
(4) Sound pressure levels measured at 1 metres from the unit in free field under nominal working
6
Screw
1
1
Continue
18
20
46
79
conditions, according to ISO 3744
(5) Values in compliance with EN 14511-3:2011
This data sheet shows the data of the basic and standard series; for further details refer to the
specific documentation.
Swegon reserves the right to alter specifications.
www.swegon.com
COBALT W
TECHNICAL DATA COBALT W
Unit size
Cooling (Gross values)
Nominal cooling capacity
Total power input for cooling
EER
ESEER
Efficiency class
Cooling (EN 14511 values)
Nominal cooling capacity
EER
ESEER
Efficiency class
Compressors
Type
Quantity/Cooling circuits
Capacity steps
Total oil load
Refrigerant total load
Evaporator
Water flow
Pressure drop
Condenser
Water flow
Pressure drop
Noise levels
Noise power level
Noise pressure level
Noise power level (LN version)
Noise pressure level (LN version )
Noise power level (SLN version)
Noise pressure level (SLN version )
Basic version dimensions and weights
Length
Depth
Height
Operating weight
46.2
49.2
53.2
57.2
62.2
65.2
69.2
72.2
76.2
78.2
83.2
88.2
kW
kW
458
100
4,60
5,54
C
490
106
4,62
5,61
C
527
115
4,58
5,58
C
569
127
4,48
5,50
C
607
133
4,56
5,55
C
642
139
4,62
5,62
C
672
144
4,67
5,51
B
712
154
4,64
5,63
C
753
166
4,54
5,53
C
780
163
4,80
5,62
B
831
181
4,59
5,59
C
878
192
4,57
5,42
C
(1),(5) kW
(1),(5)
(5)
457
4,46
4,90
C
488
4,47
4,94
C
525
4,43
4,92
C
567
4,32
4,78
C
604
4,39
4,81
C
640
4,48
4,97
C
670
4,52
4,84
C
710
4,50
4,99
C
751
4,40
4,89
C
778
4,65
4,96
B
828
4,45
4,92
C
875
4,39
4,65
C
2
2
2
2
2
2
2
2
2
2
32
60
32
71
30
81
33
83
36
76
43
142
46
146
40
160
51
180
56
190
(1)
(1)
(1)
n°/n°
n°
l
kg
Screw
2
2
Continue
38
40
129
160
(1)
(2)
l/h 78.762 84.265 90.628 97.850 104.385 110.404 115.563 122.442 129.493 134.136 142.906 151.055
kPa
38
42
43
55
60
37
39
36
40
41
46
48
(1)
l/h 95.873 102.494 110.404 119.690 127.257 134.308 140.327 148.839 158.040 162.081 174.033 184.141
kPa
33
33
32
33
33
33
38
33
32
32
31
51
(3)
(4)
(3)
(4)
(3)
(4)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
87
69
82
64
76
58
87
69
82
64
76
58
87
69
82
64
75
57
91
73
87
69
80
62
93
75
88
70
81
63
91
72
87
68
80
61
96
77
91
72
84
65
96
77
92
73
85
66
97
78
92
73
85
66
98
79
93
74
86
67
100
81
95
76
88
69
100
81
95
76
89
70
mm
mm
mm
kg
3.640
1.250
1.690
2.431
3.640
1.250
1.690
2.469
3.640
1.250
1.690
2.730
3.640
1.250
1.690
2.807
3.640
1.250
1.690
2.887
4.070
1.280
1.900
3.138
4.070
1.280
1.900
3.097
4.060
1.280
1.950
3.303
4.060
1.280
1.950
3.371
4.060
1.280
1.950
3.365
4.060
1.280
1.950
3.354
4.770
1.460
2.150
3.975
(1) Water temperature at evaporator inlet-outlet 12-7°C; water temperature at condenser inletoutlet 30-35°C;
(2) Water temperature at evaporator inlet-outlet 12-7°C
(3) Calculated according to ISO 3744 under nominal operating conditions.
(4) Sound pressure levels measured at 1 metres from the unit in free field under nominal working
Swegon reserves the right to alter specifications.
conditions, according to ISO 3744
(5) Values in compliance with EN 14511-3:2011
This data sheet shows the data of the basic and standard series; for further details refer to the
specific documentation.
www.swegon.com
7
COBALT W
TECHNICAL DATA COBALT W
Unit size
Cooling (Gross values)
Nominal cooling capacity
Total power input for cooling
EER
ESEER
Efficiency class
Cooling (EN 14511 values)
Nominal cooling capacity
EER
ESEER
Efficiency class
Compressors
Type
Quantity/Cooling circuits
Capacity steps
Total oil load
Refrigerant total load
Evaporator
Water flow
Pressure drop
Condenser
Water flow
Pressure drop
Noise levels
Noise power level
Noise pressure level
Noise power level (LN version)
Noise pressure level (LN version )
Noise power level (SLN version)
Noise pressure level (SLN version )
Basic version dimensions and weights
Length
Depth
Height
Operating weight
95.2
(1)
(1)
(1)
100.2 105.2 110.2 117.2 124.2 130.3 137.3 143.3 147.3 153.3
kW
kW
946
199
4,74
5,56
B
993
218
4,55
5,40
C
1049
221
4,74
5,60
B
1091
239
4,56
5,39
C
1171
254
4,62
5,41
C
1225
267
4,59
5,52
C
1282
281
4,56
5,46
C
1369
297
4,61
5,49
C
1424
311
4,58
5,47
C
1464
318
4,60
5,49
C
1527
326
4,68
5,60
B
(1),(5) kW
(1),(5)
(5)
942
4,55
4,73
C
989
4,35
4,56
C
1044
4,52
4,71
C
1087
4,40
4,65
C
1167
4,44
4,62
C
1221
4,41
4,68
C
1278
4,39
4,67
C
1364
4,43
4,68
C
1418
4,39
4,61
C
1457
4,40
4,62
C
1520
4,47
4,76
C
2
2
2
2
3
3
3
3
40
160
51
180
56
190
56
195
79
250
84
270
84
280
84
290
n°/n°
n°
l
kg
(1)
(2)
l/h 134.136 142.906 151.055 162.683 201.431 210.711 220.546 235.409 244.911 251.752 262.622
kPa
41
46
48
54
50
55
53
58
69
72
75
(1)
l/h 162.081 174.033 184.141 196.973 245.059 256.592 268.904 286.450 298.359 306.438 318.684
kPa
32
31
51
54
54
57
50
50
54
54
54
(3)
(4)
(3)
(4)
(3)
(4)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
98
79
93
74
86
67
100
81
95
76
88
69
100
81
95
76
89
70
100
81
95
76
89
70
101
81
96
76
90
70
101
81
96
76
91
71
101
81
96
76
91
71
101
81
96
76
91
71
101
81
96
76
91
71
101
81
97
77
91
71
101
81
97
77
91
71
mm
mm
mm
kg
4.060
1.280
1.950
3.365
4.060
1.280
1.950
3.354
4.770
1.460
2.150
3.975
4.770
1.460
2.150
4.080
4.770
1.420
2.220
4.772
4.770
1.420
2.220
4.810
4.450
2.130
2.300
6.192
4.450
2.130
2.300
6.297
4.450
2.130
2.300
6.402
4.450
2.130
2.300
6.492
4.450
2.130
2.300
6.581
(1) Water temperature at evaporator inlet-outlet 12-7°C; water temperature at condenser inletoutlet 30-35°C;
(2) Water temperature at evaporator inlet-outlet 12-7°C
(3) Calculated according to ISO 3744 under nominal operating conditions.
(4) Sound pressure levels measured at 1 metres from the unit in free field under nominal working
8
Screw
2
3
Continue
56
56
74
220
230
225
2
conditions, according to ISO 3744
(5) Values in compliance with EN 14511-3:2011
This data sheet shows the data of the basic and standard series; for further details refer to the
specific documentation.
Swegon reserves the right to alter specifications.
www.swegon.com
COBALT W
TECHNICAL DATA COBALT W /A
Unit size
Cooling (Gross values)
Nominal cooling capacity
Total power input for cooling
EER
ESEER
Efficiency class
Cooling (EN 14511 values)
Nominal cooling capacity
EER
ESEER
Efficiency class
Compressors
Type
Quantity/Cooling circuits
Capacity steps
Total oil load
Refrigerant total load
Evaporator
Water flow
Pressure drop
Condenser
Water flow
Pressure drop
Noise levels
Noise power level
Noise pressure level
Noise power level (LN version)
Noise pressure level (LN version )
Noise power level (SLN version)
Noise pressure level (SLN version )
Basic version dimensions and weights
Length
Depth
Height
Operating weight
18.1
20.1
22.1
24.1
27.1
31.1
35.1
36.2
38.2
41.2
42.1
45.2
kW
kW
186
35
5,32
5,97
A
206
39
5,28
5,86
A
223
42
5,27
5,91
A
256
49
5,26
5,85
A
284
54
5,28
5,89
A
317
61
5,23
5,79
A
364
69
5,27
5,96
A
368
70
5,28
5,98
A
391
74
5,28
5,91
A
413
79
5,23
5,84
A
419
79
5,33
6,01
A
448
85
5,27
5,96
A
(1),(5) kW
(1),(5)
(5)
185
5,09
5,24
A
205
5,08
5,17
A
222
5,09
5,27
A
255
5,07
5,14
A
283
5,09
5,22
A
315
5,07
5,16
A
362
5,08
5,23
A
367
5,11
5,34
A
389
5,10
5,23
A
411
5,06
5,18
A
417
5,13
5,24
A
446
5,09
5,27
A
1
1
1
1
1
2
2
2
1
2
14
35
16
35
16
33
16
37
15
44
28
68
30
68
32
68
20
81
32
66
(1)
(1)
(1)
n°/n°
n°
l
kg
Screw
1
1
Continue
18
20
51
87
(1)
(2)
l/h 31.860 34.662 37.863 43.254 48.443 53.368 62.592 63.354 66.711 70.001 71.991 77.007
kPa
67
59
59
50
60
52
57
58
66
57
56
65
(1)
l/h
kPa
(3)
(4)
(3)
(4)
(3)
(4)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
84
67
80
63
73
56
84
67
80
63
73
56
84
67
80
63
73
56
87
70
82
65
76
59
89
72
84
67
78
61
mm
mm
mm
kg
3.420
960
1.370
1.240
3.420
960
1.370
1.278
3.420
960
1.400
1.398
2.450
1.340
1.460
1.374
2.450
1.340
1.540
1.704
37.913 41.524 45.137 51.818 57.884 63.927
13
14
7
22
11
11
(1) Water temperature at evaporator inlet-outlet 12-7°C; water temperature at condenser inletoutlet 30-35°C;
(2) Water temperature at evaporator inlet-outlet 12-7°C
(3) Calculated according to ISO 3744 under nominal operating conditions.
(4) Sound pressure levels measured at 1 metres from the unit in free field under nominal working
Swegon reserves the right to alter specifications.
74.475
18
75.357
7
79.574 83.689 85.508 91.625
8
12
24
9
91
74
87
70
80
63
93
75
88
70
81
63
89
71
85
67
78
60
87
69
83
65
76
58
87
69
83
65
75
57
97
79
93
75
86
68
87
69
82
64
76
58
2.450
1.340
1.540
1.774
3.530
1.350
1.470
1.605
3.890
1.380
1.730
2.335
3.890
1.380
1.730
2.361
3.890
1.380
1.730
2.441
3.530
1.350
1.470
1.792
3.890
1.380
1.730
2.497
conditions, according to ISO 3744
(5) Values in compliance with EN 14511-3:2011
This data sheet shows the data of the basic and standard series; for further details refer to the
specific documentation.
www.swegon.com
9
COBALT W
TECHNICAL DATA COBALT W /A
Unit size
Cooling (Gross values)
Nominal cooling capacity
Total power input for cooling
EER
ESEER
Efficiency class
Cooling (EN 14511 values)
Nominal cooling capacity
EER
ESEER
Efficiency class
Compressors
Type
Quantity/Cooling circuits
Capacity steps
Total oil load
Refrigerant total load
Evaporator
Water flow
Pressure drop
Condenser
Water flow
Pressure drop
Noise levels
Noise power level
Noise pressure level
Noise power level (LN version)
Noise pressure level (LN version )
Noise power level (SLN version)
Noise pressure level (SLN version )
Basic version dimensions and weights
Length
Depth
Height
Operating weight
46.2
49.2
53.2
57.2
62.2
65.2
69.2
72.2
76.2
78.2
83.2
88.2
kW
kW
487
93
5,26
5,91
A
521
99
5,24
5,96
A
569
109
5,22
5,81
A
603
115
5,24
5,80
A
639
122
5,26
5,86
A
692
132
5,24
5,98
A
730
137
5,31
5,99
A
755
144
5,24
5,93
A
795
151
5,27
5,99
A
822
155
5,29
6,02
A
858
160
5,37
6,10
A
931
178
5,23
5,94
A
(1),(5) kW
(1),(5)
(5)
485
5,10
5,22
A
519
5,07
5,24
A
567
5,06
5,15
A
600
5,08
5,14
A
636
5,09
5,17
A
690
5,07
5,27
A
728
5,16
5,28
A
753
5,09
5,22
A
793
5,10
5,25
A
820
5,12
5,23
A
855
5,17
5,27
A
928
5,06
5,13
A
2
2
2
2
2
2
2
2
2
2
32
66
32
78
30
89
33
91
36
84
43
156
46
161
43
172
40
176
51
198
(1)
(1)
(1)
n°/n°
n°
l
kg
(1)
(2)
l/h 82.784 88.967 96.067 101.662 108.694 119.077 125.584 129.444 136.767 141.402 147.521 158.320
kPa
49
55
56
62
68
52
56
45
48
50
53
57
(1)
l/h 98.846 106.061 115.052 121.679 129.812 141.794 149.212 154.397 162.700 168.109 175.002 189.240
kPa
18
18
12
10
10
18
16
23
25
29
33
29
(3)
(4)
(3)
(4)
(3)
(4)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
87
69
82
64
76
58
87
69
82
64
76
58
87
69
82
64
75
57
91
73
87
69
80
62
93
75
88
70
81
63
91
72
87
68
80
61
96
77
91
72
84
65
96
77
92
73
85
66
97
78
92
73
85
66
98
79
93
74
86
67
100
81
95
76
88
69
100
81
95
76
89
70
mm
mm
mm
kg
3.890
1.380
1.780
2.547
3.890
1.380
1.780
2.592
3.890
1.380
1.780
2.870
3.890
1.380
1.780
3.004
3.890
1.380
1.780
3.102
4.250
1.380
2.040
3.266
4.250
1.380
2.040
3.244
4.250
1.380
2.000
3.261
4.250
1.380
2.000
3.310
4.250
1.380
2.000
3.282
4.250
1.380
2.000
3.272
4.770
1.460
2.150
3.971
(1) Water temperature at evaporator inlet-outlet 12-7°C; water temperature at condenser inletoutlet 30-35°C;
(2) Water temperature at evaporator inlet-outlet 12-7°C
(3) Calculated according to ISO 3744 under nominal operating conditions.
(4) Sound pressure levels measured at 1 metres from the unit in free field under nominal working
10
Screw
2
2
Continue
38
40
142
176
conditions, according to ISO 3744
(5) Values in compliance with EN 14511-3:2011
This data sheet shows the data of the basic and standard series; for further details refer to the
specific documentation.
Swegon reserves the right to alter specifications.
www.swegon.com
COBALT W
TECHNICAL DATA COBALT W /A
Unit size
Cooling (Gross values)
Nominal cooling capacity
Total power input for cooling
EER
ESEER
Efficiency class
Cooling (EN 14511 values)
Nominal cooling capacity
EER
ESEER
Efficiency class
Compressors
Type
Quantity/Cooling circuits
Capacity steps
Total oil load
Refrigerant total load
Evaporator
Water flow
Pressure drop
Condenser
Water flow
Pressure drop
Noise levels
Noise power level
Noise pressure level
Noise power level (LN version)
Noise pressure level (LN version )
Noise power level (SLN version)
Noise pressure level (SLN version )
Basic version dimensions and weights
Length
Depth
Height
Operating weight
95.2
100.2 105.2 110.2 117.2 124.2 130.3 137.3 143.3 147.3 153.3
kW
kW
994
189
5,26
5,98
A
1048
200
5,24
5,98
A
1093
208
5,25
5,98
A
1160
221
5,25
5,96
A
1233
235
5,25
5,94
A
1296
247
5,25
5,97
A
1349
258
5,23
5,97
A
1428
271
5,27
5,96
A
1480
283
5,23
5,93
A
1525
291
5,24
5,96
A
1575
299
5,27
5,95
A
(1),(5) kW
(1),(5)
(5)
990
5,08
5,16
A
1044
5,07
5,21
A
1089
5,09
5,21
A
1156
5,08
5,16
A
1229
5,07
5,10
A
1291
5,06
5,10
A
1345
5,06
5,12
A
1423
5,07
5,03
A
1476
5,09
5,23
A
1520
5,08
5,13
A
1569
5,10
5,11
A
1
2
2
2
3
3
3
3
56
209
56
215
56
223
56
231
79
275
84
297
84
308
84
319
(1)
(1)
(1)
n°/n°
n°
l
kg
Screw
2
3
Continue
56
56
74
242
253
248
2
(1)
(2)
l/h 169.449 178.248 186.346 197.253 209.657 220.213 228.421 242.416 251.844 259.664 267.484
kPa
64
53
57
49
59
64
57
70
42
58
61
(1)
l/h 202.536 213.038 222.734 235.774 250.620 263.240 273.580 289.793 301.061 310.412 319.762
kPa
27
26
24
33
34
35
36
43
24
33
29
(3)
(4)
(3)
(4)
(3)
(4)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
100
81
95
76
89
70
100
81
95
76
89
70
100
81
95
76
90
71
100
80
96
76
90
70
101
81
96
76
90
70
101
81
96
76
91
71
101
81
96
76
91
71
101
81
96
76
91
71
101
81
96
76
91
71
101
81
97
77
91
71
101
81
97
77
91
71
mm
mm
mm
kg
4.770
1.460
2.150
4.088
4.770
1.460
2.150
4.213
4.770
1.460
2.150
4.302
4.770
1.420
2.220
4.724
4.770
1.420
2.220
4.754
4.770
1.420
2.220
4.784
4.450
2.130
2.300
6.282
4.450
2.130
2.300
6.377
4.450
2.130
2.300
6.507
4.450
2.130
2.300
6.627
4.450
2.130
2.300
6.734
(1) Water temperature at evaporator inlet-outlet 12-7°C; water temperature at condenser inletoutlet 30-35°C;
(2) Water temperature at evaporator inlet-outlet 12-7°C
(3) Calculated according to ISO 3744 under nominal operating conditions.
(4) Sound pressure levels measured at 1 metres from the unit in free field under nominal working
Swegon reserves the right to alter specifications.
conditions, according to ISO 3744
(5) Values in compliance with EN 14511-3:2011
This data sheet shows the data of the basic and standard series; for further details refer to the
specific documentation.
www.swegon.com
11
COBALT W
TECHNICAL DATA COBALT W /LC
Unit size
18.1
20.1
Cooling (Gross values)
(1) kW
143
172
Nominal cooling capacity
(1) kW
44
50
Total power input for cooling
(1)
3,30
3,47
EER
Cooling (EN 14511 values)
(1),(5) kW
143
171
Nominal cooling capacity
(1),(5)
3,25
3,40
EER
Compressors
Type
n°/n°
1/1
1/1
Quantity/Cooling circuits
n°
Capacity steps
l
14
16
Total oil load
Evaporator
(1)
l/h 24.660 29.531
Water flow
(2) kPa
28
41
Pressure drop
Noise levels
(3) dB(A)
84
84
Noise power level
(4) dB(A) 67
67
Noise pressure level
(3) dB(A) 80
80
Noise power level (LN version)
(4) dB(A) 63
63
Noise pressure level (LN version )
(3) dB(A) 73
73
Noise power level (SLN version)
(4) dB(A)
56
56
Noise pressure level (SLN version )
Basic version dimensions and weights
mm 2.500 2.500
Length
mm 1.200 1.200
Depth
mm 1.250 1.250
Height
kg 1.190 1.278
Operating weight
Grandezza unità
46.2
49.2
Cooling (Gross values)
(1) kW
402
426
Nominal cooling capacity
(1) kW
115
122
Total power input for cooling
(1)
3,51
3,49
EER
Cooling (EN 14511 values)
(1),(5) kW
401
425
Nominal cooling capacity
(1),(5)
3,47
3,45
EER
Compressors
Type
n°/n° 2/2
2/2
Quantity/Cooling circuits
n°
Capacity steps
l
32
32
Total oil load
Evaporator
(1)
l/h 69.087 73.279
Water flow
(2) kPa
31
35
Pressure drop
Noise levels
(3) dB(A)
87
87
Noise power level
(4) dB(A) 69
69
Noise pressure level
(3) dB(A) 82
82
Noise power level (LN version)
(4) dB(A) 64
64
Noise pressure level (LN version )
(3) dB(A)
76
76
Noise power level (SLN version)
(4) dB(A)
58
58
Noise pressure level (SLN version )
Basic version dimensions and weights
mm 3.700 3.700
Length
mm 1.250 1.250
Depth
mm 1.360 1.360
Height
kg 2.118 2.148
Operating weight
22.1
24.1
27.1
31.1
35.1
36.2
38.2
41.2
42.1
45.2
180
53
3,40
214
61
3,51
236
69
3,43
266
77
3,45
283
84
3,37
293
87
3,37
322
94
3,44
340
99
3,43
341
96
3,55
368
106
3,47
180
3,34
213
3,45
236
3,37
265
3,40
282
3,33
292
3,32
321
3,39
339
3,38
340
3,50
366
3,42
1/1
1/1
1/1
2/2
2/2
2/2
1/1
2/2
16
16
15
28
30
32
20
32
31.006 36.822 40.650 45.727 48.702 50.421 55.324 58.469 58.641 63.250
40
37
36
43
33
40
34
38
38
42
84
67
80
63
73
56
87
70
82
65
76
59
89
72
84
67
78
61
91
74
87
70
80
63
93
75
88
70
81
63
89
71
85
67
78
60
87
69
83
65
76
58
87
69
83
65
75
57
97
79
93
75
86
68
87
69
82
64
76
58
2.500
1.200
1.250
1.256
2.600
1.200
1.320
1.296
2.600
1.200
1.320
1.417
2.600
1.200
1.320
1.487
3.600
1.250
1.370
1.471
3.600
1.250
1.250
1.809
3.600
1.250
1.250
1.895
3.600
1.250
1.250
1.981
3.600
1.250
1.370
1.516
3.600
1.250
1.250
1.938
53.2
57.2
62.2
65.2
69.2
72.2
76.2
78.2
83.2
88.2
465
137
3,39
506
146
3,47
541
154
3,51
558
162
3,45
575
169
3,40
620
177
3,51
640
183
3,50
665
188
3,54
697
193
3,61
769
216
3,56
464
3,35
504
3,41
539
3,45
556
3,41
573
3,36
619
3,48
639
3,46
663
3,50
695
3,56
767
3,51
2/2
2/2
2/2
2/2
2/2
2/2
2/2
2/2
30
33
36
43
46
43
40
51
Screw
2/2
2/2
Continue
38
40
79.983 87.042 92.984 95.924 98.831 106.638 110.129 114.294 119.897 132.244
35
44
49
31
34
28
30
32
38
40
87
69
82
64
75
57
91
73
87
69
80
62
93
75
88
70
81
63
91
72
87
68
80
61
96
77
91
72
84
65
96
77
92
73
85
66
97
78
92
73
85
66
98
79
93
74
86
67
100
81
95
76
88
69
100
81
95
76
89
70
3.700
1.250
1.360
2.389
3.700
1.250
1.360
2.458
3.700
1.250
1.360
2.529
4.070
1.280
1.570
2.781
4.070
1.280
1.570
2.741
4.070
1.280
1.550
2.800
4.070
1.280
1.550
2.861
4.070
1.280
1.550
2846
4.070
1.280
1.550
2826
4.710
1.350
1.630
3415
(1) Water temperature at evaporator inlet-outlet 12-7°C; water temperature at condenser inletoutlet 30-35°C;
(2) Water temperature at evaporator inlet-outlet 12-7°C
(3) Calculated according to ISO 3744 under nominal operating conditions.
(4) Sound pressure levels measured at 1 metres from the unit in free field under nominal working
12
Screw
1/1
1/1
Continue
18
20
conditions, according to ISO 3744
(5) Values in compliance with EN 14511-3:2011
This data sheet shows the data of the basic and standard series; for further details refer to the
specific documentation.
