HiMAP

Transcription

HiMAP
HYUNDAI DIGITAL PROTECTION & MEASURING DEVICE
HiMAP&HiCAM-II
Hyundai Intelligent Measuring & Protection Device
HiMAP
Hyundai Intelligent Communication & Measuring Device
HiCAM-II
HYUNDAI DIGITAL PROTECTION & MEASURING DEVICE
HiMAP is a multifunctional digital protection relay that has a protection function
to protect incoming and feeder lines, the motor and the transformer.
It also has various kinds of measuring functions to check synchronization and a
communication function for the Power Management System (HIPMS) to supervise
operating conditions.
HiCAM-II has integrated as many as 15 analog meters in one body.
The measuring accuracy is below ±0.2-1.0% at rating.
For power monitoring system connection, HiCAM has RS485 communication port,
communication control device (HICM series) and support modbus protocol.
Remote CB On/Off control is possible by the command from power monitoring
system.
Protection
Relay
Function
Measuring
Function
Event
Record
Function
Communication
Function
Circuit Breaker
Remote Control
Function
Fault Wave
Record
Function
HiMAP
Hyundai Intelligent Measuring &
Protection Device
Characteristics
M-2
Display
M-4
Power Management System HIPMS-Plus M-6
Setting Range
M-8
Connection Diagram
M-9
Terminal Block Pin Specification
M-11
Characteristic Curve
M-12
Order Form
M-14
View & Dimension
M-15
HiMAP
Hyundai Intelligent Measuring & Protection Device
Characteristics
▶ Excellent operating characteristics using a 32 bit microprocessor.
▶ Easy to operate using an interactive menu system.
▶ Easy to connect monitoring system & local computer using four communication channels.
▶ Increased reliability using a self-diagnostic function.
▶ Designed for operator’s convenience.
Easy Installation and Maintenance
HiMAP is designed with a removable case so that
the external electric lines can be connected to the
inner part for easy installation and maintenance.
Self-diagnosis Function
HiMAP has a self-diagnosis function set to observe
any system failures, send an alarm signal, and
display it on the VFD window.
Use of a Digital Filter
HiMAP uses a digital filter, which prevents any
harmonic effects from the high frequency on the
power line.
Circuit Breaker Remote Control Function
HiMAP remotely controls circuit breakers by means of the
command from SCADA Systems and controls the load of
power in the computer through RS-485 communication port.
If there is interfacing with another company’s monitoring
system, it is easy to connect both systems because our
communication control device provides various interface
ports and protocols.
Harmonic Analysis Function
▶ Harmonic contents (1st-18th) for three phase current
can be measured. (THD, TDD)
▶ Harmonic contents for three phase fault wave can be
analyzed using HiMAP manager program.
Fault / Event Recording Function
HiMAP saves fault events up to 100. Each event
data has a fault phase, pick up ratio, operating time
and fault date.
Also, for the latest fault, HiMAP saves a fault wave
which is 300 cycles with the resolution 36 sampling /
cycle.
This can be transfer to monitoring system by
communication port.
Vector Diagram
Harmonic Analysis
M-2
HiMAP
Protection Relay Function
Model
Protection Object
HiMAP–FI
Incoming Feeder
HiMAP–M
Motor
HiMAP-T
Transformer
HiMAP-SC
Syncro-Check
Relay Function
•OCR(50/51)
•SGR(67G)
•UVR(27)
•OCGR(50G/51G)
•OVR(59)
•PSR(47P/47N)
•DGR(67G)
•DOCR(67)
•OVGR(64)
•DOCGR(67N)
•Trip coil supervision(94) (Option)
•OCR(50)
•NCHR(66)
•SGR(67G)
•51LR
•UCR(37)
•DFR(87M)
•THR(49)
•NSR(46)
•OCGR(50G/51G)
•DGR(67G)
•Closing/Trip coil supervision(94)(Option)
•OCR(50/51P)✽
•OCR(50/51S)✽
•DGR(67G)
•Closing/Trip coil supervision(94)(Option)
•DFR(87T)
•OCGR(50G/51G)
•SGR(67G)
•SCR(25)
•UVR(27)
✽ HiMAP-T Type has 2 OCRs. P means primary and S means secondary.
