ks series - vertical installation

Transcription

ks series - vertical installation
KS SERIES - VERTICAL INSTALLATION
CS-DS-01-KSV
CS-PJ-01-KSV
CS-PJ-02-KSV
CS-PJ-03-KSV
CS-PJ-04-KSV
CS-PJ-05-KSV
CS-PJ-06-KSV
CS-PJ-07-KSV
CS-PJ-08-KSV
CS-BS-01-KSV
CS-BS-02-KSV
CS-BS-03-KSV
CS-BS-04-KSV
CS-BS-05-KSV
CS-BS-06-KSV
CS-BS-07-KSV
CS-BS-08-KSV
CS-BS-09-KSV
CS-BS-10-KSV
CS-OC-01-KSV
CS-OC-02-KSV
CS-OC-03-KSV
CS DISCLAIMER
KS42SL EXPANDED PANEL JOINT
KS42SL ENGAGED PANEL JOINT
KS45SL EXPANDED PANEL JOINT
KS45SL ENGAGED PANEL JOINT
INTERMEDIATE SUPPORT
INTERMEDIATE SUPPORT - SLIP CONNECTION
LINER PANEL TO CONCRETE WITH SUPPORT
LINER PANEL TO CONCRETE
BASE DETAIL - INSULATED SLAB
HEAVY GAUGE ANGLE
BASE DETAIL - INSULATED SLAB
LIGHT GAUGE Z
BASE DETAIL - PARTITION W/ FLOOR INSULATION
BASE DETAIL - INSULATED/NON-INSULATED
BASE DETAIL - PART. W/ CURBS INSULATED
BASE DETAIL - PART. NON-INSULATED
BASE DETAIL - LINER PANEL
BASE DETAIL - PART. W/ CURBS NON-INSULATED
BASE DETAIL - PART. W/ CURBS (ALTERNATE)
PARTITION BASE ON TOP OF CURB
OUTSIDE CORNER - FLUSH TRIM
OUTSIDE CORNER AT PARTITION
OUTSIDE CORNER LINER PANEL AT CONC WALL
INDEX SHEET
KS SERIES - VERTICAL INSTALLATION
CS-IC-01-KSV
CS-IC-02-KSV
CS-FO-01-KSV
CS-FO-02-KSV
CS-ST-01-KSV
CS-RK-01-KSV
CS-RK-02-KSV
CS-EV-01-KSV
CS-CE-01-KSV
CS-CE-02-KSV
CS-CE-03-KSV
CS-CE-04-KSV
CS-CE-05-KSV
CS-CE-06-KSV
CS-CE-07-KSV
CS-CE-08-KSV
CS-CE-09-KSV
CS-CE-10-KSV
CS-TL-01-KSV
CS-TL-02-KSV
CS-TL-03-KSV
CS-TL-04-KSV
INSIDE CORNER - FLUSH TRIM
PARTITION TO EXTERIOR WALL
HEADER CONDITION
JAMB CONDITION
STACK JOINT
RAKE
RAKE W/ MEMBRANE ROOF
LOW EAVE
INTERIOR WALL TO CEILING
INTERIOR WALL TO CEILING - 'T' SECTION
CEILING CHANNEL
CEILING TEE
CEILING TEE ASSEMBLY
CEILING CHANNEL ASSEMBLY
CEILING TO WALL - LONGITUDINAL
CEILING TO WALL - TRANSVERSE
PARTITION TO ROOF
PARTITION TO ROOF WITH BLOCKING
TRIM END LAP
TRIM LAP WITH HEM
TRIM END LAP WITH LAP STRIP
TRIM LAP AT FRAMED OPENING
INDEX SHEET
KS SERIES - VERTICAL INSTALLATION
DISCLAIMERS:
THESE DETAILS ARE PROVIDED AS A GUIDELINE FOR PROPER PANEL AND ASSOCIATED
COMPONENT INSTALLATION, AND ARE BASED ON INDUSTRY ACCEPTED PRACTICES.
REFRIGERATION EQUIPMENT IN COMBINATION WITH THE TEMPERATURE DIFFERENTIAL BETWEEN
BUILDING EXTERIOR AND INTERIOR CAN CREATE NEGATIVE AIR PRESSURE WITHIN THE BUILDING
(WARM AIR FROM OUTSIDE THE BUILDING IS DRAWN INTO THE BUILDING THROUGH AIR LEAKS
IN THE BUILDING ENVELOPE). AS A RESULT, VAPOR SEALS ARE OF PRIMARY CONCERN TO PROPER
COLD STORAGE PERFORMANCE. IN GENERAL, COLD STORAGE FACILITIES REQUIRE THE PRIMARY
VAPOR BARRIER TO BE ON THE EXTERIOR (I.E. "WARM" SIDE), RATHER THAN INTERIOR SIDE OF THE
PANEL.
PROJECTS LOCATED IN AREAS SUBJECT TO EXTREME COLD AND/OR HIGH SNOW LOADS MAY
REQUIRE MODIFICATIONS TO THESE DETAILS - CONTACT KINGSPAN TECHNICAL SERVICES
FOR SPECIFIC PROJECT RECOMMENDATIONS.
ALL STRUCTURAL SUPPORTS ARE NOT BY KINGSPAN AND ARE SHOWN FOR CLARIFICATION AND
ILLUSTRATION PURPOSES ONLY.
CONTACT KINGSPAN TECHNICAL SERVICES FOR MAXIMUM ALLOWABLE PANEL SPANS
AND FASTENING PATTERNS.