Swegon reserves the right to alter specifications.
www.swegon.com
COBALT W
TECHNICAL DATA COBALT W /LC
Unit size
Cooling (Gross values)
Nominal cooling capacity
Total power input for cooling
EER
Cooling (EN 14511 values)
Nominal cooling capacity
EER
Compressors
Type
Quantity/Cooling circuits
Capacity steps
Total oil load
Evaporator
Water flow
Pressure drop
Noise levels
Noise power level
Noise pressure level
Noise power level (LN version)
Noise pressure level (LN version )
Noise power level (SLN version)
Noise pressure level (SLN version )
Basic version dimensions and weights
Length
Depth
Height
Operating weight
95.2
(1)
(1)
(1)
100.2 105.2 110.2 117.2 124.2 130.3 137.3 143.3 147.3 153.3
kW
kW
833
227
3,67
895
243
3,69
941
258
3,65
991
268
3,70
1062
285
3,73
1112
301
3,69
1154
317
3,65
1202
329
3,66
1271
342
3,72
1300
353
3,68
1357
372
3,65
(1),(5) kW
(1),(5)
830
3,62
892
3,63
937
3,58
989
3,65
1059
3,68
1108
3,64
1150
3,59
1198
3,60
1266
3,65
1294
3,61
1351
3,58
n°/n°
n°
l
2/2
2/2
2/2
2/2
2/2
3/3
3/3
3/3
3/3
3/3
56
56
56
56
56
74
79
84
84
84
(1)
(2)
(3)
(4)
(3)
(4)
(3)
(4)
Screw
2/2
Continue
56
l/h 143.272 153.994 161.758 170.447 182.648 191.152 198.454 206.681 218.512 223.504 233.302
kPa
44
55
58
35
40
41
44
47
57
60
63
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
100
81
95
76
89
70
100
81
95
76
89
70
100
81
95
76
90
71
100
80
96
76
90
70
101
81
96
76
90
70
101
81
96
76
91
71
101
81
96
76
91
71
101
81
96
76
91
71
101
81
96
76
91
71
101
81
97
77
91
71
101
81
97
77
91
71
mm
mm
mm
kg
4.710
1.350
1.630
3508
4.710
1.350
1.630
3600
4.710
1.350
1.630
3690
4.770
1.350
1.700
4116
4.770
1.350
1.700
4158
4.770
1.350
1.700
4188
4.450
2.130
1.770
5800
4.450
2.130
1.770
5958
4.450
2.130
1.770
6118
4.450
2.130
1.770
6172
4.450
2.130
1.770
6220
(1) Water temperature at evaporator inlet-outlet 12-7°C; water temperature at condenser inletoutlet 30-35°C;
(2) Water temperature at evaporator inlet-outlet 12-7°C
(3) Calculated according to ISO 3744 under nominal operating conditions.
(4) Sound pressure levels measured at 1 metres from the unit in free field under nominal working
Swegon reserves the right to alter specifications.
conditions, according to ISO 3744
(5) Values in compliance with EN 14511-3:2011
This data sheet shows the data of the basic and standard series; for further details refer to the
specific documentation.
www.swegon.com
13
COBALT W
ELECTRICAL DATA COBALT W
Unit size
Maximum absorbed power
Maximum absorbed current
Maximum input current
Main power supply
Auxiliary power supply
(1)
(2)
(3)
kW
A
A
20.1
22.1
24.1
27.1
31.1
35.1
36.2
38.2
41.2
42.1
45.2
63
104
167
72
118
208
78
127
208
89
146
240
100
164
230
112
183
282
123
202
282
126
207
271
135
222
312
144
236
326
140
229
305
155
254
335
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
46.2
49.2
53.2
57.2
62.2
65.2
69.2
72.2
76.2
78.2
83.2
88.2
166
273
367
178
291
386
200
327
394
212
347
446
224
367
465
235
385
465
246
403
484
256
419
507
265
435
523
272
447
523
279
458
534
315
517
706
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
V/ph/Hz 400/3~/50
V/ph/Hz 230/1~/50
Unit size
Maximum absorbed power
Maximum absorbed current
Maximum input current
Main power supply
Auxiliary power supply
18.1
(1)
(2)
(3)
kW
A
A
V/ph/Hz 400/3~/50
V/ph/Hz 230/1~/50
Unit size
95.2
Maximum absorbed power
Maximum absorbed current
Maximum input current
Main power supply
Auxiliary power supply
(1)
(2)
(3)
kW
A
A
339
557
745
V/ph/Hz 400/3~/50
V/ph/Hz 230/1~/50
100.2 105.2 110.2
117.2 124.2 130.3 137.3 143.3 147.3 153.3
358
587
776
376
617
807
393
644
867
415
681
1.015
437
717
1.052
460
755
944
485
795
984
509
835
1.024
527
865
1.055
546
896
1.085
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
ELECTRICAL DATA COBALT W /A
Unit size
Maximum absorbed power
Maximum absorbed current
Maximum input current
Main power supply
Auxiliary power supply
(1)
(2)
(3)
kW
A
A
20.1
22.1
24.1
27.1
31.1
35.1
36.2
38.2
41.2
42.1
45.2
63
104
167
72
118
208
78
127
208
89
146
240
100
164
230
112
183
282
123
202
282
126
207
271
135
222
312
144
236
326
140
229
305
155
254
335
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
46.2
49.2
53.2
57.2
62.2
65.2
69.2
72.2
76.2
78.2
83.2
88.2
166
273
367
178
291
386
200
327
394
212
347
446
224
367
465
235
385
465
246
403
484
256
419
507
265
435
523
272
447
523
279
458
534
315
517
706
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
V/ph/Hz 400/3~/50
V/ph/Hz 230/1~/50
Unit size
Maximum absorbed power
Maximum absorbed current
Maximum input current
Main power supply
Auxiliary power supply
18.1
(1)
(2)
(3)
kW
A
A
V/ph/Hz 400/3~/50
V/ph/Hz 230/1~/50
Unit size
Maximum absorbed power
Maximum absorbed current
Maximum input current
Main power supply
Auxiliary power supply
95.2
(1)
(2)
(3)
kW
A
A
339
557
745
V/ph/Hz 400/3~/50
V/ph/Hz 230/1~/50
100.2 105.2 110.2
376
617
807
393
644
867
415
681
1.015
437
717
1.052
460
755
944
485
795
984
509
835
1.024
527
865
1.055
546
896
1.085
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
(1) Electrical power that must be supplied by the mains to power the unit
(2) Is the maximum current absorbed by the unit. This value is never exceeded and must be used
to size the line and its protections (refer to the electric diagram supplied with the unit).
(3) Maximum input current calculated considering the power of the compressor with the higher
14
117.2 124.2 130.3 137.3 143.3 147.3 153.3
358
587
776
power and the maximum current absorbed by all other devices
This data sheet shows the data of the basic and standard series; for further details refer to the
specific documentation.
Swegon reserves the right to alter specifications.
www.swegon.com
COBALT W
ELECTRICAL DATA COBALT W /LC
Unit size
Maximum absorbed power
Maximum absorbed current
Maximum input current
Main power supply
Auxiliary power supply
(1)
(2)
(3)
kW
A
A
20.1
22.1
24.1
27.1
31.1
35.1
36.2
38.2
41.2
42.1
45.2
63
104
167
72
118
208
78
127
208
89
146
240
100
164
230
112
183
282
123
202
282
126
207
271
135
222
312
144
236
326
140
229
305
155
254
335
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
46.2
49.2
53.2
57.2
62.2
65.2
69.2
72.2
76.2
78.2
83.2
88.2
166
273
367
178
291
386
200
327
394
212
347
446
224
367
465
235
385
465
246
403
484
256
419
507
265
435
523
272
447
523
279
458
534
315
517
706
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
V/ph/Hz 400/3~/50
V/ph/Hz 230/1~/50
Unit size
Maximum absorbed power
Maximum absorbed current
Maximum input current
Main power supply
Auxiliary power supply
18.1
(1)
(2)
(3)
kW
A
A
V/ph/Hz 400/3~/50
V/ph/Hz 230/1~/50
Unit size
Maximum absorbed power
Maximum absorbed current
Maximum input current
Main power supply
Auxiliary power supply
95.2
(1)
(2)
(3)
kW
A
A
339
557
745
V/ph/Hz 400/3~/50
V/ph/Hz 230/1~/50
100.2 105.2 110.2
117.2 124.2 130.3 137.3 143.3 147.3 153.3
358
587
776
376
617
807
393
644
867
415
681
1.015
437
717
1.052
460
755
944
485
795
984
509
835
1.024
527
865
1.055
546
896
1.085
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
400/3~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
230/1~/50
(1) Electrical power that must be supplied by the mains to power the unit
(2) Is the maximum current absorbed by the unit. This value is never exceeded and must be used
to size the line and its protections (refer to the electric diagram supplied with the unit).
(3) Maximum input current calculated considering the power of the compressor with the higher
Swegon reserves the right to alter specifications.
power and the maximum current absorbed by all other devices
This data sheet shows the data of the basic and standard series; for further details refer to the
specific documentation.
www.swegon.com
15
COBALT W
OPERATING LIMITS - COOLING - COBALT W COBALT W/A
+20
+10
+5
+3
0
-1
-3
-5
-8
26
30
32
35
40
45
50
53 54 55
60
Using ethylene glycol
Using BRINE KIT accessory
User outgoing water temperature (°C)
+15
Source outgoing water temperature (°C)
Please ALWAYS contact our office if you need the ”heating only” version; Operating limits for the ”heating only” version: the limits for produced hot water exceeding 53°C must
be validated by our office.
OPERATING LIMITS - RECOVERY - COBALT W COBALT W/A
+20
+15
+10
+5
0
-1
-3
-5
-8
26
30
32
35
40
45
50
53 55
Using ethylene glycol
+3
Using BRINE KIT accessory
User outgoing water temperature (°C)
H
60
Source outgoing water temperature (°C)
THE THERMAL HEAD OF WATER FOR ALL VERSIONS MUST BE BETWEEN: min:4 °C max: 7°C
BY USING THE PRESSURE RELIEF VALVE ACCESSORY, THE LOWER LIMITS OF INGOING SOURCE WATER TEMPERATURE DECREASE
16
Swegon reserves the right to alter specifications.
www.swegon.com
COBALT W
OPERATING LIMITS - COOLING - COBALT W /LC
+20
+10
+5
0
-4
-5
-8
30
32
35
40
45
50
55
58
60
62
Using ethylene glycol
+3
Using BRINE KIT accessory
User outgoing water temperature [°C]
+15
Condensation temperature [°C]
Swegon reserves the right to alter specifications.
www.swegon.com
17
COBALT W
COOLING CAPACITY - COBALT W
To
Model
18.1
20.1
22.1
24.1
27.1
31.1
35.1
36.2
38.2
41.2
42.1
45.2
[°C]
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
Condenser outgoing water temperature [°C]
30
35
40
45
50
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
176
182
188
194
200
197
204
211
218
225
214
221
230
238
246
246
255
263
272
281
276
286
296
306
317
307
317
328
339
351
342
354
366
380
394
355
367
380
392
404
376
389
403
416
430
397
411
425
440
456
415
429
445
461
474
435
450
468
484
499
36
36
37
37
38
40
40
40
41
41
43
43
44
44
45
49
49
50
50
51
55
56
57
57
58
61
62
62
63
64
66
67
68
68
69
72
72
73
74
75
75
75
76
77
78
79
80
81
82
82
83
84
85
86
87
86
87
88
89
90
212
218
225
231
238
237
244
251
258
266
257
265
273
282
290
295
304
313
323
332
331
342
353
363
375
368
379
390
402
415
409
421
434
448
462
426
440
453
466
479
451
465
479
493
508
476
491
506
522
539
498
514
530
546
562
521
537
555
573
589
166
172
177
183
189
187
193
200
207
213
202
210
217
224
231
233
241
249
257
266
261
270
280
289
299
290
299
310
320
331
323
334
347
359
370
335
346
358
370
382
356
368
381
394
408
376
389
403
418
432
393
407
421
434
449
412
427
442
456
471
38
39
39
40
40
43
43
43
44
44
46
46
47
48
48
52
53
54
54
55
59
60
61
62
62
65
66
67
68
69
71
72
72
73
75
77
78
79
80
81
80
81
82
83
84
85
86
87
88
89
89
90
91
93
94
92
93
94
96
97
205
211
217
223
230
229
236
243
250
258
248
256
264
271
279
285
294
303
312
321
320
330
340
351
362
355
365
377
388
400
394
406
419
433
444
412
424
437
450
463
436
449
463
477
492
461
475
490
505
521
482
497
512
527
542
504
520
537
552
569
157
162
168
173
179
177
183
189
195
202
191
198
205
213
220
219
226
234
242
250
245
254
263
272
281
273
282
292
302
312
303
314
324
336
347
316
327
339
349
361
337
348
360
373
386
356
368
381
395
409
370
383
395
408
422
389
403
418
433
449
42
42
42
43
44
46
46
47
48
48
50
50
51
51
52
57
58
58
59
60
64
65
66
67
68
70
72
73
74
75
77
78
79
80
81
83
84
85
86
87
86
88
89
90
91
92
93
94
95
96
97
98
100
101
102
100
101
102
103
104
198
204
210
216
222
223
229
236
243
250
241
248
256
264
272
276
284
293
301
310
309
319
329
339
349
343
353
364
375
387
380
392
404
416
429
399
411
424
435
448
423
436
449
462
476
447
461
475
490
505
466
481
494
509
524
489
504
520
537
553
147
152
158
163
169
165
171
177
183
189
178
185
192
199
205
203
211
218
226
233
228
236
245
253
262
254
262
271
281
291
283
293
302
312
323
296
307
318
330
342
315
327
339
351
364
332
344
356
369
383
344
355
368
380
394
363
376
391
404
419
45
46
46
47
47
51
51
52
52
53
55
55
56
57
58
63
64
65
65
66
71
72
73
74
75
78
79
80
81
82
85
86
88
89
90
91
92
93
93
95
95
96
97
98
99
101
102
104
105
106
107
109
110
112
113
110
112
113
114
115
192
198
204
210
217
216
222
229
235
242
233
240
248
255
262
267
275
283
291
299
298
308
317
327
337
332
341
352
362
374
368
379
389
401
413
387
398
411
424
436
410
422
436
449
463
433
446
460
474
489
451
464
478
492
507
473
488
503
518
534
135
140
146
151
157
153
158
164
170
176
165
171
177
183
189
187
194
201
208
215
209
217
225
233
241
232
241
250
259
268
260
268
277
287
297
273
283
294
305
315
291
302
313
325
336
306
318
330
342
355
315
327
339
351
363
335
348
360
373
384
51
51
52
52
53
57
57
58
58
59
61
62
62
64
64
71
71
72
73
74
79
80
81
82
83
88
89
90
91
92
95
97
98
100
101
101
102
103
104
106
106
107
108
109
111
113
114
115
116
118
121
122
124
126
127
123
124
126
127
130
186
192
198
203
209
209
215
222
228
234
226
233
240
246
253
258
265
273
281
289
288
297
306
315
325
320
329
339
350
360
355
365
376
387
398
374
386
397
409
421
397
409
421
434
447
419
432
445
459
472
436
449
462
476
490
458
472
486
501
514
Pf: cooling capacity [kW]
Pe: electrical power absorbed by the compressors [kW]
Pr: condenser heating capacity [kW]
T0: evaporator outgoing water temperature [°C] Evaporator thermal gap = 5°C
18
Swegon reserves the right to alter specifications.
www.swegon.com
COBALT W
COOLING CAPACITY - COBALT W
To
Model
46.2
49.2
53.2
57.2
62.2
65.2
69.2
72.2
76.2
78.2
83.2
88.2
[°C]
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
Condenser outgoing water temperature [°C]
30
35
40
45
50
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
467
485
502
518
536
500
519
537
556
575
538
557
577
597
617
583
601
621
641
661
623
642
662
683
704
656
679
703
728
754
687
711
736
762
790
725
751
779
805
832
766
795
824
850
880
794
823
853
884
913
851
880
911
940
967
902
929
957
988
1018
92
93
94
95
96
98
99
100
101
102
106
107
109
110
111
117
119
120
121
122
123
124
125
127
128
129
130
131
133
134
133
135
136
138
139
143
144
145
147
149
154
156
157
159
161
151
152
154
155
157
169
170
171
173
175
178
180
182
183
185
559
577
595
613
632
598
617
637
657
677
644
665
685
707
728
700
720
741
762
783
746
766
788
810
832
785
809
835
861
888
820
846
872
900
929
867
895
924
952
980
921
951
981
1009
1040
945
976
1007
1039
1070
1019
1050
1082
1113
1142
1080
1109
1139
1171
1203
442
458
473
490
507
473
490
508
526
544
509
527
546
565
584
551
569
587
606
626
589
607
627
646
666
620
642
665
690
714
649
672
696
723
748
686
712
736
760
787
727
753
777
804
832
752
780
807
834
862
803
831
858
883
910
852
878
907
935
965
98
100
101
102
104
105
106
107
109
110
114
115
116
118
119
126
127
128
130
131
132
133
134
136
137
137
139
141
142
144
142
144
146
147
148
152
154
156
158
160
164
166
169
171
173
161
163
165
167
169
179
181
183
186
188
191
192
194
196
198
540
558
574
592
610
577
596
615
634
654
622
642
662
683
704
677
696
716
736
757
721
740
761
782
804
757
781
806
832
857
791
816
842
870
897
838
866
892
918
947
891
919
946
975
1005
913
943
971
1001
1031
982
1012
1041
1068
1098
1043
1071
1101
1132
1163
416
431
447
463
478
443
460
476
494
511
478
495
513
531
549
518
535
553
572
590
553
571
589
610
630
582
603
626
648
670
609
631
656
680
700
646
669
691
715
740
683
708
731
757
783
708
734
759
784
812
753
776
800
826
852
802
826
854
882
909
107
108
109
111
113
114
116
117
119
120
123
125
127
128
130
137
138
140
141
143
143
145
147
148
149
149
151
152
154
157
155
157
158
160
163
165
167
170
172
174
178
180
183
186
188
174
176
179
182
184
194
197
200
202
204
207
209
211
213
216
523
539
556
574
591
558
575
594
612
631
601
620
640
659
679
655
673
693
713
733
697
716
736
757
779
731
754
778
803
827
763
787
813
839
863
810
836
860
887
914
861
889
914
942
971
882
910
938
966
996
947
973
1000
1028
1056
1008
1036
1065
1095
1125
387
402
417
430
445
412
427
443
459
476
445
461
478
495
512
482
499
517
534
551
516
532
552
570
588
542
563
583
604
625
567
589
611
630
652
602
622
644
667
691
637
657
681
706
731
659
682
706
731
757
699
719
743
767
791
746
769
795
819
844
118
119
121
123
125
127
128
130
131
133
136
138
140
141
144
151
152
154
156
158
158
160
161
163
165
164
166
168
170
173
170
172
174
177
180
181
185
187
190
192
196
200
202
205
208
192
195
198
201
203
214
217
220
222
225
229
231
234
237
240
505
521
537
553
570
538
555
573
591
609
581
599
618
637
656
633
652
671
689
709
674
692
713
733
753
706
729
751
774
798
737
761
785
808
832
783
806
831
857
883
833
857
884
911
939
851
877
904
932
960
913
936
962
989
1016
975
1001
1029
1056
1084
356
370
382
396
410
378
393
407
422
438
409
425
440
456
472
445
461
476
491
507
474
492
509
527
540
499
518
537
556
577
522
542
559
580
601
553
572
593
615
637
583
605
628
651
674
604
627
650
674
699
638
659
681
704
727
687
710
732
756
780
132
133
136
137
139
142
143
145
147
149
152
154
156
158
160
168
170
172
175
177
177
178
180
182
186
183
185
188
191
193
190
192
196
199
201
204
207
210
212
215
221
224
227
230
233
216
219
222
225
228
240
243
246
248
251
256
259
263
266
269
488
503
518
534
550
520
536
552
569
587
561
578
596
614
632
613
631
648
666
684
652
671
690
709
726
682
704
725
747
770
712
734
755
778
802
756
779
803
827
852
804
829
854
880
907
820
846
872
899
926
878
902
927
952
978
943
969
995
1022
1049
Pf: cooling capacity [kW]
Pe: electrical power absorbed by the compressors [kW]
Pr: condenser heating capacity [kW]
T0: evaporator outgoing water temperature [°C] Evaporator thermal gap = 5°C
Swegon reserves the right to alter specifications.
www.swegon.com
19
COBALT W
COOLING CAPACITY - COBALT W
To
Model
95.2
100.2
105.2
110.2
117.2
124.2
130.3
137.3
143.3
147.3
153.3
[°C]
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
Condenser outgoing water temperature [°C]
30
35
40
45
50
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
971
999
1031
1059
1092
1020
1049
1084
1119
1155
1077
1108
1145
1182
1220
1116
1152
1190
1228
1266
1199
1238
1278
1318
1360
1255
1295
1337
1379
1422
1313
1354
1398
1442
1487
1401
1446
1492
1539
1587
1459
1504
1553
1603
1654
1499
1546
1596
1648
1700
1564
1613
1665
1719
1773
185
187
188
191
193
203
204
206
208
210
206
207
209
211
213
222
224
226
228
230
235
237
240
242
244
247
249
252
254
257
261
263
266
268
271
276
278
281
283
286
288
291
294
297
299
295
298
301
303
306
303
305
308
311
314
1156
1186
1219
1250
1285
1223
1254
1290
1327
1365
1283
1316
1354
1394
1434
1338
1376
1416
1456
1496
1434
1475
1517
1560
1604
1502
1544
1588
1633
1679
1574
1618
1664
1710
1757
1677
1724
1773
1822
1873
1747
1795
1847
1900
1953
1795
1844
1897
1951
2007
1867
1918
1974
2030
2087
920
946
973
1003
1034
965
993
1026
1059
1094
1020
1049
1084
1120
1156
1056
1091
1126
1162
1198
1135
1171
1209
1248
1287
1187
1225
1265
1305
1346
1243
1282
1324
1366
1408
1327
1369
1413
1458
1503
1381
1424
1471
1519
1567
1420
1464
1512
1561
1611
1481
1527
1577
1628
1680
198
199
202
205
207
216
218
221
223
225
219
221
224
226
228
237
239
242
245
247
251
254
256
259
262
264
267
270
273
276
278
281
284
287
290
294
297
300
303
306
308
311
314
317
321
315
318
321
325
328
323
326
329
333
336
1117
1145
1175
1207
1241
1182
1212
1247
1282
1319
1239
1271
1308
1346
1384
1293
1330
1368
1407
1445
1386
1425
1466
1507
1549
1451
1492
1535
1578
1621
1521
1564
1608
1653
1698
1621
1666
1713
1761
1809
1689
1735
1785
1836
1888
1735
1782
1833
1886
1939
1804
1853
1907
1961
2016
865
887
915
943
972
908
935
966
997
1030
959
987
1020
1054
1088
992
1026
1059
1093
1128
1067
1101
1137
1174
1211
1116
1152
1189
1227
1266
1169
1206
1245
1285
1325
1248
1288
1330
1373
1416
1300
1341
1386
1431
1477
1336
1378
1424
1470
1517
1394
1437
1485
1533
1582
215
218
220
223
225
235
237
240
242
245
238
240
243
246
248
257
260
263
266
269
273
276
279
282
286
287
290
294
297
300
302
306
309
312
316
319
322
326
329
333
334
337
341
345
349
342
345
349
353
357
350
354
358
362
366
1079
1104
1135
1166
1198
1143
1172
1205
1240
1275
1197
1227
1263
1299
1336
1250
1286
1322
1359
1397
1340
1377
1416
1456
1497
1403
1442
1483
1524
1566
1471
1512
1554
1597
1641
1567
1611
1656
1702
1748
1634
1678
1727
1776
1825
1678
1723
1773
1823
1874
1744
1791
1843
1895
1948
800
823
850
877
903
847
872
901
931
961
894
920
952
983
1016
925
956
988
1020
1052
992
1025
1058
1093
1128
1036
1069
1105
1140
1176
1091
1126
1163
1201
1239
1165
1202
1242
1282
1323
1213
1251
1293
1336
1379
1246
1286
1329
1373
1417
1300
1341
1386
1432
1478
239
242
245
248
250
259
261
264
268
271
262
265
268
271
274
284
287
291
294
297
302
305
309
313
317
318
322
326
330
334
333
337
340
344
348
351
355
359
363
367
368
372
376
381
385
377
381
385
390
394
386
390
395
399
404
1039
1065
1095
1124
1154
1106
1133
1165
1198
1232
1156
1185
1220
1254
1290
1208
1243
1278
1314
1350
1294
1330
1368
1406
1444
1354
1392
1431
1470
1510
1424
1463
1504
1545
1587
1516
1558
1601
1645
1690
1581
1623
1670
1717
1765
1623
1667
1714
1763
1812
1686
1731
1781
1831
1882
736
759
784
809
834
781
804
831
859
888
824
849
878
908
938
852
881
911
941
971
913
944
976
1008
1040
953
985
1018
1051
1085
1006
1039
1074
1109
1144
1074
1109
1147
1184
1222
1118
1155
1194
1234
1275
1149
1186
1227
1268
1310
1199
1237
1280
1323
1366
268
271
274
277
281
289
292
296
299
303
293
296
299
303
307
318
321
325
329
333
338
342
346
350
355
357
361
365
370
374
372
376
381
385
389
393
397
402
406
411
411
416
421
426
431
421
426
431
436
441
432
436
442
447
452
1004
1030
1058
1086
1114
1070
1097
1127
1158
1191
1117
1145
1178
1211
1245
1169
1202
1236
1270
1304
1251
1286
1322
1358
1395
1310
1346
1383
1421
1459
1378
1415
1454
1494
1534
1467
1506
1548
1590
1633
1530
1570
1615
1660
1706
1571
1612
1658
1704
1751
1631
1674
1721
1769
1818
Pf: cooling capacity [kW]
Pe: electrical power absorbed by the compressors [kW]
Pr: condenser heating capacity [kW]
T0: evaporator outgoing water temperature [°C] Evaporator thermal gap = 5°C
20
Swegon reserves the right to alter specifications.