Measuring Function
HiMAP has a measuring function as shown in the below table. It displays the value of each measurement on the
VFD window by operating a menu key and then transfers and displays the data on the HIMIX window, which has an
outside digital indicator connected by a communication cable.
Various kinds of measuring values are converted to a primary value by input of a CT/PT ratio and then displayed on
the VFD window.
Measuring
Display
Accuracy (%)
0-999999V
±0.2
Current(Ir, Is, It, Io, Ips, Ins, Iavg, ITHD, ITDD)
0-999999A
±0.2
Real Power
0-99999999 kW
±0.2
Reactive Power
0-99999999 kvar
±0.5
Accumulated Real Energy
0-99999999 kWh
±1.0
Accumulated Reactive Energy
0-99999999 kvarh
±1.0
Power Factor
-1.0-1.0 PF
±0.5
Power
Voltage(Vr, Vs, Vt, Vo, Vps, Vns, Vavg, Vomax)
Frequency
45-65Hz
±0.01Hz
※ CT/PT ratio will be set by using relay control keys and then displayed via VFD window.
The values will be saved at flash memory even though the power line will be off.
Communication Function
HiMAP has four communication ports. RS-485 ports transfer all information related to relay operation status,
measuring information, and operation status of circuit breakers. This information is then perceived by HiMAP and
sent to communication control device at the speed of 62.5 K bps, using RS-485 HDLC frame protocol and
MODBUS-RTU protocol.
The communication control device connects a master PC to the Power Management System (HIPMS) at the speed
of 10M bps by Ethernet, TCP/IP. Please refer to the HIPMS manual for details on the monitoring function.
HIMIX communication port transfers kinds of measuring values optional to HIMIX at the speed of 9600 bps.
The external port of HiMAP transfers the fault record from a site to the PC for analysis, changes the relay element
value to a correct one, and is an RS-232C communication port to monitor the status of all kinds of protection relay.
Interface with SCADA
Communication Control Device
Type of Communication
Protocol
HICM-PC(II)
Ethernet
Modbus / TCP
M-3
HiMAP
Hyundai Intelligent Measuring & Protection Device
Display
Front View
Display Window(VFD)
Exterior Case
Internal Case
System Status Indicator
CB Status
CB Control
(Normal Operation,
System Fail, Fault)
Display Key
Input Key
Select Switch & Led
RS232 Port
Set
M-4
Movement Key
ACK
HiMAP
Specification
Item
Rating
Accuracy
Temperature
Insulation
Resistance
Voltage
Withstand
Overland
Withstand
Specification
Current
1A or 5A, Burden: Below 0.1VA/Phase
Voltage
110V or 190V, Burden: Below 0.3VA/Phase
Frequency
50Hz or 60Hz
Measuring
±0.2%
Protection Relaying
±2%
Operation Guarantee
-10℃ - 55℃
Restoration Guarantee
-25℃ - 70℃
Circuits-Ground
10 MΩ
Between Circuits
5 MΩ
Between Contacts
5 MΩ
Power Frequency
AC 60Hz 2000V/1 Min
Lightning Impulse
1.2/50㎲ 5 kV
Current Circuit