ALL SEALANTS TO BE COMPATIBLE WITH VAPOR BARRIERS AS SHOWN
COLD STORAGE
DISCLAIMER
KS SERIES - VERTICAL INSTALLATION
SHADOWLINE
INTERIOR FACE
KS42SL
2" - 6"
EXTERIOR FACE
SHADOWLINE
42" COVERAGE (36", 30", & 24" OPTIONAL)
HORIZONTAL SUPPORT
MALE LEG
COLD SIDE
"WARM" SIDE
12 GA. STAINLESS STEEL
HIDDEN FASTENER CLIP
(1 PER PANEL, PER SUPPORT)
SET CLIP IN BUTYL SEALANT
FEMALE POCKET
OPTIONAL BUTYL
(RECOMMENDED FOR
WASHDOWN APPLICATIONS)
CONTINUOUS BUTYL
SEALANT (AT "WARM"
SIDE JOINT)
1
4" - 14 HEX HEAD
FASTENERS WITHOUT WASHER
WALL PANEL INSTALLATION DIRECTION
NOTE: FILL FEMALE POCKET(S) 3/4 FULL WITH SEALANT TO PROVIDE PROPER AIR/WATER SEAL
KS42SL
EXPANDED JOINT
KS SERIES - VERTICAL INSTALLATION
HORIZONTAL SUPPORT
MALE JOINT
FEMALE JOINT
COLD SIDE
"WARM" SIDE
PANEL MODULE
1 "
8
12 GA. STAINLESS STEEL
HIDDEN FASTENER CLIP
(1 PER PANEL, PER SUPPORT)
SET CLIP IN BUTYL SEALANT
1
4" - 14 HEX HEAD
FASTENERS WITHOUT WASHER
WALL PANEL INSTALLATION DIRECTION
KS42SL
ENGAGED JOINT
OPTIONAL BUTYL
(RECOMMENDED FOR
WASHDOWN APPLICATIONS)
CONTINUOUS BUTYL SEALANT
(AT "WARM" SIDE JOINT)
KS SERIES - VERTICAL INSTALLATION
SHADOWLINE
INTERIOR FACE
KS45SL
EXTERIOR FACE
2"-6"
SHADOWLINE
45.378" COVERAGE
OPTIONAL BUTYL
(RECOMMENDED FOR
WASHDOWN APPLICATIONS)
COLD SIDE
FEMALE POCKET
MALE LEG
"WARM" SIDE
CONTINUOUS BUTYL
SEALANT (AT "WARM"
SIDE JOINT)
WALL PANEL INSTALLATION DIRECTION
NOTE: FILL FEMALE POCKET(S) 3/4 FULL WITH SEALANT TO PROVIDE PROPER AIR/WATER SEAL
KS45SL
EXPANDED JOINT
KS SERIES - VERTICAL INSTALLATION
OPTIONAL BUTYL
(RECOMMENDED FOR
WASHDOWN APPLICATIONS)
COLD SIDE
CONTINUOUS BUTYL
SEALANT
(AT "WARM" SIDE JOINT)
"WARM" SIDE
WALL PANEL INSTALLATION DIRECTION
KS45SL
ENGAGED JOINT
KS SERIES - VERTICAL INSTALLATION
INTERIOR OF
BUILDING
EXTERIOR OF
BUILDING
OPTIONAL BUTYL
(RECOMMENDED FOR
WASHDOWN APPLICATIONS)
CONTINUOUS BUTYL SEALANT
AT "WARM" SIDE PANEL JOINT
1
4" - 14 HEX HEAD FASTENERS
WITHOUT WASHER
12 GA. STAINLESS STEEL
HIDDEN FASTENER CLIP
(1 PER PANEL, PER SUPPORT)
SET CLIP IN BUTYL SEALANT
COLD SIDE
3
4"
1 "
2 4
1"
5
"WARM" SIDE
16
STANDARD:
12 GA. STAINLESS STEEL
TWO-HOLE HIDDEN FASTENER CLIP
5
16
OPTIONAL:
12 GA. STAINLESS STEEL
ONE-HOLE HIDDEN FASTENER CLIP
NOTE:
CONTACT KINGSPAN TECHNICAL SERVICES
FOR SPECIFIC PROJECT RECOMMENDATIONS
INTERMEDIATE
SUPPORT
3
4"
1 "
2 4
KS SERIES - VERTICAL INSTALLATION
12 GA. STAINLESS STEEL
HIDDEN FASTENER CLIP
(1 PER PANEL, PER SUPPORT)
WARM SIDE
COLD SIDE
LOW PROFILE BOLT W/ WASHER
AND LOCK NUT
OFFSET BEAM CLIP
12 GA. STAINLESS STEEL
HIDDEN FASTENER CLIP
(1 PER PANEL, PER SUPPORT)
WARM SIDE
COLD SIDE
LOW PROFILE BOLT W/ WASHER
AND LOCK NUT
OFFSET BEAM CLIP
NOTE: BEAM CLIP TO ALLOW STRUCTURAL STEEL TO DEFLECT W/O PUTTING
VERTICAL LOAD INTO WALL PANEL.
CONTACT KINGSPAN TECHNICAL SERVICES FOR ADDITIONAL INFO
INTERMEDIATE
SUPPORT - SLIP
CONNECTION
KS SERIES - VERTICAL INSTALLATION
INTERIOR OF
BUILDING
CONTINUOUS BUTYL SEALANT
AT "WARM" SIDE PANEL JOINT
SHIM AS NECESSARY
1
4"
- 14 HEX HEAD FASTENERS
CONCRETE/MASONRY
WALL
(NOT BY KINGSPAN)
"WARM" SIDE
12 GA. STAINLESS STEEL
HIDDEN FASTENER CLIP
(1 PER PANEL, PER SUPPORT)
HAT CHANNEL & FASTENING
(NOT BY KINGSPAN)
COLD SIDE
OPTIONAL BUTYL
(RECOMMENDED FOR
WASHDOWN APPLICATIONS)
3
4"
1 "
2 4
1"
5
16
STANDARD:
12 GA. STAINLESS STEEL
TWO-HOLE HIDDEN FASTENER CLIP
5
16
OPTIONAL:
12 GA. STAINLESS STEEL
ONE-HOLE HIDDEN FASTENER CLIP
NOTE:
CONTACT KINGSPAN TECHNICAL SERVICES
FOR SPECIFIC PROJECT RECOMMENDATIONS
LINER PANEL TO
CONCRETE WITH
SUPPORT
3
4"
1 "
2 4
KS SERIES - VERTICAL INSTALLATION
INTERIOR OF
BUILDING
CONTINUOUS BUTYL SEALANT
AT "WARM" SIDE PANEL JOINT
FASTENERS TO MASONRY
(NOT BY KINGSPAN)
CONCRETE/MASONRY
WALL
(NOT BY KINGSPAN)
12 GA. STAINLESS STEEL
HIDDEN FASTENER CLIP
(1 PER PANEL, PER SUPPORT)
SLIP SHEET TO PROTECT PANELS
(NOT BY KINGSPAN)
"WARM" SIDE
COLD SIDE
OPTIONAL BUTYL
(RECOMMENDED FOR
WASHDOWN APPLICATIONS)
3
4"
1 "
2 4
1"
5
16
STANDARD:
12 GA. STAINLESS STEEL
TWO-HOLE HIDDEN FASTENER CLIP
5
16
OPTIONAL:
12 GA. STAINLESS STEEL
ONE-HOLE HIDDEN FASTENER CLIP
NOTE:
CONTACT KINGSPAN TECHNICAL SERVICES
FOR SPECIFIC PROJECT RECOMMENDATIONS
LINER PANEL TO
CONCRETE
3
4"
1 "
2 4
KS SERIES - VERTICAL INSTALLATION
SEALANT (OPTIONAL NOT BY KINGSPAN)
(INSTALL AFTER TEMP.
PULL DOWN )
"Z" TRIM
"WARM" SIDE
2 BEADS OF
BUTYL SEALANT
ON EACH SIDE
SLIP SHEET TO PROTECT
PANELS (NOT BY KINGSPAN)
F.I.P INSULATION
(NOT BY KINGSPAN)
"Z" TRIM
FIELD CUT THERMAL
BREAK
LAP TRIM
3"
N.
