Joussard School
Transcription
Joussard School
RECAPP Facility Evaluation Report High Prairie School Div #48 Joussard School B3611A Joussard Report run on: May 11, 2006 6:55 AM Joussard - Joussard School (B3611A) Facility Details Building Name: Joussard School Address: P. O. Box 60 Location: Joussard Building Id: B3611A 0.00 $2,306,265 Construction Year: 0 Evaluation Details Evaluation Company: Burgess Bredo Architect Evaluation Date: June 2 2005 Evaluator Name: Mr. Burgess Bredo Gross Area (sq. m): Replacement Cost: Total Maintenance Events Next 5 years: 5 year Facility Condition Index (FCI): $112,885 4.89% General Summary: Original 204.0 sq m single story school with pitched wood roof trusses, wood framed walls, and concrete foundations constructed in 1954. Similar additions with pitched wood roof trusses and concrete foundations were constructed in 1958 (239.0 sq m) and 1960 (90.0 sq m). Concrete block and steel roof assembly addition of 482.0 sq m was added in 1972. Two small wood framed additions (total area 107.8 sq m) were added in 1985. One portable of 100.0 sq m was added in 1994, while another portable of 120.0 sq m complete with link was added in 2004. Modernizations have taken place in 1985 and 1987. Current gross area of the school is 1335.8 sq m and student capacity is 150. The building is in fair condition. Structural Summary: Concrete foundation system of grade beams and spread footings. Roof and suspended floor assemblies are wood framed and bear on masonry walls and wood framed walls. There is a concern with the condition of the concrete foundation in 1972 phase. Otherwise the sturcture is in good condition. Envelope Summary: Exterior walls are clad with stucco, concrete block, metal siding, fascia and trim. windows are double glazed aluminum, doors are hollow metal set in pressed steel frames. 1972 roof has been replaced with SBS system. 1954, 1958, and 1960 phase have asphalt shingles on pitched wood trusses. Asphalt shingles should be replaced. Single wythe concrete block exterior walls are a concern warranting further study. Building envelope is in fair condition. Interior Summary: Partitions are a combination of concrete block and wood studs/ gypsum board. Ceiling finished include gypsum board and acoustic tile in T-bar. Flooring finishes include vinyl tile, epoxy flooring, carpet and hardwood. Carpet requires replacement. Solid core wood doors and hollow metal doors. Code issues are limited to Barrier Free Access. Interior is in good condition in the 1954, 1958, 1960, and 1987 sections. 1972 section requires flooring, ceilings, and millwork to be replaced. Interior walls to be patched, repaired and refinished. Barrier free entrance required. Size of gym as noted by staff is too small. Building interior is in fair condition. Mechanical Summary: In 1985 two classrooms were added and the 1954 original building, 1958 addition, 1960 addition were modernized. Classrooms and support areas heated by perimeter radiation. Heating system consists of two (2) copper tube heating boilers, two in line circulation pumps, distribution piping to heating elements in modernization area, 1972 addition, 1994 and 2004 portables. Ventilation provided by one (1) built up air system. Supply air distribution is low velocity with Report run on: May 11, 2006 6:55 AM Page 2 of 31 Joussard - Joussard School (B3611A) ducted return air. In 1999 the 1972 addition was upgraded mechanically. Perimeter radiation was installed, existing rooftop units removed and replaced with air system located within ceiling space. Supply air distribution is low velocity with ceiling return air. Exhaust fans expel foul odors. Plumbing fixtures and brass are commercial quality. Fire protection consists of fire extinguishers. Items found during review which should be addressed are: - Computer room and server room cooling. - Provide corridor return air plenum to eliminate usage of ceiling space containing combustibles. Mechanical systems and components are fair to good condition. Electrical Summary: 120/240V/1PH overhead power service to building. Fluorescent lighting in building with T8 lamps and electronic ballasts. Simplex fire alarm system needs upgrading. ADT security system needs upgrading. Additional receptacle outlets required to classrooms. DC emergency lighting system needs upgrading. Electrical installation generally appears in good condition. Condition Rating 1 - Critical 2 - Poor 3 - Marginal 4 - Acceptable 5 - Good 6 - Excellent Rating Guide Performance Unsafe, high risk of injury or critical system failure. Does not meet requirements, has significant deficiencies. May have high operating/maintenance costs. Meets minimum requirements, has significant deficiencies. May have above average operating maintenance costs. Meets present requirements, minor deficiencies. Average operating/maintenance costs. Meets all present requirements. No deficiencies. As new/state of the art, meets present and foreseeable requirements. Report run on: May 11, 2006 6:55 AM Page 3 of 31 Joussard - Joussard School (B3611A) S1 STRUCTURAL A1010 Standard Foundations*1954,1958, 1960 phases Perimeter and interior grade beams bearing on concrete spread footings Rating Installed Design Life Updated 5 - Good 0 100 JUN-05 A1010 Standard Foundations*1972 Concrete grade beams and spread footings. Rating Installed Design Life Updated 3 - Marginal Event: 0 100 JUN-05 Study concrete foundation. Concern: Concrete is spalling noticably in areas Recommendation: Study concrete foundation in 1972 phase Type Year Cost Priority Study 2006 $5,350 Medium Updated: November 2 2005 A1030 Slab on Grade*1972 Concrete slab on grade throughout Rating 5 - Good Installed Design Life Updated 0 100 JUN-05 A2020 Basement Walls (& Crawl Space)*1954, 1958, 1960 phases Concrete grade beams at exterior perimeter of crawl space. Rating 5 - Good Installed Design Life Updated 0 0 JUN-05 B1010.01 Floor Structural Frame*(Building Frame) 1954, 1958, 1960 phases Wood framed suspended floor assembly over crawl space. Rating 5 - Good Installed Design Life Updated 0 100 JUN-05 B1010.07 Exterior Stairs** Cast in place concrete stairs at north and west entrances. Rating 5 - Good Installed Design Life Updated 0 Report run on: May 11, 2006 6:55 AM 40 JUN-05 Page 4 of 31 Joussard - Joussard School (B3611A) B1020.01 Roof Structural Frame* Wood framed roof assembly bearing on concrete block partitions Rating 5 - Good Installed Design Life Updated 0 100 JUN-05 B1020.01 Roof Structural Frame*1954, 1958, 1960 phases Pitched wood roof trusses. Rating 4 - Acceptable Installed Design Life Updated 0 Report run on: May 11, 2006 6:55 AM 100 JUN-05 Page 5 of 31 Joussard - Joussard School (B3611A) S2 ENVELOPE B2010.01.06.03 Metal Siding**1954. 