ks series - vertical installation
Transcription
ks series - vertical installation
KS SERIES - VERTICAL INSTALLATION CS-DS-01-KSV CS-PJ-01-KSV CS-PJ-02-KSV CS-PJ-03-KSV CS-PJ-04-KSV CS-PJ-05-KSV CS-PJ-06-KSV CS-PJ-07-KSV CS-PJ-08-KSV CS-BS-01-KSV CS-BS-02-KSV CS-BS-03-KSV CS-BS-04-KSV CS-BS-05-KSV CS-BS-06-KSV CS-BS-07-KSV CS-BS-08-KSV CS-BS-09-KSV CS-BS-10-KSV CS-OC-01-KSV CS-OC-02-KSV CS-OC-03-KSV CS DISCLAIMER KS42SL EXPANDED PANEL JOINT KS42SL ENGAGED PANEL JOINT KS45SL EXPANDED PANEL JOINT KS45SL ENGAGED PANEL JOINT INTERMEDIATE SUPPORT INTERMEDIATE SUPPORT - SLIP CONNECTION LINER PANEL TO CONCRETE WITH SUPPORT LINER PANEL TO CONCRETE BASE DETAIL - INSULATED SLAB HEAVY GAUGE ANGLE BASE DETAIL - INSULATED SLAB LIGHT GAUGE Z BASE DETAIL - PARTITION W/ FLOOR INSULATION BASE DETAIL - INSULATED/NON-INSULATED BASE DETAIL - PART. W/ CURBS INSULATED BASE DETAIL - PART. NON-INSULATED BASE DETAIL - LINER PANEL BASE DETAIL - PART. W/ CURBS NON-INSULATED BASE DETAIL - PART. W/ CURBS (ALTERNATE) PARTITION BASE ON TOP OF CURB OUTSIDE CORNER - FLUSH TRIM OUTSIDE CORNER AT PARTITION OUTSIDE CORNER LINER PANEL AT CONC WALL INDEX SHEET KS SERIES - VERTICAL INSTALLATION CS-IC-01-KSV CS-IC-02-KSV CS-FO-01-KSV CS-FO-02-KSV CS-ST-01-KSV CS-RK-01-KSV CS-RK-02-KSV CS-EV-01-KSV CS-CE-01-KSV CS-CE-02-KSV CS-CE-03-KSV CS-CE-04-KSV CS-CE-05-KSV CS-CE-06-KSV CS-CE-07-KSV CS-CE-08-KSV CS-CE-09-KSV CS-CE-10-KSV CS-TL-01-KSV CS-TL-02-KSV CS-TL-03-KSV CS-TL-04-KSV INSIDE CORNER - FLUSH TRIM PARTITION TO EXTERIOR WALL HEADER CONDITION JAMB CONDITION STACK JOINT RAKE RAKE W/ MEMBRANE ROOF LOW EAVE INTERIOR WALL TO CEILING INTERIOR WALL TO CEILING - 'T' SECTION CEILING CHANNEL CEILING TEE CEILING TEE ASSEMBLY CEILING CHANNEL ASSEMBLY CEILING TO WALL - LONGITUDINAL CEILING TO WALL - TRANSVERSE PARTITION TO ROOF PARTITION TO ROOF WITH BLOCKING TRIM END LAP TRIM LAP WITH HEM TRIM END LAP WITH LAP STRIP TRIM LAP AT FRAMED OPENING INDEX SHEET KS SERIES - VERTICAL INSTALLATION DISCLAIMERS: THESE DETAILS ARE PROVIDED AS A GUIDELINE FOR PROPER PANEL AND ASSOCIATED COMPONENT INSTALLATION, AND ARE BASED ON INDUSTRY ACCEPTED PRACTICES. REFRIGERATION EQUIPMENT IN COMBINATION WITH THE TEMPERATURE DIFFERENTIAL BETWEEN BUILDING EXTERIOR AND INTERIOR CAN CREATE NEGATIVE AIR PRESSURE WITHIN THE BUILDING (WARM AIR FROM OUTSIDE THE BUILDING IS DRAWN INTO THE BUILDING THROUGH AIR LEAKS IN THE BUILDING ENVELOPE). AS A RESULT, VAPOR SEALS ARE OF PRIMARY CONCERN TO PROPER COLD STORAGE PERFORMANCE. IN GENERAL, COLD STORAGE FACILITIES REQUIRE THE PRIMARY VAPOR BARRIER TO BE ON THE EXTERIOR (I.E. "WARM" SIDE), RATHER THAN INTERIOR SIDE OF THE PANEL. PROJECTS LOCATED IN AREAS SUBJECT TO EXTREME COLD AND/OR HIGH SNOW LOADS MAY REQUIRE MODIFICATIONS TO THESE DETAILS - CONTACT KINGSPAN TECHNICAL SERVICES FOR SPECIFIC PROJECT RECOMMENDATIONS. ALL STRUCTURAL SUPPORTS ARE NOT BY KINGSPAN AND ARE SHOWN FOR CLARIFICATION AND ILLUSTRATION PURPOSES ONLY. CONTACT KINGSPAN TECHNICAL SERVICES FOR MAXIMUM ALLOWABLE PANEL SPANS AND FASTENING PATTERNS. ALL SEALANTS TO BE COMPATIBLE WITH VAPOR BARRIERS AS SHOWN COLD STORAGE DISCLAIMER KS SERIES - VERTICAL INSTALLATION SHADOWLINE INTERIOR FACE KS42SL 2" - 6" EXTERIOR FACE SHADOWLINE 42" COVERAGE (36", 30", & 24" OPTIONAL) HORIZONTAL SUPPORT MALE LEG COLD SIDE "WARM" SIDE 12 GA. STAINLESS STEEL HIDDEN FASTENER CLIP (1 PER PANEL, PER SUPPORT) SET CLIP IN BUTYL SEALANT FEMALE POCKET OPTIONAL BUTYL (RECOMMENDED FOR WASHDOWN APPLICATIONS) CONTINUOUS BUTYL SEALANT (AT "WARM" SIDE JOINT) 1 4" - 14 HEX HEAD FASTENERS WITHOUT WASHER WALL PANEL INSTALLATION DIRECTION NOTE: FILL FEMALE POCKET(S) 3/4 FULL WITH SEALANT TO