MI RIM
T P
LA
1
4" - 14 HEX HEAD FASTENERS
WITHOUT WASHER
CONCRETE CURB
(NOT BY KINGSPAN)
12 GA. STAINLESS STEEL
HIDDEN FASTENER CLIP
(1 PER PANEL, PER SUPPORT)
SET CLIP IN BUTYL SEALANT
SET PANEL IN CONT. HEAVY
BEAD BUTYL SEALANT W/
MARRIAGE BEAD TO
EXT. PANEL JOINT
COLD SIDE
CONCRETE SLAB
(NOT BY KINGSPAN)
BASE TRIM
POP RIVETS
CONTINUOUS "Z" TRIM SET IN
BUTYL SEALANT (SEE LAP TRIM
ABOVE FOR "Z" TRIM)
HEAVY GA. BASE ANGLE
(NOT BY KINGSPAN)
FLOOR INSULATION
(NOT BY KINGSPAN)
SUB SLAB
(NOT BY KINGSPAN)
CONTINUOUS HEAVY BEAD
OF BUTYL SEALANT
FASTENER TO CONCRETE
(NOT BY KINGSPAN)
VAPOR BARRIER (NOT BY KINGSPAN)
NOTES: 1) BASE ANGLE MUST BE FASTENED SECURELY TO SLAB TO RESIST LATERAL LOAD
APPLIED BY PANEL
2) BASE ANGLE GAUGE TO BE DETERMINED BY PROJECT ENGINEER OF RECORD
3) FLOOR INSULATION REQUIRED FOR FREEZER APPLICATIONS
BASE DETAIL INSULATED SLAB
HEAVY GAUGE ANGLE
KS SERIES - VERTICAL INSTALLATION
SEALANT (OPTIONAL NOT BY KINGSPAN)
(INSTALL AFTER TEMP.
PULL DOWN )
LAP TRIM
2 BEADS OF
BUTYL SEALANT
ON EACH SIDE
SLIP SHEET TO PROTECT
PANELS (NOT BY KINGSPAN)
F.I.P INSULATION
(NOT BY KINGSPAN)
3"
D
"
3
EN P
D
A
EN P L
LA
"Z" ANGLE
LAP TRIM
FIELD CUT THERMAL
BREAK
1
4" - 14 HEX HEAD FASTENERS
WITHOUT WASHER
CONCRETE CURB
(NOT BY KINGSPAN)
12 GA. STAINLESS STEEL
HIDDEN FASTENER CLIP
(1 PER PANEL, PER SUPPORT)
SET CLIP IN BUTYL SEALANT
SET PANEL IN CONT. HEAVY
BEAD BUTYL SEALANT W/
MARRIAGE BEAD TO
EXT. PANEL JOINT
COLD SIDE
CONCRETE SLAB
(NOT BY KINGSPAN)
BASE TRIM
POP RIVETS
"Z" SHAPED BASE ANGLE
(NOT BY KINGSPAN)
FLOOR INSULATION
(NOT BY KINGSPAN)
"WARM" SIDE
SUB SLAB
(NOT BY KINGSPAN)
CONTINUOUS HEAVY BEAD
OF BUTYL SEALANT
FASTENER TO CONCRETE
(NOT BY KINGSPAN)
VAPOR BARRIER (NOT BY KINGSPAN)
SEE LAP TRIM ABOVE FOR "Z" BASE ANGLE
NOTES: 1) BASE ANGLE MUST BE FASTENED SECURELY TO SLAB TO RESIST LATERAL LOAD
APPLIED BY PANEL
2) Z SHAPED BASE ANGLE GAUGE TO BE DETERMINED BY PROJECT ENGINEER OF RECORD
3) FLOOR INSULATION REQUIRED FOR FREEZER APPLICATIONS
BASE DETAIL INSULATED SLAB
LIGHT GAUGE Z
KS SERIES - VERTICAL INSTALLATION
COLD SIDE
OPTIONAL BUTYL
(RECOMMENDED FOR
WASHDOWN APPLICATIONS)
"WARM" SIDE
CONTINUOUS BUTYL SEALANT
AT "WARM" SIDE PANEL JOINT
SEALANT
(OPTIONAL - NOT BY KINGSPAN)
(INSTALL AFTER TEMP. PULL
DOWN )
CONTINUOUS BUTYL SEALANT
WITH MARRIAGE BEAD TO SEALANT
AT "WARM" SIDE PANEL JOINT
3
3
4"
PHIL. PAN HEAD
MIN. 16 GA. GALVANIZED
BASE ANGLE
FASTENER TO CONCRETE
(NOT BY KINGSPAN)
CONCRETE SLAB
(NOT BY KINGSPAN)
4"
PHIL. PAN HEAD
MIN. 16 GA. GALVANIZED
BASE ANGLE
FASTENER TO CONCRETE
(NOT BY KINGSPAN)
BUTYL SEALANT
BUTYL SEALANT
(OPTIONAL)
FLOOR INSULATION
(NOT BY KINGSPAN)
BASE DETAIL PARTITION W/ FLOOR
INSULATION
VAPOR BARRIER
(NOT BY KINGSPAN)
KS SERIES - VERTICAL INSTALLATION
OPTIONAL BUTYL
(RECOMMENDED FOR
WASHDOWN APPLICATIONS)
CONTINUOUS BUTYL SEALANT
AT "WARM" SIDE PANEL JOINT
"WARM" SIDE
COLD SIDE
SEALANT
(OPTIONAL - NOT BY KINGSPAN)
(INSTALL AFTER TEMP. PULL
DOWN )
SLIP SHEET TO PROTECT
PANELS (NOT BY KINGSPAN)
CONCRETE CURB
(NOT BY KINGSPAN)
CONCRETE CURB
(NOT BY KINGSPAN)
F.I.P INSULATION
(NOT BY KINGSPAN)
CONCRETE SLAB
(NOT BY KINGSPAN)
FIELD CUT THERMAL
BREAK
FINISH FLOOR
SET PANEL IN CONT. HEAVY
BEAD BUTYL SEALANT W/
MARRIAGE BEAD TO
EXT. PANEL JOINT
STAGGERED
FLOOR INSULATION
(NOT BY KINGSPAN)
BASE CHANNEL
(NOT BY KINGSPAN)
SUB SLAB
(NOT BY KINGSPAN)
CONTINUOUS HEAVY BEAD
OF BUTYL SEALANT
FASTENER TO CONCRETE
(NOT BY KINGSPAN)
VAPOR BARRIER
(NOT BY KINGSPAN)
NOTES: 1) BASE CHANNEL MUST BE FASTENED SECURELY TO SLAB
2) ANGLE IRON MAY BE USED IN LIEU OF CHANNEL