Rating Current×3: 3 hours / Rating Current × 20: 2sec
Voltage Circuit
Rating Voltage × 3: 3 hours
Control Power
Rating Voltage × 1.3: 3 hours
Control Power Interruption
Maximum 300 ms
Control Power
AC/DC 95V - 250V 50/60Hz, DC 48V
Standards
IEC 60255 / KEMC 1120 / IEC 61000-4
Communication Type
RS-485 Multi Drop
Protocol
HD-BUS / DNP 3.0 / MODBUS
Size
202.5(W) × 156(H) × 251(D)
Weight
4.3kg
I / O Point
Item
Input
Point
Remark
AI
Voltage
4
Default✽
AI
Current
4
Default✽
DI
5
Default
DO
7
Default(R1-R7) (21-34)
Output
31, 32(R6): Remote CB On
33, 34(R7): Remote CB Off
✽ HiMAP-87M(Self-balancing Type) : Current(7CH), Voltage(1CH)
HiMAP-87M(Differential Type)
: Current(7CH), Voltage(0CH)
HiMAP-T
: Current(7CH), Voltage(1CH)
M-5
HiMAP
Hyundai Intelligent Measuring & Protection Device
Power Management System HIPMS-Plus
System Configuration
Remote HIPMS-Plus Station
To Wide and
Local Area Networks
Enterprise Management Network
Web Client
(Web Browser)
Router
Mobile Phone
(SMS)
GPS
Web Server
Maintenance
& Operating
Multi Server
Maintenance
& Operating
Multi Server
Internet
Redundant Ethernet Network 10/100Mbps(Fiber Optic)
FEP
HICM860S(P)
HICM860S(S)
HICM860S(P)
HICM860S(S)
HICM860S(P)
HICM860S(S)
Notebook PC
HiMAP-BC
RTU(HRC-NET)
HiCAM-II
Display Configuration
M-6
System Configuration
System Detail(1)
System Detail(2)
HiMAP Detail
RTU Detail
Network Status
HiMAP
Alarm Printer
External System
Network
Report Printer
Color Hard Copler
Gateway
HICM860S(P)
HICM860S(S)
HiMAP-F
HICM860S(P)
HICM860S(S)
HiMAP
Trend
Report Setting
Report
Alarm
Fault Analysis
Remote Setting
HiMIX
M-7
HiMAP
Hyundai Intelligent Measuring & Protection Device
Setting Range
FI Type
Mode
OCR
(50/51)
OCGR
(50G/51G)
UVR
(27)
POR
47P
NSOVR
47N
OVR
(59)
OVGR
Current
(67GD)
SGR
(67GS)
Below 0.05sec
0.05-10.0sec (0.01sec Step)
Mode
Instant
Definite
Current
(67)
DOCGR
(67N)
Inverse, Very Inverse, Extremely Inverse
(0.02-1.0) × In (Time Delay) (0.1A Step)
(0.1-12) × In (0.1A Step)
Below 0.05sec
0.05-10.0sec (0.01sec Step)
0.05-10.0 Tap (Time Delay) (0.01 Step)
Mode
-
Definite
-
Voltage
-
(0.2-1.0) × Vn (0.1V Step)
-
Time
-
0.1-10.0sec (0.1sec Step)
-
Mode
-
Definite
-
Voltage
-
(0.5-1.0) × Vn (0.1V Step)
-
Time
-
0.1-10.0sec (0.1sec Step)
-
Mode
-
Definite
-
Voltage
-
(0.02-0.5) × Vn (0.1V Step)
-
Time
-
0.1-10.0sec (0.1sec Step)
-
Mode
-
Definite
Inverse
Voltage
-
Time
-
0.1-10.0sec (0.1sec Step)
0.05-10.0 Tap (Time Delay) (0.01 Step)
Mode
Instant
-
Inverse
(1.1-1.45) × Vn (0.1V Step)
Voltage
(0.11-0.5) × Vn (0.1V Step)
Time
Below 0.05sec
Mode
Definite
Current
(0.04-0.4) × In (0.1A Step)
Voltage
(0.1-0.2) × Vn (0.1V Step)
Time
0.1-10.0sec (0.1sec Step)
Angle
10°- 45°(1°Step)
Mode
Definite
Current
1-10 mA (0.1 mA Step)
Voltage
(0.1-0.2) × Vn (0.1V Step)
Time
0.1-10.0sec (0.1sec Step)
Angle
45°-75°(1°Step)
Instant
-
0.05-10.0 Tap (Time Delay) (0.01 Step)