PROVIDE PROPER AIR/WATER SEAL KS42SL EXPANDED JOINT KS SERIES - VERTICAL INSTALLATION HORIZONTAL SUPPORT MALE JOINT FEMALE JOINT COLD SIDE "WARM" SIDE PANEL MODULE 1 " 8 12 GA. STAINLESS STEEL HIDDEN FASTENER CLIP (1 PER PANEL, PER SUPPORT) SET CLIP IN BUTYL SEALANT 1 4" - 14 HEX HEAD FASTENERS WITHOUT WASHER WALL PANEL INSTALLATION DIRECTION KS42SL ENGAGED JOINT OPTIONAL BUTYL (RECOMMENDED FOR WASHDOWN APPLICATIONS) CONTINUOUS BUTYL SEALANT (AT "WARM" SIDE JOINT) KS SERIES - VERTICAL INSTALLATION SHADOWLINE INTERIOR FACE KS45SL EXTERIOR FACE 2"-6" SHADOWLINE 45.378" COVERAGE OPTIONAL BUTYL (RECOMMENDED FOR WASHDOWN APPLICATIONS) COLD SIDE FEMALE POCKET MALE LEG "WARM" SIDE CONTINUOUS BUTYL SEALANT (AT "WARM" SIDE JOINT) WALL PANEL INSTALLATION DIRECTION NOTE: FILL FEMALE POCKET(S) 3/4 FULL WITH SEALANT TO PROVIDE PROPER AIR/WATER SEAL KS45SL EXPANDED JOINT KS SERIES - VERTICAL INSTALLATION OPTIONAL BUTYL (RECOMMENDED FOR WASHDOWN APPLICATIONS) COLD SIDE CONTINUOUS BUTYL SEALANT (AT "WARM" SIDE JOINT) "WARM" SIDE WALL PANEL INSTALLATION DIRECTION KS45SL ENGAGED JOINT KS SERIES - VERTICAL INSTALLATION INTERIOR OF BUILDING EXTERIOR OF BUILDING OPTIONAL BUTYL (RECOMMENDED FOR WASHDOWN APPLICATIONS) CONTINUOUS BUTYL SEALANT AT "WARM" SIDE PANEL JOINT 1 4" - 14 HEX HEAD FASTENERS WITHOUT WASHER 12 GA. STAINLESS STEEL HIDDEN FASTENER CLIP (1 PER PANEL, PER SUPPORT) SET CLIP IN BUTYL SEALANT COLD SIDE 3 4" 1 " 2 4 1" 5 "WARM" SIDE 16 STANDARD: 12 GA. STAINLESS STEEL TWO-HOLE HIDDEN FASTENER CLIP 5 16 OPTIONAL: 12 GA. STAINLESS STEEL ONE-HOLE HIDDEN FASTENER CLIP NOTE: CONTACT KINGSPAN TECHNICAL SERVICES FOR SPECIFIC PROJECT RECOMMENDATIONS INTERMEDIATE SUPPORT 3 4" 1 " 2 4 KS SERIES - VERTICAL INSTALLATION 12 GA. STAINLESS STEEL HIDDEN FASTENER CLIP (1 PER PANEL, PER SUPPORT) WARM SIDE COLD SIDE LOW PROFILE BOLT W/ WASHER AND LOCK NUT OFFSET BEAM CLIP 12 GA. STAINLESS STEEL HIDDEN FASTENER CLIP (1 PER PANEL, PER SUPPORT) WARM SIDE COLD SIDE LOW PROFILE BOLT W/ WASHER AND LOCK NUT OFFSET BEAM CLIP NOTE: BEAM CLIP TO ALLOW STRUCTURAL STEEL TO DEFLECT W/O PUTTING VERTICAL LOAD INTO WALL PANEL. CONTACT KINGSPAN TECHNICAL SERVICES FOR ADDITIONAL INFO INTERMEDIATE SUPPORT - SLIP CONNECTION KS SERIES - VERTICAL INSTALLATION INTERIOR OF BUILDING CONTINUOUS BUTYL SEALANT AT "WARM" SIDE PANEL JOINT SHIM AS NECESSARY 1 4" - 14 HEX HEAD FASTENERS CONCRETE/MASONRY WALL (NOT BY KINGSPAN) "WARM" SIDE 12 GA. STAINLESS STEEL HIDDEN FASTENER CLIP (1 PER PANEL, PER SUPPORT) HAT CHANNEL & FASTENING (NOT BY KINGSPAN) COLD SIDE OPTIONAL BUTYL (RECOMMENDED FOR WASHDOWN APPLICATIONS) 3 4" 1 " 2 4 1" 5 16 STANDARD: 12 GA. STAINLESS STEEL TWO-HOLE HIDDEN FASTENER CLIP 5 16 OPTIONAL: 12 GA. STAINLESS STEEL ONE-HOLE HIDDEN FASTENER CLIP NOTE: CONTACT KINGSPAN TECHNICAL SERVICES FOR SPECIFIC PROJECT RECOMMENDATIONS LINER PANEL TO CONCRETE WITH SUPPORT 3 4" 1 " 2 4 KS SERIES - VERTICAL INSTALLATION INTERIOR OF BUILDING CONTINUOUS BUTYL SEALANT AT "WARM" SIDE PANEL JOINT FASTENERS TO MASONRY (NOT BY KINGSPAN) CONCRETE/MASONRY WALL (NOT BY KINGSPAN) 12 GA. STAINLESS STEEL HIDDEN FASTENER CLIP (1 PER PANEL, PER SUPPORT) SLIP SHEET TO PROTECT PANELS (NOT BY KINGSPAN) "WARM" SIDE COLD SIDE OPTIONAL BUTYL (RECOMMENDED FOR WASHDOWN APPLICATIONS) 3 4" 1 " 2 4 1" 5 16 STANDARD: 12 GA. STAINLESS STEEL TWO-HOLE HIDDEN FASTENER CLIP 5 16 OPTIONAL: 12 GA. STAINLESS STEEL ONE-HOLE HIDDEN FASTENER CLIP NOTE: CONTACT KINGSPAN TECHNICAL SERVICES FOR SPECIFIC PROJECT RECOMMENDATIONS LINER PANEL TO CONCRETE 3 4" 1 " 2 4 KS SERIES - VERTICAL INSTALLATION SEALANT (OPTIONAL NOT BY KINGSPAN) (INSTALL AFTER TEMP. PULL DOWN ) "Z" TRIM "WARM" SIDE 