BASE DETAIL INSULATED/
NON-INSULATED FLOOR
KS SERIES - VERTICAL INSTALLATION
COLD SIDE
"WARM" SIDE
OPTIONAL BUTYL
(RECOMMENDED FOR
WASHDOWN APPLICATIONS)
SEALANT
(OPTIONAL - NOT BY KINGSPAN)
(INSTALL AFTER TEMP. PULL
DOWN)
12 GA. STAINLESS STEEL
HIDDEN FASTENER CLIP
(1 PER PANEL, PER SUPPORT)
SET CLIP IN BUTYL SEALANT
CONTINUOUS BUTYL SEALANT
AT "WARM" SIDE PANEL JOINT
1
4" - 14 HEX HEAD FASTENERS
WITHOUT WASHER
ABUSE CURB (NOT BY
KINGSPAN - CAN BE
POURED AFTER PANEL
INSTALLATION)
SLIP SHEET
TO PROTECT PANELS
(NOT BY KINGSPAN)
BUTYL SEALANT
BUTYL SEALANT
MIN. 16 GA. GALVANIZED
BASE ANGLE
FASTENER TO CONCRETE
(NOT BY KINGSPAN)
FLOOR INSULATION
(NOT BY KINGSPAN)
SEALANT MARRIAGE BEAD TO
VERTICAL PANEL JOINT
VAPOR BARRIER
(NOT BY KINGSPAN)
BASE DETAIL PARTITION W/ CURBS
INSULATED FLOOR
KS SERIES - VERTICAL INSTALLATION
CONTINUOUS BUTYL SEALANT
AT "WARM" SIDE PANEL JOINT
"WARM" SIDE
OPTIONAL BUTYL
(RECOMMENDED FOR
WASHDOWN APPLICATIONS)
COLD SIDE
SEALANT
(OPTIONAL - NOT BY KINGSPAN)
(INSTALL AFTER TEMP. PULL
DOWN)
3
4"
PHIL. PAN HEAD
BUTYL SEALANT
SEALANT MARRIAGE BEAD TO
VERTICAL PANEL JOINT
BUTYL SEALANT
(OPTIONAL)
BASE DETAIL PARTITION
NON-INSULATED FLOOR
MIN. 16 GA. GALVANIZED
BASE ANGLE
FASTENER TO CONCRETE
(NOT BY KINGSPAN)
KS SERIES - VERTICAL INSTALLATION
OPTIONAL BUTYL
(RECOMMENDED FOR
WASHDOWN APPLICATIONS)
3
4"
PHIL. PAN HEAD
BASE TRIM
"WARM" SIDE
CONTINUOUS BUTYL SEALANT
AT "WARM" SIDE PANEL JOINT
12 GA. STAINLESS STEEL
HIDDEN FASTENER CLIP
(1 PER PANEL, PER SUPPORT)
SET CLIP IN BUTYL SEALANT
1
4" - 14 HEX HEAD FASTENERS
WITHOUT WASHER
MIN. 16 GA. GALVANIZED
BASE ANGLE
BUTYL SEALANT
SEALANT
(OPTIONAL - NOT BY KINGSPAN)
(INSTALL AFTER TEMP. PULL
DOWN - SEE SCHEDULE)
EXISTING EXTERIOR WALL
(NOT BY KINGSPAN)
COLD SIDE
BUTYL SEALANT
(OPTIONAL)
SEALANT MARRIAGE BEAD TO
VERTICAL PANEL JOINT
BASE DETAIL - LINER
PANEL
FASTENER TO CONCRETE
(NOT BY KINGSPAN)
KS SERIES - VERTICAL INSTALLATION
CONTINUOUS BUTYL SEALANT
AT "WARM" SIDE PANEL JOINT
SEALANT
(OPTIONAL - NOT BY KINGSPAN)
(INSTALL AFTER TEMP. PULL
DOWN)
VAPOR BARRIER
(NOT BY KINGSPAN)
3
4"
"WARM" SIDE
OPTIONAL BUTYL
(RECOMMENDED FOR
WASHDOWN APPLICATIONS)
COLD SIDE
ABUSE CURB (NOT BY
KINGSPAN - CAN BE
POURED AFTER PANEL
INSTALLATION)
PHIL. PAN HEAD
BUTYL SEALANT W/
MARRIAGE BEAD
SLIP SHEET
TO PROTECT PANELS
(NOT BY KINGSPAN)
BUTYL SEALANT
BUTYL SEALANT
MIN. 16 GA. GALVANIZED
BASE CHANNEL
FASTENER TO CONCRETE
(NOT BY KINGSPAN)
BASE DETAIL PARTITION W/ CURBS
(NON-INSULATED FLOOR)
KS SERIES - VERTICAL INSTALLATION
COLD SIDE
"WARM" SIDE
OPTIONAL BUTYL
(RECOMMENDED FOR
WASHDOWN APPLICATIONS)
SEALANT
(OPTIONAL - NOT BY KINGSPAN)
(INSTALL AFTER TEMP. PULL
DOWN - SEE SCHEDULE)
12 GA. STAINLESS STEEL
HIDDEN FASTENER CLIP
(1 PER PANEL, PER SUPPORT)
SET CLIP IN BUTYL SEALANT
SLIP SHEET
TO PROTECT PANELS
(NOT BY KINGSPAN)
CONTINUOUS BUTYL SEALANT
AT "WARM" SIDE PANEL JOINT
1
4" - 14 HEX HEAD FASTENERS
WITHOUT WASHER
ABUSE CURB (NOT BY
KINGSPAN - CAN BE
POURED AFTER PANEL
INSTALLATION)
VAPOR BARRIER
(NOT BY KINGSPAN)
BUTYL SEALANT
BUTYL SEALANT
MIN. 16 GA. GALVANIZED
BASE ANGLE
FASTENER TO CONCRETE
(NOT BY KINGSPAN)
SEALANT MARRIAGE BEAD TO
VERTICAL PANEL JOINT
BASE DETAIL PARTITION W/ CURBS
(ALTERNATE)
KS SERIES - VERTICAL INSTALLATION
CONTINUOUS BUTYL SEALANT
AT "WARM" SIDE PANEL JOINT
BUTYL SEALANT
3
4"
PHIL. PAN HEAD
MIN. 16 GA. GALVANIZED
BASE CHANNEL
OPTIONAL BUTYL
(RECOMMENDED FOR
WASHDOWN APPLICATIONS)
SEALANT
(OPTIONAL - NOT BY KINGSPAN)
(INSTALL AFTER TEMP. PULL
DOWN)
BUTYL SEALANT
FASTENER TO CONC.