1958, 1960, 1985 phases Prefinished corrugated metal cladding added to lower portions of exterior walls in 1987 modernization. Rating Installed Design Life Updated 5 - Good 0 40 JUN-05 B2010.01.08 Cement Plaster (Stucco): Ext. Wall* 1954, 1958, 1960 phases Stucco added to upper portions of exterior walls in 1987 modernization. Rating Installed Design Life Updated 5 - Good 0 75 JUN-05 B2010.01.09 Expansion Control: Exterior Wall Skin* Control joints in concrete block and at joints between dissimilar materials. Rating Installed Design Life Updated 4 - Acceptable 0 75 JUN-05 B2010.01.11 Joint Sealers (caulking): Ext. Wall** Caulking in control joints in concrete block and at joints between dissimilar materials. Rating Installed Design Life Updated 4 - Acceptable 0 15 JUN-05 B2010.01.13 Paints (& Stains): Exterior Wall** 1972 Concrete block walls are painted. Rating Installed Design Life Updated 4 - Acceptable 0 15 JUN-05 B2010.02.03 Masonry Units: Ext. Wall Const.* 1972 Single wythe concrete block exterior walls. Rating Installed Design Life Updated 3 - Marginal Event: 0 100 JUN-05 Study flaking paint on concrete block. Concern: Concrete block paint reported to be flaking as a recurring problem. Recommendation: Undertake study to determine best means of correction mointure migration prior to remedial action. Type Year Cost Priority Study 2007 $1,070 Low Updated: November 2 2005 Report run on: May 11, 2006 6:55 AM Page 6 of 31 Joussard - Joussard School (B3611A) B2010.02.05 Wood Framing*: Ext. Wall Const. 1954, 1958, 1960, 1985 phases Wood framed exterior walls. Rating Installed Design Life Updated 4 - Acceptable 0 100 JUN-05 B2010.03 Exterior Wall Vapor Retarders, Air Barriers, and Insulation* Insulation within wood framed walls. Rating Installed Design Life Updated 5 - Good 0 20 JUN-05 B2010.06 Exterior Louvers, Grilles, and Screens* Painted metal louvres throughout. Rating Installed Design Life Updated 4 - Acceptable 0 20 JUN-05 B2010.09 Exterior Soffits* Prefinished vented aluminum soffit panels. Rating Installed Design Life Updated 5 - Good 0 20 JUN-05 B2020.01.01.02 Aluminum Windows (Glass & Frame)** 1972 Clear anodized aluminum framed windows with double field glazed units. Insulated aluminum panel at base of unit serves as hopper vent. Rating Installed Design Life Updated 3 - Marginal Event: 0 35 JUN-05 Replace aluminum windows. Concern: Windows reported to be draughty and leak under wind driven conditions. Some condensation and frosting during winter. Recommendation: Replace aluminum windows with aluminum curtain wall type throughout (24.0 sq m). Type Year Cost Priority Failure Replacement 2007 $12,840 Low Updated: November 2 2005 B2020.01.01.06 Vinyl, Fibreglass &Plastic Windows** 1954, 1958, 1960 phases Original windows replaced with vinyl framed double glazed units with hopper vent at bottom during 1987 modernization. Rating 4 - Acceptable Installed Design Life Updated 0 Report run on: May 11, 2006 6:55 AM 35 JUN-05 Page 7 of 31 Joussard - Joussard School (B3611A) B2030.01 Exterior Entrance Doors Insulated hollow metal doors with and without glazing set in pressed steel frames Rating Installed Design Life Updated 5 - Good 0 30 JUN-05 B2030.01.02 Steel-Framed Storefronts** Hollow metal storefront complete with double glazed sidelites introduced during 1987 modernization. Rating Installed Design Life Updated 5 - Good 0 15 JUN-05 B2030.05 Other Exterior Doors** Insulated hollow metal doors set in pressed frames. Rating Installed Design Life Updated 5 - Good 0 20 JUN-05 B3010.02.01.01 Asphalt Shingles** 1954, 1958, 1960 phases Asphalt shingles on pitched roof replaced in 1987. Rating Installed Design Life Updated 3 - Marginal Event: 0 25 JUN-05 Replace asphalt shingles. Concern: Shingles have been problematic, requiring a number of repairs due to vandalism. Recommendation: Replace asphalt shingles with SBS roof membrane (720.0 sq m). Type Year Cost Priority Failure Replacement 2007 $48,150 Low Updated: November 2 2005 B3010.04.04 Modified Bituminous Membrane Roofing (SBS)** 1972 SBS roof membrane replaced original BUR in 1998. Rating 5 - Good Installed Design Life Updated 0 25 JUN-05 B3010.08.02 Metal Gutters and Downspouts** Prefinished metal eavestroughs and downspouts spill on to concrete splashpads. Rating 4 - Acceptable Installed Design Life Updated 0 Report run on: May 11, 2006 6:55 AM 25 JUN-05 Page 8 of 31 Joussard - Joussard School (B3611A) B3010.09 Roof Specialties and Accessories Metal ship's ladder from mechanical mezzanine to roof. Rating 5 - Good Installed Design Life Updated 0 25 JUN-05 B3020.02 Other Roofing Openings (Hatch,Vent, etc)* Roof hatch in 1972 phase accessed by fixed steel ladder in staff washroom. Rating 5 - Good Installed Design Life Updated 0 Report run on: May 11, 2006 6:55 AM 0 JUN-05 Page 9 of 31 Joussard - Joussard School (B3611A) S3 INTERIOR C1010.01 Interior Fixed Partitions* Concrete block and metal stud partitions throughout. Rating Installed Design Life Updated 4 - Acceptable 0 50 JUN-05 C1010.03 Interior Operable Folding Panel Partitions** 1972 Folding panel partition between two classrooms appears to be kept closed all the time. Rating Installed Design Life Updated 4 - Acceptable 0 30 JUN-05 C1010.05 Interior Windows* Wired glass set in wood frames. Rating Installed Design Life Updated 4 - Acceptable 0 40 JUN-05 C1020.01 Interior Swinging Doors** Solid core wood doors set in pressed steel and wood frames throughout. Rating