2 BEADS OF BUTYL SEALANT ON EACH SIDE SLIP SHEET TO PROTECT PANELS (NOT BY KINGSPAN) F.I.P INSULATION (NOT BY KINGSPAN) "Z" TRIM FIELD CUT THERMAL BREAK LAP TRIM 3" N. MI RIM T P LA 1 4" - 14 HEX HEAD FASTENERS WITHOUT WASHER CONCRETE CURB (NOT BY KINGSPAN) 12 GA. STAINLESS STEEL HIDDEN FASTENER CLIP (1 PER PANEL, PER SUPPORT) SET CLIP IN BUTYL SEALANT SET PANEL IN CONT. HEAVY BEAD BUTYL SEALANT W/ MARRIAGE BEAD TO EXT. PANEL JOINT COLD SIDE CONCRETE SLAB (NOT BY KINGSPAN) BASE TRIM POP RIVETS CONTINUOUS "Z" TRIM SET IN BUTYL SEALANT (SEE LAP TRIM ABOVE FOR "Z" TRIM) HEAVY GA. BASE ANGLE (NOT BY KINGSPAN) FLOOR INSULATION (NOT BY KINGSPAN) SUB SLAB (NOT BY KINGSPAN) CONTINUOUS HEAVY BEAD OF BUTYL SEALANT FASTENER TO CONCRETE (NOT BY KINGSPAN) VAPOR BARRIER (NOT BY KINGSPAN) NOTES: 1) BASE ANGLE MUST BE FASTENED SECURELY TO SLAB TO RESIST LATERAL LOAD APPLIED BY PANEL 2) BASE ANGLE GAUGE TO BE DETERMINED BY PROJECT ENGINEER OF RECORD 3) FLOOR INSULATION REQUIRED FOR FREEZER APPLICATIONS BASE DETAIL INSULATED SLAB HEAVY GAUGE ANGLE KS SERIES - VERTICAL INSTALLATION SEALANT (OPTIONAL NOT BY KINGSPAN) (INSTALL AFTER TEMP. PULL DOWN ) LAP TRIM 2 BEADS OF BUTYL SEALANT ON EACH SIDE SLIP SHEET TO PROTECT PANELS (NOT BY KINGSPAN) F.I.P INSULATION (NOT BY KINGSPAN) 3" D " 3 EN P D A EN P L LA "Z" ANGLE LAP TRIM FIELD CUT THERMAL BREAK 1 4" - 14 HEX HEAD FASTENERS WITHOUT WASHER CONCRETE CURB (NOT BY KINGSPAN) 12 GA. STAINLESS STEEL HIDDEN FASTENER CLIP (1 PER PANEL, PER SUPPORT) SET CLIP IN BUTYL SEALANT SET PANEL IN CONT. HEAVY BEAD BUTYL SEALANT W/ MARRIAGE BEAD TO EXT. PANEL JOINT COLD SIDE CONCRETE SLAB (NOT BY KINGSPAN) BASE TRIM POP RIVETS "Z" SHAPED BASE ANGLE (NOT BY KINGSPAN) FLOOR INSULATION (NOT BY KINGSPAN) "WARM" SIDE SUB SLAB (NOT BY KINGSPAN) CONTINUOUS HEAVY BEAD OF BUTYL SEALANT FASTENER TO CONCRETE (NOT BY KINGSPAN) VAPOR BARRIER (NOT BY KINGSPAN) SEE LAP TRIM ABOVE FOR "Z" BASE ANGLE NOTES: 1) BASE ANGLE MUST BE FASTENED SECURELY TO SLAB TO RESIST LATERAL LOAD APPLIED BY PANEL 2) Z SHAPED BASE ANGLE GAUGE TO BE DETERMINED BY PROJECT ENGINEER OF RECORD 3) FLOOR INSULATION REQUIRED FOR FREEZER APPLICATIONS BASE DETAIL INSULATED SLAB LIGHT GAUGE Z KS SERIES - VERTICAL INSTALLATION COLD SIDE OPTIONAL BUTYL (RECOMMENDED FOR WASHDOWN APPLICATIONS) "WARM" SIDE CONTINUOUS BUTYL SEALANT AT "WARM" SIDE PANEL JOINT SEALANT (OPTIONAL - NOT BY KINGSPAN) (INSTALL AFTER TEMP. PULL DOWN ) CONTINUOUS BUTYL SEALANT WITH MARRIAGE BEAD TO SEALANT AT "WARM" SIDE PANEL JOINT 3 3 4" PHIL. PAN HEAD MIN. 16 GA. GALVANIZED BASE ANGLE FASTENER TO CONCRETE (NOT BY KINGSPAN) CONCRETE SLAB (NOT BY KINGSPAN) 4" PHIL. PAN HEAD MIN. 16 GA. GALVANIZED BASE ANGLE FASTENER TO CONCRETE (NOT BY KINGSPAN) BUTYL SEALANT BUTYL SEALANT (OPTIONAL) FLOOR INSULATION (NOT BY KINGSPAN) BASE DETAIL PARTITION W/ FLOOR INSULATION VAPOR BARRIER (NOT BY KINGSPAN) KS SERIES - VERTICAL INSTALLATION OPTIONAL BUTYL (RECOMMENDED FOR WASHDOWN APPLICATIONS) CONTINUOUS BUTYL SEALANT AT "WARM" SIDE PANEL JOINT "WARM" SIDE COLD SIDE SEALANT (OPTIONAL - NOT BY KINGSPAN) (INSTALL AFTER TEMP. PULL DOWN ) SLIP SHEET TO PROTECT PANELS (NOT BY KINGSPAN) CONCRETE CURB (NOT BY KINGSPAN) CONCRETE CURB (NOT BY KINGSPAN) F.I.P INSULATION (NOT BY KINGSPAN) CONCRETE SLAB (NOT BY KINGSPAN) FIELD CUT THERMAL BREAK FINISH FLOOR SET PANEL IN CONT. HEAVY BEAD BUTYL SEALANT W/ MARRIAGE BEAD TO EXT. PANEL JOINT STAGGERED FLOOR INSULATION (NOT BY KINGSPAN) BASE CHANNEL (NOT BY KINGSPAN) SUB SLAB (NOT BY KINGSPAN) CONTINUOUS HEAVY BEAD OF BUTYL SEALANT FASTENER TO CONCRETE (NOT BY KINGSPAN) VAPOR BARRIER (NOT BY KINGSPAN) NOTES: 1) BASE CHANNEL MUST BE