Definite
Inverse, Very Inverse, Extremely Inverse
Current
-
(0.20-2.40) × In (0.01A Step)
Voltage
-
(0.03-1.45) × Vn (0.1V Step)
Time
-
Angle
-
Mode
Instant
Current
-
Voltage
-
Time
-
Angle
-
※ - In: Rating Current, Vn: Rating Voltage
- Example HiMAP Setting; In: 5A, OCR: (1-18)×In → 5-90A
M-8
0.05-10.0 Tap (Time Delay) (0.01 Step)
Time
Mode
DOCR
(0.2-2.4) × In (Time Delay) (0.1A Step)
(1-18) × In (0.1A Step)
Time
(64)
DGR
Inverse, Very Inverse, Extremely Inverse
Definite
Instant
0.05-10.00sec (0.01sec Step)
0.05-10.00 Tap (Time Delay) (0.01 Step)
Ref. Angle: 0°-359°(1°Step), Op. Angle: ±30°
-90°(1°Step)
Definite
Inverse, Very Inverse, Extremely Inverse
(0.05-10.00) × In (0.01A Step)
(0.1-0.5) × Vn (0.1V Step)
0.05-10.00sec (0.01sec Step)
0.05-10.0 Tap (Time Delay) (0.01 Step)
Ref. Angle: 0°-359°(1°Step), Op. Angle: ±10°
-170°(1°Step)
HiMAP
Connection Diagram
HiMAP-FI(3CT, 3PT)
R
S
T
R1
PT / GPT
21
9
22
DISPLAY
10
11
R2
23
12
13
24
14
R3
Relay
CPU
15
16
26
R4
Output
27
28
GPT
3rd
CB
Programmable
25
R5
29
1
30
2
R6
31
3
50
4
5
CT
51
6
7
32
R7
33
34
50G
8
Local/
Remote
CB On
Local/
Remote
CB Off
35
NA
51G
36
27
37
CCS
38
47P
Option
39
R
S
T
DC 24 V
2
50
52a
CT
52b
51
42
64
43
67G
NA
45
46
6
Remote
52
67
67N
7
ZCT
41
44
4
5
40
59
1
3
TCS
47N
8
DI1
DI2
53
Vn
Power
60
61
63
RS485
(Scada)
64
KEYBOARD
65
Vp
Vn
Control
48
62
54
59
When using ZCT
(SGR)
47
Vp
66
67
RS485
(HIMIX)
68
Option
P
N
FG
M-9
HiMAP
Hyundai Intelligent Measuring & Protection Device
Connection Diagram
HiMAP-FI(2CT, 2PT)
R
S
T
R1
PT × 2
21
9
22
DISPLAY
10
11
R2
23
12
13
24
14
R3
Relay
CPU
15
26
R4
16
Programmable
25
Output
27
28
CB
R5
29
1
30
2
R6
31
3
50
4
5
CT
51
6
7
32
R7
33
34
50G
8
Local/
Remote
CB On
Local/
Remote
CB Off
35
ZCT
NA
51G
36
27
37
CCS
38
47P
Option
39
R
S
T
DC 24 V
TCS
47N
40
59
50
52a
41
42
64
43
44
52b
51
67G
NA
45
46
Remote
47
52
Vp
DI1
DI2
Vn
53
P
N
FG
M - 10
61
63
RS485
(Scada)
64
KEYBOARD
65
Vp
Vn
Power
60
62
54
59
Control
48
66
67
RS485
(HIMIX)
68
Option
HiMAP
Terminal Block Pin Specification
HiMAP-FI Type
Control Power Terminal
P
N
(+)
(-)
FG
Communication Terminal
60
61
62
63
64
65
Vp
Vn
Vp
Vn
HIMIX Communication
Terminal
66
67
68
Digital Output
41
42
43
44
45
46
47
48
Vp
Vn
N.A.
N.A.
Digital Input
50
51
52
53
54
55
56
57
58
59
52a
52b
Remote
D/I 1
D/I 2
N.A.
Common(+24V)
R1
R2
R3
R4
R5
R6(CB On)
R7(CB Off)
N.A.
CCS
TCS
21
23
25
27
29
31
33
35
37
39
Analog Input
22
24
26
28
30
32
34
36
38
40
1
3
5
7
9
11
13
15
17
19
Ia
Ib
Ic
Io
Va
Vb
Vc
Vo
N.A.
N.A.
Terminal No.
Description
Application
50
51
52
53
54
21-22
23-24
25-26
27-28
29-30
31-32
33-34
35-36
37-38
39-40
CB On Status 52a
CB Off Status 52b
Remote Input
General DI
General DI
R1
R2
R3
R4
R5
R6(CB On)
R7(CB Off)
N.A.
TCS
TCS
Fixed
Fixed
Fixed
Variable
Variable
2
4
6
8
10
12
14
16
18
20
Programmable
Relay Output
Fixed
Fixed
N.A.