Installed Design Life Updated 3 - Marginal Event: 0 50 JUN-05 Replace door hardware Concern: Hardware is a variety of makes and styles; many have round knobs where lever design required for Barrier Free Access. Recommendation: Replace door knob hardware (24 doors) Type Year Barrier Free Access Upgrade 2008 Cost Priority $8,025 Low Updated: November 2 2005 Report run on: May 11, 2006 6:55 AM Page 10 of 31 Joussard - Joussard School (B3611A) C1020.03 Interior Fire Doors* 1954, 1958, 1960 phases Solid core wood set in pressed steel frames. Rating Installed Design Life Updated 3 - Marginal Event: 0 50 JUN-05 Replace interior fire doors. Concern: A number of fire doors lack closers and labels and do not comply to current codes. Many of the doors are damaged and are in need of replacement. Hardware is a variety of makes and styles and is in poor condition. Recommendation: Replace doors, frames, and hardware (3 doors). Type Year Cost Priority Code Upgrade 2006 $4,815 Medium Updated: November 2 2005 C1020.03 Interior Fire Doors* 1972 Solid core wood doors set in wood frames and hollow metal frames Rating 4 - Acceptable Installed Design Life Updated 0 50 JUN-05 C1020.05.01 Coiling Doors and Grilles Coiling door overhead counter pass throughs from kitchen Rating 5 - Good Installed Design Life Updated 0 0 JUN-05 C1030.01 Visual Display Boards** Whiteboards and tackboards throughout. Rating 4 - Acceptable Installed Design Life Updated 0 10 JUN-05 C1030.02 Fabricated Compartments(Toilets/Showers)** Floor supported metal toilet partitions. Rating 4 - Acceptable Installed Design Life Updated 0 20 JUN-05 C1030.06 Handrails* Metal handrails at wheelchgair ramp. Rating 5 - Good Installed Design Life Updated 0 Report run on: May 11, 2006 6:55 AM 50 JUN-05 Page 11 of 31 Joussard - Joussard School (B3611A) C1030.08 Interior Identifying Devices* Room numbers painted on walls adjacent doors. Rating Installed Design Life Updated 4 - Acceptable 0 10 JUN-05 C1030.10 Lockers** Metal lockers located in coridors throughout. Rating Installed Design Life Updated 4 - Acceptable 0 30 JUN-05 C1030.12 Storage Shelving* Clear finish plywood shelving throughout. Rating Installed Design Life Updated 5 - Good 0 20 JUN-05 C1030.14 Toilet, Bath, and Laundry Accessories* Commercial grade mirrors, soap dispensers, paper towel dispensers, and toilet tissue holders in all washrooms. Rating Installed Design Life Updated 4 - Acceptable 0 20 JUN-05 C2010 Stair Construction* Cast in place concrete steps at grade change in corridor between 1954 and 1972 phases. Rating Installed Design Life Updated 5 - Good 0 100 JUN-05 C2020.05 Resilient Stair Finishes** Vinyl tile and rubber nosings on corridor steps. Rating Installed Design Life Updated 4 - Acceptable 0 20 JUN-05 C2020.08 Stair Railings and Balustrades* Metal railings at corridor steps. Rating Installed Design Life Updated 5 - Good 0 50 JUN-05 C3010.04 Gypsum Board Wall Finishes* Gypsum board at wood stud framed partitions throughout. Rating Installed Design Life Updated 4 - Acceptable 0 40 JUN-05 C3010.06 Tile Wall Finishes** Ceramic wall tile wainscot in washrooms. Rating 5 - Good Installed Design Life Updated 0 Report run on: May 11, 2006 6:55 AM 50 JUN-05 Page 12 of 31 Joussard - Joussard School (B3611A) C3010.09 Acoustical Wall Treatment** Upper 1200 mm of walls in gym finished with fabric wrapped acoustic panels. Rating Installed Design Life Updated 5 - Good 0 20 JUN-05 C3010.11 Interior Wall Painting** All gypsum board and bulk of concrete block wall surfaces are painted. Rating Installed Design Life Updated 4 - Acceptable 0 5 JUN-05 C3020.01 Concrete Floor Finishes (Paint)* Painted concrete floor finishes in selected service rooms. Rating Installed Design Life Updated 4 - Acceptable 0 75 JUN-05 C3020.04 Wood Flooring** Sprung hardwood flooring in gym added in 1999. Rating Installed Design Life Updated 5 - Good 0 25 JUN-05 C3020.07 Resilient Flooring** 1954, 1958, 1960 phases Vinyl tile in corridors and most classrooms replaced in 1987. Rating Installed Design Life Updated 5 - Good 0 20 JUN-05 C3020.07 Resilient Flooring** 1972 phase Vinyl tile in corridors and most classrooms including below hardwood flooring in gym. Rating Installed Design Life Updated 4 - Acceptable 0 20 JUN-05 C3020.08 Carpet Flooring** Carpet in library, offices and part of one classroom. Rating Installed Design Life Updated 3 - Marginal Event: 0 10 JUN-05 Replace carpet. Concern: Carpet is worn and stained in a number of areas Recommendation: Replace carpet in nselected areas with carpet or sheet vinyl (225 .0 sq m). Type Year Cost Priority Failure Replacement 2008 $17,655 Low Updated: November 2 2005 Report run on: May 11, 2006 6:55 AM Page 13 of 31 Joussard - Joussard School (B3611A) C3020.14 Other Floor Finishes** Epoxy floor finishes in washrooms. Rating 5 - Good Installed Design Life Updated 0 0 JUN-05 C3030.04 Gypsum Board Ceiling Finishes* Gypsum board ceilings in washrooms, kitchen, storage rooms, and service rooms. Rating 4 - Acceptable Installed Design Life Updated 0 50 JUN-05 C3030.06 Acoustic Ceiling Treatment (Susp.T-Bar)** Suspended T-bar grid system with acoustic tiles in corridors, classrooms and offices. Rating 5 - Good Installed Design Life Updated 0 25 JUN-05 C3030.07 Interior Ceiling Painting** Gypsum board ceilings are painted. Rating 4 - Acceptable Installed Design Life Updated 0 10 JUN-05 C3030.09 Other Ceiling Finishes* Exposed clear finish wood decking at gym ceiling. Rating 4 - Acceptable Installed Design Life Updated 0 Report run on: May 11, 2006 6:55 AM 10 JUN-05 Page 14 of 31 Joussard - Joussard School (B3611A) S4 MECHANICAL D2010.01 Water Closets** Floor mounted, open front seat, flush tank. Rating 5 - Good Installed Design Life Updated 0 30 JUN-05 D2010.02 Urinals** Wall hung, flush valve. Rating 5 - Good Installed Design Life Updated 0 30 JUN-05 D2010.03 Lavatories** Stainless steel bowls. On/off brass. Wall hung in staff area on/off brass. Rating 5 - Good Installed Design Life Updated 0 30 JUN-05 D2010.04 Sinks** Stainless steel counter sinks with swing spout. Rating 5 - Good