FASTENED SECURELY TO SLAB 2) ANGLE IRON MAY BE USED IN LIEU OF CHANNEL BASE DETAIL INSULATED/ NON-INSULATED FLOOR KS SERIES - VERTICAL INSTALLATION COLD SIDE "WARM" SIDE OPTIONAL BUTYL (RECOMMENDED FOR WASHDOWN APPLICATIONS) SEALANT (OPTIONAL - NOT BY KINGSPAN) (INSTALL AFTER TEMP. PULL DOWN) 12 GA. STAINLESS STEEL HIDDEN FASTENER CLIP (1 PER PANEL, PER SUPPORT) SET CLIP IN BUTYL SEALANT CONTINUOUS BUTYL SEALANT AT "WARM" SIDE PANEL JOINT 1 4" - 14 HEX HEAD FASTENERS WITHOUT WASHER ABUSE CURB (NOT BY KINGSPAN - CAN BE POURED AFTER PANEL INSTALLATION) SLIP SHEET TO PROTECT PANELS (NOT BY KINGSPAN) BUTYL SEALANT BUTYL SEALANT MIN. 16 GA. GALVANIZED BASE ANGLE FASTENER TO CONCRETE (NOT BY KINGSPAN) FLOOR INSULATION (NOT BY KINGSPAN) SEALANT MARRIAGE BEAD TO VERTICAL PANEL JOINT VAPOR BARRIER (NOT BY KINGSPAN) BASE DETAIL PARTITION W/ CURBS INSULATED FLOOR KS SERIES - VERTICAL INSTALLATION CONTINUOUS BUTYL SEALANT AT "WARM" SIDE PANEL JOINT "WARM" SIDE OPTIONAL BUTYL (RECOMMENDED FOR WASHDOWN APPLICATIONS) COLD SIDE SEALANT (OPTIONAL - NOT BY KINGSPAN) (INSTALL AFTER TEMP. PULL DOWN) 3 4" PHIL. PAN HEAD BUTYL SEALANT SEALANT MARRIAGE BEAD TO VERTICAL PANEL JOINT BUTYL SEALANT (OPTIONAL) BASE DETAIL PARTITION NON-INSULATED FLOOR MIN. 16 GA. GALVANIZED BASE ANGLE FASTENER TO CONCRETE (NOT BY KINGSPAN) KS SERIES - VERTICAL INSTALLATION OPTIONAL BUTYL (RECOMMENDED FOR WASHDOWN APPLICATIONS) 3 4" PHIL. PAN HEAD BASE TRIM "WARM" SIDE CONTINUOUS BUTYL SEALANT AT "WARM" SIDE PANEL JOINT 12 GA. STAINLESS STEEL HIDDEN FASTENER CLIP (1 PER PANEL, PER SUPPORT) SET CLIP IN BUTYL SEALANT 1 4" - 14 HEX HEAD FASTENERS WITHOUT WASHER MIN. 16 GA. GALVANIZED BASE ANGLE BUTYL SEALANT SEALANT (OPTIONAL - NOT BY KINGSPAN) (INSTALL AFTER TEMP. PULL DOWN - SEE SCHEDULE) EXISTING EXTERIOR WALL (NOT BY KINGSPAN) COLD SIDE BUTYL SEALANT (OPTIONAL) SEALANT MARRIAGE BEAD TO VERTICAL PANEL JOINT BASE DETAIL - LINER PANEL FASTENER TO CONCRETE (NOT BY KINGSPAN) KS SERIES - VERTICAL INSTALLATION CONTINUOUS BUTYL SEALANT AT "WARM" SIDE PANEL JOINT SEALANT (OPTIONAL - NOT BY KINGSPAN) (INSTALL AFTER TEMP. PULL DOWN) VAPOR BARRIER (NOT BY KINGSPAN) 3 4" "WARM" SIDE OPTIONAL BUTYL (RECOMMENDED FOR WASHDOWN APPLICATIONS) COLD SIDE ABUSE CURB (NOT BY KINGSPAN - CAN BE POURED AFTER PANEL INSTALLATION) PHIL. PAN HEAD BUTYL SEALANT W/ MARRIAGE BEAD SLIP SHEET TO PROTECT PANELS (NOT BY KINGSPAN) BUTYL SEALANT BUTYL SEALANT MIN. 16 GA. GALVANIZED BASE CHANNEL FASTENER TO CONCRETE (NOT BY KINGSPAN) BASE DETAIL PARTITION W/ CURBS (NON-INSULATED FLOOR) KS SERIES - VERTICAL INSTALLATION COLD SIDE "WARM" SIDE OPTIONAL BUTYL (RECOMMENDED FOR WASHDOWN APPLICATIONS) SEALANT (OPTIONAL - NOT BY KINGSPAN) (INSTALL AFTER TEMP. PULL DOWN - SEE SCHEDULE) 12 GA. STAINLESS STEEL HIDDEN FASTENER CLIP (1 PER PANEL, PER SUPPORT) SET CLIP IN BUTYL SEALANT SLIP SHEET TO PROTECT PANELS (NOT BY KINGSPAN) CONTINUOUS BUTYL SEALANT AT "WARM" SIDE PANEL JOINT 1 4" - 14 HEX HEAD FASTENERS WITHOUT WASHER ABUSE CURB (NOT BY KINGSPAN - CAN BE POURED AFTER PANEL INSTALLATION) VAPOR BARRIER (NOT BY KINGSPAN) BUTYL SEALANT BUTYL SEALANT MIN. 16 GA. GALVANIZED BASE ANGLE FASTENER TO CONCRETE (NOT BY KINGSPAN) SEALANT MARRIAGE BEAD TO VERTICAL PANEL JOINT BASE DETAIL PARTITION W/ CURBS (ALTERNATE) KS SERIES - VERTICAL INSTALLATION CONTINUOUS BUTYL SEALANT AT "WARM" SIDE PANEL JOINT BUTYL SEALANT 3 4" PHIL. PAN HEAD MIN. 16 GA. GALVANIZED BASE CHANNEL OPTIONAL BUTYL (RECOMMENDED FOR WASHDOWN APPLICATIONS) SEALANT (OPTIONAL - NOT BY KINGSPAN) (INSTALL AFTER TEMP. PULL DOWN) BUTYL SEALANT FASTENER TO CONC. (NOT BY KINGSPAN) CONTINUOUS BUTYL SEALANT AT "WARM" SIDE PANEL