(NOT BY KINGSPAN)
CONTINUOUS BUTYL SEALANT
AT "WARM" SIDE PANEL JOINT
OPTIONAL BUTYL
(RECOMMENDED FOR
WASHDOWN APPLICATIONS)
3
SEALANT
(OPTIONAL - NOT BY KINGSPAN)
(INSTALL AFTER TEMP. PULL
DOWN)
4"
PHIL. PAN HEAD
MIN. 16 GA. GALVANIZED
BASE ANGLE
MIN. 16 GA. GALVANIZED
BASE ANGLE
BUTYL SEALANT
BUTYL SEALANT
FASTENER TO CONC.
(NOT BY KINGSPAN)
PARTITION BASE ON
TOP OF CURB
KS SERIES - VERTICAL INSTALLATION
WILL VARY WITH
FIELD CONDITION
WILL VARY WITH
FIELD CONDITION
FIELD CUT
MIN. 1 4" GAP FOR
F.I.P. INSTALLATION
FIELD CUT THERMAL
BREAK
F.I.P. INSULATION
(NOT BY KINGSPAN)
"WARM" SIDE
OUTSIDE CORNER TRIM
SELF-ADHERING VAPOR
BARRIER (AT "WARM" SIDE NOT BY KINGSPAN)
1
4" - 14 "LOW PROFILE"
THROUGH FASTENER
3
4"
PHIL. PAN HEAD
INSIDE CORNER TRIM
POP RIVETS
COLD SIDE
HORIZONTAL SUPPORT
OUTSIDE CORNER FLUSH TRIM
KS SERIES - VERTICAL INSTALLATION
WILL VARY WITH
FIELD CONDITION
WILL VARY WITH
FIELD CONDITION
FIELD CUT
MIN. 1 4" GAP FOR
F.I.P. INSTALLATION
FIELD CUT THERMAL
BREAK
F.I.P. INSULATION
(NOT BY KINGSPAN)
OUTSIDE CORNER TRIM
SELF-ADHERING
VAPOR BARRIER
(AT "WARM" SIDE NOT BY KINGSPAN)
3
4"
PHIL. PAN HEAD
INSIDE CORNER TRIM
3
4"
PHIL. PAN HEAD
OUTSIDE CORNER
AT PARTITION
KS SERIES - VERTICAL INSTALLATION
FASTENER TO CONCRETE
(NOT BY KINGSPAN)
OUTSIDE CORNER TRIM
(PRE-INSTALL)
TRANS FLASHING
SELF-ADHERING
VAPOR BARRIER
(AT "WARM" SIDE NOT BY KINGSPAN)
INSIDE CORNER TRIM
FIELD CUT THERMAL
BREAK
3
F.I.P. INSULATION
(NOT BY KINGSPAN)
OUTSIDE CORNER
LINER PANEL AT CONC
WALL
4"
PHIL. PAN HEAD
KS SERIES - VERTICAL INSTALLATION
WILL VARY WITH
FIELD CONDITION
WILL VARY WITH
FIELD CONDITION
3
4"
FIELD CUT
PHIL. PAN HEAD
COLD SIDE
OUTSIDE CORNER TRIM
FIELD CUT THERMAL
BREAK
F.I.P. INSULATION
(NOT BY KINGSPAN)
MIN. 1 4" GAP FOR
F.I.P. INSTALLATION
"WARM" SIDE
POP RIVETS
HORIZONTAL SUPPORT
SELF-ADHERING
VAPOR BARRIER
(NOT BY KINGSPAN)
INSIDE CORNER TRIM
1
4" - 14 "LOW PROFILE"
THROUGH FASTENER
INSIDE CORNER FLUSH TRIM
KS SERIES - VERTICAL INSTALLATION
INTERIOR
"WARM" SIDE
3
4"
PHIL. PAN HEAD
EXTERIOR
SELF-ADHERING
VAPOR BARRIER
(NOT BY KINGSPAN)
FIELD CUT THERMAL
BREAK
INSIDE CORNER TRIM
INTERIOR
PARTITION
F.I.P. INSULATION
(NOT BY KINGSPAN)
OPTIONAL BUTYL AT
WASH DOWN
EXPANSION FASTENER
(TO BE LOCATED ON
OPPOSITE SIDE OF
THERMAL CUT FROM
PANEL'S LEADING EDGE)
INSIDE CORNER TRIM
3
4"
PHIL. PAN HEAD
STRUCTURAL SUPPORT
INTERIOR
COLD SIDE
NOTES: 1) ADDITIONAL FASTENERS MAY BE REQUIRED ON EITHER SIDE
OF THE FIELD CUT THERMAL BREAK BASED UPON ACTUAL DESIGN
LOADS AND THERMAL REQUIREMENTS
FIELD FILL WITH
INSULATION
(NOT BY KINGSPAN)
INSULATE SUPPORTING
STEEL ON "WARM" SIDE
OF PARTITION
(APPROX. 4'-0")
FIELD NOTCH PANELS
AT GIRT LOCATIONS
GIRT
CAP TRIM
(NOT BY KINGSPAN)
PARTITION TO
EXTERIOR WALL
KS SERIES - VERTICAL INSTALLATION
OPTIONAL BUTYL
(RECOMMENDED FOR
WASHDOWN APPLICATIONS)
CONTINUOUS BUTYL SEALANT
AT "WARM" SIDE PANEL JOINT
COLD SIDE
SEALANT
(OPTIONAL - NOT
BY KINGSPAN)
(INSTALL AFTER
TEMP. PULL
DOWN )
SELF ADHERING VAPOR
BARRIER (OPTIONAL - NOT BY
KINGSPAN)
HEADER CONDITION
"WARM" SIDE
FREEZER DOOR CASING,
FASTENERS, SEALANT, &
REQUIRED SUPPORT
(NOT BY KINGSPAN)
CONTINUOUS BUTYL SEALANT
WITH MARRIAGE BEAD TO SEALANT
AT "WARM" SIDE PANEL JOINT
KS SERIES - VERTICAL INSTALLATION
SEALANT
(OPTIONAL - NOT BY KINGSPAN)
(INSTALL AFTER TEMP. PULL
DOWN )
COLD SIDE
"WARM" SIDE
SELF ADHERING VAPOR
BARRIER (OPTIONAL - NOT BY
KINGSPAN)
FREEZER DOOR CASING,
FASTENERS, SEALANT, &
REQUIRED SUPPORT
(NOT BY KINGSPAN)
CONTINUOUS BUTYL SEALANT
JAMB CONDITION
KS SERIES - VERTICAL INSTALLATION
"WARM" SIDE
COLD SIDE
FIELD ROUT PANELS
FOR WOOD SPLINE
BASE TRIM WITH POP
RIVETS (PRE-INSTALL
WEEP HOLES)
CONTINUOUS BUTYL
SEALANT
STACK JOINT TRIM
WITH POP RIVETS
FIR SPLINE
(NOT BY KINGSPAN)