Installed Design Life Updated 0 30 JUN-05 D2010.08 Drinking Fountains / Coolers** Wall hung, porcelain, non refrigerated. Rating 5 - Good Installed Design Life Updated 0 30 JUN-05 D2010.09 Other Plumbing Fixtures** Three compartment sink with heat element in kitchen. Rating 5 - Good Installed Design Life Updated 0 0 JUN-05 D2020.01.01 Pipes and Tubes: Domestic Water* Copper piping and fittings. Rating 5 - Good Installed Design Life Updated 0 40 JUN-05 D2020.01.03 Piping Specialties (Backflow Preventors)** Backflow preventer installed on heating system make up water line. Rating 5 - Good Installed Design Life Updated 0 30 JUN-05 D2020.02.02 Plumbing Pumps: Domestic Water** Inline domestic hot water recirculation pump, Grundfoss UP-15-425:, .03 kw motor. Rating 5 - Good Installed Design Life Updated 0 Report run on: May 11, 2006 6:55 AM 20 JUN-05 Page 15 of 31 Joussard - Joussard School (B3611A) D2020.02.06 Domestic Water Heaters** A.O. Smith cyclone hot water heater, 125,000 BTU/hr input. Plastic chimney. Approximately two (2) years old. Rating Installed Design Life Updated 6 - Excellent 0 20 JUN-05 D2020.03 Water Supply Insulation*: Domestic Domestic hot, cold recirculation piping insulated. Rating Installed Design Life Updated 5 - Good 0 30 JUN-05 D2030.01 Waste and Vent Piping* Cat iron, copper. Rating Installed Design Life Updated 5 - Good 0 50 JUN-05 D2030.02 Waste Piping Specialties* Grease interceptor installed in kitchen. Rating Installed Design Life Updated 5 - Good 0 50 JUN-05 D2040.01 Rain Water Drainage Piping Systems* Rainwater leaders from roof hoppers and eave troughs discharge to grade. Rating Installed Design Life Updated 5 - Good 0 50 JUN-05 D2040.02.04 Roof Drains** Cast iron domes, full flow. Rating Installed Design Life Updated 5 - Good 0 40 JUN-05 D3010.02 Gas Supply Systems* Gas distribution piping to heating boilers, domestic hot water heater, kitchen make up unit, kitchen range. Rating 5 - Good Installed Design Life Updated 0 50 JUN-05 D3020.02.01 Heating Boilers and Accessories: H.W.** Copper tube boilers, Raypak 824-WTD, 348 kw input. Complete with low water cut off, relief valve, flow switch. Rating 4 - Acceptable Installed Design Life Updated 0 30 JUN-05 D3020.02.02 Chimneys (&Comb. Air): H.W. Boiler** Class B chimney. Insulated combustion air. Rating 5 - Good Installed Design Life Updated 0 Report run on: May 11, 2006 6:55 AM 30 JUN-05 Page 16 of 31 Joussard - Joussard School (B3611A) D3020.02.03 Water Treatment: H. W. Boiler* Sidestream filter and chemical pot feeder. Rating Installed Design Life Updated 5 - Good 0 30 JUN-05 D3020.05 Auxiliary Equipment: Heat Generation* Air cushion horizontal expansion tank. Rating Installed Design Life Updated 5 - Good 0 30 JUN-05 D3040.01.01 Air Handling Units: Air Distribution** Crawl space ventilation system installed in boiler room. Field fabricated unit complete with supply fan, return fan, motorized fresh, return, exhaust dampers, filter bank, heating coil. Indirect fired make up air unit for kitchen, complete with supply fan, stainless steel heat exchanger, gas burner, motorized fresh air damper, throw away filter, 850 l/s supply air, 300,000 BTU/hr input. Rating Installed Design Life Updated 5 - Good 0 30 JUN-05 D3040.01.01 Air Handling Units: Air Distribution**-1985 Classroom air system installed in boiler room field fabricated. Unit complete with supply fan, return fan, motorized fresh, return, exhaust dampers, filter bank. Coil complete with two way valve and pumped. Air system 1315 l/s supply air, 895 l/s return air. Rating Installed Design Life Updated 4 - Acceptable 0 30 JUN-05 D3040.01.01 Air Handling Units: Air Distribution**-1999 Installed in 1972 addition ceiling space. Field fabricated unit complete with supply fan, return fan, motorized fresh, return exhaust dampers, filter bank. Capacity of equipment not known. Access to equipment poor. Unit serves gymnasium, classrooms and administration area. Motorized dampers installed in branch line ducts to divert air into gymnasium during high occupancy. Ceiling space used as return air plenum which has wood deck and plastic rainwater piping installed. Rating Installed Design Life Updated 3 - Marginal Event: 0 30 JUN-05 Utilize corridor as return air plenum. Concern: Ceiling space used as return air plenum has a wood deck and plastic rainwater leader installed within ceiling space. Recommendation: Utilize corridor as return air plenum. ceiling grilles. Install ductwork and Type Year Cost Priority Code Upgrade 2006 $19,260 Medium Updated: November 2 2005 Report run on: May 11, 2006 6:55 AM Page 17 of 31 Joussard - Joussard School (B3611A) D3040.01.02 Fans: Air Distribution* Circulation fans with guard installed in gymnasium. Rating Installed Design Life Updated 5 - Good 0 30 JUN-05 D3040.01.03 Air Cleaning Devices:Air Distribution* Air systems filter section complete with 50 mm throw away filters. Rating Installed Design Life Updated 4 - Acceptable 0 30 JUN-05 D3040.01.04 Ducts: Air Distribution* Low velocity supply air ductwork. Rating Installed Design Life Updated 5 - Good 0 50 JUN-05 D3040.01.07 Air Outlets & Inlets:Air Distribution* Outlets vary as to type. Square diffusers, linear grilles, adjustable double deflected, egg crate return air. Rating Installed Design Life Updated 5 - Good 0 30 JUN-05 D3040.03.01 Hot Water Distribution Systems** Two inline circulation pumps, Grundfoss UPS 60, 1.119 kw motor, circulate hot water via black iron piping to radiation, unit heaters entrance heating. Rating Installed Design Life Updated 5 - Good 0 40 JUN-05 D3040.04.01 Fans: Exhaust** Indoor, centrifugal. Residential ceiling exhaust fans. Rating Installed Design Life Updated 5 - Good 0 30 JUN-05 D3040.04.03 Ducts: Exhaust* Low velocity ductwork to exhaust air outlets and fans. Rating 5 - Good Installed Design Life Updated 0 0 JUN-05 D3040.04.05 Air Outlets and Inlets: Exhaust* Egg crate exhaust air grilles. Rating 5 - Good Installed Design Life Updated 0 Report run on: May 11, 2006 6:55 AM 0 JUN-05 Page 18 of 31 Joussard - Joussard School (B3611A) D3050.01.01 Computer Room Air Conditioning