Fixed
Fixed
M - 11
HiMAP
Hyundai Intelligent Measuring & Protection Device
Characteristic Curve
OCR & OCGR
Inverse | OP LEVEL 0.05-10.0
0.01
Very Inverse | OP LEVEL 0.05-10.0
0.01
DOCR
Extremely Inverse | OP LEVEL 0.05-10.0
0.01
M - 12
DOCR
Op. Current
Ia
Ib
Ic
Ref. Volt
Vbc
Vca
Vab
HiMAP
OVR
Inverse | OP LEVEL 0.05-10.0
OVGR
Very Inverse | OP LEVEL 0.05-10.0
0.01
0.01
DGR / SGR / DOCGR
DGR
SGR
DOCGR
M - 13
HiMAP
Hyundai Intelligent Measuring & Protection Device
Order Form
A. Type Selection of HiMAP
Please check mark(⋏) into the type required.
HiMAP – ❶ – ❷ ❸ – ❹ (Option)
❶
❷
Relay Type
Feeder/Incoming
FI
Motor
M
87M Big Motor
Transformer
T
SY Synchro check
❹ (option) 4)
❸
Ground Fault Type
C
OCGR
D
DGR / DOCGR
S
SGR
Communication
RS-485 HDLC
C
No System Interface
X
M MODBUS-RTU
T
X
TCS Function
Required
Not Apply
※ Type of 87M (Protection for big motor): ( ) self-balancing type / ( ) differential type
B. System Specification Required
Please check mark(⋏) into a parenthesis.
1) Measuring Current (CT) Inputs for OCR: ( ) 5A / ( ) 1A
2) Measuring Zero Phase Current (ZCT) Inputs for GFR: ( ) 5A / ( ) 1A / ( ) 1.5 mA
3) Frequency 3): ( ) 50Hz / ( ) 60Hz
4) Measuring Voltage (line to ground) inputs: ( ) 110V / ( ) 190V / Others (
V)
C. Ground Fault Function Selection
Table 1 (FI)
DGR(67G) /
DOCGR(67N)
Item
OCR(50/51)
OCGR(50/51G)
C
D
S
●
●
●
●
Item
MPR
OCGR(50/51G)
C
D
S
●
●
●
●
Item
87M
MPR
OCGR(50/51G)
C
D
S
●
●
●
●
●
●
●
SGR(67G)
OVR(59)
UVR(27)
OVGR(64)
PSR(47P/47N)
●
●
●
●
●
●
●
●
●
●
●
●
●
●
Table 2 (M)
DGR(67G) /
DOCGR(67N)
SGR(67G)
●
●
Table 3 (87M)
DGR(67G) /
DOCGR(67N)
SGR(67G)
●
●
Table 4 (T)
Item
DFR
C
D
S
●
●
●
OCR P(50/51P) 1) OCR S(50/51S) 2) OCGR(50/51G)
DGR(67G) /
DOCGR(67N)
●
●
●
●
●
●
●
●
※ 1) OCR P is transformer primary OCR
2) OCR S is transformer secondary OCR
3) The control voltage of HiMAP is only allow AC / DC 95 - 250V, 50 / 60Hz as a free voltage
4) TCS(Trip Coil Supervision): Circuit breaker coil disconnection check. (option)
Note
Ground fault function shell be selected in accordance with the system ground method.
- OCGR (50G/51G): Effective ground system
- DGR (67G): Resister ground system
- SGR (67G): Floated ground system
M - 14
SGR(67G)
●
HiMAP
View & Dimension
139
Weight 4.3Kg
186
Panel Cut-out Dimension
156
Top View
33
218
251
206
Side View
138
Front View
185
Rear View
M - 15
HiCAM-II
Hyundai Intelligent Communication &
Measuring Device
Characteristics
C-2
Display
C-2
Connection Diagram
C-4
Terminal Block Pin Specification
C-5
View & Dimension
C-6
HiCAM-II
Hyundai Intelligent Communication & Measuring Device
Characteristics
Accuracy
▶ ±0.2~1.0% at rating
Compact Size and Display
▶ Various indicator and measuring display
▶ Size : 202.5 (W) × 156 (H) × 189 (D)
Voltage / Current Input
Power Management System Connection
▶ CT : 0.1~10 A
▶ PT : 10~380 V
▶ RS485 HD-Bus
▶ Modbus protocol by communication control device
Various Measuring
(HICM Series)
▶ 15 measuring points
Display
Front View
Display Window
Communication Address
Current, Active Power
% Display
D/I Status LED
Select Key
D/O Status LED
Navigation Key
CB Control Switch/LED
Remote Key
C- 2
HiCAM-II
I / O Point
Point
Item
Input
Output
AI
Voltage
AI
Current
Remark
4
Default
4
Default
DI
12
Default(41~55)
DO
5
Default(31~40)
37, 38(D04) : Remote CB On
39, 40(D05) : Remote CB Off
31~36(D01~D03) use current demand output.