JOINT OPTIONAL BUTYL (RECOMMENDED FOR WASHDOWN APPLICATIONS) 3 SEALANT (OPTIONAL - NOT BY KINGSPAN) (INSTALL AFTER TEMP. PULL DOWN) 4" PHIL. PAN HEAD MIN. 16 GA. GALVANIZED BASE ANGLE MIN. 16 GA. GALVANIZED BASE ANGLE BUTYL SEALANT BUTYL SEALANT FASTENER TO CONC. (NOT BY KINGSPAN) PARTITION BASE ON TOP OF CURB KS SERIES - VERTICAL INSTALLATION WILL VARY WITH FIELD CONDITION WILL VARY WITH FIELD CONDITION FIELD CUT MIN. 1 4" GAP FOR F.I.P. INSTALLATION FIELD CUT THERMAL BREAK F.I.P. INSULATION (NOT BY KINGSPAN) "WARM" SIDE OUTSIDE CORNER TRIM SELF-ADHERING VAPOR BARRIER (AT "WARM" SIDE NOT BY KINGSPAN) 1 4" - 14 "LOW PROFILE" THROUGH FASTENER 3 4" PHIL. PAN HEAD INSIDE CORNER TRIM POP RIVETS COLD SIDE HORIZONTAL SUPPORT OUTSIDE CORNER FLUSH TRIM KS SERIES - VERTICAL INSTALLATION WILL VARY WITH FIELD CONDITION WILL VARY WITH FIELD CONDITION FIELD CUT MIN. 1 4" GAP FOR F.I.P. INSTALLATION FIELD CUT THERMAL BREAK F.I.P. INSULATION (NOT BY KINGSPAN) OUTSIDE CORNER TRIM SELF-ADHERING VAPOR BARRIER (AT "WARM" SIDE NOT BY KINGSPAN) 3 4" PHIL. PAN HEAD INSIDE CORNER TRIM 3 4" PHIL. PAN HEAD OUTSIDE CORNER AT PARTITION KS SERIES - VERTICAL INSTALLATION FASTENER TO CONCRETE (NOT BY KINGSPAN) OUTSIDE CORNER TRIM (PRE-INSTALL) TRANS FLASHING SELF-ADHERING VAPOR BARRIER (AT "WARM" SIDE NOT BY KINGSPAN) INSIDE CORNER TRIM FIELD CUT THERMAL BREAK 3 F.I.P. INSULATION (NOT BY KINGSPAN) OUTSIDE CORNER LINER PANEL AT CONC WALL 4" PHIL. PAN HEAD KS SERIES - VERTICAL INSTALLATION WILL VARY WITH FIELD CONDITION WILL VARY WITH FIELD CONDITION 3 4" FIELD CUT PHIL. PAN HEAD COLD SIDE OUTSIDE CORNER TRIM FIELD CUT THERMAL BREAK F.I.P. INSULATION (NOT BY KINGSPAN) MIN. 1 4" GAP FOR F.I.P. INSTALLATION "WARM" SIDE POP RIVETS HORIZONTAL SUPPORT SELF-ADHERING VAPOR BARRIER (NOT BY KINGSPAN) INSIDE CORNER TRIM 1 4" - 14 "LOW PROFILE" THROUGH FASTENER INSIDE CORNER FLUSH TRIM KS SERIES - VERTICAL INSTALLATION INTERIOR "WARM" SIDE 3 4" PHIL. PAN HEAD EXTERIOR SELF-ADHERING VAPOR BARRIER (NOT BY KINGSPAN) FIELD CUT THERMAL BREAK INSIDE CORNER TRIM INTERIOR PARTITION F.I.P. INSULATION (NOT BY KINGSPAN) OPTIONAL BUTYL AT WASH DOWN EXPANSION FASTENER (TO BE LOCATED ON OPPOSITE SIDE OF THERMAL CUT FROM PANEL'S LEADING EDGE) INSIDE CORNER TRIM 3 4" PHIL. PAN HEAD STRUCTURAL SUPPORT INTERIOR COLD SIDE NOTES: 1) ADDITIONAL FASTENERS MAY BE REQUIRED ON EITHER SIDE OF THE FIELD CUT THERMAL BREAK BASED UPON ACTUAL DESIGN LOADS AND THERMAL REQUIREMENTS FIELD FILL WITH INSULATION (NOT BY KINGSPAN) INSULATE SUPPORTING STEEL ON "WARM" SIDE OF PARTITION (APPROX. 4'-0") FIELD NOTCH PANELS AT GIRT LOCATIONS GIRT CAP TRIM (NOT BY KINGSPAN) PARTITION TO EXTERIOR WALL KS SERIES - VERTICAL INSTALLATION OPTIONAL BUTYL (RECOMMENDED FOR WASHDOWN APPLICATIONS) CONTINUOUS BUTYL SEALANT AT "WARM" SIDE PANEL JOINT COLD SIDE SEALANT (OPTIONAL - NOT BY KINGSPAN) (INSTALL AFTER TEMP. PULL DOWN ) SELF ADHERING VAPOR BARRIER (OPTIONAL - NOT BY KINGSPAN) HEADER CONDITION "WARM" SIDE FREEZER DOOR CASING, FASTENERS, SEALANT, & REQUIRED SUPPORT (NOT BY KINGSPAN) CONTINUOUS BUTYL SEALANT WITH MARRIAGE BEAD TO SEALANT AT "WARM" SIDE PANEL JOINT KS SERIES - VERTICAL INSTALLATION SEALANT (OPTIONAL - NOT BY KINGSPAN) (INSTALL AFTER TEMP. PULL DOWN ) COLD SIDE "WARM" SIDE SELF ADHERING VAPOR BARRIER (OPTIONAL - NOT BY KINGSPAN) FREEZER DOOR CASING, FASTENERS, SEALANT, & REQUIRED SUPPORT (NOT BY KINGSPAN) CONTINUOUS BUTYL SEALANT JAMB CONDITION KS SERIES - VERTICAL INSTALLATION "WARM" SIDE COLD SIDE FIELD ROUT PANELS FOR WOOD SPLINE BASE TRIM WITH POP RIVETS (PRE-INSTALL WEEP HOLES) CONTINUOUS BUTYL SEALANT STACK JOINT TRIM WITH POP RIVETS FIR SPLINE (NOT BY