Units** Computer room and server room temperature excessive. Rating Installed Design Life Updated 3 - Marginal Event: 0 30 JUN-05 Install air conditioning. Concern: Computer and server room temperatures excessive. Recommendation: Install air conditioning for computer room and server room. Type Year Operating Efficiency Upgrade 2006 Cost Priority $48,150 High Updated: November 2 2005 D3050.05.02 Fan Coil Units** Ceiling and wall mounted fan coil units installed in main and secondary entrances. Rating 5 - Good Installed Design Life Updated 0 30 JUN-05 D3050.05.03 Finned Tube Radiation** Wall fin radiation. Rating 5 - Good Installed Design Life Updated 0 40 JUN-05 D3050.05.06 Unit Heaters** Vertical unit heater in mechanical room. Rating 5 - Good Installed Design Life Updated 0 30 JUN-05 D3060.02.01 Electric and Electronic Controls** Electric thermostat cycles fan coil motors to maintain set point. Rating 5 - Good Installed Design Life Updated 0 30 JUN-05 D3060.02.02 Pneumatic Controls** Air compressor, refrigerated air dryer, pneumatic dampers, control valves. Rating 4 - Acceptable Installed Design Life Updated 0 40 JUN-05 D3060.02.03 Pneumatic and Electric Controls Transducers to integrate pneumatic components with BMCS. Rating 5 - Good Installed Design Life Updated 0 Report run on: May 11, 2006 6:55 AM 40 JUN-05 Page 19 of 31 Joussard - Joussard School (B3611A) D3060.02.05 Building Systems Controls(BMCS, EMCS)** Multinet BMCS. System controls equipment activation and assists in maintaining building environment. Installed in 1999. Limiting thermostats installed in classrooms and offices. Rating 5 - Good Installed Design Life Updated 0 30 JUN-05 D4030.01 Fire Extinguisher, Cabinets and Accessories** Water pump tank and ABC fire extinguishers installed on wall brackets and in fire extinguisher cabinets. Rating 5 - Good Installed Design Life Updated 0 30 JUN-05 D4090 Other Fire Protection Systems* Kitchen range hood complete with dry chemical fire suppression system. Rating 5 - Good Installed Design Life Updated 0 Report run on: May 11, 2006 6:55 AM 0 JUN-05 Page 20 of 31 Joussard - Joussard School (B3611A) S5 ELECTRICAL D5010.03 Main Electrical Switchboards (Main Distribution)** Built-up main power distribution system comprising of 300 ampere main circuit breaker, CT cabinet, and CDP distribution panelboard. Rating Installed Design Life Updated 4 - Acceptable 0 40 JUN-05 D5010.05 Electrical Branch Circuit Panelboards (Secondary Distribution)** Branch circuit panels located throughout school. Rating Installed Design Life Updated 4 - Acceptable 0 25 JUN-05 D5010.07 Motor Control Centers (Motor Control)** Square D combination motor and manual motor starters. Rating Installed Design Life Updated 4 - Acceptable 0 30 JUN-05 D5020.01 Electrical Branch Wiring* Ivory devices with stainless steel coverplates. Wiring installed in conduit. Rating Installed Design Life Updated 3 - Marginal Event: 0 50 JUN-05 Add receptacles to classroom. Concern: Insufficient receptacle outlets in classrooms to provide service to computers in classrooms. Recommendation: Provide at least two dedicated power outlets per classroom. Costs based on 20 new receptacles. Type Year Program Functional Upgrade 2007 Cost Priority $16,050 High Updated: November 2 2005 D5020.02.01 Lighting Accessories (Lighting Controls)* Interior light fixtures controlled by light switches installed in each room. Rating 4 - Acceptable Installed Design Life Updated 0 30 JUN-05 D5020.02.02.02 Interior Florescent Fixtures** Mixture of surface and recess mounted light fixtures upgraded to T8 lamps with electronic ballasts in 2003. Rating 4 - Acceptable Installed Design Life Updated 0 Report run on: May 11, 2006 6:55 AM 30 JUN-05 Page 21 of 31 Joussard - Joussard School (B3611A) D5020.02.03 Emergency Lighting* DC battery pack type emergengy lighting with remote heads and exit signs. Rating Installed Design Life Updated 3 - Marginal Event: 0 0 JUN-05 Replace emergency lighting system. Concern: Battery pack units, remote heads, and exit signs are old and in poor shape. Also, several corridors require additional exit signs and remote heads to comply with code. Recommendation: Replace emergency lighing system with new system along with added exit signs and remote heads where required to comply with code. Type Year Cost Priority Failure Replacement 2007 $8,560 Medium Updated: November 2 2005 D5020.03.01.04 Exterior H.P. Sodium Fixtures* Wall mounted high pressure sodium light fixtures installed along perimeter of building. Also some soffit mounted light fixtures installed at building entrances. Rating 4 - Acceptable Installed Design Life Updated 0 25 JUN-05 D5020.03.02 Lighting Accessories (Lighting Controls)* Exterior lighting appears to be photocell controlled. Rating 4 - Acceptable Installed Design Life Updated 0 Report run on: May 11, 2006 6:55 AM 25 JUN-05 Page 22 of 31 Joussard - Joussard School (B3611A) D5030.01 Detection and Fire Alarm** Simplex 2001 fire alarm control panel installed in General Office. Installation includes fire alarm bells with no strobe lights, fire pull stations and heat detectors. Rating Installed Design Life Updated 3 - Marginal Event: 0 25 JUN-05 Replace fire alarm control panel. Concern: Existing fire alarm control panel is old, repair parts no longer available, and existing panel is in poor shape. Also, a remote annunciator does not exist at school main front entrance as required to comply with code. Recommendation: Replace fire alarm system control panel and provide remote annunciator at school front entrance. Type Year Cost Priority Failure Replacement 2006 $10,700 High Updated: November 2 2005 D5030.02.02 Intrusion Detection** ADT Focus security system with motion sensors and door contacts. Rating Installed Design Life Updated 3 - Marginal Event: 0 25 JUN-05 Replace security system control panel. Concern: Secuity sytstem control panel is very old and in poor shape. Recommendation: Replace security system control panel with new. Type Year Cost Priority Failure Replacement 2007 $6,420 Medium Updated: November 2 2005 D5030.03 Clock