www.swegon.com
COBALT W
COOLING CAPACITY - COBALT W /A
To
Model
18.1
20.1
22.1
24.1
27.1
31.1
35.1
36.2
38.2
41.2
42.1
45.2
[°C]
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
Condenser outgoing water temperature [°C]
30
35
40
45
50
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
187
193
200
207
214
208
216
223
231
238
225
233
241
249
258
259
268
277
287
297
287
298
309
320
332
320
332
344
357
370
368
382
395
410
424
371
385
399
413
427
394
409
424
438
454
417
432
448
463
480
423
438
454
470
487
453
470
486
504
522
33
33
33
33
34
36
37
37
37
38
39
40
40
40
41
45
46
46
47
47
50
51
51
52
52
57
57
57
58
59
64
65
66
66
67
65
66
66
67
67
69
70
70
71
71
74
74
75
76
76
73
74
75
75
76
79
80
81
81
82
219
226
233
240
248
245
252
260
268
276
264
273
281
290
299
304
314
324
334
344
337
349
360
372
384
376
389
402
415
428
432
447
461
476
491
437
451
465
480
495
464
478
494
509
526
491
507
523
539
556
496
512
529
545
563
532
549
567
585
604
179
186
192
199
206
199
206
213
220
228
215
223
231
239
248
247
256
265
274
284
274
284
295
305
317
305
317
328
339
351
351
364
377
391
405
355
368
382
395
409
377
391
405
419
434
398
413
428
443
459
404
419
434
449
466
432
448
464
481
499
35
35
35
36
36
39
39
39
40
40
42
42
43
43
43
48
49
49
50
50
53
54
54
55
55
60
61
61
62
63
68
69
70
70
71
69
70
70
71
72
73
74
75
75
76
78
79
80
81
81
78
79
79
80
81
84
85
86
86
87
214
220
227
234
242
238
245
253
260
268
257
265
274
282
291
295
305
314
324
334
327
338
349
360
372
365
377
389
401
414
420
433
447
461
476
424
438
452
466
481
451
465
480
495
510
477
492
508
523
540
482
497
513
529
546
516
533
549
568
586
170
177
183
190
197
190
196
203
210
217
205
213
220
228
237
235
243
252
261
270
259
269
279
289
300
289
300
312
322
334
334
346
359
372
386
338
350
363
376
390
359
372
386
400
414
379
393
408
422
437
383
398
413
427
443
411
427
442
458
474
37
38
38
38
39
42
42
42
43
43
45
46
46
47
47
52
53
53
54
54
58
58
59
59
60
65
65
66
67
68
74
75
76
76
77
75
75
76
77
78
79
80
81
81
82
84
85
86
87
88
84
85
86
86
87
91
92
93
94
95
208
215
221
228
235
231
238
246
253
261
251
258
267
275
284
287
296
305
315
325
317
327
338
349
360
354
366
378
389
402
408
421
434
448
463
412
426
440
453
467
438
452
467
481
496
464
479
494
509
525
467
483
498
514
530
502
518
534
551
569
162
168
174
180
187
179
185
192
199
205
194
201
208
216
224
221
229
237
246
255
244
253
262
272
283
272
282
293
303
314
316
327
339
352
365
320
332
344
356
369
339
352
365
378
392
359
372
385
398
413
362
376
390
403
417
388
403
417
432
449
41
41
42
42
42
46
46
47
47
48
50
50
51
51
52
58
58
59
59
60
63
64
65
65
66
71
72
73
74
75
82
82
83
84
85
82
82
83
84
85
87
88
88
89
90
93
94
95
96
97
92
93
94
95
96
100
101
102
103
104
202
209
215
222
229
225
231
238
246
253
244
251
259
267
276
279
287
296
305
315
307
317
327
338
349
343
354
366
377
389
397
409
423
436
450
401
414
427
440
454
426
440
453
467
482
451
466
480
494
510
455
469
484
498
513
488
504
519
535
552
151
157
163
169
175
167
173
179
186
193
182
189
196
203
211
206
214
222
230
238
227
236
245
254
264
253
263
272
283
293
295
306
318
329
340
298
310
322
334
346
317
329
342
354
368
336
348
361
374
388
339
352
365
378
391
363
377
391
405
420
45
46
46
47
47
51
52
52
53
53
55
56
57
57
58
64
65
66
66
67
70
71
72
72
73
79
80
81
82
83
91
92
93
94
95
91
92
93
93
94
97
98
99
100
100
103
105
106
107
108
103
104
105
107
108
111
113
113
114
116
196
203
209
216
222
218
224
231
238
246
237
245
252
260
268
270
279
287
296
305
297
307
316
327
337
332
343
354
365
376
386
398
410
423
436
389
402
414
428
441
413
427
440
454
468
439
453
467
481
496
442
456
471
484
499
474
489
504
520
536
Pf: cooling capacity [kW]
Pe: electrical power absorbed by the compressors [kW]
Pr: condenser heating capacity [kW]
T0: evaporator outgoing water temperature [°C] Evaporator thermal gap = 5°C
Swegon reserves the right to alter specifications.
www.swegon.com
21
COBALT W
COOLING CAPACITY - COBALT W /A
To
Model
46.2
49.2
53.2
57.2
62.2
65.2
69.2
72.2
76.2
78.2
83.2
88.2
[°C]
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
Condenser outgoing water temperature [°C]
30
35
40
45
50
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
492
511
529
548
568
527
547
566
587
608
575
597
618
640
663
611
631
652
674
697
649
669
691
714
738
701
727
753
780
808
740
766
794
823
852
764
792
821
851
882
805
834
865
896
929
832
863
894
926
960
863
892
923
954
986
949
978
1010
1044
1077
86
87
88
88
89
93
93
94
95
96
102
103
104
104
105
107
108
109
110
111
114
114
115
116
117
123
124
126
127
128
128
129
131
132
133
135
136
137
138
139
141
142
143
144
146
145
147
148
149
150
149
150
152
153
154
165
167
168
170
171
579
598
617
637
657
620
640
660
682
704
677
699
721
745
769
719
740
762
784
808
763
783
807
830
855
824
851
878
906
935
868
896
925
954
985
899
928
958
989
1021
946
977
1008
1041
1074
977
1009
1042
1075
1110
1012
1043
1075
1107
1140
1114
1145
1179
1213
1249
470
487
505
523
542
502
521
540
559
579
549
569
589
611
633
583
603
623
644
666
619
639
661
683
705
668
692
717
743
771
705
730
757
784
813
728
755
783
812
841
767
795
825
855
885
793
822
853
884
916
829
858
887
919
949
901
931
962
994
1027
92
93
93
94
95
98
99
100
101
103
108
109
110
111
112
114
115
116
117
118
120
122
123
124
125
131
132
133
135
136
136
137
139
140
141
143
144
145
147
148
149
151
152
153
155
154
155
157
158
159
158
160
161
162
164
176
178
180
182
184
561
580
598
618
637
601
620
640
661
682
656
678
699
722
745
697
718
739
761
784
739
761
783
807
830
799
825
851
878
907
841
868
896
925
955
871
899
929
958
989
916
946
977
1008
1040
947
978
1009
1042
1075
987
1018
1049
1081
1113
1077
1109
1142
1176
1210
446
462
479
497
515
476
494
512
530
550
520
539
559
579
600
553
572
592
612
633
587
607
628
649
671
633
656
680
705
731
668
692
717
744
772
689
716
743
769
795
726
754
783
811
838
751
780
809
838
869
790
819
849
878
908
853
881
911
942
973
99
100
101
102
103
107
108
109
110
111
117
118
119
120
122
123
124
126
127
128
130
131
133
134
135
141
143
144
146
147
147
149
150
152
153
154
155
157
159
161
161
163
164
166
168
166
168
169
171
172
171
173
174
176
178
191
193
195
198
200
545
562
580
599
618
582
601
620
640
661
636
657
678
699
721
676
697
717
739
761
717
738
761
783
806
774
799
824
851
878
815
840
868
896
925
843
871
900
928
956
887
917
947
977
1006
917
947
978
1009
1041
961
992
1023
1054
1086
1044
1074
1107
1140
1173
419
435
451
468
486
447
464
481
500
518
488
507
525
546
566
520
539
558
577
597
552
572
592
613
634
594
617
640
664
689
627
650
675
701
727
648
673
699
723
749
683
709
736
761
789
707
734
761
789
816
744
773
802
832
860
800
828
857
886
916
109
110
111
112
113
118
119
120
121
122
128
130
131
132
134
135
137
138
139
141
143
145
146
147
149
155
157
159
160
162
162
164
165
167
168
169
171
172
175
177
177
179
181
183
185
182
184
186
188
190
188
190
192
194
196
211
213
215
218
220
528
545
563
581
599
564
582
601
621
641
617
636
656
678
699
656
676
696
717
738
695
716
738
760
783
750
774
799
824
851
789
814
841
868
896
817
844
871
898
926
860
888
917
944
974
889
918
947
977
1007
932
963
994
1025
1056
1011
1041
1072
1104
1137
391
406
422
438
454
416
433
449
466
484
455
473
491
509
528
485
503
522
540
559
515
534
553
574
594
554
575
597
620
642
585
607
630
654
676
603
627
649
674
698
636
661
684
710
735
658
683
709
735
762
692
720
748
775
804
743
769
797
825
854
121
123
124
125
126
131
132
134
135
136
142
144
145
147
149
151
152
154
155
157
160
161
163
164
166
173
175
177
178
181
180
182
184
186
189
188
190
193
195
198
197
199
202
204
207
203
205
207
210
212
209
211
214
217
219
236
238
241
244
247
512
529
546
563
580
547
565
583
601
620
597
617
636
656
677
636
656
675
695
715
675
695
716
738
759
727
750
774
799
823
765
789
814
840
865
792
817
842
869
896
833
860
886
914
942
861
888
916
945
974
902
931
962
992
1023
979
1008
1038
1069
1100
Pf: cooling capacity [kW]
Pe: electrical power absorbed by the compressors [kW]
Pr: condenser heating capacity [kW]
T0: evaporator outgoing water temperature [°C] Evaporator thermal gap = 5°C
22
Swegon reserves the right to alter specifications.
www.swegon.com
COBALT W
COOLING CAPACITY - COBALT W /A
To
Model
95.2
100.2
105.2
110.2
117.2
124.2
130.3
137.3
143.3
147.3
153.3
[°C]
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
Condenser outgoing water temperature [°C]
30
35
40
45
50
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
1014
1043
1078
1114
1150
1068
1101
1138
1177
1215
1114
1149
1188
1227
1268
1179
1219
1260
1302
1345
1254
1297
1340
1384
1430
1319
1363
1409
1456
1503
1373
1419
1467
1516
1565
1454
1502
1553
1604
1657
1506
1557
1610
1664
1720
1552
1604
1659
1715
1772
1603
1656
1713
1771
1830
176
177
179
180
182
186
188
189
191
193
194
195
197
199
201
206
207
209
211
213
218
220
222
224
227
230
232
234
236
238
240
242
244
246
249
252
254
256
259
261
263
266
268
270
273
271
273
276
278
281
278
281
283
286
288
1190
1221
1257
1294
1332
1254
1289
1328
1368
1408
1308
1344
1385
1426
1469
1385
1427
1470
1513
1558
1473
1517
1562
1609
1656
1548
1595
1643
1692
1742
1613
1661
1711
1762
1814
1705
1756
1809
1863
1918
1769
1822
1878
1935
1993
1823
1877
1935
1993
2053
1881
1937
1996
2057
2119
965
994
1027
1061
1095
1016
1048
1083
1120
1157
1060
1093
1130
1168
1207
1121
1160
1199
1239
1280
1192
1233
1274
1317
1361
1253
1296
1340
1385
1430
1305
1349
1395
1441
1489
1381
1428
1476
1526
1576
1432
1480
1531
1583
1636
1475
1525
1578
1631
1686
1524
1575
1629
1685
1741
187
189
191
193
195
198
200
202
204
206
206
208
210
212
214
219
221
223
226
228
233
235
237
240
242
244
247
250
252
255
255
258
261
263
266
268
271
274
277
280
280
283
286
289
292
288
291
294
297
300
296
299
302
305
308
1152
1183
1218
1253
1290
1214
1248
1286
1324
1363
1266
1301
1340
1381
1422
1340
1381
1423
1465
1508
1425
1468
1512
1557
1603
1498
1543
1590
1637
1685
1560
1607
1655
1705
1755
1650
1699
1750
1802
1855
1712
1763
1817
1872
1928
1763
1816
1872
1928
1986
1820
1874
1931
1990
2050
913
942
974
1006
1039
961
992
1026
1060
1096
1002
1034
1069
1105
1143
1060
1097
1135
1173
1212
1127
1166
1205
1246
1288
1184
1225
1267
1310
1354
1233
1275
1318
1363
1408
1306
1350
1396
1443
1491
1353
1400
1449
1498
1549
1395
1442
1493
1544
1596
1440
1489
1541
1594
1648
203
205
207
209
212
215
217
219
222
224
223
226
228
231
233
237
240
242
245
248
252
255
258
261
264
265
268
271
274
277
277
280
283
286
290
291
294
298
301
304
304
307
310
314
317
312
316
319
323
326
321
324
328
332
335
1116
1147
1181
1215
1250
1175
1209
1245
1282
1320
1225
1259
1298
1336
1376
1297
1336
1377
1418
1460
1379
1421
1463
1507
1551
1450
1493
1538
1584
1631
1510
1555
1602
1650
1698
1597
1644
1694
1744
1795
1657
1707
1759
1812
1866
1707
1758
1812
1866
1922
1761
1814
1869
1925
1983
857
885
916
947
978
901
931
963
997
1030
940
970
1004
1039
1074
995
1029
1065
1102
1139
1055
1092
1129
1168
1208
1107
1146
1186
1226
1267
1156
1196
1238
1281
1324
1224
1267
1311
1355
1401
1269
1313
1360
1407
1456
1308
1353
1401
1450
1500
1351
1398
1447
1497
1549
224
226
229
231
234
237
239
242
245
248
246
249
252
255
258
262
264
267
270
274
279
282
285
288
292
294
297
301
304
308
305
309
312
316
320
321
325
328
332
336
334
338
342
346
350
344
348
352
356
360
354
358
362
366
370
1080
1111
1144
1178
1212
1138
1170
1205
1241
1278
1186
1219
1256
1293
1332
1257
1293
1332
1372
1413
1333
1373
1414
1457
1500
1401
1443
1486
1530
1575
1461
1505
1551
1597
1644
1545
1591
1639
1688
1737
1604
1652
1702
1753
1806
1652
1701
1753
1806
1860
1704
1755
1809
1863
1919
796
824
853
882
912
837
866
897
928
960
873
902
934
966
1000
924
956
990
1025
1061
979
1013
1050
1086
1124
1028
1064
1101
1140
1179
1075
1111
1151
1191
1232
1136
1176
1218
1260
1304
1180
1220
1264
1309
1355
1214
1258
1303
1349
1396
1254
1299
1346
1393
1442
250
253
256
259
262
265
268
271
274
277
276
279
282
285
288
292
296
299
303
306
312
315
319
323
327
329
333
337
341
345
342
345
349
354
358
359
363
368
372
376
374
378
383
387
392
385
389
394
398
403
396
400
405
409
414
1046
1077
1109
1141
1174
1102
1134
1168
1202
1237
1149
1181
1216
1251
1288
1216
1251
1289
1328
1367
1291
1329
1369
1409
1450
1357
1396
1438
1481
1524
1416
1457
1500
1545
1590
1495
1539
1585
1632
1680
1554
1599
1647
1696
1747
1599
1647
1697
1747
1799
1650
1699
1750
1803
1856
Pf: cooling capacity [kW]
Pe: electrical power absorbed by the compressors [kW]
Pr: condenser heating capacity [kW]
T0: evaporator outgoing water temperature [°C] Evaporator thermal gap = 5°C
Swegon reserves the right to alter specifications.
www.swegon.com
23
COBALT W
COOLING CAPACITY - COBALT W /LC
To
Model
18.1
20.1
22.1
24.1
27.1
31.1
35.1
36.2
38.2
41.2
42.1
45.2
[°C]
5
6
7
8
9
10
5
6
7
8
9
10
5
6
7
8
9
10
5
6
7
8
9
10
5
6
7
8
9
10
5
6
7
8
9
10
5
6
7
8
9
10
5
6
7
8
9
10
5
6
7
8
9
10
5
6
7
8
9
10
5
6
7
8
9
10
5
6
7
8
9
10
Average condensation temperature [°C]
35
40
45
50
55
60
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
162
167
174
180
187
194
192
199
207
214
222
229
203
210
218
226
234
243
241
250
259
269
278
288
266
276
286
297
309
320
299
311
323
335
348
361
321
331
343
356
369
382
331
342
355
369
382
396
358
373
387
402
416
432
382
395
410
426
442
458
384
397
412
427
443
460
414
427
444
461
478
496
33
34
34
34
34
35
38
38
38
39
39
39
41
41
41
41
42
42
47
47
47
48
48
48
53
54
54
54
55
55
59
60
60
61
61
61
65
65
66
66
66
67
67
67
68
68
69
69
72
72
73
73
74
74
76
76
77
77
78
78
74
74
75
75
76
76
81
82
82
83
83
84
195
201
208
214
221
228
230
237
245
253
260
268
243
251
259
267
276
285
287
297
306
316
326
337
319
329
340
352
364
376
359
370
383
396
409
422
385
396
409
422
436
449
398
410
423
437
451
465
430
446
460
475
490
506
458
471
487
503
520
537
458
471
487
503
519
536
495
509
526
543
561
580
153
158
164
170
177
183
182
189
196
203
210
217
192
198
206
214
222
230
228
236
245
254
263
273
251
261
271
281
292
303
283
294
305
317
329
341
303
313
325
337
349
362
313
324
336
349
362
375
339
353
367
381
395
409
362
374
388
403
418
434
363
375
390
404
420
435
392
404
420
436
452
469
36
36
36
36
37
37
40
41
41
41
42
42
43
44
44
44
45
45
50
50
51
51
51
52
57
57
58
58
59
59
63
64
64
65
65
66
69
69
70
70
71
71
71
72
72
73
73
74
76
77
78
78
79
79
81
82
82
83
83
84
79
79
80
80
81
82
87
87
88
89
89
90
188
194
200
207
213
220
222
230
237
244
252
259
235
242
250
258
266
275
277
286
296
305
315
325
308
318
328
339
351
362
346
357
369
381
394
407
372
382
394
407
420
434
384
395
408
422
435
449
415
430
444
459
473
488
443
455
470
486
502
518
442
455
469
485
501
517
478
492
508
525
542
559
143
148
154
160
166
172
171
178
184
191
198
205
180
186
194
201
209
216
213
222
230
239
248
257
236
244
254
264
274
285
265
275
286
297
309
321
284
293
304
316
328
340
293
303
315
327
340
353
318
332
345
358
372
385
340
351
365
379
393
408
341
352
366
380
395
410
368
380
395
410
425
442
39
39
39
40
40
40
44
44
45
45
45
46
47
48
48
48
49
49
54
55
55
56
56
56
62
62
63
63
64
64
69
69
70
70
71
71
75
75
76
77
77
78
78
78
79
79
80
80
83
84
85
85
86
86
88
89
90
90
91
92
86
86
87
87
88
89
94
95
96
97
97
98
182
187
193
200
206
212
215
222
229
236
243
251
227
234
241
249
257
265
268
276
285
294
304
313
297
307
317
327
338
349
333
344
356
367
380
392
359
369
380
393
405
418
371
381
394
407
420
433
401
416
429
443
457
472
428
440
454
469
484
500
426
439
453
468
483
498
462
475
490
506
523
540
133
138
143
149
155
161
159
165
172
178
185
191
168
173
180
187
195
202
198
206
214
222
231
239
219
227
236
246
256
266
246
256
266
277
288
299
264
272
283
294
306
317
272
282
293
305
317
329
296
309
322
334
347
360
316
327
340
353
367
381
317
328
341
354
368
382
342
354
368
382
397
412
43
43
44
44
44
44
49
49
50
50
50
51
52
53
53
53
54
54
60
61
61
61
62
62
68
68
69
70
70
71
76
76
77
78
78
79
83
83
84
85
85
86
86
86
87
88
88
89
92
93
94
94
95
96
98
98
99
100
100
101
95
95
96
97
97
98
105
105
106
107
108
108
176
181
187
193
199
205
208
215
221
228
235
242
220
226
233
241
248
256
258
267
275
284
293
302
287
296
305
315
326
336
322
332
343
354
366
378
346
356
367
379
391
403
358
368
380
392
405
418
388
402
415
429
442
456
414
425
439
453
467
482
412
423
437
451
466
480
447
459
474
489
504
521
122
127
132
137
143
148
147
153
159
165
171
177
154
160
166
173
180
187
182
190
197
205
213
221
201
209
217
226
236
245
225
235
245
255
265
276
242
251
261
271
282
293
250
259
270
281
292
304
272
285
297
309
321
334
291
302
314
326
339
353
291
302
314
327
340
354
315
326
339
353
367
381
48
48
49
49
49
50
55
55
55
56
56
57
59
59
59
60
60
61
67
68
68
69
69
70
76
76
77
78
78
79
85
86
86
87
87
88
93
93
94
95
95
96
96
97
97
98
99
100
103
104
105
105
106
107
109
110
111
112
112
113
106
107
108
108
109
110
117
118
119
119
120
121
170
175
181
186
192
198
201
208
214
220
227
234
213
219
226
233
240
247
249
257
265
274
282
291
277
285
294
304
314
324
310
320
331
342
353
364
335
344
355
366
377
389
346
356
367
379
391
403
375
389
402
414
427
441
400
412
425
438
451
466
397
409
422
435
449
464
432
443
458
472
487
502
111
115
120
125
130
136
133
139
145
150
156
162
140
145
151
158
164
171
165
172
179
186
194
202
182
189
197
206
214
223
204
213
222
232
241
252
220
228
237
247
257
268
227
236
246
256
266
277
247
260
271
282
293
305
264
275
286
298
310
322
264
276
287
298
311
323
285
296
308
321
335
348
54
55
55
55
56
56
62
62
62
63
63
64
66
66
67
67
68
68
76
76
77
78
78
79
85
86
86
87
88
88
96
97
98
98
99
100
105
106
106
107
108
109
109
109
110
111
112
112
116
117
118
119
120
121
123
124
125
126
127
127
120
121
122
122
123
124
132
133
134
135
135
136
165
170
175
181
186
192
195
201
207
213
219
226
206
212
218
225
232
239
241
248
256
264
272
280
267
275
284
293
302
312
300
310
320
330
340
351
325
333
344
354
365
376
336
345
356
367
378
390
363
377
389
401
413
426
387
399
411
424
436
449
384
396
409
421
434
448
418
429
442
456
470
485
Pf: cooling capacity [kW]
Pe: electrical power absorbed by the compressors [kW]
Pr: condenser heating capacity [kW]
T0:evaporator outgoing water temperature [°C] Evaporator thermal gap = 5°C
24
Swegon reserves the right to alter specifications.