KINGSPAN) SET FIR SPLINE IN BUTYL SEALANT CONTINUOUS BUTYL SEALANT MARRIED TO SEALANT IN PANEL JOINT CONTINUOUS BUTYL SEALANT AT "WARM" SIDE PANEL JOINT HORIZONTAL SUPPORT (NOT BY KINGSPAN) 14 GA. GALVANIZED HIDDEN CLIP (1 PER PANEL, PER GIRT) NOTES: 1) SEE DETAIL CS-TL-01-KSV AND CS-TL-02-KSV FOR PROPER TRIM LAP DETAILS 2) CONTACT KINGSPAN TECHNICAL SERVICES FOR PROPER PANEL FASTENING REQUIREMENTS STACK JOINT KS SERIES - VERTICAL INSTALLATION GALVANIZED CAP FLASHING (NOT BY KINGSPAN) ROOF MEMBRANE SYSTEM ATTACHMENT (NOT BY KINGSPAN) ROOF MEMBRANE (NOT BY KINGSPAN) ROOF MEMBRANE SYSTEM ATTACHMENT (NOT BY KINGSPAN) SEALANT MARRIAGE BEAD TO VERTICAL PANEL JOINT RAKE TRIM, FASTENERS, SEALANT AND WEATHER TIGHTNESS (NOT BY KINGSPAN) BOARD INSULATION AND ROOF UNDERLAYMENT (NOT BY KINGSPAN) "WARM" SIDE FIELD CUT THERMAL BREAK 1 SHEETING OR RAKE ANGLE REQUIRED (NOT BY KINGSPAN) F.I.P. INSULATION (NOT BY KINGSPAN) COLD SIDE OPTIONAL BUTYL (RECOMMENDED FOR WASHDOWN APPLICATIONS) RAKE 4" - 14 HEX HEAD FASTENERS WITHOUT WASHER 12 GA. STAINLESS STEEL HIDDEN FASTENER CLIP (1 PER PANEL, PER SUPPORT) SET CLIP IN BUTYL SEALANT CONTINUOUS BUTYL SEALANT AT "WARM" SIDE PANEL JOINT KS SERIES - VERTICAL INSTALLATION GALVANIZED CAP FLASHING (NOT BY KINGSPAN) ROOF MEMBRANE (NOT BY KINGSPAN) ROOF MEMBRANE SYSTEM ATTACHMENT (NOT BY KINGSPAN) CONT. HEAVY BEAD BUTYL SEALANT W/ MARRIAGE BEAD TO EXT. PANEL JOINT RAKE TRIM, FASTENERS, SEALANT AND WEATHER TIGHTNESS (NOT BY KINGSPAN) INSULATION AND ROOF UNDERLAYMENT (NOT BY KINGSPAN) FASTENER (NOT BY KINGSPAN) "WARM" SIDE SEALANT TO MEMBRANE (NOT BY KINGSPAN) FIELD CUT THERMAL BREAK F.I.P. INSULATION (NOT BY KINGSPAN) SHEETING OR RAKE ANGLE REQUIRED (NOT BY KINGSPAN) COLD SIDE OPTIONAL BUTYL (RECOMMENDED FOR WASHDOWN APPLICATIONS) RAKE W/ MEMBRANE ROOF 1 4" - 14 HEX HEAD FASTENERS WITHOUT WASHER 12 GA. STAINLESS STEEL HIDDEN FASTENER CLIP (1 PER PANEL, PER SUPPORT) SET CLIP IN BUTYL SEALANT KS SERIES - VERTICAL INSTALLATION F.I.P. INSULATION (NOT BY KINGSPAN) GALVANIZED CAP FLASHING (NOT BY KINGSPAN) ROOF MEMBRANE (NOT BY KINGSPAN) ROOF MEMBRANE SYSTEM ATTACHMENT (NOT BY KINGSPAN) CONT. HEAVY BEAD BUTYL SEALANT W/ MARRIAGE BEAD TO EXT. PANEL JOINT RAKE TRIM, FASTENERS, SEALANT AND WEATHER TIGHTNESS (NOT BY KINGSPAN) INSULATION AND ROOF UNDERLAYMENT (NOT BY KINGSPAN) "WARM" SIDE SEALANT TO MEMBRANE (NOT BY KINGSPAN) FASTENER (NOT BY KINGSPAN) FIELD CUT THERMAL BREAK 1 EAVE STRUT (NOT BY KINGSPAN) COLD SIDE OPTIONAL BUTYL (RECOMMENDED FOR WASHDOWN APPLICATIONS) LOW EAVE 4" - 14 HEX HEAD FASTENERS WITHOUT WASHER 12 GA. STAINLESS STEEL HIDDEN FASTENER CLIP (1 PER PANEL, PER SUPPORT) SET CLIP IN BUTYL SEALANT CONTINUOUS BUTYL SEALANT AT "WARM" SIDE PANEL JOINT KS SERIES - VERTICAL INSTALLATION SEE CS-CE-04-KSV FOR ADDITIONAL INFO ATTIC ABOVE CEILING MUST BE VENTILATED FIELD CUT THERMAL BREAK F.I.P. INSULATION (NOT BY KINGSPAN) OUTSIDE CORNER TRIM CEILING SELF ADHERING VAPOR BARRIER (NOT BY KINGSPAN) COLD SIDE "WARM" SIDE 3 WALL 3 4" 4" PHIL. PAN HEAD INSIDE CORNER TRIM PHIL. PAN HEAD CONTINUOUS BUTYL SEALANT AT "WARM" SIDE PANEL JOINT INTERIOR WALL TO CEILING KS SERIES - VERTICAL INSTALLATION #10 X 13 8" FASTENER AT EVERY PANEL JOINT BOTH SIDES OF PANEL AA CROSS SECTION (SECTION VIEW ) FIELD CUT THERMAL BREAK CEILING BUTYL SEALANT SUPPORT ANGLE COMPRESSIBLE INSULATION (NOT BY KINGSPAN) EXPANSION FASTENER A WALL A BUTYL SEALANT #10 X 13 8" TEK 1 FASTENER AT EVERY PANEL JOINT (SEE DETAIL ABOVE) WALL TO CEILING INTERSECTION KS SERIES - VERTICAL INSTALLATION INSULATE HANGER RODS AS REQUIRED (NOT BY KINGSPAN) ATTIC ABOVE CEILING MUST BE VENTILATED HEX NUT AND LOCK WASHER 3 