Specification
Specification
Item
Rating
Accuracy
Temperature
Insulation
Resistance
Voltage
Withstand
Overland
Withstand
Current
1 A or 5 A(0.1 A~10 A), Burden : Below 0.1 VA / Phase
Voltage
110 V or 190 V(10 V~380 V), Burden : Below 0.3 VA / Phase
Frequency
50 Hz or 60 Hz
Measuring
±0.2 %
Operation Guarantee
-10 ℃ ~ 55 ℃
Restoration Guarantee
-25 ℃ ~ 70 ℃
Circuit-Ground
10 ㏁
Between Circuits
5㏁
Between Contacts
5㏁
Power Frequency
AC 60 Hz 2,000V/1 Min
Lightning Impulse
1.2/50 ㎲ 5 kV
Current Circuit
Rating Current×3 : 3 hours / Rating Current×20 : 1 sec
Voltage Circuit
Rating Voltage×3 : 3 hours
Control Power
Rating Voltage×1.3 : 3 hours
Control Power
AC 85 ~ 264 V (50 / 60 Hz), DC 90 ~ 120 V
Power Consumption
18 VA, AC 220 V
Communication Type
RS–485 / Multi Drop
Protocol
HD-BUS / Modbus
Standards
KEMC1110, IEC1036
Size
202.5 (W)×156 (H)×189 (D)
Weight
1.5 Kg
Measuring
Accuracy
Remark
Voltage
0~999999 V
±0.2%
Line to Line Voltage
Current
0~999999 A
±0.2%
Phase Current
Real Power
0~99999999 kW
±0.2%
Reactive Power
0~99999999 kvar
±0.5%
Apparent Power
0~99999999 kVA
±1.0%
Accumulated Real Energy
0~99999999 kWh
±1.0%
Accumulated Reactive Energy
0~99999999 kvarh
±1.0%
Power Factor
-1.0~1.0 PF
±0.5%
Frequency
45~65 Hz
±0.01 Hz
Reverse Real Power
0~999999 kW
±0.5%
(-) Sign
Reverse
0~999999 kWh
±1.0%
(-) Sign
Measuring
Display
C- 3
HiCAM-II
Hyundai Intelligent Communication & Measuring Device
Connection Diagram
3P 4W 3PT_3CT
RS T N
3P 3W 2PT_2CT
45/50/55 41
PT/GPT
42
43
44
46
47
48
49
51
52
53
RS T
54
45/50/55 41
PT
9
10
12
Vp
Vn
15
16
AI
1
2
3
4
5
6
7
8
48
49
51
52
53
54
DI
Vp
Vn
66
67
15
16
L
N
FG
AD/DC
R5
39
R4
38
37
R3
36
R2
35
34
33
95~250V
50/60Hz
R1
32
1
2
3
4
5
6
7
8
CT
COMM.
L
N
FG
DO
AD/DC
R5
40
31
Remote CB On : 37, 38 Terminal
Remote CB Off : 39, 40 Terminal
66
67
68
69
70
AI
COMM.
DO
40
39
R4
38
37
R3
36
R2
35
34
33
R1
32
95~250V
50/60Hz
31
Remote CB On : 37, 38 Terminal
Remote CB Off : 39, 40 Terminal
3P 3W 3PT_3CT
3P 3W 2PT_3CT
45/50/55 41
42
43
44
46
47
48
49
51
52
53
RS T
54
45/50/55 41
PT
9
10
11
42
43
44
46
47
48
49
51
52
53
54
9
10
11
12
12
DI
13
Vp
Vn
15
16
14
AI
15
16
L
N
FG
AD/DC
R5
40
39
R4
38
37
R3
36
35
R2
34
33
R1
32
Remote CB On : 37, 38 Terminal
Remote CB Off : 39, 40 Terminal
31
95~250V
50/60Hz
CT
66
67
68
69
70
AI
COMM.
DO
Vp
Vn
66
67
68
69
70
1
2
3
4
5
6
7
8
DI
13
14
C- 4
47
14
68
69
70
GPT
CT
46
13
14
PT
44
12
DI
13
RS T
43
11
11
CT
42
9
10
1
2
3
4
5
6
7
8
COMM.