www.swegon.com
COBALT W
COOLING CAPACITY - COBALT W /LC
To
Model
46.2
49.2
53.2
57.2
62.2
65.2
69.2
72.2
76.2
78.2
83.2
88.2
[°C]
5
6
7
8
9
10
5
6
7
8
9
10
5
6
7
8
9
10
5
6
7
8
9
10
5
6
7
8
9
10
5
6
7
8
9
10
5
6
7
8
9
10
5
6
7
8
9
10
5
6
7
8
9
10
5
6
7
8
9
10
5
6
7
8
9
10
5
6
7
8
9
10
Average condensation temperature [°C]
35
40
45
50
55
60
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
453
468
486
505
524
543
481
497
516
536
556
577
525
541
562
583
605
628
569
589
610
632
654
677
609
631
653
675
699
723
628
652
677
703
730
757
648
672
698
725
752
780
697
723
751
779
809
839
720
747
775
805
835
867
748
775
805
836
867
900
790
821
853
884
916
948
867
898
928
961
993
1027
88
88
89
89
90
91
93
94
95
95
96
97
106
106
107
108
109
110
112
113
114
115
115
116
118
119
120
121
122
122
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
141
142
143
144
145
146
144
145
146
147
148
149
149
150
151
152
153
154
166
167
168
169
171
172
541
556
575
594
614
634
574
591
611
631
652
674
630
647
669
691
714
738
681
703
724
747
769
793
727
750
773
796
820
845
753
777
803
830
858
886
778
803
830
857
886
915
833
860
888
918
948
980
861
888
918
949
980
1013
892
920
951
983
1016
1049
938
970
1004
1036
1069
1102
1033
1065
1097
1130
1164
1198
429
442
460
477
496
514
455
470
488
507
526
546
496
512
532
552
573
595
538
558
578
598
619
641
575
597
618
640
662
685
593
616
640
665
690
716
611
635
659
685
711
738
659
683
710
737
766
795
680
706
733
762
791
821
706
733
761
791
821
852
745
774
804
834
864
894
820
850
879
909
941
973
94
94
95
96
96
97
100
100
101
102
103
104
113
113
114
115
116
117
120
121
122
122
123
124
126
127
128
129
130
131
132
133
134
135
136
137
138
140
141
142
143
144
145
146
147
148
149
150
150
151
152
153
154
156
154
155
156
157
158
159
158
160
161
162
163
164
177
178
180
181
182
183
522
537
555
573
592
612
554
570
589
609
629
650
609
625
646
667
689
712
658
678
699
721
743
765
702
724
746
768
792
815
726
749
774
800
827
854
750
774
800
827
854
882
803
829
857
885
915
945
830
857
885
915
945
976
860
887
917
948
979
1011
903
934
965
996
1027
1058
997
1028
1058
1090
1123
1156
402
415
431
448
466
484
427
441
458
476
495
514
465
481
499
519
539
560
505
524
543
563
583
603
540
560
580
601
623
644
556
577
600
624
648
673
573
595
618
643
668
694
618
641
666
693
719
747
638
662
688
715
743
772
662
687
714
742
771
801
696
724
752
780
808
837
769
798
825
855
885
915
102
103
104
104
105
106
109
109
110
111
112
113
122
123
124
125
126
127
130
131
132
133
134
135
137
138
139
140
141
142
144
145
146
147
148
149
151
152
153
154
155
156
157
158
160
161
162
163
163
164
166
167
168
169
167
168
170
171
172
173
172
173
175
176
177
178
193
194
195
197
198
199
504
518
535
553
571
590
535
550
568
587
607
627
588
604
624
644
665
687
635
655
675
696
717
738
677
698
720
741
764
786
700
722
746
771
796
823
723
746
771
797
823
850
775
799
826
853
882
911
801
826
854
882
911
941
829
855
884
913
944
975
869
898
927
956
985
1016
962
992
1021
1052
1083
1114
374
386
402
418
434
451
396
410
426
443
461
479
433
447
465
484
503
522
470
488
506
525
544
563
503
521
541
561
581
602
516
536
558
580
603
627
531
552
575
598
622
646
574
596
620
645
671
697
593
615
640
666
693
720
615
639
665
691
719
747
645
672
697
723
750
777
715
742
769
797
825
854
113
114
115
115
116
117
120
121
122
123
124
125
135
136
137
138
139
140
144
145
146
147
148
149
152
153
154
155
156
157
159
160
162
163
164
165
166
168
169
170
172
173
174
175
177
178
179
181
180
182
183
184
186
187
185
186
188
189
190
192
190
192
193
194
196
197
213
215
216
217
219
220
487
500
516
533
550
568
517
531
548
566
585
604
568
583
602
622
642
663
614
633
652
672
692
712
654
674
695
716
737
759
675
696
719
743
767
792
698
720
744
768
793
819
748
771
797
823
850
877
773
797
823
850
878
907
800
825
852
880
909
939
836
863
890
918
946
974
928
957
985
1014
1044
1075
344
356
370
385
401
416
364
377
392
408
425
442
398
411
429
446
464
483
433
450
467
484
502
521
463
480
499
518
537
556
473
492
513
534
556
579
487
507
528
550
573
596
527
548
571
595
619
644
544
566
590
614
639
665
565
587
612
637
663
690
591
616
639
664
689
714
658
684
709
736
763
790
126
127
128
129
130
131
135
135
136
138
139
140
150
152
153
154
155
156
161
162
163
164
165
167
170
171
173
174
175
176
178
180
181
182
184
185
187
188
189
191
192
193
195
196
198
199
201
202
202
203
205
206
208
209
207
208
210
212
213
215
213
214
216
217
219
220
239
240
242
244
245
247
470
483
498
514
531
547
499
512
529
546
564
582
548
563
581
600
619
639
594
612
630
649
668
687
633
652
671
691
712
732
651
672
694
716
740
764
674
695
718
741
765
790
722
744
769
794
819
846
746
769
795
820
847
874
772
796
822
849
876
905
804
830
855
881
908
935
897
924
951
979
1008
1037
311
323
336
351
365
380
330
342
356
371
387
403
361
374
390
406
423
441
393
409
425
442
458
476
420
437
454
472
490
509
428
446
466
486
506
528
441
460
480
500
522
544
478
498
519
541
564
588
493
514
536
559
583
607
512
533
556
580
605
630
534
557
579
602
625
649
597
622
646
671
696
722
143
143
144
145
146
147
152
153
154
155
156
157
169
170
172
173
174
176
182
183
184
185
186
188
193
194
195
196
198
199
202
203
204
206
207
209
211
213
214
215
217
218
220
222
223
225
227
228
229
230
232
233
235
236
234
236
237
239
241
242
241
242
244
245
247
249
270
272
274
275
277
279
454
466
481
496
511
527
482
494
510
526
543
560
530
544
561
579
597
616
575
592
609
627
645
664
613
631
650
668
688
708
630
649
670
692
714
736
652
672
694
716
739
762
698
719
743
766
791
816
722
744
768
792
818
844
746
769
794
819
845
872
775
799
823
847
872
897
867
894
920
946
973
1001
Pf: cooling capacity [kW]
Pe: electrical power absorbed by the compressors [kW]
Pr: condenser heating capacity [kW]
T0:evaporator outgoing water temperature [°C] Evaporator thermal gap = 5°C
Swegon reserves the right to alter specifications.
www.swegon.com
25
COBALT W
COOLING CAPACITY - COBALT W /LC
To
Model
95.2
100.2
105.2
110.2
117.2
124.2
130.3
137.3
143.3
147.3
153.3
[°C]
5
6
7
8
9
10
5
6
7
8
9
10
5
6
7
8
9
10
5
6
7
8
9
10
5
6
7
8
9
10
5
6
7
8
9
10
5
6
7
8
9
10
5
6
7
8
9
10
5
6
7
8
9
10
5
6
7
8
9
10
5
6
7
8
9
10
Average condensation temperature [°C]
35
40
45
50
55
60
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
943
975
1006
1041
1076
1111
1014
1049
1082
1120
1159
1199
1068
1103
1138
1178
1220
1262
1117
1157
1198
1241
1284
1327
1197
1240
1283
1328
1374
1421
1254
1298
1343
1390
1438
1487
1302
1348
1394
1442
1492
1542
1356
1404
1452
1502
1553
1606
1436
1485
1534
1589
1644
1700
1469
1519
1570
1625
1681
1739
1534
1586
1639
1696
1755
1815
175
176
177
178
179
180
187
188
189
190
191
193
199
200
201
203
204
205
206
208
209
210
212
213
219
221
222
224
225
226
232
233
235
236
238
239
244
245
247
248
250
251
253
254
256
258
259
261
263
265
267
268
270
272
272
273
275
277
279
280
286
288
290
292
294
296
1118
1151
1183
1219
1255
1292
1201
1237
1271
1310
1350
1392
1267
1303
1339
1381
1424
1467
1323
1365
1407
1451
1495
1540
1417
1460
1505
1552
1599
1647
1485
1531
1578
1626
1676
1726
1546
1593
1641
1691
1741
1793
1609
1658
1708
1760
1813
1867
1699
1750
1801
1857
1914
1972
1741
1792
1845
1902
1960
2020
1820
1874
1929
1988
2049
2111
891
922
952
985
1019
1053
959
992
1024
1060
1097
1135
1010
1044
1076
1115
1155
1195
1056
1094
1134
1174
1216
1257
1132
1173
1214
1257
1301
1346
1185
1228
1271
1316
1362
1409
1232
1275
1319
1365
1413
1461
1283
1328
1374
1422
1471
1521
1358
1405
1452
1504
1557
1611
1389
1437
1485
1538
1592
1648
1451
1500
1551
1606
1662
1720
186
188
189
190
191
193
199
200
202
203
204
206
212
213
215
216
218
219
220
221
223
224
226
227
234
235
237
239
240
242
247
249
250
252
254
255
260
261
263
265
267
268
269
271
273
275
277
279
281
282
284
286
288
290
290
292
294
296
298
300
305
307
309
311
314
316
1078
1110
1141
1175
1210
1245
1158
1192
1225
1263
1301
1341
1222
1257
1291
1331
1372
1414
1276
1316
1357
1399
1442
1485
1366
1408
1451
1496
1541
1588
1432
1476
1521
1568
1616
1664
1491
1536
1582
1630
1679
1729
1552
1599
1647
1697
1748
1800
1638
1687
1737
1790
1845
1901
1679
1729
1779
1834
1890
1947
1756
1808
1860
1917
1976
2036
836
866
895
926
958
990
900
931
962
996
1031
1068
947
980
1011
1048
1085
1124
991
1027
1065
1104
1143
1183
1062
1101
1141
1182
1224
1266
1112
1153
1194
1237
1280
1325
1156
1197
1239
1283
1328
1374
1204
1247
1291
1337
1383
1431
1274
1319
1364
1414
1464
1516
1304
1349
1396
1446
1498
1550
1361
1409
1457
1509
1563
1618
203
204
205
207
208
209
216
218
219
221
222
224
230
232
233
235
237
238
239
241
242
244
246
247
254
256
258
260
261
263
268
270
272
274
276
278
282
284
286
288
290
292
293
295
297
299
301
303
305
307
309
311
314
316
315
317
319
322
324
326
332
334
336
339
341
343
1039
1070
1100
1133
1166
1200
1116
1149
1181
1217
1254
1292
1178
1212
1244
1283
1322
1362
1230
1268
1307
1348
1389
1430
1317
1357
1398
1441
1485
1529
1381
1423
1466
1511
1556
1603
1438
1481
1525
1572
1619
1666
1497
1542
1588
1636
1685
1734
1580
1626
1674
1725
1778
1831
1619
1667
1715
1768
1821
1876
1693
1743
1793
1848
1904
1962
777
806
833
863
894
924
836
867
895
928
961
996
881
912
941
976
1012
1048
921
956
991
1028
1066
1103
988
1025
1062
1101
1141
1182
1034
1073
1112
1152
1194
1236
1075
1114
1154
1196
1239
1282
1119
1160
1202
1246
1290
1335
1185
1228
1271
1318
1366
1415
1213
1256
1300
1348
1397
1447
1266
1311
1357
1407
1458
1510
224
226
227
229
230
232
239
241
243
244
246
248
255
256
258
260
262
263
264
266
268
270
272
274
281
283
285
287
289
291
297
299
301
303
305
307
312
314
317
319
321
323
324
326
329
331
333
335
337
340
342
344
347
349
348
351
353
355
358
360
367
370
372
375
377
380
1001
1031
1060
1092
1124
1156
1076
1108
1138
1172
1207
1244
1135
1168
1199
1235
1273
1312
1185
1222
1259
1298
1337
1377
1269
1308
1347
1388
1430
1473
1331
1371
1413
1455
1499
1544
1387
1428
1471
1515
1560
1605
1443
1487
1530
1576
1623
1670
1523
1568
1613
1662
1712
1764
1561
1607
1653
1703
1755
1807
1633
1681
1729
1781
1835
1890
715
742
768
797
825
855
769
798
826
856
888
920
810
839
867
900
934
968
847
879
913
948
984
1020
909
943
979
1016
1054
1092
951
987
1024
1063
1102
1143
989
1026
1064
1103
1144
1185
1030
1068
1108
1149
1191
1234
1090
1131
1171
1216
1261
1308
1115
1157
1198
1243
1290
1337
1165
1207
1250
1298
1346
1396
251
253
254
256
258
259
268
270
272
273
275
277
286
287
289
291
293
295
296
298
300
302
304
306
315
317
319
321
323
326
333
335
337
339
342
344
350
352
355
357
359
361
363
366
368
370
373
375
378
381
383
386
388
391
390
393
395
398
401
403
411
414
417
419
422
425
966
995
1022
1053
1083
1114
1037
1068
1097
1130
1163
1197
1095
1126
1156
1191
1226
1263
1143
1178
1213
1250
1288
1326
1224
1261
1298
1337
1377
1418
1284
1322
1362
1402
1444
1486
1338
1378
1418
1460
1503
1547
1393
1434
1476
1519
1564
1609
1469
1511
1554
1601
1649
1698
1506
1549
1593
1641
1691
1741
1576
1621
1667
1717
1768
1821
648
674
700
726
754
781
698
725
752
781
810
840
734
763
789
819
851
884
768
799
831
864
897
931
825
857
891
926
962
998
863
897
932
969
1006
1044
897
932
968
1006
1044
1083
934
971
1008
1047
1087
1127
990
1028
1066
1108
1151
1195
1013
1051
1090
1133
1177
1222
1057
1097
1138
1183
1228
1275
284
286
288
289
291
293
303
305
307
309
311
313
323
325
327
329
331
333
335
337
339
342
344
346
356
359
361
363
365
368
376
379
381
384
386
388
396
398
401
403
406
408
411
414
416
419
421
424
428
431
433
436
439
441
442
444
447
450
453
456
466
468
471
474
477
480
932
960
987
1016
1045
1074
1001
1030
1059
1090
1121
1153
1057
1088
1116
1148
1182
1217
1103
1136
1170
1205
1241
1277
1181
1216
1252
1289
1327
1366
1239
1276
1313
1352
1392
1432
1293
1331
1369
1409
1450
1491
1345
1385
1424
1466
1508
1551
1418
1458
1499
1544
1590
1636
1454
1496
1537
1583
1630
1677
1523
1566
1609
1657
1705
1755
Pf: cooling capacity [kW]
Pe: electrical power absorbed by the compressors [kW]
Pr: condenser heating capacity [kW]
T0:evaporator outgoing water temperature [°C] Evaporator thermal gap = 5°C
26
Swegon reserves the right to alter specifications.
www.swegon.com
COBALT W
RECOVERY CAPACITY - COBALT W /DC
To
Model
18.1
20.1
22.1
24.1
27.1
31.1
35.1
36.2
38.2
41.2
42.1
45.2
[°C]
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
Condenser outgoing water temperature [°C]
30
35
40
45
50
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
173
179
186
192
199
195
202
209
216
223
212
220
227
235
243
244
252
261
270
280
273
283
294
304
316
302
313
325
337
349
338
350
363
376
390
349
361
375
388
401
371
385
399
413
427
393
407
422
436
452
411
426
441
457
473
432
448
464
481
498
36
37
37
37
37
40
40
41
41
41
43
43
44
44
44
49
50
50
51
51
56
57
57
58
58
62
63
63
64
65
67
68
68
69
69
73
73
74
75
75
75
76
77
77
78
80
81
81
82
83
84
85
86
86
87
87
88
89
89
90
209
216
222
229
236
235
242
250
257
264
255
263
271
279
288
293
302
311
321
331
329
340
351
362
374
364
376
388
401
413
405
418
431
445
459
422
435
449
462
476
447
461
475
490
505
473
488
503
518
535
495
511
527
543
560
519
535
552
570
588
166
172
178
184
191
186
193
200
207
213
203
210
218
226
234
233
241
250
258
267
260
270
280
290
301
288
299
310
320
332
323
334
346
359
372
333
346
359
371
384
355
368
381
395
408
375
389
403
417
432
393
407
422
437
453
412
427
442
459
476
39
39
39
40
40
42
43
43
44
44
46
46
46
47
47
52
53
53
54
54
59
60
61
61
62
66
67
67
68
69
71
72
72
73
74
77
78
79
79
80
80
81
82
82
83
85
86
87
87
88
89
90
91
91
92
92
93
94
95
96
204
211
217
224
231
229
236
243
250
258
249
256
264
273
281
285
294
303
312
322
320
330
341
352
363
354
366
377
389
401
394
406
419
432
446
410
424
437
450
464
435
449
463
477
491
460
475
490
505
520
482
497
513
528
545
504
520
536
554
572
158
164
170
176
182
178
184
190
197
204
194
201
208
216
223
221
229
237
246
254
247
256
266
275
285
273
284
294
304
315
307
318
330
342
354
317
329
341
353
366
338
350
363
376
389
357
371
384
398
412
373
387
401
415
430
392
407
421
437
452
42
42
42
43
43
46
46
47
47
48
49
50
50
51
51
57
57
58
59
59
64
65
66
66
67
71
72
73
74
75
77
78
79
79
80
83
84
85
86
86
86
87
88
89
90
92
93
93
94
95
96
97
98
99
100
100
101
102
103
104
200
206
212
219
225
223
230
237
244
251
243
250
258
266
274
278
286
295
304
313
311
321
331
342
352
345
356
367
378
390
384
396
408
421
434
400
413
426
439
452
424
438
451
465
479
449
463
478
492
507
469
484
499
514
530
492
508
523
539
556
150
155
161
167
173
167
173
180
186
193
183
190
197
204
212
208
216
224
231
240
232
240
250
259
269
257
267
277
286
297
290
300
312
323
335
300
311
323
335
347
319
331
343
356
369
338
350
363
375
389
352
366
379
392
405
370
384
398
412
428
45
46
46
47
47
50
51
51
52
52
54
55
55
56
56
63
63
64
65
65
70
71
72
73
74
78
79
80
81
82
85
86
86
87
88
91
92
93
94
95
95
96
97
98
99
101
102
103
104
105
106
107
108
109
110
110
111
112
113
114
195
201
207
214
220
218
224
231
238
245
237
245
252
260
268
271
279
287
296
305
302
312
322
332
342
335
346
357
368
379
375
386
398
410
423
391
403
416
428
441
414
427
440
453
467
438
452
466
479
494
458
472
487
501
516
480
495
509
525
542
140
145
151
157
163
156
162
168
174
180
172
178
185
192
199
194
201
209
216
224
216
224
233
242
251
239
248
257
267
277
271
281
292
303
313
280
291
302
314
325
298
310
321
333
346
316
328
340
353
366
330
342
355
367
380
346
359
373
386
401
51
51
52
52
53
56
57
57
58
58
60
61
61
62
63
70
71
71
72
73
78
79
80
81
82
87
88
90
91
92
94
95
96
97
99
101
102
103
104
105
106
107
108
109
110
112
114
115
116
117
118
119
120
122
123
122
124
125
126
127
191
197
203
209
215
212
219
225
232
239
232
239
246
254
261
264
272
280
289
297
294
303
313
323
333
326
337
347
358
369
366
377
388
400
412
381
393
405
418
431
404
416
429
442
456
428
442
455
468
483
448
461
476
489
504
469
483
497
512
528
Pf: cooling capacity [kW]
Pe: electrical power absorbed by the compressors [kW]
Pr: condenser heating capacity [kW]
T0: evaporator outgoing water temperature [°C] Evaporator thermal gap = 5°C
Swegon reserves the right to alter specifications.
www.swegon.com
27
COBALT W
RECOVERY CAPACITY - COBALT W /DC
To
Model
46.2
49.2
53.2
57.2
62.2
65.2
69.2
72.2
76.2
78.2
83.2
88.2
[°C]
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
Condenser outgoing water temperature [°C]
30
35
40
45
50
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
463
480
497
516
534
496
514
532
552
571
533
553
572
593
615
577
596
615
636
657
616
635
656
678
701
650
673
697
723
748
681
705
730
757
784
721
748
775
803
832
762
790
818
848
879
789
818
848
879
911
836
864
894
924
955
894
922
953
984
1016
93
93
94
95
96
99
100
101
101
102
107
108
109
110
111
118
119
120
121
122
125
126
127
128
129
130
131
132
133
134
134
136
137
138
139
143
145
146
147
148
155
157
158
159
160
152
153
155
156
157
169
170
172
173
174
178
180
182
183
185
556
574
592
611
630
594
614
633
653
674
640
661
682
703
726
695
715
735
757
779
741
761
783
806
829
779
804
829
856
883
815
840
867
895
923
864
892
921
950
980
917
946
976
1007
1039
941
972
1002
1034
1068
1005
1035
1066
1097
1130
1073
1102
1135
1167
1201
441
458
475
492
509
472
490
507
526
545
508
527
546
566
586
550
569
588
608
628
588
607
627
649
670
619
642
665
689
714
648
672
696
721
748
687
712
739
766
794
725
753
781
809
838
752
780
809
839
869
803
831
860
890
919
850
878
908
938
968
99
99
100
101
102
105
106
107
108
109
114
115
116
117
118
125
126
128
129
130
132
133
134
136
137
137
139
140
142
143
143
144
145
147
148
152
153
155
156
158
164
166
167
169
171
161
162
164
165
167
179
181
183
184
186
190
192
194
196
198
540
557
575
593
612
577
596
615
634
654
622
642
662
683
705
676
695
715
737
758
720
740
762
784
807
757
780
805
831
857
791
816
842
868
896
839
866
894
922
951
890
919
948
978
1008
913
942
973
1004
1036
982
1012
1042
1074
1105
1040
1070
1102
1134
1166
419
435
451
467
484
447
464
481
499
517
481
500
518
536
555
522
540
558
577
597
557
576
596
617
637
586
608
630
654
678
614
636
660
685
710
650
676
701
726
751
687
714
741
767
793
712
740
767
795
824
765
793
822
851
880
804
831
860
888
918
106
108
109
110
111
114
115
116
117
119
123
124
126
127
129
135
137
138
139
141
143
144
146
147
148
149
150
152
153
155
154
156
158
159
160
164
165
167
169
171
178
179
181
183
185
174
175
177
179
180
194
196
197
199
201
206
208
211
213
215
525
542
559
577
595
561
579
597
616
636
605
624
643
663
684
657
677
696
717
738
700
720
742
764
786
735
758
782
807
832
768
792
817
844
871
814
841
868
895
922
865
893
921
950
978
886
915
944
974
1005
959
989
1019
1050
1081
1011
1040
1070
1102
1133
394
409
424
440
457
420
436
453
470
488
453
470
487
505
524
491
509
526
545
563
525
543
562
582
602
551
572
593
616
638
577
598
621
645
669
612
635
659
683
707
647
671
697
720
747
670
696
722
749
775
720
749
777
806
833
755
781
808
836
864
117
118
120
121
122
125
127
128
129
131
135
137
138
140
141
149
150
152
153
155
157
159
160
162
163
163
165
167
168
170
170
171
173
175
176
180
182
184
186
188
195
197
199
202
204
190
192
194
196
199
213
215
217
219
223
227
230
232
235
238
511
527
544
561
579
545
563
581
599
618
588
606
625
645
665
640
659
678
698
718
682
702
722
744
765
714
737
760
784
808
747
770
794
820
846
792
817
843
869
895
841
868
895
922
950
861
888
916
945
974
933
964
994
1025
1055
982
1011
1041
1071
1102
368
382
397
411
427
392
407
423
438
455
421
438
455
472
489
458
475
492
509
527
489
507
526
545
564
513
533
553
575
595
538
558
580
602
622
569
592
613
636
659
602
625
647
672
696
624
648
672
697
723
671
697
725
751
779
701
726
752
778
805
131
132
133
134
136
140
141
143
144
146
150
152
153
155
157
166
167
169
170
172
175
177
179
180
182
182
184
186
188
190
189
191
193
195
198
200
203
206
208
210
217
219
222
225
228
212
214
217
220
222
237
240
242
246
248
254
257
260
263
266
498
514
530
546
563
531
548
565
582
600
572
590
608
627
646
624
642
661
680
699
665
684
704
725
746
695
717
739
762
785
726
749
772
797
820
770
794
818
844
869
819
844
870
897
924
836
863
889
917
945
908
937
967
996
1027
955
983
1012
1041
1072
Pf: cooling capacity [kW]
Pe: electrical power absorbed by the compressors [kW]
Pr: condenser heating capacity [kW]
T0: evaporator outgoing water temperature [°C] Evaporator thermal gap = 5°C
28
Swegon reserves the right to alter specifications.