8" GALVANIZED HANGER ALL-THREAD ROD (ROD SPACING TO BE DETERMINED) (NOT BY KINGSPAN) 4" X 4" X 14 GA. PLATE WASHER* SELF ADHERING VAPOR BARRIER (NOT BY KINGSPAN) TRANSITION FLASHING 3 4" PHIL. PAN HEAD INTERIOR FACE OF PANEL CEILING 3 4" CEILING EXTERIOR SIDE OF PANEL MUST BE ON BOTTOM OF CEILING. PANEL CUTLIST MUST MATCH THIS ORIENTATION PHIL. PAN HEAD FILL 12" GAP BETWEEN PANEL WITH F.I.P. INSULATION (NOT BY KINGSPAN) 1 12" X 6" X 14 GA. GALVANIZED CEILING CHANNEL (WHITE POWDER COAT - OPTIONAL) (CAP TRIM - OPTIONAL) HEX NUT AND LOCK WASHER 3 #8 GA. SPLAY BRACE WIRE IN FOUR DIRECTIONS (NOT BY KINGSPAN) 3 8" ALL-THREAD HANGER ROD 4" PHIL. PAN HEAD SEISMIC BRACE PLATE * CONTACT KINGSPAN TECHNICAL SERVICES FOR SEISMIC BRACE PLATE QUANTITY AND LOCATION FOUR TIGHT TURNS IN 112" SEISMIC BRACE PLATE CEILING CHANNEL KS SERIES - VERTICAL INSTALLATION ATTIC ABOVE CEILING MUST BE VENTILATED 3 INSULATE HANGER RODS AS REQUIRED (NOT BY KINGSPAN) HEX NUT AND LOCK WASHER 8" GALVANIZED HANGER ALL-THREAD ROD (SPACED NO GREATER THAN 6'-0" O.C.) (NOT BY KINGSPAN) 4" X 4" X 14 GA. PLATE WASHER* TRANSITION FLASHING 3 4" SELF-ADHERING VAPOR BARRIER (NOT BY KINGSPAN) PHIL. PAN HEAD INTERIOR FACE OF PANEL CEILING CEILING EXTERIOR SIDE OF PANEL MUST BE ON BOTTOM OF CEILING. PANEL CUTLIST MUST MATCH THIS ORIENTATION 3 3 1 2" BOLT WITH (3) " WASHERS AND (1) 8 LOCK-NUT PER BOLT 4" X 3" X 3 16" EXTRUDED ALUMINUM CEILING TEE (WHITE POWDER COAT FINISH) 3 8" ALL-THREAD HANGER ROD 8 3 3 FILL 12" GAP BETWEEN PANEL WITH F.I.P. INSULATION (NOT BY KINGSPAN) #8 GA. SPLAY BRACE WIRE IN FOUR DIRECTIONS (NOT BY KINGSPAN) 8 4" PHIL. PAN HEAD BUTYL SEALANT SEISMIC BRACE PLATE * CONTACT KINGSPAN TECHNICAL SERVICES FOR SEISMIC BRACE PLATE QUANTITY AND LOCATION FOUR TIGHT TURNS IN 112" SEISMIC BRACE PLATE CEILING TEE CEILING TEE ASSEMBLY I CE G LIN E TE EXTERIOR SIDE OF PANEL MUST BE ON BOTTOM OF CEILING. PANEL CUTLIST MUST MATCH THIS ORIENTATION INTERIOR FACE OF PANEL HEX NUT ROUND WSHR 4" X 4" X 14 GA. PLATE WASHER WIRE TIE ERECTOR MAY PRE-ASSEMBLE HARDWARE ON 3 8" HANGAR RODSWIRE TIES HOLD WASHERS ABOVE WORKING POINT PROJECT ENGINEER OF RECORD MUST VERIFY ROOF IS CAPABLE OF SUPPORTING CEILING SYSTEM LOADS AS WELL AS PROPER CEILING TO ROOF CONNECTION DETAILS LIC E T LA EP NG ILI CE TE E 3 4" PHIL. PAN HEAD LOCATE FIRST HANGER ROD AT LESS THAN 24" FROM FACE OF PANEL SEE DETAIL CS-CE-01-KSV FOR ADD'L INFO. OUTSIDE CORNER TRIM WITH 3 4" PHIL. PAN HEAD @ 12" OC. (SEALANT OR VAPOR SEAL TAPE AS REQUIRED) CEILING TEE SPLICE PLATE W/ (4) 3 8" X 112" BOLTS, NUTS, AND WASHERS SP SEISMIC BRACE PLATE (IF REQUIRED) TO BE LOCATED AT EVERY THIRD ROD LOCATION IN LIEU OF PLATE WASHER (SEE DETAIL CS-CE-04-KSV). CONTACT KINGSPAN TECHNICAL SERVICES FOR VERIFICATION. KS SERIES - VERTICAL INSTALLATION CEILING CHANNEL ASSEMBLY NUT 3 4" MA X. PHIL. PAN HEAD CEILING CHANNEL SPLICE PLATE 0" 2'- FIELD NOTCH END OF CHANNEL TO REST ON TOP OF WALL PANEL 9/16" DIA. HOLES PRE-PUNCHED FOR 3/8" OR ALL-THREAD ROD AT 5'-0" O/C (DO NOT SPACE ALL-THREAD RODS FURTHER THAN 60" APART. THE SPAN FROM WALL TO FIRST ROD, SHALL BE NO GREATER THAN 24".) INTERIOR FACE OF PANEL EXTERIOR SIDE OF PANEL MUST BE ON BOTTOM OF CEILING. PANEL CUTLIST MUST MATCH THIS ORIENTATION WIRE TIE 4" X 4" X 14 GA. PLATE WASHER ROUND WSHR ERECTOR MAY PRE-ASSEMBLE HARDWARE ON 3/8" HANGER RODSWIRE TIES HOLD WASHERS ABOVE WORKING POINT PROJECT ENGINEER OF RECORD MUST VERIFY ROOF IS CAPABLE OF SUPPORTING CEILING SYSTEM LOADS AS WELL AS PROPER CEILING TO ROOF CONNECTION DETAILS KS SERIES - VERTICAL INSTALLATION KS SERIES - VERTICAL INSTALLATION ATTIC ABOVE CEILING MUST BE VENTILATED 3 4" PHIL. PAN HEAD