and Program Systems** Battery operated clocks in classrooms. Rating 4 - Acceptable Installed Design Life Updated 0 25 JUN-05 D5030.04.01 Telephone Systems** Basic telephone system integrated with school call system. Rating 4 - Acceptable Installed Design Life Updated 0 Report run on: May 11, 2006 6:55 AM 25 JUN-05 Page 23 of 31 Joussard - Joussard School (B3611A) D5030.04.03 Call Systems** Bogen multi-com intercom system integrated with school telephone system. classroom, and appears to have been installed in 2002. Rating Installation has a telephone in each Installed Design Life Updated 4 - Acceptable 0 25 JUN-05 D5030.04.04 Data Systems** Cat. 5 data cabling in approximately 3 data outlets installed in each classroom with wiring installed to dedicated hub and server located in closet by computer room. Rating Installed Design Life Updated 4 - Acceptable 0 25 JUN-05 D5030.06 Television Systems* Tower with TV antenna and cable distribution service to each classroom. Rating 4 - Acceptable Installed Design Life Updated 0 Report run on: May 11, 2006 6:55 AM 20 JUN-05 Page 24 of 31 Joussard - Joussard School (B3611A) S6 EQUIPMENT, FURNISHINGS AND SPECIAL CONSTRUCTION E1090 Other Equipment Television sets in most classrooms. Rating Installed Design Life Updated 5 - Good 0 0 JUN-05 E1090.03 Food Service Equipment* Commercial food service equipment located in kitchen adjacent lunch room. Rating Installed Design Life Updated 4 - Acceptable 0 25 JUN-05 E1090.04 Residential Equipment* Residential grade microwave and under counter refrigerator in staff lounge. Rating Installed Design Life Updated 5 - Good 0 25 JUN-05 E1090.07 Athletic, Recreational, and Therapeutic Equipment* Two plywood wall mouted basketball backboards and wall climbing equipment in gym. Rating Installed Design Life Updated 5 - Good 0 15 JUN-05 E2010.02.05 Educational Facility Casework* Clear finish plywood with plastic laminate countertops. Rating Installed Design Life Updated 5 - Good 0 35 JUN-05 E2010.02.07 Kitchen Casework* Painted plywood casework with plastic laminate clad countertop located in kitchen. Rating Installed Design Life Updated 3 - Marginal Event: 0 35 JUN-05 Replace kitchen millwork. Concern: Countertops anmd casework are damaged. Recommendation: Replace kitchen millwork (12 m) with plastic laminate clad casework and stainless steel countertops. Type Year Cost Priority Failure Replacement 2006 $8,560 Low Updated: November 2 2005 Report run on: May 11, 2006 6:55 AM Page 25 of 31 Joussard - Joussard School (B3611A) E2010.02.09 Library Casework* Clear finish plywood shelving in library. Rating Installed Design Life Updated 4 - Acceptable 0 35 JUN-05 E2010.02.99 Other Casework* Plastic laminate clad vanities in washrooms. Clear finish casework with plastic laminate countertops in office reception area. Display cases with tempered glass sliding doors. Rating Installed Design Life Updated 4 - Acceptable 0 0 JUN-05 E2010.03.01 Blinds** Metal horizontal blinds at most windows. Rating Installed Design Life Updated 5 - Good 0 35 JUN-05 E2020 Moveable Furnishings* Wide variety of educational and office furnishings including desks, tables, bookshelves, and chairs. Rating 5 - Good Installed Design Life Updated 0 0 JUN-05 F1010.02.04 Portable and Mobile Buildings* Wood framed storage shed located on north side of school; solid core wood door, asphalt shingles, vinyl cladding on exterior walls. No mechanical or electrical services. Rating 4 - Acceptable Installed Design Life Updated 0 Report run on: May 11, 2006 6:55 AM 0 JUN-05 Page 26 of 31 Joussard - Joussard School (B3611A) F1010.02.04 Portable and Mobile Buildings* 1994 Portable added in 1994 at south central portion of school. Architectural: Wood framed wall, roof and floor construction. Envelope includes metal cladding and stucco on wood framed walls. Twp ply SBS roof membrane, double glazed windows. Interior components include vinyl tile in classroom, storage, and mechanical; solid core wood doors, pressed steel frames, painted gypsum board walls, acoustic tile ceiling, clear finish millwork, lockers, and whiteboards/tackboards. Mechanical:Van EE heat recovery ventilator with supply, fresh air, exhaust connections. Provides ventilation air in addition to sidewall supply and return air from 1999 air system upgrade. Perimeter radiation. Storage room has no ventilation. Crawl space supply fan provides supply air into crawl space during summer months. Open flow roof drain to grade. Electrical: Recess mounted fluorescentlight fixtures with wraparound lens, T8 lamps, and electronic ballasts. Basic electrical installation with combined telephone/intercom handset to classroom ceiling mounted intercom speaker and ivory devices with stainless steel cover plates. Rating Installed Design Life Updated 3 - Marginal Event: 0 0 JUN-05 Replace interior fire doors. Concern: Doors to mechanical and storage rooms lack labels and closers. Recommendation: Replace fire doors with new doors and add closers (2 doors). Type Year Cost Priority Code Upgrade 2006 $3,210 Low Updated: November 2 2005 Event: Replace locksets Concern: Doors to classroom, ctorage and mechanical rooms have round knobs where code requires levers. Recommendation: Replace locksets on doors (3 doors). Type Year Cost Priority Barrier Free Access Upgrade 2008 $963 Low Updated: November 2 2005 Event: Test air quality Concern: Indoor Air Quality is poor. Recommendation: Conduct air quality testing during upcoming heating season to determine if acceptable carbon dioxide levels are met during occupancy and at design winter conditions. Type Year Cost Priority Study 2006 $3,210 Medium Report run on: May 11, 2006 6:55 AM Page 27 of 31 Joussard - Joussard School (B3611A) Updated: November 2 2005 F1010.02.04 Portable and Mobile Buildings* 2004 Portable added in 1994 at south central portion of school. Architectural: Wood framed wall, roof and floor construction. Envelope includes metal cladding and stucco on wood framed walls. Twp ply SBS roof membrane, double glazed windows. Interior components include vinyl tile in classroom, storage, and