www.swegon.com
COBALT W
RECOVERY CAPACITY - COBALT W /DC
To
Model
95.2
100.2
105.2
110.2
117.2
124.2
130.3
137.3
143.3
147.3
153.3
[°C]
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
6
7
8
9
10
Condenser outgoing water temperature [°C]
30
35
40
45
50
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
Pf
Pe
Pr
965
993
1026
1060
1094
1012
1043
1079
1115
1152
1069
1103
1140
1178
1217
1109
1147
1185
1225
1265
1191
1231
1272
1315
1358
1246
1288
1332
1376
1421
1305
1348
1394
1440
1487
1393
1440
1488
1537
1588
1449
1498
1549
1601
1655
1490
1540
1593
1646
1701
1554
1606
1661
1717
1774
186
187
189
191
192
202
204
206
208
210
206
208
210
212
213
222
224
226
228
230
235
238
240
242
244
248
250
252
255
257
261
264
266
269
271
275
277
280
283
285
288
291
294
296
299
296
299
302
305
307
304
306
309
312
315
1150
1180
1214
1250
1287
1214
1247
1285
1323
1361
1275
1310
1349
1389
1430
1331
1371
1411
1452
1494
1427
1469
1512
1557
1602
1494
1538
1584
1631
1678
1566
1612
1660
1709
1758
1668
1717
1768
1820
1873
1737
1789
1843
1898
1954
1786
1839
1894
1951
2009
1857
1912
1970
2029
2089
918
946
977
1009
1042
963
993
1027
1061
1096
1017
1049
1085
1121
1158
1055
1091
1128
1166
1204
1132
1171
1210
1251
1292
1185
1225
1267
1309
1352
1240
1282
1325
1370
1415
1324
1369
1415
1462
1510
1377
1424
1473
1523
1574
1416
1464
1514
1566
1619
1477
1527
1580
1633
1688
198
200
202
204
206
216
218
220
222
224
219
221
224
226
228
236
238
241
243
246
251
253
256
258
261
264
267
270
272
275
278
281
284
287
290
293
296
299
302
306
307
310
313
316
320
316
319
322
325
329
323
326
330
333
336
1116
1145
1179
1213
1248
1178
1211
1246
1283
1321
1236
1270
1308
1347
1387
1291
1329
1369
1409
1450
1383
1424
1466
1509
1553
1449
1492
1536
1581
1627
1518
1563
1610
1657
1705
1617
1665
1714
1764
1816
1684
1734
1786
1840
1894
1732
1783
1836
1891
1947
1800
1853
1909
1966
2025
869
896
927
957
989
910
940
972
1005
1038
961
992
1026
1061
1097
997
1032
1067
1103
1140
1070
1107
1144
1183
1223
1120
1158
1198
1238
1279
1171
1211
1253
1295
1338
1251
1294
1338
1383
1429
1302
1347
1394
1442
1491
1339
1385
1433
1482
1532
1396
1444
1494
1546
1598
214
216
219
221
224
234
236
239
241
244
238
240
243
246
248
256
259
262
264
267
272
275
278
281
284
287
290
293
296
300
302
305
309
312
316
318
321
325
329
332
332
336
340
343
347
342
346
349
353
357
350
354
358
362
366
1083
1113
1145
1178
1212
1144
1176
1210
1246
1282
1199
1232
1269
1307
1345
1253
1290
1329
1368
1407
1342
1382
1422
1464
1507
1406
1448
1491
1534
1579
1473
1517
1562
1608
1654
1569
1615
1663
1712
1762
1635
1683
1733
1785
1838
1681
1730
1782
1835
1890
1746
1798
1852
1907
1964
815
842
871
901
931
854
882
913
944
976
902
931
964
997
1031
936
968
1002
1036
1072
1002
1037
1072
1109
1147
1047
1083
1121
1159
1198
1099
1137
1177
1217
1258
1173
1214
1256
1299
1343
1221
1264
1308
1354
1401
1256
1299
1345
1392
1440
1310
1355
1403
1452
1502
236
239
241
244
247
258
260
263
266
269
262
265
268
271
274
282
285
289
292
295
300
304
307
311
315
317
321
325
329
333
333
337
340
344
348
351
355
359
363
367
366
370
375
379
383
377
381
385
390
394
386
390
395
399
404
1052
1081
1113
1145
1178
1112
1143
1176
1211
1246
1164
1196
1232
1268
1305
1218
1253
1290
1328
1367
1302
1340
1380
1420
1461
1364
1404
1445
1488
1531
1432
1474
1517
1562
1607
1524
1569
1615
1662
1710
1588
1634
1683
1733
1784
1632
1680
1731
1782
1834
1695
1745
1798
1851
1906
757
784
812
840
868
793
821
850
879
910
838
866
897
928
960
869
899
931
964
998
930
963
997
1032
1067
972
1006
1041
1078
1114
1021
1056
1094
1132
1171
1089
1127
1167
1208
1250
1136
1174
1217
1260
1304
1166
1208
1251
1295
1341
1216
1260
1305
1351
1398
264
267
270
273
277
288
291
295
298
301
293
297
300
303
307
316
319
323
326
330
336
340
344
348
352
355
359
364
368
373
372
376
381
385
390
392
397
402
406
411
410
414
419
424
429
421
426
431
436
441
432
437
442
447
452
1022
1051
1082
1113
1145
1081
1112
1144
1177
1211
1131
1163
1197
1231
1267
1185
1218
1254
1291
1328
1266
1302
1341
1380
1419
1328
1365
1405
1446
1487
1394
1433
1475
1518
1561
1481
1524
1569
1615
1661
1545
1589
1636
1684
1733
1587
1634
1682
1732
1782
1648
1696
1746
1798
1850
Pf: cooling capacity [kW]
Pe: electrical power absorbed by the compressors [kW]
Pr: condenser heating capacity [kW]
T0: evaporator outgoing water temperature [°C] Evaporator thermal gap = 5°C
Swegon reserves the right to alter specifications.
www.swegon.com
29
COBALT W
SOUND LEVEL - COBALT W /A /LC - STANDARD UNIT
MODEL
Octave bande [dB]
63 Hz
125 Hz
250 Hz
500 Hz
1000 Hz
2000 Hz
4000 Hz
8000 Hz
Total
[dB(A)]
Lw
Lp
Lw
Lp
Lw
Lp
Lw
Lp
Lw
Lp
Lw
Lp
Lw
Lp
Lw
Lp
Lw
Lp
18.1
70
53
69
52
73
56
71
54
81
64
78
61
73
56
62
45
84
67
20.1
70
53
69
52
73
56
71
54
81
64
78
61
73
56
62
45
84
67
22.1
70
53
69
52
73
56
71
54
81
64
78
61
73
56
62
45
84
67
24.1
73
56
71
54
76
59
74
57
84
67
81
64
76
59
65
48
87
70
27.1
75
58
73
56
78
61
76
59
86
69
83
66
78
61
66
49
89
72
31.1
77
60
75
58
79
62
78
61
88
71
85
68
80
63
68
51
91
74
35.1
78
60
77
59
81
63
79
61
90
72
87
69
82
64
69
51
93
75
36.2
75
57
74
56
78
60
76
58
86
68
83
65
78
60
67
49
89
71
38.2
73
55
72
54
76
58
74
56
84
66
81
63
76
58
65
47
87
69
41.2
73
55
72
54
76
58
74
56
84
66
81
63
76
58
65
47
87
69
42.1
82
64
80
62
85
67
83
65
94
76
91
73
85
67
73
55
97
79
45.2
73
55
72
54
76
58
74
56
84
66
81
63
76
58
65
47
87
69
46.2
73
55
72
54
76
58
74
56
84
66
81
63
76
58
65
47
87
69
49.2
73
55
72
54
76
58
74
56
84
66
81
63
76
58
65
47
87
69
53.2
73
55
72
54
76
58
74
56
84
66
81
63
76
58
65
47
87
69
73
57.2
77
59
75
57
80
62
78
60
88
70
85
67
80
62
69
51
91
62.2
79
61
77
59
82
64
80
62
90
72
87
69
82
64
70
52
93
75
65.2
77
58
75
57
80
61
78
59
88
69
85
67
80
61
69
50
91
72
69.2
81
63
80
61
84
66
82
64
93
74
90
72
85
66
72
54
96
77
72.2
81
63
80
61
84
66
82
64
93
74
90
72
85
66
72
54
96
77
76.2
82
64
80
62
85
67
83
65
94
76
91
73
86
67
73
55
97
78
78.2
83
64
81
62
86
67
84
65
95
76
92
73
86
67
74
55
98
79
83.2
85
66
83
64
88
69
86
67
97
78
94
75
88
69
76
57
100
81
88.2
85
66
83
64
88
69
86
67
97
78
94
75
88
69
76
57
100
81
95.2
85
66
83
64
88
69
86
67
97
78
94
75
88
69
76
57
100
81
100.2
85
66
83
64
88
69
86
67
97
78
94
75
88
69
76
57
100
81
105.2
85
66
83
64
88
69
86
67
97
78
94
75
88
69
76
57
100
81
110.2
85
65
83
63
88
68
86
66
97
77
94
74
88
68
76
56
100
80
117.2
86
66
84
64
89
69
87
67
98
78
95
75
89
69
76
56
101
81
124.2
86
66
84
64
89
69
87
67
98
78
95
75
89
69
76
56
101
81
130.3
86
66
84
64
89
69
87
67
98
78
95
75
89
69
77
57
101
81
137.3
86
66
84
64
89
69
87
67
98
78
95
75
89
69
77
57
101
81
143.3
86
66
84
64
89
69
87
67
98
78
95
75
89
69
77
57
101
81
147.3
86
66
84
64
89
69
87
67
98
78
95
75
89
69
77
57
101
81
153.3
86
66
84
64
89
69
87
67
98
78
95
75
89
69
77
57
101
81
Lw:noise power levels measured in free field according to standard ISO 3744.
Lp: sound pressure levels measured at 1 metres from the unit in free field under nominal working conditions, according to ISO 3744
Data acquired with unit operating at the following conditions: A 35°C; W12/7°C
30
Swegon reserves the right to alter specifications.
www.swegon.com
COBALT W
SOUND LEVEL - COBALT W /A /LC - LOW NOISE UNIT
MODEL
Octave bande [dB]
63 Hz
125 Hz
250 Hz
500 Hz
1000 Hz
2000 Hz
4000 Hz
8000 Hz
Total
[dB(A)]
Lw
Lp
Lw
Lp
Lw
Lp
Lw
Lp
Lw
Lp
Lw
Lp
Lw
Lp
Lw
Lp
Lw
Lp
18.1
67
50
65
48
69
52
68
51
76
59
74
57
69
52
60
43
80
63
20.1
67
50
65
48
69
52
68
51
76
59
74
57
69
52
60
43
80
63
22.1
67
50
65
48
69
52
68
51
76
59
74
57
69
52
60
43
80
63
24.1
69
52
67
50
71
54
70
53
78
61
76
59
71
54
61
44
82
65
27.1
71
54
69
52
73
56
71
54
80
63
78
61
73
56
63
46
84
67
31.1
73
56
71
54
76
59
74
57
84
67
81
64
76
59
65
48
87
70
35.1
74
56
72
54
77
59
75
57
85
67
82
64
77
59
66
48
88
70
36.2
72
54
70
52
74
56
72
54
81
63
79
61
74
56
64
46
85
67
38.2
70
52
68
50
72
54
71
53
79
61
77
59
72
54
63
45
83
65
41.2
70
52
68
50
72
54
71
53
79
61
77
59
72
54
63
45
83
65
42.1
79
61
77
59
81
63
79
61
90
72
87
69
82
64
70
52
93
75
45.2
69
51
68
50
71
53
70
52
78
60
76
58
72
54
62
44
82
64
46.2
69
51
68
50
71
53
70
52
78
60
76
58
72
54
62
44
82
64
49.2
69
51
68
50
71
53
70
52
78
60
76
58
72
54
62
44
82
64
53.2
69
51
67
49
71
53
70
52
78
60
76
58
71
53
62
44
82
64
57.2
73
55
72
54
76
58
74
56
84
66
81
63
76
58
66
48
87
69
62.2
74
56
73
55
77
59
75
57
85
67
82
64
77
59
67
49
88
70
65.2
73
55
72
53
76
57
74
56
84
65
81
63
76
58
66
47
87
68
69.2
77
59
75
57
80
61
78
59
88
69
85
67
80
61
69
50
91
72
72.2
78
59
76
58
81
62
79
60
89
70
86
68
81
62
70
51
92
73
76.2
78
59
76
58
81
62
79
60
89
70
86
68
81
62
70
51
92
73
78.2
79
60
77
58
82
63
80
61
90
71
87
68
82
63
70
51
93
74
83.2
81
62
79
60
84
65
82
63
92
73
89
70
84
65
72
53
95
76
88.2
81
62
79
60
84
65
82
63
92
73
89
70
84
65
72
53
95
76
95.2
81
62
79
60
84
65
82
63
92
73
89
70
84
65
72
53
95
76
100.2
81
62
79
60
84
65
82
63
92
73
89
70
84
65
72
53
95
76
105.2
81
62
79
60
83
64
81
62
92
73
89
70
84
65
72
53
95
76
110.2
82
62
80
60
84
64
82
62
93
73
90
70
85
65
73
53
96
76
117.2
82
62
80
60
84
64
82
62
93
73
90
70
85
65
73
53
96
76
124.2
82
62
80
60
84
64
82
62
93
73
90
70
85
65
73
53
96
76
130.3
82
62
80
60
85
65
83
63
93
73
90
70
85
65
73
53
96
76
137.3
82
62
80
60
85
65
83
63
93
73
90
70
85
65
73
53
96
76
143.3
82
62
80
60
85
65
83
63
93
73
90
70
85
65
73
53
96
76
147.3
83
63
81
61
85
65
83
63
94
74
91
71
86
66
74
54
97
77
153.3
83
63
81
61
85
65
83
63
94
74
91
71
86
66
74
54
97
77
Lw:noise power levels measured in free field according to standard ISO 3744.
Lp: sound pressure levels measured at 1 metres from the unit in free field under nominal working conditions, according to ISO 3744
Data acquired with unit operating at the following conditions: A 35°C; W12/7°C
Swegon reserves the right to alter specifications.
www.swegon.com
31
COBALT W
SOUND LEVEL - COBALT W /A /LC - SUPER LOW NOISE UNIT
MODEL
18.1
Octave bande [dB]
63 Hz
125 Hz
250 Hz
500 Hz
1000 Hz
2000 Hz
4000 Hz
8000 Hz
Total
[dB(A)]
Lw
Lp
Lw
Lp
Lw
Lp
Lw
Lp
Lw
Lp
Lw
Lp
Lw
Lp
Lw
Lp
Lw
Lp
61
44
60
43
63
46
61
44
69
52
67
50
63
46
55
38
73
56
20.1
61
44
60
43
63
46
61
44
69
52
67
50
63
46
55
38
73
56
22.1
61
44
60
43
63
46
61
44
69
52
67
50
63
46
55
38
73
56
24.1
64
47
62
45
66
49
64
47
72
55
70
53
66
49
57
40
76
59
27.1
65
48
64
47
68
51
66
49
74
57
72
55
68
51
59
42
78
61
31.1
67
50
66
49
69
52
68
51
76
59
74
57
70
53
60
43
80
63
35.1
68
50
67
49
70
52
69
51
77
59
75
57
71
53
61
43
81
63
36.2
66
48
64
46
68
50
66
48
74
56
72
54
68
50
59
41
78
60
38.2
64
46
62
44
66
48
64
46
72
54
70
52
66
48
58
40
76
58
41.2
63
45
62
44
65
47
63
45
71
53
69
51
65
47
57
39
75
57
42.1
73
55
71
53
75
57
73
55
82
64
80
62
75
57
65
47
86
68
45.2
64
46
62
44
66
48
64
46
72
54
70
52
66
48
58
40
76
58
46.2
64
46
62
44
66
48
64
46
72
54
70
52
66
48
57
39
76
58
58
49.2
64
46
62
44
66
48
64
46
72
54
70
52
66
48
57
39
76
53.2
63
45
62
44
65
47
63
45
71
53
69
51
65
47
57
39
75
57
57.2
67
49
66
48
70
52
68
50
76
58
74
56
70
52
61
43
80
62
62.2
68
50
67
49
71
53
69
51
77
59
75
57
71
53
61
43
81
63
65.2
67
49
66
47
70
51
68
50
76
58
74
55
70
51
61
42
80
61
69.2
71
52
69
51
73
55
72
53
80
62
78
59
73
55
64
45
84
65
72.2
72
53
70
52
74
56
73
54
81
63
79
60
74
56
64
46
85
66
76.2
72
53
70
52
74
56
73
54
81
63
79
60
74
56
65
46
85
66
78.2
73
54
71
52
75
56
74
55
82
63
80
61
75
56
65
46
86
67
83.2
75
56
73
54
77
58
75
56
84
65
82
63
77
58
67
48
88
69
88.2
75
56
74
55
78
59
76
57
86
67
83
64
78
59
68
49
89
70
95.2
75
56
74
55
78
59
76
57
86
67
83
64
78
59
68
49
89
70
100.2
75
56
74
55
78
59
76
57
86
67
83
64
78
59
68
49
89
70
105.2
76
57
75
56
79
60
77
58
87
68
84
65
79
60
68
49
90
71
110.2
76
56
75
55
79
59
77
57
87
67
84
64
79
59
68
48
90
70
117.2
76
56
75
55
79
59
77
57
87
67
84
64
79
59
68
48
90
70
124.2
77
57
75
55
80
60
78
58
88
68
85
65
80
60
69
49
91
71
130.3
77
57
76
56
80
60
78
58
88
68
85
65
80
60
69
49
91
71
137.3
77
57
76
56
80
60
78
58
88
68
85
65
80
60
69
49
91
71
143.3
77
57
76
56
80
60
78
58
88
68
85
65
80
60
69
49
91
71
147.3
77
57
76
56
80
60
78
58
88
68
85
65
80
60
69
49
91
71
153.3
77
57
76
56
80
60
78
58
88
68
85
65
80
60
69
49
91
71
Lw:noise power levels measured in free field according to standard ISO 3744.
Lp: sound pressure levels measured at 1 metres from the unit in free field under nominal working conditions, according to ISO 3744
Data acquired with unit operating at the following conditions: A 35°C; W12/7°C
32
Swegon reserves the right to alter specifications.
www.swegon.com
COBALT W
DIMENSIONAL DATA
COBALT W 18.1-22.1
Sc
Ep
*
Es
"B"
Cin
259
"A"
(*) 36
680
900
1000
954 (*)
Lh
936
1300
1700
3406
200
770
220
18 (*)
1000
1000
1370
1000
200
259
259
Cout
220
680
900
VISTA DA "A" / VIEW FROM "A"
513
1500
358
513
2526
Uout
523
VISTA DA "B" / VIEV FROM "B"
(*) CON CUFFIA INSONORIZZANTE
WITH SOUNDROOF CASING
Uin
Lh
FORI DI SOLLEVAMENTO
LIFTING HOLES
Ep
QUADRO ELETTRICO
ELECTRICAL PANEL
Cin
INGR. ACQUA CONDENSAZIONE
CONDENSING WATER INLET
G 4"
Es
INGRESSO ALIMENTAZIONE ELETTRICA
ELECTRICAL SUPPLY INLET
Cout
USCITA ACQUA CONDENSAZIONE
CONDENSING WATER OUTLET
G 4"
Sc
CUFFIA INSONORIZZANTE
SOUNDPROOF CASING
Uin
INGRESSO ACQUA UTILIZZO
USER WATER INLET
OD 88.9
SPAZI DI INSTALLAZIONE
CLEARANCES
Uout
USCITA ACQUA UTILIZZO
USER WATER OUTLET
OD 88.9
Denominazione-Denomination
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
OMEGA V ECHOS
18.1-22.1
*
OPTIONAL
Codice-Code
Disegno-Drawing
Rev.
-
A4C237
A
A4C237A
Swegon reserves the right to alter specifications.
www.swegon.com
33
COBALT W
COBALT W 18.1-22.1
40
Fh
820
G2
IMPRONTA A TERRA / FOOTPRINT
100
G3
1500
100
40
G4
900
G1
1700
MODELLO
MODEL
OMEGA V ECHOS 18.1
OMEGA V ECHOS 18.1 LN
OMEGA V ECHOS 20.1
OMEGA V ECHOS 20.1 LN
OMEGA V ECHOS 22.1
OMEGA V ECHOS 22.1 LN
Fh
G..
FORI DI FISSAGGIO
FIXING HOLES
PESO (kg) PESO IN FUNZIONE (kg)
G1 (kg) G2 (kg) G3 (kg) G4 (kg)
WEIGHT(kg) OPERATING WEIGHT (kg)
1152
1224
268
388
336
232
1351
1423
275
483
424
241
1244
1318
278
433
370
237
1445
1519
285
529
458
247
1223
1297
276
422
362
237
1423
1497
283
517
450
247
Ø22
PUNTI DI APPOGGIO ANTIVIBRANTI
VIBRATION DAMPER FOOT HOLDS
Denominazione-Denomination
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
OMEGA V ECHOS
18.1-22.1
Codice-Code
Disegno-Drawing
Rev.
-
A4C237
A
A4C237A
34
Swegon reserves the right to alter specifications.
www.swegon.com
COBALT W
COBALT W /LC 18.1-22.1
Sc
Ep
*
Es
"A"
Rl
"B"
Lh
200
1000
545
200
1400
1000
140 (*)
1000
543
1200
1000
1340 (*)
1000
1374 (*)
1245
2490
Rd
1200
293
VISTA DA "A" / VIEW TO "A"
168
1200
1536
475
(*) CON CUFFIA INSONORIZZANTE
WITH SOUNDPROOF CASING
168
477
Uin
Uout
VISTA DA "B" / VIEW TO "B"
Lh
FORI DI SOLLEVAMENTO
LIFTING HOLES
Ep
QUADRO ELETTRICO
ELECTRICAL PANEL
Rl
CONNESSIONI REFRIGERANTE (LIQUIDO)
REFRIGERANT CONNECTIONS (LIQUID)
Es
INGRESSO ALIMENTAZIONE ELETTRICA
ELECTRICAL SUPPLY INLET
Rd
CONNESSIONI REFRIGERANTE (MANDATA)
REFRIGERANT CONNECTIONS (DISCHARGE)
Sc
CUFFIA INSONORIZZANTE
SOUNDPROOF CASING
Uin
INGRESSO ACQUA UTILIZZO
USER WATER INLET
OD 114.3
SPAZI DI INSTALLAZIONE
CLEARANCES
Uout
USCITA ACQUA UTILIZZO
USER WATER OUTLET
OD 114.3
/
/
/
Rev. Data-Date
Dis.-Draftsman
Denominazione-Denomination
/
Visto-Checked by
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
A4C423A
Scala-Scale
1:35
Data-Date
21/10/09
Sost. il dis.-Replace draw.
/
Materiale-Material
/
Spessore-Thickness
/
/
Descrizione revisione-Revision description
Codice-Code
OMEGA V ECHOS LC
18.1-22.1
Dis.-Draftsman
A.Greguoldo
Visto-Checked by
G.Morosin
Sost. dal dis.-Replaced by draw.
/
Trattamento-Treatment
/
/
Swegon reserves the right to alter specifications.
Foglio
di 2
N. 1
Sheet
of
Peso-Weight [kg]
-
Colore vernice-Painted colour
/
*
OPTIONAL
Disegno-Drawing
Rev.
A4C423
A
- Proprietà riservata, riproduzione vietata a termini di
legge.Copyright.
- Reserved property, reproduction prohibited accordin to
existent laws.Copyright.
MTE 56 rev. 03 date: 22/02/08
www.swegon.com
35
COBALT W
COBALT W /LC 18.1-22.1
40
Fh
IMPRONTA A TERRA /
FOOTPRINT
G4
1200
1120
G2
G1
40
G3
100
MODELLO
MODEL
OMEGA V ECHOS 18.1 LC
OMEGA V ECHOS 18.1 LC LN
OMEGA V ECHOS 20.1 LC
OMEGA V ECHOS 20.1 LC LN
OMEGA V ECHOS 22.1 LC
OMEGA V ECHOS 22.1 LC LN
Fh
G..
100
PESO (kg) PESO IN FUNZIONE (kg)
WEIGHT(kg) OPERATING WEIGHT (kg)
1190
1190
1389
1389
1278
1278
1477
1477
1256
1256
1456
1456
FORI DI FISSAGGIO
FIXING HOLES
G1 (kg)
G2 (kg)
G3 (kg)
G4 (kg)
346
425
375
455
368
448
330
397
358
424
351
418
251
274
266
289
262
285
263
293
279
309
275
305
Ø22
PUNTI DI APPOGGIO ANTIVIBRANTI
VIBRATION DAMPER FOOT HOLDS
/
/
/
Rev. Data-Date
Dis.-Draftsman
Denominazione-Denomination
/
Visto-Checked by
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
Scala-Scale
1:35
Sost. il dis.-Replace draw.
A4C423A
Data-Date
21/10/09
/
Materiale-Material
/
36
1200
1400
Spessore-Thickness
/
/
Descrizione revisione-Revision description
Codice-Code
OMEGA V ECHOS LC
18.1-22.1
Dis.-Draftsman
A.Greguoldo
Visto-Checked by
G.Morosin
Sost. dal dis.-Replaced by draw.
/
Trattamento-Treatment
/
/
Foglio
di 2
N. 2
Sheet
of
Peso-Weight [kg]
-
Colore vernice-Painted colour
/
Swegon reserves the right to alter specifications.
Disegno-Drawing
Rev.
A4C423
A
- Proprietà riservata, riproduzione vietata a termini di
legge.Copyright.
- Reserved property, reproduction prohibited accordin to
existent laws.Copyright.
MTE 56 rev. 03 date: 22/02/08
www.swegon.com
COBALT W
COBALT W 24.1-31.1
Ep
Sc
"B"
150
"A"
Es
*
Cout
218
Cin
Lh
200
557
200
960
1200
(*) 140
486
474,9
1000
240
1000
1340 (*)
1460
1000
995
1395
2438
1200
293
VISTA DA "A" / VIEW FROM "A"
170,5
416
1195
1536
Uin
170,5
486
(*) CON CUFFIA INSONORIZZANTE
WITH SOUNDPROOF CASING
Uout
VISTA DA "B" / VIEW FROM "B"
Lh
FORI DI SOLLEVAMENTO
LIFTING HOLES
Ep
QUADRO ELETTRICO
ELECTRICAL PANEL
Cin
INGR. ACQUA CONDENSAZIONE
CONDENSING WATER INLET
G 4"
Es
INGRESSO ALIMENTAZIONE ELETTRICA
ELECTRICAL SUPPLY INLET
Cout
USCITA ACQUA CONDENSAZIONE
CONDENSING WATER OUTLET
G 4"
Sc
CUFFIA INSONORIZZANTE
SOUNDPROOF CASING
Uin
INGRESSO ACQUA UTILIZZO
USER WATER INLET
OD 114.3
SPAZI DI INSTALLAZIONE
CLEARANCES
Uout
USCITA ACQUA UTILIZZO
USER WATER OUTLET
OD 114.3
Denominazione-Denomination
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
OMEGA V ECHOS
24.1-31.1
*
OPTIONAL
Codice-Code
Disegno-Drawing
Rev.
-
A4C358
A
A4C358A
Swegon reserves the right to alter specifications.
www.swegon.com
37
COBALT W
COBALT W 24.1-31.1
40
Fh
G1
G2
G3
40
G4
1120
1200
IMPRONTA A TERRA /
FOOTPRINT
100
1195
100
1395
MODELLO
MODEL
PESO (kg)
WEIGHT(kg)
PESO IN FUNZIONE (kg)
OPERATING WEIGHT (kg)
1373
1573
1498
1697
1570
1771
1471
1671
1596
1795
1669
1870
OMEGA V ECHOS 24.1
OMEGA V ECHOS 24.1 LN
OMEGA V ECHOS 27.1
OMEGA V ECHOS 27.1 LN
OMEGA V ECHOS 31.1
OMEGA V ECHOS 31.1 LN
Fh
G..
FORI DI FISSAGGIO
FIXING HOLES
G1 (kg) G2 (kg) G3 (kg) G4 (kg)
481
591
535
646
567
678
296
332
321
356
335
371
264
269
277
282
285
290
430
479
463
511
482
531
Ø22
PUNTI DI APPOGGIO ANTIVIBRANTI
VIBRATION DAMPER FOOT HOLDS
Denominazione-Denomination
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
OMEGA V ECHOS
24.1-31.1
Codice-Code
Disegno-Drawing
Rev.