BUTYL SEALANT INSIDE CORNER TRIM FIELD CUT THERMAL BREAK F.I.P. INSULATION (NOT BY KINGSPAN) EXPANSION FASTENER CEILING CONTINUOUS BUTYL SEALANT AT "WARM" SIDE PANEL JOINT 3 4" PHIL. PAN HEAD SUPPORT ANGLE NOTE: CONTACT KINGSPAN TECHNICAL SERVICES FOR ENGINEERING ASSISTANCE CEILING TO WALL LONGITUDINAL KS SERIES - VERTICAL INSTALLATION ATTIC ABOVE CEILING MUST BE VENTILATED 3 8" GALVANIZED HANGER ALL-THREAD ROD (ROD SPACING TO BE DETERMINED) (NOT BY KINGSPAN) 3 4" PHIL. PAN HEAD BUTYL SEALANT INSIDE CORNER TRIM FIELD CUT THERMAL BREAK 1 4" MAX DISTANCE BETWEEN PANEL EDGE AND THREAD ROD F.I.P. INSULATION (NOT BY KINGSPAN) EXPANSION FASTENER CEILING 3 4" CONTINUOUS BUTYL SEALANT AT "WARM" SIDE PANEL JOINT PHIL. PAN HEAD 16 GA. SUPPORT ANGLE HEX NUT AND LOCK WASHER NOTE: CONTACT KINGSPAN TECHNICAL SERVICES FOR ENGINEERING ASSISTANCE CEILING TO WALL TRANSVERSE KS SERIES - VERTICAL INSTALLATION A EXPANSION FASTENERS AS REQUIRED COMPRESSIBLE INSULATION (NOT BY KINGSPAN) SUPPORT ANGLE (SET IN BUTYL SEALANT) #10 X 13 8" TEK 1 FASTENER AT EVERY PANEL JOINT A PARTITION TO ROOF (PERPENDICULAR TO PURLIN) FIELD FILL WITH INSULATION (NOT BY KINGSPAN) FIELD NOTCH PANELS AT PURLIN LOCATIONS KINGSPAN TO SUPPLY FLAT-STOCK SHEETING TO BE FIELD FORMED FOR PANEL CLOSURES COMPRESSIBLE INSULATION (NOT BY KINGSPAN) AA PURLIN CROSS SECTION (SECTION VIEW -- TYPICAL AT EACH PURLIN) PARTITION TO ROOF KS SERIES - VERTICAL INSTALLATION FILL VOIDS WITH FOAM BLOCK, SET IN BUTYL SEALANT 1/4"-14 STITCH TEKS AT EACH PURLIN PURLIN CLOSURE TRIM TO BE FIELD CUT TO FIT AT PURLIN FLANGES. USE SILICONE TO SEAL ALL EDGES WHEN COMPLETE. FIELD CUT PANELS AS REQUIRED 1/4"-14 STITCH TEKS AT EACH PURLIN ATTACH PURLIN CLOSURES W/ POP RIVETS SUPPORT ANGLE (SET IN BUTYL SEALANT) COMPRESSIBLE INSULATION (NOT BY KINGSPAN) #10 X 13 8" TEK 1 FASTENER AT EVERY PANEL JOINT PARTITION TO ROOF (WITH FOAM BLOCKING) (PERPENDICULAR TO PURLIN) FIELD CUT CONTINUOUS THERMAL BREAK (FREEZER ONLY) COMPRESSIBLE INSULATION (NOT BY KINGSPAN) EXPANSION FASTENERS AS REQUIRED SUPPORT ANGLE SET IN BUTYL SEALANT #10 X 13 8" TEK 1 FASTENER AT EVERY PANEL JOINT PARTITION TO ROOF (PARALLEL TO PURLIN) PARTITION TO ROOF WITH BLOCKING KS SERIES - VERTICAL INSTALLATION 3" P N. MI LA M I TR (2) BEADS BUTYL SEALANT 3" N. AP I L M IM TR TRIM END LAP KS SERIES - VERTICAL INSTALLATION FIELD NOTCH HEM(S) AS REQUIRED (NOT BY KINGSPAN) 3" N. AP I L M IM TR (2) BEADS BUTYL SEALANT 3" N. AP I L M IM TR TRIM LAP WITH HEM KS SERIES - VERTICAL INSTALLATION (2) BEADS BUTYL SEALANT 8" LONG LAP STRIP 1 " . 4 M NO AP G TRIM END LAP WITH LAP STRIP KS SERIES - VERTICAL INSTALLATION NOTE: DETAIL SHOWN IS FOR GENERAL USE ONLY (NOT FOR COOLER/FREEZER APPLICATIONS). FIELD NOTCH AND OVERLAP TRIMS, POP RIVET AND SEAL AS NECESSARY (NOT BY KINGSPAN) FIELD MITER AND OVERLAP TRIMS, POP RIVET AS NECESSARY (NOT BY KINGSPAN) SEALANT END DAM 2 INTERIOR HEAD TRIM WITH TABS BENT DOWN AD IM E TH A R PT CA D EA E NT I OR PT CA M RI H AT EXTERIOR CAP TRIM AT JAMB R O RI I ER T EX 5 EXTERIOR HEAD TRIM W/ FIELD DRILL 3 8 (NOT BY KINGSPAN) 1 INTERIOR JAMB TRIM 6 EXPOSED SEALANT (NOT BY KINGSPAN) 3 SILL TRIM WITH TABS BENT UP T EX R 4 EXTERIOR JAMB TRIM FIELD CUT/NOTCH CAP TRIM AT CORNERS TO ALLOW FOR LAP (NOT BY KINGSPAN) RI IO ER FIELD CUT/NOTCH CAP TRIM AT CORNERS TO ALLOW FOR LAP (NOT BY KINGSPAN) T AP M L SIL T A C TRIM LAP AT FRAMED OPENING FIELD MITER AND OVERLAP TRIMS, POP RIVET AND SEAL AS NECESSARY (NOT BY KINGSPAN) TRIM INSTALLATION SEQUENCE: 1 INTERIOR JAMB TRIM 2 INTERIOR HEAD TRIM WITH TABS DOWN 3 SILL TRIM WITH TABS UP 4 EXTERIOR JAMB TRIM 5 EXTERIOR HEAD TRIM 6 EXTERIOR SEALANTS AS REQUIRED