SET FIR SPLINE IN BUTYL
SEALANT
CONTINUOUS BUTYL
SEALANT MARRIED TO
SEALANT IN PANEL JOINT
CONTINUOUS BUTYL SEALANT
AT "WARM" SIDE PANEL JOINT
HORIZONTAL SUPPORT
(NOT BY KINGSPAN)
14 GA. GALVANIZED HIDDEN CLIP
(1 PER PANEL, PER GIRT)
NOTES: 1) SEE DETAIL CS-TL-01-KSV AND CS-TL-02-KSV FOR PROPER TRIM LAP DETAILS
2) CONTACT KINGSPAN TECHNICAL SERVICES FOR PROPER PANEL FASTENING
REQUIREMENTS
STACK JOINT
KS SERIES - VERTICAL INSTALLATION
GALVANIZED CAP FLASHING
(NOT BY KINGSPAN)
ROOF MEMBRANE SYSTEM
ATTACHMENT (NOT BY KINGSPAN)
ROOF MEMBRANE
(NOT BY KINGSPAN)
ROOF MEMBRANE SYSTEM
ATTACHMENT (NOT BY KINGSPAN)
SEALANT MARRIAGE BEAD TO
VERTICAL PANEL JOINT
RAKE TRIM, FASTENERS, SEALANT
AND WEATHER TIGHTNESS
(NOT BY KINGSPAN)
BOARD INSULATION AND
ROOF UNDERLAYMENT
(NOT BY KINGSPAN)
"WARM" SIDE
FIELD CUT THERMAL BREAK
1
SHEETING OR RAKE
ANGLE REQUIRED
(NOT BY KINGSPAN)
F.I.P. INSULATION
(NOT BY KINGSPAN)
COLD SIDE
OPTIONAL BUTYL
(RECOMMENDED FOR
WASHDOWN APPLICATIONS)
RAKE
4" - 14 HEX HEAD FASTENERS
WITHOUT WASHER
12 GA. STAINLESS STEEL
HIDDEN FASTENER CLIP
(1 PER PANEL, PER SUPPORT)
SET CLIP IN BUTYL SEALANT
CONTINUOUS BUTYL SEALANT
AT "WARM" SIDE PANEL JOINT
KS SERIES - VERTICAL INSTALLATION
GALVANIZED CAP FLASHING
(NOT BY KINGSPAN)
ROOF MEMBRANE
(NOT BY KINGSPAN)
ROOF MEMBRANE SYSTEM
ATTACHMENT (NOT BY KINGSPAN)
CONT. HEAVY BEAD BUTYL
SEALANT W/ MARRIAGE BEAD
TO EXT. PANEL JOINT
RAKE TRIM, FASTENERS, SEALANT
AND WEATHER TIGHTNESS
(NOT BY KINGSPAN)
INSULATION AND
ROOF UNDERLAYMENT
(NOT BY KINGSPAN)
FASTENER
(NOT BY KINGSPAN)
"WARM" SIDE
SEALANT TO MEMBRANE
(NOT BY KINGSPAN)
FIELD CUT THERMAL BREAK
F.I.P. INSULATION
(NOT BY KINGSPAN)
SHEETING OR RAKE
ANGLE REQUIRED
(NOT BY KINGSPAN)
COLD SIDE
OPTIONAL BUTYL
(RECOMMENDED FOR
WASHDOWN APPLICATIONS)
RAKE W/ MEMBRANE
ROOF
1
4" - 14 HEX HEAD FASTENERS
WITHOUT WASHER
12 GA. STAINLESS STEEL
HIDDEN FASTENER CLIP
(1 PER PANEL, PER SUPPORT)
SET CLIP IN BUTYL SEALANT
KS SERIES - VERTICAL INSTALLATION
F.I.P. INSULATION
(NOT BY KINGSPAN)
GALVANIZED CAP FLASHING
(NOT BY KINGSPAN)
ROOF MEMBRANE
(NOT BY KINGSPAN)
ROOF MEMBRANE SYSTEM
ATTACHMENT (NOT BY KINGSPAN)
CONT. HEAVY BEAD BUTYL
SEALANT W/ MARRIAGE BEAD
TO EXT. PANEL JOINT
RAKE TRIM, FASTENERS, SEALANT
AND WEATHER TIGHTNESS
(NOT BY KINGSPAN)
INSULATION AND
ROOF UNDERLAYMENT
(NOT BY KINGSPAN)
"WARM" SIDE
SEALANT TO MEMBRANE
(NOT BY KINGSPAN)
FASTENER
(NOT BY KINGSPAN)
FIELD CUT THERMAL BREAK
1
EAVE STRUT
(NOT BY KINGSPAN)
COLD SIDE
OPTIONAL BUTYL
(RECOMMENDED FOR
WASHDOWN APPLICATIONS)
LOW EAVE
4" - 14 HEX HEAD FASTENERS
WITHOUT WASHER
12 GA. STAINLESS STEEL
HIDDEN FASTENER CLIP
(1 PER PANEL, PER SUPPORT)
SET CLIP IN BUTYL SEALANT
CONTINUOUS BUTYL SEALANT
AT "WARM" SIDE PANEL JOINT
KS SERIES - VERTICAL INSTALLATION
SEE CS-CE-04-KSV
FOR ADDITIONAL INFO
ATTIC ABOVE CEILING
MUST BE VENTILATED
FIELD CUT THERMAL
BREAK
F.I.P. INSULATION
(NOT BY KINGSPAN)
OUTSIDE CORNER TRIM
CEILING
SELF ADHERING
VAPOR BARRIER
(NOT BY KINGSPAN)
COLD SIDE
"WARM" SIDE
3
WALL
3
4"
4"
PHIL. PAN HEAD
INSIDE CORNER TRIM
PHIL. PAN HEAD
CONTINUOUS BUTYL SEALANT
AT "WARM" SIDE PANEL JOINT
INTERIOR WALL TO
CEILING
KS SERIES - VERTICAL INSTALLATION
#10 X 13 8" FASTENER
AT EVERY PANEL JOINT
BOTH SIDES OF PANEL
AA
CROSS SECTION
(SECTION VIEW )
FIELD CUT THERMAL
BREAK
CEILING
BUTYL SEALANT
SUPPORT ANGLE
COMPRESSIBLE INSULATION
(NOT BY KINGSPAN)
EXPANSION FASTENER
A
WALL
A
BUTYL SEALANT
#10 X 13 8" TEK 1 FASTENER
AT EVERY PANEL JOINT
(SEE DETAIL ABOVE)
WALL TO CEILING
INTERSECTION
KS SERIES - VERTICAL INSTALLATION
INSULATE HANGER RODS
AS REQUIRED (NOT BY
KINGSPAN)
ATTIC ABOVE CEILING
MUST BE VENTILATED
HEX NUT AND LOCK WASHER
3
8" GALVANIZED HANGER
ALL-THREAD ROD (ROD
SPACING TO BE DETERMINED)
(NOT BY KINGSPAN)
4" X 4" X 14 GA.