mechanical; solid core wood doors, pressed steel frames, painted gypsum board walls, acoustic tile ceiling, clear finish millwork, lockers, and whiteboards/tackboards. Mechanical: Energy savings fan coil unit rated at 475 l/s. Unit complete with supply fan, heating coil, 25 mm throwaway filter, ceiling space used as return air plenum, insulated fresh air duct with no motorized or manual damper. Low velocity supply air ductwork to square diffusers connected to BMCS. Ceiling space used as return air plenum which is wood construction and is a code violation. Heating piping not insulated. Radiant ceiling panels installed along building perimeter. Hot water ceiling force flo in entrance. Open flow roof drain to grade. Electrical: Recess mounted fluorescentlight fixtures with wraparound lens, T8 lamps, and electronic ballasts. Basic electrical installation with combined telephone/intercom handset to classroom ceiling mounted intercom speaker and ivory devices with stainless steel cover plates. Rating Installed Design Life Updated 6 - Excellent Event: 0 0 JUN-05 Provide ducted return air. Concern: Ceiling space used as return air plenum has a wood deck. Recommendation: Install ductwork and ceiling grilles and connect to air system. Type Year Cost Priority Code Upgrade 2006 $8,560 High Updated: November 2 2005 F1010.02.04 Portable and Mobile Buildings* Northeast Link Link to portable added in 1994 at south central portion of school. Architectural: Concrete block walls with wood framed roof and floor construction. Exterior finishes are metal cladding and concrete block. Two ply SBS roof membrane, glazed entrance. Interior components include porcelain tile, solid core wood doors, pressed steel frames, acoustic tile ceiling and metal boot racks. Electrical: Recess mounted fluorescentlight fixtures with wraparound lens, T8 lamps, and electronic ballasts. Rating 4 - Acceptable Installed Design Life Updated 0 0 JUN-05 F2020.01 Asbestos* Hazmat survey by PHH Environmental dated March 30, 2002 has determined that asbestos in present in vinyl floor tiles of 1972 phase. report recommends no further action until renovation or demolition work is undertaken. Rating 4 - Acceptable Installed Design Life Updated 0 Report run on: May 11, 2006 6:55 AM 0 JUN-05 Page 28 of 31 Joussard - Joussard School (B3611A) F2020.02 PCBs* Hazmat survey by PHH Environmental dated March 30, 2002 has determined that PCBs are likely not present. Rating 5 - Good Installed Design Life Updated 0 0 JUN-05 F2020.04 Mould* Hazmat survey by PHH Environmental dated March 30, 2002 has noted a strong odour in one classroom and water stained ceiling tiles. Rating 4 - Acceptable Installed Design Life Updated 0 Report run on: May 11, 2006 6:55 AM 0 JUN-05 Page 29 of 31 Joussard - Joussard School (B3611A) S8 FUNCTIONAL ASSESSMENT K3020 Indoor Environment Gym is too short to accomodate basketball court and could cause injuries. Confusion over main entrance and proximity of administration offices. Rating Installed Design Life Updated 4 - Acceptable 0 0 JUN-05 K40 Current Code Issues 1994 portable located within recess of permanent construction. Narrow space between portable and school has been provided with uninsulated roof. Floor and walls form staorage room. 2004 portable has been placed adjacent permanent construction in northeast corner. Rating Installed Design Life Updated 3 - Marginal Event: 0 0 JUN-05 Study portable locations. Concern: Portables located too close to permanent construction. fire separation required around storage rooms. Recommendation: Undertake study to review locations of portables and compliance to current codes. Type Year Cost Priority Study 2006 $4,280 Medium Updated: November 2 2005 K4010.01 Barrier Free Route: Parking to Entrance Designated parking provided in south parking lot adjacent maintenance. Rating Installed Design Life Updated 3 - Marginal Event: 0 0 JUN-05 Add ramp at main entrance. Concern: Concrete steps at main entry present barrier to wheel chairs. Recommendation: Add ramp at main entrance. Type Year Barrier Free Access Upgrade 2006 Cost Priority $10,700 Low Updated: November 2 2005 Report run on: May 11, 2006 6:55 AM Page 30 of 31 Joussard - Joussard School (B3611A) K4010.02 Barrier Free Entrances Main entrance has two concrete steps adjacent. Rating Installed Design Life Updated 3 - Marginal Event: 0 0 JUN-05 Provide power assisted door operators Concern: No power assisted door operators at main entrance Recommendation: Provide power assisted door operators (2 doors). Type Year Cost Priority $6,420 Low Barrier Free Access Upgrade 2006 Updated: November 2 2005 K4010.03 Barrier Free Interior Circulation Ramp provided at grade change in corridor. Good access to all portions of the school. Rating Installed Design Life Updated 5 - Good 0 0 JUN-05 K4010.04 Barrier Free Washrooms Washrooms have acceptable cubicles and grab bars. Rating Installed Design Life Updated 3 - Marginal Event: 0 0 JUN-05 Upgrade washroom vanities. Concern: Height of vanities is within acceptable limits but clearances below do not comply to current codes. Recommendation: Upgrade washroom vanities to comply to current codes. Type Year Barrier Free Access Upgrade 2006 Cost Priority $1,070 Low Updated: November 2 2005 Report run on: May 11, 2006 6:55 AM Page 31 of 31 RECAPP Facility Evaluation Report Joussard School S3611 Joussard Report run on: May 11, 2006 7:00 AM Joussard - Joussard School (S3611) Facility Details Building Name: Joussard School Address: Location: Joussard Building Id: S3611 0.00 $0 Construction Year: 0 Evaluation Details Evaluation Company: Evaluation Date: Evaluator Name: Gross Area (sq. m): Replacement Cost: Total Maintenance Events Next 5 years: 5 year Facility Condition Index (FCI): $1,070 0% General Summary: Overall site size and playing fields are adequate. Site is bound by village recreation fields, hockey rink, residential areas, open fields, and the highway on its eastern edge. Prominent site problems include por drainage, unsafe bus drop off along the highway, and lack of exterior signage. Site systems are in fair to poor