L
N
FG
DO
AD/DC
R5
40
39
R4
38
37
R3
36
35
R2
34
33
R1
32
Remote CB On : 37, 38 Terminal
Remote CB Off : 39, 40 Terminal
31
95~250V
50/60Hz
HiCAM-II
Terminal Block Pin Specification
Control Power Terminal
L
N
FG
(+)
(-)
FG
Terminal
56
57
58
59
60
61
62
63
64
65
N.A.
Communication
Terminal
66
67
68
69
70
Vp
Vn
Vp
Vn
N.A.
Digital Input
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
52a
52b
Remote
DI 1
Common(+24V)
DI 2
DI 3
DI 4
DI 5
Common(+24V)
DI 6
DI 7
DI 8
DI 9
Common(+24V)
Digital Output
31
32
33
34
35
36
37
38
39
40
1
3
5
7
9
11
13
15
17
19
R1(+)
R1(-)
R2(+)
R2(-)
R3(+)
R3(-)
R4(CB On)
R4(CB On)
R5(CB Off)
R5(CB Off)
Terminal No.
Description
31~32
R1
33~34
R2
35~36
R3
37~38
R4(Remote On)
Fixed
39~40
R5(Remote Off)
Fixed
41
CB On Status 52a
42
CB Off Status 52b
43
Remote Input
44
General DI
Variable
45
Common
HiCAM Self Power +24V
46
General DI
Analog Input
47
General DI
Ia
Ib
Ic
Io
Vab
Vbc
Vca
Vo
N.A.
N.A.
48
General DI
49
General DI
2
4
6
8
10
12
14
16
18
20
50
Common
51
General DI
52
General DI
53
General DI
54
General DI
55
Common
Application
Variable
Fixed
Variable
HiCAM Self Power +24V
Variable
HiCAM Self Power +24V
C- 5
HiCAM-II
Hyundai Intelligent Communication & Measuring Device
View & Dimension
Weight 1.5Kg
139
186
Panel Cut-out Dimension
Top View
189
33
141
156
206
Side View
Front View
138
185
Rear View
C- 6
15
HHIS-WC-SE-B11-04, 2009.12 Designed by MERMONT
Head Office
1, Jeonha-dong, Dong-gu, Ulsan, Korea
Tel: 82-52-202-8101~8
Fax: 82-52-202-8100
Seoul
(Sales & Marketing)
140-2, Gye-dong, Jongno-gu, Seoul, Korea
Tel: 82-2-746-7579, 7523
Fax: 82-2-746-7648
Orlando
3452 Lake Lynda Drive, Suite 170, Orlando, Florida 32817, U.S.A.
Tel: 1-407-249-7350
Fax: 1-407-275-4940
New Jersey
300 Sylvan Avenue, Englewood Cliffs, NJ 07632, U.S.A.
Tel: 1-201-816-0286
Fax: 1-201-816-4083
London
2nd Floor, The Triangle, 5-17 Hammersmith Grove, London, W6 0LG, UK
Tel: 44-20-8741-0501
Fax: 44-20-8741-5620
Tokyo
8th Fl., Yurakucho Denki Bldg.1-7-1, Yuraku-cho, Chiyoda-gu, Tokyo, 100-0006, Japan
Tel: 81-3-3212-2076, 3215-7159
Fax: 81-3-3211-2093
Osaka
I-Room 5th Fl. Nagahori-Plaza Bldg. 2-4-8, Minami Senba, Chuo-Ku, Osaka, 542-0081, Japan
Tel: 81-6-6261-5766, 5767
Fax: 81-6-6261-5818
Dubai
Level 2, Unit 205, Emaar Square-Bldg.4 Sheikh Zayed Road, P.O.Box 252458, Dubai, U.A.E.
Tel: 971-4-425-7995
Fax: 971-4-425-7996
Sofia
1271, Sofia 41, Rojen Blvd., Bulgaria
Tel: 359-2-803-3200
Fax: 359-2-803-3203
Yangzhong
No. 9 Xiandai Road, Xinba Scientific and Technologic Zone, Yangzhong, Jiangsu, P.R.C. Zip: 212212, China
Tel: 86-511-8842-0666, 0212
Fax: 86-511-8842-0668, 0231