-
A4C358
A
A4C358A
38
Swegon reserves the right to alter specifications.
www.swegon.com
COBALT W
COBALT W /LC 24.1-31.1
Sc
Ep
*
Es
"A"
Rl
"B"
Lh
1000
1400
2548
543
605
1200
1340 (*)
1000
1000
1374 (*)
1000
(*) 140
1000
200
1314
200
1200
Rd
293
VISTA DA "A" / VIEW FROM "A"
168
538
1200
1536
(*) CON CUFFIA INSONORIZZANTE
WITH SOUNDPROOF CASING
168
475
Uin
Uout
VISTA DA "B" / VIEW FROM "B"
Lh
FORI DI SOLLEVAMENTO
LIFTING HOLES
Ep
QUADRO ELETTRICO
ELECTRICAL PANEL
Rd
CONNESSIONI REFRIGERANTE (MANDATA)
REFRIGERANT CONNECTIONS (DISCHARGE)
Es
INGRESSO ALIMENTAZIONE ELETTRICA
ELECTRICAL SUPPLY INLET
Rl
CONNESSIONI REFRIGERANTE (LIQUIDO)
REFRIGERANT CONNECTIONS (LIQUID)
Sc
CUFFIA INSONORIZZANTE
SOUNDPROOF CASING
Uin
INGRESSO ACQUA UTILIZZO
USER WATER INLET
OD 114.3
SPAZI DI INSTALLAZIONE
CLEARANCES
Uout
USCITA ACQUA UTILIZZO
USER WATER OUTLET
OD 114.3
/
/
/
Rev. Data-Date
Dis.-Draftsman
Denominazione-Denomination
/
Visto-Checked by
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
Scala-Scale
1:35
Sost. il dis.-Replace draw.
A49454A
Data-Date
07/09/09
/
Materiale-Material
/
Spessore-Thickness
/
/
Descrizione revisione-Revision description
Codice-Code
OMEGA V ECHOS LC
24.1-31.1
Dis.-Draftsman
A.Greguoldo
Visto-Checked by
G.Morosin
Sost. dal dis.-Replaced by draw.
/
Trattamento-Treatment
/
/
Swegon reserves the right to alter specifications.
-
*
OPTIONAL
Disegno-Drawing
Rev.
A4C424
A
Foglio
di 2
N. 1
Sheet
of
Peso-Weight [kg]
-
Colore vernice-Painted colour
/
- Proprietà riservata, riproduzione vietata a termini di
legge.Copyright.
- Reserved property, reproduction prohibited accordin to
existent laws.Copyright.
MTE 56 rev. 03 date: 22/02/08
www.swegon.com
39
COBALT W
COBALT W /LC 24.1-31.1
40
Fh
G1
G2
G3
40
G4
1120
1200
IMPRONTA A TERRA /
FOOTPRINT
100
1200
100
1400
MODELLO
MODEL
OMEGA V ECHOS 24.1 LC
OMEGA V ECHOS 24.1 LC LN
OMEGA V ECHOS 27.1 LC
OMEGA V ECHOS 27.1 LC LN
OMEGA V ECHOS 31.1 LC
OMEGA V ECHOS 31.1 LC LN
Fh
G..
FORI DI FISSAGGIO
FIXING HOLES
Ø22
PUNTI DI APPOGGIO ANTIVIBRANTI
VIBRATION DAMPER FOOT HOLDS
/
/
/
Rev. Data-Date
Dis.-Draftsman
Denominazione-Denomination
/
Visto-Checked by
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
Scala-Scale
1:35
Sost. il dis.-Replace draw.
A4C424A
Data-Date
07/09/09
/
Materiale-Material
/
40
PESO (kg) PESO IN FUNZIONE (kg)
G1 (kg) G2 (kg) G3 (kg) G4 (kg)
WEIGHT(kg) OPERATING WEIGHT (kg)
1222
1296
381
364
269
282
1422
1496
461
431
292
312
1345
1417
423
401
289
304
1545
1617
502
468
312
335
1415
1487
447
423
300
317
1615
1687
526
490
324
347
Spessore-Thickness
/
/
Descrizione revisione-Revision description
Codice-Code
OMEGA V ECHOS LC
24.1-31.1
Dis.-Draftsman
A.Greguoldo
Visto-Checked by
G.Morosin
Sost. dal dis.-Replaced by draw.
/
Trattamento-Treatment
/
/
-
Rev.
A4C424
A
Foglio
di 2
N. 2
Sheet
of
Peso-Weight [kg]
-
Colore vernice-Painted colour
/
Swegon reserves the right to alter specifications.
Disegno-Drawing
- Proprietà riservata, riproduzione vietata a termini di
legge.Copyright.
- Reserved property, reproduction prohibited accordin to
existent laws.Copyright.
MTE 56 rev. 03 date: 22/02/08
www.swegon.com
COBALT W
COBALT W 35.1
Sc
Ep
*
Es
"B"
Cin
259
"A"
200
800
1300
200
1700
1000
1000
3426
980
1200
1250
50
220
1000
Cout
259
1464 (*)
1390
436,2
926
220
980
1200
293
VISTA DA "A" / VIEW FROM "A"
Lh
493
532
Uin
1500
2486
493
408
VISTA DA "B" / VIEW FROM "B"
(*) CON CUFFIA INSONORIZZANTE
WITH SOUNDPROOF CASING
Uout
Lh
FORI DI SOLLEVAMENTO
LIFTING HOLES
Ep
QUADRO ELETTRICO
ELECTRICAL PANEL
Cin
INGR. ACQUA CONDENSAZIONE
CONDENSING WATER INLET
G 5"
Es
INGRESSO ALIMENTAZIONE ELETTRICA
ELECTRICAL SUPPLY INLET
Cout
USCITA ACQUA CONDENSAZIONE
CONDENSING WATER OUTLET
G 5"
Sc
CUFFIA INSONORIZZANTE
SOUNDPROOF CASING
Uin
INGRESSO ACQUA UTILIZZO
USER WATER INLET
OD 114.3
SPAZI DI INSTALLAZIONE
CLEARANCES
Uout
USCITA ACQUA UTILIZZO
USER WATER OUTLET
OD 114.3
Denominazione-Denomination
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
OMEGA V ECHOS
35.1
*
OPTIONAL
Codice-Code
Disegno-Drawing
Rev.
-
A4C365
A
A4C365A
Swegon reserves the right to alter specifications.
www.swegon.com
41
COBALT W
COBALT W 35.1
40
Fh
G1
G2
G4
1120
1200
IMPRONTA A TERRA /
FOOTPRINT
40
G3
100
1500
100
1700
MODELLO
MODEL
OMEGA V ECHOS 35.1
OMEGA V ECHOS 35.1 LN
Fh
G..
FORI DI FISSAGGIO
FIXING HOLES
PESO (kg)
PESO IN FUNZIONE (kg)
G1 (kg) G2 (kg) G3 (kg) G4 (kg)
WEIGHT(kg) OPERATING WEIGHT (kg)
1509
1648
497
408
335
408
1769
1908
600
500
367
441
Ø22
PUNTI DI APPOGGIO ANTIVIBRANTI
VIBRATION DAMPER FOOT HOLDS
Denominazione-Denomination
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
OMEGA V ECHOS
35.1
Codice-Code
Disegno-Drawing
Rev.
-
A4C365
A
A4C365A
42
Swegon reserves the right to alter specifications.
www.swegon.com
COBALT W
COBALT W 42.1
Sc
Ep
*
Es
"B"
Cin
290
"A"
200
1300
1700
898
1000
200
926
1000
3524
980
1200
1253
53
(*) 96
1000
220
1000
Cout
290
1464 (*)
1412
1350 (*)
220
980
1200
293
VISTA DA "A" / VIEV FROM "A"
Lh
493
532
1500
(*) CON CUFFIA INSONORIZZANTE
WITH SOUNDROOF CASING
493
2486
Uin
505
VISTA DA "B" / VIEW FROM "B" Uout
Lh
FORI DI SOLLEVAMENTO
LIFTING HOLES
Ep
QUADRO ELETTRICO
ELECTRICAL PANEL
Cin
INGR. ACQUA CONDENSAZIONE
CONDENSING WATER INLET
G 5"
Es
INGRESSO ALIMENTAZIONE ELETTRICA
ELECTRICAL SUPPLY INLET
Cout
USCITA ACQUA CONDENSAZIONE
CONDENSING WATER OUTLET
G 5"
Sc
CUFFIA INSONORIZZANTE
SOUNDPROOF CASING
Uin
INGRESSO ACQUA UTILIZZO
USER WATER INLET
OD 114.3
Uout
USCITA ACQUA UTILIZZO
USER WATER OUTLET
OD 114.3
SPAZI DI INSTALLAZIONE
CLEARANCES
Denominazione-Denomination
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
OMEGA V ECHOS
42.1
*
OPTIONAL
Codice-Code
Disegno-Drawing
Rev.
-
A4C325
A
A4C325A
Swegon reserves the right to alter specifications.
www.swegon.com
43
COBALT W
COBALT W 42.1
40
Fh
G1
G2
G4
1120
1200
IMPRONTA A TERRA /
FOOTPRINT
40
G3
100
1500
100
1700
MODELLO
MODEL
OMEGA V ECHOS 42.1
OMEGA V ECHOS 42.1 LN
Fh
G..
FORI DI FISSAGGIO
FIXING HOLES
PESO (kg) PESO IN FUNZIONE (kg)
G1 (kg) G2 (kg) G3 (kg) G4 (kg)
WEIGHT(kg) OPERATING WEIGHT (kg)
1631
1779
518
430
377
454
1891
2039
621
522
409
487
Ø22
PUNTI DI APPOGGIO ANTIVIBRANTI
VIBRATION DAMPER FOOT HOLDS
Denominazione-Denomination
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
OMEGA V ECHOS
42.1
Codice-Code
Disegno-Drawing
Rev.
-
A4C325
A
A4C325A
44
Swegon reserves the right to alter specifications.
www.swegon.com
COBALT W
COBALT W /LC 35.1-42.1
Sc
Ep
*
Es
200
1000
1400
3500
1040
"B"
40
100 (*)
1000
200
1060
1000
1464 (*)
1000
"A"
1200
1240
1000
1340 (*)
1370
Rl
Rd
1200
293
VISTA DA "A" / VIEW FROM "A"
(*) CON CUFFIA INSONORIZZANTE
WITH SOUNDPROOF CASING
Lh
643
1200
2486
516
Uin
643
501
VISTA DA "B" / VIEW FROM "B"
Uout
Lh
FORI DI SOLLEVAMENTO
LIFTING HOLES
Ep
QUADRO ELETTRICO
ELECTRICAL PANEL
Rd
CONNESSIONI REFRIGERANTE (MANDATA)
REFRIGERANT CONNECTIONS (DISCHARGE)
Es
INGRESSO ALIMENTAZIONE ELETTRICA
ELECTRICAL SUPPLY INLET
Rl
CONNESSIONI REFRIGERANTE (LIQUIDO)
REFRIGERANT CONNECTIONS (LIQUID)
Sc
CUFFIA INSONORIZZANTE
SOUNDPROOF CASING
Uin
INGRESSO ACQUA UTILIZZO
USER WATER INLET
OD 114.3
SPAZI DI INSTALLAZIONE
CLEARANCES
Uout
USCITA ACQUA UTILIZZO
USER WATER OUTLET
OD 114.3
/
/
/
Rev. Data-Date
Dis.-Draftsman
Denominazione-Denomination
/
Visto-Checked by
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
Scala-Scale
1:40
Sost. il dis.-Replace draw.
A4C425A
Data-Date
08/09/09
/
Materiale-Material
/
Spessore-Thickness
/
/
Descrizione revisione-Revision description
Codice-Code
OMEGA V ECHOS LC
35.1-42.1
Dis.-Draftsman
A.Greguoldo
Visto-Checked by
G.Morosin
Sost. dal dis.-Replaced by draw.
/
Trattamento-Treatment
/
/
-
OPTIONAL
Disegno-Drawing
Rev.
A4C425
A
Foglio
di 2
N. 1
Sheet
of
Peso-Weight [kg]
-
Colore vernice-Painted colour
/
Swegon reserves the right to alter specifications.
*
- Proprietà riservata, riproduzione vietata a termini di
legge.Copyright.
- Reserved property, reproduction prohibited accordin to
existent laws.Copyright.
MTE 56 rev. 03 date: 22/02/08
www.swegon.com
45
COBALT W
COBALT W /LC 35.1-42.1
40
Fh
G1
G2
G3
40
G4
1120
1200
IMPRONTA A TERRA /
FOOTPRINT
100
1200
100
1400
MODELLO
MODEL
PESO (kg) PESO IN FUNZIONE (kg)
G1 (kg) G2 (kg) G3 (kg) G4 (kg)
WEIGHT(kg) OPERATING WEIGHT (kg)
OMEGA V ECHOS 35.1 LC
OMEGA V ECHOS 35.1 LC LN
OMEGA V ECHOS 42.1 LC
OMEGA V ECHOS 42.1 LC LN
Fh
G..
FORI DI FISSAGGIO
FIXING HOLES
1471
1731
1516
1775
450
552
465
567
427
520
441
534
289
320
297
327
305
339
313
347
Ø22
PUNTI DI APPOGGIO ANTIVIBRANTI
VIBRATION DAMPER FOOT HOLDS
/
/
/
Rev. Data-Date
Dis.-Draftsman
Denominazione-Denomination
/
Visto-Checked by
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
Scala-Scale
1:40
Sost. il dis.-Replace draw.
A4C425A
Data-Date
08/09/09
/
Materiale-Material
/
46
1358
1618
1403
1662
Spessore-Thickness
/
/
Descrizione revisione-Revision description
Codice-Code
OMEGA V ECHOS LC
35.1-42.1
Dis.-Draftsman
A.Greguoldo
Visto-Checked by
G.Morosin
Sost. dal dis.-Replaced by draw.
/
Trattamento-Treatment
/
/
-
Rev.
A4C425
A
Foglio
di 2
N. 2
Sheet
of
Peso-Weight [kg]
-
Colore vernice-Painted colour
/
Swegon reserves the right to alter specifications.
Disegno-Drawing
- Proprietà riservata, riproduzione vietata a termini di
legge.Copyright.
- Reserved property, reproduction prohibited accordin to
existent laws.Copyright.
MTE 56 rev. 03 date: 22/02/08
www.swegon.com
COBALT W
COBALT W 36.2-45.2
*
"A
"B"
259
Cin
Es
220
200
1210 (**)
960
438
(*) 130
1000
1000
1000
1380 (*)
259
Cout
592
1250
259
1550
1950
3628
3878 (**)
1710 (*)
1000
718
1580
200
Cin
259
Sc
Ep
592
438
Cout
220
1250
626
VISTA DA "A" / VIEW FROM "A"
Lh
368
942 (**)
692
Uin
1750
2486
368
450
VISTA DA "B" / VIEW FROM "B"
Uout
(*) CON CUFFIA INSONORIZZANTE
WITH SOUNDPROOF CASING
(**) CON RUBINETTO IN ASPIRAZIONE
WITH SUCTION SHUT-OFF VALVE
Lh
FORI DI SOLLEVAMENTO
LIFTING HOLES
Ep
QUADRO ELETTRICO
ELECTRICAL PANEL
Cin
INGR. ACQUA CONDENSAZIONE
CONDENSING WATER INLET
G 4"
Es
INGRESSO ALIMENTAZIONE ELETTRICA
ELECTRICAL SUPPLY INLET
Cout
USCITA ACQUA CONDENSAZIONE
CONDENSING WATER OUTLET
G 4"
Sc
CUFFIA INSONORIZZANTE
SOUNDPROOF CASING
Uin
INGRESSO ACQUA UTILIZZO
USER WATER INLET
OD 114.3
SPAZI DI INSTALLAZIONE
CLEARANCES
Uout
USCITA ACQUA UTILIZZO
USER WATER OUTLET
OD 114.3
Denominazione-Denomination
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
OMEGA V ECHOS
36.2-45.2
*
OPTIONAL
Codice-Code
Disegno-Drawing
Rev.
-
A4C314
A
A4C314A
Swegon reserves the right to alter specifications.
www.swegon.com
47
COBALT W
COBALT W 36.2-45.2
40
Fh
G1
G2
1250
1170
IMPRONTA A TERRA /
FOOTPRINT
G3
40
G4
MODELLO
MODEL
OMEGA V ECHOS 36.2
OMEGA V ECHOS 36.2 LN
OMEGA V ECHOS 38.2
OMEGA V ECHOS 38.2 LN
OMEGA V ECHOS 41.2
OMEGA V ECHOS 41.2 LN
OMEGA V ECHOS 45.2
OMEGA V ECHOS 45.2 LN
Fh
G..
FORI DI FISSAGGIO
FIXING HOLES
100
1750
1950
100
PESO (kg) PESO IN FUNZIONE (kg)
G1 (kg) G2 (kg) G3 (kg) G4 (kg)
WEIGHT(kg) OPERATING WEIGHT (kg)
1954
2097
594
677
440
386
2304
2447
721
807
485
434
2051
2192
598
737
473
384
2400
2541
725
867
517
432
2142
2285
648
746
477
414
2493
2636
776
876
522
462
2100
2243
636
731
468
408
2451
2594
764
861
513
456
Ø22
PUNTI DI APPOGGIO ANTIVIBRANTI
VIBRATION DAMPER FOOT HOLDS
Denominazione-Denomination
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
OMEGA V ECHOS
36.2-45.2
Codice-Code
Disegno-Drawing
Rev.
-
A4C314
A
A4C314A
48
Swegon reserves the right to alter specifications.
www.swegon.com
COBALT W
COBALT W /LC 36.2-45.2
Sc
Ep
*
"A"
"B"
Rl
Es
678
(*) 130
200
1210 (**)
960
Rd
VISTA DA "A" / VIEW FROM "A"
1750
2486
(*) CON CUFFIA INSONORIZZANTE
WITH SOUNDPROOF CASING
(**) CON RUBINETTO IN ASPIRAZIONE
WITH SUCTION SHUT-OFF VALVE
368
410
VISTA DA "B" / VIEW FROM "B"
Uin
Uout
Lh
FORI DI SOLLEVAMENTO
LIFTING HOLES
Ep
QUADRO ELETTRICO
ELECTRICAL PANEL
Rd
CONNESSIONI REFRIGERANTE (MANDATA)
REFRIGERANT CONNECTIONS (DISCHARGE)
Es
INGRESSO ALIMENTAZIONE ELETTRICA
ELECTRICAL SUPPLY INLET
Rl
CONNESSIONI REFRIGERANTE (LIQUIDO)
REFRIGERANT CONNECTIONS (LIQUID)
Sc
CUFFIA INSONORIZZANTE
SOUNDPROOF CASING
Uin
INGRESSO ACQUA UTILIZZO
USER WATER INLET
OD 114.3
SPAZI DI INSTALLAZIONE
CLEARANCES
Uout
USCITA ACQUA UTILIZZO
USER WATER OUTLET
OD 114.3
/
/
/
Rev. Data-Date
Dis.-Draftsman
Denominazione-Denomination
/
Visto-Checked by
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
A4C426A
Scala-Scale
1:40
Data-Date
09/09/09
Sost. il dis.-Replace draw.
/
Materiale-Material
/
Spessore-Thickness
/
1000
1250
Rd
293
368
1380 (*)
1000
Lh
942 (**)
692
1250
1000
1370 (*)
1000
1550
1950
3588
3877 (**)
1250
200
/
Descrizione revisione-Revision description
Codice-Code
OMEGA V ECHOS LC
36.2-45.2
Dis.-Draftsman
A.Greguoldo
Visto-Checked by
G.Morosin
Sost. dal dis.-Replaced by draw.
/
Trattamento-Treatment
/
/
Swegon reserves the right to alter specifications.
-
*
OPTIONAL
Disegno-Drawing
Rev.
A4C426
A
Foglio
di 2
N. 1
Sheet
of
Peso-Weight [kg]
-
Colore vernice-Painted colour
/
- Proprietà riservata, riproduzione vietata a termini di
legge.Copyright.
- Reserved property, reproduction prohibited accordin to
existent laws.Copyright.
MTE 56 rev. 03 date: 22/02/08
www.swegon.com
49
COBALT W
COBALT W /LC 36.2-45.2
40
Fh
G1
G2
1250
1170
IMPRONTA A TERRA /
FOOTPRINT
G3
40
G4
100
MODELLO
MODEL
G..
FORI DI FISSAGGIO
FIXING HOLES
1696
2045
1787
2137
1873
2222
1830
2180
1809
2158
1895
2245
1981
2330
1938
2288
503
630
504
630
552
679
540
667
578
708
634
765
642
772
626
756
389
434
422
466
423
468
415
460
339
386
335
384
364
411
357
405
Ø22
PUNTI DI APPOGGIO ANTIVIBRANTI
VIBRATION DAMPER FOOT HOLDS
/
/
/
Rev. Data-Date
Dis.-Draftsman
Denominazione-Denomination
/
Visto-Checked by
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
Scala-Scale
1:40
Sost. il dis.-Replace draw.
A4C426A
Data-Date
09/09/09
/
Materiale-Material
/
50
100
PESO (kg) PESO IN FUNZIONE (kg)
G1 (kg) G2 (kg) G3 (kg) G4 (kg)
WEIGHT(kg) OPERATING WEIGHT (kg)
OMEGA V ECHOS 36.2 LC
OMEGA V ECHOS 36.2 LC LN
OMEGA V ECHOS 38.2 LC
OMEGA V ECHOS 38.2 LC LN
OMEGA V ECHOS 41.2 LC
OMEGA V ECHOS 41.2 LC LN
OMEGA V ECHOS 45.2 LC
OMEGA V ECHOS 45.2 LC LN
Fh
1750
1950
Spessore-Thickness
/
/
Descrizione revisione-Revision description
Codice-Code
OMEGA V ECHOS LC
36.2-45.2
Dis.-Draftsman
A.Greguoldo
Visto-Checked by
G.Morosin
Sost. dal dis.-Replaced by draw.
/
Trattamento-Treatment
/
/
-
Rev.
A4C426
A
Foglio
di 2
N. 2
Sheet
of
Peso-Weight [kg]
-
Colore vernice-Painted colour
/
Swegon reserves the right to alter specifications.
Disegno-Drawing
- Proprietà riservata, riproduzione vietata a termini di
legge.Copyright.
- Reserved property, reproduction prohibited accordin to
existent laws.Copyright.
MTE 56 rev. 03 date: 22/02/08
www.swegon.com
COBALT W
COBALT W 46.2-62.2
*
"A"
"B"
259
Cin
Es
200
1550
1950
3638
3878 (**)
200
220
1210 (**)
970
(*) 130
1000
1000
438
592
1250
1000
1380 (*)
259
Cout
259
1745 (*)
1684
1000
718
Cin
259
Sc
Ep
592
438
Cout
220
1250
645
VISTA DA "A" / VIEW FROM "A"
Lh
960 (**)
720
350
Uin
1750
2450
350
468
VISTA DA "B" / VIEW FROM "B"
Lh
FORI DI SOLLEVAMENTO
LIFTING HOLES
Ep
QUADRO ELETTRICO
ELECTRICAL PANEL
Uout
(*) CON CUFFIA INSONORIZZANTE
WITH SOUNDPROOF CASING
(**) CON RUBINETTO IN ASPIRAZIONE
WITH SUCTION SHUT-OFF VALVE
Cin
INGR. ACQUA CONDENSAZIONE
CONDENSING WATER INLET
G 4"
Es
INGRESSO ALIMENTAZIONE ELETTRICA
ELECTRICAL SUPPLY INLET
Cout
USCITA ACQUA CONDENSAZIONE
CONDENSING WATER OUTLET
G 4"
Sc
CUFFIA INSONORIZZANTE
SOUNDPROOF CASING
Uin
INGRESSO ACQUA UTILIZZO
USER WATER INLET
OD 139.7
SPAZI DI INSTALLAZIONE
CLEARANCES
Uout
USCITA ACQUA UTILIZZO
USER WATER OUTLET
OD 139.7
Denominazione-Denomination
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
OMEGA V ECHOS
46.2-62.2
*
OPTIONAL
Codice-Code
Disegno-Drawing
Rev.
-
A4C359
A
A4C359A
Swegon reserves the right to alter specifications.
www.swegon.com
51
COBALT W
COBALT W 46.2-62.2
40
Fh
G1
G2
1250
1170
IMPRONTA A TERRA /
FOOTPRINT
G3
40
G4
MODELLO
MODEL
OMEGA V ECHOS 46.2
OMEGA V ECHOS 46.2 LN
OMEGA V ECHOS 49.2
OMEGA V ECHOS 49.2 LN
OMEGA V ECHOS 53.2
OMEGA V ECHOS 53.2 LN
OMEGA V ECHOS 57.2
OMEGA V ECHOS 57.2 LN
OMEGA V ECHOS 62.2
OMEGA V ECHOS 62.2 LN
Fh
G..