PLATE WASHER*
SELF ADHERING
VAPOR BARRIER
(NOT BY KINGSPAN)
TRANSITION FLASHING
3
4"
PHIL. PAN HEAD
INTERIOR FACE OF PANEL
CEILING
3
4"
CEILING
EXTERIOR SIDE OF PANEL
MUST BE ON BOTTOM OF
CEILING. PANEL CUTLIST MUST
MATCH THIS ORIENTATION
PHIL. PAN HEAD
FILL 12" GAP BETWEEN
PANEL WITH F.I.P. INSULATION
(NOT BY KINGSPAN)
1 12" X 6" X 14 GA. GALVANIZED
CEILING CHANNEL (WHITE
POWDER COAT - OPTIONAL)
(CAP TRIM - OPTIONAL)
HEX NUT AND LOCK WASHER
3
#8 GA. SPLAY BRACE
WIRE IN FOUR DIRECTIONS
(NOT BY KINGSPAN)
3
8"
ALL-THREAD
HANGER ROD
4"
PHIL. PAN HEAD
SEISMIC
BRACE PLATE
* CONTACT KINGSPAN TECHNICAL
SERVICES FOR SEISMIC BRACE PLATE
QUANTITY AND LOCATION
FOUR TIGHT
TURNS IN 112"
SEISMIC BRACE PLATE
CEILING CHANNEL
KS SERIES - VERTICAL INSTALLATION
ATTIC ABOVE CEILING
MUST BE VENTILATED
3
INSULATE HANGER RODS
AS REQUIRED (NOT BY
KINGSPAN)
HEX NUT AND LOCK
WASHER
8"
GALVANIZED HANGER
ALL-THREAD ROD (SPACED
NO GREATER THAN 6'-0" O.C.)
(NOT BY KINGSPAN)
4" X 4" X 14 GA.
PLATE WASHER*
TRANSITION FLASHING
3
4"
SELF-ADHERING
VAPOR BARRIER
(NOT BY KINGSPAN)
PHIL. PAN HEAD
INTERIOR FACE OF PANEL
CEILING
CEILING
EXTERIOR SIDE OF PANEL
MUST BE ON BOTTOM OF
CEILING. PANEL CUTLIST MUST
MATCH THIS ORIENTATION
3
3
1
2" BOLT WITH (3)
"
WASHERS
AND (1)
8
LOCK-NUT PER BOLT
4" X 3" X 3 16" EXTRUDED
ALUMINUM CEILING TEE
(WHITE POWDER COAT FINISH)
3
8"
ALL-THREAD
HANGER ROD
8
3
3
FILL 12" GAP BETWEEN
PANEL WITH F.I.P. INSULATION
(NOT BY KINGSPAN)
#8 GA. SPLAY BRACE
WIRE IN FOUR DIRECTIONS
(NOT BY KINGSPAN)
8
4"
PHIL. PAN HEAD
BUTYL SEALANT
SEISMIC
BRACE PLATE
* CONTACT KINGSPAN TECHNICAL
SERVICES FOR SEISMIC BRACE PLATE
QUANTITY AND LOCATION
FOUR TIGHT
TURNS IN 112"
SEISMIC BRACE PLATE
CEILING TEE
CEILING TEE
ASSEMBLY
I
CE
G
LIN
E
TE
EXTERIOR SIDE OF PANEL MUST BE ON BOTTOM OF
CEILING. PANEL CUTLIST MUST MATCH THIS ORIENTATION
INTERIOR FACE OF PANEL
HEX NUT
ROUND WSHR
4" X 4" X 14 GA.
PLATE WASHER
WIRE TIE
ERECTOR MAY PRE-ASSEMBLE
HARDWARE ON 3 8" HANGAR RODSWIRE TIES HOLD WASHERS ABOVE
WORKING POINT
PROJECT ENGINEER OF RECORD
MUST VERIFY ROOF IS CAPABLE OF
SUPPORTING CEILING SYSTEM
LOADS AS WELL AS PROPER CEILING
TO ROOF CONNECTION DETAILS
LIC
E
T
LA
EP
NG
ILI
CE
TE
E
3
4"
PHIL. PAN HEAD
LOCATE FIRST HANGER
ROD AT LESS THAN 24"
FROM FACE OF PANEL
SEE DETAIL CS-CE-01-KSV
FOR ADD'L INFO.
OUTSIDE CORNER TRIM WITH
3
4" PHIL. PAN HEAD @ 12" OC.
(SEALANT OR VAPOR SEAL
TAPE AS REQUIRED)
CEILING TEE SPLICE PLATE W/
(4) 3 8" X 112" BOLTS, NUTS,
AND WASHERS
SP
SEISMIC BRACE PLATE (IF REQUIRED) TO BE LOCATED AT EVERY THIRD
ROD LOCATION IN LIEU OF PLATE WASHER (SEE DETAIL CS-CE-04-KSV).
CONTACT KINGSPAN TECHNICAL SERVICES FOR VERIFICATION.
KS SERIES - VERTICAL INSTALLATION
CEILING CHANNEL
ASSEMBLY
NUT
3
4"
MA
X.
PHIL. PAN HEAD
CEILING CHANNEL
SPLICE PLATE
0"
2'-
FIELD NOTCH END OF
CHANNEL TO REST ON
TOP OF WALL PANEL
9/16" DIA. HOLES PRE-PUNCHED FOR 3/8" OR ALL-THREAD ROD
AT 5'-0" O/C (DO NOT SPACE ALL-THREAD RODS FURTHER THAN 60"
APART. THE SPAN FROM WALL TO FIRST ROD, SHALL BE
NO GREATER THAN 24".)
INTERIOR FACE OF PANEL
EXTERIOR SIDE OF PANEL MUST BE ON BOTTOM OF
CEILING. PANEL CUTLIST MUST MATCH THIS ORIENTATION
WIRE TIE
4" X 4" X 14 GA.