condition. Structural Summary: Envelope Summary: Interior Summary: Mechanical Summary: Electrical Summary: Condition Rating 1 - Critical 2 - Poor 3 - Marginal 4 - Acceptable 5 - Good 6 - Excellent Rating Guide Performance Unsafe, high risk of injury or critical system failure. Does not meet requirements, has significant deficiencies. May have high operating/maintenance costs. Meets minimum requirements, has significant deficiencies. May have above average operating maintenance costs. Meets present requirements, minor deficiencies. Average operating/maintenance costs. Meets all present requirements. No deficiencies. As new/state of the art, meets present and foreseeable requirements. Report run on: May 11, 2006 7:00 AM Page 2 of 7 Joussard - Joussard School (S3611) S7 SITE G2010.02.01 Aggregate Roadway (Gravel)** Gravel raodway on north side of school. Rating Installed Design Life Updated 2 - Poor Event: 0 0 Add bus drop off. Concern: Location of bus drop off along highway is a significant safety concern. Recommendation: Add bus drop off on north side of school property. Type Year Program Functional Upgrade 2006 Cost Priority $133,750 High Updated: November 2 2005 G2020.02.01 Aggregate Parking Lots (Gravel)** Gravel parking area for visitors on north side of school. Rating Installed Design Life Updated 4 - Acceptable 0 0 G2020.02.02 Flexible Paving Parking Lots(Asphalt)** Asphalt paved parking lot for staff on south side of school. Rating Installed Design Life Updated 5 - Good 0 0 G2020.06.02 Parking Bumpers* Precast concrete bumpers in parking lot. Rating 5 - Good Installed Design Life Updated 0 0 G2020.06.03 Parking Lot Signs* Wood and metal signage on metal posts Rating 5 - Good Installed Design Life Updated 0 Report run on: May 11, 2006 7:00 AM 0 Page 3 of 7 Joussard - Joussard School (S3611) G2020.06.04 Pavement Markings* No pavement markings in parking lot. Rating Installed Design Life Updated 3 - Marginal Event: 0 0 Add pavement markings Concern: No pavement markings provided. Recommendation: Add pavement markings complete with BFA parking stall. Type Year Cost Priority Failure Replacement 2009 $1,070 Low Updated: November 2 2005 G2030.03 Pedestrian Unit Pavers** Unit pavers adjacent main entrance and east portable entrance. Rating Installed Design Life Updated 4 - Acceptable 0 0 G2030.04 Rigid Pedestrian Pavement (Concrete)** Concrete sidewalks between parking lot and entrances. Rating Installed Design Life Updated 5 - Good 0 0 G2030.06 Exterior Steps and Ramps* Cast in place concrete steps at all entrances. Rating Installed Design Life Updated 5 - Good 0 0 G2040.02 Fences and Gates** Chain link fencing around playground. Rating 5 - Good Installed Design Life Updated 0 Report run on: May 11, 2006 7:00 AM 0 Page 4 of 7 Joussard - Joussard School (S3611) G2040.03 Athletic and Recreational Surfaces** concrete pad with two basketball hoops, rough grasses throughout. Rating Installed Design Life Updated 3 - Marginal Event: 0 0 Drain low spot in playing feild. Concern: Large low spot in middle of playing feilds render feilds unplayable until late May. Recommendation: Drain low spot in playing feilds by introducing french drains or leach pit with man hole to permit pumping out during rainy periods. Type Year Program Functional Upgrade 2006 Cost Priority $21,400 Low Updated: November 2 2005 G2040.05 Site and Street Furnishings* Wood and steel benches adjacent playground. Rating Installed Design Life Updated 4 - Acceptable 0 0 G2040.06 Exterior Signs* No exterior signage provided. Rating Installed Design Life Updated 3 - Marginal Event: 0 0 Add exterior signage. Concern: No exterior signage on site or building Recommendation: Add illuminated exterior signage to site and building. Type Year Program Functional Upgrade 2006 Cost Priority $5,350 Low Updated: November 2 2005 Report run on: May 11, 2006 7:00 AM Page 5 of 7 Joussard - Joussard School (S3611) G2040.08 Flagpoles* No flagpoles on site. Rating Installed Design Life Updated 3 - Marginal Event: 0 0 Provide flagpoles. Concern: No flagpoles have been provided. Recommendation: Add two flagpoles. Type Year Program Functional Upgrade 2009 Cost Priority $2,675 Low Updated: November 2 2005 G2050.04 Lawns and Grasses* Rough grasses throughout. Rating 4 - Acceptable Installed Design Life Updated 0 0 G2050.05 Trees, Plants and Ground Covers* Mature trees around perimeter of site. Rating 5 - Good Installed Design Life Updated 0 0 G3010.02 Site Domestic Water Distribution* Domestic water connected to Town main. Rating 5 - Good Installed Design Life Updated 0 0 G3010.03 Site Fire Protection Water Distribution* Fire hydrant within 45 meters of front entrance. Rating 5 - Good Installed Design Life Updated 0 0 G3020.01 Sanitary Sewage Collection* Sanitary sewer line connected to Town main. Rating 5 - Good Installed Design Life Updated 0 0 G3030.01 Storm Water Collection* Building drainage to grade. Rating 5 - Good Installed Design Life Updated 0 Report run on: May 11, 2006 7:00 AM 0 Page 6 of 7 Joussard - Joussard School (S3611) G3060.01 Gas Distribution* Natural gas line to exterior meter. Rating Installed Design Life Updated 5 - Good 0 0 G4010.02 Electrical Power Distribution Lines* 120/240V/1PH overhead power service from north side of building. Rating Installed Design Life Updated 4 - Acceptable 0 0 G4010.03 Electrical Power Distribution Equipment* Weatherproof enclosure containing panel for service to parking outlets. Installed in 2003. Rating Installed Design Life Updated 4 - Acceptable 0 0 G4010.04 Car Plugs-ins* 14 energized parking stalls comprising of duplex weatherproof receptacle outlets installed on wood rails and connected to exterior parking panel. Install completed in 2003. Rating Installed Design Life Updated 5 - Good 0 0 G4030.02 Site Voice and Data* Underground telephone service from Telus. Rating 4 - Acceptable Installed Design Life Updated 0 Report run on: May 11, 2006 7:00 AM 0 Page 7 of 7
Similar documents
Newbrook School B3827A - Alberta Infrastructure
1 - Critical 2 - Poor 3 - Marginal 4 - Acceptable 5 - Good 6 - Excellent
More information