FORI DI FISSAGGIO
FIXING HOLES
100
1750
1950
PESO (kg)
WEIGHT(kg)
2228
2578
2264
2615
2524
2874
2601
2952
2678
3029
100
PESO IN FUNZIONE (kg)
G1 (kg) G2 (kg) G3 (kg) G4 (kg)
OPERATING WEIGHT (kg)
2431
715
771
490
455
2781
843
900
536
502
2469
740
771
489
469
2820
869
900
535
516
2730
823
860
535
512
3080
951
989
581
559
2807
826
909
562
510
3158
954
1039
607
558
2887
873
913
563
538
3238
1001 1043
609
585
Ø22
PUNTI DI APPOGGIO ANTIVIBRANTI
VIBRATION DAMPER FOOT HOLDS
Denominazione-Denomination
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
OMEGA V ECHOS
46.2-62.2
Codice-Code
Disegno-Drawing
Rev.
-
A4C359
A
A4C359A
52
Swegon reserves the right to alter specifications.
www.swegon.com
COBALT W
COBALT W /LC 46.2-62.2
Sc
Ep
*
"A"
"B"
Rl
Es
1550
1950
718
1000
200
(*) 130
1000
1210 (**)
970
1000
1000
1412 (*)
3638
3878 (**)
Rd
1250
1380 (*)
1351
200
Rd
1250
312
VISTA DA "A" / VIEW FROM "A"
(*) CON CUFFIA INSONORIZZANTE
WITH SOUNDPROOF CASING
Lh
350
960 (**)
720
1750
2450
350
VISTA DA "B" / VIEW FROM "B"
Uin
(**) CON RUBINETTO IN ASPIRAZIONE
WITH SUCTION SHUT-OFF VALVE
468
Uout
Lh
FORI DI SOLLEVAMENTO
LIFTING HOLES
Ep
QUADRO ELETTRICO
ELECTRICAL PANEL
Rd
CONNESSIONI REFRIGERANTE (MANDATA)
REFRIGERANT CONNECTIONS (DISCHARGE)
Es
INGRESSO ALIMENTAZIONE ELETTRICA
ELECTRICAL SUPPLY INLET
Rl
CONNESSIONI REFRIGERANTE (LIQUIDO)
REFRIGERANT CONNECTIONS (LIQUID)
Sc
CUFFIA INSONORIZZANTE
SOUNDPROOF CASING
Uin
INGRESSO ACQUA UTILIZZO
USER WATER INLET
OD 139.7
SPAZI DI INSTALLAZIONE
CLEARANCES
Uout
USCITA ACQUA UTILIZZO
USER WATER OUTLET
OD 139.7
/
/
/
Rev. Data-Date
Dis.-Draftsman
Denominazione-Denomination
/
Visto-Checked by
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
Scala-Scale
1:40
Sost. il dis.-Replace draw.
A4C427A
Data-Date
09/09/09
/
Materiale-Material
/
Spessore-Thickness
/
/
Descrizione revisione-Revision description
Codice-Code
OMEGA V ECHOS LC
46.2-62.2
Dis.-Draftsman
A.Greguoldo
Visto-Checked by
G.Morosin
Sost. dal dis.-Replaced by draw.
/
Trattamento-Treatment
/
/
Swegon reserves the right to alter specifications.
-
*
OPTIONAL
Disegno-Drawing
Rev.
A4C427
A
Foglio
di 2
N. 1
Sheet
of
Peso-Weight [kg]
-
Colore vernice-Painted colour
/
- Proprietà riservata, riproduzione vietata a termini di
legge.Copyright.
- Reserved property, reproduction prohibited accordin to
existent laws.Copyright.
MTE 56 rev. 03 date: 22/02/08
www.swegon.com
53
COBALT W
COBALT W /LC 46.2-62.2
40
Fh
G1
G2
1250
1170
IMPRONTA A TERRA /
FOOTPRINT
G3
40
G4
MODELLO
MODEL
OMEGA V ECHOS 46.2 LC
OMEGA V ECHOS 46.2 LC LN
OMEGA V ECHOS 49.2 LC
OMEGA V ECHOS 49.2 LC LN
OMEGA V ECHOS 53.2 LC
OMEGA V ECHOS 53.2 LC LN
OMEGA V ECHOS 57.2 LC
OMEGA V ECHOS 57.2 LC LN
OMEGA V ECHOS 62.2 LC
OMEGA V ECHOS 62.2 LC LN
Fh
G..
FORI DI FISSAGGIO
FIXING HOLES
1750
1950
100
PESO (kg) PESO IN FUNZIONE (kg)
G1 (kg) G2 (kg) G3 (kg) G4 (kg)
WEIGHT(kg) OPERATING WEIGHT (kg)
1953
2118
612
666
438
402
2301
2466
739
795
483
449
1983
2148
635
665
434
414
2333
2498
763
794
480
461
2229
2389
711
747
477
454
2580
2740
839
877
523
501
2301
2458
711
793
503
451
2653
2810
839
923
549
499
2372
2529
755
795
502
477
2721
2878
883
924
548
523
Ø22
PUNTI DI APPOGGIO ANTIVIBRANTI
VIBRATION DAMPER FOOT HOLDS
/
/
/
Rev. Data-Date
Dis.-Draftsman
Denominazione-Denomination
/
Visto-Checked by
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
Scala-Scale
1:40
Sost. il dis.-Replace draw.
A4C427A
Data-Date
09/09/09
/
Materiale-Material
/
54
100
Spessore-Thickness
/
/
Descrizione revisione-Revision description
Codice-Code
OMEGA V ECHOS LC
46.2-62.2
Dis.-Draftsman
A.Greguoldo
Visto-Checked by
G.Morosin
Sost. dal dis.-Replaced by draw.
/
Trattamento-Treatment
/
/
-
Rev.
A4C427
A
Foglio
di 2
N. 2
Sheet
of
Peso-Weight [kg]
-
Colore vernice-Painted colour
/
Swegon reserves the right to alter specifications.
Disegno-Drawing
- Proprietà riservata, riproduzione vietata a termini di
legge.Copyright.
- Reserved property, reproduction prohibited accordin to
existent laws.Copyright.
MTE 56 rev. 03 date: 22/02/08
www.swegon.com
COBALT W
COBALT W 65.2-69.2
*
"A"
"B"
259
Cin
Es
200
200
170
1380 (**)
1200
530
30
100
1000
1000
550
1250
1280
1000
1380 (*)
259
Cout
259
1980 (*)
1900
1000
920
1550
1950
4070
4250 (**)
Cin
259
Sc
Ep
550
530
Cout
170
1250
715
VISTA DA "A" / VIEW FROM "A"
1148 (**)
967
331
Uin
Lh
1750
2412
331
690
VISTA DA "B" / VIEW FROM "B" Uout
Lh
FORI DI SOLLEVAMENTO
LIFTING HOLES
Ep
QUADRO ELETTRICO
ELECTRICAL PANEL
(*) CON CUFFIA INSONORIZZANTE
WITH SOUNDROOF CASING
(**) CON RUBINETTO IN ASPIRAZIONE
WITH SUCTION SHUT-OFF VALVE
Cin
INGR. ACQUA CONDENSAZIONE
CONDENSING WATER INLET
G 4"
Es
INGRESSO ALIMENTAZIONE ELETTRICA
ELECTRICAL SUPPLY INLET
Cout
USCITA ACQUA CONDENSAZIONE
CONDENSING WATER OUTLET
G 4"
Sc
CUFFIA INSONORIZZANTE
SOUNDPROOF CASING
Uin
INGRESSO ACQUA UTILIZZO
USER WATER INLET
OD 168.3
SPAZI DI INSTALLAZIONE
CLEARANCES
Uout
USCITA ACQUA UTILIZZO
USER WATER OUTLET
OD 168.3
Denominazione-Denomination
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
OMEGA V ECHOS
65.2-69.2
*
OPTIONAL
Codice-Code
Disegno-Drawing
Rev.
-
A4C366
A
A4C366A
Swegon reserves the right to alter specifications.
www.swegon.com
55
COBALT W
COBALT W 65.2-69.2
40
Fh
G1
G2
1250
1170
IMPRONTA A TERRA /
FOOTPRINT
G3
40
G4
MODELLO
MODEL
OMEGA V ECHOS 65.2
OMEGA V ECHOS 65.2 LN
OMEGA V ECHOS 69.2
OMEGA V ECHOS 69.2 LN
Fh
G..
FORI DI FISSAGGIO
FIXING HOLES
100
1750
1950
100
PESO (kg)
PESO IN FUNZIONE (kg)
G1 (kg) G2 (kg) G3 (kg) G4 (kg)
WEIGHT(kg) OPERATING WEIGHT (kg)
2816
3138
973
975
596
594
3216
3538
1120 1122
649
647
2775
3097
947
974
596
580
3175
3497
1094 1121
649
633
Ø22
PUNTI DI APPOGGIO ANTIVIBRANTI
VIBRATION DAMPER FOOT HOLDS
Denominazione-Denomination
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
OMEGA V ECHOS
65.2-69.2
Codice-Code
Disegno-Drawing
Rev.
-
A4C366
A
A4C366A
56
Swegon reserves the right to alter specifications.
www.swegon.com
COBALT W
COBALT W /LC 65.2-69.2
Sc
Ep
*
"A"
"B"
Rl
Es
200
850
200
1355 (**)
1170
1000
30
(*) 100
1000
1250
1280
1380 (*)
1000
1652 (*)
1570
1000
1550
1950
3970
4130 (**)
Rd
Rd
1250
382
VISTA DA "A" / VIEW FROM "A"
Lh
1750
2412
331
1099 (**)
939
Uin
331
(*) CON CUFFIA INSONORIZZANTE
WITH SOUNDROOF CASING
(**) CON RUBINETTO IN ASPIRAZIONE
WITH SUCTION SHUT-OFF VALVE
594
VISTA DA "B" / VIEW FROM "B" Uout
Lh
FORI DI SOLLEVAMENTO
LIFTING HOLES
Ep
QUADRO ELETTRICO
ELECTRICAL PANEL
Rd
CONNESSIONI REFRIGERANTE (MANDATA)
REFRIGERANT CONNECTIONS (DISCHARGE)
Es
INGRESSO ALIMENTAZIONE ELETTRICA
ELECTRICAL SUPPLY INLET
Rl
CONNESSIONI REFRIGERANTE (LIQUIDO)
REFRIGERANT CONNECTIONS (LIQUID)
Sc
CUFFIA INSONORIZZANTE
SOUNDPROOF CASING
Uin
INGRESSO ACQUA UTILIZZO
USER WATER INLET
OD 168.3
SPAZI DI INSTALLAZIONE
CLEARANCES
Uout
USCITA ACQUA UTILIZZO
USER WATER OUTLET
OD 168.3
/
/
/
Rev. Data-Date
Dis.-Draftsman
Denominazione-Denomination
/
Visto-Checked by
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
Scala-Scale
1:40
Sost. il dis.-Replace draw.
A4C428A
Data-Date
10/09/09
/
Materiale-Material
/
Spessore-Thickness
/
/
Descrizione revisione-Revision description
Codice-Code
OMEGA V ECHOS LC
65.2-69.2
Dis.-Draftsman
A.Greguoldo
Visto-Checked by
G.Morosin
Sost. dal dis.-Replaced by draw.
/
Trattamento-Treatment
/
/
Swegon reserves the right to alter specifications.
-
*
OPTIONAL
Disegno-Drawing
Rev.
A4C428
A
Foglio
di 2
N. 1
Sheet
of
Peso-Weight [kg]
-
Colore vernice-Painted colour
/
- Proprietà riservata, riproduzione vietata a termini di
legge.Copyright.
- Reserved property, reproduction prohibited accordin to
existent laws.Copyright.
MTE 56 rev. 03 date: 22/02/08
www.swegon.com
57
COBALT W
COBALT W /LC 65.2-69.2
40
Fh
G1
G2
1250
1170
IMPRONTA A TERRA /
FOOTPRINT
G3
40
G4
MODELLO
MODEL
OMEGA V ECHOS 65.2 LC
OMEGA V ECHOS 65.2 LC LN
OMEGA V ECHOS 69.2 LC
OMEGA V ECHOS 69.2 LC LN
Fh
G..
FORI DI FISSAGGIO
FIXING HOLES
1700
1900
100
PESO (kg) PESO IN FUNZIONE (kg)
G1 (kg) G2 (kg) G3 (kg) G4 (kg)
WEIGHT(kg) OPERATING WEIGHT (kg)
2510
2781
855
857
535
534
2910
3181
1002 1004
588
587
2470
2741
829
856
536
520
2870
3141
976
1003
589
573
Ø22
PUNTI DI APPOGGIO ANTIVIBRANTI
VIBRATION DAMPER FOOT HOLDS
/
/
/
Rev. Data-Date
Dis.-Draftsman
Denominazione-Denomination
/
Visto-Checked by
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
Scala-Scale
1:40
Sost. il dis.-Replace draw.
A4C428A
Data-Date
10/09/09
/
Materiale-Material
/
58
100
Spessore-Thickness
/
/
Descrizione revisione-Revision description
Codice-Code
OMEGA V ECHOS LC
65.2-69.2
Dis.-Draftsman
A.Greguoldo
Visto-Checked by
G.Morosin
Sost. dal dis.-Replaced by draw.
/
Trattamento-Treatment
/
/
-
Rev.
A4C428
A
Foglio
di 2
N. 2
Sheet
of
Peso-Weight [kg]
-
Colore vernice-Painted colour
/
Swegon reserves the right to alter specifications.
Disegno-Drawing
- Proprietà riservata, riproduzione vietata a termini di
legge.Copyright.
- Reserved property, reproduction prohibited accordin to
existent laws.Copyright.
MTE 56 rev. 03 date: 22/02/08
www.swegon.com
COBALT W
COBALT W 72.2-83.2
Sc
*
"A"
"B"
200
200
170
1380 (**)
1190
13,2
30
100
1000
1000
Cin
550
1250
1280
1380 (*)
1000
290
Cout
290
2043 (*)
1950
1000
920
Es
1550
1950
4060
4250 (**)
290
Cin
290
Ep
550
13,2
Cout
170
1250
783
VISTA DA "A" / VIEW FROM "A"
Lh
1148 (**)
959
331
Uin
1750
2412
331
690
VISTA DA "B" / VIEW FROM "B" Uout
(*) CON CUFFIA INSONORIZZANTE
WITH SOUNDPROOF CASING
(**) CON RUBINETTO IN ASPIRAZIONE
WITH SUCTION SHUT-OFF VALVE
Lh
FORI DI SOLLEVAMENTO
LIFTING HOLES
Ep
QUADRO ELETTRICO
ELECTRICAL PANEL
Cin
INGR. ACQUA CONDENSAZIONE
CONDENSING WATER INLET
G 5"
Es
INGRESSO ALIMENTAZIONE ELETTRICA
ELECTRICAL SUPPLY INLET
Cout
USCITA ACQUA CONDENSAZIONE
CONDENSING WATER OUTLET
G 5"
Sc
CUFFIA INSONORIZZANTE
SOUNDPROOF CASING
Uin
INGRESSO ACQUA UTILIZZO
USER WATER INLET
OD 168.3
SPAZI DI INSTALLAZIONE
CLEARANCES
Uout
USCITA ACQUA UTILIZZO
USER WATER OUTLET
OD 168.3
Denominazione-Denomination
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
OMEGA V ECHOS
72.2-83.2
*
OPTIONAL
Codice-Code
Disegno-Drawing
Rev.
-
A4C367
A
A4C367A
Swegon reserves the right to alter specifications.
www.swegon.com
59
COBALT W
COBALT W 72.2-83.2
40
Fh
G1
G2
1250
1170
IMPRONTA A TERRA /
FOOTPRINT
G3
40
G4
100
MODELLO
MODEL
OMEGA V ECHOS 72.2
OMEGA V ECHOS 72.2 LN
OMEGA V ECHOS 76.2
OMEGA V ECHOS 76.2 LN
OMEGA V ECHOS 78.2
OMEGA V ECHOS 78.2 LN
OMEGA V ECHOS 83.2
OMEGA V ECHOS 83.2 LN
Fh
G..
FORI DI FISSAGGIO
FIXING HOLES
1750
1950
PESO (kg) PESO IN FUNZIONE (kg)
WEIGHT(kg) OPERATING WEIGHT (kg)
2987
3303
3385
3701
3052
3371
3452
3771
3043
3365
3443
3765
3043
3354
3443
3754
100
G1 (kg) G2 (kg) G3 (kg) G4 (kg)
996
1142
1036
1183
1040
1187
1031
1178
1063
1210
1066
1213
1060
1207
1060
1207
642
694
643
696
638
691
640
693
602
655
626
679
627
680
623
676
Ø22
PUNTI DI APPOGGIO ANTIVIBRANTI
VIBRATION DAMPER FOOT HOLDS
Denominazione-Denomination
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
OMEGA V ECHOS
72.2-83.2
Codice-Code
Disegno-Drawing
Rev.
-
A4C367
A
A4C367A
60
Swegon reserves the right to alter specifications.
www.swegon.com
COBALT W
COBALT W /LC 72.2-83.2
Sc
Ep
*
"A"
"B"
Rl
200
1380 (**)
1170
1000
30
(*) 100
1000
1652 (*)
1000
850
1550
1950
3970
4130 (**)
Rd
1250
1280
1380 (*)
1000
1550
Es
200
Rd
1250
382
VISTA DA "A" / VIEW FROM "A"
Lh
1750
2412
331
1149 (**)
939
Uin
(*) CON CUFFIA INSONORIZZANTE
WITH SOUNDROOF CASING
331
594
(**) CON RUBINETTO IN ASPIRAZIONE
WITH SUCTION SHUT-OFF VALVE
VISTA DA "B" / VIEW FROM "B" Uout
Lh
FORI DI SOLLEVAMENTO
LIFTING HOLES
Ep
QUADRO ELETTRICO
ELECTRICAL PANEL
Rd
CONNESSIONI REFRIGERANTE (MANDATA)
REFRIGERANT CONNECTIONS (DISCHARGE)
Es
INGRESSO ALIMENTAZIONE ELETTRICA
ELECTRICAL SUPPLY INLET
Rl
CONNESSIONI REFRIGERANTE (LIQUIDO)
REFRIGERANT CONNECTIONS (LIQUID)
Sc
CUFFIA INSONORIZZANTE
SOUNDPROOF CASING
Uin
INGRESSO ACQUA UTILIZZO
USER WATER INLET
OD 168.3
SPAZI DI INSTALLAZIONE
CLEARANCES
Uout
USCITA ACQUA UTILIZZO
USER WATER OUTLET
OD 168.3
/
/
/
Rev. Data-Date
Dis.-Draftsman
Denominazione-Denomination
/
Visto-Checked by
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
Scala-Scale
1:40
Sost. il dis.-Replace draw.
A4C429A
Data-Date
10/09/09
/
Materiale-Material
/
Spessore-Thickness
/
/
Descrizione revisione-Revision description
Codice-Code
OMEGA V ECHOS LC
72.2-83.2
Dis.-Draftsman
A.Greguoldo
Visto-Checked by
G.Morosin
Sost. dal dis.-Replaced by draw.
/
Trattamento-Treatment
/
/
Swegon reserves the right to alter specifications.
-
*
OPTIONAL
Disegno-Drawing
Rev.
A4C429
A
Foglio
di 2
N. 1
Sheet
of
Peso-Weight [kg]
-
Colore vernice-Painted colour
/
- Proprietà riservata, riproduzione vietata a termini di
legge.Copyright.
- Reserved property, reproduction prohibited accordin to
existent laws.Copyright.
MTE 56 rev. 03 date: 22/02/08
www.swegon.com
61
COBALT W
COBALT W /LC 72.2-83.2
40
Fh
G1
G2
1250
1170
IMPRONTA A TERRA /
FOOTPRINT
G3
40
G4
MODELLO
MODEL
OMEGA V ECHOS 72.2 LC
OMEGA V ECHOS 72.2 LC LN
OMEGA V ECHOS 76.2 LC
OMEGA V ECHOS 76.2 LC LN
OMEGA V ECHOS 78.2 LC
OMEGA V ECHOS 78.2 LC LN
OMEGA V ECHOS 83.2 LC
OMEGA V ECHOS 83.2 LC LN
Fh
G..
1700
1900
100
PESO (kg) PESO IN FUNZIONE (kg)
G1 (kg) G2 (kg) G3 (kg) G4 (kg)
WEIGHT(kg) OPERATING WEIGHT (kg)
2545
2800
803
921
575
501
2947
3202
945
1074
629
554
2606
2861
841
923
574
523
3006
3261
984
1074
628
575
2591
2846
841
913
568
524
2990
3245
984
1064
622
575
2585
2826
830
911
568
517
2985
3226
973
1062
622
569
FORI DI FISSAGGIO
FIXING HOLES
Ø22
PUNTI DI APPOGGIO ANTIVIBRANTI
VIBRATION DAMPER FOOT HOLDS
/
/
/
Rev. Data-Date
Dis.-Draftsman
Denominazione-Denomination
/
Visto-Checked by
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
Scala-Scale
1:40
Sost. il dis.-Replace draw.
A4C429A
Data-Date
10/09/09
/
Materiale-Material
/
62
100
Spessore-Thickness
/
/
Descrizione revisione-Revision description
Codice-Code
OMEGA V ECHOS LC
72.2-83.2
Dis.-Draftsman
A.Greguoldo
Visto-Checked by
G.Morosin
Sost. dal dis.-Replaced by draw.
/
Trattamento-Treatment
/
/
-
Rev.
A4C429
A
Foglio
di 2
N. 2
Sheet
of
Peso-Weight [kg]
-
Colore vernice-Painted colour
/
Swegon reserves the right to alter specifications.
Disegno-Drawing
- Proprietà riservata, riproduzione vietata a termini di
legge.Copyright.
- Reserved property, reproduction prohibited accordin to
existent laws.Copyright.
MTE 56 rev. 03 date: 22/02/08
www.swegon.com
COBALT W
COBALT W 88.2-105.2
Sc
*
"A"
"B"
Es
200
(*) 170
1550
1950
1257
1000
293
Cin
200
530
40
80
1503
650
1350
1390
1000
1000
1000
1470 (*)
293
Cout
293
2143 (*)
2022
4710
Cin
293
Ep
650
530
Cout
170
1350
783
VISTA DA "A" / VIEW FROM "A"
Lh
606
1000
Uin
1750
2962
606
751
VISTA DA "B" / VIEW FROM "B"
Lh
FORI DI SOLLEVAMENTO
LIFTING HOLES
Ep
QUADRO ELETTRICO
ELECTRICAL PANEL
Uout
Cin
INGR. ACQUA CONDENSAZIONE
CONDENSING WATER INLET
G 5"
Es
INGRESSO ALIMENTAZIONE ELETTRICA
ELECTRICAL SUPPLY INLET
Cout
USCITA ACQUA CONDENSAZIONE
CONDENSING WATER OUTLET
G 5"
Sc
CUFFIA INSONORIZZANTE
SOUNDPROOF CASING
Uin
INGRESSO ACQUA UTILIZZO
USER WATER INLET
OD 168.3
SPAZI DI INSTALLAZIONE
CLEARANCES
Uout
USCITA ACQUA UTILIZZO
USER WATER OUTLET
OD 168.3
B
11/10/2010
F. Voltan
Rev. Data-Date
Dis.-Draftsman
Denominazione-Denomination
G. Morosin
Visto-Checked by
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
Scala-Scale
1:50
Sost. il dis.-Replace draw.
A4C377B
Data-Date
31/07/09
/
Materiale-Material
/
Spessore-Thickness
/
*
OPTIONAL
Aggiornate dimensioni e proprietà della cuffia insonorizzante
Descrizione revisione-Revision description
Codice-Code
OMEGA V ECHOS
88.2-105.2
Dis.-Draftsman
A.Greguoldo
Visto-Checked by
G.Morosin
Sost. dal dis.-Replaced by draw.
/
Trattamento-Treatment
/
/
Swegon reserves the right to alter specifications.
-
Disegno-Drawing
Rev.
A4C377
B
Foglio
di 2
N. 1
Sheet
of
Peso-Weight [kg]
-
Colore vernice-Painted colour
/
- Proprietà riservata, riproduzione vietata a termini di
legge.Copyright.
- Reserved property, reproduction prohibited accordin to
existent laws.Copyright.
MTE 56 rev. 03 date: 22/02/08
www.swegon.com
63
COBALT W
COBALT W 88.2-105.2
40
Fh
1270
1350
G1
G2
IMPRONTA A TERRA /
FOOTPRINT
G3
40
G4
MODELLO
MODEL
100
G..
3611
4131
3713
4232
3819
4338
3913
4434
FORI DI FISSAGGIO
FIXING HOLES
3975
4495
4080
4599
4180
4699
4277
4798
1326
1534
1491
1700
1476
1684
1569
1779
1299
1506
1328
1534
1418
1625
1394
1600
668
721
594
647
630
683
618
672
682
734
667
718
656
707
696
747
Ø22
PUNTI DI APPOGGIO ANTIVIBRANTI
VIBRATION DAMPER FOOT HOLDS
B
11/10/2010
F. Voltan
Rev. Data-Date
Dis.-Draftsman
Denominazione-Denomination
G. Morosin
Visto-Checked by
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
Scala-Scale
1:40
Sost. il dis.-Replace draw.
A4C377B
Data-Date
31/07/09
/
Materiale-Material
/
64
100
PESO (kg) PESO IN FUNZIONE (kg)
G1 (kg) G2 (kg) G3 (kg) G4 (kg)
WEIGHT(kg) OPERATING WEIGHT (kg)
OMEGA V ECHOS 88.2
OMEGA V ECHOS 88.2 LN
OMEGA V ECHOS 95.2
OMEGA V ECHOS 95.2 LN
OMEGA V ECHOS 100.2
OMEGA V ECHOS 100.2 LN
OMEGA V ECHOS 105.2
OMEGA V ECHOS 105.2 LN
Fh
1750
1950
Spessore-Thickness
/
Aggiornate dimensioni e proprietà della cuffia insonorizzante
Descrizione revisione-Revision description
Codice-Code
OMEGA V ECHOS
88.2-105.2
Dis.-Draftsman
A.Greguoldo
Visto-Checked by
G.Morosin
Sost. dal dis.-Replaced by draw.