PLATE WASHER
ROUND WSHR
ERECTOR MAY PRE-ASSEMBLE
HARDWARE ON 3/8" HANGER RODSWIRE TIES HOLD WASHERS
ABOVE WORKING POINT
PROJECT ENGINEER OF RECORD
MUST VERIFY ROOF IS CAPABLE OF
SUPPORTING CEILING SYSTEM
LOADS AS WELL AS PROPER CEILING
TO ROOF CONNECTION DETAILS
KS SERIES - VERTICAL INSTALLATION
KS SERIES - VERTICAL INSTALLATION
ATTIC ABOVE CEILING
MUST BE VENTILATED
3
4"
PHIL. PAN HEAD
BUTYL SEALANT
INSIDE CORNER TRIM
FIELD CUT THERMAL
BREAK
F.I.P. INSULATION
(NOT BY KINGSPAN)
EXPANSION FASTENER
CEILING
CONTINUOUS BUTYL
SEALANT AT "WARM"
SIDE PANEL JOINT
3
4"
PHIL. PAN HEAD
SUPPORT ANGLE
NOTE: CONTACT KINGSPAN TECHNICAL SERVICES FOR ENGINEERING ASSISTANCE
CEILING TO WALL LONGITUDINAL
KS SERIES - VERTICAL INSTALLATION
ATTIC ABOVE CEILING
MUST BE VENTILATED
3
8" GALVANIZED HANGER
ALL-THREAD ROD (ROD
SPACING TO BE DETERMINED)
(NOT BY KINGSPAN)
3
4"
PHIL. PAN HEAD
BUTYL SEALANT
INSIDE CORNER TRIM
FIELD CUT THERMAL
BREAK
1
4" MAX DISTANCE BETWEEN PANEL
EDGE AND THREAD ROD
F.I.P. INSULATION
(NOT BY KINGSPAN)
EXPANSION FASTENER
CEILING
3
4"
CONTINUOUS BUTYL
SEALANT AT "WARM"
SIDE PANEL JOINT
PHIL. PAN HEAD
16 GA. SUPPORT ANGLE
HEX NUT AND LOCK WASHER
NOTE: CONTACT KINGSPAN TECHNICAL SERVICES FOR ENGINEERING ASSISTANCE
CEILING TO WALL TRANSVERSE
KS SERIES - VERTICAL INSTALLATION
A
EXPANSION FASTENERS
AS REQUIRED
COMPRESSIBLE INSULATION
(NOT BY KINGSPAN)
SUPPORT ANGLE
(SET IN BUTYL SEALANT)
#10 X 13 8" TEK 1 FASTENER
AT EVERY PANEL JOINT
A
PARTITION TO ROOF
(PERPENDICULAR TO PURLIN)
FIELD FILL WITH
INSULATION
(NOT BY KINGSPAN)
FIELD NOTCH PANELS
AT PURLIN LOCATIONS
KINGSPAN TO SUPPLY FLAT-STOCK
SHEETING TO BE FIELD
FORMED FOR PANEL CLOSURES
COMPRESSIBLE INSULATION
(NOT BY KINGSPAN)
AA
PURLIN
CROSS SECTION
(SECTION VIEW -- TYPICAL AT EACH PURLIN)
PARTITION TO ROOF
KS SERIES - VERTICAL INSTALLATION
FILL VOIDS WITH
FOAM BLOCK, SET IN
BUTYL SEALANT
1/4"-14 STITCH TEKS
AT EACH PURLIN
PURLIN CLOSURE TRIM TO BE
FIELD CUT TO FIT AT PURLIN
FLANGES. USE SILICONE TO SEAL
ALL EDGES WHEN COMPLETE.
FIELD CUT PANELS
AS REQUIRED
1/4"-14 STITCH TEKS
AT EACH PURLIN
ATTACH PURLIN CLOSURES
W/ POP RIVETS
SUPPORT ANGLE
(SET IN BUTYL SEALANT)
COMPRESSIBLE INSULATION
(NOT BY KINGSPAN)
#10 X 13 8" TEK 1 FASTENER
AT EVERY PANEL JOINT
PARTITION TO ROOF (WITH FOAM BLOCKING)
(PERPENDICULAR TO PURLIN)
FIELD CUT
CONTINUOUS
THERMAL BREAK
(FREEZER ONLY)
COMPRESSIBLE INSULATION
(NOT BY KINGSPAN)
EXPANSION FASTENERS
AS REQUIRED
SUPPORT ANGLE
SET IN BUTYL SEALANT
#10 X 13 8" TEK 1 FASTENER
AT EVERY PANEL JOINT
PARTITION TO ROOF
(PARALLEL TO PURLIN)
PARTITION TO ROOF
WITH BLOCKING
KS SERIES - VERTICAL INSTALLATION
3"
P
N.
MI LA
M
I
TR
(2) BEADS
BUTYL SEALANT
3"
N. AP
I
L
M
IM
TR
TRIM END LAP
KS SERIES - VERTICAL INSTALLATION
FIELD NOTCH HEM(S)
AS REQUIRED
(NOT BY KINGSPAN)
3"
N. AP
I
L
M
IM
TR
(2) BEADS
BUTYL SEALANT
3"
N. AP
I
L
M
IM
TR
TRIM LAP WITH HEM
KS SERIES - VERTICAL INSTALLATION
(2) BEADS
BUTYL SEALANT
8" LONG LAP STRIP
1 "
. 4
M
NO AP
G
TRIM END LAP WITH
LAP STRIP
KS SERIES - VERTICAL INSTALLATION
NOTE: DETAIL SHOWN IS FOR GENERAL
USE ONLY (NOT FOR COOLER/FREEZER
APPLICATIONS).
FIELD NOTCH AND OVERLAP
TRIMS, POP RIVET AND SEAL AS
NECESSARY (NOT BY KINGSPAN)
FIELD MITER AND OVERLAP
TRIMS, POP RIVET AS
NECESSARY (NOT BY KINGSPAN)
SEALANT END DAM
2
INTERIOR HEAD TRIM
WITH TABS BENT DOWN
AD
IM
E
TH
A
R
PT
CA
D
EA
E
NT
I
OR
PT
CA
M
RI
H
AT
EXTERIOR CAP TRIM AT JAMB
R
O
RI
I
ER
T
EX
5
EXTERIOR HEAD TRIM W/
FIELD DRILL 3 8
(NOT BY KINGSPAN)
1
INTERIOR JAMB TRIM
6
EXPOSED SEALANT
(NOT BY KINGSPAN)
3
SILL TRIM WITH TABS
BENT UP
T
EX
R
4
EXTERIOR JAMB TRIM
FIELD CUT/NOTCH CAP
TRIM AT CORNERS TO
ALLOW FOR LAP
(NOT BY KINGSPAN)
RI
IO
ER
FIELD CUT/NOTCH CAP
TRIM AT CORNERS TO
ALLOW FOR LAP
(NOT BY KINGSPAN)
T
AP
M
L
SIL
T
A
C
TRIM LAP AT
FRAMED OPENING
FIELD MITER AND OVERLAP
TRIMS, POP RIVET AND SEAL AS
NECESSARY (NOT BY KINGSPAN)
TRIM INSTALLATION SEQUENCE:
1
INTERIOR JAMB TRIM
2
INTERIOR HEAD TRIM WITH TABS DOWN
3
SILL TRIM WITH TABS UP
4
EXTERIOR JAMB TRIM
5
EXTERIOR HEAD TRIM
6
EXTERIOR SEALANTS AS REQUIRED