/
Trattamento-Treatment
/
/
-
Rev.
A4C377
B
Foglio
di 2
N. 2
Sheet
of
Peso-Weight [kg]
-
Colore vernice-Painted colour
/
Swegon reserves the right to alter specifications.
Disegno-Drawing
- Proprietà riservata, riproduzione vietata a termini di
legge.Copyright.
- Reserved property, reproduction prohibited accordin to
existent laws.Copyright.
MTE 56 rev. 03 date: 22/02/08
www.swegon.com
COBALT W
COBALT W /LC 88.2-105.2
Ep
Sc
*
"A"
"B"
Rl
Es
(*) 80
1550
1257
200
1950
1000
1350
1000
1430 (*)
1503
1000
1000
1742 (*)
4710
Rd
1621
200
Rd
1350
382
VISTA DA "A" / VIEW FROM "A"
Lh
606
1750
1000
606
2962
751
Uin
(*) CON CUFFIA INSONORIZZANTE
WITH SOUNDROOF CASING
Uout
VISTA DA "B" / VIEW FROM "B"
Lh
FORI DI SOLLEVAMENTO
LIFTING HOLES
Ep
QUADRO ELETTRICO
ELECTRICAL PANEL
Rd
CONNESSIONI REFRIGERANTE (MANDATA)
REFRIGERANT CONNECTIONS (DISCHARGE)
Es
INGRESSO ALIMENTAZIONE ELETTRICA
ELECTRICAL SUPPLY INLET
Rl
CONNESSIONI REFRIGERANTE (LIQUIDO)
REFRIGERANT CONNECTIONS (LIQUID)
Sc
CUFFIA INSONORIZZANTE
SOUNDPROOF CASING
Uin
INGRESSO ACQUA UTILIZZO
USER WATER INLET
OD 168.3
Uout
USCITA ACQUA UTILIZZO
USER WATER OUTLET
OD 168.3
SPAZI DI INSTALLAZIONE
CLEARANCES
Rev. Data-Date
Dis.-Draftsman
Denominazione-Denomination
Visto-Checked by
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
Scala-Scale
1:50
Data-Date
23/11/10
Sost. il dis.-Replace draw.
A4D362A
/
Materiale-Material
/
Spessore-Thickness
/
*
Descrizione revisione-Revision description
Codice-Code
OMEGA V ECHOS LC
88.2-105.2
Dis.-Draftsman
A.Greguoldo
Visto-Checked by
G.Morosin
Sost. dal dis.-Replaced by draw.
/
Trattamento-Treatment
/
/
Swegon reserves the right to alter specifications.
-
OPTIONAL
Disegno-Drawing
Rev.
A4D362
A
Foglio
di 2
N. 1
Sheet
of
Peso-Weight [kg]
-
Colore vernice-Painted colour
/
- Proprietà riservata, riproduzione vietata a termini di
legge.Copyright.
- Reserved property, reproduction prohibited accordin to
existent laws.Copyright.
MTE 56 rev. 03 date: 22/02/08
www.swegon.com
65
COBALT W
COBALT W /LC 88.2-105.2
40
Fh
1270
1350
G1
G2
IMPRONTA A TERRA /
FOOTPRINT
G3
40
G4
MODELLO
MODEL
100
G..
FORI DI FISSAGGIO
FIXING HOLES
3415
3934
3508
4028
3600
4120
3690
4210
1178
1386
1278
1487
1259
1467
1126
1559
1150
1357
1118
1324
1203
1411
984
1384
537
589
519
573
556
609
736
596
550
602
593
644
582
633
844
671
Ø22
Visto-Checked by
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
Scala-Scale
1:40
Data-Date
23/11/10
Sost. il dis.-Replace draw.
/
66
3112
3631
3205
3725
3306
3826
3396
3916
PUNTI DI APPOGGIO ANTIVIBRANTI
VIBRATION DAMPER FOOT HOLDS
Rev. Data-Date
Dis.-Draftsman
Denominazione-Denomination
A4D362A
100
PESO (kg) PESO IN FUNZIONE (kg)
G1 (kg) G2 (kg) G3 (kg) G4 (kg)
WEIGHT(kg) OPERATING WEIGHT (kg)
OMEGA V ECHOS 88.2 LC
OMEGA V ECHOS 88.2 LC LN
OMEGA V ECHOS 95.2 LC
OMEGA V ECHOS 95.2 LC LN
OMEGA V ECHOS 100.2 LC
OMEGA V ECHOS 100.2 LC LN
OMEGA V ECHOS 105.2 LC
OMEGA V ECHOS 105.2 LC LN
Fh
1750
1950
Materiale-Material
/
Spessore-Thickness
/
Descrizione revisione-Revision description
Codice-Code
OMEGA V ECHOS LC
88.2-105.2
Dis.-Draftsman
A.Greguoldo
Visto-Checked by
G.Morosin
Sost. dal dis.-Replaced by draw.
/
Trattamento-Treatment
/
/
-
Rev.
A4D362
A
Foglio
di 2
N. 2
Sheet
of
Peso-Weight [kg]
-
Colore vernice-Painted colour
/
Swegon reserves the right to alter specifications.
Disegno-Drawing
- Proprietà riservata, riproduzione vietata a termini di
legge.Copyright.
- Reserved property, reproduction prohibited accordin to
existent laws.Copyright.
MTE 56 rev. 03 date: 22/02/08
www.swegon.com
COBALT W
COBALT W 110.2-124.2
Sc
*
"A"
"B"
Es
1550
1950
4770
200
190
200
620
(*) 55
1563
540
1350
1000
1000
Cin
1000
1405 (*)
293
Cout
293
2220 (*)
2100
1000
1256
293
Cin
293
Ep
540
620
1350
Cout
190
821
VISTA DA "A" / VIEW FROM "A"
Lh
1750
2910
580
1083
580
776
Uin
Uout
VISTA DA "B" / VIEW FROM "B"
Lh
FORI DI SOLLEVAMENTO
LIFTING HOLES
Ep
QUADRO ELETTRICO
ELECTRICAL PANEL
Cin
INGR. ACQUA CONDENSAZIONE
CONDENSING WATER INLET
G 5"
G 5"
Es
INGRESSO ALIMENTAZIONE ELETTRICA
ELECTRICAL SUPPLY INLET
Cout
USCITA ACQUA CONDENSAZIONE
CONDENSING WATER OUTLET
Sc
CUFFIA INSONORIZZANTE
SOUNDPROOF CASING
Uin
INGRESSO ACQUA UTILIZZO
USER WATER INLET
OD 219.1
SPAZI DI INSTALLAZIONE
CLEARANCES
Uout
USCITA ACQUA UTILIZZO
USER WATER OUTLET
OD 219.1
B
04/08/10
A.Greguoldo
Rev. Data-Date
Dis.-Draftsman
Denominazione-Denomination
G.Morosin
Visto-Checked by
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
Scala-Scale
1:50
Data-Date
31/07/09
Sost. il dis.-Replace draw.
A4C378B
/
Materiale-Material
/
Spessore-Thickness
/
Modified
Descrizione revisione-Revision description
Codice-Code
OMEGA V ECHOS
110.2-124.2
Dis.-Draftsman
A.Greguoldo
Visto-Checked by
G.Morosin
Sost. dal dis.-Replaced by draw.
/
Trattamento-Treatment
/
/
Swegon reserves the right to alter specifications.
-
*
OPTIONAL
Disegno-Drawing
Rev.
A4C378
B
Foglio
di 2
N. 1
Sheet
of
Peso-Weight [kg]
-
Colore vernice-Painted colour
/
- Proprietà riservata, riproduzione vietata a termini di
legge.Copyright.
- Reserved property, reproduction prohibited accordin to
existent laws.Copyright.
MTE 56 rev. 03 date: 22/02/08
www.swegon.com
67
COBALT W
COBALT W 110.2-124.2
40
Fh
G1
G2
1350
1270
IMPRONTA A TERRA /
FOOTPRINT
G3
40
G4
100
MODELLO
MODEL
1750
1950
PESO (kg) PESO IN FUNZIONE (kg)
G1 (kg) G2 (kg) G3 (kg) G4 (kg)
WEIGHT(kg) OPERATING WEIGHT (kg)
OMEGA V ECHOS 110.2
OMEGA V ECHOS 110.2 LN
OMEGA V ECHOS 117.2
OMEGA V ECHOS 117.2 LN
OMEGA V ECHOS 124.2
OMEGA V ECHOS 124.2 LN
Fh
G..
FORI DI FISSAGGIO
FIXING HOLES
4146
4596
4194
4593
4229
4630
4721
5171
4772
5171
4810
5211
1585
1758
1592
1739
1616
1764
1533
1705
1563
1710
1563
1710
788
841
801
854
802
855
815
867
816
868
829
882
Ø22
PUNTI DI APPOGGIO ANTIVIBRANTI
VIBRATION DAMPER FOOT HOLDS
B
04/08/10
A.Greguoldo
Rev. Data-Date
Dis.-Draftsman
Denominazione-Denomination
G.Morosin
Visto-Checked by
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
Scala-Scale
1:40
Sost. il dis.-Replace draw.
A4C378B
Data-Date
31/07/09
/
Materiale-Material
/
68
100
Spessore-Thickness
/
Modified
Descrizione revisione-Revision description
Codice-Code
OMEGA V ECHOS
110.2-124.2
Dis.-Draftsman
A.Greguoldo
Visto-Checked by
G.Morosin
Sost. dal dis.-Replaced by draw.
/
Trattamento-Treatment
/
/
-
Rev.
A4C378
B
Foglio
di 2
N. 2
Sheet
of
Peso-Weight [kg]
-
Colore vernice-Painted colour
/
Swegon reserves the right to alter specifications.
Disegno-Drawing
- Proprietà riservata, riproduzione vietata a termini di
legge.Copyright.
- Reserved property, reproduction prohibited accordin to
existent laws.Copyright.
MTE 56 rev. 03 date: 22/02/08
www.swegon.com
COBALT W
COBALT W /LC 110.2-124.2
Ep
Sc
*
"A"
"B"
Rl
(*) 80
Es
200
1256
1350
1000
200
1563
1430 (*)
1000
1000
1820 (*)
1694
1000
1550
1950
4770
Rd
Rd
1350
420
VISTA DA "A" / VIEW FROM "A"
Lh
1750
2910
580
1083
580
(*) CON CUFFIA INSONORIZZANTE
WITH SOUNDPROOF CASING
776
Uin
Uout
VISTA DA "B" / VIEW FROM "B"
Lh
FORI DI SOLLEVAMENTO
LIFTING HOLES
Ep
QUADRO ELETTRICO
ELECTRICAL PANEL
Rd
CONNESSIONI REFRIGERANTE (MANDATA)
REFRIGERANT CONNECTIONS (DISCHARGE)
Es
INGRESSO ALIMENTAZIONE ELETTRICA
ELECTRICAL SUPPLY INLET
Rl
CONNESSIONI REFRIGERANTE (LIQUIDO)
REFRIGERANT CONNECTIONS (LIQUID)
Sc
CUFFIA INSONORIZZANTE
SOUNDPROOF CASING
Uin
INGRESSO ACQUA UTILIZZO
USER WATER INLET
OD 219.1
Uout
USCITA ACQUA UTILIZZO
USER WATER OUTLET
OD 219.1
SPAZI DI INSTALLAZIONE
CLEARANCES
Rev. Data-Date
Dis.-Draftsman
Denominazione-Denomination
Visto-Checked by
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
Scala-Scale
1:50
Data-Date
23/11/10
Sost. il dis.-Replace draw.
/
A4D363A
Materiale-Material
/
Spessore-Thickness
/
Descrizione revisione-Revision description
Codice-Code
OMEGA V ECHOS LC
110.2-124.2
Dis.-Draftsman
A.Greguoldo
Visto-Checked by
G.Morosin
Sost. dal dis.-Replaced by draw.
/
Trattamento-Treatment
/
/
Swegon reserves the right to alter specifications.
-
*
OPTIONAL
Disegno-Drawing
Rev.
A4D363
A
Foglio
di 2
N. 1
Sheet
of
Peso-Weight [kg]
-
Colore vernice-Painted colour
/
- Proprietà riservata, riproduzione vietata a termini di
legge.Copyright.
- Reserved property, reproduction prohibited accordin to
existent laws.Copyright.
MTE 56 rev. 03 date: 22/02/08
www.swegon.com
69
COBALT W
COBALT W /LC 110.2-124.2
40
Fh
G1
G2
1350
1270
IMPRONTA A TERRA /
FOOTPRINT
G3
40
G4
100
MODELLO
MODEL
1750
1950
PESO (kg) PESO IN FUNZIONE (kg)
G1 (kg) G2 (kg) G3 (kg) G4 (kg)
WEIGHT(kg) OPERATING WEIGHT (kg)
OMEGA V ECHOS 110.2 LC
OMEGA V ECHOS 110.2 LC LN
OMEGA V ECHOS 117.2 LC
OMEGA V ECHOS 117.2 LC LN
OMEGA V ECHOS 124.2 LC
OMEGA V ECHOS 124.2 LC LN
Fh
G..
FORI DI FISSAGGIO
FIXING HOLES
4116
4567
4158
4558
4188
4589
1410
1584
1413
1560
1436
1584
1357
1530
1384
1531
1382
1529
662
714
673
727
672
725
687
739
688
740
698
751
Ø22
Visto-Checked by
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
Scala-Scale
1:40
Data-Date
23/11/10
Sost. il dis.-Replace draw.
/
Materiale-Material
/
70
3615
4066
3657
4057
3687
4088
PUNTI DI APPOGGIO ANTIVIBRANTI
VIBRATION DAMPER FOOT HOLDS
Rev. Data-Date
Dis.-Draftsman
Denominazione-Denomination
A4D363A
100
Spessore-Thickness
/
Descrizione revisione-Revision description
Codice-Code
OMEGA V ECHOS LC
110.2-124.2
Dis.-Draftsman
A.Greguoldo
Visto-Checked by
G.Morosin
Sost. dal dis.-Replaced by draw.
/
Trattamento-Treatment
/
/
-
Rev.
A4D363
A
Foglio
di 2
N. 2
Sheet
of
Peso-Weight [kg]
-
Colore vernice-Painted colour
/
Swegon reserves the right to alter specifications.
Disegno-Drawing
- Proprietà riservata, riproduzione vietata a termini di
legge.Copyright.
- Reserved property, reproduction prohibited accordin to
existent laws.Copyright.
MTE 56 rev. 03 date: 22/02/08
www.swegon.com
COBALT W
COBALT W 130.3-153.3
Ep
"A"
2267
"B"
1000
352,5
Lh
Es
2720
4420
907
1000
650
1000
Cout
385 352,5
1740
2125
385
1000
385
Lh
793
385
Cin
352,5 385
650
352,5
1740
930
VISTA DA "A" / VIEW TO "A"
245
2720
662
245
3210
548
VISTA DA "B" / VIEW TO "B"
Uin
Uout
Lh
FORI DI SOLLEVAMENTO
LIFTING HOLES
Cin
INGR. ACQUA CONDENSATORE
CONDENSER WATER INLET
G 4"
Ep
QUADRO ELETTRICO
ELECTRICAL PANEL
Cout
USCITA ACQUA CONDENSATORE
CONDENSER WATER OUTLET
G 4"
Es
INGRESSO ALIMENTAZIONE ELETTRICA
ELECTRICAL SUPPLY INLET
Uin
INGRESSO ACQUA EVAPORATORE
EVAPORATOR WATER INLET
OD 219.1
SPAZI DI INSTALLAZIONE
CLEARANCES
Uout
USCITA ACQUA EVAPORTORE
EVAPORATOR WATER OUTLET
OD 219.1
B
23/11/10
A.Greguoldo
Rev. Data-Date
Dis.-Draftsman
Denominazione-Denomination
G.Morosin
Visto-Checked by
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
Scala-Scale
1:50
Sost. il dis.-Replace draw.
A4C820B
Data-Date
02/03/10
/
Materiale-Material
/
Spessore-Thickness
/
*
Added weights table
Descrizione revisione-Revision description
Codice-Code
OMEGA V ECHOS
130.3-153.3
Dis.-Draftsman
A.Greguoldo
Visto-Checked by
G.Morosin
Sost. dal dis.-Replaced by draw.
/
Trattamento-Treatment
/
/
-
Disegno-Drawing
Rev.
A4C820
B
Foglio
di 2
N. 1
Sheet
of
Peso-Weight [kg]
-
Colore vernice-Painted colour
/
Swegon reserves the right to alter specifications.
OPTIONAL
- Proprietà riservata, riproduzione vietata a termini di
legge.Copyright.
- Reserved property, reproduction prohibited accordin to
existent laws.Copyright.
MTE 56 rev. 03 date: 22/02/08
www.swegon.com
71
COBALT W
COBALT W 130.3-153.3
2708
696
600
600
406
50
406
G2
G1
1628
1728
G1
G2
IMPRONTA A TERRA /
FOOTPRINT
G4
G3
G3
50
G4
MODELLO
MODEL
OMEGA V ECHOS
OMEGA V ECHOS
OMEGA V ECHOS
OMEGA V ECHOS
OMEGA V ECHOS
Fh
G..
PESO (kg) PESO IN FUNZIONE (kg)
G1 (kg) G2 (kg) G3 (kg) G4 (kg)
WEIGHT(kg) OPERATING WEIGHT (kg)
130.3
137.3
143.3
147.3
153.3
6024
6187
6352
6413
6464
FORI DI FISSAGGIO
FIXING HOLES
586
583
636
633
634
961
1024
1013
1025
1042
1099
1141
1126
1147
1160
669
650
707
709
705
Ø22
PUNTI DI APPOGGIO ANTIVIBRANTI
VIBRATION DAMPER FOOT HOLDS
B
23/11/10
A.Greguoldo
Rev. Data-Date
Dis.-Draftsman
Denominazione-Denomination
G.Morosin
Visto-Checked by
SCHEMA DIMENSIONALE
DIMENSIONAL DRAWING
Scala-Scale
1:40
Sost. il dis.-Replace draw.
A4C820B
Data-Date
02/03/10
/
Materiale-Material
/
72
6630
6796
6964
7028
7082
Spessore-Thickness
/
Added weights table
Descrizione revisione-Revision description
Codice-Code
OMEGA V ECHOS
130.3-153.3
Dis.-Draftsman
A.Greguoldo
Visto-Checked by
G.Morosin
Sost. dal dis.-Replaced by draw.
/
Trattamento-Treatment
/
/
-
Rev.
A4C820
B
Foglio
di 2
N. 2
Sheet
of
Peso-Weight [kg]
-
Colore vernice-Painted colour
/
Swegon reserves the right to alter specifications.
Disegno-Drawing
- Proprietà riservata, riproduzione vietata a termini di
legge.Copyright.
- Reserved property, reproduction prohibited accordin to
existent laws.Copyright.
MTE 56 rev. 03 date: 22/02/08
www.swegon.com
COBALT W
COBALT W /LC 130.3-153.3
Ep
"B"
1770
"A"
Es
Lh
793
1000
1740
Lh
2720
1000
907
385
1000
2125
1000
4420
Rl
Rd
1740
Rd
412
VISTA DA "A" / VIEW TO "A"
245
2720
662
245
3210
548
VISTA DA "B" / VIEW TO "B"
Uin
Uout
Lh
FORI DI SOLLEVAMENTO
LIFTING HOLES
Ep
QUADRO ELETTRICO
ELECTRICAL PANEL
Rd
CONNESSIONI REFRIGERANTE (MANDATA)
REFRIGERANT CONNECTIONS (DISCHARGE)
Es
INGRESSO ALIMENTAZIONE ELETTRICA
ELECTRICAL SUPPLY INLET
Rl
CONNESSIONI REFRIGERANTE (LIQUIDO)
REFRIGERANT CONNECTIONS (LIQUID)
Sc
CUFFIA INSONORIZZANTE
SOUNDPROOF CASING
Uin
INGRESSO ACQUA UTILIZZO
USER WATER INLET
OD 219.1
Uout
USCITA ACQUA UTILIZZO
USER WATER OUTLET
OD 219.1
SPAZI DI INSTALLAZIONE
CLEARANCES
/
/
/
Rev. Data-Date
Dis.-Draftsman
Denominazione-Denomination
/
Visto-Checked by
/
Descrizione revisione-Revision description
Codice-Code
SCHEMA DIMENSIONALE OMEGA V ECHOS LC
DIMENSIONAL DRAWING
130.3-153.3
Scala-Scale
1:50
Data-Date
24/11/10
Sost. il dis.-Replace draw.
A4D364A
/
Materiale-Material
/
Spessore-Thickness
/
Dis.-Draftsman
A.Greguoldo
Visto-Checked by
G.Morosin
Sost. dal dis.-Replaced by draw.
/
Trattamento-Treatment
/
/
Swegon reserves the right to alter specifications.
-
*
OPTIONAL
Disegno-Drawing
Rev.
A3D364
A
Foglio
di 2
N. 1
Sheet
of
Peso-Weight [kg]
-
Colore vernice-Painted colour
/
- Proprietà riservata, riproduzione vietata a termini di
legge.Copyright.
- Reserved property, reproduction prohibited accordin to
existent laws.Copyright.
MTE 56 rev. 03 date: 22/02/08
www.swegon.com
73
COBALT W
COBALT W /LC 130.3-153.3
2708
696
600
600
406
50
406
1628
1728
G1
G1
G2
G2
IMPRONTA A TERRA /
FOOTPRINT
G4
G3
G3
50
G4
MODELLO
MODEL
OMEGA V ECHOS 130.3 LC
OMEGA V ECHOS 137.3 LC
OMEGA V ECHOS 143.3 LC
OMEGA V ECHOS 147.3 LC
OMEGA V ECHOS 153.3 LC
Fh
G..
FORI DI FISSAGGIO
FIXING HOLES
PESO (kg)
WEIGHT(kg)
5284
5442
5602
5656
5704
PESO IN FUNZIONE (kg)
G1 (kg) G2 (kg) G3 (kg) G4 (kg)
OPERATING WEIGHT (kg)
5800
473
879
1006
542
5958
469
941
1047
522
6118
520
929
1032
578
6172
517
940
1051
578
6220
517
957
1063
573
Ø22
PUNTI DI APPOGGIO ANTIVIBRANTI
VIBRATION DAMPER FOOT HOLDS
/
/
/
Rev. Data-Date
Dis.-Draftsman
Denominazione-Denomination
/
Visto-Checked by
/
Descrizione revisione-Revision description
Codice-Code
SCHEMA DIMENSIONALE OMEGA V ECHOS LC
DIMENSIONAL DRAWING
130.3-153.3
Scala-Scale
1:40
Data-Date
24/11/10
Sost. il dis.-Replace draw.
/
A4D364A
Materiale-Material
/
74
Spessore-Thickness
/
Dis.-Draftsman
A.Greguoldo
Visto-Checked by
G.Morosin
Sost. dal dis.-Replaced by draw.
/
Trattamento-Treatment
/
/
-
Rev.
A3D364
A
Foglio
di 2
N. 2
Sheet
of
Peso-Weight [kg]
-
Colore vernice-Painted colour
/
Swegon reserves the right to alter specifications.
Disegno-Drawing
- Proprietà riservata, riproduzione vietata a termini di
legge.Copyright.
- Reserved property, reproduction prohibited accordin to
existent laws.Copyright.
MTE 56 rev. 03 date: 22/02/08
www.swegon.com
COBALT W
INSTALLATION GUIDELINES
POSITIONING
Strictly comply with the clearance areas indicated in the catalogue.
Make sure that there are no obstructions near the finned coil
suction line or the fan delivery line.
Place the unit in a manner that assures the lowest environmental impact (noise, integration with nearby structures, etc.).
ELECTRICAL CONNECTIONS
Always consult the enclosed wiring diagram, which provides all
the instructions required for making the electrical connections.
Power the unit (by turning the main switch off) at least 12
hours before start-up to supply the cranckase heaters.
Do not cut off the power from the unit during short stops.
Before turning on the disconnect switch, stop the unit by turning off all the operating switches or, if none, using the remote
control.
Before accessing the inner components, cut the power off by
turning on the main switch.
The power supply must be fitted with all protections according
to the standards in force.
Electrical connections: three-pole power cable + earth, or
three pole cable + neutral + earth; external interlock; remote
alarm signalling.
HYDRAULIC CONNECTIONS
Carefully vent the hydraulic system with the pumps switched
off, by operating the air valves. This procedure is particularly
important, as even small air bubbles may cause the evaporator
to freeze.
Drain the hydraulic system during winter stops or use special
anti-freeze solutions. During short stops, it is advisable to install an electric heater (defroster) on the evaporator and the
hydraulic circuit.
Assembe the hydraulic circuit with all the components shown
in the diagrams (expansion vessel, flow switch, storage tank,
air valve, shut-off valves, anti-vibrating connections, etc. Please
refer to the user, installation and maintenance manual).
Connect the flow switch when supplied in the kit, following
carefully the instructions provided with the units.
START-UP AND MAINTENANCE
Strictly follow the instructions given in the use and maintenance manual. These operations must be carried out by qualified
personnel only.
Swegon reserves the right to alter specifications.
www.swegon.com
75
60240050902 Cobalt W_08-04-2014